Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 09:03:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 37076.79 | 800.44 | 800.44 |
Net Site Energy | 37076.79 | 800.44 | 800.44 |
Total Source Energy | 99016.99 | 2137.66 | 2137.66 |
Net Source Energy | 99016.99 | 2137.66 | 2137.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 7893.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2589.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 897.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2461.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 310.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 554.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.21 |
Humidification | 228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.04 |
Heat Recovery | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 942.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28240.88 | 8835.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3504.42 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 7893.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2589.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 897.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2461.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 310.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 554.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.21 |
Humidification | General | 228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.04 |
Heat Recovery | General | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 942.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 7893.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2589.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 897.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2461.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 310.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 554.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.21 |
Humidification | Unassigned | 228.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.04 |
Heat Recovery | Unassigned | 44.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 942.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.67 | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 609.69 | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.67 | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 609.69 | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28240.879 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28240.879 | 100.00 |
Total On-Site and Utility Electric Sources | 28240.879 | 100.00 |
Total Electricity End Uses | 28240.879 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2.52 | 0.04 |
Air to Air Heat Recovery for Heating | 6493.14 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6495.66 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3504.42 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3504.42 | 100.00 |
Total Water End Uses | 3504.42 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 255.67 |
Time Setpoint Not Met During Occupied Cooling | 67.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5930.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.1390 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.1390 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1390 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.1390 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.1390 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.1390 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.1390 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8180 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-AUG-15:39 | 27-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 20-JUL-14:50 |
Heating | 0.00 | 3841258.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 360971.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 86589.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271883.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62306.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64336.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4264.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33846.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1988589.75 | 3875105.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3841258.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 360971.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 271883.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 62306.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 64336.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4264.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33846.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 8556.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8201.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2843.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6326.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7796.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 984.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1755.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 724.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 140.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1021.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 89438.86 | 9578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 184.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 37.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 15.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1930.88 | 206.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 184.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 37.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 15.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1930.88 | 206.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.73 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.513224 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.93 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.497241 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.74 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.06 | 0.314058 | 0.300000 | 1.82 | 0.837487 | 0.500000 | 0.001213 | 0.000264 | 1.82 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.05 | 0.333394 | 0.300000 | 17.12 | 0.889051 | 0.500000 | 0.001143 | 0.004412 | 17.12 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.60 | 0.339719 | 0.300000 | 1.68 | 0.905917 | 0.500000 | 0.001122 | 0.001055 | 3.65 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.971557 | 0.245812 | 0.300000 | 0.291467 | 0.655499 | 0.500000 | 0.001550 | 0.000182 | 0.631041 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.26 | 0.122279 | 0.300000 | 0.377592 | 0.326077 | 0.500000 | 0.003116 | 0.000125 | 0.433051 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.93 | 0.123943 | 0.300000 | 0.578070 | 0.330515 | 0.500000 | 0.003074 | 0.000196 | 0.680086 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.49 | 0.103553 | 0.300000 | 0.445872 | 0.300000 | 0.500000 | 0.003679 | 0.000110 | 0.445872 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.93 | 0.267446 | 0.300000 | 2.68 | 0.713188 | 0.500000 | 0.001425 | 0.002386 | 8.27 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.25 | 0.116174 | 0.300000 | 3.97 | 0.309797 | 0.500000 | 0.003280 | 0.001583 | 5.48 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 20.17 | 0.118394 | 0.300000 | 6.05 | 0.315719 | 0.500000 | 0.003218 | 0.002371 | 8.21 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.50 | 0.114009 | 0.300000 | 4.05 | 0.304023 | 0.500000 | 0.003342 | 0.001520 | 5.26 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.12 | 0.212617 | 0.300000 | 0.336972 | 0.566979 | 0.500000 | 0.001792 | 0.000324 | 1.12 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.32 | 0.116717 | 0.300000 | 0.395585 | 0.311246 | 0.500000 | 0.003264 | 0.000214 | 0.740531 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.09 | 0.114277 | 0.300000 | 0.626963 | 0.304740 | 0.500000 | 0.003334 | 0.000322 | 1.12 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.40 | 0.110106 | 0.300000 | 0.419335 | 0.300000 | 0.500000 | 0.003460 | 0.000210 | 0.726739 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 30181.27 | 0.000264 | 651.96 |
CORE_MID VAV BOX REHEAT COIL | 504293.33 | 0.004412 | 12682.41 |
CORE_TOP VAV BOX REHEAT COIL | 120587.92 | 0.001055 | 3182.02 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20833.58 | 0.000182 | 549.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14295.06 | 0.000125 | 377.03 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22449.41 | 0.000196 | 592.09 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12525.03 | 0.000110 | 309.46 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 272765.95 | 0.002386 | 7192.83 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 180956.04 | 0.001583 | 4771.70 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 271050.32 | 0.002371 | 7147.62 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 173723.64 | 0.001520 | 4581.12 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 37048.14 | 0.000324 | 976.77 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24424.45 | 0.000214 | 643.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36819.49 | 0.000322 | 970.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23969.97 | 0.000210 | 631.96 |
VAV_BOT WITH REHEAT HEATING COIL | 174483.31 | 0.001526 | 2303.85 |
VAV_MID WITH REHEAT HEATING COIL | 1802938.97 | 0.015773 | 23052.73 |
VAV_TOP WITH REHEAT HEATING COIL | 190614.86 | 0.001668 | 2437.24 |
CAV_BAS HEATING COIL | 332722.40 | 0.002911 | 6874.66 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.85 | 3.51 | 11.70 | 3.51 | 9.88 | 9.88 | 0.300000 | 0.355146 | 9.88 |
VAV_MID WITH REHEAT | 56.45 | 33.87 | 112.90 | 41.60 | 92.23 | 92.23 | 0.300000 | 0.451013 | 92.23 |
VAV_TOP WITH REHEAT | 5.76 | 3.46 | 11.53 | 7.36 | 9.75 | 9.75 | 0.300000 | 0.754355 | 9.75 |
CAV_BAS | 5.73 | 5.73 | 5.73 | 5.73 | 5.73 | 5.73 | 1.00 | 1.00 | 5.73 |
AIRLOOP DATACENTER BASEMENT | 21.74 | 21.74 | 21.74 | 21.74 | 21.74 | 21.74 | 1.00 | 0.999995 | 21.74 |
AIRLOOP DATACENTER BOT | 0.513224 | 0.513224 | 0.513224 | 0.513224 | 0.513224 | 0.513224 | 1.00 | 1.00 | 0.513224 |
AIRLOOP DATACENTER MID | 4.93 | 4.93 | 4.93 | 4.93 | 4.93 | 4.93 | 1.00 | 1.00 | 4.93 |
AIRLOOP DATACENTER TOP | 0.497241 | 0.497241 | 0.497241 | 0.497241 | 0.497241 | 0.497241 | 1.00 | 1.00 | 0.497241 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.88 | 2.72 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.23 | 28.45 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.75 | 2.96 |
CAV_BAS_OA_CONTROLLER | 5.73 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.74 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.513224 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.93 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.497241 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.95 | 6.67 | 10.92 | 0.007236 | 0.007000 | 174332.54 | 0.007417 | 9.88 |
VAV_MID WITH REHEAT COOLING COIL | 25.08 | 6.67 | 10.91 | 0.007241 | 0.007000 | 1644304.47 | 0.069953 | 92.23 |
VAV_TOP WITH REHEAT COOLING COIL | 25.03 | 6.67 | 10.92 | 0.007227 | 0.007000 | 172765.96 | 0.007350 | 9.75 |
CAV_BAS COOLING COIL | 24.48 | 6.67 | 11.27 | 0.007372 | 0.007000 | 97699.81 | 0.004156 | 5.73 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.88 |
VAV_MID WITH REHEAT FAN | 92.23 |
VAV_TOP WITH REHEAT FAN | 9.75 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007417 | 0.000064 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001526 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.069953 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.015773 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007350 | 0.000065 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001668 | |
CAV_BAS_COOLC_CONTROLLER | 0.004156 | 0.000115 |
CAV_BAS_HEATC_CONTROLLER | 0.002911 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 28.45 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.96 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.73 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.74 | 443573.66 | 281154.70 | 0.010863 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.513224 | 10184.73 | 6527.77 | 0.000249 |
AIRLOOP DATACENTER MID COOLING COIL | 4.93 | 97757.63 | 62649.59 | 0.002394 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.497241 | 9868.48 | 6324.51 | 0.000242 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.74 | 21.74 | 21.74 | 21.74 | 443573.66 | 443573.66 | 33013.32 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.513224 | 0.513224 | 0.513224 | 0.513224 | 10184.73 | 10184.73 | 1525.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.93 | 4.93 | 4.93 | 4.93 | 97757.63 | 97757.63 | 15250.79 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.497241 | 0.497241 | 0.497241 | 0.497241 | 9868.48 | 9868.48 | 1525.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.74 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.513224 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.93 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.497241 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.74 | 443573.66 | 0.010863 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.513224 | 10184.73 | 0.000249 |
AIRLOOP DATACENTER MID HEATING COIL | 4.93 | 97757.63 | 0.002394 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.497241 | 9868.48 | 0.000242 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 33013.32 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1525.08 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 15250.79 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1525.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000197 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.088875 | 18313.90 | |
HEATSYS1 PUMP | 0.037152 | 11188.50 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.088875 | 10.67 |
HEATSYS1 | 0.037152 | 4.46 |
COOLSYS1_SUPPLY | 0.088875 | 10.67 |
SINGLE WATER PLANT LOOP | 0.013748 | 1.65 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.088875 | 0.088875 | 373054.07 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 4246683.13 | 4246683.13 | 0.037152 |
CENTRAL BOILER | 566310.88 | 555349.99 | 0.013748 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.088875 | 12679.33 |
PLANT CIRC PUMP | 0.013748 | 3506.50 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.088875 | 0.044712 | 1053584.82 | 1058581.80 | 0.052586 |
COOLSYS1 CHILLER2 | 0.088875 | 0.044712 | 1053584.82 | 1058581.80 | 0.052586 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013748 | 139666.47 | 57582.79 | 69833.23 | 7879.72 | 21243.36 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.105171 | 12.62 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.105171 | 31675.22 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 43.28 | 1257570.15 | 8.66 | 157196.27 |
TOWERWATERSYS COOLTOWER 2 | 43.28 | 1257570.15 | 8.66 | 157196.27 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.054413 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.139 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.981 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.139 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.562 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25401.240 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25401.240 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7162.063 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7162.063 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.002 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9296 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.327 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8307 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9084 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5862 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.33543647E-15 | 0.37175517E-16 | -0.14631797E-09 | 0.12118624E-17 |
51 | 8 | 0.21396566E-07 | 0.13443687E-12 | 0.37275451E-03 | -0.24328632E-09 |
52 | 7 | -0.12091173E-01 | 0.70158236E-08 | -0.22869277E-01 | 0.13748104E-03 |
53 | 6 | 0.40126415 | 0.24497036E-05 | 0.46860994 | -0.46995957E-02 |
54 | 5 | -5.1506864 | 0.91758480E-04 | -4.4145205 | 0.62689390E-01 |
55 | 4 | 32.826465 | 0.75276522E-03 | 21.335811 | -0.41978091 |
56 | 3 | -110.85094 | 0.16448005E-02 | -55.417368 | 1.5097726 |
57 | 2 | 196.75927 | 0.92731797E-03 | 77.685319 | -2.8948114 |
58 | 1 | -171.02718 | 0.99203986E-04 | -55.199609 | 2.7431803 |
59 | 0 | 57.057407 | 0.56605462E-06 | 15.567773 | |
60 | 9 | -0.28960779E-14 | 0.35098193E-16 | -0.14971922E-09 | 0.47215659E-16 |
61 | 8 | 0.21874741E-07 | 0.12520865E-12 | 0.37779602E-03 | -0.24872334E-09 |
62 | 7 | -0.12241669E-01 | 0.65002252E-08 | -0.23085984E-01 | 0.13919224E-03 |
63 | 6 | 0.40535349 | 0.22649272E-05 | 0.47209413 | -0.47477991E-02 |
64 | 5 | -5.1905946 | 0.84684606E-04 | -4.4412874 | 0.63184232E-01 |
65 | 4 | 33.002996 | 0.69360465E-03 | 21.440451 | -0.42212474 |
66 | 3 | -111.22654 | 0.15133424E-02 | -55.624249 | 1.5151992 |
67 | 2 | 197.13156 | 0.85210513E-03 | 77.875032 | -2.9007233 |
68 | 1 | -171.16470 | 0.91049108E-04 | -55.254723 | 2.7455905 |
69 | 0 | 57.057407 | 0.51888301E-06 | 15.558627 | |
70 | 9 | 0.91129428E-15 | 0.43215878E-16 | -0.13089627E-09 | -0.20490080E-17 |
71 | 8 | 0.19220221E-07 | 0.17438783E-12 | 0.34930596E-03 | -0.21854054E-09 |
72 | 7 | -0.11389480E-01 | 0.93361245E-08 | -0.21858301E-01 | 0.12950253E-03 |
73 | 6 | 0.38219501 | 0.32933165E-05 | 0.45231959 | -0.44748175E-02 |
74 | 5 | -4.9645592 | 0.12444350E-03 | -4.2891815 | 0.60381528E-01 |
75 | 4 | 32.002960 | 0.10289719E-02 | 20.845393 | -0.40884736 |
76 | 3 | -109.09821 | 0.22640533E-02 | -54.447585 | 1.4844515 |
77 | 2 | 195.02141 | 0.12843697E-02 | 76.796791 | -2.8672153 |
78 | 1 | -170.38497 | 0.13818870E-03 | -54.942931 | 2.7319248 |
79 | 0 | 57.057407 | 0.79338380E-06 | 15.611548 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78071.46708 | 78071.46708 | 5.72577 | 5.72577 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -41.90000 | 6.45023E-005 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82582.64438 | 82582.64438 | 6.05635 | 6.05635 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 12171.71979 | 12171.71979 | 0.52031 | 1.07782 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 778122.46694 | 778122.46694 | 57.05093 | 57.05093 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 334643.07043 | 334643.07043 | 14.36900 | 14.36900 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76367.21057 | 76367.21057 | 5.59888 | 5.59888 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 84416.72780 | 84416.72780 | 3.64915 | 3.64915 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13128.25891 | 13128.25891 | 0.97156 | 0.97156 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14579.08646 | 14579.08646 | 0.63104 | 0.63104 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17007.68508 | 17007.68508 | 1.25864 | 1.25864 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.99871E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 10002.89642 | 10002.89642 | 0.43305 | 0.43305 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 26037.68277 | 26037.68277 | 1.92690 | 1.92690 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15708.74082 | 15708.74082 | 0.68009 | 0.68009 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20083.21517 | 20083.21517 | 1.48624 | 1.48624 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 8106.01622 | 8106.01622 | 0.35067 | 0.35067 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 120663.57522 | 120663.57522 | 8.92969 | 8.92969 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 21.22900 | 6.99788E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 190839.55490 | 190839.55490 | 8.26630 | 8.26630 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 179014.51056 | 179014.51056 | 13.24781 | 13.24781 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 126602.55877 | 126602.55877 | 5.48422 | 5.48422 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 272579.64197 | 272579.64197 | 20.17204 | 20.17204 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 189640.17244 | 189640.17244 | 8.21422 | 8.21422 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 182414.30175 | 182414.30175 | 13.49941 | 13.49941 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 121546.11285 | 121546.11285 | 5.26470 | 5.26470 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12428.96507 | 12428.96507 | 0.91980 | 0.91980 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 25915.73297 | 25915.73297 | 1.12324 | 1.12324 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 17818.15765 | 17818.15765 | 1.31862 | 1.31862 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17085.08181 | 17085.08181 | 0.74053 | 0.74053 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 28240.01432 | 28240.01432 | 2.08988 | 2.08988 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 25755.88013 | 25755.88013 | 1.11630 | 1.11630 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18887.93975 | 18887.93975 | 1.39778 | 1.39778 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16767.30697 | 16767.30697 | 0.72674 | 0.72674 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8792.53064 | 8792.53064 | 0.51322 | 0.51322 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84384.80450 | 84384.80450 | 4.92560 | 4.92560 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 21.99400 | 6.99901E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8518.67631 | 8518.67631 | 0.49724 | 0.49724 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 21.99400 | 6.99901E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372440.57291 | 372440.57291 | 21.73930 | 21.73930 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.11800 | 6.99333E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | -41.90000 | 6.45023E-005 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 140896.37 | 9.88300 | 9.88300 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 176905.61 | 3.17267 | 3.17267 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1309984.88 | 92.23339 | 92.23339 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1847822.30 | 41.59845 | 41.59845 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 141664.18 | 9.75133 | 9.75133 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 192627.82 | 7.35597 | 7.35597 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
7 | CAV_BAS | Cooling | Sensible | 71998.53 | 5.72577 | 5.72577 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 117086.28 | 1.20016 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367356.34 | 21.73940 | 21.73940 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 33013.32 | 0.33839 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8586.97 | 0.51322 | 0.51322 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82375.65 | 4.92560 | 4.92560 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 15250.79 | 0.15632 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8316.74 | 0.49724 | 0.49724 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.72577 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.05635 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31406 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81691 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83749 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21315E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64039E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81691 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30181.26644 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64039E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 651.95787 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.05093 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33339 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 17.11528 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88905 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14279E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.41178E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 17.11528 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 504293.32767 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41178E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12682.40955 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.59888 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33972 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.67966 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90592 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12152E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05496E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.64915 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120587.91882 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05496E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3182.01973 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97156 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24581 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29147 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65550 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54996E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82261E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63104 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20833.58449 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82261E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 549.51247 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25864 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12228 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37759 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32608 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11583E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25059E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43305 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14295.05707 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25059E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 377.02694 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92690 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12394 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.57807 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33051 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07399E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96397E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68009 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22449.41369 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96397E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 592.09134 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48624 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10355 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44587 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67927E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09574E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44587 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12525.03172 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09574E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 309.45714 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.92969 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26745 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.67891 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71319 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42459E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38628E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.26630 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 272765.94526 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38628E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7192.82817 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.24781 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11617 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.97434 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30980 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27956E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58308E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.48422 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 180956.04420 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58308E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4771.69958 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 20.17204 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11839 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.05161 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31572 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21805E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37127E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.21422 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 271050.32103 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37127E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7147.62243 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.49941 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11401 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.04982 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30402 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34185E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51981E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.26470 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 173723.64455 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51981E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4581.11645 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12324 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21262 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33697 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56698 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79195E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.24113E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12324 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37048.13843 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24113E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 976.76736 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31862 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11672 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39558 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31125 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26430E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13676E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74053 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24424.44777 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13676E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 643.93797 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08988 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11428 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.62696 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30474 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33399E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22113E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11630 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36819.48809 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22113E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 970.74243 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39778 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11011 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41934 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46029E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09700E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72674 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23969.96536 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09700E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 631.96074 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51322 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.92560 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49724 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.73930 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.84985 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.50991 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.69969 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.50991 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.88300 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.88300 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35515 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 56.44994 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.86996 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 112.89988 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 41.59845 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.23339 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.23339 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45101 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.76420 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.45852 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.52840 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.35597 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.75133 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.75133 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.75436 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.72577 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.72577 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.72577 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.72577 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.72577 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.72577 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.73930 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.73930 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.73930 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.73930 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.73940 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.73940 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51322 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51322 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51322 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51322 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51322 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51322 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.92560 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.92560 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.92560 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.92560 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.92560 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.92560 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49724 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49724 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49724 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49724 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49724 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49724 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.88300 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.23339 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.75133 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.72577 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.73940 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51322 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.92560 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49724 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.88300 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.71525 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.94724 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91817 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23583E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 174332.54051 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.41651E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.88300 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 174483.30930 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52646E-003 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2303.84702 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.88300 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.41651E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.42068E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.52646E-003 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.23339 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 28.44599 |
307 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 28.44599 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.07910 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90814 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24137E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1644304.46617 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.99525E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.23339 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1802938.97162 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57729E-002 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 23052.72930 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.23339 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.99525E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.80734E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.57729E-002 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.75133 |
324 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.96008 |
325 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.96008 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.03456 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91814 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.22659E-003 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 172765.95959 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.34986E-003 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.75133 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 190614.86053 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66758E-003 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2437.23878 |
337 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.75133 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.34986E-003 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.47890E-005 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.66758E-003 |
341 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.72577 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.47999 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.26860 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.37178E-003 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 97699.81310 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.15638E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.72577 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 332722.39663 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.91080E-003 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6874.65525 |
354 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.72577 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.15638E-003 |
356 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.14569E-004 |
357 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.91080E-003 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.73940 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.73940 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 443573.65656 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 281154.69596 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08631E-002 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.73940 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.73940 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.73940 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.73940 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 443573.65656 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 443573.65656 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 33013.32304 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
372 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.73940 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.73940 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 443573.65656 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08631E-002 |
376 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 33013.32304 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.97498E-004 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51322 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51322 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10184.73475 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6527.77234 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49423E-004 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51322 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51322 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51322 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51322 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10184.73475 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10184.73475 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
395 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51322 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51322 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10184.73475 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49423E-004 |
399 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.92560 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.92560 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 97757.63007 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 62649.58751 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39408E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.92560 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.92560 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.92560 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.92560 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 97757.63007 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 97757.63007 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 15250.78758 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.92560 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.92560 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 97757.63007 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.39408E-003 |
418 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 15250.78758 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49724 |
420 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49724 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9868.48397 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6324.51238 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41679E-004 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49724 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49724 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49724 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49724 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9868.48397 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9868.48397 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
433 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49724 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49724 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9868.48397 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41679E-004 |
437 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.88753E-002 |
439 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18313.89739 |
440 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.88753E-002 |
441 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.66503 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.88753E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.88753E-002 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 373054.06775 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
446 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.71518E-002 |
447 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 4.45822 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.71518E-002 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 11188.50167 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 4246683.13265 |
452 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 4246683.13000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.71518E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.88753E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.66503 |
456 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.88753E-002 |
457 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12679.32893 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.88753E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.47121E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1053584.82149 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1058581.80500 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.25855E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.88753E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.47121E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1053584.82149 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1058581.80500 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.25855E-002 |
468 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.37483E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.64979 |
470 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.37483E-002 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3506.49647 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.37483E-002 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57582.79269 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21243.35929 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 566310.87606 |
479 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 555349.99000 |
480 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37483E-002 |
481 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
482 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
483 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
485 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
486 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10517 |
487 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.62052 |
488 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10517 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31675.21635 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 43.28377 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1257570.14574 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.65675 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 157196.26822 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 43.28377 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1257570.14574 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.65675 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 157196.26822 |
498 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.44125E-002 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.44125E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 28606.94 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 477613.82 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 114263.79 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19739.41 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13544.13 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21270.10 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11863.30 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 258428.79 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 171443.91 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 256803.58 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 164592.57 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35099.53 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23139.75 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34882.93 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22709.20 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 96758.23 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 957476.72 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 101228.77 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 241323.84 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 260963.45 | 178957.30 | 82006.16 | 0.69 | 36758.56 | 372.83 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2445694.35 | 1674455.84 | 771238.51 | 0.68 | 343592.45 | 3484.91 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 257838.07 | 176715.14 | 81122.93 | 0.69 | 36243.02 | 367.60 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 147217.68 | 101862.92 | 45354.76 | 0.69 | 20216.50 | 205.05 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.002 | 0.871 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.930 | 0.816 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.327 | 1.107 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 7.8034882784E-004 | 1.6008343454E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1282368346 | 7.1901463126E-002 | Pass | Pass | 0.3683242989 | 0.4757968070 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0798395818E-002 | 6.3367775888E-003 | Pass | Pass | 0.4854691188 | 0.4925099592 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1550452297 | 0.1414973522 | Pass | Pass | 0.7787261587 | 0.9965962683 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.8677175013E-002 | 4.4382822707E-002 | Pass | Pass | 10.1027192180 | 88.5616022817 | Fail | Fail |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1196805691 | 0.1212514786 | Pass | Pass | 1.4896346417 | 3.8957031901 | Fail | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1765748097 | 0.1715574137 | Pass | Pass | 1.4218084842 | 3.5152237424 | Fail | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1066412055 | 6.7331983825E-002 | Pass | Pass | 0.3833534626 | 0.4802041474 | Pass | Fail |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6284354080 | 0.5538567536 | Pass | Pass | 0.6375253602 | 0.5601526891 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6686148319 | 0.6476647713 | Pass | Pass | 0.6820460160 | 0.6515196879 | Fail | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6308448179 | 0.6096566184 | Pass | Pass | 0.6850682972 | 0.6610041166 | Fail | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5748537259 | 0.5604334545 | Pass | Pass | 0.7002921789 | 0.6647515555 | Fail | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8682955786 | 0.7490374198 | Pass | Pass | 0.6028929435 | 0.5580919353 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8889172602 | 0.8561903194 | Pass | Pass | 0.6267758862 | 0.6038685034 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.8474473348 | 0.8211936308 | Pass | Pass | 0.6316955282 | 0.6111381228 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8076732615 | 0.7884683159 | Pass | Pass | 0.6440289180 | 0.6053863769 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3505596547E-002 | 2.1564080832E-002 | Pass | Pass | 0.4168743599 | 0.4987454855 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1036959399 | 6.0870897788E-002 | Pass | Pass | 0.4848373630 | 0.4829001338 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2442195716 | 0.1612726530 | Pass | Pass | 0.4865307038 | 0.4932295139 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.6507306773E-003 | 3.9543138360E-003 | Pass | Pass | 1.7066242355E-003 | 1.8783795982E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3838036107E-003 | 1.9990645648E-003 | Pass | Pass | 1.8252140870E-003 | 1.3736443608E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.6059088831E-003 | 3.4371437550E-003 | Pass | Pass | 3.2284065032E-003 | 2.0739377770E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1998060692E-003 | 1.0521620153E-003 | Pass | Pass | 9.7994123894E-005 | 1.5317167474E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4557.29 | 221.59 | 0.00 | 30456.24 | 16789.60 | 52024.72 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.871 | 1.002 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.816 | 0.930 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.107 | 1.327 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 1043.06 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 1.661 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1390 | 2779.43 | 25401.24 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 235.63 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.1390 | 24961.20 | 228120.99 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 2116.09 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.1390 | 3134.13 | 28642.87 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.1390 | 3134.20 | 28643.49 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.1390 | 783.68 | 7162.06 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 66.44 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 11.7111 | 362.03 | 4239.75 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 43.70 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
Interior Lighting Total | 9.1631 | 46320.38 | 424440.34 | 1212.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 57580.60 | AstronomicalClock | - | 83.06 | 83.06 | 897.74 | |
Exterior Lighting Total | 57580.60 | 897.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2084298.46 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 4246683.13 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1058581.80 | 6.11 | 1012488.58 | 5.82 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1058581.80 | 6.11 | 1012488.58 | 5.82 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 555349.99 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1257570.15 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1257570.15 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 174332.54 | 260963.45 | 178957.30 | 82006.16 | 0.69 | - | 36758.56 | 372.83 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1644304.47 | 2445694.35 | 1674455.84 | 771238.51 | 0.68 | - | 343592.45 | 3484.91 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 172765.96 | 257838.07 | 176715.14 | 81122.93 | 0.69 | - | 36243.02 | 367.60 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 97699.81 | 147217.68 | 101862.92 | 45354.76 | 0.69 | - | 20216.50 | 205.05 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 443573.66 | 281154.70 | 162418.96 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10184.73 | 6527.77 | 3656.96 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 97757.63 | 62649.59 | 35108.04 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9868.48 | 6324.51 | 3543.97 | 0.64 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 30181.27 | 28606.94 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 504293.33 | 477613.82 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 120587.92 | 114263.79 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20833.58 | 19739.41 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14295.06 | 13544.13 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22449.41 | 21270.10 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12525.03 | 11863.30 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 272765.95 | 258428.79 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 180956.04 | 171443.91 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 271050.32 | 256803.58 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 173723.64 | 164592.57 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37048.14 | 35099.53 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24424.45 | 23139.75 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36819.49 | 34882.93 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23969.97 | 22709.20 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 174483.31 | 96758.23 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1802938.97 | 957476.72 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 190614.86 | 101228.77 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 332722.40 | 241323.84 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 443573.66 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10184.73 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 97757.63 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9868.48 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 33013.32 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 15250.79 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.88 | 22450.16 | 2271.59 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 92.23 | 210635.96 | 2283.73 | 1.00 | 1.07 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.75 | 22151.06 | 2271.59 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.73 | 10587.24 | 1849.05 | 1.00 | 1.15 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.74 | 35853.65 | 1649.25 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 574.87 | 1120.11 | 1.00 | 1.59 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.93 | 5517.21 | 1120.11 | 1.00 | 1.16 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 556.96 | 1120.11 | 1.00 | 1.61 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.088875 | 18313.90 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.037152 | 11188.50 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.088875 | 12679.33 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013748 | 3506.50 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.105171 | 31675.22 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78071.47 | 78071.47 | 28.09 | 5.726 | 5.726 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00745 | 19.85 | 0.00700 | 1.200 | 0.00 |
CORE_BOTTOM | 82582.64 | 82582.64 | 33.08 | 6.056 | 6.056 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 19.85 | 0.00700 | 1.078 | 0.00 |
CORE_MID | 778122.47 | 778122.47 | 311.73 | 57.051 | 57.051 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 19.85 | 0.00700 | 10.778 | 0.00 |
CORE_TOP | 76367.21 | 76367.21 | 30.59 | 5.599 | 5.599 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 19.85 | 0.00700 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13128.26 | 13128.26 | 41.89 | 0.972 | 0.972 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00729 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17007.69 | 17007.69 | 84.21 | 1.259 | 1.259 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00714 | 21.79 | 0.00700 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 26037.68 | 26037.68 | 83.08 | 1.927 | 1.927 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00714 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20083.22 | 20083.22 | 99.43 | 1.486 | 1.486 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00712 | 24.70 | 0.00700 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120663.58 | 120663.58 | 385.00 | 8.930 | 8.930 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00730 | 21.23 | 0.00700 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 179014.51 | 179014.51 | 886.32 | 13.248 | 13.248 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00713 | 22.37 | 0.00700 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 272579.64 | 272579.64 | 869.70 | 20.172 | 20.172 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00714 | 27.40 | 0.00701 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 182414.30 | 182414.30 | 903.15 | 13.499 | 13.499 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00713 | 24.44 | 0.00700 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12428.97 | 12428.97 | 39.66 | 0.920 | 0.920 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00729 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17818.16 | 17818.16 | 88.22 | 1.319 | 1.319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00713 | 22.66 | 0.00700 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 28240.01 | 28240.01 | 90.10 | 2.090 | 2.090 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00713 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18887.94 | 18887.94 | 93.52 | 1.398 | 1.398 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00713 | 24.44 | 0.00700 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8792.53 | 8792.53 | 242.87 | 0.513 | 0.513 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00708 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84384.80 | 84384.80 | 2330.90 | 4.926 | 4.926 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 27.00 | 27.00 | 0.00709 | 21.99 | 0.00700 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8518.68 | 8518.68 | 235.30 | 0.497 | 0.497 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 27.00 | 27.00 | 0.00708 | 21.99 | 0.00700 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372440.57 | 372440.57 | 475.25 | 21.739 | 21.739 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.12 | 0.00699 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 22.38 | 0.00006 | -41.90 | 0.00006 | 1.200 | 0.00 |
CORE_BOTTOM | 12171.72 | 12171.72 | 4.88 | 0.520 | 1.078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
CORE_MID | 334643.07 | 334643.07 | 134.07 | 14.369 | 14.369 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 10.778 | 0.00 |
CORE_TOP | 84416.73 | 84416.73 | 33.82 | 3.649 | 3.649 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14579.09 | 14579.09 | 46.52 | 0.631 | 0.631 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 10002.90 | 10002.90 | 49.53 | 0.433 | 0.433 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15708.74 | 15708.74 | 50.12 | 0.680 | 0.680 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 8106.02 | 8106.02 | 40.13 | 0.351 | 0.351 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 190839.55 | 190839.55 | 608.91 | 8.266 | 8.266 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 126602.56 | 126602.56 | 626.82 | 5.484 | 5.484 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 189640.17 | 189640.17 | 605.07 | 8.214 | 8.214 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 121546.11 | 121546.11 | 601.79 | 5.265 | 5.265 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 25915.73 | 25915.73 | 82.69 | 1.123 | 1.123 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17085.08 | 17085.08 | 84.59 | 0.741 | 0.741 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25755.88 | 25755.88 | 82.18 | 1.116 | 1.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16767.31 | 16767.31 | 83.02 | 0.727 | 0.727 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.05 | 0.00056 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.24 | 0.00056 | -41.90 | 0.00006 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.41 | 0.00056 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | 18.00 | 27.00 | 0.00700 | -41.90 | 0.00006 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.88 | 9.88 | 3.17 | 3.17 | 9.8830 | 3.5099 | 9.8830 | 0.3551 | 0.3000 |
VAV_MID WITH REHEAT | 92.23 | 92.23 | 41.60 | 41.60 | 92.2334 | 41.5984 | 92.2334 | 0.4510 | 0.3000 |
VAV_TOP WITH REHEAT | 9.75 | 9.75 | 7.36 | 7.36 | 9.7513 | 7.3560 | 9.7513 | 0.7544 | 0.3000 |
