Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 09:02:55
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31188.78 | 673.33 | 673.33 |
Net Site Energy | 31188.78 | 673.33 | 673.33 |
Total Source Energy | 96252.34 | 2077.97 | 2077.97 |
Net Source Energy | 96252.34 | 2077.97 | 2077.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 469.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2462.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1391.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4100.17 |
Humidification | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 741.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29977.77 | 1211.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6381.37 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 469.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2462.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1391.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4100.17 |
Humidification | General | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 741.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 469.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2462.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 670.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1391.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4100.17 |
Humidification | Unassigned | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 741.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 170.96 | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 647.18 | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 170.96 | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 647.18 | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29977.769 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29977.769 | 100.00 |
Total On-Site and Utility Electric Sources | 29977.769 | 100.00 |
Total Electricity End Uses | 29977.769 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6381.37 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6381.37 | 100.00 |
Total Water End Uses | 6381.37 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 229.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.1390 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.1390 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1390 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.1390 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.1390 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.1390 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.1390 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8180 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:50 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 752660.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 448084.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 86589.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197236.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63208.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82101.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31236.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2015457.69 | 783896.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 752660.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 448084.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 197236.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 63208.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 82101.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 31236.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 508.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10740.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2866.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6326.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7797.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2124.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4408.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 94939.60 | 1312.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 10.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 231.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2049.63 | 28.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 10.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 231.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2049.63 | 28.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.63 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.477450 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.54 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.463128 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.68 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.92 | 0.321237 | 0.300000 | 1.78 | 0.856632 | 0.500000 | 0.001186 | 0.000154 | 1.78 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.72 | 0.341355 | 0.301000 | 16.77 | 0.910281 | 0.500000 | 0.001116 | 0.003093 | 16.77 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.47 | 0.347709 | 0.308000 | 1.68 | 0.927225 | 0.500000 | 0.001096 | 0.000596 | 2.06 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.881074 | 0.271056 | 0.300000 | 0.264322 | 0.722817 | 0.500000 | 0.001406 | 0.000056 | 0.264322 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.947007 | 0.162517 | 0.300000 | 0.284102 | 0.433380 | 0.500000 | 0.002344 | 0.000050 | 0.284102 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.16 | 0.205147 | 0.300000 | 0.349250 | 0.547060 | 0.500000 | 0.001857 | 0.000079 | 0.349250 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.21 | 0.126859 | 0.300000 | 0.363961 | 0.338290 | 0.500000 | 0.003003 | 0.000043 | 0.363961 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.25 | 0.289401 | 0.301000 | 2.48 | 0.771737 | 0.500000 | 0.001317 | 0.001398 | 4.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.63 | 0.159888 | 0.301000 | 2.90 | 0.426369 | 0.500000 | 0.002383 | 0.000936 | 3.25 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.17 | 0.213751 | 0.301000 | 3.36 | 0.570003 | 0.500000 | 0.001782 | 0.001405 | 4.88 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.30 | 0.149402 | 0.301000 | 3.10 | 0.398406 | 0.500000 | 0.002550 | 0.000857 | 3.10 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.955114 | 0.250044 | 0.308000 | 0.294175 | 0.666784 | 0.500000 | 0.001524 | 0.000190 | 0.661605 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.962924 | 0.159831 | 0.308000 | 0.296581 | 0.426216 | 0.500000 | 0.002384 | 0.000126 | 0.438351 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.24 | 0.192030 | 0.308000 | 0.383057 | 0.512079 | 0.500000 | 0.001984 | 0.000191 | 0.664281 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.12 | 0.137660 | 0.308000 | 0.344348 | 0.367092 | 0.500000 | 0.002768 | 0.000119 | 0.414957 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17552.69 | 0.000154 | 353.85 |
CORE_MID VAV BOX REHEAT COIL | 353599.38 | 0.003093 | 8033.88 |
CORE_TOP VAV BOX REHEAT COIL | 68122.29 | 0.000596 | 1799.58 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6366.37 | 0.000056 | 149.84 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5673.93 | 0.000050 | 127.28 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9078.50 | 0.000079 | 218.71 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4956.20 | 0.000043 | 103.78 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 159768.61 | 0.001398 | 4214.86 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 106940.67 | 0.000936 | 2821.08 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 160569.90 | 0.001405 | 4235.98 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 98000.55 | 0.000857 | 2539.12 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21768.65 | 0.000190 | 574.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14422.12 | 0.000126 | 380.34 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21856.52 | 0.000191 | 576.41 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13653.72 | 0.000119 | 360.09 |
VAV_BOT WITH REHEAT HEATING COIL | 29592.92 | 0.000259 | 508.99 |
VAV_MID WITH REHEAT HEATING COIL | 276530.50 | 0.002419 | 4753.75 |
VAV_TOP WITH REHEAT HEATING COIL | 29917.59 | 0.000262 | 514.30 |
CAV_BAS HEATING COIL | 261828.03 | 0.002291 | 5929.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.06 | 3.04 | 10.13 | 3.04 | 9.31 | 9.31 | 0.300000 | 0.326268 | 9.31 |
VAV_MID WITH REHEAT | 47.54 | 28.62 | 95.07 | 28.62 | 86.25 | 86.25 | 0.300000 | 0.331806 | 86.25 |
VAV_TOP WITH REHEAT | 4.87 | 3.00 | 9.75 | 4.24 | 9.33 | 9.33 | 0.300000 | 0.454626 | 9.33 |
CAV_BAS | 5.63 | 5.63 | 5.63 | 5.63 | 5.63 | 5.63 | 1.00 | 1.00 | 5.63 |
AIRLOOP DATACENTER BASEMENT | 21.68 | 21.68 | 21.68 | 21.68 | 21.68 | 21.68 | 1.00 | 0.999988 | 21.68 |
AIRLOOP DATACENTER BOT | 0.477450 | 0.477450 | 0.477450 | 0.477450 | 0.477450 | 0.477450 | 1.00 | 1.00 | 0.477450 |
AIRLOOP DATACENTER MID | 4.54 | 4.54 | 4.54 | 4.54 | 4.54 | 4.54 | 1.00 | 1.00 | 4.54 |
AIRLOOP DATACENTER TOP | 0.463128 | 0.463128 | 0.463128 | 0.463128 | 0.463128 | 0.463128 | 1.00 | 1.00 | 0.463128 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.31 | 2.74 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.25 | 28.64 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.33 | 3.01 |
CAV_BAS_OA_CONTROLLER | 5.63 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.68 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.477450 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.54 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.463128 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.25 | 6.67 | 10.91 | 0.008660 | 0.008500 | 176854.47 | 0.007524 | 9.31 |
VAV_MID WITH REHEAT COOLING COIL | 26.62 | 6.67 | 10.91 | 0.008647 | 0.008500 | 1673011.05 | 0.071174 | 86.25 |
VAV_TOP WITH REHEAT COOLING COIL | 26.35 | 6.67 | 10.91 | 0.008632 | 0.008500 | 177525.69 | 0.007552 | 9.33 |
CAV_BAS COOLING COIL | 24.27 | 6.67 | 11.27 | 0.008799 | 0.008500 | 93307.53 | 0.003970 | 5.63 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.31 |
VAV_MID WITH REHEAT FAN | 86.25 |
VAV_TOP WITH REHEAT FAN | 9.33 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007524 | 0.000063 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000259 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.071174 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002419 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007552 | 0.000063 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000262 | |
CAV_BAS_COOLC_CONTROLLER | 0.003970 | 0.000120 |
CAV_BAS_HEATC_CONTROLLER | 0.002291 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.63 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.68 | 427734.10 | 304842.55 | 0.010475 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.477450 | 9238.26 | 6647.40 | 0.000226 |
AIRLOOP DATACENTER MID COOLING COIL | 4.54 | 87938.88 | 63251.64 | 0.002154 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.463128 | 8965.04 | 6449.24 | 0.000220 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.68 | 21.68 | 21.68 | 21.68 | 427734.10 | 427734.10 | 14546.91 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.477450 | 0.477450 | 0.477450 | 0.477450 | 9238.26 | 9238.26 | 672.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.54 | 4.54 | 4.54 | 4.54 | 87938.88 | 87938.88 | 6720.07 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.463128 | 0.463128 | 0.463128 | 0.463128 | 8965.04 | 8965.04 | 672.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.68 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.477450 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.54 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.463128 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.68 | 427734.10 | 0.010475 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.477450 | 9238.26 | 0.000226 |
AIRLOOP DATACENTER MID HEATING COIL | 4.54 | 87938.88 | 0.002154 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.463128 | 8965.04 | 0.000220 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14546.91 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 672.01 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6720.07 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 672.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000085 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.090219 | 18590.88 | |
HEATSYS1 PUMP | 0.014524 | 4374.04 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.090219 | 10.83 |
HEATSYS1 | 0.014524 | 1.74 |
COOLSYS1_SUPPLY | 0.090219 | 10.83 |
SINGLE WATER PLANT LOOP | 0.013075 | 1.57 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.090219 | 0.090219 | 378696.21 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1660199.14 | 1660199.14 | 0.014524 |
CENTRAL BOILER | 538561.25 | 527854.83 | 0.013075 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.090219 | 12871.09 |
PLANT CIRC PUMP | 0.013075 | 3334.68 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.090219 | 0.045365 | 1068974.31 | 1074044.39 | 0.053354 |
COOLSYS1 CHILLER2 | 0.090219 | 0.045365 | 1068974.31 | 1074044.39 | 0.053354 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013075 | 139666.47 | 60190.47 | 69833.23 | 7879.72 | 21503.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.106707 | 12.80 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.106707 | 32137.89 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 44.05 | 1275205.56 | 8.81 | 159400.70 |
TOWERWATERSYS COOLTOWER 2 | 44.05 | 1275205.56 | 8.81 | 159400.70 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.055207 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.139 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.981 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.139 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.562 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25401.240 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25401.240 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7162.063 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7162.063 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.388 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.309 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.748 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5529 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5968 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4048 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.14936390E-14 | 0.46629455E-16 | -0.12795352E-09 | -0.66400649E-17 |
51 | 8 | 0.18805887E-07 | 0.18159818E-12 | 0.34474146E-03 | -0.21382941E-09 |
52 | 7 | -0.11252545E-01 | 0.97723248E-08 | -0.21660891E-01 | 0.12794553E-03 |
53 | 6 | 0.37847320 | 0.34543709E-05 | 0.44913146 | -0.44309468E-02 |
54 | 5 | -4.9282258 | 0.13076234E-03 | -4.2646138 | 0.59931023E-01 |
55 | 4 | 31.842168 | 0.10829460E-02 | 20.749181 | -0.40671262 |
56 | 3 | -108.75588 | 0.23861691E-02 | -54.257293 | 1.4795061 |
57 | 2 | 194.68186 | 0.13553303E-02 | 76.622599 | -2.8618236 |
58 | 1 | -170.25944 | 0.14599092E-03 | -54.892904 | 2.7297248 |
59 | 0 | 57.057407 | 0.83922952E-06 | 15.620320 | |
60 | 9 | 0.13190950E-14 | 0.47053660E-16 | -0.13177724E-09 | -0.28207423E-17 |
61 | 8 | 0.19344724E-07 | 0.17221620E-12 | 0.35067097E-03 | -0.21995616E-09 |
62 | 7 | -0.11430408E-01 | 0.92046754E-08 | -0.21917296E-01 | 0.12996789E-03 |
63 | 6 | 0.38330737 | 0.32449471E-05 | 0.45327188 | -0.44879295E-02 |
64 | 5 | -4.9754179 | 0.12255100E-03 | -4.2965173 | 0.60516169E-01 |
65 | 4 | 32.051012 | 0.10128445E-02 | 20.874116 | -0.40948534 |
66 | 3 | -109.20051 | 0.22276377E-02 | -54.504393 | 1.4859293 |
67 | 2 | 195.12287 | 0.12632445E-02 | 76.848802 | -2.8688263 |
68 | 1 | -170.42247 | 0.13586949E-03 | -54.957888 | 2.7325821 |
69 | 0 | 57.057407 | 0.77977499E-06 | 15.608941 | |
70 | 9 | 0.10819255E-14 | 0.54711344E-16 | -0.11066527E-09 | -0.36132711E-17 |
71 | 8 | 0.16356712E-07 | 0.22118555E-12 | 0.31701547E-03 | -0.18598145E-09 |
72 | 7 | -0.10418202E-01 | 0.12306004E-07 | -0.20457116E-01 | 0.11845872E-03 |
73 | 6 | 0.35579247 | 0.44086679E-05 | 0.42963628 | -0.41635997E-02 |
74 | 5 | -4.7067638 | 0.16880913E-03 | -4.1140972 | 0.57185110E-01 |
75 | 4 | 30.861815 | 0.14123489E-02 | 20.159088 | -0.39369740 |
76 | 3 | -106.66785 | 0.31399051E-02 | -53.089917 | 1.4493439 |
77 | 2 | 192.60981 | 0.17975336E-02 | 75.555228 | -2.8289238 |
78 | 1 | -169.49307 | 0.19502980E-03 | -54.588616 | 2.7162932 |
79 | 0 | 57.057407 | 0.11300463E-05 | 15.675537 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.640 | 2.640 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.48111E-002 | 0.16139 | 0.61554 | 0.61554 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11929 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 9.868E-004 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 9.962E-004 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 9.868E-004 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 9.962E-004 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 1.025E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 1.025E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 7.891E-005 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76688.93544 | 76688.93544 | 5.62609 | 5.62609 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80713.56388 | 80713.56388 | 5.92100 | 5.92100 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 759760.96948 | 759760.96948 | 55.72034 | 55.72034 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 187866.90747 | 187866.90747 | 8.02400 | 10.77825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 73889.26520 | 73889.26520 | 5.47021 | 5.47021 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 47737.95645 | 47737.95645 | 2.06286 | 2.06286 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11901.42621 | 11901.42621 | 0.88107 | 0.88107 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3761.33019 | 3761.33019 | 0.16177 | 0.16177 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12884.84675 | 12884.84675 | 0.94701 | 0.94701 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2873.21552 | 2873.21552 | 0.12385 | 0.12385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15725.44031 | 15725.44031 | 1.16417 | 1.16417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 5633.96746 | 5633.96746 | 0.24330 | 0.24330 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16387.88874 | 16387.88874 | 1.21320 | 1.21320 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1372.67592 | 1372.67592 | 5.90882E-002 | 8.72129E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 111471.06789 | 111471.06789 | 8.25222 | 8.25222 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 111877.16979 | 111877.16979 | 4.85240 | 4.85240 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 130026.18337 | 130026.18337 | 9.62579 | 9.62579 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.22398E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74880.49074 | 74880.49074 | 3.24827 | 3.24827 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 150926.18726 | 150926.18726 | 11.17308 | 11.17308 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 112437.30642 | 112437.30642 | 4.87680 | 4.87680 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 139151.48309 | 139151.48309 | 10.30138 | 10.30138 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 67401.92541 | 67401.92541 | 2.92268 | 2.92268 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12901.74859 | 12901.74859 | 0.95511 | 0.95511 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15237.29805 | 15237.29805 | 0.66161 | 0.66161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13007.28723 | 13007.28723 | 0.96292 | 0.96292 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 26.90933 | 8.22654E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10094.73660 | 10094.73660 | 0.43835 | 0.43835 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16799.89557 | 16799.89557 | 1.24369 | 1.24369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 31.15167 | 8.23326E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15298.72887 | 15298.72887 | 0.66428 | 0.66428 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15102.22618 | 15102.22618 | 1.11801 | 1.11801 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9557.52177 | 9557.52177 | 0.41496 | 0.41496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8176.66956 | 8176.66956 | 0.47745 | 0.47745 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77777.92418 | 77777.92418 | 4.54163 | 4.54163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7931.34969 | 7931.34969 | 0.46313 | 0.46313 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371299.30296 | 371299.30296 | 21.68043 | 21.68043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 141483.41 | 9.31115 | 9.31115 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 18104.43 | 1.69395 | 1.69395 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1307904.75 | 86.24584 | 86.24584 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 285130.34 | 26.67840 | 26.67840 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 150163.11 | 9.33086 | 9.33086 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 32059.03 | 4.24205 | 4.24205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 |
7 | CAV_BAS | Cooling | Sensible | 76329.63 | 5.62609 | 5.62609 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51592.61 | 1.20016 | 1.20016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366827.56 | 21.68069 | 21.68069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.91 | 0.33839 | 0.33839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8089.27 | 0.47745 | 0.47745 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76954.54 | 4.54163 | 4.54163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6720.07 | 0.15632 | 0.15632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7848.91 | 0.46313 | 0.46313 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.62609 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.92100 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32124 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.77630 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85663 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18604E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53559E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77630 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17552.69135 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53559E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 353.84848 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.72034 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34136 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.77182 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91028 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11614E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09344E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.77182 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 353599.38375 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09344E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8033.88418 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.47021 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34771 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.68482 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92723 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09574E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.95964E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.06286 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 68122.29390 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95964E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1799.57966 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88107 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27106 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26432 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72282 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40561E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.56957E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26432 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6366.36540 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.56957E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.83770 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94701 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16252 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28410 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43338 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34437E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.96380E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28410 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5673.92669 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96380E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 127.28467 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16417 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20515 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34925 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54706 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85720E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.94227E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34925 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9078.50276 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.94227E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 218.71405 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21320 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12686 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36396 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33829 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00334E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.33590E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36396 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4956.19805 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33590E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 103.78059 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.25222 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28940 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.48392 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77174 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31651E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39773E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.85240 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 159768.61090 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39773E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4214.86317 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.62579 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15989 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89736 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42637 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38291E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.35564E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.24827 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 106940.67072 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.35564E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2821.07749 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.17308 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21375 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.36310 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78245E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40474E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.87680 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160569.90271 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40474E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4235.97664 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.30138 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14940 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.10071 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39841 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55016E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.57352E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.10071 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 98000.54662 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.57352E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2539.11791 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95511 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25004 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29418 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66678 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52373E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.90442E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66161 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21768.65055 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.90442E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 574.09703 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96292 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15983 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29658 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42622 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38377E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26171E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43835 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14422.12269 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26171E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 380.33936 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24369 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19203 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38306 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51208 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98407E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91210E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66428 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21856.52257 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91210E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 576.41231 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11801 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13766 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34435 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36709 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76770E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.19449E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41496 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13653.72445 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19449E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 360.09080 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47745 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.54163 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46313 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.68043 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06323 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.03794 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.12645 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.03794 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.31115 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.31115 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32627 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 47.53641 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.61692 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 95.07282 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.61692 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.24584 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.24584 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33181 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.87498 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.00299 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.74995 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.24205 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.33086 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.33086 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45463 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.62609 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.62609 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62609 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.62609 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.62609 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.62609 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.68043 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.68043 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.68043 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.68043 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.68069 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.68069 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47745 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47745 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47745 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47745 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47745 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47745 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.54163 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.54163 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.54163 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.54163 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.54163 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.54163 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46313 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46313 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46313 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46313 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46313 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46313 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.31115 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.24584 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.33086 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.62609 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.68069 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47745 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.54163 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46313 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.31115 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.73523 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.25396 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90718 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66029E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 176854.47099 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.52380E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.31115 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 29592.91549 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58892E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 508.99113 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.31115 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.52380E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.32912E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.58892E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.24584 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 28.63723 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.62301 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90714 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64669E-003 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1673011.05238 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.11738E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 86.24584 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 276530.49726 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41921E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4753.75390 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.24584 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.11738E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.69053E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.41921E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.33086 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.00717 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.35191 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90709 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63159E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 177525.69110 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.55235E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.33086 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 29917.58998 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61732E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 514.30443 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.33086 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.55235E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.30519E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.61732E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.62609 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.27261 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.26784 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79872E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 93307.53408 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.96952E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.62609 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 261828.02781 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29059E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5929.35416 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.62609 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.96952E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.19962E-004 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.29059E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.68069 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.68069 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 427734.09707 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 304842.54544 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04752E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.68069 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.68069 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.68069 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.68069 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 427734.09707 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 427734.09707 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14546.90948 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.68069 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.68069 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 427734.09707 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04752E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14546.90948 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.49392E-005 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47745 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47745 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9238.26226 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6647.39520 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26244E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47745 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47745 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47745 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47745 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9238.26226 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9238.26226 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47745 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47745 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9238.26226 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26244E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.54163 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.54163 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 87938.87845 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 63251.64278 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15362E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.54163 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.54163 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.54163 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.54163 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 87938.87845 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 87938.87845 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6720.06953 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.54163 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.54163 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 87938.87845 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15362E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6720.06953 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46313 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46313 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 8965.04141 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6449.23822 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19553E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46313 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46313 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46313 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46313 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8965.04141 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8965.04141 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46313 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46313 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 8965.04141 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19553E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.02194E-002 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18590.88009 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.02194E-002 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.82633 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.02194E-002 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.02194E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 378696.20510 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.45241E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.74290 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.45241E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4374.03506 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1660199.14366 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1660199.14000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.45241E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.02194E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.82633 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.02194E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12871.09340 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.02194E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.53652E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1068974.30771 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1074044.39000 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.33536E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.02194E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.53652E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1068974.30771 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1074044.39000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.33536E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30746E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.56895 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30746E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3334.67574 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30746E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60190.46691 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21503.61655 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 538561.25436 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 527854.83000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30746E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10671 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.80487 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10671 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32137.89267 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 44.05221 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1275205.56141 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.81044 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 159400.69518 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 44.05221 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1275205.56141 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.81044 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 159400.69518 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.52075E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.52075E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16643.60 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 335082.40 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 64563.42 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6031.64 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5377.08 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8600.34 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4698.70 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 151383.62 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 101327.33 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 152142.68 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 92805.72 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20624.96 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13664.34 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20708.20 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12936.42 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 24861.72 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 232085.64 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 25109.14 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 211800.41 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 219921.55 | 153949.18 | 65972.37 | 0.70 | 22910.40 | 232.37 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2054186.91 | 1433613.99 | 620572.92 | 0.70 | 213382.00 | 2164.24 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 220451.68 | 154294.20 | 66157.47 | 0.70 | 22946.39 | 232.73 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 123829.61 | 88770.95 | 35058.66 | 0.72 | 12896.63 | 130.80 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_NORTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_EAST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | N/A | 2.640 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4644_SHGC_WEST_0.25 | N/A | 2.640 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.388 | 1.149 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.309 | 1.094 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.748 | 1.385 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3091734169 | 0.2656494879 | Pass | Pass | 0.8447240822 | 0.9851338063 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.5622810398E-003 | 2.6688360018E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7203470910E-003 | 2.6645872633E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.3596102935E-002 | 9.3545346750E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1039210835E-002 | 2.0230751733E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1077637861E-002 | 8.9220003143E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.9907396126E-002 | 7.2766728148E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.1932811091E-002 | 2.9229461117E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3538727568E-002 | 2.3985417690E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.3379478374E-002 | 9.2585238934E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.2873764344E-002 | 7.3619362402E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4435885867E-002 | 2.9994379283E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7742444964E-002 | 2.2836681283E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.3274078173E-002 | 8.7233910072E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.4945408143E-002 | 7.1142444996E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9256047803E-002 | 2.9483582891E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4397604304E-003 | 7.1066306362E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.6334810489E-003 | 9.7566927042E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6984944850E-002 | 3.6441798008E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1272292433E-006 | 6.8816733353E-006 | Pass | Pass | 2.1010461199E-003 | 1.7972698879E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2892534564E-006 | 5.5775863515E-006 | Pass | Pass | 1.3121583206E-002 | 9.0869000263E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2773944850E-002 | 9.6092523934E-003 | Pass | Pass | 4.9712676852E-003 | 3.3924486115E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1364154984E-006 | 7.2241775705E-006 | Pass | Pass | 4.1534688369E-005 | 1.0451346325E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6714.24 | 142.04 | 0.00 | 21545.59 | 21414.56 | 49816.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.149 | 1.388 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.094 | 1.309 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.385 | 1.748 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.4644_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.4644_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.640 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.640 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4644_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4644_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4644_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4644_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.640 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.640 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.640 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1390 | 2779.43 | 25401.24 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 235.63 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.1390 | 24961.20 | 228120.99 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 2116.09 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.1390 | 3134.13 | 28642.87 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.1390 | 3134.20 | 28643.49 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.1390 | 783.68 | 7162.06 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 66.44 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 11.7111 | 362.03 | 4239.75 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 43.70 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
Interior Lighting Total | 9.1631 | 46320.38 | 424440.34 | 1212.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 57580.60 | AstronomicalClock | - | 83.75 | 83.75 | 905.27 | |
Exterior Lighting Total | 57580.60 | 905.27 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2115821.77 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1660199.14 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1074044.39 | 6.11 | 1027277.87 | 5.82 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1074044.39 | 6.11 | 1027277.87 | 5.82 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 527854.83 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1275205.56 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1275205.56 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 176854.47 | 219921.55 | 153949.18 | 65972.37 | 0.70 | - | 22910.40 | 232.37 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1673011.05 | 2054186.91 | 1433613.99 | 620572.92 | 0.70 | - | 213382.00 | 2164.24 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 177525.69 | 220451.68 | 154294.20 | 66157.47 | 0.70 | - | 22946.39 | 232.73 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 93307.53 | 123829.61 | 88770.95 | 35058.66 | 0.72 | - | 12896.63 | 130.80 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 427734.10 | 304842.55 | 122891.55 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9238.26 | 6647.40 | 2590.87 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 87938.88 | 63251.64 | 24687.24 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8965.04 | 6449.24 | 2515.80 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17552.69 | 16643.60 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 353599.38 | 335082.40 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 68122.29 | 64563.42 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6366.37 | 6031.64 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5673.93 | 5377.08 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9078.50 | 8600.34 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4956.20 | 4698.70 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 159768.61 | 151383.62 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 106940.67 | 101327.33 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 160569.90 | 152142.68 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 98000.55 | 92805.72 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21768.65 | 20624.96 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14422.12 | 13664.34 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21856.52 | 20708.20 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13653.72 | 12936.42 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 29592.92 | 24861.72 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 276530.50 | 232085.64 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 29917.59 | 25109.14 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 261828.03 | 211800.41 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 427734.10 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9238.26 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 87938.88 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 8965.04 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14546.91 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6720.07 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.31 | 21264.14 | 2283.73 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 86.25 | 196962.03 | 2283.73 | 1.00 | 1.07 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.33 | 21309.15 | 2283.73 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.63 | 10402.93 | 1849.05 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.68 | 35756.81 | 1649.25 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 534.80 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.54 | 5087.11 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 518.75 | 1120.11 | 1.00 | 1.64 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.090219 | 18590.88 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014524 | 4374.04 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.090219 | 12871.09 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013075 | 3334.68 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.106707 | 32137.89 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76688.94 | 76688.94 | 27.59 | 5.626 | 5.626 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 80713.56 | 80713.56 | 32.34 | 5.921 | 5.921 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 759760.97 | 759760.97 | 304.38 | 55.720 | 55.720 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 73889.27 | 73889.27 | 29.60 | 5.470 | 5.470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00891 | 31.30 | 0.00823 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11901.43 | 11901.43 | 37.97 | 0.881 | 0.881 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00879 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12884.85 | 12884.85 | 63.79 | 0.947 | 0.947 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00868 | 24.71 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15725.44 | 15725.44 | 50.17 | 1.164 | 1.164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00873 | 30.86 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16387.89 | 16387.89 | 81.14 | 1.213 | 1.213 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111471.07 | 111471.07 | 355.67 | 8.252 | 8.252 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00878 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 130026.18 | 130026.18 | 643.77 | 9.626 | 9.626 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00866 | 25.28 | 0.00822 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 150926.19 | 150926.19 | 481.55 | 11.173 | 11.173 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00871 | 30.93 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 139151.48 | 139151.48 | 688.95 | 10.301 | 10.301 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12901.75 | 12901.75 | 41.17 | 0.955 | 0.955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00873 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13007.29 | 13007.29 | 64.40 | 0.963 | 0.963 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00865 | 26.91 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16799.90 | 16799.90 | 53.60 | 1.244 | 1.244 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00868 | 31.15 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15102.23 | 15102.23 | 74.77 | 1.118 | 1.118 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00863 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8176.67 | 8176.67 | 225.86 | 0.477 | 0.477 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77777.92 | 77777.92 | 2148.40 | 4.542 | 4.542 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7931.35 | 7931.35 | 219.08 | 0.463 | 0.463 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 27.00 | 27.00 | 0.00859 | 29.16 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371299.30 | 371299.30 | 473.79 | 21.680 | 21.680 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.79 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.59 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 187866.91 | 187866.91 | 75.26 | 8.024 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 47737.96 | 47737.96 | 19.12 | 2.063 | 2.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3761.33 | 3761.33 | 12.00 | 0.162 | 0.162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00667 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2873.22 | 2873.22 | 14.23 | 0.124 | 0.124 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00682 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 5633.97 | 5633.97 | 17.98 | 0.243 | 0.243 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00707 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1372.68 | 1372.68 | 6.80 | 0.059 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00610 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111877.17 | 111877.17 | 356.96 | 4.852 | 4.852 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74880.49 | 74880.49 | 370.74 | 3.248 | 3.248 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 112437.31 | 112437.31 | 358.74 | 4.877 | 4.877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 67401.93 | 67401.93 | 333.71 | 2.923 | 2.923 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15237.30 | 15237.30 | 48.62 | 0.662 | 0.662 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10094.74 | 10094.74 | 49.98 | 0.438 | 0.438 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15298.73 | 15298.73 | 48.81 | 0.664 | 0.664 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9557.52 | 9557.52 | 47.32 | 0.415 | 0.415 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.89 | 0.00766 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.76 | 0.00525 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.31 | 9.31 | 1.69 | 1.69 | 9.3112 | 3.0379 | 9.3112 | 0.3263 | 0.3000 |
VAV_MID WITH REHEAT | 86.25 | 86.25 | 26.68 | 26.68 | 86.2458 | 28.6169 | 86.2458 | 0.3318 | 0.3000 |
VAV_TOP WITH REHEAT | 9.33 | 9.33 | 4.24 | 4.24 | 9.3309 | 4.2421 | 9.3309 | 0.4546 | 0.3000 |
