Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750

Simulation Timestamp: 2023-10-16 09:02:59


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 36677.09 791.81 791.81
Net Site Energy 36677.09 791.81 791.81
Total Source Energy 102575.17 2214.47 2214.47
Net Source Energy 102575.17 2214.47 2214.47


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 5671.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3247.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 903.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1997.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2738.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 434.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 837.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3086.19
Humidification 841.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.99
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 848.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 30157.09 6520.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5679.35
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 5671.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3247.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 903.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 61.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2738.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 434.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 837.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3086.19
Humidification General 841.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.99
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 848.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 5671.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3247.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 903.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1997.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2738.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 434.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 837.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3086.19
Humidification Unassigned 841.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.99
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 848.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 104.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 174.88 140.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12
Other 371.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 651.05 140.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 104.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 174.88 140.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12
Other 371.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 651.05 140.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 30157.088 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 30157.088 100.00
     
Total On-Site and Utility Electric Sources 30157.088 100.00
Total Electricity End Uses 30157.088 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5679.35 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5679.35 100.00
Total Water End Uses 5679.35 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 113.17
Time Setpoint Not Met During Occupied Cooling 485.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 5942.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Latitude [deg] 47.47
Longitude [deg] -111.4
Elevation [m] 1117.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.1390 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.1390 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.1631 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.1631 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1390 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.1390 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.1390 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.1390 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.1390 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.1390 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.1390 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.1390 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.1390 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.1390 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.1390 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.1390 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.1390 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.1390 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.1390 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.1390 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 11.7111 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 11.7111 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 11.7111 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.1390 18.58 484.4232  
Total 46320.38             9.1631 9.29 17.8789  
Conditioned Total 46320.38             9.1631 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8180 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:30 09-JAN-07:10 - - - - - - - - - - 17-JUL-15:00
Heating 0.00 3008975.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 476400.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 86589.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 277580.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 65860.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 83442.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 16074.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 33067.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2144185.78 3042043.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 3008975.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 476400.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5474.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 277580.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 65860.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 83442.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 16074.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 33067.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 6148.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10284.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12485.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2860.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6326.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8673.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1377.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2653.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 2664.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 919.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 95507.50 7067.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 132.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 222.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 136.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 187.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 29.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 57.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 57.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2061.89 152.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 132.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 222.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 136.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 187.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 29.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 57.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 57.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2061.89 152.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 6.42
DATACENTER_BOT_ZN_6 DIRECT AIR 0.564620
DATACENTER_MID_ZN_6 DIRECT AIR 5.40
DATACENTER_TOP_ZN_6 DIRECT AIR 0.550025
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 24.46
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.75 0.281949 0.300000 2.02 0.751865 0.500000 0.001351 0.000235 2.02 12.80 0.008000
CORE_MID VAV BOX COMPONENT 63.39 0.300031 0.300000 19.02 0.800083 0.500000 0.001270 0.004534 19.02 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.14 0.310016 0.300000 1.84 0.826710 0.500000 0.001229 0.001000 3.89 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.08 0.221837 0.300000 0.322967 0.591566 0.500000 0.001717 0.000174 0.679405 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.34 0.115112 0.300000 0.401102 0.306965 0.500000 0.003310 0.000120 0.466446 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.69 0.141219 0.300000 0.507351 0.376584 0.500000 0.002698 0.000192 0.747402 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.67 0.092377 0.300000 0.499814 0.300000 0.500000 0.004124 0.000108 0.499814 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 10.13 0.235729 0.300000 3.04 0.628610 0.500000 0.001616 0.002496 9.73 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 14.07 0.109422 0.300000 4.22 0.300000 0.500000 0.003482 0.001655 6.46 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 17.01 0.140391 0.300000 5.10 0.374377 0.500000 0.002714 0.002526 9.85 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 15.10 0.101933 0.300000 4.53 0.300000 0.500000 0.003738 0.001622 6.33 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.28 0.186008 0.300000 0.385177 0.496022 0.500000 0.002048 0.000329 1.28 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.41 0.109139 0.300000 0.423052 0.300000 0.500000 0.003491 0.000217 0.847139 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.84 0.130102 0.300000 0.550703 0.346939 0.500000 0.002928 0.000333 1.30 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.61 0.095740 0.300000 0.482259 0.300000 0.500000 0.003980 0.000217 0.845030 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 26868.26 0.000235 570.16
CORE_MID VAV BOX REHEAT COIL 518248.16 0.004534 13242.68
CORE_TOP VAV BOX REHEAT COIL 114310.89 0.001000 3016.10
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 19921.41 0.000174 525.39
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 13675.36 0.000120 360.64
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 21911.67 0.000192 577.83
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 12346.71 0.000108 303.95
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 285251.84 0.002496 7520.59
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 189222.60 0.001655 4988.71
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 288704.02 0.002526 7611.56
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 185387.20 0.001622 4887.64
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 37609.66 0.000329 991.43
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 24814.38 0.000217 654.12
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 38037.39 0.000333 1002.70
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 24752.52 0.000217 652.49
VAV_BOT WITH REHEAT HEATING COIL 100624.94 0.000880 1540.99
VAV_MID WITH REHEAT HEATING COIL 1087733.29 0.009516 15999.52
VAV_TOP WITH REHEAT HEATING COIL 113866.20 0.000996 1704.28
CAV_BAS HEATING COIL 306811.68 0.002684 6559.52
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 6.26 3.76 12.52 3.76 10.86 10.86 0.300000 0.345837 10.86
VAV_MID WITH REHEAT 59.85 35.91 119.70 49.36 100.56 100.56 0.300000 0.490834 100.56
VAV_TOP WITH REHEAT 6.14 3.68 12.27 8.17 11.24 11.24 0.300000 0.726914 11.24
CAV_BAS 6.42 6.42 6.42 6.42 6.42 6.42 1.00 1.00 6.42
AIRLOOP DATACENTER BASEMENT 24.46 24.46 24.46 24.46 24.46 24.46 1.00 0.999991 24.46
AIRLOOP DATACENTER BOT 0.564620 0.564620 0.564620 0.564620 0.564620 0.564620 1.00 1.00 0.564620
AIRLOOP DATACENTER MID 5.40 5.40 5.40 5.40 5.40 5.40 1.00 1.00 5.40
AIRLOOP DATACENTER TOP 0.550025 0.550025 0.550025 0.550025 0.550025 0.550025 1.00 1.00 0.550025
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.86 2.51
VAV_MID WITH REHEAT_OA_CONTROLLER 100.56 26.05
VAV_TOP WITH REHEAT_OA_CONTROLLER 11.24 2.77
CAV_BAS_OA_CONTROLLER 6.42 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 24.46 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.564620 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.40 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.550025 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.21 6.67 10.68 0.007087 0.007000 183273.83 0.007797 10.86
VAV_MID WITH REHEAT COOLING COIL 26.52 6.67 10.68 0.007069 0.007000 1725379.89 0.073402 100.56
VAV_TOP WITH REHEAT COOLING COIL 26.32 6.67 10.68 0.007053 0.007000 190044.12 0.008085 11.24
CAV_BAS COOLING COIL 25.81 6.67 11.09 0.007243 0.007000 105528.98 0.004489 6.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.86
VAV_MID WITH REHEAT FAN 100.56
VAV_TOP WITH REHEAT FAN 11.24
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007797 0.000061
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000880  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.073402 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.009516  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.008085 0.000059
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000996  
CAV_BAS_COOLC_CONTROLLER 0.004489 0.000106
CAV_BAS_HEATC_CONTROLLER 0.002684  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 6.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 24.46 464992.53 261685.82 0.011388
AIRLOOP DATACENTER BOT COOLING COIL 0.564620 10430.86 5931.89 0.000255
AIRLOOP DATACENTER MID COOLING COIL 5.40 99842.12 56766.72 0.002445
AIRLOOP DATACENTER TOP COOLING COIL 0.550025 10163.31 5778.98 0.000249
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 24.46 24.46 24.46 24.46 464992.53 464992.53 24207.99 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.564620 0.564620 0.564620 0.564620 10430.86 10430.86 1118.31 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.40 5.40 5.40 5.40 99842.12 99842.12 11183.09 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.550025 0.550025 0.550025 0.550025 10163.31 10163.31 1118.31 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 24.46
AIRLOOP DATACENTER BOT SUPPLY FAN 0.564620
AIRLOOP DATACENTER MID SUPPLY FAN 5.40
AIRLOOP DATACENTER TOP SUPPLY FAN 0.550025
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 24.46 464992.53 0.011388
AIRLOOP DATACENTER BOT HEATING COIL 0.564620 10430.86 0.000255
AIRLOOP DATACENTER MID HEATING COIL 5.40 99842.12 0.002445
AIRLOOP DATACENTER TOP HEATING COIL 0.550025 10163.31 0.000249
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 24207.99
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1118.31
AIRLOOP DATACENTER MID_SUPPHEATCOIL 11183.09
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1118.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000190 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.093773 19323.12  
HEATSYS1 PUMP 0.029833 8984.40 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.093773 11.25
HEATSYS1 0.029833 3.58
COOLSYS1_SUPPLY 0.093773 11.25
SINGLE WATER PLANT LOOP 0.014337 1.72
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.093773 0.093773 393611.93 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 3410098.20 3410098.20 0.029833
CENTRAL BOILER 590566.19 577839.35 0.014337
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.093773 13378.05
PLANT CIRC PUMP 0.014337 3656.68
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.093773 0.047217 1112603.77 1117881.23 0.055531
COOLSYS1 CHILLER2 0.093773 0.047217 1112603.77 1117881.23 0.055531
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.014337 139666.47 55731.90 69833.23 7879.72 21042.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.111062 13.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.111062 33449.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 51.45 1328003.32 10.29 166000.41
TOWERWATERSYS COOLTOWER 2 51.45 1328003.32 10.29 166000.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.057460
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 8.60 2.80 -4.10 -8.80 -2.20 0.30 6.70 10.10 16.50 20.60 19.20 14.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Great Falls Intl Arpt MT USA TMY3 WMO#=727750 47.47 -111.38 -7.00 1117.00 88606 1.0531


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 7.03 29.40 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.139 4.842 0.000 0.000 0.000 0.000 13.981 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.139 484.423 0.000 0.000 0.000 0.000 493.562 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25401.240 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25401.240
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7162.063 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7162.063
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.132 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.057 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.468 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7163
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7788
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5137
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 0.13403145E-14 0.38554392E-16 -0.14019045E-09 -0.57508437E-17
51 8 0.20532604E-07 0.15070655E-12 0.36354762E-03 -0.23346278E-09
52 7 -0.11816003E-01 0.79423826E-08 -0.22472937E-01 0.13435225E-03
53 6 0.39378663 0.27841024E-05 0.46223068 -0.46114540E-02
54 5 -5.0777070 0.10463539E-03 -4.3654760 0.61784485E-01
55 4 32.503611 0.86100720E-03 21.143998 -0.41549437
56 3 -110.16389 0.18863771E-02 -55.038103 1.4998468
57 2 196.07818 0.10660615E-02 77.337676 -2.8839958
58 1 -170.77553 0.11429885E-03 -55.098892 2.7387699
59 0 57.057407 0.65377189E-06 15.584712  
60 9 -0.15090952E-15 0.38559946E-16 -0.14372032E-09 0.30204083E-17
61 8 0.21031043E-07 0.14138600E-12 0.36887497E-03 -0.23913020E-09
62 7 -0.11975277E-01 0.74086432E-08 -0.22702364E-01 0.13616326E-03
63 6 0.39811484 0.25910953E-05 0.46592450 -0.46624730E-02
64 5 -5.1199506 0.97191092E-04 -4.3938804 0.62308282E-01
65 4 32.690498 0.79834332E-03 21.255101 -0.41797567
66 3 -110.56161 0.17463541E-02 -55.257788 1.5055927
67 2 196.47247 0.98555898E-03 77.539021 -2.8902570
68 1 -170.92122 0.10553222E-03 -55.157180 2.7413232
69 0 57.057407 0.60276357E-06 15.574872  
70 9 0.86852889E-15 0.51837175E-16 -0.12412508E-09 -0.62404215E-17
71 8 0.18264368E-07 0.19079871E-12 0.33872361E-03 -0.20767217E-09
72 7 -0.11071833E-01 0.10339392E-07 -0.21400306E-01 0.12589076E-03
73 6 0.37356127 0.36650528E-05 0.44491930 -0.43730477E-02
74 5 -4.8802711 0.13907014E-03 -4.2321352 0.59336424E-01
75 4 31.629927 0.11542129E-02 20.621944 -0.40389484
76 3 -108.30396 0.25479898E-02 -54.005619 1.4729777
77 2 194.23353 0.14496506E-02 76.392304 -2.8547049
78 1 -170.09368 0.15639004E-03 -54.826917 2.7268196
79 0 57.057407 0.90049143E-06 15.632017  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.3622_SHGC_EAST_0.4 35 1 VerySmooth 2.058 2.058 1.000 0.401    
2 WINDOW_U_0.3622_SHGC_SOUTH_0.4 36 1 VerySmooth 2.058 2.058 1.000 0.401    
3 WINDOW_U_0.3622_SHGC_WEST_0.4 37 1 VerySmooth 2.058 2.058 1.000 0.401    
4 WINDOW_U_0.3622_SHGC_NORTH_0.4 38 1 VerySmooth 2.058 2.058 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.63487E-002 0.31435 0.48131 0.48131 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11603 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 77734.26176 77734.26176 6.41994 6.41994 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 81690.28724 81690.28724 6.74605 6.74605 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 9046.60604 9046.60604 0.43772 1.07782 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 767846.42320 767846.42320 63.39486 63.39486 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 350772.16234 350772.16234 16.98417 16.98417 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 74316.21799 74316.21799 6.13530 6.13530 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 21.56000 6.28881E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 80015.37239 80015.37239 3.89458 3.89458 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12923.61332 12923.61332 1.07656 1.07656 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.40000 6.30683E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 13941.81357 13941.81357 0.67941 0.67941 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 16050.32941 16050.32941 1.33701 1.33701 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.09333 6.29258E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 9569.96367 9569.96367 0.46645 0.46645 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 20301.89060 20301.89060 1.69117 1.69117 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 33.13333 6.30642E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 15333.21178 15333.21178 0.74740 0.74740 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 20000.40897 20000.40897 1.66605 1.66605 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 7948.46912 7948.46912 0.38717 0.38717 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 121621.55872 121621.55872 10.13116 10.13116 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.40000 6.30683E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 199600.44822 199600.44822 9.73489 9.73489 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 168850.87456 168850.87456 14.06527 14.06527 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 25.96000 6.29539E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 132403.62029 132403.62029 6.45793 6.45793 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 204218.06836 204218.06836 17.01144 17.01144 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 33.26667 6.30663E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 202014.07413 202014.07413 9.85285 9.85285 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 181256.07217 181256.07217 15.09864 15.09864 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 129721.79218 129721.79218 6.32691 6.32691 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13852.39605 13852.39605 1.15391 1.15391 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.08000 6.30633E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 26313.23705 26313.23705 1.28392 1.28392 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 16928.91541 16928.91541 1.41017 1.41017 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 26.41333 6.29608E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 17361.04710 17361.04710 0.84714 0.84714 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 22036.96753 22036.96753 1.83568 1.83568 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40000 6.30683E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 26612.30622 26612.30622 1.29854 1.29854 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 19298.14147 19298.14147 1.60753 1.60753 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36000 6.30211E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 17317.75698 17317.75698 0.84503 0.84503 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60000 3.41898E-004 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8593.43284 8593.43284 0.56462 0.56462 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 82226.56401 82226.56401 5.40262 5.40262 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 26.28000 6.29588E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -27.60000 3.41898E-004 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8371.25934 8371.25934 0.55002 0.55002 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 26.57333 6.29632E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -27.60000 3.41898E-004 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 372312.11499 372312.11499 24.46196 24.46196 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.84000 6.28481E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:20:00 -27.60000 3.41898E-004 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 151240.75 10.85785 10.85785 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 106928.19 3.35825 3.35825 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00
3 VAV_MID WITH REHEAT Cooling Sensible 1411894.46 100.55697 100.55697 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1108519.27 49.35675 49.35675 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:50:00
5 VAV_TOP WITH REHEAT Cooling Sensible 160266.96 11.23820 11.23820 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 118096.35 8.16921 8.16921 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00
7 CAV_BAS Cooling Sensible 78394.65 6.41994 6.41994 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 85856.97 1.20016 1.20016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369378.91 24.46219 24.46219 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 24207.99 0.33839 0.33839 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8472.07 0.56462 0.56462 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 81059.37 5.40262 5.40262 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 11183.09 0.15632 0.15632 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8257.36 0.55002 0.55002 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1118.31 1.56323E-002 1.56323E-002 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.41994
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.74605
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28195
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02382
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75186
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.35131E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.35055E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.02382
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26868.26419
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.35055E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 570.16425
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 63.39486
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30003
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.01846
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80008
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26987E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.53386E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.01846
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 518248.15676
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.53386E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 13242.68484
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.13530
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31002
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.84059
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82671
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22897E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00004E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.89458
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 114310.89202
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00004E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3016.09562
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07656
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22184
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32297
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59157
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.71748E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74281E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.67941
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19921.40865
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74281E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 525.38526
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.33701
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11511
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40110
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30696
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30983E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.19638E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.46645
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13675.36324
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.19638E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 360.63846
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.69117
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14122
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.50735
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37658
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.69793E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.91693E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74740
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21911.66933
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.91693E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 577.83145
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.66605
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.23773E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.49981
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.12439E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08014E-004
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.49981
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12346.70640
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08014E-004
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 303.94549
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.13116
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23573
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.03935
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62861
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.61626E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.49551E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.73489
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 285251.83801
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.49551E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7520.59249
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.06527
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10942
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.21958
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.48193E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.65540E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.45793
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 189222.60353
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.65540E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4988.71263
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 17.01144
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14039
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.10343
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37438
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.71384E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.52571E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.85285
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 288704.01805
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.52571E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7611.55591
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 15.09864
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10193
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.52959
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.73775E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.62185E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.32691
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 185387.20177
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.62185E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4887.63798
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.28392
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18601
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38518
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49602
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.04830E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.29026E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.28392
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 37609.65682
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.29026E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 991.42581
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.41017
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10914
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.42305
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.49095E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.17087E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84714
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24814.38462
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.17087E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 654.12259
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.83568
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13010
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.55070
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34694
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.92847E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.32768E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.29854
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 38037.39215
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.32768E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1002.69664
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.60753
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.57402E-002
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.48226
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.97952E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.16546E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84503
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24752.51948
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.16546E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 652.49089
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.56462
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.40262
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.55002
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 24.46196
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.25842
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.75505
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 12.51683
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.75505
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.85785
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.85785
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34584
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 59.85068
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 35.91041
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 119.70137
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 49.35675
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 100.55697
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 100.55697
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.49083
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.13630
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.68178
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 12.27260
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 8.16921
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 11.23820
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 11.23820
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.72691
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 6.41994
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 6.41994
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 6.41994
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 6.41994
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 6.41994
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 6.41994
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.46196
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.46196
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.46196
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 24.46196
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 24.46219
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 24.46219
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.56462
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.56462
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.56462
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.56462
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.56462
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.56462
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.40262
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.40262
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.40262
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.40262
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.40262
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.40262
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.55002
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.55002
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.55002
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.55002
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.55002
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.55002
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.85785
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 100.55697
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 11.23820
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 6.41994
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 24.46219
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.56462
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.40262
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.55002
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.85785
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.50608
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.20937
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68120
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.08718E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 183273.83040
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.79689E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.85785
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 100624.94488
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.80311E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1540.98634
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.85785
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.79689E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.10744E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.80311E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 100.55697
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 26.04512
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.51607
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68113
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.06855E-003
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1725379.88709
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.34016E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 100.55697
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 1087733.29347
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.51597E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 15999.52356
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 100.55697
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.34016E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.48746E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.51597E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 11.23820
323 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.76931
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.32370
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.68107
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.05309E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 190044.12238
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 8.08492E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 11.23820
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 113866.20461
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.96151E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1704.28059
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 11.23820
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 8.08492E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.88986E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.96151E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.41994
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.81181
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.08693
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.24345E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 105528.97885
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.48945E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.41994
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 306811.68402
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.68412E-003
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6559.51887
352 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 6.41994
353 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.48945E-003
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.06069E-004
355 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.68412E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.46219
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 24.46219
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 464992.52754
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 261685.82449
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.13876E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 24.46219
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 24.46219
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 24.46219
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 24.46219
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 464992.52754
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 464992.52754
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 24207.99248
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 24.46219
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 24.46219
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 464992.52754
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.13876E-002
374 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 24207.99248
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.90481E-004
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.56462
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.56462
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10430.86373
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5931.89024
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.55451E-004
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.56462
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.56462
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.56462
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.56462
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10430.86373
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10430.86373
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.56462
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.56462
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10430.86373
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.55451E-004
397 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
398 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.40262
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.40262
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 99842.11851
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 56766.71986
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.44513E-003
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.40262
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.40262
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.40262
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.40262
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 99842.11851
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 99842.11851
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 11183.08965
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.40262
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.40262
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 99842.11851
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.44513E-003
416 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 11183.08965
417 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.55002
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.55002
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 10163.31163
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5778.97971
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.48899E-004
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.55002
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.55002
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.55002
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.55002
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 10163.31163
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 10163.31163
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1118.30896
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.55002
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.55002
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 10163.31163
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.48899E-004
435 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1118.30896
436 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 9.37729E-002
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 19323.12004
438 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 9.37729E-002
439 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 11.25275
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 9.37729E-002
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 9.37729E-002
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 393611.93191
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
444 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.98330E-002
445 PlantLoop HEATSYS1 Plant Loop Volume [m3] 3.57996
446 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.98330E-002
447 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 8984.39752
448 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 3410098.20200
450 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 3410098.20000
451 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.98330E-002
452 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 9.37729E-002
453 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 11.25275
454 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 9.37729E-002
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 13378.04782
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 9.37729E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.72168E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1112603.77213
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1117881.23000
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.55312E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 9.37729E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.72168E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1112603.77213
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1117881.23000
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.55312E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.43371E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.72045
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.43371E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3656.68107
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.43371E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
472 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 55731.89894
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21042.59405
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 590566.19050
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 577839.35000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.43371E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.11106
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 13.32749
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.11106
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 33449.59232
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 51.44999
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1328003.31862
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.29000
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 166000.41483
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 51.44999
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1328003.31862
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.29000
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 166000.41483
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.74600E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.74600E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 25472.78
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 490961.26
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 108340.07
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 18879.22
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12959.80
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 20765.07
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 11698.05
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 270313.19
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 179312.38
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 273584.23
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 175678.14
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 35639.07
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 23514.16
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 36044.36
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 23455.53
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 67231.24
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 692551.98
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 74040.47
19 Coil:Heating:Water CAV_BAS HEATING COIL 231818.43


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 306577.93 188195.96 118381.97 0.61 60730.23 615.96
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2851151.06 1747604.35 1103546.71 0.61 556147.33 5640.75
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 317321.51 194787.97 122533.53 0.61 62616.79 635.09
4 Coil:Cooling:Water CAV_BAS COOLING COIL 176484.70 109338.67 67146.03 0.62 32869.79 333.38


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.65 22.69
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.65 22.69


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_NORTH_0.4 N/A 2.058 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_EAST_0.4 N/A 2.058 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_SOUTH_0.4 N/A 2.058 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3622_SHGC_WEST_0.4 N/A 2.058 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.132 0.968   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.057 0.913   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.468 1.204   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2682970549 0.2062433537 Pass Pass 5.3039811861 16.8461679681 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 4.7631101362E-002 0.1234143227 Pass Pass 4.9521545938E-002 0.2158024786 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 6.1819386399E-003 4.4867703598E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.4636416529E-002 2.5607381975E-002 Pass Pass 0.5157456752 0.4941917390 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 4.5628708249E-002 8.7713212907E-002 Pass Pass 4.9251088785E-002 0.2145313808 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 9.8132448117E-002 0.1783916492 Pass Pass 5.0055021410E-002 0.2176738736 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1475670689 0.2115005507 Pass Pass 4.9831854794E-002 0.2170164824 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 8.9332086524E-002 0.2075590799 Pass Pass 4.8851317874E-002 0.2129635548 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.5459689789E-002 2.5224495026E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 4.8153533182E-002 7.0288590022E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1261405886 0.1211397473 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 5.0678331948E-002 5.3941280034E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.3402578637 0.3538616175 Pass Pass 6.4416502091 18.3670545428 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2338422443 0.3300664102 Pass Pass 7.8393122200 26.8831421369 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2327267458 0.2347643155 Pass Pass 1.0101832974 2.9028289440 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1994513094 0.2594152889 Pass Pass 5.3761032743 26.0523765500 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.4007449197E-002 2.2650209912E-002 Pass Pass 1.0324548387 7.5040287280 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.1198505589E-002 1.2840191595E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1136750036 8.2871047869E-002 Pass Pass 0.5238261570 0.4808271245 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.0727542664E-006 5.0614240590E-006 Pass Pass 4.1383882072E-003 3.8582895009E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 4.1367742577E-003 6.8513315476E-003 Pass Pass 5.9978743273E-002 0.1789162139 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.5501731710E-002 1.9898750053E-002 Pass Pass 4.5380103475E-003 4.5151993146E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 8.1975825311E-005 7.4935083239E-005 Pass Pass 4.5306926868E-005 1.0640075130E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 7022.73 302.84 0.00 22958.96 20481.65 50766.17



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB -27.60 0.00 -27.60 Wetbulb [C] 2.70 230.00
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 33.40 16.00 16.30 Wetbulb [C] 4.90 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 11.00 18      
May 24.00 14      
Jun 29.00 21      
Jul 6.00 9      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.968 1.132 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.968 1.132 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.968 1.132 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.968 1.132 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.913 1.057 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.913 1.057 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.913 1.057 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.913 1.057 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.204 1.468 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.204 1.468 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.204 1.468 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.204 1.468 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.968 1.132 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.968 1.132 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.968 1.132 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.968 1.132 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.913 1.057 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.913 1.057 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.913 1.057 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.913 1.057 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.204 1.468 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.204 1.468 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.204 1.468 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.204 1.468 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.3622_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.3622_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.3622_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 2.058 0.401 0.402             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.3622_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 2.058 0.401 0.402             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3622_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 869.21 2.058 0.401 0.402             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3622_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 579.48 2.058 0.401 0.402             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3622_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 869.21 2.058 0.401 0.402             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3622_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 579.48 2.058 0.401 0.402             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3622_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 86.92 2.058 0.401 0.402             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3622_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 57.95 2.058 0.401 0.402             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3622_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 86.92 2.058 0.401 0.402             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3622_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 57.95 2.058 0.401 0.402             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.058 0.401 0.402                      
North Total or Average             1043.06 2.058 0.401 0.402                      
Non-North Total or Average             2433.80 2.058 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1390 2779.43 25401.24 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 235.63
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.1390 2496.12 22812.10 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 211.61
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.1390 24961.20 228120.99 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 2116.09
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.1390 2496.12 22812.10 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 211.61
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.1390 313.41 2864.29 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.1390 313.42 2864.35 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.1390 3134.13 28642.87 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 265.70
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.1390 2019.75 18458.55 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 171.22
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.1390 3134.20 28643.49 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 265.70
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.1390 2019.75 18458.55 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 171.22
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.1390 313.41 2864.29 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.1390 313.42 2864.35 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.1390 783.68 7162.06 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 66.44
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 11.7111 36.20 423.97 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 4.37
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 11.7111 362.03 4239.75 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 43.70
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 11.7111 36.20 423.97 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 4.37
Interior Lighting Total       9.1631 46320.38 424440.34               1212.16


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 57580.60 AstronomicalClock -   83.57 83.57 903.27
Exterior Lighting Total 57580.60           903.27



