Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 09:02:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 36677.09 | 791.81 | 791.81 |
Net Site Energy | 36677.09 | 791.81 | 791.81 |
Total Source Energy | 102575.17 | 2214.47 | 2214.47 |
Net Source Energy | 102575.17 | 2214.47 | 2214.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 5671.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3247.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 903.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2738.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 434.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 837.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3086.19 |
Humidification | 841.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.99 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 848.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30157.09 | 6520.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5679.35 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 5671.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3247.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 903.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2738.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 434.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 837.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3086.19 |
Humidification | General | 841.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.99 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 848.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 5671.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3247.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 903.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2738.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 434.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 837.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3086.19 |
Humidification | Unassigned | 841.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.99 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 848.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 174.88 | 140.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 651.05 | 140.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 174.88 | 140.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 651.05 | 140.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30157.088 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30157.088 | 100.00 |
Total On-Site and Utility Electric Sources | 30157.088 | 100.00 |
Total Electricity End Uses | 30157.088 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5679.35 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5679.35 | 100.00 |
Total Water End Uses | 5679.35 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 113.17 |
Time Setpoint Not Met During Occupied Cooling | 485.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5942.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.1390 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.1390 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1390 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.1390 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.1390 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.1390 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.1390 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8180 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:30 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 17-JUL-15:00 |
Heating | 0.00 | 3008975.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 476400.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 86589.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 277580.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 65860.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83442.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16074.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33067.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2144185.78 | 3042043.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3008975.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 476400.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 277580.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 65860.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 83442.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 16074.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33067.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 6148.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10284.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2860.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6326.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8673.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1377.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2653.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2664.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 919.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 95507.50 | 7067.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 57.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2061.89 | 152.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 57.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2061.89 | 152.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.42 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.564620 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.40 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.550025 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.46 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.75 | 0.281949 | 0.300000 | 2.02 | 0.751865 | 0.500000 | 0.001351 | 0.000235 | 2.02 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 63.39 | 0.300031 | 0.300000 | 19.02 | 0.800083 | 0.500000 | 0.001270 | 0.004534 | 19.02 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.14 | 0.310016 | 0.300000 | 1.84 | 0.826710 | 0.500000 | 0.001229 | 0.001000 | 3.89 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.08 | 0.221837 | 0.300000 | 0.322967 | 0.591566 | 0.500000 | 0.001717 | 0.000174 | 0.679405 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.34 | 0.115112 | 0.300000 | 0.401102 | 0.306965 | 0.500000 | 0.003310 | 0.000120 | 0.466446 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.69 | 0.141219 | 0.300000 | 0.507351 | 0.376584 | 0.500000 | 0.002698 | 0.000192 | 0.747402 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.67 | 0.092377 | 0.300000 | 0.499814 | 0.300000 | 0.500000 | 0.004124 | 0.000108 | 0.499814 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.13 | 0.235729 | 0.300000 | 3.04 | 0.628610 | 0.500000 | 0.001616 | 0.002496 | 9.73 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.07 | 0.109422 | 0.300000 | 4.22 | 0.300000 | 0.500000 | 0.003482 | 0.001655 | 6.46 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 17.01 | 0.140391 | 0.300000 | 5.10 | 0.374377 | 0.500000 | 0.002714 | 0.002526 | 9.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.10 | 0.101933 | 0.300000 | 4.53 | 0.300000 | 0.500000 | 0.003738 | 0.001622 | 6.33 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.28 | 0.186008 | 0.300000 | 0.385177 | 0.496022 | 0.500000 | 0.002048 | 0.000329 | 1.28 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.41 | 0.109139 | 0.300000 | 0.423052 | 0.300000 | 0.500000 | 0.003491 | 0.000217 | 0.847139 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.84 | 0.130102 | 0.300000 | 0.550703 | 0.346939 | 0.500000 | 0.002928 | 0.000333 | 1.30 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.61 | 0.095740 | 0.300000 | 0.482259 | 0.300000 | 0.500000 | 0.003980 | 0.000217 | 0.845030 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26868.26 | 0.000235 | 570.16 |
CORE_MID VAV BOX REHEAT COIL | 518248.16 | 0.004534 | 13242.68 |
CORE_TOP VAV BOX REHEAT COIL | 114310.89 | 0.001000 | 3016.10 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19921.41 | 0.000174 | 525.39 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13675.36 | 0.000120 | 360.64 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21911.67 | 0.000192 | 577.83 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12346.71 | 0.000108 | 303.95 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 285251.84 | 0.002496 | 7520.59 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 189222.60 | 0.001655 | 4988.71 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 288704.02 | 0.002526 | 7611.56 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 185387.20 | 0.001622 | 4887.64 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 37609.66 | 0.000329 | 991.43 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24814.38 | 0.000217 | 654.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38037.39 | 0.000333 | 1002.70 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24752.52 | 0.000217 | 652.49 |
VAV_BOT WITH REHEAT HEATING COIL | 100624.94 | 0.000880 | 1540.99 |
VAV_MID WITH REHEAT HEATING COIL | 1087733.29 | 0.009516 | 15999.52 |
VAV_TOP WITH REHEAT HEATING COIL | 113866.20 | 0.000996 | 1704.28 |
CAV_BAS HEATING COIL | 306811.68 | 0.002684 | 6559.52 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.26 | 3.76 | 12.52 | 3.76 | 10.86 | 10.86 | 0.300000 | 0.345837 | 10.86 |
VAV_MID WITH REHEAT | 59.85 | 35.91 | 119.70 | 49.36 | 100.56 | 100.56 | 0.300000 | 0.490834 | 100.56 |
VAV_TOP WITH REHEAT | 6.14 | 3.68 | 12.27 | 8.17 | 11.24 | 11.24 | 0.300000 | 0.726914 | 11.24 |
CAV_BAS | 6.42 | 6.42 | 6.42 | 6.42 | 6.42 | 6.42 | 1.00 | 1.00 | 6.42 |
AIRLOOP DATACENTER BASEMENT | 24.46 | 24.46 | 24.46 | 24.46 | 24.46 | 24.46 | 1.00 | 0.999991 | 24.46 |
AIRLOOP DATACENTER BOT | 0.564620 | 0.564620 | 0.564620 | 0.564620 | 0.564620 | 0.564620 | 1.00 | 1.00 | 0.564620 |
AIRLOOP DATACENTER MID | 5.40 | 5.40 | 5.40 | 5.40 | 5.40 | 5.40 | 1.00 | 1.00 | 5.40 |
AIRLOOP DATACENTER TOP | 0.550025 | 0.550025 | 0.550025 | 0.550025 | 0.550025 | 0.550025 | 1.00 | 1.00 | 0.550025 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.86 | 2.51 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.56 | 26.05 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.24 | 2.77 |
CAV_BAS_OA_CONTROLLER | 6.42 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.46 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.564620 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.40 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.550025 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.21 | 6.67 | 10.68 | 0.007087 | 0.007000 | 183273.83 | 0.007797 | 10.86 |
VAV_MID WITH REHEAT COOLING COIL | 26.52 | 6.67 | 10.68 | 0.007069 | 0.007000 | 1725379.89 | 0.073402 | 100.56 |
VAV_TOP WITH REHEAT COOLING COIL | 26.32 | 6.67 | 10.68 | 0.007053 | 0.007000 | 190044.12 | 0.008085 | 11.24 |
CAV_BAS COOLING COIL | 25.81 | 6.67 | 11.09 | 0.007243 | 0.007000 | 105528.98 | 0.004489 | 6.42 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.86 |
VAV_MID WITH REHEAT FAN | 100.56 |
VAV_TOP WITH REHEAT FAN | 11.24 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007797 | 0.000061 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000880 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073402 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009516 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008085 | 0.000059 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000996 | |
CAV_BAS_COOLC_CONTROLLER | 0.004489 | 0.000106 |
CAV_BAS_HEATC_CONTROLLER | 0.002684 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.42 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.46 | 464992.53 | 261685.82 | 0.011388 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.564620 | 10430.86 | 5931.89 | 0.000255 |
AIRLOOP DATACENTER MID COOLING COIL | 5.40 | 99842.12 | 56766.72 | 0.002445 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.550025 | 10163.31 | 5778.98 | 0.000249 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.46 | 24.46 | 24.46 | 24.46 | 464992.53 | 464992.53 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.564620 | 0.564620 | 0.564620 | 0.564620 | 10430.86 | 10430.86 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.40 | 5.40 | 5.40 | 5.40 | 99842.12 | 99842.12 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.550025 | 0.550025 | 0.550025 | 0.550025 | 10163.31 | 10163.31 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.46 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.564620 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.40 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.550025 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.46 | 464992.53 | 0.011388 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.564620 | 10430.86 | 0.000255 |
AIRLOOP DATACENTER MID HEATING COIL | 5.40 | 99842.12 | 0.002445 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.550025 | 10163.31 | 0.000249 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000190 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.093773 | 19323.12 | |
HEATSYS1 PUMP | 0.029833 | 8984.40 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.093773 | 11.25 |
HEATSYS1 | 0.029833 | 3.58 |
COOLSYS1_SUPPLY | 0.093773 | 11.25 |
SINGLE WATER PLANT LOOP | 0.014337 | 1.72 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.093773 | 0.093773 | 393611.93 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3410098.20 | 3410098.20 | 0.029833 |
CENTRAL BOILER | 590566.19 | 577839.35 | 0.014337 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.093773 | 13378.05 |
PLANT CIRC PUMP | 0.014337 | 3656.68 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.093773 | 0.047217 | 1112603.77 | 1117881.23 | 0.055531 |
COOLSYS1 CHILLER2 | 0.093773 | 0.047217 | 1112603.77 | 1117881.23 | 0.055531 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014337 | 139666.47 | 55731.90 | 69833.23 | 7879.72 | 21042.59 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.111062 | 13.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.111062 | 33449.59 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 51.45 | 1328003.32 | 10.29 | 166000.41 |
TOWERWATERSYS COOLTOWER 2 | 51.45 | 1328003.32 | 10.29 | 166000.41 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.057460 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.139 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.981 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.139 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.562 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25401.240 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25401.240 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7162.063 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7162.063 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.132 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.057 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.468 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7163 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7788 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5137 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.13403145E-14 | 0.38554392E-16 | -0.14019045E-09 | -0.57508437E-17 |
51 | 8 | 0.20532604E-07 | 0.15070655E-12 | 0.36354762E-03 | -0.23346278E-09 |
52 | 7 | -0.11816003E-01 | 0.79423826E-08 | -0.22472937E-01 | 0.13435225E-03 |
53 | 6 | 0.39378663 | 0.27841024E-05 | 0.46223068 | -0.46114540E-02 |
54 | 5 | -5.0777070 | 0.10463539E-03 | -4.3654760 | 0.61784485E-01 |
55 | 4 | 32.503611 | 0.86100720E-03 | 21.143998 | -0.41549437 |
56 | 3 | -110.16389 | 0.18863771E-02 | -55.038103 | 1.4998468 |
57 | 2 | 196.07818 | 0.10660615E-02 | 77.337676 | -2.8839958 |
58 | 1 | -170.77553 | 0.11429885E-03 | -55.098892 | 2.7387699 |
59 | 0 | 57.057407 | 0.65377189E-06 | 15.584712 | |
60 | 9 | -0.15090952E-15 | 0.38559946E-16 | -0.14372032E-09 | 0.30204083E-17 |
61 | 8 | 0.21031043E-07 | 0.14138600E-12 | 0.36887497E-03 | -0.23913020E-09 |
62 | 7 | -0.11975277E-01 | 0.74086432E-08 | -0.22702364E-01 | 0.13616326E-03 |
63 | 6 | 0.39811484 | 0.25910953E-05 | 0.46592450 | -0.46624730E-02 |
64 | 5 | -5.1199506 | 0.97191092E-04 | -4.3938804 | 0.62308282E-01 |
65 | 4 | 32.690498 | 0.79834332E-03 | 21.255101 | -0.41797567 |
66 | 3 | -110.56161 | 0.17463541E-02 | -55.257788 | 1.5055927 |
67 | 2 | 196.47247 | 0.98555898E-03 | 77.539021 | -2.8902570 |
68 | 1 | -170.92122 | 0.10553222E-03 | -55.157180 | 2.7413232 |
69 | 0 | 57.057407 | 0.60276357E-06 | 15.574872 | |
70 | 9 | 0.86852889E-15 | 0.51837175E-16 | -0.12412508E-09 | -0.62404215E-17 |
71 | 8 | 0.18264368E-07 | 0.19079871E-12 | 0.33872361E-03 | -0.20767217E-09 |
72 | 7 | -0.11071833E-01 | 0.10339392E-07 | -0.21400306E-01 | 0.12589076E-03 |
73 | 6 | 0.37356127 | 0.36650528E-05 | 0.44491930 | -0.43730477E-02 |
74 | 5 | -4.8802711 | 0.13907014E-03 | -4.2321352 | 0.59336424E-01 |
75 | 4 | 31.629927 | 0.11542129E-02 | 20.621944 | -0.40389484 |
76 | 3 | -108.30396 | 0.25479898E-02 | -54.005619 | 1.4729777 |
77 | 2 | 194.23353 | 0.14496506E-02 | 76.392304 | -2.8547049 |
78 | 1 | -170.09368 | 0.15639004E-03 | -54.826917 | 2.7268196 |
79 | 0 | 57.057407 | 0.90049143E-06 | 15.632017 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77734.26176 | 77734.26176 | 6.41994 | 6.41994 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81690.28724 | 81690.28724 | 6.74605 | 6.74605 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 9046.60604 | 9046.60604 | 0.43772 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 767846.42320 | 767846.42320 | 63.39486 | 63.39486 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 350772.16234 | 350772.16234 | 16.98417 | 16.98417 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 74316.21799 | 74316.21799 | 6.13530 | 6.13530 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 80015.37239 | 80015.37239 | 3.89458 | 3.89458 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12923.61332 | 12923.61332 | 1.07656 | 1.07656 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13941.81357 | 13941.81357 | 0.67941 | 0.67941 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16050.32941 | 16050.32941 | 1.33701 | 1.33701 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9569.96367 | 9569.96367 | 0.46645 | 0.46645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20301.89060 | 20301.89060 | 1.69117 | 1.69117 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15333.21178 | 15333.21178 | 0.74740 | 0.74740 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20000.40897 | 20000.40897 | 1.66605 | 1.66605 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7948.46912 | 7948.46912 | 0.38717 | 0.38717 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 121621.55872 | 121621.55872 | 10.13116 | 10.13116 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 199600.44822 | 199600.44822 | 9.73489 | 9.73489 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 168850.87456 | 168850.87456 | 14.06527 | 14.06527 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 132403.62029 | 132403.62029 | 6.45793 | 6.45793 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 204218.06836 | 204218.06836 | 17.01144 | 17.01144 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 202014.07413 | 202014.07413 | 9.85285 | 9.85285 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 181256.07217 | 181256.07217 | 15.09864 | 15.09864 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 129721.79218 | 129721.79218 | 6.32691 | 6.32691 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13852.39605 | 13852.39605 | 1.15391 | 1.15391 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 26313.23705 | 26313.23705 | 1.28392 | 1.28392 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16928.91541 | 16928.91541 | 1.41017 | 1.41017 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17361.04710 | 17361.04710 | 0.84714 | 0.84714 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22036.96753 | 22036.96753 | 1.83568 | 1.83568 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 26612.30622 | 26612.30622 | 1.29854 | 1.29854 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19298.14147 | 19298.14147 | 1.60753 | 1.60753 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 17317.75698 | 17317.75698 | 0.84503 | 0.84503 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8593.43284 | 8593.43284 | 0.56462 | 0.56462 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 82226.56401 | 82226.56401 | 5.40262 | 5.40262 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8371.25934 | 8371.25934 | 0.55002 | 0.55002 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.57333 | 6.29632E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372312.11499 | 372312.11499 | 24.46196 | 24.46196 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:20:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 151240.75 | 10.85785 | 10.85785 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 106928.19 | 3.35825 | 3.35825 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1411894.46 | 100.55697 | 100.55697 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1108519.27 | 49.35675 | 49.35675 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 160266.96 | 11.23820 | 11.23820 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 118096.35 | 8.16921 | 8.16921 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 78394.65 | 6.41994 | 6.41994 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369378.91 | 24.46219 | 24.46219 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8472.07 | 0.56462 | 0.56462 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 81059.37 | 5.40262 | 5.40262 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8257.36 | 0.55002 | 0.55002 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.41994 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.74605 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28195 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02382 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75186 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35131E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.35055E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.02382 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26868.26419 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35055E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 570.16425 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 63.39486 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30003 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.01846 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80008 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26987E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.53386E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.01846 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 518248.15676 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53386E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13242.68484 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.13530 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31002 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.84059 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82671 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22897E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00004E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.89458 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114310.89202 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00004E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3016.09562 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07656 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22184 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32297 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59157 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71748E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74281E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67941 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19921.40865 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74281E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 525.38526 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33701 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11511 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40110 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30696 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30983E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.19638E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46645 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13675.36324 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19638E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 360.63846 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69117 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14122 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50735 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37658 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69793E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91693E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74740 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21911.66933 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91693E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.83145 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66605 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.23773E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49981 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.12439E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08014E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49981 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12346.70640 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08014E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.94549 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.13116 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23573 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.03935 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62861 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61626E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.49551E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.73489 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 285251.83801 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.49551E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7520.59249 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.06527 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10942 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.21958 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48193E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65540E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.45793 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 189222.60353 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65540E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4988.71263 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.01144 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14039 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.10343 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37438 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71384E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.52571E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.85285 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 288704.01805 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52571E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7611.55591 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.09864 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10193 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.52959 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.73775E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62185E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.32691 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 185387.20177 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62185E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4887.63798 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28392 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18601 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38518 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49602 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04830E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29026E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28392 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37609.65682 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29026E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 991.42581 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41017 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10914 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42305 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49095E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17087E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84714 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24814.38462 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17087E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 654.12259 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.83568 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13010 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55070 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34694 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92847E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32768E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29854 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38037.39215 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32768E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1002.69664 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60753 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.57402E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48226 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97952E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.16546E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84503 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24752.51948 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16546E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 652.49089 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56462 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.40262 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55002 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.46196 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.25842 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.75505 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.51683 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.75505 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.85785 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.85785 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34584 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.85068 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 35.91041 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 119.70137 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 49.35675 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.55697 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.55697 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49083 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.13630 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.68178 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.27260 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 8.16921 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.23820 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.23820 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.72691 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.41994 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.41994 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.41994 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.41994 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.41994 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.41994 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.46196 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.46196 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.46196 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.46196 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.46219 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.46219 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56462 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56462 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56462 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56462 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56462 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.56462 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.40262 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.40262 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.40262 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.40262 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.40262 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.40262 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55002 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55002 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55002 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55002 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55002 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.55002 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.85785 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.55697 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.23820 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.41994 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.46219 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.56462 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.40262 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.55002 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.85785 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.50608 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.20937 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68120 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08718E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 183273.83040 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.79689E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.85785 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 100624.94488 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.80311E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1540.98634 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.85785 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.79689E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.10744E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.80311E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.55697 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 26.04512 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.51607 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68113 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.06855E-003 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1725379.88709 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.34016E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.55697 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1087733.29347 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.51597E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15999.52356 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.55697 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.34016E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.48746E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.51597E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.23820 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.76931 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.32370 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68107 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.05309E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 190044.12238 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.08492E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.23820 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 113866.20461 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.96151E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1704.28059 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.23820 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.08492E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.88986E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.96151E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.41994 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.81181 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08693 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24345E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 105528.97885 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.48945E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.41994 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 306811.68402 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.68412E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6559.51887 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.41994 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48945E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.06069E-004 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.68412E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.46219 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.46219 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 464992.52754 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 261685.82449 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13876E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.46219 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.46219 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.46219 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.46219 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 464992.52754 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 464992.52754 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.46219 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.46219 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 464992.52754 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13876E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.90481E-004 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56462 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56462 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10430.86373 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5931.89024 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.55451E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56462 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56462 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56462 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56462 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10430.86373 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10430.86373 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56462 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56462 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10430.86373 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.55451E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.40262 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.40262 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 99842.11851 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 56766.71986 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44513E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.40262 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.40262 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.40262 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.40262 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 99842.11851 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 99842.11851 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.40262 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.40262 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 99842.11851 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44513E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55002 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10163.31163 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5778.97971 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48899E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55002 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55002 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55002 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55002 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10163.31163 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10163.31163 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55002 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55002 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10163.31163 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48899E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.37729E-002 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 19323.12004 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.37729E-002 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.25275 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.37729E-002 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.37729E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 393611.93191 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.98330E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.57996 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.98330E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8984.39752 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3410098.20200 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3410098.20000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.98330E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.37729E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.25275 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.37729E-002 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13378.04782 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.37729E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.72168E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1112603.77213 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1117881.23000 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.55312E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.37729E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.72168E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1112603.77213 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1117881.23000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.55312E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.43371E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.72045 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.43371E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3656.68107 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.43371E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55731.89894 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21042.59405 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 590566.19050 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 577839.35000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.43371E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11106 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.32749 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11106 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33449.59232 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 51.44999 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1328003.31862 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.29000 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 166000.41483 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 51.44999 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1328003.31862 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.29000 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 166000.41483 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.74600E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.74600E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 25472.78 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 490961.26 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108340.07 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18879.22 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12959.80 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20765.07 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11698.05 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 270313.19 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 179312.38 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 273584.23 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 175678.14 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35639.07 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23514.16 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36044.36 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23455.53 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 67231.24 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 692551.98 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 74040.47 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 231818.43 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 306577.93 | 188195.96 | 118381.97 | 0.61 | 60730.23 | 615.96 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2851151.06 | 1747604.35 | 1103546.71 | 0.61 | 556147.33 | 5640.75 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 317321.51 | 194787.97 | 122533.53 | 0.61 | 62616.79 | 635.09 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 176484.70 | 109338.67 | 67146.03 | 0.62 | 32869.79 | 333.38 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.132 | 0.968 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.057 | 0.913 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.468 | 1.204 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2682970549 | 0.2062433537 | Pass | Pass | 5.3039811861 | 16.8461679681 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.7631101362E-002 | 0.1234143227 | Pass | Pass | 4.9521545938E-002 | 0.2158024786 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.1819386399E-003 | 4.4867703598E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4636416529E-002 | 2.5607381975E-002 | Pass | Pass | 0.5157456752 | 0.4941917390 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.5628708249E-002 | 8.7713212907E-002 | Pass | Pass | 4.9251088785E-002 | 0.2145313808 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.8132448117E-002 | 0.1783916492 | Pass | Pass | 5.0055021410E-002 | 0.2176738736 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1475670689 | 0.2115005507 | Pass | Pass | 4.9831854794E-002 | 0.2170164824 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.9332086524E-002 | 0.2075590799 | Pass | Pass | 4.8851317874E-002 | 0.2129635548 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5459689789E-002 | 2.5224495026E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.8153533182E-002 | 7.0288590022E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1261405886 | 0.1211397473 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.0678331948E-002 | 5.3941280034E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3402578637 | 0.3538616175 | Pass | Pass | 6.4416502091 | 18.3670545428 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2338422443 | 0.3300664102 | Pass | Pass | 7.8393122200 | 26.8831421369 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2327267458 | 0.2347643155 | Pass | Pass | 1.0101832974 | 2.9028289440 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1994513094 | 0.2594152889 | Pass | Pass | 5.3761032743 | 26.0523765500 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4007449197E-002 | 2.2650209912E-002 | Pass | Pass | 1.0324548387 | 7.5040287280 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1198505589E-002 | 1.2840191595E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1136750036 | 8.2871047869E-002 | Pass | Pass | 0.5238261570 | 0.4808271245 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0727542664E-006 | 5.0614240590E-006 | Pass | Pass | 4.1383882072E-003 | 3.8582895009E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1367742577E-003 | 6.8513315476E-003 | Pass | Pass | 5.9978743273E-002 | 0.1789162139 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5501731710E-002 | 1.9898750053E-002 | Pass | Pass | 4.5380103475E-003 | 4.5151993146E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.1975825311E-005 | 7.4935083239E-005 | Pass | Pass | 4.5306926868E-005 | 1.0640075130E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7022.73 | 302.84 | 0.00 | 22958.96 | 20481.65 | 50766.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.968 | 1.132 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.913 | 1.057 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.204 | 1.468 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1390 | 2779.43 | 25401.24 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 235.63 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.1390 | 24961.20 | 228120.99 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 2116.09 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.1390 | 3134.13 | 28642.87 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.1390 | 3134.20 | 28643.49 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.1390 | 783.68 | 7162.06 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 66.44 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 11.7111 | 362.03 | 4239.75 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 43.70 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
Interior Lighting Total | 9.1631 | 46320.38 | 424440.34 | 1212.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 57580.60 | AstronomicalClock | - | 83.57 | 83.57 | 903.27 | |
Exterior Lighting Total | 57580.60 | 903.27 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2199157.75 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3410098.20 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1117881.23 | 6.11 | 1069205.87 | 5.82 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1117881.23 | 6.11 | 1069205.87 | 5.82 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 577839.35 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1328003.32 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1328003.32 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 183273.83 | 306577.93 | 188195.96 | 118381.97 | 0.61 | - | 60730.23 | 615.96 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1725379.89 | 2851151.06 | 1747604.35 | 1103546.71 | 0.61 | - | 556147.33 | 5640.75 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 190044.12 | 317321.51 | 194787.97 | 122533.53 | 0.61 | - | 62616.79 | 635.09 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 105528.98 | 176484.70 | 109338.67 | 67146.03 | 0.62 | - | 32869.79 | 333.38 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 464992.53 | 261685.82 | 203306.70 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10430.86 | 5931.89 | 4498.97 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 99842.12 | 56766.72 | 43075.40 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10163.31 | 5778.98 | 4384.33 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 26868.26 | 25472.78 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 518248.16 | 490961.26 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114310.89 | 108340.07 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19921.41 | 18879.22 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13675.36 | 12959.80 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21911.67 | 20765.07 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12346.71 | 11698.05 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 285251.84 | 270313.19 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 189222.60 | 179312.38 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 288704.02 | 273584.23 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 185387.20 | 175678.14 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37609.66 | 35639.07 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24814.38 | 23514.16 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38037.39 | 36044.36 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24752.52 | 23455.53 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 100624.94 | 67231.24 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1087733.29 | 692551.98 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 113866.20 | 74040.47 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 306811.68 | 231818.43 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 464992.53 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10430.86 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 99842.12 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10163.31 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.86 | 24664.63 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 100.56 | 228424.53 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.24 | 25528.63 | 2271.59 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 6.42 | 11794.21 | 1837.12 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.46 | 40344.20 | 1649.25 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 632.44 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.40 | 6051.52 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 616.09 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.093773 | 19323.12 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.029833 | 8984.40 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.093773 | 13378.05 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014337 | 3656.68 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.111062 | 33449.59 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77734.26 | 77734.26 | 27.97 | 6.420 | 6.420 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00745 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 81690.29 | 81690.29 | 32.73 | 6.746 | 6.746 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 767846.42 | 767846.42 | 307.62 | 63.395 | 63.395 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 74316.22 | 74316.22 | 29.77 | 6.135 | 6.135 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12923.61 | 12923.61 | 41.24 | 1.077 | 1.077 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00727 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16050.33 | 16050.33 | 79.47 | 1.337 | 1.337 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00714 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20301.89 | 20301.89 | 64.78 | 1.691 | 1.691 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00717 | 33.13 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20000.41 | 20000.41 | 99.02 | 1.666 | 1.666 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 121621.56 | 121621.56 | 388.06 | 10.131 | 10.131 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00725 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 168850.87 | 168850.87 | 836.00 | 14.065 | 14.065 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 25.96 | 0.00630 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 204218.07 | 204218.07 | 651.58 | 17.011 | 17.011 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00715 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 181256.07 | 181256.07 | 897.42 | 15.099 | 15.099 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13852.40 | 13852.40 | 44.20 | 1.154 | 1.154 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00721 | 33.08 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16928.92 | 16928.92 | 83.82 | 1.410 | 1.410 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00711 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22036.97 | 22036.97 | 70.31 | 1.836 | 1.836 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00714 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19298.14 | 19298.14 | 95.55 | 1.608 | 1.608 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8593.43 | 8593.43 | 237.37 | 0.565 | 0.565 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 82226.56 | 82226.56 | 2271.28 | 5.403 | 5.403 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8371.26 | 8371.26 | 231.23 | 0.550 | 0.550 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00709 | 26.57 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372312.11 | 372312.11 | 475.08 | 24.462 | 24.462 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.71 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 9046.61 | 9046.61 | 3.62 | 0.438 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 350772.16 | 350772.16 | 140.53 | 16.984 | 16.984 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 80015.37 | 80015.37 | 32.06 | 3.895 | 3.895 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13941.81 | 13941.81 | 44.48 | 0.679 | 0.679 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9569.96 | 9569.96 | 47.38 | 0.466 | 0.466 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15333.21 | 15333.21 | 48.92 | 0.747 | 0.747 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7948.47 | 7948.47 | 39.35 | 0.387 | 0.387 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 199600.45 | 199600.45 | 636.86 | 9.735 | 9.735 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 132403.62 | 132403.62 | 655.54 | 6.458 | 6.458 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 202014.07 | 202014.07 | 644.55 | 9.853 | 9.853 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 129721.79 | 129721.79 | 642.27 | 6.327 | 6.327 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 26313.24 | 26313.24 | 83.96 | 1.284 | 1.284 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17361.05 | 17361.05 | 85.96 | 0.847 | 0.847 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26612.31 | 26612.31 | 84.91 | 1.299 | 1.299 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17317.76 | 17317.76 | 85.74 | 0.845 | 0.845 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.22 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.24 | 0.00098 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.69 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:20:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.86 | 10.86 | 3.36 | 3.36 | 10.8579 | 3.7551 | 10.8579 | 0.3458 | 0.3000 |
VAV_MID WITH REHEAT | 100.56 | 100.56 | 49.36 | 49.36 | 100.5570 | 49.3568 | 100.5570 | 0.4908 | 0.3000 |
VAV_TOP WITH REHEAT | 11.24 | 11.24 | 8.17 | 8.17 | 11.2382 | 8.1692 | 11.2382 | 0.7269 | 0.3000 |
