Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 09:03:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 35491.17 | 766.21 | 766.21 |
Net Site Energy | 35491.17 | 766.21 | 766.21 |
Total Source Energy | 104601.31 | 2258.21 | 2258.21 |
Net Source Energy | 104601.31 | 2258.21 | 2258.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2930.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3809.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 904.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3038.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 576.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 983.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4859.42 |
Humidification | 1281.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 813.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31746.94 | 3744.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7616.24 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2930.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3809.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 904.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 3038.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 576.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 983.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4859.42 |
Humidification | General | 1281.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 813.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2930.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3809.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 904.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 3038.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 576.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 983.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4859.42 |
Humidification | Unassigned | 1281.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.65 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 813.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.18 | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.38 | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.18 | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 685.38 | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31746.944 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31746.944 | 100.00 |
Total On-Site and Utility Electric Sources | 31746.944 | 100.00 |
Total Electricity End Uses | 31746.944 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7616.24 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7616.24 | 100.00 |
Total Water End Uses | 7616.24 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.67 |
Time Setpoint Not Met During Occupied Cooling | 1566.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.1390 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.1390 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1390 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.1390 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.1390 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.1390 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.1390 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8180 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-15:09 | 23-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 26-JUN-15:09 |
Heating | 0.00 | 1918931.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 473581.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 86589.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290018.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65303.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83544.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 38183.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2175458.54 | 1927078.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1918931.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 473581.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 290018.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 65303.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 83544.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 38183.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12065.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2864.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6326.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9623.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1824.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3114.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4057.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 882.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 100542.57 | 4058.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 260.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 67.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2170.59 | 87.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 68.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 260.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 67.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2170.59 | 87.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.90 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.601406 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.75 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.588921 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.35 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.26 | 0.262002 | 0.300000 | 2.18 | 0.698672 | 0.500000 | 0.001454 | 0.000156 | 2.18 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 68.34 | 0.278313 | 0.300000 | 20.50 | 0.742167 | 0.500000 | 0.001369 | 0.003987 | 20.50 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.98 | 0.272354 | 0.300000 | 2.10 | 0.726277 | 0.500000 | 0.001399 | 0.000927 | 3.89 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.18 | 0.202865 | 0.300000 | 0.353171 | 0.540974 | 0.500000 | 0.001878 | 0.000128 | 0.539076 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.41 | 0.108921 | 0.300000 | 0.423899 | 0.300000 | 0.500000 | 0.003498 | 0.000094 | 0.423899 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.61 | 0.148370 | 0.300000 | 0.482900 | 0.395653 | 0.500000 | 0.002568 | 0.000150 | 0.630142 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.79 | 0.085820 | 0.300000 | 0.538004 | 0.300000 | 0.500000 | 0.004440 | 0.000087 | 0.538004 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.04 | 0.216350 | 0.300000 | 3.31 | 0.576933 | 0.500000 | 0.001761 | 0.002073 | 8.71 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.83 | 0.103783 | 0.300000 | 4.45 | 0.300000 | 0.500000 | 0.003671 | 0.001391 | 5.84 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 15.70 | 0.152121 | 0.300000 | 4.71 | 0.405657 | 0.500000 | 0.002505 | 0.002095 | 8.80 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 16.20 | 0.095027 | 0.300000 | 4.86 | 0.300000 | 0.500000 | 0.004009 | 0.001331 | 5.59 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.30 | 0.184334 | 0.300000 | 0.388676 | 0.491557 | 0.500000 | 0.002067 | 0.000282 | 1.19 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.49 | 0.103250 | 0.300000 | 0.447180 | 0.300000 | 0.500000 | 0.003690 | 0.000188 | 0.788818 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.75 | 0.136514 | 0.300000 | 0.524838 | 0.364038 | 0.500000 | 0.002791 | 0.000285 | 1.20 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.75 | 0.087831 | 0.300000 | 0.525687 | 0.300000 | 0.500000 | 0.004338 | 0.000184 | 0.772945 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17799.89 | 0.000156 | 358.83 |
CORE_MID VAV BOX REHEAT COIL | 455795.52 | 0.003987 | 11102.80 |
CORE_TOP VAV BOX REHEAT COIL | 105937.95 | 0.000927 | 2795.18 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14677.80 | 0.000128 | 387.18 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10751.09 | 0.000094 | 275.04 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17152.00 | 0.000150 | 452.39 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9970.98 | 0.000087 | 230.04 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 236946.62 | 0.002073 | 6247.57 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 158947.88 | 0.001391 | 4190.86 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 239498.35 | 0.002095 | 6314.80 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 152100.72 | 0.001331 | 4010.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32220.87 | 0.000282 | 849.42 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21447.30 | 0.000188 | 565.39 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32532.30 | 0.000285 | 857.62 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21016.04 | 0.000184 | 554.03 |
VAV_BOT WITH REHEAT HEATING COIL | 73716.75 | 0.000645 | 1180.02 |
VAV_MID WITH REHEAT HEATING COIL | 699935.80 | 0.006123 | 11179.01 |
VAV_TOP WITH REHEAT HEATING COIL | 66719.71 | 0.000584 | 1084.35 |
CAV_BAS HEATING COIL | 292168.50 | 0.002556 | 6371.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.63 | 3.98 | 13.25 | 3.98 | 11.79 | 11.79 | 0.300000 | 0.337183 | 11.79 |
VAV_MID WITH REHEAT | 63.05 | 37.83 | 126.11 | 43.97 | 109.87 | 109.87 | 0.300000 | 0.400214 | 109.87 |
VAV_TOP WITH REHEAT | 6.64 | 3.98 | 13.27 | 7.83 | 12.37 | 12.37 | 0.300000 | 0.633182 | 12.37 |
CAV_BAS | 6.90 | 6.90 | 6.90 | 6.90 | 6.90 | 6.90 | 1.00 | 1.00 | 6.90 |
AIRLOOP DATACENTER BASEMENT | 26.35 | 26.35 | 26.35 | 26.35 | 26.35 | 26.35 | 1.00 | 0.999987 | 26.35 |
AIRLOOP DATACENTER BOT | 0.601406 | 0.601406 | 0.601406 | 0.601406 | 0.601406 | 0.601406 | 1.00 | 1.00 | 0.601406 |
AIRLOOP DATACENTER MID | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 1.00 | 1.00 | 5.75 |
AIRLOOP DATACENTER TOP | 0.588921 | 0.588921 | 0.588921 | 0.588921 | 0.588921 | 0.588921 | 1.00 | 1.00 | 0.588921 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.79 | 2.40 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 109.87 | 24.85 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 12.37 | 2.50 |
CAV_BAS_OA_CONTROLLER | 6.90 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.35 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.601406 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.75 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.588921 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.09 | 6.67 | 10.52 | 0.006937 | 0.006937 | 182680.54 | 0.007772 | 11.79 |
VAV_MID WITH REHEAT COOLING COIL | 26.39 | 6.67 | 10.52 | 0.006896 | 0.006896 | 1734326.69 | 0.073782 | 109.87 |
VAV_TOP WITH REHEAT COOLING COIL | 26.00 | 6.67 | 10.52 | 0.006918 | 0.006918 | 190571.55 | 0.008107 | 12.37 |
CAV_BAS COOLING COIL | 25.80 | 6.67 | 10.95 | 0.007099 | 0.007099 | 101906.94 | 0.004335 | 6.90 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.79 |
VAV_MID WITH REHEAT FAN | 109.87 |
VAV_TOP WITH REHEAT FAN | 12.37 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007772 | 0.000061 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000645 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073782 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006123 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008107 | 0.000059 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000584 | |
CAV_BAS_COOLC_CONTROLLER | 0.004335 | 0.000110 |
CAV_BAS_HEATC_CONTROLLER | 0.002556 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.90 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.35 | 478002.60 | 250502.35 | 0.011706 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.601406 | 10605.13 | 5613.55 | 0.000260 |
AIRLOOP DATACENTER MID COOLING COIL | 5.75 | 101449.93 | 53688.94 | 0.002485 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.588921 | 10386.82 | 5497.43 | 0.000254 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.35 | 26.35 | 26.35 | 26.35 | 478002.60 | 478002.60 | 19243.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.601406 | 0.601406 | 0.601406 | 0.601406 | 10605.13 | 10605.13 | 888.99 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.75 | 5.75 | 5.75 | 5.75 | 101449.93 | 101449.93 | 8889.90 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.588921 | 0.588921 | 0.588921 | 0.588921 | 10386.82 | 10386.82 | 888.99 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.35 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.601406 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.75 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.588921 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.35 | 478002.60 | 0.011706 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.601406 | 10605.13 | 0.000260 |
AIRLOOP DATACENTER MID HEATING COIL | 5.75 | 101449.93 | 0.002485 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.588921 | 10386.82 | 0.000254 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 19243.92 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 888.99 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8889.90 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 888.99 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000175 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.093997 | 19369.22 | |
HEATSYS1 PUMP | 0.023265 | 7006.41 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.093997 | 11.28 |
HEATSYS1 | 0.023265 | 2.79 |
COOLSYS1_SUPPLY | 0.093997 | 11.28 |
SINGLE WATER PLANT LOOP | 0.014705 | 1.76 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.093997 | 0.093997 | 394551.02 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2659336.07 | 2659336.07 | 0.023265 |
CENTRAL BOILER | 605713.62 | 591890.33 | 0.014705 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.093997 | 13409.97 |
PLANT CIRC PUMP | 0.014705 | 3750.47 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.093997 | 0.047358 | 1115932.15 | 1121225.54 | 0.055697 |
COOLSYS1 CHILLER2 | 0.093997 | 0.047358 | 1115932.15 | 1121225.54 | 0.055697 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014705 | 139666.47 | 54731.58 | 69833.23 | 7879.72 | 20929.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.111395 | 13.37 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.111395 | 33549.66 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 55.60 | 1331990.10 | 11.12 | 166498.76 |
TOWERWATERSYS COOLTOWER 2 | 55.60 | 1331990.10 | 11.12 | 166498.76 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.057633 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.139 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.981 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.139 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.562 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25401.240 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25401.240 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7162.063 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7162.063 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.132 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.057 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.468 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7163 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7788 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5137 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.13403145E-14 | 0.38554392E-16 | -0.14019045E-09 | -0.57508437E-17 |
51 | 8 | 0.20532604E-07 | 0.15070655E-12 | 0.36354762E-03 | -0.23346278E-09 |
52 | 7 | -0.11816003E-01 | 0.79423826E-08 | -0.22472937E-01 | 0.13435225E-03 |
53 | 6 | 0.39378663 | 0.27841024E-05 | 0.46223068 | -0.46114540E-02 |
54 | 5 | -5.0777070 | 0.10463539E-03 | -4.3654760 | 0.61784485E-01 |
55 | 4 | 32.503611 | 0.86100720E-03 | 21.143998 | -0.41549437 |
56 | 3 | -110.16389 | 0.18863771E-02 | -55.038103 | 1.4998468 |
57 | 2 | 196.07818 | 0.10660615E-02 | 77.337676 | -2.8839958 |
58 | 1 | -170.77553 | 0.11429885E-03 | -55.098892 | 2.7387699 |
59 | 0 | 57.057407 | 0.65377189E-06 | 15.584712 | |
60 | 9 | -0.15090952E-15 | 0.38559946E-16 | -0.14372032E-09 | 0.30204083E-17 |
61 | 8 | 0.21031043E-07 | 0.14138600E-12 | 0.36887497E-03 | -0.23913020E-09 |
62 | 7 | -0.11975277E-01 | 0.74086432E-08 | -0.22702364E-01 | 0.13616326E-03 |
63 | 6 | 0.39811484 | 0.25910953E-05 | 0.46592450 | -0.46624730E-02 |
64 | 5 | -5.1199506 | 0.97191092E-04 | -4.3938804 | 0.62308282E-01 |
65 | 4 | 32.690498 | 0.79834332E-03 | 21.255101 | -0.41797567 |
66 | 3 | -110.56161 | 0.17463541E-02 | -55.257788 | 1.5055927 |
67 | 2 | 196.47247 | 0.98555898E-03 | 77.539021 | -2.8902570 |
68 | 1 | -170.92122 | 0.10553222E-03 | -55.157180 | 2.7413232 |
69 | 0 | 57.057407 | 0.60276357E-06 | 15.574872 | |
70 | 9 | 0.86852889E-15 | 0.51837175E-16 | -0.12412508E-09 | -0.62404215E-17 |
71 | 8 | 0.18264368E-07 | 0.19079871E-12 | 0.33872361E-03 | -0.20767217E-09 |
72 | 7 | -0.11071833E-01 | 0.10339392E-07 | -0.21400306E-01 | 0.12589076E-03 |
73 | 6 | 0.37356127 | 0.36650528E-05 | 0.44491930 | -0.43730477E-02 |
74 | 5 | -4.8802711 | 0.13907014E-03 | -4.2321352 | 0.59336424E-01 |
75 | 4 | 31.629927 | 0.11542129E-02 | 20.621944 | -0.40389484 |
76 | 3 | -108.30396 | 0.25479898E-02 | -54.005619 | 1.4729777 |
77 | 2 | 194.23353 | 0.14496506E-02 | 76.392304 | -2.8547049 |
78 | 1 | -170.09368 | 0.15639004E-03 | -54.826917 | 2.7268196 |
79 | 0 | 57.057407 | 0.90049143E-06 | 15.632017 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77518.37346 | 77518.37346 | 6.89962 | 6.89962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81572.07615 | 81572.07615 | 7.25965 | 7.25965 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 768075.17837 | 768075.17837 | 68.34201 | 68.34201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 288228.23018 | 288228.23018 | 15.01914 | 15.01914 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77807.95933 | 77807.95933 | 6.98372 | 6.98372 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 74154.53446 | 74154.53446 | 3.88884 | 3.88884 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13116.36332 | 13116.36332 | 1.17724 | 1.17724 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10274.75454 | 10274.75454 | 0.53908 | 0.53908 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15743.52147 | 15743.52147 | 1.41300 | 1.41300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.88533 | 5.46009E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7288.50675 | 7288.50675 | 0.38253 | 0.38253 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17934.39341 | 17934.39341 | 1.60967 | 1.60967 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12004.33280 | 12004.33280 | 0.63014 | 0.63014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19981.04820 | 19981.04820 | 1.79335 | 1.79335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5578.00519 | 5578.00519 | 0.29243 | 0.29243 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 122990.26147 | 122990.26147 | 11.03863 | 11.03863 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 165805.75444 | 165805.75444 | 8.71103 | 8.71103 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 165228.75741 | 165228.75741 | 14.82948 | 14.82948 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 111222.38830 | 111222.38830 | 5.84387 | 5.84387 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 174923.57908 | 174923.57908 | 15.69970 | 15.69970 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 167589.76779 | 167589.76779 | 8.80498 | 8.80498 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 180453.84928 | 180453.84928 | 16.19596 | 16.19596 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 106434.99925 | 106434.99925 | 5.59182 | 5.59182 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14435.27626 | 14435.27626 | 1.29559 | 1.29559 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 22542.92555 | 22542.92555 | 1.18502 | 1.18502 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16608.24309 | 16608.24309 | 1.49060 | 1.49060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15005.13510 | 15005.13510 | 0.78882 | 0.78882 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19492.32854 | 19492.32854 | 1.74946 | 1.74946 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 22760.66770 | 22760.66770 | 1.19648 | 1.19648 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19523.96921 | 19523.96921 | 1.75229 | 1.75229 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 14703.56879 | 14703.56879 | 0.77295 | 0.77295 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8495.31144 | 8495.31144 | 0.60141 | 0.60141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81237.47102 | 81237.47102 | 5.75106 | 5.75106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8318.92218 | 8318.92218 | 0.58892 | 0.58892 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 28.86800 | 5.46756E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372239.13792 | 372239.13792 | 26.35146 | 26.35146 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 03:10:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 148358.49 | 11.79142 | 11.79142 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 72597.36 | 2.92201 | 2.92201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1375207.70 | 109.86823 | 109.86823 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 741166.65 | 43.97084 | 43.97084 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 160190.12 | 12.36945 | 12.36945 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 75353.85 | 7.83211 | 7.83211 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 78046.26 | 6.89962 | 6.89962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68251.22 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369340.76 | 26.35180 | 26.35180 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 19243.92 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8412.79 | 0.60141 | 0.60141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80453.23 | 5.75106 | 5.75106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8889.90 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8241.43 | 0.58892 | 0.58892 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.89962 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.25965 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.17790 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69867 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45419E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55721E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.17790 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17799.89161 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55721E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 358.83184 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 68.34201 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27831 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 20.50260 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74217 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36896E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.98750E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 20.50260 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 455795.51813 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.98750E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11102.79798 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.98372 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27235 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.09512 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72628 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39892E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.26791E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.88884 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105937.94942 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.26791E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2795.17762 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17724 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20287 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35317 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54097 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87809E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28408E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53908 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14677.79840 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28408E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 387.18437 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41300 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10892 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42390 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49794E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.40552E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42390 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10751.09079 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.40552E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.03781 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60967 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14837 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48290 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39565 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56791E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50053E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63014 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17151.99784 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50053E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 452.38681 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79335 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.58201E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.43952E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.72305E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53800 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9970.98018 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.72305E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.03937 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.03863 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21635 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.31159 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57693 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76104E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07291E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.71103 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 236946.61730 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07291E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6247.56622 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.82948 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10378 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.44884 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67112E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39055E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.84387 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 158947.88138 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39055E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4190.85753 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.69970 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15212 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.70991 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40566 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50458E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09524E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.80498 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 239498.34729 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09524E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6314.80273 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.19596 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.50268E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.85879 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.00940E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33064E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.59182 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 152100.71971 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33064E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4010.42580 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29559 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18433 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38868 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49156 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06690E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81882E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18502 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32220.86963 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81882E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 849.41615 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49060 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10325 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44718 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69006E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87630E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78882 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21447.30256 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87630E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 565.39055 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74946 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13651 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52484 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36404 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79092E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.84607E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19648 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32532.29876 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.84607E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 857.62224 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.75229 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.78308E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52569 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.33788E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83857E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77295 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21016.03680 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83857E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 554.02513 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60141 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.75106 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58892 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.35146 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.62645 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.97587 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.25290 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.97587 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.79142 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.79142 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33718 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 63.05289 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 37.83174 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 126.10579 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 43.97084 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 109.86823 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 109.86823 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40021 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.63583 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.98150 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.27166 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.83211 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.36945 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.36945 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.63318 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.89962 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.89962 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.89962 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.89962 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.89962 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.89962 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.35146 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.35146 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.35146 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.35146 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.35180 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.35180 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60141 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60141 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60141 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60141 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60141 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.60141 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.75106 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.75106 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75106 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.75106 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.75106 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.75106 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58892 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58892 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58892 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58892 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58892 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.58892 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.79142 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 109.86823 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.36945 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.89962 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.35180 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.60141 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.75106 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.58892 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.79142 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.40109 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.09055 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51647 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.93669E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.93669E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 182680.54481 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.77165E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.79142 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 73716.75013 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.44906E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1180.01807 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.79142 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.77165E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.12727E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.44906E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 109.86823 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 24.84725 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.38596 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51630 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.89554E-003 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.89554E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1734326.68722 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.37823E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 109.86823 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 699935.80368 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.12334E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11179.01475 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 109.86823 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.37823E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.45400E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.12334E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.36945 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.50203 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.00451 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51639 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.91820E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.91820E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 190571.55140 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.10735E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.36945 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 66719.71157 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.83693E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1084.35093 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.36945 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.10735E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.87356E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.83693E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.89962 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.79693 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95377 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09893E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09893E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 101906.93773 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.33536E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.89962 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 292168.50401 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.55602E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6371.06377 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.89962 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.33536E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09839E-004 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.55602E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.35180 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.35180 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 478002.60175 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 250502.34909 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17063E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.35180 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.35180 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.35180 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.35180 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 478002.60175 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 478002.60175 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 19243.92393 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.35180 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.35180 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 478002.60175 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.17063E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19243.92393 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.75196E-004 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60141 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60141 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10605.12542 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5613.54697 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.59719E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.60141 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.60141 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.60141 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.60141 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10605.12542 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10605.12542 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60141 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60141 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10605.12542 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.59719E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.75106 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.75106 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 101449.93373 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 53688.93532 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48450E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.75106 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.75106 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.75106 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.75106 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 101449.93373 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 101449.93373 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8889.89563 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.75106 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.75106 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 101449.93373 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48450E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8889.89563 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58892 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58892 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10386.81671 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5497.42820 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54372E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58892 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58892 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58892 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58892 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10386.81671 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10386.81671 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58892 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58892 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10386.81671 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54372E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.39966E-002 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 19369.22165 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.39966E-002 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.27960 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.39966E-002 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.39966E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 394551.02164 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.32650E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.79180 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.32650E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7006.40597 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2659336.06916 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2659336.07000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.32650E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.39966E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.27960 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.39966E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13409.96552 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.39966E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.73580E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1115932.15206 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1121225.54500 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.56974E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.39966E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.73580E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1115932.15206 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1121225.54500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.56974E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.47048E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.76458 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.47048E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3750.47124 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.47048E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54731.58134 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20929.91128 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 605713.61501 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 591890.33000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47048E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11139 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.36737 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11139 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33549.66197 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 55.60120 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1331990.10199 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.12024 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 166498.76275 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 55.60120 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1331990.10199 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.12024 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 166498.76275 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.76325E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.76325E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16880.74 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 431976.62 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 100421.22 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13912.84 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10187.34 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16257.66 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9451.26 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 224578.62 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 150650.42 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 226996.86 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 144161.39 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30538.00 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20327.06 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30833.14 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19918.35 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 53554.60 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 506182.80 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 50067.62 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 226030.25 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 251659.58 | 158871.32 | 92788.26 | 0.63 | 26136.63 | 265.09 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2364384.52 | 1487791.08 | 876593.44 | 0.63 | 244748.68 | 2482.38 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 263431.60 | 166440.22 | 96991.38 | 0.63 | 27376.88 | 277.67 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 140805.70 | 90043.31 | 50762.39 | 0.64 | 14065.23 | 142.66 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2297495655 | 0.1893736396 | Pass | Pass | 8.9133558954 | 61.9460731832 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.4203168072E-002 | 0.1742256869 | Pass | Pass | 0.1327622752 | 0.3381919853 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.0024747454E-002 | 0.1025884415 | Pass | Pass | 0.1049808610 | 0.3059510563 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.1666852342E-002 | 3.6895026863E-002 | Pass | Pass | 0.4592774905 | 0.4836538617 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.2263308374E-002 | 0.1361811867 | Pass | Pass | 0.1330176916 | 0.3378363519 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1985725800 | 0.3200171334 | Pass | Pass | 0.1364000718 | 0.3432764130 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2461196818 | 0.3879185372 | Pass | Pass | 0.1378742753 | 0.3479125397 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1950034481 | 0.3630023154 | Pass | Pass | 0.1335524133 | 0.3325083322 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.0139446384E-002 | 4.4508068089E-002 | Pass | Pass | 0.1047945160 | 0.3006235779 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1351111385 | 0.2098325448 | Pass | Pass | 0.1102737379 | 0.3166970076 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2621091238 | 0.3866144854 | Pass | Pass | 0.1136690520 | 0.3138337198 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1198901845 | 0.1872371438 | Pass | Pass | 0.1033376704 | 0.2933830050 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3141101226 | 0.3410316554 | Pass | Pass | 7.1819683388 | 32.8600027997 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2194623677 | 0.2724314208 | Pass | Pass | 1.9472014315 | 9.9012269566 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2346588997 | 0.2564305099 | Pass | Pass | 0.5548296966 | 0.8784666547 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1672862044 | 0.2019339707 | Pass | Pass | 0.7534694741 | 1.3879177375 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2243014879E-002 | 3.1015122560E-002 | Pass | Pass | 0.2467965199 | 0.6763011122 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6411449823E-002 | 3.8907807843E-002 | Pass | Pass | 0.6087726854 | 3.8242662350 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1284802790 | 0.1053631866 | Pass | Pass | 0.5354068689 | 0.5748292560 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2145950858E-006 | 7.8712180650E-006 | Pass | Pass | 7.4104136269E-003 | 9.1470049007E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5193571535E-003 | 2.6958855556E-002 | Pass | Pass | 0.1877422929 | 0.5996307145 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.6536142832E-002 | 5.3784089177E-002 | Pass | Pass | 9.0548103650E-003 | 1.4994196745E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1934534228E-006 | 1.8783602159E-006 | Pass | Pass | 5.5171353045E-005 | 1.0503926204E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8209.43 | 192.97 | 0.00 | 21049.52 | 23582.80 | 53034.70 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1390 | 2779.43 | 25401.24 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 235.63 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.1390 | 24961.20 | 228120.99 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 2116.09 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.1390 | 3134.13 | 28642.87 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.1390 | 3134.20 | 28643.49 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.1390 | 783.68 | 7162.06 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 66.44 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 11.7111 | 362.03 | 4239.75 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 43.70 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
Interior Lighting Total | 9.1631 | 46320.38 | 424440.34 | 1212.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 57580.60 | AstronomicalClock | - | 83.67 | 83.67 | 904.37 | |
Exterior Lighting Total | 57580.60 | 904.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2204404.56 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2659336.07 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1121225.54 | 6.11 | 1072404.54 | 5.82 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1121225.54 | 6.11 | 1072404.54 | 5.82 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 591890.33 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1331990.10 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1331990.10 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 182680.54 | 251659.58 | 158871.32 | 92788.26 | 0.63 | - | 26136.63 | 265.09 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1734326.69 | 2364384.52 | 1487791.08 | 876593.44 | 0.63 | - | 244748.68 | 2482.38 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 190571.55 | 263431.60 | 166440.22 | 96991.38 | 0.63 | - | 27376.88 | 277.67 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 101906.94 | 140805.70 | 90043.31 | 50762.39 | 0.64 | - | 14065.23 | 142.66 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 478002.60 | 250502.35 | 227500.25 | 0.52 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10605.13 | 5613.55 | 4991.58 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 101449.93 | 53688.94 | 47761.00 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10386.82 | 5497.43 | 4889.39 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17799.89 | 16880.74 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 455795.52 | 431976.62 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 105937.95 | 100421.22 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14677.80 | 13912.84 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10751.09 | 10187.34 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17152.00 | 16257.66 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9970.98 | 9451.26 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 236946.62 | 224578.62 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 158947.88 | 150650.42 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 239498.35 | 226996.86 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 152100.72 | 144161.39 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 32220.87 | 30538.00 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21447.30 | 20327.06 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32532.30 | 30833.14 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21016.04 | 19918.35 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 73716.75 | 53554.60 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 699935.80 | 506182.80 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 66719.71 | 50067.62 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 292168.50 | 226030.25 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 478002.60 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10605.13 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 101449.93 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10386.82 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 19243.92 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8889.90 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.79 | 26785.31 | 2271.59 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 109.87 | 249575.93 | 2271.59 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 12.37 | 28098.36 | 2271.59 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 6.90 | 12675.43 | 1837.12 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.35 | 43278.41 | 1642.33 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 673.64 | 1120.11 | 1.00 | 1.53 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.75 | 6441.81 | 1120.11 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.59 | 659.66 | 1120.11 | 1.00 | 1.54 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.093997 | 19369.22 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023265 | 7006.41 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.093997 | 13409.97 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014705 | 3750.47 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.111395 | 33549.66 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77518.37 | 77518.37 | 27.89 | 6.900 | 6.900 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00745 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 81572.08 | 81572.08 | 32.68 | 7.260 | 7.260 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 768075.18 | 768075.18 | 307.71 | 68.342 | 68.342 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 77807.96 | 77807.96 | 31.17 | 6.984 | 6.984 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00739 | 33.90 | 0.00548 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13116.36 | 13116.36 | 41.85 | 1.177 | 1.177 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00726 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15743.52 | 15743.52 | 77.95 | 1.413 | 1.413 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.00 | 24.00 | 0.00714 | 23.89 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17934.39 | 17934.39 | 57.22 | 1.610 | 1.610 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00719 | 33.28 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19981.05 | 19981.05 | 98.93 | 1.793 | 1.793 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00711 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 122990.26 | 122990.26 | 392.42 | 11.039 | 11.039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00723 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 165228.76 | 165228.76 | 818.06 | 14.829 | 14.829 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00711 | 25.76 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 174923.58 | 174923.58 | 558.11 | 15.700 | 15.700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00717 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 180453.85 | 180453.85 | 893.45 | 16.196 | 16.196 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00710 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14435.28 | 14435.28 | 46.06 | 1.296 | 1.296 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00719 | 33.75 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16608.24 | 16608.24 | 82.23 | 1.491 | 1.491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00710 | 26.60 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19492.33 | 19492.33 | 62.19 | 1.749 | 1.749 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00714 | 33.65 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19523.97 | 19523.97 | 96.67 | 1.752 | 1.752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 31.83 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8495.31 | 8495.31 | 234.66 | 0.601 | 0.601 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81237.47 | 81237.47 | 2243.96 | 5.751 | 5.751 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8318.92 | 8318.92 | 229.79 | 0.589 | 0.589 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 28.87 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372239.14 | 372239.14 | 474.99 | 26.351 | 26.351 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | 21.00 | 23.72 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 17.60 | 21.04 | 0.00096 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 288228.23 | 288228.23 | 115.47 | 15.019 | 15.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 74154.53 | 74154.53 | 29.71 | 3.889 | 3.889 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10274.75 | 10274.75 | 32.78 | 0.539 | 0.539 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7288.51 | 7288.51 | 36.09 | 0.383 | 0.383 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12004.33 | 12004.33 | 38.30 | 0.630 | 0.630 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5578.01 | 5578.01 | 27.62 | 0.292 | 0.292 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 165805.75 | 165805.75 | 529.03 | 8.711 | 8.711 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 111222.39 | 111222.39 | 550.67 | 5.844 | 5.844 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 167589.77 | 167589.77 | 534.71 | 8.805 | 8.805 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 106435.00 | 106435.00 | 526.97 | 5.592 | 5.592 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 22542.93 | 22542.93 | 71.93 | 1.185 | 1.185 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15005.14 | 15005.14 | 74.29 | 0.789 | 0.789 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22760.67 | 22760.67 | 72.62 | 1.196 | 1.196 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14703.57 | 14703.57 | 72.80 | 0.773 | 0.773 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 25.27 | 0.00510 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.72 | 0.00179 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.14 | 0.00162 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 03:10:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.79 | 11.79 | 2.92 | 2.92 | 11.7914 | 3.9759 | 11.7914 | 0.3372 | 0.3000 |
VAV_MID WITH REHEAT | 109.87 | 109.87 | 43.97 | 43.97 | 109.8682 | 43.9708 | 109.8682 | 0.4002 | 0.3000 |
VAV_TOP WITH REHEAT | 12.37 | 12.37 | 7.83 | 7.83 | 12.3695 | 7.8321 | 12.3695 | 0.6332 | 0.3000 |