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2199157.75          
HEATSYS1 BOILER Boiler:HotWater 3410098.20 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1117881.23 6.11 1069205.87 5.82 6.65 22.69
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1117881.23 6.11 1069205.87 5.82 6.65 22.69
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 577839.35 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1328003.32          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1328003.32          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 183273.83 306577.93 188195.96 118381.97 0.61 - 60730.23 615.96
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1725379.89 2851151.06 1747604.35 1103546.71 0.61 - 556147.33 5640.75
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 190044.12 317321.51 194787.97 122533.53 0.61 - 62616.79 635.09
CAV_BAS COOLING COIL Coil:Cooling:Water 105528.98 176484.70 109338.67 67146.03 0.62 - 32869.79 333.38
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   464992.53 261685.82 203306.70 0.56 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10430.86 5931.89 4498.97 0.57 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   99842.12 56766.72 43075.40 0.57 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10163.31 5778.98 4384.33 0.57 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 26868.26 25472.78 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 518248.16 490961.26 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 114310.89 108340.07 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19921.41 18879.22 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13675.36 12959.80 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 21911.67 20765.07 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12346.71 11698.05 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 285251.84 270313.19 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 189222.60 179312.38 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 288704.02 273584.23 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 185387.20 175678.14 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 37609.66 35639.07 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 24814.38 23514.16 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 38037.39 36044.36 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 24752.52 23455.53 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 100624.94 67231.24 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 1087733.29 692551.98 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 113866.20 74040.47 -
CAV_BAS HEATING COIL Coil:Heating:Water 306811.68 231818.43 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   464992.53 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10430.86 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   99842.12 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10163.31 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   24207.99 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   11183.09 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1118.31 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 10.86 24664.63 2271.59 1.00 1.12 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 100.56 228424.53 2271.59 1.00 1.08 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 11.24 25528.63 2271.59 1.00 1.11 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1110.54 6.42 11794.21 1837.12 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 24.46 40344.20 1649.25 1.00 1.14 General GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.56 632.44 1120.11 1.00 1.55 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.40 6051.52 1120.11 1.00 1.15 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.55 616.09 1120.11 1.00 1.56 General GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.093773 19323.12 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.029833 8984.40 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.093773 13378.05 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.014337 3656.68 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.111062 33449.59 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 77734.26 77734.26 27.97 6.420 6.420 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00745 21.56 0.00629 1.200 0.00
CORE_BOTTOM 81690.29 81690.29 32.73 6.746 6.746 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00738 21.56 0.00629 1.078 0.00
CORE_MID 767846.42 767846.42 307.62 63.395 63.395 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00741 21.56 0.00629 10.778 0.00
CORE_TOP 74316.22 74316.22 29.77 6.135 6.135 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00742 21.56 0.00629 1.078 0.00
PERIMETER_BOT_ZN_3 12923.61 12923.61 41.24 1.077 1.077 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00727 33.40 0.00631 0.135 0.00
PERIMETER_BOT_ZN_2 16050.33 16050.33 79.47 1.337 1.337 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00714 24.09 0.00629 0.087 0.00
PERIMETER_BOT_ZN_1 20301.89 20301.89 64.78 1.691 1.691 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00717 33.13 0.00631 0.135 0.00
PERIMETER_BOT_ZN_4 20000.41 20000.41 99.02 1.666 1.666 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00711 30.36 0.00630 0.087 0.00
PERIMETER_MID_ZN_3 121621.56 121621.56 388.06 10.131 10.131 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00725 33.40 0.00631 1.353 0.00
PERIMETER_MID_ZN_2 168850.87 168850.87 836.00 14.065 14.065 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00712 25.96 0.00630 0.872 0.00
PERIMETER_MID_ZN_1 204218.07 204218.07 651.58 17.011 17.011 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00715 33.27 0.00631 1.353 0.00
PERIMETER_MID_ZN_4 181256.07 181256.07 897.42 15.099 15.099 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00711 30.36 0.00630 0.872 0.00
PERIMETER_TOP_ZN_3 13852.40 13852.40 44.20 1.154 1.154 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00721 33.08 0.00631 0.135 0.00
PERIMETER_TOP_ZN_2 16928.92 16928.92 83.82 1.410 1.410 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00711 26.41 0.00630 0.087 0.00
PERIMETER_TOP_ZN_1 22036.97 22036.97 70.31 1.836 1.836 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00714 33.40 0.00631 0.135 0.00
PERIMETER_TOP_ZN_4 19298.14 19298.14 95.55 1.608 1.608 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00710 30.36 0.00630 0.087 0.00
DATACENTER_BOT_ZN_6 8593.43 8593.43 237.37 0.565 0.565 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00708 26.28 0.00630 0.016 0.00
DATACENTER_MID_ZN_6 82226.56 82226.56 2271.28 5.403 5.403 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 27.00 27.00 0.00709 26.28 0.00630 0.156 0.00
DATACENTER_TOP_ZN_6 8371.26 8371.26 231.23 0.550 0.550 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 27.00 27.00 0.00709 26.57 0.00630 0.016 0.00
DATACENTER_BASEMENT_ZN_6 372312.11 372312.11 475.08 24.462 24.462 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 18.84 0.00628 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 22.71 0.00034 -27.60 0.00034 1.200 0.00
CORE_BOTTOM 9046.61 9046.61 3.62 0.438 1.078 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
CORE_MID 350772.16 350772.16 140.53 16.984 16.984 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 10.778 0.00
CORE_TOP 80015.37 80015.37 32.06 3.895 3.895 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -27.60 0.00034 1.078 0.00
PERIMETER_BOT_ZN_3 13941.81 13941.81 44.48 0.679 0.679 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00777 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_2 9569.96 9569.96 47.38 0.466 0.466 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 -27.60 0.00034 0.087 0.00
PERIMETER_BOT_ZN_1 15333.21 15333.21 48.92 0.747 0.747 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 -27.60 0.00034 0.135 0.00
PERIMETER_BOT_ZN_4 7948.47 7948.47 39.35 0.387 0.387 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -27.60 0.00034 0.087 0.00
PERIMETER_MID_ZN_3 199600.45 199600.45 636.86 9.735 9.735 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_2 132403.62 132403.62 655.54 6.458 6.458 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -27.60 0.00034 0.872 0.00
PERIMETER_MID_ZN_1 202014.07 202014.07 644.55 9.853 9.853 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -27.60 0.00034 1.353 0.00
PERIMETER_MID_ZN_4 129721.79 129721.79 642.27 6.327 6.327 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 -27.60 0.00034 0.872 0.00
PERIMETER_TOP_ZN_3 26313.24 26313.24 83.96 1.284 1.284 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_2 17361.05 17361.05 85.96 0.847 0.847 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -27.60 0.00034 0.087 0.00
PERIMETER_TOP_ZN_1 26612.31 26612.31 84.91 1.299 1.299 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -27.60 0.00034 0.135 0.00
PERIMETER_TOP_ZN_4 17317.76 17317.76 85.74 0.845 0.845 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -27.60 0.00034 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.22 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.24 0.00098 -27.60 0.00034 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 19.69 0.00098 -27.60 0.00034 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:20:00 18.00 27.00 0.00700 -27.60 0.00034 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.86 10.86 3.36 3.36 10.8579 3.7551 10.8579 0.3458 0.3000
VAV_MID WITH REHEAT 100.56 100.56 49.36 49.36 100.5570 49.3568 100.5570 0.4908 0.3000
VAV_TOP WITH REHEAT 11.24 11.24 8.17 8.17 11.2382 8.1692 11.2382 0.7269 0.3000
CAV_BAS 6.42 6.42 1.20 1.20 6.4199 6.4199 6.4199 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 24.46 24.46 0.34 0.34 24.4622 24.4620 24.4622 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.56 0.56 0.02 0.02 0.5646 0.5646 0.5646 1.0000 1.0000
AIRLOOP DATACENTER MID 5.40 5.40 0.16 0.16 5.4026 5.4026 5.4026 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.55 0.55 0.02 0.02 0.5500 0.5500 0.5500 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 26868.264 26868.264 2.023815 0.00023506 570.164 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 26868.26 26868.26 2.023815 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00799998 45.2309 9046.61 0.00 26963.05 26963.05
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 518248.157 518248.157 19.018458 0.00453386 13242.685 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 518248.16 518248.16 19.018458 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 350772.16 0.00 519845.86 519845.86
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 114310.892 114310.892 3.894575 0.00100004 3016.096 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 114310.89 114310.89 3.894575 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00800000 45.2310 80015.37 0.00 114696.12 114696.12
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 19921.409 19921.409 0.679405 0.00017428 525.385 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19921.41 19921.41 0.679405 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00777109 43.9554 13941.81 0.00 19986.81 19986.81
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 13675.363 13675.363 0.466446 0.00011964 360.638 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13675.36 13675.36 0.466446 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00778325 44.0233 9569.96 0.00 13720.11 13720.11
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 21911.669 21911.669 0.747402 0.00019169 577.831 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21911.67 21911.67 0.747402 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00779929 44.1127 15333.21 0.00 21983.29 21983.29
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 12346.706 12346.706 0.499814 0.00010801 303.945 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12346.71 12346.71 0.499814 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00769762 43.5457 7948.47 0.00 12385.54 12385.54
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 285251.838 285251.838 9.734888 0.00249551 7520.592 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 285251.84 285251.84 9.734888 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00765620 43.3159 199600.45 0.00 286171.48 286171.48
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 189222.604 189222.604 6.457930 0.00165540 4988.713 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 189222.60 189222.60 6.457930 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00765483 43.3084 132403.62 0.00 189831.98 189831.98
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 288704.018 288704.018 9.852850 0.00252571 7611.556 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 288704.02 288704.02 9.852850 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00766025 43.3385 202014.07 0.00 289634.41 289634.41
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 185387.202 185387.202 6.326911 0.00162185 4887.638 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 185387.20 185387.20 6.326911 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00764787 43.2695 129721.79 0.00 185984.53 185984.53
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 37609.657 37609.657 1.283924 0.00032903 991.426 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 37609.66 37503.48 1.283924 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767579 43.4262 26313.24 0.00 37729.87 37729.87
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 24814.385 24814.385 0.847139 0.00021709 654.123 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24814.38 24814.38 0.847139 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767247 43.4078 17361.05 0.00 24893.65 24893.65
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 38037.392 38037.392 1.298539 0.00033277 1002.697 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 38037.39 38037.39 1.298539 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767927 43.4457 26612.31 0.00 38158.94 38158.94
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 24752.519 24752.519 0.845030 0.00021655 652.491 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24752.52 24752.52 0.845030 12.80 10.41 0.00800000 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 0.0000 21.00 0.00767190 43.4047 17317.76 0.00 24831.58 24831.58
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 183273.830 -999.000 10.857854 0.00779689 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 183273.83 181238.05 10.857854 26.21 14.59 0.00708718 10.68 8.51 0.00700000 33.40 0.00630683 16.37 23.0808 24.00 0.00732708 34.5623 127941.30 0.00 206597.82 203529.67
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 100624.945 100624.945 3.257356 0.00088031 1540.986 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 100624.94 100624.94 3.257356 -16.39 -16.39 0.00206690 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 76.9360 19.41 0.00772474 48.1954 33568.16 0.00 81310.18 81310.18
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1725379.887 -999.000 100.556968 0.07340165 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1725379.89 1710503.99 100.556968 26.52 14.69 0.00706855 10.68 8.51 0.00700000 33.40 0.00630683 16.37 25.9009 24.00 0.00734708 34.6554 1167681.85 0.00 1941965.12 1918087.50
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 1087733.293 1087733.293 30.167091 0.00951597 15999.524 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:50:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1087733.29 1087733.29 30.167091 -21.27 -21.27 0.00133142 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 86.3362 17.81 0.00756926 52.2232 393184.49 0.00 837237.44 837237.44
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 190044.122 -999.000 11.238205 0.00808492 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 190044.12 188760.44 11.238205 26.32 14.61 0.00705309 10.68 8.51 0.00700000 33.40 0.00630683 16.37 24.6419 24.00 0.00729826 34.4278 134431.73 0.00 214186.74 212020.38
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 113866.205 113866.205 3.371461 0.00099615 1704.281 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 113866.20 113866.20 3.371461 -19.11 -19.11 0.00162904 12.80 10.41 0.00800000 -27.60 0.00034190 -27.60 82.1398 16.98 0.00753938 54.8331 57030.40 0.00 89524.83 89524.83
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 105528.979 -999.000 6.419937 0.00448945 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 105528.98 102255.54 6.419937 25.81 14.59 0.00724345 11.09 8.68 0.00700000 32.60 0.00630558 16.10 18.6942 24.00 0.00749396 35.3405 68342.71 0.00 119059.31 116192.07
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 306811.684 306811.684 6.419937 0.00268412 6559.519 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 306811.68 306811.68 6.419937 -5.16 -9.55 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 18.6942 22.83 0.00034190 1.7505 0.00 0.00 244517.09 244517.09
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 464992.528 261685.824 24.462192 0.01138764 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 404049.62 402578.36 -999.0 28.68 15.39 0.00703191 12.80 9.41 0.00700000 33.40 0.00630683 16.37 -999.0000 27.00 0.00704209 27.8119 371832.90 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10430.864 5931.890 0.564620 0.00025545 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 9015.76 8950.35 -999.0 28.07 15.21 0.00706206 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708387 27.9731 8593.43 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 99842.119 56766.720 5.402620 0.00244513 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 86302.12 85649.12 -999.0 28.07 15.21 0.00706474 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708765 27.9880 82226.56 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10163.312 5778.980 0.550025 0.00024890 -999.000 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 8784.82 8719.42 -999.0 28.07 15.21 0.00706369 12.80 9.41 0.00700000 26.57 0.00629632 14.04 -999.0000 27.00 0.00708614 27.9820 8371.26 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 464992.528 464992.528 24.462192 0.01138764 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 464992.53 464992.53 24.462192 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3833 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10430.864 10430.864 0.564620 0.00025545 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10430.86 10430.86 0.564620 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7686 25.07 0.00098406 4.3988 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 99842.119 99842.119 5.402620 0.00244513 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 99842.12 99842.12 5.402620 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8935 23.50 0.00098408 4.8335 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 10163.312 10163.312 0.550025 0.00024890 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10163.31 10163.31 0.550025 -27.60 -27.60 0.00034190 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8421 21.94 0.00098348 5.3100 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 24207.992 24207.992 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 24207.99 24207.99 24.462192 -0.38 -0.38 0.00690790 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 1.3833 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.564620 -0.76 -5.61 0.00096628 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.7686 25.07 0.00098406 4.3988 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 11183.090 11183.090 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 11183.09 11183.09 5.402620 -0.80 -5.63 0.00096550 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8935 23.50 0.00098408 4.8335 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1118.309 1118.309 -999.0 -999.0 -999.000 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1118.31 1118.31 0.550025 -0.78 -5.62 0.00096524 40.00 19.63 0.00800000 -27.60 0.00034190 -27.60 2.8421 21.94 0.00098348 5.3100 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 26868.264 26868.264 2.023815 0.00023506 570.164 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.7724 0.787903 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 26868.26 26868.26 1.0000 2.13136036 2.023815 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.23503132 60.00 32.22 27.78 0.000 26868.26 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.77 0.00799998 21.00 0.00799998 45.2309 9046.61 0.00 26963.05 26963.05 2.13136036 12.80 11.60 0.00800000 33059.8 25.21 16.39 0.00800000 45710.5
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 518248.157 518248.157 19.018458 0.00453386 13242.685 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 14.8976 15.197456 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 518248.16 518248.16 1.0000 20.02909623 19.018458 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 4.53339845 60.00 32.22 27.78 0.000 518248.16 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 45.2310 350772.16 0.00 519845.86 519845.86 20.02909623 12.80 11.60 0.00800000 33059.8 38.25 20.66 0.00800000 59014.4
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 114310.892 114310.892 3.894575 0.00100004 3016.096 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 3.2860 3.352129 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 114310.89 114310.89 1.0000 4.10153267 3.894575 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.99993954 60.00 32.22 27.78 0.000 114310.89 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 45.2310 80015.37 0.00 114696.12 114696.12 4.10153267 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61024.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 19921.409 19921.409 0.679405 0.00017428 525.385 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.5727 0.584189 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19921.41 19921.41 1.0000 0.71550864 0.679405 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.17426339 60.00 32.22 27.78 0.000 19921.41 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00777109 21.00 0.00777109 43.9554 13941.81 0.00 19986.81 19986.81 0.71550864 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.5
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 13675.363 13675.363 0.466446 0.00011964 360.638 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.3931 0.401025 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13675.36 13675.36 1.0000 0.49123314 0.466446 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.11962584 60.00 32.22 27.78 0.000 13675.36 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00778325 21.00 0.00778325 44.0233 9569.96 0.00 13720.11 13720.11 0.49123314 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60989.8
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 21911.669 21911.669 0.747402 0.00019169 577.831 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.6299 0.642552 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 21911.67 21911.67 1.0000 0.78711932 0.747402 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.19167329 60.00 32.22 27.78 0.000 21911.67 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00779929 21.00 0.00779929 44.1127 15333.21 0.00 21983.29 21983.29 0.78711932 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60988.6
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 12346.706 12346.706 0.499814 0.00010801 303.945 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.3549 0.362063 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12346.71 12346.71 1.0000 0.52637445 0.499814 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.10800336 60.00 32.22 27.78 0.000 12346.71 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00769762 21.00 0.00769762 43.5457 7948.47 0.00 12385.54 12385.54 0.52637445 12.80 11.60 0.00800000 33059.8 35.88 19.93 0.00800000 56589.7
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 285251.838 285251.838 9.734888 0.00249551 7520.592 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 8.1999 8.364916 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 285251.84 285251.84 1.0000 10.25219856 9.734888 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.49525295 60.00 32.22 27.78 0.000 285251.84 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00765620 21.00 0.00765620 43.3159 199600.45 0.00 286171.48 286171.48 10.25219856 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 189222.604 189222.604 6.457930 0.00165540 4988.713 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 5.4394 5.548890 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 189222.60 189222.60 1.0000 6.80110334 6.457930 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.65523301 60.00 32.22 27.78 0.000 189222.60 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00765483 21.00 0.00765483 43.3084 132403.62 0.00 189831.98 189831.98 6.80110334 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 288704.018 288704.018 9.852850 0.00252571 7611.556 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 8.2991 8.466150 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 288704.02 288704.02 1.0000 10.37642940 9.852850 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 2.52545105 60.00 32.22 27.78 0.000 288704.02 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00766025 21.00 0.00766025 43.3385 202014.07 0.00 289634.41 289634.41 10.37642940 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.6
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 185387.202 185387.202 6.326911 0.00162185 4887.638 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 5.3292 5.436418 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 185387.20 185387.20 1.0000 6.66312209 6.326911 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 1.62168267 60.00 32.22 27.78 0.000 185387.20 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00764787 21.00 0.00764787 43.2695 129721.79 0.00 185984.53 185984.53 6.66312209 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.3
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 37609.657 37609.657 1.283924 0.00032903 991.426 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 1.0811 1.102891 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 37609.66 37503.48 1.0000 1.35215148 1.283924 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.32899212 60.00 32.22 27.78 0.000 37609.66 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767579 21.00 0.00767579 43.4262 26313.24 0.00 37729.87 37729.87 1.35215148 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.4
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 24814.385 24814.385 0.847139 0.00021709 654.123 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.7133 0.727674 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24814.38 24814.38 1.0000 0.89215621 0.847139 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.21706492 60.00 32.22 27.78 0.000 24814.38 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767247 21.00 0.00767247 43.4078 17361.05 0.00 24893.65 24893.65 0.89215621 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 38037.392 38037.392 1.298539 0.00033277 1002.697 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 1.0934 1.115434 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 38037.39 38037.39 1.0000 1.36754350 1.298539 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.33273375 60.00 32.22 27.78 0.000 38037.39 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767927 21.00 0.00767927 43.4457 26612.31 0.00 38158.94 38158.94 1.36754350 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60963.1
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 24752.519 24752.519 0.845030 0.00021655 652.491 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 0.7115 0.725859 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24752.52 24752.52 1.0000 0.88993466 0.845030 12.80 10.41 0.00800000 33059.8 40.00 19.63 0.00800000 60796.0 0.21652375 60.00 32.22 27.78 0.000 24752.52 -27.60 0.00034190 -27.60 0.00000000 0.0000 20.95 0.00767190 21.00 0.00767190 43.4047 17317.76 0.00 24831.58 24831.58 0.88993466 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.5
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 183273.830 -999.000 10.857854 0.00779689 -999.000 -999.0000 1.00000 1.00000 1018.0147 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.857854 11.43483919   4197.9300 999.8980 93.76333858 12.27 6.67 5.60 2204226.82 8.3147 8.314654 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 183273.83 181238.05 1.0000 11.43483919 10.857854 26.21 14.59 0.00708718 44406.1 10.68 8.51 0.00700000 28378.5 7.79609706 6.67 12.27 5.60 24664.628 158609.20 33.40 0.00630683 16.37 2.50608000 23.0808 24.00 0.00732708 24.00 0.00732708 34.5623 127941.30 0.00 206597.82 203529.67 11.43483919 26.21 15.95 0.00708718 44406.1 8.73 8.71 0.00698058 26338.7
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 100624.945 100624.945 3.257356 0.00088031 1540.986 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.857854 11.43483919   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 2.8926 2.950793 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 100624.94 100624.94 1.0000 3.43045176 3.257356 -16.39 -16.39 0.00206690 -11364.2 12.80 10.41 0.00800000 33059.8 0.88022111 60.00 32.22 27.78 0.000 100624.94 -27.60 0.00034190 -27.60 2.50608000 76.9360 21.00 0.00782108 19.41 0.00772474 48.1954 33568.16 0.00 81310.18 81310.18 3.43045176 2.80 -1.08 0.00206690 7993.5 26.30 11.15 0.00206690 31696.0
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1725379.887 -999.000 100.556968 0.07340165 -999.000 -999.0000 1.00000 1.00000 1017.9801 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 100.556968 105.90055367   4197.9300 999.8980 93.76333858 12.27 6.67 5.60 2204226.82 78.2760 78.275968 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1725379.89 1710503.99 1.0000 105.90055367 100.556968 26.52 14.69 0.00706855 44670.8 10.68 8.51 0.00700000 28378.4 73.39416123 6.67 12.27 5.60 228424.529 1496955.36 33.40 0.00630683 16.37 26.04512000 25.9009 24.00 0.00734708 24.00 0.00734708 34.6554 1167681.85 0.00 1941965.12 1918087.50 105.90055367 26.52 16.05 0.00706855 44670.8 8.72 8.71 0.00697897 26333.2
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1087733.293 1087733.293 30.167091 0.00951597 15999.524 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_MID WITH REHEAT FAN Fan:VariableVolume 100.556968 105.90055367   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 31.2681 31.897418 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:50:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1087733.29 1087733.29 1.0000 31.77016610 30.167091 -21.27 -21.27 0.00133142 -18097.8 12.80 10.41 0.00800000 33059.8 9.51499464 60.00 32.22 27.78 0.000 1087733.29 -27.60 0.00034190 -27.60 26.04512000 86.3362 18.71 0.00758381 17.81 0.00756926 52.2232 393184.49 0.00 837237.44 837237.44 31.77016610 2.80 -2.25 0.00133142 6150.3 28.96 11.51 0.00133142 32503.2
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 190044.122 -999.000 11.238205 0.00808492 -999.000 -999.0000 1.00000 1.00000 1017.9513 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.238205 11.83540141   4197.9300 999.8980 93.76333858 12.27 6.67 5.60 2204226.82 8.6218 8.621804 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 190044.12 188760.44 1.0000 11.83540141 11.238205 26.32 14.61 0.00705309 44435.6 10.68 8.51 0.00700000 28378.3 8.08409155 6.67 12.27 5.60 25528.629 164515.49 33.40 0.00630683 16.37 2.76931000 24.6419 24.00 0.00729826 24.00 0.00729826 34.4278 134431.73 0.00 214186.74 212020.38 11.83540141 26.32 15.96 0.00705309 44435.6 8.73 8.71 0.00698037 26338.5
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 113866.205 113866.205 3.371461 0.00099615 1704.281 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 11.238205 11.83540141   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 3.2732 3.339089 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 113866.20 113866.20 1.0000 3.55062042 3.371461 -19.11 -19.11 0.00162904 -15190.6 12.80 10.41 0.00800000 33059.8 0.99604961 60.00 32.22 27.78 0.000 113866.20 -27.60 0.00034190 -27.60 2.76931000 82.1398 19.91 0.00754865 16.98 0.00753938 54.8331 57030.40 0.00 89524.83 89524.83 3.55062042 2.80 -1.77 0.00162904 6896.2 27.82 11.33 0.00162904 32110.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 105528.979 -999.000 6.419937 0.00448945 -999.000 -999.0000 1.00000 1.00000 1018.3052 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.419937 6.76109201   4197.9300 999.8980 93.76333858 12.27 6.67 5.60 2204226.82 4.7876 4.787573 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 105528.98 102255.54 1.0000 6.76109201 6.419937 25.81 14.59 0.00724345 44399.7 11.09 8.68 0.00700000 28791.4 4.48898874 6.67 12.27 5.60 11794.205 93734.77 32.60 0.00630558 16.10 1.20015641 18.6942 24.00 0.00749396 24.00 0.00749396 35.3405 68342.71 0.00 119059.31 116192.07 6.76109201 25.81 15.95 0.00724345 44399.7 8.94 8.91 0.00707500 26790.2
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 306811.684 306811.684 6.419937 0.00268412 6559.519 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 CAV_BAS FAN Fan:ConstantVolume 6.419937 6.76109201   4197.9300 999.8980 29.82998341 54.44 82.22 27.78 3478727.78 8.8197 8.997151 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 306811.68 306811.68 1.0000 6.76109201 6.419937 -5.16 -9.55 0.00034190 -4332.8 40.00 19.63 0.00800000 60796.0 2.68384865 60.00 32.22 27.78 0.000 306811.68 -27.60 0.00034190 -27.60 1.20015641 18.6942 0.00 0.00034190 22.83 0.00034190 1.7505 0.00 0.00 244517.09 244517.09 6.76109201 12.80 2.46 0.00034190 13725.2 48.77 18.00 0.00034190 49890.5
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 464992.528 261685.824 24.462192 0.01138764 -999.000 -999.0000 -999.00000 -999.00000 1017.9120 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 404049.62 402578.36 0.8689 -999.0 -999.0 28.68 15.39 0.00703191 46779.4 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 404049.62 33.40 0.00630683 16.37 0.33839277 -999.0000 27.00 0.00704209 27.00 0.00704209 27.8119 371832.90 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10430.864 5931.890 0.564620 0.00025545 -999.000 -999.0000 -999.00000 -999.00000 1017.9680 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 9015.76 8950.35 0.8643 -999.0 -999.0 28.07 15.21 0.00706206 46234.6 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 9015.76 26.57 0.00629632 14.04 0.01563234 -999.0000 27.00 0.00708387 27.00 0.00708387 27.9731 8593.43 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 99842.119 56766.720 5.402620 0.00244513 -999.000 -999.0000 -999.00000 -999.00000 1017.9730 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 86302.12 85649.12 0.8644 -999.0 -999.0 28.07 15.21 0.00706474 46240.8 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 86302.12 26.57 0.00629632 14.04 0.15632344 -999.0000 27.00 0.00708765 27.00 0.00708765 27.9880 82226.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10163.312 5778.980 0.550025 0.00024890 -999.000 -999.0000 -999.00000 -999.00000 1017.9710 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 8784.82 8719.42 0.8644 -999.0 -999.0 28.07 15.21 0.00706369 46238.4 12.80 9.41 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8784.82 26.57 0.00629632 14.04 0.01563234 -999.0000 27.00 0.00708614 27.00 0.00708614 27.9820 8371.26 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 464992.528 464992.528 24.462192 0.01138764 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 464992.53 464992.53 1.0000 25.76210965 24.462192 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 464992.53 -27.60 0.00034190 -27.60 0.33839277 1.3833 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10430.864 10430.864 0.564620 0.00025545 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10430.86 10430.86 1.0000 0.59462423 0.564620 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10430.86 -27.60 0.00034190 -27.60 0.01563234 2.7686 0.00 0.00098406 25.07 0.00098406 4.3988 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 99842.119 99842.119 5.402620 0.00244513 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 99842.12 99842.12 1.0000 5.68971498 5.402620 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 99842.12 -27.60 0.00034190 -27.60 0.15632344 2.8935 0.00 0.00098408 23.50 0.00098408 4.8335 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10163.312 10163.312 0.550025 0.00024890 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0531 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10163.31 10163.31 1.0000 0.57925290 0.550025 -27.60 -27.60 0.00034190 -26896.1 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10163.31 -27.60 0.00034190 -27.60 0.01563234 2.8421 0.00 0.00098348 21.94 0.00098348 5.3100 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 24207.992 24207.992 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 24.462192 25.76210965   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 24207.99 24207.99 1.0000 25.76210965 24.462192 -0.38 -0.38 0.00690790 16887.7 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24207.99 -27.60 0.00034190 -27.60 0.33839277 1.3833 0.00 0.00700000 27.00 0.00700000 27.6430 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.564620 0.59462423   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.59462423 0.564620 -0.76 -5.61 0.00096628 1647.4 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.7686 0.00 0.00098406 25.07 0.00098406 4.3988 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 11183.090 11183.090 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.402620 5.68971498   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 11183.09 11183.09 1.0000 5.68971498 5.402620 -0.80 -5.63 0.00096550 1610.7 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 11183.09 -27.60 0.00034190 -27.60 0.15632344 2.8935 0.00 0.00098408 23.50 0.00098408 4.8335 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1118.309 1118.309 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0531 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.550025 0.57925290   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1118.31 1118.31 1.0000 0.57925290 0.550025 -0.78 -5.62 0.00096524 1624.4 40.00 19.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1118.31 -27.60 0.00034190 -27.60 0.01563234 2.8421 0.00 0.00098348 21.94 0.00098348 5.3100 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.51 10.86 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 26.05 100.56 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.77 11.24 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 6.42 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1515.00 1616.17 36.17
CORE_BOTTOM 1360.83 1713.83 21.50
CORE_MID 974.83 3454.67 229.50
CORE_TOP 1841.00 4078.17 1117.83
PERIMETER_BOT_ZN_3 1636.00 3858.00 675.50
PERIMETER_BOT_ZN_2 2030.17 3873.50 821.17
PERIMETER_BOT_ZN_1 2207.00 3255.50 689.83
PERIMETER_BOT_ZN_4 2391.00 2954.67 445.50
PERIMETER_MID_ZN_3 2679.00 4430.17 2016.17
PERIMETER_MID_ZN_2 2466.67 3716.50 1632.50
PERIMETER_MID_ZN_1 2566.50 3704.33 1253.83
PERIMETER_MID_ZN_4 2698.50 4353.00 1678.67
PERIMETER_TOP_ZN_3 3324.00 4730.67 2732.83
PERIMETER_TOP_ZN_2 3459.83 4372.33 2410.17
PERIMETER_TOP_ZN_1 3040.33 4069.67 1891.17
PERIMETER_TOP_ZN_4 3223.83 4575.83 2286.17
DATACENTER_BOT_ZN_6 5810.50 386.00 385.17
DATACENTER_MID_ZN_6 5268.33 198.67 65.50
DATACENTER_TOP_ZN_6 4525.00 564.17 144.33
DATACENTER_BASEMENT_ZN_6 5943.00 5665.83 5665.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5942.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 61.33 0.00 2.83
CORE_BOTTOM 0.00 4.83 0.00 0.00
CORE_MID 0.33 0.00 0.00 0.00
CORE_TOP 14.83 0.00 3.17 0.00
PERIMETER_BOT_ZN_3 6.00 1.00 1.00 0.67
PERIMETER_BOT_ZN_2 5.50 14.67 0.17 14.67
PERIMETER_BOT_ZN_1 6.33 22.17 0.50 21.33
PERIMETER_BOT_ZN_4 2.50 54.00 0.00 20.67
PERIMETER_MID_ZN_3 113.00 0.00 37.67 0.00
PERIMETER_MID_ZN_2 64.33 15.33 8.50 15.33
PERIMETER_MID_ZN_1 46.83 20.17 6.00 18.83
PERIMETER_MID_ZN_4 50.83 19.17 7.67 9.17
PERIMETER_TOP_ZN_3 299.17 1.00 103.50 0.33
PERIMETER_TOP_ZN_2 189.83 17.83 37.17 17.00
PERIMETER_TOP_ZN_1 153.33 15.00 25.33 12.83
PERIMETER_TOP_ZN_4 145.83 19.33 29.00 8.67
DATACENTER_BOT_ZN_6 0.00 21.17 0.00 16.00
DATACENTER_MID_ZN_6 0.00 8.33 0.00 4.50
DATACENTER_TOP_ZN_6 0.00 8.50 0.00 4.50
DATACENTER_BASEMENT_ZN_6 0.00 524.83 0.00 405.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 345.17 695.00 113.17 485.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 1.338 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 1.055 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.836 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.788 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 1.048 0.059 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 1.841 0.061 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 1.766 0.059 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 2.350 0.061 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.924 0.137 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 1.815 0.151 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 1.763 0.138 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 1.976 0.142 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 1.117 0.170 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 2.005 0.176 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 1.842 0.171 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 2.144 0.176 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.01 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.48 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1027.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 55660275.14 0.00 55660275.14 0.00 55660275.14 37848132.68 3909.91 910.34 3939.75 408.00
CORE_BOTTOM 45048678.66 0.00 45048678.66 0.00 45048678.66 33990283.35 3675.89 12.21 5071.90 506.91
CORE_MID 0.35E+09 0.00 0.35E+09 0.00 0.35E+09 0.34E+09 4101.77 7.99 4650.23 371.99
CORE_TOP 32397261.10 0.00 32397261.10 0.00 32397261.10 33990283.35 4151.72 6.58 4601.70 424.82
PERIMETER_BOT_ZN_3 5705500.64 0.00 5705500.64 591585.02 6297085.66 4267819.30 3778.22 53.47 4928.32 506.91
PERIMETER_BOT_ZN_2 6515481.77 0.00 6515481.77 394389.74 6909871.51 2750345.05 3430.81 0.13 5329.06 506.91
PERIMETER_BOT_ZN_1 9567512.77 0.00 9567512.77 591585.02 10159097.78 4267912.63 3450.33 2.49 5307.18 506.91
PERIMETER_BOT_ZN_4 8307101.79 0.00 8307101.79 394389.74 8701491.53 2750345.05 3416.30 0.57 5343.13 506.91
PERIMETER_MID_ZN_3 48296557.95 0.00 48296557.95 1387434.57 49683992.52 42678193.03 4027.70 5.92 4726.38 371.99
PERIMETER_MID_ZN_2 65599531.54 0.00 65599531.54 924955.75 66524487.29 27503450.52 3818.84 5.28 4935.88 1280.99
PERIMETER_MID_ZN_1 91592872.06 0.00 91592872.06 1387434.57 92980306.63 42679126.28 3873.59 3.63 4882.77 371.99
PERIMETER_MID_ZN_4 66844887.29 0.00 66844887.29 924955.75 67769843.04 27503450.52 3808.49 2.79 4948.72 371.99
PERIMETER_TOP_ZN_3 5816259.39 0.00 5816259.39 1722650.34 7538909.73 4267819.30 4075.29 3.50 4681.22 424.82
PERIMETER_TOP_ZN_2 6709183.03 0.00 6709183.03 1148432.78 7857615.81 2750345.05 3950.18 3.40 4806.42 424.82
PERIMETER_TOP_ZN_1 9529683.97 0.00 9529683.97 1722650.34 11252334.32 4267912.63 3999.19 5.28 4755.54 424.82
PERIMETER_TOP_ZN_4 7200565.58 0.00 7200565.58 1148432.78 8348998.36 2750345.05 3921.91 4.71 4833.38 424.82
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.64E+10 0.00 0.64E+10 53961922.12 0.65E+10 0.50E+10 4626.75 4406.01 5555.59 1963.23