CAV_BAS | 6.42 | 6.42 | 1.20 | 1.20 | 6.4199 | 6.4199 | 6.4199 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.46 | 24.46 | 0.34 | 0.34 | 24.4622 | 24.4620 | 24.4622 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.56 | 0.56 | 0.02 | 0.02 | 0.5646 | 0.5646 | 0.5646 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.40 | 5.40 | 0.16 | 0.16 | 5.4026 | 5.4026 | 5.4026 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.55 | 0.55 | 0.02 | 0.02 | 0.5500 | 0.5500 | 0.5500 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26868.264 | 26868.264 | 2.023815 | 0.00023506 | 570.164 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26868.26 | 26868.26 | 2.023815 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799998 | 45.2309 | 9046.61 | 0.00 | 26963.05 | 26963.05 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 518248.157 | 518248.157 | 19.018458 | 0.00453386 | 13242.685 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 518248.16 | 518248.16 | 19.018458 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 350772.16 | 0.00 | 519845.86 | 519845.86 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114310.892 | 114310.892 | 3.894575 | 0.00100004 | 3016.096 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114310.89 | 114310.89 | 3.894575 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 80015.37 | 0.00 | 114696.12 | 114696.12 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19921.409 | 19921.409 | 0.679405 | 0.00017428 | 525.385 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19921.41 | 19921.41 | 0.679405 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00777109 | 43.9554 | 13941.81 | 0.00 | 19986.81 | 19986.81 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13675.363 | 13675.363 | 0.466446 | 0.00011964 | 360.638 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13675.36 | 13675.36 | 0.466446 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00778325 | 44.0233 | 9569.96 | 0.00 | 13720.11 | 13720.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21911.669 | 21911.669 | 0.747402 | 0.00019169 | 577.831 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21911.67 | 21911.67 | 0.747402 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00779929 | 44.1127 | 15333.21 | 0.00 | 21983.29 | 21983.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12346.706 | 12346.706 | 0.499814 | 0.00010801 | 303.945 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12346.71 | 12346.71 | 0.499814 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00769762 | 43.5457 | 7948.47 | 0.00 | 12385.54 | 12385.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 285251.838 | 285251.838 | 9.734888 | 0.00249551 | 7520.592 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 285251.84 | 285251.84 | 9.734888 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765620 | 43.3159 | 199600.45 | 0.00 | 286171.48 | 286171.48 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 189222.604 | 189222.604 | 6.457930 | 0.00165540 | 4988.713 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 189222.60 | 189222.60 | 6.457930 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765483 | 43.3084 | 132403.62 | 0.00 | 189831.98 | 189831.98 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 288704.018 | 288704.018 | 9.852850 | 0.00252571 | 7611.556 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 288704.02 | 288704.02 | 9.852850 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00766025 | 43.3385 | 202014.07 | 0.00 | 289634.41 | 289634.41 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 185387.202 | 185387.202 | 6.326911 | 0.00162185 | 4887.638 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 185387.20 | 185387.20 | 6.326911 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764787 | 43.2695 | 129721.79 | 0.00 | 185984.53 | 185984.53 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 37609.657 | 37609.657 | 1.283924 | 0.00032903 | 991.426 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37609.66 | 37503.48 | 1.283924 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767579 | 43.4262 | 26313.24 | 0.00 | 37729.87 | 37729.87 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24814.385 | 24814.385 | 0.847139 | 0.00021709 | 654.123 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24814.38 | 24814.38 | 0.847139 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767247 | 43.4078 | 17361.05 | 0.00 | 24893.65 | 24893.65 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 38037.392 | 38037.392 | 1.298539 | 0.00033277 | 1002.697 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38037.39 | 38037.39 | 1.298539 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767927 | 43.4457 | 26612.31 | 0.00 | 38158.94 | 38158.94 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24752.519 | 24752.519 | 0.845030 | 0.00021655 | 652.491 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24752.52 | 24752.52 | 0.845030 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767190 | 43.4047 | 17317.76 | 0.00 | 24831.58 | 24831.58 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 183273.830 | -999.000 | 10.857854 | 0.00779689 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 183273.83 | 181238.05 | 10.857854 | 26.21 | 14.59 | 0.00708718 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 23.0808 | 24.00 | 0.00732708 | 34.5623 | 127941.30 | 0.00 | 206597.82 | 203529.67 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 100624.945 | 100624.945 | 3.257356 | 0.00088031 | 1540.986 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100624.94 | 100624.94 | 3.257356 | -16.39 | -16.39 | 0.00206690 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 76.9360 | 19.41 | 0.00772474 | 48.1954 | 33568.16 | 0.00 | 81310.18 | 81310.18 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1725379.887 | -999.000 | 100.556968 | 0.07340165 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1725379.89 | 1710503.99 | 100.556968 | 26.52 | 14.69 | 0.00706855 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 25.9009 | 24.00 | 0.00734708 | 34.6554 | 1167681.85 | 0.00 | 1941965.12 | 1918087.50 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1087733.293 | 1087733.293 | 30.167091 | 0.00951597 | 15999.524 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1087733.29 | 1087733.29 | 30.167091 | -21.27 | -21.27 | 0.00133142 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 86.3362 | 17.81 | 0.00756926 | 52.2232 | 393184.49 | 0.00 | 837237.44 | 837237.44 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 190044.122 | -999.000 | 11.238205 | 0.00808492 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 190044.12 | 188760.44 | 11.238205 | 26.32 | 14.61 | 0.00705309 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 24.6419 | 24.00 | 0.00729826 | 34.4278 | 134431.73 | 0.00 | 214186.74 | 212020.38 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 113866.205 | 113866.205 | 3.371461 | 0.00099615 | 1704.281 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113866.20 | 113866.20 | 3.371461 | -19.11 | -19.11 | 0.00162904 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 82.1398 | 16.98 | 0.00753938 | 54.8331 | 57030.40 | 0.00 | 89524.83 | 89524.83 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 105528.979 | -999.000 | 6.419937 | 0.00448945 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 105528.98 | 102255.54 | 6.419937 | 25.81 | 14.59 | 0.00724345 | 11.09 | 8.68 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 18.6942 | 24.00 | 0.00749396 | 35.3405 | 68342.71 | 0.00 | 119059.31 | 116192.07 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 306811.684 | 306811.684 | 6.419937 | 0.00268412 | 6559.519 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 306811.68 | 306811.68 | 6.419937 | -5.16 | -9.55 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 18.6942 | 22.83 | 0.00034190 | 1.7505 | 0.00 | 0.00 | 244517.09 | 244517.09 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 464992.528 | 261685.824 | 24.462192 | 0.01138764 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 404049.62 | 402578.36 | -999.0 | 28.68 | 15.39 | 0.00703191 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704209 | 27.8119 | 371832.90 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10430.864 | 5931.890 | 0.564620 | 0.00025545 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9015.76 | 8950.35 | -999.0 | 28.07 | 15.21 | 0.00706206 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708387 | 27.9731 | 8593.43 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99842.119 | 56766.720 | 5.402620 | 0.00244513 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 86302.12 | 85649.12 | -999.0 | 28.07 | 15.21 | 0.00706474 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708765 | 27.9880 | 82226.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10163.312 | 5778.980 | 0.550025 | 0.00024890 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 8784.82 | 8719.42 | -999.0 | 28.07 | 15.21 | 0.00706369 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708614 | 27.9820 | 8371.26 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 464992.528 | 464992.528 | 24.462192 | 0.01138764 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 464992.53 | 464992.53 | 24.462192 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3833 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10430.864 | 10430.864 | 0.564620 | 0.00025545 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10430.86 | 10430.86 | 0.564620 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7686 | 25.07 | 0.00098406 | 4.3988 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99842.119 | 99842.119 | 5.402620 | 0.00244513 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 99842.12 | 99842.12 | 5.402620 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8935 | 23.50 | 0.00098408 | 4.8335 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10163.312 | 10163.312 | 0.550025 | 0.00024890 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10163.31 | 10163.31 | 0.550025 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8421 | 21.94 | 0.00098348 | 5.3100 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 24.462192 | -0.38 | -0.38 | 0.00690790 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3833 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.564620 | -0.76 | -5.61 | 0.00096628 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7686 | 25.07 | 0.00098406 | 4.3988 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.402620 | -0.80 | -5.63 | 0.00096550 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8935 | 23.50 | 0.00098408 | 4.8335 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.550025 | -0.78 | -5.62 | 0.00096524 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8421 | 21.94 | 0.00098348 | 5.3100 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 26868.264 | 26868.264 | 2.023815 | 0.00023506 | 570.164 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.7724 | 0.787903 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26868.26 | 26868.26 | 1.0000 | 2.13136036 | 2.023815 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.23503132 | 60.00 | 32.22 | 27.78 | 0.000 | 26868.26 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.77 | 0.00799998 | 21.00 | 0.00799998 | 45.2309 | 9046.61 | 0.00 | 26963.05 | 26963.05 | 2.13136036 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.21 | 16.39 | 0.00800000 | 45710.5 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 518248.157 | 518248.157 | 19.018458 | 0.00453386 | 13242.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 14.8976 | 15.197456 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 518248.16 | 518248.16 | 1.0000 | 20.02909623 | 19.018458 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.53339845 | 60.00 | 32.22 | 27.78 | 0.000 | 518248.16 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 350772.16 | 0.00 | 519845.86 | 519845.86 | 20.02909623 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.25 | 20.66 | 0.00800000 | 59014.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114310.892 | 114310.892 | 3.894575 | 0.00100004 | 3016.096 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 3.2860 | 3.352129 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114310.89 | 114310.89 | 1.0000 | 4.10153267 | 3.894575 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.99993954 | 60.00 | 32.22 | 27.78 | 0.000 | 114310.89 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 80015.37 | 0.00 | 114696.12 | 114696.12 | 4.10153267 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19921.409 | 19921.409 | 0.679405 | 0.00017428 | 525.385 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.5727 | 0.584189 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19921.41 | 19921.41 | 1.0000 | 0.71550864 | 0.679405 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.17426339 | 60.00 | 32.22 | 27.78 | 0.000 | 19921.41 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777109 | 21.00 | 0.00777109 | 43.9554 | 13941.81 | 0.00 | 19986.81 | 19986.81 | 0.71550864 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13675.363 | 13675.363 | 0.466446 | 0.00011964 | 360.638 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.3931 | 0.401025 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13675.36 | 13675.36 | 1.0000 | 0.49123314 | 0.466446 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11962584 | 60.00 | 32.22 | 27.78 | 0.000 | 13675.36 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00778325 | 21.00 | 0.00778325 | 44.0233 | 9569.96 | 0.00 | 13720.11 | 13720.11 | 0.49123314 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21911.669 | 21911.669 | 0.747402 | 0.00019169 | 577.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.6299 | 0.642552 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21911.67 | 21911.67 | 1.0000 | 0.78711932 | 0.747402 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19167329 | 60.00 | 32.22 | 27.78 | 0.000 | 21911.67 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00779929 | 21.00 | 0.00779929 | 44.1127 | 15333.21 | 0.00 | 21983.29 | 21983.29 | 0.78711932 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12346.706 | 12346.706 | 0.499814 | 0.00010801 | 303.945 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.3549 | 0.362063 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12346.71 | 12346.71 | 1.0000 | 0.52637445 | 0.499814 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.10800336 | 60.00 | 32.22 | 27.78 | 0.000 | 12346.71 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00769762 | 21.00 | 0.00769762 | 43.5457 | 7948.47 | 0.00 | 12385.54 | 12385.54 | 0.52637445 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.88 | 19.93 | 0.00800000 | 56589.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 285251.838 | 285251.838 | 9.734888 | 0.00249551 | 7520.592 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 8.1999 | 8.364916 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 285251.84 | 285251.84 | 1.0000 | 10.25219856 | 9.734888 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.49525295 | 60.00 | 32.22 | 27.78 | 0.000 | 285251.84 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765620 | 21.00 | 0.00765620 | 43.3159 | 199600.45 | 0.00 | 286171.48 | 286171.48 | 10.25219856 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 189222.604 | 189222.604 | 6.457930 | 0.00165540 | 4988.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 5.4394 | 5.548890 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 189222.60 | 189222.60 | 1.0000 | 6.80110334 | 6.457930 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.65523301 | 60.00 | 32.22 | 27.78 | 0.000 | 189222.60 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765483 | 21.00 | 0.00765483 | 43.3084 | 132403.62 | 0.00 | 189831.98 | 189831.98 | 6.80110334 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 288704.018 | 288704.018 | 9.852850 | 0.00252571 | 7611.556 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 8.2991 | 8.466150 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 288704.02 | 288704.02 | 1.0000 | 10.37642940 | 9.852850 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.52545105 | 60.00 | 32.22 | 27.78 | 0.000 | 288704.02 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00766025 | 21.00 | 0.00766025 | 43.3385 | 202014.07 | 0.00 | 289634.41 | 289634.41 | 10.37642940 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 185387.202 | 185387.202 | 6.326911 | 0.00162185 | 4887.638 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 5.3292 | 5.436418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 185387.20 | 185387.20 | 1.0000 | 6.66312209 | 6.326911 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.62168267 | 60.00 | 32.22 | 27.78 | 0.000 | 185387.20 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764787 | 21.00 | 0.00764787 | 43.2695 | 129721.79 | 0.00 | 185984.53 | 185984.53 | 6.66312209 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37609.657 | 37609.657 | 1.283924 | 0.00032903 | 991.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 1.0811 | 1.102891 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37609.66 | 37503.48 | 1.0000 | 1.35215148 | 1.283924 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.32899212 | 60.00 | 32.22 | 27.78 | 0.000 | 37609.66 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767579 | 21.00 | 0.00767579 | 43.4262 | 26313.24 | 0.00 | 37729.87 | 37729.87 | 1.35215148 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24814.385 | 24814.385 | 0.847139 | 0.00021709 | 654.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.7133 | 0.727674 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24814.38 | 24814.38 | 1.0000 | 0.89215621 | 0.847139 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21706492 | 60.00 | 32.22 | 27.78 | 0.000 | 24814.38 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767247 | 21.00 | 0.00767247 | 43.4078 | 17361.05 | 0.00 | 24893.65 | 24893.65 | 0.89215621 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38037.392 | 38037.392 | 1.298539 | 0.00033277 | 1002.697 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 1.0934 | 1.115434 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38037.39 | 38037.39 | 1.0000 | 1.36754350 | 1.298539 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.33273375 | 60.00 | 32.22 | 27.78 | 0.000 | 38037.39 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767927 | 21.00 | 0.00767927 | 43.4457 | 26612.31 | 0.00 | 38158.94 | 38158.94 | 1.36754350 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24752.519 | 24752.519 | 0.845030 | 0.00021655 | 652.491 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 0.7115 | 0.725859 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24752.52 | 24752.52 | 1.0000 | 0.88993466 | 0.845030 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21652375 | 60.00 | 32.22 | 27.78 | 0.000 | 24752.52 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767190 | 21.00 | 0.00767190 | 43.4047 | 17317.76 | 0.00 | 24831.58 | 24831.58 | 0.88993466 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 183273.830 | -999.000 | 10.857854 | 0.00779689 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0147 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.857854 | 11.43483919 | 4197.9300 | 999.8980 | 93.76333858 | 12.27 | 6.67 | 5.60 | 2204226.82 | 8.3147 | 8.314654 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 183273.83 | 181238.05 | 1.0000 | 11.43483919 | 10.857854 | 26.21 | 14.59 | 0.00708718 | 44406.1 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 7.79609706 | 6.67 | 12.27 | 5.60 | 24664.628 | 158609.20 | 33.40 | 0.00630683 | 16.37 | 2.50608000 | 23.0808 | 24.00 | 0.00732708 | 24.00 | 0.00732708 | 34.5623 | 127941.30 | 0.00 | 206597.82 | 203529.67 | 11.43483919 | 26.21 | 15.95 | 0.00708718 | 44406.1 | 8.73 | 8.71 | 0.00698058 | 26338.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100624.945 | 100624.945 | 3.257356 | 0.00088031 | 1540.986 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.857854 | 11.43483919 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 2.8926 | 2.950793 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 100624.94 | 100624.94 | 1.0000 | 3.43045176 | 3.257356 | -16.39 | -16.39 | 0.00206690 | -11364.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.88022111 | 60.00 | 32.22 | 27.78 | 0.000 | 100624.94 | -27.60 | 0.00034190 | -27.60 | 2.50608000 | 76.9360 | 21.00 | 0.00782108 | 19.41 | 0.00772474 | 48.1954 | 33568.16 | 0.00 | 81310.18 | 81310.18 | 3.43045176 | 2.80 | -1.08 | 0.00206690 | 7993.5 | 26.30 | 11.15 | 0.00206690 | 31696.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1725379.887 | -999.000 | 100.556968 | 0.07340165 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9801 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.556968 | 105.90055367 | 4197.9300 | 999.8980 | 93.76333858 | 12.27 | 6.67 | 5.60 | 2204226.82 | 78.2760 | 78.275968 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1725379.89 | 1710503.99 | 1.0000 | 105.90055367 | 100.556968 | 26.52 | 14.69 | 0.00706855 | 44670.8 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 73.39416123 | 6.67 | 12.27 | 5.60 | 228424.529 | 1496955.36 | 33.40 | 0.00630683 | 16.37 | 26.04512000 | 25.9009 | 24.00 | 0.00734708 | 24.00 | 0.00734708 | 34.6554 | 1167681.85 | 0.00 | 1941965.12 | 1918087.50 | 105.90055367 | 26.52 | 16.05 | 0.00706855 | 44670.8 | 8.72 | 8.71 | 0.00697897 | 26333.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1087733.293 | 1087733.293 | 30.167091 | 0.00951597 | 15999.524 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.556968 | 105.90055367 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 31.2681 | 31.897418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1087733.29 | 1087733.29 | 1.0000 | 31.77016610 | 30.167091 | -21.27 | -21.27 | 0.00133142 | -18097.8 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.51499464 | 60.00 | 32.22 | 27.78 | 0.000 | 1087733.29 | -27.60 | 0.00034190 | -27.60 | 26.04512000 | 86.3362 | 18.71 | 0.00758381 | 17.81 | 0.00756926 | 52.2232 | 393184.49 | 0.00 | 837237.44 | 837237.44 | 31.77016610 | 2.80 | -2.25 | 0.00133142 | 6150.3 | 28.96 | 11.51 | 0.00133142 | 32503.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 190044.122 | -999.000 | 11.238205 | 0.00808492 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9513 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.238205 | 11.83540141 | 4197.9300 | 999.8980 | 93.76333858 | 12.27 | 6.67 | 5.60 | 2204226.82 | 8.6218 | 8.621804 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 190044.12 | 188760.44 | 1.0000 | 11.83540141 | 11.238205 | 26.32 | 14.61 | 0.00705309 | 44435.6 | 10.68 | 8.51 | 0.00700000 | 28378.3 | 8.08409155 | 6.67 | 12.27 | 5.60 | 25528.629 | 164515.49 | 33.40 | 0.00630683 | 16.37 | 2.76931000 | 24.6419 | 24.00 | 0.00729826 | 24.00 | 0.00729826 | 34.4278 | 134431.73 | 0.00 | 214186.74 | 212020.38 | 11.83540141 | 26.32 | 15.96 | 0.00705309 | 44435.6 | 8.73 | 8.71 | 0.00698037 | 26338.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 113866.205 | 113866.205 | 3.371461 | 0.00099615 | 1704.281 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.238205 | 11.83540141 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 3.2732 | 3.339089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 113866.20 | 113866.20 | 1.0000 | 3.55062042 | 3.371461 | -19.11 | -19.11 | 0.00162904 | -15190.6 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.99604961 | 60.00 | 32.22 | 27.78 | 0.000 | 113866.20 | -27.60 | 0.00034190 | -27.60 | 2.76931000 | 82.1398 | 19.91 | 0.00754865 | 16.98 | 0.00753938 | 54.8331 | 57030.40 | 0.00 | 89524.83 | 89524.83 | 3.55062042 | 2.80 | -1.77 | 0.00162904 | 6896.2 | 27.82 | 11.33 | 0.00162904 | 32110.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 105528.979 | -999.000 | 6.419937 | 0.00448945 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3052 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.419937 | 6.76109201 | 4197.9300 | 999.8980 | 93.76333858 | 12.27 | 6.67 | 5.60 | 2204226.82 | 4.7876 | 4.787573 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 105528.98 | 102255.54 | 1.0000 | 6.76109201 | 6.419937 | 25.81 | 14.59 | 0.00724345 | 44399.7 | 11.09 | 8.68 | 0.00700000 | 28791.4 | 4.48898874 | 6.67 | 12.27 | 5.60 | 11794.205 | 93734.77 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 18.6942 | 24.00 | 0.00749396 | 24.00 | 0.00749396 | 35.3405 | 68342.71 | 0.00 | 119059.31 | 116192.07 | 6.76109201 | 25.81 | 15.95 | 0.00724345 | 44399.7 | 8.94 | 8.91 | 0.00707500 | 26790.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 306811.684 | 306811.684 | 6.419937 | 0.00268412 | 6559.519 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 6.419937 | 6.76109201 | 4197.9300 | 999.8980 | 29.82998341 | 54.44 | 82.22 | 27.78 | 3478727.78 | 8.8197 | 8.997151 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 306811.68 | 306811.68 | 1.0000 | 6.76109201 | 6.419937 | -5.16 | -9.55 | 0.00034190 | -4332.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.68384865 | 60.00 | 32.22 | 27.78 | 0.000 | 306811.68 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 18.6942 | 0.00 | 0.00034190 | 22.83 | 0.00034190 | 1.7505 | 0.00 | 0.00 | 244517.09 | 244517.09 | 6.76109201 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 48.77 | 18.00 | 0.00034190 | 49890.5 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 464992.528 | 261685.824 | 24.462192 | 0.01138764 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9120 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 404049.62 | 402578.36 | 0.8689 | -999.0 | -999.0 | 28.68 | 15.39 | 0.00703191 | 46779.4 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404049.62 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704209 | 27.00 | 0.00704209 | 27.8119 | 371832.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10430.864 | 5931.890 | 0.564620 | 0.00025545 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9680 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9015.76 | 8950.35 | 0.8643 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706206 | 46234.6 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9015.76 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708387 | 27.00 | 0.00708387 | 27.9731 | 8593.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 99842.119 | 56766.720 | 5.402620 | 0.00244513 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9730 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 86302.12 | 85649.12 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706474 | 46240.8 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86302.12 | 26.57 | 0.00629632 | 14.04 | 0.15632344 | -999.0000 | 27.00 | 0.00708765 | 27.00 | 0.00708765 | 27.9880 | 82226.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10163.312 | 5778.980 | 0.550025 | 0.00024890 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9710 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 8784.82 | 8719.42 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706369 | 46238.4 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8784.82 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708614 | 27.00 | 0.00708614 | 27.9820 | 8371.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 464992.528 | 464992.528 | 24.462192 | 0.01138764 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 464992.53 | 464992.53 | 1.0000 | 25.76210965 | 24.462192 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 464992.53 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3833 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10430.864 | 10430.864 | 0.564620 | 0.00025545 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10430.86 | 10430.86 | 1.0000 | 0.59462423 | 0.564620 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10430.86 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7686 | 0.00 | 0.00098406 | 25.07 | 0.00098406 | 4.3988 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99842.119 | 99842.119 | 5.402620 | 0.00244513 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 99842.12 | 99842.12 | 1.0000 | 5.68971498 | 5.402620 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99842.12 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8935 | 0.00 | 0.00098408 | 23.50 | 0.00098408 | 4.8335 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10163.312 | 10163.312 | 0.550025 | 0.00024890 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10163.31 | 10163.31 | 1.0000 | 0.57925290 | 0.550025 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10163.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8421 | 0.00 | 0.00098348 | 21.94 | 0.00098348 | 5.3100 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.462192 | 25.76210965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 25.76210965 | 24.462192 | -0.38 | -0.38 | 0.00690790 | 16887.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3833 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.564620 | 0.59462423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.59462423 | 0.564620 | -0.76 | -5.61 | 0.00096628 | 1647.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7686 | 0.00 | 0.00098406 | 25.07 | 0.00098406 | 4.3988 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.402620 | 5.68971498 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.68971498 | 5.402620 | -0.80 | -5.63 | 0.00096550 | 1610.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8935 | 0.00 | 0.00098408 | 23.50 | 0.00098408 | 4.8335 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.550025 | 0.57925290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.57925290 | 0.550025 | -0.78 | -5.62 | 0.00096524 | 1624.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8421 | 0.00 | 0.00098348 | 21.94 | 0.00098348 | 5.3100 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.51 | 10.86 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 26.05 | 100.56 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 2.77 | 11.24 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.42 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1515.00 | 1616.17 | 36.17 |
CORE_BOTTOM | 1360.83 | 1713.83 | 21.50 |
CORE_MID | 974.83 | 3454.67 | 229.50 |
CORE_TOP | 1841.00 | 4078.17 | 1117.83 |
PERIMETER_BOT_ZN_3 | 1636.00 | 3858.00 | 675.50 |
PERIMETER_BOT_ZN_2 | 2030.17 | 3873.50 | 821.17 |
PERIMETER_BOT_ZN_1 | 2207.00 | 3255.50 | 689.83 |
PERIMETER_BOT_ZN_4 | 2391.00 | 2954.67 | 445.50 |
PERIMETER_MID_ZN_3 | 2679.00 | 4430.17 | 2016.17 |
PERIMETER_MID_ZN_2 | 2466.67 | 3716.50 | 1632.50 |
PERIMETER_MID_ZN_1 | 2566.50 | 3704.33 | 1253.83 |
PERIMETER_MID_ZN_4 | 2698.50 | 4353.00 | 1678.67 |
PERIMETER_TOP_ZN_3 | 3324.00 | 4730.67 | 2732.83 |
PERIMETER_TOP_ZN_2 | 3459.83 | 4372.33 | 2410.17 |
PERIMETER_TOP_ZN_1 | 3040.33 | 4069.67 | 1891.17 |
PERIMETER_TOP_ZN_4 | 3223.83 | 4575.83 | 2286.17 |
DATACENTER_BOT_ZN_6 | 5810.50 | 386.00 | 385.17 |
DATACENTER_MID_ZN_6 | 5268.33 | 198.67 | 65.50 |
DATACENTER_TOP_ZN_6 | 4525.00 | 564.17 | 144.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5665.83 | 5665.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5942.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 61.33 | 0.00 | 2.83 |
CORE_BOTTOM | 0.00 | 4.83 | 0.00 | 0.00 |
CORE_MID | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14.83 | 0.00 | 3.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 6.00 | 1.00 | 1.00 | 0.67 |
PERIMETER_BOT_ZN_2 | 5.50 | 14.67 | 0.17 | 14.67 |
PERIMETER_BOT_ZN_1 | 6.33 | 22.17 | 0.50 | 21.33 |
PERIMETER_BOT_ZN_4 | 2.50 | 54.00 | 0.00 | 20.67 |
PERIMETER_MID_ZN_3 | 113.00 | 0.00 | 37.67 | 0.00 |
PERIMETER_MID_ZN_2 | 64.33 | 15.33 | 8.50 | 15.33 |
PERIMETER_MID_ZN_1 | 46.83 | 20.17 | 6.00 | 18.83 |
PERIMETER_MID_ZN_4 | 50.83 | 19.17 | 7.67 | 9.17 |
PERIMETER_TOP_ZN_3 | 299.17 | 1.00 | 103.50 | 0.33 |
PERIMETER_TOP_ZN_2 | 189.83 | 17.83 | 37.17 | 17.00 |
PERIMETER_TOP_ZN_1 | 153.33 | 15.00 | 25.33 | 12.83 |
PERIMETER_TOP_ZN_4 | 145.83 | 19.33 | 29.00 | 8.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 21.17 | 0.00 | 16.00 |
DATACENTER_MID_ZN_6 | 0.00 | 8.33 | 0.00 | 4.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 8.50 | 0.00 | 4.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 524.83 | 0.00 | 405.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 345.17 | 695.00 | 113.17 | 485.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.338 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 1.055 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.836 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.788 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 1.048 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.841 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.766 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.350 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.924 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.815 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.763 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.976 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 1.117 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 2.005 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.842 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 2.144 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 55660275.14 | 0.00 | 55660275.14 | 0.00 | 55660275.14 | 37848132.68 | 3909.91 | 910.34 | 3939.75 | 408.00 |
CORE_BOTTOM | 45048678.66 | 0.00 | 45048678.66 | 0.00 | 45048678.66 | 33990283.35 | 3675.89 | 12.21 | 5071.90 | 506.91 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 4101.77 | 7.99 | 4650.23 | 371.99 |
CORE_TOP | 32397261.10 | 0.00 | 32397261.10 | 0.00 | 32397261.10 | 33990283.35 | 4151.72 | 6.58 | 4601.70 | 424.82 |
PERIMETER_BOT_ZN_3 | 5705500.64 | 0.00 | 5705500.64 | 591585.02 | 6297085.66 | 4267819.30 | 3778.22 | 53.47 | 4928.32 | 506.91 |
PERIMETER_BOT_ZN_2 | 6515481.77 | 0.00 | 6515481.77 | 394389.74 | 6909871.51 | 2750345.05 | 3430.81 | 0.13 | 5329.06 | 506.91 |
PERIMETER_BOT_ZN_1 | 9567512.77 | 0.00 | 9567512.77 | 591585.02 | 10159097.78 | 4267912.63 | 3450.33 | 2.49 | 5307.18 | 506.91 |
PERIMETER_BOT_ZN_4 | 8307101.79 | 0.00 | 8307101.79 | 394389.74 | 8701491.53 | 2750345.05 | 3416.30 | 0.57 | 5343.13 | 506.91 |
PERIMETER_MID_ZN_3 | 48296557.95 | 0.00 | 48296557.95 | 1387434.57 | 49683992.52 | 42678193.03 | 4027.70 | 5.92 | 4726.38 | 371.99 |
PERIMETER_MID_ZN_2 | 65599531.54 | 0.00 | 65599531.54 | 924955.75 | 66524487.29 | 27503450.52 | 3818.84 | 5.28 | 4935.88 | 1280.99 |
PERIMETER_MID_ZN_1 | 91592872.06 | 0.00 | 91592872.06 | 1387434.57 | 92980306.63 | 42679126.28 | 3873.59 | 3.63 | 4882.77 | 371.99 |
PERIMETER_MID_ZN_4 | 66844887.29 | 0.00 | 66844887.29 | 924955.75 | 67769843.04 | 27503450.52 | 3808.49 | 2.79 | 4948.72 | 371.99 |
PERIMETER_TOP_ZN_3 | 5816259.39 | 0.00 | 5816259.39 | 1722650.34 | 7538909.73 | 4267819.30 | 4075.29 | 3.50 | 4681.22 | 424.82 |
PERIMETER_TOP_ZN_2 | 6709183.03 | 0.00 | 6709183.03 | 1148432.78 | 7857615.81 | 2750345.05 | 3950.18 | 3.40 | 4806.42 | 424.82 |
PERIMETER_TOP_ZN_1 | 9529683.97 | 0.00 | 9529683.97 | 1722650.34 | 11252334.32 | 4267912.63 | 3999.19 | 5.28 | 4755.54 | 424.82 |
PERIMETER_TOP_ZN_4 | 7200565.58 | 0.00 | 7200565.58 | 1148432.78 | 8348998.36 | 2750345.05 | 3921.91 | 4.71 | 4833.38 | 424.82 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.64E+10 | 0.00 | 0.64E+10 | 53961922.12 | 0.65E+10 | 0.50E+10 | 4626.75 | 4406.01 | 5555.59 | 1963.23 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4723 | 0.0000 | 2.4723 | 0.0000 | 2.4723 | 1.2002 | 1336.01 | 905.68 | 3701.31 |
CORE_BOTTOM | 1.9697 | 0.0000 | 1.9697 | 0.0000 | 1.9697 | 1.0778 | 1233.64 | 8.23 | 4701.12 |
CORE_MID | 15.6172 | 0.0000 | 15.6172 | 0.0000 | 15.6172 | 10.7782 | 1408.96 | 7.40 | 4526.64 |
CORE_TOP | 1.4740 | 0.0000 | 1.4740 | 0.0000 | 1.4740 | 1.0778 | 1423.56 | 6.33 | 4513.11 |
PERIMETER_BOT_ZN_3 | 0.2462 | 0.0000 | 0.2462 | 0.0139 | 0.2601 | 0.1353 | 1377.27 | 47.90 | 4517.83 |
PERIMETER_BOT_ZN_2 | 0.2792 | 0.0000 | 0.2792 | 0.0092 | 0.2884 | 0.0872 | 1090.82 | 0.02 | 4852.16 |
PERIMETER_BOT_ZN_1 | 0.4151 | 0.0000 | 0.4151 | 0.0139 | 0.4289 | 0.1353 | 1104.41 | 1.33 | 4837.26 |
PERIMETER_BOT_ZN_4 | 0.3559 | 0.0000 | 0.3559 | 0.0092 | 0.3651 | 0.0872 | 1082.80 | 0.39 | 4859.81 |
PERIMETER_MID_ZN_3 | 2.1756 | 0.0000 | 2.1756 | 0.0325 | 2.2081 | 1.3533 | 1348.99 | 4.44 | 4589.57 |
PERIMETER_MID_ZN_2 | 2.7575 | 0.0000 | 2.7575 | 0.0230 | 2.7805 | 0.8721 | 1207.37 | 2.69 | 3823.94 |
PERIMETER_MID_ZN_1 | 4.1469 | 0.0000 | 4.1469 | 0.0325 | 4.1794 | 1.3533 | 1234.90 | 1.90 | 4706.19 |
PERIMETER_MID_ZN_4 | 3.0030 | 0.0000 | 3.0030 | 0.0217 | 3.0247 | 0.8721 | 1202.49 | 1.14 | 4739.37 |
PERIMETER_TOP_ZN_3 | 0.2636 | 0.0000 | 0.2636 | 0.0404 | 0.3040 | 0.1353 | 1362.65 | 2.55 | 4577.80 |
PERIMETER_TOP_ZN_2 | 0.3047 | 0.0000 | 0.3047 | 0.0269 | 0.3316 | 0.0872 | 1289.02 | 1.79 | 4652.19 |
PERIMETER_TOP_ZN_1 | 0.4338 | 0.0000 | 0.4338 | 0.0404 | 0.4742 | 0.1353 | 1314.57 | 3.26 | 4625.16 |
PERIMETER_TOP_ZN_4 | 0.3261 | 0.0000 | 0.3261 | 0.0269 | 0.3530 | 0.0872 | 1273.30 | 2.33 | 4667.37 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 286.9537 | 0.0000 | 286.9537 | 1.2778 | 288.2315 | 158.4706 | 1809.75 | 4375.73 | 4906.76 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 83342868.47 | 0.00 | 83342868.47 | 48026705.38 | 3508.26 | 8.03 | 5243.71 | 506.91 |
VAV_MID WITH REHEAT | 0.69E+09 | 0.00 | 0.69E+09 | 0.48E+09 | 3990.94 | 8.27 | 4760.78 | 371.99 |
VAV_TOP WITH REHEAT | 68379516.38 | 0.00 | 68379516.38 | 48026705.38 | 4091.02 | 1.95 | 4667.02 | 424.74 |
CAV_BAS | 61733011.92 | 0.00 | 61733011.92 | 37848132.68 | 3875.59 | 5.71 | 4878.70 | 408.00 |
AIRLOOP DATACENTER BASEMENT | 5865235.79 | 0.00 | 5865235.79 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6223 | 0.0000 | 3.6223 | 1.5229 | 1141.55 | 3.60 | 4797.85 |
VAV_MID WITH REHEAT | 30.9418 | 0.0000 | 30.9418 | 15.2292 | 1314.57 | 6.80 | 4621.64 |
VAV_TOP WITH REHEAT | 3.1079 | 0.0000 | 3.1079 | 1.5229 | 1373.28 | 1.58 | 4568.14 |
CAV_BAS | 2.7421 | 0.0000 | 2.7421 | 1.2002 | 1327.19 | 1.32 | 4614.49 |
AIRLOOP DATACENTER BASEMENT | 0.2741 | 0.0000 | 0.2741 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1932.74 | 3449.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2541.78 | 2645.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 2777.28 | 2460.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 898.58 | 4170.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.7809 | 5.4911 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 28.8953 | 48.5985 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.0718 | 4.8845 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3320 | 4.0138 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3754 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1335 |
Defaulted Fields | 1179 |
Fields with Defaults | 3690 |
Autosized Fields | 333 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
Electricity:Building | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 660.02 | 14600.60 | 01-JAN-00:10 | 34031.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 532.90 | 7069.41 | 01-JAN-00:10 | 36605.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5328.94 | 70693.84 | 01-JAN-00:10 | 366051.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 532.89 | 7069.38 | 01-JAN-00:10 | 36605.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 669.12 | 8876.66 | 01-JAN-00:10 | 45962.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 431.21 | 5720.45 | 01-JAN-00:10 | 29619.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 669.13 | 8876.80 | 01-JAN-00:10 | 45963.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 431.20 | 5720.42 | 01-JAN-00:10 | 29619.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7561.29 | 95230.42 | 01-JAN-00:10 | 385433.43 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1582.51 | 19698.04 | 01-JAN-00:10 | 81759.99 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1809.35 | 5154.49 | 10-JAN-22:10 | 475803.86 | 07-SEP-14:50 |
HeatRejection:Electricity | 837.86 | 1247.82 | 10-JAN-22:00 | 83442.05 | 19-MAY-14:00 |
General:HeatRejection:Electricity | 837.86 | 1247.82 | 10-JAN-22:00 | 83442.05 | 19-MAY-14:00 |
Electricity:HVAC | 6378.53 | 96595.57 | 09-JAN-24:00 | 538131.52 | 11-AUG-15:40 |
ExteriorEquipment:Electricity | 1997.59 | 30702.09 | 01-JAN-00:10 | 120520.01 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.51 | 1613.62 | 01-JAN-00:10 | 5474.05 | 03-APR-07:20 |
ElectricityPurchased:Facility | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
ElectricityPurchased:Plant | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
Cogeneration:ElectricityPurchased | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
ElectricityNet:Plant | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
Cogeneration:ElectricityNet | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
General:Cogeneration:ElectricityNet | 30157.09 | 391967.65 | 29-JAN-10:40 | 2144185.78 | 07-AUG-15:30 |
Fans:Electricity | 2738.66 | 47644.24 | 29-JAN-06:00 | 325068.55 | 11-AUG-15:40 |
General:Fans:Electricity | 2738.66 | 47644.24 | 29-JAN-06:00 | 325068.55 | 11-AUG-15:40 |
ExteriorLights:Electricity | 903.27 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 903.27 | 0.00 | 01-JAN-08:20 | 57580.60 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Cooling:Electricity | 3247.48 | 30241.90 | 09-JAN-07:10 | 476400.57 | 07-AUG-15:30 |
General:Cooling:Electricity | 3247.48 | 30241.90 | 09-JAN-07:10 | 476400.57 | 07-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 841.38 | 0.00 | 13-JUL-15:20 | 52018.99 | 28-DEC-19:00 |
General:Humidifier:Electricity | 841.38 | 0.00 | 13-JUL-15:20 | 52018.99 | 28-DEC-19:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 434.99 | 3656.68 | 07-JAN-04:50 | 66157.66 | 17-JUL-16:00 |
General:Pumps:Electricity | 434.99 | 3656.68 | 07-JAN-04:50 | 66157.66 | 17-JUL-16:00 |
WIRED_LTG_ELECTRICITY | 110.78 | 0.00 | 01-JAN-00:10 | 9672.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6520.00 | 8146.58 | 05-JAN-22:20 | 3042043.47 | 09-JAN-07:10 |
NaturalGas:Plant | 6520.00 | 8146.58 | 05-JAN-22:20 | 3042043.47 | 09-JAN-07:10 |
Heating:NaturalGas | 5671.61 | 0.00 | 01-JAN-00:10 | 3008975.83 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 5671.61 | 0.00 | 01-JAN-00:10 | 3008975.83 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 848.39 | 8146.58 | 05-JAN-22:20 | 87977.56 | 17-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 848.39 | 8146.58 | 05-JAN-22:20 | 87977.56 | 17-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 17075.52 | 147205.54 | 09-JAN-07:10 | 2567895.29 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 17075.52 | 147205.54 | 09-JAN-07:10 | 2567895.29 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 17075.52 | 147205.54 | 09-JAN-07:10 | 2567895.29 | 07-SEP-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5679.35 | 0.00 | 03-SEP-24:00 | 0.00 | 17-JUL-16:00 |
Water:HVAC | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:Water | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:Water | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
MainsWater:Facility | 5679.35 | 0.00 | 03-SEP-24:00 | 0.00 | 17-JUL-16:00 |
MainsWater:HVAC | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:MainsWater | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:MainsWater | 312.99 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Water:Plant | 5366.36 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5366.36 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3086.19 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:Water | 3086.19 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 3086.19 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:MainsWater | 3086.19 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 53456.44 | 228552.70 | 30-JAN-06:00 | 10818293.02 | 07-SEP-15:00 |
EnergyTransfer:Building | 18806.21 | 87916.57 | 12-JAN-22:40 | 1749929.65 | 07-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 670.00 | 0.00 | 01-JAN-00:40 | 69663.21 | 05-SEP-05:10 |
Heating:EnergyTransfer | 873.08 | 0.00 | 13-JAN-22:10 | 1268216.45 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.43 | 0.00 | 01-JAN-00:40 | 22665.98 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 873.08 | 0.00 | 13-JAN-22:10 | 1268216.45 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.43 | 0.00 | 01-JAN-00:40 | 22665.98 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 17933.13 | 83789.67 | 30-JAN-06:00 | 1749929.65 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 666.57 | 0.00 | 01-JAN-00:10 | 69663.21 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 17933.13 | 83789.67 | 30-JAN-06:00 | 1749929.65 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 666.57 | 0.00 | 01-JAN-00:10 | 69663.21 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 604.03 | 0.00 | 01-JAN-00:10 | 57078.27 | 07-AUG-10:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 604.03 | 0.00 | 01-JAN-00:10 | 57078.27 | 07-AUG-10:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 604.03 | 0.00 | 01-JAN-00:10 | 57078.27 | 07-AUG-10:30 |
EnergyTransfer:Zone:CORE_MID | 4234.42 | 0.00 | 01-JAN-00:10 | 454343.39 | 05-SEP-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.40 | 0.00 | 01-JAN-00:10 | 339588.03 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 6.40 | 0.00 | 01-JAN-00:10 | 339588.03 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4228.02 | 0.00 | 01-JAN-00:10 | 454343.39 | 05-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4228.02 | 0.00 | 01-JAN-00:10 | 454343.39 | 05-SEP-14:00 |
EnergyTransfer:Zone:CORE_TOP | 368.60 | 0.00 | 01-JAN-00:10 | 70276.53 | 06-MAR-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 19.45 | 0.00 | 01-JAN-00:10 | 70276.53 | 06-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 19.45 | 0.00 | 01-JAN-00:10 | 70276.53 | 06-MAR-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 349.15 | 0.00 | 01-JAN-00:10 | 54273.90 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 349.15 | 0.00 | 01-JAN-00:10 | 54273.90 | 17-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 69.84 | 0.00 | 01-JAN-00:10 | 11488.22 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.76 | 0.00 | 01-JAN-00:10 | 11488.22 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.76 | 0.00 | 01-JAN-00:10 | 11488.22 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.09 | 0.00 | 01-JAN-00:10 | 10811.55 | 09-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.09 | 0.00 | 01-JAN-00:10 | 10811.55 | 09-AUG-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.94 | 0.00 | 01-JAN-00:10 | 14524.45 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.07 | 0.00 | 01-JAN-00:10 | 8753.71 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.07 | 0.00 | 01-JAN-00:10 | 8753.71 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 69.87 | 0.00 | 01-JAN-00:10 | 14524.45 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 69.87 | 0.00 | 01-JAN-00:10 | 14524.45 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.66 | 0.00 | 01-JAN-00:10 | 20590.07 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.94 | 0.00 | 01-JAN-00:10 | 14822.56 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.94 | 0.00 | 01-JAN-00:10 | 14822.56 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 113.72 | 0.00 | 01-JAN-00:10 | 20590.07 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 113.72 | 0.00 | 01-JAN-00:10 | 20590.07 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 102.00 | 0.00 | 01-JAN-00:10 | 18585.53 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 6720.24 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 6720.24 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.40 | 0.00 | 01-JAN-00:10 | 18585.53 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.40 | 0.00 | 01-JAN-00:10 | 18585.53 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 611.98 | 0.00 | 01-JAN-00:10 | 130657.24 | 30-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 180.72 | 0.00 | 01-JAN-00:10 | 130657.24 | 30-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 180.72 | 0.00 | 01-JAN-00:10 | 130657.24 | 30-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 431.25 | 0.00 | 01-JAN-00:10 | 99929.89 | 18-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 431.25 | 0.00 | 01-JAN-00:10 | 99929.89 | 18-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 663.48 | 0.00 | 01-JAN-00:10 | 149693.84 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 108.12 | 0.00 | 01-JAN-00:10 | 146595.91 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 108.12 | 0.00 | 01-JAN-00:10 | 146595.91 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 555.36 | 0.00 | 01-JAN-00:10 | 149693.84 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 555.36 | 0.00 | 01-JAN-00:10 | 149693.84 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1060.91 | 0.00 | 01-JAN-00:10 | 213378.17 | 18-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 108.17 | 0.00 | 01-JAN-00:10 | 191445.18 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 108.17 | 0.00 | 01-JAN-00:10 | 191445.18 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 952.74 | 0.00 | 01-JAN-00:10 | 213378.17 | 18-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 952.74 | 0.00 | 01-JAN-00:10 | 213378.17 | 18-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 664.09 | 0.00 | 01-JAN-00:10 | 157375.24 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 87.37 | 0.00 | 01-JAN-00:10 | 141299.20 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 87.37 | 0.00 | 01-JAN-00:10 | 141299.20 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 576.72 | 0.00 | 01-JAN-00:10 | 157375.24 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 576.72 | 0.00 | 01-JAN-00:10 | 157375.24 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 85.61 | 0.00 | 01-JAN-00:10 | 17253.94 | 09-JAN-02:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.80 | 0.00 | 01-JAN-00:10 | 17253.94 | 09-JAN-02:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.80 | 0.00 | 01-JAN-00:10 | 17253.94 | 09-JAN-02:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.81 | 0.00 | 01-JAN-00:10 | 11295.81 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.81 | 0.00 | 01-JAN-00:10 | 11295.81 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 76.52 | 0.00 | 01-JAN-00:10 | 16612.27 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.59 | 0.00 | 01-JAN-00:10 | 16612.27 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.59 | 0.00 | 01-JAN-00:10 | 16612.27 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.93 | 0.00 | 01-JAN-00:10 | 15278.06 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.93 | 0.00 | 01-JAN-00:10 | 15278.06 | 07-AUG-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 115.73 | 0.00 | 01-JAN-00:10 | 22407.99 | 01-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 30.59 | 0.00 | 01-JAN-00:10 | 22325.81 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 30.59 | 0.00 | 01-JAN-00:10 | 22325.81 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.14 | 0.00 | 01-JAN-00:10 | 22407.99 | 01-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.14 | 0.00 | 01-JAN-00:10 | 22407.99 | 01-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.51 | 0.00 | 01-JAN-00:10 | 17747.56 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.27 | 0.00 | 01-JAN-00:10 | 17747.56 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.27 | 0.00 | 01-JAN-00:10 | 17747.56 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.24 | 0.00 | 01-JAN-00:10 | 16641.00 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.24 | 0.00 | 01-JAN-00:10 | 16641.00 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 59.55 | 0.00 | 01-JAN-00:10 | 10468.22 | 07-AUG-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.68 | 0.00 | 01-JAN-00:10 | 6569.19 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.68 | 0.00 | 01-JAN-00:10 | 6569.19 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 54.87 | 0.00 | 01-JAN-00:10 | 10468.22 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 54.87 | 0.00 | 01-JAN-00:10 | 10468.22 | 07-AUG-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 490.53 | 0.00 | 01-JAN-00:10 | 117843.85 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 144.51 | 0.00 | 01-JAN-00:10 | 117843.85 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 144.51 | 0.00 | 01-JAN-00:10 | 117843.85 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 346.02 | 0.00 | 01-JAN-00:10 | 81962.74 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 346.02 | 0.00 | 01-JAN-00:10 | 81962.74 | 07-AUG-15:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 118.24 | 0.00 | 01-JAN-00:10 | 33506.08 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.83 | 0.00 | 01-JAN-00:10 | 33506.08 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.83 | 0.00 | 01-JAN-00:10 | 33506.08 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.41 | 0.00 | 01-JAN-00:10 | 23043.35 | 17-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.41 | 0.00 | 01-JAN-00:10 | 23043.35 | 17-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.26 | 6.56 | 28-JAN-04:50 | 8241.22 | 22-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.06 | 0.00 | 01-JAN-00:10 | 632.93 | 09-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.06 | 0.00 | 01-JAN-00:10 | 632.93 | 09-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.20 | 0.00 | 08-JAN-00:10 | 8241.22 | 22-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.20 | 0.00 | 08-JAN-00:10 | 8241.22 | 22-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1154.81 | 6.81 | 15-JAN-14:30 | 78368.54 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.58 | 0.00 | 02-JAN-08:50 | 6634.73 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.58 | 0.00 | 02-JAN-08:50 | 6634.73 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1149.23 | 0.00 | 01-JAN-00:10 | 78368.54 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1149.23 | 0.00 | 01-JAN-00:10 | 78368.54 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.25 | 0.46 | 18-JAN-12:00 | 7952.55 | 03-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.11 | 0.00 | 02-JAN-13:20 | 752.69 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.11 | 0.00 | 02-JAN-13:20 | 752.69 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.15 | 0.00 | 01-JAN-00:10 | 7952.55 | 03-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.15 | 0.00 | 01-JAN-00:10 | 7952.55 | 03-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.22 | 83196.13 | 09-JAN-05:00 | 369514.73 | 22-AUG-07:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.22 | 83196.13 | 09-JAN-05:00 | 369514.73 | 22-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7153.22 | 83196.13 | 09-JAN-05:00 | 369514.73 | 22-AUG-07:20 |
PlantLoopHeatingDemand:Facility | 4737.39 | 0.00 | 01-JAN-00:10 | 2420277.47 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57405.82 | 17-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57405.82 | 17-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57405.82 | 17-FEB-12:20 |
EnergyTransfer:HVAC | 18638.62 | 137864.48 | 30-JAN-04:40 | 2518665.25 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 4274.08 | 0.00 | 01-JAN-00:10 | 2401701.61 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 4274.08 | 0.00 | 01-JAN-00:10 | 2401701.61 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 4274.08 | 0.00 | 01-JAN-00:10 | 2401701.61 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 14364.54 | 116963.65 | 09-JAN-07:10 | 2510732.03 | 07-SEP-15:00 |
EnergyTransfer:Plant | 16011.61 | 0.00 | 01-JAN-00:10 | 7112119.31 | 07-SEP-15:00 |
LoopToLoop:EnergyTransfer | 3783.72 | -0.37 | 01-FEB-05:50 | 2296821.11 | 07-SEP-15:00 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57405.82 | 17-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57405.82 | 17-FEB-12:20 |
Boilers:EnergyTransfer | 4236.52 | 0.00 | 01-JAN-00:10 | 2424189.94 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3495.78 | 0.00 | 01-JAN-00:10 | 2235762.46 | 07-SEP-14:50 |
HeatRejection:EnergyTransfer | 4032.28 | 0.00 | 01-JAN-00:10 | 2563123.44 | 07-SEP-14:50 |
General:HeatRejection:EnergyTransfer | 4032.28 | 0.00 | 01-JAN-00:10 | 2563123.44 | 07-SEP-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.435 | -666.566 | 0.000 | 0.000 | 93.181 | 235.627 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -90.074 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -604.032 | 0.000 | 0.000 | 83.572 | 211.610 | 321.286 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -12.436 |
CORE_MID | 0.000 | 0.000 | 6.402 | -4227.997 | 0.000 | 0.000 | 849.693 | 2116.097 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1957.041 |
CORE_TOP | 0.000 | 0.000 | 19.454 | -349.146 | 0.000 | 0.000 | 88.098 | 211.610 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -291.300 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.756 | -67.088 | 0.000 | 0.000 | 10.995 | 26.570 | 40.342 | 22.599 | 0.000 | 0.090 | 36.508 | 0.000 | -62.406 | 0.000 | -10.366 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.072 | -69.868 | 0.000 | 0.000 | 7.209 | 17.123 | 25.998 | 52.573 | 0.000 | 0.063 | 9.667 | 0.000 | -38.055 | 0.000 | -6.782 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.941 | -113.717 | 0.000 | 0.000 | 10.979 | 26.570 | 40.343 | 113.819 | 0.000 | 0.086 | 0.000 | 0.000 | -56.615 | 0.000 | -10.393 | -14.013 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.606 | -101.397 | 0.000 | 0.000 | 7.068 | 17.123 | 25.998 | 49.196 | 0.000 | 0.057 | 52.071 | 0.000 | -43.339 | 0.000 | -7.384 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 180.725 | -431.251 | 0.000 | 0.000 | 115.062 | 265.697 | 403.423 | 236.131 | 0.000 | 2.129 | 17.685 | 0.000 | -573.048 | 0.000 | -216.552 | -0.017 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 108.117 | -555.360 | 0.000 | 0.000 | 54.701 | 171.225 | 259.981 | 528.852 | 0.000 | 1.416 | 0.005 | 0.000 | -359.120 | 0.000 | -146.194 | -63.619 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 108.173 | -952.733 | 0.000 | 0.000 | 112.104 | 265.703 | 403.429 | 1136.705 | 0.000 | 1.957 | 0.043 | 0.000 | -547.947 | 0.000 | -230.377 | -297.014 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 87.372 | -576.714 | 0.000 | 0.000 | 75.135 | 171.225 | 259.979 | 504.688 | 0.000 | 1.399 | 12.353 | 0.000 | -385.847 | 0.000 | -149.591 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 45.802 | -39.808 | 0.000 | 0.000 | 11.781 | 26.570 | 40.342 | 24.366 | 0.000 | 0.267 | 0.001 | 0.000 | -54.097 | 0.000 | -25.231 | -29.992 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 26.587 | -49.934 | 0.000 | 0.000 | 7.502 | 17.123 | 25.998 | 53.312 | 0.000 | 0.167 | 0.000 | 0.000 | -34.193 | 0.000 | -17.183 | -29.377 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 30.590 | -85.143 | 0.000 | 0.000 | 11.437 | 26.570 | 40.343 | 114.483 | 0.000 | 0.235 | 0.001 | 0.000 | -51.871 | 0.000 | -26.817 | -59.827 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 22.271 | -52.235 | 0.000 | 0.000 | 7.615 | 17.123 | 25.998 | 50.771 | 0.000 | 0.171 | 0.000 | 0.000 | -36.835 | 0.000 | -17.623 | -17.256 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.062 | -135.198 | 0.000 | 0.000 | 0.950 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.065 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.584 | -1149.227 | 0.000 | 0.000 | 9.520 | 43.701 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -448.384 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.109 | -103.146 | 0.000 | 0.000 | 0.957 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.171 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7153.222 | 0.000 | 0.000 | 20.232 | 66.437 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -428.304 |
GROUNDFLOOR_PLENUM | 4.676 | -54.869 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.160 | 72.060 | 0.000 | 0.000 | 0.000 | -22.026 | 0.000 |
MIDFLOOR_PLENUM | 144.515 | -346.017 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.949 | 570.903 | 0.000 | 0.000 | 0.000 | -372.350 | -0.007 |
TOPFLOOR_PLENUM | 69.834 | -48.406 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.259 | 17.314 | 0.000 | 0.000 | 0.000 | -39.002 | -0.000 |
Total Facility | 219.025 | -449.292 | 654.056 | -17483.780 | 0.000 | 0.000 | 1577.792 | 3942.443 | 15213.411 | 2887.496 | 0.000 | 11.405 | 788.610 | 0.000 | -2243.372 | 0.000 | -1297.872 | -3819.897 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -112853.23 | 0.00 | 0.00 | 0.00 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 98252.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -94871.04 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.15 | 0.00 | 0.00 | 0.00 | 85787.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 | -853212.66 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 762376.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-03:02 | 0.00 | 0.00 | 0.00 | -82450.24 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 73366.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-16:01 | 0.00 | 0.00 | 0.00 | -16290.15 | 0.00 | 0.00 | 41.81 | 128.89 | 758.77 | 4037.20 | 0.00 | 257.92 | 11065.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-08:41 | 0.00 | 0.00 | 0.00 | -23102.70 | 0.00 | 0.00 | 19.77 | 83.06 | 488.98 | 18360.91 | 0.00 | 0.00 | 4188.80 | 0.00 | -0.00 | 0.00 | -38.84 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:31 | 0.00 | 0.00 | 0.00 | -28486.08 | 0.00 | 0.00 | 32.96 | 128.90 | 758.78 | 29217.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -420.40 | -1231.42 |
PERIMETER_BOT_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -30550.40 | 0.00 | 0.00 | 14.26 | 83.06 | 488.98 | 13968.01 | 0.00 | 105.75 | 15890.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:01 | 0.00 | 0.00 | 0.00 | -148778.81 | 0.00 | 0.00 | 435.75 | 1288.93 | 7587.73 | 41215.76 | 0.00 | 6217.17 | 92033.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:21 | 0.00 | 0.00 | 0.00 | -250621.22 | 0.00 | 0.00 | 180.62 | 830.63 | 4889.82 | 164059.61 | 0.00 | 0.00 | 81070.56 | 0.00 | -0.00 | 0.00 | -410.02 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -306599.03 | 0.00 | 0.00 | 279.53 | 1288.96 | 7587.84 | 241746.30 | 0.00 | 3783.42 | 51912.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:41 | 0.00 | 0.00 | 0.00 | -263558.58 | 0.00 | 0.00 | 174.32 | 830.63 | 4889.79 | 140200.24 | 0.00 | 2815.65 | 114647.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -16288.71 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 5851.83 | 0.00 | 268.20 | 9281.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:02 | 0.00 | 0.00 | 0.00 | -22634.44 | 0.00 | 0.00 | 22.03 | 83.06 | 488.98 | 13253.85 | 0.00 | 0.00 | 9082.66 | 0.00 | -0.00 | 0.00 | -296.15 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:31 | 0.00 | 0.00 | 0.00 | -30587.44 | 0.00 | 0.00 | 26.19 | 128.90 | 758.78 | 20590.12 | 0.00 | 573.05 | 8510.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:41 | 0.00 | 0.00 | 0.00 | -27583.96 | 0.00 | 0.00 | 18.89 | 83.06 | 488.98 | 18270.22 | 0.00 | 0.00 | 8780.19 | 0.00 | -0.00 | 0.00 | -57.39 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:10 | 0.00 | 0.00 | 0.00 | -8241.22 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 425.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -78365.55 | 0.00 | 0.00 | 105.11 | 1271.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -955.70 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7952.22 | 0.00 | 0.00 | 10.62 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 19.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 22-AUG-07:20 | 0.00 | 0.00 | 0.00 | -369520.48 | 0.00 | 0.00 | 2182.49 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18095.45 |
GROUNDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -14002.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14081.95 | 0.00 | -0.00 | 0.00 | -79.27 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -112520.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144189.84 | 0.00 | -0.00 | 0.00 | -31669.62 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:10 | 0.00 | -23042.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 22991.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:03 | 0.00 | -57088.05 | 0.00 | -1937888.45 | 0.00 | 0.00 | 15851.47 | 38246.31 | 623236.89 | 0.00 | 0.00 | 0.00 | 1384539.69 | 0.00 | -61308.13 | 0.00 | -5589.73 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 24095.29 | 0.00 | 0.00 | 0.00 | 520.12 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39216.02 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 535746.54 | 0.00 | 0.00 | 0.00 | 0.00 | 20528.61 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -636846.35 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 79494.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88577.87 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 13695.25 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6555.78 | 0.00 | -841.39 | -7438.67 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 15467.80 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4349.21 | 0.00 | -563.19 | -11290.44 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 21685.78 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6292.44 | 0.00 | -838.45 | -15695.49 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 13726.31 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4391.98 | 0.00 | -577.29 | -9492.08 |
PERIMETER_MID_ZN_3 | 09-JAN-02:31 | 0.00 | 0.00 | 138508.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63284.32 | 0.00 | -26284.20 | -60346.30 |
PERIMETER_MID_ZN_2 | 09-JAN-02:31 | 0.00 | 0.00 | 188846.11 | 0.00 | 0.00 | 0.00 | 0.00 | 830.63 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42149.45 | 0.00 | -17709.41 | -136337.64 |
PERIMETER_MID_ZN_1 | 09-JAN-02:31 | 0.00 | 0.00 | 228412.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.96 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61634.92 | 0.00 | -26569.64 | -151614.37 |
PERIMETER_MID_ZN_4 | 09-JAN-02:31 | 0.00 | 0.00 | 200624.21 | 0.00 | 0.00 | 0.00 | 0.00 | 830.63 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41168.30 | 0.00 | -17831.64 | -148974.63 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 18760.28 | 0.00 | 0.00 | 0.00 | 186.78 | 257.76 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4553.99 | 0.00 | -967.55 | -14694.98 |
PERIMETER_TOP_ZN_2 | 27-NOV-04:11 | 0.00 | 0.00 | 20126.93 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3014.06 | 0.00 | -2284.14 | -15563.77 |
PERIMETER_TOP_ZN_1 | 27-NOV-04:11 | 0.00 | 0.00 | 26129.68 | 0.00 | 0.00 | 0.00 | 0.00 | 128.90 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4703.49 | 0.00 | -3436.42 | -19130.37 |
PERIMETER_TOP_ZN_4 | 27-NOV-04:11 | 0.00 | 0.00 | 22394.81 | 0.00 | 0.00 | 0.00 | 0.00 | 83.06 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3180.02 | 0.00 | -2335.39 | -17614.43 |
DATACENTER_BOT_ZN_6 | 09-JAN-03:52 | 0.00 | 0.00 | 633.39 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2603.20 |
DATACENTER_MID_ZN_6 | 29-JAN-17:50 | 0.00 | 0.00 | 6634.76 | 0.00 | 0.00 | 0.00 | 53.74 | 211.99 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26386.54 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 760.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2730.71 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-DEC-05:01 | 14917.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1835.66 | -13081.97 |
MIDFLOOR_PLENUM | 09-JAN-06:12 | 146608.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8410.48 | -138198.16 |
TOPFLOOR_PLENUM | 11-JAN-05:12 | 35028.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1463.82 | -33564.73 |
Total Facility | 30-JAN-06:01 | -4071.34 | 97926.66 | 1445058.72 | -97926.66 | 0.00 | 0.00 | 22385.18 | 38246.31 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204406.04 | 0.00 | -49973.89 | -1515601.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.5168 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.8579 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 119.7014 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.5570 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.2726 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2382 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4199 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4199 | 0.1869 | 1.0000 | Not calculated | 1.2002 | 0.1869 | ||
AIRLOOP DATACENTER BASEMENT | 24.4620 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4622 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5646 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5646 | 0.0277 | 1.0000 | Not calculated | 0.0156 | 0.0277 | ||
AIRLOOP DATACENTER MID | 5.4026 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4026 | 0.0289 | 1.0000 | Not calculated | 0.1563 | 0.0289 | ||
AIRLOOP DATACENTER TOP | 0.5500 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5500 | 0.0284 | 1.0000 | Not calculated | 0.0156 | 0.0284 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2584 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.7551 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.8507 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 35.9104 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1363 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.6818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4199 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4199 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1869 | ||
AIRLOOP DATACENTER BASEMENT | 24.4620 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.4620 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.5646 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5646 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0277 | ||
AIRLOOP DATACENTER MID | 5.4026 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4026 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0289 | ||
AIRLOOP DATACENTER TOP | 0.5500 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5500 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0284 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4199 | 6.4199 | 6.4199 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7461 | 6.7461 | 2.0238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 63.3949 | 63.3949 | 19.0185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1353 | 6.1353 | 1.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0766 | 1.0766 | 0.3230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3370 | 1.3370 | 0.4011 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6912 | 1.6912 | 0.5074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6660 | 1.6660 | 0.4998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1312 | 10.1312 | 3.0393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0653 | 14.0653 | 4.2196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0114 | 17.0114 | 5.1034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.0986 | 15.0986 | 4.5296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2839 | 1.2839 | 0.3852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4102 | 1.4102 | 0.4231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8357 | 1.8357 | 0.5507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6075 | 1.6075 | 0.4823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5646 | 0.5646 | 0.5646 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4026 | 5.4026 | 5.4026 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5500 | 0.5500 | 0.5500 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4620 | 24.4620 | 24.4620 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.5168 | 10.8579 | 12.5168 | 3.7551 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 119.7014 | 100.5570 | 119.7014 | 35.9104 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.2726 | 11.2382 | 12.2726 | 3.6818 | 0.0000 | 1.0000 |
CAV_BAS | 6.4199 | 6.4199 | 6.4199 | 6.4199 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4620 | 24.4622 | 24.4620 | 24.4620 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5646 | 0.5646 | 0.5646 | 0.5646 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4026 | 5.4026 | 5.4026 | 5.4026 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5500 | 0.5500 | 0.5500 | 0.5500 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4199 | 6.4199 | 6.4199 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3730 | 3.3730 | 2.0238 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 31.6974 | 31.6974 | 19.0185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0677 | 3.0677 | 1.8406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5383 | 0.5383 | 0.3230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6685 | 0.6685 | 0.4011 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8456 | 0.8456 | 0.5074 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8330 | 0.8330 | 0.4998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0656 | 5.0656 | 3.0393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0326 | 7.0326 | 4.2196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5057 | 8.5057 | 5.1034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5493 | 7.5493 | 4.5296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6420 | 0.6420 | 0.3852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7051 | 0.7051 | 0.4231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9178 | 0.9178 | 0.5507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8038 | 0.8038 | 0.4823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5646 | 0.5646 | 0.5646 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4026 | 5.4026 | 5.4026 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5500 | 0.5500 | 0.5500 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.4620 | 24.4620 | 24.4620 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2584 | 3.7551 | 3.7551 | 3.7551 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.8507 | 35.9104 | 35.9104 | 35.9104 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1363 | 3.6818 | 3.6818 | 3.6818 | 0.0000 | 1.0000 |
CAV_BAS | 6.4199 | 6.4199 | 6.4199 | 6.4199 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.4620 | 24.4620 | 24.4620 | 24.4620 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5646 | 0.5646 | 0.5646 | 0.5646 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4026 | 5.4026 | 5.4026 | 5.4026 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5500 | 0.5500 | 0.5500 | 0.5500 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 113.17 |
Number of hours cooling loads not met | 485.67 |
Number of hours not met | 598.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 5671.61 | 3008975.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3247.48 | 476400.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3942.44 | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 903.27 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.51 | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2738.66 | 325068.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 434.99 | 66157.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 837.86 | 83442.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 841.38 | 52018.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 848.39 | 87977.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 30157.09 |
Natural Gas | 0.00 | 6520.00 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 36677.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.11 |
Space Heating | 0.00 |
Space Cooling | 70.11 |
Fans (All) | 59.12 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 651.05 |
Subtotal | 651.05 |
Natural Gas [MJ/m2] | |
Space Heating | 122.44 |
Service Water Heating | 18.32 |
Miscellaneous (All) | 140.76 |
Subtotal | 140.76 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.75 |
Space Heating | 15.46 |
Space Cooling | 8.85 |
Fans (All) | 7.47 |
Service Water Heating | 2.31 |
Receptacle Equipment | 41.48 |
Miscellaneous | 13.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8718.33 | 41.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8697.83 | 62.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8201.33 | 558.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
Min | 8201.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 558.67 | 0.00 | 0.00 | 0.00 |
Average | 8723.14 | 36.86 | 0.00 | 0.00 | 0.00 |
Sum | 200632.17 | 847.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368436.33 | 179.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330794.00 | 19.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2264.17 | 3.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 95487.50 | 7907.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368436.33 | 7907.50 | 0.00 | 0.00 | 0.00 |
Average | 79982.30 | 352.61 | 0.00 | 0.00 | 0.00 |
Sum | 1839593.00 | 8110.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8711.17 | 48.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8708.83 | 51.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8391.00 | 369.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
Min | 8391.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 369.00 | 0.00 | 0.00 | 0.00 |
Average | 8723.49 | 36.51 | 0.00 | 0.00 | 0.00 |
Sum | 200640.17 | 839.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368352.00 | 264.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330735.00 | 78.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330707.00 | 106.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330755.00 | 58.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98003.67 | 5391.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368352.00 | 5391.33 | 0.00 | 0.00 | 0.00 |
Average | 80078.51 | 256.41 | 0.00 | 0.00 | 0.00 |
Sum | 1841805.67 | 5897.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480240E+11 | 111728.48 | 02-JAN-04:11 | -0.4 | -2.9 | 0.535418E+10 | 7499.18 | 13-JAN-14:30 | 8.90 | 4.37 |
February | 0.431146E+11 | 111032.38 | 21-FEB-04:01 | 6.88 | 1.33 | 0.504758E+10 | 7499.21 | 06-FEB-10:00 | 6.88 | 1.33 |
March | 0.535255E+11 | 108843.47 | 20-MAR-03:01 | -1.6 | -3.4 | 0.611680E+10 | 7499.15 | 06-MAR-10:50 | -1.6 | -3.4 |
April | 0.514433E+11 | 110281.74 | 24-APR-03:02 | 4.82 | 3.52 | 0.544585E+10 | 7499.14 | 04-APR-09:09 | 4.82 | 3.52 |
May | 0.544044E+11 | 112411.30 | 30-MAY-03:02 | 15.60 | 10.52 | 0.589981E+10 | 7499.79 | 02-MAY-13:20 | 15.60 | 10.52 |
June | 0.588288E+11 | 112888.39 | 05-JUN-03:02 | 8.62 | 5.44 | 0.588127E+10 | 7499.11 | 20-JUN-13:20 | 27.77 | 18.21 |
July | 0.611302E+11 | 111648.41 | 05-JUL-03:02 | 9.90 | 9.28 | 0.547407E+10 | 7499.21 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.681508E+11 | 112338.43 | 14-AUG-03:02 | 12.20 | 10.20 | 0.613850E+10 | 7499.05 | 01-AUG-13:20 | 12.20 | 10.20 |
September | 0.588644E+11 | 112864.53 | 11-SEP-03:02 | 11.10 | 10.41 | 0.545257E+10 | 7499.34 | 07-SEP-09:00 | 11.10 | 10.41 |
October | 0.602477E+11 | 112117.63 | 30-OCT-03:02 | 5.82 | 2.52 | 0.567038E+10 | 7499.08 | 06-OCT-09:00 | 5.82 | 2.52 |