CAV_BAS | 5.63 | 5.63 | 1.20 | 1.20 | 5.6261 | 5.6261 | 5.6261 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.68 | 21.68 | 0.34 | 0.34 | 21.6807 | 21.6804 | 21.6807 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4775 | 0.4775 | 0.4775 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.54 | 4.54 | 0.16 | 0.16 | 4.5416 | 4.5416 | 4.5416 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4631 | 0.4631 | 0.4631 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17552.691 | 17552.691 | 1.776300 | 0.00015356 | 353.848 | 12/21 00:10:00 | 12/21 00:10:00 | 17552.69 | 17552.69 | 1.776300 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 17617.41 | 17617.41 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 353599.384 | 353599.384 | 16.771823 | 0.00309344 | 8033.884 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353599.38 | 353599.38 | 16.771823 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 187866.91 | 0.00 | 354803.32 | 354803.32 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 68122.294 | 68122.294 | 2.062858 | 0.00059596 | 1799.580 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 68122.29 | 68122.29 | 2.062858 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 47737.96 | 0.00 | 68367.44 | 68367.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6366.365 | 6366.365 | 0.264322 | 0.00005570 | 149.838 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6366.37 | 6366.37 | 0.264322 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00667187 | 42.4236 | 3761.33 | 0.00 | 6387.21 | 6387.21 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5673.927 | 5673.927 | 0.284102 | 0.00004964 | 127.285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5673.93 | 5673.93 | 0.284102 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00682198 | 43.3680 | 2873.22 | 0.00 | 5693.35 | 5693.35 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9078.503 | 9078.503 | 0.349250 | 0.00007942 | 218.714 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9078.50 | 9078.50 | 0.349250 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00706926 | 44.9221 | 5633.97 | 0.00 | 9107.90 | 9107.90 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4956.198 | 4956.198 | 0.363961 | 0.00004336 | 103.781 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4956.20 | 4956.20 | 0.363961 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00610385 | 38.8457 | 1372.68 | 0.00 | 4974.14 | 4974.14 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 159768.611 | 159768.611 | 4.852403 | 0.00139773 | 4214.863 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 159768.61 | 159768.61 | 4.852403 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00745838 | 47.3656 | 111877.17 | 0.00 | 160302.47 | 160302.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 106940.671 | 106940.671 | 3.248268 | 0.00093556 | 2821.077 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 106940.67 | 106940.67 | 3.248268 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00747416 | 47.4646 | 74880.49 | 0.00 | 107297.07 | 107297.07 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 160569.903 | 160569.903 | 4.876803 | 0.00140474 | 4235.977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 160569.90 | 160569.90 | 4.876803 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00746190 | 47.3877 | 112437.31 | 0.00 | 161106.25 | 161106.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 98000.547 | 98000.547 | 3.100715 | 0.00085735 | 2539.118 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 98000.55 | 98000.55 | 3.100715 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00739015 | 46.9377 | 67401.93 | 0.00 | 98300.90 | 98300.90 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21768.651 | 21768.651 | 0.661605 | 0.00019044 | 574.097 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21768.65 | 21768.65 | 0.661605 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758235 | 48.1432 | 15237.30 | 0.00 | 21840.07 | 21840.07 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14422.123 | 14422.123 | 0.438351 | 0.00012617 | 380.339 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14422.12 | 14422.12 | 0.438351 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758310 | 48.1479 | 10094.74 | 0.00 | 14469.37 | 14469.37 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21856.523 | 21856.523 | 0.664281 | 0.00019121 | 576.412 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21856.52 | 21856.52 | 0.664281 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758418 | 48.1546 | 15298.73 | 0.00 | 21928.22 | 21928.22 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13653.724 | 13653.724 | 0.414957 | 0.00011945 | 360.091 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13653.72 | 13653.72 | 0.414957 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755511 | 47.9725 | 9557.52 | 0.00 | 13698.56 | 13698.56 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 176854.471 | -999.000 | 9.311152 | 0.00752380 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 176854.47 | 172237.73 | 9.311152 | 26.25 | 17.11 | 0.00866029 | 10.91 | 10.91 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 29.3758 | 24.00 | 0.00885103 | 46.7373 | 119617.85 | 0.00 | 179389.26 | 162355.13 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 29592.915 | 29592.915 | 2.793346 | 0.00025889 | 508.991 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29592.92 | 29592.92 | 2.793346 | 3.88 | 3.86 | 0.00507145 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 97.9195 | 21.77 | 0.00592028 | 35.9405 | 13641.19 | 0.00 | 30095.93 | 30095.93 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1673011.052 | -999.000 | 86.245844 | 0.07117376 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1673011.05 | 1633887.94 | 86.245844 | 26.62 | 17.23 | 0.00864669 | 10.91 | 10.91 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 33.2042 | 24.00 | 0.00887852 | 46.8803 | 1076255.13 | 0.00 | 1696701.53 | 1541546.93 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 276530.497 | 276530.497 | 25.873753 | 0.00241921 | 4753.754 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 276530.50 | 276530.50 | 25.873753 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 110.6806 | 21.00 | 0.00763456 | 48.4691 | 554463.80 | 0.00 | 280946.59 | 280946.59 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 177525.691 | -999.000 | 9.330862 | 0.00755235 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 177525.69 | 173727.40 | 9.330862 | 26.35 | 17.12 | 0.00863159 | 10.91 | 10.91 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 32.2282 | 24.00 | 0.00882090 | 46.5802 | 126039.27 | 0.00 | 180066.64 | 163716.77 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 29917.590 | 29917.590 | 2.799258 | 0.00026173 | 514.304 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29917.59 | 29917.59 | 2.799258 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 107.4274 | 21.00 | 0.00773405 | 49.0919 | 69046.25 | 0.00 | 30395.36 | 30395.36 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 93307.534 | -999.000 | 5.626089 | 0.00396952 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 93307.53 | 88233.29 | 5.626089 | 24.27 | 16.55 | 0.00879872 | 11.27 | 11.27 | 0.00850000 | 25.28 | 0.00822398 | 16.41 | 21.3320 | 24.00 | 0.00895540 | 47.2810 | 75676.93 | 0.00 | 94760.38 | 83542.33 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 261828.028 | 261828.028 | 5.626089 | 0.00229059 | 5929.354 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 261828.03 | 261828.03 | 5.626089 | 0.81 | 0.81 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.3320 | 24.79 | 0.00505843 | 25.6219 | 0.00 | 0.00 | 224042.41 | 224042.41 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 427734.097 | 304842.545 | 21.680690 | 0.01047518 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 397442.20 | 395281.97 | -999.0 | 28.48 | 17.77 | 0.00853750 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | -999.0000 | 27.00 | 0.00854232 | 37.7673 | 370832.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9238.262 | 6647.395 | 0.477450 | 0.00022624 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8556.19 | 8459.06 | -999.0 | 28.03 | 17.65 | 0.00857674 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00858847 | 37.9663 | 8175.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87938.878 | 63251.643 | 4.541627 | 0.00215362 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 81455.71 | 80486.31 | -999.0 | 28.04 | 17.65 | 0.00858051 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859301 | 37.9863 | 77754.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8965.041 | 6449.238 | 0.463128 | 0.00021955 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 8303.74 | 8206.64 | -999.0 | 28.04 | 17.65 | 0.00857908 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859128 | 37.9786 | 7931.35 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 427734.097 | 427734.097 | 21.680690 | 0.01047518 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 427734.10 | 427734.10 | 21.680690 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5608 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9238.262 | 9238.262 | 0.477450 | 0.00022624 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9238.26 | 9238.26 | 0.477450 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2741 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87938.878 | 87938.878 | 4.541627 | 0.00215362 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 87938.88 | 87938.88 | 4.541627 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4420 | 24.89 | 0.00765726 | 38.3989 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8965.041 | 8965.041 | 0.463128 | 0.00021955 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8965.04 | 8965.04 | 0.463128 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3754 | 23.76 | 0.00525367 | 28.2990 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.91 | 14546.91 | 21.680690 | 0.06 | 0.06 | 0.00844628 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.5608 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.477450 | 0.12 | 0.12 | 0.00838732 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2741 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6720.07 | 6720.07 | 4.541627 | 0.13 | 0.13 | 0.00756781 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4420 | 24.89 | 0.00765726 | 38.3989 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.463128 | 0.13 | 0.13 | 0.00524708 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3754 | 23.76 | 0.00525367 | 28.2990 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17552.691 | 17552.691 | 1.776300 | 0.00015356 | 353.848 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 1.0364 | 1.057264 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 17552.69 | 17552.69 | 1.0000 | 2.09919365 | 1.776300 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.15354294 | 60.00 | 32.22 | 27.78 | 0.000 | 17552.69 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 17617.41 | 17617.41 | 2.09919365 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 353599.384 | 353599.384 | 16.771823 | 0.00309344 | 8033.884 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 20.8784 | 21.298613 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 353599.38 | 353599.38 | 1.0000 | 19.82058211 | 16.771823 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 3.09312610 | 60.00 | 32.22 | 27.78 | 0.000 | 353599.38 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 187866.91 | 0.00 | 354803.32 | 354803.32 | 19.82058211 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.35 | 18.16 | 0.00800000 | 50960.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 68122.294 | 68122.294 | 2.062858 | 0.00059596 | 1799.580 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 4.0223 | 4.103260 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 68122.29 | 68122.29 | 1.0000 | 2.43784106 | 2.062858 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.59590275 | 60.00 | 32.22 | 27.78 | 0.000 | 68122.29 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 47737.96 | 0.00 | 68367.44 | 68367.44 | 2.43784106 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61104.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6366.365 | 6366.365 | 0.264322 | 0.00005570 | 149.838 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.3759 | 0.383470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6366.37 | 6366.37 | 1.0000 | 0.31237033 | 0.264322 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05569006 | 60.00 | 32.22 | 27.78 | 0.000 | 6366.37 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00667187 | 21.00 | 0.00667187 | 42.4236 | 3761.33 | 0.00 | 6387.21 | 6387.21 | 0.31237033 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.85 | 18.97 | 0.00800000 | 53507.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5673.927 | 5673.927 | 0.284102 | 0.00004964 | 127.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.3350 | 0.341762 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5673.93 | 5673.93 | 1.0000 | 0.33574579 | 0.284102 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04963292 | 60.00 | 32.22 | 27.78 | 0.000 | 5673.93 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00682198 | 21.00 | 0.00682198 | 43.3680 | 2873.22 | 0.00 | 5693.35 | 5693.35 | 0.33574579 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.43 | 17.85 | 0.00800000 | 50017.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9078.503 | 9078.503 | 0.349250 | 0.00007942 | 218.714 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.5360 | 0.546832 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9078.50 | 9078.50 | 1.0000 | 0.41273625 | 0.349250 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07941460 | 60.00 | 32.22 | 27.78 | 0.000 | 9078.50 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00706926 | 21.00 | 0.00706926 | 44.9221 | 5633.97 | 0.00 | 9107.90 | 9107.90 | 0.41273625 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.44 | 19.48 | 0.00800000 | 55126.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4956.198 | 4956.198 | 0.363961 | 0.00004336 | 103.781 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.2926 | 0.298530 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4956.20 | 4956.20 | 1.0000 | 0.43012081 | 0.363961 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04335456 | 60.00 | 32.22 | 27.78 | 0.000 | 4956.20 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00610385 | 21.00 | 0.00610385 | 38.8457 | 1372.68 | 0.00 | 4974.14 | 4974.14 | 0.43012081 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.14 | 16.01 | 0.00800000 | 44624.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 159768.611 | 159768.611 | 4.852403 | 0.00139773 | 4214.863 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 9.4336 | 9.623461 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 159768.61 | 159768.61 | 1.0000 | 5.73446637 | 4.852403 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.39758292 | 60.00 | 32.22 | 27.78 | 0.000 | 159768.61 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00745838 | 21.00 | 0.00745838 | 47.3656 | 111877.17 | 0.00 | 160302.47 | 160302.47 | 5.73446637 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 106940.671 | 106940.671 | 3.248268 | 0.00093556 | 2821.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 6.3144 | 6.441436 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 106940.67 | 106940.67 | 1.0000 | 3.83873339 | 3.248268 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.93546820 | 60.00 | 32.22 | 27.78 | 0.000 | 106940.67 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00747416 | 21.00 | 0.00747416 | 47.4646 | 74880.49 | 0.00 | 107297.07 | 107297.07 | 3.83873339 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160569.903 | 160569.903 | 4.876803 | 0.00140474 | 4235.977 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 9.4809 | 9.671725 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 160569.90 | 160569.90 | 1.0000 | 5.76330223 | 4.876803 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.40459226 | 60.00 | 32.22 | 27.78 | 0.000 | 160569.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00746190 | 21.00 | 0.00746190 | 47.3877 | 112437.31 | 0.00 | 161106.25 | 161106.25 | 5.76330223 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 98000.547 | 98000.547 | 3.100715 | 0.00085735 | 2539.118 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 5.7865 | 5.902939 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 98000.55 | 98000.55 | 1.0000 | 3.66435844 | 3.100715 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.85726407 | 60.00 | 32.22 | 27.78 | 0.000 | 98000.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00739015 | 21.00 | 0.00739015 | 46.9377 | 67401.93 | 0.00 | 98300.90 | 98300.90 | 3.66435844 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.11 | 20.92 | 0.00800000 | 59886.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21768.651 | 21768.651 | 0.661605 | 0.00019044 | 574.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 1.2853 | 1.311207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21768.65 | 21768.65 | 1.0000 | 0.78187116 | 0.661605 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.19042222 | 60.00 | 32.22 | 27.78 | 0.000 | 21768.65 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00758235 | 21.00 | 0.00758235 | 48.1432 | 15237.30 | 0.00 | 21840.07 | 21840.07 | 0.78187116 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14422.123 | 14422.123 | 0.438351 | 0.00012617 | 380.339 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.8516 | 0.868698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14422.12 | 14422.12 | 1.0000 | 0.51803426 | 0.438351 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.12615815 | 60.00 | 32.22 | 27.78 | 0.000 | 14422.12 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00758310 | 21.00 | 0.00758310 | 48.1479 | 10094.74 | 0.00 | 14469.37 | 14469.37 | 0.51803426 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21856.523 | 21856.523 | 0.664281 | 0.00019121 | 576.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 1.2905 | 1.316500 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21856.52 | 21856.52 | 1.0000 | 0.78503367 | 0.664281 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.19119089 | 60.00 | 32.22 | 27.78 | 0.000 | 21856.52 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00758418 | 21.00 | 0.00758418 | 48.1546 | 15298.73 | 0.00 | 21928.22 | 21928.22 | 0.78503367 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13653.724 | 13653.724 | 0.414957 | 0.00011945 | 360.091 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 0.8062 | 0.822415 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13653.72 | 13653.72 | 1.0000 | 0.49038741 | 0.414957 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.11943655 | 60.00 | 32.22 | 27.78 | 0.000 | 13653.72 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00755511 | 21.00 | 0.00755511 | 47.9725 | 9557.52 | 0.00 | 13698.56 | 13698.56 | 0.49038741 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 176854.471 | -999.000 | 9.311152 | 0.00752380 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9390 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.311152 | 11.00372113 | 4197.9300 | 999.8980 | 90.21022387 | 12.27 | 6.67 | 5.60 | 2120698.75 | 8.3394 | 8.339443 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 176854.47 | 172237.73 | 1.0000 | 11.00372113 | 9.311152 | 26.25 | 17.11 | 0.00866029 | 48462.6 | 10.91 | 10.91 | 0.00850000 | 32390.3 | 7.52303053 | 6.67 | 12.27 | 5.60 | 21264.137 | 155590.33 | 31.30 | 0.00823349 | 18.45 | 2.73523000 | 29.3758 | 24.00 | 0.00885103 | 24.00 | 0.00885103 | 46.7373 | 119617.85 | 0.00 | 179389.26 | 162355.13 | 11.00372113 | 26.25 | 17.31 | 0.00866029 | 48462.6 | 11.80 | 11.22 | 0.00804669 | 32160.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29592.915 | 29592.915 | 2.793346 | 0.00025889 | 508.991 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.311152 | 11.00372113 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 1.7473 | 1.782492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29592.92 | 29592.92 | 1.0000 | 3.30111634 | 2.793346 | 3.88 | 3.86 | 0.00507145 | 16617.6 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.25886532 | 60.00 | 32.22 | 27.78 | 0.000 | 29592.92 | 3.80 | 0.00505843 | 3.80 | 2.73523000 | 97.9195 | 7.59 | 0.00568408 | 21.77 | 0.00592028 | 35.9405 | 13641.19 | 0.00 | 30095.93 | 30095.93 | 3.30111634 | 2.80 | 2.80 | 0.00507145 | 15523.3 | 11.79 | 7.96 | 0.00507145 | 24640.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1673011.052 | -999.000 | 86.245844 | 0.07117376 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9138 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.245844 | 101.92349825 | 4197.9300 | 999.8980 | 90.21022387 | 12.27 | 6.67 | 5.60 | 2120698.75 | 78.8896 | 78.889614 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1673011.05 | 1633887.94 | 1.0000 | 101.92349825 | 86.245844 | 26.62 | 17.23 | 0.00864669 | 48804.6 | 10.91 | 10.91 | 0.00850000 | 32390.3 | 71.16649721 | 6.67 | 12.27 | 5.60 | 196962.032 | 1476049.02 | 31.30 | 0.00823349 | 18.45 | 28.63723000 | 33.2042 | 24.00 | 0.00887852 | 24.00 | 0.00887852 | 46.8803 | 1076255.13 | 0.00 | 1696701.53 | 1541546.93 | 101.92349825 | 26.62 | 17.43 | 0.00864669 | 48804.6 | 11.81 | 11.22 | 0.00804330 | 32157.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 276530.497 | 276530.497 | 25.873753 | 0.00241921 | 4753.754 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.245844 | 101.92349825 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 16.3279 | 16.656465 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 276530.50 | 276530.50 | 1.0000 | 30.57704947 | 25.873753 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 2.41896264 | 60.00 | 32.22 | 27.78 | 0.000 | 276530.50 | 3.80 | 0.00505843 | 3.80 | 28.63723000 | 110.6806 | 20.79 | 0.00767229 | 21.00 | 0.00763456 | 48.4691 | 554463.80 | 0.00 | 280946.59 | 280946.59 | 30.57704947 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.86 | 7.98 | 0.00505843 | 24678.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 177525.691 | -999.000 | 9.330862 | 0.00755235 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8857 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.330862 | 11.02701315 | 4197.9300 | 999.8980 | 90.21022387 | 12.27 | 6.67 | 5.60 | 2120698.75 | 8.3711 | 8.371094 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 177525.69 | 173727.40 | 1.0000 | 11.02701315 | 9.330862 | 26.35 | 17.12 | 0.00863159 | 48489.4 | 10.91 | 10.91 | 0.00850000 | 32390.2 | 7.55158287 | 6.67 | 12.27 | 5.60 | 21309.148 | 156216.54 | 31.30 | 0.00823349 | 18.45 | 3.00717000 | 32.2282 | 24.00 | 0.00882090 | 24.00 | 0.00882090 | 46.5802 | 126039.27 | 0.00 | 180066.64 | 163716.77 | 11.02701315 | 26.35 | 17.32 | 0.00863159 | 48489.4 | 11.81 | 11.22 | 0.00804389 | 32159.8 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29917.590 | 29917.590 | 2.799258 | 0.00026173 | 514.304 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.330862 | 11.02701315 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 1.7665 | 1.802048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29917.59 | 29917.59 | 1.0000 | 3.30810395 | 2.799258 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.26170543 | 60.00 | 32.22 | 27.78 | 0.000 | 29917.59 | 3.80 | 0.00505843 | 3.80 | 3.00717000 | 107.4274 | 21.00 | 0.00773405 | 21.00 | 0.00773405 | 49.0919 | 69046.25 | 0.00 | 30395.36 | 30395.36 | 3.30810395 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.86 | 7.98 | 0.00505843 | 24678.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 93307.534 | -999.000 | 5.626089 | 0.00396952 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1964 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.626089 | 6.64879192 | 4197.9300 | 999.8980 | 90.21022387 | 12.27 | 6.67 | 5.60 | 2120698.75 | 4.3998 | 4.399849 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 93307.53 | 88233.29 | 1.0000 | 6.64879192 | 5.626089 | 24.27 | 16.55 | 0.00879872 | 46792.2 | 11.27 | 11.27 | 0.00850000 | 32758.4 | 3.96911327 | 6.67 | 12.27 | 5.60 | 10402.925 | 82904.61 | 25.28 | 0.00822398 | 16.41 | 1.20015641 | 21.3320 | 24.00 | 0.00895540 | 24.00 | 0.00895540 | 47.2810 | 75676.93 | 0.00 | 94760.38 | 83542.33 | 6.64879192 | 24.27 | 16.74 | 0.00879872 | 46792.2 | 11.97 | 11.38 | 0.00813003 | 32539.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 261828.028 | 261828.028 | 5.626089 | 0.00229059 | 5929.354 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 5.626089 | 6.64879192 | 4197.9300 | 999.8980 | 14.52266474 | 54.44 | 82.22 | 27.78 | 1693611.31 | 15.4597 | 15.770881 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 261828.03 | 261828.03 | 1.0000 | 6.64879192 | 5.626089 | 0.81 | 0.81 | 0.00505843 | 13473.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 2.29035214 | 60.00 | 32.22 | 27.78 | 0.000 | 261828.03 | 3.80 | 0.00505843 | 3.80 | 1.20015641 | 21.3320 | 0.00 | 0.00505843 | 24.79 | 0.00505843 | 25.6219 | 0.00 | 0.00 | 224042.41 | 224042.41 | 6.64879192 | 12.80 | 8.42 | 0.00505843 | 25633.1 | 46.02 | 20.83 | 0.00505843 | 59329.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 427734.097 | 304842.545 | 21.680690 | 0.01047518 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7108 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 397442.20 | 395281.97 | 0.9292 | -999.0 | -999.0 | 28.48 | 17.77 | 0.00853750 | 50425.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 397442.20 | 31.30 | 0.00823349 | 18.45 | 0.33839277 | -999.0000 | 27.00 | 0.00854232 | 27.00 | 0.00854232 | 37.7673 | 370832.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9238.262 | 6647.395 | 0.477450 | 0.00022624 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7837 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8556.19 | 8459.06 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857674 | 50065.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8556.19 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858847 | 27.00 | 0.00858847 | 37.9663 | 8175.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 87938.878 | 63251.643 | 4.541627 | 0.00215362 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7907 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 81455.71 | 80486.31 | 0.9263 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00858051 | 50079.1 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81455.71 | 29.16 | 0.00823009 | 17.74 | 0.15632344 | -999.0000 | 27.00 | 0.00859301 | 27.00 | 0.00859301 | 37.9863 | 77754.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8965.041 | 6449.238 | 0.463128 | 0.00021955 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7881 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 8303.74 | 8206.64 | 0.9262 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00857908 | 50074.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8303.74 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | -999.0000 | 27.00 | 0.00859128 | 27.00 | 0.00859128 | 37.9786 | 7931.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 427734.097 | 427734.097 | 21.680690 | 0.01047518 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 427734.10 | 427734.10 | 1.0000 | 25.62177724 | 21.680690 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 427734.10 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.5608 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9238.262 | 9238.262 | 0.477450 | 0.00022624 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9238.26 | 9238.26 | 1.0000 | 0.56424049 | 0.477450 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9238.26 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2741 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87938.878 | 87938.878 | 4.541627 | 0.00215362 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 87938.88 | 87938.88 | 1.0000 | 5.36719769 | 4.541627 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87938.88 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4420 | 0.00 | 0.00765726 | 24.89 | 0.00765726 | 38.3989 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8965.041 | 8965.041 | 0.463128 | 0.00021955 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8965.04 | 8965.04 | 1.0000 | 0.54731423 | 0.463128 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8965.04 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3754 | 0.00 | 0.00525367 | 23.76 | 0.00525367 | 28.2990 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.680690 | 25.62177724 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14546.91 | 14546.91 | 1.0000 | 25.62177724 | 21.680690 | 0.06 | 0.06 | 0.00844628 | 21184.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.91 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.5608 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.477450 | 0.56424049 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.56424049 | 0.477450 | 0.12 | 0.12 | 0.00838732 | 21103.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2741 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.541627 | 5.36719769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6720.07 | 6720.07 | 1.0000 | 5.36719769 | 4.541627 | 0.13 | 0.13 | 0.00756781 | 19059.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6720.07 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.4420 | 0.00 | 0.00765726 | 24.89 | 0.00765726 | 38.3989 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.463128 | 0.54731423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.54731423 | 0.463128 | 0.13 | 0.13 | 0.00524708 | 13252.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3754 | 0.00 | 0.00525367 | 23.76 | 0.00525367 | 28.2990 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.74 | 9.31 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 28.64 | 86.25 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 3.01 | 9.33 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.63 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4357.00 | 401.67 | 284.33 |
CORE_BOTTOM | 4473.50 | 108.67 | 14.33 |
CORE_MID | 3553.17 | 646.50 | 20.83 |
CORE_TOP | 2700.83 | 2051.33 | 21.00 |
PERIMETER_BOT_ZN_3 | 2845.17 | 1643.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 2746.17 | 2012.83 | 39.33 |
PERIMETER_BOT_ZN_1 | 3639.67 | 1199.67 | 62.50 |
PERIMETER_BOT_ZN_4 | 4506.17 | 722.67 | 202.50 |
PERIMETER_MID_ZN_3 | 1910.83 | 3090.17 | 44.50 |
PERIMETER_MID_ZN_2 | 1698.17 | 2738.00 | 68.17 |
PERIMETER_MID_ZN_1 | 2965.00 | 1957.33 | 69.33 |
PERIMETER_MID_ZN_4 | 2476.00 | 2747.17 | 73.83 |
PERIMETER_TOP_ZN_3 | 1875.67 | 3865.50 | 422.67 |
PERIMETER_TOP_ZN_2 | 2107.17 | 3444.17 | 237.50 |
PERIMETER_TOP_ZN_1 | 2538.83 | 2738.17 | 168.33 |
PERIMETER_TOP_ZN_4 | 2241.33 | 3385.33 | 285.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1128.50 | 1128.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 35.33 | 35.33 |
DATACENTER_TOP_ZN_6 | 5910.50 | 198.17 | 187.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 70.33 | 0.00 | 5.17 |
CORE_BOTTOM | 0.00 | 3.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 5.17 | 0.00 | 5.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 22.00 | 0.00 | 22.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 72.83 | 0.00 | 35.33 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 3.83 | 0.00 | 3.83 |
PERIMETER_MID_ZN_1 | 0.00 | 23.17 | 0.00 | 23.17 |
PERIMETER_MID_ZN_4 | 0.00 | 10.50 | 0.00 | 8.83 |
PERIMETER_TOP_ZN_3 | 3.50 | 0.00 | 0.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 2.83 | 1.67 | 0.00 | 1.67 |
PERIMETER_TOP_ZN_1 | 1.50 | 10.33 | 0.00 | 10.17 |
PERIMETER_TOP_ZN_4 | 1.67 | 10.33 | 0.00 | 8.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 6.00 | 0.00 | 6.00 |
DATACENTER_MID_ZN_6 | 0.00 | 1.50 | 0.00 | 1.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 128.83 | 0.00 | 128.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.50 | 334.33 | 0.17 | 229.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.54 | 149.60 | 6779.02 | 1.952 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.16 | 134.35 | 6849.35 | 1.439 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.16 | 134.35 | 6849.35 | 1.144 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.16 | 134.35 | 6849.35 | 1.057 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.05 | 16.87 | 860.00 | 1.339 | 0.054 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 1.915 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.05 | 16.87 | 860.02 | 1.987 | 0.054 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 2.876 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.05 | 16.87 | 860.00 | 1.052 | 0.125 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 1.699 | 0.134 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.05 | 16.87 | 860.02 | 1.787 | 0.126 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 2.013 | 0.130 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.05 | 16.87 | 860.00 | 1.142 | 0.155 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 1.844 | 0.161 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.05 | 16.87 | 860.02 | 1.819 | 0.156 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 2.144 | 0.161 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.63 | 42.18 | 1911.37 | 0.482 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.54 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.16 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.05 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.05 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.63 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.54 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.16 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.97 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.05 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.05 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.63 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1036.48 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 80360299.67 | 0.00 | 80360299.67 | 0.00 | 80360299.67 | 37848132.68 | 3753.04 | 337.18 | 4669.78 | 466.23 |
CORE_BOTTOM | 61106585.33 | 0.00 | 61106585.33 | 0.00 | 61106585.33 | 33990283.35 | 3179.85 | 6.96 | 5573.19 | 629.55 |
CORE_MID | 0.47E+09 | 0.00 | 0.47E+09 | 0.00 | 0.47E+09 | 0.34E+09 | 3788.68 | 6.75 | 4964.57 | 181.53 |
CORE_TOP | 42390220.73 | 0.00 | 42390220.73 | 0.00 | 42390220.73 | 33990283.35 | 4010.04 | 3.47 | 4746.50 | 95.92 |
PERIMETER_BOT_ZN_3 | 7213368.56 | 0.00 | 7213368.56 | 464654.29 | 7678022.84 | 4267819.30 | 3149.59 | 3.54 | 5606.88 | 629.55 |
PERIMETER_BOT_ZN_2 | 6734345.99 | 0.00 | 6734345.99 | 309769.31 | 7044115.30 | 2750345.05 | 3132.36 | 0.00 | 5627.64 | 629.55 |
PERIMETER_BOT_ZN_1 | 10625120.58 | 0.00 | 10625120.58 | 464654.29 | 11089774.87 | 4267912.63 | 3132.36 | 0.00 | 5627.64 | 629.55 |
PERIMETER_BOT_ZN_4 | 9997389.76 | 0.00 | 9997389.76 | 309769.31 | 10307159.07 | 2750345.05 | 3132.36 | 0.00 | 5627.64 | 629.55 |
PERIMETER_MID_ZN_3 | 53991191.88 | 0.00 | 53991191.88 | 1089732.13 | 55080924.01 | 42678193.03 | 3758.51 | 5.44 | 4996.05 | 181.53 |
PERIMETER_MID_ZN_2 | 59970800.19 | 0.00 | 59970800.19 | 726487.59 | 60697287.78 | 27503450.52 | 3724.11 | 0.00 | 5035.89 | 1090.53 |
PERIMETER_MID_ZN_1 | 91266560.21 | 0.00 | 91266560.21 | 1089732.13 | 92356292.34 | 42679126.28 | 3725.69 | 0.17 | 5034.14 | 181.53 |
PERIMETER_MID_ZN_4 | 66652549.54 | 0.00 | 66652549.54 | 726487.59 | 67379037.13 | 27503450.52 | 3724.11 | 0.00 | 5035.89 | 181.53 |
PERIMETER_TOP_ZN_3 | 5782426.70 | 0.00 | 5782426.70 | 1353003.24 | 7135429.94 | 4267819.30 | 3946.86 | 1.59 | 4811.55 | 95.92 |
PERIMETER_TOP_ZN_2 | 6014641.27 | 0.00 | 6014641.27 | 902001.54 | 6916642.81 | 2750345.05 | 3876.57 | 0.67 | 4882.75 | 95.92 |
PERIMETER_TOP_ZN_1 | 9185207.59 | 0.00 | 9185207.59 | 1353003.24 | 10538210.83 | 4267912.63 | 3896.54 | 4.14 | 4859.32 | 95.92 |
PERIMETER_TOP_ZN_4 | 6994048.46 | 0.00 | 6994048.46 | 902001.54 | 7896050.00 | 2750345.05 | 3872.64 | 0.26 | 4887.10 | 95.92 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.77E+10 | 0.00 | 0.77E+10 | 42383251.12 | 0.77E+10 | 0.50E+10 | 4420.17 | 4377.21 | 5846.39 | 1739.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 3.5862 | 0.0000 | 3.5862 | 0.0000 | 3.5862 | 1.2002 | 1278.05 | 333.05 | 4331.90 |
CORE_BOTTOM | 2.6718 | 0.0000 | 2.6718 | 0.0000 | 2.6718 | 1.0778 | 954.90 | 1.76 | 4986.34 |
CORE_MID | 21.2339 | 0.0000 | 21.2339 | 0.0000 | 21.2339 | 10.7782 | 1141.30 | 4.99 | 4796.72 |
CORE_TOP | 1.9612 | 0.0000 | 1.9612 | 0.0000 | 1.9612 | 1.0778 | 1243.71 | 3.22 | 4696.08 |
PERIMETER_BOT_ZN_3 | 0.3122 | 0.0000 | 0.3122 | 0.0125 | 0.3247 | 0.1353 | 954.31 | 1.55 | 4987.13 |
PERIMETER_BOT_ZN_2 | 0.2880 | 0.0000 | 0.2880 | 0.0083 | 0.2963 | 0.0872 | 944.91 | 0.00 | 4998.09 |
PERIMETER_BOT_ZN_1 | 0.4637 | 0.0000 | 0.4637 | 0.0125 | 0.4762 | 0.1353 | 944.91 | 0.00 | 4998.09 |
PERIMETER_BOT_ZN_4 | 0.4320 | 0.0000 | 0.4320 | 0.0083 | 0.4404 | 0.0872 | 944.91 | 0.00 | 4998.09 |
PERIMETER_MID_ZN_3 | 2.4547 | 0.0000 | 2.4547 | 0.0293 | 2.4841 | 1.3533 | 1118.97 | 4.37 | 4819.65 |
PERIMETER_MID_ZN_2 | 2.5592 | 0.0000 | 2.5592 | 0.0202 | 2.5794 | 0.8721 | 1088.64 | 0.00 | 3945.36 |
PERIMETER_MID_ZN_1 | 4.1724 | 0.0000 | 4.1724 | 0.0293 | 4.2017 | 1.3533 | 1089.97 | 0.17 | 4852.86 |
PERIMETER_MID_ZN_4 | 3.0289 | 0.0000 | 3.0289 | 0.0196 | 3.0484 | 0.8721 | 1088.64 | 0.00 | 4854.36 |
PERIMETER_TOP_ZN_3 | 0.2669 | 0.0000 | 0.2669 | 0.0364 | 0.3033 | 0.1353 | 1190.91 | 1.03 | 4751.06 |
PERIMETER_TOP_ZN_2 | 0.2778 | 0.0000 | 0.2778 | 0.0243 | 0.3020 | 0.0872 | 1149.60 | 0.29 | 4793.11 |
PERIMETER_TOP_ZN_1 | 0.4250 | 0.0000 | 0.4250 | 0.0364 | 0.4614 | 0.1353 | 1158.35 | 2.19 | 4782.46 |
PERIMETER_TOP_ZN_4 | 0.3230 | 0.0000 | 0.3230 | 0.0243 | 0.3472 | 0.0872 | 1147.66 | 0.00 | 4795.34 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 346.9107 | 0.0000 | 346.9107 | 1.1472 | 348.0579 | 158.4706 | 1603.17 | 4359.99 | 5081.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.13E+09 | 0.00 | 0.13E+09 | 48026705.38 | 3132.36 | 0.00 | 5627.64 | 629.55 |
VAV_MID WITH REHEAT | 0.10E+10 | 0.00 | 0.10E+10 | 0.48E+09 | 3724.26 | 0.39 | 5035.36 | 181.53 |
VAV_TOP WITH REHEAT | 98273985.22 | 0.00 | 98273985.22 | 48026705.38 | 3901.75 | 4.22 | 4854.04 | 95.92 |
CAV_BAS | 0.11E+09 | 0.00 | 0.11E+09 | 37848132.68 | 3696.05 | 2.23 | 5061.72 | 466.23 |
AIRLOOP DATACENTER BASEMENT | 7385597.71 | 0.00 | 7385597.71 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3411840.17 | 0.00 | 3411840.17 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 5.8206 | 0.0000 | 5.8206 | 1.5229 | 944.91 | 0.00 | 4998.09 |
VAV_MID WITH REHEAT | 46.9435 | 0.0000 | 46.9435 | 15.2292 | 1088.64 | 0.29 | 4854.08 |
VAV_TOP WITH REHEAT | 4.5443 | 0.0000 | 4.5443 | 1.5229 | 1161.29 | 1.98 | 4779.73 |
CAV_BAS | 5.0086 | 0.0000 | 5.0086 | 1.2002 | 1270.44 | 0.85 | 4671.71 |
AIRLOOP DATACENTER BASEMENT | 0.3452 | 0.0000 | 0.3452 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1595 | 0.0000 | 0.1595 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 405.61 | 5222.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 507.39 | 3965.42 | 0.00 | 563.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 254.31 | 3261.10 | 0.00 | 1377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 332.67 | 4816.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.8258 | 7.1957 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 40.0255 | 62.4341 | 0.0000 | 39.9724 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 4.2049 | 6.3697 | 0.0000 | 4.1964 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6795 | 6.7145 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4727 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1335 |
Defaulted Fields | 1179 |
Fields with Defaults | 3690 |
Autosized Fields | 333 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
Electricity:Building | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 660.02 | 14600.60 | 01-JAN-00:10 | 34031.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 532.90 | 7069.41 | 01-JAN-00:10 | 36605.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5328.94 | 70693.84 | 01-JAN-00:10 | 366051.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 532.89 | 7069.38 | 01-JAN-00:10 | 36605.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 669.12 | 8876.66 | 01-JAN-00:10 | 45962.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 431.21 | 5720.45 | 01-JAN-00:10 | 29619.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 669.13 | 8876.80 | 01-JAN-00:10 | 45963.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 431.20 | 5720.42 | 01-JAN-00:10 | 29619.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7561.29 | 95230.42 | 01-JAN-00:10 | 385433.43 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1582.51 | 19698.04 | 01-JAN-00:10 | 81759.99 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2979.33 | 7150.42 | 08-JAN-07:00 | 442261.00 | 18-AUG-15:50 |
HeatRejection:Electricity | 1391.89 | 3759.54 | 08-JAN-07:00 | 82101.62 | 13-JAN-13:50 |
General:HeatRejection:Electricity | 1391.89 | 3759.54 | 08-JAN-07:00 | 82101.62 | 13-JAN-13:50 |
Electricity:HVAC | 5027.23 | 76595.14 | 01-JAN-06:50 | 368994.08 | 17-AUG-14:20 |
ExteriorEquipment:Electricity | 1997.59 | 30702.09 | 01-JAN-00:10 | 120520.01 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.51 | 1613.62 | 01-JAN-00:10 | 5474.05 | 03-APR-07:20 |
ElectricityPurchased:Facility | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
ElectricityPurchased:Plant | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
Cogeneration:ElectricityPurchased | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
ElectricityNet:Plant | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
Cogeneration:ElectricityNet | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
General:Cogeneration:ElectricityNet | 29977.77 | 382421.69 | 01-JAN-10:10 | 2015457.69 | 18-AUG-15:50 |
Fans:Electricity | 2462.16 | 41897.47 | 01-JAN-00:10 | 205774.29 | 31-JUL-15:00 |
General:Fans:Electricity | 2462.16 | 41897.47 | 01-JAN-00:10 | 205774.29 | 31-JUL-15:00 |
ExteriorLights:Electricity | 905.27 | 0.00 | 01-JAN-07:00 | 57580.60 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 905.27 | 0.00 | 01-JAN-07:00 | 57580.60 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Cooling:Electricity | 3391.36 | 30837.49 | 03-JAN-07:10 | 448084.30 | 18-AUG-15:50 |
General:Cooling:Electricity | 3391.36 | 30837.49 | 03-JAN-07:10 | 448084.30 | 18-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2.77 | 0.00 | 01-JAN-00:10 | 6835.20 | 19-DEC-10:40 |
General:Humidifier:Electricity | 2.77 | 0.00 | 01-JAN-00:10 | 6835.20 | 19-DEC-10:40 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 670.87 | 3334.68 | 01-JAN-00:10 | 67222.11 | 29-SEP-12:30 |
General:Pumps:Electricity | 670.87 | 3334.68 | 01-JAN-00:10 | 67222.11 | 29-SEP-12:30 |
WIRED_LTG_ELECTRICITY | 110.78 | 0.00 | 01-JAN-00:10 | 9672.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1211.02 | 8146.58 | 30-APR-16:00 | 783896.78 | 09-JAN-07:10 |
NaturalGas:Plant | 1211.02 | 8146.58 | 30-APR-16:00 | 783896.78 | 09-JAN-07:10 |
Heating:NaturalGas | 469.15 | 0.00 | 01-JAN-00:10 | 752660.69 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 469.15 | 0.00 | 01-JAN-00:10 | 752660.69 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 741.87 | 8146.58 | 02-JAN-05:10 | 78860.74 | 02-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 741.87 | 8146.58 | 02-JAN-05:10 | 78860.74 | 02-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 18453.81 | 152646.94 | 03-JAN-07:10 | 2669759.43 | 18-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 18453.81 | 152646.94 | 03-JAN-07:10 | 2669759.43 | 18-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 18453.81 | 152646.94 | 03-JAN-07:10 | 2669759.43 | 18-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6381.37 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
Water:HVAC | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
Humidifier:Water | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
General:Humidifier:Water | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
MainsWater:Facility | 6381.37 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
MainsWater:HVAC | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
Humidifier:MainsWater | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
General:Humidifier:MainsWater | 1.03 | 0.00 | 01-JAN-00:10 | 0.00 | 19-DEC-10:40 |
Water:Plant | 6380.34 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 6380.34 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4100.17 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:Water | 4100.17 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 4100.17 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:MainsWater | 4100.17 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 55258.54 | 227916.80 | 01-JAN-05:30 | 10350640.76 | 18-AUG-15:50 |
EnergyTransfer:Building | 19624.64 | 93337.60 | 01-JAN-07:30 | 1488650.89 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 704.05 | 0.00 | 01-JAN-00:10 | 72037.57 | 13-NOV-06:10 |
Heating:EnergyTransfer | 29.23 | 0.00 | 02-JAN-22:10 | 162488.38 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.87 | 0.00 | 01-JAN-00:10 | 16819.07 | 14-OCT-16:10 |
General:Heating:EnergyTransfer | 29.23 | 0.00 | 02-JAN-22:10 | 162488.38 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.87 | 0.00 | 01-JAN-00:10 | 16819.07 | 14-OCT-16:10 |
Cooling:EnergyTransfer | 19595.41 | 92813.62 | 01-JAN-07:00 | 1488650.89 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 700.17 | 0.00 | 01-JAN-00:10 | 72037.57 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 19595.41 | 92813.62 | 01-JAN-07:00 | 1488650.89 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 700.17 | 0.00 | 01-JAN-00:10 | 72037.57 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 682.06 | 0.00 | 01-JAN-00:10 | 54238.36 | 26-DEC-10:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 682.06 | 0.00 | 01-JAN-00:10 | 54238.36 | 26-DEC-10:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 682.06 | 0.00 | 01-JAN-00:10 | 54238.36 | 26-DEC-10:20 |
EnergyTransfer:Zone:CORE_MID | 5033.32 | 0.00 | 01-JAN-00:10 | 455238.04 | 02-OCT-10:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5033.32 | 0.00 | 01-JAN-00:10 | 455238.04 | 02-OCT-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5033.32 | 0.00 | 01-JAN-00:10 | 455238.04 | 02-OCT-10:00 |
EnergyTransfer:Zone:CORE_TOP | 438.16 | 0.00 | 01-JAN-00:10 | 52259.11 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.18 | 0.00 | 01-JAN-00:10 | 30548.57 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.18 | 0.00 | 01-JAN-00:10 | 30548.57 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 437.98 | 0.00 | 01-JAN-00:10 | 52259.11 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 437.98 | 0.00 | 01-JAN-00:10 | 52259.11 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.39 | 0.00 | 01-JAN-00:10 | 9078.35 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.39 | 0.00 | 01-JAN-00:10 | 9078.35 | 16-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.39 | 0.00 | 01-JAN-00:10 | 9078.35 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.06 | 0.00 | 01-JAN-00:10 | 9628.89 | 16-OCT-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.06 | 0.00 | 01-JAN-00:10 | 9628.89 | 16-OCT-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.06 | 0.00 | 01-JAN-00:10 | 9628.89 | 16-OCT-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.97 | 0.00 | 01-JAN-00:10 | 16630.49 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.97 | 0.00 | 01-JAN-00:10 | 16630.49 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.97 | 0.00 | 01-JAN-00:10 | 16630.49 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 110.57 | 0.00 | 01-JAN-00:10 | 13621.62 | 26-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 110.57 | 0.00 | 01-JAN-00:10 | 13621.62 | 26-APR-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 110.57 | 0.00 | 01-JAN-00:10 | 13621.62 | 26-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 545.25 | 0.00 | 01-JAN-00:10 | 80648.96 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.72 | 0.00 | 01-JAN-00:10 | 41666.01 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.72 | 0.00 | 01-JAN-00:10 | 41666.01 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 544.53 | 0.00 | 01-JAN-00:10 | 80648.96 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 544.53 | 0.00 | 01-JAN-00:10 | 80648.96 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 593.01 | 0.00 | 01-JAN-00:10 | 94424.24 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 29192.80 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.38 | 0.00 | 01-JAN-00:10 | 29192.80 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 592.62 | 0.00 | 01-JAN-00:10 | 94424.24 | 19-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 592.62 | 0.00 | 01-JAN-00:10 | 94424.24 | 19-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 974.27 | 0.00 | 01-JAN-00:10 | 162685.69 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.20 | 0.00 | 01-JAN-00:10 | 40396.14 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.20 | 0.00 | 01-JAN-00:10 | 40396.14 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 974.08 | 0.00 | 01-JAN-00:10 | 162685.69 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 974.08 | 0.00 | 01-JAN-00:10 | 162685.69 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 665.72 | 0.00 | 01-JAN-00:10 | 110609.86 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.13 | 0.00 | 01-JAN-00:10 | 24666.22 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.13 | 0.00 | 01-JAN-00:10 | 24666.22 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 665.58 | 0.00 | 01-JAN-00:10 | 110609.86 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 665.58 | 0.00 | 01-JAN-00:10 | 110609.86 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.53 | 0.00 | 01-JAN-00:10 | 10320.09 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.13 | 0.00 | 01-JAN-00:10 | 10320.09 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.13 | 0.00 | 01-JAN-00:10 | 10320.09 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.40 | 0.00 | 01-JAN-00:10 | 9007.22 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.40 | 0.00 | 01-JAN-00:10 | 9007.22 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 56.02 | 0.00 | 01-JAN-00:10 | 9443.44 | 19-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.93 | 0.00 | 01-JAN-00:10 | 6522.69 | 30-MAR-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.93 | 0.00 | 01-JAN-00:10 | 6522.69 | 30-MAR-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.09 | 0.00 | 01-JAN-00:10 | 9443.44 | 19-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.09 | 0.00 | 01-JAN-00:10 | 9443.44 | 19-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.23 | 0.00 | 01-JAN-00:10 | 17841.07 | 16-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.83 | 0.00 | 01-JAN-00:10 | 9058.90 | 30-MAR-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.83 | 0.00 | 01-JAN-00:10 | 9058.90 | 30-MAR-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.41 | 0.00 | 01-JAN-00:10 | 17841.07 | 16-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.41 | 0.00 | 01-JAN-00:10 | 17841.07 | 16-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.91 | 0.00 | 01-JAN-00:10 | 11716.12 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.58 | 0.00 | 01-JAN-00:10 | 5698.15 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.58 | 0.00 | 01-JAN-00:10 | 5698.15 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.33 | 0.00 | 01-JAN-00:10 | 11716.12 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.33 | 0.00 | 01-JAN-00:10 | 11716.12 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.65 | 0.00 | 01-JAN-00:10 | 9003.60 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.15 | 0.00 | 01-JAN-00:10 | 3321.14 | 18-DEC-04:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.15 | 0.00 | 01-JAN-00:10 | 3321.14 | 18-DEC-04:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.50 | 0.00 | 01-JAN-00:10 | 9003.60 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.50 | 0.00 | 01-JAN-00:10 | 9003.60 | 16-OCT-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 484.94 | 0.00 | 01-JAN-00:10 | 69040.06 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.71 | 0.00 | 01-JAN-00:10 | 28209.59 | 02-APR-14:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.71 | 0.00 | 01-JAN-00:10 | 28209.59 | 02-APR-14:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 477.23 | 0.00 | 01-JAN-00:10 | 69040.06 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 477.23 | 0.00 | 01-JAN-00:10 | 69040.06 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 80.14 | 0.00 | 01-JAN-00:10 | 18809.70 | 29-SEP-13:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 10.28 | 0.00 | 01-JAN-00:10 | 11110.19 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 10.28 | 0.00 | 01-JAN-00:10 | 11110.19 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.86 | 0.00 | 01-JAN-00:10 | 18809.70 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.86 | 0.00 | 01-JAN-00:10 | 18809.70 | 29-SEP-13:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.20 | 1116.94 | 09-JAN-07:00 | 7895.55 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.20 | 1116.94 | 09-JAN-07:00 | 7895.55 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.20 | 1116.94 | 09-JAN-07:00 | 7895.55 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1279.62 | 2378.84 | 02-JAN-06:00 | 73500.51 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1279.62 | 2378.84 | 02-JAN-06:00 | 73500.51 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1279.62 | 2378.84 | 02-JAN-06:00 | 73500.51 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.98 | 0.16 | 13-JAN-08:00 | 7499.12 | 20-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-10:20 | 541.29 | 08-JAN-07:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-10:20 | 541.29 | 08-JAN-07:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.85 | 0.00 | 01-JAN-00:10 | 7499.12 | 20-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 119.85 | 0.00 | 01-JAN-00:10 | 7499.12 | 20-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.58 | 87418.34 | 14-MAY-05:00 | 369050.75 | 18-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.58 | 87418.34 | 14-MAY-05:00 | 369050.75 | 18-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.58 | 87418.34 | 14-MAY-05:00 | 369050.75 | 18-DEC-17:00 |
PlantLoopHeatingDemand:Facility | 704.06 | 0.00 | 01-JAN-00:10 | 518317.87 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 377.81 | 0.00 | 01-JAN-00:10 | 43844.35 | 03-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43844.35 | 03-FEB-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43844.35 | 03-FEB-13:00 |
EnergyTransfer:HVAC | 16305.26 | 133904.40 | 02-JAN-06:00 | 2518625.86 | 18-AUG-15:50 |
HeatingCoils:EnergyTransfer | 326.24 | 0.00 | 01-JAN-00:10 | 503867.32 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 326.24 | 0.00 | 01-JAN-00:10 | 503867.32 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 326.24 | 0.00 | 01-JAN-00:10 | 503867.32 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 15979.02 | 121809.46 | 03-JAN-07:10 | 2518625.86 | 18-AUG-15:50 |
EnergyTransfer:Plant | 19328.64 | 0.00 | 01-JAN-00:10 | 6357219.82 | 18-AUG-15:50 |
LoopToLoop:EnergyTransfer | 6278.47 | -0.00 | 02-JAN-04:10 | 2027158.25 | 18-AUG-15:50 |
WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43844.35 | 03-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43844.35 | 03-FEB-13:00 |
Boilers:EnergyTransfer | 323.01 | 0.00 | 01-JAN-00:10 | 597320.42 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 5716.39 | 0.00 | 01-JAN-00:10 | 2001327.07 | 18-AUG-15:50 |
HeatRejection:EnergyTransfer | 6632.96 | 0.00 | 01-JAN-00:10 | 2298277.80 | 18-AUG-15:50 |
General:HeatRejection:EnergyTransfer | 6632.96 | 0.00 | 01-JAN-00:10 | 2298277.80 | 18-AUG-15:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.872 | -700.179 | 0.000 | 0.000 | 92.698 | 235.627 | 424.397 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -56.415 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -682.059 | 0.000 | 0.000 | 83.378 | 211.610 | 321.286 | 0.000 | 0.000 | 0.000 | 65.786 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5033.349 | 0.000 | 0.000 | 835.265 | 2116.097 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1130.858 |
CORE_TOP | 0.000 | 0.000 | 0.179 | -437.978 | 0.000 | 0.000 | 84.511 | 211.610 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -179.606 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -78.394 | 0.000 | 0.000 | 10.544 | 26.570 | 40.342 | 16.002 | 0.000 | 0.037 | 30.201 | 0.000 | -40.544 | 0.000 | -4.759 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -71.064 | 0.000 | 0.000 | 6.832 | 17.123 | 25.998 | 38.353 | 0.000 | 0.024 | 10.918 | 0.000 | -25.086 | 0.000 | -3.098 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -116.976 | 0.000 | 0.000 | 10.543 | 26.570 | 40.343 | 75.789 | 0.000 | 0.033 | 7.991 | 0.000 | -39.447 | 0.000 | -4.847 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -110.574 | 0.000 | 0.000 | 6.773 | 17.123 | 25.998 | 42.651 | 0.000 | 0.023 | 51.385 | 0.000 | -29.820 | 0.000 | -3.558 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.724 | -544.531 | 0.000 | 0.000 | 107.782 | 265.697 | 403.423 | 170.171 | 0.000 | 0.947 | 65.333 | 0.000 | -370.697 | 0.000 | -98.850 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.383 | -592.630 | 0.000 | 0.000 | 51.297 | 171.225 | 259.981 | 385.374 | 0.000 | 0.566 | 29.918 | 0.000 | -238.464 | 0.000 | -67.650 | -0.007 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.198 | -974.095 | 0.000 | 0.000 | 106.250 | 265.703 | 403.429 | 755.670 | 0.000 | 0.744 | 0.044 | 0.000 | -383.013 | 0.000 | -108.757 | -66.130 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.133 | -665.589 | 0.000 | 0.000 | 70.142 | 171.225 | 259.979 | 437.530 | 0.000 | 0.637 | 55.514 | 0.000 | -258.677 | 0.000 | -70.895 | -0.010 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.128 | -51.403 | 0.000 | 0.000 | 11.112 | 26.570 | 40.342 | 17.905 | 0.000 | 0.132 | 0.000 | 0.000 | -33.853 | 0.000 | -10.995 | -1.938 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.934 | -55.086 | 0.000 | 0.000 | 7.074 | 17.123 | 25.998 | 39.048 | 0.000 | 0.070 | 0.000 | 0.000 | -22.309 | 0.000 | -7.734 | -5.118 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.827 | -90.408 | 0.000 | 0.000 | 10.824 | 26.570 | 40.343 | 76.218 | 0.000 | 0.091 | 0.002 | 0.000 | -35.756 | 0.000 | -12.434 | -16.276 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.579 | -63.331 | 0.000 | 0.000 | 7.183 | 17.123 | 25.998 | 44.030 | 0.000 | 0.082 | 0.704 | 0.000 | -24.207 | 0.000 | -8.160 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.201 | 0.000 | 0.000 | 0.950 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.000 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1279.617 | 0.000 | 0.000 | 9.500 | 43.701 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -312.390 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.129 | -119.849 | 0.000 | 0.000 | 0.950 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.481 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7164.581 | 0.000 | 0.000 | 20.460 | 66.437 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -417.172 |
GROUNDFLOOR_PLENUM | 1.152 | -75.502 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.059 | 84.652 | 0.000 | 0.000 | 0.000 | -10.361 | 0.000 |
MIDFLOOR_PLENUM | 7.710 | -477.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.117 | 645.347 | 0.000 | 0.000 | 0.000 | -176.948 | 0.000 |
TOPFLOOR_PLENUM | 10.283 | -69.861 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.096 | 77.961 | 0.000 | 0.000 | 0.000 | -18.479 | -0.001 |
Total Facility | 19.146 | -622.589 | 10.087 | -18972.894 | 0.000 | 0.000 | 1534.067 | 3942.443 | 15213.411 | 2098.740 | 0.000 | 4.659 | 1125.761 | 0.000 | -1501.872 | 0.000 | -607.524 | -2243.404 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-DEC-04:02 | 0.00 | 0.00 | 0.00 | -110907.18 | 0.00 | 0.00 | 0.00 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 96306.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -94815.85 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.15 | 0.00 | 0.00 | 0.00 | 85732.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-03:02 | 0.00 | 0.00 | 0.00 | -851126.18 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 760289.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-OCT-03:02 | 0.00 | 0.00 | 0.00 | -83446.58 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 74362.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-05:03 | 0.00 | 0.00 | 0.00 | -11799.92 | 0.00 | 0.00 | 108.96 | 257.76 | 1011.70 | 0.00 | 0.00 | 0.00 | 11681.86 | 0.00 | -1260.35 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:43 | 0.00 | 0.00 | 0.00 | -16198.46 | 0.00 | 0.00 | 24.64 | 83.06 | 488.98 | 10062.94 | 0.00 | 186.89 | 5351.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19-NOV-12:12 | 0.00 | 0.00 | 0.00 | -21280.42 | 0.00 | 0.00 | 36.49 | 128.90 | 758.78 | 17534.39 | 0.00 | 0.00 | 2908.89 | 0.00 | -0.00 | 0.00 | -87.03 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-15:02 | 0.00 | 0.00 | 0.00 | -21553.67 | 0.00 | 0.00 | 22.99 | 83.06 | 488.98 | 9144.15 | 0.00 | 0.00 | 11933.59 | 0.00 | -0.00 | 0.00 | -119.11 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -95613.43 | 0.00 | 0.00 | 1162.14 | 2577.57 | 10116.97 | 0.00 | 0.00 | 0.00 | 89529.98 | 0.00 | -7765.13 | 0.00 | -8.10 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-08:53 | 0.00 | 0.00 | 0.00 | -164896.53 | 0.00 | 0.00 | 250.94 | 830.63 | 4889.82 | 91550.86 | 0.00 | 0.00 | 68656.76 | 0.00 | -0.00 | 0.00 | -1282.49 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:01 | 0.00 | 0.00 | 0.00 | -215135.22 | 0.00 | 0.00 | 334.12 | 1288.96 | 7587.84 | 145471.87 | 0.00 | 4447.58 | 56004.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 | -181182.56 | 0.00 | 0.00 | 241.64 | 830.63 | 4889.79 | 91273.58 | 0.00 | 0.00 | 83946.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | -11534.18 | 0.00 | 0.00 | 110.87 | 257.76 | 1011.70 | 0.00 | 0.00 | 0.00 | 10932.27 | 0.00 | -776.95 | 0.00 | -1.46 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-09:13 | 0.00 | 0.00 | 0.00 | -16417.18 | 0.00 | 0.00 | 24.73 | 83.06 | 488.98 | 8682.31 | 0.00 | 486.13 | 6651.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-15:52 | 0.00 | 0.00 | 0.00 | -22587.41 | 0.00 | 0.00 | 36.38 | 128.90 | 758.78 | 4006.81 | 0.00 | 190.56 | 17465.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:52 | 0.00 | 0.00 | 0.00 | -20296.04 | 0.00 | 0.00 | 22.22 | 83.06 | 488.98 | 9325.39 | 0.00 | 127.52 | 10248.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:43 | 0.00 | 0.00 | 0.00 | -7895.50 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 79.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:43 | 0.00 | 0.00 | 0.00 | -73499.99 | 0.00 | 0.00 | 0.00 | 211.99 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4656.22 |
DATACENTER_TOP_ZN_6 | 20-AUG-17:23 | 0.00 | 0.00 | 0.00 | -7499.08 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -316.54 |
DATACENTER_BASEMENT_ZN_6 | 19-DEC-17:05 | 0.00 | 0.00 | 0.00 | -369352.20 | 0.00 | 0.00 | 667.28 | 3222.71 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14170.32 |
GROUNDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -10672.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10748.30 | 0.00 | -0.00 | 0.00 | -76.01 | 0.00 |
MIDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -79326.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80675.33 | 0.00 | -0.00 | 0.00 | -1348.52 | 0.00 |
TOPFLOOR_PLENUM | 29-SEP-12:10 | 0.00 | -19726.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.05 | 19224.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:03 | 0.00 | 12092.71 | 0.00 | -1706257.36 | 0.00 | 0.00 | 15826.01 | 38246.31 | 623236.89 | 0.00 | 0.00 | 0.00 | 1084391.20 | 0.00 | -60537.73 | 0.00 | -6998.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-OCT-16:03 | 0.00 | 0.00 | 18072.26 | 0.00 | 0.00 | 0.00 | 520.12 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33192.98 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 65150.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2052.86 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -75260.53 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 100102.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2577.57 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18536.15 | 0.00 | -17139.19 | -77121.75 |
PERIMETER_MID_ZN_2 | 30-MAR-04:01 | 0.00 | 0.00 | 101332.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1661.09 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21616.84 | 0.00 | -13381.81 | -74515.09 |
PERIMETER_MID_ZN_1 | 02-JAN-06:01 | 0.00 | 0.00 | 128983.05 | 0.00 | 0.00 | 0.00 | 1445.96 | 2577.63 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20180.64 | 0.00 | -2760.16 | -120182.97 |
PERIMETER_MID_ZN_4 | 09-JAN-06:01 | 0.00 | 0.00 | 90750.01 | 0.00 | 0.00 | 0.00 | 941.49 | 1661.09 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25390.03 | 0.00 | -2997.94 | -71484.34 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:02 | 0.00 | 0.00 | 13393.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1372.66 | 0.00 | -1522.17 | -11638.76 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:02 | 0.00 | 0.00 | 13117.14 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -959.67 | 0.00 | -1113.53 | -11778.98 |
PERIMETER_TOP_ZN_1 | 02-JAN-04:02 | 0.00 | 0.00 | 16830.67 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1534.89 | 0.00 | -1705.07 | -14731.32 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 13400.16 | 0.00 | 0.00 | 0.00 | 0.00 | 166.11 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.68 | 0.00 | -1244.17 | -12000.39 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 08-JAN-07:00 | 0.00 | 0.00 | 541.30 | 0.00 | 0.00 | 0.00 | 5.58 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2516.69 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-04:02 | 12550.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1640.50 | -10910.05 |
MIDFLOOR_PLENUM | 28-MAR-05:02 | 83880.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8126.49 | -75754.38 |
TOPFLOOR_PLENUM | 30-MAY-05:03 | 19160.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -240.11 | -18920.34 |
Total Facility | 02-JAN-06:01 | -456284.07 | 451377.79 | 526530.28 | -451377.79 | 0.00 | 0.00 | 18724.62 | 38246.31 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -80325.53 | 0.00 | -15937.38 | -299316.94 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.1265 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 95.0728 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 86.2458 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.7500 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3309 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6261 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6261 | 0.2133 | 1.0000 | Not calculated | 1.2002 | 0.2133 | ||
AIRLOOP DATACENTER BASEMENT | 21.6804 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.6807 | 0.0156 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 0.0327 | 1.0000 | Not calculated | 0.0156 | 0.0327 | ||
AIRLOOP DATACENTER MID | 4.5416 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5416 | 0.0344 | 1.0000 | Not calculated | 0.1563 | 0.0344 | ||
AIRLOOP DATACENTER TOP | 0.4631 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4631 | 0.0338 | 1.0000 | Not calculated | 0.0156 | 0.0338 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0632 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0379 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 47.5364 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.6169 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.8750 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0030 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6261 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6261 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2133 | ||
AIRLOOP DATACENTER BASEMENT | 21.6804 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.6804 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0156 | ||
AIRLOOP DATACENTER BOT | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0327 | ||
AIRLOOP DATACENTER MID | 4.5416 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5416 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0344 | ||
AIRLOOP DATACENTER TOP | 0.4631 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4631 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0338 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6261 | 5.6261 | 5.6261 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9210 | 5.9210 | 1.7763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.7203 | 55.7203 | 16.7718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4702 | 5.4702 | 1.6848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8811 | 0.8811 | 0.2643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9470 | 0.9470 | 0.2841 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1642 | 1.1642 | 0.3493 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2132 | 1.2132 | 0.3640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2522 | 8.2522 | 2.4839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.6258 | 9.6258 | 2.8974 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1731 | 11.1731 | 3.3631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3014 | 10.3014 | 3.1007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9551 | 0.9551 | 0.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9629 | 0.9629 | 0.2966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2437 | 1.2437 | 0.3831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1180 | 1.1180 | 0.3443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5416 | 4.5416 | 4.5416 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4631 | 0.4631 | 0.4631 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.6804 | 21.6804 | 21.6804 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.1265 | 9.3112 | 10.1265 | 3.0379 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 95.0728 | 86.2458 | 95.0728 | 28.6169 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.7500 | 9.3309 | 9.7500 | 3.0030 | 0.0000 | 1.0000 |
CAV_BAS | 5.6261 | 5.6261 | 5.6261 | 5.6261 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.6804 | 21.6807 | 21.6804 | 21.6804 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5416 | 4.5416 | 4.5416 | 4.5416 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4631 | 0.4631 | 0.4631 | 0.4631 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6261 | 5.6261 | 5.6261 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9605 | 2.9605 | 1.7763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.8602 | 27.8602 | 16.7718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7351 | 2.7351 | 1.6848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4405 | 0.4405 | 0.2643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4735 | 0.4735 | 0.2841 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5821 | 0.5821 | 0.3493 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6066 | 0.6066 | 0.3640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.1261 | 4.1261 | 2.4839 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8129 | 4.8129 | 2.8974 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5865 | 5.5865 | 3.3631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1507 | 5.1507 | 3.1007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4776 | 0.4776 | 0.2942 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4815 | 0.4815 | 0.2966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6218 | 0.6218 | 0.3831 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5590 | 0.5590 | 0.3443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5416 | 4.5416 | 4.5416 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4631 | 0.4631 | 0.4631 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.6804 | 21.6804 | 21.6804 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0632 | 3.0379 | 3.0379 | 3.0379 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 47.5364 | 28.6169 | 28.6169 | 28.6169 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.8750 | 3.0030 | 3.0030 | 3.0030 | 0.0000 | 1.0000 |
CAV_BAS | 5.6261 | 5.6261 | 5.6261 | 5.6261 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.6804 | 21.6804 | 21.6804 | 21.6804 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5416 | 4.5416 | 4.5416 | 4.5416 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4631 | 0.4631 | 0.4631 | 0.4631 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 229.67 |
Number of hours not met | 229.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 469.15 | 752660.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3391.36 | 448084.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3942.44 | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 905.27 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.51 | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2462.16 | 205774.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 670.87 | 67222.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1391.89 | 82101.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2.77 | 6835.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 741.87 | 78860.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 29977.77 |
Natural Gas | 0.00 | 1211.02 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 31188.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.11 |
Space Heating | 0.00 |
Space Cooling | 73.22 |
Fans (All) | 53.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 647.18 |
Subtotal | 647.18 |
Natural Gas [MJ/m2] | |
Space Heating | 10.13 |
Service Water Heating | 16.02 |
Miscellaneous (All) | 26.14 |
Subtotal | 26.14 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.64 |
Space Heating | 1.50 |
Space Cooling | 10.87 |
Fans (All) | 7.89 |
Service Water Heating | 2.38 |
Receptacle Equipment | 48.78 |
Miscellaneous | 15.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2355. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8140.50 | 619.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8620.00 | 140.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8098.50 | 661.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8714.50 | 45.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8697.00 | 63.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8707.00 | 53.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6600.33 | 2159.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6560.17 | 2199.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6497.83 | 2262.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6879.00 | 1881.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8674.83 | 85.17 | 0.00 | 0.00 | 0.00 |
Min | 6497.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2262.17 | 0.00 | 0.00 | 0.00 |
Average | 8309.17 | 450.83 | 0.00 | 0.00 | 0.00 |
Sum | 191111.00 | 10369.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367030.50 | 1585.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330660.00 | 153.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 946.17 | 1321.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 929.67 | 1338.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 901.83 | 1366.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 54920.33 | 48474.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367030.50 | 48474.67 | 0.00 | 0.00 | 0.00 |
Average | 77976.67 | 2358.24 | 0.00 | 0.00 | 0.00 |
Sum | 1793463.50 | 54239.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7057.50 | 1702.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7564.33 | 1195.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7709.67 | 1050.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7982.83 | 777.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8417.50 | 342.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8517.83 | 242.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8362.33 | 397.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7471.17 | 1288.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8496.83 | 263.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8387.83 | 372.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8320.50 | 439.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8050.50 | 709.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8603.83 | 156.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8433.33 | 326.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8457.00 | 303.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8171.50 | 588.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7800.83 | 959.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7749.17 | 1010.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7706.67 | 1053.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8242.83 | 517.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7980.17 | 779.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8161.00 | 599.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7941.67 | 818.33 | 0.00 | 0.00 | 0.00 |