CAV_BAS | 5.73 | 5.73 | 1.20 | 1.20 | 5.7258 | 5.7258 | 5.7258 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.74 | 21.74 | 0.34 | 0.34 | 21.7394 | 21.7393 | 21.7394 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5132 | 0.5132 | 0.5132 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.93 | 4.93 | 0.16 | 0.16 | 4.9256 | 4.9256 | 4.9256 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4972 | 0.4972 | 0.4972 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 30181.266 | 30181.266 | 1.816905 | 0.00026404 | 651.958 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30181.27 | 30181.27 | 1.816905 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799999 | 50.9130 | 12171.72 | 0.00 | 30286.60 | 30286.60 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 504293.328 | 504293.328 | 17.115279 | 0.00441178 | 12682.410 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 504293.33 | 504293.33 | 17.115279 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 334643.07 | 0.00 | 505860.34 | 505860.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 120587.919 | 120587.919 | 3.649155 | 0.00105496 | 3182.020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120587.92 | 120587.92 | 3.649155 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 84416.73 | 0.00 | 120996.49 | 120996.49 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 20833.584 | 20833.584 | 0.631041 | 0.00018226 | 549.512 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20833.58 | 20833.58 | 0.631041 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796496 | 50.6934 | 14579.09 | 0.00 | 20902.48 | 20902.48 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 14295.057 | 14295.057 | 0.433051 | 0.00012506 | 377.027 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14295.06 | 14295.06 | 0.433051 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796759 | 50.7099 | 10002.90 | 0.00 | 14342.16 | 14342.16 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 22449.414 | 22449.414 | 0.680086 | 0.00019640 | 592.091 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22449.41 | 22449.41 | 0.680086 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796964 | 50.7227 | 15708.74 | 0.00 | 22523.36 | 22523.36 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12525.032 | 12525.032 | 0.445872 | 0.00010957 | 309.457 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12525.03 | 12525.03 | 0.445872 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00794504 | 50.5684 | 8106.02 | 0.00 | 12564.34 | 12564.34 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 272765.945 | 272765.945 | 8.266303 | 0.00238628 | 7192.828 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 272765.95 | 272765.95 | 8.266303 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00794542 | 50.5710 | 190839.55 | 0.00 | 273655.60 | 273655.60 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 180956.044 | 180956.044 | 5.484223 | 0.00158308 | 4771.700 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180956.04 | 180956.04 | 5.484223 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00794545 | 50.5711 | 126602.56 | 0.00 | 181545.49 | 181545.49 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 271050.321 | 271050.321 | 8.214222 | 0.00237127 | 7147.622 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 271050.32 | 271050.32 | 8.214222 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00794500 | 50.5683 | 189640.17 | 0.00 | 271934.63 | 271934.63 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 173723.645 | 173723.645 | 5.264703 | 0.00151981 | 4581.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 173723.64 | 173723.64 | 5.264703 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00794264 | 50.5535 | 121546.11 | 0.00 | 174290.48 | 174290.48 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 37048.138 | 37048.138 | 1.123241 | 0.00032411 | 976.767 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37048.14 | 36931.65 | 1.123241 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795188 | 50.6116 | 25915.73 | 0.00 | 37167.60 | 37167.60 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24424.448 | 24424.448 | 0.740531 | 0.00021368 | 643.938 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24424.45 | 24424.45 | 0.740531 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795138 | 50.6085 | 17085.08 | 0.00 | 24503.15 | 24503.15 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 36819.488 | 36819.488 | 1.116301 | 0.00032211 | 970.742 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36819.49 | 36819.49 | 1.116301 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795156 | 50.6097 | 25755.88 | 0.00 | 36938.24 | 36938.24 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23969.965 | 23969.965 | 0.726739 | 0.00020970 | 631.961 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23969.97 | 23969.97 | 0.726739 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795040 | 50.6024 | 16767.31 | 0.00 | 24047.23 | 24047.23 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 174332.541 | -999.000 | 9.883001 | 0.00741651 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 174332.54 | 168293.14 | 9.883001 | 24.95 | 15.47 | 0.00723583 | 10.92 | 9.60 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 27.4739 | 24.00 | 0.00732425 | 38.8892 | 131575.30 | 0.00 | 176824.34 | 176824.34 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 174483.309 | 174483.309 | 2.964900 | 0.00152646 | 2303.847 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 174483.31 | 174483.31 | 2.964900 | -36.60 | -36.60 | 0.00073084 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 91.5798 | 21.00 | 0.00796929 | 50.7204 | 44531.42 | 0.00 | 116903.01 | 116903.01 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1644304.466 | -999.000 | 92.233391 | 0.06995251 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1644304.47 | 1586491.14 | 92.233391 | 25.08 | 15.52 | 0.00724137 | 10.91 | 9.59 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 30.8413 | 24.00 | 0.00735039 | 39.0263 | 1210186.04 | 0.00 | 1667654.89 | 1667654.89 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1802938.972 | 1802938.972 | 27.670017 | 0.01577290 | 23052.729 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1802938.97 | 1802938.97 | 27.670017 | -41.90 | -41.90 | 0.00006450 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 102.8044 | 19.64 | 0.00793082 | 54.9183 | 565283.77 | 0.00 | 1156266.68 | 1156266.68 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 172765.960 | -999.000 | 9.751331 | 0.00734986 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 172765.96 | 167036.58 | 9.751331 | 25.03 | 15.49 | 0.00722659 | 10.92 | 9.60 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 30.3557 | 24.00 | 0.00732267 | 38.8808 | 131348.33 | 0.00 | 175227.26 | 175227.26 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 190614.861 | 190614.861 | 2.925399 | 0.00166758 | 2437.239 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 190614.86 | 190614.86 | 2.925399 | -41.90 | -41.90 | 0.00006450 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 101.1855 | 17.60 | 0.00793864 | 62.4299 | 80591.88 | 0.00 | 122245.74 | 122245.74 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 97699.813 | -999.000 | 5.725768 | 0.00415638 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 97699.81 | 92325.65 | 5.725768 | 24.48 | 15.42 | 0.00737178 | 11.27 | 9.75 | 0.00700000 | 26.07 | 0.00700513 | 15.67 | 20.9606 | 24.00 | 0.00748249 | 39.7197 | 69924.27 | 0.00 | 99118.64 | 99118.64 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 332722.397 | 332722.397 | 5.725768 | 0.00291080 | 6874.655 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 332722.40 | 332722.40 | 5.725768 | -8.78 | -12.32 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 20.9606 | 22.50 | 0.00006450 | 0.3794 | 0.00 | 0.00 | 254555.35 | 254555.35 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 443573.657 | 281154.696 | 21.739403 | 0.01086309 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 398303.67 | 396230.44 | -999.0 | 28.42 | 16.54 | 0.00704154 | 12.80 | 10.42 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | -999.0000 | 27.00 | 0.00704208 | 31.3054 | 371942.32 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10184.735 | 6527.772 | 0.513224 | 0.00024942 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 9098.25 | 9005.20 | -999.0 | 27.81 | 16.35 | 0.00707954 | 12.80 | 10.42 | 0.00700000 | 21.99 | 0.00699901 | 14.15 | -999.0000 | 27.00 | 0.00708207 | 31.4791 | 8792.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97757.630 | 62649.588 | 4.925605 | 0.00239408 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 87330.32 | 86400.82 | -999.0 | 27.80 | 16.35 | 0.00708279 | 12.80 | 10.42 | 0.00700000 | 21.99 | 0.00699901 | 14.15 | -999.0000 | 27.00 | 0.00708553 | 31.4944 | 84384.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9868.484 | 6324.512 | 0.497241 | 0.00024168 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | 8815.85 | 8722.80 | -999.0 | 27.80 | 16.35 | 0.00708209 | 12.80 | 10.42 | 0.00700000 | 21.99 | 0.00699901 | 14.15 | -999.0000 | 27.00 | 0.00708479 | 31.4911 | 8518.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 443573.657 | 443573.657 | 21.739403 | 0.01086309 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 443573.66 | 443573.66 | 21.739403 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.5566 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10184.735 | 10184.735 | 0.513224 | 0.00024942 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10184.73 | 10184.73 | 0.513224 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0459 | 24.93 | 0.00056008 | 2.8425 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97757.630 | 97757.630 | 4.925605 | 0.00239408 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 97757.63 | 97757.63 | 4.925605 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1737 | 23.52 | 0.00056011 | 3.0943 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9868.484 | 9868.484 | 0.497241 | 0.00024168 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9868.48 | 9868.48 | 0.497241 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1438 | 21.72 | 0.00055956 | 3.4473 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 33013.32 | 33013.32 | 21.739403 | -0.65 | -0.65 | 0.00689204 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.5566 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.513224 | -1.28 | -6.15 | 0.00054499 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0459 | 24.93 | 0.00056008 | 2.8425 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15250.79 | 15250.79 | 4.925605 | -1.33 | -6.19 | 0.00054438 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1737 | 23.52 | 0.00056011 | 3.0943 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.497241 | -1.32 | -6.18 | 0.00054400 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.1438 | 21.72 | 0.00055956 | 3.4473 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 30181.266 | 30181.266 | 1.816905 | 0.00026404 | 651.958 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.6967 | 0.710702 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30181.27 | 30181.27 | 1.0000 | 2.15383076 | 1.816905 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.26401195 | 60.00 | 32.22 | 27.78 | 0.000 | 30181.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.69 | 0.00799999 | 21.00 | 0.00799999 | 50.9130 | 12171.72 | 0.00 | 30286.60 | 30286.60 | 2.15383076 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.59 | 16.87 | 0.00800000 | 47121.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 504293.328 | 504293.328 | 17.115279 | 0.00441178 | 12682.410 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 11.6407 | 11.874993 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 504293.33 | 504293.33 | 1.0000 | 20.28912465 | 17.115279 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 4.41132798 | 60.00 | 32.22 | 27.78 | 0.000 | 504293.33 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 334643.07 | 0.00 | 505860.34 | 505860.34 | 20.28912465 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.25 | 20.35 | 0.00800000 | 57992.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 120587.919 | 120587.919 | 3.649155 | 0.00105496 | 3182.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 2.7836 | 2.839579 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 120587.92 | 120587.92 | 1.0000 | 4.32585140 | 3.649155 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.05484810 | 60.00 | 32.22 | 27.78 | 0.000 | 120587.92 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 84416.73 | 0.00 | 120996.49 | 120996.49 | 4.32585140 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20833.584 | 20833.584 | 0.631041 | 0.00018226 | 549.512 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.4809 | 0.490585 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20833.58 | 20833.58 | 1.0000 | 0.74806100 | 0.631041 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.18224269 | 60.00 | 32.22 | 27.78 | 0.000 | 20833.58 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796496 | 21.00 | 0.00796496 | 50.6934 | 14579.09 | 0.00 | 20902.48 | 20902.48 | 0.74806100 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14295.057 | 14295.057 | 0.433051 | 0.00012506 | 377.027 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.3300 | 0.336617 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14295.06 | 14295.06 | 1.0000 | 0.51335534 | 0.433051 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12504664 | 60.00 | 32.22 | 27.78 | 0.000 | 14295.06 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796759 | 21.00 | 0.00796759 | 50.7099 | 10002.90 | 0.00 | 14342.16 | 14342.16 | 0.51335534 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22449.414 | 22449.414 | 0.680086 | 0.00019640 | 592.091 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.5182 | 0.528634 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22449.41 | 22449.41 | 1.0000 | 0.80620091 | 0.680086 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19637723 | 60.00 | 32.22 | 27.78 | 0.000 | 22449.41 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796964 | 21.00 | 0.00796964 | 50.7227 | 15708.74 | 0.00 | 22523.36 | 22523.36 | 0.80620091 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12525.032 | 12525.032 | 0.445872 | 0.00010957 | 309.457 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.2891 | 0.294937 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12525.03 | 12525.03 | 1.0000 | 0.52855437 | 0.445872 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10956326 | 60.00 | 32.22 | 27.78 | 0.000 | 12525.03 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00794504 | 21.00 | 0.00794504 | 50.5684 | 8106.02 | 0.00 | 12564.34 | 12564.34 | 0.52855437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.11 | 20.00 | 0.00800000 | 56831.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 272765.945 | 272765.945 | 8.266303 | 0.00238628 | 7192.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 6.2963 | 6.423035 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 272765.95 | 272765.95 | 1.0000 | 9.79920041 | 8.266303 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.38603206 | 60.00 | 32.22 | 27.78 | 0.000 | 272765.95 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00794542 | 21.00 | 0.00794542 | 50.5710 | 190839.55 | 0.00 | 273655.60 | 273655.60 | 9.79920041 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 180956.044 | 180956.044 | 5.484223 | 0.00158308 | 4771.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 4.1771 | 4.261115 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 180956.04 | 180956.04 | 1.0000 | 6.50121387 | 5.484223 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.58292092 | 60.00 | 32.22 | 27.78 | 0.000 | 180956.04 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00794545 | 21.00 | 0.00794545 | 50.5711 | 126602.56 | 0.00 | 181545.49 | 181545.49 | 6.50121387 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60984.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 271050.321 | 271050.321 | 8.214222 | 0.00237127 | 7147.622 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 6.2567 | 6.382636 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 271050.32 | 271050.32 | 1.0000 | 9.73746113 | 8.214222 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.37102456 | 60.00 | 32.22 | 27.78 | 0.000 | 271050.32 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00794500 | 21.00 | 0.00794500 | 50.5683 | 189640.17 | 0.00 | 271934.63 | 271934.63 | 9.73746113 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 173723.645 | 173723.645 | 5.264703 | 0.00151981 | 4581.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 4.0101 | 4.090808 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 173723.64 | 173723.64 | 1.0000 | 6.24098535 | 5.264703 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.51965519 | 60.00 | 32.22 | 27.78 | 0.000 | 173723.64 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00794264 | 21.00 | 0.00794264 | 50.5535 | 121546.11 | 0.00 | 174290.48 | 174290.48 | 6.24098535 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37048.138 | 37048.138 | 1.123241 | 0.00032411 | 976.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.8552 | 0.872402 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37048.14 | 36931.65 | 1.0000 | 1.33153458 | 1.123241 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.32408021 | 60.00 | 32.22 | 27.78 | 0.000 | 37048.14 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795188 | 21.00 | 0.00795188 | 50.6116 | 25915.73 | 0.00 | 37167.60 | 37167.60 | 1.33153458 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24424.448 | 24424.448 | 0.740531 | 0.00021368 | 643.938 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.5638 | 0.575142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24424.45 | 24424.45 | 1.0000 | 0.87785498 | 0.740531 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.21365393 | 60.00 | 32.22 | 27.78 | 0.000 | 24424.45 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795138 | 21.00 | 0.00795138 | 50.6085 | 17085.08 | 0.00 | 24503.15 | 24503.15 | 0.87785498 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36819.488 | 36819.488 | 1.116301 | 0.00032211 | 970.742 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.8499 | 0.867018 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36819.49 | 36819.49 | 1.0000 | 1.32330659 | 1.116301 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.32208008 | 60.00 | 32.22 | 27.78 | 0.000 | 36819.49 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795156 | 21.00 | 0.00795156 | 50.6097 | 25755.88 | 0.00 | 36938.24 | 36938.24 | 1.32330659 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23969.965 | 23969.965 | 0.726739 | 0.00020970 | 631.961 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 0.5533 | 0.564440 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23969.97 | 23969.97 | 1.0000 | 0.86150531 | 0.726739 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.20967832 | 60.00 | 32.22 | 27.78 | 0.000 | 23969.97 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795040 | 21.00 | 0.00795040 | 50.6024 | 16767.31 | 0.00 | 24047.23 | 24047.23 | 0.86150531 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 174332.541 | -999.000 | 9.883001 | 0.00741651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2910 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.883001 | 11.71569725 | 4197.9300 | 999.8980 | 88.86619542 | 12.27 | 6.67 | 5.60 | 2089102.78 | 8.3449 | 8.344852 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 174332.54 | 168293.14 | 1.0000 | 11.71569725 | 9.883001 | 24.95 | 15.47 | 0.00723583 | 43499.9 | 10.92 | 9.60 | 0.00700000 | 28619.7 | 7.41575272 | 6.67 | 12.27 | 5.60 | 22450.157 | 151882.38 | 27.40 | 0.00700714 | 16.15 | 2.71525000 | 27.4739 | 24.00 | 0.00732425 | 24.00 | 0.00732425 | 38.8892 | 131575.30 | 0.00 | 176824.34 | 176824.34 | 11.71569725 | 24.95 | 15.62 | 0.00723583 | 43499.9 | 10.13 | 9.63 | 0.00723583 | 28407.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 174483.309 | 174483.309 | 2.964900 | 0.00152646 | 2303.847 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.883001 | 11.71569725 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 4.0276 | 4.108696 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 174483.31 | 174483.31 | 1.0000 | 3.51470918 | 2.964900 | -36.60 | -36.60 | 0.00073084 | -35002.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.52630039 | 60.00 | 32.22 | 27.78 | 0.000 | 174483.31 | -41.90 | 0.00006450 | -41.90 | 2.71525000 | 91.5798 | 21.00 | 0.00797808 | 21.00 | 0.00796929 | 50.7204 | 44531.42 | 0.00 | 116903.01 | 116903.01 | 3.51470918 | 2.80 | -3.23 | 0.00073084 | 4645.1 | 35.86 | 13.70 | 0.00073084 | 37906.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1644304.466 | -999.000 | 92.233391 | 0.06995251 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3013 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.233391 | 109.33708626 | 4197.9300 | 999.8980 | 88.86619542 | 12.27 | 6.67 | 5.60 | 2089102.78 | 78.7086 | 78.708644 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1644304.47 | 1586491.14 | 1.0000 | 109.33708626 | 92.233391 | 25.08 | 15.52 | 0.00724137 | 43648.3 | 10.91 | 9.59 | 0.00700000 | 28609.5 | 69.94537725 | 6.67 | 12.27 | 5.60 | 210635.961 | 1433668.51 | 27.40 | 0.00700714 | 16.15 | 28.44599000 | 30.8413 | 24.00 | 0.00735039 | 24.00 | 0.00735039 | 39.0263 | 1210186.04 | 0.00 | 1667654.89 | 1667654.89 | 109.33708626 | 25.08 | 15.68 | 0.00724137 | 43648.3 | 10.10 | 9.62 | 0.00724137 | 28395.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1802938.972 | 1802938.972 | 27.670017 | 0.01577290 | 23052.729 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.233391 | 109.33708626 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 41.6177 | 42.455227 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1802938.97 | 1802938.97 | 1.0000 | 32.80112588 | 27.670017 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 15.77128764 | 60.00 | 32.22 | 27.78 | 0.000 | 1802938.97 | -41.90 | 0.00006450 | -41.90 | 28.44599000 | 102.8044 | 19.00 | 0.00794815 | 19.64 | 0.00793082 | 54.9183 | 565283.77 | 0.00 | 1156266.68 | 1156266.68 | 32.80112588 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 37.88 | 13.83 | 0.00006450 | 38226.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 172765.960 | -999.000 | 9.751331 | 0.00734986 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2739 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.751331 | 11.55961115 | 4197.9300 | 999.8980 | 88.86619542 | 12.27 | 6.67 | 5.60 | 2089102.78 | 8.2699 | 8.269864 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 172765.96 | 167036.58 | 1.0000 | 11.55961115 | 9.751331 | 25.03 | 15.49 | 0.00722659 | 43565.3 | 10.92 | 9.60 | 0.00700000 | 28619.6 | 7.34911354 | 6.67 | 12.27 | 5.60 | 22151.058 | 150614.90 | 27.40 | 0.00700714 | 16.15 | 2.96008000 | 30.3557 | 24.00 | 0.00732267 | 24.00 | 0.00732267 | 38.8808 | 131348.33 | 0.00 | 175227.26 | 175227.26 | 11.55961115 | 25.03 | 15.65 | 0.00722659 | 43565.3 | 10.15 | 9.63 | 0.00722659 | 28406.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 190614.861 | 190614.861 | 2.925399 | 0.00166758 | 2437.239 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.751331 | 11.55961115 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 4.4000 | 4.488559 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 190614.86 | 190614.86 | 1.0000 | 3.46788335 | 2.925399 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.66741184 | 60.00 | 32.22 | 27.78 | 0.000 | 190614.86 | -41.90 | 0.00006450 | -41.90 | 2.96008000 | 101.1855 | 16.46 | 0.00794200 | 17.60 | 0.00793864 | 62.4299 | 80591.88 | 0.00 | 122245.74 | 122245.74 | 3.46788335 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 37.88 | 13.83 | 0.00006450 | 38226.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 97699.813 | -999.000 | 5.725768 | 0.00415638 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5438 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:ConstantVolume | 5.725768 | 6.78754986 | 4197.9300 | 999.8980 | 88.86619542 | 12.27 | 6.67 | 5.60 | 2089102.78 | 4.6766 | 4.676640 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 97699.81 | 92325.65 | 1.0000 | 6.78754986 | 5.725768 | 24.48 | 15.42 | 0.00737178 | 43370.3 | 11.27 | 9.75 | 0.00700000 | 28976.3 | 4.15595191 | 6.67 | 12.27 | 5.60 | 10587.236 | 87112.58 | 26.07 | 0.00700513 | 15.67 | 1.20015641 | 20.9606 | 24.00 | 0.00748249 | 24.00 | 0.00748249 | 39.7197 | 69924.27 | 0.00 | 99118.64 | 99118.64 | 6.78754986 | 24.48 | 15.57 | 0.00737178 | 43370.3 | 10.14 | 9.78 | 0.00737178 | 28767.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 332722.397 | 332722.397 | 5.725768 | 0.00291080 | 6874.655 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:ConstantVolume | 5.725768 | 6.78754986 | 4197.9300 | 999.8980 | 37.14804674 | 54.44 | 82.22 | 27.78 | 4332149.32 | 7.6803 | 7.834877 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 332722.40 | 332722.40 | 1.0000 | 6.78754986 | 5.725768 | -8.78 | -12.32 | 0.00006450 | -8664.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.91050374 | 60.00 | 32.22 | 27.78 | 0.000 | 332722.40 | -41.90 | 0.00006450 | -41.90 | 1.20015641 | 20.9606 | 0.00 | 0.00006450 | 22.50 | 0.00006450 | 0.3794 | 0.00 | 0.00 | 254555.35 | 254555.35 | 6.78754986 | 12.80 | 2.07 | 0.00006450 | 13024.8 | 50.12 | 18.22 | 0.00006450 | 50528.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 443573.657 | 281154.696 | 21.739403 | 0.01086309 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9299 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 398303.67 | 396230.44 | 0.8979 | -999.0 | -999.0 | 28.42 | 16.54 | 0.00704154 | 46538.9 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 398303.67 | 27.40 | 0.00700714 | 16.15 | 0.33839277 | -999.0000 | 27.00 | 0.00704208 | 27.00 | 0.00704208 | 31.3054 | 371942.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10184.735 | 6527.772 | 0.513224 | 0.00024942 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0005 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 9098.25 | 9005.20 | 0.8933 | -999.0 | -999.0 | 27.81 | 16.35 | 0.00707954 | 46012.8 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9098.25 | 21.99 | 0.00699901 | 14.15 | 0.01563234 | -999.0000 | 27.00 | 0.00708207 | 27.00 | 0.00708207 | 31.4791 | 8792.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 97757.630 | 62649.588 | 4.925605 | 0.00239408 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0065 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | Sensible | 87330.32 | 86400.82 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708279 | 46014.5 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87330.32 | 21.99 | 0.00699901 | 14.15 | 0.15632344 | -999.0000 | 27.00 | 0.00708553 | 27.00 | 0.00708553 | 31.4944 | 84384.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9868.484 | 6324.512 | 0.497241 | 0.00024168 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0053 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:20:00 | Sensible | 8815.85 | 8722.80 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708209 | 46014.2 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8815.85 | 21.99 | 0.00699901 | 14.15 | 0.01563234 | -999.0000 | 27.00 | 0.00708479 | 27.00 | 0.00708479 | 31.4911 | 8518.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 443573.657 | 443573.657 | 21.739403 | 0.01086309 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 443573.66 | 443573.66 | 1.0000 | 25.77074313 | 21.739403 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 443573.66 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.5566 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10184.735 | 10184.735 | 0.513224 | 0.00024942 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10184.73 | 10184.73 | 1.0000 | 0.60839615 | 0.513224 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10184.73 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0459 | 0.00 | 0.00056008 | 24.93 | 0.00056008 | 2.8425 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97757.630 | 97757.630 | 4.925605 | 0.00239408 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 97757.63 | 97757.63 | 1.0000 | 5.83900557 | 4.925605 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97757.63 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.1737 | 0.00 | 0.00056011 | 23.52 | 0.00056011 | 3.0943 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9868.484 | 9868.484 | 0.497241 | 0.00024168 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9868.48 | 9868.48 | 1.0000 | 0.58944889 | 0.497241 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9868.48 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.1438 | 0.00 | 0.00055956 | 21.72 | 0.00055956 | 3.4473 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.739403 | 25.77074313 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 33013.32 | 33013.32 | 1.0000 | 25.77074313 | 21.739403 | -0.65 | -0.65 | 0.00689204 | 16572.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33013.32 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.5566 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.513224 | 0.60839615 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.60839615 | 0.513224 | -1.28 | -6.15 | 0.00054499 | 79.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0459 | 0.00 | 0.00056008 | 24.93 | 0.00056008 | 2.8425 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.925605 | 5.83900557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15250.79 | 15250.79 | 1.0000 | 5.83900557 | 4.925605 | -1.33 | -6.19 | 0.00054438 | 23.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15250.79 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.1737 | 0.00 | 0.00056011 | 23.52 | 0.00056011 | 3.0943 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.497241 | 0.58944889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.58944889 | 0.497241 | -1.32 | -6.18 | 0.00054400 | 35.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.1438 | 0.00 | 0.00055956 | 21.72 | 0.00055956 | 3.4473 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.72 | 9.88 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 28.45 | 92.23 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.96 | 9.75 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.73 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1132.00 | 3081.50 | 39.83 |
CORE_BOTTOM | 1121.00 | 3096.83 | 36.67 |
CORE_MID | 1318.67 | 3866.00 | 640.50 |
CORE_TOP | 2747.00 | 4298.50 | 2183.83 |
PERIMETER_BOT_ZN_3 | 3220.50 | 4050.00 | 2270.00 |
PERIMETER_BOT_ZN_2 | 3386.67 | 4035.00 | 2268.67 |
PERIMETER_BOT_ZN_1 | 3421.50 | 3895.33 | 2134.50 |
PERIMETER_BOT_ZN_4 | 3154.50 | 3583.00 | 1522.67 |
PERIMETER_MID_ZN_3 | 3573.67 | 4436.50 | 2898.33 |
PERIMETER_MID_ZN_2 | 3136.67 | 3741.83 | 2345.50 |
PERIMETER_MID_ZN_1 | 3546.00 | 4174.17 | 2397.17 |
PERIMETER_MID_ZN_4 | 3551.50 | 4565.83 | 2723.33 |
PERIMETER_TOP_ZN_3 | 3903.50 | 4723.00 | 3351.67 |
PERIMETER_TOP_ZN_2 | 4017.67 | 4462.50 | 3092.83 |
PERIMETER_TOP_ZN_1 | 3858.67 | 4439.33 | 2858.83 |
PERIMETER_TOP_ZN_4 | 3838.33 | 4779.33 | 3102.50 |
DATACENTER_BOT_ZN_6 | 5393.67 | 197.33 | 179.00 |
DATACENTER_MID_ZN_6 | 3840.00 | 456.50 | 33.67 |
DATACENTER_TOP_ZN_6 | 3274.67 | 1030.67 | 100.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5379.00 | 5379.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5930.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 26.00 | 0.00 | 0.17 |
CORE_BOTTOM | 0.00 | 2.00 | 0.00 | 0.00 |
CORE_MID | 3.17 | 0.00 | 1.00 | 0.00 |
CORE_TOP | 37.17 | 0.00 | 7.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16.50 | 11.33 | 1.33 | 0.83 |
PERIMETER_BOT_ZN_2 | 17.17 | 10.00 | 0.17 | 6.83 |
PERIMETER_BOT_ZN_1 | 19.83 | 12.17 | 0.33 | 12.00 |
PERIMETER_BOT_ZN_4 | 3.83 | 42.00 | 0.00 | 14.00 |
PERIMETER_MID_ZN_3 | 223.50 | 6.00 | 86.83 | 0.33 |
PERIMETER_MID_ZN_2 | 123.50 | 8.83 | 26.17 | 7.50 |
PERIMETER_MID_ZN_1 | 93.50 | 12.50 | 17.33 | 12.33 |
PERIMETER_MID_ZN_4 | 83.67 | 10.17 | 14.33 | 2.00 |
PERIMETER_TOP_ZN_3 | 588.50 | 2.00 | 240.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 333.50 | 6.83 | 78.50 | 6.33 |
PERIMETER_TOP_ZN_1 | 283.83 | 8.33 | 63.83 | 8.00 |
PERIMETER_TOP_ZN_4 | 265.83 | 7.50 | 67.67 | 1.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 12.00 | 0.00 | 12.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 651.00 | 143.33 | 255.67 | 67.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.067 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.940 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.809 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.768 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 1.062 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.883 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.962 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.225 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.978 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.903 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 2.117 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.933 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 1.141 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 2.070 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 2.162 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 2.013 | 0.083 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.429 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.484 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43267128.19 | 0.00 | 43267128.19 | 0.00 | 43267128.19 | 37848132.68 | 4136.46 | 2019.70 | 2603.84 | 243.58 |
CORE_BOTTOM | 39429622.93 | 0.00 | 39429622.93 | 0.00 | 39429622.93 | 33990283.35 | 3841.26 | 9.87 | 4908.87 | 511.54 |
CORE_MID | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 0.34E+09 | 4128.15 | 6.50 | 4625.35 | 572.21 |
CORE_TOP | 31149766.59 | 0.00 | 31149766.59 | 0.00 | 31149766.59 | 33990283.35 | 4203.65 | 5.70 | 4550.65 | 415.65 |
PERIMETER_BOT_ZN_3 | 5644028.69 | 0.00 | 5644028.69 | 288582.77 | 5932611.46 | 4267819.30 | 3865.25 | 27.41 | 4867.35 | 511.54 |
PERIMETER_BOT_ZN_2 | 6495747.64 | 0.00 | 6495747.64 | 192388.38 | 6688136.02 | 2750345.05 | 3640.20 | 3.50 | 5116.29 | 511.54 |
PERIMETER_BOT_ZN_1 | 10459418.78 | 0.00 | 10459418.78 | 288582.77 | 10748001.54 | 4267912.63 | 3642.07 | 2.50 | 5115.42 | 511.54 |
PERIMETER_BOT_ZN_4 | 7681253.28 | 0.00 | 7681253.28 | 192388.38 | 7873641.66 | 2750345.05 | 3612.12 | 2.48 | 5145.40 | 511.54 |
PERIMETER_MID_ZN_3 | 50632230.95 | 0.00 | 50632230.95 | 676813.33 | 51309044.29 | 42678193.03 | 4118.78 | 10.33 | 4630.89 | 572.21 |
PERIMETER_MID_ZN_2 | 68652918.02 | 0.00 | 68652918.02 | 451208.58 | 69104126.60 | 27503450.52 | 3958.03 | 3.09 | 4798.87 | 1481.21 |
PERIMETER_MID_ZN_1 | 0.11E+09 | 0.00 | 0.11E+09 | 676813.33 | 0.11E+09 | 42679126.28 | 3961.75 | 3.16 | 4795.09 | 572.21 |
PERIMETER_MID_ZN_4 | 64833694.91 | 0.00 | 64833694.91 | 451208.58 | 65284903.49 | 27503450.52 | 3955.64 | 3.63 | 4800.73 | 572.21 |
PERIMETER_TOP_ZN_3 | 5840303.71 | 0.00 | 5840303.71 | 840343.21 | 6680646.92 | 4267819.30 | 4144.72 | 1.60 | 4613.68 | 415.65 |
PERIMETER_TOP_ZN_2 | 6817795.05 | 0.00 | 6817795.05 | 560228.43 | 7378023.47 | 2750345.05 | 4095.67 | 1.22 | 4663.10 | 415.65 |
PERIMETER_TOP_ZN_1 | 11041597.12 | 0.00 | 11041597.12 | 840343.21 | 11881940.33 | 4267912.63 | 4094.33 | 1.75 | 4663.93 | 415.65 |
PERIMETER_TOP_ZN_4 | 6650390.17 | 0.00 | 6650390.17 | 560228.43 | 7210618.60 | 2750345.05 | 4091.53 | 1.63 | 4666.84 | 415.65 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.65E+10 | 0.00 | 0.65E+10 | 26323523.88 | 0.65E+10 | 0.50E+10 | 4521.50 | 4402.47 | 5269.40 | 2075.10 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.9616 | 0.0000 | 1.9616 | 0.0000 | 1.9616 | 1.2002 | 1444.55 | 2015.80 | 2482.65 |
CORE_BOTTOM | 1.7450 | 0.0000 | 1.7450 | 0.0000 | 1.7450 | 1.0778 | 1313.25 | 4.40 | 4625.35 |
CORE_MID | 15.0399 | 0.0000 | 15.0399 | 0.0000 | 15.0399 | 10.7782 | 1419.78 | 4.24 | 4518.98 |
CORE_TOP | 1.4296 | 0.0000 | 1.4296 | 0.0000 | 1.4296 | 1.0778 | 1459.42 | 3.79 | 4479.79 |
PERIMETER_BOT_ZN_3 | 0.2483 | 0.0000 | 0.2483 | 0.0065 | 0.2548 | 0.1353 | 1376.81 | 21.89 | 4544.30 |
PERIMETER_BOT_ZN_2 | 0.2842 | 0.0000 | 0.2842 | 0.0043 | 0.2886 | 0.0872 | 1212.03 | 2.70 | 4728.27 |
PERIMETER_BOT_ZN_1 | 0.4592 | 0.0000 | 0.4592 | 0.0065 | 0.4657 | 0.1353 | 1213.70 | 1.77 | 4727.53 |
PERIMETER_BOT_ZN_4 | 0.3355 | 0.0000 | 0.3355 | 0.0043 | 0.3398 | 0.0872 | 1192.25 | 2.11 | 4748.65 |
PERIMETER_MID_ZN_3 | 2.2890 | 0.0000 | 2.2890 | 0.0152 | 2.3042 | 1.3533 | 1427.28 | 9.64 | 4506.09 |
PERIMETER_MID_ZN_2 | 2.8739 | 0.0000 | 2.8739 | 0.0109 | 2.8848 | 0.8721 | 1304.76 | 2.05 | 3727.19 |
PERIMETER_MID_ZN_1 | 4.9586 | 0.0000 | 4.9586 | 0.0152 | 4.9738 | 1.3533 | 1306.90 | 2.56 | 4633.54 |
PERIMETER_MID_ZN_4 | 2.9203 | 0.0000 | 2.9203 | 0.0101 | 2.9304 | 0.8721 | 1303.86 | 1.42 | 4637.72 |
PERIMETER_TOP_ZN_3 | 0.2677 | 0.0000 | 0.2677 | 0.0189 | 0.2865 | 0.1353 | 1409.86 | 1.40 | 4531.74 |
PERIMETER_TOP_ZN_2 | 0.3127 | 0.0000 | 0.3127 | 0.0126 | 0.3253 | 0.0872 | 1370.41 | 0.86 | 4571.73 |
PERIMETER_TOP_ZN_1 | 0.5066 | 0.0000 | 0.5066 | 0.0189 | 0.5255 | 0.1353 | 1369.85 | 0.65 | 4572.50 |
PERIMETER_TOP_ZN_4 | 0.3044 | 0.0000 | 0.3044 | 0.0126 | 0.3170 | 0.0872 | 1369.10 | 0.68 | 4573.22 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 290.0837 | 0.0000 | 290.0837 | 0.5991 | 290.6829 | 158.4706 | 1704.50 | 4374.88 | 4791.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 97961238.60 | 0.00 | 97961238.60 | 48026705.38 | 3681.40 | 4.00 | 5074.60 | 511.54 |
VAV_MID WITH REHEAT | 0.88E+09 | 0.00 | 0.88E+09 | 0.48E+09 | 4024.75 | 2.22 | 4733.03 | 572.21 |
VAV_TOP WITH REHEAT | 86426133.44 | 0.00 | 86426133.44 | 48026705.38 | 4127.83 | 1.95 | 4630.22 | 415.35 |
CAV_BAS | 60801837.98 | 0.00 | 60801837.98 | 37848132.68 | 4069.37 | 2.99 | 4687.64 | 243.58 |
AIRLOOP DATACENTER BASEMENT | 7431423.23 | 0.00 | 7431423.23 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3433009.67 | 0.00 | 3433009.67 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.3173 | 0.0000 | 4.3173 | 1.5229 | 1242.07 | 2.84 | 4698.09 |
VAV_MID WITH REHEAT | 39.7865 | 0.0000 | 39.7865 | 15.2292 | 1345.72 | 2.19 | 4595.08 |
VAV_TOP WITH REHEAT | 3.9643 | 0.0000 | 3.9643 | 1.5229 | 1393.30 | 1.78 | 4547.92 |
CAV_BAS | 2.7566 | 0.0000 | 2.7566 | 1.2002 | 1421.85 | 1.01 | 4520.14 |
AIRLOOP DATACENTER BASEMENT | 0.3473 | 0.0000 | 0.3473 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1605 | 0.0000 | 0.1605 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 2562.08 | 2804.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2801.65 | 2662.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2981.42 | 2229.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2007.75 | 2858.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.8158 | 6.9262 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 39.9835 | 59.5490 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 4.1603 | 6.1545 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6872 | 4.9698 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4756 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1339 |
Defaulted Fields | 1179 |
Fields with Defaults | 3730 |
Autosized Fields | 335 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
Electricity:Building | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 660.02 | 14600.60 | 01-JAN-00:10 | 34031.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 532.90 | 7069.41 | 01-JAN-00:10 | 36605.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5328.94 | 70693.84 | 01-JAN-00:10 | 366051.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 532.89 | 7069.38 | 01-JAN-00:10 | 36605.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 669.12 | 8876.66 | 01-JAN-00:10 | 45962.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 431.21 | 5720.45 | 01-JAN-00:10 | 29619.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 669.13 | 8876.80 | 01-JAN-00:10 | 45963.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 431.20 | 5720.42 | 01-JAN-00:10 | 29619.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7561.29 | 95230.42 | 01-JAN-00:10 | 385433.43 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1582.51 | 19698.04 | 01-JAN-00:10 | 81759.99 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1120.37 | 4734.01 | 12-JAN-03:30 | 356348.69 | 30-JUN-12:20 |
HeatRejection:Electricity | 554.23 | 982.39 | 12-JAN-08:00 | 81628.52 | 29-JUN-11:50 |
General:HeatRejection:Electricity | 554.23 | 982.39 | 12-JAN-08:00 | 81628.52 | 29-JUN-11:50 |
Electricity:HVAC | 5156.83 | 75286.52 | 01-JAN-06:40 | 441359.05 | 11-AUG-15:40 |
ExteriorEquipment:Electricity | 1997.59 | 30702.09 | 01-JAN-00:10 | 120520.01 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.51 | 1613.62 | 01-JAN-00:10 | 5474.05 | 03-APR-07:20 |
ElectricityPurchased:Facility | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
ElectricityPurchased:Plant | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
Cogeneration:ElectricityPurchased | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
ElectricityNet:Plant | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
Cogeneration:ElectricityNet | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
General:Cogeneration:ElectricityNet | 28240.88 | 369916.43 | 01-JAN-12:40 | 1988589.75 | 11-AUG-15:40 |
Fans:Electricity | 2461.79 | 42502.68 | 01-JAN-08:00 | 284369.36 | 12-JUL-15:20 |
General:Fans:Electricity | 2461.79 | 42502.68 | 01-JAN-08:00 | 284369.36 | 12-JUL-15:20 |
ExteriorLights:Electricity | 897.74 | 0.00 | 01-JAN-11:20 | 57580.60 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 897.74 | 0.00 | 01-JAN-11:20 | 57580.60 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 44.42 | 0.00 | 01-JAN-00:10 | 4264.87 | 07-JAN-17:10 |
General:HeatRecovery:Electricity | 44.42 | 0.00 | 01-JAN-00:10 | 4264.87 | 07-JAN-17:10 |
Cooling:Electricity | 2589.67 | 25612.99 | 12-JAN-08:00 | 377653.12 | 11-AUG-15:20 |
General:Cooling:Electricity | 2589.67 | 25612.99 | 12-JAN-08:00 | 377653.12 | 11-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 228.61 | 0.00 | 16-MAY-08:40 | 23714.49 | 28-DEC-07:10 |
General:Humidifier:Electricity | 228.61 | 0.00 | 16-MAY-08:40 | 23714.49 | 28-DEC-07:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 310.97 | 3506.50 | 06-FEB-05:00 | 62306.02 | 11-AUG-15:40 |
General:Pumps:Electricity | 310.97 | 3506.50 | 06-FEB-05:00 | 62306.02 | 11-AUG-15:40 |
WIRED_LTG_ELECTRICITY | 110.78 | 0.00 | 01-JAN-00:10 | 9672.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8835.91 | 8146.58 | 06-FEB-05:40 | 3875105.37 | 27-FEB-07:10 |
NaturalGas:Plant | 8835.91 | 8146.58 | 06-FEB-05:40 | 3875105.37 | 27-FEB-07:10 |
Heating:NaturalGas | 7893.41 | 0.00 | 01-JAN-00:40 | 3841258.89 | 27-FEB-07:10 |
Boiler:Heating:NaturalGas | 7893.41 | 0.00 | 01-JAN-00:40 | 3841258.89 | 27-FEB-07:10 |
WaterSystems:NaturalGas | 942.50 | 8146.58 | 02-JAN-05:10 | 90199.20 | 31-MAR-11:30 |
Water Heater:WaterSystems:NaturalGas | 942.50 | 8146.58 | 02-JAN-05:10 | 90199.20 | 31-MAR-11:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 13681.78 | 124562.11 | 12-JAN-08:00 | 2095360.43 | 11-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 13681.78 | 124562.11 | 12-JAN-08:00 | 2095360.43 | 11-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 13681.78 | 124562.11 | 12-JAN-08:00 | 2095360.43 | 11-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3504.42 | 0.00 | 13-JUN-23:10 | 0.00 | 20-JUL-14:50 |
Water:HVAC | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
Humidifier:Water | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
General:Humidifier:Water | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
MainsWater:Facility | 3504.42 | 0.00 | 13-JUN-23:10 | 0.00 | 20-JUL-14:50 |
MainsWater:HVAC | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
Humidifier:MainsWater | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
General:Humidifier:MainsWater | 85.04 | 0.00 | 16-MAY-08:40 | 0.00 | 28-DEC-07:10 |
Water:Plant | 3419.38 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3419.38 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1139.21 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
General:HeatRejection:Water | 1139.21 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
HeatRejection:MainsWater | 1139.21 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
General:HeatRejection:MainsWater | 1139.21 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JUL-14:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 54341.12 | 204333.48 | 01-JAN-03:20 | 8674402.22 | 11-AUG-15:20 |
EnergyTransfer:Building | 18947.32 | 86776.35 | 01-JAN-03:20 | 1664492.86 | 10-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 667.32 | 0.00 | 01-JAN-00:10 | 68996.41 | 05-SEP-05:10 |
Heating:EnergyTransfer | 2043.15 | 0.00 | 01-FEB-01:00 | 1496705.41 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.21 | 0.00 | 01-JAN-00:10 | 15810.03 | 29-JUL-16:40 |
General:Heating:EnergyTransfer | 2043.15 | 0.00 | 01-FEB-01:00 | 1496705.41 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.21 | 0.00 | 01-JAN-00:10 | 15810.03 | 29-JUL-16:40 |
Cooling:EnergyTransfer | 16904.18 | 80091.85 | 02-JAN-04:20 | 1664492.86 | 10-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 664.11 | 0.00 | 01-JAN-00:10 | 68996.41 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16904.18 | 80091.85 | 02-JAN-04:20 | 1664492.86 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 664.11 | 0.00 | 01-JAN-00:10 | 68996.41 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 528.17 | 0.00 | 01-JAN-00:40 | 53502.90 | 24-JUL-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 15616.26 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.04 | 0.00 | 01-JAN-00:10 | 15616.26 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 528.13 | 0.00 | 01-JAN-00:40 | 53502.90 | 24-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 528.13 | 0.00 | 01-JAN-00:40 | 53502.90 | 24-JUL-09:20 |
EnergyTransfer:Zone:CORE_MID | 3960.09 | 0.00 | 01-JAN-00:40 | 513876.98 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 31.65 | 0.00 | 01-JAN-00:20 | 513876.98 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 31.65 | 0.00 | 01-JAN-00:20 | 513876.98 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3928.44 | 0.00 | 01-JAN-00:40 | 452467.77 | 24-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3928.44 | 0.00 | 01-JAN-00:40 | 452467.77 | 24-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 347.69 | 0.00 | 01-JAN-00:40 | 73042.66 | 21-FEB-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 50.45 | 0.00 | 01-JAN-00:40 | 73042.66 | 21-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 50.45 | 0.00 | 01-JAN-00:40 | 73042.66 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 297.24 | 0.00 | 01-JAN-00:20 | 48779.66 | 21-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 297.24 | 0.00 | 01-JAN-00:20 | 48779.66 | 21-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.78 | 0.00 | 01-JAN-00:40 | 12658.05 | 11-JUL-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.73 | 0.00 | 01-JAN-00:40 | 12042.14 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.73 | 0.00 | 01-JAN-00:40 | 12042.14 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 55.05 | 0.00 | 01-JAN-00:10 | 12658.05 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 55.05 | 0.00 | 01-JAN-00:10 | 12658.05 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 68.14 | 0.00 | 01-JAN-00:40 | 15424.20 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 9.42 | 0.00 | 01-JAN-00:40 | 8982.61 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 9.42 | 0.00 | 01-JAN-00:40 | 8982.61 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.72 | 0.00 | 01-JAN-00:10 | 15424.20 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.72 | 0.00 | 01-JAN-00:10 | 15424.20 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 113.08 | 0.00 | 01-JAN-00:40 | 23282.19 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 13.28 | 0.00 | 01-JAN-00:40 | 15316.08 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 13.28 | 0.00 | 01-JAN-00:40 | 15316.08 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.81 | 0.00 | 01-JAN-00:10 | 23282.19 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.81 | 0.00 | 01-JAN-00:10 | 23282.19 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 82.94 | 0.00 | 01-JAN-00:40 | 15254.13 | 10-AUG-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.32 | 0.00 | 01-JAN-00:10 | 6588.12 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.32 | 0.00 | 01-JAN-00:10 | 6588.12 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.62 | 0.00 | 01-JAN-00:40 | 15254.13 | 10-AUG-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.62 | 0.00 | 01-JAN-00:40 | 15254.13 | 10-AUG-16:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 776.92 | 0.00 | 01-JAN-00:40 | 125910.45 | 30-JAN-04:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 406.86 | 0.00 | 01-JAN-00:40 | 125910.45 | 30-JAN-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 406.86 | 0.00 | 01-JAN-00:40 | 125910.45 | 30-JAN-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 370.06 | 0.00 | 01-JAN-00:10 | 113872.10 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 370.06 | 0.00 | 01-JAN-00:10 | 113872.10 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 759.94 | 0.00 | 01-JAN-00:40 | 165004.46 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 262.45 | 0.00 | 01-JAN-00:40 | 137208.02 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 262.45 | 0.00 | 01-JAN-00:40 | 137208.02 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 497.49 | 0.00 | 01-JAN-00:20 | 165004.46 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 497.49 | 0.00 | 01-JAN-00:20 | 165004.46 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1188.65 | 0.00 | 01-JAN-00:40 | 250295.63 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 309.15 | 0.00 | 01-JAN-00:40 | 203493.51 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 309.15 | 0.00 | 01-JAN-00:40 | 203493.51 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 879.50 | 0.00 | 01-JAN-00:20 | 250295.63 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 879.50 | 0.00 | 01-JAN-00:20 | 250295.63 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 645.28 | 0.00 | 01-JAN-00:40 | 134081.20 | 11-JUL-17:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 211.86 | 0.00 | 01-JAN-00:40 | 133451.12 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 211.86 | 0.00 | 01-JAN-00:40 | 133451.12 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 433.42 | 0.00 | 01-JAN-00:20 | 134081.20 | 11-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 433.42 | 0.00 | 01-JAN-00:20 | 134081.20 | 11-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 119.60 | 0.00 | 01-JAN-00:40 | 17425.43 | 29-JAN-00:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.62 | 0.00 | 01-JAN-00:40 | 17425.43 | 29-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.62 | 0.00 | 01-JAN-00:40 | 17425.43 | 29-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.98 | 0.00 | 01-JAN-00:10 | 10801.36 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.98 | 0.00 | 01-JAN-00:10 | 10801.36 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 97.52 | 0.00 | 01-JAN-00:40 | 16697.34 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.39 | 0.00 | 01-JAN-00:40 | 16697.34 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.39 | 0.00 | 01-JAN-00:40 | 16697.34 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.13 | 0.00 | 01-JAN-00:10 | 16563.96 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.13 | 0.00 | 01-JAN-00:10 | 16563.96 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 145.67 | 0.00 | 01-JAN-00:40 | 26171.38 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.79 | 0.00 | 01-JAN-00:40 | 26171.38 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.79 | 0.00 | 01-JAN-00:40 | 26171.38 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.88 | 0.00 | 01-JAN-00:10 | 25345.72 | 10-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.88 | 0.00 | 01-JAN-00:10 | 25345.72 | 10-AUG-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 83.93 | 0.00 | 01-JAN-00:40 | 17393.18 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.63 | 0.00 | 01-JAN-00:40 | 17393.18 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.63 | 0.00 | 01-JAN-00:40 | 17393.18 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.30 | 0.00 | 01-JAN-00:20 | 13777.68 | 11-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.30 | 0.00 | 01-JAN-00:20 | 13777.68 | 11-JUL-17:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.84 | 0.00 | 01-JAN-00:40 | 11821.09 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 14.95 | 0.00 | 01-JAN-00:40 | 11821.09 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 14.95 | 0.00 | 01-JAN-00:40 | 11821.09 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 44.89 | 0.00 | 01-JAN-00:10 | 9034.94 | 24-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 44.89 | 0.00 | 01-JAN-00:10 | 9034.94 | 24-JUL-12:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 651.01 | 0.00 | 01-JAN-00:40 | 213092.37 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 317.64 | 0.00 | 01-JAN-00:40 | 213092.37 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 317.64 | 0.00 | 01-JAN-00:40 | 213092.37 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 333.37 | 0.00 | 01-JAN-00:10 | 74581.74 | 24-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 333.37 | 0.00 | 01-JAN-00:10 | 74581.74 | 24-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 168.23 | 0.00 | 01-JAN-00:40 | 35114.47 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 136.99 | 0.00 | 01-JAN-00:40 | 35114.47 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 136.99 | 0.00 | 01-JAN-00:40 | 35114.47 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.25 | 0.00 | 01-JAN-00:10 | 15595.06 | 21-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.25 | 0.00 | 01-JAN-00:10 | 15595.06 | 21-JUL-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.66 | 5.44 | 11-JAN-06:40 | 8540.14 | 20-APR-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.25 | 0.00 | 02-JAN-07:10 | 578.91 | 29-JAN-22:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.25 | 0.00 | 02-JAN-07:10 | 578.91 | 29-JAN-22:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.41 | 0.00 | 01-JAN-00:10 | 8540.14 | 20-APR-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 127.41 | 0.00 | 01-JAN-00:10 | 8540.14 | 20-APR-18:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1073.85 | 5.49 | 27-FEB-02:30 | 81361.82 | 20-APR-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.19 | 0.00 | 02-JAN-07:10 | 5759.23 | 10-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.19 | 0.00 | 02-JAN-07:10 | 5759.23 | 10-JAN-00:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1066.67 | 0.00 | 01-JAN-00:10 | 81361.82 | 20-APR-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1066.67 | 0.00 | 01-JAN-00:10 | 81361.82 | 20-APR-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 93.68 | 0.46 | 30-SEP-10:40 | 8126.93 | 20-APR-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.28 | 0.00 | 02-JAN-07:10 | 607.88 | 10-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.28 | 0.00 | 02-JAN-07:10 | 607.88 | 10-JAN-00:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 92.40 | 0.00 | 01-JAN-00:10 | 8126.93 | 20-APR-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 92.40 | 0.00 | 01-JAN-00:10 | 8126.93 | 20-APR-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7122.33 | 80086.75 | 02-JAN-03:10 | 368873.22 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7122.33 | 80086.75 | 02-JAN-03:10 | 368873.22 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7122.33 | 80086.75 | 02-JAN-03:10 | 368873.22 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 6475.47 | 0.00 | 01-JAN-00:40 | 3049590.04 | 27-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 538.62 | 0.00 | 01-JAN-00:10 | 61994.50 | 12-APR-12:00 |
WaterSystems:PlantLoopHeatingDemand | 538.62 | 0.00 | 01-JAN-00:10 | 61994.50 | 12-APR-12:00 |
General:WaterSystems:PlantLoopHeatingDemand | 538.62 | 0.00 | 01-JAN-00:10 | 61994.50 | 12-APR-12:00 |
EnergyTransfer:HVAC | 23779.79 | 117527.04 | 01-JAN-06:00 | 3222338.65 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 5936.85 | 0.00 | 01-JAN-00:40 | 3028998.45 | 27-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 5936.85 | 0.00 | 01-JAN-00:40 | 3028998.45 | 27-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 5936.85 | 0.00 | 01-JAN-00:40 | 3028998.45 | 27-FEB-07:10 |
CoolingCoils:EnergyTransfer | 11347.29 | 98949.13 | 12-JAN-08:00 | 1935623.60 | 11-AUG-15:40 |
HeatRecoveryForHeating:EnergyTransfer | 6493.14 | 0.00 | 01-JAN-00:10 | 1279660.25 | 08-DEC-17:00 |
HeatRecoveryForCooling:EnergyTransfer | 2.52 | 0.00 | 01-JAN-00:10 | 162133.88 | 29-JUL-16:00 |
EnergyTransfer:Plant | 11614.00 | 0.00 | 01-JAN-00:40 | 5105042.80 | 11-AUG-15:20 |
LoopToLoop:EnergyTransfer | 1756.23 | -0.47 | 14-JAN-05:30 | 1624040.51 | 11-AUG-15:20 |
WaterSystems:EnergyTransfer | 538.62 | 0.00 | 01-JAN-00:10 | 61994.50 | 12-APR-12:00 |
WaterUse:WaterSystems:EnergyTransfer | 538.62 | 0.00 | 01-JAN-00:10 | 61994.50 | 12-APR-12:00 |
Boilers:EnergyTransfer | 5885.06 | 0.00 | 01-JAN-00:40 | 3095663.50 | 27-FEB-07:10 |
Chillers:EnergyTransfer | 1589.46 | 0.00 | 01-JAN-00:10 | 1609347.70 | 11-AUG-15:20 |
HeatRejection:EnergyTransfer | 1844.63 | 0.00 | 01-JAN-00:10 | 1828788.82 | 11-AUG-15:20 |
General:HeatRejection:EnergyTransfer | 1844.63 | 0.00 | 01-JAN-00:10 | 1828788.82 | 11-AUG-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.208 | -664.111 | 0.000 | 0.000 | 97.390 | 235.627 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -96.512 |
CORE_BOTTOM | 0.000 | 0.000 | 0.045 | -528.128 | 0.000 | 0.000 | 84.274 | 211.610 | 321.286 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -89.086 |
CORE_MID | 0.000 | 0.000 | 31.650 | -3928.437 | 0.000 | 0.000 | 868.430 | 2116.097 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2300.585 |
CORE_TOP | 0.000 | 0.000 | 50.449 | -297.236 | 0.000 | 0.000 | 90.797 | 211.610 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -376.905 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 10.734 | -55.050 | 0.000 | 0.000 | 11.403 | 26.570 | 40.342 | 21.997 | 0.000 | 0.004 | 28.690 | 0.000 | -77.465 | 0.000 | -7.224 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 9.424 | -58.715 | 0.000 | 0.000 | 7.389 | 17.123 | 25.998 | 50.826 | 0.000 | 0.003 | 1.171 | 0.000 | -48.475 | 0.000 | -4.744 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 13.277 | -99.807 | 0.000 | 0.000 | 11.428 | 26.570 | 40.343 | 99.908 | 0.000 | 0.004 | 0.001 | 0.000 | -69.121 | 0.000 | -7.186 | -15.418 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.319 | -81.619 | 0.000 | 0.000 | 7.324 | 17.123 | 25.998 | 34.688 | 0.000 | 0.002 | 53.159 | 0.000 | -52.903 | 0.000 | -5.092 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 406.862 | -370.058 | 0.000 | 0.000 | 116.524 | 265.697 | 403.423 | 224.258 | 0.000 | 0.086 | 0.000 | 0.000 | -736.777 | 0.000 | -158.759 | -151.257 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 262.447 | -497.494 | 0.000 | 0.000 | 55.260 | 171.225 | 259.981 | 508.544 | 0.000 | 0.065 | 0.006 | 0.000 | -468.340 | 0.000 | -106.581 | -185.108 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 309.150 | -879.496 | 0.000 | 0.000 | 115.684 | 265.703 | 403.429 | 998.407 | 0.000 | 0.085 | 0.009 | 0.000 | -676.750 | 0.000 | -163.968 | -372.244 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 211.857 | -433.423 | 0.000 | 0.000 | 76.040 | 171.225 | 259.979 | 354.685 | 0.000 | 0.055 | 0.000 | 0.000 | -487.349 | 0.000 | -108.603 | -44.466 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 86.618 | -32.982 | 0.000 | 0.000 | 11.849 | 26.570 | 40.342 | 23.001 | 0.000 | 0.010 | 0.001 | 0.000 | -70.866 | 0.000 | -18.892 | -65.651 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 53.393 | -44.129 | 0.000 | 0.000 | 7.570 | 17.123 | 25.998 | 51.190 | 0.000 | 0.007 | 0.001 | 0.000 | -45.249 | 0.000 | -12.773 | -53.129 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 68.789 | -76.879 | 0.000 | 0.000 | 11.720 | 26.570 | 40.343 | 100.483 | 0.000 | 0.010 | 0.001 | 0.000 | -65.158 | 0.000 | -19.554 | -86.324 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 45.628 | -38.297 | 0.000 | 0.000 | 7.689 | 17.123 | 25.998 | 35.727 | 0.000 | 0.006 | 0.001 | 0.000 | -47.126 | 0.000 | -13.009 | -33.738 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.249 | -127.411 | 0.000 | 0.000 | 0.951 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -32.040 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.186 | -1066.668 | 0.000 | 0.000 | 9.572 | 43.701 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -532.598 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.282 | -92.395 | 0.000 | 0.000 | 0.966 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -68.103 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7122.327 | 0.000 | 0.000 | 20.557 | 66.437 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -459.524 |
GROUNDFLOOR_PLENUM | 14.950 | -44.886 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.005 | 45.066 | 0.000 | 0.000 | 0.000 | -15.135 | -0.000 |
MIDFLOOR_PLENUM | 317.642 | -333.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.090 | 278.170 | 0.000 | 0.000 | 0.000 | -262.531 | -0.001 |
TOPFLOOR_PLENUM | 136.986 | -31.246 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.006 | 0.001 | 0.000 | 0.000 | 0.000 | -28.480 | -77.266 |
Total Facility | 469.578 | -409.504 | 1573.569 | -16494.660 | 0.000 | 0.000 | 1612.816 | 3942.443 | 15213.411 | 2503.715 | 0.000 | 0.440 | 406.276 | 0.000 | -2845.579 | 0.000 | -932.532 | -5039.954 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-AUG-21:42 | 0.00 | 0.00 | 0.00 | -115708.82 | 0.00 | 0.00 | 0.00 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 101108.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-JUL-03:02 | 0.00 | 0.00 | 0.00 | -96051.60 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.15 | 0.00 | 0.00 | 0.00 | 86967.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-03:02 | 0.00 | 0.00 | 0.00 | -875422.20 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 784585.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-03:02 | 0.00 | 0.00 | 0.00 | -84589.92 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 75506.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-05:03 | 0.00 | 0.00 | 0.00 | -15479.30 | 0.00 | 0.00 | 89.72 | 257.76 | 1011.70 | 12652.76 | 0.00 | 0.00 | 1517.19 | 0.00 | -0.00 | 0.00 | -49.82 | 0.00 |
PERIMETER_BOT_ZN_2 | 14-MAY-08:51 | 0.00 | 0.00 | 0.00 | -23338.26 | 0.00 | 0.00 | 21.49 | 83.06 | 488.98 | 17961.62 | 0.00 | 0.00 | 5044.04 | 0.00 | -0.00 | 0.00 | -260.93 | 0.00 |
PERIMETER_BOT_ZN_1 | 27-AUG-12:41 | 0.00 | 0.00 | 0.00 | -36473.67 | 0.00 | 0.00 | 32.39 | 128.90 | 758.78 | 27425.65 | 0.00 | 0.00 | 8253.98 | 0.00 | -0.00 | 0.00 | -126.03 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-19:22 | 0.00 | 0.00 | 0.00 | -26046.97 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 11445.14 | 0.00 | 0.00 | 14161.10 | 0.00 | -0.00 | 0.00 | -131.31 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUL-05:05 | 0.00 | 0.00 | 0.00 | -138210.08 | 0.00 | 0.00 | 928.34 | 2577.57 | 10116.97 | 126228.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1033.99 | -607.05 |
PERIMETER_MID_ZN_2 | 23-JUL-09:41 | 0.00 | 0.00 | 0.00 | -260013.59 | 0.00 | 0.00 | 191.82 | 830.63 | 4889.82 | 167221.80 | 0.00 | 0.00 | 88771.56 | 0.00 | -0.00 | 0.00 | -1892.05 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:41 | 0.00 | 0.00 | 0.00 | -403594.92 | 0.00 | 0.00 | 277.77 | 1288.96 | 7587.84 | 247911.64 | 0.00 | 0.00 | 148146.29 | 0.00 | -0.00 | 0.00 | -1617.58 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:02 | 0.00 | 0.00 | 0.00 | -241305.72 | 0.00 | 0.00 | 0.00 | 830.63 | 4889.79 | 144973.63 | 0.00 | 0.00 | 98293.08 | 0.00 | -0.00 | 0.00 | -7681.41 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-05:02 | 0.00 | 0.00 | 0.00 | -17306.27 | 0.00 | 0.00 | 94.79 | 257.76 | 1011.70 | 12621.72 | 0.00 | 0.00 | 3470.59 | 0.00 | -0.00 | 0.00 | -150.29 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-10:11 | 0.00 | 0.00 | 0.00 | -24349.57 | 0.00 | 0.00 | 21.40 | 83.06 | 488.98 | 12304.98 | 0.00 | 0.00 | 12021.64 | 0.00 | -0.00 | 0.00 | -570.49 | 0.00 |
PERIMETER_TOP_ZN_1 | 27-AUG-13:11 | 0.00 | 0.00 | 0.00 | -39889.81 | 0.00 | 0.00 | 31.10 | 128.90 | 758.78 | 26322.34 | 0.00 | 0.00 | 13061.53 | 0.00 | -0.00 | 0.00 | -412.84 | 0.00 |
PERIMETER_TOP_ZN_4 | 27-AUG-17:51 | 0.00 | 0.00 | 0.00 | -23871.68 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 13317.21 | 0.00 | 0.00 | 10508.79 | 0.00 | -0.00 | 0.00 | -526.36 | 0.00 |
DATACENTER_BOT_ZN_6 | 20-APR-18:50 | 0.00 | 0.00 | 0.00 | -8539.59 | 0.00 | 0.00 | 10.62 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 607.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 20-APR-18:50 | 0.00 | 0.00 | 0.00 | -81356.51 | 0.00 | 0.00 | 106.16 | 1271.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 2034.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 20-APR-18:50 | 0.00 | 0.00 | 0.00 | -8126.40 | 0.00 | 0.00 | 10.62 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 194.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-16:00 | 0.00 | 0.00 | 0.00 | -368878.35 | 0.00 | 0.00 | 2183.09 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18738.17 |
GROUNDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -12108.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12190.14 | 0.00 | -0.00 | 0.00 | -82.10 | 0.00 |
MIDFLOOR_PLENUM | 28-JAN-04:01 | 0.00 | -99728.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151818.40 | 0.00 | -0.00 | 0.00 | -52089.62 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:50 | 0.00 | -15596.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 | 15566.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-05:02 | 0.00 | 25117.73 | 0.00 | -1971482.11 | 0.00 | 0.00 | 15469.51 | 38246.31 | 504945.49 | 328642.11 | 0.00 | 0.00 | 1069054.95 | 0.00 | -3733.57 | 0.00 | -6260.42 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:03 | 0.00 | 0.00 | 16649.52 | 0.00 | 0.00 | 0.00 | 520.12 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31770.24 |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 21775.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2052.86 | 8057.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31885.22 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 600995.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -691831.73 |
CORE_TOP | 01-JAN-22:42 | 0.00 | 0.00 | 81741.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.54 | 6042.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88811.27 |
PERIMETER_BOT_ZN_3 | 30-JAN-04:01 | 0.00 | 0.00 | 13976.94 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5328.55 | 0.00 | -1050.35 | -8738.62 |
PERIMETER_BOT_ZN_2 | 30-JAN-04:01 | 0.00 | 0.00 | 16329.61 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3470.36 | 0.00 | -703.39 | -12890.90 |
PERIMETER_BOT_ZN_1 | 30-JAN-04:01 | 0.00 | 0.00 | 25566.59 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5145.89 | 0.00 | -1050.19 | -20511.12 |
PERIMETER_BOT_ZN_4 | 30-JAN-04:01 | 0.00 | 0.00 | 13952.03 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3667.39 | 0.00 | -723.20 | -10296.48 |
PERIMETER_MID_ZN_3 | 29-JAN-15:02 | 0.00 | 0.00 | 139969.77 | 0.00 | 0.00 | 0.00 | 909.54 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45579.02 | 0.00 | -34071.06 | -70105.88 |
PERIMETER_MID_ZN_2 | 29-JAN-00:21 | 0.00 | 0.00 | 200648.45 | 0.00 | 0.00 | 0.00 | 0.00 | 830.63 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35313.74 | 0.00 | -47984.36 | -123070.80 |
PERIMETER_MID_ZN_1 | 01-JAN-07:22 | 0.00 | 0.00 | 301211.90 | 0.00 | 0.00 | 0.00 | 902.35 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37129.93 | 0.00 | -17187.51 | -256673.61 |
PERIMETER_MID_ZN_4 | 29-JAN-15:02 | 0.00 | 0.00 | 196543.26 | 0.00 | 0.00 | 0.00 | 582.68 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29587.39 | 0.00 | -23474.68 | -149784.30 |
PERIMETER_TOP_ZN_3 | 29-JAN-00:01 | 0.00 | 0.00 | 18140.86 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5127.94 | 0.00 | -8889.55 | -5011.03 |
PERIMETER_TOP_ZN_2 | 29-JAN-00:01 | 0.00 | 0.00 | 20833.63 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3425.09 | 0.00 | -6024.61 | -11955.98 |
PERIMETER_TOP_ZN_1 | 29-JAN-00:01 | 0.00 | 0.00 | 32631.07 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5024.81 | 0.00 | -9093.93 | -19400.01 |
PERIMETER_TOP_ZN_4 | 29-JAN-00:01 | 0.00 | 0.00 | 21864.09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3351.22 | 0.00 | -6060.51 | -13024.40 |
DATACENTER_BOT_ZN_6 | 29-JAN-22:23 | 0.00 | 0.00 | 581.93 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2551.73 |
DATACENTER_MID_ZN_6 | 12-JAN-22:13 | 0.00 | 0.00 | 5826.48 | 0.00 | 0.00 | 0.00 | 55.34 | 423.97 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25791.85 |
DATACENTER_TOP_ZN_6 | 10-JAN-00:20 | 0.00 | 0.00 | 607.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2577.68 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 07-APR-04:01 | 13238.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3087.37 | -10150.91 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 235738.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1943.30 | -233795.01 |
TOPFLOOR_PLENUM | 27-FEB-05:41 | 36354.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36354.90 |
Total Facility | 02-JAN-04:01 | -26835.91 | 88465.55 | 1666889.47 | -88465.55 | 0.00 | 0.00 | 0.00 | 19125.25 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -148218.49 | 0.00 | -63398.94 | -1715924.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.6997 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8830 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 112.8999 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.2334 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.5284 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7258 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7258 | 0.2096 | 1.0000 | Not calculated | 1.2002 | 0.2096 | ||
AIRLOOP DATACENTER BASEMENT | 21.7393 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.7394 | 0.0156 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5132 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5132 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9256 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9256 | 0.0317 | 1.0000 | Not calculated | 0.1563 | 0.0317 | ||
AIRLOOP DATACENTER TOP | 0.4972 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4972 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.8498 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5099 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 56.4499 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.8700 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.7642 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4585 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7258 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7258 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2096 | ||
AIRLOOP DATACENTER BASEMENT | 21.7393 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.7393 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.5132 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5132 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9256 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9256 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0317 | ||
AIRLOOP DATACENTER TOP | 0.4972 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4972 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7258 | 5.7258 | 5.7258 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0564 | 6.0564 | 1.8169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.0509 | 57.0509 | 17.1153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5989 | 5.5989 | 1.6797 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9716 | 0.9716 | 0.2915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2586 | 1.2586 | 0.3776 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9269 | 1.9269 | 0.5781 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4862 | 1.4862 | 0.4459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.9297 | 8.9297 | 2.6789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2478 | 13.2478 | 3.9743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 20.1720 | 20.1720 | 6.0516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.4994 | 13.4994 | 4.0498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1232 | 1.1232 | 0.3370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3186 | 1.3186 | 0.3956 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0899 | 2.0899 | 0.6270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3978 | 1.3978 | 0.4193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5132 | 0.5132 | 0.5132 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9256 | 4.9256 | 4.9256 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4972 | 0.4972 | 0.4972 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.7393 | 21.7393 | 21.7393 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.6997 | 9.8830 | 11.6997 | 3.5099 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 112.8999 | 92.2334 | 112.8999 | 33.8700 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.5284 | 9.7513 | 11.5284 | 3.4585 | 0.0000 | 1.0000 |
CAV_BAS | 5.7258 | 5.7258 | 5.7258 | 5.7258 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7393 | 21.7394 | 21.7393 | 21.7393 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5132 | 0.5132 | 0.5132 | 0.5132 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9256 | 4.9256 | 4.9256 | 4.9256 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4972 | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7258 | 5.7258 | 5.7258 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0282 | 3.0282 | 1.8169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.5255 | 28.5255 | 17.1153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7994 | 2.7994 | 1.6797 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4858 | 0.4858 | 0.2915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6293 | 0.6293 | 0.3776 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9635 | 0.9635 | 0.5781 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7431 | 0.7431 | 0.4459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4648 | 4.4648 | 2.6789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6239 | 6.6239 | 3.9743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0860 | 10.0860 | 6.0516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7497 | 6.7497 | 4.0498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5616 | 0.5616 | 0.3370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6593 | 0.6593 | 0.3956 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0449 | 1.0449 | 0.6270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6989 | 0.6989 | 0.4193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5132 | 0.5132 | 0.5132 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9256 | 4.9256 | 4.9256 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4972 | 0.4972 | 0.4972 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.7393 | 21.7393 | 21.7393 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.8498 | 3.5099 | 3.5099 | 3.5099 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 56.4499 | 33.8700 | 33.8700 | 33.8700 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.7642 | 3.4585 | 3.4585 | 3.4585 | 0.0000 | 1.0000 |
CAV_BAS | 5.7258 | 5.7258 | 5.7258 | 5.7258 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7393 | 21.7393 | 21.7393 | 21.7393 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5132 | 0.5132 | 0.5132 | 0.5132 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9256 | 4.9256 | 4.9256 | 4.9256 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4972 | 0.4972 | 0.4972 | 0.4972 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 255.67 |
Number of hours cooling loads not met | 67.17 |
Number of hours not met | 322.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 7893.41 | 3841258.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2589.67 | 377653.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3942.44 | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 897.74 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.51 | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2461.79 | 284369.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 310.97 | 62306.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 554.23 | 81628.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 228.61 | 23714.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 44.42 | 4264.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 942.50 | 90199.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 28240.88 |
Natural Gas | 0.00 | 8835.91 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 37076.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.11 |
Space Heating | 0.00 |
Space Cooling | 55.91 |
Fans (All) | 53.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 609.69 |
Subtotal | 609.69 |
Natural Gas [MJ/m2] | |
Space Heating | 170.41 |
Service Water Heating | 20.35 |
Miscellaneous (All) | 190.76 |
Subtotal | 190.76 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.63 |
Space Heating | 21.29 |
Space Cooling | 6.98 |
Fans (All) | 6.64 |
Service Water Heating | 2.54 |
Receptacle Equipment | 41.03 |