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4723 0.0000 2.4723 0.0000 2.4723 1.2002 1336.01 905.68 3701.31
CORE_BOTTOM 1.9697 0.0000 1.9697 0.0000 1.9697 1.0778 1233.64 8.23 4701.12
CORE_MID 15.6172 0.0000 15.6172 0.0000 15.6172 10.7782 1408.96 7.40 4526.64
CORE_TOP 1.4740 0.0000 1.4740 0.0000 1.4740 1.0778 1423.56 6.33 4513.11
PERIMETER_BOT_ZN_3 0.2462 0.0000 0.2462 0.0139 0.2601 0.1353 1377.27 47.90 4517.83
PERIMETER_BOT_ZN_2 0.2792 0.0000 0.2792 0.0092 0.2884 0.0872 1090.82 0.02 4852.16
PERIMETER_BOT_ZN_1 0.4151 0.0000 0.4151 0.0139 0.4289 0.1353 1104.41 1.33 4837.26
PERIMETER_BOT_ZN_4 0.3559 0.0000 0.3559 0.0092 0.3651 0.0872 1082.80 0.39 4859.81
PERIMETER_MID_ZN_3 2.1756 0.0000 2.1756 0.0325 2.2081 1.3533 1348.99 4.44 4589.57
PERIMETER_MID_ZN_2 2.7575 0.0000 2.7575 0.0230 2.7805 0.8721 1207.37 2.69 3823.94
PERIMETER_MID_ZN_1 4.1469 0.0000 4.1469 0.0325 4.1794 1.3533 1234.90 1.90 4706.19
PERIMETER_MID_ZN_4 3.0030 0.0000 3.0030 0.0217 3.0247 0.8721 1202.49 1.14 4739.37
PERIMETER_TOP_ZN_3 0.2636 0.0000 0.2636 0.0404 0.3040 0.1353 1362.65 2.55 4577.80
PERIMETER_TOP_ZN_2 0.3047 0.0000 0.3047 0.0269 0.3316 0.0872 1289.02 1.79 4652.19
PERIMETER_TOP_ZN_1 0.4338 0.0000 0.4338 0.0404 0.4742 0.1353 1314.57 3.26 4625.16
PERIMETER_TOP_ZN_4 0.3261 0.0000 0.3261 0.0269 0.3530 0.0872 1273.30 2.33 4667.37
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 286.9537 0.0000 286.9537 1.2778 288.2315 158.4706 1809.75 4375.73 4906.76


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 83342868.47 0.00 83342868.47 48026705.38 3508.26 8.03 5243.71 506.91
VAV_MID WITH REHEAT 0.69E+09 0.00 0.69E+09 0.48E+09 3990.94 8.27 4760.78 371.99
VAV_TOP WITH REHEAT 68379516.38 0.00 68379516.38 48026705.38 4091.02 1.95 4667.02 424.74
CAV_BAS 61733011.92 0.00 61733011.92 37848132.68 3875.59 5.71 4878.70 408.00
AIRLOOP DATACENTER BASEMENT 5865235.79 0.00 5865235.79 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2709495.95 0.00 2709495.95 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 270949.60 0.00 270949.60 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.6223 0.0000 3.6223 1.5229 1141.55 3.60 4797.85
VAV_MID WITH REHEAT 30.9418 0.0000 30.9418 15.2292 1314.57 6.80 4621.64
VAV_TOP WITH REHEAT 3.1079 0.0000 3.1079 1.5229 1373.28 1.58 4568.14
CAV_BAS 2.7421 0.0000 2.7421 1.2002 1327.19 1.32 4614.49
AIRLOOP DATACENTER BASEMENT 0.2741 0.0000 0.2741 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1266 0.0000 0.1266 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0127 0.0000 0.0127 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 1932.74 3449.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 2541.78 2645.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 2777.28 2460.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 898.58 4170.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.7809 5.4911 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 28.8953 48.5985 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 3.0718 4.8845 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.3320 4.0138 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.3754 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1734 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0173 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1335
Defaulted Fields 1179
Fields with Defaults 3690
Autosized Fields 333
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
Electricity:Building 19155.85 253334.51 01-JAN-00:10 1138237.68 03-APR-07:10
Electricity:Zone:BASEMENT 660.02 14600.60 01-JAN-00:10 34031.28 02-JAN-08:10
Electricity:SpaceType:GENERAL 19155.85 253334.51 01-JAN-00:10 1138237.68 03-APR-07:10
InteriorLights:Electricity 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 235.63 1143.06 01-JAN-00:10 20573.73 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
LightsWired:InteriorLights:Electricity 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 235.63 1143.06 01-JAN-00:10 20573.73 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 532.90 7069.41 01-JAN-00:10 36605.25 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
Electricity:Zone:CORE_MID 5328.94 70693.84 01-JAN-00:10 366051.79 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2116.10 10265.44 01-JAN-00:10 184766.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2116.10 10265.44 01-JAN-00:10 184766.59 02-JAN-08:10
Electricity:Zone:CORE_TOP 532.89 7069.38 01-JAN-00:10 36605.18 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 66.91 887.67 01-JAN-00:10 4596.25 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 43.12 572.05 01-JAN-00:10 2962.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 66.91 887.68 01-JAN-00:10 4596.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 43.12 572.04 01-JAN-00:10 2961.99 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 669.12 8876.66 01-JAN-00:10 45962.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 265.70 1288.93 01-JAN-00:10 23199.29 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 265.70 1288.93 01-JAN-00:10 23199.29 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 431.21 5720.45 01-JAN-00:10 29619.96 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 669.13 8876.80 01-JAN-00:10 45963.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 265.70 1288.96 01-JAN-00:10 23199.80 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 265.70 1288.96 01-JAN-00:10 23199.80 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 431.20 5720.42 01-JAN-00:10 29619.87 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 66.91 887.67 01-JAN-00:10 4596.25 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 43.12 572.05 01-JAN-00:10 2962.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 66.91 887.68 01-JAN-00:10 4596.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 43.12 572.04 01-JAN-00:10 2961.99 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7561.29 95230.42 01-JAN-00:10 385433.43 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 66.44 322.29 01-JAN-00:10 5800.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 66.44 322.29 01-JAN-00:10 5800.91 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.25 1969.80 01-JAN-00:10 8176.00 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1582.51 19698.04 01-JAN-00:10 81759.99 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 43.70 211.99 01-JAN-00:10 3815.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 43.70 211.99 01-JAN-00:10 3815.77 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.25 1969.80 01-JAN-00:10 8176.00 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1809.35 5154.49 10-JAN-22:10 475803.86 07-SEP-14:50
HeatRejection:Electricity 837.86 1247.82 10-JAN-22:00 83442.05 19-MAY-14:00
General:HeatRejection:Electricity 837.86 1247.82 10-JAN-22:00 83442.05 19-MAY-14:00
Electricity:HVAC 6378.53 96595.57 09-JAN-24:00 538131.52 11-AUG-15:40
ExteriorEquipment:Electricity 1997.59 30702.09 01-JAN-00:10 120520.01 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 87.51 1613.62 01-JAN-00:10 5474.05 03-APR-07:20
ElectricityPurchased:Facility 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
ElectricityPurchased:Plant 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
Cogeneration:ElectricityPurchased 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
General:Cogeneration:ElectricityPurchased 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
ElectricityNet:Plant 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
Cogeneration:ElectricityNet 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
General:Cogeneration:ElectricityNet 30157.09 391967.65 29-JAN-10:40 2144185.78 07-AUG-15:30
Fans:Electricity 2738.66 47644.24 29-JAN-06:00 325068.55 11-AUG-15:40
General:Fans:Electricity 2738.66 47644.24 29-JAN-06:00 325068.55 11-AUG-15:40
ExteriorLights:Electricity 903.27 0.00 01-JAN-08:20 57580.60 01-JAN-00:10
General:ExteriorLights:Electricity 903.27 0.00 01-JAN-08:20 57580.60 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 61.31 1944.00 01-JAN-00:10 1944.00 01-JAN-00:10
Cooling:Electricity 3247.48 30241.90 09-JAN-07:10 476400.57 07-AUG-15:30
General:Cooling:Electricity 3247.48 30241.90 09-JAN-07:10 476400.57 07-AUG-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 841.38 0.00 13-JUL-15:20 52018.99 28-DEC-19:00
General:Humidifier:Electricity 841.38 0.00 13-JUL-15:20 52018.99 28-DEC-19:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 434.99 3656.68 07-JAN-04:50 66157.66 17-JUL-16:00
General:Pumps:Electricity 434.99 3656.68 07-JAN-04:50 66157.66 17-JUL-16:00
WIRED_LTG_ELECTRICITY 110.78 0.00 01-JAN-00:10 9672.96 02-JAN-08:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 6520.00 8146.58 05-JAN-22:20 3042043.47 09-JAN-07:10
NaturalGas:Plant 6520.00 8146.58 05-JAN-22:20 3042043.47 09-JAN-07:10
Heating:NaturalGas 5671.61 0.00 01-JAN-00:10 3008975.83 09-JAN-07:10
Boiler:Heating:NaturalGas 5671.61 0.00 01-JAN-00:10 3008975.83 09-JAN-07:10
WaterSystems:NaturalGas 848.39 8146.58 05-JAN-22:20 87977.56 17-FEB-12:40
Water Heater:WaterSystems:NaturalGas 848.39 8146.58 05-JAN-22:20 87977.56 17-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 17075.52 147205.54 09-JAN-07:10 2567895.29 07-SEP-15:00
PlantLoopCoolingDemand:HVAC 17075.52 147205.54 09-JAN-07:10 2567895.29 07-SEP-15:00
CoolingCoils:PlantLoopCoolingDemand 17075.52 147205.54 09-JAN-07:10 2567895.29 07-SEP-15:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 5679.35 0.00 03-SEP-24:00 0.00 17-JUL-16:00
Water:HVAC 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Humidifier:Water 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
General:Humidifier:Water 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
MainsWater:Facility 5679.35 0.00 03-SEP-24:00 0.00 17-JUL-16:00
MainsWater:HVAC 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Humidifier:MainsWater 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
General:Humidifier:MainsWater 312.99 0.00 13-JUL-15:20 0.00 28-DEC-19:00
Water:Plant 5366.36 0.00 01-JAN-00:10 0.00 17-JUL-16:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 5366.36 0.00 01-JAN-00:10 0.00 17-JUL-16:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 3086.19 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:Water 3086.19 0.00 01-JAN-00:10 0.00 17-JUL-16:00
HeatRejection:MainsWater 3086.19 0.00 01-JAN-00:10 0.00 17-JUL-16:00
General:HeatRejection:MainsWater 3086.19 0.00 01-JAN-00:10 0.00 17-JUL-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 53456.44 228552.70 30-JAN-06:00 10818293.02 07-SEP-15:00
EnergyTransfer:Building 18806.21 87916.57 12-JAN-22:40 1749929.65 07-AUG-15:20
EnergyTransfer:Zone:BASEMENT 670.00 0.00 01-JAN-00:40 69663.21 05-SEP-05:10
Heating:EnergyTransfer 873.08 0.00 13-JAN-22:10 1268216.45 09-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 3.43 0.00 01-JAN-00:40 22665.98 05-AUG-16:10
General:Heating:EnergyTransfer 873.08 0.00 13-JAN-22:10 1268216.45 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 3.43 0.00 01-JAN-00:40 22665.98 05-AUG-16:10
Cooling:EnergyTransfer 17933.13 83789.67 30-JAN-06:00 1749929.65 07-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 666.57 0.00 01-JAN-00:10 69663.21 05-SEP-05:10
General:Cooling:EnergyTransfer 17933.13 83789.67 30-JAN-06:00 1749929.65 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 666.57 0.00 01-JAN-00:10 69663.21 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 604.03 0.00 01-JAN-00:10 57078.27 07-AUG-10:30
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 604.03 0.00 01-JAN-00:10 57078.27 07-AUG-10:30
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 604.03 0.00 01-JAN-00:10 57078.27 07-AUG-10:30
EnergyTransfer:Zone:CORE_MID 4234.42 0.00 01-JAN-00:10 454343.39 05-SEP-14:00
Heating:EnergyTransfer:Zone:CORE_MID 6.40 0.00 01-JAN-00:10 339588.03 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 6.40 0.00 01-JAN-00:10 339588.03 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 4228.02 0.00 01-JAN-00:10 454343.39 05-SEP-14:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 4228.02 0.00 01-JAN-00:10 454343.39 05-SEP-14:00
EnergyTransfer:Zone:CORE_TOP 368.60 0.00 01-JAN-00:10 70276.53 06-MAR-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 19.45 0.00 01-JAN-00:10 70276.53 06-MAR-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 19.45 0.00 01-JAN-00:10 70276.53 06-MAR-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 349.15 0.00 01-JAN-00:10 54273.90 17-JUL-15:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 349.15 0.00 01-JAN-00:10 54273.90 17-JUL-15:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 69.84 0.00 01-JAN-00:10 11488.22 30-JAN-06:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.76 0.00 01-JAN-00:10 11488.22 30-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.76 0.00 01-JAN-00:10 11488.22 30-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 67.09 0.00 01-JAN-00:10 10811.55 09-AUG-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 67.09 0.00 01-JAN-00:10 10811.55 09-AUG-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.94 0.00 01-JAN-00:10 14524.45 07-AUG-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.07 0.00 01-JAN-00:10 8753.71 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.07 0.00 01-JAN-00:10 8753.71 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.87 0.00 01-JAN-00:10 14524.45 07-AUG-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.87 0.00 01-JAN-00:10 14524.45 07-AUG-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.66 0.00 01-JAN-00:10 20590.07 18-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 2.94 0.00 01-JAN-00:10 14822.56 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 2.94 0.00 01-JAN-00:10 14822.56 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 113.72 0.00 01-JAN-00:10 20590.07 18-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 113.72 0.00 01-JAN-00:10 20590.07 18-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 102.00 0.00 01-JAN-00:10 18585.53 07-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.61 0.00 01-JAN-00:10 6720.24 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.61 0.00 01-JAN-00:10 6720.24 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 101.40 0.00 01-JAN-00:10 18585.53 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 101.40 0.00 01-JAN-00:10 18585.53 07-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 611.98 0.00 01-JAN-00:10 130657.24 30-JAN-04:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 180.72 0.00 01-JAN-00:10 130657.24 30-JAN-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 180.72 0.00 01-JAN-00:10 130657.24 30-JAN-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 431.25 0.00 01-JAN-00:10 99929.89 18-JUL-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 431.25 0.00 01-JAN-00:10 99929.89 18-JUL-15:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 663.48 0.00 01-JAN-00:10 149693.84 07-AUG-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 108.12 0.00 01-JAN-00:10 146595.91 09-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 108.12 0.00 01-JAN-00:10 146595.91 09-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 555.36 0.00 01-JAN-00:10 149693.84 07-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 555.36 0.00 01-JAN-00:10 149693.84 07-AUG-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1060.91 0.00 01-JAN-00:10 213378.17 18-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 108.17 0.00 01-JAN-00:10 191445.18 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 108.17 0.00 01-JAN-00:10 191445.18 09-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 952.74 0.00 01-JAN-00:10 213378.17 18-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 952.74 0.00 01-JAN-00:10 213378.17 18-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 664.09 0.00 01-JAN-00:10 157375.24 17-JUL-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 87.37 0.00 01-JAN-00:10 141299.20 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 87.37 0.00 01-JAN-00:10 141299.20 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 576.72 0.00 01-JAN-00:10 157375.24 17-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 576.72 0.00 01-JAN-00:10 157375.24 17-JUL-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 85.61 0.00 01-JAN-00:10 17253.94 09-JAN-02:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.80 0.00 01-JAN-00:10 17253.94 09-JAN-02:50
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.80 0.00 01-JAN-00:10 17253.94 09-JAN-02:50
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.81 0.00 01-JAN-00:10 11295.81 17-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 39.81 0.00 01-JAN-00:10 11295.81 17-JUL-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 76.52 0.00 01-JAN-00:10 16612.27 09-JAN-04:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 26.59 0.00 01-JAN-00:10 16612.27 09-JAN-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 26.59 0.00 01-JAN-00:10 16612.27 09-JAN-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 49.93 0.00 01-JAN-00:10 15278.06 07-AUG-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 49.93 0.00 01-JAN-00:10 15278.06 07-AUG-09:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 115.73 0.00 01-JAN-00:10 22407.99 01-SEP-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 30.59 0.00 01-JAN-00:10 22325.81 09-JAN-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 30.59 0.00 01-JAN-00:10 22325.81 09-JAN-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 85.14 0.00 01-JAN-00:10 22407.99 01-SEP-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 85.14 0.00 01-JAN-00:10 22407.99 01-SEP-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 74.51 0.00 01-JAN-00:10 17747.56 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 22.27 0.00 01-JAN-00:10 17747.56 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 22.27 0.00 01-JAN-00:10 17747.56 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 52.24 0.00 01-JAN-00:10 16641.00 17-JUL-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 52.24 0.00 01-JAN-00:10 16641.00 17-JUL-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 59.55 0.00 01-JAN-00:10 10468.22 07-AUG-15:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.68 0.00 01-JAN-00:10 6569.19 30-JAN-13:40
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.68 0.00 01-JAN-00:10 6569.19 30-JAN-13:40
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 54.87 0.00 01-JAN-00:10 10468.22 07-AUG-15:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 54.87 0.00 01-JAN-00:10 10468.22 07-AUG-15:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 490.53 0.00 01-JAN-00:10 117843.85 09-JAN-06:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 144.51 0.00 01-JAN-00:10 117843.85 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 144.51 0.00 01-JAN-00:10 117843.85 09-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 346.02 0.00 01-JAN-00:10 81962.74 07-AUG-15:40
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 346.02 0.00 01-JAN-00:10 81962.74 07-AUG-15:40
EnergyTransfer:Zone:TOPFLOOR_PLENUM 118.24 0.00 01-JAN-00:10 33506.08 09-JAN-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.83 0.00 01-JAN-00:10 33506.08 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.83 0.00 01-JAN-00:10 33506.08 09-JAN-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 48.41 0.00 01-JAN-00:10 23043.35 17-JUL-15:10
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 48.41 0.00 01-JAN-00:10 23043.35 17-JUL-15:10
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.26 6.56 28-JAN-04:50 8241.22 22-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.06 0.00 01-JAN-00:10 632.93 09-JAN-04:00
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.06 0.00 01-JAN-00:10 632.93 09-JAN-04:00
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.20 0.00 08-JAN-00:10 8241.22 22-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 135.20 0.00 08-JAN-00:10 8241.22 22-APR-18:10
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1154.81 6.81 15-JAN-14:30 78368.54 03-AUG-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.58 0.00 02-JAN-08:50 6634.73 29-JAN-17:50
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 5.58 0.00 02-JAN-08:50 6634.73 29-JAN-17:50
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1149.23 0.00 01-JAN-00:10 78368.54 03-AUG-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1149.23 0.00 01-JAN-00:10 78368.54 03-AUG-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 104.25 0.46 18-JAN-12:00 7952.55 03-AUG-18:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.11 0.00 02-JAN-13:20 752.69 30-APR-23:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.11 0.00 02-JAN-13:20 752.69 30-APR-23:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.15 0.00 01-JAN-00:10 7952.55 03-AUG-18:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 103.15 0.00 01-JAN-00:10 7952.55 03-AUG-18:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7153.22 83196.13 09-JAN-05:00 369514.73 22-AUG-07:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7153.22 83196.13 09-JAN-05:00 369514.73 22-AUG-07:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7153.22 83196.13 09-JAN-05:00 369514.73 22-AUG-07:20
PlantLoopHeatingDemand:Facility 4737.39 0.00 01-JAN-00:10 2420277.47 09-JAN-07:10
PlantLoopHeatingDemand:Plant 463.31 0.00 01-JAN-00:10 57405.82 17-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57405.82 17-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 463.31 0.00 01-JAN-00:10 57405.82 17-FEB-12:20
EnergyTransfer:HVAC 18638.62 137864.48 30-JAN-04:40 2518665.25 09-JAN-07:10
HeatingCoils:EnergyTransfer 4274.08 0.00 01-JAN-00:10 2401701.61 09-JAN-07:10
PlantLoopHeatingDemand:HVAC 4274.08 0.00 01-JAN-00:10 2401701.61 09-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 4274.08 0.00 01-JAN-00:10 2401701.61 09-JAN-07:10
CoolingCoils:EnergyTransfer 14364.54 116963.65 09-JAN-07:10 2510732.03 07-SEP-15:00
EnergyTransfer:Plant 16011.61 0.00 01-JAN-00:10 7112119.31 07-SEP-15:00
LoopToLoop:EnergyTransfer 3783.72 -0.37 01-FEB-05:50 2296821.11 07-SEP-15:00
WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57405.82 17-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 463.31 0.00 01-JAN-00:10 57405.82 17-FEB-12:20
Boilers:EnergyTransfer 4236.52 0.00 01-JAN-00:10 2424189.94 09-JAN-07:10
Chillers:EnergyTransfer 3495.78 0.00 01-JAN-00:10 2235762.46 07-SEP-14:50
HeatRejection:EnergyTransfer 4032.28 0.00 01-JAN-00:10 2563123.44 07-SEP-14:50
General:HeatRejection:EnergyTransfer 4032.28 0.00 01-JAN-00:10 2563123.44 07-SEP-14:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 3.435 -666.566 0.000 0.000 93.181 235.627 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -90.074
CORE_BOTTOM 0.000 0.000 0.000 -604.032 0.000 0.000 83.572 211.610 321.286 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -12.436
CORE_MID 0.000 0.000 6.402 -4227.997 0.000 0.000 849.693 2116.097 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1957.041
CORE_TOP 0.000 0.000 19.454 -349.146 0.000 0.000 88.098 211.610 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -291.300
PERIMETER_BOT_ZN_3 0.000 0.000 2.756 -67.088 0.000 0.000 10.995 26.570 40.342 22.599 0.000 0.090 36.508 0.000 -62.406 0.000 -10.366 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 2.072 -69.868 0.000 0.000 7.209 17.123 25.998 52.573 0.000 0.063 9.667 0.000 -38.055 0.000 -6.782 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 2.941 -113.717 0.000 0.000 10.979 26.570 40.343 113.819 0.000 0.086 0.000 0.000 -56.615 0.000 -10.393 -14.013
PERIMETER_BOT_ZN_4 0.000 0.000 0.606 -101.397 0.000 0.000 7.068 17.123 25.998 49.196 0.000 0.057 52.071 0.000 -43.339 0.000 -7.384 0.000
PERIMETER_MID_ZN_3 0.000 0.000 180.725 -431.251 0.000 0.000 115.062 265.697 403.423 236.131 0.000 2.129 17.685 0.000 -573.048 0.000 -216.552 -0.017
PERIMETER_MID_ZN_2 0.000 0.000 108.117 -555.360 0.000 0.000 54.701 171.225 259.981 528.852 0.000 1.416 0.005 0.000 -359.120 0.000 -146.194 -63.619
PERIMETER_MID_ZN_1 0.000 0.000 108.173 -952.733 0.000 0.000 112.104 265.703 403.429 1136.705 0.000 1.957 0.043 0.000 -547.947 0.000 -230.377 -297.014
PERIMETER_MID_ZN_4 0.000 0.000 87.372 -576.714 0.000 0.000 75.135 171.225 259.979 504.688 0.000 1.399 12.353 0.000 -385.847 0.000 -149.591 -0.002
PERIMETER_TOP_ZN_3 0.000 0.000 45.802 -39.808 0.000 0.000 11.781 26.570 40.342 24.366 0.000 0.267 0.001 0.000 -54.097 0.000 -25.231 -29.992
PERIMETER_TOP_ZN_2 0.000 0.000 26.587 -49.934 0.000 0.000 7.502 17.123 25.998 53.312 0.000 0.167 0.000 0.000 -34.193 0.000 -17.183 -29.377
PERIMETER_TOP_ZN_1 0.000 0.000 30.590 -85.143 0.000 0.000 11.437 26.570 40.343 114.483 0.000 0.235 0.001 0.000 -51.871 0.000 -26.817 -59.827
PERIMETER_TOP_ZN_4 0.000 0.000 22.271 -52.235 0.000 0.000 7.615 17.123 25.998 50.771 0.000 0.171 0.000 0.000 -36.835 0.000 -17.623 -17.256
DATACENTER_BOT_ZN_6 0.000 0.000 0.062 -135.198 0.000 0.000 0.950 4.370 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -24.065
DATACENTER_MID_ZN_6 0.000 0.000 5.584 -1149.227 0.000 0.000 9.520 43.701 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -448.384
DATACENTER_TOP_ZN_6 0.000 0.000 1.109 -103.146 0.000 0.000 0.957 4.370 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -57.171
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7153.222 0.000 0.000 20.232 66.437 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -428.304
GROUNDFLOOR_PLENUM 4.676 -54.869 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.160 72.060 0.000 0.000 0.000 -22.026 0.000
MIDFLOOR_PLENUM 144.515 -346.017 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.949 570.903 0.000 0.000 0.000 -372.350 -0.007
TOPFLOOR_PLENUM 69.834 -48.406 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.259 17.314 0.000 0.000 0.000 -39.002 -0.000
Total Facility 219.025 -449.292 654.056 -17483.780 0.000 0.000 1577.792 3942.443 15213.411 2887.496 0.000 11.405 788.610 0.000 -2243.372 0.000 -1297.872 -3819.897