November | 0.557192E+11 | 112007.94 | 20-NOV-04:01 | -1.7 | -4.9 | 0.561276E+10 | 7499.05 | 03-NOV-09:09 | -1.7 | -4.9 |
December | 0.531149E+11 | 111379.76 | 26-DEC-04:01 | -6.3 | -8.0 | 0.541246E+10 | 7499.17 | 07-DEC-10:09 | -6.3 | -8.0 |
Annual Sum or Average | 0.666568E+12 | 0.675062E+11 | ||||||||
Minimum of Months | 0.431146E+11 | 108843.47 | -6.3 | -8.0 | 0.504758E+10 | 7499.05 | -6.3 | -8.0 | ||
Maximum of Months | 0.681508E+11 | 112888.39 | 15.60 | 10.52 | 0.613850E+10 | 7499.79 | 27.77 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317375E+11 | 85689.76 | 02-JAN-06:02 | -1.3 | -3.4 | 0.495291E+10 | 6734.77 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.340286E+11 | 86823.56 | 28-FEB-05:01 | -3.4 | -4.0 | 0.457316E+10 | 6734.74 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.477226E+11 | 88639.44 | 20-MAR-04:02 | -1.1 | -3.1 | 0.549218E+10 | 6734.79 | 01-MAR-10:09 | -1.1 | -3.1 |
April | 0.521193E+11 | 90943.46 | 10-APR-03:02 | 4.40 | 0.24 | 0.488358E+10 | 6734.78 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.491476E+11 | 93872.97 | 30-MAY-03:02 | 15.60 | 10.52 | 0.528982E+10 | 6735.16 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.598758E+11 | 91751.84 | 05-JUN-03:02 | 8.62 | 5.44 | 0.526947E+10 | 6734.81 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.662267E+11 | 94681.66 | 05-JUL-03:02 | 9.90 | 9.28 | 0.489769E+10 | 6734.96 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.743314E+11 | 90441.61 | 23-AUG-03:02 | 11.20 | 7.14 | 0.549787E+10 | 6734.79 | 01-AUG-13:09 | 11.20 | 7.14 |
September | 0.520856E+11 | 94871.92 | 11-SEP-03:02 | 11.10 | 10.41 | 0.488236E+10 | 6735.13 | 07-SEP-09:50 | 11.10 | 10.41 |
October | 0.499802E+11 | 90205.02 | 02-OCT-03:02 | 5.00 | 2.94 | 0.507988E+10 | 6734.74 | 27-OCT-09:20 | 8.13 | 3.61 |
November | 0.453272E+11 | 90980.79 | 06-NOV-04:02 | -2.8 | -3.9 | 0.502850E+10 | 6734.74 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.414509E+11 | 87296.87 | 07-DEC-05:01 | -1.6 | -2.7 | 0.488885E+10 | 6734.78 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.604033E+12 | 0.607363E+11 | ||||||||
Minimum of Months | 0.317375E+11 | 85689.76 | -3.4 | -4.0 | 0.457316E+10 | 6734.74 | -2.8 | -3.9 | ||
Maximum of Months | 0.743314E+11 | 94871.92 | 15.60 | 10.52 | 0.549787E+10 | 6735.16 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224110E+11 | 22299.46 | 05-JAN-17:00 | -20.0 | -20.5 | 0.455723E+10 | 6734.50 | 04-JAN-14:00 | -20.0 | -20.5 |
February | 0.225979E+11 | 60797.01 | 28-FEB-06:02 | -3.9 | -4.3 | 0.432712E+10 | 6734.73 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.309634E+11 | 72700.29 | 30-MAR-05:02 | 0.00 | -2.1 | 0.534573E+10 | 6734.78 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.332309E+11 | 78454.85 | 08-APR-05:02 | 7.88 | 4.42 | 0.483825E+10 | 6734.77 | 04-APR-09:09 | 7.88 | 4.42 |
May | 0.376265E+11 | 81791.04 | 30-MAY-03:02 | 15.60 | 10.52 | 0.525994E+10 | 6735.19 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.471460E+11 | 82437.06 | 23-JUN-03:02 | 17.38 | 11.72 | 0.526222E+10 | 6734.84 | 20-JUN-13:09 | 17.38 | 11.72 |
July | 0.494214E+11 | 83308.83 | 19-JUL-03:02 | 21.02 | 16.34 | 0.489342E+10 | 6734.97 | 03-JUL-13:09 | 21.02 | 16.34 |
August | 0.515379E+11 | 85315.68 | 14-AUG-03:02 | 12.20 | 10.20 | 0.549573E+10 | 6734.80 | 01-AUG-13:09 | 12.20 | 10.20 |
September | 0.410934E+11 | 84391.47 | 11-SEP-03:02 | 11.10 | 10.41 | 0.486924E+10 | 6735.14 | 07-SEP-09:00 | 11.10 | 10.41 |
October | 0.342962E+11 | 78644.19 | 18-OCT-05:02 | 10.68 | 3.79 | 0.503985E+10 | 6734.74 | 27-OCT-09:20 | 8.13 | 3.61 |
November | 0.278543E+11 | 73361.53 | 08-NOV-06:02 | 10.13 | 4.88 | 0.488201E+10 | 6734.74 | 03-NOV-09:09 | 10.13 | 4.88 |
December | 0.246232E+11 | 29153.64 | 07-DEC-16:30 | 5.55 | 1.71 | 0.456840E+10 | 6734.76 | 07-DEC-10:09 | 5.55 | 1.71 |
Annual Sum or Average | 0.422802E+12 | 0.593391E+11 | ||||||||
Minimum of Months | 0.224110E+11 | 22299.46 | -20.0 | -20.5 | 0.432712E+10 | 6734.50 | -20.0 | -20.5 | ||
Maximum of Months | 0.515379E+11 | 85315.68 | 21.02 | 16.34 | 0.549573E+10 | 6735.19 | 21.02 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132437E+11 | 16185.38 | 13-JAN-17:00 | 7.80 | 3.93 | 0.400211E+10 | 6372.67 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.154331E+11 | 26421.68 | 28-FEB-17:00 | 10.00 | 4.31 | 0.387571E+10 | 6734.33 | 28-FEB-14:09 | 10.00 | 4.31 |
March | 0.216417E+11 | 29807.03 | 23-MAR-15:30 | 7.50 | 0.92 | 0.494048E+10 | 6734.60 | 02-MAR-14:20 | 7.50 | 0.92 |
April | 0.254419E+11 | 43890.06 | 26-APR-05:03 | 5.37 | 2.97 | 0.464050E+10 | 6734.64 | 13-APR-13:00 | 5.37 | 2.97 |
May | 0.322077E+11 | 76928.28 | 20-MAY-05:02 | 11.47 | 8.41 | 0.509509E+10 | 6735.17 | 02-MAY-13:09 | 11.47 | 8.41 |
June | 0.458976E+11 | 82481.49 | 21-JUN-03:02 | 19.22 | 13.03 | 0.524243E+10 | 6734.79 | 20-JUN-13:09 | 19.22 | 13.03 |
July | 0.505589E+11 | 81572.57 | 19-JUL-03:02 | 21.02 | 16.34 | 0.488847E+10 | 6734.96 | 03-JUL-13:09 | 21.02 | 16.34 |
August | 0.502235E+11 | 80738.99 | 07-AUG-03:02 | 20.60 | 11.11 | 0.548449E+10 | 6734.78 | 01-AUG-13:09 | 20.60 | 11.11 |
September | 0.355250E+11 | 82193.83 | 05-SEP-03:02 | 18.30 | 12.34 | 0.479123E+10 | 6735.10 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.250191E+11 | 51582.25 | 19-OCT-05:03 | 12.20 | 5.54 | 0.479653E+10 | 6734.68 | 18-OCT-09:09 | 12.20 | 5.54 |
November | 0.188215E+11 | 28208.22 | 03-NOV-16:00 | 14.30 | 7.69 | 0.441624E+10 | 6734.45 | 17-NOV-14:00 | 16.50 | 8.23 |
December | 0.151358E+11 | 20190.61 | 06-DEC-17:00 | 6.70 | 2.38 | 0.403736E+10 | 6734.33 | 07-DEC-14:39 | 8.30 | 2.62 |
Annual Sum or Average | 0.349149E+12 | 0.562107E+11 | ||||||||
Minimum of Months | 0.132437E+11 | 16185.38 | 5.37 | 0.92 | 0.387571E+10 | 6372.67 | 5.37 | 0.92 | ||
Maximum of Months | 0.505589E+11 | 82481.49 | 21.02 | 16.34 | 0.548449E+10 | 6735.17 | 21.02 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150980E+10 | 3154.18 | 02-JAN-06:02 | -1.3 | -3.4 | 0.495463E+09 | 802.46 | 02-JAN-14:00 | 6.10 | 1.11 |
February | 0.236360E+10 | 4506.20 | 27-FEB-16:00 | 18.90 | 7.06 | 0.484496E+09 | 845.60 | 21-FEB-14:00 | 18.90 | 7.06 |
March | 0.390053E+10 | 4953.60 | 27-MAR-14:40 | 9.63 | 2.75 | 0.633724E+09 | 845.61 | 21-MAR-13:00 | 9.63 | 2.75 |
April | 0.520127E+10 | 7392.64 | 07-APR-14:30 | 22.50 | 9.29 | 0.593423E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.587266E+10 | 12755.73 | 30-MAY-05:03 | 15.60 | 11.34 | 0.647060E+09 | 845.68 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.918081E+10 | 12610.63 | 26-JUN-05:03 | 9.87 | 8.82 | 0.659428E+09 | 845.64 | 20-JUN-13:09 | 9.87 | 8.82 |
July | 0.109850E+11 | 12918.87 | 03-JUL-05:02 | 10.65 | 9.22 | 0.614788E+09 | 846.48 | 20-JUL-13:39 | 26.70 | 14.19 |
August | 0.109711E+11 | 16290.43 | 06-AUG-16:01 | 35.50 | 16.24 | 0.689086E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.627991E+10 | 15637.02 | 04-SEP-16:51 | 32.80 | 16.77 | 0.602177E+09 | 845.67 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.471930E+10 | 6267.99 | 19-OCT-14:30 | 21.40 | 10.24 | 0.613095E+09 | 845.62 | 18-OCT-13:30 | 21.40 | 10.24 |
November | 0.351118E+10 | 4507.07 | 24-NOV-14:30 | 14.90 | 6.43 | 0.572061E+09 | 845.63 | 16-NOV-14:09 | 14.90 | 6.43 |
December | 0.259293E+10 | 3194.97 | 06-DEC-05:01 | 7.20 | 4.06 | 0.519174E+09 | 845.60 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.670881E+11 | 0.712397E+10 | ||||||||
Minimum of Months | 0.150980E+10 | 3154.18 | -1.3 | -3.4 | 0.484496E+09 | 802.46 | 6.10 | 1.11 | ||
Maximum of Months | 0.109850E+11 | 16290.43 | 35.50 | 16.77 | 0.689086E+09 | 846.48 | 35.50 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157180E+10 | 3756.16 | 02-JAN-06:02 | -1.3 | -3.4 | 0.313091E+09 | 520.16 | 17-JAN-10:39 | 5.53 | 1.42 |
February | 0.257452E+10 | 6709.06 | 27-FEB-10:00 | 11.70 | 4.23 | 0.306668E+09 | 544.95 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.435543E+10 | 9365.63 | 28-MAR-09:20 | 5.73 | 0.86 | 0.391889E+09 | 544.96 | 01-MAR-10:09 | 5.73 | 0.86 |
April | 0.572594E+10 | 11614.20 | 24-APR-08:30 | 10.30 | 6.86 | 0.366830E+09 | 544.95 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.655036E+10 | 11810.37 | 19-MAY-08:30 | 16.95 | 11.09 | 0.409401E+09 | 544.99 | 02-MAY-13:09 | 16.95 | 11.09 |
June | 0.933495E+10 | 21305.67 | 25-JUN-07:52 | 15.60 | 11.35 | 0.421566E+09 | 546.56 | 23-JUN-09:00 | 15.60 | 11.35 |
July | 0.112015E+11 | 22480.31 | 02-JUL-07:51 | 20.60 | 14.56 | 0.394655E+09 | 546.31 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.108804E+11 | 23097.67 | 06-AUG-08:41 | 26.55 | 14.17 | 0.440071E+09 | 546.47 | 11-AUG-09:50 | 27.52 | 12.49 |
September | 0.677864E+10 | 21429.73 | 04-SEP-08:52 | 26.70 | 14.88 | 0.380761E+09 | 544.98 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.506227E+10 | 8933.72 | 18-OCT-09:20 | 18.13 | 8.00 | 0.382680E+09 | 544.95 | 16-OCT-09:09 | 18.13 | 8.00 |
November | 0.353176E+10 | 6190.08 | 06-NOV-09:35 | 1.20 | -1.1 | 0.346303E+09 | 544.95 | 03-NOV-09:09 | 1.20 | -1.1 |
December | 0.230099E+10 | 3583.64 | 06-DEC-05:01 | 7.20 | 4.06 | 0.313430E+09 | 522.31 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.698685E+11 | 0.446735E+10 | ||||||||
Minimum of Months | 0.157180E+10 | 3583.64 | -1.3 | -3.4 | 0.306668E+09 | 520.16 | 1.20 | -1.1 | ||
Maximum of Months | 0.112015E+11 | 23097.67 | 26.70 | 14.88 | 0.440071E+09 | 546.56 | 27.52 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340041E+10 | 12048.22 | 19-JAN-13:30 | -6.2 | -7.9 | 0.523312E+09 | 845.64 | 13-JAN-14:30 | -6.2 | -7.9 |
February | 0.575602E+10 | 25691.50 | 26-FEB-13:22 | 15.30 | 5.63 | 0.516856E+09 | 847.14 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.820847E+10 | 19413.40 | 01-MAR-13:40 | 6.33 | 2.52 | 0.629639E+09 | 847.80 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.875281E+10 | 19309.22 | 16-APR-12:02 | 17.38 | 7.48 | 0.574372E+09 | 846.31 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.882818E+10 | 15395.07 | 19-MAY-13:30 | 26.65 | 14.96 | 0.627426E+09 | 846.15 | 19-MAY-13:00 | 27.20 | 15.02 |
June | 0.118594E+11 | 16211.72 | 25-JUN-15:12 | 24.80 | 13.02 | 0.651468E+09 | 846.26 | 30-JUN-13:20 | 27.77 | 13.75 |
July | 0.149345E+11 | 25863.69 | 02-JUL-14:32 | 24.80 | 14.09 | 0.612389E+09 | 846.92 | 19-JUL-13:00 | 29.40 | 17.26 |
August | 0.171160E+11 | 27271.99 | 06-AUG-16:01 | 35.50 | 16.24 | 0.685439E+09 | 853.33 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.121922E+11 | 27749.97 | 03-SEP-13:11 | 33.50 | 16.05 | 0.595557E+09 | 853.78 | 01-SEP-13:30 | 33.50 | 16.05 |
October | 0.103007E+11 | 28482.31 | 15-OCT-12:31 | 21.83 | 10.70 | 0.610924E+09 | 863.65 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.732717E+10 | 19300.92 | 03-NOV-13:20 | 14.13 | 7.69 | 0.578362E+09 | 847.16 | 06-NOV-14:00 | 7.80 | 2.97 |
December | 0.504236E+10 | 13777.73 | 12-DEC-12:30 | -2.8 | -5.7 | 0.535513E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.113718E+12 | 0.714126E+10 | ||||||||
Minimum of Months | 0.340041E+10 | 12048.22 | -6.2 | -7.9 | 0.516856E+09 | 845.64 | -6.2 | -7.9 | ||
Maximum of Months | 0.171160E+11 | 28482.31 | 35.50 | 16.24 | 0.685439E+09 | 863.65 | 33.50 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259928E+10 | 4895.51 | 02-JAN-05:01 | -0.2 | -2.7 | 0.316873E+09 | 531.53 | 02-JAN-14:00 | 6.10 | 1.11 |
February | 0.439852E+10 | 10319.47 | 28-FEB-16:40 | 10.37 | 4.49 | 0.318636E+09 | 544.94 | 21-FEB-14:00 | 10.37 | 4.49 |
March | 0.694024E+10 | 12863.35 | 28-MAR-16:00 | 10.60 | 3.09 | 0.413699E+09 | 544.95 | 14-MAR-13:00 | 10.60 | 3.09 |
April | 0.906426E+10 | 25904.11 | 16-APR-17:22 | 19.70 | 8.86 | 0.388597E+09 | 544.96 | 13-APR-13:00 | 19.70 | 8.86 |
May | 0.844091E+10 | 25756.48 | 13-MAY-18:22 | 21.95 | 8.73 | 0.406807E+09 | 544.99 | 02-MAY-13:09 | 21.95 | 8.73 |
June | 0.118182E+11 | 25696.33 | 18-JUN-17:02 | 25.50 | 14.50 | 0.423722E+09 | 544.97 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.148093E+11 | 30353.99 | 02-JUL-17:51 | 25.60 | 14.12 | 0.397002E+09 | 544.98 | 13-JUL-09:00 | 23.30 | 13.98 |
August | 0.163656E+11 | 30550.80 | 06-AUG-16:41 | 35.10 | 15.80 | 0.445402E+09 | 544.97 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.860920E+10 | 28533.36 | 04-SEP-16:51 | 32.80 | 16.77 | 0.378733E+09 | 544.99 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.719553E+10 | 20065.31 | 15-OCT-14:31 | 22.97 | 11.08 | 0.390859E+09 | 544.96 | 20-OCT-13:00 | 13.30 | 6.77 |
November | 0.601096E+10 | 9648.80 | 03-NOV-15:40 | 14.40 | 7.69 | 0.375643E+09 | 544.95 | 17-NOV-14:09 | 16.17 | 7.86 |
December | 0.514552E+10 | 8907.63 | 06-DEC-15:30 | 10.25 | 4.94 | 0.353013E+09 | 544.94 | 19-DEC-14:30 | 11.70 | 7.15 |
Annual Sum or Average | 0.101398E+12 | 0.460899E+10 | ||||||||
Minimum of Months | 0.259928E+10 | 4895.51 | -0.2 | -2.7 | 0.316873E+09 | 531.53 | 6.10 | 1.11 | ||
Maximum of Months | 0.163656E+11 | 30550.80 | 35.10 | 16.77 | 0.445402E+09 | 544.99 | 35.10 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188623E+09 | 1832.99 | 13-JAN-15:10 | 9.82 | 5.10 | 0.463192E+09 | 640.66 | 13-JAN-14:00 | 9.82 | 5.10 |
February | 0.761060E+09 | 3059.51 | 27-FEB-13:40 | 17.93 | 6.85 | 0.431973E+09 | 750.72 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.194713E+10 | 3031.87 | 23-MAR-13:30 | 9.70 | 2.18 | 0.546185E+09 | 801.69 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.289792E+10 | 5631.47 | 07-APR-14:30 | 22.50 | 9.29 | 0.537499E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.423957E+10 | 7688.92 | 19-MAY-16:00 | 27.80 | 14.54 | 0.609037E+09 | 845.63 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.724401E+10 | 11644.03 | 23-JUN-05:02 | 17.88 | 11.72 | 0.653166E+09 | 845.64 | 20-JUN-13:09 | 17.88 | 11.72 |
July | 0.852035E+10 | 10308.00 | 20-JUL-05:03 | 19.50 | 13.96 | 0.612850E+09 | 846.15 | 18-JUL-13:30 | 19.50 | 13.96 |
August | 0.758756E+10 | 14878.26 | 06-AUG-16:01 | 35.50 | 16.24 | 0.683036E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.473692E+10 | 10142.98 | 03-SEP-16:01 | 33.67 | 16.10 | 0.576631E+09 | 845.67 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.293305E+10 | 4846.05 | 19-OCT-14:40 | 21.50 | 10.24 | 0.554982E+09 | 845.61 | 19-OCT-13:09 | 21.50 | 10.24 |
November | 0.155760E+10 | 3011.12 | 03-NOV-13:30 | 14.35 | 7.74 | 0.492829E+09 | 798.35 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.511676E+09 | 2076.38 | 06-DEC-15:50 | 9.68 | 4.65 | 0.451793E+09 | 692.49 | 06-DEC-14:00 | 9.68 | 4.65 |
Annual Sum or Average | 0.431255E+11 | 0.661317E+10 | ||||||||
Minimum of Months | 0.188623E+09 | 1832.99 | 9.68 | 2.18 | 0.431973E+09 | 640.66 | 9.68 | 4.50 | ||
Maximum of Months | 0.852035E+10 | 14878.26 | 35.50 | 16.24 | 0.683036E+09 | 846.15 | 35.50 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345064E+09 | 2519.26 | 20-JAN-10:00 | -3.3 | -5.9 | 0.219677E+09 | 390.66 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.127473E+10 | 4566.58 | 26-FEB-11:52 | 13.30 | 4.89 | 0.206728E+09 | 521.16 | 28-FEB-09:00 | 1.10 | -0.5 |
March | 0.277543E+10 | 7339.60 | 28-MAR-10:05 | 7.38 | 1.58 | 0.261094E+09 | 521.21 | 22-MAR-10:20 | 7.38 | 1.58 |
April | 0.429994E+10 | 10811.08 | 24-APR-09:00 | 11.70 | 7.62 | 0.253034E+09 | 521.20 | 13-APR-12:20 | 11.70 | 7.62 |
May | 0.563932E+10 | 12271.44 | 19-MAY-08:50 | 17.52 | 11.29 | 0.287491E+09 | 521.26 | 02-MAY-12:09 | 17.52 | 11.29 |
June | 0.876308E+10 | 21090.55 | 04-JUN-07:42 | 15.63 | 13.07 | 0.306151E+09 | 522.83 | 23-JUN-10:09 | 27.98 | 15.45 |
July | 0.104569E+11 | 23370.12 | 02-JUL-07:41 | 20.03 | 14.35 | 0.289511E+09 | 523.14 | 25-JUL-10:50 | 31.52 | 15.07 |
August | 0.959074E+10 | 25062.17 | 06-AUG-09:21 | 28.60 | 14.63 | 0.320648E+09 | 523.35 | 10-AUG-10:50 | 31.52 | 14.77 |
September | 0.598877E+10 | 21403.15 | 03-SEP-11:21 | 31.10 | 15.57 | 0.267862E+09 | 521.21 | 06-SEP-15:30 | 26.40 | 18.80 |
October | 0.382347E+10 | 7535.97 | 18-OCT-10:10 | 20.28 | 8.90 | 0.257848E+09 | 521.21 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.192971E+10 | 4076.77 | 03-NOV-13:00 | 13.70 | 7.60 | 0.229111E+09 | 519.86 | 03-NOV-10:30 | 13.70 | 7.60 |
December | 0.648892E+09 | 2740.63 | 07-DEC-11:20 | 6.67 | 2.71 | 0.212445E+09 | 415.90 | 07-DEC-11:30 | 6.95 | 2.80 |
Annual Sum or Average | 0.555360E+11 | 0.311160E+10 | ||||||||
Minimum of Months | 0.345064E+09 | 2519.26 | -3.3 | -5.9 | 0.206728E+09 | 390.66 | -3.3 | -5.9 | ||
Maximum of Months | 0.104569E+11 | 25062.17 | 31.10 | 15.57 | 0.320648E+09 | 523.35 | 31.52 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233142E+10 | 11615.32 | 19-JAN-14:00 | -5.6 | -7.5 | 0.503844E+09 | 845.64 | 13-JAN-14:00 | -5.6 | -7.5 |
February | 0.469543E+10 | 28028.78 | 26-FEB-13:12 | 15.20 | 5.59 | 0.496684E+09 | 846.07 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.662536E+10 | 20448.61 | 01-MAR-14:00 | 6.70 | 2.77 | 0.596862E+09 | 851.72 | 01-MAR-14:09 | 6.97 | 2.89 |
April | 0.680130E+10 | 24811.53 | 16-APR-13:12 | 18.67 | 7.93 | 0.546021E+09 | 845.86 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.769590E+10 | 15805.83 | 19-MAY-13:30 | 26.65 | 14.96 | 0.607184E+09 | 846.15 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.103847E+11 | 15549.42 | 30-JUN-13:30 | 28.05 | 13.89 | 0.640948E+09 | 846.11 | 30-JUN-13:00 | 28.90 | 14.31 |
July | 0.127917E+11 | 25485.55 | 16-JUL-15:12 | 33.13 | 18.76 | 0.607948E+09 | 846.58 | 19-JUL-13:00 | 29.40 | 17.26 |
August | 0.142678E+11 | 27588.52 | 06-AUG-16:01 | 35.50 | 16.24 | 0.677608E+09 | 867.53 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.115527E+11 | 30660.34 | 03-SEP-12:41 | 33.22 | 15.94 | 0.582576E+09 | 879.22 | 01-SEP-13:50 | 33.22 | 15.94 |
October | 0.926272E+10 | 27245.48 | 15-OCT-13:22 | 22.75 | 10.91 | 0.592833E+09 | 890.65 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.571179E+10 | 19832.34 | 03-NOV-13:30 | 14.35 | 7.74 | 0.553513E+09 | 846.29 | 06-NOV-14:00 | 7.80 | 2.97 |
December | 0.315333E+10 | 11909.96 | 12-DEC-14:30 | -2.2 | -5.4 | 0.503341E+09 | 845.63 | 14-DEC-14:09 | 3.40 | -0.7 |
Annual Sum or Average | 0.952741E+11 | 0.690936E+10 | ||||||||
Minimum of Months | 0.233142E+10 | 11615.32 | -5.6 | -7.5 | 0.496684E+09 | 845.63 | -5.6 | -7.5 | ||
Maximum of Months | 0.142678E+11 | 30660.34 | 35.50 | 18.76 | 0.677608E+09 | 890.65 | 33.22 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515323E+09 | 3477.56 | 13-JAN-15:50 | 9.08 | 4.76 | 0.301442E+09 | 463.97 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.153591E+10 | 7175.20 | 28-FEB-16:40 | 10.37 | 4.49 | 0.282979E+09 | 521.21 | 27-FEB-16:40 | 10.37 | 4.49 |
March | 0.303027E+10 | 8764.54 | 28-MAR-16:00 | 10.60 | 3.09 | 0.347570E+09 | 544.93 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.457375E+10 | 22853.94 | 16-APR-17:11 | 19.80 | 8.90 | 0.330372E+09 | 544.94 | 07-APR-13:00 | 19.80 | 8.90 |
May | 0.616008E+10 | 25407.65 | 28-MAY-18:01 | 19.82 | 10.31 | 0.374323E+09 | 544.94 | 30-MAY-13:00 | 18.90 | 10.34 |
June | 0.854858E+10 | 23178.33 | 18-JUN-17:22 | 25.30 | 14.49 | 0.406350E+09 | 544.96 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.100300E+11 | 25059.52 | 16-JUL-17:11 | 33.13 | 17.22 | 0.388442E+09 | 544.97 | 03-JUL-13:09 | 33.13 | 17.22 |
August | 0.938165E+10 | 26356.80 | 06-AUG-16:41 | 35.10 | 15.80 | 0.427986E+09 | 544.96 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.635409E+10 | 24039.07 | 03-SEP-16:01 | 33.67 | 16.10 | 0.351598E+09 | 544.95 | 05-SEP-09:09 | 17.20 | 11.96 |
October | 0.421793E+10 | 10200.01 | 16-OCT-16:00 | 19.40 | 8.07 | 0.340899E+09 | 544.06 | 13-OCT-13:00 | 19.40 | 8.07 |
November | 0.234640E+10 | 5566.46 | 03-NOV-15:50 | 14.35 | 7.69 | 0.317454E+09 | 533.39 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.978039E+09 | 3792.19 | 06-DEC-15:50 | 9.68 | 4.65 | 0.293849E+09 | 493.98 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.576720E+11 | 0.416326E+10 | ||||||||
Minimum of Months | 0.515323E+09 | 3477.56 | 9.08 | 3.09 | 0.282979E+09 | 463.97 | 8.90 | 3.09 | ||
Maximum of Months | 0.100300E+11 | 26356.80 | 35.10 | 17.22 | 0.427986E+09 | 544.97 | 35.10 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43748169.31 | 2085.86 | 14-JAN-17:03 | 8.90 | 4.06 | 0.459150E+09 | 626.07 | 06-JAN-10:50 | 8.90 | 4.06 |
February | 0.333491E+09 | 2761.66 | 27-FEB-13:30 | 17.75 | 6.76 | 0.422471E+09 | 689.60 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.117136E+10 | 3009.94 | 23-MAR-13:30 | 9.70 | 2.18 | 0.515496E+09 | 725.92 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.238490E+10 | 5180.85 | 07-APR-14:30 | 22.50 | 9.29 | 0.493087E+09 | 845.60 | 07-APR-13:09 | 22.50 | 9.29 |
May | 0.400092E+10 | 8364.42 | 19-MAY-16:00 | 27.80 | 14.54 | 0.572170E+09 | 845.63 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.733480E+10 | 11997.29 | 23-JUN-05:02 | 17.88 | 11.72 | 0.637243E+09 | 845.64 | 20-JUN-13:09 | 17.88 | 11.72 |
July | 0.895192E+10 | 16288.60 | 16-JUL-18:31 | 32.40 | 17.11 | 0.607526E+09 | 845.65 | 03-JUL-13:09 | 32.40 | 17.11 |
August | 0.775263E+10 | 13844.14 | 06-AUG-16:11 | 35.40 | 16.13 | 0.667967E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.456385E+10 | 8680.26 | 05-SEP-14:00 | 24.40 | 15.14 | 0.543882E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.227280E+10 | 4328.94 | 18-OCT-14:20 | 25.00 | 11.47 | 0.506164E+09 | 845.60 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.821103E+09 | 2775.67 | 08-NOV-15:30 | 12.80 | 7.38 | 0.466364E+09 | 717.89 | 08-NOV-14:00 | 12.80 | 7.38 |
December | 0.177082E+09 | 2293.02 | 06-DEC-16:00 | 9.40 | 4.51 | 0.446669E+09 | 633.77 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.398086E+11 | 0.633819E+10 | ||||||||
Minimum of Months | 43748169.31 | 2085.86 | 8.90 | 2.18 | 0.422471E+09 | 626.07 | 8.90 | 4.06 | ||
Maximum of Months | 0.895192E+10 | 16288.60 | 35.40 | 17.11 | 0.667967E+09 | 845.66 | 35.40 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97577953.20 | 2457.96 | 13-JAN-06:04 | 0.50 | -2.4 | 0.298680E+09 | 403.50 | 09-JAN-10:00 | 0.50 | -2.4 |
February | 0.784220E+09 | 3372.48 | 28-FEB-10:40 | 2.97 | 0.62 | 0.276031E+09 | 499.41 | 28-FEB-10:50 | 3.43 | 0.87 |
March | 0.194132E+10 | 5686.81 | 23-MAR-10:30 | 8.60 | 1.66 | 0.346520E+09 | 544.95 | 28-MAR-09:39 | 6.47 | 1.20 |
April | 0.340722E+10 | 9798.22 | 25-APR-09:40 | 11.27 | 5.45 | 0.336762E+09 | 544.95 | 25-APR-09:09 | 11.27 | 5.45 |
May | 0.505401E+10 | 11836.27 | 19-MAY-09:20 | 18.53 | 11.74 | 0.385749E+09 | 544.99 | 02-MAY-13:09 | 18.53 | 11.74 |
June | 0.864884E+10 | 22635.34 | 25-JUN-09:02 | 17.15 | 11.95 | 0.415169E+09 | 545.93 | 23-JUN-09:00 | 17.15 | 11.95 |
July | 0.106806E+11 | 22318.50 | 16-JUL-09:12 | 22.57 | 16.22 | 0.392547E+09 | 546.22 | 13-JUL-09:50 | 22.57 | 16.22 |
August | 0.954453E+10 | 22553.57 | 06-AUG-09:32 | 29.07 | 14.77 | 0.435850E+09 | 546.05 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.541316E+10 | 16548.09 | 04-SEP-09:02 | 26.88 | 14.90 | 0.359769E+09 | 544.95 | 15-SEP-13:09 | 19.08 | 11.71 |
October | 0.294461E+10 | 6411.26 | 18-OCT-10:00 | 20.00 | 8.80 | 0.337833E+09 | 544.95 | 18-OCT-09:09 | 20.00 | 8.80 |
November | 0.113897E+10 | 3307.93 | 03-NOV-10:00 | 8.70 | 5.33 | 0.301896E+09 | 490.30 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.279345E+09 | 2481.82 | 09-DEC-06:04 | -5.1 | -5.7 | 0.288257E+09 | 407.02 | 06-DEC-10:50 | -5.1 | -5.7 |
Annual Sum or Average | 0.499344E+11 | 0.417506E+10 | ||||||||
Minimum of Months | 97577953.20 | 2457.96 | -5.1 | -5.7 | 0.276031E+09 | 403.50 | -5.1 | -5.7 | ||
Maximum of Months | 0.106806E+11 | 22635.34 | 29.07 | 16.22 | 0.435850E+09 | 546.22 | 27.80 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156949E+10 | 9656.95 | 31-JAN-13:40 | -0.8 | -4.5 | 0.487618E+09 | 845.63 | 31-JAN-14:30 | -0.9 | -4.4 |
February | 0.355052E+10 | 27512.63 | 26-FEB-14:21 | 16.15 | 6.12 | 0.474980E+09 | 845.82 | 28-FEB-14:00 | 10.60 | 4.78 |
March | 0.511860E+10 | 18718.32 | 01-MAR-14:10 | 6.97 | 2.89 | 0.573192E+09 | 846.16 | 23-MAR-13:50 | 9.90 | 2.40 |
April | 0.556586E+10 | 17679.10 | 25-APR-13:40 | 16.30 | 6.98 | 0.522425E+09 | 845.86 | 24-APR-13:00 | 16.30 | 6.98 |
May | 0.694045E+10 | 16380.47 | 19-MAY-13:50 | 27.02 | 15.00 | 0.587448E+09 | 845.71 | 02-MAY-13:09 | 27.02 | 15.00 |
June | 0.102636E+11 | 19277.38 | 25-JUN-15:02 | 24.90 | 13.05 | 0.627992E+09 | 845.67 | 20-JUN-13:09 | 24.90 | 13.05 |
July | 0.131604E+11 | 27848.79 | 16-JUL-13:52 | 31.70 | 18.44 | 0.601856E+09 | 846.48 | 19-JUL-13:50 | 29.68 | 17.39 |
August | 0.142849E+11 | 28943.26 | 06-AUG-13:32 | 34.23 | 15.17 | 0.667615E+09 | 849.62 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.107619E+11 | 30587.20 | 03-SEP-13:31 | 33.70 | 16.17 | 0.564754E+09 | 860.86 | 01-SEP-13:50 | 33.70 | 16.17 |
October | 0.756288E+10 | 29486.48 | 15-OCT-15:02 | 22.70 | 11.00 | 0.566148E+09 | 854.85 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.425078E+10 | 18101.60 | 03-NOV-13:30 | 14.35 | 7.74 | 0.526003E+09 | 845.81 | 03-NOV-13:00 | 15.00 | 7.85 |
December | 0.211469E+10 | 9396.43 | 06-DEC-14:40 | 11.30 | 5.42 | 0.482829E+09 | 845.63 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.851441E+11 | 0.668286E+10 | ||||||||
Minimum of Months | 0.156949E+10 | 9396.43 | -0.8 | -4.5 | 0.474980E+09 | 845.63 | -0.9 | -4.4 | ||
Maximum of Months | 0.142849E+11 | 30587.20 | 34.23 | 18.44 | 0.667615E+09 | 860.86 | 33.70 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259327E+09 | 3477.46 | 13-JAN-15:50 | 9.08 | 4.76 | 0.299353E+09 | 444.22 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.102082E+10 | 6563.70 | 28-FEB-16:40 | 10.37 | 4.49 | 0.278741E+09 | 521.19 | 27-FEB-16:19 | 10.37 | 4.49 |
March | 0.213351E+10 | 8310.56 | 28-MAR-16:00 | 10.60 | 3.09 | 0.339878E+09 | 543.18 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.378274E+10 | 18279.34 | 16-APR-17:11 | 19.80 | 8.90 | 0.317298E+09 | 543.25 | 25-APR-13:00 | 16.10 | 6.69 |
May | 0.564424E+10 | 26835.91 | 28-MAY-18:01 | 19.82 | 10.31 | 0.362030E+09 | 544.95 | 19-MAY-13:09 | 19.82 | 10.31 |
June | 0.847788E+10 | 24627.15 | 18-JUN-17:22 | 25.30 | 14.49 | 0.396892E+09 | 544.96 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.102817E+11 | 27584.86 | 09-JUL-16:41 | 28.30 | 12.98 | 0.383555E+09 | 544.97 | 03-JUL-13:09 | 28.30 | 12.98 |
August | 0.937683E+10 | 25648.46 | 06-AUG-16:11 | 35.40 | 16.13 | 0.419434E+09 | 544.96 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.588147E+10 | 25575.92 | 04-SEP-17:01 | 32.62 | 16.70 | 0.340408E+09 | 544.94 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.330285E+10 | 9988.47 | 18-OCT-16:00 | 24.40 | 11.02 | 0.326453E+09 | 525.64 | 13-OCT-13:00 | 24.40 | 11.02 |
November | 0.153340E+10 | 4821.57 | 03-NOV-15:50 | 14.35 | 7.69 | 0.307699E+09 | 521.17 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.540465E+09 | 3781.48 | 06-DEC-15:50 | 9.68 | 4.65 | 0.290174E+09 | 471.06 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.522352E+11 | 0.406191E+10 | ||||||||
Minimum of Months | 0.259327E+09 | 3477.46 | 9.08 | 3.09 | 0.278741E+09 | 444.22 | 8.90 | 3.09 | ||
Maximum of Months | 0.102817E+11 | 27584.86 | 35.40 | 16.70 | 0.419434E+09 | 544.97 | 35.40 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.682721E+09 | 7725.21 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.103301E+10 | 5665.94 | 28-FEB-06:08 | -3.9 | -4.3 | 0.00 | 0.00 | 01-FEB-00:10 | -3.9 | -4.3 |
March | 0.256497E+10 | 5312.50 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.426985E+10 | 6048.70 | 25-APR-05:15 | 1.10 | -0.7 | 0.00 | 0.00 | 01-APR-00:10 | 1.10 | -0.7 |
May | 0.433834E+10 | 9818.21 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.776956E+10 | 8937.68 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.974827E+10 | 10514.54 | 31-JUL-05:15 | 14.60 | 10.97 | 0.00 | 0.00 | 01-JUL-00:10 | 14.60 | 10.97 |
August | 0.101712E+11 | 11554.42 | 07-AUG-05:15 | 17.77 | 10.09 | 0.00 | 0.00 | 01-AUG-00:10 | 17.77 | 10.09 |
September | 0.604158E+10 | 14003.90 | 05-SEP-05:15 | 18.50 | 11.75 | 0.00 | 0.00 | 01-SEP-00:10 | 18.50 | 11.75 |
October | 0.437484E+10 | 5711.03 | 02-OCT-05:15 | 4.80 | 2.86 | 0.00 | 0.00 | 01-OCT-00:10 | 4.80 | 2.86 |
November | 0.259337E+10 | 6122.83 | 06-NOV-06:07 | -3.5 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.5 | -4.3 |
December | 0.128179E+10 | 4409.69 | 09-DEC-06:07 | -5.1 | -5.7 | 0.00 | 0.00 | 01-DEC-00:10 | -5.1 | -5.7 |
Annual Sum or Average | 0.548696E+11 | 0.00 | ||||||||
Minimum of Months | 0.682721E+09 | 4409.69 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.101712E+11 | 14003.90 | 18.50 | 11.75 | 0.00 | 0.00 | 18.50 | 11.75 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441798E+09 | 10393.84 | 06-JAN-04:11 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.367042E+09 | 9283.22 | 04-FEB-04:01 | -21.9 | -22.2 | 0.00 | 0.00 | 01-FEB-00:10 | -21.9 | -22.2 |
March | 0.104429E+10 | 11251.97 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.181807E+10 | 6537.90 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.251695E+10 | 6861.90 | 08-MAY-04:01 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.568103E+10 | 6922.24 | 22-JUN-05:15 | 16.10 | 12.59 | 0.00 | 0.00 | 01-JUN-00:10 | 16.10 | 12.59 |
July | 0.733787E+10 | 8085.29 | 17-JUL-15:40 | 36.83 | 17.19 | 0.00 | 0.00 | 01-JUL-00:10 | 36.83 | 17.19 |
August | 0.719658E+10 | 8196.27 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.434519E+10 | 7925.50 | 05-SEP-14:50 | 24.40 | 14.84 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.84 |
October | 0.220580E+10 | 6097.50 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.103645E+10 | 8875.89 | 27-NOV-04:01 | -15.8 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.8 | -16.7 |
December | 0.610829E+09 | 8195.77 | 29-DEC-04:01 | -24.5 | -24.8 | 0.00 | 0.00 | 01-DEC-00:10 | -24.5 | -24.8 |
Annual Sum or Average | 0.346019E+11 | 0.00 | ||||||||
Minimum of Months | 0.367042E+09 | 6097.50 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.733787E+10 | 11251.97 | 36.83 | 17.19 | 0.00 | 0.00 | 36.83 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15997.73 | 106.65 | 14-JAN-17:10 | 8.90 | 4.06 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 4.06 |
February | 95437794.01 | 2356.28 | 26-FEB-15:07 | 16.60 | 6.44 | 0.00 | 0.00 | 01-FEB-00:10 | 16.60 | 6.44 |
March | 0.582116E+09 | 4722.57 | 23-MAR-13:50 | 9.90 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 9.90 | 2.40 |
April | 0.222066E+10 | 11197.31 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.476256E+10 | 16794.04 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.983082E+10 | 19593.51 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.130322E+11 | 23043.35 | 17-JUL-15:10 | 36.28 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 36.28 | 17.05 |
August | 0.111281E+11 | 20548.87 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.524412E+10 | 15101.18 | 05-SEP-14:40 | 24.40 | 14.90 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.90 |
October | 0.140643E+10 | 8736.54 | 18-OCT-15:10 | 24.90 | 11.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.90 | 11.51 |
November | 0.104728E+09 | 2174.14 | 03-NOV-14:10 | 14.93 | 7.82 | 0.00 | 0.00 | 01-NOV-00:10 | 14.93 | 7.82 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.484072E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.130322E+11 | 23043.35 | 36.28 | 17.05 | 0.00 | 0.00 | 36.28 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201969E+10 | 1980.93 | 19-JAN-16:50 | -6.4 | -8.0 | 95180074.29 | 126.82 | 02-JAN-10:09 | -6.4 | -8.0 |
February | 0.723711E+10 | 4315.35 | 28-FEB-17:00 | 10.00 | 4.31 | 86396454.73 | 126.82 | 02-FEB-14:09 | 10.00 | 4.31 |
March | 0.137747E+11 | 6834.60 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.50 | 0.99 |
April | 0.187440E+11 | 8241.22 | 22-APR-18:10 | 15.63 | 8.19 | 91605256.35 | 126.82 | 20-APR-13:00 | 15.63 | 8.19 |
May | 0.421289E+10 | 3506.71 | 31-MAY-24:00 | 15.50 | 10.27 | 99234981.46 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.932884E+10 | 5359.07 | 30-JUN-24:00 | 19.60 | 12.23 | 98962606.91 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.148240E+11 | 7239.20 | 31-JUL-23:35 | 19.77 | 11.91 | 91883758.73 | 126.84 | 03-JUL-13:09 | 19.77 | 11.91 |
August | 0.198949E+11 | 8218.20 | 29-AUG-17:50 | 23.90 | 12.71 | 0.103515E+09 | 133.36 | 11-AUG-13:00 | 23.90 | 12.71 |
September | 0.419490E+10 | 3316.17 | 30-SEP-24:00 | 11.80 | 6.26 | 91610960.71 | 126.86 | 06-SEP-13:50 | 11.80 | 6.26 |
October | 0.915534E+10 | 4965.71 | 31-OCT-24:00 | 4.70 | 1.47 | 95230928.37 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.134092E+11 | 6077.34 | 13-NOV-16:20 | 3.27 | -2.5 | 94300329.95 | 126.83 | 08-NOV-14:00 | 3.27 | -2.5 |
December | 0.184029E+11 | 7853.15 | 06-DEC-16:10 | 8.95 | 4.16 | 91880816.28 | 126.82 | 04-DEC-14:50 | 8.95 | 4.16 |
Annual Sum or Average | 0.135199E+12 | 0.114304E+10 | ||||||||
Minimum of Months | 0.201969E+10 | 1980.93 | -6.4 | -8.0 | 86396454.73 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.198949E+11 | 8241.22 | 23.90 | 12.71 | 0.103515E+09 | 133.36 | 23.90 | 12.71 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513429E+09 | 1617.99 | 19-JAN-16:50 | -6.4 | -8.0 | 93322651.35 | 126.93 | 31-JAN-10:00 | -5.0 | -7.7 |
February | 0.502283E+10 | 3943.24 | 28-FEB-17:00 | 10.00 | 4.31 | 86396467.06 | 126.82 | 17-FEB-14:20 | 10.00 | 4.31 |
March | 0.113951E+11 | 5924.91 | 31-MAR-23:30 | 2.00 | 0.53 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.00 | 0.53 |
April | 0.167910E+11 | 7806.77 | 25-APR-18:10 | 16.73 | 7.64 | 91605289.01 | 126.82 | 24-APR-09:09 | 16.73 | 7.64 |
May | 0.323062E+10 | 3309.65 | 31-MAY-24:00 | 15.50 | 10.27 | 99234857.04 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.854312E+10 | 5241.94 | 30-JUN-24:00 | 19.60 | 12.23 | 98962343.83 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.139855E+11 | 7067.02 | 31-JUL-23:55 | 19.20 | 11.32 | 91883948.32 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.186822E+11 | 7836.85 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103356E+09 | 131.23 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.338163E+10 | 2886.21 | 30-SEP-23:40 | 12.27 | 6.64 | 91609777.88 | 126.84 | 11-SEP-13:00 | 12.27 | 6.64 |
October | 0.750762E+10 | 4161.96 | 31-OCT-24:00 | 4.70 | 1.47 | 95230855.15 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.109711E+11 | 5550.58 | 03-NOV-16:00 | 14.30 | 7.69 | 94300350.55 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.148987E+11 | 7146.80 | 06-DEC-16:20 | 8.50 | 3.80 | 91880839.67 | 126.82 | 18-DEC-14:39 | 0.60 | -2.8 |
Annual Sum or Average | 0.114923E+12 | 0.114102E+10 | ||||||||
Minimum of Months | 0.513429E+09 | 1617.99 | -6.4 | -8.0 | 86396467.06 | 126.82 | -5.0 | -7.7 | ||
Maximum of Months | 0.186822E+11 | 7836.85 | 24.60 | 12.54 | 0.103356E+09 | 131.23 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201331E+09 | 1412.43 | 13-JAN-16:30 | 8.35 | 4.30 | 88195039.26 | 128.11 | 13-JAN-10:20 | 8.35 | 4.30 |
February | 0.341619E+10 | 3888.33 | 28-FEB-17:00 | 10.00 | 4.31 | 86391041.43 | 126.82 | 03-FEB-14:20 | 10.00 | 4.31 |
March | 0.972390E+10 | 5844.66 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.155993E+11 | 7859.35 | 25-APR-18:10 | 16.73 | 7.64 | 91605316.29 | 126.82 | 21-APR-09:00 | 16.73 | 7.64 |
May | 0.264916E+10 | 3227.06 | 31-MAY-24:00 | 15.50 | 10.27 | 98938187.53 | 126.92 | 09-MAY-09:09 | 15.50 | 10.27 |
June | 0.830857E+10 | 5241.29 | 30-JUN-24:00 | 19.60 | 12.23 | 98962428.58 | 126.84 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.139123E+11 | 7015.60 | 31-JUL-23:55 | 19.20 | 11.32 | 91884000.36 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.185280E+11 | 7952.55 | 03-AUG-18:40 | 24.80 | 12.58 | 0.103322E+09 | 129.46 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.284575E+10 | 2786.97 | 04-SEP-17:32 | 32.07 | 16.48 | 91608024.72 | 126.84 | 05-SEP-09:00 | 17.20 | 11.96 |
October | 0.609368E+10 | 4034.26 | 18-OCT-17:00 | 21.70 | 10.27 | 95230835.25 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.905619E+10 | 5476.74 | 03-NOV-16:00 | 14.30 | 7.69 | 94300356.97 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.128116E+11 | 7048.30 | 06-DEC-16:20 | 8.50 | 3.80 | 91880847.24 | 126.82 | 27-DEC-14:20 | -15.4 | -15.9 |
Annual Sum or Average | 0.103146E+12 | 0.113555E+10 | ||||||||
Minimum of Months | 0.201331E+09 | 1412.43 | 8.35 | 2.32 | 86391041.43 | 126.82 | -15.4 | -15.9 | ||
Maximum of Months | 0.185280E+11 | 7952.55 | 32.07 | 16.48 | 0.103322E+09 | 129.46 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234226E+12 | 91682.57 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206142E+10 | 2745.29 | 02-JAN-14:00 | 2.20 | -1.7 |
February | 0.433314E+12 | 183625.07 | 28-FEB-17:00 | 10.00 | 4.31 | 0.187202E+10 | 2748.44 | 10-FEB-10:09 | 10.00 | 4.31 |
March | 0.726961E+12 | 357618.64 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223629E+10 | 2747.51 | 03-MAR-10:00 | 2.50 | 0.99 |
April | 0.941031E+12 | 367084.58 | 26-APR-16:00 | 9.40 | 4.24 | 0.199585E+10 | 3008.79 | 07-APR-13:00 | 9.40 | 4.24 |
May | 0.239968E+12 | 176046.09 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214841E+10 | 2747.90 | 30-MAY-13:00 | 15.50 | 10.27 |
June | 0.469948E+12 | 267987.34 | 30-JUN-24:00 | 19.60 | 12.23 | 0.214395E+10 | 2748.66 | 20-JUN-13:50 | 19.60 | 12.23 |
July | 0.732512E+12 | 359225.79 | 31-JUL-23:12 | 20.33 | 12.51 | 0.198985E+10 | 2750.06 | 18-JUL-09:00 | 20.33 | 12.51 |
August | 0.972051E+12 | 369521.79 | 22-AUG-07:20 | 12.77 | 9.84 | 0.254859E+10 | 3863.51 | 07-AUG-13:00 | 12.77 | 9.84 |
September | 0.235600E+12 | 175720.50 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198353E+10 | 2748.17 | 06-SEP-13:39 | 11.80 | 6.26 |
October | 0.486898E+12 | 267723.28 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206337E+10 | 2748.50 | 24-OCT-13:09 | 4.70 | 1.47 |
November | 0.707098E+12 | 276676.74 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204275E+10 | 2747.58 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.973608E+12 | 367838.30 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198912E+10 | 2745.72 | 05-DEC-14:20 | 6.70 | 2.38 |
Annual Sum or Average | 0.715322E+13 | 0.250752E+11 | ||||||||
Minimum of Months | 0.234226E+12 | 91682.57 | 2.20 | -1.7 | 0.187202E+10 | 2745.29 | 2.20 | -1.7 | ||
Maximum of Months | 0.973608E+12 | 369521.79 | 20.33 | 12.51 | 0.254859E+10 | 3863.51 | 20.33 | 12.51 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305745E+09 | 14079.44 | 02-JAN-04:54 | 0.00 |
February | 71849494.39 | 14214.15 | 21-FEB-05:25 | 7.25 |
March | 0.142831E+09 | 13955.87 | 20-MAR-04:25 | -1.1 |
April | 0.134399E+09 | 13825.76 | 03-APR-03:04 | 1.88 |
May | 0.315604E+09 | 16552.78 | 20-MAY-16:03 | 29.82 |
June | 0.280818E+09 | 15277.84 | 24-JUN-16:02 | 28.22 |
July | 0.440733E+09 | 21193.10 | 15-JUL-16:01 | 32.80 |
August | 0.433607E+09 | 24095.36 | 05-AUG-16:01 | 35.22 |
September | 0.491742E+09 | 21890.93 | 02-SEP-16:02 | 33.98 |
October | 0.403321E+09 | 13775.48 | 03-OCT-03:04 | 2.98 |
November | 0.283637E+09 | 14924.00 | 12-NOV-16:53 | -1.1 |
December | 0.130516E+09 | 13486.07 | 18-DEC-04:03 | -3.7 |
Annual Sum or Average | 0.343480E+10 | |||
Minimum of Months | 71849494.39 | 13486.07 | -3.7 | |
Maximum of Months | 0.491742E+09 | 24095.36 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403122E+09 | 53574.72 | 09-JAN-05:11 | -27.2 |
February | 0.117829E+09 | 52093.94 | 06-FEB-05:11 | -0.2 |
March | 29398266.56 | 50074.95 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 5371359.26 | 47194.87 | 27-NOV-06:01 | -14.5 |
December | 84472069.24 | 51078.30 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.640193E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.403122E+09 | 53574.72 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.830696E+10 | 79494.31 | 09-JAN-04:01 | -27.2 |
February | 0.279767E+10 | 78408.44 | 06-FEB-04:11 | -0.6 |
March | 0.158365E+10 | 78268.05 | 06-MAR-04:01 | -18.4 |
April | 33902239.42 | 63565.52 | 10-APR-05:01 | 3.90 |
May | 0.504102E+09 | 71073.94 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.258359E+09 | 70726.77 | 10-OCT-04:11 | -5.4 |
November | 0.191861E+10 | 78142.24 | 27-NOV-04:11 | -15.7 |
December | 0.405027E+10 | 78368.44 | 26-DEC-04:01 | -6.3 |
Annual Sum or Average | 0.194535E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.830696E+10 | 79494.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194098E+10 | 13695.23 | 09-JAN-04:01 | -27.2 |
February | 0.438110E+09 | 12138.78 | 04-FEB-05:01 | -20.4 |
March | 76086044.36 | 12344.80 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 27417684.13 | 11600.13 | 27-NOV-05:01 | -15.4 |
December | 0.273393E+09 | 12052.97 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.275599E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.194098E+10 | 13695.23 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129713E+10 | 15467.79 | 09-JAN-04:01 | -27.2 |
February | 0.352255E+09 | 13648.61 | 04-FEB-05:01 | -20.4 |
March | 69037298.52 | 13797.14 | 06-MAR-05:01 | -18.4 |
April | 1566324.96 | 7384.52 | 15-APR-05:01 | -0.6 |
May | 117333.28 | 1760.00 | 22-MAY-05:01 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 126275.02 | 829.97 | 04-OCT-05:03 | -0.5 |
November | 41414131.50 | 13358.90 | 27-NOV-05:01 | -15.4 |
December | 0.310715E+09 | 13743.85 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.207236E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.129713E+10 | 15467.79 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185490E+10 | 21685.77 | 09-JAN-04:01 | -27.2 |
February | 0.413699E+09 | 19488.03 | 04-FEB-05:01 | -20.4 |
March | 0.130721E+09 | 20104.95 | 06-MAR-04:01 | -18.4 |
April | 2736289.07 | 13655.70 | 29-APR-05:01 | -7.7 |
May | 13464824.52 | 16520.63 | 08-MAY-05:02 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 3465996.49 | 13217.99 | 10-OCT-05:02 | -6.1 |
November | 96175531.02 | 19192.76 | 27-NOV-05:01 | -15.4 |
December | 0.425454E+09 | 19324.18 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.294062E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.185490E+10 | 21685.77 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565758E+09 | 13726.31 | 09-JAN-04:01 | -27.2 |
February | 30471001.82 | 10751.27 | 04-FEB-06:01 | -19.5 |
March | 4483999.68 | 11427.66 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 1518963.64 | 10650.50 | 27-NOV-06:01 | -14.5 |
December | 3892496.65 | 10619.92 | 29-DEC-06:01 | -25.1 |
Annual Sum or Average | 0.606125E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.565758E+09 | 13726.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.735710E+10 | 13850.88 | 09-JAN-02:31 | -27.2 |
February | 0.326001E+10 | 13350.70 | 06-FEB-03:53 | -0.6 |
March | 0.143508E+10 | 13652.63 | 06-MAR-03:23 | -18.6 |
April | 0.126707E+09 | 11282.67 | 29-APR-04:01 | -7.8 |
May | 0.158171E+09 | 11904.51 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 14777635.14 | 10375.23 | 19-SEP-05:03 | 2.20 |
October | 0.120827E+09 | 11609.26 | 10-OCT-04:01 | -5.2 |
November | 0.137388E+10 | 13426.37 | 27-NOV-04:01 | -15.8 |
December | 0.422593E+10 | 13688.13 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.180725E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.735710E+10 | 13850.88 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.446882E+10 | 18884.58 | 09-JAN-02:31 | -27.2 |
February | 0.183078E+10 | 17659.54 | 04-FEB-04:01 | -21.9 |
March | 0.813014E+09 | 18460.07 | 06-MAR-04:01 | -18.4 |
April | 78946448.45 | 15358.91 | 29-APR-04:01 | -7.8 |
May | 0.103073E+09 | 16184.84 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 9666758.26 | 8099.36 | 19-SEP-05:03 | 2.20 |
October | 72534075.40 | 15664.50 | 10-OCT-04:01 | -5.2 |
November | 0.864649E+09 | 18341.41 | 27-NOV-04:01 | -15.8 |
December | 0.257024E+10 | 18646.02 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.108117E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.446882E+10 | 18884.58 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472006E+10 | 22841.26 | 09-JAN-02:31 | -27.2 |
February | 0.165778E+10 | 21404.97 | 04-FEB-04:01 | -21.9 |
March | 0.832138E+09 | 22346.13 | 06-MAR-04:01 | -18.4 |
April | 0.106889E+09 | 18560.23 | 29-APR-04:01 | -7.8 |
May | 0.158527E+09 | 19663.78 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 7581291.02 | 8641.63 | 19-SEP-05:03 | 2.20 |
October | 59558408.63 | 18851.75 | 10-OCT-04:01 | -5.2 |
November | 0.792812E+09 | 22089.27 | 27-NOV-04:01 | -15.8 |
December | 0.248191E+10 | 22641.24 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.108173E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.472006E+10 | 22841.26 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398708E+10 | 20062.39 | 09-JAN-02:31 | -27.2 |
February | 0.141908E+10 | 18761.75 | 04-FEB-04:01 | -21.9 |
March | 0.625607E+09 | 19547.29 | 06-MAR-04:01 | -18.4 |
April | 47370959.74 | 15253.22 | 29-APR-05:01 | -7.7 |
May | 76130471.94 | 17147.89 | 08-MAY-04:01 | -2.3 |
June | 45236.99 | 301.58 | 17-JUN-05:05 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 27762.44 | 231.35 | 18-AUG-05:04 | 7.30 |
September | 6182986.57 | 6824.24 | 19-SEP-05:03 | 2.20 |
October | 47440772.97 | 16383.79 | 10-OCT-04:01 | -5.2 |
November | 0.604897E+09 | 19420.94 | 27-NOV-04:01 | -15.8 |
December | 0.192338E+10 | 19757.50 | 31-DEC-07:31 | -28.0 |
Annual Sum or Average | 0.873724E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.398708E+10 | 20062.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147429E+11 | 18760.56 | 30-JAN-06:01 | -15.9 |
February | 0.749916E+10 | 18083.62 | 06-FEB-01:32 | -2.4 |
March | 0.455159E+10 | 18217.78 | 06-MAR-05:01 | -18.4 |
April | 0.115565E+10 | 15722.80 | 29-APR-03:02 | -6.9 |
May | 0.941454E+09 | 16477.90 | 01-MAY-03:11 | -0.7 |
June | 17529167.97 | 13969.83 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 13004597.51 | 13148.60 | 18-AUG-05:02 | 7.30 |
September | 0.282623E+09 | 14975.23 | 19-SEP-04:01 | 2.20 |
October | 0.112690E+10 | 16298.43 | 10-OCT-03:01 | -4.1 |
November | 0.485229E+10 | 18608.02 | 27-NOV-04:11 | -15.7 |
December | 0.106190E+11 | 18443.83 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.458021E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.9 | |
Maximum of Months | 0.147429E+11 | 18760.56 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.891097E+10 | 19657.30 | 09-JAN-04:01 | -27.2 |
February | 0.418426E+10 | 19421.94 | 05-FEB-06:52 | -20.0 |
March | 0.249350E+10 | 19375.58 | 06-MAR-05:01 | -18.4 |
April | 0.568793E+09 | 16860.50 | 29-APR-03:02 | -6.9 |
May | 0.534553E+09 | 17740.01 | 01-MAY-03:11 | -0.7 |
June | 9801958.74 | 14226.72 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 7717128.31 | 9744.48 | 18-AUG-05:02 | 7.30 |
September | 0.145503E+09 | 16078.33 | 19-SEP-04:01 | 2.20 |
October | 0.587105E+09 | 17529.99 | 10-OCT-03:01 | -4.1 |
November | 0.276284E+10 | 20127.63 | 27-NOV-04:11 | -15.7 |
December | 0.638165E+10 | 19934.19 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.265867E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.891097E+10 | 20127.63 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103515E+11 | 25542.86 | 09-JAN-02:41 | -27.2 |
February | 0.450007E+10 | 25338.31 | 05-FEB-06:52 | -20.0 |
March | 0.307876E+10 | 25216.50 | 06-MAR-05:01 | -18.4 |
April | 0.881616E+09 | 22010.18 | 29-APR-03:02 | -6.9 |
May | 0.898405E+09 | 23190.58 | 01-MAY-03:11 | -0.7 |
June | 31985694.73 | 19691.35 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 18005185.82 | 15111.36 | 18-AUG-05:02 | 7.30 |
September | 0.180523E+09 | 20850.55 | 19-SEP-04:01 | 2.20 |
October | 0.616033E+09 | 22991.13 | 10-OCT-03:01 | -4.1 |
November | 0.295375E+10 | 26130.50 | 27-NOV-04:11 | -15.7 |
December | 0.707907E+10 | 25861.24 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.305897E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.103515E+11 | 26130.50 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827503E+10 | 22122.77 | 09-JAN-04:01 | -27.2 |
February | 0.342408E+10 | 21526.47 | 05-FEB-08:12 | -20.2 |
March | 0.204511E+10 | 21592.71 | 06-MAR-05:01 | -18.4 |
April | 0.427709E+09 | 17977.69 | 15-APR-04:01 | -0.1 |
May | 0.412759E+09 | 19761.38 | 08-MAY-03:01 | -2.7 |
June | 13152488.90 | 9260.40 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 8271712.20 | 9552.54 | 18-AUG-05:02 | 7.30 |
September | 0.106796E+09 | 17876.04 | 19-SEP-04:01 | 2.20 |
October | 0.415066E+09 | 19728.30 | 10-OCT-03:01 | -4.1 |
November | 0.208603E+10 | 22395.44 | 27-NOV-04:11 | -15.7 |
December | 0.505661E+10 | 22065.95 | 31-DEC-03:41 | -24.9 |
Annual Sum or Average | 0.222706E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.827503E+10 | 22395.44 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214193E+10 | 12759.61 | 24-JAN-06:03 | 8.22 |
February | 0.871152E+09 | 13654.18 | 08-FEB-06:01 | -4.1 |
March | 0.354848E+09 | 13728.28 | 09-MAR-06:01 | 2.30 |
April | 0.131101E+09 | 12434.30 | 17-APR-03:02 | 9.40 |
May | 74191735.93 | 11253.84 | 01-MAY-04:01 | -0.6 |
June | 91527320.98 | 9808.80 | 19-JUN-03:02 | 13.53 |
July | 0.120110E+09 | 10657.19 | 05-JUL-03:02 | 9.90 |
August | 0.110171E+09 | 11580.81 | 06-AUG-16:01 | 35.50 |
September | 81098870.73 | 9854.27 | 20-SEP-04:01 | 3.30 |
October | 94976196.91 | 10969.52 | 10-OCT-03:01 | -4.1 |
November | 0.209502E+09 | 14172.67 | 30-NOV-06:01 | 1.10 |
December | 0.394928E+09 | 14917.18 | 19-DEC-05:01 | 3.40 |
Annual Sum or Average | 0.467554E+10 | |||
Minimum of Months | 74191735.93 | 9808.80 | -4.1 | |
Maximum of Months | 0.214193E+10 | 14917.18 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507036E+10 | 14660.86 | 09-JAN-06:12 | -27.2 |
February | 0.278954E+10 | 10134.13 | 06-FEB-06:03 | 0.60 |
March | 0.142554E+10 | 8225.48 | 06-MAR-13:30 | -0.3 |
April | 0.135267E+09 | 8039.02 | 16-APR-14:31 | 19.40 |
May | 0.376376E+09 | 8837.75 | 03-MAY-05:02 | 0.92 |
June | 61772269.46 | 6923.56 | 21-JUN-03:02 | 19.22 |
July | 70703491.05 | 7392.06 | 16-JUL-15:12 | 33.13 |
August | 58621078.81 | 10876.73 | 06-AUG-16:01 | 35.50 |
September | 75439704.84 | 7963.45 | 03-SEP-15:21 | 33.30 |
October | 0.243012E+09 | 8595.32 | 13-OCT-05:02 | 14.03 |
November | 0.125400E+10 | 7467.43 | 08-NOV-06:02 | 10.13 |
December | 0.289065E+10 | 8405.53 | 26-DEC-06:05 | -7.9 |
Annual Sum or Average | 0.144513E+11 | |||
Minimum of Months | 58621078.81 | 6923.56 | -27.2 | |
Maximum of Months | 0.507036E+10 | 14660.86 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200505E+11 | 35028.54 | 11-JAN-05:12 | -30.2 |
February | 0.106292E+11 | 29822.86 | 04-FEB-05:12 | -20.2 |
March | 0.733057E+10 | 32975.08 | 06-MAR-05:09 | -18.4 |
April | 0.267272E+10 | 14641.20 | 26-APR-05:03 | 5.37 |
May | 0.203570E+10 | 22259.69 | 08-MAY-04:12 | -2.4 |
June | 0.356893E+09 | 17827.86 | 14-JUN-05:02 | 7.30 |
July | 0.135862E+09 | 16841.84 | 12-JUL-05:03 | 6.85 |
August | 0.260309E+09 | 18668.78 | 17-AUG-05:02 | 7.38 |
September | 0.987324E+09 | 17514.96 | 28-SEP-05:03 | 8.90 |
October | 0.269981E+10 | 21545.24 | 10-OCT-04:23 | -5.5 |
November | 0.767012E+10 | 31237.34 | 27-NOV-05:11 | -15.3 |
December | 0.150048E+11 | 32197.38 | 29-DEC-05:22 | -25.0 |
Annual Sum or Average | 0.698339E+11 | |||
Minimum of Months | 0.135862E+09 | 14641.20 | -30.2 | |
Maximum of Months | 0.200505E+11 | 35028.54 | 8.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62287741.73 | 633.39 | 09-JAN-03:52 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 62287741.73 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 62287741.73 | 633.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556240E+09 | 663.47 | 29-JAN-17:50 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 2135343.30 | 139.42 | 08-MAY-04:12 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.558376E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.556240E+09 | 663.47 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887275E+09 | 692.73 | 29-JAN-17:50 | -21.9 |
February | 68950576.14 | 635.53 | 05-FEB-18:33 | -18.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2481248.24 | 760.90 | 30-APR-23:05 | -1.3 |
May | 0.123438E+09 | 659.32 | 01-MAY-00:20 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 26422515.57 | 499.09 | 17-SEP-07:25 | 3.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.110857E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.887275E+09 | 760.90 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196603E+11 | 20573.73 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.178333E+11 | 20573.73 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.211910E+11 | 20573.73 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.189279E+11 | 20573.73 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.204256E+11 | 20573.73 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.203269E+11 | 20573.73 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.190266E+11 | 20573.73 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.211910E+11 | 20573.73 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.189279E+11 | 20573.73 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.196603E+11 | 20573.73 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.194299E+11 | 20573.73 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.190266E+11 | 20573.73 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.235627E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.178333E+11 | 20573.73 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.211910E+11 | 20573.73 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554336E+10 | 5800.91 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.502824E+10 | 5800.91 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.597494E+10 | 5800.91 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.533685E+10 | 5800.91 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.575915E+10 | 5800.91 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.573131E+10 | 5800.91 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.536469E+10 | 5800.91 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.597494E+10 | 5800.91 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.533685E+10 | 5800.91 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.554336E+10 | 5800.91 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.547839E+10 | 5800.91 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.536469E+10 | 5800.91 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.664368E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.502824E+10 | 5800.91 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.597494E+10 | 5800.91 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.204256E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.203269E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.194299E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.235627E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154238E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123675E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112890E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819604E+09 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1854467.83 | 0.803399E+09 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9420242.08 | 0.396890E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32740590.35 | 0.259296E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27325766.70 | 0.285114E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18051397.25 | 0.529134E+09 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109081.56 | 0.798337E+09 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113097E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143569E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89501545.77 | 0.103665E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259296E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32740590.35 | 0.154238E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102533E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822439E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741321E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533368E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1394641.85 | 0.523945E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6684409.60 | 0.256805E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23221878.45 | 0.161825E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19066931.01 | 0.173486E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12553946.64 | 0.347676E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90902.65 | 0.524359E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734713E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936597E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63012710.21 | 0.678187E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161825E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23221878.45 | 0.102533E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155106E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126680E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113277E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814162E+09 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1885520.62 | 0.787879E+09 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9561963.11 | 0.388398E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32044062.68 | 0.251602E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26900298.78 | 0.279978E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15687212.83 | 0.535970E+09 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94381.94 | 0.815574E+09 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113246E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143600E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86173439.96 | 0.103926E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251602E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32044062.68 | 0.155106E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105579E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878442E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803203E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604220E+09 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1217288.13 | 0.565001E+09 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6056602.58 | 0.284555E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20216424.51 | 0.192765E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17353555.72 | 0.210780E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12097021.72 | 0.369451E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74265.41 | 0.570913E+09 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810242E+09 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103821E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57015158.07 | 0.738357E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192765E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20216424.51 | 0.105579E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328820E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253420E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235648E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169578E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4083229.93 | 0.171907E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22134128.29 | 0.885555E+09 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78383148.18 | 0.596361E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63791678.86 | 0.650928E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42684371.06 | 0.113722E+10 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825527.10 | 0.161856E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228964E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288324E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212902E+09 | 0.216552E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596361E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78383148.18 | 0.328820E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221340E+10 |
February | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172892E+10 |
March | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159892E+10 |
April | 0.688021E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116130E+10 |
May | 0.744847E+09 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2965910.29 | 0.114130E+10 |
June | 0.742030E+09 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15137121.12 | 0.593206E+09 |
July | 0.690839E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52001394.41 | 0.403860E+09 |
August | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42683122.04 | 0.432922E+09 |
September | 0.688021E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28230239.15 | 0.767451E+09 |
October | 0.715730E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 626170.24 | 0.110417E+10 |
November | 0.708685E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153617E+10 |
December | 0.690839E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193778E+10 |
Annual Sum or Average | 0.858171E+10 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141644E+09 | 0.146194E+11 |
Minimum of Months | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403860E+09 |
Maximum of Months | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52001394.41 | 0.221340E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345515E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279275E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251312E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180354E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4056715.99 | 0.174980E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21732648.94 | 0.883897E+09 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73356216.77 | 0.603702E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61595577.33 | 0.672099E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34813071.04 | 0.121080E+10 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119094.76 | 0.181125E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246809E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307349E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195673E+09 | 0.230377E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603702E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73356216.77 | 0.345515E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223587E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176218E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162392E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119770E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2777181.70 | 0.120040E+10 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14242672.67 | 0.613302E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50823086.64 | 0.429561E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41985402.21 | 0.451007E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29451857.66 | 0.779373E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 607724.24 | 0.112285E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157048E+10 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197250E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139888E+09 | 0.149591E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429561E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50823086.64 | 0.223587E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396250E+10 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293359E+10 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274372E+10 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191595E+10 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5050395.47 | 0.199318E+10 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26868750.87 | 0.105667E+10 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96989333.83 | 0.716388E+09 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78040325.16 | 0.774622E+09 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53634249.18 | 0.130562E+10 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6400007.47 | 0.176991E+10 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261788E+10 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344146E+10 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266983E+09 | 0.252315E+11 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716388E+09 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96989333.83 | 0.396250E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266114E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199760E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187197E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133879E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3458441.29 | 0.134647E+10 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17700151.90 | 0.724690E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60520391.40 | 0.499804E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50854148.82 | 0.532016E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32501767.24 | 0.908324E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1639019.00 | 0.123315E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176387E+10 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230536E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166674E+09 | 0.171832E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499804E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60520391.40 | 0.266114E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408325E+10 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320410E+10 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293316E+10 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207136E+10 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4826555.77 | 0.205284E+10 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25888367.46 | 0.106715E+10 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88414450.01 | 0.736272E+09 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74425278.40 | 0.816735E+09 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41603567.09 | 0.142604E+10 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206200.93 | 0.204171E+10 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280697E+10 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357788E+10 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235364E+09 | 0.268175E+11 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736272E+09 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88414450.01 | 0.408325E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267889E+10 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205138E+10 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191387E+10 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138900E+10 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3329438.84 | 0.141700E+10 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17139986.99 | 0.743411E+09 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62097252.59 | 0.525601E+09 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51264543.42 | 0.549080E+09 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35726599.10 | 0.920583E+09 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1524582.71 | 0.127402E+10 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181778E+10 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234212E+10 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171082E+09 | 0.176227E+11 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525601E+09 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62097252.59 | 0.267889E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.554336E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.502824E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.597494E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.533685E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.575915E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.573131E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.536469E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.597494E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.533685E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.554336E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.547839E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.536469E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.664368E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.502824E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.597494E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328645E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264459E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238712E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172711E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2893834.87 | 0.168010E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15241865.63 | 0.828158E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58675239.36 | 0.551565E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49733686.49 | 0.612285E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33302808.80 | 0.112566E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64615.68 | 0.169890E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241341E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307062E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159912E+09 | 0.220260E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551565E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58675239.36 | 0.328645E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552928E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440084E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404938E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293554E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5366670.93 | 0.290569E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27920476.65 | 0.145362E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109223E+09 | 0.976204E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90643953.52 | 0.108438E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61619363.60 | 0.196451E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161983.64 | 0.287429E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403188E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502938E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294936E+09 | 0.372350E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976204E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109223E+09 | 0.552928E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580060E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451159E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426672E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308392E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3352676.39 | 0.315981E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23046136.83 | 0.166100E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94520697.95 | 0.112681E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85434899.21 | 0.122566E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52758139.21 | 0.210896E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289250E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404803E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511607E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259113E+09 | 0.390017E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112681E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94520697.95 | 0.580060E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20573.73 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20573.73 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20573.73 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20573.73 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20573.73 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20573.73 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20573.73 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20573.73 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20573.73 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20573.73 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20573.73 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20573.73 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2513.75 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1593.39 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1934.99 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1389.75 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.29 | 20-MAY-17:02 | 2620.83 | 22-MAY-04:20 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1115.14 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.92 | 30-JUL-12:00 | 668.70 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.47 | 06-AUG-17:26 | 859.97 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.76 | 03-SEP-12:52 | 1483.19 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 18-OCT-14:00 | 1266.41 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1508.63 | 26-NOV-19:53 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2355.15 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.70 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 414.76 | 2620.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1675.25 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1041.94 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1262.10 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 907.56 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.55 | 20-MAY-17:02 | 1718.20 | 22-MAY-04:20 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.23 | 24-JUN-17:10 | 722.01 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.60 | 30-JUL-11:50 | 430.16 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.19 | 06-AUG-17:30 | 551.42 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.20 | 03-SEP-12:52 | 969.61 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 15-OCT-14:00 | 824.81 | 30-OCT-22:10 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1003.94 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1519.05 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.16 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 287.20 | 1718.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2512.63 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1568.44 | 17-FEB-04:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1961.72 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1372.55 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.92 | 20-MAY-17:02 | 2534.41 | 22-MAY-04:20 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1092.41 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.11 | 30-JUL-11:50 | 653.79 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.15 | 06-AUG-17:26 | 856.13 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 03-SEP-12:55 | 1439.99 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 | 18-OCT-14:50 | 1283.86 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.88 | 28-NOV-05:58 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2271.76 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.79 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 2534.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1677.40 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1130.57 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1374.00 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1013.78 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 20-MAY-17:02 | 1766.68 | 22-MAY-04:20 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 807.55 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.29 | 30-JUL-11:50 | 500.39 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.68 | 06-AUG-12:05 | 669.21 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.55 | 03-SEP-12:52 | 1019.23 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 898.71 | 30-OCT-22:50 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1068.09 | 26-NOV-19:53 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1713.34 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.39 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 307.55 | 1766.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5882.82 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3237.96 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4135.10 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2929.09 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.81 | 20-MAY-17:02 | 5691.68 | 22-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2351.22 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 674.43 | 30-JUL-12:00 | 1405.33 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 753.98 | 06-AUG-17:50 | 1747.21 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 941.27 | 03-SEP-13:00 | 3051.41 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.96 | 15-OCT-14:10 | 2601.28 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3529.09 | 28-NOV-05:49 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.15 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.33 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 941.27 | 5882.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3921.35 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2157.95 | 08-FEB-22:02 |