Miscellaneous | 10.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8650.83 | 109.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8626.33 | 133.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
Min | 8626.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 133.67 | 0.00 | 0.00 | 0.00 |
Average | 8744.10 | 15.90 | 0.00 | 0.00 | 0.00 |
Sum | 201114.33 | 365.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368306.83 | 309.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103035.17 | 359.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368306.83 | 359.83 | 0.00 | 0.00 | 0.00 |
Average | 80305.83 | 29.09 | 0.00 | 0.00 | 0.00 |
Sum | 1847034.00 | 669.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8575.67 | 184.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8683.83 | 76.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8691.83 | 68.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8649.50 | 110.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8575.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 184.33 | 0.00 | 0.00 | 0.00 |
Average | 8734.46 | 25.54 | 0.00 | 0.00 | 0.00 |
Sum | 200892.50 | 587.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368133.00 | 483.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330695.00 | 118.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330710.00 | 103.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330771.00 | 42.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368133.00 | 483.00 | 0.00 | 0.00 | 0.00 |
Average | 80302.48 | 32.43 | 0.00 | 0.00 | 0.00 |
Sum | 1846957.00 | 746.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490226E+11 | 75276.36 | 12-JAN-07:01 | -38.3 | -38.4 | 0.437938E+10 | 6559.90 | 23-JAN-14:30 | -9.8 | -10.3 |
February | 0.440852E+11 | 101953.32 | 13-FEB-06:01 | -16.3 | -16.6 | 0.435170E+10 | 7499.03 | 08-FEB-14:00 | -16.3 | -16.6 |
March | 0.522591E+11 | 105457.72 | 20-MAR-04:01 | -4.5 | -5.7 | 0.563577E+10 | 7499.09 | 22-MAR-13:39 | 5.20 | 1.80 |
April | 0.501337E+11 | 110454.70 | 24-APR-03:02 | -2.8 | -5.4 | 0.541926E+10 | 7499.14 | 14-APR-13:30 | -2.8 | -5.4 |
May | 0.553752E+11 | 111289.56 | 01-MAY-03:02 | 6.70 | 2.21 | 0.589800E+10 | 7499.05 | 19-MAY-09:20 | 12.60 | 7.05 |
June | 0.588390E+11 | 113088.88 | 05-JUN-03:02 | 10.50 | 8.79 | 0.588047E+10 | 7499.05 | 30-JUN-09:20 | 17.93 | 15.10 |
July | 0.607112E+11 | 114112.12 | 03-JUL-03:02 | 10.50 | 10.21 | 0.547339E+10 | 7500.47 | 19-JUL-09:20 | 17.57 | 14.42 |
August | 0.677575E+11 | 115711.29 | 06-AUG-21:42 | 12.30 | 10.96 | 0.613752E+10 | 7499.02 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.560515E+11 | 112433.24 | 18-SEP-03:02 | 3.03 | 1.93 | 0.544929E+10 | 7499.19 | 08-SEP-13:20 | 3.03 | 1.93 |
October | 0.540022E+11 | 110521.18 | 16-OCT-03:01 | -1.1 | -1.3 | 0.557606E+10 | 7499.09 | 13-OCT-13:00 | -1.1 | -1.3 |
November | 0.576275E+11 | 102943.11 | 06-NOV-06:01 | -16.6 | -17.0 | 0.478859E+10 | 7227.81 | 02-NOV-13:00 | -16.6 | -17.0 |
December | 0.582472E+11 | 99324.75 | 26-DEC-06:03 | -12.1 | -12.4 | 0.430804E+10 | 7259.59 | 26-DEC-10:09 | -8.6 | -9.4 |
Annual Sum or Average | 0.664112E+12 | 0.632975E+11 | ||||||||
Minimum of Months | 0.440852E+11 | 75276.36 | -38.3 | -38.4 | 0.430804E+10 | 6559.90 | -16.6 | -17.0 | ||
Maximum of Months | 0.677575E+11 | 115711.29 | 12.30 | 10.96 | 0.613752E+10 | 7500.47 | 17.93 | 15.10 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238253E+11 | 21640.83 | 24-JAN-17:00 | -17.2 | -17.5 | 0.465600E+10 | 6734.51 | 23-JAN-14:09 | -17.2 | -17.5 |
February | 0.250937E+11 | 80073.22 | 10-FEB-06:01 | -9.5 | -10.1 | 0.444627E+10 | 6734.62 | 14-FEB-14:09 | -0.9 | -2.8 |
March | 0.378979E+11 | 87334.70 | 23-MAR-04:01 | -2.3 | -3.8 | 0.544742E+10 | 6734.73 | 22-MAR-13:39 | -2.3 | -3.8 |
April | 0.501592E+11 | 91848.20 | 24-APR-03:02 | -2.8 | -5.4 | 0.487920E+10 | 6734.78 | 24-APR-09:20 | 0.97 | -3.2 |
May | 0.548993E+11 | 92240.00 | 01-MAY-03:02 | 6.70 | 2.21 | 0.528515E+10 | 6734.75 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.616666E+11 | 94819.66 | 26-JUN-03:02 | 12.70 | 11.22 | 0.527218E+10 | 6734.77 | 30-JUN-09:09 | 17.57 | 14.96 |
July | 0.650833E+11 | 96054.39 | 05-JUL-03:02 | 8.30 | 7.78 | 0.489850E+10 | 6735.91 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.697986E+11 | 92309.27 | 08-AUG-03:02 | 12.70 | 11.82 | 0.549982E+10 | 6734.73 | 25-AUG-09:00 | 15.60 | 11.89 |
September | 0.455945E+11 | 95721.89 | 05-SEP-03:02 | 5.50 | 5.03 | 0.488277E+10 | 6734.85 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.391134E+11 | 89427.59 | 10-OCT-03:01 | -0.6 | -0.9 | 0.506034E+10 | 6734.77 | 13-OCT-13:00 | 1.10 | -2.4 |
November | 0.286523E+11 | 78489.79 | 02-NOV-05:01 | -11.0 | -11.4 | 0.494500E+10 | 6734.56 | 10-NOV-10:09 | -13.8 | -14.8 |
December | 0.263441E+11 | 30291.65 | 26-DEC-17:00 | -15.6 | -15.9 | 0.476195E+10 | 6734.59 | 29-DEC-10:09 | -11.6 | -12.1 |
Annual Sum or Average | 0.528128E+12 | 0.600346E+11 | ||||||||
Minimum of Months | 0.238253E+11 | 21640.83 | -17.2 | -17.5 | 0.444627E+10 | 6734.51 | -17.2 | -17.5 | ||
Maximum of Months | 0.697986E+11 | 96054.39 | 12.70 | 11.82 | 0.549982E+10 | 6735.91 | 17.57 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196667E+11 | 17078.06 | 27-JAN-17:00 | -12.2 | -12.5 | 0.424959E+10 | 6573.50 | 27-JAN-14:00 | -12.2 | -12.5 |
February | 0.207592E+11 | 23687.05 | 17-FEB-17:00 | -10.6 | -12.3 | 0.407790E+10 | 6734.55 | 14-FEB-14:39 | -10.6 | -12.3 |
March | 0.264735E+11 | 61530.92 | 23-MAR-05:02 | -2.8 | -4.2 | 0.520803E+10 | 6782.38 | 22-MAR-13:20 | -2.8 | -4.2 |
April | 0.318141E+11 | 80862.37 | 22-APR-05:02 | 0.00 | -1.8 | 0.478505E+10 | 6923.11 | 13-APR-09:00 | 0.00 | -1.8 |
May | 0.450702E+11 | 81693.41 | 11-MAY-04:02 | 3.48 | 0.36 | 0.527579E+10 | 6734.75 | 16-MAY-09:09 | 5.97 | 4.63 |
June | 0.499778E+11 | 83892.91 | 23-JUN-03:02 | 13.40 | 8.88 | 0.526822E+10 | 6734.76 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.485052E+11 | 87557.66 | 05-JUL-03:02 | 8.30 | 7.78 | 0.489635E+10 | 6735.76 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.486827E+11 | 86271.78 | 14-AUG-03:02 | 12.12 | 10.59 | 0.549545E+10 | 6734.73 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.345937E+11 | 81401.66 | 02-SEP-05:02 | 6.70 | 5.73 | 0.485298E+10 | 6823.19 | 15-SEP-09:30 | 4.15 | 2.95 |
October | 0.260263E+11 | 74429.67 | 06-OCT-05:03 | 6.60 | 2.71 | 0.484867E+10 | 6805.45 | 12-OCT-13:50 | -1.1 | -3.6 |
November | 0.208828E+11 | 19256.33 | 03-NOV-16:00 | -11.1 | -11.5 | 0.439608E+10 | 6716.56 | 03-NOV-13:00 | -11.1 | -11.5 |
December | 0.203918E+11 | 16430.20 | 22-DEC-17:00 | -21.7 | -22.0 | 0.411139E+10 | 6397.52 | 22-DEC-14:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.392844E+12 | 0.574655E+11 | ||||||||
Minimum of Months | 0.196667E+11 | 16430.20 | -21.7 | -22.0 | 0.407790E+10 | 6397.52 | -21.7 | -22.0 | ||
Maximum of Months | 0.499778E+11 | 87557.66 | 13.40 | 10.59 | 0.549545E+10 | 6923.11 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.884620E+10 | 13825.55 | 20-JAN-17:00 | -11.1 | -11.2 | 0.378984E+10 | 5686.42 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.108885E+11 | 15942.74 | 09-FEB-17:00 | -2.2 | -2.6 | 0.357736E+10 | 6323.68 | 09-FEB-14:00 | -2.2 | -2.6 |
March | 0.175993E+11 | 22139.22 | 22-MAR-16:00 | 5.60 | 2.61 | 0.453067E+10 | 6733.62 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.237046E+11 | 45941.52 | 28-APR-10:50 | 6.20 | 3.04 | 0.446797E+10 | 6739.91 | 06-APR-13:30 | 6.20 | 3.04 |
May | 0.383893E+11 | 74665.12 | 23-MAY-05:02 | 8.30 | 5.28 | 0.522522E+10 | 6747.00 | 26-MAY-13:50 | 7.30 | 3.23 |
June | 0.482819E+11 | 80888.95 | 23-JUN-04:02 | 14.08 | 9.52 | 0.526191E+10 | 6734.75 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.466136E+11 | 84589.43 | 24-JUL-03:02 | 13.72 | 12.61 | 0.489201E+10 | 6735.65 | 19-JUL-09:09 | 13.72 | 12.61 |
August | 0.432821E+11 | 81533.86 | 03-AUG-04:02 | 15.00 | 13.08 | 0.547024E+10 | 6746.04 | 22-AUG-09:30 | 9.45 | 7.38 |
September | 0.243325E+11 | 38504.50 | 08-SEP-10:20 | 7.57 | 4.06 | 0.463400E+10 | 6734.78 | 15-SEP-09:00 | 5.00 | 3.51 |
October | 0.166989E+11 | 24982.98 | 05-OCT-16:00 | 11.10 | 5.87 | 0.423893E+10 | 6734.43 | 05-OCT-13:09 | 11.10 | 5.87 |
November | 0.995898E+10 | 14126.82 | 02-NOV-16:00 | -8.9 | -9.4 | 0.379618E+10 | 5737.32 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.864084E+10 | 12864.87 | 21-DEC-17:00 | -16.7 | -17.3 | 0.362712E+10 | 5412.78 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.297237E+12 | 0.535115E+11 | ||||||||
Minimum of Months | 0.864084E+10 | 12864.87 | -16.7 | -17.3 | 0.357736E+10 | 5412.78 | -16.7 | -17.3 | ||
Maximum of Months | 0.482819E+11 | 84589.43 | 15.00 | 13.08 | 0.547024E+10 | 6747.00 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154164E+09 | 1924.33 | 20-JAN-06:04 | -7.6 | -7.8 | 0.465621E+09 | 625.94 | 31-JAN-10:39 | -23.3 | -23.8 |
February | 0.874779E+09 | 2741.93 | 09-FEB-06:02 | 0.00 | -0.5 | 0.432445E+09 | 724.50 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.239666E+10 | 3615.52 | 22-MAR-14:00 | 5.60 | 1.90 | 0.561759E+09 | 845.62 | 22-MAR-13:39 | 5.60 | 1.90 |
April | 0.470453E+10 | 6268.93 | 28-APR-14:00 | 11.70 | 4.88 | 0.580129E+09 | 845.63 | 24-APR-09:20 | 11.70 | 4.88 |
May | 0.742489E+10 | 13822.34 | 31-MAY-05:02 | 12.07 | 7.63 | 0.660396E+09 | 845.63 | 19-MAY-13:39 | 12.07 | 7.63 |
June | 0.108327E+11 | 15059.13 | 16-JUN-03:42 | 8.40 | 7.27 | 0.661772E+09 | 845.64 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.108868E+11 | 15479.65 | 11-JUL-05:03 | 15.18 | 11.97 | 0.615158E+09 | 845.84 | 11-JUL-13:50 | 25.10 | 15.96 |
August | 0.941494E+10 | 12971.61 | 07-AUG-05:03 | 10.60 | 10.26 | 0.688611E+09 | 845.63 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.451044E+10 | 6089.04 | 01-SEP-13:40 | 14.63 | 10.60 | 0.588655E+09 | 845.64 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.286666E+10 | 3824.06 | 04-OCT-14:40 | 11.10 | 4.80 | 0.545393E+09 | 845.60 | 05-OCT-13:09 | 10.10 | 5.15 |
November | 0.767128E+09 | 2189.48 | 02-NOV-14:10 | -8.9 | -9.5 | 0.466037E+09 | 685.88 | 02-NOV-13:00 | -8.9 | -9.5 |
December | 0.216214E+09 | 1921.44 | 26-DEC-12:00 | -10.6 | -11.5 | 0.450734E+09 | 631.18 | 26-DEC-10:00 | -10.6 | -11.5 |
Annual Sum or Average | 0.550499E+11 | 0.671671E+10 | ||||||||
Minimum of Months | 0.154164E+09 | 1921.44 | -10.6 | -11.5 | 0.432445E+09 | 625.94 | -23.3 | -23.8 | ||
Maximum of Months | 0.108868E+11 | 15479.65 | 15.18 | 11.97 | 0.688611E+09 | 845.84 | 25.10 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89287838.54 | 2499.79 | 07-JAN-06:03 | -6.8 | -6.9 | 0.299815E+09 | 403.42 | 11-JAN-14:20 | -33.7 | -33.8 |
February | 0.845799E+09 | 3161.60 | 15-FEB-10:50 | -16.0 | -16.2 | 0.276096E+09 | 476.87 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.321057E+10 | 7049.42 | 27-MAR-09:40 | -10.2 | -12.2 | 0.370893E+09 | 544.95 | 22-MAR-09:39 | -10.2 | -12.2 |
April | 0.575281E+10 | 11385.03 | 23-APR-10:52 | 10.00 | 3.85 | 0.369931E+09 | 544.95 | 21-APR-09:00 | 10.00 | 3.85 |
May | 0.959190E+10 | 23338.93 | 14-MAY-08:51 | 15.00 | 7.79 | 0.424223E+09 | 545.86 | 30-MAY-09:00 | 15.00 | 8.95 |
June | 0.104234E+11 | 21623.75 | 04-JUN-09:12 | 16.33 | 10.97 | 0.424479E+09 | 546.25 | 08-JUN-09:30 | 16.15 | 10.27 |
July | 0.107693E+11 | 21389.62 | 23-JUL-10:02 | 21.38 | 14.90 | 0.393935E+09 | 546.63 | 07-JUL-09:30 | 21.38 | 14.90 |
August | 0.948187E+10 | 16658.34 | 27-AUG-10:42 | 13.53 | 10.98 | 0.439487E+09 | 546.12 | 11-AUG-09:30 | 13.53 | 10.98 |
September | 0.515748E+10 | 13655.87 | 10-SEP-10:52 | 14.40 | 7.80 | 0.366422E+09 | 544.97 | 08-SEP-13:09 | 14.40 | 7.80 |
October | 0.300155E+10 | 6824.62 | 03-OCT-09:45 | 3.43 | 2.35 | 0.334600E+09 | 544.95 | 03-OCT-09:20 | 3.43 | 2.35 |
November | 0.339703E+09 | 2524.87 | 02-NOV-05:02 | -11.0 | -11.4 | 0.297979E+09 | 403.40 | 30-NOV-10:20 | -28.5 | -28.7 |
December | 51480655.20 | 2492.21 | 18-DEC-06:04 | -16.7 | -17.1 | 0.289759E+09 | 403.42 | 15-DEC-10:39 | -16.7 | -17.1 |
Annual Sum or Average | 0.587152E+11 | 0.428762E+10 | ||||||||
Minimum of Months | 51480655.20 | 2492.21 | -16.7 | -17.1 | 0.276096E+09 | 403.40 | -33.7 | -33.8 | ||
Maximum of Months | 0.107693E+11 | 23338.93 | 21.38 | 14.90 | 0.439487E+09 | 546.63 | 21.38 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450049E+09 | 4678.58 | 25-JAN-13:30 | -19.8 | -20.0 | 0.466782E+09 | 709.96 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.235026E+10 | 10714.89 | 15-FEB-13:30 | -8.9 | -9.7 | 0.451357E+09 | 845.64 | 14-FEB-14:09 | -8.9 | -9.7 |
March | 0.686344E+10 | 16870.92 | 31-MAR-13:30 | -11.4 | -13.3 | 0.595138E+09 | 845.64 | 31-MAR-13:20 | -11.4 | -13.3 |
April | 0.120464E+11 | 32686.50 | 23-APR-12:12 | 10.00 | 3.78 | 0.573382E+09 | 845.99 | 27-APR-13:00 | 11.10 | 4.54 |
May | 0.136655E+11 | 33763.47 | 14-MAY-11:32 | 17.60 | 9.36 | 0.646109E+09 | 847.24 | 12-MAY-13:50 | 17.60 | 9.36 |
June | 0.154104E+11 | 32577.85 | 04-JUN-13:52 | 18.90 | 11.87 | 0.654958E+09 | 846.15 | 16-JUN-13:00 | 19.40 | 10.50 |
July | 0.163182E+11 | 34071.90 | 23-JUL-13:22 | 25.00 | 15.26 | 0.608724E+09 | 847.42 | 20-JUL-13:50 | 25.00 | 15.26 |
August | 0.165872E+11 | 36479.14 | 27-AUG-12:41 | 17.62 | 13.43 | 0.678912E+09 | 847.01 | 31-AUG-13:00 | 13.30 | 4.88 |
September | 0.935237E+10 | 25347.20 | 10-SEP-10:52 | 14.40 | 7.80 | 0.565115E+09 | 845.69 | 08-SEP-13:09 | 14.40 | 7.80 |
October | 0.534727E+10 | 17978.18 | 03-OCT-13:30 | 10.85 | 6.24 | 0.531043E+09 | 845.64 | 13-OCT-13:00 | 1.10 | -2.4 |
November | 0.128304E+10 | 7374.13 | 08-NOV-13:30 | -13.6 | -14.4 | 0.470617E+09 | 845.63 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 0.132928E+09 | 3554.15 | 23-DEC-17:02 | -2.6 | -3.4 | 0.449264E+09 | 626.02 | 04-DEC-10:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.998070E+11 | 0.669140E+10 | ||||||||
Minimum of Months | 0.132928E+09 | 3554.15 | -19.8 | -20.0 | 0.449264E+09 | 626.02 | -18.9 | -19.2 | ||
Maximum of Months | 0.165872E+11 | 36479.14 | 25.00 | 15.26 | 0.678912E+09 | 847.42 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.760385E+09 | 3003.13 | 07-JAN-06:03 | -6.8 | -6.9 | 0.301129E+09 | 403.42 | 12-JAN-10:20 | -37.9 | -38.0 |
February | 0.236920E+10 | 4871.56 | 09-FEB-06:02 | 0.00 | -0.5 | 0.283085E+09 | 491.07 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.520597E+10 | 8000.72 | 27-MAR-16:00 | -4.4 | -7.8 | 0.379835E+09 | 544.95 | 22-MAR-13:39 | -4.4 | -7.8 |
April | 0.943131E+10 | 24009.72 | 22-APR-17:04 | 14.13 | 6.18 | 0.385560E+09 | 544.95 | 14-APR-13:30 | 14.13 | 6.18 |
May | 0.908281E+10 | 25407.57 | 29-MAY-18:42 | 13.98 | 8.09 | 0.419499E+09 | 544.96 | 19-MAY-13:39 | 13.98 | 8.09 |
June | 0.121926E+11 | 25479.69 | 11-JUN-16:52 | 18.90 | 11.02 | 0.426493E+09 | 544.97 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.130118E+11 | 26048.04 | 09-JUL-19:22 | 19.70 | 13.07 | 0.396882E+09 | 545.07 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.132496E+11 | 25948.49 | 27-AUG-17:22 | 20.85 | 12.52 | 0.445184E+09 | 544.96 | 28-AUG-09:00 | 12.20 | 8.79 |
September | 0.619702E+10 | 12765.01 | 01-SEP-03:02 | 7.88 | 7.33 | 0.364333E+09 | 544.95 | 01-SEP-09:00 | 10.60 | 8.83 |
October | 0.460745E+10 | 6632.17 | 03-OCT-14:50 | 12.62 | 6.87 | 0.347301E+09 | 544.79 | 03-OCT-13:00 | 12.62 | 6.87 |
November | 0.294538E+10 | 4652.71 | 02-NOV-05:01 | -11.0 | -11.4 | 0.308140E+09 | 479.75 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.256575E+10 | 3653.31 | 26-DEC-05:01 | -12.2 | -12.5 | 0.295271E+09 | 435.50 | 26-DEC-10:00 | -10.0 | -10.8 |
Annual Sum or Average | 0.816192E+11 | 0.435271E+10 | ||||||||
Minimum of Months | 0.760385E+09 | 3003.13 | -12.2 | -12.5 | 0.283085E+09 | 403.42 | -37.9 | -38.0 | ||
Maximum of Months | 0.132496E+11 | 26048.04 | 20.85 | 13.07 | 0.445184E+09 | 545.07 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14551199.49 | 1647.07 | 21-JAN-17:02 | -5.5 | -5.8 | 0.462523E+09 | 626.00 | 02-JAN-10:50 | -5.5 | -5.8 |
February | 0.120406E+09 | 1776.89 | 10-FEB-16:20 | 1.67 | -1.1 | 0.420764E+09 | 626.25 | 09-FEB-14:20 | 1.67 | -1.1 |
March | 0.698153E+09 | 2793.32 | 22-MAR-16:10 | 5.60 | 2.47 | 0.514349E+09 | 773.69 | 22-MAR-13:39 | 5.60 | 2.47 |
April | 0.241684E+10 | 4491.25 | 28-APR-14:00 | 11.70 | 4.88 | 0.520340E+09 | 845.60 | 27-APR-13:09 | 11.70 | 4.88 |
May | 0.575488E+10 | 12580.94 | 31-MAY-04:42 | 11.78 | 7.46 | 0.653365E+09 | 845.63 | 19-MAY-13:39 | 11.78 | 7.46 |
June | 0.912002E+10 | 13748.61 | 29-JUN-04:52 | 12.20 | 10.91 | 0.660678E+09 | 845.93 | 30-JUN-13:00 | 27.20 | 16.69 |
July | 0.841753E+10 | 13821.22 | 11-JUL-05:05 | 15.18 | 11.97 | 0.614357E+09 | 845.83 | 07-JUL-13:00 | 15.18 | 11.97 |
August | 0.631529E+10 | 9480.78 | 05-AUG-05:03 | 13.98 | 12.01 | 0.680318E+09 | 845.62 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.302763E+10 | 4548.03 | 25-SEP-13:50 | 4.32 | 1.11 | 0.549126E+09 | 845.63 | 08-SEP-13:09 | 4.32 | 1.11 |
October | 0.107995E+10 | 4379.33 | 10-OCT-15:50 | 2.70 | 0.20 | 0.485325E+09 | 777.54 | 04-OCT-13:00 | 2.70 | 0.20 |
November | 23611418.01 | 1648.25 | 04-NOV-16:02 | -9.6 | -11.3 | 0.459197E+09 | 625.96 | 27-NOV-14:00 | -23.9 | -24.2 |
December | 17046389.01 | 1640.21 | 23-DEC-17:02 | -2.6 | -3.4 | 0.446580E+09 | 626.03 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.370059E+11 | 0.646692E+10 | ||||||||
Minimum of Months | 14551199.49 | 1640.21 | -9.6 | -11.3 | 0.420764E+09 | 625.96 | -23.9 | -24.2 | ||
Maximum of Months | 0.912002E+10 | 13821.22 | 15.18 | 12.01 | 0.680318E+09 | 845.93 | 27.20 | 16.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28679903.15 | 2711.61 | 18-JAN-06:04 | -20.0 | -20.2 | 0.218809E+09 | 385.91 | 10-JAN-16:00 | -20.0 | -20.2 |
February | 0.263328E+09 | 2734.95 | 15-FEB-11:30 | -13.6 | -14.0 | 0.199123E+09 | 400.59 | 15-FEB-11:39 | -13.0 | -13.4 |
March | 0.196798E+10 | 5445.23 | 22-MAR-10:30 | 2.25 | 0.43 | 0.251435E+09 | 521.21 | 31-MAR-10:20 | -15.7 | -17.0 |
April | 0.432168E+10 | 13669.54 | 13-APR-10:10 | -0.3 | -3.3 | 0.255069E+09 | 536.38 | 13-APR-10:00 | 1.10 | -2.2 |
May | 0.917304E+10 | 24794.69 | 21-MAY-09:01 | 12.30 | 5.76 | 0.308423E+09 | 522.45 | 11-MAY-10:30 | 12.30 | 5.76 |
June | 0.100770E+11 | 18377.78 | 08-JUN-05:02 | 8.48 | 6.28 | 0.309971E+09 | 522.56 | 13-JUN-10:50 | 22.02 | 12.32 |
July | 0.998437E+10 | 25999.12 | 23-JUL-09:41 | 20.63 | 14.69 | 0.288664E+09 | 522.72 | 11-JUL-10:00 | 20.63 | 14.69 |
August | 0.817015E+10 | 15402.96 | 10-AUG-09:00 | 14.40 | 10.07 | 0.318331E+09 | 533.14 | 31-AUG-07:00 | 2.20 | -1.1 |
September | 0.423756E+10 | 17303.25 | 10-SEP-10:02 | 13.07 | 7.24 | 0.250384E+09 | 527.87 | 28-SEP-10:39 | 1.47 | -1.1 |
October | 0.146448E+10 | 6181.11 | 03-OCT-10:20 | 4.63 | 3.18 | 0.227694E+09 | 522.01 | 03-OCT-10:50 | 5.73 | 3.91 |
November | 30082271.23 | 2666.69 | 14-NOV-06:04 | -15.6 | -15.9 | 0.216832E+09 | 385.84 | 28-NOV-09:39 | -28.9 | -29.1 |
December | 30895606.54 | 2669.98 | 20-DEC-06:04 | -15.8 | -16.1 | 0.210948E+09 | 385.91 | 27-DEC-13:00 | -23.9 | -24.1 |
Annual Sum or Average | 0.497493E+11 | 0.305568E+10 | ||||||||
Minimum of Months | 28679903.15 | 2666.69 | -20.0 | -20.2 | 0.199123E+09 | 385.84 | -28.9 | -29.1 | ||
Maximum of Months | 0.100770E+11 | 25999.12 | 20.63 | 14.69 | 0.318331E+09 | 536.38 | 22.02 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299412E+09 | 4644.55 | 25-JAN-13:40 | -19.5 | -19.7 | 0.464673E+09 | 689.68 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.181156E+10 | 10369.29 | 15-FEB-13:40 | -8.7 | -9.6 | 0.442527E+09 | 845.64 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.576167E+10 | 18026.48 | 31-MAR-13:50 | -11.2 | -13.1 | 0.575730E+09 | 873.23 | 22-MAR-13:20 | -11.2 | -13.1 |
April | 0.104875E+11 | 33203.84 | 09-APR-14:42 | 3.62 | -1.9 | 0.556776E+09 | 870.45 | 07-APR-13:30 | 3.62 | -1.9 |
May | 0.132695E+11 | 36381.04 | 21-MAY-13:02 | 14.60 | 6.77 | 0.635061E+09 | 847.55 | 12-MAY-13:00 | 14.60 | 6.77 |
June | 0.144466E+11 | 26124.33 | 11-JUN-15:02 | 18.40 | 10.87 | 0.646653E+09 | 845.93 | 16-JUN-13:00 | 19.40 | 10.50 |
July | 0.144291E+11 | 40356.35 | 23-JUL-13:41 | 25.00 | 15.26 | 0.600584E+09 | 846.99 | 20-JUL-13:50 | 25.00 | 15.26 |
August | 0.142759E+11 | 35647.05 | 27-AUG-13:32 | 18.87 | 14.02 | 0.665002E+09 | 846.24 | 09-AUG-13:39 | 18.87 | 14.02 |
September | 0.864524E+10 | 25987.32 | 10-SEP-12:02 | 15.68 | 8.36 | 0.546072E+09 | 845.69 | 08-SEP-13:09 | 15.68 | 8.36 |
October | 0.384601E+10 | 19056.77 | 13-OCT-13:50 | 0.92 | -2.5 | 0.506875E+09 | 892.15 | 12-OCT-13:50 | 0.92 | -2.5 |
November | 0.628525E+09 | 5999.12 | 08-NOV-14:00 | -13.3 | -14.1 | 0.464170E+09 | 836.60 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 48842316.02 | 4063.25 | 20-DEC-06:04 | -15.8 | -16.1 | 0.447242E+09 | 626.14 | 22-DEC-10:00 | -24.4 | -24.7 |
Annual Sum or Average | 0.879499E+11 | 0.655136E+10 | ||||||||
Minimum of Months | 48842316.02 | 4063.25 | -19.5 | -19.7 | 0.442527E+09 | 626.14 | -24.4 | -24.7 | ||
Maximum of Months | 0.144466E+11 | 40356.35 | 25.00 | 15.26 | 0.665002E+09 | 892.15 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31269174.87 | 2791.35 | 18-JAN-06:04 | -20.0 | -20.2 | 0.299075E+09 | 403.46 | 30-JAN-10:20 | -25.4 | -25.8 |
February | 0.264871E+09 | 2754.92 | 09-FEB-06:03 | 0.00 | -0.5 | 0.271956E+09 | 408.40 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.139852E+10 | 4422.90 | 22-MAR-16:10 | 5.60 | 2.47 | 0.331798E+09 | 500.57 | 22-MAR-15:39 | 5.60 | 2.47 |
April | 0.470411E+10 | 15860.90 | 13-APR-17:08 | 5.68 | 1.20 | 0.330816E+09 | 540.61 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.690765E+10 | 23036.44 | 21-MAY-18:22 | 16.10 | 7.39 | 0.396577E+09 | 544.95 | 22-MAY-13:09 | 17.30 | 8.40 |
June | 0.893008E+10 | 24130.18 | 11-JUN-17:02 | 18.80 | 10.99 | 0.417570E+09 | 544.97 | 29-JUN-13:20 | 24.80 | 15.87 |
July | 0.827710E+10 | 22958.42 | 08-JUL-18:32 | 20.00 | 15.32 | 0.386437E+09 | 544.97 | 07-JUL-13:09 | 20.00 | 15.32 |
August | 0.733010E+10 | 18516.46 | 27-AUG-17:32 | 20.77 | 12.41 | 0.420176E+09 | 544.95 | 28-AUG-13:09 | 18.30 | 12.24 |
September | 0.401676E+10 | 8512.65 | 02-SEP-17:14 | 16.70 | 10.26 | 0.326910E+09 | 524.32 | 01-SEP-13:00 | 16.70 | 10.26 |
October | 0.135638E+10 | 6549.71 | 10-OCT-15:50 | 2.70 | 0.20 | 0.306624E+09 | 496.98 | 12-OCT-15:39 | -0.6 | -3.0 |
November | 84948867.86 | 2728.91 | 17-NOV-06:03 | -22.9 | -23.1 | 0.296509E+09 | 403.44 | 27-NOV-10:50 | -27.2 | -27.4 |
December | 40597881.86 | 2772.75 | 19-DEC-06:04 | -21.1 | -21.4 | 0.288411E+09 | 403.51 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.433424E+11 | 0.407286E+10 | ||||||||
Minimum of Months | 31269174.87 | 2728.91 | -22.9 | -23.1 | 0.271956E+09 | 403.44 | -27.2 | -27.4 | ||
Maximum of Months | 0.893008E+10 | 24130.18 | 20.77 | 15.32 | 0.420176E+09 | 544.97 | 24.80 | 15.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12185112.58 | 2018.25 | 21-JAN-17:02 | -5.5 | -5.8 | 0.459908E+09 | 626.08 | 12-JAN-10:00 | -5.5 | -5.8 |
February | 18614581.33 | 2024.30 | 11-FEB-17:02 | -1.2 | -2.7 | 0.418315E+09 | 626.06 | 24-FEB-10:20 | -25.2 | -25.7 |
March | 0.195122E+09 | 2593.21 | 22-MAR-16:00 | 5.60 | 2.61 | 0.504218E+09 | 677.44 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.190554E+10 | 3616.06 | 13-APR-12:08 | 2.98 | -1.4 | 0.478070E+09 | 825.20 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.518188E+10 | 9051.59 | 31-MAY-05:02 | 12.07 | 7.63 | 0.624208E+09 | 845.63 | 19-MAY-13:39 | 12.07 | 7.63 |
June | 0.880872E+10 | 16460.56 | 19-JUN-04:42 | 7.62 | 6.81 | 0.657740E+09 | 845.64 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.820175E+10 | 17305.56 | 11-JUL-05:02 | 15.18 | 11.97 | 0.610788E+09 | 845.73 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.592864E+10 | 7734.17 | 02-AUG-15:40 | 22.93 | 14.75 | 0.659408E+09 | 845.62 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.230973E+10 | 3397.86 | 01-SEP-16:00 | 15.60 | 10.82 | 0.489447E+09 | 824.32 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.393407E+09 | 2732.12 | 04-OCT-15:30 | 10.55 | 4.70 | 0.466905E+09 | 687.44 | 04-OCT-13:50 | 10.55 | 4.70 |
November | 10714814.26 | 2015.61 | 04-NOV-16:02 | -9.6 | -11.3 | 0.457199E+09 | 626.04 | 30-NOV-10:39 | -28.7 | -28.9 |
December | 15445111.47 | 2011.82 | 23-DEC-17:02 | -2.6 | -3.4 | 0.444058E+09 | 626.16 | 12-DEC-14:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.329817E+11 | 0.627026E+10 | ||||||||
Minimum of Months | 10714814.26 | 2011.82 | -9.6 | -11.3 | 0.418315E+09 | 626.04 | -28.7 | -28.9 | ||
Maximum of Months | 0.880872E+10 | 17305.56 | 22.93 | 14.75 | 0.659408E+09 | 845.73 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17709718.98 | 2330.86 | 21-JAN-17:02 | -5.5 | -5.8 | 0.298417E+09 | 403.47 | 12-JAN-14:20 | -5.5 | -5.8 |
February | 51692029.50 | 2658.03 | 23-FEB-06:04 | -22.1 | -22.4 | 0.271078E+09 | 403.42 | 01-FEB-10:30 | -22.1 | -22.4 |
March | 0.104357E+10 | 3815.06 | 22-MAR-10:40 | 2.43 | 0.50 | 0.331854E+09 | 513.38 | 22-MAR-09:00 | 2.43 | 0.50 |
April | 0.335565E+10 | 11076.28 | 21-APR-09:50 | 7.52 | 3.12 | 0.336264E+09 | 547.07 | 21-APR-09:00 | 7.80 | 3.31 |
May | 0.833056E+10 | 24350.57 | 14-MAY-10:11 | 16.47 | 8.71 | 0.416613E+09 | 546.42 | 05-MAY-09:30 | 16.47 | 8.71 |
June | 0.993158E+10 | 18082.92 | 08-JUN-05:02 | 8.48 | 6.28 | 0.421587E+09 | 545.87 | 08-JUN-09:39 | 16.33 | 10.32 |
July | 0.984656E+10 | 23998.01 | 23-JUL-11:51 | 23.90 | 15.81 | 0.390935E+09 | 546.60 | 07-JUL-09:00 | 23.90 | 15.81 |
August | 0.768917E+10 | 16437.94 | 27-AUG-10:32 | 13.17 | 10.82 | 0.430563E+09 | 545.56 | 25-AUG-09:00 | 13.17 | 10.82 |
September | 0.310147E+10 | 9013.95 | 08-SEP-10:20 | 7.57 | 4.06 | 0.323384E+09 | 544.95 | 15-SEP-09:00 | 5.00 | 3.51 |
October | 0.716265E+09 | 3632.87 | 03-OCT-10:30 | 5.00 | 3.43 | 0.302891E+09 | 501.81 | 03-OCT-09:00 | 5.00 | 3.43 |
November | 20223618.19 | 2678.50 | 17-NOV-06:04 | -22.9 | -23.1 | 0.295696E+09 | 403.46 | 30-NOV-10:50 | -28.8 | -29.0 |
December | 24252541.35 | 2321.98 | 23-DEC-17:02 | -2.6 | -3.4 | 0.287718E+09 | 403.54 | 12-DEC-14:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.441287E+11 | 0.410700E+10 | ||||||||
Minimum of Months | 17709718.98 | 2321.98 | -22.9 | -23.1 | 0.271078E+09 | 403.42 | -28.8 | -29.0 | ||
Maximum of Months | 0.993158E+10 | 24350.57 | 23.90 | 15.81 | 0.430563E+09 | 547.07 | 23.90 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87785734.95 | 3846.95 | 25-JAN-06:04 | -22.1 | -22.4 | 0.463194E+09 | 626.08 | 11-JAN-10:30 | -22.1 | -22.4 |
February | 0.943699E+09 | 6520.77 | 15-FEB-13:50 | -8.5 | -9.4 | 0.429675E+09 | 845.63 | 15-FEB-14:30 | -7.8 | -8.9 |
March | 0.392167E+10 | 14495.15 | 31-MAR-14:20 | -10.7 | -12.8 | 0.555370E+09 | 845.64 | 31-MAR-13:20 | -10.7 | -12.8 |
April | 0.867214E+10 | 26460.86 | 13-APR-12:08 | 2.98 | -1.4 | 0.537424E+09 | 861.07 | 12-APR-15:30 | 2.98 | -1.4 |
May | 0.120493E+11 | 36767.36 | 14-MAY-13:32 | 19.23 | 9.59 | 0.619251E+09 | 847.88 | 12-MAY-13:00 | 19.23 | 9.59 |
June | 0.141674E+11 | 22020.20 | 04-JUN-14:43 | 19.32 | 11.73 | 0.639483E+09 | 846.02 | 16-JUN-13:00 | 19.40 | 10.50 |
July | 0.141995E+11 | 39313.39 | 23-JUL-11:51 | 23.90 | 15.81 | 0.593654E+09 | 847.15 | 20-JUL-13:50 | 23.90 | 15.81 |
August | 0.135196E+11 | 39892.96 | 27-AUG-13:11 | 18.33 | 13.81 | 0.651014E+09 | 846.11 | 31-AUG-13:00 | 13.30 | 4.88 |
September | 0.671621E+10 | 18297.76 | 08-SEP-14:30 | 13.05 | 8.68 | 0.516195E+09 | 845.68 | 08-SEP-13:09 | 13.05 | 8.68 |
October | 0.231702E+10 | 15127.63 | 03-OCT-13:20 | 10.57 | 6.12 | 0.487461E+09 | 845.64 | 13-OCT-13:00 | 1.10 | -2.4 |
November | 0.242462E+09 | 5157.19 | 08-NOV-13:50 | -13.4 | -14.2 | 0.460107E+09 | 729.92 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 43093581.57 | 4237.34 | 23-DEC-06:04 | -3.8 | -5.0 | 0.446543E+09 | 626.15 | 12-DEC-14:20 | -3.8 | -5.0 |
Annual Sum or Average | 0.768799E+11 | 0.639937E+10 | ||||||||
Minimum of Months | 43093581.57 | 3846.95 | -22.1 | -22.4 | 0.429675E+09 | 626.08 | -22.1 | -22.4 | ||
Maximum of Months | 0.141995E+11 | 39892.96 | 23.90 | 15.81 | 0.651014E+09 | 861.07 | 23.90 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22225303.08 | 2480.69 | 21-JAN-17:02 | -5.5 | -5.8 | 0.298514E+09 | 403.45 | 09-JAN-10:50 | -5.5 | -5.8 |
February | 81787353.02 | 2916.36 | 03-FEB-06:04 | -10.5 | -10.7 | 0.271218E+09 | 403.45 | 24-FEB-10:20 | -25.2 | -25.7 |
March | 0.729943E+09 | 3632.84 | 22-MAR-16:00 | 5.60 | 2.61 | 0.327549E+09 | 464.51 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.381526E+10 | 13792.96 | 13-APR-17:00 | 5.60 | 1.18 | 0.316018E+09 | 521.18 | 12-APR-15:50 | 5.60 | 1.18 |
May | 0.628036E+10 | 21263.31 | 21-MAY-18:22 | 16.10 | 7.39 | 0.380546E+09 | 544.94 | 22-MAY-13:00 | 17.80 | 8.63 |
June | 0.874826E+10 | 21106.43 | 10-JUN-17:42 | 21.60 | 11.19 | 0.411762E+09 | 544.97 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.810413E+10 | 16877.01 | 30-JUL-19:32 | 17.20 | 11.89 | 0.380559E+09 | 544.97 | 07-JUL-13:09 | 17.20 | 11.89 |
August | 0.688852E+10 | 23873.33 | 27-AUG-17:51 | 20.60 | 12.18 | 0.407286E+09 | 544.94 | 01-AUG-13:09 | 20.60 | 12.18 |
September | 0.293535E+10 | 7145.96 | 08-SEP-16:00 | 14.40 | 9.03 | 0.309553E+09 | 521.18 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.629634E+09 | 3558.41 | 03-OCT-15:20 | 12.43 | 6.74 | 0.301147E+09 | 458.08 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 29844984.98 | 2864.65 | 02-NOV-05:04 | -11.0 | -11.4 | 0.295896E+09 | 403.45 | 27-NOV-10:20 | -27.2 | -27.4 |
December | 32065074.17 | 2481.58 | 23-DEC-17:02 | -2.6 | -3.4 | 0.287897E+09 | 403.51 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.382974E+11 | 0.398795E+10 | ||||||||
Minimum of Months | 22225303.08 | 2480.69 | -11.0 | -11.4 | 0.271218E+09 | 403.45 | -27.2 | -27.4 | ||
Maximum of Months | 0.874826E+10 | 23873.33 | 21.60 | 12.18 | 0.411762E+09 | 544.97 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119485E+09 | 5715.46 | 12-JAN-04:01 | -37.3 | -37.4 | 0.00 | 0.00 | 01-JAN-00:10 | -37.3 | -37.4 |
February | 0.292581E+09 | 4751.01 | 25-FEB-05:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-FEB-00:10 | -24.4 | -24.9 |
March | 0.962266E+09 | 4864.21 | 21-MAR-05:08 | -4.3 | -5.7 | 0.00 | 0.00 | 01-MAR-00:10 | -4.3 | -5.7 |
April | 0.364252E+10 | 6207.61 | 21-APR-05:10 | -2.0 | -3.0 | 0.00 | 0.00 | 01-APR-00:10 | -2.0 | -3.0 |
May | 0.640346E+10 | 7683.78 | 31-MAY-05:15 | 12.43 | 7.84 | 0.00 | 0.00 | 01-MAY-00:10 | 12.43 | 7.84 |
June | 0.892321E+10 | 10765.84 | 05-JUN-05:15 | 10.77 | 8.82 | 0.00 | 0.00 | 01-JUN-00:10 | 10.77 | 8.82 |
July | 0.933270E+10 | 12108.56 | 24-JUL-05:15 | 13.17 | 12.61 | 0.00 | 0.00 | 01-JUL-00:10 | 13.17 | 12.61 |
August | 0.879425E+10 | 10826.61 | 28-AUG-05:13 | 5.93 | 5.13 | 0.00 | 0.00 | 01-AUG-00:10 | 5.93 | 5.13 |
September | 0.434122E+10 | 8839.59 | 05-SEP-05:15 | 5.00 | 4.17 | 0.00 | 0.00 | 01-SEP-00:10 | 5.00 | 4.17 |
October | 0.192444E+10 | 5991.54 | 03-OCT-05:08 | -1.1 | -1.4 | 0.00 | 0.00 | 01-OCT-00:10 | -1.1 | -1.4 |
November | 0.108721E+09 | 4288.34 | 29-NOV-05:01 | -28.9 | -29.1 | 0.00 | 0.00 | 01-NOV-00:10 | -28.9 | -29.1 |
December | 41413348.38 | 4484.48 | 15-DEC-05:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-DEC-00:10 | -33.2 | -33.3 |
Annual Sum or Average | 0.448863E+11 | 0.00 | ||||||||
Minimum of Months | 41413348.38 | 4288.34 | -37.3 | -37.4 | 0.00 | 0.00 | -37.3 | -37.4 | ||
Maximum of Months | 0.933270E+10 | 12108.56 | 13.17 | 12.61 | 0.00 | 0.00 | 13.17 | 12.61 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528936E+09 | 9973.02 | 28-JAN-04:01 | -18.5 | -19.2 | 0.00 | 0.00 | 01-JAN-00:10 | -18.5 | -19.2 |
February | 0.677979E+09 | 8695.68 | 25-FEB-04:01 | -25.4 | -25.8 | 0.00 | 0.00 | 01-FEB-00:10 | -25.4 | -25.8 |
March | 0.406434E+09 | 8707.65 | 03-MAR-04:11 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.152248E+10 | 8019.94 | 03-APR-03:01 | -21.1 | -21.6 | 0.00 | 0.00 | 01-APR-00:10 | -21.1 | -21.6 |
May | 0.460275E+10 | 5981.02 | 16-MAY-05:10 | 3.30 | 1.49 | 0.00 | 0.00 | 01-MAY-00:10 | 3.30 | 1.49 |
June | 0.699424E+10 | 6834.46 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.711909E+10 | 7727.34 | 24-JUL-05:15 | 13.17 | 12.61 | 0.00 | 0.00 | 01-JUL-00:10 | 13.17 | 12.61 |
August | 0.613503E+10 | 7677.01 | 26-AUG-05:13 | 8.53 | 7.65 | 0.00 | 0.00 | 01-AUG-00:10 | 8.53 | 7.65 |
September | 0.284895E+10 | 6296.33 | 14-SEP-05:10 | 6.70 | 5.87 | 0.00 | 0.00 | 01-SEP-00:10 | 6.70 | 5.87 |
October | 0.869167E+09 | 8507.34 | 23-OCT-03:11 | -11.5 | -12.4 | 0.00 | 0.00 | 01-OCT-00:10 | -11.5 | -12.4 |
November | 0.783417E+09 | 8995.49 | 10-NOV-04:01 | -18.9 | -19.3 | 0.00 | 0.00 | 01-NOV-00:10 | -18.9 | -19.3 |
December | 0.848785E+09 | 9051.53 | 09-DEC-04:01 | -24.4 | -24.6 | 0.00 | 0.00 | 01-DEC-00:10 | -24.4 | -24.6 |
Annual Sum or Average | 0.333373E+11 | 0.00 | ||||||||
Minimum of Months | 0.406434E+09 | 5981.02 | -25.6 | -26.1 | 0.00 | 0.00 | -25.6 | -26.1 | ||
Maximum of Months | 0.711909E+10 | 9973.02 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 8654978.25 | 1273.25 | 22-MAR-16:20 | 5.60 | 2.33 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.33 |
April | 0.120893E+10 | 7273.88 | 20-APR-15:30 | 13.60 | 6.09 | 0.00 | 0.00 | 01-APR-00:10 | 13.60 | 6.09 |
May | 0.495819E+10 | 13497.00 | 31-MAY-14:30 | 20.55 | 10.45 | 0.00 | 0.00 | 01-MAY-00:10 | 20.55 | 10.45 |
June | 0.914647E+10 | 15078.08 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.901103E+10 | 15595.06 | 21-JUL-14:50 | 27.52 | 14.73 | 0.00 | 0.00 | 01-JUL-00:10 | 27.52 | 14.73 |
August | 0.600503E+10 | 12790.25 | 11-AUG-15:40 | 25.20 | 14.55 | 0.00 | 0.00 | 01-AUG-00:10 | 25.20 | 14.55 |
September | 0.888522E+09 | 4917.72 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 19651803.78 | 1546.93 | 04-OCT-16:20 | 9.80 | 4.48 | 0.00 | 0.00 | 01-OCT-00:10 | 9.80 | 4.48 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.312465E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.914647E+10 | 15595.06 | 27.52 | 16.10 | 0.00 | 0.00 | 27.52 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.859516E+09 | 1015.44 | 25-JAN-15:00 | -18.9 | -19.2 | 94529046.42 | 126.82 | 23-JAN-14:30 | -18.9 | -19.2 |
February | 0.602510E+10 | 3505.14 | 15-FEB-16:10 | -7.3 | -8.7 | 86396480.35 | 126.82 | 14-FEB-14:09 | -7.3 | -8.7 |
March | 0.130052E+11 | 6684.60 | 31-MAR-24:00 | -11.8 | -13.4 | 0.103236E+09 | 126.82 | 31-MAR-13:09 | -11.8 | -13.4 |
April | 0.187342E+11 | 8540.14 | 20-APR-18:50 | 11.28 | 4.73 | 91605018.15 | 126.82 | 19-APR-13:09 | 11.28 | 4.73 |
May | 0.438168E+10 | 3476.87 | 31-MAY-24:00 | 12.40 | 8.53 | 99233130.02 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.941227E+10 | 5350.08 | 30-JUN-24:00 | 15.10 | 14.10 | 98962206.63 | 126.85 | 27-JUN-13:00 | 15.10 | 14.10 |
July | 0.147526E+11 | 7270.52 | 31-JUL-23:40 | 17.10 | 11.88 | 91885922.86 | 126.84 | 25-JUL-09:09 | 17.10 | 11.88 |
August | 0.196983E+11 | 8354.46 | 27-AUG-18:53 | 19.40 | 11.72 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 19.40 | 11.72 |
September | 0.379285E+10 | 2898.82 | 30-SEP-24:00 | 1.30 | -0.1 | 91606661.52 | 126.83 | 05-SEP-13:00 | 1.30 | -0.1 |
October | 0.814666E+10 | 4409.75 | 31-OCT-24:00 | -10.1 | -11.0 | 95230022.42 | 126.82 | 04-OCT-13:09 | -10.1 | -11.0 |
November | 0.117277E+11 | 5437.94 | 08-NOV-16:00 | -16.1 | -16.4 | 94300266.86 | 126.82 | 02-NOV-13:30 | -16.1 | -16.4 |
December | 0.168752E+11 | 6868.67 | 26-DEC-17:00 | -15.6 | -15.9 | 91880855.30 | 126.82 | 07-DEC-14:39 | -15.6 | -15.9 |
Annual Sum or Average | 0.127411E+12 | 0.114210E+10 | ||||||||
Minimum of Months | 0.859516E+09 | 1015.44 | -18.9 | -19.2 | 86396480.35 | 126.82 | -18.9 | -19.2 | ||
Maximum of Months | 0.196983E+11 | 8540.14 | 19.40 | 14.10 | 0.103239E+09 | 126.85 | 19.40 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398416E+09 | 645.53 | 12-JAN-10:00 | -38.3 | -38.4 | 88225923.63 | 126.82 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.381194E+10 | 3027.19 | 16-FEB-16:10 | -4.6 | -6.9 | 86396483.25 | 126.82 | 02-FEB-14:09 | -4.6 | -6.9 |
March | 0.105039E+11 | 5821.05 | 31-MAR-23:20 | -12.1 | -13.7 | 0.103236E+09 | 126.82 | 31-MAR-13:09 | -12.1 | -13.7 |
April | 0.166505E+11 | 8136.18 | 20-APR-18:50 | 11.28 | 4.73 | 91605041.75 | 126.82 | 19-APR-13:09 | 11.28 | 4.73 |
May | 0.367106E+10 | 3245.02 | 31-MAY-24:00 | 12.40 | 8.53 | 99233132.01 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.875424E+10 | 5148.44 | 30-JUN-24:00 | 15.10 | 14.10 | 98961994.81 | 126.85 | 27-JUN-13:00 | 15.10 | 14.10 |
July | 0.138937E+11 | 7034.63 | 31-JUL-23:55 | 16.60 | 11.46 | 91886253.76 | 126.84 | 25-JUL-13:00 | 16.60 | 11.46 |
August | 0.184907E+11 | 7804.41 | 27-AUG-18:46 | 19.60 | 11.80 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 19.60 | 11.80 |
September | 0.265646E+10 | 2179.03 | 30-SEP-23:50 | 1.17 | -0.3 | 91606494.42 | 126.83 | 05-SEP-13:00 | 1.17 | -0.3 |
October | 0.577085E+10 | 3439.61 | 12-OCT-16:00 | -0.6 | -3.4 | 95230029.54 | 126.82 | 04-OCT-13:09 | -0.6 | -3.4 |
November | 0.869422E+10 | 4811.97 | 08-NOV-15:50 | -15.7 | -16.1 | 94300272.02 | 126.82 | 01-NOV-13:00 | -15.7 | -16.1 |
December | 0.133708E+11 | 6007.02 | 21-DEC-17:00 | -16.7 | -17.3 | 91880860.86 | 126.82 | 08-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.106667E+12 | 0.113580E+10 | ||||||||
Minimum of Months | 0.398416E+09 | 645.53 | -38.3 | -38.4 | 86396483.25 | 126.82 | -16.7 | -17.3 | ||
Maximum of Months | 0.184907E+11 | 8136.18 | 19.60 | 14.10 | 0.103239E+09 | 126.85 | 19.60 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326373E+09 | 624.71 | 12-JAN-08:15 | -38.1 | -38.2 | 79766726.73 | 124.59 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.223601E+10 | 2632.17 | 09-FEB-16:00 | 0.60 | -0.5 | 86307481.20 | 126.82 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.834843E+10 | 5099.21 | 31-MAR-17:30 | -9.4 | -11.7 | 0.103236E+09 | 126.82 | 31-MAR-13:09 | -9.4 | -11.7 |
April | 0.151647E+11 | 8126.93 | 20-APR-18:50 | 11.28 | 4.73 | 91605051.54 | 126.82 | 19-APR-13:09 | 11.28 | 4.73 |
May | 0.302945E+10 | 3193.19 | 31-MAY-24:00 | 12.40 | 8.53 | 99233183.23 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.856874E+10 | 5108.64 | 30-JUN-24:00 | 15.10 | 14.10 | 98962020.50 | 126.85 | 27-JUN-13:00 | 15.10 | 14.10 |
July | 0.137416E+11 | 6998.13 | 31-JUL-23:40 | 17.10 | 11.88 | 91886276.15 | 126.84 | 25-JUL-13:00 | 17.10 | 11.88 |
August | 0.181258E+11 | 7833.78 | 10-AUG-19:00 | 21.70 | 11.86 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 21.70 | 11.86 |
September | 0.151143E+10 | 1883.51 | 06-SEP-17:50 | 12.20 | 9.07 | 91429800.67 | 127.05 | 25-SEP-09:00 | 0.60 | -1.2 |
October | 0.360667E+10 | 3253.96 | 03-OCT-16:00 | 11.70 | 6.37 | 95230157.38 | 126.82 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.647143E+10 | 4313.32 | 08-NOV-15:50 | -15.7 | -16.1 | 94300274.58 | 126.82 | 01-NOV-13:09 | -15.7 | -16.1 |
December | 0.112647E+11 | 5501.69 | 21-DEC-17:00 | -16.7 | -17.3 | 91880863.31 | 126.82 | 20-DEC-14:39 | -16.7 | -17.3 |
Annual Sum or Average | 0.923953E+11 | 0.112708E+10 | ||||||||
Minimum of Months | 0.326373E+09 | 624.71 | -38.1 | -38.2 | 79766726.73 | 124.59 | -16.7 | -17.3 | ||
Maximum of Months | 0.181258E+11 | 8126.93 | 21.70 | 14.10 | 0.103239E+09 | 127.05 | 21.70 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228202E+12 | 89099.93 | 20-JAN-17:00 | -11.1 | -11.2 | 0.206189E+10 | 2746.12 | 11-JAN-14:00 | -11.1 | -11.2 |
February | 0.427173E+12 | 181056.59 | 09-FEB-17:00 | -2.2 | -2.6 | 0.187078E+10 | 2746.33 | 22-FEB-10:20 | -26.9 | -27.1 |
March | 0.722328E+12 | 356817.45 | 31-MAR-24:00 | -11.8 | -13.4 | 0.223524E+10 | 2746.18 | 01-MAR-10:09 | -11.8 | -13.4 |
April | 0.940696E+12 | 367294.20 | 21-APR-16:00 | 14.40 | 5.45 | 0.198314E+10 | 2750.57 | 17-APR-13:00 | 14.40 | 5.45 |
May | 0.239751E+12 | 175686.57 | 31-MAY-24:00 | 12.40 | 8.53 | 0.214859E+10 | 2747.47 | 31-MAY-09:30 | 12.40 | 8.53 |
June | 0.469749E+12 | 267472.32 | 30-JUN-24:00 | 15.10 | 14.10 | 0.214322E+10 | 2749.92 | 26-JUN-09:09 | 15.10 | 14.10 |
July | 0.732137E+12 | 360185.21 | 31-JUL-23:55 | 16.60 | 11.46 | 0.198968E+10 | 2750.97 | 25-JUL-09:09 | 16.60 | 11.46 |
August | 0.978476E+12 | 368873.22 | 28-AUG-16:00 | 20.00 | 12.62 | 0.224141E+10 | 2833.46 | 23-AUG-13:00 | 20.00 | 12.62 |
September | 0.234326E+12 | 174656.83 | 30-SEP-24:00 | 1.30 | -0.1 | 0.198356E+10 | 2747.77 | 21-SEP-09:00 | 1.30 | -0.1 |
October | 0.483115E+12 | 265564.02 | 31-OCT-24:00 | -10.1 | -11.0 | 0.206197E+10 | 2746.34 | 30-OCT-09:39 | -10.1 | -11.0 |
November | 0.700093E+12 | 274042.88 | 03-NOV-16:00 | -11.1 | -11.5 | 0.204179E+10 | 2746.21 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 0.966280E+12 | 364943.33 | 27-DEC-17:00 | -21.1 | -21.4 | 0.198915E+10 | 2745.63 | 15-DEC-10:20 | -21.1 | -21.4 |
Annual Sum or Average | 0.712233E+13 | 0.247504E+11 | ||||||||
Minimum of Months | 0.228202E+12 | 89099.93 | -21.1 | -21.4 | 0.187078E+10 | 2745.63 | -27.2 | -27.4 | ||
Maximum of Months | 0.978476E+12 | 368873.22 | 20.00 | 14.10 | 0.224141E+10 | 2833.46 | 20.00 | 14.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.687088E+09 | 10828.23 | 23-JAN-06:03 | -11.2 |
February | 0.311338E+09 | 12281.91 | 15-FEB-06:04 | -15.9 |
March | 0.146619E+09 | 12166.28 | 22-MAR-04:03 | -1.7 |
April | 0.110452E+09 | 12627.19 | 21-APR-04:05 | -2.2 |
May | 0.156307E+09 | 14485.73 | 31-MAY-03:53 | 12.20 |
June | 0.215454E+09 | 12594.77 | 10-JUN-05:07 | 10.18 |
July | 0.400575E+09 | 16649.52 | 29-JUL-16:03 | 30.00 |
August | 0.326296E+09 | 14395.63 | 27-AUG-22:03 | 14.32 |
September | 0.372377E+09 | 12797.92 | 25-SEP-03:05 | -0.7 |
October | 0.185750E+09 | 12779.08 | 02-OCT-03:05 | 6.28 |
November | 56617225.19 | 12100.54 | 16-NOV-06:03 | -16.6 |
December | 0.239483E+09 | 12383.98 | 27-DEC-06:05 | -20.8 |
Annual Sum or Average | 0.320836E+10 | |||
Minimum of Months | 56617225.19 | 10828.23 | -20.8 | |
Maximum of Months | 0.687088E+09 | 16649.52 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44769535.86 | 21775.24 | 02-JAN-05:01 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 44769535.86 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 44769535.86 | 21775.24 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159922E+10 | 60099.56 | 02-JAN-04:01 | -15.1 |
February | 0.432647E+09 | 51878.27 | 27-FEB-05:11 | -36.1 |
March | 14589622.73 | 45432.41 | 06-MAR-06:02 | -21.1 |
April | 2606343.94 | 17375.63 | 03-APR-05:03 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 509430.53 | 2547.15 | 25-SEP-11:20 | 2.77 |
October | 26797688.62 | 46054.81 | 23-OCT-05:01 | -11.0 |
November | 0.398253E+09 | 51618.50 | 27-NOV-05:01 | -25.8 |
December | 0.690376E+09 | 51675.91 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.316500E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.159922E+10 | 60099.56 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128351E+11 | 81741.55 | 01-JAN-22:42 | -15.0 |
February | 0.786709E+10 | 81414.88 | 27-FEB-04:01 | -34.7 |
March | 0.429651E+10 | 79202.07 | 06-MAR-04:01 | -20.0 |
April | 0.114130E+10 | 76968.24 | 03-APR-03:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 79922640.16 | 68658.15 | 25-SEP-04:01 | -1.1 |
October | 0.301990E+10 | 79544.72 | 30-OCT-03:01 | -13.5 |
November | 0.940517E+10 | 81395.77 | 13-NOV-04:11 | -20.2 |
December | 0.118041E+11 | 81143.20 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.504491E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.128351E+11 | 81741.55 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394111E+10 | 13976.94 | 30-JAN-04:01 | -25.1 |
February | 0.179568E+10 | 13607.65 | 27-FEB-04:01 | -34.7 |
March | 0.661609E+09 | 12667.81 | 02-MAR-05:01 | -26.7 |
April | 26164899.15 | 11608.36 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.144769E+09 | 11805.87 | 31-OCT-04:01 | -17.9 |
November | 0.143301E+10 | 12592.81 | 29-NOV-05:01 | -28.9 |
December | 0.273156E+10 | 12642.92 | 05-DEC-05:01 | -26.4 |
Annual Sum or Average | 0.107339E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.394111E+10 | 13976.94 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311725E+10 | 16329.61 | 30-JAN-04:01 | -25.1 |
February | 0.132610E+10 | 16107.34 | 27-FEB-04:01 | -34.7 |
March | 0.462163E+09 | 14654.65 | 02-MAR-05:01 | -26.7 |
April | 25757228.31 | 13392.70 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.146801E+09 | 13808.67 | 30-OCT-04:01 | -14.4 |
November | 0.147629E+10 | 14692.55 | 30-NOV-05:01 | -27.8 |
December | 0.287014E+10 | 15415.58 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.942451E+10 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.311725E+10 | 16329.61 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465413E+10 | 25566.59 | 30-JAN-04:01 | -25.1 |
February | 0.171497E+10 | 25063.63 | 27-FEB-04:01 | -34.7 |
March | 0.548680E+09 | 22782.90 | 06-MAR-05:01 | -20.2 |
April | 33913675.51 | 20893.53 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 108757.88 | 725.05 | 30-SEP-05:05 | -4.5 |
October | 0.237199E+09 | 22732.63 | 30-OCT-04:01 | -14.4 |
November | 0.198460E+10 | 23738.88 | 27-NOV-04:02 | -26.0 |
December | 0.410391E+10 | 24754.67 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.132775E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.465413E+10 | 25566.59 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.981031E+09 | 13952.03 | 30-JAN-04:01 | -25.1 |
February | 0.221981E+09 | 12674.09 | 27-FEB-05:01 | -36.1 |
March | 29032468.69 | 12039.39 | 01-MAR-05:01 | -28.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 5349170.58 | 10891.00 | 31-OCT-05:01 | -18.2 |
November | 43717249.83 | 11636.82 | 27-NOV-05:01 | -25.8 |
December | 38336992.96 | 10979.23 | 02-DEC-06:01 | -21.1 |
Annual Sum or Average | 0.131945E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.981031E+09 | 13952.03 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102876E+11 | 13997.11 | 29-JAN-15:02 | -21.8 |
February | 0.650578E+10 | 13583.34 | 26-FEB-09:51 | -27.2 |
March | 0.372282E+10 | 12989.36 | 03-MAR-04:11 | -25.6 |
April | 0.826363E+09 | 12808.55 | 03-APR-03:01 | -21.1 |
May | 6898.49 | 45.99 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 9784.33 | 65.23 | 31-AUG-07:05 | -0.1 |
September | 56445322.11 | 10479.81 | 25-SEP-05:01 | -1.2 |
October | 0.219790E+10 | 13194.61 | 30-OCT-02:62 | -12.9 |
November | 0.710514E+10 | 13237.54 | 13-NOV-04:01 | -20.1 |
December | 0.998424E+10 | 13281.69 | 04-DEC-00:01 | -22.1 |
Annual Sum or Average | 0.406863E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.102876E+11 | 13997.11 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.711163E+10 | 20064.73 | 29-JAN-00:21 | -25.0 |
February | 0.386896E+10 | 19578.36 | 26-FEB-05:11 | -25.6 |
March | 0.164887E+10 | 18878.27 | 03-MAR-04:11 | -25.6 |
April | 0.367573E+09 | 18483.57 | 03-APR-03:01 | -21.1 |
May | 52341.42 | 348.94 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 104240.33 | 694.94 | 30-AUG-05:03 | 0.00 |
September | 35813583.59 | 13939.45 | 25-SEP-05:01 | -1.2 |
October | 0.126533E+10 | 18718.89 | 23-OCT-03:11 | -11.5 |
November | 0.487755E+10 | 19296.83 | 27-NOV-04:11 | -25.9 |
December | 0.706900E+10 | 19327.20 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.262449E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.711163E+10 | 20064.73 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.898013E+10 | 30121.25 | 01-JAN-07:22 | -15.3 |
February | 0.391297E+10 | 29485.06 | 26-FEB-05:11 | -25.6 |
March | 0.166022E+10 | 27867.17 | 01-MAR-04:01 | -27.9 |
April | 0.311938E+09 | 26949.73 | 03-APR-03:01 | -21.1 |
May | 258462.87 | 1723.09 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 17490.41 | 116.60 | 31-AUG-07:05 | -0.1 |
September | 28742729.41 | 15677.67 | 25-SEP-05:01 | -1.2 |
October | 0.128241E+10 | 27907.78 | 30-OCT-03:01 | -13.5 |
November | 0.521813E+10 | 29000.82 | 27-NOV-04:11 | -25.9 |
December | 0.952033E+10 | 29135.10 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.309151E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.952033E+10 | 30121.25 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606637E+10 | 19654.43 | 29-JAN-15:02 | -21.8 |
February | 0.322380E+10 | 19354.40 | 26-FEB-09:51 | -27.2 |
March | 0.157873E+10 | 18478.12 | 03-MAR-04:11 | -25.6 |
April | 0.225506E+09 | 17630.87 | 03-APR-03:01 | -21.1 |
May | 513827.60 | 2566.70 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 16274.61 | 108.50 | 31-AUG-07:05 | -0.1 |
September | 23901251.10 | 10131.26 | 25-SEP-05:01 | -1.2 |
October | 0.105380E+10 | 18319.72 | 23-OCT-03:11 | -11.5 |
November | 0.357660E+10 | 18848.80 | 27-NOV-04:11 | -25.9 |
December | 0.543659E+10 | 18870.81 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.211858E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.606637E+10 | 19654.43 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182328E+11 | 18140.80 | 29-JAN-00:01 | -25.0 |
February | 0.135484E+11 | 17864.11 | 26-FEB-00:42 | -27.1 |
March | 0.100089E+11 | 17497.43 | 27-MAR-02:62 | -19.0 |
April | 0.328496E+10 | 17511.17 | 03-APR-01:22 | -18.0 |
May | 47541284.63 | 13951.35 | 27-MAY-04:02 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 42873539.51 | 13549.11 | 31-AUG-04:02 | -0.7 |
September | 0.776069E+09 | 15091.30 | 25-SEP-03:02 | -0.7 |
October | 0.695171E+10 | 17521.25 | 22-OCT-20:22 | -14.7 |
November | 0.151848E+11 | 17505.45 | 26-NOV-17:32 | -23.0 |
December | 0.185404E+11 | 17854.64 | 03-DEC-10:12 | -22.8 |
Annual Sum or Average | 0.866184E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.1 | |
Maximum of Months | 0.185404E+11 | 18140.80 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122399E+11 | 20833.51 | 29-JAN-00:01 | -25.0 |
February | 0.811189E+10 | 20428.72 | 26-FEB-00:42 | -27.1 |
March | 0.454410E+10 | 19851.40 | 27-MAR-02:62 | -19.0 |
April | 0.148318E+10 | 19872.41 | 02-APR-19:22 | -11.4 |
May | 13883188.45 | 15890.08 | 27-MAY-04:02 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 19287826.12 | 9018.75 | 30-AUG-05:03 | 0.00 |
September | 0.348666E+09 | 17230.42 | 30-SEP-04:01 | -4.0 |
October | 0.392598E+10 | 19953.42 | 30-OCT-02:62 | -12.9 |
November | 0.100663E+11 | 20037.70 | 13-NOV-04:11 | -20.2 |
December | 0.126397E+11 | 20501.73 | 03-DEC-10:12 | -22.8 |
Annual Sum or Average | 0.533929E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.1 | |
Maximum of Months | 0.126397E+11 | 20833.51 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166582E+11 | 32630.89 | 29-JAN-00:01 | -25.0 |
February | 0.933407E+10 | 32087.52 | 26-FEB-00:42 | -27.1 |
March | 0.532146E+10 | 30673.21 | 03-MAR-04:11 | -25.6 |
April | 0.162185E+10 | 30951.41 | 02-APR-06:42 | -16.6 |
May | 37083490.69 | 22976.08 | 27-MAY-04:02 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 19320864.93 | 13748.91 | 30-AUG-05:03 | 0.00 |
September | 0.427515E+09 | 26854.21 | 30-SEP-04:01 | -4.0 |
October | 0.470413E+10 | 31390.49 | 30-OCT-02:62 | -12.9 |
November | 0.125074E+11 | 31550.88 | 13-NOV-04:11 | -20.2 |
December | 0.181581E+11 | 32361.25 | 03-DEC-10:12 | -22.8 |
Annual Sum or Average | 0.687891E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.1 | |
Maximum of Months | 0.181581E+11 | 32630.89 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111940E+11 | 21863.96 | 29-JAN-00:01 | -25.0 |
February | 0.706064E+10 | 21236.65 | 26-FEB-10:01 | -27.2 |
March | 0.441271E+10 | 20579.73 | 03-MAR-04:11 | -25.6 |
April | 0.104564E+10 | 19475.75 | 03-APR-03:01 | -21.1 |
May | 25960444.88 | 15276.20 | 27-MAY-04:02 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 10767448.62 | 8708.89 | 30-AUG-05:03 | 0.00 |
September | 0.289516E+09 | 17960.46 | 30-SEP-04:01 | -4.0 |
October | 0.330087E+10 | 20654.05 | 30-OCT-02:62 | -12.9 |
November | 0.797982E+10 | 20839.41 | 13-NOV-04:11 | -20.2 |
December | 0.103087E+11 | 21184.45 | 03-DEC-10:12 | -22.8 |
Annual Sum or Average | 0.456286E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.111940E+11 | 21863.96 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470971E+10 | 12817.62 | 02-JAN-06:08 | -15.4 |
February | 0.229030E+10 | 12846.31 | 09-FEB-06:02 | 0.00 |
March | 0.136427E+10 | 11940.88 | 07-MAR-06:01 | -8.0 |
April | 0.254884E+09 | 13237.97 | 07-APR-04:01 | -3.9 |
May | 0.111523E+09 | 11313.99 | 01-MAY-03:02 | 6.70 |
June | 89829102.64 | 10649.21 | 26-JUN-03:02 | 12.70 |
July | 0.126780E+09 | 10975.57 | 03-JUL-03:02 | 10.50 |
August | 0.129441E+09 | 11777.15 | 08-AUG-03:02 | 12.70 |
September | 66610221.69 | 10697.85 | 01-SEP-03:02 | 7.88 |
October | 0.351043E+09 | 12344.32 | 24-OCT-05:01 | -4.4 |
November | 0.200935E+10 | 11316.85 | 02-NOV-05:01 | -11.0 |
December | 0.344652E+10 | 5956.27 | 04-DEC-06:06 | -19.4 |
Annual Sum or Average | 0.149503E+11 | |||
Minimum of Months | 66610221.69 | 5956.27 | -19.4 | |
Maximum of Months | 0.470971E+10 | 13237.97 | 12.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.804862E+10 | 23573.84 | 02-JAN-06:13 | -15.2 |
February | 0.471968E+10 | 14128.00 | 27-FEB-06:12 | -35.7 |
March | 0.332313E+10 | 8004.87 | 30-MAR-14:10 | -9.8 |
April | 0.987852E+09 | 11520.80 | 09-APR-14:42 | 3.62 |
May | 99388238.35 | 10875.03 | 21-MAY-11:42 | 14.22 |
June | 64297369.01 | 7725.25 | 28-JUN-04:02 | 11.47 |
July | 66125002.66 | 9193.73 | 23-JUL-12:21 | 24.45 |
August | 57018390.75 | 7870.46 | 27-AUG-16:12 | 20.77 |
September | 0.104905E+09 | 6996.53 | 26-SEP-05:02 | 0.50 |
October | 0.178489E+10 | 9676.32 | 10-OCT-14:10 | 2.20 |
November | 0.541870E+10 | 12344.39 | 13-NOV-06:13 | -17.9 |
December | 0.708911E+10 | 14753.16 | 04-DEC-06:12 | -19.4 |
Annual Sum or Average | 0.317637E+11 | |||
Minimum of Months | 57018390.75 | 6996.53 | -35.7 | |
Maximum of Months | 0.804862E+10 | 23573.84 | 24.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274755E+11 | 36239.95 | 13-JAN-05:12 | -33.0 |
February | 0.205885E+11 | 36354.90 | 27-FEB-05:41 | -36.1 |
March | 0.155778E+11 | 33175.63 | 01-MAR-05:11 | -28.3 |
April | 0.546664E+10 | 29994.69 | 03-APR-04:04 | -21.1 |
May | 0.522219E+09 | 20246.60 | 10-MAY-05:02 | 5.28 |
June | 0.107877E+09 | 20264.71 | 02-JUN-05:03 | 5.78 |
July | 99715049.97 | 18443.39 | 06-JUL-05:03 | 8.77 |
August | 0.354668E+09 | 16776.40 | 22-AUG-05:03 | 5.68 |
September | 0.239019E+10 | 13631.03 | 25-SEP-05:03 | -1.2 |
October | 0.115156E+11 | 31408.29 | 30-OCT-04:12 | -14.4 |
November | 0.242989E+11 | 34565.43 | 27-NOV-05:13 | -26.0 |
December | 0.285877E+11 | 33537.87 | 15-DEC-05:12 | -33.1 |
Annual Sum or Average | 0.136985E+12 | |||
Minimum of Months | 99715049.97 | 13631.03 | -36.1 | |
Maximum of Months | 0.285877E+11 | 36354.90 | 8.77 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249443E+09 | 581.93 | 29-JAN-22:23 | -24.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.249443E+09 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.249443E+09 | 581.93 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.718492E+09 | 582.65 | 12-JAN-22:13 | -36.3 |
February | 128046.61 | 33.00 | 27-FEB-04:01 | -34.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.718620E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.718492E+09 | 582.65 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.779484E+09 | 607.88 | 10-JAN-00:20 | -18.3 |
February | 0.270967E+09 | 588.74 | 26-FEB-17:40 | -24.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 14176134.68 | 510.45 | 28-MAY-05:40 | 2.93 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.123336E+09 | 575.43 | 30-SEP-04:00 | -3.9 |
October | 94013937.69 | 567.05 | 22-OCT-21:20 | -15.4 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.128198E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.779484E+09 | 607.88 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196603E+11 | 20573.73 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.178333E+11 | 20573.73 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.211910E+11 | 20573.73 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.189279E+11 | 20573.73 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.204256E+11 | 20573.73 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.203269E+11 | 20573.73 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.190266E+11 | 20573.73 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.211910E+11 | 20573.73 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.189279E+11 | 20573.73 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.196603E+11 | 20573.73 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.194299E+11 | 20573.73 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.190266E+11 | 20573.73 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.235627E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.178333E+11 | 20573.73 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.211910E+11 | 20573.73 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554336E+10 | 5800.91 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.502824E+10 | 5800.91 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.597494E+10 | 5800.91 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.533685E+10 | 5800.91 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.575915E+10 | 5800.91 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.573131E+10 | 5800.91 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.536469E+10 | 5800.91 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.597494E+10 | 5800.91 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.533685E+10 | 5800.91 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.554336E+10 | 5800.91 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.547839E+10 | 5800.91 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.536469E+10 | 5800.91 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.664368E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.502824E+10 | 5800.91 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.597494E+10 | 5800.91 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.204256E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.203269E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.194299E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.235627E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765794E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626850E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961131E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110141E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644666E+09 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 813658.43 | 0.377772E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2705299.44 | 0.274346E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 380761.24 | 0.331627E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406101E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865282E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294484E+09 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574970E+09 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3899719.11 | 0.722443E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274346E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2705299.44 | 0.110141E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507367E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415451E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639815E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727099E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427158E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 561962.07 | 0.240038E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186662.59 | 0.169893E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 288756.13 | 0.206043E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269306E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570637E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193788E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377238E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3037380.80 | 0.474383E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169893E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186662.59 | 0.727099E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758892E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626981E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971478E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112066E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642812E+09 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 814383.13 | 0.365562E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2812084.44 | 0.263501E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379486.38 | 0.323905E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406762E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853245E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289700E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562147E+09 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4005953.95 | 0.718565E+10 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263501E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2812084.44 | 0.112066E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524457E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432664E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676480E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808388E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451815E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 542434.40 | 0.268599E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1486635.15 | 0.196927E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253831.02 | 0.241088E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281488E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601049E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205275E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404024E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2282900.57 | 0.509225E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196927E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1486635.15 | 0.808388E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174651E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141051E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209889E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233004E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142720E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1768475.53 | 0.850376E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6074538.84 | 0.637510E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780305.58 | 0.745648E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877587E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183465E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647020E+09 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126991E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8623319.95 | 0.158759E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637510E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6074538.84 | 0.233004E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116590E+10 |
February | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942543E+09 |
March | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142151E+10 |
April | 0.688021E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159691E+10 |
May | 0.744847E+09 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963310E+09 |
June | 0.742030E+09 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244258.12 | 0.554354E+09 |
July | 0.690839E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4641237.61 | 0.419074E+09 |
August | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 641654.69 | 0.490833E+09 |
September | 0.688021E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594808E+09 |
October | 0.715730E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123206E+10 |
November | 0.708685E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430967E+09 |
December | 0.690839E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845839E+09 |
Annual Sum or Average | 0.858171E+10 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6527150.43 | 0.106581E+11 |
Minimum of Months | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419074E+09 |