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 11-SEP-03:02 0.00 0.00 0.00 -112853.23 0.00 0.00 0.00 1143.06 13457.54 0.00 0.00 0.00 98252.63 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 11-SEP-03:02 0.00 0.00 0.00 -94871.04 0.00 0.00 0.00 1026.54 8057.15 0.00 0.00 0.00 85787.35 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-03:02 0.00 0.00 0.00 -853212.66 0.00 0.00 0.00 10265.44 80571.20 0.00 0.00 0.00 762376.02 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 21-JUN-03:02 0.00 0.00 0.00 -82450.24 0.00 0.00 0.00 1026.54 8057.12 0.00 0.00 0.00 73366.57 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 06-AUG-16:01 0.00 0.00 0.00 -16290.15 0.00 0.00 41.81 128.89 758.77 4037.20 0.00 257.92 11065.56 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 06-AUG-08:41 0.00 0.00 0.00 -23102.70 0.00 0.00 19.77 83.06 488.98 18360.91 0.00 0.00 4188.80 0.00 -0.00 0.00 -38.84 0.00
PERIMETER_BOT_ZN_1 15-OCT-12:31 0.00 0.00 0.00 -28486.08 0.00 0.00 32.96 128.90 758.78 29217.25 0.00 0.00 0.00 0.00 -0.00 0.00 -420.40 -1231.42
PERIMETER_BOT_ZN_4 06-AUG-16:41 0.00 0.00 0.00 -30550.40 0.00 0.00 14.26 83.06 488.98 13968.01 0.00 105.75 15890.34 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 06-AUG-16:01 0.00 0.00 0.00 -148778.81 0.00 0.00 435.75 1288.93 7587.73 41215.76 0.00 6217.17 92033.47 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 06-AUG-09:21 0.00 0.00 0.00 -250621.22 0.00 0.00 180.62 830.63 4889.82 164059.61 0.00 0.00 81070.56 0.00 -0.00 0.00 -410.02 0.00
PERIMETER_MID_ZN_1 03-SEP-12:41 0.00 0.00 0.00 -306599.03 0.00 0.00 279.53 1288.96 7587.84 241746.30 0.00 3783.42 51912.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 06-AUG-16:41 0.00 0.00 0.00 -263558.58 0.00 0.00 174.32 830.63 4889.79 140200.24 0.00 2815.65 114647.95 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 16-JUL-18:31 0.00 0.00 0.00 -16288.71 0.00 0.00 0.00 128.89 758.77 5851.83 0.00 268.20 9281.00 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 25-JUN-09:02 0.00 0.00 0.00 -22634.44 0.00 0.00 22.03 83.06 488.98 13253.85 0.00 0.00 9082.66 0.00 -0.00 0.00 -296.15 0.00
PERIMETER_TOP_ZN_1 03-SEP-13:31 0.00 0.00 0.00 -30587.44 0.00 0.00 26.19 128.90 758.78 20590.12 0.00 573.05 8510.39 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 09-JUL-16:41 0.00 0.00 0.00 -27583.96 0.00 0.00 18.89 83.06 488.98 18270.22 0.00 0.00 8780.19 0.00 -0.00 0.00 -57.39 0.00
DATACENTER_BOT_ZN_6 22-APR-18:10 0.00 0.00 0.00 -8241.22 0.00 0.00 0.00 21.20 7794.42 0.00 0.00 0.00 425.60 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 03-AUG-18:50 0.00 0.00 0.00 -78365.55 0.00 0.00 105.11 1271.92 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -955.70
DATACENTER_TOP_ZN_6 03-AUG-18:40 0.00 0.00 0.00 -7952.22 0.00 0.00 10.62 127.19 7794.42 0.00 0.00 0.00 19.99 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 22-AUG-07:20 0.00 0.00 0.00 -369520.48 0.00 0.00 2182.49 5800.91 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18095.45
GROUNDFLOOR_PLENUM 05-SEP-05:15 0.00 -14002.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14081.95 0.00 -0.00 0.00 -79.27 0.00
MIDFLOOR_PLENUM 04-MAR-04:01 0.00 -112520.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 144189.84 0.00 -0.00 0.00 -31669.62 0.00
TOPFLOOR_PLENUM 17-JUL-15:10 0.00 -23042.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.58 22991.09 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-05:03 0.00 -57088.05 0.00 -1937888.45 0.00 0.00 15851.47 38246.31 623236.89 0.00 0.00 0.00 1384539.69 0.00 -61308.13 0.00 -5589.73 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 05-AUG-16:01 0.00 0.00 24095.29 0.00 0.00 0.00 520.12 1143.06 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39216.02
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:11 0.00 0.00 535746.54 0.00 0.00 0.00 0.00 20528.61 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -636846.35
CORE_TOP 09-JAN-04:01 0.00 0.00 79494.21 0.00 0.00 0.00 0.00 1026.54 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -88577.87
PERIMETER_BOT_ZN_3 09-JAN-04:01 0.00 0.00 13695.25 0.00 0.00 0.00 0.00 128.89 1011.70 0.00 0.00 0.00 0.00 0.00 -6555.78 0.00 -841.39 -7438.67
PERIMETER_BOT_ZN_2 09-JAN-04:01 0.00 0.00 15467.80 0.00 0.00 0.00 0.00 83.06 651.98 0.00 0.00 0.00 0.00 0.00 -4349.21 0.00 -563.19 -11290.44
PERIMETER_BOT_ZN_1 09-JAN-04:01 0.00 0.00 21685.78 0.00 0.00 0.00 0.00 128.90 1011.71 0.00 0.00 0.00 0.00 0.00 -6292.44 0.00 -838.45 -15695.49
PERIMETER_BOT_ZN_4 09-JAN-04:01 0.00 0.00 13726.31 0.00 0.00 0.00 0.00 83.06 651.97 0.00 0.00 0.00 0.00 0.00 -4391.98 0.00 -577.29 -9492.08
PERIMETER_MID_ZN_3 09-JAN-02:31 0.00 0.00 138508.93 0.00 0.00 0.00 0.00 1288.93 10116.97 0.00 0.00 0.00 0.00 0.00 -63284.32 0.00 -26284.20 -60346.30
PERIMETER_MID_ZN_2 09-JAN-02:31 0.00 0.00 188846.11 0.00 0.00 0.00 0.00 830.63 6519.76 0.00 0.00 0.00 0.00 0.00 -42149.45 0.00 -17709.41 -136337.64
PERIMETER_MID_ZN_1 09-JAN-02:31 0.00 0.00 228412.85 0.00 0.00 0.00 0.00 1288.96 10117.12 0.00 0.00 0.00 0.00 0.00 -61634.92 0.00 -26569.64 -151614.37
PERIMETER_MID_ZN_4 09-JAN-02:31 0.00 0.00 200624.21 0.00 0.00 0.00 0.00 830.63 6519.72 0.00 0.00 0.00 0.00 0.00 -41168.30 0.00 -17831.64 -148974.63
PERIMETER_TOP_ZN_3 30-JAN-06:01 0.00 0.00 18760.28 0.00 0.00 0.00 186.78 257.76 1011.70 0.00 0.00 0.00 0.00 0.00 -4553.99 0.00 -967.55 -14694.98
PERIMETER_TOP_ZN_2 27-NOV-04:11 0.00 0.00 20126.93 0.00 0.00 0.00 0.00 83.06 651.98 0.00 0.00 0.00 0.00 0.00 -3014.06 0.00 -2284.14 -15563.77
PERIMETER_TOP_ZN_1 27-NOV-04:11 0.00 0.00 26129.68 0.00 0.00 0.00 0.00 128.90 1011.71 0.00 0.00 0.00 0.00 0.00 -4703.49 0.00 -3436.42 -19130.37
PERIMETER_TOP_ZN_4 27-NOV-04:11 0.00 0.00 22394.81 0.00 0.00 0.00 0.00 83.06 651.97 0.00 0.00 0.00 0.00 0.00 -3180.02 0.00 -2335.39 -17614.43
DATACENTER_BOT_ZN_6 09-JAN-03:52 0.00 0.00 633.39 0.00 0.00 0.00 0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2603.20
DATACENTER_MID_ZN_6 29-JAN-17:50 0.00 0.00 6634.76 0.00 0.00 0.00 53.74 211.99 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -26386.54
DATACENTER_TOP_ZN_6 30-APR-23:05 0.00 0.00 760.90 0.00 0.00 0.00 0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2730.71
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 19-DEC-05:01 14917.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1835.66 -13081.97
MIDFLOOR_PLENUM 09-JAN-06:12 146608.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8410.48 -138198.16
TOPFLOOR_PLENUM 11-JAN-05:12 35028.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1463.82 -33564.73
Total Facility 30-JAN-06:01 -4071.34 97926.66 1445058.72 -97926.66 0.00 0.00 22385.18 38246.31 268362.69 0.00 0.00 0.00 0.00 0.00 -204406.04 0.00 -49973.89 -1515601.63



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 12.5168 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.8579 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 119.7014 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 100.5570 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 12.2726 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.2382 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.4199 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.4199 0.1869 1.0000 Not calculated 1.2002 0.1869    
AIRLOOP DATACENTER BASEMENT 24.4620 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.4622 0.0138 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5646 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5646 0.0277 1.0000 Not calculated 0.0156 0.0277    
AIRLOOP DATACENTER MID 5.4026 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4026 0.0289 1.0000 Not calculated 0.1563 0.0289    
AIRLOOP DATACENTER TOP 0.5500 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5500 0.0284 1.0000 Not calculated 0.0156 0.0284    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 6.2584 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.7551 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 59.8507 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 35.9104 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 6.1363 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.6818 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 6.4199 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 6.4199 1.0000 1.0000 Not calculated 1.2002 0.1869    
AIRLOOP DATACENTER BASEMENT 24.4620 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 24.4620 1.0000 1.0000 Not calculated 0.3384 0.0138    
AIRLOOP DATACENTER BOT 0.5646 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5646 1.0000 1.0000 Not calculated 0.0156 0.0277    
AIRLOOP DATACENTER MID 5.4026 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4026 1.0000 1.0000 Not calculated 0.1563 0.0289    
AIRLOOP DATACENTER TOP 0.5500 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5500 1.0000 1.0000 Not calculated 0.0156 0.0284    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.4199 6.4199 6.4199 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.7461 6.7461 2.0238 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 63.3949 63.3949 19.0185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1353 6.1353 1.8406 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0766 1.0766 0.3230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3370 1.3370 0.4011 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6912 1.6912 0.5074 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6660 1.6660 0.4998 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.1312 10.1312 3.0393 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.0653 14.0653 4.2196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 17.0114 17.0114 5.1034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 15.0986 15.0986 4.5296 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2839 1.2839 0.3852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4102 1.4102 0.4231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8357 1.8357 0.5507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6075 1.6075 0.4823 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5646 0.5646 0.5646 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4026 5.4026 5.4026 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5500 0.5500 0.5500 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.4620 24.4620 24.4620 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 12.5168 10.8579 12.5168 3.7551 0.0000 1.0000
VAV_MID WITH REHEAT 119.7014 100.5570 119.7014 35.9104 0.0000 1.0000
VAV_TOP WITH REHEAT 12.2726 11.2382 12.2726 3.6818 0.0000 1.0000
CAV_BAS 6.4199 6.4199 6.4199 6.4199 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.4620 24.4622 24.4620 24.4620 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5646 0.5646 0.5646 0.5646 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4026 5.4026 5.4026 5.4026 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5500 0.5500 0.5500 0.5500 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 6.4199 6.4199 6.4199 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3730 3.3730 2.0238 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 31.6974 31.6974 19.0185 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0677 3.0677 1.8406 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5383 0.5383 0.3230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6685 0.6685 0.4011 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8456 0.8456 0.5074 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8330 0.8330 0.4998 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0656 5.0656 3.0393 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.0326 7.0326 4.2196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.5057 8.5057 5.1034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.5493 7.5493 4.5296 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6420 0.6420 0.3852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7051 0.7051 0.4231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9178 0.9178 0.5507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8038 0.8038 0.4823 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5646 0.5646 0.5646 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4026 5.4026 5.4026 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5500 0.5500 0.5500 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 24.4620 24.4620 24.4620 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 6.2584 3.7551 3.7551 3.7551 0.0000 1.0000
VAV_MID WITH REHEAT 59.8507 35.9104 35.9104 35.9104 0.0000 1.0000
VAV_TOP WITH REHEAT 6.1363 3.6818 3.6818 3.6818 0.0000 1.0000
CAV_BAS 6.4199 6.4199 6.4199 6.4199 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 24.4620 24.4620 24.4620 24.4620 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5646 0.5646 0.5646 0.5646 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4026 5.4026 5.4026 5.4026 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5500 0.5500 0.5500 0.5500 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 113.17
Number of hours cooling loads not met 485.67
Number of hours not met 598.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 5671.61 3008975.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3247.48 476400.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3942.44 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 903.27 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.51 5474.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 61.31 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2738.66 325068.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 434.99 66157.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 837.86 83442.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 841.38 52018.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 848.39 87977.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 30157.09
Natural Gas 0.00 6520.00
Additional 0.00 0.00
Total 15213.41 36677.09


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 85.11
Space Heating 0.00
Space Cooling 70.11
Fans (All) 59.12
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 651.05
Subtotal 651.05


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 122.44
Service Water Heating 18.32
Miscellaneous (All) 140.76
Subtotal 140.76


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 10.75
Space Heating 15.46
Space Cooling 8.85
Fans (All) 7.47
Service Water Heating 2.31
Receptacle Equipment 41.48
Miscellaneous 13.67


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2939. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2347. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8718.33 41.67 0.00 0.00 0.00
CORE_BOTTOM 8754.50 5.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8758.83 1.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8746.33 13.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8746.67 13.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8697.83 62.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.67 0.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8744.67 15.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8746.50 13.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8739.17 20.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8758.67 1.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8744.50 15.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8748.67 11.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8741.00 19.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8740.67 19.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8753.00 7.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8753.00 7.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8201.33 558.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8738.83 21.17 0.00 0.00 0.00
Min 8201.33 0.00 0.00 0.00 0.00
Max 8760.00 558.67 0.00 0.00 0.00
Average 8723.14 36.86 0.00 0.00 0.00
Sum 200632.17 847.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368436.33 179.67 0.00 0.00 0.00
CORE_BOTTOM 330794.00 19.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2264.17 3.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 95487.50 7907.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368436.33 7907.50 0.00 0.00 0.00
Average 79982.30 352.61 0.00 0.00 0.00
Sum 1839593.00 8110.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8686.33 73.67 0.00 0.00 0.00
CORE_BOTTOM 8725.50 34.50 0.00 0.00 0.00
CORE_MID 8711.17 48.83 0.00 0.00 0.00
CORE_TOP 8732.33 27.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8748.00 12.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8747.17 12.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8744.67 15.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8708.83 51.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8750.83 9.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8743.00 17.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8741.83 18.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8734.00 26.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8751.00 9.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8742.17 17.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8742.50 17.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8736.67 23.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8391.00 369.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8745.50 14.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 8751.67 8.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 8726.00 34.00 0.00 0.00 0.00
Min 8391.00 0.00 0.00 0.00 0.00
Max 8760.00 369.00 0.00 0.00 0.00
Average 8723.49 36.51 0.00 0.00 0.00
Sum 200640.17 839.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 368352.00 264.00 0.00 0.00 0.00
CORE_BOTTOM 330735.00 78.00 0.00 0.00 0.00
CORE_MID 330707.00 106.00 0.00 0.00 0.00
CORE_TOP 330755.00 58.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 98003.67 5391.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368352.00 5391.33 0.00 0.00 0.00
Average 80078.51 256.41 0.00 0.00 0.00
Sum 1841805.67 5897.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:59

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -8.80
February -2.17
March 0.301
April 6.668
May 10.099
June 16.456
July 20.571
August 19.174
September 14.689
October 8.635
November 2.839
December -4.07
   
Annual Sum or Average 7.074
Minimum of Months -8.80
Maximum of Months 20.571



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.480240E+11 111728.48 02-JAN-04:11 -0.4 -2.9 0.535418E+10 7499.18 13-JAN-14:30 8.90 4.37
February 0.431146E+11 111032.38 21-FEB-04:01 6.88 1.33 0.504758E+10 7499.21 06-FEB-10:00 6.88 1.33
March 0.535255E+11 108843.47 20-MAR-03:01 -1.6 -3.4 0.611680E+10 7499.15 06-MAR-10:50 -1.6 -3.4
April 0.514433E+11 110281.74 24-APR-03:02 4.82 3.52 0.544585E+10 7499.14 04-APR-09:09 4.82 3.52
May 0.544044E+11 112411.30 30-MAY-03:02 15.60 10.52 0.589981E+10 7499.79 02-MAY-13:20 15.60 10.52
June 0.588288E+11 112888.39 05-JUN-03:02 8.62 5.44 0.588127E+10 7499.11 20-JUN-13:20 27.77 18.21
July 0.611302E+11 111648.41 05-JUL-03:02 9.90 9.28 0.547407E+10 7499.21 03-JUL-13:09 9.90 9.28
August 0.681508E+11 112338.43 14-AUG-03:02 12.20 10.20 0.613850E+10 7499.05 01-AUG-13:20 12.20 10.20
September 0.588644E+11 112864.53 11-SEP-03:02 11.10 10.41 0.545257E+10 7499.34 07-SEP-09:00 11.10 10.41
October 0.602477E+11 112117.63 30-OCT-03:02 5.82 2.52 0.567038E+10 7499.08 06-OCT-09:00 5.82 2.52
November 0.557192E+11 112007.94 20-NOV-04:01 -1.7 -4.9 0.561276E+10 7499.05 03-NOV-09:09 -1.7 -4.9
December 0.531149E+11 111379.76 26-DEC-04:01 -6.3 -8.0 0.541246E+10 7499.17 07-DEC-10:09 -6.3 -8.0
                     
Annual Sum or Average 0.666568E+12         0.675062E+11        
Minimum of Months 0.431146E+11 108843.47   -6.3 -8.0 0.504758E+10 7499.05   -6.3 -8.0
Maximum of Months 0.681508E+11 112888.39   15.60 10.52 0.613850E+10 7499.79   27.77 18.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.317375E+11 85689.76 02-JAN-06:02 -1.3 -3.4 0.495291E+10 6734.77 02-JAN-10:09 2.48 -0.4
February 0.340286E+11 86823.56 28-FEB-05:01 -3.4 -4.0 0.457316E+10 6734.74 28-FEB-10:09 1.57 -0.3
March 0.477226E+11 88639.44 20-MAR-04:02 -1.1 -3.1 0.549218E+10 6734.79 01-MAR-10:09 -1.1 -3.1
April 0.521193E+11 90943.46 10-APR-03:02 4.40 0.24 0.488358E+10 6734.78 04-APR-09:09 4.40 0.24
May 0.491476E+11 93872.97 30-MAY-03:02 15.60 10.52 0.528982E+10 6735.16 02-MAY-13:09 15.60 10.52
June 0.598758E+11 91751.84 05-JUN-03:02 8.62 5.44 0.526947E+10 6734.81 20-JUN-13:09 27.48 18.05
July 0.662267E+11 94681.66 05-JUL-03:02 9.90 9.28 0.489769E+10 6734.96 03-JUL-13:09 9.90 9.28
August 0.743314E+11 90441.61 23-AUG-03:02 11.20 7.14 0.549787E+10 6734.79 01-AUG-13:09 11.20 7.14
September 0.520856E+11 94871.92 11-SEP-03:02 11.10 10.41 0.488236E+10 6735.13 07-SEP-09:50 11.10 10.41
October 0.499802E+11 90205.02 02-OCT-03:02 5.00 2.94 0.507988E+10 6734.74 27-OCT-09:20 8.13 3.61
November 0.453272E+11 90980.79 06-NOV-04:02 -2.8 -3.9 0.502850E+10 6734.74 03-NOV-09:09 -2.8 -3.9
December 0.414509E+11 87296.87 07-DEC-05:01 -1.6 -2.7 0.488885E+10 6734.78 07-DEC-10:09 3.35 1.22
                     
Annual Sum or Average 0.604033E+12         0.607363E+11        
Minimum of Months 0.317375E+11 85689.76   -3.4 -4.0 0.457316E+10 6734.74   -2.8 -3.9
Maximum of Months 0.743314E+11 94871.92   15.60 10.52 0.549787E+10 6735.16   27.48 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.224110E+11 22299.46 05-JAN-17:00 -20.0 -20.5 0.455723E+10 6734.50 04-JAN-14:00 -20.0 -20.5
February 0.225979E+11 60797.01 28-FEB-06:02 -3.9 -4.3 0.432712E+10 6734.73 28-FEB-10:09 1.57 -0.3
March 0.309634E+11 72700.29 30-MAR-05:02 0.00 -2.1 0.534573E+10 6734.78 01-MAR-10:09 0.00 -2.1
April 0.332309E+11 78454.85 08-APR-05:02 7.88 4.42 0.483825E+10 6734.77 04-APR-09:09 7.88 4.42
May 0.376265E+11 81791.04 30-MAY-03:02 15.60 10.52 0.525994E+10 6735.19 02-MAY-13:09 15.60 10.52
June 0.471460E+11 82437.06 23-JUN-03:02 17.38 11.72 0.526222E+10 6734.84 20-JUN-13:09 17.38 11.72
July 0.494214E+11 83308.83 19-JUL-03:02 21.02 16.34 0.489342E+10 6734.97 03-JUL-13:09 21.02 16.34
August 0.515379E+11 85315.68 14-AUG-03:02 12.20 10.20 0.549573E+10 6734.80 01-AUG-13:09 12.20 10.20
September 0.410934E+11 84391.47 11-SEP-03:02 11.10 10.41 0.486924E+10 6735.14 07-SEP-09:00 11.10 10.41
October 0.342962E+11 78644.19 18-OCT-05:02 10.68 3.79 0.503985E+10 6734.74 27-OCT-09:20 8.13 3.61
November 0.278543E+11 73361.53 08-NOV-06:02 10.13 4.88 0.488201E+10 6734.74 03-NOV-09:09 10.13 4.88
December 0.246232E+11 29153.64 07-DEC-16:30 5.55 1.71 0.456840E+10 6734.76 07-DEC-10:09 5.55 1.71
                     
Annual Sum or Average 0.422802E+12         0.593391E+11        
Minimum of Months 0.224110E+11 22299.46   -20.0 -20.5 0.432712E+10 6734.50   -20.0 -20.5
Maximum of Months 0.515379E+11 85315.68   21.02 16.34 0.549573E+10 6735.19   21.02 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.132437E+11 16185.38 13-JAN-17:00 7.80 3.93 0.400211E+10 6372.67 13-JAN-14:00 7.80 3.93
February 0.154331E+11 26421.68 28-FEB-17:00 10.00 4.31 0.387571E+10 6734.33 28-FEB-14:09 10.00 4.31
March 0.216417E+11 29807.03 23-MAR-15:30 7.50 0.92 0.494048E+10 6734.60 02-MAR-14:20 7.50 0.92
April 0.254419E+11 43890.06 26-APR-05:03 5.37 2.97 0.464050E+10 6734.64 13-APR-13:00 5.37 2.97
May 0.322077E+11 76928.28 20-MAY-05:02 11.47 8.41 0.509509E+10 6735.17 02-MAY-13:09 11.47 8.41
June 0.458976E+11 82481.49 21-JUN-03:02 19.22 13.03 0.524243E+10 6734.79 20-JUN-13:09 19.22 13.03
July 0.505589E+11 81572.57 19-JUL-03:02 21.02 16.34 0.488847E+10 6734.96 03-JUL-13:09 21.02 16.34
August 0.502235E+11 80738.99 07-AUG-03:02 20.60 11.11 0.548449E+10 6734.78 01-AUG-13:09 20.60 11.11
September 0.355250E+11 82193.83 05-SEP-03:02 18.30 12.34 0.479123E+10 6735.10 07-SEP-09:00 16.70 15.61
October 0.250191E+11 51582.25 19-OCT-05:03 12.20 5.54 0.479653E+10 6734.68 18-OCT-09:09 12.20 5.54
November 0.188215E+11 28208.22 03-NOV-16:00 14.30 7.69 0.441624E+10 6734.45 17-NOV-14:00 16.50 8.23
December 0.151358E+11 20190.61 06-DEC-17:00 6.70 2.38 0.403736E+10 6734.33 07-DEC-14:39 8.30 2.62
                     
Annual Sum or Average 0.349149E+12         0.562107E+11        
Minimum of Months 0.132437E+11 16185.38   5.37 0.92 0.387571E+10 6372.67   5.37 0.92
Maximum of Months 0.505589E+11 82481.49   21.02 16.34 0.548449E+10 6735.17   21.02 16.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150980E+10 3154.18 02-JAN-06:02 -1.3 -3.4 0.495463E+09 802.46 02-JAN-14:00 6.10 1.11
February 0.236360E+10 4506.20 27-FEB-16:00 18.90 7.06 0.484496E+09 845.60 21-FEB-14:00 18.90 7.06
March 0.390053E+10 4953.60 27-MAR-14:40 9.63 2.75 0.633724E+09 845.61 21-MAR-13:00 9.63 2.75
April 0.520127E+10 7392.64 07-APR-14:30 22.50 9.29 0.593423E+09 845.62 13-APR-13:00 13.30 7.60
May 0.587266E+10 12755.73 30-MAY-05:03 15.60 11.34 0.647060E+09 845.68 02-MAY-13:09 15.60 11.34
June 0.918081E+10 12610.63 26-JUN-05:03 9.87 8.82 0.659428E+09 845.64 20-JUN-13:09 9.87 8.82
July 0.109850E+11 12918.87 03-JUL-05:02 10.65 9.22 0.614788E+09 846.48 20-JUL-13:39 26.70 14.19
August 0.109711E+11 16290.43 06-AUG-16:01 35.50 16.24 0.689086E+09 845.64 01-AUG-13:09 35.50 16.24
September 0.627991E+10 15637.02 04-SEP-16:51 32.80 16.77 0.602177E+09 845.67 07-SEP-09:50 16.52 15.26
October 0.471930E+10 6267.99 19-OCT-14:30 21.40 10.24 0.613095E+09 845.62 18-OCT-13:30 21.40 10.24
November 0.351118E+10 4507.07 24-NOV-14:30 14.90 6.43 0.572061E+09 845.63 16-NOV-14:09 14.90 6.43
December 0.259293E+10 3194.97 06-DEC-05:01 7.20 4.06 0.519174E+09 845.60 06-DEC-14:00 11.10 5.34
                     