CAV_BAS | 6.90 | 6.90 | 1.20 | 1.20 | 6.8996 | 6.8996 | 6.8996 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.35 | 26.35 | 0.34 | 0.34 | 26.3518 | 26.3515 | 26.3518 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.60 | 0.60 | 0.02 | 0.02 | 0.6014 | 0.6014 | 0.6014 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.75 | 5.75 | 0.16 | 0.16 | 5.7511 | 5.7511 | 5.7511 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.59 | 0.59 | 0.02 | 0.02 | 0.5889 | 0.5889 | 0.5889 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17799.892 | 17799.892 | 2.177896 | 0.00015572 | 358.832 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | 17799.89 | 17799.89 | 2.177896 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 17865.52 | 17865.52 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 455795.518 | 455795.518 | 20.502602 | 0.00398750 | 11102.798 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 455795.52 | 455795.52 | 20.502602 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 288228.23 | 0.00 | 457264.80 | 457264.80 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 105937.949 | 105937.949 | 3.888842 | 0.00092679 | 2795.178 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 105937.95 | 105937.95 | 3.888842 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 74154.53 | 0.00 | 106294.98 | 106294.98 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14677.798 | 14677.798 | 0.539076 | 0.00012841 | 387.184 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14677.80 | 14677.80 | 0.539076 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771975 | 40.5297 | 10274.75 | 0.00 | 14726.62 | 14726.62 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10751.091 | 10751.091 | 0.423899 | 0.00009406 | 275.038 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10751.09 | 10751.09 | 0.423899 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00775781 | 40.7268 | 7288.51 | 0.00 | 10784.22 | 10784.22 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17151.998 | 17151.998 | 0.630142 | 0.00015005 | 452.387 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17152.00 | 17152.00 | 0.630142 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00779177 | 40.9026 | 12004.33 | 0.00 | 17208.58 | 17208.58 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9970.980 | 9970.980 | 0.538004 | 0.00008723 | 230.039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9970.98 | 9970.98 | 0.538004 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00757902 | 39.8005 | 5578.01 | 0.00 | 10004.01 | 10004.01 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 236946.617 | 236946.617 | 8.711031 | 0.00207291 | 6247.566 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 236946.62 | 236946.62 | 8.711031 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768516 | 40.3515 | 165805.75 | 0.00 | 237714.34 | 237714.34 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 158947.881 | 158947.881 | 5.843870 | 0.00139055 | 4190.858 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 158947.88 | 158947.88 | 5.843870 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768758 | 40.3642 | 111222.39 | 0.00 | 159462.03 | 159462.03 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 239498.347 | 239498.347 | 8.804979 | 0.00209524 | 6314.803 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 239498.35 | 239498.35 | 8.804979 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768853 | 40.3690 | 167589.77 | 0.00 | 240274.01 | 240274.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 152100.720 | 152100.720 | 5.591815 | 0.00133064 | 4010.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 152100.72 | 152100.72 | 5.591815 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00767348 | 40.2910 | 106435.00 | 0.00 | 152593.46 | 152593.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 32220.870 | 32220.870 | 1.185018 | 0.00028188 | 849.416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32220.87 | 32220.87 | 1.185018 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771234 | 40.4931 | 22542.93 | 0.00 | 32324.18 | 32324.18 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 21447.303 | 21447.303 | 0.788818 | 0.00018763 | 565.391 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21447.30 | 21447.30 | 0.788818 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771182 | 40.4905 | 15005.14 | 0.00 | 21516.00 | 21516.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 32532.299 | 32532.299 | 1.196484 | 0.00028461 | 857.622 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32532.30 | 32532.30 | 1.196484 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771497 | 40.5067 | 22760.67 | 0.00 | 32636.58 | 32636.58 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 21016.037 | 21016.037 | 0.772945 | 0.00018386 | 554.025 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21016.04 | 21016.04 | 0.772945 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770638 | 40.4623 | 14703.57 | 0.00 | 21083.38 | 21083.38 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 182680.545 | -999.000 | 11.791419 | 0.00777165 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 182680.54 | 182680.54 | 11.791419 | 26.09 | 13.67 | 0.00693669 | 10.52 | 7.74 | 0.00693669 | 33.90 | 0.00547527 | 15.07 | 20.3630 | 24.00 | 0.00732814 | 32.0825 | 126624.66 | 0.00 | 163817.83 | 163817.83 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 73716.750 | 73716.750 | 3.537426 | 0.00064491 | 1180.018 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 73716.75 | 73716.75 | 3.537426 | -8.42 | -8.56 | 0.00219091 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 67.8768 | 21.03 | 0.00527701 | 27.7635 | 29700.53 | 0.00 | 64743.18 | 64743.18 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1734326.687 | -999.000 | 109.868233 | 0.07378227 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1734326.69 | 1734326.69 | 109.868233 | 26.39 | 13.73 | 0.00689554 | 10.52 | 7.70 | 0.00689554 | 33.90 | 0.00547527 | 15.07 | 22.6155 | 24.00 | 0.00734674 | 32.1629 | 1148230.89 | 0.00 | 1551475.21 | 1551475.21 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 699935.804 | 699935.804 | 32.960470 | 0.00612334 | 11179.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 699935.80 | 699935.80 | 32.960470 | -8.82 | -8.82 | 0.00259833 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 75.3850 | 19.35 | 0.00744189 | 43.2913 | 379284.72 | 0.00 | 611992.42 | 611992.42 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 190571.551 | -999.000 | 12.369450 | 0.00810735 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 190571.55 | 190571.55 | 12.369450 | 26.00 | 13.62 | 0.00691820 | 10.52 | 7.72 | 0.00691820 | 33.90 | 0.00547527 | 15.07 | 20.2275 | 24.00 | 0.00728474 | 31.8945 | 137615.23 | 0.00 | 170489.39 | 170489.39 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 66719.712 | 66719.712 | 3.710835 | 0.00058369 | 1084.351 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 66719.71 | 66719.71 | 3.710835 | -5.51 | -5.51 | 0.00312594 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 67.4250 | 17.33 | 0.00760695 | 50.2240 | 46362.34 | 0.00 | 60553.06 | 60553.06 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 101906.938 | -999.000 | 6.899615 | 0.00433536 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 101906.94 | 101906.94 | 6.899615 | 25.80 | 13.70 | 0.00709893 | 10.95 | 8.09 | 0.00709893 | 33.16 | 0.00547412 | 14.83 | 17.3945 | 24.00 | 0.00749579 | 32.8081 | 68116.52 | 0.00 | 92008.45 | 92008.45 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 292168.504 | 292168.504 | 6.899615 | 0.00255602 | 6371.064 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 292168.50 | 292168.50 | 6.899615 | -3.11 | -7.40 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 17.3945 | 23.82 | 0.00095524 | 4.2701 | 0.00 | 0.00 | 238453.50 | 238453.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 478002.602 | 250502.349 | 26.351805 | 0.01170625 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 406287.66 | 405321.26 | -999.0 | 28.80 | 14.64 | 0.00702195 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | -999.0000 | 27.00 | 0.00704210 | 25.8129 | 371792.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10605.125 | 5613.547 | 0.601406 | 0.00025972 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8966.80 | 8924.29 | -999.0 | 28.21 | 14.47 | 0.00704277 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708483 | 25.9659 | 8492.50 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101449.934 | 53688.935 | 5.751061 | 0.00248450 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 85783.17 | 85359.09 | -999.0 | 28.21 | 14.47 | 0.00704461 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708870 | 25.9800 | 81202.80 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10386.817 | 5497.428 | 0.588921 | 0.00025437 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8782.50 | 8739.95 | -999.0 | 28.21 | 14.47 | 0.00704372 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708670 | 25.9727 | 8318.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 478002.602 | 478002.602 | 26.351805 | 0.01170625 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 478002.60 | 478002.60 | 26.351805 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2841 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10605.125 | 10605.125 | 0.601406 | 0.00025972 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10605.13 | 10605.13 | 0.601406 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5993 | 25.87 | 0.00509851 | 20.0357 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 101449.934 | 101449.934 | 5.751061 | 0.00248450 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 101449.93 | 101449.93 | 5.751061 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7182 | 23.89 | 0.00178546 | 7.9367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10386.817 | 10386.817 | 0.588921 | 0.00025437 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10386.82 | 10386.82 | 0.588921 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6544 | 22.30 | 0.00162222 | 7.9444 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 19243.92 | 19243.92 | 26.351805 | -0.23 | -0.23 | 0.00692238 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2841 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.601406 | -0.47 | -0.47 | 0.00499082 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.5993 | 25.87 | 0.00509851 | 20.0357 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8889.90 | 8889.90 | 5.751061 | -0.49 | -4.49 | 0.00176289 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7182 | 23.89 | 0.00178546 | 7.9367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.588921 | -0.48 | -4.74 | 0.00160452 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6544 | 22.30 | 0.00162222 | 7.9444 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17799.892 | 17799.892 | 2.177896 | 0.00015572 | 358.832 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.6561 | 0.669336 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | Sensible | 17799.89 | 17799.89 | 1.0000 | 2.12875728 | 2.177896 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.15570533 | 60.00 | 32.22 | 27.78 | 0.000 | 17799.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 17865.52 | 17865.52 | 2.12875728 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 455795.518 | 455795.518 | 20.502602 | 0.00398750 | 11102.798 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 16.8013 | 17.139448 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 455795.52 | 455795.52 | 1.0000 | 20.04001437 | 20.502602 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 3.98709126 | 60.00 | 32.22 | 27.78 | 0.000 | 455795.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 288228.23 | 0.00 | 457264.80 | 457264.80 | 20.04001437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.18 | 19.71 | 0.00800000 | 55877.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 105937.949 | 105937.949 | 3.888842 | 0.00092679 | 2795.178 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 3.9050 | 3.983624 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 105937.95 | 105937.95 | 1.0000 | 3.80110044 | 3.888842 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.92669685 | 60.00 | 32.22 | 27.78 | 0.000 | 105937.95 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 74154.53 | 0.00 | 106294.98 | 106294.98 | 3.80110044 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14677.798 | 14677.798 | 0.539076 | 0.00012841 | 387.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.5410 | 0.551935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14677.80 | 14677.80 | 1.0000 | 0.52691335 | 0.539076 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.12839468 | 60.00 | 32.22 | 27.78 | 0.000 | 14677.80 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771975 | 21.00 | 0.00771975 | 40.5297 | 10274.75 | 0.00 | 14726.62 | 14726.62 | 0.52691335 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10751.091 | 10751.091 | 0.423899 | 0.00009406 | 275.038 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.3963 | 0.404277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10751.09 | 10751.09 | 1.0000 | 0.41433449 | 0.423899 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09404564 | 60.00 | 32.22 | 27.78 | 0.000 | 10751.09 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00775781 | 21.00 | 0.00775781 | 40.7268 | 7288.51 | 0.00 | 10784.22 | 10784.22 | 0.41433449 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.32 | 20.68 | 0.00800000 | 59087.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17151.998 | 17151.998 | 0.630142 | 0.00015005 | 452.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.6322 | 0.644973 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17152.00 | 17152.00 | 1.0000 | 0.61592497 | 0.630142 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.15003785 | 60.00 | 32.22 | 27.78 | 0.000 | 17152.00 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779177 | 21.00 | 0.00779177 | 40.9026 | 12004.33 | 0.00 | 17208.58 | 17208.58 | 0.61592497 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9970.980 | 9970.980 | 0.538004 | 0.00008723 | 230.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.3675 | 0.374942 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9970.98 | 9970.98 | 1.0000 | 0.52586510 | 0.538004 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.08722159 | 60.00 | 32.22 | 27.78 | 0.000 | 9970.98 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00757902 | 21.00 | 0.00757902 | 39.8005 | 5578.01 | 0.00 | 10004.01 | 10004.01 | 0.52586510 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.46 | 18.52 | 0.00800000 | 52083.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 236946.617 | 236946.617 | 8.711031 | 0.00207291 | 6247.566 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 8.7342 | 8.909991 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 236946.62 | 236946.62 | 1.0000 | 8.51448973 | 8.711031 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.07270091 | 60.00 | 32.22 | 27.78 | 0.000 | 236946.62 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768516 | 21.00 | 0.00768516 | 40.3515 | 165805.75 | 0.00 | 237714.34 | 237714.34 | 8.51448973 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 158947.881 | 158947.881 | 5.843870 | 0.00139055 | 4190.858 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 5.8591 | 5.976976 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 158947.88 | 158947.88 | 1.0000 | 5.71201795 | 5.843870 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.39040356 | 60.00 | 32.22 | 27.78 | 0.000 | 158947.88 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768758 | 21.00 | 0.00768758 | 40.3642 | 111222.39 | 0.00 | 159462.03 | 159462.03 | 5.71201795 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 239498.347 | 239498.347 | 8.804979 | 0.00209524 | 6314.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 8.8283 | 9.005945 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 239498.35 | 239498.35 | 1.0000 | 8.60631805 | 8.804979 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.09502228 | 60.00 | 32.22 | 27.78 | 0.000 | 239498.35 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768853 | 21.00 | 0.00768853 | 40.3690 | 167589.77 | 0.00 | 240274.01 | 240274.01 | 8.60631805 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 152100.720 | 152100.720 | 5.591815 | 0.00133064 | 4010.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 5.6067 | 5.719500 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 152100.72 | 152100.72 | 1.0000 | 5.46565072 | 5.591815 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.33050771 | 60.00 | 32.22 | 27.78 | 0.000 | 152100.72 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00767348 | 21.00 | 0.00767348 | 40.2910 | 106435.00 | 0.00 | 152593.46 | 152593.46 | 5.46565072 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32220.870 | 32220.870 | 1.185018 | 0.00028188 | 849.416 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 1.1877 | 1.211613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32220.87 | 32220.87 | 1.0000 | 1.15828162 | 1.185018 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28185347 | 60.00 | 32.22 | 27.78 | 0.000 | 32220.87 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771234 | 21.00 | 0.00771234 | 40.4931 | 22542.93 | 0.00 | 32324.18 | 32324.18 | 1.15828162 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21447.303 | 21447.303 | 0.788818 | 0.00018763 | 565.391 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.7906 | 0.806491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21447.30 | 21447.30 | 1.0000 | 0.77102022 | 0.788818 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18761122 | 60.00 | 32.22 | 27.78 | 0.000 | 21447.30 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771182 | 21.00 | 0.00771182 | 40.4905 | 15005.14 | 0.00 | 21516.00 | 21516.00 | 0.77102022 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60965.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32532.299 | 32532.299 | 1.196484 | 0.00028461 | 857.622 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 1.1992 | 1.223324 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32532.30 | 32532.30 | 1.0000 | 1.16948856 | 1.196484 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28457771 | 60.00 | 32.22 | 27.78 | 0.000 | 32532.30 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771497 | 21.00 | 0.00771497 | 40.5067 | 22760.67 | 0.00 | 32636.58 | 32636.58 | 1.16948856 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21016.037 | 21016.037 | 0.772945 | 0.00018386 | 554.025 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 0.7747 | 0.790274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21016.04 | 21016.04 | 1.0000 | 0.75550584 | 0.772945 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18383870 | 60.00 | 32.22 | 27.78 | 0.000 | 21016.04 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770638 | 21.00 | 0.00770638 | 40.4623 | 14703.57 | 0.00 | 21083.38 | 21083.38 | 0.75550584 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 182680.545 | -999.000 | 11.791419 | 0.00777165 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7350 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.791419 | 11.52537615 | 4197.9300 | 999.8980 | 93.98704162 | 12.27 | 6.67 | 5.60 | 2209485.72 | 8.2680 | 8.268012 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 182680.54 | 182680.54 | 1.0000 | 11.52537615 | 11.791419 | 26.09 | 13.67 | 0.00693669 | 43901.5 | 10.52 | 7.74 | 0.00693669 | 28051.2 | 7.77085989 | 6.67 | 12.27 | 5.60 | 26785.307 | 155895.24 | 33.90 | 0.00547527 | 15.07 | 2.40109000 | 20.3630 | 24.00 | 0.00732814 | 24.00 | 0.00732814 | 32.0825 | 126624.66 | 0.00 | 163817.83 | 163817.83 | 11.52537615 | 26.09 | 15.78 | 0.00693669 | 43901.5 | 12.12 | 10.19 | 0.00693669 | 29687.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 73716.750 | 73716.750 | 3.537426 | 0.00064491 | 1180.018 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.791419 | 11.52537615 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 2.7173 | 2.771998 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 73716.75 | 73716.75 | 1.0000 | 3.45761285 | 3.537426 | -8.42 | -8.56 | 0.00219091 | -3012.7 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.64484050 | 60.00 | 32.22 | 27.78 | 0.000 | 73716.75 | -17.90 | 0.00095524 | -17.90 | 2.40109000 | 67.8768 | 11.62 | 0.00480191 | 21.03 | 0.00527701 | 27.7635 | 29700.53 | 0.00 | 64743.18 | 64743.18 | 3.45761285 | 2.80 | -0.89 | 0.00219091 | 8304.3 | 21.36 | 9.11 | 0.00219091 | 27029.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1734326.687 | -999.000 | 109.868233 | 0.07378227 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6585 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 109.868233 | 107.38934318 | 4197.9300 | 999.8980 | 93.98704162 | 12.27 | 6.67 | 5.60 | 2209485.72 | 78.4946 | 78.494587 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1734326.69 | 1734326.69 | 1.0000 | 107.38934318 | 109.868233 | 26.39 | 13.73 | 0.00689554 | 44097.2 | 10.52 | 7.70 | 0.00689554 | 27947.3 | 73.77473997 | 6.67 | 12.27 | 5.60 | 249575.934 | 1484750.75 | 33.90 | 0.00547527 | 15.07 | 24.84725000 | 22.6155 | 24.00 | 0.00734674 | 24.00 | 0.00734674 | 32.1629 | 1148230.89 | 0.00 | 1551475.21 | 1551475.21 | 107.38934318 | 26.39 | 15.85 | 0.00689554 | 44097.2 | 12.19 | 10.18 | 0.00689554 | 29650.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 699935.804 | 699935.804 | 32.960470 | 0.00612334 | 11179.015 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 109.868233 | 107.38934318 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 25.8007 | 26.319945 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 699935.80 | 699935.80 | 1.0000 | 32.21680295 | 32.960470 | -8.82 | -8.82 | 0.00259833 | -2407.8 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 6.12271911 | 60.00 | 32.22 | 27.78 | 0.000 | 699935.80 | -17.90 | 0.00095524 | -17.90 | 24.84725000 | 75.3850 | 18.99 | 0.00763040 | 19.35 | 0.00744189 | 43.2913 | 379284.72 | 0.00 | 611992.42 | 611992.42 | 32.21680295 | 2.80 | -0.26 | 0.00259833 | 9325.3 | 21.61 | 9.68 | 0.00259833 | 28321.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 190571.551 | -999.000 | 12.369450 | 0.00810735 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7006 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.369450 | 12.09036591 | 4197.9300 | 999.8980 | 93.98704162 | 12.27 | 6.67 | 5.60 | 2209485.72 | 8.6252 | 8.625154 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 190571.55 | 190571.55 | 1.0000 | 12.09036591 | 12.369450 | 26.00 | 13.62 | 0.00691820 | 43766.8 | 10.52 | 7.72 | 0.00691820 | 28004.5 | 8.10652731 | 6.67 | 12.27 | 5.60 | 28098.359 | 162473.19 | 33.90 | 0.00547527 | 15.07 | 2.50203000 | 20.2275 | 24.00 | 0.00728474 | 24.00 | 0.00728474 | 31.8945 | 137615.23 | 0.00 | 170489.39 | 170489.39 | 12.09036591 | 26.00 | 15.73 | 0.00691820 | 43766.8 | 12.15 | 10.18 | 0.00691820 | 29665.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 66719.712 | 66719.712 | 3.710835 | 0.00058369 | 1084.351 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.369450 | 12.09036591 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 2.4594 | 2.508886 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 66719.71 | 66719.71 | 1.0000 | 3.62710977 | 3.710835 | -5.51 | -5.51 | 0.00312594 | 2253.4 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.58363360 | 60.00 | 32.22 | 27.78 | 0.000 | 66719.71 | -17.90 | 0.00095524 | -17.90 | 2.50203000 | 67.4250 | 20.15 | 0.00761893 | 17.33 | 0.00760695 | 50.2240 | 46362.34 | 0.00 | 60553.06 | 60553.06 | 3.62710977 | 2.80 | 0.71 | 0.00312594 | 10647.6 | 19.32 | 9.23 | 0.00312594 | 27342.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 101906.938 | -999.000 | 6.899615 | 0.00433536 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0366 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 6.899615 | 6.74394360 | 4197.9300 | 999.8980 | 93.98704162 | 12.27 | 6.67 | 5.60 | 2209485.72 | 4.6122 | 4.612247 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 101906.94 | 101906.94 | 1.0000 | 6.74394360 | 6.899615 | 25.80 | 13.70 | 0.00709893 | 44016.2 | 10.95 | 8.09 | 0.00709893 | 28905.3 | 4.33491446 | 6.67 | 12.27 | 5.60 | 12675.432 | 89231.51 | 33.16 | 0.00547412 | 14.83 | 1.20015641 | 17.3945 | 24.00 | 0.00749579 | 24.00 | 0.00749579 | 32.8081 | 68116.52 | 0.00 | 92008.45 | 92008.45 | 6.74394360 | 25.80 | 15.81 | 0.00709893 | 44016.2 | 12.40 | 10.48 | 0.00709893 | 30373.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 292168.504 | 292168.504 | 6.899615 | 0.00255602 | 6371.064 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 6.899615 | 6.74394360 | 4197.9300 | 999.8980 | 23.26265876 | 54.44 | 82.22 | 27.78 | 2712856.26 | 10.7698 | 10.986521 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 292168.50 | 292168.50 | 1.0000 | 6.74394360 | 6.899615 | -3.11 | -7.40 | 0.00095524 | -745.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.55575679 | 60.00 | 32.22 | 27.78 | 0.000 | 292168.50 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 17.3945 | 0.00 | 0.00095524 | 23.82 | 0.00095524 | 4.2701 | 0.00 | 0.00 | 238453.50 | 238453.50 | 6.74394360 | 12.80 | 3.31 | 0.00095524 | 15273.7 | 47.93 | 18.23 | 0.00095524 | 50631.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 478002.602 | 250502.349 | 26.351805 | 0.01170625 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8935 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 406287.66 | 405321.26 | 0.8500 | -999.0 | -999.0 | 28.80 | 14.64 | 0.00702195 | 46872.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406287.66 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | -999.0000 | 27.00 | 0.00704210 | 27.00 | 0.00704210 | 25.8129 | 371792.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10605.125 | 5613.547 | 0.601406 | 0.00025972 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9322 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8966.80 | 8924.29 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704277 | 46332.3 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8966.80 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708483 | 27.00 | 0.00708483 | 25.9659 | 8492.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 101449.934 | 53688.935 | 5.751061 | 0.00248450 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9356 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 85783.17 | 85359.09 | 0.8456 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704461 | 46339.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85783.17 | 28.87 | 0.00546756 | 13.38 | 0.15632344 | -999.0000 | 27.00 | 0.00708870 | 27.00 | 0.00708870 | 25.9800 | 81202.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10386.817 | 5497.428 | 0.588921 | 0.00025437 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9339 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8782.50 | 8739.95 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704372 | 46335.7 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8782.50 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708670 | 27.00 | 0.00708670 | 25.9727 | 8318.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 478002.602 | 478002.602 | 26.351805 | 0.01170625 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 478002.60 | 478002.60 | 1.0000 | 25.75724493 | 26.351805 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 478002.60 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2841 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10605.125 | 10605.125 | 0.601406 | 0.00025972 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10605.13 | 10605.13 | 1.0000 | 0.58783728 | 0.601406 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10605.13 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5993 | 0.00 | 0.00509851 | 25.87 | 0.00509851 | 20.0357 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 101449.934 | 101449.934 | 5.751061 | 0.00248450 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 101449.93 | 101449.93 | 1.0000 | 5.62130322 | 5.751061 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101449.93 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7182 | 0.00 | 0.00178546 | 23.89 | 0.00178546 | 7.9367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10386.817 | 10386.817 | 0.588921 | 0.00025437 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10386.82 | 10386.82 | 1.0000 | 0.57563361 | 0.588921 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10386.82 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6544 | 0.00 | 0.00162222 | 22.30 | 0.00162222 | 7.9444 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.351805 | 25.75724493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 19243.92 | 19243.92 | 1.0000 | 25.75724493 | 26.351805 | -0.23 | -0.23 | 0.00692238 | 17078.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.92 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2841 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.601406 | 0.58783728 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.58783728 | 0.601406 | -0.47 | -0.47 | 0.00499082 | 12009.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.5993 | 0.00 | 0.00509851 | 25.87 | 0.00509851 | 20.0357 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.751061 | 5.62130322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8889.90 | 8889.90 | 1.0000 | 5.62130322 | 5.751061 | -0.49 | -4.49 | 0.00176289 | 3918.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8889.90 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7182 | 0.00 | 0.00178546 | 23.89 | 0.00178546 | 7.9367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.588921 | 0.57563361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.57563361 | 0.588921 | -0.48 | -4.74 | 0.00160452 | 3533.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6544 | 0.00 | 0.00162222 | 22.30 | 0.00162222 | 7.9444 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.40 | 11.79 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 24.85 | 109.87 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.50 | 12.37 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1952.50 | 1225.67 | 153.50 |
CORE_BOTTOM | 1725.83 | 1366.50 | 144.83 |
CORE_MID | 1099.00 | 3267.67 | 196.00 |
CORE_TOP | 1794.00 | 3851.17 | 907.33 |
PERIMETER_BOT_ZN_3 | 1678.67 | 3647.33 | 419.00 |
PERIMETER_BOT_ZN_2 | 1992.17 | 3411.83 | 484.33 |
PERIMETER_BOT_ZN_1 | 2539.50 | 2567.33 | 512.00 |
PERIMETER_BOT_ZN_4 | 2601.00 | 2498.00 | 306.33 |
PERIMETER_MID_ZN_3 | 2498.17 | 4100.00 | 1535.50 |
PERIMETER_MID_ZN_2 | 2239.83 | 3317.50 | 1147.17 |
PERIMETER_MID_ZN_1 | 2704.50 | 2933.67 | 857.67 |
PERIMETER_MID_ZN_4 | 2419.83 | 3939.67 | 1113.50 |
PERIMETER_TOP_ZN_3 | 3305.17 | 4300.17 | 2376.67 |
PERIMETER_TOP_ZN_2 | 3230.17 | 3949.17 | 1879.83 |
PERIMETER_TOP_ZN_1 | 3036.00 | 3323.00 | 1398.33 |
PERIMETER_TOP_ZN_4 | 3022.33 | 4157.67 | 1800.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 553.33 | 553.33 |
DATACENTER_MID_ZN_6 | 5711.83 | 84.17 | 72.67 |
DATACENTER_TOP_ZN_6 | 5040.00 | 331.50 | 126.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5919.83 | 5919.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 68.50 | 0.00 | 2.00 |
CORE_BOTTOM | 0.00 | 6.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8.00 | 0.17 | 0.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.50 | 2.00 | 0.00 | 1.67 |
PERIMETER_BOT_ZN_2 | 0.67 | 21.83 | 0.00 | 21.83 |
PERIMETER_BOT_ZN_1 | 1.17 | 61.17 | 0.00 | 61.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 72.67 | 0.00 | 34.50 |
PERIMETER_MID_ZN_3 | 32.83 | 2.00 | 6.33 | 1.67 |
PERIMETER_MID_ZN_2 | 24.50 | 21.67 | 2.33 | 21.67 |
PERIMETER_MID_ZN_1 | 14.83 | 107.00 | 2.17 | 106.33 |
PERIMETER_MID_ZN_4 | 15.67 | 19.83 | 1.83 | 12.33 |
PERIMETER_TOP_ZN_3 | 203.50 | 5.00 | 65.50 | 3.83 |
PERIMETER_TOP_ZN_2 | 128.50 | 24.00 | 20.17 | 23.33 |
PERIMETER_TOP_ZN_1 | 107.67 | 43.67 | 19.17 | 42.50 |
PERIMETER_TOP_ZN_4 | 91.33 | 22.00 | 14.50 | 13.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 65.67 | 0.00 | 60.33 |
DATACENTER_MID_ZN_6 | 0.00 | 42.67 | 0.00 | 41.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 36.83 | 0.00 | 34.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 2077.67 | 0.00 | 1382.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 217.50 | 2338.17 | 66.67 | 1566.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.505 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.138 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.885 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.838 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 1.162 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.996 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.954 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.584 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 1.009 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.948 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.890 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 2.068 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 1.107 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 2.044 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.911 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 2.180 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.480 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 63825211.78 | 0.00 | 63825211.78 | 0.00 | 63825211.78 | 37848132.68 | 3776.63 | 969.74 | 4013.64 | 508.52 |
CORE_BOTTOM | 49583358.01 | 0.00 | 49583358.01 | 0.00 | 49583358.01 | 33990283.35 | 3493.71 | 19.75 | 5246.55 | 579.34 |
CORE_MID | 0.37E+09 | 0.00 | 0.37E+09 | 0.00 | 0.37E+09 | 0.34E+09 | 4040.54 | 21.66 | 4697.79 | 286.80 |
CORE_TOP | 34695416.20 | 0.00 | 34695416.20 | 0.00 | 34695416.20 | 33990283.35 | 4133.19 | 21.61 | 4605.19 | 357.89 |
PERIMETER_BOT_ZN_3 | 6464537.78 | 0.00 | 6464537.78 | 451114.65 | 6915652.43 | 4267819.30 | 3502.37 | 47.34 | 5210.30 | 579.34 |
PERIMETER_BOT_ZN_2 | 7221595.78 | 0.00 | 7221595.78 | 300742.89 | 7522338.67 | 2750345.05 | 3256.91 | 0.00 | 5503.09 | 579.34 |
PERIMETER_BOT_ZN_1 | 10687972.32 | 0.00 | 10687972.32 | 451114.65 | 11139086.96 | 4267912.63 | 3289.87 | 3.67 | 5466.46 | 579.34 |
PERIMETER_BOT_ZN_4 | 9337790.57 | 0.00 | 9337790.57 | 300742.89 | 9638533.46 | 2750345.05 | 3248.60 | 1.31 | 5510.09 | 579.34 |
PERIMETER_MID_ZN_3 | 53115634.09 | 0.00 | 53115634.09 | 1057988.21 | 54173622.30 | 42678193.03 | 3915.06 | 10.18 | 4834.76 | 286.80 |
PERIMETER_MID_ZN_2 | 69760247.07 | 0.00 | 69760247.07 | 705324.99 | 70465572.06 | 27503450.52 | 3708.62 | 4.52 | 5046.86 | 1195.80 |
PERIMETER_MID_ZN_1 | 98397835.78 | 0.00 | 98397835.78 | 1057988.21 | 99455823.99 | 42679126.28 | 3803.62 | 10.31 | 4946.07 | 286.80 |
PERIMETER_MID_ZN_4 | 70519149.89 | 0.00 | 70519149.89 | 705324.99 | 71224474.88 | 27503450.52 | 3698.33 | 4.25 | 5057.43 | 286.80 |
PERIMETER_TOP_ZN_3 | 5780028.03 | 0.00 | 5780028.03 | 1313602.61 | 7093630.64 | 4267819.30 | 4011.50 | 4.26 | 4744.24 | 357.89 |
PERIMETER_TOP_ZN_2 | 6867570.26 | 0.00 | 6867570.26 | 875734.47 | 7743304.73 | 2750345.05 | 3904.43 | 4.77 | 4850.80 | 357.89 |
PERIMETER_TOP_ZN_1 | 9892740.72 | 0.00 | 9892740.72 | 1313602.61 | 11206343.33 | 4267912.63 | 3967.89 | 3.07 | 4789.04 | 357.89 |
PERIMETER_TOP_ZN_4 | 7355646.77 | 0.00 | 7355646.77 | 875734.47 | 8231381.24 | 2750345.05 | 3867.41 | 4.60 | 4887.99 | 357.89 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.69E+10 | 0.00 | 0.69E+10 | 41148653.23 | 0.69E+10 | 0.50E+10 | 4632.42 | 4420.83 | 5788.96 | 1934.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.7945 | 0.0000 | 2.7945 | 0.0000 | 2.7945 | 1.2002 | 1298.85 | 963.88 | 3680.27 |
CORE_BOTTOM | 2.1356 | 0.0000 | 2.1356 | 0.0000 | 2.1356 | 1.0778 | 1158.88 | 15.42 | 4768.70 |
CORE_MID | 16.6092 | 0.0000 | 16.6092 | 0.0000 | 16.6092 | 10.7782 | 1371.99 | 21.01 | 4550.00 |
CORE_TOP | 1.5761 | 0.0000 | 1.5761 | 0.0000 | 1.5761 | 1.0778 | 1410.25 | 21.61 | 4511.13 |
PERIMETER_BOT_ZN_3 | 0.2742 | 0.0000 | 0.2742 | 0.0102 | 0.2844 | 0.1353 | 1210.85 | 44.16 | 4687.99 |
PERIMETER_BOT_ZN_2 | 0.3040 | 0.0000 | 0.3040 | 0.0068 | 0.3108 | 0.0872 | 1015.28 | 0.00 | 4927.72 |
PERIMETER_BOT_ZN_1 | 0.4613 | 0.0000 | 0.4613 | 0.0102 | 0.4715 | 0.1353 | 1038.64 | 2.81 | 4901.54 |
PERIMETER_BOT_ZN_4 | 0.3931 | 0.0000 | 0.3931 | 0.0068 | 0.3999 | 0.0872 | 1010.63 | 0.79 | 4931.58 |
PERIMETER_MID_ZN_3 | 2.3864 | 0.0000 | 2.3864 | 0.0239 | 2.4103 | 1.3533 | 1256.59 | 9.62 | 4676.80 |
PERIMETER_MID_ZN_2 | 2.9700 | 0.0000 | 2.9700 | 0.0171 | 2.9870 | 0.8721 | 1124.19 | 1.06 | 3908.76 |
PERIMETER_MID_ZN_1 | 4.4637 | 0.0000 | 4.4637 | 0.0239 | 4.4875 | 1.3533 | 1172.67 | 6.01 | 4764.32 |
PERIMETER_MID_ZN_4 | 3.1550 | 0.0000 | 3.1550 | 0.0159 | 3.1709 | 0.8721 | 1121.72 | 0.69 | 4820.59 |
PERIMETER_TOP_ZN_3 | 0.2620 | 0.0000 | 0.2620 | 0.0297 | 0.2917 | 0.1353 | 1297.96 | 3.65 | 4641.38 |
PERIMETER_TOP_ZN_2 | 0.3118 | 0.0000 | 0.3118 | 0.0198 | 0.3316 | 0.0872 | 1231.45 | 2.39 | 4709.16 |
PERIMETER_TOP_ZN_1 | 0.4516 | 0.0000 | 0.4516 | 0.0297 | 0.4812 | 0.1353 | 1267.68 | 1.68 | 4673.64 |
PERIMETER_TOP_ZN_4 | 0.3328 | 0.0000 | 0.3328 | 0.0198 | 0.3525 | 0.0872 | 1212.83 | 1.81 | 4728.35 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 306.5507 | 0.0000 | 306.5507 | 0.9407 | 307.4914 | 158.4706 | 1815.42 | 4386.87 | 5015.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 79579086.07 | 0.00 | 79579086.07 | 48026705.38 | 3387.32 | 7.60 | 5365.08 | 579.34 |
VAV_MID WITH REHEAT | 0.63E+09 | 0.00 | 0.63E+09 | 0.48E+09 | 3921.63 | 5.17 | 4833.20 | 286.80 |
VAV_TOP WITH REHEAT | 61709618.06 | 0.00 | 61709618.06 | 48026705.38 | 4038.09 | 3.08 | 4718.83 | 357.72 |
CAV_BAS | 60977604.38 | 0.00 | 60977604.38 | 37848132.68 | 4770.12 | 21.46 | 3968.42 | 508.39 |
AIRLOOP DATACENTER BASEMENT | 5052327.01 | 0.00 | 5052327.01 | 10671554.30 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.4091 | 0.0000 | 3.4091 | 1.5229 | 1092.95 | 4.11 | 4845.94 |
VAV_MID WITH REHEAT | 28.4199 | 0.0000 | 28.4199 | 15.2292 | 1258.09 | 4.77 | 4680.14 |
VAV_TOP WITH REHEAT | 2.8034 | 0.0000 | 2.8034 | 1.5229 | 1317.00 | 2.58 | 4623.42 |
CAV_BAS | 2.6698 | 0.0000 | 2.6698 | 1.2002 | 2280.33 | 16.69 | 3645.98 |
AIRLOOP DATACENTER BASEMENT | 0.2361 | 0.0000 | 0.2361 | 0.3384 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1691.81 | 3820.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2277.35 | 2850.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2436.08 | 2781.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 959.00 | 4223.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.2951 | 5.0553 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 23.7423 | 44.7888 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3905 | 4.4708 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1478 | 3.9750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3234 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1335 |
Defaulted Fields | 1179 |
Fields with Defaults | 3690 |
Autosized Fields | 333 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
Electricity:Building | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 660.02 | 14600.60 | 01-JAN-00:10 | 34031.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 532.90 | 7069.41 | 01-JAN-00:10 | 36605.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5328.94 | 70693.84 | 01-JAN-00:10 | 366051.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 532.89 | 7069.38 | 01-JAN-00:10 | 36605.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 669.12 | 8876.66 | 01-JAN-00:10 | 45962.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 431.21 | 5720.45 | 01-JAN-00:10 | 29619.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 669.13 | 8876.80 | 01-JAN-00:10 | 45963.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 431.20 | 5720.42 | 01-JAN-00:10 | 29619.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7561.29 | 95230.42 | 01-JAN-00:10 | 385433.43 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1582.51 | 19698.04 | 01-JAN-00:10 | 81759.99 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2389.50 | 6141.75 | 05-JAN-03:30 | 411972.92 | 26-JUN-15:20 |
HeatRejection:Electricity | 983.27 | 2026.16 | 05-JAN-19:00 | 83544.70 | 16-JUN-13:40 |
General:HeatRejection:Electricity | 983.27 | 2026.16 | 05-JAN-19:00 | 83544.70 | 16-JUN-13:40 |
Electricity:HVAC | 7387.13 | 111189.20 | 08-JAN-03:30 | 563738.34 | 17-AUG-15:20 |
ExteriorEquipment:Electricity | 1997.59 | 30702.09 | 01-JAN-00:10 | 120520.01 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.51 | 1613.62 | 01-JAN-00:10 | 5474.05 | 03-APR-07:20 |
ElectricityPurchased:Facility | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
ElectricityPurchased:Plant | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
Cogeneration:ElectricityPurchased | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
ElectricityNet:Plant | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
Cogeneration:ElectricityNet | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
General:Cogeneration:ElectricityNet | 31746.94 | 409412.36 | 16-JAN-10:30 | 2175458.54 | 16-AUG-15:10 |
Fans:Electricity | 3038.52 | 51053.51 | 01-JAN-04:40 | 314431.41 | 17-AUG-15:20 |
General:Fans:Electricity | 3038.52 | 51053.51 | 01-JAN-04:40 | 314431.41 | 17-AUG-15:20 |
ExteriorLights:Electricity | 904.37 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 904.37 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Cooling:Electricity | 3809.89 | 34948.97 | 05-JAN-07:10 | 474127.94 | 16-AUG-15:20 |
General:Cooling:Electricity | 3809.89 | 34948.97 | 05-JAN-07:10 | 474127.94 | 16-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1281.32 | 0.00 | 31-AUG-23:10 | 81746.97 | 17-AUG-06:10 |
General:Humidifier:Electricity | 1281.32 | 0.00 | 31-AUG-23:10 | 81746.97 | 17-AUG-06:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 576.12 | 3750.47 | 01-JAN-00:40 | 70117.74 | 15-JUN-15:50 |
General:Pumps:Electricity | 576.12 | 3750.47 | 01-JAN-00:40 | 70117.74 | 15-JUN-15:50 |
WIRED_LTG_ELECTRICITY | 110.78 | 0.00 | 01-JAN-00:10 | 9672.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3744.23 | 8146.58 | 19-MAR-07:00 | 1927078.22 | 23-DEC-07:10 |
NaturalGas:Plant | 3744.23 | 8146.58 | 19-MAR-07:00 | 1927078.22 | 23-DEC-07:10 |
Heating:NaturalGas | 2930.56 | 0.00 | 01-JAN-00:40 | 1918931.64 | 23-DEC-07:10 |
Boiler:Heating:NaturalGas | 2930.56 | 0.00 | 01-JAN-00:40 | 1918931.64 | 23-DEC-07:10 |
WaterSystems:NaturalGas | 813.67 | 8146.58 | 02-JAN-04:10 | 85998.34 | 13-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 813.67 | 8146.58 | 02-JAN-04:10 | 85998.34 | 13-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19994.68 | 170677.15 | 05-JAN-07:10 | 2584123.02 | 16-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 19994.68 | 170677.15 | 05-JAN-07:10 | 2584123.02 | 16-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 19994.68 | 170677.15 | 05-JAN-07:10 | 2584123.02 | 16-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7616.24 | 0.00 | 31-AUG-23:10 | 0.00 | 26-JUN-15:10 |
Water:HVAC | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Humidifier:Water | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
General:Humidifier:Water | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
MainsWater:Facility | 7616.24 | 0.00 | 31-AUG-23:10 | 0.00 | 26-JUN-15:10 |
MainsWater:HVAC | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Humidifier:MainsWater | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
General:Humidifier:MainsWater | 476.65 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Water:Plant | 7139.59 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7139.59 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4859.42 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
General:HeatRejection:Water | 4859.42 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
HeatRejection:MainsWater | 4859.42 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
General:HeatRejection:MainsWater | 4859.42 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 59309.03 | 244781.21 | 08-JAN-02:50 | 9898319.69 | 16-AUG-15:10 |
EnergyTransfer:Building | 19755.56 | 88346.41 | 08-JAN-13:20 | 1691944.47 | 31-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 698.59 | 0.00 | 01-JAN-00:10 | 72746.72 | 10-OCT-05:10 |
Heating:EnergyTransfer | 435.66 | 0.00 | 09-JAN-22:10 | 834927.04 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.13 | 0.00 | 01-JAN-00:10 | 21180.01 | 15-JUL-16:10 |
General:Heating:EnergyTransfer | 435.66 | 0.00 | 09-JAN-22:10 | 834927.04 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.13 | 0.00 | 01-JAN-00:10 | 21180.01 | 15-JUL-16:10 |
Cooling:EnergyTransfer | 19319.91 | 87166.78 | 08-JAN-05:30 | 1691944.47 | 31-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 695.47 | 0.00 | 01-JAN-00:10 | 72746.72 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 19319.91 | 87166.78 | 08-JAN-05:30 | 1691944.47 | 31-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 695.47 | 0.00 | 01-JAN-00:10 | 72746.72 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 650.52 | 0.00 | 01-JAN-00:10 | 57598.00 | 21-AUG-14:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 650.52 | 0.00 | 01-JAN-00:10 | 57598.00 | 21-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 650.52 | 0.00 | 01-JAN-00:10 | 57598.00 | 21-AUG-14:40 |
EnergyTransfer:Zone:CORE_MID | 4597.95 | 0.00 | 01-JAN-00:10 | 455838.17 | 17-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.14 | 0.00 | 01-JAN-00:10 | 242749.99 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.14 | 0.00 | 01-JAN-00:10 | 242749.99 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4596.80 | 0.00 | 01-JAN-00:10 | 455838.17 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4596.80 | 0.00 | 01-JAN-00:10 | 455838.17 | 17-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 413.78 | 0.00 | 01-JAN-00:40 | 72330.54 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.79 | 0.00 | 01-JAN-00:10 | 72330.54 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.79 | 0.00 | 01-JAN-00:10 | 72330.54 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 400.98 | 0.00 | 01-JAN-00:40 | 54842.85 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 400.98 | 0.00 | 01-JAN-00:40 | 54842.85 | 26-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.47 | 0.00 | 01-JAN-00:10 | 11922.93 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.45 | 0.00 | 01-JAN-00:10 | 5999.16 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.45 | 0.00 | 01-JAN-00:10 | 5999.16 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.02 | 0.00 | 01-JAN-00:10 | 11922.93 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.02 | 0.00 | 01-JAN-00:10 | 11922.93 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 82.34 | 0.00 | 01-JAN-00:10 | 13766.96 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.47 | 0.00 | 01-JAN-00:10 | 5336.42 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.47 | 0.00 | 01-JAN-00:10 | 5336.42 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.87 | 0.00 | 01-JAN-00:10 | 13766.96 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.87 | 0.00 | 01-JAN-00:10 | 13766.96 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 134.69 | 0.00 | 01-JAN-00:10 | 19507.07 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.81 | 0.00 | 01-JAN-00:10 | 9024.37 | 21-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.81 | 0.00 | 01-JAN-00:10 | 9024.37 | 21-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 133.88 | 0.00 | 01-JAN-00:10 | 19507.07 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 133.88 | 0.00 | 01-JAN-00:10 | 19507.07 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.44 | 0.00 | 01-JAN-00:10 | 20065.01 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1655.60 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1655.60 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.42 | 0.00 | 01-JAN-00:10 | 20065.01 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.42 | 0.00 | 01-JAN-00:10 | 20065.01 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 631.99 | 0.00 | 01-JAN-00:10 | 120206.77 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 81.48 | 0.00 | 01-JAN-00:10 | 120206.77 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 81.48 | 0.00 | 01-JAN-00:10 | 120206.77 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 550.51 | 0.00 | 01-JAN-00:10 | 112332.89 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 550.51 | 0.00 | 01-JAN-00:10 | 112332.89 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 732.82 | 0.00 | 01-JAN-00:10 | 147840.03 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 45.81 | 0.00 | 01-JAN-00:10 | 118194.07 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 45.81 | 0.00 | 01-JAN-00:10 | 118194.07 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 687.00 | 0.00 | 01-JAN-00:10 | 147840.03 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 687.00 | 0.00 | 01-JAN-00:10 | 147840.03 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1215.88 | 0.00 | 01-JAN-00:10 | 201029.12 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.26 | 0.00 | 01-JAN-00:10 | 152902.52 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.26 | 0.00 | 01-JAN-00:10 | 152902.52 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1173.61 | 0.00 | 01-JAN-00:10 | 201029.12 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1173.61 | 0.00 | 01-JAN-00:10 | 201029.12 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 732.51 | 0.00 | 01-JAN-00:10 | 166169.93 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.10 | 0.00 | 01-JAN-00:10 | 109294.92 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.10 | 0.00 | 01-JAN-00:10 | 109294.92 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 700.41 | 0.00 | 01-JAN-00:10 | 166169.93 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 700.41 | 0.00 | 01-JAN-00:10 | 166169.93 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.39 | 0.00 | 01-JAN-00:40 | 15499.84 | 19-MAR-07:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.22 | 0.00 | 01-JAN-00:40 | 15499.84 | 19-MAR-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.22 | 0.00 | 01-JAN-00:40 | 15499.84 | 19-MAR-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.18 | 0.00 | 01-JAN-00:10 | 12470.46 | 17-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.18 | 0.00 | 01-JAN-00:10 | 12470.46 | 17-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 79.51 | 0.00 | 01-JAN-00:40 | 15427.54 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.31 | 0.00 | 01-JAN-00:40 | 15427.54 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.31 | 0.00 | 01-JAN-00:40 | 15427.54 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.20 | 0.00 | 01-JAN-00:10 | 14998.63 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.20 | 0.00 | 01-JAN-00:10 | 14998.63 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 125.83 | 0.00 | 01-JAN-00:40 | 21622.43 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.18 | 0.00 | 01-JAN-00:10 | 18948.31 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.18 | 0.00 | 01-JAN-00:10 | 18948.31 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.65 | 0.00 | 01-JAN-00:40 | 21622.43 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.65 | 0.00 | 01-JAN-00:40 | 21622.43 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 77.64 | 0.00 | 01-JAN-00:40 | 17664.08 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.51 | 0.00 | 01-JAN-00:40 | 15036.90 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.51 | 0.00 | 01-JAN-00:40 | 15036.90 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.13 | 0.00 | 01-JAN-00:10 | 17664.08 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.13 | 0.00 | 01-JAN-00:10 | 17664.08 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.74 | 0.00 | 01-JAN-00:10 | 10111.07 | 21-AUG-15:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.08 | 0.00 | 01-JAN-00:10 | 3867.00 | 17-DEC-09:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.08 | 0.00 | 01-JAN-00:10 | 3867.00 | 17-DEC-09:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.66 | 0.00 | 01-JAN-00:10 | 10111.07 | 21-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.66 | 0.00 | 01-JAN-00:10 | 10111.07 | 21-AUG-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 512.86 | 0.00 | 01-JAN-00:10 | 81965.13 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 81.22 | 0.00 | 01-JAN-00:10 | 81197.55 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 81.22 | 0.00 | 01-JAN-00:10 | 81197.55 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 431.64 | 0.00 | 01-JAN-00:10 | 81965.13 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 431.64 | 0.00 | 01-JAN-00:10 | 81965.13 | 17-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 127.91 | 0.00 | 01-JAN-00:40 | 28840.60 | 22-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.16 | 0.00 | 01-JAN-00:40 | 28840.60 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.16 | 0.00 | 01-JAN-00:40 | 28840.60 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 74.75 | 0.00 | 01-JAN-00:10 | 25814.54 | 26-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 74.75 | 0.00 | 01-JAN-00:10 | 25814.54 | 26-JUN-13:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.78 | 545.72 | 06-JAN-06:30 | 8497.53 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.78 | 545.72 | 06-JAN-06:30 | 8497.53 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.78 | 545.72 | 06-JAN-06:30 | 8497.53 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1199.01 | 10.41 | 09-JAN-07:30 | 79247.35 | 05-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.65 | 0.00 | 01-JAN-14:40 | 3871.63 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.65 | 0.00 | 01-JAN-14:40 | 3871.63 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1198.36 | 0.00 | 01-JAN-00:10 | 79247.35 | 05-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1198.36 | 0.00 | 01-JAN-00:10 | 79247.35 | 05-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.61 | 0.31 | 05-JAN-12:10 | 8042.64 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.86 | 0.00 | 02-JAN-12:40 | 741.38 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.86 | 0.00 | 02-JAN-12:40 | 741.38 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.74 | 0.00 | 01-JAN-00:10 | 8042.64 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.74 | 0.00 | 01-JAN-00:10 | 8042.64 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.30 | 86460.41 | 08-JAN-06:00 | 367542.19 | 19-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.30 | 86460.41 | 08-JAN-06:00 | 367542.19 | 19-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.30 | 86460.41 | 08-JAN-06:00 | 367542.19 | 19-DEC-17:00 |
PlantLoopHeatingDemand:Facility | 2626.73 | 0.00 | 01-JAN-00:40 | 1519302.68 | 23-DEC-07:20 |
PlantLoopHeatingDemand:Plant | 435.47 | 0.00 | 01-JAN-00:10 | 53785.14 | 15-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53785.14 | 15-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53785.14 | 15-FEB-12:40 |
EnergyTransfer:HVAC | 19206.15 | 153940.79 | 08-JAN-05:30 | 2364690.62 | 16-AUG-15:10 |
HeatingCoils:EnergyTransfer | 2191.26 | 0.00 | 01-JAN-00:40 | 1509357.48 | 23-DEC-07:20 |
PlantLoopHeatingDemand:HVAC | 2191.26 | 0.00 | 01-JAN-00:40 | 1509357.48 | 23-DEC-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 2191.26 | 0.00 | 01-JAN-00:40 | 1509357.48 | 23-DEC-07:20 |
CoolingCoils:EnergyTransfer | 17014.89 | 135728.18 | 05-JAN-07:10 | 2364690.62 | 16-AUG-15:10 |
EnergyTransfer:Plant | 20347.32 | 0.00 | 01-JAN-00:40 | 6067416.87 | 26-JUN-15:20 |
LoopToLoop:EnergyTransfer | 5912.83 | -0.40 | 05-JAN-12:00 | 1917651.47 | 26-JUN-15:20 |
WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53785.14 | 15-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53785.14 | 15-FEB-12:40 |
Boilers:EnergyTransfer | 2171.77 | 0.00 | 01-JAN-00:40 | 1541909.51 | 23-DEC-07:10 |
Chillers:EnergyTransfer | 5498.57 | 0.00 | 01-JAN-00:10 | 1926318.08 | 26-JUN-15:20 |
HeatRejection:EnergyTransfer | 6328.68 | 0.00 | 01-JAN-00:10 | 2189381.58 | 26-JUN-15:20 |
General:HeatRejection:EnergyTransfer | 6328.68 | 0.00 | 01-JAN-00:10 | 2189381.58 | 26-JUN-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.126 | -695.464 | 0.000 | 0.000 | 92.718 | 235.627 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -60.404 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -650.520 | 0.000 | 0.000 | 83.435 | 211.610 | 321.286 | 0.000 | 0.000 | 0.000 | 34.189 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 1.145 | -4596.769 | 0.000 | 0.000 | 842.411 | 2116.097 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1575.728 |
CORE_TOP | 0.000 | 0.000 | 12.791 | -400.981 | 0.000 | 0.000 | 87.414 | 211.610 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -232.119 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.449 | -80.023 | 0.000 | 0.000 | 10.854 | 26.570 | 40.342 | 28.099 | 0.000 | 0.130 | 37.300 | 0.000 | -57.163 | 0.000 | -6.559 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.470 | -81.867 | 0.000 | 0.000 | 7.060 | 17.123 | 25.998 | 65.109 | 0.000 | 0.092 | 5.774 | 0.000 | -35.474 | 0.000 | -4.284 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.815 | -133.874 | 0.000 | 0.000 | 10.738 | 26.570 | 40.343 | 134.891 | 0.000 | 0.128 | 0.004 | 0.000 | -53.542 | 0.000 | -6.612 | -19.457 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.014 | -117.422 | 0.000 | 0.000 | 6.958 | 17.123 | 25.998 | 58.654 | 0.000 | 0.083 | 53.354 | 0.000 | -40.040 | 0.000 | -4.721 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 81.478 | -550.503 | 0.000 | 0.000 | 113.381 | 265.697 | 403.423 | 290.999 | 0.000 | 3.055 | 55.386 | 0.000 | -523.847 | 0.000 | -139.069 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 45.810 | -686.999 | 0.000 | 0.000 | 53.357 | 171.225 | 259.981 | 652.151 | 0.000 | 2.060 | 0.020 | 0.000 | -336.325 | 0.000 | -94.407 | -66.853 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 42.262 | -1173.602 | 0.000 | 0.000 | 108.490 | 265.703 | 403.429 | 1344.818 | 0.000 | 2.941 | 0.056 | 0.000 | -522.462 | 0.000 | -149.123 | -322.456 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 32.099 | -700.411 | 0.000 | 0.000 | 73.468 | 171.225 | 259.979 | 599.714 | 0.000 | 2.050 | 13.510 | 0.000 | -354.845 | 0.000 | -96.790 | -0.012 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 30.217 | -51.177 | 0.000 | 0.000 | 11.562 | 26.570 | 40.342 | 29.688 | 0.000 | 0.367 | 0.001 | 0.000 | -48.886 | 0.000 | -16.185 | -22.499 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 16.313 | -63.200 | 0.000 | 0.000 | 7.325 | 17.123 | 25.998 | 65.583 | 0.000 | 0.241 | 0.002 | 0.000 | -31.716 | 0.000 | -11.094 | -26.571 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.179 | -107.648 | 0.000 | 0.000 | 11.057 | 26.570 | 40.343 | 135.173 | 0.000 | 0.353 | 0.002 | 0.000 | -49.042 | 0.000 | -17.402 | -57.583 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 12.511 | -65.129 | 0.000 | 0.000 | 7.442 | 17.123 | 25.998 | 60.206 | 0.000 | 0.249 | 0.001 | 0.000 | -33.559 | 0.000 | -11.402 | -13.439 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.784 | 0.000 | 0.000 | 0.948 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.415 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.655 | -1198.356 | 0.000 | 0.000 | 9.491 | 43.701 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -394.297 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.865 | -107.742 | 0.000 | 0.000 | 0.951 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.324 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7146.313 | 0.000 | 0.000 | 19.134 | 66.437 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -434.115 |
GROUNDFLOOR_PLENUM | 2.081 | -66.663 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.235 | 78.357 | 0.000 | 0.000 | 0.000 | -14.010 | 0.000 |
MIDFLOOR_PLENUM | 81.219 | -431.638 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.309 | 586.132 | 0.000 | 0.000 | 0.000 | -240.022 | -0.005 |
TOPFLOOR_PLENUM | 53.157 | -74.749 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.352 | 46.028 | 0.000 | 0.000 | 0.000 | -24.787 | -0.003 |
Total Facility | 136.457 | -573.050 | 299.198 | -18746.785 | 0.000 | 0.000 | 1558.194 | 3942.443 | 15213.411 | 3465.085 | 0.000 | 16.644 | 910.117 | 0.000 | -2086.900 | 0.000 | -836.466 | -3298.282 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-NOV-04:01 | 0.00 | 0.00 | 0.00 | -113133.21 | 0.00 | 0.00 | 0.00 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 98532.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 | -94387.95 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.15 | 0.00 | 0.00 | 0.00 | 85304.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 | -848116.15 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 757279.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-03:02 | 0.00 | 0.00 | 0.00 | -89100.30 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 80016.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -16435.97 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 5174.32 | 0.00 | 204.47 | 10169.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-JUL-09:21 | 0.00 | 0.00 | 0.00 | -21249.98 | 0.00 | 0.00 | 22.14 | 83.06 | 488.98 | 13924.77 | 0.00 | 0.00 | 6746.77 | 0.00 | -0.00 | 0.00 | -15.75 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-NOV-12:41 | 0.00 | 0.00 | 0.00 | -26254.15 | 0.00 | 0.00 | 29.96 | 128.90 | 758.78 | 29604.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -29.47 | -4238.35 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -29540.74 | 0.00 | 0.00 | 16.26 | 83.06 | 488.98 | 17262.92 | 0.00 | 50.89 | 11638.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -154248.71 | 0.00 | 0.00 | 0.00 | 1288.93 | 7587.73 | 51801.65 | 0.00 | 4609.58 | 88960.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -237554.18 | 0.00 | 0.00 | 194.80 | 830.63 | 4889.82 | 155217.72 | 0.00 | 0.00 | 77231.98 | 0.00 | -0.00 | 0.00 | -810.78 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-12:31 | 0.00 | 0.00 | 0.00 | -260298.96 | 0.00 | 0.00 | 291.64 | 1288.96 | 7587.84 | 251479.68 | 0.00 | 0.00 | 1378.78 | 0.00 | -0.00 | 0.00 | -1727.94 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -266182.15 | 0.00 | 0.00 | 166.79 | 830.63 | 4889.79 | 172305.77 | 0.00 | 1130.82 | 86858.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:51 | 0.00 | 0.00 | 0.00 | -17883.99 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 5070.54 | 0.00 | 607.47 | 11318.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:12 | 0.00 | 0.00 | 0.00 | -21996.38 | 0.00 | 0.00 | 22.22 | 83.06 | 488.98 | 13197.64 | 0.00 | 0.00 | 8528.97 | 0.00 | -0.00 | 0.00 | -324.51 | 0.00 |
PERIMETER_TOP_ZN_1 | 08-OCT-13:11 | 0.00 | 0.00 | 0.00 | -28416.44 | 0.00 | 0.00 | 30.12 | 128.90 | 758.78 | 23179.18 | 0.00 | 0.00 | 4919.91 | 0.00 | -0.00 | 0.00 | -600.44 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -29220.00 | 0.00 | 0.00 | 16.57 | 83.06 | 488.98 | 16788.73 | 0.00 | 0.00 | 11894.28 | 0.00 | -0.00 | 0.00 | -51.63 | 0.00 |
DATACENTER_BOT_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8497.89 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 682.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 05-AUG-18:11 | 0.00 | 0.00 | 0.00 | -79247.12 | 0.00 | 0.00 | 0.00 | 211.99 | 77944.22 | 0.00 | 0.00 | 0.00 | 1090.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:41 | 0.00 | 0.00 | 0.00 | -8052.60 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 236.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19-DEC-17:00 | 0.00 | 0.00 | 0.00 | -367541.81 | 0.00 | 0.00 | 2082.78 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19974.41 |
GROUNDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -12168.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12329.08 | 0.00 | -0.00 | 0.00 | -160.48 | 0.00 |
MIDFLOOR_PLENUM | 20-DEC-04:01 | 0.00 | -105784.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148261.71 | 0.00 | -0.00 | 0.00 | -42476.99 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-12:05 | 0.00 | -26464.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.72 | 26317.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-05:02 | 0.00 | -39974.42 | 0.00 | -1912382.32 | 0.00 | 0.00 | 15351.82 | 38246.31 | 504945.49 | 11357.62 | 0.00 | 0.00 | 1405407.08 | 0.00 | -18785.27 | 0.00 | -4166.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUL-16:01 | 0.00 | 0.00 | 22445.81 | 0.00 | 0.00 | 0.00 | 520.13 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37566.54 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-DEC-05:11 | 0.00 | 0.00 | 437535.28 | 0.00 | 0.00 | 0.00 | 0.00 | 20528.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -538635.08 |
CORE_TOP | 06-FEB-04:11 | 0.00 | 0.00 | 82837.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -91920.94 |
PERIMETER_BOT_ZN_3 | 23-DEC-05:01 | 0.00 | 0.00 | 12255.24 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6502.76 | 0.00 | -1283.39 | -5356.76 |
PERIMETER_BOT_ZN_2 | 23-DEC-05:01 | 0.00 | 0.00 | 11282.26 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4388.36 | 0.00 | -846.89 | -6619.06 |
PERIMETER_BOT_ZN_1 | 21-DEC-05:01 | 0.00 | 0.00 | 16714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.76 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7249.01 | 0.00 | -876.77 | -9857.70 |
PERIMETER_BOT_ZN_4 | 21-DEC-06:01 | 0.00 | 0.00 | 7783.36 | 0.00 | 0.00 | 0.00 | 94.15 | 166.11 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4162.48 | 0.00 | -162.84 | -4370.27 |
PERIMETER_MID_ZN_3 | 24-DEC-05:51 | 0.00 | 0.00 | 138570.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53222.02 | 0.00 | -18545.22 | -75680.08 |
PERIMETER_MID_ZN_2 | 24-DEC-05:51 | 0.00 | 0.00 | 177611.86 | 0.00 | 0.00 | 0.00 | 0.00 | 830.63 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36487.38 | 0.00 | -12582.70 | -134262.25 |
PERIMETER_MID_ZN_1 | 19-MAR-07:01 | 0.00 | 0.00 | 190817.75 | 0.00 | 0.00 | 0.00 | 896.41 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44161.71 | 0.00 | -51460.28 | -104968.97 |
PERIMETER_MID_ZN_4 | 22-DEC-04:11 | 0.00 | 0.00 | 172811.71 | 0.00 | 0.00 | 0.00 | 0.00 | 830.63 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41661.59 | 0.00 | -15084.29 | -123416.19 |
PERIMETER_TOP_ZN_3 | 24-DEC-05:51 | 0.00 | 0.00 | 17244.66 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5050.48 | 0.00 | -2202.46 | -10879.39 |
PERIMETER_TOP_ZN_2 | 24-DEC-05:51 | 0.00 | 0.00 | 19424.95 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3468.02 | 0.00 | -1494.79 | -15034.18 |
PERIMETER_TOP_ZN_1 | 24-DEC-05:51 | 0.00 | 0.00 | 22765.79 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5265.82 | 0.00 | -2245.76 | -16141.89 |
PERIMETER_TOP_ZN_4 | 24-DEC-05:51 | 0.00 | 0.00 | 22096.50 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3442.29 | 0.00 | -1536.47 | -17689.78 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 07-JAN-21:55 | 0.00 | 0.00 | 4278.35 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23976.39 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 747.10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2716.91 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:02 | 16199.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1535.77 | -14663.58 |
MIDFLOOR_PLENUM | 01-JAN-14:02 | 95830.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18610.56 | -77220.01 |
TOPFLOOR_PLENUM | 22-DEC-05:21 | 34489.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2150.30 | -32339.18 |
Total Facility | 26-DEC-05:11 | -414535.35 | 440328.80 | 1202644.66 | -440328.80 | 0.00 | 0.00 | 0.00 | 38246.31 | 623236.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87509.98 | 0.00 | -74644.24 | -1287438.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 13.2529 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.7914 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 126.1058 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 109.8682 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 13.2717 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.3695 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8996 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8996 | 0.1739 | 1.0000 | Not calculated | 1.2002 | 0.1739 | ||
AIRLOOP DATACENTER BASEMENT | 26.3515 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.3518 | 0.0128 | 1.0000 | Not calculated | 0.3384 | 0.0128 | ||
AIRLOOP DATACENTER BOT | 0.6014 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6014 | 0.0260 | 1.0000 | Not calculated | 0.0156 | 0.0260 | ||
AIRLOOP DATACENTER MID | 5.7511 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7511 | 0.0272 | 1.0000 | Not calculated | 0.1563 | 0.0272 | ||
AIRLOOP DATACENTER TOP | 0.5889 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5889 | 0.0265 | 1.0000 | Not calculated | 0.0156 | 0.0265 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.6264 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9759 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 63.0529 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 37.8317 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.6358 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9815 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8996 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8996 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1739 | ||
AIRLOOP DATACENTER BASEMENT | 26.3515 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.3515 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0128 | ||
AIRLOOP DATACENTER BOT | 0.6014 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.6014 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0260 | ||
AIRLOOP DATACENTER MID | 5.7511 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.7511 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0272 | ||
AIRLOOP DATACENTER TOP | 0.5889 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5889 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0265 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8996 | 6.8996 | 6.8996 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2597 | 7.2597 | 2.1779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 68.3420 | 68.3420 | 20.5026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9837 | 6.9837 | 2.0951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1772 | 1.1772 | 0.3532 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4130 | 1.4130 | 0.4239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6097 | 1.6097 | 0.4829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7933 | 1.7933 | 0.5380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.0386 | 11.0386 | 3.3116 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.8295 | 14.8295 | 4.4488 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.6997 | 15.6997 | 4.7099 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.1960 | 16.1960 | 4.8588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2956 | 1.2956 | 0.3887 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4906 | 1.4906 | 0.4472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7495 | 1.7495 | 0.5248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7523 | 1.7523 | 0.5257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6014 | 0.6014 | 0.6014 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7511 | 5.7511 | 5.7511 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5889 | 0.5889 | 0.5889 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.3515 | 26.3515 | 26.3515 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 13.2529 | 11.7914 | 13.2529 | 3.9759 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 126.1058 | 109.8682 | 126.1058 | 37.8317 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 13.2717 | 12.3695 | 13.2717 | 3.9815 | 0.0000 | 1.0000 |
CAV_BAS | 6.8996 | 6.8996 | 6.8996 | 6.8996 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.3515 | 26.3518 | 26.3515 | 26.3515 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6014 | 0.6014 | 0.6014 | 0.6014 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7511 | 5.7511 | 5.7511 | 5.7511 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5889 | 0.5889 | 0.5889 | 0.5889 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8996 | 6.8996 | 6.8996 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6298 | 3.6298 | 2.1779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 34.1710 | 34.1710 | 20.5026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4919 | 3.4919 | 2.0951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5886 | 0.5886 | 0.3532 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7065 | 0.7065 | 0.4239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8048 | 0.8048 | 0.4829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8967 | 0.8967 | 0.5380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5193 | 5.5193 | 3.3116 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4147 | 7.4147 | 4.4488 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8499 | 7.8499 | 4.7099 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.0980 | 8.0980 | 4.8588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6478 | 0.6478 | 0.3887 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7453 | 0.7453 | 0.4472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8747 | 0.8747 | 0.5248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8761 | 0.8761 | 0.5257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6014 | 0.6014 | 0.6014 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.7511 | 5.7511 | 5.7511 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5889 | 0.5889 | 0.5889 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.3515 | 26.3515 | 26.3515 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.6264 | 3.9759 | 3.9759 | 3.9759 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 63.0529 | 37.8317 | 37.8317 | 37.8317 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.6358 | 3.9815 | 3.9815 | 3.9815 | 0.0000 | 1.0000 |
CAV_BAS | 6.8996 | 6.8996 | 6.8996 | 6.8996 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.3515 | 26.3515 | 26.3515 | 26.3515 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.6014 | 0.6014 | 0.6014 | 0.6014 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.7511 | 5.7511 | 5.7511 | 5.7511 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5889 | 0.5889 | 0.5889 | 0.5889 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 66.67 |
Number of hours cooling loads not met | 1566.33 |
Number of hours not met | 1607.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2930.56 | 1918931.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3809.89 | 474127.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3942.44 | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 904.37 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.51 | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 3038.52 | 314431.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 576.12 | 70117.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 983.27 | 83544.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1281.32 | 81746.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 813.67 | 85998.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 31746.94 |
Natural Gas | 0.00 | 3744.23 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 35491.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.11 |
Space Heating | 0.00 |
Space Cooling | 82.25 |
Fans (All) | 65.60 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 685.38 |
Subtotal | 685.38 |
Natural Gas [MJ/m2] | |
Space Heating | 63.27 |
Service Water Heating | 17.57 |
Miscellaneous (All) | 80.83 |
Subtotal | 80.83 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.11 |
Space Heating | 8.26 |
Space Cooling | 10.73 |
Fans (All) | 8.56 |
Service Water Heating | 2.29 |
Receptacle Equipment | 42.87 |
Miscellaneous | 16.18 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8672.00 | 88.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8635.50 | 124.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.50 | 24.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8708.50 | 51.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8726.50 | 33.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6649.67 | 2044.33 | 66.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
Min | 6649.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2044.33 | 66.00 | 0.00 | 0.00 |
Average | 8643.49 | 113.64 | 2.87 | 0.00 | 0.00 |
Sum | 198800.17 | 2613.83 | 66.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368333.67 | 282.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2243.67 | 24.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2250.67 | 17.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2255.33 | 12.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 79098.33 | 22977.33 | 1319.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368333.67 | 22977.33 | 1319.33 | 0.00 | 0.00 |
Average | 79263.90 | 1013.65 | 57.36 | 0.00 | 0.00 |
Sum | 1823069.67 | 23314.00 | 1319.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8558.50 | 201.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8663.50 | 96.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8670.00 | 90.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8687.83 | 72.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8712.33 | 47.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8617.17 | 142.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8706.17 | 53.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8714.50 | 45.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7254.33 | 1505.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8689.67 | 70.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8712.17 | 47.83 | 0.00 | 0.00 | 0.00 |
Min | 7254.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1505.67 | 0.00 | 0.00 | 0.00 |
Average | 8643.32 | 116.68 | 0.00 | 0.00 | 0.00 |
Sum | 198796.33 | 2683.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368075.17 | 540.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330678.00 | 135.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330714.00 | 99.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2267.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 86838.17 | 16556.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368075.17 | 16556.83 | 0.00 | 0.00 | 0.00 |
Average | 79578.12 | 756.79 | 0.00 | 0.00 | 0.00 |
Sum | 1830296.83 | 17406.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:00
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511988E+11 | 112520.86 | 02-JAN-04:01 | -2.8 | -3.4 | 0.566002E+10 | 7499.20 | 06-JAN-10:20 | -0.3 | -1.7 |
February | 0.452986E+11 | 109780.60 | 21-FEB-04:01 | -1.0 | -1.0 | 0.513615E+10 | 7499.18 | 14-FEB-14:00 | -1.0 | -1.0 |
March | 0.558994E+11 | 110805.27 | 13-MAR-03:02 | 7.83 | 1.71 | 0.612946E+10 | 7499.14 | 14-MAR-13:20 | 23.67 | 7.80 |
April | 0.540016E+11 | 110386.73 | 10-APR-03:02 | 3.00 | -3.0 | 0.544705E+10 | 7499.26 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.572172E+11 | 112622.44 | 30-MAY-03:02 | 9.83 | 8.73 | 0.590120E+10 | 7499.23 | 26-MAY-13:20 | 9.83 | 8.73 |
June | 0.612851E+11 | 104779.98 | 26-JUN-03:02 | 16.05 | 10.54 | 0.588305E+10 | 7503.43 | 26-JUN-13:09 | 36.78 | 15.39 |
July | 0.610382E+11 | 104967.01 | 06-JUL-03:01 | 14.00 | 9.95 | 0.547451E+10 | 7499.03 | 21-JUL-09:20 | 25.00 | 15.23 |
August | 0.710181E+11 | 104407.19 | 17-AUG-03:02 | 13.00 | 5.30 | 0.614009E+10 | 7499.43 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.625688E+11 | 112258.47 | 25-SEP-03:02 | 7.70 | 3.87 | 0.545428E+10 | 7499.81 | 05-SEP-09:20 | 7.70 | 3.87 |
October | 0.611677E+11 | 111541.27 | 30-OCT-03:01 | -9.2 | -9.2 | 0.567161E+10 | 7499.36 | 03-OCT-13:20 | -9.2 | -9.2 |
November | 0.583953E+11 | 113143.33 | 20-NOV-04:01 | -3.0 | -3.0 | 0.561443E+10 | 7499.10 | 29-NOV-10:30 | -9.0 | -9.0 |
December | 0.563777E+11 | 109886.63 | 11-DEC-04:01 | -6.8 | -8.8 | 0.545758E+10 | 7499.04 | 21-DEC-14:09 | -16.0 | -16.7 |
Annual Sum or Average | 0.695467E+12 | 0.679694E+11 | ||||||||
Minimum of Months | 0.452986E+11 | 104407.19 | -9.2 | -9.2 | 0.513615E+10 | 7499.03 | -16.0 | -16.7 | ||
Maximum of Months | 0.710181E+11 | 113143.33 | 16.05 | 10.54 | 0.614009E+10 | 7503.43 | 36.78 | 15.39 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411750E+11 | 84949.16 | 23-JAN-05:01 | 4.17 | 0.03 | 0.506359E+10 | 6734.78 | 10-JAN-10:09 | 4.17 | 0.03 |
February | 0.382467E+11 | 87926.98 | 21-FEB-04:01 | -1.0 | -1.0 | 0.459441E+10 | 6734.75 | 08-FEB-14:09 | -1.0 | -1.0 |
March | 0.520604E+11 | 90064.51 | 13-MAR-03:02 | 7.83 | 1.71 | 0.549452E+10 | 6734.77 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.517834E+11 | 90847.77 | 10-APR-03:02 | 3.00 | -3.0 | 0.488645E+10 | 6735.10 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.530068E+11 | 92083.90 | 30-MAY-03:02 | 9.83 | 8.73 | 0.528910E+10 | 6734.90 | 26-MAY-13:09 | 9.83 | 8.73 |
June | 0.640009E+11 | 90210.70 | 20-JUN-03:02 | 15.00 | 11.91 | 0.526952E+10 | 6735.12 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.668907E+11 | 90148.00 | 06-JUL-03:01 | 14.00 | 9.95 | 0.489696E+10 | 6734.75 | 20-JUL-09:09 | 18.33 | 15.40 |
August | 0.806124E+11 | 90231.29 | 21-AUG-05:03 | 19.92 | 12.21 | 0.549654E+10 | 6773.38 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.556683E+11 | 94388.82 | 05-SEP-03:02 | 13.90 | 9.20 | 0.488300E+10 | 6735.43 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.509601E+11 | 90660.27 | 02-OCT-03:02 | 4.00 | 4.00 | 0.507751E+10 | 6735.02 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.487809E+11 | 91455.65 | 13-NOV-04:01 | 1.00 | 0.92 | 0.502662E+10 | 6734.75 | 29-NOV-10:30 | -9.0 | -9.0 |