Min | 7057.50 | 156.17 | 0.00 | 0.00 | 0.00 |
Max | 8603.83 | 1702.50 | 0.00 | 0.00 | 0.00 |
Average | 8068.99 | 691.01 | 0.00 | 0.00 | 0.00 |
Sum | 185586.83 | 15893.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 361422.17 | 7193.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328877.83 | 1935.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329300.33 | 1512.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329713.00 | 1100.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1519.33 | 748.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1484.67 | 783.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1461.33 | 806.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 86773.33 | 16621.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 361422.17 | 16621.67 | 0.00 | 0.00 | 0.00 |
Average | 79000.04 | 1334.87 | 0.00 | 0.00 | 0.00 |
Sum | 1817001.00 | 30702.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:55
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581253E+11 | 109087.97 | 23-JAN-04:03 | 9.00 | 7.85 | 0.566860E+10 | 7499.45 | 10-JAN-14:20 | 9.00 | 7.85 |
February | 0.501685E+11 | 110018.52 | 21-FEB-04:02 | 7.17 | 5.77 | 0.513927E+10 | 7500.25 | 01-FEB-14:20 | 7.17 | 5.77 |
March | 0.593979E+11 | 110567.16 | 20-MAR-03:02 | 8.50 | 8.42 | 0.613297E+10 | 7499.46 | 01-MAR-14:20 | 8.50 | 8.42 |
April | 0.557816E+11 | 110124.99 | 17-APR-03:02 | 10.00 | 8.82 | 0.544977E+10 | 7499.38 | 13-APR-09:00 | 10.00 | 8.82 |
May | 0.566455E+11 | 107313.42 | 22-MAY-03:02 | 12.00 | 10.34 | 0.589985E+10 | 7499.46 | 05-MAY-13:00 | 12.00 | 10.34 |
June | 0.576664E+11 | 106263.77 | 05-JUN-03:02 | 12.00 | 11.37 | 0.588005E+10 | 7499.15 | 21-JUN-13:20 | 23.67 | 16.91 |
July | 0.581716E+11 | 99412.28 | 17-JUL-03:02 | 14.17 | 13.59 | 0.547189E+10 | 7499.08 | 11-JUL-13:20 | 14.17 | 13.59 |
August | 0.642696E+11 | 95510.00 | 28-AUG-03:02 | 14.00 | 14.00 | 0.613583E+10 | 7499.13 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.572791E+11 | 98928.89 | 19-SEP-03:02 | 13.83 | 12.18 | 0.545122E+10 | 7499.34 | 21-SEP-09:09 | 19.33 | 17.40 |
October | 0.620112E+11 | 109906.31 | 30-OCT-03:02 | 9.00 | 6.92 | 0.567175E+10 | 7542.41 | 16-OCT-13:39 | 9.00 | 6.92 |
November | 0.605608E+11 | 110229.24 | 06-NOV-04:03 | 8.33 | 7.63 | 0.561558E+10 | 7499.84 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.600955E+11 | 110923.87 | 11-DEC-04:02 | 8.00 | 7.91 | 0.547274E+10 | 7500.06 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.700173E+12 | 0.679895E+11 | ||||||||
Minimum of Months | 0.501685E+11 | 95510.00 | 7.17 | 5.77 | 0.513927E+10 | 7499.08 | 7.17 | 5.77 | ||
Maximum of Months | 0.642696E+11 | 110923.87 | 14.17 | 14.00 | 0.613583E+10 | 7542.41 | 23.67 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485363E+11 | 94933.39 | 02-JAN-04:02 | 10.17 | 8.61 | 0.508104E+10 | 6735.06 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.461100E+11 | 92459.84 | 21-FEB-04:02 | 7.17 | 5.77 | 0.460643E+10 | 6735.61 | 01-FEB-14:09 | 7.17 | 5.77 |
March | 0.569310E+11 | 91356.22 | 20-MAR-03:02 | 8.50 | 8.42 | 0.550165E+10 | 6735.06 | 01-MAR-14:09 | 8.50 | 8.42 |
April | 0.597677E+11 | 90545.77 | 17-APR-03:02 | 10.00 | 8.82 | 0.488381E+10 | 6735.18 | 13-APR-09:00 | 10.00 | 8.82 |
May | 0.531970E+11 | 92141.81 | 30-MAY-03:02 | 11.83 | 10.73 | 0.528835E+10 | 6735.24 | 03-MAY-13:00 | 11.83 | 10.73 |
June | 0.575953E+11 | 93617.11 | 12-JUN-03:02 | 13.00 | 11.87 | 0.527353E+10 | 6734.75 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.641172E+11 | 88784.73 | 06-JUL-03:02 | 13.17 | 12.60 | 0.489744E+10 | 6734.77 | 11-JUL-09:09 | 19.33 | 16.00 |
August | 0.714876E+11 | 87618.97 | 23-AUG-03:02 | 15.37 | 14.00 | 0.549792E+10 | 6734.60 | 29-AUG-13:00 | 24.00 | 17.64 |
September | 0.528929E+11 | 94326.25 | 05-SEP-03:02 | 15.17 | 13.86 | 0.488403E+10 | 6734.75 | 01-SEP-13:09 | 15.17 | 13.86 |
October | 0.583542E+11 | 92240.43 | 23-OCT-03:02 | 17.00 | 14.51 | 0.507991E+10 | 6735.08 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.557432E+11 | 93927.82 | 20-NOV-04:02 | 11.00 | 10.37 | 0.503244E+10 | 6735.51 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.573225E+11 | 93614.80 | 11-DEC-04:02 | 8.00 | 7.91 | 0.490382E+10 | 6735.80 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.682055E+12 | 0.609304E+11 | ||||||||
Minimum of Months | 0.461100E+11 | 87618.97 | 7.17 | 5.77 | 0.460643E+10 | 6734.60 | 7.17 | 5.77 | ||
Maximum of Months | 0.714876E+11 | 94933.39 | 17.00 | 14.51 | 0.550165E+10 | 6735.80 | 24.00 | 17.64 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367391E+11 | 79506.39 | 20-JAN-06:02 | 11.33 | 10.71 | 0.505377E+10 | 6735.03 | 10-JAN-14:09 | 11.33 | 10.71 |
February | 0.337704E+11 | 79576.04 | 15-FEB-06:02 | 11.83 | 10.84 | 0.458655E+10 | 6735.52 | 01-FEB-14:09 | 11.83 | 10.84 |
March | 0.398044E+11 | 79483.82 | 23-MAR-05:02 | 10.67 | 9.62 | 0.548298E+10 | 6735.03 | 01-MAR-14:09 | 10.67 | 9.62 |
April | 0.403997E+11 | 80786.00 | 27-APR-04:03 | 15.00 | 14.41 | 0.487223E+10 | 6735.10 | 13-APR-09:00 | 15.00 | 14.41 |
May | 0.432608E+11 | 80513.69 | 04-MAY-04:03 | 13.17 | 11.94 | 0.528110E+10 | 6735.21 | 03-MAY-13:00 | 13.17 | 11.94 |
June | 0.459973E+11 | 81408.14 | 21-JUN-04:02 | 17.00 | 14.51 | 0.526759E+10 | 6734.74 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.466878E+11 | 80964.82 | 14-JUL-04:03 | 16.00 | 14.77 | 0.489384E+10 | 6734.76 | 07-JUL-13:09 | 16.00 | 14.77 |
August | 0.505980E+11 | 80944.80 | 31-AUG-04:03 | 14.17 | 14.07 | 0.549505E+10 | 6734.77 | 22-AUG-13:09 | 14.17 | 14.07 |
September | 0.439478E+11 | 83448.51 | 25-SEP-03:02 | 17.00 | 16.37 | 0.487845E+10 | 6734.78 | 01-SEP-13:09 | 17.00 | 16.37 |
October | 0.453807E+11 | 85128.36 | 02-OCT-03:02 | 19.00 | 17.66 | 0.507126E+10 | 6735.03 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.390881E+11 | 82424.43 | 13-NOV-04:02 | 11.83 | 10.73 | 0.501859E+10 | 6735.34 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.376581E+11 | 79115.77 | 02-DEC-06:02 | 10.00 | 10.00 | 0.488056E+10 | 6735.64 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.503332E+12 | 0.607820E+11 | ||||||||
Minimum of Months | 0.337704E+11 | 79115.77 | 10.00 | 9.62 | 0.458655E+10 | 6734.74 | 10.67 | 9.62 | ||
Maximum of Months | 0.505980E+11 | 85128.36 | 19.00 | 17.66 | 0.549505E+10 | 6735.64 | 23.00 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269220E+11 | 38767.62 | 19-JAN-15:00 | 20.00 | 15.12 | 0.484341E+10 | 6734.94 | 10-JAN-14:09 | 20.00 | 15.12 |
February | 0.258002E+11 | 39245.39 | 16-FEB-16:20 | 16.47 | 13.30 | 0.443331E+10 | 6735.72 | 01-FEB-14:09 | 16.47 | 13.30 |
March | 0.313444E+11 | 69157.68 | 24-MAR-05:03 | 12.00 | 12.00 | 0.532796E+10 | 6734.92 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.362987E+11 | 76727.75 | 27-APR-05:03 | 15.00 | 14.41 | 0.481925E+10 | 6735.11 | 13-APR-13:00 | 15.00 | 14.41 |
May | 0.389750E+11 | 76568.26 | 03-MAY-05:03 | 14.17 | 14.07 | 0.523395E+10 | 6735.26 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.443159E+11 | 78599.12 | 20-JUN-05:02 | 17.00 | 14.42 | 0.525190E+10 | 6734.70 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.471388E+11 | 79754.16 | 31-JUL-04:02 | 17.00 | 16.37 | 0.488983E+10 | 6734.73 | 07-JUL-13:09 | 17.00 | 16.37 |
August | 0.502220E+11 | 78693.54 | 18-AUG-05:02 | 17.92 | 17.36 | 0.548900E+10 | 6734.73 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.403674E+11 | 78678.97 | 25-SEP-04:03 | 17.00 | 16.37 | 0.485865E+10 | 6734.74 | 01-SEP-13:09 | 17.00 | 16.37 |
October | 0.397195E+11 | 83462.29 | 02-OCT-03:02 | 19.00 | 17.66 | 0.503130E+10 | 6734.99 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.294618E+11 | 65881.64 | 01-NOV-05:03 | 12.83 | 9.89 | 0.490458E+10 | 6735.29 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.274126E+11 | 51489.98 | 06-DEC-06:03 | 12.33 | 6.18 | 0.471442E+10 | 6735.55 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.437978E+12 | 0.597976E+11 | ||||||||
Minimum of Months | 0.258002E+11 | 38767.62 | 12.00 | 6.18 | 0.443331E+10 | 6734.70 | 12.00 | 12.00 | ||
Maximum of Months | 0.502220E+11 | 83462.29 | 20.00 | 17.66 | 0.548900E+10 | 6735.72 | 26.83 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451136E+10 | 6283.75 | 17-JAN-13:40 | 23.33 | 17.00 | 0.621693E+09 | 845.66 | 10-JAN-14:09 | 23.33 | 17.00 |
February | 0.445997E+10 | 5417.76 | 01-FEB-12:00 | 26.00 | 14.67 | 0.567397E+09 | 845.73 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.555766E+10 | 6218.16 | 13-MAR-14:00 | 18.00 | 13.88 | 0.679464E+09 | 845.66 | 01-MAR-14:09 | 18.00 | 13.88 |
April | 0.678394E+10 | 7494.13 | 26-APR-14:00 | 26.00 | 16.74 | 0.608677E+09 | 845.68 | 13-APR-09:00 | 26.00 | 16.74 |
May | 0.646533E+10 | 8678.84 | 01-MAY-05:03 | 13.17 | 11.94 | 0.659562E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.775702E+10 | 11716.29 | 26-JUN-05:03 | 17.17 | 15.13 | 0.660763E+09 | 845.63 | 22-JUN-09:00 | 17.17 | 15.13 |
July | 0.904973E+10 | 11801.61 | 05-JUL-05:03 | 17.00 | 14.42 | 0.614319E+09 | 845.63 | 11-JUL-09:09 | 19.33 | 16.00 |
August | 0.957668E+10 | 11527.42 | 01-AUG-05:03 | 17.00 | 15.07 | 0.689409E+09 | 845.61 | 01-AUG-13:09 | 22.00 | 16.85 |
September | 0.650468E+10 | 11638.38 | 25-SEP-05:03 | 17.00 | 16.37 | 0.610200E+09 | 845.63 | 01-SEP-13:09 | 17.00 | 16.37 |
October | 0.695022E+10 | 10637.47 | 02-OCT-05:03 | 19.08 | 17.74 | 0.634015E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.543734E+10 | 6075.26 | 28-NOV-14:10 | 24.67 | 11.00 | 0.624135E+09 | 845.71 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.533905E+10 | 6655.73 | 05-DEC-15:00 | 25.00 | 13.22 | 0.605526E+09 | 845.74 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.783930E+11 | 0.757516E+10 | ||||||||
Minimum of Months | 0.445997E+10 | 5417.76 | 13.17 | 11.00 | 0.567397E+09 | 845.61 | 17.00 | 12.37 | ||
Maximum of Months | 0.957668E+10 | 11801.61 | 26.00 | 17.74 | 0.689409E+09 | 845.74 | 26.83 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440375E+10 | 6143.55 | 20-JAN-09:10 | 17.33 | 14.09 | 0.399372E+09 | 544.97 | 05-JAN-10:00 | 17.33 | 14.09 |
February | 0.413377E+10 | 6980.14 | 21-FEB-09:10 | 14.50 | 10.04 | 0.360744E+09 | 545.02 | 01-FEB-14:09 | 14.50 | 10.04 |
March | 0.508982E+10 | 8095.64 | 23-MAR-08:40 | 18.33 | 14.51 | 0.431587E+09 | 544.98 | 01-MAR-14:09 | 18.33 | 14.51 |
April | 0.642188E+10 | 14325.13 | 30-APR-08:43 | 21.33 | 15.18 | 0.389683E+09 | 545.01 | 13-APR-09:00 | 21.33 | 15.18 |
May | 0.598208E+10 | 10147.17 | 28-MAY-07:53 | 18.00 | 13.88 | 0.422567E+09 | 545.00 | 03-MAY-13:00 | 18.00 | 13.88 |
June | 0.666446E+10 | 11586.75 | 18-JUN-07:33 | 18.67 | 15.17 | 0.423065E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.809552E+10 | 15948.18 | 23-JUL-08:23 | 24.00 | 19.32 | 0.394395E+09 | 544.95 | 11-JUL-09:09 | 24.00 | 19.32 |
August | 0.863292E+10 | 10155.69 | 13-AUG-07:33 | 21.00 | 17.80 | 0.442400E+09 | 544.95 | 01-AUG-13:09 | 21.00 | 17.80 |
September | 0.603320E+10 | 10915.30 | 03-SEP-08:32 | 19.33 | 14.88 | 0.390830E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.611553E+10 | 16199.39 | 15-OCT-08:43 | 32.33 | 15.60 | 0.406233E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.474727E+10 | 6815.30 | 19-NOV-09:00 | 24.00 | 12.56 | 0.399050E+09 | 545.00 | 10-NOV-10:00 | 24.00 | 12.56 |
December | 0.474331E+10 | 6688.20 | 05-DEC-09:00 | 24.00 | 11.80 | 0.384574E+09 | 544.98 | 04-DEC-14:09 | 24.00 | 11.80 |
Annual Sum or Average | 0.710635E+11 | 0.484450E+10 | ||||||||
Minimum of Months | 0.413377E+10 | 6143.55 | 14.50 | 10.04 | 0.360744E+09 | 544.95 | 14.50 | 10.04 | ||
Maximum of Months | 0.863292E+10 | 16199.39 | 32.33 | 19.32 | 0.442400E+09 | 545.02 | 24.00 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.997814E+10 | 15734.95 | 18-JAN-13:30 | 25.30 | 14.77 | 0.630028E+09 | 847.10 | 20-JAN-14:20 | 17.00 | 14.51 |
February | 0.798240E+10 | 14785.05 | 21-FEB-13:20 | 20.33 | 13.83 | 0.566981E+09 | 846.33 | 16-FEB-14:00 | 20.33 | 13.83 |
March | 0.849955E+10 | 13404.05 | 23-MAR-13:20 | 22.33 | 16.99 | 0.674747E+09 | 846.26 | 01-MAR-14:09 | 22.33 | 16.99 |
April | 0.929458E+10 | 11773.18 | 26-APR-13:10 | 26.83 | 17.07 | 0.606307E+09 | 845.71 | 13-APR-09:00 | 26.83 | 17.07 |
May | 0.724931E+10 | 8852.16 | 04-MAY-12:30 | 23.50 | 16.62 | 0.653139E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.800961E+10 | 9275.95 | 26-JUN-05:03 | 17.17 | 15.13 | 0.656896E+09 | 845.64 | 22-JUN-09:00 | 17.17 | 15.13 |
July | 0.990923E+10 | 12782.23 | 31-JUL-05:03 | 17.00 | 16.37 | 0.612271E+09 | 845.64 | 11-JUL-09:09 | 17.00 | 16.37 |
August | 0.120776E+11 | 12572.65 | 30-AUG-13:00 | 24.00 | 18.12 | 0.688399E+09 | 846.39 | 29-AUG-13:00 | 24.00 | 18.12 |
September | 0.101083E+11 | 15988.26 | 29-SEP-13:50 | 34.33 | 17.92 | 0.610694E+09 | 890.71 | 29-SEP-13:09 | 34.33 | 17.92 |
October | 0.117890E+11 | 20994.55 | 01-OCT-12:32 | 25.33 | 20.49 | 0.637139E+09 | 898.84 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.106781E+11 | 21280.47 | 19-NOV-12:12 | 26.33 | 15.30 | 0.627957E+09 | 847.39 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.113985E+11 | 20300.75 | 03-DEC-13:02 | 16.17 | 12.63 | 0.611886E+09 | 868.63 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.116974E+12 | 0.757644E+10 | ||||||||
Minimum of Months | 0.724931E+10 | 8852.16 | 16.17 | 12.63 | 0.566981E+09 | 845.64 | 17.00 | 9.22 | ||
Maximum of Months | 0.120776E+11 | 21280.47 | 34.33 | 20.49 | 0.688399E+09 | 898.84 | 34.33 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597954E+10 | 8763.50 | 18-JAN-14:50 | 23.27 | 14.80 | 0.396865E+09 | 544.99 | 10-JAN-14:09 | 23.27 | 14.80 |
February | 0.627290E+10 | 10120.84 | 22-FEB-15:30 | 16.90 | 12.24 | 0.367508E+09 | 545.04 | 01-FEB-14:09 | 16.90 | 12.24 |
March | 0.838608E+10 | 13919.15 | 24-MAR-05:03 | 12.00 | 12.00 | 0.442365E+09 | 544.99 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.110203E+11 | 20651.18 | 30-APR-16:02 | 22.00 | 15.83 | 0.395958E+09 | 545.00 | 13-APR-13:50 | 22.00 | 15.83 |
May | 0.807941E+10 | 16254.42 | 01-MAY-05:03 | 13.17 | 11.94 | 0.424581E+09 | 545.02 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.100240E+11 | 16145.41 | 26-JUN-05:03 | 17.17 | 15.13 | 0.426942E+09 | 544.96 | 22-JUN-09:00 | 17.17 | 15.13 |
July | 0.126086E+11 | 21567.61 | 23-JUL-15:02 | 24.00 | 19.32 | 0.397469E+09 | 544.96 | 11-JUL-09:09 | 24.00 | 19.32 |
August | 0.144001E+11 | 21330.18 | 13-AUG-14:12 | 24.33 | 19.41 | 0.445905E+09 | 544.95 | 01-AUG-13:09 | 24.33 | 19.41 |
September | 0.830799E+10 | 21098.67 | 04-SEP-15:52 | 20.00 | 16.16 | 0.393825E+09 | 544.96 | 01-SEP-13:09 | 20.00 | 16.16 |
October | 0.892406E+10 | 21160.50 | 01-OCT-14:32 | 23.33 | 19.66 | 0.410260E+09 | 544.99 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.802821E+10 | 16609.14 | 19-NOV-13:32 | 25.67 | 15.08 | 0.406012E+09 | 545.06 | 30-NOV-14:50 | 21.33 | 12.71 |
December | 0.854148E+10 | 16251.27 | 05-DEC-04:02 | 15.17 | 8.67 | 0.396161E+09 | 545.08 | 20-DEC-14:50 | 19.20 | 11.87 |
Annual Sum or Average | 0.110573E+12 | 0.490385E+10 | ||||||||
Minimum of Months | 0.597954E+10 | 8763.50 | 12.00 | 8.67 | 0.367508E+09 | 544.95 | 12.00 | 11.87 | ||
Maximum of Months | 0.144001E+11 | 21567.61 | 25.67 | 19.66 | 0.445905E+09 | 545.08 | 26.83 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316358E+10 | 4658.47 | 18-JAN-14:20 | 24.07 | 14.82 | 0.578403E+09 | 845.63 | 25-JAN-14:00 | 17.00 | 13.48 |
February | 0.293069E+10 | 3974.48 | 03-FEB-15:00 | 23.00 | 8.84 | 0.535190E+09 | 845.71 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.350538E+10 | 4650.82 | 23-MAR-15:20 | 21.67 | 17.34 | 0.638804E+09 | 845.63 | 09-MAR-14:30 | 21.67 | 17.34 |
April | 0.419893E+10 | 6095.73 | 26-APR-14:00 | 26.00 | 16.74 | 0.593984E+09 | 845.67 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.487253E+10 | 6561.77 | 04-MAY-14:00 | 23.00 | 16.67 | 0.650785E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.591687E+10 | 6528.96 | 29-JUN-16:00 | 23.00 | 18.43 | 0.656803E+09 | 845.62 | 22-JUN-09:00 | 23.00 | 18.43 |
July | 0.643101E+10 | 7299.82 | 01-JUL-05:03 | 17.17 | 15.80 | 0.612040E+09 | 845.63 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.650012E+10 | 7019.61 | 18-AUG-15:00 | 27.00 | 20.85 | 0.685758E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.514010E+10 | 9561.19 | 30-SEP-05:02 | 23.80 | 13.84 | 0.604834E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.513911E+10 | 8699.27 | 05-OCT-05:03 | 20.00 | 18.62 | 0.624115E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.341549E+10 | 4148.54 | 10-NOV-14:30 | 19.50 | 15.78 | 0.597312E+09 | 845.67 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.323889E+10 | 4651.52 | 05-DEC-15:00 | 25.00 | 13.22 | 0.563133E+09 | 845.65 | 04-DEC-14:09 | 25.00 | 13.22 |
Annual Sum or Average | 0.544527E+11 | 0.734116E+10 | ||||||||
Minimum of Months | 0.293069E+10 | 3974.48 | 17.17 | 8.84 | 0.535190E+09 | 845.62 | 17.00 | 8.84 | ||
Maximum of Months | 0.650012E+10 | 9561.19 | 27.00 | 20.85 | 0.685758E+09 | 845.71 | 26.83 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359293E+10 | 5233.30 | 20-JAN-09:40 | 18.33 | 14.51 | 0.274541E+09 | 521.21 | 24-JAN-11:20 | 23.00 | 14.46 |
February | 0.327006E+10 | 5095.67 | 21-FEB-10:00 | 17.00 | 11.03 | 0.250509E+09 | 521.23 | 01-FEB-11:09 | 17.00 | 11.03 |
March | 0.401897E+10 | 7456.22 | 23-MAR-09:00 | 19.00 | 14.76 | 0.299446E+09 | 521.22 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.505925E+10 | 8749.37 | 26-APR-08:50 | 22.83 | 16.63 | 0.282170E+09 | 521.26 | 13-APR-10:09 | 22.83 | 16.63 |
May | 0.516956E+10 | 7853.48 | 18-MAY-08:50 | 19.50 | 14.41 | 0.304655E+09 | 521.28 | 24-MAY-10:39 | 21.00 | 14.32 |
June | 0.593008E+10 | 12182.59 | 18-JUN-08:43 | 21.50 | 16.60 | 0.306865E+09 | 521.22 | 22-JUN-10:09 | 23.00 | 17.27 |
July | 0.688045E+10 | 16499.34 | 23-JUL-08:53 | 25.00 | 19.60 | 0.289592E+09 | 521.21 | 05-JUL-07:10 | 25.00 | 19.60 |
August | 0.724958E+10 | 14563.67 | 06-AUG-09:13 | 23.67 | 19.41 | 0.323528E+09 | 521.21 | 23-AUG-10:30 | 23.50 | 17.16 |
September | 0.539950E+10 | 12857.00 | 10-SEP-08:23 | 20.50 | 17.00 | 0.283181E+09 | 521.22 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.522488E+10 | 16331.49 | 15-OCT-09:43 | 31.33 | 16.43 | 0.293525E+09 | 521.26 | 27-OCT-10:30 | 22.00 | 13.04 |
November | 0.377898E+10 | 4893.66 | 20-NOV-09:10 | 13.50 | 12.26 | 0.278817E+09 | 521.22 | 08-NOV-11:00 | 13.50 | 12.26 |
December | 0.368820E+10 | 5365.28 | 05-DEC-09:50 | 25.67 | 12.88 | 0.265230E+09 | 521.21 | 04-DEC-13:00 | 25.67 | 12.88 |
Annual Sum or Average | 0.592624E+11 | 0.345206E+10 | ||||||||
Minimum of Months | 0.327006E+10 | 4893.66 | 13.50 | 11.03 | 0.250509E+09 | 521.21 | 13.50 | 11.03 | ||
Maximum of Months | 0.724958E+10 | 16499.34 | 31.33 | 19.60 | 0.323528E+09 | 521.28 | 25.67 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926299E+10 | 19671.82 | 22-JAN-13:53 | 18.00 | 12.36 | 0.624440E+09 | 863.49 | 18-JAN-14:09 | 18.00 | 12.36 |
February | 0.688423E+10 | 14321.43 | 22-FEB-13:50 | 19.00 | 12.78 | 0.557246E+09 | 846.11 | 16-FEB-14:00 | 19.00 | 12.78 |
March | 0.684621E+10 | 12999.36 | 23-MAR-13:30 | 22.50 | 17.06 | 0.656168E+09 | 846.01 | 10-MAR-14:39 | 22.50 | 17.06 |
April | 0.689589E+10 | 10910.01 | 26-APR-13:10 | 26.83 | 17.07 | 0.596961E+09 | 845.70 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.598754E+10 | 8193.61 | 04-MAY-12:30 | 23.50 | 16.62 | 0.643475E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.649144E+10 | 7414.96 | 30-JUN-13:10 | 23.00 | 17.85 | 0.650557E+09 | 845.64 | 22-JUN-09:00 | 23.00 | 17.85 |
July | 0.737833E+10 | 10015.14 | 31-JUL-13:10 | 27.83 | 21.13 | 0.608830E+09 | 845.65 | 07-JUL-13:09 | 27.83 | 21.13 |
August | 0.910113E+10 | 11868.97 | 30-AUG-13:00 | 24.00 | 18.12 | 0.685068E+09 | 846.10 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.915383E+10 | 15892.19 | 29-SEP-12:15 | 36.00 | 18.21 | 0.608481E+09 | 923.88 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.105331E+11 | 21513.42 | 15-OCT-13:01 | 31.83 | 15.74 | 0.634756E+09 | 920.58 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.920293E+10 | 19734.99 | 19-NOV-11:02 | 26.00 | 15.13 | 0.623062E+09 | 854.41 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.967001E+10 | 19103.60 | 25-DEC-11:53 | 23.00 | 9.63 | 0.605760E+09 | 874.13 | 19-DEC-14:09 | 23.00 | 9.63 |
Annual Sum or Average | 0.974076E+11 | 0.749480E+10 | ||||||||
Minimum of Months | 0.598754E+10 | 7414.96 | 18.00 | 9.63 | 0.557246E+09 | 845.64 | 18.00 | 9.22 | ||
Maximum of Months | 0.105331E+11 | 21513.42 | 36.00 | 21.13 | 0.685068E+09 | 923.88 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394375E+10 | 6862.21 | 18-JAN-15:00 | 23.00 | 14.79 | 0.366304E+09 | 544.96 | 18-JAN-14:39 | 23.00 | 14.79 |
February | 0.377778E+10 | 7319.92 | 22-FEB-16:20 | 15.33 | 12.12 | 0.335949E+09 | 545.02 | 01-FEB-14:09 | 15.33 | 12.12 |
March | 0.461615E+10 | 9611.53 | 23-MAR-15:50 | 21.17 | 17.23 | 0.401373E+09 | 544.97 | 09-MAR-14:09 | 21.17 | 17.23 |
April | 0.566751E+10 | 14486.67 | 30-APR-16:23 | 22.00 | 15.83 | 0.379142E+09 | 544.99 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.577486E+10 | 11411.71 | 28-MAY-17:03 | 18.67 | 14.22 | 0.411480E+09 | 545.01 | 03-MAY-13:00 | 18.67 | 14.22 |
June | 0.677201E+10 | 17180.39 | 25-JUN-16:33 | 21.00 | 16.52 | 0.418919E+09 | 544.95 | 22-JUN-09:00 | 21.00 | 16.52 |
July | 0.754007E+10 | 18121.03 | 04-JUL-16:32 | 19.67 | 15.52 | 0.393562E+09 | 544.96 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.788177E+10 | 17734.70 | 06-AUG-16:12 | 23.67 | 19.59 | 0.440930E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.615897E+10 | 11060.99 | 29-SEP-15:30 | 32.50 | 17.18 | 0.386343E+09 | 544.96 | 01-SEP-13:09 | 32.50 | 17.18 |
October | 0.579937E+10 | 17465.91 | 15-OCT-15:02 | 30.83 | 15.40 | 0.395527E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.443523E+10 | 7279.68 | 07-NOV-15:30 | 19.00 | 14.51 | 0.376032E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.419086E+10 | 7172.12 | 19-DEC-15:30 | 21.50 | 8.94 | 0.357093E+09 | 545.05 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.665583E+11 | 0.466265E+10 | ||||||||
Minimum of Months | 0.377778E+10 | 6862.21 | 15.33 | 8.94 | 0.335949E+09 | 544.95 | 15.33 | 12.12 | ||
Maximum of Months | 0.788177E+10 | 18121.03 | 32.50 | 19.59 | 0.440930E+09 | 545.05 | 32.50 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255531E+10 | 4129.65 | 18-JAN-15:00 | 23.00 | 14.79 | 0.532248E+09 | 845.62 | 18-JAN-14:30 | 23.00 | 14.79 |
February | 0.243713E+10 | 3492.13 | 01-FEB-15:00 | 19.00 | 14.76 | 0.491330E+09 | 845.69 | 01-FEB-14:20 | 19.00 | 14.76 |
March | 0.308992E+10 | 4644.32 | 23-MAR-15:20 | 21.67 | 17.34 | 0.589427E+09 | 845.62 | 10-MAR-14:00 | 21.67 | 17.34 |
April | 0.401190E+10 | 6593.96 | 26-APR-14:00 | 26.00 | 16.74 | 0.570003E+09 | 845.67 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.464257E+10 | 7111.49 | 04-MAY-14:00 | 23.00 | 16.67 | 0.629170E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.591402E+10 | 7174.78 | 30-JUN-14:00 | 23.00 | 17.85 | 0.647232E+09 | 845.62 | 22-JUN-09:00 | 23.00 | 17.85 |
July | 0.667367E+10 | 8126.84 | 19-JUL-15:00 | 27.00 | 20.17 | 0.607671E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.17 |
August | 0.666196E+10 | 7779.99 | 18-AUG-15:00 | 27.00 | 20.85 | 0.678992E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.501150E+10 | 11533.95 | 30-SEP-05:02 | 23.80 | 13.84 | 0.591244E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.485085E+10 | 9007.22 | 16-OCT-13:10 | 33.75 | 16.65 | 0.604283E+09 | 845.66 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.292737E+10 | 3764.35 | 10-NOV-14:40 | 19.33 | 15.82 | 0.550598E+09 | 845.62 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.262697E+10 | 4159.26 | 05-DEC-15:00 | 25.00 | 13.22 | 0.515028E+09 | 845.60 | 05-DEC-14:00 | 25.00 | 13.22 |
Annual Sum or Average | 0.514032E+11 | 0.700723E+10 | ||||||||
Minimum of Months | 0.243713E+10 | 3492.13 | 19.00 | 13.22 | 0.491330E+09 | 845.60 | 19.00 | 10.79 | ||
Maximum of Months | 0.667367E+10 | 11533.95 | 33.75 | 20.85 | 0.678992E+09 | 845.69 | 27.00 | 20.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288274E+10 | 3968.73 | 20-JAN-10:10 | 19.33 | 14.89 | 0.356316E+09 | 544.95 | 19-JAN-10:00 | 19.33 | 14.89 |
February | 0.258941E+10 | 3805.67 | 02-FEB-10:10 | 17.17 | 12.19 | 0.328172E+09 | 545.03 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.340071E+10 | 6532.91 | 23-MAR-09:40 | 21.00 | 15.89 | 0.393029E+09 | 544.96 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.474321E+10 | 8262.93 | 26-APR-09:30 | 23.50 | 16.85 | 0.380529E+09 | 545.00 | 13-APR-09:00 | 23.50 | 16.85 |
May | 0.488610E+10 | 7479.56 | 04-MAY-09:30 | 21.00 | 15.49 | 0.409721E+09 | 545.00 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.593232E+10 | 9080.93 | 25-JUN-09:23 | 22.50 | 16.84 | 0.415645E+09 | 544.96 | 22-JUN-09:00 | 22.50 | 16.84 |
July | 0.706879E+10 | 12884.63 | 04-JUL-09:02 | 22.00 | 15.93 | 0.393099E+09 | 544.96 | 17-JUL-09:39 | 22.33 | 17.42 |
August | 0.739078E+10 | 11215.95 | 13-AUG-09:23 | 24.00 | 19.61 | 0.440496E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.524075E+10 | 9154.15 | 30-SEP-05:02 | 23.80 | 13.84 | 0.382665E+09 | 544.96 | 12-SEP-09:00 | 23.80 | 13.84 |
October | 0.488377E+10 | 16418.26 | 15-OCT-09:13 | 32.33 | 16.14 | 0.395105E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.314245E+10 | 4041.60 | 19-NOV-13:22 | 26.00 | 15.06 | 0.364515E+09 | 544.94 | 01-NOV-09:50 | 26.00 | 15.06 |
December | 0.292443E+10 | 4132.59 | 05-DEC-10:00 | 26.00 | 13.09 | 0.343633E+09 | 544.96 | 05-DEC-10:39 | 24.67 | 13.14 |
Annual Sum or Average | 0.550854E+11 | 0.460293E+10 | ||||||||
Minimum of Months | 0.258941E+10 | 3805.67 | 17.17 | 12.19 | 0.328172E+09 | 544.94 | 17.17 | 11.71 | ||
Maximum of Months | 0.739078E+10 | 16418.26 | 32.33 | 19.61 | 0.440496E+09 | 545.03 | 26.00 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.777129E+10 | 18682.54 | 22-JAN-14:02 | 17.83 | 12.38 | 0.605623E+09 | 846.42 | 20-JAN-14:09 | 17.83 | 12.38 |
February | 0.577041E+10 | 13932.23 | 22-FEB-14:10 | 18.80 | 12.73 | 0.533906E+09 | 846.23 | 01-FEB-14:20 | 18.80 | 12.73 |
March | 0.601256E+10 | 13223.01 | 23-MAR-14:00 | 23.00 | 17.27 | 0.622320E+09 | 845.98 | 22-MAR-13:50 | 23.00 | 17.27 |
April | 0.657579E+10 | 11515.49 | 26-APR-13:10 | 26.83 | 17.07 | 0.579794E+09 | 845.70 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.573001E+10 | 8711.30 | 03-MAY-13:10 | 23.83 | 15.35 | 0.620787E+09 | 845.72 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.656694E+10 | 8104.86 | 30-JUN-13:30 | 23.00 | 17.85 | 0.636547E+09 | 845.64 | 07-JUN-13:00 | 23.00 | 17.85 |
July | 0.768256E+10 | 10923.44 | 31-JUL-13:10 | 27.83 | 21.13 | 0.602094E+09 | 845.65 | 07-JUL-13:09 | 27.83 | 21.13 |
August | 0.932764E+10 | 12486.67 | 30-AUG-13:10 | 23.83 | 18.18 | 0.678088E+09 | 845.65 | 29-AUG-13:09 | 23.83 | 18.18 |
September | 0.896190E+10 | 16948.39 | 29-SEP-12:05 | 36.00 | 18.21 | 0.599203E+09 | 948.12 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.100472E+11 | 22587.73 | 15-OCT-15:52 | 30.00 | 14.89 | 0.622847E+09 | 906.49 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.788533E+10 | 22357.69 | 19-NOV-13:22 | 26.00 | 15.06 | 0.606833E+09 | 846.42 | 28-NOV-14:50 | 23.33 | 10.84 |
December | 0.807459E+10 | 16556.66 | 19-DEC-13:20 | 25.00 | 11.01 | 0.587621E+09 | 846.20 | 20-DEC-14:50 | 19.20 | 11.87 |
Annual Sum or Average | 0.904063E+11 | 0.729566E+10 | ||||||||
Minimum of Months | 0.573001E+10 | 8104.86 | 17.83 | 11.01 | 0.533906E+09 | 845.64 | 17.83 | 10.84 | ||
Maximum of Months | 0.100472E+11 | 22587.73 | 36.00 | 21.13 | 0.678088E+09 | 948.12 | 35.33 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331199E+10 | 6570.33 | 18-JAN-15:00 | 23.00 | 14.79 | 0.347453E+09 | 544.96 | 18-JAN-14:39 | 23.00 | 14.79 |
February | 0.319995E+10 | 6971.48 | 22-FEB-16:20 | 15.33 | 12.12 | 0.317486E+09 | 545.04 | 01-FEB-14:09 | 15.33 | 12.12 |
March | 0.413045E+10 | 9687.98 | 23-MAR-15:50 | 21.17 | 17.23 | 0.379284E+09 | 544.96 | 10-MAR-14:00 | 21.17 | 17.23 |
April | 0.549759E+10 | 11046.33 | 26-APR-16:00 | 22.00 | 16.41 | 0.365080E+09 | 544.99 | 13-APR-13:00 | 22.00 | 16.41 |
May | 0.561322E+10 | 10849.74 | 28-MAY-17:03 | 18.67 | 14.22 | 0.396451E+09 | 545.01 | 03-MAY-13:00 | 18.67 | 14.22 |
June | 0.682708E+10 | 17114.83 | 25-JUN-16:42 | 21.00 | 16.52 | 0.409902E+09 | 544.95 | 07-JUN-13:00 | 21.00 | 16.52 |
July | 0.774465E+10 | 19957.03 | 09-JUL-16:02 | 20.67 | 15.87 | 0.389415E+09 | 544.96 | 07-JUL-13:09 | 20.67 | 15.87 |
August | 0.801932E+10 | 13788.21 | 20-AUG-17:33 | 19.60 | 16.68 | 0.435176E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.608451E+10 | 12328.96 | 30-SEP-05:02 | 23.80 | 13.84 | 0.376107E+09 | 544.96 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.557568E+10 | 20296.35 | 15-OCT-15:52 | 30.00 | 14.89 | 0.382850E+09 | 544.97 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.384136E+10 | 6963.45 | 10-NOV-14:50 | 19.17 | 15.85 | 0.357191E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.348480E+10 | 6928.82 | 19-DEC-15:30 | 21.50 | 8.94 | 0.337588E+09 | 545.04 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.633306E+11 | 0.449398E+10 | ||||||||
Minimum of Months | 0.319995E+10 | 6570.33 | 15.33 | 8.94 | 0.317486E+09 | 544.95 | 15.33 | 11.58 | ||
Maximum of Months | 0.801932E+10 | 20296.35 | 30.00 | 17.23 | 0.435176E+09 | 545.04 | 24.00 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464773E+10 | 8328.31 | 17-JAN-06:15 | 15.67 | 13.46 | 0.00 | 0.00 | 01-JAN-00:10 | 15.67 | 13.46 |
February | 0.422456E+10 | 7140.37 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 6.97 |
March | 0.507629E+10 | 7070.04 | 20-MAR-05:15 | 10.67 | 10.47 | 0.00 | 0.00 | 01-MAR-00:10 | 10.67 | 10.47 |
April | 0.635894E+10 | 8467.78 | 11-APR-05:13 | 12.00 | 12.00 | 0.00 | 0.00 | 01-APR-00:10 | 12.00 | 12.00 |
May | 0.571216E+10 | 9646.56 | 01-MAY-05:13 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.698284E+10 | 8409.33 | 19-JUN-05:13 | 16.33 | 14.87 | 0.00 | 0.00 | 01-JUN-00:10 | 16.33 | 14.87 |
July | 0.801762E+10 | 9439.67 | 05-JUL-05:15 | 17.00 | 14.32 | 0.00 | 0.00 | 01-JUL-00:10 | 17.00 | 14.32 |
August | 0.893186E+10 | 10044.23 | 07-AUG-05:15 | 18.00 | 17.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.00 | 17.96 |
September | 0.668793E+10 | 10460.39 | 05-SEP-05:13 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.00 | 14.76 |
October | 0.726862E+10 | 10673.65 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.584483E+10 | 8485.86 | 21-NOV-06:13 | 13.00 | 11.87 | 0.00 | 0.00 | 01-NOV-00:10 | 13.00 | 11.87 |
December | 0.574850E+10 | 9100.96 | 26-DEC-06:15 | 7.00 | 1.09 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 1.09 |
Annual Sum or Average | 0.755019E+11 | 0.00 | ||||||||
Minimum of Months | 0.422456E+10 | 7070.04 | 7.00 | 1.09 | 0.00 | 0.00 | 7.00 | 1.09 | ||
Maximum of Months | 0.893186E+10 | 10673.65 | 19.07 | 17.96 | 0.00 | 0.00 | 19.07 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250163E+10 | 4871.99 | 21-JAN-06:13 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 13.00 |
February | 0.231309E+10 | 4832.21 | 04-FEB-06:08 | 5.67 | 0.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.67 | 0.59 |
March | 0.250387E+10 | 4994.74 | 23-MAR-05:13 | 10.33 | 9.39 | 0.00 | 0.00 | 01-MAR-00:10 | 10.33 | 9.39 |
April | 0.363080E+10 | 6541.20 | 27-APR-05:13 | 15.00 | 14.41 | 0.00 | 0.00 | 01-APR-00:10 | 15.00 | 14.41 |
May | 0.389755E+10 | 5571.45 | 01-MAY-05:13 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.488372E+10 | 6500.28 | 22-JUN-05:13 | 14.00 | 12.84 | 0.00 | 0.00 | 01-JUN-00:10 | 14.00 | 12.84 |
July | 0.568080E+10 | 6671.30 | 01-JUL-05:13 | 17.33 | 15.87 | 0.00 | 0.00 | 01-JUL-00:10 | 17.33 | 15.87 |
August | 0.618384E+10 | 6523.87 | 31-AUG-05:13 | 15.33 | 14.60 | 0.00 | 0.00 | 01-AUG-00:10 | 15.33 | 14.60 |
September | 0.499107E+10 | 6111.82 | 26-SEP-05:02 | 15.83 | 14.71 | 0.00 | 0.00 | 01-SEP-00:10 | 15.83 | 14.71 |
October | 0.507541E+10 | 7933.24 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.320407E+10 | 5053.74 | 13-NOV-06:15 | 11.33 | 10.63 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 10.63 |
December | 0.285671E+10 | 4689.93 | 02-DEC-06:10 | 10.00 | 10.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10.00 | 10.00 |
Annual Sum or Average | 0.477226E+11 | 0.00 | ||||||||
Minimum of Months | 0.231309E+10 | 4689.93 | 5.67 | 0.59 | 0.00 | 0.00 | 5.67 | 0.59 | ||
Maximum of Months | 0.618384E+10 | 7933.24 | 19.07 | 17.72 | 0.00 | 0.00 | 19.07 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204726E+10 | 8849.86 | 18-JAN-14:40 | 23.53 | 14.82 | 0.00 | 0.00 | 01-JAN-00:10 | 23.53 | 14.82 |
February | 0.205526E+10 | 8818.12 | 01-FEB-14:00 | 19.00 | 15.88 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.88 |
March | 0.320132E+10 | 12845.84 | 23-MAR-14:40 | 22.33 | 17.37 | 0.00 | 0.00 | 01-MAR-00:10 | 22.33 | 17.37 |
April | 0.640337E+10 | 17206.28 | 26-APR-13:40 | 26.33 | 16.87 | 0.00 | 0.00 | 01-APR-00:10 | 26.33 | 16.87 |
May | 0.651560E+10 | 16236.48 | 03-MAY-13:10 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.892611E+10 | 16336.37 | 30-JUN-13:10 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.110912E+11 | 18429.59 | 19-JUL-13:10 | 27.00 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.29 |
August | 0.113508E+11 | 17900.19 | 14-AUG-12:10 | 26.83 | 20.78 | 0.00 | 0.00 | 01-AUG-00:10 | 26.83 | 20.78 |
September | 0.749560E+10 | 19724.66 | 29-SEP-12:10 | 36.00 | 18.21 | 0.00 | 0.00 | 01-SEP-00:10 | 36.00 | 18.21 |
October | 0.623823E+10 | 18398.64 | 16-OCT-13:10 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.254935E+10 | 8483.97 | 10-NOV-14:00 | 20.00 | 15.64 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 15.64 |
December | 0.198644E+10 | 8074.10 | 19-DEC-13:10 | 25.50 | 11.30 | 0.00 | 0.00 | 01-DEC-00:10 | 25.50 | 11.30 |
Annual Sum or Average | 0.698605E+11 | 0.00 | ||||||||
Minimum of Months | 0.198644E+10 | 8074.10 | 19.00 | 11.30 | 0.00 | 0.00 | 19.00 | 11.30 | ||
Maximum of Months | 0.113508E+11 | 19724.66 | 36.00 | 20.78 | 0.00 | 0.00 | 36.00 | 20.78 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402811E+10 | 2045.85 | 30-JAN-16:40 | 14.00 | 11.39 | 95232975.30 | 126.84 | 20-JAN-14:00 | 14.00 | 11.39 |
February | 0.831607E+10 | 4034.44 | 22-FEB-17:00 | 14.00 | 12.23 | 86400313.34 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.143901E+11 | 7024.47 | 31-MAR-24:00 | 9.70 | 9.11 | 0.103240E+09 | 126.83 | 24-MAR-09:09 | 9.70 | 9.11 |
April | 0.189624E+11 | 7812.54 | 30-APR-17:14 | 21.33 | 15.80 | 91606341.52 | 126.83 | 05-APR-09:09 | 21.33 | 15.80 |
May | 0.435023E+10 | 3327.86 | 31-MAY-24:00 | 13.10 | 11.97 | 99240377.43 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.928852E+10 | 5366.83 | 30-JUN-24:00 | 16.40 | 15.78 | 98967684.75 | 126.85 | 28-JUN-13:39 | 16.40 | 15.78 |
July | 0.146803E+11 | 7236.87 | 31-JUL-23:45 | 18.15 | 17.39 | 91888179.90 | 126.84 | 20-JUL-09:09 | 18.15 | 17.39 |
August | 0.197038E+11 | 7895.55 | 06-AUG-17:50 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.435795E+10 | 3524.20 | 30-SEP-24:00 | 18.40 | 17.30 | 91616509.79 | 126.85 | 25-SEP-13:00 | 18.40 | 17.30 |
October | 0.957069E+10 | 5332.72 | 31-OCT-24:00 | 14.90 | 11.04 | 95236607.25 | 126.85 | 04-OCT-13:00 | 14.90 | 11.04 |
November | 0.140404E+11 | 5900.41 | 07-NOV-16:20 | 18.33 | 14.34 | 94302726.58 | 126.83 | 20-NOV-14:30 | 18.00 | 14.97 |
December | 0.195125E+11 | 7838.88 | 25-DEC-16:10 | 20.17 | 9.85 | 92192022.13 | 136.22 | 19-DEC-10:00 | 20.17 | 9.85 |
Annual Sum or Average | 0.141201E+12 | 0.114316E+10 | ||||||||
Minimum of Months | 0.402811E+10 | 2045.85 | 9.70 | 9.11 | 86400313.34 | 126.83 | 9.70 | 9.11 | ||
Maximum of Months | 0.197038E+11 | 7895.55 | 21.33 | 19.00 | 0.103240E+09 | 136.22 | 21.33 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284880E+10 | 1861.99 | 30-JAN-16:50 | 14.00 | 11.30 | 95232778.92 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.708930E+10 | 3767.85 | 22-FEB-17:00 | 14.00 | 12.23 | 86400043.35 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.128784E+11 | 6267.75 | 31-MAR-23:40 | 9.83 | 9.24 | 0.103240E+09 | 126.83 | 24-MAR-13:00 | 9.83 | 9.24 |
April | 0.176505E+11 | 7288.86 | 27-APR-17:00 | 17.00 | 14.51 | 91606503.87 | 126.83 | 05-APR-09:09 | 17.00 | 14.51 |
May | 0.365852E+10 | 2991.97 | 31-MAY-24:00 | 13.10 | 11.97 | 99239939.58 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.854198E+10 | 5072.43 | 30-JUN-24:00 | 16.40 | 15.78 | 98967027.55 | 126.84 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.138691E+11 | 6925.30 | 31-JUL-23:53 | 18.10 | 17.45 | 91888444.22 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.186787E+11 | 7350.05 | 06-AUG-17:50 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.377951E+10 | 3378.07 | 30-SEP-24:00 | 18.40 | 17.30 | 91613808.10 | 126.85 | 06-SEP-13:00 | 18.40 | 17.30 |
October | 0.865170E+10 | 4921.29 | 31-OCT-24:00 | 14.90 | 11.04 | 95236058.82 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.126321E+11 | 5539.36 | 07-NOV-16:20 | 18.33 | 14.34 | 94302758.92 | 126.83 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.176831E+11 | 7326.15 | 18-DEC-16:20 | 20.33 | 7.98 | 91991959.44 | 132.37 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.127962E+12 | 0.114296E+10 | ||||||||
Minimum of Months | 0.284880E+10 | 1861.99 | 9.83 | 7.98 | 86400043.35 | 126.83 | 9.83 | 9.24 | ||
Maximum of Months | 0.186787E+11 | 7350.05 | 21.33 | 19.00 | 0.103240E+09 | 132.37 | 22.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165907E+10 | 1821.74 | 18-JAN-16:10 | 21.83 | 15.33 | 95103140.10 | 126.84 | 20-JAN-14:00 | 17.00 | 14.51 |
February | 0.598992E+10 | 3762.00 | 22-FEB-17:00 | 14.00 | 12.23 | 86400003.61 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.118498E+11 | 5846.27 | 31-MAR-23:20 | 9.97 | 9.37 | 0.103240E+09 | 126.83 | 24-MAR-13:00 | 9.97 | 9.37 |
April | 0.171061E+11 | 7364.41 | 26-APR-16:00 | 22.00 | 16.41 | 91606722.70 | 126.83 | 05-APR-09:09 | 22.00 | 16.41 |
May | 0.310882E+10 | 2672.04 | 31-MAY-24:00 | 13.10 | 11.97 | 99240064.07 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.828705E+10 | 4932.26 | 30-JUN-24:00 | 16.40 | 15.78 | 98967360.75 | 126.85 | 28-JUN-13:50 | 16.40 | 15.78 |
July | 0.137604E+11 | 6814.40 | 31-JUL-24:00 | 18.10 | 17.45 | 91888730.47 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.185367E+11 | 7499.12 | 20-AUG-17:30 | 19.90 | 16.77 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 19.90 | 16.77 |
September | 0.343987E+10 | 3304.93 | 30-SEP-24:00 | 18.40 | 17.30 | 91615002.79 | 126.85 | 25-SEP-13:00 | 18.40 | 17.30 |
October | 0.812787E+10 | 4667.61 | 31-OCT-23:50 | 15.02 | 11.31 | 95236131.77 | 126.85 | 05-OCT-13:00 | 15.02 | 11.31 |
November | 0.115956E+11 | 5518.84 | 10-NOV-16:20 | 17.67 | 15.55 | 94302825.37 | 126.83 | 10-NOV-14:00 | 17.67 | 15.55 |
December | 0.163880E+11 | 7327.28 | 19-DEC-16:30 | 20.00 | 7.77 | 91901252.01 | 128.55 | 19-DEC-14:09 | 20.00 | 7.77 |
Annual Sum or Average | 0.119849E+12 | 0.114274E+10 | ||||||||
Minimum of Months | 0.165907E+10 | 1821.74 | 9.97 | 7.77 | 86400003.61 | 126.83 | 9.97 | 7.77 | ||
Maximum of Months | 0.185367E+11 | 7499.12 | 22.00 | 17.45 | 0.103240E+09 | 128.55 | 22.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240120E+12 | 92704.43 | 18-JAN-17:00 | 21.00 | 15.00 | 0.206163E+10 | 2747.17 | 04-JAN-10:00 | 21.00 | 15.00 |
February | 0.436154E+12 | 183710.63 | 21-FEB-17:00 | 16.00 | 13.03 | 0.187047E+10 | 2748.56 | 06-FEB-10:09 | 16.00 | 13.03 |
March | 0.728835E+12 | 358135.06 | 31-MAR-24:00 | 9.70 | 9.11 | 0.223483E+10 | 2745.57 | 24-MAR-09:09 | 9.70 | 9.11 |
April | 0.942073E+12 | 367252.46 | 27-APR-16:00 | 18.00 | 14.37 | 0.198778E+10 | 2989.46 | 26-APR-13:39 | 18.00 | 14.37 |
May | 0.240166E+12 | 175388.57 | 31-MAY-24:00 | 13.10 | 11.97 | 0.214833E+10 | 2745.98 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.468588E+12 | 267121.52 | 30-JUN-24:00 | 16.40 | 15.78 | 0.214240E+10 | 2746.00 | 28-JUN-13:39 | 16.40 | 15.78 |
July | 0.730131E+12 | 359211.30 | 31-JUL-23:53 | 18.10 | 17.45 | 0.198911E+10 | 2745.67 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.974728E+12 | 367697.22 | 25-AUG-16:00 | 21.00 | 17.71 | 0.228840E+10 | 3080.24 | 14-AUG-13:09 | 21.00 | 17.71 |
September | 0.234134E+12 | 175694.97 | 30-SEP-24:00 | 18.40 | 17.30 | 0.198339E+10 | 2746.60 | 22-SEP-13:50 | 18.40 | 17.30 |
October | 0.486337E+12 | 267929.38 | 31-OCT-24:00 | 14.90 | 11.04 | 0.206170E+10 | 2746.96 | 27-OCT-09:09 | 14.90 | 11.04 |
November | 0.707609E+12 | 276274.68 | 13-NOV-17:00 | 15.00 | 13.80 | 0.204168E+10 | 2748.54 | 29-NOV-10:39 | 21.33 | 8.11 |
December | 0.975707E+12 | 369381.26 | 19-DEC-17:05 | 18.50 | 7.09 | 0.203764E+10 | 3263.11 | 05-DEC-10:20 | 18.50 | 7.09 |
Annual Sum or Average | 0.716458E+13 | 0.248474E+11 | ||||||||
Minimum of Months | 0.234134E+12 | 92704.43 | 9.70 | 7.09 | 0.187047E+10 | 2745.57 | 9.70 | 7.09 | ||
Maximum of Months | 0.975707E+12 | 369381.26 | 21.00 | 17.71 | 0.228840E+10 | 3263.11 | 21.33 | 17.71 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527732E+09 | 12418.05 | 02-JAN-04:17 | 10.33 |
February | 0.222343E+09 | 12548.79 | 27-FEB-04:05 | 11.00 |
March | 0.171875E+09 | 12394.89 | 01-MAR-05:05 | 7.00 |
April | 0.215727E+09 | 14122.50 | 04-APR-03:53 | 9.00 |
May | 0.247579E+09 | 12554.08 | 15-MAY-03:05 | 9.00 |
June | 0.190008E+09 | 13954.02 | 27-JUN-03:53 | 17.00 |
July | 0.234104E+09 | 14444.74 | 06-JUL-03:53 | 14.00 |
August | 0.242962E+09 | 13969.67 | 21-AUG-02:62 | 17.00 |
September | 0.371143E+09 | 14492.12 | 30-SEP-16:03 | 28.50 |
October | 0.528241E+09 | 18072.20 | 14-OCT-16:03 | 31.17 |
November | 0.449628E+09 | 14432.94 | 12-NOV-16:53 | 15.00 |
December | 0.471162E+09 | 14259.96 | 06-DEC-04:53 | 14.00 |
Annual Sum or Average | 0.387251E+10 | |||
Minimum of Months | 0.171875E+09 | 12394.89 | 7.00 | |
Maximum of Months | 0.528241E+09 | 18072.20 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171867E+09 | 65157.36 | 02-JAN-05:01 | 11.00 |
February | 5536643.21 | 36910.95 | 27-FEB-06:03 | 11.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1463221.87 | 9754.81 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.178867E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 0.171867E+09 | 65157.36 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43469827.73 | 10010.22 | 02-JAN-05:01 | 11.00 |
February | 817567.95 | 2765.85 | 27-FEB-06:03 | 11.00 |
March | 21159964.03 | 9936.97 | 30-MAR-04:01 | 4.48 |
April | 390154.84 | 2601.03 | 01-APR-05:03 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 710639.54 | 5659.37 | 24-NOV-06:02 | 8.92 |
December | 5838386.00 | 9413.24 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 72386540.08 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 43469827.73 | 10010.22 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17148342.22 | 9771.08 | 09-JAN-06:01 | 2.17 |
February | 489822.36 | 1542.11 | 28-FEB-06:02 | 10.17 |
March | 15506034.49 | 10133.24 | 30-MAR-04:01 | 4.48 |
April | 596758.65 | 2575.61 | 01-APR-05:03 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 115796.27 | 964.97 | 24-NOV-06:02 | 8.92 |
December | 4444938.39 | 8318.96 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 38301692.37 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 17148342.22 | 10133.24 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4045723.25 | 12897.97 | 02-JAN-06:01 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 14496030.16 | 12792.64 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1249567.86 | 5823.23 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 19791321.27 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 14496030.16 | 12897.97 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7573308.17 | 9074.93 | 09-JAN-06:01 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 4856077.31 | 8081.80 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 909666.18 | 4129.62 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 13339051.67 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 7573308.17 | 9074.93 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655614E+09 | 13392.99 | 02-JAN-04:02 | 10.17 |
February | 0.329859E+09 | 12267.44 | 06-FEB-05:01 | 8.17 |
March | 0.425565E+09 | 12577.09 | 30-MAR-04:01 | 4.48 |
April | 42577670.97 | 11656.55 | 01-APR-04:03 | 8.00 |
May | 7837671.95 | 11081.26 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 16067173.34 | 11259.80 | 30-OCT-05:02 | 10.83 |
November | 0.201891E+09 | 12284.77 | 24-NOV-05:01 | 8.17 |
December | 0.448847E+09 | 12436.82 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.212826E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.655614E+09 | 13392.99 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283600E+09 | 13117.11 | 02-JAN-04:02 | 10.17 |
February | 0.157776E+09 | 12008.67 | 27-FEB-05:02 | 11.00 |
March | 0.202457E+09 | 12574.35 | 30-MAR-04:01 | 4.48 |
April | 19435119.31 | 10541.32 | 18-APR-05:02 | 11.17 |
May | 3239199.45 | 9178.03 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 5368958.69 | 8726.75 | 30-OCT-05:02 | 10.83 |
November | 75021471.54 | 12018.15 | 24-NOV-05:01 | 8.17 |
December | 0.187177E+09 | 12447.48 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.934075E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.283600E+09 | 13117.11 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220474E+09 | 16830.64 | 02-JAN-04:02 | 10.17 |
February | 0.136744E+09 | 15140.92 | 27-FEB-05:02 | 11.00 |
March | 0.282819E+09 | 16223.24 | 30-MAR-04:01 | 4.48 |
April | 34119011.89 | 14280.44 | 18-APR-05:02 | 11.17 |
May | 13761519.01 | 14379.21 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 221663.64 | 1477.76 | 12-OCT-05:03 | 9.00 |
November | 31837998.41 | 14288.25 | 06-NOV-06:02 | 10.17 |
December | 0.107202E+09 | 15842.51 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.827180E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.282819E+09 | 16830.64 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217857E+09 | 13399.49 | 02-JAN-05:01 | 11.00 |
February | 76009596.98 | 10570.07 | 28-FEB-06:02 | 10.17 |
March | 0.129863E+09 | 13272.33 | 30-MAR-04:01 | 4.48 |
April | 15116794.41 | 8890.65 | 01-APR-05:03 | 7.83 |
May | 2547470.86 | 8350.62 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 47903.53 | 260.74 | 28-OCT-05:03 | 9.33 |
November | 32798122.15 | 10767.78 | 24-NOV-05:01 | 8.17 |
December | 0.105066E+09 | 12983.49 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.579306E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.217857E+09 | 13399.49 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67628152.87 | 10300.88 | 02-JAN-04:02 | 10.17 |
February | 84621616.15 | 10693.55 | 13-FEB-04:03 | 13.83 |
March | 0.100374E+09 | 11165.41 | 30-MAR-04:01 | 4.48 |
April | 0.136227E+09 | 10962.73 | 17-APR-03:02 | 10.00 |
May | 78894177.22 | 8525.12 | 08-MAY-03:02 | 14.00 |
June | 62737119.02 | 9225.30 | 12-JUN-03:02 | 13.00 |
July | 0.112791E+09 | 7937.58 | 15-JUL-03:02 | 17.83 |
August | 0.120541E+09 | 8647.28 | 23-AUG-03:02 | 15.37 |
September | 65457660.53 | 8857.74 | 25-SEP-03:02 | 17.00 |
October | 87778884.46 | 9788.81 | 23-OCT-03:02 | 17.00 |
November | 0.112860E+09 | 10345.84 | 24-NOV-04:03 | 7.17 |
December | 0.122223E+09 | 12549.43 | 18-DEC-04:02 | 18.00 |
Annual Sum or Average | 0.115213E+10 | |||
Minimum of Months | 62737119.02 | 7937.58 | 4.48 | |
Maximum of Months | 0.136227E+09 | 12549.43 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154552E+09 | 7820.48 | 04-JAN-06:03 | 7.17 |
February | 68889780.91 | 8165.40 | 28-FEB-06:02 | 10.17 |
March | 73842338.55 | 8387.51 | 28-MAR-05:02 | 11.83 |
April | 56557908.25 | 7063.06 | 18-APR-05:02 | 11.17 |
May | 58625193.79 | 7169.82 | 08-MAY-04:03 | 14.00 |
June | 46693741.11 | 6205.52 | 13-JUN-04:03 | 11.00 |
July | 46594086.41 | 5965.21 | 12-JUL-04:03 | 17.00 |
August | 45278260.81 | 5854.68 | 28-AUG-03:02 | 14.00 |
September | 52889016.81 | 6907.61 | 25-SEP-03:02 | 17.00 |
October | 62326287.29 | 6620.93 | 02-OCT-03:02 | 19.00 |
November | 52253478.11 | 7642.64 | 13-NOV-04:02 | 11.83 |
December | 52514250.13 | 7610.60 | 18-DEC-06:03 | 17.00 |
Annual Sum or Average | 0.771016E+09 | |||
Minimum of Months | 45278260.81 | 5854.68 | 7.17 | |
Maximum of Months | 0.154552E+09 | 8387.51 | 19.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202411E+10 | 12030.13 | 09-JAN-06:03 | 2.17 |
February | 0.143211E+10 | 10104.58 | 16-FEB-06:03 | 11.98 |
March | 0.166438E+10 | 14681.07 | 24-MAR-05:03 | 12.00 |
April | 0.583269E+09 | 17916.05 | 25-APR-05:03 | 11.33 |
May | 0.444400E+09 | 19160.14 | 30-MAY-05:03 | 11.00 |
June | 0.182766E+09 | 18922.42 | 05-JUN-05:03 | 12.17 |
July | 0.103766E+09 | 16072.32 | 06-JUL-05:03 | 14.33 |
August | 0.113572E+09 | 16020.45 | 31-AUG-05:02 | 15.17 |
September | 0.221590E+09 | 16174.46 | 12-SEP-05:03 | 15.00 |
October | 0.533674E+09 | 16618.02 | 18-OCT-05:03 | 15.00 |
November | 0.116792E+10 | 15740.62 | 01-NOV-05:03 | 12.83 |
December | 0.181167E+10 | 17066.21 | 06-DEC-06:03 | 12.33 |
Annual Sum or Average | 0.102832E+11 | |||
Minimum of Months | 0.103766E+09 | 10104.58 | 2.17 | |
Maximum of Months | 0.202411E+10 | 19160.14 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128322E+09 | 541.29 | 08-JAN-07:00 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 918937.26 | 359.19 | 14-MAY-07:35 | 14.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.129241E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.128322E+09 | 541.29 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196603E+11 | 20573.73 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.178333E+11 | 20573.73 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.211910E+11 | 20573.73 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.189279E+11 | 20573.73 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.204256E+11 | 20573.73 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.203269E+11 | 20573.73 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.190266E+11 | 20573.73 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.211910E+11 | 20573.73 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.189279E+11 | 20573.73 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.196603E+11 | 20573.73 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.194299E+11 | 20573.73 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.190266E+11 | 20573.73 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.235627E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.178333E+11 | 20573.73 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.211910E+11 | 20573.73 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554336E+10 | 5800.91 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.502824E+10 | 5800.91 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.597494E+10 | 5800.91 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.533685E+10 | 5800.91 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.575915E+10 | 5800.91 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.573131E+10 | 5800.91 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.536469E+10 | 5800.91 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.597494E+10 | 5800.91 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.533685E+10 | 5800.91 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.554336E+10 | 5800.91 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.547839E+10 | 5800.91 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.536469E+10 | 5800.91 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.664368E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.502824E+10 | 5800.91 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.597494E+10 | 5800.91 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.204256E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.203269E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.194299E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.235627E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 491476.83 | 0.519750E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81550.31 | 0.606496E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6404.13 | 0.644015E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 622869.85 | 0.373473E+09 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.77 | 0.443286E+09 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50738.04 | 0.237088E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3492589.11 | 0.164388E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3667314.46 | 0.204201E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5763898.03 | 0.206212E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21110959.59 | 0.330666E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1262122.20 | 0.491101E+09 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354069.55 | 0.538222E+09 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36904083.88 | 0.475890E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.77 | 0.164388E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21110959.59 | 0.644015E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386654.74 | 0.345741E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54365.53 | 0.396521E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20114.50 | 0.419344E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 294849.27 | 0.241492E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 | 0.294059E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33813.59 | 0.153642E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2271836.95 | 0.104808E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2487884.13 | 0.127163E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3849815.60 | 0.136230E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13698375.95 | 0.213983E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 788008.64 | 0.319168E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 289032.84 | 0.345807E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24174811.17 | 0.309796E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 | 0.104808E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13698375.95 | 0.419344E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409744.69 | 0.538909E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81513.59 | 0.617973E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.71 | 0.642151E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 412986.51 | 0.375693E+09 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.20 | 0.430515E+09 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50739.90 | 0.227363E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3635348.71 | 0.158322E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3562720.43 | 0.204106E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5707822.67 | 0.220651E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18342634.89 | 0.352819E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174103.87 | 0.514178E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 305107.80 | 0.564040E+09 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32682968.97 | 0.484672E+10 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.20 | 0.158322E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18342634.89 | 0.642151E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 324159.26 | 0.367916E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54368.06 | 0.445921E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.86 | 0.475962E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 290250.00 | 0.288583E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 | 0.322608E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33819.75 | 0.176603E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2305857.42 | 0.129446E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2365503.44 | 0.163318E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3834407.39 | 0.155532E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13234104.16 | 0.251066E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432188.44 | 0.369361E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 220171.37 | 0.412117E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23094995.85 | 0.355843E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 | 0.129446E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13234104.16 | 0.475962E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2038192.23 | 0.104711E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171984.70 | 0.121597E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407591.09 | 0.132257E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2763169.37 | 0.786733E+09 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959374E+09 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94915.93 | 0.522526E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8381565.73 | 0.372201E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8747371.11 | 0.462264E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13283724.13 | 0.443773E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50220823.11 | 0.687051E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5894051.47 | 0.100163E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2736770.75 | 0.106375E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94740159.62 | 0.988496E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372201E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50220823.11 | 0.132257E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1372820.52 | 0.714919E+09 |
February | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131455.92 | 0.823798E+09 |
March | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88281.18 | 0.896233E+09 |
April | 0.688021E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 614567.08 | 0.552913E+09 |
May | 0.744847E+09 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658013E+09 |
June | 0.742030E+09 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63247.40 | 0.352231E+09 |
July | 0.690839E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5026420.40 | 0.263387E+09 |
August | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5224680.75 | 0.325524E+09 |
September | 0.688021E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8870582.88 | 0.307029E+09 |
October | 0.715730E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31043980.90 | 0.468232E+09 |
November | 0.708685E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2710113.32 | 0.679616E+09 |
December | 0.690839E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491752.98 | 0.723092E+09 |
Annual Sum or Average | 0.858171E+10 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56637903.33 | 0.676499E+10 |
Minimum of Months | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263387E+09 |
Maximum of Months | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31043980.90 | 0.896233E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 845429.31 | 0.120841E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171961.27 | 0.135987E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140818E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1207298.05 | 0.848451E+09 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962415E+09 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94917.87 | 0.507667E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8724566.19 | 0.368628E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7848354.69 | 0.487567E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13000376.99 | 0.510302E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41563434.75 | 0.802592E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 350470.17 | 0.115562E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 631031.33 | 0.125598E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74437840.63 | 0.108757E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368628E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41563434.75 | 0.140818E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220248.83 | 0.730803E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 200487.74 | 0.853124E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249033.19 | 0.918852E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1844759.73 | 0.585486E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693203E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63274.82 | 0.374275E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6338785.05 | 0.285446E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6315216.87 | 0.353439E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8962774.33 | 0.334336E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32903427.97 | 0.497739E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3511249.54 | 0.708607E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2058006.36 | 0.754140E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63667264.42 | 0.708945E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285446E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32903427.97 | 0.918852E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4763698.54 | 0.110886E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 335954.85 | 0.128825E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 926151.07 | 0.145687E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4938548.54 | 0.900189E+09 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110839E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91341.09 | 0.627523E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10339013.58 | 0.458598E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10785851.05 | 0.557333E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16259951.53 | 0.519887E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62521308.48 | 0.766216E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10167621.00 | 0.107455E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10725107.91 | 0.112796E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131855E+09 | 0.109946E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458598E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62521308.48 | 0.145687E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2329951.00 | 0.775539E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130343.79 | 0.898966E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 169648.88 | 0.101029E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 817444.74 | 0.651356E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777692E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60879.89 | 0.432534E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5877610.31 | 0.333472E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6038353.05 | 0.404739E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10814740.60 | 0.372731E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36774547.58 | 0.539285E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4014591.78 | 0.750173E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3035475.88 | 0.787112E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70063587.51 | 0.773389E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333472E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36774547.58 | 0.101029E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1152911.25 | 0.133815E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189697.61 | 0.149782E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158212E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1745286.51 | 0.988339E+09 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111650E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91343.72 | 0.608802E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10726010.44 | 0.454601E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9351952.72 | 0.593708E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15737206.37 | 0.613899E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51103363.32 | 0.932408E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399237.37 | 0.130460E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 735722.21 | 0.140312E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91232731.52 | 0.124341E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454601E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51103363.32 | 0.158212E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2235044.48 | 0.809743E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346614.01 | 0.948074E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440264.28 | 0.104349E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2466680.15 | 0.689264E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819442E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60890.88 | 0.453138E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7888551.20 | 0.352268E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8136005.04 | 0.432010E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11099150.51 | 0.402447E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40688347.63 | 0.576673E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5055425.10 | 0.795899E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3929720.27 | 0.837870E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82346693.55 | 0.816032E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352268E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40688347.63 | 0.104349E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.554336E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.502824E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.597494E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.533685E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.575915E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.573131E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.536469E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.597494E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.533685E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.554336E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.547839E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.536469E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.664368E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.502824E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.597494E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498129.59 | 0.113629E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90445.56 | 0.131622E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138061E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643902.10 | 0.811641E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941958E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11468.86 | 0.504716E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4603090.91 | 0.365295E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4307936.74 | 0.462825E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10087206.03 | 0.454719E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36906253.35 | 0.729750E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190417.79 | 0.107559E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264639.24 | 0.118110E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58603490.16 | 0.103607E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365295E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36906253.35 | 0.138061E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363419.56 | 0.191061E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186099.65 | 0.222524E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235212E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1920669.41 | 0.138502E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163813E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17428.40 | 0.878332E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8548071.78 | 0.639989E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7867714.94 | 0.813873E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18064706.25 | 0.791316E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68590368.58 | 0.125119E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4302591.74 | 0.183079E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832238.68 | 0.197822E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111693E+09 | 0.176948E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639989E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68590368.58 | 0.235212E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895625.66 | 0.180512E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40020.86 | 0.214146E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238572E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188300.43 | 0.155796E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185226E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107527E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3337888.67 | 0.845621E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2375949.04 | 0.972036E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17973370.34 | 0.932586E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63491310.66 | 0.128243E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4897103.10 | 0.177794E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153377.37 | 0.185075E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96352946.11 | 0.184792E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845621E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63491310.66 | 0.238572E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20573.73 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20573.73 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20573.73 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20573.73 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20573.73 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20573.73 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20573.73 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20573.73 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20573.73 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20573.73 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20573.73 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20573.73 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 14-JAN-11:00 | 1287.91 | 02-JAN-02:55 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 01-FEB-12:00 | 1137.25 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 11-MAR-13:10 | 1224.20 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 | 30-APR-10:53 | 768.17 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 03-MAY-12:00 | 715.72 | 20-MAY-17:57 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 29-JUN-11:00 | 503.29 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 | 31-JUL-13:00 | 388.30 | 09-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.39 | 06-AUG-12:50 | 351.59 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.89 | 29-SEP-14:00 | 414.04 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.08 | 15-OCT-13:00 | 824.62 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.97 | 19-NOV-13:00 | 1082.95 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.65 | 05-DEC-10:00 | 999.28 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 351.59 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 448.08 | 1287.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 14-JAN-15:00 | 862.45 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 01-FEB-12:00 | 729.86 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 11-MAR-14:00 | 778.51 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 26-APR-13:00 | 497.81 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 454.55 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 29-JUN-11:00 | 325.56 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 31-JUL-13:00 | 253.45 | 02-JUL-18:57 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.30 | 06-AUG-12:50 | 217.17 | 21-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 | 29-SEP-14:00 | 323.90 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.82 | 15-OCT-12:50 | 549.11 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.86 | 19-NOV-13:00 | 699.69 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 17-DEC-13:00 | 648.26 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 217.17 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 315.82 | 862.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 14-JAN-11:00 | 1148.94 | 02-JAN-02:55 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 01-FEB-12:00 | 1104.20 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-14:00 | 1192.31 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 26-APR-13:00 | 753.65 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 | 03-MAY-12:00 | 670.13 | 20-MAY-17:57 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 29-JUN-11:00 | 493.12 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.68 | 23-JUL-10:50 | 376.97 | 02-JUL-18:57 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 17-AUG-14:00 | 346.26 | 21-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.31 | 29-SEP-14:00 | 462.37 | 24-SEP-15:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.77 | 15-OCT-12:56 | 853.89 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.21 | 19-NOV-12:55 | 1100.71 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.65 | 05-DEC-10:00 | 1014.50 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 346.26 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 370.77 | 1192.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 14-JAN-11:00 | 888.26 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 01-FEB-12:00 | 851.58 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-14:00 | 897.47 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 30-APR-10:53 | 630.11 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 03-MAY-12:00 | 604.23 | 20-MAY-17:57 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 29-JUN-11:00 | 406.74 | 03-JUN-17:08 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 31-JUL-13:00 | 389.61 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 17-AUG-14:00 | 311.22 | 27-AUG-17:50 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 | 29-SEP-14:00 | 380.91 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.33 | 15-OCT-09:00 | 634.30 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 19-NOV-13:00 | 835.13 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 | 05-DEC-10:00 | 752.48 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 311.22 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 294.33 | 897.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.45 | 15-JAN-10:00 | 2226.30 | 27-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 | 01-FEB-12:00 | 2245.87 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 11-MAR-14:00 | 2507.95 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.39 | 30-APR-11:20 | 1555.32 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1561.37 | 20-MAY-17:53 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 29-JUN-11:00 | 1071.74 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.61 | 23-JUL-11:00 | 842.02 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.30 | 06-AUG-12:50 | 774.23 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.29 | 29-SEP-14:00 | 855.48 | 04-SEP-17:57 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.79 | 15-OCT-08:52 | 1647.10 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.50 | 19-NOV-12:52 | 2102.53 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 240.71 | 25-DEC-12:00 | 2051.43 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.23 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.79 | 2507.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.35 | 15-JAN-14:50 | 1483.03 | 27-JAN-04:55 |