Annual Sum or Average 0.670881E+11         0.712397E+10        
Minimum of Months 0.150980E+10 3154.18   -1.3 -3.4 0.484496E+09 802.46   6.10 1.11
Maximum of Months 0.109850E+11 16290.43   35.50 16.77 0.689086E+09 846.48   35.50 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157180E+10 3756.16 02-JAN-06:02 -1.3 -3.4 0.313091E+09 520.16 17-JAN-10:39 5.53 1.42
February 0.257452E+10 6709.06 27-FEB-10:00 11.70 4.23 0.306668E+09 544.95 28-FEB-10:09 1.57 -0.3
March 0.435543E+10 9365.63 28-MAR-09:20 5.73 0.86 0.391889E+09 544.96 01-MAR-10:09 5.73 0.86
April 0.572594E+10 11614.20 24-APR-08:30 10.30 6.86 0.366830E+09 544.95 25-APR-09:09 9.87 4.86
May 0.655036E+10 11810.37 19-MAY-08:30 16.95 11.09 0.409401E+09 544.99 02-MAY-13:09 16.95 11.09
June 0.933495E+10 21305.67 25-JUN-07:52 15.60 11.35 0.421566E+09 546.56 23-JUN-09:00 15.60 11.35
July 0.112015E+11 22480.31 02-JUL-07:51 20.60 14.56 0.394655E+09 546.31 03-JUL-09:00 23.30 14.49
August 0.108804E+11 23097.67 06-AUG-08:41 26.55 14.17 0.440071E+09 546.47 11-AUG-09:50 27.52 12.49
September 0.677864E+10 21429.73 04-SEP-08:52 26.70 14.88 0.380761E+09 544.98 07-SEP-09:50 16.52 15.26
October 0.506227E+10 8933.72 18-OCT-09:20 18.13 8.00 0.382680E+09 544.95 16-OCT-09:09 18.13 8.00
November 0.353176E+10 6190.08 06-NOV-09:35 1.20 -1.1 0.346303E+09 544.95 03-NOV-09:09 1.20 -1.1
December 0.230099E+10 3583.64 06-DEC-05:01 7.20 4.06 0.313430E+09 522.31 20-DEC-10:30 3.85 -0.4
                     
Annual Sum or Average 0.698685E+11         0.446735E+10        
Minimum of Months 0.157180E+10 3583.64   -1.3 -3.4 0.306668E+09 520.16   1.20 -1.1
Maximum of Months 0.112015E+11 23097.67   26.70 14.88 0.440071E+09 546.56   27.52 15.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.340041E+10 12048.22 19-JAN-13:30 -6.2 -7.9 0.523312E+09 845.64 13-JAN-14:30 -6.2 -7.9
February 0.575602E+10 25691.50 26-FEB-13:22 15.30 5.63 0.516856E+09 847.14 27-FEB-14:39 18.70 7.17
March 0.820847E+10 19413.40 01-MAR-13:40 6.33 2.52 0.629639E+09 847.80 23-MAR-13:00 10.00 2.51
April 0.875281E+10 19309.22 16-APR-12:02 17.38 7.48 0.574372E+09 846.31 24-APR-13:00 17.80 9.82
May 0.882818E+10 15395.07 19-MAY-13:30 26.65 14.96 0.627426E+09 846.15 19-MAY-13:00 27.20 15.02
June 0.118594E+11 16211.72 25-JUN-15:12 24.80 13.02 0.651468E+09 846.26 30-JUN-13:20 27.77 13.75
July 0.149345E+11 25863.69 02-JUL-14:32 24.80 14.09 0.612389E+09 846.92 19-JUL-13:00 29.40 17.26
August 0.171160E+11 27271.99 06-AUG-16:01 35.50 16.24 0.685439E+09 853.33 30-AUG-13:39 26.33 14.35
September 0.121922E+11 27749.97 03-SEP-13:11 33.50 16.05 0.595557E+09 853.78 01-SEP-13:30 33.50 16.05
October 0.103007E+11 28482.31 15-OCT-12:31 21.83 10.70 0.610924E+09 863.65 18-OCT-13:30 24.70 11.11
November 0.732717E+10 19300.92 03-NOV-13:20 14.13 7.69 0.578362E+09 847.16 06-NOV-14:00 7.80 2.97
December 0.504236E+10 13777.73 12-DEC-12:30 -2.8 -5.7 0.535513E+09 845.64 19-DEC-14:09 10.97 6.81
                     
Annual Sum or Average 0.113718E+12         0.714126E+10        
Minimum of Months 0.340041E+10 12048.22   -6.2 -7.9 0.516856E+09 845.64   -6.2 -7.9
Maximum of Months 0.171160E+11 28482.31   35.50 16.24 0.685439E+09 863.65   33.50 17.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.259928E+10 4895.51 02-JAN-05:01 -0.2 -2.7 0.316873E+09 531.53 02-JAN-14:00 6.10 1.11
February 0.439852E+10 10319.47 28-FEB-16:40 10.37 4.49 0.318636E+09 544.94 21-FEB-14:00 10.37 4.49
March 0.694024E+10 12863.35 28-MAR-16:00 10.60 3.09 0.413699E+09 544.95 14-MAR-13:00 10.60 3.09
April 0.906426E+10 25904.11 16-APR-17:22 19.70 8.86 0.388597E+09 544.96 13-APR-13:00 19.70 8.86
May 0.844091E+10 25756.48 13-MAY-18:22 21.95 8.73 0.406807E+09 544.99 02-MAY-13:09 21.95 8.73
June 0.118182E+11 25696.33 18-JUN-17:02 25.50 14.50 0.423722E+09 544.97 20-JUN-13:09 27.48 18.05
July 0.148093E+11 30353.99 02-JUL-17:51 25.60 14.12 0.397002E+09 544.98 13-JUL-09:00 23.30 13.98
August 0.163656E+11 30550.80 06-AUG-16:41 35.10 15.80 0.445402E+09 544.97 01-AUG-13:09 35.10 15.80
September 0.860920E+10 28533.36 04-SEP-16:51 32.80 16.77 0.378733E+09 544.99 07-SEP-09:50 16.52 15.26
October 0.719553E+10 20065.31 15-OCT-14:31 22.97 11.08 0.390859E+09 544.96 20-OCT-13:00 13.30 6.77
November 0.601096E+10 9648.80 03-NOV-15:40 14.40 7.69 0.375643E+09 544.95 17-NOV-14:09 16.17 7.86
December 0.514552E+10 8907.63 06-DEC-15:30 10.25 4.94 0.353013E+09 544.94 19-DEC-14:30 11.70 7.15
                     
Annual Sum or Average 0.101398E+12         0.460899E+10        
Minimum of Months 0.259928E+10 4895.51   -0.2 -2.7 0.316873E+09 531.53   6.10 1.11
Maximum of Months 0.163656E+11 30550.80   35.10 16.77 0.445402E+09 544.99   35.10 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188623E+09 1832.99 13-JAN-15:10 9.82 5.10 0.463192E+09 640.66 13-JAN-14:00 9.82 5.10
February 0.761060E+09 3059.51 27-FEB-13:40 17.93 6.85 0.431973E+09 750.72 27-FEB-14:00 18.90 7.23
March 0.194713E+10 3031.87 23-MAR-13:30 9.70 2.18 0.546185E+09 801.69 29-MAR-13:00 12.80 4.50
April 0.289792E+10 5631.47 07-APR-14:30 22.50 9.29 0.537499E+09 845.62 13-APR-13:00 13.30 7.60
May 0.423957E+10 7688.92 19-MAY-16:00 27.80 14.54 0.609037E+09 845.63 25-MAY-13:09 17.20 8.78
June 0.724401E+10 11644.03 23-JUN-05:02 17.88 11.72 0.653166E+09 845.64 20-JUN-13:09 17.88 11.72
July 0.852035E+10 10308.00 20-JUL-05:03 19.50 13.96 0.612850E+09 846.15 18-JUL-13:30 19.50 13.96
August 0.758756E+10 14878.26 06-AUG-16:01 35.50 16.24 0.683036E+09 845.64 01-AUG-13:09 35.50 16.24
September 0.473692E+10 10142.98 03-SEP-16:01 33.67 16.10 0.576631E+09 845.67 07-SEP-09:00 16.70 15.61
October 0.293305E+10 4846.05 19-OCT-14:40 21.50 10.24 0.554982E+09 845.61 19-OCT-13:09 21.50 10.24
November 0.155760E+10 3011.12 03-NOV-13:30 14.35 7.74 0.492829E+09 798.35 08-NOV-14:00 13.20 7.65
December 0.511676E+09 2076.38 06-DEC-15:50 9.68 4.65 0.451793E+09 692.49 06-DEC-14:00 9.68 4.65
                     
Annual Sum or Average 0.431255E+11         0.661317E+10        
Minimum of Months 0.188623E+09 1832.99   9.68 2.18 0.431973E+09 640.66   9.68 4.50
Maximum of Months 0.852035E+10 14878.26   35.50 16.24 0.683036E+09 846.15   35.50 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.345064E+09 2519.26 20-JAN-10:00 -3.3 -5.9 0.219677E+09 390.66 20-JAN-09:00 -3.3 -5.9
February 0.127473E+10 4566.58 26-FEB-11:52 13.30 4.89 0.206728E+09 521.16 28-FEB-09:00 1.10 -0.5
March 0.277543E+10 7339.60 28-MAR-10:05 7.38 1.58 0.261094E+09 521.21 22-MAR-10:20 7.38 1.58
April 0.429994E+10 10811.08 24-APR-09:00 11.70 7.62 0.253034E+09 521.20 13-APR-12:20 11.70 7.62
May 0.563932E+10 12271.44 19-MAY-08:50 17.52 11.29 0.287491E+09 521.26 02-MAY-12:09 17.52 11.29
June 0.876308E+10 21090.55 04-JUN-07:42 15.63 13.07 0.306151E+09 522.83 23-JUN-10:09 27.98 15.45
July 0.104569E+11 23370.12 02-JUL-07:41 20.03 14.35 0.289511E+09 523.14 25-JUL-10:50 31.52 15.07
August 0.959074E+10 25062.17 06-AUG-09:21 28.60 14.63 0.320648E+09 523.35 10-AUG-10:50 31.52 14.77
September 0.598877E+10 21403.15 03-SEP-11:21 31.10 15.57 0.267862E+09 521.21 06-SEP-15:30 26.40 18.80
October 0.382347E+10 7535.97 18-OCT-10:10 20.28 8.90 0.257848E+09 521.21 19-OCT-10:09 19.18 9.33
November 0.192971E+10 4076.77 03-NOV-13:00 13.70 7.60 0.229111E+09 519.86 03-NOV-10:30 13.70 7.60
December 0.648892E+09 2740.63 07-DEC-11:20 6.67 2.71 0.212445E+09 415.90 07-DEC-11:30 6.95 2.80
                     
Annual Sum or Average 0.555360E+11         0.311160E+10        
Minimum of Months 0.345064E+09 2519.26   -3.3 -5.9 0.206728E+09 390.66   -3.3 -5.9
Maximum of Months 0.104569E+11 25062.17   31.10 15.57 0.320648E+09 523.35   31.52 18.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.233142E+10 11615.32 19-JAN-14:00 -5.6 -7.5 0.503844E+09 845.64 13-JAN-14:00 -5.6 -7.5
February 0.469543E+10 28028.78 26-FEB-13:12 15.20 5.59 0.496684E+09 846.07 27-FEB-14:39 18.70 7.17
March 0.662536E+10 20448.61 01-MAR-14:00 6.70 2.77 0.596862E+09 851.72 01-MAR-14:09 6.97 2.89
April 0.680130E+10 24811.53 16-APR-13:12 18.67 7.93 0.546021E+09 845.86 24-APR-13:00 17.80 9.82
May 0.769590E+10 15805.83 19-MAY-13:30 26.65 14.96 0.607184E+09 846.15 19-MAY-13:50 27.02 15.00
June 0.103847E+11 15549.42 30-JUN-13:30 28.05 13.89 0.640948E+09 846.11 30-JUN-13:00 28.90 14.31
July 0.127917E+11 25485.55 16-JUL-15:12 33.13 18.76 0.607948E+09 846.58 19-JUL-13:00 29.40 17.26
August 0.142678E+11 27588.52 06-AUG-16:01 35.50 16.24 0.677608E+09 867.53 30-AUG-13:39 26.33 14.35
September 0.115527E+11 30660.34 03-SEP-12:41 33.22 15.94 0.582576E+09 879.22 01-SEP-13:50 33.22 15.94
October 0.926272E+10 27245.48 15-OCT-13:22 22.75 10.91 0.592833E+09 890.65 18-OCT-13:50 24.90 11.31
November 0.571179E+10 19832.34 03-NOV-13:30 14.35 7.74 0.553513E+09 846.29 06-NOV-14:00 7.80 2.97
December 0.315333E+10 11909.96 12-DEC-14:30 -2.2 -5.4 0.503341E+09 845.63 14-DEC-14:09 3.40 -0.7
                     
Annual Sum or Average 0.952741E+11         0.690936E+10        
Minimum of Months 0.233142E+10 11615.32   -5.6 -7.5 0.496684E+09 845.63   -5.6 -7.5
Maximum of Months 0.142678E+11 30660.34   35.50 18.76 0.677608E+09 890.65   33.22 17.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.515323E+09 3477.56 13-JAN-15:50 9.08 4.76 0.301442E+09 463.97 13-JAN-15:00 8.90 4.67
February 0.153591E+10 7175.20 28-FEB-16:40 10.37 4.49 0.282979E+09 521.21 27-FEB-16:40 10.37 4.49
March 0.303027E+10 8764.54 28-MAR-16:00 10.60 3.09 0.347570E+09 544.93 02-MAR-14:00 10.60 3.09
April 0.457375E+10 22853.94 16-APR-17:11 19.80 8.90 0.330372E+09 544.94 07-APR-13:00 19.80 8.90
May 0.616008E+10 25407.65 28-MAY-18:01 19.82 10.31 0.374323E+09 544.94 30-MAY-13:00 18.90 10.34
June 0.854858E+10 23178.33 18-JUN-17:22 25.30 14.49 0.406350E+09 544.96 20-JUN-13:09 27.48 18.05
July 0.100300E+11 25059.52 16-JUL-17:11 33.13 17.22 0.388442E+09 544.97 03-JUL-13:09 33.13 17.22
August 0.938165E+10 26356.80 06-AUG-16:41 35.10 15.80 0.427986E+09 544.96 01-AUG-13:09 35.10 15.80
September 0.635409E+10 24039.07 03-SEP-16:01 33.67 16.10 0.351598E+09 544.95 05-SEP-09:09 17.20 11.96
October 0.421793E+10 10200.01 16-OCT-16:00 19.40 8.07 0.340899E+09 544.06 13-OCT-13:00 19.40 8.07
November 0.234640E+10 5566.46 03-NOV-15:50 14.35 7.69 0.317454E+09 533.39 09-NOV-14:00 9.00 3.82
December 0.978039E+09 3792.19 06-DEC-15:50 9.68 4.65 0.293849E+09 493.98 06-DEC-15:00 9.40 4.51
                     
Annual Sum or Average 0.576720E+11         0.416326E+10        
Minimum of Months 0.515323E+09 3477.56   9.08 3.09 0.282979E+09 463.97   8.90 3.09
Maximum of Months 0.100300E+11 26356.80   35.10 17.22 0.427986E+09 544.97   35.10 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 43748169.31 2085.86 14-JAN-17:03 8.90 4.06 0.459150E+09 626.07 06-JAN-10:50 8.90 4.06
February 0.333491E+09 2761.66 27-FEB-13:30 17.75 6.76 0.422471E+09 689.60 27-FEB-14:00 18.90 7.23
March 0.117136E+10 3009.94 23-MAR-13:30 9.70 2.18 0.515496E+09 725.92 29-MAR-13:00 12.80 4.50
April 0.238490E+10 5180.85 07-APR-14:30 22.50 9.29 0.493087E+09 845.60 07-APR-13:09 22.50 9.29
May 0.400092E+10 8364.42 19-MAY-16:00 27.80 14.54 0.572170E+09 845.63 25-MAY-13:09 17.20 8.78
June 0.733480E+10 11997.29 23-JUN-05:02 17.88 11.72 0.637243E+09 845.64 20-JUN-13:09 17.88 11.72
July 0.895192E+10 16288.60 16-JUL-18:31 32.40 17.11 0.607526E+09 845.65 03-JUL-13:09 32.40 17.11
August 0.775263E+10 13844.14 06-AUG-16:11 35.40 16.13 0.667967E+09 845.64 01-AUG-13:09 35.40 16.13
September 0.456385E+10 8680.26 05-SEP-14:00 24.40 15.14 0.543882E+09 845.66 07-SEP-09:00 16.70 15.61
October 0.227280E+10 4328.94 18-OCT-14:20 25.00 11.47 0.506164E+09 845.60 19-OCT-13:00 21.10 10.22
November 0.821103E+09 2775.67 08-NOV-15:30 12.80 7.38 0.466364E+09 717.89 08-NOV-14:00 12.80 7.38
December 0.177082E+09 2293.02 06-DEC-16:00 9.40 4.51 0.446669E+09 633.77 06-DEC-14:00 9.40 4.51
                     
Annual Sum or Average 0.398086E+11         0.633819E+10        
Minimum of Months 43748169.31 2085.86   8.90 2.18 0.422471E+09 626.07   8.90 4.06
Maximum of Months 0.895192E+10 16288.60   35.40 17.11 0.667967E+09 845.66   35.40 17.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 97577953.20 2457.96 13-JAN-06:04 0.50 -2.4 0.298680E+09 403.50 09-JAN-10:00 0.50 -2.4
February 0.784220E+09 3372.48 28-FEB-10:40 2.97 0.62 0.276031E+09 499.41 28-FEB-10:50 3.43 0.87
March 0.194132E+10 5686.81 23-MAR-10:30 8.60 1.66 0.346520E+09 544.95 28-MAR-09:39 6.47 1.20
April 0.340722E+10 9798.22 25-APR-09:40 11.27 5.45 0.336762E+09 544.95 25-APR-09:09 11.27 5.45
May 0.505401E+10 11836.27 19-MAY-09:20 18.53 11.74 0.385749E+09 544.99 02-MAY-13:09 18.53 11.74
June 0.864884E+10 22635.34 25-JUN-09:02 17.15 11.95 0.415169E+09 545.93 23-JUN-09:00 17.15 11.95
July 0.106806E+11 22318.50 16-JUL-09:12 22.57 16.22 0.392547E+09 546.22 13-JUL-09:50 22.57 16.22
August 0.954453E+10 22553.57 06-AUG-09:32 29.07 14.77 0.435850E+09 546.05 11-AUG-09:00 27.80 12.62
September 0.541316E+10 16548.09 04-SEP-09:02 26.88 14.90 0.359769E+09 544.95 15-SEP-13:09 19.08 11.71
October 0.294461E+10 6411.26 18-OCT-10:00 20.00 8.80 0.337833E+09 544.95 18-OCT-09:09 20.00 8.80
November 0.113897E+10 3307.93 03-NOV-10:00 8.70 5.33 0.301896E+09 490.30 03-NOV-09:00 8.70 5.33
December 0.279345E+09 2481.82 09-DEC-06:04 -5.1 -5.7 0.288257E+09 407.02 06-DEC-10:50 -5.1 -5.7
                     
Annual Sum or Average 0.499344E+11         0.417506E+10        
Minimum of Months 97577953.20 2457.96   -5.1 -5.7 0.276031E+09 403.50   -5.1 -5.7
Maximum of Months 0.106806E+11 22635.34   29.07 16.22 0.435850E+09 546.22   27.80 16.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156949E+10 9656.95 31-JAN-13:40 -0.8 -4.5 0.487618E+09 845.63 31-JAN-14:30 -0.9 -4.4
February 0.355052E+10 27512.63 26-FEB-14:21 16.15 6.12 0.474980E+09 845.82 28-FEB-14:00 10.60 4.78
March 0.511860E+10 18718.32 01-MAR-14:10 6.97 2.89 0.573192E+09 846.16 23-MAR-13:50 9.90 2.40
April 0.556586E+10 17679.10 25-APR-13:40 16.30 6.98 0.522425E+09 845.86 24-APR-13:00 16.30 6.98
May 0.694045E+10 16380.47 19-MAY-13:50 27.02 15.00 0.587448E+09 845.71 02-MAY-13:09 27.02 15.00
June 0.102636E+11 19277.38 25-JUN-15:02 24.90 13.05 0.627992E+09 845.67 20-JUN-13:09 24.90 13.05
July 0.131604E+11 27848.79 16-JUL-13:52 31.70 18.44 0.601856E+09 846.48 19-JUL-13:50 29.68 17.39
August 0.142849E+11 28943.26 06-AUG-13:32 34.23 15.17 0.667615E+09 849.62 30-AUG-13:39 26.33 14.35
September 0.107619E+11 30587.20 03-SEP-13:31 33.70 16.17 0.564754E+09 860.86 01-SEP-13:50 33.70 16.17
October 0.756288E+10 29486.48 15-OCT-15:02 22.70 11.00 0.566148E+09 854.85 18-OCT-13:50 24.90 11.31
November 0.425078E+10 18101.60 03-NOV-13:30 14.35 7.74 0.526003E+09 845.81 03-NOV-13:00 15.00 7.85
December 0.211469E+10 9396.43 06-DEC-14:40 11.30 5.42 0.482829E+09 845.63 06-DEC-14:00 11.10 5.34
                     
Annual Sum or Average 0.851441E+11         0.668286E+10        
Minimum of Months 0.156949E+10 9396.43   -0.8 -4.5 0.474980E+09 845.63   -0.9 -4.4
Maximum of Months 0.142849E+11 30587.20   34.23 18.44 0.667615E+09 860.86   33.70 17.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.259327E+09 3477.46 13-JAN-15:50 9.08 4.76 0.299353E+09 444.22 13-JAN-15:00 8.90 4.67
February 0.102082E+10 6563.70 28-FEB-16:40 10.37 4.49 0.278741E+09 521.19 27-FEB-16:19 10.37 4.49
March 0.213351E+10 8310.56 28-MAR-16:00 10.60 3.09 0.339878E+09 543.18 02-MAR-14:00 10.60 3.09
April 0.378274E+10 18279.34 16-APR-17:11 19.80 8.90 0.317298E+09 543.25 25-APR-13:00 16.10 6.69
May 0.564424E+10 26835.91 28-MAY-18:01 19.82 10.31 0.362030E+09 544.95 19-MAY-13:09 19.82 10.31
June 0.847788E+10 24627.15 18-JUN-17:22 25.30 14.49 0.396892E+09 544.96 20-JUN-13:09 27.48 18.05
July 0.102817E+11 27584.86 09-JUL-16:41 28.30 12.98 0.383555E+09 544.97 03-JUL-13:09 28.30 12.98
August 0.937683E+10 25648.46 06-AUG-16:11 35.40 16.13 0.419434E+09 544.96 01-AUG-13:09 35.40 16.13
September 0.588147E+10 25575.92 04-SEP-17:01 32.62 16.70 0.340408E+09 544.94 05-SEP-13:00 24.40 15.14
October 0.330285E+10 9988.47 18-OCT-16:00 24.40 11.02 0.326453E+09 525.64 13-OCT-13:00 24.40 11.02
November 0.153340E+10 4821.57 03-NOV-15:50 14.35 7.69 0.307699E+09 521.17 03-NOV-15:00 14.30 7.69
December 0.540465E+09 3781.48 06-DEC-15:50 9.68 4.65 0.290174E+09 471.06 06-DEC-15:00 9.40 4.51
                     
Annual Sum or Average 0.522352E+11         0.406191E+10        
Minimum of Months 0.259327E+09 3477.46   9.08 3.09 0.278741E+09 444.22   8.90 3.09
Maximum of Months 0.102817E+11 27584.86   35.40 16.70 0.419434E+09 544.97   35.40 18.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.682721E+09 7725.21 06-JAN-05:01 -24.5 -24.9 0.00 0.00 01-JAN-00:10 -24.5 -24.9
February 0.103301E+10 5665.94 28-FEB-06:08 -3.9 -4.3 0.00 0.00 01-FEB-00:10 -3.9 -4.3
March 0.256497E+10 5312.50 04-MAR-06:01 -20.1 -20.7 0.00 0.00 01-MAR-00:10 -20.1 -20.7
April 0.426985E+10 6048.70 25-APR-05:15 1.10 -0.7 0.00 0.00 01-APR-00:10 1.10 -0.7
May 0.433834E+10 9818.21 30-MAY-05:15 15.60 11.34 0.00 0.00 01-MAY-00:10 15.60 11.34
June 0.776956E+10 8937.68 26-JUN-05:15 10.33 9.12 0.00 0.00 01-JUN-00:10 10.33 9.12
July 0.974827E+10 10514.54 31-JUL-05:15 14.60 10.97 0.00 0.00 01-JUL-00:10 14.60 10.97
August 0.101712E+11 11554.42 07-AUG-05:15 17.77 10.09 0.00 0.00 01-AUG-00:10 17.77 10.09
September 0.604158E+10 14003.90 05-SEP-05:15 18.50 11.75 0.00 0.00 01-SEP-00:10 18.50 11.75
October 0.437484E+10 5711.03 02-OCT-05:15 4.80 2.86 0.00 0.00 01-OCT-00:10 4.80 2.86
November 0.259337E+10 6122.83 06-NOV-06:07 -3.5 -4.3 0.00 0.00 01-NOV-00:10 -3.5 -4.3
December 0.128179E+10 4409.69 09-DEC-06:07 -5.1 -5.7 0.00 0.00 01-DEC-00:10 -5.1 -5.7
                     
Annual Sum or Average 0.548696E+11         0.00        
Minimum of Months 0.682721E+09 4409.69   -24.5 -24.9 0.00 0.00   -24.5 -24.9
Maximum of Months 0.101712E+11 14003.90   18.50 11.75 0.00 0.00   18.50 11.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.441798E+09 10393.84 06-JAN-04:11 -24.4 -24.9 0.00 0.00 01-JAN-00:10 -24.4 -24.9
February 0.367042E+09 9283.22 04-FEB-04:01 -21.9 -22.2 0.00 0.00 01-FEB-00:10 -21.9 -22.2
March 0.104429E+10 11251.97 04-MAR-04:01 -18.4 -18.9 0.00 0.00 01-MAR-00:10 -18.4 -18.9
April 0.181807E+10 6537.90 29-APR-04:01 -7.8 -8.7 0.00 0.00 01-APR-00:10 -7.8 -8.7
May 0.251695E+10 6861.90 08-MAY-04:01 -2.3 -2.7 0.00 0.00 01-MAY-00:10 -2.3 -2.7
June 0.568103E+10 6922.24 22-JUN-05:15 16.10 12.59 0.00 0.00 01-JUN-00:10 16.10 12.59
July 0.733787E+10 8085.29 17-JUL-15:40 36.83 17.19 0.00 0.00 01-JUL-00:10 36.83 17.19
August 0.719658E+10 8196.27 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.434519E+10 7925.50 05-SEP-14:50 24.40 14.84 0.00 0.00 01-SEP-00:10 24.40 14.84
October 0.220580E+10 6097.50 10-OCT-04:01 -5.2 -5.7 0.00 0.00 01-OCT-00:10 -5.2 -5.7
November 0.103645E+10 8875.89 27-NOV-04:01 -15.8 -16.7 0.00 0.00 01-NOV-00:10 -15.8 -16.7
December 0.610829E+09 8195.77 29-DEC-04:01 -24.5 -24.8 0.00 0.00 01-DEC-00:10 -24.5 -24.8
                     
Annual Sum or Average 0.346019E+11         0.00        
Minimum of Months 0.367042E+09 6097.50   -24.5 -24.9 0.00 0.00   -24.5 -24.9
Maximum of Months 0.733787E+10 11251.97   36.83 17.19 0.00 0.00   36.83 17.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 15997.73 106.65 14-JAN-17:10 8.90 4.06 0.00 0.00 01-JAN-00:10 8.90 4.06
February 95437794.01 2356.28 26-FEB-15:07 16.60 6.44 0.00 0.00 01-FEB-00:10 16.60 6.44
March 0.582116E+09 4722.57 23-MAR-13:50 9.90 2.40 0.00 0.00 01-MAR-00:10 9.90 2.40
April 0.222066E+10 11197.31 25-APR-15:00 17.00 7.46 0.00 0.00 01-APR-00:10 17.00 7.46
May 0.476256E+10 16794.04 19-MAY-15:00 28.30 14.88 0.00 0.00 01-MAY-00:10 28.30 14.88
June 0.983082E+10 19593.51 23-JUN-13:30 31.40 15.21 0.00 0.00 01-JUN-00:10 31.40 15.21
July 0.130322E+11 23043.35 17-JUL-15:10 36.28 17.05 0.00 0.00 01-JUL-00:10 36.28 17.05
August 0.111281E+11 20548.87 07-AUG-15:40 32.40 16.10 0.00 0.00 01-AUG-00:10 32.40 16.10
September 0.524412E+10 15101.18 05-SEP-14:40 24.40 14.90 0.00 0.00 01-SEP-00:10 24.40 14.90
October 0.140643E+10 8736.54 18-OCT-15:10 24.90 11.51 0.00 0.00 01-OCT-00:10 24.90 11.51
November 0.104728E+09 2174.14 03-NOV-14:10 14.93 7.82 0.00 0.00 01-NOV-00:10 14.93 7.82
December 0.00 0.00 01-DEC-00:10 -2.1 -4.2 0.00 0.00 01-DEC-00:10 -2.1 -4.2
                     