December | 0.473372E+11 | 92373.89 | 04-DEC-04:02 | 1.83 | -0.9 | 0.489516E+10 | 6734.70 | 22-DEC-10:09 | -17.7 | -17.9 |
Annual Sum or Average | 0.650523E+12 | 0.608734E+11 | ||||||||
Minimum of Months | 0.382467E+11 | 84949.16 | -1.0 | -3.0 | 0.459441E+10 | 6734.70 | -17.7 | -17.9 | ||
Maximum of Months | 0.806124E+11 | 94388.82 | 19.92 | 12.21 | 0.549654E+10 | 6773.38 | 29.00 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294742E+11 | 75009.63 | 27-JAN-06:02 | -1.2 | -1.2 | 0.496154E+10 | 6734.73 | 10-JAN-10:09 | -1.2 | -1.2 |
February | 0.262613E+11 | 72261.97 | 28-FEB-06:03 | -3.0 | -3.4 | 0.443415E+10 | 6734.70 | 28-FEB-10:00 | 4.00 | 2.09 |
March | 0.351584E+11 | 77944.25 | 15-MAR-04:02 | 11.83 | 3.76 | 0.539043E+10 | 6734.71 | 02-MAR-10:20 | 11.83 | 3.76 |
April | 0.311688E+11 | 78825.27 | 14-APR-05:02 | 4.67 | 4.13 | 0.481495E+10 | 6735.02 | 13-APR-13:00 | 4.67 | 4.13 |
May | 0.422697E+11 | 80417.71 | 18-MAY-04:02 | 11.83 | 7.63 | 0.527789E+10 | 6734.87 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.515540E+11 | 82947.76 | 16-JUN-03:01 | 16.00 | 13.23 | 0.526596E+10 | 6735.12 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.504358E+11 | 84101.65 | 10-JUL-03:02 | 17.83 | 9.72 | 0.489239E+10 | 6734.75 | 27-JUL-13:09 | 28.50 | 17.50 |
August | 0.530486E+11 | 84078.57 | 28-AUG-03:02 | 15.67 | 14.58 | 0.549596E+10 | 6734.76 | 29-AUG-09:00 | 22.00 | 14.30 |
September | 0.456375E+11 | 84814.35 | 05-SEP-03:02 | 13.90 | 9.20 | 0.487562E+10 | 6735.36 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.362311E+11 | 78972.74 | 12-OCT-05:02 | -0.8 | -0.8 | 0.503115E+10 | 6734.94 | 03-OCT-13:09 | -0.8 | -0.8 |
November | 0.309335E+11 | 78748.68 | 10-NOV-06:02 | 5.67 | 4.71 | 0.495420E+10 | 6734.74 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.275077E+11 | 51452.40 | 15-DEC-06:03 | -0.5 | -3.8 | 0.467315E+10 | 6734.68 | 08-DEC-10:09 | -0.5 | -3.8 |
Annual Sum or Average | 0.459680E+12 | 0.600674E+11 | ||||||||
Minimum of Months | 0.262613E+11 | 51452.40 | -3.0 | -3.8 | 0.443415E+10 | 6734.68 | -9.0 | -9.0 | ||
Maximum of Months | 0.530486E+11 | 84814.35 | 17.83 | 14.58 | 0.549596E+10 | 6735.36 | 28.50 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198428E+11 | 32947.67 | 20-JAN-16:20 | 16.00 | 6.84 | 0.438308E+10 | 6734.38 | 26-JAN-14:00 | 9.00 | 2.97 |
February | 0.178063E+11 | 27715.43 | 23-FEB-17:00 | 5.00 | 2.11 | 0.400334E+10 | 6734.61 | 17-FEB-14:00 | 5.00 | 2.11 |
March | 0.274119E+11 | 61059.81 | 15-MAR-05:03 | 10.83 | 3.07 | 0.504994E+10 | 6734.62 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.264433E+11 | 65193.03 | 21-APR-05:03 | 5.83 | 3.87 | 0.451936E+10 | 6735.02 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.378880E+11 | 78713.03 | 18-MAY-05:02 | 11.67 | 7.89 | 0.518215E+10 | 6734.83 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.549041E+11 | 84450.06 | 26-JUN-03:02 | 16.05 | 10.54 | 0.526378E+10 | 6735.16 | 20-JUN-13:00 | 16.05 | 10.54 |
July | 0.532489E+11 | 89108.02 | 24-JUL-03:02 | 18.83 | 14.98 | 0.489225E+10 | 6734.72 | 27-JUL-13:09 | 28.50 | 17.50 |
August | 0.549738E+11 | 87358.58 | 21-AUG-03:02 | 18.17 | 11.57 | 0.549294E+10 | 6734.80 | 10-AUG-09:00 | 18.17 | 11.57 |
September | 0.428298E+11 | 85216.18 | 11-SEP-03:01 | 17.10 | 8.74 | 0.483993E+10 | 6735.33 | 05-SEP-09:09 | 17.10 | 8.74 |
October | 0.268973E+11 | 50216.21 | 11-OCT-05:03 | 10.17 | 3.29 | 0.468779E+10 | 6734.74 | 03-OCT-13:09 | 10.17 | 3.29 |
November | 0.210671E+11 | 35648.96 | 08-NOV-16:20 | 16.33 | 7.18 | 0.445843E+10 | 6734.52 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.176717E+11 | 23660.28 | 15-DEC-16:20 | 4.67 | 1.42 | 0.412122E+10 | 6734.47 | 15-DEC-14:00 | 4.67 | 1.42 |
Annual Sum or Average | 0.400985E+12 | 0.568942E+11 | ||||||||
Minimum of Months | 0.176717E+11 | 23660.28 | 4.67 | 1.42 | 0.400334E+10 | 6734.38 | 4.67 | 1.42 | ||
Maximum of Months | 0.549738E+11 | 89108.02 | 18.83 | 14.98 | 0.549294E+10 | 6735.33 | 28.50 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334920E+10 | 4020.44 | 20-JAN-15:00 | 20.00 | 6.78 | 0.559674E+09 | 845.59 | 20-JAN-14:00 | 20.00 | 6.78 |
February | 0.305388E+10 | 4763.87 | 27-FEB-15:30 | 13.50 | 4.54 | 0.504347E+09 | 845.61 | 22-FEB-14:00 | 13.50 | 4.54 |
March | 0.491191E+10 | 7132.70 | 14-MAR-14:30 | 23.00 | 7.59 | 0.651317E+09 | 845.61 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.535877E+10 | 8063.09 | 20-APR-13:30 | 21.50 | 8.83 | 0.593011E+09 | 845.67 | 13-APR-13:50 | 21.50 | 8.83 |
May | 0.717804E+10 | 9225.22 | 17-MAY-13:30 | 29.00 | 11.78 | 0.658738E+09 | 845.65 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.114526E+11 | 16436.15 | 25-JUN-17:41 | 31.78 | 13.99 | 0.661869E+09 | 846.99 | 26-JUN-13:09 | 36.78 | 15.39 |
July | 0.118006E+11 | 14348.87 | 16-JUL-14:22 | 35.50 | 14.51 | 0.615417E+09 | 847.33 | 24-JUL-13:20 | 32.00 | 16.99 |
August | 0.127616E+11 | 13053.96 | 21-AUG-05:02 | 19.92 | 12.21 | 0.690108E+09 | 883.01 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.782426E+10 | 12710.38 | 05-SEP-05:03 | 14.30 | 8.64 | 0.608797E+09 | 845.71 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.490461E+10 | 7481.94 | 10-OCT-14:40 | 25.00 | 8.55 | 0.601640E+09 | 845.66 | 03-OCT-13:09 | 25.00 | 8.55 |
November | 0.407612E+10 | 6049.18 | 09-NOV-13:30 | 20.00 | 8.78 | 0.577277E+09 | 845.61 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.335146E+10 | 5461.26 | 04-DEC-14:10 | 19.83 | 6.62 | 0.543007E+09 | 845.61 | 04-DEC-10:00 | 19.83 | 6.62 |
Annual Sum or Average | 0.800231E+11 | 0.726520E+10 | ||||||||
Minimum of Months | 0.305388E+10 | 4020.44 | 13.50 | 4.54 | 0.504347E+09 | 845.59 | 6.83 | 4.54 | ||
Maximum of Months | 0.127616E+11 | 16436.15 | 35.50 | 14.51 | 0.690108E+09 | 883.01 | 36.78 | 16.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389117E+10 | 7286.84 | 20-JAN-09:30 | 12.00 | 3.86 | 0.357699E+09 | 544.96 | 10-JAN-10:09 | 12.00 | 3.86 |
February | 0.373138E+10 | 9554.39 | 27-FEB-09:05 | 9.17 | 2.67 | 0.327579E+09 | 544.96 | 23-FEB-10:09 | 9.17 | 2.67 |
March | 0.577531E+10 | 19905.63 | 12-MAR-09:12 | 14.33 | 5.23 | 0.411580E+09 | 544.97 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.575838E+10 | 11961.03 | 21-APR-08:00 | 11.00 | 5.86 | 0.373407E+09 | 544.99 | 13-APR-13:50 | 11.00 | 5.86 |
May | 0.741154E+10 | 12708.39 | 28-MAY-09:32 | 13.33 | 8.91 | 0.422598E+09 | 545.13 | 16-MAY-09:09 | 13.33 | 8.91 |
June | 0.110627E+11 | 20880.94 | 11-JUN-08:62 | 17.67 | 10.77 | 0.425570E+09 | 546.24 | 26-JUN-09:39 | 29.40 | 15.89 |
July | 0.108367E+11 | 21251.01 | 09-JUL-09:21 | 26.00 | 13.06 | 0.395352E+09 | 546.70 | 18-JUL-09:50 | 30.50 | 14.42 |
August | 0.118668E+11 | 20085.04 | 06-AUG-09:12 | 25.67 | 15.47 | 0.442495E+09 | 549.19 | 21-AUG-09:00 | 27.00 | 14.16 |
September | 0.830510E+10 | 21050.45 | 04-SEP-09:02 | 24.68 | 13.41 | 0.390529E+09 | 546.31 | 18-SEP-09:30 | 23.85 | 10.92 |
October | 0.545882E+10 | 15911.05 | 08-OCT-09:22 | 18.00 | 8.32 | 0.374648E+09 | 544.98 | 03-OCT-13:09 | 18.00 | 8.32 |
November | 0.436150E+10 | 9188.35 | 06-NOV-08:45 | 12.50 | 3.54 | 0.359802E+09 | 544.95 | 27-NOV-10:20 | -0.7 | -1.9 |
December | 0.340795E+10 | 6067.65 | 18-DEC-09:15 | 1.00 | -1.7 | 0.335950E+09 | 544.94 | 13-DEC-10:09 | 1.00 | -1.7 |
Annual Sum or Average | 0.818674E+11 | 0.461721E+10 | ||||||||
Minimum of Months | 0.340795E+10 | 6067.65 | 1.00 | -1.7 | 0.327579E+09 | 544.94 | -0.7 | -1.9 | ||
Maximum of Months | 0.118668E+11 | 21251.01 | 26.00 | 15.47 | 0.442495E+09 | 549.19 | 30.50 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966250E+10 | 22593.74 | 22-JAN-12:22 | 6.50 | 3.36 | 0.603068E+09 | 906.45 | 20-JAN-14:09 | 6.50 | 3.36 |
February | 0.882550E+10 | 23880.91 | 26-FEB-14:02 | 17.00 | 4.30 | 0.543330E+09 | 862.27 | 17-FEB-14:09 | 17.00 | 4.30 |
March | 0.102034E+11 | 24194.93 | 12-MAR-13:52 | 17.00 | 5.49 | 0.651289E+09 | 887.43 | 15-MAR-13:20 | 20.33 | 5.93 |
April | 0.806518E+10 | 15240.81 | 19-APR-13:20 | 22.00 | 8.59 | 0.580420E+09 | 848.90 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.893351E+10 | 12308.49 | 16-MAY-13:10 | 27.17 | 12.14 | 0.650005E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.129079E+11 | 22265.29 | 25-JUN-14:21 | 33.25 | 13.33 | 0.660164E+09 | 847.05 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.136959E+11 | 22599.14 | 30-JUL-13:52 | 29.00 | 19.75 | 0.614285E+09 | 847.16 | 31-JUL-13:39 | 26.33 | 17.62 |
August | 0.173131E+11 | 23026.53 | 27-AUG-11:52 | 24.00 | 15.01 | 0.690276E+09 | 890.07 | 21-AUG-13:20 | 24.00 | 15.01 |
September | 0.134744E+11 | 25188.44 | 04-SEP-12:21 | 28.85 | 13.46 | 0.610331E+09 | 931.60 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.112724E+11 | 23953.89 | 09-OCT-13:22 | 22.00 | 8.88 | 0.599931E+09 | 926.59 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.106312E+11 | 26256.27 | 05-NOV-12:41 | 20.83 | 6.41 | 0.603776E+09 | 920.65 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.889021E+10 | 25427.73 | 03-DEC-13:11 | 17.47 | 6.39 | 0.575073E+09 | 881.53 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.133875E+12 | 0.738195E+10 | ||||||||
Minimum of Months | 0.806518E+10 | 12308.49 | 6.50 | 3.36 | 0.543330E+09 | 845.68 | 6.50 | 3.36 | ||
Maximum of Months | 0.173131E+11 | 26256.27 | 33.25 | 19.75 | 0.690276E+09 | 931.60 | 34.97 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558770E+10 | 9845.17 | 23-JAN-16:00 | 19.00 | 6.19 | 0.358730E+09 | 544.94 | 09-JAN-14:00 | 19.00 | 6.19 |
February | 0.576069E+10 | 11297.79 | 17-FEB-16:30 | 13.50 | 6.66 | 0.332505E+09 | 544.96 | 14-FEB-14:00 | 13.50 | 6.66 |
March | 0.871669E+10 | 25037.20 | 12-MAR-15:52 | 18.00 | 5.76 | 0.424789E+09 | 544.95 | 23-MAR-13:00 | 12.00 | 5.15 |
April | 0.934718E+10 | 23211.27 | 08-APR-17:42 | 14.33 | 4.60 | 0.389165E+09 | 545.00 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.892046E+10 | 19861.53 | 07-MAY-15:52 | 22.00 | 8.57 | 0.419172E+09 | 544.98 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.138190E+11 | 29541.08 | 25-JUN-16:21 | 32.70 | 13.84 | 0.426665E+09 | 545.01 | 20-JUN-13:00 | 32.70 | 13.84 |
July | 0.143155E+11 | 26912.62 | 02-JUL-16:41 | 28.00 | 12.40 | 0.397126E+09 | 544.97 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.190471E+11 | 27491.94 | 13-AUG-16:51 | 22.00 | 9.79 | 0.445946E+09 | 551.76 | 21-AUG-13:00 | 29.00 | 14.55 |
September | 0.980201E+10 | 28680.14 | 10-SEP-15:51 | 32.20 | 12.77 | 0.389647E+09 | 545.01 | 05-SEP-09:09 | 32.20 | 12.77 |
October | 0.807159E+10 | 24677.45 | 09-OCT-15:22 | 22.00 | 8.88 | 0.384102E+09 | 544.99 | 03-OCT-13:09 | 22.00 | 8.88 |
November | 0.722841E+10 | 25725.28 | 05-NOV-14:41 | 21.00 | 6.70 | 0.380671E+09 | 544.95 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.680615E+10 | 24665.77 | 17-DEC-14:52 | 17.50 | 5.64 | 0.370547E+09 | 544.96 | 15-DEC-14:39 | 17.50 | 5.64 |
Annual Sum or Average | 0.117423E+12 | 0.471907E+10 | ||||||||
Minimum of Months | 0.558770E+10 | 9845.17 | 13.50 | 4.60 | 0.332505E+09 | 544.94 | 12.00 | 5.15 | ||
Maximum of Months | 0.190471E+11 | 29541.08 | 32.70 | 13.84 | 0.445946E+09 | 551.76 | 32.70 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178222E+10 | 3390.16 | 20-JAN-16:00 | 18.00 | 7.49 | 0.494997E+09 | 778.50 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.145517E+10 | 3320.32 | 27-FEB-15:10 | 13.83 | 4.68 | 0.442546E+09 | 769.43 | 28-FEB-14:09 | 4.83 | 2.68 |
March | 0.276273E+10 | 5448.39 | 14-MAR-15:00 | 23.00 | 7.59 | 0.580336E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.290818E+10 | 5899.34 | 20-APR-13:30 | 21.50 | 8.83 | 0.536762E+09 | 845.66 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.555171E+10 | 8729.08 | 17-MAY-13:30 | 29.00 | 11.78 | 0.643341E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.968609E+10 | 15425.27 | 25-JUN-17:41 | 31.78 | 13.99 | 0.661095E+09 | 846.47 | 29-JUN-13:39 | 32.90 | 14.02 |
July | 0.943030E+10 | 15037.91 | 16-JUL-14:22 | 35.50 | 14.51 | 0.614427E+09 | 846.37 | 24-JUL-13:20 | 32.00 | 16.99 |
August | 0.866541E+10 | 10056.58 | 03-AUG-05:03 | 17.33 | 13.86 | 0.687946E+09 | 845.93 | 18-AUG-13:20 | 33.67 | 12.84 |
September | 0.635230E+10 | 9443.21 | 11-SEP-14:30 | 28.85 | 13.58 | 0.600979E+09 | 845.70 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.313784E+10 | 5987.20 | 11-OCT-14:40 | 26.33 | 9.55 | 0.551375E+09 | 845.61 | 10-OCT-13:50 | 26.33 | 9.55 |
November | 0.209040E+10 | 3892.60 | 09-NOV-13:50 | 20.00 | 8.66 | 0.504035E+09 | 845.60 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.122840E+10 | 3146.99 | 01-DEC-15:00 | 21.00 | 7.36 | 0.463439E+09 | 767.60 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.550507E+11 | 0.678128E+10 | ||||||||
Minimum of Months | 0.122840E+10 | 3146.99 | 13.83 | 4.68 | 0.442546E+09 | 767.60 | 4.83 | 2.68 | ||
Maximum of Months | 0.968609E+10 | 15425.27 | 35.50 | 14.51 | 0.687946E+09 | 846.47 | 33.67 | 16.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261548E+10 | 5618.24 | 20-JAN-09:40 | 12.67 | 4.18 | 0.239038E+09 | 521.18 | 24-JAN-09:30 | 9.00 | 2.21 |
February | 0.258103E+10 | 7215.53 | 27-FEB-09:20 | 9.33 | 2.70 | 0.221957E+09 | 521.19 | 23-FEB-09:00 | 9.33 | 2.70 |
March | 0.438518E+10 | 11064.70 | 12-MAR-10:02 | 15.17 | 5.61 | 0.285365E+09 | 521.22 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.432018E+10 | 11829.15 | 21-APR-08:50 | 11.83 | 5.97 | 0.260438E+09 | 521.23 | 13-APR-10:09 | 11.83 | 5.97 |
May | 0.672931E+10 | 15628.35 | 28-MAY-08:42 | 11.67 | 8.61 | 0.303928E+09 | 521.64 | 16-MAY-08:00 | 11.67 | 8.61 |
June | 0.106979E+11 | 21250.26 | 18-JUN-10:12 | 25.33 | 18.24 | 0.312200E+09 | 523.01 | 29-JUN-08:00 | 28.30 | 13.38 |
July | 0.100628E+11 | 22804.20 | 09-JUL-09:21 | 26.00 | 13.06 | 0.290665E+09 | 521.88 | 17-JUL-07:19 | 26.00 | 12.45 |
August | 0.103862E+11 | 23769.10 | 06-AUG-09:01 | 25.33 | 15.45 | 0.324513E+09 | 523.68 | 07-AUG-10:30 | 29.00 | 14.95 |
September | 0.783486E+10 | 22050.40 | 04-SEP-09:12 | 24.97 | 13.41 | 0.283524E+09 | 521.26 | 05-SEP-08:00 | 16.10 | 11.43 |
October | 0.431750E+10 | 15375.12 | 01-OCT-09:02 | 13.17 | 7.72 | 0.260468E+09 | 521.20 | 03-OCT-10:20 | 11.33 | 8.31 |
November | 0.293877E+10 | 6916.28 | 07-NOV-09:10 | 14.00 | 4.09 | 0.242256E+09 | 521.19 | 06-NOV-08:30 | 14.00 | 4.09 |
December | 0.183127E+10 | 4165.23 | 14-DEC-11:20 | 14.00 | 3.66 | 0.221631E+09 | 500.07 | 15-DEC-09:00 | 5.00 | -0.3 |
Annual Sum or Average | 0.687005E+11 | 0.324598E+10 | ||||||||
Minimum of Months | 0.183127E+10 | 4165.23 | 9.33 | 2.70 | 0.221631E+09 | 500.07 | 0.33 | -0.4 | ||
Maximum of Months | 0.106979E+11 | 23769.10 | 26.00 | 18.24 | 0.324513E+09 | 523.68 | 29.00 | 14.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949614E+10 | 24128.13 | 22-JAN-12:12 | 6.33 | 3.28 | 0.597633E+09 | 969.18 | 20-JAN-14:09 | 6.33 | 3.28 |
February | 0.834356E+10 | 23310.03 | 26-FEB-13:32 | 17.33 | 4.46 | 0.536699E+09 | 907.32 | 17-FEB-14:09 | 17.33 | 4.46 |
March | 0.886577E+10 | 22534.98 | 12-MAR-12:42 | 18.83 | 6.01 | 0.632960E+09 | 921.39 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.608360E+10 | 14730.58 | 21-APR-13:20 | 15.67 | 6.21 | 0.556597E+09 | 847.73 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.781004E+10 | 12224.06 | 16-MAY-13:20 | 27.33 | 12.20 | 0.638763E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.113098E+11 | 21750.76 | 25-JUN-14:21 | 33.25 | 13.33 | 0.658089E+09 | 846.07 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.113938E+11 | 22263.40 | 30-JUL-13:52 | 29.00 | 19.75 | 0.612565E+09 | 846.23 | 31-JUL-13:39 | 26.33 | 17.62 |
August | 0.135028E+11 | 23068.39 | 20-AUG-11:32 | 28.33 | 14.58 | 0.688065E+09 | 901.48 | 31-AUG-13:30 | 30.00 | 11.81 |
September | 0.129586E+11 | 25440.48 | 04-SEP-13:11 | 29.40 | 13.45 | 0.608576E+09 | 989.76 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.105975E+11 | 26023.33 | 09-OCT-12:31 | 21.33 | 9.03 | 0.590928E+09 | 966.60 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.975182E+10 | 25940.14 | 05-NOV-11:51 | 20.00 | 5.63 | 0.593998E+09 | 973.51 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.724818E+10 | 22871.36 | 03-DEC-13:22 | 17.60 | 6.45 | 0.555900E+09 | 905.00 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.117361E+12 | 0.727077E+10 | ||||||||
Minimum of Months | 0.608360E+10 | 12224.06 | 6.33 | 3.28 | 0.536699E+09 | 845.68 | 6.33 | 3.28 | ||
Maximum of Months | 0.135028E+11 | 26023.33 | 33.25 | 19.75 | 0.688065E+09 | 989.76 | 34.97 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308184E+10 | 7904.42 | 20-JAN-16:00 | 18.00 | 7.49 | 0.327667E+09 | 544.85 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.284665E+10 | 8701.67 | 17-FEB-16:30 | 13.50 | 6.66 | 0.297108E+09 | 544.83 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.473924E+10 | 12830.18 | 13-MAR-16:00 | 23.00 | 6.97 | 0.368149E+09 | 544.94 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.448888E+10 | 16855.68 | 08-APR-17:04 | 15.67 | 5.07 | 0.335960E+09 | 544.95 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.671450E+10 | 15606.94 | 07-MAY-15:52 | 22.00 | 8.57 | 0.396755E+09 | 544.96 | 10-MAY-13:39 | 24.67 | 8.89 |
June | 0.104574E+11 | 26618.96 | 25-JUN-16:21 | 32.70 | 13.84 | 0.421328E+09 | 545.01 | 20-JUN-13:00 | 32.70 | 13.84 |
July | 0.944185E+10 | 24073.84 | 02-JUL-16:41 | 28.00 | 12.40 | 0.391076E+09 | 544.97 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.985858E+10 | 24225.29 | 20-AUG-15:31 | 28.00 | 14.04 | 0.436735E+09 | 544.98 | 16-AUG-13:00 | 28.00 | 14.04 |
September | 0.766990E+10 | 26088.63 | 10-SEP-15:51 | 32.20 | 12.77 | 0.374234E+09 | 544.99 | 01-SEP-13:00 | 32.20 | 12.77 |
October | 0.500510E+10 | 22562.08 | 09-OCT-16:31 | 21.33 | 8.70 | 0.343847E+09 | 544.96 | 10-OCT-13:50 | 24.83 | 8.58 |
November | 0.347555E+10 | 9549.11 | 07-NOV-15:40 | 21.33 | 7.24 | 0.329222E+09 | 544.94 | 06-NOV-14:00 | 21.33 | 7.24 |
December | 0.226188E+10 | 6339.54 | 01-DEC-15:30 | 19.50 | 7.14 | 0.307885E+09 | 544.87 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.700414E+11 | 0.432997E+10 | ||||||||
Minimum of Months | 0.226188E+10 | 6339.54 | 13.50 | 5.07 | 0.297108E+09 | 544.83 | 13.50 | 5.44 | ||
Maximum of Months | 0.104574E+11 | 26618.96 | 32.70 | 14.04 | 0.436735E+09 | 545.01 | 32.70 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.899396E+09 | 3744.00 | 20-JAN-15:30 | 19.00 | 7.19 | 0.472217E+09 | 731.56 | 20-JAN-14:00 | 19.00 | 7.19 |
February | 0.757289E+09 | 3322.77 | 17-FEB-14:10 | 15.00 | 6.34 | 0.426977E+09 | 704.56 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.213593E+10 | 5298.17 | 14-MAR-15:00 | 23.00 | 7.59 | 0.549168E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.241824E+10 | 6256.26 | 20-APR-13:30 | 21.50 | 8.83 | 0.506612E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.520184E+10 | 9196.27 | 17-MAY-13:30 | 29.00 | 11.78 | 0.617552E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.102584E+11 | 17883.71 | 25-JUN-17:51 | 31.60 | 13.99 | 0.659130E+09 | 847.02 | 26-JUN-13:09 | 36.78 | 15.39 |
July | 0.999062E+10 | 17813.93 | 16-JUL-14:22 | 35.50 | 14.51 | 0.612551E+09 | 846.24 | 25-JUL-13:20 | 28.67 | 16.33 |
August | 0.904340E+10 | 10694.39 | 16-AUG-14:00 | 37.00 | 16.36 | 0.683507E+09 | 845.65 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.623725E+10 | 10079.91 | 11-SEP-14:30 | 28.85 | 13.58 | 0.586710E+09 | 845.69 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.245723E+10 | 6125.35 | 11-OCT-15:00 | 26.00 | 9.46 | 0.513690E+09 | 845.61 | 11-OCT-13:09 | 26.00 | 9.46 |
November | 0.119508E+10 | 3905.54 | 07-NOV-15:20 | 21.67 | 7.29 | 0.479113E+09 | 833.61 | 09-NOV-14:30 | 19.00 | 8.37 |
December | 0.582637E+09 | 3179.03 | 14-DEC-13:30 | 16.15 | 4.27 | 0.449786E+09 | 704.63 | 04-DEC-14:00 | 16.15 | 4.27 |
Annual Sum or Average | 0.511773E+11 | 0.655701E+10 | ||||||||
Minimum of Months | 0.582637E+09 | 3179.03 | 15.00 | 4.27 | 0.426977E+09 | 704.56 | 12.83 | 4.27 | ||
Maximum of Months | 0.102584E+11 | 17883.71 | 37.00 | 16.36 | 0.683507E+09 | 847.02 | 37.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165142E+10 | 4433.57 | 20-JAN-11:40 | 19.33 | 7.26 | 0.313021E+09 | 544.93 | 20-JAN-10:39 | 19.33 | 7.26 |
February | 0.178571E+10 | 4319.40 | 27-FEB-09:30 | 9.50 | 2.73 | 0.292659E+09 | 544.95 | 23-FEB-10:09 | 9.50 | 2.73 |
March | 0.352025E+10 | 9919.35 | 15-MAR-09:30 | 14.50 | 4.21 | 0.382716E+09 | 544.96 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.371451E+10 | 11216.71 | 21-APR-09:10 | 12.00 | 5.90 | 0.346376E+09 | 544.98 | 13-APR-13:50 | 12.00 | 5.90 |
May | 0.622365E+10 | 11992.12 | 16-MAY-08:50 | 22.50 | 11.55 | 0.408234E+09 | 544.98 | 17-MAY-09:20 | 25.67 | 11.70 |
June | 0.111247E+11 | 21991.94 | 11-JUN-09:12 | 20.73 | 10.95 | 0.425283E+09 | 547.13 | 29-JUN-09:09 | 28.58 | 13.43 |
July | 0.104871E+11 | 21689.14 | 04-JUL-09:32 | 19.33 | 11.50 | 0.394370E+09 | 546.31 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.106859E+11 | 21658.43 | 20-AUG-08:52 | 26.00 | 13.90 | 0.442104E+09 | 545.99 | 16-AUG-09:00 | 26.00 | 13.90 |
September | 0.756392E+10 | 17688.02 | 17-SEP-09:52 | 21.10 | 11.24 | 0.384347E+09 | 545.02 | 05-SEP-09:09 | 21.10 | 11.24 |
October | 0.338355E+10 | 8125.94 | 11-OCT-09:40 | 22.07 | 8.25 | 0.349039E+09 | 544.95 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.191783E+10 | 4829.53 | 07-NOV-09:30 | 14.00 | 4.09 | 0.319745E+09 | 544.94 | 07-NOV-10:39 | 15.33 | 5.06 |
December | 0.114246E+10 | 3710.65 | 14-DEC-13:30 | 16.15 | 4.27 | 0.293755E+09 | 464.69 | 14-DEC-10:20 | 16.15 | 4.27 |
Annual Sum or Average | 0.632010E+11 | 0.435165E+10 | ||||||||
Minimum of Months | 0.114246E+10 | 3710.65 | 9.50 | 2.73 | 0.292659E+09 | 464.69 | 1.33 | -0.7 | ||
Maximum of Months | 0.111247E+11 | 21991.94 | 26.00 | 13.90 | 0.442104E+09 | 547.13 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.747956E+10 | 22017.76 | 22-JAN-12:12 | 6.33 | 3.28 | 0.569731E+09 | 909.00 | 20-JAN-14:09 | 6.33 | 3.28 |
February | 0.681240E+10 | 25010.66 | 26-FEB-13:11 | 17.67 | 4.65 | 0.516973E+09 | 845.92 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.765709E+10 | 26036.16 | 12-MAR-12:22 | 18.50 | 6.07 | 0.611421E+09 | 884.86 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.518674E+10 | 15195.45 | 21-APR-13:20 | 15.67 | 6.21 | 0.535506E+09 | 847.49 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.727029E+10 | 12805.33 | 16-MAY-13:30 | 27.50 | 12.26 | 0.617781E+09 | 845.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.119525E+11 | 20128.73 | 25-JUN-15:51 | 32.70 | 13.68 | 0.654077E+09 | 847.38 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.120275E+11 | 22749.56 | 23-JUL-13:22 | 34.50 | 16.47 | 0.608940E+09 | 845.67 | 18-JUL-13:00 | 34.50 | 16.47 |
August | 0.139856E+11 | 25980.49 | 20-AUG-11:32 | 28.33 | 14.58 | 0.682869E+09 | 883.36 | 31-AUG-13:30 | 30.00 | 11.81 |
September | 0.126903E+11 | 26263.58 | 17-SEP-14:32 | 26.60 | 11.05 | 0.599093E+09 | 952.48 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.918971E+10 | 28417.55 | 08-OCT-13:11 | 20.67 | 8.60 | 0.567434E+09 | 918.03 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.770937E+10 | 25903.88 | 05-NOV-13:32 | 21.00 | 6.43 | 0.568687E+09 | 912.04 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.568781E+10 | 26090.87 | 03-DEC-13:51 | 18.00 | 6.62 | 0.530217E+09 | 846.06 | 15-DEC-14:50 | 9.50 | 3.13 |
Annual Sum or Average | 0.107649E+12 | 0.706273E+10 | ||||||||
Minimum of Months | 0.518674E+10 | 12805.33 | 6.33 | 3.28 | 0.516973E+09 | 845.67 | 6.33 | 3.13 | ||
Maximum of Months | 0.139856E+11 | 28417.55 | 34.50 | 16.47 | 0.682869E+09 | 952.48 | 34.97 | 16.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211965E+10 | 7586.30 | 20-JAN-16:00 | 18.00 | 7.49 | 0.318841E+09 | 542.66 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.208842E+10 | 8282.00 | 17-FEB-16:30 | 13.50 | 6.66 | 0.291595E+09 | 538.07 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.400897E+10 | 15051.48 | 12-MAR-16:21 | 18.00 | 5.68 | 0.358465E+09 | 544.94 | 08-MAR-14:00 | 18.00 | 5.68 |
April | 0.389156E+10 | 15267.52 | 08-APR-17:04 | 15.67 | 5.07 | 0.325259E+09 | 544.95 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.636539E+10 | 14387.35 | 31-MAY-16:00 | 28.00 | 14.86 | 0.383380E+09 | 544.95 | 04-MAY-13:00 | 28.00 | 14.86 |
June | 0.109170E+11 | 29190.89 | 11-JUN-16:31 | 28.17 | 12.60 | 0.417880E+09 | 557.61 | 15-JUN-15:00 | 32.70 | 14.57 |
July | 0.989318E+10 | 28490.04 | 02-JUL-17:11 | 28.00 | 12.39 | 0.387281E+09 | 544.97 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.101569E+11 | 26311.95 | 20-AUG-15:31 | 28.00 | 14.04 | 0.431243E+09 | 544.98 | 16-AUG-13:00 | 28.00 | 14.04 |
September | 0.750644E+10 | 25829.01 | 10-SEP-16:01 | 31.92 | 12.68 | 0.365820E+09 | 545.00 | 01-SEP-13:00 | 31.92 | 12.68 |
October | 0.415368E+10 | 17872.38 | 08-OCT-16:31 | 17.33 | 8.37 | 0.332899E+09 | 544.94 | 11-OCT-13:00 | 27.00 | 9.73 |
November | 0.247881E+10 | 9165.38 | 07-NOV-15:40 | 21.33 | 7.24 | 0.320881E+09 | 544.93 | 08-NOV-14:00 | 19.00 | 7.64 |
December | 0.154945E+10 | 5865.11 | 01-DEC-15:30 | 19.50 | 7.14 | 0.301719E+09 | 538.58 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.651294E+11 | 0.423526E+10 | ||||||||
Minimum of Months | 0.154945E+10 | 5865.11 | 13.50 | 5.07 | 0.291595E+09 | 538.07 | 14.00 | 4.75 | ||
Maximum of Months | 0.109170E+11 | 29190.89 | 31.92 | 14.86 | 0.431243E+09 | 557.61 | 32.70 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242224E+10 | 5778.33 | 26-JAN-06:08 | -2.0 | -2.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.0 | -2.5 |
February | 0.189100E+10 | 5044.85 | 25-FEB-06:08 | 0.17 | -0.3 | 0.00 | 0.00 | 01-FEB-00:10 | 0.17 | -0.3 |
March | 0.374976E+10 | 6709.11 | 13-MAR-05:15 | 6.33 | 1.03 | 0.00 | 0.00 | 01-MAR-00:10 | 6.33 | 1.03 |
April | 0.401579E+10 | 6015.32 | 10-APR-05:15 | 2.33 | -3.4 | 0.00 | 0.00 | 01-APR-00:10 | 2.33 | -3.4 |
May | 0.579363E+10 | 7446.28 | 30-MAY-05:15 | 8.33 | 7.37 | 0.00 | 0.00 | 01-MAY-00:10 | 8.33 | 7.37 |
June | 0.974080E+10 | 11015.38 | 05-JUN-05:13 | 13.47 | 9.51 | 0.00 | 0.00 | 01-JUN-00:10 | 13.47 | 9.51 |
July | 0.998895E+10 | 11592.79 | 24-JUL-05:15 | 18.00 | 14.77 | 0.00 | 0.00 | 01-JUL-00:10 | 18.00 | 14.77 |
August | 0.111850E+11 | 11852.22 | 21-AUG-05:15 | 19.83 | 12.23 | 0.00 | 0.00 | 01-AUG-00:10 | 19.83 | 12.23 |
September | 0.767146E+10 | 12169.44 | 05-SEP-05:15 | 14.20 | 8.43 | 0.00 | 0.00 | 01-SEP-00:10 | 14.20 | 8.43 |
October | 0.459464E+10 | 9511.85 | 10-OCT-05:15 | 8.67 | 4.93 | 0.00 | 0.00 | 01-OCT-00:10 | 8.67 | 4.93 |
November | 0.337240E+10 | 5486.38 | 20-NOV-06:05 | -3.0 | -3.0 | 0.00 | 0.00 | 01-NOV-00:10 | -3.0 | -3.0 |
December | 0.223785E+10 | 5815.44 | 04-DEC-06:09 | 4.33 | 0.46 | 0.00 | 0.00 | 01-DEC-00:10 | 4.33 | 0.46 |
Annual Sum or Average | 0.666635E+11 | 0.00 | ||||||||
Minimum of Months | 0.189100E+10 | 5044.85 | -3.0 | -3.4 | 0.00 | 0.00 | -3.0 | -3.4 | ||
Maximum of Months | 0.111850E+11 | 12169.44 | 19.83 | 14.77 | 0.00 | 0.00 | 19.83 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999308E+09 | 6955.70 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.864559E+09 | 8172.82 | 06-FEB-04:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-FEB-00:10 | -10.0 | -10.0 |
March | 0.190230E+10 | 10110.00 | 19-MAR-07:01 | -15.2 | -15.2 | 0.00 | 0.00 | 01-MAR-00:10 | -15.2 | -15.2 |
April | 0.163474E+10 | 7677.23 | 15-APR-04:01 | -4.2 | -4.2 | 0.00 | 0.00 | 01-APR-00:10 | -4.2 | -4.2 |
May | 0.391639E+10 | 6184.09 | 19-MAY-05:08 | 5.17 | 3.18 | 0.00 | 0.00 | 01-MAY-00:10 | 5.17 | 3.18 |
June | 0.770854E+10 | 7656.32 | 27-JUN-15:10 | 33.38 | 14.35 | 0.00 | 0.00 | 01-JUN-00:10 | 33.38 | 14.35 |
July | 0.775555E+10 | 8729.77 | 24-JUL-05:15 | 18.00 | 14.77 | 0.00 | 0.00 | 01-JUL-00:10 | 18.00 | 14.77 |
August | 0.773832E+10 | 7740.08 | 21-AUG-14:40 | 27.00 | 14.47 | 0.00 | 0.00 | 01-AUG-00:10 | 27.00 | 14.47 |
September | 0.588318E+10 | 7709.51 | 12-SEP-05:13 | 16.43 | 9.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.43 | 9.91 |
October | 0.263410E+10 | 9283.70 | 30-OCT-03:01 | -9.2 | -9.2 | 0.00 | 0.00 | 01-OCT-00:10 | -9.2 | -9.2 |
November | 0.133877E+10 | 7042.99 | 29-NOV-05:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.0 |
December | 0.788257E+09 | 10578.50 | 20-DEC-04:01 | -19.0 | -19.2 | 0.00 | 0.00 | 01-DEC-00:10 | -19.0 | -19.2 |
Annual Sum or Average | 0.431640E+11 | 0.00 | ||||||||
Minimum of Months | 0.788257E+09 | 6184.09 | -19.0 | -19.2 | 0.00 | 0.00 | -19.0 | -19.2 | ||
Maximum of Months | 0.775555E+10 | 10578.50 | 33.38 | 14.77 | 0.00 | 0.00 | 33.38 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504173E+09 | 5991.66 | 20-JAN-14:10 | 20.83 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 20.83 | 6.93 |
February | 0.711141E+09 | 6718.77 | 18-FEB-13:40 | 20.00 | 7.73 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.73 |
March | 0.276930E+10 | 13619.32 | 14-MAR-14:20 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.329710E+10 | 14719.61 | 21-APR-13:40 | 15.33 | 5.87 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 5.87 |
May | 0.720059E+10 | 19496.09 | 31-MAY-14:20 | 28.00 | 14.79 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.79 |
June | 0.163221E+11 | 26466.75 | 26-JUN-12:05 | 36.18 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 36.18 | 15.20 |
July | 0.149413E+11 | 22963.60 | 07-JUL-14:30 | 31.50 | 14.08 | 0.00 | 0.00 | 01-JUL-00:10 | 31.50 | 14.08 |
August | 0.150019E+11 | 25029.78 | 16-AUG-15:10 | 36.17 | 16.19 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 16.19 |
September | 0.944971E+10 | 18192.69 | 12-SEP-14:30 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.318405E+10 | 13145.09 | 11-OCT-14:30 | 26.50 | 9.60 | 0.00 | 0.00 | 01-OCT-00:10 | 26.50 | 9.60 |
November | 0.105896E+10 | 8071.24 | 09-NOV-13:10 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.310299E+09 | 3975.85 | 01-DEC-13:10 | 21.17 | 7.79 | 0.00 | 0.00 | 01-DEC-00:10 | 21.17 | 7.79 |
Annual Sum or Average | 0.747507E+11 | 0.00 | ||||||||
Minimum of Months | 0.310299E+09 | 3975.85 | 15.33 | 5.87 | 0.00 | 0.00 | 15.33 | 5.87 | ||
Maximum of Months | 0.163221E+11 | 26466.75 | 36.18 | 16.19 | 0.00 | 0.00 | 36.18 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330927E+10 | 2409.23 | 23-JAN-16:40 | 15.67 | 5.76 | 95230900.63 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.768236E+10 | 4409.54 | 23-FEB-17:00 | 5.00 | 2.11 | 86396826.32 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.140612E+11 | 7169.75 | 31-MAR-24:00 | 6.10 | 2.00 | 0.103237E+09 | 126.83 | 17-MAR-13:30 | 6.10 | 2.00 |
April | 0.188068E+11 | 8260.33 | 07-APR-17:40 | 17.67 | 7.11 | 91605817.03 | 126.83 | 28-APR-09:09 | 10.17 | 7.81 |
May | 0.434853E+10 | 3505.16 | 31-MAY-24:00 | 16.00 | 10.67 | 99237925.80 | 126.86 | 22-MAY-13:00 | 16.00 | 10.67 |
June | 0.946608E+10 | 5352.58 | 30-JUN-23:35 | 22.97 | 11.07 | 98962765.72 | 126.86 | 22-JUN-13:09 | 22.97 | 11.07 |
July | 0.147707E+11 | 7280.58 | 31-JUL-23:52 | 18.90 | 16.75 | 91884589.10 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.201704E+11 | 8498.02 | 05-AUG-18:40 | 19.33 | 15.14 | 0.105057E+09 | 150.28 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.442457E+10 | 3354.54 | 30-SEP-24:00 | 10.40 | 8.79 | 91608384.38 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.915330E+10 | 4674.85 | 09-OCT-16:45 | 21.17 | 8.73 | 95231514.98 | 126.84 | 03-OCT-13:30 | 21.17 | 8.73 |
November | 0.136168E+11 | 6338.98 | 07-NOV-16:10 | 20.00 | 7.03 | 94301052.09 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.189738E+11 | 8104.15 | 14-DEC-16:00 | 13.00 | 4.65 | 91880912.15 | 126.82 | 26-DEC-14:00 | 9.00 | 2.31 |
Annual Sum or Average | 0.138784E+12 | 0.114464E+10 | ||||||||
Minimum of Months | 0.330927E+10 | 2409.23 | 5.00 | 2.00 | 86396826.32 | 126.82 | 5.00 | 2.00 | ||
Maximum of Months | 0.201704E+11 | 8498.02 | 22.97 | 16.75 | 0.105057E+09 | 150.28 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171076E+10 | 2175.27 | 23-JAN-16:40 | 15.67 | 5.76 | 95228946.49 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.579950E+10 | 4081.05 | 23-FEB-17:00 | 5.00 | 2.11 | 86396815.62 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.120119E+11 | 6619.67 | 31-MAR-23:50 | 6.32 | 2.06 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.32 | 2.06 |
April | 0.164702E+11 | 7743.63 | 07-APR-17:50 | 17.33 | 7.10 | 91605701.72 | 126.83 | 28-APR-09:00 | 11.00 | 8.15 |
May | 0.357140E+10 | 3293.71 | 31-MAY-24:00 | 16.00 | 10.67 | 99237150.35 | 126.84 | 22-MAY-09:50 | 16.00 | 10.67 |
June | 0.886104E+10 | 5243.56 | 30-JUN-23:55 | 22.50 | 11.08 | 98962662.08 | 126.85 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.139778E+11 | 6841.93 | 31-JUL-23:52 | 18.90 | 16.75 | 91884943.05 | 126.84 | 28-JUL-09:20 | 18.90 | 16.75 |
August | 0.187610E+11 | 7924.75 | 05-AUG-18:11 | 19.67 | 15.26 | 0.104344E+09 | 145.32 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.378320E+10 | 2986.74 | 30-SEP-24:00 | 10.40 | 8.79 | 91608205.62 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.763379E+10 | 4160.11 | 05-OCT-16:50 | 19.12 | 7.42 | 95231429.15 | 126.83 | 03-OCT-09:00 | 19.12 | 7.42 |
November | 0.115439E+11 | 5908.81 | 07-NOV-16:20 | 19.00 | 6.82 | 94301050.43 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.157113E+11 | 7403.91 | 14-DEC-16:00 | 13.00 | 4.65 | 91880785.42 | 126.82 | 20-DEC-14:50 | -17.0 | -17.4 |
Annual Sum or Average | 0.119836E+12 | 0.114392E+10 | ||||||||
Minimum of Months | 0.171076E+10 | 2175.27 | 5.00 | 2.06 | 86396815.62 | 126.82 | -17.0 | -17.4 | ||
Maximum of Months | 0.187610E+11 | 7924.75 | 22.50 | 16.75 | 0.104344E+09 | 145.32 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703105E+09 | 2159.66 | 20-JAN-16:40 | 14.00 | 6.06 | 93648375.41 | 128.69 | 03-JAN-10:50 | 14.00 | 6.06 |
February | 0.411889E+10 | 4031.07 | 17-FEB-17:00 | 13.00 | 6.46 | 86396814.79 | 126.83 | 23-FEB-10:00 | 6.00 | 3.52 |
March | 0.105301E+11 | 6365.90 | 31-MAR-23:20 | 6.97 | 2.22 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.97 | 2.22 |
April | 0.149589E+11 | 7833.42 | 07-APR-17:40 | 17.67 | 7.11 | 91605781.03 | 126.83 | 28-APR-09:00 | 11.00 | 8.15 |
May | 0.300697E+10 | 3224.55 | 31-MAY-24:00 | 16.00 | 10.67 | 99205157.71 | 126.84 | 30-MAY-13:00 | 16.00 | 10.67 |
June | 0.884536E+10 | 5198.58 | 30-JUN-23:03 | 23.67 | 11.03 | 98962822.26 | 126.86 | 22-JUN-13:09 | 23.67 | 11.03 |
July | 0.139688E+11 | 6716.31 | 31-JUL-23:52 | 18.90 | 16.75 | 91884962.64 | 126.84 | 28-JUL-09:20 | 18.90 | 16.75 |
August | 0.187229E+11 | 8052.60 | 13-AUG-18:41 | 21.33 | 9.71 | 0.104163E+09 | 145.42 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.345089E+10 | 2836.92 | 10-SEP-17:35 | 29.77 | 11.98 | 91607845.06 | 126.85 | 01-SEP-13:00 | 29.77 | 11.98 |
October | 0.617903E+10 | 4182.18 | 05-OCT-16:50 | 19.12 | 7.42 | 95231410.85 | 126.83 | 03-OCT-09:00 | 19.12 | 7.42 |
November | 0.967111E+10 | 5896.80 | 07-NOV-16:20 | 19.00 | 6.82 | 94301082.73 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.135863E+11 | 7334.35 | 14-DEC-16:00 | 13.00 | 4.65 | 91880802.09 | 126.82 | 14-DEC-14:00 | 13.00 | 4.65 |
Annual Sum or Average | 0.107742E+12 | 0.114212E+10 | ||||||||
Minimum of Months | 0.703105E+09 | 2159.66 | 6.97 | 2.22 | 86396814.79 | 126.82 | 5.00 | 2.22 | ||
Maximum of Months | 0.187229E+11 | 8052.60 | 29.77 | 16.75 | 0.104163E+09 | 145.42 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237901E+12 | 92341.04 | 20-JAN-17:00 | 12.00 | 5.16 | 0.206148E+10 | 2745.81 | 23-JAN-14:09 | 19.00 | 5.51 |
February | 0.434984E+12 | 183831.73 | 27-FEB-17:00 | 13.00 | 4.60 | 0.187274E+10 | 2749.94 | 17-FEB-14:39 | 13.00 | 4.60 |
March | 0.728439E+12 | 358540.06 | 31-MAR-24:00 | 6.10 | 2.00 | 0.223672E+10 | 2748.37 | 30-MAR-13:39 | 6.10 | 2.00 |
April | 0.937063E+12 | 366229.72 | 21-APR-07:15 | 9.67 | 5.88 | 0.223296E+10 | 3595.44 | 19-APR-13:00 | 9.67 | 5.88 |
May | 0.240948E+12 | 176084.86 | 31-MAY-24:00 | 16.00 | 10.67 | 0.214839E+10 | 2748.12 | 31-MAY-13:30 | 16.00 | 10.67 |
June | 0.471197E+12 | 268216.08 | 30-JUN-23:53 | 22.50 | 11.08 | 0.214403E+10 | 2749.62 | 09-JUN-09:09 | 22.50 | 11.08 |
July | 0.732262E+12 | 356359.51 | 31-JUL-23:15 | 18.70 | 17.05 | 0.198982E+10 | 2751.15 | 17-JUL-13:30 | 18.70 | 17.05 |
August | 0.959108E+12 | 366510.61 | 17-AUG-07:10 | 14.33 | 5.88 | 0.322621E+10 | 4634.87 | 16-AUG-13:00 | 14.33 | 5.88 |
September | 0.237511E+12 | 176256.34 | 30-SEP-24:00 | 10.40 | 8.79 | 0.198365E+10 | 2748.07 | 27-SEP-13:00 | 10.40 | 8.79 |
October | 0.487394E+12 | 266441.07 | 31-OCT-24:00 | -5.8 | -5.8 | 0.206422E+10 | 2749.77 | 26-OCT-13:00 | -5.8 | -5.8 |
November | 0.708349E+12 | 277311.45 | 07-NOV-17:00 | 15.00 | 5.62 | 0.204305E+10 | 2748.25 | 17-NOV-14:50 | 12.33 | 5.08 |
December | 0.971149E+12 | 367542.19 | 19-DEC-17:00 | -17.0 | -17.2 | 0.216927E+10 | 3440.97 | 04-DEC-14:00 | -17.0 | -17.2 |
Annual Sum or Average | 0.714630E+13 | 0.261725E+11 | ||||||||
Minimum of Months | 0.237511E+12 | 92341.04 | -17.0 | -17.2 | 0.187274E+10 | 2745.81 | -17.0 | -17.2 | ||
Maximum of Months | 0.971149E+12 | 367542.19 | 22.50 | 17.05 | 0.322621E+10 | 4634.87 | 22.50 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207519E+09 | 16203.46 | 01-JAN-10:23 | 6.50 |
February | 0.125626E+09 | 14730.18 | 27-FEB-04:04 | 5.00 |
March | 0.144465E+09 | 14917.17 | 13-MAR-04:25 | 6.50 |
April | 0.116573E+09 | 14614.07 | 07-APR-04:05 | 9.17 |
May | 0.244685E+09 | 16382.64 | 29-MAY-15:12 | 14.67 |
June | 0.334787E+09 | 19726.15 | 24-JUN-16:01 | 31.60 |
July | 0.507393E+09 | 22445.88 | 15-JUL-16:01 | 34.00 |
August | 0.435713E+09 | 21027.48 | 26-AUG-16:01 | 32.67 |
September | 0.424522E+09 | 17131.60 | 02-SEP-16:02 | 29.62 |
October | 0.219135E+09 | 15270.11 | 10-OCT-03:35 | 8.67 |
November | 0.216261E+09 | 14619.90 | 27-NOV-04:54 | -7.0 |
December | 0.149385E+09 | 14587.39 | 18-DEC-04:45 | 4.00 |
Annual Sum or Average | 0.312606E+10 | |||
Minimum of Months | 0.116573E+09 | 14587.39 | -7.0 | |
Maximum of Months | 0.507393E+09 | 22445.88 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 8992778.89 | 39460.57 | 13-FEB-06:01 | -10.8 |
March | 1895175.09 | 30732.29 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.103590E+09 | 43753.45 | 26-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.114478E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.8 | |
Maximum of Months | 0.103590E+09 | 43753.45 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240513E+10 | 79777.55 | 17-JAN-04:01 | -1.8 |
February | 0.233402E+10 | 82837.50 | 06-FEB-04:11 | -10.0 |
March | 0.107481E+10 | 80977.40 | 20-MAR-03:01 | -1.5 |
April | 0.144568E+10 | 79256.77 | 03-APR-03:11 | -8.0 |
May | 0.120758E+09 | 72315.52 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.870805E+09 | 78124.07 | 30-OCT-03:01 | -9.2 |
November | 0.123008E+10 | 73928.70 | 27-NOV-05:01 | -7.0 |
December | 0.330958E+10 | 81933.70 | 26-DEC-04:01 | 0.50 |
Annual Sum or Average | 0.127909E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.330958E+10 | 82837.50 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79120761.19 | 11628.74 | 06-JAN-05:01 | -7.8 |
February | 60939463.41 | 11582.23 | 13-FEB-05:01 | -11.0 |
March | 1441937.24 | 11216.77 | 20-MAR-05:01 | 0.00 |
April | 229771.46 | 2388.23 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 4924482.67 | 11215.09 | 30-OCT-05:01 | -10.0 |
November | 19934003.65 | 11365.98 | 30-NOV-06:01 | -12.0 |
December | 0.282496E+09 | 12255.21 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.449086E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.282496E+09 | 12255.21 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66577386.33 | 10331.17 | 06-JAN-05:01 | -7.8 |
February | 76194208.14 | 10320.13 | 06-FEB-05:01 | -10.0 |
March | 5367909.13 | 9796.19 | 20-MAR-05:01 | 0.00 |
April | 5321972.41 | 8677.29 | 15-APR-05:01 | -5.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 17973075.45 | 9683.25 | 30-OCT-05:01 | -10.0 |
November | 43662798.42 | 9858.22 | 30-NOV-06:01 | -12.0 |
December | 0.255363E+09 | 11282.18 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.470460E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.255363E+09 | 11282.18 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101507E+09 | 15696.80 | 06-JAN-05:01 | -7.8 |
February | 0.187097E+09 | 16582.70 | 06-FEB-05:01 | -10.0 |
March | 30434010.46 | 15412.22 | 20-MAR-04:01 | 0.83 |
April | 44938661.89 | 14383.26 | 17-APR-04:50 | -8.0 |
May | 403642.27 | 5381.90 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 73414313.12 | 15649.53 | 31-OCT-04:01 | -8.0 |
November | 75808574.08 | 15409.01 | 01-NOV-04:01 | -3.0 |
December | 0.301370E+09 | 16713.93 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.814973E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.301370E+09 | 16713.93 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6131413.33 | 7682.26 | 05-JAN-06:01 | -17.0 |
February | 3187139.84 | 7763.15 | 13-FEB-06:01 | -10.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 428575.25 | 7142.92 | 30-OCT-05:01 | -10.0 |
November | 921402.08 | 7693.28 | 01-NOV-05:01 | -3.0 |
December | 3575597.44 | 7783.47 | 21-DEC-06:01 | -19.0 |
Annual Sum or Average | 14244127.95 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 6131413.33 | 7783.47 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112395E+10 | 12351.85 | 17-JAN-04:01 | -1.8 |
February | 0.164675E+10 | 13246.30 | 06-FEB-04:01 | -10.0 |
March | 0.777723E+09 | 13583.87 | 19-MAR-07:01 | -15.2 |
April | 0.384203E+09 | 12565.94 | 17-APR-03:01 | -8.0 |
May | 14000498.70 | 10810.17 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 2087198.36 | 6577.36 | 22-SEP-05:02 | -1.7 |
October | 0.444469E+09 | 12704.24 | 30-OCT-03:01 | -9.2 |
November | 0.803214E+09 | 12557.91 | 01-NOV-03:01 | -3.5 |
December | 0.295140E+10 | 13857.13 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.814780E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.295140E+10 | 13857.13 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553273E+09 | 15003.57 | 07-JAN-05:01 | -8.8 |
February | 0.883888E+09 | 16964.89 | 06-FEB-04:01 | -10.0 |
March | 0.461830E+09 | 17024.16 | 19-MAR-07:01 | -15.2 |
April | 0.237756E+09 | 15846.84 | 17-APR-03:01 | -8.0 |
May | 8112511.39 | 13729.60 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 1891965.19 | 5342.40 | 22-SEP-05:02 | -1.7 |
October | 0.322202E+09 | 16309.18 | 30-OCT-03:01 | -9.2 |
November | 0.477060E+09 | 16189.71 | 01-NOV-03:01 | -3.5 |
December | 0.163504E+10 | 17761.26 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.458106E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.163504E+10 | 17761.26 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368073E+09 | 16593.42 | 06-JAN-05:01 | -7.8 |
February | 0.847627E+09 | 18636.12 | 06-FEB-04:01 | -10.0 |
March | 0.527891E+09 | 19081.67 | 19-MAR-07:01 | -15.2 |
April | 0.347890E+09 | 17626.54 | 17-APR-03:01 | -8.0 |
May | 15957005.74 | 15254.28 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 1001034.63 | 4395.74 | 22-SEP-05:02 | -1.7 |
October | 0.370146E+09 | 17594.89 | 30-OCT-03:01 | -9.2 |
November | 0.405612E+09 | 17642.87 | 01-NOV-03:01 | -3.5 |
December | 0.134200E+10 | 19077.75 | 24-DEC-07:11 | -18.7 |
Annual Sum or Average | 0.422619E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.134200E+10 | 19081.67 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396544E+09 | 15095.78 | 06-JAN-05:01 | -7.8 |
February | 0.595333E+09 | 17030.03 | 06-FEB-04:01 | -10.0 |
March | 0.305769E+09 | 16241.31 | 20-MAR-03:01 | -1.5 |
April | 0.181214E+09 | 15109.57 | 17-APR-04:01 | -8.0 |
May | 4362410.11 | 13471.17 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 2533383.11 | 6085.34 | 22-SEP-05:02 | -1.7 |
October | 0.220437E+09 | 16215.81 | 30-OCT-03:01 | -9.2 |
November | 0.320514E+09 | 16089.37 | 01-NOV-03:01 | -3.5 |
December | 0.118321E+10 | 17281.10 | 22-DEC-04:11 | -21.7 |
Annual Sum or Average | 0.320991E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.118321E+10 | 17281.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506635E+10 | 16117.34 | 16-JAN-07:12 | -9.7 |
February | 0.535801E+10 | 16906.44 | 12-FEB-04:42 | -19.8 |
March | 0.338606E+10 | 16980.80 | 18-MAR-23:02 | -8.8 |
April | 0.229670E+10 | 16148.67 | 16-APR-20:12 | -2.3 |
May | 0.201430E+09 | 15135.84 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 80664160.03 | 13471.43 | 22-SEP-04:02 | -0.3 |
October | 0.228354E+10 | 16216.19 | 29-OCT-19:42 | -6.8 |
November | 0.348167E+10 | 15998.55 | 30-NOV-03:23 | -14.0 |
December | 0.806279E+10 | 17244.84 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.302172E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 0.806279E+10 | 17244.84 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245396E+10 | 17869.39 | 17-JAN-04:01 | -1.8 |
February | 0.279358E+10 | 18971.89 | 12-FEB-04:42 | -19.8 |
March | 0.182790E+10 | 19005.85 | 18-MAR-23:02 | -8.8 |
April | 0.131717E+10 | 18225.35 | 03-APR-03:11 | -8.0 |
May | 0.101110E+09 | 17127.60 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 40579457.43 | 15078.57 | 22-SEP-04:02 | -0.3 |
October | 0.140885E+10 | 18219.14 | 30-OCT-03:01 | -9.2 |
November | 0.184440E+10 | 18100.70 | 30-NOV-04:01 | -13.8 |
December | 0.452547E+10 | 19425.09 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.163130E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 0.452547E+10 | 19425.09 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210922E+10 | 20969.74 | 05-JAN-04:11 | -16.3 |
February | 0.318144E+10 | 22088.44 | 12-FEB-04:42 | -19.8 |
March | 0.250014E+10 | 22599.07 | 18-MAR-23:02 | -8.8 |
April | 0.200833E+10 | 21531.16 | 03-APR-03:11 | -8.0 |
May | 0.205595E+09 | 20210.88 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 60042704.69 | 17804.61 | 22-SEP-04:02 | -0.3 |
October | 0.179722E+10 | 21478.98 | 30-OCT-03:01 | -9.2 |
November | 0.184783E+10 | 21262.57 | 01-NOV-03:01 | -3.5 |
December | 0.446908E+10 | 22766.00 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.181789E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 0.446908E+10 | 22766.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194621E+10 | 20564.15 | 17-JAN-04:01 | -1.8 |
February | 0.217847E+10 | 21426.09 | 12-FEB-04:42 | -19.8 |
March | 0.142372E+10 | 21775.22 | 19-MAR-07:01 | -15.2 |
April | 0.934577E+09 | 20880.46 | 03-APR-03:11 | -8.0 |
May | 92333695.62 | 18164.69 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 38089127.89 | 17483.19 | 22-SEP-04:02 | -0.3 |
October | 0.101605E+10 | 20943.36 | 30-OCT-03:01 | -9.2 |
November | 0.138003E+10 | 20751.89 | 30-NOV-04:01 | -13.8 |
December | 0.350154E+10 | 22096.64 | 24-DEC-05:51 | -18.0 |
Annual Sum or Average | 0.125110E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 0.350154E+10 | 22096.64 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188096E+09 | 11335.79 | 17-JAN-06:01 | -0.2 |
February | 0.402381E+09 | 12158.27 | 14-FEB-06:01 | -5.2 |
March | 0.176002E+09 | 12987.44 | 21-MAR-05:01 | 0.00 |
April | 88035990.70 | 14053.14 | 18-APR-04:01 | 5.50 |
May | 73774016.36 | 12391.11 | 01-MAY-03:01 | 5.92 |
June | 80366581.75 | 8385.50 | 23-JUN-03:01 | 13.62 |
July | 0.115210E+09 | 9179.21 | 06-JUL-03:01 | 14.00 |
August | 86455687.56 | 9530.08 | 20-AUG-15:01 | 28.00 |
September | 76870975.78 | 9073.77 | 25-SEP-03:02 | 7.70 |
October | 0.100611E+09 | 10651.39 | 26-OCT-04:02 | 3.83 |
November | 0.248594E+09 | 12379.17 | 03-NOV-04:01 | -2.0 |
December | 0.444434E+09 | 16194.05 | 26-DEC-05:02 | 3.67 |
Annual Sum or Average | 0.208083E+10 | |||
Minimum of Months | 73774016.36 | 8385.50 | -5.2 | |
Maximum of Months | 0.444434E+09 | 16194.05 | 28.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113982E+10 | 9583.05 | 01-JAN-14:02 | 5.97 |
February | 0.162784E+10 | 7255.67 | 26-FEB-13:32 | 17.33 |
March | 0.955920E+09 | 7721.74 | 08-MAR-06:03 | 8.17 |
April | 0.745605E+09 | 8363.66 | 19-APR-05:03 | 5.33 |
May | 0.130847E+09 | 7578.07 | 04-MAY-05:02 | 8.17 |
June | 57513132.77 | 8235.12 | 25-JUN-15:01 | 33.62 |
July | 61229374.07 | 6375.02 | 24-JUL-03:02 | 18.83 |
August | 50507684.44 | 7436.25 | 20-AUG-15:31 | 28.00 |
September | 66689117.71 | 8530.17 | 24-SEP-15:42 | 22.20 |
October | 0.339459E+09 | 9119.10 | 09-OCT-15:51 | 22.00 |
November | 0.817481E+09 | 8509.10 | 05-NOV-11:53 | 20.00 |
December | 0.212888E+10 | 8777.19 | 26-DEC-06:05 | 7.00 |
Annual Sum or Average | 0.812179E+10 | |||
Minimum of Months | 50507684.44 | 6375.02 | 5.33 | |
Maximum of Months | 0.212888E+10 | 9583.05 | 33.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.890323E+10 | 26613.38 | 05-JAN-06:01 | -17.0 |
February | 0.855844E+10 | 31329.47 | 13-FEB-05:33 | -11.0 |
March | 0.605111E+10 | 24412.58 | 20-MAR-04:07 | 0.83 |
April | 0.437696E+10 | 28802.62 | 17-APR-04:22 | -8.0 |
May | 0.822210E+09 | 19676.38 | 05-MAY-05:03 | 6.00 |
June | 0.140739E+09 | 19238.91 | 09-JUN-05:03 | 6.97 |
July | 0.110666E+09 | 16798.49 | 03-JUL-04:02 | 11.00 |
August | 0.115279E+09 | 15825.43 | 23-AUG-05:03 | 11.17 |
September | 0.533430E+09 | 19314.40 | 27-SEP-05:03 | 9.22 |
October | 0.478461E+10 | 28331.49 | 30-OCT-05:12 | -10.0 |
November | 0.632173E+10 | 29550.21 | 30-NOV-06:12 | -12.0 |
December | 0.124382E+11 | 34489.47 | 22-DEC-05:21 | -21.0 |
Annual Sum or Average | 0.531566E+11 | |||
Minimum of Months | 0.110666E+09 | 15825.43 | -21.0 | |
Maximum of Months | 0.124382E+11 | 34489.47 | 11.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65497377.86 | 427.84 | 07-JAN-21:55 | -8.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 65497377.86 | |||
Minimum of Months | 0.00 | 0.00 | -8.0 | |
Maximum of Months | 65497377.86 | 427.84 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.724399E+09 | 729.12 | 01-JAN-17:15 | 1.67 |
February | 88248936.55 | 668.16 | 05-FEB-19:15 | -8.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 2569513.71 | 747.10 | 30-APR-23:05 | 5.32 |
May | 29308001.88 | 694.41 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 6684757.47 | 530.22 | 23-SEP-04:43 | 7.38 |
October | 13327975.18 | 522.93 | 30-OCT-03:13 | -9.3 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.864538E+09 | |||
Minimum of Months | 0.00 | 0.00 | -9.3 | |
Maximum of Months | 0.724399E+09 | 747.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196603E+11 | 20573.73 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.178333E+11 | 20573.73 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.211910E+11 | 20573.73 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.189279E+11 | 20573.73 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.204256E+11 | 20573.73 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.203269E+11 | 20573.73 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.190266E+11 | 20573.73 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.211910E+11 | 20573.73 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.189279E+11 | 20573.73 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.196603E+11 | 20573.73 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.194299E+11 | 20573.73 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.190266E+11 | 20573.73 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.235627E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.178333E+11 | 20573.73 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.211910E+11 | 20573.73 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554336E+10 | 5800.91 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.502824E+10 | 5800.91 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.597494E+10 | 5800.91 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.533685E+10 | 5800.91 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.575915E+10 | 5800.91 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.573131E+10 | 5800.91 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.536469E+10 | 5800.91 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.597494E+10 | 5800.91 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.533685E+10 | 5800.91 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.554336E+10 | 5800.91 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.547839E+10 | 5800.91 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.536469E+10 | 5800.91 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.664368E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.502824E+10 | 5800.91 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.597494E+10 | 5800.91 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.204256E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.203269E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.194299E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.235627E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492330E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765768E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 0.839312E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914029E+09 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1768096.28 | 0.457710E+09 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38012721.17 | 0.188539E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49551892.32 | 0.182271E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25643945.68 | 0.174122E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14816619.89 | 0.287326E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250150.58 | 0.638977E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558999E+09 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105941E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130043E+09 | 0.655879E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174122E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49551892.32 | 0.105941E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329561E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510319E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.552584E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593034E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198692.35 | 0.300037E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26629717.34 | 0.117961E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35510878.50 | 0.111161E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18217024.09 | 97217660.31 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10555302.00 | 0.189282E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167907.58 | 0.423233E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366699E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692980E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92279524.73 | 0.428407E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97217660.31 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35510878.50 | 0.692980E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512012E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784794E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842354E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890109E+09 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1770610.15 | 0.449235E+09 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38700080.49 | 0.182368E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50454294.02 | 0.175609E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24782408.80 | 0.171596E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12547165.46 | 0.298585E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174863.74 | 0.653101E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573405E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107883E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128429E+09 | 0.661199E+10 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171596E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50454294.02 | 0.107883E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343275E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541629E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 0.602981E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669399E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189059.72 | 0.322098E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24677305.18 | 0.139195E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31433011.72 | 0.134546E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16280482.75 | 0.135972E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9308324.63 | 0.208166E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166980.24 | 0.453772E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399354E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770286E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83055167.24 | 0.472067E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134546E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31433011.72 | 0.770286E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103461E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161595E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175355E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188066E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3949492.36 | 0.100444E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88586571.39 | 0.434692E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115977E+09 | 0.432768E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60822951.31 | 0.423512E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35561711.85 | 0.627606E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591051.78 | 0.134577E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.10 | 0.117528E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20431.58 | 0.217805E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305509E+09 | 0.139069E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423512E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115977E+09 | 0.217805E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707899E+09 |
February | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110313E+10 |
March | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119739E+10 |
April | 0.688021E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127887E+10 |
May | 0.744847E+09 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2729704.37 | 0.672257E+09 |
June | 0.742030E+09 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60496727.05 | 0.287580E+09 |
July | 0.690839E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78755986.87 | 0.292494E+09 |
August | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39706630.27 | 0.285870E+09 |
September | 0.688021E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23886383.34 | 0.428265E+09 |
October | 0.715730E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401293.51 | 0.920564E+09 |
November | 0.708685E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795386E+09 |
December | 0.690839E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19712.89 | 0.147098E+10 |
Annual Sum or Average | 0.858171E+10 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205996E+09 | 0.944069E+10 |
Minimum of Months | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285870E+09 |
Maximum of Months | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78755986.87 | 0.147098E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117230E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176630E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187543E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193921E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3949839.32 | 0.101542E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89522022.05 | 0.427658E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116205E+09 | 0.431151E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56452004.55 | 0.449062E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27748801.54 | 0.686507E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 230042.89 | 0.147539E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129795E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237594E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294108E+09 | 0.149123E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427658E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116205E+09 | 0.237594E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723971E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112448E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4707.79 | 0.121914E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129942E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2929943.62 | 0.692462E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58961930.97 | 0.309239E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78183734.16 | 0.303009E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41326355.27 | 0.309392E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22998314.14 | 0.444535E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 545978.73 | 0.935516E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814793E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150306E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204951E+09 | 0.967902E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303009E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78183734.16 | 0.150306E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117789E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189274E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205141E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214441E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4814045.51 | 0.116982E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107002E+09 | 0.532730E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137767E+09 | 0.529790E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72610746.17 | 0.515592E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43666475.28 | 0.735194E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 793057.47 | 0.152625E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200754.57 | 0.133951E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57262.81 | 0.256935E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366912E+09 | 0.161847E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515592E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137767E+09 | 0.256935E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802078E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129682E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141286E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147180E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3155074.07 | 0.798877E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71317383.45 | 0.359779E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91198473.96 | 0.364859E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46766884.67 | 0.356891E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27631490.32 | 0.516725E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 423390.06 | 0.106256E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.77 | 0.915667E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21622.92 | 0.173510E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240516E+09 | 0.110940E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356891E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91198473.96 | 0.173510E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131730E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206645E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220372E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222454E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4704049.34 | 0.119293E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108008E+09 | 0.525262E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137988E+09 | 0.528473E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68326585.05 | 0.552159E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33350974.13 | 0.822080E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 412725.57 | 0.170321E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149973E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276634E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352791E+09 | 0.174022E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525262E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137988E+09 | 0.276634E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825292E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132802E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9396.11 | 0.144234E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150175E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3727333.88 | 0.823384E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72090986.00 | 0.382028E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94274256.29 | 0.371973E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50066926.91 | 0.381675E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28321699.60 | 0.533936E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706204.99 | 0.108569E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 697.96 | 0.948554E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177715E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249198E+09 | 0.114018E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371973E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94274256.29 | 0.177715E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.554336E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.502824E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.597494E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.533685E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.575915E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.573131E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.536469E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.597494E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.533685E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.554336E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.547839E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.536469E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.664368E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.502824E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.597494E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106209E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164634E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179957E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193276E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578419.01 | 0.952794E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68913756.56 | 0.395150E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94186529.22 | 0.388393E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44259414.14 | 0.388999E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24348376.44 | 0.611436E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218960.80 | 0.136851E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119608E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226740E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234505E+09 | 0.140095E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388393E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94186529.22 | 0.226740E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182018E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281388E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307052E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327929E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4719568.51 | 0.166420E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126245E+09 | 0.700092E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173013E+09 | 0.692931E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81077632.77 | 0.701203E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45350723.01 | 0.107224E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447658.59 | 0.236670E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204827E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377269E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430853E+09 | 0.240022E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692931E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173013E+09 | 0.377269E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179510E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287878E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316178E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334030E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2816325.55 | 0.181062E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108529E+09 | 0.787468E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140695E+09 | 0.786394E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66920002.52 | 0.794012E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32836084.48 | 0.114487E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86069.64 | 0.239876E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206550E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382359E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351882E+09 | 0.247872E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786394E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140695E+09 | 0.382359E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20573.73 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20573.73 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20573.73 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20573.73 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20573.73 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20573.73 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20573.73 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20573.73 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20573.73 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20573.73 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20573.73 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20573.73 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 960.15 | 13-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1192.18 | 05-FEB-22:52 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 2458.93 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1735.96 | 16-APR-14:53 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 987.85 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.14 | 25-JUN-17:50 | 572.76 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.42 | 16-JUL-12:00 | 531.30 | 03-JUL-03:10 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 629.44 | 27-AUG-17:50 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.42 | 10-SEP-14:40 | 621.54 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 11-OCT-14:00 | 1476.88 | 29-OCT-08:55 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1434.64 | 01-NOV-03:55 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2052.19 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.30 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 388.42 | 2458.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 635.47 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 780.89 | 05-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1610.87 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1148.70 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 649.49 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.34 | 25-JUN-17:50 | 376.47 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.84 | 16-JUL-12:00 | 354.02 | 02-JUL-08:40 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.20 | 06-AUG-16:00 | 353.08 | 27-AUG-17:50 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 10-SEP-14:40 | 409.75 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 976.94 | 29-OCT-08:55 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 936.30 | 01-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1346.55 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.08 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 272.84 | 1610.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 966.03 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1203.61 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2357.02 | 19-MAR-06:51 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1623.96 | 16-APR-14:53 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 965.21 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.89 | 25-JUN-17:50 | 569.45 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.60 | 16-JUL-12:00 | 521.40 | 03-JUL-03:10 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 672.03 | 27-AUG-17:50 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.75 | 10-SEP-14:34 | 611.95 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 11-OCT-14:00 | 1446.58 | 29-OCT-08:55 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1379.72 | 01-NOV-04:03 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2056.27 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.40 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 397.60 | 2357.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 672.02 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 835.88 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1716.37 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1269.19 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 17-MAY-14:50 | 699.83 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.08 | 25-JUN-17:44 | 449.70 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.50 | 16-JUL-12:00 | 388.28 | 03-JUL-03:10 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 02-AUG-16:00 | 556.32 | 27-AUG-17:50 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 | 10-SEP-12:55 | 426.44 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 1040.15 | 29-OCT-08:55 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1009.74 | 01-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1442.73 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.28 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 274.50 | 1716.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1992.36 | 31-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2421.93 | 23-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5240.57 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.31 | 15-APR-04:59 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2055.54 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.36 | 25-JUN-17:50 | 1245.16 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.56 | 16-JUL-12:00 | 1203.70 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.02 | 06-AUG-12:00 | 1434.74 | 27-AUG-17:53 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.20 | 10-SEP-15:00 | 1357.69 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 11-OCT-14:00 | 2936.50 | 29-OCT-08:55 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 05-NOV-13:20 | 3238.76 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 02-DEC-15:00 | 4444.76 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.70 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 889.56 | 5240.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1330.49 | 13-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1642.13 | 23-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3492.00 | 19-MAR-06:51 |