March | 1239.33 | 01-MAR-08:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2742.85 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1948.84 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.04 | 20-MAY-17:02 | 3794.45 | 22-MAY-04:53 |
June | 1239.33 | 01-JUN-07:10 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.84 | 24-JUN-17:10 | 1532.51 | 14-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.23 | 30-JUL-11:50 | 932.72 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 563.85 | 06-AUG-17:30 | 1159.27 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.26 | 03-SEP-12:52 | 1988.70 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 15-OCT-14:10 | 1729.26 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.68 | 28-NOV-05:41 |
December | 1239.33 | 01-DEC-08:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.16 | 01-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.72 | |||||
Maximum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 641.26 | 3921.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5884.69 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3391.38 | 19-FEB-13:00 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4306.44 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2958.47 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.53 | 20-MAY-17:02 | 5691.75 | 22-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2327.04 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.10 | 30-JUL-12:00 | 1416.97 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.42 | 06-AUG-17:26 | 1791.39 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 03-SEP-13:00 | 3028.29 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 18-OCT-15:10 | 2774.94 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3529.09 | 28-NOV-05:46 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.34 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.97 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 5884.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3922.08 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2163.22 | 17-FEB-05:45 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2833.13 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1976.49 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.67 | 20-MAY-17:02 | 3794.51 | 22-MAY-04:57 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1592.21 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.68 | 30-JUL-11:50 | 999.24 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.28 | 06-AUG-12:10 | 1205.86 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.56 | 03-SEP-12:55 | 1992.87 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.30 | 15-OCT-12:50 | 1770.75 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.74 | 28-NOV-05:41 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.90 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 999.24 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 705.56 | 3922.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7293.61 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4018.47 | 17-FEB-05:45 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4957.92 | 17-MAR-04:47 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3338.70 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.52 | 20-MAY-17:02 | 7101.79 | 22-MAY-04:50 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 | 29-JUN-15:00 | 2703.20 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 879.93 | 30-JUL-12:00 | 1616.64 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 948.44 | 06-AUG-17:40 | 2003.75 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.15 | 03-SEP-13:00 | 3332.71 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.05 | 15-OCT-14:00 | 3160.98 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4283.71 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6098.05 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.64 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.15 | 7293.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4861.63 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2679.19 | 17-FEB-05:47 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3305.41 | 17-MAR-04:50 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2245.55 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.00 | 20-MAY-17:02 | 4734.95 | 22-MAY-04:47 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1849.60 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.76 | 30-JUL-14:40 | 1081.60 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 700.58 | 06-AUG-17:40 | 1327.06 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.80 | 03-SEP-13:00 | 2195.73 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.22 | 15-OCT-13:50 | 2110.71 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.79 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.72 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.60 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 804.80 | 4861.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7296.80 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4030.20 | 08-FEB-22:02 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5099.11 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3397.16 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.41 | 20-MAY-17:02 | 7102.51 | 22-MAY-04:47 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 | 29-JUN-15:00 | 2677.58 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.84 | 30-JUL-12:00 | 1640.61 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 973.89 | 06-AUG-17:38 | 2063.31 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 991.80 | 03-SEP-12:55 | 3327.15 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 18-OCT-14:40 | 3215.57 | 30-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4423.08 | 28-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6297.80 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.61 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 991.80 | 7296.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4863.11 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2683.13 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3368.76 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2279.04 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.80 | 20-MAY-17:02 | 4735.04 | 22-MAY-04:47 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.29 | 29-JUN-15:00 | 1838.30 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 731.26 | 30-JUL-12:00 | 1171.32 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.16 | 06-AUG-11:52 | 1387.42 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 899.26 | 03-SEP-13:00 | 2215.49 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.72 | 15-OCT-12:31 | 2125.15 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.78 | 28-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.47 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.32 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 899.26 | 4863.11 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5800.91 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5800.91 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5800.91 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5800.91 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5800.91 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5800.91 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5800.91 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5800.91 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5800.91 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5800.91 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5800.91 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5800.91 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5188.83 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3467.82 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4108.49 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2933.59 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.48 | 20-MAY-17:02 | 5822.53 | 22-MAY-03:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.10 | 29-JUN-15:00 | 2330.29 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.24 | 30-JUL-12:00 | 1368.65 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.67 | 06-AUG-17:51 | 1786.53 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.26 | 03-SEP-13:00 | 3188.42 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 18-OCT-15:00 | 2697.00 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3282.41 | 26-NOV-19:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5141.14 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1368.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.26 | 5822.53 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9180.22 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5870.37 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7163.07 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5106.59 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.60 | 20-MAY-17:02 | 10067.11 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.01 | 29-JUN-15:00 | 4056.10 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.94 | 30-JUL-12:00 | 2374.68 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.51 | 06-AUG-17:51 | 3075.49 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.34 | 03-SEP-13:00 | 5541.81 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 18-OCT-14:00 | 4605.03 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5445.33 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8325.36 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.34 | 10067.11 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10273.79 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5792.53 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7777.72 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5341.41 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.68 | 20-MAY-17:02 | 10116.73 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.92 | 29-JUN-15:00 | 4197.33 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.02 | 30-JUL-11:55 | 2529.61 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.56 | 06-AUG-18:00 | 3182.35 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1310.21 | 03-SEP-13:00 | 5453.88 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4870.46 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5747.60 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8276.38 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2529.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1310.21 | 10273.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 111728.48 | 02-JAN-04:11 | 0.00 | 9144.45 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111032.38 | 21-FEB-04:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 108843.47 | 20-MAR-03:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110281.74 | 24-APR-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112411.30 | 30-MAY-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 112888.39 | 05-JUN-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111648.41 | 05-JUL-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112338.43 | 14-AUG-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 112864.53 | 11-SEP-03:02 | 0.00 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112117.63 | 30-OCT-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112007.94 | 20-NOV-04:01 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 111379.76 | 26-DEC-04:01 | 0.00 | 11430.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 108843.47 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 112888.39 | 0.00 | 11430.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85689.76 | 02-JAN-06:02 | 8061.19 | 10264.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86823.56 | 28-FEB-05:01 | 0.00 | 16422.89 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88639.44 | 20-MAR-04:02 | 0.00 | 20528.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90943.46 | 10-APR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93872.97 | 30-MAY-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91751.84 | 05-JUN-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 94681.66 | 05-JUL-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90441.61 | 23-AUG-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94871.92 | 11-SEP-03:02 | 0.00 | 6159.27 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90205.02 | 02-OCT-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90980.79 | 06-NOV-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87296.87 | 07-DEC-05:01 | 0.00 | 16422.89 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 85689.76 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94871.92 | 8061.19 | 20528.61 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22299.46 | 05-JAN-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60797.01 | 28-FEB-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72700.29 | 30-MAR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78454.85 | 08-APR-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81791.04 | 30-MAY-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82437.06 | 23-JUN-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83308.83 | 19-JUL-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85315.68 | 14-AUG-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84391.47 | 11-SEP-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78644.19 | 18-OCT-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73361.53 | 08-NOV-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29153.64 | 07-DEC-16:30 | 30632.53 | 36953.32 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22299.46 | 0.00 | 5132.72 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85315.68 | 30632.53 | 36953.32 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16185.38 | 13-JAN-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26421.68 | 28-FEB-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29807.03 | 23-MAR-15:30 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43890.06 | 26-APR-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76928.28 | 20-MAY-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82481.49 | 21-JUN-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81572.57 | 19-JUL-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80738.99 | 07-AUG-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82193.83 | 05-SEP-03:02 | 0.00 | 6159.27 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51582.25 | 19-OCT-05:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28208.22 | 03-NOV-16:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20190.61 | 06-DEC-17:00 | 15316.26 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16185.38 | 0.00 | 6159.27 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82481.49 | 15316.26 | 18476.66 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3154.18 | 02-JAN-06:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.36 |
February | 4506.20 | 27-FEB-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
March | 4953.60 | 27-MAR-14:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.41 |
April | 7392.64 | 07-APR-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 |
May | 12755.73 | 30-MAY-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
June | 12610.63 | 26-JUN-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 |
July | 12918.87 | 03-JUL-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.20 |
August | 16290.43 | 06-AUG-16:01 | 1012.16 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 257.92 | 0.00 |
September | 15637.02 | 04-SEP-16:51 | 910.95 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 95.42 | 0.00 |
October | 6267.99 | 19-OCT-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 4507.07 | 24-NOV-14:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 |
December | 3194.97 | 06-DEC-05:01 | 0.00 | 2062.06 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3154.18 | 0.00 | 1031.03 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16290.43 | 2010.79 | 2319.93 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 257.92 | 833.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3756.16 | 02-JAN-06:02 | 652.28 | 830.54 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 |
February | 6709.06 | 27-FEB-10:00 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
March | 9365.63 | 28-MAR-09:20 | 2591.66 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 11614.20 | 24-APR-08:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
May | 11810.37 | 19-MAY-08:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
June | 21305.67 | 25-JUN-07:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.72 |
July | 22480.31 | 02-JUL-07:51 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.67 |
August | 23097.67 | 06-AUG-08:41 | 587.05 | 747.57 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.84 |
September | 21429.73 | 04-SEP-08:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 |
October | 8933.72 | 18-OCT-09:20 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
November | 6190.08 | 06-NOV-09:35 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
December | 3583.64 | 06-DEC-05:01 | 0.00 | 1328.87 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3583.64 | 0.00 | 498.38 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | |
Maximum of Months | 23097.67 | 2591.66 | 2990.10 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12048.22 | 19-JAN-13:30 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.04 |
February | 25691.50 | 26-FEB-13:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.69 |
March | 19413.40 | 01-MAR-13:40 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.43 |
April | 19309.22 | 16-APR-12:02 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.64 |
May | 15395.07 | 19-MAY-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
June | 16211.72 | 25-JUN-15:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.27 |
July | 25863.69 | 02-JUL-14:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.46 |
August | 27271.99 | 06-AUG-16:01 | 1012.19 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 228.39 | 0.00 |
September | 27749.97 | 03-SEP-13:11 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 245.79 | 0.00 |
October | 28482.31 | 15-OCT-12:31 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.40 |
November | 19300.92 | 03-NOV-13:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.02 |
December | 13777.73 | 12-DEC-12:30 | 1058.33 | 2319.98 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12048.22 | 506.09 | 644.48 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28482.31 | 2010.83 | 2319.98 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 245.79 | 473.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4895.51 | 02-JAN-05:01 | 0.00 | 1328.87 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 |
February | 10319.47 | 28-FEB-16:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 |
March | 12863.35 | 28-MAR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 |
April | 25904.11 | 16-APR-17:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.28 |
May | 25756.48 | 13-MAY-18:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.09 |
June | 25696.33 | 18-JUN-17:02 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 |
July | 30353.99 | 02-JUL-17:51 | 0.00 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.97 |
August | 30550.80 | 06-AUG-16:41 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 105.75 | 0.00 |
September | 28533.36 | 04-SEP-16:51 | 587.05 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 0.00 |
October | 20065.31 | 15-OCT-14:31 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.11 |
November | 9648.80 | 03-NOV-15:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
December | 8907.63 | 06-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4895.51 | 0.00 | 498.38 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30550.80 | 1239.33 | 1495.05 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 105.75 | 214.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1832.99 | 13-JAN-15:10 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.78 |
February | 3059.51 | 27-FEB-13:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.05 |
March | 3031.87 | 23-MAR-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.75 |
April | 5631.47 | 07-APR-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
May | 7688.92 | 19-MAY-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 11644.03 | 23-JUN-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.10 |
July | 10308.00 | 20-JUL-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.47 |
August | 14878.26 | 06-AUG-16:01 | 1012.16 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 621.72 | 0.00 |
September | 10142.98 | 03-SEP-16:01 | 708.51 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 684.18 | 0.00 |
October | 4846.05 | 19-OCT-14:40 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 |
November | 3011.12 | 03-NOV-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.56 |
December | 2076.38 | 06-DEC-15:50 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1832.99 | 708.51 | 902.25 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14878.26 | 2010.79 | 2319.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 684.18 | 617.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2519.26 | 20-JAN-10:00 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.42 |
February | 4566.58 | 26-FEB-11:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 723.76 |
March | 7339.60 | 28-MAR-10:05 | 2478.65 | 2990.10 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.50 |
April | 10811.08 | 24-APR-09:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.31 |
May | 12271.44 | 19-MAY-08:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 |
June | 21090.55 | 04-JUN-07:42 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.14 |
July | 23370.12 | 02-JUL-07:41 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.35 |
August | 25062.17 | 06-AUG-09:21 | 587.05 | 747.57 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 |
September | 21403.15 | 03-SEP-11:21 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 121.25 | 0.00 |
October | 7535.97 | 18-OCT-10:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 |
November | 4076.77 | 03-NOV-13:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.64 |
December | 2740.63 | 07-DEC-11:20 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2519.26 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25062.17 | 2478.65 | 2990.10 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 121.25 | 723.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11615.32 | 19-JAN-14:00 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.93 |
February | 28028.78 | 26-FEB-13:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.60 |
March | 20448.61 | 01-MAR-14:00 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.44 |
April | 24811.53 | 16-APR-13:12 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.58 |
May | 15805.83 | 19-MAY-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 76.25 | 0.00 |
June | 15549.42 | 30-JUN-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 0.00 |
July | 25485.55 | 16-JUL-15:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 301.36 | 0.00 |
August | 27588.52 | 06-AUG-16:01 | 1012.19 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 515.14 | 0.00 |
September | 30660.34 | 03-SEP-12:41 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 378.34 | 0.00 |
October | 27245.48 | 15-OCT-13:22 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 731.66 |
November | 19832.34 | 03-NOV-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.78 |
December | 11909.96 | 12-DEC-14:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11615.32 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30660.34 | 2010.83 | 2319.98 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 515.14 | 1244.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3477.56 | 13-JAN-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.76 |
February | 7175.20 | 28-FEB-16:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.78 |
March | 8764.54 | 28-MAR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.85 |
April | 22853.94 | 16-APR-17:11 | 0.00 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.41 |
May | 25407.65 | 28-MAY-18:01 | 0.00 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.16 |
June | 23178.33 | 18-JUN-17:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 |
July | 25059.52 | 16-JUL-17:11 | 0.00 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 110.45 | 0.00 |
August | 26356.80 | 06-AUG-16:41 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 281.57 | 0.00 |
September | 24039.07 | 03-SEP-16:01 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 368.06 | 0.00 |
October | 10200.01 | 16-OCT-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.46 |
November | 5566.46 | 03-NOV-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 |
December | 3792.19 | 06-DEC-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3477.56 | 0.00 | 498.38 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26356.80 | 1239.33 | 1495.05 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 368.06 | 775.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2085.86 | 14-JAN-17:03 | 404.87 | 515.57 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.14 |
February | 2761.66 | 27-FEB-13:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.68 |
March | 3009.94 | 23-MAR-13:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.79 |
April | 5180.85 | 07-APR-14:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
May | 8364.42 | 19-MAY-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 215.49 | 0.00 |
June | 11997.29 | 23-JUN-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.25 |
July | 16288.60 | 16-JUL-18:31 | 0.00 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 268.20 | 0.00 |
August | 13844.14 | 06-AUG-16:11 | 708.51 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 796.53 | 0.00 |
September | 8680.26 | 05-SEP-14:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
October | 4328.94 | 18-OCT-14:20 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 0.00 |
November | 2775.67 | 08-NOV-15:30 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.17 |
December | 2293.02 | 06-DEC-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2085.86 | 0.00 | 515.57 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16288.60 | 2010.79 | 2319.93 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 796.53 | 702.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2457.96 | 13-JAN-06:04 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.56 |
February | 3372.48 | 28-FEB-10:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.35 |
March | 5686.81 | 23-MAR-10:30 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.22 |
April | 9798.22 | 25-APR-09:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
May | 11836.27 | 19-MAY-09:20 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 |
June | 22635.34 | 25-JUN-09:02 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.15 |
July | 22318.50 | 16-JUL-09:12 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.35 |
August | 22553.57 | 06-AUG-09:32 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 58.25 | 0.00 |
September | 16548.09 | 04-SEP-09:02 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
October | 6411.26 | 18-OCT-10:00 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.46 |
November | 3307.93 | 03-NOV-10:00 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.94 |
December | 2481.82 | 09-DEC-06:04 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2457.96 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22635.34 | 1295.83 | 1495.05 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 58.25 | 675.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9656.95 | 31-JAN-13:40 | 1923.15 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.90 |
February | 27512.63 | 26-FEB-14:21 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.31 |
March | 18718.32 | 01-MAR-14:10 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.88 |
April | 17679.10 | 25-APR-13:40 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.43 |
May | 16380.47 | 19-MAY-13:50 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
June | 19277.38 | 25-JUN-15:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.02 |
July | 27848.79 | 16-JUL-13:52 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 210.48 | 0.00 |
August | 28943.26 | 06-AUG-13:32 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 585.99 | 0.00 |
September | 30587.20 | 03-SEP-13:31 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 573.05 | 0.00 |
October | 29486.48 | 15-OCT-15:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.13 |
November | 18101.60 | 03-NOV-13:30 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.01 |
December | 9396.43 | 06-DEC-14:40 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9396.43 | 506.09 | 644.48 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30587.20 | 2010.83 | 2319.98 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 585.99 | 1178.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3477.46 | 13-JAN-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.97 |
February | 6563.70 | 28-FEB-16:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.20 |
March | 8310.56 | 28-MAR-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.83 |
April | 18279.34 | 16-APR-17:11 | 0.00 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.22 |
May | 26835.91 | 28-MAY-18:01 | 0.00 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959.48 |
June | 24627.15 | 18-JUN-17:22 | 0.00 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.25 |
July | 27584.86 | 09-JUL-16:41 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.39 |
August | 25648.46 | 06-AUG-16:11 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 448.94 | 0.00 |
September | 25575.92 | 04-SEP-17:01 | 0.00 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 135.43 | 0.00 |
October | 9988.47 | 18-OCT-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
November | 4821.57 | 03-NOV-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.85 |
December | 3781.48 | 06-DEC-15:50 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3477.46 | 0.00 | 498.38 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27584.86 | 1239.33 | 1495.05 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 448.94 | 959.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7725.21 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.25 |
February | 5665.94 | 28-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.95 |
March | 5312.50 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.08 |
April | 6048.70 | 25-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.95 |
May | 9818.21 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.13 |
June | 8937.68 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.52 |
July | 10514.54 | 31-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.61 |
August | 11554.42 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.76 |
September | 14003.90 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.27 |
October | 5711.03 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.96 |
November | 6122.83 | 06-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.56 |
December | 4409.69 | 09-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4409.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14003.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10393.84 | 06-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5994.79 |
February | 9283.22 | 04-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2938.96 |
March | 11251.97 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3166.96 |
April | 6537.90 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3276.42 |
May | 6861.90 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.81 |
June | 6922.24 | 22-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.32 |
July | 8085.29 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.98 | 0.00 |
August | 8196.27 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.96 | 0.00 |
September | 7925.50 | 05-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
October | 6097.50 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2712.17 |
November | 8875.89 | 27-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5033.58 |
December | 8195.77 | 29-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6097.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11251.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.98 | 5994.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 106.65 | 14-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.89 |
February | 2356.28 | 26-FEB-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.23 |
March | 4722.57 | 23-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.54 |
April | 11197.31 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.41 |
May | 16794.04 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.10 | 0.00 |
June | 19593.51 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.11 | 0.00 |
July | 23043.35 | 17-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.58 | 0.00 |
August | 20548.87 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.78 | 0.00 |
September | 15101.18 | 05-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 |
October | 8736.54 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 |
November | 2174.14 | 03-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.98 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5166.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23043.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.10 | 5166.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1980.93 | 19-JAN-16:50 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4315.35 | 28-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6834.60 | 31-MAR-24:00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8241.22 | 22-APR-18:10 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3506.71 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5359.07 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7239.20 | 31-JUL-23:35 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8218.20 | 29-AUG-17:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3316.17 | 30-SEP-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4965.71 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6077.34 | 13-NOV-16:20 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7853.15 | 06-DEC-16:10 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1980.93 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8241.22 | 222.14 | 381.58 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1617.99 | 19-JAN-16:50 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3943.24 | 28-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5924.91 | 31-MAR-23:30 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7806.77 | 25-APR-18:10 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3309.65 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5241.94 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7067.02 | 31-JUL-23:55 | 0.00 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7836.85 | 03-AUG-18:50 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2886.21 | 30-SEP-23:40 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4161.96 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5550.58 | 03-NOV-16:00 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7146.80 | 06-DEC-16:20 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1617.99 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7836.85 | 222.14 | 381.58 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1412.43 | 13-JAN-16:30 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3888.33 | 28-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5844.66 | 28-MAR-17:50 | 23.38 | 127.19 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7859.35 | 25-APR-18:10 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3227.06 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5241.29 | 30-JUN-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7015.60 | 31-JUL-23:55 | 0.00 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7952.55 | 03-AUG-18:40 | 23.38 | 127.19 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2786.97 | 04-SEP-17:32 | 0.00 | 190.79 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4034.26 | 18-OCT-17:00 | 70.15 | 211.99 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5476.74 | 03-NOV-16:00 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7048.30 | 06-DEC-16:20 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1412.43 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7952.55 | 222.14 | 381.58 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91682.57 | 02-JAN-17:00 | 4808.68 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183625.07 | 28-FEB-17:00 | 4808.68 | 5800.91 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357618.64 | 31-MAR-24:00 | 0.00 | 322.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367084.58 | 26-APR-16:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176046.09 | 31-MAY-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267987.34 | 30-JUN-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359225.79 | 31-JUL-23:12 | 0.00 | 1611.46 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369521.79 | 22-AUG-07:20 | 9617.36 | 11601.83 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175720.50 | 30-SEP-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267723.28 | 31-OCT-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276676.74 | 06-NOV-16:55 | 9617.36 | 11601.83 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367838.30 | 06-DEC-17:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91682.57 | 0.00 | 322.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369521.79 | 9617.36 | 11601.83 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.176838E+13 | 1113276.43 | 02-JAN-08:09 | 0.173971E+13 | 3042043.47 | 09-JAN-07:10 |
February | 0.198947E+13 | 1363330.19 | 27-FEB-16:10 | 0.103887E+13 | 2340260.84 | 01-FEB-07:10 |
March | 0.266949E+13 | 1447490.94 | 28-MAR-15:50 | 0.754080E+12 | 2302913.94 | 06-MAR-07:10 |
April | 0.300198E+13 | 1782389.44 | 06-APR-15:00 | 0.315255E+12 | 1143646.88 | 29-APR-06:10 |
May | 0.188895E+13 | 1529519.66 | 19-MAY-15:30 | 0.235302E+12 | 1064991.78 | 08-MAY-06:10 |
June | 0.245720E+13 | 1752179.15 | 29-JUN-15:09 | 0.824924E+11 | 511973.26 | 16-JUN-06:10 |
July | 0.305227E+13 | 2006149.26 | 17-JUL-15:20 | 0.656361E+11 | 105938.40 | 08-JUL-06:19 |
August | 0.350995E+13 | 2144185.78 | 07-AUG-15:30 | 0.724799E+11 | 279234.32 | 18-AUG-06:10 |
September | 0.191734E+13 | 1609669.35 | 07-SEP-15:09 | 0.121451E+12 | 665811.43 | 19-SEP-06:10 |
October | 0.228516E+13 | 1567254.23 | 18-OCT-15:00 | 0.256086E+12 | 1202289.70 | 10-OCT-06:10 |
November | 0.258640E+13 | 1542905.79 | 17-NOV-16:00 | 0.599248E+12 | 1913728.51 | 27-NOV-07:10 |
December | 0.303049E+13 | 1595432.88 | 19-DEC-08:09 | 0.123939E+13 | 2413501.45 | 29-DEC-07:10 |
Annual Sum or Average | 0.301571E+14 | 0.652000E+13 | ||||
Minimum of Months | 0.176838E+13 | 1113276.43 | 0.656361E+11 | 105938.40 | ||
Maximum of Months | 0.350995E+13 | 2144185.78 | 0.173971E+13 | 3042043.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328950E+12 | 0.979791E+11 | 0.811612E+12 | 0.169596E+12 | 0.198797E+12 | 0.163744E+11 | 0.00 | 0.955004E+11 | 0.852750E+10 | 0.410448E+11 | 0.00 | 0.00 | 0.00 |
February | 0.298382E+12 | 0.809468E+11 | 0.102011E+13 | 0.153195E+12 | 0.180072E+12 | 0.147538E+11 | 0.00 | 0.159078E+12 | 0.215281E+11 | 0.614094E+11 | 0.00 | 0.00 | 0.00 |
March | 0.354561E+12 | 0.790466E+11 | 0.146267E+13 | 0.169879E+12 | 0.209835E+12 | 0.141554E+11 | 0.00 | 0.247903E+12 | 0.388872E+11 | 0.925541E+11 | 0.00 | 0.00 | 0.00 |
April | 0.316695E+12 | 0.658146E+11 | 0.170311E+13 | 0.164100E+12 | 0.210527E+12 | 0.218776E+11 | 0.00 | 0.325372E+12 | 0.831352E+11 | 0.111350E+12 | 0.00 | 0.00 | 0.00 |
May | 0.341755E+12 | 0.585249E+11 | 0.820521E+12 | 0.169738E+12 | 0.227583E+12 | 0.338039E+11 | 0.00 | 0.145991E+12 | 0.540175E+11 | 0.370179E+11 | 0.00 | 0.00 | 0.00 |
June | 0.340103E+12 | 0.516843E+11 | 0.110677E+13 | 0.164363E+12 | 0.269904E+12 | 0.619713E+11 | 0.00 | 0.302288E+12 | 0.110746E+12 | 0.493680E+11 | 0.00 | 0.00 | 0.00 |
July | 0.318348E+12 | 0.556920E+11 | 0.143888E+13 | 0.169473E+12 | 0.296912E+12 | 0.858682E+11 | 0.00 | 0.488812E+12 | 0.143431E+12 | 0.548624E+11 | 0.00 | 0.00 | 0.00 |
August | 0.354561E+12 | 0.637417E+11 | 0.177780E+13 | 0.169879E+12 | 0.295907E+12 | 0.813128E+11 | 0.00 | 0.540240E+12 | 0.140168E+12 | 0.863396E+11 | 0.00 | 0.00 | 0.00 |
September | 0.316695E+12 | 0.718260E+11 | 0.784732E+12 | 0.164097E+12 | 0.235020E+12 | 0.482637E+11 | 0.00 | 0.184526E+12 | 0.806450E+11 | 0.315373E+11 | 0.00 | 0.00 | 0.00 |
October | 0.328950E+12 | 0.851963E+11 | 0.112899E+13 | 0.169597E+12 | 0.216495E+12 | 0.262262E+11 | 0.00 | 0.203806E+12 | 0.615301E+11 | 0.643691E+11 | 0.00 | 0.00 | 0.00 |
November | 0.325095E+12 | 0.921059E+11 | 0.140306E+13 | 0.164207E+12 | 0.198153E+12 | 0.158074E+11 | 0.00 | 0.243455E+12 | 0.527406E+11 | 0.917708E+11 | 0.00 | 0.00 | 0.00 |
December | 0.318348E+12 | 0.100708E+12 | 0.175516E+13 | 0.169471E+12 | 0.199460E+12 | 0.145751E+11 | 0.00 | 0.310508E+12 | 0.425046E+11 | 0.119755E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394244E+13 | 0.903267E+12 | 0.152134E+14 | 0.199759E+13 | 0.273866E+13 | 0.434990E+12 | 0.00 | 0.324748E+13 | 0.837861E+12 | 0.841378E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298382E+12 | 0.516843E+11 | 0.784732E+12 | 0.153195E+12 | 0.180072E+12 | 0.141554E+11 | 0.00 | 0.955004E+11 | 0.852750E+10 | 0.315373E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354561E+12 | 0.100708E+12 | 0.177780E+13 | 0.169879E+12 | 0.296912E+12 | 0.858682E+11 | 0.00 | 0.540240E+12 | 0.143431E+12 | 0.119755E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.166355E+13 | 0.00 | 0.761577E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.968957E+12 | 0.00 | 0.699122E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.673885E+12 | 0.00 | 0.801945E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243036E+12 | 0.00 | 0.722192E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.161868E+12 | 0.00 | 0.734345E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133383E+11 | 0.00 | 0.691541E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.308018E+09 | 0.00 | 0.653281E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.417565E+10 | 0.00 | 0.683043E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.575377E+11 | 0.00 | 0.639129E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.188108E+12 | 0.00 | 0.679785E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.530051E+12 | 0.00 | 0.691965E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.116679E+13 | 0.00 | 0.725989E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.567161E+13 | 0.00 | 0.848392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.308018E+09 | 0.00 | 0.639129E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.166355E+13 | 0.00 | 0.801945E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 344233.60 | 02-JAN-08:09 | 57580.60 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 120520.01 | 02-JAN-08:20 | 114844.93 | 09-JAN-06:10 | 36632.14 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 344233.60 | 01-FEB-08:09 | 57580.60 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 120520.01 | 01-FEB-08:20 | 158353.69 | 28-FEB-16:10 | 39773.61 | 27-FEB-13:39 | 0.00 | 01-FEB-00:10 |
March | 344233.60 | 01-MAR-08:09 | 57580.60 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 120520.01 | 01-MAR-08:20 | 168692.31 | 28-MAR-15:50 | 36560.51 | 07-MAR-19:49 | 0.00 | 01-MAR-00:10 |
April | 344233.60 | 03-APR-07:10 | 57580.60 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 120520.01 | 03-APR-07:19 | 226197.61 | 25-APR-15:30 | 57939.15 | 06-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 344233.60 | 01-MAY-07:10 | 57580.60 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 120520.01 | 01-MAY-07:19 | 263225.71 | 19-MAY-15:30 | 64654.33 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 344233.60 | 01-JUN-07:10 | 57580.60 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 120520.01 | 01-JUN-07:19 | 292601.52 | 29-JUN-14:30 | 65283.71 | 23-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 344233.60 | 03-JUL-07:10 | 57580.60 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 120520.01 | 03-JUL-07:19 | 316712.83 | 14-JUL-15:20 | 66157.66 | 17-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 344233.60 | 01-AUG-07:10 | 57580.60 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 120520.01 | 01-AUG-07:19 | 325068.55 | 11-AUG-15:39 | 65997.58 | 07-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 344233.60 | 01-SEP-07:10 | 57580.60 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 120520.01 | 01-SEP-07:19 | 269252.46 | 05-SEP-14:50 | 65479.00 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 344233.60 | 02-OCT-07:10 | 57580.60 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 120520.01 | 02-OCT-07:19 | 190222.43 | 18-OCT-15:00 | 60797.47 | 18-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 344233.60 | 01-NOV-07:10 | 57580.60 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 120520.01 | 01-NOV-07:19 | 163286.20 | 03-NOV-15:20 | 37077.93 | 03-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 344233.60 | 01-DEC-08:09 | 57580.60 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 120520.01 | 01-DEC-08:20 | 124328.37 | 07-DEC-14:09 | 36056.75 | 11-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 344233.60 | 57580.60 | 439129.89 | 120520.01 | 114844.93 | 36056.75 | 0.00 | |||||||
Maximum of Months | 344233.60 | 57580.60 | 794004.08 | 120520.01 | 325068.55 | 66157.66 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 40656.26 | 03-JAN-06:00 | 7432.49 | 14-JAN-14:00 | 20104.05 | 26-JAN-18:00 | 0.00 | 0.00 | 0.00 |
February | 144822.67 | 27-FEB-15:30 | 49363.90 | 27-FEB-15:30 | 31485.33 | 04-FEB-07:40 | 0.00 | 0.00 | 0.00 |
March | 118479.15 | 14-MAR-13:30 | 49248.27 | 14-MAR-11:20 | 43078.61 | 31-MAR-23:00 | 0.00 | 0.00 | 0.00 |
April | 243187.99 | 07-APR-12:39 | 53564.90 | 06-APR-15:00 | 50215.57 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 263820.25 | 19-MAY-15:20 | 83442.05 | 19-MAY-13:00 | 21892.17 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 345069.31 | 29-JUN-14:00 | 83442.05 | 06-JUN-14:30 | 27062.01 | 08-JUN-20:00 | 0.00 | 0.00 | 0.00 |
July | 457262.74 | 17-JUL-15:00 | 83442.05 | 10-JUL-14:00 | 36642.14 | 12-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 476400.57 | 07-AUG-15:30 | 83442.05 | 05-AUG-12:20 | 49347.31 | 01-AUG-20:00 | 0.00 | 0.00 | 0.00 |
September | 383539.31 | 07-SEP-14:50 | 83442.05 | 02-SEP-10:20 | 22843.54 | 30-SEP-23:00 | 0.00 | 0.00 | 0.00 |
October | 270939.81 | 18-OCT-13:00 | 59418.29 | 18-OCT-14:00 | 33045.11 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 152402.88 | 17-NOV-16:00 | 49286.39 | 17-NOV-16:00 | 41306.56 | 20-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 125009.60 | 10-DEC-01:00 | 49248.27 | 05-DEC-11:00 | 52018.99 | 28-DEC-18:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 40656.26 | 7432.49 | 20104.05 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 476400.57 | 83442.05 | 52018.99 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1113276.43 | 02-JAN-08:09 | 344233.60 | 439129.89 | 57580.60 | 120330.96 | 91529.92 | 6534.79 | 0.00 | 34456.59 | 3330.50 |
February | 1363330.19 | 27-FEB-16:10 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 133921.60 | 37568.27 | 0.00 | 132931.01 | 49301.74 |
March | 1447490.94 | 28-MAR-15:50 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 168692.31 | 3712.89 | 0.00 | 95364.05 | 37269.07 |
April | 1782389.44 | 06-APR-15:00 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 202814.66 | 42292.05 | 0.00 | 233752.03 | 53564.90 |
May | 1529519.66 | 19-MAY-15:30 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 263225.71 | 64624.56 | 0.00 | 263808.45 | 64107.65 |
June | 1752179.15 | 29-JUN-15:09 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 285977.70 | 61590.70 | 0.00 | 343755.77 | 71842.86 |
July | 2006149.26 | 17-JUL-15:20 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 297573.57 | 66032.81 | 0.00 | 452565.12 | 83442.05 |
August | 2144185.78 | 07-AUG-15:30 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 277580.83 | 65860.87 | 0.00 | 476400.57 | 83442.05 |
September | 1609669.35 | 07-SEP-15:09 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 246497.20 | 64091.56 | 0.00 | 345685.64 | 83442.05 |
October | 1567254.23 | 18-OCT-15:00 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 190222.43 | 59573.21 | 0.00 | 258837.82 | 58317.76 |
November | 1542905.79 | 17-NOV-16:00 | 344233.60 | 675712.68 | 57580.60 | 86589.42 | 114876.15 | 36324.20 | 0.00 | 152402.88 | 49286.39 |
December | 1595432.88 | 19-DEC-08:09 | 344233.60 | 794004.08 | 57580.60 | 120330.96 | 90383.40 | 5496.63 | 0.00 | 115067.50 | 25150.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1113276.43 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 90383.40 | 3712.89 | 0.00 | 34456.59 | 3330.50 | |
Maximum of Months | 2144185.78 | 344233.60 | 794004.08 | 57580.60 | 120330.96 | 297573.57 | 66032.81 | 0.00 | 476400.57 | 83442.05 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 3008975.83 | 09-JAN-07:10 | 0.00 | 87803.99 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 2307440.93 | 01-FEB-07:10 | 0.00 | 87977.56 | 17-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 2271005.31 | 06-MAR-07:10 | 0.00 | 87910.57 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 1113284.11 | 29-APR-06:10 | 0.00 | 87069.87 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 1032860.92 | 08-MAY-06:10 | 0.00 | 85654.55 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 480305.56 | 16-JUN-06:10 | 0.00 | 83551.72 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 93241.69 | 08-JUL-06:10 | 0.00 | 81328.04 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 248034.01 | 18-AUG-06:10 | 0.00 | 79976.81 | 02-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 634405.80 | 19-SEP-06:10 | 0.00 | 80897.35 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 1170744.05 | 10-OCT-06:10 | 0.00 | 83000.44 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 1881756.18 | 27-NOV-07:10 | 0.00 | 85100.04 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 2392165.38 | 29-DEC-07:10 | 0.00 | 86719.36 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 93241.69 | 0.00 | 79976.81 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3008975.83 | 0.00 | 87977.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.12 | 1.00 | 27.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.96 | 0.00 | 25.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.98 | 0.00 | 25.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.89 | 0.00 | 25.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.27 | 0.17 | 26.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.88 | 0.00 | 25.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.12 | 0.00 | 26.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.89 | 0.00 | 25.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.43 | 0.50 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.46 | 0.83 | 26.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.44 | 0.33 | 26.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.04 | 0.00 | 26.04 |
Annual Sum or Average | 0.00 | 0.00 | 61.33 | 26.32 | 2.83 | 26.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.88 | 0.00 | 25.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.12 | 1.00 | 27.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.73 | 0.00 | 25.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.64 | 0.00 | 25.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.85 | 0.00 | 25.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 25.71 | 0.00 | 25.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
February | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 18.84 | 2.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 1.00 | 18.27 | 0.17 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
March | 1.17 | 18.52 | 0.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
November | 1.33 | 18.27 | 0.17 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
December | 3.00 | 18.70 | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 14.83 | 18.70 | 3.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 19.44 | 2.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.71 | 1.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.67 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 6.00 | 18.80 | 1.00 | 19.00 | 1.00 | 20.04 | 0.67 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 19.34 | 1.00 | 19.34 | 1.00 | 27.35 | 0.67 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.18 | 0.17 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
February | 0.67 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.87 | 4.33 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.24 | 5.17 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.45 | 1.50 | 28.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.76 | 2.83 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Annual Sum or Average | 5.50 | 18.47 | 0.17 | 18.53 | 14.67 | 25.37 | 14.67 | 26.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.23 | 0.17 | 19.23 | 5.17 | 28.45 | 5.17 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.29 | 0.50 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
February | 0.67 | 19.18 | 0.00 | 19.18 | 1.83 | 25.63 | 1.83 | 26.62 |
March | 0.50 | 18.86 | 0.00 | 18.86 | 0.50 | 23.13 | 0.50 | 24.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.72 | 4.67 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.92 | 3.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.07 | 5.67 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.06 | 2.83 | 28.06 |
November | 0.17 | 19.07 | 0.00 | 19.07 | 1.33 | 26.62 | 1.33 | 27.06 |
December | 0.50 | 19.09 | 0.00 | 19.09 | 0.17 | 21.14 | 0.17 | 22.37 |
Annual Sum or Average | 6.33 | 18.51 | 0.50 | 18.65 | 22.17 | 25.71 | 21.33 | 26.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.18 | 0.50 | 19.18 | 6.00 | 28.07 | 5.67 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.45 | 0.67 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.29 | 1.83 | 28.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.30 | 1.17 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.92 | 2.83 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.99 | 6.00 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.52 | 4.83 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.15 | 2.33 | 28.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.30 | 0.50 | 28.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 2.50 | 18.90 | 0.00 | 18.90 | 54.00 | 27.47 | 20.67 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 18.90 | 0.00 | 18.90 | 18.17 | 28.30 | 6.00 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.17 | 17.10 | 22.83 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
February | 19.33 | 17.22 | 5.67 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
March | 8.17 | 17.57 | 2.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
April | 0.33 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 8.00 | 17.40 | 1.50 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
December | 21.00 | 17.07 | 5.67 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
Annual Sum or Average | 113.00 | 17.19 | 37.67 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.17 | 19.30 | 22.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 15.65 | 4.50 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
February | 11.67 | 16.55 | 1.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
March | 5.50 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
April | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
May | 0.67 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.98 | 3.83 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.30 | 6.17 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.39 | 2.50 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.84 | 2.83 | 27.84 |
October | 0.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 5.00 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
December | 13.67 | 16.33 | 3.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
Annual Sum or Average | 64.33 | 16.19 | 8.50 | 16.04 | 15.33 | 18.14 | 15.33 | 19.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 | 15.56 |
Maximum of Months | 27.17 | 19.29 | 4.50 | 19.29 | 6.17 | 28.39 | 6.17 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.00 | 16.18 | 3.00 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
February | 6.83 | 17.47 | 0.50 | 17.29 | 1.33 | 18.99 | 1.33 | 20.24 |
March | 3.50 | 17.27 | 0.17 | 17.41 | 0.33 | 18.24 | 0.33 | 18.93 |
April | 0.17 | 19.18 | 0.00 | 19.18 | 0.67 | 25.90 | 0.67 | 26.65 |
May | 0.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.70 | 4.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.01 | 2.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.20 | 5.83 | 28.23 |
October | 0.17 | 19.25 | 0.00 | 19.25 | 3.00 | 27.40 | 3.00 | 27.62 |
November | 2.67 | 17.43 | 0.17 | 17.61 | 1.00 | 20.23 | 1.00 | 21.77 |
December | 11.00 | 16.73 | 2.17 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
Annual Sum or Average | 46.83 | 16.70 | 6.00 | 16.60 | 20.17 | 19.74 | 18.83 | 21.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.00 | 19.25 | 3.00 | 19.25 | 6.50 | 28.20 | 5.83 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 15.75 | 3.83 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
February | 7.83 | 17.03 | 1.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
March | 3.67 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.17 | 19.44 | 0.00 | 19.44 | 0.83 | 26.60 | 0.33 | 26.95 |
May | 0.33 | 19.05 | 0.00 | 19.05 | 2.50 | 26.96 | 1.17 | 27.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.11 | 1.50 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.46 | 3.50 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.37 | 1.17 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.53 | 1.50 | 28.59 |
October | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
November | 3.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
December | 11.50 | 16.54 | 2.83 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
Annual Sum or Average | 50.83 | 16.36 | 7.67 | 16.17 | 19.17 | 19.17 | 9.17 | 20.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 0.00 | 15.64 |
Maximum of Months | 24.00 | 19.44 | 3.83 | 19.44 | 7.33 | 28.53 | 3.50 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 112.33 | 16.29 | 45.67 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
February | 44.17 | 16.69 | 13.17 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
March | 25.67 | 16.69 | 7.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
April | 3.50 | 18.51 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
May | 5.67 | 17.47 | 0.50 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.33 | 27.34 |
September | 0.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
October | 3.83 | 18.23 | 0.33 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
November | 30.33 | 16.25 | 9.83 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
December | 72.83 | 16.01 | 26.67 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
Annual Sum or Average | 299.17 | 16.39 | 103.50 | 16.61 | 1.00 | 16.64 | 0.33 | 16.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.33 | 19.21 | 45.67 | 19.21 | 0.50 | 27.41 | 0.33 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.33 | 15.19 | 13.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
February | 26.17 | 15.62 | 3.67 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 18.17 | 16.01 | 3.00 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
April | 3.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
May | 4.33 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.78 | 3.00 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.11 | 7.33 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.40 | 2.67 | 28.45 |
September | 0.67 | 19.18 | 0.00 | 19.18 | 4.00 | 26.57 | 4.00 | 27.13 |
October | 2.67 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
November | 20.67 | 15.67 | 3.33 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
December | 52.83 | 15.10 | 13.33 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 189.83 | 15.50 | 37.17 | 15.38 | 17.83 | 16.30 | 17.00 | 17.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 61.33 | 19.18 | 13.83 | 19.18 | 7.83 | 28.40 | 7.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.00 | 15.73 | 12.00 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
February | 20.00 | 16.17 | 1.50 | 16.09 | 0.83 | 16.53 | 0.83 | 16.94 |