Maximum of Months | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4641237.61 | 0.159691E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175369E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143211E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220206E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253412E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147196E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785214.00 | 0.840950E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5960641.07 | 0.639169E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780931.77 | 0.766480E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929312E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190252E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652025E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127241E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8526786.84 | 0.163968E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639169E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5960641.07 | 0.253412E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117103E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947471E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142882E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166932E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989877E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1179229.86 | 0.578744E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3761415.31 | 0.436954E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520191.56 | 0.510742E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597116E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124096E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435171E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854108E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5460836.72 | 0.108603E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435171E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3761415.31 | 0.166932E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214299E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172119E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252242E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272037E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165158E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2031042.78 | 0.101483E+10 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7265747.95 | 0.771246E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 845450.65 | 0.878486E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985838E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213488E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789890E+09 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155827E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10142241.39 | 0.188920E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771246E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7265747.95 | 0.272037E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143521E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115223E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169701E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187069E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114517E+10 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1395224.76 | 0.672800E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5174791.93 | 0.517667E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 659012.36 | 0.592197E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685524E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143536E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527840E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104172E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7229029.05 | 0.127734E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517667E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5174791.93 | 0.187069E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215623E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173828E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260229E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295542E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174611E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2040143.46 | 0.101513E+10 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6905714.96 | 0.783468E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836634.87 | 0.923598E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107627E+10 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219950E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793885E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156393E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9782493.29 | 0.195541E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783468E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6905714.96 | 0.295542E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143864E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115809E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170870E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195716E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117471E+10 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1354020.90 | 0.699310E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4390595.99 | 0.535158E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 558466.19 | 0.613619E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694112E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145403E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530392E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104544E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6303083.08 | 0.130094E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530392E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4390595.99 | 0.195716E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.554336E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.502824E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.597494E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.533685E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.575915E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.573131E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.536469E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.597494E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.533685E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.554336E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.547839E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.536469E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.664368E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.502824E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.597494E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160407E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131828E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203022E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232323E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133559E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936536.18 | 0.769431E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3824174.87 | 0.564481E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253816.12 | 0.695123E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849866E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182353E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621143E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120027E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5014527.17 | 0.151352E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564481E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3824174.87 | 0.232323E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279087E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229392E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351813E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398741E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235147E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1615014.23 | 0.135814E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6973984.54 | 0.100383E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437093.78 | 0.122664E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148448E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311361E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106834E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205625E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9026092.55 | 0.262531E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100383E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6973984.54 | 0.398741E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305740E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249836E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377672E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425986E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260476E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990914.96 | 0.156674E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5131064.39 | 0.118784E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82758.90 | 0.138336E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155899E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320829E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114168E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223631E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6204738.25 | 0.284803E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114168E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5131064.39 | 0.425986E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20573.73 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20573.73 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20573.73 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20573.73 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20573.73 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20573.73 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20573.73 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20573.73 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20573.73 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20573.73 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20573.73 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20573.73 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3316.54 | 28-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2041.53 | 25-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1490.28 | 25-MAR-03:52 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2268.74 | 01-APR-18:55 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1090.13 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 30-JUN-15:00 | 1100.13 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.64 | 21-JUL-16:00 | 765.29 | 04-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 11-AUG-16:00 | 863.04 | 30-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 722.67 | 04-SEP-13:55 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1383.90 | 21-OCT-04:01 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1132.74 | 10-NOV-01:52 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1204.55 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.67 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 113.64 | 3316.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2187.18 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1350.58 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 988.13 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1486.23 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 724.32 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 30-JUN-15:00 | 712.70 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 29-JUL-19:53 | 486.81 | 04-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-AUG-16:00 | 558.90 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 482.80 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 907.65 | 21-OCT-04:01 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 744.20 | 10-NOV-01:52 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 789.98 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.80 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 2187.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3283.90 | 28-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2032.28 | 25-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1674.35 | 12-MAR-15:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2392.50 | 01-APR-18:55 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1088.10 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 30-JUN-15:00 | 1041.67 | 25-JUN-06:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.45 | 29-JUL-19:53 | 752.88 | 04-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 11-AUG-16:10 | 849.18 | 30-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 696.31 | 04-SEP-13:55 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1351.64 | 22-OCT-17:55 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1124.23 | 10-NOV-01:52 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1181.96 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.31 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 149.45 | 3283.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2289.57 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1415.19 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1042.65 | 12-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1888.17 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 763.34 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 30-JUN-15:00 | 793.12 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 21-JUL-16:00 | 563.03 | 04-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-AUG-16:00 | 629.57 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 502.53 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 967.05 | 21-OCT-04:01 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 797.42 | 10-NOV-01:52 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 845.87 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.53 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 2289.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7780.19 | 28-JAN-23:57 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4611.51 | 25-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3467.09 | 14-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4755.27 | 01-APR-18:55 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2349.21 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 30-JUN-15:00 | 2213.71 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.12 | 21-JUL-16:00 | 1704.04 | 04-JUL-16:55 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.66 | 11-AUG-16:00 | 1851.27 | 30-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1466.90 | 04-SEP-13:55 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3126.13 | 21-OCT-04:58 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2520.87 | 10-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2661.78 | 28-DEC-02:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.90 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 261.12 | 7780.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5186.80 | 28-JAN-23:53 |
February | 1239.33 | 01-FEB-08:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3074.28 | 25-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2313.26 | 14-MAR-21:01 |
April | 1239.33 | 03-APR-07:10 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3194.33 | 01-APR-18:55 |
May | 1239.33 | 01-MAY-07:10 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1570.23 | 26-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 | 30-JUN-15:00 | 1452.96 | 25-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.71 | 29-JUL-20:00 | 1154.08 | 04-JUL-16:55 |
August | 1239.33 | 01-AUG-07:10 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 11-AUG-16:00 | 1215.39 | 30-AUG-01:00 |
September | 1239.33 | 01-SEP-07:10 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1007.65 | 04-SEP-13:55 |
October | 1239.33 | 02-OCT-07:10 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2088.24 | 21-OCT-04:04 |
November | 1239.33 | 01-NOV-07:10 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1689.19 | 10-NOV-05:10 |
December | 1239.33 | 01-DEC-08:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1779.10 | 28-DEC-02:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.65 | |||||
Maximum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 251.71 | 5186.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7780.20 | 28-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4611.73 | 25-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3939.98 | 12-MAR-14:53 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5407.99 | 01-APR-18:55 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2383.75 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 30-JUN-15:00 | 2157.35 | 25-JUN-06:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.84 | 29-JUL-20:00 | 1764.76 | 04-JUL-16:55 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 11-AUG-16:20 | 1846.70 | 30-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1532.53 | 04-SEP-13:55 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3150.85 | 21-OCT-04:45 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2537.20 | 10-NOV-05:04 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2662.33 | 28-DEC-02:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1532.53 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 298.84 | 7780.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5186.78 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3074.31 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2315.02 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3997.35 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1575.24 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 | 30-JUN-15:00 | 1456.99 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 21-JUL-16:00 | 1193.77 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 11-AUG-16:00 | 1234.35 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 996.97 | 04-SEP-13:55 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2097.35 | 21-OCT-04:45 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1689.94 | 10-NOV-05:04 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1771.23 | 28-DEC-02:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 996.97 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 174.08 | 5186.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 9489.08 | 28-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5741.21 | 25-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4299.16 | 14-MAR-21:01 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5467.79 | 01-APR-18:55 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2688.89 | 26-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 | 30-JUN-15:00 | 2503.70 | 24-JUN-21:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.32 | 29-JUL-19:53 | 1998.20 | 04-JUL-16:55 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.35 | 11-AUG-16:00 | 2124.98 | 30-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1727.78 | 30-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3897.34 | 21-OCT-04:45 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3131.29 | 10-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3301.48 | 28-DEC-02:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.78 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 332.32 | 9489.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6378.85 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3827.32 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2868.88 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3674.31 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1813.51 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 30-JUN-15:00 | 1630.21 | 24-JUN-21:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.13 | 29-JUL-19:53 | 1357.94 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 11-AUG-16:00 | 1405.44 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1151.74 | 30-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2598.24 | 21-OCT-04:47 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2103.24 | 10-NOV-05:10 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2201.01 | 28-DEC-02:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.74 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 310.13 | 6378.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 9579.22 | 28-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5741.36 | 25-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4317.92 | 14-MAR-21:01 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6247.98 | 01-APR-18:55 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2754.20 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.75 | 30-JUN-15:00 | 2597.82 | 18-JUN-13:53 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.48 | 29-JUL-19:53 | 2075.68 | 04-JUL-16:55 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 11-AUG-16:20 | 2132.84 | 30-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1735.38 | 30-SEP-21:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3897.35 | 21-OCT-04:45 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3154.90 | 10-NOV-05:10 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3301.46 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1735.38 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 392.48 | 9579.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6383.79 | 28-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3827.43 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2872.21 | 14-MAR-21:01 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4672.52 | 01-APR-18:55 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1815.40 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 | 30-JUN-15:00 | 1670.97 | 24-JUN-21:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.68 | 21-JUL-16:00 | 1406.69 | 04-JUL-16:55 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 11-AUG-16:00 | 1429.20 | 30-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1152.02 | 30-SEP-04:55 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2598.20 | 21-OCT-04:45 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2103.25 | 10-NOV-05:07 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2207.78 | 28-DEC-02:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.02 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 211.68 | 6383.79 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5800.91 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5800.91 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5800.91 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5800.91 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5800.91 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5800.91 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5800.91 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5800.91 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5800.91 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5800.91 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5800.91 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5800.91 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7239.62 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4374.38 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3175.61 | 25-MAR-03:52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4890.21 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2278.04 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.01 | 30-JUN-15:00 | 2241.66 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.49 | 29-JUL-17:02 | 1470.83 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 11-AUG-16:00 | 1794.21 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1425.29 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2951.84 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2430.52 | 10-NOV-01:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2561.31 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.49 | 7239.62 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12609.56 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7627.72 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5481.68 | 25-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 8405.16 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 4013.08 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.46 | 30-JUN-15:00 | 3855.23 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.58 | 29-JUL-17:02 | 2604.66 | 04-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 11-AUG-16:00 | 3149.20 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2405.61 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5080.09 | 21-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4252.31 | 10-NOV-01:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4382.79 | 28-DEC-02:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2405.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.58 | 12609.56 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 13466.84 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8410.82 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6132.90 | 14-MAR-21:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 9093.64 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 4226.08 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.17 | 30-JUN-15:00 | 3931.53 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.09 | 21-JUL-16:00 | 3126.12 | 04-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 11-AUG-18:00 | 3270.99 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2484.15 | 04-SEP-13:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5327.22 | 21-OCT-04:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4489.76 | 10-NOV-01:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4784.27 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2484.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.09 | 13466.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 75276.36 | 12-JAN-07:01 | 25133.15 | 48004.79 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101953.32 | 13-FEB-06:01 | 17952.25 | 22858.58 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 105457.72 | 20-MAR-04:01 | 0.00 | 20572.72 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110454.70 | 24-APR-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111289.56 | 01-MAY-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113088.88 | 05-JUN-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114112.12 | 03-JUL-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115711.29 | 06-AUG-21:42 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 112433.24 | 18-SEP-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 110521.18 | 16-OCT-03:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102943.11 | 06-NOV-06:01 | 16157.03 | 20572.72 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99324.75 | 26-DEC-06:03 | 7180.90 | 9143.43 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 75276.36 | 0.00 | 5715.28 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115711.29 | 25133.15 | 48004.79 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21640.83 | 24-JAN-17:00 | 15316.26 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80073.22 | 10-FEB-06:01 | 12897.91 | 16422.89 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87334.70 | 23-MAR-04:01 | 0.00 | 16422.89 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91848.20 | 24-APR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92240.00 | 01-MAY-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94819.66 | 26-JUN-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96054.39 | 05-JUL-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 92309.27 | 08-AUG-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95721.89 | 05-SEP-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89427.59 | 10-OCT-03:01 | 0.00 | 8212.36 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78489.79 | 02-NOV-05:01 | 12897.91 | 16422.89 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30291.65 | 26-DEC-17:00 | 15316.26 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21640.83 | 0.00 | 5132.72 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96054.39 | 15316.26 | 18476.66 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17078.06 | 27-JAN-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23687.05 | 17-FEB-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61530.92 | 23-MAR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80862.37 | 22-APR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81693.41 | 11-MAY-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83892.91 | 23-JUN-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87557.66 | 05-JUL-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86271.78 | 14-AUG-03:02 | 0.00 | 4106.18 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81401.66 | 02-SEP-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74429.67 | 06-OCT-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19256.33 | 03-NOV-16:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16430.20 | 22-DEC-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16430.20 | 0.00 | 4106.18 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87557.66 | 15316.26 | 18476.66 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13825.55 | 20-JAN-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15942.74 | 09-FEB-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22139.22 | 22-MAR-16:00 | 30632.53 | 36953.32 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45941.52 | 28-APR-10:50 | 45948.79 | 55429.98 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74665.12 | 23-MAY-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80888.95 | 23-JUN-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84589.43 | 24-JUL-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81533.86 | 03-AUG-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38504.50 | 08-SEP-10:20 | 45948.79 | 55429.98 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24982.98 | 05-OCT-16:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14126.82 | 02-NOV-16:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12864.87 | 21-DEC-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12864.87 | 0.00 | 5132.72 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84589.43 | 45948.79 | 55429.98 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1924.33 | 20-JAN-06:04 | 1619.46 | 2062.06 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 |
February | 2741.93 | 09-FEB-06:02 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 |
March | 3615.52 | 22-MAR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6268.93 | 28-APR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13822.34 | 31-MAY-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
June | 15059.13 | 16-JUN-03:42 | 0.00 | 515.57 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.68 |
July | 15479.65 | 11-JUL-05:03 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 |
August | 12971.61 | 07-AUG-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 |
September | 6089.04 | 01-SEP-13:40 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 |
October | 3824.06 | 04-OCT-14:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.01 |
November | 2189.48 | 02-NOV-14:10 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1921.44 | 26-DEC-12:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1921.44 | 0.00 | 515.57 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15479.65 | 2010.79 | 2319.93 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2499.79 | 07-JAN-06:03 | 782.73 | 996.65 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.03 |
February | 3161.60 | 15-FEB-10:50 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.66 |
March | 7049.42 | 27-MAR-09:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.70 |
April | 11385.03 | 23-APR-10:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.05 |
May | 23338.93 | 14-MAY-08:51 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.93 |
June | 21623.75 | 04-JUN-09:12 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.87 |
July | 21389.62 | 23-JUL-10:02 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 |
August | 16658.34 | 27-AUG-10:42 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.81 |
September | 13655.87 | 10-SEP-10:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.58 |
October | 6824.62 | 03-OCT-09:45 | 2591.66 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.75 |
November | 2524.87 | 02-NOV-05:02 | 1043.64 | 1328.87 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 |
December | 2492.21 | 18-DEC-06:04 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2492.21 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 | |
Maximum of Months | 23338.93 | 2591.66 | 2990.10 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4678.58 | 25-JAN-13:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.16 |
February | 10714.89 | 15-FEB-13:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16870.92 | 31-MAR-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.23 |
April | 32686.50 | 23-APR-12:12 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.10 |
May | 33763.47 | 14-MAY-11:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.35 |
June | 32577.85 | 04-JUN-13:52 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.33 |
July | 34071.90 | 23-JUL-13:22 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 |
August | 36479.14 | 27-AUG-12:41 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.03 |
September | 25347.20 | 10-SEP-10:52 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.05 |
October | 17978.18 | 03-OCT-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.74 |
November | 7374.13 | 08-NOV-13:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.39 |
December | 3554.15 | 23-DEC-17:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3554.15 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36479.14 | 2010.83 | 2319.98 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3003.13 | 07-JAN-06:03 | 782.73 | 996.65 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.37 |
February | 4871.56 | 09-FEB-06:02 | 782.73 | 996.65 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 |
March | 8000.72 | 27-MAR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.52 |
April | 24009.72 | 22-APR-17:04 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.86 |
May | 25407.57 | 29-MAY-18:42 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 |
June | 25479.69 | 11-JUN-16:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.24 |
July | 26048.04 | 09-JUL-19:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 |
August | 25948.49 | 27-AUG-17:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.39 |
September | 12765.01 | 01-SEP-03:02 | 0.00 | 498.38 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.75 |
October | 6632.17 | 03-OCT-14:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 |
November | 4652.71 | 02-NOV-05:01 | 1043.64 | 1328.87 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 |
December | 3653.31 | 26-DEC-05:01 | 0.00 | 1162.76 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3003.13 | 0.00 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | |
Maximum of Months | 26048.04 | 1239.33 | 1495.05 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1647.07 | 21-JAN-17:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 |
February | 1776.89 | 10-FEB-16:20 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.03 |
March | 2793.32 | 22-MAR-16:10 | 1214.60 | 2577.69 | 2529.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4491.25 | 28-APR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12580.94 | 31-MAY-04:42 | 0.00 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13748.61 | 29-JUN-04:52 | 0.00 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.62 |
July | 13821.22 | 11-JUL-05:05 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.40 |
August | 9480.78 | 05-AUG-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 |
September | 4548.03 | 25-SEP-13:50 | 4021.58 | 4639.86 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.07 |
October | 4379.33 | 10-OCT-15:50 | 7692.44 | 9279.72 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.35 |
November | 1648.25 | 04-NOV-16:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1640.21 | 23-DEC-17:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1640.21 | 0.00 | 773.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13821.22 | 7692.44 | 9279.72 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2711.61 | 18-JAN-06:04 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 |
February | 2734.95 | 15-FEB-11:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.19 |
March | 5445.23 | 22-MAR-10:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.81 |
April | 13669.54 | 13-APR-10:10 | 4957.30 | 5980.20 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.29 |
May | 24794.69 | 21-MAY-09:01 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.05 |
June | 18377.78 | 08-JUN-05:02 | 652.28 | 830.54 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 |
July | 25999.12 | 23-JUL-09:41 | 521.82 | 664.51 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.20 |
August | 15402.96 | 10-AUG-09:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.66 |
September | 17303.25 | 10-SEP-10:02 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.12 |
October | 6181.11 | 03-OCT-10:20 | 3717.98 | 4485.15 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.44 |
November | 2666.69 | 14-NOV-06:04 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.19 |
December | 2669.98 | 20-DEC-06:04 | 1043.64 | 1328.87 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2666.69 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25999.12 | 4957.30 | 5980.20 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4644.55 | 25-JAN-13:40 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.00 |
February | 10369.29 | 15-FEB-13:40 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18026.48 | 31-MAR-13:50 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.44 |
April | 33203.84 | 09-APR-14:42 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.72 |
May | 36381.04 | 21-MAY-13:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1346.28 |
June | 26124.33 | 11-JUN-15:02 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.27 |
July | 40356.35 | 23-JUL-13:41 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.76 |
August | 35647.05 | 27-AUG-13:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.63 |
September | 25987.32 | 10-SEP-12:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.44 |
October | 19056.77 | 13-OCT-13:50 | 6032.50 | 6959.94 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.16 |
November | 5999.12 | 08-NOV-14:00 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.32 |
December | 4063.25 | 20-DEC-06:04 | 1619.50 | 2062.10 | 8093.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4063.25 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40356.35 | 6032.50 | 6959.94 | 8093.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1346.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2791.35 | 18-JAN-06:04 | 913.19 | 1162.76 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 |
February | 2754.92 | 09-FEB-06:03 | 782.73 | 996.65 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.46 |
March | 4422.90 | 22-MAR-16:10 | 782.73 | 1661.16 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15860.90 | 13-APR-17:08 | 521.82 | 1993.38 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.02 |
May | 23036.44 | 21-MAY-18:22 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.14 |
June | 24130.18 | 11-JUN-17:02 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.14 |
July | 22958.42 | 08-JUL-18:32 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.31 |
August | 18516.46 | 27-AUG-17:32 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.75 |
September | 8512.65 | 02-SEP-17:14 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.18 |
October | 6549.71 | 10-OCT-15:50 | 4957.30 | 5980.20 | 5867.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.91 |
November | 2728.91 | 17-NOV-06:03 | 1174.10 | 1494.98 | 5867.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2772.75 | 19-DEC-06:04 | 1043.64 | 1328.87 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2728.91 | 0.00 | 415.32 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24130.18 | 4957.30 | 5980.20 | 5867.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2018.25 | 21-JAN-17:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 |
February | 2024.30 | 11-FEB-17:02 | 506.08 | 644.46 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.98 |
March | 2593.21 | 22-MAR-16:00 | 3846.22 | 4639.86 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3616.06 | 13-APR-12:08 | 7692.44 | 9279.72 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.49 |
May | 9051.59 | 31-MAY-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
June | 16460.56 | 19-JUN-04:42 | 0.00 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.82 |
July | 17305.56 | 11-JUL-05:02 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.29 |
August | 7734.17 | 02-AUG-15:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
September | 3397.86 | 01-SEP-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.80 |
October | 2732.12 | 04-OCT-15:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 |
November | 2015.61 | 04-NOV-16:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2011.82 | 23-DEC-17:02 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2011.82 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17305.56 | 7692.44 | 9279.72 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2330.86 | 21-JAN-17:02 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 |
February | 2658.03 | 23-FEB-06:04 | 1174.10 | 1494.98 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3815.06 | 22-MAR-10:40 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 |
April | 11076.28 | 21-APR-09:50 | 3887.49 | 4485.15 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.28 |
May | 24350.57 | 14-MAY-10:11 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.49 |
June | 18082.92 | 08-JUN-05:02 | 652.28 | 830.54 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.82 |
July | 23998.01 | 23-JUL-11:51 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16437.94 | 27-AUG-10:32 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.33 |
September | 9013.95 | 08-SEP-10:20 | 3717.98 | 4485.15 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 |
October | 3632.87 | 03-OCT-10:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.30 |
November | 2678.50 | 17-NOV-06:04 | 1174.10 | 1494.98 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2321.98 | 23-DEC-17:02 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2321.98 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24350.57 | 3887.49 | 4485.15 | 5867.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3846.95 | 25-JAN-06:04 | 1821.93 | 2319.87 | 9105.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6520.77 | 15-FEB-13:50 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14495.15 | 31-MAR-14:20 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.79 |
April | 26460.86 | 13-APR-12:08 | 7692.61 | 9279.92 | 9105.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.95 |
May | 36767.36 | 14-MAY-13:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.64 |
June | 22020.20 | 04-JUN-14:43 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.12 |
July | 39313.39 | 23-JUL-11:51 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39892.96 | 27-AUG-13:11 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.84 |
September | 18297.76 | 08-SEP-14:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.02 |
October | 15127.63 | 03-OCT-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.33 |
November | 5157.19 | 08-NOV-13:50 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.13 |
December | 4237.34 | 23-DEC-06:04 | 1821.93 | 2319.87 | 9105.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3846.95 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39892.96 | 7692.61 | 9279.92 | 9105.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2480.69 | 21-JAN-17:02 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
February | 2916.36 | 03-FEB-06:04 | 1043.64 | 1328.87 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.23 |
March | 3632.84 | 22-MAR-16:00 | 2478.65 | 2990.10 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13792.96 | 13-APR-17:00 | 1565.46 | 3322.32 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.12 |
May | 21263.31 | 21-MAY-18:22 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.11 |
June | 21106.43 | 10-JUN-17:42 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.56 |
July | 16877.01 | 30-JUL-19:32 | 0.00 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.56 |
August | 23873.33 | 27-AUG-17:51 | 0.00 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.36 |
September | 7145.96 | 08-SEP-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 |
October | 3558.41 | 03-OCT-15:20 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.61 |
November | 2864.65 | 02-NOV-05:04 | 1043.64 | 1328.87 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.69 |
December | 2481.58 | 23-DEC-17:02 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2480.69 | 0.00 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23873.33 | 2478.65 | 3322.32 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5715.46 | 12-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.63 |
February | 4751.01 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3121.39 |
March | 4864.21 | 21-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6207.61 | 21-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.70 |
May | 7683.78 | 31-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 |
June | 10765.84 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.34 |
July | 12108.56 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.10 |
August | 10826.61 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
September | 8839.59 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 |
October | 5991.54 | 03-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.72 |
November | 4288.34 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4484.48 | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4288.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12108.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3121.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9973.02 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5208.96 |
February | 8695.68 | 25-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2544.32 |
March | 8707.65 | 03-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3824.88 |
April | 8019.94 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4124.69 |
May | 5981.02 | 16-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.66 |
June | 6834.46 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 0.00 |
July | 7727.34 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.37 |
August | 7677.01 | 26-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.04 |
September | 6296.33 | 14-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 |
October | 8507.34 | 23-OCT-03:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2261.89 |
November | 8995.49 | 10-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.45 |
December | 9051.53 | 09-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5981.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9973.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 5208.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.45 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2277.88 |
March | 1273.25 | 22-MAR-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7273.88 | 20-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.13 |
May | 13497.00 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 |
June | 15078.08 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
July | 15595.06 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 | 0.00 |
August | 12790.25 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 |
September | 4917.72 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.68 |
October | 1546.93 | 04-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2514.31 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15595.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 | 2693.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1015.44 | 25-JAN-15:00 | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3505.14 | 15-FEB-16:10 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6684.60 | 31-MAR-24:00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8540.14 | 20-APR-18:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3476.87 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5350.08 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7270.52 | 31-JUL-23:40 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8354.46 | 27-AUG-18:53 | 0.00 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2898.82 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4409.75 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5437.94 | 08-NOV-16:00 | 444.28 | 763.15 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6868.67 | 26-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1015.44 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8540.14 | 444.28 | 763.15 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 645.53 | 12-JAN-10:00 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3027.19 | 16-FEB-16:10 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5821.05 | 31-MAR-23:20 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8136.18 | 20-APR-18:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3245.02 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5148.44 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7034.63 | 31-JUL-23:55 | 0.00 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7804.41 | 27-AUG-18:46 | 0.00 | 105.99 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2179.03 | 30-SEP-23:50 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3439.61 | 12-OCT-16:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4811.97 | 08-NOV-15:50 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6007.02 | 21-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 645.53 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8136.18 | 222.14 | 381.58 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 624.71 | 12-JAN-08:15 | 444.28 | 763.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2632.17 | 09-FEB-16:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5099.21 | 31-MAR-17:30 | 23.38 | 127.19 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8126.93 | 20-APR-18:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3193.19 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5108.64 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6998.13 | 31-JUL-23:40 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7833.78 | 10-AUG-19:00 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1883.51 | 06-SEP-17:50 | 23.38 | 127.19 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3253.96 | 03-OCT-16:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4313.32 | 08-NOV-15:50 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5501.69 | 21-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 624.71 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8126.93 | 444.28 | 763.15 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89099.93 | 20-JAN-17:00 | 4808.68 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181056.59 | 09-FEB-17:00 | 4808.68 | 5800.91 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 356817.45 | 31-MAR-24:00 | 0.00 | 322.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367294.20 | 21-APR-16:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175686.57 | 31-MAY-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267472.32 | 30-JUN-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360185.21 | 31-JUL-23:55 | 0.00 | 1289.17 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368873.22 | 28-AUG-16:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 174656.83 | 30-SEP-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265564.02 | 31-OCT-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274042.88 | 03-NOV-16:00 | 4808.68 | 5800.91 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 364943.33 | 27-DEC-17:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89099.93 | 0.00 | 322.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368873.22 | 4808.68 | 5800.91 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.173785E+13 | 1096689.96 | 12-JAN-08:09 | 0.190672E+13 | 3665692.87 | 12-JAN-07:10 |
February | 0.191135E+13 | 1244108.74 | 22-FEB-08:30 | 0.123413E+13 | 3875105.37 | 27-FEB-07:10 |
March | 0.253720E+13 | 1403699.01 | 22-MAR-15:00 | 0.763701E+12 | 3115263.58 | 01-MAR-07:10 |
April | 0.281683E+13 | 1657616.94 | 21-APR-15:50 | 0.249734E+12 | 1477320.83 | 08-APR-06:10 |
May | 0.181284E+13 | 1432085.60 | 31-MAY-15:09 | 0.976891E+11 | 877421.91 | 27-MAY-06:10 |
June | 0.232571E+13 | 1676662.19 | 20-JUN-15:39 | 0.804467E+11 | 329116.36 | 02-JUN-06:10 |
July | 0.278267E+13 | 1854646.14 | 11-JUL-15:00 | 0.761179E+11 | 187275.29 | 17-JUL-06:10 |
August | 0.317496E+13 | 1988589.75 | 11-AUG-15:39 | 0.860788E+11 | 969896.38 | 31-AUG-06:10 |
September | 0.167060E+13 | 1217610.93 | 07-SEP-15:50 | 0.148268E+12 | 1259263.10 | 29-SEP-06:10 |
October | 0.211382E+13 | 1271113.76 | 12-OCT-15:30 | 0.516105E+12 | 1974637.25 | 23-OCT-06:10 |
November | 0.244834E+13 | 1395116.72 | 27-NOV-08:50 | 0.156907E+13 | 3310938.14 | 27-NOV-07:10 |
December | 0.290870E+13 | 1543349.74 | 28-DEC-08:00 | 0.210784E+13 | 3339839.38 | 15-DEC-07:10 |
Annual Sum or Average | 0.282409E+14 | 0.883591E+13 | ||||
Minimum of Months | 0.167060E+13 | 1096689.96 | 0.761179E+11 | 187275.29 | ||
Maximum of Months | 0.317496E+13 | 1988589.75 | 0.210784E+13 | 3875105.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328950E+12 | 0.123890E+12 | 0.811612E+12 | 0.169596E+12 | 0.183311E+12 | 0.171837E+11 | 0.00 | 0.793142E+11 | 0.485606E+10 | 0.136290E+11 | 0.551192E+10 | 0.00 | 0.00 |
February | 0.298382E+12 | 0.926932E+11 | 0.102011E+13 | 0.153195E+12 | 0.163827E+12 | 0.131644E+11 | 0.00 | 0.136676E+12 | 0.863479E+10 | 0.196171E+11 | 0.505131E+10 | 0.00 | 0.00 |
March | 0.354561E+12 | 0.808777E+11 | 0.146267E+13 | 0.169879E+12 | 0.182930E+12 | 0.127667E+11 | 0.00 | 0.223272E+12 | 0.156908E+11 | 0.285923E+11 | 0.596479E+10 | 0.00 | 0.00 |
April | 0.316695E+12 | 0.569357E+11 | 0.170311E+13 | 0.164100E+12 | 0.198545E+12 | 0.112780E+11 | 0.00 | 0.282987E+12 | 0.498326E+11 | 0.291382E+11 | 0.420920E+10 | 0.00 | 0.00 |
May | 0.341755E+12 | 0.372086E+11 | 0.820521E+12 | 0.169738E+12 | 0.235472E+12 | 0.286872E+11 | 0.00 | 0.121588E+12 | 0.461666E+11 | 0.100987E+11 | 0.160367E+10 | 0.00 | 0.00 |
June | 0.340103E+12 | 0.207290E+11 | 0.110677E+13 | 0.164363E+12 | 0.263043E+12 | 0.558252E+11 | 0.00 | 0.255150E+12 | 0.109791E+12 | 0.935003E+10 | 0.583145E+09 | 0.00 | 0.00 |
July | 0.318348E+12 | 0.288133E+11 | 0.143888E+13 | 0.169473E+12 | 0.259839E+12 | 0.651126E+11 | 0.00 | 0.361992E+12 | 0.129972E+12 | 0.955602E+10 | 0.687798E+09 | 0.00 | 0.00 |
August | 0.354561E+12 | 0.497151E+11 | 0.177780E+13 | 0.169879E+12 | 0.249253E+12 | 0.481651E+11 | 0.00 | 0.382442E+12 | 0.123379E+12 | 0.188149E+11 | 0.951267E+09 | 0.00 | 0.00 |
September | 0.316695E+12 | 0.691313E+11 | 0.784732E+12 | 0.164097E+12 | 0.190818E+12 | 0.141710E+11 | 0.00 | 0.956166E+11 | 0.222242E+11 | 0.937726E+10 | 0.373953E+10 | 0.00 | 0.00 |
October | 0.328950E+12 | 0.932460E+11 | 0.112899E+13 | 0.169597E+12 | 0.180085E+12 | 0.126213E+11 | 0.00 | 0.159368E+12 | 0.170419E+11 | 0.185936E+11 | 0.532594E+10 | 0.00 | 0.00 |
November | 0.325095E+12 | 0.111833E+12 | 0.140306E+13 | 0.164207E+12 | 0.173161E+12 | 0.150665E+11 | 0.00 | 0.211612E+12 | 0.117286E+11 | 0.272342E+11 | 0.534303E+10 | 0.00 | 0.00 |
December | 0.318348E+12 | 0.132666E+12 | 0.175516E+13 | 0.169471E+12 | 0.181507E+12 | 0.169252E+11 | 0.00 | 0.279651E+12 | 0.149150E+11 | 0.346107E+11 | 0.545051E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394244E+13 | 0.897739E+12 | 0.152134E+14 | 0.199759E+13 | 0.246179E+13 | 0.310967E+12 | 0.00 | 0.258967E+13 | 0.554232E+12 | 0.228612E+12 | 0.444221E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298382E+12 | 0.207290E+11 | 0.784732E+12 | 0.153195E+12 | 0.163827E+12 | 0.112780E+11 | 0.00 | 0.793142E+11 | 0.485606E+10 | 0.935003E+10 | 0.583145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.354561E+12 | 0.132666E+12 | 0.177780E+13 | 0.169879E+12 | 0.263043E+12 | 0.651126E+11 | 0.00 | 0.382442E+12 | 0.129972E+12 | 0.346107E+11 | 0.596479E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.182514E+13 | 0.00 | 0.815844E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116015E+13 | 0.00 | 0.739860E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.678134E+12 | 0.00 | 0.855676E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.170780E+12 | 0.00 | 0.789536E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.145991E+11 | 0.00 | 0.830899E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.815595E+09 | 0.00 | 0.796311E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.618916E+09 | 0.00 | 0.754990E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.699165E+10 | 0.00 | 0.790872E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.753116E+11 | 0.00 | 0.729561E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.439756E+12 | 0.00 | 0.763486E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149254E+13 | 0.00 | 0.765247E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.202858E+13 | 0.00 | 0.792694E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.789341E+13 | 0.00 | 0.942498E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.618916E+09 | 0.00 | 0.729561E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.202858E+13 | 0.00 | 0.855676E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 344233.60 | 02-JAN-08:09 | 57580.60 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 120520.01 | 02-JAN-08:20 | 113820.94 | 02-JAN-06:19 | 36941.23 | 09-JAN-06:30 | 0.00 | 01-JAN-00:10 |
February | 344233.60 | 01-FEB-08:09 | 57580.60 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 120520.01 | 01-FEB-08:20 | 102874.98 | 27-FEB-06:10 | 36160.28 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 344233.60 | 01-MAR-08:09 | 57580.60 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 120520.01 | 01-MAR-08:20 | 186254.78 | 22-MAR-16:10 | 34845.65 | 30-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 344233.60 | 03-APR-07:10 | 57580.60 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 120520.01 | 03-APR-07:19 | 219534.14 | 21-APR-15:50 | 34431.26 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 344233.60 | 01-MAY-07:10 | 57580.60 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 120520.01 | 01-MAY-07:19 | 244500.15 | 31-MAY-15:20 | 58094.13 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 344233.60 | 01-JUN-07:10 | 57580.60 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 120520.01 | 01-JUN-07:19 | 268571.22 | 30-JUN-12:09 | 61982.85 | 21-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 344233.60 | 03-JUL-07:10 | 57580.60 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 120520.01 | 03-JUL-07:19 | 284369.36 | 12-JUL-15:20 | 62272.95 | 21-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 344233.60 | 01-AUG-07:10 | 57580.60 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 120520.01 | 01-AUG-07:19 | 277485.19 | 10-AUG-15:00 | 62306.02 | 11-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 344233.60 | 01-SEP-07:10 | 57580.60 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 120520.01 | 01-SEP-07:19 | 199337.63 | 28-SEP-11:30 | 36368.91 | 07-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 344233.60 | 02-OCT-07:10 | 57580.60 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 120520.01 | 02-OCT-07:19 | 198103.30 | 12-OCT-15:30 | 35498.27 | 30-OCT-04:00 | 0.00 | 01-OCT-00:10 |
November | 344233.60 | 01-NOV-07:10 | 57580.60 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 120520.01 | 01-NOV-07:19 | 99079.78 | 27-NOV-06:10 | 35815.64 | 06-NOV-06:30 | 0.00 | 01-NOV-00:10 |
December | 344233.60 | 01-DEC-08:09 | 57580.60 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 120520.01 | 01-DEC-08:20 | 103496.55 | 04-DEC-06:10 | 36430.65 | 26-DEC-06:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 344233.60 | 57580.60 | 439129.89 | 120520.01 | 99079.78 | 34431.26 | 0.00 | |||||||
Maximum of Months | 344233.60 | 57580.60 | 794004.08 | 120520.01 | 284369.36 | 62306.02 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 35071.97 | 27-JAN-06:40 | 3206.11 | 21-JAN-20:00 | 11065.16 | 12-JAN-18:10 | 4264.87 | 07-JAN-17:10 | 0.00 | 0.00 |
February | 68370.31 | 10-FEB-15:00 | 6891.97 | 10-FEB-16:10 | 14521.90 | 18-FEB-07:10 | 4264.87 | 04-FEB-17:10 | 0.00 | 0.00 |
March | 108161.69 | 31-MAR-23:19 | 19852.82 | 20-MAR-14:00 | 18624.71 | 04-MAR-07:00 | 4264.87 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 144127.78 | 20-APR-14:09 | 49249.48 | 20-APR-14:30 | 19750.46 | 03-APR-06:10 | 4264.87 | 01-APR-06:10 | 0.00 | 0.00 |
May | 212124.99 | 31-MAY-15:00 | 57936.40 | 31-MAY-15:09 | 7597.74 | 05-MAY-06:00 | 4264.87 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 305180.18 | 30-JUN-12:20 | 81628.52 | 29-JUN-11:50 | 9325.77 | 02-JUN-06:10 | 4264.87 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 340179.00 | 21-JUL-14:50 | 81628.52 | 03-JUL-14:00 | 11160.03 | 31-JUL-06:10 | 4264.87 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 377653.12 | 11-AUG-15:20 | 81628.52 | 23-AUG-14:20 | 18260.81 | 30-AUG-06:10 | 4264.87 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 90086.19 | 07-SEP-15:00 | 49327.39 | 07-SEP-15:00 | 8514.76 | 30-SEP-16:10 | 4264.87 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 83023.43 | 31-OCT-23:30 | 38255.20 | 01-OCT-14:00 | 14340.82 | 30-OCT-19:00 | 4264.87 | 28-OCT-16:10 | 0.00 | 0.00 |
November | 86563.54 | 09-NOV-06:00 | 6547.51 | 18-NOV-03:00 | 18910.49 | 27-NOV-07:00 | 4264.87 | 04-NOV-16:10 | 0.00 | 0.00 |
December | 108584.79 | 09-DEC-06:00 | 15947.26 | 24-DEC-11:00 | 23714.49 | 28-DEC-07:10 | 4264.87 | 15-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 35071.97 | 3206.11 | 7597.74 | 4264.87 | 0.00 | 0.00 | ||||
Maximum of Months | 377653.12 | 81628.52 | 23714.49 | 4264.87 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1096689.96 | 12-JAN-08:09 | 344233.60 | 439129.89 | 57580.60 | 120330.96 | 82955.68 | 12417.65 | 0.00 | 26053.98 | 999.06 |
February | 1244108.74 | 22-FEB-08:30 | 344233.60 | 557421.28 | 57580.60 | 120520.01 | 81996.74 | 11912.41 | 0.00 | 51795.91 | 2257.76 |
March | 1403699.01 | 22-MAR-15:00 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 175567.63 | 3711.23 | 0.00 | 86327.74 | 17487.14 |
April | 1657616.94 | 21-APR-15:50 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 219534.14 | 32285.95 | 0.00 | 123729.87 | 49248.27 |
May | 1432085.60 | 31-MAY-15:09 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 244157.29 | 57808.02 | 0.00 | 201709.46 | 57936.40 |
June | 1676662.19 | 20-JUN-15:39 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 267344.97 | 61961.75 | 0.00 | 289937.14 | 64909.15 |
July | 1854646.14 | 11-JUL-15:00 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 272192.00 | 60890.26 | 0.00 | 333049.48 | 77713.82 |
August | 1988589.75 | 11-AUG-15:39 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 271883.30 | 62306.02 | 0.00 | 360971.91 | 64336.55 |
September | 1217610.93 | 07-SEP-15:50 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 170996.46 | 36177.09 | 0.00 | 88008.92 | 49309.73 |
October | 1271113.76 | 12-OCT-15:30 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 198103.30 | 3734.54 | 0.00 | 61803.49 | 5791.11 |
November | 1395116.72 | 27-NOV-08:50 | 344233.60 | 675712.68 | 57580.60 | 120520.01 | 82935.10 | 11701.34 | 0.00 | 77931.09 | 3532.10 |
December | 1543349.74 | 28-DEC-08:00 | 344233.60 | 794004.08 | 57580.60 | 120520.01 | 81471.02 | 11693.76 | 0.00 | 103476.85 | 4450.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1096689.96 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 81471.02 | 3711.23 | 0.00 | 26053.98 | 999.06 | |
Maximum of Months | 1988589.75 | 344233.60 | 794004.08 | 57580.60 | 120520.01 | 272192.00 | 62306.02 | 0.00 | 360971.91 | 77713.82 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3632416.99 | 12-JAN-07:10 | 0.00 | 90169.09 | 26-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 3841258.89 | 27-FEB-07:10 | 0.00 | 90171.74 | 27-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 3083486.19 | 01-MAR-07:10 | 0.00 | 90199.20 | 31-MAR-11:30 | 0.00 |
April | 0.00 | 0.00 | 1446740.97 | 08-APR-06:10 | 0.00 | 90179.85 | 06-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 846877.49 | 27-MAY-06:10 | 0.00 | 90156.25 | 10-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 296109.30 | 02-JUN-06:10 | 0.00 | 89452.54 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 154719.93 | 17-JUL-06:10 | 0.00 | 88205.49 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 939682.47 | 31-AUG-06:10 | 0.00 | 87283.77 | 02-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 1232399.50 | 29-SEP-06:10 | 0.00 | 87105.01 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 1942101.75 | 23-OCT-06:10 | 0.00 | 87995.24 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 3278640.67 | 27-NOV-07:10 | 0.00 | 89140.17 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 3306119.25 | 15-DEC-07:10 | 0.00 | 90163.26 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 154719.93 | 0.00 | 87105.01 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3841258.89 | 0.00 | 90199.20 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.76 | 0.00 | 25.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.73 | 0.00 | 25.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.80 | 0.00 | 25.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.52 | 0.00 | 26.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.01 | 0.00 | 26.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.57 | 0.17 | 26.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.32 | 0.00 | 26.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.00 | 26.29 | 0.17 | 26.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.57 | 0.17 | 26.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.59 | 0.00 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 25.65 | 0.00 | 25.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.27 | 1.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
February | 0.17 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 3.17 | 19.20 | 1.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.27 | 1.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 18.79 | 2.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 7.33 | 18.76 | 1.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
March | 2.17 | 18.55 | 0.17 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
April | 0.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.73 | 0.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
November | 7.33 | 18.52 | 1.17 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
December | 8.67 | 18.66 | 1.50 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Annual Sum or Average | 37.17 | 18.68 | 7.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 18.79 | 2.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.85 | 1.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 3.33 | 18.86 | 0.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 1.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.79 | 0.00 | 25.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.90 | 0.50 | 25.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.84 | 0.33 | 25.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 4.00 | 19.16 | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 16.50 | 18.97 | 1.33 | 19.07 | 11.33 | 21.71 | 0.83 | 21.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 19.16 | 1.00 | 19.21 | 7.50 | 25.90 | 0.50 | 25.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
February | 3.00 | 18.73 | 0.17 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
March | 1.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.09 | 2.83 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.53 | 0.83 | 26.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 2.17 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.72 | 0.67 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 4.83 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Annual Sum or Average | 17.17 | 18.73 | 0.17 | 18.74 | 10.00 | 21.90 | 6.83 | 23.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.33 | 19.03 | 0.17 | 19.03 | 3.17 | 28.09 | 2.83 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 18.18 | 0.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
February | 3.17 | 18.64 | 0.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 1.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.65 | 2.17 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.98 | 2.67 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.74 | 2.17 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.09 | 3.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.21 | 1.83 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.99 | 0.17 | 27.99 |
October | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
November | 2.67 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
December | 5.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Annual Sum or Average | 19.83 | 18.59 | 0.33 | 18.57 | 12.17 | 22.10 | 12.00 | 23.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 0.00 | 18.11 |
Maximum of Months | 7.33 | 19.13 | 0.17 | 19.13 | 3.00 | 28.21 | 3.00 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 1.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.90 | 2.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.05 | 1.50 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.98 | 1.83 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.47 | 5.00 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.52 | 3.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 19.14 | 0.00 | 19.14 | 42.00 | 26.96 | 14.00 | 27.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.28 | 0.00 | 19.28 | 13.67 | 28.05 | 5.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.00 | 16.98 | 30.33 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 41.00 | 17.27 | 16.17 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
March | 18.83 | 18.77 | 4.83 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
April | 4.50 | 18.35 | 0.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.92 | 0.00 | 25.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.63 | 0.33 | 25.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8.67 | 18.13 | 1.50 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
November | 31.83 | 17.97 | 11.67 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
December | 49.67 | 17.82 | 21.50 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
Annual Sum or Average | 223.50 | 17.58 | 86.83 | 17.79 | 6.00 | 17.94 | 0.33 | 17.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.00 | 18.77 | 30.33 | 19.03 | 4.00 | 25.92 | 0.33 | 25.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 15.39 | 12.83 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
February | 21.33 | 15.94 | 4.00 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
March | 8.17 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
April | 2.17 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.45 | 2.67 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.75 | 0.83 | 27.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.94 | 3.17 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
October | 3.83 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
November | 17.33 | 16.61 | 2.50 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
December | 28.50 | 16.05 | 6.83 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Annual Sum or Average | 123.50 | 16.10 | 26.17 | 15.86 | 8.83 | 16.53 | 7.50 | 17.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 | 15.20 |
Maximum of Months | 42.17 | 18.40 | 12.83 | 18.40 | 3.50 | 28.45 | 3.17 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.67 | 15.61 | 9.33 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
February | 12.00 | 16.67 | 1.83 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
March | 6.67 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
April | 1.17 | 18.42 | 0.00 | 18.42 | 1.83 | 24.07 | 1.83 | 25.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.03 | 3.83 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.76 | 1.83 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.36 | 2.67 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.31 | 1.83 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.81 | 0.33 | 27.81 |
October | 3.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
November | 12.00 | 17.44 | 0.33 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
December | 24.00 | 16.28 | 5.83 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Annual Sum or Average | 93.50 | 16.47 | 17.33 | 16.21 | 12.50 | 17.41 | 12.33 | 18.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 | 15.40 |
Maximum of Months | 34.67 | 18.43 | 9.33 | 18.43 | 3.83 | 28.36 | 3.83 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 15.62 | 9.83 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
February | 13.33 | 16.54 | 2.33 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
March | 7.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
April | 1.17 | 18.36 | 0.00 | 18.36 | 0.50 | 21.11 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.87 | 0.50 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.82 | 0.83 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.53 | 0.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.15 | 0.33 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
November | 9.50 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
December | 16.33 | 17.00 | 2.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Annual Sum or Average | 83.67 | 16.67 | 14.33 | 16.39 | 10.17 | 17.47 | 2.00 | 17.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 18.36 | 9.83 | 18.36 | 3.67 | 28.15 | 0.83 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.33 | 16.44 | 52.67 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
February | 95.33 | 16.44 | 41.00 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
March | 75.33 | 17.03 | 26.33 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
April | 24.33 | 16.53 | 7.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
May | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.67 | 0.00 | 25.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.90 | 0.00 | 25.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
October | 40.00 | 16.64 | 13.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
November | 98.00 | 16.61 | 43.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
December | 132.67 | 16.77 | 57.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
Annual Sum or Average | 588.50 | 16.64 | 240.83 | 16.95 | 2.00 | 16.97 | 0.00 | 16.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.67 | 19.33 | 57.50 | 19.33 | 1.33 | 25.90 | 0.00 | 25.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 14.79 | 18.50 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
February | 56.00 | 15.08 | 14.17 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
March | 33.00 | 15.76 | 1.83 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
April | 12.00 | 16.27 | 0.83 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
May | 0.17 | 19.36 | 0.00 | 19.36 | 2.50 | 27.61 | 2.50 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.97 | 0.50 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.90 | 3.33 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
October | 24.00 | 15.68 | 5.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
November | 61.83 | 14.97 | 18.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
December | 76.67 | 14.92 | 19.67 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
Annual Sum or Average | 333.50 | 15.13 | 78.50 | 15.02 | 6.83 | 15.23 | 6.33 | 15.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.67 | 19.36 | 19.67 | 19.36 | 3.50 | 27.90 | 3.33 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.33 | 14.84 | 16.50 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
February | 43.17 | 15.32 | 7.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 23.00 | 16.27 | 2.00 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
April | 8.00 | 16.80 | 1.00 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
May | 0.17 | 19.38 | 0.00 | 19.38 | 2.33 | 27.43 | 2.33 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.70 | 1.83 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.43 | 2.50 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.50 | 1.33 | 28.55 |