April | 1239.33 | 03-APR-07:10 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.20 | 15-APR-05:00 |
May | 1239.33 | 01-MAY-07:10 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1364.58 | 03-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.18 | 25-JUN-17:50 | 831.00 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.90 | 16-JUL-12:00 | 856.30 | 02-JUL-08:40 |
August | 1239.33 | 01-AUG-07:10 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.07 | 02-AUG-16:00 | 976.48 | 27-AUG-17:53 |
September | 1239.33 | 01-SEP-07:10 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.13 | 10-SEP-14:40 | 899.70 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 11-OCT-14:00 | 1982.77 | 29-OCT-08:55 |
November | 1239.33 | 01-NOV-07:10 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2159.25 | 01-NOV-04:10 |
December | 1239.33 | 01-DEC-08:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 02-DEC-15:00 | 2947.27 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.00 | |||||
Maximum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 598.90 | 3492.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2123.24 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2663.61 | 19-FEB-16:55 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5241.70 | 19-MAR-06:51 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.31 | 15-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2090.17 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.83 | 25-JUN-17:50 | 1238.70 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 919.47 | 16-JUL-12:00 | 1206.13 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.60 | 02-AUG-16:00 | 1680.77 | 27-AUG-17:53 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.36 | 10-SEP-14:34 | 1369.04 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 11-OCT-14:00 | 3091.84 | 29-OCT-08:55 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3238.87 | 01-NOV-04:07 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4552.37 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.13 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 919.47 | 5241.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1367.39 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1692.40 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 14-MAR-13:00 | 3495.76 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.22 | 15-APR-04:59 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1429.20 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.60 | 25-JUN-17:44 | 917.68 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.40 | 16-JUL-12:00 | 879.52 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.69 | 06-AUG-15:50 | 1107.68 | 27-AUG-17:53 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.48 | 04-SEP-12:00 | 895.50 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 | 11-OCT-14:00 | 1998.06 | 29-OCT-08:55 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2159.16 | 01-NOV-04:06 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3008.42 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.52 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 678.40 | 3495.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2469.56 | 13-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2956.14 | 05-FEB-22:58 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6473.07 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4551.89 | 15-APR-04:51 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2367.73 | 02-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.03 | 25-JUN-17:56 | 1505.57 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.13 | 16-JUL-11:55 | 1457.84 | 03-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.32 | 06-AUG-12:00 | 1809.15 | 27-AUG-17:53 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.92 | 10-SEP-14:50 | 1551.11 | 21-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 11-OCT-14:00 | 3300.06 | 29-OCT-18:52 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.64 | 05-NOV-15:00 | 3901.87 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 17-DEC-12:51 | 5461.70 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.84 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.13 | 6473.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1646.40 | 13-JAN-05:07 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1978.13 | 05-FEB-22:54 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4313.68 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3034.77 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1578.48 | 02-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 600.79 | 25-JUN-18:00 | 1011.97 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 723.98 | 16-JUL-11:55 | 1018.96 | 02-JUL-08:30 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 06-AUG-12:00 | 1238.42 | 27-AUG-17:53 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.65 | 10-SEP-14:50 | 1036.84 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2200.23 | 29-OCT-18:52 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 | 05-NOV-15:00 | 2693.70 | 01-NOV-04:09 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 02-DEC-15:00 | 3640.93 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.97 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 723.98 | 4313.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2469.51 | 13-JAN-05:09 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3053.51 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6474.64 | 19-MAR-06:51 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4557.89 | 15-APR-04:51 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2367.73 | 02-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 805.12 | 25-JUN-18:00 | 1497.51 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.78 | 16-JUL-12:00 | 1460.77 | 03-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 2107.11 | 27-AUG-17:53 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.17 | 10-SEP-14:45 | 1575.40 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 11-OCT-14:00 | 3307.60 | 29-OCT-18:52 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4040.31 | 01-NOV-04:10 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5461.59 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1460.77 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.78 | 6474.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1646.35 | 13-JAN-05:06 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1978.89 | 05-FEB-22:54 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 14-MAR-13:00 | 4321.85 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3040.75 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1611.79 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.98 | 25-JUN-10:00 | 1120.34 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 813.05 | 16-JUL-12:00 | 1063.68 | 03-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.05 | 06-AUG-16:00 | 1383.24 | 27-AUG-17:53 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.83 | 04-SEP-12:10 | 1033.96 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2208.64 | 29-OCT-18:52 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 05-NOV-12:20 | 2693.57 | 01-NOV-04:10 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3641.06 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1033.96 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 813.05 | 4321.85 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5800.91 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5800.91 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5800.91 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5800.91 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5800.91 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5800.91 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5800.91 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5800.91 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5800.91 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5800.91 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5800.91 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5800.91 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2120.83 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2596.14 | 05-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5412.22 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3631.39 | 15-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 17-MAY-14:40 | 2120.88 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.85 | 25-JUN-18:00 | 1151.75 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.27 | 16-JUL-12:00 | 1099.82 | 03-JUL-03:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.50 | 06-AUG-12:00 | 1273.74 | 27-AUG-17:57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.74 | 10-SEP-15:00 | 1335.00 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 11-OCT-14:00 | 3164.00 | 29-OCT-08:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3131.86 | 01-NOV-03:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4414.56 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.27 | 5412.22 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3696.11 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4327.47 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9209.56 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6227.15 | 15-APR-04:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.34 | 17-MAY-14:40 | 3638.79 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.99 | 25-JUN-18:00 | 2027.38 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.94 | 16-JUL-12:00 | 1953.02 | 03-JUL-03:34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.27 | 06-AUG-12:00 | 2245.78 | 27-AUG-17:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.92 | 10-SEP-15:00 | 2373.64 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 11-OCT-14:00 | 5378.37 | 29-OCT-08:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5249.79 | 01-NOV-03:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7645.53 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.02 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.94 | 9209.56 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3512.67 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4384.92 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9180.11 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6318.65 | 15-APR-04:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.52 | 17-MAY-13:00 | 3488.69 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.63 | 25-JUN-18:00 | 2192.07 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.84 | 16-JUL-12:00 | 2118.45 | 03-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.77 | 02-AUG-16:00 | 2921.56 | 27-AUG-17:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.75 | 10-SEP-14:30 | 2349.04 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 11-OCT-14:00 | 5128.06 | 29-OCT-08:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5146.58 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8105.28 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2118.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.84 | 9180.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 112520.86 | 02-JAN-04:01 | 0.00 | 10287.50 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109780.60 | 21-FEB-04:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110805.27 | 13-MAR-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110386.73 | 10-APR-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112622.44 | 30-MAY-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104779.98 | 26-JUN-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 104967.01 | 06-JUL-03:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 104407.19 | 17-AUG-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 112258.47 | 25-SEP-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111541.27 | 30-OCT-03:01 | 0.00 | 11430.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113143.33 | 20-NOV-04:01 | 0.00 | 9144.45 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 109886.63 | 11-DEC-04:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 104407.19 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113143.33 | 0.00 | 11430.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84949.16 | 23-JAN-05:01 | 0.00 | 14370.03 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87926.98 | 21-FEB-04:01 | 0.00 | 7185.81 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90064.51 | 13-MAR-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90847.77 | 10-APR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92083.90 | 30-MAY-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90210.70 | 20-JUN-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90148.00 | 06-JUL-03:01 | 0.00 | 7185.81 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90231.29 | 21-AUG-05:03 | 9673.43 | 12317.16 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94388.82 | 05-SEP-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90660.27 | 02-OCT-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91455.65 | 13-NOV-04:01 | 0.00 | 8212.36 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92373.89 | 04-DEC-04:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84949.16 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94388.82 | 9673.43 | 14370.03 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 75009.63 | 27-JAN-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72261.97 | 28-FEB-06:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77944.25 | 15-MAR-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78825.27 | 14-APR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80417.71 | 18-MAY-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82947.76 | 16-JUN-03:01 | 0.00 | 7185.81 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84101.65 | 10-JUL-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84078.57 | 28-AUG-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84814.35 | 05-SEP-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78972.74 | 12-OCT-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78748.68 | 10-NOV-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51452.40 | 15-DEC-06:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 51452.40 | 0.00 | 5132.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84814.35 | 8061.19 | 10264.30 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32947.67 | 20-JAN-16:20 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27715.43 | 23-FEB-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61059.81 | 15-MAR-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65193.03 | 21-APR-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78713.03 | 18-MAY-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84450.06 | 26-JUN-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89108.02 | 24-JUL-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87358.58 | 21-AUG-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85216.18 | 11-SEP-03:01 | 0.00 | 7185.81 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50216.21 | 11-OCT-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35648.96 | 08-NOV-16:20 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23660.28 | 15-DEC-16:20 | 30632.53 | 36953.32 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23660.28 | 0.00 | 6159.27 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89108.02 | 30632.53 | 36953.32 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4020.44 | 20-JAN-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
February | 4763.87 | 27-FEB-15:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.36 |
March | 7132.70 | 14-MAR-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
April | 8063.09 | 20-APR-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 9225.22 | 17-MAY-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
June | 16436.15 | 25-JUN-17:41 | 0.00 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 204.47 | 0.00 |
July | 14348.87 | 16-JUL-14:22 | 506.08 | 644.46 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 318.53 | 0.00 |
August | 13053.96 | 21-AUG-05:02 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
September | 12710.38 | 05-SEP-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 |
October | 7481.94 | 10-OCT-14:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
November | 6049.18 | 09-NOV-13:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
December | 5461.26 | 04-DEC-14:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4020.44 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16436.15 | 2010.79 | 2319.93 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 318.53 | 149.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7286.84 | 20-JAN-09:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 9554.39 | 27-FEB-09:05 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 |
March | 19905.63 | 12-MAR-09:12 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.32 |
April | 11961.03 | 21-APR-08:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 |
May | 12708.39 | 28-MAY-09:32 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.67 |
June | 20880.94 | 11-JUN-08:62 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.92 |
July | 21251.01 | 09-JUL-09:21 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
August | 20085.04 | 06-AUG-09:12 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
September | 21050.45 | 04-SEP-09:02 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 |
October | 15911.05 | 08-OCT-09:22 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 |
November | 9188.35 | 06-NOV-08:45 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 |
December | 6067.65 | 18-DEC-09:15 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6067.65 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | |
Maximum of Months | 21251.01 | 2478.65 | 2990.10 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22593.74 | 22-JAN-12:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.29 |
February | 23880.91 | 26-FEB-14:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.58 |
March | 24194.93 | 12-MAR-13:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.28 |
April | 15240.81 | 19-APR-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
May | 12308.49 | 16-MAY-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 0.00 |
June | 22265.29 | 25-JUN-14:21 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 | 0.00 |
July | 22599.14 | 30-JUL-13:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 0.00 |
August | 23026.53 | 27-AUG-11:52 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 |
September | 25188.44 | 04-SEP-12:21 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 0.00 |
October | 23953.89 | 09-OCT-13:22 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 |
November | 26256.27 | 05-NOV-12:41 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
December | 25427.73 | 03-DEC-13:11 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12308.49 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26256.27 | 2010.83 | 2319.98 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 | 554.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9845.17 | 23-JAN-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
February | 11297.79 | 17-FEB-16:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.02 |
March | 25037.20 | 12-MAR-15:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.10 |
April | 23211.27 | 08-APR-17:42 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.92 |
May | 19861.53 | 07-MAY-15:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.72 |
June | 29541.08 | 25-JUN-16:21 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 | 0.00 |
July | 26912.62 | 02-JUL-16:41 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 27491.94 | 13-AUG-16:51 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.82 |
September | 28680.14 | 10-SEP-15:51 | 587.05 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 0.00 |
October | 24677.45 | 09-OCT-15:22 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.11 |
November | 25725.28 | 05-NOV-14:41 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.35 |
December | 24665.77 | 17-DEC-14:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9845.17 | 326.14 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29541.08 | 1239.33 | 1495.05 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 | 173.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3390.16 | 20-JAN-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
February | 3320.32 | 27-FEB-15:10 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.62 |
March | 5448.39 | 14-MAR-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 |
April | 5899.34 | 20-APR-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
May | 8729.08 | 17-MAY-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 | 0.00 |
June | 15425.27 | 25-JUN-17:41 | 0.00 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 460.96 | 0.00 |
July | 15037.91 | 16-JUL-14:22 | 506.08 | 644.46 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 738.29 | 0.00 |
August | 10056.58 | 03-AUG-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 |
September | 9443.21 | 11-SEP-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 | 0.00 |
October | 5987.20 | 11-OCT-14:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 0.00 |
November | 3892.60 | 09-NOV-13:50 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
December | 3146.99 | 01-DEC-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3146.99 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15425.27 | 2010.79 | 2319.93 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 738.29 | 324.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5618.24 | 20-JAN-09:40 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
February | 7215.53 | 27-FEB-09:20 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 |
March | 11064.70 | 12-MAR-10:02 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.15 |
April | 11829.15 | 21-APR-08:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.69 |
May | 15628.35 | 28-MAY-08:42 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.74 |
June | 21250.26 | 18-JUN-10:12 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 |
July | 22804.20 | 09-JUL-09:21 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
August | 23769.10 | 06-AUG-09:01 | 521.82 | 664.51 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.08 |
September | 22050.40 | 04-SEP-09:12 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.60 |
October | 15375.12 | 01-OCT-09:02 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.43 |
November | 6916.28 | 07-NOV-09:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.19 |
December | 4165.23 | 14-DEC-11:20 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4165.23 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | |
Maximum of Months | 23769.10 | 1239.33 | 1495.05 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24128.13 | 22-JAN-12:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.99 |
February | 23310.03 | 26-FEB-13:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.98 |
March | 22534.98 | 12-MAR-12:42 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.60 |
April | 14730.58 | 21-APR-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.35 |
May | 12224.06 | 16-MAY-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
June | 21750.76 | 25-JUN-14:21 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 139.29 | 0.00 |
July | 22263.40 | 30-JUL-13:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 93.43 | 0.00 |
August | 23068.39 | 20-AUG-11:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 0.00 |
September | 25440.48 | 04-SEP-13:11 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
October | 26023.33 | 09-OCT-12:31 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.79 |
November | 25940.14 | 05-NOV-11:51 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.87 |
December | 22871.36 | 03-DEC-13:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12224.06 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26023.33 | 2010.83 | 2319.98 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 139.29 | 1321.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7904.42 | 20-JAN-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
February | 8701.67 | 17-FEB-16:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 |
March | 12830.18 | 13-MAR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
April | 16855.68 | 08-APR-17:04 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.94 |
May | 15606.94 | 07-MAY-15:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.04 |
June | 26618.96 | 25-JUN-16:21 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 113.08 | 0.00 |
July | 24073.84 | 02-JUL-16:41 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
August | 24225.29 | 20-AUG-15:31 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
September | 26088.63 | 10-SEP-15:51 | 587.05 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 51.91 | 0.00 |
October | 22562.08 | 09-OCT-16:31 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.14 |
November | 9549.11 | 07-NOV-15:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
December | 6339.54 | 01-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6339.54 | 326.14 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26618.96 | 1239.33 | 1495.05 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 113.08 | 501.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3744.00 | 20-JAN-15:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 |
February | 3322.77 | 17-FEB-14:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
March | 5298.17 | 14-MAR-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 |
April | 6256.26 | 20-APR-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 |
May | 9196.27 | 17-MAY-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 97.04 | 0.00 |
June | 17883.71 | 25-JUN-17:51 | 0.00 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 607.47 | 0.00 |
July | 17813.93 | 16-JUL-14:22 | 506.08 | 644.46 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 891.95 | 0.00 |
August | 10694.39 | 16-AUG-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 188.17 | 0.00 |
September | 10079.91 | 11-SEP-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 150.00 | 0.00 |
October | 6125.35 | 11-OCT-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 | 0.00 |
November | 3905.54 | 07-NOV-15:20 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 |
December | 3179.03 | 14-DEC-13:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3179.03 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17883.71 | 2010.79 | 2319.93 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 891.95 | 47.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4433.57 | 20-JAN-11:40 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 |
February | 4319.40 | 27-FEB-09:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 |
March | 9919.35 | 15-MAR-09:30 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 |
April | 11216.71 | 21-APR-09:10 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.61 |
May | 11992.12 | 16-MAY-08:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
June | 21991.94 | 11-JUN-09:12 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.51 |
July | 21689.14 | 04-JUL-09:32 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.57 |
August | 21658.43 | 20-AUG-08:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 |
September | 17688.02 | 17-SEP-09:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 |
October | 8125.94 | 11-OCT-09:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 |
November | 4829.53 | 07-NOV-09:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 |
December | 3710.65 | 14-DEC-13:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3710.65 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | |
Maximum of Months | 21991.94 | 1295.83 | 1495.05 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22017.76 | 22-JAN-12:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1531.76 |
February | 25010.66 | 26-FEB-13:11 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.48 |
March | 26036.16 | 12-MAR-12:22 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 982.44 |
April | 15195.45 | 21-APR-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.57 |
May | 12805.33 | 16-MAY-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 0.00 |
June | 20128.73 | 25-JUN-15:51 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 340.86 | 0.00 |
July | 22749.56 | 23-JUL-13:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 409.08 | 0.00 |
August | 25980.49 | 20-AUG-11:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 0.00 |
September | 26263.58 | 17-SEP-14:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.77 |
October | 28417.55 | 08-OCT-13:11 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.44 |
November | 25903.88 | 05-NOV-13:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.27 |
December | 26090.87 | 03-DEC-13:51 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 893.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12805.33 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28417.55 | 2010.83 | 2319.98 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 409.08 | 1531.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7586.30 | 20-JAN-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
February | 8282.00 | 17-FEB-16:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
March | 15051.48 | 12-MAR-16:21 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.52 |
April | 15267.52 | 08-APR-17:04 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.64 |
May | 14387.35 | 31-MAY-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 0.00 |
June | 29190.89 | 11-JUN-16:31 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 |
July | 28490.04 | 02-JUL-17:11 | 0.00 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.46 |
August | 26311.95 | 20-AUG-15:31 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 |
September | 25829.01 | 10-SEP-16:01 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 93.74 | 0.00 |
October | 17872.38 | 08-OCT-16:31 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.66 |
November | 9165.38 | 07-NOV-15:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 |
December | 5865.11 | 01-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5865.11 | 0.00 | 581.44 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29190.89 | 1239.33 | 1495.05 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 93.74 | 623.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5778.33 | 26-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.41 |
February | 5044.85 | 25-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.03 |
March | 6709.11 | 13-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.26 |
April | 6015.32 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.88 |
May | 7446.28 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.93 |
June | 11015.38 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.04 |
July | 11592.79 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.85 |
August | 11852.22 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
September | 12169.44 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.48 |
October | 9511.85 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.91 |
November | 5486.38 | 20-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.87 |
December | 5815.44 | 04-DEC-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5044.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 | |
Maximum of Months | 12169.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6955.70 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 989.23 |
February | 8172.82 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2414.42 |
March | 10110.00 | 19-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9033.90 |
April | 7677.23 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.04 |
May | 6184.09 | 19-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.82 |
June | 7656.32 | 27-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.14 | 0.00 |
July | 8729.77 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.40 |
August | 7740.08 | 21-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 0.00 |
September | 7709.51 | 12-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.33 |
October | 9283.70 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.98 |
November | 7042.99 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2271.41 |
December | 10578.50 | 20-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4247.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6184.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10578.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.14 | 9033.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5991.66 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 |
February | 6718.77 | 18-FEB-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.54 |
March | 13619.32 | 14-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.01 |
April | 14719.61 | 21-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.33 |
May | 19496.09 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 0.00 |
June | 26466.75 | 26-JUN-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.72 | 0.00 |
July | 22963.60 | 07-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.95 | 0.00 |
August | 25029.78 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.52 | 0.00 |
September | 18192.69 | 12-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 | 0.00 |
October | 13145.09 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | 0.00 |
November | 8071.24 | 09-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
December | 3975.85 | 01-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3975.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26466.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.72 | 324.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2409.23 | 23-JAN-16:40 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4409.54 | 23-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7169.75 | 31-MAR-24:00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8260.33 | 07-APR-17:40 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3505.16 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5352.58 | 30-JUN-23:35 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7280.58 | 31-JUL-23:52 | 0.00 | 127.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8498.02 | 05-AUG-18:40 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3354.54 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4674.85 | 09-OCT-16:45 | 70.15 | 127.19 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6338.98 | 07-NOV-16:10 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8104.15 | 14-DEC-16:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2409.23 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8498.02 | 222.14 | 381.58 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2175.27 | 23-JAN-16:40 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4081.05 | 23-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6619.67 | 31-MAR-23:50 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7743.63 | 07-APR-17:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3293.71 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5243.56 | 30-JUN-23:55 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6841.93 | 31-JUL-23:52 | 0.00 | 127.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7924.75 | 05-AUG-18:11 | 0.00 | 190.79 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2986.74 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4160.11 | 05-OCT-16:50 | 70.15 | 211.99 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5908.81 | 07-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7403.91 | 14-DEC-16:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2175.27 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7924.75 | 222.14 | 381.58 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2159.66 | 20-JAN-16:40 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4031.07 | 17-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6365.90 | 31-MAR-23:20 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7833.42 | 07-APR-17:40 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3224.55 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5198.58 | 30-JUN-23:03 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6716.31 | 31-JUL-23:52 | 0.00 | 127.19 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8052.60 | 13-AUG-18:41 | 0.00 | 169.59 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2836.92 | 10-SEP-17:35 | 0.00 | 42.40 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4182.18 | 05-OCT-16:50 | 70.15 | 211.99 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5896.80 | 07-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7334.35 | 14-DEC-16:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2159.66 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8052.60 | 222.14 | 381.58 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92341.04 | 20-JAN-17:00 | 4808.68 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183831.73 | 27-FEB-17:00 | 4808.68 | 5800.91 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358540.06 | 31-MAR-24:00 | 0.00 | 322.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366229.72 | 21-APR-07:15 | 9617.36 | 11601.83 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176084.86 | 31-MAY-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268216.08 | 30-JUN-23:53 | 0.00 | 1289.17 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356359.51 | 31-JUL-23:15 | 0.00 | 644.59 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366510.61 | 17-AUG-07:10 | 9617.36 | 11601.83 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176256.34 | 30-SEP-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266441.07 | 31-OCT-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277311.45 | 07-NOV-17:00 | 4808.68 | 5800.91 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367542.19 | 19-DEC-17:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92341.04 | 0.00 | 322.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367542.19 | 9617.36 | 11601.83 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.183454E+13 | 1245777.96 | 23-JAN-16:10 | 0.558059E+12 | 1676110.35 | 05-JAN-07:10 |
February | 0.205181E+13 | 1343509.18 | 17-FEB-16:10 | 0.572480E+12 | 1585544.01 | 06-FEB-07:10 |
March | 0.280978E+13 | 1748549.99 | 13-MAR-15:00 | 0.422561E+12 | 1117137.60 | 04-MAR-07:10 |
April | 0.310454E+13 | 1815805.28 | 20-APR-15:00 | 0.285116E+12 | 1243031.64 | 03-APR-06:10 |
May | 0.201698E+13 | 1533789.15 | 31-MAY-15:50 | 0.916773E+11 | 604357.31 | 02-MAY-06:10 |
June | 0.272123E+13 | 1824985.28 | 26-JUN-15:20 | 0.659880E+11 | 80945.51 | 02-JUN-11:50 |
July | 0.318729E+13 | 1980483.77 | 24-JUL-15:30 | 0.626843E+11 | 78744.15 | 05-JUL-11:20 |
August | 0.373167E+13 | 2175458.54 | 16-AUG-15:09 | 0.657695E+11 | 77703.19 | 30-AUG-11:30 |
September | 0.210121E+13 | 1585514.77 | 13-SEP-15:39 | 0.736500E+11 | 647876.84 | 22-SEP-06:10 |
October | 0.235879E+13 | 1600499.04 | 10-OCT-15:00 | 0.303518E+12 | 1366801.43 | 30-OCT-06:10 |
November | 0.266883E+13 | 1627183.10 | 06-NOV-16:49 | 0.448775E+12 | 1393952.33 | 30-NOV-07:10 |
December | 0.316027E+13 | 1715114.13 | 04-DEC-16:30 | 0.793949E+12 | 1927078.22 | 23-DEC-07:10 |
Annual Sum or Average | 0.317469E+14 | 0.374423E+13 | ||||
Minimum of Months | 0.183454E+13 | 1245777.96 | 0.626843E+11 | 77703.19 | ||
Maximum of Months | 0.373167E+13 | 2175458.54 | 0.793949E+12 | 1927078.22 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328950E+12 | 0.929005E+11 | 0.811612E+12 | 0.169596E+12 | 0.218251E+12 | 0.200681E+11 | 0.00 | 0.117537E+12 | 0.184825E+11 | 0.571453E+11 | 0.00 | 0.00 | 0.00 |
February | 0.298382E+12 | 0.782175E+11 | 0.102011E+13 | 0.153195E+12 | 0.198526E+12 | 0.182671E+11 | 0.00 | 0.173512E+12 | 0.243637E+11 | 0.872354E+11 | 0.00 | 0.00 | 0.00 |
March | 0.354561E+12 | 0.785630E+11 | 0.146267E+13 | 0.169879E+12 | 0.235703E+12 | 0.263178E+11 | 0.00 | 0.285327E+12 | 0.648113E+11 | 0.131952E+12 | 0.00 | 0.00 | 0.00 |
April | 0.316695E+12 | 0.678875E+11 | 0.170311E+13 | 0.164100E+12 | 0.223493E+12 | 0.251862E+11 | 0.00 | 0.343731E+12 | 0.840420E+11 | 0.176301E+12 | 0.00 | 0.00 | 0.00 |
May | 0.341755E+12 | 0.630853E+11 | 0.820521E+12 | 0.169738E+12 | 0.259904E+12 | 0.466305E+11 | 0.00 | 0.185676E+12 | 0.752934E+11 | 0.543781E+11 | 0.00 | 0.00 | 0.00 |
June | 0.340103E+12 | 0.573157E+11 | 0.110677E+13 | 0.164363E+12 | 0.320086E+12 | 0.932201E+11 | 0.00 | 0.434106E+12 | 0.140183E+12 | 0.650812E+11 | 0.00 | 0.00 | 0.00 |
July | 0.318348E+12 | 0.609088E+11 | 0.143888E+13 | 0.169473E+12 | 0.314875E+12 | 0.983038E+11 | 0.00 | 0.552444E+12 | 0.149105E+12 | 0.849540E+11 | 0.00 | 0.00 | 0.00 |
August | 0.354561E+12 | 0.670238E+11 | 0.177780E+13 | 0.169879E+12 | 0.324021E+12 | 0.103982E+12 | 0.00 | 0.625835E+12 | 0.146027E+12 | 0.162540E+12 | 0.00 | 0.00 | 0.00 |
September | 0.316695E+12 | 0.724825E+11 | 0.784732E+12 | 0.164097E+12 | 0.273522E+12 | 0.711974E+11 | 0.00 | 0.260500E+12 | 0.109065E+12 | 0.489188E+11 | 0.00 | 0.00 | 0.00 |
October | 0.328950E+12 | 0.832961E+11 | 0.112899E+13 | 0.169597E+12 | 0.234849E+12 | 0.315528E+11 | 0.00 | 0.226308E+12 | 0.597599E+11 | 0.954897E+11 | 0.00 | 0.00 | 0.00 |
November | 0.325095E+12 | 0.877874E+11 | 0.140306E+13 | 0.164207E+12 | 0.217204E+12 | 0.214515E+11 | 0.00 | 0.268189E+12 | 0.523654E+11 | 0.129472E+12 | 0.00 | 0.00 | 0.00 |
December | 0.318348E+12 | 0.949043E+11 | 0.175516E+13 | 0.169471E+12 | 0.218088E+12 | 0.199468E+11 | 0.00 | 0.336721E+12 | 0.597749E+11 | 0.187851E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394244E+13 | 0.904372E+12 | 0.152134E+14 | 0.199759E+13 | 0.303852E+13 | 0.576124E+12 | 0.00 | 0.380989E+13 | 0.983273E+12 | 0.128132E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298382E+12 | 0.573157E+11 | 0.784732E+12 | 0.153195E+12 | 0.198526E+12 | 0.182671E+11 | 0.00 | 0.117537E+12 | 0.184825E+11 | 0.489188E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354561E+12 | 0.949043E+11 | 0.177780E+13 | 0.169879E+12 | 0.324021E+12 | 0.103982E+12 | 0.00 | 0.625835E+12 | 0.149105E+12 | 0.187851E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.485019E+12 | 0.00 | 0.730400E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.505670E+12 | 0.00 | 0.668104E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.346211E+12 | 0.00 | 0.763498E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.216378E+12 | 0.00 | 0.687373E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217877E+11 | 0.00 | 0.698896E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3617669.65 | 0.00 | 0.659843E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.626843E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5740989.34 | 0.00 | 0.657638E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.118549E+11 | 0.00 | 0.617951E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.237721E+12 | 0.00 | 0.657964E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.381912E+12 | 0.00 | 0.668633E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.723997E+12 | 0.00 | 0.699525E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.293056E+13 | 0.00 | 0.813667E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.617951E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.723997E+12 | 0.00 | 0.763498E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 344233.60 | 02-JAN-08:09 | 57580.60 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 120520.01 | 02-JAN-08:20 | 169664.79 | 24-JAN-16:40 | 61269.69 | 20-JAN-14:39 | 0.00 | 01-JAN-00:10 |
February | 344233.60 | 01-FEB-08:09 | 57580.60 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 120520.01 | 01-FEB-08:20 | 169552.27 | 23-FEB-16:30 | 42178.82 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 344233.60 | 01-MAR-08:09 | 57580.60 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 120520.01 | 01-MAR-08:20 | 212622.45 | 14-MAR-15:00 | 64298.73 | 13-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 344233.60 | 03-APR-07:10 | 57580.60 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 120520.01 | 03-APR-07:19 | 214426.40 | 21-APR-13:50 | 59945.32 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 344233.60 | 01-MAY-07:10 | 57580.60 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 120520.01 | 01-MAY-07:19 | 255716.01 | 18-MAY-14:30 | 66147.98 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 |
June | 344233.60 | 01-JUN-07:10 | 57580.60 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 120520.01 | 01-JUN-07:19 | 302310.07 | 07-JUN-14:00 | 70117.74 | 15-JUN-15:50 | 0.00 | 01-JUN-00:10 |
July | 344233.60 | 03-JUL-07:10 | 57580.60 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 120520.01 | 03-JUL-07:19 | 302495.86 | 24-JUL-15:30 | 69233.21 | 18-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 344233.60 | 01-AUG-07:10 | 57580.60 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 120520.01 | 01-AUG-07:19 | 314431.41 | 17-AUG-15:20 | 68980.13 | 07-AUG-12:30 | 0.00 | 01-AUG-00:10 |
September | 344233.60 | 01-SEP-07:10 | 57580.60 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 120520.01 | 01-SEP-07:19 | 296035.87 | 13-SEP-15:39 | 67719.33 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 344233.60 | 02-OCT-07:10 | 57580.60 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 120520.01 | 02-OCT-07:19 | 208911.21 | 20-OCT-15:50 | 64541.70 | 10-OCT-13:09 | 0.00 | 01-OCT-00:10 |
November | 344233.60 | 01-NOV-07:10 | 57580.60 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 120520.01 | 01-NOV-07:19 | 188210.12 | 08-NOV-15:50 | 61464.00 | 09-NOV-11:30 | 0.00 | 01-NOV-00:10 |
December | 344233.60 | 01-DEC-08:09 | 57580.60 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 120520.01 | 01-DEC-08:20 | 156221.87 | 04-DEC-15:30 | 60890.45 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 344233.60 | 57580.60 | 439129.89 | 120520.01 | 156221.87 | 42178.82 | 0.00 | |||||||
Maximum of Months | 344233.60 | 57580.60 | 794004.08 | 120520.01 | 314431.41 | 70117.74 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 134106.00 | 20-JAN-14:39 | 50874.88 | 20-JAN-13:00 | 25576.17 | 14-JAN-12:09 | 0.00 | 0.00 | 0.00 |
February | 155693.97 | 18-FEB-13:30 | 49857.20 | 18-FEB-13:30 | 40524.30 | 09-FEB-18:00 | 0.00 | 0.00 | 0.00 |
March | 316237.87 | 14-MAR-12:00 | 55007.95 | 14-MAR-12:20 | 62456.11 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 |
April | 251481.32 | 19-APR-14:09 | 52169.50 | 20-APR-12:00 | 80621.82 | 18-APR-20:49 | 0.00 | 0.00 | 0.00 |
May | 258206.37 | 17-MAY-13:30 | 82590.46 | 31-MAY-15:00 | 32507.49 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 408276.77 | 26-JUN-15:20 | 83544.70 | 16-JUN-13:39 | 39117.56 | 09-JUN-06:00 | 0.00 | 0.00 | 0.00 |
July | 427917.91 | 17-JUL-12:00 | 83544.70 | 18-JUL-16:10 | 58400.51 | 31-JUL-23:00 | 0.00 | 0.00 | 0.00 |
August | 474127.94 | 16-AUG-15:20 | 83544.70 | 03-AUG-11:09 | 81746.97 | 17-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 296081.31 | 12-SEP-15:00 | 78545.57 | 13-SEP-13:50 | 34499.09 | 30-SEP-23:19 | 0.00 | 0.00 | 0.00 |
October | 290431.07 | 11-OCT-14:30 | 58363.91 | 11-OCT-13:00 | 49544.81 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 213400.78 | 06-NOV-12:39 | 51959.33 | 07-NOV-14:00 | 55159.12 | 29-NOV-18:00 | 0.00 | 0.00 | 0.00 |
December | 245913.94 | 01-DEC-14:00 | 51231.50 | 01-DEC-14:20 | 80087.34 | 16-DEC-07:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 134106.00 | 49857.20 | 25576.17 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 474127.94 | 83544.70 | 81746.97 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1245777.96 | 23-JAN-16:10 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 147999.75 | 40651.25 | 0.00 | 116560.63 | 49312.15 |
February | 1343509.18 | 17-FEB-16:10 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 150516.73 | 34469.66 | 0.00 | 86662.87 | 46648.63 |
March | 1748549.99 | 13-MAR-15:00 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 185163.87 | 63522.59 | 0.00 | 309291.55 | 50461.14 |
April | 1815805.28 | 20-APR-15:00 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 185554.73 | 58625.43 | 0.00 | 239496.77 | 49311.83 |
May | 1533789.15 | 31-MAY-15:50 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 247115.98 | 66066.42 | 0.00 | 257976.85 | 82385.56 |
June | 1824985.28 | 26-JUN-15:20 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 278493.35 | 65364.71 | 0.00 | 408276.77 | 83544.70 |
July | 1980483.77 | 24-JUL-15:30 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 302495.86 | 66270.42 | 0.00 | 409911.74 | 83544.70 |
August | 2175458.54 | 16-AUG-15:09 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 290018.98 | 65303.03 | 0.00 | 473581.33 | 83544.70 |
September | 1585514.77 | 13-SEP-15:39 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 296035.87 | 67241.84 | 0.00 | 278502.64 | 63254.85 |
October | 1600499.04 | 10-OCT-15:00 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 195551.41 | 62954.17 | 0.00 | 273978.57 | 55676.00 |
November | 1627183.10 | 06-NOV-16:49 | 344233.60 | 675712.68 | 57580.60 | 86589.42 | 147824.92 | 39385.26 | 0.00 | 185052.56 | 49302.25 |
December | 1715114.13 | 04-DEC-16:30 | 344233.60 | 794004.08 | 57580.60 | 86589.42 | 132102.38 | 34005.04 | 0.00 | 149774.91 | 49248.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1245777.96 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 132102.38 | 34005.04 | 0.00 | 86662.87 | 46648.63 | |
Maximum of Months | 2175458.54 | 344233.60 | 794004.08 | 57580.60 | 86589.42 | 302495.86 | 67241.84 | 0.00 | 473581.33 | 83544.70 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1647639.10 | 05-JAN-07:10 | 0.00 | 85890.30 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 1553286.44 | 06-FEB-07:10 | 0.00 | 85998.34 | 13-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 1102856.70 | 04-MAR-07:10 | 0.00 | 85856.18 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 1211018.60 | 03-APR-06:10 | 0.00 | 84840.32 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 585818.67 | 02-MAY-06:10 | 0.00 | 83232.16 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 4200.02 | 09-JUN-06:10 | 0.00 | 80945.51 | 02-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 78744.15 | 05-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 1284.64 | 23-AUG-05:40 | 0.00 | 77703.19 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 637350.09 | 22-SEP-06:10 | 0.00 | 79023.32 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 1335307.20 | 30-OCT-06:10 | 0.00 | 81140.70 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 1370702.76 | 30-NOV-07:10 | 0.00 | 83261.44 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 1918931.64 | 23-DEC-07:10 | 0.00 | 84912.52 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 77703.19 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1918931.64 | 0.00 | 85998.34 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.81 | 1.00 | 26.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.39 | 0.00 | 26.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.90 | 0.00 | 25.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.81 | 0.00 | 25.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.08 | 0.00 | 26.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.83 | 0.00 | 25.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 25.96 | 0.00 | 25.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.90 | 0.00 | 25.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.11 | 0.17 | 26.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.21 | 0.17 | 26.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.38 | 0.67 | 26.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.14 | 0.00 | 26.14 |
Annual Sum or Average | 0.00 | 0.00 | 68.50 | 26.14 | 2.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.81 | 0.00 | 25.81 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.81 | 1.00 | 26.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.65 | 0.00 | 25.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.88 | 0.00 | 25.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.63 | 0.00 | 25.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.67 | 0.00 | 25.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.88 | 0.00 | 25.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Annual Sum or Average | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
February | 1.50 | 18.11 | 0.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
March | 0.83 | 19.27 | 0.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
April | 1.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
November | 0.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 2.50 | 18.67 | 0.17 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Annual Sum or Average | 8.00 | 18.62 | 0.50 | 18.72 | 0.17 | 18.85 | 0.00 | 18.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.42 | 0.17 | 19.46 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.00 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.49 | 1.67 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 0.50 | 19.27 | 0.00 | 19.27 | 2.00 | 25.82 | 1.67 | 26.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.27 | 0.00 | 19.27 | 1.67 | 27.49 | 1.67 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.69 | 1.33 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.90 | 3.00 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.05 | 7.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.20 | 3.00 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.01 | 2.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.59 | 2.50 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Annual Sum or Average | 0.67 | 19.03 | 0.00 | 19.03 | 21.83 | 27.66 | 21.83 | 27.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.03 | 0.00 | 19.03 | 7.50 | 28.20 | 7.50 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.00 | 19.44 | 7.67 | 26.21 | 7.67 | 26.28 |
February | 0.33 | 19.19 | 0.00 | 19.19 | 2.50 | 27.00 | 2.50 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.13 | 2.17 | 28.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.56 | 4.67 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.77 | 4.83 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.04 | 9.83 | 27.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.81 | 12.17 | 26.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.51 | 12.00 | 26.51 |
December | 0.67 | 19.01 | 0.00 | 19.01 | 4.17 | 26.70 | 4.17 | 27.27 |
Annual Sum or Average | 1.17 | 19.12 | 0.00 | 19.12 | 61.17 | 26.90 | 61.00 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.44 | 0.00 | 19.44 | 12.17 | 28.13 | 12.17 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.68 | 0.33 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.48 | 1.50 | 28.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.79 | 1.17 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.49 | 1.67 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.23 | 4.33 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.82 | 8.00 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.34 | 8.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.96 | 4.17 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.48 | 2.50 | 28.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.17 | 0.83 | 28.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.03 | 1.33 | 28.03 |
Annual Sum or Average | 0.00 | 0.00 | 72.67 | 27.76 | 34.50 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 28.48 | 8.67 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
February | 6.33 | 18.16 | 1.33 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
March | 3.67 | 17.05 | 1.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
April | 1.83 | 18.61 | 0.17 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.00 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.52 | 1.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
November | 2.83 | 18.79 | 0.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
December | 14.83 | 17.10 | 3.33 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
Annual Sum or Average | 32.83 | 17.69 | 6.33 | 17.73 | 2.00 | 18.20 | 1.67 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.83 | 18.79 | 3.33 | 18.92 | 1.67 | 27.52 | 1.67 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
February | 3.67 | 17.77 | 0.33 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
March | 4.00 | 16.66 | 1.17 | 16.20 | 0.50 | 17.18 | 0.50 | 18.01 |
April | 1.67 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.52 | 0.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.97 | 3.67 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.17 | 10.00 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.29 | 4.33 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.99 | 2.33 | 27.99 |
October | 1.33 | 18.67 | 0.00 | 18.67 | 0.33 | 20.41 | 0.33 | 21.58 |
November | 2.17 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
December | 9.50 | 16.38 | 0.83 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
Annual Sum or Average | 24.50 | 17.29 | 2.33 | 17.10 | 21.67 | 22.01 | 21.67 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 0.00 | 16.33 |
Maximum of Months | 9.50 | 18.78 | 1.17 | 18.78 | 10.00 | 28.29 | 10.00 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.63 | 0.00 | 18.63 | 19.67 | 25.51 | 19.67 | 25.62 |
February | 2.67 | 18.29 | 0.17 | 18.41 | 6.17 | 23.63 | 6.17 | 24.60 |
March | 2.33 | 16.14 | 1.17 | 15.67 | 8.83 | 22.78 | 8.83 | 23.96 |
April | 1.50 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.58 | 3.83 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.85 | 5.83 | 26.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.02 | 11.50 | 27.01 |
October | 0.67 | 18.63 | 0.00 | 18.63 | 19.83 | 25.94 | 19.67 | 26.05 |
November | 1.67 | 18.71 | 0.17 | 18.86 | 22.50 | 25.32 | 22.50 | 25.57 |
December | 5.33 | 17.10 | 0.67 | 17.14 | 7.33 | 22.15 | 7.33 | 23.60 |
Annual Sum or Average | 14.83 | 17.61 | 2.17 | 17.46 | 107.00 | 24.98 | 106.33 | 25.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 18.71 | 1.17 | 18.86 | 22.50 | 27.59 | 22.50 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 2.67 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
March | 1.83 | 16.73 | 1.00 | 16.04 | 0.83 | 18.71 | 0.50 | 19.81 |
April | 1.17 | 18.53 | 0.00 | 18.53 | 0.17 | 19.73 | 0.17 | 20.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.63 | 0.17 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.67 | 3.33 | 28.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.30 | 3.17 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.49 | 1.83 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.36 | 2.17 | 28.37 |
October | 0.67 | 18.68 | 0.00 | 18.68 | 1.17 | 24.71 | 1.00 | 25.96 |
November | 1.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
December | 6.00 | 16.85 | 0.83 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 15.67 | 17.70 | 1.83 | 17.45 | 19.83 | 23.28 | 12.33 | 24.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 | 16.73 |
Maximum of Months | 6.00 | 19.06 | 1.00 | 19.06 | 6.00 | 28.67 | 3.33 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 16.73 | 9.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
February | 36.00 | 16.43 | 11.67 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
March | 24.50 | 16.22 | 6.67 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
April | 20.67 | 16.41 | 7.50 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
May | 0.83 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.61 | 0.83 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.69 | 3.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
October | 12.17 | 17.24 | 4.00 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
November | 15.50 | 17.80 | 3.00 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
December | 59.50 | 16.46 | 23.50 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
Annual Sum or Average | 203.50 | 16.62 | 65.50 | 16.80 | 5.00 | 16.99 | 3.83 | 17.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.50 | 19.11 | 23.50 | 19.11 | 3.50 | 27.69 | 3.00 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 16.00 | 1.67 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
February | 23.33 | 15.65 | 4.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 18.00 | 15.70 | 3.50 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
April | 15.00 | 15.44 | 3.83 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
May | 0.83 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.83 | 4.67 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.17 | 11.50 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.22 | 5.00 | 28.22 |
September | 0.17 | 19.10 | 0.00 | 19.10 | 2.17 | 27.12 | 2.17 | 27.42 |
October | 7.83 | 16.19 | 1.33 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
November | 9.33 | 16.88 | 0.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
December | 34.17 | 15.42 | 5.50 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
Annual Sum or Average | 128.50 | 15.77 | 20.17 | 15.63 | 24.00 | 17.36 | 23.33 | 18.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 | 15.32 |
Maximum of Months | 34.17 | 19.10 | 5.50 | 19.10 | 11.83 | 28.22 | 11.50 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 17.36 | 0.67 | 17.19 | 2.50 | 18.99 | 2.50 | 20.16 |
February | 21.50 | 16.22 | 4.33 | 16.09 | 1.17 | 16.60 | 1.17 | 17.07 |
March | 17.17 | 15.91 | 3.83 | 15.64 | 1.33 | 16.39 | 1.33 | 17.05 |
April | 15.50 | 15.72 | 4.50 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
May | 0.83 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.75 | 5.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.94 | 4.33 | 27.95 |
September | 0.17 | 19.19 | 0.00 | 19.19 | 10.33 | 26.98 | 9.83 | 27.02 |
October | 6.67 | 16.32 | 0.83 | 16.39 | 10.17 | 22.36 | 10.17 | 23.96 |
November | 7.83 | 17.50 | 0.50 | 17.65 | 4.83 | 20.91 | 4.83 | 22.42 |
December | 29.67 | 16.21 | 4.50 | 16.27 | 1.50 | 16.77 | 1.50 | 17.22 |
Annual Sum or Average | 107.67 | 16.30 | 19.17 | 16.21 | 43.67 | 19.01 | 42.50 | 20.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 0.00 | 15.61 |
Maximum of Months | 29.67 | 19.19 | 4.50 | 19.19 | 10.33 | 27.94 | 10.17 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 16.82 | 2.00 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
February | 19.17 | 15.93 | 4.50 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
March | 14.67 | 16.12 | 3.17 | 15.80 | 0.33 | 16.02 | 0.33 | 16.23 |
April | 7.50 | 16.13 | 0.33 | 16.09 | 0.17 | 16.33 | 0.17 | 16.57 |
May | 0.83 | 18.57 | 0.00 | 18.57 | 0.33 | 21.08 | 0.33 | 22.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.54 | 3.50 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.45 | 3.67 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.61 | 1.83 | 28.66 |
September | 0.17 | 19.17 | 0.00 | 19.17 | 3.83 | 27.85 | 2.83 | 27.99 |
October | 5.17 | 16.02 | 0.33 | 15.96 | 1.00 | 17.80 | 1.00 | 19.15 |
November | 6.83 | 17.61 | 0.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
December | 26.67 | 15.62 | 4.00 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 91.33 | 16.15 | 14.50 | 15.96 | 22.00 | 18.10 | 13.67 | 19.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 | 0.00 | 15.51 |
Maximum of Months | 26.67 | 19.17 | 4.50 | 19.17 | 6.83 | 28.61 | 3.67 | 28.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 28.33 | 60.33 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.67 | 28.33 | 60.33 | 28.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 | 28.33 | 60.33 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 28.26 | 41.50 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 42.67 | 28.26 | 41.50 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 | 28.26 | 41.50 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 28.22 | 34.83 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.83 | 28.22 | 34.83 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 28.22 | 34.83 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 665.83 | 28.41 | 442.67 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.19 | 0.00 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.64 | 514.00 | 31.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 667.83 | 28.26 | 425.83 | 28.26 |
Annual Sum or Average | 0.00 | 0.00 | 2077.67 | 29.52 | 1382.50 | 29.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.64 | 514.00 | 31.75 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 148.50 | 23.96 | 79.50 | 24.75 | 0.00 | 24.75 |
February | 214.33 | 23.99 | 53.67 | 24.47 | 0.00 | 24.47 |
March | 216.83 | 23.99 | 68.50 | 24.43 | 0.00 | 24.43 |
April | 67.83 | 24.01 | 100.83 | 25.21 | 0.00 | 25.21 |
May | 63.50 | 24.00 | 165.83 | 25.01 | 0.00 | 25.01 |
June | 37.00 | 24.40 | 296.83 | 24.73 | 34.33 | 24.70 |
July | 89.50 | 24.62 | 352.67 | 24.80 | 79.17 | 24.79 |
August | 41.17 | 25.15 | 345.83 | 24.77 | 40.00 | 24.81 |
September | 17.50 | 24.00 | 189.00 | 25.30 | 0.00 | 25.30 |
October | 75.83 | 24.00 | 119.17 | 25.40 | 0.00 | 25.40 |
November | 47.67 | 23.99 | 105.17 | 25.70 | 0.00 | 25.70 |
December | 206.00 | 23.91 | 75.50 | 24.60 | 0.00 | 24.60 |
Annual Sum or Average | 1225.67 | 24.07 | 1952.50 | 24.86 | 153.50 | 24.85 |
Minimum of Months | 17.50 | 23.91 | 53.67 | 24.43 | 0.00 | 24.43 |
Maximum of Months | 216.83 | 25.15 | 352.67 | 25.70 | 79.17 | 25.70 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 214.83 | 23.93 | 31.33 | 24.14 | 0.00 | 24.14 |
February | 243.67 | 23.97 | 31.17 | 24.19 | 0.00 | 24.19 |
March | 179.00 | 23.97 | 34.50 | 24.20 | 0.00 | 24.20 |
April | 64.00 | 24.00 | 95.17 | 24.97 | 0.00 | 24.97 |
May | 51.50 | 23.99 | 160.67 | 24.69 | 0.00 | 24.69 |
June | 41.17 | 24.33 | 297.33 | 24.39 | 40.00 | 24.38 |
July | 86.33 | 24.40 | 349.50 | 24.39 | 80.00 | 24.40 |
August | 24.83 | 24.18 | 360.83 | 24.29 | 24.83 | 24.28 |
September | 34.83 | 23.99 | 158.67 | 24.72 | 0.00 | 24.72 |
October | 106.50 | 23.98 | 95.33 | 24.69 | 0.00 | 24.69 |
November | 88.00 | 23.98 | 75.00 | 24.79 | 0.00 | 24.79 |
December | 231.83 | 24.02 | 36.33 | 24.29 | 0.00 | 24.29 |
Annual Sum or Average | 1366.50 | 24.02 | 1725.83 | 24.43 | 144.83 | 24.43 |
Minimum of Months | 24.83 | 23.93 | 31.17 | 24.14 | 0.00 | 24.14 |
Maximum of Months | 243.67 | 24.40 | 360.83 | 24.97 | 80.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.33 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