Annual Sum or Average 0.484072E+11         0.00        
Minimum of Months 0.00 0.00   -2.1 -4.2 0.00 0.00   -2.1 -4.2
Maximum of Months 0.130322E+11 23043.35   36.28 17.05 0.00 0.00   36.28 17.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201969E+10 1980.93 19-JAN-16:50 -6.4 -8.0 95180074.29 126.82 02-JAN-10:09 -6.4 -8.0
February 0.723711E+10 4315.35 28-FEB-17:00 10.00 4.31 86396454.73 126.82 02-FEB-14:09 10.00 4.31
March 0.137747E+11 6834.60 31-MAR-24:00 2.50 0.99 0.103236E+09 126.82 15-MAR-13:09 2.50 0.99
April 0.187440E+11 8241.22 22-APR-18:10 15.63 8.19 91605256.35 126.82 20-APR-13:00 15.63 8.19
May 0.421289E+10 3506.71 31-MAY-24:00 15.50 10.27 99234981.46 126.84 30-MAY-09:30 15.50 10.27
June 0.932884E+10 5359.07 30-JUN-24:00 19.60 12.23 98962606.91 126.85 01-JUN-13:00 19.60 12.23
July 0.148240E+11 7239.20 31-JUL-23:35 19.77 11.91 91883758.73 126.84 03-JUL-13:09 19.77 11.91
August 0.198949E+11 8218.20 29-AUG-17:50 23.90 12.71 0.103515E+09 133.36 11-AUG-13:00 23.90 12.71
September 0.419490E+10 3316.17 30-SEP-24:00 11.80 6.26 91610960.71 126.86 06-SEP-13:50 11.80 6.26
October 0.915534E+10 4965.71 31-OCT-24:00 4.70 1.47 95230928.37 126.83 25-OCT-09:00 4.70 1.47
November 0.134092E+11 6077.34 13-NOV-16:20 3.27 -2.5 94300329.95 126.83 08-NOV-14:00 3.27 -2.5
December 0.184029E+11 7853.15 06-DEC-16:10 8.95 4.16 91880816.28 126.82 04-DEC-14:50 8.95 4.16
                     
Annual Sum or Average 0.135199E+12         0.114304E+10        
Minimum of Months 0.201969E+10 1980.93   -6.4 -8.0 86396454.73 126.82   -6.4 -8.0
Maximum of Months 0.198949E+11 8241.22   23.90 12.71 0.103515E+09 133.36   23.90 12.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.513429E+09 1617.99 19-JAN-16:50 -6.4 -8.0 93322651.35 126.93 31-JAN-10:00 -5.0 -7.7
February 0.502283E+10 3943.24 28-FEB-17:00 10.00 4.31 86396467.06 126.82 17-FEB-14:20 10.00 4.31
March 0.113951E+11 5924.91 31-MAR-23:30 2.00 0.53 0.103236E+09 126.82 15-MAR-13:09 2.00 0.53
April 0.167910E+11 7806.77 25-APR-18:10 16.73 7.64 91605289.01 126.82 24-APR-09:09 16.73 7.64
May 0.323062E+10 3309.65 31-MAY-24:00 15.50 10.27 99234857.04 126.84 30-MAY-09:30 15.50 10.27
June 0.854312E+10 5241.94 30-JUN-24:00 19.60 12.23 98962343.83 126.85 01-JUN-13:00 19.60 12.23
July 0.139855E+11 7067.02 31-JUL-23:55 19.20 11.32 91883948.32 126.84 03-JUL-13:09 19.20 11.32
August 0.186822E+11 7836.85 03-AUG-18:50 24.60 12.54 0.103356E+09 131.23 11-AUG-13:00 32.20 13.16
September 0.338163E+10 2886.21 30-SEP-23:40 12.27 6.64 91609777.88 126.84 11-SEP-13:00 12.27 6.64
October 0.750762E+10 4161.96 31-OCT-24:00 4.70 1.47 95230855.15 126.83 25-OCT-09:00 4.70 1.47
November 0.109711E+11 5550.58 03-NOV-16:00 14.30 7.69 94300350.55 126.83 08-NOV-14:00 13.20 7.65
December 0.148987E+11 7146.80 06-DEC-16:20 8.50 3.80 91880839.67 126.82 18-DEC-14:39 0.60 -2.8
                     
Annual Sum or Average 0.114923E+12         0.114102E+10        
Minimum of Months 0.513429E+09 1617.99   -6.4 -8.0 86396467.06 126.82   -5.0 -7.7
Maximum of Months 0.186822E+11 7836.85   24.60 12.54 0.103356E+09 131.23   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.201331E+09 1412.43 13-JAN-16:30 8.35 4.30 88195039.26 128.11 13-JAN-10:20 8.35 4.30
February 0.341619E+10 3888.33 28-FEB-17:00 10.00 4.31 86391041.43 126.82 03-FEB-14:20 10.00 4.31
March 0.972390E+10 5844.66 28-MAR-17:50 9.18 2.32 0.103236E+09 126.82 15-MAR-13:09 9.18 2.32
April 0.155993E+11 7859.35 25-APR-18:10 16.73 7.64 91605316.29 126.82 21-APR-09:00 16.73 7.64
May 0.264916E+10 3227.06 31-MAY-24:00 15.50 10.27 98938187.53 126.92 09-MAY-09:09 15.50 10.27
June 0.830857E+10 5241.29 30-JUN-24:00 19.60 12.23 98962428.58 126.84 01-JUN-13:00 19.60 12.23
July 0.139123E+11 7015.60 31-JUL-23:55 19.20 11.32 91884000.36 126.84 03-JUL-13:09 19.20 11.32
August 0.185280E+11 7952.55 03-AUG-18:40 24.80 12.58 0.103322E+09 129.46 11-AUG-13:00 32.20 13.16
September 0.284575E+10 2786.97 04-SEP-17:32 32.07 16.48 91608024.72 126.84 05-SEP-09:00 17.20 11.96
October 0.609368E+10 4034.26 18-OCT-17:00 21.70 10.27 95230835.25 126.83 25-OCT-09:00 13.30 8.54
November 0.905619E+10 5476.74 03-NOV-16:00 14.30 7.69 94300356.97 126.83 08-NOV-14:00 13.20 7.65
December 0.128116E+11 7048.30 06-DEC-16:20 8.50 3.80 91880847.24 126.82 27-DEC-14:20 -15.4 -15.9
                     
Annual Sum or Average 0.103146E+12         0.113555E+10        
Minimum of Months 0.201331E+09 1412.43   8.35 2.32 86391041.43 126.82   -15.4 -15.9
Maximum of Months 0.185280E+11 7952.55   32.07 16.48 0.103322E+09 129.46   32.20 13.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234226E+12 91682.57 02-JAN-17:00 2.20 -1.7 0.206142E+10 2745.29 02-JAN-14:00 2.20 -1.7
February 0.433314E+12 183625.07 28-FEB-17:00 10.00 4.31 0.187202E+10 2748.44 10-FEB-10:09 10.00 4.31
March 0.726961E+12 357618.64 31-MAR-24:00 2.50 0.99 0.223629E+10 2747.51 03-MAR-10:00 2.50 0.99
April 0.941031E+12 367084.58 26-APR-16:00 9.40 4.24 0.199585E+10 3008.79 07-APR-13:00 9.40 4.24
May 0.239968E+12 176046.09 31-MAY-24:00 15.50 10.27 0.214841E+10 2747.90 30-MAY-13:00 15.50 10.27
June 0.469948E+12 267987.34 30-JUN-24:00 19.60 12.23 0.214395E+10 2748.66 20-JUN-13:50 19.60 12.23
July 0.732512E+12 359225.79 31-JUL-23:12 20.33 12.51 0.198985E+10 2750.06 18-JUL-09:00 20.33 12.51
August 0.972051E+12 369521.79 22-AUG-07:20 12.77 9.84 0.254859E+10 3863.51 07-AUG-13:00 12.77 9.84
September 0.235600E+12 175720.50 30-SEP-24:00 11.80 6.26 0.198353E+10 2748.17 06-SEP-13:39 11.80 6.26
October 0.486898E+12 267723.28 31-OCT-24:00 4.70 1.47 0.206337E+10 2748.50 24-OCT-13:09 4.70 1.47
November 0.707098E+12 276676.74 06-NOV-16:55 6.70 2.26 0.204275E+10 2747.58 08-NOV-14:00 13.20 7.65
December 0.973608E+12 367838.30 06-DEC-17:00 6.70 2.38 0.198912E+10 2745.72 05-DEC-14:20 6.70 2.38
                     
Annual Sum or Average 0.715322E+13         0.250752E+11        
Minimum of Months 0.234226E+12 91682.57   2.20 -1.7 0.187202E+10 2745.29   2.20 -1.7
Maximum of Months 0.973608E+12 369521.79   20.33 12.51 0.254859E+10 3863.51   20.33 12.51



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.305745E+09 14079.44 02-JAN-04:54 0.00
February 71849494.39 14214.15 21-FEB-05:25 7.25
March 0.142831E+09 13955.87 20-MAR-04:25 -1.1
April 0.134399E+09 13825.76 03-APR-03:04 1.88
May 0.315604E+09 16552.78 20-MAY-16:03 29.82
June 0.280818E+09 15277.84 24-JUN-16:02 28.22
July 0.440733E+09 21193.10 15-JUL-16:01 32.80
August 0.433607E+09 24095.36 05-AUG-16:01 35.22
September 0.491742E+09 21890.93 02-SEP-16:02 33.98
October 0.403321E+09 13775.48 03-OCT-03:04 2.98
November 0.283637E+09 14924.00 12-NOV-16:53 -1.1
December 0.130516E+09 13486.07 18-DEC-04:03 -3.7
         
Annual Sum or Average 0.343480E+10      
Minimum of Months 71849494.39 13486.07   -3.7
Maximum of Months 0.491742E+09 24095.36   35.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.403122E+09 53574.72 09-JAN-05:11 -27.2
February 0.117829E+09 52093.94 06-FEB-05:11 -0.2
March 29398266.56 50074.95 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 5371359.26 47194.87 27-NOV-06:01 -14.5
December 84472069.24 51078.30 26-DEC-05:01 -7.3
         
Annual Sum or Average 0.640193E+09      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.403122E+09 53574.72   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.830696E+10 79494.31 09-JAN-04:01 -27.2
February 0.279767E+10 78408.44 06-FEB-04:11 -0.6
March 0.158365E+10 78268.05 06-MAR-04:01 -18.4
April 33902239.42 63565.52 10-APR-05:01 3.90
May 0.504102E+09 71073.94 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.258359E+09 70726.77 10-OCT-04:11 -5.4
November 0.191861E+10 78142.24 27-NOV-04:11 -15.7
December 0.405027E+10 78368.44 26-DEC-04:01 -6.3
         
Annual Sum or Average 0.194535E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.830696E+10 79494.31   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194098E+10 13695.23 09-JAN-04:01 -27.2
February 0.438110E+09 12138.78 04-FEB-05:01 -20.4
March 76086044.36 12344.80 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 27417684.13 11600.13 27-NOV-05:01 -15.4
December 0.273393E+09 12052.97 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.275599E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.194098E+10 13695.23   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.129713E+10 15467.79 09-JAN-04:01 -27.2
February 0.352255E+09 13648.61 04-FEB-05:01 -20.4
March 69037298.52 13797.14 06-MAR-05:01 -18.4
April 1566324.96 7384.52 15-APR-05:01 -0.6
May 117333.28 1760.00 22-MAY-05:01 -0.6
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 126275.02 829.97 04-OCT-05:03 -0.5
November 41414131.50 13358.90 27-NOV-05:01 -15.4
December 0.310715E+09 13743.85 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.207236E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.129713E+10 15467.79   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185490E+10 21685.77 09-JAN-04:01 -27.2
February 0.413699E+09 19488.03 04-FEB-05:01 -20.4
March 0.130721E+09 20104.95 06-MAR-04:01 -18.4
April 2736289.07 13655.70 29-APR-05:01 -7.7
May 13464824.52 16520.63 08-MAY-05:02 -2.8
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 3465996.49 13217.99 10-OCT-05:02 -6.1
November 96175531.02 19192.76 27-NOV-05:01 -15.4
December 0.425454E+09 19324.18 30-DEC-05:01 -20.6
         
Annual Sum or Average 0.294062E+10      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.185490E+10 21685.77   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.565758E+09 13726.31 09-JAN-04:01 -27.2
February 30471001.82 10751.27 04-FEB-06:01 -19.5
March 4483999.68 11427.66 06-MAR-05:01 -18.4
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 1518963.64 10650.50 27-NOV-06:01 -14.5
December 3892496.65 10619.92 29-DEC-06:01 -25.1
         
Annual Sum or Average 0.606125E+09      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.565758E+09 13726.31   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.735710E+10 13850.88 09-JAN-02:31 -27.2
February 0.326001E+10 13350.70 06-FEB-03:53 -0.6
March 0.143508E+10 13652.63 06-MAR-03:23 -18.6
April 0.126707E+09 11282.67 29-APR-04:01 -7.8
May 0.158171E+09 11904.51 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 14777635.14 10375.23 19-SEP-05:03 2.20
October 0.120827E+09 11609.26 10-OCT-04:01 -5.2
November 0.137388E+10 13426.37 27-NOV-04:01 -15.8
December 0.422593E+10 13688.13 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.180725E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.735710E+10 13850.88   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.446882E+10 18884.58 09-JAN-02:31 -27.2
February 0.183078E+10 17659.54 04-FEB-04:01 -21.9
March 0.813014E+09 18460.07 06-MAR-04:01 -18.4
April 78946448.45 15358.91 29-APR-04:01 -7.8
May 0.103073E+09 16184.84 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 9666758.26 8099.36 19-SEP-05:03 2.20
October 72534075.40 15664.50 10-OCT-04:01 -5.2
November 0.864649E+09 18341.41 27-NOV-04:01 -15.8
December 0.257024E+10 18646.02 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.108117E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.446882E+10 18884.58   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472006E+10 22841.26 09-JAN-02:31 -27.2
February 0.165778E+10 21404.97 04-FEB-04:01 -21.9
March 0.832138E+09 22346.13 06-MAR-04:01 -18.4
April 0.106889E+09 18560.23 29-APR-04:01 -7.8
May 0.158527E+09 19663.78 08-MAY-04:01 -2.3
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 7581291.02 8641.63 19-SEP-05:03 2.20
October 59558408.63 18851.75 10-OCT-04:01 -5.2
November 0.792812E+09 22089.27 27-NOV-04:01 -15.8
December 0.248191E+10 22641.24 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.108173E+11      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.472006E+10 22841.26   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.398708E+10 20062.39 09-JAN-02:31 -27.2
February 0.141908E+10 18761.75 04-FEB-04:01 -21.9
March 0.625607E+09 19547.29 06-MAR-04:01 -18.4
April 47370959.74 15253.22 29-APR-05:01 -7.7
May 76130471.94 17147.89 08-MAY-04:01 -2.3
June 45236.99 301.58 17-JUN-05:05 2.35
July 0.00 0.00 01-JUL-00:10 19.45
August 27762.44 231.35 18-AUG-05:04 7.30
September 6182986.57 6824.24 19-SEP-05:03 2.20
October 47440772.97 16383.79 10-OCT-04:01 -5.2
November 0.604897E+09 19420.94 27-NOV-04:01 -15.8
December 0.192338E+10 19757.50 31-DEC-07:31 -28.0
         
Annual Sum or Average 0.873724E+10      
Minimum of Months 0.00 0.00   -28.0
Maximum of Months 0.398708E+10 20062.39   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147429E+11 18760.56 30-JAN-06:01 -15.9
February 0.749916E+10 18083.62 06-FEB-01:32 -2.4
March 0.455159E+10 18217.78 06-MAR-05:01 -18.4
April 0.115565E+10 15722.80 29-APR-03:02 -6.9
May 0.941454E+09 16477.90 01-MAY-03:11 -0.7
June 17529167.97 13969.83 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 13004597.51 13148.60 18-AUG-05:02 7.30
September 0.282623E+09 14975.23 19-SEP-04:01 2.20
October 0.112690E+10 16298.43 10-OCT-03:01 -4.1
November 0.485229E+10 18608.02 27-NOV-04:11 -15.7
December 0.106190E+11 18443.83 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.458021E+11      
Minimum of Months 0.00 0.00   -24.9
Maximum of Months 0.147429E+11 18760.56   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.891097E+10 19657.30 09-JAN-04:01 -27.2
February 0.418426E+10 19421.94 05-FEB-06:52 -20.0
March 0.249350E+10 19375.58 06-MAR-05:01 -18.4
April 0.568793E+09 16860.50 29-APR-03:02 -6.9
May 0.534553E+09 17740.01 01-MAY-03:11 -0.7
June 9801958.74 14226.72 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 7717128.31 9744.48 18-AUG-05:02 7.30
September 0.145503E+09 16078.33 19-SEP-04:01 2.20
October 0.587105E+09 17529.99 10-OCT-03:01 -4.1
November 0.276284E+10 20127.63 27-NOV-04:11 -15.7
December 0.638165E+10 19934.19 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.265867E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.891097E+10 20127.63   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103515E+11 25542.86 09-JAN-02:41 -27.2
February 0.450007E+10 25338.31 05-FEB-06:52 -20.0
March 0.307876E+10 25216.50 06-MAR-05:01 -18.4
April 0.881616E+09 22010.18 29-APR-03:02 -6.9
May 0.898405E+09 23190.58 01-MAY-03:11 -0.7
June 31985694.73 19691.35 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 18005185.82 15111.36 18-AUG-05:02 7.30
September 0.180523E+09 20850.55 19-SEP-04:01 2.20
October 0.616033E+09 22991.13 10-OCT-03:01 -4.1
November 0.295375E+10 26130.50 27-NOV-04:11 -15.7
December 0.707907E+10 25861.24 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.305897E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.103515E+11 26130.50   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.827503E+10 22122.77 09-JAN-04:01 -27.2
February 0.342408E+10 21526.47 05-FEB-08:12 -20.2
March 0.204511E+10 21592.71 06-MAR-05:01 -18.4
April 0.427709E+09 17977.69 15-APR-04:01 -0.1
May 0.412759E+09 19761.38 08-MAY-03:01 -2.7
June 13152488.90 9260.40 17-JUN-04:02 2.12
July 0.00 0.00 01-JUL-00:10 19.45
August 8271712.20 9552.54 18-AUG-05:02 7.30
September 0.106796E+09 17876.04 19-SEP-04:01 2.20
October 0.415066E+09 19728.30 10-OCT-03:01 -4.1
November 0.208603E+10 22395.44 27-NOV-04:11 -15.7
December 0.505661E+10 22065.95 31-DEC-03:41 -24.9
         
Annual Sum or Average 0.222706E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.827503E+10 22395.44   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.214193E+10 12759.61 24-JAN-06:03 8.22
February 0.871152E+09 13654.18 08-FEB-06:01 -4.1
March 0.354848E+09 13728.28 09-MAR-06:01 2.30
April 0.131101E+09 12434.30 17-APR-03:02 9.40
May 74191735.93 11253.84 01-MAY-04:01 -0.6
June 91527320.98 9808.80 19-JUN-03:02 13.53
July 0.120110E+09 10657.19 05-JUL-03:02 9.90
August 0.110171E+09 11580.81 06-AUG-16:01 35.50
September 81098870.73 9854.27 20-SEP-04:01 3.30
October 94976196.91 10969.52 10-OCT-03:01 -4.1
November 0.209502E+09 14172.67 30-NOV-06:01 1.10
December 0.394928E+09 14917.18 19-DEC-05:01 3.40
         
Annual Sum or Average 0.467554E+10      
Minimum of Months 74191735.93 9808.80   -4.1
Maximum of Months 0.214193E+10 14917.18   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.507036E+10 14660.86 09-JAN-06:12 -27.2
February 0.278954E+10 10134.13 06-FEB-06:03 0.60
March 0.142554E+10 8225.48 06-MAR-13:30 -0.3
April 0.135267E+09 8039.02 16-APR-14:31 19.40
May 0.376376E+09 8837.75 03-MAY-05:02 0.92
June 61772269.46 6923.56 21-JUN-03:02 19.22
July 70703491.05 7392.06 16-JUL-15:12 33.13
August 58621078.81 10876.73 06-AUG-16:01 35.50
September 75439704.84 7963.45 03-SEP-15:21 33.30
October 0.243012E+09 8595.32 13-OCT-05:02 14.03
November 0.125400E+10 7467.43 08-NOV-06:02 10.13
December 0.289065E+10 8405.53 26-DEC-06:05 -7.9
         
Annual Sum or Average 0.144513E+11      
Minimum of Months 58621078.81 6923.56   -27.2
Maximum of Months 0.507036E+10 14660.86   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200505E+11 35028.54 11-JAN-05:12 -30.2
February 0.106292E+11 29822.86 04-FEB-05:12 -20.2
March 0.733057E+10 32975.08 06-MAR-05:09 -18.4
April 0.267272E+10 14641.20 26-APR-05:03 5.37
May 0.203570E+10 22259.69 08-MAY-04:12 -2.4
June 0.356893E+09 17827.86 14-JUN-05:02 7.30
July 0.135862E+09 16841.84 12-JUL-05:03 6.85
August 0.260309E+09 18668.78 17-AUG-05:02 7.38
September 0.987324E+09 17514.96 28-SEP-05:03 8.90
October 0.269981E+10 21545.24 10-OCT-04:23 -5.5
November 0.767012E+10 31237.34 27-NOV-05:11 -15.3
December 0.150048E+11 32197.38 29-DEC-05:22 -25.0
         
Annual Sum or Average 0.698339E+11      
Minimum of Months 0.135862E+09 14641.20   -30.2
Maximum of Months 0.200505E+11 35028.54   8.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 62287741.73 633.39 09-JAN-03:52 -27.2
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 62287741.73      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 62287741.73 633.39   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.556240E+09 663.47 29-JAN-17:50 -21.9
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 2135343.30 139.42 08-MAY-04:12 -2.4
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.558376E+09      
Minimum of Months 0.00 0.00   -21.9
Maximum of Months 0.556240E+09 663.47   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.887275E+09 692.73 29-JAN-17:50 -21.9
February 68950576.14 635.53 05-FEB-18:33 -18.3
March 0.00 0.00 01-MAR-00:10 -3.0
April 2481248.24 760.90 30-APR-23:05 -1.3
May 0.123438E+09 659.32 01-MAY-00:20 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 26422515.57 499.09 17-SEP-07:25 3.60
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.110857E+10      
Minimum of Months 0.00 0.00   -21.9
Maximum of Months 0.887275E+09 760.90   19.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.38
February 0.00 0.00 01-FEB-00:10 -12.4
March 0.00 0.00 01-MAR-00:10 -3.0
April 0.00 0.00 01-APR-00:10 2.68
May 0.00 0.00 01-MAY-00:10 -1.1
June 0.00 0.00 01-JUN-00:10 15.42
July 0.00 0.00 01-JUL-00:10 19.45
August 0.00 0.00 01-AUG-00:03 18.90
September 0.00 0.00 01-SEP-00:02 18.43
October 0.00 0.00 01-OCT-00:10 11.57
November 0.00 0.00 01-NOV-00:10 4.98
December 0.00 0.00 01-DEC-00:10 -2.1
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -12.4
Maximum of Months 0.00 0.00   19.45



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196603E+11 20573.73 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.178333E+11 20573.73 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.211910E+11 20573.73 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.189279E+11 20573.73 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.204256E+11 20573.73 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.203269E+11 20573.73 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.190266E+11 20573.73 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.211910E+11 20573.73 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.189279E+11 20573.73 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.196603E+11 20573.73 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.194299E+11 20573.73 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.190266E+11 20573.73 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.235627E+12     0.424397E+12    
Minimum of Months 0.178333E+11 20573.73   0.325565E+11 13457.54  
Maximum of Months 0.211910E+11 20573.73   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321286E+12    
Minimum of Months 0.160156E+11 18476.66   0.244881E+11 18128.59  
Maximum of Months 0.190310E+11 18476.66   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321285E+12    
Minimum of Months 0.160156E+11 18476.66   0.244880E+11 18128.52  
Maximum of Months 0.190310E+11 18476.66   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321285E+12    
Minimum of Months 0.160156E+11 18476.66   0.244880E+11 18128.52  
Maximum of Months 0.190310E+11 18476.66   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554336E+10 5800.91 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.502824E+10 5800.91 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.597494E+10 5800.91 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.533685E+10 5800.91 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.575915E+10 5800.91 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.573131E+10 5800.91 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.536469E+10 5800.91 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.597494E+10 5800.91 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.533685E+10 5800.91 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.554336E+10 5800.91 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.547839E+10 5800.91 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.536469E+10 5800.91 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.664368E+11     0.749486E+13    
Minimum of Months 0.502824E+10 5800.91   0.246344E+12 94908.13  
Maximum of Months 0.597494E+10 5800.91   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.196603E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.178333E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.189279E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.204256E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.203269E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.190266E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.189279E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.196603E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.194299E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.190266E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.235627E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.178333E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.154238E+10
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.123675E+10
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.112890E+10
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.819604E+09
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 1854467.83 0.803399E+09
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 9420242.08 0.396890E+09
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 32740590.35 0.259296E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 27325766.70 0.285114E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 18051397.25 0.529134E+09
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 109081.56 0.798337E+09
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.113097E+10
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.143569E+10
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 89501545.77 0.103665E+11
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.259296E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 32740590.35 0.154238E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.102533E+10
February 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.822439E+09
March 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.741321E+09
April 0.936002E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.533368E+09
May 0.101394E+10 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 1394641.85 0.523945E+09
June 0.101113E+10 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 6684409.60 0.256805E+09
July 0.938820E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 23221878.45 0.161825E+09
August 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 19066931.01 0.173486E+09
September 0.936002E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 12553946.64 0.347676E+09
October 0.973041E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 90902.65 0.524359E+09
November 0.963541E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.734713E+09
December 0.938820E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.936597E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 63012710.21 0.678187E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.161825E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 23221878.45 0.102533E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.155106E+10
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.126680E+10
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.113277E+10
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.814162E+09
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 1885520.62 0.787879E+09
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 9561963.11 0.388398E+09
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 32044062.68 0.251602E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 26900298.78 0.279978E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 15687212.83 0.535970E+09
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 94381.94 0.815574E+09
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.113246E+10
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.143600E+10
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 86173439.96 0.103926E+11
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.251602E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 32044062.68 0.155106E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.105579E+10
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.878442E+09
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.803203E+09
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.604220E+09
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 1217288.13 0.565001E+09
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 6056602.58 0.284555E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 20216424.51 0.192765E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 17353555.72 0.210780E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 12097021.72 0.369451E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 74265.41 0.570913E+09
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.810242E+09
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.103821E+10
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 57015158.07 0.738357E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.192765E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 20216424.51 0.105579E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.328820E+10
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.253420E+10
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.235648E+10
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.169578E+10
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 4083229.93 0.171907E+10
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 22134128.29 0.885555E+09
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 78383148.18 0.596361E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 63791678.86 0.650928E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 42684371.06 0.113722E+10
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 1825527.10 0.161856E+10
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.228964E+10
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.288324E+10
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.212902E+09 0.216552E+11
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.596361E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 78383148.18 0.328820E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.221340E+10
February 0.649041E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.172892E+10
March 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.159892E+10
April 0.688021E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.116130E+10
May 0.744847E+09 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 2965910.29 0.114130E+10
June 0.742030E+09 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 15137121.12 0.593206E+09
July 0.690839E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 52001394.41 0.403860E+09
August 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 42683122.04 0.432922E+09
September 0.688021E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 28230239.15 0.767451E+09
October 0.715730E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 626170.24 0.110417E+10
November 0.708685E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.153617E+10
December 0.690839E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.193778E+10
                   