September | 0.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
October | 19.67 | 15.99 | 3.00 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
November | 53.17 | 15.13 | 15.67 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
December | 72.50 | 14.97 | 17.83 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 283.83 | 15.27 | 63.83 | 15.14 | 8.33 | 15.45 | 8.00 | 15.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 0.00 | 14.75 |
Maximum of Months | 72.50 | 19.38 | 17.83 | 19.38 | 2.67 | 28.50 | 2.50 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.17 | 14.82 | 16.67 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
February | 47.67 | 15.23 | 13.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
March | 23.33 | 16.21 | 2.33 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
April | 7.50 | 16.91 | 1.83 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
May | 0.17 | 19.37 | 0.00 | 19.37 | 2.17 | 26.99 | 0.17 | 27.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.89 | 0.67 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 0.17 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.02 | 0.17 | 27.97 |
September | 0.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
October | 19.50 | 16.00 | 3.67 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
November | 49.67 | 15.28 | 15.33 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
December | 56.17 | 15.14 | 14.83 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
Annual Sum or Average | 265.83 | 15.33 | 67.67 | 15.19 | 7.50 | 15.46 | 1.17 | 15.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 | 0.00 | 14.70 |
Maximum of Months | 61.17 | 19.37 | 16.67 | 19.37 | 3.17 | 28.02 | 0.67 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.79 | 12.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 27.79 | 12.00 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.79 | 12.00 | 27.79 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.82 | 29.00 | 21.80 | 29.00 | 21.77 |
February | 445.17 | 22.52 | 7.00 | 22.49 | 7.00 | 22.46 |
March | 466.00 | 23.17 | 0.83 | 23.16 | 0.83 | 23.16 |
April | 306.83 | 23.93 | 35.33 | 24.18 | 0.00 | 24.18 |
May | 113.83 | 24.00 | 80.50 | 24.92 | 0.00 | 24.92 |
June | 4.50 | 24.00 | 183.50 | 25.11 | 0.00 | 25.11 |
July | 0.00 | 0.00 | 352.17 | 24.84 | 0.00 | 24.84 |
August | 11.00 | 24.00 | 278.83 | 24.82 | 0.00 | 24.82 |
September | 47.00 | 24.00 | 103.83 | 25.50 | 0.00 | 25.50 |
October | 223.33 | 23.67 | 58.00 | 24.23 | 0.00 | 24.23 |
November | 476.33 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
December | 485.50 | 22.05 | 3.00 | 22.04 | 3.00 | 22.03 |
Annual Sum or Average | 3081.50 | 22.77 | 1132.00 | 23.40 | 39.83 | 23.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.80 | 0.00 | 21.77 |
Maximum of Months | 502.00 | 24.00 | 352.17 | 25.50 | 29.00 | 25.50 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.61 | 35.83 | 22.47 | 35.83 | 22.36 |
February | 453.33 | 23.36 | 0.83 | 23.36 | 0.83 | 23.36 |
March | 453.67 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
April | 228.00 | 24.01 | 30.50 | 24.25 | 0.00 | 24.25 |
May | 93.67 | 23.99 | 43.83 | 24.61 | 0.00 | 24.61 |
June | 0.00 | 0.00 | 201.17 | 24.68 | 0.00 | 24.68 |
July | 0.00 | 0.00 | 392.33 | 24.41 | 0.00 | 24.41 |
August | 9.33 | 24.00 | 311.33 | 24.45 | 0.00 | 24.45 |
September | 81.17 | 23.94 | 73.67 | 24.79 | 0.00 | 24.79 |
October | 289.67 | 23.91 | 31.50 | 24.09 | 0.00 | 24.09 |
November | 489.00 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
December | 497.00 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
Annual Sum or Average | 3096.83 | 23.50 | 1121.00 | 23.79 | 36.67 | 23.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.47 | 0.00 | 22.36 |
Maximum of Months | 502.00 | 24.01 | 392.33 | 24.79 | 35.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.49 | 189.17 | 21.14 | 189.17 | 20.95 |
February | 454.00 | 22.17 | 111.50 | 21.86 | 111.50 | 21.66 |
March | 513.83 | 23.05 | 11.17 | 23.01 | 11.17 | 22.97 |
April | 422.67 | 23.58 | 2.17 | 23.57 | 2.17 | 23.56 |
May | 209.83 | 23.95 | 6.33 | 24.00 | 0.00 | 24.00 |
June | 18.17 | 23.92 | 145.00 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 300.17 | 24.49 | 0.00 | 24.49 |
August | 37.33 | 23.87 | 200.33 | 24.43 | 0.00 | 24.43 |
September | 240.00 | 23.77 | 26.33 | 23.94 | 0.00 | 23.94 |
October | 482.17 | 23.21 | 6.67 | 23.18 | 6.67 | 23.15 |
November | 489.00 | 22.09 | 105.33 | 21.84 | 105.33 | 21.67 |
December | 497.00 | 21.59 | 214.50 | 21.31 | 214.50 | 21.16 |
Annual Sum or Average | 3866.00 | 22.62 | 1318.67 | 22.62 | 640.50 | 22.39 |
Minimum of Months | 0.00 | 0.00 | 2.17 | 21.14 | 0.00 | 20.95 |
Maximum of Months | 513.83 | 23.95 | 300.17 | 24.61 | 214.50 | 24.61 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 444.33 | 20.22 | 444.33 | 20.19 |
February | 454.00 | 20.63 | 313.00 | 20.40 | 313.00 | 20.30 |
March | 514.00 | 21.40 | 236.33 | 21.08 | 236.33 | 20.91 |
April | 473.33 | 22.55 | 85.50 | 22.17 | 85.50 | 21.90 |
May | 314.33 | 23.56 | 1.17 | 23.57 | 0.00 | 23.57 |
June | 47.83 | 23.81 | 119.00 | 24.36 | 0.00 | 24.36 |
July | 4.00 | 23.61 | 282.83 | 24.43 | 0.00 | 24.43 |
August | 96.00 | 23.50 | 160.17 | 24.11 | 0.00 | 24.11 |
September | 405.00 | 22.96 | 8.83 | 22.92 | 8.83 | 22.88 |
October | 502.00 | 21.44 | 209.17 | 21.07 | 209.17 | 20.87 |
November | 489.00 | 20.44 | 413.00 | 20.33 | 413.00 | 20.29 |
December | 497.00 | 20.28 | 473.67 | 20.25 | 473.67 | 20.24 |
Annual Sum or Average | 4298.50 | 21.46 | 2747.00 | 21.31 | 2183.83 | 21.04 |
Minimum of Months | 4.00 | 20.28 | 1.17 | 20.22 | 0.00 | 20.19 |
Maximum of Months | 514.00 | 23.81 | 473.67 | 24.43 | 473.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.24 | 502.00 | 20.24 | 502.00 | 20.24 |
February | 454.00 | 20.61 | 383.33 | 20.53 | 383.33 | 20.50 |
March | 514.00 | 21.50 | 253.67 | 21.27 | 253.67 | 21.15 |
April | 460.33 | 23.06 | 39.67 | 22.87 | 39.67 | 22.72 |
May | 223.83 | 23.79 | 7.67 | 23.85 | 0.00 | 23.85 |
June | 0.00 | 0.00 | 256.17 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 435.33 | 24.37 | 0.00 | 24.37 |
August | 49.17 | 23.69 | 239.50 | 24.21 | 0.00 | 24.21 |
September | 362.50 | 23.09 | 11.83 | 23.16 | 0.00 | 23.16 |
October | 498.17 | 22.03 | 127.33 | 21.76 | 127.33 | 21.59 |
November | 489.00 | 20.65 | 467.00 | 20.63 | 467.00 | 20.62 |
December | 497.00 | 20.54 | 497.00 | 20.54 | 497.00 | 20.54 |
Annual Sum or Average | 4050.00 | 21.56 | 3220.50 | 21.60 | 2270.00 | 21.35 |
Minimum of Months | 0.00 | 0.00 | 7.67 | 20.24 | 0.00 | 20.24 |
Maximum of Months | 514.00 | 23.79 | 502.00 | 24.44 | 502.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 502.00 | 20.17 | 502.00 | 20.17 |
February | 454.00 | 20.58 | 382.00 | 20.52 | 382.00 | 20.50 |
March | 493.67 | 21.53 | 209.33 | 21.31 | 209.33 | 21.19 |
April | 352.67 | 22.40 | 61.83 | 22.44 | 34.83 | 22.31 |
May | 174.83 | 23.36 | 141.17 | 23.92 | 8.33 | 24.00 |
June | 61.67 | 23.31 | 294.50 | 24.09 | 2.67 | 24.11 |
July | 46.00 | 23.89 | 371.67 | 24.24 | 11.00 | 24.31 |
August | 126.67 | 22.94 | 250.67 | 23.73 | 0.50 | 23.74 |
September | 343.67 | 22.49 | 56.67 | 22.87 | 1.17 | 22.88 |
October | 493.83 | 21.65 | 130.83 | 21.45 | 130.83 | 21.32 |
November | 489.00 | 20.49 | 489.00 | 20.49 | 489.00 | 20.49 |
December | 497.00 | 20.35 | 497.00 | 20.35 | 497.00 | 20.35 |
Annual Sum or Average | 4035.00 | 21.33 | 3386.67 | 21.52 | 2268.67 | 21.28 |
Minimum of Months | 46.00 | 20.17 | 56.67 | 20.17 | 0.50 | 20.17 |
Maximum of Months | 502.00 | 23.89 | 502.00 | 24.24 | 502.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 489.17 | 20.14 | 489.17 | 20.13 |
February | 444.17 | 20.90 | 325.33 | 20.72 | 325.33 | 20.65 |
March | 429.67 | 21.55 | 198.00 | 21.44 | 178.50 | 21.30 |
April | 273.33 | 22.41 | 132.67 | 22.80 | 34.67 | 22.66 |
May | 218.00 | 23.04 | 137.83 | 23.64 | 6.33 | 23.70 |
June | 88.17 | 23.34 | 284.83 | 24.11 | 6.50 | 24.15 |
July | 66.50 | 23.62 | 366.50 | 24.22 | 10.50 | 24.28 |
August | 120.83 | 23.14 | 303.17 | 23.96 | 6.67 | 24.01 |
September | 309.00 | 22.45 | 97.50 | 22.93 | 2.17 | 22.92 |
October | 457.67 | 21.60 | 142.50 | 21.45 | 130.67 | 21.31 |
November | 489.00 | 20.58 | 447.00 | 20.52 | 447.00 | 20.50 |
December | 497.00 | 20.27 | 497.00 | 20.27 | 497.00 | 20.27 |
Annual Sum or Average | 3895.33 | 21.36 | 3421.50 | 21.62 | 2134.50 | 21.37 |
Minimum of Months | 66.50 | 20.16 | 97.50 | 20.14 | 2.17 | 20.13 |
Maximum of Months | 502.00 | 23.62 | 497.00 | 24.22 | 497.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.56 | 485.67 | 20.55 | 485.67 | 20.55 |
February | 454.00 | 21.07 | 259.83 | 20.95 | 259.83 | 20.90 |
March | 478.33 | 22.13 | 62.17 | 22.04 | 57.83 | 21.94 |
April | 171.83 | 23.20 | 123.17 | 23.98 | 4.17 | 24.02 |
May | 164.33 | 23.18 | 117.33 | 23.92 | 3.67 | 23.96 |
June | 11.33 | 25.72 | 408.00 | 24.52 | 7.50 | 24.56 |
July | 17.00 | 26.88 | 490.83 | 24.54 | 17.00 | 24.62 |
August | 16.17 | 25.61 | 458.50 | 24.49 | 10.17 | 24.54 |
September | 315.17 | 22.64 | 69.17 | 23.05 | 0.17 | 23.05 |
October | 466.83 | 22.12 | 55.00 | 22.03 | 51.83 | 21.94 |
November | 489.00 | 21.25 | 257.00 | 21.16 | 257.00 | 21.11 |
December | 497.00 | 21.18 | 367.83 | 21.10 | 367.83 | 21.07 |
Annual Sum or Average | 3583.00 | 21.72 | 3154.50 | 22.22 | 1522.67 | 21.99 |
Minimum of Months | 11.33 | 20.56 | 55.00 | 20.55 | 0.17 | 20.55 |
Maximum of Months | 502.00 | 26.88 | 490.83 | 24.54 | 485.67 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.86 | 502.00 | 19.86 | 502.00 | 19.86 |
February | 454.00 | 20.00 | 445.50 | 19.99 | 445.50 | 19.98 |
March | 514.00 | 20.49 | 441.17 | 20.41 | 441.17 | 20.38 |
April | 485.00 | 21.71 | 163.50 | 21.32 | 163.50 | 21.08 |
May | 357.67 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
June | 22.50 | 23.41 | 188.00 | 24.26 | 0.00 | 24.26 |
July | 4.50 | 23.56 | 356.50 | 24.37 | 0.17 | 24.37 |
August | 145.50 | 23.17 | 131.00 | 23.71 | 0.00 | 23.71 |
September | 463.33 | 22.36 | 35.17 | 22.26 | 35.17 | 22.16 |
October | 502.00 | 20.67 | 324.83 | 20.48 | 324.83 | 20.40 |
November | 489.00 | 19.92 | 489.00 | 19.92 | 489.00 | 19.92 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 4436.50 | 20.93 | 3573.67 | 20.89 | 2898.33 | 20.66 |
Minimum of Months | 4.50 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
Maximum of Months | 514.00 | 23.56 | 502.00 | 24.37 | 502.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.70 | 427.00 | 19.70 | 427.00 | 19.70 |
February | 385.00 | 19.93 | 376.00 | 19.92 | 376.00 | 19.92 |
March | 430.83 | 20.76 | 291.50 | 20.59 | 291.50 | 20.53 |
April | 352.17 | 21.65 | 106.83 | 21.48 | 94.00 | 21.28 |
May | 210.33 | 23.04 | 96.67 | 23.58 | 9.67 | 23.69 |
June | 86.50 | 23.17 | 213.00 | 23.99 | 3.33 | 24.02 |
July | 66.67 | 23.64 | 296.50 | 24.35 | 14.33 | 24.45 |
August | 168.17 | 22.75 | 174.67 | 23.57 | 1.17 | 23.59 |
September | 350.33 | 21.88 | 48.50 | 22.06 | 22.50 | 22.00 |
October | 425.83 | 20.64 | 267.00 | 20.48 | 267.00 | 20.41 |
November | 417.00 | 19.75 | 417.00 | 19.75 | 417.00 | 19.75 |
December | 422.00 | 19.65 | 422.00 | 19.65 | 422.00 | 19.65 |
Annual Sum or Average | 3741.83 | 20.82 | 3136.67 | 20.95 | 2345.50 | 20.71 |
Minimum of Months | 66.67 | 19.65 | 48.50 | 19.65 | 1.17 | 19.65 |
Maximum of Months | 430.83 | 23.64 | 427.00 | 24.35 | 427.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 493.83 | 19.94 | 493.83 | 19.94 |
February | 447.50 | 20.52 | 361.00 | 20.37 | 361.00 | 20.32 |
March | 432.83 | 21.09 | 259.50 | 20.99 | 236.67 | 20.86 |
April | 300.83 | 21.88 | 165.50 | 22.20 | 71.67 | 21.98 |
May | 255.17 | 22.77 | 137.67 | 23.38 | 11.17 | 23.46 |
June | 138.67 | 23.02 | 255.50 | 23.87 | 7.00 | 23.92 |
July | 116.83 | 23.12 | 326.67 | 24.10 | 11.33 | 24.17 |
August | 183.00 | 22.78 | 249.50 | 23.73 | 6.83 | 23.78 |
September | 338.33 | 22.10 | 101.33 | 22.57 | 12.00 | 22.54 |
October | 473.00 | 21.06 | 231.67 | 20.88 | 221.83 | 20.75 |
November | 489.00 | 20.12 | 466.83 | 20.09 | 466.83 | 20.07 |
December | 497.00 | 19.88 | 497.00 | 19.88 | 497.00 | 19.88 |
Annual Sum or Average | 4174.17 | 21.07 | 3546.00 | 21.29 | 2397.17 | 21.03 |
Minimum of Months | 116.83 | 19.88 | 101.33 | 19.88 | 6.83 | 19.88 |
Maximum of Months | 502.00 | 23.12 | 497.00 | 24.10 | 497.00 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 502.00 | 19.95 | 502.00 | 19.95 |
February | 454.00 | 20.12 | 432.00 | 20.10 | 432.00 | 20.09 |
March | 514.00 | 20.71 | 376.50 | 20.60 | 376.50 | 20.55 |
April | 400.33 | 21.71 | 130.33 | 21.59 | 100.67 | 21.39 |
May | 325.17 | 22.70 | 56.00 | 22.98 | 0.67 | 22.99 |
June | 121.17 | 22.96 | 233.67 | 23.95 | 2.67 | 23.97 |
July | 97.83 | 22.88 | 318.00 | 24.05 | 1.83 | 24.07 |
August | 219.50 | 22.69 | 183.50 | 23.47 | 1.17 | 23.48 |
September | 443.83 | 21.89 | 37.00 | 21.91 | 23.33 | 21.87 |
October | 502.00 | 20.70 | 297.33 | 20.56 | 297.33 | 20.49 |
November | 489.00 | 20.05 | 488.17 | 20.05 | 488.17 | 20.05 |
December | 497.00 | 19.94 | 497.00 | 19.94 | 497.00 | 19.94 |
Annual Sum or Average | 4565.83 | 20.96 | 3551.50 | 21.03 | 2723.33 | 20.81 |
Minimum of Months | 97.83 | 19.94 | 37.00 | 19.94 | 0.67 | 19.94 |
Maximum of Months | 514.00 | 22.96 | 502.00 | 24.05 | 502.00 | 24.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 502.00 | 19.63 | 502.00 | 19.63 |
February | 454.00 | 19.75 | 454.00 | 19.75 | 454.00 | 19.75 |
March | 514.00 | 20.09 | 494.33 | 20.06 | 494.33 | 20.06 |
April | 485.00 | 20.83 | 281.83 | 20.53 | 281.83 | 20.40 |
May | 423.67 | 22.73 | 28.33 | 22.59 | 28.33 | 22.46 |
June | 72.00 | 23.05 | 152.00 | 23.87 | 0.00 | 23.87 |
July | 49.33 | 23.25 | 308.50 | 24.13 | 0.00 | 24.13 |
August | 251.00 | 22.67 | 100.83 | 23.03 | 9.50 | 22.97 |
September | 484.00 | 21.32 | 152.33 | 21.12 | 152.33 | 20.99 |
October | 502.00 | 20.02 | 443.33 | 19.95 | 443.33 | 19.92 |
November | 489.00 | 19.70 | 489.00 | 19.70 | 489.00 | 19.70 |
December | 497.00 | 19.60 | 497.00 | 19.60 | 497.00 | 19.60 |
Annual Sum or Average | 4723.00 | 20.56 | 3903.50 | 20.51 | 3351.67 | 20.32 |
Minimum of Months | 49.33 | 19.60 | 28.33 | 19.60 | 0.00 | 19.60 |
Maximum of Months | 514.00 | 23.25 | 502.00 | 24.13 | 502.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.86 | 452.50 | 19.85 | 452.50 | 19.85 |
March | 514.00 | 20.33 | 431.83 | 20.22 | 431.83 | 20.18 |
April | 438.17 | 21.28 | 193.17 | 20.94 | 187.33 | 20.74 |
May | 246.33 | 22.65 | 116.83 | 23.12 | 17.00 | 23.13 |
June | 99.50 | 22.86 | 279.17 | 23.87 | 2.33 | 23.89 |
July | 83.33 | 23.41 | 356.17 | 24.19 | 14.67 | 24.28 |
August | 199.17 | 22.48 | 197.17 | 23.34 | 2.83 | 23.33 |
September | 438.00 | 21.45 | 96.67 | 21.33 | 90.17 | 21.20 |
October | 502.00 | 20.14 | 406.17 | 20.03 | 406.17 | 19.98 |
November | 489.00 | 19.77 | 489.00 | 19.77 | 489.00 | 19.77 |
December | 497.00 | 19.70 | 497.00 | 19.70 | 497.00 | 19.70 |
Annual Sum or Average | 4462.50 | 20.60 | 4017.67 | 20.75 | 3092.83 | 20.53 |
Minimum of Months | 83.33 | 19.70 | 96.67 | 19.70 | 2.33 | 19.70 |
Maximum of Months | 514.00 | 23.41 | 502.00 | 24.19 | 502.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 502.00 | 19.76 | 502.00 | 19.76 |
February | 454.00 | 20.07 | 416.83 | 19.99 | 416.83 | 19.96 |
March | 469.83 | 20.65 | 339.83 | 20.44 | 339.17 | 20.35 |
April | 344.17 | 21.36 | 215.00 | 21.46 | 141.33 | 21.20 |
May | 288.83 | 22.31 | 132.33 | 22.87 | 18.67 | 22.85 |
June | 161.00 | 22.68 | 237.17 | 23.65 | 6.50 | 23.70 |
July | 142.83 | 22.88 | 305.67 | 23.92 | 11.83 | 23.99 |
August | 223.00 | 22.44 | 231.50 | 23.39 | 11.83 | 23.40 |
September | 381.83 | 21.54 | 135.67 | 21.76 | 71.67 | 21.61 |
October | 485.83 | 20.38 | 361.17 | 20.22 | 357.50 | 20.14 |
November | 489.00 | 19.83 | 484.50 | 19.82 | 484.50 | 19.82 |
December | 497.00 | 19.72 | 497.00 | 19.72 | 497.00 | 19.72 |
Annual Sum or Average | 4439.33 | 20.74 | 3858.67 | 20.91 | 2858.83 | 20.67 |
Minimum of Months | 142.83 | 19.72 | 132.33 | 19.72 | 6.50 | 19.72 |
Maximum of Months | 502.00 | 22.88 | 502.00 | 23.92 | 502.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 502.00 | 19.77 | 502.00 | 19.77 |
February | 454.00 | 19.90 | 450.50 | 19.90 | 450.50 | 19.90 |
March | 514.00 | 20.32 | 448.17 | 20.24 | 448.17 | 20.22 |
April | 421.17 | 21.14 | 203.83 | 20.93 | 182.67 | 20.74 |
May | 370.17 | 22.28 | 62.83 | 22.46 | 14.17 | 22.40 |
June | 158.50 | 22.70 | 221.50 | 23.71 | 3.50 | 23.74 |
July | 136.17 | 22.72 | 284.67 | 23.83 | 2.17 | 23.84 |
August | 275.00 | 22.37 | 163.67 | 23.07 | 6.00 | 23.05 |
September | 460.33 | 21.37 | 99.67 | 21.28 | 91.83 | 21.18 |
October | 502.00 | 20.19 | 415.50 | 20.10 | 415.50 | 20.07 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4779.33 | 20.69 | 3838.33 | 20.74 | 3102.50 | 20.53 |
Minimum of Months | 136.17 | 19.76 | 62.83 | 19.76 | 2.17 | 19.76 |
Maximum of Months | 514.00 | 22.72 | 502.00 | 23.83 | 502.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.33 | 25.93 | 158.50 | 26.88 | 0.00 | 26.88 |
February | 0.00 | 0.00 | 321.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 500.50 | 27.00 | 0.00 | 27.00 |
April | 20.17 | 27.00 | 485.00 | 27.00 | 20.17 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 8.33 | 27.00 | 496.00 | 27.00 | 8.33 | 27.00 |
July | 52.33 | 27.00 | 497.00 | 27.00 | 52.33 | 27.00 |
August | 98.17 | 27.00 | 514.00 | 27.00 | 98.17 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 466.33 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 460.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 197.33 | 26.90 | 5393.67 | 27.00 | 179.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 158.50 | 26.88 | 0.00 | 26.88 |
Maximum of Months | 98.17 | 27.00 | 514.00 | 27.00 | 98.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.50 | 25.29 | 29.33 | 25.26 | 12.00 | 25.15 |
February | 55.17 | 27.00 | 122.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 289.83 | 27.00 | 0.00 | 27.00 |
April | 5.83 | 27.00 | 429.17 | 27.00 | 5.83 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.67 | 27.00 | 496.00 | 27.00 | 1.67 | 27.00 |
July | 8.00 | 27.00 | 497.00 | 27.00 | 8.00 | 27.00 |
August | 6.17 | 27.00 | 514.00 | 27.00 | 6.17 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 364.17 | 27.00 | 0.00 | 27.00 |
November | 26.67 | 27.00 | 76.83 | 27.00 | 0.00 | 27.00 |
December | 54.50 | 27.00 | 28.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 456.50 | 25.88 | 3840.00 | 26.87 | 33.67 | 26.85 |
Minimum of Months | 0.00 | 0.00 | 28.33 | 25.26 | 0.00 | 25.15 |
Maximum of Months | 298.50 | 27.00 | 514.00 | 27.00 | 12.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.17 | 24.41 | 76.50 | 24.04 | 76.50 | 23.76 |
February | 112.50 | 26.73 | 41.83 | 26.80 | 0.00 | 26.80 |
March | 66.33 | 27.00 | 147.00 | 27.00 | 0.00 | 27.00 |
April | 33.00 | 27.00 | 351.33 | 27.00 | 5.33 | 27.00 |
May | 0.00 | 0.00 | 501.33 | 27.00 | 0.00 | 27.00 |
June | 2.50 | 27.00 | 496.00 | 27.00 | 2.50 | 27.00 |
July | 8.67 | 27.00 | 497.00 | 27.00 | 8.67 | 27.00 |
August | 7.50 | 27.00 | 514.00 | 27.00 | 7.50 | 27.00 |
September | 5.17 | 25.94 | 439.50 | 26.99 | 0.00 | 26.99 |
October | 56.33 | 27.00 | 205.83 | 27.00 | 0.00 | 27.00 |
November | 121.17 | 27.00 | 4.33 | 27.00 | 0.00 | 27.00 |
December | 136.33 | 27.00 | 0.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1030.67 | 25.75 | 3274.67 | 26.61 | 100.50 | 26.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 | 23.76 |
Maximum of Months | 481.17 | 27.00 | 514.00 | 27.00 | 76.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 438.83 | 27.00 | 454.00 | 27.00 | 438.83 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 461.17 | 27.00 | 508.00 | 27.00 | 461.17 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.04 | 514.00 | 27.04 | 514.00 | 27.04 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5379.00 | 27.01 | 5943.00 | 27.01 | 5379.00 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 27.04 | 514.00 | 27.04 | 514.00 | 27.04 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.89212 | 11.37181 | 0.49753 | 10.31237 |
February | 454.00000 | 27.00000 | 11.33826 | 0.59697 | 12.61510 |
March | 514.00000 | 27.00000 | 12.14817 | 0.70021 | 15.45692 |
April | 485.00000 | 26.99999 | 15.42751 | 0.84743 | 20.31375 |
May | 508.00000 | 27.00000 | 22.39290 | 0.15519 | 5.60027 |
June | 496.00000 | 27.00037 | 28.62778 | 0.29228 | 6.84455 |
July | 497.00000 | 27.00045 | 30.33895 | 0.34852 | 7.58358 |
August | 514.00000 | 27.00018 | 28.89262 | 0.36703 | 7.87396 |
September | 485.00000 | 27.00012 | 25.30740 | 0.12916 | 5.50334 |
October | 502.00000 | 27.00000 | 17.60627 | 0.72816 | 16.30625 |
November | 489.00000 | 27.00000 | 9.96629 | 0.62570 | 13.26688 |
December | 497.00000 | 27.00000 | 9.01602 | 0.62187 | 13.16982 |
Annual Sum or Average | 5943.00000 | 26.99098 | 18.60237 | 0.49143 | 11.21402 |
Minimum of Months | 454.00000 | 26.89212 | 9.01602 | 0.12916 | 5.50334 |
Maximum of Months | 514.00000 | 27.00045 | 30.33895 | 0.84743 | 20.31375 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.89180 | 11.20653 | 0.21908 | 7.40907 |
February | 454.00000 | 27.00000 | 11.31761 | 0.47785 | 9.98684 |
March | 514.00000 | 27.00000 | 12.13655 | 0.55980 | 11.74662 |
April | 485.00000 | 26.99999 | 15.41429 | 0.69894 | 15.59508 |
May | 508.00000 | 27.00000 | 22.37786 | 0.07637 | 5.28030 |
June | 496.00000 | 27.00036 | 28.63410 | 0.20512 | 5.99041 |
July | 497.00000 | 27.00047 | 30.36072 | 0.23642 | 6.25772 |
August | 514.00000 | 27.00020 | 28.89341 | 0.21858 | 6.13479 |
September | 485.00000 | 27.00011 | 25.33911 | 0.01804 | 5.20805 |
October | 502.00000 | 27.00000 | 17.58912 | 0.59617 | 12.65292 |
November | 489.00000 | 27.00000 | 9.95274 | 0.46747 | 9.68282 |
December | 497.00000 | 27.00000 | 9.00925 | 0.44656 | 9.27280 |
Annual Sum or Average | 5943.00000 | 26.90649 | 18.58533 | 0.35043 | 8.74860 |
Minimum of Months | 454.00000 | 25.89180 | 9.00925 | 0.01804 | 5.20805 |
Maximum of Months | 514.00000 | 27.00047 | 30.36072 | 0.69894 | 15.59508 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.49704 | 11.28322 | -0.1095 | 7.87673 |
February | 454.00000 | 26.93316 | 11.32404 | 0.38471 | 8.57389 |
March | 514.00000 | 27.00000 | 12.13918 | 0.47409 | 9.97905 |
April | 485.00000 | 27.00000 | 15.41734 | 0.62919 | 13.86225 |
May | 508.00000 | 27.00002 | 22.38191 | 0.03122 | 5.34560 |
June | 496.00000 | 27.00036 | 28.64383 | 0.19525 | 5.99190 |
July | 497.00000 | 27.00047 | 30.36821 | 0.22718 | 6.23283 |
August | 514.00000 | 27.00021 | 28.90383 | 0.18792 | 5.99845 |
September | 485.00000 | 26.97237 | 25.42549 | -0.0806 | 5.59650 |
October | 502.00000 | 27.00024 | 17.59239 | 0.50449 | 10.62306 |
November | 489.00000 | 27.00000 | 9.95586 | 0.38177 | 8.23744 |
December | 497.00000 | 27.00000 | 9.01081 | 0.36922 | 8.01381 |
Annual Sum or Average | 5943.00000 | 26.78133 | 18.60318 | 0.26504 | 8.01373 |
Minimum of Months | 454.00000 | 24.49704 | 9.01081 | -0.1095 | 5.34560 |
Maximum of Months | 514.00000 | 27.00047 | 30.36821 | 0.62919 | 13.86225 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00245 | 30.00083 | 0.91639 | 22.77614 |
February | 454.00000 | 27.00322 | 30.00011 | 1.11012 | 31.00717 |
March | 514.00000 | 27.00242 | 29.99919 | 1.30045 | 40.30584 |
April | 485.00000 | 27.00126 | 29.99899 | 1.48226 | 49.94057 |
May | 508.00000 | 27.00252 | 29.99925 | 0.46576 | 9.58239 |
June | 496.00000 | 27.00521 | 30.18343 | 0.71225 | 15.69261 |
July | 497.00000 | 27.00400 | 30.49625 | 0.93129 | 23.33775 |
August | 514.00000 | 27.03531 | 30.17078 | 1.13987 | 32.39669 |
September | 485.00000 | 27.00298 | 30.00375 | 0.50431 | 10.37090 |
October | 502.00000 | 27.00302 | 29.99975 | 1.20940 | 35.72114 |
November | 489.00000 | 27.00258 | 30.00009 | 1.30829 | 40.70224 |
December | 497.00000 | 27.00199 | 30.00017 | 1.42248 | 46.71743 |
Annual Sum or Average | 5943.00000 | 27.00568 | 30.07175 | 1.04129 | 29.85618 |
Minimum of Months | 454.00000 | 27.00126 | 29.99899 | 0.46576 | 9.58239 |
Maximum of Months | 514.00000 | 27.03531 | 30.49625 | 1.48226 | 49.94057 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.82314 | 12.26023 | -0.3482 | 8.09568 |
February | 454.00000 | 22.56767 | 11.44696 | -0.1775 | 6.89937 |
March | 514.00000 | 23.33516 | 11.98993 | 0.01242 | 6.05919 |
April | 485.00000 | 24.33065 | 13.97994 | 0.26000 | 6.81755 |
May | 508.00000 | 24.43972 | 20.55740 | -0.5213 | 11.37944 |
June | 496.00000 | 24.42836 | 33.09293 | -0.4209 | 9.47701 |
July | 497.00000 | 24.59493 | 42.03759 | -0.2986 | 8.15805 |
August | 514.00000 | 24.46887 | 36.40286 | -0.3662 | 8.82037 |
September | 485.00000 | 24.49845 | 25.82035 | -0.4544 | 10.38998 |
October | 502.00000 | 24.26944 | 17.30001 | 0.27326 | 7.32171 |
November | 489.00000 | 22.80221 | 9.56814 | -0.1120 | 6.17776 |
December | 497.00000 | 22.11891 | 8.80640 | -0.2767 | 7.54325 |
Annual Sum or Average | 5943.00000 | 23.64740 | 20.36324 | -0.2034 | 8.10557 |
Minimum of Months | 454.00000 | 21.82314 | 8.80640 | -0.5213 | 6.05919 |
Maximum of Months | 514.00000 | 24.59493 | 42.03759 | 0.27326 | 11.37944 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60513 | 10.38229 | -0.2386 | 7.18142 |
February | 454.00000 | 23.36698 | 11.35190 | -0.0374 | 5.75208 |
March | 514.00000 | 23.91667 | 11.53085 | 0.12279 | 5.71764 |
April | 485.00000 | 24.27902 | 14.32174 | 0.26889 | 6.77864 |
May | 508.00000 | 24.26098 | 21.38497 | -0.5438 | 11.52891 |
June | 496.00000 | 24.28696 | 34.20734 | -0.4200 | 9.17986 |
July | 497.00000 | 24.32085 | 42.47637 | -0.3424 | 7.88821 |
August | 514.00000 | 24.28642 | 37.53665 | -0.3850 | 8.56146 |
September | 485.00000 | 24.32562 | 27.03115 | -0.5063 | 11.05321 |
October | 502.00000 | 24.19262 | 17.97609 | 0.24173 | 6.66376 |
November | 489.00000 | 23.68493 | 9.26521 | 0.02653 | 5.29471 |
December | 497.00000 | 23.40281 | 8.97589 | -0.0525 | 5.50515 |
Annual Sum or Average | 5943.00000 | 23.91422 | 20.62921 | -0.1570 | 7.60645 |
Minimum of Months | 454.00000 | 22.60513 | 8.97589 | -0.5438 | 5.29471 |
Maximum of Months | 514.00000 | 24.32562 | 42.47637 | 0.26889 | 11.52891 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.48803 | 13.94413 | -0.4975 | 12.60634 |
February | 454.00000 | 22.16954 | 15.40269 | -0.3139 | 9.08976 |
March | 514.00000 | 23.04979 | 16.27159 | -0.0876 | 6.13415 |
April | 485.00000 | 23.71348 | 16.64114 | 0.10260 | 5.93442 |
May | 508.00000 | 24.13534 | 22.04687 | -0.6127 | 13.12967 |
June | 496.00000 | 24.22997 | 34.63384 | -0.4718 | 9.99092 |
July | 497.00000 | 24.29458 | 43.37101 | -0.3923 | 8.65896 |
August | 514.00000 | 24.22217 | 38.14923 | -0.4583 | 9.81929 |
September | 485.00000 | 24.04313 | 28.59252 | -0.6312 | 13.95495 |
October | 502.00000 | 23.24401 | 22.27732 | 0.00213 | 6.03505 |
November | 489.00000 | 22.08544 | 13.80891 | -0.3509 | 8.88997 |
December | 497.00000 | 21.58794 | 11.68079 | -0.4833 | 11.14645 |
Annual Sum or Average | 5943.00000 | 23.19744 | 23.14961 | -0.3500 | 9.61585 |
Minimum of Months | 454.00000 | 21.48803 | 11.68079 | -0.6312 | 5.93442 |
Maximum of Months | 514.00000 | 24.29458 | 43.37101 | 0.10260 | 13.95495 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30615 | 14.42383 | -0.8303 | 22.19059 |
February | 454.00000 | 20.63176 | 16.30050 | -0.7229 | 19.25727 |
March | 514.00000 | 21.39630 | 17.15361 | -0.5167 | 13.09355 |
April | 485.00000 | 22.58986 | 17.89001 | -0.1870 | 8.93640 |
May | 508.00000 | 23.79319 | 22.94214 | -0.7454 | 17.80003 |
June | 496.00000 | 24.16101 | 34.71869 | -0.4972 | 10.47239 |
July | 497.00000 | 24.24197 | 43.52431 | -0.4116 | 8.87387 |
August | 514.00000 | 24.06333 | 38.80700 | -0.5269 | 11.60761 |
September | 485.00000 | 23.13532 | 31.31749 | -0.9723 | 26.84999 |
October | 502.00000 | 21.43935 | 24.28788 | -0.4578 | 12.38840 |
November | 489.00000 | 20.44100 | 14.42802 | -0.7887 | 20.56882 |
December | 497.00000 | 20.28445 | 12.30831 | -0.8487 | 22.35112 |
Annual Sum or Average | 5943.00000 | 22.22145 | 24.08586 | -0.6244 | 16.14806 |
Minimum of Months | 454.00000 | 20.28445 | 12.30831 | -0.9723 | 8.87387 |
Maximum of Months | 514.00000 | 24.24197 | 43.52431 | -0.1870 | 26.84999 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24498 | 8.89160 | -0.8825 | 22.95158 |
February | 454.00000 | 20.60811 | 10.48534 | -0.7399 | 18.04876 |
March | 514.00000 | 21.50417 | 11.36515 | -0.4805 | 11.30300 |
April | 485.00000 | 23.11375 | 14.30258 | -0.0370 | 6.63202 |
May | 508.00000 | 24.00799 | 20.76299 | -0.6375 | 13.96301 |
June | 496.00000 | 24.24776 | 33.31451 | -0.3961 | 8.59426 |
July | 497.00000 | 24.32844 | 41.58487 | -0.3146 | 7.51732 |
August | 514.00000 | 24.13439 | 37.17116 | -0.4547 | 9.85649 |
September | 485.00000 | 23.36916 | 27.68499 | -0.8670 | 22.46083 |
October | 502.00000 | 22.04234 | 18.26072 | -0.2963 | 8.65883 |
November | 489.00000 | 20.65006 | 8.41581 | -0.7415 | 17.20158 |
December | 497.00000 | 20.53712 | 7.67040 | -0.8024 | 19.25480 |
Annual Sum or Average | 5943.00000 | 22.41389 | 20.08569 | -0.5527 | 13.81825 |
Minimum of Months | 454.00000 | 20.24498 | 7.67040 | -0.8825 | 6.63202 |
Maximum of Months | 514.00000 | 24.32844 | 41.58487 | -0.0370 | 22.95158 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17206 | 7.96074 | -0.9171 | 24.34602 |
February | 454.00000 | 20.58382 | 9.55481 | -0.7464 | 18.12878 |
March | 514.00000 | 21.63375 | 10.38402 | -0.4139 | 10.65746 |
April | 485.00000 | 22.90922 | 13.78424 | -0.0190 | 7.42737 |
May | 508.00000 | 23.92269 | 20.38010 | -0.5200 | 13.03023 |
June | 496.00000 | 24.03930 | 33.53832 | -0.3678 | 8.92920 |
July | 497.00000 | 24.07606 | 41.91435 | -0.2956 | 8.27265 |
August | 514.00000 | 23.75057 | 37.70761 | -0.4828 | 11.36517 |
September | 485.00000 | 23.04997 | 27.49110 | -0.8906 | 25.09311 |
October | 502.00000 | 21.68346 | 17.76621 | -0.3549 | 9.36592 |
November | 489.00000 | 20.49344 | 7.43988 | -0.8002 | 19.29982 |
December | 497.00000 | 20.34785 | 6.82242 | -0.8783 | 22.24665 |
Annual Sum or Average | 5943.00000 | 22.23632 | 19.65991 | -0.5554 | 14.79049 |
Minimum of Months | 454.00000 | 20.17206 | 6.82242 | -0.9171 | 7.42737 |
Maximum of Months | 514.00000 | 24.07606 | 41.91435 | -0.0190 | 25.09311 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15582 | 7.99373 | -0.9137 | 24.48878 |
February | 454.00000 | 20.96292 | 9.39080 | -0.6370 | 16.08536 |
March | 514.00000 | 22.00450 | 10.13547 | -0.3022 | 10.37655 |
April | 485.00000 | 23.23280 | 13.36712 | 0.09426 | 8.43242 |
May | 508.00000 | 23.74509 | 20.59168 | -0.6008 | 15.68424 |
June | 496.00000 | 24.02536 | 33.58507 | -0.3864 | 9.57164 |
July | 497.00000 | 24.07407 | 41.93170 | -0.3047 | 8.55807 |
August | 514.00000 | 23.89298 | 37.29756 | -0.4085 | 10.72785 |
September | 485.00000 | 23.11921 | 27.28764 | -0.8424 | 23.92192 |
October | 502.00000 | 21.83218 | 17.67542 | -0.3135 | 9.60363 |
November | 489.00000 | 20.58392 | 7.42246 | -0.7655 | 18.72119 |
December | 497.00000 | 20.27465 | 6.89254 | -0.8941 | 23.07257 |
Annual Sum or Average | 5943.00000 | 22.33773 | 19.56276 | -0.5217 | 14.89936 |
Minimum of Months | 454.00000 | 20.15582 | 6.89254 | -0.9137 | 8.43242 |
Maximum of Months | 514.00000 | 24.07407 | 41.93170 | 0.09426 | 24.48878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56014 | 7.64435 | -0.7597 | 18.13024 |
February | 454.00000 | 21.07442 | 9.18409 | -0.5660 | 12.56536 |
March | 514.00000 | 22.29190 | 9.81949 | -0.2174 | 7.57109 |
April | 485.00000 | 24.01414 | 12.79624 | 0.30065 | 8.42427 |
May | 508.00000 | 23.95960 | 20.39210 | -0.5313 | 12.71709 |
June | 496.00000 | 24.36209 | 32.88708 | -0.2239 | 7.22060 |
July | 497.00000 | 24.45090 | 40.92383 | -0.1276 | 6.42868 |
August | 514.00000 | 24.38175 | 36.16204 | -0.1968 | 7.00775 |
September | 485.00000 | 23.26232 | 26.95636 | -0.7958 | 21.07138 |
October | 502.00000 | 22.28822 | 16.98677 | -0.1819 | 7.36119 |
November | 489.00000 | 21.24636 | 7.05411 | -0.5316 | 11.19505 |
December | 497.00000 | 21.18459 | 6.33949 | -0.5597 | 11.92672 |
Annual Sum or Average | 5943.00000 | 22.77005 | 19.02397 | -0.3643 | 10.92697 |
Minimum of Months | 454.00000 | 20.56014 | 6.33949 | -0.7958 | 6.42868 |
Maximum of Months | 514.00000 | 24.45090 | 40.92383 | 0.30065 | 21.07138 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85604 | 12.60279 | -1.0345 | 29.57814 |
February | 454.00000 | 19.99744 | 14.53281 | -0.9457 | 26.19242 |
March | 514.00000 | 20.49445 | 15.34739 | -0.7645 | 19.17418 |
April | 485.00000 | 21.71347 | 16.38151 | -0.3894 | 11.45472 |
May | 508.00000 | 23.64016 | 21.45180 | -0.7792 | 18.86604 |
June | 496.00000 | 24.13167 | 33.74988 | -0.4561 | 9.70454 |
July | 497.00000 | 24.26587 | 42.13706 | -0.3690 | 8.26269 |
August | 514.00000 | 23.84676 | 38.04444 | -0.5915 | 13.59275 |
September | 485.00000 | 22.43531 | 29.91512 | -1.1942 | 36.67542 |
October | 502.00000 | 20.67362 | 22.12426 | -0.6563 | 16.27570 |
November | 489.00000 | 19.91618 | 12.65145 | -0.9941 | 27.91292 |
December | 497.00000 | 19.83263 | 10.39755 | -1.0566 | 30.34437 |
Annual Sum or Average | 5943.00000 | 21.75042 | 22.52429 | -0.7673 | 20.58385 |
Minimum of Months | 454.00000 | 19.83263 | 10.39755 | -1.1942 | 8.26269 |
Maximum of Months | 514.00000 | 24.26587 | 42.13706 | -0.3690 | 36.67542 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.70407 | 11.42136 | -1.0745 | 31.37867 |
February | 385.00000 | 19.93362 | 13.16744 | -0.9485 | 26.32294 |
March | 433.00000 | 20.77253 | 13.77349 | -0.6532 | 15.98971 |
April | 410.00000 | 22.03366 | 14.81593 | -0.2531 | 9.88886 |
May | 430.00000 | 23.64078 | 20.55922 | -0.6299 | 17.01207 |
June | 418.00000 | 23.95288 | 33.73061 | -0.4129 | 10.26753 |
July | 422.00000 | 24.14075 | 42.05501 | -0.2988 | 9.16333 |
August | 433.00000 | 23.60750 | 37.82248 | -0.5597 | 14.17175 |
September | 410.00000 | 22.28683 | 28.93067 | -1.1691 | 37.08025 |
October | 427.00000 | 20.65264 | 20.81402 | -0.6447 | 15.74811 |
November | 417.00000 | 19.75012 | 11.34029 | -1.0368 | 29.80529 |
December | 422.00000 | 19.64568 | 9.32372 | -1.1055 | 32.58930 |
Annual Sum or Average | 5034.00000 | 21.68976 | 21.54583 | -0.7302 | 20.70523 |
Minimum of Months | 385.00000 | 19.64568 | 9.32372 | -1.1691 | 9.16333 |
Maximum of Months | 433.00000 | 24.14075 | 42.05501 | -0.2531 | 37.08025 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95276 | 11.59200 | -0.9911 | 27.87518 |
February | 454.00000 | 20.56969 | 13.13129 | -0.7445 | 19.77530 |
March | 514.00000 | 21.59277 | 13.58123 | -0.4027 | 12.84964 |
April | 485.00000 | 22.80265 | 14.45367 | -0.0119 | 9.80207 |
May | 508.00000 | 23.49312 | 20.95030 | -0.6760 | 18.99235 |
June | 496.00000 | 23.83778 | 34.09219 | -0.4505 | 11.48045 |
July | 497.00000 | 23.96911 | 42.55404 | -0.3522 | 10.19953 |
August | 514.00000 | 23.68758 | 37.80899 | -0.4893 | 13.66097 |
September | 485.00000 | 22.76296 | 28.38132 | -0.9594 | 29.21841 |
October | 502.00000 | 21.23527 | 20.62850 | -0.4697 | 12.72398 |
November | 489.00000 | 20.12489 | 11.37490 | -0.9118 | 24.79145 |
December | 497.00000 | 19.87698 | 9.41998 | -1.0438 | 29.79760 |
Annual Sum or Average | 5943.00000 | 22.00557 | 21.58367 | -0.6238 | 18.38367 |
Minimum of Months | 454.00000 | 19.87698 | 9.41998 | -1.0438 | 9.80207 |
Maximum of Months | 514.00000 | 23.96911 | 42.55404 | -0.0119 | 29.79760 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95340 | 11.55248 | -1.0016 | 28.13167 |
February | 454.00000 | 20.12301 | 13.41101 | -0.8910 | 23.95238 |
March | 514.00000 | 20.70989 | 14.19557 | -0.6739 | 16.24699 |
April | 485.00000 | 22.13824 | 15.09557 | -0.2096 | 9.66862 |
May | 508.00000 | 23.25312 | 21.41423 | -0.8052 | 21.52336 |
June | 496.00000 | 23.91790 | 34.06917 | -0.4393 | 11.01816 |
July | 497.00000 | 23.95585 | 42.70769 | -0.3884 | 9.85692 |
August | 514.00000 | 23.51794 | 38.32064 | -0.5981 | 15.06212 |
September | 485.00000 | 22.08048 | 29.51802 | -1.2334 | 38.93240 |
October | 502.00000 | 20.69972 | 21.15682 | -0.6276 | 14.92089 |
November | 489.00000 | 20.05096 | 11.38198 | -0.9438 | 25.70415 |
December | 497.00000 | 19.93878 | 9.33378 | -1.0131 | 28.40245 |
Annual Sum or Average | 5943.00000 | 21.70946 | 21.93282 | -0.7338 | 20.21441 |
Minimum of Months | 454.00000 | 19.93878 | 9.33378 | -1.2334 | 9.66862 |
Maximum of Months | 514.00000 | 23.95585 | 42.70769 | -0.2096 | 38.93240 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63259 | 12.15424 | -1.1675 | 35.22258 |
February | 454.00000 | 19.74884 | 14.28681 | -1.0935 | 32.27510 |
March | 514.00000 | 20.08608 | 15.27804 | -0.9428 | 26.01191 |
April | 485.00000 | 20.82577 | 17.13810 | -0.6340 | 16.91326 |
May | 508.00000 | 22.94369 | 22.39365 | -1.0163 | 28.86005 |
June | 496.00000 | 23.97124 | 34.07028 | -0.5107 | 11.35281 |
July | 497.00000 | 24.08634 | 42.48028 | -0.4288 | 9.42328 |
August | 514.00000 | 23.38242 | 39.08297 | -0.7493 | 19.39723 |
September | 485.00000 | 21.32669 | 31.91358 | -1.5969 | 55.77176 |
October | 502.00000 | 20.02372 | 23.09716 | -0.8839 | 24.22779 |
November | 489.00000 | 19.69765 | 12.27470 | -1.1409 | 34.10537 |
December | 497.00000 | 19.59997 | 10.00826 | -1.1985 | 36.53924 |
Annual Sum or Average | 5943.00000 | 21.29389 | 22.93084 | -0.9447 | 27.41079 |
Minimum of Months | 454.00000 | 19.59997 | 10.00826 | -1.5969 | 9.42328 |
Maximum of Months | 514.00000 | 24.08634 | 42.48028 | -0.4288 | 55.77176 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73536 | 11.60352 | -1.1485 | 34.31148 |
February | 454.00000 | 19.85609 | 13.66369 | -1.0492 | 30.43079 |
March | 514.00000 | 20.32646 | 14.49367 | -0.8137 | 21.65569 |
April | 485.00000 | 21.54985 | 15.87286 | -0.3945 | 13.03141 |
May | 508.00000 | 23.40106 | 21.11922 | -0.7092 | 19.85377 |
June | 496.00000 | 23.86755 | 33.92805 | -0.4189 | 10.82654 |
July | 497.00000 | 24.03299 | 42.21920 | -0.3108 | 9.42421 |
August | 514.00000 | 23.45109 | 38.46316 | -0.6033 | 15.91587 |
September | 485.00000 | 21.72558 | 30.62896 | -1.3966 | 47.04521 |
October | 502.00000 | 20.14459 | 22.34658 | -0.8273 | 22.25015 |
November | 489.00000 | 19.76750 | 11.62055 | -1.1282 | 33.50326 |
December | 497.00000 | 19.70266 | 9.50809 | -1.1839 | 35.80213 |
Annual Sum or Average | 5943.00000 | 21.47966 | 22.20549 | -0.8292 | 24.39420 |
Minimum of Months | 454.00000 | 19.70266 | 9.50809 | -1.3966 | 9.42421 |
Maximum of Months | 514.00000 | 24.03299 | 42.21920 | -0.3108 | 47.04521 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76282 | 11.57181 | -1.1163 | 33.06555 |
February | 454.00000 | 20.06811 | 13.46127 | -0.9388 | 26.66958 |
March | 514.00000 | 20.93755 | 14.01446 | -0.6236 | 18.09468 |
April | 485.00000 | 22.19440 | 15.17837 | -0.1958 | 12.26387 |
May | 508.00000 | 23.12005 | 21.47229 | -0.8185 | 24.60551 |
June | 496.00000 | 23.66501 | 34.40272 | -0.5060 | 13.57673 |
July | 497.00000 | 23.80684 | 42.85776 | -0.4031 | 11.69249 |
August | 514.00000 | 23.42572 | 38.47758 | -0.5853 | 17.09847 |
September | 485.00000 | 22.13298 | 29.86791 | -1.2219 | 40.70748 |
October | 502.00000 | 20.49354 | 21.91916 | -0.7108 | 19.42391 |
November | 489.00000 | 19.83201 | 11.55644 | -1.0711 | 31.32412 |
December | 497.00000 | 19.71768 | 9.48741 | -1.1681 | 35.14726 |
Annual Sum or Average | 5943.00000 | 21.61088 | 22.10846 | -0.7780 | 23.56867 |
Minimum of Months | 454.00000 | 19.71768 | 9.48741 | -1.2219 | 11.69249 |
Maximum of Months | 514.00000 | 23.80684 | 42.85776 | -0.1958 | 40.70748 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76945 | 11.53054 | -1.1242 | 33.29484 |
February | 454.00000 | 19.90351 | 13.57811 | -1.0201 | 29.22214 |
March | 514.00000 | 20.31638 | 14.45940 | -0.8337 | 21.99597 |
April | 485.00000 | 21.52964 | 15.85687 | -0.3887 | 13.37719 |
May | 508.00000 | 22.79503 | 22.01744 | -0.9704 | 28.47444 |
June | 496.00000 | 23.72667 | 34.39488 | -0.5005 | 13.10419 |
July | 497.00000 | 23.77306 | 43.05695 | -0.4467 | 11.39828 |
August | 514.00000 | 23.19156 | 39.10771 | -0.7138 | 19.25221 |
September | 485.00000 | 21.51046 | 30.92031 | -1.4734 | 50.42053 |
October | 502.00000 | 20.19224 | 22.22547 | -0.8107 | 21.30779 |
November | 489.00000 | 19.83468 | 11.52034 | -1.0752 | 31.29831 |
December | 497.00000 | 19.76078 | 9.42503 | -1.1324 | 33.60713 |
Annual Sum or Average | 5943.00000 | 21.37275 | 22.42842 | -0.8724 | 25.48512 |
Minimum of Months | 454.00000 | 19.76078 | 9.42503 | -1.4734 | 11.39828 |
Maximum of Months | 514.00000 | 23.77306 | 43.05695 | -0.3887 | 50.42053 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.180266E+09 | 2743.78 | 10-JAN-06:13 | 18.27 | 0.750496E+09 | 0.00 | 0.930762E+09 | 0.10 | 4.17 | 21-JAN-06:30 | 0.00 | 0.00 |
February | 87725441.71 | 2908.23 | 15-FEB-13:20 | 8.88 | 0.365300E+09 | 0.00 | 0.453026E+09 | 0.06 | 4.17 | 08-FEB-13:30 | 0.00 | 0.00 |
March | 0.132627E+09 | 8679.13 | 31-MAR-15:57 | 11.64 | 0.552245E+09 | 0.00 | 0.684872E+09 | 0.07 | 4.17 | 24-MAR-05:30 | 0.00 | 0.00 |
April | 0.378147E+09 | 27482.36 | 20-APR-14:10 | 15.37 | 0.157233E+10 | 0.00 | 0.195048E+10 | 0.09 | 4.17 | 14-APR-05:30 | 0.00 | 0.00 |
May | 0.206047E+11 | 82623.37 | 31-MAY-16:00 | 168.96 | 0.111794E+12 | 0.00 | 0.132398E+12 | 1.10 | 7.03 | 31-MAY-16:30 | 0.00 | 0.00 |
June | 0.663382E+11 | 108625.18 | 21-JUN-14:50 | 364.49 | 0.406493E+12 | 0.00 | 0.472831E+12 | 2.83 | 7.33 | 21-JUN-14:50 | 0.00 | 0.00 |
July | 0.756090E+11 | 106377.67 | 21-JUL-13:10 | 409.12 | 0.475194E+12 | 0.00 | 0.550803E+12 | 3.12 | 7.32 | 21-JUL-13:10 | 0.00 | 0.00 |
August | 0.483676E+11 | 109720.56 | 11-AUG-15:20 | 302.19 | 0.293312E+12 | 0.00 | 0.341679E+12 | 2.20 | 7.33 | 11-AUG-15:20 | 0.00 | 0.00 |
September | 0.197234E+10 | 50496.30 | 07-SEP-16:00 | 45.52 | 0.838699E+10 | 0.00 | 0.103593E+11 | 0.26 | 5.72 | 07-SEP-16:00 | 0.00 | 0.00 |
October | 0.207263E+09 | 12551.07 | 13-OCT-11:00 | 17.95 | 0.863134E+09 | 0.00 | 0.107040E+10 | 0.10 | 4.17 | 22-OCT-20:50 | 0.00 | 0.00 |
November | 0.105756E+09 | 2770.62 | 10-NOV-05:29 | 10.72 | 0.440394E+09 | 0.00 | 0.546151E+09 | 0.06 | 4.18 | 10-NOV-04:30 | 0.00 | 0.00 |
December | 78038367.94 | 2809.94 | 02-DEC-06:02 | 7.90 | 0.324908E+09 | 0.00 | 0.402946E+09 | 0.04 | 4.17 | 02-DEC-04:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.214062E+12 | 1380.99 | 0.130005E+13 | 0.00 | 0.151411E+13 | 0.84 | 0.00 | 0.00 | ||||
Minimum of Months | 78038367.94 | 2743.78 | 7.90 | 0.324908E+09 | 0.00 | 0.402946E+09 | 0.04 | 4.17 | 0.00 | 0.00 | ||
Maximum of Months | 0.756090E+11 | 109720.56 | 409.12 | 0.475194E+12 | 0.00 | 0.550803E+12 | 3.12 | 7.33 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.285622E+09 | 82623.37 | 31-MAY-16:00 | 1.00 | 0.198054E+10 | 0.00 | 0.226617E+10 | 0.01 | 6.97 | 31-MAY-15:50 | 0.00 | 0.00 |
June | 0.109623E+11 | 108625.18 | 21-JUN-14:50 | 35.00 | 0.774701E+11 | 0.00 | 0.884323E+11 | 0.34 | 7.33 | 21-JUN-14:50 | 0.00 | 0.00 |
July | 0.205152E+11 | 106377.67 | 21-JUL-13:10 | 66.80 | 0.144417E+12 | 0.00 | 0.164932E+12 | 0.63 | 7.32 | 21-JUL-13:10 | 0.00 | 0.00 |
August | 0.934692E+10 | 109720.56 | 11-AUG-15:20 | 31.17 | 0.655407E+11 | 0.00 | 0.748876E+11 | 0.29 | 7.33 | 11-AUG-15:20 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.411100E+11 | 133.96 | 0.289408E+12 | 0.00 | 0.330518E+12 | 0.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.205152E+11 | 109720.56 | 66.80 | 0.144417E+12 | 0.00 | 0.164932E+12 | 0.63 | 7.33 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.485606E+10 | 744.00 | 3206.11 | 21-JAN-21:00 | 169158.37 | 27-JAN-22:10 | 21.26 | 18.33 | 14.64 |
February | 0.863479E+10 | 672.00 | 6891.97 | 10-FEB-16:10 | 348331.83 | 10-FEB-16:10 | 24.08 | 18.33 | 14.64 |
March | 0.156908E+11 | 744.00 | 21209.66 | 22-MAR-15:23 | 598109.60 | 31-MAR-23:30 | 27.08 | 18.33 | 14.62 |
April | 0.498326E+11 | 720.00 | 49248.27 | 17-APR-12:00 | 636344.68 | 22-APR-18:11 | 30.17 | 18.38 | 14.63 |
May | 0.459846E+11 | 744.00 | 49248.27 | 06-MAY-14:00 | 330376.48 | 31-MAY-24:00 | 22.34 | 18.56 | 14.53 |
June | 0.105692E+12 | 720.00 | 49248.27 | 01-JUN-10:40 | 480595.60 | 30-JUN-23:25 | 27.26 | 20.59 | 14.63 |
July | 0.122493E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 633951.70 | 31-JUL-23:22 | 31.72 | 22.19 | 14.64 |
August | 0.120123E+12 | 744.00 | 49248.27 | 01-AUG-00:02 | 669789.72 | 11-AUG-21:02 | 33.59 | 21.39 | 14.64 |
September | 0.222235E+11 | 720.00 | 49248.27 | 02-SEP-15:00 | 314378.16 | 30-SEP-24:00 | 22.01 | 18.33 | 14.50 |
October | 0.170419E+11 | 744.00 | 38255.20 | 01-OCT-15:00 | 445613.31 | 31-OCT-23:30 | 24.43 | 18.33 | 14.61 |
November | 0.117286E+11 | 720.00 | 6547.51 | 18-NOV-04:00 | 457732.80 | 03-NOV-21:10 | 26.86 | 18.33 | 14.64 |
December | 0.149150E+11 | 744.00 | 15947.26 | 24-DEC-12:00 | 599612.19 | 29-DEC-22:10 | 29.52 | 18.33 | 14.64 |
Annual Sum or Average | 0.539215E+12 | 8760.00 | 26.72 | 19.13 | 14.61 | ||||
Minimum of Months | 0.485606E+10 | 672.00 | 3206.11 | 169158.37 | 21.26 | 18.33 | 14.50 | ||
Maximum of Months | 0.122493E+12 | 744.00 | 49248.27 | 669789.72 | 33.59 | 22.19 | 14.64 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 181436.02 | 10-JAN-06:40 | 21.03 | 21.03 | 0.18 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 181313.16 | 24-FEB-02:20 | 21.07 | 21.07 | 0.07 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 182006.89 | 30-MAR-14:30 | 21.05 | 21.05 | 0.14 |
April | 888.57 | 0.33 | 1.21 | 20-APR-14:30 | 181424.55 | 06-APR-06:00 | 20.99 | 20.99 | 0.29 |
May | 0.179348E+09 | 98.95 | 4344.07 | 31-MAY-15:10 | 941961.37 | 31-MAY-15:10 | 21.25 | 21.00 | 10.35 |
June | 0.315995E+10 | 311.36 | 16190.12 | 29-JUN-11:50 | 1085838.34 | 13-JUN-14:20 | 22.17 | 21.22 | 25.60 |
July | 0.607801E+10 | 348.10 | 16190.12 | 03-JUL-14:50 | 1087206.44 | 12-JUL-14:20 | 22.27 | 21.15 | 27.46 |
August | 0.263319E+10 | 229.97 | 16190.12 | 23-AUG-14:20 | 1082587.82 | 11-AUG-14:20 | 21.82 | 21.15 | 19.62 |
September | 692054.01 | 8.73 | 79.12 | 07-SEP-16:00 | 349937.38 | 07-SEP-16:00 | 21.07 | 21.05 | 1.98 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182357.08 | 12-OCT-11:50 | 20.98 | 20.98 | 0.18 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 181413.44 | 12-NOV-23:10 | 21.02 | 21.01 | 0.11 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 181429.99 | 26-DEC-07:00 | 20.83 | 20.83 | 0.08 |
Annual Sum or Average | 0.120512E+11 | 997.45 | 21.30 | 21.04 | 7.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 181313.16 | 20.83 | 20.83 | 0.07 | ||
Maximum of Months | 0.607801E+10 | 348.10 | 16190.12 | 1087206.44 | 22.27 | 21.22 | 27.46 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 21.07 | 21.07 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.05 | 21.05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 20.99 | 20.99 | 0.00 |
May | 2606439.05 | 0.17 | 4344.07 | 31-MAY-15:10 | 941961.37 | 31-MAY-15:10 | 21.25 | 21.25 | 0.01 |
June | 0.938974E+09 | 22.00 | 16190.12 | 29-JUN-11:50 | 1085838.34 | 13-JUN-14:20 | 22.17 | 22.05 | 1.60 |
July | 0.140106E+10 | 36.83 | 16190.12 | 03-JUL-15:00 | 1087206.44 | 12-JUL-14:20 | 22.27 | 22.07 | 2.59 |
August | 0.622284E+09 | 15.83 | 16190.12 | 23-AUG-14:20 | 1082587.82 | 11-AUG-14:20 | 21.82 | 21.73 | 1.11 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 21.07 | 21.07 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 20.98 | 20.98 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.83 | 20.83 | 0.00 |
Annual Sum or Average | 0.296493E+10 | 74.83 | 21.30 | 21.26 | 0.45 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 20.83 | 0.00 | ||
Maximum of Months | 0.140106E+10 | 36.83 | 16190.12 | 1087206.44 | 22.27 | 22.07 | 2.59 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.138855E+13 | 0.00 | 635.02 | 3374210.47 | 12-JAN-07:01 | 0.00 | 36.65 | 74.99 | 3.32 | 0.00 | 0.12 | 0.79 | 12-JAN-07:01 |
February | 0.859573E+12 | 0.00 | 558.41 | 3364590.38 | 27-FEB-07:02 | 0.00 | 34.61 | 73.67 | 2.18 | 0.00 | 0.08 | 0.79 | 27-FEB-07:02 |
March | 0.472320E+12 | 0.00 | 567.42 | 2776990.09 | 01-MAR-07:02 | 0.00 | 31.46 | 69.67 | 0.96 | 0.00 | 0.04 | 0.65 | 01-MAR-07:02 |
April | 0.111616E+12 | 0.00 | 376.84 | 1524034.95 | 11-APR-05:01 | 0.00 | 28.54 | 56.27 | 0.20 | 0.00 | 0.01 | 0.36 | 11-APR-05:01 |
May | 0.919753E+10 | 0.00 | 127.35 | 638465.87 | 27-MAY-06:10 | 0.00 | 28.85 | 38.01 | 0.02 | 0.00 | 0.00 | 0.15 | 27-MAY-06:10 |
June | 0.503797E+09 | 0.00 | 23.64 | 180668.17 | 02-JUN-06:10 | 0.00 | 26.29 | 28.11 | 0.00 | 0.00 | 0.00 | 0.04 | 02-JUN-06:10 |
July | 0.377657E+09 | 0.00 | 19.71 | 94400.84 | 17-JUL-06:10 | 0.00 | 26.18 | 27.65 | 0.00 | 0.00 | 0.00 | 0.02 | 17-JUL-06:10 |
August | 0.446587E+10 | 0.00 | 64.90 | 717739.53 | 31-AUG-06:10 | 0.00 | 26.98 | 31.74 | 0.01 | 0.00 | 0.00 | 0.17 | 31-AUG-06:10 |
September | 0.476419E+11 | 0.00 | 291.14 | 1282815.48 | 25-SEP-05:01 | 0.00 | 27.95 | 49.67 | 0.08 | 0.00 | 0.00 | 0.30 | 25-SEP-05:01 |
October | 0.295194E+12 | 0.00 | 494.91 | 2006102.26 | 23-OCT-05:01 | 0.00 | 28.11 | 63.49 | 0.53 | 0.00 | 0.03 | 0.47 | 23-OCT-05:01 |
November | 0.112799E+13 | 0.00 | 592.86 | 2772887.85 | 27-NOV-07:02 | 0.00 | 36.06 | 73.72 | 2.71 | 0.00 | 0.10 | 0.65 | 27-NOV-07:02 |
December | 0.156763E+13 | 0.00 | 643.73 | 3053381.19 | 15-DEC-07:02 | 0.00 | 38.13 | 75.85 | 3.81 | 0.00 | 0.14 | 0.72 | 15-DEC-07:02 |
Annual Sum or Average | 0.588506E+13 | 0.00 | 4395.92 | 0.00 | 30.80 | 55.12 | 1.15 | 0.00 | 0.04 | ||||
Minimum of Months | 0.377657E+09 | 0.00 | 19.71 | 94400.84 | 0.00 | 26.18 | 27.65 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.156763E+13 | 0.00 | 643.73 | 3374210.47 | 0.00 | 38.13 | 75.85 | 3.81 | 0.00 | 0.14 | 0.79 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 21.26 | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 24.08 | 24.08 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.08 | 27.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.17 | 30.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.34 | 22.34 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 27.26 | 27.26 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.72 | 31.72 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 33.59 | 33.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 22.01 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.43 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 26.86 | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.52 | 29.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 26.72 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 | 33.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 835.83 | 0.00 | 0.68 | 835.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 27-JAN-05:17 | 0.40 | 27-JAN-05:17 | 0.00 | 0.00 | 0.00 |
February | 1280.14 | 0.00 | 1.24 | 1280.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 13-FEB-07:00 | 0.29 | 13-FEB-07:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.100555E+09 | 0.00 | 7.86 | 0.100555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12105.27 | 20-APR-14:00 | 12105.27 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.100888E+11 | 0.00 | 158.48 | 0.100888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83219.76 | 31-MAY-16:00 | 83219.76 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.467512E+11 | 0.00 | 353.01 | 0.466795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126302.19 | 30-JUN-14:30 | 126302.19 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.625277E+11 | 0.00 | 388.86 | 0.623014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134960.57 | 03-JUL-15:00 | 132527.53 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.357238E+11 | 0.00 | 292.16 | 0.357216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128418.49 | 11-AUG-15:30 | 128418.49 | 11-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.617268E+09 | 0.00 | 31.85 | 0.617268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25562.88 | 07-SEP-16:00 | 25562.88 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 613.74 | 0.00 | 0.58 | 613.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 29-DEC-06:03 | 0.39 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155809E+12 | 0.00 | 1234.73 | 0.155509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.625277E+11 | 0.00 | 388.86 | 0.623014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134960.57 | 132527.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 22084.72 | 0.00 | 18.21 | 22084.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 03-JAN-05:01 | 0.93 | 03-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 11979609.42 | 0.00 | 7.47 | 11979609.42 | 0.00 | 0.00 | 0.00 | 0.00 | 38717.21 | 15-FEB-13:20 | 38717.21 | 15-FEB-13:20 | 0.00 | 0.00 | 0.00 |
March | 0.188222E+09 | 0.00 | 10.58 | 0.188222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48434.94 | 31-MAR-15:57 | 48434.94 | 31-MAR-15:57 | 0.00 | 0.00 | 0.00 |
April | 0.847543E+09 | 0.00 | 12.51 | 0.847543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 102730.84 | 20-APR-14:00 | 102730.84 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.923863E+11 | 0.00 | 154.31 | 0.923863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 792332.25 | 31-MAY-16:00 | 792332.25 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.408249E+12 | 0.00 | 328.15 | 0.407406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1195014.86 | 30-JUN-12:20 | 1131995.18 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.521039E+12 | 0.00 | 345.77 | 0.519471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1166304.76 | 21-JUL-14:50 | 1166304.76 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.282990E+12 | 0.00 | 256.02 | 0.282990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1129446.59 | 11-AUG-15:40 | 1129446.59 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.540391E+10 | 0.00 | 32.22 | 0.540391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231015.14 | 07-SEP-16:00 | 231015.14 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.120451E+09 | 0.00 | 13.96 | 0.120451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46930.22 | 12-OCT-11:15 | 46930.22 | 12-OCT-11:15 | 0.00 | 0.00 | 0.00 |
November | 13209.60 | 0.00 | 10.72 | 13209.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 06-NOV-06:01 | 1.09 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 |
December | 24437.01 | 0.00 | 7.32 | 24437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 23-DEC-14:10 | 18.21 | 23-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131124E+13 | 0.00 | 1197.24 | 0.130882E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13209.60 | 0.00 | 7.32 | 13209.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.521039E+12 | 0.00 | 345.77 | 0.519471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1195014.86 | 1166304.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 183798.09 | 0.00 | 0.27 | 183798.09 | 0.00 | 0.00 | 0.00 | 0.00 | 416.78 | 14-JAN-05:28 | 416.78 | 14-JAN-05:28 | 0.00 | 0.00 | 0.00 |
February | 281578.16 | 0.00 | 0.67 | 281578.16 | 0.00 | 0.00 | 0.00 | 0.00 | 792.76 | 01-FEB-05:43 | 792.76 | 01-FEB-05:43 | 0.00 | 0.00 | 0.00 |
March | 1698137.75 | 0.00 | 1.31 | 1698137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.44 | 22-MAR-13:50 | 1475.44 | 22-MAR-13:50 | 0.00 | 0.00 | 0.00 |
April | 28275353.59 | 0.00 | 5.06 | 28275353.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5905.27 | 20-APR-14:00 | 5905.27 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.893798E+10 | 0.00 | 148.23 | 0.893798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86726.81 | 31-MAY-16:00 | 86726.81 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.422466E+11 | 0.00 | 323.19 | 0.421502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134557.77 | 30-JUN-12:30 | 129246.22 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.541282E+11 | 0.00 | 339.03 | 0.539879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133970.78 | 21-JUL-14:50 | 133970.78 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.283909E+11 | 0.00 | 246.97 | 0.283909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124407.74 | 11-AUG-15:40 | 124407.74 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.406741E+09 | 0.00 | 31.86 | 0.406741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19758.12 | 07-SEP-16:00 | 19758.12 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 334416.33 | 0.00 | 4.17 | 334416.33 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 | 12-OCT-13:30 | 63.94 | 12-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 42848.71 | 0.00 | 0.04 | 42848.71 | 0.00 | 0.00 | 0.00 | 0.00 | 377.97 | 10-NOV-05:27 | 377.97 | 10-NOV-05:27 | 0.00 | 0.00 | 0.00 |
December | 269621.01 | 0.00 | 0.16 | 269621.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.41 | 02-DEC-06:01 | 1013.41 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134141E+12 | 0.00 | 1100.96 | 0.133905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42848.71 | 0.00 | 0.04 | 42848.71 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 | 63.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.541282E+11 | 0.00 | 339.03 | 0.539879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134557.77 | 133970.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 |
February | 42566.04 | 0.00 | 0.17 | 42566.04 | 0.00 | 0.00 | 0.00 | 0.00 | 70.94 | 08-FEB-16:40 | 70.94 | 08-FEB-16:40 | 0.00 | 0.00 | 0.00 |
March | 24481.52 | 0.00 | 0.17 | 24481.52 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 23-MAR-06:30 | 40.80 | 23-MAR-06:30 | 0.00 | 0.00 | 0.00 |
April | 199680.91 | 0.00 | 1.00 | 199680.91 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 05-APR-10:20 | 95.48 | 05-APR-10:20 | 0.00 | 0.00 | 0.00 |
May | 0.298808E+10 | 0.00 | 64.42 | 0.298808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42737.49 | 31-MAY-16:00 | 42737.49 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.207306E+11 | 0.00 | 235.64 | 0.207021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60815.04 | 30-JUN-15:00 | 60815.04 | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.311589E+11 | 0.00 | 257.17 | 0.310149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73032.05 | 25-JUL-03:02 | 64925.59 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.170481E+11 | 0.00 | 193.15 | 0.169987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67487.64 | 27-AUG-17:11 | 67487.64 | 27-AUG-17:11 | 0.00 | 0.00 | 0.00 |
September | 37076608.24 | 0.00 | 2.53 | 37076608.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9340.50 | 07-SEP-16:00 | 9340.50 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 68854.97 | 0.00 | 0.50 | 68854.97 | 0.00 | 0.00 | 0.00 | 0.00 | 82.08 | 23-OCT-16:30 | 82.08 | 23-OCT-16:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719630E+11 | 0.00 | 754.75 | 0.717411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.311589E+11 | 0.00 | 257.17 | 0.310149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73032.05 | 67487.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.308382E+12 | 0.784506E+11 | 744.00 | 0.301374E+12 | 0.700747E+10 | 0.00 | 0.33 | 26-JAN-22:02 | 0.27 | 12-JAN-08:00 | 125562.17 | 26-JAN-22:02 | 122387.65 | 20-JAN-22:03 | 4074.52 | 12-JAN-08:20 | 31556.50 | 26-JAN-22:02 | 0.00 |
February | 0.509199E+12 | 0.122375E+12 | 672.00 | 0.495639E+12 | 0.135607E+11 | 0.00 | 0.55 | 09-FEB-22:03 | 0.49 | 27-FEB-07:03 | 220228.84 | 09-FEB-22:03 | 214157.28 | 09-FEB-22:03 | 7624.09 | 18-FEB-11:00 | 57009.30 | 10-FEB-16:00 | 0.00 |
March | 0.820928E+12 | 0.189032E+12 | 744.00 | 0.799671E+12 | 0.212562E+11 | 0.00 | 0.94 | 31-MAR-24:00 | 0.71 | 01-MAR-07:03 | 404018.82 | 31-MAR-24:00 | 393315.63 | 31-MAR-24:00 | 11230.23 | 04-MAR-08:70 | 89287.59 | 31-MAR-24:00 | 0.00 |
April | 0.104628E+13 | 0.232342E+12 | 720.00 | 0.102302E+13 | 0.232600E+11 | 0.00 | 0.95 | 21-APR-16:00 | 0.37 | 30-APR-24:00 | 410852.45 | 30-APR-23:00 | 400469.96 | 20-APR-21:02 | 12951.55 | 08-APR-09:00 | 97313.38 | 22-APR-14:00 | 0.00 |
May | 0.335881E+12 | 0.854789E+11 | 744.00 | 0.328532E+12 | 0.734830E+10 | 0.00 | 0.54 | 31-MAY-24:00 | 0.31 | 27-MAY-07:00 | 216584.26 | 31-MAY-24:00 | 211828.63 | 31-MAY-24:00 | 4755.64 | 31-MAY-24:00 | 51764.40 | 31-MAY-24:00 | 0.00 |
June | 0.568366E+12 | 0.146672E+12 | 720.00 | 0.558265E+12 | 0.101014E+11 | 0.00 | 0.75 | 30-JUN-23:20 | 0.53 | 01-JUN-06:05 | 309107.67 | 30-JUN-24:00 | 303728.75 | 30-JUN-24:00 | 7149.14 | 27-JUN-12:10 | 79454.42 | 30-JUN-15:00 | 0.00 |
July | 0.837157E+12 | 0.218111E+12 | 744.00 | 0.824711E+12 | 0.124463E+11 | 0.00 | 0.96 | 31-JUL-23:15 | 0.74 | 01-JUL-06:10 | 399791.70 | 31-JUL-24:00 | 396246.76 | 31-JUL-24:00 | 10672.84 | 31-JUL-06:10 | 115525.69 | 29-JUL-17:00 | 0.00 |
August | 0.108894E+13 | 0.266353E+12 | 744.00 | 0.106919E+13 | 0.197540E+11 | 0.00 | 1.00 | 02-AUG-13:00 | 0.37 | 31-AUG-24:00 | 414134.03 | 30-AUG-22:00 | 403982.58 | 11-AUG-21:23 | 14962.36 | 08-AUG-06:10 | 130611.83 | 11-AUG-18:00 | 0.00 |
September | 0.325483E+12 | 0.822108E+11 | 720.00 | 0.317658E+12 | 0.782525E+10 | 0.00 | 0.54 | 30-SEP-24:00 | 0.31 | 29-SEP-07:00 | 216768.07 | 30-SEP-24:00 | 210865.99 | 30-SEP-24:00 | 5902.08 | 30-SEP-24:00 | 51736.43 | 30-SEP-24:00 | 0.00 |
October | 0.578545E+12 | 0.138680E+12 | 744.00 | 0.564661E+12 | 0.138839E+11 | 0.00 | 0.74 | 31-OCT-24:00 | 0.52 | 31-OCT-07:00 | 308706.52 | 31-OCT-24:00 | 301834.68 | 31-OCT-24:00 | 7872.89 | 30-OCT-09:00 | 70825.64 | 31-OCT-24:00 | 0.00 |
November | 0.791807E+12 | 0.182500E+12 | 720.00 | 0.771932E+12 | 0.198751E+11 | 0.00 | 0.75 | 24-NOV-22:02 | 0.72 | 30-NOV-07:10 | 315452.66 | 24-NOV-22:02 | 306956.31 | 03-NOV-21:02 | 11856.74 | 27-NOV-11:00 | 72066.72 | 24-NOV-22:02 | 0.00 |
December | 0.106607E+13 | 0.237173E+12 | 744.00 | 0.103965E+13 | 0.264157E+11 | 0.00 | 0.95 | 27-DEC-22:02 | 0.91 | 01-DEC-07:04 | 410728.99 | 27-DEC-22:02 | 398080.16 | 27-DEC-22:02 | 16479.42 | 12-DEC-17:00 | 90461.21 | 27-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.827704E+13 | 0.197938E+13 | 8760.00 | 0.809431E+13 | 0.182734E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.308382E+12 | 0.784506E+11 | 672.00 | 0.301374E+12 | 0.700747E+10 | 0.00 | 0.33 | 0.27 | 125562.17 | 122387.65 | 4074.52 | 31556.50 | 0.00 | ||||||
Maximum of Months | 0.108894E+13 | 0.266353E+12 | 744.00 | 0.106919E+13 | 0.264157E+11 | 0.00 | 1.00 | 0.91 | 414134.03 | 403982.58 | 16479.42 | 130611.83 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.106367E+10 | 0.337464E+09 | 595.02 | 0.106367E+10 | -0.0 | 0.00 | 0.19 | 12-JAN-22:06 | 0.00 | 01-JAN-00:02 | 1338.70 | 12-JAN-22:06 | 1338.70 | 12-JAN-22:06 | 0.00 | 17-JAN-16:40 | 390.55 | 12-JAN-22:06 | 0.00 |
February | 0.652315E+10 | 0.175570E+10 | 672.00 | 0.652315E+10 | -0.0 | 0.00 | 0.43 | 16-FEB-16:10 | 0.17 | 27-FEB-07:02 | 3523.91 | 09-FEB-16:00 | 3523.91 | 09-FEB-16:00 | 0.00 | 09-FEB-17:40 | 901.69 | 16-FEB-16:10 | 0.00 |
March | 0.136097E+11 | 0.343077E+10 | 744.00 | 0.136097E+11 | 0.00 | 0.00 | 0.85 | 31-MAR-24:00 | 0.45 | 01-MAR-07:02 | 7259.46 | 31-MAR-24:00 | 7259.46 | 31-MAR-24:00 | 0.00 | 05-MAR-01:13 | 1776.62 | 31-MAR-24:00 | 0.00 |
April | 0.196600E+11 | 0.464296E+10 | 720.00 | 0.196600E+11 | -0.0 | 0.00 | 0.99 | 08-APR-18:34 | 0.31 | 30-APR-24:00 | 8967.10 | 22-APR-18:40 | 8967.10 | 22-APR-18:40 | 0.00 | 30-APR-23:20 | 2089.44 | 21-APR-18:10 | 0.00 |
May | 0.556152E+10 | 0.145639E+10 | 744.00 | 0.556136E+10 | 161949.01 | 0.00 | 0.46 | 31-MAY-24:00 | 0.15 | 27-MAY-07:00 | 4051.73 | 31-MAY-24:00 | 4051.73 | 31-MAY-24:00 | 17.76 | 16-MAY-16:10 | 975.59 | 31-MAY-24:00 | 0.00 |
June | 0.107461E+11 | 0.276127E+10 | 720.00 | 0.106744E+11 | 71714129.02 | 0.00 | 0.65 | 30-JUN-23:15 | 0.41 | 01-JUN-06:05 | 5945.80 | 30-JUN-24:00 | 5925.04 | 30-JUN-24:00 | 251.06 | 27-JUN-16:00 | 1578.81 | 30-JUN-15:00 | 0.00 |
July | 0.162565E+11 | 0.419021E+10 | 744.00 | 0.161081E+11 | 0.148383E+09 | 0.00 | 0.84 | 31-JUL-23:22 | 0.61 | 01-JUL-06:40 | 7860.18 | 31-JUL-23:45 | 7845.41 | 31-JUL-23:40 | 323.54 | 26-JUL-15:00 | 2287.75 | 21-JUL-16:00 | 0.00 |
August | 0.210643E+11 | 0.513806E+10 | 744.00 | 0.209451E+11 | 0.119253E+09 | 0.00 | 0.96 | 27-AUG-18:31 | 0.31 | 31-AUG-24:00 | 8929.33 | 27-AUG-18:53 | 8929.33 | 27-AUG-18:53 | 249.56 | 03-AUG-14:00 | 2697.97 | 11-AUG-18:10 | 0.00 |
September | 0.483224E+10 | 0.124590E+10 | 720.00 | 0.481576E+10 | 16480379.72 | 0.00 | 0.43 | 30-SEP-24:00 | 0.12 | 30-SEP-07:00 | 3473.68 | 30-SEP-24:00 | 3473.68 | 30-SEP-24:00 | 99.30 | 05-SEP-15:40 | 892.30 | 30-SEP-24:00 | 0.00 |
October | 0.897089E+10 | 0.228901E+10 | 744.00 | 0.897062E+10 | 271298.42 | 0.00 | 0.61 | 31-OCT-24:00 | 0.29 | 30-OCT-06:05 | 4984.62 | 31-OCT-24:00 | 4984.62 | 31-OCT-24:00 | 41.96 | 02-OCT-16:00 | 1265.92 | 31-OCT-24:00 | 0.00 |
November | 0.121751E+11 | 0.313596E+10 | 720.00 | 0.121751E+11 | 0.00 | 0.00 | 0.64 | 19-NOV-15:23 | 0.47 | 27-NOV-07:02 | 5293.77 | 03-NOV-01:40 | 5293.77 | 03-NOV-01:40 | 0.00 | 02-NOV-18:00 | 1342.69 | 19-NOV-15:23 | 0.00 |
December | 0.172807E+11 | 0.431311E+10 | 744.00 | 0.172807E+11 | 0.00 | 0.00 | 0.82 | 21-DEC-01:40 | 0.68 | 15-DEC-07:02 | 7087.54 | 24-DEC-18:00 | 7087.54 | 24-DEC-18:00 | 0.00 | 23-DEC-07:25 | 1708.49 | 21-DEC-01:40 | 0.00 |
Annual Sum or Average | 0.137744E+12 | 0.346968E+11 | 8611.02 | 0.137388E+12 | 0.356264E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.106367E+10 | 0.337464E+09 | 595.02 | 0.106367E+10 | -0.0 | 0.00 | 0.19 | 0.00 | 1338.70 | 1338.70 | 0.00 | 390.55 | 0.00 | ||||||
Maximum of Months | 0.210643E+11 | 0.513806E+10 | 744.00 | 0.209451E+11 | 0.148383E+09 | 0.00 | 0.99 | 0.68 | 8967.10 | 8967.10 | 323.54 | 2697.97 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.900516E+09 | 0.345770E+09 | 134.58 | 0.900516E+09 | -0.0 | 0.00 | 0.12 | 27-JAN-22:03 | 0.00 | 01-JAN-00:02 | 7800.23 | 27-JAN-22:03 | 7800.23 | 27-JAN-22:03 | 0.00 | 28-JAN-01:40 | 2334.12 | 27-JAN-22:03 | 0.00 |
February | 0.425391E+11 | 0.117706E+11 | 672.00 | 0.425391E+11 | -0.0 | 0.00 | 0.39 | 16-FEB-16:10 | 0.02 | 27-FEB-07:02 | 29887.62 | 16-FEB-16:10 | 29887.62 | 16-FEB-16:10 | 0.00 | 02-FEB-17:10 | 7855.20 | 16-FEB-16:10 | 0.00 |
March | 0.110465E+12 | 0.283472E+11 | 744.00 | 0.110465E+12 | -0.0 | 0.00 | 0.79 | 31-MAR-23:10 | 0.35 | 01-MAR-07:02 | 63727.69 | 31-MAR-23:20 | 63727.69 | 31-MAR-23:20 | 0.00 | 23-MAR-23:40 | 15791.81 | 31-MAR-23:10 | 0.00 |
April | 0.175164E+12 | 0.417578E+11 | 720.00 | 0.175164E+12 | 0.00 | 0.00 | 0.96 | 22-APR-18:35 | 0.24 | 30-APR-24:00 | 83929.28 | 20-APR-18:50 | 83929.28 | 20-APR-18:50 | 0.00 | 24-APR-05:06 | 19919.86 | 21-APR-18:10 | 0.00 |
May | 0.478894E+11 | 0.126538E+11 | 744.00 | 0.478876E+11 | 1834398.76 | 0.00 | 0.45 | 31-MAY-24:00 | 0.10 | 27-MAY-07:00 | 37967.41 | 31-MAY-24:00 | 37967.41 | 31-MAY-24:00 | 203.70 | 16-MAY-16:10 | 9164.77 | 31-MAY-24:00 | 0.00 |
June | 0.100276E+12 | 0.258642E+11 | 720.00 | 0.995636E+11 | 0.712853E+09 | 0.00 | 0.65 | 30-JUN-23:25 | 0.38 | 24-JUN-17:00 | 57211.12 | 30-JUN-24:00 | 57002.52 | 30-JUN-24:00 | 2495.61 | 27-JUN-16:00 | 15085.17 | 30-JUN-15:00 | 0.00 |
July | 0.153349E+12 | 0.396265E+11 | 744.00 | 0.151872E+12 | 0.147654E+10 | 0.00 | 0.85 | 31-JUL-23:15 | 0.58 | 06-JUL-06:10 | 76049.94 | 31-JUL-23:53 | 75864.18 | 31-JUL-23:55 | 3211.12 | 26-JUL-15:00 | 21809.33 | 21-JUL-16:00 | 0.00 |
August | 0.197946E+12 | 0.484546E+11 | 744.00 | 0.196755E+12 | 0.119102E+10 | 0.00 | 0.95 | 10-AUG-18:50 | 0.24 | 31-AUG-24:00 | 83561.29 | 27-AUG-18:46 | 83561.29 | 27-AUG-18:46 | 2488.18 | 03-AUG-14:00 | 25747.03 | 11-AUG-18:10 | 0.00 |
September | 0.363518E+11 | 0.954565E+10 | 720.00 | 0.361940E+11 | 0.157811E+09 | 0.00 | 0.36 | 30-SEP-23:50 | 0.05 | 30-SEP-07:00 | 27307.48 | 30-SEP-23:50 | 27307.48 | 30-SEP-23:50 | 970.35 | 05-SEP-15:50 | 7145.76 | 30-SEP-23:50 | 0.00 |
October | 0.653320E+11 | 0.170418E+11 | 744.00 | 0.653289E+11 | 3086355.33 | 0.00 | 0.51 | 31-OCT-23:20 | 0.13 | 30-OCT-06:05 | 39135.27 | 31-OCT-23:20 | 39135.27 | 31-OCT-23:20 | 419.28 | 02-OCT-16:00 | 10156.91 | 31-OCT-23:20 | 0.00 |
November | 0.908169E+11 | 0.240089E+11 | 720.00 | 0.908169E+11 | -0.0 | 0.00 | 0.58 | 08-NOV-15:50 | 0.30 | 27-NOV-07:02 | 45662.33 | 08-NOV-15:50 | 45662.33 | 08-NOV-15:50 | 0.00 | 03-NOV-03:30 | 11694.89 | 08-NOV-15:50 | 0.00 |
December | 0.137145E+12 | 0.350588E+11 | 744.00 | 0.137145E+12 | 0.00 | 0.00 | 0.75 | 22-DEC-22:01 | 0.55 | 04-DEC-07:03 | 60234.94 | 21-DEC-22:05 | 60234.94 | 21-DEC-22:05 | 0.00 | 09-DEC-04:27 | 15073.09 | 22-DEC-22:01 | 0.00 |
Annual Sum or Average | 0.115817E+13 | 0.294476E+12 | 8150.58 | 0.115463E+13 | 0.354314E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.900516E+09 | 0.345770E+09 | 134.58 | 0.900516E+09 | -0.0 | 0.00 | 0.12 | 0.00 | 7800.23 | 7800.23 | 0.00 | 2334.12 | 0.00 | ||||||
Maximum of Months | 0.197946E+12 | 0.484546E+11 | 744.00 | 0.196755E+12 | 0.147654E+10 | 0.00 | 0.96 | 0.58 | 83929.28 | 83929.28 | 3211.12 | 25747.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 97286.95 | 99437.64 | 1.00 | 97286.95 | -0.0 | 0.00 | 0.02 | 19-JAN-17:00 | 0.00 | 01-JAN-00:02 | 41.31 | 19-JAN-17:00 | 41.31 | 19-JAN-17:00 | 0.00 | 19-JAN-16:50 | 31.51 | 19-JAN-17:00 | 0.00 |
February | 0.241999E+10 | 0.687193E+09 | 558.94 | 0.241999E+10 | 0.00 | 0.00 | 0.34 | 09-FEB-16:00 | 0.00 | 01-FEB-00:03 | 2694.33 | 09-FEB-16:00 | 2694.33 | 09-FEB-16:00 | 0.00 | 14-FEB-05:46 | 684.51 | 09-FEB-16:00 | 0.00 |
March | 0.890518E+10 | 0.232992E+10 | 744.00 | 0.890518E+10 | -0.0 | 0.00 | 0.68 | 31-MAR-23:10 | 0.22 | 06-MAR-04:03 | 5455.37 | 31-MAR-23:10 | 5455.37 | 31-MAR-23:10 | 0.00 | 20-MAR-00:10 | 1380.03 | 31-MAR-23:10 | 0.00 |
April | 0.160442E+11 | 0.386552E+10 | 720.00 | 0.160442E+11 | -0.0 | 0.00 | 0.94 | 21-APR-18:40 | 0.16 | 30-APR-24:00 | 8388.92 | 20-APR-18:50 | 8388.92 | 20-APR-18:50 | 0.00 | 05-APR-24:00 | 1994.61 | 21-APR-18:10 | 0.00 |
May | 0.414724E+10 | 0.110844E+10 | 743.67 | 0.414707E+10 | 168234.26 | 0.00 | 0.45 | 31-MAY-24:00 | 0.00 | 27-MAY-02:55 | 3750.15 | 31-MAY-24:00 | 3750.15 | 31-MAY-24:00 | 19.42 | 16-MAY-16:10 | 907.09 | 31-MAY-24:00 | 0.00 |
June | 0.985563E+10 | 0.255224E+10 | 720.00 | 0.978446E+10 | 71170321.61 | 0.00 | 0.64 | 30-JUN-23:15 | 0.33 | 25-JUN-05:00 | 5686.73 | 30-JUN-24:00 | 5665.70 | 30-JUN-24:00 | 249.87 | 27-JUN-16:00 | 1527.81 | 30-JUN-15:00 | 0.00 |
July | 0.151967E+11 | 0.394036E+10 | 744.00 | 0.150492E+11 | 0.147512E+09 | 0.00 | 0.84 | 31-JUL-23:15 | 0.55 | 06-JUL-06:10 | 7572.79 | 31-JUL-23:53 | 7555.12 | 31-JUL-23:40 | 320.95 | 26-JUL-15:00 | 2204.47 | 21-JUL-16:00 | 0.00 |
August | 0.194436E+11 | 0.478219E+10 | 744.00 | 0.193247E+11 | 0.118912E+09 | 0.00 | 0.95 | 10-AUG-18:50 | 0.19 | 31-AUG-24:00 | 8380.44 | 27-AUG-18:42 | 8380.44 | 27-AUG-18:42 | 248.80 | 03-AUG-14:00 | 2591.23 | 11-AUG-18:10 | 0.00 |
September | 0.238044E+10 | 0.641833E+09 | 669.60 | 0.236563E+10 | 14817807.28 | 0.00 | 0.29 | 02-SEP-17:53 | 0.00 | 05-SEP-02:45 | 2358.66 | 02-SEP-17:57 | 2358.66 | 02-SEP-17:57 | 95.95 | 05-SEP-16:00 | 592.63 | 02-SEP-17:53 | 0.00 |
October | 0.428930E+10 | 0.114912E+10 | 722.64 | 0.428903E+10 | 274440.80 | 0.00 | 0.42 | 03-OCT-16:00 | 0.00 | 09-OCT-06:15 | 3523.51 | 03-OCT-16:00 | 3523.51 | 03-OCT-16:00 | 38.59 | 02-OCT-16:00 | 850.09 | 03-OCT-16:00 | 0.00 |