February | 1239.33 | 01-FEB-08:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.96 | 01-FEB-12:00 | 1460.97 | 08-FEB-05:53 |
March | 1239.33 | 01-MAR-08:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 11-MAR-14:00 | 1663.34 | 28-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 26-APR-13:00 | 1035.58 | 17-APR-03:00 |
May | 1239.33 | 01-MAY-07:10 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 980.93 | 20-MAY-17:53 |
June | 1239.33 | 01-JUN-07:10 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 29-JUN-11:00 | 723.76 | 04-JUN-14:00 |
July | 1239.33 | 03-JUL-07:10 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 31-JUL-13:00 | 618.13 | 04-JUL-13:55 |
August | 1239.33 | 01-AUG-07:10 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 17-AUG-14:00 | 514.53 | 21-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.51 | 29-SEP-14:00 | 686.78 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 677.48 | 15-OCT-13:10 | 1135.11 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.11 | 19-NOV-13:10 | 1399.86 | 23-NOV-04:00 |
December | 1239.33 | 01-DEC-08:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.39 | 17-DEC-13:10 | 1369.38 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.53 | |||||
Maximum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 677.48 | 1663.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.27 | 14-JAN-11:00 | 2350.92 | 07-JAN-02:00 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 | 01-FEB-12:00 | 2287.02 | 08-FEB-05:53 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2511.73 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.25 | 30-APR-10:32 | 1588.37 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1498.87 | 20-MAY-17:53 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 29-JUN-11:00 | 1058.35 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.67 | 23-JUL-11:00 | 839.44 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.46 | 17-AUG-14:00 | 791.49 | 21-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.02 | 29-SEP-14:00 | 1062.26 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.88 | 15-OCT-12:46 | 1887.31 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 18-NOV-13:00 | 2296.97 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.23 | 05-DEC-10:00 | 2201.95 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.49 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 836.88 | 2511.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 | 14-JAN-12:40 | 1510.36 | 27-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.12 | 01-FEB-12:00 | 1504.53 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 | 11-MAR-12:30 | 1677.16 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.22 | 30-APR-11:20 | 1281.68 | 16-APR-17:42 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1361.72 | 20-MAY-17:53 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 29-JUN-11:00 | 890.43 | 03-JUN-17:10 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.33 | 23-JUL-11:00 | 790.52 | 09-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.23 | 06-AUG-12:40 | 645.88 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.53 | 29-SEP-14:00 | 863.50 | 03-SEP-16:53 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 753.64 | 15-OCT-08:52 | 1184.95 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.50 | 19-NOV-12:30 | 1468.95 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.02 | 25-DEC-12:00 | 1419.06 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.88 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 753.64 | 1677.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.68 | 15-JAN-10:00 | 2519.66 | 27-JAN-05:08 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.64 | 01-FEB-12:00 | 2468.47 | 08-FEB-05:57 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 11-MAR-13:20 | 3078.86 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.64 | 30-APR-11:20 | 1769.33 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1851.86 | 20-MAY-17:53 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 29-JUN-11:00 | 1272.01 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.45 | 23-JUL-11:00 | 1074.60 | 02-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.55 | 06-AUG-13:00 | 900.11 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.16 | 29-SEP-14:00 | 1054.48 | 04-SEP-17:53 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.80 | 15-OCT-08:52 | 1755.33 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.70 | 19-NOV-13:00 | 2143.74 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 548.66 | 25-DEC-11:53 | 2274.88 | 13-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.11 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.80 | 3078.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.91 | 15-JAN-10:00 | 1690.00 | 27-JAN-05:05 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 | 01-FEB-12:00 | 1645.77 | 08-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 11-MAR-14:00 | 2048.46 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.08 | 26-APR-13:00 | 1213.99 | 16-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1194.19 | 29-MAY-12:53 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 29-JUN-11:00 | 969.35 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.31 | 31-JUL-13:00 | 792.76 | 04-JUL-14:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.70 | 17-AUG-14:00 | 634.72 | 27-AUG-18:30 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.11 | 29-SEP-14:00 | 776.01 | 03-SEP-18:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.23 | 15-OCT-12:40 | 1227.34 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.57 | 19-NOV-13:00 | 1453.66 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 212.06 | 17-DEC-13:00 | 1531.24 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.72 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 797.23 | 2048.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.70 | 15-JAN-10:00 | 2721.16 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.63 | 01-FEB-12:00 | 2778.18 | 20-FEB-15:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3085.89 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.44 | 30-APR-10:30 | 1896.90 | 16-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1786.48 | 20-MAY-17:53 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 29-JUN-11:00 | 1251.21 | 04-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.74 | 23-JUL-11:00 | 1074.90 | 02-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 | 17-AUG-14:00 | 960.99 | 27-AUG-18:10 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.24 | 29-SEP-12:05 | 1323.68 | 24-SEP-15:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.45 | 15-OCT-08:52 | 2089.71 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 | 18-NOV-13:00 | 2435.17 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 | 05-DEC-10:00 | 2493.37 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.99 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.45 | 3085.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.43 | 15-JAN-10:00 | 1708.09 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 01-FEB-12:00 | 1658.45 | 08-FEB-02:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.88 | 11-MAR-12:30 | 2065.20 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.73 | 30-APR-11:13 | 1684.75 | 16-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1644.77 | 20-MAY-17:53 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 29-JUN-11:00 | 1111.39 | 03-JUN-17:10 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.03 | 23-JUL-11:00 | 1040.97 | 09-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.73 | 06-AUG-12:50 | 814.43 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.11 | 29-SEP-14:00 | 1037.94 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 983.22 | 15-OCT-08:52 | 1314.46 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.28 | 19-NOV-12:12 | 1557.44 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.84 | 17-DEC-12:53 | 1605.48 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.43 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 983.22 | 2065.20 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5800.91 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5800.91 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5800.91 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5800.91 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5800.91 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5800.91 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5800.91 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5800.91 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5800.91 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5800.91 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5800.91 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5800.91 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.14 | 14-JAN-11:00 | 2838.31 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 | 01-FEB-12:00 | 2484.74 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2633.68 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 | 30-APR-11:00 | 1637.20 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1482.36 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 | 29-JUN-11:00 | 1042.85 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 | 31-JUL-13:00 | 782.27 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 | 17-AUG-14:00 | 749.88 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.93 | 29-SEP-13:50 | 899.51 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.99 | 15-OCT-13:00 | 1772.17 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 | 19-NOV-13:00 | 2413.17 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 05-DEC-10:00 | 2163.50 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.99 | 2838.31 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 15-JAN-10:00 | 4027.22 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.68 | 01-FEB-12:00 | 4228.58 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4508.13 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.89 | 30-APR-10:53 | 2748.91 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2609.11 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 29-JUN-11:00 | 1812.86 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.13 | 23-JUL-10:53 | 1359.38 | 02-JUL-18:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.47 | 06-AUG-12:53 | 1314.43 | 21-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.09 | 29-SEP-13:50 | 1516.67 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.06 | 15-OCT-12:51 | 2997.62 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.70 | 19-NOV-12:52 | 4109.04 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.08 | 05-DEC-10:00 | 3734.86 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.06 | 4508.13 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.14 | 15-JAN-10:00 | 3863.05 | 27-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 01-FEB-12:00 | 3948.31 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4755.33 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.30 | 26-APR-13:00 | 3046.39 | 16-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3204.26 | 07-MAY-14:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 2583.38 | 04-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.12 | 31-JUL-13:00 | 2034.63 | 09-JUL-12:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.18 | 17-AUG-14:00 | 1607.00 | 27-AUG-17:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.24 | 29-SEP-13:20 | 2024.45 | 24-SEP-15:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.99 | 15-OCT-08:52 | 2869.37 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.42 | 19-NOV-13:00 | 3448.03 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.82 | 04-DEC-10:00 | 3661.62 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.99 | 4755.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 109087.97 | 23-JAN-04:03 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 110018.52 | 21-FEB-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110567.16 | 20-MAR-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110124.99 | 17-APR-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107313.42 | 22-MAY-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106263.77 | 05-JUN-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99412.28 | 17-JUL-03:02 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95510.00 | 28-AUG-03:02 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98928.89 | 19-SEP-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 109906.31 | 30-OCT-03:02 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 110229.24 | 06-NOV-04:03 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 110923.87 | 11-DEC-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95510.00 | 0.00 | 4572.22 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 110923.87 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94933.39 | 02-JAN-04:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92459.84 | 21-FEB-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91356.22 | 20-MAR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90545.77 | 17-APR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92141.81 | 30-MAY-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93617.11 | 12-JUN-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88784.73 | 06-JUL-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87618.97 | 23-AUG-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94326.25 | 05-SEP-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 92240.43 | 23-OCT-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93927.82 | 20-NOV-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93614.80 | 11-DEC-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87618.97 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94933.39 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79506.39 | 20-JAN-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79576.04 | 15-FEB-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79483.82 | 23-MAR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80786.00 | 27-APR-04:03 | 0.00 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80513.69 | 04-MAY-04:03 | 0.00 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81408.14 | 21-JUN-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80964.82 | 14-JUL-04:03 | 0.00 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80944.80 | 31-AUG-04:03 | 0.00 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83448.51 | 25-SEP-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85128.36 | 02-OCT-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82424.43 | 13-NOV-04:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79115.77 | 02-DEC-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79115.77 | 0.00 | 5132.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85128.36 | 8061.19 | 10264.30 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38767.62 | 19-JAN-15:00 | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39245.39 | 16-FEB-16:20 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69157.68 | 24-MAR-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76727.75 | 27-APR-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76568.26 | 03-MAY-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78599.12 | 20-JUN-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79754.16 | 31-JUL-04:02 | 0.00 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78693.54 | 18-AUG-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78678.97 | 25-SEP-04:03 | 0.00 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83462.29 | 02-OCT-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65881.64 | 01-NOV-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51489.98 | 06-DEC-06:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 38767.62 | 0.00 | 5132.72 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83462.29 | 16014.58 | 18476.66 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6283.75 | 17-JAN-13:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
February | 5417.76 | 01-FEB-12:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 0.00 |
March | 6218.16 | 13-MAR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.92 |
April | 7494.13 | 26-APR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 0.00 |
May | 8678.84 | 01-MAY-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11716.29 | 26-JUN-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
July | 11801.61 | 05-JUL-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11527.42 | 01-AUG-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 |
September | 11638.38 | 25-SEP-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
October | 10637.47 | 02-OCT-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.51 |
November | 6075.26 | 28-NOV-14:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.00 |
December | 6655.73 | 05-DEC-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5417.76 | 809.73 | 1031.03 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11801.61 | 2010.79 | 2319.93 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 109.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6143.55 | 20-JAN-09:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
February | 6980.14 | 21-FEB-09:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 |
March | 8095.64 | 23-MAR-08:40 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14325.13 | 30-APR-08:43 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 |
May | 10147.17 | 28-MAY-07:53 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.11 |
June | 11586.75 | 18-JUN-07:33 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.83 |
July | 15948.18 | 23-JUL-08:23 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 |
August | 10155.69 | 13-AUG-07:33 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.11 |
September | 10915.30 | 03-SEP-08:32 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.13 |
October | 16199.39 | 15-OCT-08:43 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 186.89 | 0.00 |
November | 6815.30 | 19-NOV-09:00 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 |
December | 6688.20 | 05-DEC-09:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6143.55 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16199.39 | 1239.33 | 1495.05 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 186.89 | 195.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15734.95 | 18-JAN-13:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
February | 14785.05 | 21-FEB-13:20 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 |
March | 13404.05 | 23-MAR-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 |
April | 11773.18 | 26-APR-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 | 0.00 |
May | 8852.16 | 04-MAY-12:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
June | 9275.95 | 26-JUN-05:03 | 809.75 | 1031.05 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 |
July | 12782.23 | 31-JUL-05:03 | 809.75 | 1031.05 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
August | 12572.65 | 30-AUG-13:00 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15988.26 | 29-SEP-13:50 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 | 0.00 |
October | 20994.55 | 01-OCT-12:32 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.53 |
November | 21280.47 | 19-NOV-12:12 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.03 |
December | 20300.75 | 03-DEC-13:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8852.16 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21280.47 | 2010.83 | 2319.98 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 | 364.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8763.50 | 18-JAN-14:50 | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
February | 10120.84 | 22-FEB-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 |
March | 13919.15 | 24-MAR-05:03 | 521.82 | 664.43 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 |
April | 20651.18 | 30-APR-16:02 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.54 |
May | 16254.42 | 01-MAY-05:03 | 521.82 | 664.43 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16145.41 | 26-JUN-05:03 | 521.82 | 664.43 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
July | 21567.61 | 23-JUL-15:02 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 |
August | 21330.18 | 13-AUG-14:12 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 |
September | 21098.67 | 04-SEP-15:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.00 |
October | 21160.50 | 01-OCT-14:32 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 |
November | 16609.14 | 19-NOV-13:32 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
December | 16251.27 | 05-DEC-04:02 | 0.00 | 415.32 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8763.50 | 0.00 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21567.61 | 1295.83 | 1495.05 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4658.47 | 18-JAN-14:20 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
February | 3974.48 | 03-FEB-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.81 |
March | 4650.82 | 23-MAR-15:20 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 |
April | 6095.73 | 26-APR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 0.00 |
May | 6561.77 | 04-MAY-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 |
June | 6528.96 | 29-JUN-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 |
July | 7299.82 | 01-JUL-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7019.61 | 18-AUG-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 | 0.00 |
September | 9561.19 | 30-SEP-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 8699.27 | 05-OCT-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4148.54 | 10-NOV-14:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.68 |
December | 4651.52 | 05-DEC-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3974.48 | 809.73 | 1031.03 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9561.19 | 2010.79 | 2319.93 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 | 176.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5233.30 | 20-JAN-09:40 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 |
February | 5095.67 | 21-FEB-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7456.22 | 23-MAR-09:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8749.37 | 26-APR-08:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
May | 7853.48 | 18-MAY-08:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.97 |
June | 12182.59 | 18-JUN-08:43 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.77 |
July | 16499.34 | 23-JUL-08:53 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.25 |
August | 14563.67 | 06-AUG-09:13 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.75 |
September | 12857.00 | 10-SEP-08:23 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 |
October | 16331.49 | 15-OCT-09:43 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 269.25 | 0.00 |
November | 4893.66 | 20-NOV-09:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 |
December | 5365.28 | 05-DEC-09:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4893.66 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16499.34 | 1239.33 | 1495.05 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 269.25 | 213.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19671.82 | 22-JAN-13:53 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.56 |
February | 14321.43 | 22-FEB-13:50 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 |
March | 12999.36 | 23-MAR-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.05 |
April | 10910.01 | 26-APR-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 80.11 | 0.00 |
May | 8193.61 | 04-MAY-12:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 |
June | 7414.96 | 30-JUN-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
July | 10015.14 | 31-JUL-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 0.00 |
August | 11868.97 | 30-AUG-13:00 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
September | 15892.19 | 29-SEP-12:15 | 3846.30 | 4639.96 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 322.23 | 0.00 |
October | 21513.42 | 15-OCT-13:01 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 444.76 | 0.00 |
November | 19734.99 | 19-NOV-11:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.18 |
December | 19103.60 | 25-DEC-11:53 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7414.96 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21513.42 | 3846.30 | 4639.96 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 444.76 | 897.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6862.21 | 18-JAN-15:00 | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 |
February | 7319.92 | 22-FEB-16:20 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.70 |
March | 9611.53 | 23-MAR-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 |
April | 14486.67 | 30-APR-16:23 | 260.91 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.63 |
May | 11411.71 | 28-MAY-17:03 | 0.00 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.59 |
June | 17180.39 | 25-JUN-16:33 | 260.91 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.17 |
July | 18121.03 | 04-JUL-16:32 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17734.70 | 06-AUG-16:12 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.57 |
September | 11060.99 | 29-SEP-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 164.16 | 0.00 |
October | 17465.91 | 15-OCT-15:02 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 281.02 | 0.00 |
November | 7279.68 | 07-NOV-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.98 |
December | 7172.12 | 19-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6862.21 | 0.00 | 332.25 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18121.03 | 1295.83 | 1495.05 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 281.02 | 677.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4129.65 | 18-JAN-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 |
February | 3492.13 | 01-FEB-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.01 |
March | 4644.32 | 23-MAR-15:20 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.84 |
April | 6593.96 | 26-APR-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.49 | 0.00 |
May | 7111.49 | 04-MAY-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.19 |
June | 7174.78 | 30-JUN-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.53 |
July | 8126.84 | 19-JUL-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.25 | 0.00 |
August | 7779.99 | 18-AUG-15:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 91.18 | 0.00 |
September | 11533.95 | 30-SEP-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
October | 9007.22 | 16-OCT-13:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 424.71 | 0.00 |
November | 3764.35 | 10-NOV-14:40 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.63 |
December | 4159.26 | 05-DEC-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3492.13 | 1012.16 | 1288.79 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11533.95 | 2010.79 | 2319.93 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 424.71 | 232.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3968.73 | 20-JAN-10:10 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.82 |
February | 3805.67 | 02-FEB-10:10 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 |
March | 6532.91 | 23-MAR-09:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 |
April | 8262.93 | 26-APR-09:30 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
May | 7479.56 | 04-MAY-09:30 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 |
June | 9080.93 | 25-JUN-09:23 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.46 |
July | 12884.63 | 04-JUL-09:02 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.85 |
August | 11215.95 | 13-AUG-09:23 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.59 |
September | 9154.15 | 30-SEP-05:02 | 652.28 | 830.54 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 16418.26 | 15-OCT-09:13 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 0.00 |
November | 4041.60 | 19-NOV-13:22 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 151.42 | 0.00 |
December | 4132.59 | 05-DEC-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3805.67 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16418.26 | 1295.83 | 1495.05 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 486.13 | 365.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18682.54 | 22-JAN-14:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.92 |
February | 13932.23 | 22-FEB-14:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.27 |
March | 13223.01 | 23-MAR-14:00 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
April | 11515.49 | 26-APR-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 95.49 | 0.00 |
May | 8711.30 | 03-MAY-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
June | 8104.86 | 30-JUN-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.53 |
July | 10923.44 | 31-JUL-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 166.88 | 0.00 |
August | 12486.67 | 30-AUG-13:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
September | 16948.39 | 29-SEP-12:05 | 3846.30 | 4639.96 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 403.24 | 0.00 |
October | 22587.73 | 15-OCT-15:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 190.56 | 0.00 |
November | 22357.69 | 19-NOV-13:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.65 |
December | 16556.66 | 19-DEC-13:20 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8104.86 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22587.73 | 3846.30 | 4639.96 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 403.24 | 1093.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6570.33 | 18-JAN-15:00 | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.76 |
February | 6971.48 | 22-FEB-16:20 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.46 |
March | 9687.98 | 23-MAR-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.55 |
April | 11046.33 | 26-APR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 |
May | 10849.74 | 28-MAY-17:03 | 0.00 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.27 |
June | 17114.83 | 25-JUN-16:42 | 260.91 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.72 |
July | 19957.03 | 09-JUL-16:02 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.80 |
August | 13788.21 | 20-AUG-17:33 | 0.00 | 332.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.61 |
September | 12328.96 | 30-SEP-05:02 | 652.28 | 830.54 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
October | 20296.35 | 15-OCT-15:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | 0.00 |
November | 6963.45 | 10-NOV-14:50 | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.48 |
December | 6928.82 | 19-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6570.33 | 0.00 | 332.25 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20296.35 | 1295.83 | 1495.05 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | 851.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8328.31 | 17-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 |
February | 7140.37 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.11 |
March | 7070.04 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.78 |
April | 8467.78 | 11-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9646.56 | 01-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8409.33 | 19-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 |
July | 9439.67 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10044.23 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 |
September | 10460.39 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10673.65 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.01 |
November | 8485.86 | 21-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
December | 9100.96 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7070.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10673.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4871.99 | 21-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4832.21 | 04-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.18 |
March | 4994.74 | 23-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.57 |
April | 6541.20 | 27-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 |
May | 5571.45 | 01-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6500.28 | 22-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.90 |
July | 6671.30 | 01-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6523.87 | 31-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 |
September | 6111.82 | 26-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.63 |
October | 7933.24 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.85 |
November | 5053.74 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.03 |
December | 4689.93 | 02-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7933.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8849.86 | 18-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.96 |
February | 8818.12 | 01-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.19 |
March | 12845.84 | 23-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.30 |
April | 17206.28 | 26-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 0.00 |
May | 16236.48 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.92 |
June | 16336.37 | 30-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.27 |
July | 18429.59 | 19-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.11 | 0.00 |
August | 17900.19 | 14-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 0.00 |
September | 19724.66 | 29-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.05 | 0.00 |
October | 18398.64 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.82 | 0.00 |
November | 8483.97 | 10-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.62 |
December | 8074.10 | 19-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8074.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19724.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.05 | 385.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2045.85 | 30-JAN-16:40 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4034.44 | 22-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7024.47 | 31-MAR-24:00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7812.54 | 30-APR-17:14 | 0.00 | 105.99 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3327.86 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5366.83 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7236.87 | 31-JUL-23:45 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7895.55 | 06-AUG-17:50 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3524.20 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5332.72 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5900.41 | 07-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7838.88 | 25-DEC-16:10 | 23.38 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2045.85 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7895.55 | 222.14 | 381.58 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1861.99 | 30-JAN-16:50 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3767.85 | 22-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6267.75 | 31-MAR-23:40 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7288.86 | 27-APR-17:00 | 70.15 | 211.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2991.97 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5072.43 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6925.30 | 31-JUL-23:53 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7350.05 | 06-AUG-17:50 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3378.07 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4921.29 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5539.36 | 07-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7326.15 | 18-DEC-16:20 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1861.99 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7350.05 | 222.14 | 381.58 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1821.74 | 18-JAN-16:10 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3762.00 | 22-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5846.27 | 31-MAR-23:20 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7364.41 | 26-APR-16:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2672.04 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4932.26 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6814.40 | 31-JUL-24:00 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7499.12 | 20-AUG-17:30 | 0.00 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3304.93 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4667.61 | 31-OCT-23:50 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5518.84 | 10-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7327.28 | 19-DEC-16:30 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1821.74 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7499.12 | 222.14 | 381.58 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92704.43 | 18-JAN-17:00 | 4808.68 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183710.63 | 21-FEB-17:00 | 4808.68 | 5800.91 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358135.06 | 31-MAR-24:00 | 0.00 | 322.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367252.46 | 27-APR-16:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175388.57 | 31-MAY-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267121.52 | 30-JUN-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359211.30 | 31-JUL-23:53 | 0.00 | 966.88 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367697.22 | 25-AUG-16:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175694.97 | 30-SEP-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267929.38 | 31-OCT-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276274.68 | 13-NOV-17:00 | 4808.68 | 5800.91 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369381.26 | 19-DEC-17:05 | 3037.06 | 6445.43 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92704.43 | 0.00 | 322.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369381.26 | 4808.68 | 6445.43 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.182319E+13 | 1320566.92 | 24-JAN-14:30 | 0.162307E+12 | 783896.78 | 09-JAN-07:10 |
February | 0.199822E+13 | 1439636.75 | 01-FEB-13:20 | 0.132196E+12 | 564312.75 | 10-FEB-07:10 |
March | 0.264558E+13 | 1707294.40 | 23-MAR-15:20 | 0.175323E+12 | 753326.56 | 30-MAR-06:10 |
April | 0.297485E+13 | 1852857.80 | 26-APR-15:39 | 0.941019E+11 | 613480.74 | 01-APR-06:10 |
May | 0.189388E+13 | 1374060.70 | 18-MAY-15:20 | 0.849479E+11 | 268352.36 | 15-MAY-06:10 |
June | 0.234622E+13 | 1589988.07 | 29-JUN-15:00 | 0.634310E+11 | 193056.73 | 12-JUN-20:00 |
July | 0.288162E+13 | 1858287.16 | 31-JUL-15:50 | 0.595749E+11 | 74953.92 | 11-JUL-11:20 |
August | 0.339990E+13 | 2015457.69 | 18-AUG-15:50 | 0.629918E+11 | 74991.35 | 31-AUG-11:50 |
September | 0.195662E+13 | 1472508.33 | 29-SEP-15:00 | 0.606708E+11 | 165827.12 | 20-SEP-06:19 |
October | 0.244227E+13 | 1610794.82 | 17-OCT-15:00 | 0.682474E+11 | 355209.46 | 12-OCT-06:10 |
November | 0.258915E+13 | 1580896.56 | 28-NOV-14:09 | 0.105526E+12 | 435756.73 | 24-NOV-07:10 |
December | 0.302627E+13 | 1787884.33 | 05-DEC-09:39 | 0.141698E+12 | 643326.08 | 13-DEC-07:10 |
Annual Sum or Average | 0.299778E+14 | 0.121102E+13 | ||||
Minimum of Months | 0.182319E+13 | 1320566.92 | 0.595749E+11 | 74953.92 | ||
Maximum of Months | 0.339990E+13 | 2015457.69 | 0.175323E+12 | 783896.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328950E+12 | 0.892039E+11 | 0.811612E+12 | 0.169596E+12 | 0.189626E+12 | 0.391172E+11 | 0.00 | 0.132956E+12 | 0.616638E+11 | 0.461790E+09 | 0.00 | 0.00 | 0.00 |
February | 0.298382E+12 | 0.762482E+11 | 0.102011E+13 | 0.153195E+12 | 0.172238E+12 | 0.301035E+11 | 0.00 | 0.169226E+12 | 0.783599E+11 | 0.363149E+09 | 0.00 | 0.00 | 0.00 |
March | 0.354561E+12 | 0.781484E+11 | 0.146267E+13 | 0.169879E+12 | 0.195551E+12 | 0.311839E+11 | 0.00 | 0.252605E+12 | 0.100959E+12 | 19214979.11 | 0.00 | 0.00 | 0.00 |
April | 0.316695E+12 | 0.694768E+11 | 0.170311E+13 | 0.164100E+12 | 0.202287E+12 | 0.469622E+11 | 0.00 | 0.346082E+12 | 0.126075E+12 | 69008067.34 | 0.00 | 0.00 | 0.00 |
May | 0.341755E+12 | 0.663329E+11 | 0.820521E+12 | 0.169738E+12 | 0.205717E+12 | 0.508473E+11 | 0.00 | 0.152648E+12 | 0.863182E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.340103E+12 | 0.614961E+11 | 0.110677E+13 | 0.164363E+12 | 0.215135E+12 | 0.662736E+11 | 0.00 | 0.260319E+12 | 0.131758E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.318348E+12 | 0.647436E+11 | 0.143888E+13 | 0.169473E+12 | 0.227779E+12 | 0.878400E+11 | 0.00 | 0.418714E+12 | 0.155844E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.354561E+12 | 0.693386E+11 | 0.177780E+13 | 0.169879E+12 | 0.243202E+12 | 0.953385E+11 | 0.00 | 0.528562E+12 | 0.161228E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316695E+12 | 0.730007E+11 | 0.784732E+12 | 0.164097E+12 | 0.213262E+12 | 0.677110E+11 | 0.00 | 0.208453E+12 | 0.128669E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328950E+12 | 0.818105E+11 | 0.112899E+13 | 0.169597E+12 | 0.213036E+12 | 0.724986E+11 | 0.00 | 0.310687E+12 | 0.136504E+12 | 0.191897E+09 | 0.00 | 0.00 | 0.00 |
November | 0.325095E+12 | 0.847471E+11 | 0.140306E+13 | 0.164207E+12 | 0.192643E+12 | 0.423380E+11 | 0.00 | 0.267008E+12 | 0.109467E+12 | 0.587012E+09 | 0.00 | 0.00 | 0.00 |
December | 0.318348E+12 | 0.907240E+11 | 0.175516E+13 | 0.169471E+12 | 0.191685E+12 | 0.406540E+11 | 0.00 | 0.344098E+12 | 0.115047E+12 | 0.107969E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394244E+13 | 0.905271E+12 | 0.152134E+14 | 0.199759E+13 | 0.246216E+13 | 0.670868E+12 | 0.00 | 0.339136E+13 | 0.139189E+13 | 0.277176E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298382E+12 | 0.614961E+11 | 0.784732E+12 | 0.153195E+12 | 0.172238E+12 | 0.301035E+11 | 0.00 | 0.132956E+12 | 0.616638E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354561E+12 | 0.907240E+11 | 0.177780E+13 | 0.169879E+12 | 0.243202E+12 | 0.953385E+11 | 0.00 | 0.528562E+12 | 0.161228E+12 | 0.107969E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.980989E+11 | 0.00 | 0.642077E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.739358E+11 | 0.00 | 0.582601E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.108690E+12 | 0.00 | 0.666339E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.331128E+11 | 0.00 | 0.609892E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.216515E+11 | 0.00 | 0.632963E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.213311E+10 | 0.00 | 0.612979E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 152297.47 | 0.00 | 0.595747E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 18993071.69 | 0.00 | 0.629728E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.170774E+10 | 0.00 | 0.589631E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.652555E+10 | 0.00 | 0.617219E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.442686E+11 | 0.00 | 0.612570E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.790045E+11 | 0.00 | 0.626937E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.469147E+12 | 0.00 | 0.741868E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 152297.47 | 0.00 | 0.582601E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108690E+12 | 0.00 | 0.666339E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 344233.60 | 02-JAN-08:09 | 57580.60 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 120520.01 | 02-JAN-08:20 | 158365.29 | 18-JAN-15:50 | 64302.10 | 13-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 344233.60 | 01-FEB-08:09 | 57580.60 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 120520.01 | 01-FEB-08:20 | 160522.39 | 03-FEB-15:50 | 61773.64 | 01-FEB-13:20 | 0.00 | 01-FEB-00:10 |
March | 344233.60 | 01-MAR-08:09 | 57580.60 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 120520.01 | 01-MAR-08:20 | 184729.35 | 23-MAR-15:20 | 61408.99 | 23-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 344233.60 | 03-APR-07:10 | 57580.60 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 120520.01 | 03-APR-07:19 | 193528.21 | 26-APR-14:30 | 61926.11 | 12-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 344233.60 | 01-MAY-07:10 | 57580.60 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 120520.01 | 01-MAY-07:19 | 177044.13 | 03-MAY-15:20 | 62719.96 | 03-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 344233.60 | 01-JUN-07:10 | 57580.60 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 120520.01 | 01-JUN-07:19 | 186653.93 | 30-JUN-15:00 | 61870.02 | 29-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 344233.60 | 03-JUL-07:10 | 57580.60 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 120520.01 | 03-JUL-07:19 | 205774.29 | 31-JUL-14:00 | 63200.70 | 31-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 344233.60 | 01-AUG-07:10 | 57580.60 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 120520.01 | 01-AUG-07:19 | 204633.81 | 18-AUG-14:00 | 63208.66 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 344233.60 | 01-SEP-07:10 | 57580.60 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 120520.01 | 01-SEP-07:19 | 191638.08 | 11-SEP-14:30 | 67222.11 | 29-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 344233.60 | 02-OCT-07:10 | 57580.60 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 120520.01 | 02-OCT-07:19 | 196298.86 | 16-OCT-08:30 | 66885.77 | 17-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 344233.60 | 01-NOV-07:10 | 57580.60 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 120520.01 | 01-NOV-07:19 | 162773.45 | 13-NOV-15:09 | 61293.27 | 28-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 344233.60 | 01-DEC-08:09 | 57580.60 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 120520.01 | 01-DEC-08:20 | 165120.50 | 05-DEC-15:00 | 61537.93 | 19-DEC-13:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 344233.60 | 57580.60 | 439129.89 | 120520.01 | 158365.29 | 61293.27 | 0.00 | |||||||
Maximum of Months | 344233.60 | 57580.60 | 794004.08 | 120520.01 | 205774.29 | 67222.11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 235002.27 | 13-JAN-13:00 | 82101.62 | 13-JAN-13:50 | 4637.11 | 07-JAN-09:00 | 0.00 | 0.00 | 0.00 |
February | 246212.12 | 01-FEB-11:00 | 80839.38 | 01-FEB-13:20 | 5362.42 | 04-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 283760.64 | 23-MAR-13:50 | 82101.62 | 22-MAR-12:00 | 1890.35 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 331560.79 | 26-APR-12:00 | 82101.62 | 04-APR-13:00 | 6074.20 | 01-APR-11:00 | 0.00 | 0.00 | 0.00 |
May | 224341.67 | 03-MAY-12:00 | 82101.62 | 03-MAY-11:00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 300002.16 | 29-JUN-12:00 | 82101.62 | 15-JUN-14:00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 412703.01 | 31-JUL-15:50 | 82101.62 | 03-JUL-12:09 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 448084.30 | 18-AUG-15:50 | 82101.62 | 02-AUG-09:09 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 314117.85 | 29-SEP-12:20 | 82101.62 | 05-SEP-12:30 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 371046.61 | 16-OCT-10:00 | 82101.62 | 02-OCT-07:19 | 4308.07 | 25-OCT-20:00 | 0.00 | 0.00 | 0.00 |
November | 288727.03 | 28-NOV-13:00 | 65674.94 | 10-NOV-12:00 | 5551.32 | 22-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 327195.03 | 05-DEC-14:00 | 64169.08 | 07-DEC-13:30 | 6835.20 | 19-DEC-10:39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 224341.67 | 64169.08 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 448084.30 | 82101.62 | 6835.20 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1320566.92 | 24-JAN-14:30 | 344233.60 | 439129.89 | 0.00 | 41348.64 | 141998.95 | 62216.29 | 0.00 | 209537.94 | 82101.62 |
February | 1439636.75 | 01-FEB-13:20 | 344233.60 | 557421.28 | 0.00 | 41348.64 | 117909.53 | 61773.64 | 0.00 | 236110.67 | 80839.38 |
March | 1707294.40 | 23-MAR-15:20 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 184729.35 | 60546.55 | 0.00 | 273381.18 | 82101.62 |
April | 1852857.80 | 26-APR-15:39 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 185283.32 | 60589.08 | 0.00 | 300056.69 | 82101.62 |
May | 1374060.70 | 18-MAY-15:20 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 161006.87 | 62160.41 | 0.00 | 207464.70 | 73475.81 |
June | 1589988.07 | 29-JUN-15:00 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 185382.58 | 61394.98 | 0.00 | 272864.59 | 82101.62 |
July | 1858287.16 | 31-JUL-15:50 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 193746.13 | 63200.70 | 0.00 | 412703.01 | 82101.62 |
August | 2015457.69 | 18-AUG-15:50 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 197236.02 | 63208.66 | 0.00 | 448084.30 | 82101.62 |
September | 1472508.33 | 29-SEP-15:00 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 176055.97 | 64690.32 | 0.00 | 279707.52 | 82101.62 |
October | 1610794.82 | 17-OCT-15:00 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 188946.74 | 62738.25 | 0.00 | 288763.91 | 82101.62 |
November | 1580896.56 | 28-NOV-14:09 | 344233.60 | 675712.68 | 0.00 | 41348.64 | 118232.26 | 60970.53 | 0.00 | 286782.73 | 52106.82 |
December | 1787884.33 | 05-DEC-09:39 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 126151.66 | 59303.73 | 0.00 | 310559.86 | 61337.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1320566.92 | 344233.60 | 439129.89 | 0.00 | 41348.64 | 117909.53 | 59303.73 | 0.00 | 207464.70 | 52106.82 | |
Maximum of Months | 2015457.69 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 197236.02 | 64690.32 | 0.00 | 448084.30 | 82101.62 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 752660.69 | 09-JAN-07:10 | 0.00 | 78854.17 | 25-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 533092.11 | 10-FEB-07:10 | 0.00 | 78860.74 | 02-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 722165.05 | 30-MAR-06:10 | 0.00 | 78672.36 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 583856.90 | 01-APR-06:10 | 0.00 | 77949.89 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 237355.43 | 15-MAY-06:10 | 0.00 | 76893.49 | 05-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 184910.15 | 12-JUN-20:00 | 0.00 | 75748.55 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 253.83 | 07-JUL-20:00 | 0.00 | 74953.92 | 11-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 5721.42 | 28-AUG-06:00 | 0.00 | 74991.35 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 148672.93 | 20-SEP-06:10 | 0.00 | 75679.86 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 323956.89 | 12-OCT-06:10 | 0.00 | 76761.84 | 30-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 411886.16 | 30-NOV-07:10 | 0.00 | 77694.81 | 27-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 612185.97 | 13-DEC-07:10 | 0.00 | 78515.72 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 253.83 | 0.00 | 74953.92 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 752660.69 | 0.00 | 78860.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.83 | 2.83 | 26.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.29 | 0.17 | 26.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.95 | 0.00 | 25.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.00 | 0.00 | 26.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.30 | 0.00 | 26.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.99 | 0.17 | 25.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.06 | 0.00 | 26.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.42 | 0.83 | 26.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.87 | 0.50 | 26.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.84 | 0.17 | 26.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.73 | 0.50 | 26.76 |
Annual Sum or Average | 0.00 | 0.00 | 70.33 | 26.51 | 5.17 | 26.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.87 | 2.83 | 26.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.74 | 0.00 | 25.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.61 | 0.00 | 25.61 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 25.64 | 0.00 | 25.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.74 | 0.00 | 25.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.80 | 0.67 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 27.48 | 5.17 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.80 | 1.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.53 | 2.00 | 27.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.47 | 2.17 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.50 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.12 | 8.00 | 27.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 3.83 | 27.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 5.17 | 27.72 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 27.39 | 22.00 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.73 | 8.00 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.72 | 1.17 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.70 | 5.33 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.52 | 2.83 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 2.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.43 | 7.00 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.05 | 6.33 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.68 | 2.17 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 3.83 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.50 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.56 | 2.17 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 72.83 | 27.40 | 35.33 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.74 | 7.00 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.85 | 0.67 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 27.53 | 3.83 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.85 | 1.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.71 | 1.33 | 27.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.85 | 1.67 | 24.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.05 | 12.17 | 26.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.71 | 3.17 | 27.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.63 | 4.17 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 23.17 | 26.61 | 23.17 | 26.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.71 | 12.17 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.55 | 0.67 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 3.00 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.68 | 2.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.88 | 1.33 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.50 | 27.66 | 8.83 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.88 | 3.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.84 | 0.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 0.33 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.50 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 3.50 | 19.00 | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 0.50 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.54 | 1.00 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.70 | 0.67 | 27.70 |
November | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 2.83 | 19.05 | 0.00 | 19.05 | 1.67 | 22.22 | 1.67 | 23.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.41 | 0.00 | 19.41 | 1.00 | 27.70 | 1.00 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.99 | 0.00 | 18.99 | 0.17 | 20.18 | 0.17 | 21.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.01 | 2.50 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.89 | 6.17 | 26.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.78 | 1.00 | 27.78 |
December | 0.17 | 19.27 | 0.00 | 19.27 | 0.33 | 24.63 | 0.33 | 25.70 |
Annual Sum or Average | 1.50 | 19.04 | 0.00 | 19.04 | 10.33 | 25.59 | 10.17 | 26.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.27 | 0.00 | 19.27 | 6.33 | 27.78 | 6.17 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.33 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 0.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.80 | 3.33 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.79 | 2.33 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.48 | 0.17 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.04 | 1.17 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 1.67 | 19.11 | 0.00 | 19.11 | 10.33 | 26.58 | 8.33 | 27.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.36 | 0.00 | 19.36 | 4.33 | 28.04 | 3.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.86 | 6.00 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 6.00 | 27.86 | 6.00 | 27.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.86 | 6.00 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.88 | 15.83 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.97 | 58.83 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 28.19 | 54.17 | 28.19 |
Annual Sum or Average | 0.00 | 0.00 | 128.83 | 28.05 | 128.83 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 28.19 | 58.83 | 28.19 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 24.00 | 257.83 | 24.97 | 0.00 | 24.97 |
February | 26.83 | 24.00 | 235.33 | 24.85 | 0.00 | 24.85 |
March | 0.00 | 0.00 | 313.33 | 24.67 | 0.00 | 24.67 |
April | 2.83 | 24.00 | 396.67 | 24.60 | 0.00 | 24.60 |
May | 0.83 | 24.00 | 382.67 | 24.62 | 0.00 | 24.62 |
June | 2.17 | 24.00 | 478.50 | 24.44 | 2.17 | 24.44 |
July | 103.33 | 25.13 | 497.00 | 24.67 | 103.33 | 24.74 |
August | 115.17 | 25.04 | 514.00 | 24.56 | 115.17 | 24.63 |
September | 32.50 | 25.49 | 453.50 | 24.62 | 32.50 | 24.67 |
October | 33.17 | 24.64 | 338.00 | 24.85 | 29.83 | 24.84 |
November | 23.50 | 24.18 | 284.17 | 24.93 | 1.33 | 24.94 |
December | 35.17 | 24.00 | 206.00 | 25.17 | 0.00 | 25.17 |
Annual Sum or Average | 401.67 | 24.77 | 4357.00 | 24.70 | 284.33 | 24.72 |
Minimum of Months | 0.00 | 0.00 | 206.00 | 24.44 | 0.00 | 24.44 |
Maximum of Months | 115.17 | 25.49 | 514.00 | 25.17 | 115.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.33 | 24.78 | 255.33 | 24.77 | 12.17 | 24.85 |
February | 20.33 | 24.00 | 258.83 | 24.56 | 0.00 | 24.56 |
March | 0.00 | 0.00 | 336.33 | 24.49 | 0.00 | 24.49 |
April | 2.50 | 24.00 | 437.67 | 24.36 | 0.00 | 24.36 |
May | 0.17 | 23.68 | 387.00 | 24.42 | 0.00 | 24.42 |
June | 0.00 | 0.00 | 485.83 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 497.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 514.00 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 453.17 | 24.36 | 0.00 | 24.36 |
October | 1.83 | 24.00 | 342.17 | 24.55 | 0.00 | 24.55 |
November | 16.17 | 24.43 | 283.50 | 24.68 | 2.17 | 24.70 |
December | 24.33 | 24.00 | 222.67 | 24.79 | 0.00 | 24.79 |
Annual Sum or Average | 108.67 | 24.37 | 4473.50 | 24.45 | 14.33 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 222.67 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 43.33 | 24.78 | 514.00 | 24.79 | 12.17 | 24.85 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 148.33 | 23.74 | 144.83 | 24.08 | 13.00 | 24.06 |
February | 87.17 | 23.71 | 128.33 | 24.11 | 0.00 | 24.11 |
March | 62.83 | 23.68 | 205.83 | 24.19 | 0.00 | 24.19 |
April | 27.17 | 23.57 | 302.17 | 24.26 | 0.00 | 24.26 |
May | 13.67 | 23.52 | 314.00 | 24.34 | 0.00 | 24.34 |
June | 0.17 | 23.55 | 445.50 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 493.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 430.50 | 24.29 | 0.00 | 24.29 |
October | 31.33 | 23.85 | 284.83 | 24.38 | 0.00 | 24.38 |
November | 105.83 | 24.04 | 195.67 | 24.34 | 7.83 | 24.38 |
December | 170.00 | 23.81 | 94.50 | 24.08 | 0.00 | 24.08 |
Annual Sum or Average | 646.50 | 23.79 | 3553.17 | 24.24 | 20.83 | 24.24 |
Minimum of Months | 0.00 | 0.00 | 94.50 | 24.08 | 0.00 | 24.06 |
Maximum of Months | 170.00 | 24.04 | 514.00 | 24.38 | 13.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.50 | 22.82 | 50.00 | 22.83 | 12.83 | 22.73 |
February | 299.00 | 22.91 | 44.17 | 23.05 | 0.00 | 23.05 |
March | 288.83 | 23.05 | 98.00 | 23.30 | 0.00 | 23.30 |
April | 130.50 | 23.11 | 210.00 | 23.77 | 0.00 | 23.77 |
May | 125.83 | 23.22 | 230.17 | 23.87 | 0.00 | 23.87 |
June | 21.17 | 23.37 | 389.83 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 480.67 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 499.50 | 24.18 | 0.00 | 24.18 |
September | 26.17 | 23.45 | 373.33 | 24.15 | 0.33 | 24.15 |
October | 136.33 | 23.43 | 222.83 | 23.93 | 0.00 | 23.93 |
November | 278.67 | 23.20 | 82.17 | 23.42 | 6.50 | 23.44 |
December | 390.33 | 23.01 | 20.17 | 23.05 | 1.33 | 23.04 |
Annual Sum or Average | 2051.33 | 23.05 | 2700.83 | 23.69 | 21.00 | 23.68 |
Minimum of Months | 0.00 | 0.00 | 20.17 | 22.83 | 0.00 | 22.73 |
Maximum of Months | 390.33 | 23.45 | 499.50 | 24.24 | 12.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.00 | 23.18 | 35.50 | 23.29 | 0.00 | 23.29 |
February | 273.00 | 23.31 | 48.67 | 23.41 | 0.00 | 23.41 |
March | 209.83 | 23.21 | 122.83 | 23.54 | 0.00 | 23.54 |
April | 80.33 | 23.44 | 231.33 | 23.98 | 0.00 | 23.98 |
May | 89.83 | 23.43 | 240.17 | 24.00 | 0.00 | 24.00 |
June | 2.00 | 23.32 | 430.67 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 490.83 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 506.17 | 24.16 | 0.00 | 24.16 |
September | 21.67 | 23.39 | 362.67 | 24.16 | 0.00 | 24.16 |
October | 92.50 | 23.59 | 251.83 | 24.12 | 0.00 | 24.12 |
November | 235.83 | 23.51 | 96.50 | 23.74 | 0.00 | 23.74 |
December | 323.33 | 23.51 | 28.00 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 1643.33 | 23.37 | 2845.17 | 23.90 | 0.00 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 28.00 | 23.29 | 0.00 | 23.29 |
Maximum of Months | 323.33 | 23.59 | 506.17 | 24.25 | 0.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.83 | 22.87 | 74.67 | 23.23 | 0.00 | 23.23 |
February | 271.17 | 22.80 | 73.67 | 23.12 | 0.00 | 23.12 |
March | 256.33 | 22.73 | 152.50 | 23.29 | 0.17 | 23.29 |
April | 144.50 | 22.92 | 252.83 | 23.76 | 1.67 | 23.78 |
May | 138.83 | 23.01 | 255.50 | 23.91 | 1.00 | 23.92 |
June | 69.83 | 23.32 | 352.50 | 24.11 | 6.67 | 24.15 |