Annual Sum or Average 0.858171E+10 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.141644E+09 0.146194E+11
Minimum of Months 0.649041E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.403860E+09
Maximum of Months 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 52001394.41 0.221340E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.345515E+10
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.279275E+10
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.251312E+10
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.180354E+10
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 4056715.99 0.174980E+10
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 21732648.94 0.883897E+09
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 73356216.77 0.603702E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 61595577.33 0.672099E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 34813071.04 0.121080E+10
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 119094.76 0.181125E+10
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.246809E+10
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.307349E+10
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.195673E+09 0.230377E+11
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.603702E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 73356216.77 0.345515E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.223587E+10
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.176218E+10
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.162392E+10
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.119770E+10
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 2777181.70 0.120040E+10
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 14242672.67 0.613302E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 50823086.64 0.429561E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 41985402.21 0.451007E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 29451857.66 0.779373E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 607724.24 0.112285E+10
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.157048E+10
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.197250E+10
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.139888E+09 0.149591E+11
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.429561E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 50823086.64 0.223587E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.396250E+10
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.293359E+10
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.274372E+10
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.191595E+10
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 5050395.47 0.199318E+10
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 26868750.87 0.105667E+10
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 96989333.83 0.716388E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 78040325.16 0.774622E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 53634249.18 0.130562E+10
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 6400007.47 0.176991E+10
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.261788E+10
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.344146E+10
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.266983E+09 0.252315E+11
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.716388E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 96989333.83 0.396250E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.266114E+10
February 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.199760E+10
March 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.187197E+10
April 0.936002E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.133879E+10
May 0.101394E+10 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 3458441.29 0.134647E+10
June 0.101113E+10 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 17700151.90 0.724690E+09
July 0.938820E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 60520391.40 0.499804E+09
August 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 50854148.82 0.532016E+09
September 0.936002E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 32501767.24 0.908324E+09
October 0.973041E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 1639019.00 0.123315E+10
November 0.963541E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.176387E+10
December 0.938820E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.230536E+10
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 0.166674E+09 0.171832E+11
Minimum of Months 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.499804E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 60520391.40 0.266114E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.408325E+10
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.320410E+10
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.293316E+10
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.207136E+10
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 4826555.77 0.205284E+10
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 25888367.46 0.106715E+10
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 88414450.01 0.736272E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 74425278.40 0.816735E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 41603567.09 0.142604E+10
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 206200.93 0.204171E+10
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.280697E+10
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.357788E+10
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.235364E+09 0.268175E+11
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.736272E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 88414450.01 0.408325E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.267889E+10
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.205138E+10
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.191387E+10
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.138900E+10
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 3329438.84 0.141700E+10
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 17139986.99 0.743411E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 62097252.59 0.525601E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 51264543.42 0.549080E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 35726599.10 0.920583E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 1524582.71 0.127402E+10
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.181778E+10
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.234212E+10
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 0.171082E+09 0.176227E+11
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.525601E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 62097252.59 0.267889E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.554336E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.502824E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.597494E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.533685E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.575915E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.573131E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.536469E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.597494E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.533685E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.554336E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.547839E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.536469E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.664368E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.502824E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.597494E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328645E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.264459E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.238712E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.172711E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2893834.87 0.168010E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15241865.63 0.828158E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58675239.36 0.551565E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49733686.49 0.612285E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33302808.80 0.112566E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64615.68 0.169890E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.241341E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.307062E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.159912E+09 0.220260E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.551565E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58675239.36 0.328645E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.552928E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.440084E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.404938E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.293554E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5366670.93 0.290569E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27920476.65 0.145362E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109223E+09 0.976204E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90643953.52 0.108438E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61619363.60 0.196451E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161983.64 0.287429E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.403188E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.502938E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.294936E+09 0.372350E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.976204E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109223E+09 0.552928E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.580060E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.451159E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.426672E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.308392E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3352676.39 0.315981E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23046136.83 0.166100E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94520697.95 0.112681E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85434899.21 0.122566E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52758139.21 0.210896E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.289250E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.404803E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.511607E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.259113E+09 0.390017E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112681E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94520697.95 0.580060E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20573.73 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20573.73 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20573.73 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20573.73 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20573.73 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20573.73 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20573.73 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20573.73 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20573.73 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20573.73 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20573.73 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20573.73 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20573.73   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20573.73   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2513.75 05-JAN-22:01
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1593.39 17-FEB-04:00
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1934.99 02-MAR-23:00
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1389.75 27-APR-02:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 112.29 20-MAY-17:02 2620.83 22-MAY-04:20
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1115.14 14-JUN-02:00
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 278.92 30-JUL-12:00 668.70 05-JUL-01:00
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 323.47 06-AUG-17:26 859.97 23-AUG-03:00
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 414.76 03-SEP-12:52 1483.19 12-SEP-03:00
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 11.99 18-OCT-14:00 1266.41 30-OCT-22:00
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1508.63 26-NOV-19:53
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2355.15 01-DEC-04:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.00   668.70  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 414.76   2620.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1675.25 05-JAN-22:01
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1041.94 17-FEB-04:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1262.10 02-MAR-23:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 907.56 27-APR-02:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 92.55 20-MAY-17:02 1718.20 22-MAY-04:20
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 96.23 24-JUN-17:10 722.01 14-JUN-02:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 207.60 30-JUL-11:50 430.16 05-JUL-01:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 246.19 06-AUG-17:30 551.42 23-AUG-03:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 287.20 03-SEP-12:52 969.61 12-SEP-03:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 16.10 15-OCT-14:00 824.81 30-OCT-22:10
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1003.94 28-NOV-05:58
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1519.05 01-DEC-04:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 0.00   430.16  
Maximum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 287.20   1718.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2512.63 05-JAN-22:01
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1568.44 17-FEB-04:00
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1961.72 02-MAR-23:00
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1372.55 27-APR-02:00
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 119.92 20-MAY-17:02 2534.41 22-MAY-04:20
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 127.69 29-JUN-15:00 1092.41 14-JUN-02:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 282.11 30-JUL-11:50 653.79 05-JUL-01:00
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 337.15 06-AUG-17:26 856.13 23-AUG-03:00
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 351.25 03-SEP-12:55 1439.99 12-SEP-03:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 11.85 18-OCT-14:50 1283.86 30-OCT-22:00
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1505.88 28-NOV-05:58
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2271.76 01-DEC-04:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.00   653.79  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 351.25   2534.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1677.40 05-JAN-22:01
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1130.57 17-FEB-04:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1374.00 02-MAR-23:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1013.78 27-APR-02:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 75.39 20-MAY-17:02 1766.68 22-MAY-04:20
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 85.13 29-JUN-15:00 807.55 14-JUN-02:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 217.29 30-JUL-11:50 500.39 05-JUL-01:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 215.68 06-AUG-12:05 669.21 23-AUG-03:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 307.55 03-SEP-12:52 1019.23 12-SEP-03:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 7.99 18-OCT-14:00 898.71 30-OCT-22:50
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1068.09 26-NOV-19:53
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1713.34 01-DEC-04:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.00   500.39  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 307.55   1766.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5882.82 05-JAN-22:01
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3237.96 08-FEB-22:02
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4135.10 02-MAR-23:00
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2929.09 27-APR-02:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 263.81 20-MAY-17:02 5691.68 22-MAY-05:00
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2351.22 14-JUN-02:00
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 674.43 30-JUL-12:00 1405.33 05-JUL-01:00
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 753.98 06-AUG-17:50 1747.21 23-AUG-03:00
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 941.27 03-SEP-13:00 3051.41 12-SEP-03:00
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 218.96 15-OCT-14:10 2601.28 30-OCT-22:00
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3529.09 28-NOV-05:49
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5043.15 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.00   1405.33  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 941.27   5882.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3921.35 05-JAN-22:01
February 1239.33 01-FEB-08:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2157.95 08-FEB-22:02
March 1239.33 01-MAR-08:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2742.85 02-MAR-23:00
April 1239.33 03-APR-07:10 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1948.84 27-APR-02:00
May 1239.33 01-MAY-07:10 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 218.04 20-MAY-17:02 3794.45 22-MAY-04:53
June 1239.33 01-JUN-07:10 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 214.84 24-JUN-17:10 1532.51 14-JUN-02:00
July 1239.33 03-JUL-07:10 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 468.23 30-JUL-11:50 932.72 05-JUL-01:00
August 1239.33 01-AUG-07:10 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 563.85 06-AUG-17:30 1159.27 23-AUG-03:00
September 1239.33 01-SEP-07:10 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 641.26 03-SEP-12:52 1988.70 12-SEP-03:00
October 1239.33 02-OCT-07:10 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 101.60 15-OCT-14:10 1729.26 30-OCT-22:00
November 1239.33 01-NOV-07:10 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2352.68 28-NOV-05:41
December 1239.33 01-DEC-08:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.16 01-DEC-05:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   1495.05   1466.95   0.00 0.00 0.00 0.00 0.00   932.72  
Maximum of Months 1239.33   1495.05   1466.95   0.00 0.00 0.00 0.00 641.26   3921.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5884.69 05-JAN-22:01
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3391.38 19-FEB-13:00
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4306.44 02-MAR-23:00
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2958.47 27-APR-02:00
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 278.53 20-MAY-17:02 5691.75 22-MAY-05:00
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 295.49 29-JUN-15:00 2327.04 14-JUN-02:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 644.10 30-JUL-12:00 1416.97 05-JUL-01:00
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 782.42 06-AUG-17:26 1791.39 23-AUG-03:00
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 810.14 03-SEP-13:00 3028.29 12-SEP-03:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 20.33 18-OCT-15:10 2774.94 30-OCT-22:00
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3529.09 28-NOV-05:46
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5043.34 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.00   1416.97  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 810.14   5884.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3922.08 05-JAN-22:01
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2163.22 17-FEB-05:45
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2833.13 02-MAR-23:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1976.49 27-APR-02:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 192.67 20-MAY-17:02 3794.51 22-MAY-04:57
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 196.99 29-JUN-15:00 1592.21 14-JUN-02:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 568.68 30-JUL-11:50 999.24 05-JUL-01:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 566.28 06-AUG-12:10 1205.86 23-AUG-03:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 705.56 03-SEP-12:55 1992.87 12-SEP-03:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 101.30 15-OCT-12:50 1770.75 30-OCT-22:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2352.74 28-NOV-05:41
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3362.90 01-DEC-05:04
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.00   999.24  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 705.56   3922.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7293.61 05-JAN-22:01
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4018.47 17-FEB-05:45
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4957.92 17-MAR-04:47
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3338.70 27-APR-02:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 324.52 20-MAY-17:02 7101.79 22-MAY-04:50
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 361.93 29-JUN-15:00 2703.20 14-JUN-02:00
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 879.93 30-JUL-12:00 1616.64 05-JUL-01:00
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 948.44 06-AUG-17:40 2003.75 22-AUG-21:10
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 1184.15 03-SEP-13:00 3332.71 12-SEP-03:00
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 484.05 15-OCT-14:00 3160.98 30-OCT-21:03
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4283.71 28-NOV-05:50
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6098.05 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.00   1616.64  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 1184.15   7293.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4861.63 05-JAN-22:01
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2679.19 17-FEB-05:47
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3305.41 17-MAR-04:50
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2245.55 27-APR-02:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 248.00 20-MAY-17:02 4734.95 22-MAY-04:47
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 241.28 29-JUN-15:00 1849.60 04-JUN-14:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 568.76 30-JUL-14:40 1081.60 05-JUL-01:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 700.58 06-AUG-17:40 1327.06 22-AUG-24:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 804.80 03-SEP-13:00 2195.73 12-SEP-03:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 207.22 15-OCT-13:50 2110.71 30-OCT-21:03
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2948.79 28-NOV-05:58
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.72 01-DEC-05:06
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 0.00   1081.60  
Maximum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 804.80   4861.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7296.80 05-JAN-22:01
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4030.20 08-FEB-22:02
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5099.11 02-MAR-23:00
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3397.16 27-APR-02:00
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 324.41 20-MAY-17:02 7102.51 22-MAY-04:47
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 361.93 29-JUN-15:00 2677.58 14-JUN-02:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 800.84 30-JUL-12:00 1640.61 05-JUL-01:00
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 973.89 06-AUG-17:38 2063.31 22-AUG-21:10
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 991.80 03-SEP-12:55 3327.15 12-SEP-03:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 27.03 18-OCT-14:40 3215.57 30-OCT-21:03
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4423.08 28-NOV-06:00
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6297.80 01-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.00   1640.61  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 991.80   7296.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4863.11 05-JAN-22:01
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2683.13 08-FEB-22:02
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3368.76 02-MAR-23:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2279.04 27-APR-02:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 226.80 20-MAY-17:02 4735.04 22-MAY-04:47
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 241.29 29-JUN-15:00 1838.30 14-JUN-02:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 731.26 30-JUL-12:00 1171.32 05-JUL-01:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 722.16 06-AUG-11:52 1387.42 22-AUG-24:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 899.26 03-SEP-13:00 2215.49 12-SEP-03:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 195.72 15-OCT-12:31 2125.15 30-OCT-21:03
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2948.78 28-NOV-05:55
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4198.47 01-DEC-05:09
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.00   1171.32  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 899.26   4863.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5800.91 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5800.91 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5800.91 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5800.91 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5800.91 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5800.91 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5800.91 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5800.91 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5800.91 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5800.91 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5800.91 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5800.91 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5800.91   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5800.91   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 5188.83 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3467.82 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4108.49 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2933.59 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.48 20-MAY-17:02 5822.53 22-MAY-03:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 232.10 29-JUN-15:00 2330.29 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 578.24 30-JUL-12:00 1368.65 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 655.67 06-AUG-17:51 1786.53 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 798.26 03-SEP-13:00 3188.42 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.53 18-OCT-15:00 2697.00 30-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3282.41 26-NOV-19:53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5141.14 01-DEC-04:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1368.65  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 798.26   5822.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 9180.22 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5870.37 17-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7163.07 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5106.59 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 417.60 20-MAY-17:02 10067.11 22-MAY-04:01
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 415.01 29-JUN-15:00 4056.10 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1085.94 30-JUL-12:00 2374.68 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1231.51 06-AUG-17:51 3075.49 23-AUG-03:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1419.34 03-SEP-13:00 5541.81 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.92 18-OCT-14:00 4605.03 30-OCT-22:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5445.33 26-NOV-20:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8325.36 01-DEC-04:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2374.68  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1419.34   10067.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 10273.79 05-JAN-22:01
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5792.53 08-FEB-22:02
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7777.72 02-MAR-23:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5341.41 27-APR-02:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 375.68 20-MAY-17:02 10116.73 22-MAY-04:10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 430.92 29-JUN-15:00 4197.33 14-JUN-02:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1014.02 30-JUL-11:55 2529.61 05-JUL-01:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1131.56 06-AUG-18:00 3182.35 22-AUG-21:03
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1310.21 03-SEP-13:00 5453.88 12-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4870.46 30-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 5747.60 29-NOV-22:02
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 8276.38 01-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2529.61  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1310.21   10273.79  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 111728.48 02-JAN-04:11 0.00 9144.45 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 111032.38 21-FEB-04:01 0.00 8001.39 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 108843.47 20-MAR-03:01 0.00 8001.39 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
April 110281.74 24-APR-03:02 0.00 6858.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 112411.30 30-MAY-03:02 0.00 6858.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 112888.39 05-JUN-03:02 0.00 6858.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
July 111648.41 05-JUL-03:02 0.00 6858.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 112338.43 14-AUG-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 112864.53 11-SEP-03:02 0.00 6858.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 112117.63 30-OCT-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 112007.94 20-NOV-04:01 0.00 8001.39 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
December 111379.76 26-DEC-04:01 0.00 11430.56 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 108843.47   0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 112888.39   0.00 11430.56 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 85689.76 02-JAN-06:02 8061.19 10264.30 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
February 86823.56 28-FEB-05:01 0.00 16422.89 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
March 88639.44 20-MAR-04:02 0.00 20528.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00
April 90943.46 10-APR-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 93872.97 30-MAY-03:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
June 91751.84 05-JUN-03:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
July 94681.66 05-JUL-03:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
August 90441.61 23-AUG-03:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
September 94871.92 11-SEP-03:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
October 90205.02 02-OCT-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 90980.79 06-NOV-04:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 87296.87 07-DEC-05:01 0.00 16422.89 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 85689.76   0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 94871.92   8061.19 20528.61 80571.51 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22299.46 05-JAN-17:00 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 60797.01 28-FEB-06:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 72700.29 30-MAR-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 78454.85 08-APR-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 81791.04 30-MAY-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
June 82437.06 23-JUN-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 83308.83 19-JUL-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
August 85315.68 14-AUG-03:02 0.00 5132.72 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 84391.47 11-SEP-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 78644.19 18-OCT-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 73361.53 08-NOV-06:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 29153.64 07-DEC-16:30 30632.53 36953.32 36257.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 22299.46   0.00 5132.72 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 85315.68   30632.53 36953.32 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16185.38 13-JAN-17:00 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 26421.68 28-FEB-17:00 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 29807.03 23-MAR-15:30 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
April 43890.06 26-APR-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 76928.28 20-MAY-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 82481.49 21-JUN-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 81572.57 19-JUL-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
August 80738.99 07-AUG-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
September 82193.83 05-SEP-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 51582.25 19-OCT-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 28208.22 03-NOV-16:00 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 20190.61 06-DEC-17:00 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16185.38   0.00 6159.27 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 82481.49   15316.26 18476.66 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3154.18 02-JAN-06:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 84.36
February 4506.20 27-FEB-16:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 46.22
March 4953.60 27-MAR-14:40 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 96.41
April 7392.64 07-APR-14:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 23.97
May 12755.73 30-MAY-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 78.16
June 12610.63 26-JUN-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 72.40
July 12918.87 03-JUL-05:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 55.20
August 16290.43 06-AUG-16:01 1012.16 1288.93 7587.73 0.00 0.00 0.00 0.00 257.92 0.00
September 15637.02 04-SEP-16:51 910.95 1160.04 6828.95 0.00 0.00 0.00 0.00 95.42 0.00
October 6267.99 19-OCT-14:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 29.32
November 4507.07 24-NOV-14:30 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 166.86
December 3194.97 06-DEC-05:01 0.00 2062.06 8093.57 0.00 0.00 0.00 0.00 0.00 833.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3154.18   0.00 1031.03 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16290.43   2010.79 2319.93 8093.57 0.00 0.00 0.00 0.00 257.92 833.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3756.16 02-JAN-06:02 652.28 830.54 3259.88 0.00 0.00 0.00 0.00 0.00 55.33
February 6709.06 27-FEB-10:00 2478.65 2990.10 2933.89 0.00 0.00 0.00 0.00 0.00 103.07
March 9365.63 28-MAR-09:20 2591.66 2990.10 2933.89 0.00 0.00 0.00 0.00 0.00 133.10
April 11614.20 24-APR-08:30 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 35.17
May 11810.37 19-MAY-08:30 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 32.73
June 21305.67 25-JUN-07:52 391.37 498.38 2933.89 0.00 0.00 0.00 0.00 0.00 135.72
July 22480.31 02-JUL-07:51 456.59 581.44 3422.87 0.00 0.00 0.00 0.00 0.00 189.67
August 23097.67 06-AUG-08:41 587.05 747.57 4400.84 0.00 0.00 0.00 0.00 0.00 38.84
September 21429.73 04-SEP-08:52 391.37 498.38 2933.89 0.00 0.00 0.00 0.00 0.00 22.38
October 8933.72 18-OCT-09:20 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 60.01
November 6190.08 06-NOV-09:35 2478.65 2990.10 2933.89 0.00 0.00 0.00 0.00 0.00 54.71
December 3583.64 06-DEC-05:01 0.00 1328.87 5215.81 0.00 0.00 0.00 0.00 0.00 523.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3583.64   0.00 498.38 1466.95 0.00 0.00 0.00 0.00 0.00 22.38
Maximum of Months 23097.67   2591.66 2990.10 5215.81 0.00 0.00 0.00 0.00 0.00 523.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12048.22 19-JAN-13:30 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 231.04
February 25691.50 26-FEB-13:22 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 473.69
March 19413.40 01-MAR-13:40 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 125.43
April 19309.22 16-APR-12:02 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 431.64
May 15395.07 19-MAY-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 33.90 0.00
June 16211.72 25-JUN-15:12 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 49.27
July 25863.69 02-JUL-14:32 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 87.46
August 27271.99 06-AUG-16:01 1012.19 1288.96 7587.84 0.00 0.00 0.00 0.00 228.39 0.00
September 27749.97 03-SEP-13:11 910.97 1160.06 6829.06 0.00 0.00 0.00 0.00 245.79 0.00
October 28482.31 15-OCT-12:31 708.53 902.27 5311.49 0.00 0.00 0.00 0.00 0.00 420.40
November 19300.92 03-NOV-13:20 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 100.02
December 13777.73 12-DEC-12:30 1058.33 2319.98 2023.42 0.00 0.00 0.00 0.00 0.00 177.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12048.22   506.09 644.48 2023.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28482.31   2010.83 2319.98 7587.84 0.00 0.00 0.00 0.00 245.79 473.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4895.51 02-JAN-05:01 0.00 1328.87 5215.77 0.00 0.00 0.00 0.00 0.00 36.50
February 10319.47 28-FEB-16:40 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 66.32
March 12863.35 28-MAR-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 136.13
April 25904.11 16-APR-17:22 0.00 498.38 2933.87 0.00 0.00 0.00 0.00 0.00 152.28
May 25756.48 13-MAY-18:22 0.00 498.38 2933.87 0.00 0.00 0.00 0.00 0.00 125.09
June 25696.33 18-JUN-17:02 0.00 498.38 2933.87 0.00 0.00 0.00 0.00 0.00 16.09
July 30353.99 02-JUL-17:51 0.00 830.63 4889.79 0.00 0.00 0.00 0.00 0.00 55.97
August 30550.80 06-AUG-16:41 652.28 830.63 4889.79 0.00 0.00 0.00 0.00 105.75 0.00
September 28533.36 04-SEP-16:51 587.05 747.57 4400.81 0.00 0.00 0.00 0.00 38.17 0.00
October 20065.31 15-OCT-14:31 456.59 581.44 3422.85 0.00 0.00 0.00 0.00 0.00 147.11
November 9648.80 03-NOV-15:40 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 61.93
December 8907.63 06-DEC-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 214.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4895.51   0.00 498.38 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30550.80   1239.33 1495.05 5215.77 0.00 0.00 0.00 0.00 105.75 214.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1832.99 13-JAN-15:10 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 396.78
February 3059.51 27-FEB-13:40 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 125.05
March 3031.87 23-MAR-13:30 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 554.75
April 5631.47 07-APR-14:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 60.30
May 7688.92 19-MAY-16:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 178.84 0.00
June 11644.03 23-JUN-05:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 146.10
July 10308.00 20-JUL-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 116.47
August 14878.26 06-AUG-16:01 1012.16 1288.93 7587.73 0.00 0.00 0.00 0.00 621.72 0.00
September 10142.98 03-SEP-16:01 708.51 902.25 5311.41 0.00 0.00 0.00 0.00 684.18 0.00
October 4846.05 19-OCT-14:40 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 68.97
November 3011.12 03-NOV-13:30 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 192.56
December 2076.38 06-DEC-15:50 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 617.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1832.99   708.51 902.25 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14878.26   2010.79 2319.93 7587.73 0.00 0.00 0.00 0.00 684.18 617.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2519.26 20-JAN-10:00 2478.65 2990.10 2933.89 0.00 0.00 0.00 0.00 0.00 620.42
February 4566.58 26-FEB-11:52 326.14 415.32 2444.91 0.00 0.00 0.00 0.00 0.00 723.76
March 7339.60 28-MAR-10:05 2478.65 2990.10 2933.89 0.00 0.00 0.00 0.00 0.00 214.50
April 10811.08 24-APR-09:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 82.31
May 12271.44 19-MAY-08:50 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 74.37
June 21090.55 04-JUN-07:42 326.14 415.32 2444.91 0.00 0.00 0.00 0.00 0.00 314.14
July 23370.12 02-JUL-07:41 456.59 581.44 3422.87 0.00 0.00 0.00 0.00 0.00 445.35
August 25062.17 06-AUG-09:21 587.05 747.57 4400.84 0.00 0.00 0.00 0.00 0.00 41.00
September 21403.15 03-SEP-11:21 456.59 581.44 3422.87 0.00 0.00 0.00 0.00 121.25 0.00
October 7535.97 18-OCT-10:10 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 95.83
November 4076.77 03-NOV-13:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 137.64
December 2740.63 07-DEC-11:20 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 175.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2519.26   326.14 415.32 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25062.17   2478.65 2990.10 4400.84 0.00 0.00 0.00 0.00 121.25 723.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11615.32 19-JAN-14:00 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 501.93
February 28028.78 26-FEB-13:12 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 1244.60
March 20448.61 01-MAR-14:00 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 279.44
April 24811.53 16-APR-13:12 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 885.58
May 15805.83 19-MAY-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 76.25 0.00
June 15549.42 30-JUN-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 40.53 0.00
July 25485.55 16-JUL-15:12 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 301.36 0.00
August 27588.52 06-AUG-16:01 1012.19 1288.96 7587.84 0.00 0.00 0.00 0.00 515.14 0.00
September 30660.34 03-SEP-12:41 910.97 1160.06 6829.06 0.00 0.00 0.00 0.00 378.34 0.00
October 27245.48 15-OCT-13:22 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 731.66
November 19832.34 03-NOV-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 231.78
December 11909.96 12-DEC-14:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 465.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11615.32   506.09 644.48 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30660.34   2010.83 2319.98 7587.84 0.00 0.00 0.00 0.00 515.14 1244.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3477.56 13-JAN-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 363.76
February 7175.20 28-FEB-16:40 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 156.78
March 8764.54 28-MAR-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 321.85
April 22853.94 16-APR-17:11 0.00 747.57 4400.81 0.00 0.00 0.00 0.00 0.00 366.41
May 25407.65 28-MAY-18:01 0.00 664.51 3911.83 0.00 0.00 0.00 0.00 0.00 775.16
June 23178.33 18-JUN-17:22 0.00 498.38 2933.87 0.00 0.00 0.00 0.00 0.00 49.09
July 25059.52 16-JUL-17:11 0.00 581.44 3422.85 0.00 0.00 0.00 0.00 110.45 0.00
August 26356.80 06-AUG-16:41 652.28 830.63 4889.79 0.00 0.00 0.00 0.00 281.57 0.00
September 24039.07 03-SEP-16:01 456.59 581.44 3422.85 0.00 0.00 0.00 0.00 368.06 0.00
October 10200.01 16-OCT-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 72.46
November 5566.46 03-NOV-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 147.24
December 3792.19 06-DEC-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 459.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3477.56   0.00 498.38 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26356.80   1239.33 1495.05 4889.79 0.00 0.00 0.00 0.00 368.06 775.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2085.86 14-JAN-17:03 404.87 515.57 3035.09 0.00 0.00 0.00 0.00 0.00 451.14
February 2761.66 27-FEB-13:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 135.68
March 3009.94 23-MAR-13:30 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 658.79
April 5180.85 07-APR-14:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 79.94
May 8364.42 19-MAY-16:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 215.49 0.00
June 11997.29 23-JUN-05:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 183.25
July 16288.60 16-JUL-18:31 0.00 902.25 5311.41 0.00 0.00 0.00 0.00 268.20 0.00
August 13844.14 06-AUG-16:11 708.51 902.25 5311.41 0.00 0.00 0.00 0.00 796.53 0.00
September 8680.26 05-SEP-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 2.16 0.00
October 4328.94 18-OCT-14:20 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 50.25 0.00
November 2775.67 08-NOV-15:30 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 381.17
December 2293.02 06-DEC-16:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 702.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2085.86   0.00 515.57 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16288.60   2010.79 2319.93 5311.41 0.00 0.00 0.00 0.00 796.53 702.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2457.96 13-JAN-06:04 913.19 1162.76 4563.83 0.00 0.00 0.00 0.00 0.00 219.56
February 3372.48 28-FEB-10:40 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 196.35
March 5686.81 23-MAR-10:30 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 675.22
April 9798.22 25-APR-09:40 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 134.71
May 11836.27 19-MAY-09:20 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 99.00
June 22635.34 25-JUN-09:02 391.37 498.38 2933.89 0.00 0.00 0.00 0.00 0.00 296.15
July 22318.50 16-JUL-09:12 391.37 498.38 2933.89 0.00 0.00 0.00 0.00 0.00 281.35
August 22553.57 06-AUG-09:32 391.37 498.38 2933.89 0.00 0.00 0.00 0.00 58.25 0.00
September 16548.09 04-SEP-09:02 326.14 415.32 2444.91 0.00 0.00 0.00 0.00 0.00 13.98
October 6411.26 18-OCT-10:00 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 133.46
November 3307.93 03-NOV-10:00 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 266.94
December 2481.82 09-DEC-06:04 913.19 1162.76 4563.83 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2457.96   326.14 415.32 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22635.34   1295.83 1495.05 4563.83 0.00 0.00 0.00 0.00 58.25 675.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9656.95 31-JAN-13:40 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 853.90
February 27512.63 26-FEB-14:21 708.53 902.27 5311.49 0.00 0.00 0.00 0.00 0.00 1178.31
March 18718.32 01-MAR-14:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 348.88
April 17679.10 25-APR-13:40 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 147.43
May 16380.47 19-MAY-13:50 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 112.92 0.00
June 19277.38 25-JUN-15:02 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 144.02
July 27848.79 16-JUL-13:52 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 210.48 0.00
August 28943.26 06-AUG-13:32 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 585.99 0.00
September 30587.20 03-SEP-13:31 708.53 902.27 5311.49 0.00 0.00 0.00 0.00 573.05 0.00
October 29486.48 15-OCT-15:02 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 0.00 943.13
November 18101.60 03-NOV-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 291.01
December 9396.43 06-DEC-14:40 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 1018.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9396.43   506.09 644.48 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30587.20   2010.83 2319.98 5311.49 0.00 0.00 0.00 0.00 585.99 1178.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3477.46 13-JAN-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 440.97
February 6563.70 28-FEB-16:40 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 196.20
March 8310.56 28-MAR-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 402.83
April 18279.34 16-APR-17:11 0.00 747.57 4400.81 0.00 0.00 0.00 0.00 0.00 443.22
May 26835.91 28-MAY-18:01 0.00 664.51 3911.83 0.00 0.00 0.00 0.00 0.00 959.48
June 24627.15 18-JUN-17:22 0.00 498.38 2933.87 0.00 0.00 0.00 0.00 0.00 64.25
July 27584.86 09-JUL-16:41 521.82 664.51 3911.83 0.00 0.00 0.00 0.00 0.00 57.39
August 25648.46 06-AUG-16:11 456.59 581.44 3422.85 0.00 0.00 0.00 0.00 448.94 0.00
September 25575.92 04-SEP-17:01 0.00 581.44 3422.85 0.00 0.00 0.00 0.00 135.43 0.00
October 9988.47 18-OCT-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 4.27 0.00
November 4821.57 03-NOV-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 184.85
December 3781.48 06-DEC-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 555.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3477.46   0.00 498.38 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27584.86   1239.33 1495.05 4400.81 0.00 0.00 0.00 0.00 448.94 959.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7725.21 06-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2596.25
February 5665.94 28-FEB-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.95
March 5312.50 04-MAR-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 458.08
April 6048.70 25-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 230.95
May 9818.21 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 173.13
June 8937.68 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.52
July 10514.54 31-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.61
August 11554.42 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.76
September 14003.90 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.27
October 5711.03 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 358.96
November 6122.83 06-NOV-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 229.56
December 4409.69 09-DEC-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4409.69   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14003.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2596.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10393.84 06-JAN-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5994.79
February 9283.22 04-FEB-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2938.96
March 11251.97 04-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3166.96
April 6537.90 29-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3276.42
May 6861.90 08-MAY-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4216.81
June 6922.24 22-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 108.32
July 8085.29 17-JUL-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.98 0.00
August 8196.27 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.96 0.00
September 7925.50 05-SEP-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.82
October 6097.50 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2712.17
November 8875.89 27-NOV-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5033.58
December 8195.77 29-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6097.50   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11251.97   0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.98 5994.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 106.65 14-JAN-17:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 675.89
February 2356.28 26-FEB-15:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 812.23
March 4722.57 23-MAR-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1181.54
April 11197.31 25-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 185.41
May 16794.04 19-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.10 0.00
June 19593.51 23-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94.11 0.00
July 23043.35 17-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.58 0.00
August 20548.87 07-AUG-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.78 0.00
September 15101.18 05-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.98
October 8736.54 18-OCT-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.45
November 2174.14 03-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 406.98
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5166.44
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23043.35   0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.10 5166.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1980.93 19-JAN-16:50 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4315.35 28-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6834.60 31-MAR-24:00 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8241.22 22-APR-18:10 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3506.71 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5359.07 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7239.20 31-JUL-23:35 0.00 42.40 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8218.20 29-AUG-17:50 23.38 127.19 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3316.17 30-SEP-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4965.71 31-OCT-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6077.34 13-NOV-16:20 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7853.15 06-DEC-16:10 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1980.93   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8241.22   222.14 381.58 15588.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1617.99 19-JAN-16:50 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3943.24 28-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5924.91 31-MAR-23:30 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7806.77 25-APR-18:10 23.38 127.19 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3309.65 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5241.94 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7067.02 31-JUL-23:55 0.00 84.79 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7836.85 03-AUG-18:50 23.38 127.19 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2886.21 30-SEP-23:40 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4161.96 31-OCT-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5550.58 03-NOV-16:00 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7146.80 06-DEC-16:20 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1617.99   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7836.85   222.14 381.58 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1412.43 13-JAN-16:30 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3888.33 28-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5844.66 28-MAR-17:50 23.38 127.19 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7859.35 25-APR-18:10 23.38 127.19 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3227.06 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5241.29 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7015.60 31-JUL-23:55 0.00 84.79 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7952.55 03-AUG-18:40 23.38 127.19 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2786.97 04-SEP-17:32 0.00 190.79 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
October 4034.26 18-OCT-17:00 70.15 211.99 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5476.74 03-NOV-16:00 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7048.30 06-DEC-16:20 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1412.43   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7952.55   222.14 381.58 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91682.57 02-JAN-17:00 4808.68 5800.91 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183625.07 28-FEB-17:00 4808.68 5800.91 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357618.64 31-MAR-24:00 0.00 322.29 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367084.58 26-APR-16:00 4808.68 5800.91 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 176046.09 31-MAY-24:00 0.00 322.29 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267987.34 30-JUN-24:00 0.00 322.29 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359225.79 31-JUL-23:12 0.00 1611.46 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
August 369521.79 22-AUG-07:20 9617.36 11601.83 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
September 175720.50 30-SEP-24:00 0.00 322.29 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267723.28 31-OCT-24:00 0.00 322.29 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276676.74 06-NOV-16:55 9617.36 11601.83 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
December 367838.30 06-DEC-17:00 4808.68 5800.91 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91682.57   0.00 322.29 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369521.79   9617.36 11601.83 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.176838E+13 1113276.43 02-JAN-08:09 0.173971E+13 3042043.47 09-JAN-07:10
February 0.198947E+13 1363330.19 27-FEB-16:10 0.103887E+13 2340260.84 01-FEB-07:10
March 0.266949E+13 1447490.94 28-MAR-15:50 0.754080E+12 2302913.94 06-MAR-07:10
April 0.300198E+13 1782389.44 06-APR-15:00 0.315255E+12 1143646.88 29-APR-06:10
May 0.188895E+13 1529519.66 19-MAY-15:30 0.235302E+12 1064991.78 08-MAY-06:10
June 0.245720E+13 1752179.15 29-JUN-15:09 0.824924E+11 511973.26 16-JUN-06:10
July 0.305227E+13 2006149.26 17-JUL-15:20 0.656361E+11 105938.40 08-JUL-06:19
August 0.350995E+13 2144185.78 07-AUG-15:30 0.724799E+11 279234.32 18-AUG-06:10
September 0.191734E+13 1609669.35 07-SEP-15:09 0.121451E+12 665811.43 19-SEP-06:10
October 0.228516E+13 1567254.23 18-OCT-15:00 0.256086E+12 1202289.70 10-OCT-06:10
November 0.258640E+13 1542905.79 17-NOV-16:00 0.599248E+12 1913728.51 27-NOV-07:10
December 0.303049E+13 1595432.88 19-DEC-08:09 0.123939E+13 2413501.45 29-DEC-07:10
             