November | 0.687256E+10 | 0.186174E+10 | 720.00 | 0.687256E+10 | -0.0 | 0.00 | 0.52 | 08-NOV-15:50 | 0.17 | 27-NOV-03:50 | 4072.89 | 08-NOV-15:50 | 4072.89 | 08-NOV-15:50 | 0.00 | 29-NOV-14:20 | 1056.90 | 08-NOV-15:50 | 0.00 |
December | 0.116224E+11 | 0.302762E+10 | 744.00 | 0.116224E+11 | 0.00 | 0.00 | 0.69 | 20-DEC-22:02 | 0.41 | 04-DEC-00:30 | 5594.09 | 19-DEC-22:02 | 5594.09 | 19-DEC-22:02 | 0.00 | 25-DEC-16:10 | 1391.21 | 20-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.101177E+12 | 0.259463E+11 | 7831.84 | 0.100824E+12 | 0.352856E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 97286.95 | 99437.64 | 1.00 | 97286.95 | -0.0 | 0.00 | 0.02 | 0.00 | 41.31 | 41.31 | 0.00 | 31.51 | 0.00 | ||||||
Maximum of Months | 0.194436E+11 | 0.478219E+10 | 744.00 | 0.193247E+11 | 0.147512E+09 | 0.00 | 0.95 | 0.55 | 8388.92 | 8388.92 | 320.95 | 2591.23 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.61 | 0.00 | 12.61 | 0.00 | 915.34 | 0.00 | 0.00 | 0.00 |
February | 55.75 | 0.00 | 55.75 | 0.00 | 831.92 | 0.00 | 0.00 | 0.00 |
March | 149.11 | 0.00 | 149.11 | 9.34 | 630.83 | 0.00 | 0.00 | 0.00 |
April | 269.78 | 5.94 | 263.84 | 97.02 | 347.79 | 0.00 | 0.00 | 0.00 |
May | 413.47 | 65.74 | 347.74 | 309.70 | 147.86 | 0.00 | 0.00 | 0.00 |
June | 539.47 | 119.97 | 419.50 | 519.06 | 68.04 | 0.00 | 0.00 | 0.00 |
July | 452.77 | 73.59 | 379.18 | 443.99 | 82.99 | 0.00 | 0.00 | 0.00 |
August | 289.11 | 16.16 | 272.95 | 227.68 | 141.09 | 0.00 | 0.00 | 0.00 |
September | 161.29 | 0.16 | 161.13 | 54.17 | 297.48 | 0.00 | 0.00 | 0.00 |
October | 78.48 | 0.00 | 78.48 | 3.27 | 556.60 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 0.00 | 918.22 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 979.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.90 | 23.57 | 181.33 | 139.51 | 491.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 68.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.47 | 119.97 | 419.50 | 519.06 | 979.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.61 | 0.00 | 12.61 | 0.00 | 915.34 | 0.00 | 0.00 | 0.00 |
February | 55.75 | 0.00 | 55.75 | 0.00 | 831.92 | 0.00 | 0.00 | 0.00 |
March | 149.10 | 0.00 | 149.10 | 9.34 | 630.83 | 0.00 | 0.00 | 0.00 |
April | 269.77 | 5.94 | 263.83 | 97.02 | 347.79 | 0.00 | 0.00 | 0.00 |
May | 413.47 | 65.74 | 347.73 | 309.69 | 147.86 | 0.00 | 0.00 | 0.00 |
June | 539.46 | 119.97 | 419.49 | 519.05 | 68.04 | 0.00 | 0.00 | 0.00 |
July | 452.76 | 73.59 | 379.17 | 443.98 | 82.99 | 0.00 | 0.00 | 0.00 |
August | 289.11 | 16.16 | 272.95 | 227.68 | 141.09 | 0.00 | 0.00 | 0.00 |
September | 161.29 | 0.16 | 161.13 | 54.17 | 297.48 | 0.00 | 0.00 | 0.00 |
October | 78.48 | 0.00 | 78.48 | 3.27 | 556.60 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 0.00 | 918.22 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 979.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.90 | 23.57 | 181.33 | 139.51 | 491.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 68.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.46 | 119.97 | 419.49 | 519.05 | 979.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.61 | 0.00 | 12.61 | 0.00 | 915.34 | 0.00 | 0.00 | 0.00 |
February | 55.75 | 0.00 | 55.75 | 0.00 | 831.92 | 0.00 | 0.00 | 0.00 |
March | 149.11 | 0.00 | 149.11 | 9.34 | 630.83 | 0.00 | 0.00 | 0.00 |
April | 269.77 | 5.94 | 263.83 | 97.02 | 347.79 | 0.00 | 0.00 | 0.00 |
May | 413.47 | 65.74 | 347.73 | 309.70 | 147.86 | 0.00 | 0.00 | 0.00 |
June | 539.46 | 119.97 | 419.49 | 519.05 | 68.04 | 0.00 | 0.00 | 0.00 |
July | 452.76 | 73.59 | 379.17 | 443.98 | 82.99 | 0.00 | 0.00 | 0.00 |
August | 289.11 | 16.16 | 272.95 | 227.68 | 141.09 | 0.00 | 0.00 | 0.00 |
September | 161.29 | 0.16 | 161.13 | 54.17 | 297.48 | 0.00 | 0.00 | 0.00 |
October | 78.48 | 0.00 | 78.48 | 3.27 | 556.60 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 0.00 | 918.22 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 979.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.90 | 23.57 | 181.33 | 139.51 | 491.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 68.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.46 | 119.97 | 419.49 | 519.05 | 979.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.61 | 0.00 | 12.61 | 0.00 | 915.34 | 0.00 | 0.00 | 0.00 |
February | 55.75 | 0.00 | 55.75 | 0.00 | 831.92 | 0.00 | 0.00 | 0.00 |
March | 149.10 | 0.00 | 149.10 | 9.34 | 630.83 | 0.00 | 0.00 | 0.00 |
April | 269.77 | 5.94 | 263.83 | 97.02 | 347.79 | 0.00 | 0.00 | 0.00 |
May | 413.47 | 65.74 | 347.73 | 309.69 | 147.86 | 0.00 | 0.00 | 0.00 |
June | 539.46 | 119.97 | 419.49 | 519.05 | 68.04 | 0.00 | 0.00 | 0.00 |
July | 452.76 | 73.59 | 379.17 | 443.98 | 82.99 | 0.00 | 0.00 | 0.00 |
August | 289.11 | 16.16 | 272.95 | 227.68 | 141.09 | 0.00 | 0.00 | 0.00 |
September | 161.29 | 0.16 | 161.13 | 54.17 | 297.48 | 0.00 | 0.00 | 0.00 |
October | 78.48 | 0.00 | 78.48 | 3.27 | 556.60 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 0.00 | 918.22 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 979.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.90 | 23.57 | 181.33 | 139.51 | 491.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 68.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.46 | 119.97 | 419.49 | 519.05 | 979.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.61 | 0.00 | 12.61 | 0.00 | 915.30 | 0.00 | 0.00 | 0.00 |
February | 55.75 | 0.00 | 55.75 | 0.00 | 831.89 | 0.00 | 0.00 | 0.00 |
March | 149.10 | 0.00 | 149.10 | 9.34 | 630.81 | 0.00 | 0.00 | 0.00 |
April | 269.76 | 5.94 | 263.82 | 97.02 | 347.78 | 0.00 | 0.00 | 0.00 |
May | 413.45 | 65.73 | 347.72 | 309.68 | 147.85 | 0.00 | 0.00 | 0.00 |
June | 539.44 | 119.96 | 419.48 | 519.03 | 68.04 | 0.00 | 0.00 | 0.00 |
July | 452.74 | 73.59 | 379.15 | 443.96 | 82.99 | 0.00 | 0.00 | 0.00 |
August | 289.10 | 16.16 | 272.94 | 227.67 | 141.08 | 0.00 | 0.00 | 0.00 |
September | 161.28 | 0.16 | 161.12 | 54.17 | 297.47 | 0.00 | 0.00 | 0.00 |
October | 78.48 | 0.00 | 78.48 | 3.27 | 556.58 | 0.00 | 0.00 | 0.00 |
November | 24.35 | 0.00 | 24.35 | 0.00 | 918.18 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 979.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.89 | 23.57 | 181.32 | 139.50 | 491.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 68.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.44 | 119.96 | 419.48 | 519.03 | 979.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.91 | 11.62 | 25.30 | 3.30 | 980.47 | 0.00 | 0.00 | 0.00 |
February | 203.96 | 97.32 | 106.63 | 104.25 | 830.03 | 0.00 | 0.00 | 0.00 |
March | 581.76 | 294.61 | 287.15 | 476.30 | 620.59 | 0.00 | 0.00 | 0.00 |
April | 799.65 | 404.54 | 395.11 | 719.15 | 343.92 | 0.00 | 0.00 | 0.00 |
May | 1161.67 | 653.96 | 507.71 | 1247.63 | 174.63 | 0.00 | 0.00 | 0.00 |
June | 1068.76 | 497.91 | 570.85 | 1190.73 | 83.24 | 0.00 | 0.00 | 0.00 |
July | 1015.18 | 491.61 | 523.57 | 1159.89 | 94.08 | 0.00 | 0.00 | 0.00 |
August | 804.09 | 391.05 | 413.04 | 877.82 | 148.96 | 0.00 | 0.00 | 0.00 |
September | 497.43 | 217.75 | 279.68 | 449.24 | 300.65 | 0.00 | 0.00 | 0.00 |
October | 262.75 | 105.43 | 157.32 | 179.05 | 551.14 | 0.00 | 0.00 | 0.00 |
November | 55.89 | 19.53 | 36.36 | 4.35 | 972.29 | 0.00 | 0.00 | 0.00 |
December | 7.98 | 1.91 | 6.07 | 0.00 | 1068.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.41 | 266.77 | 276.63 | 537.23 | 512.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.98 | 1.91 | 6.07 | 0.00 | 83.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.67 | 653.96 | 570.85 | 1247.63 | 1068.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.91 | 11.62 | 25.30 | 3.30 | 980.47 | 0.00 | 0.00 | 0.00 |
February | 203.96 | 97.32 | 106.63 | 104.25 | 830.03 | 0.00 | 0.00 | 0.00 |
March | 581.76 | 294.61 | 287.15 | 476.30 | 620.59 | 0.00 | 0.00 | 0.00 |
April | 799.65 | 404.54 | 395.11 | 719.15 | 343.92 | 0.00 | 0.00 | 0.00 |
May | 1161.67 | 653.96 | 507.71 | 1247.63 | 174.63 | 0.00 | 0.00 | 0.00 |
June | 1068.76 | 497.91 | 570.85 | 1190.73 | 83.24 | 0.00 | 0.00 | 0.00 |
July | 1015.18 | 491.61 | 523.57 | 1159.89 | 94.08 | 0.00 | 0.00 | 0.00 |
August | 804.09 | 391.05 | 413.04 | 877.82 | 148.96 | 0.00 | 0.00 | 0.00 |
September | 497.43 | 217.75 | 279.68 | 449.24 | 300.65 | 0.00 | 0.00 | 0.00 |
October | 262.75 | 105.43 | 157.32 | 179.05 | 551.14 | 0.00 | 0.00 | 0.00 |
November | 55.89 | 19.53 | 36.36 | 4.35 | 972.29 | 0.00 | 0.00 | 0.00 |
December | 7.98 | 1.91 | 6.07 | 0.00 | 1068.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.41 | 266.77 | 276.63 | 537.23 | 512.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.98 | 1.91 | 6.07 | 0.00 | 83.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.67 | 653.96 | 570.85 | 1247.63 | 1068.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.91 | 11.62 | 25.30 | 3.30 | 980.45 | 0.00 | 0.00 | 0.00 |
February | 203.95 | 97.32 | 106.63 | 104.24 | 830.02 | 0.00 | 0.00 | 0.00 |
March | 581.75 | 294.60 | 287.14 | 476.29 | 620.58 | 0.00 | 0.00 | 0.00 |
April | 799.64 | 404.53 | 395.11 | 719.14 | 343.91 | 0.00 | 0.00 | 0.00 |
May | 1161.65 | 653.95 | 507.70 | 1247.60 | 174.63 | 0.00 | 0.00 | 0.00 |
June | 1068.74 | 497.90 | 570.84 | 1190.71 | 83.24 | 0.00 | 0.00 | 0.00 |
July | 1015.16 | 491.60 | 523.56 | 1159.87 | 94.08 | 0.00 | 0.00 | 0.00 |
August | 804.08 | 391.04 | 413.04 | 877.81 | 148.96 | 0.00 | 0.00 | 0.00 |
September | 497.42 | 217.74 | 279.68 | 449.23 | 300.65 | 0.00 | 0.00 | 0.00 |
October | 262.74 | 105.43 | 157.31 | 179.05 | 551.13 | 0.00 | 0.00 | 0.00 |
November | 55.89 | 19.53 | 36.36 | 4.35 | 972.27 | 0.00 | 0.00 | 0.00 |
December | 7.98 | 1.91 | 6.07 | 0.00 | 1068.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.40 | 266.77 | 276.63 | 537.22 | 512.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.98 | 1.91 | 6.07 | 0.00 | 83.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.65 | 653.95 | 570.84 | 1247.60 | 1068.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.30 | 99.68 | 51.62 | 87.06 | 811.71 | 0.00 | 0.00 | 0.00 |
February | 520.62 | 362.15 | 158.48 | 431.65 | 663.39 | 0.00 | 0.00 | 0.00 |
March | 894.02 | 605.97 | 288.04 | 855.27 | 516.63 | 0.00 | 0.00 | 0.00 |
April | 1090.68 | 678.51 | 412.17 | 1164.27 | 342.10 | 0.00 | 0.00 | 0.00 |
May | 899.36 | 466.01 | 433.35 | 992.17 | 181.64 | 0.00 | 0.00 | 0.00 |
June | 821.15 | 336.57 | 484.58 | 932.19 | 95.69 | 0.00 | 0.00 | 0.00 |
July | 791.15 | 344.55 | 446.61 | 919.55 | 101.24 | 0.00 | 0.00 | 0.00 |
August | 819.32 | 451.54 | 367.78 | 936.36 | 151.40 | 0.00 | 0.00 | 0.00 |
September | 662.16 | 398.78 | 263.37 | 684.52 | 272.47 | 0.00 | 0.00 | 0.00 |
October | 476.75 | 302.49 | 174.27 | 421.46 | 450.37 | 0.00 | 0.00 | 0.00 |
November | 255.62 | 178.49 | 77.13 | 164.81 | 772.76 | 0.00 | 0.00 | 0.00 |
December | 45.37 | 31.98 | 13.39 | 7.88 | 914.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.80 | 354.19 | 264.61 | 633.62 | 438.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.37 | 31.98 | 13.39 | 7.88 | 95.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1090.68 | 678.51 | 484.58 | 1164.27 | 914.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.30 | 99.68 | 51.62 | 87.06 | 811.71 | 0.00 | 0.00 | 0.00 |
February | 520.62 | 362.14 | 158.48 | 431.64 | 663.39 | 0.00 | 0.00 | 0.00 |
March | 894.01 | 605.97 | 288.04 | 855.26 | 516.63 | 0.00 | 0.00 | 0.00 |
April | 1090.67 | 678.50 | 412.17 | 1164.26 | 342.10 | 0.00 | 0.00 | 0.00 |
May | 899.35 | 466.00 | 433.35 | 992.16 | 181.64 | 0.00 | 0.00 | 0.00 |
June | 821.14 | 336.56 | 484.58 | 932.18 | 95.69 | 0.00 | 0.00 | 0.00 |
July | 791.15 | 344.54 | 446.60 | 919.55 | 101.24 | 0.00 | 0.00 | 0.00 |
August | 819.31 | 451.53 | 367.78 | 936.35 | 151.40 | 0.00 | 0.00 | 0.00 |
September | 662.15 | 398.78 | 263.37 | 684.51 | 272.47 | 0.00 | 0.00 | 0.00 |
October | 476.75 | 302.48 | 174.27 | 421.46 | 450.37 | 0.00 | 0.00 | 0.00 |
November | 255.62 | 178.49 | 77.13 | 164.80 | 772.76 | 0.00 | 0.00 | 0.00 |
December | 45.37 | 31.98 | 13.39 | 7.88 | 914.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.79 | 354.19 | 264.61 | 633.62 | 438.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.37 | 31.98 | 13.39 | 7.88 | 95.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1090.67 | 678.50 | 484.58 | 1164.26 | 914.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.30 | 99.68 | 51.62 | 87.06 | 811.71 | 0.00 | 0.00 | 0.00 |
February | 520.62 | 362.15 | 158.48 | 431.65 | 663.39 | 0.00 | 0.00 | 0.00 |
March | 894.02 | 605.97 | 288.04 | 855.27 | 516.63 | 0.00 | 0.00 | 0.00 |
April | 1090.68 | 678.51 | 412.17 | 1164.27 | 342.10 | 0.00 | 0.00 | 0.00 |
May | 899.36 | 466.01 | 433.35 | 992.17 | 181.64 | 0.00 | 0.00 | 0.00 |
June | 821.15 | 336.57 | 484.58 | 932.19 | 95.69 | 0.00 | 0.00 | 0.00 |
July | 791.15 | 344.55 | 446.61 | 919.55 | 101.24 | 0.00 | 0.00 | 0.00 |
August | 819.32 | 451.54 | 367.78 | 936.36 | 151.40 | 0.00 | 0.00 | 0.00 |
September | 662.16 | 398.78 | 263.37 | 684.52 | 272.47 | 0.00 | 0.00 | 0.00 |
October | 476.75 | 302.49 | 174.27 | 421.46 | 450.37 | 0.00 | 0.00 | 0.00 |
November | 255.62 | 178.49 | 77.13 | 164.81 | 772.76 | 0.00 | 0.00 | 0.00 |
December | 45.37 | 31.98 | 13.39 | 7.88 | 914.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.80 | 354.19 | 264.61 | 633.62 | 438.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.37 | 31.98 | 13.39 | 7.88 | 95.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1090.68 | 678.51 | 484.58 | 1164.27 | 914.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.30 | 99.68 | 51.62 | 87.06 | 811.71 | 0.00 | 0.00 | 0.00 |
February | 520.62 | 362.14 | 158.48 | 431.64 | 663.39 | 0.00 | 0.00 | 0.00 |
March | 894.01 | 605.97 | 288.04 | 855.26 | 516.63 | 0.00 | 0.00 | 0.00 |
April | 1090.67 | 678.50 | 412.17 | 1164.26 | 342.10 | 0.00 | 0.00 | 0.00 |
May | 899.35 | 466.00 | 433.35 | 992.16 | 181.64 | 0.00 | 0.00 | 0.00 |
June | 821.14 | 336.56 | 484.58 | 932.18 | 95.69 | 0.00 | 0.00 | 0.00 |
July | 791.15 | 344.54 | 446.60 | 919.55 | 101.24 | 0.00 | 0.00 | 0.00 |
August | 819.31 | 451.53 | 367.78 | 936.35 | 151.40 | 0.00 | 0.00 | 0.00 |
September | 662.15 | 398.78 | 263.37 | 684.51 | 272.47 | 0.00 | 0.00 | 0.00 |
October | 476.75 | 302.48 | 174.27 | 421.46 | 450.37 | 0.00 | 0.00 | 0.00 |
November | 255.62 | 178.49 | 77.13 | 164.80 | 772.76 | 0.00 | 0.00 | 0.00 |
December | 45.37 | 31.98 | 13.39 | 7.88 | 914.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.79 | 354.19 | 264.61 | 633.62 | 438.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.37 | 31.98 | 13.39 | 7.88 | 95.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1090.67 | 678.50 | 484.58 | 1164.26 | 914.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.29 | 99.68 | 51.62 | 87.06 | 811.68 | 0.00 | 0.00 | 0.00 |
February | 520.60 | 362.13 | 158.47 | 431.63 | 663.37 | 0.00 | 0.00 | 0.00 |
March | 893.98 | 605.95 | 288.03 | 855.23 | 516.61 | 0.00 | 0.00 | 0.00 |
April | 1090.63 | 678.48 | 412.15 | 1164.22 | 342.09 | 0.00 | 0.00 | 0.00 |
May | 899.32 | 465.99 | 433.33 | 992.13 | 181.63 | 0.00 | 0.00 | 0.00 |
June | 821.11 | 336.55 | 484.56 | 932.15 | 95.69 | 0.00 | 0.00 | 0.00 |
July | 791.12 | 344.53 | 446.59 | 919.51 | 101.23 | 0.00 | 0.00 | 0.00 |
August | 819.28 | 451.52 | 367.77 | 936.32 | 151.39 | 0.00 | 0.00 | 0.00 |
September | 662.13 | 398.77 | 263.36 | 684.49 | 272.46 | 0.00 | 0.00 | 0.00 |
October | 476.73 | 302.47 | 174.26 | 421.44 | 450.35 | 0.00 | 0.00 | 0.00 |
November | 255.61 | 178.48 | 77.13 | 164.80 | 772.73 | 0.00 | 0.00 | 0.00 |
December | 45.37 | 31.98 | 13.39 | 7.88 | 914.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.77 | 354.17 | 264.60 | 633.59 | 438.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.37 | 31.98 | 13.39 | 7.88 | 95.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1090.63 | 678.48 | 484.56 | 1164.22 | 914.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.42 | 3.47 | 15.95 | 0.00 | 1032.44 | 0.00 | 0.00 | 0.00 |
February | 114.63 | 39.86 | 74.77 | 21.14 | 901.82 | 0.00 | 0.00 | 0.00 |
March | 344.06 | 147.91 | 196.15 | 182.71 | 679.29 | 0.00 | 0.00 | 0.00 |
April | 816.43 | 423.08 | 393.35 | 743.95 | 410.48 | 0.00 | 0.00 | 0.00 |
May | 793.84 | 361.52 | 432.33 | 783.76 | 198.38 | 0.00 | 0.00 | 0.00 |
June | 870.01 | 370.95 | 499.06 | 931.95 | 110.03 | 0.00 | 0.00 | 0.00 |
July | 727.95 | 275.37 | 452.58 | 782.11 | 120.99 | 0.00 | 0.00 | 0.00 |
August | 598.30 | 253.35 | 344.95 | 603.94 | 184.75 | 0.00 | 0.00 | 0.00 |
September | 362.09 | 151.63 | 210.46 | 282.04 | 326.74 | 0.00 | 0.00 | 0.00 |
October | 141.80 | 42.63 | 99.17 | 45.81 | 609.45 | 0.00 | 0.00 | 0.00 |
November | 56.74 | 20.61 | 36.12 | 5.05 | 1020.88 | 0.00 | 0.00 | 0.00 |
December | 5.09 | 0.54 | 4.56 | 0.00 | 1136.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.24 | 174.61 | 230.63 | 366.66 | 559.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.09 | 0.54 | 4.56 | 0.00 | 110.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 870.01 | 423.08 | 499.06 | 931.95 | 1136.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.42 | 3.47 | 15.95 | 0.00 | 1032.44 | 0.00 | 0.00 | 0.00 |
February | 114.63 | 39.86 | 74.77 | 21.14 | 901.82 | 0.00 | 0.00 | 0.00 |
March | 344.06 | 147.91 | 196.15 | 182.71 | 679.29 | 0.00 | 0.00 | 0.00 |
April | 816.43 | 423.08 | 393.35 | 743.95 | 410.48 | 0.00 | 0.00 | 0.00 |
May | 793.84 | 361.52 | 432.33 | 783.76 | 198.38 | 0.00 | 0.00 | 0.00 |
June | 870.01 | 370.95 | 499.06 | 931.95 | 110.03 | 0.00 | 0.00 | 0.00 |
July | 727.95 | 275.37 | 452.58 | 782.11 | 120.99 | 0.00 | 0.00 | 0.00 |
August | 598.30 | 253.35 | 344.95 | 603.94 | 184.75 | 0.00 | 0.00 | 0.00 |
September | 362.09 | 151.63 | 210.46 | 282.04 | 326.74 | 0.00 | 0.00 | 0.00 |
October | 141.80 | 42.63 | 99.17 | 45.81 | 609.45 | 0.00 | 0.00 | 0.00 |
November | 56.74 | 20.61 | 36.12 | 5.05 | 1020.88 | 0.00 | 0.00 | 0.00 |
December | 5.09 | 0.54 | 4.56 | 0.00 | 1136.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.24 | 174.61 | 230.63 | 366.66 | 559.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.09 | 0.54 | 4.56 | 0.00 | 110.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 870.01 | 423.08 | 499.06 | 931.95 | 1136.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.42 | 3.47 | 15.95 | 0.00 | 1032.43 | 0.00 | 0.00 | 0.00 |
February | 114.63 | 39.86 | 74.77 | 21.14 | 901.81 | 0.00 | 0.00 | 0.00 |
March | 344.06 | 147.91 | 196.15 | 182.71 | 679.28 | 0.00 | 0.00 | 0.00 |
April | 816.41 | 423.07 | 393.34 | 743.94 | 410.48 | 0.00 | 0.00 | 0.00 |
May | 793.83 | 361.51 | 432.32 | 783.75 | 198.38 | 0.00 | 0.00 | 0.00 |
June | 870.00 | 370.95 | 499.05 | 931.94 | 110.03 | 0.00 | 0.00 | 0.00 |
July | 727.94 | 275.36 | 452.58 | 782.09 | 120.99 | 0.00 | 0.00 | 0.00 |
August | 598.28 | 253.35 | 344.94 | 603.92 | 184.74 | 0.00 | 0.00 | 0.00 |
September | 362.08 | 151.62 | 210.46 | 282.04 | 326.73 | 0.00 | 0.00 | 0.00 |
October | 141.80 | 42.63 | 99.17 | 45.81 | 609.44 | 0.00 | 0.00 | 0.00 |
November | 56.74 | 20.61 | 36.12 | 5.05 | 1020.86 | 0.00 | 0.00 | 0.00 |
December | 5.09 | 0.54 | 4.56 | 0.00 | 1136.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.23 | 174.61 | 230.63 | 366.65 | 559.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.09 | 0.54 | 4.56 | 0.00 | 110.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 870.00 | 423.07 | 499.05 | 931.94 | 1136.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.06 | 0.00 | 63.06 | 0.00 | 4459.15 | 0.00 | 0.00 | 0.00 |
February | 278.75 | 0.00 | 278.75 | 0.00 | 4002.89 | 0.00 | 0.00 | 0.00 |
March | 745.53 | 0.00 | 745.53 | 61.73 | 2973.31 | 0.00 | 0.00 | 0.00 |
April | 1348.88 | 29.70 | 1319.18 | 540.47 | 1580.62 | 0.00 | 0.00 | 0.00 |
May | 2067.38 | 328.69 | 1738.69 | 1572.67 | 709.06 | 0.00 | 0.00 | 0.00 |
June | 2697.35 | 599.86 | 2097.49 | 2600.45 | 330.20 | 0.00 | 0.00 | 0.00 |
July | 2263.85 | 367.97 | 1895.88 | 2226.96 | 405.01 | 0.00 | 0.00 | 0.00 |
August | 1445.56 | 80.79 | 1364.77 | 1160.08 | 673.06 | 0.00 | 0.00 | 0.00 |
September | 806.46 | 0.81 | 805.65 | 295.62 | 1380.33 | 0.00 | 0.00 | 0.00 |
October | 392.42 | 0.00 | 392.42 | 25.72 | 2557.09 | 0.00 | 0.00 | 0.00 |
November | 121.78 | 0.00 | 121.78 | 0.00 | 4372.89 | 0.00 | 0.00 | 0.00 |
December | 19.13 | 0.00 | 19.13 | 0.00 | 4699.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1024.50 | 117.84 | 906.66 | 711.12 | 2336.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.13 | 0.00 | 19.13 | 0.00 | 330.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2697.35 | 599.86 | 2097.49 | 2600.45 | 4699.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.74 | 34.85 | 75.89 | 9.92 | 2881.42 | 0.00 | 0.00 | 0.00 |
February | 611.86 | 291.96 | 319.90 | 319.61 | 2416.90 | 0.00 | 0.00 | 0.00 |
March | 1745.26 | 883.82 | 861.44 | 1443.37 | 1792.18 | 0.00 | 0.00 | 0.00 |
April | 2398.94 | 1213.61 | 1185.33 | 2171.85 | 976.26 | 0.00 | 0.00 | 0.00 |
May | 3484.97 | 1961.86 | 1523.11 | 3731.86 | 507.62 | 0.00 | 0.00 | 0.00 |
June | 3206.25 | 1493.70 | 1712.55 | 3558.77 | 247.84 | 0.00 | 0.00 | 0.00 |
July | 3045.52 | 1474.81 | 1570.70 | 3461.34 | 287.17 | 0.00 | 0.00 | 0.00 |
August | 2412.25 | 1173.13 | 1239.12 | 2624.39 | 447.59 | 0.00 | 0.00 | 0.00 |
September | 1492.27 | 653.23 | 839.04 | 1360.11 | 856.61 | 0.00 | 0.00 | 0.00 |
October | 788.23 | 316.28 | 471.95 | 551.75 | 1551.45 | 0.00 | 0.00 | 0.00 |
November | 167.67 | 58.59 | 109.08 | 14.01 | 2802.73 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 5.73 | 18.22 | 0.00 | 3109.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1630.20 | 800.31 | 829.89 | 1612.58 | 1485.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 5.73 | 18.22 | 0.00 | 247.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3484.97 | 1961.86 | 1712.55 | 3731.86 | 3109.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 756.51 | 498.41 | 258.09 | 437.39 | 4008.13 | 0.00 | 0.00 | 0.00 |
February | 2603.17 | 1810.77 | 792.40 | 2168.10 | 3256.33 | 0.00 | 0.00 | 0.00 |
March | 4470.18 | 3029.94 | 1440.24 | 4275.19 | 2532.05 | 0.00 | 0.00 | 0.00 |
April | 5453.49 | 3392.62 | 2060.87 | 5809.17 | 1662.25 | 0.00 | 0.00 | 0.00 |
May | 4496.87 | 2330.08 | 2166.79 | 4942.44 | 892.29 | 0.00 | 0.00 | 0.00 |
June | 4105.81 | 1682.87 | 2422.94 | 4650.04 | 473.04 | 0.00 | 0.00 | 0.00 |
July | 3955.83 | 1722.77 | 2233.06 | 4586.73 | 507.86 | 0.00 | 0.00 | 0.00 |
August | 4096.66 | 2257.73 | 1838.93 | 4673.69 | 752.97 | 0.00 | 0.00 | 0.00 |
September | 3310.84 | 1993.96 | 1316.88 | 3419.85 | 1336.43 | 0.00 | 0.00 | 0.00 |
October | 2383.82 | 1512.47 | 871.35 | 2121.10 | 2175.83 | 0.00 | 0.00 | 0.00 |
November | 1278.12 | 892.46 | 385.66 | 836.84 | 3754.30 | 0.00 | 0.00 | 0.00 |
December | 226.88 | 159.92 | 66.96 | 40.25 | 4463.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3094.04 | 1770.98 | 1323.06 | 3165.93 | 2145.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.88 | 159.92 | 66.96 | 40.25 | 473.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5453.49 | 3392.62 | 2422.94 | 5809.17 | 4463.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.25 | 10.40 | 47.86 | 0.00 | 2959.12 | 0.00 | 0.00 | 0.00 |
February | 343.89 | 119.58 | 224.31 | 70.31 | 2531.57 | 0.00 | 0.00 | 0.00 |
March | 1032.18 | 443.72 | 588.46 | 579.84 | 1849.12 | 0.00 | 0.00 | 0.00 |
April | 2449.26 | 1269.22 | 1180.03 | 2295.43 | 1082.01 | 0.00 | 0.00 | 0.00 |
May | 2381.51 | 1084.55 | 1296.96 | 2376.89 | 557.49 | 0.00 | 0.00 | 0.00 |
June | 2610.02 | 1112.85 | 1497.17 | 2823.33 | 303.68 | 0.00 | 0.00 | 0.00 |
July | 2183.83 | 826.09 | 1357.74 | 2384.71 | 329.28 | 0.00 | 0.00 | 0.00 |
August | 1794.87 | 760.04 | 1034.83 | 1860.41 | 488.88 | 0.00 | 0.00 | 0.00 |
September | 1086.25 | 454.88 | 631.37 | 878.29 | 891.10 | 0.00 | 0.00 | 0.00 |
October | 425.41 | 127.89 | 297.52 | 155.59 | 1635.89 | 0.00 | 0.00 | 0.00 |
November | 170.21 | 61.84 | 108.37 | 18.46 | 2824.71 | 0.00 | 0.00 | 0.00 |
December | 15.28 | 1.61 | 13.67 | 0.00 | 3152.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1215.70 | 523.82 | 691.88 | 1124.70 | 1545.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.28 | 1.61 | 13.67 | 0.00 | 303.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2610.02 | 1269.22 | 1497.17 | 2823.33 | 3152.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.06 | 0.00 | 63.06 | 0.00 | 4360.88 | 0.00 | 0.00 | 0.00 |
February | 278.75 | 0.00 | 278.75 | 0.00 | 3885.36 | 0.00 | 0.00 | 0.00 |
March | 745.53 | 0.00 | 745.53 | 73.04 | 2845.38 | 0.00 | 0.00 | 0.00 |
April | 1348.88 | 29.70 | 1319.18 | 593.27 | 1470.33 | 0.00 | 0.00 | 0.00 |
May | 2067.38 | 328.69 | 1738.69 | 1628.48 | 666.73 | 0.00 | 0.00 | 0.00 |
June | 2697.35 | 599.86 | 2097.49 | 2608.00 | 319.15 | 0.00 | 0.00 | 0.00 |
July | 2263.85 | 367.97 | 1895.88 | 2233.53 | 393.72 | 0.00 | 0.00 | 0.00 |
August | 1445.56 | 80.79 | 1364.77 | 1185.12 | 639.58 | 0.00 | 0.00 | 0.00 |
September | 806.46 | 0.81 | 805.65 | 340.97 | 1248.97 | 0.00 | 0.00 | 0.00 |
October | 392.42 | 0.00 | 392.42 | 39.49 | 2392.69 | 0.00 | 0.00 | 0.00 |
November | 121.78 | 0.00 | 121.78 | 0.00 | 4251.61 | 0.00 | 0.00 | 0.00 |
December | 19.13 | 0.00 | 19.13 | 0.00 | 4595.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1024.50 | 117.84 | 906.66 | 729.36 | 2247.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.13 | 0.00 | 19.13 | 0.00 | 319.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2697.35 | 599.86 | 2097.49 | 2608.00 | 4595.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.74 | 34.85 | 75.89 | 10.28 | 2821.39 | 0.00 | 0.00 | 0.00 |
February | 611.86 | 291.96 | 319.90 | 326.97 | 2345.89 | 0.00 | 0.00 | 0.00 |
March | 1745.26 | 883.82 | 861.44 | 1467.12 | 1712.91 | 0.00 | 0.00 | 0.00 |
April | 2398.94 | 1213.61 | 1185.33 | 2205.49 | 918.59 | 0.00 | 0.00 | 0.00 |
May | 3484.97 | 1961.86 | 1523.11 | 3746.51 | 487.22 | 0.00 | 0.00 | 0.00 |
June | 3206.25 | 1493.70 | 1712.55 | 3556.60 | 243.05 | 0.00 | 0.00 | 0.00 |
July | 3045.52 | 1474.81 | 1570.70 | 3457.52 | 283.11 | 0.00 | 0.00 | 0.00 |
August | 2412.25 | 1173.13 | 1239.12 | 2630.07 | 434.26 | 0.00 | 0.00 | 0.00 |
September | 1492.27 | 653.23 | 839.04 | 1388.06 | 795.95 | 0.00 | 0.00 | 0.00 |
October | 788.23 | 316.28 | 471.95 | 571.36 | 1455.33 | 0.00 | 0.00 | 0.00 |
November | 167.67 | 58.59 | 109.08 | 14.87 | 2727.06 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 5.73 | 18.22 | 0.00 | 3047.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1630.20 | 800.31 | 829.89 | 1623.22 | 1434.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 5.73 | 18.22 | 0.00 | 243.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3484.97 | 1961.86 | 1712.55 | 3746.51 | 3047.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 756.51 | 498.41 | 258.09 | 444.74 | 3917.41 | 0.00 | 0.00 | 0.00 |
February | 2603.17 | 1810.77 | 792.40 | 2199.43 | 3142.72 | 0.00 | 0.00 | 0.00 |
March | 4470.18 | 3029.94 | 1440.24 | 4320.91 | 2406.91 | 0.00 | 0.00 | 0.00 |
April | 5453.49 | 3392.62 | 2060.87 | 5847.58 | 1564.79 | 0.00 | 0.00 | 0.00 |
May | 4496.87 | 2330.08 | 2166.79 | 4959.91 | 849.64 | 0.00 | 0.00 | 0.00 |
June | 4105.81 | 1682.87 | 2422.94 | 4649.91 | 461.69 | 0.00 | 0.00 | 0.00 |
July | 3955.83 | 1722.77 | 2233.06 | 4585.27 | 499.14 | 0.00 | 0.00 | 0.00 |
August | 4096.66 | 2257.73 | 1838.93 | 4680.80 | 728.49 | 0.00 | 0.00 | 0.00 |
September | 3310.84 | 1993.96 | 1316.88 | 3457.01 | 1244.98 | 0.00 | 0.00 | 0.00 |
October | 2383.82 | 1512.47 | 871.35 | 2166.84 | 2034.76 | 0.00 | 0.00 | 0.00 |
November | 1278.12 | 892.46 | 385.66 | 853.09 | 3637.40 | 0.00 | 0.00 | 0.00 |
December | 226.88 | 159.92 | 66.96 | 41.20 | 4366.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3094.04 | 1770.98 | 1323.06 | 3186.30 | 2066.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.88 | 159.92 | 66.96 | 41.20 | 461.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5453.49 | 3392.62 | 2422.94 | 5847.58 | 4366.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.25 | 10.40 | 47.86 | 0.00 | 2894.37 | 0.00 | 0.00 | 0.00 |
February | 343.89 | 119.58 | 224.31 | 72.62 | 2462.48 | 0.00 | 0.00 | 0.00 |
March | 1032.18 | 443.72 | 588.46 | 591.76 | 1773.69 | 0.00 | 0.00 | 0.00 |
April | 2449.26 | 1269.22 | 1180.03 | 2319.97 | 1020.11 | 0.00 | 0.00 | 0.00 |
May | 2381.51 | 1084.55 | 1296.96 | 2393.75 | 530.65 | 0.00 | 0.00 | 0.00 |
June | 2610.02 | 1112.85 | 1497.17 | 2824.80 | 296.63 | 0.00 | 0.00 | 0.00 |
July | 2183.83 | 826.09 | 1357.74 | 2385.53 | 323.04 | 0.00 | 0.00 | 0.00 |
August | 1794.87 | 760.04 | 1034.83 | 1868.77 | 471.72 | 0.00 | 0.00 | 0.00 |
September | 1086.25 | 454.88 | 631.37 | 898.43 | 832.46 | 0.00 | 0.00 | 0.00 |
October | 425.41 | 127.89 | 297.52 | 166.13 | 1546.38 | 0.00 | 0.00 | 0.00 |
November | 170.21 | 61.84 | 108.37 | 19.64 | 2750.49 | 0.00 | 0.00 | 0.00 |
December | 15.28 | 1.61 | 13.67 | 0.00 | 3089.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1215.70 | 523.82 | 691.88 | 1132.88 | 1494.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.28 | 1.61 | 13.67 | 0.00 | 296.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2610.02 | 1269.22 | 1497.17 | 2824.80 | 3089.22 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33779162.98 | 0.00 | 33779162.98 | 0.00 | 0.245164E+10 |
February | 0.134870E+09 | 0.00 | 0.134870E+09 | 0.00 | 0.201259E+10 |
March | 0.399368E+09 | 0.00 | 0.399368E+09 | 25025974.19 | 0.168962E+10 |
April | 0.699261E+09 | 15396779.91 | 0.683865E+09 | 0.251489E+09 | 0.901474E+09 |
May | 0.110745E+10 | 0.176070E+09 | 0.931381E+09 | 0.829504E+09 | 0.396022E+09 |
June | 0.139831E+10 | 0.310967E+09 | 0.108734E+10 | 0.134539E+10 | 0.176364E+09 |
July | 0.121269E+10 | 0.197112E+09 | 0.101558E+10 | 0.118918E+10 | 0.222279E+09 |
August | 0.774357E+09 | 43276541.74 | 0.731081E+09 | 0.609827E+09 | 0.377886E+09 |
September | 0.418069E+09 | 420964.79 | 0.417648E+09 | 0.140411E+09 | 0.771080E+09 |
October | 0.210209E+09 | 0.00 | 0.210209E+09 | 8768246.76 | 0.149080E+10 |
November | 63130848.20 | 0.00 | 63130848.20 | 0.00 | 0.238002E+10 |
December | 10246828.08 | 0.00 | 10246828.08 | 0.00 | 0.262339E+10 |
Annual Sum or Average | 0.646174E+10 | 0.743244E+09 | 0.571850E+10 | 0.439960E+10 | 0.154932E+11 |
Minimum of Months | 10246828.08 | 0.00 | 10246828.08 | 0.00 | 0.176364E+09 |
Maximum of Months | 0.139831E+10 | 0.310967E+09 | 0.108734E+10 | 0.134539E+10 | 0.262339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33778590.32 | 0.00 | 33778590.32 | 0.00 | 0.245164E+10 |
February | 0.134868E+09 | 0.00 | 0.134868E+09 | 0.00 | 0.201259E+10 |
March | 0.399362E+09 | 0.00 | 0.399362E+09 | 25023903.37 | 0.168963E+10 |
April | 0.699251E+09 | 15396441.43 | 0.683855E+09 | 0.251480E+09 | 0.901476E+09 |
May | 0.110743E+10 | 0.176066E+09 | 0.931367E+09 | 0.829483E+09 | 0.396021E+09 |
June | 0.139828E+10 | 0.310961E+09 | 0.108732E+10 | 0.134537E+10 | 0.176364E+09 |
July | 0.121267E+10 | 0.197108E+09 | 0.101557E+10 | 0.118916E+10 | 0.222279E+09 |
August | 0.774345E+09 | 43275590.36 | 0.731070E+09 | 0.609813E+09 | 0.377886E+09 |
September | 0.418063E+09 | 420955.54 | 0.417642E+09 | 0.140406E+09 | 0.771081E+09 |
October | 0.210205E+09 | 0.00 | 0.210205E+09 | 8767527.44 | 0.149081E+10 |
November | 63129777.96 | 0.00 | 63129777.96 | 0.00 | 0.238002E+10 |
December | 10246646.75 | 0.00 | 10246646.75 | 0.00 | 0.262339E+10 |
Annual Sum or Average | 0.646164E+10 | 0.743228E+09 | 0.571841E+10 | 0.439950E+10 | 0.154932E+11 |
Minimum of Months | 10246646.75 | 0.00 | 10246646.75 | 0.00 | 0.176364E+09 |
Maximum of Months | 0.139828E+10 | 0.310961E+09 | 0.108732E+10 | 0.134537E+10 | 0.262339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33778781.21 | 0.00 | 33778781.21 | 0.00 | 0.245164E+10 |
February | 0.134868E+09 | 0.00 | 0.134868E+09 | 0.00 | 0.201259E+10 |
March | 0.399364E+09 | 0.00 | 0.399364E+09 | 25024593.64 | 0.168962E+10 |
April | 0.699255E+09 | 15396554.26 | 0.683858E+09 | 0.251483E+09 | 0.901476E+09 |
May | 0.110744E+10 | 0.176067E+09 | 0.931372E+09 | 0.829490E+09 | 0.396021E+09 |
June | 0.139829E+10 | 0.310963E+09 | 0.108733E+10 | 0.134538E+10 | 0.176364E+09 |
July | 0.121268E+10 | 0.197109E+09 | 0.101557E+10 | 0.118917E+10 | 0.222279E+09 |
August | 0.774349E+09 | 43275907.49 | 0.731073E+09 | 0.609818E+09 | 0.377886E+09 |
September | 0.418065E+09 | 420958.62 | 0.417644E+09 | 0.140408E+09 | 0.771081E+09 |
October | 0.210206E+09 | 0.00 | 0.210206E+09 | 8767767.21 | 0.149081E+10 |
November | 63130134.71 | 0.00 | 63130134.71 | 0.00 | 0.238002E+10 |
December | 10246707.19 | 0.00 | 10246707.19 | 0.00 | 0.262339E+10 |
Annual Sum or Average | 0.646167E+10 | 0.743233E+09 | 0.571844E+10 | 0.439953E+10 | 0.154932E+11 |
Minimum of Months | 10246707.19 | 0.00 | 10246707.19 | 0.00 | 0.176364E+09 |
Maximum of Months | 0.139829E+10 | 0.310963E+09 | 0.108733E+10 | 0.134538E+10 | 0.262339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33778590.32 | 0.00 | 33778590.32 | 0.00 | 0.245164E+10 |
February | 0.134868E+09 | 0.00 | 0.134868E+09 | 0.00 | 0.201259E+10 |
March | 0.399362E+09 | 0.00 | 0.399362E+09 | 25023903.37 | 0.168963E+10 |
April | 0.699251E+09 | 15396441.43 | 0.683855E+09 | 0.251480E+09 | 0.901476E+09 |
May | 0.110743E+10 | 0.176066E+09 | 0.931367E+09 | 0.829483E+09 | 0.396021E+09 |
June | 0.139828E+10 | 0.310961E+09 | 0.108732E+10 | 0.134537E+10 | 0.176364E+09 |
July | 0.121267E+10 | 0.197108E+09 | 0.101557E+10 | 0.118916E+10 | 0.222279E+09 |
August | 0.774345E+09 | 43275590.36 | 0.731070E+09 | 0.609813E+09 | 0.377886E+09 |
September | 0.418063E+09 | 420955.54 | 0.417642E+09 | 0.140406E+09 | 0.771081E+09 |
October | 0.210205E+09 | 0.00 | 0.210205E+09 | 8767527.44 | 0.149081E+10 |
November | 63129777.96 | 0.00 | 63129777.96 | 0.00 | 0.238002E+10 |
December | 10246646.75 | 0.00 | 10246646.75 | 0.00 | 0.262339E+10 |
Annual Sum or Average | 0.646164E+10 | 0.743228E+09 | 0.571841E+10 | 0.439950E+10 | 0.154932E+11 |
Minimum of Months | 10246646.75 | 0.00 | 10246646.75 | 0.00 | 0.176364E+09 |
Maximum of Months | 0.139828E+10 | 0.310961E+09 | 0.108732E+10 | 0.134537E+10 | 0.262339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33777324.33 | 0.00 | 33777324.33 | 0.00 | 0.245154E+10 |
February | 0.134863E+09 | 0.00 | 0.134863E+09 | 0.00 | 0.201251E+10 |
March | 0.399346E+09 | 0.00 | 0.399346E+09 | 25023239.92 | 0.168956E+10 |
April | 0.699225E+09 | 15395877.30 | 0.683829E+09 | 0.251472E+09 | 0.901440E+09 |
May | 0.110739E+10 | 0.176060E+09 | 0.931332E+09 | 0.829453E+09 | 0.396005E+09 |
June | 0.139823E+10 | 0.310949E+09 | 0.108728E+10 | 0.134532E+10 | 0.176356E+09 |
July | 0.121263E+10 | 0.197101E+09 | 0.101553E+10 | 0.118912E+10 | 0.222270E+09 |
August | 0.774316E+09 | 43274004.72 | 0.731042E+09 | 0.609791E+09 | 0.377871E+09 |
September | 0.418047E+09 | 420940.11 | 0.417626E+09 | 0.140401E+09 | 0.771050E+09 |
October | 0.210197E+09 | 0.00 | 0.210197E+09 | 8767293.95 | 0.149075E+10 |
November | 63127411.92 | 0.00 | 63127411.92 | 0.00 | 0.237992E+10 |
December | 10246263.99 | 0.00 | 10246263.99 | 0.00 | 0.262328E+10 |
Annual Sum or Average | 0.646140E+10 | 0.743200E+09 | 0.571819E+10 | 0.439934E+10 | 0.154925E+11 |
Minimum of Months | 10246263.99 | 0.00 | 10246263.99 | 0.00 | 0.176356E+09 |
Maximum of Months | 0.139823E+10 | 0.310949E+09 | 0.108728E+10 | 0.134532E+10 | 0.262328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98871890.73 | 31116260.30 | 67755630.43 | 8849744.06 | 0.262608E+10 |
February | 0.493409E+09 | 0.235440E+09 | 0.257969E+09 | 0.252190E+09 | 0.200801E+10 |
March | 0.155818E+10 | 0.789081E+09 | 0.769099E+09 | 0.127573E+10 | 0.166219E+10 |
April | 0.207270E+10 | 0.104857E+10 | 0.102414E+10 | 0.186405E+10 | 0.891439E+09 |
May | 0.311141E+10 | 0.175156E+10 | 0.135985E+10 | 0.334164E+10 | 0.467737E+09 |
June | 0.277022E+10 | 0.129057E+10 | 0.147965E+10 | 0.308638E+10 | 0.215759E+09 |
July | 0.271907E+10 | 0.131673E+10 | 0.140234E+10 | 0.310665E+10 | 0.251982E+09 |
August | 0.215368E+10 | 0.104738E+10 | 0.110630E+10 | 0.235116E+10 | 0.398969E+09 |
September | 0.128934E+10 | 0.564396E+09 | 0.724939E+09 | 0.116443E+10 | 0.779289E+09 |
October | 0.703740E+09 | 0.282382E+09 | 0.421358E+09 | 0.479571E+09 | 0.147618E+10 |
November | 0.144866E+09 | 50620862.64 | 94244678.23 | 11286987.70 | 0.252018E+10 |
December | 21386826.70 | 5119625.73 | 16267200.97 | 0.00 | 0.286068E+10 |
Annual Sum or Average | 0.171369E+11 | 0.841297E+10 | 0.872391E+10 | 0.169419E+11 | 0.161585E+11 |
Minimum of Months | 21386826.70 | 5119625.73 | 16267200.97 | 0.00 | 0.215759E+09 |
Maximum of Months | 0.311141E+10 | 0.175156E+10 | 0.147965E+10 | 0.334164E+10 | 0.286068E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98871890.73 | 31116260.30 | 67755630.43 | 8849744.06 | 0.262608E+10 |
February | 0.493409E+09 | 0.235440E+09 | 0.257969E+09 | 0.252190E+09 | 0.200801E+10 |
March | 0.155818E+10 | 0.789081E+09 | 0.769099E+09 | 0.127573E+10 | 0.166219E+10 |
April | 0.207270E+10 | 0.104857E+10 | 0.102414E+10 | 0.186405E+10 | 0.891439E+09 |
May | 0.311141E+10 | 0.175156E+10 | 0.135985E+10 | 0.334164E+10 | 0.467737E+09 |
June | 0.277022E+10 | 0.129057E+10 | 0.147965E+10 | 0.308638E+10 | 0.215759E+09 |
July | 0.271907E+10 | 0.131673E+10 | 0.140234E+10 | 0.310665E+10 | 0.251982E+09 |
August | 0.215368E+10 | 0.104738E+10 | 0.110630E+10 | 0.235116E+10 | 0.398969E+09 |
September | 0.128934E+10 | 0.564396E+09 | 0.724939E+09 | 0.116443E+10 | 0.779289E+09 |
October | 0.703740E+09 | 0.282382E+09 | 0.421358E+09 | 0.479571E+09 | 0.147618E+10 |
November | 0.144866E+09 | 50620862.64 | 94244678.23 | 11286987.70 | 0.252018E+10 |
December | 21386826.70 | 5119625.73 | 16267200.97 | 0.00 | 0.286068E+10 |
Annual Sum or Average | 0.171369E+11 | 0.841297E+10 | 0.872391E+10 | 0.169419E+11 | 0.161585E+11 |
Minimum of Months | 21386826.70 | 5119625.73 | 16267200.97 | 0.00 | 0.215759E+09 |
Maximum of Months | 0.311141E+10 | 0.175156E+10 | 0.147965E+10 | 0.334164E+10 | 0.286068E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98870084.13 | 31115691.74 | 67754392.39 | 8849582.35 | 0.262603E+10 |
February | 0.493400E+09 | 0.235436E+09 | 0.257965E+09 | 0.252185E+09 | 0.200797E+10 |
March | 0.155815E+10 | 0.789067E+09 | 0.769085E+09 | 0.127571E+10 | 0.166216E+10 |
April | 0.207267E+10 | 0.104855E+10 | 0.102412E+10 | 0.186401E+10 | 0.891423E+09 |
May | 0.311135E+10 | 0.175153E+10 | 0.135982E+10 | 0.334158E+10 | 0.467728E+09 |
June | 0.277017E+10 | 0.129055E+10 | 0.147963E+10 | 0.308632E+10 | 0.215755E+09 |
July | 0.271902E+10 | 0.131670E+10 | 0.140231E+10 | 0.310659E+10 | 0.251977E+09 |
August | 0.215364E+10 | 0.104736E+10 | 0.110628E+10 | 0.235112E+10 | 0.398962E+09 |
September | 0.128931E+10 | 0.564386E+09 | 0.724926E+09 | 0.116441E+10 | 0.779274E+09 |
October | 0.703727E+09 | 0.282377E+09 | 0.421350E+09 | 0.479563E+09 | 0.147615E+10 |
November | 0.144863E+09 | 50619937.68 | 94242956.18 | 11286781.46 | 0.252013E+10 |
December | 21386435.91 | 5119532.19 | 16266903.73 | 0.00 | 0.286063E+10 |
Annual Sum or Average | 0.171366E+11 | 0.841281E+10 | 0.872375E+10 | 0.169416E+11 | 0.161582E+11 |
Minimum of Months | 21386435.91 | 5119532.19 | 16266903.73 | 0.00 | 0.215755E+09 |
Maximum of Months | 0.311135E+10 | 0.175153E+10 | 0.147963E+10 | 0.334158E+10 | 0.286063E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405237E+09 | 0.266985E+09 | 0.138252E+09 | 0.233194E+09 | 0.217408E+10 |
February | 0.125949E+10 | 0.876107E+09 | 0.383387E+09 | 0.104424E+10 | 0.160488E+10 |
March | 0.239454E+10 | 0.162304E+10 | 0.771498E+09 | 0.229075E+10 | 0.138374E+10 |
April | 0.282704E+10 | 0.175870E+10 | 0.106834E+10 | 0.301778E+10 | 0.886731E+09 |
May | 0.240884E+10 | 0.124815E+10 | 0.116069E+10 | 0.265743E+10 | 0.486509E+09 |
June | 0.212842E+10 | 0.872381E+09 | 0.125604E+10 | 0.241623E+10 | 0.248034E+09 |
July | 0.211902E+10 | 0.922832E+09 | 0.119619E+10 | 0.246293E+10 | 0.271151E+09 |
August | 0.219446E+10 | 0.120940E+10 | 0.985065E+09 | 0.250795E+10 | 0.405503E+09 |
September | 0.171631E+10 | 0.103365E+10 | 0.682663E+09 | 0.177427E+10 | 0.706238E+09 |
October | 0.127694E+10 | 0.810181E+09 | 0.466757E+09 | 0.112885E+10 | 0.120626E+10 |
November | 0.662564E+09 | 0.462641E+09 | 0.199924E+09 | 0.427179E+09 | 0.200299E+10 |
December | 0.121531E+09 | 85662558.95 | 35868430.68 | 21115244.42 | 0.244829E+10 |
Annual Sum or Average | 0.195144E+11 | 0.111697E+11 | 0.834468E+10 | 0.199819E+11 | 0.138244E+11 |
Minimum of Months | 0.121531E+09 | 85662558.95 | 35868430.68 | 21115244.42 | 0.248034E+09 |
Maximum of Months | 0.282704E+10 | 0.175870E+10 | 0.125604E+10 | 0.301778E+10 | 0.244829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405234E+09 | 0.266983E+09 | 0.138251E+09 | 0.233191E+09 | 0.217408E+10 |
February | 0.125949E+10 | 0.876101E+09 | 0.383385E+09 | 0.104423E+10 | 0.160488E+10 |
March | 0.239452E+10 | 0.162303E+10 | 0.771494E+09 | 0.229073E+10 | 0.138374E+10 |
April | 0.282702E+10 | 0.175868E+10 | 0.106833E+10 | 0.301776E+10 | 0.886731E+09 |
May | 0.240883E+10 | 0.124814E+10 | 0.116069E+10 | 0.265741E+10 | 0.486509E+09 |
June | 0.212841E+10 | 0.872374E+09 | 0.125603E+10 | 0.241621E+10 | 0.248034E+09 |
July | 0.211901E+10 | 0.922825E+09 | 0.119618E+10 | 0.246291E+10 | 0.271152E+09 |
August | 0.219445E+10 | 0.120939E+10 | 0.985060E+09 | 0.250793E+10 | 0.405502E+09 |
September | 0.171630E+10 | 0.103364E+10 | 0.682659E+09 | 0.177426E+10 | 0.706238E+09 |
October | 0.127693E+10 | 0.810175E+09 | 0.466754E+09 | 0.112883E+10 | 0.120626E+10 |
November | 0.662560E+09 | 0.462638E+09 | 0.199922E+09 | 0.427174E+09 | 0.200298E+10 |
December | 0.121530E+09 | 85661931.21 | 35868182.48 | 21114797.94 | 0.244829E+10 |
Annual Sum or Average | 0.195143E+11 | 0.111696E+11 | 0.834463E+10 | 0.199817E+11 | 0.138244E+11 |
Minimum of Months | 0.121530E+09 | 85661931.21 | 35868182.48 | 21114797.94 | 0.248034E+09 |
Maximum of Months | 0.282702E+10 | 0.175868E+10 | 0.125603E+10 | 0.301776E+10 | 0.244829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405237E+09 | 0.266985E+09 | 0.138252E+09 | 0.233194E+09 | 0.217408E+10 |
February | 0.125949E+10 | 0.876107E+09 | 0.383387E+09 | 0.104424E+10 | 0.160488E+10 |
March | 0.239454E+10 | 0.162304E+10 | 0.771498E+09 | 0.229075E+10 | 0.138374E+10 |
April | 0.282704E+10 | 0.175870E+10 | 0.106834E+10 | 0.301778E+10 | 0.886731E+09 |
May | 0.240884E+10 | 0.124815E+10 | 0.116069E+10 | 0.265743E+10 | 0.486509E+09 |
June | 0.212842E+10 | 0.872381E+09 | 0.125604E+10 | 0.241623E+10 | 0.248034E+09 |
July | 0.211902E+10 | 0.922832E+09 | 0.119619E+10 | 0.246293E+10 | 0.271151E+09 |
August | 0.219446E+10 | 0.120940E+10 | 0.985065E+09 | 0.250795E+10 | 0.405503E+09 |
September | 0.171631E+10 | 0.103365E+10 | 0.682663E+09 | 0.177427E+10 | 0.706238E+09 |
October | 0.127694E+10 | 0.810181E+09 | 0.466757E+09 | 0.112885E+10 | 0.120626E+10 |
November | 0.662564E+09 | 0.462641E+09 | 0.199924E+09 | 0.427179E+09 | 0.200299E+10 |
December | 0.121531E+09 | 85662558.95 | 35868430.68 | 21115244.42 | 0.244829E+10 |
Annual Sum or Average | 0.195144E+11 | 0.111697E+11 | 0.834468E+10 | 0.199819E+11 | 0.138244E+11 |
Minimum of Months | 0.121531E+09 | 85662558.95 | 35868430.68 | 21115244.42 | 0.248034E+09 |
Maximum of Months | 0.282704E+10 | 0.175870E+10 | 0.125604E+10 | 0.301778E+10 | 0.244829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405234E+09 | 0.266983E+09 | 0.138251E+09 | 0.233191E+09 | 0.217408E+10 |
February | 0.125949E+10 | 0.876101E+09 | 0.383385E+09 | 0.104423E+10 | 0.160488E+10 |
March | 0.239452E+10 | 0.162303E+10 | 0.771494E+09 | 0.229073E+10 | 0.138374E+10 |
April | 0.282702E+10 | 0.175868E+10 | 0.106833E+10 | 0.301776E+10 | 0.886731E+09 |
May | 0.240883E+10 | 0.124814E+10 | 0.116069E+10 | 0.265741E+10 | 0.486509E+09 |
June | 0.212841E+10 | 0.872374E+09 | 0.125603E+10 | 0.241621E+10 | 0.248034E+09 |
July | 0.211901E+10 | 0.922825E+09 | 0.119618E+10 | 0.246291E+10 | 0.271152E+09 |
August | 0.219445E+10 | 0.120939E+10 | 0.985060E+09 | 0.250793E+10 | 0.405502E+09 |
September | 0.171630E+10 | 0.103364E+10 | 0.682659E+09 | 0.177426E+10 | 0.706238E+09 |
October | 0.127693E+10 | 0.810175E+09 | 0.466754E+09 | 0.112883E+10 | 0.120626E+10 |
November | 0.662560E+09 | 0.462638E+09 | 0.199922E+09 | 0.427174E+09 | 0.200298E+10 |
December | 0.121530E+09 | 85661931.21 | 35868182.48 | 21114797.94 | 0.244829E+10 |
Annual Sum or Average | 0.195143E+11 | 0.111696E+11 | 0.834463E+10 | 0.199817E+11 | 0.138244E+11 |
Minimum of Months | 0.121530E+09 | 85661931.21 | 35868182.48 | 21114797.94 | 0.248034E+09 |
Maximum of Months | 0.282702E+10 | 0.175868E+10 | 0.125603E+10 | 0.301776E+10 | 0.244829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405219E+09 | 0.266973E+09 | 0.138246E+09 | 0.233183E+09 | 0.217399E+10 |
February | 0.125944E+10 | 0.876068E+09 | 0.383371E+09 | 0.104419E+10 | 0.160481E+10 |
March | 0.239444E+10 | 0.162297E+10 | 0.771465E+09 | 0.229065E+10 | 0.138369E+10 |
April | 0.282691E+10 | 0.175862E+10 | 0.106829E+10 | 0.301765E+10 | 0.886696E+09 |
May | 0.240874E+10 | 0.124810E+10 | 0.116064E+10 | 0.265731E+10 | 0.486490E+09 |
June | 0.212833E+10 | 0.872342E+09 | 0.125598E+10 | 0.241612E+10 | 0.248024E+09 |
July | 0.211893E+10 | 0.922791E+09 | 0.119614E+10 | 0.246282E+10 | 0.271141E+09 |
August | 0.219437E+10 | 0.120934E+10 | 0.985023E+09 | 0.250784E+10 | 0.405486E+09 |
September | 0.171623E+10 | 0.103360E+10 | 0.682633E+09 | 0.177419E+10 | 0.706210E+09 |
October | 0.127688E+10 | 0.810146E+09 | 0.466737E+09 | 0.112879E+10 | 0.120622E+10 |
November | 0.662535E+09 | 0.462621E+09 | 0.199915E+09 | 0.427159E+09 | 0.200290E+10 |
December | 0.121526E+09 | 85658792.52 | 35866860.93 | 21114170.15 | 0.244819E+10 |
Annual Sum or Average | 0.195135E+11 | 0.111692E+11 | 0.834432E+10 | 0.199810E+11 | 0.138239E+11 |
Minimum of Months | 0.121526E+09 | 85658792.52 | 35866860.93 | 21114170.15 | 0.248024E+09 |
Maximum of Months | 0.282691E+10 | 0.175862E+10 | 0.125598E+10 | 0.301765E+10 | 0.244819E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52009464.82 | 9281157.37 | 42728307.45 | 0.00 | 0.276530E+10 |
February | 0.277312E+09 | 96429882.74 | 0.180882E+09 | 51132112.83 | 0.218169E+10 |
March | 0.921537E+09 | 0.396158E+09 | 0.525379E+09 | 0.489371E+09 | 0.181941E+10 |
April | 0.211618E+10 | 0.109662E+10 | 0.101956E+10 | 0.192833E+10 | 0.106398E+10 |
May | 0.212623E+10 | 0.968294E+09 | 0.115794E+10 | 0.209923E+10 | 0.531344E+09 |
June | 0.225508E+10 | 0.961508E+09 | 0.129357E+10 | 0.241562E+10 | 0.285193E+09 |
July | 0.194974E+10 | 0.737539E+09 | 0.121220E+10 | 0.209479E+10 | 0.324062E+09 |
August | 0.160247E+10 | 0.678572E+09 | 0.923902E+09 | 0.161758E+10 | 0.494825E+09 |
September | 0.938528E+09 | 0.393019E+09 | 0.545509E+09 | 0.731049E+09 | 0.846900E+09 |
October | 0.379810E+09 | 0.114185E+09 | 0.265625E+09 | 0.122689E+09 | 0.163234E+10 |
November | 0.147061E+09 | 53432196.16 | 93628368.67 | 13097062.19 | 0.264612E+10 |
December | 13642686.64 | 1434095.19 | 12208591.45 | 0.00 | 0.304311E+10 |
Annual Sum or Average | 0.127796E+11 | 0.550647E+10 | 0.727313E+10 | 0.115629E+11 | 0.176343E+11 |
Minimum of Months | 13642686.64 | 1434095.19 | 12208591.45 | 0.00 | 0.285193E+09 |
Maximum of Months | 0.225508E+10 | 0.109662E+10 | 0.129357E+10 | 0.241562E+10 | 0.304311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52009464.82 | 9281157.37 | 42728307.45 | 0.00 | 0.276530E+10 |
February | 0.277312E+09 | 96429882.74 | 0.180882E+09 | 51132112.83 | 0.218169E+10 |
March | 0.921537E+09 | 0.396158E+09 | 0.525379E+09 | 0.489371E+09 | 0.181941E+10 |
April | 0.211618E+10 | 0.109662E+10 | 0.101956E+10 | 0.192833E+10 | 0.106398E+10 |
May | 0.212623E+10 | 0.968294E+09 | 0.115794E+10 | 0.209923E+10 | 0.531344E+09 |
June | 0.225508E+10 | 0.961508E+09 | 0.129357E+10 | 0.241562E+10 | 0.285193E+09 |
July | 0.194974E+10 | 0.737539E+09 | 0.121220E+10 | 0.209479E+10 | 0.324062E+09 |
August | 0.160247E+10 | 0.678572E+09 | 0.923902E+09 | 0.161758E+10 | 0.494825E+09 |
September | 0.938528E+09 | 0.393019E+09 | 0.545509E+09 | 0.731049E+09 | 0.846900E+09 |
October | 0.379810E+09 | 0.114185E+09 | 0.265625E+09 | 0.122689E+09 | 0.163234E+10 |
November | 0.147061E+09 | 53432196.16 | 93628368.67 | 13097062.19 | 0.264612E+10 |
December | 13642686.64 | 1434095.19 | 12208591.45 | 0.00 | 0.304311E+10 |
Annual Sum or Average | 0.127796E+11 | 0.550647E+10 | 0.727313E+10 | 0.115629E+11 | 0.176343E+11 |
Minimum of Months | 13642686.64 | 1434095.19 | 12208591.45 | 0.00 | 0.285193E+09 |
Maximum of Months | 0.225508E+10 | 0.109662E+10 | 0.129357E+10 | 0.241562E+10 | 0.304311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52008514.49 | 9280987.78 | 42727526.71 | 0.00 | 0.276525E+10 |
February | 0.277307E+09 | 96428120.75 | 0.180879E+09 | 51131178.53 | 0.218165E+10 |
March | 0.921520E+09 | 0.396151E+09 | 0.525369E+09 | 0.489362E+09 | 0.181938E+10 |
April | 0.211614E+10 | 0.109660E+10 | 0.101954E+10 | 0.192829E+10 | 0.106396E+10 |
May | 0.212620E+10 | 0.968276E+09 | 0.115792E+10 | 0.209919E+10 | 0.531335E+09 |
June | 0.225504E+10 | 0.961491E+09 | 0.129355E+10 | 0.241558E+10 | 0.285188E+09 |
July | 0.194971E+10 | 0.737525E+09 | 0.121218E+10 | 0.209476E+10 | 0.324056E+09 |
August | 0.160244E+10 | 0.678560E+09 | 0.923885E+09 | 0.161755E+10 | 0.494816E+09 |
September | 0.938511E+09 | 0.393012E+09 | 0.545499E+09 | 0.731035E+09 | 0.846884E+09 |
October | 0.379803E+09 | 0.114183E+09 | 0.265620E+09 | 0.122687E+09 | 0.163231E+10 |
November | 0.147058E+09 | 53431219.84 | 93626657.88 | 13096822.88 | 0.264607E+10 |
December | 13642437.36 | 1434068.99 | 12208368.37 | 0.00 | 0.304305E+10 |
Annual Sum or Average | 0.127794E+11 | 0.550637E+10 | 0.727300E+10 | 0.115627E+11 | 0.176340E+11 |
Minimum of Months | 13642437.36 | 1434068.99 | 12208368.37 | 0.00 | 0.285188E+09 |
Maximum of Months | 0.225504E+10 | 0.109660E+10 | 0.129355E+10 | 0.241558E+10 | 0.304305E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168896E+09 | 0.00 | 0.168896E+09 | 0.00 | 0.119434E+11 |
February | 0.674350E+09 | 0.00 | 0.674350E+09 | 0.00 | 0.968378E+10 |
March | 0.199684E+10 | 0.00 | 0.199684E+10 | 0.165347E+09 | 0.796371E+10 |
April | 0.349631E+10 | 76984390.17 | 0.341932E+10 | 0.140091E+10 | 0.409696E+10 |
May | 0.553726E+10 | 0.880355E+09 | 0.465691E+10 | 0.421224E+10 | 0.189916E+10 |
June | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.674037E+10 | 0.855883E+09 |
July | 0.606349E+10 | 0.985567E+09 | 0.507792E+10 | 0.596468E+10 | 0.108478E+10 |
August | 0.387179E+10 | 0.216384E+09 | 0.365541E+10 | 0.310715E+10 | 0.180273E+10 |
September | 0.209035E+10 | 2104837.37 | 0.208824E+10 | 0.766243E+09 | 0.357782E+10 |
October | 0.105104E+10 | 0.00 | 0.105104E+10 | 68880615.58 | 0.684890E+10 |
November | 0.315655E+09 | 0.00 | 0.315655E+09 | 0.00 | 0.113345E+11 |
December | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.125861E+11 |
Annual Sum or Average | 0.323088E+11 | 0.371624E+10 | 0.285925E+11 | 0.224258E+11 | 0.736777E+11 |
Minimum of Months | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.855883E+09 |
Maximum of Months | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.674037E+10 | 0.125861E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296613E+09 | 93347829.41 | 0.203265E+09 | 26575589.70 | 0.771760E+10 |
February | 0.148021E+10 | 0.706313E+09 | 0.773900E+09 | 0.773199E+09 | 0.584696E+10 |
March | 0.467449E+10 | 0.236722E+10 | 0.230727E+10 | 0.386591E+10 | 0.480019E+10 |
April | 0.621805E+10 | 0.314568E+10 | 0.307237E+10 | 0.562944E+10 | 0.253046E+10 |
May | 0.933414E+10 | 0.525464E+10 | 0.407950E+10 | 0.999541E+10 | 0.135961E+10 |
June | 0.831059E+10 | 0.387167E+10 | 0.443892E+10 | 0.922432E+10 | 0.642396E+09 |
July | 0.815712E+10 | 0.395014E+10 | 0.420697E+10 | 0.927086E+10 | 0.769154E+09 |
August | 0.646096E+10 | 0.314210E+10 | 0.331886E+10 | 0.702916E+10 | 0.119882E+10 |
September | 0.386797E+10 | 0.169317E+10 | 0.217480E+10 | 0.352541E+10 | 0.222033E+10 |
October | 0.211120E+10 | 0.847137E+09 | 0.126406E+10 | 0.147779E+10 | 0.415540E+10 |
November | 0.434592E+09 | 0.151861E+09 | 0.282731E+09 | 36317635.53 | 0.726467E+10 |
December | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.832836E+10 |
Annual Sum or Average | 0.514101E+11 | 0.252386E+11 | 0.261715E+11 | 0.508544E+11 | 0.468340E+11 |
Minimum of Months | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.642396E+09 |
Maximum of Months | 0.933414E+10 | 0.525464E+10 | 0.443892E+10 | 0.999541E+10 | 0.832836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202622E+10 | 0.133495E+10 | 0.691274E+09 | 0.117152E+10 | 0.107354E+11 |
February | 0.629760E+10 | 0.438063E+10 | 0.191697E+10 | 0.524506E+10 | 0.787771E+10 |
March | 0.119729E+11 | 0.811538E+10 | 0.385755E+10 | 0.114507E+11 | 0.678184E+10 |
April | 0.141354E+11 | 0.879367E+10 | 0.534177E+10 | 0.150574E+11 | 0.430856E+10 |
May | 0.120444E+11 | 0.624088E+10 | 0.580353E+10 | 0.132378E+11 | 0.238990E+10 |
June | 0.106423E+11 | 0.436199E+10 | 0.628027E+10 | 0.120529E+11 | 0.122613E+10 |
July | 0.105953E+11 | 0.461426E+10 | 0.598103E+10 | 0.122851E+11 | 0.136026E+10 |
August | 0.109725E+11 | 0.604711E+10 | 0.492539E+10 | 0.125180E+11 | 0.201676E+10 |
September | 0.858170E+10 | 0.516834E+10 | 0.341336E+10 | 0.886425E+10 | 0.346403E+10 |
October | 0.638482E+10 | 0.405099E+10 | 0.233383E+10 | 0.568115E+10 | 0.582773E+10 |
November | 0.331289E+10 | 0.231325E+10 | 0.999636E+09 | 0.216909E+10 | 0.973115E+10 |
December | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.107794E+09 | 0.119556E+11 |
Annual Sum or Average | 0.975737E+11 | 0.558498E+11 | 0.417240E+11 | 0.998407E+11 | 0.676750E+11 |
Minimum of Months | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.107794E+09 | 0.122613E+10 |
Maximum of Months | 0.141354E+11 | 0.879367E+10 | 0.628027E+10 | 0.150574E+11 | 0.119556E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156027E+09 | 27843188.30 | 0.128184E+09 | 0.00 | 0.792570E+10 |
February | 0.831928E+09 | 0.289287E+09 | 0.542642E+09 | 0.170091E+09 | 0.612437E+10 |
March | 0.276458E+10 | 0.118846E+10 | 0.157612E+10 | 0.155304E+10 | 0.495267E+10 |
April | 0.634847E+10 | 0.328983E+10 | 0.305865E+10 | 0.594976E+10 | 0.280458E+10 |
May | 0.637864E+10 | 0.290485E+10 | 0.347378E+10 | 0.636626E+10 | 0.149318E+10 |
June | 0.676516E+10 | 0.288450E+10 | 0.388067E+10 | 0.731808E+10 | 0.787151E+09 |
July | 0.584917E+10 | 0.221259E+10 | 0.363657E+10 | 0.638721E+10 | 0.881951E+09 |
August | 0.480737E+10 | 0.203570E+10 | 0.277168E+10 | 0.498293E+10 | 0.130941E+10 |
September | 0.281556E+10 | 0.117904E+10 | 0.163651E+10 | 0.227654E+10 | 0.230974E+10 |
October | 0.113942E+10 | 0.342551E+09 | 0.796868E+09 | 0.416719E+09 | 0.438156E+10 |
November | 0.441177E+09 | 0.160295E+09 | 0.280882E+09 | 47841081.67 | 0.732165E+10 |
December | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.844293E+10 |
Annual Sum or Average | 0.383384E+11 | 0.165193E+11 | 0.218192E+11 | 0.354685E+11 | 0.487349E+11 |
Minimum of Months | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.787151E+09 |
Maximum of Months | 0.676516E+10 | 0.328983E+10 | 0.388067E+10 | 0.731808E+10 | 0.844293E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168896E+09 | 0.00 | 0.168896E+09 | 0.00 | 0.116802E+11 |
February | 0.674350E+09 | 0.00 | 0.674350E+09 | 0.00 | 0.939947E+10 |
March | 0.199684E+10 | 0.00 | 0.199684E+10 | 0.195633E+09 | 0.762106E+10 |
April | 0.349631E+10 | 76984390.17 | 0.341932E+10 | 0.153776E+10 | 0.381111E+10 |
May | 0.553726E+10 | 0.880355E+09 | 0.465691E+10 | 0.436171E+10 | 0.178577E+10 |
June | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.675992E+10 | 0.827238E+09 |
July | 0.606349E+10 | 0.985567E+09 | 0.507792E+10 | 0.598229E+10 | 0.105453E+10 |
August | 0.387179E+10 | 0.216384E+09 | 0.365541E+10 | 0.317423E+10 | 0.171306E+10 |
September | 0.209035E+10 | 2104837.37 | 0.208824E+10 | 0.883799E+09 | 0.323734E+10 |
October | 0.105104E+10 | 0.00 | 0.105104E+10 | 0.105776E+09 | 0.640858E+10 |
November | 0.315655E+09 | 0.00 | 0.315655E+09 | 0.00 | 0.110202E+11 |
December | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.123076E+11 |
Annual Sum or Average | 0.323088E+11 | 0.371624E+10 | 0.285925E+11 | 0.230011E+11 | 0.708661E+11 |
Minimum of Months | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.827238E+09 |
Maximum of Months | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.675992E+10 | 0.123076E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296613E+09 | 93347829.41 | 0.203265E+09 | 27544222.46 | 0.755682E+10 |
February | 0.148021E+10 | 0.706313E+09 | 0.773900E+09 | 0.791015E+09 | 0.567517E+10 |
March | 0.467449E+10 | 0.236722E+10 | 0.230727E+10 | 0.392952E+10 | 0.458786E+10 |
April | 0.621805E+10 | 0.314568E+10 | 0.307237E+10 | 0.571664E+10 | 0.238100E+10 |
May | 0.933414E+10 | 0.525464E+10 | 0.407950E+10 | 0.100347E+11 | 0.130497E+10 |
June | 0.831059E+10 | 0.387167E+10 | 0.443892E+10 | 0.921870E+10 | 0.629973E+09 |
July | 0.815712E+10 | 0.395014E+10 | 0.420697E+10 | 0.926063E+10 | 0.758284E+09 |
August | 0.646096E+10 | 0.314210E+10 | 0.331886E+10 | 0.704439E+10 | 0.116313E+10 |
September | 0.386797E+10 | 0.169317E+10 | 0.217480E+10 | 0.359784E+10 | 0.206309E+10 |
October | 0.211120E+10 | 0.847137E+09 | 0.126406E+10 | 0.153033E+10 | 0.389795E+10 |
November | 0.434592E+09 | 0.151861E+09 | 0.282731E+09 | 38546592.21 | 0.706853E+10 |
December | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.816215E+10 |
Annual Sum or Average | 0.514101E+11 | 0.252386E+11 | 0.261715E+11 | 0.511898E+11 | 0.452489E+11 |
Minimum of Months | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.629973E+09 |
Maximum of Months | 0.933414E+10 | 0.525464E+10 | 0.443892E+10 | 0.100347E+11 | 0.816215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202622E+10 | 0.133495E+10 | 0.691274E+09 | 0.119118E+10 | 0.104924E+11 |
February | 0.629760E+10 | 0.438063E+10 | 0.191697E+10 | 0.532086E+10 | 0.760287E+10 |
March | 0.119729E+11 | 0.811538E+10 | 0.385755E+10 | 0.115731E+11 | 0.644666E+10 |
April | 0.141354E+11 | 0.879367E+10 | 0.534177E+10 | 0.151569E+11 | 0.405594E+10 |
May | 0.120444E+11 | 0.624088E+10 | 0.580353E+10 | 0.132846E+11 | 0.227568E+10 |
June | 0.106423E+11 | 0.436199E+10 | 0.628027E+10 | 0.120526E+11 | 0.119669E+10 |
July | 0.105953E+11 | 0.461426E+10 | 0.598103E+10 | 0.122812E+11 | 0.133690E+10 |
August | 0.109725E+11 | 0.604711E+10 | 0.492539E+10 | 0.125371E+11 | 0.195119E+10 |
September | 0.858170E+10 | 0.516834E+10 | 0.341336E+10 | 0.896056E+10 | 0.322699E+10 |
October | 0.638482E+10 | 0.405099E+10 | 0.233383E+10 | 0.580368E+10 | 0.544991E+10 |
November | 0.331289E+10 | 0.231325E+10 | 0.999636E+09 | 0.221121E+10 | 0.942813E+10 |
December | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.110340E+09 | 0.116944E+11 |
Annual Sum or Average | 0.975737E+11 | 0.558498E+11 | 0.417240E+11 | 0.100483E+12 | 0.651578E+11 |
Minimum of Months | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.110340E+09 | 0.119669E+10 |
Maximum of Months | 0.141354E+11 | 0.879367E+10 | 0.628027E+10 | 0.151569E+11 | 0.116944E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156027E+09 | 27843188.30 | 0.128184E+09 | 0.00 | 0.775227E+10 |
February | 0.831928E+09 | 0.289287E+09 | 0.542642E+09 | 0.175694E+09 | 0.595723E+10 |
March | 0.276458E+10 | 0.118846E+10 | 0.157612E+10 | 0.158498E+10 | 0.475064E+10 |
April | 0.634847E+10 | 0.328983E+10 | 0.305865E+10 | 0.601337E+10 | 0.264412E+10 |
May | 0.637864E+10 | 0.290485E+10 | 0.347378E+10 | 0.641142E+10 | 0.142130E+10 |
June | 0.676516E+10 | 0.288450E+10 | 0.388067E+10 | 0.732189E+10 | 0.768854E+09 |
July | 0.584917E+10 | 0.221259E+10 | 0.363657E+10 | 0.638939E+10 | 0.865218E+09 |
August | 0.480737E+10 | 0.203570E+10 | 0.277168E+10 | 0.500532E+10 | 0.126345E+10 |
September | 0.281556E+10 | 0.117904E+10 | 0.163651E+10 | 0.232872E+10 | 0.215775E+10 |
October | 0.113942E+10 | 0.342551E+09 | 0.796868E+09 | 0.444956E+09 | 0.414181E+10 |
November | 0.441177E+09 | 0.160295E+09 | 0.280882E+09 | 50901597.35 | 0.712926E+10 |
December | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.827417E+10 |
Annual Sum or Average | 0.383384E+11 | 0.165193E+11 | 0.218192E+11 | 0.357266E+11 | 0.471261E+11 |
Minimum of Months | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.768854E+09 |
Maximum of Months | 0.676516E+10 | 0.328983E+10 | 0.388067E+10 | 0.732189E+10 | 0.827417E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4576.65 | 63.06 | 0.00 | 63.06 | 0.00 | 0.00 |
February | 0.00 | 4159.58 | 278.74 | 0.00 | 278.74 | 0.00 | 0.00 |
March | 46.72 | 3154.14 | 745.52 | 0.00 | 745.52 | 0.00 | 0.00 |
April | 485.11 | 1738.94 | 1348.86 | 29.70 | 1319.16 | 0.00 | 0.00 |
May | 1548.47 | 739.28 | 2067.33 | 328.68 | 1738.66 | 0.00 | 0.00 |
June | 2595.22 | 340.20 | 2697.29 | 599.85 | 2097.45 | 0.00 | 0.00 |
July | 2219.90 | 414.94 | 2263.80 | 367.96 | 1895.84 | 0.00 | 0.00 |
August | 1138.39 | 705.43 | 1445.53 | 80.79 | 1364.75 | 0.00 | 0.00 |
September | 270.85 | 1487.41 | 806.45 | 0.81 | 805.63 | 0.00 | 0.00 |
October | 16.37 | 2782.99 | 392.41 | 0.00 | 392.41 | 0.00 | 0.00 |
November | 0.00 | 4591.05 | 121.78 | 0.00 | 121.78 | 0.00 | 0.00 |
December | 0.00 | 4897.27 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Annual Sum or Average | 697.54 | 2456.41 | 1024.48 | 117.84 | 906.64 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 340.20 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Maximum of Months | 2595.22 | 4897.27 | 2697.29 | 599.85 | 2097.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.91 | 2941.38 | 110.74 | 34.85 | 75.89 | 0.00 | 0.00 |
February | 312.73 | 2490.08 | 611.86 | 291.96 | 319.90 | 0.00 | 0.00 |
March | 1428.90 | 1861.76 | 1745.26 | 883.82 | 861.44 | 0.00 | 0.00 |
April | 2157.45 | 1031.75 | 2398.95 | 1213.61 | 1185.33 | 0.00 | 0.00 |
May | 3742.86 | 523.90 | 3484.98 | 1961.86 | 1523.12 | 0.00 | 0.00 |
June | 3572.17 | 249.72 | 3206.26 | 1493.71 | 1712.55 | 0.00 | 0.00 |
July | 3479.65 | 282.24 | 3045.53 | 1474.82 | 1570.71 | 0.00 | 0.00 |
August | 2633.45 | 446.87 | 2412.26 | 1173.13 | 1239.13 | 0.00 | 0.00 |
September | 1347.71 | 901.95 | 1492.28 | 653.23 | 839.04 | 0.00 | 0.00 |
October | 537.15 | 1653.42 | 788.23 | 316.29 | 471.95 | 0.00 | 0.00 |
November | 13.06 | 2916.86 | 167.67 | 58.59 | 109.08 | 0.00 | 0.00 |
December | 0.00 | 3204.15 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Annual Sum or Average | 1611.67 | 1537.14 | 1630.21 | 800.32 | 829.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 249.72 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Maximum of Months | 3742.86 | 3204.15 | 3484.98 | 1961.86 | 1712.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.32 | 4058.51 | 756.48 | 498.40 | 258.08 | 0.00 | 0.00 |
February | 2158.20 | 3316.93 | 2603.09 | 1810.72 | 792.38 | 0.00 | 0.00 |
March | 4276.29 | 2583.13 | 4470.04 | 3029.84 | 1440.21 | 0.00 | 0.00 |
April | 5821.27 | 1710.50 | 5453.32 | 3392.51 | 2060.82 | 0.00 | 0.00 |
May | 4960.79 | 908.20 | 4496.74 | 2330.00 | 2166.74 | 0.00 | 0.00 |
June | 4660.88 | 478.46 | 4105.70 | 1682.81 | 2422.89 | 0.00 | 0.00 |
July | 4597.71 | 506.18 | 3955.72 | 1722.71 | 2233.01 | 0.00 | 0.00 |
August | 4681.75 | 756.98 | 4096.54 | 2257.66 | 1838.89 | 0.00 | 0.00 |
September | 3422.55 | 1362.33 | 3310.74 | 1993.89 | 1316.85 | 0.00 | 0.00 |
October | 2107.29 | 2251.82 | 2383.74 | 1512.42 | 871.33 | 0.00 | 0.00 |
November | 824.02 | 3863.75 | 1278.08 | 892.43 | 385.65 | 0.00 | 0.00 |
December | 39.42 | 4570.40 | 226.87 | 159.91 | 66.96 | 0.00 | 0.00 |
Annual Sum or Average | 3168.07 | 2191.83 | 3093.95 | 1770.93 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 39.42 | 478.46 | 226.87 | 159.91 | 66.96 | 0.00 | 0.00 |
Maximum of Months | 5821.27 | 4570.40 | 5453.32 | 3392.51 | 2422.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3097.31 | 58.25 | 10.40 | 47.86 | 0.00 | 0.00 |
February | 63.41 | 2705.46 | 343.89 | 119.58 | 224.31 | 0.00 | 0.00 |
March | 548.13 | 2037.86 | 1032.18 | 443.72 | 588.46 | 0.00 | 0.00 |
April | 2231.85 | 1231.45 | 2449.27 | 1269.23 | 1180.04 | 0.00 | 0.00 |
May | 2351.27 | 595.14 | 2381.52 | 1084.55 | 1296.97 | 0.00 | 0.00 |
June | 2795.84 | 330.08 | 2610.03 | 1112.85 | 1497.18 | 0.00 | 0.00 |
July | 2346.30 | 362.97 | 2183.84 | 826.09 | 1357.75 | 0.00 | 0.00 |
August | 1811.80 | 554.24 | 1794.87 | 760.04 | 1034.83 | 0.00 | 0.00 |
September | 846.12 | 980.20 | 1086.25 | 454.88 | 631.37 | 0.00 | 0.00 |
October | 137.42 | 1828.33 | 425.41 | 127.89 | 297.52 | 0.00 | 0.00 |
November | 15.16 | 3062.62 | 170.21 | 61.84 | 108.37 | 0.00 | 0.00 |
December | 0.00 | 3408.48 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Annual Sum or Average | 1099.96 | 1677.53 | 1215.71 | 523.82 | 691.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 330.08 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Maximum of Months | 2795.84 | 3408.48 | 2610.03 | 1269.23 | 1497.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4459.15 | 63.06 | 0.00 | 63.06 | 0.00 | 0.00 |
February | 0.00 | 4002.89 | 278.75 | 0.00 | 278.75 | 0.00 | 0.00 |
March | 61.73 | 2973.31 | 745.53 | 0.00 | 745.53 | 0.00 | 0.00 |
April | 540.47 | 1580.62 | 1348.88 | 29.70 | 1319.18 | 0.00 | 0.00 |
May | 1572.67 | 709.06 | 2067.38 | 328.69 | 1738.69 | 0.00 | 0.00 |
June | 2600.45 | 330.20 | 2697.35 | 599.86 | 2097.49 | 0.00 | 0.00 |
July | 2226.96 | 405.01 | 2263.85 | 367.97 | 1895.88 | 0.00 | 0.00 |
August | 1160.08 | 673.06 | 1445.56 | 80.79 | 1364.77 | 0.00 | 0.00 |
September | 295.62 | 1380.33 | 806.46 | 0.81 | 805.65 | 0.00 | 0.00 |
October | 25.72 | 2557.09 | 392.42 | 0.00 | 392.42 | 0.00 | 0.00 |
November | 0.00 | 4372.89 | 121.78 | 0.00 | 121.78 | 0.00 | 0.00 |
December | 0.00 | 4699.09 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Annual Sum or Average | 711.12 | 2336.30 | 1024.50 | 117.84 | 906.66 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 330.20 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Maximum of Months | 2600.45 | 4699.09 | 2697.35 | 599.86 | 2097.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.92 | 2881.42 | 110.74 | 34.85 | 75.89 | 0.00 | 0.00 |
February | 319.61 | 2416.90 | 611.86 | 291.96 | 319.90 | 0.00 | 0.00 |
March | 1443.37 | 1792.18 | 1745.26 | 883.82 | 861.44 | 0.00 | 0.00 |
April | 2171.85 | 976.26 | 2398.94 | 1213.61 | 1185.33 | 0.00 | 0.00 |
May | 3731.86 | 507.62 | 3484.97 | 1961.86 | 1523.11 | 0.00 | 0.00 |
June | 3558.77 | 247.84 | 3206.25 | 1493.70 | 1712.55 | 0.00 | 0.00 |
July | 3461.34 | 287.17 | 3045.52 | 1474.81 | 1570.70 | 0.00 | 0.00 |
August | 2624.39 | 447.59 | 2412.25 | 1173.13 | 1239.12 | 0.00 | 0.00 |
September | 1360.11 | 856.61 | 1492.27 | 653.23 | 839.04 | 0.00 | 0.00 |
October | 551.75 | 1551.45 | 788.23 | 316.28 | 471.95 | 0.00 | 0.00 |
November | 14.01 | 2802.73 | 167.67 | 58.59 | 109.08 | 0.00 | 0.00 |
December | 0.00 | 3109.45 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Annual Sum or Average | 1612.58 | 1485.09 | 1630.20 | 800.31 | 829.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 247.84 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Maximum of Months | 3731.86 | 3109.45 | 3484.97 | 1961.86 | 1712.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.39 | 4008.13 | 756.51 | 498.41 | 258.09 | 0.00 | 0.00 |
February | 2168.10 | 3256.33 | 2603.17 | 1810.77 | 792.40 | 0.00 | 0.00 |
March | 4275.19 | 2532.05 | 4470.18 | 3029.94 | 1440.24 | 0.00 | 0.00 |
April | 5809.17 | 1662.25 | 5453.49 | 3392.62 | 2060.87 | 0.00 | 0.00 |
May | 4942.44 | 892.29 | 4496.87 | 2330.08 | 2166.79 | 0.00 | 0.00 |
June | 4650.04 | 473.04 | 4105.81 | 1682.87 | 2422.94 | 0.00 | 0.00 |
July | 4586.73 | 507.86 | 3955.83 | 1722.77 | 2233.06 | 0.00 | 0.00 |
August | 4673.69 | 752.97 | 4096.66 | 2257.73 | 1838.93 | 0.00 | 0.00 |
September | 3419.85 | 1336.43 | 3310.84 | 1993.96 | 1316.88 | 0.00 | 0.00 |
October | 2121.10 | 2175.83 | 2383.82 | 1512.47 | 871.35 | 0.00 | 0.00 |
November | 836.84 | 3754.30 | 1278.12 | 892.46 | 385.66 | 0.00 | 0.00 |
December | 40.25 | 4463.70 | 226.88 | 159.92 | 66.96 | 0.00 | 0.00 |
Annual Sum or Average | 3165.93 | 2145.96 | 3094.04 | 1770.98 | 1323.06 | 0.00 | 0.00 |
Minimum of Months | 40.25 | 473.04 | 226.88 | 159.92 | 66.96 | 0.00 | 0.00 |
Maximum of Months | 5809.17 | 4463.70 | 5453.49 | 3392.62 | 2422.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2959.12 | 58.25 | 10.40 | 47.86 | 0.00 | 0.00 |
February | 70.31 | 2531.57 | 343.89 | 119.58 | 224.31 | 0.00 | 0.00 |
March | 579.84 | 1849.12 | 1032.18 | 443.72 | 588.46 | 0.00 | 0.00 |
April | 2295.43 | 1082.01 | 2449.26 | 1269.22 | 1180.03 | 0.00 | 0.00 |
May | 2376.89 | 557.49 | 2381.51 | 1084.55 | 1296.96 | 0.00 | 0.00 |
June | 2823.33 | 303.68 | 2610.02 | 1112.85 | 1497.17 | 0.00 | 0.00 |
July | 2384.71 | 329.28 | 2183.83 | 826.09 | 1357.74 | 0.00 | 0.00 |
August | 1860.41 | 488.88 | 1794.87 | 760.04 | 1034.83 | 0.00 | 0.00 |
September | 878.29 | 891.10 | 1086.25 | 454.88 | 631.37 | 0.00 | 0.00 |
October | 155.59 | 1635.89 | 425.41 | 127.89 | 297.52 | 0.00 | 0.00 |
November | 18.46 | 2824.71 | 170.21 | 61.84 | 108.37 | 0.00 | 0.00 |
December | 0.00 | 3152.23 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Annual Sum or Average | 1124.70 | 1545.37 | 1215.70 | 523.82 | 691.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 303.68 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Maximum of Months | 2823.33 | 3152.23 | 2610.02 | 1269.22 | 1497.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4360.88 | 63.06 | 0.00 | 63.06 | 0.00 | 0.00 |
February | 0.00 | 3885.36 | 278.75 | 0.00 | 278.75 | 0.00 | 0.00 |
March | 73.04 | 2845.38 | 745.53 | 0.00 | 745.53 | 0.00 | 0.00 |
April | 593.27 | 1470.33 | 1348.88 | 29.70 | 1319.18 | 0.00 | 0.00 |
May | 1628.48 | 666.73 | 2067.38 | 328.69 | 1738.69 | 0.00 | 0.00 |
June | 2608.00 | 319.15 | 2697.35 | 599.86 | 2097.49 | 0.00 | 0.00 |
July | 2233.53 | 393.72 | 2263.85 | 367.97 | 1895.88 | 0.00 | 0.00 |
August | 1185.12 | 639.58 | 1445.56 | 80.79 | 1364.77 | 0.00 | 0.00 |
September | 340.97 | 1248.97 | 806.46 | 0.81 | 805.65 | 0.00 | 0.00 |
October | 39.49 | 2392.69 | 392.42 | 0.00 | 392.42 | 0.00 | 0.00 |
November | 0.00 | 4251.61 | 121.78 | 0.00 | 121.78 | 0.00 | 0.00 |
December | 0.00 | 4595.14 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Annual Sum or Average | 729.36 | 2247.15 | 1024.50 | 117.84 | 906.66 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 319.15 | 19.13 | 0.00 | 19.13 | 0.00 | 0.00 |
Maximum of Months | 2608.00 | 4595.14 | 2697.35 | 599.86 | 2097.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.28 | 2821.39 | 110.74 | 34.85 | 75.89 | 0.00 | 0.00 |
February | 326.97 | 2345.89 | 611.86 | 291.96 | 319.90 | 0.00 | 0.00 |
March | 1467.12 | 1712.91 | 1745.26 | 883.82 | 861.44 | 0.00 | 0.00 |
April | 2205.49 | 918.59 | 2398.94 | 1213.61 | 1185.33 | 0.00 | 0.00 |
May | 3746.51 | 487.22 | 3484.97 | 1961.86 | 1523.11 | 0.00 | 0.00 |
June | 3556.60 | 243.05 | 3206.25 | 1493.70 | 1712.55 | 0.00 | 0.00 |
July | 3457.52 | 283.11 | 3045.52 | 1474.81 | 1570.70 | 0.00 | 0.00 |
August | 2630.07 | 434.26 | 2412.25 | 1173.13 | 1239.12 | 0.00 | 0.00 |
September | 1388.06 | 795.95 | 1492.27 | 653.23 | 839.04 | 0.00 | 0.00 |
October | 571.36 | 1455.33 | 788.23 | 316.28 | 471.95 | 0.00 | 0.00 |
November | 14.87 | 2727.06 | 167.67 | 58.59 | 109.08 | 0.00 | 0.00 |
December | 0.00 | 3047.40 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Annual Sum or Average | 1623.22 | 1434.83 | 1630.20 | 800.31 | 829.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 243.05 | 23.95 | 5.73 | 18.22 | 0.00 | 0.00 |