February | 405.17 | 23.29 | 5.83 | 23.26 | 5.83 | 23.23 |
March | 457.33 | 23.54 | 8.50 | 23.54 | 0.83 | 23.54 |
April | 329.83 | 23.65 | 12.83 | 23.69 | 0.00 | 23.69 |
May | 146.17 | 23.87 | 110.17 | 24.27 | 0.00 | 24.27 |
June | 56.17 | 24.13 | 244.83 | 24.30 | 40.83 | 24.29 |
July | 106.17 | 24.21 | 279.00 | 24.31 | 85.67 | 24.30 |
August | 41.00 | 24.10 | 284.17 | 24.34 | 30.83 | 24.32 |
September | 95.67 | 23.88 | 112.00 | 24.38 | 0.00 | 24.38 |
October | 314.33 | 23.75 | 8.00 | 23.79 | 0.00 | 23.79 |
November | 380.00 | 23.63 | 1.67 | 23.64 | 0.00 | 23.64 |
December | 494.50 | 23.09 | 32.00 | 22.92 | 32.00 | 22.76 |
Annual Sum or Average | 3267.67 | 23.53 | 1099.00 | 23.73 | 196.00 | 23.72 |
Minimum of Months | 41.00 | 23.09 | 0.00 | 22.92 | 0.00 | 22.76 |
Maximum of Months | 494.50 | 24.21 | 284.17 | 24.38 | 85.67 | 24.38 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 21.68 | 149.17 | 21.25 | 149.17 | 20.99 |
February | 449.67 | 21.89 | 129.67 | 21.51 | 129.67 | 21.27 |
March | 492.83 | 22.50 | 66.17 | 22.16 | 66.17 | 21.90 |
April | 402.00 | 22.35 | 79.50 | 21.97 | 74.33 | 21.68 |
May | 232.67 | 23.41 | 64.83 | 23.58 | 3.50 | 23.55 |
June | 58.67 | 24.08 | 270.00 | 24.28 | 37.17 | 24.28 |
July | 96.00 | 24.20 | 313.50 | 24.31 | 85.33 | 24.30 |
August | 50.83 | 24.01 | 286.83 | 24.29 | 32.00 | 24.27 |
September | 150.50 | 23.49 | 104.33 | 23.97 | 0.00 | 23.97 |
October | 450.83 | 22.75 | 48.17 | 22.54 | 48.17 | 22.37 |
November | 474.50 | 22.20 | 77.50 | 22.00 | 77.50 | 21.84 |
December | 497.00 | 21.43 | 204.33 | 21.03 | 204.33 | 20.81 |
Annual Sum or Average | 3851.17 | 22.34 | 1794.00 | 22.42 | 907.33 | 22.19 |
Minimum of Months | 50.83 | 21.43 | 48.17 | 21.03 | 0.00 | 20.81 |
Maximum of Months | 497.00 | 24.20 | 313.50 | 24.31 | 204.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.17 | 72.33 | 21.99 | 72.33 | 21.86 |
February | 453.17 | 22.13 | 66.67 | 21.93 | 66.67 | 21.77 |
March | 491.00 | 22.85 | 18.67 | 22.75 | 18.67 | 22.65 |
April | 366.17 | 23.12 | 7.00 | 23.13 | 0.00 | 23.13 |
May | 173.67 | 23.56 | 114.00 | 23.97 | 0.00 | 23.97 |
June | 33.50 | 24.39 | 363.50 | 24.37 | 32.67 | 24.38 |
July | 73.33 | 24.48 | 411.17 | 24.44 | 73.33 | 24.44 |
August | 28.00 | 24.10 | 366.17 | 24.25 | 23.50 | 24.24 |
September | 136.17 | 23.52 | 127.33 | 24.09 | 0.00 | 24.09 |
October | 417.83 | 22.99 | 13.83 | 22.93 | 13.83 | 22.86 |
November | 475.50 | 22.71 | 16.83 | 22.65 | 16.83 | 22.59 |
December | 497.00 | 22.24 | 101.17 | 21.97 | 101.17 | 21.78 |
Annual Sum or Average | 3647.33 | 22.72 | 1678.67 | 23.05 | 419.00 | 22.96 |
Minimum of Months | 28.00 | 22.13 | 7.00 | 21.93 | 0.00 | 21.77 |
Maximum of Months | 502.00 | 24.48 | 411.17 | 24.44 | 101.17 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.00 | 21.93 | 52.83 | 21.85 | 48.83 | 21.76 |
February | 392.83 | 21.84 | 90.50 | 21.74 | 75.50 | 21.59 |
March | 393.67 | 22.19 | 52.50 | 22.24 | 23.50 | 22.14 |
April | 326.00 | 22.31 | 58.67 | 22.52 | 9.33 | 22.49 |
May | 166.00 | 23.05 | 179.33 | 23.80 | 1.17 | 23.81 |
June | 51.67 | 24.39 | 386.67 | 24.30 | 38.00 | 24.35 |
July | 105.83 | 24.59 | 406.33 | 24.43 | 91.33 | 24.49 |
August | 90.17 | 23.69 | 346.00 | 24.06 | 34.83 | 24.11 |
September | 139.00 | 23.24 | 209.83 | 24.01 | 8.17 | 24.08 |
October | 376.67 | 22.42 | 63.50 | 22.62 | 23.17 | 22.59 |
November | 432.33 | 22.14 | 37.17 | 22.16 | 24.00 | 22.10 |
December | 474.67 | 21.73 | 108.83 | 21.55 | 106.50 | 21.41 |
Annual Sum or Average | 3411.83 | 22.31 | 1992.17 | 22.86 | 484.33 | 22.81 |
Minimum of Months | 51.67 | 21.73 | 37.17 | 21.55 | 1.17 | 21.41 |
Maximum of Months | 474.67 | 24.59 | 406.33 | 24.43 | 106.50 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.67 | 22.37 | 147.83 | 22.85 | 39.33 | 22.76 |
February | 269.50 | 22.05 | 162.17 | 22.36 | 71.50 | 22.14 |
March | 316.00 | 22.29 | 101.33 | 22.53 | 31.83 | 22.40 |
April | 301.00 | 22.32 | 79.67 | 22.42 | 31.83 | 22.28 |
May | 189.50 | 23.07 | 143.00 | 23.66 | 0.00 | 23.66 |
June | 56.33 | 24.00 | 343.33 | 24.28 | 33.00 | 24.29 |
July | 94.33 | 24.48 | 393.67 | 24.42 | 79.17 | 24.45 |
August | 56.67 | 24.73 | 410.17 | 24.33 | 41.33 | 24.40 |
September | 101.67 | 23.95 | 269.17 | 24.45 | 21.33 | 24.60 |
October | 274.00 | 22.77 | 171.83 | 23.30 | 48.33 | 23.33 |
November | 267.50 | 22.70 | 164.83 | 23.33 | 36.33 | 23.34 |
December | 338.17 | 22.32 | 152.50 | 22.51 | 78.00 | 22.35 |
Annual Sum or Average | 2567.33 | 22.67 | 2539.50 | 23.36 | 512.00 | 23.32 |
Minimum of Months | 56.33 | 22.05 | 79.67 | 22.36 | 0.00 | 22.14 |
Maximum of Months | 338.17 | 24.73 | 410.17 | 24.45 | 79.17 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 423.00 | 22.13 | 44.67 | 22.19 | 21.83 | 22.14 |
February | 346.00 | 22.24 | 53.67 | 22.48 | 10.50 | 22.45 |
March | 275.17 | 22.78 | 96.83 | 23.25 | 10.00 | 23.26 |
April | 123.67 | 23.20 | 203.67 | 24.11 | 3.17 | 24.14 |
May | 136.67 | 23.02 | 236.17 | 24.07 | 2.50 | 24.09 |
June | 54.83 | 25.49 | 448.17 | 24.55 | 52.67 | 24.65 |
July | 93.67 | 25.28 | 481.33 | 24.63 | 93.67 | 24.72 |
August | 58.83 | 25.90 | 505.67 | 24.58 | 58.83 | 24.71 |
September | 108.00 | 23.47 | 261.17 | 24.32 | 13.50 | 24.42 |
October | 273.00 | 22.77 | 103.50 | 23.35 | 8.50 | 23.43 |
November | 285.00 | 22.71 | 86.17 | 23.19 | 2.83 | 23.20 |
December | 320.17 | 22.72 | 80.00 | 22.94 | 28.33 | 22.85 |
Annual Sum or Average | 2498.00 | 22.87 | 2601.00 | 23.70 | 306.33 | 23.76 |
Minimum of Months | 54.83 | 22.13 | 44.67 | 22.19 | 2.50 | 22.14 |
Maximum of Months | 423.00 | 25.90 | 505.67 | 24.63 | 93.67 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 238.67 | 20.60 | 238.67 | 20.47 |
February | 454.00 | 20.77 | 264.17 | 20.57 | 264.17 | 20.48 |
March | 512.67 | 21.58 | 146.67 | 21.24 | 146.67 | 21.02 |
April | 457.67 | 21.77 | 104.67 | 21.44 | 101.33 | 21.20 |
May | 284.50 | 23.14 | 66.17 | 23.34 | 3.00 | 23.32 |
June | 47.83 | 24.07 | 323.67 | 24.29 | 33.00 | 24.28 |
July | 84.17 | 24.15 | 354.67 | 24.35 | 77.33 | 24.32 |
August | 67.83 | 23.64 | 263.33 | 24.14 | 24.50 | 24.13 |
September | 208.67 | 23.15 | 89.50 | 23.58 | 0.17 | 23.58 |
October | 494.67 | 22.01 | 83.17 | 21.77 | 83.17 | 21.59 |
November | 489.00 | 21.25 | 208.50 | 21.04 | 208.50 | 20.93 |
December | 497.00 | 20.47 | 355.00 | 20.31 | 355.00 | 20.24 |
Annual Sum or Average | 4100.00 | 21.60 | 2498.17 | 21.76 | 1535.50 | 21.53 |
Minimum of Months | 47.83 | 20.47 | 66.17 | 20.31 | 0.17 | 20.24 |
Maximum of Months | 512.67 | 24.15 | 355.00 | 24.35 | 355.00 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.67 | 21.03 | 168.83 | 20.82 | 168.83 | 20.71 |
February | 365.33 | 20.98 | 166.17 | 20.72 | 163.33 | 20.57 |
March | 373.67 | 21.44 | 113.50 | 21.21 | 102.17 | 20.99 |
April | 329.50 | 21.40 | 113.00 | 21.30 | 83.67 | 21.06 |
May | 209.33 | 22.65 | 126.50 | 23.36 | 3.83 | 23.35 |
June | 59.67 | 24.23 | 309.67 | 24.37 | 34.83 | 24.43 |
July | 115.50 | 24.56 | 336.17 | 24.54 | 93.17 | 24.61 |
August | 97.67 | 23.83 | 282.50 | 24.26 | 39.83 | 24.34 |
September | 167.83 | 22.90 | 147.33 | 23.71 | 7.50 | 23.78 |
October | 355.50 | 21.68 | 92.33 | 21.67 | 67.83 | 21.49 |
November | 400.83 | 21.31 | 122.17 | 21.16 | 120.50 | 21.05 |
December | 422.00 | 20.59 | 261.67 | 20.38 | 261.67 | 20.28 |
Annual Sum or Average | 3317.50 | 21.61 | 2239.83 | 22.02 | 1147.17 | 21.83 |
Minimum of Months | 59.67 | 20.59 | 92.33 | 20.38 | 3.83 | 20.28 |
Maximum of Months | 422.00 | 24.56 | 336.17 | 24.54 | 261.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.33 | 22.09 | 180.17 | 22.56 | 74.33 | 22.43 |
February | 287.17 | 21.61 | 202.83 | 21.90 | 110.17 | 21.63 |
March | 345.50 | 21.78 | 158.50 | 21.89 | 89.17 | 21.65 |
April | 356.67 | 21.58 | 117.33 | 21.47 | 82.50 | 21.22 |
May | 245.17 | 22.81 | 116.67 | 23.31 | 3.50 | 23.29 |
June | 88.00 | 23.59 | 316.17 | 24.15 | 33.67 | 24.16 |
July | 115.67 | 24.04 | 360.83 | 24.31 | 80.17 | 24.32 |
August | 80.00 | 24.03 | 369.83 | 24.32 | 37.83 | 24.38 |
September | 129.67 | 23.75 | 254.67 | 24.34 | 25.17 | 24.51 |
October | 303.83 | 22.42 | 205.17 | 22.86 | 85.67 | 22.77 |
November | 293.83 | 22.28 | 189.83 | 22.90 | 65.67 | 22.83 |
December | 373.83 | 21.63 | 232.50 | 21.67 | 169.83 | 21.45 |
Annual Sum or Average | 2933.67 | 22.25 | 2704.50 | 22.88 | 857.67 | 22.73 |
Minimum of Months | 80.00 | 21.58 | 116.67 | 21.47 | 3.50 | 21.22 |
Maximum of Months | 373.83 | 24.04 | 369.83 | 24.34 | 169.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.67 | 21.15 | 157.17 | 20.95 | 156.83 | 20.83 |
February | 419.67 | 21.06 | 176.33 | 20.85 | 171.00 | 20.72 |
March | 442.83 | 21.41 | 118.17 | 21.29 | 94.50 | 21.09 |
April | 403.17 | 21.51 | 110.33 | 21.44 | 76.50 | 21.24 |
May | 271.00 | 22.50 | 132.83 | 23.16 | 1.83 | 23.16 |
June | 111.67 | 23.72 | 356.33 | 24.20 | 49.17 | 24.26 |
July | 129.00 | 23.74 | 378.50 | 24.16 | 83.83 | 24.16 |
August | 96.67 | 23.34 | 344.00 | 24.12 | 31.17 | 24.14 |
September | 226.67 | 22.80 | 165.00 | 23.55 | 9.67 | 23.61 |
October | 422.67 | 21.73 | 104.50 | 21.79 | 66.33 | 21.66 |
November | 453.17 | 21.42 | 109.67 | 21.31 | 105.67 | 21.21 |
December | 487.50 | 20.82 | 267.00 | 20.59 | 267.00 | 20.49 |
Annual Sum or Average | 3939.67 | 21.66 | 2419.83 | 22.08 | 1113.50 | 21.91 |
Minimum of Months | 96.67 | 20.82 | 104.50 | 20.59 | 1.83 | 20.49 |
Maximum of Months | 487.50 | 23.74 | 378.50 | 24.20 | 267.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 382.67 | 19.98 | 382.67 | 19.92 |
February | 454.00 | 20.25 | 367.83 | 20.15 | 367.83 | 20.11 |
March | 514.00 | 21.02 | 269.33 | 20.70 | 269.33 | 20.54 |
April | 462.33 | 21.00 | 199.50 | 20.56 | 196.83 | 20.32 |
May | 337.50 | 22.51 | 69.17 | 22.61 | 22.67 | 22.52 |
June | 71.83 | 23.65 | 319.67 | 24.16 | 30.17 | 24.16 |
July | 117.67 | 23.94 | 359.00 | 24.25 | 81.50 | 24.24 |
August | 103.67 | 23.22 | 259.33 | 23.93 | 25.17 | 23.92 |
September | 252.33 | 22.68 | 96.17 | 22.98 | 18.00 | 22.86 |
October | 498.83 | 21.21 | 196.50 | 20.89 | 196.50 | 20.71 |
November | 489.00 | 20.48 | 332.17 | 20.28 | 332.17 | 20.19 |
December | 497.00 | 19.97 | 453.83 | 19.91 | 453.83 | 19.89 |
Annual Sum or Average | 4300.17 | 21.07 | 3305.17 | 21.18 | 2376.67 | 20.93 |
Minimum of Months | 71.83 | 19.97 | 69.17 | 19.91 | 18.00 | 19.89 |
Maximum of Months | 514.00 | 23.94 | 453.83 | 24.25 | 453.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 300.83 | 20.18 | 300.83 | 20.07 |
February | 450.67 | 20.72 | 250.83 | 20.43 | 250.83 | 20.29 |
March | 449.33 | 21.24 | 190.33 | 20.89 | 185.50 | 20.68 |
April | 386.17 | 20.88 | 182.00 | 20.57 | 156.67 | 20.28 |
May | 251.83 | 22.36 | 151.00 | 23.00 | 12.50 | 22.93 |
June | 63.33 | 24.22 | 390.67 | 24.31 | 38.67 | 24.37 |
July | 135.00 | 24.50 | 418.17 | 24.45 | 107.83 | 24.53 |
August | 100.33 | 23.78 | 375.50 | 24.19 | 42.50 | 24.27 |
September | 183.50 | 22.68 | 189.67 | 23.50 | 14.17 | 23.48 |
October | 443.67 | 21.46 | 152.83 | 21.21 | 142.00 | 20.99 |
November | 486.33 | 20.87 | 247.83 | 20.61 | 247.83 | 20.48 |
December | 497.00 | 20.18 | 380.50 | 20.03 | 380.50 | 19.97 |
Annual Sum or Average | 3949.17 | 21.25 | 3230.17 | 21.60 | 1879.83 | 21.35 |
Minimum of Months | 63.33 | 20.18 | 151.00 | 20.03 | 12.50 | 19.97 |
Maximum of Months | 502.00 | 24.50 | 418.17 | 24.45 | 380.50 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.17 | 21.19 | 241.67 | 21.23 | 173.83 | 20.98 |
February | 323.00 | 21.06 | 232.33 | 21.14 | 166.67 | 20.88 |
March | 375.17 | 21.33 | 220.33 | 21.28 | 168.00 | 21.04 |
April | 375.83 | 20.89 | 185.67 | 20.61 | 155.17 | 20.31 |
May | 297.67 | 22.34 | 119.50 | 22.75 | 20.33 | 22.67 |
June | 112.50 | 23.28 | 314.83 | 24.01 | 32.83 | 24.03 |
July | 140.33 | 23.79 | 360.17 | 24.20 | 84.17 | 24.23 |
August | 109.00 | 23.60 | 359.17 | 24.17 | 39.00 | 24.23 |
September | 165.67 | 23.22 | 242.00 | 23.94 | 31.33 | 24.03 |
October | 332.67 | 21.73 | 246.00 | 22.02 | 142.50 | 21.82 |
November | 330.00 | 21.51 | 235.50 | 21.77 | 143.67 | 21.53 |
December | 401.00 | 20.85 | 278.83 | 20.73 | 240.83 | 20.52 |
Annual Sum or Average | 3323.00 | 21.67 | 3036.00 | 22.15 | 1398.33 | 21.89 |
Minimum of Months | 109.00 | 20.85 | 119.50 | 20.61 | 20.33 | 20.31 |
Maximum of Months | 401.00 | 23.79 | 360.17 | 24.20 | 240.83 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.33 | 20.59 | 288.33 | 20.35 | 288.33 | 20.24 |
February | 428.83 | 20.70 | 261.33 | 20.49 | 258.00 | 20.38 |
March | 451.67 | 21.05 | 207.50 | 20.90 | 184.83 | 20.73 |
April | 411.67 | 20.91 | 172.00 | 20.69 | 142.33 | 20.42 |
May | 316.17 | 22.17 | 128.83 | 22.73 | 14.33 | 22.68 |
June | 127.00 | 23.38 | 341.83 | 24.07 | 45.67 | 24.12 |
July | 157.83 | 23.50 | 366.83 | 24.03 | 87.67 | 24.05 |
August | 136.17 | 23.05 | 333.17 | 23.94 | 32.67 | 23.97 |
September | 254.00 | 22.50 | 160.17 | 23.22 | 17.00 | 23.25 |
October | 432.33 | 21.23 | 177.83 | 21.16 | 146.00 | 20.98 |
November | 462.33 | 20.94 | 229.83 | 20.72 | 229.33 | 20.61 |
December | 491.33 | 20.39 | 354.67 | 20.19 | 354.67 | 20.11 |
Annual Sum or Average | 4157.67 | 21.28 | 3022.33 | 21.59 | 1800.83 | 21.36 |
Minimum of Months | 127.00 | 20.39 | 128.83 | 20.19 | 14.33 | 20.11 |
Maximum of Months | 491.33 | 23.50 | 366.83 | 24.07 | 354.67 | 24.12 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 7.33 | 27.00 | 454.00 | 27.00 | 7.33 | 27.00 |
March | 14.83 | 27.00 | 514.00 | 27.00 | 14.83 | 27.00 |
April | 36.33 | 27.00 | 485.00 | 27.00 | 36.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 28.50 | 27.00 | 496.00 | 27.00 | 28.50 | 27.00 |
July | 90.33 | 27.00 | 497.00 | 27.00 | 90.33 | 27.00 |
August | 323.17 | 27.29 | 514.00 | 27.23 | 323.17 | 27.25 |
September | 4.33 | 27.00 | 485.00 | 27.00 | 4.33 | 27.00 |
October | 13.67 | 27.00 | 502.00 | 27.00 | 13.67 | 27.00 |
November | 18.50 | 27.00 | 489.00 | 27.00 | 18.50 | 27.00 |
December | 16.33 | 27.01 | 497.00 | 27.00 | 16.33 | 27.00 |
Annual Sum or Average | 553.33 | 27.17 | 5943.00 | 27.03 | 553.33 | 27.04 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 323.17 | 27.29 | 514.00 | 27.23 | 323.17 | 27.25 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 446.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 406.83 | 27.00 | 0.00 | 27.00 |
March | 1.00 | 27.00 | 490.17 | 27.00 | 1.00 | 27.00 |
April | 2.00 | 27.00 | 470.67 | 27.00 | 2.00 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 5.50 | 27.00 | 496.00 | 27.00 | 5.50 | 27.00 |
July | 1.50 | 27.00 | 497.00 | 27.00 | 1.50 | 27.00 |
August | 58.17 | 27.93 | 514.00 | 27.20 | 58.17 | 27.26 |
September | 2.67 | 27.00 | 485.00 | 27.00 | 2.67 | 27.00 |
October | 1.83 | 27.00 | 497.33 | 27.00 | 1.83 | 27.00 |
November | 0.00 | 0.00 | 484.83 | 27.00 | 0.00 | 27.00 |
December | 11.50 | 27.00 | 415.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 84.17 | 27.64 | 5711.83 | 27.02 | 72.67 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 406.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 58.17 | 27.93 | 514.00 | 27.20 | 58.17 | 27.26 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.00 | 24.97 | 314.00 | 26.45 | 5.17 | 26.41 |
February | 25.50 | 27.00 | 284.17 | 27.00 | 0.00 | 27.00 |
March | 21.83 | 27.00 | 438.67 | 27.00 | 1.33 | 27.00 |
April | 19.00 | 27.00 | 417.50 | 27.00 | 3.50 | 27.00 |
May | 2.00 | 25.84 | 500.50 | 27.00 | 0.00 | 27.00 |
June | 18.17 | 27.00 | 496.00 | 27.00 | 18.17 | 27.00 |
July | 17.83 | 27.00 | 497.00 | 27.00 | 17.83 | 27.00 |
August | 74.83 | 27.63 | 514.00 | 27.16 | 74.83 | 27.22 |
September | 3.83 | 27.00 | 483.83 | 27.00 | 3.83 | 27.00 |
October | 5.00 | 27.00 | 423.00 | 27.00 | 1.50 | 27.00 |
November | 0.50 | 27.00 | 399.00 | 27.00 | 0.00 | 27.00 |
December | 42.00 | 27.00 | 272.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 331.50 | 26.52 | 5040.00 | 26.98 | 126.17 | 26.98 |
Minimum of Months | 0.50 | 24.97 | 272.33 | 26.45 | 0.00 | 26.41 |
Maximum of Months | 101.00 | 27.63 | 514.00 | 27.16 | 74.83 | 27.22 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.83 | 27.00 | 502.00 | 27.00 | 478.83 | 27.00 |
February | 454.00 | 27.02 | 454.00 | 27.02 | 454.00 | 27.02 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 28.39 | 485.00 | 28.39 | 485.00 | 28.39 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 31.92 | 514.00 | 31.92 | 514.00 | 31.92 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.02 | 502.00 | 27.02 | 502.00 | 27.02 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 28.10 | 497.00 | 28.10 | 497.00 | 28.10 |
Annual Sum or Average | 5919.83 | 27.64 | 5943.00 | 27.64 | 5919.83 | 27.64 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 31.92 | 514.00 | 31.92 | 514.00 | 31.92 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00006 | 18.43277 | 0.73020 | 16.35916 |
February | 454.00000 | 27.00002 | 17.23553 | 0.75711 | 17.22258 |
March | 514.00000 | 27.00005 | 17.51298 | 0.81808 | 19.21215 |
April | 485.00000 | 27.00035 | 19.56880 | 0.88895 | 21.77071 |
May | 508.00000 | 27.00041 | 22.02332 | 0.15325 | 5.59328 |
June | 496.00000 | 27.00055 | 24.16173 | 0.26278 | 6.52392 |
July | 497.00000 | 27.00038 | 24.76223 | 0.30712 | 7.03447 |
August | 514.00000 | 27.18598 | 24.53462 | 0.43875 | 9.48484 |
September | 485.00000 | 27.00030 | 21.99981 | 0.17656 | 5.79119 |
October | 502.00000 | 27.00010 | 19.03449 | 0.81004 | 18.94647 |
November | 489.00000 | 27.00005 | 19.79442 | 0.83375 | 19.76900 |
December | 497.00000 | 27.00017 | 14.65101 | 0.80884 | 18.95324 |
Annual Sum or Average | 5943.00000 | 27.01629 | 20.33429 | 0.58055 | 13.85166 |
Minimum of Months | 454.00000 | 27.00002 | 14.65101 | 0.15325 | 5.59328 |
Maximum of Months | 514.00000 | 27.18598 | 24.76223 | 0.88895 | 21.77071 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99976 | 18.44757 | 0.63801 | 13.74290 |
February | 454.00000 | 27.00002 | 17.22012 | 0.63608 | 13.73174 |
March | 514.00000 | 27.00004 | 17.49917 | 0.68745 | 15.12445 |
April | 485.00000 | 27.00006 | 19.55678 | 0.72635 | 16.30076 |
May | 508.00000 | 27.00036 | 22.06088 | 0.07037 | 5.27501 |
June | 496.00000 | 27.00054 | 24.17869 | 0.18156 | 5.81504 |
July | 497.00000 | 27.00040 | 24.77292 | 0.20128 | 5.94937 |
August | 514.00000 | 27.11334 | 24.60723 | 0.25290 | 6.72266 |
September | 485.00000 | 27.00028 | 22.02651 | 0.09954 | 5.40238 |
October | 502.00000 | 27.00010 | 19.01966 | 0.70925 | 15.75547 |
November | 489.00000 | 27.00005 | 19.78163 | 0.69666 | 15.35042 |
December | 497.00000 | 26.99999 | 14.63687 | 0.61330 | 13.14842 |
Annual Sum or Average | 5943.00000 | 27.00994 | 20.34268 | 0.45773 | 10.99777 |
Minimum of Months | 454.00000 | 26.99976 | 14.63687 | 0.07037 | 5.27501 |
Maximum of Months | 514.00000 | 27.11334 | 24.77292 | 0.72635 | 16.30076 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.56155 | 19.02119 | 0.46329 | 11.22008 |
February | 454.00000 | 27.00002 | 17.23628 | 0.55844 | 11.93861 |
March | 514.00000 | 27.00005 | 17.51985 | 0.62796 | 13.66501 |
April | 485.00000 | 27.00006 | 19.57277 | 0.66488 | 14.77554 |
May | 508.00000 | 26.99488 | 22.10373 | 0.03300 | 5.44202 |
June | 496.00000 | 27.00056 | 24.18798 | 0.19431 | 6.02483 |
July | 497.00000 | 27.00041 | 24.78284 | 0.21237 | 6.14027 |
August | 514.00000 | 27.09565 | 24.63347 | 0.25523 | 6.85163 |
September | 485.00000 | 27.00019 | 22.04588 | 0.08143 | 5.51896 |
October | 502.00000 | 27.00014 | 19.05655 | 0.64394 | 14.07339 |
November | 489.00000 | 27.00005 | 19.80332 | 0.61273 | 13.16457 |
December | 497.00000 | 26.99999 | 14.64445 | 0.52607 | 11.19761 |
Annual Sum or Average | 5943.00000 | 26.97092 | 20.41011 | 0.40469 | 9.98033 |
Minimum of Months | 454.00000 | 26.56155 | 14.64445 | 0.03300 | 5.44202 |
Maximum of Months | 514.00000 | 27.09565 | 24.78284 | 0.66488 | 14.77554 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00011 | 29.99978 | 1.04597 | 28.11015 |
February | 454.00000 | 27.01542 | 29.99819 | 1.20371 | 35.44308 |
March | 514.00000 | 27.01000 | 29.99878 | 1.35703 | 43.24469 |
April | 485.00000 | 28.38680 | 29.98813 | 1.79350 | 66.33560 |
May | 508.00000 | 27.00130 | 30.00325 | 0.48699 | 10.00671 |
June | 496.00000 | 27.01062 | 30.00253 | 0.73110 | 16.26726 |
July | 497.00000 | 27.00523 | 30.00413 | 0.92880 | 23.23463 |
August | 514.00000 | 31.91562 | 29.86084 | 2.58736 | 93.00155 |
September | 485.00000 | 27.00319 | 30.00122 | 0.55476 | 11.53577 |
October | 502.00000 | 27.01542 | 30.00059 | 1.25285 | 37.87759 |
November | 489.00000 | 27.00971 | 29.99972 | 1.38587 | 44.76496 |
December | 497.00000 | 28.10118 | 30.01987 | 1.74148 | 63.81562 |
Annual Sum or Average | 5943.00000 | 27.63626 | 29.98936 | 1.25890 | 39.59636 |
Minimum of Months | 454.00000 | 27.00011 | 29.86084 | 0.48699 | 10.00671 |
Maximum of Months | 514.00000 | 31.91562 | 30.01987 | 2.58736 | 93.00155 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45668 | 17.20565 | 0.30989 | 7.44093 |
February | 454.00000 | 24.44875 | 15.94347 | 0.29672 | 7.27802 |
March | 514.00000 | 24.36016 | 15.87031 | 0.28625 | 6.99581 |
April | 485.00000 | 24.46377 | 19.80545 | 0.34062 | 7.86115 |
May | 508.00000 | 24.48350 | 24.33306 | -0.4756 | 10.71400 |
June | 496.00000 | 24.46380 | 33.86253 | -0.3968 | 9.27697 |
July | 497.00000 | 24.60975 | 36.39171 | -0.3364 | 8.53407 |
August | 514.00000 | 24.49185 | 34.47587 | -0.3647 | 8.88497 |
September | 485.00000 | 24.56337 | 24.33313 | -0.4264 | 10.04615 |
October | 502.00000 | 24.59047 | 18.19252 | 0.36813 | 8.55563 |
November | 489.00000 | 24.57589 | 18.74629 | 0.36677 | 8.47522 |
December | 497.00000 | 24.47066 | 12.56235 | 0.29182 | 7.32754 |
Annual Sum or Average | 5943.00000 | 24.49802 | 22.70696 | 0.01884 | 8.45599 |
Minimum of Months | 454.00000 | 24.36016 | 12.56235 | -0.4756 | 6.99581 |
Maximum of Months | 514.00000 | 24.60975 | 36.39171 | 0.36813 | 10.71400 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18437 | 18.65487 | 0.25394 | 6.56383 |
February | 454.00000 | 24.20358 | 17.05882 | 0.24898 | 6.56025 |
March | 514.00000 | 24.21657 | 16.85980 | 0.27149 | 6.69142 |
April | 485.00000 | 24.37983 | 20.89268 | 0.34362 | 7.83056 |
May | 508.00000 | 24.32513 | 25.23020 | -0.4997 | 10.78921 |
June | 496.00000 | 24.24550 | 34.22137 | -0.4258 | 9.22258 |
July | 497.00000 | 24.29210 | 36.75018 | -0.3880 | 8.58717 |
August | 514.00000 | 24.21852 | 35.23754 | -0.3967 | 8.62905 |
September | 485.00000 | 24.31992 | 25.27537 | -0.4816 | 10.47400 |
October | 502.00000 | 24.35031 | 19.11685 | 0.32083 | 7.46622 |
November | 489.00000 | 24.34079 | 19.64232 | 0.31885 | 7.40245 |
December | 497.00000 | 24.30246 | 13.40547 | 0.25825 | 6.68614 |
Annual Sum or Average | 5943.00000 | 24.28149 | 23.59058 | -0.0174 | 8.08343 |
Minimum of Months | 454.00000 | 24.18437 | 13.40547 | -0.4997 | 6.56025 |
Maximum of Months | 514.00000 | 24.37983 | 36.75018 | 0.34362 | 10.78921 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53386 | 19.95413 | 0.07151 | 5.77870 |
February | 454.00000 | 23.39388 | 18.36519 | 0.02364 | 5.90816 |
March | 514.00000 | 23.63790 | 17.95437 | 0.09599 | 5.81446 |
April | 485.00000 | 23.83059 | 22.48705 | 0.16974 | 6.02696 |
May | 508.00000 | 24.19753 | 25.79562 | -0.5757 | 12.39795 |
June | 496.00000 | 24.18572 | 34.42417 | -0.4797 | 10.16899 |
July | 497.00000 | 24.22087 | 36.86213 | -0.4521 | 9.64782 |
August | 514.00000 | 24.22192 | 35.02602 | -0.4638 | 9.86806 |
September | 485.00000 | 24.21643 | 25.51486 | -0.5488 | 11.82535 |
October | 502.00000 | 23.97633 | 20.07974 | 0.20127 | 6.19314 |
November | 489.00000 | 23.75414 | 21.15269 | 0.14011 | 5.77456 |
December | 497.00000 | 23.09712 | 15.07142 | -0.0728 | 6.63266 |
Annual Sum or Average | 5943.00000 | 23.85916 | 24.44571 | -0.1595 | 8.02095 |
Minimum of Months | 454.00000 | 23.09712 | 15.07142 | -0.5757 | 5.77456 |
Maximum of Months | 514.00000 | 24.22192 | 36.86213 | 0.20127 | 12.39795 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.70494 | 21.98435 | -0.3942 | 11.84549 |
February | 454.00000 | 21.91157 | 19.93605 | -0.3578 | 10.73514 |
March | 514.00000 | 22.56011 | 19.38245 | -0.1810 | 8.81706 |
April | 485.00000 | 22.64803 | 23.75658 | -0.1251 | 8.85380 |
May | 508.00000 | 23.83433 | 26.46823 | -0.7093 | 16.89037 |
June | 496.00000 | 24.18601 | 34.24348 | -0.4621 | 9.82752 |
July | 497.00000 | 24.24193 | 36.73604 | -0.4303 | 9.27220 |
August | 514.00000 | 24.20919 | 34.92896 | -0.4558 | 9.72170 |
September | 485.00000 | 24.02603 | 25.74546 | -0.6174 | 14.18069 |
October | 502.00000 | 22.87896 | 21.69478 | -0.0838 | 7.15615 |
November | 489.00000 | 22.24865 | 23.48498 | -0.2469 | 8.10459 |
December | 497.00000 | 21.43347 | 16.36071 | -0.5009 | 13.68922 |
Annual Sum or Average | 5943.00000 | 23.00011 | 25.44276 | -0.3808 | 10.75938 |
Minimum of Months | 454.00000 | 21.43347 | 16.36071 | -0.7093 | 7.15615 |
Maximum of Months | 514.00000 | 24.24193 | 36.73604 | -0.0838 | 16.89037 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.16517 | 19.92166 | -0.2518 | 7.59584 |
February | 454.00000 | 22.13220 | 18.00431 | -0.2681 | 8.07315 |
March | 514.00000 | 22.90414 | 17.37134 | -0.0703 | 6.51305 |
April | 485.00000 | 23.34200 | 21.13511 | 0.07148 | 6.10849 |
May | 508.00000 | 24.01759 | 25.08282 | -0.6088 | 13.74163 |
June | 496.00000 | 24.28119 | 33.34720 | -0.3722 | 8.41848 |
July | 497.00000 | 24.36622 | 35.92955 | -0.3250 | 7.89168 |
August | 514.00000 | 24.19707 | 34.62063 | -0.3911 | 8.66169 |
September | 485.00000 | 24.07900 | 24.98152 | -0.5685 | 13.02969 |
October | 502.00000 | 23.17821 | 19.96276 | 0.01370 | 6.13459 |
November | 489.00000 | 22.74349 | 20.95010 | -0.0966 | 6.20534 |
December | 497.00000 | 22.23624 | 14.03239 | -0.2712 | 8.39086 |
Annual Sum or Average | 5943.00000 | 23.31264 | 23.83381 | -0.2620 | 8.40028 |
Minimum of Months | 454.00000 | 22.13220 | 14.03239 | -0.6088 | 6.10849 |
Maximum of Months | 514.00000 | 24.36622 | 35.92955 | 0.07148 | 13.74163 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.11610 | 19.29854 | -0.2224 | 7.68664 |
February | 454.00000 | 22.16890 | 17.28248 | -0.2141 | 8.56912 |
March | 514.00000 | 22.64914 | 17.02638 | -0.0686 | 7.68829 |
April | 485.00000 | 22.88084 | 21.27865 | 0.02271 | 7.18213 |
May | 508.00000 | 23.85808 | 24.96818 | -0.5710 | 13.88636 |
June | 496.00000 | 24.18286 | 33.33248 | -0.3021 | 8.15653 |
July | 497.00000 | 24.26167 | 36.09796 | -0.2723 | 8.34625 |
August | 514.00000 | 23.94658 | 34.95896 | -0.3777 | 9.70699 |
September | 485.00000 | 23.95686 | 24.84650 | -0.5033 | 12.74900 |
October | 502.00000 | 22.88842 | 19.67075 | 0.00103 | 7.45800 |
November | 489.00000 | 22.38941 | 20.69498 | -0.1360 | 7.16455 |
December | 497.00000 | 21.84743 | 13.69829 | -0.3309 | 9.20928 |
Annual Sum or Average | 5943.00000 | 23.10326 | 23.65561 | -0.2485 | 8.99028 |
Minimum of Months | 454.00000 | 21.84743 | 13.69829 | -0.5710 | 7.16455 |
Maximum of Months | 514.00000 | 24.26167 | 36.09796 | 0.02271 | 13.88636 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15756 | 18.11385 | 0.06631 | 8.80100 |
February | 454.00000 | 22.96738 | 16.46163 | 0.01064 | 9.65161 |
March | 514.00000 | 23.03702 | 16.66625 | 0.03249 | 8.62745 |
April | 485.00000 | 22.99169 | 21.20312 | 0.03014 | 7.48202 |
May | 508.00000 | 23.80400 | 25.22017 | -0.6412 | 15.53881 |
June | 496.00000 | 24.18921 | 33.45760 | -0.3787 | 8.86156 |
July | 497.00000 | 24.30028 | 36.00511 | -0.3158 | 8.22901 |
August | 514.00000 | 24.20082 | 34.45367 | -0.3124 | 8.22510 |
September | 485.00000 | 24.23553 | 24.42113 | -0.4010 | 11.11239 |
October | 502.00000 | 23.46041 | 18.98550 | 0.16627 | 9.42369 |
November | 489.00000 | 23.46586 | 19.31933 | 0.16294 | 9.16659 |
December | 497.00000 | 22.96582 | 12.82405 | -0.0242 | 9.37607 |
Annual Sum or Average | 5943.00000 | 23.56911 | 23.15714 | -0.1355 | 9.54608 |
Minimum of Months | 454.00000 | 22.96582 | 12.82405 | -0.6412 | 7.48202 |
Maximum of Months | 514.00000 | 24.30028 | 36.00511 | 0.16627 | 15.53881 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.45555 | 18.67761 | -0.1078 | 6.99263 |
February | 454.00000 | 22.75008 | 16.52042 | -0.0348 | 7.32378 |
March | 514.00000 | 23.48253 | 15.99395 | 0.17394 | 7.39081 |
April | 485.00000 | 24.06731 | 19.63757 | 0.35789 | 8.77767 |
May | 508.00000 | 24.01656 | 24.70182 | -0.4809 | 12.06126 |
June | 496.00000 | 24.37998 | 32.92477 | -0.1763 | 7.30829 |
July | 497.00000 | 24.48147 | 35.50849 | -0.1239 | 6.78772 |
August | 514.00000 | 24.42083 | 33.80967 | -0.0714 | 6.56476 |
September | 485.00000 | 24.12945 | 24.56932 | -0.4102 | 11.19013 |
October | 502.00000 | 23.48131 | 18.84456 | 0.18570 | 7.76840 |
November | 489.00000 | 23.43059 | 19.23227 | 0.15909 | 7.19025 |
December | 497.00000 | 23.34211 | 12.33958 | 0.08096 | 7.34798 |
Annual Sum or Average | 5943.00000 | 23.70946 | 22.78985 | -0.0378 | 8.05756 |
Minimum of Months | 454.00000 | 22.45555 | 12.33958 | -0.4809 | 6.56476 |
Maximum of Months | 514.00000 | 24.48147 | 35.50849 | 0.35789 | 12.06126 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84891 | 21.18831 | -0.5986 | 14.49091 |
February | 454.00000 | 20.76681 | 19.09108 | -0.6354 | 15.52933 |
March | 514.00000 | 21.58919 | 18.76386 | -0.4103 | 11.30139 |
April | 485.00000 | 21.89298 | 23.16111 | -0.2941 | 9.87289 |
May | 508.00000 | 23.58304 | 26.00179 | -0.7768 | 19.50691 |
June | 496.00000 | 24.21126 | 33.34495 | -0.4241 | 9.21096 |
July | 497.00000 | 24.28892 | 35.94132 | -0.3847 | 8.74890 |
August | 514.00000 | 24.11497 | 34.65773 | -0.4771 | 10.29620 |
September | 485.00000 | 23.76292 | 25.46406 | -0.6985 | 17.27238 |
October | 502.00000 | 22.04257 | 21.43520 | -0.2750 | 8.61073 |
November | 489.00000 | 21.25425 | 22.62874 | -0.4812 | 11.16228 |
December | 497.00000 | 20.47472 | 15.19395 | -0.7449 | 18.95747 |
Annual Sum or Average | 5943.00000 | 22.41705 | 24.79117 | -0.5159 | 12.89257 |
Minimum of Months | 454.00000 | 20.47472 | 15.19395 | -0.7768 | 8.61073 |
Maximum of Months | 514.00000 | 24.28892 | 35.94132 | -0.2750 | 19.50691 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.07232 | 19.96343 | -0.5130 | 12.22621 |
February | 385.00000 | 21.15020 | 17.86378 | -0.5014 | 13.81746 |
March | 433.00000 | 21.82422 | 17.52074 | -0.3008 | 10.98898 |
April | 410.00000 | 21.94430 | 22.41053 | -0.2260 | 10.33816 |
May | 430.00000 | 23.50343 | 25.68832 | -0.7093 | 18.96963 |
June | 418.00000 | 24.21547 | 33.06029 | -0.3119 | 8.73690 |
July | 422.00000 | 24.34566 | 35.65343 | -0.2666 | 9.11036 |
August | 433.00000 | 24.10244 | 34.48160 | -0.3628 | 10.10334 |
September | 410.00000 | 23.73668 | 25.02003 | -0.6009 | 16.21312 |
October | 427.00000 | 22.13863 | 20.27499 | -0.2058 | 9.29345 |
November | 417.00000 | 21.42102 | 21.44787 | -0.4076 | 10.24755 |
December | 422.00000 | 20.58835 | 14.16388 | -0.6892 | 17.41643 |
Annual Sum or Average | 5034.00000 | 22.51343 | 24.00770 | -0.4241 | 12.27734 |
Minimum of Months | 385.00000 | 20.58835 | 14.16388 | -0.7093 | 8.73690 |
Maximum of Months | 433.00000 | 24.34566 | 35.65343 | -0.2058 | 18.96963 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.95017 | 18.10434 | 0.01328 | 10.09670 |
February | 454.00000 | 22.61600 | 16.57230 | -0.0843 | 11.90298 |
March | 514.00000 | 22.58740 | 17.10949 | -0.0892 | 10.54941 |
April | 485.00000 | 22.25062 | 22.17947 | -0.1594 | 9.83652 |
May | 508.00000 | 23.54000 | 25.74585 | -0.7404 | 19.22736 |
June | 496.00000 | 24.10338 | 33.48559 | -0.4287 | 9.86751 |
July | 497.00000 | 24.23211 | 35.96877 | -0.3649 | 9.10982 |
August | 514.00000 | 24.19756 | 34.22651 | -0.3571 | 9.20585 |
September | 485.00000 | 24.13217 | 24.47167 | -0.4397 | 12.58105 |
October | 502.00000 | 23.16151 | 19.25531 | 0.09033 | 10.60232 |
November | 489.00000 | 23.14807 | 19.50552 | 0.07746 | 10.25486 |
December | 497.00000 | 22.30378 | 13.11438 | -0.2061 | 12.22807 |
Annual Sum or Average | 5943.00000 | 23.27447 | 23.37391 | -0.2256 | 11.29109 |
Minimum of Months | 454.00000 | 22.25062 | 13.11438 | -0.7404 | 9.10982 |
Maximum of Months | 514.00000 | 24.23211 | 35.96877 | 0.09033 | 19.22736 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29611 | 19.77884 | -0.4390 | 11.28299 |
February | 454.00000 | 21.28683 | 17.78118 | -0.4516 | 12.59686 |
March | 514.00000 | 21.79110 | 17.71853 | -0.2913 | 10.46630 |
April | 485.00000 | 21.94688 | 22.40225 | -0.2151 | 9.55644 |
May | 508.00000 | 23.33240 | 25.85278 | -0.7550 | 20.67429 |
June | 496.00000 | 24.07523 | 33.53409 | -0.3508 | 9.80776 |
July | 497.00000 | 24.09011 | 36.31885 | -0.3527 | 9.35307 |
August | 514.00000 | 24.00993 | 34.71068 | -0.3896 | 10.19848 |
September | 485.00000 | 23.57258 | 25.34650 | -0.6442 | 17.62788 |
October | 502.00000 | 22.11950 | 20.42182 | -0.1858 | 8.87333 |
November | 489.00000 | 21.61180 | 21.29185 | -0.3393 | 9.34928 |
December | 497.00000 | 20.87770 | 14.07483 | -0.5982 | 15.31030 |
Annual Sum or Average | 5943.00000 | 22.51201 | 24.16013 | -0.4176 | 12.08821 |
Minimum of Months | 454.00000 | 20.87770 | 14.07483 | -0.7550 | 8.87333 |
Maximum of Months | 514.00000 | 24.09011 | 36.31885 | -0.1858 | 20.67429 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14037 | 21.94336 | -0.8345 | 22.60933 |
February | 454.00000 | 20.25366 | 19.63234 | -0.8207 | 21.59676 |
March | 514.00000 | 21.02120 | 19.08227 | -0.5878 | 15.65476 |
April | 485.00000 | 21.13546 | 24.16791 | -0.5029 | 15.46082 |
May | 508.00000 | 23.04433 | 26.77598 | -0.9610 | 27.49601 |
June | 496.00000 | 24.12483 | 33.42944 | -0.4360 | 9.79389 |
July | 497.00000 | 24.20514 | 36.13570 | -0.3966 | 9.40671 |
August | 514.00000 | 23.98249 | 34.96636 | -0.5070 | 11.44613 |
September | 485.00000 | 23.40743 | 25.83514 | -0.8157 | 22.34691 |
October | 502.00000 | 21.22901 | 22.21575 | -0.5035 | 13.31251 |
November | 489.00000 | 20.48301 | 23.40079 | -0.7201 | 18.42353 |
December | 497.00000 | 19.97348 | 15.45268 | -0.9362 | 26.16884 |
Annual Sum or Average | 5943.00000 | 21.93222 | 25.30356 | -0.6673 | 17.77220 |
Minimum of Months | 454.00000 | 19.97348 | 15.45268 | -0.9610 | 9.40671 |
Maximum of Months | 514.00000 | 24.20514 | 36.13570 | -0.3966 | 27.49601 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43294 | 21.01157 | -0.7162 | 18.88517 |
February | 454.00000 | 20.74760 | 18.58209 | -0.6454 | 17.56086 |
March | 514.00000 | 21.60435 | 17.96954 | -0.3900 | 13.30236 |
April | 485.00000 | 21.52555 | 23.20148 | -0.3501 | 14.45588 |
May | 508.00000 | 23.28734 | 25.88840 | -0.7833 | 21.92873 |
June | 496.00000 | 24.18433 | 33.02774 | -0.2833 | 8.30679 |
July | 497.00000 | 24.28817 | 35.81992 | -0.2484 | 8.87771 |
August | 514.00000 | 24.06661 | 34.33621 | -0.3364 | 9.68986 |
September | 485.00000 | 23.64075 | 25.02485 | -0.6194 | 17.07394 |
October | 502.00000 | 21.78464 | 20.89789 | -0.3275 | 11.70270 |
November | 489.00000 | 20.88205 | 22.28791 | -0.5841 | 14.74800 |
December | 497.00000 | 20.17598 | 14.81309 | -0.8451 | 22.98700 |
Annual Sum or Average | 5943.00000 | 22.23264 | 24.45671 | -0.5095 | 14.93290 |
Minimum of Months | 454.00000 | 20.17598 | 14.81309 | -0.8451 | 8.30679 |
Maximum of Months | 514.00000 | 24.28817 | 35.81992 | -0.2484 | 22.98700 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.04142 | 19.14225 | -0.2566 | 13.12268 |
February | 454.00000 | 21.97791 | 17.36659 | -0.2873 | 14.54477 |
March | 514.00000 | 22.09956 | 17.54603 | -0.2463 | 12.94914 |
April | 485.00000 | 21.60314 | 23.21600 | -0.3434 | 14.68326 |
May | 508.00000 | 23.10629 | 26.39526 | -0.8940 | 25.81894 |
June | 496.00000 | 23.98916 | 33.63935 | -0.4470 | 10.88301 |
July | 497.00000 | 24.12641 | 36.20683 | -0.3820 | 10.09551 |
August | 514.00000 | 24.07245 | 34.51477 | -0.3822 | 10.25976 |
September | 485.00000 | 23.89280 | 24.71245 | -0.5208 | 15.67625 |
October | 502.00000 | 22.57964 | 19.97820 | -0.0872 | 12.69598 |
November | 489.00000 | 22.44010 | 20.32394 | -0.1430 | 11.84285 |
December | 497.00000 | 21.50660 | 13.75561 | -0.4475 | 16.89528 |
Annual Sum or Average | 5943.00000 | 22.79406 | 23.95946 | -0.3707 | 14.12378 |
Minimum of Months | 454.00000 | 21.50660 | 13.75561 | -0.8940 | 10.09551 |
Maximum of Months | 514.00000 | 24.12641 | 36.20683 | -0.0872 | 25.81894 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67887 | 20.55204 | -0.6444 | 17.38021 |
February | 454.00000 | 20.88476 | 18.33646 | -0.6008 | 16.63216 |
March | 514.00000 | 21.42805 | 17.99924 | -0.4179 | 13.26120 |
April | 485.00000 | 21.39092 | 23.27832 | -0.3731 | 13.88545 |
May | 508.00000 | 22.95852 | 26.38147 | -0.8871 | 26.40933 |
June | 496.00000 | 23.95753 | 33.68816 | -0.3686 | 10.84413 |
July | 497.00000 | 23.97552 | 36.57058 | -0.3722 | 10.41799 |
August | 514.00000 | 23.86537 | 35.00299 | -0.4204 | 11.49128 |
September | 485.00000 | 23.31549 | 25.57935 | -0.7288 | 21.27089 |
October | 502.00000 | 21.63877 | 20.98359 | -0.3375 | 11.82176 |
November | 489.00000 | 21.10087 | 21.84678 | -0.5135 | 13.38658 |
December | 497.00000 | 20.43109 | 14.47857 | -0.7628 | 20.81757 |
Annual Sum or Average | 5943.00000 | 22.14754 | 24.61389 | -0.5350 | 15.62321 |
Minimum of Months | 454.00000 | 20.43109 | 14.47857 | -0.8871 | 10.41799 |
Maximum of Months | 514.00000 | 23.97552 | 36.57058 | -0.3375 | 26.40933 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.649987E+10 | 81804.72 | 20-JAN-14:40 | 70.48 | 0.373068E+11 | 0.00 | 0.438066E+11 | 0.45 | 6.93 | 20-JAN-14:40 | 0.00 | 0.00 |
February | 0.340143E+10 | 71235.14 | 18-FEB-13:30 | 66.59 | 0.161744E+11 | 0.00 | 0.195758E+11 | 0.43 | 6.63 | 18-FEB-13:30 | 0.00 | 0.00 |
March | 0.152224E+11 | 88065.45 | 14-MAR-13:00 | 120.86 | 0.871197E+11 | 0.00 | 0.102342E+12 | 0.81 | 7.02 | 14-MAR-13:00 | 0.00 | 0.00 |
April | 0.154709E+11 | 86321.70 | 07-APR-14:20 | 121.48 | 0.888706E+11 | 0.00 | 0.104342E+12 | 0.84 | 7.02 | 19-APR-14:10 | 0.00 | 0.00 |
May | 0.491291E+11 | 95338.75 | 31-MAY-15:50 | 267.79 | 0.301282E+12 | 0.00 | 0.350411E+12 | 1.99 | 7.17 | 31-MAY-15:50 | 0.00 | 0.00 |
June | 0.124280E+12 | 131531.75 | 26-JUN-15:20 | 523.62 | 0.824949E+12 | 0.00 | 0.949229E+12 | 4.43 | 7.36 | 26-JUN-14:20 | 0.00 | 0.00 |
July | 0.128202E+12 | 120529.63 | 17-JUL-13:30 | 569.95 | 0.844435E+12 | 0.00 | 0.972637E+12 | 4.58 | 7.35 | 17-JUL-13:30 | 0.00 | 0.00 |
August | 0.124063E+12 | 127074.47 | 16-AUG-15:10 | 622.40 | 0.815007E+12 | 0.00 | 0.939070E+12 | 4.81 | 7.35 | 16-AUG-13:40 | 0.00 | 0.00 |
September | 0.912416E+11 | 111265.33 | 12-SEP-16:00 | 408.63 | 0.589481E+12 | 0.00 | 0.680723E+12 | 3.39 | 7.31 | 12-SEP-16:00 | 0.00 | 0.00 |
October | 0.241237E+11 | 92908.69 | 10-OCT-13:10 | 159.16 | 0.145401E+12 | 0.00 | 0.169524E+12 | 1.13 | 7.11 | 11-OCT-15:00 | 0.00 | 0.00 |
November | 0.101817E+11 | 84186.67 | 09-NOV-11:30 | 84.90 | 0.596016E+11 | 0.00 | 0.697832E+11 | 0.59 | 6.98 | 06-NOV-12:40 | 0.00 | 0.00 |
December | 0.643231E+10 | 83966.41 | 01-DEC-15:00 | 62.36 | 0.363734E+11 | 0.00 | 0.428058E+11 | 0.40 | 6.96 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598248E+12 | 3078.22 | 0.384600E+13 | 0.00 | 0.444425E+13 | 2.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.340143E+10 | 71235.14 | 62.36 | 0.161744E+11 | 0.00 | 0.195758E+11 | 0.40 | 6.63 | 0.00 | 0.00 | ||
Maximum of Months | 0.128202E+12 | 131531.75 | 622.40 | 0.844435E+12 | 0.00 | 0.972637E+12 | 4.81 | 7.36 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.137279E+10 | 88065.45 | 14-MAR-13:00 | 4.50 | 0.956196E+10 | 0.00 | 0.109347E+11 | 0.04 | 7.02 | 14-MAR-13:00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.103552E+11 | 95338.75 | 31-MAY-15:50 | 33.00 | 0.726628E+11 | 0.00 | 0.830180E+11 | 0.31 | 7.17 | 31-MAY-15:50 | 0.00 | 0.00 |
June | 0.636546E+11 | 131531.75 | 26-JUN-15:20 | 182.44 | 0.455233E+12 | 0.00 | 0.518888E+12 | 1.81 | 7.36 | 26-JUN-14:20 | 0.00 | 0.00 |
July | 0.603318E+11 | 120529.63 | 17-JUL-13:30 | 175.43 | 0.430064E+12 | 0.00 | 0.490396E+12 | 1.68 | 7.35 | 17-JUL-13:30 | 0.00 | 0.00 |
August | 0.594032E+11 | 127074.47 | 16-AUG-15:10 | 171.12 | 0.424771E+12 | 0.00 | 0.484174E+12 | 1.64 | 7.35 | 16-AUG-13:40 | 0.00 | 0.00 |
September | 0.335002E+11 | 111265.33 | 12-SEP-16:00 | 102.04 | 0.237531E+12 | 0.00 | 0.271032E+12 | 1.00 | 7.31 | 12-SEP-16:00 | 0.00 | 0.00 |
October | 0.323955E+10 | 92908.69 | 10-OCT-13:10 | 10.33 | 0.227481E+11 | 0.00 | 0.259876E+11 | 0.10 | 7.11 | 11-OCT-15:00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.231857E+12 | 678.86 | 0.165257E+13 | 0.00 | 0.188443E+13 | 0.55 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.636546E+11 | 131531.75 | 182.44 | 0.455233E+12 | 0.00 | 0.518888E+12 | 1.81 | 7.36 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.184578E+11 | 744.00 | 49248.27 | 09-JAN-14:30 | 249585.99 | 20-JAN-16:20 | 22.20 | 18.39 | 15.66 |
February | 0.243589E+11 | 672.00 | 49248.27 | 17-FEB-13:20 | 404586.43 | 26-FEB-17:12 | 25.07 | 18.40 | 15.66 |
March | 0.646927E+11 | 744.00 | 49248.27 | 06-MAR-12:50 | 685167.44 | 31-MAR-24:00 | 28.62 | 18.98 | 15.66 |
April | 0.839092E+11 | 720.00 | 49248.27 | 05-APR-16:00 | 734704.64 | 08-APR-18:12 | 31.98 | 19.43 | 15.66 |
May | 0.732471E+11 | 744.00 | 49248.27 | 03-MAY-13:00 | 386633.82 | 31-MAY-23:50 | 24.10 | 19.95 | 15.66 |
June | 0.125825E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 563522.21 | 30-JUN-23:53 | 33.89 | 26.58 | 15.66 |
July | 0.131437E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 699078.46 | 31-JUL-24:00 | 39.02 | 28.80 | 15.66 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 775640.67 | 26-AUG-19:32 | 42.71 | 29.56 | 15.66 |
September | 0.103375E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 375077.73 | 30-SEP-24:00 | 26.92 | 22.62 | 15.66 |
October | 0.593703E+11 | 744.00 | 49248.27 | 01-OCT-10:12 | 513055.16 | 31-OCT-23:45 | 26.03 | 19.12 | 15.66 |
November | 0.522845E+11 | 720.00 | 49248.27 | 03-NOV-11:40 | 583195.18 | 07-NOV-16:10 | 28.39 | 18.73 | 15.66 |
December | 0.597490E+11 | 744.00 | 49248.27 | 01-DEC-09:40 | 734034.02 | 03-DEC-16:23 | 31.13 | 18.73 | 15.66 |
Annual Sum or Average | 0.928612E+12 | 8760.00 | 30.04 | 21.63 | 15.66 | ||||
Minimum of Months | 0.184578E+11 | 672.00 | 49248.27 | 249585.99 | 22.20 | 18.39 | 15.66 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 775640.67 | 42.71 | 29.56 | 15.66 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 24700114.59 | 27.04 | 1626.60 | 20-JAN-14:00 | 813767.06 | 20-JAN-14:00 | 21.08 | 20.99 | 2.83 |
February | 4767595.68 | 13.72 | 608.93 | 18-FEB-13:30 | 558184.90 | 18-FEB-13:30 | 20.96 | 20.92 | 2.28 |
March | 0.115200E+09 | 64.16 | 3070.30 | 14-MAR-14:30 | 1031996.46 | 14-MAR-14:30 | 21.15 | 20.95 | 6.33 |
April | 0.132788E+09 | 68.08 | 2921.23 | 20-APR-13:00 | 889786.99 | 20-APR-13:10 | 21.17 | 20.98 | 6.83 |
May | 0.152890E+10 | 211.80 | 16671.10 | 31-MAY-16:00 | 1152492.17 | 31-MAY-15:50 | 21.89 | 21.22 | 18.18 |
June | 0.918180E+10 | 451.73 | 17148.22 | 16-JUN-13:40 | 1153499.32 | 08-JUN-15:10 | 23.07 | 21.21 | 38.58 |
July | 0.117218E+11 | 484.83 | 17148.22 | 18-JUL-16:10 | 1154164.65 | 05-JUL-13:00 | 23.05 | 21.19 | 40.97 |
August | 0.913924E+10 | 467.60 | 17148.22 | 03-AUG-11:10 | 1154261.51 | 07-AUG-14:30 | 22.92 | 21.10 | 42.73 |
September | 0.382522E+10 | 358.57 | 14648.65 | 13-SEP-13:50 | 1154310.42 | 12-SEP-12:40 | 22.64 | 21.26 | 30.17 |
October | 0.293169E+09 | 99.73 | 4557.82 | 11-OCT-14:00 | 1101668.25 | 11-OCT-15:00 | 21.32 | 21.00 | 9.37 |
November | 80885375.96 | 42.41 | 2711.06 | 07-NOV-15:00 | 988818.63 | 07-NOV-15:00 | 21.08 | 20.95 | 4.29 |
December | 25921316.92 | 26.60 | 1983.23 | 01-DEC-14:20 | 824674.69 | 01-DEC-14:20 | 21.03 | 20.95 | 2.98 |
Annual Sum or Average | 0.360744E+11 | 2316.29 | 21.79 | 21.06 | 17.22 | ||||
Minimum of Months | 4767595.68 | 13.72 | 608.93 | 558184.90 | 20.96 | 20.92 | 2.28 | ||
Maximum of Months | 0.117218E+11 | 484.83 | 17148.22 | 1154310.42 | 23.07 | 21.26 | 42.73 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.08 | 21.08 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.96 | 20.96 | 0.00 |
March | 3374985.84 | 0.33 | 2879.84 | 14-MAR-12:20 | 1005835.76 | 14-MAR-12:20 | 21.15 | 21.15 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.17 | 21.17 | 0.00 |
May | 0.517404E+09 | 19.83 | 16671.10 | 31-MAY-16:00 | 1152492.17 | 31-MAY-15:50 | 21.89 | 21.77 | 1.48 |
June | 0.517638E+10 | 154.83 | 17148.22 | 16-JUN-13:40 | 1153499.32 | 08-JUN-15:10 | 23.07 | 22.17 | 11.93 |
July | 0.594637E+10 | 142.93 | 17148.22 | 18-JUL-16:10 | 1154164.65 | 05-JUL-13:00 | 23.05 | 22.25 | 10.66 |
August | 0.498143E+10 | 151.00 | 17148.22 | 03-AUG-11:10 | 1154261.51 | 07-AUG-14:30 | 22.92 | 22.07 | 11.26 |
September | 0.186499E+10 | 83.17 | 14648.65 | 13-SEP-13:50 | 1154310.42 | 12-SEP-12:40 | 22.64 | 22.14 | 6.41 |
October | 96421683.43 | 7.00 | 4557.82 | 11-OCT-14:00 | 1101668.25 | 11-OCT-15:00 | 21.32 | 21.28 | 0.52 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.08 | 21.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.185864E+11 | 559.10 | 21.79 | 21.52 | 3.54 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 20.96 | 0.00 | ||
Maximum of Months | 0.594637E+10 | 154.83 | 17148.22 | 1154310.42 | 23.07 | 22.25 | 11.93 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.360586E+12 | 0.00 | 453.83 | 1392729.75 | 05-JAN-07:05 | 0.00 | 32.39 | 62.26 | 0.74 | 0.00 | 0.05 | 0.52 | 05-JAN-07:05 |
February | 0.376845E+12 | 0.00 | 411.33 | 1599759.33 | 13-FEB-06:01 | 0.00 | 31.66 | 61.63 | 0.82 | 0.00 | 0.06 | 0.60 | 13-FEB-06:01 |
March | 0.250880E+12 | 0.00 | 353.28 | 1589488.59 | 20-MAR-05:01 | 0.00 | 28.99 | 53.24 | 0.47 | 0.00 | 0.04 | 0.60 | 20-MAR-05:01 |
April | 0.154465E+12 | 0.00 | 287.13 | 1207090.61 | 03-APR-04:01 | 0.00 | 27.63 | 48.53 | 0.29 | 0.00 | 0.02 | 0.45 | 03-APR-04:01 |
May | 0.141912E+11 | 0.00 | 80.10 | 1273844.30 | 01-MAY-05:01 | 0.00 | 24.69 | 30.76 | 0.02 | 0.00 | 0.00 | 0.48 | 01-MAY-05:01 |
June | 2207285.48 | 0.00 | 0.33 | 2562.60 | 09-JUN-06:10 | 0.00 | 22.33 | 22.36 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 22.33 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 3502808.05 | 0.00 | 1.83 | 2604.64 | 23-AUG-05:10 | 0.00 | 22.32 | 22.47 | 0.00 | 0.00 | 0.00 | 0.00 | 23-AUG-05:10 |
September | 0.817155E+10 | 0.00 | 38.08 | 513345.41 | 22-SEP-05:02 | 0.00 | 22.80 | 25.77 | 0.01 | 0.00 | 0.00 | 0.19 | 22-SEP-05:02 |
October | 0.175687E+12 | 0.00 | 259.90 | 1285832.13 | 24-OCT-05:01 | 0.00 | 27.16 | 45.41 | 0.34 | 0.00 | 0.02 | 0.48 | 24-OCT-05:01 |
November | 0.281864E+12 | 0.00 | 345.26 | 1262785.08 | 29-NOV-05:01 | 0.00 | 29.73 | 54.27 | 0.57 | 0.00 | 0.04 | 0.47 | 29-NOV-05:01 |
December | 0.549072E+12 | 0.00 | 495.10 | 1870765.44 | 26-DEC-05:11 | 0.00 | 33.70 | 65.11 | 1.28 | 0.00 | 0.08 | 0.70 | 26-DEC-05:11 |
Annual Sum or Average | 0.217177E+13 | 0.00 | 2726.18 | 0.00 | 27.12 | 42.75 | 0.38 | 0.00 | 0.03 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.549072E+12 | 0.00 | 495.10 | 1870765.44 | 0.00 | 33.70 | 65.11 | 1.28 | 0.00 | 0.08 | 0.70 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 22.20 | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.07 | 25.07 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 28.62 | 28.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.98 | 31.98 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 24.10 | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 33.89 | 33.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 39.02 | 39.02 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 42.71 | 42.71 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 26.92 | 26.92 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 26.03 | 26.03 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.39 | 28.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 31.13 | 31.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 30.04 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 22.20 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 | 42.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.340075E+10 | 0.00 | 33.67 | 0.340075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61239.32 | 20-JAN-14:00 | 61239.32 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.115709E+10 | 0.00 | 21.03 | 0.115709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38109.36 | 18-FEB-13:10 | 38109.36 | 18-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.100715E+11 | 0.00 | 88.42 | 0.100715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98644.80 | 13-MAR-16:00 | 98644.80 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.109989E+11 | 0.00 | 98.32 | 0.109989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85338.73 | 19-APR-13:50 | 85338.73 | 19-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.351665E+11 | 0.00 | 246.40 | 0.351665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113320.33 | 31-MAY-15:20 | 113320.33 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.116399E+12 | 0.00 | 499.83 | 0.116183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160005.27 | 26-JUN-15:20 | 160005.27 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.123683E+12 | 0.00 | 547.66 | 0.120609E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 149677.89 | 17-JUL-13:30 | 149677.89 | 17-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.131317E+12 | 0.00 | 601.40 | 0.130218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160865.05 | 16-AUG-14:40 | 160865.05 | 16-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.762415E+11 | 0.00 | 380.84 | 0.762415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136164.84 | 12-SEP-16:00 | 136164.84 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.159666E+11 | 0.00 | 124.60 | 0.159666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117385.97 | 10-OCT-16:00 | 117385.97 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.645336E+10 | 0.00 | 55.67 | 0.645336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83312.87 | 07-NOV-15:00 | 83312.87 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.387303E+10 | 0.00 | 37.03 | 0.387303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71747.10 | 01-DEC-14:00 | 71747.10 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534728E+12 | 0.00 | 2734.88 | 0.530338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.115709E+10 | 0.00 | 21.03 | 0.115709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38109.36 | 38109.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131317E+12 | 0.00 | 601.40 | 0.130218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 160865.05 | 160865.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.295701E+11 | 0.00 | 69.61 | 0.295701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 526522.36 | 20-JAN-14:00 | 526522.36 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.110700E+11 | 0.00 | 64.93 | 0.110700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 384174.62 | 18-FEB-14:00 | 384174.62 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.804468E+11 | 0.00 | 115.82 | 0.804468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 789965.12 | 14-MAR-13:00 | 789965.12 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.702111E+11 | 0.00 | 113.52 | 0.702111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 610209.41 | 20-APR-13:00 | 610209.41 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.304209E+12 | 0.00 | 248.88 | 0.304209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1049137.11 | 17-MAY-13:30 | 1049137.11 | 17-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.101167E+13 | 0.00 | 457.96 | 0.101009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1482857.18 | 26-JUN-15:20 | 1482857.18 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.101611E+13 | 0.00 | 464.06 | 0.995293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1352016.49 | 17-JUL-13:30 | 1352016.49 | 17-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.975237E+12 | 0.00 | 455.26 | 0.971204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1431180.62 | 16-AUG-15:10 | 1431180.62 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.670335E+12 | 0.00 | 375.26 | 0.670335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1263779.37 | 12-SEP-16:00 | 1263779.37 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.136999E+12 | 0.00 | 150.33 | 0.136999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 990275.70 | 11-OCT-15:00 | 990275.70 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.500145E+11 | 0.00 | 80.94 | 0.500145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 656669.71 | 07-NOV-15:00 | 656669.71 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.275609E+11 | 0.00 | 57.84 | 0.275609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 522858.89 | 01-DEC-14:00 | 522858.89 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438344E+13 | 0.00 | 2654.42 | 0.435700E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.110700E+11 | 0.00 | 57.84 | 0.110700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 384174.62 | 384174.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101611E+13 | 0.00 | 464.06 | 0.101009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1482857.18 | 1482857.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.218077E+10 | 0.00 | 29.95 | 0.218077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50324.62 | 20-JAN-14:00 | 50324.62 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.809522E+09 | 0.00 | 18.58 | 0.809522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36151.56 | 18-FEB-13:30 | 36151.56 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.730211E+10 | 0.00 | 80.49 | 0.730211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81867.46 | 14-MAR-13:00 | 81867.46 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.708119E+10 | 0.00 | 87.82 | 0.708119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66895.49 | 20-APR-13:00 | 66895.49 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.313792E+11 | 0.00 | 229.69 | 0.313792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128502.57 | 31-MAY-15:20 | 128502.57 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.115442E+12 | 0.00 | 448.87 | 0.115306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184594.91 | 26-JUN-15:20 | 184594.91 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.113984E+12 | 0.00 | 459.81 | 0.111921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165339.42 | 17-JUL-14:00 | 165339.42 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.109467E+12 | 0.00 | 444.86 | 0.109112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 178833.81 | 16-AUG-15:10 | 178833.81 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.704405E+11 | 0.00 | 358.80 | 0.704405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148009.42 | 12-SEP-16:00 | 148009.42 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.122832E+11 | 0.00 | 113.63 | 0.122832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112139.76 | 11-OCT-15:00 | 112139.76 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.401911E+10 | 0.00 | 45.86 | 0.401911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63744.37 | 07-NOV-15:00 | 63744.37 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.209233E+10 | 0.00 | 33.09 | 0.209233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48153.66 | 01-DEC-14:00 | 48153.66 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476481E+12 | 0.00 | 2351.45 | 0.473927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.809522E+09 | 0.00 | 18.58 | 0.809522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36151.56 | 36151.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115442E+12 | 0.00 | 459.81 | 0.115306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184594.91 | 184594.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.121314E+10 | 0.00 | 18.87 | 0.121314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34244.67 | 20-JAN-14:00 | 34244.67 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.100168E+09 | 0.00 | 3.83 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12338.57 | 18-FEB-13:00 | 12338.57 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.398921E+10 | 0.00 | 49.02 | 0.398921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59038.36 | 14-MAR-13:00 | 59038.36 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.468337E+10 | 0.00 | 63.54 | 0.468337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44262.66 | 20-APR-13:00 | 44262.66 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.202976E+11 | 0.00 | 173.86 | 0.202928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62953.11 | 31-MAY-14:00 | 62953.11 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.632655E+11 | 0.00 | 359.65 | 0.632185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83812.93 | 26-JUN-15:00 | 83812.93 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.640943E+11 | 0.00 | 363.04 | 0.633375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86723.80 | 28-JUL-05:03 | 82955.42 | 17-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.681699E+11 | 0.00 | 387.96 | 0.679417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103881.56 | 20-AUG-14:58 | 103881.56 | 20-AUG-14:58 | 0.00 | 0.00 | 0.00 |
September | 0.466709E+11 | 0.00 | 306.92 | 0.466659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105065.58 | 10-SEP-15:54 | 105065.58 | 10-SEP-15:54 | 0.00 | 0.00 | 0.00 |
October | 0.804675E+10 | 0.00 | 78.24 | 0.804675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73287.21 | 10-OCT-14:00 | 73287.21 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.299240E+10 | 0.00 | 33.38 | 0.299240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55429.30 | 06-NOV-13:10 | 55429.30 | 06-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 0.164272E+10 | 0.00 | 22.46 | 0.164272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42944.11 | 04-DEC-12:00 | 42944.11 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285166E+12 | 0.00 | 1860.79 | 0.284124E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100168E+09 | 0.00 | 3.83 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12338.57 | 12338.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.681699E+11 | 0.00 | 387.96 | 0.679417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105065.58 | 105065.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.397129E+12 | 0.101102E+12 | 744.00 | 0.346598E+12 | 0.505309E+11 | 0.00 | 0.39 | 20-JAN-14:00 | 0.34 | 05-JAN-08:00 | 153260.94 | 19-JAN-22:10 | 134186.47 | 20-JAN-14:10 | 20034.60 | 19-JAN-12:00 | 45194.05 | 20-JAN-14:00 | 0.00 |
February | 0.613257E+12 | 0.148071E+12 | 672.00 | 0.534587E+12 | 0.786706E+11 | 0.00 | 0.61 | 18-FEB-13:00 | 0.57 | 01-FEB-07:10 | 259849.00 | 17-FEB-22:03 | 225985.10 | 27-FEB-22:03 | 34333.13 | 17-FEB-11:00 | 72322.42 | 18-FEB-13:20 | 0.00 |
March | 0.962611E+12 | 0.227344E+12 | 744.00 | 0.842360E+12 | 0.120251E+12 | 0.00 | 1.00 | 31-MAR-23:10 | 0.79 | 04-MAR-18:00 | 462606.76 | 31-MAR-24:00 | 405027.95 | 31-MAR-24:00 | 58606.13 | 31-MAR-23:10 | 114856.64 | 14-MAR-13:00 | 0.00 |
April | 0.121359E+13 | 0.274858E+12 | 720.00 | 0.105076E+13 | 0.162836E+12 | 0.00 | 1.00 | 01-APR-00:10 | 0.42 | 30-APR-24:00 | 480066.16 | 18-APR-21:03 | 411331.00 | 21-APR-00:05 | 74530.75 | 18-APR-20:50 | 135062.88 | 19-APR-14:00 | 0.00 |
May | 0.405068E+12 | 0.108592E+12 | 744.00 | 0.355143E+12 | 0.499250E+11 | 0.00 | 0.60 | 31-MAY-23:30 | 0.36 | 03-MAY-06:10 | 251523.33 | 31-MAY-24:00 | 221147.70 | 31-MAY-24:00 | 30375.63 | 31-MAY-24:00 | 65170.82 | 31-MAY-23:20 | 0.00 |
June | 0.648129E+12 | 0.204241E+12 | 720.00 | 0.586270E+12 | 0.618590E+11 | 0.00 | 0.84 | 30-JUN-23:12 | 0.59 | 01-JUN-06:10 | 343406.95 | 30-JUN-24:00 | 313289.12 | 30-JUN-23:53 | 34888.09 | 23-JUN-06:05 | 117697.82 | 26-JUN-15:00 | 0.00 |
July | 0.933758E+12 | 0.300455E+12 | 744.00 | 0.852256E+12 | 0.815019E+11 | 0.00 | 1.00 | 31-JUL-23:05 | 0.81 | 03-JUL-06:10 | 446196.91 | 31-JUL-24:00 | 398789.67 | 31-JUL-23:52 | 49044.99 | 31-JUL-24:00 | 152718.93 | 16-JUL-13:00 | 0.00 |
August | 0.123100E+13 | 0.361246E+12 | 744.00 | 0.107978E+13 | 0.151220E+12 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-24:00 | 486320.20 | 17-AUG-02:54 | 413336.81 | 17-AUG-03:03 | 78910.96 | 21-AUG-17:00 | 178757.18 | 16-AUG-16:00 | 0.00 |
September | 0.394486E+12 | 0.115521E+12 | 720.00 | 0.349895E+12 | 0.445908E+11 | 0.00 | 0.59 | 30-SEP-24:00 | 0.36 | 22-SEP-06:10 | 253671.27 | 30-SEP-24:00 | 221431.79 | 30-SEP-24:00 | 32351.63 | 30-SEP-23:10 | 61001.40 | 30-SEP-24:00 | 0.00 |
October | 0.687823E+12 | 0.169978E+12 | 744.00 | 0.600909E+12 | 0.869141E+11 | 0.00 | 0.80 | 31-OCT-23:45 | 0.58 | 30-OCT-06:10 | 359100.59 | 31-OCT-23:45 | 312527.36 | 31-OCT-23:45 | 46577.57 | 31-OCT-23:50 | 89225.53 | 11-OCT-14:00 | 0.00 |
November | 0.937370E+12 | 0.219292E+12 | 720.00 | 0.818404E+12 | 0.118966E+12 | 0.00 | 0.85 | 07-NOV-15:00 | 0.79 | 01-NOV-06:10 | 367467.20 | 07-NOV-22:03 | 320613.51 | 07-NOV-15:00 | 48953.77 | 10-NOV-11:00 | 110363.50 | 07-NOV-15:00 | 0.00 |
December | 0.125770E+13 | 0.278891E+12 | 744.00 | 0.108576E+13 | 0.171941E+12 | 0.00 | 1.00 | 01-DEC-00:10 | 0.99 | 23-DEC-18:00 | 480668.07 | 03-DEC-17:03 | 411076.09 | 03-DEC-17:05 | 72586.31 | 14-DEC-16:25 | 134295.22 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.968192E+13 | 0.250959E+13 | 8760.00 | 0.850271E+13 | 0.117921E+13 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.394486E+12 | 0.101102E+12 | 672.00 | 0.346598E+12 | 0.445908E+11 | 0.00 | 0.39 | 0.34 | 153260.94 | 134186.47 | 20034.60 | 45194.05 | 0.00 | ||||||
Maximum of Months | 0.125770E+13 | 0.361246E+12 | 744.00 | 0.108576E+13 | 0.171941E+12 | 0.00 | 1.00 | 0.99 | 486320.20 | 413336.81 | 78910.96 | 178757.18 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.464237E+10 | 0.128295E+10 | 744.00 | 0.463372E+10 | 8646035.34 | 0.00 | 0.36 | 23-JAN-16:20 | 0.09 | 05-JAN-07:05 | 2908.43 | 23-JAN-16:30 | 2908.43 | 23-JAN-16:30 | 107.72 | 10-JAN-16:20 | 835.64 | 23-JAN-16:00 | 0.00 |
February | 0.885759E+10 | 0.231227E+10 | 672.00 | 0.885348E+10 | 4113804.69 | 0.00 | 0.56 | 26-FEB-16:42 | 0.32 | 06-FEB-07:10 | 4868.97 | 17-FEB-17:00 | 4848.29 | 17-FEB-17:00 | 88.41 | 28-FEB-16:50 | 1303.64 | 26-FEB-16:23 | 0.00 |
March | 0.154470E+11 | 0.393060E+10 | 744.00 | 0.154356E+11 | 11498210.81 | 0.00 | 0.85 | 31-MAR-24:00 | 0.55 | 20-MAR-06:10 | 7843.39 | 31-MAR-24:00 | 7843.39 | 31-MAR-24:00 | 155.91 | 17-MAR-15:10 | 2313.01 | 13-MAR-17:00 | 0.00 |
April | 0.202298E+11 | 0.496868E+10 | 720.00 | 0.202031E+11 | 26789879.47 | 0.00 | 1.00 | 08-APR-17:20 | 0.31 | 30-APR-24:00 | 8911.82 | 08-APR-18:14 | 8911.82 | 08-APR-18:14 | 239.66 | 28-APR-16:05 | 2723.25 | 19-APR-14:00 | 0.00 |
May | 0.598688E+10 | 0.168395E+10 | 744.00 | 0.593387E+10 | 53011380.21 | 0.00 | 0.48 | 31-MAY-24:00 | 0.19 | 03-MAY-06:10 | 4198.17 | 31-MAY-24:00 | 4178.94 | 31-MAY-24:00 | 221.81 | 22-MAY-14:10 | 1115.64 | 31-MAY-23:30 | 0.00 |
June | 0.112865E+11 | 0.368626E+10 | 720.00 | 0.111802E+11 | 0.106308E+09 | 0.00 | 0.73 | 30-JUN-23:12 | 0.44 | 10-JUN-06:40 | 6026.22 | 30-JUN-23:35 | 6026.22 | 30-JUN-23:35 | 330.19 | 20-JUN-17:00 | 2417.49 | 26-JUN-18:00 | 0.00 |
July | 0.166798E+11 | 0.554345E+10 | 744.00 | 0.165471E+11 | 0.132669E+09 | 0.00 | 0.93 | 01-JUL-18:35 | 0.66 | 20-JUL-06:10 | 7954.22 | 31-JUL-23:52 | 7954.22 | 31-JUL-23:52 | 505.05 | 31-JUL-16:00 | 3148.86 | 16-JUL-13:00 | 0.00 |
August | 0.220303E+11 | 0.716889E+10 | 744.00 | 0.219203E+11 | 0.109999E+09 | 0.00 | 1.00 | 02-AUG-12:20 | 0.34 | 31-AUG-24:00 | 9205.49 | 05-AUG-18:53 | 9182.81 | 05-AUG-18:50 | 517.94 | 29-AUG-15:00 | 3780.97 | 16-AUG-16:00 | 0.00 |
September | 0.609509E+10 | 0.187907E+10 | 720.00 | 0.605527E+10 | 39815045.11 | 0.00 | 0.46 | 30-SEP-24:00 | 0.17 | 22-SEP-06:10 | 4028.18 | 30-SEP-24:00 | 4028.18 | 30-SEP-24:00 | 227.57 | 01-SEP-14:40 | 1376.75 | 10-SEP-17:22 | 0.00 |
October | 0.106206E+11 | 0.280154E+10 | 744.00 | 0.106023E+11 | 18306377.77 | 0.00 | 0.64 | 09-OCT-16:42 | 0.35 | 30-OCT-06:10 | 5348.49 | 09-OCT-16:45 | 5348.49 | 09-OCT-16:45 | 143.22 | 03-OCT-11:00 | 1724.02 | 11-OCT-14:00 | 0.00 |
November | 0.149467E+11 | 0.371098E+10 | 720.00 | 0.149327E+11 | 13947556.90 | 0.00 | 0.82 | 07-NOV-16:00 | 0.56 | 01-NOV-06:10 | 6924.51 | 05-NOV-16:17 | 6924.51 | 05-NOV-16:17 | 138.48 | 09-NOV-17:00 | 2218.77 | 07-NOV-16:00 | 0.00 |
December | 0.202549E+11 | 0.500959E+10 | 744.00 | 0.202549E+11 | -0.0 | 0.00 | 1.00 | 03-DEC-15:23 | 0.75 | 23-DEC-07:05 | 8791.43 | 03-DEC-16:13 | 8791.43 | 03-DEC-16:13 | 0.00 | 03-DEC-17:00 | 2749.78 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.157078E+12 | 0.439782E+11 | 8760.00 | 0.156553E+12 | 0.525105E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.464237E+10 | 0.128295E+10 | 672.00 | 0.463372E+10 | -0.0 | 0.00 | 0.36 | 0.09 | 2908.43 | 2908.43 | 0.00 | 835.64 | 0.00 | ||||||
Maximum of Months | 0.220303E+11 | 0.716889E+10 | 744.00 | 0.219203E+11 | 0.132669E+09 | 0.00 | 1.00 | 0.75 | 9205.49 | 9182.81 | 517.94 | 3780.97 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.289921E+11 | 0.827718E+10 | 742.19 | 0.289090E+11 | 83072695.21 | 0.00 | 0.34 | 23-JAN-16:20 | 0.00 | 01-JAN-20:05 | 26443.00 | 23-JAN-16:40 | 26443.00 | 23-JAN-16:40 | 1079.38 | 10-JAN-16:20 | 7560.51 | 23-JAN-16:00 | 0.00 |
February | 0.690355E+11 | 0.183284E+11 | 672.00 | 0.689941E+11 | 41380907.25 | 0.00 | 0.53 | 17-FEB-17:00 | 0.17 | 06-FEB-07:10 | 45192.93 | 17-FEB-17:00 | 44915.31 | 17-FEB-17:00 | 882.27 | 28-FEB-16:50 | 11299.92 | 26-FEB-16:32 | 0.00 |
March | 0.133189E+12 | 0.343472E+11 | 744.00 | 0.133074E+12 | 0.114914E+09 | 0.00 | 0.83 | 13-MAR-17:00 | 0.41 | 20-MAR-06:10 | 72638.49 | 31-MAR-23:50 | 72638.49 | 31-MAR-23:50 | 1552.87 | 17-MAR-15:10 | 21865.97 | 13-MAR-17:00 | 0.00 |
April | 0.178170E+12 | 0.443082E+11 | 720.00 | 0.177902E+12 | 0.268099E+09 | 0.00 | 0.99 | 08-APR-17:31 | 0.15 | 30-APR-24:00 | 83099.32 | 08-APR-17:48 | 83099.32 | 08-APR-17:48 | 2375.99 | 28-APR-16:05 | 25341.08 | 19-APR-14:00 | 0.00 |
May | 0.513007E+11 | 0.145935E+11 | 744.00 | 0.507785E+11 | 0.522194E+09 | 0.00 | 0.48 | 31-MAY-24:00 | 0.09 | 01-MAY-06:10 | 39591.17 | 31-MAY-24:00 | 39380.45 | 31-MAY-24:00 | 2219.88 | 22-MAY-14:10 | 10543.75 | 31-MAY-23:20 | 0.00 |
June | 0.106047E+12 | 0.347431E+11 | 720.00 | 0.104988E+12 | 0.105967E+10 | 0.00 | 0.74 | 30-JUN-23:12 | 0.41 | 10-JUN-06:40 | 58877.40 | 30-JUN-23:55 | 58877.40 | 30-JUN-23:55 | 3245.27 | 20-JUN-17:00 | 23207.29 | 26-JUN-18:00 | 0.00 |
July | 0.158078E+12 | 0.526164E+11 | 744.00 | 0.156754E+12 | 0.132450E+10 | 0.00 | 0.93 | 01-JUL-18:35 | 0.63 | 29-JUL-06:10 | 74861.16 | 31-JUL-23:52 | 74861.16 | 31-JUL-23:52 | 4990.37 | 31-JUL-16:00 | 29704.78 | 16-JUL-13:00 | 0.00 |
August | 0.205438E+12 | 0.671992E+11 | 744.00 | 0.204340E+12 | 0.109832E+10 | 0.00 | 1.00 | 02-AUG-13:00 | 0.29 | 31-AUG-24:00 | 86011.44 | 05-AUG-18:12 | 85689.39 | 05-AUG-18:11 | 5053.68 | 29-AUG-15:00 | 36158.29 | 16-AUG-16:00 | 0.00 |
September | 0.537677E+11 | 0.167522E+11 | 720.00 | 0.533754E+11 | 0.392268E+09 | 0.00 | 0.45 | 10-SEP-17:22 | 0.12 | 22-SEP-06:10 | 36309.20 | 30-SEP-24:00 | 36309.20 | 30-SEP-24:00 | 2223.70 | 01-SEP-14:40 | 13042.99 | 10-SEP-17:22 | 0.00 |
October | 0.902208E+11 | 0.240986E+11 | 744.00 | 0.900389E+11 | 0.181902E+09 | 0.00 | 0.60 | 09-OCT-16:42 | 0.23 | 30-OCT-06:10 | 47943.44 | 09-OCT-16:43 | 47943.44 | 09-OCT-16:43 | 1412.38 | 03-OCT-11:00 | 16142.93 | 11-OCT-14:00 | 0.00 |
November | 0.127974E+12 | 0.321938E+11 | 720.00 | 0.127835E+12 | 0.139653E+09 | 0.00 | 0.80 | 07-NOV-16:00 | 0.47 | 29-NOV-07:10 | 64354.33 | 07-NOV-16:10 | 64354.33 | 07-NOV-16:10 | 1347.48 | 10-NOV-11:00 | 20730.96 | 07-NOV-16:00 | 0.00 |
December | 0.169136E+12 | 0.425861E+11 | 744.00 | 0.169136E+12 | 0.00 | 0.00 | 0.95 | 01-DEC-15:50 | 0.60 | 26-DEC-04:03 | 78941.85 | 01-DEC-16:00 | 78941.85 | 01-DEC-16:00 | 0.00 | 10-DEC-22:30 | 24866.74 | 01-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.137135E+13 | 0.390044E+12 | 8758.19 | 0.136612E+13 | 0.522597E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.289921E+11 | 0.827718E+10 | 672.00 | 0.289090E+11 | 0.00 | 0.00 | 0.34 | 0.00 | 26443.00 | 26443.00 | 0.00 | 7560.51 | 0.00 | ||||||
Maximum of Months | 0.205438E+12 | 0.671992E+11 | 744.00 | 0.204340E+12 | 0.132450E+10 | 0.00 | 1.00 | 0.63 | 86011.44 | 85689.39 | 5053.68 | 36158.29 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.127828E+10 | 0.375068E+09 | 444.49 | 0.127124E+10 | 7040499.76 | 0.00 | 0.33 | 20-JAN-16:20 | 0.00 | 01-JAN-00:03 | 2629.28 | 20-JAN-16:30 | 2629.28 | 20-JAN-16:30 | 106.72 | 10-JAN-16:20 | 732.64 | 20-JAN-16:00 | 0.00 |
February | 0.517222E+10 | 0.139911E+10 | 655.59 | 0.516820E+10 | 4022565.76 | 0.00 | 0.52 | 17-FEB-17:00 | 0.00 | 05-FEB-01:15 | 4497.06 | 17-FEB-17:00 | 4473.77 | 17-FEB-17:00 | 86.15 | 28-FEB-17:00 | 1110.31 | 17-FEB-17:00 | 0.00 |
March | 0.118783E+11 | 0.311021E+10 | 744.00 | 0.118670E+11 | 11262212.22 | 0.00 | 0.82 | 13-MAR-17:00 | 0.23 | 20-MAR-03:01 | 7025.55 | 31-MAR-23:20 | 7025.55 | 31-MAR-23:20 | 154.59 | 17-MAR-15:10 | 2214.73 | 13-MAR-17:00 | 0.00 |
April | 0.163433E+11 | 0.412604E+10 | 719.00 | 0.163166E+11 | 26648396.14 | 0.00 | 0.97 | 08-APR-17:31 | 0.00 | 30-APR-23:05 | 8348.15 | 07-APR-17:40 | 8348.15 | 07-APR-17:40 | 237.98 | 28-APR-16:05 | 2572.92 | 19-APR-14:00 | 0.00 |
May | 0.457727E+10 | 0.132196E+10 | 734.67 | 0.452555E+10 | 51714694.34 | 0.00 | 0.46 | 31-MAY-23:30 | 0.00 | 01-MAY-00:10 | 3906.26 | 31-MAY-23:50 | 3884.37 | 31-MAY-24:00 | 222.24 | 22-MAY-14:10 | 1046.89 | 31-MAY-23:20 | 0.00 |
June | 0.106291E+11 | 0.350069E+10 | 720.00 | 0.105232E+11 | 0.105889E+09 | 0.00 | 0.73 | 30-JUN-23:10 | 0.37 | 10-JUN-06:40 | 5858.22 | 30-JUN-23:08 | 5858.22 | 30-JUN-23:08 | 326.80 | 20-JUN-17:00 | 2393.85 | 26-JUN-18:00 | 0.00 |
July | 0.158401E+11 | 0.529619E+10 | 744.00 | 0.157079E+11 | 0.132283E+09 | 0.00 | 0.94 | 01-JUL-18:35 | 0.60 | 29-JUL-06:10 | 7375.97 | 31-JUL-23:52 | 7375.97 | 31-JUL-23:52 | 501.06 | 31-JUL-16:00 | 3076.38 | 16-JUL-15:02 | 0.00 |
August | 0.205474E+11 | 0.675470E+10 | 744.00 | 0.204378E+11 | 0.109590E+09 | 0.00 | 1.00 | 02-AUG-15:30 | 0.28 | 31-AUG-24:00 | 8735.76 | 13-AUG-18:42 | 8735.76 | 13-AUG-18:42 | 506.85 | 29-AUG-15:00 | 3701.83 | 16-AUG-16:00 | 0.00 |
September | 0.507776E+10 | 0.160564E+10 | 718.97 | 0.503871E+10 | 39050310.57 | 0.00 | 0.47 | 10-SEP-17:35 | 0.00 | 22-SEP-00:35 | 3496.58 | 10-SEP-17:35 | 3496.58 | 10-SEP-17:35 | 224.86 | 01-SEP-14:40 | 1407.33 | 10-SEP-17:11 | 0.00 |
October | 0.759508E+10 | 0.206652E+10 | 743.96 | 0.757730E+10 | 17779263.57 | 0.00 | 0.60 | 11-OCT-16:30 | 0.00 | 30-OCT-05:12 | 4758.59 | 08-OCT-16:50 | 4758.59 | 08-OCT-16:50 | 143.51 | 03-OCT-11:00 | 1639.16 | 11-OCT-14:00 | 0.00 |
November | 0.109646E+11 | 0.281032E+10 | 720.00 | 0.109509E+11 | 13733610.00 | 0.00 | 0.79 | 07-NOV-16:00 | 0.32 | 27-NOV-04:25 | 6439.22 | 07-NOV-16:10 | 6439.22 | 07-NOV-16:10 | 134.09 | 09-NOV-17:00 | 2080.44 | 07-NOV-16:00 | 0.00 |
December | 0.148301E+11 | 0.380129E+10 | 744.00 | 0.148301E+11 | -0.0 | 0.00 | 0.92 | 01-DEC-15:50 | 0.44 | 25-DEC-06:50 | 7849.30 | 01-DEC-16:00 | 7849.30 | 01-DEC-16:00 | 0.00 | 03-DEC-08:15 | 2472.59 | 01-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.124734E+12 | 0.361677E+11 | 8432.67 | 0.124215E+12 | 0.519013E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.127828E+10 | 0.375068E+09 | 444.49 | 0.127124E+10 | -0.0 | 0.00 | 0.33 | 0.00 | 2629.28 | 2629.28 | 0.00 | 732.64 | 0.00 | ||||||