March | 15.67 | 16.34 | 1.83 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 2.50 | 18.65 | 0.00 | 18.65 | 0.17 | 19.19 | 0.17 | 19.66 |
May | 4.17 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 3.83 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.32 | 2.17 | 28.36 |
September | 0.67 | 19.27 | 0.00 | 19.27 | 5.33 | 27.36 | 4.50 | 27.84 |
October | 1.67 | 18.42 | 0.00 | 18.42 | 1.33 | 22.75 | 1.33 | 24.42 |
November | 14.33 | 16.30 | 1.83 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
December | 40.33 | 15.46 | 8.17 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
Annual Sum or Average | 153.33 | 15.96 | 25.33 | 15.93 | 15.00 | 16.87 | 12.83 | 17.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.00 | 19.27 | 12.00 | 19.27 | 5.33 | 28.32 | 4.50 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.33 | 15.05 | 11.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
February | 20.00 | 15.90 | 2.83 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
March | 14.33 | 16.18 | 1.83 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
April | 1.83 | 18.80 | 0.00 | 18.80 | 0.67 | 21.16 | 0.33 | 21.92 |
May | 2.17 | 17.69 | 0.00 | 17.69 | 2.17 | 22.85 | 0.67 | 23.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.29 | 1.17 | 28.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.63 | 2.83 | 28.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.43 | 1.67 | 28.39 |
September | 0.50 | 19.27 | 0.00 | 19.27 | 3.00 | 27.13 | 2.00 | 27.65 |
October | 1.50 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
November | 14.83 | 15.97 | 2.83 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
December | 40.33 | 15.34 | 10.33 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
Annual Sum or Average | 145.83 | 15.59 | 29.00 | 15.43 | 19.33 | 16.72 | 8.67 | 17.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Maximum of Months | 50.33 | 19.27 | 11.17 | 19.27 | 7.33 | 28.63 | 2.83 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.00 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.96 | 16.00 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.17 | 27.95 | 16.00 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.96 | 16.00 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.94 | 4.50 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 27.94 | 4.50 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.94 | 4.50 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.01 | 4.50 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 28.01 | 4.50 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.01 | 4.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.89 | 22.83 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 500.17 | 29.07 | 382.83 | 29.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 524.83 | 29.02 | 405.67 | 29.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 500.17 | 29.07 | 382.83 | 29.12 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 392.50 | 23.32 | 33.50 | 23.56 | 0.00 | 23.56 |
February | 311.00 | 23.76 | 36.33 | 24.02 | 0.00 | 24.02 |
March | 280.00 | 23.97 | 36.00 | 24.21 | 0.00 | 24.21 |
April | 101.00 | 24.01 | 77.17 | 24.94 | 0.00 | 24.94 |
May | 96.00 | 24.00 | 103.00 | 25.02 | 0.00 | 25.02 |
June | 11.17 | 24.33 | 221.00 | 24.94 | 8.50 | 24.92 |
July | 11.17 | 25.14 | 333.33 | 24.91 | 11.17 | 24.91 |
August | 0.00 | 0.00 | 214.33 | 25.14 | 0.00 | 25.14 |
September | 25.17 | 24.00 | 209.17 | 25.09 | 16.50 | 25.02 |
October | 15.33 | 24.00 | 109.83 | 26.18 | 0.00 | 26.18 |
November | 114.50 | 24.00 | 89.33 | 25.09 | 0.00 | 25.09 |
December | 258.33 | 23.82 | 52.00 | 24.24 | 0.00 | 24.24 |
Annual Sum or Average | 1616.17 | 23.77 | 1515.00 | 24.59 | 36.17 | 24.59 |
Minimum of Months | 0.00 | 0.00 | 33.50 | 23.56 | 0.00 | 23.56 |
Maximum of Months | 392.50 | 25.14 | 333.33 | 26.18 | 16.50 | 26.18 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.00 | 23.53 | 10.50 | 23.59 | 0.00 | 23.59 |
February | 323.33 | 23.81 | 6.33 | 23.85 | 0.00 | 23.85 |
March | 245.00 | 23.97 | 22.33 | 24.12 | 0.00 | 24.12 |
April | 75.17 | 23.99 | 58.67 | 24.87 | 0.00 | 24.87 |
May | 96.33 | 23.98 | 87.33 | 24.70 | 0.00 | 24.70 |
June | 6.67 | 24.40 | 218.50 | 24.52 | 5.17 | 24.52 |
July | 2.33 | 25.18 | 348.83 | 24.43 | 2.33 | 24.43 |
August | 0.00 | 0.00 | 250.17 | 24.49 | 0.00 | 24.49 |
September | 36.17 | 24.05 | 198.50 | 24.60 | 14.00 | 24.57 |
October | 50.67 | 23.98 | 83.00 | 25.22 | 0.00 | 25.22 |
November | 163.67 | 23.98 | 54.33 | 24.49 | 0.00 | 24.49 |
December | 272.50 | 23.93 | 22.33 | 24.08 | 0.00 | 24.08 |
Annual Sum or Average | 1713.83 | 23.83 | 1360.83 | 24.28 | 21.50 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 6.33 | 23.59 | 0.00 | 23.59 |
Maximum of Months | 442.00 | 25.18 | 348.83 | 25.22 | 14.00 | 25.22 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.36 | 98.17 | 22.10 | 98.17 | 21.92 |
February | 449.50 | 22.91 | 28.17 | 22.77 | 28.17 | 22.64 |
March | 499.83 | 23.44 | 16.17 | 23.37 | 16.17 | 23.30 |
April | 335.67 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
May | 228.33 | 23.78 | 56.33 | 24.09 | 0.00 | 24.09 |
June | 65.50 | 23.84 | 156.67 | 24.25 | 5.50 | 24.25 |
July | 26.17 | 24.22 | 258.00 | 24.41 | 6.50 | 24.43 |
August | 14.50 | 23.80 | 151.33 | 24.61 | 0.00 | 24.61 |
September | 116.50 | 23.82 | 143.33 | 24.24 | 14.67 | 24.24 |
October | 287.33 | 23.76 | 6.33 | 23.80 | 0.00 | 23.80 |
November | 432.33 | 23.48 | 3.83 | 23.46 | 3.83 | 23.44 |
December | 497.00 | 22.73 | 56.50 | 22.51 | 56.50 | 22.33 |
Annual Sum or Average | 3454.67 | 23.22 | 974.83 | 23.34 | 229.50 | 23.24 |
Minimum of Months | 14.50 | 22.36 | 0.00 | 22.10 | 0.00 | 21.92 |
Maximum of Months | 502.00 | 24.22 | 258.00 | 24.61 | 98.17 | 24.61 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 315.17 | 20.51 | 315.17 | 20.38 |
February | 454.00 | 21.51 | 189.17 | 21.14 | 189.17 | 20.94 |
March | 514.00 | 22.26 | 112.83 | 21.90 | 112.83 | 21.65 |
April | 436.17 | 22.89 | 38.67 | 22.71 | 38.67 | 22.55 |
May | 308.33 | 23.17 | 65.17 | 23.23 | 22.00 | 23.08 |
June | 109.17 | 23.57 | 153.83 | 24.01 | 5.17 | 24.03 |
July | 42.50 | 23.87 | 279.00 | 24.31 | 8.67 | 24.32 |
August | 60.50 | 23.68 | 155.33 | 24.29 | 0.00 | 24.29 |
September | 224.50 | 23.31 | 122.67 | 23.73 | 17.00 | 23.75 |
October | 444.50 | 22.85 | 25.00 | 22.72 | 25.00 | 22.60 |
November | 485.50 | 22.02 | 127.33 | 21.67 | 127.33 | 21.43 |
December | 497.00 | 21.12 | 256.83 | 20.73 | 256.83 | 20.54 |
Annual Sum or Average | 4078.17 | 22.16 | 1841.00 | 22.08 | 1117.83 | 21.80 |
Minimum of Months | 42.50 | 20.78 | 25.00 | 20.51 | 0.00 | 20.38 |
Maximum of Months | 514.00 | 23.87 | 315.17 | 24.31 | 315.17 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.00 | 288.17 | 20.78 | 288.17 | 20.68 |
February | 454.00 | 21.75 | 132.17 | 21.48 | 132.17 | 21.32 |
March | 511.67 | 22.61 | 46.67 | 22.44 | 46.67 | 22.30 |
April | 393.33 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
May | 284.67 | 23.29 | 59.83 | 23.58 | 0.00 | 23.58 |
June | 60.17 | 23.64 | 215.33 | 24.17 | 4.17 | 24.17 |
July | 8.17 | 24.24 | 349.17 | 24.41 | 2.33 | 24.41 |
August | 35.50 | 23.66 | 219.17 | 24.27 | 0.50 | 24.28 |
September | 223.00 | 23.29 | 128.33 | 23.77 | 9.00 | 23.78 |
October | 411.83 | 23.19 | 4.67 | 23.21 | 0.00 | 23.21 |
November | 476.67 | 22.54 | 33.17 | 22.42 | 33.17 | 22.32 |
December | 497.00 | 21.70 | 159.33 | 21.42 | 159.33 | 21.26 |
Annual Sum or Average | 3858.00 | 22.42 | 1636.00 | 22.55 | 675.50 | 22.34 |
Minimum of Months | 8.17 | 21.00 | 0.00 | 20.78 | 0.00 | 20.68 |
Maximum of Months | 511.67 | 24.24 | 349.17 | 24.41 | 288.17 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 20.92 | 298.50 | 20.74 | 298.50 | 20.66 |
February | 432.83 | 21.52 | 150.17 | 21.32 | 147.83 | 21.18 |
March | 465.33 | 21.97 | 60.83 | 21.87 | 53.50 | 21.75 |
April | 340.00 | 22.43 | 45.67 | 22.68 | 1.00 | 22.68 |
May | 255.50 | 22.64 | 103.00 | 23.17 | 0.00 | 23.17 |
June | 125.00 | 23.51 | 271.17 | 24.09 | 19.17 | 24.19 |
July | 60.17 | 24.47 | 369.33 | 24.40 | 22.67 | 24.52 |
August | 118.00 | 23.20 | 281.17 | 23.91 | 5.83 | 23.96 |
September | 226.67 | 22.83 | 177.83 | 23.58 | 16.50 | 23.65 |
October | 380.50 | 22.54 | 16.33 | 22.65 | 0.00 | 22.65 |
November | 472.83 | 21.94 | 57.83 | 21.82 | 57.83 | 21.72 |
December | 497.00 | 21.23 | 198.33 | 21.04 | 198.33 | 20.93 |
Annual Sum or Average | 3873.50 | 22.00 | 2030.17 | 22.33 | 821.17 | 22.17 |
Minimum of Months | 60.17 | 20.92 | 16.33 | 20.74 | 0.00 | 20.66 |
Maximum of Months | 499.67 | 24.47 | 369.33 | 24.40 | 298.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.67 | 21.24 | 261.50 | 21.03 | 251.83 | 20.88 |
February | 351.67 | 21.83 | 152.83 | 21.83 | 117.17 | 21.65 |
March | 388.17 | 22.14 | 99.33 | 22.21 | 49.33 | 22.06 |
April | 308.00 | 22.60 | 60.17 | 22.90 | 3.50 | 22.89 |
May | 261.83 | 22.56 | 111.17 | 23.09 | 8.33 | 23.04 |
June | 127.83 | 23.15 | 223.00 | 23.91 | 5.50 | 23.92 |
July | 54.67 | 24.14 | 358.83 | 24.37 | 15.17 | 24.45 |
August | 79.17 | 23.63 | 311.50 | 24.18 | 9.83 | 24.25 |
September | 181.67 | 23.19 | 235.00 | 24.00 | 23.17 | 24.12 |
October | 270.33 | 22.80 | 117.17 | 23.32 | 7.33 | 23.38 |
November | 350.00 | 22.20 | 105.83 | 22.40 | 46.17 | 22.25 |
December | 423.50 | 21.56 | 170.67 | 21.38 | 152.50 | 21.19 |
Annual Sum or Average | 3255.50 | 22.21 | 2207.00 | 22.68 | 689.83 | 22.50 |
Minimum of Months | 54.67 | 21.24 | 60.17 | 21.03 | 3.50 | 20.88 |
Maximum of Months | 458.67 | 24.14 | 358.83 | 24.37 | 251.83 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.17 | 21.21 | 218.50 | 21.02 | 218.50 | 20.92 |
February | 404.50 | 22.01 | 88.50 | 21.94 | 74.17 | 21.80 |
March | 375.33 | 22.75 | 50.50 | 22.84 | 14.50 | 22.78 |
April | 127.00 | 23.24 | 150.50 | 24.20 | 5.33 | 24.26 |
May | 207.00 | 22.84 | 172.83 | 23.74 | 5.00 | 23.78 |
June | 55.83 | 23.82 | 365.67 | 24.35 | 14.17 | 24.41 |
July | 31.33 | 26.90 | 467.67 | 24.67 | 31.17 | 24.80 |
August | 20.17 | 26.30 | 474.17 | 24.51 | 17.00 | 24.59 |
September | 190.00 | 22.99 | 212.33 | 23.85 | 16.00 | 23.92 |
October | 262.00 | 22.92 | 92.17 | 23.44 | 2.00 | 23.46 |
November | 349.50 | 22.67 | 45.50 | 22.96 | 2.17 | 22.95 |
December | 431.83 | 22.37 | 52.67 | 22.27 | 45.50 | 22.15 |
Annual Sum or Average | 2954.67 | 22.47 | 2391.00 | 23.16 | 445.50 | 23.07 |
Minimum of Months | 20.17 | 21.21 | 45.50 | 21.02 | 2.00 | 20.92 |
Maximum of Months | 500.17 | 26.90 | 474.17 | 24.67 | 218.50 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 490.83 | 19.97 | 490.83 | 19.97 |
February | 454.00 | 20.47 | 368.67 | 20.36 | 368.67 | 20.32 |
March | 514.00 | 21.03 | 254.83 | 20.78 | 254.83 | 20.65 |
April | 475.17 | 22.04 | 79.17 | 21.81 | 79.17 | 21.63 |
May | 386.17 | 22.58 | 60.50 | 22.52 | 33.33 | 22.35 |
June | 144.00 | 23.25 | 152.33 | 23.75 | 4.50 | 23.76 |
July | 47.67 | 23.57 | 275.83 | 24.23 | 2.50 | 24.24 |
August | 122.00 | 23.29 | 130.50 | 23.88 | 0.00 | 23.88 |
September | 304.17 | 22.59 | 102.50 | 23.00 | 18.50 | 22.98 |
October | 495.00 | 22.00 | 63.50 | 21.82 | 63.50 | 21.68 |
November | 489.00 | 20.87 | 261.67 | 20.61 | 261.67 | 20.49 |
December | 497.00 | 20.10 | 438.67 | 20.03 | 438.67 | 20.00 |
Annual Sum or Average | 4430.17 | 21.35 | 2679.00 | 21.29 | 2016.17 | 21.04 |
Minimum of Months | 47.67 | 19.99 | 60.50 | 19.97 | 0.00 | 19.97 |
Maximum of Months | 514.00 | 23.57 | 490.83 | 24.23 | 490.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.00 | 399.17 | 19.97 | 399.17 | 19.95 |
February | 382.83 | 20.59 | 270.17 | 20.44 | 270.17 | 20.37 |
March | 423.17 | 21.03 | 187.33 | 20.79 | 187.33 | 20.67 |
April | 343.83 | 21.72 | 70.83 | 21.70 | 51.00 | 21.56 |
May | 288.83 | 22.07 | 82.33 | 22.29 | 28.00 | 22.12 |
June | 148.83 | 23.15 | 200.00 | 23.95 | 19.83 | 24.07 |
July | 81.00 | 24.23 | 294.33 | 24.51 | 28.17 | 24.67 |
August | 128.83 | 22.99 | 215.50 | 23.93 | 8.00 | 24.00 |
September | 250.50 | 22.32 | 120.83 | 23.08 | 17.83 | 23.15 |
October | 403.67 | 21.76 | 44.67 | 21.67 | 41.50 | 21.56 |
November | 416.00 | 20.82 | 216.33 | 20.63 | 216.33 | 20.53 |
December | 422.00 | 20.02 | 365.17 | 19.94 | 365.17 | 19.92 |
Annual Sum or Average | 3716.50 | 21.26 | 2466.67 | 21.45 | 1632.50 | 21.22 |
Minimum of Months | 81.00 | 20.00 | 44.67 | 19.94 | 8.00 | 19.92 |
Maximum of Months | 427.00 | 24.23 | 399.17 | 24.51 | 399.17 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.33 | 20.76 | 337.83 | 20.57 | 331.83 | 20.45 |
February | 373.33 | 21.30 | 227.17 | 21.23 | 194.50 | 21.04 |
March | 411.83 | 21.43 | 188.83 | 21.41 | 143.33 | 21.21 |
April | 352.33 | 21.92 | 99.17 | 22.09 | 50.33 | 21.95 |
May | 308.33 | 22.15 | 110.17 | 22.43 | 34.67 | 22.26 |
June | 183.83 | 22.80 | 193.67 | 23.60 | 5.00 | 23.61 |
July | 88.67 | 23.48 | 316.50 | 24.23 | 13.33 | 24.30 |
August | 126.33 | 23.13 | 285.17 | 24.04 | 8.00 | 24.10 |
September | 216.00 | 22.79 | 218.83 | 23.72 | 27.50 | 23.86 |
October | 321.50 | 22.30 | 125.17 | 22.75 | 29.50 | 22.73 |
November | 392.00 | 21.61 | 178.50 | 21.59 | 132.33 | 21.37 |
December | 455.83 | 20.79 | 285.50 | 20.52 | 283.50 | 20.39 |
Annual Sum or Average | 3704.33 | 21.71 | 2566.50 | 22.05 | 1253.83 | 21.81 |
Minimum of Months | 88.67 | 20.76 | 99.17 | 20.52 | 5.00 | 20.39 |
Maximum of Months | 474.33 | 23.48 | 337.83 | 24.23 | 331.83 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.22 | 452.33 | 20.17 | 452.33 | 20.15 |
February | 443.33 | 20.72 | 287.50 | 20.55 | 287.33 | 20.48 |
March | 489.17 | 21.06 | 192.33 | 20.88 | 188.83 | 20.76 |
April | 412.67 | 21.77 | 75.17 | 21.84 | 46.83 | 21.75 |
May | 329.17 | 22.11 | 116.00 | 22.50 | 30.17 | 22.40 |
June | 190.17 | 22.75 | 217.50 | 23.61 | 10.50 | 23.67 |
July | 100.50 | 23.46 | 327.00 | 24.21 | 17.00 | 24.31 |
August | 152.50 | 22.81 | 254.00 | 23.84 | 4.83 | 23.88 |
September | 307.50 | 22.23 | 139.33 | 22.95 | 18.50 | 23.02 |
October | 448.33 | 21.72 | 50.83 | 21.72 | 35.83 | 21.64 |
November | 480.67 | 21.02 | 204.00 | 20.80 | 204.00 | 20.67 |
December | 497.00 | 20.30 | 382.50 | 20.18 | 382.50 | 20.13 |
Annual Sum or Average | 4353.00 | 21.33 | 2698.50 | 21.54 | 1678.67 | 21.32 |
Minimum of Months | 100.50 | 20.22 | 50.83 | 20.17 | 4.83 | 20.13 |
Maximum of Months | 502.00 | 23.46 | 452.33 | 24.21 | 452.33 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 496.17 | 19.65 | 496.17 | 19.65 |
February | 454.00 | 20.01 | 433.33 | 19.98 | 433.33 | 19.97 |
March | 514.00 | 20.41 | 374.83 | 20.26 | 374.83 | 20.20 |
April | 481.83 | 21.16 | 201.17 | 20.83 | 201.17 | 20.65 |
May | 428.00 | 21.96 | 121.83 | 21.76 | 97.33 | 21.52 |
June | 210.83 | 22.72 | 138.50 | 23.29 | 5.50 | 23.30 |
July | 103.50 | 23.14 | 248.83 | 23.96 | 3.83 | 23.97 |
August | 191.17 | 22.85 | 124.83 | 23.43 | 1.33 | 23.43 |
September | 358.00 | 21.99 | 118.50 | 22.26 | 53.33 | 22.14 |
October | 501.33 | 21.04 | 207.17 | 20.74 | 207.17 | 20.58 |
November | 489.00 | 20.17 | 380.50 | 20.03 | 380.50 | 19.98 |
December | 497.00 | 19.82 | 478.33 | 19.80 | 478.33 | 19.79 |
Annual Sum or Average | 4730.67 | 20.87 | 3324.00 | 20.80 | 2732.83 | 20.58 |
Minimum of Months | 103.50 | 19.66 | 118.50 | 19.65 | 1.33 | 19.65 |
Maximum of Months | 514.00 | 23.14 | 496.17 | 23.96 | 496.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 486.67 | 19.80 | 486.67 | 19.80 |
February | 454.00 | 20.24 | 372.83 | 20.13 | 372.83 | 20.09 |
March | 507.17 | 20.69 | 305.83 | 20.46 | 305.83 | 20.35 |
April | 406.33 | 21.27 | 143.67 | 21.02 | 133.17 | 20.82 |
May | 338.67 | 21.78 | 135.00 | 21.89 | 67.17 | 21.63 |
June | 154.17 | 22.69 | 254.33 | 23.75 | 15.17 | 23.82 |
July | 94.00 | 24.02 | 364.67 | 24.37 | 29.00 | 24.51 |
August | 143.33 | 22.81 | 293.50 | 23.84 | 10.00 | 23.90 |
September | 301.33 | 22.16 | 156.50 | 22.80 | 43.50 | 22.81 |
October | 485.33 | 21.27 | 136.33 | 20.99 | 136.33 | 20.82 |
November | 489.00 | 20.31 | 345.00 | 20.15 | 345.00 | 20.09 |
December | 497.00 | 19.88 | 465.50 | 19.84 | 465.50 | 19.83 |
Annual Sum or Average | 4372.33 | 20.92 | 3459.83 | 21.13 | 2410.17 | 20.89 |
Minimum of Months | 94.00 | 19.82 | 135.00 | 19.80 | 10.00 | 19.80 |
Maximum of Months | 507.17 | 24.02 | 486.67 | 24.37 | 486.67 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.67 | 20.26 | 401.17 | 20.07 | 401.17 | 20.00 |
February | 406.17 | 20.83 | 274.67 | 20.63 | 258.50 | 20.47 |
March | 437.50 | 20.90 | 269.17 | 20.74 | 242.33 | 20.57 |
April | 386.00 | 21.36 | 171.83 | 21.26 | 134.50 | 21.02 |
May | 341.50 | 21.74 | 152.17 | 21.88 | 80.67 | 21.63 |
June | 213.83 | 22.44 | 189.83 | 23.32 | 8.00 | 23.32 |
July | 125.33 | 23.17 | 298.17 | 24.05 | 15.33 | 24.14 |
August | 157.00 | 22.77 | 280.00 | 23.81 | 9.33 | 23.85 |
September | 244.50 | 22.29 | 221.83 | 23.18 | 48.50 | 23.18 |
October | 362.00 | 21.57 | 169.50 | 21.72 | 97.67 | 21.50 |
November | 428.83 | 20.94 | 247.17 | 20.73 | 230.33 | 20.57 |
December | 475.33 | 20.28 | 364.83 | 20.07 | 364.83 | 19.98 |
Annual Sum or Average | 4069.67 | 21.23 | 3040.33 | 21.45 | 1891.17 | 21.18 |
Minimum of Months | 125.33 | 20.26 | 152.17 | 20.07 | 8.00 | 19.98 |
Maximum of Months | 491.67 | 23.17 | 401.17 | 24.05 | 401.17 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 473.67 | 19.84 | 473.67 | 19.83 |
February | 448.83 | 20.36 | 353.33 | 20.22 | 353.33 | 20.17 |
March | 495.50 | 20.68 | 295.33 | 20.49 | 293.50 | 20.40 |
April | 426.33 | 21.25 | 154.50 | 21.14 | 131.00 | 20.96 |
May | 368.00 | 21.82 | 147.00 | 22.04 | 68.00 | 21.84 |
June | 223.67 | 22.45 | 210.33 | 23.37 | 11.83 | 23.42 |
July | 137.50 | 23.10 | 304.67 | 24.01 | 18.17 | 24.11 |
August | 190.17 | 22.57 | 239.00 | 23.59 | 6.83 | 23.63 |
September | 330.33 | 21.89 | 150.33 | 22.49 | 45.83 | 22.47 |
October | 468.83 | 21.20 | 144.00 | 21.03 | 132.33 | 20.86 |
November | 487.67 | 20.52 | 313.50 | 20.32 | 313.50 | 20.24 |
December | 497.00 | 19.99 | 438.17 | 19.92 | 438.17 | 19.89 |
Annual Sum or Average | 4575.83 | 20.99 | 3223.83 | 21.14 | 2286.17 | 20.91 |
Minimum of Months | 137.50 | 19.87 | 144.00 | 19.84 | 6.83 | 19.83 |
Maximum of Months | 502.00 | 23.10 | 473.67 | 24.01 | 473.67 | 24.11 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 26.27 | 386.67 | 27.00 | 0.00 | 27.00 |
February | 1.17 | 27.00 | 437.67 | 27.00 | 1.17 | 27.00 |
March | 5.17 | 27.00 | 513.17 | 27.00 | 5.17 | 27.00 |
April | 21.33 | 27.00 | 485.00 | 27.00 | 21.33 | 27.00 |
May | 1.50 | 27.00 | 508.00 | 27.00 | 1.50 | 27.00 |
June | 13.83 | 27.00 | 496.00 | 27.00 | 13.83 | 27.00 |
July | 104.17 | 27.00 | 497.00 | 27.00 | 104.17 | 27.00 |
August | 213.83 | 27.10 | 514.00 | 27.06 | 213.83 | 27.07 |
September | 7.50 | 27.00 | 485.00 | 27.00 | 7.50 | 27.00 |
October | 8.33 | 27.00 | 502.00 | 27.00 | 8.33 | 27.00 |
November | 5.67 | 27.00 | 489.00 | 27.00 | 5.67 | 27.00 |
December | 2.67 | 27.00 | 497.00 | 27.00 | 2.67 | 27.00 |
Annual Sum or Average | 386.00 | 27.06 | 5810.50 | 27.01 | 385.17 | 27.01 |
Minimum of Months | 0.83 | 26.27 | 386.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 213.83 | 27.10 | 514.00 | 27.06 | 213.83 | 27.07 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.67 | 25.60 | 211.17 | 26.54 | 0.00 | 26.54 |
February | 13.17 | 27.00 | 315.00 | 27.00 | 0.00 | 27.00 |
March | 6.33 | 27.00 | 464.67 | 27.00 | 0.00 | 27.00 |
April | 3.33 | 27.00 | 481.67 | 27.00 | 3.33 | 27.00 |
May | 0.83 | 27.00 | 500.33 | 27.00 | 0.83 | 27.00 |
June | 6.83 | 27.00 | 496.00 | 27.00 | 6.83 | 27.00 |
July | 15.67 | 27.00 | 497.00 | 27.00 | 15.67 | 27.00 |
August | 35.00 | 27.26 | 514.00 | 27.04 | 35.00 | 27.05 |
September | 3.83 | 27.00 | 485.00 | 27.00 | 3.83 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 455.83 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 345.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 198.67 | 26.33 | 5268.33 | 26.98 | 65.50 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 211.17 | 26.54 | 0.00 | 26.54 |
Maximum of Months | 101.67 | 27.26 | 514.00 | 27.04 | 35.00 | 27.05 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.33 | 24.60 | 120.33 | 24.93 | 30.33 | 24.71 |
February | 46.50 | 26.94 | 184.83 | 26.99 | 0.00 | 26.99 |
March | 21.83 | 27.00 | 356.17 | 27.00 | 0.00 | 27.00 |
April | 4.00 | 27.00 | 423.83 | 27.00 | 4.00 | 27.00 |
May | 22.67 | 25.80 | 473.33 | 26.95 | 1.50 | 26.95 |
June | 9.67 | 27.00 | 496.00 | 27.00 | 9.67 | 27.00 |
July | 38.67 | 27.00 | 497.00 | 27.00 | 38.67 | 27.00 |
August | 54.17 | 27.15 | 514.00 | 27.03 | 54.17 | 27.04 |
September | 6.00 | 27.00 | 476.33 | 27.00 | 6.00 | 27.00 |
October | 0.00 | 0.00 | 457.00 | 27.00 | 0.00 | 27.00 |
November | 22.33 | 27.00 | 321.00 | 27.00 | 0.00 | 27.00 |
December | 66.00 | 27.00 | 205.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 564.17 | 25.80 | 4525.00 | 26.84 | 144.33 | 26.81 |
Minimum of Months | 0.00 | 0.00 | 120.33 | 24.93 | 0.00 | 24.71 |
Maximum of Months | 272.33 | 27.15 | 514.00 | 27.03 | 54.17 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 241.17 | 27.00 | 502.00 | 27.00 | 241.17 | 27.00 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 27.07 | 485.00 | 27.07 | 485.00 | 27.07 |
May | 491.67 | 27.00 | 508.00 | 27.00 | 491.67 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 28.66 | 514.00 | 28.66 | 514.00 | 28.66 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5665.83 | 27.16 | 5943.00 | 27.16 | 5665.83 | 27.16 |
Minimum of Months | 241.17 | 27.00 | 454.00 | 27.00 | 241.17 | 27.00 |
Maximum of Months | 514.00 | 28.66 | 514.00 | 28.66 | 514.00 | 28.66 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99405 | 13.62705 | 0.61061 | 13.04016 |
February | 454.00000 | 27.00000 | 14.88933 | 0.70518 | 15.63201 |
March | 514.00000 | 27.00000 | 16.83122 | 0.78837 | 18.22970 |
April | 485.00000 | 27.00001 | 19.99761 | 0.88481 | 21.61421 |
May | 508.00000 | 27.00015 | 22.19870 | 0.14055 | 5.58368 |
June | 496.00000 | 27.00044 | 25.69883 | 0.25490 | 6.45331 |
July | 497.00000 | 27.00025 | 26.88134 | 0.32863 | 7.33538 |
August | 514.00000 | 27.04375 | 26.41301 | 0.38385 | 8.26142 |
September | 485.00000 | 27.00050 | 25.35357 | 0.17549 | 5.80399 |
October | 502.00000 | 27.00006 | 22.35811 | 0.83585 | 19.80843 |
November | 489.00000 | 27.00000 | 18.48412 | 0.80606 | 18.80768 |
December | 497.00000 | 27.00000 | 14.81276 | 0.76660 | 17.53778 |
Annual Sum or Average | 5943.00000 | 27.00340 | 20.66825 | 0.55517 | 13.14108 |
Minimum of Months | 454.00000 | 26.99405 | 13.62705 | 0.14055 | 5.58368 |
Maximum of Months | 514.00000 | 27.04375 | 26.88134 | 0.88481 | 21.61421 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.68681 | 13.64573 | 0.43896 | 9.89855 |
February | 454.00000 | 27.00000 | 14.88082 | 0.57091 | 12.05691 |
March | 514.00000 | 27.00000 | 16.81442 | 0.64385 | 13.92053 |
April | 485.00000 | 27.00002 | 19.96627 | 0.73886 | 16.65944 |
May | 508.00000 | 27.00014 | 22.21604 | 0.04347 | 5.33628 |
June | 496.00000 | 27.00042 | 25.71161 | 0.15741 | 5.69508 |
July | 497.00000 | 27.00027 | 26.88216 | 0.21893 | 6.14458 |
August | 514.00000 | 27.02071 | 26.43164 | 0.23183 | 6.33626 |
September | 485.00000 | 27.00042 | 25.45389 | 0.08598 | 5.40024 |
October | 502.00000 | 27.00006 | 22.33874 | 0.72743 | 16.25041 |
November | 489.00000 | 27.00000 | 18.45781 | 0.65305 | 14.13850 |
December | 497.00000 | 27.00000 | 14.78576 | 0.57106 | 12.08281 |
Annual Sum or Average | 5943.00000 | 26.97544 | 20.67153 | 0.42184 | 10.30117 |
Minimum of Months | 454.00000 | 26.68681 | 13.64573 | 0.04347 | 5.33628 |
Maximum of Months | 514.00000 | 27.02071 | 26.88216 | 0.73886 | 16.65944 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.65374 | 14.08579 | 0.16813 | 8.77225 |
February | 454.00000 | 26.99363 | 14.88239 | 0.49645 | 10.51011 |
March | 514.00000 | 27.00000 | 16.82124 | 0.57505 | 12.29428 |
April | 485.00000 | 27.00002 | 19.98205 | 0.68075 | 15.08178 |
May | 508.00000 | 26.94324 | 22.27237 | -0.0193 | 6.02306 |
June | 496.00000 | 27.00043 | 25.72502 | 0.14559 | 5.77934 |
July | 497.00000 | 27.00027 | 26.89120 | 0.22018 | 6.27739 |
August | 514.00000 | 27.01722 | 26.44358 | 0.22246 | 6.38640 |
September | 485.00000 | 27.00026 | 25.53362 | 0.04753 | 5.52354 |
October | 502.00000 | 27.00006 | 22.36171 | 0.66256 | 14.46683 |
November | 489.00000 | 27.00000 | 18.46961 | 0.56931 | 12.10518 |
December | 497.00000 | 27.00000 | 14.79698 | 0.48893 | 10.37074 |
Annual Sum or Average | 5943.00000 | 26.88252 | 20.72878 | 0.35314 | 9.44857 |
Minimum of Months | 454.00000 | 25.65374 | 14.08579 | -0.0193 | 5.52354 |
Maximum of Months | 514.00000 | 27.01722 | 26.89120 | 0.68075 | 15.08178 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99981 | 30.00048 | 0.99464 | 25.93402 |
February | 454.00000 | 27.01076 | 29.99976 | 1.18377 | 34.47959 |
March | 514.00000 | 27.00792 | 29.99988 | 1.34330 | 42.52384 |
April | 485.00000 | 27.06801 | 29.99901 | 1.49962 | 50.88221 |
May | 508.00000 | 27.00178 | 30.00193 | 0.46888 | 9.63623 |
June | 496.00000 | 27.00941 | 29.99928 | 0.71351 | 15.72974 |
July | 497.00000 | 27.00526 | 30.02750 | 0.93146 | 23.34127 |
August | 514.00000 | 28.65540 | 29.87932 | 1.59976 | 55.53314 |
September | 485.00000 | 27.00301 | 30.00190 | 0.52566 | 10.84545 |
October | 502.00000 | 27.01093 | 29.99904 | 1.24836 | 37.65016 |
November | 489.00000 | 27.00796 | 29.99858 | 1.37456 | 44.16500 |
December | 497.00000 | 27.00096 | 30.00029 | 1.48289 | 49.97483 |
Annual Sum or Average | 5943.00000 | 27.15349 | 29.99188 | 1.11435 | 33.42489 |
Minimum of Months | 454.00000 | 26.99981 | 29.87932 | 0.46888 | 9.63623 |
Maximum of Months | 514.00000 | 28.65540 | 30.02750 | 1.59976 | 55.53314 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73832 | 12.34237 | 0.10002 | 6.72593 |
February | 454.00000 | 24.15895 | 14.03776 | 0.21030 | 6.55546 |
March | 514.00000 | 24.28154 | 15.05086 | 0.25695 | 6.67277 |
April | 485.00000 | 24.44502 | 18.64676 | 0.32158 | 7.49633 |
May | 508.00000 | 24.46611 | 22.35799 | -0.5038 | 11.29442 |
June | 496.00000 | 24.43937 | 31.09516 | -0.4323 | 9.70914 |
July | 497.00000 | 24.60722 | 35.54968 | -0.3415 | 8.74563 |
August | 514.00000 | 24.47938 | 30.66735 | -0.4036 | 9.35473 |
September | 485.00000 | 24.54175 | 30.22147 | -0.4025 | 9.54645 |
October | 502.00000 | 24.57479 | 20.80531 | 0.38164 | 8.62212 |
November | 489.00000 | 24.55173 | 16.26124 | 0.33675 | 7.88526 |
December | 497.00000 | 24.31282 | 13.36666 | 0.25448 | 6.92385 |
Annual Sum or Average | 5943.00000 | 24.38378 | 21.74958 | -0.0212 | 8.30922 |
Minimum of Months | 454.00000 | 23.73832 | 12.34237 | -0.5038 | 6.55546 |
Maximum of Months | 514.00000 | 24.60722 | 35.54968 | 0.38164 | 11.29442 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68651 | 13.04966 | 0.06430 | 5.98185 |
February | 454.00000 | 24.02110 | 14.84340 | 0.17577 | 6.03968 |
March | 514.00000 | 24.20936 | 15.93786 | 0.25136 | 6.54130 |
April | 485.00000 | 24.33272 | 19.54558 | 0.32384 | 7.45273 |
May | 508.00000 | 24.33909 | 23.45996 | -0.5239 | 11.43407 |
June | 496.00000 | 24.24499 | 32.05497 | -0.4530 | 9.66159 |
July | 497.00000 | 24.30755 | 35.72359 | -0.3925 | 8.69594 |
August | 514.00000 | 24.25038 | 31.26365 | -0.4296 | 9.17083 |
September | 485.00000 | 24.30819 | 31.31189 | -0.4579 | 9.98288 |
October | 502.00000 | 24.38472 | 22.34635 | 0.34878 | 7.85851 |
November | 489.00000 | 24.37523 | 17.39576 | 0.29984 | 7.16511 |
December | 497.00000 | 24.23208 | 14.27086 | 0.23116 | 6.43252 |
Annual Sum or Average | 5943.00000 | 24.22513 | 22.64948 | -0.0495 | 8.05072 |
Minimum of Months | 454.00000 | 23.68651 | 13.04966 | -0.5239 | 5.98185 |
Maximum of Months | 514.00000 | 24.38472 | 35.72359 | 0.34878 | 11.43407 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35589 | 15.70764 | -0.2713 | 8.12650 |
February | 454.00000 | 22.92322 | 16.30397 | -0.1186 | 6.60630 |
March | 514.00000 | 23.46641 | 17.26424 | 0.03646 | 5.92256 |
April | 485.00000 | 23.88549 | 20.85431 | 0.18024 | 6.00521 |
May | 508.00000 | 24.11749 | 24.16080 | -0.6367 | 14.33974 |
June | 496.00000 | 24.14256 | 32.54658 | -0.5236 | 11.08990 |
July | 497.00000 | 24.23947 | 36.14691 | -0.4574 | 9.82442 |
August | 514.00000 | 24.22276 | 31.52262 | -0.4953 | 10.46250 |
September | 485.00000 | 24.15934 | 31.90707 | -0.5426 | 11.75378 |
October | 502.00000 | 23.98325 | 23.66789 | 0.22242 | 6.24108 |
November | 489.00000 | 23.56446 | 18.94718 | 0.06675 | 5.79849 |
December | 497.00000 | 22.73498 | 15.66881 | -0.1681 | 7.25665 |
Annual Sum or Average | 5943.00000 | 23.65457 | 23.77059 | -0.2274 | 8.64155 |
Minimum of Months | 454.00000 | 22.35589 | 15.66881 | -0.6367 | 5.79849 |
Maximum of Months | 514.00000 | 24.23947 | 36.14691 | 0.22242 | 14.33974 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78127 | 14.39112 | -0.6949 | 18.16078 |
February | 454.00000 | 21.50629 | 17.11249 | -0.4859 | 12.67041 |
March | 514.00000 | 22.26133 | 18.58611 | -0.2778 | 9.43681 |
April | 485.00000 | 23.01033 | 22.24621 | -0.0483 | 6.86140 |
May | 508.00000 | 23.63229 | 24.95672 | -0.8205 | 21.83846 |
June | 496.00000 | 24.03352 | 32.62163 | -0.5616 | 12.36369 |
July | 497.00000 | 24.20198 | 36.02322 | -0.4615 | 9.93169 |
August | 514.00000 | 24.16352 | 31.55560 | -0.5163 | 11.05732 |
September | 485.00000 | 23.83717 | 32.73849 | -0.6707 | 16.32686 |
October | 502.00000 | 22.98555 | 25.60804 | -0.0387 | 6.56109 |
November | 489.00000 | 22.03599 | 20.52812 | -0.3261 | 10.10001 |
December | 497.00000 | 21.11673 | 16.56674 | -0.5873 | 15.94368 |
Annual Sum or Average | 5943.00000 | 22.80717 | 24.45278 | -0.4580 | 12.61456 |
Minimum of Months | 454.00000 | 20.78127 | 14.39112 | -0.8205 | 6.56109 |
Maximum of Months | 514.00000 | 24.20198 | 36.02322 | -0.0387 | 21.83846 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.99918 | 12.62436 | -0.6163 | 15.18572 |
February | 454.00000 | 21.74864 | 15.24681 | -0.3888 | 10.09275 |
March | 514.00000 | 22.62051 | 16.39018 | -0.1551 | 7.03800 |
April | 485.00000 | 23.42788 | 19.92564 | 0.08019 | 5.83636 |
May | 508.00000 | 23.74334 | 23.59864 | -0.7380 | 18.39244 |
June | 496.00000 | 24.12182 | 31.56079 | -0.4831 | 10.47493 |
July | 497.00000 | 24.30231 | 34.90862 | -0.3700 | 8.45063 |
August | 514.00000 | 24.16744 | 30.75682 | -0.4597 | 9.94140 |
September | 485.00000 | 23.84059 | 31.51738 | -0.6397 | 15.52380 |
October | 502.00000 | 23.35556 | 22.86250 | 0.07289 | 5.77429 |
November | 489.00000 | 22.58376 | 18.07312 | -0.1560 | 6.89529 |
December | 497.00000 | 21.69608 | 14.73312 | -0.3998 | 10.13592 |
Annual Sum or Average | 5943.00000 | 23.05988 | 22.72789 | -0.3551 | 10.32128 |
Minimum of Months | 454.00000 | 20.99918 | 12.62436 | -0.7380 | 5.77429 |
Maximum of Months | 514.00000 | 24.30231 | 34.90862 | 0.08019 | 18.39244 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94028 | 11.92496 | -0.6183 | 15.19041 |
February | 454.00000 | 21.65624 | 14.58214 | -0.3847 | 10.39017 |
March | 514.00000 | 22.18201 | 16.02051 | -0.2131 | 8.02203 |
April | 485.00000 | 22.95723 | 19.96277 | 0.02975 | 6.86849 |
May | 508.00000 | 23.42212 | 23.47511 | -0.7527 | 20.13459 |
June | 496.00000 | 23.97954 | 31.53244 | -0.4271 | 11.23774 |
July | 497.00000 | 24.19871 | 34.93194 | -0.2913 | 8.76484 |
August | 514.00000 | 23.87382 | 31.00036 | -0.4519 | 11.21158 |
September | 485.00000 | 23.58825 | 31.59396 | -0.6301 | 16.90182 |
October | 502.00000 | 22.93725 | 22.81179 | 0.02533 | 6.43000 |
November | 489.00000 | 22.02116 | 17.90931 | -0.2554 | 7.80942 |
December | 497.00000 | 21.22731 | 14.39155 | -0.4967 | 11.59464 |
Annual Sum or Average | 5943.00000 | 22.75670 | 22.55910 | -0.3729 | 11.22750 |
Minimum of Months | 454.00000 | 20.94028 | 11.92496 | -0.7527 | 6.43000 |
Maximum of Months | 514.00000 | 24.19871 | 34.93194 | 0.02975 | 20.13459 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.52785 | 11.70618 | -0.4662 | 13.82541 |
February | 454.00000 | 22.41233 | 14.01706 | -0.1833 | 10.06063 |
March | 514.00000 | 22.64086 | 15.59496 | -0.0921 | 8.27065 |
April | 485.00000 | 23.19602 | 19.71806 | 0.07869 | 7.16350 |
May | 508.00000 | 23.40555 | 23.56771 | -0.7870 | 21.89718 |
June | 496.00000 | 23.91782 | 31.74909 | -0.4994 | 12.16169 |
July | 497.00000 | 24.20829 | 34.95816 | -0.3329 | 8.84551 |
August | 514.00000 | 24.08665 | 30.60633 | -0.3800 | 9.74566 |
September | 485.00000 | 23.88807 | 30.98856 | -0.5014 | 14.60569 |
October | 502.00000 | 23.47316 | 22.02309 | 0.17981 | 7.86180 |
November | 489.00000 | 22.83121 | 17.11766 | -0.0443 | 8.24350 |
December | 497.00000 | 21.97527 | 13.83822 | -0.3036 | 10.85671 |
Annual Sum or Average | 5943.00000 | 23.13484 | 22.20735 | -0.2793 | 11.14790 |
Minimum of Months | 454.00000 | 21.52785 | 11.70618 | -0.7870 | 7.16350 |
Maximum of Months | 514.00000 | 24.20829 | 34.95816 | 0.17981 | 21.89718 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.22336 | 11.59870 | -0.5139 | 12.28287 |
February | 454.00000 | 22.28596 | 13.85745 | -0.1899 | 8.14586 |
March | 514.00000 | 23.17127 | 14.95698 | 0.06184 | 6.70467 |
April | 485.00000 | 24.11162 | 18.49627 | 0.35353 | 8.68226 |
May | 508.00000 | 23.76945 | 22.92951 | -0.5912 | 15.88752 |
June | 496.00000 | 24.20628 | 31.10220 | -0.2955 | 8.56886 |
July | 497.00000 | 24.47833 | 34.31203 | -0.1247 | 7.07032 |
August | 514.00000 | 24.38709 | 29.94851 | -0.1663 | 7.00417 |
September | 485.00000 | 23.78446 | 31.06976 | -0.5190 | 14.15876 |
October | 502.00000 | 23.63098 | 21.70636 | 0.22340 | 7.23012 |
November | 489.00000 | 23.20763 | 16.54236 | 0.06656 | 6.71967 |
December | 497.00000 | 22.63015 | 13.10086 | -0.1115 | 7.10088 |
Annual Sum or Average | 5943.00000 | 23.41443 | 21.68260 | -0.1511 | 9.13142 |
Minimum of Months | 454.00000 | 21.22336 | 11.59870 | -0.5912 | 6.70467 |
Maximum of Months | 514.00000 | 24.47833 | 34.31203 | 0.35353 | 15.88752 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98553 | 12.72868 | -0.9403 | 25.84211 |
February | 454.00000 | 20.46821 | 15.78620 | -0.7563 | 18.84629 |
March | 514.00000 | 21.03231 | 17.46904 | -0.5623 | 13.69192 |
April | 485.00000 | 22.07558 | 21.74296 | -0.2565 | 8.25993 |
May | 508.00000 | 22.97461 | 24.75261 | -1.0155 | 29.77769 |
June | 496.00000 | 23.86244 | 32.18809 | -0.5982 | 13.70037 |
July | 497.00000 | 24.16572 | 35.08864 | -0.4519 | 9.96230 |
August | 514.00000 | 23.98070 | 31.11341 | -0.5699 | 12.83708 |
September | 485.00000 | 23.23534 | 32.65825 | -0.8622 | 24.21688 |
October | 502.00000 | 22.02872 | 24.77953 | -0.2523 | 7.91207 |
November | 489.00000 | 20.87041 | 19.27771 | -0.5963 | 14.83153 |
December | 497.00000 | 20.09934 | 15.38735 | -0.8580 | 23.04005 |
Annual Sum or Average | 5943.00000 | 22.07781 | 23.62528 | -0.6431 | 16.90480 |
Minimum of Months | 454.00000 | 19.98553 | 12.72868 | -1.0155 | 7.91207 |
Maximum of Months | 514.00000 | 24.16572 | 35.08864 | -0.2523 | 29.77769 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.00056 | 11.60973 | -0.9219 | 25.05661 |
February | 385.00000 | 20.60899 | 14.58034 | -0.6973 | 17.43834 |
March | 433.00000 | 21.09250 | 16.15237 | -0.5171 | 13.04077 |
April | 410.00000 | 22.13057 | 20.61163 | -0.1916 | 8.53810 |
May | 430.00000 | 22.78934 | 24.10187 | -0.9909 | 30.00474 |
June | 418.00000 | 23.83078 | 31.55332 | -0.4987 | 14.05799 |
July | 422.00000 | 24.24949 | 34.44596 | -0.3023 | 9.84818 |
August | 433.00000 | 23.88198 | 30.43768 | -0.4862 | 13.10655 |
September | 410.00000 | 23.12595 | 32.18143 | -0.8094 | 24.31521 |
October | 427.00000 | 21.89826 | 23.79306 | -0.2414 | 7.85736 |
November | 417.00000 | 20.82537 | 18.06420 | -0.5887 | 14.08687 |
December | 422.00000 | 20.01904 | 14.21640 | -0.8660 | 23.20927 |
Annual Sum or Average | 5034.00000 | 22.04620 | 22.67987 | -0.5926 | 16.71880 |
Minimum of Months | 385.00000 | 20.00056 | 11.60973 | -0.9909 | 7.85736 |
Maximum of Months | 433.00000 | 24.24949 | 34.44596 | -0.1916 | 30.00474 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97184 | 11.44203 | -0.6362 | 18.01768 |
February | 454.00000 | 21.85571 | 13.91524 | -0.3401 | 12.98561 |
March | 514.00000 | 21.98434 | 15.83205 | -0.2645 | 10.81426 |
April | 485.00000 | 22.57303 | 20.44451 | -0.0803 | 8.37010 |
May | 508.00000 | 22.97998 | 24.11504 | -0.9386 | 28.20120 |
June | 496.00000 | 23.67663 | 32.21559 | -0.5942 | 15.28868 |
July | 497.00000 | 24.10393 | 35.04354 | -0.3893 | 10.27579 |
August | 514.00000 | 23.98299 | 30.63275 | -0.4416 | 11.82492 |
September | 485.00000 | 23.63769 | 31.39053 | -0.5865 | 18.33589 |
October | 502.00000 | 22.99173 | 22.63822 | 0.06526 | 8.48776 |
November | 489.00000 | 22.15960 | 17.32663 | -0.2234 | 10.58435 |
December | 497.00000 | 21.06249 | 13.92676 | -0.5629 | 16.43370 |
Annual Sum or Average | 5943.00000 | 22.67084 | 22.46156 | -0.4175 | 14.15950 |
Minimum of Months | 454.00000 | 20.97184 | 11.44203 | -0.9386 | 8.37010 |
Maximum of Months | 514.00000 | 24.10393 | 35.04354 | 0.06526 | 28.20120 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22103 | 11.72890 | -0.8572 | 22.56112 |
February | 454.00000 | 20.79716 | 14.60741 | -0.6331 | 15.91979 |
March | 514.00000 | 21.20638 | 16.42169 | -0.4730 | 12.13123 |
April | 485.00000 | 22.14280 | 20.84836 | -0.1740 | 8.06968 |
May | 508.00000 | 22.87945 | 24.16951 | -0.9360 | 28.55736 |
June | 496.00000 | 23.61064 | 32.32315 | -0.5631 | 15.18531 |
July | 497.00000 | 24.03410 | 35.23663 | -0.3690 | 10.42460 |
August | 514.00000 | 23.80424 | 31.01509 | -0.4978 | 13.12441 |
September | 485.00000 | 22.97970 | 32.51527 | -0.8351 | 25.25725 |
October | 502.00000 | 21.97539 | 23.93301 | -0.2070 | 7.76378 |
November | 489.00000 | 21.07072 | 18.23502 | -0.5087 | 12.64677 |
December | 497.00000 | 20.30090 | 14.36985 | -0.7768 | 20.17113 |
Annual Sum or Average | 5943.00000 | 22.09593 | 22.99842 | -0.5692 | 15.98941 |
Minimum of Months | 454.00000 | 20.22103 | 11.72890 | -0.9360 | 7.76378 |
Maximum of Months | 514.00000 | 24.03410 | 35.23663 | -0.1740 | 28.55736 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65918 | 12.46043 | -1.0954 | 32.55441 |
February | 454.00000 | 20.01040 | 15.71318 | -0.9276 | 25.51783 |
March | 514.00000 | 20.41078 | 17.47957 | -0.7623 | 19.72263 |
April | 485.00000 | 21.17814 | 22.30994 | -0.4930 | 13.07968 |
May | 508.00000 | 22.31492 | 25.34050 | -1.2484 | 39.42905 |
June | 496.00000 | 23.50811 | 32.68185 | -0.7092 | 18.25360 |
July | 497.00000 | 23.96042 | 35.37420 | -0.5071 | 11.83338 |
August | 514.00000 | 23.67752 | 31.55103 | -0.6623 | 16.37219 |
September | 485.00000 | 22.60678 | 33.55053 | -1.0774 | 33.75156 |
October | 502.00000 | 21.04001 | 25.75063 | -0.5130 | 12.94976 |
November | 489.00000 | 20.16710 | 19.62367 | -0.8232 | 22.13715 |
December | 497.00000 | 19.81939 | 15.07545 | -1.0074 | 28.90970 |
Annual Sum or Average | 5943.00000 | 21.54284 | 23.95464 | -0.8184 | 22.85920 |
Minimum of Months | 454.00000 | 19.65918 | 12.46043 | -1.2484 | 11.83338 |
Maximum of Months | 514.00000 | 23.96042 | 35.37420 | -0.4930 | 39.42905 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82268 | 11.98107 | -1.0343 | 29.89003 |
February | 454.00000 | 20.24156 | 14.98955 | -0.8348 | 22.26286 |
March | 514.00000 | 20.73592 | 16.67275 | -0.6431 | 16.85247 |
April | 485.00000 | 21.72854 | 21.08877 | -0.3123 | 11.31696 |
May | 508.00000 | 22.57310 | 24.48710 | -1.0761 | 33.03814 |
June | 496.00000 | 23.73308 | 31.80617 | -0.5131 | 14.85538 |
July | 497.00000 | 24.16441 | 34.66736 | -0.2950 | 9.79355 |
August | 514.00000 | 23.81421 | 30.81317 | -0.4800 | 13.41518 |
September | 485.00000 | 22.95084 | 32.63217 | -0.8764 | 27.31123 |
October | 502.00000 | 21.35685 | 24.79090 | -0.3955 | 10.87616 |
November | 489.00000 | 20.30915 | 18.98745 | -0.7621 | 19.82751 |
December | 497.00000 | 19.88007 | 14.56901 | -0.9732 | 27.56004 |
Annual Sum or Average | 5943.00000 | 21.78867 | 23.16975 | -0.6823 | 19.73351 |
Minimum of Months | 454.00000 | 19.82268 | 11.98107 | -1.0761 | 9.79355 |
Maximum of Months | 514.00000 | 24.16441 | 34.66736 | -0.2950 | 33.03814 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33887 | 11.69032 | -0.8491 | 24.44875 |
February | 454.00000 | 21.19256 | 14.25556 | -0.5481 | 17.30665 |
March | 514.00000 | 21.36910 | 16.11978 | -0.4584 | 14.96891 |
April | 485.00000 | 21.95074 | 20.93084 | -0.2598 | 11.42672 |
May | 508.00000 | 22.56228 | 24.58045 | -1.1027 | 34.70852 |
June | 496.00000 | 23.43822 | 32.51958 | -0.6722 | 18.73357 |
July | 497.00000 | 23.94691 | 35.23608 | -0.4291 | 11.92818 |
August | 514.00000 | 23.80059 | 30.89434 | -0.4967 | 14.16090 |
September | 485.00000 | 23.29514 | 31.94448 | -0.7194 | 23.83454 |
October | 502.00000 | 22.30140 | 23.47795 | -0.1316 | 10.42757 |
November | 489.00000 | 21.32569 | 17.99184 | -0.4698 | 14.77043 |
December | 497.00000 | 20.44055 | 14.17324 | -0.7745 | 22.44491 |
Annual Sum or Average | 5943.00000 | 22.17132 | 22.86847 | -0.5769 | 18.28530 |
Minimum of Months | 454.00000 | 20.33887 | 11.69032 | -1.1027 | 10.42757 |
Maximum of Months | 514.00000 | 23.94691 | 35.23608 | -0.1316 | 34.70852 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87402 | 11.85611 | -1.0091 | 28.94655 |
February | 454.00000 | 20.40127 | 14.75463 | -0.7800 | 20.88740 |
March | 514.00000 | 20.79352 | 16.50185 | -0.6204 | 16.32561 |
April | 485.00000 | 21.61106 | 21.20115 | -0.3302 | 10.93222 |
May | 508.00000 | 22.49667 | 24.56518 | -1.0856 | 34.58652 |
June | 496.00000 | 23.37985 | 32.60288 | -0.6377 | 18.42760 |
July | 497.00000 | 23.86768 | 35.43630 | -0.4111 | 12.07362 |
August | 514.00000 | 23.59879 | 31.30789 | -0.5598 | 15.64472 |
September | 485.00000 | 22.64971 | 33.03980 | -0.9622 | 31.01355 |
October | 502.00000 | 21.38862 | 24.61306 | -0.3786 | 10.74183 |
November | 489.00000 | 20.53248 | 18.64971 | -0.6889 | 17.91495 |
December | 497.00000 | 19.99197 | 14.37504 | -0.9173 | 25.50254 |
Annual Sum or Average | 5943.00000 | 21.72699 | 23.29014 | -0.6981 | 20.24713 |
Minimum of Months | 454.00000 | 19.87402 | 11.85611 | -1.0856 | 10.74183 |
Maximum of Months | 514.00000 | 23.86768 | 35.43630 | -0.3302 | 34.58652 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 99053850.16 | 2895.00 | 13-JAN-05:20 | 9.52 | 0.412465E+09 | 0.00 | 0.511519E+09 | 0.05 | 4.17 | 03-JAN-06:50 | 0.00 | 0.00 |
February | 0.128583E+10 | 65060.76 | 27-FEB-15:30 | 23.68 | 0.693541E+10 | 0.00 | 0.822123E+10 | 0.16 | 6.39 | 27-FEB-15:30 | 0.00 | 0.00 |
March | 0.267485E+09 | 18487.76 | 14-MAR-13:30 | 19.95 | 0.111353E+10 | 0.00 | 0.138102E+10 | 0.11 | 4.17 | 15-MAR-05:30 | 0.00 | 0.00 |
April | 0.111077E+11 | 86499.01 | 07-APR-12:40 | 99.22 | 0.607392E+11 | 0.00 | 0.718469E+11 | 0.66 | 7.01 | 07-APR-12:40 | 0.00 | 0.00 |
May | 0.302983E+11 | 100697.89 | 19-MAY-15:30 | 187.31 | 0.179619E+12 | 0.00 | 0.209917E+12 | 1.34 | 7.23 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.749624E+11 | 114923.91 | 29-JUN-14:50 | 368.64 | 0.472897E+12 | 0.00 | 0.547859E+12 | 2.93 | 7.33 | 29-JUN-14:50 | 0.00 | 0.00 |
July | 0.113914E+12 | 137064.83 | 17-JUL-15:40 | 505.12 | 0.747905E+12 | 0.00 | 0.861819E+12 | 4.07 | 7.36 | 25-JUL-15:50 | 0.00 | 0.00 |
August | 0.100072E+12 | 138784.57 | 07-AUG-15:30 | 493.54 | 0.648925E+12 | 0.00 | 0.748997E+12 | 3.83 | 7.36 | 10-AUG-15:20 | 0.00 | 0.00 |
September | 0.550771E+11 | 163680.49 | 07-SEP-14:50 | 283.48 | 0.343351E+12 | 0.00 | 0.398428E+12 | 2.23 | 7.28 | 01-SEP-16:00 | 0.00 | 0.00 |
October | 0.167268E+11 | 87767.38 | 18-OCT-14:00 | 129.79 | 0.955486E+11 | 0.00 | 0.112275E+12 | 0.87 | 7.03 | 16-OCT-12:40 | 0.00 | 0.00 |
November | 0.174623E+10 | 44217.06 | 17-NOV-17:00 | 41.58 | 0.724393E+10 | 0.00 | 0.899016E+10 | 0.24 | 4.18 | 13-NOV-05:00 | 0.00 | 0.00 |
December | 85777324.05 | 2898.10 | 04-DEC-04:46 | 8.24 | 0.357184E+09 | 0.00 | 0.442961E+09 | 0.05 | 4.17 | 08-DEC-06:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.405642E+12 | 2170.07 | 0.256505E+13 | 0.00 | 0.297069E+13 | 1.39 | 0.00 | 0.00 | ||||
Minimum of Months | 85777324.05 | 2895.00 | 8.24 | 0.357184E+09 | 0.00 | 0.442961E+09 | 0.05 | 4.17 | 0.00 | 0.00 | ||
Maximum of Months | 0.113914E+12 | 163680.49 | 505.12 | 0.747905E+12 | 0.00 | 0.861819E+12 | 4.07 | 7.36 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.230976E+10 | 100697.89 | 19-MAY-15:30 | 7.17 | 0.163151E+11 | 0.00 | 0.186249E+11 | 0.07 | 7.23 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.239445E+11 | 114923.91 | 29-JUN-14:50 | 71.19 | 0.169805E+12 | 0.00 | 0.193749E+12 | 0.70 | 7.33 | 29-JUN-14:50 | 0.00 | 0.00 |
July | 0.499368E+11 | 137064.83 | 17-JUL-15:40 | 143.10 | 0.355980E+12 | 0.00 | 0.405916E+12 | 1.37 | 7.36 | 25-JUL-15:50 | 0.00 | 0.00 |
August | 0.413944E+11 | 138784.57 | 07-AUG-15:30 | 120.30 | 0.295370E+12 | 0.00 | 0.336765E+12 | 1.15 | 7.36 | 10-AUG-15:20 | 0.00 | 0.00 |
September | 0.121728E+11 | 163680.49 | 07-SEP-14:50 | 36.47 | 0.856368E+11 | 0.00 | 0.978096E+11 | 0.36 | 7.28 | 01-SEP-16:00 | 0.00 | 0.00 |
October | 0.109884E+10 | 87767.38 | 18-OCT-14:00 | 3.67 | 0.762557E+10 | 0.00 | 0.872441E+10 | 0.03 | 6.98 | 18-OCT-12:40 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.130857E+12 | 381.90 | 0.930732E+12 | 0.00 | 0.106159E+13 | 0.31 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.499368E+11 | 163680.49 | 143.10 | 0.355980E+12 | 0.00 | 0.405916E+12 | 1.37 | 7.36 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.852750E+10 | 744.00 | 7432.49 | 14-JAN-15:00 | 203101.59 | 13-JAN-16:30 | 21.70 | 18.33 | 15.27 |
February | 0.215271E+11 | 672.00 | 49248.27 | 20-FEB-15:40 | 388031.90 | 26-FEB-17:03 | 24.72 | 18.36 | 15.27 |
March | 0.388872E+11 | 744.00 | 49248.27 | 14-MAR-11:20 | 646691.25 | 31-MAR-24:00 | 27.64 | 18.34 | 15.27 |
April | 0.830388E+11 | 720.00 | 49248.27 | 01-APR-11:00 | 704416.63 | 16-APR-18:02 | 31.47 | 19.19 | 15.27 |
May | 0.529467E+11 | 744.00 | 49248.27 | 02-MAY-10:20 | 365843.25 | 31-MAY-24:00 | 23.16 | 19.26 | 15.27 |
June | 0.103297E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 527592.67 | 30-JUN-23:23 | 29.08 | 22.14 | 15.27 |
July | 0.127795E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 685546.55 | 31-JUL-23:53 | 36.33 | 26.39 | 15.27 |
August | 0.129383E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 758305.36 | 05-AUG-19:32 | 39.15 | 26.45 | 15.27 |
September | 0.754299E+11 | 720.00 | 49248.27 | 01-SEP-00:02 | 354011.72 | 30-SEP-24:00 | 24.70 | 20.68 | 15.27 |
October | 0.612386E+11 | 744.00 | 49248.27 | 02-OCT-13:20 | 498866.79 | 31-OCT-24:00 | 25.60 | 18.89 | 15.27 |
November | 0.527401E+11 | 720.00 | 49248.27 | 01-NOV-10:55 | 528948.10 | 03-NOV-16:00 | 27.83 | 18.44 | 15.27 |
December | 0.425046E+11 | 744.00 | 49248.27 | 05-DEC-12:00 | 664886.19 | 06-DEC-16:10 | 30.31 | 18.34 | 15.27 |
Annual Sum or Average | 0.797316E+12 | 8760.00 | 28.51 | 20.42 | 15.27 | ||||
Minimum of Months | 0.852750E+10 | 672.00 | 7432.49 | 203101.59 | 21.70 | 18.33 | 15.27 | ||
Maximum of Months | 0.129383E+12 | 744.00 | 49248.27 | 758305.36 | 39.15 | 26.45 | 15.27 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 191173.26 | 25-JAN-05:42 | 21.07 | 21.07 | 0.09 |
February | 941504.01 | 4.42 | 115.63 | 27-FEB-15:30 | 495057.03 | 27-FEB-15:30 | 21.12 | 21.10 | 0.77 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 191627.80 | 01-MAR-07:00 | 20.94 | 20.94 | 0.24 |
April | 96409501.18 | 51.90 | 4316.63 | 06-APR-16:00 | 932905.12 | 06-APR-16:00 | 21.09 | 20.96 | 5.46 |
May | 0.856993E+09 | 136.62 | 17096.89 | 19-MAY-14:00 | 1140795.38 | 19-MAY-14:40 | 21.58 | 21.20 | 12.11 |
June | 0.508526E+10 | 308.94 | 17096.89 | 06-JUN-14:30 | 1149349.02 | 29-JUN-10:30 | 22.26 | 21.19 | 26.65 |
July | 0.100561E+11 | 429.86 | 17096.89 | 01-JUL-13:10 | 1150417.08 | 26-JUL-09:10 | 22.81 | 21.18 | 36.03 |
August | 0.687636E+10 | 379.01 | 17096.89 | 05-AUG-11:30 | 1148781.70 | 04-AUG-12:20 | 22.54 | 21.10 | 33.06 |
September | 0.368884E+10 | 232.48 | 17096.89 | 02-SEP-10:20 | 1281217.20 | 07-SEP-15:00 | 22.01 | 21.24 | 20.52 |
October | 0.256790E+09 | 72.24 | 5085.01 | 18-OCT-15:00 | 988793.45 | 18-OCT-12:20 | 21.29 | 21.08 | 7.53 |
November | 466860.52 | 8.33 | 38.12 | 17-NOV-17:00 | 240598.81 | 17-NOV-17:00 | 20.99 | 20.97 | 1.39 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 191554.18 | 20-DEC-07:00 | 21.00 | 21.00 | 0.09 |
Annual Sum or Average | 0.269181E+11 | 1623.81 | 21.56 | 21.09 | 12.07 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 191173.26 | 20.94 | 20.94 | 0.09 | ||
Maximum of Months | 0.100561E+11 | 429.86 | 17096.89 | 1281217.20 | 22.81 | 21.24 | 36.03 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.07 | 21.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.12 | 21.12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.94 | 20.94 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.09 | 21.09 | 0.00 |
May | 0.213744E+09 | 5.50 | 17096.89 | 19-MAY-14:00 | 1140795.38 | 19-MAY-14:40 | 21.58 | 21.55 | 0.41 |
June | 0.236423E+10 | 55.67 | 17096.89 | 06-JUN-14:30 | 1149349.02 | 29-JUN-10:30 | 22.26 | 21.94 | 4.28 |
July | 0.557953E+10 | 120.33 | 17096.89 | 10-JUL-15:00 | 1150417.08 | 26-JUL-09:10 | 22.81 | 22.13 | 8.94 |
August | 0.390911E+10 | 97.50 | 17096.89 | 05-AUG-12:20 | 1148781.70 | 04-AUG-12:20 | 22.54 | 21.99 | 7.25 |
September | 0.152623E+10 | 31.17 | 17096.89 | 02-SEP-10:20 | 1281217.20 | 07-SEP-15:00 | 22.01 | 21.82 | 2.39 |
October | 34719445.08 | 2.00 | 5085.01 | 18-OCT-15:00 | 988793.45 | 18-OCT-12:20 | 21.29 | 21.28 | 0.15 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.99 | 20.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 | 0.00 |
Annual Sum or Average | 0.136276E+11 | 312.16 | 21.56 | 21.41 | 1.97 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | ||
Maximum of Months | 0.557953E+10 | 120.33 | 17096.89 | 1281217.20 | 22.81 | 22.13 | 8.94 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.128569E+13 | 0.00 | 604.50 | 2527902.40 | 09-JAN-07:02 | 0.00 | 37.11 | 72.75 | 3.08 | 0.00 | 0.14 | 0.74 | 09-JAN-07:02 |
February | 0.733416E+12 | 0.00 | 463.71 | 2015123.65 | 01-FEB-07:03 | 0.00 | 33.25 | 65.98 | 1.73 | 0.00 | 0.09 | 0.59 | 01-FEB-07:03 |
March | 0.490776E+12 | 0.00 | 458.69 | 1911868.99 | 06-MAR-05:01 | 0.00 | 30.43 | 61.78 | 0.94 | 0.00 | 0.05 | 0.56 | 06-MAR-05:01 |
April | 0.165613E+12 | 0.00 | 279.77 | 1281219.27 | 29-APR-05:01 | 0.00 | 26.90 | 47.93 | 0.29 | 0.00 | 0.02 | 0.38 | 29-APR-05:01 |
May | 0.110376E+12 | 0.00 | 207.74 | 1451349.99 | 22-MAY-04:01 | 0.00 | 26.44 | 41.53 | 0.19 | 0.00 | 0.01 | 0.43 | 22-MAY-04:01 |
June | 0.835304E+10 | 0.00 | 53.58 | 342073.22 | 16-JUN-06:10 | 0.00 | 23.72 | 27.99 | 0.01 | 0.00 | 0.00 | 0.10 | 16-JUN-06:10 |
July | 0.187934E+09 | 0.00 | 5.88 | 56890.50 | 08-JUL-06:10 | 0.00 | 23.04 | 23.51 | 0.00 | 0.00 | 0.00 | 0.02 | 08-JUL-06:10 |
August | 0.254773E+10 | 0.00 | 29.18 | 151553.94 | 18-AUG-06:05 | 0.00 | 23.13 | 25.43 | 0.00 | 0.00 | 0.00 | 0.04 | 18-AUG-06:05 |
September | 0.374813E+11 | 0.00 | 129.38 | 740681.87 | 19-SEP-05:03 | 0.00 | 24.24 | 34.38 | 0.06 | 0.00 | 0.00 | 0.22 | 19-SEP-05:03 |
October | 0.128495E+12 | 0.00 | 270.54 | 1275256.03 | 11-OCT-05:01 | 0.00 | 25.71 | 45.72 | 0.22 | 0.00 | 0.01 | 0.37 | 11-OCT-05:01 |
November | 0.388385E+12 | 0.00 | 432.20 | 1661552.86 | 27-NOV-06:01 | 0.00 | 29.02 | 60.31 | 0.74 | 0.00 | 0.04 | 0.49 | 27-NOV-06:01 |
December | 0.885195E+12 | 0.00 | 566.81 | 2057964.46 | 29-DEC-07:03 | 0.00 | 34.19 | 70.20 | 1.89 | 0.00 | 0.10 | 0.60 | 29-DEC-07:03 |
Annual Sum or Average | 0.423652E+13 | 0.00 | 3501.98 | 0.00 | 28.08 | 48.04 | 0.76 | 0.00 | 0.04 | ||||
Minimum of Months | 0.187934E+09 | 0.00 | 5.88 | 56890.50 | 0.00 | 23.04 | 23.51 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.128569E+13 | 0.00 | 604.50 | 2527902.40 | 0.00 | 37.11 | 72.75 | 3.08 | 0.00 | 0.14 | 0.74 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.72 | 24.72 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.64 | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.47 | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 23.16 | 23.16 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.08 | 29.08 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.33 | 36.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 39.15 | 39.15 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 24.70 | 24.70 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.60 | 25.60 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.83 | 27.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.31 | 30.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 | 28.51 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 39.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.668222E+09 | 0.00 | 11.73 | 0.668222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44378.93 | 27-FEB-15:30 | 44378.93 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 47762575.90 | 0.00 | 4.24 | 47762575.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9966.38 | 14-MAR-13:30 | 9966.38 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.684875E+10 | 0.00 | 77.90 | 0.684875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86545.32 | 07-APR-14:00 | 86545.32 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.187044E+11 | 0.00 | 168.39 | 0.187044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117249.50 | 19-MAY-15:20 | 117249.50 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.621322E+11 | 0.00 | 349.79 | 0.620638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137820.64 | 29-JUN-14:50 | 137820.64 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.106594E+12 | 0.00 | 481.39 | 0.106443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164290.46 | 17-JUL-15:40 | 164290.46 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.982073E+11 | 0.00 | 471.61 | 0.982073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162762.80 | 07-AUG-15:20 | 162762.80 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.400732E+11 | 0.00 | 260.48 | 0.386793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201959.36 | 07-SEP-15:00 | 129958.33 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.108484E+11 | 0.00 | 111.98 | 0.108484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103923.85 | 18-OCT-15:50 | 103923.85 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.603942E+09 | 0.00 | 23.07 | 0.603942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19068.72 | 17-NOV-17:00 | 19068.72 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344728E+12 | 0.00 | 1960.59 | 0.343114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106594E+12 | 0.00 | 481.39 | 0.106443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 201959.36 | 164290.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12346.86 | 0.00 | 7.61 | 12346.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 02-JAN-05:24 | 3.72 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 |
February | 0.481262E+10 | 0.00 | 20.77 | 0.481262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317620.76 | 27-FEB-13:50 | 317620.76 | 27-FEB-13:50 | 0.00 | 0.00 | 0.00 |
March | 0.149095E+09 | 0.00 | 18.35 | 0.149095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45260.37 | 14-MAR-13:30 | 45260.37 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.487552E+11 | 0.00 | 89.23 | 0.487552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 668693.39 | 06-APR-16:00 | 668693.39 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.159328E+12 | 0.00 | 172.60 | 0.159328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1124859.96 | 19-MAY-15:20 | 1124859.96 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.531036E+12 | 0.00 | 328.73 | 0.530444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1312498.82 | 29-JUN-14:50 | 1312498.82 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.891038E+12 | 0.00 | 418.93 | 0.890185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1518576.57 | 17-JUL-15:40 | 1518576.57 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.771346E+12 | 0.00 | 391.58 | 0.771346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1410966.27 | 10-AUG-15:40 | 1410966.27 | 10-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.351058E+12 | 0.00 | 255.67 | 0.338388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1874627.15 | 07-SEP-15:00 | 1194643.76 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.856662E+11 | 0.00 | 115.95 | 0.856662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 885272.71 | 18-OCT-15:10 | 885272.71 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.429216E+10 | 0.00 | 37.63 | 0.429216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152718.07 | 03-NOV-14:00 | 152718.07 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 18227.04 | 0.00 | 6.60 | 18227.04 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 | 14-DEC-05:01 | 4.72 | 14-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284748E+13 | 0.00 | 1863.66 | 0.283337E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12346.86 | 0.00 | 6.60 | 12346.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 3.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.891038E+12 | 0.00 | 418.93 | 0.890185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1874627.15 | 1518576.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2274.08 | 0.00 | 1.91 | 2274.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 11-JAN-06:08 | 0.71 | 11-JAN-06:08 | 0.00 | 0.00 | 0.00 |
February | 0.324425E+09 | 0.00 | 11.96 | 0.324425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21826.99 | 27-FEB-15:30 | 21826.99 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 2489376.22 | 0.00 | 1.85 | 2489376.22 | 0.00 | 0.00 | 0.00 | 0.00 | 696.31 | 14-MAR-14:00 | 696.31 | 14-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.450198E+10 | 0.00 | 65.60 | 0.450198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66876.09 | 06-APR-16:00 | 66876.09 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.163879E+11 | 0.00 | 153.52 | 0.163879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132937.35 | 19-MAY-15:30 | 132937.35 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.578964E+11 | 0.00 | 319.84 | 0.578252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155101.84 | 29-JUN-15:00 | 155101.84 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.981358E+11 | 0.00 | 418.35 | 0.980708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185803.12 | 17-JUL-15:30 | 185803.12 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.826728E+11 | 0.00 | 380.57 | 0.826728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167623.81 | 07-AUG-15:50 | 167623.81 | 07-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.357250E+11 | 0.00 | 242.52 | 0.344700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191018.01 | 07-SEP-15:20 | 136230.45 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.731607E+10 | 0.00 | 94.02 | 0.731607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90887.39 | 18-OCT-15:00 | 90887.39 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.304082E+09 | 0.00 | 17.37 | 0.304082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11133.88 | 17-NOV-17:00 | 11133.88 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 10175.89 | 0.00 | 1.64 | 10175.89 | 0.00 | 0.00 | 0.00 | 0.00 | 69.91 | 04-DEC-04:46 | 69.91 | 04-DEC-04:46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303267E+12 | 0.00 | 1709.15 | 0.301876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2274.08 | 0.00 | 1.64 | 2274.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.981358E+11 | 0.00 | 418.35 | 0.980708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191018.01 | 185803.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.282783E+09 | 0.00 | 5.17 | 0.282783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24820.80 | 27-FEB-15:00 | 24820.80 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 13603.64 | 0.00 | 0.17 | 13603.64 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 07-MAR-19:50 | 22.67 | 07-MAR-19:50 | 0.00 | 0.00 | 0.00 |
April | 0.245389E+10 | 0.00 | 38.46 | 0.245389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50035.33 | 07-APR-14:00 | 50035.33 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.921493E+10 | 0.00 | 107.02 | 0.921493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79182.78 | 29-MAY-15:02 | 79182.78 | 29-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.318869E+11 | 0.00 | 234.94 | 0.318637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68420.25 | 26-JUN-11:00 | 68420.25 | 26-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.540153E+11 | 0.00 | 324.91 | 0.539751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119516.51 | 19-JUL-03:02 | 89279.45 | 25-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.502708E+11 | 0.00 | 320.86 | 0.502698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105211.96 | 06-AUG-15:54 | 105211.96 | 06-AUG-15:54 | 0.00 | 0.00 | 0.00 |
September | 0.210305E+11 | 0.00 | 186.58 | 0.206158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109241.30 | 04-SEP-08:62 | 109241.30 | 04-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.595290E+10 | 0.00 | 62.91 | 0.595290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60329.65 | 18-OCT-14:00 | 60329.65 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 91667054.30 | 0.00 | 5.56 | 91667054.30 | 0.00 | 0.00 | 0.00 | 0.00 | 28477.05 | 17-NOV-06:03 | 28477.05 | 17-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175200E+12 | 0.00 | 1286.57 | 0.174721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.540153E+11 | 0.00 | 324.91 | 0.539751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119516.51 | 109241.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.361909E+12 | 0.918933E+11 | 744.00 | 0.328250E+12 | 0.336590E+11 | 0.00 | 0.36 | 03-JAN-22:02 | 0.30 | 09-JAN-07:02 | 142962.30 | 18-JAN-22:01 | 129776.17 | 02-JAN-22:03 | 13975.31 | 18-JAN-22:01 | 35976.58 | 03-JAN-22:02 | 0.00 |
February | 0.575784E+12 | 0.138535E+12 | 672.00 | 0.522013E+12 | 0.537706E+11 | 0.00 | 0.59 | 27-FEB-16:00 | 0.54 | 01-FEB-07:07 | 245399.65 | 27-FEB-22:03 | 222167.03 | 28-FEB-22:03 | 23908.25 | 05-FEB-00:52 | 66479.59 | 27-FEB-16:00 | 0.00 |
March | 0.910685E+12 | 0.209937E+12 | 744.00 | 0.827825E+12 | 0.828603E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.76 | 06-MAR-07:07 | 440877.89 | 31-MAR-24:00 | 400397.01 | 31-MAR-24:00 | 40480.88 | 31-MAR-24:00 | 97771.73 | 31-MAR-24:00 | 0.00 |
April | 0.114524E+13 | 0.261602E+12 | 720.00 | 0.104328E+13 | 0.101963E+12 | 0.00 | 1.00 | 06-APR-09:50 | 0.39 | 30-APR-23:55 | 449754.83 | 24-APR-21:02 | 407582.13 | 06-APR-22:55 | 44491.16 | 21-APR-16:00 | 132384.94 | 07-APR-14:00 | 0.00 |
May | 0.375786E+12 | 0.982122E+11 | 744.00 | 0.342806E+12 | 0.329792E+11 | 0.00 | 0.58 | 31-MAY-23:40 | 0.33 | 08-MAY-06:10 | 238081.21 | 31-MAY-24:00 | 217599.45 | 31-MAY-24:00 | 20481.75 | 31-MAY-24:00 | 59590.13 | 31-MAY-23:20 | 0.00 |
June | 0.620356E+12 | 0.169495E+12 | 720.00 | 0.573415E+12 | 0.469411E+11 | 0.00 | 0.80 | 30-JUN-23:12 | 0.57 | 01-JUN-06:10 | 330267.18 | 30-JUN-23:02 | 309528.14 | 30-JUN-24:00 | 23537.06 | 01-JUN-19:00 | 95880.63 | 30-JUN-23:12 | 0.00 |
July | 0.894926E+12 | 0.267645E+12 | 744.00 | 0.842158E+12 | 0.527680E+11 | 0.00 | 1.00 | 31-JUL-23:02 | 0.78 | 08-JUL-06:10 | 427134.26 | 31-JUL-24:00 | 400795.34 | 31-JUL-23:55 | 34342.70 | 05-JUL-09:00 | 149972.76 | 17-JUL-16:00 | 0.00 |
August | 0.116139E+13 | 0.326789E+12 | 744.00 | 0.108102E+13 | 0.803694E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.41 | 31-AUG-24:00 | 456799.34 | 04-AUG-00:25 | 412535.18 | 12-AUG-04:57 | 47258.71 | 01-AUG-21:00 | 167703.01 | 06-AUG-16:00 | 0.00 |
September | 0.366932E+12 | 0.100654E+12 | 720.00 | 0.336771E+12 | 0.301608E+11 | 0.00 | 0.57 | 30-SEP-24:00 | 0.34 | 18-SEP-07:00 | 238747.67 | 30-SEP-24:00 | 217327.62 | 30-SEP-24:00 | 21420.06 | 30-SEP-24:00 | 59151.55 | 02-SEP-17:00 | 0.00 |
October | 0.649209E+12 | 0.158745E+12 | 744.00 | 0.590738E+12 | 0.584707E+11 | 0.00 | 0.78 | 31-OCT-24:00 | 0.56 | 10-OCT-06:10 | 340967.62 | 31-OCT-24:00 | 309926.37 | 31-OCT-24:00 | 31041.25 | 31-OCT-24:00 | 79056.67 | 18-OCT-15:00 | 0.00 |
November | 0.889825E+12 | 0.205428E+12 | 720.00 | 0.806765E+12 | 0.830605E+11 | 0.00 | 0.81 | 17-NOV-17:00 | 0.77 | 27-NOV-07:10 | 349084.27 | 06-NOV-22:03 | 315595.10 | 06-NOV-22:03 | 34458.66 | 03-NOV-08:00 | 89793.90 | 17-NOV-17:00 | 0.00 |
December | 0.118270E+13 | 0.262986E+12 | 744.00 | 0.107455E+13 | 0.108156E+12 | 0.00 | 0.99 | 07-DEC-24:00 | 0.96 | 30-DEC-07:10 | 448640.98 | 07-DEC-24:00 | 407066.75 | 07-DEC-22:03 | 43518.89 | 16-DEC-17:00 | 104955.46 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.913475E+13 | 0.229192E+13 | 8760.00 | 0.836959E+13 | 0.765160E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.361909E+12 | 0.918933E+11 | 672.00 | 0.328250E+12 | 0.301608E+11 | 0.00 | 0.36 | 0.30 | 142962.30 | 129776.17 | 13975.31 | 35976.58 | 0.00 | ||||||
Maximum of Months | 0.118270E+13 | 0.326789E+12 | 744.00 | 0.108102E+13 | 0.108156E+12 | 0.00 | 1.00 | 0.96 | 456799.34 | 412535.18 | 47258.71 | 167703.01 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.289943E+10 | 0.833422E+09 | 730.24 | 0.289911E+10 | 320542.28 | 0.00 | 0.27 | 13-JAN-16:20 | 0.00 | 07-JAN-23:35 | 2188.32 | 13-JAN-16:20 | 2188.32 | 13-JAN-16:20 | 12.58 | 02-JAN-07:10 | 572.95 | 13-JAN-16:20 | 0.00 |
February | 0.819962E+10 | 0.215724E+10 | 672.00 | 0.819962E+10 | -0.0 | 0.00 | 0.58 | 26-FEB-17:03 | 0.27 | 01-FEB-07:03 | 4834.21 | 26-FEB-17:14 | 4834.21 | 26-FEB-17:14 | 0.00 | 06-FEB-18:10 | 1270.74 | 26-FEB-16:53 | 0.00 |
March | 0.148985E+11 | 0.368919E+10 | 744.00 | 0.148985E+11 | 0.00 | 0.00 | 0.82 | 31-MAR-24:00 | 0.53 | 06-MAR-07:03 | 7467.03 | 31-MAR-24:00 | 7467.03 | 31-MAR-24:00 | 0.00 | 15-MAR-18:10 | 1757.71 | 31-MAR-24:00 | 0.00 |
April | 0.199971E+11 | 0.481875E+10 | 720.00 | 0.199896E+11 | 7462423.50 | 0.00 | 1.00 | 16-APR-17:02 | 0.30 | 30-APR-23:55 | 8873.66 | 22-APR-18:10 | 8873.66 | 22-APR-18:10 | 128.66 | 17-APR-16:10 | 2690.34 | 07-APR-14:00 | 0.00 |
May | 0.559262E+10 | 0.152687E+10 | 744.00 | 0.557105E+10 | 21573746.09 | 0.00 | 0.48 | 31-MAY-24:00 | 0.14 | 08-MAY-06:40 | 4139.15 | 31-MAY-24:00 | 4139.15 | 31-MAY-24:00 | 138.95 | 30-MAY-09:10 | 1072.47 | 31-MAY-23:30 | 0.00 |
June | 0.108705E+11 | 0.303130E+10 | 720.00 | 0.107904E+11 | 80149531.40 | 0.00 | 0.68 | 30-JUN-23:12 | 0.39 | 17-JUN-06:40 | 5991.51 | 30-JUN-24:00 | 5991.51 | 30-JUN-24:00 | 305.37 | 06-JUN-16:50 | 1871.40 | 29-JUN-15:00 | 0.00 |
July | 0.165395E+11 | 0.501897E+10 | 744.00 | 0.164503E+11 | 89209286.81 | 0.00 | 0.89 | 16-JUL-18:45 | 0.62 | 08-JUL-06:20 | 7871.64 | 31-JUL-23:35 | 7871.64 | 31-JUL-23:35 | 313.07 | 03-JUL-17:00 | 3051.04 | 17-JUL-16:00 | 0.00 |
August | 0.215283E+11 | 0.632577E+10 | 744.00 | 0.214652E+11 | 63083612.30 | 0.00 | 1.00 | 03-AUG-18:10 | 0.31 | 31-AUG-24:00 | 8850.50 | 05-AUG-20:12 | 8850.50 | 05-AUG-20:12 | 368.35 | 22-AUG-16:00 | 3594.90 | 06-AUG-16:00 | 0.00 |
September | 0.567817E+10 | 0.160752E+10 | 720.00 | 0.559615E+10 | 82010846.27 | 0.00 | 0.46 | 30-SEP-24:00 | 0.16 | 19-SEP-07:00 | 3948.60 | 30-SEP-24:00 | 3948.60 | 30-SEP-24:00 | 344.91 | 07-SEP-15:30 | 1349.60 | 04-SEP-17:21 | 0.00 |
October | 0.105001E+11 | 0.266959E+10 | 744.00 | 0.104895E+11 | 10523962.02 | 0.00 | 0.65 | 31-OCT-24:00 | 0.36 | 10-OCT-06:40 | 5598.15 | 31-OCT-24:00 | 5598.15 | 31-OCT-24:00 | 111.43 | 25-OCT-11:00 | 1565.40 | 15-OCT-16:43 | 0.00 |
November | 0.145875E+11 | 0.358023E+10 | 720.00 | 0.145858E+11 | 1686766.53 | 0.00 | 0.72 | 12-NOV-16:13 | 0.54 | 27-NOV-07:10 | 6496.40 | 03-NOV-16:00 | 6461.92 | 12-NOV-16:17 | 83.70 | 08-NOV-15:20 | 1649.26 | 17-NOV-16:50 | 0.00 |
December | 0.194587E+11 | 0.471474E+10 | 744.00 | 0.194584E+11 | 217433.99 | 0.00 | 0.91 | 10-DEC-16:05 | 0.74 | 29-DEC-07:03 | 8260.01 | 10-DEC-16:10 | 8260.01 | 10-DEC-16:10 | 49.64 | 19-DEC-17:05 | 1977.14 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.150750E+12 | 0.399736E+11 | 8746.24 | 0.150394E+12 | 0.356238E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.289943E+10 | 0.833422E+09 | 672.00 | 0.289911E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 2188.32 | 2188.32 | 0.00 | 572.95 | 0.00 | ||||||
Maximum of Months | 0.215283E+11 | 0.632577E+10 | 744.00 | 0.214652E+11 | 89209286.81 | 0.00 | 1.00 | 0.74 | 8873.66 | 8873.66 | 368.35 | 3594.90 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.830672E+10 | 0.260027E+10 | 481.53 | 0.830364E+10 | 3080852.31 | 0.00 | 0.23 | 13-JAN-16:30 | 0.00 | 01-JAN-04:13 | 18012.41 | 13-JAN-16:30 | 18012.41 | 13-JAN-16:30 | 136.33 | 01-JAN-15:45 | 4771.78 | 13-JAN-16:30 | 0.00 |
February | 0.591940E+11 | 0.159276E+11 | 672.00 | 0.591940E+11 | -0.0 | 0.00 | 0.52 | 26-FEB-17:23 | 0.13 | 06-FEB-04:01 | 42648.69 | 28-FEB-17:00 | 42648.69 | 28-FEB-17:00 | 0.00 | 23-FEB-16:20 | 11465.36 | 27-FEB-16:00 | 0.00 |
March | 0.124458E+12 | 0.312592E+11 | 744.00 | 0.124458E+12 | -0.0 | 0.00 | 0.76 | 31-MAR-23:30 | 0.37 | 06-MAR-07:03 | 65300.66 | 31-MAR-23:30 | 65300.66 | 31-MAR-23:30 | 0.00 | 26-MAR-09:45 | 15558.23 | 31-MAR-23:30 | 0.00 |
April | 0.179736E+12 | 0.437101E+11 | 720.00 | 0.179659E+12 | 76457861.13 | 0.00 | 1.00 | 16-APR-17:42 | 0.14 | 30-APR-24:00 | 82415.87 | 25-APR-18:00 | 82415.87 | 25-APR-18:00 | 1282.90 | 17-APR-16:10 | 25471.81 | 07-APR-14:00 | 0.00 |
May | 0.453476E+11 | 0.125618E+11 | 744.00 | 0.451359E+11 | 0.211737E+09 | 0.00 | 0.48 | 31-MAY-24:00 | 0.03 | 08-MAY-06:10 | 39148.00 | 31-MAY-24:00 | 39148.00 | 31-MAY-24:00 | 1329.36 | 30-MAY-09:10 | 10167.55 | 31-MAY-23:30 | 0.00 |
June | 0.100138E+12 | 0.280845E+11 | 720.00 | 0.993392E+11 | 0.798828E+09 | 0.00 | 0.69 | 30-JUN-23:12 | 0.34 | 17-JUN-06:10 | 58470.88 | 30-JUN-24:00 | 58470.88 | 30-JUN-24:00 | 2991.54 | 06-JUN-16:50 | 17822.99 | 29-JUN-15:00 | 0.00 |