Maximum of Months | 3746.51 | 3047.40 | 3484.97 | 1961.86 | 1712.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.74 | 3917.41 | 756.51 | 498.41 | 258.09 | 0.00 | 0.00 |
February | 2199.43 | 3142.72 | 2603.17 | 1810.77 | 792.40 | 0.00 | 0.00 |
March | 4320.91 | 2406.91 | 4470.18 | 3029.94 | 1440.24 | 0.00 | 0.00 |
April | 5847.58 | 1564.79 | 5453.49 | 3392.62 | 2060.87 | 0.00 | 0.00 |
May | 4959.91 | 849.64 | 4496.87 | 2330.08 | 2166.79 | 0.00 | 0.00 |
June | 4649.91 | 461.69 | 4105.81 | 1682.87 | 2422.94 | 0.00 | 0.00 |
July | 4585.27 | 499.14 | 3955.83 | 1722.77 | 2233.06 | 0.00 | 0.00 |
August | 4680.80 | 728.49 | 4096.66 | 2257.73 | 1838.93 | 0.00 | 0.00 |
September | 3457.01 | 1244.98 | 3310.84 | 1993.96 | 1316.88 | 0.00 | 0.00 |
October | 2166.84 | 2034.76 | 2383.82 | 1512.47 | 871.35 | 0.00 | 0.00 |
November | 853.09 | 3637.40 | 1278.12 | 892.46 | 385.66 | 0.00 | 0.00 |
December | 41.20 | 4366.20 | 226.88 | 159.92 | 66.96 | 0.00 | 0.00 |
Annual Sum or Average | 3186.30 | 2066.14 | 3094.04 | 1770.98 | 1323.06 | 0.00 | 0.00 |
Minimum of Months | 41.20 | 461.69 | 226.88 | 159.92 | 66.96 | 0.00 | 0.00 |
Maximum of Months | 5847.58 | 4366.20 | 5453.49 | 3392.62 | 2422.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2894.37 | 58.25 | 10.40 | 47.86 | 0.00 | 0.00 |
February | 72.62 | 2462.48 | 343.89 | 119.58 | 224.31 | 0.00 | 0.00 |
March | 591.76 | 1773.69 | 1032.18 | 443.72 | 588.46 | 0.00 | 0.00 |
April | 2319.97 | 1020.11 | 2449.26 | 1269.22 | 1180.03 | 0.00 | 0.00 |
May | 2393.75 | 530.65 | 2381.51 | 1084.55 | 1296.96 | 0.00 | 0.00 |
June | 2824.80 | 296.63 | 2610.02 | 1112.85 | 1497.17 | 0.00 | 0.00 |
July | 2385.53 | 323.04 | 2183.83 | 826.09 | 1357.74 | 0.00 | 0.00 |
August | 1868.77 | 471.72 | 1794.87 | 760.04 | 1034.83 | 0.00 | 0.00 |
September | 898.43 | 832.46 | 1086.25 | 454.88 | 631.37 | 0.00 | 0.00 |
October | 166.13 | 1546.38 | 425.41 | 127.89 | 297.52 | 0.00 | 0.00 |
November | 19.64 | 2750.49 | 170.21 | 61.84 | 108.37 | 0.00 | 0.00 |
December | 0.00 | 3089.22 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Annual Sum or Average | 1132.88 | 1494.36 | 1215.70 | 523.82 | 691.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 296.63 | 15.28 | 1.61 | 13.67 | 0.00 | 0.00 |
Maximum of Months | 2824.80 | 3089.22 | 2610.02 | 1269.22 | 1497.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.122581E+11 | 0.168892E+09 | 0.00 | 0.168892E+09 | 0.00 | 0.00 |
February | 0.00 | 0.100629E+11 | 0.674336E+09 | 0.00 | 0.674336E+09 | 0.00 | 0.00 |
March | 0.125122E+09 | 0.844805E+10 | 0.199680E+10 | 0.00 | 0.199680E+10 | 0.00 | 0.00 |
April | 0.125740E+10 | 0.450734E+10 | 0.349624E+10 | 76982094.35 | 0.341926E+10 | 0.00 | 0.00 |
May | 0.414741E+10 | 0.198009E+10 | 0.553715E+10 | 0.880329E+09 | 0.465682E+10 | 0.00 | 0.00 |
June | 0.672682E+10 | 0.881811E+09 | 0.699139E+10 | 0.155480E+10 | 0.543659E+10 | 0.00 | 0.00 |
July | 0.594579E+10 | 0.111139E+10 | 0.606335E+10 | 0.985538E+09 | 0.507782E+10 | 0.00 | 0.00 |
August | 0.304906E+10 | 0.188942E+10 | 0.387171E+10 | 0.216378E+09 | 0.365534E+10 | 0.00 | 0.00 |
September | 0.702033E+09 | 0.385537E+10 | 0.209031E+10 | 2104774.60 | 0.208820E+10 | 0.00 | 0.00 |
October | 43838362.80 | 0.745397E+10 | 0.105102E+10 | 0.00 | 0.105102E+10 | 0.00 | 0.00 |
November | 0.00 | 0.119000E+11 | 0.315648E+09 | 0.00 | 0.315648E+09 | 0.00 | 0.00 |
December | 0.00 | 0.131168E+11 | 51233092.76 | 0.00 | 51233092.76 | 0.00 | 0.00 |
Annual Sum or Average | 0.219975E+11 | 0.774652E+11 | 0.323081E+11 | 0.371613E+10 | 0.285920E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.881811E+09 | 51233092.76 | 0.00 | 51233092.76 | 0.00 | 0.00 |
Maximum of Months | 0.672682E+10 | 0.131168E+11 | 0.699139E+10 | 0.155480E+10 | 0.543659E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26549070.47 | 0.787820E+10 | 0.296614E+09 | 93348212.34 | 0.203266E+09 | 0.00 | 0.00 |
February | 0.756566E+09 | 0.602400E+10 | 0.148022E+10 | 0.706315E+09 | 0.773903E+09 | 0.00 | 0.00 |
March | 0.382717E+10 | 0.498655E+10 | 0.467451E+10 | 0.236723E+10 | 0.230728E+10 | 0.00 | 0.00 |
April | 0.559210E+10 | 0.267430E+10 | 0.621808E+10 | 0.314569E+10 | 0.307239E+10 | 0.00 | 0.00 |
May | 0.100249E+11 | 0.140320E+10 | 0.933418E+10 | 0.525466E+10 | 0.407952E+10 | 0.00 | 0.00 |
June | 0.925908E+10 | 0.647272E+09 | 0.831062E+10 | 0.387169E+10 | 0.443894E+10 | 0.00 | 0.00 |
July | 0.931990E+10 | 0.755940E+09 | 0.815715E+10 | 0.395016E+10 | 0.420699E+10 | 0.00 | 0.00 |
August | 0.705344E+10 | 0.119690E+10 | 0.646099E+10 | 0.314212E+10 | 0.331887E+10 | 0.00 | 0.00 |
September | 0.349328E+10 | 0.233785E+10 | 0.386798E+10 | 0.169318E+10 | 0.217480E+10 | 0.00 | 0.00 |
October | 0.143871E+10 | 0.442851E+10 | 0.211121E+10 | 0.847140E+09 | 0.126407E+10 | 0.00 | 0.00 |
November | 33860756.87 | 0.756049E+10 | 0.434594E+09 | 0.151862E+09 | 0.282732E+09 | 0.00 | 0.00 |
December | 0.00 | 0.858198E+10 | 64160089.31 | 15358783.65 | 48801305.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.508255E+11 | 0.484752E+11 | 0.514103E+11 | 0.252387E+11 | 0.261716E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.647272E+09 | 64160089.31 | 15358783.65 | 48801305.66 | 0.00 | 0.00 |
Maximum of Months | 0.100249E+11 | 0.858198E+10 | 0.933418E+10 | 0.525466E+10 | 0.443894E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116595E+10 | 0.108703E+11 | 0.202616E+10 | 0.133491E+10 | 0.691253E+09 | 0.00 | 0.00 |
February | 0.522112E+10 | 0.802433E+10 | 0.629740E+10 | 0.438048E+10 | 0.191692E+10 | 0.00 | 0.00 |
March | 0.114536E+11 | 0.691867E+10 | 0.119726E+11 | 0.811511E+10 | 0.385745E+10 | 0.00 | 0.00 |
April | 0.150887E+11 | 0.443362E+10 | 0.141350E+11 | 0.879338E+10 | 0.534164E+10 | 0.00 | 0.00 |
May | 0.132870E+11 | 0.243253E+10 | 0.120441E+11 | 0.624068E+10 | 0.580339E+10 | 0.00 | 0.00 |
June | 0.120810E+11 | 0.124016E+10 | 0.106420E+11 | 0.436185E+10 | 0.628013E+10 | 0.00 | 0.00 |
July | 0.123145E+11 | 0.135575E+10 | 0.105950E+11 | 0.461411E+10 | 0.598089E+10 | 0.00 | 0.00 |
August | 0.125396E+11 | 0.202750E+10 | 0.109722E+11 | 0.604691E+10 | 0.492527E+10 | 0.00 | 0.00 |
September | 0.887125E+10 | 0.353116E+10 | 0.858144E+10 | 0.516817E+10 | 0.341328E+10 | 0.00 | 0.00 |
October | 0.564416E+10 | 0.603127E+10 | 0.638462E+10 | 0.405086E+10 | 0.233376E+10 | 0.00 | 0.00 |
November | 0.213586E+10 | 0.100148E+11 | 0.331278E+10 | 0.231318E+10 | 0.999606E+09 | 0.00 | 0.00 |
December | 0.105574E+09 | 0.122414E+11 | 0.607648E+09 | 0.428308E+09 | 0.179340E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.999083E+11 | 0.691215E+11 | 0.975709E+11 | 0.558479E+11 | 0.417229E+11 | 0.00 | 0.00 |
Minimum of Months | 0.105574E+09 | 0.124016E+10 | 0.607648E+09 | 0.428308E+09 | 0.179340E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150887E+11 | 0.122414E+11 | 0.141350E+11 | 0.879338E+10 | 0.628013E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.829585E+10 | 0.156027E+09 | 27843302.52 | 0.128184E+09 | 0.00 | 0.00 |
February | 0.153395E+09 | 0.654504E+10 | 0.831932E+09 | 0.289288E+09 | 0.542644E+09 | 0.00 | 0.00 |
March | 0.146810E+10 | 0.545820E+10 | 0.276459E+10 | 0.118847E+10 | 0.157613E+10 | 0.00 | 0.00 |
April | 0.578495E+10 | 0.319191E+10 | 0.634850E+10 | 0.328984E+10 | 0.305866E+10 | 0.00 | 0.00 |
May | 0.629765E+10 | 0.159402E+10 | 0.637866E+10 | 0.290486E+10 | 0.347380E+10 | 0.00 | 0.00 |
June | 0.724683E+10 | 0.855574E+09 | 0.676519E+10 | 0.288451E+10 | 0.388068E+10 | 0.00 | 0.00 |
July | 0.628434E+10 | 0.972179E+09 | 0.584919E+10 | 0.221260E+10 | 0.363659E+10 | 0.00 | 0.00 |
August | 0.485271E+10 | 0.148447E+10 | 0.480739E+10 | 0.203570E+10 | 0.277169E+10 | 0.00 | 0.00 |
September | 0.219313E+10 | 0.254068E+10 | 0.281557E+10 | 0.117905E+10 | 0.163652E+10 | 0.00 | 0.00 |
October | 0.368065E+09 | 0.489700E+10 | 0.113942E+10 | 0.342552E+09 | 0.796871E+09 | 0.00 | 0.00 |
November | 39290947.26 | 0.793831E+10 | 0.441179E+09 | 0.160296E+09 | 0.280883E+09 | 0.00 | 0.00 |
December | 0.00 | 0.912927E+10 | 40927810.63 | 4302259.37 | 36625551.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.346885E+11 | 0.529025E+11 | 0.383386E+11 | 0.165193E+11 | 0.218193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.855574E+09 | 40927810.63 | 4302259.37 | 36625551.27 | 0.00 | 0.00 |
Maximum of Months | 0.724683E+10 | 0.912927E+10 | 0.676519E+10 | 0.328984E+10 | 0.388068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.119434E+11 | 0.168896E+09 | 0.00 | 0.168896E+09 | 0.00 | 0.00 |
February | 0.00 | 0.968378E+10 | 0.674350E+09 | 0.00 | 0.674350E+09 | 0.00 | 0.00 |
March | 0.165347E+09 | 0.796371E+10 | 0.199684E+10 | 0.00 | 0.199684E+10 | 0.00 | 0.00 |
April | 0.140091E+10 | 0.409696E+10 | 0.349631E+10 | 76984390.17 | 0.341932E+10 | 0.00 | 0.00 |
May | 0.421224E+10 | 0.189916E+10 | 0.553726E+10 | 0.880355E+09 | 0.465691E+10 | 0.00 | 0.00 |
June | 0.674037E+10 | 0.855883E+09 | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.00 | 0.00 |
July | 0.596468E+10 | 0.108478E+10 | 0.606349E+10 | 0.985567E+09 | 0.507792E+10 | 0.00 | 0.00 |
August | 0.310715E+10 | 0.180273E+10 | 0.387179E+10 | 0.216384E+09 | 0.365541E+10 | 0.00 | 0.00 |
September | 0.766243E+09 | 0.357782E+10 | 0.209035E+10 | 2104837.37 | 0.208824E+10 | 0.00 | 0.00 |
October | 68880615.58 | 0.684890E+10 | 0.105104E+10 | 0.00 | 0.105104E+10 | 0.00 | 0.00 |
November | 0.00 | 0.113345E+11 | 0.315655E+09 | 0.00 | 0.315655E+09 | 0.00 | 0.00 |
December | 0.00 | 0.125861E+11 | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.224258E+11 | 0.736777E+11 | 0.323088E+11 | 0.371624E+10 | 0.285925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.855883E+09 | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.00 |
Maximum of Months | 0.674037E+10 | 0.125861E+11 | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26575589.70 | 0.771760E+10 | 0.296613E+09 | 93347829.41 | 0.203265E+09 | 0.00 | 0.00 |
February | 0.773199E+09 | 0.584696E+10 | 0.148021E+10 | 0.706313E+09 | 0.773900E+09 | 0.00 | 0.00 |
March | 0.386591E+10 | 0.480019E+10 | 0.467449E+10 | 0.236722E+10 | 0.230727E+10 | 0.00 | 0.00 |
April | 0.562944E+10 | 0.253046E+10 | 0.621805E+10 | 0.314568E+10 | 0.307237E+10 | 0.00 | 0.00 |
May | 0.999541E+10 | 0.135961E+10 | 0.933414E+10 | 0.525464E+10 | 0.407950E+10 | 0.00 | 0.00 |
June | 0.922432E+10 | 0.642396E+09 | 0.831059E+10 | 0.387167E+10 | 0.443892E+10 | 0.00 | 0.00 |
July | 0.927086E+10 | 0.769154E+09 | 0.815712E+10 | 0.395014E+10 | 0.420697E+10 | 0.00 | 0.00 |
August | 0.702916E+10 | 0.119882E+10 | 0.646096E+10 | 0.314210E+10 | 0.331886E+10 | 0.00 | 0.00 |
September | 0.352541E+10 | 0.222033E+10 | 0.386797E+10 | 0.169317E+10 | 0.217480E+10 | 0.00 | 0.00 |
October | 0.147779E+10 | 0.415540E+10 | 0.211120E+10 | 0.847137E+09 | 0.126406E+10 | 0.00 | 0.00 |
November | 36317635.53 | 0.726467E+10 | 0.434592E+09 | 0.151861E+09 | 0.282731E+09 | 0.00 | 0.00 |
December | 0.00 | 0.832836E+10 | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.508544E+11 | 0.468340E+11 | 0.514101E+11 | 0.252386E+11 | 0.261715E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.642396E+09 | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.00 |
Maximum of Months | 0.999541E+10 | 0.832836E+10 | 0.933414E+10 | 0.525464E+10 | 0.443892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117152E+10 | 0.107354E+11 | 0.202622E+10 | 0.133495E+10 | 0.691274E+09 | 0.00 | 0.00 |
February | 0.524506E+10 | 0.787771E+10 | 0.629760E+10 | 0.438063E+10 | 0.191697E+10 | 0.00 | 0.00 |
March | 0.114507E+11 | 0.678184E+10 | 0.119729E+11 | 0.811538E+10 | 0.385755E+10 | 0.00 | 0.00 |
April | 0.150574E+11 | 0.430856E+10 | 0.141354E+11 | 0.879367E+10 | 0.534177E+10 | 0.00 | 0.00 |
May | 0.132378E+11 | 0.238990E+10 | 0.120444E+11 | 0.624088E+10 | 0.580353E+10 | 0.00 | 0.00 |
June | 0.120529E+11 | 0.122613E+10 | 0.106423E+11 | 0.436199E+10 | 0.628027E+10 | 0.00 | 0.00 |
July | 0.122851E+11 | 0.136026E+10 | 0.105953E+11 | 0.461426E+10 | 0.598103E+10 | 0.00 | 0.00 |
August | 0.125180E+11 | 0.201676E+10 | 0.109725E+11 | 0.604711E+10 | 0.492539E+10 | 0.00 | 0.00 |
September | 0.886425E+10 | 0.346403E+10 | 0.858170E+10 | 0.516834E+10 | 0.341336E+10 | 0.00 | 0.00 |
October | 0.568115E+10 | 0.582773E+10 | 0.638482E+10 | 0.405099E+10 | 0.233383E+10 | 0.00 | 0.00 |
November | 0.216909E+10 | 0.973115E+10 | 0.331289E+10 | 0.231325E+10 | 0.999636E+09 | 0.00 | 0.00 |
December | 0.107794E+09 | 0.119556E+11 | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.998407E+11 | 0.676750E+11 | 0.975737E+11 | 0.558498E+11 | 0.417240E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107794E+09 | 0.122613E+10 | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150574E+11 | 0.119556E+11 | 0.141354E+11 | 0.879367E+10 | 0.628027E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.792570E+10 | 0.156027E+09 | 27843188.30 | 0.128184E+09 | 0.00 | 0.00 |
February | 0.170091E+09 | 0.612437E+10 | 0.831928E+09 | 0.289287E+09 | 0.542642E+09 | 0.00 | 0.00 |
March | 0.155304E+10 | 0.495267E+10 | 0.276458E+10 | 0.118846E+10 | 0.157612E+10 | 0.00 | 0.00 |
April | 0.594976E+10 | 0.280458E+10 | 0.634847E+10 | 0.328983E+10 | 0.305865E+10 | 0.00 | 0.00 |
May | 0.636626E+10 | 0.149318E+10 | 0.637864E+10 | 0.290485E+10 | 0.347378E+10 | 0.00 | 0.00 |
June | 0.731808E+10 | 0.787151E+09 | 0.676516E+10 | 0.288450E+10 | 0.388067E+10 | 0.00 | 0.00 |
July | 0.638721E+10 | 0.881951E+09 | 0.584917E+10 | 0.221259E+10 | 0.363657E+10 | 0.00 | 0.00 |
August | 0.498293E+10 | 0.130941E+10 | 0.480737E+10 | 0.203570E+10 | 0.277168E+10 | 0.00 | 0.00 |
September | 0.227654E+10 | 0.230974E+10 | 0.281556E+10 | 0.117904E+10 | 0.163651E+10 | 0.00 | 0.00 |
October | 0.416719E+09 | 0.438156E+10 | 0.113942E+10 | 0.342551E+09 | 0.796868E+09 | 0.00 | 0.00 |
November | 47841081.67 | 0.732165E+10 | 0.441177E+09 | 0.160295E+09 | 0.280882E+09 | 0.00 | 0.00 |
December | 0.00 | 0.844293E+10 | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.354685E+11 | 0.487349E+11 | 0.383384E+11 | 0.165193E+11 | 0.218192E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.787151E+09 | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.00 |
Maximum of Months | 0.731808E+10 | 0.844293E+10 | 0.676516E+10 | 0.328983E+10 | 0.388067E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.116802E+11 | 0.168896E+09 | 0.00 | 0.168896E+09 | 0.00 | 0.00 |
February | 0.00 | 0.939947E+10 | 0.674350E+09 | 0.00 | 0.674350E+09 | 0.00 | 0.00 |
March | 0.195633E+09 | 0.762106E+10 | 0.199684E+10 | 0.00 | 0.199684E+10 | 0.00 | 0.00 |
April | 0.153776E+10 | 0.381111E+10 | 0.349631E+10 | 76984390.17 | 0.341932E+10 | 0.00 | 0.00 |
May | 0.436171E+10 | 0.178577E+10 | 0.553726E+10 | 0.880355E+09 | 0.465691E+10 | 0.00 | 0.00 |
June | 0.675992E+10 | 0.827238E+09 | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.00 | 0.00 |
July | 0.598229E+10 | 0.105453E+10 | 0.606349E+10 | 0.985567E+09 | 0.507792E+10 | 0.00 | 0.00 |
August | 0.317423E+10 | 0.171306E+10 | 0.387179E+10 | 0.216384E+09 | 0.365541E+10 | 0.00 | 0.00 |
September | 0.883799E+09 | 0.323734E+10 | 0.209035E+10 | 2104837.37 | 0.208824E+10 | 0.00 | 0.00 |
October | 0.105776E+09 | 0.640858E+10 | 0.105104E+10 | 0.00 | 0.105104E+10 | 0.00 | 0.00 |
November | 0.00 | 0.110202E+11 | 0.315655E+09 | 0.00 | 0.315655E+09 | 0.00 | 0.00 |
December | 0.00 | 0.123076E+11 | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.00 |
Annual Sum or Average | 0.230011E+11 | 0.708661E+11 | 0.323088E+11 | 0.371624E+10 | 0.285925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.827238E+09 | 51234282.39 | 0.00 | 51234282.39 | 0.00 | 0.00 |
Maximum of Months | 0.675992E+10 | 0.123076E+11 | 0.699154E+10 | 0.155485E+10 | 0.543669E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27544222.46 | 0.755682E+10 | 0.296613E+09 | 93347829.41 | 0.203265E+09 | 0.00 | 0.00 |
February | 0.791015E+09 | 0.567517E+10 | 0.148021E+10 | 0.706313E+09 | 0.773900E+09 | 0.00 | 0.00 |
March | 0.392952E+10 | 0.458786E+10 | 0.467449E+10 | 0.236722E+10 | 0.230727E+10 | 0.00 | 0.00 |
April | 0.571664E+10 | 0.238100E+10 | 0.621805E+10 | 0.314568E+10 | 0.307237E+10 | 0.00 | 0.00 |
May | 0.100347E+11 | 0.130497E+10 | 0.933414E+10 | 0.525464E+10 | 0.407950E+10 | 0.00 | 0.00 |
June | 0.921870E+10 | 0.629973E+09 | 0.831059E+10 | 0.387167E+10 | 0.443892E+10 | 0.00 | 0.00 |
July | 0.926063E+10 | 0.758284E+09 | 0.815712E+10 | 0.395014E+10 | 0.420697E+10 | 0.00 | 0.00 |
August | 0.704439E+10 | 0.116313E+10 | 0.646096E+10 | 0.314210E+10 | 0.331886E+10 | 0.00 | 0.00 |
September | 0.359784E+10 | 0.206309E+10 | 0.386797E+10 | 0.169317E+10 | 0.217480E+10 | 0.00 | 0.00 |
October | 0.153033E+10 | 0.389795E+10 | 0.211120E+10 | 0.847137E+09 | 0.126406E+10 | 0.00 | 0.00 |
November | 38546592.21 | 0.706853E+10 | 0.434592E+09 | 0.151861E+09 | 0.282731E+09 | 0.00 | 0.00 |
December | 0.00 | 0.816215E+10 | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.511898E+11 | 0.452489E+11 | 0.514101E+11 | 0.252386E+11 | 0.261715E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.629973E+09 | 64159826.11 | 15358720.65 | 48801105.47 | 0.00 | 0.00 |
Maximum of Months | 0.100347E+11 | 0.816215E+10 | 0.933414E+10 | 0.525464E+10 | 0.443892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119118E+10 | 0.104924E+11 | 0.202622E+10 | 0.133495E+10 | 0.691274E+09 | 0.00 | 0.00 |
February | 0.532086E+10 | 0.760287E+10 | 0.629760E+10 | 0.438063E+10 | 0.191697E+10 | 0.00 | 0.00 |
March | 0.115731E+11 | 0.644666E+10 | 0.119729E+11 | 0.811538E+10 | 0.385755E+10 | 0.00 | 0.00 |
April | 0.151569E+11 | 0.405594E+10 | 0.141354E+11 | 0.879367E+10 | 0.534177E+10 | 0.00 | 0.00 |
May | 0.132846E+11 | 0.227568E+10 | 0.120444E+11 | 0.624088E+10 | 0.580353E+10 | 0.00 | 0.00 |
June | 0.120526E+11 | 0.119669E+10 | 0.106423E+11 | 0.436199E+10 | 0.628027E+10 | 0.00 | 0.00 |
July | 0.122812E+11 | 0.133690E+10 | 0.105953E+11 | 0.461426E+10 | 0.598103E+10 | 0.00 | 0.00 |
August | 0.125371E+11 | 0.195119E+10 | 0.109725E+11 | 0.604711E+10 | 0.492539E+10 | 0.00 | 0.00 |
September | 0.896056E+10 | 0.322699E+10 | 0.858170E+10 | 0.516834E+10 | 0.341336E+10 | 0.00 | 0.00 |
October | 0.580368E+10 | 0.544991E+10 | 0.638482E+10 | 0.405099E+10 | 0.233383E+10 | 0.00 | 0.00 |
November | 0.221121E+10 | 0.942813E+10 | 0.331289E+10 | 0.231325E+10 | 0.999636E+09 | 0.00 | 0.00 |
December | 0.110340E+09 | 0.116944E+11 | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100483E+12 | 0.651578E+11 | 0.975737E+11 | 0.558498E+11 | 0.417240E+11 | 0.00 | 0.00 |
Minimum of Months | 0.110340E+09 | 0.119669E+10 | 0.607667E+09 | 0.428322E+09 | 0.179346E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151569E+11 | 0.116944E+11 | 0.141354E+11 | 0.879367E+10 | 0.628027E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.775227E+10 | 0.156027E+09 | 27843188.30 | 0.128184E+09 | 0.00 | 0.00 |
February | 0.175694E+09 | 0.595723E+10 | 0.831928E+09 | 0.289287E+09 | 0.542642E+09 | 0.00 | 0.00 |
March | 0.158498E+10 | 0.475064E+10 | 0.276458E+10 | 0.118846E+10 | 0.157612E+10 | 0.00 | 0.00 |
April | 0.601337E+10 | 0.264412E+10 | 0.634847E+10 | 0.328983E+10 | 0.305865E+10 | 0.00 | 0.00 |
May | 0.641142E+10 | 0.142130E+10 | 0.637864E+10 | 0.290485E+10 | 0.347378E+10 | 0.00 | 0.00 |
June | 0.732189E+10 | 0.768854E+09 | 0.676516E+10 | 0.288450E+10 | 0.388067E+10 | 0.00 | 0.00 |
July | 0.638939E+10 | 0.865218E+09 | 0.584917E+10 | 0.221259E+10 | 0.363657E+10 | 0.00 | 0.00 |
August | 0.500532E+10 | 0.126345E+10 | 0.480737E+10 | 0.203570E+10 | 0.277168E+10 | 0.00 | 0.00 |
September | 0.232872E+10 | 0.215775E+10 | 0.281556E+10 | 0.117904E+10 | 0.163651E+10 | 0.00 | 0.00 |
October | 0.444956E+09 | 0.414181E+10 | 0.113942E+10 | 0.342551E+09 | 0.796868E+09 | 0.00 | 0.00 |
November | 50901597.35 | 0.712926E+10 | 0.441177E+09 | 0.160295E+09 | 0.280882E+09 | 0.00 | 0.00 |
December | 0.00 | 0.827417E+10 | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.357266E+11 | 0.471261E+11 | 0.383384E+11 | 0.165193E+11 | 0.218192E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.768854E+09 | 40927642.74 | 4302241.72 | 36625401.02 | 0.00 | 0.00 |
Maximum of Months | 0.732189E+10 | 0.827417E+10 | 0.676516E+10 | 0.328983E+10 | 0.388067E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.480500E+11 | -0.469432E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.110678E+10 | 58.98 | 0.00 | 0.00 |
February | 0.436362E+11 | -0.426571E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -979075030.6 | 58.97 | 0.00 | 0.00 |
March | 0.512500E+11 | -0.501895E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.106050E+10 | 58.97 | 0.00 | 0.00 |
April | 0.464986E+11 | -0.455021E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -996503189.7 | 58.97 | 0.00 | 0.00 |
May | 0.492548E+11 | -0.482288E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102601E+10 | 58.97 | 0.00 | 0.00 |
June | 0.470503E+11 | -0.460571E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993123099.8 | 58.99 | 0.00 | 0.00 |
July | 0.431550E+11 | -0.421352E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101976E+10 | 58.98 | 0.00 | 0.00 |
August | 0.460391E+11 | -0.450151E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102408E+10 | 58.99 | 0.00 | 0.00 |
September | 0.416739E+11 | -0.406834E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990490842.7 | 58.99 | 0.00 | 0.00 |
October | 0.438327E+11 | -0.428017E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103095E+10 | 58.98 | 0.00 | 0.00 |
November | 0.445477E+11 | -0.435095E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.103827E+10 | 58.98 | 0.00 | 0.00 |
December | 0.461876E+11 | -0.450941E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.109349E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.551176E+12 | -0.538817E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.123590E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.416739E+11 | -0.501895E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.110678E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.512500E+11 | -0.406834E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -979075030.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131220E+12 | 162641.91 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.984526E+11 | 156012.52 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.851535E+11 | 136350.15 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209238E+11 | 111244.03 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252582E+10 | 40664.59 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4479395.19 | 2969.85 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.366940E+09 | 34408.38 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116258E+11 | 59148.52 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.516321E+11 | 104910.75 | 31-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120015E+12 | 139437.09 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137570E+12 | 152433.11 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137570E+12 | 162641.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201726E+09 | 36224.35 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201726E+09 | 36224.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.654755E+10 | 14276.23 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345278E+10 | 14928.11 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153548E+10 | 15476.69 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89153437.96 | 15362.77 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.542198E+09 | 15252.81 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330564E+10 | 14208.92 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521008E+10 | 14209.40 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654755E+10 | 15476.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.656383E+10 | 16689.00 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370842E+10 | 17113.11 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165471E+10 | 17159.98 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196449E+09 | 17113.68 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46574351.88 | 2642.26 | 28-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104627E+10 | 17068.63 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452648E+10 | 17089.75 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629500E+10 | 16646.33 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.656383E+10 | 17159.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.963980E+10 | 25898.76 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465861E+10 | 26558.68 | 11-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200967E+10 | 26592.66 | 25-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262159E+09 | 25797.00 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 447499.24 | 119.76 | 27-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114711E+09 | 4961.29 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159476E+10 | 26597.27 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.599658E+10 | 26519.99 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929504E+10 | 25832.56 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.963980E+10 | 26597.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447215E+10 | 15374.52 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176205E+10 | 15337.59 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352747E+09 | 15318.12 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3482290.53 | 547.47 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284701E+09 | 15320.27 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123201E+10 | 15321.45 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165668E+10 | 15321.91 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.976382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447215E+10 | 15374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545209E+12 | 1702475.89 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326630E+12 | 1657748.79 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131707E+12 | 1444236.93 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246752E+11 | 706647.43 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420401E+10 | 437697.53 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.379054E+09 | 147258.86 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283868E+09 | 77721.11 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.287194E+10 | 508228.28 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131442E+11 | 610107.88 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452261E+11 | 845605.16 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491394E+12 | 1492642.65 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732287E+12 | 1616577.15 | 15-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231801E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.283868E+09 | 77721.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.732287E+12 | 1702475.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377899E+11 | 620823.28 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128942E+11 | 620439.63 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119474E+10 | 616856.08 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280036E+09 | 282020.83 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154606E+10 | 620607.16 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127006E+11 | 620604.94 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213003E+11 | 620896.83 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377899E+11 | 620896.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130421E+12 | 137540.53 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.881743E+11 | 131662.84 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585513E+11 | 133057.15 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146379E+11 | 142042.20 | 13-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5731484.68 | 25274.57 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30927211.28 | 14953.45 | 31-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237111E+10 | 141623.62 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.372367E+11 | 131671.69 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.966538E+11 | 131682.72 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127076E+12 | 131999.87 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130421E+12 | 142042.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108600E+12 | 192902.66 | 30-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703691E+11 | 192971.52 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393612E+11 | 192589.65 | 31-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113516E+11 | 192630.72 | 03-APR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191144E+09 | 40270.97 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147911E+09 | 43407.20 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410020E+10 | 175889.05 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358304E+11 | 192562.23 | 27-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847239E+11 | 193016.16 | 24-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107376E+12 | 192970.12 | 04-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108600E+12 | 193016.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144419E+12 | 291388.46 | 30-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772344E+11 | 291491.20 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427251E+11 | 290895.15 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117271E+11 | 290662.01 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.500012E+09 | 73225.01 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197743E+09 | 35246.89 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.423984E+10 | 198054.73 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399220E+11 | 290769.78 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101730E+12 | 291558.24 | 24-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151036E+12 | 291489.96 | 04-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573731E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151036E+12 | 291558.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.987997E+11 | 190861.43 | 30-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644672E+11 | 190926.55 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437493E+11 | 190530.52 | 03-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.958140E+10 | 190383.85 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.472849E+09 | 63106.73 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132368E+09 | 20891.72 | 30-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.454954E+10 | 127919.28 | 25-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349262E+11 | 190520.11 | 27-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718851E+11 | 190947.26 | 20-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.916838E+11 | 190897.98 | 11-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.987997E+11 | 190947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.683248E+11 | 182857.60 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437993E+11 | 172591.81 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209258E+11 | 153098.46 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344193E+10 | 76106.53 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508250E+09 | 47924.20 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102199E+09 | 23279.18 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103696E+09 | 19278.14 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292362E+09 | 55417.99 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102126E+10 | 66156.79 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922211E+10 | 89846.82 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622741E+11 | 157174.53 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868200E+11 | 171044.86 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.102199E+09 | 19278.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.868200E+11 | 182857.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224460E+11 | 82241.97 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143095E+11 | 82231.05 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861842E+10 | 82249.85 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223044E+10 | 82233.30 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259623E+09 | 82518.79 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648639E+10 | 82517.91 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175381E+11 | 82212.69 | 04-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217843E+11 | 82237.14 | 26-DEC-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.936728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224460E+11 | 82518.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218824E+11 | 17502.00 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167105E+11 | 16615.37 | 09-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134473E+11 | 16612.81 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.480156E+10 | 16555.80 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166773E+09 | 16424.05 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100755E+09 | 16425.56 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183641E+10 | 16617.35 | 25-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.984346E+10 | 16619.62 | 02-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186012E+11 | 16564.78 | 02-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222543E+11 | 16565.31 | 26-DEC-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222543E+11 | 17502.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160330E+11 | 19394.32 | 28-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115216E+11 | 19391.81 | 01-FEB-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.767079E+10 | 19394.79 | 04-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273382E+10 | 19396.91 | 10-APR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117431E+09 | 19193.29 | 27-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62417133.38 | 11555.18 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138111E+10 | 19323.10 | 28-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.698522E+10 | 19442.27 | 13-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137126E+11 | 19390.84 | 10-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163738E+11 | 19342.55 | 02-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163738E+11 | 19442.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225822E+11 | 30699.80 | 20-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140148E+11 | 30700.26 | 03-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.925257E+10 | 30692.57 | 08-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330882E+10 | 30679.21 | 03-APR-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.380015E+09 | 27830.18 | 27-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8968814.70 | 3042.50 | 26-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1705038.48 | 1896.03 | 06-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150726E+09 | 17767.82 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184046E+10 | 30574.10 | 30-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.884969E+10 | 30681.51 | 31-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180701E+11 | 30699.52 | 15-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240342E+11 | 30691.29 | 30-DEC-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1705038.48 | 1896.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240342E+11 | 30700.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151793E+11 | 20552.58 | 07-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106225E+11 | 20549.56 | 15-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.805477E+10 | 20506.97 | 08-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241503E+10 | 20497.58 | 01-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235166E+09 | 18504.67 | 27-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1383861.13 | 449.78 | 26-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101895E+09 | 11395.60 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157813E+10 | 20471.53 | 30-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.664614E+10 | 20499.57 | 31-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118009E+11 | 20501.78 | 17-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142039E+11 | 20493.02 | 07-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.708392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151793E+11 | 20552.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102820E+11 | 45556.14 | 12-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422015E+10 | 47401.33 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.801708E+09 | 32199.03 | 01-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154157E+10 | 24677.98 | 30-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527174E+10 | 29789.67 | 15-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102820E+11 | 47401.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 835.83 | 835.83 | 0.40 | 27-JAN-05:17 | 0.40 | 0.00 |
February | 0.00 | 0.00 | 1280.14 | 1280.14 | 0.29 | 13-FEB-07:00 | 0.29 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.100555E+09 | 0.100555E+09 | 12105.27 | 20-APR-14:00 | 12105.27 | 0.00 |
May | 0.00 | 0.00 | 0.100888E+11 | 0.100888E+11 | 83219.76 | 31-MAY-16:00 | 83219.76 | 0.00 |
June | 0.00 | 0.00 | 0.467512E+11 | 0.466795E+11 | 126302.19 | 30-JUN-14:30 | 126302.19 | 0.14 |
July | 0.00 | 0.00 | 0.625277E+11 | 0.623014E+11 | 134960.57 | 03-JUL-15:00 | 59053.81 | 0.41 |
August | 0.00 | 0.00 | 0.357238E+11 | 0.357216E+11 | 128418.49 | 11-AUG-15:30 | 128418.49 | 0.28 |
September | 0.00 | 0.00 | 0.617268E+09 | 0.617268E+09 | 25562.88 | 07-SEP-16:00 | 25562.88 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 613.74 | 613.74 | 0.39 | 29-DEC-06:03 | 0.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155809E+12 | 0.155509E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.625277E+11 | 0.623014E+11 | 134960.57 | 128418.49 | 0.41 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 22084.72 | 22084.72 | 0.93 | 03-JAN-05:01 | 0.93 | 0.00 |
February | 0.00 | 0.00 | 11979609.42 | 11979609.42 | 38717.21 | 15-FEB-13:20 | 38717.21 | 0.00 |
March | 0.00 | 0.00 | 0.188222E+09 | 0.188222E+09 | 48434.94 | 31-MAR-15:57 | 48434.94 | 0.00 |
April | 0.00 | 0.00 | 0.847543E+09 | 0.847543E+09 | 102730.84 | 20-APR-14:00 | 102730.84 | 0.00 |
May | 0.00 | 0.00 | 0.923863E+11 | 0.923863E+11 | 792332.25 | 31-MAY-16:00 | 792332.25 | 0.00 |
June | 0.00 | 0.00 | 0.408249E+12 | 0.407406E+12 | 1195014.86 | 30-JUN-12:20 | 1094779.40 | 0.13 |
July | 0.00 | 0.00 | 0.521039E+12 | 0.519471E+12 | 1166304.76 | 21-JUL-14:50 | 1166304.76 | 0.36 |
August | 0.00 | 0.00 | 0.282990E+12 | 0.282990E+12 | 1129446.59 | 11-AUG-15:40 | 1129446.59 | 0.24 |
September | 0.00 | 0.00 | 0.540391E+10 | 0.540391E+10 | 231015.14 | 07-SEP-16:00 | 231015.14 | 0.00 |
October | 0.00 | 0.00 | 0.120451E+09 | 0.120451E+09 | 46930.22 | 12-OCT-11:15 | 46930.22 | 0.00 |
November | 0.00 | 0.00 | 13209.60 | 13209.60 | 1.09 | 06-NOV-06:01 | 1.09 | 0.00 |
December | 0.00 | 0.00 | 24437.01 | 24437.01 | 18.21 | 23-DEC-14:10 | 18.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131124E+13 | 0.130882E+13 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 13209.60 | 13209.60 | 0.93 | 0.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.521039E+12 | 0.519471E+12 | 1195014.86 | 1166304.76 | 0.36 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 183798.09 | 183798.09 | 416.78 | 14-JAN-05:28 | 416.78 | 0.00 |
February | 0.00 | 0.00 | 281578.16 | 281578.16 | 792.76 | 01-FEB-05:43 | 792.76 | 0.00 |
March | 0.00 | 0.00 | 1698137.75 | 1698137.75 | 1475.44 | 22-MAR-13:50 | 1475.44 | 0.00 |
April | 0.00 | 0.00 | 28275353.59 | 28275353.59 | 5905.27 | 20-APR-14:00 | 5905.27 | 0.00 |
May | 0.00 | 0.00 | 0.893798E+10 | 0.893798E+10 | 86726.81 | 31-MAY-16:00 | 86726.81 | 0.00 |
June | 0.00 | 0.00 | 0.422466E+11 | 0.421502E+11 | 134557.77 | 30-JUN-12:30 | 125450.85 | 0.12 |
July | 0.00 | 0.00 | 0.541282E+11 | 0.539879E+11 | 133970.78 | 21-JUL-14:50 | 133970.78 | 0.35 |
August | 0.00 | 0.00 | 0.283909E+11 | 0.283909E+11 | 124407.74 | 11-AUG-15:40 | 124407.74 | 0.23 |
September | 0.00 | 0.00 | 0.406741E+09 | 0.406741E+09 | 19758.12 | 07-SEP-16:00 | 19758.12 | 0.00 |
October | 0.00 | 0.00 | 334416.33 | 334416.33 | 63.94 | 12-OCT-13:30 | 63.94 | 0.00 |
November | 0.00 | 0.00 | 42848.71 | 42848.71 | 377.97 | 10-NOV-05:27 | 377.97 | 0.00 |
December | 0.00 | 0.00 | 269621.01 | 269621.01 | 1013.41 | 02-DEC-06:01 | 1013.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134141E+12 | 0.133905E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 42848.71 | 42848.71 | 63.94 | 63.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.541282E+11 | 0.539879E+11 | 134557.77 | 133970.78 | 0.35 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 42566.04 | 42566.04 | 70.94 | 08-FEB-16:40 | 70.94 | 0.00 |
March | 0.00 | 0.00 | 24481.52 | 24481.52 | 40.80 | 23-MAR-06:30 | 40.80 | 0.00 |
April | 0.00 | 0.00 | 199680.91 | 199680.91 | 95.48 | 05-APR-10:20 | 95.48 | 0.00 |
May | 0.00 | 0.00 | 0.298808E+10 | 0.298808E+10 | 42737.49 | 31-MAY-16:00 | 42737.49 | 0.00 |
June | 0.00 | 0.00 | 0.207306E+11 | 0.207021E+11 | 60815.04 | 30-JUN-15:00 | 60815.04 | 0.09 |
July | 0.00 | 0.00 | 0.311589E+11 | 0.310149E+11 | 73032.05 | 25-JUL-03:02 | 34328.45 | 0.26 |
August | 0.00 | 0.00 | 0.170481E+11 | 0.169987E+11 | 67487.64 | 27-AUG-17:11 | 67487.64 | 0.18 |
September | 0.00 | 0.00 | 37076608.24 | 37076608.24 | 9340.50 | 07-SEP-16:00 | 9340.50 | 0.00 |
October | 0.00 | 0.00 | 68854.97 | 68854.97 | 82.08 | 23-OCT-16:30 | 82.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.719630E+11 | 0.717411E+11 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.311589E+11 | 0.310149E+11 | 73032.05 | 67487.64 | 0.26 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308382E+12 | 0.301374E+12 | 125562.17 | 26-JAN-22:02 | 122254.55 | 0.00 |
February | 0.00 | 0.00 | 0.509199E+12 | 0.495639E+12 | 220228.84 | 09-FEB-22:03 | 214157.28 | 0.00 |
March | 0.00 | 0.00 | 0.820928E+12 | 0.799671E+12 | 404018.82 | 31-MAR-24:00 | 393315.63 | 0.00 |
April | 0.00 | 0.00 | 0.104628E+13 | 0.102302E+13 | 410852.45 | 30-APR-23:00 | 399397.14 | 0.00 |
May | 0.00 | 0.00 | 0.335881E+12 | 0.328532E+12 | 216584.26 | 31-MAY-24:00 | 211828.63 | 0.00 |
June | 0.00 | 0.00 | 0.568366E+12 | 0.558265E+12 | 309107.67 | 30-JUN-24:00 | 303728.75 | 0.00 |
July | 0.00 | 0.00 | 0.837157E+12 | 0.824711E+12 | 399791.70 | 31-JUL-24:00 | 396246.76 | 0.00 |
August | 0.00 | 0.00 | 0.108894E+13 | 0.106919E+13 | 414134.03 | 30-AUG-22:00 | 401695.79 | 0.00 |
September | 0.00 | 0.00 | 0.325483E+12 | 0.317658E+12 | 216768.07 | 30-SEP-24:00 | 210865.99 | 0.00 |
October | 0.00 | 0.00 | 0.578545E+12 | 0.564661E+12 | 308706.52 | 31-OCT-24:00 | 301834.68 | 0.00 |
November | 0.00 | 0.00 | 0.791807E+12 | 0.771932E+12 | 315452.66 | 24-NOV-22:02 | 306465.37 | 0.00 |
December | 0.00 | 0.00 | 0.106607E+13 | 0.103965E+13 | 410728.99 | 27-DEC-22:02 | 398080.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.827704E+13 | 0.809431E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.308382E+12 | 0.301374E+12 | 125562.17 | 122254.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108894E+13 | 0.106919E+13 | 414134.03 | 401695.79 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.106367E+10 | 0.106367E+10 | 1338.70 | 12-JAN-22:06 | 1338.70 | 0.00 |
February | 0.00 | 0.00 | 0.652315E+10 | 0.652315E+10 | 3523.91 | 09-FEB-16:00 | 3523.91 | 0.00 |
March | 0.00 | 0.00 | 0.136097E+11 | 0.136097E+11 | 7259.46 | 31-MAR-24:00 | 7259.46 | 0.00 |
April | 0.00 | 0.00 | 0.196600E+11 | 0.196600E+11 | 8967.10 | 22-APR-18:40 | 8967.10 | 0.00 |
May | 0.00 | 0.00 | 0.556152E+10 | 0.556136E+10 | 4051.73 | 31-MAY-24:00 | 4051.73 | 0.00 |
June | 0.00 | 0.00 | 0.107461E+11 | 0.106744E+11 | 5945.80 | 30-JUN-24:00 | 5925.04 | 0.00 |
July | 0.00 | 0.00 | 0.162565E+11 | 0.161081E+11 | 7860.18 | 31-JUL-23:45 | 7842.17 | 0.00 |
August | 0.00 | 0.00 | 0.210643E+11 | 0.209451E+11 | 8929.33 | 27-AUG-18:53 | 8929.33 | 0.00 |
September | 0.00 | 0.00 | 0.483224E+10 | 0.481576E+10 | 3473.68 | 30-SEP-24:00 | 3473.68 | 0.00 |
October | 0.00 | 0.00 | 0.897089E+10 | 0.897062E+10 | 4984.62 | 31-OCT-24:00 | 4984.62 | 0.00 |
November | 0.00 | 0.00 | 0.121751E+11 | 0.121751E+11 | 5293.77 | 03-NOV-01:40 | 5293.77 | 0.00 |
December | 0.00 | 0.00 | 0.172807E+11 | 0.172807E+11 | 7087.54 | 24-DEC-18:00 | 7087.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137744E+12 | 0.137388E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.106367E+10 | 0.106367E+10 | 1338.70 | 1338.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210643E+11 | 0.209451E+11 | 8967.10 | 8967.10 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.900516E+09 | 0.900516E+09 | 7800.23 | 27-JAN-22:03 | 7800.23 | 0.00 |
February | 0.00 | 0.00 | 0.425391E+11 | 0.425391E+11 | 29887.62 | 16-FEB-16:10 | 29887.62 | 0.00 |
March | 0.00 | 0.00 | 0.110465E+12 | 0.110465E+12 | 63727.69 | 31-MAR-23:20 | 63727.69 | 0.00 |
April | 0.00 | 0.00 | 0.175164E+12 | 0.175164E+12 | 83929.28 | 20-APR-18:50 | 83929.28 | 0.00 |
May | 0.00 | 0.00 | 0.478894E+11 | 0.478876E+11 | 37967.41 | 31-MAY-24:00 | 37967.41 | 0.00 |
June | 0.00 | 0.00 | 0.100276E+12 | 0.995636E+11 | 57211.12 | 30-JUN-24:00 | 57002.52 | 0.00 |
July | 0.00 | 0.00 | 0.153349E+12 | 0.151872E+12 | 76049.94 | 31-JUL-23:53 | 75862.36 | 0.00 |
August | 0.00 | 0.00 | 0.197946E+12 | 0.196755E+12 | 83561.29 | 27-AUG-18:46 | 83561.29 | 0.00 |
September | 0.00 | 0.00 | 0.363518E+11 | 0.361940E+11 | 27307.48 | 30-SEP-23:50 | 27307.48 | 0.00 |
October | 0.00 | 0.00 | 0.653320E+11 | 0.653289E+11 | 39135.27 | 31-OCT-23:20 | 39135.27 | 0.00 |
November | 0.00 | 0.00 | 0.908169E+11 | 0.908169E+11 | 45662.33 | 08-NOV-15:50 | 45662.33 | 0.00 |
December | 0.00 | 0.00 | 0.137145E+12 | 0.137145E+12 | 60234.94 | 21-DEC-22:05 | 60234.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115817E+13 | 0.115463E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.900516E+09 | 0.900516E+09 | 7800.23 | 7800.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197946E+12 | 0.196755E+12 | 83929.28 | 83929.28 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 97286.95 | 97286.95 | 41.31 | 19-JAN-17:00 | 41.31 | 0.00 |
February | 0.00 | 0.00 | 0.241999E+10 | 0.241999E+10 | 2694.33 | 09-FEB-16:00 | 2694.33 | 0.00 |
March | 0.00 | 0.00 | 0.890518E+10 | 0.890518E+10 | 5455.37 | 31-MAR-23:10 | 5455.37 | 0.00 |
April | 0.00 | 0.00 | 0.160442E+11 | 0.160442E+11 | 8388.92 | 20-APR-18:50 | 8388.92 | 0.00 |
May | 0.00 | 0.00 | 0.414724E+10 | 0.414707E+10 | 3750.15 | 31-MAY-24:00 | 3750.15 | 0.00 |
June | 0.00 | 0.00 | 0.985563E+10 | 0.978446E+10 | 5686.73 | 30-JUN-24:00 | 5665.70 | 0.00 |
July | 0.00 | 0.00 | 0.151967E+11 | 0.150492E+11 | 7572.79 | 31-JUL-23:53 | 7554.01 | 0.00 |
August | 0.00 | 0.00 | 0.194436E+11 | 0.193247E+11 | 8380.44 | 27-AUG-18:42 | 8380.44 | 0.00 |
September | 0.00 | 0.00 | 0.238044E+10 | 0.236563E+10 | 2358.66 | 02-SEP-17:57 | 2358.66 | 0.00 |
October | 0.00 | 0.00 | 0.428930E+10 | 0.428903E+10 | 3523.51 | 03-OCT-16:00 | 3523.51 | 0.00 |
November | 0.00 | 0.00 | 0.687256E+10 | 0.687256E+10 | 4072.89 | 08-NOV-15:50 | 4072.89 | 0.00 |
December | 0.00 | 0.00 | 0.116224E+11 | 0.116224E+11 | 5594.09 | 19-DEC-22:02 | 5594.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101177E+12 | 0.100824E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 97286.95 | 97286.95 | 41.31 | 41.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194436E+11 | 0.193247E+11 | 8388.92 | 8388.92 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 518426.55 | 3374210.47 | 12-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 355312.81 | 3364590.38 | 27-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 176344.15 | 2776990.09 | 01-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 43061.67 | 1524034.95 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 3433.97 | 638465.87 | 27-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 194.37 | 180668.17 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 141.00 | 94400.84 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 1667.37 | 717739.53 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18380.37 | 1282815.48 | 25-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 110212.98 | 2006102.26 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 435181.63 | 2772887.85 | 27-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 585286.05 | 3053381.19 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 186614.17 | ||||
Minimum of Months | 0.00 | 0.00 | 141.00 | 94400.84 | ||
Maximum of Months | 0.00 | 0.00 | 585286.05 | 3374210.47 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 556.97 | 22682.69 | 20-JAN-05:20 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 300.15 | 24109.01 | 15-FEB-13:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 409.84 | 71720.85 | 31-MAR-15:57 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1205.77 | 226556.55 | 20-APR-14:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83001.57 | 1147094.83 | 31-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 312195.71 | 1592209.27 | 21-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353421.13 | 1556821.21 | 21-JUL-13:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 218024.48 | 1609347.70 | 11-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 6431.72 | 574616.33 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 638.81 | 103959.23 | 13-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 337.72 | 22908.28 | 10-NOV-05:29 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.12 | 23245.19 | 02-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82078.47 | 0.00 | ||||
Minimum of Months | 241.12 | 22682.69 | 0.00 | 0.00 | ||
Maximum of Months | 353421.13 | 1609347.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.30 | 14-JAN-05:28 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 0.16 | 1254.28 | 15-FEB-13:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 28.52 | 30427.38 | 31-MAR-15:57 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 370.98 | 110504.27 | 20-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46713.77 | 1129532.45 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 218691.71 | 1606258.97 | 21-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 276654.98 | 1849949.13 | 23-JUL-16:22 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 152148.27 | 1624040.51 | 11-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 2595.99 | 306181.88 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 47.01 | 47327.40 | 12-OCT-11:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.02 | 419.03 | 10-NOV-05:27 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.12 | 1148.51 | 02-DEC-06:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 58611.34 | 0.00 | ||||
Minimum of Months | 0.00 | 0.30 | 0.00 | 0.00 | ||
Maximum of Months | 276654.98 | 1849949.13 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 148991.23 | 169158.37 | 27-JAN-22:10 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 293004.94 | 348331.83 | 10-FEB-16:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 446377.56 | 598109.60 | 31-MAR-23:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 606642.39 | 762051.62 | 22-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 199978.07 | 500906.59 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 456787.64 | 1079679.44 | 30-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 688312.92 | 1402739.23 | 29-JUL-17:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 785785.23 | 1372166.70 | 11-AUG-18:00 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 182301.45 | 314378.16 | 30-SEP-24:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 309730.75 | 445613.31 | 31-OCT-23:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 436222.56 | 457732.80 | 03-NOV-21:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 573757.94 | 599612.19 | 29-DEC-22:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 428503.30 | 0.00 | ||||
Minimum of Months | 148991.23 | 169158.37 | 0.00 | 0.00 | ||
Maximum of Months | 785785.23 | 1402739.23 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 18918.71 | 63727.41 | 09-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 19024.95 | 63726.50 | 15-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 20128.93 | 63802.70 | 31-MAR-11:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18948.81 | 63877.90 | 14-APR-11:23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19399.04 | 63726.90 | 09-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19162.49 | 62159.15 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17130.64 | 59634.41 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18202.48 | 57876.98 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 17102.20 | 57510.90 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17385.40 | 59169.88 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18183.96 | 61462.34 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 18232.54 | 63716.77 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 18482.06 | ||||
Minimum of Months | 0.00 | 0.00 | 17102.20 | 57510.90 | ||
Maximum of Months | 0.00 | 0.00 | 20128.93 | 63877.90 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.45 | 21847.23 | 10-JAN-06:40 | 421.71 | 112617.03 | 10-JAN-06:50 |
February | 8.64 | 19198.70 | 24-FEB-02:20 | 327.17 | 114501.24 | 01-FEB-06:30 |
March | 22.49 | 34146.15 | 30-MAR-14:30 | 343.71 | 125613.97 | 24-MAR-04:07 |
April | 223.33 | 142085.70 | 20-APR-14:30 | 517.65 | 114096.35 | 07-APR-19:00 |
May | 51279.06 | 1883922.75 | 31-MAY-15:10 | 551.25 | 89810.55 | 27-MAY-06:20 |
June | 251206.30 | 2367601.32 | 30-JUN-12:20 | 203.79 | 53270.36 | 01-JUN-18:30 |
July | 322729.74 | 2177630.78 | 03-JUL-15:00 | 287.09 | 55248.75 | 06-JUL-07:40 |
August | 179506.51 | 2165175.65 | 11-AUG-14:20 | 457.01 | 65625.56 | 31-AUG-15:20 |
September | 2793.30 | 349937.38 | 07-SEP-16:00 | 651.33 | 101364.26 | 28-SEP-11:00 |
October | 27.60 | 41685.20 | 12-OCT-11:50 | 583.75 | 110753.10 | 18-OCT-04:01 |
November | 20.99 | 21360.48 | 12-NOV-23:10 | 309.78 | 132518.81 | 10-NOV-04:01 |
December | 13.33 | 21717.13 | 26-DEC-07:00 | 220.75 | 130514.97 | 16-DEC-06:03 |
Annual Sum or Average | 67916.03 | 406.74 | ||||
Minimum of Months | 8.64 | 19198.70 | 203.79 | 53270.36 | ||
Maximum of Months | 322729.74 | 2367601.32 | 651.33 | 132518.81 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146358E+11 | 0.80 | 10587.24 | 02-JAN-06:01 | 1.51 |
February | 0.134161E+11 | 0.81 | 10587.24 | 01-FEB-06:02 | 1.55 |
March | 0.160155E+11 | 0.87 | 10587.24 | 01-MAR-06:02 | 1.55 |
April | 0.154289E+11 | 0.87 | 10587.24 | 01-APR-05:01 | 1.55 |
May | 0.163499E+11 | 0.89 | 10587.24 | 01-MAY-03:02 | 1.54 |
June | 0.166402E+11 | 0.93 | 10587.24 | 01-JUN-03:02 | 1.54 |
July | 0.164327E+11 | 0.89 | 10587.24 | 01-JUL-03:02 | 1.53 |
August | 0.179987E+11 | 0.97 | 10587.24 | 01-AUG-03:02 | 1.53 |
September | 0.164621E+11 | 0.92 | 10587.24 | 01-SEP-03:02 | 1.53 |
October | 0.157062E+11 | 0.85 | 10587.24 | 02-OCT-03:02 | 1.54 |
November | 0.141784E+11 | 0.80 | 10587.24 | 01-NOV-05:01 | 1.55 |
December | 0.144833E+11 | 0.79 | 10587.24 | 01-DEC-06:01 | 1.55 |
Annual Sum or Average | 0.187748E+12 | 0.87 | |||
Minimum of Months | 0.134161E+11 | 0.79 | 10587.24 | 1.51 | |
Maximum of Months | 0.179987E+11 | 0.97 | 10587.24 | 1.55 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.378811E+10 | 0.34 | 5905.55 | 02-JAN-05:01 | 0.85 |
February | 0.349640E+10 | 0.32 | 15264.00 | 14-FEB-06:02 | 1.49 |
March | 0.533915E+10 | 0.38 | 15264.00 | 09-MAR-06:01 | 1.49 |
April | 0.894188E+10 | 0.50 | 17798.00 | 21-APR-15:30 | 1.64 |
May | 0.104093E+11 | 0.54 | 19711.24 | 31-MAY-05:02 | 1.74 |
June | 0.135446E+11 | 0.65 | 22441.18 | 08-JUN-05:02 | 1.89 |
July | 0.140955E+11 | 0.66 | 22441.18 | 11-JUL-05:02 | 1.88 |
August | 0.141869E+11 | 0.68 | 22146.51 | 03-AUG-05:03 | 1.86 |
September | 0.681859E+10 | 0.42 | 13445.54 | 01-SEP-03:02 | 1.37 |
October | 0.531766E+10 | 0.36 | 15264.00 | 26-OCT-05:01 | 1.49 |
November | 0.380348E+10 | 0.32 | 14743.72 | 02-NOV-05:01 | 1.46 |
December | 0.365530E+10 | 0.31 | 3776.28 | 26-DEC-17:00 | 0.67 |
Annual Sum or Average | 0.933969E+11 | 0.46 | |||
Minimum of Months | 0.349640E+10 | 0.31 | 3776.28 | 0.67 | |
Maximum of Months | 0.141869E+11 | 0.68 | 22441.18 | 1.89 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.456403E+11 | 0.41 | 59758.09 | 02-JAN-04:01 | 0.89 |
February | 0.394288E+11 | 0.40 | 59758.09 | 01-FEB-06:02 | 0.89 |
March | 0.428496E+11 | 0.36 | 210551.71 | 22-MAR-16:05 | 1.90 |
April | 0.591497E+11 | 0.41 | 210551.71 | 11-APR-10:27 | 1.91 |
May | 0.878519E+11 | 0.50 | 192731.88 | 11-MAY-06:17 | 1.80 |
June | 0.112248E+12 | 0.59 | 210551.71 | 20-JUN-05:03 | 1.89 |
July | 0.105606E+12 | 0.55 | 210551.71 | 12-JUL-05:02 | 1.90 |
August | 0.951729E+11 | 0.52 | 184921.24 | 10-AUG-16:00 | 1.75 |
September | 0.534919E+11 | 0.38 | 210551.71 | 28-SEP-10:07 | 1.90 |
October | 0.409334E+11 | 0.34 | 210551.71 | 03-OCT-10:17 | 1.90 |
November | 0.399591E+11 | 0.38 | 59758.09 | 06-NOV-06:01 | 0.89 |
December | 0.440180E+11 | 0.40 | 59758.09 | 04-DEC-05:01 | 0.89 |
Annual Sum or Average | 0.766350E+12 | 0.44 | |||
Minimum of Months | 0.394288E+11 | 0.34 | 59758.09 | 0.89 | |
Maximum of Months | 0.112248E+12 | 0.59 | 210551.71 | 1.91 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.540802E+10 | 0.47 | 5809.49 | 01-JAN-22:42 | 0.84 |
February | 0.466268E+10 | 0.45 | 5809.49 | 01-FEB-05:01 | 0.84 |
March | 0.488633E+10 | 0.43 | 5809.49 | 01-MAR-05:01 | 0.85 |
April | 0.485712E+10 | 0.39 | 22142.20 | 12-APR-16:05 | 1.89 |
May | 0.702151E+10 | 0.43 | 17738.54 | 31-MAY-15:20 | 1.64 |
June | 0.104430E+11 | 0.54 | 19412.06 | 20-JUN-15:30 | 1.73 |
July | 0.986539E+10 | 0.50 | 20780.63 | 12-JUL-15:20 | 1.81 |
August | 0.805492E+10 | 0.45 | 22142.20 | 30-AUG-09:55 | 1.89 |
September | 0.387844E+10 | 0.32 | 22142.20 | 07-SEP-10:17 | 1.89 |
October | 0.428832E+10 | 0.38 | 5809.49 | 02-OCT-04:01 | 0.84 |
November | 0.505321E+10 | 0.46 | 5809.49 | 01-NOV-04:01 | 0.84 |
December | 0.551169E+10 | 0.48 | 5809.49 | 01-DEC-05:01 | 0.85 |
Annual Sum or Average | 0.739306E+11 | 0.44 | |||
Minimum of Months | 0.387844E+10 | 0.32 | 5809.49 | 0.84 | |
Maximum of Months | 0.104430E+11 | 0.54 | 22142.20 | 1.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.960304E+11 | 1.37 | 35853.65 | 01-JAN-00:02 | 1.37 |
February | 0.867371E+11 | 1.37 | 35853.65 | 01-FEB-00:03 | 1.37 |
March | 0.960304E+11 | 1.37 | 35853.65 | 01-MAR-00:10 | 1.37 |
April | 0.929326E+11 | 1.37 | 35853.65 | 01-APR-00:10 | 1.37 |
May | 0.960304E+11 | 1.37 | 35853.65 | 01-MAY-00:10 | 1.37 |
June | 0.929326E+11 | 1.37 | 35853.65 | 01-JUN-00:40 | 1.37 |
July | 0.960304E+11 | 1.37 | 35853.65 | 01-JUL-00:10 | 1.37 |
August | 0.960304E+11 | 1.37 | 35853.65 | 01-AUG-00:02 | 1.37 |
September | 0.929326E+11 | 1.37 | 35853.65 | 01-SEP-00:30 | 1.37 |
October | 0.960304E+11 | 1.37 | 35853.65 | 01-OCT-00:10 | 1.37 |
November | 0.929326E+11 | 1.37 | 35853.65 | 01-NOV-00:20 | 1.37 |
December | 0.960304E+11 | 1.37 | 35853.65 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.113068E+13 | 1.37 | |||
Minimum of Months | 0.867371E+11 | 1.37 | 35853.65 | 1.37 | |
Maximum of Months | 0.960304E+11 | 1.37 | 35853.65 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153972E+10 | 0.94 | 574.87 | 01-JAN-00:02 | 0.93 |
February | 0.139072E+10 | 0.94 | 574.87 | 01-FEB-00:03 | 0.94 |
March | 0.153972E+10 | 0.94 | 574.87 | 01-MAR-00:10 | 0.94 |
April | 0.149005E+10 | 0.93 | 574.87 | 01-APR-00:10 | 0.94 |
May | 0.153972E+10 | 0.93 | 574.87 | 01-MAY-00:10 | 0.93 |
June | 0.149005E+10 | 0.93 | 574.87 | 01-JUN-00:10 | 0.93 |
July | 0.153972E+10 | 0.93 | 574.87 | 01-JUL-00:10 | 0.93 |
August | 0.153972E+10 | 0.93 | 574.87 | 01-AUG-00:02 | 0.93 |
September | 0.149005E+10 | 0.93 | 574.87 | 01-SEP-00:10 | 0.93 |
October | 0.153972E+10 | 0.93 | 574.87 | 01-OCT-00:10 | 0.93 |
November | 0.149005E+10 | 0.94 | 574.87 | 01-NOV-00:10 | 0.94 |
December | 0.153972E+10 | 0.94 | 574.87 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.181290E+11 | 0.93 | |||
Minimum of Months | 0.139072E+10 | 0.93 | 574.87 | 0.93 | |
Maximum of Months | 0.153972E+10 | 0.94 | 574.87 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147773E+11 | 0.94 | 5517.21 | 01-JAN-00:02 | 0.93 |
February | 0.133472E+11 | 0.94 | 5517.21 | 01-FEB-00:03 | 0.94 |
March | 0.147773E+11 | 0.94 | 5517.21 | 01-MAR-00:10 | 0.94 |
April | 0.143006E+11 | 0.93 | 5517.21 | 01-APR-00:10 | 0.94 |
May | 0.147773E+11 | 0.93 | 5517.21 | 01-MAY-00:10 | 0.93 |
June | 0.143006E+11 | 0.93 | 5517.21 | 01-JUN-00:10 | 0.93 |
July | 0.147773E+11 | 0.93 | 5517.21 | 01-JUL-00:10 | 0.93 |
August | 0.147773E+11 | 0.93 | 5517.21 | 01-AUG-00:02 | 0.93 |
September | 0.143006E+11 | 0.93 | 5517.21 | 01-SEP-00:10 | 0.93 |
October | 0.147773E+11 | 0.93 | 5517.21 | 01-OCT-00:10 | 0.93 |
November | 0.143006E+11 | 0.94 | 5517.21 | 01-NOV-00:10 | 0.94 |
December | 0.147773E+11 | 0.94 | 5517.21 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.173991E+12 | 0.93 | |||
Minimum of Months | 0.133472E+11 | 0.93 | 5517.21 | 0.93 | |
Maximum of Months | 0.147773E+11 | 0.94 | 5517.21 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149177E+10 | 0.94 | 556.96 | 01-JAN-00:02 | 0.93 |
February | 0.134741E+10 | 0.94 | 556.96 | 01-FEB-00:03 | 0.94 |
March | 0.149177E+10 | 0.94 | 556.96 | 01-MAR-00:10 | 0.94 |
April | 0.144365E+10 | 0.93 | 556.96 | 01-APR-00:10 | 0.94 |
May | 0.149177E+10 | 0.93 | 556.96 | 01-MAY-00:10 | 0.93 |
June | 0.144365E+10 | 0.93 | 556.96 | 01-JUN-00:10 | 0.93 |
July | 0.149177E+10 | 0.93 | 556.96 | 01-JUL-00:10 | 0.93 |
August | 0.149177E+10 | 0.93 | 556.96 | 01-AUG-00:02 | 0.93 |
September | 0.144365E+10 | 0.93 | 556.96 | 01-SEP-00:10 | 0.93 |
October | 0.149177E+10 | 0.93 | 556.96 | 01-OCT-00:10 | 0.93 |
November | 0.144365E+10 | 0.94 | 556.96 | 01-NOV-00:10 | 0.94 |
December | 0.149177E+10 | 0.94 | 556.96 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.175644E+11 | 0.93 | |||
Minimum of Months | 0.134741E+10 | 0.93 | 556.96 | 0.93 | |
Maximum of Months | 0.149177E+10 | 0.94 | 556.96 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.581123E+10 | 0.523011E+10 | 8971.74 | 12-JAN-07:10 | 8074.57 | 8074.57 | 53.81 | 23.84 |
February | 0.367189E+10 | 0.330470E+10 | 9072.87 | 27-FEB-07:10 | 8165.58 | 8165.58 | 52.95 | 24.97 |
March | 0.206909E+10 | 0.186218E+10 | 8395.82 | 01-MAR-07:08 | 7556.24 | 7556.24 | 50.53 | 17.99 |
April | 0.488120E+09 | 0.439308E+09 | 6259.44 | 03-APR-05:03 | 5633.50 | 5633.50 | 45.70 | 9.31 |
May | 39362079.24 | 35425871.31 | 2517.92 | 27-MAY-06:10 | 2266.13 | 2266.13 | 28.89 | 2.88 |
June | 2086160.24 | 1877544.22 | 729.63 | 02-JUN-06:10 | 656.67 | 656.67 | 25.59 | 0.77 |
July | 1581712.43 | 1423541.19 | 392.39 | 17-JUL-06:10 | 353.16 | 353.16 | 26.39 | 0.41 |
August | 18960889.51 | 17064800.56 | 2792.54 | 31-AUG-06:10 | 2513.29 | 2513.29 | 28.95 | 3.24 |
September | 0.202206E+09 | 0.181985E+09 | 4605.73 | 25-SEP-05:01 | 4145.15 | 4145.15 | 30.63 | 5.97 |
October | 0.127936E+10 | 0.115142E+10 | 7328.88 | 23-OCT-05:01 | 6596.00 | 6596.00 | 43.60 | 12.50 |
November | 0.477251E+10 | 0.429526E+10 | 8517.19 | 27-NOV-07:04 | 7665.47 | 7665.47 | 48.69 | 19.02 |
December | 0.661271E+10 | 0.595144E+10 | 8726.45 | 15-DEC-08:00 | 7853.80 | 7853.80 | 53.32 | 21.04 |
Annual Sum or Average | 0.249691E+11 | 0.224722E+11 | ||||||
Minimum of Months | 1581712.43 | 1423541.19 | 392.39 | 353.16 | 353.16 | 25.59 | 0.41 | |
Maximum of Months | 0.661271E+10 | 0.595144E+10 | 9072.87 | 8165.58 | 8165.58 | 53.81 | 24.97 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 3979.96 | 3581.97 | 7.93 | 14-JAN-05:28 | 7.14 | 7.14 | 6.70 | 0.01 |
February | 213960.83 | 192564.75 | 669.97 | 15-FEB-13:20 | 602.98 | 602.98 | 6.71 | 1.02 |
March | 3408824.40 | 3067941.96 | 860.70 | 31-MAR-15:57 | 774.63 | 774.63 | 6.83 | 1.31 |
April | 20908744.15 | 18817869.74 | 2465.74 | 20-APR-14:00 | 2219.17 | 2219.17 | 6.96 | 3.93 |
May | 0.163525E+10 | 0.147173E+10 | 10338.24 | 31-MAY-16:00 | 9304.41 | 9304.41 | 7.25 | 22.84 |
June | 0.674126E+10 | 0.606714E+10 | 14212.40 | 21-JUN-16:00 | 12791.16 | 12791.16 | 6.76 | 49.90 |
July | 0.931491E+10 | 0.838342E+10 | 14499.27 | 21-JUL-14:40 | 13049.35 | 13049.35 | 6.76 | 54.62 |
August | 0.565436E+10 | 0.508892E+10 | 14534.72 | 11-AUG-15:40 | 13081.25 | 13081.25 | 6.76 | 55.23 |
September | 0.116513E+09 | 0.104861E+09 | 4388.02 | 07-SEP-16:00 | 3949.22 | 3949.22 | 7.53 | 7.42 |
October | 2189822.07 | 1970839.86 | 818.36 | 12-OCT-11:15 | 736.53 | 736.53 | 6.97 | 1.25 |
November | 1113.90 | 1002.51 | 7.42 | 10-NOV-05:27 | 6.68 | 6.68 | 6.97 | 0.01 |
December | 5888.68 | 5299.81 | 20.33 | 02-DEC-06:01 | 18.30 | 18.30 | 6.97 | 0.03 |
Annual Sum or Average | 0.234890E+11 | 0.211401E+11 | ||||||
Minimum of Months | 1113.90 | 1002.51 | 7.42 | 6.68 | 6.68 | 6.70 | 0.01 | |
Maximum of Months | 0.931491E+10 | 0.838342E+10 | 14534.72 | 13081.25 | 13081.25 | 7.53 | 55.23 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.833901E+09 | 0.750511E+09 | 12679.33 | 03-JAN-04:01 | 11411.40 | 11411.40 | 6.76 | 88.87 |
February | 0.405147E+09 | 0.364632E+09 | 12679.33 | 01-FEB-02:53 | 11411.40 | 11411.40 | 6.76 | 88.87 |
March | 0.531089E+09 | 0.477980E+09 | 12679.33 | 07-MAR-05:01 | 11411.40 | 11411.40 | 6.76 | 88.87 |
April | 0.701348E+09 | 0.631213E+09 | 12679.33 | 04-APR-16:05 | 11411.40 | 11411.40 | 6.80 | 88.87 |
May | 0.771224E+10 | 0.694101E+10 | 12679.33 | 01-MAY-14:40 | 11411.40 | 11411.40 | 6.76 | 88.87 |
June | 0.166373E+11 | 0.149736E+11 | 12679.33 | 01-JUN-10:10 | 11411.40 | 11411.40 | 6.93 | 88.87 |
July | 0.186744E+11 | 0.168069E+11 | 12679.33 | 01-JUL-03:02 | 11411.40 | 11411.40 | 6.79 | 88.87 |
August | 0.137938E+11 | 0.124145E+11 | 12679.33 | 01-AUG-00:02 | 11411.40 | 11411.40 | 6.82 | 88.87 |
September | 0.207776E+10 | 0.186999E+10 | 12679.33 | 01-SEP-13:30 | 11411.40 | 11411.40 | 6.76 | 88.87 |
October | 0.819302E+09 | 0.737372E+09 | 12679.33 | 02-OCT-06:20 | 11411.40 | 11411.40 | 6.76 | 88.87 |
November | 0.489265E+09 | 0.440339E+09 | 12679.33 | 06-NOV-04:01 | 11411.40 | 11411.40 | 6.76 | 88.87 |
December | 0.360660E+09 | 0.324594E+09 | 12679.33 | 02-DEC-04:05 | 11411.40 | 11411.40 | 6.76 | 88.87 |
Annual Sum or Average | 0.630362E+11 | 0.567326E+11 | ||||||
Minimum of Months | 0.360660E+09 | 0.324594E+09 | 12679.33 | 11411.40 | 11411.40 | 6.76 | 88.87 | |
Maximum of Months | 0.186744E+11 | 0.168069E+11 | 12679.33 | 11411.40 | 11411.40 | 6.93 | 88.87 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-JAN-00:02 | 3155.85 | 3155.85 | 21.30 | 14.64 |
February | 0.848292E+10 | 0.763462E+10 | 3506.50 | 01-FEB-00:03 | 3155.85 | 3155.85 | 22.99 | 14.64 |
March | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-MAR-00:10 | 3155.85 | 3155.85 | 26.63 | 14.64 |
April | 0.908884E+10 | 0.817995E+10 | 3506.50 | 01-APR-00:10 | 3155.85 | 3155.85 | 29.99 | 14.64 |
May | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-MAY-00:10 | 3155.85 | 3155.85 | 22.40 | 14.64 |
June | 0.908884E+10 | 0.817995E+10 | 3506.50 | 01-JUN-00:10 | 3155.85 | 3155.85 | 24.81 | 14.64 |
July | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-JUL-00:10 | 3155.85 | 3155.85 | 28.74 | 14.64 |
August | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-AUG-00:02 | 3155.85 | 3155.85 | 34.60 | 14.64 |
September | 0.908884E+10 | 0.817995E+10 | 3506.50 | 01-SEP-00:10 | 3155.85 | 3155.85 | 22.42 | 14.64 |
October | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-OCT-00:10 | 3155.85 | 3155.85 | 24.48 | 14.64 |
November | 0.908884E+10 | 0.817995E+10 | 3506.50 | 01-NOV-00:10 | 3155.85 | 3155.85 | 27.02 | 14.64 |
December | 0.939180E+10 | 0.845262E+10 | 3506.50 | 01-DEC-00:10 | 3155.85 | 3155.85 | 29.40 | 14.64 |
Annual Sum or Average | 0.110581E+12 | 0.995228E+11 | ||||||
Minimum of Months | 0.848292E+10 | 0.763462E+10 | 3506.50 | 3155.85 | 3155.85 | 21.30 | 14.64 | |
Maximum of Months | 0.939180E+10 | 0.845262E+10 | 3506.50 | 3155.85 | 3155.85 | 34.60 | 14.64 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 55.51 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 55.77 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 55.78 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 55.66 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.08 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 54.73 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 55.14 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 55.27 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.31 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.19 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 55.24 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.01 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 54.73 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.08 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103388E+10 | 0.930491E+09 | 15721.91 | 10-JAN-06:40 | 14149.72 | 14149.72 | 21.20 | 52.37 |
February | 0.502292E+09 | 0.452062E+09 | 15721.77 | 24-FEB-02:20 | 14149.59 | 14149.59 | 21.19 | 52.37 |
March | 0.658439E+09 | 0.592595E+09 | 15722.54 | 30-MAR-14:30 | 14150.29 | 14150.29 | 21.26 | 52.37 |
April | 0.869544E+09 | 0.782590E+09 | 15728.12 | 20-APR-14:30 | 14155.30 | 14155.30 | 21.75 | 52.37 |
May | 0.979561E+10 | 0.881605E+10 | 31540.65 | 31-MAY-15:10 | 28386.59 | 28386.59 | 25.40 | 104.74 |
June | 0.232464E+11 | 0.209218E+11 | 31569.88 | 30-JUN-12:20 | 28412.89 | 28412.89 | 26.51 | 104.74 |
July | 0.276170E+11 | 0.248553E+11 | 31558.39 | 03-JUL-15:00 | 28402.55 | 28402.55 | 26.07 | 104.74 |
August | 0.191933E+11 | 0.172739E+11 | 31557.64 | 11-AUG-14:20 | 28401.88 | 28401.88 | 26.05 | 104.74 |
September | 0.257645E+10 | 0.231881E+10 | 15738.86 | 07-SEP-16:00 | 14164.97 | 14164.97 | 22.70 | 52.37 |
October | 0.101575E+10 | 0.914179E+09 | 15722.93 | 12-OCT-11:50 | 14150.64 | 14150.64 | 21.29 | 52.37 |
November | 0.606589E+09 | 0.545930E+09 | 15721.88 | 12-NOV-23:10 | 14149.69 | 14149.69 | 21.20 | 52.37 |
December | 0.447145E+09 | 0.402431E+09 | 15721.90 | 26-DEC-07:00 | 14149.71 | 14149.71 | 21.20 | 52.37 |
Annual Sum or Average | 0.875625E+11 | 0.788062E+11 | ||||||
Minimum of Months | 0.447145E+09 | 0.402431E+09 | 15721.77 | 14149.59 | 14149.59 | 21.19 | 52.37 | |