July | 33.33 | 24.43 | 430.83 | 24.26 | 13.17 | 24.33 |
August | 37.00 | 23.96 | 431.50 | 24.13 | 10.17 | 24.18 |
September | 80.83 | 23.15 | 335.17 | 24.04 | 5.17 | 24.07 |
October | 124.17 | 23.12 | 244.33 | 23.94 | 1.33 | 23.95 |
November | 244.67 | 23.02 | 112.67 | 23.43 | 0.00 | 23.43 |
December | 326.33 | 22.99 | 30.00 | 23.14 | 0.00 | 23.14 |
Annual Sum or Average | 2012.83 | 22.98 | 2746.17 | 23.73 | 39.33 | 23.75 |
Minimum of Months | 33.33 | 22.73 | 30.00 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 326.33 | 24.43 | 431.50 | 24.26 | 13.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.33 | 23.21 | 214.67 | 23.96 | 4.67 | 24.00 |
February | 184.17 | 23.03 | 167.00 | 23.71 | 4.00 | 23.74 |
March | 198.17 | 22.97 | 196.33 | 23.61 | 3.17 | 23.63 |
April | 100.83 | 23.10 | 285.67 | 23.96 | 0.00 | 23.96 |
May | 166.50 | 23.07 | 204.83 | 23.70 | 0.00 | 23.70 |
June | 52.83 | 23.15 | 353.50 | 24.04 | 0.00 | 24.04 |
July | 2.83 | 23.25 | 450.00 | 24.17 | 0.00 | 24.17 |
August | 1.67 | 23.35 | 488.00 | 24.16 | 0.00 | 24.16 |
September | 32.00 | 24.01 | 407.00 | 24.32 | 7.83 | 24.36 |
October | 76.00 | 24.57 | 361.50 | 24.55 | 27.33 | 24.69 |
November | 102.17 | 23.61 | 273.33 | 24.27 | 7.67 | 24.33 |
December | 125.17 | 23.51 | 237.83 | 24.23 | 7.83 | 24.29 |
Annual Sum or Average | 1199.67 | 23.29 | 3639.67 | 24.07 | 62.50 | 24.11 |
Minimum of Months | 1.67 | 22.97 | 167.00 | 23.61 | 0.00 | 23.63 |
Maximum of Months | 198.17 | 24.57 | 488.00 | 24.55 | 27.33 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 221.17 | 22.97 | 153.33 | 23.60 | 0.00 | 23.60 |
February | 104.67 | 23.11 | 218.17 | 24.03 | 0.67 | 24.04 |
March | 50.67 | 23.53 | 357.17 | 24.33 | 5.33 | 24.37 |
April | 28.50 | 26.44 | 469.67 | 24.65 | 24.67 | 24.76 |
May | 63.50 | 23.65 | 364.83 | 24.36 | 11.17 | 24.42 |
June | 20.83 | 26.55 | 485.83 | 24.53 | 19.33 | 24.61 |
July | 50.33 | 26.88 | 497.00 | 24.76 | 50.33 | 24.94 |
August | 45.33 | 26.91 | 514.00 | 24.65 | 45.33 | 24.81 |
September | 19.50 | 25.70 | 444.33 | 24.44 | 14.17 | 24.51 |
October | 41.33 | 24.96 | 383.00 | 24.63 | 19.83 | 24.73 |
November | 38.67 | 24.10 | 320.50 | 24.57 | 6.67 | 24.61 |
December | 38.17 | 23.96 | 298.33 | 24.67 | 5.00 | 24.70 |
Annual Sum or Average | 722.67 | 24.15 | 4506.17 | 24.46 | 202.50 | 24.55 |
Minimum of Months | 19.50 | 22.97 | 153.33 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 221.17 | 26.91 | 514.00 | 24.76 | 50.33 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.00 | 22.29 | 29.83 | 22.27 | 17.33 | 22.21 |
February | 391.67 | 22.38 | 16.33 | 22.41 | 5.33 | 22.39 |
March | 420.50 | 22.48 | 37.17 | 22.59 | 1.17 | 22.59 |
April | 285.00 | 22.89 | 95.67 | 23.17 | 0.00 | 23.17 |
May | 234.17 | 23.10 | 132.83 | 23.44 | 0.00 | 23.44 |
June | 64.00 | 23.29 | 309.00 | 23.95 | 0.00 | 23.95 |
July | 17.83 | 23.58 | 436.00 | 24.12 | 3.33 | 24.13 |
August | 30.50 | 23.20 | 411.33 | 24.01 | 0.33 | 24.01 |
September | 119.67 | 23.16 | 255.50 | 23.77 | 0.00 | 23.77 |
October | 230.50 | 23.12 | 151.00 | 23.54 | 0.00 | 23.54 |
November | 386.67 | 22.66 | 19.33 | 22.69 | 5.17 | 22.67 |
December | 470.67 | 22.43 | 16.83 | 22.40 | 11.83 | 22.36 |
Annual Sum or Average | 3090.17 | 22.64 | 1910.83 | 23.17 | 44.50 | 23.15 |
Minimum of Months | 17.83 | 22.29 | 16.33 | 22.27 | 0.00 | 22.21 |
Maximum of Months | 470.67 | 23.58 | 436.00 | 24.12 | 17.33 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 379.33 | 22.32 | 23.17 | 22.38 | 5.67 | 22.35 |
February | 324.17 | 22.17 | 23.50 | 22.30 | 1.83 | 22.29 |
March | 322.50 | 22.17 | 57.67 | 22.49 | 1.67 | 22.48 |
April | 192.33 | 22.60 | 160.17 | 23.44 | 1.33 | 23.45 |
May | 203.00 | 22.73 | 159.83 | 23.50 | 0.33 | 23.50 |
June | 126.17 | 23.03 | 227.67 | 23.86 | 5.83 | 23.91 |
July | 67.83 | 24.18 | 333.83 | 24.37 | 24.00 | 24.49 |
August | 71.33 | 23.79 | 327.33 | 24.18 | 18.00 | 24.29 |
September | 140.67 | 22.84 | 217.50 | 23.71 | 3.83 | 23.74 |
October | 186.83 | 22.78 | 139.67 | 23.50 | 0.83 | 23.51 |
November | 325.00 | 22.51 | 24.17 | 22.62 | 1.17 | 22.62 |
December | 398.83 | 22.38 | 3.67 | 22.37 | 3.67 | 22.35 |
Annual Sum or Average | 2738.00 | 22.54 | 1698.17 | 23.23 | 68.17 | 23.26 |
Minimum of Months | 67.83 | 22.17 | 3.67 | 22.30 | 0.33 | 22.29 |
Maximum of Months | 398.83 | 24.18 | 333.83 | 24.37 | 24.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.00 | 22.91 | 193.17 | 23.66 | 7.33 | 23.70 |
February | 236.67 | 22.58 | 127.67 | 23.25 | 3.17 | 23.28 |
March | 290.83 | 22.52 | 138.00 | 23.08 | 2.00 | 23.09 |
April | 187.33 | 22.78 | 203.33 | 23.56 | 0.00 | 23.56 |
May | 251.83 | 22.86 | 151.50 | 23.34 | 0.00 | 23.34 |
June | 138.33 | 23.05 | 245.00 | 23.71 | 0.00 | 23.71 |
July | 50.83 | 23.22 | 377.00 | 24.05 | 3.67 | 24.06 |
August | 38.67 | 23.35 | 424.67 | 24.08 | 3.00 | 24.10 |
September | 67.67 | 23.52 | 370.50 | 24.19 | 8.50 | 24.24 |
October | 117.17 | 24.00 | 318.33 | 24.41 | 28.17 | 24.56 |
November | 170.50 | 23.19 | 216.83 | 23.95 | 7.33 | 24.01 |
December | 203.50 | 23.08 | 199.00 | 23.86 | 6.17 | 23.91 |
Annual Sum or Average | 1957.33 | 22.95 | 2965.00 | 23.77 | 69.33 | 23.82 |
Minimum of Months | 38.67 | 22.52 | 127.67 | 23.08 | 0.00 | 23.09 |
Maximum of Months | 290.83 | 24.00 | 424.67 | 24.41 | 28.17 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.00 | 22.21 | 43.17 | 22.35 | 4.50 | 22.33 |
February | 360.83 | 22.25 | 50.50 | 22.49 | 0.00 | 22.49 |
March | 383.17 | 22.32 | 85.83 | 22.65 | 0.33 | 22.65 |
April | 186.33 | 22.74 | 207.83 | 23.58 | 5.00 | 23.62 |
May | 201.50 | 22.83 | 215.83 | 23.62 | 4.33 | 23.65 |
June | 80.83 | 23.17 | 346.17 | 24.05 | 7.17 | 24.10 |
July | 36.67 | 25.30 | 435.33 | 24.42 | 23.33 | 24.53 |
August | 33.50 | 24.59 | 445.67 | 24.25 | 15.00 | 24.32 |
September | 97.50 | 23.11 | 324.33 | 24.00 | 7.67 | 24.05 |
October | 199.00 | 22.97 | 218.00 | 23.68 | 6.50 | 23.73 |
November | 342.00 | 22.52 | 79.17 | 22.84 | 0.00 | 22.84 |
December | 414.83 | 22.37 | 24.17 | 22.46 | 0.00 | 22.46 |
Annual Sum or Average | 2747.17 | 22.56 | 2476.00 | 23.37 | 73.83 | 23.41 |
Minimum of Months | 33.50 | 22.21 | 24.17 | 22.35 | 0.00 | 22.33 |
Maximum of Months | 414.83 | 25.30 | 445.67 | 24.42 | 23.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.17 | 21.43 | 113.33 | 21.17 | 112.33 | 20.98 |
February | 435.00 | 21.56 | 71.83 | 21.37 | 69.17 | 21.21 |
March | 470.17 | 21.71 | 67.33 | 21.65 | 47.83 | 21.53 |
April | 340.83 | 22.28 | 88.50 | 22.56 | 9.17 | 22.51 |
May | 308.33 | 22.50 | 107.00 | 22.86 | 2.67 | 22.84 |
June | 163.00 | 22.98 | 245.17 | 23.63 | 0.00 | 23.63 |
July | 66.67 | 23.06 | 363.33 | 23.95 | 3.00 | 23.96 |
August | 115.83 | 22.98 | 335.50 | 23.76 | 2.00 | 23.77 |
September | 222.17 | 22.78 | 183.67 | 23.34 | 0.00 | 23.34 |
October | 299.17 | 22.52 | 125.00 | 22.95 | 6.83 | 22.90 |
November | 470.50 | 21.92 | 56.00 | 21.79 | 50.67 | 21.65 |
December | 491.67 | 21.47 | 119.00 | 21.23 | 119.00 | 21.06 |
Annual Sum or Average | 3865.50 | 22.01 | 1875.67 | 22.39 | 422.67 | 22.24 |
Minimum of Months | 66.67 | 21.43 | 56.00 | 21.17 | 0.00 | 20.98 |
Maximum of Months | 491.67 | 23.06 | 363.33 | 23.95 | 119.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.17 | 21.74 | 73.17 | 21.59 | 62.83 | 21.44 |
February | 399.67 | 21.72 | 50.33 | 21.64 | 38.50 | 21.51 |
March | 414.33 | 21.78 | 74.67 | 21.95 | 23.83 | 21.87 |
April | 224.83 | 22.19 | 194.00 | 23.11 | 3.00 | 23.09 |
May | 255.67 | 22.38 | 177.67 | 23.16 | 0.83 | 23.16 |
June | 162.33 | 22.79 | 273.50 | 23.69 | 4.33 | 23.72 |
July | 80.67 | 23.86 | 399.00 | 24.25 | 24.00 | 24.36 |
August | 88.83 | 23.38 | 392.67 | 24.05 | 16.17 | 24.13 |
September | 181.50 | 22.59 | 248.67 | 23.51 | 2.33 | 23.52 |
October | 240.50 | 22.46 | 154.67 | 23.15 | 2.83 | 23.14 |
November | 448.83 | 22.14 | 27.00 | 22.11 | 18.00 | 22.05 |
December | 480.83 | 21.78 | 41.83 | 21.66 | 40.83 | 21.56 |
Annual Sum or Average | 3444.17 | 22.11 | 2107.17 | 22.78 | 237.50 | 22.73 |
Minimum of Months | 80.67 | 21.72 | 27.00 | 21.59 | 0.83 | 21.44 |
Maximum of Months | 480.83 | 23.86 | 399.00 | 24.25 | 62.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 277.17 | 22.14 | 167.83 | 22.66 | 33.50 | 22.48 |
February | 296.00 | 21.87 | 121.83 | 22.41 | 21.33 | 22.29 |
March | 360.50 | 21.88 | 131.00 | 22.29 | 27.67 | 22.20 |
April | 253.83 | 22.32 | 180.17 | 23.07 | 7.17 | 23.05 |
May | 315.33 | 22.33 | 128.67 | 22.81 | 3.00 | 22.79 |
June | 215.83 | 22.73 | 201.50 | 23.36 | 0.00 | 23.36 |
July | 106.33 | 22.88 | 329.33 | 23.82 | 3.67 | 23.83 |
August | 92.50 | 22.92 | 369.50 | 23.88 | 4.83 | 23.90 |
September | 125.17 | 22.98 | 307.00 | 23.91 | 8.67 | 23.97 |
October | 174.50 | 23.16 | 272.67 | 23.99 | 20.50 | 24.12 |
November | 249.17 | 22.49 | 173.17 | 23.20 | 13.50 | 23.16 |
December | 271.83 | 22.31 | 156.17 | 22.90 | 24.50 | 22.77 |
Annual Sum or Average | 2738.17 | 22.37 | 2538.83 | 23.19 | 168.33 | 23.15 |
Minimum of Months | 92.50 | 21.87 | 121.83 | 22.29 | 0.00 | 22.20 |
Maximum of Months | 360.50 | 23.16 | 369.50 | 23.99 | 33.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.67 | 21.60 | 93.50 | 21.56 | 65.83 | 21.41 |
February | 390.67 | 21.64 | 64.67 | 21.74 | 30.17 | 21.64 |
March | 419.83 | 21.71 | 88.33 | 21.94 | 25.33 | 21.87 |
April | 265.67 | 22.38 | 168.17 | 23.09 | 9.83 | 23.11 |
May | 273.00 | 22.42 | 168.83 | 23.14 | 6.83 | 23.18 |
June | 147.00 | 22.82 | 286.00 | 23.74 | 8.00 | 23.79 |
July | 77.67 | 23.93 | 399.67 | 24.25 | 25.00 | 24.37 |
August | 86.83 | 23.42 | 397.83 | 24.04 | 17.67 | 24.13 |
September | 165.50 | 22.72 | 257.50 | 23.63 | 6.83 | 23.68 |
October | 262.33 | 22.53 | 171.00 | 23.24 | 7.17 | 23.30 |
November | 396.33 | 21.96 | 77.67 | 22.11 | 25.33 | 22.02 |
December | 451.83 | 21.75 | 68.17 | 21.66 | 57.33 | 21.53 |
Annual Sum or Average | 3385.33 | 22.09 | 2241.33 | 22.80 | 285.33 | 22.76 |
Minimum of Months | 77.67 | 21.60 | 64.67 | 21.56 | 6.83 | 21.41 |
Maximum of Months | 451.83 | 23.93 | 399.67 | 24.25 | 65.83 | 24.37 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 12.50 | 27.00 | 454.00 | 27.00 | 12.50 | 27.00 |
March | 51.33 | 27.00 | 514.00 | 27.00 | 51.33 | 27.00 |
April | 244.50 | 27.00 | 485.00 | 27.00 | 244.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 51.00 | 27.00 | 496.00 | 27.00 | 51.00 | 27.00 |
July | 219.83 | 27.00 | 497.00 | 27.00 | 219.83 | 27.00 |
August | 343.83 | 27.00 | 514.00 | 27.00 | 343.83 | 27.00 |
September | 11.17 | 27.00 | 485.00 | 27.00 | 11.17 | 27.00 |
October | 32.50 | 27.00 | 502.00 | 27.00 | 32.50 | 27.00 |
November | 63.00 | 27.00 | 489.00 | 27.00 | 63.00 | 27.00 |
December | 98.83 | 27.07 | 497.00 | 27.03 | 98.83 | 27.03 |
Annual Sum or Average | 1128.50 | 27.01 | 5943.00 | 27.00 | 1128.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 343.83 | 27.07 | 514.00 | 27.03 | 343.83 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 4.00 | 27.00 | 485.00 | 27.00 | 4.00 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.33 | 27.00 | 497.00 | 27.00 | 0.33 | 27.00 |
August | 28.50 | 27.00 | 514.00 | 27.00 | 28.50 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 1.83 | 27.00 | 502.00 | 27.00 | 1.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.67 | 27.00 | 497.00 | 27.01 | 0.67 | 27.01 |
Annual Sum or Average | 35.33 | 27.00 | 5943.00 | 27.00 | 35.33 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 28.50 | 27.00 | 514.00 | 27.01 | 28.50 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 25.53 | 476.67 | 26.96 | 0.00 | 26.96 |
February | 0.00 | 0.00 | 446.83 | 27.00 | 0.00 | 27.00 |
March | 1.17 | 27.00 | 514.00 | 27.00 | 1.17 | 27.00 |
April | 24.33 | 27.00 | 485.00 | 27.00 | 24.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.50 | 27.00 | 496.00 | 27.00 | 0.50 | 27.00 |
July | 48.67 | 27.00 | 497.00 | 27.00 | 48.67 | 27.00 |
August | 105.00 | 27.00 | 514.00 | 27.00 | 105.00 | 27.00 |
September | 2.50 | 27.00 | 485.00 | 27.00 | 2.50 | 27.00 |
October | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.50 | 27.00 | 497.00 | 27.00 | 0.50 | 27.00 |
Annual Sum or Average | 198.17 | 26.92 | 5910.50 | 27.00 | 187.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 446.83 | 26.96 | 0.00 | 26.96 |
Maximum of Months | 105.00 | 27.00 | 514.00 | 27.00 | 105.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.04 | 485.00 | 27.04 | 485.00 | 27.04 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.16 | 497.00 | 27.16 | 497.00 | 27.16 |
Annual Sum or Average | 5943.00 | 27.03 | 5943.00 | 27.03 | 5943.00 | 27.03 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00027 | 32.25054 | 0.88548 | 21.63694 |
February | 454.00000 | 27.00034 | 33.08090 | 0.92932 | 23.31539 |
March | 514.00000 | 27.00028 | 34.43592 | 0.97882 | 25.28217 |
April | 485.00000 | 27.00012 | 35.37810 | 1.03543 | 27.67423 |
May | 508.00000 | 27.00063 | 36.53776 | 0.26958 | 6.58252 |
June | 496.00000 | 27.00089 | 37.05004 | 0.34091 | 7.47072 |
July | 497.00000 | 27.00070 | 37.47366 | 0.39808 | 8.35050 |
August | 514.00000 | 27.00024 | 37.43911 | 0.44061 | 9.09903 |
September | 485.00000 | 27.00109 | 37.91670 | 0.29714 | 6.90496 |
October | 502.00000 | 27.00058 | 34.30663 | 0.96769 | 24.83127 |
November | 489.00000 | 27.00021 | 32.06334 | 0.97049 | 24.97215 |
December | 497.00000 | 27.01868 | 29.65045 | 0.98035 | 25.37313 |
Annual Sum or Average | 5943.00000 | 27.00201 | 34.81404 | 0.70566 | 17.56293 |
Minimum of Months | 454.00000 | 27.00012 | 29.65045 | 0.26958 | 6.58252 |
Maximum of Months | 514.00000 | 27.01868 | 37.91670 | 1.03543 | 27.67423 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00025 | 32.31082 | 0.81004 | 18.96073 |
February | 454.00000 | 27.00032 | 33.10447 | 0.83657 | 19.86967 |
March | 514.00000 | 27.00027 | 34.42406 | 0.86830 | 20.99419 |
April | 485.00000 | 27.00013 | 35.35861 | 0.92465 | 23.13820 |
May | 508.00000 | 27.00060 | 36.62455 | 0.19439 | 5.89441 |
June | 496.00000 | 27.00085 | 37.08809 | 0.24896 | 6.36986 |
July | 497.00000 | 27.00071 | 37.49544 | 0.29164 | 6.83658 |
August | 514.00000 | 27.00024 | 37.44757 | 0.31273 | 7.11049 |
September | 485.00000 | 27.00087 | 38.07085 | 0.22910 | 6.18464 |
October | 502.00000 | 27.00054 | 34.33226 | 0.89404 | 21.95051 |
November | 489.00000 | 27.00021 | 32.04637 | 0.86030 | 20.73511 |
December | 497.00000 | 27.00672 | 29.63225 | 0.83938 | 19.96450 |
Annual Sum or Average | 5943.00000 | 27.00098 | 34.84329 | 0.60692 | 14.78026 |
Minimum of Months | 454.00000 | 27.00013 | 29.63225 | 0.19439 | 5.89441 |
Maximum of Months | 514.00000 | 27.00672 | 38.07085 | 0.92465 | 23.13820 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94915 | 32.74078 | 0.74082 | 16.91550 |
February | 454.00000 | 27.00032 | 33.16239 | 0.78036 | 18.04370 |
March | 514.00000 | 27.00028 | 34.45854 | 0.81951 | 19.34725 |
April | 485.00000 | 27.00015 | 35.38236 | 0.89923 | 22.24928 |
May | 508.00000 | 27.00068 | 36.68679 | 0.16209 | 5.81417 |
June | 496.00000 | 27.00087 | 37.10636 | 0.23790 | 6.37025 |
July | 497.00000 | 27.00074 | 37.50763 | 0.29511 | 6.96628 |
August | 514.00000 | 27.00025 | 37.46433 | 0.31094 | 7.18198 |
September | 485.00000 | 27.00094 | 38.13082 | 0.20932 | 6.10841 |
October | 502.00000 | 27.00054 | 34.35637 | 0.86936 | 21.09537 |
November | 489.00000 | 27.00022 | 32.07641 | 0.80758 | 18.95243 |
December | 497.00000 | 27.00126 | 29.64889 | 0.77409 | 17.80929 |
Annual Sum or Average | 5943.00000 | 26.99623 | 34.90906 | 0.57343 | 13.85786 |
Minimum of Months | 454.00000 | 26.94915 | 29.64889 | 0.16209 | 5.81417 |
Maximum of Months | 514.00000 | 27.00126 | 38.13082 | 0.89923 | 22.24928 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00083 | 33.79348 | 1.10622 | 30.81971 |
February | 454.00000 | 27.00103 | 34.46323 | 1.25185 | 37.82889 |
March | 514.00000 | 27.00034 | 34.73292 | 1.39788 | 45.40410 |
April | 485.00000 | 27.03800 | 35.74115 | 1.54943 | 53.59023 |
May | 508.00000 | 27.00101 | 36.08289 | 0.52388 | 10.79869 |
June | 496.00000 | 27.00112 | 36.65894 | 0.74775 | 16.79501 |
July | 497.00000 | 27.00076 | 37.13069 | 0.96208 | 24.57005 |
August | 514.00000 | 27.17521 | 37.10145 | 1.20386 | 35.54898 |
September | 485.00000 | 27.00186 | 36.91956 | 0.56310 | 11.68859 |
October | 502.00000 | 27.00119 | 34.78271 | 1.28320 | 39.42000 |
November | 489.00000 | 27.00159 | 33.97463 | 1.41392 | 46.26002 |
December | 497.00000 | 27.15529 | 32.80845 | 1.56074 | 54.19260 |
Annual Sum or Average | 5943.00000 | 27.03205 | 35.35607 | 1.12939 | 33.86960 |
Minimum of Months | 454.00000 | 27.00034 | 32.80845 | 0.52388 | 10.79869 |
Maximum of Months | 514.00000 | 27.17521 | 37.13069 | 1.56074 | 54.19260 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55146 | 34.90280 | 0.47326 | 10.35673 |
February | 454.00000 | 24.49733 | 37.64769 | 0.47453 | 10.29795 |
March | 514.00000 | 24.40908 | 40.45568 | 0.47895 | 10.21651 |
April | 485.00000 | 24.49968 | 44.20022 | 0.52612 | 11.24201 |
May | 508.00000 | 24.46607 | 43.65393 | -0.3454 | 8.32015 |
June | 496.00000 | 24.42519 | 50.44370 | -0.3034 | 7.64445 |
July | 497.00000 | 24.57421 | 56.97816 | -0.2057 | 6.99479 |
August | 514.00000 | 24.45008 | 58.36347 | -0.2251 | 6.95918 |
September | 485.00000 | 24.51819 | 52.25025 | -0.2557 | 7.45898 |
October | 502.00000 | 24.59116 | 41.82093 | 0.53894 | 11.89854 |
November | 489.00000 | 24.59152 | 35.82747 | 0.49655 | 10.97773 |
December | 497.00000 | 24.58286 | 31.02831 | 0.45869 | 10.26231 |
Annual Sum or Average | 5943.00000 | 24.51264 | 44.02389 | 0.17295 | 9.37386 |
Minimum of Months | 454.00000 | 24.40908 | 31.02831 | -0.3454 | 6.95918 |
Maximum of Months | 514.00000 | 24.59152 | 58.36347 | 0.53894 | 11.89854 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40297 | 37.56893 | 0.46073 | 10.19600 |
February | 454.00000 | 24.34800 | 38.81657 | 0.46049 | 9.79225 |
March | 514.00000 | 24.32030 | 41.62830 | 0.48316 | 10.19966 |
April | 485.00000 | 24.32808 | 45.10581 | 0.52092 | 10.92612 |
May | 508.00000 | 24.31574 | 45.00248 | -0.3635 | 8.22612 |
June | 496.00000 | 24.31235 | 50.96083 | -0.3044 | 7.41913 |
July | 497.00000 | 24.30652 | 54.48025 | -0.2696 | 6.83826 |
August | 514.00000 | 24.25177 | 55.18145 | -0.2697 | 6.79534 |
September | 485.00000 | 24.33891 | 52.07737 | -0.2947 | 7.37313 |
October | 502.00000 | 24.38080 | 42.17576 | 0.51068 | 10.93823 |
November | 489.00000 | 24.42642 | 36.79393 | 0.47999 | 10.38664 |
December | 497.00000 | 24.41223 | 31.57580 | 0.44190 | 9.60033 |
Annual Sum or Average | 5943.00000 | 24.34495 | 44.32922 | 0.15158 | 9.04820 |
Minimum of Months | 454.00000 | 24.25177 | 31.57580 | -0.3635 | 6.79534 |
Maximum of Months | 514.00000 | 24.42642 | 55.18145 | 0.52092 | 10.93823 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09884 | 38.96395 | 0.36379 | 8.07467 |
February | 454.00000 | 24.09001 | 40.23376 | 0.37334 | 8.11855 |
March | 514.00000 | 24.11519 | 42.81920 | 0.40032 | 8.53568 |
April | 485.00000 | 24.17630 | 46.21280 | 0.44945 | 9.44098 |
May | 508.00000 | 24.21379 | 45.69177 | -0.4276 | 9.13953 |
June | 496.00000 | 24.22147 | 51.64467 | -0.3676 | 8.10763 |
July | 497.00000 | 24.24912 | 55.39212 | -0.3272 | 7.50930 |
August | 514.00000 | 24.21149 | 56.25167 | -0.3268 | 7.46183 |
September | 485.00000 | 24.25153 | 52.68341 | -0.3516 | 7.94127 |
October | 502.00000 | 24.24660 | 43.03438 | 0.45464 | 9.67212 |
November | 489.00000 | 24.22357 | 38.24460 | 0.39988 | 8.80890 |
December | 497.00000 | 24.10064 | 33.20296 | 0.33072 | 7.57635 |
Annual Sum or Average | 5943.00000 | 24.18363 | 45.41089 | 0.07797 | 8.36568 |
Minimum of Months | 454.00000 | 24.09001 | 33.20296 | -0.4276 | 7.46183 |
Maximum of Months | 514.00000 | 24.25153 | 56.25167 | 0.45464 | 9.67212 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16462 | 41.64864 | 0.11713 | 6.75525 |
February | 454.00000 | 23.28416 | 43.07092 | 0.16302 | 6.61536 |
March | 514.00000 | 23.47727 | 44.90107 | 0.22933 | 7.00599 |
April | 485.00000 | 23.83247 | 47.46831 | 0.36300 | 8.36037 |
May | 508.00000 | 23.91519 | 46.88537 | -0.5355 | 11.86621 |
June | 496.00000 | 24.11600 | 52.15877 | -0.4022 | 8.71174 |
July | 497.00000 | 24.22354 | 55.56076 | -0.3263 | 7.49209 |
August | 514.00000 | 24.16512 | 56.53755 | -0.3364 | 7.57738 |
September | 485.00000 | 24.10035 | 53.60091 | -0.4078 | 8.86237 |
October | 502.00000 | 23.97145 | 44.39939 | 0.38171 | 8.60419 |
November | 489.00000 | 23.56202 | 40.66488 | 0.22331 | 6.98333 |
December | 497.00000 | 23.22001 | 36.43406 | 0.10172 | 6.23844 |
Annual Sum or Average | 5943.00000 | 23.75579 | 46.98021 | -0.0381 | 7.93382 |
Minimum of Months | 454.00000 | 23.16462 | 36.43406 | -0.5355 | 6.23844 |
Maximum of Months | 514.00000 | 24.22354 | 56.53755 | 0.38171 | 11.86621 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53237 | 36.86112 | 0.20428 | 6.57390 |
February | 454.00000 | 23.58225 | 39.56321 | 0.24328 | 6.69741 |
March | 514.00000 | 23.69905 | 42.35183 | 0.29749 | 7.37668 |
April | 485.00000 | 23.97351 | 45.39568 | 0.40618 | 8.68961 |
May | 508.00000 | 23.99228 | 44.92168 | -0.4961 | 10.62690 |
June | 496.00000 | 24.18069 | 50.53307 | -0.3625 | 8.04239 |
July | 497.00000 | 24.24211 | 54.15420 | -0.2983 | 7.11828 |
August | 514.00000 | 24.15536 | 55.09421 | -0.3217 | 7.35390 |
September | 485.00000 | 24.08495 | 52.15554 | -0.4080 | 8.85269 |
October | 502.00000 | 24.08524 | 42.27176 | 0.41512 | 9.07634 |
November | 489.00000 | 23.81876 | 37.33361 | 0.29389 | 7.30782 |
December | 497.00000 | 23.70412 | 31.88269 | 0.22481 | 6.44423 |
Annual Sum or Average | 5943.00000 | 23.92298 | 44.41984 | 0.01403 | 7.85431 |
Minimum of Months | 454.00000 | 23.53237 | 31.88269 | -0.4961 | 6.44423 |
Maximum of Months | 514.00000 | 24.24211 | 55.09421 | 0.41512 | 10.62690 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44616 | 36.48101 | 0.22036 | 6.98314 |
February | 454.00000 | 23.32250 | 39.81931 | 0.21769 | 6.91606 |
March | 514.00000 | 23.41458 | 42.65956 | 0.26854 | 7.60696 |
April | 485.00000 | 23.75876 | 45.70773 | 0.40441 | 9.25394 |
May | 508.00000 | 23.88224 | 44.94576 | -0.4738 | 11.32786 |
June | 496.00000 | 23.98817 | 50.91763 | -0.3742 | 9.17587 |
July | 497.00000 | 24.11303 | 54.29270 | -0.2775 | 7.75519 |
August | 514.00000 | 23.99282 | 55.30972 | -0.3073 | 8.01726 |
September | 485.00000 | 23.92308 | 52.34152 | -0.3994 | 9.59041 |
October | 502.00000 | 23.89673 | 42.52111 | 0.40838 | 9.24720 |
November | 489.00000 | 23.57322 | 37.57396 | 0.26903 | 7.30071 |
December | 497.00000 | 23.36878 | 32.18463 | 0.18137 | 6.41008 |
Annual Sum or Average | 5943.00000 | 23.72602 | 44.60502 | 0.00915 | 8.30790 |
Minimum of Months | 454.00000 | 23.32250 | 32.18463 | -0.4738 | 6.41008 |
Maximum of Months | 514.00000 | 24.11303 | 55.30972 | 0.40838 | 11.32786 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.95036 | 35.22663 | 0.37943 | 9.25618 |
February | 454.00000 | 23.74583 | 38.76307 | 0.33788 | 8.67331 |
March | 514.00000 | 23.67408 | 41.92561 | 0.33367 | 8.53023 |
April | 485.00000 | 23.94598 | 45.19276 | 0.43599 | 9.65966 |
May | 508.00000 | 23.75908 | 45.43074 | -0.5562 | 12.58983 |
June | 496.00000 | 23.97643 | 51.13291 | -0.4260 | 9.31316 |
July | 497.00000 | 24.11581 | 54.48169 | -0.3273 | 7.66871 |
August | 514.00000 | 24.13194 | 54.94971 | -0.2853 | 7.19800 |
September | 485.00000 | 24.20828 | 51.40737 | -0.2917 | 7.92513 |
October | 502.00000 | 24.32608 | 41.31176 | 0.53799 | 12.19066 |
November | 489.00000 | 24.16072 | 36.05127 | 0.44962 | 10.27247 |
December | 497.00000 | 24.13383 | 30.49405 | 0.41156 | 9.71200 |
Annual Sum or Average | 5943.00000 | 24.01129 | 43.91190 | 0.08021 | 9.42173 |
Minimum of Months | 454.00000 | 23.67408 | 30.49405 | -0.5562 | 7.19800 |
Maximum of Months | 514.00000 | 24.32608 | 54.94971 | 0.53799 | 12.58983 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68949 | 35.65122 | 0.30764 | 7.93441 |
February | 454.00000 | 23.98037 | 37.91054 | 0.41522 | 9.35958 |
March | 514.00000 | 24.19226 | 40.36299 | 0.50785 | 11.14255 |
April | 485.00000 | 24.51566 | 43.44122 | 0.66343 | 15.09775 |
May | 508.00000 | 24.17837 | 43.95267 | -0.3188 | 8.72369 |
June | 496.00000 | 24.42275 | 49.39937 | -0.1394 | 6.67801 |
July | 497.00000 | 24.54266 | 52.72218 | -0.0243 | 6.50269 |
August | 514.00000 | 24.44585 | 53.54560 | -0.0209 | 6.29619 |
September | 485.00000 | 24.30760 | 50.96871 | -0.2076 | 7.19349 |
October | 502.00000 | 24.39950 | 40.95372 | 0.57747 | 12.94568 |
November | 489.00000 | 24.36107 | 35.39813 | 0.51445 | 11.38102 |
December | 497.00000 | 24.40974 | 29.76537 | 0.49225 | 10.83474 |
Annual Sum or Average | 5943.00000 | 24.28828 | 42.88422 | 0.22838 | 9.49550 |
Minimum of Months | 454.00000 | 23.68949 | 29.76537 | -0.3188 | 6.29619 |
Maximum of Months | 514.00000 | 24.54266 | 53.54560 | 0.66343 | 15.09775 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49835 | 38.84952 | -0.0528 | 6.66057 |
February | 454.00000 | 22.59890 | 42.00797 | -0.0017 | 6.23485 |
March | 514.00000 | 22.74533 | 44.98333 | 0.05532 | 6.35456 |
April | 485.00000 | 23.33935 | 47.47357 | 0.23264 | 6.94921 |
May | 508.00000 | 23.58223 | 46.24227 | -0.6550 | 14.99660 |
June | 496.00000 | 23.92779 | 51.62821 | -0.4743 | 10.09109 |
July | 497.00000 | 24.07514 | 55.55224 | -0.3857 | 8.38567 |
August | 514.00000 | 23.94702 | 57.07122 | -0.4250 | 9.08058 |
September | 485.00000 | 23.77400 | 53.52170 | -0.5332 | 11.53485 |
October | 502.00000 | 23.63731 | 43.73449 | 0.29110 | 7.65771 |
November | 489.00000 | 22.93734 | 39.61255 | 0.06671 | 6.35749 |
December | 497.00000 | 22.50838 | 34.12634 | -0.0768 | 6.31928 |
Annual Sum or Average | 5943.00000 | 23.30240 | 46.27410 | -0.1653 | 8.40610 |
Minimum of Months | 454.00000 | 22.49835 | 34.12634 | -0.6550 | 6.23485 |
Maximum of Months | 514.00000 | 24.07514 | 57.07122 | 0.29110 | 14.99660 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.50907 | 38.11208 | -0.0140 | 6.35657 |
February | 385.00000 | 22.47247 | 41.57451 | 0.00502 | 6.30429 |
March | 433.00000 | 22.65860 | 43.92146 | 0.07265 | 6.88797 |
April | 410.00000 | 23.47098 | 46.39209 | 0.31224 | 8.50639 |
May | 430.00000 | 23.53742 | 45.75829 | -0.6104 | 15.21773 |
June | 418.00000 | 23.77640 | 51.58217 | -0.4662 | 11.46166 |
July | 422.00000 | 24.13600 | 54.84049 | -0.2946 | 8.72818 |
August | 433.00000 | 23.97737 | 56.35718 | -0.3348 | 9.03669 |
September | 410.00000 | 23.65687 | 53.32424 | -0.5100 | 12.28675 |
October | 427.00000 | 23.56369 | 43.78976 | 0.31508 | 8.25018 |
November | 417.00000 | 22.83402 | 39.14611 | 0.08085 | 6.28638 |
December | 422.00000 | 22.46888 | 33.42552 | -0.0485 | 6.03303 |
Annual Sum or Average | 5034.00000 | 23.25972 | 45.70763 | -0.1256 | 8.79421 |
Minimum of Months | 385.00000 | 22.46888 | 33.42552 | -0.6104 | 6.03303 |
Maximum of Months | 433.00000 | 24.13600 | 56.35718 | 0.31508 | 15.21773 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70648 | 35.44798 | 0.31805 | 8.98544 |
February | 454.00000 | 23.36955 | 39.58236 | 0.24362 | 8.24371 |
March | 514.00000 | 23.21094 | 43.04595 | 0.21366 | 7.90203 |
April | 485.00000 | 23.62108 | 46.21668 | 0.34050 | 8.61457 |
May | 508.00000 | 23.45078 | 46.33741 | -0.6724 | 16.06692 |
June | 496.00000 | 23.71234 | 52.18901 | -0.5317 | 11.69417 |
July | 497.00000 | 23.95539 | 55.76688 | -0.4054 | 9.07810 |
August | 514.00000 | 23.99563 | 56.44964 | -0.3560 | 8.40011 |
September | 485.00000 | 24.08937 | 51.96979 | -0.3426 | 8.87998 |
October | 502.00000 | 24.18529 | 41.79566 | 0.49591 | 11.63512 |
November | 489.00000 | 23.91118 | 36.57582 | 0.37984 | 9.58975 |
December | 497.00000 | 23.84097 | 30.80016 | 0.32770 | 9.06213 |
Annual Sum or Average | 5943.00000 | 23.75515 | 44.73202 | -0.0022 | 9.86466 |
Minimum of Months | 454.00000 | 23.21094 | 30.80016 | -0.6724 | 7.90203 |
Maximum of Months | 514.00000 | 24.18529 | 56.44964 | 0.49591 | 16.06692 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53438 | 37.86143 | 0.00322 | 6.61246 |
February | 454.00000 | 22.61386 | 41.09324 | 0.05357 | 6.55543 |
March | 514.00000 | 22.74569 | 44.04108 | 0.11112 | 6.92296 |
April | 485.00000 | 23.59306 | 46.11228 | 0.36154 | 9.25437 |
May | 508.00000 | 23.62397 | 45.56793 | -0.5551 | 13.98406 |
June | 496.00000 | 23.93902 | 51.15827 | -0.3761 | 9.49312 |
July | 497.00000 | 24.20984 | 54.62056 | -0.2378 | 7.65836 |
August | 514.00000 | 24.07640 | 55.97745 | -0.2720 | 7.82849 |
September | 485.00000 | 23.89192 | 52.57934 | -0.3990 | 9.91554 |
October | 502.00000 | 23.65696 | 43.04911 | 0.35295 | 9.03303 |
November | 489.00000 | 22.98256 | 38.51561 | 0.13269 | 6.90320 |
December | 497.00000 | 22.63667 | 32.97178 | 0.00533 | 6.33126 |
Annual Sum or Average | 5943.00000 | 23.38002 | 45.33719 | -0.0701 | 8.38816 |
Minimum of Months | 454.00000 | 22.53438 | 32.97178 | -0.5551 | 6.33126 |
Maximum of Months | 514.00000 | 24.20984 | 55.97745 | 0.36154 | 13.98406 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52916 | 40.77178 | -0.3011 | 9.57228 |
February | 454.00000 | 21.65595 | 43.97287 | -0.2394 | 8.21081 |
March | 514.00000 | 21.89385 | 46.86852 | -0.1569 | 7.54609 |
April | 485.00000 | 22.77369 | 48.96303 | 0.10003 | 6.93014 |
May | 508.00000 | 23.07063 | 47.62141 | -0.8233 | 21.65906 |
June | 496.00000 | 23.65291 | 52.48601 | -0.5587 | 12.69867 |
July | 497.00000 | 23.90751 | 56.14968 | -0.4281 | 9.53054 |
August | 514.00000 | 23.74058 | 57.89826 | -0.4825 | 10.72026 |
September | 485.00000 | 23.40216 | 54.85822 | -0.6523 | 15.45367 |
October | 502.00000 | 23.14256 | 45.06574 | 0.17342 | 7.48734 |
November | 489.00000 | 21.99680 | 41.49192 | -0.1658 | 7.54883 |
December | 497.00000 | 21.49886 | 35.84543 | -0.3337 | 9.28888 |
Annual Sum or Average | 5943.00000 | 22.69620 | 47.70207 | -0.3238 | 10.58096 |
Minimum of Months | 454.00000 | 21.49886 | 35.84543 | -0.8233 | 6.93014 |
Maximum of Months | 514.00000 | 23.90751 | 57.89826 | 0.17342 | 21.65906 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88929 | 39.43189 | -0.1799 | 7.85869 |
February | 454.00000 | 21.96734 | 42.86366 | -0.1351 | 7.40449 |
March | 514.00000 | 22.20949 | 45.48031 | -0.0452 | 7.47744 |
April | 485.00000 | 23.22483 | 47.22727 | 0.25851 | 8.46348 |
May | 508.00000 | 23.26210 | 46.64081 | -0.6953 | 18.46850 |
June | 496.00000 | 23.65041 | 52.06501 | -0.4892 | 12.45637 |
July | 497.00000 | 24.07422 | 55.06699 | -0.2860 | 8.66873 |
August | 514.00000 | 23.91596 | 56.55819 | -0.3287 | 9.06874 |
September | 485.00000 | 23.50034 | 54.01087 | -0.5492 | 13.78023 |
October | 502.00000 | 23.31726 | 44.32269 | 0.25692 | 7.99421 |
November | 489.00000 | 22.27567 | 40.40750 | -0.0644 | 6.61832 |
December | 497.00000 | 21.84466 | 34.74409 | -0.2161 | 7.43532 |
Annual Sum or Average | 5943.00000 | 22.93442 | 46.60379 | -0.2074 | 9.66064 |
Minimum of Months | 454.00000 | 21.84466 | 34.74409 | -0.6953 | 6.61832 |
Maximum of Months | 514.00000 | 24.07422 | 56.55819 | 0.25851 | 18.46850 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07541 | 36.81352 | 0.14338 | 8.88400 |
February | 454.00000 | 22.71118 | 41.11743 | 0.06631 | 8.47401 |
March | 514.00000 | 22.54820 | 44.61591 | 0.04225 | 8.25172 |
April | 485.00000 | 23.17363 | 47.41893 | 0.23424 | 8.35806 |
May | 508.00000 | 22.96063 | 47.63914 | -0.8340 | 22.56375 |
June | 496.00000 | 23.40667 | 53.09982 | -0.6237 | 14.84914 |
July | 497.00000 | 23.77723 | 56.39362 | -0.4488 | 10.41479 |
August | 514.00000 | 23.81479 | 57.18132 | -0.4028 | 9.76901 |
September | 485.00000 | 23.82476 | 52.95796 | -0.4270 | 11.32041 |
October | 502.00000 | 23.84952 | 42.78465 | 0.41366 | 10.88324 |
November | 489.00000 | 23.35899 | 37.83988 | 0.23031 | 8.68405 |
December | 497.00000 | 23.23618 | 31.91195 | 0.15735 | 8.46852 |
Annual Sum or Average | 5943.00000 | 23.31380 | 45.86268 | -0.1236 | 10.94332 |
Minimum of Months | 454.00000 | 22.54820 | 31.91195 | -0.8340 | 8.25172 |
Maximum of Months | 514.00000 | 23.84952 | 57.18132 | 0.41366 | 22.56375 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.85676 | 39.31974 | -0.1774 | 8.19406 |
February | 454.00000 | 21.97472 | 42.48458 | -0.1156 | 7.53866 |
March | 514.00000 | 22.12831 | 45.49147 | -0.0473 | 7.50995 |
April | 485.00000 | 23.15110 | 47.27230 | 0.25840 | 8.80884 |
May | 508.00000 | 23.19350 | 46.68829 | -0.6950 | 19.17896 |
June | 496.00000 | 23.67128 | 51.94919 | -0.4543 | 11.88333 |
July | 497.00000 | 24.05022 | 55.19162 | -0.2740 | 8.59237 |
August | 514.00000 | 23.89257 | 56.70917 | -0.3189 | 9.05485 |
September | 485.00000 | 23.57788 | 53.68128 | -0.4962 | 12.73099 |
October | 502.00000 | 23.25471 | 44.13671 | 0.25790 | 8.65875 |
November | 489.00000 | 22.34392 | 39.89411 | -0.0318 | 7.24067 |
December | 497.00000 | 21.95178 | 34.22309 | -0.1779 | 7.63822 |
Annual Sum or Average | 5943.00000 | 22.92667 | 46.45945 | -0.1908 | 9.77421 |
Minimum of Months | 454.00000 | 21.85676 | 34.22309 | -0.6950 | 7.24067 |
Maximum of Months | 514.00000 | 24.05022 | 56.70917 | 0.25840 | 19.17896 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.345551E+11 | 92886.13 | 18-JAN-14:30 | 241.82 | 0.197067E+12 | 0.00 | 0.231622E+12 | 1.66 | 7.18 | 13-JAN-14:00 | 0.00 | 0.00 |
February | 0.220488E+11 | 82201.94 | 03-FEB-12:20 | 186.23 | 0.117044E+12 | 0.00 | 0.139092E+12 | 1.32 | 7.01 | 03-FEB-12:20 | 0.00 | 0.00 |
March | 0.233605E+11 | 86280.47 | 23-MAR-13:50 | 183.41 | 0.127155E+12 | 0.00 | 0.150516E+12 | 1.20 | 7.05 | 23-MAR-13:50 | 0.00 | 0.00 |
April | 0.471358E+11 | 89407.86 | 12-APR-14:00 | 305.43 | 0.276562E+12 | 0.00 | 0.323698E+12 | 2.24 | 7.05 | 26-APR-13:50 | 0.00 | 0.00 |
May | 0.522540E+11 | 88392.16 | 03-MAY-13:00 | 336.89 | 0.298062E+12 | 0.00 | 0.350316E+12 | 2.34 | 7.09 | 03-MAY-13:00 | 0.00 | 0.00 |
June | 0.758837E+11 | 108626.22 | 29-JUN-13:00 | 442.21 | 0.453199E+12 | 0.00 | 0.529082E+12 | 3.33 | 7.04 | 29-JUN-16:00 | 0.00 | 0.00 |
July | 0.111316E+12 | 146882.69 | 31-JUL-15:50 | 567.26 | 0.700343E+12 | 0.00 | 0.811659E+12 | 4.30 | 7.14 | 29-JUL-05:03 | 0.00 | 0.00 |
August | 0.124160E+12 | 148475.36 | 18-AUG-15:50 | 598.32 | 0.795338E+12 | 0.00 | 0.919498E+12 | 4.62 | 7.27 | 17-AUG-05:03 | 0.00 | 0.00 |
September | 0.815125E+11 | 126703.19 | 29-SEP-12:20 | 430.69 | 0.501788E+12 | 0.00 | 0.583301E+12 | 3.34 | 7.34 | 30-SEP-05:02 | 0.00 | 0.00 |
October | 0.904472E+11 | 135187.03 | 03-OCT-13:30 | 446.41 | 0.570061E+12 | 0.00 | 0.660509E+12 | 3.44 | 7.31 | 02-OCT-05:03 | 0.00 | 0.00 |
November | 0.385073E+11 | 83018.93 | 28-NOV-14:00 | 276.37 | 0.220576E+12 | 0.00 | 0.259083E+12 | 1.96 | 7.03 | 08-NOV-12:30 | 0.00 | 0.00 |
December | 0.381397E+11 | 88058.36 | 05-DEC-15:00 | 252.66 | 0.226325E+12 | 0.00 | 0.264465E+12 | 1.79 | 7.05 | 05-DEC-14:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.739321E+12 | 4267.70 | 0.448352E+13 | 0.00 | 0.522284E+13 | 2.64 | 0.00 | 0.00 | ||||
Minimum of Months | 0.220488E+11 | 82201.94 | 183.41 | 0.117044E+12 | 0.00 | 0.139092E+12 | 1.20 | 7.01 | 0.00 | 0.00 | ||
Maximum of Months | 0.124160E+12 | 148475.36 | 598.32 | 0.795338E+12 | 0.00 | 0.919498E+12 | 4.62 | 7.34 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.219818E+10 | 92886.13 | 18-JAN-14:30 | 7.33 | 0.154101E+11 | 0.00 | 0.176083E+11 | 0.07 | 7.18 | 13-JAN-14:00 | 0.00 | 0.00 |
February | 0.191081E+09 | 80454.60 | 01-FEB-12:00 | 0.67 | 0.132659E+10 | 0.00 | 0.151767E+10 | 0.01 | 6.96 | 01-FEB-13:20 | 0.00 | 0.00 |
March | 0.982937E+09 | 86280.47 | 23-MAR-13:50 | 3.33 | 0.683578E+10 | 0.00 | 0.781871E+10 | 0.03 | 7.05 | 23-MAR-13:50 | 0.00 | 0.00 |
April | 0.266871E+10 | 89407.86 | 12-APR-14:00 | 9.00 | 0.185573E+11 | 0.00 | 0.212260E+11 | 0.09 | 7.05 | 26-APR-13:50 | 0.00 | 0.00 |
May | 0.108142E+10 | 88392.16 | 03-MAY-13:00 | 3.67 | 0.755523E+10 | 0.00 | 0.863665E+10 | 0.03 | 7.09 | 03-MAY-13:00 | 0.00 | 0.00 |
June | 0.124995E+11 | 108626.22 | 29-JUN-13:00 | 39.71 | 0.868856E+11 | 0.00 | 0.993851E+11 | 0.38 | 7.04 | 29-JUN-16:00 | 0.00 | 0.00 |
July | 0.408316E+11 | 146882.69 | 31-JUL-15:50 | 113.98 | 0.283112E+12 | 0.00 | 0.323944E+12 | 1.06 | 7.14 | 29-JUL-05:03 | 0.00 | 0.00 |
August | 0.565302E+11 | 148475.36 | 18-AUG-15:50 | 157.41 | 0.392226E+12 | 0.00 | 0.448757E+12 | 1.47 | 7.27 | 17-AUG-05:03 | 0.00 | 0.00 |
September | 0.239105E+11 | 126703.19 | 29-SEP-12:20 | 73.58 | 0.166591E+12 | 0.00 | 0.190502E+12 | 0.71 | 7.34 | 30-SEP-05:02 | 0.00 | 0.00 |
October | 0.330136E+11 | 135187.03 | 03-OCT-13:30 | 98.87 | 0.231144E+12 | 0.00 | 0.264158E+12 | 0.93 | 7.31 | 02-OCT-05:03 | 0.00 | 0.00 |
November | 0.534798E+09 | 83018.93 | 28-NOV-14:00 | 1.83 | 0.372510E+10 | 0.00 | 0.425990E+10 | 0.02 | 7.01 | 28-NOV-13:10 | 0.00 | 0.00 |
December | 0.280482E+10 | 88058.36 | 05-DEC-15:00 | 9.67 | 0.195001E+11 | 0.00 | 0.223049E+11 | 0.09 | 7.05 | 05-DEC-14:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.177247E+12 | 519.04 | 0.123287E+13 | 0.00 | 0.141012E+13 | 0.41 | 0.00 | 0.00 | ||||
Minimum of Months | 0.191081E+09 | 80454.60 | 0.67 | 0.132659E+10 | 0.00 | 0.151767E+10 | 0.01 | 6.96 | 0.00 | 0.00 | ||
Maximum of Months | 0.565302E+11 | 148475.36 | 157.41 | 0.392226E+12 | 0.00 | 0.448757E+12 | 1.47 | 7.34 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.597406E+11 | 744.00 | 49248.27 | 03-JAN-11:40 | 214300.22 | 17-JAN-14:20 | 22.72 | 18.98 | 13.93 |
February | 0.776705E+11 | 672.00 | 49248.27 | 01-FEB-03:40 | 355036.18 | 01-FEB-12:10 | 25.44 | 18.83 | 13.93 |
March | 0.994085E+11 | 744.00 | 49248.27 | 01-MAR-09:00 | 588884.68 | 31-MAR-24:00 | 28.64 | 19.16 | 13.93 |
April | 0.122060E+12 | 720.00 | 49248.27 | 01-APR-07:40 | 666078.56 | 26-APR-14:20 | 33.43 | 20.96 | 13.93 |
May | 0.828452E+11 | 744.00 | 49248.27 | 01-MAY-08:50 | 317723.49 | 31-MAY-24:00 | 23.12 | 19.24 | 13.93 |
June | 0.120799E+12 | 720.00 | 49248.27 | 01-JUN-07:45 | 466983.66 | 30-JUN-24:00 | 27.74 | 20.85 | 13.93 |
July | 0.131795E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 617940.40 | 31-JUL-23:53 | 33.50 | 23.55 | 13.93 |
August | 0.131892E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 675150.62 | 18-AUG-15:30 | 37.89 | 25.02 | 13.93 |
September | 0.113850E+12 | 720.00 | 49248.27 | 01-SEP-07:50 | 330988.72 | 30-SEP-24:00 | 24.60 | 20.59 | 13.93 |
October | 0.121834E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 464388.22 | 31-OCT-23:40 | 29.14 | 22.19 | 13.93 |
November | 0.108037E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 513440.64 | 19-NOV-14:02 | 29.39 | 19.81 | 13.93 |
December | 0.113874E+12 | 744.00 | 49248.27 | 01-DEC-10:30 | 652357.97 | 05-DEC-15:50 | 32.86 | 20.46 | 13.93 |
Annual Sum or Average | 0.128381E+13 | 8760.00 | 29.07 | 20.82 | 13.93 | ||||
Minimum of Months | 0.597406E+11 | 672.00 | 49248.27 | 214300.22 | 22.72 | 18.83 | 13.93 | ||
Maximum of Months | 0.131892E+12 | 744.00 | 49248.27 | 675150.62 | 37.89 | 25.02 | 13.93 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.176158E+10 | 180.05 | 16426.67 | 13-JAN-13:50 | 1012476.59 | 18-JAN-13:50 | 21.62 | 21.17 | 15.22 |
February | 0.679862E+09 | 126.04 | 15795.55 | 01-FEB-13:20 | 982455.49 | 01-FEB-13:20 | 21.37 | 21.08 | 13.09 |
March | 0.140250E+10 | 134.78 | 16426.67 | 22-MAR-11:30 | 850560.29 | 23-MAR-13:50 | 21.38 | 21.09 | 11.93 |
April | 0.371210E+10 | 244.65 | 16426.67 | 04-APR-11:30 | 956879.22 | 13-APR-09:20 | 21.80 | 21.16 | 21.16 |
May | 0.338691E+10 | 283.61 | 16426.67 | 02-MAY-12:30 | 988127.51 | 18-MAY-15:20 | 21.81 | 21.15 | 23.16 |
June | 0.879066E+10 | 400.34 | 16426.67 | 13-JUN-10:50 | 887046.61 | 20-JUN-15:10 | 22.33 | 21.28 | 31.90 |
July | 0.173713E+11 | 505.73 | 16426.67 | 01-JUL-10:30 | 1150991.54 | 31-JUL-16:00 | 23.10 | 21.62 | 39.62 |
August | 0.201819E+11 | 541.56 | 16426.67 | 01-AUG-09:50 | 1150723.53 | 18-AUG-16:00 | 23.39 | 21.74 | 42.05 |
September | 0.108092E+11 | 393.58 | 16426.67 | 01-SEP-10:40 | 1016610.60 | 29-SEP-08:20 | 22.64 | 21.51 | 30.96 |
October | 0.103597E+11 | 405.14 | 16426.67 | 01-OCT-10:40 | 1093176.46 | 17-OCT-08:50 | 22.70 | 21.46 | 31.07 |
November | 0.142760E+10 | 199.78 | 16426.67 | 10-NOV-13:00 | 976793.13 | 28-NOV-11:50 | 21.61 | 21.09 | 18.27 |
December | 0.113488E+10 | 184.54 | 14920.81 | 07-DEC-13:30 | 985678.23 | 18-DEC-13:10 | 21.63 | 21.10 | 16.06 |
Annual Sum or Average | 0.810183E+11 | 3599.81 | 22.12 | 21.29 | 24.62 | ||||
Minimum of Months | 0.679862E+09 | 126.04 | 14920.81 | 850560.29 | 21.37 | 21.08 | 11.93 | ||
Maximum of Months | 0.201819E+11 | 541.56 | 16426.67 | 1150991.54 | 23.39 | 21.74 | 42.05 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.161651E+09 | 3.17 | 16426.67 | 13-JAN-13:50 | 1012476.59 | 18-JAN-13:50 | 21.62 | 21.60 | 0.23 |
February | 9477332.46 | 0.17 | 15795.55 | 01-FEB-13:20 | 982455.49 | 01-FEB-13:20 | 21.37 | 21.37 | 0.01 |
March | 0.147840E+09 | 2.50 | 16426.67 | 22-MAR-13:00 | 850560.29 | 23-MAR-13:50 | 21.38 | 21.37 | 0.18 |
April | 0.303239E+09 | 5.17 | 16426.67 | 04-APR-14:00 | 956879.22 | 13-APR-09:20 | 21.80 | 21.77 | 0.38 |
May | 86116286.19 | 1.50 | 16426.67 | 03-MAY-12:00 | 988127.51 | 18-MAY-15:20 | 21.81 | 21.80 | 0.11 |
June | 0.216832E+10 | 36.67 | 16426.67 | 15-JUN-15:00 | 881092.06 | 29-JUN-13:00 | 22.33 | 22.16 | 2.71 |
July | 0.667728E+10 | 112.91 | 16426.67 | 03-JUL-12:10 | 1150991.54 | 31-JUL-16:00 | 23.10 | 22.55 | 8.06 |
August | 0.915393E+10 | 154.79 | 16426.67 | 02-AUG-09:10 | 1150723.53 | 18-AUG-16:00 | 23.39 | 22.62 | 11.06 |
September | 0.401014E+10 | 68.02 | 16426.67 | 05-SEP-12:30 | 1016610.60 | 29-SEP-08:20 | 22.64 | 22.31 | 5.02 |
October | 0.431043E+10 | 77.59 | 16426.67 | 01-OCT-12:32 | 1093176.46 | 17-OCT-08:50 | 22.70 | 22.30 | 5.54 |
November | 2429067.48 | 0.17 | 4048.45 | 28-NOV-11:50 | 976793.13 | 28-NOV-11:50 | 21.61 | 21.60 | 0.01 |
December | 37681604.13 | 2.17 | 6357.98 | 05-DEC-11:10 | 985678.23 | 18-DEC-13:10 | 21.63 | 21.62 | 0.15 |
Annual Sum or Average | 0.270685E+11 | 464.83 | 22.12 | 21.93 | 2.82 | ||||
Minimum of Months | 2429067.48 | 0.17 | 4048.45 | 850560.29 | 21.37 | 21.37 | 0.01 | ||
Maximum of Months | 0.915393E+10 | 154.79 | 16426.67 | 1150991.54 | 23.39 | 22.62 | 11.06 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.703403E+11 | 0.00 | 207.87 | 811333.50 | 02-JAN-06:01 | 0.00 | 36.62 | 49.35 | 0.16 | 0.00 | 0.02 | 0.49 | 02-JAN-06:01 |
February | 0.504628E+11 | 0.00 | 203.48 | 417537.49 | 10-FEB-07:10 | 0.00 | 32.49 | 47.32 | 0.11 | 0.00 | 0.01 | 0.25 | 10-FEB-07:10 |
March | 0.759570E+11 | 0.00 | 248.86 | 817124.51 | 30-MAR-05:03 | 0.00 | 35.00 | 50.66 | 0.16 | 0.00 | 0.02 | 0.49 | 30-MAR-05:03 |
April | 0.211443E+11 | 0.00 | 114.75 | 458938.46 | 01-APR-06:10 | 0.00 | 29.12 | 37.38 | 0.04 | 0.00 | 0.00 | 0.28 | 01-APR-06:10 |
May | 0.137213E+11 | 0.00 | 89.37 | 169544.12 | 15-MAY-06:10 | 0.00 | 29.02 | 35.35 | 0.02 | 0.00 | 0.00 | 0.10 | 15-MAY-06:10 |
June | 0.131553E+10 | 0.00 | 21.25 | 124745.56 | 12-JUN-21:00 | 0.00 | 28.48 | 30.12 | 0.00 | 0.00 | 0.00 | 0.08 | 12-JUN-21:00 |
July | 92922.80 | 0.00 | 0.17 | 154.87 | 07-JUL-21:00 | 0.00 | 30.37 | 30.38 | 0.00 | 0.00 | 0.00 | 0.00 | 07-JUL-21:00 |
August | 11588435.48 | 0.00 | 2.17 | 3491.72 | 28-AUG-07:00 | 0.00 | 30.31 | 30.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28-AUG-07:00 |
September | 0.104381E+10 | 0.00 | 19.54 | 93791.87 | 20-SEP-06:10 | 0.00 | 28.00 | 29.49 | 0.00 | 0.00 | 0.00 | 0.06 | 20-SEP-06:10 |
October | 0.422594E+10 | 0.00 | 32.58 | 265240.19 | 12-OCT-06:05 | 0.00 | 29.20 | 31.47 | 0.01 | 0.00 | 0.00 | 0.16 | 12-OCT-06:05 |
November | 0.290211E+11 | 0.00 | 158.67 | 318627.61 | 30-NOV-07:10 | 0.00 | 31.60 | 42.65 | 0.06 | 0.00 | 0.01 | 0.19 | 30-NOV-07:10 |
December | 0.557633E+11 | 0.00 | 197.44 | 520745.29 | 23-DEC-07:05 | 0.00 | 34.97 | 47.20 | 0.12 | 0.00 | 0.01 | 0.31 | 23-DEC-07:05 |
Annual Sum or Average | 0.323007E+12 | 0.00 | 1296.13 | 0.00 | 31.28 | 38.45 | 0.06 | 0.00 | 0.01 | ||||
Minimum of Months | 92922.80 | 0.00 | 0.17 | 154.87 | 0.00 | 28.00 | 29.49 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.759570E+11 | 0.00 | 248.86 | 817124.51 | 0.00 | 36.62 | 50.66 | 0.16 | 0.00 | 0.02 | 0.49 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.72 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.44 | 25.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 28.64 | 28.64 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 33.43 | 33.43 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 23.12 | 23.12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 27.74 | 27.74 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 33.50 | 33.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 37.89 | 37.89 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 24.60 | 24.60 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 29.14 | 29.14 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 29.39 | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 32.86 | 32.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 29.07 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 22.72 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 | 37.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.207122E+11 | 0.00 | 219.99 | 0.206778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90868.20 | 18-JAN-13:10 | 90868.20 | 18-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.121801E+11 | 0.00 | 171.64 | 0.121008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87297.82 | 01-FEB-12:00 | 87297.82 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.147850E+11 | 0.00 | 173.81 | 0.143362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100180.10 | 23-MAR-14:00 | 83220.37 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.333266E+11 | 0.00 | 292.90 | 0.332214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112697.87 | 26-APR-11:00 | 112480.53 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.301885E+11 | 0.00 | 324.66 | 0.300778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82853.43 | 03-MAY-13:00 | 82853.43 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.561840E+11 | 0.00 | 427.58 | 0.502566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134915.59 | 29-JUN-13:00 | 90598.68 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.104123E+12 | 0.00 | 543.62 | 0.744661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188451.06 | 31-JUL-15:40 | 119130.22 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.128606E+12 | 0.00 | 580.52 | 0.862185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190354.86 | 07-AUG-10:40 | 120395.30 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 |
September | 0.636230E+11 | 0.00 | 414.47 | 0.522577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152911.92 | 22-SEP-12:30 | 135869.44 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.784053E+11 | 0.00 | 422.75 | 0.655185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176946.09 | 04-OCT-05:03 | 149068.67 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.253077E+11 | 0.00 | 254.30 | 0.249706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96446.35 | 28-NOV-14:00 | 96446.35 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.295185E+11 | 0.00 | 236.30 | 0.294169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103801.22 | 05-DEC-15:00 | 103801.22 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596959E+12 | 0.00 | 4062.54 | 0.493519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.121801E+11 | 0.00 | 171.64 | 0.121008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82853.43 | 82853.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128606E+12 | 0.00 | 580.52 | 0.862185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190354.86 | 149068.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.172506E+12 | 0.00 | 227.82 | 0.171849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 777380.88 | 18-JAN-13:10 | 777380.88 | 18-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.939737E+11 | 0.00 | 175.73 | 0.931998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 741571.96 | 01-FEB-12:00 | 741571.96 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.106589E+12 | 0.00 | 169.47 | 0.103675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 818431.57 | 23-MAR-14:20 | 681846.43 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.237220E+12 | 0.00 | 267.94 | 0.237071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 921181.56 | 26-APR-13:00 | 921181.56 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.250196E+12 | 0.00 | 315.20 | 0.249228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 745828.92 | 03-MAY-13:00 | 745828.92 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.454366E+12 | 0.00 | 402.50 | 0.408591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1169203.87 | 29-JUN-13:00 | 786417.63 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.799079E+12 | 0.00 | 447.59 | 0.580492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1549712.96 | 31-JUL-15:50 | 1004716.72 | 31-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.945120E+12 | 0.00 | 466.08 | 0.651876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1575514.05 | 18-AUG-15:50 | 1016884.83 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.544737E+12 | 0.00 | 398.27 | 0.449783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1365300.00 | 22-SEP-12:30 | 1309611.89 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.638222E+12 | 0.00 | 402.53 | 0.536457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1682907.34 | 05-OCT-05:03 | 1354048.95 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.183258E+12 | 0.00 | 251.55 | 0.181383E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 746291.43 | 28-NOV-14:00 | 746291.43 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.207585E+12 | 0.00 | 225.21 | 0.206864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 788584.41 | 05-DEC-15:00 | 788584.41 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463285E+13 | 0.00 | 3749.89 | 0.387047E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.939737E+11 | 0.00 | 169.47 | 0.931998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 741571.96 | 681846.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.945120E+12 | 0.00 | 466.08 | 0.651876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1682907.34 | 1354048.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.131388E+11 | 0.00 | 197.89 | 0.131388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75255.74 | 18-JAN-13:30 | 75255.74 | 18-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.740741E+10 | 0.00 | 150.03 | 0.734068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68162.52 | 01-FEB-12:00 | 68162.52 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.918160E+10 | 0.00 | 150.72 | 0.904819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80375.68 | 23-MAR-15:00 | 71781.24 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.233213E+11 | 0.00 | 253.22 | 0.233150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110117.24 | 26-APR-14:00 | 110117.24 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.245790E+11 | 0.00 | 299.98 | 0.245021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84671.26 | 03-MAY-13:00 | 84671.26 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.472310E+11 | 0.00 | 390.09 | 0.422587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132681.07 | 29-JUN-13:00 | 85054.48 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.858566E+11 | 0.00 | 433.07 | 0.623418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195991.94 | 31-JUL-15:10 | 123204.27 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.100159E+12 | 0.00 | 449.09 | 0.687529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193425.62 | 18-AUG-15:30 | 122339.91 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.536031E+11 | 0.00 | 372.99 | 0.446671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155159.47 | 29-SEP-13:00 | 155159.47 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.612202E+11 | 0.00 | 379.98 | 0.516692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156844.69 | 05-OCT-05:03 | 152620.36 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 |
November | 0.141092E+11 | 0.00 | 223.67 | 0.141032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72217.30 | 28-NOV-14:00 | 72217.30 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.160405E+11 | 0.00 | 199.97 | 0.160405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80413.59 | 05-DEC-15:00 | 80413.59 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455848E+12 | 0.00 | 3500.70 | 0.377178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.740741E+10 | 0.00 | 150.03 | 0.734068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68162.52 | 68162.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100159E+12 | 0.00 | 449.09 | 0.687529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195991.94 | 155159.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.121005E+11 | 0.00 | 149.63 | 0.120595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70283.31 | 17-JAN-14:00 | 68583.98 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.537816E+10 | 0.00 | 94.02 | 0.534066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64735.52 | 13-FEB-06:03 | 56568.59 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.624411E+10 | 0.00 | 96.30 | 0.619945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47834.86 | 23-MAR-14:00 | 47834.86 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.160624E+11 | 0.00 | 193.95 | 0.159714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63932.99 | 27-APR-05:03 | 59551.72 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.156200E+11 | 0.00 | 211.32 | 0.155462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60871.43 | 03-MAY-05:03 | 53257.82 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.285060E+11 | 0.00 | 277.02 | 0.271747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84518.98 | 30-JUN-05:03 | 63730.26 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.484688E+11 | 0.00 | 327.83 | 0.411180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105925.76 | 31-JUL-09:10 | 69936.55 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 |
August | 0.562466E+11 | 0.00 | 365.67 | 0.457965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121803.78 | 07-AUG-09:50 | 71902.06 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 |
September | 0.340179E+11 | 0.00 | 283.03 | 0.301664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97954.20 | 22-SEP-10:00 | 83785.91 | 30-SEP-04:02 | 0.00 | 0.00 | 0.00 |
October | 0.440538E+11 | 0.00 | 307.50 | 0.383321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110840.74 | 05-OCT-04:03 | 86694.13 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.134614E+11 | 0.00 | 175.33 | 0.134305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61339.83 | 10-NOV-04:02 | 60316.64 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.166741E+11 | 0.00 | 159.71 | 0.166620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70463.54 | 25-DEC-15:10 | 70463.54 | 25-DEC-15:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296834E+12 | 0.00 | 2641.33 | 0.267797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.537816E+10 | 0.00 | 94.02 | 0.534066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47834.86 | 47834.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.562466E+11 | 0.00 | 365.67 | 0.457965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121803.78 | 86694.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.331040E+12 | 0.838854E+11 | 744.00 | 0.329840E+12 | 0.120003E+10 | 0.00 | 0.37 | 14-JAN-12:00 | 0.31 | 28-JAN-07:10 | 130973.02 | 17-JAN-14:50 | 127419.32 | 18-JAN-13:10 | 5465.73 | 17-JAN-15:00 | 42136.49 | 14-JAN-12:00 | 0.00 |
February | 0.518421E+12 | 0.123697E+12 | 672.00 | 0.516791E+12 | 0.163027E+10 | 0.00 | 0.60 | 03-FEB-15:00 | 0.53 | 11-FEB-07:40 | 220265.99 | 13-FEB-17:00 | 217491.00 | 03-FEB-15:00 | 6229.62 | 01-FEB-17:00 | 70548.62 | 01-FEB-12:00 | 0.00 |
March | 0.819587E+12 | 0.189624E+12 | 744.00 | 0.817356E+12 | 0.223076E+10 | 0.00 | 0.93 | 31-MAR-24:00 | 0.73 | 01-MAR-07:05 | 393891.87 | 31-MAR-24:00 | 393891.87 | 31-MAR-24:00 | 6395.74 | 23-MAR-16:10 | 95029.03 | 11-MAR-12:00 | 0.00 |
April | 0.103220E+13 | 0.243465E+12 | 720.00 | 0.102956E+13 | 0.263927E+10 | 0.00 | 1.00 | 01-APR-09:50 | 0.36 | 30-APR-24:00 | 408230.00 | 26-APR-15:00 | 402236.12 | 26-APR-16:00 | 6569.97 | 26-APR-15:00 | 127894.82 | 26-APR-13:00 | 0.00 |
May | 0.333693E+12 | 0.845005E+11 | 744.00 | 0.330665E+12 | 0.302800E+10 | 0.00 | 0.53 | 31-MAY-24:00 | 0.32 | 15-MAY-06:10 | 211325.01 | 31-MAY-23:20 | 211147.21 | 31-MAY-24:00 | 5966.65 | 05-MAY-15:00 | 49338.69 | 31-MAY-24:00 | 0.00 |
June | 0.562586E+12 | 0.142361E+12 | 720.00 | 0.557048E+12 | 0.553783E+10 | 0.00 | 0.74 | 30-JUN-24:00 | 0.53 | 01-JUN-06:10 | 303012.04 | 30-JUN-24:00 | 302878.42 | 30-JUN-24:00 | 7439.08 | 28-JUN-13:00 | 72513.01 | 30-JUN-24:00 | 0.00 |
July | 0.829763E+12 | 0.218780E+12 | 744.00 | 0.822910E+12 | 0.685299E+10 | 0.00 | 0.95 | 31-JUL-23:22 | 0.74 | 17-JUL-06:10 | 394968.11 | 31-JUL-23:53 | 394968.11 | 31-JUL-23:53 | 8960.15 | 28-JUL-14:00 | 106657.40 | 31-JUL-13:00 | 0.00 |
August | 0.107393E+13 | 0.284640E+12 | 744.00 | 0.106710E+13 | 0.682936E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.36 | 31-AUG-24:00 | 411515.09 | 18-AUG-17:00 | 402179.49 | 25-AUG-15:40 | 10273.83 | 18-AUG-16:10 | 130672.73 | 14-AUG-11:00 | 0.00 |
September | 0.328657E+12 | 0.868723E+11 | 720.00 | 0.323200E+12 | 0.545668E+10 | 0.00 | 0.55 | 30-SEP-24:00 | 0.32 | 20-SEP-06:10 | 211451.78 | 30-SEP-24:00 | 211451.78 | 30-SEP-24:00 | 8534.47 | 22-SEP-10:50 | 57485.30 | 29-SEP-12:05 | 0.00 |
October | 0.582342E+12 | 0.155383E+12 | 744.00 | 0.578820E+12 | 0.352197E+10 | 0.00 | 0.74 | 31-OCT-23:20 | 0.53 | 28-OCT-06:15 | 304835.47 | 31-OCT-24:00 | 303687.02 | 31-OCT-24:00 | 9023.80 | 05-OCT-16:00 | 100239.12 | 16-OCT-11:00 | 0.00 |
November | 0.796594E+12 | 0.188830E+12 | 720.00 | 0.794786E+12 | 0.180743E+10 | 0.00 | 0.84 | 28-NOV-14:00 | 0.73 | 01-NOV-07:00 | 314123.47 | 10-NOV-17:00 | 310687.69 | 28-NOV-14:00 | 6430.70 | 10-NOV-17:10 | 102438.78 | 19-NOV-13:00 | 0.00 |
December | 0.106628E+13 | 0.249858E+12 | 744.00 | 0.106563E+13 | 0.646031E+09 | 0.00 | 1.00 | 04-DEC-08:55 | 0.92 | 23-DEC-07:05 | 405241.38 | 29-DEC-16:30 | 405241.38 | 29-DEC-16:30 | 5416.17 | 07-DEC-17:00 | 124961.63 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.827508E+13 | 0.205190E+13 | 8760.00 | 0.823370E+13 | 0.413806E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.328657E+12 | 0.838854E+11 | 672.00 | 0.323200E+12 | 0.646031E+09 | 0.00 | 0.37 | 0.31 | 130973.02 | 127419.32 | 5416.17 | 42136.49 | 0.00 | ||||||
Maximum of Months | 0.107393E+13 | 0.284640E+12 | 744.00 | 0.106710E+13 | 0.685299E+10 | 0.00 | 1.00 | 0.92 | 411515.09 | 405241.38 | 10273.83 | 130672.73 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.522427E+10 | 0.132507E+10 | 744.00 | 0.517997E+10 | 44295557.81 | 0.00 | 0.33 | 15-JAN-15:53 | 0.17 | 28-JAN-07:20 | 2492.25 | 18-JAN-16:10 | 2402.22 | 18-JAN-16:10 | 178.42 | 20-JAN-17:00 | 740.88 | 13-JAN-14:00 | 0.00 |
February | 0.940320E+10 | 0.222251E+10 | 672.00 | 0.933815E+10 | 65043290.21 | 0.00 | 0.56 | 03-FEB-15:00 | 0.39 | 25-FEB-18:00 | 4498.56 | 21-FEB-17:00 | 4455.18 | 20-FEB-17:07 | 229.90 | 13-FEB-17:00 | 1320.47 | 01-FEB-12:00 | 0.00 |
March | 0.155809E+11 | 0.354443E+10 | 744.00 | 0.154876E+11 | 93336503.86 | 0.00 | 0.85 | 31-MAR-24:00 | 0.61 | 01-MAR-07:05 | 7559.27 | 31-MAR-24:00 | 7559.27 | 31-MAR-24:00 | 253.23 | 23-MAR-16:10 | 1781.50 | 11-MAR-14:00 | 0.00 |
April | 0.202252E+11 | 0.468752E+10 | 720.00 | 0.201093E+11 | 0.115927E+09 | 0.00 | 0.99 | 02-APR-13:52 | 0.31 | 30-APR-24:00 | 8360.58 | 16-APR-17:30 | 8347.34 | 30-APR-17:14 | 230.36 | 17-APR-16:00 | 2572.08 | 26-APR-13:00 | 0.00 |
May | 0.564666E+10 | 0.140969E+10 | 744.00 | 0.553903E+10 | 0.107622E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.19 | 13-MAY-07:00 | 3881.69 | 31-MAY-24:00 | 3862.81 | 31-MAY-24:00 | 214.54 | 05-MAY-15:20 | 888.71 | 31-MAY-24:00 | 0.00 |
June | 0.106846E+11 | 0.264527E+10 | 720.00 | 0.104797E+11 | 0.204884E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.43 | 01-JUN-06:10 | 5913.33 | 30-JUN-24:00 | 5901.62 | 30-JUN-24:00 | 291.41 | 28-JUN-13:00 | 1383.03 | 30-JUN-24:00 | 0.00 |
July | 0.162546E+11 | 0.418781E+10 | 744.00 | 0.159745E+11 | 0.280107E+09 | 0.00 | 0.88 | 31-JUL-23:33 | 0.66 | 07-JUL-21:00 | 7773.03 | 31-JUL-23:50 | 7771.67 | 31-JUL-23:45 | 360.56 | 28-JUL-14:00 | 2103.48 | 31-JUL-13:00 | 0.00 |
August | 0.212940E+11 | 0.552801E+10 | 744.00 | 0.209851E+11 | 0.308928E+09 | 0.00 | 1.00 | 17-AUG-14:00 | 0.31 | 31-AUG-24:00 | 8520.65 | 17-AUG-15:50 | 8430.35 | 06-AUG-17:47 | 365.21 | 18-AUG-16:00 | 2708.64 | 17-AUG-14:00 | 0.00 |
September | 0.577372E+10 | 0.149864E+10 | 720.00 | 0.557702E+10 | 0.196697E+09 | 0.00 | 0.50 | 30-SEP-24:00 | 0.22 | 20-SEP-06:20 | 4059.00 | 30-SEP-24:00 | 4059.00 | 30-SEP-24:00 | 336.51 | 22-SEP-10:50 | 1094.51 | 29-SEP-13:00 | 0.00 |
October | 0.109838E+11 | 0.288560E+10 | 744.00 | 0.108509E+11 | 0.132978E+09 | 0.00 | 0.68 | 31-OCT-24:00 | 0.42 | 28-OCT-06:35 | 5893.22 | 31-OCT-24:00 | 5867.56 | 31-OCT-24:00 | 349.49 | 05-OCT-16:00 | 1980.38 | 16-OCT-11:00 | 0.00 |
November | 0.152437E+11 | 0.357506E+10 | 720.00 | 0.151712E+11 | 72490589.70 | 0.00 | 0.83 | 28-NOV-14:00 | 0.62 | 18-NOV-07:40 | 6444.37 | 07-NOV-16:20 | 6388.76 | 12-NOV-16:17 | 250.94 | 10-NOV-17:00 | 2037.74 | 28-NOV-14:00 | 0.00 |
December | 0.207071E+11 | 0.483688E+10 | 744.00 | 0.206768E+11 | 30284661.36 | 0.00 | 1.00 | 18-DEC-13:00 | 0.81 | 23-DEC-07:05 | 8373.67 | 25-DEC-16:10 | 8373.67 | 25-DEC-16:10 | 212.67 | 07-DEC-17:00 | 2579.07 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.157022E+12 | 0.383465E+11 | 8760.00 | 0.155369E+12 | 0.165259E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.522427E+10 | 0.132507E+10 | 672.00 | 0.517997E+10 | 30284661.36 | 0.00 | 0.33 | 0.17 | 2492.25 | 2402.22 | 178.42 | 740.88 | 0.00 | ||||||
Maximum of Months | 0.212940E+11 | 0.552801E+10 | 744.00 | 0.209851E+11 | 0.308928E+09 | 0.00 | 1.00 | 0.81 | 8520.65 | 8430.35 | 365.21 | 2708.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.397351E+11 | 0.102771E+11 | 744.00 | 0.393082E+11 | 0.426814E+09 | 0.00 | 0.31 | 18-JAN-16:10 | 0.08 | 02-JAN-07:10 | 23086.00 | 18-JAN-16:20 | 22212.75 | 18-JAN-16:10 | 1758.75 | 20-JAN-16:30 | 6761.07 | 24-JAN-16:00 | 0.00 |
February | 0.811230E+11 | 0.193630E+11 | 672.00 | 0.804831E+11 | 0.639886E+09 | 0.00 | 0.56 | 03-FEB-15:00 | 0.34 | 25-FEB-18:00 | 42195.79 | 01-FEB-16:50 | 40322.40 | 22-FEB-17:00 | 2287.07 | 13-FEB-17:00 | 12234.55 | 01-FEB-12:00 | 0.00 |
March | 0.139988E+12 | 0.320817E+11 | 744.00 | 0.139060E+12 | 0.927305E+09 | 0.00 | 0.80 | 31-MAR-23:40 | 0.55 | 30-MAR-06:10 | 67764.60 | 31-MAR-23:40 | 67764.60 | 31-MAR-23:40 | 2511.99 | 23-MAR-16:10 | 16861.14 | 23-MAR-14:00 | 0.00 |
April | 0.188456E+12 | 0.438296E+11 | 720.00 | 0.187298E+12 | 0.115836E+10 | 0.00 | 0.97 | 26-APR-13:20 | 0.27 | 30-APR-24:00 | 78656.43 | 26-APR-16:00 | 77588.07 | 30-APR-17:14 | 2275.25 | 17-APR-16:00 | 24488.57 | 26-APR-13:00 | 0.00 |
May | 0.488200E+11 | 0.122916E+11 | 744.00 | 0.477745E+11 | 0.104542E+10 | 0.00 | 0.44 | 31-MAY-24:00 | 0.15 | 13-MAY-07:00 | 35242.03 | 31-MAY-24:00 | 35008.69 | 31-MAY-24:00 | 2112.64 | 05-MAY-15:20 | 8103.04 | 31-MAY-24:00 | 0.00 |
June | 0.986743E+11 | 0.245200E+11 | 720.00 | 0.966553E+11 | 0.201900E+10 | 0.00 | 0.68 | 30-JUN-24:00 | 0.41 | 01-JUN-06:10 | 55934.26 | 30-JUN-24:00 | 55811.43 | 30-JUN-24:00 | 2892.49 | 28-JUN-13:10 | 13092.49 | 30-JUN-24:00 | 0.00 |
July | 0.153719E+12 | 0.396403E+11 | 744.00 | 0.150934E+12 | 0.278505E+10 | 0.00 | 0.89 | 31-JUL-23:53 | 0.65 | 06-JUL-06:10 | 74374.95 | 31-JUL-24:00 | 74340.15 | 31-JUL-24:00 | 3579.08 | 28-JUL-14:00 | 20077.87 | 31-JUL-13:00 | 0.00 |
August | 0.201986E+12 | 0.524651E+11 | 744.00 | 0.198901E+12 | 0.308510E+10 | 0.00 | 1.00 | 17-AUG-14:00 | 0.26 | 31-AUG-24:00 | 81024.64 | 17-AUG-16:00 | 78587.75 | 06-AUG-17:47 | 3632.80 | 18-AUG-16:00 | 25784.18 | 17-AUG-14:00 | 0.00 |
September | 0.512239E+11 | 0.133899E+11 | 720.00 | 0.493092E+11 | 0.191469E+10 | 0.00 | 0.50 | 30-SEP-24:00 | 0.19 | 20-SEP-06:40 | 38867.78 | 30-SEP-24:00 | 38867.78 | 30-SEP-24:00 | 3324.29 | 22-SEP-10:50 | 10329.65 | 29-SEP-13:00 | 0.00 |
October | 0.999301E+11 | 0.264204E+11 | 744.00 | 0.986202E+11 | 0.130987E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 54548.75 | 31-OCT-24:00 | 54300.39 | 31-OCT-24:00 | 3461.11 | 05-OCT-16:00 | 18805.32 | 16-OCT-11:00 | 0.00 |
November | 0.137672E+12 | 0.325125E+11 | 720.00 | 0.136954E+12 | 0.718586E+09 | 0.00 | 0.81 | 28-NOV-14:00 | 0.58 | 18-NOV-07:40 | 60820.14 | 10-NOV-16:20 | 59325.16 | 12-NOV-16:30 | 2495.31 | 10-NOV-17:00 | 19122.53 | 28-NOV-14:00 | 0.00 |
December | 0.188085E+12 | 0.442730E+11 | 744.00 | 0.187780E+12 | 0.304966E+09 | 0.00 | 1.00 | 18-DEC-15:30 | 0.76 | 13-DEC-07:10 | 78611.87 | 07-DEC-16:10 | 77208.71 | 18-DEC-16:20 | 2117.49 | 07-DEC-17:00 | 24536.82 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.142941E+13 | 0.351064E+12 | 8760.00 | 0.141308E+13 | 0.163350E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.397351E+11 | 0.102771E+11 | 672.00 | 0.393082E+11 | 0.304966E+09 | 0.00 | 0.31 | 0.08 | 23086.00 | 22212.75 | 1758.75 | 6761.07 | 0.00 | ||||||
Maximum of Months | 0.201986E+12 | 0.524651E+11 | 744.00 | 0.198901E+12 | 0.308510E+10 | 0.00 | 1.00 | 0.76 | 81024.64 | 78587.75 | 3632.80 | 25784.18 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.268086E+10 | 0.715037E+09 | 687.26 | 0.263987E+10 | 40991754.53 | 0.00 | 0.31 | 18-JAN-16:10 | 0.00 | 01-JAN-00:05 | 2331.04 | 18-JAN-16:10 | 2243.61 | 18-JAN-16:10 | 175.90 | 20-JAN-16:30 | 676.74 | 24-JAN-16:00 | 0.00 |
February | 0.703618E+10 | 0.170376E+10 | 672.00 | 0.697325E+10 | 62926743.08 | 0.00 | 0.55 | 03-FEB-15:00 | 0.23 | 26-FEB-07:40 | 4241.43 | 01-FEB-16:50 | 4037.81 | 03-FEB-16:50 | 229.25 | 13-FEB-17:00 | 1228.45 | 03-FEB-15:00 | 0.00 |
March | 0.129964E+11 | 0.301156E+10 | 744.00 | 0.129044E+11 | 91982780.68 | 0.00 | 0.75 | 31-MAR-23:20 | 0.45 | 30-MAR-06:10 | 6365.03 | 31-MAR-23:20 | 6365.03 | 31-MAR-23:20 | 251.49 | 23-MAR-16:10 | 1701.50 | 23-MAR-14:00 | 0.00 |
April | 0.183270E+11 | 0.429476E+10 | 720.00 | 0.182115E+11 | 0.115489E+09 | 0.00 | 0.96 | 26-APR-14:00 | 0.24 | 30-APR-24:00 | 7967.24 | 26-APR-16:00 | 7833.97 | 30-APR-17:25 | 226.90 | 17-APR-16:00 | 2473.29 | 26-APR-13:00 | 0.00 |
May | 0.435687E+10 | 0.111083E+10 | 743.83 | 0.425376E+10 | 0.103110E+09 | 0.00 | 0.40 | 31-MAY-23:30 | 0.00 | 14-MAY-04:25 | 3231.45 | 31-MAY-23:20 | 3191.03 | 31-MAY-24:00 | 209.34 | 05-MAY-15:20 | 748.88 | 31-MAY-23:30 | 0.00 |
June | 0.963787E+10 | 0.240887E+10 | 720.00 | 0.943663E+10 | 0.201235E+09 | 0.00 | 0.66 | 30-JUN-24:00 | 0.35 | 01-JUN-06:30 | 5463.85 | 30-JUN-24:00 | 5451.01 | 30-JUN-24:00 | 291.01 | 28-JUN-13:00 | 1286.78 | 29-JUN-11:00 | 0.00 |
July | 0.152898E+11 | 0.395838E+10 | 744.00 | 0.150116E+11 | 0.278248E+09 | 0.00 | 0.86 | 31-JUL-23:53 | 0.61 | 06-JUL-06:20 | 7336.91 | 31-JUL-23:57 | 7333.16 | 31-JUL-24:00 | 358.78 | 28-JUL-14:00 | 2036.35 | 31-JUL-13:00 | 0.00 |
August | 0.200832E+11 | 0.523844E+10 | 744.00 | 0.197750E+11 | 0.308146E+09 | 0.00 | 1.00 | 17-AUG-14:30 | 0.23 | 31-AUG-24:00 | 8212.26 | 17-AUG-16:00 | 8017.88 | 20-AUG-17:25 | 363.73 | 18-AUG-16:00 | 2612.38 | 17-AUG-14:00 | 0.00 |
September | 0.480689E+10 | 0.126954E+10 | 720.00 | 0.461736E+10 | 0.189532E+09 | 0.00 | 0.48 | 30-SEP-24:00 | 0.12 | 20-SEP-06:50 | 3823.69 | 30-SEP-24:00 | 3823.69 | 30-SEP-24:00 | 332.67 | 22-SEP-11:00 | 1071.53 | 29-SEP-13:00 | 0.00 |
October | 0.949510E+10 | 0.253704E+10 | 744.00 | 0.936511E+10 | 0.129991E+09 | 0.00 | 0.64 | 16-OCT-11:00 | 0.30 | 30-OCT-06:20 | 5211.27 | 31-OCT-23:50 | 5186.42 | 31-OCT-23:50 | 346.18 | 05-OCT-16:00 | 1907.89 | 16-OCT-11:00 | 0.00 |
November | 0.127562E+11 | 0.304849E+10 | 720.00 | 0.126849E+11 | 71219815.12 | 0.00 | 0.80 | 28-NOV-14:00 | 0.47 | 27-NOV-07:05 | 6096.57 | 10-NOV-16:20 | 5874.19 | 07-NOV-16:10 | 249.00 | 10-NOV-17:00 | 1916.80 | 28-NOV-14:00 | 0.00 |
December | 0.175402E+11 | 0.418530E+10 | 744.00 | 0.175100E+11 | 30208279.11 | 0.00 | 1.00 | 19-DEC-11:30 | 0.65 | 26-DEC-07:05 | 7858.31 | 07-DEC-16:10 | 7739.69 | 19-DEC-16:30 | 211.64 | 07-DEC-17:00 | 2500.27 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.135006E+12 | 0.334820E+11 | 8703.10 | 0.133383E+12 | 0.162308E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.268086E+10 | 0.715037E+09 | 672.00 | 0.263987E+10 | 30208279.11 | 0.00 | 0.31 | 0.00 | 2331.04 | 2243.61 | 175.90 | 676.74 | 0.00 | ||||||
Maximum of Months | 0.200832E+11 | 0.523844E+10 | 744.00 | 0.197750E+11 | 0.308146E+09 | 0.00 | 1.00 | 0.65 | 8212.26 | 8017.88 | 363.73 | 2612.38 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 36.24 | 356.56 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 44.72 | 325.86 | 0.00 | 0.00 | 0.00 |
March | 120.24 | 0.00 | 120.24 | 69.74 | 331.09 | 0.00 | 0.00 | 0.00 |
April | 138.53 | 0.53 | 137.99 | 104.27 | 258.89 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 137.34 | 219.22 | 0.00 | 0.00 | 0.00 |
June | 177.38 | 17.34 | 160.03 | 181.65 | 172.99 | 0.00 | 0.00 | 0.00 |
July | 167.95 | 14.08 | 153.87 | 193.22 | 151.40 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 153.64 | 160.27 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 118.51 | 196.57 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 101.15 | 223.00 | 0.00 | 0.00 | 0.00 |