July | 0.156279E+12 | 0.475346E+11 | 744.00 | 0.155387E+12 | 0.892314E+09 | 0.00 | 0.89 | 31-JUL-23:12 | 0.59 | 08-JUL-06:30 | 76721.69 | 31-JUL-23:55 | 76721.69 | 31-JUL-23:55 | 3073.67 | 03-JUL-17:00 | 29046.84 | 17-JUL-16:00 | 0.00 |
August | 0.202432E+12 | 0.596950E+11 | 744.00 | 0.201800E+12 | 0.632379E+09 | 0.00 | 1.00 | 03-AUG-18:20 | 0.27 | 31-AUG-24:00 | 84091.67 | 03-AUG-19:00 | 84091.67 | 03-AUG-19:00 | 3616.71 | 22-AUG-16:00 | 34390.74 | 06-AUG-16:00 | 0.00 |
September | 0.479241E+11 | 0.137675E+11 | 720.00 | 0.471217E+11 | 0.802370E+09 | 0.00 | 0.43 | 04-SEP-17:31 | 0.10 | 19-SEP-06:10 | 34913.64 | 30-SEP-23:40 | 34913.64 | 30-SEP-23:40 | 3444.63 | 07-SEP-15:30 | 12696.48 | 04-SEP-17:21 | 0.00 |
October | 0.877932E+11 | 0.226271E+11 | 744.00 | 0.876879E+11 | 0.105298E+09 | 0.00 | 0.59 | 31-OCT-24:00 | 0.25 | 10-OCT-06:10 | 47671.08 | 31-OCT-24:00 | 47671.08 | 31-OCT-24:00 | 1092.09 | 25-OCT-11:00 | 14495.09 | 18-OCT-16:00 | 0.00 |
November | 0.120788E+12 | 0.301158E+11 | 720.00 | 0.120770E+12 | 17602132.04 | 0.00 | 0.69 | 03-NOV-16:00 | 0.37 | 27-NOV-07:10 | 59983.80 | 03-NOV-16:00 | 59435.75 | 03-NOV-16:00 | 833.91 | 08-NOV-15:20 | 15242.55 | 17-NOV-17:00 | 0.00 |
December | 0.158815E+12 | 0.392489E+11 | 744.00 | 0.158812E+12 | 3034038.54 | 0.00 | 0.83 | 12-DEC-16:00 | 0.56 | 31-DEC-23:55 | 74768.39 | 06-DEC-16:10 | 74485.33 | 06-DEC-16:10 | 527.58 | 19-DEC-17:05 | 17037.18 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.129121E+13 | 0.347133E+12 | 8497.53 | 0.128767E+13 | 0.354310E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.830672E+10 | 0.260027E+10 | 481.53 | 0.830364E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 18012.41 | 18012.41 | 0.00 | 4771.78 | 0.00 | ||||||
Maximum of Months | 0.202432E+12 | 0.596950E+11 | 744.00 | 0.201800E+12 | 0.892314E+09 | 0.00 | 1.00 | 0.59 | 84091.67 | 84091.67 | 3616.71 | 34390.74 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.230045E+09 | 74414483.78 | 168.13 | 0.230045E+09 | -0.0 | 0.00 | 0.22 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1717.40 | 13-JAN-16:30 | 1717.40 | 13-JAN-16:30 | 0.00 | 14-JAN-17:10 | 457.59 | 13-JAN-16:30 | 0.00 |
February | 0.427029E+10 | 0.117250E+10 | 649.96 | 0.427029E+10 | -0.0 | 0.00 | 0.50 | 28-FEB-17:00 | 0.00 | 04-FEB-02:42 | 4220.91 | 28-FEB-17:00 | 4220.91 | 28-FEB-17:00 | 0.00 | 07-FEB-15:50 | 1127.87 | 27-FEB-16:00 | 0.00 |
March | 0.108040E+11 | 0.275025E+10 | 744.00 | 0.108040E+11 | -0.0 | 0.00 | 0.72 | 28-MAR-17:50 | 0.19 | 06-MAR-04:02 | 6164.11 | 28-MAR-17:50 | 6164.11 | 28-MAR-17:50 | 0.00 | 10-MAR-05:20 | 1493.82 | 28-MAR-17:50 | 0.00 |
April | 0.168079E+11 | 0.413369E+10 | 719.00 | 0.168004E+11 | 7519061.60 | 0.00 | 0.97 | 16-APR-17:51 | 0.00 | 30-APR-23:05 | 8308.89 | 25-APR-18:00 | 8308.89 | 25-APR-18:00 | 127.12 | 17-APR-16:10 | 2556.73 | 07-APR-14:00 | 0.00 |
May | 0.386146E+10 | 0.108238E+10 | 691.95 | 0.384062E+10 | 20836967.62 | 0.00 | 0.46 | 31-MAY-23:40 | 0.00 | 01-MAY-00:10 | 3843.15 | 31-MAY-24:00 | 3843.15 | 31-MAY-24:00 | 128.78 | 30-MAY-09:20 | 1003.49 | 31-MAY-23:20 | 0.00 |
June | 0.980741E+10 | 0.276982E+10 | 720.00 | 0.972772E+10 | 79691191.06 | 0.00 | 0.68 | 30-JUN-23:12 | 0.25 | 17-JUN-06:10 | 5857.38 | 30-JUN-24:00 | 5857.38 | 30-JUN-24:00 | 301.51 | 06-JUN-16:50 | 1821.31 | 29-JUN-15:00 | 0.00 |
July | 0.155838E+11 | 0.476269E+10 | 744.00 | 0.154948E+11 | 89067702.31 | 0.00 | 0.91 | 16-JUL-18:45 | 0.54 | 08-JUL-06:30 | 7631.69 | 31-JUL-23:55 | 7631.69 | 31-JUL-23:55 | 308.14 | 03-JUL-17:00 | 2972.71 | 17-JUL-16:00 | 0.00 |
August | 0.201183E+11 | 0.596379E+10 | 744.00 | 0.200552E+11 | 63090107.70 | 0.00 | 1.00 | 03-AUG-18:40 | 0.26 | 31-AUG-24:00 | 8557.07 | 05-AUG-19:57 | 8557.07 | 05-AUG-19:57 | 362.92 | 22-AUG-16:00 | 3501.49 | 06-AUG-16:00 | 0.00 |
September | 0.425735E+10 | 0.124689E+10 | 718.78 | 0.417828E+10 | 79068868.71 | 0.00 | 0.45 | 04-SEP-17:21 | 0.00 | 12-SEP-03:43 | 3403.05 | 04-SEP-17:32 | 3403.05 | 04-SEP-17:32 | 347.23 | 07-SEP-15:30 | 1378.96 | 04-SEP-17:21 | 0.00 |
October | 0.739448E+10 | 0.193847E+10 | 744.00 | 0.738418E+10 | 10298093.99 | 0.00 | 0.56 | 18-OCT-16:50 | 0.09 | 10-OCT-03:20 | 4565.94 | 18-OCT-16:50 | 4565.94 | 18-OCT-16:50 | 108.23 | 25-OCT-11:00 | 1460.81 | 18-OCT-16:00 | 0.00 |
November | 0.101922E+11 | 0.258459E+10 | 720.00 | 0.101905E+11 | 1713153.61 | 0.00 | 0.67 | 03-NOV-16:00 | 0.19 | 27-NOV-04:23 | 5935.38 | 03-NOV-16:00 | 5880.69 | 03-NOV-16:00 | 82.62 | 08-NOV-15:20 | 1502.47 | 17-NOV-16:50 | 0.00 |
December | 0.138238E+11 | 0.347260E+10 | 744.00 | 0.138235E+11 | 263218.83 | 0.00 | 0.81 | 06-DEC-16:10 | 0.40 | 31-DEC-23:55 | 7386.01 | 06-DEC-16:10 | 7359.70 | 06-DEC-16:10 | 49.97 | 19-DEC-17:05 | 1689.66 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.117151E+12 | 0.319521E+11 | 8107.81 | 0.116800E+12 | 0.351548E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.230045E+09 | 74414483.78 | 168.13 | 0.230045E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1717.40 | 1717.40 | 0.00 | 457.59 | 0.00 | ||||||
Maximum of Months | 0.201183E+11 | 0.596379E+10 | 744.00 | 0.200552E+11 | 89067702.31 | 0.00 | 1.00 | 0.54 | 8557.07 | 8557.07 | 362.92 | 3501.49 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.47 | 794.59 | 0.00 | 0.00 | 0.00 |
February | 127.65 | 0.00 | 127.65 | 15.34 | 599.63 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.97 | 489.05 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 115.20 | 351.27 | 0.00 | 0.00 | 0.00 |
May | 310.49 | 18.40 | 292.09 | 225.01 | 253.75 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.99 | 366.75 | 158.89 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.94 | 299.35 | 398.66 | 130.67 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.48 | 151.13 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.38 | 235.46 | 0.00 | 0.00 | 0.00 |
October | 144.59 | 0.00 | 144.59 | 58.23 | 361.27 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.43 | 523.54 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 709.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.33 | 395.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.99 | 398.66 | 794.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.47 | 794.59 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.33 | 599.63 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.96 | 489.05 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 115.19 | 351.27 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.01 | 253.75 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.74 | 158.89 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.65 | 130.67 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.48 | 151.13 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.37 | 235.46 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.22 | 361.27 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.43 | 523.54 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 709.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.32 | 395.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.65 | 794.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.47 | 794.59 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.33 | 599.63 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.97 | 489.05 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 115.20 | 351.27 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.01 | 253.75 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.74 | 158.89 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.66 | 130.67 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.48 | 151.13 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.37 | 235.46 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.22 | 361.27 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.43 | 523.54 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 709.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.33 | 395.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.66 | 794.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.47 | 794.59 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.33 | 599.63 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.96 | 489.05 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 115.19 | 351.27 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 225.01 | 253.75 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 366.74 | 158.89 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 398.65 | 130.67 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 288.48 | 151.13 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 167.37 | 235.46 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.22 | 361.27 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.43 | 523.54 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 709.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 143.32 | 395.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 398.65 | 794.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.47 | 794.55 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.33 | 599.61 | 0.00 | 0.00 | 0.00 |
March | 207.34 | 0.00 | 207.34 | 61.96 | 489.03 | 0.00 | 0.00 | 0.00 |
April | 236.41 | 1.38 | 235.04 | 115.19 | 351.25 | 0.00 | 0.00 | 0.00 |
May | 310.47 | 18.40 | 292.07 | 225.00 | 253.74 | 0.00 | 0.00 | 0.00 |
June | 361.52 | 41.55 | 319.97 | 366.73 | 158.89 | 0.00 | 0.00 | 0.00 |
July | 330.27 | 30.93 | 299.34 | 398.64 | 130.66 | 0.00 | 0.00 | 0.00 |
August | 264.65 | 7.09 | 257.56 | 288.46 | 151.12 | 0.00 | 0.00 | 0.00 |
September | 198.20 | 0.07 | 198.13 | 167.37 | 235.45 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 58.22 | 361.26 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.43 | 523.52 | 0.00 | 0.00 | 0.00 |
December | 75.80 | 0.00 | 75.80 | 0.46 | 709.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.21 | 8.33 | 195.88 | 143.32 | 395.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.80 | 0.00 | 75.80 | 0.46 | 130.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 41.55 | 319.97 | 398.64 | 794.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.59 | 805.10 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 263.74 | 602.05 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 389.31 | 497.61 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 594.79 | 357.85 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 707.92 | 278.65 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1058.15 | 176.05 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1198.54 | 138.70 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1017.87 | 155.03 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 651.39 | 240.60 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.36 | 365.15 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 173.72 | 513.67 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 90.91 | 705.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 555.69 | 402.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 90.91 | 138.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1198.54 | 805.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.59 | 805.10 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 263.74 | 602.05 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 389.31 | 497.61 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 594.79 | 357.85 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 707.92 | 278.65 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1058.15 | 176.05 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1198.54 | 138.70 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1017.87 | 155.03 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 651.39 | 240.60 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.36 | 365.15 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 173.72 | 513.67 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 90.91 | 705.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 555.69 | 402.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 90.91 | 138.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1198.54 | 805.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.65 | 105.75 | 124.91 | 118.58 | 805.09 | 0.00 | 0.00 | 0.00 |
February | 360.76 | 179.11 | 181.65 | 263.74 | 602.04 | 0.00 | 0.00 | 0.00 |
March | 485.08 | 200.71 | 284.37 | 389.30 | 497.60 | 0.00 | 0.00 | 0.00 |
April | 618.91 | 306.73 | 312.18 | 594.78 | 357.84 | 0.00 | 0.00 | 0.00 |
May | 683.67 | 304.19 | 379.48 | 707.90 | 278.65 | 0.00 | 0.00 | 0.00 |
June | 884.92 | 455.38 | 429.54 | 1058.13 | 176.05 | 0.00 | 0.00 | 0.00 |
July | 928.75 | 525.05 | 403.70 | 1198.52 | 138.70 | 0.00 | 0.00 | 0.00 |
August | 807.13 | 449.71 | 357.42 | 1017.85 | 155.02 | 0.00 | 0.00 | 0.00 |
September | 570.96 | 294.73 | 276.23 | 651.38 | 240.60 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 383.35 | 365.14 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 173.72 | 513.66 | 0.00 | 0.00 | 0.00 |
December | 191.48 | 82.24 | 109.24 | 90.91 | 705.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.88 | 269.87 | 267.02 | 555.68 | 402.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.48 | 82.24 | 109.24 | 90.91 | 138.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.75 | 525.05 | 429.54 | 1198.52 | 805.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.34 | 666.75 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.48 | 509.62 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 737.83 | 458.18 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 615.45 | 344.91 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 558.97 | 267.31 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 635.32 | 180.37 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.96 | 141.39 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 880.16 | 160.00 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.80 | 233.27 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 866.05 | 334.94 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 716.86 | 435.61 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 571.80 | 583.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.85 | 359.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 558.97 | 141.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 905.80 | 666.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.33 | 666.75 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.48 | 509.62 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 737.83 | 458.18 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 615.45 | 344.91 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 558.96 | 267.31 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 635.31 | 180.37 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.96 | 141.39 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 880.15 | 160.00 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.80 | 233.27 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 866.04 | 334.94 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 716.85 | 435.61 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 571.80 | 583.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.84 | 359.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 558.96 | 141.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 905.80 | 666.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.34 | 666.75 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.48 | 509.62 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 737.83 | 458.18 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 615.45 | 344.91 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 558.97 | 267.31 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 635.32 | 180.37 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.96 | 141.39 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 880.16 | 160.00 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.80 | 233.27 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 866.05 | 334.94 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 716.86 | 435.61 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 571.80 | 583.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.85 | 359.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 558.97 | 141.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 905.80 | 666.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.33 | 666.75 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.48 | 509.62 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 737.83 | 458.18 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 615.45 | 344.91 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 558.96 | 267.31 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 635.31 | 180.37 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 763.96 | 141.39 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 880.15 | 160.00 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 905.80 | 233.27 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 866.04 | 334.94 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 716.85 | 435.61 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 571.80 | 583.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 721.84 | 359.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 558.96 | 141.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 905.80 | 666.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.21 | 455.11 | 182.10 | 591.31 | 666.72 | 0.00 | 0.00 | 0.00 |
February | 811.48 | 583.64 | 227.83 | 828.45 | 509.60 | 0.00 | 0.00 | 0.00 |
March | 725.35 | 407.32 | 318.03 | 737.80 | 458.16 | 0.00 | 0.00 | 0.00 |
April | 583.06 | 278.88 | 304.18 | 615.42 | 344.90 | 0.00 | 0.00 | 0.00 |
May | 518.04 | 172.05 | 345.99 | 558.94 | 267.30 | 0.00 | 0.00 | 0.00 |
June | 514.72 | 150.12 | 364.61 | 635.29 | 180.36 | 0.00 | 0.00 | 0.00 |
July | 554.92 | 204.99 | 349.94 | 763.93 | 141.38 | 0.00 | 0.00 | 0.00 |
August | 659.49 | 332.50 | 326.99 | 880.12 | 159.99 | 0.00 | 0.00 | 0.00 |
September | 731.45 | 448.18 | 283.27 | 905.76 | 233.26 | 0.00 | 0.00 | 0.00 |
October | 764.69 | 528.77 | 235.92 | 866.01 | 334.92 | 0.00 | 0.00 | 0.00 |
November | 697.17 | 505.00 | 192.17 | 716.82 | 435.60 | 0.00 | 0.00 | 0.00 |
December | 605.95 | 437.56 | 168.39 | 571.78 | 583.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.18 | 373.96 | 275.22 | 721.81 | 359.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.72 | 150.12 | 168.39 | 558.94 | 141.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.48 | 583.64 | 364.61 | 905.76 | 666.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 102.32 | 864.59 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 259.47 | 656.38 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 344.89 | 565.86 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 557.82 | 429.52 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 778.04 | 313.71 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 947.50 | 215.38 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1053.28 | 180.20 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 863.66 | 203.08 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 643.22 | 275.53 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 374.75 | 418.37 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 207.52 | 586.10 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 91.29 | 797.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 520.01 | 458.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 91.29 | 180.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1053.28 | 864.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 102.32 | 864.59 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 259.47 | 656.38 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 344.89 | 565.86 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 557.82 | 429.52 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 778.04 | 313.71 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 947.50 | 215.38 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1053.28 | 180.20 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 863.66 | 203.08 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 643.22 | 275.53 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 374.75 | 418.37 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 207.52 | 586.10 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 91.29 | 797.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 520.01 | 458.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 91.29 | 180.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1053.28 | 864.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.92 | 84.20 | 124.73 | 102.32 | 864.57 | 0.00 | 0.00 | 0.00 |
February | 356.60 | 175.29 | 181.31 | 259.47 | 656.37 | 0.00 | 0.00 | 0.00 |
March | 456.36 | 167.22 | 289.14 | 344.88 | 565.85 | 0.00 | 0.00 | 0.00 |
April | 595.78 | 263.96 | 331.82 | 557.81 | 429.51 | 0.00 | 0.00 | 0.00 |
May | 736.94 | 336.09 | 400.86 | 778.02 | 313.71 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 368.28 | 433.48 | 947.48 | 215.38 | 0.00 | 0.00 | 0.00 |
July | 821.32 | 415.02 | 406.29 | 1053.26 | 180.20 | 0.00 | 0.00 | 0.00 |
August | 697.41 | 342.27 | 355.14 | 863.64 | 203.07 | 0.00 | 0.00 | 0.00 |
September | 561.02 | 283.63 | 277.39 | 643.21 | 275.53 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.22 | 201.75 | 374.75 | 418.36 | 0.00 | 0.00 | 0.00 |
November | 283.85 | 140.82 | 143.04 | 207.52 | 586.09 | 0.00 | 0.00 | 0.00 |
December | 190.80 | 80.53 | 110.27 | 91.29 | 797.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.01 | 238.27 | 271.73 | 520.00 | 458.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.80 | 80.53 | 110.27 | 91.29 | 180.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.32 | 415.02 | 433.48 | 1053.26 | 864.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 15.58 | 3734.47 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 117.29 | 2759.65 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 374.15 | 2226.76 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 637.97 | 1584.53 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1163.60 | 1180.77 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1854.85 | 763.42 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2013.82 | 635.95 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1465.95 | 727.13 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 863.71 | 1100.39 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 339.85 | 1626.70 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 83.64 | 2321.48 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 8.02 | 3187.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 748.76 | 1817.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 8.02 | 635.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2013.82 | 3734.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 372.08 | 2295.76 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 819.06 | 1696.14 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1195.46 | 1400.79 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1799.00 | 1010.59 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2129.31 | 788.67 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3162.75 | 518.98 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3579.47 | 424.07 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3038.54 | 477.34 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1956.22 | 689.02 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1172.99 | 1016.72 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 547.33 | 1416.02 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 292.92 | 1955.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1676.98 | 1138.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 292.92 | 424.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3579.47 | 2295.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2954.49 | 3259.57 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4132.75 | 2469.54 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3683.31 | 2210.45 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3078.53 | 1649.07 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2790.58 | 1289.03 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3172.44 | 880.39 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3815.13 | 702.77 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4389.16 | 797.13 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4501.65 | 1141.78 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4313.47 | 1620.91 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3588.27 | 2088.61 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2882.50 | 2773.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3604.47 | 1737.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2790.58 | 702.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4501.65 | 3259.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 321.74 | 2422.95 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 821.80 | 1773.66 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1096.56 | 1492.38 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1743.05 | 1101.40 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2361.08 | 865.37 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2872.76 | 595.99 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3193.56 | 499.92 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2637.96 | 539.72 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1954.08 | 757.81 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1174.76 | 1097.48 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 670.19 | 1506.31 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 308.42 | 2052.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1600.35 | 1223.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 308.42 | 499.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3193.56 | 2422.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 22.08 | 3600.33 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 140.62 | 2624.16 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 413.02 | 2091.06 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 690.19 | 1456.73 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1202.19 | 1103.26 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1871.53 | 737.60 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2016.68 | 624.56 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1474.40 | 703.38 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 890.42 | 1028.81 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 389.42 | 1474.20 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 104.38 | 2139.49 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 10.74 | 3040.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 772.65 | 1715.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 10.74 | 624.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2016.68 | 3600.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 384.33 | 2214.05 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 844.28 | 1616.12 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1223.99 | 1323.52 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1825.28 | 945.57 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2140.75 | 748.82 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3160.31 | 510.33 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3570.51 | 423.21 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3033.06 | 472.21 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1963.31 | 661.08 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1205.56 | 938.10 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 573.35 | 1313.57 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 304.19 | 1866.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1690.52 | 1084.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 304.19 | 423.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3570.51 | 2214.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2993.25 | 3116.55 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4177.65 | 2335.14 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3721.85 | 2080.86 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3114.34 | 1537.36 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2808.09 | 1218.17 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3173.56 | 856.51 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3807.65 | 694.14 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4383.16 | 781.57 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4509.31 | 1090.40 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4352.89 | 1497.31 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3646.42 | 1929.88 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2925.18 | 2629.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3630.24 | 1644.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2808.09 | 694.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4509.31 | 3116.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 330.23 | 2337.39 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 836.52 | 1695.08 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1113.20 | 1417.76 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1763.43 | 1036.01 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2370.32 | 822.45 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2872.56 | 582.10 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3189.04 | 494.67 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2636.73 | 530.07 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1960.43 | 725.16 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1196.09 | 1021.06 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 687.16 | 1409.11 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 315.90 | 1966.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1609.94 | 1168.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 315.90 | 494.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3189.04 | 2337.39 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242139E+09 | 0.00 | 0.242139E+09 | 3938393.23 | 0.212822E+10 |
February | 0.308799E+09 | 0.00 | 0.308799E+09 | 37098676.10 | 0.145062E+10 |
March | 0.555376E+09 | 0.00 | 0.555376E+09 | 0.165973E+09 | 0.130988E+10 |
April | 0.612820E+09 | 3576254.47 | 0.609243E+09 | 0.298592E+09 | 0.910482E+09 |
May | 0.831604E+09 | 49277394.08 | 0.782327E+09 | 0.602675E+09 | 0.679643E+09 |
June | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.950613E+09 | 0.411852E+09 |
July | 0.884648E+09 | 82857303.69 | 0.801791E+09 | 0.106777E+10 | 0.349979E+09 |
August | 0.708873E+09 | 19000970.75 | 0.689872E+09 | 0.772663E+09 | 0.404790E+09 |
September | 0.513771E+09 | 184367.60 | 0.513587E+09 | 0.433838E+09 | 0.610303E+09 |
October | 0.387258E+09 | 0.00 | 0.387258E+09 | 0.155952E+09 | 0.967630E+09 |
November | 0.254769E+09 | 0.00 | 0.254769E+09 | 29623057.50 | 0.135703E+10 |
December | 0.203047E+09 | 0.00 | 0.203047E+09 | 1240095.59 | 0.190080E+10 |
Annual Sum or Average | 0.644022E+10 | 0.262610E+09 | 0.617761E+10 | 0.451998E+10 | 0.124812E+11 |
Minimum of Months | 0.203047E+09 | 0.00 | 0.203047E+09 | 1240095.59 | 0.349979E+09 |
Maximum of Months | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.106777E+10 | 0.212822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 3938013.47 | 0.212822E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37096871.73 | 0.145062E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.165966E+09 | 0.130988E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.298584E+09 | 0.910482E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.602662E+09 | 0.679643E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.950596E+09 | 0.411851E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106775E+10 | 0.349977E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.772653E+09 | 0.404789E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.433831E+09 | 0.610302E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.155947E+09 | 0.967629E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29621545.97 | 0.135703E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1239942.68 | 0.190080E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.451989E+10 | 0.124812E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1239942.68 | 0.349977E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106775E+10 | 0.212822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242136E+09 | 0.00 | 0.242136E+09 | 3938140.05 | 0.212822E+10 |
February | 0.308796E+09 | 0.00 | 0.308796E+09 | 37097473.19 | 0.145062E+10 |
March | 0.555371E+09 | 0.00 | 0.555371E+09 | 0.165969E+09 | 0.130988E+10 |
April | 0.612814E+09 | 3576202.05 | 0.609237E+09 | 0.298587E+09 | 0.910482E+09 |
May | 0.831596E+09 | 49276671.88 | 0.782319E+09 | 0.602666E+09 | 0.679643E+09 |
June | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.950602E+09 | 0.411852E+09 |
July | 0.884640E+09 | 82856089.35 | 0.801784E+09 | 0.106776E+10 | 0.349978E+09 |
August | 0.708867E+09 | 19000692.27 | 0.689866E+09 | 0.772656E+09 | 0.404789E+09 |
September | 0.513767E+09 | 184364.90 | 0.513582E+09 | 0.433834E+09 | 0.610302E+09 |
October | 0.387254E+09 | 0.00 | 0.387254E+09 | 0.155949E+09 | 0.967629E+09 |
November | 0.254767E+09 | 0.00 | 0.254767E+09 | 29622049.81 | 0.135703E+10 |
December | 0.203045E+09 | 0.00 | 0.203045E+09 | 1239993.65 | 0.190080E+10 |
Annual Sum or Average | 0.644016E+10 | 0.262606E+09 | 0.617756E+10 | 0.451992E+10 | 0.124812E+11 |
Minimum of Months | 0.203045E+09 | 0.00 | 0.203045E+09 | 1239993.65 | 0.349978E+09 |
Maximum of Months | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.106776E+10 | 0.212822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 3938013.47 | 0.212822E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37096871.73 | 0.145062E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.165966E+09 | 0.130988E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.298584E+09 | 0.910482E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.602662E+09 | 0.679643E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.950596E+09 | 0.411851E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106775E+10 | 0.349977E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.772653E+09 | 0.404789E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.433831E+09 | 0.610302E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.155947E+09 | 0.967629E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29621545.97 | 0.135703E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1239942.68 | 0.190080E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.451989E+10 | 0.124812E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1239942.68 | 0.349977E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106775E+10 | 0.212822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242126E+09 | 0.00 | 0.242126E+09 | 3937918.04 | 0.212813E+10 |
February | 0.308783E+09 | 0.00 | 0.308783E+09 | 37095677.28 | 0.145057E+10 |
March | 0.555347E+09 | 0.00 | 0.555347E+09 | 0.165961E+09 | 0.130983E+10 |
April | 0.612788E+09 | 3576044.81 | 0.609211E+09 | 0.298573E+09 | 0.910446E+09 |
May | 0.831561E+09 | 49274505.26 | 0.782286E+09 | 0.602640E+09 | 0.679616E+09 |
June | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.950561E+09 | 0.411835E+09 |
July | 0.884602E+09 | 82852446.31 | 0.801750E+09 | 0.106771E+10 | 0.349964E+09 |
August | 0.708837E+09 | 18999856.84 | 0.689837E+09 | 0.772623E+09 | 0.404773E+09 |
September | 0.513745E+09 | 184356.80 | 0.513560E+09 | 0.433815E+09 | 0.610278E+09 |
October | 0.387238E+09 | 0.00 | 0.387238E+09 | 0.155942E+09 | 0.967590E+09 |
November | 0.254756E+09 | 0.00 | 0.254756E+09 | 29620604.00 | 0.135697E+10 |
December | 0.203036E+09 | 0.00 | 0.203036E+09 | 1239918.19 | 0.190072E+10 |
Annual Sum or Average | 0.643989E+10 | 0.262594E+09 | 0.617729E+10 | 0.451972E+10 | 0.124807E+11 |
Minimum of Months | 0.203036E+09 | 0.00 | 0.203036E+09 | 1239918.19 | 0.349964E+09 |
Maximum of Months | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.106771E+10 | 0.212813E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317623E+09 | 0.215639E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.638044E+09 | 0.145648E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.104272E+10 | 0.133281E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.154169E+10 | 0.927543E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.189608E+10 | 0.746343E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.274272E+10 | 0.456334E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.321018E+10 | 0.371490E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.272625E+10 | 0.415225E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168840E+10 | 0.623634E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102679E+10 | 0.978020E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.450286E+09 | 0.133143E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243495E+09 | 0.188921E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.175243E+11 | 0.126849E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243495E+09 | 0.371490E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.321018E+10 | 0.215639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317623E+09 | 0.215639E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.638044E+09 | 0.145648E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.104272E+10 | 0.133281E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.154169E+10 | 0.927543E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.189608E+10 | 0.746343E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.274272E+10 | 0.456334E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.321018E+10 | 0.371490E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.272625E+10 | 0.415225E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168840E+10 | 0.623634E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102679E+10 | 0.978020E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.450286E+09 | 0.133143E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243495E+09 | 0.188921E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.175243E+11 | 0.126849E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.243495E+09 | 0.371490E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.321018E+10 | 0.215639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617784E+09 | 0.283229E+09 | 0.334555E+09 | 0.317617E+09 | 0.215635E+10 |
February | 0.872759E+09 | 0.433304E+09 | 0.439455E+09 | 0.638033E+09 | 0.145645E+10 |
March | 0.129924E+10 | 0.537588E+09 | 0.761649E+09 | 0.104270E+10 | 0.133278E+10 |
April | 0.160422E+10 | 0.795042E+09 | 0.809182E+09 | 0.154166E+10 | 0.927526E+09 |
May | 0.183114E+10 | 0.814744E+09 | 0.101640E+10 | 0.189605E+10 | 0.746329E+09 |
June | 0.229372E+10 | 0.118035E+10 | 0.111337E+10 | 0.274267E+10 | 0.456325E+09 |
July | 0.248757E+10 | 0.140629E+10 | 0.108128E+10 | 0.321012E+10 | 0.371483E+09 |
August | 0.216181E+10 | 0.120449E+10 | 0.957315E+09 | 0.272620E+10 | 0.415218E+09 |
September | 0.147994E+10 | 0.763937E+09 | 0.715998E+09 | 0.168837E+10 | 0.623623E+09 |
October | 0.109717E+10 | 0.557125E+09 | 0.540043E+09 | 0.102677E+10 | 0.978003E+09 |
November | 0.672933E+09 | 0.314171E+09 | 0.358762E+09 | 0.450277E+09 | 0.133141E+10 |
December | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.243491E+09 | 0.188918E+10 |
Annual Sum or Average | 0.169312E+11 | 0.851055E+10 | 0.842060E+10 | 0.175240E+11 | 0.126847E+11 |
Minimum of Months | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.243491E+09 | 0.371483E+09 |
Maximum of Months | 0.248757E+10 | 0.140629E+10 | 0.111337E+10 | 0.321012E+10 | 0.215635E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158384E+10 | 0.178583E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200426E+10 | 0.123287E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197621E+10 | 0.122719E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159525E+10 | 0.894006E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149714E+10 | 0.715953E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164674E+10 | 0.467508E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204619E+10 | 0.378697E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235741E+10 | 0.428541E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234784E+10 | 0.604639E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231962E+10 | 0.897097E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185809E+10 | 0.112911E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153152E+10 | 0.156164E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227641E+11 | 0.113231E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149714E+10 | 0.378697E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235741E+10 | 0.178583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158382E+10 | 0.178583E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200425E+10 | 0.123287E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197619E+10 | 0.122719E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159523E+10 | 0.894006E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149713E+10 | 0.715953E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164673E+10 | 0.467508E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204618E+10 | 0.378696E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235740E+10 | 0.428540E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234782E+10 | 0.604639E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231960E+10 | 0.897097E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185808E+10 | 0.112911E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153150E+10 | 0.156164E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227639E+11 | 0.113231E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149713E+10 | 0.378696E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235740E+10 | 0.178583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158384E+10 | 0.178583E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200426E+10 | 0.123287E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197621E+10 | 0.122719E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159525E+10 | 0.894006E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149714E+10 | 0.715953E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164674E+10 | 0.467508E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204619E+10 | 0.378697E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235741E+10 | 0.428541E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234784E+10 | 0.604639E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231962E+10 | 0.897097E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185809E+10 | 0.112911E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153152E+10 | 0.156164E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227641E+11 | 0.113231E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149714E+10 | 0.378697E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235741E+10 | 0.178583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158382E+10 | 0.178583E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200425E+10 | 0.123287E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197619E+10 | 0.122719E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159523E+10 | 0.894006E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149713E+10 | 0.715953E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164673E+10 | 0.467508E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204618E+10 | 0.378696E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235740E+10 | 0.428540E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234782E+10 | 0.604639E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231960E+10 | 0.897097E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185808E+10 | 0.112911E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153150E+10 | 0.156164E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227639E+11 | 0.113231E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149713E+10 | 0.378696E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235740E+10 | 0.178583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170670E+10 | 0.121896E+10 | 0.487742E+09 | 0.158376E+10 | 0.178575E+10 |
February | 0.196312E+10 | 0.141195E+10 | 0.551174E+09 | 0.200417E+10 | 0.123282E+10 |
March | 0.194279E+10 | 0.109098E+10 | 0.851812E+09 | 0.197612E+10 | 0.122714E+10 |
April | 0.151130E+10 | 0.722862E+09 | 0.788441E+09 | 0.159518E+10 | 0.893970E+09 |
May | 0.138752E+10 | 0.460829E+09 | 0.926687E+09 | 0.149707E+10 | 0.715924E+09 |
June | 0.133417E+10 | 0.389103E+09 | 0.945063E+09 | 0.164667E+10 | 0.467489E+09 |
July | 0.148631E+10 | 0.549034E+09 | 0.937277E+09 | 0.204610E+10 | 0.378681E+09 |
August | 0.176638E+10 | 0.890571E+09 | 0.875807E+09 | 0.235731E+10 | 0.428523E+09 |
September | 0.189592E+10 | 0.116169E+10 | 0.734234E+09 | 0.234774E+10 | 0.604615E+09 |
October | 0.204815E+10 | 0.141627E+10 | 0.631885E+09 | 0.231952E+10 | 0.897061E+09 |
November | 0.180707E+10 | 0.130897E+10 | 0.498104E+09 | 0.185801E+10 | 0.112906E+10 |
December | 0.162297E+10 | 0.117195E+10 | 0.451025E+09 | 0.153145E+10 | 0.156158E+10 |
Annual Sum or Average | 0.204724E+11 | 0.117932E+11 | 0.867925E+10 | 0.227631E+11 | 0.113226E+11 |
Minimum of Months | 0.133417E+10 | 0.389103E+09 | 0.451025E+09 | 0.149707E+10 | 0.378681E+09 |
Maximum of Months | 0.204815E+10 | 0.141627E+10 | 0.945063E+09 | 0.235731E+10 | 0.178575E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.274047E+09 | 0.231572E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.627720E+09 | 0.158792E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.923751E+09 | 0.151560E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144587E+10 | 0.111330E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.208389E+10 | 0.840253E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.245592E+10 | 0.558273E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.282110E+10 | 0.482660E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.231322E+10 | 0.543924E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.166723E+10 | 0.714182E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.100374E+10 | 0.112056E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.537894E+09 | 0.151918E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244511E+09 | 0.213482E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.163989E+11 | 0.144464E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244511E+09 | 0.482660E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.282110E+10 | 0.231572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.274047E+09 | 0.231572E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.627720E+09 | 0.158792E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.923751E+09 | 0.151560E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144587E+10 | 0.111330E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.208389E+10 | 0.840253E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.245592E+10 | 0.558273E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.282110E+10 | 0.482660E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.231322E+10 | 0.543924E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.166723E+10 | 0.714182E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.100374E+10 | 0.112056E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.537894E+09 | 0.151918E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244511E+09 | 0.213482E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.163989E+11 | 0.144464E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.244511E+09 | 0.482660E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.282110E+10 | 0.231572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559581E+09 | 0.225515E+09 | 0.334066E+09 | 0.274042E+09 | 0.231568E+10 |
February | 0.862689E+09 | 0.424056E+09 | 0.438634E+09 | 0.627709E+09 | 0.158789E+10 |
March | 0.122232E+10 | 0.447877E+09 | 0.774445E+09 | 0.923734E+09 | 0.151557E+10 |
April | 0.154427E+10 | 0.684184E+09 | 0.860088E+09 | 0.144585E+10 | 0.111328E+10 |
May | 0.197383E+10 | 0.900170E+09 | 0.107366E+10 | 0.208386E+10 | 0.840237E+09 |
June | 0.207817E+10 | 0.954583E+09 | 0.112359E+10 | 0.245587E+10 | 0.558263E+09 |
July | 0.219982E+10 | 0.111160E+10 | 0.108822E+10 | 0.282105E+10 | 0.482652E+09 |
August | 0.186794E+10 | 0.916748E+09 | 0.951197E+09 | 0.231317E+10 | 0.543914E+09 |
September | 0.145417E+10 | 0.735170E+09 | 0.719002E+09 | 0.166720E+10 | 0.714169E+09 |
October | 0.107398E+10 | 0.533602E+09 | 0.540376E+09 | 0.100372E+10 | 0.112054E+10 |
November | 0.735749E+09 | 0.364994E+09 | 0.370755E+09 | 0.537884E+09 | 0.151915E+10 |
December | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.244507E+09 | 0.213478E+10 |
Annual Sum or Average | 0.160836E+11 | 0.751420E+10 | 0.856937E+10 | 0.163986E+11 | 0.144461E+11 |
Minimum of Months | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.244507E+09 | 0.482652E+09 |
Maximum of Months | 0.219982E+10 | 0.111160E+10 | 0.112359E+10 | 0.282105E+10 | 0.231568E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 41722084.11 | 0.100024E+11 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.283747E+09 | 0.667614E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.100213E+10 | 0.596415E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.165363E+10 | 0.410710E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.311660E+10 | 0.316259E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.480776E+10 | 0.197877E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.539381E+10 | 0.170332E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.392641E+10 | 0.194754E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.223873E+10 | 0.285221E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.910255E+09 | 0.435694E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.216783E+09 | 0.601727E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 21475302.38 | 0.853638E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.236131E+11 | 0.573048E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 21475302.38 | 0.170332E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.539381E+10 | 0.100024E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.996576E+09 | 0.614897E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.198148E+10 | 0.410331E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.320193E+10 | 0.375187E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.466302E+10 | 0.261946E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.570316E+10 | 0.211236E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.819784E+10 | 0.134520E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.958727E+10 | 0.113582E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.813842E+10 | 0.127852E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.507053E+10 | 0.178595E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.314174E+10 | 0.272318E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.141868E+10 | 0.367034E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.784550E+09 | 0.523701E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.528852E+11 | 0.359120E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.784550E+09 | 0.113582E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.958727E+10 | 0.614897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.791329E+10 | 0.873042E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.999794E+10 | 0.597430E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.986536E+10 | 0.592047E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.797954E+10 | 0.427440E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.747430E+10 | 0.345253E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.822297E+10 | 0.228198E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.102184E+11 | 0.188229E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117559E+11 | 0.213503E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116683E+11 | 0.295949E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.115532E+11 | 0.434144E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.930079E+10 | 0.541367E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.772049E+10 | 0.742866E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.113671E+12 | 0.547947E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.747430E+10 | 0.188229E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117559E+11 | 0.873042E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.861749E+09 | 0.648962E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.198811E+10 | 0.429085E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.293703E+10 | 0.399718E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.451799E+10 | 0.285482E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.632391E+10 | 0.231781E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.744620E+10 | 0.154481E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.855363E+10 | 0.133899E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.706551E+10 | 0.144558E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.506497E+10 | 0.196423E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.314648E+10 | 0.293950E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.173714E+10 | 0.390436E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.826068E+09 | 0.549698E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.504688E+11 | 0.385847E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.826068E+09 | 0.133899E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.855363E+10 | 0.648962E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 59127059.33 | 0.964311E+10 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.340190E+09 | 0.634837E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.110622E+10 | 0.560069E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.178898E+10 | 0.377585E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.321993E+10 | 0.295496E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.485099E+10 | 0.191186E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.540147E+10 | 0.167283E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.394904E+10 | 0.188394E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.230798E+10 | 0.266667E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.104303E+10 | 0.394849E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.270563E+09 | 0.554557E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 28777957.44 | 0.814453E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.243663E+11 | 0.540969E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 28777957.44 | 0.167283E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.540147E+10 | 0.964311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.102938E+10 | 0.593010E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.204248E+10 | 0.390973E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.327833E+10 | 0.354492E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.473112E+10 | 0.245092E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.573379E+10 | 0.200565E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.819151E+10 | 0.132279E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.956325E+10 | 0.113351E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.812374E+10 | 0.126478E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.508891E+10 | 0.171353E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.322897E+10 | 0.251261E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.148612E+10 | 0.340478E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.814734E+09 | 0.500011E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.533123E+11 | 0.341934E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.814734E+09 | 0.113351E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.956325E+10 | 0.593010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.801711E+10 | 0.834737E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.101066E+11 | 0.564916E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.996859E+10 | 0.557337E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.807238E+10 | 0.398484E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.752120E+10 | 0.326274E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.822587E+10 | 0.222007E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.101984E+11 | 0.185918E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117399E+11 | 0.209335E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116881E+11 | 0.282631E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.116588E+11 | 0.401040E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.945151E+10 | 0.500225E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.783481E+10 | 0.704172E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.114483E+12 | 0.518708E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.752120E+10 | 0.185918E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117399E+11 | 0.834737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.884481E+09 | 0.626046E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.202371E+10 | 0.410073E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.298160E+10 | 0.379732E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.457082E+10 | 0.268534E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.634868E+10 | 0.220284E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.744566E+10 | 0.150881E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.854154E+10 | 0.132493E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.706222E+10 | 0.141973E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.508144E+10 | 0.187961E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.320360E+10 | 0.273480E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.178111E+10 | 0.365241E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.846095E+09 | 0.526802E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.507710E+11 | 0.368350E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.846095E+09 | 0.132493E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.854154E+10 | 0.626046E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.35 | 3972.90 | 452.01 | 0.00 | 452.01 | 0.00 | 0.00 |
February | 76.67 | 2998.12 | 638.21 | 0.00 | 638.21 | 0.00 | 0.00 |
March | 309.82 | 2445.25 | 1036.75 | 0.00 | 1036.75 | 0.00 | 0.00 |
April | 575.97 | 1756.32 | 1182.12 | 6.90 | 1175.22 | 0.00 | 0.00 |
May | 1125.04 | 1268.74 | 1552.40 | 91.99 | 1460.41 | 0.00 | 0.00 |
June | 1833.71 | 794.46 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
July | 1993.26 | 653.33 | 1651.42 | 154.67 | 1496.75 | 0.00 | 0.00 |
August | 1442.37 | 755.65 | 1323.29 | 35.47 | 1287.82 | 0.00 | 0.00 |
September | 836.86 | 1177.27 | 991.05 | 0.36 | 990.70 | 0.00 | 0.00 |
October | 291.12 | 1806.34 | 722.92 | 0.00 | 722.92 | 0.00 | 0.00 |
November | 57.14 | 2617.70 | 491.44 | 0.00 | 491.44 | 0.00 | 0.00 |
December | 2.31 | 3548.36 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Annual Sum or Average | 716.62 | 1978.87 | 1021.07 | 41.64 | 979.44 | 0.00 | 0.00 |
Minimum of Months | 2.31 | 653.33 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Maximum of Months | 1993.26 | 3972.90 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.76 | 2415.29 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 791.22 | 1806.14 | 1082.30 | 537.34 | 544.97 | 0.00 | 0.00 |
March | 1167.91 | 1492.83 | 1455.26 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1784.35 | 1073.54 | 1856.76 | 920.20 | 936.56 | 0.00 | 0.00 |
May | 2123.74 | 835.95 | 2051.04 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3174.42 | 528.16 | 2654.80 | 1366.16 | 1288.64 | 0.00 | 0.00 |
July | 3595.61 | 416.09 | 2786.29 | 1575.16 | 1211.13 | 0.00 | 0.00 |
August | 3053.58 | 465.08 | 2421.41 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1954.15 | 721.79 | 1712.91 | 884.20 | 828.71 | 0.00 | 0.00 |
October | 1150.07 | 1095.45 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 521.16 | 1541.00 | 778.87 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 272.73 | 2116.04 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1667.06 | 1206.70 | 1610.67 | 809.61 | 801.06 | 0.00 | 0.00 |
Minimum of Months | 272.73 | 416.09 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3595.61 | 2415.29 | 2786.29 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2956.65 | 3333.73 | 3186.14 | 2275.60 | 910.54 | 0.00 | 0.00 |
February | 4142.36 | 2548.08 | 4057.51 | 2918.31 | 1139.20 | 0.00 | 0.00 |
March | 3689.11 | 2290.87 | 3626.89 | 2036.69 | 1590.20 | 0.00 | 0.00 |
April | 3077.21 | 1724.54 | 2915.42 | 1394.46 | 1520.96 | 0.00 | 0.00 |
May | 2794.80 | 1336.52 | 2590.28 | 860.30 | 1729.98 | 0.00 | 0.00 |
June | 3176.54 | 901.82 | 2573.71 | 750.61 | 1823.10 | 0.00 | 0.00 |
July | 3819.76 | 706.94 | 2774.71 | 1024.96 | 1749.75 | 0.00 | 0.00 |
August | 4400.73 | 799.99 | 3297.56 | 1662.56 | 1635.00 | 0.00 | 0.00 |
September | 4528.96 | 1166.35 | 3657.38 | 2240.99 | 1416.39 | 0.00 | 0.00 |
October | 4330.19 | 1674.67 | 3823.59 | 2643.96 | 1179.63 | 0.00 | 0.00 |
November | 3584.24 | 2178.05 | 3485.98 | 2525.10 | 960.88 | 0.00 | 0.00 |
December | 2858.98 | 2915.22 | 3029.84 | 2187.85 | 841.99 | 0.00 | 0.00 |
Annual Sum or Average | 3609.18 | 1795.25 | 3245.98 | 1869.85 | 1376.13 | 0.00 | 0.00 |
Minimum of Months | 2794.80 | 706.94 | 2573.71 | 750.61 | 841.99 | 0.00 | 0.00 |
Maximum of Months | 4528.96 | 3333.73 | 4057.51 | 2918.31 | 1823.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 306.95 | 2593.75 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 778.42 | 1969.13 | 1069.82 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1034.66 | 1697.57 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1673.46 | 1288.54 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2334.10 | 941.14 | 2210.85 | 1008.27 | 1202.59 | 0.00 | 0.00 |
June | 2842.48 | 646.15 | 2405.32 | 1104.86 | 1300.47 | 0.00 | 0.00 |
July | 3159.82 | 540.61 | 2463.99 | 1245.09 | 1218.90 | 0.00 | 0.00 |
August | 2590.95 | 609.23 | 2092.26 | 1026.84 | 1065.42 | 0.00 | 0.00 |
September | 1929.66 | 826.59 | 1683.09 | 850.90 | 832.19 | 0.00 | 0.00 |
October | 1124.25 | 1255.10 | 1202.95 | 597.68 | 605.27 | 0.00 | 0.00 |
November | 622.56 | 1758.30 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 273.87 | 2391.14 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1560.01 | 1374.27 | 1530.04 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 273.87 | 540.61 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3159.82 | 2593.75 | 2463.99 | 1245.09 | 1300.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.58 | 3734.47 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 117.29 | 2759.65 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 374.15 | 2226.76 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 637.97 | 1584.53 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1163.60 | 1180.77 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1854.85 | 763.42 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2013.82 | 635.95 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1465.95 | 727.13 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 863.71 | 1100.39 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 339.85 | 1626.70 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 83.64 | 2321.48 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 8.02 | 3187.12 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 748.76 | 1817.12 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 8.02 | 635.95 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2013.82 | 3734.47 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.08 | 2295.76 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 819.06 | 1696.14 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1195.46 | 1400.79 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1799.00 | 1010.59 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2129.31 | 788.67 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3162.75 | 518.98 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3579.47 | 424.07 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3038.54 | 477.34 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1956.22 | 689.02 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1172.99 | 1016.72 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 547.33 | 1416.02 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 292.92 | 1955.27 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1676.98 | 1138.76 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 292.92 | 424.07 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3579.47 | 2295.76 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2954.49 | 3259.57 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4132.75 | 2469.54 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3683.31 | 2210.45 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3078.53 | 1649.07 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2790.58 | 1289.03 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3172.44 | 880.39 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3815.13 | 702.77 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4389.16 | 797.13 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4501.65 | 1141.78 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4313.47 | 1620.91 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3588.27 | 2088.61 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2882.50 | 2773.54 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3604.47 | 1737.53 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2790.58 | 702.77 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4501.65 | 3259.57 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.74 | 2422.95 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 821.80 | 1773.66 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1096.56 | 1492.38 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1743.05 | 1101.40 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2361.08 | 865.37 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2872.76 | 595.99 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3193.56 | 499.92 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2637.96 | 539.72 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1954.08 | 757.81 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1174.76 | 1097.48 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 670.19 | 1506.31 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 308.42 | 2052.34 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1600.35 | 1223.51 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 308.42 | 499.92 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3193.56 | 2422.95 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.08 | 3600.33 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 140.62 | 2624.16 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 413.02 | 2091.06 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 690.19 | 1456.73 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1202.19 | 1103.26 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1871.53 | 737.60 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2016.68 | 624.56 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1474.40 | 703.38 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 890.42 | 1028.81 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 389.42 | 1474.20 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 104.38 | 2139.49 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 10.74 | 3040.82 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 772.65 | 1715.40 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 10.74 | 624.56 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2016.68 | 3600.33 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 384.33 | 2214.05 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 844.28 | 1616.12 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1223.99 | 1323.52 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1825.28 | 945.57 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2140.75 | 748.82 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3160.31 | 510.33 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3570.51 | 423.21 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3033.06 | 472.21 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1963.31 | 661.08 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1205.56 | 938.10 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 573.35 | 1313.57 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 304.19 | 1866.83 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1690.52 | 1084.27 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 304.19 | 423.21 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3570.51 | 2214.05 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2993.25 | 3116.55 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4177.65 | 2335.14 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3721.85 | 2080.86 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3114.34 | 1537.36 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2808.09 | 1218.17 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3173.56 | 856.51 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3807.65 | 694.14 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4383.16 | 781.57 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4509.31 | 1090.40 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4352.89 | 1497.31 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3646.42 | 1929.88 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2925.18 | 2629.08 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3630.24 | 1644.81 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2808.09 | 694.14 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4509.31 | 3116.55 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.23 | 2337.39 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 836.52 | 1695.08 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1113.20 | 1417.76 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1763.43 | 1036.01 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2370.32 | 822.45 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2872.56 | 582.10 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3189.04 | 494.67 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2636.73 | 530.07 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1960.43 | 725.16 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1196.09 | 1021.06 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 687.16 | 1409.11 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 315.90 | 1966.85 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1609.94 | 1168.03 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 315.90 | 494.67 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3189.04 | 2337.39 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19690478.26 | 0.106410E+11 | 0.121067E+10 | 0.00 | 0.121067E+10 | 0.00 | 0.00 |