Maximum of Months | 0.205474E+11 | 0.675470E+10 | 744.00 | 0.204378E+11 | 0.132283E+09 | 0.00 | 1.00 | 0.60 | 8735.76 | 8735.76 | 506.85 | 3701.83 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.37 | 0.00 | 110.37 | 16.10 | 573.33 | 0.00 | 0.00 | 0.00 |
February | 138.73 | 0.00 | 138.73 | 21.12 | 576.54 | 0.00 | 0.00 | 0.00 |
March | 188.76 | 0.00 | 188.76 | 76.35 | 443.16 | 0.00 | 0.00 | 0.00 |
April | 237.06 | 1.32 | 235.74 | 118.45 | 391.46 | 0.00 | 0.00 | 0.00 |
May | 323.83 | 10.70 | 313.13 | 283.73 | 217.97 | 0.00 | 0.00 | 0.00 |
June | 355.11 | 39.37 | 315.74 | 463.72 | 117.57 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.74 | 314.09 | 443.44 | 110.41 | 0.00 | 0.00 | 0.00 |
August | 267.30 | 6.32 | 260.97 | 334.89 | 127.47 | 0.00 | 0.00 | 0.00 |
September | 224.53 | 0.05 | 224.48 | 248.19 | 200.75 | 0.00 | 0.00 | 0.00 |
October | 160.82 | 0.00 | 160.82 | 82.03 | 428.88 | 0.00 | 0.00 | 0.00 |
November | 122.08 | 0.00 | 122.08 | 27.62 | 523.95 | 0.00 | 0.00 | 0.00 |
December | 103.27 | 0.00 | 103.27 | 12.28 | 652.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.37 | 6.64 | 207.72 | 178.20 | 362.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.27 | 0.00 | 103.27 | 12.28 | 110.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.11 | 39.37 | 315.74 | 463.72 | 652.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.37 | 0.00 | 110.37 | 16.10 | 573.33 | 0.00 | 0.00 | 0.00 |
February | 138.72 | 0.00 | 138.72 | 21.11 | 576.54 | 0.00 | 0.00 | 0.00 |
March | 188.76 | 0.00 | 188.76 | 76.35 | 443.16 | 0.00 | 0.00 | 0.00 |
April | 237.05 | 1.32 | 235.74 | 118.45 | 391.46 | 0.00 | 0.00 | 0.00 |
May | 323.83 | 10.70 | 313.12 | 283.73 | 217.97 | 0.00 | 0.00 | 0.00 |
June | 355.10 | 39.37 | 315.73 | 463.72 | 117.57 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.74 | 314.09 | 443.44 | 110.41 | 0.00 | 0.00 | 0.00 |
August | 267.29 | 6.32 | 260.97 | 334.88 | 127.47 | 0.00 | 0.00 | 0.00 |
September | 224.53 | 0.05 | 224.47 | 248.19 | 200.75 | 0.00 | 0.00 | 0.00 |
October | 160.82 | 0.00 | 160.82 | 82.03 | 428.88 | 0.00 | 0.00 | 0.00 |
November | 122.08 | 0.00 | 122.08 | 27.62 | 523.95 | 0.00 | 0.00 | 0.00 |
December | 103.27 | 0.00 | 103.27 | 12.28 | 652.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.36 | 6.64 | 207.72 | 178.20 | 362.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.27 | 0.00 | 103.27 | 12.28 | 110.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.10 | 39.37 | 315.73 | 463.72 | 652.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.37 | 0.00 | 110.37 | 16.10 | 573.33 | 0.00 | 0.00 | 0.00 |
February | 138.73 | 0.00 | 138.73 | 21.11 | 576.54 | 0.00 | 0.00 | 0.00 |
March | 188.76 | 0.00 | 188.76 | 76.35 | 443.16 | 0.00 | 0.00 | 0.00 |
April | 237.05 | 1.32 | 235.74 | 118.45 | 391.46 | 0.00 | 0.00 | 0.00 |
May | 323.83 | 10.70 | 313.13 | 283.73 | 217.97 | 0.00 | 0.00 | 0.00 |
June | 355.10 | 39.37 | 315.73 | 463.72 | 117.57 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.74 | 314.09 | 443.44 | 110.41 | 0.00 | 0.00 | 0.00 |
August | 267.30 | 6.32 | 260.97 | 334.88 | 127.47 | 0.00 | 0.00 | 0.00 |
September | 224.53 | 0.05 | 224.48 | 248.19 | 200.75 | 0.00 | 0.00 | 0.00 |
October | 160.82 | 0.00 | 160.82 | 82.03 | 428.88 | 0.00 | 0.00 | 0.00 |
November | 122.08 | 0.00 | 122.08 | 27.62 | 523.95 | 0.00 | 0.00 | 0.00 |
December | 103.27 | 0.00 | 103.27 | 12.28 | 652.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.36 | 6.64 | 207.72 | 178.20 | 362.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.27 | 0.00 | 103.27 | 12.28 | 110.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.10 | 39.37 | 315.73 | 463.72 | 652.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.37 | 0.00 | 110.37 | 16.10 | 573.33 | 0.00 | 0.00 | 0.00 |
February | 138.72 | 0.00 | 138.72 | 21.11 | 576.54 | 0.00 | 0.00 | 0.00 |
March | 188.76 | 0.00 | 188.76 | 76.35 | 443.16 | 0.00 | 0.00 | 0.00 |
April | 237.05 | 1.32 | 235.74 | 118.45 | 391.46 | 0.00 | 0.00 | 0.00 |
May | 323.83 | 10.70 | 313.12 | 283.73 | 217.97 | 0.00 | 0.00 | 0.00 |
June | 355.10 | 39.37 | 315.73 | 463.72 | 117.57 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.74 | 314.09 | 443.44 | 110.41 | 0.00 | 0.00 | 0.00 |
August | 267.29 | 6.32 | 260.97 | 334.88 | 127.47 | 0.00 | 0.00 | 0.00 |
September | 224.53 | 0.05 | 224.47 | 248.19 | 200.75 | 0.00 | 0.00 | 0.00 |
October | 160.82 | 0.00 | 160.82 | 82.03 | 428.88 | 0.00 | 0.00 | 0.00 |
November | 122.08 | 0.00 | 122.08 | 27.62 | 523.95 | 0.00 | 0.00 | 0.00 |
December | 103.27 | 0.00 | 103.27 | 12.28 | 652.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.36 | 6.64 | 207.72 | 178.20 | 362.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.27 | 0.00 | 103.27 | 12.28 | 110.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.10 | 39.37 | 315.73 | 463.72 | 652.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.37 | 0.00 | 110.37 | 16.10 | 573.31 | 0.00 | 0.00 | 0.00 |
February | 138.72 | 0.00 | 138.72 | 21.11 | 576.52 | 0.00 | 0.00 | 0.00 |
March | 188.75 | 0.00 | 188.75 | 76.35 | 443.14 | 0.00 | 0.00 | 0.00 |
April | 237.04 | 1.32 | 235.73 | 118.44 | 391.44 | 0.00 | 0.00 | 0.00 |
May | 323.82 | 10.70 | 313.11 | 283.72 | 217.97 | 0.00 | 0.00 | 0.00 |
June | 355.09 | 39.37 | 315.72 | 463.70 | 117.56 | 0.00 | 0.00 | 0.00 |
July | 335.82 | 21.74 | 314.08 | 443.42 | 110.41 | 0.00 | 0.00 | 0.00 |
August | 267.28 | 6.32 | 260.96 | 334.87 | 127.47 | 0.00 | 0.00 | 0.00 |
September | 224.52 | 0.05 | 224.47 | 248.18 | 200.74 | 0.00 | 0.00 | 0.00 |
October | 160.81 | 0.00 | 160.81 | 82.03 | 428.86 | 0.00 | 0.00 | 0.00 |
November | 122.08 | 0.00 | 122.08 | 27.62 | 523.93 | 0.00 | 0.00 | 0.00 |
December | 103.26 | 0.00 | 103.26 | 12.28 | 652.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.35 | 6.64 | 207.71 | 178.19 | 362.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.26 | 0.00 | 103.26 | 12.28 | 110.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.09 | 39.37 | 315.72 | 463.70 | 652.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.02 | 235.34 | 148.68 | 330.14 | 583.53 | 0.00 | 0.00 | 0.00 |
February | 510.12 | 322.04 | 188.08 | 469.27 | 598.25 | 0.00 | 0.00 | 0.00 |
March | 615.70 | 359.13 | 256.57 | 611.96 | 457.32 | 0.00 | 0.00 | 0.00 |
April | 631.44 | 307.58 | 323.85 | 613.71 | 404.15 | 0.00 | 0.00 | 0.00 |
May | 738.14 | 308.32 | 429.82 | 823.75 | 238.46 | 0.00 | 0.00 | 0.00 |
June | 900.61 | 472.80 | 427.81 | 1194.70 | 126.11 | 0.00 | 0.00 | 0.00 |
July | 818.72 | 389.86 | 428.87 | 1096.60 | 115.19 | 0.00 | 0.00 | 0.00 |
August | 825.80 | 454.82 | 370.98 | 1098.78 | 127.92 | 0.00 | 0.00 | 0.00 |
September | 687.10 | 373.25 | 313.85 | 865.28 | 208.59 | 0.00 | 0.00 | 0.00 |
October | 497.60 | 272.66 | 224.94 | 514.45 | 452.12 | 0.00 | 0.00 | 0.00 |
November | 387.32 | 218.68 | 168.63 | 353.13 | 539.91 | 0.00 | 0.00 | 0.00 |
December | 335.31 | 193.16 | 142.15 | 274.26 | 662.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.37 | 325.48 | 285.90 | 688.20 | 374.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 335.31 | 193.16 | 142.15 | 274.26 | 115.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 900.61 | 472.80 | 429.82 | 1194.70 | 662.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.02 | 235.34 | 148.68 | 330.14 | 583.53 | 0.00 | 0.00 | 0.00 |
February | 510.12 | 322.04 | 188.08 | 469.27 | 598.25 | 0.00 | 0.00 | 0.00 |
March | 615.70 | 359.13 | 256.57 | 611.96 | 457.32 | 0.00 | 0.00 | 0.00 |
April | 631.44 | 307.58 | 323.85 | 613.71 | 404.15 | 0.00 | 0.00 | 0.00 |
May | 738.14 | 308.32 | 429.82 | 823.75 | 238.46 | 0.00 | 0.00 | 0.00 |
June | 900.61 | 472.80 | 427.81 | 1194.70 | 126.11 | 0.00 | 0.00 | 0.00 |
July | 818.72 | 389.86 | 428.87 | 1096.60 | 115.19 | 0.00 | 0.00 | 0.00 |
August | 825.80 | 454.82 | 370.98 | 1098.78 | 127.92 | 0.00 | 0.00 | 0.00 |
September | 687.10 | 373.25 | 313.85 | 865.28 | 208.59 | 0.00 | 0.00 | 0.00 |
October | 497.60 | 272.66 | 224.94 | 514.45 | 452.12 | 0.00 | 0.00 | 0.00 |
November | 387.32 | 218.68 | 168.63 | 353.13 | 539.91 | 0.00 | 0.00 | 0.00 |
December | 335.31 | 193.16 | 142.15 | 274.26 | 662.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.37 | 325.48 | 285.90 | 688.20 | 374.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 335.31 | 193.16 | 142.15 | 274.26 | 115.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 900.61 | 472.80 | 429.82 | 1194.70 | 662.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.01 | 235.33 | 148.68 | 330.14 | 583.52 | 0.00 | 0.00 | 0.00 |
February | 510.11 | 322.03 | 188.08 | 469.26 | 598.24 | 0.00 | 0.00 | 0.00 |
March | 615.69 | 359.13 | 256.56 | 611.95 | 457.31 | 0.00 | 0.00 | 0.00 |
April | 631.43 | 307.58 | 323.85 | 613.70 | 404.14 | 0.00 | 0.00 | 0.00 |
May | 738.13 | 308.32 | 429.81 | 823.73 | 238.45 | 0.00 | 0.00 | 0.00 |
June | 900.59 | 472.79 | 427.80 | 1194.68 | 126.11 | 0.00 | 0.00 | 0.00 |
July | 818.71 | 389.85 | 428.86 | 1096.58 | 115.18 | 0.00 | 0.00 | 0.00 |
August | 825.78 | 454.81 | 370.97 | 1098.76 | 127.92 | 0.00 | 0.00 | 0.00 |
September | 687.09 | 373.25 | 313.84 | 865.26 | 208.58 | 0.00 | 0.00 | 0.00 |
October | 497.59 | 272.65 | 224.94 | 514.44 | 452.11 | 0.00 | 0.00 | 0.00 |
November | 387.31 | 218.68 | 168.63 | 353.13 | 539.90 | 0.00 | 0.00 | 0.00 |
December | 335.31 | 193.16 | 142.15 | 274.26 | 662.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.36 | 325.47 | 285.89 | 688.19 | 374.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 335.31 | 193.16 | 142.15 | 274.26 | 115.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 900.59 | 472.79 | 429.81 | 1194.68 | 662.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1057.78 | 870.14 | 187.64 | 1188.34 | 499.54 | 0.00 | 0.00 | 0.00 |
February | 1014.61 | 808.91 | 205.70 | 1131.25 | 519.35 | 0.00 | 0.00 | 0.00 |
March | 748.05 | 492.17 | 255.88 | 843.47 | 417.56 | 0.00 | 0.00 | 0.00 |
April | 484.49 | 194.82 | 289.68 | 495.48 | 381.83 | 0.00 | 0.00 | 0.00 |
May | 443.99 | 81.38 | 362.61 | 498.87 | 232.92 | 0.00 | 0.00 | 0.00 |
June | 409.34 | 74.82 | 334.53 | 581.13 | 127.19 | 0.00 | 0.00 | 0.00 |
July | 426.11 | 76.30 | 349.81 | 606.12 | 116.48 | 0.00 | 0.00 | 0.00 |
August | 542.53 | 226.80 | 315.73 | 773.91 | 132.05 | 0.00 | 0.00 | 0.00 |
September | 698.02 | 389.49 | 308.53 | 935.73 | 204.21 | 0.00 | 0.00 | 0.00 |
October | 834.62 | 592.18 | 242.44 | 994.93 | 411.64 | 0.00 | 0.00 | 0.00 |
November | 1016.87 | 810.59 | 206.28 | 1167.59 | 478.33 | 0.00 | 0.00 | 0.00 |
December | 972.39 | 787.04 | 185.35 | 1067.81 | 565.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.07 | 448.35 | 270.72 | 855.48 | 339.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.34 | 74.82 | 185.35 | 495.48 | 116.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1057.78 | 870.14 | 362.61 | 1188.34 | 565.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1057.78 | 870.13 | 187.64 | 1188.33 | 499.54 | 0.00 | 0.00 | 0.00 |
February | 1014.60 | 808.90 | 205.70 | 1131.24 | 519.35 | 0.00 | 0.00 | 0.00 |
March | 748.05 | 492.17 | 255.88 | 843.47 | 417.56 | 0.00 | 0.00 | 0.00 |
April | 484.49 | 194.81 | 289.68 | 495.48 | 381.83 | 0.00 | 0.00 | 0.00 |
May | 443.98 | 81.38 | 362.61 | 498.87 | 232.92 | 0.00 | 0.00 | 0.00 |
June | 409.34 | 74.81 | 334.53 | 581.13 | 127.19 | 0.00 | 0.00 | 0.00 |
July | 426.11 | 76.30 | 349.81 | 606.11 | 116.48 | 0.00 | 0.00 | 0.00 |
August | 542.53 | 226.79 | 315.73 | 773.91 | 132.05 | 0.00 | 0.00 | 0.00 |
September | 698.01 | 389.48 | 308.53 | 935.73 | 204.21 | 0.00 | 0.00 | 0.00 |
October | 834.62 | 592.18 | 242.44 | 994.92 | 411.64 | 0.00 | 0.00 | 0.00 |
November | 1016.86 | 810.58 | 206.28 | 1167.58 | 478.33 | 0.00 | 0.00 | 0.00 |
December | 972.38 | 787.03 | 185.35 | 1067.80 | 565.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.07 | 448.35 | 270.72 | 855.47 | 339.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.34 | 74.81 | 185.35 | 495.48 | 116.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1057.78 | 870.13 | 362.61 | 1188.33 | 565.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1057.78 | 870.14 | 187.64 | 1188.34 | 499.54 | 0.00 | 0.00 | 0.00 |
February | 1014.61 | 808.91 | 205.70 | 1131.25 | 519.35 | 0.00 | 0.00 | 0.00 |
March | 748.05 | 492.17 | 255.88 | 843.47 | 417.56 | 0.00 | 0.00 | 0.00 |
April | 484.49 | 194.82 | 289.68 | 495.48 | 381.83 | 0.00 | 0.00 | 0.00 |
May | 443.99 | 81.38 | 362.61 | 498.87 | 232.92 | 0.00 | 0.00 | 0.00 |
June | 409.34 | 74.82 | 334.53 | 581.13 | 127.19 | 0.00 | 0.00 | 0.00 |
July | 426.11 | 76.30 | 349.81 | 606.12 | 116.48 | 0.00 | 0.00 | 0.00 |
August | 542.53 | 226.80 | 315.73 | 773.91 | 132.05 | 0.00 | 0.00 | 0.00 |
September | 698.02 | 389.49 | 308.53 | 935.73 | 204.21 | 0.00 | 0.00 | 0.00 |
October | 834.62 | 592.18 | 242.44 | 994.93 | 411.64 | 0.00 | 0.00 | 0.00 |
November | 1016.87 | 810.59 | 206.28 | 1167.59 | 478.33 | 0.00 | 0.00 | 0.00 |
December | 972.39 | 787.04 | 185.35 | 1067.81 | 565.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.07 | 448.35 | 270.72 | 855.48 | 339.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.34 | 74.82 | 185.35 | 495.48 | 116.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1057.78 | 870.14 | 362.61 | 1188.34 | 565.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1057.78 | 870.13 | 187.64 | 1188.33 | 499.54 | 0.00 | 0.00 | 0.00 |
February | 1014.60 | 808.90 | 205.70 | 1131.24 | 519.35 | 0.00 | 0.00 | 0.00 |
March | 748.05 | 492.17 | 255.88 | 843.47 | 417.56 | 0.00 | 0.00 | 0.00 |
April | 484.49 | 194.81 | 289.68 | 495.48 | 381.83 | 0.00 | 0.00 | 0.00 |
May | 443.98 | 81.38 | 362.61 | 498.87 | 232.92 | 0.00 | 0.00 | 0.00 |
June | 409.34 | 74.81 | 334.53 | 581.13 | 127.19 | 0.00 | 0.00 | 0.00 |
July | 426.11 | 76.30 | 349.81 | 606.11 | 116.48 | 0.00 | 0.00 | 0.00 |
August | 542.53 | 226.79 | 315.73 | 773.91 | 132.05 | 0.00 | 0.00 | 0.00 |
September | 698.01 | 389.48 | 308.53 | 935.73 | 204.21 | 0.00 | 0.00 | 0.00 |
October | 834.62 | 592.18 | 242.44 | 994.92 | 411.64 | 0.00 | 0.00 | 0.00 |
November | 1016.86 | 810.58 | 206.28 | 1167.58 | 478.33 | 0.00 | 0.00 | 0.00 |
December | 972.38 | 787.03 | 185.35 | 1067.80 | 565.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.07 | 448.35 | 270.72 | 855.47 | 339.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.34 | 74.81 | 185.35 | 495.48 | 116.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1057.78 | 870.13 | 362.61 | 1188.33 | 565.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1057.74 | 870.10 | 187.64 | 1188.29 | 499.52 | 0.00 | 0.00 | 0.00 |
February | 1014.57 | 808.87 | 205.69 | 1131.20 | 519.33 | 0.00 | 0.00 | 0.00 |
March | 748.02 | 492.15 | 255.87 | 843.44 | 417.55 | 0.00 | 0.00 | 0.00 |
April | 484.47 | 194.81 | 289.67 | 495.46 | 381.81 | 0.00 | 0.00 | 0.00 |
May | 443.97 | 81.38 | 362.59 | 498.85 | 232.91 | 0.00 | 0.00 | 0.00 |
June | 409.32 | 74.81 | 334.51 | 581.11 | 127.18 | 0.00 | 0.00 | 0.00 |
July | 426.10 | 76.30 | 349.80 | 606.09 | 116.47 | 0.00 | 0.00 | 0.00 |
August | 542.51 | 226.79 | 315.72 | 773.88 | 132.05 | 0.00 | 0.00 | 0.00 |
September | 697.99 | 389.47 | 308.52 | 935.69 | 204.20 | 0.00 | 0.00 | 0.00 |
October | 834.58 | 592.16 | 242.43 | 994.89 | 411.63 | 0.00 | 0.00 | 0.00 |
November | 1016.82 | 810.55 | 206.27 | 1167.53 | 478.31 | 0.00 | 0.00 | 0.00 |
December | 972.35 | 787.00 | 185.34 | 1067.76 | 565.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 719.04 | 448.33 | 270.71 | 855.44 | 339.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.32 | 74.81 | 185.34 | 495.46 | 116.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1057.74 | 870.10 | 362.59 | 1188.29 | 565.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 408.51 | 258.85 | 149.65 | 375.39 | 623.11 | 0.00 | 0.00 | 0.00 |
February | 492.60 | 305.27 | 187.33 | 448.62 | 645.55 | 0.00 | 0.00 | 0.00 |
March | 576.81 | 318.24 | 258.57 | 554.94 | 514.44 | 0.00 | 0.00 | 0.00 |
April | 543.09 | 229.93 | 313.15 | 491.43 | 478.49 | 0.00 | 0.00 | 0.00 |
May | 663.79 | 234.01 | 429.78 | 733.33 | 270.67 | 0.00 | 0.00 | 0.00 |
June | 811.86 | 390.62 | 421.24 | 1077.71 | 160.17 | 0.00 | 0.00 | 0.00 |
July | 661.47 | 242.29 | 419.19 | 876.12 | 148.92 | 0.00 | 0.00 | 0.00 |
August | 690.39 | 341.06 | 349.33 | 894.08 | 175.40 | 0.00 | 0.00 | 0.00 |
September | 612.17 | 293.58 | 318.59 | 769.16 | 240.48 | 0.00 | 0.00 | 0.00 |
October | 515.00 | 294.36 | 220.64 | 540.51 | 496.05 | 0.00 | 0.00 | 0.00 |
November | 422.58 | 256.56 | 166.02 | 393.62 | 598.64 | 0.00 | 0.00 | 0.00 |
December | 341.33 | 201.63 | 139.70 | 276.26 | 741.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.81 | 280.20 | 281.61 | 619.97 | 423.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.33 | 201.63 | 139.70 | 276.26 | 148.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.86 | 390.62 | 429.78 | 1077.71 | 741.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 408.51 | 258.85 | 149.65 | 375.39 | 623.11 | 0.00 | 0.00 | 0.00 |
February | 492.60 | 305.27 | 187.33 | 448.62 | 645.55 | 0.00 | 0.00 | 0.00 |
March | 576.81 | 318.24 | 258.57 | 554.94 | 514.44 | 0.00 | 0.00 | 0.00 |
April | 543.09 | 229.93 | 313.15 | 491.43 | 478.49 | 0.00 | 0.00 | 0.00 |
May | 663.79 | 234.01 | 429.78 | 733.33 | 270.67 | 0.00 | 0.00 | 0.00 |
June | 811.86 | 390.62 | 421.24 | 1077.71 | 160.17 | 0.00 | 0.00 | 0.00 |
July | 661.47 | 242.29 | 419.19 | 876.12 | 148.92 | 0.00 | 0.00 | 0.00 |
August | 690.39 | 341.06 | 349.33 | 894.08 | 175.40 | 0.00 | 0.00 | 0.00 |
September | 612.17 | 293.58 | 318.59 | 769.16 | 240.48 | 0.00 | 0.00 | 0.00 |
October | 515.00 | 294.36 | 220.64 | 540.51 | 496.05 | 0.00 | 0.00 | 0.00 |
November | 422.58 | 256.56 | 166.02 | 393.62 | 598.64 | 0.00 | 0.00 | 0.00 |
December | 341.33 | 201.63 | 139.70 | 276.26 | 741.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.81 | 280.20 | 281.61 | 619.97 | 423.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.33 | 201.63 | 139.70 | 276.26 | 148.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.86 | 390.62 | 429.78 | 1077.71 | 741.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 408.50 | 258.85 | 149.65 | 375.39 | 623.10 | 0.00 | 0.00 | 0.00 |
February | 492.59 | 305.26 | 187.33 | 448.62 | 645.54 | 0.00 | 0.00 | 0.00 |
March | 576.79 | 318.23 | 258.56 | 554.93 | 514.43 | 0.00 | 0.00 | 0.00 |
April | 543.08 | 229.93 | 313.15 | 491.42 | 478.48 | 0.00 | 0.00 | 0.00 |
May | 663.78 | 234.01 | 429.77 | 733.32 | 270.67 | 0.00 | 0.00 | 0.00 |
June | 811.85 | 390.61 | 421.24 | 1077.69 | 160.17 | 0.00 | 0.00 | 0.00 |
July | 661.46 | 242.28 | 419.18 | 876.11 | 148.91 | 0.00 | 0.00 | 0.00 |
August | 690.38 | 341.06 | 349.32 | 894.06 | 175.40 | 0.00 | 0.00 | 0.00 |
September | 612.16 | 293.57 | 318.59 | 769.15 | 240.48 | 0.00 | 0.00 | 0.00 |
October | 514.99 | 294.35 | 220.63 | 540.50 | 496.04 | 0.00 | 0.00 | 0.00 |
November | 422.57 | 256.56 | 166.02 | 393.61 | 598.63 | 0.00 | 0.00 | 0.00 |
December | 341.32 | 201.63 | 139.70 | 276.25 | 741.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.80 | 280.19 | 281.61 | 619.96 | 423.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.32 | 201.63 | 139.70 | 276.25 | 148.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.85 | 390.61 | 429.77 | 1077.69 | 741.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 551.87 | 0.00 | 551.87 | 106.51 | 2626.51 | 0.00 | 0.00 | 0.00 |
February | 693.63 | 0.00 | 693.63 | 140.47 | 2634.66 | 0.00 | 0.00 | 0.00 |
March | 943.80 | 0.00 | 943.80 | 434.03 | 2008.11 | 0.00 | 0.00 | 0.00 |
April | 1185.28 | 6.58 | 1178.71 | 648.41 | 1731.48 | 0.00 | 0.00 | 0.00 |
May | 1619.17 | 53.52 | 1565.64 | 1444.69 | 1036.85 | 0.00 | 0.00 | 0.00 |
June | 1775.53 | 196.85 | 1578.68 | 2330.74 | 574.72 | 0.00 | 0.00 | 0.00 |
July | 1679.17 | 108.70 | 1570.47 | 2231.07 | 544.12 | 0.00 | 0.00 | 0.00 |
August | 1336.49 | 31.62 | 1304.87 | 1699.89 | 620.82 | 0.00 | 0.00 | 0.00 |
September | 1122.65 | 0.26 | 1122.39 | 1263.35 | 953.26 | 0.00 | 0.00 | 0.00 |
October | 804.09 | 0.00 | 804.09 | 449.73 | 1974.55 | 0.00 | 0.00 | 0.00 |
November | 610.41 | 0.00 | 610.41 | 177.42 | 2369.92 | 0.00 | 0.00 | 0.00 |
December | 516.34 | 0.00 | 516.34 | 94.52 | 2919.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1071.83 | 33.20 | 1038.62 | 922.75 | 1661.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.34 | 0.00 | 516.34 | 94.52 | 544.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1775.53 | 196.85 | 1578.68 | 2330.74 | 2919.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1152.04 | 706.00 | 446.03 | 1012.70 | 1643.35 | 0.00 | 0.00 | 0.00 |
February | 1530.35 | 966.11 | 564.25 | 1420.93 | 1684.88 | 0.00 | 0.00 | 0.00 |
March | 1847.09 | 1077.39 | 769.70 | 1843.94 | 1287.06 | 0.00 | 0.00 | 0.00 |
April | 1894.30 | 922.74 | 971.55 | 1849.31 | 1121.69 | 0.00 | 0.00 | 0.00 |
May | 2214.40 | 924.96 | 1289.44 | 2467.50 | 690.97 | 0.00 | 0.00 | 0.00 |
June | 2701.80 | 1418.37 | 1283.43 | 3567.62 | 380.77 | 0.00 | 0.00 | 0.00 |
July | 2456.15 | 1169.56 | 1286.59 | 3271.81 | 361.10 | 0.00 | 0.00 | 0.00 |
August | 2477.36 | 1364.44 | 1112.92 | 3277.34 | 412.09 | 0.00 | 0.00 | 0.00 |
September | 2061.29 | 1119.75 | 941.54 | 2590.07 | 606.29 | 0.00 | 0.00 | 0.00 |
October | 1492.79 | 817.96 | 674.83 | 1549.90 | 1283.72 | 0.00 | 0.00 | 0.00 |
November | 1161.94 | 656.04 | 505.90 | 1078.43 | 1519.75 | 0.00 | 0.00 | 0.00 |
December | 1005.93 | 579.49 | 426.44 | 849.56 | 1845.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1834.11 | 976.42 | 857.69 | 2067.96 | 1066.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1005.93 | 579.49 | 426.44 | 849.56 | 361.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2701.80 | 1418.37 | 1289.44 | 3567.62 | 1845.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5289.02 | 4350.79 | 938.23 | 5909.93 | 2479.51 | 0.00 | 0.00 | 0.00 |
February | 5073.15 | 4044.64 | 1028.51 | 5620.36 | 2541.16 | 0.00 | 0.00 | 0.00 |
March | 3740.32 | 2460.92 | 1279.40 | 4200.67 | 2014.17 | 0.00 | 0.00 | 0.00 |
April | 2422.51 | 974.10 | 1448.41 | 2483.76 | 1798.08 | 0.00 | 0.00 | 0.00 |
May | 2219.96 | 406.90 | 1813.06 | 2492.36 | 1137.82 | 0.00 | 0.00 | 0.00 |
June | 2046.73 | 374.08 | 1672.65 | 2909.22 | 626.01 | 0.00 | 0.00 | 0.00 |
July | 2130.60 | 381.53 | 1749.07 | 3033.71 | 583.11 | 0.00 | 0.00 | 0.00 |
August | 2712.69 | 1134.01 | 1578.68 | 3867.33 | 665.44 | 0.00 | 0.00 | 0.00 |
September | 3490.14 | 1947.48 | 1542.66 | 4656.83 | 1007.10 | 0.00 | 0.00 | 0.00 |
October | 4173.18 | 2960.97 | 1212.21 | 4950.06 | 2019.04 | 0.00 | 0.00 | 0.00 |
November | 5084.44 | 4053.04 | 1031.40 | 5808.96 | 2346.73 | 0.00 | 0.00 | 0.00 |
December | 4862.05 | 3935.28 | 926.77 | 5332.05 | 2720.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3595.41 | 2241.79 | 1353.62 | 4264.39 | 1656.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2046.73 | 374.08 | 926.77 | 2483.76 | 583.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5289.02 | 4350.79 | 1813.06 | 5909.93 | 2720.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1225.51 | 776.55 | 448.96 | 1155.42 | 1721.38 | 0.00 | 0.00 | 0.00 |
February | 1477.79 | 915.79 | 562.00 | 1382.89 | 1746.59 | 0.00 | 0.00 | 0.00 |
March | 1730.40 | 954.70 | 775.70 | 1717.29 | 1346.90 | 0.00 | 0.00 | 0.00 |
April | 1629.25 | 689.80 | 939.45 | 1541.65 | 1183.19 | 0.00 | 0.00 | 0.00 |
May | 1991.36 | 702.03 | 1289.33 | 2228.50 | 753.16 | 0.00 | 0.00 | 0.00 |
June | 2435.56 | 1171.84 | 1263.72 | 3257.81 | 447.42 | 0.00 | 0.00 | 0.00 |
July | 1984.40 | 726.85 | 1257.55 | 2666.33 | 407.61 | 0.00 | 0.00 | 0.00 |
August | 2071.15 | 1023.18 | 1047.97 | 2740.30 | 457.68 | 0.00 | 0.00 | 0.00 |
September | 1836.49 | 880.72 | 955.77 | 2331.36 | 667.79 | 0.00 | 0.00 | 0.00 |
October | 1544.98 | 883.07 | 661.91 | 1659.36 | 1337.87 | 0.00 | 0.00 | 0.00 |
November | 1267.73 | 769.67 | 498.06 | 1229.61 | 1578.90 | 0.00 | 0.00 | 0.00 |
December | 1023.98 | 604.89 | 419.09 | 883.78 | 1894.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.41 | 840.58 | 844.83 | 1901.68 | 1125.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1023.98 | 604.89 | 419.09 | 883.78 | 407.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2435.56 | 1171.84 | 1289.33 | 3257.81 | 1894.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 551.87 | 0.00 | 551.87 | 132.82 | 2414.78 | 0.00 | 0.00 | 0.00 |
February | 693.63 | 0.00 | 693.63 | 163.46 | 2465.90 | 0.00 | 0.00 | 0.00 |
March | 943.80 | 0.00 | 943.80 | 464.07 | 1870.74 | 0.00 | 0.00 | 0.00 |
April | 1185.28 | 6.58 | 1178.71 | 684.99 | 1573.01 | 0.00 | 0.00 | 0.00 |
May | 1619.17 | 53.52 | 1565.64 | 1481.53 | 977.88 | 0.00 | 0.00 | 0.00 |
June | 1775.53 | 196.85 | 1578.68 | 2320.56 | 569.05 | 0.00 | 0.00 | 0.00 |
July | 1679.17 | 108.70 | 1570.47 | 2220.01 | 539.26 | 0.00 | 0.00 | 0.00 |
August | 1336.49 | 31.62 | 1304.87 | 1694.11 | 609.81 | 0.00 | 0.00 | 0.00 |
September | 1122.65 | 0.26 | 1122.39 | 1275.26 | 908.43 | 0.00 | 0.00 | 0.00 |
October | 804.09 | 0.00 | 804.09 | 485.93 | 1814.80 | 0.00 | 0.00 | 0.00 |
November | 610.41 | 0.00 | 610.41 | 211.59 | 2172.05 | 0.00 | 0.00 | 0.00 |
December | 516.34 | 0.00 | 516.34 | 110.61 | 2743.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1071.83 | 33.20 | 1038.62 | 941.40 | 1550.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.34 | 0.00 | 516.34 | 110.61 | 539.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1775.53 | 196.85 | 1578.68 | 2320.56 | 2743.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1152.04 | 706.00 | 446.03 | 1046.74 | 1516.53 | 0.00 | 0.00 | 0.00 |
February | 1530.35 | 966.11 | 564.25 | 1446.01 | 1586.81 | 0.00 | 0.00 | 0.00 |
March | 1847.09 | 1077.39 | 769.70 | 1861.72 | 1212.36 | 0.00 | 0.00 | 0.00 |
April | 1894.30 | 922.74 | 971.55 | 1870.15 | 1030.57 | 0.00 | 0.00 | 0.00 |
May | 2214.40 | 924.96 | 1289.44 | 2479.73 | 662.30 | 0.00 | 0.00 | 0.00 |
June | 2701.80 | 1418.37 | 1283.43 | 3553.15 | 381.92 | 0.00 | 0.00 | 0.00 |
July | 2456.15 | 1169.56 | 1286.59 | 3258.07 | 361.87 | 0.00 | 0.00 | 0.00 |
August | 2477.36 | 1364.44 | 1112.92 | 3266.25 | 411.75 | 0.00 | 0.00 | 0.00 |
September | 2061.29 | 1119.75 | 941.54 | 2589.63 | 590.21 | 0.00 | 0.00 | 0.00 |
October | 1492.79 | 817.96 | 674.83 | 1566.74 | 1198.74 | 0.00 | 0.00 | 0.00 |
November | 1161.94 | 656.04 | 505.90 | 1108.81 | 1409.94 | 0.00 | 0.00 | 0.00 |
December | 1005.93 | 579.49 | 426.44 | 872.93 | 1742.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1834.11 | 976.42 | 857.69 | 2079.61 | 1005.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1005.93 | 579.49 | 426.44 | 872.93 | 361.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2701.80 | 1418.37 | 1289.44 | 3553.15 | 1742.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 5289.02 | 4350.79 | 938.23 | 5976.92 | 2278.91 | 0.00 | 0.00 | 0.00 |
February | 5073.15 | 4044.64 | 1028.51 | 5658.99 | 2382.88 | 0.00 | 0.00 | 0.00 |
March | 3740.32 | 2460.92 | 1279.40 | 4226.88 | 1888.21 | 0.00 | 0.00 | 0.00 |
April | 2422.51 | 974.10 | 1448.41 | 2511.73 | 1647.56 | 0.00 | 0.00 | 0.00 |
May | 2219.96 | 406.90 | 1813.06 | 2514.27 | 1077.63 | 0.00 | 0.00 | 0.00 |
June | 2046.73 | 374.08 | 1672.65 | 2897.04 | 619.13 | 0.00 | 0.00 | 0.00 |
July | 2130.60 | 381.53 | 1749.07 | 3021.04 | 577.34 | 0.00 | 0.00 | 0.00 |
August | 2712.69 | 1134.01 | 1578.68 | 3856.12 | 657.33 | 0.00 | 0.00 | 0.00 |
September | 3490.14 | 1947.48 | 1542.66 | 4656.94 | 973.44 | 0.00 | 0.00 | 0.00 |
October | 4173.18 | 2960.97 | 1212.21 | 4974.11 | 1883.60 | 0.00 | 0.00 | 0.00 |
November | 5084.44 | 4053.04 | 1031.40 | 5854.16 | 2180.24 | 0.00 | 0.00 | 0.00 |
December | 4862.05 | 3935.28 | 926.77 | 5380.96 | 2549.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3595.41 | 2241.79 | 1353.62 | 4286.32 | 1555.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2046.73 | 374.08 | 926.77 | 2511.73 | 577.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5289.02 | 4350.79 | 1813.06 | 5976.92 | 2549.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1225.51 | 776.55 | 448.96 | 1176.76 | 1596.70 | 0.00 | 0.00 | 0.00 |
February | 1477.79 | 915.79 | 562.00 | 1395.02 | 1651.65 | 0.00 | 0.00 | 0.00 |
March | 1730.40 | 954.70 | 775.70 | 1727.91 | 1270.81 | 0.00 | 0.00 | 0.00 |
April | 1629.25 | 689.80 | 939.45 | 1555.83 | 1094.34 | 0.00 | 0.00 | 0.00 |
May | 1991.36 | 702.03 | 1289.33 | 2238.99 | 719.34 | 0.00 | 0.00 | 0.00 |
June | 2435.56 | 1171.84 | 1263.72 | 3248.63 | 444.07 | 0.00 | 0.00 | 0.00 |
July | 1984.40 | 726.85 | 1257.55 | 2657.91 | 403.40 | 0.00 | 0.00 | 0.00 |
August | 2071.15 | 1023.18 | 1047.97 | 2734.25 | 452.91 | 0.00 | 0.00 | 0.00 |
September | 1836.49 | 880.72 | 955.77 | 2333.29 | 646.67 | 0.00 | 0.00 | 0.00 |
October | 1544.98 | 883.07 | 661.91 | 1671.87 | 1256.25 | 0.00 | 0.00 | 0.00 |
November | 1267.73 | 769.67 | 498.06 | 1247.23 | 1476.98 | 0.00 | 0.00 | 0.00 |
December | 1023.98 | 604.89 | 419.09 | 896.29 | 1794.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1685.41 | 840.58 | 844.83 | 1909.13 | 1064.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1023.98 | 604.89 | 419.09 | 896.29 | 403.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2435.56 | 1171.84 | 1289.33 | 3248.63 | 1794.18 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295625E+09 | 0.00 | 0.295625E+09 | 43130320.70 | 0.153562E+10 |
February | 0.335607E+09 | 0.00 | 0.335607E+09 | 51081870.86 | 0.139476E+10 |
March | 0.505577E+09 | 0.00 | 0.505577E+09 | 0.204498E+09 | 0.118695E+10 |
April | 0.614450E+09 | 3408681.96 | 0.611041E+09 | 0.307019E+09 | 0.101465E+10 |
May | 0.867355E+09 | 28671082.05 | 0.838684E+09 | 0.759948E+09 | 0.583824E+09 |
June | 0.920434E+09 | 0.102044E+09 | 0.818390E+09 | 0.120197E+10 | 0.304736E+09 |
July | 0.899496E+09 | 58225575.18 | 0.841270E+09 | 0.118772E+10 | 0.295722E+09 |
August | 0.715932E+09 | 16936393.65 | 0.698995E+09 | 0.896959E+09 | 0.341424E+09 |
September | 0.581983E+09 | 136696.43 | 0.581846E+09 | 0.643311E+09 | 0.520351E+09 |
October | 0.430735E+09 | 0.00 | 0.430735E+09 | 0.219721E+09 | 0.114871E+10 |
November | 0.316435E+09 | 0.00 | 0.316435E+09 | 71602171.32 | 0.135808E+10 |
December | 0.276594E+09 | 0.00 | 0.276594E+09 | 32880570.22 | 0.174784E+10 |
Annual Sum or Average | 0.676022E+10 | 0.209423E+09 | 0.655080E+10 | 0.561984E+10 | 0.114327E+11 |
Minimum of Months | 0.276594E+09 | 0.00 | 0.276594E+09 | 32880570.22 | 0.295722E+09 |
Maximum of Months | 0.920434E+09 | 0.102044E+09 | 0.841270E+09 | 0.120197E+10 | 0.174784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295621E+09 | 0.00 | 0.295621E+09 | 43128733.96 | 0.153562E+10 |
February | 0.335603E+09 | 0.00 | 0.335603E+09 | 51080295.67 | 0.139476E+10 |
March | 0.505571E+09 | 0.00 | 0.505571E+09 | 0.204493E+09 | 0.118695E+10 |
April | 0.614441E+09 | 3408607.02 | 0.611033E+09 | 0.307012E+09 | 0.101466E+10 |
May | 0.867342E+09 | 28670451.75 | 0.838672E+09 | 0.759933E+09 | 0.583823E+09 |
June | 0.920421E+09 | 0.102042E+09 | 0.818379E+09 | 0.120195E+10 | 0.304734E+09 |
July | 0.899483E+09 | 58224295.16 | 0.841258E+09 | 0.118771E+10 | 0.295721E+09 |
August | 0.715923E+09 | 16936021.33 | 0.698987E+09 | 0.896949E+09 | 0.341422E+09 |
September | 0.581975E+09 | 136693.42 | 0.581839E+09 | 0.643303E+09 | 0.520349E+09 |
October | 0.430729E+09 | 0.00 | 0.430729E+09 | 0.219717E+09 | 0.114871E+10 |
November | 0.316431E+09 | 0.00 | 0.316431E+09 | 71600330.39 | 0.135808E+10 |
December | 0.276590E+09 | 0.00 | 0.276590E+09 | 32879658.06 | 0.174784E+10 |
Annual Sum or Average | 0.676013E+10 | 0.209418E+09 | 0.655071E+10 | 0.561976E+10 | 0.114327E+11 |
Minimum of Months | 0.276590E+09 | 0.00 | 0.276590E+09 | 32879658.06 | 0.295721E+09 |
Maximum of Months | 0.920421E+09 | 0.102042E+09 | 0.841258E+09 | 0.120195E+10 | 0.174784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295622E+09 | 0.00 | 0.295622E+09 | 43129262.88 | 0.153562E+10 |
February | 0.335604E+09 | 0.00 | 0.335604E+09 | 51080820.73 | 0.139476E+10 |
March | 0.505573E+09 | 0.00 | 0.505573E+09 | 0.204495E+09 | 0.118695E+10 |
April | 0.614444E+09 | 3408632.00 | 0.611036E+09 | 0.307014E+09 | 0.101466E+10 |
May | 0.867347E+09 | 28670661.85 | 0.838676E+09 | 0.759938E+09 | 0.583823E+09 |
June | 0.920426E+09 | 0.102043E+09 | 0.818383E+09 | 0.120196E+10 | 0.304735E+09 |
July | 0.899487E+09 | 58224721.83 | 0.841262E+09 | 0.118771E+10 | 0.295721E+09 |
August | 0.715926E+09 | 16936145.44 | 0.698989E+09 | 0.896952E+09 | 0.341423E+09 |
September | 0.581978E+09 | 136694.43 | 0.581841E+09 | 0.643306E+09 | 0.520350E+09 |
October | 0.430731E+09 | 0.00 | 0.430731E+09 | 0.219718E+09 | 0.114871E+10 |
November | 0.316432E+09 | 0.00 | 0.316432E+09 | 71600944.04 | 0.135808E+10 |
December | 0.276591E+09 | 0.00 | 0.276591E+09 | 32879962.11 | 0.174784E+10 |
Annual Sum or Average | 0.676016E+10 | 0.209420E+09 | 0.655074E+10 | 0.561978E+10 | 0.114327E+11 |
Minimum of Months | 0.276591E+09 | 0.00 | 0.276591E+09 | 32879962.11 | 0.295721E+09 |
Maximum of Months | 0.920426E+09 | 0.102043E+09 | 0.841262E+09 | 0.120196E+10 | 0.174784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295621E+09 | 0.00 | 0.295621E+09 | 43128733.96 | 0.153562E+10 |
February | 0.335603E+09 | 0.00 | 0.335603E+09 | 51080295.67 | 0.139476E+10 |
March | 0.505571E+09 | 0.00 | 0.505571E+09 | 0.204493E+09 | 0.118695E+10 |
April | 0.614441E+09 | 3408607.02 | 0.611033E+09 | 0.307012E+09 | 0.101466E+10 |
May | 0.867342E+09 | 28670451.75 | 0.838672E+09 | 0.759933E+09 | 0.583823E+09 |
June | 0.920421E+09 | 0.102042E+09 | 0.818379E+09 | 0.120195E+10 | 0.304734E+09 |
July | 0.899483E+09 | 58224295.16 | 0.841258E+09 | 0.118771E+10 | 0.295721E+09 |
August | 0.715923E+09 | 16936021.33 | 0.698987E+09 | 0.896949E+09 | 0.341422E+09 |
September | 0.581975E+09 | 136693.42 | 0.581839E+09 | 0.643303E+09 | 0.520349E+09 |
October | 0.430729E+09 | 0.00 | 0.430729E+09 | 0.219717E+09 | 0.114871E+10 |
November | 0.316431E+09 | 0.00 | 0.316431E+09 | 71600330.39 | 0.135808E+10 |
December | 0.276590E+09 | 0.00 | 0.276590E+09 | 32879658.06 | 0.174784E+10 |
Annual Sum or Average | 0.676013E+10 | 0.209418E+09 | 0.655071E+10 | 0.561976E+10 | 0.114327E+11 |
Minimum of Months | 0.276590E+09 | 0.00 | 0.276590E+09 | 32879658.06 | 0.295721E+09 |
Maximum of Months | 0.920421E+09 | 0.102042E+09 | 0.841258E+09 | 0.120195E+10 | 0.174784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295610E+09 | 0.00 | 0.295610E+09 | 43127260.13 | 0.153556E+10 |
February | 0.335590E+09 | 0.00 | 0.335590E+09 | 51078499.43 | 0.139471E+10 |
March | 0.505552E+09 | 0.00 | 0.505552E+09 | 0.204486E+09 | 0.118690E+10 |
April | 0.614418E+09 | 3408482.13 | 0.611010E+09 | 0.307001E+09 | 0.101461E+10 |
May | 0.867309E+09 | 28669401.25 | 0.838640E+09 | 0.759905E+09 | 0.583800E+09 |
June | 0.920386E+09 | 0.102038E+09 | 0.818348E+09 | 0.120191E+10 | 0.304722E+09 |
July | 0.899449E+09 | 58222161.79 | 0.841227E+09 | 0.118766E+10 | 0.295709E+09 |
August | 0.715895E+09 | 16935400.78 | 0.698960E+09 | 0.896915E+09 | 0.341409E+09 |
September | 0.581953E+09 | 136688.41 | 0.581816E+09 | 0.643279E+09 | 0.520329E+09 |
October | 0.430713E+09 | 0.00 | 0.430713E+09 | 0.219708E+09 | 0.114867E+10 |
November | 0.316419E+09 | 0.00 | 0.316419E+09 | 71597751.39 | 0.135803E+10 |
December | 0.276580E+09 | 0.00 | 0.276580E+09 | 32878484.88 | 0.174776E+10 |
Annual Sum or Average | 0.675987E+10 | 0.209410E+09 | 0.655046E+10 | 0.561954E+10 | 0.114322E+11 |
Minimum of Months | 0.276580E+09 | 0.00 | 0.276580E+09 | 32878484.88 | 0.295709E+09 |
Maximum of Months | 0.920386E+09 | 0.102038E+09 | 0.841227E+09 | 0.120191E+10 | 0.174776E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102855E+10 | 0.630326E+09 | 0.398223E+09 | 0.884260E+09 | 0.156294E+10 |
February | 0.123409E+10 | 0.779076E+09 | 0.455013E+09 | 0.113526E+10 | 0.144729E+10 |
March | 0.164910E+10 | 0.961907E+09 | 0.687196E+09 | 0.163907E+10 | 0.122487E+10 |
April | 0.163669E+10 | 0.797260E+09 | 0.839429E+09 | 0.159075E+10 | 0.104755E+10 |
May | 0.197704E+10 | 0.825816E+09 | 0.115122E+10 | 0.220632E+10 | 0.638684E+09 |
June | 0.233438E+10 | 0.122549E+10 | 0.110889E+10 | 0.309666E+10 | 0.326873E+09 |
July | 0.219287E+10 | 0.104419E+10 | 0.114868E+10 | 0.293713E+10 | 0.308512E+09 |
August | 0.221181E+10 | 0.121819E+10 | 0.993625E+09 | 0.294296E+10 | 0.342620E+09 |
September | 0.178097E+10 | 0.967476E+09 | 0.813499E+09 | 0.224279E+10 | 0.540659E+09 |
October | 0.133277E+10 | 0.730283E+09 | 0.602491E+09 | 0.137790E+10 | 0.121096E+10 |
November | 0.100393E+10 | 0.566828E+09 | 0.437101E+09 | 0.915322E+09 | 0.139945E+10 |
December | 0.898105E+09 | 0.517373E+09 | 0.380733E+09 | 0.734584E+09 | 0.177444E+10 |
Annual Sum or Average | 0.192803E+11 | 0.102642E+11 | 0.901610E+10 | 0.217030E+11 | 0.118249E+11 |
Minimum of Months | 0.898105E+09 | 0.517373E+09 | 0.380733E+09 | 0.734584E+09 | 0.308512E+09 |
Maximum of Months | 0.233438E+10 | 0.122549E+10 | 0.115122E+10 | 0.309666E+10 | 0.177444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102855E+10 | 0.630326E+09 | 0.398223E+09 | 0.884260E+09 | 0.156294E+10 |
February | 0.123409E+10 | 0.779076E+09 | 0.455013E+09 | 0.113526E+10 | 0.144729E+10 |
March | 0.164910E+10 | 0.961907E+09 | 0.687196E+09 | 0.163907E+10 | 0.122487E+10 |
April | 0.163669E+10 | 0.797260E+09 | 0.839429E+09 | 0.159075E+10 | 0.104755E+10 |
May | 0.197704E+10 | 0.825816E+09 | 0.115122E+10 | 0.220632E+10 | 0.638684E+09 |
June | 0.233438E+10 | 0.122549E+10 | 0.110889E+10 | 0.309666E+10 | 0.326873E+09 |
July | 0.219287E+10 | 0.104419E+10 | 0.114868E+10 | 0.293713E+10 | 0.308512E+09 |
August | 0.221181E+10 | 0.121819E+10 | 0.993625E+09 | 0.294296E+10 | 0.342620E+09 |
September | 0.178097E+10 | 0.967476E+09 | 0.813499E+09 | 0.224279E+10 | 0.540659E+09 |
October | 0.133277E+10 | 0.730283E+09 | 0.602491E+09 | 0.137790E+10 | 0.121096E+10 |
November | 0.100393E+10 | 0.566828E+09 | 0.437101E+09 | 0.915322E+09 | 0.139945E+10 |
December | 0.898105E+09 | 0.517373E+09 | 0.380733E+09 | 0.734584E+09 | 0.177444E+10 |
Annual Sum or Average | 0.192803E+11 | 0.102642E+11 | 0.901610E+10 | 0.217030E+11 | 0.118249E+11 |
Minimum of Months | 0.898105E+09 | 0.517373E+09 | 0.380733E+09 | 0.734584E+09 | 0.308512E+09 |
Maximum of Months | 0.233438E+10 | 0.122549E+10 | 0.115122E+10 | 0.309666E+10 | 0.177444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102853E+10 | 0.630315E+09 | 0.398216E+09 | 0.884244E+09 | 0.156291E+10 |
February | 0.123407E+10 | 0.779062E+09 | 0.455005E+09 | 0.113524E+10 | 0.144727E+10 |
March | 0.164907E+10 | 0.961889E+09 | 0.687183E+09 | 0.163904E+10 | 0.122485E+10 |
April | 0.163666E+10 | 0.797245E+09 | 0.839413E+09 | 0.159072E+10 | 0.104753E+10 |
May | 0.197700E+10 | 0.825801E+09 | 0.115120E+10 | 0.220628E+10 | 0.638672E+09 |
June | 0.233433E+10 | 0.122546E+10 | 0.110887E+10 | 0.309660E+10 | 0.326867E+09 |
July | 0.219283E+10 | 0.104417E+10 | 0.114866E+10 | 0.293708E+10 | 0.308506E+09 |
August | 0.221177E+10 | 0.121816E+10 | 0.993607E+09 | 0.294291E+10 | 0.342613E+09 |
September | 0.178094E+10 | 0.967458E+09 | 0.813484E+09 | 0.224275E+10 | 0.540649E+09 |
October | 0.133275E+10 | 0.730269E+09 | 0.602480E+09 | 0.137787E+10 | 0.121094E+10 |
November | 0.100391E+10 | 0.566818E+09 | 0.437093E+09 | 0.915305E+09 | 0.139943E+10 |
December | 0.898089E+09 | 0.517363E+09 | 0.380726E+09 | 0.734571E+09 | 0.177441E+10 |
Annual Sum or Average | 0.192800E+11 | 0.102640E+11 | 0.901594E+10 | 0.217026E+11 | 0.118246E+11 |
Minimum of Months | 0.898089E+09 | 0.517363E+09 | 0.380726E+09 | 0.734571E+09 | 0.308506E+09 |
Maximum of Months | 0.233433E+10 | 0.122546E+10 | 0.115120E+10 | 0.309660E+10 | 0.177441E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283317E+10 | 0.233058E+10 | 0.502585E+09 | 0.318285E+10 | 0.133798E+10 |
February | 0.245455E+10 | 0.195692E+10 | 0.497631E+09 | 0.273672E+10 | 0.125641E+10 |
March | 0.200358E+10 | 0.131824E+10 | 0.685342E+09 | 0.225916E+10 | 0.111840E+10 |
April | 0.125581E+10 | 0.504963E+09 | 0.750846E+09 | 0.128429E+10 | 0.989695E+09 |
May | 0.118917E+10 | 0.217965E+09 | 0.971208E+09 | 0.133618E+10 | 0.623844E+09 |
June | 0.106101E+10 | 0.193922E+09 | 0.867093E+09 | 0.150629E+10 | 0.329672E+09 |
July | 0.114131E+10 | 0.204374E+09 | 0.936931E+09 | 0.162343E+10 | 0.311971E+09 |
August | 0.145311E+10 | 0.607451E+09 | 0.845660E+09 | 0.207285E+10 | 0.353695E+09 |
September | 0.180926E+10 | 0.100955E+10 | 0.799706E+09 | 0.242542E+10 | 0.529312E+09 |
October | 0.223545E+10 | 0.158610E+10 | 0.649351E+09 | 0.266482E+10 | 0.110254E+10 |
November | 0.263572E+10 | 0.210105E+10 | 0.534673E+09 | 0.302638E+10 | 0.123984E+10 |
December | 0.260445E+10 | 0.210801E+10 | 0.496447E+09 | 0.286003E+10 | 0.151509E+10 |
Annual Sum or Average | 0.226766E+11 | 0.141391E+11 | 0.853747E+10 | 0.269784E+11 | 0.107084E+11 |
Minimum of Months | 0.106101E+10 | 0.193922E+09 | 0.496447E+09 | 0.128429E+10 | 0.311971E+09 |
Maximum of Months | 0.283317E+10 | 0.233058E+10 | 0.971208E+09 | 0.318285E+10 | 0.151509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283315E+10 | 0.233056E+10 | 0.502583E+09 | 0.318283E+10 | 0.133798E+10 |
February | 0.245453E+10 | 0.195690E+10 | 0.497629E+09 | 0.273670E+10 | 0.125641E+10 |
March | 0.200357E+10 | 0.131823E+10 | 0.685339E+09 | 0.225914E+10 | 0.111840E+10 |
April | 0.125580E+10 | 0.504959E+09 | 0.750842E+09 | 0.128428E+10 | 0.989696E+09 |
May | 0.118917E+10 | 0.217964E+09 | 0.971203E+09 | 0.133617E+10 | 0.623844E+09 |
June | 0.106101E+10 | 0.193920E+09 | 0.867089E+09 | 0.150628E+10 | 0.329671E+09 |
July | 0.114130E+10 | 0.204373E+09 | 0.936927E+09 | 0.162342E+10 | 0.311970E+09 |
August | 0.145310E+10 | 0.607447E+09 | 0.845656E+09 | 0.207284E+10 | 0.353695E+09 |
September | 0.180924E+10 | 0.100954E+10 | 0.799702E+09 | 0.242540E+10 | 0.529311E+09 |
October | 0.223543E+10 | 0.158609E+10 | 0.649348E+09 | 0.266480E+10 | 0.110254E+10 |
November | 0.263571E+10 | 0.210104E+10 | 0.534670E+09 | 0.302636E+10 | 0.123984E+10 |
December | 0.260443E+10 | 0.210799E+10 | 0.496444E+09 | 0.286000E+10 | 0.151509E+10 |
Annual Sum or Average | 0.226764E+11 | 0.141390E+11 | 0.853743E+10 | 0.269782E+11 | 0.107084E+11 |
Minimum of Months | 0.106101E+10 | 0.193920E+09 | 0.496444E+09 | 0.128428E+10 | 0.311970E+09 |
Maximum of Months | 0.283315E+10 | 0.233056E+10 | 0.971203E+09 | 0.318283E+10 | 0.151509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283317E+10 | 0.233058E+10 | 0.502585E+09 | 0.318285E+10 | 0.133798E+10 |
February | 0.245455E+10 | 0.195692E+10 | 0.497631E+09 | 0.273672E+10 | 0.125641E+10 |
March | 0.200358E+10 | 0.131824E+10 | 0.685342E+09 | 0.225916E+10 | 0.111840E+10 |
April | 0.125581E+10 | 0.504963E+09 | 0.750846E+09 | 0.128429E+10 | 0.989695E+09 |
May | 0.118917E+10 | 0.217965E+09 | 0.971208E+09 | 0.133618E+10 | 0.623844E+09 |
June | 0.106101E+10 | 0.193922E+09 | 0.867093E+09 | 0.150629E+10 | 0.329672E+09 |
July | 0.114131E+10 | 0.204374E+09 | 0.936931E+09 | 0.162343E+10 | 0.311971E+09 |
August | 0.145311E+10 | 0.607451E+09 | 0.845660E+09 | 0.207285E+10 | 0.353695E+09 |
September | 0.180926E+10 | 0.100955E+10 | 0.799706E+09 | 0.242542E+10 | 0.529312E+09 |
October | 0.223545E+10 | 0.158610E+10 | 0.649351E+09 | 0.266482E+10 | 0.110254E+10 |
November | 0.263572E+10 | 0.210105E+10 | 0.534673E+09 | 0.302638E+10 | 0.123984E+10 |
December | 0.260445E+10 | 0.210801E+10 | 0.496447E+09 | 0.286003E+10 | 0.151509E+10 |
Annual Sum or Average | 0.226766E+11 | 0.141391E+11 | 0.853747E+10 | 0.269784E+11 | 0.107084E+11 |
Minimum of Months | 0.106101E+10 | 0.193922E+09 | 0.496447E+09 | 0.128429E+10 | 0.311971E+09 |
Maximum of Months | 0.283317E+10 | 0.233058E+10 | 0.971208E+09 | 0.318285E+10 | 0.151509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283315E+10 | 0.233056E+10 | 0.502583E+09 | 0.318283E+10 | 0.133798E+10 |
February | 0.245453E+10 | 0.195690E+10 | 0.497629E+09 | 0.273670E+10 | 0.125641E+10 |
March | 0.200357E+10 | 0.131823E+10 | 0.685339E+09 | 0.225914E+10 | 0.111840E+10 |
April | 0.125580E+10 | 0.504959E+09 | 0.750842E+09 | 0.128428E+10 | 0.989696E+09 |
May | 0.118917E+10 | 0.217964E+09 | 0.971203E+09 | 0.133617E+10 | 0.623844E+09 |
June | 0.106101E+10 | 0.193920E+09 | 0.867089E+09 | 0.150628E+10 | 0.329671E+09 |
July | 0.114130E+10 | 0.204373E+09 | 0.936927E+09 | 0.162342E+10 | 0.311970E+09 |
August | 0.145310E+10 | 0.607447E+09 | 0.845656E+09 | 0.207284E+10 | 0.353695E+09 |
September | 0.180924E+10 | 0.100954E+10 | 0.799702E+09 | 0.242540E+10 | 0.529311E+09 |
October | 0.223543E+10 | 0.158609E+10 | 0.649348E+09 | 0.266480E+10 | 0.110254E+10 |
November | 0.263571E+10 | 0.210104E+10 | 0.534670E+09 | 0.302636E+10 | 0.123984E+10 |
December | 0.260443E+10 | 0.210799E+10 | 0.496444E+09 | 0.286000E+10 | 0.151509E+10 |
Annual Sum or Average | 0.226764E+11 | 0.141390E+11 | 0.853743E+10 | 0.269782E+11 | 0.107084E+11 |
Minimum of Months | 0.106101E+10 | 0.193920E+09 | 0.496444E+09 | 0.128428E+10 | 0.311970E+09 |
Maximum of Months | 0.283315E+10 | 0.233056E+10 | 0.971203E+09 | 0.318283E+10 | 0.151509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283304E+10 | 0.233048E+10 | 0.502564E+09 | 0.318271E+10 | 0.133792E+10 |
February | 0.245444E+10 | 0.195683E+10 | 0.497610E+09 | 0.273660E+10 | 0.125636E+10 |
March | 0.200349E+10 | 0.131818E+10 | 0.685313E+09 | 0.225906E+10 | 0.111836E+10 |
April | 0.125575E+10 | 0.504941E+09 | 0.750814E+09 | 0.128424E+10 | 0.989656E+09 |
May | 0.118912E+10 | 0.217956E+09 | 0.971167E+09 | 0.133612E+10 | 0.623819E+09 |
June | 0.106097E+10 | 0.193913E+09 | 0.867056E+09 | 0.150623E+10 | 0.329658E+09 |
July | 0.114126E+10 | 0.204365E+09 | 0.936891E+09 | 0.162336E+10 | 0.311958E+09 |
August | 0.145305E+10 | 0.607424E+09 | 0.845624E+09 | 0.207276E+10 | 0.353681E+09 |
September | 0.180918E+10 | 0.100951E+10 | 0.799671E+09 | 0.242531E+10 | 0.529290E+09 |
October | 0.223535E+10 | 0.158603E+10 | 0.649324E+09 | 0.266470E+10 | 0.110250E+10 |
November | 0.263561E+10 | 0.210096E+10 | 0.534650E+09 | 0.302625E+10 | 0.123979E+10 |
December | 0.260434E+10 | 0.210791E+10 | 0.496426E+09 | 0.285990E+10 | 0.151503E+10 |
Annual Sum or Average | 0.226756E+11 | 0.141385E+11 | 0.853711E+10 | 0.269772E+11 | 0.107080E+11 |
Minimum of Months | 0.106097E+10 | 0.193913E+09 | 0.496426E+09 | 0.128424E+10 | 0.311958E+09 |
Maximum of Months | 0.283304E+10 | 0.233048E+10 | 0.971167E+09 | 0.318271E+10 | 0.151503E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109415E+10 | 0.693311E+09 | 0.400836E+09 | 0.100545E+10 | 0.166894E+10 |
February | 0.119170E+10 | 0.738503E+09 | 0.453200E+09 | 0.108531E+10 | 0.156172E+10 |
March | 0.154491E+10 | 0.852364E+09 | 0.692551E+09 | 0.148636E+10 | 0.137787E+10 |
April | 0.140769E+10 | 0.595990E+09 | 0.811696E+09 | 0.127379E+10 | 0.124025E+10 |
May | 0.177790E+10 | 0.626778E+09 | 0.115113E+10 | 0.196415E+10 | 0.724971E+09 |
June | 0.210434E+10 | 0.101248E+10 | 0.109186E+10 | 0.279341E+10 | 0.415168E+09 |
July | 0.177169E+10 | 0.648938E+09 | 0.112275E+10 | 0.234660E+10 | 0.398858E+09 |
August | 0.184914E+10 | 0.913503E+09 | 0.935640E+09 | 0.239471E+10 | 0.469799E+09 |
September | 0.158674E+10 | 0.760950E+09 | 0.825795E+09 | 0.199367E+10 | 0.623329E+09 |
October | 0.137937E+10 | 0.788412E+09 | 0.590957E+09 | 0.144769E+10 | 0.132861E+10 |
November | 0.109533E+10 | 0.665003E+09 | 0.430330E+09 | 0.102026E+10 | 0.155168E+10 |
December | 0.914221E+09 | 0.540055E+09 | 0.374166E+09 | 0.739923E+09 | 0.198550E+10 |
Annual Sum or Average | 0.177172E+11 | 0.883629E+10 | 0.888091E+10 | 0.195513E+11 | 0.133467E+11 |
Minimum of Months | 0.914221E+09 | 0.540055E+09 | 0.374166E+09 | 0.739923E+09 | 0.398858E+09 |
Maximum of Months | 0.210434E+10 | 0.101248E+10 | 0.115113E+10 | 0.279341E+10 | 0.198550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109415E+10 | 0.693311E+09 | 0.400836E+09 | 0.100545E+10 | 0.166894E+10 |
February | 0.119170E+10 | 0.738503E+09 | 0.453200E+09 | 0.108531E+10 | 0.156172E+10 |
March | 0.154491E+10 | 0.852364E+09 | 0.692551E+09 | 0.148636E+10 | 0.137787E+10 |
April | 0.140769E+10 | 0.595990E+09 | 0.811696E+09 | 0.127379E+10 | 0.124025E+10 |
May | 0.177790E+10 | 0.626778E+09 | 0.115113E+10 | 0.196415E+10 | 0.724971E+09 |
June | 0.210434E+10 | 0.101248E+10 | 0.109186E+10 | 0.279341E+10 | 0.415168E+09 |
July | 0.177169E+10 | 0.648938E+09 | 0.112275E+10 | 0.234660E+10 | 0.398858E+09 |
August | 0.184914E+10 | 0.913503E+09 | 0.935640E+09 | 0.239471E+10 | 0.469799E+09 |
September | 0.158674E+10 | 0.760950E+09 | 0.825795E+09 | 0.199367E+10 | 0.623329E+09 |
October | 0.137937E+10 | 0.788412E+09 | 0.590957E+09 | 0.144769E+10 | 0.132861E+10 |
November | 0.109533E+10 | 0.665003E+09 | 0.430330E+09 | 0.102026E+10 | 0.155168E+10 |
December | 0.914221E+09 | 0.540055E+09 | 0.374166E+09 | 0.739923E+09 | 0.198550E+10 |
Annual Sum or Average | 0.177172E+11 | 0.883629E+10 | 0.888091E+10 | 0.195513E+11 | 0.133467E+11 |
Minimum of Months | 0.914221E+09 | 0.540055E+09 | 0.374166E+09 | 0.739923E+09 | 0.398858E+09 |
Maximum of Months | 0.210434E+10 | 0.101248E+10 | 0.115113E+10 | 0.279341E+10 | 0.198550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109413E+10 | 0.693298E+09 | 0.400828E+09 | 0.100544E+10 | 0.166891E+10 |
February | 0.119168E+10 | 0.738490E+09 | 0.453192E+09 | 0.108529E+10 | 0.156169E+10 |
March | 0.154489E+10 | 0.852348E+09 | 0.692538E+09 | 0.148633E+10 | 0.137784E+10 |
April | 0.140766E+10 | 0.595979E+09 | 0.811681E+09 | 0.127377E+10 | 0.124023E+10 |
May | 0.177787E+10 | 0.626766E+09 | 0.115111E+10 | 0.196412E+10 | 0.724958E+09 |
June | 0.210430E+10 | 0.101246E+10 | 0.109184E+10 | 0.279336E+10 | 0.415161E+09 |
July | 0.177166E+10 | 0.648926E+09 | 0.112273E+10 | 0.234656E+10 | 0.398851E+09 |
August | 0.184911E+10 | 0.913486E+09 | 0.935623E+09 | 0.239466E+10 | 0.469790E+09 |
September | 0.158672E+10 | 0.760936E+09 | 0.825780E+09 | 0.199363E+10 | 0.623317E+09 |
October | 0.137934E+10 | 0.788398E+09 | 0.590946E+09 | 0.144766E+10 | 0.132859E+10 |
November | 0.109531E+10 | 0.664991E+09 | 0.430323E+09 | 0.102024E+10 | 0.155165E+10 |
December | 0.914204E+09 | 0.540045E+09 | 0.374159E+09 | 0.739910E+09 | 0.198546E+10 |
Annual Sum or Average | 0.177169E+11 | 0.883613E+10 | 0.888075E+10 | 0.195510E+11 | 0.133464E+11 |
Minimum of Months | 0.914204E+09 | 0.540045E+09 | 0.374159E+09 | 0.739910E+09 | 0.398851E+09 |
Maximum of Months | 0.210430E+10 | 0.101246E+10 | 0.115111E+10 | 0.279336E+10 | 0.198546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147812E+10 | 0.00 | 0.147812E+10 | 0.285287E+09 | 0.703483E+10 |
February | 0.167803E+10 | 0.00 | 0.167803E+10 | 0.339815E+09 | 0.637378E+10 |
March | 0.252788E+10 | 0.00 | 0.252788E+10 | 0.116250E+10 | 0.537851E+10 |
April | 0.307225E+10 | 17043518.41 | 0.305521E+10 | 0.168069E+10 | 0.448799E+10 |
May | 0.433678E+10 | 0.143356E+09 | 0.419342E+10 | 0.386946E+10 | 0.277709E+10 |
June | 0.460217E+10 | 0.510225E+09 | 0.409194E+10 | 0.604128E+10 | 0.148969E+10 |
July | 0.449748E+10 | 0.291130E+09 | 0.420635E+10 | 0.597569E+10 | 0.145736E+10 |
August | 0.357965E+10 | 84682507.92 | 0.349497E+10 | 0.455299E+10 | 0.166281E+10 |
September | 0.290991E+10 | 683486.50 | 0.290923E+10 | 0.327460E+10 | 0.247084E+10 |
October | 0.215367E+10 | 0.00 | 0.215367E+10 | 0.120455E+10 | 0.528863E+10 |
November | 0.158217E+10 | 0.00 | 0.158217E+10 | 0.459863E+09 | 0.614283E+10 |
December | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.253170E+09 | 0.782029E+10 |
Annual Sum or Average | 0.338011E+11 | 0.104712E+10 | 0.327540E+11 | 0.290999E+11 | 0.523847E+11 |
Minimum of Months | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.253170E+09 | 0.145736E+10 |
Maximum of Months | 0.460217E+10 | 0.510225E+09 | 0.420635E+10 | 0.604128E+10 | 0.782029E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308562E+10 | 0.189096E+10 | 0.119466E+10 | 0.271241E+10 | 0.440154E+10 |
February | 0.370223E+10 | 0.233720E+10 | 0.136503E+10 | 0.343752E+10 | 0.407606E+10 |
March | 0.494726E+10 | 0.288569E+10 | 0.206157E+10 | 0.493882E+10 | 0.344727E+10 |
April | 0.491001E+10 | 0.239175E+10 | 0.251826E+10 | 0.479340E+10 | 0.290741E+10 |
May | 0.593105E+10 | 0.247742E+10 | 0.345363E+10 | 0.660896E+10 | 0.185069E+10 |
June | 0.700306E+10 | 0.367642E+10 | 0.332664E+10 | 0.924726E+10 | 0.986963E+09 |
July | 0.657855E+10 | 0.313254E+10 | 0.344601E+10 | 0.876322E+10 | 0.967162E+09 |
August | 0.663537E+10 | 0.365452E+10 | 0.298085E+10 | 0.877803E+10 | 0.110375E+10 |
September | 0.534287E+10 | 0.290240E+10 | 0.244047E+10 | 0.671346E+10 | 0.157151E+10 |
October | 0.399828E+10 | 0.219083E+10 | 0.180745E+10 | 0.415126E+10 | 0.343832E+10 |
November | 0.301176E+10 | 0.170047E+10 | 0.131129E+10 | 0.279529E+10 | 0.393919E+10 |
December | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.227547E+10 | 0.494269E+10 |
Annual Sum or Average | 0.578403E+11 | 0.307923E+11 | 0.270480E+11 | 0.652151E+11 | 0.336325E+11 |
Minimum of Months | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.227547E+10 | 0.967162E+09 |
Maximum of Months | 0.700306E+10 | 0.367642E+10 | 0.345363E+10 | 0.924726E+10 | 0.494269E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141661E+11 | 0.116532E+11 | 0.251296E+10 | 0.158292E+11 | 0.664112E+10 |
February | 0.122730E+11 | 0.978479E+10 | 0.248818E+10 | 0.135968E+11 | 0.614758E+10 |
March | 0.100181E+11 | 0.659132E+10 | 0.342675E+10 | 0.112511E+11 | 0.539475E+10 |
April | 0.627914E+10 | 0.252487E+10 | 0.375427E+10 | 0.643792E+10 | 0.466063E+10 |
May | 0.594594E+10 | 0.108985E+10 | 0.485610E+10 | 0.667553E+10 | 0.304753E+10 |
June | 0.530512E+10 | 0.969628E+09 | 0.433550E+10 | 0.754071E+10 | 0.162263E+10 |
July | 0.570660E+10 | 0.102189E+10 | 0.468470E+10 | 0.812550E+10 | 0.156180E+10 |
August | 0.726566E+10 | 0.303732E+10 | 0.422834E+10 | 0.103582E+11 | 0.178232E+10 |
September | 0.904643E+10 | 0.504786E+10 | 0.399857E+10 | 0.120705E+11 | 0.261041E+10 |
October | 0.111775E+11 | 0.793066E+10 | 0.324679E+10 | 0.132582E+11 | 0.540781E+10 |
November | 0.131789E+11 | 0.105055E+11 | 0.267340E+10 | 0.150568E+11 | 0.608273E+10 |
December | 0.130225E+11 | 0.105402E+11 | 0.248227E+10 | 0.142814E+11 | 0.728687E+10 |
Annual Sum or Average | 0.113385E+12 | 0.706971E+11 | 0.426878E+11 | 0.134482E+12 | 0.522462E+11 |
Minimum of Months | 0.530512E+10 | 0.969628E+09 | 0.248227E+10 | 0.643792E+10 | 0.156180E+10 |
Maximum of Months | 0.141661E+11 | 0.116532E+11 | 0.485610E+10 | 0.158292E+11 | 0.728687E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328241E+10 | 0.207991E+10 | 0.120249E+10 | 0.309468E+10 | 0.461054E+10 |
February | 0.357507E+10 | 0.221549E+10 | 0.135959E+10 | 0.334548E+10 | 0.422535E+10 |
March | 0.463470E+10 | 0.255707E+10 | 0.207763E+10 | 0.459958E+10 | 0.360754E+10 |
April | 0.422302E+10 | 0.178795E+10 | 0.243506E+10 | 0.399595E+10 | 0.306683E+10 |
May | 0.533366E+10 | 0.188031E+10 | 0.345335E+10 | 0.596882E+10 | 0.201726E+10 |
June | 0.631296E+10 | 0.303741E+10 | 0.327555E+10 | 0.844426E+10 | 0.115971E+10 |
July | 0.531502E+10 | 0.194679E+10 | 0.336823E+10 | 0.714149E+10 | 0.109175E+10 |
August | 0.554737E+10 | 0.274048E+10 | 0.280689E+10 | 0.733961E+10 | 0.122585E+10 |
September | 0.476019E+10 | 0.228283E+10 | 0.247736E+10 | 0.604288E+10 | 0.173090E+10 |
October | 0.413806E+10 | 0.236521E+10 | 0.177285E+10 | 0.444442E+10 | 0.358335E+10 |
November | 0.328597E+10 | 0.199499E+10 | 0.129098E+10 | 0.318715E+10 | 0.409250E+10 |
December | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.236712E+10 | 0.507289E+10 |
Annual Sum or Average | 0.531511E+11 | 0.265086E+11 | 0.266425E+11 | 0.599714E+11 | 0.354845E+11 |
Minimum of Months | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.236712E+10 | 0.109175E+10 |
Maximum of Months | 0.631296E+10 | 0.303741E+10 | 0.345335E+10 | 0.844426E+10 | 0.507289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147812E+10 | 0.00 | 0.147812E+10 | 0.355745E+09 | 0.646774E+10 |
February | 0.167803E+10 | 0.00 | 0.167803E+10 | 0.395454E+09 | 0.596550E+10 |
March | 0.252788E+10 | 0.00 | 0.252788E+10 | 0.124297E+10 | 0.501059E+10 |
April | 0.307225E+10 | 17043518.41 | 0.305521E+10 | 0.177550E+10 | 0.407725E+10 |
May | 0.433678E+10 | 0.143356E+09 | 0.419342E+10 | 0.396813E+10 | 0.261915E+10 |
June | 0.460217E+10 | 0.510225E+09 | 0.409194E+10 | 0.601488E+10 | 0.147497E+10 |
July | 0.449748E+10 | 0.291130E+09 | 0.420635E+10 | 0.594606E+10 | 0.144436E+10 |
August | 0.357965E+10 | 84682507.92 | 0.349497E+10 | 0.453751E+10 | 0.163332E+10 |
September | 0.290991E+10 | 683486.50 | 0.290923E+10 | 0.330547E+10 | 0.235464E+10 |
October | 0.215367E+10 | 0.00 | 0.215367E+10 | 0.130152E+10 | 0.486075E+10 |
November | 0.158217E+10 | 0.00 | 0.158217E+10 | 0.548451E+09 | 0.562995E+10 |
December | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.296250E+09 | 0.734782E+10 |
Annual Sum or Average | 0.338011E+11 | 0.104712E+10 | 0.327540E+11 | 0.296879E+11 | 0.488860E+11 |
Minimum of Months | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.296250E+09 | 0.144436E+10 |
Maximum of Months | 0.460217E+10 | 0.510225E+09 | 0.420635E+10 | 0.601488E+10 | 0.734782E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308562E+10 | 0.189096E+10 | 0.119466E+10 | 0.280359E+10 | 0.406188E+10 |
February | 0.370223E+10 | 0.233720E+10 | 0.136503E+10 | 0.349818E+10 | 0.383881E+10 |
March | 0.494726E+10 | 0.288569E+10 | 0.206157E+10 | 0.498644E+10 | 0.324719E+10 |
April | 0.491001E+10 | 0.239175E+10 | 0.251826E+10 | 0.484743E+10 | 0.267124E+10 |
May | 0.593105E+10 | 0.247742E+10 | 0.345363E+10 | 0.664172E+10 | 0.177389E+10 |
June | 0.700306E+10 | 0.367642E+10 | 0.332664E+10 | 0.920975E+10 | 0.989944E+09 |
July | 0.657855E+10 | 0.313254E+10 | 0.344601E+10 | 0.872643E+10 | 0.969238E+09 |
August | 0.663537E+10 | 0.365452E+10 | 0.298085E+10 | 0.874832E+10 | 0.110284E+10 |
September | 0.534287E+10 | 0.290240E+10 | 0.244047E+10 | 0.671232E+10 | 0.152981E+10 |
October | 0.399828E+10 | 0.219083E+10 | 0.180745E+10 | 0.419634E+10 | 0.321070E+10 |
November | 0.301176E+10 | 0.170047E+10 | 0.131129E+10 | 0.287403E+10 | 0.365455E+10 |
December | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.233806E+10 | 0.466605E+10 |
Annual Sum or Average | 0.578403E+11 | 0.307923E+11 | 0.270480E+11 | 0.655826E+11 | 0.317162E+11 |
Minimum of Months | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.233806E+10 | 0.969238E+09 |
Maximum of Months | 0.700306E+10 | 0.367642E+10 | 0.345363E+10 | 0.920975E+10 | 0.466605E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141661E+11 | 0.116532E+11 | 0.251296E+10 | 0.160086E+11 | 0.610382E+10 |
February | 0.122730E+11 | 0.978479E+10 | 0.248818E+10 | 0.136902E+11 | 0.576466E+10 |
March | 0.100181E+11 | 0.659132E+10 | 0.342675E+10 | 0.113213E+11 | 0.505739E+10 |
April | 0.627914E+10 | 0.252487E+10 | 0.375427E+10 | 0.651041E+10 | 0.427047E+10 |
May | 0.594594E+10 | 0.108985E+10 | 0.485610E+10 | 0.673422E+10 | 0.288633E+10 |
June | 0.530512E+10 | 0.969628E+09 | 0.433550E+10 | 0.750912E+10 | 0.160479E+10 |
July | 0.570660E+10 | 0.102189E+10 | 0.468470E+10 | 0.809156E+10 | 0.154634E+10 |
August | 0.726566E+10 | 0.303732E+10 | 0.422834E+10 | 0.103282E+11 | 0.176058E+10 |
September | 0.904643E+10 | 0.504786E+10 | 0.399857E+10 | 0.120708E+11 | 0.252316E+10 |
October | 0.111775E+11 | 0.793066E+10 | 0.324679E+10 | 0.133227E+11 | 0.504504E+10 |
November | 0.131789E+11 | 0.105055E+11 | 0.267340E+10 | 0.151740E+11 | 0.565118E+10 |
December | 0.130225E+11 | 0.105402E+11 | 0.248227E+10 | 0.144124E+11 | 0.682848E+10 |
Annual Sum or Average | 0.113385E+12 | 0.706971E+11 | 0.426878E+11 | 0.135173E+12 | 0.490423E+11 |
Minimum of Months | 0.530512E+10 | 0.969628E+09 | 0.248227E+10 | 0.651041E+10 | 0.154634E+10 |
Maximum of Months | 0.141661E+11 | 0.116532E+11 | 0.485610E+10 | 0.160086E+11 | 0.682848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328241E+10 | 0.207991E+10 | 0.120249E+10 | 0.315183E+10 | 0.427659E+10 |
February | 0.357507E+10 | 0.221549E+10 | 0.135959E+10 | 0.337484E+10 | 0.399567E+10 |
March | 0.463470E+10 | 0.255707E+10 | 0.207763E+10 | 0.462802E+10 | 0.340375E+10 |
April | 0.422302E+10 | 0.178795E+10 | 0.243506E+10 | 0.403271E+10 | 0.283654E+10 |
May | 0.533366E+10 | 0.188031E+10 | 0.345335E+10 | 0.599690E+10 | 0.192667E+10 |
June | 0.631296E+10 | 0.303741E+10 | 0.327555E+10 | 0.842045E+10 | 0.115104E+10 |
July | 0.531502E+10 | 0.194679E+10 | 0.336823E+10 | 0.711894E+10 | 0.108048E+10 |
August | 0.554737E+10 | 0.274048E+10 | 0.280689E+10 | 0.732342E+10 | 0.121308E+10 |
September | 0.476019E+10 | 0.228283E+10 | 0.247736E+10 | 0.604789E+10 | 0.167618E+10 |
October | 0.413806E+10 | 0.236521E+10 | 0.177285E+10 | 0.447794E+10 | 0.336474E+10 |
November | 0.328597E+10 | 0.199499E+10 | 0.129098E+10 | 0.323282E+10 | 0.382834E+10 |
December | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.240063E+10 | 0.480552E+10 |
Annual Sum or Average | 0.531511E+11 | 0.265086E+11 | 0.266425E+11 | 0.602064E+11 | 0.335586E+11 |
Minimum of Months | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.240063E+10 | 0.108048E+10 |
Maximum of Months | 0.631296E+10 | 0.303741E+10 | 0.345335E+10 | 0.842045E+10 | 0.480552E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 80.51 | 2866.65 | 551.86 | 0.00 | 551.86 | 0.00 | 0.00 |
February | 105.57 | 2882.67 | 693.62 | 0.00 | 693.62 | 0.00 | 0.00 |
March | 381.74 | 2215.76 | 943.79 | 0.00 | 943.79 | 0.00 | 0.00 |
April | 592.23 | 1957.27 | 1185.26 | 6.58 | 1178.69 | 0.00 | 0.00 |
May | 1418.63 | 1089.86 | 1619.14 | 53.52 | 1565.62 | 0.00 | 0.00 |
June | 2318.57 | 587.83 | 1775.50 | 196.84 | 1578.66 | 0.00 | 0.00 |
July | 2217.18 | 552.04 | 1679.14 | 108.69 | 1570.44 | 0.00 | 0.00 |
August | 1674.40 | 637.36 | 1336.47 | 31.62 | 1304.85 | 0.00 | 0.00 |
September | 1240.93 | 1003.75 | 1122.63 | 0.26 | 1122.37 | 0.00 | 0.00 |
October | 410.16 | 2144.39 | 804.08 | 0.00 | 804.08 | 0.00 | 0.00 |
November | 138.12 | 2619.73 | 610.40 | 0.00 | 610.40 | 0.00 | 0.00 |
December | 61.38 | 3262.81 | 516.33 | 0.00 | 516.33 | 0.00 | 0.00 |
Annual Sum or Average | 891.00 | 1812.62 | 1071.81 | 33.20 | 1038.60 | 0.00 | 0.00 |
Minimum of Months | 61.38 | 552.04 | 516.33 | 0.00 | 516.33 | 0.00 | 0.00 |
Maximum of Months | 2318.57 | 3262.81 | 1775.50 | 196.84 | 1578.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 990.43 | 1750.59 | 1152.04 | 706.01 | 446.04 | 0.00 | 0.00 |
February | 1407.80 | 1794.75 | 1530.36 | 966.11 | 564.25 | 0.00 | 0.00 |
March | 1835.86 | 1371.94 | 1847.10 | 1077.40 | 769.70 | 0.00 | 0.00 |
April | 1841.13 | 1212.44 | 1894.30 | 922.75 | 971.56 | 0.00 | 0.00 |
May | 2471.22 | 715.37 | 2214.41 | 924.97 | 1289.44 | 0.00 | 0.00 |
June | 3584.08 | 378.32 | 2701.81 | 1418.38 | 1283.43 | 0.00 | 0.00 |
July | 3289.78 | 345.55 | 2456.16 | 1169.56 | 1286.60 | 0.00 | 0.00 |
August | 3296.31 | 383.76 | 2477.37 | 1364.45 | 1112.92 | 0.00 | 0.00 |
September | 2595.81 | 625.76 | 2061.30 | 1119.76 | 941.54 | 0.00 | 0.00 |
October | 1543.34 | 1356.35 | 1492.79 | 817.96 | 674.83 | 0.00 | 0.00 |
November | 1059.39 | 1619.73 | 1161.95 | 656.05 | 505.90 | 0.00 | 0.00 |
December | 822.78 | 1987.49 | 1005.94 | 579.49 | 426.45 | 0.00 | 0.00 |
Annual Sum or Average | 2064.58 | 1124.88 | 1834.11 | 976.42 | 857.69 | 0.00 | 0.00 |
Minimum of Months | 822.78 | 345.55 | 1005.94 | 579.49 | 426.45 | 0.00 | 0.00 |
Maximum of Months | 3584.08 | 1987.49 | 2701.81 | 1418.38 | 1289.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5941.64 | 2497.70 | 5288.86 | 4350.65 | 938.21 | 0.00 | 0.00 |
February | 5656.18 | 2596.73 | 5073.00 | 4044.50 | 1028.49 | 0.00 | 0.00 |
March | 4217.31 | 2087.80 | 3740.21 | 2460.84 | 1279.37 | 0.00 | 0.00 |
April | 2477.39 | 1909.12 | 2422.44 | 974.07 | 1448.38 | 0.00 | 0.00 |
May | 2494.33 | 1164.57 | 2219.91 | 406.89 | 1813.02 | 0.00 | 0.00 |
June | 2905.62 | 635.94 | 2046.69 | 374.07 | 1672.62 | 0.00 | 0.00 |
July | 3030.56 | 582.38 | 2130.55 | 381.52 | 1749.03 | 0.00 | 0.00 |
August | 3869.53 | 660.27 | 2712.62 | 1133.97 | 1578.65 | 0.00 | 0.00 |
September | 4678.60 | 1021.04 | 3490.04 | 1947.41 | 1542.63 | 0.00 | 0.00 |
October | 4974.59 | 2058.19 | 4173.06 | 2960.87 | 1212.19 | 0.00 | 0.00 |
November | 5837.86 | 2391.64 | 5084.28 | 4052.90 | 1031.38 | 0.00 | 0.00 |
December | 5339.00 | 2828.32 | 4861.90 | 3935.15 | 926.75 | 0.00 | 0.00 |
Annual Sum or Average | 4277.35 | 1697.80 | 3595.31 | 2241.72 | 1353.59 | 0.00 | 0.00 |
Minimum of Months | 2477.39 | 582.38 | 2046.69 | 374.07 | 926.75 | 0.00 | 0.00 |
Maximum of Months | 5941.64 | 2828.32 | 5288.86 | 4350.65 | 1813.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1126.17 | 1869.32 | 1225.51 | 776.55 | 448.96 | 0.00 | 0.00 |
February | 1345.86 | 1936.65 | 1477.80 | 915.80 | 562.00 | 0.00 | 0.00 |
March | 1664.81 | 1543.30 | 1730.40 | 954.70 | 775.70 | 0.00 | 0.00 |
April | 1474.29 | 1435.47 | 1629.26 | 689.80 | 939.46 | 0.00 | 0.00 |
May | 2199.98 | 812.01 | 1991.37 | 702.03 | 1289.34 | 0.00 | 0.00 |
June | 3233.10 | 480.52 | 2435.57 | 1171.84 | 1263.72 | 0.00 | 0.00 |
July | 2628.35 | 446.75 | 1984.41 | 726.85 | 1257.56 | 0.00 | 0.00 |
August | 2682.23 | 526.21 | 2071.16 | 1023.18 | 1047.98 | 0.00 | 0.00 |
September | 2307.47 | 721.44 | 1836.50 | 880.72 | 955.78 | 0.00 | 0.00 |
October | 1621.51 | 1488.13 | 1544.98 | 883.07 | 661.91 | 0.00 | 0.00 |
November | 1180.85 | 1795.91 | 1267.74 | 769.68 | 498.06 | 0.00 | 0.00 |
December | 828.76 | 2223.88 | 1023.99 | 604.90 | 419.09 | 0.00 | 0.00 |
Annual Sum or Average | 1859.89 | 1269.65 | 1685.42 | 840.59 | 844.83 | 0.00 | 0.00 |
Minimum of Months | 828.76 | 446.75 | 1023.99 | 604.90 | 419.09 | 0.00 | 0.00 |
Maximum of Months | 3233.10 | 2223.88 | 2435.57 | 1171.84 | 1289.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 106.51 | 2626.51 | 551.87 | 0.00 | 551.87 | 0.00 | 0.00 |
February | 140.47 | 2634.66 | 693.63 | 0.00 | 693.63 | 0.00 | 0.00 |
March | 434.03 | 2008.11 | 943.80 | 0.00 | 943.80 | 0.00 | 0.00 |
April | 648.41 | 1731.48 | 1185.28 | 6.58 | 1178.71 | 0.00 | 0.00 |
May | 1444.69 | 1036.85 | 1619.17 | 53.52 | 1565.64 | 0.00 | 0.00 |
June | 2330.74 | 574.72 | 1775.53 | 196.85 | 1578.68 | 0.00 | 0.00 |
July | 2231.07 | 544.12 | 1679.17 | 108.70 | 1570.47 | 0.00 | 0.00 |
August | 1699.89 | 620.82 | 1336.49 | 31.62 | 1304.87 | 0.00 | 0.00 |
September | 1263.35 | 953.26 | 1122.65 | 0.26 | 1122.39 | 0.00 | 0.00 |
October | 449.73 | 1974.55 | 804.09 | 0.00 | 804.09 | 0.00 | 0.00 |
November | 177.42 | 2369.92 | 610.41 | 0.00 | 610.41 | 0.00 | 0.00 |
December | 94.52 | 2919.76 | 516.34 | 0.00 | 516.34 | 0.00 | 0.00 |
Annual Sum or Average | 922.75 | 1661.11 | 1071.83 | 33.20 | 1038.62 | 0.00 | 0.00 |
Minimum of Months | 94.52 | 544.12 | 516.34 | 0.00 | 516.34 | 0.00 | 0.00 |
Maximum of Months | 2330.74 | 2919.76 | 1775.53 | 196.85 | 1578.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1012.70 | 1643.35 | 1152.04 | 706.00 | 446.03 | 0.00 | 0.00 |
February | 1420.93 | 1684.88 | 1530.35 | 966.11 | 564.25 | 0.00 | 0.00 |
March | 1843.94 | 1287.06 | 1847.09 | 1077.39 | 769.70 | 0.00 | 0.00 |
April | 1849.31 | 1121.69 | 1894.30 | 922.74 | 971.55 | 0.00 | 0.00 |
May | 2467.50 | 690.97 | 2214.40 | 924.96 | 1289.44 | 0.00 | 0.00 |
June | 3567.62 | 380.77 | 2701.80 | 1418.37 | 1283.43 | 0.00 | 0.00 |
July | 3271.81 | 361.10 | 2456.15 | 1169.56 | 1286.59 | 0.00 | 0.00 |
August | 3277.34 | 412.09 | 2477.36 | 1364.44 | 1112.92 | 0.00 | 0.00 |
September | 2590.07 | 606.29 | 2061.29 | 1119.75 | 941.54 | 0.00 | 0.00 |
October | 1549.90 | 1283.72 | 1492.79 | 817.96 | 674.83 | 0.00 | 0.00 |
November | 1078.43 | 1519.75 | 1161.94 | 656.04 | 505.90 | 0.00 | 0.00 |
December | 849.56 | 1845.39 | 1005.93 | 579.49 | 426.44 | 0.00 | 0.00 |
Annual Sum or Average | 2067.96 | 1066.48 | 1834.11 | 976.42 | 857.69 | 0.00 | 0.00 |
Minimum of Months | 849.56 | 361.10 | 1005.93 | 579.49 | 426.44 | 0.00 | 0.00 |
Maximum of Months | 3567.62 | 1845.39 | 2701.80 | 1418.37 | 1289.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5909.93 | 2479.51 | 5289.02 | 4350.79 | 938.23 | 0.00 | 0.00 |
February | 5620.36 | 2541.16 | 5073.15 | 4044.64 | 1028.51 | 0.00 | 0.00 |
March | 4200.67 | 2014.17 | 3740.32 | 2460.92 | 1279.40 | 0.00 | 0.00 |
April | 2483.76 | 1798.08 | 2422.51 | 974.10 | 1448.41 | 0.00 | 0.00 |
May | 2492.36 | 1137.82 | 2219.96 | 406.90 | 1813.06 | 0.00 | 0.00 |
June | 2909.22 | 626.01 | 2046.73 | 374.08 | 1672.65 | 0.00 | 0.00 |
July | 3033.71 | 583.11 | 2130.60 | 381.53 | 1749.07 | 0.00 | 0.00 |
August | 3867.33 | 665.44 | 2712.69 | 1134.01 | 1578.68 | 0.00 | 0.00 |
September | 4656.83 | 1007.10 | 3490.14 | 1947.48 | 1542.66 | 0.00 | 0.00 |
October | 4950.06 | 2019.04 | 4173.18 | 2960.97 | 1212.21 | 0.00 | 0.00 |
November | 5808.96 | 2346.73 | 5084.44 | 4053.04 | 1031.40 | 0.00 | 0.00 |
December | 5332.05 | 2720.61 | 4862.05 | 3935.28 | 926.77 | 0.00 | 0.00 |
Annual Sum or Average | 4264.39 | 1656.72 | 3595.41 | 2241.79 | 1353.62 | 0.00 | 0.00 |
Minimum of Months | 2483.76 | 583.11 | 2046.73 | 374.08 | 926.77 | 0.00 | 0.00 |
Maximum of Months | 5909.93 | 2720.61 | 5289.02 | 4350.79 | 1813.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1155.42 | 1721.38 | 1225.51 | 776.55 | 448.96 | 0.00 | 0.00 |
February | 1382.89 | 1746.59 | 1477.79 | 915.79 | 562.00 | 0.00 | 0.00 |
March | 1717.29 | 1346.90 | 1730.40 | 954.70 | 775.70 | 0.00 | 0.00 |
April | 1541.65 | 1183.19 | 1629.25 | 689.80 | 939.45 | 0.00 | 0.00 |
May | 2228.50 | 753.16 | 1991.36 | 702.03 | 1289.33 | 0.00 | 0.00 |
June | 3257.81 | 447.42 | 2435.56 | 1171.84 | 1263.72 | 0.00 | 0.00 |
July | 2666.33 | 407.61 | 1984.40 | 726.85 | 1257.55 | 0.00 | 0.00 |
August | 2740.30 | 457.68 | 2071.15 | 1023.18 | 1047.97 | 0.00 | 0.00 |
September | 2331.36 | 667.79 | 1836.49 | 880.72 | 955.77 | 0.00 | 0.00 |
October | 1659.36 | 1337.87 | 1544.98 | 883.07 | 661.91 | 0.00 | 0.00 |
November | 1229.61 | 1578.90 | 1267.73 | 769.67 | 498.06 | 0.00 | 0.00 |
December | 883.78 | 1894.00 | 1023.98 | 604.89 | 419.09 | 0.00 | 0.00 |
Annual Sum or Average | 1901.68 | 1125.21 | 1685.41 | 840.58 | 844.83 | 0.00 | 0.00 |
Minimum of Months | 883.78 | 407.61 | 1023.98 | 604.89 | 419.09 | 0.00 | 0.00 |
Maximum of Months | 3257.81 | 1894.00 | 2435.56 | 1171.84 | 1289.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 132.82 | 2414.78 | 551.87 | 0.00 | 551.87 | 0.00 | 0.00 |
February | 163.46 | 2465.90 | 693.63 | 0.00 | 693.63 | 0.00 | 0.00 |
March | 464.07 | 1870.74 | 943.80 | 0.00 | 943.80 | 0.00 | 0.00 |
April | 684.99 | 1573.01 | 1185.28 | 6.58 | 1178.71 | 0.00 | 0.00 |
May | 1481.53 | 977.88 | 1619.17 | 53.52 | 1565.64 | 0.00 | 0.00 |
June | 2320.56 | 569.05 | 1775.53 | 196.85 | 1578.68 | 0.00 | 0.00 |
July | 2220.01 | 539.26 | 1679.17 | 108.70 | 1570.47 | 0.00 | 0.00 |
August | 1694.11 | 609.81 | 1336.49 | 31.62 | 1304.87 | 0.00 | 0.00 |
September | 1275.26 | 908.43 | 1122.65 | 0.26 | 1122.39 | 0.00 | 0.00 |
October | 485.93 | 1814.80 | 804.09 | 0.00 | 804.09 | 0.00 | 0.00 |
November | 211.59 | 2172.05 | 610.41 | 0.00 | 610.41 | 0.00 | 0.00 |
December | 110.61 | 2743.36 | 516.34 | 0.00 | 516.34 | 0.00 | 0.00 |
Annual Sum or Average | 941.40 | 1550.17 | 1071.83 | 33.20 | 1038.62 | 0.00 | 0.00 |
Minimum of Months | 110.61 | 539.26 | 516.34 | 0.00 | 516.34 | 0.00 | 0.00 |
Maximum of Months | 2320.56 | 2743.36 | 1775.53 | 196.85 | 1578.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1046.74 | 1516.53 | 1152.04 | 706.00 | 446.03 | 0.00 | 0.00 |
February | 1446.01 | 1586.81 | 1530.35 | 966.11 | 564.25 | 0.00 | 0.00 |
March | 1861.72 | 1212.36 | 1847.09 | 1077.39 | 769.70 | 0.00 | 0.00 |
April | 1870.15 | 1030.57 | 1894.30 | 922.74 | 971.55 | 0.00 | 0.00 |
May | 2479.73 | 662.30 | 2214.40 | 924.96 | 1289.44 | 0.00 | 0.00 |
June | 3553.15 | 381.92 | 2701.80 | 1418.37 | 1283.43 | 0.00 | 0.00 |