November | 84.79 | 0.00 | 84.79 | 43.32 | 327.30 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 29.87 | 366.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 101.48 | 257.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 29.87 | 151.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.38 | 17.34 | 160.03 | 193.22 | 366.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 36.24 | 356.56 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 44.72 | 325.86 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 69.74 | 331.09 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 104.27 | 258.89 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 137.33 | 219.22 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 181.64 | 172.99 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.87 | 193.22 | 151.40 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 153.64 | 160.27 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 118.51 | 196.57 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 101.15 | 223.00 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 43.32 | 327.30 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 29.87 | 366.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 101.48 | 257.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 29.87 | 151.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 193.22 | 366.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 36.24 | 356.56 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 44.72 | 325.86 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 69.74 | 331.09 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 104.27 | 258.89 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 137.33 | 219.22 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 181.64 | 172.99 | 0.00 | 0.00 | 0.00 |
July | 167.95 | 14.08 | 153.87 | 193.22 | 151.40 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 153.64 | 160.27 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 118.51 | 196.57 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 101.15 | 223.00 | 0.00 | 0.00 | 0.00 |
November | 84.79 | 0.00 | 84.79 | 43.32 | 327.30 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 29.87 | 366.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 101.48 | 257.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 29.87 | 151.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 193.22 | 366.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 36.24 | 356.56 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 44.72 | 325.86 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 69.74 | 331.09 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 104.27 | 258.89 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 137.33 | 219.22 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 181.64 | 172.99 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.87 | 193.22 | 151.40 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 153.64 | 160.27 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 118.51 | 196.57 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 101.15 | 223.00 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 43.32 | 327.30 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 29.87 | 366.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 101.48 | 257.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 29.87 | 151.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 193.22 | 366.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 36.24 | 356.54 | 0.00 | 0.00 | 0.00 |
February | 98.11 | 0.00 | 98.11 | 44.72 | 325.84 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 69.73 | 331.08 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 104.26 | 258.88 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.70 | 137.33 | 219.21 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 181.64 | 172.98 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.86 | 193.21 | 151.39 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.67 | 153.63 | 160.26 | 0.00 | 0.00 | 0.00 |
September | 118.04 | 0.02 | 118.03 | 118.50 | 196.57 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 101.15 | 222.99 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 43.32 | 327.29 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 29.87 | 366.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 101.48 | 257.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 29.87 | 151.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 193.21 | 366.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 267.43 | 361.83 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 265.11 | 329.96 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 340.00 | 332.83 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 506.42 | 265.15 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 457.11 | 243.06 | 0.00 | 0.00 | 0.00 |
June | 359.94 | 156.17 | 203.77 | 490.99 | 192.78 | 0.00 | 0.00 | 0.00 |
July | 407.84 | 202.66 | 205.17 | 604.93 | 166.77 | 0.00 | 0.00 | 0.00 |
August | 402.77 | 213.94 | 188.83 | 605.80 | 168.75 | 0.00 | 0.00 | 0.00 |
September | 293.25 | 134.38 | 158.87 | 413.02 | 207.33 | 0.00 | 0.00 | 0.00 |
October | 259.58 | 133.42 | 126.16 | 372.50 | 228.10 | 0.00 | 0.00 | 0.00 |
November | 236.64 | 120.22 | 116.42 | 272.30 | 328.50 | 0.00 | 0.00 | 0.00 |
December | 225.75 | 125.43 | 100.32 | 257.46 | 360.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.86 | 150.47 | 159.39 | 405.39 | 265.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.75 | 113.21 | 100.32 | 257.46 | 166.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.84 | 213.94 | 211.04 | 605.80 | 361.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 267.43 | 361.83 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 265.11 | 329.96 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 340.00 | 332.83 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 506.42 | 265.15 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 457.11 | 243.06 | 0.00 | 0.00 | 0.00 |
June | 359.94 | 156.17 | 203.77 | 490.99 | 192.78 | 0.00 | 0.00 | 0.00 |
July | 407.84 | 202.66 | 205.17 | 604.93 | 166.77 | 0.00 | 0.00 | 0.00 |
August | 402.77 | 213.94 | 188.83 | 605.80 | 168.75 | 0.00 | 0.00 | 0.00 |
September | 293.25 | 134.38 | 158.87 | 413.02 | 207.33 | 0.00 | 0.00 | 0.00 |
October | 259.58 | 133.42 | 126.16 | 372.50 | 228.10 | 0.00 | 0.00 | 0.00 |
November | 236.64 | 120.22 | 116.42 | 272.30 | 328.50 | 0.00 | 0.00 | 0.00 |
December | 225.75 | 125.43 | 100.32 | 257.46 | 360.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.86 | 150.47 | 159.39 | 405.39 | 265.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.75 | 113.21 | 100.32 | 257.46 | 166.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.84 | 213.94 | 211.04 | 605.80 | 361.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 267.42 | 361.82 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 265.10 | 329.96 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 339.99 | 332.83 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 506.41 | 265.15 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 457.11 | 243.05 | 0.00 | 0.00 | 0.00 |
June | 359.93 | 156.17 | 203.76 | 490.98 | 192.77 | 0.00 | 0.00 | 0.00 |
July | 407.83 | 202.66 | 205.17 | 604.92 | 166.77 | 0.00 | 0.00 | 0.00 |
August | 402.76 | 213.93 | 188.83 | 605.79 | 168.75 | 0.00 | 0.00 | 0.00 |
September | 293.24 | 134.38 | 158.87 | 413.01 | 207.33 | 0.00 | 0.00 | 0.00 |
October | 259.57 | 133.41 | 126.16 | 372.49 | 228.10 | 0.00 | 0.00 | 0.00 |
November | 236.63 | 120.22 | 116.41 | 272.30 | 328.49 | 0.00 | 0.00 | 0.00 |
December | 225.74 | 125.43 | 100.32 | 257.46 | 360.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.85 | 150.47 | 159.38 | 405.38 | 265.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.74 | 113.21 | 100.32 | 257.46 | 166.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.83 | 213.93 | 211.04 | 605.79 | 361.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 744.88 | 327.99 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 547.58 | 301.85 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 427.34 | 315.88 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 383.12 | 261.75 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 218.04 | 232.89 | 0.00 | 0.00 | 0.00 |
June | 168.70 | 10.19 | 158.51 | 191.26 | 183.40 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 240.39 | 159.35 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 360.19 | 167.49 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 504.49 | 199.45 | 0.00 | 0.00 | 0.00 |
October | 406.26 | 271.59 | 134.66 | 643.32 | 217.65 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.59 | 145.17 | 710.45 | 303.91 | 0.00 | 0.00 | 0.00 |
December | 551.07 | 419.43 | 131.63 | 799.03 | 333.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.37 | 153.21 | 480.66 | 250.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.70 | 10.19 | 131.63 | 191.26 | 159.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.07 | 419.43 | 168.63 | 799.03 | 333.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 744.87 | 327.99 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 547.57 | 301.85 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 427.33 | 315.88 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 383.12 | 261.75 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 218.04 | 232.89 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.51 | 191.26 | 183.40 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 240.39 | 159.35 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 360.19 | 167.49 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 504.49 | 199.45 | 0.00 | 0.00 | 0.00 |
October | 406.25 | 271.59 | 134.66 | 643.31 | 217.65 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.58 | 145.17 | 710.45 | 303.91 | 0.00 | 0.00 | 0.00 |
December | 551.06 | 419.43 | 131.63 | 799.02 | 333.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.36 | 153.21 | 480.66 | 250.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 191.26 | 159.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.06 | 419.43 | 168.63 | 799.02 | 333.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 744.88 | 327.99 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 547.58 | 301.85 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 427.34 | 315.88 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 383.12 | 261.75 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 218.04 | 232.89 | 0.00 | 0.00 | 0.00 |
June | 168.70 | 10.19 | 158.51 | 191.26 | 183.40 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 240.39 | 159.35 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 360.19 | 167.49 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 504.49 | 199.45 | 0.00 | 0.00 | 0.00 |
October | 406.26 | 271.59 | 134.66 | 643.32 | 217.65 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.59 | 145.17 | 710.45 | 303.91 | 0.00 | 0.00 | 0.00 |
December | 551.07 | 419.43 | 131.63 | 799.03 | 333.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.37 | 153.21 | 480.66 | 250.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.70 | 10.19 | 131.63 | 191.26 | 159.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.07 | 419.43 | 168.63 | 799.03 | 333.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 744.87 | 327.99 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 547.57 | 301.85 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 427.33 | 315.88 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 383.12 | 261.75 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 218.04 | 232.89 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.51 | 191.26 | 183.40 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 240.39 | 159.35 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 360.19 | 167.49 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 504.49 | 199.45 | 0.00 | 0.00 | 0.00 |
October | 406.25 | 271.59 | 134.66 | 643.31 | 217.65 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.58 | 145.17 | 710.45 | 303.91 | 0.00 | 0.00 | 0.00 |
December | 551.06 | 419.43 | 131.63 | 799.02 | 333.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.36 | 153.21 | 480.66 | 250.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 191.26 | 159.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.06 | 419.43 | 168.63 | 799.02 | 333.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.80 | 378.36 | 137.44 | 744.84 | 327.98 | 0.00 | 0.00 | 0.00 |
February | 405.39 | 249.70 | 155.69 | 547.55 | 301.84 | 0.00 | 0.00 | 0.00 |
March | 323.19 | 156.12 | 167.08 | 427.32 | 315.86 | 0.00 | 0.00 | 0.00 |
April | 270.04 | 102.97 | 167.07 | 383.11 | 261.74 | 0.00 | 0.00 | 0.00 |
May | 192.29 | 23.66 | 168.62 | 218.03 | 232.88 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.50 | 191.25 | 183.39 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.11 | 158.57 | 240.38 | 159.35 | 0.00 | 0.00 | 0.00 |
August | 229.56 | 72.41 | 157.15 | 360.17 | 167.48 | 0.00 | 0.00 | 0.00 |
September | 319.43 | 161.86 | 157.56 | 504.47 | 199.44 | 0.00 | 0.00 | 0.00 |
October | 406.24 | 271.58 | 134.66 | 643.29 | 217.64 | 0.00 | 0.00 | 0.00 |
November | 493.74 | 348.57 | 145.17 | 710.42 | 303.90 | 0.00 | 0.00 | 0.00 |
December | 551.04 | 419.41 | 131.63 | 798.99 | 333.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.56 | 184.36 | 153.20 | 480.64 | 250.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 191.25 | 159.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.04 | 419.41 | 168.62 | 798.99 | 333.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.99 | 112.46 | 110.52 | 262.96 | 405.77 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 296.12 | 384.81 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.91 | 170.03 | 342.81 | 397.52 | 0.00 | 0.00 | 0.00 |
April | 420.37 | 218.88 | 201.48 | 548.86 | 328.78 | 0.00 | 0.00 | 0.00 |
May | 412.93 | 190.73 | 222.20 | 532.25 | 275.07 | 0.00 | 0.00 | 0.00 |
June | 437.46 | 218.72 | 218.74 | 597.84 | 226.54 | 0.00 | 0.00 | 0.00 |
July | 463.08 | 247.79 | 215.29 | 670.11 | 202.59 | 0.00 | 0.00 | 0.00 |
August | 434.46 | 235.46 | 199.00 | 635.38 | 215.59 | 0.00 | 0.00 | 0.00 |
September | 371.98 | 199.04 | 172.94 | 531.45 | 236.24 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 410.17 | 272.32 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.51 | 307.89 | 394.05 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 264.95 | 447.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.16 | 174.56 | 167.59 | 450.82 | 315.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.99 | 112.46 | 105.18 | 262.96 | 202.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 247.79 | 222.20 | 670.11 | 447.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.99 | 112.46 | 110.52 | 262.96 | 405.77 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 296.12 | 384.81 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.91 | 170.03 | 342.81 | 397.52 | 0.00 | 0.00 | 0.00 |
April | 420.37 | 218.88 | 201.48 | 548.86 | 328.78 | 0.00 | 0.00 | 0.00 |
May | 412.93 | 190.73 | 222.20 | 532.25 | 275.07 | 0.00 | 0.00 | 0.00 |
June | 437.46 | 218.72 | 218.74 | 597.84 | 226.54 | 0.00 | 0.00 | 0.00 |
July | 463.08 | 247.79 | 215.29 | 670.11 | 202.59 | 0.00 | 0.00 | 0.00 |
August | 434.46 | 235.46 | 199.00 | 635.38 | 215.59 | 0.00 | 0.00 | 0.00 |
September | 371.98 | 199.04 | 172.94 | 531.45 | 236.24 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 410.17 | 272.32 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.51 | 307.89 | 394.05 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 264.95 | 447.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.16 | 174.56 | 167.59 | 450.82 | 315.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.99 | 112.46 | 105.18 | 262.96 | 202.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 247.79 | 222.20 | 670.11 | 447.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.98 | 112.46 | 110.52 | 262.95 | 405.76 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 296.11 | 384.80 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.90 | 170.02 | 342.81 | 397.51 | 0.00 | 0.00 | 0.00 |
April | 420.36 | 218.88 | 201.48 | 548.85 | 328.78 | 0.00 | 0.00 | 0.00 |
May | 412.92 | 190.73 | 222.20 | 532.24 | 275.07 | 0.00 | 0.00 | 0.00 |
June | 437.45 | 218.72 | 218.73 | 597.83 | 226.54 | 0.00 | 0.00 | 0.00 |
July | 463.07 | 247.79 | 215.29 | 670.09 | 202.59 | 0.00 | 0.00 | 0.00 |
August | 434.45 | 235.46 | 199.00 | 635.37 | 215.59 | 0.00 | 0.00 | 0.00 |
September | 371.97 | 199.04 | 172.94 | 531.44 | 236.24 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 410.16 | 272.31 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.50 | 307.88 | 394.05 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 264.94 | 447.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.15 | 174.56 | 167.59 | 450.81 | 315.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.98 | 112.46 | 105.18 | 262.95 | 202.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.07 | 247.79 | 222.20 | 670.09 | 447.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.82 | 0.00 | 390.82 | 222.69 | 1601.83 | 0.00 | 0.00 | 0.00 |
February | 490.59 | 0.00 | 490.59 | 265.32 | 1455.51 | 0.00 | 0.00 | 0.00 |
March | 601.18 | 0.00 | 601.18 | 393.25 | 1491.36 | 0.00 | 0.00 | 0.00 |
April | 692.63 | 2.67 | 689.96 | 562.25 | 1184.98 | 0.00 | 0.00 | 0.00 |
May | 832.32 | 38.76 | 793.56 | 714.00 | 1035.86 | 0.00 | 0.00 | 0.00 |
June | 886.88 | 86.71 | 800.17 | 921.67 | 821.16 | 0.00 | 0.00 | 0.00 |
July | 839.73 | 70.38 | 769.35 | 982.96 | 731.03 | 0.00 | 0.00 | 0.00 |
August | 697.37 | 13.96 | 683.41 | 790.27 | 765.47 | 0.00 | 0.00 | 0.00 |
September | 590.25 | 0.09 | 590.16 | 608.77 | 924.38 | 0.00 | 0.00 | 0.00 |
October | 468.21 | 0.00 | 468.21 | 533.85 | 1027.36 | 0.00 | 0.00 | 0.00 |
November | 423.93 | 0.00 | 423.93 | 258.41 | 1469.52 | 0.00 | 0.00 | 0.00 |
December | 363.82 | 0.00 | 363.82 | 201.52 | 1614.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.97 | 17.81 | 589.16 | 539.61 | 1175.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.82 | 0.00 | 363.82 | 201.52 | 731.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 886.88 | 86.71 | 800.17 | 982.96 | 1614.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 702.81 | 375.88 | 326.93 | 827.22 | 1000.17 | 0.00 | 0.00 | 0.00 |
February | 741.39 | 339.64 | 401.75 | 814.87 | 913.06 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 401.25 | 499.33 | 1036.12 | 935.20 | 0.00 | 0.00 | 0.00 |
April | 1151.37 | 577.43 | 573.93 | 1516.99 | 771.05 | 0.00 | 0.00 | 0.00 |
May | 1086.56 | 453.45 | 633.12 | 1371.78 | 701.78 | 0.00 | 0.00 | 0.00 |
June | 1079.80 | 468.51 | 611.29 | 1467.02 | 563.01 | 0.00 | 0.00 | 0.00 |
July | 1223.49 | 607.99 | 615.51 | 1799.54 | 508.64 | 0.00 | 0.00 | 0.00 |
August | 1208.30 | 641.81 | 566.49 | 1802.70 | 518.11 | 0.00 | 0.00 | 0.00 |
September | 879.74 | 403.13 | 476.61 | 1238.07 | 598.32 | 0.00 | 0.00 | 0.00 |
October | 778.73 | 400.25 | 378.48 | 1121.02 | 653.74 | 0.00 | 0.00 | 0.00 |
November | 709.90 | 360.66 | 349.24 | 835.98 | 919.96 | 0.00 | 0.00 | 0.00 |
December | 677.23 | 376.28 | 300.96 | 798.91 | 1000.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.57 | 451.41 | 478.15 | 1222.01 | 756.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 677.23 | 339.64 | 300.96 | 798.91 | 508.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.49 | 641.81 | 633.12 | 1802.70 | 1000.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2579.17 | 1891.94 | 687.23 | 3707.39 | 1609.62 | 0.00 | 0.00 | 0.00 |
February | 2027.09 | 1248.58 | 778.51 | 2721.70 | 1456.15 | 0.00 | 0.00 | 0.00 |
March | 1616.06 | 780.64 | 835.43 | 2135.47 | 1512.38 | 0.00 | 0.00 | 0.00 |
April | 1350.26 | 514.87 | 835.39 | 1915.65 | 1258.68 | 0.00 | 0.00 | 0.00 |
May | 961.49 | 118.32 | 843.17 | 1092.24 | 1127.02 | 0.00 | 0.00 | 0.00 |
June | 843.48 | 50.93 | 792.56 | 964.53 | 880.38 | 0.00 | 0.00 | 0.00 |
July | 893.48 | 100.58 | 792.90 | 1210.10 | 779.21 | 0.00 | 0.00 | 0.00 |
August | 1147.85 | 362.07 | 785.78 | 1801.14 | 824.65 | 0.00 | 0.00 | 0.00 |
September | 1597.24 | 809.38 | 787.86 | 2504.74 | 979.57 | 0.00 | 0.00 | 0.00 |
October | 2031.31 | 1357.99 | 673.32 | 3197.16 | 1067.60 | 0.00 | 0.00 | 0.00 |
November | 2468.85 | 1742.97 | 725.88 | 3533.19 | 1478.04 | 0.00 | 0.00 | 0.00 |
December | 2755.38 | 2097.20 | 658.18 | 3981.25 | 1615.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1687.89 | 921.85 | 766.04 | 2396.21 | 1214.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.48 | 50.93 | 658.18 | 964.53 | 779.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2755.38 | 2097.20 | 843.17 | 3981.25 | 1615.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 668.95 | 337.39 | 331.56 | 824.29 | 1075.84 | 0.00 | 0.00 | 0.00 |
February | 798.06 | 368.42 | 429.64 | 931.78 | 981.52 | 0.00 | 0.00 | 0.00 |
March | 914.79 | 404.72 | 510.07 | 1082.03 | 1003.46 | 0.00 | 0.00 | 0.00 |
April | 1261.09 | 656.65 | 604.44 | 1693.59 | 847.84 | 0.00 | 0.00 | 0.00 |
May | 1238.78 | 572.19 | 666.59 | 1611.53 | 761.26 | 0.00 | 0.00 | 0.00 |
June | 1312.36 | 656.15 | 656.20 | 1812.00 | 608.63 | 0.00 | 0.00 | 0.00 |
July | 1389.23 | 743.37 | 645.87 | 2035.50 | 554.70 | 0.00 | 0.00 | 0.00 |
August | 1303.37 | 706.37 | 597.00 | 1938.39 | 573.86 | 0.00 | 0.00 | 0.00 |
September | 1115.93 | 597.12 | 518.81 | 1603.57 | 648.88 | 0.00 | 0.00 | 0.00 |
October | 853.08 | 465.74 | 387.33 | 1261.26 | 712.84 | 0.00 | 0.00 | 0.00 |
November | 770.58 | 403.07 | 367.51 | 972.12 | 991.41 | 0.00 | 0.00 | 0.00 |
December | 680.56 | 365.02 | 315.54 | 855.78 | 1092.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.45 | 523.68 | 502.77 | 1387.40 | 820.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 668.95 | 337.39 | 315.54 | 824.29 | 554.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1389.23 | 743.37 | 666.59 | 2035.50 | 1092.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.82 | 0.00 | 390.82 | 274.57 | 1415.18 | 0.00 | 0.00 | 0.00 |
February | 490.59 | 0.00 | 490.59 | 317.01 | 1283.82 | 0.00 | 0.00 | 0.00 |
March | 601.18 | 0.00 | 601.18 | 442.04 | 1348.47 | 0.00 | 0.00 | 0.00 |
April | 692.63 | 2.67 | 689.96 | 589.49 | 1099.59 | 0.00 | 0.00 | 0.00 |
May | 832.32 | 38.76 | 793.56 | 745.76 | 967.77 | 0.00 | 0.00 | 0.00 |
June | 886.88 | 86.71 | 800.17 | 926.12 | 784.42 | 0.00 | 0.00 | 0.00 |
July | 839.73 | 70.38 | 769.35 | 975.15 | 709.74 | 0.00 | 0.00 | 0.00 |
August | 697.37 | 13.96 | 683.41 | 787.27 | 737.10 | 0.00 | 0.00 | 0.00 |
September | 590.25 | 0.09 | 590.16 | 619.53 | 868.55 | 0.00 | 0.00 | 0.00 |
October | 468.21 | 0.00 | 468.21 | 556.31 | 949.14 | 0.00 | 0.00 | 0.00 |
November | 423.93 | 0.00 | 423.93 | 307.64 | 1306.96 | 0.00 | 0.00 | 0.00 |
December | 363.82 | 0.00 | 363.82 | 253.72 | 1423.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.97 | 17.81 | 589.16 | 567.78 | 1073.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.82 | 0.00 | 363.82 | 253.72 | 709.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 886.88 | 86.71 | 800.17 | 975.15 | 1423.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 702.81 | 375.88 | 326.93 | 868.50 | 904.53 | 0.00 | 0.00 | 0.00 |
February | 741.39 | 339.64 | 401.75 | 847.92 | 825.62 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 401.25 | 499.33 | 1066.71 | 865.45 | 0.00 | 0.00 | 0.00 |
April | 1151.37 | 577.43 | 573.93 | 1528.01 | 733.36 | 0.00 | 0.00 | 0.00 |
May | 1086.56 | 453.45 | 633.12 | 1384.49 | 668.16 | 0.00 | 0.00 | 0.00 |
June | 1079.80 | 468.51 | 611.29 | 1465.00 | 547.46 | 0.00 | 0.00 | 0.00 |
July | 1223.49 | 607.99 | 615.51 | 1788.53 | 503.37 | 0.00 | 0.00 | 0.00 |
August | 1208.30 | 641.81 | 566.49 | 1794.03 | 509.93 | 0.00 | 0.00 | 0.00 |
September | 879.74 | 403.13 | 476.61 | 1239.43 | 574.31 | 0.00 | 0.00 | 0.00 |
October | 778.73 | 400.25 | 378.48 | 1132.13 | 618.63 | 0.00 | 0.00 | 0.00 |
November | 709.90 | 360.66 | 349.24 | 870.50 | 839.19 | 0.00 | 0.00 | 0.00 |
December | 677.23 | 376.28 | 300.96 | 840.14 | 905.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.57 | 451.41 | 478.15 | 1238.19 | 707.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 677.23 | 339.64 | 300.96 | 840.14 | 503.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.49 | 641.81 | 633.12 | 1794.03 | 905.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2579.17 | 1891.94 | 687.23 | 3754.25 | 1470.31 | 0.00 | 0.00 | 0.00 |
February | 2027.09 | 1248.58 | 778.51 | 2764.26 | 1319.10 | 0.00 | 0.00 | 0.00 |
March | 1616.06 | 780.64 | 835.43 | 2175.53 | 1390.27 | 0.00 | 0.00 | 0.00 |
April | 1350.26 | 514.87 | 835.39 | 1931.99 | 1184.82 | 0.00 | 0.00 | 0.00 |
May | 961.49 | 118.32 | 843.17 | 1114.26 | 1055.21 | 0.00 | 0.00 | 0.00 |
June | 843.48 | 50.93 | 792.56 | 969.79 | 841.92 | 0.00 | 0.00 | 0.00 |
July | 893.48 | 100.58 | 792.90 | 1202.78 | 759.54 | 0.00 | 0.00 | 0.00 |
August | 1147.85 | 362.07 | 785.78 | 1792.86 | 801.39 | 0.00 | 0.00 | 0.00 |
September | 1597.24 | 809.38 | 787.86 | 2503.50 | 936.55 | 0.00 | 0.00 | 0.00 |
October | 2031.31 | 1357.99 | 673.32 | 3208.53 | 1011.84 | 0.00 | 0.00 | 0.00 |
November | 2468.85 | 1742.97 | 725.88 | 3568.92 | 1362.97 | 0.00 | 0.00 | 0.00 |
December | 2755.38 | 2097.20 | 658.18 | 4026.71 | 1482.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1687.89 | 921.85 | 766.04 | 2416.84 | 1133.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.48 | 50.93 | 658.18 | 969.79 | 759.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2755.38 | 2097.20 | 843.17 | 4026.71 | 1482.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 668.95 | 337.39 | 331.56 | 847.91 | 980.26 | 0.00 | 0.00 | 0.00 |
February | 798.06 | 368.42 | 429.64 | 953.83 | 894.63 | 0.00 | 0.00 | 0.00 |
March | 914.79 | 404.72 | 510.07 | 1102.78 | 928.93 | 0.00 | 0.00 | 0.00 |
April | 1261.09 | 656.65 | 604.44 | 1700.38 | 803.24 | 0.00 | 0.00 | 0.00 |
May | 1238.78 | 572.19 | 666.59 | 1618.97 | 721.51 | 0.00 | 0.00 | 0.00 |
June | 1312.36 | 656.15 | 656.20 | 1807.55 | 587.39 | 0.00 | 0.00 | 0.00 |
July | 1389.23 | 743.37 | 645.87 | 2023.79 | 543.69 | 0.00 | 0.00 | 0.00 |
August | 1303.37 | 706.37 | 597.00 | 1929.07 | 559.67 | 0.00 | 0.00 | 0.00 |
September | 1115.93 | 597.12 | 518.81 | 1603.35 | 621.13 | 0.00 | 0.00 | 0.00 |
October | 853.08 | 465.74 | 387.33 | 1269.03 | 672.74 | 0.00 | 0.00 | 0.00 |
November | 770.58 | 403.07 | 367.51 | 992.49 | 909.79 | 0.00 | 0.00 | 0.00 |
December | 680.56 | 365.02 | 315.54 | 878.81 | 995.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.45 | 523.68 | 502.77 | 1396.17 | 767.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 668.95 | 337.39 | 315.54 | 847.91 | 543.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1389.23 | 743.37 | 666.59 | 2023.79 | 995.88 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209357E+09 | 0.00 | 0.209357E+09 | 97067783.51 | 0.955009E+09 |
February | 0.237367E+09 | 0.00 | 0.237367E+09 | 0.108197E+09 | 0.788315E+09 |
March | 0.322040E+09 | 0.00 | 0.322040E+09 | 0.186788E+09 | 0.886795E+09 |
April | 0.359060E+09 | 1381952.98 | 0.357678E+09 | 0.270265E+09 | 0.671045E+09 |
May | 0.445857E+09 | 20761368.39 | 0.425095E+09 | 0.367840E+09 | 0.587157E+09 |
June | 0.459758E+09 | 44948691.38 | 0.414809E+09 | 0.470828E+09 | 0.448381E+09 |
July | 0.449829E+09 | 37702800.77 | 0.412126E+09 | 0.517532E+09 | 0.405508E+09 |
August | 0.373568E+09 | 7480269.97 | 0.366088E+09 | 0.411507E+09 | 0.429262E+09 |
September | 0.305987E+09 | 47959.78 | 0.305939E+09 | 0.307174E+09 | 0.509519E+09 |
October | 0.250810E+09 | 0.00 | 0.250810E+09 | 0.270929E+09 | 0.597292E+09 |
November | 0.219765E+09 | 0.00 | 0.219765E+09 | 0.112285E+09 | 0.848367E+09 |
December | 0.194894E+09 | 0.00 | 0.194894E+09 | 79999694.23 | 0.982140E+09 |
Annual Sum or Average | 0.382829E+10 | 0.112323E+09 | 0.371597E+10 | 0.320041E+10 | 0.810879E+10 |
Minimum of Months | 0.194894E+09 | 0.00 | 0.194894E+09 | 79999694.23 | 0.405508E+09 |
Maximum of Months | 0.459758E+09 | 44948691.38 | 0.425095E+09 | 0.517532E+09 | 0.982140E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209354E+09 | 0.00 | 0.209354E+09 | 97066060.89 | 0.955007E+09 |
February | 0.237363E+09 | 0.00 | 0.237363E+09 | 0.108194E+09 | 0.788314E+09 |
March | 0.322035E+09 | 0.00 | 0.322035E+09 | 0.186783E+09 | 0.886795E+09 |
April | 0.359055E+09 | 1381922.60 | 0.357673E+09 | 0.270261E+09 | 0.671045E+09 |
May | 0.445851E+09 | 20760911.98 | 0.425090E+09 | 0.367832E+09 | 0.587156E+09 |
June | 0.459751E+09 | 44947703.23 | 0.414804E+09 | 0.470819E+09 | 0.448381E+09 |
July | 0.449823E+09 | 37701971.92 | 0.412122E+09 | 0.517525E+09 | 0.405507E+09 |
August | 0.373564E+09 | 7480105.53 | 0.366084E+09 | 0.411502E+09 | 0.429261E+09 |
September | 0.305984E+09 | 47958.73 | 0.305936E+09 | 0.307170E+09 | 0.509517E+09 |
October | 0.250807E+09 | 0.00 | 0.250807E+09 | 0.270926E+09 | 0.597289E+09 |
November | 0.219762E+09 | 0.00 | 0.219762E+09 | 0.112282E+09 | 0.848365E+09 |
December | 0.194891E+09 | 0.00 | 0.194891E+09 | 79998150.82 | 0.982138E+09 |
Annual Sum or Average | 0.382824E+10 | 0.112321E+09 | 0.371592E+10 | 0.320036E+10 | 0.810878E+10 |
Minimum of Months | 0.194891E+09 | 0.00 | 0.194891E+09 | 79998150.82 | 0.405507E+09 |
Maximum of Months | 0.459751E+09 | 44947703.23 | 0.425090E+09 | 0.517525E+09 | 0.982138E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209355E+09 | 0.00 | 0.209355E+09 | 97066370.15 | 0.955008E+09 |
February | 0.237365E+09 | 0.00 | 0.237365E+09 | 0.108195E+09 | 0.788315E+09 |
March | 0.322037E+09 | 0.00 | 0.322037E+09 | 0.186785E+09 | 0.886795E+09 |
April | 0.359057E+09 | 1381932.73 | 0.357675E+09 | 0.270263E+09 | 0.671045E+09 |
May | 0.445853E+09 | 20761064.12 | 0.425092E+09 | 0.367835E+09 | 0.587156E+09 |
June | 0.459754E+09 | 44948032.62 | 0.414806E+09 | 0.470822E+09 | 0.448381E+09 |
July | 0.449825E+09 | 37702248.20 | 0.412123E+09 | 0.517527E+09 | 0.405507E+09 |
August | 0.373565E+09 | 7480160.34 | 0.366085E+09 | 0.411504E+09 | 0.429261E+09 |
September | 0.305985E+09 | 47959.08 | 0.305937E+09 | 0.307171E+09 | 0.509518E+09 |
October | 0.250808E+09 | 0.00 | 0.250808E+09 | 0.270927E+09 | 0.597290E+09 |
November | 0.219763E+09 | 0.00 | 0.219763E+09 | 0.112283E+09 | 0.848366E+09 |
December | 0.194892E+09 | 0.00 | 0.194892E+09 | 79998665.33 | 0.982139E+09 |
Annual Sum or Average | 0.382826E+10 | 0.112321E+09 | 0.371594E+10 | 0.320038E+10 | 0.810878E+10 |
Minimum of Months | 0.194892E+09 | 0.00 | 0.194892E+09 | 79998665.33 | 0.405507E+09 |
Maximum of Months | 0.459754E+09 | 44948032.62 | 0.425092E+09 | 0.517527E+09 | 0.982139E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209354E+09 | 0.00 | 0.209354E+09 | 97066060.89 | 0.955007E+09 |
February | 0.237363E+09 | 0.00 | 0.237363E+09 | 0.108194E+09 | 0.788314E+09 |
March | 0.322035E+09 | 0.00 | 0.322035E+09 | 0.186783E+09 | 0.886795E+09 |
April | 0.359055E+09 | 1381922.60 | 0.357673E+09 | 0.270261E+09 | 0.671045E+09 |
May | 0.445851E+09 | 20760911.98 | 0.425090E+09 | 0.367832E+09 | 0.587156E+09 |
June | 0.459751E+09 | 44947703.23 | 0.414804E+09 | 0.470819E+09 | 0.448381E+09 |
July | 0.449823E+09 | 37701971.92 | 0.412122E+09 | 0.517525E+09 | 0.405507E+09 |
August | 0.373564E+09 | 7480105.53 | 0.366084E+09 | 0.411502E+09 | 0.429261E+09 |
September | 0.305984E+09 | 47958.73 | 0.305936E+09 | 0.307170E+09 | 0.509517E+09 |
October | 0.250807E+09 | 0.00 | 0.250807E+09 | 0.270926E+09 | 0.597289E+09 |
November | 0.219762E+09 | 0.00 | 0.219762E+09 | 0.112282E+09 | 0.848365E+09 |
December | 0.194891E+09 | 0.00 | 0.194891E+09 | 79998150.82 | 0.982138E+09 |
Annual Sum or Average | 0.382824E+10 | 0.112321E+09 | 0.371592E+10 | 0.320036E+10 | 0.810878E+10 |
Minimum of Months | 0.194891E+09 | 0.00 | 0.194891E+09 | 79998150.82 | 0.405507E+09 |
Maximum of Months | 0.459751E+09 | 44947703.23 | 0.425090E+09 | 0.517525E+09 | 0.982138E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209346E+09 | 0.00 | 0.209346E+09 | 97062502.05 | 0.954969E+09 |
February | 0.237354E+09 | 0.00 | 0.237354E+09 | 0.108190E+09 | 0.788283E+09 |
March | 0.322023E+09 | 0.00 | 0.322023E+09 | 0.186777E+09 | 0.886759E+09 |
April | 0.359042E+09 | 1381871.97 | 0.357660E+09 | 0.270251E+09 | 0.671018E+09 |
May | 0.445834E+09 | 20760151.29 | 0.425073E+09 | 0.367818E+09 | 0.587133E+09 |
June | 0.459734E+09 | 44946056.33 | 0.414788E+09 | 0.470801E+09 | 0.448363E+09 |
July | 0.449806E+09 | 37700590.50 | 0.412106E+09 | 0.517505E+09 | 0.405491E+09 |
August | 0.373550E+09 | 7479831.45 | 0.366070E+09 | 0.411486E+09 | 0.429244E+09 |
September | 0.305972E+09 | 47956.97 | 0.305924E+09 | 0.307158E+09 | 0.509497E+09 |
October | 0.250797E+09 | 0.00 | 0.250797E+09 | 0.270915E+09 | 0.597266E+09 |
November | 0.219753E+09 | 0.00 | 0.219753E+09 | 0.112278E+09 | 0.848331E+09 |
December | 0.194884E+09 | 0.00 | 0.194884E+09 | 79995183.80 | 0.982099E+09 |
Annual Sum or Average | 0.382810E+10 | 0.112316E+09 | 0.371578E+10 | 0.320024E+10 | 0.810845E+10 |
Minimum of Months | 0.194884E+09 | 0.00 | 0.194884E+09 | 79995183.80 | 0.405491E+09 |
Maximum of Months | 0.459734E+09 | 44946056.33 | 0.425073E+09 | 0.517505E+09 | 0.982099E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627473E+09 | 0.335587E+09 | 0.291886E+09 | 0.716276E+09 | 0.969122E+09 |
February | 0.597862E+09 | 0.273886E+09 | 0.323977E+09 | 0.641349E+09 | 0.798251E+09 |
March | 0.804038E+09 | 0.358236E+09 | 0.445802E+09 | 0.910655E+09 | 0.891465E+09 |
April | 0.994793E+09 | 0.498909E+09 | 0.495884E+09 | 0.131264E+10 | 0.687274E+09 |
May | 0.970094E+09 | 0.404843E+09 | 0.565251E+09 | 0.122434E+10 | 0.651001E+09 |
June | 0.932955E+09 | 0.404793E+09 | 0.528162E+09 | 0.127264E+10 | 0.499677E+09 |
July | 0.109235E+10 | 0.542816E+09 | 0.549530E+09 | 0.162024E+10 | 0.446688E+09 |
August | 0.107878E+10 | 0.573012E+09 | 0.505768E+09 | 0.162258E+10 | 0.451989E+09 |
September | 0.760101E+09 | 0.348307E+09 | 0.411794E+09 | 0.107054E+10 | 0.537402E+09 |
October | 0.695256E+09 | 0.357344E+09 | 0.337912E+09 | 0.997694E+09 | 0.610944E+09 |
November | 0.613362E+09 | 0.311613E+09 | 0.301749E+09 | 0.705808E+09 | 0.851461E+09 |
December | 0.604640E+09 | 0.335945E+09 | 0.268696E+09 | 0.689594E+09 | 0.966628E+09 |
Annual Sum or Average | 0.977170E+10 | 0.474529E+10 | 0.502641E+10 | 0.127843E+11 | 0.836190E+10 |
Minimum of Months | 0.597862E+09 | 0.273886E+09 | 0.268696E+09 | 0.641349E+09 | 0.446688E+09 |
Maximum of Months | 0.109235E+10 | 0.573012E+09 | 0.565251E+09 | 0.162258E+10 | 0.969122E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627473E+09 | 0.335587E+09 | 0.291886E+09 | 0.716276E+09 | 0.969122E+09 |
February | 0.597862E+09 | 0.273886E+09 | 0.323977E+09 | 0.641349E+09 | 0.798251E+09 |
March | 0.804038E+09 | 0.358236E+09 | 0.445802E+09 | 0.910655E+09 | 0.891465E+09 |
April | 0.994793E+09 | 0.498909E+09 | 0.495884E+09 | 0.131264E+10 | 0.687274E+09 |
May | 0.970094E+09 | 0.404843E+09 | 0.565251E+09 | 0.122434E+10 | 0.651001E+09 |
June | 0.932955E+09 | 0.404793E+09 | 0.528162E+09 | 0.127264E+10 | 0.499677E+09 |
July | 0.109235E+10 | 0.542816E+09 | 0.549530E+09 | 0.162024E+10 | 0.446688E+09 |
August | 0.107878E+10 | 0.573012E+09 | 0.505768E+09 | 0.162258E+10 | 0.451989E+09 |
September | 0.760101E+09 | 0.348307E+09 | 0.411794E+09 | 0.107054E+10 | 0.537402E+09 |
October | 0.695256E+09 | 0.357344E+09 | 0.337912E+09 | 0.997694E+09 | 0.610944E+09 |
November | 0.613362E+09 | 0.311613E+09 | 0.301749E+09 | 0.705808E+09 | 0.851461E+09 |
December | 0.604640E+09 | 0.335945E+09 | 0.268696E+09 | 0.689594E+09 | 0.966628E+09 |
Annual Sum or Average | 0.977170E+10 | 0.474529E+10 | 0.502641E+10 | 0.127843E+11 | 0.836190E+10 |
Minimum of Months | 0.597862E+09 | 0.273886E+09 | 0.268696E+09 | 0.641349E+09 | 0.446688E+09 |
Maximum of Months | 0.109235E+10 | 0.573012E+09 | 0.565251E+09 | 0.162258E+10 | 0.969122E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627461E+09 | 0.335581E+09 | 0.291880E+09 | 0.716263E+09 | 0.969104E+09 |
February | 0.597852E+09 | 0.273881E+09 | 0.323971E+09 | 0.641338E+09 | 0.798236E+09 |
March | 0.804023E+09 | 0.358229E+09 | 0.445794E+09 | 0.910638E+09 | 0.891448E+09 |
April | 0.994775E+09 | 0.498900E+09 | 0.495875E+09 | 0.131262E+10 | 0.687261E+09 |
May | 0.970077E+09 | 0.404836E+09 | 0.565241E+09 | 0.122431E+10 | 0.650989E+09 |
June | 0.932938E+09 | 0.404785E+09 | 0.528152E+09 | 0.127261E+10 | 0.499668E+09 |
July | 0.109233E+10 | 0.542806E+09 | 0.549520E+09 | 0.162021E+10 | 0.446680E+09 |
August | 0.107876E+10 | 0.573001E+09 | 0.505759E+09 | 0.162255E+10 | 0.451981E+09 |
September | 0.760087E+09 | 0.348301E+09 | 0.411786E+09 | 0.107052E+10 | 0.537392E+09 |
October | 0.695243E+09 | 0.357337E+09 | 0.337906E+09 | 0.997675E+09 | 0.610933E+09 |
November | 0.613351E+09 | 0.311608E+09 | 0.301743E+09 | 0.705795E+09 | 0.851445E+09 |
December | 0.604629E+09 | 0.335938E+09 | 0.268691E+09 | 0.689581E+09 | 0.966610E+09 |
Annual Sum or Average | 0.977152E+10 | 0.474520E+10 | 0.502632E+10 | 0.127841E+11 | 0.836175E+10 |
Minimum of Months | 0.597852E+09 | 0.273881E+09 | 0.268691E+09 | 0.641338E+09 | 0.446680E+09 |
Maximum of Months | 0.109233E+10 | 0.573001E+09 | 0.565241E+09 | 0.162255E+10 | 0.969104E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368131E+09 | 0.199508E+10 | 0.878492E+09 |
February | 0.980770E+09 | 0.604101E+09 | 0.376669E+09 | 0.132470E+10 | 0.730237E+09 |
March | 0.865679E+09 | 0.418162E+09 | 0.447517E+09 | 0.114458E+10 | 0.846045E+09 |
April | 0.699966E+09 | 0.266902E+09 | 0.433064E+09 | 0.993056E+09 | 0.678462E+09 |
May | 0.515046E+09 | 63382741.22 | 0.451663E+09 | 0.583991E+09 | 0.623775E+09 |
June | 0.437258E+09 | 26399694.62 | 0.410858E+09 | 0.495747E+09 | 0.475363E+09 |
July | 0.478615E+09 | 53877696.07 | 0.424738E+09 | 0.643866E+09 | 0.426810E+09 |
August | 0.614875E+09 | 0.193949E+09 | 0.420926E+09 | 0.964732E+09 | 0.448597E+09 |
September | 0.827995E+09 | 0.419571E+09 | 0.408424E+09 | 0.130764E+10 | 0.516966E+09 |
October | 0.108811E+10 | 0.727433E+09 | 0.360682E+09 | 0.172306E+10 | 0.582943E+09 |
November | 0.127983E+10 | 0.903539E+09 | 0.376292E+09 | 0.184150E+10 | 0.787747E+09 |
December | 0.147597E+10 | 0.112341E+10 | 0.352567E+09 | 0.214011E+10 | 0.894013E+09 |
Annual Sum or Average | 0.106457E+11 | 0.581418E+10 | 0.483153E+10 | 0.151581E+11 | 0.788945E+10 |
Minimum of Months | 0.437258E+09 | 26399694.62 | 0.352567E+09 | 0.495747E+09 | 0.426810E+09 |
Maximum of Months | 0.147597E+10 | 0.112341E+10 | 0.451663E+09 | 0.214011E+10 | 0.894013E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368129E+09 | 0.199506E+10 | 0.878491E+09 |
February | 0.980763E+09 | 0.604097E+09 | 0.376667E+09 | 0.132469E+10 | 0.730236E+09 |
March | 0.865673E+09 | 0.418159E+09 | 0.447515E+09 | 0.114457E+10 | 0.846044E+09 |
April | 0.699962E+09 | 0.266900E+09 | 0.433063E+09 | 0.993049E+09 | 0.678462E+09 |
May | 0.515043E+09 | 63382276.75 | 0.451661E+09 | 0.583987E+09 | 0.623774E+09 |
June | 0.437256E+09 | 26399501.16 | 0.410856E+09 | 0.495744E+09 | 0.475363E+09 |
July | 0.478613E+09 | 53877301.25 | 0.424736E+09 | 0.643863E+09 | 0.426810E+09 |
August | 0.614872E+09 | 0.193947E+09 | 0.420924E+09 | 0.964726E+09 | 0.448597E+09 |
September | 0.827990E+09 | 0.419568E+09 | 0.408422E+09 | 0.130763E+10 | 0.516966E+09 |
October | 0.108811E+10 | 0.727427E+09 | 0.360680E+09 | 0.172305E+10 | 0.582942E+09 |
November | 0.127982E+10 | 0.903532E+09 | 0.376290E+09 | 0.184148E+10 | 0.787746E+09 |
December | 0.147596E+10 | 0.112340E+10 | 0.352566E+09 | 0.214010E+10 | 0.894012E+09 |
Annual Sum or Average | 0.106456E+11 | 0.581413E+10 | 0.483151E+10 | 0.151579E+11 | 0.788944E+10 |
Minimum of Months | 0.437256E+09 | 26399501.16 | 0.352566E+09 | 0.495744E+09 | 0.426810E+09 |
Maximum of Months | 0.147596E+10 | 0.112340E+10 | 0.451661E+09 | 0.214010E+10 | 0.894012E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368131E+09 | 0.199508E+10 | 0.878492E+09 |
February | 0.980770E+09 | 0.604101E+09 | 0.376669E+09 | 0.132470E+10 | 0.730237E+09 |
March | 0.865679E+09 | 0.418162E+09 | 0.447517E+09 | 0.114458E+10 | 0.846045E+09 |
April | 0.699966E+09 | 0.266902E+09 | 0.433064E+09 | 0.993056E+09 | 0.678462E+09 |
May | 0.515046E+09 | 63382741.22 | 0.451663E+09 | 0.583991E+09 | 0.623775E+09 |
June | 0.437258E+09 | 26399694.62 | 0.410858E+09 | 0.495747E+09 | 0.475363E+09 |
July | 0.478615E+09 | 53877696.07 | 0.424738E+09 | 0.643866E+09 | 0.426810E+09 |
August | 0.614875E+09 | 0.193949E+09 | 0.420926E+09 | 0.964732E+09 | 0.448597E+09 |
September | 0.827995E+09 | 0.419571E+09 | 0.408424E+09 | 0.130764E+10 | 0.516966E+09 |
October | 0.108811E+10 | 0.727433E+09 | 0.360682E+09 | 0.172306E+10 | 0.582943E+09 |
November | 0.127983E+10 | 0.903539E+09 | 0.376292E+09 | 0.184150E+10 | 0.787747E+09 |
December | 0.147597E+10 | 0.112341E+10 | 0.352567E+09 | 0.214011E+10 | 0.894013E+09 |
Annual Sum or Average | 0.106457E+11 | 0.581418E+10 | 0.483153E+10 | 0.151581E+11 | 0.788945E+10 |
Minimum of Months | 0.437258E+09 | 26399694.62 | 0.352567E+09 | 0.495747E+09 | 0.426810E+09 |
Maximum of Months | 0.147597E+10 | 0.112341E+10 | 0.451663E+09 | 0.214011E+10 | 0.894013E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368129E+09 | 0.199506E+10 | 0.878491E+09 |
February | 0.980763E+09 | 0.604097E+09 | 0.376667E+09 | 0.132469E+10 | 0.730236E+09 |
March | 0.865673E+09 | 0.418159E+09 | 0.447515E+09 | 0.114457E+10 | 0.846044E+09 |
April | 0.699962E+09 | 0.266900E+09 | 0.433063E+09 | 0.993049E+09 | 0.678462E+09 |
May | 0.515043E+09 | 63382276.75 | 0.451661E+09 | 0.583987E+09 | 0.623774E+09 |
June | 0.437256E+09 | 26399501.16 | 0.410856E+09 | 0.495744E+09 | 0.475363E+09 |
July | 0.478613E+09 | 53877301.25 | 0.424736E+09 | 0.643863E+09 | 0.426810E+09 |
August | 0.614872E+09 | 0.193947E+09 | 0.420924E+09 | 0.964726E+09 | 0.448597E+09 |
September | 0.827990E+09 | 0.419568E+09 | 0.408422E+09 | 0.130763E+10 | 0.516966E+09 |
October | 0.108811E+10 | 0.727427E+09 | 0.360680E+09 | 0.172305E+10 | 0.582942E+09 |
November | 0.127982E+10 | 0.903532E+09 | 0.376290E+09 | 0.184148E+10 | 0.787746E+09 |
December | 0.147596E+10 | 0.112340E+10 | 0.352566E+09 | 0.214010E+10 | 0.894012E+09 |
Annual Sum or Average | 0.106456E+11 | 0.581413E+10 | 0.483151E+10 | 0.151579E+11 | 0.788944E+10 |
Minimum of Months | 0.437256E+09 | 26399501.16 | 0.352566E+09 | 0.495744E+09 | 0.426810E+09 |
Maximum of Months | 0.147596E+10 | 0.112340E+10 | 0.451661E+09 | 0.214010E+10 | 0.894012E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138152E+10 | 0.101341E+10 | 0.368115E+09 | 0.199499E+10 | 0.878456E+09 |
February | 0.980727E+09 | 0.604074E+09 | 0.376653E+09 | 0.132464E+10 | 0.730207E+09 |
March | 0.865641E+09 | 0.418143E+09 | 0.447498E+09 | 0.114453E+10 | 0.846010E+09 |
April | 0.699936E+09 | 0.266890E+09 | 0.433046E+09 | 0.993013E+09 | 0.678434E+09 |
May | 0.515024E+09 | 63379954.39 | 0.451644E+09 | 0.583965E+09 | 0.623749E+09 |
June | 0.437239E+09 | 26398533.87 | 0.410841E+09 | 0.495726E+09 | 0.475344E+09 |
July | 0.478595E+09 | 53875327.16 | 0.424720E+09 | 0.643839E+09 | 0.426793E+09 |
August | 0.614849E+09 | 0.193940E+09 | 0.420908E+09 | 0.964690E+09 | 0.448579E+09 |
September | 0.827959E+09 | 0.419553E+09 | 0.408406E+09 | 0.130758E+10 | 0.516945E+09 |
October | 0.108807E+10 | 0.727401E+09 | 0.360666E+09 | 0.172298E+10 | 0.582919E+09 |
November | 0.127977E+10 | 0.903499E+09 | 0.376276E+09 | 0.184142E+10 | 0.787715E+09 |
December | 0.147591E+10 | 0.112336E+10 | 0.352552E+09 | 0.214002E+10 | 0.893977E+09 |
Annual Sum or Average | 0.106452E+11 | 0.581392E+10 | 0.483132E+10 | 0.151574E+11 | 0.788913E+10 |
Minimum of Months | 0.437239E+09 | 26398533.87 | 0.352552E+09 | 0.495726E+09 | 0.426793E+09 |
Maximum of Months | 0.147591E+10 | 0.112336E+10 | 0.451644E+09 | 0.214002E+10 | 0.893977E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597244E+09 | 0.301223E+09 | 0.296021E+09 | 0.704301E+09 | 0.108681E+10 |
February | 0.643562E+09 | 0.297098E+09 | 0.346464E+09 | 0.716365E+09 | 0.930923E+09 |
March | 0.816733E+09 | 0.361335E+09 | 0.455397E+09 | 0.918190E+09 | 0.106471E+10 |
April | 0.108959E+10 | 0.567348E+09 | 0.522243E+09 | 0.142264E+10 | 0.852209E+09 |
May | 0.110600E+10 | 0.510859E+09 | 0.595139E+09 | 0.142558E+10 | 0.736751E+09 |
June | 0.113389E+10 | 0.566922E+09 | 0.566965E+09 | 0.154959E+10 | 0.587193E+09 |
July | 0.124032E+10 | 0.663685E+09 | 0.576636E+09 | 0.179481E+10 | 0.542622E+09 |
August | 0.116366E+10 | 0.630657E+09 | 0.533006E+09 | 0.170180E+10 | 0.577436E+09 |
September | 0.964171E+09 | 0.515914E+09 | 0.448257E+09 | 0.137751E+10 | 0.612342E+09 |
October | 0.761634E+09 | 0.415819E+09 | 0.345814E+09 | 0.109860E+10 | 0.729375E+09 |
November | 0.665790E+09 | 0.348255E+09 | 0.317535E+09 | 0.798043E+09 | 0.102139E+10 |
December | 0.607608E+09 | 0.325892E+09 | 0.281715E+09 | 0.709640E+09 | 0.119841E+10 |
Annual Sum or Average | 0.107902E+11 | 0.550501E+10 | 0.528519E+10 | 0.142171E+11 | 0.994017E+10 |
Minimum of Months | 0.597244E+09 | 0.297098E+09 | 0.281715E+09 | 0.704301E+09 | 0.542622E+09 |
Maximum of Months | 0.124032E+10 | 0.663685E+09 | 0.595139E+09 | 0.179481E+10 | 0.119841E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597244E+09 | 0.301223E+09 | 0.296021E+09 | 0.704301E+09 | 0.108681E+10 |
February | 0.643562E+09 | 0.297098E+09 | 0.346464E+09 | 0.716365E+09 | 0.930923E+09 |
March | 0.816733E+09 | 0.361335E+09 | 0.455397E+09 | 0.918190E+09 | 0.106471E+10 |
April | 0.108959E+10 | 0.567348E+09 | 0.522243E+09 | 0.142264E+10 | 0.852209E+09 |
May | 0.110600E+10 | 0.510859E+09 | 0.595139E+09 | 0.142558E+10 | 0.736751E+09 |
June | 0.113389E+10 | 0.566922E+09 | 0.566965E+09 | 0.154959E+10 | 0.587193E+09 |
July | 0.124032E+10 | 0.663685E+09 | 0.576636E+09 | 0.179481E+10 | 0.542622E+09 |
August | 0.116366E+10 | 0.630657E+09 | 0.533006E+09 | 0.170180E+10 | 0.577436E+09 |
September | 0.964171E+09 | 0.515914E+09 | 0.448257E+09 | 0.137751E+10 | 0.612342E+09 |
October | 0.761634E+09 | 0.415819E+09 | 0.345814E+09 | 0.109860E+10 | 0.729375E+09 |
November | 0.665790E+09 | 0.348255E+09 | 0.317535E+09 | 0.798043E+09 | 0.102139E+10 |
December | 0.607608E+09 | 0.325892E+09 | 0.281715E+09 | 0.709640E+09 | 0.119841E+10 |
Annual Sum or Average | 0.107902E+11 | 0.550501E+10 | 0.528519E+10 | 0.142171E+11 | 0.994017E+10 |
Minimum of Months | 0.597244E+09 | 0.297098E+09 | 0.281715E+09 | 0.704301E+09 | 0.542622E+09 |
Maximum of Months | 0.124032E+10 | 0.663685E+09 | 0.595139E+09 | 0.179481E+10 | 0.119841E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597233E+09 | 0.301218E+09 | 0.296016E+09 | 0.704288E+09 | 0.108679E+10 |
February | 0.643550E+09 | 0.297093E+09 | 0.346457E+09 | 0.716351E+09 | 0.930906E+09 |
March | 0.816718E+09 | 0.361329E+09 | 0.455389E+09 | 0.918174E+09 | 0.106469E+10 |
April | 0.108957E+10 | 0.567338E+09 | 0.522233E+09 | 0.142261E+10 | 0.852193E+09 |
May | 0.110598E+10 | 0.510849E+09 | 0.595129E+09 | 0.142555E+10 | 0.736738E+09 |
June | 0.113387E+10 | 0.566912E+09 | 0.566955E+09 | 0.154956E+10 | 0.587182E+09 |
July | 0.124030E+10 | 0.663673E+09 | 0.576625E+09 | 0.179478E+10 | 0.542612E+09 |
August | 0.116364E+10 | 0.630646E+09 | 0.532996E+09 | 0.170177E+10 | 0.577426E+09 |
September | 0.964154E+09 | 0.515905E+09 | 0.448249E+09 | 0.137748E+10 | 0.612330E+09 |
October | 0.761620E+09 | 0.415812E+09 | 0.345808E+09 | 0.109858E+10 | 0.729362E+09 |
November | 0.665778E+09 | 0.348249E+09 | 0.317529E+09 | 0.798028E+09 | 0.102137E+10 |
December | 0.607596E+09 | 0.325886E+09 | 0.281710E+09 | 0.709627E+09 | 0.119839E+10 |
Annual Sum or Average | 0.107900E+11 | 0.550491E+10 | 0.528510E+10 | 0.142168E+11 | 0.993999E+10 |
Minimum of Months | 0.597233E+09 | 0.297093E+09 | 0.281710E+09 | 0.704288E+09 | 0.542612E+09 |
Maximum of Months | 0.124030E+10 | 0.663673E+09 | 0.595129E+09 | 0.179478E+10 | 0.119839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.596445E+09 | 0.429034E+10 |
February | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.641858E+09 | 0.352118E+10 |
March | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.105329E+10 | 0.399445E+10 |
April | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.145736E+10 | 0.307147E+10 |
May | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.191239E+10 | 0.277444E+10 |
June | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.238897E+10 | 0.212846E+10 |
July | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.263276E+10 | 0.195800E+10 |
August | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.211666E+10 | 0.205022E+10 |
September | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.157794E+10 | 0.239598E+10 |
October | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.142985E+10 | 0.275168E+10 |
November | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.669811E+09 | 0.380900E+10 |
December | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.539762E+09 | 0.432451E+10 |
Annual Sum or Average | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.170171E+11 | 0.370697E+11 |
Minimum of Months | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.539762E+09 | 0.195800E+10 |
Maximum of Months | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.263276E+10 | 0.432451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.221562E+10 | 0.267886E+10 |
February | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.197134E+10 | 0.220887E+10 |
March | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.277514E+10 | 0.250485E+10 |
April | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.393203E+10 | 0.199857E+10 |
May | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.367418E+10 | 0.187964E+10 |
June | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.380252E+10 | 0.145932E+10 |
July | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.481989E+10 | 0.136234E+10 |
August | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.482835E+10 | 0.138770E+10 |
September | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.320909E+10 | 0.155085E+10 |
October | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.300255E+10 | 0.175099E+10 |
November | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.216686E+10 | 0.238454E+10 |
December | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.213981E+10 | 0.267986E+10 |
Annual Sum or Average | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.385374E+11 | 0.238464E+11 |
Minimum of Months | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.197134E+10 | 0.136234E+10 |
Maximum of Months | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.482835E+10 | 0.267986E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.992988E+10 | 0.431121E+10 |
February | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.658434E+10 | 0.352271E+10 |
March | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.571964E+10 | 0.405077E+10 |
April | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.496536E+10 | 0.326249E+10 |
May | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.292547E+10 | 0.301860E+10 |
June | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.250007E+10 | 0.228193E+10 |
July | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.324112E+10 | 0.208703E+10 |
August | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.482417E+10 | 0.220873E+10 |
September | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.649230E+10 | 0.253905E+10 |
October | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.856328E+10 | 0.285947E+10 |
November | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.915803E+10 | 0.383107E+10 |
December | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.106634E+11 | 0.432823E+10 |
Annual Sum or Average | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.755670E+11 | 0.383013E+11 |
Minimum of Months | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.250007E+10 | 0.208703E+10 |
Maximum of Months | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.106634E+11 | 0.432823E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.220777E+10 | 0.288153E+10 |
February | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.225417E+10 | 0.237450E+10 |
March | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.289812E+10 | 0.268766E+10 |
April | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.438978E+10 | 0.219761E+10 |
May | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.431633E+10 | 0.203896E+10 |
June | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.469671E+10 | 0.157758E+10 |
July | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.545187E+10 | 0.148570E+10 |
August | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.519177E+10 | 0.153704E+10 |
September | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.415646E+10 | 0.168191E+10 |
October | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.337816E+10 | 0.190927E+10 |
November | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.251973E+10 | 0.256974E+10 |
December | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.229212E+10 | 0.292616E+10 |
Annual Sum or Average | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.437530E+11 | 0.258677E+11 |
Minimum of Months | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.220777E+10 | 0.148570E+10 |
Maximum of Months | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.545187E+10 | 0.292616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.735419E+09 | 0.379041E+10 |
February | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.766900E+09 | 0.310583E+10 |
March | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.118397E+10 | 0.361175E+10 |
April | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.152795E+10 | 0.285013E+10 |
May | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.199744E+10 | 0.259207E+10 |
June | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.240050E+10 | 0.203321E+10 |
July | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.261183E+10 | 0.190096E+10 |
August | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.210863E+10 | 0.197424E+10 |
September | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.160583E+10 | 0.225128E+10 |
October | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.149001E+10 | 0.254217E+10 |
November | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.797410E+09 | 0.338764E+10 |
December | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.679569E+09 | 0.381354E+10 |
Annual Sum or Average | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.179054E+11 | 0.338532E+11 |
Minimum of Months | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.679569E+09 | 0.190096E+10 |
Maximum of Months | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.261183E+10 | 0.381354E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.232620E+10 | 0.242269E+10 |
February | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.205128E+10 | 0.199734E+10 |
March | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.285707E+10 | 0.231801E+10 |
April | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.396060E+10 | 0.190087E+10 |
May | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.370823E+10 | 0.178961E+10 |
June | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.379729E+10 | 0.141901E+10 |
July | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.479039E+10 | 0.134822E+10 |
August | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.480514E+10 | 0.136578E+10 |
September | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.321261E+10 | 0.148861E+10 |
October | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.303230E+10 | 0.165693E+10 |
November | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.225634E+10 | 0.217519E+10 |
December | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.225023E+10 | 0.242660E+10 |
Annual Sum or Average | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.390477E+11 | 0.223089E+11 |
Minimum of Months | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.205128E+10 | 0.134822E+10 |
Maximum of Months | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.480514E+10 | 0.242660E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.100554E+11 | 0.393808E+10 |
February | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.668729E+10 | 0.319118E+10 |
March | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.582695E+10 | 0.372371E+10 |
April | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.500771E+10 | 0.307104E+10 |
May | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.298445E+10 | 0.282629E+10 |
June | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.251369E+10 | 0.218226E+10 |
July | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.322153E+10 | 0.203435E+10 |
August | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.480198E+10 | 0.214644E+10 |
September | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.648907E+10 | 0.242753E+10 |
October | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.859372E+10 | 0.271012E+10 |
November | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.925064E+10 | 0.353281E+10 |
December | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.107851E+11 | 0.397199E+10 |
Annual Sum or Average | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.762175E+11 | 0.357558E+11 |
Minimum of Months | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.251369E+10 | 0.203435E+10 |
Maximum of Months | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.107851E+11 | 0.397199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.227105E+10 | 0.262553E+10 |
February | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.230751E+10 | 0.216430E+10 |
March | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.295370E+10 | 0.248804E+10 |
April | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.440737E+10 | 0.208199E+10 |
May | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.433624E+10 | 0.193250E+10 |
June | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.468517E+10 | 0.152252E+10 |
July | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.542052E+10 | 0.145621E+10 |
August | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.516683E+10 | 0.149901E+10 |
September | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.415588E+10 | 0.160997E+10 |
October | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.339896E+10 | 0.180186E+10 |
November | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.257253E+10 | 0.235819E+10 |
December | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.235382E+10 | 0.266737E+10 |
Annual Sum or Average | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.440296E+11 | 0.242075E+11 |
Minimum of Months | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.227105E+10 | 0.145621E+10 |
Maximum of Months | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.542052E+10 | 0.266737E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.20 | 1782.78 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 223.62 | 1629.27 | 490.58 | 0.00 | 490.58 | 0.00 | 0.00 |
March | 348.68 | 1655.44 | 601.17 | 0.00 | 601.17 | 0.00 | 0.00 |
April | 521.34 | 1294.44 | 692.62 | 2.67 | 689.95 | 0.00 | 0.00 |
May | 686.66 | 1096.09 | 832.30 | 38.76 | 793.55 | 0.00 | 0.00 |
June | 908.21 | 864.93 | 886.86 | 86.70 | 800.16 | 0.00 | 0.00 |
July | 966.10 | 756.99 | 839.72 | 70.38 | 769.34 | 0.00 | 0.00 |
August | 768.18 | 801.33 | 697.36 | 13.96 | 683.40 | 0.00 | 0.00 |
September | 592.53 | 982.86 | 590.24 | 0.09 | 590.15 | 0.00 | 0.00 |
October | 505.76 | 1115.00 | 468.20 | 0.00 | 468.20 | 0.00 | 0.00 |
November | 216.59 | 1636.49 | 423.92 | 0.00 | 423.92 | 0.00 | 0.00 |
December | 149.34 | 1833.43 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 507.41 | 1285.63 | 606.96 | 17.81 | 589.15 | 0.00 | 0.00 |
Minimum of Months | 149.34 | 756.99 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 966.10 | 1833.43 | 886.86 | 86.70 | 800.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 802.28 | 1085.48 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 795.32 | 989.89 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1019.99 | 998.50 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1519.25 | 795.45 | 1151.37 | 577.44 | 573.94 | 0.00 | 0.00 |
May | 1371.34 | 729.16 | 1086.57 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1472.95 | 578.33 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1814.77 | 500.32 | 1223.50 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1817.39 | 506.26 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1239.04 | 621.99 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1117.48 | 684.30 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 816.90 | 985.48 | 709.91 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 772.39 | 1082.69 | 677.24 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1216.16 | 795.46 | 929.57 | 451.41 | 478.16 | 0.00 | 0.00 |
Minimum of Months | 772.39 | 500.32 | 677.24 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1817.39 | 1085.48 | 1223.50 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3724.34 | 1639.94 | 2579.09 | 1891.88 | 687.21 | 0.00 | 0.00 |
February | 2737.85 | 1509.24 | 2027.03 | 1248.54 | 778.49 | 0.00 | 0.00 |
March | 2136.66 | 1579.37 | 1616.02 | 780.61 | 835.41 | 0.00 | 0.00 |
April | 1915.60 | 1308.75 | 1350.23 | 514.85 | 835.38 | 0.00 | 0.00 |
May | 1090.17 | 1164.44 | 961.47 | 118.32 | 843.15 | 0.00 | 0.00 |
June | 956.29 | 916.97 | 843.47 | 50.92 | 792.54 | 0.00 | 0.00 |
July | 1201.95 | 796.76 | 893.46 | 100.58 | 792.89 | 0.00 | 0.00 |
August | 1800.93 | 837.43 | 1147.83 | 362.06 | 785.77 | 0.00 | 0.00 |
September | 2522.42 | 997.23 | 1597.19 | 809.35 | 787.85 | 0.00 | 0.00 |
October | 3216.54 | 1088.22 | 2031.25 | 1357.95 | 673.31 | 0.00 | 0.00 |
November | 3552.23 | 1519.56 | 2468.78 | 1742.92 | 725.86 | 0.00 | 0.00 |
December | 3995.09 | 1668.92 | 2755.30 | 2097.14 | 658.16 | 0.00 | 0.00 |
Annual Sum or Average | 2403.27 | 1250.85 | 1687.85 | 921.82 | 766.03 | 0.00 | 0.00 |
Minimum of Months | 956.29 | 796.76 | 843.47 | 50.92 | 658.16 | 0.00 | 0.00 |
Maximum of Months | 3995.09 | 1668.92 | 2755.30 | 2097.14 | 843.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 788.86 | 1217.30 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 888.34 | 1154.41 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1028.43 | 1192.55 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1646.56 | 986.35 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1596.74 | 825.21 | 1238.79 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1793.50 | 679.62 | 1312.36 | 656.16 | 656.21 | 0.00 | 0.00 |
July | 2010.30 | 607.77 | 1389.24 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1906.13 | 646.77 | 1303.38 | 706.38 | 597.00 | 0.00 | 0.00 |
September | 1594.33 | 708.72 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1230.50 | 816.95 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 923.65 | 1182.15 | 770.59 | 403.07 | 367.52 | 0.00 | 0.00 |
December | 794.84 | 1342.30 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1352.45 | 945.60 | 1026.46 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 788.86 | 607.77 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2010.30 | 1342.30 | 1389.24 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.69 | 1601.83 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 265.32 | 1455.51 | 490.59 | 0.00 | 490.59 | 0.00 | 0.00 |
March | 393.25 | 1491.36 | 601.18 | 0.00 | 601.18 | 0.00 | 0.00 |
April | 562.25 | 1184.98 | 692.63 | 2.67 | 689.96 | 0.00 | 0.00 |
May | 714.00 | 1035.86 | 832.32 | 38.76 | 793.56 | 0.00 | 0.00 |
June | 921.67 | 821.16 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
July | 982.96 | 731.03 | 839.73 | 70.38 | 769.35 | 0.00 | 0.00 |
August | 790.27 | 765.47 | 697.37 | 13.96 | 683.41 | 0.00 | 0.00 |
September | 608.77 | 924.38 | 590.25 | 0.09 | 590.16 | 0.00 | 0.00 |
October | 533.85 | 1027.36 | 468.21 | 0.00 | 468.21 | 0.00 | 0.00 |
November | 258.41 | 1469.52 | 423.93 | 0.00 | 423.93 | 0.00 | 0.00 |
December | 201.52 | 1614.59 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 539.61 | 1175.47 | 606.97 | 17.81 | 589.16 | 0.00 | 0.00 |
Minimum of Months | 201.52 | 731.03 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 982.96 | 1614.59 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 827.22 | 1000.17 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 814.87 | 913.06 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1036.12 | 935.20 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1516.99 | 771.05 | 1151.37 | 577.43 | 573.93 | 0.00 | 0.00 |
May | 1371.78 | 701.78 | 1086.56 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1467.02 | 563.01 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1799.54 | 508.64 | 1223.49 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1802.70 | 518.11 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1238.07 | 598.32 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1121.02 | 653.74 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 835.98 | 919.96 | 709.90 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 798.91 | 1000.55 | 677.23 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1222.01 | 756.16 | 929.57 | 451.41 | 478.15 | 0.00 | 0.00 |
Minimum of Months | 798.91 | 508.64 | 677.23 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1802.70 | 1000.55 | 1223.49 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3707.39 | 1609.62 | 2579.17 | 1891.94 | 687.23 | 0.00 | 0.00 |
February | 2721.70 | 1456.15 | 2027.09 | 1248.58 | 778.51 | 0.00 | 0.00 |
March | 2135.47 | 1512.38 | 1616.06 | 780.64 | 835.43 | 0.00 | 0.00 |
April | 1915.65 | 1258.68 | 1350.26 | 514.87 | 835.39 | 0.00 | 0.00 |
May | 1092.24 | 1127.02 | 961.49 | 118.32 | 843.17 | 0.00 | 0.00 |
June | 964.53 | 880.38 | 843.48 | 50.93 | 792.56 | 0.00 | 0.00 |
July | 1210.10 | 779.21 | 893.48 | 100.58 | 792.90 | 0.00 | 0.00 |
August | 1801.14 | 824.65 | 1147.85 | 362.07 | 785.78 | 0.00 | 0.00 |
September | 2504.74 | 979.57 | 1597.24 | 809.38 | 787.86 | 0.00 | 0.00 |
October | 3197.16 | 1067.60 | 2031.31 | 1357.99 | 673.32 | 0.00 | 0.00 |
November | 3533.19 | 1478.04 | 2468.85 | 1742.97 | 725.88 | 0.00 | 0.00 |
December | 3981.25 | 1615.98 | 2755.38 | 2097.20 | 658.18 | 0.00 | 0.00 |
Annual Sum or Average | 2396.21 | 1214.53 | 1687.89 | 921.85 | 766.04 | 0.00 | 0.00 |
Minimum of Months | 964.53 | 779.21 | 843.48 | 50.93 | 658.18 | 0.00 | 0.00 |
Maximum of Months | 3981.25 | 1615.98 | 2755.38 | 2097.20 | 843.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 824.29 | 1075.84 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 931.78 | 981.52 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1082.03 | 1003.46 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1693.59 | 847.84 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1611.53 | 761.26 | 1238.78 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1812.00 | 608.63 | 1312.36 | 656.15 | 656.20 | 0.00 | 0.00 |
July | 2035.50 | 554.70 | 1389.23 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1938.39 | 573.86 | 1303.37 | 706.37 | 597.00 | 0.00 | 0.00 |
September | 1603.57 | 648.88 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1261.26 | 712.84 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 972.12 | 991.41 | 770.58 | 403.07 | 367.51 | 0.00 | 0.00 |
December | 855.78 | 1092.50 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1387.40 | 820.26 | 1026.45 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 824.29 | 554.70 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2035.50 | 1092.50 | 1389.23 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.57 | 1415.18 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 317.01 | 1283.82 | 490.59 | 0.00 | 490.59 | 0.00 | 0.00 |
March | 442.04 | 1348.47 | 601.18 | 0.00 | 601.18 | 0.00 | 0.00 |
April | 589.49 | 1099.59 | 692.63 | 2.67 | 689.96 | 0.00 | 0.00 |
May | 745.76 | 967.77 | 832.32 | 38.76 | 793.56 | 0.00 | 0.00 |
June | 926.12 | 784.42 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
July | 975.15 | 709.74 | 839.73 | 70.38 | 769.35 | 0.00 | 0.00 |
August | 787.27 | 737.10 | 697.37 | 13.96 | 683.41 | 0.00 | 0.00 |
September | 619.53 | 868.55 | 590.25 | 0.09 | 590.16 | 0.00 | 0.00 |
October | 556.31 | 949.14 | 468.21 | 0.00 | 468.21 | 0.00 | 0.00 |
November | 307.64 | 1306.96 | 423.93 | 0.00 | 423.93 | 0.00 | 0.00 |
December | 253.72 | 1423.81 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 567.78 | 1073.48 | 606.97 | 17.81 | 589.16 | 0.00 | 0.00 |
Minimum of Months | 253.72 | 709.74 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 975.15 | 1423.81 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 868.50 | 904.53 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 847.92 | 825.62 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1066.71 | 865.45 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1528.01 | 733.36 | 1151.37 | 577.43 | 573.93 | 0.00 | 0.00 |
May | 1384.49 | 668.16 | 1086.56 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1465.00 | 547.46 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1788.53 | 503.37 | 1223.49 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1794.03 | 509.93 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1239.43 | 574.31 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1132.13 | 618.63 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 870.50 | 839.19 | 709.90 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 840.14 | 905.99 | 677.23 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1238.19 | 707.41 | 929.57 | 451.41 | 478.15 | 0.00 | 0.00 |