February | 0.185486E+09 | 0.725306E+10 | 0.154397E+10 | 0.00 | 0.154397E+10 | 0.00 | 0.00 |
March | 0.829835E+09 | 0.654935E+10 | 0.277683E+10 | 0.00 | 0.277683E+10 | 0.00 | 0.00 |
April | 0.149292E+10 | 0.455237E+10 | 0.306404E+10 | 17880853.02 | 0.304616E+10 | 0.00 | 0.00 |
May | 0.301330E+10 | 0.339819E+10 | 0.415795E+10 | 0.246381E+09 | 0.391156E+10 | 0.00 | 0.00 |
June | 0.475297E+10 | 0.205924E+10 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
July | 0.533875E+10 | 0.174988E+10 | 0.442316E+10 | 0.414277E+09 | 0.400889E+10 | 0.00 | 0.00 |
August | 0.386325E+10 | 0.202393E+10 | 0.354431E+10 | 95002625.92 | 0.344930E+10 | 0.00 | 0.00 |
September | 0.216915E+10 | 0.305149E+10 | 0.256881E+10 | 921816.40 | 0.256789E+10 | 0.00 | 0.00 |
October | 0.779736E+09 | 0.483811E+10 | 0.193626E+10 | 0.00 | 0.193626E+10 | 0.00 | 0.00 |
November | 0.148109E+09 | 0.678508E+10 | 0.127382E+10 | 0.00 | 0.127382E+10 | 0.00 | 0.00 |
December | 6199892.79 | 0.950392E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.225994E+11 | 0.624056E+11 | 0.322005E+11 | 0.131302E+10 | 0.308875E+11 | 0.00 | 0.00 |
Minimum of Months | 6199892.79 | 0.174988E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.533875E+10 | 0.106410E+11 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952863E+09 | 0.646912E+10 | 0.185337E+10 | 0.849697E+09 | 0.100368E+10 | 0.00 | 0.00 |
February | 0.191412E+10 | 0.436941E+10 | 0.261831E+10 | 0.129993E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.312813E+10 | 0.399840E+10 | 0.389776E+10 | 0.161278E+10 | 0.228497E+10 | 0.00 | 0.00 |
April | 0.462504E+10 | 0.278261E+10 | 0.481273E+10 | 0.238515E+10 | 0.242758E+10 | 0.00 | 0.00 |
May | 0.568822E+10 | 0.223901E+10 | 0.549350E+10 | 0.244426E+10 | 0.304924E+10 | 0.00 | 0.00 |
June | 0.822811E+10 | 0.136899E+10 | 0.688124E+10 | 0.354108E+10 | 0.334016E+10 | 0.00 | 0.00 |
July | 0.963048E+10 | 0.111446E+10 | 0.746279E+10 | 0.421892E+10 | 0.324388E+10 | 0.00 | 0.00 |
August | 0.817871E+10 | 0.124567E+10 | 0.648550E+10 | 0.361352E+10 | 0.287198E+10 | 0.00 | 0.00 |
September | 0.506516E+10 | 0.187089E+10 | 0.443986E+10 | 0.229184E+10 | 0.214802E+10 | 0.00 | 0.00 |
October | 0.308035E+10 | 0.293404E+10 | 0.329155E+10 | 0.167140E+10 | 0.162015E+10 | 0.00 | 0.00 |
November | 0.135085E+10 | 0.399428E+10 | 0.201882E+10 | 0.942526E+09 | 0.107630E+10 | 0.00 | 0.00 |
December | 0.730482E+09 | 0.566761E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525725E+11 | 0.380545E+11 | 0.507941E+11 | 0.255320E+11 | 0.252621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.730482E+09 | 0.111446E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.963048E+10 | 0.646912E+10 | 0.746279E+10 | 0.421892E+10 | 0.334016E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791908E+10 | 0.892905E+10 | 0.853377E+10 | 0.609498E+10 | 0.243879E+10 | 0.00 | 0.00 |
February | 0.100212E+11 | 0.616432E+10 | 0.981593E+10 | 0.705997E+10 | 0.275596E+10 | 0.00 | 0.00 |
March | 0.988092E+10 | 0.613588E+10 | 0.971426E+10 | 0.545506E+10 | 0.425920E+10 | 0.00 | 0.00 |
April | 0.797613E+10 | 0.447000E+10 | 0.755676E+10 | 0.361443E+10 | 0.394233E+10 | 0.00 | 0.00 |
May | 0.748560E+10 | 0.357973E+10 | 0.693780E+10 | 0.230422E+10 | 0.463359E+10 | 0.00 | 0.00 |
June | 0.823360E+10 | 0.233752E+10 | 0.667105E+10 | 0.194558E+10 | 0.472547E+10 | 0.00 | 0.00 |
July | 0.102309E+11 | 0.189347E+10 | 0.743179E+10 | 0.274526E+10 | 0.468653E+10 | 0.00 | 0.00 |
August | 0.117869E+11 | 0.214269E+10 | 0.883217E+10 | 0.445300E+10 | 0.437918E+10 | 0.00 | 0.00 |
September | 0.117391E+11 | 0.302317E+10 | 0.947992E+10 | 0.580863E+10 | 0.367129E+10 | 0.00 | 0.00 |
October | 0.115980E+11 | 0.448545E+10 | 0.102411E+11 | 0.708157E+10 | 0.315953E+10 | 0.00 | 0.00 |
November | 0.929034E+10 | 0.564550E+10 | 0.903565E+10 | 0.654505E+10 | 0.249060E+10 | 0.00 | 0.00 |
December | 0.765749E+10 | 0.780813E+10 | 0.811513E+10 | 0.585994E+10 | 0.225520E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113819E+12 | 0.566149E+11 | 0.102365E+12 | 0.589677E+11 | 0.433977E+11 | 0.00 | 0.00 |
Minimum of Months | 0.748560E+10 | 0.189347E+10 | 0.667105E+10 | 0.194558E+10 | 0.225520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117869E+11 | 0.892905E+10 | 0.102411E+11 | 0.708157E+10 | 0.472547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.822135E+09 | 0.694711E+10 | 0.167876E+10 | 0.676554E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.188315E+10 | 0.476372E+10 | 0.258810E+10 | 0.127218E+10 | 0.131592E+10 | 0.00 | 0.00 |
March | 0.277124E+10 | 0.454676E+10 | 0.366701E+10 | 0.134365E+10 | 0.232336E+10 | 0.00 | 0.00 |
April | 0.433760E+10 | 0.333989E+10 | 0.463287E+10 | 0.205258E+10 | 0.258030E+10 | 0.00 | 0.00 |
May | 0.625165E+10 | 0.252074E+10 | 0.592155E+10 | 0.270054E+10 | 0.322101E+10 | 0.00 | 0.00 |
June | 0.736770E+10 | 0.167481E+10 | 0.623460E+10 | 0.286378E+10 | 0.337081E+10 | 0.00 | 0.00 |
July | 0.846325E+10 | 0.144797E+10 | 0.659954E+10 | 0.333485E+10 | 0.326470E+10 | 0.00 | 0.00 |
August | 0.693960E+10 | 0.163176E+10 | 0.560390E+10 | 0.275028E+10 | 0.285362E+10 | 0.00 | 0.00 |
September | 0.500167E+10 | 0.214253E+10 | 0.436257E+10 | 0.220554E+10 | 0.215703E+10 | 0.00 | 0.00 |
October | 0.301120E+10 | 0.336166E+10 | 0.322197E+10 | 0.160082E+10 | 0.162115E+10 | 0.00 | 0.00 |
November | 0.161367E+10 | 0.455750E+10 | 0.220727E+10 | 0.109500E+10 | 0.111228E+10 | 0.00 | 0.00 |
December | 0.733529E+09 | 0.640442E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.491964E+11 | 0.433389E+11 | 0.482513E+11 | 0.225429E+11 | 0.257084E+11 | 0.00 | 0.00 |
Minimum of Months | 0.733529E+09 | 0.144797E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.846325E+10 | 0.694711E+10 | 0.659954E+10 | 0.333485E+10 | 0.337081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41722084.11 | 0.100024E+11 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.283747E+09 | 0.667614E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.100213E+10 | 0.596415E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.165363E+10 | 0.410710E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.311660E+10 | 0.316259E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.480776E+10 | 0.197877E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.539381E+10 | 0.170332E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.392641E+10 | 0.194754E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.223873E+10 | 0.285221E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.910255E+09 | 0.435694E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.216783E+09 | 0.601727E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 21475302.38 | 0.853638E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.236131E+11 | 0.573048E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 21475302.38 | 0.170332E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.539381E+10 | 0.100024E+11 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996576E+09 | 0.614897E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.198148E+10 | 0.410331E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.320193E+10 | 0.375187E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.466302E+10 | 0.261946E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.570316E+10 | 0.211236E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.819784E+10 | 0.134520E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.958727E+10 | 0.113582E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.813842E+10 | 0.127852E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.507053E+10 | 0.178595E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.314174E+10 | 0.272318E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.141868E+10 | 0.367034E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.784550E+09 | 0.523701E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.528852E+11 | 0.359120E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784550E+09 | 0.113582E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.958727E+10 | 0.614897E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791329E+10 | 0.873042E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.999794E+10 | 0.597430E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.986536E+10 | 0.592047E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.797954E+10 | 0.427440E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.747430E+10 | 0.345253E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.822297E+10 | 0.228198E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.102184E+11 | 0.188229E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117559E+11 | 0.213503E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116683E+11 | 0.295949E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.115532E+11 | 0.434144E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.930079E+10 | 0.541367E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.772049E+10 | 0.742866E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113671E+12 | 0.547947E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.747430E+10 | 0.188229E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117559E+11 | 0.873042E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861749E+09 | 0.648962E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.198811E+10 | 0.429085E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.293703E+10 | 0.399718E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.451799E+10 | 0.285482E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.632391E+10 | 0.231781E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.744620E+10 | 0.154481E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.855363E+10 | 0.133899E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.706551E+10 | 0.144558E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.506497E+10 | 0.196423E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.314648E+10 | 0.293950E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.173714E+10 | 0.390436E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.826068E+09 | 0.549698E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.504688E+11 | 0.385847E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.826068E+09 | 0.133899E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.855363E+10 | 0.648962E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59127059.33 | 0.964311E+10 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.340190E+09 | 0.634837E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.110622E+10 | 0.560069E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.178898E+10 | 0.377585E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.321993E+10 | 0.295496E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.485099E+10 | 0.191186E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.540147E+10 | 0.167283E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.394904E+10 | 0.188394E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.230798E+10 | 0.266667E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.104303E+10 | 0.394849E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.270563E+09 | 0.554557E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 28777957.44 | 0.814453E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243663E+11 | 0.540969E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 28777957.44 | 0.167283E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.540147E+10 | 0.964311E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102938E+10 | 0.593010E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.204248E+10 | 0.390973E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.327833E+10 | 0.354492E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.473112E+10 | 0.245092E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.573379E+10 | 0.200565E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.819151E+10 | 0.132279E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.956325E+10 | 0.113351E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.812374E+10 | 0.126478E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.508891E+10 | 0.171353E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.322897E+10 | 0.251261E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.148612E+10 | 0.340478E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.814734E+09 | 0.500011E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.533123E+11 | 0.341934E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.814734E+09 | 0.113351E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.956325E+10 | 0.593010E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.801711E+10 | 0.834737E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.101066E+11 | 0.564916E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.996859E+10 | 0.557337E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.807238E+10 | 0.398484E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.752120E+10 | 0.326274E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.822587E+10 | 0.222007E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.101984E+11 | 0.185918E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117399E+11 | 0.209335E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116881E+11 | 0.282631E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.116588E+11 | 0.401040E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.945151E+10 | 0.500225E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.783481E+10 | 0.704172E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114483E+12 | 0.518708E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.752120E+10 | 0.185918E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117399E+11 | 0.834737E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.884481E+09 | 0.626046E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.202371E+10 | 0.410073E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.298160E+10 | 0.379732E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.457082E+10 | 0.268534E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.634868E+10 | 0.220284E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.744566E+10 | 0.150881E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.854154E+10 | 0.132493E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.706222E+10 | 0.141973E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.508144E+10 | 0.187961E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.320360E+10 | 0.273480E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.178111E+10 | 0.365241E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.846095E+09 | 0.526802E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.507710E+11 | 0.368350E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.846095E+09 | 0.132493E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.854154E+10 | 0.626046E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.436859E+11 | -0.426369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104892E+10 | 58.99 | 0.00 | 0.00 |
February | 0.403610E+11 | -0.394250E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -935960464.6 | 58.98 | 0.00 | 0.00 |
March | 0.469302E+11 | -0.458978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103240E+10 | 58.98 | 0.00 | 0.00 |
April | 0.410870E+11 | -0.400940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992974006.6 | 58.98 | 0.00 | 0.00 |
May | 0.414898E+11 | -0.404645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102530E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386219E+11 | -0.376295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992388715.7 | 58.98 | 0.00 | 0.00 |
July | 0.349796E+11 | -0.339604E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101919E+10 | 58.98 | 0.00 | 0.00 |
August | 0.373659E+11 | -0.363426E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102329E+10 | 58.97 | 0.00 | 0.00 |
September | 0.344094E+11 | -0.334210E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988419292.2 | 58.97 | 0.00 | 0.00 |
October | 0.371110E+11 | -0.360906E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102036E+10 | 58.97 | 0.00 | 0.00 |
November | 0.386508E+11 | -0.376621E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988774192.4 | 58.97 | 0.00 | 0.00 |
December | 0.408244E+11 | -0.397945E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102987E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475517E+12 | -0.463419E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120979E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344094E+11 | -0.458978E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104892E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469302E+11 | -0.334210E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -935960464.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.598126E+11 | 103258.03 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329097E+11 | 96883.97 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179924E+11 | 83854.98 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.410754E+10 | 45516.70 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293158E+10 | 36392.75 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113068E+09 | 15446.64 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.887931E+09 | 20886.20 | 19-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336346E+10 | 36211.44 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120175E+11 | 65676.18 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341690E+11 | 99810.91 | 29-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.598126E+11 | 103258.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332737E+10 | 15095.78 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999054E+09 | 14780.47 | 11-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226301E+09 | 13965.28 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2064419.59 | 1069.71 | 08-MAY-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121006E+09 | 13976.57 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763495E+09 | 14087.99 | 28-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332737E+10 | 15095.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319889E+10 | 15822.69 | 31-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132125E+10 | 16122.39 | 11-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474191E+09 | 16019.40 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55376055.64 | 10551.11 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32357541.16 | 5192.24 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3638105.76 | 693.23 | 19-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41101978.97 | 3251.03 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443701E+09 | 15808.10 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150060E+10 | 16229.06 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319889E+10 | 16229.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376151E+10 | 23190.29 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126099E+10 | 23168.48 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503285E+09 | 21920.59 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67137452.68 | 19166.52 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109038E+09 | 23218.64 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8810060.62 | 1868.11 | 19-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49896257.70 | 18451.36 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448435E+09 | 23193.84 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137629E+10 | 23191.86 | 18-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376151E+10 | 23218.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237616E+10 | 15111.00 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502363E+09 | 15094.49 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66993328.60 | 15096.08 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7039226.47 | 2008.44 | 22-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36410700.46 | 15095.70 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178336E+09 | 15090.78 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237616E+10 | 15111.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.732674E+12 | 1116038.05 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453617E+12 | 1033935.17 | 01-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318381E+12 | 902358.33 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114583E+12 | 524517.79 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736923E+11 | 420036.32 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.587426E+10 | 263744.73 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101762E+09 | 46946.95 | 08-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156477E+10 | 99720.32 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239898E+11 | 272706.04 | 19-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858357E+11 | 512196.41 | 10-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231761E+12 | 722960.93 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527710E+12 | 1077860.06 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256978E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.101762E+09 | 46946.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.732674E+12 | 1116038.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114457E+11 | 638713.16 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264673E+10 | 638242.19 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118914E+10 | 638051.46 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.572816E+09 | 636084.74 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315899E+10 | 638254.04 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114457E+11 | 638713.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.988770E+11 | 149171.20 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.496007E+11 | 134288.26 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246844E+11 | 142493.18 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.438396E+10 | 142067.30 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310571E+10 | 141546.92 | 23-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751293E+09 | 142549.56 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378379E+10 | 142518.13 | 05-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244530E+11 | 142553.15 | 03-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629701E+11 | 133352.59 | 29-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.988770E+11 | 149171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.769324E+11 | 183650.11 | 09-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395949E+11 | 183680.49 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230549E+11 | 183604.57 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607023E+10 | 181786.76 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.408077E+10 | 195135.09 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136484E+09 | 22996.44 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47016913.46 | 24519.21 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164619E+10 | 113690.42 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.590571E+10 | 181789.35 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248178E+11 | 195373.95 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.540810E+11 | 184086.55 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769324E+11 | 195373.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.751244E+11 | 222094.62 | 11-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326027E+11 | 222111.06 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204196E+11 | 222021.28 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595492E+10 | 231278.11 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.524114E+10 | 237546.30 | 23-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171194E+09 | 31183.35 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79734081.64 | 30318.20 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106518E+10 | 125110.39 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300702E+10 | 220392.92 | 10-OCT-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193785E+11 | 222051.58 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461490E+11 | 222756.95 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.751244E+11 | 237546.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.732064E+11 | 196437.35 | 30-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359387E+11 | 196545.11 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217386E+11 | 196463.61 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.538954E+10 | 194525.75 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.385823E+10 | 200634.66 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174175E+09 | 33135.90 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98914955.83 | 29345.36 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170238E+10 | 102504.55 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.547610E+10 | 195276.21 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215513E+11 | 196491.11 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473173E+11 | 195411.67 | 26-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.732064E+11 | 200634.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.840420E+11 | 120651.26 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530162E+11 | 111640.67 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416783E+11 | 101065.17 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181895E+11 | 60853.53 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116148E+11 | 48447.44 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145143E+10 | 31490.23 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73515691.36 | 9463.88 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.537851E+09 | 15822.51 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.510892E+10 | 33289.99 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141097E+11 | 58577.97 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306745E+11 | 78733.27 | 27-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629578E+11 | 114954.04 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 73515691.36 | 9463.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.840420E+11 | 120651.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146453E+11 | 80063.48 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582507E+10 | 80054.93 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311099E+10 | 79764.64 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264987E+09 | 79011.81 | 10-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.833293E+09 | 80037.98 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.455101E+09 | 80039.38 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356752E+10 | 79723.43 | 13-NOV-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.851134E+10 | 79781.42 | 04-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146453E+11 | 80063.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183300E+11 | 20284.94 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102936E+11 | 17059.64 | 01-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699638E+10 | 16809.03 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237264E+10 | 16814.08 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164291E+10 | 16812.57 | 01-MAY-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72822313.18 | 16721.55 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43449564.28 | 16725.99 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.717703E+09 | 16785.53 | 20-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.241585E+10 | 16858.93 | 10-OCT-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724039E+10 | 16814.77 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138130E+11 | 18413.67 | 29-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183300E+11 | 20284.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125262E+11 | 18433.85 | 12-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675626E+10 | 18437.24 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465918E+10 | 18434.64 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169328E+10 | 18375.63 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116962E+10 | 18483.73 | 08-MAY-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76866765.43 | 17246.63 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5261980.32 | 1808.17 | 05-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47357987.32 | 12471.23 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579177E+09 | 18349.91 | 13-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169254E+10 | 18362.82 | 05-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511558E+10 | 18483.41 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963865E+10 | 18435.40 | 19-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5261980.32 | 1808.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125262E+11 | 18483.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141282E+11 | 24445.88 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684228E+10 | 24003.30 | 14-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.533144E+10 | 23998.89 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226349E+10 | 23906.05 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184725E+10 | 24088.76 | 08-MAY-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.211037E+09 | 23872.35 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10549064.50 | 1971.90 | 08-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77580503.02 | 19337.98 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668820E+09 | 23969.78 | 19-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163020E+10 | 24093.59 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499922E+10 | 24087.73 | 29-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102046E+11 | 23999.86 | 19-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10549064.50 | 1971.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141282E+11 | 24445.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122185E+11 | 20968.33 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628770E+10 | 20971.14 | 17-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.465143E+10 | 20958.67 | 04-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172115E+10 | 20882.84 | 19-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122496E+10 | 20953.51 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150772E+09 | 11483.35 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1526320.81 | 320.72 | 08-JUL-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70027111.04 | 12299.81 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.687166E+09 | 20837.88 | 19-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180353E+10 | 20945.69 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462646E+10 | 20962.82 | 14-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855086E+10 | 20968.76 | 04-DEC-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1526320.81 | 320.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122185E+11 | 20971.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319450E+09 | 23714.12 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319450E+09 | 23714.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.668222E+09 | 0.668222E+09 | 44378.93 | 27-FEB-15:30 | 44378.93 | 0.00 |
March | 0.00 | 0.00 | 47762575.90 | 47762575.90 | 9966.38 | 14-MAR-13:30 | 9966.38 | 0.00 |
April | 0.00 | 0.00 | 0.684875E+10 | 0.684875E+10 | 86545.32 | 07-APR-14:00 | 86545.32 | 0.00 |
May | 0.00 | 0.00 | 0.187044E+11 | 0.187044E+11 | 117249.50 | 19-MAY-15:20 | 117249.50 | 0.02 |
June | 0.00 | 0.00 | 0.621322E+11 | 0.620638E+11 | 137820.64 | 29-JUN-14:50 | 137820.64 | 0.19 |
July | 0.00 | 0.00 | 0.106594E+12 | 0.106443E+12 | 164290.46 | 17-JUL-15:40 | 164290.46 | 0.30 |
August | 0.00 | 0.00 | 0.982073E+11 | 0.982073E+11 | 162762.80 | 07-AUG-15:20 | 162762.80 | 0.14 |
September | 0.00 | 0.00 | 0.400732E+11 | 0.386793E+11 | 201959.36 | 07-SEP-15:00 | 106758.95 | 0.12 |
October | 0.00 | 0.00 | 0.108484E+11 | 0.108484E+11 | 103923.85 | 18-OCT-15:50 | 103923.85 | 0.00 |
November | 0.00 | 0.00 | 0.603942E+09 | 0.603942E+09 | 19068.72 | 17-NOV-17:00 | 19068.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344728E+12 | 0.343114E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106594E+12 | 0.106443E+12 | 201959.36 | 164290.46 | 0.30 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12346.86 | 12346.86 | 3.72 | 02-JAN-05:24 | 3.72 | 0.00 |
February | 0.00 | 0.00 | 0.481262E+10 | 0.481262E+10 | 317620.76 | 27-FEB-13:50 | 317620.76 | 0.00 |
March | 0.00 | 0.00 | 0.149095E+09 | 0.149095E+09 | 45260.37 | 14-MAR-13:30 | 45260.37 | 0.00 |
April | 0.00 | 0.00 | 0.487552E+11 | 0.487552E+11 | 668693.39 | 06-APR-16:00 | 668693.39 | 0.00 |
May | 0.00 | 0.00 | 0.159328E+12 | 0.159328E+12 | 1124859.96 | 19-MAY-15:20 | 1124859.96 | 0.02 |
June | 0.00 | 0.00 | 0.531036E+12 | 0.530444E+12 | 1312498.82 | 29-JUN-14:50 | 1312498.82 | 0.18 |
July | 0.00 | 0.00 | 0.891038E+12 | 0.890185E+12 | 1518576.57 | 17-JUL-15:40 | 1518576.57 | 0.27 |
August | 0.00 | 0.00 | 0.771346E+12 | 0.771346E+12 | 1410966.27 | 10-AUG-15:40 | 1410966.27 | 0.12 |
September | 0.00 | 0.00 | 0.351058E+12 | 0.338388E+12 | 1874627.15 | 07-SEP-15:00 | 992409.20 | 0.12 |
October | 0.00 | 0.00 | 0.856662E+11 | 0.856662E+11 | 885272.71 | 18-OCT-15:10 | 885272.71 | 0.00 |
November | 0.00 | 0.00 | 0.429216E+10 | 0.429216E+10 | 152718.07 | 03-NOV-14:00 | 152718.07 | 0.00 |
December | 0.00 | 0.00 | 18227.04 | 18227.04 | 4.72 | 14-DEC-05:01 | 4.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.284748E+13 | 0.283337E+13 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 12346.86 | 12346.86 | 3.72 | 3.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.891038E+12 | 0.890185E+12 | 1874627.15 | 1518576.57 | 0.27 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2274.08 | 2274.08 | 0.71 | 11-JAN-06:08 | 0.71 | 0.00 |
February | 0.00 | 0.00 | 0.324425E+09 | 0.324425E+09 | 21826.99 | 27-FEB-15:30 | 21826.99 | 0.00 |
March | 0.00 | 0.00 | 2489376.22 | 2489376.22 | 696.31 | 14-MAR-14:00 | 696.31 | 0.00 |
April | 0.00 | 0.00 | 0.450198E+10 | 0.450198E+10 | 66876.09 | 06-APR-16:00 | 66876.09 | 0.00 |
May | 0.00 | 0.00 | 0.163879E+11 | 0.163879E+11 | 132937.35 | 19-MAY-15:30 | 132937.35 | 0.02 |
June | 0.00 | 0.00 | 0.578964E+11 | 0.578252E+11 | 155101.84 | 29-JUN-15:00 | 155101.84 | 0.17 |
July | 0.00 | 0.00 | 0.981358E+11 | 0.980708E+11 | 185803.12 | 17-JUL-15:30 | 185803.12 | 0.27 |
August | 0.00 | 0.00 | 0.826728E+11 | 0.826728E+11 | 167623.81 | 07-AUG-15:50 | 167623.81 | 0.11 |
September | 0.00 | 0.00 | 0.357250E+11 | 0.344700E+11 | 191018.01 | 07-SEP-15:20 | 109280.12 | 0.11 |
October | 0.00 | 0.00 | 0.731607E+10 | 0.731607E+10 | 90887.39 | 18-OCT-15:00 | 90887.39 | 0.00 |
November | 0.00 | 0.00 | 0.304082E+09 | 0.304082E+09 | 11133.88 | 17-NOV-17:00 | 11133.88 | 0.00 |
December | 0.00 | 0.00 | 10175.89 | 10175.89 | 69.91 | 04-DEC-04:46 | 69.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303267E+12 | 0.301876E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 2274.08 | 2274.08 | 0.71 | 0.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.981358E+11 | 0.980708E+11 | 191018.01 | 185803.12 | 0.27 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.282783E+09 | 0.282783E+09 | 24820.80 | 27-FEB-15:00 | 24820.80 | 0.00 |
March | 0.00 | 0.00 | 13603.64 | 13603.64 | 22.67 | 07-MAR-19:50 | 22.67 | 0.00 |
April | 0.00 | 0.00 | 0.245389E+10 | 0.245389E+10 | 50035.33 | 07-APR-14:00 | 50035.33 | 0.00 |
May | 0.00 | 0.00 | 0.921493E+10 | 0.921493E+10 | 79182.78 | 29-MAY-15:02 | 79182.78 | 0.02 |
June | 0.00 | 0.00 | 0.318869E+11 | 0.318637E+11 | 68420.25 | 26-JUN-11:00 | 68420.25 | 0.14 |
July | 0.00 | 0.00 | 0.540153E+11 | 0.539751E+11 | 119516.51 | 19-JUL-03:02 | 75800.38 | 0.24 |
August | 0.00 | 0.00 | 0.502708E+11 | 0.502698E+11 | 105211.96 | 06-AUG-15:54 | 105211.96 | 0.14 |
September | 0.00 | 0.00 | 0.210305E+11 | 0.206158E+11 | 109241.30 | 04-SEP-08:62 | 109241.30 | 0.10 |
October | 0.00 | 0.00 | 0.595290E+10 | 0.595290E+10 | 60329.65 | 18-OCT-14:00 | 60329.65 | 0.00 |
November | 0.00 | 0.00 | 91667054.30 | 91667054.30 | 28477.05 | 17-NOV-06:03 | 28477.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175200E+12 | 0.174721E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.540153E+11 | 0.539751E+11 | 119516.51 | 109241.30 | 0.24 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361909E+12 | 0.328250E+12 | 142962.30 | 18-JAN-22:01 | 128986.99 | 0.00 |
February | 0.00 | 0.00 | 0.575784E+12 | 0.522013E+12 | 245399.65 | 27-FEB-22:03 | 222099.61 | 0.00 |
March | 0.00 | 0.00 | 0.910685E+12 | 0.827825E+12 | 440877.89 | 31-MAR-24:00 | 400397.01 | 0.00 |
April | 0.00 | 0.00 | 0.114524E+13 | 0.104328E+13 | 449754.83 | 24-APR-21:02 | 407450.27 | 0.00 |
May | 0.00 | 0.00 | 0.375786E+12 | 0.342806E+12 | 238081.21 | 31-MAY-24:00 | 217599.45 | 0.00 |
June | 0.00 | 0.00 | 0.620356E+12 | 0.573415E+12 | 330267.18 | 30-JUN-23:02 | 309028.28 | 0.00 |
July | 0.00 | 0.00 | 0.894926E+12 | 0.842158E+12 | 427134.26 | 31-JUL-24:00 | 400767.91 | 0.00 |
August | 0.00 | 0.00 | 0.116139E+13 | 0.108102E+13 | 456799.34 | 04-AUG-00:25 | 411584.40 | 0.00 |
September | 0.00 | 0.00 | 0.366932E+12 | 0.336771E+12 | 238747.67 | 30-SEP-24:00 | 217327.62 | 0.00 |
October | 0.00 | 0.00 | 0.649209E+12 | 0.590738E+12 | 340967.62 | 31-OCT-24:00 | 309926.37 | 0.00 |
November | 0.00 | 0.00 | 0.889825E+12 | 0.806765E+12 | 349084.27 | 06-NOV-22:03 | 315595.10 | 0.00 |
December | 0.00 | 0.00 | 0.118270E+13 | 0.107455E+13 | 448640.98 | 07-DEC-24:00 | 406798.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.913475E+13 | 0.836959E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.361909E+12 | 0.328250E+12 | 142962.30 | 128986.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118270E+13 | 0.108102E+13 | 456799.34 | 411584.40 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.289943E+10 | 0.289911E+10 | 2188.32 | 13-JAN-16:20 | 2188.32 | 0.00 |
February | 0.00 | 0.00 | 0.819962E+10 | 0.819962E+10 | 4834.21 | 26-FEB-17:14 | 4834.21 | 0.00 |
March | 0.00 | 0.00 | 0.148985E+11 | 0.148985E+11 | 7467.03 | 31-MAR-24:00 | 7467.03 | 0.00 |
April | 0.00 | 0.00 | 0.199971E+11 | 0.199896E+11 | 8873.66 | 22-APR-18:10 | 8873.66 | 0.00 |
May | 0.00 | 0.00 | 0.559262E+10 | 0.557105E+10 | 4139.15 | 31-MAY-24:00 | 4139.15 | 0.00 |
June | 0.00 | 0.00 | 0.108705E+11 | 0.107904E+11 | 5991.51 | 30-JUN-24:00 | 5991.51 | 0.00 |
July | 0.00 | 0.00 | 0.165395E+11 | 0.164503E+11 | 7871.64 | 31-JUL-23:35 | 7871.64 | 0.00 |
August | 0.00 | 0.00 | 0.215283E+11 | 0.214652E+11 | 8850.50 | 05-AUG-20:12 | 8850.50 | 0.00 |
September | 0.00 | 0.00 | 0.567817E+10 | 0.559615E+10 | 3948.60 | 30-SEP-24:00 | 3948.60 | 0.00 |
October | 0.00 | 0.00 | 0.105001E+11 | 0.104895E+11 | 5598.15 | 31-OCT-24:00 | 5598.15 | 0.00 |
November | 0.00 | 0.00 | 0.145875E+11 | 0.145858E+11 | 6496.40 | 03-NOV-16:00 | 6441.50 | 0.00 |
December | 0.00 | 0.00 | 0.194587E+11 | 0.194584E+11 | 8260.01 | 10-DEC-16:10 | 8260.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150750E+12 | 0.150394E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.289943E+10 | 0.289911E+10 | 2188.32 | 2188.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215283E+11 | 0.214652E+11 | 8873.66 | 8873.66 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.830672E+10 | 0.830364E+10 | 18012.41 | 13-JAN-16:30 | 18012.41 | 0.00 |
February | 0.00 | 0.00 | 0.591940E+11 | 0.591940E+11 | 42648.69 | 28-FEB-17:00 | 42648.69 | 0.00 |
March | 0.00 | 0.00 | 0.124458E+12 | 0.124458E+12 | 65300.66 | 31-MAR-23:30 | 65300.66 | 0.00 |
April | 0.00 | 0.00 | 0.179736E+12 | 0.179659E+12 | 82415.87 | 25-APR-18:00 | 82415.87 | 0.00 |
May | 0.00 | 0.00 | 0.453476E+11 | 0.451359E+11 | 39148.00 | 31-MAY-24:00 | 39148.00 | 0.00 |
June | 0.00 | 0.00 | 0.100138E+12 | 0.993392E+11 | 58470.88 | 30-JUN-24:00 | 58470.88 | 0.00 |
July | 0.00 | 0.00 | 0.156279E+12 | 0.155387E+12 | 76721.69 | 31-JUL-23:55 | 76721.69 | 0.00 |
August | 0.00 | 0.00 | 0.202432E+12 | 0.201800E+12 | 84091.67 | 03-AUG-19:00 | 84091.67 | 0.00 |
September | 0.00 | 0.00 | 0.479241E+11 | 0.471217E+11 | 34913.64 | 30-SEP-23:40 | 34913.64 | 0.00 |
October | 0.00 | 0.00 | 0.877932E+11 | 0.876879E+11 | 47671.08 | 31-OCT-24:00 | 47671.08 | 0.00 |
November | 0.00 | 0.00 | 0.120788E+12 | 0.120770E+12 | 59983.80 | 03-NOV-16:00 | 59435.75 | 0.00 |
December | 0.00 | 0.00 | 0.158815E+12 | 0.158812E+12 | 74768.39 | 06-DEC-16:10 | 74485.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129121E+13 | 0.128767E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.830672E+10 | 0.830364E+10 | 18012.41 | 18012.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202432E+12 | 0.201800E+12 | 84091.67 | 84091.67 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.230045E+09 | 0.230045E+09 | 1717.40 | 13-JAN-16:30 | 1717.40 | 0.00 |
February | 0.00 | 0.00 | 0.427029E+10 | 0.427029E+10 | 4220.91 | 28-FEB-17:00 | 4220.91 | 0.00 |
March | 0.00 | 0.00 | 0.108040E+11 | 0.108040E+11 | 6164.11 | 28-MAR-17:50 | 6164.11 | 0.00 |
April | 0.00 | 0.00 | 0.168079E+11 | 0.168004E+11 | 8308.89 | 25-APR-18:00 | 8308.89 | 0.00 |
May | 0.00 | 0.00 | 0.386146E+10 | 0.384062E+10 | 3843.15 | 31-MAY-24:00 | 3843.15 | 0.00 |
June | 0.00 | 0.00 | 0.980741E+10 | 0.972772E+10 | 5857.38 | 30-JUN-24:00 | 5857.38 | 0.00 |
July | 0.00 | 0.00 | 0.155838E+11 | 0.154948E+11 | 7631.69 | 31-JUL-23:55 | 7631.69 | 0.00 |
August | 0.00 | 0.00 | 0.201183E+11 | 0.200552E+11 | 8557.07 | 05-AUG-19:57 | 8557.07 | 0.00 |
September | 0.00 | 0.00 | 0.425735E+10 | 0.417828E+10 | 3403.05 | 04-SEP-17:32 | 3403.05 | 0.00 |
October | 0.00 | 0.00 | 0.739448E+10 | 0.738418E+10 | 4565.94 | 18-OCT-16:50 | 4565.94 | 0.00 |
November | 0.00 | 0.00 | 0.101922E+11 | 0.101905E+11 | 5935.38 | 03-NOV-16:00 | 5880.69 | 0.00 |
December | 0.00 | 0.00 | 0.138238E+11 | 0.138235E+11 | 7386.01 | 06-DEC-16:10 | 7359.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117151E+12 | 0.116800E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.230045E+09 | 0.230045E+09 | 1717.40 | 1717.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201183E+11 | 0.200552E+11 | 8557.07 | 8557.07 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 480023.47 | 2527902.40 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 303164.77 | 2015123.65 | 01-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 183234.93 | 1911868.99 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 63893.97 | 1281219.27 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 41209.60 | 1451349.99 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3222.62 | 342073.22 | 16-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 70.17 | 56890.50 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 951.21 | 151553.94 | 18-AUG-06:05 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 14460.37 | 740681.87 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 47974.42 | 1275256.03 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 149839.85 | 1661552.86 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 330493.89 | 2057964.46 | 29-DEC-07:03 |
Annual Sum or Average | 0.00 | 134339.20 | ||||
Minimum of Months | 0.00 | 0.00 | 70.17 | 56890.50 | ||
Maximum of Months | 0.00 | 0.00 | 480023.47 | 2527902.40 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 305.84 | 23912.03 | 25-JAN-05:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5693.53 | 826197.23 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 825.67 | 152822.36 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46551.88 | 1213503.56 | 07-APR-12:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 133338.71 | 1456136.29 | 19-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 363351.68 | 1684751.88 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 556560.39 | 1966244.79 | 17-JUL-15:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 482858.86 | 2019470.65 | 07-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 263757.44 | 2704073.55 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 70926.62 | 1218008.98 | 16-OCT-12:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5550.35 | 362823.85 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 264.85 | 23960.44 | 04-DEC-04:46 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 162008.96 | 0.00 | ||||
Minimum of Months | 264.85 | 23912.03 | 0.00 | 0.00 | ||
Maximum of Months | 556560.39 | 2704073.55 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2647.44 | 445040.33 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 92.70 | 67616.28 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26208.98 | 947434.34 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82155.35 | 1445921.39 | 19-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 281583.70 | 1675261.25 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 453509.67 | 1957819.28 | 17-JUL-15:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 393777.54 | 2035012.82 | 07-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 186087.32 | 2531478.16 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 44595.02 | 1206972.75 | 18-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2160.65 | 180549.92 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.01 | 75.24 | 04-DEC-04:46 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123707.91 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 453509.67 | 2531478.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 178882.23 | 203101.59 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 339929.93 | 609079.57 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 496669.48 | 646691.25 | 31-MAR-24:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 703935.88 | 1327720.89 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 257135.32 | 975040.46 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 575841.98 | 1377905.50 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 970669.83 | 1956865.43 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1125235.96 | 2072271.40 | 06-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 339770.54 | 1245137.13 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 387310.63 | 961169.91 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 506782.82 | 750693.74 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 640662.97 | 768649.98 | 10-DEC-02:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 545374.06 | 0.00 | ||||
Minimum of Months | 178882.23 | 203101.59 | 0.00 | 0.00 | ||
Maximum of Months | 1125235.96 | 2072271.40 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17320.88 | 58837.17 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17697.89 | 59145.27 | 16-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18534.81 | 59081.24 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16871.72 | 57467.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16514.02 | 54935.49 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15920.98 | 51670.33 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14087.26 | 48630.05 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14974.26 | 46956.75 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 14302.61 | 48062.99 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14888.17 | 50858.03 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15938.81 | 54021.94 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16263.11 | 56856.14 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16100.34 | ||||
Minimum of Months | 0.00 | 0.00 | 14087.26 | 46956.75 | ||
Maximum of Months | 0.00 | 0.00 | 18534.81 | 59145.27 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.65 | 13877.38 | 25-JAN-05:42 | 314.51 | 101747.55 | 17-JAN-06:30 |
February | 2785.11 | 495057.03 | 27-FEB-15:30 | 521.01 | 104307.37 | 20-FEB-04:30 |
March | 31.14 | 23677.28 | 01-MAR-07:00 | 713.37 | 120998.68 | 21-MAR-05:30 |
April | 29179.71 | 932905.12 | 06-APR-16:00 | 1171.11 | 99930.25 | 14-APR-16:00 |
May | 95345.93 | 2281590.76 | 19-MAY-14:40 | 963.97 | 121002.38 | 06-MAY-05:30 |
June | 343872.09 | 2881577.65 | 20-JUN-15:20 | 640.58 | 86472.28 | 02-JUN-05:30 |
July | 574789.11 | 3012469.21 | 17-JUL-16:00 | 328.18 | 55923.47 | 29-JUL-06:30 |
August | 487455.53 | 2621173.96 | 07-AUG-15:30 | 941.10 | 63406.59 | 30-AUG-07:50 |
September | 237331.38 | 4551358.72 | 07-SEP-15:00 | 560.53 | 96544.40 | 16-SEP-06:00 |
October | 50561.47 | 1977586.91 | 18-OCT-12:20 | 1061.14 | 97708.60 | 31-OCT-10:00 |
November | 2556.07 | 240598.81 | 17-NOV-17:00 | 919.02 | 113422.72 | 29-NOV-05:30 |
December | 10.88 | 22090.58 | 20-DEC-07:00 | 280.48 | 113252.48 | 11-DEC-07:00 |
Annual Sum or Average | 153206.78 | 701.40 | ||||
Minimum of Months | 9.65 | 13877.38 | 280.48 | 55923.47 | ||
Maximum of Months | 574789.11 | 4551358.72 | 1171.11 | 121002.38 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174828E+11 | 0.96 | 11794.21 | 01-JAN-00:10 | 1.73 |
February | 0.155487E+11 | 0.94 | 11794.21 | 01-FEB-06:01 | 1.73 |
March | 0.187145E+11 | 1.02 | 11794.21 | 01-MAR-04:20 | 1.72 |
April | 0.174026E+11 | 0.98 | 11794.21 | 01-APR-04:01 | 1.73 |
May | 0.185322E+11 | 1.01 | 11794.21 | 01-MAY-03:05 | 1.73 |
June | 0.185411E+11 | 1.04 | 11794.21 | 01-JUN-03:02 | 1.71 |
July | 0.185708E+11 | 1.01 | 11794.21 | 01-JUL-03:02 | 1.71 |
August | 0.202277E+11 | 1.10 | 11794.21 | 01-AUG-03:02 | 1.71 |
September | 0.189750E+11 | 1.06 | 11794.21 | 01-SEP-03:02 | 1.71 |
October | 0.186655E+11 | 1.02 | 11794.21 | 01-OCT-23:40 | 1.72 |
November | 0.177535E+11 | 1.00 | 11794.21 | 01-NOV-03:10 | 1.73 |
December | 0.173201E+11 | 0.95 | 11794.21 | 01-DEC-05:01 | 1.73 |
Annual Sum or Average | 0.217734E+12 | 1.01 | |||
Minimum of Months | 0.155487E+11 | 0.94 | 11794.21 | 1.71 | |
Maximum of Months | 0.202277E+11 | 1.10 | 11794.21 | 1.73 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.469374E+10 | 0.38 | 15628.84 | 18-JAN-06:01 | 1.60 |
February | 0.527111E+10 | 0.41 | 16164.09 | 07-FEB-06:01 | 1.63 |
March | 0.785973E+10 | 0.48 | 14652.00 | 28-MAR-15:40 | 1.54 |
April | 0.966328E+10 | 0.55 | 20031.02 | 24-APR-15:00 | 1.86 |
May | 0.890906E+10 | 0.52 | 18710.42 | 30-MAY-05:03 | 1.78 |
June | 0.135143E+11 | 0.69 | 24654.76 | 21-JUN-05:03 | 2.11 |
July | 0.163002E+11 | 0.78 | 24654.76 | 18-JUL-05:02 | 2.12 |
August | 0.177722E+11 | 0.84 | 24654.76 | 07-AUG-04:02 | 2.12 |
September | 0.981073E+10 | 0.57 | 24654.76 | 05-SEP-05:03 | 2.12 |
October | 0.877571E+10 | 0.50 | 17440.54 | 16-OCT-16:00 | 1.71 |
November | 0.736984E+10 | 0.46 | 14960.79 | 06-NOV-14:50 | 1.56 |
December | 0.633126E+10 | 0.42 | 16164.09 | 23-DEC-06:01 | 1.64 |
Annual Sum or Average | 0.116271E+12 | 0.55 | |||
Minimum of Months | 0.469374E+10 | 0.38 | 14652.00 | 1.54 | |
Maximum of Months | 0.177722E+11 | 0.84 | 24654.76 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435905E+11 | 0.42 | 60836.23 | 09-JAN-05:11 | 0.96 |
February | 0.397318E+11 | 0.40 | 138182.32 | 28-FEB-06:02 | 1.55 |
March | 0.510296E+11 | 0.42 | 140044.96 | 02-MAR-06:02 | 1.57 |
April | 0.554782E+11 | 0.42 | 158627.52 | 19-APR-05:02 | 1.69 |
May | 0.667292E+11 | 0.46 | 176480.97 | 22-MAY-04:01 | 1.81 |
June | 0.104582E+12 | 0.61 | 221023.48 | 21-JUN-05:03 | 2.07 |
July | 0.122355E+12 | 0.64 | 210393.23 | 31-JUL-15:40 | 2.01 |
August | 0.119194E+12 | 0.64 | 228333.16 | 07-AUG-05:03 | 2.12 |
September | 0.762832E+11 | 0.50 | 228333.16 | 05-SEP-03:02 | 2.12 |
October | 0.570605E+11 | 0.41 | 143431.07 | 31-OCT-05:02 | 1.59 |
November | 0.452959E+11 | 0.39 | 150463.13 | 06-NOV-06:01 | 1.64 |
December | 0.432169E+11 | 0.40 | 60836.23 | 26-DEC-05:01 | 0.96 |
Annual Sum or Average | 0.824546E+12 | 0.48 | |||
Minimum of Months | 0.397318E+11 | 0.39 | 60836.23 | 0.96 | |
Maximum of Months | 0.122355E+12 | 0.64 | 228333.16 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.541981E+10 | 0.50 | 5635.22 | 02-JAN-04:11 | 0.86 |
February | 0.425912E+10 | 0.43 | 5635.22 | 01-FEB-05:01 | 0.87 |
March | 0.462097E+10 | 0.41 | 6227.97 | 28-MAR-15:50 | 0.91 |
April | 0.448921E+10 | 0.38 | 12819.31 | 25-APR-16:00 | 1.38 |
May | 0.580186E+10 | 0.42 | 18592.93 | 19-MAY-15:40 | 1.73 |
June | 0.977286E+10 | 0.55 | 21703.86 | 29-JUN-14:50 | 1.91 |
July | 0.120759E+11 | 0.60 | 25518.42 | 17-JUL-15:20 | 2.12 |
August | 0.111030E+11 | 0.58 | 24310.91 | 11-AUG-15:40 | 2.06 |
September | 0.645737E+10 | 0.44 | 17845.71 | 05-SEP-14:50 | 1.69 |
October | 0.438305E+10 | 0.36 | 10504.68 | 18-OCT-16:00 | 1.23 |
November | 0.423959E+10 | 0.40 | 5635.22 | 06-NOV-06:01 | 0.86 |
December | 0.498120E+10 | 0.46 | 5635.22 | 01-DEC-06:01 | 0.86 |
Annual Sum or Average | 0.776039E+11 | 0.46 | |||
Minimum of Months | 0.423959E+10 | 0.36 | 5635.22 | 0.86 | |
Maximum of Months | 0.120759E+11 | 0.60 | 25518.42 | 2.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108058E+12 | 1.54 | 40344.20 | 01-JAN-00:05 | 1.54 |
February | 0.976007E+11 | 1.54 | 40344.20 | 01-FEB-00:10 | 1.54 |
March | 0.108058E+12 | 1.54 | 40344.20 | 01-MAR-00:10 | 1.54 |
April | 0.104572E+12 | 1.54 | 40344.20 | 01-APR-00:10 | 1.54 |
May | 0.108058E+12 | 1.54 | 40344.20 | 01-MAY-00:10 | 1.54 |
June | 0.104572E+12 | 1.54 | 40344.20 | 01-JUN-00:10 | 1.54 |
July | 0.108058E+12 | 1.54 | 40344.20 | 01-JUL-00:10 | 1.54 |
August | 0.108058E+12 | 1.54 | 40344.20 | 01-AUG-00:03 | 1.54 |
September | 0.104572E+12 | 1.54 | 40344.20 | 01-SEP-00:06 | 1.54 |
October | 0.108058E+12 | 1.54 | 40344.20 | 01-OCT-00:10 | 1.54 |
November | 0.104572E+12 | 1.54 | 40344.20 | 01-NOV-00:10 | 1.54 |
December | 0.108058E+12 | 1.54 | 40344.20 | 01-DEC-00:10 | 1.54 |
Annual Sum or Average | 0.127229E+13 | 1.54 | |||
Minimum of Months | 0.976007E+11 | 1.54 | 40344.20 | 1.54 | |
Maximum of Months | 0.108058E+12 | 1.54 | 40344.20 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169392E+10 | 1.05 | 632.44 | 01-JAN-00:05 | 1.05 |
February | 0.152999E+10 | 1.05 | 632.44 | 01-FEB-00:10 | 1.05 |
March | 0.169392E+10 | 1.05 | 632.44 | 01-MAR-00:10 | 1.05 |
April | 0.163927E+10 | 1.05 | 632.44 | 01-APR-00:10 | 1.05 |
May | 0.169392E+10 | 1.05 | 632.44 | 01-MAY-00:10 | 1.05 |
June | 0.163927E+10 | 1.05 | 632.44 | 01-JUN-00:10 | 1.05 |
July | 0.169392E+10 | 1.05 | 632.44 | 01-JUL-00:10 | 1.05 |
August | 0.169392E+10 | 1.05 | 632.44 | 01-AUG-00:03 | 1.05 |
September | 0.163927E+10 | 1.05 | 632.44 | 01-SEP-00:02 | 1.05 |
October | 0.169392E+10 | 1.05 | 632.44 | 01-OCT-00:10 | 1.05 |
November | 0.163927E+10 | 1.05 | 632.44 | 01-NOV-00:10 | 1.05 |
December | 0.169392E+10 | 1.05 | 632.44 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.199445E+11 | 1.05 | |||
Minimum of Months | 0.152999E+10 | 1.05 | 632.44 | 1.05 | |
Maximum of Months | 0.169392E+10 | 1.05 | 632.44 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162084E+11 | 1.05 | 6051.52 | 01-JAN-00:10 | 1.05 |
February | 0.146398E+11 | 1.05 | 6051.52 | 01-FEB-00:25 | 1.05 |
March | 0.162084E+11 | 1.05 | 6051.52 | 01-MAR-00:10 | 1.05 |
April | 0.156855E+11 | 1.05 | 6051.52 | 01-APR-00:10 | 1.05 |
May | 0.162084E+11 | 1.05 | 6051.52 | 01-MAY-00:10 | 1.05 |
June | 0.156855E+11 | 1.05 | 6051.52 | 01-JUN-00:10 | 1.05 |
July | 0.162084E+11 | 1.05 | 6051.52 | 01-JUL-00:10 | 1.05 |
August | 0.162084E+11 | 1.05 | 6051.52 | 01-AUG-00:03 | 1.05 |
September | 0.156855E+11 | 1.05 | 6051.52 | 01-SEP-00:02 | 1.05 |
October | 0.162084E+11 | 1.05 | 6051.52 | 01-OCT-00:10 | 1.05 |
November | 0.156855E+11 | 1.05 | 6051.52 | 01-NOV-00:10 | 1.05 |
December | 0.162084E+11 | 1.05 | 6051.52 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.190841E+12 | 1.05 | |||
Minimum of Months | 0.146398E+11 | 1.05 | 6051.52 | 1.05 | |
Maximum of Months | 0.162084E+11 | 1.05 | 6051.52 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165013E+10 | 1.05 | 616.09 | 01-JAN-00:05 | 1.05 |
February | 0.149044E+10 | 1.05 | 616.09 | 01-FEB-00:10 | 1.05 |
March | 0.165013E+10 | 1.05 | 616.09 | 01-MAR-00:10 | 1.05 |
April | 0.159690E+10 | 1.05 | 616.09 | 01-APR-00:10 | 1.05 |
May | 0.165013E+10 | 1.05 | 616.09 | 01-MAY-00:10 | 1.05 |
June | 0.159690E+10 | 1.05 | 616.09 | 01-JUN-00:20 | 1.05 |
July | 0.165013E+10 | 1.05 | 616.09 | 01-JUL-00:10 | 1.05 |
August | 0.165013E+10 | 1.05 | 616.09 | 01-AUG-00:03 | 1.05 |
September | 0.159690E+10 | 1.05 | 616.09 | 01-SEP-00:02 | 1.05 |
October | 0.165013E+10 | 1.05 | 616.09 | 01-OCT-00:10 | 1.05 |
November | 0.159690E+10 | 1.05 | 616.09 | 01-NOV-00:10 | 1.05 |
December | 0.165013E+10 | 1.05 | 616.09 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.194289E+11 | 1.05 | |||
Minimum of Months | 0.149044E+10 | 1.05 | 616.09 | 1.05 | |
Maximum of Months | 0.165013E+10 | 1.05 | 616.09 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.544035E+10 | 0.489631E+10 | 7120.99 | 09-JAN-07:06 | 6408.89 | 6408.89 | 50.51 | 18.21 |
February | 0.315889E+10 | 0.284300E+10 | 6632.89 | 01-FEB-07:10 | 5969.60 | 5969.60 | 51.41 | 13.65 |
March | 0.209107E+10 | 0.188196E+10 | 6405.33 | 06-MAR-07:03 | 5764.80 | 5764.80 | 45.93 | 12.31 |
April | 0.692171E+09 | 0.622954E+09 | 4811.40 | 29-APR-05:01 | 4330.26 | 4330.26 | 38.14 | 6.99 |
May | 0.463238E+09 | 0.416914E+09 | 4793.01 | 09-MAY-05:01 | 4313.71 | 4313.71 | 37.30 | 6.95 |
June | 33884191.38 | 30495772.24 | 1420.56 | 16-JUN-07:00 | 1278.50 | 1278.50 | 30.11 | 1.56 |
July | 745908.91 | 671318.02 | 224.40 | 08-JUL-06:10 | 201.96 | 201.96 | 23.18 | 0.23 |
August | 10087189.47 | 9078470.53 | 589.75 | 18-AUG-06:05 | 530.78 | 530.78 | 23.51 | 0.62 |
September | 0.153087E+09 | 0.137778E+09 | 2954.53 | 19-SEP-05:03 | 2659.08 | 2659.08 | 32.79 | 3.60 |
October | 0.535079E+09 | 0.481571E+09 | 4574.99 | 11-OCT-05:01 | 4117.49 | 4117.49 | 34.85 | 6.47 |
November | 0.163936E+10 | 0.147542E+10 | 6301.46 | 27-NOV-06:01 | 5671.32 | 5671.32 | 48.21 | 11.76 |
December | 0.377872E+10 | 0.340085E+10 | 6805.02 | 29-DEC-08:00 | 6124.52 | 6124.52 | 52.38 | 14.95 |
Annual Sum or Average | 0.179967E+11 | 0.161970E+11 | ||||||
Minimum of Months | 745908.91 | 671318.02 | 224.40 | 201.96 | 201.96 | 23.18 | 0.23 | |
Maximum of Months | 0.544035E+10 | 0.489631E+10 | 7120.99 | 6408.89 | 6408.89 | 52.38 | 18.21 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 282.34 | 254.11 | 0.07 | 02-JAN-05:24 | 0.06 | 0.06 | 6.70 | 0.00 |
February | 90655806.83 | 81590226.15 | 6056.42 | 27-FEB-13:40 | 5450.78 | 5450.78 | 7.79 | 10.73 |
March | 4079062.29 | 3671156.06 | 1123.61 | 14-MAR-13:30 | 1011.25 | 1011.25 | 7.27 | 1.72 |
April | 0.816187E+09 | 0.734568E+09 | 8551.16 | 06-APR-16:00 | 7696.04 | 7696.04 | 7.42 | 16.71 |
May | 0.241263E+10 | 0.217137E+10 | 14273.89 | 19-MAY-16:00 | 12846.50 | 12846.50 | 6.77 | 43.53 |
June | 0.774509E+10 | 0.697058E+10 | 14891.69 | 23-JUN-14:00 | 13402.52 | 13402.52 | 6.76 | 51.08 |
July | 0.120772E+11 | 0.108695E+11 | 15697.36 | 17-JUL-16:00 | 14127.63 | 14127.63 | 6.75 | 64.30 |
August | 0.100916E+11 | 0.908245E+10 | 15570.82 | 07-AUG-15:40 | 14013.74 | 14013.74 | 6.75 | 62.26 |
September | 0.527761E+10 | 0.474985E+10 | 15092.84 | 01-SEP-16:00 | 13583.56 | 13583.56 | 6.76 | 54.19 |
October | 0.134166E+10 | 0.120749E+10 | 10427.14 | 18-OCT-14:00 | 9384.42 | 9384.42 | 7.22 | 22.39 |
November | 92582658.37 | 83324392.53 | 3373.25 | 03-NOV-14:00 | 3035.92 | 3035.92 | 7.26 | 5.49 |
December | 569.87 | 512.88 | 1.39 | 04-DEC-04:46 | 1.26 | 1.26 | 6.99 | 0.00 |
Annual Sum or Average | 0.399493E+11 | 0.359544E+11 | ||||||
Minimum of Months | 282.34 | 254.11 | 0.07 | 0.06 | 0.06 | 6.70 | 0.00 | |
Maximum of Months | 0.120772E+11 | 0.108695E+11 | 15697.36 | 14127.63 | 14127.63 | 7.79 | 64.30 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.458370E+09 | 0.412533E+09 | 13378.05 | 01-JAN-13:32 | 12040.24 | 12040.24 | 6.76 | 93.76 |
February | 0.114046E+10 | 0.102641E+10 | 13378.05 | 01-FEB-04:01 | 12040.24 | 12040.24 | 6.76 | 93.76 |
March | 0.960907E+09 | 0.864816E+09 | 13378.05 | 01-MAR-05:01 | 12040.24 | 12040.24 | 6.84 | 93.76 |
April | 0.477851E+10 | 0.430066E+10 | 13378.05 | 01-APR-12:05 | 12040.24 | 12040.24 | 6.76 | 93.76 |
May | 0.902122E+10 | 0.811910E+10 | 13378.05 | 01-MAY-13:20 | 12040.24 | 12040.24 | 6.76 | 93.76 |
June | 0.177539E+11 | 0.159785E+11 | 13378.05 | 01-JUN-03:02 | 12040.24 | 12040.24 | 7.37 | 93.76 |
July | 0.243272E+11 | 0.218944E+11 | 13378.05 | 01-JUL-00:12 | 12040.24 | 12040.24 | 6.90 | 93.76 |
August | 0.237696E+11 | 0.213926E+11 | 13378.05 | 01-AUG-00:03 | 12040.24 | 12040.24 | 6.86 | 93.76 |
September | 0.136526E+11 | 0.122873E+11 | 13378.05 | 01-SEP-00:02 | 12040.24 | 12040.24 | 6.83 | 93.76 |
October | 0.625064E+10 | 0.562558E+10 | 13378.05 | 02-OCT-05:05 | 12040.24 | 12040.24 | 7.67 | 93.76 |
November | 0.200266E+10 | 0.180240E+10 | 13378.05 | 01-NOV-04:01 | 12040.24 | 12040.24 | 6.88 | 93.76 |
December | 0.396898E+09 | 0.357208E+09 | 13378.05 | 01-DEC-04:33 | 12040.24 | 12040.24 | 6.76 | 93.76 |
Annual Sum or Average | 0.104513E+12 | 0.940616E+11 | ||||||
Minimum of Months | 0.396898E+09 | 0.357208E+09 | 13378.05 | 12040.24 | 12040.24 | 6.76 | 93.76 | |
Maximum of Months | 0.243272E+11 | 0.218944E+11 | 13378.05 | 12040.24 | 12040.24 | 7.67 | 93.76 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-JAN-00:05 | 3291.01 | 3291.01 | 21.85 | 15.27 |
February | 0.884624E+10 | 0.796162E+10 | 3656.68 | 01-FEB-00:10 | 3291.01 | 3291.01 | 24.25 | 15.27 |
March | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-MAR-00:10 | 3291.01 | 3291.01 | 27.43 | 15.27 |
April | 0.947812E+10 | 0.853031E+10 | 3656.68 | 01-APR-00:10 | 3291.01 | 3291.01 | 30.42 | 15.27 |
May | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-MAY-00:10 | 3291.01 | 3291.01 | 22.36 | 15.27 |
June | 0.947812E+10 | 0.853031E+10 | 3656.68 | 01-JUN-00:10 | 3291.01 | 3291.01 | 26.00 | 15.27 |
July | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-JUL-00:10 | 3291.01 | 3291.01 | 34.65 | 15.27 |
August | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-AUG-00:03 | 3291.01 | 3291.01 | 38.65 | 15.27 |
September | 0.947812E+10 | 0.853031E+10 | 3656.68 | 01-SEP-00:02 | 3291.01 | 3291.01 | 25.52 | 15.27 |
October | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-OCT-00:10 | 3291.01 | 3291.01 | 24.99 | 15.27 |
November | 0.947812E+10 | 0.853031E+10 | 3656.68 | 01-NOV-00:10 | 3291.01 | 3291.01 | 27.68 | 15.27 |
December | 0.979405E+10 | 0.881465E+10 | 3656.68 | 01-DEC-00:10 | 3291.01 | 3291.01 | 30.08 | 15.27 |
Annual Sum or Average | 0.115317E+12 | 0.103785E+12 | ||||||
Minimum of Months | 0.884624E+10 | 0.796162E+10 | 3656.68 | 3291.01 | 3291.01 | 21.85 | 15.27 | |
Maximum of Months | 0.979405E+10 | 0.881465E+10 | 3656.68 | 3291.01 | 3291.01 | 38.65 | 15.27 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 55.97 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 55.91 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 55.94 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:01 | 16.86 | 16.86 | 55.91 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.21 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.38 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.85 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.51 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 55.55 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.17 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 55.93 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.19 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.38 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.85 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.568770E+09 | 0.511893E+09 | 16602.14 | 25-JAN-05:42 | 14941.92 | 14941.92 | 21.16 | 55.31 |
February | 0.141553E+10 | 0.127398E+10 | 16627.01 | 27-FEB-15:30 | 14964.31 | 14964.31 | 23.24 | 55.31 |
March | 0.119234E+10 | 0.107310E+10 | 16602.64 | 01-MAR-07:00 | 14942.38 | 14942.38 | 21.20 | 55.31 |
April | 0.600335E+10 | 0.540302E+10 | 33242.93 | 06-APR-14:20 | 29918.63 | 29918.63 | 22.77 | 110.61 |
May | 0.119998E+11 | 0.107999E+11 | 33325.14 | 19-MAY-14:40 | 29992.62 | 29992.62 | 26.04 | 110.61 |
June | 0.268510E+11 | 0.241659E+11 | 33361.43 | 20-JUN-15:20 | 30025.29 | 30025.29 | 27.33 | 110.61 |
July | 0.395561E+11 | 0.356005E+11 | 33369.36 | 17-JUL-16:00 | 30032.42 | 30032.42 | 27.62 | 110.61 |
August | 0.375346E+11 | 0.337811E+11 | 33345.67 | 07-AUG-15:30 | 30011.10 | 30011.10 | 26.77 | 110.61 |
September | 0.195931E+11 | 0.176338E+11 | 33402.76 | 07-SEP-14:30 | 30062.49 | 30062.49 | 28.94 | 110.61 |
October | 0.819189E+10 | 0.737270E+10 | 33306.77 | 18-OCT-12:20 | 29976.10 | 29976.10 | 25.38 | 110.61 |
November | 0.248541E+10 | 0.223687E+10 | 16613.85 | 17-NOV-17:00 | 14952.46 | 14952.46 | 22.14 | 55.31 |
December | 0.492491E+09 | 0.443242E+09 | 16602.56 | 20-DEC-07:00 | 14942.31 | 14942.31 | 21.20 | 55.31 |
Annual Sum or Average | 0.155884E+12 | 0.140296E+12 | ||||||
Minimum of Months | 0.492491E+09 | 0.443242E+09 | 16602.14 | 14941.92 | 14941.92 | 21.16 | 55.31 | |
Maximum of Months | 0.395561E+11 | 0.356005E+11 | 33402.76 | 30062.49 | 30062.49 | 28.94 | 110.61 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35.81 | 35.81 | 480023.47 | 2527902.40 | 09-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 36.31 | 36.31 | 303164.77 | 2015123.65 | 01-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 31.63 | 31.63 | 183234.93 | 1911868.99 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 31.93 | 31.93 | 63893.97 | 1281219.27 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.20 | 82.00 | 41209.60 | 1451349.99 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.99 | 23.99 | 3222.62 | 342073.22 | 16-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.35 | 23.35 | 70.17 | 56890.50 | 08-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.95 | 22.95 | 951.21 | 151553.94 | 18-AUG-06:05 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 23.39 | 23.39 | 14460.37 | 740681.87 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.05 | 23.05 | 47974.42 | 1275256.03 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.21 | 32.21 | 149839.85 | 1661552.86 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34.74 | 34.74 | 330493.89 | 2057964.46 | 29-DEC-07:03 |
Annual Sum or Average | 0.00 | 134339.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.95 | 22.95 | 70.17 | 56890.50 | ||
Maximum of Months | 0.00 | 0.00 | 36.31 | 82.00 | 480023.47 | 2527902.40 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 305.84 | 23912.03 | 25-JAN-05:10 | 6.76 | 6.73 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5693.53 | 826197.23 | 27-FEB-15:30 | 8.80 | 7.74 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 825.67 | 152822.36 | 14-MAR-13:30 | 7.09 | 6.89 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46551.88 | 1213503.56 | 07-APR-12:40 | 9.79 | 8.12 | 0.00 | 0.00 | 01-APR-00:10 |
May | 133338.71 | 1456136.29 | 19-MAY-15:30 | 10.41 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 363351.68 | 1684751.88 | 29-JUN-14:50 | 10.99 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 556560.39 | 1966244.79 | 17-JUL-15:40 | 11.71 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 482858.86 | 2019470.65 | 07-AUG-15:30 | 11.84 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 263757.44 | 2704073.55 | 07-SEP-15:00 | 13.59 | 7.89 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 70926.62 | 1218008.98 | 16-OCT-12:40 | 9.80 | 8.12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5550.35 | 362823.85 | 17-NOV-17:00 | 7.62 | 7.16 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 264.85 | 23960.44 | 04-DEC-04:46 | 6.76 | 6.73 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 162008.96 | 0.00 | ||||||