July | 3258.07 | 361.87 | 2456.15 | 1169.56 | 1286.59 | 0.00 | 0.00 |
August | 3266.25 | 411.75 | 2477.36 | 1364.44 | 1112.92 | 0.00 | 0.00 |
September | 2589.63 | 590.21 | 2061.29 | 1119.75 | 941.54 | 0.00 | 0.00 |
October | 1566.74 | 1198.74 | 1492.79 | 817.96 | 674.83 | 0.00 | 0.00 |
November | 1108.81 | 1409.94 | 1161.94 | 656.04 | 505.90 | 0.00 | 0.00 |
December | 872.93 | 1742.10 | 1005.93 | 579.49 | 426.44 | 0.00 | 0.00 |
Annual Sum or Average | 2079.61 | 1005.71 | 1834.11 | 976.42 | 857.69 | 0.00 | 0.00 |
Minimum of Months | 872.93 | 361.87 | 1005.93 | 579.49 | 426.44 | 0.00 | 0.00 |
Maximum of Months | 3553.15 | 1742.10 | 2701.80 | 1418.37 | 1289.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5976.92 | 2278.91 | 5289.02 | 4350.79 | 938.23 | 0.00 | 0.00 |
February | 5658.99 | 2382.88 | 5073.15 | 4044.64 | 1028.51 | 0.00 | 0.00 |
March | 4226.88 | 1888.21 | 3740.32 | 2460.92 | 1279.40 | 0.00 | 0.00 |
April | 2511.73 | 1647.56 | 2422.51 | 974.10 | 1448.41 | 0.00 | 0.00 |
May | 2514.27 | 1077.63 | 2219.96 | 406.90 | 1813.06 | 0.00 | 0.00 |
June | 2897.04 | 619.13 | 2046.73 | 374.08 | 1672.65 | 0.00 | 0.00 |
July | 3021.04 | 577.34 | 2130.60 | 381.53 | 1749.07 | 0.00 | 0.00 |
August | 3856.12 | 657.33 | 2712.69 | 1134.01 | 1578.68 | 0.00 | 0.00 |
September | 4656.94 | 973.44 | 3490.14 | 1947.48 | 1542.66 | 0.00 | 0.00 |
October | 4974.11 | 1883.60 | 4173.18 | 2960.97 | 1212.21 | 0.00 | 0.00 |
November | 5854.16 | 2180.24 | 5084.44 | 4053.04 | 1031.40 | 0.00 | 0.00 |
December | 5380.96 | 2549.46 | 4862.05 | 3935.28 | 926.77 | 0.00 | 0.00 |
Annual Sum or Average | 4286.32 | 1555.12 | 3595.41 | 2241.79 | 1353.62 | 0.00 | 0.00 |
Minimum of Months | 2511.73 | 577.34 | 2046.73 | 374.08 | 926.77 | 0.00 | 0.00 |
Maximum of Months | 5976.92 | 2549.46 | 5289.02 | 4350.79 | 1813.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1176.76 | 1596.70 | 1225.51 | 776.55 | 448.96 | 0.00 | 0.00 |
February | 1395.02 | 1651.65 | 1477.79 | 915.79 | 562.00 | 0.00 | 0.00 |
March | 1727.91 | 1270.81 | 1730.40 | 954.70 | 775.70 | 0.00 | 0.00 |
April | 1555.83 | 1094.34 | 1629.25 | 689.80 | 939.45 | 0.00 | 0.00 |
May | 2238.99 | 719.34 | 1991.36 | 702.03 | 1289.33 | 0.00 | 0.00 |
June | 3248.63 | 444.07 | 2435.56 | 1171.84 | 1263.72 | 0.00 | 0.00 |
July | 2657.91 | 403.40 | 1984.40 | 726.85 | 1257.55 | 0.00 | 0.00 |
August | 2734.25 | 452.91 | 2071.15 | 1023.18 | 1047.97 | 0.00 | 0.00 |
September | 2333.29 | 646.67 | 1836.49 | 880.72 | 955.77 | 0.00 | 0.00 |
October | 1671.87 | 1256.25 | 1544.98 | 883.07 | 661.91 | 0.00 | 0.00 |
November | 1247.23 | 1476.98 | 1267.73 | 769.67 | 498.06 | 0.00 | 0.00 |
December | 896.29 | 1794.18 | 1023.98 | 604.89 | 419.09 | 0.00 | 0.00 |
Annual Sum or Average | 1909.13 | 1064.14 | 1685.41 | 840.58 | 844.83 | 0.00 | 0.00 |
Minimum of Months | 896.29 | 403.40 | 1023.98 | 604.89 | 419.09 | 0.00 | 0.00 |
Maximum of Months | 3248.63 | 1794.18 | 2435.56 | 1171.84 | 1289.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.215644E+09 | 0.767803E+10 | 0.147810E+10 | 0.00 | 0.147810E+10 | 0.00 | 0.00 |
February | 0.255402E+09 | 0.697376E+10 | 0.167801E+10 | 0.00 | 0.167801E+10 | 0.00 | 0.00 |
March | 0.102246E+10 | 0.593470E+10 | 0.252784E+10 | 0.00 | 0.252784E+10 | 0.00 | 0.00 |
April | 0.153506E+10 | 0.507324E+10 | 0.307220E+10 | 17043010.14 | 0.305515E+10 | 0.00 | 0.00 |
May | 0.379966E+10 | 0.291909E+10 | 0.433670E+10 | 0.143352E+09 | 0.419334E+10 | 0.00 | 0.00 |
June | 0.600974E+10 | 0.152366E+10 | 0.460209E+10 | 0.510210E+09 | 0.409188E+10 | 0.00 | 0.00 |
July | 0.593850E+10 | 0.147859E+10 | 0.449740E+10 | 0.291121E+09 | 0.420628E+10 | 0.00 | 0.00 |
August | 0.448472E+10 | 0.170710E+10 | 0.357960E+10 | 84679982.52 | 0.349492E+10 | 0.00 | 0.00 |
September | 0.321650E+10 | 0.260173E+10 | 0.290986E+10 | 683466.12 | 0.290918E+10 | 0.00 | 0.00 |
October | 0.109858E+10 | 0.574353E+10 | 0.215364E+10 | 0.00 | 0.215364E+10 | 0.00 | 0.00 |
November | 0.358002E+09 | 0.679035E+10 | 0.158215E+10 | 0.00 | 0.158215E+10 | 0.00 | 0.00 |
December | 0.164398E+09 | 0.873911E+10 | 0.138294E+10 | 0.00 | 0.138294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.280987E+11 | 0.571629E+11 | 0.338005E+11 | 0.104709E+10 | 0.327534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.164398E+09 | 0.147859E+10 | 0.138294E+10 | 0.00 | 0.138294E+10 | 0.00 | 0.00 |
Maximum of Months | 0.600974E+10 | 0.873911E+10 | 0.460209E+10 | 0.510210E+09 | 0.420628E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265276E+10 | 0.468878E+10 | 0.308563E+10 | 0.189097E+10 | 0.119466E+10 | 0.00 | 0.00 |
February | 0.340575E+10 | 0.434185E+10 | 0.370225E+10 | 0.233721E+10 | 0.136503E+10 | 0.00 | 0.00 |
March | 0.491717E+10 | 0.367460E+10 | 0.494728E+10 | 0.288570E+10 | 0.206157E+10 | 0.00 | 0.00 |
April | 0.477221E+10 | 0.314263E+10 | 0.491003E+10 | 0.239176E+10 | 0.251827E+10 | 0.00 | 0.00 |
May | 0.661892E+10 | 0.191604E+10 | 0.593108E+10 | 0.247743E+10 | 0.345364E+10 | 0.00 | 0.00 |
June | 0.928992E+10 | 0.980612E+09 | 0.700309E+10 | 0.367644E+10 | 0.332665E+10 | 0.00 | 0.00 |
July | 0.881134E+10 | 0.925529E+09 | 0.657858E+10 | 0.313256E+10 | 0.344602E+10 | 0.00 | 0.00 |
August | 0.882883E+10 | 0.102785E+10 | 0.663540E+10 | 0.365454E+10 | 0.298086E+10 | 0.00 | 0.00 |
September | 0.672834E+10 | 0.162197E+10 | 0.534289E+10 | 0.290241E+10 | 0.244048E+10 | 0.00 | 0.00 |
October | 0.413368E+10 | 0.363285E+10 | 0.399830E+10 | 0.219083E+10 | 0.180746E+10 | 0.00 | 0.00 |
November | 0.274595E+10 | 0.419834E+10 | 0.301177E+10 | 0.170047E+10 | 0.131129E+10 | 0.00 | 0.00 |
December | 0.220374E+10 | 0.532330E+10 | 0.269430E+10 | 0.155211E+10 | 0.114219E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.651086E+11 | 0.354744E+11 | 0.578406E+11 | 0.307924E+11 | 0.270481E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220374E+10 | 0.925529E+09 | 0.269430E+10 | 0.155211E+10 | 0.114219E+10 | 0.00 | 0.00 |
Maximum of Months | 0.928992E+10 | 0.532330E+10 | 0.700309E+10 | 0.367644E+10 | 0.345364E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159141E+11 | 0.668984E+10 | 0.141657E+11 | 0.116528E+11 | 0.251290E+10 | 0.00 | 0.00 |
February | 0.136834E+11 | 0.628200E+10 | 0.122726E+11 | 0.978447E+10 | 0.248813E+10 | 0.00 | 0.00 |
March | 0.112957E+11 | 0.559197E+10 | 0.100178E+11 | 0.659111E+10 | 0.342667E+10 | 0.00 | 0.00 |
April | 0.642139E+10 | 0.494844E+10 | 0.627898E+10 | 0.252478E+10 | 0.375419E+10 | 0.00 | 0.00 |
May | 0.668082E+10 | 0.311920E+10 | 0.594580E+10 | 0.108981E+10 | 0.485599E+10 | 0.00 | 0.00 |
June | 0.753137E+10 | 0.164834E+10 | 0.530501E+10 | 0.969596E+09 | 0.433542E+10 | 0.00 | 0.00 |
July | 0.811704E+10 | 0.155984E+10 | 0.570647E+10 | 0.102186E+10 | 0.468461E+10 | 0.00 | 0.00 |
August | 0.103641E+11 | 0.176846E+10 | 0.726548E+10 | 0.303722E+10 | 0.422826E+10 | 0.00 | 0.00 |
September | 0.121269E+11 | 0.264654E+10 | 0.904618E+10 | 0.504769E+10 | 0.399849E+10 | 0.00 | 0.00 |
October | 0.133239E+11 | 0.551266E+10 | 0.111771E+11 | 0.793040E+10 | 0.324672E+10 | 0.00 | 0.00 |
November | 0.151317E+11 | 0.619913E+10 | 0.131785E+11 | 0.105051E+11 | 0.267334E+10 | 0.00 | 0.00 |
December | 0.143000E+11 | 0.757538E+10 | 0.130221E+11 | 0.105399E+11 | 0.248221E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134891E+12 | 0.535418E+11 | 0.113382E+12 | 0.706947E+11 | 0.426869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.642139E+10 | 0.155984E+10 | 0.530501E+10 | 0.969596E+09 | 0.248221E+10 | 0.00 | 0.00 |
Maximum of Months | 0.159141E+11 | 0.757538E+10 | 0.141657E+11 | 0.116528E+11 | 0.485599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301634E+10 | 0.500679E+10 | 0.328242E+10 | 0.207992E+10 | 0.120250E+10 | 0.00 | 0.00 |
February | 0.325592E+10 | 0.468513E+10 | 0.357509E+10 | 0.221550E+10 | 0.135959E+10 | 0.00 | 0.00 |
March | 0.445904E+10 | 0.413358E+10 | 0.463472E+10 | 0.255708E+10 | 0.207764E+10 | 0.00 | 0.00 |
April | 0.382135E+10 | 0.372073E+10 | 0.422303E+10 | 0.178796E+10 | 0.243507E+10 | 0.00 | 0.00 |
May | 0.589243E+10 | 0.217490E+10 | 0.533368E+10 | 0.188032E+10 | 0.345336E+10 | 0.00 | 0.00 |
June | 0.838018E+10 | 0.124550E+10 | 0.631299E+10 | 0.303742E+10 | 0.327556E+10 | 0.00 | 0.00 |
July | 0.703977E+10 | 0.119657E+10 | 0.531504E+10 | 0.194680E+10 | 0.336824E+10 | 0.00 | 0.00 |
August | 0.718408E+10 | 0.140939E+10 | 0.554740E+10 | 0.274049E+10 | 0.280690E+10 | 0.00 | 0.00 |
September | 0.598096E+10 | 0.186997E+10 | 0.476021E+10 | 0.228284E+10 | 0.247737E+10 | 0.00 | 0.00 |
October | 0.434304E+10 | 0.398581E+10 | 0.413808E+10 | 0.236522E+10 | 0.177286E+10 | 0.00 | 0.00 |
November | 0.306076E+10 | 0.465501E+10 | 0.328598E+10 | 0.199500E+10 | 0.129098E+10 | 0.00 | 0.00 |
December | 0.221976E+10 | 0.595645E+10 | 0.274265E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.586536E+11 | 0.400398E+11 | 0.531513E+11 | 0.265087E+11 | 0.266426E+11 | 0.00 | 0.00 |
Minimum of Months | 0.221976E+10 | 0.119657E+10 | 0.274265E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.838018E+10 | 0.595645E+10 | 0.631299E+10 | 0.303742E+10 | 0.345336E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.285287E+09 | 0.703483E+10 | 0.147812E+10 | 0.00 | 0.147812E+10 | 0.00 | 0.00 |
February | 0.339815E+09 | 0.637378E+10 | 0.167803E+10 | 0.00 | 0.167803E+10 | 0.00 | 0.00 |
March | 0.116250E+10 | 0.537851E+10 | 0.252788E+10 | 0.00 | 0.252788E+10 | 0.00 | 0.00 |
April | 0.168069E+10 | 0.448799E+10 | 0.307225E+10 | 17043518.41 | 0.305521E+10 | 0.00 | 0.00 |
May | 0.386946E+10 | 0.277709E+10 | 0.433678E+10 | 0.143356E+09 | 0.419342E+10 | 0.00 | 0.00 |
June | 0.604128E+10 | 0.148969E+10 | 0.460217E+10 | 0.510225E+09 | 0.409194E+10 | 0.00 | 0.00 |
July | 0.597569E+10 | 0.145736E+10 | 0.449748E+10 | 0.291130E+09 | 0.420635E+10 | 0.00 | 0.00 |
August | 0.455299E+10 | 0.166281E+10 | 0.357965E+10 | 84682507.92 | 0.349497E+10 | 0.00 | 0.00 |
September | 0.327460E+10 | 0.247084E+10 | 0.290991E+10 | 683486.50 | 0.290923E+10 | 0.00 | 0.00 |
October | 0.120455E+10 | 0.528863E+10 | 0.215367E+10 | 0.00 | 0.215367E+10 | 0.00 | 0.00 |
November | 0.459863E+09 | 0.614283E+10 | 0.158217E+10 | 0.00 | 0.158217E+10 | 0.00 | 0.00 |
December | 0.253170E+09 | 0.782029E+10 | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290999E+11 | 0.523847E+11 | 0.338011E+11 | 0.104712E+10 | 0.327540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253170E+09 | 0.145736E+10 | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.00 | 0.00 |
Maximum of Months | 0.604128E+10 | 0.782029E+10 | 0.460217E+10 | 0.510225E+09 | 0.420635E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271241E+10 | 0.440154E+10 | 0.308562E+10 | 0.189096E+10 | 0.119466E+10 | 0.00 | 0.00 |
February | 0.343752E+10 | 0.407606E+10 | 0.370223E+10 | 0.233720E+10 | 0.136503E+10 | 0.00 | 0.00 |
March | 0.493882E+10 | 0.344727E+10 | 0.494726E+10 | 0.288569E+10 | 0.206157E+10 | 0.00 | 0.00 |
April | 0.479340E+10 | 0.290741E+10 | 0.491001E+10 | 0.239175E+10 | 0.251826E+10 | 0.00 | 0.00 |
May | 0.660896E+10 | 0.185069E+10 | 0.593105E+10 | 0.247742E+10 | 0.345363E+10 | 0.00 | 0.00 |
June | 0.924726E+10 | 0.986963E+09 | 0.700306E+10 | 0.367642E+10 | 0.332664E+10 | 0.00 | 0.00 |
July | 0.876322E+10 | 0.967162E+09 | 0.657855E+10 | 0.313254E+10 | 0.344601E+10 | 0.00 | 0.00 |
August | 0.877803E+10 | 0.110375E+10 | 0.663537E+10 | 0.365452E+10 | 0.298085E+10 | 0.00 | 0.00 |
September | 0.671346E+10 | 0.157151E+10 | 0.534287E+10 | 0.290240E+10 | 0.244047E+10 | 0.00 | 0.00 |
October | 0.415126E+10 | 0.343832E+10 | 0.399828E+10 | 0.219083E+10 | 0.180745E+10 | 0.00 | 0.00 |
November | 0.279529E+10 | 0.393919E+10 | 0.301176E+10 | 0.170047E+10 | 0.131129E+10 | 0.00 | 0.00 |
December | 0.227547E+10 | 0.494269E+10 | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652151E+11 | 0.336325E+11 | 0.578403E+11 | 0.307923E+11 | 0.270480E+11 | 0.00 | 0.00 |
Minimum of Months | 0.227547E+10 | 0.967162E+09 | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.00 | 0.00 |
Maximum of Months | 0.924726E+10 | 0.494269E+10 | 0.700306E+10 | 0.367642E+10 | 0.345363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158292E+11 | 0.664112E+10 | 0.141661E+11 | 0.116532E+11 | 0.251296E+10 | 0.00 | 0.00 |
February | 0.135968E+11 | 0.614758E+10 | 0.122730E+11 | 0.978479E+10 | 0.248818E+10 | 0.00 | 0.00 |
March | 0.112511E+11 | 0.539475E+10 | 0.100181E+11 | 0.659132E+10 | 0.342675E+10 | 0.00 | 0.00 |
April | 0.643792E+10 | 0.466063E+10 | 0.627914E+10 | 0.252487E+10 | 0.375427E+10 | 0.00 | 0.00 |
May | 0.667553E+10 | 0.304753E+10 | 0.594594E+10 | 0.108985E+10 | 0.485610E+10 | 0.00 | 0.00 |
June | 0.754071E+10 | 0.162263E+10 | 0.530512E+10 | 0.969628E+09 | 0.433550E+10 | 0.00 | 0.00 |
July | 0.812550E+10 | 0.156180E+10 | 0.570660E+10 | 0.102189E+10 | 0.468470E+10 | 0.00 | 0.00 |
August | 0.103582E+11 | 0.178232E+10 | 0.726566E+10 | 0.303732E+10 | 0.422834E+10 | 0.00 | 0.00 |
September | 0.120705E+11 | 0.261041E+10 | 0.904643E+10 | 0.504786E+10 | 0.399857E+10 | 0.00 | 0.00 |
October | 0.132582E+11 | 0.540781E+10 | 0.111775E+11 | 0.793066E+10 | 0.324679E+10 | 0.00 | 0.00 |
November | 0.150568E+11 | 0.608273E+10 | 0.131789E+11 | 0.105055E+11 | 0.267340E+10 | 0.00 | 0.00 |
December | 0.142814E+11 | 0.728687E+10 | 0.130225E+11 | 0.105402E+11 | 0.248227E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.134482E+12 | 0.522462E+11 | 0.113385E+12 | 0.706971E+11 | 0.426878E+11 | 0.00 | 0.00 |
Minimum of Months | 0.643792E+10 | 0.156180E+10 | 0.530512E+10 | 0.969628E+09 | 0.248227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158292E+11 | 0.728687E+10 | 0.141661E+11 | 0.116532E+11 | 0.485610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.309468E+10 | 0.461054E+10 | 0.328241E+10 | 0.207991E+10 | 0.120249E+10 | 0.00 | 0.00 |
February | 0.334548E+10 | 0.422535E+10 | 0.357507E+10 | 0.221549E+10 | 0.135959E+10 | 0.00 | 0.00 |
March | 0.459958E+10 | 0.360754E+10 | 0.463470E+10 | 0.255707E+10 | 0.207763E+10 | 0.00 | 0.00 |
April | 0.399595E+10 | 0.306683E+10 | 0.422302E+10 | 0.178795E+10 | 0.243506E+10 | 0.00 | 0.00 |
May | 0.596882E+10 | 0.201726E+10 | 0.533366E+10 | 0.188031E+10 | 0.345335E+10 | 0.00 | 0.00 |
June | 0.844426E+10 | 0.115971E+10 | 0.631296E+10 | 0.303741E+10 | 0.327555E+10 | 0.00 | 0.00 |
July | 0.714149E+10 | 0.109175E+10 | 0.531502E+10 | 0.194679E+10 | 0.336823E+10 | 0.00 | 0.00 |
August | 0.733961E+10 | 0.122585E+10 | 0.554737E+10 | 0.274048E+10 | 0.280689E+10 | 0.00 | 0.00 |
September | 0.604288E+10 | 0.173090E+10 | 0.476019E+10 | 0.228283E+10 | 0.247736E+10 | 0.00 | 0.00 |
October | 0.444442E+10 | 0.358335E+10 | 0.413806E+10 | 0.236521E+10 | 0.177285E+10 | 0.00 | 0.00 |
November | 0.318715E+10 | 0.409250E+10 | 0.328597E+10 | 0.199499E+10 | 0.129098E+10 | 0.00 | 0.00 |
December | 0.236712E+10 | 0.507289E+10 | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.599714E+11 | 0.354845E+11 | 0.531511E+11 | 0.265086E+11 | 0.266425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236712E+10 | 0.109175E+10 | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.844426E+10 | 0.507289E+10 | 0.631296E+10 | 0.303741E+10 | 0.345335E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.355745E+09 | 0.646774E+10 | 0.147812E+10 | 0.00 | 0.147812E+10 | 0.00 | 0.00 |
February | 0.395454E+09 | 0.596550E+10 | 0.167803E+10 | 0.00 | 0.167803E+10 | 0.00 | 0.00 |
March | 0.124297E+10 | 0.501059E+10 | 0.252788E+10 | 0.00 | 0.252788E+10 | 0.00 | 0.00 |
April | 0.177550E+10 | 0.407725E+10 | 0.307225E+10 | 17043518.41 | 0.305521E+10 | 0.00 | 0.00 |
May | 0.396813E+10 | 0.261915E+10 | 0.433678E+10 | 0.143356E+09 | 0.419342E+10 | 0.00 | 0.00 |
June | 0.601488E+10 | 0.147497E+10 | 0.460217E+10 | 0.510225E+09 | 0.409194E+10 | 0.00 | 0.00 |
July | 0.594606E+10 | 0.144436E+10 | 0.449748E+10 | 0.291130E+09 | 0.420635E+10 | 0.00 | 0.00 |
August | 0.453751E+10 | 0.163332E+10 | 0.357965E+10 | 84682507.92 | 0.349497E+10 | 0.00 | 0.00 |
September | 0.330547E+10 | 0.235464E+10 | 0.290991E+10 | 683486.50 | 0.290923E+10 | 0.00 | 0.00 |
October | 0.130152E+10 | 0.486075E+10 | 0.215367E+10 | 0.00 | 0.215367E+10 | 0.00 | 0.00 |
November | 0.548451E+09 | 0.562995E+10 | 0.158217E+10 | 0.00 | 0.158217E+10 | 0.00 | 0.00 |
December | 0.296250E+09 | 0.734782E+10 | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.296879E+11 | 0.488860E+11 | 0.338011E+11 | 0.104712E+10 | 0.327540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.296250E+09 | 0.144436E+10 | 0.138297E+10 | 0.00 | 0.138297E+10 | 0.00 | 0.00 |
Maximum of Months | 0.601488E+10 | 0.734782E+10 | 0.460217E+10 | 0.510225E+09 | 0.420635E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.280359E+10 | 0.406188E+10 | 0.308562E+10 | 0.189096E+10 | 0.119466E+10 | 0.00 | 0.00 |
February | 0.349818E+10 | 0.383881E+10 | 0.370223E+10 | 0.233720E+10 | 0.136503E+10 | 0.00 | 0.00 |
March | 0.498644E+10 | 0.324719E+10 | 0.494726E+10 | 0.288569E+10 | 0.206157E+10 | 0.00 | 0.00 |
April | 0.484743E+10 | 0.267124E+10 | 0.491001E+10 | 0.239175E+10 | 0.251826E+10 | 0.00 | 0.00 |
May | 0.664172E+10 | 0.177389E+10 | 0.593105E+10 | 0.247742E+10 | 0.345363E+10 | 0.00 | 0.00 |
June | 0.920975E+10 | 0.989944E+09 | 0.700306E+10 | 0.367642E+10 | 0.332664E+10 | 0.00 | 0.00 |
July | 0.872643E+10 | 0.969238E+09 | 0.657855E+10 | 0.313254E+10 | 0.344601E+10 | 0.00 | 0.00 |
August | 0.874832E+10 | 0.110284E+10 | 0.663537E+10 | 0.365452E+10 | 0.298085E+10 | 0.00 | 0.00 |
September | 0.671232E+10 | 0.152981E+10 | 0.534287E+10 | 0.290240E+10 | 0.244047E+10 | 0.00 | 0.00 |
October | 0.419634E+10 | 0.321070E+10 | 0.399828E+10 | 0.219083E+10 | 0.180745E+10 | 0.00 | 0.00 |
November | 0.287403E+10 | 0.365455E+10 | 0.301176E+10 | 0.170047E+10 | 0.131129E+10 | 0.00 | 0.00 |
December | 0.233806E+10 | 0.466605E+10 | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.655826E+11 | 0.317162E+11 | 0.578403E+11 | 0.307923E+11 | 0.270480E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233806E+10 | 0.969238E+09 | 0.269429E+10 | 0.155210E+10 | 0.114219E+10 | 0.00 | 0.00 |
Maximum of Months | 0.920975E+10 | 0.466605E+10 | 0.700306E+10 | 0.367642E+10 | 0.345363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160086E+11 | 0.610382E+10 | 0.141661E+11 | 0.116532E+11 | 0.251296E+10 | 0.00 | 0.00 |
February | 0.136902E+11 | 0.576466E+10 | 0.122730E+11 | 0.978479E+10 | 0.248818E+10 | 0.00 | 0.00 |
March | 0.113213E+11 | 0.505739E+10 | 0.100181E+11 | 0.659132E+10 | 0.342675E+10 | 0.00 | 0.00 |
April | 0.651041E+10 | 0.427047E+10 | 0.627914E+10 | 0.252487E+10 | 0.375427E+10 | 0.00 | 0.00 |
May | 0.673422E+10 | 0.288633E+10 | 0.594594E+10 | 0.108985E+10 | 0.485610E+10 | 0.00 | 0.00 |
June | 0.750912E+10 | 0.160479E+10 | 0.530512E+10 | 0.969628E+09 | 0.433550E+10 | 0.00 | 0.00 |
July | 0.809156E+10 | 0.154634E+10 | 0.570660E+10 | 0.102189E+10 | 0.468470E+10 | 0.00 | 0.00 |
August | 0.103282E+11 | 0.176058E+10 | 0.726566E+10 | 0.303732E+10 | 0.422834E+10 | 0.00 | 0.00 |
September | 0.120708E+11 | 0.252316E+10 | 0.904643E+10 | 0.504786E+10 | 0.399857E+10 | 0.00 | 0.00 |
October | 0.133227E+11 | 0.504504E+10 | 0.111775E+11 | 0.793066E+10 | 0.324679E+10 | 0.00 | 0.00 |
November | 0.151740E+11 | 0.565118E+10 | 0.131789E+11 | 0.105055E+11 | 0.267340E+10 | 0.00 | 0.00 |
December | 0.144124E+11 | 0.682848E+10 | 0.130225E+11 | 0.105402E+11 | 0.248227E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135173E+12 | 0.490423E+11 | 0.113385E+12 | 0.706971E+11 | 0.426878E+11 | 0.00 | 0.00 |
Minimum of Months | 0.651041E+10 | 0.154634E+10 | 0.530512E+10 | 0.969628E+09 | 0.248227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.160086E+11 | 0.682848E+10 | 0.141661E+11 | 0.116532E+11 | 0.485610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315183E+10 | 0.427659E+10 | 0.328241E+10 | 0.207991E+10 | 0.120249E+10 | 0.00 | 0.00 |
February | 0.337484E+10 | 0.399567E+10 | 0.357507E+10 | 0.221549E+10 | 0.135959E+10 | 0.00 | 0.00 |
March | 0.462802E+10 | 0.340375E+10 | 0.463470E+10 | 0.255707E+10 | 0.207763E+10 | 0.00 | 0.00 |
April | 0.403271E+10 | 0.283654E+10 | 0.422302E+10 | 0.178795E+10 | 0.243506E+10 | 0.00 | 0.00 |
May | 0.599690E+10 | 0.192667E+10 | 0.533366E+10 | 0.188031E+10 | 0.345335E+10 | 0.00 | 0.00 |
June | 0.842045E+10 | 0.115104E+10 | 0.631296E+10 | 0.303741E+10 | 0.327555E+10 | 0.00 | 0.00 |
July | 0.711894E+10 | 0.108048E+10 | 0.531502E+10 | 0.194679E+10 | 0.336823E+10 | 0.00 | 0.00 |
August | 0.732342E+10 | 0.121308E+10 | 0.554737E+10 | 0.274048E+10 | 0.280689E+10 | 0.00 | 0.00 |
September | 0.604789E+10 | 0.167618E+10 | 0.476019E+10 | 0.228283E+10 | 0.247736E+10 | 0.00 | 0.00 |
October | 0.447794E+10 | 0.336474E+10 | 0.413806E+10 | 0.236521E+10 | 0.177285E+10 | 0.00 | 0.00 |
November | 0.323282E+10 | 0.382834E+10 | 0.328597E+10 | 0.199499E+10 | 0.129098E+10 | 0.00 | 0.00 |
December | 0.240063E+10 | 0.480552E+10 | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.602064E+11 | 0.335586E+11 | 0.531511E+11 | 0.265086E+11 | 0.266425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.240063E+10 | 0.108048E+10 | 0.274264E+10 | 0.162015E+10 | 0.112249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.842045E+10 | 0.480552E+10 | 0.631296E+10 | 0.303741E+10 | 0.345335E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.411787E+11 | -0.401524E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102630E+10 | 58.98 | 0.00 | 0.00 |
February | 0.378665E+11 | -0.369394E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -927107321.3 | 58.97 | 0.00 | 0.00 |
March | 0.438411E+11 | -0.428117E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102943E+10 | 58.98 | 0.00 | 0.00 |
April | 0.382813E+11 | -0.372895E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991753960.5 | 58.97 | 0.00 | 0.00 |
May | 0.386450E+11 | -0.376204E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102455E+10 | 58.98 | 0.00 | 0.00 |
June | 0.360732E+11 | -0.350819E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991312862.0 | 58.98 | 0.00 | 0.00 |
July | 0.328560E+11 | -0.318371E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101891E+10 | 58.97 | 0.00 | 0.00 |
August | 0.353219E+11 | -0.342992E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102272E+10 | 58.98 | 0.00 | 0.00 |
September | 0.327061E+11 | -0.317186E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987570941.3 | 58.98 | 0.00 | 0.00 |
October | 0.353521E+11 | -0.343321E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102004E+10 | 58.97 | 0.00 | 0.00 |
November | 0.367755E+11 | -0.357877E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987802263.8 | 58.98 | 0.00 | 0.00 |
December | 0.387009E+11 | -0.376768E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102406E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.447598E+12 | -0.435547E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120516E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.327061E+11 | -0.428117E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102943E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.438411E+11 | -0.317186E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -927107321.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143869E+11 | 67961.22 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136439E+11 | 51085.49 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730072E+10 | 46428.65 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324902E+10 | 36887.82 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208610E+09 | 17284.92 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296722E+09 | 21582.00 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.516412E+10 | 45056.55 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808806E+10 | 58164.27 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194167E+11 | 73793.69 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.717548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194167E+11 | 73793.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314144E+09 | 15207.71 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311135E+09 | 14121.09 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22554545.93 | 14186.44 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6956663.82 | 4934.31 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70478126.15 | 14267.93 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115808E+09 | 15196.92 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.647576E+09 | 14186.11 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.647576E+09 | 15207.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.490587E+09 | 13606.99 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603810E+09 | 13625.06 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247190E+09 | 13245.02 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92102912.50 | 13587.61 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2198134.77 | 928.30 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240434E+09 | 13581.63 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366176E+09 | 13595.90 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.988291E+09 | 13589.08 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.988291E+09 | 13625.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.399365E+09 | 18764.34 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.619012E+09 | 19307.32 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272238E+09 | 18782.70 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167674E+09 | 19351.71 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4139765.89 | 9099.87 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3837698.27 | 970.79 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338517E+09 | 19343.04 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297069E+09 | 19266.40 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769547E+09 | 18764.98 | 21-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769547E+09 | 19351.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226496E+09 | 12063.13 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136503E+09 | 12066.90 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3022580.31 | 923.51 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52192284.13 | 11258.55 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30647133.60 | 12066.81 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137577E+09 | 12061.38 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226496E+09 | 12066.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225464E+12 | 706951.56 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223145E+12 | 570113.38 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150934E+12 | 520296.62 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.934321E+11 | 474923.56 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.850322E+10 | 264235.45 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.543535E+10 | 291721.54 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104898E+12 | 528103.34 | 30-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176223E+12 | 640231.47 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315684E+12 | 736386.48 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130372E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315684E+12 | 736386.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.901711E+09 | 555287.54 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321673E+09 | 415542.58 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237307E+10 | 558265.81 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237307E+10 | 558265.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226203E+11 | 133819.14 | 31-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287495E+11 | 137544.77 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155762E+11 | 133838.08 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804805E+10 | 144395.81 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486561E+09 | 134694.77 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144793E+09 | 92607.17 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.907769E+10 | 133821.55 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171980E+11 | 143792.20 | 15-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458771E+11 | 144544.16 | 23-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.458771E+11 | 144544.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195477E+11 | 173442.32 | 18-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220780E+11 | 173918.44 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147261E+11 | 173546.12 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882048E+10 | 173426.75 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.516188E+09 | 173381.14 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251674E+09 | 87481.02 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109360E+11 | 173468.49 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167550E+11 | 177809.40 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363651E+11 | 173506.09 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.363651E+11 | 177809.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.940654E+10 | 189456.97 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164771E+11 | 190786.93 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132237E+11 | 190089.72 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834079E+10 | 190087.94 | 24-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.720353E+09 | 189332.99 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177799E+09 | 80087.63 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.903934E+10 | 189589.16 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940548E+10 | 189582.47 | 01-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245357E+11 | 190893.20 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.913269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245357E+11 | 190893.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183232E+11 | 176787.25 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206016E+11 | 177372.31 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136660E+11 | 176960.21 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.799041E+10 | 176747.66 | 03-APR-04:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.703400E+09 | 176801.68 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.374107E+09 | 98028.42 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.964153E+10 | 176906.51 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150194E+11 | 176900.52 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323361E+11 | 176853.72 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118656E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323361E+11 | 177372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276477E+11 | 69300.71 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270547E+11 | 60506.70 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187542E+11 | 56927.01 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118172E+11 | 51313.10 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136107E+10 | 30364.32 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2280128.66 | 2622.20 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.887640E+09 | 34213.12 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141181E+11 | 57122.94 | 30-OCT-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222667E+11 | 66162.45 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360341E+11 | 73102.68 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360341E+11 | 73102.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499080E+10 | 84603.98 | 09-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488036E+10 | 84545.61 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253096E+10 | 84594.52 | 20-MAR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248822E+10 | 84597.32 | 24-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249452E+09 | 85006.38 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190738E+10 | 84524.65 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279564E+10 | 84848.60 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765454E+10 | 84328.97 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.765454E+10 | 85006.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.745523E+10 | 16422.38 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.757198E+10 | 15783.49 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504065E+10 | 15825.91 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.345987E+10 | 15785.34 | 24-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.394815E+09 | 15824.05 | 01-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185613E+09 | 15623.98 | 22-SEP-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353117E+10 | 15782.72 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.553112E+10 | 15825.23 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109347E+11 | 18158.03 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109347E+11 | 18158.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460009E+10 | 18129.38 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.455695E+10 | 18128.15 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328520E+10 | 18125.76 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236227E+10 | 18025.15 | 24-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.258650E+09 | 18111.32 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 202932.40 | 997.88 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133754E+09 | 17914.21 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264111E+10 | 18137.73 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370843E+10 | 18138.06 | 24-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718990E+10 | 18127.71 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718990E+10 | 18138.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352630E+10 | 21338.79 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453223E+10 | 21259.10 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398753E+10 | 21344.28 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331826E+10 | 21337.32 | 24-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511810E+09 | 21326.86 | 01-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150655E+09 | 21066.17 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298538E+10 | 21333.86 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312009E+10 | 21334.24 | 24-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.647984E+10 | 23923.10 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.647984E+10 | 23923.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.443651E+10 | 21126.02 | 09-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440527E+10 | 21119.51 | 08-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326974E+10 | 21128.84 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227964E+10 | 21201.85 | 24-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.392599E+09 | 21129.72 | 01-MAY-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3616953.05 | 1769.61 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196126E+09 | 21107.22 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251470E+10 | 21235.32 | 30-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351162E+10 | 21237.90 | 02-NOV-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655181E+10 | 21223.66 | 08-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.655181E+10 | 21237.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.340075E+10 | 0.340075E+10 | 61239.32 | 20-JAN-14:00 | 61239.32 | 0.00 |
February | 0.00 | 0.00 | 0.115709E+10 | 0.115709E+10 | 38109.36 | 18-FEB-13:10 | 38109.36 | 0.00 |
March | 0.00 | 0.00 | 0.100715E+11 | 0.100715E+11 | 98644.80 | 13-MAR-16:00 | 98644.80 | 0.00 |
April | 0.00 | 0.00 | 0.109989E+11 | 0.109989E+11 | 85338.73 | 19-APR-13:50 | 85338.73 | 0.01 |
May | 0.00 | 0.00 | 0.351665E+11 | 0.351665E+11 | 113320.33 | 31-MAY-15:20 | 113320.33 | 0.04 |
June | 0.00 | 0.00 | 0.116399E+12 | 0.116183E+12 | 160005.27 | 26-JUN-15:20 | 160005.27 | 0.28 |
July | 0.00 | 0.00 | 0.123683E+12 | 0.120609E+12 | 149677.89 | 17-JUL-13:30 | 149677.89 | 0.34 |
August | 0.00 | 0.00 | 0.131317E+12 | 0.130218E+12 | 160865.05 | 16-AUG-14:40 | 160865.05 | 0.43 |
September | 0.00 | 0.00 | 0.762415E+11 | 0.762415E+11 | 136164.84 | 12-SEP-16:00 | 136164.84 | 0.06 |
October | 0.00 | 0.00 | 0.159666E+11 | 0.159666E+11 | 117385.97 | 10-OCT-16:00 | 117385.97 | 0.00 |
November | 0.00 | 0.00 | 0.645336E+10 | 0.645336E+10 | 83312.87 | 07-NOV-15:00 | 83312.87 | 0.00 |
December | 0.00 | 0.00 | 0.387303E+10 | 0.387303E+10 | 71747.10 | 01-DEC-14:00 | 71747.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.534728E+12 | 0.530338E+12 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.115709E+10 | 0.115709E+10 | 38109.36 | 38109.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131317E+12 | 0.130218E+12 | 160865.05 | 160865.05 | 0.43 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.295701E+11 | 0.295701E+11 | 526522.36 | 20-JAN-14:00 | 526522.36 | 0.00 |
February | 0.00 | 0.00 | 0.110700E+11 | 0.110700E+11 | 384174.62 | 18-FEB-14:00 | 384174.62 | 0.00 |
March | 0.00 | 0.00 | 0.804468E+11 | 0.804468E+11 | 789965.12 | 14-MAR-13:00 | 789965.12 | 0.00 |
April | 0.00 | 0.00 | 0.702111E+11 | 0.702111E+11 | 610209.41 | 20-APR-13:00 | 610209.41 | 0.01 |
May | 0.00 | 0.00 | 0.304209E+12 | 0.304209E+12 | 1049137.11 | 17-MAY-13:30 | 1049137.11 | 0.04 |
June | 0.00 | 0.00 | 0.101167E+13 | 0.101009E+13 | 1482857.18 | 26-JUN-15:20 | 1482857.18 | 0.26 |
July | 0.00 | 0.00 | 0.101611E+13 | 0.995293E+12 | 1352016.49 | 17-JUL-13:30 | 1352016.49 | 0.29 |
August | 0.00 | 0.00 | 0.975237E+12 | 0.971204E+12 | 1431180.62 | 16-AUG-15:10 | 1431180.62 | 0.29 |
September | 0.00 | 0.00 | 0.670335E+12 | 0.670335E+12 | 1263779.37 | 12-SEP-16:00 | 1263779.37 | 0.05 |
October | 0.00 | 0.00 | 0.136999E+12 | 0.136999E+12 | 990275.70 | 11-OCT-15:00 | 990275.70 | 0.00 |
November | 0.00 | 0.00 | 0.500145E+11 | 0.500145E+11 | 656669.71 | 07-NOV-15:00 | 656669.71 | 0.00 |
December | 0.00 | 0.00 | 0.275609E+11 | 0.275609E+11 | 522858.89 | 01-DEC-14:00 | 522858.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438344E+13 | 0.435700E+13 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.110700E+11 | 0.110700E+11 | 384174.62 | 384174.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101611E+13 | 0.101009E+13 | 1482857.18 | 1482857.18 | 0.29 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.218077E+10 | 0.218077E+10 | 50324.62 | 20-JAN-14:00 | 50324.62 | 0.00 |
February | 0.00 | 0.00 | 0.809522E+09 | 0.809522E+09 | 36151.56 | 18-FEB-13:30 | 36151.56 | 0.00 |
March | 0.00 | 0.00 | 0.730211E+10 | 0.730211E+10 | 81867.46 | 14-MAR-13:00 | 81867.46 | 0.00 |
April | 0.00 | 0.00 | 0.708119E+10 | 0.708119E+10 | 66895.49 | 20-APR-13:00 | 66895.49 | 0.00 |
May | 0.00 | 0.00 | 0.313792E+11 | 0.313792E+11 | 128502.57 | 31-MAY-15:20 | 128502.57 | 0.03 |
June | 0.00 | 0.00 | 0.115442E+12 | 0.115306E+12 | 184594.91 | 26-JUN-15:20 | 184594.91 | 0.25 |
July | 0.00 | 0.00 | 0.113984E+12 | 0.111921E+12 | 165339.42 | 17-JUL-14:00 | 165339.42 | 0.28 |
August | 0.00 | 0.00 | 0.109467E+12 | 0.109112E+12 | 178833.81 | 16-AUG-15:10 | 178833.81 | 0.27 |
September | 0.00 | 0.00 | 0.704405E+11 | 0.704405E+11 | 148009.42 | 12-SEP-16:00 | 148009.42 | 0.05 |
October | 0.00 | 0.00 | 0.122832E+11 | 0.122832E+11 | 112139.76 | 11-OCT-15:00 | 112139.76 | 0.00 |
November | 0.00 | 0.00 | 0.401911E+10 | 0.401911E+10 | 63744.37 | 07-NOV-15:00 | 63744.37 | 0.00 |
December | 0.00 | 0.00 | 0.209233E+10 | 0.209233E+10 | 48153.66 | 01-DEC-14:00 | 48153.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.476481E+12 | 0.473927E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.809522E+09 | 0.809522E+09 | 36151.56 | 36151.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115442E+12 | 0.115306E+12 | 184594.91 | 184594.91 | 0.28 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121314E+10 | 0.121314E+10 | 34244.67 | 20-JAN-14:00 | 34244.67 | 0.00 |
February | 0.00 | 0.00 | 0.100168E+09 | 0.100168E+09 | 12338.57 | 18-FEB-13:00 | 12338.57 | 0.00 |
March | 0.00 | 0.00 | 0.398921E+10 | 0.398921E+10 | 59038.36 | 14-MAR-13:00 | 59038.36 | 0.00 |
April | 0.00 | 0.00 | 0.468337E+10 | 0.468337E+10 | 44262.66 | 20-APR-13:00 | 44262.66 | 0.00 |
May | 0.00 | 0.00 | 0.202976E+11 | 0.202928E+11 | 62953.11 | 31-MAY-14:00 | 62953.11 | 0.03 |
June | 0.00 | 0.00 | 0.632655E+11 | 0.632185E+11 | 83812.93 | 26-JUN-15:00 | 83812.93 | 0.22 |
July | 0.00 | 0.00 | 0.640943E+11 | 0.633375E+11 | 86723.80 | 28-JUL-05:03 | 38719.91 | 0.25 |
August | 0.00 | 0.00 | 0.681699E+11 | 0.679417E+11 | 103881.56 | 20-AUG-14:58 | 103881.56 | 0.25 |
September | 0.00 | 0.00 | 0.466709E+11 | 0.466659E+11 | 105065.58 | 10-SEP-15:54 | 105065.58 | 0.04 |
October | 0.00 | 0.00 | 0.804675E+10 | 0.804675E+10 | 73287.21 | 10-OCT-14:00 | 73287.21 | 0.00 |
November | 0.00 | 0.00 | 0.299240E+10 | 0.299240E+10 | 55429.30 | 06-NOV-13:10 | 55429.30 | 0.00 |
December | 0.00 | 0.00 | 0.164272E+10 | 0.164272E+10 | 42944.11 | 04-DEC-12:00 | 42944.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.285166E+12 | 0.284124E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.100168E+09 | 0.100168E+09 | 12338.57 | 12338.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.681699E+11 | 0.679417E+11 | 105065.58 | 105065.58 | 0.25 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397129E+12 | 0.346598E+12 | 153260.94 | 19-JAN-22:10 | 133435.21 | 0.00 |
February | 0.00 | 0.00 | 0.613257E+12 | 0.534587E+12 | 259849.00 | 17-FEB-22:03 | 225926.46 | 0.00 |
March | 0.00 | 0.00 | 0.962611E+12 | 0.842360E+12 | 462606.76 | 31-MAR-24:00 | 405027.95 | 0.00 |
April | 0.00 | 0.00 | 0.121359E+13 | 0.105076E+13 | 480066.16 | 18-APR-21:03 | 406897.23 | 0.00 |
May | 0.00 | 0.00 | 0.405068E+12 | 0.355143E+12 | 251523.33 | 31-MAY-24:00 | 221147.70 | 0.00 |
June | 0.00 | 0.00 | 0.648129E+12 | 0.586270E+12 | 343406.95 | 30-JUN-24:00 | 313269.58 | 0.00 |
July | 0.00 | 0.00 | 0.933758E+12 | 0.852256E+12 | 446196.91 | 31-JUL-24:00 | 397151.92 | 0.00 |
August | 0.00 | 0.00 | 0.123100E+13 | 0.107978E+13 | 486320.20 | 17-AUG-02:54 | 413099.29 | 0.00 |
September | 0.00 | 0.00 | 0.394486E+12 | 0.349895E+12 | 253671.27 | 30-SEP-24:00 | 221431.79 | 0.00 |
October | 0.00 | 0.00 | 0.687823E+12 | 0.600909E+12 | 359100.59 | 31-OCT-23:45 | 312527.36 | 0.00 |
November | 0.00 | 0.00 | 0.937370E+12 | 0.818404E+12 | 367467.20 | 07-NOV-22:03 | 319983.00 | 0.00 |
December | 0.00 | 0.00 | 0.125770E+13 | 0.108576E+13 | 480668.07 | 03-DEC-17:03 | 410673.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.968192E+13 | 0.850271E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.394486E+12 | 0.346598E+12 | 153260.94 | 133435.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125770E+13 | 0.108576E+13 | 486320.20 | 413099.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.464237E+10 | 0.463372E+10 | 2908.43 | 23-JAN-16:30 | 2908.43 | 0.00 |
February | 0.00 | 0.00 | 0.885759E+10 | 0.885348E+10 | 4868.97 | 17-FEB-17:00 | 4848.29 | 0.00 |
March | 0.00 | 0.00 | 0.154470E+11 | 0.154356E+11 | 7843.39 | 31-MAR-24:00 | 7843.39 | 0.00 |
April | 0.00 | 0.00 | 0.202298E+11 | 0.202031E+11 | 8911.82 | 08-APR-18:14 | 8911.82 | 0.00 |
May | 0.00 | 0.00 | 0.598688E+10 | 0.593387E+10 | 4198.17 | 31-MAY-24:00 | 4178.94 | 0.00 |
June | 0.00 | 0.00 | 0.112865E+11 | 0.111802E+11 | 6026.22 | 30-JUN-23:35 | 6026.22 | 0.00 |
July | 0.00 | 0.00 | 0.166798E+11 | 0.165471E+11 | 7954.22 | 31-JUL-23:52 | 7954.22 | 0.00 |
August | 0.00 | 0.00 | 0.220303E+11 | 0.219203E+11 | 9205.49 | 05-AUG-18:53 | 9169.83 | 0.00 |
September | 0.00 | 0.00 | 0.609509E+10 | 0.605527E+10 | 4028.18 | 30-SEP-24:00 | 4028.18 | 0.00 |
October | 0.00 | 0.00 | 0.106206E+11 | 0.106023E+11 | 5348.49 | 09-OCT-16:45 | 5348.49 | 0.00 |
November | 0.00 | 0.00 | 0.149467E+11 | 0.149327E+11 | 6924.51 | 05-NOV-16:17 | 6924.51 | 0.00 |
December | 0.00 | 0.00 | 0.202549E+11 | 0.202549E+11 | 8791.43 | 03-DEC-16:13 | 8791.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157078E+12 | 0.156553E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.464237E+10 | 0.463372E+10 | 2908.43 | 2908.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220303E+11 | 0.219203E+11 | 9205.49 | 9169.83 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.289921E+11 | 0.289090E+11 | 26443.00 | 23-JAN-16:40 | 26443.00 | 0.00 |
February | 0.00 | 0.00 | 0.690355E+11 | 0.689941E+11 | 45192.93 | 17-FEB-17:00 | 44915.31 | 0.00 |
March | 0.00 | 0.00 | 0.133189E+12 | 0.133074E+12 | 72638.49 | 31-MAR-23:50 | 72638.49 | 0.00 |
April | 0.00 | 0.00 | 0.178170E+12 | 0.177902E+12 | 83099.32 | 08-APR-17:48 | 83099.32 | 0.00 |
May | 0.00 | 0.00 | 0.513007E+11 | 0.507785E+11 | 39591.17 | 31-MAY-24:00 | 39380.45 | 0.00 |
June | 0.00 | 0.00 | 0.106047E+12 | 0.104988E+12 | 58877.40 | 30-JUN-23:55 | 58877.40 | 0.00 |
July | 0.00 | 0.00 | 0.158078E+12 | 0.156754E+12 | 74861.16 | 31-JUL-23:52 | 74861.16 | 0.00 |
August | 0.00 | 0.00 | 0.205438E+12 | 0.204340E+12 | 86011.44 | 05-AUG-18:12 | 85689.13 | 0.00 |
September | 0.00 | 0.00 | 0.537677E+11 | 0.533754E+11 | 36309.20 | 30-SEP-24:00 | 36309.20 | 0.00 |
October | 0.00 | 0.00 | 0.902208E+11 | 0.900389E+11 | 47943.44 | 09-OCT-16:43 | 47943.44 | 0.00 |
November | 0.00 | 0.00 | 0.127974E+12 | 0.127835E+12 | 64354.33 | 07-NOV-16:10 | 64354.33 | 0.00 |
December | 0.00 | 0.00 | 0.169136E+12 | 0.169136E+12 | 78941.85 | 01-DEC-16:00 | 78941.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137135E+13 | 0.136612E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.289921E+11 | 0.289090E+11 | 26443.00 | 26443.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205438E+12 | 0.204340E+12 | 86011.44 | 85689.13 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127828E+10 | 0.127124E+10 | 2629.28 | 20-JAN-16:30 | 2629.28 | 0.00 |
February | 0.00 | 0.00 | 0.517222E+10 | 0.516820E+10 | 4497.06 | 17-FEB-17:00 | 4473.77 | 0.00 |
March | 0.00 | 0.00 | 0.118783E+11 | 0.118670E+11 | 7025.55 | 31-MAR-23:20 | 7025.55 | 0.00 |
April | 0.00 | 0.00 | 0.163433E+11 | 0.163166E+11 | 8348.15 | 07-APR-17:40 | 8348.15 | 0.00 |
May | 0.00 | 0.00 | 0.457727E+10 | 0.452555E+10 | 3906.26 | 31-MAY-23:50 | 3882.90 | 0.00 |
June | 0.00 | 0.00 | 0.106291E+11 | 0.105232E+11 | 5858.22 | 30-JUN-23:08 | 5858.22 | 0.00 |
July | 0.00 | 0.00 | 0.158401E+11 | 0.157079E+11 | 7375.97 | 31-JUL-23:52 | 7375.97 | 0.00 |
August | 0.00 | 0.00 | 0.205474E+11 | 0.204378E+11 | 8735.76 | 13-AUG-18:42 | 8735.76 | 0.00 |
September | 0.00 | 0.00 | 0.507776E+10 | 0.503871E+10 | 3496.58 | 10-SEP-17:35 | 3496.58 | 0.00 |
October | 0.00 | 0.00 | 0.759508E+10 | 0.757730E+10 | 4758.59 | 08-OCT-16:50 | 4758.59 | 0.00 |
November | 0.00 | 0.00 | 0.109646E+11 | 0.109509E+11 | 6439.22 | 07-NOV-16:10 | 6439.22 | 0.00 |
December | 0.00 | 0.00 | 0.148301E+11 | 0.148301E+11 | 7849.30 | 01-DEC-16:00 | 7849.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124734E+12 | 0.124215E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127828E+10 | 0.127124E+10 | 2629.28 | 2629.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205474E+11 | 0.204378E+11 | 8735.76 | 8735.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 134627.32 | 1392729.75 | 05-JAN-07:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 155772.47 | 1599759.33 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 93667.78 | 1589488.59 | 20-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 59592.81 | 1207090.61 | 03-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5298.37 | 1273844.30 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.85 | 2562.60 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 1.31 | 2604.64 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 3152.60 | 513345.41 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 65593.84 | 1285832.13 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 108744.02 | 1262785.08 | 29-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 205000.06 | 1870765.44 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 68866.26 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 205000.06 | 1870765.44 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27647.85 | 1133540.00 | 20-JAN-14:40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 13270.13 | 937199.71 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64629.63 | 1237007.59 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 68082.74 | 1210876.14 | 19-APR-14:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 223734.43 | 1366296.62 | 31-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 634479.58 | 1926318.08 | 26-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 628296.27 | 1771456.19 | 17-JUL-13:30 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 606485.42 | 1854821.91 | 16-AUG-15:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 452899.19 | 1626638.17 | 12-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 107900.72 | 1303721.33 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45661.55 | 1174438.80 | 06-NOV-12:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26962.03 | 1168776.59 | 01-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 242905.76 | 0.00 | ||||
Minimum of Months | 13270.13 | 937199.71 | 0.00 | 0.00 | ||
Maximum of Months | 634479.58 | 1926318.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15679.90 | 794201.86 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 5984.96 | 542926.42 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43686.38 | 1229626.64 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 40127.03 | 906956.20 | 20-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 160393.89 | 1355901.65 | 31-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 536515.36 | 1917651.47 | 26-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 524740.36 | 1926622.15 | 24-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 510484.88 | 2146921.64 | 04-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 358740.06 | 1618794.78 | 12-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 72901.18 | 1293134.14 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28304.46 | 1028634.37 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14859.62 | 803385.75 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 193707.72 | 0.00 | ||||
Minimum of Months | 5984.96 | 542926.42 | 0.00 | 0.00 | ||
Maximum of Months | 536515.36 | 2146921.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 210437.29 | 514377.90 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 367757.82 | 693934.85 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 563806.07 | 1208130.54 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 750469.93 | 1350021.72 | 19-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 315258.52 | 988400.91 | 17-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 858956.34 | 1883623.96 | 26-JUN-15:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1146692.81 | 1992617.76 | 16-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1355356.98 | 2263589.39 | 16-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 470956.98 | 1189620.51 | 10-SEP-13:40 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 421264.83 | 1137072.12 | 11-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 551268.36 | 1105929.73 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 702865.07 | 1321952.56 | 02-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 645021.63 | 0.00 | ||||
Minimum of Months | 210437.29 | 514377.90 | 0.00 | 0.00 | ||
Maximum of Months | 1355356.98 | 2263589.39 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16398.34 | 55393.86 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16672.14 | 55523.10 | 17-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17385.98 | 55311.08 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15795.25 | 53606.49 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15456.57 | 51232.13 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14942.10 | 48217.45 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 13298.21 | 45599.81 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14213.86 | 44350.24 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 13651.50 | 45785.80 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14230.70 | 48476.62 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15219.07 | 51378.62 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15473.33 | 53824.94 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15219.79 | ||||
Minimum of Months | 0.00 | 0.00 | 13298.21 | 44350.24 | ||
Maximum of Months | 0.00 | 0.00 | 17385.98 | 55523.10 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16738.99 | 813767.06 | 20-JAN-14:00 | 1481.23 | 118879.50 | 13-JAN-16:00 |
February | 6754.10 | 558184.90 | 18-FEB-13:30 | 1601.30 | 119116.52 | 14-FEB-07:00 |
March | 47639.30 | 2011671.52 | 14-MAR-12:20 | 1487.75 | 121461.50 | 19-MAR-06:50 |
April | 42885.62 | 889786.99 | 20-APR-13:10 | 1362.76 | 119880.80 | 24-APR-05:50 |
May | 195972.48 | 2304984.34 | 31-MAY-15:50 | 871.46 | 102671.09 | 02-MAY-10:10 |
June | 671746.17 | 2387385.83 | 26-JUN-15:20 | 473.88 | 70208.99 | 09-JUN-04:02 |
July | 656673.80 | 2312569.60 | 24-JUL-11:40 | 330.16 | 47698.86 | 01-JUL-03:55 |
August | 637862.05 | 2411858.29 | 16-AUG-15:20 | 715.80 | 63222.35 | 19-AUG-01:00 |
September | 455749.86 | 2308620.85 | 12-SEP-12:40 | 758.11 | 105728.85 | 21-SEP-15:50 |
October | 84855.39 | 2203336.50 | 11-OCT-15:00 | 1246.81 | 102001.74 | 25-OCT-05:30 |
November | 29530.58 | 988818.63 | 07-NOV-15:00 | 1306.16 | 113462.64 | 27-NOV-07:00 |
December | 15844.90 | 824674.69 | 01-DEC-14:20 | 891.81 | 120067.05 | 07-DEC-15:00 |
Annual Sum or Average | 239752.54 | 1040.11 | ||||
Minimum of Months | 6754.10 | 558184.90 | 330.16 | 47698.86 | ||
Maximum of Months | 671746.17 | 2411858.29 | 1601.30 | 121461.50 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193701E+11 | 1.06 | 12675.43 | 01-JAN-00:15 | 1.86 |
February | 0.173281E+11 | 1.05 | 12675.43 | 01-FEB-05:01 | 1.86 |
March | 0.203173E+11 | 1.11 | 12675.43 | 01-MAR-04:55 | 1.85 |
April | 0.189360E+11 | 1.07 | 12675.43 | 01-APR-03:02 | 1.86 |
May | 0.200941E+11 | 1.10 | 12675.43 | 01-MAY-03:01 | 1.85 |
June | 0.201818E+11 | 1.13 | 12675.43 | 01-JUN-03:01 | 1.84 |
July | 0.199690E+11 | 1.08 | 12675.43 | 01-JUL-03:02 | 1.86 |
August | 0.222029E+11 | 1.21 | 12675.43 | 01-AUG-03:02 | 1.85 |
September | 0.208407E+11 | 1.17 | 12675.43 | 01-SEP-03:02 | 1.84 |
October | 0.207827E+11 | 1.14 | 12675.43 | 01-OCT-17:55 | 1.84 |
November | 0.193812E+11 | 1.10 | 12675.43 | 01-NOV-04:01 | 1.86 |
December | 0.191992E+11 | 1.05 | 12675.43 | 01-DEC-04:50 | 1.86 |
Annual Sum or Average | 0.238603E+12 | 1.11 | |||
Minimum of Months | 0.173281E+11 | 1.05 | 12675.43 | 1.84 | |
Maximum of Months | 0.222029E+11 | 1.21 | 12675.43 | 1.86 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.685727E+10 | 0.46 | 16355.65 | 07-JAN-06:01 | 1.69 |
February | 0.658822E+10 | 0.47 | 16096.44 | 09-FEB-06:01 | 1.67 |
March | 0.976979E+10 | 0.57 | 17981.34 | 14-MAR-14:30 | 1.79 |
April | 0.107384E+11 | 0.59 | 19771.76 | 07-APR-14:40 | 1.90 |
May | 0.109446E+11 | 0.60 | 16562.63 | 18-MAY-14:30 | 1.69 |
June | 0.168729E+11 | 0.83 | 26774.59 | 26-JUN-05:02 | 2.28 |
July | 0.171026E+11 | 0.82 | 26774.59 | 10-JUL-05:02 | 2.29 |
August | 0.210295E+11 | 0.98 | 26774.59 | 07-AUG-10:00 | 2.28 |
September | 0.124575E+11 | 0.67 | 26774.59 | 11-SEP-05:03 | 2.29 |
October | 0.921254E+10 | 0.54 | 19759.04 | 10-OCT-16:00 | 1.90 |
November | 0.858077E+10 | 0.53 | 17039.90 | 06-NOV-15:40 | 1.73 |
December | 0.813067E+10 | 0.50 | 18777.47 | 04-DEC-15:30 | 1.84 |
Annual Sum or Average | 0.138285E+12 | 0.63 | |||
Minimum of Months | 0.658822E+10 | 0.46 | 16096.44 | 1.67 | |
Maximum of Months | 0.210295E+11 | 0.98 | 26774.59 | 2.29 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.501432E+11 | 0.41 | 138870.63 | 11-JAN-06:02 | 1.58 |
February | 0.464443E+11 | 0.43 | 140550.29 | 25-FEB-06:02 | 1.60 |
March | 0.629973E+11 | 0.48 | 127912.59 | 08-MAR-06:03 | 1.51 |
April | 0.559677E+11 | 0.43 | 156664.32 | 26-APR-05:02 | 1.71 |
May | 0.848468E+11 | 0.53 | 158759.88 | 18-MAY-14:30 | 1.72 |
June | 0.136206E+12 | 0.73 | 194388.45 | 15-JUN-15:00 | 1.94 |
July | 0.127872E+12 | 0.68 | 249476.10 | 24-JUL-05:02 | 2.27 |
August | 0.130680E+12 | 0.70 | 207966.42 | 17-AUG-15:20 | 2.04 |
September | 0.987630E+11 | 0.60 | 193436.37 | 13-SEP-15:40 | 1.94 |
October | 0.627162E+11 | 0.46 | 137693.24 | 28-OCT-05:03 | 1.57 |
November | 0.523138E+11 | 0.43 | 149047.07 | 14-NOV-06:01 | 1.66 |
December | 0.487918E+11 | 0.43 | 136633.67 | 15-DEC-06:03 | 1.58 |
Annual Sum or Average | 0.957742E+12 | 0.53 | |||
Minimum of Months | 0.464443E+11 | 0.41 | 127912.59 | 1.51 | |
Maximum of Months | 0.136206E+12 | 0.73 | 249476.10 | 2.27 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.513860E+10 | 0.45 | 7420.57 | 20-JAN-16:30 | 1.02 |
February | 0.465643E+10 | 0.45 | 5977.41 | 09-FEB-06:01 | 0.91 |
March | 0.587677E+10 | 0.48 | 13013.13 | 15-MAR-16:00 | 1.43 |
April | 0.552008E+10 | 0.45 | 13561.88 | 21-APR-13:40 | 1.46 |
May | 0.727661E+10 | 0.46 | 17436.55 | 31-MAY-16:00 | 1.69 |
June | 0.144944E+11 | 0.70 | 28087.12 | 15-JUN-15:25 | 2.28 |
July | 0.131897E+11 | 0.64 | 28087.12 | 18-JUL-16:00 | 2.28 |
August | 0.133670E+11 | 0.65 | 24625.92 | 10-AUG-15:10 | 2.10 |
September | 0.913025E+10 | 0.53 | 20807.46 | 12-SEP-16:00 | 1.89 |
October | 0.539589E+10 | 0.43 | 11903.12 | 10-OCT-16:00 | 1.35 |
November | 0.459776E+10 | 0.41 | 8493.43 | 07-NOV-16:10 | 1.11 |
December | 0.522507E+10 | 0.47 | 5977.41 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.938686E+11 | 0.51 | |||
Minimum of Months | 0.459776E+10 | 0.41 | 5977.41 | 0.91 | |
Maximum of Months | 0.144944E+11 | 0.70 | 28087.12 | 2.28 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115917E+12 | 1.65 | 43278.41 | 01-JAN-00:10 | 1.65 |
February | 0.104699E+12 | 1.65 | 43278.41 | 01-FEB-00:10 | 1.65 |
March | 0.115917E+12 | 1.65 | 43278.41 | 01-MAR-00:10 | 1.65 |
April | 0.112178E+12 | 1.65 | 43278.41 | 01-APR-00:10 | 1.65 |
May | 0.115917E+12 | 1.65 | 43278.41 | 01-MAY-00:10 | 1.65 |
June | 0.112178E+12 | 1.65 | 43278.41 | 01-JUN-00:10 | 1.65 |
July | 0.115917E+12 | 1.65 | 43278.41 | 01-JUL-00:03 | 1.65 |
August | 0.115917E+12 | 1.64 | 43278.41 | 01-AUG-00:03 | 1.65 |
September | 0.112178E+12 | 1.65 | 43278.41 | 01-SEP-00:03 | 1.65 |
October | 0.115917E+12 | 1.65 | 43278.41 | 01-OCT-00:10 | 1.65 |
November | 0.112178E+12 | 1.65 | 43278.41 | 01-NOV-00:10 | 1.65 |
December | 0.115917E+12 | 1.65 | 43278.41 | 01-DEC-00:10 | 1.65 |
Annual Sum or Average | 0.136483E+13 | 1.65 | |||
Minimum of Months | 0.104699E+12 | 1.64 | 43278.41 | 1.65 | |
Maximum of Months | 0.115917E+12 | 1.65 | 43278.41 | 1.65 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.180428E+10 | 1.13 | 673.64 | 01-JAN-00:03 | 1.13 |
February | 0.162967E+10 | 1.13 | 673.64 | 01-FEB-00:10 | 1.13 |
March | 0.180428E+10 | 1.13 | 673.64 | 01-MAR-00:10 | 1.13 |
April | 0.174608E+10 | 1.13 | 673.64 | 01-APR-00:10 | 1.13 |
May | 0.180428E+10 | 1.13 | 673.64 | 01-MAY-00:10 | 1.13 |
June | 0.174608E+10 | 1.13 | 673.64 | 01-JUN-00:10 | 1.13 |
July | 0.180428E+10 | 1.13 | 673.64 | 01-JUL-00:03 | 1.13 |
August | 0.180428E+10 | 1.13 | 673.64 | 01-AUG-00:03 | 1.13 |
September | 0.174608E+10 | 1.13 | 673.64 | 01-SEP-00:03 | 1.13 |
October | 0.180428E+10 | 1.13 | 673.64 | 01-OCT-00:10 | 1.13 |
November | 0.174608E+10 | 1.13 | 673.64 | 01-NOV-00:10 | 1.13 |
December | 0.180428E+10 | 1.13 | 673.64 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.212439E+11 | 1.13 | |||
Minimum of Months | 0.162967E+10 | 1.13 | 673.64 | 1.13 | |
Maximum of Months | 0.180428E+10 | 1.13 | 673.64 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172537E+11 | 1.13 | 6441.81 | 01-JAN-00:03 | 1.13 |
February | 0.155840E+11 | 1.13 | 6441.81 | 01-FEB-00:10 | 1.13 |
March | 0.172537E+11 | 1.13 | 6441.81 | 01-MAR-00:10 | 1.13 |
April | 0.166972E+11 | 1.13 | 6441.81 | 01-APR-00:10 | 1.13 |
May | 0.172537E+11 | 1.13 | 6441.81 | 01-MAY-00:10 | 1.13 |
June | 0.166972E+11 | 1.13 | 6441.81 | 01-JUN-00:10 | 1.13 |
July | 0.172537E+11 | 1.13 | 6441.81 | 01-JUL-00:03 | 1.13 |
August | 0.172537E+11 | 1.13 | 6441.81 | 01-AUG-00:03 | 1.13 |
September | 0.166972E+11 | 1.13 | 6441.81 | 01-SEP-00:03 | 1.13 |
October | 0.172537E+11 | 1.13 | 6441.81 | 01-OCT-00:10 | 1.13 |
November | 0.166972E+11 | 1.13 | 6441.81 | 01-NOV-00:10 | 1.13 |
December | 0.172537E+11 | 1.13 | 6441.81 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.203149E+12 | 1.13 | |||
Minimum of Months | 0.155840E+11 | 1.13 | 6441.81 | 1.13 | |
Maximum of Months | 0.172537E+11 | 1.13 | 6441.81 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176682E+10 | 1.13 | 659.66 | 01-JAN-00:03 | 1.13 |
February | 0.159584E+10 | 1.13 | 659.66 | 01-FEB-00:10 | 1.13 |
March | 0.176682E+10 | 1.13 | 659.66 | 01-MAR-00:10 | 1.13 |
April | 0.170983E+10 | 1.13 | 659.66 | 01-APR-00:10 | 1.13 |
May | 0.176682E+10 | 1.13 | 659.66 | 01-MAY-00:10 | 1.13 |
June | 0.170983E+10 | 1.13 | 659.66 | 01-JUN-00:10 | 1.13 |
July | 0.176682E+10 | 1.13 | 659.66 | 01-JUL-00:03 | 1.13 |
August | 0.176682E+10 | 1.13 | 659.66 | 01-AUG-00:03 | 1.13 |
September | 0.170983E+10 | 1.13 | 659.66 | 01-SEP-00:03 | 1.13 |
October | 0.176682E+10 | 1.13 | 659.66 | 01-OCT-00:10 | 1.13 |
November | 0.170983E+10 | 1.13 | 659.66 | 01-NOV-00:10 | 1.13 |
December | 0.176682E+10 | 1.13 | 659.66 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.208029E+11 | 1.13 | |||
Minimum of Months | 0.159584E+10 | 1.13 | 659.66 | 1.13 | |
Maximum of Months | 0.176682E+10 | 1.13 | 659.66 | 1.13 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.157337E+10 | 0.141603E+10 | 4946.29 | 05-JAN-07:10 | 4451.66 | 4451.66 | 50.02 | 9.33 |
February | 0.163106E+10 | 0.146796E+10 | 5182.20 | 06-FEB-06:01 | 4663.98 | 4663.98 | 48.24 | 10.73 |
March | 0.107255E+10 | 0.965291E+09 | 5093.07 | 20-MAR-05:01 | 4583.77 | 4583.77 | 44.59 | 10.16 |
April | 0.656798E+09 | 0.591118E+09 | 4201.27 | 17-APR-05:01 | 3781.14 | 3781.14 | 44.68 | 6.58 |
May | 58460218.61 | 52614196.75 | 4124.29 | 01-MAY-05:01 | 3711.86 | 3711.86 | 34.30 | 6.39 |
June | 8674.52 | 7807.06 | 10.07 | 09-JUN-06:10 | 9.06 | 9.06 | 22.34 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 22.33 | 0.00 |
August | 13763.68 | 12387.31 | 10.23 | 23-AUG-05:10 | 9.21 | 9.21 | 22.33 | 0.01 |
September | 34625014.00 | 31162512.60 | 2146.14 | 22-SEP-05:02 | 1931.53 | 1931.53 | 34.30 | 2.57 |
October | 0.748991E+09 | 0.674092E+09 | 4264.30 | 30-OCT-05:01 | 3837.87 | 3837.87 | 43.15 | 6.76 |
November | 0.121642E+10 | 0.109478E+10 | 4375.78 | 29-NOV-21:00 | 3938.21 | 3938.21 | 48.66 | 7.09 |
December | 0.239261E+10 | 0.215335E+10 | 5302.98 | 23-DEC-07:05 | 4772.68 | 4772.68 | 49.45 | 11.64 |
Annual Sum or Average | 0.938491E+10 | 0.844642E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 0.00 | |
Maximum of Months | 0.239261E+10 | 0.215335E+10 | 5302.98 | 4772.68 | 4772.68 | 50.02 | 11.64 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.696641E+09 | 0.626977E+09 | 10955.21 | 20-JAN-14:00 | 9859.69 | 9859.69 | 8.14 | 24.23 |
February | 0.254310E+09 | 0.228879E+09 | 8280.41 | 18-FEB-13:30 | 7452.37 | 7452.37 | 7.94 | 15.97 |
March | 0.165205E+10 | 0.148684E+10 | 13701.85 | 13-MAR-15:30 | 12331.66 | 12331.66 | 7.07 | 38.34 |
April | 0.139690E+10 | 0.125721E+10 | 10057.94 | 20-APR-13:00 | 9052.15 | 9052.15 | 7.30 | 21.13 |
May | 0.512887E+10 | 0.461598E+10 | 15506.91 | 31-MAY-14:50 | 13956.22 | 13956.22 | 6.75 | 60.72 |
June | 0.151538E+11 | 0.136384E+11 | 19499.12 | 15-JUN-15:50 | 17549.21 | 17549.21 | 6.75 | 92.01 |
July | 0.153861E+11 | 0.138475E+11 | 18608.67 | 18-JUL-16:00 | 16747.81 | 16747.81 | 6.75 | 88.18 |
August | 0.155170E+11 | 0.139653E+11 | 18368.95 | 07-AUG-12:30 | 16532.05 | 16532.05 | 6.75 | 87.02 |
September | 0.103684E+11 | 0.933160E+10 | 17113.12 | 13-SEP-14:20 | 15401.81 | 15401.81 | 6.75 | 79.40 |
October | 0.266994E+10 | 0.240295E+10 | 13941.06 | 10-OCT-13:10 | 12546.95 | 12546.95 | 7.06 | 40.25 |
November | 0.110302E+10 | 0.992716E+09 | 12777.15 | 07-NOV-15:00 | 11499.44 | 11499.44 | 7.23 | 32.40 |
December | 0.605433E+09 | 0.544890E+09 | 10749.88 | 01-DEC-14:00 | 9674.89 | 9674.89 | 8.15 | 23.48 |
Annual Sum or Average | 0.699326E+11 | 0.629393E+11 | ||||||
Minimum of Months | 0.254310E+09 | 0.228879E+09 | 8280.41 | 7452.37 | 7452.37 | 6.75 | 15.97 | |
Maximum of Months | 0.155170E+11 | 0.139653E+11 | 19499.12 | 17549.21 | 17549.21 | 8.15 | 92.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.340271E+10 | 0.306244E+10 | 13409.97 | 02-JAN-05:09 | 12068.97 | 12068.97 | 6.76 | 93.99 |
February | 0.321450E+10 | 0.289305E+10 | 13409.97 | 01-FEB-05:01 | 12068.97 | 12068.97 | 6.76 | 93.99 |
March | 0.583441E+10 | 0.525097E+10 | 13409.97 | 01-MAR-05:01 | 12068.97 | 12068.97 | 6.76 | 93.99 |
April | 0.586459E+10 | 0.527813E+10 | 13409.97 | 03-APR-03:04 | 12068.97 | 12068.97 | 6.82 | 93.99 |
May | 0.129276E+11 | 0.116349E+11 | 13409.97 | 01-MAY-03:06 | 12068.97 | 12068.97 | 6.76 | 93.99 |
June | 0.252781E+11 | 0.227503E+11 | 13409.97 | 01-JUN-03:01 | 12068.97 | 12068.97 | 7.45 | 93.99 |
July | 0.275149E+11 | 0.247634E+11 | 13409.97 | 01-JUL-00:42 | 12068.97 | 12068.97 | 6.92 | 93.99 |
August | 0.300469E+11 | 0.270422E+11 | 13409.97 | 01-AUG-00:03 | 12068.97 | 12068.97 | 6.92 | 93.99 |
September | 0.197272E+11 | 0.177545E+11 | 13409.97 | 01-SEP-00:03 | 12068.97 | 12068.97 | 6.84 | 93.99 |
October | 0.768380E+10 | 0.691542E+10 | 13409.97 | 01-OCT-07:42 | 12068.97 | 12068.97 | 6.83 | 93.99 |
November | 0.409864E+10 | 0.368878E+10 | 13409.97 | 02-NOV-04:01 | 12068.97 | 12068.97 | 6.76 | 93.99 |
December | 0.301046E+10 | 0.270941E+10 | 13409.97 | 01-DEC-05:01 | 12068.97 | 12068.97 | 6.85 | 93.99 |
Annual Sum or Average | 0.148604E+12 | 0.133743E+12 | ||||||
Minimum of Months | 0.301046E+10 | 0.270941E+10 | 13409.97 | 12068.97 | 12068.97 | 6.76 | 93.99 | |
Maximum of Months | 0.300469E+11 | 0.270422E+11 | 13409.97 | 12068.97 | 12068.97 | 7.45 | 93.99 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-JAN-00:03 | 3375.42 | 3375.42 | 22.05 | 15.66 |
February | 0.907314E+10 | 0.816583E+10 | 3750.47 | 01-FEB-00:10 | 3375.42 | 3375.42 | 24.67 | 15.66 |
March | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-MAR-00:10 | 3375.42 | 3375.42 | 27.56 | 15.66 |
April | 0.972122E+10 | 0.874910E+10 | 3750.47 | 01-APR-00:10 | 3375.42 | 3375.42 | 30.81 | 15.66 |
May | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-MAY-00:10 | 3375.42 | 3375.42 | 22.72 | 15.66 |
June | 0.972122E+10 | 0.874910E+10 | 3750.47 | 01-JUN-00:10 | 3375.42 | 3375.42 | 27.07 | 15.66 |
July | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-JUL-00:03 | 3375.42 | 3375.42 | 38.43 | 15.66 |
August | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-AUG-00:03 | 3375.42 | 3375.42 | 39.03 | 15.66 |
September | 0.972122E+10 | 0.874910E+10 | 3750.47 | 01-SEP-00:03 | 3375.42 | 3375.42 | 26.34 | 15.66 |
October | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-OCT-00:10 | 3375.42 | 3375.42 | 25.20 | 15.66 |
November | 0.972122E+10 | 0.874910E+10 | 3750.47 | 01-NOV-00:10 | 3375.42 | 3375.42 | 27.68 | 15.66 |
December | 0.100453E+11 | 0.904074E+10 | 3750.47 | 01-DEC-00:10 | 3375.42 | 3375.42 | 30.31 | 15.66 |
Annual Sum or Average | 0.118275E+12 | 0.106447E+12 | ||||||
Minimum of Months | 0.907314E+10 | 0.816583E+10 | 3750.47 | 3375.42 | 3375.42 | 22.05 | 15.66 | |
Maximum of Months | 0.100453E+11 | 0.904074E+10 | 3750.47 | 3375.42 | 3375.42 | 39.03 | 15.66 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.83 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.05 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 55.69 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.37 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 55.85 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.53 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.05 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.43 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.78 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.45 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:01 | 16.86 | 16.86 | 56.54 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 55.91 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.53 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.05 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.423723E+10 | 0.381351E+10 | 33341.45 | 20-JAN-14:40 | 30007.30 | 30007.30 | 22.73 | 110.94 |
February | 0.399208E+10 | 0.359287E+10 | 16679.94 | 18-FEB-13:30 | 15011.95 | 15011.95 | 23.51 | 55.47 |
March | 0.760063E+10 | 0.684057E+10 | 33408.12 | 14-MAR-12:20 | 30067.31 | 30067.31 | 25.44 | 110.94 |
April | 0.743746E+10 | 0.669371E+10 | 33343.99 | 19-APR-14:10 | 30009.59 | 30009.59 | 22.83 | 110.94 |
May | 0.183573E+11 | 0.165216E+11 | 33425.83 | 31-MAY-15:50 | 30083.25 | 30083.25 | 26.07 | 110.94 |
June | 0.429577E+11 | 0.386619E+11 | 33430.81 | 26-JUN-15:20 | 30087.73 | 30087.73 | 26.25 | 110.94 |
July | 0.452446E+11 | 0.407201E+11 | 33426.29 | 24-JUL-11:40 | 30083.66 | 30083.66 | 26.09 | 110.94 |
August | 0.482599E+11 | 0.434339E+11 | 33432.29 | 16-AUG-15:20 | 30089.06 | 30089.06 | 26.30 | 110.94 |
September | 0.312367E+11 | 0.281130E+11 | 33426.05 | 12-SEP-12:40 | 30083.45 | 30083.45 | 26.08 | 110.94 |
October | 0.102919E+11 | 0.926270E+10 | 33419.69 | 11-OCT-15:00 | 30077.72 | 30077.72 | 25.85 | 110.94 |
November | 0.520295E+10 | 0.468265E+10 | 33341.79 | 09-NOV-11:50 | 30007.61 | 30007.61 | 22.74 | 110.94 |
December | 0.378011E+10 | 0.340210E+10 | 33341.41 | 01-DEC-14:50 | 30007.27 | 30007.27 | 22.73 | 110.94 |
Annual Sum or Average | 0.228598E+12 | 0.205739E+12 | ||||||
Minimum of Months | 0.378011E+10 | 0.340210E+10 | 16679.94 | 15011.95 | 15011.95 | 22.73 | 55.47 | |
Maximum of Months | 0.482599E+11 | 0.434339E+11 | 33432.29 | 30089.06 | 30089.06 | 26.30 | 110.94 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 38.49 | 38.49 | 134627.32 | 1392729.75 | 05-JAN-07:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 37.19 | 37.19 | 155772.47 | 1599759.33 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 31.44 | 31.44 | 93667.78 | 1589488.59 | 20-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.78 | 25.78 | 59592.81 | 1207090.61 | 03-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.22 | 21.22 | 5298.37 | 1273844.30 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.34 | 22.34 | 0.85 | 2562.60 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.33 | 22.33 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.33 | 22.33 | 1.31 | 2604.64 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 22.28 | 22.28 | 3152.60 | 513345.41 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.02 | 23.02 | 65593.84 | 1285832.13 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 40.59 | 82.00 | 108744.02 | 1262785.08 | 29-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34.70 | 34.70 | 205000.06 | 1870765.44 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 68866.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.22 | 21.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 40.59 | 82.00 | 205000.06 | 1870765.44 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27647.85 | 1133540.00 | 20-JAN-14:40 | 9.58 | 8.12 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 13270.13 | 937199.71 | 18-FEB-13:30 | 9.08 | 7.88 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64629.63 | 1237007.59 | 14-MAR-13:00 | 9.84 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 68082.74 | 1210876.14 | 19-APR-14:10 | 9.77 | 8.11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 223734.43 | 1366296.62 | 31-MAY-15:50 | 10.17 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 634479.58 | 1926318.08 | 26-JUN-15:20 | 11.59 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 628296.27 | 1771456.19 | 17-JUL-13:30 | 11.20 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 606485.42 | 1854821.91 | 16-AUG-15:10 | 11.41 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 452899.19 | 1626638.17 | 12-SEP-16:00 | 10.83 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 107900.72 | 1303721.33 | 11-OCT-15:00 | 10.01 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45661.55 | 1174438.80 | 06-NOV-12:40 | 9.68 | 8.07 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26962.03 | 1168776.59 | 01-DEC-15:00 | 9.67 | 8.07 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 242905.76 | 0.00 | ||||||