Minimum of Months | 840.14 | 503.37 | 677.23 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1794.03 | 905.99 | 1223.49 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3754.25 | 1470.31 | 2579.17 | 1891.94 | 687.23 | 0.00 | 0.00 |
February | 2764.26 | 1319.10 | 2027.09 | 1248.58 | 778.51 | 0.00 | 0.00 |
March | 2175.53 | 1390.27 | 1616.06 | 780.64 | 835.43 | 0.00 | 0.00 |
April | 1931.99 | 1184.82 | 1350.26 | 514.87 | 835.39 | 0.00 | 0.00 |
May | 1114.26 | 1055.21 | 961.49 | 118.32 | 843.17 | 0.00 | 0.00 |
June | 969.79 | 841.92 | 843.48 | 50.93 | 792.56 | 0.00 | 0.00 |
July | 1202.78 | 759.54 | 893.48 | 100.58 | 792.90 | 0.00 | 0.00 |
August | 1792.86 | 801.39 | 1147.85 | 362.07 | 785.78 | 0.00 | 0.00 |
September | 2503.50 | 936.55 | 1597.24 | 809.38 | 787.86 | 0.00 | 0.00 |
October | 3208.53 | 1011.84 | 2031.31 | 1357.99 | 673.32 | 0.00 | 0.00 |
November | 3568.92 | 1362.97 | 2468.85 | 1742.97 | 725.88 | 0.00 | 0.00 |
December | 4026.71 | 1482.97 | 2755.38 | 2097.20 | 658.18 | 0.00 | 0.00 |
Annual Sum or Average | 2416.84 | 1133.81 | 1687.89 | 921.85 | 766.04 | 0.00 | 0.00 |
Minimum of Months | 969.79 | 759.54 | 843.48 | 50.93 | 658.18 | 0.00 | 0.00 |
Maximum of Months | 4026.71 | 1482.97 | 2755.38 | 2097.20 | 843.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 847.91 | 980.26 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 953.83 | 894.63 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1102.78 | 928.93 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1700.38 | 803.24 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1618.97 | 721.51 | 1238.78 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1807.55 | 587.39 | 1312.36 | 656.15 | 656.20 | 0.00 | 0.00 |
July | 2023.79 | 543.69 | 1389.23 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1929.07 | 559.67 | 1303.37 | 706.37 | 597.00 | 0.00 | 0.00 |
September | 1603.35 | 621.13 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1269.03 | 672.74 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 992.49 | 909.79 | 770.58 | 403.07 | 367.51 | 0.00 | 0.00 |
December | 878.81 | 995.88 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1396.17 | 767.61 | 1026.45 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 847.91 | 543.69 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2023.79 | 995.88 | 1389.23 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.485329E+09 | 0.477500E+10 | 0.104677E+10 | 0.00 | 0.104677E+10 | 0.00 | 0.00 |
February | 0.540971E+09 | 0.394154E+10 | 0.118681E+10 | 0.00 | 0.118681E+10 | 0.00 | 0.00 |
March | 0.933917E+09 | 0.443394E+10 | 0.161017E+10 | 0.00 | 0.161017E+10 | 0.00 | 0.00 |
April | 0.135130E+10 | 0.335520E+10 | 0.179527E+10 | 6909602.89 | 0.178836E+10 | 0.00 | 0.00 |
May | 0.183916E+10 | 0.293576E+10 | 0.222924E+10 | 0.103804E+09 | 0.212544E+10 | 0.00 | 0.00 |
June | 0.235409E+10 | 0.224189E+10 | 0.229875E+10 | 0.224738E+09 | 0.207401E+10 | 0.00 | 0.00 |
July | 0.258762E+10 | 0.202752E+10 | 0.224911E+10 | 0.188510E+09 | 0.206060E+10 | 0.00 | 0.00 |
August | 0.205750E+10 | 0.214629E+10 | 0.186781E+10 | 37400472.82 | 0.183041E+10 | 0.00 | 0.00 |
September | 0.153584E+10 | 0.254757E+10 | 0.152991E+10 | 239793.28 | 0.152967E+10 | 0.00 | 0.00 |
October | 0.135462E+10 | 0.298643E+10 | 0.125403E+10 | 0.00 | 0.125403E+10 | 0.00 | 0.00 |
November | 0.561410E+09 | 0.424179E+10 | 0.109880E+10 | 0.00 | 0.109880E+10 | 0.00 | 0.00 |
December | 0.399990E+09 | 0.491065E+10 | 0.974451E+09 | 0.00 | 0.974451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.160017E+11 | 0.405436E+11 | 0.191411E+11 | 0.561602E+09 | 0.185795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399990E+09 | 0.202752E+10 | 0.974451E+09 | 0.00 | 0.974451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.258762E+10 | 0.491065E+10 | 0.229875E+10 | 0.224738E+09 | 0.212544E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214882E+10 | 0.290735E+10 | 0.188241E+10 | 0.100676E+10 | 0.875651E+09 | 0.00 | 0.00 |
February | 0.192404E+10 | 0.239474E+10 | 0.179358E+10 | 0.821652E+09 | 0.971925E+09 | 0.00 | 0.00 |
March | 0.273195E+10 | 0.267438E+10 | 0.241210E+10 | 0.107470E+10 | 0.133740E+10 | 0.00 | 0.00 |
April | 0.393791E+10 | 0.206181E+10 | 0.298436E+10 | 0.149672E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.367298E+10 | 0.195299E+10 | 0.291027E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.381789E+10 | 0.149902E+10 | 0.279885E+10 | 0.121437E+10 | 0.158448E+10 | 0.00 | 0.00 |
July | 0.486069E+10 | 0.134006E+10 | 0.327702E+10 | 0.162844E+10 | 0.164858E+10 | 0.00 | 0.00 |
August | 0.486770E+10 | 0.135596E+10 | 0.323632E+10 | 0.171902E+10 | 0.151730E+10 | 0.00 | 0.00 |
September | 0.321160E+10 | 0.161220E+10 | 0.228029E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.299306E+10 | 0.183282E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.211741E+10 | 0.255437E+10 | 0.184007E+10 | 0.934834E+09 | 0.905241E+09 | 0.00 | 0.00 |
December | 0.206877E+10 | 0.289986E+10 | 0.181391E+10 | 0.100783E+10 | 0.806083E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383528E+11 | 0.250855E+11 | 0.293149E+11 | 0.142358E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192404E+10 | 0.134006E+10 | 0.179358E+10 | 0.821652E+09 | 0.806083E+09 | 0.00 | 0.00 |
Maximum of Months | 0.486770E+10 | 0.290735E+10 | 0.327702E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.997528E+10 | 0.439242E+10 | 0.690784E+10 | 0.506721E+10 | 0.184063E+10 | 0.00 | 0.00 |
February | 0.662340E+10 | 0.365115E+10 | 0.490379E+10 | 0.302047E+10 | 0.188332E+10 | 0.00 | 0.00 |
March | 0.572283E+10 | 0.423019E+10 | 0.432835E+10 | 0.209078E+10 | 0.223756E+10 | 0.00 | 0.00 |
April | 0.496522E+10 | 0.339228E+10 | 0.349979E+10 | 0.133449E+10 | 0.216530E+10 | 0.00 | 0.00 |
May | 0.291992E+10 | 0.311885E+10 | 0.257520E+10 | 0.316910E+09 | 0.225829E+10 | 0.00 | 0.00 |
June | 0.247871E+10 | 0.237680E+10 | 0.218627E+10 | 0.131997E+09 | 0.205427E+10 | 0.00 | 0.00 |
July | 0.321930E+10 | 0.213403E+10 | 0.239305E+10 | 0.269385E+09 | 0.212367E+10 | 0.00 | 0.00 |
August | 0.482361E+10 | 0.224297E+10 | 0.307434E+10 | 0.969733E+09 | 0.210461E+10 | 0.00 | 0.00 |
September | 0.653812E+10 | 0.258481E+10 | 0.413993E+10 | 0.209783E+10 | 0.204210E+10 | 0.00 | 0.00 |
October | 0.861519E+10 | 0.291469E+10 | 0.544051E+10 | 0.363712E+10 | 0.180339E+10 | 0.00 | 0.00 |
November | 0.920738E+10 | 0.393870E+10 | 0.639908E+10 | 0.451764E+10 | 0.188144E+10 | 0.00 | 0.00 |
December | 0.107004E+11 | 0.447003E+10 | 0.737979E+10 | 0.561697E+10 | 0.176282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.757894E+11 | 0.394469E+11 | 0.532279E+11 | 0.290705E+11 | 0.241574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247871E+10 | 0.213403E+10 | 0.218627E+10 | 0.131997E+09 | 0.176282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107004E+11 | 0.447003E+10 | 0.737979E+10 | 0.561697E+10 | 0.225829E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211289E+10 | 0.326041E+10 | 0.179172E+10 | 0.903664E+09 | 0.888058E+09 | 0.00 | 0.00 |
February | 0.214908E+10 | 0.279275E+10 | 0.193067E+10 | 0.891289E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.275455E+10 | 0.319412E+10 | 0.245018E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.426789E+10 | 0.255661E+10 | 0.326875E+10 | 0.170204E+10 | 0.156672E+10 | 0.00 | 0.00 |
May | 0.427671E+10 | 0.221024E+10 | 0.331797E+10 | 0.153257E+10 | 0.178541E+10 | 0.00 | 0.00 |
June | 0.464875E+10 | 0.176157E+10 | 0.340164E+10 | 0.170076E+10 | 0.170089E+10 | 0.00 | 0.00 |
July | 0.538440E+10 | 0.162786E+10 | 0.372094E+10 | 0.199104E+10 | 0.172990E+10 | 0.00 | 0.00 |
August | 0.510538E+10 | 0.173230E+10 | 0.349097E+10 | 0.189196E+10 | 0.159901E+10 | 0.00 | 0.00 |
September | 0.413250E+10 | 0.183701E+10 | 0.289250E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.329578E+10 | 0.218811E+10 | 0.228489E+10 | 0.124745E+10 | 0.103744E+10 | 0.00 | 0.00 |
November | 0.239411E+10 | 0.306414E+10 | 0.199736E+10 | 0.104476E+10 | 0.952599E+09 | 0.00 | 0.00 |
December | 0.212891E+10 | 0.359522E+10 | 0.182281E+10 | 0.977671E+09 | 0.845141E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.426510E+11 | 0.298203E+11 | 0.323704E+11 | 0.165149E+11 | 0.158555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.211289E+10 | 0.162786E+10 | 0.179172E+10 | 0.891289E+09 | 0.845141E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538440E+10 | 0.359522E+10 | 0.372094E+10 | 0.199104E+10 | 0.178541E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.596445E+09 | 0.429034E+10 | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.00 | 0.00 |
February | 0.641858E+09 | 0.352118E+10 | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.00 | 0.00 |
March | 0.105329E+10 | 0.399445E+10 | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.00 | 0.00 |
April | 0.145736E+10 | 0.307147E+10 | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.00 | 0.00 |
May | 0.191239E+10 | 0.277444E+10 | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.00 | 0.00 |
June | 0.238897E+10 | 0.212846E+10 | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.00 | 0.00 |
July | 0.263276E+10 | 0.195800E+10 | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.00 | 0.00 |
August | 0.211666E+10 | 0.205022E+10 | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.00 | 0.00 |
September | 0.157794E+10 | 0.239598E+10 | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.00 | 0.00 |
October | 0.142985E+10 | 0.275168E+10 | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.00 | 0.00 |
November | 0.669811E+09 | 0.380900E+10 | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
December | 0.539762E+09 | 0.432451E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170171E+11 | 0.370697E+11 | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.539762E+09 | 0.195800E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263276E+10 | 0.432451E+10 | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.221562E+10 | 0.267886E+10 | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.00 | 0.00 |
February | 0.197134E+10 | 0.220887E+10 | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.00 | 0.00 |
March | 0.277514E+10 | 0.250485E+10 | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.00 | 0.00 |
April | 0.393203E+10 | 0.199857E+10 | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.367418E+10 | 0.187964E+10 | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.380252E+10 | 0.145932E+10 | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.00 | 0.00 |
July | 0.481989E+10 | 0.136234E+10 | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.00 | 0.00 |
August | 0.482835E+10 | 0.138770E+10 | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.00 | 0.00 |
September | 0.320909E+10 | 0.155085E+10 | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.300255E+10 | 0.175099E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.216686E+10 | 0.238454E+10 | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.00 | 0.00 |
December | 0.213981E+10 | 0.267986E+10 | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.385374E+11 | 0.238464E+11 | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.197134E+10 | 0.136234E+10 | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.00 | 0.00 |
Maximum of Months | 0.482835E+10 | 0.267986E+10 | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.992988E+10 | 0.431121E+10 | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.00 | 0.00 |
February | 0.658434E+10 | 0.352271E+10 | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.00 | 0.00 |
March | 0.571964E+10 | 0.405077E+10 | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.00 | 0.00 |
April | 0.496536E+10 | 0.326249E+10 | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.00 | 0.00 |
May | 0.292547E+10 | 0.301860E+10 | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.00 | 0.00 |
June | 0.250007E+10 | 0.228193E+10 | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.00 | 0.00 |
July | 0.324112E+10 | 0.208703E+10 | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.00 | 0.00 |
August | 0.482417E+10 | 0.220873E+10 | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.00 | 0.00 |
September | 0.649230E+10 | 0.253905E+10 | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.00 | 0.00 |
October | 0.856328E+10 | 0.285947E+10 | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.00 | 0.00 |
November | 0.915803E+10 | 0.383107E+10 | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.00 | 0.00 |
December | 0.106634E+11 | 0.432823E+10 | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.755670E+11 | 0.383013E+11 | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250007E+10 | 0.208703E+10 | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106634E+11 | 0.432823E+10 | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220777E+10 | 0.288153E+10 | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.00 | 0.00 |
February | 0.225417E+10 | 0.237450E+10 | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.289812E+10 | 0.268766E+10 | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.438978E+10 | 0.219761E+10 | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.00 | 0.00 |
May | 0.431633E+10 | 0.203896E+10 | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.00 | 0.00 |
June | 0.469671E+10 | 0.157758E+10 | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.00 | 0.00 |
July | 0.545187E+10 | 0.148570E+10 | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.00 | 0.00 |
August | 0.519177E+10 | 0.153704E+10 | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.00 | 0.00 |
September | 0.415646E+10 | 0.168191E+10 | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.337816E+10 | 0.190927E+10 | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.00 | 0.00 |
November | 0.251973E+10 | 0.256974E+10 | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.00 | 0.00 |
December | 0.229212E+10 | 0.292616E+10 | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.437530E+11 | 0.258677E+11 | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220777E+10 | 0.148570E+10 | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545187E+10 | 0.292616E+10 | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.735419E+09 | 0.379041E+10 | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.00 | 0.00 |
February | 0.766900E+09 | 0.310583E+10 | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.00 | 0.00 |
March | 0.118397E+10 | 0.361175E+10 | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.00 | 0.00 |
April | 0.152795E+10 | 0.285013E+10 | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.00 | 0.00 |
May | 0.199744E+10 | 0.259207E+10 | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.00 | 0.00 |
June | 0.240050E+10 | 0.203321E+10 | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.00 | 0.00 |
July | 0.261183E+10 | 0.190096E+10 | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.00 | 0.00 |
August | 0.210863E+10 | 0.197424E+10 | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.00 | 0.00 |
September | 0.160583E+10 | 0.225128E+10 | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.00 | 0.00 |
October | 0.149001E+10 | 0.254217E+10 | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.00 | 0.00 |
November | 0.797410E+09 | 0.338764E+10 | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
December | 0.679569E+09 | 0.381354E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179054E+11 | 0.338532E+11 | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.679569E+09 | 0.190096E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261183E+10 | 0.381354E+10 | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232620E+10 | 0.242269E+10 | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.00 | 0.00 |
February | 0.205128E+10 | 0.199734E+10 | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.00 | 0.00 |
March | 0.285707E+10 | 0.231801E+10 | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.00 | 0.00 |
April | 0.396060E+10 | 0.190087E+10 | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.370823E+10 | 0.178961E+10 | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.379729E+10 | 0.141901E+10 | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.00 | 0.00 |
July | 0.479039E+10 | 0.134822E+10 | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.00 | 0.00 |
August | 0.480514E+10 | 0.136578E+10 | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.00 | 0.00 |
September | 0.321261E+10 | 0.148861E+10 | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.303230E+10 | 0.165693E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.225634E+10 | 0.217519E+10 | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.00 | 0.00 |
December | 0.225023E+10 | 0.242660E+10 | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.390477E+11 | 0.223089E+11 | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205128E+10 | 0.134822E+10 | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480514E+10 | 0.242660E+10 | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100554E+11 | 0.393808E+10 | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.00 | 0.00 |
February | 0.668729E+10 | 0.319118E+10 | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.00 | 0.00 |
March | 0.582695E+10 | 0.372371E+10 | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.00 | 0.00 |
April | 0.500771E+10 | 0.307104E+10 | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.00 | 0.00 |
May | 0.298445E+10 | 0.282629E+10 | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.00 | 0.00 |
June | 0.251369E+10 | 0.218226E+10 | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.00 | 0.00 |
July | 0.322153E+10 | 0.203435E+10 | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.00 | 0.00 |
August | 0.480198E+10 | 0.214644E+10 | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.00 | 0.00 |
September | 0.648907E+10 | 0.242753E+10 | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.00 | 0.00 |
October | 0.859372E+10 | 0.271012E+10 | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.00 | 0.00 |
November | 0.925064E+10 | 0.353281E+10 | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.00 | 0.00 |
December | 0.107851E+11 | 0.397199E+10 | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762175E+11 | 0.357558E+11 | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251369E+10 | 0.203435E+10 | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107851E+11 | 0.397199E+10 | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.227105E+10 | 0.262553E+10 | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.00 | 0.00 |
February | 0.230751E+10 | 0.216430E+10 | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.295370E+10 | 0.248804E+10 | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.440737E+10 | 0.208199E+10 | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.00 | 0.00 |
May | 0.433624E+10 | 0.193250E+10 | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.00 | 0.00 |
June | 0.468517E+10 | 0.152252E+10 | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.00 | 0.00 |
July | 0.542052E+10 | 0.145621E+10 | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.00 | 0.00 |
August | 0.516683E+10 | 0.149901E+10 | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.00 | 0.00 |
September | 0.415588E+10 | 0.160997E+10 | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.339896E+10 | 0.180186E+10 | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.00 | 0.00 |
November | 0.257253E+10 | 0.235819E+10 | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.00 | 0.00 |
December | 0.235382E+10 | 0.266737E+10 | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.440296E+11 | 0.242075E+11 | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.227105E+10 | 0.145621E+10 | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.542052E+10 | 0.266737E+10 | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340789E+11 | -0.330571E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102182E+10 | 58.98 | 0.00 | 0.00 |
February | 0.309987E+11 | -0.300737E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925070694.1 | 58.98 | 0.00 | 0.00 |
March | 0.360195E+11 | -0.349929E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102663E+10 | 58.97 | 0.00 | 0.00 |
April | 0.320555E+11 | -0.310658E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989728801.4 | 58.96 | 0.00 | 0.00 |
May | 0.333498E+11 | -0.323248E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102499E+10 | 58.98 | 0.00 | 0.00 |
June | 0.323035E+11 | -0.313106E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992892425.9 | 58.97 | 0.00 | 0.00 |
July | 0.303458E+11 | -0.293259E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101992E+10 | 58.97 | 0.00 | 0.00 |
August | 0.330865E+11 | -0.320617E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102475E+10 | 58.99 | 0.00 | 0.00 |
September | 0.304275E+11 | -0.294386E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988963504.8 | 58.97 | 0.00 | 0.00 |
October | 0.320807E+11 | -0.310608E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101988E+10 | 58.98 | 0.00 | 0.00 |
November | 0.322667E+11 | -0.312800E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986709981.4 | 58.96 | 0.00 | 0.00 |
December | 0.328584E+11 | -0.318385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101982E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.389872E+12 | -0.377830E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120412E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.303458E+11 | -0.349929E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102663E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360195E+11 | -0.293259E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925070694.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.236170E+10 | 30189.53 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100927E+10 | 17149.05 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155746E+10 | 23597.14 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42037811.24 | 16693.05 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130064E+09 | 7151.61 | 10-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12770830.23 | 4735.55 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112780E+09 | 7972.77 | 18-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.924681E+09 | 19712.26 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.236170E+10 | 30189.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1547278.15 | 1012.67 | 30-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1547278.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1547278.15 | 1012.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 861371.69 | 466.20 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 861371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 861371.69 | 466.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535513E+11 | 290645.89 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400529E+11 | 273281.17 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602343E+11 | 284778.32 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180681E+11 | 252737.87 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119722E+11 | 139284.62 | 10-MAY-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111014E+10 | 105098.13 | 12-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.883495E+09 | 76184.26 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355059E+10 | 183445.14 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242412E+11 | 217576.82 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449326E+11 | 285018.19 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602343E+11 | 290645.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161956E+10 | 131344.58 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316158E+09 | 46631.51 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878613E+09 | 132095.76 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89860357.30 | 48607.91 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102321E+09 | 80255.55 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587521E+09 | 131871.52 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161956E+10 | 132095.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129360E+10 | 126758.45 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840316E+09 | 41887.97 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103334E+10 | 129248.48 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71898701.48 | 52092.61 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1285252.35 | 1761.16 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131258E+09 | 37094.62 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695135E+09 | 121704.91 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129360E+10 | 129248.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389148E+09 | 163421.85 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117424E+09 | 14206.59 | 28-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731046E+09 | 170951.43 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103597E+09 | 24049.13 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90651172.47 | 89117.58 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.731046E+09 | 170951.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137226E+10 | 121851.86 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490172E+09 | 19446.02 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796281E+09 | 105077.47 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117616E+09 | 21957.68 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5984305.88 | 5404.46 | 13-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63533700.10 | 11964.88 | 24-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.514095E+09 | 69751.16 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137226E+10 | 121851.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.675425E+10 | 31073.07 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540639E+10 | 28689.15 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.854645E+10 | 30390.18 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239442E+10 | 26533.27 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151706E+10 | 14627.20 | 10-MAY-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.200666E+09 | 11040.24 | 12-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116948.42 | 194.91 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12978636.37 | 3830.82 | 28-AUG-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174352E+09 | 10439.96 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480800E+09 | 19377.46 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328819E+10 | 22843.63 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593839E+10 | 30415.67 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 116948.42 | 194.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.854645E+10 | 31073.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.429607E+09 | 76136.39 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61911724.61 | 47673.04 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1217119.93 | 856.42 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2998362.05 | 1516.44 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37320088.33 | 20528.32 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429607E+09 | 76136.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131299E+10 | 14116.58 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.838823E+09 | 14093.08 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929934E+09 | 14035.42 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142492E+09 | 13990.13 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41113556.70 | 13990.45 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85129.47 | 128.92 | 20-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87513775.28 | 13984.98 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.529179E+09 | 14039.35 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101676E+10 | 13990.98 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131299E+10 | 14116.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737039E+09 | 14153.67 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.626071E+09 | 14089.67 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.633196E+09 | 14142.93 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92677988.10 | 13491.31 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25419780.19 | 11744.29 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 751763.08 | 161.65 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2404407.82 | 982.27 | 20-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47507642.14 | 11177.86 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278901E+09 | 14094.45 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582459E+09 | 14095.33 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737039E+09 | 14153.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.553738E+09 | 18300.16 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558506E+09 | 18308.10 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757677E+09 | 18247.74 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147020E+09 | 18248.62 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100611E+09 | 18250.11 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 62339.46 | 64.91 | 13-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26148228.35 | 3957.11 | 12-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178641E+09 | 18200.02 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374496E+09 | 18208.75 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.757677E+09 | 18308.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.810358E+09 | 15373.23 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579533E+09 | 13517.41 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.610935E+09 | 15356.54 | 30-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106694E+09 | 11376.54 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57039381.10 | 10695.36 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410721.99 | 216.84 | 01-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57512830.59 | 2489.55 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333599E+09 | 13765.97 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.615494E+09 | 15351.32 | 13-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.810358E+09 | 15373.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 107.33 | 0.72 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80.47 | 0.80 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 187.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107.33 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.207122E+11 | 0.206778E+11 | 90868.20 | 18-JAN-13:10 | 90868.20 | 0.18 |
February | 0.00 | 0.00 | 0.121801E+11 | 0.121008E+11 | 87297.82 | 01-FEB-12:00 | 87297.82 | 0.15 |
March | 0.00 | 0.00 | 0.147850E+11 | 0.143362E+11 | 100180.10 | 23-MAR-14:00 | 83220.37 | 0.19 |
April | 0.00 | 0.00 | 0.333266E+11 | 0.332214E+11 | 112697.87 | 26-APR-11:00 | 103660.65 | 0.38 |
May | 0.00 | 0.00 | 0.301885E+11 | 0.300778E+11 | 82853.43 | 03-MAY-13:00 | 82853.43 | 0.41 |
June | 0.00 | 0.00 | 0.561840E+11 | 0.502566E+11 | 134915.59 | 29-JUN-13:00 | 85567.29 | 0.59 |
July | 0.00 | 0.00 | 0.104123E+12 | 0.744661E+11 | 188451.06 | 31-JUL-15:40 | 106375.55 | 0.73 |
August | 0.00 | 0.00 | 0.128606E+12 | 0.862185E+11 | 190354.86 | 07-AUG-10:40 | 108702.04 | 0.78 |
September | 0.00 | 0.00 | 0.636230E+11 | 0.522577E+11 | 152911.92 | 22-SEP-12:30 | 79638.94 | 0.55 |
October | 0.00 | 0.00 | 0.784053E+11 | 0.655185E+11 | 176946.09 | 04-OCT-05:03 | 85177.32 | 0.40 |
November | 0.00 | 0.00 | 0.253077E+11 | 0.249706E+11 | 96446.35 | 28-NOV-14:00 | 96446.35 | 0.20 |
December | 0.00 | 0.00 | 0.295185E+11 | 0.294169E+11 | 103801.22 | 05-DEC-15:00 | 103801.22 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.596959E+12 | 0.493519E+12 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.121801E+11 | 0.121008E+11 | 82853.43 | 79638.94 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.128606E+12 | 0.862185E+11 | 190354.86 | 108702.04 | 0.78 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.172506E+12 | 0.171849E+12 | 777380.88 | 18-JAN-13:10 | 777380.88 | 0.18 |
February | 0.00 | 0.00 | 0.939737E+11 | 0.931998E+11 | 741571.96 | 01-FEB-12:00 | 741571.96 | 0.15 |
March | 0.00 | 0.00 | 0.106589E+12 | 0.103675E+12 | 818431.57 | 23-MAR-14:20 | 668620.59 | 0.18 |
April | 0.00 | 0.00 | 0.237220E+12 | 0.237071E+12 | 921181.56 | 26-APR-13:00 | 921181.56 | 0.35 |
May | 0.00 | 0.00 | 0.250196E+12 | 0.249228E+12 | 745828.92 | 03-MAY-13:00 | 745828.92 | 0.39 |
June | 0.00 | 0.00 | 0.454366E+12 | 0.408591E+12 | 1169203.87 | 29-JUN-13:00 | 747597.07 | 0.55 |
July | 0.00 | 0.00 | 0.799079E+12 | 0.580492E+12 | 1549712.96 | 31-JUL-15:50 | 877079.72 | 0.60 |
August | 0.00 | 0.00 | 0.945120E+12 | 0.651876E+12 | 1575514.05 | 18-AUG-15:50 | 898014.93 | 0.63 |
September | 0.00 | 0.00 | 0.544737E+12 | 0.449783E+12 | 1365300.00 | 22-SEP-12:30 | 712745.79 | 0.53 |
October | 0.00 | 0.00 | 0.638222E+12 | 0.536457E+12 | 1682907.34 | 05-OCT-05:03 | 728786.01 | 0.37 |
November | 0.00 | 0.00 | 0.183258E+12 | 0.181383E+12 | 746291.43 | 28-NOV-14:00 | 746291.43 | 0.20 |
December | 0.00 | 0.00 | 0.207585E+12 | 0.206864E+12 | 788584.41 | 05-DEC-15:00 | 788584.41 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.463285E+13 | 0.387047E+13 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.939737E+11 | 0.931998E+11 | 741571.96 | 668620.59 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.945120E+12 | 0.651876E+12 | 1682907.34 | 921181.56 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131388E+11 | 0.131388E+11 | 75255.74 | 18-JAN-13:30 | 75255.74 | 0.16 |
February | 0.00 | 0.00 | 0.740741E+10 | 0.734068E+10 | 68162.52 | 01-FEB-12:00 | 68162.52 | 0.14 |
March | 0.00 | 0.00 | 0.918160E+10 | 0.904819E+10 | 80375.68 | 23-MAR-15:00 | 66249.16 | 0.16 |
April | 0.00 | 0.00 | 0.233213E+11 | 0.233150E+11 | 110117.24 | 26-APR-14:00 | 110117.24 | 0.33 |
May | 0.00 | 0.00 | 0.245790E+11 | 0.245021E+11 | 84671.26 | 03-MAY-13:00 | 84671.26 | 0.37 |
June | 0.00 | 0.00 | 0.472310E+11 | 0.422587E+11 | 132681.07 | 29-JUN-13:00 | 84348.16 | 0.54 |
July | 0.00 | 0.00 | 0.858566E+11 | 0.623418E+11 | 195991.94 | 31-JUL-15:10 | 116270.65 | 0.58 |
August | 0.00 | 0.00 | 0.100159E+12 | 0.687529E+11 | 193425.62 | 18-AUG-15:30 | 112913.97 | 0.60 |
September | 0.00 | 0.00 | 0.536031E+11 | 0.446671E+11 | 155159.47 | 29-SEP-13:00 | 155159.47 | 0.49 |
October | 0.00 | 0.00 | 0.612202E+11 | 0.516692E+11 | 156844.69 | 05-OCT-05:03 | 67857.81 | 0.35 |
November | 0.00 | 0.00 | 0.141092E+11 | 0.141032E+11 | 72217.30 | 28-NOV-14:00 | 72217.30 | 0.18 |
December | 0.00 | 0.00 | 0.160405E+11 | 0.160405E+11 | 80413.59 | 05-DEC-15:00 | 80413.59 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.455848E+12 | 0.377178E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.740741E+10 | 0.734068E+10 | 68162.52 | 66249.16 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.100159E+12 | 0.687529E+11 | 195991.94 | 155159.47 | 0.60 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121005E+11 | 0.120595E+11 | 70283.31 | 17-JAN-14:00 | 66306.61 | 0.11 |
February | 0.00 | 0.00 | 0.537816E+10 | 0.534066E+10 | 64735.52 | 13-FEB-06:03 | 29000.37 | 0.08 |
March | 0.00 | 0.00 | 0.624411E+10 | 0.619945E+10 | 47834.86 | 23-MAR-14:00 | 47834.86 | 0.10 |
April | 0.00 | 0.00 | 0.160624E+11 | 0.159714E+11 | 63932.99 | 27-APR-05:03 | 29302.97 | 0.25 |
May | 0.00 | 0.00 | 0.156200E+11 | 0.155462E+11 | 60871.43 | 03-MAY-05:03 | 25235.80 | 0.26 |
June | 0.00 | 0.00 | 0.285060E+11 | 0.271747E+11 | 84518.98 | 30-JUN-05:03 | 36063.99 | 0.38 |
July | 0.00 | 0.00 | 0.484688E+11 | 0.411180E+11 | 105925.76 | 31-JUL-09:10 | 63943.32 | 0.44 |
August | 0.00 | 0.00 | 0.562466E+11 | 0.457965E+11 | 121803.78 | 07-AUG-09:50 | 67065.76 | 0.49 |
September | 0.00 | 0.00 | 0.340179E+11 | 0.301664E+11 | 97954.20 | 22-SEP-10:00 | 40906.59 | 0.38 |
October | 0.00 | 0.00 | 0.440538E+11 | 0.383321E+11 | 110840.74 | 05-OCT-04:03 | 51106.65 | 0.28 |
November | 0.00 | 0.00 | 0.134614E+11 | 0.134305E+11 | 61339.83 | 10-NOV-04:02 | 28941.60 | 0.13 |
December | 0.00 | 0.00 | 0.166741E+11 | 0.166620E+11 | 70463.54 | 25-DEC-15:10 | 70463.54 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.296834E+12 | 0.267797E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.537816E+10 | 0.534066E+10 | 47834.86 | 25235.80 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.562466E+11 | 0.457965E+11 | 121803.78 | 70463.54 | 0.49 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.331040E+12 | 0.329840E+12 | 130973.02 | 17-JAN-14:50 | 125751.53 | 0.00 |
February | 0.00 | 0.00 | 0.518421E+12 | 0.516791E+12 | 220265.99 | 13-FEB-17:00 | 214222.50 | 0.00 |
March | 0.00 | 0.00 | 0.819587E+12 | 0.817356E+12 | 393891.87 | 31-MAR-24:00 | 393891.87 | 0.00 |
April | 0.00 | 0.00 | 0.103220E+13 | 0.102956E+13 | 408230.00 | 26-APR-15:00 | 401660.03 | 0.00 |
May | 0.00 | 0.00 | 0.333693E+12 | 0.330665E+12 | 211325.01 | 31-MAY-23:20 | 210927.45 | 0.00 |
June | 0.00 | 0.00 | 0.562586E+12 | 0.557048E+12 | 303012.04 | 30-JUN-24:00 | 302878.42 | 0.00 |
July | 0.00 | 0.00 | 0.829763E+12 | 0.822910E+12 | 394968.11 | 31-JUL-23:53 | 394968.11 | 0.00 |
August | 0.00 | 0.00 | 0.107393E+13 | 0.106710E+13 | 411515.09 | 18-AUG-17:00 | 401833.85 | 0.00 |
September | 0.00 | 0.00 | 0.328657E+12 | 0.323200E+12 | 211451.78 | 30-SEP-24:00 | 211451.78 | 0.00 |
October | 0.00 | 0.00 | 0.582342E+12 | 0.578820E+12 | 304835.47 | 31-OCT-24:00 | 303687.02 | 0.00 |
November | 0.00 | 0.00 | 0.796594E+12 | 0.794786E+12 | 314123.47 | 10-NOV-17:00 | 307762.88 | 0.00 |
December | 0.00 | 0.00 | 0.106628E+13 | 0.106563E+13 | 405241.38 | 29-DEC-16:30 | 405241.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.827508E+13 | 0.823370E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.328657E+12 | 0.323200E+12 | 130973.02 | 125751.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107393E+13 | 0.106710E+13 | 411515.09 | 405241.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.522427E+10 | 0.517997E+10 | 2492.25 | 18-JAN-16:10 | 2402.22 | 0.00 |
February | 0.00 | 0.00 | 0.940320E+10 | 0.933815E+10 | 4498.56 | 21-FEB-17:00 | 4339.17 | 0.00 |
March | 0.00 | 0.00 | 0.155809E+11 | 0.154876E+11 | 7559.27 | 31-MAR-24:00 | 7559.27 | 0.00 |
April | 0.00 | 0.00 | 0.202252E+11 | 0.201093E+11 | 8360.58 | 16-APR-17:30 | 8338.97 | 0.00 |
May | 0.00 | 0.00 | 0.564666E+10 | 0.553903E+10 | 3881.69 | 31-MAY-24:00 | 3862.81 | 0.00 |
June | 0.00 | 0.00 | 0.106846E+11 | 0.104797E+11 | 5913.33 | 30-JUN-24:00 | 5901.62 | 0.00 |
July | 0.00 | 0.00 | 0.162546E+11 | 0.159745E+11 | 7773.03 | 31-JUL-23:50 | 7771.66 | 0.00 |
August | 0.00 | 0.00 | 0.212940E+11 | 0.209851E+11 | 8520.65 | 17-AUG-15:50 | 8170.94 | 0.00 |
September | 0.00 | 0.00 | 0.577372E+10 | 0.557702E+10 | 4059.00 | 30-SEP-24:00 | 4059.00 | 0.00 |
October | 0.00 | 0.00 | 0.109838E+11 | 0.108509E+11 | 5893.22 | 31-OCT-24:00 | 5867.56 | 0.00 |
November | 0.00 | 0.00 | 0.152437E+11 | 0.151712E+11 | 6444.37 | 07-NOV-16:20 | 6272.32 | 0.00 |
December | 0.00 | 0.00 | 0.207071E+11 | 0.206768E+11 | 8373.67 | 25-DEC-16:10 | 8373.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157022E+12 | 0.155369E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.522427E+10 | 0.517997E+10 | 2492.25 | 2402.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212940E+11 | 0.209851E+11 | 8520.65 | 8373.67 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397351E+11 | 0.393082E+11 | 23086.00 | 18-JAN-16:20 | 22164.44 | 0.00 |
February | 0.00 | 0.00 | 0.811230E+11 | 0.804831E+11 | 42195.79 | 01-FEB-16:50 | 39992.43 | 0.00 |
March | 0.00 | 0.00 | 0.139988E+12 | 0.139060E+12 | 67764.60 | 31-MAR-23:40 | 67764.60 | 0.00 |
April | 0.00 | 0.00 | 0.188456E+12 | 0.187298E+12 | 78656.43 | 26-APR-16:00 | 76877.70 | 0.00 |
May | 0.00 | 0.00 | 0.488200E+11 | 0.477745E+11 | 35242.03 | 31-MAY-24:00 | 35008.69 | 0.00 |
June | 0.00 | 0.00 | 0.986743E+11 | 0.966553E+11 | 55934.26 | 30-JUN-24:00 | 55811.43 | 0.00 |
July | 0.00 | 0.00 | 0.153719E+12 | 0.150934E+12 | 74374.95 | 31-JUL-24:00 | 74340.15 | 0.00 |
August | 0.00 | 0.00 | 0.201986E+12 | 0.198901E+12 | 81024.64 | 17-AUG-16:00 | 77550.24 | 0.00 |
September | 0.00 | 0.00 | 0.512239E+11 | 0.493092E+11 | 38867.78 | 30-SEP-24:00 | 38867.78 | 0.00 |
October | 0.00 | 0.00 | 0.999301E+11 | 0.986202E+11 | 54548.75 | 31-OCT-24:00 | 54300.39 | 0.00 |
November | 0.00 | 0.00 | 0.137672E+12 | 0.136954E+12 | 60820.14 | 10-NOV-16:20 | 58476.31 | 0.00 |
December | 0.00 | 0.00 | 0.188085E+12 | 0.187780E+12 | 78611.87 | 07-DEC-16:10 | 76589.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142941E+13 | 0.141308E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.397351E+11 | 0.393082E+11 | 23086.00 | 22164.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201986E+12 | 0.198901E+12 | 81024.64 | 77550.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.268086E+10 | 0.263987E+10 | 2331.04 | 18-JAN-16:10 | 2243.61 | 0.00 |
February | 0.00 | 0.00 | 0.703618E+10 | 0.697325E+10 | 4241.43 | 01-FEB-16:50 | 4021.47 | 0.00 |
March | 0.00 | 0.00 | 0.129964E+11 | 0.129044E+11 | 6365.03 | 31-MAR-23:20 | 6365.03 | 0.00 |
April | 0.00 | 0.00 | 0.183270E+11 | 0.182115E+11 | 7967.24 | 26-APR-16:00 | 7789.26 | 0.00 |
May | 0.00 | 0.00 | 0.435687E+10 | 0.425376E+10 | 3231.45 | 31-MAY-23:20 | 3180.62 | 0.00 |
June | 0.00 | 0.00 | 0.963787E+10 | 0.943663E+10 | 5463.85 | 30-JUN-24:00 | 5451.01 | 0.00 |
July | 0.00 | 0.00 | 0.152898E+11 | 0.150116E+11 | 7336.91 | 31-JUL-23:57 | 7333.16 | 0.00 |
August | 0.00 | 0.00 | 0.200832E+11 | 0.197750E+11 | 8212.26 | 17-AUG-16:00 | 7864.89 | 0.00 |
September | 0.00 | 0.00 | 0.480689E+10 | 0.461736E+10 | 3823.69 | 30-SEP-24:00 | 3823.69 | 0.00 |
October | 0.00 | 0.00 | 0.949510E+10 | 0.936511E+10 | 5211.27 | 31-OCT-23:50 | 5186.42 | 0.00 |
November | 0.00 | 0.00 | 0.127562E+11 | 0.126849E+11 | 6096.57 | 10-NOV-16:20 | 5862.40 | 0.00 |
December | 0.00 | 0.00 | 0.175402E+11 | 0.175100E+11 | 7858.31 | 07-DEC-16:10 | 7656.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135006E+12 | 0.133383E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.268086E+10 | 0.263987E+10 | 2331.04 | 2243.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200832E+11 | 0.197750E+11 | 8212.26 | 7864.89 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26262.07 | 811333.50 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 20859.31 | 417537.49 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28359.09 | 817124.51 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 8157.52 | 458938.46 | 01-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5122.95 | 169544.12 | 15-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 507.53 | 124745.56 | 12-JUN-21:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.03 | 154.87 | 07-JUL-21:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 4.33 | 3491.72 | 28-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 402.70 | 93791.87 | 20-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1577.79 | 265240.19 | 12-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11196.40 | 318627.61 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 20819.63 | 520745.29 | 23-DEC-07:05 |
Annual Sum or Average | 0.00 | 10242.49 | ||||
Minimum of Months | 0.00 | 0.00 | 0.03 | 154.87 | ||
Maximum of Months | 0.00 | 0.00 | 28359.09 | 817124.51 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 146408.74 | 1328627.50 | 13-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 96234.30 | 1152935.75 | 03-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 94455.42 | 1216619.57 | 23-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 212313.15 | 1243759.71 | 12-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 221395.34 | 1253185.81 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 348152.75 | 1517911.77 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 521288.72 | 1985103.15 | 31-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 592302.03 | 2001327.07 | 18-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 385792.86 | 1790777.20 | 29-SEP-12:20 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 424332.75 | 1852748.50 | 03-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 169304.21 | 1165884.92 | 08-NOV-12:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 168168.45 | 1225054.88 | 05-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 283233.82 | 0.00 | ||||
Minimum of Months | 94455.42 | 1152935.75 | 0.00 | 0.00 | ||
Maximum of Months | 592302.03 | 2001327.07 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 95146.19 | 1327421.49 | 13-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56173.18 | 1110276.85 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57760.91 | 1210040.45 | 23-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 138219.21 | 1237860.10 | 12-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 140395.37 | 1244111.18 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 252385.29 | 1578196.13 | 30-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 415016.46 | 2189227.63 | 29-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 487379.89 | 2431179.96 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 293305.58 | 2403659.50 | 30-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 333481.04 | 2812206.03 | 05-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105699.67 | 1420182.26 | 19-NOV-12:23 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 115924.18 | 1222812.73 | 05-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 208929.77 | 0.00 | ||||
Minimum of Months | 56173.18 | 1110276.85 | 0.00 | 0.00 | ||
Maximum of Months | 487379.89 | 2812206.03 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 212913.89 | 660512.84 | 13-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 345277.26 | 869994.96 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 502179.87 | 975489.14 | 11-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 739587.98 | 1363370.23 | 26-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 232100.82 | 569275.70 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 458429.03 | 842990.15 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 742887.99 | 1234814.01 | 31-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 961780.97 | 1425758.93 | 14-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 304630.97 | 1206350.36 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 527572.46 | 1498438.32 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 539601.56 | 1140845.15 | 19-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 710954.16 | 1291884.46 | 19-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 524759.85 | 0.00 | ||||
Minimum of Months | 212913.89 | 569275.70 | 0.00 | 0.00 | ||
Maximum of Months | 961780.97 | 1498438.32 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13761.22 | 45604.66 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13850.03 | 45610.16 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14479.53 | 45388.87 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13398.11 | 44586.71 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13487.12 | 43620.80 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13496.54 | 42534.91 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12365.30 | 41693.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13385.15 | 41613.85 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12778.31 | 42289.81 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13013.81 | 43383.91 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13485.38 | 44436.83 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13306.31 | 45227.38 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 13398.09 | ||||
Minimum of Months | 0.00 | 0.00 | 12365.30 | 41613.85 | ||
Maximum of Months | 0.00 | 0.00 | 14479.53 | 45610.16 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106766.44 | 2099476.79 | 13-JAN-13:50 | 959.92 | 90861.30 | 04-JAN-06:40 |
February | 62682.99 | 1964910.99 | 01-FEB-13:20 | 664.88 | 92724.52 | 06-FEB-06:30 |
March | 66631.05 | 2148432.22 | 23-MAR-13:50 | 387.17 | 71153.54 | 31-MAR-05:40 |
April | 152771.35 | 2184802.58 | 26-APR-13:40 | 293.37 | 67152.59 | 01-APR-05:50 |
May | 152648.04 | 1976255.02 | 18-MAY-15:20 | 208.05 | 47366.38 | 24-MAY-05:30 |
June | 309385.17 | 2997583.62 | 29-JUN-13:00 | 127.57 | 29780.78 | 22-JUN-20:10 |
July | 636625.77 | 4249943.31 | 31-JUL-13:00 | 99.10 | 28108.21 | 17-JUL-06:00 |
August | 777221.25 | 4242209.77 | 17-AUG-14:10 | 106.17 | 29867.54 | 21-AUG-20:20 |
September | 393499.55 | 3903193.36 | 22-SEP-12:30 | 219.48 | 34800.05 | 15-SEP-20:00 |
October | 459594.30 | 3838963.26 | 03-OCT-13:30 | 262.75 | 52881.51 | 27-OCT-06:00 |
November | 113929.32 | 1953586.26 | 28-NOV-11:50 | 709.68 | 76819.85 | 30-NOV-06:50 |
December | 126803.10 | 1971356.46 | 18-DEC-13:10 | 833.38 | 93099.85 | 28-DEC-06:30 |
Annual Sum or Average | 282075.82 | 404.58 | ||||
Minimum of Months | 62682.99 | 1953586.26 | 99.10 | 28108.21 | ||
Maximum of Months | 777221.25 | 4249943.31 | 959.92 | 93099.85 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169526E+11 | 0.94 | 10402.93 | 01-JAN-00:20 | 1.54 |
February | 0.147321E+11 | 0.90 | 10402.93 | 01-FEB-04:03 | 1.54 |
March | 0.169401E+11 | 0.93 | 10402.93 | 01-MAR-05:03 | 1.54 |
April | 0.155451E+11 | 0.88 | 10402.93 | 01-APR-04:03 | 1.54 |
May | 0.164257E+11 | 0.90 | 10402.93 | 01-MAY-03:02 | 1.54 |
June | 0.163888E+11 | 0.93 | 10402.93 | 01-JUN-03:02 | 1.53 |
July | 0.156377E+11 | 0.86 | 10402.93 | 01-JUL-03:02 | 1.53 |
August | 0.171897E+11 | 0.94 | 10402.93 | 01-AUG-03:02 | 1.53 |
September | 0.161062E+11 | 0.91 | 10402.93 | 01-SEP-03:02 | 1.53 |
October | 0.168618E+11 | 0.93 | 10402.93 | 01-OCT-19:20 | 1.53 |
November | 0.163479E+11 | 0.93 | 10402.93 | 01-NOV-03:02 | 1.54 |
December | 0.165075E+11 | 0.91 | 10402.93 | 01-DEC-04:03 | 1.54 |
Annual Sum or Average | 0.195635E+12 | 0.91 | |||
Minimum of Months | 0.147321E+11 | 0.86 | 10402.93 | 1.53 | |
Maximum of Months | 0.171897E+11 | 0.94 | 10402.93 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.713698E+10 | 0.43 | 11455.46 | 18-JAN-15:40 | 1.28 |
February | 0.694513E+10 | 0.46 | 13534.48 | 21-FEB-15:50 | 1.42 |
March | 0.890471E+10 | 0.51 | 14241.38 | 23-MAR-15:20 | 1.46 |
April | 0.107086E+11 | 0.59 | 15891.67 | 26-APR-14:00 | 1.57 |
May | 0.836995E+10 | 0.49 | 17174.40 | 01-MAY-05:03 | 1.65 |
June | 0.100582E+11 | 0.56 | 20392.20 | 26-JUN-05:03 | 1.84 |
July | 0.118191E+11 | 0.63 | 21255.63 | 03-JUL-05:03 | 1.89 |
August | 0.140552E+11 | 0.71 | 19928.13 | 07-AUG-05:02 | 1.81 |
September | 0.921968E+10 | 0.52 | 20090.50 | 25-SEP-05:03 | 1.83 |
October | 0.968026E+10 | 0.53 | 21255.63 | 02-OCT-05:03 | 1.89 |
November | 0.900659E+10 | 0.51 | 15071.64 | 13-NOV-15:10 | 1.52 |
December | 0.895690E+10 | 0.50 | 15950.98 | 18-DEC-16:10 | 1.60 |
Annual Sum or Average | 0.114861E+12 | 0.54 | |||
Minimum of Months | 0.694513E+10 | 0.43 | 11455.46 | 1.28 | |
Maximum of Months | 0.140552E+11 | 0.71 | 21255.63 | 1.89 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495175E+11 | 0.37 | 125921.84 | 03-JAN-06:02 | 1.44 |
February | 0.456579E+11 | 0.38 | 102169.07 | 01-FEB-06:03 | 1.26 |
March | 0.532505E+11 | 0.40 | 126716.88 | 29-MAR-05:03 | 1.44 |
April | 0.619449E+11 | 0.43 | 112478.91 | 26-APR-14:30 | 1.33 |
May | 0.631051E+11 | 0.43 | 107730.73 | 01-MAY-05:03 | 1.30 |
June | 0.730499E+11 | 0.48 | 127684.93 | 24-JUN-05:02 | 1.44 |
July | 0.798750E+11 | 0.49 | 142052.47 | 01-JUL-05:03 | 1.54 |
August | 0.906323E+11 | 0.53 | 123111.28 | 18-AUG-15:00 | 1.40 |
September | 0.727225E+11 | 0.47 | 176420.89 | 30-SEP-05:02 | 1.77 |
October | 0.683322E+11 | 0.45 | 146492.31 | 02-OCT-03:02 | 1.57 |
November | 0.546350E+11 | 0.40 | 102237.00 | 24-NOV-06:02 | 1.27 |
December | 0.502046E+11 | 0.38 | 114193.81 | 13-DEC-06:03 | 1.35 |
Annual Sum or Average | 0.762927E+12 | 0.43 | |||
Minimum of Months | 0.456579E+11 | 0.37 | 102169.07 | 1.26 | |
Maximum of Months | 0.906323E+11 | 0.53 | 176420.89 | 1.77 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.380114E+10 | 0.32 | 7776.06 | 18-JAN-15:30 | 1.02 |
February | 0.354472E+10 | 0.33 | 7657.90 | 03-FEB-15:10 | 1.02 |
March | 0.423762E+10 | 0.35 | 10709.79 | 23-MAR-15:20 | 1.23 |
April | 0.548970E+10 | 0.38 | 13162.35 | 26-APR-14:30 | 1.40 |
May | 0.559796E+10 | 0.38 | 12184.51 | 03-MAY-15:20 | 1.33 |
June | 0.704032E+10 | 0.44 | 12904.06 | 30-JUN-15:50 | 1.38 |
July | 0.822852E+10 | 0.47 | 15335.72 | 31-JUL-14:40 | 1.53 |
August | 0.910614E+10 | 0.50 | 14872.01 | 18-AUG-15:00 | 1.50 |
September | 0.661569E+10 | 0.42 | 21300.62 | 30-SEP-05:02 | 1.90 |
October | 0.594331E+10 | 0.39 | 13404.12 | 17-OCT-16:00 | 1.41 |
November | 0.405523E+10 | 0.33 | 9154.85 | 01-NOV-05:03 | 1.12 |
December | 0.379781E+10 | 0.32 | 9154.85 | 06-DEC-06:03 | 1.13 |
Annual Sum or Average | 0.674582E+11 | 0.39 | |||
Minimum of Months | 0.354472E+10 | 0.32 | 7657.90 | 1.02 | |
Maximum of Months | 0.910614E+10 | 0.50 | 21300.62 | 1.90 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.957710E+11 | 1.37 | 35756.81 | 01-JAN-00:05 | 1.37 |
February | 0.865029E+11 | 1.37 | 35756.81 | 01-FEB-00:10 | 1.37 |
March | 0.957710E+11 | 1.37 | 35756.81 | 01-MAR-00:10 | 1.37 |
April | 0.926817E+11 | 1.37 | 35756.81 | 01-APR-00:10 | 1.37 |
May | 0.957710E+11 | 1.37 | 35756.81 | 01-MAY-00:10 | 1.37 |
June | 0.926817E+11 | 1.37 | 35756.81 | 01-JUN-00:10 | 1.37 |
July | 0.957710E+11 | 1.37 | 35756.81 | 01-JUL-00:10 | 1.37 |
August | 0.957710E+11 | 1.37 | 35756.81 | 01-AUG-00:03 | 1.37 |
September | 0.926817E+11 | 1.37 | 35756.81 | 01-SEP-00:03 | 1.37 |
October | 0.957710E+11 | 1.37 | 35756.81 | 01-OCT-00:10 | 1.37 |
November | 0.926817E+11 | 1.37 | 35756.81 | 01-NOV-00:10 | 1.37 |
December | 0.957710E+11 | 1.37 | 35756.81 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112763E+13 | 1.37 | |||
Minimum of Months | 0.865029E+11 | 1.37 | 35756.81 | 1.37 | |
Maximum of Months | 0.957710E+11 | 1.37 | 35756.81 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143240E+10 | 0.93 | 534.80 | 01-JAN-00:05 | 0.93 |
February | 0.129378E+10 | 0.93 | 534.80 | 01-FEB-00:10 | 0.93 |
March | 0.143240E+10 | 0.93 | 534.80 | 01-MAR-00:10 | 0.93 |
April | 0.138619E+10 | 0.93 | 534.80 | 01-APR-00:10 | 0.93 |
May | 0.143240E+10 | 0.93 | 534.80 | 01-MAY-00:10 | 0.93 |
June | 0.138619E+10 | 0.93 | 534.80 | 01-JUN-00:10 | 0.93 |
July | 0.143240E+10 | 0.93 | 534.80 | 01-JUL-00:10 | 0.93 |
August | 0.143240E+10 | 0.93 | 534.80 | 01-AUG-00:03 | 0.93 |
September | 0.138619E+10 | 0.93 | 534.80 | 01-SEP-00:03 | 0.93 |
October | 0.143240E+10 | 0.93 | 534.80 | 01-OCT-00:10 | 0.93 |
November | 0.138619E+10 | 0.93 | 534.80 | 01-NOV-00:10 | 0.93 |
December | 0.143240E+10 | 0.93 | 534.80 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168653E+11 | 0.93 | |||
Minimum of Months | 0.129378E+10 | 0.93 | 534.80 | 0.93 | |
Maximum of Months | 0.143240E+10 | 0.93 | 534.80 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136253E+11 | 0.93 | 5087.11 | 01-JAN-00:05 | 0.93 |
February | 0.123067E+11 | 0.93 | 5087.11 | 01-FEB-00:10 | 0.93 |
March | 0.136253E+11 | 0.93 | 5087.11 | 01-MAR-00:10 | 0.93 |
April | 0.131858E+11 | 0.93 | 5087.11 | 01-APR-00:20 | 0.93 |
May | 0.136253E+11 | 0.93 | 5087.11 | 01-MAY-00:24 | 0.93 |
June | 0.131858E+11 | 0.93 | 5087.11 | 01-JUN-00:10 | 0.93 |
July | 0.136253E+11 | 0.93 | 5087.11 | 01-JUL-00:10 | 0.93 |
August | 0.136253E+11 | 0.93 | 5087.11 | 01-AUG-00:03 | 0.93 |
September | 0.131858E+11 | 0.93 | 5087.11 | 01-SEP-00:03 | 0.93 |
October | 0.136253E+11 | 0.93 | 5087.11 | 01-OCT-00:10 | 0.93 |
November | 0.131858E+11 | 0.93 | 5087.11 | 01-NOV-00:10 | 0.93 |
December | 0.136253E+11 | 0.93 | 5087.11 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.160427E+12 | 0.93 | |||
Minimum of Months | 0.123067E+11 | 0.93 | 5087.11 | 0.93 | |
Maximum of Months | 0.136253E+11 | 0.93 | 5087.11 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138943E+10 | 0.93 | 518.75 | 01-JAN-00:05 | 0.93 |
February | 0.125497E+10 | 0.93 | 518.75 | 01-FEB-00:10 | 0.93 |
March | 0.138943E+10 | 0.93 | 518.75 | 01-MAR-00:10 | 0.93 |
April | 0.134461E+10 | 0.93 | 518.75 | 01-APR-00:10 | 0.93 |
May | 0.138943E+10 | 0.93 | 518.75 | 01-MAY-00:10 | 0.93 |
June | 0.134461E+10 | 0.93 | 518.75 | 01-JUN-00:10 | 0.93 |
July | 0.138943E+10 | 0.93 | 518.75 | 01-JUL-00:10 | 0.93 |
August | 0.138943E+10 | 0.93 | 518.75 | 01-AUG-00:03 | 0.93 |
September | 0.134461E+10 | 0.93 | 518.75 | 01-SEP-00:03 | 0.93 |
October | 0.138943E+10 | 0.93 | 518.75 | 01-OCT-00:10 | 0.93 |
November | 0.134461E+10 | 0.93 | 518.75 | 01-NOV-00:10 | 0.93 |
December | 0.138943E+10 | 0.93 | 518.75 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.163594E+11 | 0.93 | |||
Minimum of Months | 0.125497E+10 | 0.93 | 518.75 | 0.93 | |
Maximum of Months | 0.138943E+10 | 0.93 | 518.75 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.360341E+09 | 0.324307E+09 | 2927.27 | 02-JAN-06:01 | 2634.54 | 2634.54 | 44.09 | 5.12 |
February | 0.239797E+09 | 0.215817E+09 | 1999.53 | 09-FEB-07:10 | 1799.58 | 1799.58 | 46.04 | 2.68 |
March | 0.378368E+09 | 0.340531E+09 | 2804.14 | 29-MAR-05:03 | 2523.73 | 2523.73 | 47.02 | 4.66 |
April | 94166555.21 | 84749899.69 | 1895.37 | 01-APR-06:10 | 1705.83 | 1705.83 | 38.02 | 2.50 |
May | 60296384.15 | 54266745.73 | 782.80 | 10-MAY-21:00 | 704.52 | 704.52 | 38.01 | 0.87 |
June | 5401301.01 | 4861170.91 | 535.71 | 12-JUN-21:00 | 482.14 | 482.14 | 30.38 | 0.58 |
July | 423.10 | 380.79 | 0.71 | 07-JUL-21:00 | 0.63 | 0.63 | 30.37 | 0.00 |
August | 52490.83 | 47241.74 | 15.77 | 28-AUG-06:55 | 14.19 | 14.19 | 30.05 | 0.02 |
September | 4332003.28 | 3898802.96 | 379.02 | 20-SEP-06:10 | 341.12 | 341.12 | 26.20 | 0.40 |
October | 18773633.69 | 16896270.32 | 1108.10 | 12-OCT-06:05 | 997.29 | 997.29 | 32.66 | 1.29 |
November | 0.132699E+09 | 0.119429E+09 | 1422.38 | 30-NOV-07:10 | 1280.14 | 1280.14 | 37.84 | 1.73 |
December | 0.283827E+09 | 0.255444E+09 | 2353.30 | 13-DEC-06:03 | 2117.97 | 2117.97 | 48.26 | 3.41 |
Annual Sum or Average | 0.157805E+10 | 0.142025E+10 | ||||||
Minimum of Months | 423.10 | 380.79 | 0.71 | 0.63 | 0.63 | 26.20 | 0.00 | |
Maximum of Months | 0.378368E+09 | 0.340531E+09 | 2927.27 | 2634.54 | 2634.54 | 48.26 | 5.12 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.405178E+10 | 0.364660E+10 | 16055.86 | 13-JAN-14:00 | 14450.28 | 14450.28 | 6.89 | 73.20 |
February | 0.225834E+10 | 0.203250E+10 | 13698.83 | 21-FEB-13:10 | 12328.95 | 12328.95 | 8.05 | 41.53 |
March | 0.244436E+10 | 0.219993E+10 | 13131.34 | 23-MAR-13:50 | 11818.21 | 11818.21 | 7.08 | 36.65 |
April | 0.563821E+10 | 0.507439E+10 | 13673.84 | 12-APR-14:00 | 12306.46 | 12306.46 | 7.04 | 41.29 |
May | 0.621133E+10 | 0.559020E+10 | 14477.88 | 03-MAY-13:00 | 13030.10 | 13030.10 | 6.98 | 51.44 |
June | 0.895700E+10 | 0.806130E+10 | 14243.15 | 30-JUN-05:03 | 12818.84 | 12818.84 | 7.09 | 47.94 |
July | 0.127134E+11 | 0.114421E+11 | 15794.41 | 29-JUL-05:03 | 14214.97 | 14214.97 | 7.03 | 70.71 |
August | 0.143434E+11 | 0.129091E+11 | 16109.35 | 07-AUG-05:02 | 14498.41 | 14498.41 | 7.34 | 73.67 |
September | 0.955455E+10 | 0.859910E+10 | 18894.91 | 29-SEP-12:20 | 17005.42 | 17005.42 | 6.75 | 89.01 |
October | 0.107927E+11 | 0.971340E+10 | 18989.58 | 05-OCT-05:03 | 17090.62 | 17090.62 | 7.18 | 89.37 |
November | 0.433103E+10 | 0.389793E+10 | 14506.20 | 08-NOV-13:30 | 13055.58 | 13055.58 | 8.13 | 51.89 |
December | 0.427983E+10 | 0.385184E+10 | 13613.56 | 07-DEC-11:30 | 12252.21 | 12252.21 | 8.05 | 40.71 |
Annual Sum or Average | 0.855760E+11 | 0.770184E+11 | ||||||
Minimum of Months | 0.225834E+10 | 0.203250E+10 | 13131.34 | 11818.21 | 11818.21 | 6.75 | 36.65 | |
Maximum of Months | 0.143434E+11 | 0.129091E+11 | 18989.58 | 17090.62 | 17090.62 | 8.13 | 89.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112050E+11 | 0.100845E+11 | 12871.09 | 02-JAN-04:02 | 11583.98 | 11583.98 | 6.72 | 90.21 |
February | 0.862930E+10 | 0.776637E+10 | 12871.09 | 01-FEB-04:03 | 11583.98 | 11583.98 | 6.80 | 90.21 |
March | 0.849840E+10 | 0.764856E+10 | 12871.09 | 01-MAR-06:05 | 11583.98 | 11583.98 | 6.95 | 90.21 |
April | 0.141525E+11 | 0.127373E+11 | 12871.09 | 01-APR-05:03 | 11583.98 | 11583.98 | 6.83 | 90.21 |
May | 0.156102E+11 | 0.140492E+11 | 12871.09 | 01-MAY-00:33 | 11583.98 | 11583.98 | 6.77 | 90.21 |
June | 0.204901E+11 | 0.184411E+11 | 12871.09 | 01-JUN-05:02 | 11583.98 | 11583.98 | 7.11 | 90.21 |
July | 0.262847E+11 | 0.236562E+11 | 12871.09 | 01-JUL-03:02 | 11583.98 | 11583.98 | 7.29 | 90.21 |
August | 0.277236E+11 | 0.249512E+11 | 12871.09 | 01-AUG-00:52 | 11583.98 | 11583.98 | 6.88 | 90.21 |
September | 0.199565E+11 | 0.179609E+11 | 12871.09 | 01-SEP-01:12 | 11583.98 | 11583.98 | 6.78 | 90.21 |
October | 0.206846E+11 | 0.186162E+11 | 12871.09 | 01-OCT-06:12 | 11583.98 | 11583.98 | 6.95 | 90.21 |
November | 0.128060E+11 | 0.115254E+11 | 12871.09 | 01-NOV-03:02 | 11583.98 | 11583.98 | 7.19 | 90.21 |
December | 0.117070E+11 | 0.105363E+11 | 12871.09 | 01-DEC-06:03 | 11583.98 | 11583.98 | 6.87 | 90.21 |
Annual Sum or Average | 0.197748E+12 | 0.177973E+12 | ||||||
Minimum of Months | 0.849840E+10 | 0.764856E+10 | 12871.09 | 11583.98 | 11583.98 | 6.72 | 90.21 | |
Maximum of Months | 0.277236E+11 | 0.249512E+11 | 12871.09 | 11583.98 | 11583.98 | 7.29 | 90.21 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-JAN-00:05 | 3001.21 | 3001.21 | 21.89 | 13.93 |
February | 0.806725E+10 | 0.726052E+10 | 3334.68 | 01-FEB-00:10 | 3001.21 | 3001.21 | 24.55 | 13.93 |
March | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-MAR-00:10 | 3001.21 | 3001.21 | 27.30 | 13.93 |
April | 0.864348E+10 | 0.777913E+10 | 3334.68 | 01-APR-00:10 | 3001.21 | 3001.21 | 30.40 | 13.93 |
May | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-MAY-00:10 | 3001.21 | 3001.21 | 22.58 | 13.93 |
June | 0.864348E+10 | 0.777913E+10 | 3334.68 | 01-JUN-00:10 | 3001.21 | 3001.21 | 24.88 | 13.93 |
July | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-JUL-00:10 | 3001.21 | 3001.21 | 29.94 | 13.93 |
August | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-AUG-00:03 | 3001.21 | 3001.21 | 35.88 | 13.93 |
September | 0.864348E+10 | 0.777913E+10 | 3334.68 | 01-SEP-00:03 | 3001.21 | 3001.21 | 22.58 | 13.93 |
October | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-OCT-00:10 | 3001.21 | 3001.21 | 28.01 | 13.93 |
November | 0.864348E+10 | 0.777913E+10 | 3334.68 | 01-NOV-00:10 | 3001.21 | 3001.21 | 28.21 | 13.93 |
December | 0.893160E+10 | 0.803844E+10 | 3334.68 | 01-DEC-00:10 | 3001.21 | 3001.21 | 30.25 | 13.93 |
Annual Sum or Average | 0.105162E+12 | 0.946461E+11 | ||||||
Minimum of Months | 0.806725E+10 | 0.726052E+10 | 3334.68 | 3001.21 | 3001.21 | 21.89 | 13.93 | |
Maximum of Months | 0.893160E+10 | 0.803844E+10 | 3334.68 | 3001.21 | 3001.21 | 35.88 | 13.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.88 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.92 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.92 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 55.90 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 55.92 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 56.74 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.71 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.09 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.73 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.58 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.96 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.88 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.32 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.144555E+11 | 0.130100E+11 | 32012.72 | 13-JAN-13:50 | 28811.45 | 28811.45 | 25.83 | 106.27 |
February | 0.108068E+11 | 0.972615E+10 | 32004.59 | 01-FEB-13:20 | 28804.13 | 28804.13 | 25.52 | 106.27 |
March | 0.108183E+11 | 0.973647E+10 | 32015.68 | 23-MAR-13:50 | 28814.11 | 28814.11 | 25.94 | 106.27 |
April | 0.183245E+11 | 0.164921E+11 | 32017.87 | 26-APR-13:40 | 28816.09 | 28816.09 | 26.02 | 106.27 |
May | 0.199210E+11 | 0.179289E+11 | 32005.28 | 18-MAY-15:20 | 28804.75 | 28804.75 | 25.55 | 106.27 |
June | 0.280683E+11 | 0.252615E+11 | 32067.06 | 29-JUN-13:00 | 28860.35 | 28860.35 | 27.85 | 106.27 |
July | 0.397974E+11 | 0.358177E+11 | 32092.90 | 18-JUL-12:10 | 28883.61 | 28883.61 | 29.01 | 106.27 |
August | 0.442270E+11 | 0.398043E+11 | 32092.90 | 07-AUG-09:20 | 28883.61 | 28883.61 | 28.87 | 106.27 |
September | 0.294428E+11 | 0.264986E+11 | 32092.90 | 22-SEP-10:00 | 28883.61 | 28883.61 | 29.01 | 106.27 |
October | 0.319580E+11 | 0.287622E+11 | 32092.90 | 03-OCT-13:20 | 28883.61 | 28883.61 | 29.49 | 106.27 |
November | 0.163156E+11 | 0.146840E+11 | 32003.91 | 28-NOV-11:50 | 28803.52 | 28803.52 | 25.50 | 106.27 |
December | 0.153388E+11 | 0.138049E+11 | 32004.98 | 18-DEC-13:10 | 28804.48 | 28804.48 | 25.54 | 106.27 |
Annual Sum or Average | 0.279474E+12 | 0.251527E+12 | ||||||
Minimum of Months | 0.108068E+11 | 0.972615E+10 | 32003.91 | 28803.52 | 28803.52 | 25.50 | 106.27 | |
Maximum of Months | 0.442270E+11 | 0.398043E+11 | 32092.90 | 28883.61 | 28883.61 | 29.49 | 106.27 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 26262.07 | 811333.50 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35.95 | 35.95 | 20859.31 | 417537.49 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 46.41 | 46.41 | 28359.09 | 817124.51 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.81 | 37.81 | 8157.52 | 458938.46 | 01-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 27.13 | 27.13 | 5122.95 | 169544.12 | 15-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.20 | 26.20 | 507.53 | 124745.56 | 12-JUN-21:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.37 | 30.37 | 0.03 | 154.87 | 07-JUL-21:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 30.37 | 30.37 | 4.33 | 3491.72 | 28-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 30.01 | 30.01 | 402.70 | 93791.87 | 20-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.06 | 28.06 | 1577.79 | 265240.19 | 12-OCT-06:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.16 | 28.16 | 11196.40 | 318627.61 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 35.34 | 35.34 | 20819.63 | 520745.29 | 23-DEC-07:05 |
Annual Sum or Average | 0.00 | 10242.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.20 | 26.20 | 0.03 | 154.87 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 28359.09 | 817124.51 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 146408.74 | 1328627.50 | 13-JAN-14:00 | 10.21 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 96234.30 | 1152935.75 | 03-FEB-12:20 | 9.75 | 8.10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 94455.42 | 1216619.57 | 23-MAR-13:50 | 9.92 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 212313.15 | 1243759.71 | 12-APR-14:00 | 9.99 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 221395.34 | 1253185.81 | 03-MAY-13:00 | 10.01 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 348152.75 | 1517911.77 | 29-JUN-13:00 | 10.72 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 521288.72 | 1985103.15 | 31-JUL-15:50 | 11.95 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 592302.03 | 2001327.07 | 18-AUG-15:50 | 12.00 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 385792.86 | 1790777.20 | 29-SEP-12:20 | 11.44 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 424332.75 | 1852748.50 | 03-OCT-13:30 | 11.60 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 169304.21 | 1165884.92 | 08-NOV-12:30 | 9.78 | 8.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 168168.45 | 1225054.88 | 05-DEC-15:00 | 9.94 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 283233.82 | 0.00 | ||||||
Minimum of Months | 94455.42 | 1152935.75 | 9.75 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 592302.03 | 2001327.07 | 12.00 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 95146.19 | 1327421.49 | 13-JAN-14:00 | 11.03 | 7.91 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 56173.18 | 1110276.85 | 01-FEB-12:00 | 16.01 | 7.92 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 57760.91 | 1210040.45 | 23-MAR-13:50 | 14.59 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 138219.21 | 1237860.10 | 12-APR-14:00 | 13.86 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 140395.37 | 1244111.18 | 03-MAY-13:00 | 12.47 | 7.94 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 252385.29 | 1578196.13 | 30-JUN-05:03 | 14.56 | 6.86 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 415016.46 | 2189227.63 | 29-JUL-05:03 | 14.10 | 6.74 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 487379.89 | 2431179.96 | 07-AUG-05:02 | 14.58 | 7.04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 293305.58 | 2403659.50 | 30-SEP-05:02 | 16.29 | 7.06 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 333481.04 | 2812206.03 | 05-OCT-05:03 | 14.22 | 6.75 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 105699.67 | 1420182.26 | 19-NOV-12:23 | 14.97 | 7.68 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 115924.18 | 1222812.73 | 05-DEC-15:00 | 14.97 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 208929.77 | 0.00 | ||||||