Minimum of Months | 264.85 | 23912.03 | 6.76 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 556560.39 | 2704073.55 | 13.59 | 8.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2647.44 | 445040.33 | 27-FEB-15:30 | 18.19 | 7.75 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 92.70 | 67616.28 | 14-MAR-13:30 | 16.07 | 6.89 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26208.98 | 947434.34 | 06-APR-16:00 | 20.26 | 7.91 | 0.00 | 0.00 | 01-APR-00:10 |
May | 82155.35 | 1445921.39 | 19-MAY-15:20 | 14.74 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 281583.70 | 1675261.25 | 29-JUN-14:50 | 22.52 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 453509.67 | 1957819.28 | 17-JUL-15:40 | 14.08 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 393777.54 | 2035012.82 | 07-AUG-15:30 | 14.83 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 186087.32 | 2531478.16 | 07-SEP-15:00 | 18.71 | 7.85 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 44595.02 | 1206972.75 | 18-OCT-14:00 | 19.59 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2160.65 | 180549.92 | 03-NOV-14:00 | 14.55 | 7.16 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.01 | 75.24 | 04-DEC-04:46 | 15.33 | 6.73 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 123707.91 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 453509.67 | 2531478.16 | 22.52 | 7.91 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 178882.23 | 203101.59 | 13-JAN-16:30 | 22.16 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 339929.93 | 609079.57 | 27-FEB-16:00 | 29.72 | 22.72 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 496669.48 | 646691.25 | 31-MAR-24:00 | 30.42 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 703935.88 | 1327720.89 | 07-APR-14:00 | 42.86 | 30.29 | 0.00 | 0.00 | 01-APR-00:10 |
May | 257135.32 | 975040.46 | 20-MAY-16:00 | 36.45 | 32.29 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 575841.98 | 1377905.50 | 29-JUN-15:00 | 43.76 | 36.33 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 970669.83 | 1956865.43 | 17-JUL-16:00 | 54.10 | 43.30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1125235.96 | 2072271.40 | 06-AUG-16:00 | 56.14 | 43.03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 339770.54 | 1245137.13 | 02-SEP-17:00 | 41.36 | 36.88 | 0.00 | 0.00 | 01-SEP-00:02 |
October | 387310.63 | 961169.91 | 18-OCT-15:00 | 36.20 | 28.97 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 506782.82 | 750693.74 | 17-NOV-17:00 | 32.34 | 22.55 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 640662.97 | 768649.98 | 10-DEC-02:00 | 32.67 | 20.54 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 545374.06 | 0.00 | ||||||
Minimum of Months | 178882.23 | 203101.59 | 22.16 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1125235.96 | 2072271.40 | 56.14 | 43.30 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.49 | 57.49 | 17320.88 | 58837.17 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.23 | 56.23 | 17697.89 | 59145.27 | 16-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.34 | 56.34 | 18534.81 | 59081.24 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.17 | 56.17 | 16871.72 | 57467.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.21 | 57.21 | 16514.02 | 54935.49 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.06 | 56.06 | 15920.98 | 51670.33 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.35 | 57.35 | 14087.26 | 48630.05 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.03 | 57.03 | 14974.26 | 46956.75 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 56.07 | 56.07 | 14302.61 | 48062.99 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.19 | 57.19 | 14888.17 | 50858.03 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.59 | 56.59 | 15938.81 | 54021.94 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.69 | 56.69 | 16263.11 | 56856.14 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16100.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.06 | 56.06 | 14087.26 | 46956.75 | ||
Maximum of Months | 0.00 | 0.00 | 57.49 | 57.49 | 18534.81 | 59145.27 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.65 | 13877.38 | 25-JAN-05:42 | 21.16 | 20.33 | 314.51 | 101747.55 | 17-JAN-06:30 |
February | 2785.11 | 495057.03 | 27-FEB-15:30 | 23.24 | 21.10 | 521.01 | 104307.37 | 20-FEB-04:30 |
March | 31.14 | 23677.28 | 01-MAR-07:00 | 21.20 | 20.37 | 713.37 | 120998.68 | 21-MAR-05:30 |
April | 29179.71 | 932905.12 | 06-APR-16:00 | 25.14 | 21.10 | 1171.11 | 99930.25 | 14-APR-16:00 |
May | 95345.93 | 2281590.76 | 19-MAY-14:40 | 26.04 | 21.10 | 963.97 | 121002.38 | 06-MAY-05:30 |
June | 343872.09 | 2881577.65 | 20-JUN-15:20 | 27.33 | 23.34 | 640.58 | 86472.28 | 02-JUN-05:30 |
July | 574789.11 | 3012469.21 | 17-JUL-16:00 | 27.62 | 22.74 | 328.18 | 55923.47 | 29-JUL-06:30 |
August | 487455.53 | 2621173.96 | 07-AUG-15:30 | 26.77 | 21.87 | 941.10 | 63406.59 | 30-AUG-07:50 |
September | 237331.38 | 4551358.72 | 07-SEP-15:00 | 30.94 | 25.40 | 560.53 | 96544.40 | 16-SEP-06:00 |
October | 50561.47 | 1977586.91 | 18-OCT-12:20 | 25.38 | 21.10 | 1061.14 | 97708.60 | 31-OCT-10:00 |
November | 2556.07 | 240598.81 | 17-NOV-17:00 | 22.14 | 21.10 | 919.02 | 113422.72 | 29-NOV-05:30 |
December | 10.88 | 22090.58 | 20-DEC-07:00 | 21.20 | 20.37 | 280.48 | 113252.48 | 11-DEC-07:00 |
Annual Sum or Average | 153206.78 | 701.40 | ||||||
Minimum of Months | 9.65 | 13877.38 | 21.16 | 20.33 | 280.48 | 55923.47 | ||
Maximum of Months | 574789.11 | 4551358.72 | 30.94 | 25.40 | 1171.11 | 121002.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.724766E+11 | 0.00 | 0.00 | 0.469374E+10 | 0.00 | 0.00 |
February | 0.369934E+11 | 0.00 | 0.668222E+09 | 0.527111E+10 | 0.00 | 0.00 |
March | 0.192631E+11 | 0.00 | 47762575.90 | 0.785973E+10 | 0.00 | 0.00 |
April | 0.423006E+10 | 0.00 | 0.684875E+10 | 0.966328E+10 | 0.00 | 0.00 |
May | 0.308207E+10 | 0.00 | 0.187044E+11 | 0.890906E+10 | 0.00 | 0.00 |
June | 0.113068E+09 | 0.00 | 0.621322E+11 | 0.135143E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.106594E+12 | 0.163002E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.982073E+11 | 0.177722E+11 | 0.00 | 0.00 |
September | 0.900379E+09 | 0.00 | 0.400732E+11 | 0.981073E+10 | 0.00 | 0.00 |
October | 0.345445E+10 | 0.00 | 0.108484E+11 | 0.877571E+10 | 0.00 | 0.00 |
November | 0.130670E+11 | 0.00 | 0.603942E+09 | 0.736984E+10 | 0.00 | 0.00 |
December | 0.379877E+11 | 0.00 | 0.00 | 0.633126E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.191568E+12 | 0.00 | 0.344728E+12 | 0.116271E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.469374E+10 | 0.00 | 0.00 |
Maximum of Months | 0.724766E+11 | 0.00 | 0.106594E+12 | 0.177722E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.106826E+13 | 0.00 | 12346.86 | 0.435905E+11 | 0.00 | 0.00 |
February | 0.614001E+12 | 0.00 | 0.481262E+10 | 0.397318E+11 | 0.00 | 0.00 |
March | 0.409468E+12 | 0.00 | 0.149095E+09 | 0.510296E+11 | 0.00 | 0.00 |
April | 0.136382E+12 | 0.00 | 0.487552E+11 | 0.554782E+11 | 0.00 | 0.00 |
May | 0.899782E+11 | 0.00 | 0.159328E+12 | 0.667292E+11 | 0.00 | 0.00 |
June | 0.635612E+10 | 0.00 | 0.531036E+12 | 0.104582E+12 | 0.00 | 0.00 |
July | 0.101762E+09 | 0.00 | 0.891038E+12 | 0.122355E+12 | 0.00 | 0.00 |
August | 0.179044E+10 | 0.00 | 0.771346E+12 | 0.119194E+12 | 0.00 | 0.00 |
September | 0.291548E+11 | 0.00 | 0.351058E+12 | 0.762832E+11 | 0.00 | 0.00 |
October | 0.104008E+12 | 0.00 | 0.856662E+11 | 0.570605E+11 | 0.00 | 0.00 |
November | 0.322534E+12 | 0.00 | 0.429216E+10 | 0.452959E+11 | 0.00 | 0.00 |
December | 0.741386E+12 | 0.00 | 18227.04 | 0.432169E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.352342E+13 | 0.00 | 0.284748E+13 | 0.824546E+12 | 0.00 | 0.00 |
Minimum of Months | 0.101762E+09 | 0.00 | 12346.86 | 0.397318E+11 | 0.00 | 0.00 |
Maximum of Months | 0.106826E+13 | 0.00 | 0.891038E+12 | 0.122355E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.155890E+12 | 0.00 | 2274.08 | 0.541981E+10 | 0.00 | 0.00 |
February | 0.890210E+11 | 0.00 | 0.324425E+09 | 0.425912E+10 | 0.00 | 0.00 |
March | 0.664277E+11 | 0.00 | 2489376.22 | 0.462097E+10 | 0.00 | 0.00 |
April | 0.265050E+11 | 0.00 | 0.450198E+10 | 0.448921E+10 | 0.00 | 0.00 |
May | 0.183328E+11 | 0.00 | 0.163879E+11 | 0.580186E+10 | 0.00 | 0.00 |
June | 0.196293E+10 | 0.00 | 0.578964E+11 | 0.977286E+10 | 0.00 | 0.00 |
July | 90853056.98 | 0.00 | 0.981358E+11 | 0.120759E+11 | 0.00 | 0.00 |
August | 0.776267E+09 | 0.00 | 0.826728E+11 | 0.111030E+11 | 0.00 | 0.00 |
September | 0.776179E+10 | 0.00 | 0.357250E+11 | 0.645737E+10 | 0.00 | 0.00 |
October | 0.221069E+11 | 0.00 | 0.731607E+10 | 0.438305E+10 | 0.00 | 0.00 |
November | 0.562236E+11 | 0.00 | 0.304082E+09 | 0.423959E+10 | 0.00 | 0.00 |
December | 0.113676E+12 | 0.00 | 10175.89 | 0.498120E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.558776E+12 | 0.00 | 0.303267E+12 | 0.776039E+11 | 0.00 | 0.00 |
Minimum of Months | 90853056.98 | 0.00 | 2274.08 | 0.423959E+10 | 0.00 | 0.00 |
Maximum of Months | 0.155890E+12 | 0.00 | 0.981358E+11 | 0.120759E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.319450E+09 | 0.00 | 0.00 | 0.174828E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.282783E+09 | 0.155487E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13603.64 | 0.187145E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245389E+10 | 0.174026E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.921493E+10 | 0.185322E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.318869E+11 | 0.185411E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.540153E+11 | 0.185708E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.502708E+11 | 0.202277E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.210305E+11 | 0.189750E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.595290E+10 | 0.186655E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 91667054.30 | 0.177535E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.173201E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.319450E+09 | 0.00 | 0.175200E+12 | 0.217734E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155487E+11 | 0.00 | 0.00 |
Maximum of Months | 0.319450E+09 | 0.00 | 0.540153E+11 | 0.202277E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.453802E+12 | 0.240996E+12 | 0.00 | 15.27 |
February | 0.00 | 0.00 | 0.714318E+12 | 0.297545E+12 | 0.00 | 22.84 |
March | 0.00 | 0.00 | 0.112062E+13 | 0.410549E+12 | 0.00 | 34.43 |
April | 0.00 | 0.00 | 0.140684E+13 | 0.477524E+12 | 0.00 | 41.42 |
May | 0.00 | 0.00 | 0.473998E+12 | 0.243288E+12 | 0.00 | 13.77 |
June | 0.00 | 0.00 | 0.789851E+12 | 0.323435E+12 | 0.00 | 18.36 |
July | 0.00 | 0.00 | 0.116257E+13 | 0.430565E+12 | 0.00 | 20.41 |
August | 0.00 | 0.00 | 0.148818E+13 | 0.521186E+12 | 0.00 | 32.12 |
September | 0.00 | 0.00 | 0.467587E+12 | 0.236764E+12 | 0.00 | 11.73 |
October | 0.00 | 0.00 | 0.807954E+12 | 0.331172E+12 | 0.00 | 23.95 |
November | 0.00 | 0.00 | 0.109525E+13 | 0.401771E+12 | 0.00 | 34.14 |
December | 0.00 | 0.00 | 0.144569E+13 | 0.490799E+12 | 0.00 | 44.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.114267E+14 | 0.440559E+13 | 0.00 | 312.99 |
Minimum of Months | 0.00 | 0.00 | 0.453802E+12 | 0.236764E+12 | 0.00 | 11.73 |
Maximum of Months | 0.00 | 0.00 | 0.148818E+13 | 0.521186E+12 | 0.00 | 44.55 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.373285E+10 | 0.252734E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103569E+11 | 0.368723E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185876E+11 | 0.538311E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248159E+11 | 0.645803E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.711949E+10 | 0.322079E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139018E+11 | 0.467058E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.215584E+11 | 0.671289E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278541E+11 | 0.801969E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.728569E+10 | 0.324679E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131697E+11 | 0.436350E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181677E+11 | 0.521950E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241734E+11 | 0.640866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190723E+12 | 0.599181E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.373285E+10 | 0.252734E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278541E+11 | 0.801969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.109070E+11 | 0.188087E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.751216E+11 | 0.305675E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155718E+12 | 0.474676E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223446E+12 | 0.593957E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.579095E+11 | 0.287702E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128223E+12 | 0.437701E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203814E+12 | 0.637430E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262127E+12 | 0.759034E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.616915E+11 | 0.294530E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.110420E+12 | 0.388355E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150904E+12 | 0.458014E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198064E+12 | 0.554573E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163834E+13 | 0.537973E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.109070E+11 | 0.188087E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262127E+12 | 0.759034E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.304459E+09 | 0.172454E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544278E+10 | 0.266294E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135543E+11 | 0.440038E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209416E+11 | 0.573058E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.494384E+10 | 0.273251E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125772E+11 | 0.436672E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203465E+11 | 0.641281E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260821E+11 | 0.761392E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.550424E+10 | 0.284379E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.933294E+10 | 0.358859E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127768E+11 | 0.418149E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.172964E+11 | 0.512272E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149103E+12 | 0.513810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.304459E+09 | 0.172454E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260821E+11 | 0.761392E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.469374E+10 | 0.00 | 0.724766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527111E+10 | 0.668222E+09 | 0.369934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785973E+10 | 47762575.90 | 0.192631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.966328E+10 | 0.684875E+10 | 0.423006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.890906E+10 | 0.187044E+11 | 0.308207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135143E+11 | 0.621322E+11 | 0.113068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163002E+11 | 0.106594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177722E+11 | 0.982073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.981073E+10 | 0.400732E+11 | 0.900379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.877571E+10 | 0.108484E+11 | 0.345445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736984E+10 | 0.603942E+09 | 0.130670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633126E+10 | 0.00 | 0.379877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116271E+12 | 0.344728E+12 | 0.191568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.469374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177722E+11 | 0.106594E+12 | 0.724766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.435905E+11 | 12346.86 | 0.106826E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397318E+11 | 0.481262E+10 | 0.614001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510296E+11 | 0.149095E+09 | 0.409468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554782E+11 | 0.487552E+11 | 0.136382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.667292E+11 | 0.159328E+12 | 0.899782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104582E+12 | 0.531036E+12 | 0.635612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122355E+12 | 0.891038E+12 | 0.101762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119194E+12 | 0.771346E+12 | 0.179044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.762832E+11 | 0.351058E+12 | 0.291548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.570605E+11 | 0.856662E+11 | 0.104008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452959E+11 | 0.429216E+10 | 0.322534E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432169E+11 | 18227.04 | 0.741386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824546E+12 | 0.284748E+13 | 0.352342E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397318E+11 | 12346.86 | 0.101762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122355E+12 | 0.891038E+12 | 0.106826E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.541981E+10 | 2274.08 | 0.155890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425912E+10 | 0.324425E+09 | 0.890210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.462097E+10 | 2489376.22 | 0.664277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448921E+10 | 0.450198E+10 | 0.265050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.580186E+10 | 0.163879E+11 | 0.183328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.977286E+10 | 0.578964E+11 | 0.196293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120759E+11 | 0.981358E+11 | 90853056.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111030E+11 | 0.826728E+11 | 0.776267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645737E+10 | 0.357250E+11 | 0.776179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.438305E+10 | 0.731607E+10 | 0.221069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.423959E+10 | 0.304082E+09 | 0.562236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498120E+10 | 10175.89 | 0.113676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776039E+11 | 0.303267E+12 | 0.558776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.423959E+10 | 2274.08 | 90853056.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120759E+11 | 0.981358E+11 | 0.155890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174828E+11 | 0.00 | 0.319450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155487E+11 | 0.282783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187145E+11 | 13603.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174026E+11 | 0.245389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185322E+11 | 0.921493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185411E+11 | 0.318869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185708E+11 | 0.540153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202277E+11 | 0.502708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189750E+11 | 0.210305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186655E+11 | 0.595290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177535E+11 | 91667054.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217734E+12 | 0.175200E+12 | 0.319450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202277E+11 | 0.540153E+11 | 0.319450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108058E+12 | 0.361909E+12 | 0.00 | 0.00 | 0.00 | 0.408609E+11 | 0.00 | 0.00 |
February | 0.976007E+11 | 0.575784E+12 | 0.00 | 0.00 | 0.00 | 0.611342E+11 | 0.00 | 0.00 |
March | 0.108058E+12 | 0.910685E+12 | 0.00 | 0.00 | 0.00 | 0.921393E+11 | 0.00 | 0.00 |
April | 0.104572E+12 | 0.114524E+13 | 0.00 | 0.00 | 0.00 | 0.110851E+12 | 0.00 | 0.00 |
May | 0.108058E+12 | 0.375786E+12 | 0.00 | 0.00 | 0.00 | 0.368520E+11 | 0.00 | 0.00 |
June | 0.104572E+12 | 0.620356E+12 | 0.00 | 0.00 | 0.00 | 0.491468E+11 | 0.00 | 0.00 |
July | 0.108058E+12 | 0.894926E+12 | 0.00 | 0.00 | 0.00 | 0.546166E+11 | 0.00 | 0.00 |
August | 0.108058E+12 | 0.116139E+13 | 0.00 | 0.00 | 0.00 | 0.859527E+11 | 0.00 | 0.00 |
September | 0.104572E+12 | 0.366932E+12 | 0.00 | 0.00 | 0.00 | 0.313960E+11 | 0.00 | 0.00 |
October | 0.108058E+12 | 0.649209E+12 | 0.00 | 0.00 | 0.00 | 0.640807E+11 | 0.00 | 0.00 |
November | 0.104572E+12 | 0.889825E+12 | 0.00 | 0.00 | 0.00 | 0.913596E+11 | 0.00 | 0.00 |
December | 0.108058E+12 | 0.118270E+13 | 0.00 | 0.00 | 0.00 | 0.119218E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.127229E+13 | 0.913475E+13 | 0.00 | 0.00 | 0.00 | 0.837608E+12 | 0.00 | 0.00 |
Minimum of Months | 0.976007E+11 | 0.361909E+12 | 0.00 | 0.00 | 0.00 | 0.313960E+11 | 0.00 | 0.00 |
Maximum of Months | 0.108058E+12 | 0.118270E+13 | 0.00 | 0.00 | 0.00 | 0.119218E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169392E+10 | 0.289943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152999E+10 | 0.819962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169392E+10 | 0.148985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163927E+10 | 0.199971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169392E+10 | 0.559262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163927E+10 | 0.108705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169392E+10 | 0.165395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169392E+10 | 0.215283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163927E+10 | 0.567817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169392E+10 | 0.105001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163927E+10 | 0.145875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169392E+10 | 0.194587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199445E+11 | 0.150750E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152999E+10 | 0.289943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169392E+10 | 0.215283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162084E+11 | 0.830672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146398E+11 | 0.591940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162084E+11 | 0.124458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156855E+11 | 0.179736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162084E+11 | 0.453476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156855E+11 | 0.100138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162084E+11 | 0.156279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162084E+11 | 0.202432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156855E+11 | 0.479241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162084E+11 | 0.877932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156855E+11 | 0.120788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162084E+11 | 0.158815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190841E+12 | 0.129121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146398E+11 | 0.830672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162084E+11 | 0.202432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165013E+10 | 0.230045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149044E+10 | 0.427029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165013E+10 | 0.108040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159690E+10 | 0.168079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165013E+10 | 0.386146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159690E+10 | 0.980741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165013E+10 | 0.155838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165013E+10 | 0.201183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159690E+10 | 0.425735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165013E+10 | 0.739448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159690E+10 | 0.101922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165013E+10 | 0.138238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194289E+11 | 0.117151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149044E+10 | 0.230045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165013E+10 | 0.201183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.469374E+10 | 0.724766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527111E+10 | 0.369934E+11 | 0.668222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.785973E+10 | 0.192631E+11 | 47762575.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.966328E+10 | 0.423006E+10 | 0.684875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.890906E+10 | 0.308207E+10 | 0.187044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135143E+11 | 0.113068E+09 | 0.621322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163002E+11 | 0.00 | 0.106594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177722E+11 | 0.00 | 0.982073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.981073E+10 | 0.900379E+09 | 0.400732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.877571E+10 | 0.345445E+10 | 0.108484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736984E+10 | 0.130670E+11 | 0.603942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633126E+10 | 0.379877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116271E+12 | 0.191568E+12 | 0.344728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.469374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.177722E+11 | 0.724766E+11 | 0.106594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.435905E+11 | 0.106826E+13 | 12346.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397318E+11 | 0.614001E+12 | 0.481262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510296E+11 | 0.409468E+12 | 0.149095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554782E+11 | 0.136382E+12 | 0.487552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.667292E+11 | 0.899782E+11 | 0.159328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104582E+12 | 0.635612E+10 | 0.531036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122355E+12 | 0.101762E+09 | 0.891038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119194E+12 | 0.179044E+10 | 0.771346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.762832E+11 | 0.291548E+11 | 0.351058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.570605E+11 | 0.104008E+12 | 0.856662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452959E+11 | 0.322534E+12 | 0.429216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432169E+11 | 0.741386E+12 | 18227.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824546E+12 | 0.352342E+13 | 0.284748E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397318E+11 | 0.101762E+09 | 12346.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122355E+12 | 0.106826E+13 | 0.891038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.541981E+10 | 0.155890E+12 | 2274.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425912E+10 | 0.890210E+11 | 0.324425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.462097E+10 | 0.664277E+11 | 2489376.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448921E+10 | 0.265050E+11 | 0.450198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.580186E+10 | 0.183328E+11 | 0.163879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.977286E+10 | 0.196293E+10 | 0.578964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120759E+11 | 90853056.98 | 0.981358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111030E+11 | 0.776267E+09 | 0.826728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645737E+10 | 0.776179E+10 | 0.357250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.438305E+10 | 0.221069E+11 | 0.731607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.423959E+10 | 0.562236E+11 | 0.304082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498120E+10 | 0.113676E+12 | 10175.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776039E+11 | 0.558776E+12 | 0.303267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.423959E+10 | 90853056.98 | 2274.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120759E+11 | 0.155890E+12 | 0.981358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174828E+11 | 0.319450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155487E+11 | 0.00 | 0.282783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187145E+11 | 0.00 | 13603.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174026E+11 | 0.00 | 0.245389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185322E+11 | 0.00 | 0.921493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185411E+11 | 0.00 | 0.318869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185708E+11 | 0.00 | 0.540153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202277E+11 | 0.00 | 0.502708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189750E+11 | 0.00 | 0.210305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186655E+11 | 0.00 | 0.595290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177535E+11 | 0.00 | 91667054.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217734E+12 | 0.319450E+09 | 0.175200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202277E+11 | 0.319450E+09 | 0.540153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108058E+12 | 0.00 | 0.453802E+12 | 0.00 | 0.918933E+11 | 0.00 | 0.00 | 0.00 | 0.410448E+11 | 0.00 | 0.00 | 0.00 |
February | 0.976007E+11 | 0.00 | 0.714318E+12 | 0.00 | 0.138535E+12 | 0.00 | 0.00 | 0.00 | 0.614094E+11 | 0.00 | 0.00 | 0.00 |
March | 0.108058E+12 | 0.00 | 0.112062E+13 | 0.00 | 0.209937E+12 | 0.00 | 0.00 | 0.00 | 0.925541E+11 | 0.00 | 0.00 | 0.00 |
April | 0.104572E+12 | 0.00 | 0.140684E+13 | 0.00 | 0.261602E+12 | 0.00 | 0.00 | 0.00 | 0.111350E+12 | 0.00 | 0.00 | 0.00 |
May | 0.108058E+12 | 0.00 | 0.473998E+12 | 0.00 | 0.982122E+11 | 0.00 | 0.00 | 0.00 | 0.370179E+11 | 0.00 | 0.00 | 0.00 |
June | 0.104572E+12 | 0.00 | 0.789851E+12 | 0.00 | 0.169495E+12 | 0.00 | 0.00 | 0.00 | 0.493680E+11 | 0.00 | 0.00 | 0.00 |
July | 0.108058E+12 | 0.00 | 0.116257E+13 | 0.00 | 0.267645E+12 | 0.00 | 0.00 | 0.00 | 0.548624E+11 | 0.00 | 0.00 | 0.00 |
August | 0.108058E+12 | 0.00 | 0.148818E+13 | 0.00 | 0.326789E+12 | 0.00 | 0.00 | 0.00 | 0.863396E+11 | 0.00 | 0.00 | 0.00 |
September | 0.104572E+12 | 0.00 | 0.467587E+12 | 0.00 | 0.100654E+12 | 0.00 | 0.00 | 0.00 | 0.315373E+11 | 0.00 | 0.00 | 0.00 |
October | 0.108058E+12 | 0.00 | 0.807954E+12 | 0.00 | 0.158745E+12 | 0.00 | 0.00 | 0.00 | 0.643691E+11 | 0.00 | 0.00 | 0.00 |
November | 0.104572E+12 | 0.00 | 0.109525E+13 | 0.00 | 0.205428E+12 | 0.00 | 0.00 | 0.00 | 0.917708E+11 | 0.00 | 0.00 | 0.00 |
December | 0.108058E+12 | 0.00 | 0.144569E+13 | 0.00 | 0.262986E+12 | 0.00 | 0.00 | 0.00 | 0.119755E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127229E+13 | 0.00 | 0.114267E+14 | 0.00 | 0.229192E+13 | 0.00 | 0.00 | 0.00 | 0.841378E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.976007E+11 | 0.00 | 0.453802E+12 | 0.00 | 0.918933E+11 | 0.00 | 0.00 | 0.00 | 0.315373E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108058E+12 | 0.00 | 0.148818E+13 | 0.00 | 0.326789E+12 | 0.00 | 0.00 | 0.00 | 0.119755E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169392E+10 | 0.00 | 0.373285E+10 | 0.00 | 0.833422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152999E+10 | 0.00 | 0.103569E+11 | 0.00 | 0.215724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169392E+10 | 0.00 | 0.185876E+11 | 0.00 | 0.368919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163927E+10 | 0.00 | 0.248159E+11 | 0.00 | 0.481875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169392E+10 | 0.00 | 0.711949E+10 | 0.00 | 0.152687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163927E+10 | 0.00 | 0.139018E+11 | 0.00 | 0.303130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169392E+10 | 0.00 | 0.215584E+11 | 0.00 | 0.501897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169392E+10 | 0.00 | 0.278541E+11 | 0.00 | 0.632577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163927E+10 | 0.00 | 0.728569E+10 | 0.00 | 0.160752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169392E+10 | 0.00 | 0.131697E+11 | 0.00 | 0.266959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163927E+10 | 0.00 | 0.181677E+11 | 0.00 | 0.358023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169392E+10 | 0.00 | 0.241734E+11 | 0.00 | 0.471474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199445E+11 | 0.00 | 0.190723E+12 | 0.00 | 0.399736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152999E+10 | 0.00 | 0.373285E+10 | 0.00 | 0.833422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169392E+10 | 0.00 | 0.278541E+11 | 0.00 | 0.632577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162084E+11 | 0.00 | 0.109070E+11 | 0.00 | 0.260027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146398E+11 | 0.00 | 0.751216E+11 | 0.00 | 0.159276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162084E+11 | 0.00 | 0.155718E+12 | 0.00 | 0.312592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156855E+11 | 0.00 | 0.223446E+12 | 0.00 | 0.437101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162084E+11 | 0.00 | 0.579095E+11 | 0.00 | 0.125618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156855E+11 | 0.00 | 0.128223E+12 | 0.00 | 0.280845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162084E+11 | 0.00 | 0.203814E+12 | 0.00 | 0.475346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162084E+11 | 0.00 | 0.262127E+12 | 0.00 | 0.596950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156855E+11 | 0.00 | 0.616915E+11 | 0.00 | 0.137675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162084E+11 | 0.00 | 0.110420E+12 | 0.00 | 0.226271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156855E+11 | 0.00 | 0.150904E+12 | 0.00 | 0.301158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162084E+11 | 0.00 | 0.198064E+12 | 0.00 | 0.392489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190841E+12 | 0.00 | 0.163834E+13 | 0.00 | 0.347133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146398E+11 | 0.00 | 0.109070E+11 | 0.00 | 0.260027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162084E+11 | 0.00 | 0.262127E+12 | 0.00 | 0.596950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165013E+10 | 0.00 | 0.304459E+09 | 0.00 | 74414483.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149044E+10 | 0.00 | 0.544278E+10 | 0.00 | 0.117250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165013E+10 | 0.00 | 0.135543E+11 | 0.00 | 0.275025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159690E+10 | 0.00 | 0.209416E+11 | 0.00 | 0.413369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165013E+10 | 0.00 | 0.494384E+10 | 0.00 | 0.108238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159690E+10 | 0.00 | 0.125772E+11 | 0.00 | 0.276982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165013E+10 | 0.00 | 0.203465E+11 | 0.00 | 0.476269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165013E+10 | 0.00 | 0.260821E+11 | 0.00 | 0.596379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159690E+10 | 0.00 | 0.550424E+10 | 0.00 | 0.124689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165013E+10 | 0.00 | 0.933294E+10 | 0.00 | 0.193847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159690E+10 | 0.00 | 0.127768E+11 | 0.00 | 0.258459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165013E+10 | 0.00 | 0.172964E+11 | 0.00 | 0.347260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194289E+11 | 0.00 | 0.149103E+12 | 0.00 | 0.319521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149044E+10 | 0.00 | 0.304459E+09 | 0.00 | 74414483.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165013E+10 | 0.00 | 0.260821E+11 | 0.00 | 0.596379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249746E+11 | 0.00 | 0.00 | 62017720.89 | 0.00 | 0.00 | 0.460334E+11 | 0.00 | 0.43 |
February | 0.845178E+10 | 0.00 | 0.00 | 76470015.44 | 0.00 | 0.00 | 0.549091E+11 | 0.00 | 0.55 |
March | 0.271370E+10 | 0.00 | 0.00 | 0.113026E+09 | 0.00 | 0.00 | 0.755399E+11 | 0.00 | 0.69 |
April | 0.339076E+09 | 0.00 | 0.00 | 0.108718E+09 | 0.00 | 0.00 | 0.714405E+11 | 0.00 | 0.95 |
May | 0.159295E+09 | 41999800.24 | 0.00 | 0.113538E+09 | 6376103.83 | 0.00 | 0.692177E+11 | 0.00 | 1.15 |
June | 0.106587E+09 | 0.376684E+09 | 0.00 | 0.108100E+09 | 354436.60 | 0.00 | 0.512737E+11 | 0.00 | 1.34 |
July | 0.124298E+09 | 0.132368E+10 | 0.00 | 0.105376E+09 | 30573486.60 | 0.00 | 0.319779E+11 | 0.00 | 1.13 |
August | 0.111198E+09 | 0.930228E+09 | 0.00 | 0.122940E+09 | 49603332.19 | 0.00 | 0.447037E+11 | 0.00 | 1.36 |
September | 0.249879E+09 | 0.375528E+09 | 0.00 | 0.119885E+09 | 37349549.71 | 0.00 | 0.620434E+11 | 0.00 | 1.34 |
October | 0.420469E+09 | 0.00 | 0.00 | 0.130493E+09 | 0.00 | 0.00 | 0.779676E+11 | 0.00 | 1.12 |
November | 0.395849E+09 | 0.00 | 0.00 | 0.125859E+09 | 0.00 | 0.00 | 0.783608E+11 | 0.00 | 0.83 |
December | 0.579433E+10 | 0.00 | 0.00 | 0.107327E+09 | 0.00 | 0.00 | 0.699801E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.438411E+11 | 0.304812E+10 | 0.00 | 0.129375E+10 | 0.124257E+09 | 0.00 | 0.733448E+12 | 0.00 | 0.96 |
Minimum of Months | 0.106587E+09 | 0.00 | 0.00 | 62017720.89 | 0.00 | 0.00 | 0.319779E+11 | 0.00 | 0.43 |
Maximum of Months | 0.249746E+11 | 0.132368E+10 | 0.00 | 0.130493E+09 | 49603332.19 | 0.00 | 0.783608E+11 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254387E+11 | 0.00 | 0.00 | 37590533.64 | 0.00 | 0.00 | 0.434579E+11 | 0.00 | 0.40 |
February | 0.967281E+10 | 0.00 | 0.00 | 57333126.70 | 0.00 | 0.00 | 0.483354E+11 | 0.00 | 0.48 |
March | 0.355624E+10 | 0.00 | 0.00 | 93188894.49 | 0.00 | 0.00 | 0.644311E+11 | 0.00 | 0.58 |
April | 0.403519E+10 | 0.00 | 0.00 | 96272826.17 | 0.00 | 0.00 | 0.593320E+11 | 0.00 | 0.80 |
May | 0.242762E+10 | 26495848.49 | 0.00 | 89267813.44 | 14532957.14 | 0.00 | 0.506574E+11 | 0.00 | 0.81 |
June | 0.466387E+10 | 0.461765E+09 | 0.00 | 89736536.97 | 11827359.90 | 0.00 | 0.388784E+11 | 0.00 | 1.07 |
July | 0.719025E+10 | 0.138261E+10 | 0.00 | 77822023.58 | 72629495.85 | 0.00 | 0.218791E+11 | 0.00 | 1.00 |
August | 0.932397E+10 | 0.964595E+09 | 0.00 | 94930644.37 | 73971252.17 | 0.00 | 0.334942E+11 | 0.00 | 1.21 |
September | 0.303906E+10 | 0.505297E+09 | 0.00 | 86943878.95 | 54249455.57 | 0.00 | 0.418854E+11 | 0.00 | 0.91 |
October | 0.279794E+10 | 0.00 | 0.00 | 95354457.73 | 0.00 | 0.00 | 0.553168E+11 | 0.00 | 0.80 |
November | 0.213484E+10 | 0.00 | 0.00 | 87885571.50 | 0.00 | 0.00 | 0.594264E+11 | 0.00 | 0.62 |
December | 0.451350E+10 | 0.00 | 0.00 | 77885656.27 | 0.00 | 0.00 | 0.641899E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.787940E+11 | 0.334077E+10 | 0.00 | 0.984212E+09 | 0.227211E+09 | 0.00 | 0.581284E+12 | 0.00 | 0.77 |
Minimum of Months | 0.213484E+10 | 0.00 | 0.00 | 37590533.64 | 0.00 | 0.00 | 0.218791E+11 | 0.00 | 0.40 |
Maximum of Months | 0.254387E+11 | 0.138261E+10 | 0.00 | 96272826.17 | 73971252.17 | 0.00 | 0.644311E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.486649E+12 | 0.00 | 0.00 | 58177873.88 | 0.00 | 0.743414E+10 | 0.130558E+12 | 0.00 | 0.37 |
February | 0.314742E+12 | 0.00 | 0.00 | 0.146525E+09 | 0.00 | 0.128664E+10 | 0.170534E+12 | 0.00 | 0.40 |
March | 0.210177E+12 | 0.00 | 0.00 | 0.342626E+09 | 0.00 | 0.131220E+10 | 0.316677E+12 | 0.00 | 0.45 |
April | 0.806886E+11 | 0.00 | 0.00 | 0.483167E+09 | 0.00 | 0.00 | 0.357636E+12 | 0.00 | 0.56 |
May | 0.463766E+11 | 0.292583E+09 | 0.00 | 0.580972E+09 | 0.157953E+09 | 0.00 | 0.373104E+12 | 0.00 | 0.66 |
June | 0.249676E+11 | 0.510864E+10 | 0.00 | 0.695254E+09 | 0.146662E+09 | 0.00 | 0.306612E+12 | 0.00 | 0.85 |
July | 0.267083E+11 | 0.145533E+11 | 0.00 | 0.620732E+09 | 0.513499E+09 | 0.00 | 0.166428E+12 | 0.00 | 0.74 |
August | 0.241394E+11 | 0.101037E+11 | 0.00 | 0.722265E+09 | 0.714597E+09 | 0.00 | 0.250046E+12 | 0.00 | 0.84 |
September | 0.251605E+11 | 0.492433E+10 | 0.00 | 0.628880E+09 | 0.573261E+09 | 0.00 | 0.322335E+12 | 0.00 | 0.72 |
October | 0.567900E+11 | 0.00 | 0.00 | 0.529097E+09 | 0.00 | 0.00 | 0.359500E+12 | 0.00 | 0.58 |
November | 0.184030E+12 | 0.00 | 0.00 | 0.307909E+09 | 0.00 | 51038884.84 | 0.257699E+12 | 0.00 | 0.45 |
December | 0.369410E+12 | 0.00 | 0.00 | 0.144244E+09 | 0.00 | 0.210153E+10 | 0.177734E+12 | 0.00 | 0.39 |
Annual Sum or Average | 0.184984E+13 | 0.349826E+11 | 0.00 | 0.525985E+10 | 0.210597E+10 | 0.121856E+11 | 0.318886E+13 | 0.00 | 0.59 |
Minimum of Months | 0.241394E+11 | 0.00 | 0.00 | 58177873.88 | 0.00 | 0.00 | 0.130558E+12 | 0.00 | 0.37 |
Maximum of Months | 0.486649E+12 | 0.145533E+11 | 0.00 | 0.722265E+09 | 0.714597E+09 | 0.743414E+10 | 0.373104E+12 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.413310E+11 | 0.00 | 0.00 | 81160.80 | 0.00 | 0.134341E+11 | 0.166007E+09 | 0.00 | 0.36 |
February | 0.359231E+11 | 0.00 | 0.00 | 1907190.93 | 0.00 | 0.416761E+10 | 0.287425E+10 | 0.00 | 0.38 |
March | 0.306186E+11 | 0.00 | 0.00 | 9212894.96 | 0.00 | 0.292581E+10 | 0.111395E+11 | 0.00 | 0.41 |
April | 0.166599E+11 | 0.00 | 0.00 | 23789887.64 | 0.00 | 36921490.94 | 0.201276E+11 | 0.00 | 0.49 |
May | 0.112939E+11 | 18434716.18 | 0.00 | 39352187.43 | 11888898.10 | 0.317084E+09 | 0.259711E+11 | 0.00 | 0.61 |
June | 0.384748E+10 | 0.366783E+09 | 0.00 | 62567519.01 | 13205794.38 | 0.00 | 0.268267E+11 | 0.00 | 0.85 |
July | 0.251936E+10 | 0.128128E+10 | 0.00 | 60431518.19 | 43845819.21 | 0.00 | 0.151905E+11 | 0.00 | 0.76 |
August | 0.266444E+10 | 0.831145E+09 | 0.00 | 64358962.22 | 60267806.08 | 0.00 | 0.212897E+11 | 0.00 | 0.82 |
September | 0.718483E+10 | 0.438074E+09 | 0.00 | 43513877.54 | 47400086.10 | 0.00 | 0.216535E+11 | 0.00 | 0.66 |
October | 0.165856E+11 | 0.00 | 0.00 | 21842867.53 | 475538.05 | 0.227114E+09 | 0.157523E+11 | 0.00 | 0.48 |
November | 0.266998E+11 | 0.00 | 0.00 | 6682729.39 | 0.00 | 0.216559E+10 | 0.672103E+10 | 0.00 | 0.39 |
December | 0.382078E+11 | 0.00 | 0.00 | 1485359.94 | 0.00 | 0.682110E+10 | 0.213075E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.233536E+12 | 0.293572E+10 | 0.00 | 0.335226E+09 | 0.177084E+09 | 0.300953E+11 | 0.169843E+12 | 0.00 | 0.55 |
Minimum of Months | 0.251936E+10 | 0.00 | 0.00 | 81160.80 | 0.00 | 0.00 | 0.166007E+09 | 0.00 | 0.36 |
Maximum of Months | 0.413310E+11 | 0.128128E+10 | 0.00 | 64358962.22 | 60267806.08 | 0.134341E+11 | 0.268267E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427441E+10 | 0.00 | 0.00 | 29.88 | 0.00 | 0.498839E+10 | 4609210.47 | 0.00 | 0.42 |
February | 0.484373E+10 | 0.00 | 0.00 | 370642.44 | 0.00 | 0.164407E+10 | 0.392775E+09 | 0.00 | 0.44 |
March | 0.482356E+10 | 0.00 | 0.00 | 1977355.29 | 0.00 | 0.286930E+09 | 0.193174E+10 | 0.00 | 0.47 |
April | 0.290648E+10 | 0.00 | 0.00 | 4997068.89 | 0.00 | 0.00 | 0.380747E+10 | 0.00 | 0.71 |
May | 0.203410E+10 | 7271913.04 | 0.00 | 6798765.21 | 2319219.38 | 0.00 | 0.419051E+10 | 0.00 | 0.83 |
June | 0.109691E+10 | 91022906.90 | 0.00 | 11195776.04 | 1887450.85 | 0.00 | 0.490920E+10 | 0.00 | 1.30 |
July | 0.131135E+10 | 0.293993E+09 | 0.00 | 10842053.62 | 11599399.59 | 0.00 | 0.289115E+10 | 0.00 | 1.26 |
August | 0.181244E+10 | 0.195634E+09 | 0.00 | 10983096.31 | 11804587.30 | 0.00 | 0.380872E+10 | 0.00 | 1.39 |
September | 0.182240E+10 | 90922892.84 | 0.00 | 6395912.44 | 8657315.04 | 0.00 | 0.326195E+10 | 0.00 | 0.89 |
October | 0.309151E+10 | 0.00 | 0.00 | 3963154.27 | 0.00 | 0.00 | 0.280912E+10 | 0.00 | 0.67 |
November | 0.453533E+10 | 0.00 | 0.00 | 1355910.55 | 0.00 | 81350658.88 | 0.135821E+10 | 0.00 | 0.47 |
December | 0.565975E+10 | 0.00 | 0.00 | 220663.20 | 0.00 | 0.118761E+10 | 0.366072E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.382120E+11 | 0.678845E+09 | 0.00 | 59100428.12 | 36267972.15 | 0.818835E+10 | 0.297315E+11 | 0.00 | 0.77 |
Minimum of Months | 0.109691E+10 | 0.00 | 0.00 | 29.88 | 0.00 | 0.00 | 4609210.47 | 0.00 | 0.38 |
Maximum of Months | 0.565975E+10 | 0.293993E+09 | 0.00 | 11195776.04 | 11804587.30 | 0.498839E+10 | 0.490920E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580859E+10 | 0.00 | 0.00 | 10406.40 | 0.00 | 0.561194E+10 | 22941546.93 | 0.00 | 0.80 |
February | 0.575586E+10 | 0.00 | 0.00 | 893720.78 | 0.00 | 0.206404E+10 | 0.772957E+09 | 0.00 | 0.85 |
March | 0.617331E+10 | 0.00 | 0.00 | 2500417.79 | 0.00 | 0.550777E+09 | 0.213468E+10 | 0.00 | 0.90 |
April | 0.437322E+10 | 0.00 | 0.00 | 5048806.98 | 0.00 | 4122883.72 | 0.374840E+10 | 0.00 | 1.27 |
May | 0.287598E+10 | 4999154.39 | 0.00 | 7321796.61 | 2880301.09 | 431896.30 | 0.472819E+10 | 0.00 | 1.47 |
June | 0.184172E+10 | 70382252.26 | 0.00 | 11602701.17 | 2344076.11 | 0.00 | 0.486606E+10 | 0.00 | 2.15 |
July | 0.182839E+10 | 0.216937E+09 | 0.00 | 12586295.53 | 14405607.19 | 0.00 | 0.327298E+10 | 0.00 | 2.19 |
August | 0.281966E+10 | 0.152306E+09 | 0.00 | 9823478.74 | 14226181.18 | 0.00 | 0.376557E+10 | 0.00 | 2.33 |
September | 0.274681E+10 | 73840515.83 | 0.00 | 6184093.63 | 10680047.97 | 0.00 | 0.333826E+10 | 0.00 | 1.56 |
October | 0.411613E+10 | 0.00 | 0.00 | 3754326.83 | 0.00 | 1384836.57 | 0.285043E+10 | 0.00 | 1.17 |
November | 0.587376E+10 | 0.00 | 0.00 | 768050.65 | 0.00 | 0.311646E+09 | 0.110857E+10 | 0.00 | 0.88 |
December | 0.667117E+10 | 0.00 | 0.00 | 23250.58 | 0.00 | 0.220275E+10 | 83340448.26 | 0.00 | 0.74 |
Annual Sum or Average | 0.508846E+11 | 0.518465E+09 | 0.00 | 60517345.67 | 44536213.54 | 0.107471E+11 | 0.306924E+11 | 0.00 | 1.36 |
Minimum of Months | 0.182839E+10 | 0.00 | 0.00 | 10406.40 | 0.00 | 0.00 | 22941546.93 | 0.00 | 0.74 |
Maximum of Months | 0.667117E+10 | 0.216937E+09 | 0.00 | 12586295.53 | 14405607.19 | 0.561194E+10 | 0.486606E+10 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.659413E+10 | 0.00 | 0.00 | 2447698.52 | 0.00 | 0.595936E+10 | 0.273319E+10 | 0.00 | 0.70 |
February | 0.606380E+10 | 0.00 | 0.00 | 7260141.16 | 0.00 | 0.183609E+10 | 0.498036E+10 | 0.00 | 0.90 |
March | 0.662709E+10 | 0.00 | 0.00 | 8910119.95 | 0.00 | 0.541491E+09 | 0.684879E+10 | 0.00 | 0.99 |
April | 0.497664E+10 | 0.00 | 0.00 | 9202971.88 | 0.00 | 11769117.81 | 0.655376E+10 | 0.00 | 1.26 |
May | 0.396769E+10 | 10099449.60 | 0.00 | 9343002.97 | 3643276.32 | 71459094.10 | 0.572499E+10 | 0.00 | 1.30 |
June | 0.264224E+10 | 0.122242E+09 | 0.00 | 11897655.99 | 2965008.42 | 0.00 | 0.512234E+10 | 0.00 | 1.68 |
July | 0.247520E+10 | 0.405408E+09 | 0.00 | 12549552.82 | 18221569.88 | 0.00 | 0.312634E+10 | 0.00 | 1.69 |
August | 0.333056E+10 | 0.334050E+09 | 0.00 | 15560835.50 | 18543900.54 | 0.00 | 0.488601E+10 | 0.00 | 2.12 |
September | 0.293041E+10 | 0.225982E+09 | 0.00 | 13540124.97 | 6005895.93 | 0.00 | 0.620462E+10 | 0.00 | 1.71 |
October | 0.389394E+10 | 0.00 | 0.00 | 14855188.69 | 0.00 | 25492483.26 | 0.818668E+10 | 0.00 | 1.45 |
November | 0.542253E+10 | 0.00 | 0.00 | 8060594.82 | 0.00 | 0.460948E+09 | 0.602765E+10 | 0.00 | 0.97 |
December | 0.697306E+10 | 0.00 | 0.00 | 4177503.62 | 0.00 | 0.222939E+10 | 0.345612E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.558973E+11 | 0.109778E+10 | 0.00 | 0.117805E+09 | 49379651.09 | 0.111360E+11 | 0.638509E+11 | 0.00 | 1.29 |
Minimum of Months | 0.247520E+10 | 0.00 | 0.00 | 2447698.52 | 0.00 | 0.00 | 0.273319E+10 | 0.00 | 0.70 |
Maximum of Months | 0.697306E+10 | 0.405408E+09 | 0.00 | 15560835.50 | 18543900.54 | 0.595936E+10 | 0.818668E+10 | 0.00 | 2.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.913639E+10 | 0.00 | 0.00 | 157079.36 | 0.00 | 0.487549E+10 | 0.243094E+09 | 0.00 | 1.00 |
February | 0.852137E+10 | 0.00 | 0.00 | 1862706.29 | 0.00 | 0.330047E+09 | 0.201808E+10 | 0.00 | 1.09 |
March | 0.571575E+10 | 0.00 | 0.00 | 5798255.40 | 0.00 | 42302912.69 | 0.578889E+10 | 0.00 | 1.22 |
April | 0.210980E+10 | 0.00 | 0.00 | 12853118.89 | 0.00 | 0.00 | 0.893042E+10 | 0.00 | 1.85 |
May | 0.292896E+10 | 8110637.71 | 0.00 | 10195124.42 | 3589152.50 | 0.00 | 0.618730E+10 | 0.00 | 1.84 |
June | 0.152490E+10 | 0.129558E+09 | 0.00 | 14632557.94 | 972230.94 | 0.00 | 0.606706E+10 | 0.00 | 2.55 |
July | 0.171048E+10 | 0.440057E+09 | 0.00 | 17365970.34 | 9590657.66 | 0.00 | 0.382657E+10 | 0.00 | 2.57 |
August | 0.211154E+10 | 0.319119E+09 | 0.00 | 19369031.59 | 4730159.78 | 0.00 | 0.598355E+10 | 0.00 | 3.11 |
September | 0.278876E+10 | 0.146972E+09 | 0.00 | 7641951.05 | 2135997.08 | 0.00 | 0.432560E+10 | 0.00 | 1.91 |
October | 0.364432E+10 | 0.00 | 0.00 | 6803051.33 | 0.00 | 0.00 | 0.533494E+10 | 0.00 | 1.56 |
November | 0.536494E+10 | 0.00 | 0.00 | 4102800.25 | 0.00 | 1570726.85 | 0.422988E+10 | 0.00 | 1.18 |
December | 0.867669E+10 | 0.00 | 0.00 | 2212317.36 | 0.00 | 13549441.90 | 0.267367E+10 | 0.00 | 0.94 |
Annual Sum or Average | 0.542339E+11 | 0.104382E+10 | 0.00 | 0.102994E+09 | 21018197.96 | 0.526296E+10 | 0.556091E+11 | 0.00 | 1.74 |
Minimum of Months | 0.152490E+10 | 0.00 | 0.00 | 157079.36 | 0.00 | 0.00 | 0.243094E+09 | 0.00 | 0.94 |
Maximum of Months | 0.913639E+10 | 0.440057E+09 | 0.00 | 19369031.59 | 9590657.66 | 0.487549E+10 | 0.893042E+10 | 0.00 | 3.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962790E+11 | 0.00 | 0.00 | 0.50 |
February | 0.221376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538038E+11 | 0.00 | 0.00 | 0.49 |
March | 0.482707E+11 | 0.00 | 0.00 | 93509.84 | 0.00 | 0.237730E+11 | 0.276244E+09 | 0.00 | 0.48 |
April | 0.390214E+11 | 0.00 | 0.00 | 10974933.55 | 0.00 | 0.381931E+10 | 0.915146E+10 | 0.00 | 0.53 |
May | 0.291156E+11 | 80883403.26 | 0.00 | 35387013.05 | 26338574.07 | 0.252898E+10 | 0.199062E+11 | 0.00 | 0.68 |
June | 0.112466E+11 | 0.107392E+10 | 0.00 | 80312850.14 | 23438154.07 | 0.00 | 0.332084E+11 | 0.00 | 1.02 |
July | 0.646914E+10 | 0.341663E+10 | 0.00 | 81206977.99 | 83192405.40 | 0.00 | 0.204489E+11 | 0.00 | 0.96 |
August | 0.110990E+11 | 0.227416E+10 | 0.00 | 69693139.41 | 0.114200E+09 | 0.00 | 0.227970E+11 | 0.00 | 0.95 |
September | 0.246161E+11 | 0.879882E+09 | 0.00 | 35491098.15 | 91613033.71 | 0.621244E+09 | 0.151338E+11 | 0.00 | 0.71 |
October | 0.397210E+11 | 0.00 | 0.00 | 8354732.25 | 0.00 | 0.347433E+10 | 0.581550E+10 | 0.00 | 0.53 |
November | 0.349467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257439E+11 | 0.00 | 0.00 | 0.47 |
December | 0.200590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655639E+11 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.298841E+12 | 0.772547E+10 | 0.00 | 0.321514E+09 | 0.338782E+09 | 0.275608E+12 | 0.126737E+12 | 0.00 | 0.65 |
Minimum of Months | 0.646914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.482707E+11 | 0.341663E+10 | 0.00 | 81206977.99 | 0.114200E+09 | 0.962790E+11 | 0.332084E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110934E+12 | 0.00 | 0.00 | 1.01 |
February | 0.400059E+11 | 0.00 | 0.00 | 1353427.15 | 0.00 | 0.620231E+11 | 0.116884E+10 | 0.00 | 1.04 |
March | 0.626905E+11 | 0.00 | 0.00 | 9084652.47 | 0.00 | 0.280063E+11 | 0.101103E+11 | 0.00 | 1.05 |
April | 0.475791E+11 | 0.00 | 0.00 | 32779030.85 | 0.00 | 0.367407E+10 | 0.262303E+11 | 0.00 | 1.21 |
May | 0.350599E+11 | 64399230.56 | 0.00 | 54748209.59 | 35044719.18 | 0.361400E+10 | 0.358777E+11 | 0.00 | 1.45 |
June | 0.169453E+11 | 0.936246E+09 | 0.00 | 0.107082E+09 | 31775042.11 | 0.00 | 0.431486E+11 | 0.00 | 2.03 |
July | 0.100896E+11 | 0.288992E+10 | 0.00 | 0.127548E+09 | 0.115497E+09 | 0.00 | 0.308996E+11 | 0.00 | 2.00 |
August | 0.173243E+11 | 0.218072E+10 | 0.00 | 92260096.76 | 0.157750E+09 | 0.00 | 0.335021E+11 | 0.00 | 2.00 |
September | 0.333828E+11 | 0.851951E+09 | 0.00 | 46214256.27 | 0.127068E+09 | 0.609339E+09 | 0.227108E+11 | 0.00 | 1.47 |
October | 0.529259E+11 | 0.00 | 0.00 | 14097954.03 | 0.00 | 0.315045E+10 | 0.123077E+11 | 0.00 | 1.15 |
November | 0.510465E+11 | 0.00 | 0.00 | 711135.30 | 0.00 | 0.313342E+11 | 0.113212E+10 | 0.00 | 1.01 |
December | 0.345256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814499E+11 | 0.00 | 0.00 | 1.00 |
Annual Sum or Average | 0.428460E+12 | 0.692323E+10 | 0.00 | 0.485879E+09 | 0.467135E+09 | 0.324796E+12 | 0.217088E+12 | 0.00 | 1.37 |
Minimum of Months | 0.100896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
Maximum of Months | 0.626905E+11 | 0.288992E+10 | 0.00 | 0.127548E+09 | 0.157750E+09 | 0.110934E+12 | 0.431486E+11 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529320E+11 | 0.00 | 0.00 | 15889586.42 | 0.00 | 0.971806E+11 | 0.234333E+11 | 0.00 | 0.83 |
February | 0.568692E+11 | 0.00 | 0.00 | 62541380.79 | 0.00 | 0.429294E+11 | 0.438489E+11 | 0.00 | 1.02 |
March | 0.691597E+11 | 0.00 | 0.00 | 72893015.65 | 0.00 | 0.237476E+11 | 0.557152E+11 | 0.00 | 1.06 |
April | 0.530549E+11 | 0.00 | 0.00 | 70097723.37 | 0.00 | 0.471350E+10 | 0.474632E+11 | 0.00 | 1.15 |
May | 0.444996E+11 | 0.129625E+09 | 0.00 | 77920585.52 | 42385325.82 | 0.438569E+10 | 0.447046E+11 | 0.00 | 1.25 |
June | 0.264848E+11 | 0.154710E+10 | 0.00 | 95505052.63 | 33849796.43 | 0.00 | 0.390903E+11 | 0.00 | 1.49 |
July | 0.160044E+11 | 0.508898E+10 | 0.00 | 0.104415E+09 | 0.139690E+09 | 0.00 | 0.244402E+11 | 0.00 | 1.42 |
August | 0.213983E+11 | 0.448618E+10 | 0.00 | 0.130354E+09 | 0.191756E+09 | 0.00 | 0.378318E+11 | 0.00 | 1.74 |
September | 0.319710E+11 | 0.266441E+10 | 0.00 | 0.125146E+09 | 68929734.69 | 0.608596E+09 | 0.519959E+11 | 0.00 | 1.64 |
October | 0.430689E+11 | 0.00 | 0.00 | 0.134611E+09 | 0.00 | 0.239551E+10 | 0.690989E+11 | 0.00 | 1.40 |
November | 0.547697E+11 | 0.00 | 0.00 | 62058652.08 | 0.00 | 0.210437E+11 | 0.469862E+11 | 0.00 | 0.99 |
December | 0.631185E+11 | 0.00 | 0.00 | 23128532.91 | 0.00 | 0.605657E+11 | 0.243545E+11 | 0.00 | 0.83 |
Annual Sum or Average | 0.533331E+12 | 0.139163E+11 | 0.00 | 0.974560E+09 | 0.476610E+09 | 0.257570E+12 | 0.508963E+12 | 0.00 | 1.23 |
Minimum of Months | 0.160044E+11 | 0.00 | 0.00 | 15889586.42 | 0.00 | 0.00 | 0.234333E+11 | 0.00 | 0.83 |
Maximum of Months | 0.691597E+11 | 0.508898E+10 | 0.00 | 0.134611E+09 | 0.191756E+09 | 0.971806E+11 | 0.690989E+11 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.326693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115022E+12 | 0.00 | 0.00 | 1.08 |
February | 0.517303E+11 | 0.00 | 0.00 | 3623358.47 | 0.00 | 0.560878E+11 | 0.328325E+10 | 0.00 | 1.12 |
March | 0.732207E+11 | 0.00 | 0.00 | 10747809.00 | 0.00 | 0.257908E+11 | 0.987782E+10 | 0.00 | 1.14 |
April | 0.585134E+11 | 0.00 | 0.00 | 28420206.26 | 0.00 | 0.310622E+10 | 0.199618E+11 | 0.00 | 1.32 |
May | 0.430870E+11 | 77572278.56 | 0.00 | 59786183.50 | 39252820.27 | 0.311715E+10 | 0.320064E+11 | 0.00 | 1.57 |
June | 0.230211E+11 | 0.143597E+10 | 0.00 | 75294481.78 | 19117113.04 | 8096346.06 | 0.317822E+11 | 0.00 | 1.91 |
July | 0.137796E+11 | 0.469718E+10 | 0.00 | 82890996.67 | 47204790.48 | 0.00 | 0.190723E+11 | 0.00 | 1.76 |
August | 0.200597E+11 | 0.308738E+10 | 0.00 | 70290995.57 | 89976259.21 | 6035692.34 | 0.236788E+11 | 0.00 | 1.84 |
September | 0.394198E+11 | 0.140207E+10 | 0.00 | 38360243.06 | 35774177.22 | 0.620749E+09 | 0.182212E+11 | 0.00 | 1.56 |
October | 0.589729E+11 | 0.00 | 0.00 | 17098832.43 | 0.00 | 0.314586E+10 | 0.120469E+11 | 0.00 | 1.26 |
November | 0.609097E+11 | 0.00 | 0.00 | 3744137.08 | 0.00 | 0.239697E+11 | 0.486706E+10 | 0.00 | 1.09 |
December | 0.480244E+11 | 0.00 | 0.00 | 111741.67 | 0.00 | 0.760968E+11 | 0.317016E+09 | 0.00 | 1.07 |
Annual Sum or Average | 0.523408E+12 | 0.107002E+11 | 0.00 | 0.390369E+09 | 0.231325E+09 | 0.306971E+12 | 0.175115E+12 | 0.00 | 1.39 |
Minimum of Months | 0.137796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
Maximum of Months | 0.732207E+11 | 0.469718E+10 | 0.00 | 82890996.67 | 89976259.21 | 0.115022E+12 | 0.320064E+11 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130869E+11 | 0.00 | 0.00 | 0.67 |
February | 0.149769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789017E+10 | 0.00 | 0.00 | 0.65 |
March | 0.383743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539185E+10 | 0.00 | 0.00 | 0.66 |
April | 0.452496E+10 | 0.00 | 0.00 | 385642.19 | 0.00 | 0.181681E+10 | 0.363880E+09 | 0.00 | 0.68 |
May | 0.377411E+10 | 5029020.00 | 0.00 | 2342358.28 | 2487969.10 | 0.114045E+10 | 0.139898E+10 | 0.00 | 0.80 |
June | 0.176707E+10 | 73073458.80 | 0.00 | 7190662.01 | 2763553.70 | 40419577.67 | 0.287648E+10 | 0.00 | 1.11 |
July | 0.105319E+10 | 0.280936E+09 | 0.00 | 7678261.75 | 9329720.95 | 0.00 | 0.174930E+10 | 0.00 | 1.03 |
August | 0.166370E+10 | 0.176646E+09 | 0.00 | 5973188.68 | 12612139.33 | 29371949.41 | 0.186216E+10 | 0.00 | 1.01 |
September | 0.311326E+10 | 75749599.41 | 0.00 | 2485235.37 | 11160006.98 | 0.514924E+09 | 0.101341E+10 | 0.00 | 0.82 |
October | 0.404714E+10 | 0.00 | 0.00 | 158685.81 | 99515.02 | 0.190025E+10 | 0.140929E+09 | 0.00 | 0.69 |
November | 0.230733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509912E+10 | 0.00 | 0.00 | 0.63 |
December | 0.964096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952120E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.288935E+11 | 0.611434E+09 | 0.00 | 26214034.08 | 38452905.09 | 0.464314E+11 | 0.940514E+10 | 0.00 | 0.78 |
Minimum of Months | 0.343501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.452496E+10 | 0.280936E+09 | 0.00 | 7678261.75 | 12612139.33 | 0.130869E+11 | 0.287648E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116782E+11 | 0.00 | 0.00 | 1.02 |
February | 0.296777E+10 | 0.00 | 0.00 | 1152.20 | 0.00 | 0.687594E+10 | 15660889.71 | 0.00 | 1.07 |
March | 0.529786E+10 | 0.00 | 0.00 | 380870.22 | 0.00 | 0.420102E+10 | 0.500086E+09 | 0.00 | 1.11 |
April | 0.435642E+10 | 0.00 | 0.00 | 2503577.96 | 0.00 | 0.135941E+10 | 0.207067E+10 | 0.00 | 1.24 |
May | 0.329255E+10 | 3815396.42 | 0.00 | 4774126.18 | 2732611.03 | 0.877710E+09 | 0.328108E+10 | 0.00 | 1.46 |
June | 0.164404E+10 | 62825775.22 | 0.00 | 10688358.93 | 3035293.86 | 30079249.46 | 0.413030E+10 | 0.00 | 2.07 |
July | 0.864347E+09 | 0.235318E+09 | 0.00 | 13023763.39 | 10247112.13 | 0.00 | 0.309081E+10 | 0.00 | 2.07 |
August | 0.151769E+10 | 0.171331E+09 | 0.00 | 9345356.94 | 13669854.50 | 13565718.08 | 0.322958E+10 | 0.00 | 2.00 |
September | 0.299101E+10 | 76289992.33 | 0.00 | 4110245.83 | 10797604.10 | 0.374424E+09 | 0.199877E+10 | 0.00 | 1.46 |
October | 0.468963E+10 | 0.00 | 0.00 | 727102.49 | 109300.33 | 0.136793E+10 | 0.627617E+09 | 0.00 | 1.18 |
November | 0.359076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440450E+10 | 0.00 | 0.00 | 1.06 |
December | 0.172130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912625E+10 | 0.00 | 0.00 | 1.02 |
Annual Sum or Average | 0.339937E+11 | 0.549581E+09 | 0.00 | 45554554.13 | 40591775.95 | 0.403091E+11 | 0.189446E+11 | 0.00 | 1.40 |
Minimum of Months | 0.864347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
Maximum of Months | 0.529786E+10 | 0.235318E+09 | 0.00 | 13023763.39 | 13669854.50 | 0.116782E+11 | 0.413030E+10 | 0.00 | 2.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406423E+10 | 0.00 | 0.00 | 652142.82 | 0.00 | 0.117249E+11 | 0.111337E+10 | 0.00 | 0.87 |
February | 0.467755E+10 | 0.00 | 0.00 | 3724128.52 | 0.00 | 0.629027E+10 | 0.303293E+10 | 0.00 | 1.04 |
March | 0.616947E+10 | 0.00 | 0.00 | 5405258.98 | 0.00 | 0.438197E+10 | 0.455652E+10 | 0.00 | 1.11 |
April | 0.522017E+10 | 0.00 | 0.00 | 5321254.76 | 0.00 | 0.188772E+10 | 0.398149E+10 | 0.00 | 1.19 |
May | 0.437445E+10 | 7435691.72 | 0.00 | 6769467.88 | 3557150.48 | 0.143954E+10 | 0.413163E+10 | 0.00 | 1.31 |
June | 0.288863E+10 | 0.100494E+09 | 0.00 | 9697431.00 | 3951164.98 | 61471951.67 | 0.378894E+10 | 0.00 | 1.57 |
July | 0.170017E+10 | 0.399080E+09 | 0.00 | 11075997.65 | 13339080.98 | 0.00 | 0.245754E+10 | 0.00 | 1.52 |
August | 0.218038E+10 | 0.339871E+09 | 0.00 | 13153242.84 | 13489669.18 | 41441033.38 | 0.376148E+10 | 0.00 | 1.81 |
September | 0.324216E+10 | 0.226296E+09 | 0.00 | 11139893.65 | 5751733.94 | 0.497465E+09 | 0.476203E+10 | 0.00 | 1.67 |
October | 0.465603E+10 | 159548.23 | 0.00 | 9737689.45 | 0.00 | 0.111185E+10 | 0.529500E+10 | 0.00 | 1.39 |
November | 0.463232E+10 | 0.00 | 0.00 | 3707336.01 | 0.00 | 0.392262E+10 | 0.321523E+10 | 0.00 | 1.02 |
December | 0.452772E+10 | 0.00 | 0.00 | 1228921.99 | 0.00 | 0.847827E+10 | 0.146303E+10 | 0.00 | 0.88 |
Annual Sum or Average | 0.483333E+11 | 0.107334E+10 | 0.00 | 81612765.56 | 40088799.55 | 0.398375E+11 | 0.415592E+11 | 0.00 | 1.28 |
Minimum of Months | 0.170017E+10 | 0.00 | 0.00 | 652142.82 | 0.00 | 0.00 | 0.111337E+10 | 0.00 | 0.87 |
Maximum of Months | 0.616947E+10 | 0.399080E+09 | 0.00 | 13153242.84 | 13489669.18 | 0.117249E+11 | 0.529500E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129766E+11 | 0.00 | 0.00 | 1.16 |
February | 0.356408E+10 | 0.00 | 0.00 | 221352.51 | 0.00 | 0.743077E+10 | 0.241363E+09 | 0.00 | 1.22 |
March | 0.615823E+10 | 0.00 | 0.00 | 791622.06 | 0.00 | 0.453313E+10 | 0.805990E+09 | 0.00 | 1.28 |
April | 0.585973E+10 | 0.00 | 0.00 | 2287625.37 | 0.00 | 0.135384E+10 | 0.163318E+10 | 0.00 | 1.43 |
May | 0.453909E+10 | 4734339.14 | 0.00 | 5359278.51 | 3115045.31 | 0.905581E+09 | 0.295529E+10 | 0.00 | 1.68 |
June | 0.262891E+10 | 98465511.97 | 0.00 | 8324131.52 | 1024171.20 | 40227354.44 | 0.296927E+10 | 0.00 | 2.05 |
July | 0.151930E+10 | 0.372567E+09 | 0.00 | 9124437.30 | 4246721.45 | 0.00 | 0.180877E+10 | 0.00 | 1.86 |
August | 0.214832E+10 | 0.237204E+09 | 0.00 | 6858620.08 | 7895738.85 | 36526324.53 | 0.215477E+10 | 0.00 | 1.91 |
September | 0.396484E+10 | 0.120321E+09 | 0.00 | 3441369.25 | 4566832.39 | 0.420776E+09 | 0.157313E+10 | 0.00 | 1.64 |
October | 0.542362E+10 | 0.00 | 0.00 | 1239342.32 | 124597.13 | 0.135864E+10 | 0.929600E+09 | 0.00 | 1.38 |
November | 0.439318E+10 | 0.00 | 0.00 | 127391.62 | 0.00 | 0.448468E+10 | 0.224014E+09 | 0.00 | 1.21 |
December | 0.267619E+10 | 0.00 | 0.00 | 421.38 | 0.00 | 0.964218E+10 | 10132693.15 | 0.00 | 1.16 |
Annual Sum or Average | 0.443034E+11 | 0.833292E+09 | 0.00 | 37775591.92 | 20973106.33 | 0.431830E+11 | 0.153055E+11 | 0.00 | 1.50 |
Minimum of Months | 0.142793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Maximum of Months | 0.615823E+10 | 0.372567E+09 | 0.00 | 9124437.30 | 7895738.85 | 0.129766E+11 | 0.296927E+10 | 0.00 | 2.05 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16595666.86 | 0.00 | 0.00 | 2218040.25 | 0.00 | 0.00 | 0.833107E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7049352.96 | 0.00 | 0.00 | 0.645519E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 13705713.73 | 0.00 | 0.00 | 0.660970E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17215289.28 | 0.00 | 0.00 | 0.462854E+09 | 0.00 | 0.29 |
May | 0.00 | 143399.66 | 0.00 | 3900858.10 | 0.00 | 0.00 | 0.407828E+09 | 0.00 | 0.29 |
June | 0.00 | 13403669.55 | 0.00 | 7431706.91 | 0.00 | 0.00 | 0.201194E+09 | 0.00 | 0.30 |
July | 0.00 | 21322335.00 | 0.00 | 9021917.80 | 0.00 | 0.00 | 81813280.51 | 0.00 | 0.28 |
August | 0.00 | 5612491.84 | 0.00 | 16503821.57 | 0.00 | 0.00 | 0.152172E+09 | 0.00 | 0.31 |
September | 0.00 | 11368597.48 | 0.00 | 3451254.10 | 0.00 | 0.00 | 0.257568E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8277901.24 | 0.00 | 0.00 | 0.439690E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12063774.15 | 0.00 | 0.00 | 0.543950E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16568441.08 | 0.00 | 0.00 | 0.716686E+09 | 0.00 | 0.28 |
Annual Sum or Average | 16595666.86 | 51850493.53 | 0.00 | 0.117408E+09 | 0.00 | 0.00 | 0.540335E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2218040.25 | 0.00 | 0.00 | 81813280.51 | 0.00 | 0.28 |
Maximum of Months | 16595666.86 | 21322335.00 | 0.00 | 17215289.28 | 0.00 | 0.00 | 0.833107E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291351E+10 | 0.00 | 0.00 | 8147513.27 | 0.00 | 0.00 | 0.552456E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 54758098.88 | 0.00 | 0.00 | 0.647117E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.118463E+09 | 0.00 | 0.00 | 0.662790E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.156928E+09 | 0.00 | 0.00 | 0.464116E+10 | 0.00 | 0.29 |
May | 0.00 | 1351187.95 | 0.00 | 31291592.59 | 0.00 | 0.00 | 0.409093E+10 | 0.00 | 0.29 |
June | 0.00 | 0.132730E+09 | 0.00 | 68601801.57 | 0.00 | 0.00 | 0.201973E+10 | 0.00 | 0.30 |
July | 0.00 | 0.212285E+09 | 0.00 | 85232475.30 | 0.00 | 0.00 | 0.823344E+09 | 0.00 | 0.28 |
August | 0.00 | 58666637.34 | 0.00 | 0.154427E+09 | 0.00 | 0.00 | 0.152739E+10 | 0.00 | 0.31 |
September | 0.00 | 0.110849E+09 | 0.00 | 28184791.85 | 0.00 | 0.00 | 0.259714E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 70934306.57 | 0.00 | 0.00 | 0.440798E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.103582E+09 | 0.00 | 0.00 | 0.545556E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.142294E+09 | 0.00 | 0.00 | 0.718798E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.291351E+10 | 0.515882E+09 | 0.00 | 0.102284E+10 | 0.00 | 0.00 | 0.513748E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8147513.27 | 0.00 | 0.00 | 0.823344E+09 | 0.00 | 0.28 |
Maximum of Months | 0.291351E+10 | 0.212285E+09 | 0.00 | 0.156928E+09 | 0.00 | 0.00 | 0.718798E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606268E+09 | 0.00 | 0.00 | 246534.67 | 0.00 | 0.00 | 0.218872E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4492817.06 | 0.00 | 0.00 | 0.648037E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 10827164.88 | 0.00 | 0.00 | 0.663825E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14980378.05 | 0.00 | 0.00 | 0.464987E+09 | 0.00 | 0.29 |
May | 28709560.03 | 137152.95 | 0.00 | 2677942.54 | 0.00 | 0.00 | 0.380144E+09 | 0.00 | 0.29 |
June | 0.00 | 13309660.90 | 0.00 | 6718166.48 | 0.00 | 0.00 | 0.202326E+09 | 0.00 | 0.30 |
July | 0.00 | 21232271.97 | 0.00 | 8493275.44 | 0.00 | 0.00 | 82479775.99 | 0.00 | 0.28 |
August | 0.00 | 5906715.87 | 0.00 | 15302650.64 | 0.00 | 0.00 | 0.152866E+09 | 0.00 | 0.31 |
September | 7047073.91 | 11064536.49 | 0.00 | 2419627.78 | 0.00 | 0.00 | 0.254285E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6269141.26 | 0.00 | 0.00 | 0.441886E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9298106.52 | 0.00 | 0.00 | 0.546674E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13079601.28 | 0.00 | 0.00 | 0.720045E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.642025E+09 | 51650338.19 | 0.00 | 94805406.61 | 0.00 | 0.00 | 0.477643E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 246534.67 | 0.00 | 0.00 | 82479775.99 | 0.00 | 0.28 |
Maximum of Months | 0.606268E+09 | 21232271.97 | 0.00 | 15302650.64 | 0.00 | 0.00 | 0.720045E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.216601E+09 | 0.00 | 0.00 | 0.230704E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.407125E+09 | 0.00 | 0.00 | 0.176929E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.712707E+09 | 0.00 | 0.00 | 0.179595E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.863455E+09 | 0.00 | 0.00 | 0.123157E+11 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.220047E+09 | 0.00 | 0.00 | 0.110013E+11 | 0.00 | 0.33 |
June | 0.00 | 0.269553E+09 | 0.00 | 0.378334E+09 | 0.00 | 0.00 | 0.531985E+10 | 0.00 | 0.34 |
July | 0.00 | 0.421842E+09 | 0.00 | 0.459977E+09 | 0.00 | 0.00 | 0.221016E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.935221E+09 | 0.00 | 0.00 | 0.549376E+10 | 0.00 | 0.35 |
September | 0.00 | 0.251405E+09 | 0.00 | 0.195488E+09 | 0.00 | 0.00 | 0.667052E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.436266E+09 | 0.00 | 0.00 | 0.114184E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.629818E+09 | 0.00 | 0.00 | 0.145839E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.866095E+09 | 0.00 | 0.00 | 0.192765E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.942800E+09 | 0.00 | 0.632113E+10 | 0.00 | 0.00 | 0.147013E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.195488E+09 | 0.00 | 0.00 | 0.221016E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.421842E+09 | 0.00 | 0.935221E+09 | 0.00 | 0.00 | 0.230704E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.279061E+12 | 0.456807E+11 | 0.00 | 0.211017E+13 | 0.866305E+12 |
February | 0.371583E+12 | 0.356649E+11 | 0.00 | 0.188299E+13 | 0.108466E+13 |
March | 0.634618E+12 | 0.333850E+11 | 0.00 | 0.216405E+13 | 0.155326E+13 |
April | 0.679568E+12 | 0.239685E+11 | 0.00 | 0.215028E+13 | 0.194596E+13 |
May | 0.893715E+12 | 0.236969E+11 | 0.00 | 0.206377E+13 | 0.912854E+12 |
June | 0.976872E+12 | 0.121997E+11 | 0.00 | 0.169231E+13 | 0.190803E+13 |
July | 0.967427E+12 | 0.779028E+10 | 0.00 | 0.131988E+13 | 0.300940E+13 |
August | 0.805540E+12 | 0.853993E+10 | 0.00 | 0.149249E+13 | 0.321949E+13 |
September | 0.607826E+12 | 0.157173E+11 | 0.00 | 0.177507E+13 | 0.122632E+13 |
October | 0.401095E+12 | 0.230578E+11 | 0.00 | 0.221642E+13 | 0.121403E+13 |
November | 0.221802E+12 | 0.322648E+11 | 0.00 | 0.206027E+13 | 0.150257E+13 |
December | 0.183626E+12 | 0.408763E+11 | 0.00 | 0.203107E+13 | 0.203871E+13 |
Annual Sum or Average | 0.702273E+13 | 0.302842E+12 | 0.00 | 0.229588E+14 | 0.204816E+14 |
Minimum of Months | 0.183626E+12 | 0.779028E+10 | 0.00 | 0.131988E+13 | 0.866305E+12 |
Maximum of Months | 0.976872E+12 | 0.456807E+11 | 0.00 | 0.221642E+13 | 0.321949E+13 |