Minimum of Months | 13270.13 | 937199.71 | 9.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 634479.58 | 1926318.08 | 11.59 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15679.90 | 794201.86 | 20-JAN-14:00 | 14.53 | 8.07 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 5984.96 | 542926.42 | 18-FEB-13:30 | 14.82 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 43686.38 | 1229626.64 | 14-MAR-13:00 | 14.45 | 7.94 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 40127.03 | 906956.20 | 20-APR-13:00 | 16.96 | 7.83 | 0.00 | 0.00 | 01-APR-00:10 |
May | 160393.89 | 1355901.65 | 31-MAY-15:50 | 12.16 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 536515.36 | 1917651.47 | 26-JUN-15:20 | 16.19 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 524740.36 | 1926622.15 | 24-JUL-05:02 | 13.35 | 6.87 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 510484.88 | 2146921.64 | 04-AUG-05:03 | 14.19 | 6.73 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 358740.06 | 1618794.78 | 12-SEP-16:00 | 16.33 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 72901.18 | 1293134.14 | 11-OCT-15:00 | 14.65 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28304.46 | 1028634.37 | 07-NOV-15:00 | 14.29 | 7.93 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 14859.62 | 803385.75 | 01-DEC-14:00 | 14.87 | 8.06 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 193707.72 | 0.00 | ||||||
Minimum of Months | 5984.96 | 542926.42 | 12.16 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 536515.36 | 2146921.64 | 16.96 | 8.07 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 210437.29 | 514377.90 | 20-JAN-14:00 | 27.73 | 23.48 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 367757.82 | 693934.85 | 18-FEB-14:00 | 30.97 | 24.05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 563806.07 | 1208130.54 | 14-MAR-13:00 | 40.15 | 30.01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 750469.93 | 1350021.72 | 19-APR-14:00 | 42.65 | 29.71 | 0.00 | 0.00 | 01-APR-00:10 |
May | 315258.52 | 988400.91 | 17-MAY-14:00 | 36.25 | 31.69 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 858956.34 | 1883623.96 | 26-JUN-15:10 | 51.97 | 44.07 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1146692.81 | 1992617.76 | 16-JUL-13:00 | 53.85 | 43.35 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1355356.98 | 2263589.39 | 16-AUG-16:00 | 58.51 | 45.14 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 470956.98 | 1189620.51 | 10-SEP-13:40 | 39.82 | 35.35 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 421264.83 | 1137072.12 | 11-OCT-14:00 | 38.89 | 31.42 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 551268.36 | 1105929.73 | 07-NOV-15:00 | 38.34 | 28.07 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 702865.07 | 1321952.56 | 02-DEC-15:00 | 42.16 | 29.52 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 645021.63 | 0.00 | ||||||
Minimum of Months | 210437.29 | 514377.90 | 27.73 | 23.48 | 0.00 | 0.00 | ||
Maximum of Months | 1355356.98 | 2263589.39 | 58.51 | 45.14 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.44 | 57.44 | 16398.34 | 55393.86 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.30 | 56.30 | 16672.14 | 55523.10 | 17-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.24 | 56.24 | 17385.98 | 55311.08 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.88 | 56.88 | 15795.25 | 53606.49 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.45 | 56.45 | 15456.57 | 51232.13 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.13 | 56.13 | 14942.10 | 48217.45 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.56 | 57.56 | 13298.21 | 45599.81 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.98 | 56.98 | 14213.86 | 44350.24 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.33 | 56.33 | 13651.50 | 45785.80 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.38 | 57.38 | 14230.70 | 48476.62 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.73 | 56.73 | 15219.07 | 51378.62 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.43 | 56.43 | 15473.33 | 53824.94 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15219.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.13 | 56.13 | 13298.21 | 44350.24 | ||
Maximum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 17385.98 | 55523.10 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16738.99 | 813767.06 | 20-JAN-14:00 | 24.61 | 21.10 | 1481.23 | 118879.50 | 13-JAN-16:00 |
February | 6754.10 | 558184.90 | 18-FEB-13:30 | 23.51 | 21.10 | 1601.30 | 119116.52 | 14-FEB-07:00 |
March | 47639.30 | 2011671.52 | 14-MAR-12:20 | 25.44 | 21.10 | 1487.75 | 121461.50 | 19-MAR-06:50 |
April | 42885.62 | 889786.99 | 20-APR-13:10 | 24.94 | 21.10 | 1362.76 | 119880.80 | 24-APR-05:50 |
May | 195972.48 | 2304984.34 | 31-MAY-15:50 | 26.07 | 21.10 | 871.46 | 102671.09 | 02-MAY-10:10 |
June | 671746.17 | 2387385.83 | 26-JUN-15:20 | 26.25 | 21.47 | 473.88 | 70208.99 | 09-JUN-04:02 |
July | 656673.80 | 2312569.60 | 24-JUL-11:40 | 26.09 | 21.42 | 330.16 | 47698.86 | 01-JUL-03:55 |
August | 637862.05 | 2411858.29 | 16-AUG-15:20 | 26.30 | 21.70 | 715.80 | 63222.35 | 19-AUG-01:00 |
September | 455749.86 | 2308620.85 | 12-SEP-12:40 | 26.08 | 21.10 | 758.11 | 105728.85 | 21-SEP-15:50 |
October | 84855.39 | 2203336.50 | 11-OCT-15:00 | 25.85 | 21.10 | 1246.81 | 102001.74 | 25-OCT-05:30 |
November | 29530.58 | 988818.63 | 07-NOV-15:00 | 25.37 | 21.10 | 1306.16 | 113462.64 | 27-NOV-07:00 |
December | 15844.90 | 824674.69 | 01-DEC-14:20 | 24.66 | 21.10 | 891.81 | 120067.05 | 07-DEC-15:00 |
Annual Sum or Average | 239752.54 | 1040.11 | ||||||
Minimum of Months | 6754.10 | 558184.90 | 23.51 | 21.10 | 330.16 | 47698.86 | ||
Maximum of Months | 671746.17 | 2411858.29 | 26.30 | 21.70 | 1601.30 | 121461.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.158175E+11 | 0.00 | 0.340075E+10 | 0.685727E+10 | 0.00 | 0.00 |
February | 0.153144E+11 | 0.00 | 0.115709E+10 | 0.658822E+10 | 0.00 | 0.00 |
March | 0.784573E+10 | 0.00 | 0.100715E+11 | 0.976979E+10 | 0.00 | 0.00 |
April | 0.351575E+10 | 0.00 | 0.109989E+11 | 0.107384E+11 | 0.00 | 0.00 |
May | 0.212750E+09 | 0.00 | 0.351665E+11 | 0.109446E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.116399E+12 | 0.168729E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.123683E+12 | 0.171026E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.131317E+12 | 0.210295E+11 | 0.00 | 0.00 |
September | 0.302758E+09 | 0.00 | 0.762415E+11 | 0.124575E+11 | 0.00 | 0.00 |
October | 0.586574E+10 | 0.00 | 0.159666E+11 | 0.921254E+10 | 0.00 | 0.00 |
November | 0.889776E+10 | 0.00 | 0.645336E+10 | 0.858077E+10 | 0.00 | 0.00 |
December | 0.219597E+11 | 0.00 | 0.387303E+10 | 0.813067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.797321E+11 | 0.00 | 0.534728E+12 | 0.138285E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.115709E+10 | 0.658822E+10 | 0.00 | 0.00 |
Maximum of Months | 0.219597E+11 | 0.00 | 0.131317E+12 | 0.210295E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.295362E+12 | 0.00 | 0.295701E+11 | 0.501432E+11 | 0.00 | 0.00 |
February | 0.311953E+12 | 0.00 | 0.110700E+11 | 0.464443E+11 | 0.00 | 0.00 |
March | 0.208447E+12 | 0.00 | 0.804468E+11 | 0.629973E+11 | 0.00 | 0.00 |
April | 0.126632E+12 | 0.00 | 0.702111E+11 | 0.559677E+11 | 0.00 | 0.00 |
May | 0.109297E+11 | 0.00 | 0.304209E+12 | 0.848468E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.101167E+13 | 0.136206E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.101611E+13 | 0.127872E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.975237E+12 | 0.130680E+12 | 0.00 | 0.00 |
September | 0.638372E+10 | 0.00 | 0.670335E+12 | 0.987630E+11 | 0.00 | 0.00 |
October | 0.143592E+12 | 0.00 | 0.136999E+12 | 0.627162E+11 | 0.00 | 0.00 |
November | 0.234601E+12 | 0.00 | 0.500145E+11 | 0.523138E+11 | 0.00 | 0.00 |
December | 0.457171E+12 | 0.00 | 0.275609E+11 | 0.487918E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.179507E+13 | 0.00 | 0.438344E+13 | 0.957742E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.110700E+11 | 0.464443E+11 | 0.00 | 0.00 |
Maximum of Months | 0.457171E+12 | 0.00 | 0.101611E+13 | 0.136206E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.526566E+11 | 0.00 | 0.218077E+10 | 0.513860E+10 | 0.00 | 0.00 |
February | 0.530015E+11 | 0.00 | 0.809522E+09 | 0.465643E+10 | 0.00 | 0.00 |
March | 0.368683E+11 | 0.00 | 0.730211E+10 | 0.587677E+10 | 0.00 | 0.00 |
April | 0.257255E+11 | 0.00 | 0.708119E+10 | 0.552008E+10 | 0.00 | 0.00 |
May | 0.316840E+10 | 0.00 | 0.313792E+11 | 0.727661E+10 | 0.00 | 0.00 |
June | 2280128.66 | 0.00 | 0.115442E+12 | 0.144944E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.113984E+12 | 0.131897E+11 | 0.00 | 0.00 |
August | 3819885.45 | 0.00 | 0.109467E+12 | 0.133670E+11 | 0.00 | 0.00 |
September | 0.155379E+10 | 0.00 | 0.704405E+11 | 0.913025E+10 | 0.00 | 0.00 |
October | 0.276979E+11 | 0.00 | 0.122832E+11 | 0.539589E+10 | 0.00 | 0.00 |
November | 0.409336E+11 | 0.00 | 0.401911E+10 | 0.459776E+10 | 0.00 | 0.00 |
December | 0.748450E+11 | 0.00 | 0.209233E+10 | 0.522507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316457E+12 | 0.00 | 0.476481E+12 | 0.938686E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.809522E+09 | 0.459776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.748450E+11 | 0.00 | 0.115442E+12 | 0.144944E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.121314E+10 | 0.193701E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100168E+09 | 0.173281E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.398921E+10 | 0.203173E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.468337E+10 | 0.189360E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.202976E+11 | 0.200941E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.632655E+11 | 0.201818E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.640943E+11 | 0.199690E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.681699E+11 | 0.222029E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.466709E+11 | 0.208407E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.804675E+10 | 0.207827E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.299240E+10 | 0.193812E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.164272E+10 | 0.191992E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.285166E+12 | 0.238603E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.100168E+09 | 0.173281E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.681699E+11 | 0.222029E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.498231E+12 | 0.274164E+12 | 0.00 | 21.26 |
February | 0.00 | 0.00 | 0.761328E+12 | 0.340006E+12 | 0.00 | 32.45 |
March | 0.00 | 0.00 | 0.118996E+13 | 0.475212E+12 | 0.00 | 49.09 |
April | 0.00 | 0.00 | 0.148845E+13 | 0.563336E+12 | 0.00 | 65.58 |
May | 0.00 | 0.00 | 0.513660E+12 | 0.278887E+12 | 0.00 | 20.23 |
June | 0.00 | 0.00 | 0.852371E+12 | 0.381500E+12 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 0.123421E+13 | 0.501326E+12 | 0.00 | 31.60 |
August | 0.00 | 0.00 | 0.159224E+13 | 0.639703E+12 | 0.00 | 60.46 |
September | 0.00 | 0.00 | 0.510007E+12 | 0.276618E+12 | 0.00 | 18.20 |
October | 0.00 | 0.00 | 0.857801E+12 | 0.381385E+12 | 0.00 | 35.52 |
November | 0.00 | 0.00 | 0.115666E+13 | 0.460942E+12 | 0.00 | 48.16 |
December | 0.00 | 0.00 | 0.153659E+13 | 0.582660E+12 | 0.00 | 69.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.121915E+14 | 0.515574E+13 | 0.00 | 476.65 |
Minimum of Months | 0.00 | 0.00 | 0.498231E+12 | 0.274164E+12 | 0.00 | 18.20 |
Maximum of Months | 0.00 | 0.00 | 0.159224E+13 | 0.639703E+12 | 0.00 | 69.88 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.592532E+10 | 0.308723E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111699E+11 | 0.394195E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193776E+11 | 0.573488E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.251985E+11 | 0.671476E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.767083E+10 | 0.348823E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149727E+11 | 0.543234E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.222233E+11 | 0.734773E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.291992E+11 | 0.897316E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.797416E+10 | 0.362515E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.134221E+11 | 0.460582E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186576E+11 | 0.545705E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252645E+11 | 0.681387E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201056E+12 | 0.652222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.592532E+10 | 0.308723E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.291992E+11 | 0.897316E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.372692E+11 | 0.255309E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.873639E+11 | 0.339124E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167536E+12 | 0.516009E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222478E+12 | 0.610053E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.658941E+11 | 0.318472E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140790E+12 | 0.514403E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210694E+12 | 0.698702E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272637E+12 | 0.844530E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.705200E+11 | 0.334494E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114319E+12 | 0.413524E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.160168E+12 | 0.488910E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.211722E+12 | 0.598399E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176139E+13 | 0.593193E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.372692E+11 | 0.255309E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272637E+12 | 0.844530E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.165335E+10 | 0.214189E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.657133E+10 | 0.299495E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149885E+11 | 0.487703E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204693E+11 | 0.583587E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.589923E+10 | 0.308878E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141298E+11 | 0.521052E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211363E+11 | 0.706301E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.273021E+11 | 0.852152E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.668340E+10 | 0.331547E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.966161E+10 | 0.383334E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.137750E+11 | 0.452014E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.186314E+11 | 0.556811E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160901E+12 | 0.569706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.165335E+10 | 0.214189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.273021E+11 | 0.852152E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.685727E+10 | 0.340075E+10 | 0.158175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658822E+10 | 0.115709E+10 | 0.153144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976979E+10 | 0.100715E+11 | 0.784573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107384E+11 | 0.109989E+11 | 0.351575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109446E+11 | 0.351665E+11 | 0.212750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168729E+11 | 0.116399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171026E+11 | 0.123683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210295E+11 | 0.131317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124575E+11 | 0.762415E+11 | 0.302758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921254E+10 | 0.159666E+11 | 0.586574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858077E+10 | 0.645336E+10 | 0.889776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813067E+10 | 0.387303E+10 | 0.219597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138285E+12 | 0.534728E+12 | 0.797321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.658822E+10 | 0.115709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210295E+11 | 0.131317E+12 | 0.219597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.501432E+11 | 0.295701E+11 | 0.295362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464443E+11 | 0.110700E+11 | 0.311953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629973E+11 | 0.804468E+11 | 0.208447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.559677E+11 | 0.702111E+11 | 0.126632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.848468E+11 | 0.304209E+12 | 0.109297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136206E+12 | 0.101167E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127872E+12 | 0.101611E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130680E+12 | 0.975237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.987630E+11 | 0.670335E+12 | 0.638372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.627162E+11 | 0.136999E+12 | 0.143592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523138E+11 | 0.500145E+11 | 0.234601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487918E+11 | 0.275609E+11 | 0.457171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.957742E+12 | 0.438344E+13 | 0.179507E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.464443E+11 | 0.110700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136206E+12 | 0.101611E+13 | 0.457171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.513860E+10 | 0.218077E+10 | 0.526566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465643E+10 | 0.809522E+09 | 0.530015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587677E+10 | 0.730211E+10 | 0.368683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552008E+10 | 0.708119E+10 | 0.257255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.727661E+10 | 0.313792E+11 | 0.316840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144944E+11 | 0.115442E+12 | 2280128.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131897E+11 | 0.113984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133670E+11 | 0.109467E+12 | 3819885.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913025E+10 | 0.704405E+11 | 0.155379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539589E+10 | 0.122832E+11 | 0.276979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459776E+10 | 0.401911E+10 | 0.409336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522507E+10 | 0.209233E+10 | 0.748450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938686E+11 | 0.476481E+12 | 0.316457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.459776E+10 | 0.809522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144944E+11 | 0.115442E+12 | 0.748450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193701E+11 | 0.121314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173281E+11 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203173E+11 | 0.398921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189360E+11 | 0.468337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200941E+11 | 0.202976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201818E+11 | 0.632655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199690E+11 | 0.640943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222029E+11 | 0.681699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208407E+11 | 0.466709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207827E+11 | 0.804675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193812E+11 | 0.299240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191992E+11 | 0.164272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238603E+12 | 0.285166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173281E+11 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.222029E+11 | 0.681699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115917E+12 | 0.397129E+12 | 0.00 | 0.00 | 0.00 | 0.568892E+11 | 0.00 | 0.00 |
February | 0.104699E+12 | 0.613257E+12 | 0.00 | 0.00 | 0.00 | 0.868445E+11 | 0.00 | 0.00 |
March | 0.115917E+12 | 0.962611E+12 | 0.00 | 0.00 | 0.00 | 0.131360E+12 | 0.00 | 0.00 |
April | 0.112178E+12 | 0.121359E+13 | 0.00 | 0.00 | 0.00 | 0.175511E+12 | 0.00 | 0.00 |
May | 0.115917E+12 | 0.405068E+12 | 0.00 | 0.00 | 0.00 | 0.541345E+11 | 0.00 | 0.00 |
June | 0.112178E+12 | 0.648129E+12 | 0.00 | 0.00 | 0.00 | 0.647895E+11 | 0.00 | 0.00 |
July | 0.115917E+12 | 0.933758E+12 | 0.00 | 0.00 | 0.00 | 0.845733E+11 | 0.00 | 0.00 |
August | 0.115917E+12 | 0.123100E+13 | 0.00 | 0.00 | 0.00 | 0.161811E+12 | 0.00 | 0.00 |
September | 0.112178E+12 | 0.394486E+12 | 0.00 | 0.00 | 0.00 | 0.486996E+11 | 0.00 | 0.00 |
October | 0.115917E+12 | 0.687823E+12 | 0.00 | 0.00 | 0.00 | 0.950618E+11 | 0.00 | 0.00 |
November | 0.112178E+12 | 0.937370E+12 | 0.00 | 0.00 | 0.00 | 0.128891E+12 | 0.00 | 0.00 |
December | 0.115917E+12 | 0.125770E+13 | 0.00 | 0.00 | 0.00 | 0.187009E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.136483E+13 | 0.968192E+13 | 0.00 | 0.00 | 0.00 | 0.127558E+13 | 0.00 | 0.00 |
Minimum of Months | 0.104699E+12 | 0.394486E+12 | 0.00 | 0.00 | 0.00 | 0.486996E+11 | 0.00 | 0.00 |
Maximum of Months | 0.115917E+12 | 0.125770E+13 | 0.00 | 0.00 | 0.00 | 0.187009E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.180428E+10 | 0.464237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162967E+10 | 0.885759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180428E+10 | 0.154470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174608E+10 | 0.202298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180428E+10 | 0.598688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174608E+10 | 0.112865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180428E+10 | 0.166798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180428E+10 | 0.220303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174608E+10 | 0.609509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180428E+10 | 0.106206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174608E+10 | 0.149467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180428E+10 | 0.202549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212439E+11 | 0.157078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162967E+10 | 0.464237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180428E+10 | 0.220303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172537E+11 | 0.289921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155840E+11 | 0.690355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172537E+11 | 0.133189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166972E+11 | 0.178170E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172537E+11 | 0.513007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166972E+11 | 0.106047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172537E+11 | 0.158078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172537E+11 | 0.205438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166972E+11 | 0.537677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172537E+11 | 0.902208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166972E+11 | 0.127974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172537E+11 | 0.169136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203149E+12 | 0.137135E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155840E+11 | 0.289921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172537E+11 | 0.205438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176682E+10 | 0.127828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159584E+10 | 0.517222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176682E+10 | 0.118783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170983E+10 | 0.163433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176682E+10 | 0.457727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170983E+10 | 0.106291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176682E+10 | 0.158401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176682E+10 | 0.205474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170983E+10 | 0.507776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176682E+10 | 0.759508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170983E+10 | 0.109646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176682E+10 | 0.148301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208029E+11 | 0.124734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159584E+10 | 0.127828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176682E+10 | 0.205474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.685727E+10 | 0.158175E+11 | 0.340075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658822E+10 | 0.153144E+11 | 0.115709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.976979E+10 | 0.784573E+10 | 0.100715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107384E+11 | 0.351575E+10 | 0.109989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109446E+11 | 0.212750E+09 | 0.351665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168729E+11 | 0.00 | 0.116399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171026E+11 | 0.00 | 0.123683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.210295E+11 | 0.00 | 0.131317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124575E+11 | 0.302758E+09 | 0.762415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.921254E+10 | 0.586574E+10 | 0.159666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858077E+10 | 0.889776E+10 | 0.645336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813067E+10 | 0.219597E+11 | 0.387303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138285E+12 | 0.797321E+11 | 0.534728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.658822E+10 | 0.00 | 0.115709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.210295E+11 | 0.219597E+11 | 0.131317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.501432E+11 | 0.295362E+12 | 0.295701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464443E+11 | 0.311953E+12 | 0.110700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629973E+11 | 0.208447E+12 | 0.804468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.559677E+11 | 0.126632E+12 | 0.702111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.848468E+11 | 0.109297E+11 | 0.304209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136206E+12 | 0.00 | 0.101167E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127872E+12 | 0.00 | 0.101611E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130680E+12 | 0.00 | 0.975237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.987630E+11 | 0.638372E+10 | 0.670335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.627162E+11 | 0.143592E+12 | 0.136999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523138E+11 | 0.234601E+12 | 0.500145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487918E+11 | 0.457171E+12 | 0.275609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.957742E+12 | 0.179507E+13 | 0.438344E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.464443E+11 | 0.00 | 0.110700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136206E+12 | 0.457171E+12 | 0.101611E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.513860E+10 | 0.526566E+11 | 0.218077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465643E+10 | 0.530015E+11 | 0.809522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587677E+10 | 0.368683E+11 | 0.730211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552008E+10 | 0.257255E+11 | 0.708119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.727661E+10 | 0.316840E+10 | 0.313792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144944E+11 | 2280128.66 | 0.115442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131897E+11 | 0.00 | 0.113984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133670E+11 | 3819885.45 | 0.109467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913025E+10 | 0.155379E+10 | 0.704405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539589E+10 | 0.276979E+11 | 0.122832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459776E+10 | 0.409336E+11 | 0.401911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522507E+10 | 0.748450E+11 | 0.209233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938686E+11 | 0.316457E+12 | 0.476481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.459776E+10 | 0.00 | 0.809522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144944E+11 | 0.748450E+11 | 0.115442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193701E+11 | 0.00 | 0.121314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173281E+11 | 0.00 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203173E+11 | 0.00 | 0.398921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189360E+11 | 0.00 | 0.468337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200941E+11 | 0.00 | 0.202976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.201818E+11 | 0.00 | 0.632655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199690E+11 | 0.00 | 0.640943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222029E+11 | 0.00 | 0.681699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208407E+11 | 0.00 | 0.466709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207827E+11 | 0.00 | 0.804675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193812E+11 | 0.00 | 0.299240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191992E+11 | 0.00 | 0.164272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238603E+12 | 0.00 | 0.285166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173281E+11 | 0.00 | 0.100168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.222029E+11 | 0.00 | 0.681699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115917E+12 | 0.00 | 0.498231E+12 | 0.00 | 0.101102E+12 | 0.00 | 0.00 | 0.00 | 0.571453E+11 | 0.00 | 0.00 | 0.00 |
February | 0.104699E+12 | 0.00 | 0.761328E+12 | 0.00 | 0.148071E+12 | 0.00 | 0.00 | 0.00 | 0.872354E+11 | 0.00 | 0.00 | 0.00 |
March | 0.115917E+12 | 0.00 | 0.118996E+13 | 0.00 | 0.227344E+12 | 0.00 | 0.00 | 0.00 | 0.131952E+12 | 0.00 | 0.00 | 0.00 |
April | 0.112178E+12 | 0.00 | 0.148845E+13 | 0.00 | 0.274858E+12 | 0.00 | 0.00 | 0.00 | 0.176301E+12 | 0.00 | 0.00 | 0.00 |
May | 0.115917E+12 | 0.00 | 0.513660E+12 | 0.00 | 0.108592E+12 | 0.00 | 0.00 | 0.00 | 0.543781E+11 | 0.00 | 0.00 | 0.00 |
June | 0.112178E+12 | 0.00 | 0.852371E+12 | 0.00 | 0.204241E+12 | 0.00 | 0.00 | 0.00 | 0.650812E+11 | 0.00 | 0.00 | 0.00 |
July | 0.115917E+12 | 0.00 | 0.123421E+13 | 0.00 | 0.300455E+12 | 0.00 | 0.00 | 0.00 | 0.849540E+11 | 0.00 | 0.00 | 0.00 |
August | 0.115917E+12 | 0.00 | 0.159224E+13 | 0.00 | 0.361246E+12 | 0.00 | 0.00 | 0.00 | 0.162540E+12 | 0.00 | 0.00 | 0.00 |
September | 0.112178E+12 | 0.00 | 0.510007E+12 | 0.00 | 0.115521E+12 | 0.00 | 0.00 | 0.00 | 0.489188E+11 | 0.00 | 0.00 | 0.00 |
October | 0.115917E+12 | 0.00 | 0.857801E+12 | 0.00 | 0.169978E+12 | 0.00 | 0.00 | 0.00 | 0.954897E+11 | 0.00 | 0.00 | 0.00 |
November | 0.112178E+12 | 0.00 | 0.115666E+13 | 0.00 | 0.219292E+12 | 0.00 | 0.00 | 0.00 | 0.129472E+12 | 0.00 | 0.00 | 0.00 |
December | 0.115917E+12 | 0.00 | 0.153659E+13 | 0.00 | 0.278891E+12 | 0.00 | 0.00 | 0.00 | 0.187851E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136483E+13 | 0.00 | 0.121915E+14 | 0.00 | 0.250959E+13 | 0.00 | 0.00 | 0.00 | 0.128132E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104699E+12 | 0.00 | 0.498231E+12 | 0.00 | 0.101102E+12 | 0.00 | 0.00 | 0.00 | 0.489188E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115917E+12 | 0.00 | 0.159224E+13 | 0.00 | 0.361246E+12 | 0.00 | 0.00 | 0.00 | 0.187851E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.180428E+10 | 0.00 | 0.592532E+10 | 0.00 | 0.128295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162967E+10 | 0.00 | 0.111699E+11 | 0.00 | 0.231227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180428E+10 | 0.00 | 0.193776E+11 | 0.00 | 0.393060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174608E+10 | 0.00 | 0.251985E+11 | 0.00 | 0.496868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180428E+10 | 0.00 | 0.767083E+10 | 0.00 | 0.168395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174608E+10 | 0.00 | 0.149727E+11 | 0.00 | 0.368626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180428E+10 | 0.00 | 0.222233E+11 | 0.00 | 0.554345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180428E+10 | 0.00 | 0.291992E+11 | 0.00 | 0.716889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174608E+10 | 0.00 | 0.797416E+10 | 0.00 | 0.187907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180428E+10 | 0.00 | 0.134221E+11 | 0.00 | 0.280154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174608E+10 | 0.00 | 0.186576E+11 | 0.00 | 0.371098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180428E+10 | 0.00 | 0.252645E+11 | 0.00 | 0.500959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212439E+11 | 0.00 | 0.201056E+12 | 0.00 | 0.439782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162967E+10 | 0.00 | 0.592532E+10 | 0.00 | 0.128295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180428E+10 | 0.00 | 0.291992E+11 | 0.00 | 0.716889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.172537E+11 | 0.00 | 0.372692E+11 | 0.00 | 0.827718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155840E+11 | 0.00 | 0.873639E+11 | 0.00 | 0.183284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172537E+11 | 0.00 | 0.167536E+12 | 0.00 | 0.343472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166972E+11 | 0.00 | 0.222478E+12 | 0.00 | 0.443082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172537E+11 | 0.00 | 0.658941E+11 | 0.00 | 0.145935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166972E+11 | 0.00 | 0.140790E+12 | 0.00 | 0.347431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.172537E+11 | 0.00 | 0.210694E+12 | 0.00 | 0.526164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172537E+11 | 0.00 | 0.272637E+12 | 0.00 | 0.671992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166972E+11 | 0.00 | 0.705200E+11 | 0.00 | 0.167522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172537E+11 | 0.00 | 0.114319E+12 | 0.00 | 0.240986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166972E+11 | 0.00 | 0.160168E+12 | 0.00 | 0.321938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172537E+11 | 0.00 | 0.211722E+12 | 0.00 | 0.425861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203149E+12 | 0.00 | 0.176139E+13 | 0.00 | 0.390044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155840E+11 | 0.00 | 0.372692E+11 | 0.00 | 0.827718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172537E+11 | 0.00 | 0.272637E+12 | 0.00 | 0.671992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176682E+10 | 0.00 | 0.165335E+10 | 0.00 | 0.375068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159584E+10 | 0.00 | 0.657133E+10 | 0.00 | 0.139911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176682E+10 | 0.00 | 0.149885E+11 | 0.00 | 0.311021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170983E+10 | 0.00 | 0.204693E+11 | 0.00 | 0.412604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176682E+10 | 0.00 | 0.589923E+10 | 0.00 | 0.132196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170983E+10 | 0.00 | 0.141298E+11 | 0.00 | 0.350069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176682E+10 | 0.00 | 0.211363E+11 | 0.00 | 0.529619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176682E+10 | 0.00 | 0.273021E+11 | 0.00 | 0.675470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170983E+10 | 0.00 | 0.668340E+10 | 0.00 | 0.160564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176682E+10 | 0.00 | 0.966161E+10 | 0.00 | 0.206652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170983E+10 | 0.00 | 0.137750E+11 | 0.00 | 0.281032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176682E+10 | 0.00 | 0.186314E+11 | 0.00 | 0.380129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208029E+11 | 0.00 | 0.160901E+12 | 0.00 | 0.361677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159584E+10 | 0.00 | 0.165335E+10 | 0.00 | 0.375068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176682E+10 | 0.00 | 0.273021E+11 | 0.00 | 0.675470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510970E+09 | 0.00 | 0.00 | 0.118186E+09 | 0.00 | 0.00 | 0.743388E+11 | 0.00 | 0.79 |
February | 0.449102E+09 | 0.00 | 0.00 | 0.108200E+09 | 0.00 | 0.00 | 0.670722E+11 | 0.00 | 0.70 |
March | 0.397301E+09 | 0.00 | 0.00 | 0.124572E+09 | 0.00 | 0.00 | 0.778445E+11 | 0.00 | 1.06 |
April | 0.453913E+09 | 0.00 | 0.00 | 0.116800E+09 | 0.00 | 0.00 | 0.730728E+11 | 0.00 | 1.14 |
May | 0.132546E+09 | 13765139.57 | 0.00 | 0.116333E+09 | 304336.62 | 0.00 | 0.625951E+11 | 0.00 | 1.44 |
June | 77349753.56 | 0.165870E+10 | 0.00 | 89484606.48 | 21237466.23 | 0.00 | 0.255490E+11 | 0.00 | 1.16 |
July | 76924893.96 | 0.161719E+10 | 0.00 | 97273998.69 | 61370481.40 | 0.00 | 0.231639E+11 | 0.00 | 1.11 |
August | 0.161163E+09 | 0.165857E+10 | 0.00 | 0.126775E+09 | 24075102.88 | 0.00 | 0.323838E+11 | 0.00 | 1.30 |
September | 0.210281E+09 | 0.326518E+09 | 0.00 | 0.126682E+09 | 21937588.74 | 0.00 | 0.418497E+11 | 0.00 | 1.43 |
October | 0.338074E+09 | 0.00 | 0.00 | 0.140183E+09 | 0.00 | 0.00 | 0.792402E+11 | 0.00 | 1.18 |
November | 0.431477E+09 | 0.00 | 0.00 | 0.139231E+09 | 0.00 | 0.00 | 0.797744E+11 | 0.00 | 0.95 |
December | 0.831682E+09 | 0.00 | 0.00 | 0.129042E+09 | 0.00 | 0.00 | 0.783450E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.407078E+10 | 0.527474E+10 | 0.00 | 0.143276E+10 | 0.128925E+09 | 0.00 | 0.715229E+12 | 0.00 | 1.09 |
Minimum of Months | 76924893.96 | 0.00 | 0.00 | 89484606.48 | 0.00 | 0.00 | 0.231639E+11 | 0.00 | 0.70 |
Maximum of Months | 0.831682E+09 | 0.165870E+10 | 0.00 | 0.140183E+09 | 61370481.40 | 0.00 | 0.797744E+11 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.393382E+10 | 0.00 | 0.00 | 78448789.32 | 0.00 | 0.00 | 0.519959E+11 | 0.00 | 0.55 |
February | 0.401117E+10 | 0.00 | 0.00 | 75376348.38 | 0.00 | 0.00 | 0.487655E+11 | 0.00 | 0.53 |
March | 0.336615E+10 | 0.00 | 0.00 | 0.101343E+09 | 0.00 | 0.00 | 0.595790E+11 | 0.00 | 0.80 |
April | 0.313895E+10 | 0.00 | 0.00 | 98133907.08 | 0.00 | 0.00 | 0.572249E+11 | 0.00 | 0.90 |
May | 0.314613E+10 | 15163767.44 | 0.00 | 93264243.95 | 817451.51 | 0.00 | 0.449868E+11 | 0.00 | 1.03 |
June | 0.508329E+10 | 0.175882E+10 | 0.00 | 68744978.72 | 83262014.97 | 0.00 | 0.166736E+11 | 0.00 | 0.96 |
July | 0.589710E+10 | 0.172373E+10 | 0.00 | 67648098.87 | 0.239328E+09 | 0.00 | 0.137743E+11 | 0.00 | 0.97 |
August | 0.101085E+11 | 0.164047E+10 | 0.00 | 92669779.99 | 0.274306E+09 | 0.00 | 0.233542E+11 | 0.00 | 1.23 |
September | 0.312803E+10 | 0.316296E+09 | 0.00 | 86953855.50 | 70569316.42 | 0.00 | 0.266887E+11 | 0.00 | 0.96 |
October | 0.414682E+10 | 0.00 | 0.00 | 95704794.00 | 0.00 | 0.00 | 0.535335E+11 | 0.00 | 0.81 |
November | 0.378945E+10 | 0.00 | 0.00 | 97218386.76 | 0.00 | 0.00 | 0.569027E+11 | 0.00 | 0.69 |
December | 0.424235E+10 | 0.00 | 0.00 | 95575369.23 | 0.00 | 0.00 | 0.619780E+11 | 0.00 | 0.61 |
Annual Sum or Average | 0.539918E+11 | 0.545448E+10 | 0.00 | 0.105108E+10 | 0.668283E+09 | 0.00 | 0.515457E+12 | 0.00 | 0.84 |
Minimum of Months | 0.312803E+10 | 0.00 | 0.00 | 67648098.87 | 0.00 | 0.00 | 0.137743E+11 | 0.00 | 0.53 |
Maximum of Months | 0.101085E+11 | 0.175882E+10 | 0.00 | 0.101343E+09 | 0.274306E+09 | 0.00 | 0.619780E+11 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166537E+12 | 0.00 | 0.00 | 0.350215E+09 | 0.00 | 0.00 | 0.284862E+12 | 0.00 | 0.44 |
February | 0.203178E+12 | 0.00 | 0.00 | 0.260817E+09 | 0.00 | 70405418.51 | 0.213148E+12 | 0.00 | 0.42 |
March | 0.151061E+12 | 0.00 | 0.00 | 0.464355E+09 | 0.00 | 11266674.27 | 0.308790E+12 | 0.00 | 0.59 |
April | 0.903807E+11 | 0.00 | 0.00 | 0.428711E+09 | 0.00 | 0.00 | 0.296591E+12 | 0.00 | 0.59 |
May | 0.248110E+11 | 0.234548E+09 | 0.00 | 0.704483E+09 | 30296141.56 | 0.00 | 0.347673E+12 | 0.00 | 0.83 |
June | 0.243890E+11 | 0.189770E+11 | 0.00 | 0.566912E+09 | 0.885243E+09 | 0.00 | 0.134315E+12 | 0.00 | 0.77 |
July | 0.202658E+11 | 0.175730E+11 | 0.00 | 0.558558E+09 | 0.182838E+10 | 0.00 | 0.108023E+12 | 0.00 | 0.72 |
August | 0.233004E+11 | 0.166720E+11 | 0.00 | 0.692702E+09 | 0.985513E+09 | 0.00 | 0.169072E+12 | 0.00 | 0.79 |
September | 0.200622E+11 | 0.351243E+10 | 0.00 | 0.678485E+09 | 0.477536E+09 | 0.00 | 0.211157E+12 | 0.00 | 0.78 |
October | 0.824378E+11 | 0.00 | 0.00 | 0.556150E+09 | 0.00 | 0.00 | 0.346478E+12 | 0.00 | 0.61 |
November | 0.131531E+12 | 0.00 | 0.00 | 0.415155E+09 | 0.00 | 0.00 | 0.303513E+12 | 0.00 | 0.50 |
December | 0.254393E+12 | 0.00 | 0.00 | 0.235955E+09 | 0.00 | 0.104671E+10 | 0.212962E+12 | 0.00 | 0.42 |
Annual Sum or Average | 0.119235E+13 | 0.569691E+11 | 0.00 | 0.591250E+10 | 0.420697E+10 | 0.112839E+10 | 0.293659E+13 | 0.00 | 0.62 |
Minimum of Months | 0.200622E+11 | 0.00 | 0.00 | 0.235955E+09 | 0.00 | 0.00 | 0.108023E+12 | 0.00 | 0.42 |
Maximum of Months | 0.254393E+12 | 0.189770E+11 | 0.00 | 0.704483E+09 | 0.182838E+10 | 0.104671E+10 | 0.347673E+12 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280404E+11 | 0.00 | 0.00 | 6583317.60 | 0.00 | 0.231902E+10 | 0.618090E+10 | 0.00 | 0.38 |
February | 0.253137E+11 | 0.00 | 0.00 | 5718952.34 | 0.00 | 0.267559E+10 | 0.630410E+10 | 0.00 | 0.37 |
March | 0.220425E+11 | 0.00 | 0.00 | 22326541.54 | 0.00 | 0.603620E+09 | 0.162833E+11 | 0.00 | 0.53 |
April | 0.158243E+11 | 0.00 | 0.00 | 24486932.14 | 0.00 | 0.865551E+09 | 0.178107E+11 | 0.00 | 0.55 |
May | 0.634750E+10 | 1015985.96 | 0.00 | 51231878.08 | 3740837.68 | 0.131954E+09 | 0.264931E+11 | 0.00 | 0.78 |
June | 0.207787E+10 | 0.143417E+10 | 0.00 | 60061910.28 | 66202130.93 | 0.00 | 0.130184E+11 | 0.00 | 0.81 |
July | 0.156453E+10 | 0.127183E+10 | 0.00 | 58791231.62 | 0.139052E+09 | 0.00 | 0.103004E+11 | 0.00 | 0.74 |
August | 0.197312E+10 | 0.130548E+10 | 0.00 | 70678493.78 | 88086853.25 | 0.00 | 0.155417E+11 | 0.00 | 0.79 |
September | 0.336603E+10 | 0.217373E+09 | 0.00 | 59085397.51 | 52633788.16 | 0.00 | 0.160055E+11 | 0.00 | 0.74 |
October | 0.178580E+11 | 0.00 | 0.00 | 23126015.75 | 0.00 | 0.113620E+10 | 0.150583E+11 | 0.00 | 0.53 |
November | 0.248276E+11 | 0.00 | 0.00 | 10484735.82 | 0.00 | 0.142729E+10 | 0.827436E+10 | 0.00 | 0.42 |
December | 0.288672E+11 | 0.00 | 0.00 | 3317407.33 | 0.00 | 0.545881E+10 | 0.380079E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.178103E+12 | 0.422988E+10 | 0.00 | 0.395893E+09 | 0.349715E+09 | 0.146180E+11 | 0.155072E+12 | 0.00 | 0.59 |
Minimum of Months | 0.156453E+10 | 0.00 | 0.00 | 3317407.33 | 0.00 | 0.00 | 0.380079E+10 | 0.00 | 0.37 |
Maximum of Months | 0.288672E+11 | 0.143417E+10 | 0.00 | 70678493.78 | 0.139052E+09 | 0.545881E+10 | 0.264931E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.517578E+10 | 0.00 | 0.00 | 683143.23 | 0.00 | 0.388606E+09 | 0.755602E+09 | 0.00 | 0.48 |
February | 0.485068E+10 | 0.00 | 0.00 | 654793.16 | 0.00 | 0.288112E+09 | 0.788816E+09 | 0.00 | 0.47 |
March | 0.395179E+10 | 0.00 | 0.00 | 3772307.33 | 0.00 | 7554590.18 | 0.273616E+10 | 0.00 | 0.69 |
April | 0.268008E+10 | 0.00 | 0.00 | 5696619.99 | 0.00 | 694846.19 | 0.390732E+10 | 0.00 | 0.82 |
May | 0.134504E+10 | 3234908.04 | 0.00 | 9452513.35 | 132559.38 | 0.00 | 0.479581E+10 | 0.00 | 1.13 |
June | 0.968497E+09 | 0.384549E+09 | 0.00 | 10287387.00 | 13253857.26 | 0.00 | 0.236894E+10 | 0.00 | 1.29 |
July | 0.107921E+10 | 0.377681E+09 | 0.00 | 9891033.77 | 38809809.88 | 0.00 | 0.188685E+10 | 0.00 | 1.28 |
August | 0.185098E+10 | 0.313021E+09 | 0.00 | 12305757.33 | 44482003.47 | 0.00 | 0.287326E+10 | 0.00 | 1.47 |
September | 0.115013E+10 | 63460050.75 | 0.00 | 8705375.09 | 11443644.60 | 0.00 | 0.252532E+10 | 0.00 | 1.03 |
October | 0.361301E+10 | 0.00 | 0.00 | 3994230.90 | 0.00 | 45536510.11 | 0.242795E+10 | 0.00 | 0.70 |
November | 0.438538E+10 | 0.00 | 0.00 | 1994820.52 | 0.00 | 0.157512E+09 | 0.158716E+10 | 0.00 | 0.56 |
December | 0.444847E+10 | 0.00 | 0.00 | 984217.90 | 0.00 | 0.112316E+10 | 0.107921E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.354991E+11 | 0.114195E+10 | 0.00 | 68422199.57 | 0.108122E+09 | 0.201117E+10 | 0.277324E+11 | 0.00 | 0.87 |
Minimum of Months | 0.968497E+09 | 0.00 | 0.00 | 654793.16 | 0.00 | 0.00 | 0.755602E+09 | 0.00 | 0.47 |
Maximum of Months | 0.517578E+10 | 0.384549E+09 | 0.00 | 12305757.33 | 44482003.47 | 0.112316E+10 | 0.479581E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580695E+10 | 0.00 | 0.00 | 1786517.46 | 0.00 | 0.488452E+09 | 0.146298E+10 | 0.00 | 0.91 |
February | 0.480910E+10 | 0.00 | 0.00 | 3083331.51 | 0.00 | 0.545299E+09 | 0.215571E+10 | 0.00 | 0.92 |
March | 0.454068E+10 | 0.00 | 0.00 | 6225833.10 | 0.00 | 43567371.65 | 0.404078E+10 | 0.00 | 1.33 |
April | 0.362265E+10 | 0.00 | 0.00 | 6234498.21 | 0.00 | 43392324.38 | 0.416995E+10 | 0.00 | 1.42 |
May | 0.188566E+10 | 2507219.82 | 0.00 | 9502004.41 | 159106.14 | 0.00 | 0.497772E+10 | 0.00 | 1.86 |
June | 0.128587E+10 | 0.274569E+09 | 0.00 | 10708527.77 | 16056123.15 | 0.00 | 0.271811E+10 | 0.00 | 2.13 |
July | 0.142237E+10 | 0.275690E+09 | 0.00 | 9337906.44 | 45223284.35 | 0.00 | 0.175328E+10 | 0.00 | 1.94 |
August | 0.254416E+10 | 0.217398E+09 | 0.00 | 11487945.15 | 53390111.64 | 0.00 | 0.299686E+10 | 0.00 | 2.43 |
September | 0.153086E+10 | 53866113.15 | 0.00 | 9716529.66 | 13735385.44 | 0.00 | 0.303453E+10 | 0.00 | 1.85 |
October | 0.417399E+10 | 0.00 | 0.00 | 5074593.85 | 0.00 | 0.308505E+09 | 0.304185E+10 | 0.00 | 1.30 |
November | 0.523049E+10 | 0.00 | 0.00 | 2652370.17 | 0.00 | 0.367577E+09 | 0.182950E+10 | 0.00 | 1.02 |
December | 0.573404E+10 | 0.00 | 0.00 | 1086040.03 | 0.00 | 0.135123E+10 | 0.917814E+09 | 0.00 | 0.88 |
Annual Sum or Average | 0.425868E+11 | 0.824031E+09 | 0.00 | 76896097.77 | 0.128564E+09 | 0.314802E+10 | 0.330991E+11 | 0.00 | 1.50 |
Minimum of Months | 0.128587E+10 | 0.00 | 0.00 | 1086040.03 | 0.00 | 0.00 | 0.917814E+09 | 0.00 | 0.88 |
Maximum of Months | 0.580695E+10 | 0.275690E+09 | 0.00 | 11487945.15 | 53390111.64 | 0.135123E+10 | 0.497772E+10 | 0.00 | 2.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.411228E+10 | 0.00 | 0.00 | 15240017.62 | 0.00 | 0.562895E+09 | 0.895666E+10 | 0.00 | 1.18 |
February | 0.360290E+10 | 0.00 | 0.00 | 14610508.23 | 0.00 | 0.715505E+09 | 0.895501E+10 | 0.00 | 1.15 |
March | 0.444992E+10 | 0.00 | 0.00 | 14963099.66 | 0.00 | 71511977.63 | 0.842893E+10 | 0.00 | 1.46 |
April | 0.383844E+10 | 0.00 | 0.00 | 9280318.71 | 0.00 | 0.143660E+09 | 0.613654E+10 | 0.00 | 1.30 |
May | 0.246805E+10 | 4410638.21 | 0.00 | 10569559.03 | 181251.69 | 626009.27 | 0.532671E+10 | 0.00 | 1.44 |
June | 0.153848E+10 | 0.418463E+09 | 0.00 | 9873213.17 | 18461499.94 | 0.00 | 0.223789E+10 | 0.00 | 1.44 |
July | 0.156989E+10 | 0.451155E+09 | 0.00 | 9735622.82 | 45325978.08 | 0.00 | 0.186580E+10 | 0.00 | 1.46 |
August | 0.264333E+10 | 0.429343E+09 | 0.00 | 15925266.15 | 60821335.93 | 0.00 | 0.340770E+10 | 0.00 | 1.92 |
September | 0.152402E+10 | 0.115643E+09 | 0.00 | 16256890.46 | 15647176.34 | 0.00 | 0.418795E+10 | 0.00 | 1.71 |
October | 0.326310E+10 | 0.00 | 0.00 | 20542472.12 | 0.00 | 0.455008E+09 | 0.887073E+10 | 0.00 | 1.64 |
November | 0.378544E+10 | 0.00 | 0.00 | 20410817.30 | 0.00 | 0.259240E+09 | 0.955083E+10 | 0.00 | 1.38 |
December | 0.421684E+10 | 0.00 | 0.00 | 15007332.67 | 0.00 | 0.111251E+10 | 0.806945E+10 | 0.00 | 1.12 |
Annual Sum or Average | 0.370127E+11 | 0.141901E+10 | 0.00 | 0.172415E+09 | 0.140437E+09 | 0.332095E+10 | 0.759942E+11 | 0.00 | 1.44 |
Minimum of Months | 0.152402E+10 | 0.00 | 0.00 | 9280318.71 | 0.00 | 0.00 | 0.186580E+10 | 0.00 | 1.12 |
Maximum of Months | 0.444992E+10 | 0.451155E+09 | 0.00 | 20542472.12 | 60821335.93 | 0.111251E+10 | 0.955083E+10 | 0.00 | 1.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743735E+10 | 0.00 | 0.00 | 2700337.78 | 0.00 | 81101139.69 | 0.246650E+10 | 0.00 | 1.20 |
February | 0.602031E+10 | 0.00 | 0.00 | 4103495.05 | 0.00 | 10247985.79 | 0.375685E+10 | 0.00 | 1.22 |
March | 0.388778E+10 | 0.00 | 0.00 | 10802346.55 | 0.00 | 0.00 | 0.723624E+10 | 0.00 | 1.85 |
April | 0.191876E+10 | 0.00 | 0.00 | 13634879.82 | 0.00 | 0.00 | 0.902042E+10 | 0.00 | 2.14 |
May | 0.205220E+10 | 4830392.92 | 0.00 | 10539179.80 | 201934.35 | 0.00 | 0.579206E+10 | 0.00 | 2.21 |
June | 0.130254E+10 | 0.517801E+09 | 0.00 | 12015676.27 | 8590236.28 | 0.00 | 0.269964E+10 | 0.00 | 2.35 |
July | 0.147968E+10 | 0.503384E+09 | 0.00 | 11841684.71 | 34339792.58 | 0.00 | 0.230136E+10 | 0.00 | 2.42 |
August | 0.183833E+10 | 0.550063E+09 | 0.00 | 22969805.86 | 33753129.89 | 0.00 | 0.507574E+10 | 0.00 | 3.35 |
September | 0.170300E+10 | 85628864.07 | 0.00 | 10255498.74 | 14553817.42 | 0.00 | 0.318397E+10 | 0.00 | 2.06 |
October | 0.421586E+10 | 0.00 | 0.00 | 8877411.58 | 0.00 | 482041.30 | 0.550331E+10 | 0.00 | 1.79 |
November | 0.473395E+10 | 0.00 | 0.00 | 6687960.31 | 0.00 | 785256.04 | 0.527402E+10 | 0.00 | 1.44 |
December | 0.536827E+10 | 0.00 | 0.00 | 6832323.44 | 0.00 | 19125352.01 | 0.551896E+10 | 0.00 | 1.27 |
Annual Sum or Average | 0.419580E+11 | 0.166171E+10 | 0.00 | 0.121261E+09 | 91438910.53 | 0.111742E+09 | 0.578291E+11 | 0.00 | 1.95 |
Minimum of Months | 0.130254E+10 | 0.00 | 0.00 | 2700337.78 | 0.00 | 0.00 | 0.230136E+10 | 0.00 | 1.20 |
Maximum of Months | 0.743735E+10 | 0.550063E+09 | 0.00 | 22969805.86 | 34339792.58 | 81101139.69 | 0.902042E+10 | 0.00 | 3.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.381688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258967E+11 | 0.00 | 0.00 | 0.48 |
February | 0.324642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285558E+11 | 0.00 | 0.00 | 0.48 |
March | 0.390146E+11 | 0.00 | 0.00 | 9840322.91 | 0.00 | 0.157177E+11 | 0.623647E+10 | 0.00 | 0.60 |
April | 0.341790E+11 | 0.00 | 0.00 | 15913984.10 | 0.00 | 0.625933E+10 | 0.102723E+11 | 0.00 | 0.59 |
May | 0.178267E+11 | 46070504.80 | 0.00 | 62504647.09 | 4893446.65 | 0.417312E+09 | 0.292135E+11 | 0.00 | 0.91 |
June | 0.499117E+10 | 0.454849E+10 | 0.00 | 82266421.19 | 0.142985E+09 | 0.00 | 0.188770E+11 | 0.00 | 1.07 |
July | 0.459089E+10 | 0.435041E+10 | 0.00 | 78624173.41 | 0.294418E+09 | 0.00 | 0.143832E+11 | 0.00 | 0.99 |
August | 0.714518E+10 | 0.351813E+10 | 0.00 | 81430793.33 | 0.160080E+09 | 0.00 | 0.185993E+11 | 0.00 | 0.95 |
September | 0.130014E+11 | 0.730747E+09 | 0.00 | 59216952.67 | 77131774.58 | 0.132290E+09 | 0.154517E+11 | 0.00 | 0.84 |
October | 0.351910E+11 | 0.00 | 0.00 | 11193898.65 | 0.00 | 0.115922E+11 | 0.669576E+10 | 0.00 | 0.59 |
November | 0.400287E+11 | 0.00 | 0.00 | 2613917.41 | 0.00 | 0.172200E+11 | 0.195047E+10 | 0.00 | 0.52 |
December | 0.267244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446520E+11 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.293326E+12 | 0.131939E+11 | 0.00 | 0.403605E+09 | 0.679508E+09 | 0.150443E+12 | 0.121680E+12 | 0.00 | 0.71 |
Minimum of Months | 0.459089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.400287E+11 | 0.454849E+10 | 0.00 | 82266421.19 | 0.294418E+09 | 0.446520E+11 | 0.292135E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.549458E+11 | 0.00 | 0.00 | 4283451.04 | 0.00 | 0.267844E+11 | 0.435559E+10 | 0.00 | 1.01 |
February | 0.461175E+11 | 0.00 | 0.00 | 12005089.67 | 0.00 | 0.277694E+11 | 0.860928E+10 | 0.00 | 1.02 |
March | 0.447891E+11 | 0.00 | 0.00 | 39586763.83 | 0.00 | 0.159324E+11 | 0.271259E+11 | 0.00 | 1.35 |
April | 0.383942E+11 | 0.00 | 0.00 | 42551800.49 | 0.00 | 0.674639E+10 | 0.286597E+11 | 0.00 | 1.33 |
May | 0.221271E+11 | 42682643.49 | 0.00 | 79121910.88 | 6573936.78 | 0.267366E+09 | 0.399527E+11 | 0.00 | 1.75 |
June | 0.779747E+10 | 0.357646E+10 | 0.00 | 0.104678E+09 | 0.188294E+09 | 0.00 | 0.264142E+11 | 0.00 | 2.03 |
July | 0.737823E+10 | 0.369920E+10 | 0.00 | 93637849.43 | 0.345326E+09 | 0.00 | 0.165554E+11 | 0.00 | 1.72 |
August | 0.984906E+10 | 0.314939E+10 | 0.00 | 0.114857E+09 | 0.215055E+09 | 0.00 | 0.300262E+11 | 0.00 | 1.98 |
September | 0.171328E+11 | 0.718372E+09 | 0.00 | 82919588.16 | 0.103499E+09 | 0.116445E+09 | 0.242645E+11 | 0.00 | 1.77 |
October | 0.397323E+11 | 0.00 | 0.00 | 30952540.86 | 0.00 | 0.152869E+11 | 0.201878E+11 | 0.00 | 1.29 |
November | 0.525092E+11 | 0.00 | 0.00 | 9401434.86 | 0.00 | 0.193352E+11 | 0.806812E+10 | 0.00 | 1.08 |
December | 0.430135E+11 | 0.00 | 0.00 | 429942.40 | 0.00 | 0.497999E+11 | 0.104568E+10 | 0.00 | 1.03 |
Annual Sum or Average | 0.383786E+12 | 0.111861E+11 | 0.00 | 0.614425E+09 | 0.858748E+09 | 0.162038E+12 | 0.235265E+12 | 0.00 | 1.45 |
Minimum of Months | 0.737823E+10 | 0.00 | 0.00 | 429942.40 | 0.00 | 0.00 | 0.104568E+10 | 0.00 | 1.01 |
Maximum of Months | 0.549458E+11 | 0.369920E+10 | 0.00 | 0.114857E+09 | 0.345326E+09 | 0.497999E+11 | 0.399527E+11 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417757E+11 | 0.00 | 0.00 | 0.165459E+09 | 0.00 | 0.109385E+11 | 0.887410E+11 | 0.00 | 1.23 |
February | 0.332935E+11 | 0.00 | 0.00 | 0.144942E+09 | 0.00 | 0.171343E+11 | 0.862752E+11 | 0.00 | 1.20 |
March | 0.382010E+11 | 0.00 | 0.00 | 0.137456E+09 | 0.00 | 0.145776E+11 | 0.726879E+11 | 0.00 | 1.42 |
April | 0.383487E+11 | 0.00 | 0.00 | 67138411.33 | 0.00 | 0.748096E+10 | 0.423504E+11 | 0.00 | 1.14 |
May | 0.250168E+11 | 69348280.24 | 0.00 | 87548361.46 | 6959709.01 | 0.698436E+09 | 0.421137E+11 | 0.00 | 1.29 |
June | 0.118368E+11 | 0.507010E+10 | 0.00 | 79486072.60 | 0.203360E+09 | 0.00 | 0.167427E+11 | 0.00 | 1.24 |
July | 0.865136E+10 | 0.532674E+10 | 0.00 | 80188515.59 | 0.383969E+09 | 0.00 | 0.144957E+11 | 0.00 | 1.18 |
August | 0.111412E+11 | 0.551368E+10 | 0.00 | 0.126651E+09 | 0.216079E+09 | 0.00 | 0.260263E+11 | 0.00 | 1.42 |
September | 0.139840E+11 | 0.154294E+10 | 0.00 | 0.152672E+09 | 0.109240E+09 | 0.132735E+09 | 0.363899E+11 | 0.00 | 1.62 |
October | 0.276551E+11 | 0.00 | 0.00 | 0.219138E+09 | 0.00 | 0.139848E+11 | 0.800627E+11 | 0.00 | 1.61 |
November | 0.362769E+11 | 0.00 | 0.00 | 0.201872E+09 | 0.00 | 0.995243E+10 | 0.885111E+11 | 0.00 | 1.38 |
December | 0.435815E+11 | 0.00 | 0.00 | 0.119680E+09 | 0.00 | 0.257334E+11 | 0.636111E+11 | 0.00 | 1.11 |
Annual Sum or Average | 0.329763E+12 | 0.175228E+11 | 0.00 | 0.158223E+10 | 0.919608E+09 | 0.100633E+12 | 0.658008E+12 | 0.00 | 1.32 |
Minimum of Months | 0.865136E+10 | 0.00 | 0.00 | 67138411.33 | 0.00 | 0.00 | 0.144957E+11 | 0.00 | 1.11 |
Maximum of Months | 0.435815E+11 | 0.551368E+10 | 0.00 | 0.219138E+09 | 0.383969E+09 | 0.257334E+11 | 0.887410E+11 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.645851E+11 | 0.00 | 0.00 | 10387572.38 | 0.00 | 0.207103E+11 | 0.916797E+10 | 0.00 | 1.12 |
February | 0.563322E+11 | 0.00 | 0.00 | 13271058.26 | 0.00 | 0.234147E+11 | 0.111182E+11 | 0.00 | 1.13 |
March | 0.599860E+11 | 0.00 | 0.00 | 33456718.95 | 0.00 | 0.143275E+11 | 0.204783E+11 | 0.00 | 1.51 |
April | 0.484152E+11 | 0.00 | 0.00 | 33094995.58 | 0.00 | 0.663134E+10 | 0.223869E+11 | 0.00 | 1.42 |
May | 0.299806E+11 | 66336529.11 | 0.00 | 60183186.80 | 7179701.86 | 0.349196E+09 | 0.317392E+11 | 0.00 | 1.80 |
June | 0.119052E+11 | 0.566754E+10 | 0.00 | 63638685.95 | 0.107042E+09 | 0.00 | 0.143763E+11 | 0.00 | 1.77 |
July | 0.993191E+10 | 0.484046E+10 | 0.00 | 54552260.08 | 0.327472E+09 | 0.00 | 0.116334E+11 | 0.00 | 1.60 |
August | 0.130480E+11 | 0.496952E+10 | 0.00 | 78681883.50 | 0.187020E+09 | 0.00 | 0.168514E+11 | 0.00 | 1.72 |
September | 0.207677E+11 | 0.938213E+09 | 0.00 | 56234776.37 | 88078414.66 | 0.300007E+09 | 0.174909E+11 | 0.00 | 1.69 |
October | 0.515645E+11 | 0.00 | 0.00 | 36085732.69 | 0.00 | 0.128935E+11 | 0.184907E+11 | 0.00 | 1.47 |
November | 0.619383E+11 | 0.00 | 0.00 | 14186229.16 | 0.00 | 0.152525E+11 | 0.106864E+11 | 0.00 | 1.21 |
December | 0.538923E+11 | 0.00 | 0.00 | 5102902.51 | 0.00 | 0.439033E+11 | 0.484705E+10 | 0.00 | 1.13 |
Annual Sum or Average | 0.482347E+12 | 0.164821E+11 | 0.00 | 0.458876E+09 | 0.716793E+09 | 0.137782E+12 | 0.189267E+12 | 0.00 | 1.47 |
Minimum of Months | 0.993191E+10 | 0.00 | 0.00 | 5102902.51 | 0.00 | 0.00 | 0.484705E+10 | 0.00 | 1.12 |
Maximum of Months | 0.645851E+11 | 0.566754E+10 | 0.00 | 78681883.50 | 0.327472E+09 | 0.439033E+11 | 0.317392E+11 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464488E+10 | 0.00 | 0.00 | 0.56 |
February | 0.216412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425480E+10 | 0.00 | 0.00 | 0.55 |
March | 0.326548E+10 | 0.00 | 0.00 | 569820.66 | 0.00 | 0.286966E+10 | 0.444559E+09 | 0.00 | 0.67 |
April | 0.292257E+10 | 0.00 | 0.00 | 1144693.51 | 0.00 | 0.184823E+10 | 0.840172E+09 | 0.00 | 0.67 |
May | 0.226033E+10 | 185106.44 | 0.00 | 5152596.60 | 693982.06 | 0.150274E+09 | 0.240061E+10 | 0.00 | 0.93 |
June | 0.636781E+09 | 0.324390E+09 | 0.00 | 8949428.93 | 12281498.25 | 0.00 | 0.182743E+10 | 0.00 | 1.15 |
July | 0.529819E+09 | 0.294936E+09 | 0.00 | 8431036.26 | 24591445.23 | 0.00 | 0.138991E+10 | 0.00 | 1.04 |
August | 0.925383E+09 | 0.255146E+09 | 0.00 | 8600580.63 | 16428410.82 | 0.00 | 0.167474E+10 | 0.00 | 1.00 |
September | 0.146247E+10 | 44003305.48 | 0.00 | 6076662.43 | 9764365.11 | 90979119.65 | 0.130135E+10 | 0.00 | 0.89 |
October | 0.330542E+10 | 0.00 | 0.00 | 503679.70 | 0.00 | 0.218123E+10 | 0.277549E+09 | 0.00 | 0.68 |
November | 0.226740E+10 | 0.00 | 0.00 | 52558.71 | 0.00 | 0.392669E+10 | 75186232.31 | 0.00 | 0.58 |
December | 0.157180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612011E+10 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.235085E+11 | 0.918660E+09 | 0.00 | 39481057.43 | 63759701.47 | 0.260869E+11 | 0.102315E+11 | 0.00 | 0.77 |
Minimum of Months | 0.529819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.330542E+10 | 0.324390E+09 | 0.00 | 8949428.93 | 24591445.23 | 0.612011E+10 | 0.240061E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.387636E+10 | 0.00 | 0.00 | 68186.02 | 0.00 | 0.366481E+10 | 0.131407E+09 | 0.00 | 0.98 |
February | 0.380325E+10 | 0.00 | 0.00 | 298569.98 | 0.00 | 0.305006E+10 | 0.357671E+09 | 0.00 | 0.96 |
March | 0.347283E+10 | 0.00 | 0.00 | 2950559.89 | 0.00 | 0.220214E+10 | 0.220048E+10 | 0.00 | 1.27 |
April | 0.285041E+10 | 0.00 | 0.00 | 3439677.22 | 0.00 | 0.159427E+10 | 0.249852E+10 | 0.00 | 1.31 |
May | 0.202423E+10 | 499279.08 | 0.00 | 7198180.76 | 456363.49 | 96625818.61 | 0.368830E+10 | 0.00 | 1.70 |
June | 0.603699E+09 | 0.251405E+09 | 0.00 | 11950204.29 | 13925507.01 | 0.00 | 0.273946E+10 | 0.00 | 2.12 |
July | 0.618655E+09 | 0.248099E+09 | 0.00 | 10450390.80 | 24428570.52 | 0.00 | 0.165974E+10 | 0.00 | 1.76 |
August | 0.818913E+09 | 0.226703E+09 | 0.00 | 12812595.50 | 18901261.38 | 0.00 | 0.301822E+10 | 0.00 | 2.01 |
September | 0.143388E+10 | 44742617.04 | 0.00 | 8781016.78 | 11234124.78 | 62063648.49 | 0.223579E+10 | 0.00 | 1.75 |
October | 0.300477E+10 | 0.00 | 0.00 | 2054547.10 | 0.00 | 0.214899E+10 | 0.153815E+10 | 0.00 | 1.24 |
November | 0.362050E+10 | 0.00 | 0.00 | 308249.30 | 0.00 | 0.301851E+10 | 0.456999E+09 | 0.00 | 1.03 |
December | 0.298750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513847E+10 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.291150E+11 | 0.771448E+09 | 0.00 | 60312177.65 | 68945827.19 | 0.209759E+11 | 0.205247E+11 | 0.00 | 1.43 |
Minimum of Months | 0.603699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
Maximum of Months | 0.387636E+10 | 0.251405E+09 | 0.00 | 12812595.50 | 24428570.52 | 0.513847E+10 | 0.368830E+10 | 0.00 | 2.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336285E+10 | 0.00 | 0.00 | 9875680.82 | 0.00 | 0.253460E+10 | 0.669778E+10 | 0.00 | 1.17 |
February | 0.297336E+10 | 0.00 | 0.00 | 10131478.27 | 0.00 | 0.231843E+10 | 0.710387E+10 | 0.00 | 1.14 |
March | 0.333559E+10 | 0.00 | 0.00 | 11160862.61 | 0.00 | 0.225248E+10 | 0.675701E+10 | 0.00 | 1.42 |
April | 0.319964E+10 | 0.00 | 0.00 | 5732520.17 | 0.00 | 0.184341E+10 | 0.396550E+10 | 0.00 | 1.15 |
May | 0.276304E+10 | 276605.75 | 0.00 | 7855008.65 | 937099.56 | 0.199036E+09 | 0.383380E+10 | 0.00 | 1.31 |
June | 0.123995E+10 | 0.350700E+09 | 0.00 | 9313454.40 | 17204688.61 | 0.00 | 0.179344E+10 | 0.00 | 1.36 |
July | 0.926604E+09 | 0.346776E+09 | 0.00 | 9082229.13 | 29388563.10 | 0.00 | 0.147192E+10 | 0.00 | 1.26 |
August | 0.123889E+10 | 0.378105E+09 | 0.00 | 15090590.87 | 22183651.97 | 0.00 | 0.260368E+10 | 0.00 | 1.48 |
September | 0.133590E+10 | 87596710.00 | 0.00 | 17150982.94 | 13139799.81 | 87463009.32 | 0.360319E+10 | 0.00 | 1.66 |
October | 0.230701E+10 | 0.00 | 0.00 | 17601451.81 | 0.00 | 0.224139E+10 | 0.724752E+10 | 0.00 | 1.62 |
November | 0.297825E+10 | 0.00 | 0.00 | 12974498.52 | 0.00 | 0.228301E+10 | 0.683249E+10 | 0.00 | 1.30 |
December | 0.370604E+10 | 0.00 | 0.00 | 7424359.96 | 0.00 | 0.373329E+10 | 0.441096E+10 | 0.00 | 1.05 |
Annual Sum or Average | 0.293671E+11 | 0.116345E+10 | 0.00 | 0.133393E+09 | 82853803.06 | 0.174931E+11 | 0.563212E+11 | 0.00 | 1.33 |
Minimum of Months | 0.926604E+09 | 0.00 | 0.00 | 5732520.17 | 0.00 | 0.00 | 0.147192E+10 | 0.00 | 1.05 |
Maximum of Months | 0.370604E+10 | 0.378105E+09 | 0.00 | 17601451.81 | 29388563.10 | 0.373329E+10 | 0.724752E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444836E+10 | 0.00 | 0.00 | 651059.46 | 0.00 | 0.390258E+10 | 0.702446E+09 | 0.00 | 1.17 |
February | 0.414040E+10 | 0.00 | 0.00 | 1045765.81 | 0.00 | 0.350495E+10 | 0.962363E+09 | 0.00 | 1.15 |
March | 0.495496E+10 | 0.00 | 0.00 | 2969652.78 | 0.00 | 0.247742E+10 | 0.198670E+10 | 0.00 | 1.56 |
April | 0.423986E+10 | 0.00 | 0.00 | 3018866.15 | 0.00 | 0.153779E+10 | 0.213345E+10 | 0.00 | 1.49 |
May | 0.320508E+10 | 335363.30 | 0.00 | 5725220.16 | 823277.98 | 0.136980E+09 | 0.294736E+10 | 0.00 | 1.86 |
June | 0.119010E+10 | 0.391970E+09 | 0.00 | 8178837.29 | 7889225.22 | 0.00 | 0.150798E+10 | 0.00 | 1.91 |
July | 0.100979E+10 | 0.321021E+09 | 0.00 | 6266455.06 | 24973495.80 | 0.00 | 0.114867E+10 | 0.00 | 1.69 |
August | 0.136164E+10 | 0.346023E+09 | 0.00 | 9390942.85 | 20036749.38 | 0.00 | 0.163732E+10 | 0.00 | 1.79 |
September | 0.208175E+10 | 58108743.21 | 0.00 | 6534255.34 | 10427636.17 | 84416153.68 | 0.159676E+10 | 0.00 | 1.77 |
October | 0.409875E+10 | 0.00 | 0.00 | 3015635.71 | 0.00 | 0.233990E+10 | 0.171357E+10 | 0.00 | 1.54 |
November | 0.429683E+10 | 0.00 | 0.00 | 1035240.99 | 0.00 | 0.327905E+10 | 0.844046E+09 | 0.00 | 1.24 |
December | 0.369457E+10 | 0.00 | 0.00 | 306873.06 | 0.00 | 0.553359E+10 | 0.295499E+09 | 0.00 | 1.15 |
Annual Sum or Average | 0.387221E+11 | 0.111746E+10 | 0.00 | 48138804.66 | 64150384.53 | 0.227967E+11 | 0.174762E+11 | 0.00 | 1.53 |
Minimum of Months | 0.100979E+10 | 0.00 | 0.00 | 306873.06 | 0.00 | 0.00 | 0.295499E+09 | 0.00 | 1.15 |
Maximum of Months | 0.495496E+10 | 0.391970E+09 | 0.00 | 9390942.85 | 24973495.80 | 0.553359E+10 | 0.294736E+10 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3506174.54 | 0.00 | 0.00 | 0.566378E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7995917.40 | 0.00 | 0.00 | 0.533129E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14432639.30 | 0.00 | 0.00 | 0.509111E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17438810.94 | 0.00 | 0.00 | 0.396323E+09 | 0.00 | 0.29 |
May | 0.00 | 161211.18 | 0.00 | 3912773.15 | 0.00 | 0.00 | 0.262661E+09 | 0.00 | 0.29 |
June | 0.00 | 27270652.47 | 0.00 | 5101880.80 | 0.00 | 0.00 | 47272908.75 | 0.00 | 0.30 |
July | 0.00 | 51781249.23 | 0.00 | 5465245.89 | 0.00 | 0.00 | 30766180.22 | 0.00 | 0.28 |
August | 0.00 | 26233379.93 | 0.00 | 12718710.63 | 0.00 | 0.00 | 61323235.59 | 0.00 | 0.30 |
September | 0.00 | 674262.15 | 0.00 | 3832913.66 | 0.00 | 0.00 | 0.165451E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 8489249.51 | 0.00 | 0.00 | 0.427761E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13197834.58 | 0.00 | 0.00 | 0.499413E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18259116.16 | 0.00 | 0.00 | 0.597423E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.106121E+09 | 0.00 | 0.114351E+09 | 0.00 | 0.00 | 0.409701E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3506174.54 | 0.00 | 0.00 | 30766180.22 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 51781249.23 | 0.00 | 18259116.16 | 0.00 | 0.00 | 0.597423E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 89116678.47 | 0.00 | 0.00 | 23402337.97 | 0.00 | 0.00 | 0.558944E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 65282289.04 | 0.00 | 0.00 | 0.534555E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.127441E+09 | 0.00 | 0.00 | 0.510743E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.157053E+09 | 0.00 | 0.00 | 0.398041E+10 | 0.00 | 0.29 |
May | 0.00 | 1451325.70 | 0.00 | 33243311.22 | 0.00 | 0.00 | 0.264017E+10 | 0.00 | 0.29 |
June | 0.00 | 0.269016E+09 | 0.00 | 48158146.85 | 0.00 | 0.00 | 0.476228E+09 | 0.00 | 0.30 |
July | 0.00 | 0.514446E+09 | 0.00 | 52007944.98 | 0.00 | 0.00 | 0.310422E+09 | 0.00 | 0.28 |
August | 0.00 | 0.264992E+09 | 0.00 | 0.116531E+09 | 0.00 | 0.00 | 0.604145E+09 | 0.00 | 0.30 |
September | 0.00 | 6589179.82 | 0.00 | 33384838.30 | 0.00 | 0.00 | 0.166492E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 73288697.02 | 0.00 | 0.00 | 0.428945E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.115680E+09 | 0.00 | 0.00 | 0.500959E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.158547E+09 | 0.00 | 0.00 | 0.599786E+10 | 0.00 | 0.28 |
Annual Sum or Average | 89116678.47 | 0.105649E+10 | 0.00 | 0.100402E+10 | 0.00 | 0.00 | 0.410156E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23402337.97 | 0.00 | 0.00 | 0.310422E+09 | 0.00 | 0.28 |
Maximum of Months | 89116678.47 | 0.514446E+09 | 0.00 | 0.158547E+09 | 0.00 | 0.00 | 0.599786E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194292E+09 | 0.00 | 0.00 | 1235984.57 | 0.00 | 0.00 | 0.371694E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5414325.25 | 0.00 | 0.00 | 0.535819E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11800330.44 | 0.00 | 0.00 | 0.511954E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14993121.12 | 0.00 | 0.00 | 0.398919E+09 | 0.00 | 0.29 |
May | 7180225.19 | 154939.31 | 0.00 | 2997757.51 | 0.00 | 0.00 | 0.257603E+09 | 0.00 | 0.29 |
June | 0.00 | 26907772.64 | 0.00 | 4835501.14 | 0.00 | 0.00 | 47663461.82 | 0.00 | 0.30 |
July | 0.00 | 51391168.45 | 0.00 | 5210709.13 | 0.00 | 0.00 | 31052463.50 | 0.00 | 0.28 |
August | 0.00 | 26539385.31 | 0.00 | 11598583.35 | 0.00 | 0.00 | 59977791.94 | 0.00 | 0.30 |
September | 3559694.85 | 647675.01 | 0.00 | 3133197.66 | 0.00 | 0.00 | 0.163348E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 6382613.23 | 0.00 | 0.00 | 0.430382E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10364228.71 | 0.00 | 0.00 | 0.502445E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14569043.28 | 0.00 | 0.00 | 0.601094E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.205032E+09 | 0.105641E+09 | 0.00 | 92535395.37 | 0.00 | 0.00 | 0.391195E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1235984.57 | 0.00 | 0.00 | 31052463.50 | 0.00 | 0.28 |
Maximum of Months | 0.194292E+09 | 51391168.45 | 0.00 | 14993121.12 | 0.00 | 0.00 | 0.601094E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.230852E+09 | 0.00 | 0.00 | 0.153913E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.439251E+09 | 0.00 | 0.00 | 0.146599E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.738097E+09 | 0.00 | 0.00 | 0.145440E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.896919E+09 | 0.00 | 0.00 | 0.124127E+11 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.215690E+09 | 0.00 | 0.00 | 0.786760E+10 | 0.00 | 0.33 |
June | 0.00 | 0.285396E+09 | 0.00 | 0.326877E+09 | 0.00 | 0.00 | 0.212027E+10 | 0.00 | 0.34 |
July | 0.00 | 0.666047E+09 | 0.00 | 0.357323E+09 | 0.00 | 0.00 | 0.125262E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.100048E+10 | 0.00 | 0.00 | 0.703558E+10 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.00 | 0.213460E+09 | 0.00 | 0.00 | 0.565646E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.448968E+09 | 0.00 | 0.00 | 0.121280E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.681598E+09 | 0.00 | 0.00 | 0.133506E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.956388E+09 | 0.00 | 0.00 | 0.177130E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.951444E+09 | 0.00 | 0.650591E+10 | 0.00 | 0.00 | 0.124132E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213460E+09 | 0.00 | 0.00 | 0.125262E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.666047E+09 | 0.00 | 0.100048E+10 | 0.00 | 0.00 | 0.177130E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:00
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.464424E+12 | 0.147029E+11 | 0.00 | 0.213765E+13 | 0.747122E+12 |
February | 0.585067E+12 | 0.231526E+11 | 0.00 | 0.189566E+13 | 0.105640E+13 |
March | 0.719917E+12 | 0.250642E+11 | 0.00 | 0.205832E+13 | 0.169831E+13 |
April | 0.773652E+12 | 0.264887E+11 | 0.00 | 0.205441E+13 | 0.204887E+13 |
May | 0.884768E+12 | 0.135501E+11 | 0.00 | 0.199431E+13 | 0.118381E+13 |
June | 0.929962E+12 | 0.578145E+10 | 0.00 | 0.114573E+13 | 0.284728E+13 |
July | 0.880492E+12 | 0.448341E+10 | 0.00 | 0.944193E+12 | 0.332014E+13 |
August | 0.862545E+12 | 0.484270E+10 | 0.00 | 0.103168E+13 | 0.375961E+13 |
September | 0.653456E+12 | 0.859657E+10 | 0.00 | 0.145473E+13 | 0.185257E+13 |
October | 0.574910E+12 | 0.187289E+11 | 0.00 | 0.217946E+13 | 0.135986E+13 |
November | 0.490540E+12 | 0.167179E+11 | 0.00 | 0.214532E+13 | 0.160354E+13 |
December | 0.389693E+12 | 0.308557E+11 | 0.00 | 0.200793E+13 | 0.210525E+13 |
Annual Sum or Average | 0.820943E+13 | 0.192965E+12 | 0.00 | 0.210494E+14 | 0.235828E+14 |
Minimum of Months | 0.389693E+12 | 0.448341E+10 | 0.00 | 0.944193E+12 | 0.747122E+12 |
Maximum of Months | 0.929962E+12 | 0.308557E+11 | 0.00 | 0.217946E+13 | 0.375961E+13 |