Maximum of Months | 0.276170E+11 | 0.248553E+11 | 31569.88 | 28412.89 | 28412.89 | 26.51 | 104.74 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 37.47 | 37.47 | 518426.55 | 3374210.47 | 12-JAN-07:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 35.52 | 82.00 | 355312.81 | 3364590.38 | 27-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 51.51 | 82.00 | 176344.15 | 2776990.09 | 01-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31.42 | 31.42 | 43061.67 | 1524034.95 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.47 | 28.47 | 3433.97 | 638465.87 | 27-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.57 | 25.57 | 194.37 | 180668.17 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.88 | 26.88 | 141.00 | 94400.84 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 26.01 | 26.01 | 1667.37 | 717739.53 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.35 | 31.35 | 18380.37 | 1282815.48 | 25-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.95 | 26.95 | 110212.98 | 2006102.26 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31.62 | 31.62 | 435181.63 | 2772887.85 | 27-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.66 | 82.00 | 585286.05 | 3053381.19 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 186614.17 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.57 | 25.57 | 141.00 | 94400.84 | ||
Maximum of Months | 0.00 | 0.00 | 51.51 | 82.00 | 585286.05 | 3374210.47 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 556.97 | 22682.69 | 20-JAN-05:20 | 6.76 | 6.73 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 300.15 | 24109.01 | 15-FEB-13:20 | 6.76 | 6.73 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 409.84 | 71720.85 | 31-MAR-15:57 | 6.89 | 6.80 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1205.77 | 226556.55 | 20-APR-14:10 | 7.31 | 7.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83001.57 | 1147094.83 | 31-MAY-16:30 | 9.78 | 8.11 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 312195.71 | 1592209.27 | 21-JUN-14:50 | 10.98 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 353421.13 | 1556821.21 | 21-JUL-13:10 | 10.88 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 218024.48 | 1609347.70 | 11-AUG-15:20 | 11.02 | 6.70 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 6431.72 | 574616.33 | 07-SEP-16:00 | 8.24 | 7.47 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 638.81 | 103959.23 | 13-OCT-11:00 | 6.98 | 6.84 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 337.72 | 22908.28 | 10-NOV-05:29 | 6.76 | 6.73 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 241.12 | 23245.19 | 02-DEC-06:02 | 6.76 | 6.73 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 82078.47 | 0.00 | ||||||
Minimum of Months | 241.12 | 22682.69 | 6.76 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 353421.13 | 1609347.70 | 11.02 | 8.11 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.30 | 14-JAN-05:28 | 6.71 | 6.73 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 0.16 | 1254.28 | 15-FEB-13:20 | 6.99 | 6.73 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 28.52 | 30427.38 | 31-MAR-15:57 | 12.23 | 6.79 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 370.98 | 110504.27 | 20-APR-14:00 | 13.41 | 6.98 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46713.77 | 1129532.45 | 31-MAY-16:00 | 18.52 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 218691.71 | 1606258.97 | 21-JUN-14:50 | 14.41 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 276654.98 | 1849949.13 | 23-JUL-16:22 | 18.82 | 6.85 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 152148.27 | 1624040.51 | 11-AUG-15:20 | 13.90 | 6.70 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 2595.99 | 306181.88 | 07-SEP-16:00 | 16.57 | 7.46 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 47.01 | 47327.40 | 12-OCT-11:15 | 15.76 | 6.84 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.02 | 419.03 | 10-NOV-05:27 | 15.73 | 6.73 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.12 | 1148.51 | 02-DEC-06:01 | 15.73 | 6.73 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 58611.34 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.30 | 6.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 276654.98 | 1849949.13 | 18.82 | 7.46 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 148991.23 | 169158.37 | 27-JAN-22:10 | 21.66 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 293004.94 | 348331.83 | 10-FEB-16:10 | 25.15 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 446377.56 | 598109.60 | 31-MAR-23:30 | 29.99 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 606642.39 | 762051.62 | 22-APR-14:00 | 33.15 | 21.33 | 0.00 | 0.00 | 01-APR-00:10 |
May | 199978.07 | 500906.59 | 31-MAY-16:00 | 28.11 | 24.12 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 456787.64 | 1079679.44 | 30-JUN-15:00 | 39.20 | 31.88 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 688312.92 | 1402739.23 | 29-JUL-17:00 | 45.29 | 35.06 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 785785.23 | 1372166.70 | 11-AUG-18:00 | 44.72 | 31.92 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 182301.45 | 314378.16 | 30-SEP-24:00 | 24.49 | 18.33 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 309730.75 | 445613.31 | 31-OCT-23:30 | 27.04 | 18.33 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 436222.56 | 457732.80 | 03-NOV-21:10 | 27.28 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 573757.94 | 599612.19 | 29-DEC-22:10 | 30.02 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 428503.30 | 0.00 | ||||||
Minimum of Months | 148991.23 | 169158.37 | 21.66 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 785785.23 | 1402739.23 | 45.29 | 35.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.79 | 56.79 | 18918.71 | 63727.41 | 09-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.30 | 56.30 | 19024.95 | 63726.50 | 15-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.31 | 56.31 | 20128.93 | 63802.70 | 31-MAR-11:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.04 | 56.04 | 18948.81 | 63877.90 | 14-APR-11:23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.16 | 57.16 | 19399.04 | 63726.90 | 09-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.54 | 55.54 | 19162.49 | 62159.15 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.84 | 55.84 | 17130.64 | 59634.41 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 55.87 | 55.87 | 18202.48 | 57876.98 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.17 | 56.17 | 17102.20 | 57510.90 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.52 | 56.52 | 17385.40 | 59169.88 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55.84 | 55.84 | 18183.96 | 61462.34 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.54 | 56.54 | 18232.54 | 63716.77 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 18482.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.54 | 55.54 | 17102.20 | 57510.90 | ||
Maximum of Months | 0.00 | 0.00 | 57.16 | 57.16 | 20128.93 | 63877.90 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.45 | 21847.23 | 10-JAN-06:40 | 21.20 | 20.37 | 421.71 | 112617.03 | 10-JAN-06:50 |
February | 8.64 | 19198.70 | 24-FEB-02:20 | 21.19 | 20.36 | 327.17 | 114501.24 | 01-FEB-06:30 |
March | 22.49 | 34146.15 | 30-MAR-14:30 | 21.26 | 20.42 | 343.71 | 125613.97 | 24-MAR-04:07 |
April | 223.33 | 142085.70 | 20-APR-14:30 | 21.75 | 21.10 | 517.65 | 114096.35 | 07-APR-19:00 |
May | 51279.06 | 1883922.75 | 31-MAY-15:10 | 25.40 | 21.10 | 551.25 | 89810.55 | 27-MAY-06:20 |
June | 251206.30 | 2367601.32 | 30-JUN-12:20 | 26.51 | 22.46 | 203.79 | 53270.36 | 01-JUN-18:30 |
July | 322729.74 | 2177630.78 | 03-JUL-15:00 | 26.07 | 22.37 | 287.09 | 55248.75 | 06-JUL-07:40 |
August | 179506.51 | 2165175.65 | 11-AUG-14:20 | 26.05 | 21.10 | 457.01 | 65625.56 | 31-AUG-15:20 |
September | 2793.30 | 349937.38 | 07-SEP-16:00 | 22.70 | 21.10 | 651.33 | 101364.26 | 28-SEP-11:00 |
October | 27.60 | 41685.20 | 12-OCT-11:50 | 21.29 | 20.46 | 583.75 | 110753.10 | 18-OCT-04:01 |
November | 20.99 | 21360.48 | 12-NOV-23:10 | 21.20 | 20.37 | 309.78 | 132518.81 | 10-NOV-04:01 |
December | 13.33 | 21717.13 | 26-DEC-07:00 | 21.20 | 20.37 | 220.75 | 130514.97 | 16-DEC-06:03 |
Annual Sum or Average | 67916.03 | 406.74 | ||||||
Minimum of Months | 8.64 | 19198.70 | 21.19 | 20.36 | 203.79 | 53270.36 | ||
Maximum of Months | 322729.74 | 2367601.32 | 26.51 | 22.46 | 651.33 | 132518.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.158645E+12 | 0.00 | 835.83 | 0.378811E+10 | 0.00 | 0.00 |
February | 0.112034E+12 | 0.00 | 1280.14 | 0.349640E+10 | 0.00 | 0.00 |
March | 0.907061E+11 | 0.00 | 0.00 | 0.533915E+10 | 0.00 | 0.00 |
April | 0.214716E+11 | 0.00 | 0.100555E+09 | 0.894188E+10 | 0.00 | 0.00 |
May | 0.252627E+10 | 0.00 | 0.100888E+11 | 0.104093E+11 | 0.00 | 0.00 |
June | 4479395.19 | 0.00 | 0.467512E+11 | 0.135446E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.625277E+11 | 0.140955E+11 | 0.00 | 0.00 |
August | 0.366940E+09 | 0.00 | 0.357238E+11 | 0.141869E+11 | 0.00 | 0.00 |
September | 0.117906E+11 | 0.00 | 0.617268E+09 | 0.681859E+10 | 0.00 | 0.00 |
October | 0.551000E+11 | 0.00 | 0.00 | 0.531766E+10 | 0.00 | 0.00 |
November | 0.135075E+12 | 0.00 | 0.00 | 0.380348E+10 | 0.00 | 0.00 |
December | 0.160027E+12 | 0.00 | 613.74 | 0.365530E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.747748E+12 | 0.00 | 0.155809E+12 | 0.933969E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.349640E+10 | 0.00 | 0.00 |
Maximum of Months | 0.160027E+12 | 0.00 | 0.625277E+11 | 0.141869E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.106524E+13 | 0.00 | 22084.72 | 0.456403E+11 | 0.00 | 0.00 |
February | 0.639769E+12 | 0.00 | 11979609.42 | 0.394288E+11 | 0.00 | 0.00 |
March | 0.317288E+12 | 0.00 | 0.188222E+09 | 0.428496E+11 | 0.00 | 0.00 |
April | 0.722533E+11 | 0.00 | 0.847543E+09 | 0.591497E+11 | 0.00 | 0.00 |
May | 0.537374E+10 | 0.00 | 0.923863E+11 | 0.878519E+11 | 0.00 | 0.00 |
June | 0.379054E+09 | 0.00 | 0.408249E+12 | 0.112248E+12 | 0.00 | 0.00 |
July | 0.283868E+09 | 0.00 | 0.521039E+12 | 0.105606E+12 | 0.00 | 0.00 |
August | 0.338089E+10 | 0.00 | 0.282990E+12 | 0.951729E+11 | 0.00 | 0.00 |
September | 0.284049E+11 | 0.00 | 0.540391E+10 | 0.534919E+11 | 0.00 | 0.00 |
October | 0.194687E+12 | 0.00 | 0.120451E+09 | 0.409334E+11 | 0.00 | 0.00 |
November | 0.859087E+12 | 0.00 | 13209.60 | 0.399591E+11 | 0.00 | 0.00 |
December | 0.123076E+13 | 0.00 | 24437.01 | 0.440180E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.441691E+13 | 0.00 | 0.131124E+13 | 0.766350E+12 | 0.00 | 0.00 |
Minimum of Months | 0.283868E+09 | 0.00 | 13209.60 | 0.394288E+11 | 0.00 | 0.00 |
Maximum of Months | 0.123076E+13 | 0.00 | 0.521039E+12 | 0.112248E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.166448E+12 | 0.00 | 183798.09 | 0.540802E+10 | 0.00 | 0.00 |
February | 0.110978E+12 | 0.00 | 281578.16 | 0.466268E+10 | 0.00 | 0.00 |
March | 0.679697E+11 | 0.00 | 1698137.75 | 0.488633E+10 | 0.00 | 0.00 |
April | 0.189316E+11 | 0.00 | 28275353.59 | 0.485712E+10 | 0.00 | 0.00 |
May | 0.140764E+10 | 0.00 | 0.893798E+10 | 0.702151E+10 | 0.00 | 0.00 |
June | 0.112552E+09 | 0.00 | 0.422466E+11 | 0.104430E+11 | 0.00 | 0.00 |
July | 0.105401E+09 | 0.00 | 0.541282E+11 | 0.986539E+10 | 0.00 | 0.00 |
August | 0.708155E+09 | 0.00 | 0.283909E+11 | 0.805492E+10 | 0.00 | 0.00 |
September | 0.791700E+10 | 0.00 | 0.406741E+09 | 0.387844E+10 | 0.00 | 0.00 |
October | 0.480330E+11 | 0.00 | 334416.33 | 0.428832E+10 | 0.00 | 0.00 |
November | 0.141997E+12 | 0.00 | 42848.71 | 0.505321E+10 | 0.00 | 0.00 |
December | 0.185471E+12 | 0.00 | 269621.01 | 0.551169E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.750078E+12 | 0.00 | 0.134141E+12 | 0.739306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.105401E+09 | 0.00 | 42848.71 | 0.387844E+10 | 0.00 | 0.00 |
Maximum of Months | 0.185471E+12 | 0.00 | 0.541282E+11 | 0.104430E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.102820E+11 | 0.00 | 0.00 | 0.146358E+11 | 0.00 | 0.00 |
February | 0.422015E+10 | 0.00 | 42566.04 | 0.134161E+11 | 0.00 | 0.00 |
March | 0.801708E+09 | 0.00 | 24481.52 | 0.160155E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 199680.91 | 0.154289E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.298808E+10 | 0.163499E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.207306E+11 | 0.166402E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.311589E+11 | 0.164327E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.170481E+11 | 0.179987E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 37076608.24 | 0.164621E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 68854.97 | 0.157062E+11 | 0.00 | 0.00 |
November | 0.154157E+10 | 0.00 | 0.00 | 0.141784E+11 | 0.00 | 0.00 |
December | 0.527174E+10 | 0.00 | 0.00 | 0.144833E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.221171E+11 | 0.00 | 0.719630E+11 | 0.187748E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134161E+11 | 0.00 | 0.00 |
Maximum of Months | 0.102820E+11 | 0.00 | 0.311589E+11 | 0.179987E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.386833E+12 | 0.188110E+12 | 0.00 | 5.07 |
February | 0.00 | 0.00 | 0.631574E+12 | 0.228729E+12 | 0.00 | 7.30 |
March | 0.00 | 0.00 | 0.100996E+13 | 0.313654E+12 | 0.00 | 10.64 |
April | 0.00 | 0.00 | 0.127862E+13 | 0.354413E+12 | 0.00 | 10.84 |
May | 0.00 | 0.00 | 0.421359E+12 | 0.191608E+12 | 0.00 | 3.76 |
June | 0.00 | 0.00 | 0.715038E+12 | 0.248955E+12 | 0.00 | 3.48 |
July | 0.00 | 0.00 | 0.105527E+13 | 0.323697E+12 | 0.00 | 3.55 |
August | 0.00 | 0.00 | 0.135530E+13 | 0.381198E+12 | 0.00 | 7.00 |
September | 0.00 | 0.00 | 0.407694E+12 | 0.184521E+12 | 0.00 | 3.49 |
October | 0.00 | 0.00 | 0.717225E+12 | 0.253304E+12 | 0.00 | 6.92 |
November | 0.00 | 0.00 | 0.974306E+12 | 0.302666E+12 | 0.00 | 10.13 |
December | 0.00 | 0.00 | 0.130324E+13 | 0.367814E+12 | 0.00 | 12.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.102564E+14 | 0.333867E+13 | 0.00 | 85.04 |
Minimum of Months | 0.00 | 0.00 | 0.386833E+12 | 0.184521E+12 | 0.00 | 3.48 |
Maximum of Months | 0.00 | 0.00 | 0.135530E+13 | 0.381198E+12 | 0.00 | 12.88 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.140113E+10 | 0.187719E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.827886E+10 | 0.314642E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.170405E+11 | 0.497049E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243030E+11 | 0.613302E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.701792E+10 | 0.299612E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135074E+11 | 0.425133E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204467E+11 | 0.572993E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262024E+11 | 0.667779E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.607813E+10 | 0.273595E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112599E+11 | 0.382873E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153110E+11 | 0.462602E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.215938E+11 | 0.585283E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172441E+12 | 0.528258E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.140113E+10 | 0.187719E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262024E+11 | 0.667779E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.124629E+10 | 0.151231E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.543097E+11 | 0.251179E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.138813E+12 | 0.431245E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.216921E+12 | 0.560584E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.605432E+11 | 0.274311E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126141E+12 | 0.401648E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192975E+12 | 0.544038E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246400E+12 | 0.632319E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.458975E+11 | 0.238463E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.823738E+11 | 0.318191E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.114826E+12 | 0.383095E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.172204E+12 | 0.498361E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145265E+13 | 0.468466E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.124629E+10 | 0.151231E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246400E+12 | 0.632319E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 196724.60 | 0.149187E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.310719E+10 | 0.203460E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.112351E+11 | 0.382170E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199097E+11 | 0.530917E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.525567E+10 | 0.260021E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124079E+11 | 0.399589E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191370E+11 | 0.543213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.242258E+11 | 0.627396E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.302228E+10 | 0.208548E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.543842E+10 | 0.264089E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.873429E+10 | 0.330539E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.146500E+11 | 0.451939E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127124E+12 | 0.435107E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 196724.60 | 0.149187E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.242258E+11 | 0.627396E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.378811E+10 | 835.83 | 0.158645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349640E+10 | 1280.14 | 0.112034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533915E+10 | 0.00 | 0.907061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894188E+10 | 0.100555E+09 | 0.214716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104093E+11 | 0.100888E+11 | 0.252627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135446E+11 | 0.467512E+11 | 4479395.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140955E+11 | 0.625277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141869E+11 | 0.357238E+11 | 0.366940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681859E+10 | 0.617268E+09 | 0.117906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.531766E+10 | 0.00 | 0.551000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380348E+10 | 0.00 | 0.135075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365530E+10 | 613.74 | 0.160027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933969E+11 | 0.155809E+12 | 0.747748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141869E+11 | 0.625277E+11 | 0.160027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.456403E+11 | 22084.72 | 0.106524E+13 | 0.942582E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394288E+11 | 11979609.42 | 0.639769E+12 | 0.844555E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428496E+11 | 0.188222E+09 | 0.317288E+12 | 0.100027E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591497E+11 | 0.847543E+09 | 0.722533E+11 | 0.357830E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.878519E+11 | 0.923863E+11 | 0.537374E+10 | 0.452928E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112248E+12 | 0.408249E+12 | 0.379054E+09 | 0.406749E+10 | 26662796.80 | 0.00 | 0.00 | 0.00 |
July | 0.105606E+12 | 0.521039E+12 | 0.283868E+09 | 0.630348E+10 | 0.228850E+10 | 0.00 | 0.00 | 0.00 |
August | 0.951729E+11 | 0.282990E+12 | 0.338089E+10 | 0.185180E+11 | 5619283.29 | 0.00 | 0.00 | 0.00 |
September | 0.534919E+11 | 0.540391E+10 | 0.284049E+11 | 0.197358E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409334E+11 | 0.120451E+09 | 0.194687E+12 | 0.711240E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399591E+11 | 13209.60 | 0.859087E+12 | 0.931603E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440180E+11 | 24437.01 | 0.123076E+13 | 0.821585E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766350E+12 | 0.131124E+13 | 0.441691E+13 | 0.588121E+13 | 0.232079E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.394288E+11 | 13209.60 | 0.283868E+09 | 0.406749E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112248E+12 | 0.521039E+12 | 0.123076E+13 | 0.100027E+13 | 0.228850E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.540802E+10 | 183798.09 | 0.166448E+12 | 0.925699E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466268E+10 | 281578.16 | 0.110978E+12 | 0.832656E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.488633E+10 | 1698137.75 | 0.679697E+11 | 0.102535E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485712E+10 | 28275353.59 | 0.189316E+11 | 0.441779E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.702151E+10 | 0.893798E+10 | 0.140764E+10 | 0.727352E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104430E+11 | 0.422466E+11 | 0.112552E+09 | 0.678380E+09 | 13988286.42 | 0.00 | 0.00 | 0.00 |
July | 0.986539E+10 | 0.541282E+11 | 0.105401E+09 | 0.805753E+09 | 0.187003E+09 | 0.00 | 0.00 | 0.00 |
August | 0.805492E+10 | 0.283909E+11 | 0.708155E+09 | 0.383225E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387844E+10 | 0.406741E+09 | 0.791700E+10 | 0.299427E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428832E+10 | 334416.33 | 0.480330E+11 | 0.757897E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505321E+10 | 42848.71 | 0.141997E+12 | 0.906256E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.551169E+10 | 269621.01 | 0.185471E+12 | 0.804354E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739306E+11 | 0.134141E+12 | 0.750078E+12 | 0.611932E+12 | 0.200992E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.387844E+10 | 42848.71 | 0.105401E+09 | 0.678380E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104430E+11 | 0.541282E+11 | 0.185471E+12 | 0.102535E+12 | 0.187003E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146358E+11 | 0.00 | 0.102820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134161E+11 | 42566.04 | 0.422015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160155E+11 | 24481.52 | 0.801708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154289E+11 | 199680.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163499E+11 | 0.298808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166402E+11 | 0.207306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164327E+11 | 0.311589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179987E+11 | 0.170481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164621E+11 | 37076608.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157062E+11 | 68854.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141784E+11 | 0.00 | 0.154157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144833E+11 | 0.00 | 0.527174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187748E+12 | 0.719630E+11 | 0.221171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179987E+11 | 0.311589E+11 | 0.102820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.960304E+11 | 0.308382E+12 | 0.00 | 0.00 | 0.00 | 0.135679E+11 | 0.00 | 0.00 |
February | 0.867371E+11 | 0.509199E+12 | 0.00 | 0.00 | 0.00 | 0.195292E+11 | 0.00 | 0.00 |
March | 0.960304E+11 | 0.820928E+12 | 0.00 | 0.00 | 0.00 | 0.284642E+11 | 0.00 | 0.00 |
April | 0.929326E+11 | 0.104628E+13 | 0.00 | 0.00 | 0.00 | 0.290076E+11 | 0.00 | 0.00 |
May | 0.960304E+11 | 0.335881E+12 | 0.00 | 0.00 | 0.00 | 0.100535E+11 | 0.00 | 0.00 |
June | 0.929326E+11 | 0.568366E+12 | 0.00 | 0.00 | 0.00 | 0.930813E+10 | 0.00 | 0.00 |
July | 0.960304E+11 | 0.837157E+12 | 0.00 | 0.00 | 0.00 | 0.951320E+10 | 0.00 | 0.00 |
August | 0.960304E+11 | 0.108894E+13 | 0.00 | 0.00 | 0.00 | 0.187306E+11 | 0.00 | 0.00 |
September | 0.929326E+11 | 0.325483E+12 | 0.00 | 0.00 | 0.00 | 0.933523E+10 | 0.00 | 0.00 |
October | 0.960304E+11 | 0.578545E+12 | 0.00 | 0.00 | 0.00 | 0.185102E+11 | 0.00 | 0.00 |
November | 0.929326E+11 | 0.791807E+12 | 0.00 | 0.00 | 0.00 | 0.271122E+11 | 0.00 | 0.00 |
December | 0.960304E+11 | 0.106607E+13 | 0.00 | 0.00 | 0.00 | 0.344556E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.113068E+13 | 0.827704E+13 | 0.00 | 0.00 | 0.00 | 0.227588E+12 | 0.00 | 0.00 |
Minimum of Months | 0.867371E+11 | 0.308382E+12 | 0.00 | 0.00 | 0.00 | 0.930813E+10 | 0.00 | 0.00 |
Maximum of Months | 0.960304E+11 | 0.108894E+13 | 0.00 | 0.00 | 0.00 | 0.344556E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153972E+10 | 0.106367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139072E+10 | 0.652315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153972E+10 | 0.136097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149005E+10 | 0.196600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153972E+10 | 0.556152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149005E+10 | 0.107461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153972E+10 | 0.162565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153972E+10 | 0.210643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149005E+10 | 0.483224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153972E+10 | 0.897089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149005E+10 | 0.121751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153972E+10 | 0.172807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181290E+11 | 0.137744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139072E+10 | 0.106367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153972E+10 | 0.210643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147773E+11 | 0.900516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133472E+11 | 0.425391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147773E+11 | 0.110465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143006E+11 | 0.175164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147773E+11 | 0.478894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143006E+11 | 0.100276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147773E+11 | 0.153349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147773E+11 | 0.197946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143006E+11 | 0.363518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147773E+11 | 0.653320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143006E+11 | 0.908169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147773E+11 | 0.137145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173991E+12 | 0.115817E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133472E+11 | 0.900516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147773E+11 | 0.197946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149177E+10 | 97286.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134741E+10 | 0.241999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149177E+10 | 0.890518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144365E+10 | 0.160442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149177E+10 | 0.414724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144365E+10 | 0.985563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149177E+10 | 0.151967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149177E+10 | 0.194436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144365E+10 | 0.238044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149177E+10 | 0.428930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144365E+10 | 0.687256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149177E+10 | 0.116224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175644E+11 | 0.101177E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134741E+10 | 97286.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149177E+10 | 0.194436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.378811E+10 | 0.158645E+12 | 835.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349640E+10 | 0.112034E+12 | 1280.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533915E+10 | 0.907061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.894188E+10 | 0.214716E+11 | 0.100555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104093E+11 | 0.252627E+10 | 0.100888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135446E+11 | 4479395.19 | 0.467512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140955E+11 | 0.00 | 0.625277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141869E+11 | 0.366940E+09 | 0.357238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681859E+10 | 0.117906E+11 | 0.617268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.531766E+10 | 0.551000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380348E+10 | 0.135075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365530E+10 | 0.160027E+12 | 613.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933969E+11 | 0.747748E+12 | 0.155809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141869E+11 | 0.160027E+12 | 0.625277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.456403E+11 | 0.106524E+13 | 22084.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394288E+11 | 0.639769E+12 | 11979609.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428496E+11 | 0.317288E+12 | 0.188222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591497E+11 | 0.722533E+11 | 0.847543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.878519E+11 | 0.537374E+10 | 0.923863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112248E+12 | 0.379054E+09 | 0.408249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105606E+12 | 0.283868E+09 | 0.521039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.951729E+11 | 0.338089E+10 | 0.282990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.534919E+11 | 0.284049E+11 | 0.540391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409334E+11 | 0.194687E+12 | 0.120451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399591E+11 | 0.859087E+12 | 13209.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440180E+11 | 0.123076E+13 | 24437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766350E+12 | 0.441691E+13 | 0.131124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.394288E+11 | 0.283868E+09 | 13209.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112248E+12 | 0.123076E+13 | 0.521039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.540802E+10 | 0.166448E+12 | 183798.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466268E+10 | 0.110978E+12 | 281578.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.488633E+10 | 0.679697E+11 | 1698137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485712E+10 | 0.189316E+11 | 28275353.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.702151E+10 | 0.140764E+10 | 0.893798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104430E+11 | 0.112552E+09 | 0.422466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.986539E+10 | 0.105401E+09 | 0.541282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.805492E+10 | 0.708155E+09 | 0.283909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387844E+10 | 0.791700E+10 | 0.406741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428832E+10 | 0.480330E+11 | 334416.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505321E+10 | 0.141997E+12 | 42848.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.551169E+10 | 0.185471E+12 | 269621.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739306E+11 | 0.750078E+12 | 0.134141E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.387844E+10 | 0.105401E+09 | 42848.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104430E+11 | 0.185471E+12 | 0.541282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146358E+11 | 0.102820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134161E+11 | 0.422015E+10 | 42566.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160155E+11 | 0.801708E+09 | 24481.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154289E+11 | 0.00 | 199680.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163499E+11 | 0.00 | 0.298808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166402E+11 | 0.00 | 0.207306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164327E+11 | 0.00 | 0.311589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179987E+11 | 0.00 | 0.170481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164621E+11 | 0.00 | 37076608.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157062E+11 | 0.00 | 68854.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141784E+11 | 0.154157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144833E+11 | 0.527174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187748E+12 | 0.221171E+11 | 0.719630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179987E+11 | 0.102820E+11 | 0.311589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.960304E+11 | 0.00 | 0.386833E+12 | 0.00 | 0.784506E+11 | 0.00 | 0.00 | 0.00 | 0.136290E+11 | 0.00 | 0.00 | 0.00 |
February | 0.867371E+11 | 0.00 | 0.631574E+12 | 0.00 | 0.122375E+12 | 0.00 | 0.00 | 0.00 | 0.196171E+11 | 0.00 | 0.00 | 0.00 |
March | 0.960304E+11 | 0.00 | 0.100996E+13 | 0.00 | 0.189032E+12 | 0.00 | 0.00 | 0.00 | 0.285923E+11 | 0.00 | 0.00 | 0.00 |
April | 0.929326E+11 | 0.00 | 0.127862E+13 | 0.00 | 0.232342E+12 | 0.00 | 0.00 | 0.00 | 0.291382E+11 | 0.00 | 0.00 | 0.00 |
May | 0.960304E+11 | 0.00 | 0.421359E+12 | 0.00 | 0.854789E+11 | 0.00 | 0.00 | 0.00 | 0.100987E+11 | 0.00 | 0.00 | 0.00 |
June | 0.929326E+11 | 0.00 | 0.715038E+12 | 0.00 | 0.146672E+12 | 0.00 | 0.00 | 0.00 | 0.935003E+10 | 0.00 | 0.00 | 0.00 |
July | 0.960304E+11 | 0.00 | 0.105527E+13 | 0.00 | 0.218111E+12 | 0.00 | 0.00 | 0.00 | 0.955602E+10 | 0.00 | 0.00 | 0.00 |
August | 0.960304E+11 | 0.00 | 0.135530E+13 | 0.00 | 0.266353E+12 | 0.00 | 0.00 | 0.00 | 0.188149E+11 | 0.00 | 0.00 | 0.00 |
September | 0.929326E+11 | 0.00 | 0.407694E+12 | 0.00 | 0.822108E+11 | 0.00 | 0.00 | 0.00 | 0.937726E+10 | 0.00 | 0.00 | 0.00 |
October | 0.960304E+11 | 0.00 | 0.717225E+12 | 0.00 | 0.138680E+12 | 0.00 | 0.00 | 0.00 | 0.185936E+11 | 0.00 | 0.00 | 0.00 |
November | 0.929326E+11 | 0.00 | 0.974306E+12 | 0.00 | 0.182500E+12 | 0.00 | 0.00 | 0.00 | 0.272342E+11 | 0.00 | 0.00 | 0.00 |
December | 0.960304E+11 | 0.00 | 0.130324E+13 | 0.00 | 0.237173E+12 | 0.00 | 0.00 | 0.00 | 0.346107E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113068E+13 | 0.00 | 0.102564E+14 | 0.00 | 0.197938E+13 | 0.00 | 0.00 | 0.00 | 0.228612E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.867371E+11 | 0.00 | 0.386833E+12 | 0.00 | 0.784506E+11 | 0.00 | 0.00 | 0.00 | 0.935003E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.960304E+11 | 0.00 | 0.135530E+13 | 0.00 | 0.266353E+12 | 0.00 | 0.00 | 0.00 | 0.346107E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153972E+10 | 0.00 | 0.140113E+10 | 0.00 | 0.337464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139072E+10 | 0.00 | 0.827886E+10 | 0.00 | 0.175570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153972E+10 | 0.00 | 0.170405E+11 | 0.00 | 0.343077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149005E+10 | 0.00 | 0.243030E+11 | 0.00 | 0.464296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153972E+10 | 0.00 | 0.701792E+10 | 0.00 | 0.145639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149005E+10 | 0.00 | 0.135074E+11 | 0.00 | 0.276127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153972E+10 | 0.00 | 0.204467E+11 | 0.00 | 0.419021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153972E+10 | 0.00 | 0.262024E+11 | 0.00 | 0.513806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149005E+10 | 0.00 | 0.607813E+10 | 0.00 | 0.124590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153972E+10 | 0.00 | 0.112599E+11 | 0.00 | 0.228901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149005E+10 | 0.00 | 0.153110E+11 | 0.00 | 0.313596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153972E+10 | 0.00 | 0.215938E+11 | 0.00 | 0.431311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181290E+11 | 0.00 | 0.172441E+12 | 0.00 | 0.346968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139072E+10 | 0.00 | 0.140113E+10 | 0.00 | 0.337464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153972E+10 | 0.00 | 0.262024E+11 | 0.00 | 0.513806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147773E+11 | 0.00 | 0.124629E+10 | 0.00 | 0.345770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133472E+11 | 0.00 | 0.543097E+11 | 0.00 | 0.117706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147773E+11 | 0.00 | 0.138813E+12 | 0.00 | 0.283472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143006E+11 | 0.00 | 0.216921E+12 | 0.00 | 0.417578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147773E+11 | 0.00 | 0.605432E+11 | 0.00 | 0.126538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143006E+11 | 0.00 | 0.126141E+12 | 0.00 | 0.258642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147773E+11 | 0.00 | 0.192975E+12 | 0.00 | 0.396265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147773E+11 | 0.00 | 0.246400E+12 | 0.00 | 0.484546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143006E+11 | 0.00 | 0.458975E+11 | 0.00 | 0.954565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147773E+11 | 0.00 | 0.823738E+11 | 0.00 | 0.170418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143006E+11 | 0.00 | 0.114826E+12 | 0.00 | 0.240089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147773E+11 | 0.00 | 0.172204E+12 | 0.00 | 0.350588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173991E+12 | 0.00 | 0.145265E+13 | 0.00 | 0.294476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133472E+11 | 0.00 | 0.124629E+10 | 0.00 | 0.345770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147773E+11 | 0.00 | 0.246400E+12 | 0.00 | 0.484546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149177E+10 | 0.00 | 196724.60 | 0.00 | 99437.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134741E+10 | 0.00 | 0.310719E+10 | 0.00 | 0.687193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149177E+10 | 0.00 | 0.112351E+11 | 0.00 | 0.232992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144365E+10 | 0.00 | 0.199097E+11 | 0.00 | 0.386552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149177E+10 | 0.00 | 0.525567E+10 | 0.00 | 0.110844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144365E+10 | 0.00 | 0.124079E+11 | 0.00 | 0.255224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149177E+10 | 0.00 | 0.191370E+11 | 0.00 | 0.394036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149177E+10 | 0.00 | 0.242258E+11 | 0.00 | 0.478219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144365E+10 | 0.00 | 0.302228E+10 | 0.00 | 0.641833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149177E+10 | 0.00 | 0.543842E+10 | 0.00 | 0.114912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144365E+10 | 0.00 | 0.873429E+10 | 0.00 | 0.186174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149177E+10 | 0.00 | 0.146500E+11 | 0.00 | 0.302762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175644E+11 | 0.00 | 0.127124E+12 | 0.00 | 0.259463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134741E+10 | 0.00 | 196724.60 | 0.00 | 99437.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149177E+10 | 0.00 | 0.242258E+11 | 0.00 | 0.478219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.778929E+11 | 0.00 | 0.00 | 159495.21 | 0.00 | 28133009.64 | 0.209227E+09 | 0.00 | 0.31 |
February | 0.560693E+11 | 0.00 | 0.00 | 8297589.37 | 0.00 | 0.00 | 0.980821E+10 | 0.00 | 0.32 |
March | 0.414802E+11 | 0.00 | 0.00 | 36848317.11 | 0.00 | 0.00 | 0.331950E+11 | 0.00 | 0.37 |
April | 0.270416E+10 | 0.00 | 0.00 | 0.110455E+09 | 0.00 | 0.00 | 0.680674E+11 | 0.00 | 0.61 |
May | 0.260810E+09 | 0.00 | 0.00 | 0.111381E+09 | 0.00 | 0.00 | 0.741794E+11 | 0.00 | 1.11 |
June | 0.196780E+09 | 30831806.28 | 0.00 | 0.118116E+09 | 0.00 | 0.00 | 0.600116E+11 | 0.00 | 1.45 |
July | 0.266278E+09 | 0.302575E+09 | 0.00 | 0.122946E+09 | 22711150.65 | 0.00 | 0.512438E+11 | 0.00 | 1.36 |
August | 0.240751E+09 | 3754686.31 | 0.00 | 0.144372E+09 | 0.00 | 0.00 | 0.744707E+11 | 0.00 | 1.44 |
September | 0.551331E+09 | 0.00 | 0.00 | 0.123667E+09 | 0.00 | 0.00 | 0.770426E+11 | 0.00 | 0.82 |
October | 0.867208E+10 | 0.00 | 0.00 | 99193509.33 | 0.00 | 0.00 | 0.665585E+11 | 0.00 | 0.49 |
November | 0.670447E+11 | 0.00 | 0.00 | 10703548.46 | 0.00 | 0.00 | 0.112493E+11 | 0.00 | 0.32 |
December | 0.794680E+11 | 0.00 | 0.00 | 2082306.80 | 0.00 | 0.00 | 0.270714E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.334847E+12 | 0.337162E+09 | 0.00 | 0.888221E+09 | 22711150.65 | 28133009.64 | 0.528743E+12 | 0.00 | 0.75 |
Minimum of Months | 0.196780E+09 | 0.00 | 0.00 | 159495.21 | 0.00 | 0.00 | 0.209227E+09 | 0.00 | 0.31 |
Maximum of Months | 0.794680E+11 | 0.302575E+09 | 0.00 | 0.144372E+09 | 22711150.65 | 28133009.64 | 0.770426E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.698514E+11 | 0.00 | 0.00 | 5601167.82 | 0.00 | 0.241505E+09 | 0.224499E+11 | 0.00 | 0.38 |
February | 0.396583E+11 | 0.00 | 0.00 | 20702523.88 | 0.00 | 0.00 | 0.396709E+11 | 0.00 | 0.40 |
March | 0.180456E+11 | 0.00 | 0.00 | 60401341.16 | 0.00 | 0.00 | 0.721867E+11 | 0.00 | 0.45 |
April | 0.581818E+10 | 0.00 | 0.00 | 0.103328E+09 | 0.00 | 0.00 | 0.669693E+11 | 0.00 | 0.60 |
May | 0.556182E+10 | 0.00 | 0.00 | 94600822.87 | 0.00 | 0.00 | 0.594445E+11 | 0.00 | 0.89 |
June | 0.630916E+10 | 23116944.89 | 0.00 | 0.101648E+09 | 0.00 | 0.00 | 0.475748E+11 | 0.00 | 1.14 |
July | 0.104605E+11 | 0.266822E+09 | 0.00 | 98584232.13 | 46314244.71 | 0.00 | 0.392508E+11 | 0.00 | 1.14 |
August | 0.964407E+10 | 1514635.68 | 0.00 | 0.115318E+09 | 0.00 | 0.00 | 0.593038E+11 | 0.00 | 1.18 |
September | 0.283241E+10 | 0.00 | 0.00 | 89375159.60 | 0.00 | 0.00 | 0.592219E+11 | 0.00 | 0.63 |
October | 0.770464E+10 | 0.00 | 0.00 | 71603048.05 | 0.00 | 0.00 | 0.672636E+11 | 0.00 | 0.47 |
November | 0.350316E+11 | 0.00 | 0.00 | 29412046.48 | 0.00 | 0.00 | 0.613876E+11 | 0.00 | 0.40 |
December | 0.460106E+11 | 0.00 | 0.00 | 20683730.06 | 0.00 | 0.00 | 0.543595E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.256928E+12 | 0.291454E+09 | 0.00 | 0.811258E+09 | 46314244.71 | 0.241505E+09 | 0.649083E+12 | 0.00 | 0.67 |
Minimum of Months | 0.283241E+10 | 0.00 | 0.00 | 5601167.82 | 0.00 | 0.00 | 0.224499E+11 | 0.00 | 0.38 |
Maximum of Months | 0.698514E+11 | 0.266822E+09 | 0.00 | 0.115318E+09 | 46314244.71 | 0.241505E+09 | 0.721867E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451947E+12 | 0.00 | 0.00 | 5673607.60 | 0.00 | 0.204795E+11 | 0.116534E+11 | 0.00 | 0.39 |
February | 0.331294E+12 | 0.00 | 0.00 | 48941069.09 | 0.00 | 0.669668E+10 | 0.444727E+11 | 0.00 | 0.40 |
March | 0.217267E+12 | 0.00 | 0.00 | 0.181423E+09 | 0.00 | 0.153448E+09 | 0.133049E+12 | 0.00 | 0.42 |
April | 0.892263E+11 | 0.00 | 0.00 | 0.496046E+09 | 0.00 | 14908846.96 | 0.296630E+12 | 0.00 | 0.47 |
May | 0.401139E+11 | 0.00 | 0.00 | 0.757990E+09 | 0.00 | 0.00 | 0.477773E+12 | 0.00 | 0.76 |
June | 0.379863E+11 | 2871389.65 | 0.00 | 0.841902E+09 | 0.00 | 0.00 | 0.393149E+12 | 0.00 | 0.94 |
July | 0.466525E+11 | 0.128977E+10 | 0.00 | 0.788852E+09 | 0.157279E+09 | 0.00 | 0.311450E+12 | 0.00 | 0.86 |
August | 0.297626E+11 | 0.00 | 0.00 | 0.872933E+09 | 0.00 | 0.00 | 0.443210E+12 | 0.00 | 0.84 |
September | 0.498147E+11 | 0.00 | 0.00 | 0.571346E+09 | 0.00 | 0.00 | 0.370482E+12 | 0.00 | 0.53 |
October | 0.150191E+12 | 0.00 | 0.00 | 0.233626E+09 | 0.00 | 0.395942E+09 | 0.160063E+12 | 0.00 | 0.41 |
November | 0.434140E+12 | 0.00 | 0.00 | 19072635.91 | 0.00 | 0.642976E+10 | 0.289199E+11 | 0.00 | 0.39 |
December | 0.574731E+12 | 0.00 | 0.00 | 221512.12 | 0.00 | 0.579872E+10 | 0.192309E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.245313E+13 | 0.129264E+10 | 0.00 | 0.481803E+10 | 0.157279E+09 | 0.399689E+11 | 0.267278E+13 | 0.00 | 0.57 |
Minimum of Months | 0.297626E+11 | 0.00 | 0.00 | 221512.12 | 0.00 | 0.00 | 0.192309E+10 | 0.00 | 0.38 |
Maximum of Months | 0.574731E+12 | 0.128977E+10 | 0.00 | 0.872933E+09 | 0.157279E+09 | 0.204795E+11 | 0.477773E+12 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177186E+11 | 0.00 | 0.00 | 0.37 |
February | 0.196537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123032E+11 | 0.00 | 0.00 | 0.38 |
March | 0.230846E+11 | 0.00 | 0.00 | 832802.88 | 0.00 | 0.444594E+10 | 0.720369E+09 | 0.00 | 0.40 |
April | 0.139087E+11 | 0.00 | 0.00 | 18868490.47 | 0.00 | 0.569795E+09 | 0.139098E+11 | 0.00 | 0.42 |
May | 0.691108E+10 | 0.00 | 0.00 | 52673615.96 | 0.00 | 0.00 | 0.368249E+11 | 0.00 | 0.68 |
June | 0.333605E+10 | 13939566.04 | 0.00 | 78246870.51 | 0.00 | 0.00 | 0.377743E+11 | 0.00 | 0.92 |
July | 0.364578E+10 | 0.119512E+09 | 0.00 | 73544171.80 | 11190177.61 | 0.00 | 0.293091E+11 | 0.00 | 0.85 |
August | 0.363469E+10 | 0.00 | 0.00 | 69920546.31 | 0.00 | 0.00 | 0.364598E+11 | 0.00 | 0.78 |
September | 0.115513E+11 | 0.00 | 0.00 | 20715927.60 | 0.00 | 0.109134E+09 | 0.163587E+11 | 0.00 | 0.45 |
October | 0.179845E+11 | 0.00 | 0.00 | 2537601.66 | 0.00 | 0.216253E+10 | 0.239288E+10 | 0.00 | 0.38 |
November | 0.264964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139045E+11 | 0.00 | 0.00 | 0.37 |
December | 0.294150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207717E+11 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.183820E+12 | 0.133451E+09 | 0.00 | 0.317340E+09 | 11190177.61 | 0.719854E+11 | 0.173750E+12 | 0.00 | 0.53 |
Minimum of Months | 0.333605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.294150E+11 | 0.119512E+09 | 0.00 | 78246870.51 | 11190177.61 | 0.207717E+11 | 0.377743E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129832E+11 | 0.00 | 0.00 | 0.48 |
February | 0.473456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700622E+10 | 0.00 | 0.00 | 0.46 |
March | 0.813881E+10 | 0.00 | 0.00 | 250372.18 | 0.00 | 0.276372E+10 | 0.326411E+09 | 0.00 | 0.44 |
April | 0.428060E+10 | 0.00 | 0.00 | 4594576.22 | 0.00 | 0.117474E+09 | 0.342041E+10 | 0.00 | 0.52 |
May | 0.149648E+10 | 0.00 | 0.00 | 10714580.11 | 0.00 | 0.00 | 0.734573E+10 | 0.00 | 0.99 |
June | 0.903874E+09 | 5335459.08 | 0.00 | 19106834.12 | 0.00 | 0.00 | 0.836806E+10 | 0.00 | 1.59 |
July | 0.171788E+10 | 51849539.79 | 0.00 | 16427731.46 | 7429710.72 | 0.00 | 0.628069E+10 | 0.00 | 1.52 |
August | 0.194288E+10 | 251181.13 | 0.00 | 13307525.89 | 0.00 | 0.00 | 0.719564E+10 | 0.00 | 1.31 |
September | 0.372465E+10 | 0.00 | 0.00 | 3596435.99 | 0.00 | 0.00 | 0.308175E+10 | 0.00 | 0.55 |
October | 0.682569E+10 | 0.00 | 0.00 | 611114.32 | 0.00 | 0.106328E+10 | 0.606279E+09 | 0.00 | 0.41 |
November | 0.568212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774661E+10 | 0.00 | 0.00 | 0.44 |
December | 0.196822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130920E+11 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.432768E+11 | 57436180.01 | 0.00 | 68609170.31 | 7429710.72 | 0.447725E+11 | 0.366250E+11 | 0.00 | 0.77 |
Minimum of Months | 0.903874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.813881E+10 | 51849539.79 | 0.00 | 19106834.12 | 7429710.72 | 0.130920E+11 | 0.836806E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172842E+11 | 0.00 | 0.00 | 0.96 |
February | 0.653478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863749E+10 | 0.00 | 0.00 | 0.92 |
March | 0.100861E+11 | 0.00 | 0.00 | 1271355.57 | 0.00 | 0.293001E+10 | 0.179888E+10 | 0.00 | 0.89 |
April | 0.552279E+10 | 0.00 | 0.00 | 6356040.52 | 0.00 | 0.187653E+09 | 0.442203E+10 | 0.00 | 1.01 |
May | 0.238180E+10 | 0.00 | 0.00 | 14288261.08 | 0.00 | 0.00 | 0.937169E+10 | 0.00 | 1.96 |
June | 0.176154E+10 | 3430529.67 | 0.00 | 14865720.92 | 0.00 | 0.00 | 0.789207E+10 | 0.00 | 2.44 |
July | 0.268643E+10 | 39177509.42 | 0.00 | 14027927.18 | 9625106.61 | 0.00 | 0.589035E+10 | 0.00 | 2.42 |
August | 0.339014E+10 | 186349.41 | 0.00 | 11155021.62 | 0.00 | 0.00 | 0.673466E+10 | 0.00 | 2.09 |
September | 0.520604E+10 | 0.00 | 0.00 | 3751831.73 | 0.00 | 0.00 | 0.319370E+10 | 0.00 | 1.03 |
October | 0.851983E+10 | 0.00 | 0.00 | 552481.58 | 0.00 | 0.173578E+10 | 0.739904E+09 | 0.00 | 0.82 |
November | 0.514786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122439E+11 | 0.00 | 0.00 | 0.88 |
December | 0.103899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184605E+11 | 0.00 | 0.00 | 0.91 |
Annual Sum or Average | 0.541383E+11 | 42794388.50 | 0.00 | 66268640.20 | 9625106.61 | 0.614796E+11 | 0.400433E+11 | 0.00 | 1.36 |
Minimum of Months | 0.103899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.100861E+11 | 39177509.42 | 0.00 | 14865720.92 | 9625106.61 | 0.184605E+11 | 0.937169E+10 | 0.00 | 2.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244236E+11 | 0.00 | 0.00 | 0.95 |
February | 0.120149E+11 | 0.00 | 0.00 | 859452.77 | 0.00 | 0.100073E+11 | 0.138893E+10 | 0.00 | 0.91 |
March | 0.140936E+11 | 0.00 | 0.00 | 6592090.50 | 0.00 | 0.300784E+10 | 0.783209E+10 | 0.00 | 0.97 |
April | 0.725797E+10 | 0.00 | 0.00 | 17113848.92 | 0.00 | 0.277116E+09 | 0.117852E+11 | 0.00 | 1.34 |
May | 0.475214E+10 | 0.00 | 0.00 | 16953300.39 | 0.00 | 0.00 | 0.118709E+11 | 0.00 | 1.92 |
June | 0.340956E+10 | 5887585.14 | 0.00 | 19641398.85 | 0.00 | 0.00 | 0.958207E+10 | 0.00 | 2.34 |
July | 0.453673E+10 | 93344804.81 | 0.00 | 20043818.96 | 14580760.00 | 0.00 | 0.708986E+10 | 0.00 | 2.32 |
August | 0.527801E+10 | 434971.10 | 0.00 | 21192297.07 | 0.00 | 0.00 | 0.107350E+11 | 0.00 | 2.35 |
September | 0.745795E+10 | 0.00 | 0.00 | 9029493.33 | 0.00 | 1092901.43 | 0.719564E+10 | 0.00 | 1.22 |
October | 0.127885E+11 | 0.00 | 0.00 | 3364905.80 | 0.00 | 0.192247E+10 | 0.290596E+10 | 0.00 | 0.86 |
November | 0.108863E+11 | 0.00 | 0.00 | 136712.71 | 0.00 | 0.154810E+11 | 0.281814E+09 | 0.00 | 0.87 |
December | 0.308646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267683E+11 | 0.00 | 0.00 | 0.90 |
Annual Sum or Average | 0.904529E+11 | 99667361.04 | 0.00 | 0.114927E+09 | 14580760.00 | 0.818888E+11 | 0.706675E+11 | 0.00 | 1.42 |
Minimum of Months | 0.308646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
Maximum of Months | 0.140936E+11 | 93344804.81 | 0.00 | 21192297.07 | 14580760.00 | 0.267683E+11 | 0.118709E+11 | 0.00 | 2.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120944E+11 | 0.00 | 0.00 | 1.14 |
February | 0.148868E+11 | 0.00 | 0.00 | 353.47 | 0.00 | 0.299929E+10 | 22551724.96 | 0.00 | 1.08 |
March | 0.143228E+11 | 0.00 | 0.00 | 1930882.82 | 0.00 | 0.256709E+09 | 0.285329E+10 | 0.00 | 1.06 |
April | 0.334511E+10 | 0.00 | 0.00 | 14740627.37 | 0.00 | 0.00 | 0.106338E+11 | 0.00 | 1.50 |
May | 0.273158E+10 | 0.00 | 0.00 | 11500634.16 | 0.00 | 0.00 | 0.811949E+10 | 0.00 | 1.91 |
June | 0.155027E+10 | 8490925.52 | 0.00 | 19008318.54 | 0.00 | 0.00 | 0.820055E+10 | 0.00 | 2.77 |
July | 0.244232E+10 | 87430668.47 | 0.00 | 18957335.90 | 5935585.96 | 0.00 | 0.662057E+10 | 0.00 | 2.78 |
August | 0.233239E+10 | 577222.42 | 0.00 | 21287960.19 | 0.00 | 0.00 | 0.988754E+10 | 0.00 | 2.79 |
September | 0.560922E+10 | 0.00 | 0.00 | 3739908.71 | 0.00 | 0.00 | 0.421005E+10 | 0.00 | 1.23 |
October | 0.116956E+11 | 0.00 | 0.00 | 884359.08 | 0.00 | 13298197.00 | 0.124339E+10 | 0.00 | 0.97 |
November | 0.196969E+11 | 0.00 | 0.00 | 281.61 | 0.00 | 0.817021E+09 | 14941044.36 | 0.00 | 1.04 |
December | 0.226872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325264E+09 | 0.00 | 0.00 | 1.07 |
Annual Sum or Average | 0.111806E+12 | 96498816.41 | 0.00 | 92050661.87 | 5935585.96 | 0.165060E+11 | 0.518062E+11 | 0.00 | 1.62 |
Minimum of Months | 0.155027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
Maximum of Months | 0.226872E+11 | 87430668.47 | 0.00 | 21287960.19 | 5935585.96 | 0.120944E+11 | 0.106338E+11 | 0.00 | 2.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.628921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847248E+11 | 0.00 | 0.00 | 0.52 |
February | 0.446851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612484E+11 | 0.00 | 0.00 | 0.51 |
March | 0.163889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377710E+11 | 0.00 | 0.00 | 0.50 |
April | 0.307779E+11 | 0.00 | 0.00 | 6525875.46 | 0.00 | 0.814605E+10 | 0.705769E+10 | 0.00 | 0.46 |
May | 0.158603E+11 | 0.00 | 0.00 | 72262147.84 | 0.00 | 5780532.72 | 0.512948E+11 | 0.00 | 0.81 |
June | 0.523323E+10 | 599871.93 | 0.00 | 0.162493E+09 | 0.00 | 0.00 | 0.711836E+11 | 0.00 | 1.35 |
July | 0.756039E+10 | 0.253405E+09 | 0.00 | 0.134190E+09 | 24617575.46 | 0.00 | 0.507029E+11 | 0.00 | 1.19 |
August | 0.138132E+11 | 0.00 | 0.00 | 83434764.94 | 0.00 | 0.00 | 0.459658E+11 | 0.00 | 0.91 |
September | 0.328728E+11 | 0.00 | 0.00 | 11346817.46 | 0.00 | 0.166735E+10 | 0.115550E+11 | 0.00 | 0.48 |
October | 0.210193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221757E+11 | 0.00 | 0.00 | 0.46 |
November | 0.150124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771445E+11 | 0.00 | 0.00 | 0.50 |
December | 0.916285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984906E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.151041E+12 | 0.254004E+09 | 0.00 | 0.470252E+09 | 24617575.46 | 0.391374E+12 | 0.237760E+12 | 0.00 | 0.69 |
Minimum of Months | 0.628921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.328728E+11 | 0.253405E+09 | 0.00 | 0.162493E+09 | 24617575.46 | 0.984906E+11 | 0.711836E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111404E+12 | 0.00 | 0.00 | 1.11 |
February | 0.140377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740828E+11 | 0.00 | 0.00 | 1.11 |
March | 0.393366E+11 | 0.00 | 0.00 | 3933461.55 | 0.00 | 0.331100E+11 | 0.406489E+10 | 0.00 | 1.13 |
April | 0.361149E+11 | 0.00 | 0.00 | 42353780.10 | 0.00 | 0.729401E+10 | 0.297657E+11 | 0.00 | 1.12 |
May | 0.224221E+11 | 0.00 | 0.00 | 0.134088E+09 | 0.00 | 8575819.03 | 0.871720E+11 | 0.00 | 1.96 |
June | 0.139372E+11 | 628378.25 | 0.00 | 0.145198E+09 | 0.00 | 0.00 | 0.776796E+11 | 0.00 | 2.37 |
July | 0.170871E+11 | 0.235438E+09 | 0.00 | 0.147973E+09 | 36521871.32 | 0.00 | 0.573289E+11 | 0.00 | 2.26 |
August | 0.229454E+11 | 0.00 | 0.00 | 0.101017E+09 | 0.00 | 9661313.69 | 0.612707E+11 | 0.00 | 1.85 |
September | 0.506929E+11 | 0.00 | 0.00 | 20385737.64 | 0.00 | 0.201259E+10 | 0.163332E+11 | 0.00 | 1.10 |
October | 0.357839E+11 | 0.00 | 0.00 | 1077779.73 | 0.00 | 0.265930E+11 | 0.926181E+09 | 0.00 | 1.05 |
November | 0.212538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107055E+12 | 0.00 | 0.00 | 1.11 |
December | 0.158646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133888E+12 | 0.00 | 0.00 | 1.10 |
Annual Sum or Average | 0.257239E+12 | 0.236066E+09 | 0.00 | 0.596027E+09 | 36521871.32 | 0.495457E+12 | 0.334541E+12 | 0.00 | 1.44 |
Minimum of Months | 0.116918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
Maximum of Months | 0.506929E+11 | 0.235438E+09 | 0.00 | 0.147973E+09 | 36521871.32 | 0.133888E+12 | 0.871720E+11 | 0.00 | 2.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158225E+12 | 0.00 | 0.00 | 1.09 |
February | 0.417185E+11 | 0.00 | 0.00 | 6239326.31 | 0.00 | 0.872100E+11 | 0.561212E+10 | 0.00 | 1.10 |
March | 0.533754E+11 | 0.00 | 0.00 | 59957290.80 | 0.00 | 0.389488E+11 | 0.385252E+11 | 0.00 | 1.24 |
April | 0.417523E+11 | 0.00 | 0.00 | 0.157790E+09 | 0.00 | 0.783772E+10 | 0.999860E+11 | 0.00 | 1.45 |
May | 0.456598E+11 | 0.00 | 0.00 | 0.167428E+09 | 0.00 | 13058137.22 | 0.111190E+12 | 0.00 | 1.94 |
June | 0.336536E+11 | 1347055.60 | 0.00 | 0.182647E+09 | 0.00 | 0.00 | 0.858533E+11 | 0.00 | 2.22 |
July | 0.377374E+11 | 0.525329E+09 | 0.00 | 0.195675E+09 | 53330706.56 | 0.00 | 0.581128E+11 | 0.00 | 2.09 |
August | 0.404334E+11 | 0.00 | 0.00 | 0.191093E+09 | 0.00 | 0.00 | 0.923912E+11 | 0.00 | 2.09 |
September | 0.595284E+11 | 0.00 | 0.00 | 82337598.19 | 0.00 | 0.213918E+10 | 0.625795E+11 | 0.00 | 1.30 |
October | 0.550484E+11 | 0.00 | 0.00 | 26457549.39 | 0.00 | 0.291460E+11 | 0.177250E+11 | 0.00 | 1.08 |
November | 0.294290E+11 | 0.00 | 0.00 | 707044.98 | 0.00 | 0.135792E+12 | 0.969186E+09 | 0.00 | 1.09 |
December | 0.275228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203497E+12 | 0.00 | 0.00 | 1.08 |
Annual Sum or Average | 0.454190E+12 | 0.526676E+09 | 0.00 | 0.107033E+10 | 53330706.56 | 0.662808E+12 | 0.572944E+12 | 0.00 | 1.48 |
Minimum of Months | 0.275228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
Maximum of Months | 0.595284E+11 | 0.525329E+09 | 0.00 | 0.195675E+09 | 53330706.56 | 0.203497E+12 | 0.111190E+12 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112783E+12 | 0.00 | 0.00 | 1.13 |
February | 0.125440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771310E+11 | 0.00 | 0.00 | 1.13 |
March | 0.366222E+11 | 0.00 | 0.00 | 549204.56 | 0.00 | 0.398043E+11 | 0.134948E+10 | 0.00 | 1.14 |
April | 0.419841E+11 | 0.00 | 0.00 | 37759312.90 | 0.00 | 0.631949E+10 | 0.291297E+11 | 0.00 | 1.21 |
May | 0.359773E+11 | 0.00 | 0.00 | 64608520.17 | 0.00 | 15878070.27 | 0.485238E+11 | 0.00 | 1.60 |
June | 0.195966E+11 | 420883.08 | 0.00 | 0.116799E+09 | 0.00 | 0.00 | 0.514267E+11 | 0.00 | 2.10 |
July | 0.230401E+11 | 0.342256E+09 | 0.00 | 88067639.09 | 37039562.98 | 0.00 | 0.334158E+11 | 0.00 | 1.86 |
August | 0.297797E+11 | 0.00 | 0.00 | 72547340.09 | 0.00 | 0.00 | 0.409948E+11 | 0.00 | 1.70 |
September | 0.559515E+11 | 0.00 | 0.00 | 10242537.26 | 0.00 | 0.198457E+10 | 0.113546E+11 | 0.00 | 1.12 |
October | 0.378013E+11 | 0.00 | 0.00 | 141134.54 | 0.00 | 0.262118E+11 | 0.406644E+09 | 0.00 | 1.07 |
November | 0.783587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103355E+12 | 0.00 | 0.00 | 1.13 |
December | 0.286033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135109E+12 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.305823E+12 | 0.342677E+09 | 0.00 | 0.390714E+09 | 37039562.98 | 0.502714E+12 | 0.216601E+12 | 0.00 | 1.36 |
Minimum of Months | 0.182990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
Maximum of Months | 0.559515E+11 | 0.342256E+09 | 0.00 | 0.116799E+09 | 37039562.98 | 0.135109E+12 | 0.514267E+11 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 48554078.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105000E+11 | 0.00 | 0.00 | 0.69 |
February | 92564684.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758642E+10 | 0.00 | 0.00 | 0.66 |
March | 0.588528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566268E+10 | 0.00 | 0.00 | 0.67 |
April | 0.326514E+10 | 0.00 | 0.00 | 84821.11 | 0.00 | 0.156016E+10 | 0.179517E+09 | 0.00 | 0.60 |
May | 0.290979E+10 | 0.00 | 0.00 | 4119242.71 | 0.00 | 97838709.74 | 0.339516E+10 | 0.00 | 0.81 |
June | 0.838115E+09 | 3561743.43 | 0.00 | 14150484.10 | 0.00 | 0.00 | 0.651261E+10 | 0.00 | 1.33 |
July | 0.109527E+10 | 22726972.18 | 0.00 | 11823437.52 | 2244962.29 | 0.00 | 0.451820E+10 | 0.00 | 1.19 |
August | 0.228478E+10 | 0.00 | 0.00 | 6053096.21 | 0.00 | 54657661.51 | 0.339482E+10 | 0.00 | 0.92 |
September | 0.375255E+10 | 0.00 | 0.00 | 49627.62 | 0.00 | 0.967631E+09 | 95117520.90 | 0.00 | 0.62 |
October | 0.107621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351898E+10 | 0.00 | 0.00 | 0.62 |
November | 40156504.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943718E+10 | 0.00 | 0.00 | 0.66 |
December | 62827649.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124133E+11 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.160545E+11 | 26288715.62 | 0.00 | 36280709.27 | 2244962.29 | 0.517988E+11 | 0.180954E+11 | 0.00 | 0.79 |
Minimum of Months | 40156504.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.375255E+10 | 22726972.18 | 0.00 | 14150484.10 | 2244962.29 | 0.124133E+11 | 0.651261E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56968363.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985982E+10 | 0.00 | 0.00 | 1.07 |
February | 0.218618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733606E+10 | 0.00 | 0.00 | 1.09 |
March | 0.255742E+10 | 0.00 | 0.00 | 23370.00 | 0.00 | 0.406492E+10 | 42756863.85 | 0.00 | 1.17 |
April | 0.328527E+10 | 0.00 | 0.00 | 2488574.81 | 0.00 | 0.106538E+10 | 0.175160E+10 | 0.00 | 1.14 |
May | 0.208050E+10 | 0.00 | 0.00 | 11695441.48 | 0.00 | 35870005.55 | 0.770649E+10 | 0.00 | 1.87 |
June | 0.117970E+10 | 2426482.92 | 0.00 | 14464473.10 | 0.00 | 0.00 | 0.778457E+10 | 0.00 | 2.36 |
July | 0.150043E+10 | 20835780.99 | 0.00 | 14574701.54 | 2546405.76 | 0.00 | 0.568405E+10 | 0.00 | 2.26 |
August | 0.208544E+10 | 0.00 | 0.00 | 9224321.14 | 0.00 | 45683241.91 | 0.555177E+10 | 0.00 | 1.81 |
September | 0.418270E+10 | 0.00 | 0.00 | 1136460.02 | 0.00 | 0.643474E+09 | 0.900437E+09 | 0.00 | 1.15 |
October | 0.190883E+10 | 0.00 | 0.00 | 3977.82 | 0.00 | 0.332686E+10 | 11013604.30 | 0.00 | 1.10 |
November | 47536816.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947529E+10 | 0.00 | 0.00 | 1.08 |
December | 73735177.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117829E+11 | 0.00 | 0.00 | 1.05 |
Annual Sum or Average | 0.191771E+11 | 23262263.90 | 0.00 | 53611319.92 | 2546405.76 | 0.476362E+11 | 0.294327E+11 | 0.00 | 1.43 |
Minimum of Months | 47536816.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
Maximum of Months | 0.418270E+10 | 20835780.99 | 0.00 | 14574701.54 | 2546405.76 | 0.117829E+11 | 0.778457E+10 | 0.00 | 2.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.515683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151405E+11 | 0.00 | 0.00 | 1.09 |
February | 0.214071E+10 | 0.00 | 0.00 | 136409.49 | 0.00 | 0.963071E+10 | 0.138190E+09 | 0.00 | 1.11 |
March | 0.389723E+10 | 0.00 | 0.00 | 3480271.26 | 0.00 | 0.498276E+10 | 0.222651E+10 | 0.00 | 1.26 |
April | 0.342019E+10 | 0.00 | 0.00 | 11812456.87 | 0.00 | 0.144260E+10 | 0.809956E+10 | 0.00 | 1.47 |
May | 0.441808E+10 | 0.00 | 0.00 | 14647590.27 | 0.00 | 0.109098E+09 | 0.101806E+11 | 0.00 | 1.88 |
June | 0.337684E+10 | 3927062.55 | 0.00 | 17424876.19 | 0.00 | 0.00 | 0.860123E+10 | 0.00 | 2.23 |
July | 0.378731E+10 | 45033725.27 | 0.00 | 18859662.35 | 4035803.13 | 0.00 | 0.573722E+10 | 0.00 | 2.12 |
August | 0.419479E+10 | 0.00 | 0.00 | 17558476.08 | 0.00 | 79379158.46 | 0.838058E+10 | 0.00 | 2.07 |
September | 0.527860E+10 | 0.00 | 0.00 | 5567439.21 | 0.00 | 0.798360E+09 | 0.441029E+10 | 0.00 | 1.34 |
October | 0.354217E+10 | 0.00 | 0.00 | 1343760.92 | 0.00 | 0.421487E+10 | 0.775160E+09 | 0.00 | 1.15 |
November | 0.839389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142093E+11 | 0.00 | 0.00 | 1.10 |
December | 0.117066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186200E+11 | 0.00 | 0.00 | 1.07 |
Annual Sum or Average | 0.355281E+11 | 48960787.82 | 0.00 | 90830942.63 | 4035803.13 | 0.692276E+11 | 0.485494E+11 | 0.00 | 1.49 |
Minimum of Months | 0.117066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
Maximum of Months | 0.527860E+10 | 45033725.27 | 0.00 | 18859662.35 | 4035803.13 | 0.186200E+11 | 0.101806E+11 | 0.00 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65928199.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103916E+11 | 0.00 | 0.00 | 1.13 |
February | 0.426805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752387E+10 | 0.00 | 0.00 | 1.15 |
March | 0.212459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491572E+10 | 0.00 | 0.00 | 1.23 |
April | 0.346355E+10 | 0.00 | 0.00 | 2858587.37 | 0.00 | 0.113101E+10 | 0.230374E+10 | 0.00 | 1.28 |
May | 0.404159E+10 | 0.00 | 0.00 | 4941840.14 | 0.00 | 0.106444E+09 | 0.385449E+10 | 0.00 | 1.59 |
June | 0.214055E+10 | 5210239.17 | 0.00 | 10864833.38 | 0.00 | 0.00 | 0.494432E+10 | 0.00 | 2.11 |
July | 0.247788E+10 | 30865020.19 | 0.00 | 8281056.88 | 2470534.74 | 0.00 | 0.304470E+10 | 0.00 | 1.89 |
August | 0.347725E+10 | 0.00 | 0.00 | 6118292.86 | 0.00 | 53416120.40 | 0.319020E+10 | 0.00 | 1.71 |
September | 0.473306E+10 | 0.00 | 0.00 | 611191.37 | 0.00 | 0.665292E+09 | 0.650288E+09 | 0.00 | 1.21 |
October | 0.197762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357874E+10 | 0.00 | 0.00 | 1.17 |
November | 81421499.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996775E+10 | 0.00 | 0.00 | 1.14 |
December | 81093551.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124275E+11 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.250913E+11 | 36075259.36 | 0.00 | 33675802.00 | 2470534.74 | 0.507614E+11 | 0.179877E+11 | 0.00 | 1.39 |
Minimum of Months | 65928199.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Maximum of Months | 0.473306E+10 | 30865020.19 | 0.00 | 10864833.38 | 2470534.74 | 0.124275E+11 | 0.494432E+10 | 0.00 | 2.11 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174595E+09 | 0.00 | 0.00 | 1064686.87 | 0.00 | 0.00 | 0.101334E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5987399.20 | 0.00 | 0.00 | 0.973298E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13704441.98 | 0.00 | 0.00 | 0.102480E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 19028790.16 | 0.00 | 0.00 | 0.635596E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3961021.11 | 0.00 | 0.00 | 0.454608E+09 | 0.00 | 0.30 |
June | 0.00 | 1506225.80 | 0.00 | 8157527.73 | 0.00 | 0.00 | 0.251651E+09 | 0.00 | 0.30 |
July | 0.00 | 2249040.33 | 0.00 | 11193138.03 | 0.00 | 0.00 | 0.126402E+09 | 0.00 | 0.28 |
August | 0.00 | 6547.19 | 0.00 | 18309311.68 | 0.00 | 0.00 | 0.262580E+09 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 3647473.09 | 0.00 | 0.00 | 0.540264E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7555618.58 | 0.00 | 0.00 | 0.805165E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10864977.72 | 0.00 | 0.00 | 0.112727E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15737956.34 | 0.00 | 0.00 | 0.120968E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.174595E+09 | 3761813.32 | 0.00 | 0.119212E+09 | 0.00 | 0.00 | 0.842466E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1064686.87 | 0.00 | 0.00 | 0.126402E+09 | 0.00 | 0.28 |
Maximum of Months | 0.174595E+09 | 2249040.33 | 0.00 | 19028790.16 | 0.00 | 0.00 | 0.120968E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879452E+10 | 0.00 | 0.00 | 1677630.51 | 0.00 | 0.00 | 0.280114E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 44787690.28 | 0.00 | 0.00 | 0.974708E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.116542E+09 | 0.00 | 0.00 | 0.102685E+11 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.172751E+09 | 0.00 | 0.00 | 0.637338E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 34202073.97 | 0.00 | 0.00 | 0.455143E+10 | 0.00 | 0.30 |
June | 0.00 | 14783367.21 | 0.00 | 76466742.66 | 0.00 | 0.00 | 0.252401E+10 | 0.00 | 0.30 |
July | 0.00 | 22244610.95 | 0.00 | 0.105741E+09 | 0.00 | 0.00 | 0.127397E+10 | 0.00 | 0.28 |
August | 0.00 | 64255.39 | 0.00 | 0.172208E+09 | 0.00 | 0.00 | 0.263734E+10 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 27340530.44 | 0.00 | 0.00 | 0.541833E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 59078423.89 | 0.00 | 0.00 | 0.806713E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 87955698.04 | 0.00 | 0.00 | 0.112932E+11 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.133080E+09 | 0.00 | 0.00 | 0.121212E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.879452E+10 | 37092233.54 | 0.00 | 0.103183E+10 | 0.00 | 0.00 | 0.770768E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1677630.51 | 0.00 | 0.00 | 0.127397E+10 | 0.00 | 0.28 |
Maximum of Months | 0.879452E+10 | 22244610.95 | 0.00 | 0.172751E+09 | 0.00 | 0.00 | 0.121212E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111357E+10 | 0.00 | 0.00 | 1186.49 | 0.00 | 0.00 | 9038589.04 | 0.00 | 0.28 |
February | 8019940.64 | 0.00 | 0.00 | 3290823.79 | 0.00 | 0.00 | 0.967522E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10171634.73 | 0.00 | 0.00 | 0.102834E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16351917.83 | 0.00 | 0.00 | 0.638264E+09 | 0.00 | 0.29 |
May | 1026065.26 | 0.00 | 0.00 | 3065179.46 | 0.00 | 0.00 | 0.454485E+09 | 0.00 | 0.30 |
June | 0.00 | 1483394.82 | 0.00 | 7588510.90 | 0.00 | 0.00 | 0.252595E+09 | 0.00 | 0.30 |
July | 0.00 | 2224821.48 | 0.00 | 10515894.90 | 0.00 | 0.00 | 0.127582E+09 | 0.00 | 0.28 |
August | 0.00 | 6351.51 | 0.00 | 16963384.86 | 0.00 | 0.00 | 0.264172E+09 | 0.00 | 0.30 |
September | 50630456.30 | 0.00 | 0.00 | 1834917.88 | 0.00 | 0.00 | 0.492239E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 4602837.61 | 0.00 | 0.00 | 0.808054E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 7487381.11 | 0.00 | 0.00 | 0.113063E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12015763.47 | 0.00 | 0.00 | 0.121341E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.117325E+10 | 3714567.82 | 0.00 | 93889433.04 | 0.00 | 0.00 | 0.738633E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1186.49 | 0.00 | 0.00 | 9038589.04 | 0.00 | 0.28 |
Maximum of Months | 0.111357E+10 | 2224821.48 | 0.00 | 16963384.86 | 0.00 | 0.00 | 0.121341E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.213273E+09 | 0.00 | 0.00 | 0.312588E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.398914E+09 | 0.00 | 0.00 | 0.257048E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.745534E+09 | 0.00 | 0.00 | 0.273612E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.950070E+09 | 0.00 | 0.00 | 0.173677E+11 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.213098E+09 | 0.00 | 0.00 | 0.118744E+11 | 0.00 | 0.33 |
June | 0.00 | 41890543.06 | 0.00 | 0.400545E+09 | 0.00 | 0.00 | 0.558711E+10 | 0.00 | 0.34 |
July | 0.00 | 56731584.22 | 0.00 | 0.531738E+09 | 0.00 | 0.00 | 0.244262E+10 | 0.00 | 0.32 |
August | 0.00 | 242375.68 | 0.00 | 0.902040E+09 | 0.00 | 0.00 | 0.561549E+10 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.00 | 0.222820E+09 | 0.00 | 0.00 | 0.128647E+11 | 0.00 | 0.33 |
October | 0.00 | 0.00 | 0.00 | 0.438138E+09 | 0.00 | 0.00 | 0.207168E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.633742E+09 | 0.00 | 0.00 | 0.297165E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.889495E+09 | 0.00 | 0.00 | 0.317756E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 98864502.96 | 0.00 | 0.653941E+10 | 0.00 | 0.00 | 0.222286E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213098E+09 | 0.00 | 0.00 | 0.244262E+10 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 56731584.22 | 0.00 | 0.950070E+09 | 0.00 | 0.00 | 0.317756E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.125649E+11 | 0.239063E+11 | 0.00 | 0.277705E+13 | 0.842180E+12 |
February | 0.838123E+11 | 0.195769E+11 | 0.00 | 0.249958E+13 | 0.101867E+13 |
March | 0.384963E+12 | 0.298662E+11 | 0.00 | 0.290039E+13 | 0.141832E+13 |
April | 0.672256E+12 | 0.331599E+11 | 0.00 | 0.246921E+13 | 0.167691E+13 |
May | 0.826374E+12 | 0.197864E+11 | 0.00 | 0.249729E+13 | 0.702446E+12 |
June | 0.851364E+12 | 0.110833E+11 | 0.00 | 0.202316E+13 | 0.160406E+13 |
July | 0.772855E+12 | 0.889753E+10 | 0.00 | 0.211011E+13 | 0.222350E+13 |
August | 0.583367E+12 | 0.104506E+11 | 0.00 | 0.228257E+13 | 0.225419E+13 |
September | 0.280168E+12 | 0.122971E+11 | 0.00 | 0.248623E+13 | 0.535177E+12 |
October | 0.130824E+12 | 0.259367E+11 | 0.00 | 0.262041E+13 | 0.992831E+12 |
November | 0.146634E+11 | 0.910773E+10 | 0.00 | 0.287912E+13 | 0.150794E+13 |
December | -0.307936E+11 | 0.175214E+11 | 0.00 | 0.291112E+13 | 0.201335E+13 |
Annual Sum or Average | 0.455729E+13 | 0.221590E+12 | 0.00 | 0.304562E+14 | 0.167896E+14 |
Minimum of Months | -0.307936E+11 | 0.889753E+10 | 0.00 | 0.202316E+13 | 0.535177E+12 |
Maximum of Months | 0.851364E+12 | 0.331599E+11 | 0.00 | 0.291112E+13 | 0.225419E+13 |