Minimum of Months | 56173.18 | 1110276.85 | 11.03 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 487379.89 | 2812206.03 | 16.29 | 7.94 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 212913.89 | 660512.84 | 13-JAN-14:00 | 31.85 | 27.71 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 345277.26 | 869994.96 | 01-FEB-12:00 | 36.07 | 28.95 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 502179.87 | 975489.14 | 11-MAR-14:00 | 38.18 | 28.17 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 739587.98 | 1363370.23 | 26-APR-13:00 | 45.87 | 32.60 | 0.00 | 0.00 | 01-APR-00:10 |
May | 232100.82 | 569275.70 | 03-MAY-13:00 | 30.00 | 25.75 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 458429.03 | 842990.15 | 29-JUN-11:00 | 35.53 | 28.08 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 742887.99 | 1234814.01 | 31-JUL-13:00 | 43.33 | 32.53 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 961780.97 | 1425758.93 | 14-AUG-11:00 | 47.09 | 33.67 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 304630.97 | 1206350.36 | 29-SEP-13:00 | 42.77 | 38.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 527572.46 | 1498438.32 | 16-OCT-11:00 | 48.52 | 40.43 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 539601.56 | 1140845.15 | 19-NOV-13:00 | 41.47 | 31.27 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 710954.16 | 1291884.46 | 19-DEC-13:00 | 44.46 | 31.47 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 524759.85 | 0.00 | ||||||
Minimum of Months | 212913.89 | 569275.70 | 30.00 | 25.75 | 0.00 | 0.00 | ||
Maximum of Months | 961780.97 | 1498438.32 | 48.52 | 40.43 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.42 | 57.42 | 13761.22 | 45604.66 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.31 | 57.31 | 13850.03 | 45610.16 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.48 | 56.48 | 14479.53 | 45388.87 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.45 | 56.45 | 13398.11 | 44586.71 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.62 | 56.62 | 13487.12 | 43620.80 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.21 | 57.21 | 13496.54 | 42534.91 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.22 | 57.22 | 12365.30 | 41693.94 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.58 | 56.58 | 13385.15 | 41613.85 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.65 | 57.65 | 12778.31 | 42289.81 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.56 | 57.56 | 13013.81 | 43383.91 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.12 | 57.12 | 13485.38 | 44436.83 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.44 | 57.44 | 13306.31 | 45227.38 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 13398.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.45 | 56.45 | 12365.30 | 41613.85 | ||
Maximum of Months | 0.00 | 0.00 | 57.65 | 57.65 | 14479.53 | 45610.16 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 106766.44 | 2099476.79 | 13-JAN-13:50 | 25.83 | 21.36 | 959.92 | 90861.30 | 04-JAN-06:40 |
February | 62682.99 | 1964910.99 | 01-FEB-13:20 | 25.52 | 21.10 | 664.88 | 92724.52 | 06-FEB-06:30 |
March | 66631.05 | 2148432.22 | 23-MAR-13:50 | 25.94 | 22.11 | 387.17 | 71153.54 | 31-MAR-05:40 |
April | 152771.35 | 2184802.58 | 26-APR-13:40 | 26.02 | 22.03 | 293.37 | 67152.59 | 01-APR-05:50 |
May | 152648.04 | 1976255.02 | 18-MAY-15:20 | 25.55 | 21.10 | 208.05 | 47366.38 | 24-MAY-05:30 |
June | 309385.17 | 2997583.62 | 29-JUN-13:00 | 27.85 | 23.88 | 127.57 | 29780.78 | 22-JUN-20:10 |
July | 636625.77 | 4249943.31 | 31-JUL-13:00 | 30.67 | 25.98 | 99.10 | 28108.21 | 17-JUL-06:00 |
August | 777221.25 | 4242209.77 | 17-AUG-14:10 | 30.65 | 25.95 | 106.17 | 29867.54 | 21-AUG-20:20 |
September | 393499.55 | 3903193.36 | 22-SEP-12:30 | 29.89 | 25.42 | 219.48 | 34800.05 | 15-SEP-20:00 |
October | 459594.30 | 3838963.26 | 03-OCT-13:30 | 29.74 | 24.86 | 262.75 | 52881.51 | 27-OCT-06:00 |
November | 113929.32 | 1953586.26 | 28-NOV-11:50 | 25.50 | 21.10 | 709.68 | 76819.85 | 30-NOV-06:50 |
December | 126803.10 | 1971356.46 | 18-DEC-13:10 | 25.54 | 21.10 | 833.38 | 93099.85 | 28-DEC-06:30 |
Annual Sum or Average | 282075.82 | 404.58 | ||||||
Minimum of Months | 62682.99 | 1953586.26 | 25.50 | 21.10 | 99.10 | 28108.21 | ||
Maximum of Months | 777221.25 | 4249943.31 | 30.67 | 25.98 | 959.92 | 93099.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.236170E+10 | 0.00 | 0.207122E+11 | 0.713698E+10 | 0.00 | 0.00 |
February | 0.100927E+10 | 0.00 | 0.121801E+11 | 0.694513E+10 | 0.00 | 0.00 |
March | 0.155987E+10 | 0.00 | 0.147850E+11 | 0.890471E+10 | 0.00 | 0.00 |
April | 42037811.24 | 0.00 | 0.333266E+11 | 0.107086E+11 | 0.00 | 0.00 |
May | 0.130064E+09 | 0.00 | 0.301885E+11 | 0.836995E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.561840E+11 | 0.100582E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104123E+12 | 0.118191E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.128606E+12 | 0.140552E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.636230E+11 | 0.921968E+10 | 0.00 | 0.00 |
October | 12770830.23 | 0.00 | 0.784053E+11 | 0.968026E+10 | 0.00 | 0.00 |
November | 0.112780E+09 | 0.00 | 0.253077E+11 | 0.900659E+10 | 0.00 | 0.00 |
December | 0.924681E+09 | 0.00 | 0.295185E+11 | 0.895690E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.615317E+10 | 0.00 | 0.596959E+12 | 0.114861E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.121801E+11 | 0.694513E+10 | 0.00 | 0.00 |
Maximum of Months | 0.236170E+10 | 0.00 | 0.128606E+12 | 0.140552E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.582259E+11 | 0.00 | 0.172506E+12 | 0.495175E+11 | 0.00 | 0.00 |
February | 0.418170E+11 | 0.00 | 0.939737E+11 | 0.456579E+11 | 0.00 | 0.00 |
March | 0.636736E+11 | 0.00 | 0.106589E+12 | 0.532505E+11 | 0.00 | 0.00 |
April | 0.184511E+11 | 0.00 | 0.237220E+12 | 0.619449E+11 | 0.00 | 0.00 |
May | 0.119782E+11 | 0.00 | 0.250196E+12 | 0.631051E+11 | 0.00 | 0.00 |
June | 0.111014E+10 | 0.00 | 0.454366E+12 | 0.730499E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.799079E+12 | 0.798750E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.945120E+12 | 0.906323E+11 | 0.00 | 0.00 |
September | 0.883495E+09 | 0.00 | 0.544737E+12 | 0.727225E+11 | 0.00 | 0.00 |
October | 0.355187E+10 | 0.00 | 0.638222E+12 | 0.683322E+11 | 0.00 | 0.00 |
November | 0.245383E+11 | 0.00 | 0.183258E+12 | 0.546350E+11 | 0.00 | 0.00 |
December | 0.468200E+11 | 0.00 | 0.207585E+12 | 0.502046E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.271050E+12 | 0.00 | 0.463285E+13 | 0.762927E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.939737E+11 | 0.456579E+11 | 0.00 | 0.00 |
Maximum of Months | 0.636736E+11 | 0.00 | 0.945120E+12 | 0.906323E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.105980E+11 | 0.00 | 0.131388E+11 | 0.380114E+10 | 0.00 | 0.00 |
February | 0.807123E+10 | 0.00 | 0.740741E+10 | 0.354472E+10 | 0.00 | 0.00 |
March | 0.114794E+11 | 0.00 | 0.918160E+10 | 0.423762E+10 | 0.00 | 0.00 |
April | 0.288330E+10 | 0.00 | 0.233213E+11 | 0.548970E+10 | 0.00 | 0.00 |
May | 0.174125E+10 | 0.00 | 0.245790E+11 | 0.559796E+10 | 0.00 | 0.00 |
June | 0.201891E+09 | 0.00 | 0.472310E+11 | 0.704032E+10 | 0.00 | 0.00 |
July | 116948.42 | 0.00 | 0.858566E+11 | 0.822852E+10 | 0.00 | 0.00 |
August | 12978636.37 | 0.00 | 0.100159E+12 | 0.910614E+10 | 0.00 | 0.00 |
September | 0.176842E+09 | 0.00 | 0.536031E+11 | 0.661569E+10 | 0.00 | 0.00 |
October | 0.699482E+09 | 0.00 | 0.612202E+11 | 0.594331E+10 | 0.00 | 0.00 |
November | 0.461150E+10 | 0.00 | 0.141092E+11 | 0.405523E+10 | 0.00 | 0.00 |
December | 0.856492E+10 | 0.00 | 0.160405E+11 | 0.379781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490409E+11 | 0.00 | 0.455848E+12 | 0.674582E+11 | 0.00 | 0.00 |
Minimum of Months | 116948.42 | 0.00 | 0.740741E+10 | 0.354472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114794E+11 | 0.00 | 0.100159E+12 | 0.910614E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 107.33 | 0.00 | 0.121005E+11 | 0.169526E+11 | 0.00 | 0.00 |
February | 80.47 | 0.00 | 0.537816E+10 | 0.147321E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.624411E+10 | 0.169401E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.160624E+11 | 0.155451E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.156200E+11 | 0.164257E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.285060E+11 | 0.163888E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.484688E+11 | 0.156377E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.562466E+11 | 0.171897E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.340179E+11 | 0.161062E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.440538E+11 | 0.168618E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.134614E+11 | 0.163479E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.166741E+11 | 0.165075E+11 | 0.00 | 0.00 |
Annual Sum or Average | 187.80 | 0.00 | 0.296834E+12 | 0.195635E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.537816E+10 | 0.147321E+11 | 0.00 | 0.00 |
Maximum of Months | 107.33 | 0.00 | 0.562466E+11 | 0.171897E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.414925E+12 | 0.180118E+12 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.642118E+12 | 0.210563E+12 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.100921E+13 | 0.285415E+12 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.127566E+13 | 0.336216E+12 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.418193E+12 | 0.180272E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.704947E+12 | 0.235043E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104854E+13 | 0.314551E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.135857E+13 | 0.380411E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.415529E+12 | 0.179554E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.737725E+12 | 0.251346E+12 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.985423E+12 | 0.282098E+12 | 0.00 | 0.22 |
December | 0.00 | 0.00 | 0.131613E+13 | 0.346709E+12 | 0.00 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.103270E+14 | 0.318230E+13 | 0.00 | 1.03 |
Minimum of Months | 0.00 | 0.00 | 0.414925E+12 | 0.179554E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.135857E+13 | 0.380411E+12 | 0.00 | 0.40 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.654934E+10 | 0.275747E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116257E+11 | 0.351629E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191254E+11 | 0.497683E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249128E+11 | 0.607371E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.705635E+10 | 0.284209E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133298E+11 | 0.403147E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204424E+11 | 0.562021E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268220E+11 | 0.696040E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.727236E+10 | 0.288483E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138695E+11 | 0.431800E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.188188E+11 | 0.496125E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.255440E+11 | 0.626928E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195368E+12 | 0.552118E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.654934E+10 | 0.275747E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268220E+11 | 0.696040E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.500121E+11 | 0.239024E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100486E+12 | 0.316698E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172069E+12 | 0.457070E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.232286E+12 | 0.570154E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.611116E+11 | 0.259170E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123194E+12 | 0.377058E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.193359E+12 | 0.532656E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.254452E+12 | 0.660904E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.646138E+11 | 0.265757E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126350E+12 | 0.400457E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.170185E+12 | 0.456983E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.232358E+12 | 0.578983E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178048E+13 | 0.511491E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.500121E+11 | 0.239024E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.254452E+12 | 0.660904E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.339590E+10 | 0.210446E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.873993E+10 | 0.295872E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160079E+11 | 0.440099E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.226217E+11 | 0.563936E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.546771E+10 | 0.250026E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120467E+11 | 0.375348E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192482E+11 | 0.534781E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253216E+11 | 0.662787E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.607643E+10 | 0.261415E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120321E+11 | 0.392646E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.158047E+11 | 0.439310E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.217255E+11 | 0.557472E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168488E+12 | 0.498414E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.339590E+10 | 0.210446E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253216E+11 | 0.662787E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.713698E+10 | 0.207122E+11 | 0.236170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694513E+10 | 0.121801E+11 | 0.100927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.890471E+10 | 0.147850E+11 | 0.155987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107086E+11 | 0.333266E+11 | 42037811.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.836995E+10 | 0.301885E+11 | 0.130064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100582E+11 | 0.561840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118191E+11 | 0.104123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140552E+11 | 0.128606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921968E+10 | 0.636230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.968026E+10 | 0.784053E+11 | 12770830.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900659E+10 | 0.253077E+11 | 0.112780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.895690E+10 | 0.295185E+11 | 0.924681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114861E+12 | 0.596959E+12 | 0.615317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694513E+10 | 0.121801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140552E+11 | 0.128606E+12 | 0.236170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.495175E+11 | 0.172506E+12 | 0.582259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456579E+11 | 0.939737E+11 | 0.418170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532505E+11 | 0.106589E+12 | 0.636736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619449E+11 | 0.237220E+12 | 0.184511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631051E+11 | 0.250196E+12 | 0.119782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730499E+11 | 0.454366E+12 | 0.111014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798750E+11 | 0.799079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.906323E+11 | 0.945120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.727225E+11 | 0.544737E+12 | 0.883495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683322E+11 | 0.638222E+12 | 0.355187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546350E+11 | 0.183258E+12 | 0.245383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502046E+11 | 0.207585E+12 | 0.468200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.762927E+12 | 0.463285E+13 | 0.271050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.456579E+11 | 0.939737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.906323E+11 | 0.945120E+12 | 0.636736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.380114E+10 | 0.131388E+11 | 0.105980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354472E+10 | 0.740741E+10 | 0.807123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423762E+10 | 0.918160E+10 | 0.114794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548970E+10 | 0.233213E+11 | 0.288330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.559796E+10 | 0.245790E+11 | 0.174125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704032E+10 | 0.472310E+11 | 0.201891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.822852E+10 | 0.858566E+11 | 116948.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.910614E+10 | 0.100159E+12 | 12978636.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661569E+10 | 0.536031E+11 | 0.176842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594331E+10 | 0.612202E+11 | 0.699482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405523E+10 | 0.141092E+11 | 0.461150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379781E+10 | 0.160405E+11 | 0.856492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674582E+11 | 0.455848E+12 | 0.490409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.354472E+10 | 0.740741E+10 | 116948.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910614E+10 | 0.100159E+12 | 0.114794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169526E+11 | 0.121005E+11 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147321E+11 | 0.537816E+10 | 80.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169401E+11 | 0.624411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155451E+11 | 0.160624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164257E+11 | 0.156200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163888E+11 | 0.285060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156377E+11 | 0.484688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171897E+11 | 0.562466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161062E+11 | 0.340179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168618E+11 | 0.440538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163479E+11 | 0.134614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165075E+11 | 0.166741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195635E+12 | 0.296834E+12 | 187.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147321E+11 | 0.537816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171897E+11 | 0.562466E+11 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.957710E+11 | 0.331040E+12 | 0.00 | 0.00 | 0.00 | 0.459721E+09 | 0.00 | 0.00 |
February | 0.865029E+11 | 0.518421E+12 | 0.00 | 0.00 | 0.00 | 0.361522E+09 | 0.00 | 0.00 |
March | 0.957710E+11 | 0.819587E+12 | 0.00 | 0.00 | 0.00 | 19128872.30 | 0.00 | 0.00 |
April | 0.926817E+11 | 0.103220E+13 | 0.00 | 0.00 | 0.00 | 68698826.08 | 0.00 | 0.00 |
May | 0.957710E+11 | 0.333693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.926817E+11 | 0.562586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957710E+11 | 0.829763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.957710E+11 | 0.107393E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926817E+11 | 0.328657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957710E+11 | 0.582342E+12 | 0.00 | 0.00 | 0.00 | 0.191037E+09 | 0.00 | 0.00 |
November | 0.926817E+11 | 0.796594E+12 | 0.00 | 0.00 | 0.00 | 0.584381E+09 | 0.00 | 0.00 |
December | 0.957710E+11 | 0.106628E+13 | 0.00 | 0.00 | 0.00 | 0.107485E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112763E+13 | 0.827508E+13 | 0.00 | 0.00 | 0.00 | 0.275934E+10 | 0.00 | 0.00 |
Minimum of Months | 0.865029E+11 | 0.328657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957710E+11 | 0.107393E+13 | 0.00 | 0.00 | 0.00 | 0.107485E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143240E+10 | 0.522427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129378E+10 | 0.940320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143240E+10 | 0.155809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138619E+10 | 0.202252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143240E+10 | 0.564666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138619E+10 | 0.106846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143240E+10 | 0.162546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143240E+10 | 0.212940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138619E+10 | 0.577372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143240E+10 | 0.109838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138619E+10 | 0.152437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143240E+10 | 0.207071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168653E+11 | 0.157022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129378E+10 | 0.522427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143240E+10 | 0.212940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136253E+11 | 0.397351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123067E+11 | 0.811230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136253E+11 | 0.139988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131858E+11 | 0.188456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136253E+11 | 0.488200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131858E+11 | 0.986743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136253E+11 | 0.153719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136253E+11 | 0.201986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131858E+11 | 0.512239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136253E+11 | 0.999301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131858E+11 | 0.137672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136253E+11 | 0.188085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160427E+12 | 0.142941E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123067E+11 | 0.397351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136253E+11 | 0.201986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138943E+10 | 0.268086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125497E+10 | 0.703618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138943E+10 | 0.129964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134461E+10 | 0.183270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138943E+10 | 0.435687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134461E+10 | 0.963787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138943E+10 | 0.152898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138943E+10 | 0.200832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134461E+10 | 0.480689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138943E+10 | 0.949510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134461E+10 | 0.127562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138943E+10 | 0.175402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163594E+11 | 0.135006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125497E+10 | 0.268086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138943E+10 | 0.200832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.713698E+10 | 0.236170E+10 | 0.207122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694513E+10 | 0.100927E+10 | 0.121801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.890471E+10 | 0.155987E+10 | 0.147850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107086E+11 | 42037811.24 | 0.333266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.836995E+10 | 0.130064E+09 | 0.301885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100582E+11 | 0.00 | 0.561840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118191E+11 | 0.00 | 0.104123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140552E+11 | 0.00 | 0.128606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921968E+10 | 0.00 | 0.636230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.968026E+10 | 12770830.23 | 0.784053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.900659E+10 | 0.112780E+09 | 0.253077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.895690E+10 | 0.924681E+09 | 0.295185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114861E+12 | 0.615317E+10 | 0.596959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.694513E+10 | 0.00 | 0.121801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140552E+11 | 0.236170E+10 | 0.128606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.495175E+11 | 0.582259E+11 | 0.172506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456579E+11 | 0.418170E+11 | 0.939737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532505E+11 | 0.636736E+11 | 0.106589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.619449E+11 | 0.184511E+11 | 0.237220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631051E+11 | 0.119782E+11 | 0.250196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730499E+11 | 0.111014E+10 | 0.454366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798750E+11 | 0.00 | 0.799079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.906323E+11 | 0.00 | 0.945120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.727225E+11 | 0.883495E+09 | 0.544737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683322E+11 | 0.355187E+10 | 0.638222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546350E+11 | 0.245383E+11 | 0.183258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502046E+11 | 0.468200E+11 | 0.207585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.762927E+12 | 0.271050E+12 | 0.463285E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.456579E+11 | 0.00 | 0.939737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.906323E+11 | 0.636736E+11 | 0.945120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.380114E+10 | 0.105980E+11 | 0.131388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354472E+10 | 0.807123E+10 | 0.740741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.423762E+10 | 0.114794E+11 | 0.918160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548970E+10 | 0.288330E+10 | 0.233213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.559796E+10 | 0.174125E+10 | 0.245790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704032E+10 | 0.201891E+09 | 0.472310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.822852E+10 | 116948.42 | 0.858566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.910614E+10 | 12978636.37 | 0.100159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.661569E+10 | 0.176842E+09 | 0.536031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594331E+10 | 0.699482E+09 | 0.612202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405523E+10 | 0.461150E+10 | 0.141092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379781E+10 | 0.856492E+10 | 0.160405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674582E+11 | 0.490409E+11 | 0.455848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.354472E+10 | 116948.42 | 0.740741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.910614E+10 | 0.114794E+11 | 0.100159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169526E+11 | 107.33 | 0.121005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147321E+11 | 80.47 | 0.537816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169401E+11 | 0.00 | 0.624411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155451E+11 | 0.00 | 0.160624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164257E+11 | 0.00 | 0.156200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163888E+11 | 0.00 | 0.285060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156377E+11 | 0.00 | 0.484688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171897E+11 | 0.00 | 0.562466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161062E+11 | 0.00 | 0.340179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168618E+11 | 0.00 | 0.440538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163479E+11 | 0.00 | 0.134614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165075E+11 | 0.00 | 0.166741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195635E+12 | 187.80 | 0.296834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147321E+11 | 0.00 | 0.537816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171897E+11 | 107.33 | 0.562466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.957710E+11 | 0.00 | 0.414925E+12 | 0.00 | 0.838854E+11 | 0.00 | 0.00 | 0.00 | 0.461790E+09 | 0.00 | 0.00 | 0.00 |
February | 0.865029E+11 | 0.00 | 0.642118E+12 | 0.00 | 0.123697E+12 | 0.00 | 0.00 | 0.00 | 0.363149E+09 | 0.00 | 0.00 | 0.00 |
March | 0.957710E+11 | 0.00 | 0.100921E+13 | 0.00 | 0.189624E+12 | 0.00 | 0.00 | 0.00 | 19214979.11 | 0.00 | 0.00 | 0.00 |
April | 0.926817E+11 | 0.00 | 0.127566E+13 | 0.00 | 0.243465E+12 | 0.00 | 0.00 | 0.00 | 69008067.34 | 0.00 | 0.00 | 0.00 |
May | 0.957710E+11 | 0.00 | 0.418193E+12 | 0.00 | 0.845005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.926817E+11 | 0.00 | 0.704947E+12 | 0.00 | 0.142361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957710E+11 | 0.00 | 0.104854E+13 | 0.00 | 0.218780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.957710E+11 | 0.00 | 0.135857E+13 | 0.00 | 0.284640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.926817E+11 | 0.00 | 0.415529E+12 | 0.00 | 0.868723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.957710E+11 | 0.00 | 0.737725E+12 | 0.00 | 0.155383E+12 | 0.00 | 0.00 | 0.00 | 0.191897E+09 | 0.00 | 0.00 | 0.00 |
November | 0.926817E+11 | 0.00 | 0.985423E+12 | 0.00 | 0.188830E+12 | 0.00 | 0.00 | 0.00 | 0.587012E+09 | 0.00 | 0.00 | 0.00 |
December | 0.957710E+11 | 0.00 | 0.131613E+13 | 0.00 | 0.249858E+12 | 0.00 | 0.00 | 0.00 | 0.107969E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112763E+13 | 0.00 | 0.103270E+14 | 0.00 | 0.205190E+13 | 0.00 | 0.00 | 0.00 | 0.277176E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.865029E+11 | 0.00 | 0.414925E+12 | 0.00 | 0.838854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957710E+11 | 0.00 | 0.135857E+13 | 0.00 | 0.284640E+12 | 0.00 | 0.00 | 0.00 | 0.107969E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143240E+10 | 0.00 | 0.654934E+10 | 0.00 | 0.132507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129378E+10 | 0.00 | 0.116257E+11 | 0.00 | 0.222251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143240E+10 | 0.00 | 0.191254E+11 | 0.00 | 0.354443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138619E+10 | 0.00 | 0.249128E+11 | 0.00 | 0.468752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143240E+10 | 0.00 | 0.705635E+10 | 0.00 | 0.140969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138619E+10 | 0.00 | 0.133298E+11 | 0.00 | 0.264527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143240E+10 | 0.00 | 0.204424E+11 | 0.00 | 0.418781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143240E+10 | 0.00 | 0.268220E+11 | 0.00 | 0.552801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138619E+10 | 0.00 | 0.727236E+10 | 0.00 | 0.149864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143240E+10 | 0.00 | 0.138695E+11 | 0.00 | 0.288560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138619E+10 | 0.00 | 0.188188E+11 | 0.00 | 0.357506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143240E+10 | 0.00 | 0.255440E+11 | 0.00 | 0.483688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168653E+11 | 0.00 | 0.195368E+12 | 0.00 | 0.383465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129378E+10 | 0.00 | 0.654934E+10 | 0.00 | 0.132507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143240E+10 | 0.00 | 0.268220E+11 | 0.00 | 0.552801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136253E+11 | 0.00 | 0.500121E+11 | 0.00 | 0.102771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123067E+11 | 0.00 | 0.100486E+12 | 0.00 | 0.193630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136253E+11 | 0.00 | 0.172069E+12 | 0.00 | 0.320817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131858E+11 | 0.00 | 0.232286E+12 | 0.00 | 0.438296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136253E+11 | 0.00 | 0.611116E+11 | 0.00 | 0.122916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131858E+11 | 0.00 | 0.123194E+12 | 0.00 | 0.245200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136253E+11 | 0.00 | 0.193359E+12 | 0.00 | 0.396403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136253E+11 | 0.00 | 0.254452E+12 | 0.00 | 0.524651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131858E+11 | 0.00 | 0.646138E+11 | 0.00 | 0.133899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136253E+11 | 0.00 | 0.126350E+12 | 0.00 | 0.264204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131858E+11 | 0.00 | 0.170185E+12 | 0.00 | 0.325125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136253E+11 | 0.00 | 0.232358E+12 | 0.00 | 0.442730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160427E+12 | 0.00 | 0.178048E+13 | 0.00 | 0.351064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123067E+11 | 0.00 | 0.500121E+11 | 0.00 | 0.102771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136253E+11 | 0.00 | 0.254452E+12 | 0.00 | 0.524651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138943E+10 | 0.00 | 0.339590E+10 | 0.00 | 0.715037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125497E+10 | 0.00 | 0.873993E+10 | 0.00 | 0.170376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138943E+10 | 0.00 | 0.160079E+11 | 0.00 | 0.301156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134461E+10 | 0.00 | 0.226217E+11 | 0.00 | 0.429476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138943E+10 | 0.00 | 0.546771E+10 | 0.00 | 0.111083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134461E+10 | 0.00 | 0.120467E+11 | 0.00 | 0.240887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138943E+10 | 0.00 | 0.192482E+11 | 0.00 | 0.395838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138943E+10 | 0.00 | 0.253216E+11 | 0.00 | 0.523844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134461E+10 | 0.00 | 0.607643E+10 | 0.00 | 0.126954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138943E+10 | 0.00 | 0.120321E+11 | 0.00 | 0.253704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134461E+10 | 0.00 | 0.158047E+11 | 0.00 | 0.304849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138943E+10 | 0.00 | 0.217255E+11 | 0.00 | 0.418530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163594E+11 | 0.00 | 0.168488E+12 | 0.00 | 0.334820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125497E+10 | 0.00 | 0.339590E+10 | 0.00 | 0.715037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138943E+10 | 0.00 | 0.253216E+11 | 0.00 | 0.523844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.540138E+09 | 93268399.34 | 0.00 | 0.119951E+09 | 0.00 | 0.00 | 0.678443E+11 | 0.00 | 1.24 |
February | 0.370586E+09 | 5300542.89 | 0.00 | 0.101848E+09 | 0.00 | 0.00 | 0.642592E+11 | 0.00 | 1.23 |
March | 0.308466E+09 | 0.00 | 0.00 | 0.118770E+09 | 0.00 | 0.00 | 0.758317E+11 | 0.00 | 1.26 |
April | 0.240115E+09 | 9731625.54 | 0.00 | 0.112469E+09 | 0.00 | 0.00 | 0.602310E+11 | 0.00 | 1.38 |
May | 0.271318E+09 | 4268669.93 | 0.00 | 0.112292E+09 | 0.00 | 0.00 | 0.629137E+11 | 0.00 | 1.45 |
June | 0.181067E+09 | 0.177347E+09 | 0.00 | 0.113140E+09 | 0.00 | 0.00 | 0.512422E+11 | 0.00 | 1.62 |
July | 0.162656E+09 | 0.255887E+10 | 0.00 | 96568563.10 | 0.00 | 0.00 | 0.329016E+11 | 0.00 | 1.40 |
August | 0.151041E+09 | 0.325392E+10 | 0.00 | 0.102497E+09 | 0.00 | 0.00 | 0.341337E+11 | 0.00 | 1.54 |
September | 0.244729E+09 | 0.117902E+10 | 0.00 | 0.109256E+09 | 31436097.51 | 0.00 | 0.455872E+11 | 0.00 | 1.52 |
October | 0.308478E+09 | 0.291159E+10 | 0.00 | 0.107308E+09 | 20847139.15 | 0.00 | 0.426812E+11 | 0.00 | 1.40 |
November | 0.359653E+09 | 11240089.23 | 0.00 | 0.125019E+09 | 0.00 | 0.00 | 0.686525E+11 | 0.00 | 1.36 |
December | 0.564176E+09 | 1049088.24 | 0.00 | 0.124200E+09 | 0.00 | 0.00 | 0.643441E+11 | 0.00 | 1.24 |
Annual Sum or Average | 0.370242E+10 | 0.102056E+11 | 0.00 | 0.134332E+10 | 52283236.66 | 0.00 | 0.670622E+12 | 0.00 | 1.39 |
Minimum of Months | 0.151041E+09 | 0.00 | 0.00 | 96568563.10 | 0.00 | 0.00 | 0.329016E+11 | 0.00 | 1.23 |
Maximum of Months | 0.564176E+09 | 0.325392E+10 | 0.00 | 0.125019E+09 | 31436097.51 | 0.00 | 0.758317E+11 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275348E+10 | 82668194.57 | 0.00 | 88614767.37 | 18615916.20 | 0.00 | 0.470981E+11 | 0.00 | 0.84 |
February | 0.344142E+10 | 22238397.39 | 0.00 | 82166804.48 | 0.00 | 0.00 | 0.474460E+11 | 0.00 | 0.90 |
March | 0.327283E+10 | 0.00 | 0.00 | 0.102140E+09 | 9010515.32 | 0.00 | 0.603072E+11 | 0.00 | 0.99 |
April | 0.693745E+10 | 14870613.75 | 0.00 | 98608795.99 | 39132122.45 | 0.00 | 0.481072E+11 | 0.00 | 1.13 |
May | 0.396645E+10 | 34984088.89 | 0.00 | 91814034.38 | 0.00 | 0.00 | 0.448126E+11 | 0.00 | 1.01 |
June | 0.378772E+10 | 0.745826E+09 | 0.00 | 92622705.69 | 0.00 | 0.00 | 0.359210E+11 | 0.00 | 1.16 |
July | 0.742332E+10 | 0.601697E+10 | 0.00 | 63301828.18 | 0.315741E+09 | 0.00 | 0.173415E+11 | 0.00 | 1.18 |
August | 0.629993E+10 | 0.821036E+10 | 0.00 | 63038628.38 | 0.368460E+09 | 0.00 | 0.162778E+11 | 0.00 | 1.31 |
September | 0.317154E+10 | 0.180732E+10 | 0.00 | 79566992.08 | 53271911.96 | 0.00 | 0.281489E+11 | 0.00 | 1.03 |
October | 0.318790E+10 | 0.368536E+10 | 0.00 | 76012770.92 | 0.266098E+09 | 0.00 | 0.272729E+11 | 0.00 | 1.00 |
November | 0.386904E+10 | 12115442.44 | 0.00 | 98961233.83 | 13106353.29 | 0.00 | 0.512124E+11 | 0.00 | 1.02 |
December | 0.468298E+10 | 5193857.26 | 0.00 | 0.102044E+09 | 0.00 | 0.00 | 0.493306E+11 | 0.00 | 0.96 |
Annual Sum or Average | 0.527941E+11 | 0.206379E+11 | 0.00 | 0.103889E+10 | 0.108344E+10 | 0.00 | 0.473276E+12 | 0.00 | 1.04 |
Minimum of Months | 0.275348E+10 | 0.00 | 0.00 | 63038628.38 | 0.00 | 0.00 | 0.162778E+11 | 0.00 | 0.84 |
Maximum of Months | 0.742332E+10 | 0.821036E+10 | 0.00 | 0.102140E+09 | 0.368460E+09 | 0.00 | 0.603072E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.397382E+11 | 0.450440E+09 | 0.00 | 0.585170E+09 | 0.460830E+09 | 0.00 | 0.338918E+12 | 0.00 | 0.67 |
February | 0.289177E+11 | 0.226713E+09 | 0.00 | 0.552760E+09 | 0.00 | 0.00 | 0.350880E+12 | 0.00 | 0.70 |
March | 0.258331E+11 | 0.00 | 0.00 | 0.649032E+09 | 0.283650E+09 | 0.00 | 0.434602E+12 | 0.00 | 0.74 |
April | 0.243517E+11 | 0.122852E+09 | 0.00 | 0.684566E+09 | 0.410981E+09 | 0.00 | 0.347549E+12 | 0.00 | 0.80 |
May | 0.226625E+11 | 0.373577E+09 | 0.00 | 0.741767E+09 | 0.00 | 0.00 | 0.370409E+12 | 0.00 | 0.84 |
June | 0.184477E+11 | 0.538533E+10 | 0.00 | 0.759739E+09 | 0.00 | 0.00 | 0.289883E+12 | 0.00 | 0.93 |
July | 0.243180E+11 | 0.456177E+11 | 0.00 | 0.513471E+09 | 0.211344E+10 | 0.00 | 0.138188E+12 | 0.00 | 0.87 |
August | 0.137271E+11 | 0.570702E+11 | 0.00 | 0.531635E+09 | 0.245796E+10 | 0.00 | 0.130326E+12 | 0.00 | 0.94 |
September | 0.188507E+11 | 0.172500E+11 | 0.00 | 0.651255E+09 | 0.523121E+09 | 0.00 | 0.232975E+12 | 0.00 | 0.86 |
October | 0.168684E+11 | 0.324260E+11 | 0.00 | 0.579826E+09 | 0.207103E+10 | 0.00 | 0.206953E+12 | 0.00 | 0.79 |
November | 0.204517E+11 | 0.155261E+09 | 0.00 | 0.665491E+09 | 0.180111E+09 | 0.00 | 0.368973E+12 | 0.00 | 0.74 |
December | 0.281076E+11 | 79218258.55 | 0.00 | 0.601733E+09 | 36533514.74 | 0.00 | 0.333604E+12 | 0.00 | 0.67 |
Annual Sum or Average | 0.282274E+12 | 0.159157E+12 | 0.00 | 0.751645E+10 | 0.853766E+10 | 0.00 | 0.354326E+13 | 0.00 | 0.80 |
Minimum of Months | 0.137271E+11 | 0.00 | 0.00 | 0.513471E+09 | 0.00 | 0.00 | 0.130326E+12 | 0.00 | 0.67 |
Maximum of Months | 0.397382E+11 | 0.570702E+11 | 0.00 | 0.759739E+09 | 0.245796E+10 | 0.00 | 0.434602E+12 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139074E+11 | 5851259.30 | 0.00 | 25508196.74 | 68674962.24 | 0.240109E+09 | 0.150207E+11 | 0.00 | 0.55 |
February | 0.114928E+11 | 9421656.84 | 0.00 | 26463906.72 | 0.00 | 1652581.12 | 0.184531E+11 | 0.00 | 0.58 |
March | 0.129811E+11 | 0.00 | 0.00 | 33045247.84 | 51159.52 | 0.00 | 0.248268E+11 | 0.00 | 0.63 |
April | 0.605652E+10 | 516911.47 | 0.00 | 49888732.33 | 20959750.13 | 0.00 | 0.282193E+11 | 0.00 | 0.74 |
May | 0.573051E+10 | 12146490.88 | 0.00 | 55176348.69 | 0.00 | 0.00 | 0.302949E+11 | 0.00 | 0.78 |
June | 0.253083E+10 | 0.245572E+09 | 0.00 | 67482951.80 | 0.00 | 0.00 | 0.273757E+11 | 0.00 | 0.91 |
July | 0.208326E+10 | 0.385456E+10 | 0.00 | 52283852.61 | 0.164711E+09 | 0.00 | 0.137322E+11 | 0.00 | 0.89 |
August | 0.881589E+09 | 0.504141E+10 | 0.00 | 53777705.84 | 0.146591E+09 | 0.00 | 0.122652E+11 | 0.00 | 0.96 |
September | 0.264174E+10 | 0.127521E+10 | 0.00 | 55059906.97 | 45828584.86 | 0.00 | 0.200794E+11 | 0.00 | 0.80 |
October | 0.397837E+10 | 0.267144E+10 | 0.00 | 39309973.53 | 0.209507E+09 | 0.00 | 0.137868E+11 | 0.00 | 0.71 |
November | 0.914665E+10 | 838653.28 | 0.00 | 33645598.90 | 18867076.90 | 0.00 | 0.208932E+11 | 0.00 | 0.61 |
December | 0.124578E+11 | 1650921.39 | 0.00 | 26505253.43 | 9930138.42 | 1543173.57 | 0.146085E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.838885E+11 | 0.131186E+11 | 0.00 | 0.518148E+09 | 0.685120E+09 | 0.243305E+09 | 0.239556E+12 | 0.00 | 0.72 |
Minimum of Months | 0.881589E+09 | 0.00 | 0.00 | 25508196.74 | 0.00 | 0.00 | 0.122652E+11 | 0.00 | 0.54 |
Maximum of Months | 0.139074E+11 | 0.504141E+10 | 0.00 | 67482951.80 | 0.209507E+09 | 0.240109E+09 | 0.302949E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263993E+10 | 10665014.41 | 0.00 | 4142744.98 | 2978778.65 | 0.00 | 0.226370E+10 | 0.00 | 0.66 |
February | 0.234167E+10 | 2662727.57 | 0.00 | 4380791.56 | 0.00 | 0.00 | 0.283645E+10 | 0.00 | 0.73 |
March | 0.226205E+10 | 0.00 | 0.00 | 6050236.88 | 1340808.94 | 0.00 | 0.413311E+10 | 0.00 | 0.81 |
April | 0.188699E+10 | 1905022.94 | 0.00 | 8108521.59 | 5823052.06 | 0.00 | 0.435078E+10 | 0.00 | 1.05 |
May | 0.144413E+10 | 5042161.30 | 0.00 | 8311209.15 | 0.00 | 0.00 | 0.444947E+10 | 0.00 | 1.00 |
June | 0.768262E+09 | 0.113357E+09 | 0.00 | 10513491.87 | 0.00 | 0.00 | 0.435442E+10 | 0.00 | 1.25 |
July | 0.121823E+10 | 0.958137E+09 | 0.00 | 7207174.05 | 46983868.79 | 0.00 | 0.206108E+10 | 0.00 | 1.34 |
August | 0.106350E+10 | 0.123745E+10 | 0.00 | 6329108.44 | 54828682.03 | 0.00 | 0.170437E+10 | 0.00 | 1.40 |
September | 0.896203E+09 | 0.286804E+09 | 0.00 | 6701307.94 | 7927122.19 | 0.00 | 0.269924E+10 | 0.00 | 1.01 |
October | 0.110133E+10 | 0.554298E+09 | 0.00 | 5732051.07 | 39755731.35 | 0.00 | 0.219348E+10 | 0.00 | 0.94 |
November | 0.207468E+10 | 1418088.73 | 0.00 | 5947612.31 | 1950289.75 | 0.00 | 0.340888E+10 | 0.00 | 0.82 |
December | 0.241046E+10 | 608367.23 | 0.00 | 5442625.91 | 0.00 | 0.00 | 0.273783E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.201074E+11 | 0.317234E+10 | 0.00 | 78866875.75 | 0.161588E+09 | 0.00 | 0.371928E+11 | 0.00 | 0.98 |
Minimum of Months | 0.768262E+09 | 0.00 | 0.00 | 4142744.98 | 0.00 | 0.00 | 0.170437E+10 | 0.00 | 0.66 |
Maximum of Months | 0.263993E+10 | 0.123745E+10 | 0.00 | 10513491.87 | 54828682.03 | 0.00 | 0.444947E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273198E+10 | 3960246.23 | 0.00 | 3906702.03 | 10091008.62 | 0.00 | 0.237028E+10 | 0.00 | 1.03 |
February | 0.272157E+10 | 1917914.85 | 0.00 | 3576300.21 | 0.00 | 0.00 | 0.238314E+10 | 0.00 | 1.10 |
March | 0.298058E+10 | 147932.25 | 0.00 | 4742380.47 | 1293212.82 | 0.00 | 0.315447E+10 | 0.00 | 1.18 |
April | 0.270790E+10 | 2259837.39 | 0.00 | 7001650.86 | 6133853.13 | 0.00 | 0.353769E+10 | 0.00 | 1.58 |
May | 0.201448E+10 | 4491010.47 | 0.00 | 6898618.43 | 0.00 | 0.00 | 0.368133E+10 | 0.00 | 1.46 |
June | 0.154821E+10 | 86904851.00 | 0.00 | 7536850.01 | 0.00 | 0.00 | 0.306156E+10 | 0.00 | 1.71 |
July | 0.160635E+10 | 0.756633E+09 | 0.00 | 5503243.64 | 43125321.93 | 0.00 | 0.166138E+10 | 0.00 | 1.90 |
August | 0.154928E+10 | 0.105640E+10 | 0.00 | 4476201.31 | 49837722.41 | 0.00 | 0.128640E+10 | 0.00 | 2.02 |
September | 0.155844E+10 | 0.218799E+09 | 0.00 | 5473570.14 | 11431044.20 | 0.00 | 0.204663E+10 | 0.00 | 1.49 |
October | 0.169921E+10 | 0.410219E+09 | 0.00 | 4098706.19 | 46345581.36 | 0.00 | 0.161223E+10 | 0.00 | 1.32 |
November | 0.260013E+10 | 1266567.74 | 0.00 | 4537696.19 | 2096234.87 | 0.00 | 0.257821E+10 | 0.00 | 1.14 |
December | 0.300123E+10 | 520513.32 | 0.00 | 3841945.12 | 0.00 | 0.00 | 0.204174E+10 | 0.00 | 1.08 |
Annual Sum or Average | 0.267194E+11 | 0.254352E+10 | 0.00 | 61593864.61 | 0.170354E+09 | 0.00 | 0.294151E+11 | 0.00 | 1.42 |
Minimum of Months | 0.154821E+10 | 147932.25 | 0.00 | 3576300.21 | 0.00 | 0.00 | 0.128640E+10 | 0.00 | 1.03 |
Maximum of Months | 0.300123E+10 | 0.105640E+10 | 0.00 | 7536850.01 | 49837722.41 | 0.00 | 0.368133E+10 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217991E+10 | 43444640.22 | 0.00 | 14013377.33 | 3660197.57 | 0.00 | 0.749007E+10 | 0.00 | 1.42 |
February | 0.242866E+10 | 6689382.50 | 0.00 | 10399613.57 | 0.00 | 0.00 | 0.616733E+10 | 0.00 | 1.31 |
March | 0.293318E+10 | 614093.87 | 0.00 | 10221259.21 | 1236232.25 | 0.00 | 0.634125E+10 | 0.00 | 1.26 |
April | 0.276984E+10 | 3828005.11 | 0.00 | 11004598.71 | 6850225.75 | 0.00 | 0.557208E+10 | 0.00 | 1.45 |
May | 0.263025E+10 | 5994788.52 | 0.00 | 7879360.12 | 0.00 | 0.00 | 0.414725E+10 | 0.00 | 1.15 |
June | 0.172577E+10 | 0.123871E+09 | 0.00 | 8694429.52 | 0.00 | 0.00 | 0.373546E+10 | 0.00 | 1.32 |
July | 0.177852E+10 | 0.105352E+10 | 0.00 | 6017114.83 | 60757125.99 | 0.00 | 0.196968E+10 | 0.00 | 1.48 |
August | 0.149529E+10 | 0.160938E+10 | 0.00 | 6676942.87 | 71211299.93 | 0.00 | 0.194484E+10 | 0.00 | 1.77 |
September | 0.123676E+10 | 0.463810E+09 | 0.00 | 10836358.89 | 10420408.95 | 0.00 | 0.391293E+10 | 0.00 | 1.55 |
October | 0.130684E+10 | 0.982830E+09 | 0.00 | 11409558.80 | 27374895.86 | 0.00 | 0.362862E+10 | 0.00 | 1.51 |
November | 0.171670E+10 | 7265768.87 | 0.00 | 15571043.38 | 867781.71 | 0.00 | 0.801371E+10 | 0.00 | 1.57 |
December | 0.196439E+10 | 1290237.33 | 0.00 | 17589224.65 | 0.00 | 0.00 | 0.764755E+10 | 0.00 | 1.54 |
Annual Sum or Average | 0.241661E+11 | 0.430254E+10 | 0.00 | 0.130313E+09 | 0.182378E+09 | 0.00 | 0.605708E+11 | 0.00 | 1.44 |
Minimum of Months | 0.123676E+10 | 614093.87 | 0.00 | 6017114.83 | 0.00 | 0.00 | 0.194484E+10 | 0.00 | 1.15 |
Maximum of Months | 0.293318E+10 | 0.160938E+10 | 0.00 | 17589224.65 | 71211299.93 | 0.00 | 0.801371E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307192E+10 | 17888054.26 | 0.00 | 5242255.65 | 3814366.04 | 0.00 | 0.362275E+10 | 0.00 | 1.37 |
February | 0.180306E+10 | 3461442.87 | 0.00 | 7307004.62 | 0.00 | 0.00 | 0.535189E+10 | 0.00 | 1.57 |
March | 0.117304E+10 | 111973.53 | 0.00 | 12137421.66 | 1734264.03 | 0.00 | 0.813791E+10 | 0.00 | 1.84 |
April | 0.130075E+10 | 7286098.25 | 0.00 | 18643708.27 | 3899017.73 | 0.00 | 0.851271E+10 | 0.00 | 2.56 |
May | 0.143358E+10 | 5076110.70 | 0.00 | 10779172.51 | 0.00 | 0.00 | 0.599948E+10 | 0.00 | 1.93 |
June | 0.811921E+09 | 0.123088E+09 | 0.00 | 15111479.12 | 0.00 | 0.00 | 0.584510E+10 | 0.00 | 2.49 |
July | 0.129009E+10 | 0.128213E+10 | 0.00 | 13750047.94 | 41254542.31 | 0.00 | 0.333981E+10 | 0.00 | 2.84 |
August | 0.103821E+10 | 0.172594E+10 | 0.00 | 13828224.89 | 41363536.89 | 0.00 | 0.315664E+10 | 0.00 | 3.22 |
September | 0.773764E+09 | 0.307284E+09 | 0.00 | 9829622.35 | 10859319.28 | 0.00 | 0.399384E+10 | 0.00 | 2.00 |
October | 0.966946E+09 | 0.622723E+09 | 0.00 | 8978329.01 | 43807510.30 | 0.00 | 0.339229E+10 | 0.00 | 1.85 |
November | 0.103926E+10 | 3861806.22 | 0.00 | 11580131.66 | 2133443.43 | 0.00 | 0.679432E+10 | 0.00 | 1.82 |
December | 0.117248E+10 | 749941.94 | 0.00 | 13024167.59 | 0.00 | 0.00 | 0.669823E+10 | 0.00 | 1.78 |
Annual Sum or Average | 0.158750E+11 | 0.409960E+10 | 0.00 | 0.140212E+09 | 0.148866E+09 | 0.00 | 0.648450E+11 | 0.00 | 2.11 |
Minimum of Months | 0.773764E+09 | 111973.53 | 0.00 | 5242255.65 | 0.00 | 0.00 | 0.315664E+10 | 0.00 | 1.37 |
Maximum of Months | 0.307192E+10 | 0.172594E+10 | 0.00 | 18643708.27 | 43807510.30 | 0.00 | 0.851271E+10 | 0.00 | 3.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339374E+11 | 19440622.60 | 0.00 | 12370357.88 | 0.103465E+09 | 0.142466E+10 | 0.633532E+10 | 0.00 | 0.56 |
February | 0.299999E+11 | 22795703.84 | 0.00 | 13705798.91 | 0.00 | 17339572.06 | 0.989693E+10 | 0.00 | 0.57 |
March | 0.354370E+11 | 0.00 | 0.00 | 17993145.98 | 42008744.76 | 0.646055E+09 | 0.124698E+11 | 0.00 | 0.60 |
April | 0.215148E+11 | 11027394.02 | 0.00 | 39391082.67 | 64918169.11 | 6451102.99 | 0.196463E+11 | 0.00 | 0.70 |
May | 0.185392E+11 | 50002413.95 | 0.00 | 53693167.16 | 0.00 | 0.00 | 0.270734E+11 | 0.00 | 0.79 |
June | 0.973532E+10 | 0.796229E+09 | 0.00 | 71434402.93 | 0.00 | 0.00 | 0.287223E+11 | 0.00 | 0.97 |
July | 0.635514E+10 | 0.726966E+10 | 0.00 | 46418427.80 | 0.313003E+09 | 0.00 | 0.141865E+11 | 0.00 | 0.96 |
August | 0.703396E+10 | 0.836414E+10 | 0.00 | 36173852.15 | 0.366052E+09 | 0.00 | 0.966423E+10 | 0.00 | 0.97 |
September | 0.132616E+11 | 0.266909E+10 | 0.00 | 42440006.75 | 0.104046E+09 | 0.00 | 0.151086E+11 | 0.00 | 0.82 |
October | 0.151662E+11 | 0.473731E+10 | 0.00 | 29959347.63 | 0.330848E+09 | 0.00 | 0.954292E+10 | 0.00 | 0.72 |
November | 0.264511E+11 | 4469583.99 | 0.00 | 20802786.60 | 41494712.75 | 7915939.83 | 0.130435E+11 | 0.00 | 0.58 |
December | 0.330035E+11 | 5563862.81 | 0.00 | 11578089.36 | 6788888.79 | 0.215704E+09 | 0.579114E+10 | 0.00 | 0.55 |
Annual Sum or Average | 0.250435E+12 | 0.239497E+11 | 0.00 | 0.395960E+09 | 0.137262E+10 | 0.231813E+10 | 0.171481E+12 | 0.00 | 0.73 |
Minimum of Months | 0.635514E+10 | 0.00 | 0.00 | 11578089.36 | 0.00 | 0.00 | 0.579114E+10 | 0.00 | 0.55 |
Maximum of Months | 0.354370E+11 | 0.836414E+10 | 0.00 | 71434402.93 | 0.366052E+09 | 0.142466E+10 | 0.287223E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.373812E+11 | 31524411.59 | 0.00 | 13509074.89 | 0.110232E+09 | 0.671255E+09 | 0.102549E+11 | 0.00 | 0.98 |
February | 0.333121E+11 | 20993169.93 | 0.00 | 17094779.14 | 0.00 | 27008861.04 | 0.132489E+11 | 0.00 | 1.02 |
March | 0.381563E+11 | 0.00 | 0.00 | 24766599.71 | 49001011.05 | 0.364904E+09 | 0.180644E+11 | 0.00 | 1.09 |
April | 0.219053E+11 | 23034412.57 | 0.00 | 55417334.88 | 69539428.61 | 69716479.28 | 0.278580E+11 | 0.00 | 1.31 |
May | 0.230593E+11 | 51197266.39 | 0.00 | 53365162.95 | 0.00 | 0.00 | 0.275601E+11 | 0.00 | 1.33 |
June | 0.155609E+11 | 0.683312E+09 | 0.00 | 64127245.47 | 0.00 | 0.00 | 0.247934E+11 | 0.00 | 1.54 |
July | 0.960389E+10 | 0.672590E+10 | 0.00 | 51518711.20 | 0.300820E+09 | 0.00 | 0.145185E+11 | 0.00 | 1.62 |
August | 0.899887E+10 | 0.895718E+10 | 0.00 | 43146068.54 | 0.336274E+09 | 0.00 | 0.113083E+11 | 0.00 | 1.70 |
September | 0.168766E+11 | 0.226522E+10 | 0.00 | 43918526.08 | 0.120788E+09 | 0.00 | 0.154871E+11 | 0.00 | 1.37 |
October | 0.175237E+11 | 0.406861E+10 | 0.00 | 28578125.06 | 0.437443E+09 | 0.00 | 0.106455E+11 | 0.00 | 1.17 |
November | 0.296287E+11 | 2006310.02 | 0.00 | 18188432.28 | 51459689.35 | 5228150.30 | 0.156289E+11 | 0.00 | 1.02 |
December | 0.371099E+11 | 4996310.35 | 0.00 | 11749047.90 | 10048531.86 | 0.169315E+09 | 0.796634E+10 | 0.00 | 0.99 |
Annual Sum or Average | 0.289117E+12 | 0.228340E+11 | 0.00 | 0.425379E+09 | 0.148561E+10 | 0.130743E+10 | 0.197335E+12 | 0.00 | 1.26 |
Minimum of Months | 0.899887E+10 | 0.00 | 0.00 | 11749047.90 | 0.00 | 0.00 | 0.796634E+10 | 0.00 | 0.98 |
Maximum of Months | 0.381563E+11 | 0.895718E+10 | 0.00 | 64127245.47 | 0.437443E+09 | 0.671255E+09 | 0.278580E+11 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235415E+11 | 0.538579E+09 | 0.00 | 0.128821E+09 | 0.00 | 0.224037E+09 | 0.653823E+11 | 0.00 | 1.35 |
February | 0.269592E+11 | 79528316.55 | 0.00 | 86342575.87 | 0.00 | 0.00 | 0.487604E+11 | 0.00 | 1.19 |
March | 0.355781E+11 | 23555785.25 | 0.00 | 74663635.94 | 40454370.34 | 0.604092E+09 | 0.440944E+11 | 0.00 | 1.10 |
April | 0.248193E+11 | 30142437.71 | 0.00 | 78774919.12 | 78535937.73 | 0.00 | 0.382697E+11 | 0.00 | 1.13 |
May | 0.282491E+11 | 62158605.43 | 0.00 | 57566992.30 | 0.00 | 0.00 | 0.292901E+11 | 0.00 | 0.99 |
June | 0.190380E+11 | 0.897418E+09 | 0.00 | 62219649.53 | 0.00 | 0.00 | 0.251848E+11 | 0.00 | 1.09 |
July | 0.129461E+11 | 0.832686E+10 | 0.00 | 40523108.56 | 0.421118E+09 | 0.00 | 0.117446E+11 | 0.00 | 1.12 |
August | 0.915555E+10 | 0.120305E+11 | 0.00 | 49292178.92 | 0.497663E+09 | 0.00 | 0.133460E+11 | 0.00 | 1.35 |
September | 0.123208E+11 | 0.490235E+10 | 0.00 | 93882829.43 | 0.140873E+09 | 0.00 | 0.327918E+11 | 0.00 | 1.42 |
October | 0.125238E+11 | 0.102475E+11 | 0.00 | 96888190.66 | 0.172433E+09 | 0.00 | 0.285394E+11 | 0.00 | 1.36 |
November | 0.194008E+11 | 0.123016E+09 | 0.00 | 0.129743E+09 | 3614758.40 | 0.00 | 0.642149E+11 | 0.00 | 1.40 |
December | 0.219087E+11 | 51335396.48 | 0.00 | 0.143011E+09 | 0.00 | 46602799.69 | 0.588497E+11 | 0.00 | 1.37 |
Annual Sum or Average | 0.246441E+12 | 0.373130E+11 | 0.00 | 0.104173E+10 | 0.135469E+10 | 0.874731E+09 | 0.460468E+12 | 0.00 | 1.24 |
Minimum of Months | 0.915555E+10 | 23555785.25 | 0.00 | 40523108.56 | 0.00 | 0.00 | 0.117446E+11 | 0.00 | 0.99 |
Maximum of Months | 0.355781E+11 | 0.120305E+11 | 0.00 | 0.143011E+09 | 0.497663E+09 | 0.604092E+09 | 0.653823E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413492E+11 | 85365006.50 | 0.00 | 17725789.19 | 70630091.14 | 0.674330E+09 | 0.110097E+11 | 0.00 | 1.09 |
February | 0.368180E+11 | 25686901.83 | 0.00 | 20661751.50 | 0.00 | 0.00 | 0.151829E+11 | 0.00 | 1.15 |
March | 0.425035E+11 | 0.00 | 0.00 | 29017977.39 | 52440154.00 | 0.261690E+09 | 0.209166E+11 | 0.00 | 1.24 |
April | 0.215042E+11 | 15213000.65 | 0.00 | 59928476.89 | 75971681.85 | 0.00 | 0.335758E+11 | 0.00 | 1.46 |
May | 0.214333E+11 | 43634048.42 | 0.00 | 60368786.70 | 0.00 | 0.00 | 0.343627E+11 | 0.00 | 1.47 |
June | 0.120447E+11 | 0.720030E+09 | 0.00 | 79435190.90 | 0.00 | 0.00 | 0.332243E+11 | 0.00 | 1.74 |
July | 0.717787E+10 | 0.823707E+10 | 0.00 | 61090775.66 | 0.329897E+09 | 0.00 | 0.180257E+11 | 0.00 | 1.75 |
August | 0.658907E+10 | 0.927083E+10 | 0.00 | 52572226.65 | 0.339317E+09 | 0.00 | 0.140694E+11 | 0.00 | 1.83 |
September | 0.127032E+11 | 0.259963E+10 | 0.00 | 54725777.16 | 0.133139E+09 | 0.00 | 0.231820E+11 | 0.00 | 1.53 |
October | 0.177546E+11 | 0.449887E+10 | 0.00 | 32099454.95 | 0.488275E+09 | 0.00 | 0.120330E+11 | 0.00 | 1.29 |
November | 0.334661E+11 | 18473228.44 | 0.00 | 27741125.90 | 41111283.49 | 0.00 | 0.179121E+11 | 0.00 | 1.18 |
December | 0.387548E+11 | 14625703.87 | 0.00 | 19333575.58 | 1722169.60 | 54373681.88 | 0.109506E+11 | 0.00 | 1.10 |
Annual Sum or Average | 0.292099E+12 | 0.255294E+11 | 0.00 | 0.514701E+09 | 0.153250E+10 | 0.990394E+09 | 0.244445E+12 | 0.00 | 1.40 |
Minimum of Months | 0.658907E+10 | 0.00 | 0.00 | 17725789.19 | 0.00 | 0.00 | 0.109506E+11 | 0.00 | 1.09 |
Maximum of Months | 0.425035E+11 | 0.927083E+10 | 0.00 | 79435190.90 | 0.488275E+09 | 0.674330E+09 | 0.343627E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.337106E+10 | 61770.66 | 0.00 | 382205.62 | 12607503.52 | 0.803647E+09 | 0.226319E+09 | 0.00 | 0.63 |
February | 0.343510E+10 | 808964.47 | 0.00 | 364236.00 | 0.00 | 0.510387E+09 | 0.313285E+09 | 0.00 | 0.65 |
March | 0.432772E+10 | 0.00 | 0.00 | 735708.19 | 8932.60 | 0.489632E+09 | 0.598277E+09 | 0.00 | 0.69 |
April | 0.259760E+10 | 62419.70 | 0.00 | 2950132.37 | 3659632.87 | 75777290.99 | 0.170697E+10 | 0.00 | 0.74 |
May | 0.234543E+10 | 1450980.18 | 0.00 | 4186728.05 | 0.00 | 11103434.04 | 0.235160E+10 | 0.00 | 0.80 |
June | 0.135722E+10 | 34869206.77 | 0.00 | 6543684.40 | 0.00 | 0.00 | 0.273440E+10 | 0.00 | 1.00 |
July | 0.898080E+09 | 0.596890E+09 | 0.00 | 4718128.51 | 29127692.29 | 0.00 | 0.133985E+10 | 0.00 | 1.02 |
August | 0.831670E+09 | 0.713261E+09 | 0.00 | 4102765.82 | 34775935.19 | 0.00 | 0.921012E+09 | 0.00 | 1.04 |
September | 0.160699E+10 | 0.193110E+09 | 0.00 | 3859920.74 | 12952730.04 | 0.00 | 0.134850E+10 | 0.00 | 0.83 |
October | 0.166351E+10 | 0.373776E+09 | 0.00 | 2138399.11 | 56495765.99 | 56088139.12 | 0.707972E+09 | 0.00 | 0.75 |
November | 0.325424E+10 | 73239.67 | 0.00 | 474059.33 | 3294246.08 | 0.336346E+09 | 0.484863E+09 | 0.00 | 0.64 |
December | 0.328353E+10 | 0.00 | 0.00 | 255558.46 | 1923492.41 | 0.619334E+09 | 0.157144E+09 | 0.00 | 0.63 |
Annual Sum or Average | 0.289722E+11 | 0.191436E+10 | 0.00 | 30711526.61 | 0.154846E+09 | 0.290231E+10 | 0.128902E+11 | 0.00 | 0.78 |
Minimum of Months | 0.831670E+09 | 0.00 | 0.00 | 255558.46 | 0.00 | 0.00 | 0.157144E+09 | 0.00 | 0.63 |
Maximum of Months | 0.432772E+10 | 0.713261E+09 | 0.00 | 6543684.40 | 56495765.99 | 0.803647E+09 | 0.273440E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.360582E+10 | 578195.54 | 0.00 | 608013.53 | 12194668.86 | 0.443365E+09 | 0.378748E+09 | 0.00 | 0.98 |
February | 0.306659E+10 | 841463.78 | 0.00 | 1030465.60 | 0.00 | 0.361925E+09 | 0.870345E+09 | 0.00 | 1.01 |
March | 0.396710E+10 | 9005.64 | 0.00 | 1520258.15 | 0.00 | 0.328907E+09 | 0.122438E+10 | 0.00 | 1.11 |
April | 0.199555E+10 | 336616.19 | 0.00 | 5166672.12 | 3447734.47 | 35244126.91 | 0.278929E+10 | 0.00 | 1.29 |
May | 0.222296E+10 | 1816533.71 | 0.00 | 4940561.63 | 0.00 | 2198632.72 | 0.267652E+10 | 0.00 | 1.30 |
June | 0.146838E+10 | 31336898.78 | 0.00 | 6737105.29 | 0.00 | 0.00 | 0.266123E+10 | 0.00 | 1.56 |
July | 0.824594E+09 | 0.567252E+09 | 0.00 | 5939364.84 | 17760326.88 | 0.00 | 0.161999E+10 | 0.00 | 1.68 |
August | 0.737567E+09 | 0.792007E+09 | 0.00 | 5347082.09 | 21571573.59 | 0.00 | 0.121862E+10 | 0.00 | 1.77 |
September | 0.150047E+10 | 0.176528E+09 | 0.00 | 4735013.59 | 12875087.50 | 0.00 | 0.162739E+10 | 0.00 | 1.34 |
October | 0.153669E+10 | 0.359617E+09 | 0.00 | 2533261.21 | 43244731.42 | 23320718.71 | 0.904122E+09 | 0.00 | 1.14 |
November | 0.304199E+10 | 73838.52 | 0.00 | 740972.11 | 3321181.46 | 0.119014E+09 | 0.939708E+09 | 0.00 | 1.00 |
December | 0.349104E+10 | 259457.30 | 0.00 | 476738.26 | 1737290.83 | 0.326102E+09 | 0.271411E+09 | 0.00 | 0.98 |
Annual Sum or Average | 0.274587E+11 | 0.193066E+10 | 0.00 | 39775508.42 | 0.116153E+09 | 0.164008E+10 | 0.171817E+11 | 0.00 | 1.27 |
Minimum of Months | 0.737567E+09 | 9005.64 | 0.00 | 476738.26 | 0.00 | 0.00 | 0.271411E+09 | 0.00 | 0.98 |
Maximum of Months | 0.396710E+10 | 0.792007E+09 | 0.00 | 6737105.29 | 43244731.42 | 0.443365E+09 | 0.278929E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268858E+10 | 45103009.32 | 0.00 | 9505865.81 | 0.00 | 0.319342E+09 | 0.520079E+10 | 0.00 | 1.29 |
February | 0.300539E+10 | 3414079.53 | 0.00 | 6470308.60 | 0.00 | 0.312219E+09 | 0.392666E+10 | 0.00 | 1.17 |
March | 0.436065E+10 | 11631.49 | 0.00 | 5603812.96 | 0.00 | 0.437530E+09 | 0.351934E+10 | 0.00 | 1.13 |
April | 0.277057E+10 | 118033.09 | 0.00 | 7025616.85 | 4765353.64 | 74474371.61 | 0.376812E+10 | 0.00 | 1.15 |
May | 0.328932E+10 | 1756173.81 | 0.00 | 4720040.02 | 0.00 | 39966992.11 | 0.266621E+10 | 0.00 | 1.01 |
June | 0.225715E+10 | 39218840.42 | 0.00 | 5835476.31 | 0.00 | 0.00 | 0.253044E+10 | 0.00 | 1.14 |
July | 0.135612E+10 | 0.676900E+09 | 0.00 | 4572444.83 | 38521177.40 | 0.00 | 0.133509E+10 | 0.00 | 1.19 |
August | 0.974601E+09 | 0.100092E+10 | 0.00 | 6125624.85 | 44562150.26 | 0.00 | 0.140811E+10 | 0.00 | 1.45 |
September | 0.143250E+10 | 0.348265E+09 | 0.00 | 9621673.21 | 16819572.73 | 0.00 | 0.331786E+10 | 0.00 | 1.41 |
October | 0.142357E+10 | 0.853228E+09 | 0.00 | 8358885.62 | 27897564.55 | 477479.32 | 0.252817E+10 | 0.00 | 1.37 |
November | 0.235222E+10 | 6287328.40 | 0.00 | 9819706.38 | 1521000.08 | 65982560.49 | 0.530999E+10 | 0.00 | 1.33 |
December | 0.262895E+10 | 6044058.07 | 0.00 | 10174315.60 | 0.00 | 0.189007E+09 | 0.448460E+10 | 0.00 | 1.30 |
Annual Sum or Average | 0.285396E+11 | 0.298127E+10 | 0.00 | 87833771.04 | 0.134087E+09 | 0.143900E+10 | 0.399954E+11 | 0.00 | 1.25 |
Minimum of Months | 0.974601E+09 | 11631.49 | 0.00 | 4572444.83 | 0.00 | 0.00 | 0.133509E+10 | 0.00 | 1.01 |
Maximum of Months | 0.436065E+10 | 0.100092E+10 | 0.00 | 10174315.60 | 44562150.26 | 0.437530E+09 | 0.530999E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.375101E+10 | 4551040.91 | 0.00 | 1185903.20 | 10279017.98 | 0.609836E+09 | 0.865086E+09 | 0.00 | 1.17 |
February | 0.373847E+10 | 1053139.57 | 0.00 | 1459915.52 | 0.00 | 0.343824E+09 | 0.112271E+10 | 0.00 | 1.23 |
March | 0.462017E+10 | 0.00 | 0.00 | 2234440.66 | 10456.08 | 0.355328E+09 | 0.172594E+10 | 0.00 | 1.35 |
April | 0.255825E+10 | 305127.91 | 0.00 | 5169840.78 | 4065966.34 | 45011426.99 | 0.316356E+10 | 0.00 | 1.51 |
May | 0.265161E+10 | 1118884.16 | 0.00 | 5144042.50 | 0.00 | 7489815.57 | 0.313859E+10 | 0.00 | 1.51 |
June | 0.144705E+10 | 29744424.92 | 0.00 | 7729125.02 | 0.00 | 0.00 | 0.342035E+10 | 0.00 | 1.80 |
July | 0.804156E+09 | 0.679171E+09 | 0.00 | 6791244.45 | 32511450.81 | 0.00 | 0.190359E+10 | 0.00 | 1.84 |
August | 0.688539E+09 | 0.771816E+09 | 0.00 | 6174623.26 | 38795331.51 | 0.00 | 0.145306E+10 | 0.00 | 1.94 |
September | 0.153020E+10 | 0.184028E+09 | 0.00 | 5315604.81 | 20017985.03 | 0.00 | 0.218336E+10 | 0.00 | 1.56 |
October | 0.186756E+10 | 0.349415E+09 | 0.00 | 2729787.59 | 73098245.02 | 1037039.66 | 0.102059E+10 | 0.00 | 1.33 |
November | 0.355799E+10 | 739219.40 | 0.00 | 2009053.84 | 3244513.36 | 0.147821E+09 | 0.129984E+10 | 0.00 | 1.23 |
December | 0.365550E+10 | 638607.24 | 0.00 | 1279210.50 | 1631690.25 | 0.423091E+09 | 0.762661E+09 | 0.00 | 1.17 |
Annual Sum or Average | 0.308705E+11 | 0.202258E+10 | 0.00 | 47222792.13 | 0.183655E+09 | 0.193344E+10 | 0.220593E+11 | 0.00 | 1.47 |
Minimum of Months | 0.688539E+09 | 0.00 | 0.00 | 1185903.20 | 0.00 | 0.00 | 0.762661E+09 | 0.00 | 1.17 |
Maximum of Months | 0.462017E+10 | 0.771816E+09 | 0.00 | 7729125.02 | 73098245.02 | 0.609836E+09 | 0.342035E+10 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3605843.26 | 0.00 | 0.00 | 0.333032E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7324633.31 | 0.00 | 0.00 | 0.293317E+09 | 0.00 | 0.29 |
March | 0.00 | 8393.27 | 0.00 | 13156804.16 | 0.00 | 0.00 | 0.340829E+09 | 0.00 | 0.31 |
April | 0.00 | 158512.19 | 0.00 | 16411205.53 | 0.00 | 0.00 | 0.202944E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3868114.56 | 0.00 | 0.00 | 0.247038E+09 | 0.00 | 0.29 |
June | 0.00 | 7422133.04 | 0.00 | 7372454.48 | 0.00 | 0.00 | 0.122206E+09 | 0.00 | 0.30 |
July | 0.00 | 58766526.24 | 0.00 | 4935027.45 | 0.00 | 0.00 | 27854700.86 | 0.00 | 0.28 |
August | 0.00 | 75987865.28 | 0.00 | 5438823.55 | 0.00 | 0.00 | 20011839.43 | 0.00 | 0.31 |
September | 0.00 | 13269212.04 | 0.00 | 2985024.77 | 0.00 | 0.00 | 96849752.85 | 0.00 | 0.29 |
October | 0.00 | 22302941.32 | 0.00 | 6141068.14 | 0.00 | 0.00 | 0.149653E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11889538.24 | 0.00 | 0.00 | 0.278160E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16430780.36 | 0.00 | 0.00 | 0.313501E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.177916E+09 | 0.00 | 99559317.81 | 0.00 | 0.00 | 0.242540E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2985024.77 | 0.00 | 0.00 | 20011839.43 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 75987865.28 | 0.00 | 16430780.36 | 0.00 | 0.00 | 0.340829E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 28296948.02 | 0.00 | 0.00 | 0.334779E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 64722180.52 | 0.00 | 0.00 | 0.294589E+10 | 0.00 | 0.29 |
March | 0.00 | 63986.23 | 0.00 | 0.119982E+09 | 0.00 | 0.00 | 0.341948E+10 | 0.00 | 0.31 |
April | 0.00 | 1571780.83 | 0.00 | 0.154048E+09 | 0.00 | 0.00 | 0.203772E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 33727369.15 | 0.00 | 0.00 | 0.249095E+10 | 0.00 | 0.29 |
June | 0.00 | 72509585.24 | 0.00 | 68620307.13 | 0.00 | 0.00 | 0.123287E+10 | 0.00 | 0.30 |
July | 0.00 | 0.583901E+09 | 0.00 | 46798400.28 | 0.00 | 0.00 | 0.281993E+09 | 0.00 | 0.28 |
August | 0.00 | 0.757463E+09 | 0.00 | 51827008.90 | 0.00 | 0.00 | 0.202571E+09 | 0.00 | 0.31 |
September | 0.00 | 0.125129E+09 | 0.00 | 26730430.67 | 0.00 | 0.00 | 0.989968E+09 | 0.00 | 0.29 |
October | 0.00 | 0.219768E+09 | 0.00 | 56138932.17 | 0.00 | 0.00 | 0.150324E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.109028E+09 | 0.00 | 0.00 | 0.279042E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.151332E+09 | 0.00 | 0.00 | 0.313879E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.176041E+10 | 0.00 | 0.911251E+09 | 0.00 | 0.00 | 0.243817E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26730430.67 | 0.00 | 0.00 | 0.202571E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.757463E+09 | 0.00 | 0.154048E+09 | 0.00 | 0.00 | 0.341948E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27235329.30 | 0.00 | 0.00 | 2095698.54 | 0.00 | 0.00 | 0.310547E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5856181.32 | 0.00 | 0.00 | 0.296059E+09 | 0.00 | 0.29 |
March | 0.00 | 6120.47 | 0.00 | 11375244.31 | 0.00 | 0.00 | 0.343118E+09 | 0.00 | 0.31 |
April | 0.00 | 155864.44 | 0.00 | 15125099.60 | 0.00 | 0.00 | 0.204384E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3106270.66 | 0.00 | 0.00 | 0.250381E+09 | 0.00 | 0.29 |
June | 0.00 | 7274206.14 | 0.00 | 6758999.86 | 0.00 | 0.00 | 0.123693E+09 | 0.00 | 0.30 |
July | 0.00 | 58318265.12 | 0.00 | 4657206.70 | 0.00 | 0.00 | 28332936.62 | 0.00 | 0.28 |
August | 0.00 | 75584390.53 | 0.00 | 5148376.16 | 0.00 | 0.00 | 20417298.17 | 0.00 | 0.31 |
September | 0.00 | 12316575.83 | 0.00 | 2523150.58 | 0.00 | 0.00 | 99795550.19 | 0.00 | 0.29 |
October | 0.00 | 21897807.23 | 0.00 | 5347109.63 | 0.00 | 0.00 | 0.150902E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10349466.36 | 0.00 | 0.00 | 0.280016E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14433002.63 | 0.00 | 0.00 | 0.314573E+09 | 0.00 | 0.28 |
Annual Sum or Average | 27235329.30 | 0.175553E+09 | 0.00 | 86775806.35 | 0.00 | 0.00 | 0.242222E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2095698.54 | 0.00 | 0.00 | 20417298.17 | 0.00 | 0.28 |
Maximum of Months | 27235329.30 | 75584390.53 | 0.00 | 15125099.60 | 0.00 | 0.00 | 0.343118E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.209158E+09 | 0.00 | 0.00 | 0.743756E+10 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.379981E+09 | 0.00 | 0.00 | 0.646113E+10 | 0.00 | 0.32 |
March | 0.00 | 1038470.64 | 0.00 | 0.661179E+09 | 0.00 | 0.00 | 0.705551E+10 | 0.00 | 0.34 |
April | 0.00 | 2078785.04 | 0.00 | 0.810547E+09 | 0.00 | 0.00 | 0.402347E+10 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.209949E+09 | 0.00 | 0.00 | 0.503828E+10 | 0.00 | 0.33 |
June | 0.00 | 0.203735E+09 | 0.00 | 0.358247E+09 | 0.00 | 0.00 | 0.233280E+10 | 0.00 | 0.34 |
July | 0.00 | 0.137912E+10 | 0.00 | 0.231192E+09 | 0.00 | 0.00 | 0.448077E+09 | 0.00 | 0.32 |
August | 0.00 | 0.149208E+10 | 0.00 | 0.236721E+09 | 0.00 | 0.00 | 0.308210E+09 | 0.00 | 0.35 |
September | 0.00 | 0.414621E+09 | 0.00 | 0.146217E+09 | 0.00 | 0.00 | 0.176693E+10 | 0.00 | 0.33 |
October | 0.00 | 0.506548E+09 | 0.00 | 0.308332E+09 | 0.00 | 0.00 | 0.319853E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.597913E+09 | 0.00 | 0.00 | 0.623182E+10 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.823573E+09 | 0.00 | 0.00 | 0.751932E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.399922E+10 | 0.00 | 0.497301E+10 | 0.00 | 0.00 | 0.518216E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146217E+09 | 0.00 | 0.00 | 0.308210E+09 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.149208E+10 | 0.00 | 0.823573E+09 | 0.00 | 0.00 | 0.751932E+10 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:55
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.340850E+12 | 0.156118E+11 | 0.00 | 0.208921E+13 | 0.853922E+12 |
February | 0.413706E+12 | 0.182977E+11 | 0.00 | 0.201739E+13 | 0.103578E+13 |
March | 0.570339E+12 | 0.189918E+11 | 0.00 | 0.216197E+13 | 0.154748E+13 |
April | 0.715878E+12 | 0.117197E+11 | 0.00 | 0.199831E+13 | 0.210118E+13 |
May | 0.752778E+12 | 0.140600E+11 | 0.00 | 0.207921E+13 | 0.997888E+12 |
June | 0.734711E+12 | 0.740125E+10 | 0.00 | 0.174434E+13 | 0.170124E+13 |
July | 0.785469E+12 | 0.359775E+10 | 0.00 | 0.114089E+13 | 0.267174E+13 |
August | 0.733668E+12 | 0.394290E+10 | 0.00 | 0.906405E+12 | 0.329136E+13 |
September | 0.573784E+12 | 0.615560E+10 | 0.00 | 0.155767E+13 | 0.146802E+13 |
October | 0.411046E+12 | 0.980989E+10 | 0.00 | 0.148350E+13 | 0.202769E+13 |
November | 0.370982E+12 | 0.154155E+11 | 0.00 | 0.217098E+13 | 0.163058E+13 |
December | 0.311031E+12 | 0.170313E+11 | 0.00 | 0.219548E+13 | 0.208763E+13 |
Annual Sum or Average | 0.671424E+13 | 0.142035E+12 | 0.00 | 0.215454E+14 | 0.214145E+14 |
Minimum of Months | 0.311031E+12 | 0.359775E+10 | 0.00 | 0.906405E+12 | 0.853922E+12 |
Maximum of Months | 0.785469E+12 | 0.189918E+11 | 0.00 | 0.219548E+13 | 0.329136E+13 |