Annual Sum or Average 0.301571E+14     0.652000E+13    
Minimum of Months 0.176838E+13 1113276.43   0.656361E+11 105938.40  
Maximum of Months 0.350995E+13 2144185.78   0.173971E+13 3042043.47  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.328950E+12 0.979791E+11 0.811612E+12 0.169596E+12 0.198797E+12 0.163744E+11 0.00 0.955004E+11 0.852750E+10 0.410448E+11 0.00 0.00 0.00
February 0.298382E+12 0.809468E+11 0.102011E+13 0.153195E+12 0.180072E+12 0.147538E+11 0.00 0.159078E+12 0.215281E+11 0.614094E+11 0.00 0.00 0.00
March 0.354561E+12 0.790466E+11 0.146267E+13 0.169879E+12 0.209835E+12 0.141554E+11 0.00 0.247903E+12 0.388872E+11 0.925541E+11 0.00 0.00 0.00
April 0.316695E+12 0.658146E+11 0.170311E+13 0.164100E+12 0.210527E+12 0.218776E+11 0.00 0.325372E+12 0.831352E+11 0.111350E+12 0.00 0.00 0.00
May 0.341755E+12 0.585249E+11 0.820521E+12 0.169738E+12 0.227583E+12 0.338039E+11 0.00 0.145991E+12 0.540175E+11 0.370179E+11 0.00 0.00 0.00
June 0.340103E+12 0.516843E+11 0.110677E+13 0.164363E+12 0.269904E+12 0.619713E+11 0.00 0.302288E+12 0.110746E+12 0.493680E+11 0.00 0.00 0.00
July 0.318348E+12 0.556920E+11 0.143888E+13 0.169473E+12 0.296912E+12 0.858682E+11 0.00 0.488812E+12 0.143431E+12 0.548624E+11 0.00 0.00 0.00
August 0.354561E+12 0.637417E+11 0.177780E+13 0.169879E+12 0.295907E+12 0.813128E+11 0.00 0.540240E+12 0.140168E+12 0.863396E+11 0.00 0.00 0.00
September 0.316695E+12 0.718260E+11 0.784732E+12 0.164097E+12 0.235020E+12 0.482637E+11 0.00 0.184526E+12 0.806450E+11 0.315373E+11 0.00 0.00 0.00
October 0.328950E+12 0.851963E+11 0.112899E+13 0.169597E+12 0.216495E+12 0.262262E+11 0.00 0.203806E+12 0.615301E+11 0.643691E+11 0.00 0.00 0.00
November 0.325095E+12 0.921059E+11 0.140306E+13 0.164207E+12 0.198153E+12 0.158074E+11 0.00 0.243455E+12 0.527406E+11 0.917708E+11 0.00 0.00 0.00
December 0.318348E+12 0.100708E+12 0.175516E+13 0.169471E+12 0.199460E+12 0.145751E+11 0.00 0.310508E+12 0.425046E+11 0.119755E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.394244E+13 0.903267E+12 0.152134E+14 0.199759E+13 0.273866E+13 0.434990E+12 0.00 0.324748E+13 0.837861E+12 0.841378E+12 0.00 0.00 0.00
Minimum of Months 0.298382E+12 0.516843E+11 0.784732E+12 0.153195E+12 0.180072E+12 0.141554E+11 0.00 0.955004E+11 0.852750E+10 0.315373E+11 0.00 0.00 0.00
Maximum of Months 0.354561E+12 0.100708E+12 0.177780E+13 0.169879E+12 0.296912E+12 0.858682E+11 0.00 0.540240E+12 0.143431E+12 0.119755E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.166355E+13 0.00 0.761577E+11 0.00 0.00
February 0.00 0.00 0.968957E+12 0.00 0.699122E+11 0.00 0.00
March 0.00 0.00 0.673885E+12 0.00 0.801945E+11 0.00 0.00
April 0.00 0.00 0.243036E+12 0.00 0.722192E+11 0.00 0.00
May 0.00 0.00 0.161868E+12 0.00 0.734345E+11 0.00 0.00
June 0.00 0.00 0.133383E+11 0.00 0.691541E+11 0.00 0.00
July 0.00 0.00 0.308018E+09 0.00 0.653281E+11 0.00 0.00
August 0.00 0.00 0.417565E+10 0.00 0.683043E+11 0.00 0.00
September 0.00 0.00 0.575377E+11 0.00 0.639129E+11 0.00 0.00
October 0.00 0.00 0.188108E+12 0.00 0.679785E+11 0.00 0.00
November 0.00 0.00 0.530051E+12 0.00 0.691965E+11 0.00 0.00
December 0.00 0.00 0.116679E+13 0.00 0.725989E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.567161E+13 0.00 0.848392E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.308018E+09 0.00 0.639129E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.166355E+13 0.00 0.801945E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 344233.60 02-JAN-08:09 57580.60 01-JAN-00:10 439129.89 02-JAN-08:09 120520.01 02-JAN-08:20 114844.93 09-JAN-06:10 36632.14 25-JAN-06:10 0.00 01-JAN-00:10
February 344233.60 01-FEB-08:09 57580.60 01-FEB-00:10 557421.28 01-FEB-08:09 120520.01 01-FEB-08:20 158353.69 28-FEB-16:10 39773.61 27-FEB-13:39 0.00 01-FEB-00:10
March 344233.60 01-MAR-08:09 57580.60 01-MAR-00:10 675712.68 01-MAR-08:09 120520.01 01-MAR-08:20 168692.31 28-MAR-15:50 36560.51 07-MAR-19:49 0.00 01-MAR-00:10
April 344233.60 03-APR-07:10 57580.60 01-APR-00:10 794004.08 03-APR-07:10 120520.01 03-APR-07:19 226197.61 25-APR-15:30 57939.15 06-APR-14:20 0.00 01-APR-00:10
May 344233.60 01-MAY-07:10 57580.60 01-MAY-00:10 439129.89 01-MAY-07:10 120520.01 01-MAY-07:19 263225.71 19-MAY-15:30 64654.33 19-MAY-15:00 0.00 01-MAY-00:10
June 344233.60 01-JUN-07:10 57580.60 01-JUN-00:10 557421.28 01-JUN-07:10 120520.01 01-JUN-07:19 292601.52 29-JUN-14:30 65283.71 23-JUN-13:00 0.00 01-JUN-00:10
July 344233.60 03-JUL-07:10 57580.60 01-JUL-00:10 675712.68 03-JUL-07:10 120520.01 03-JUL-07:19 316712.83 14-JUL-15:20 66157.66 17-JUL-15:00 0.00 01-JUL-00:10
August 344233.60 01-AUG-07:10 57580.60 01-AUG-00:10 794004.08 01-AUG-07:10 120520.01 01-AUG-07:19 325068.55 11-AUG-15:39 65997.58 07-AUG-15:39 0.00 01-AUG-00:10
September 344233.60 01-SEP-07:10 57580.60 01-SEP-00:10 439129.89 01-SEP-07:10 120520.01 01-SEP-07:19 269252.46 05-SEP-14:50 65479.00 01-SEP-15:00 0.00 01-SEP-00:10
October 344233.60 02-OCT-07:10 57580.60 01-OCT-00:10 557421.28 02-OCT-07:10 120520.01 02-OCT-07:19 190222.43 18-OCT-15:00 60797.47 18-OCT-13:00 0.00 01-OCT-00:10
November 344233.60 01-NOV-07:10 57580.60 01-NOV-00:10 675712.68 01-NOV-07:10 120520.01 01-NOV-07:19 163286.20 03-NOV-15:20 37077.93 03-NOV-13:00 0.00 01-NOV-00:10
December 344233.60 01-DEC-08:09 57580.60 01-DEC-00:10 794004.08 01-DEC-08:09 120520.01 01-DEC-08:20 124328.37 07-DEC-14:09 36056.75 11-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 344233.60   57580.60   439129.89   120520.01   114844.93   36056.75   0.00  
Maximum of Months 344233.60   57580.60   794004.08   120520.01   325068.55   66157.66   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 40656.26 03-JAN-06:00 7432.49 14-JAN-14:00 20104.05 26-JAN-18:00 0.00 0.00 0.00
February 144822.67 27-FEB-15:30 49363.90 27-FEB-15:30 31485.33 04-FEB-07:40 0.00 0.00 0.00
March 118479.15 14-MAR-13:30 49248.27 14-MAR-11:20 43078.61 31-MAR-23:00 0.00 0.00 0.00
April 243187.99 07-APR-12:39 53564.90 06-APR-15:00 50215.57 29-APR-06:10 0.00 0.00 0.00
May 263820.25 19-MAY-15:20 83442.05 19-MAY-13:00 21892.17 31-MAY-23:00 0.00 0.00 0.00
June 345069.31 29-JUN-14:00 83442.05 06-JUN-14:30 27062.01 08-JUN-20:00 0.00 0.00 0.00
July 457262.74 17-JUL-15:00 83442.05 10-JUL-14:00 36642.14 12-JUL-06:19 0.00 0.00 0.00
August 476400.57 07-AUG-15:30 83442.05 05-AUG-12:20 49347.31 01-AUG-20:00 0.00 0.00 0.00
September 383539.31 07-SEP-14:50 83442.05 02-SEP-10:20 22843.54 30-SEP-23:00 0.00 0.00 0.00
October 270939.81 18-OCT-13:00 59418.29 18-OCT-14:00 33045.11 31-OCT-23:00 0.00 0.00 0.00
November 152402.88 17-NOV-16:00 49286.39 17-NOV-16:00 41306.56 20-NOV-21:00 0.00 0.00 0.00
December 125009.60 10-DEC-01:00 49248.27 05-DEC-11:00 52018.99 28-DEC-18:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 40656.26   7432.49   20104.05   0.00 0.00 0.00
Maximum of Months 476400.57   83442.05   52018.99   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1113276.43 02-JAN-08:09 344233.60 439129.89 57580.60 120330.96 91529.92 6534.79 0.00 34456.59 3330.50
February 1363330.19 27-FEB-16:10 344233.60 557421.28 0.00 86589.42 133921.60 37568.27 0.00 132931.01 49301.74
March 1447490.94 28-MAR-15:50 344233.60 675712.68 0.00 86589.42 168692.31 3712.89 0.00 95364.05 37269.07
April 1782389.44 06-APR-15:00 344233.60 794004.08 0.00 86589.42 202814.66 42292.05 0.00 233752.03 53564.90
May 1529519.66 19-MAY-15:30 344233.60 439129.89 0.00 86589.42 263225.71 64624.56 0.00 263808.45 64107.65
June 1752179.15 29-JUN-15:09 344233.60 557421.28 0.00 86589.42 285977.70 61590.70 0.00 343755.77 71842.86
July 2006149.26 17-JUL-15:20 344233.60 675712.68 0.00 86589.42 297573.57 66032.81 0.00 452565.12 83442.05
August 2144185.78 07-AUG-15:30 344233.60 794004.08 0.00 86589.42 277580.83 65860.87 0.00 476400.57 83442.05
September 1609669.35 07-SEP-15:09 344233.60 439129.89 0.00 86589.42 246497.20 64091.56 0.00 345685.64 83442.05
October 1567254.23 18-OCT-15:00 344233.60 557421.28 0.00 86589.42 190222.43 59573.21 0.00 258837.82 58317.76
November 1542905.79 17-NOV-16:00 344233.60 675712.68 57580.60 86589.42 114876.15 36324.20 0.00 152402.88 49286.39
December 1595432.88 19-DEC-08:09 344233.60 794004.08 57580.60 120330.96 90383.40 5496.63 0.00 115067.50 25150.57
                       
Annual Sum or Average                      
Minimum of Months 1113276.43   344233.60 439129.89 0.00 86589.42 90383.40 3712.89 0.00 34456.59 3330.50
Maximum of Months 2144185.78   344233.60 794004.08 57580.60 120330.96 297573.57 66032.81 0.00 476400.57 83442.05



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 3008975.83 09-JAN-07:10 0.00 87803.99 31-JAN-12:20 0.00
February 0.00 0.00 2307440.93 01-FEB-07:10 0.00 87977.56 17-FEB-12:39 0.00
March 0.00 0.00 2271005.31 06-MAR-07:10 0.00 87910.57 01-MAR-12:50 0.00
April 0.00 0.00 1113284.11 29-APR-06:10 0.00 87069.87 03-APR-11:00 0.00
May 0.00 0.00 1032860.92 08-MAY-06:10 0.00 85654.55 01-MAY-11:30 0.00
June 0.00 0.00 480305.56 16-JUN-06:10 0.00 83551.72 01-JUN-11:39 0.00
July 0.00 0.00 93241.69 08-JUL-06:10 0.00 81328.04 03-JUL-11:39 0.00
August 0.00 0.00 248034.01 18-AUG-06:10 0.00 79976.81 02-AUG-11:50 0.00
September 0.00 0.00 634405.80 19-SEP-06:10 0.00 80897.35 29-SEP-11:00 0.00
October 0.00 0.00 1170744.05 10-OCT-06:10 0.00 83000.44 31-OCT-11:20 0.00
November 0.00 0.00 1881756.18 27-NOV-07:10 0.00 85100.04 30-NOV-12:39 0.00
December 0.00 0.00 2392165.38 29-DEC-07:10 0.00 86719.36 29-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 93241.69   0.00 79976.81   0.00
Maximum of Months 0.00 0.00 3008975.83   0.00 87977.56   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.00 27.12 1.00 27.15
February 0.00 0.00 0.00 0.00 1.17 25.96 0.00 25.96
March 0.00 0.00 0.00 0.00 1.83 25.98 0.00 25.98
April 0.00 0.00 0.00 0.00 2.17 25.89 0.00 25.89
May 0.00 0.00 0.00 0.00 2.83 26.27 0.17 26.33
June 0.00 0.00 0.00 0.00 2.83 25.88 0.00 25.88
July 0.00 0.00 0.00 0.00 6.67 26.12 0.00 26.12
August 0.00 0.00 0.00 0.00 7.17 25.89 0.00 25.89
September 0.00 0.00 0.00 0.00 9.00 26.43 0.50 26.48
October 0.00 0.00 0.00 0.00 11.83 26.46 0.83 26.53
November 0.00 0.00 0.00 0.00 7.67 26.44 0.33 26.48
December 0.00 0.00 0.00 0.00 2.17 26.04 0.00 26.04
                 
Annual Sum or Average 0.00   0.00   61.33 26.32 2.83 26.37
Minimum of Months 0.00 0.00 0.00 0.00 1.17 25.88 0.00 25.88
Maximum of Months 0.00 0.00 0.00 0.00 11.83 27.12 1.00 27.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 26.20 0.00 26.20
May 0.00 0.00 0.00 0.00 1.00 25.73 0.00 25.73
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 25.61 0.00 25.61
August 0.00 0.00 0.00 0.00 1.00 25.63 0.00 25.63
September 0.00 0.00 0.00 0.00 0.83 25.64 0.00 25.64
October 0.00 0.00 0.00 0.00 0.50 25.85 0.00 25.85
November 0.00 0.00 0.00 0.00 0.17 26.21 0.00 26.21
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.83 25.71 0.00 25.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 26.21 0.00 26.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 18.56 0.00 18.56 0.00 18.56 0.00 18.56
February 0.17 19.03 0.00 19.03 0.00 19.03 0.00 19.03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.80 0.00 18.80 0.00 18.80 0.00 18.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.03 0.00 19.03 0.00 19.03 0.00 19.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.00 18.84 2.17 19.06 0.00 19.06 0.00 19.06
February 1.00 18.27 0.17 18.58 0.00 18.58 0.00 18.58
March 1.17 18.52 0.33 18.90 0.00 18.90 0.00 18.90
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 18.10 0.00 18.10 0.00 18.10 0.00 18.10
November 1.33 18.27 0.17 18.51 0.00 18.51 0.00 18.51
December 3.00 18.70 0.33 18.82 0.00 18.82 0.00 18.82
                 
Annual Sum or Average 14.83 18.70 3.17 18.92 0.00 18.92 0.00 18.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.00 19.44 2.17 19.44 0.00 19.44 0.00 19.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.00 18.71 1.00 18.95 0.00 18.95 0.00 18.95
February 0.50 19.32 0.00 19.32 0.00 19.32 0.00 19.32
March 0.33 19.06 0.00 19.06 0.00 19.06 0.00 19.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.00 27.35 0.67 27.36
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34
                 
Annual Sum or Average 6.00 18.80 1.00 19.00 1.00 20.04 0.67 20.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.00 19.34 1.00 19.34 1.00 27.35 0.67 27.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.83 18.18 0.17 18.27 0.00 18.27 0.00 18.27
February 0.67 19.23 0.00 19.23 0.00 19.23 0.00 19.23
March 0.50 19.05 0.00 19.05 0.00 19.05 0.00 19.05
April 0.00 0.00 0.00 0.00 0.67 27.53 0.67 27.53
May 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
June 0.00 0.00 0.00 0.00 4.33 27.87 4.33 27.87
July 0.00 0.00 0.00 0.00 5.17 28.24 5.17 28.24
August 0.00 0.00 0.00 0.00 1.50 28.45 1.50 28.45
September 0.00 0.00 0.00 0.00 2.83 27.76 2.83 27.76
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 19.17 0.00 19.17 0.00 19.17 0.00 19.17
                 
Annual Sum or Average 5.50 18.47 0.17 18.53 14.67 25.37 14.67 26.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.83 19.23 0.17 19.23 5.17 28.45 5.17 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 18.29 0.50 18.50 0.00 18.50 0.00 18.50
February 0.67 19.18 0.00 19.18 1.83 25.63 1.83 26.62
March 0.50 18.86 0.00 18.86 0.50 23.13 0.50 24.55
April 0.00 0.00 0.00 0.00 1.00 27.63 1.00 27.63
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.67 27.72 4.67 27.72
August 0.00 0.00 0.00 0.00 3.83 27.92 3.33 27.95
September 0.00 0.00 0.00 0.00 6.00 28.07 5.67 28.08
October 0.00 0.00 0.00 0.00 2.83 28.06 2.83 28.06
November 0.17 19.07 0.00 19.07 1.33 26.62 1.33 27.06
December 0.50 19.09 0.00 19.09 0.17 21.14 0.17 22.37
                 
Annual Sum or Average 6.33 18.51 0.50 18.65 22.17 25.71 21.33 26.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.18 0.50 19.18 6.00 28.07 5.67 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 18.90 0.00 18.90 0.00 18.90 0.00 18.90
February 0.00 0.00 0.00 0.00 0.67 27.45 0.67 27.45
March 0.00 0.00 0.00 0.00 0.33 27.32 0.33 27.32
April 0.00 0.00 0.00 0.00 2.67 28.29 1.83 28.25
May 0.00 0.00 0.00 0.00 2.67 28.30 1.17 28.26
June 0.00 0.00 0.00 0.00 7.83 27.92 2.83 27.96
July 0.00 0.00 0.00 0.00 18.17 27.99 6.00 28.12
August 0.00 0.00 0.00 0.00 17.00 27.52 4.83 27.69
September 0.00 0.00 0.00 0.00 3.83 28.15 2.33 28.20
October 0.00 0.00 0.00 0.00 0.67 28.30 0.50 28.31
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
                 
Annual Sum or Average 2.50 18.90 0.00 18.90 54.00 27.47 20.67 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 18.90 0.00 18.90 18.17 28.30 6.00 28.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 55.17 17.10 22.83 17.42 0.00 17.42 0.00 17.42
February 19.33 17.22 5.67 17.24 0.00 17.24 0.00 17.24
March 8.17 17.57 2.00 17.99 0.00 17.99 0.00 17.99
April 0.33 19.30 0.00 19.30 0.00 19.30 0.00 19.30
May 0.67 19.15 0.00 19.15 0.00 19.15 0.00 19.15
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 19.26 0.00 19.26 0.00 19.26 0.00 19.26
November 8.00 17.40 1.50 17.78 0.00 17.78 0.00 17.78
December 21.00 17.07 5.67 17.06 0.00 17.06 0.00 17.06
                 
Annual Sum or Average 113.00 17.19 37.67 17.40 0.00 17.40 0.00 17.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 55.17 19.30 22.83 19.30 0.00 19.30 0.00 19.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 27.17 15.65 4.50 15.56 0.00 15.56 0.00 15.56
February 11.67 16.55 1.00 16.41 0.00 16.41 0.00 16.41
March 5.50 16.62 0.00 16.62 0.00 16.62 0.00 16.62
April 0.33 19.19 0.00 19.19 0.00 19.19 0.00 19.19
May 0.67 19.10 0.00 19.10 0.00 19.10 0.00 19.10
June 0.00 0.00 0.00 0.00 3.83 27.98 3.83 27.98
July 0.00 0.00 0.00 0.00 6.17 28.30 6.17 28.30
August 0.00 0.00 0.00 0.00 2.50 28.39 2.50 28.39
September 0.00 0.00 0.00 0.00 2.83 27.84 2.83 27.84
October 0.33 19.29 0.00 19.29 0.00 19.29 0.00 19.29
November 5.00 16.57 0.00 16.57 0.00 16.57 0.00 16.57
December 13.67 16.33 3.00 16.05 0.00 16.05 0.00 16.05
                 
Annual Sum or Average 64.33 16.19 8.50 16.04 15.33 18.14 15.33 19.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.56 0.00 15.56
Maximum of Months 27.17 19.29 4.50 19.29 6.17 28.39 6.17 28.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 22.00 16.18 3.00 16.14 0.00 16.14 0.00 16.14
February 6.83 17.47 0.50 17.29 1.33 18.99 1.33 20.24
March 3.50 17.27 0.17 17.41 0.33 18.24 0.33 18.93
April 0.17 19.18 0.00 19.18 0.67 25.90 0.67 26.65
May 0.50 19.11 0.00 19.11 0.00 19.11 0.00 19.11
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.17 27.70 4.00 27.70
August 0.00 0.00 0.00 0.00 3.17 28.01 2.67 28.04
September 0.00 0.00 0.00 0.00 6.50 28.20 5.83 28.23
October 0.17 19.25 0.00 19.25 3.00 27.40 3.00 27.62
November 2.67 17.43 0.17 17.61 1.00 20.23 1.00 21.77
December 11.00 16.73 2.17 16.51 0.00 16.51 0.00 16.51
                 
Annual Sum or Average 46.83 16.70 6.00 16.60 20.17 19.74 18.83 21.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22.00 19.25 3.00 19.25 6.50 28.20 5.83 28.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.00 15.75 3.83 15.64 0.00 15.64 0.00 15.64
February 7.83 17.03 1.00 16.80 0.00 16.80 0.00 16.80
March 3.67 17.11 0.00 17.11 0.00 17.11 0.00 17.11
April 0.17 19.44 0.00 19.44 0.83 26.60 0.33 26.95
May 0.33 19.05 0.00 19.05 2.50 26.96 1.17 27.19
June 0.00 0.00 0.00 0.00 3.50 28.11 1.50 28.06
July 0.00 0.00 0.00 0.00 7.33 28.46 3.50 28.42
August 0.00 0.00 0.00 0.00 2.67 28.37 1.17 28.40
September 0.00 0.00 0.00 0.00 2.33 28.53 1.50 28.59
October 0.17 19.30 0.00 19.30 0.00 19.30 0.00 19.30
November 3.17 17.19 0.00 17.19 0.00 17.19 0.00 17.19
December 11.50 16.54 2.83 16.23 0.00 16.23 0.00 16.23
                 
Annual Sum or Average 50.83 16.36 7.67 16.17 19.17 19.17 9.17 20.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.64 0.00 15.64
Maximum of Months 24.00 19.44 3.83 19.44 7.33 28.53 3.50 28.59



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 112.33 16.29 45.67 16.67 0.00 16.67 0.00 16.67
February 44.17 16.69 13.17 16.92 0.00 16.92 0.00 16.92
March 25.67 16.69 7.17 16.82 0.00 16.82 0.00 16.82
April 3.50 18.51 0.17 18.59 0.00 18.59 0.00 18.59
May 5.67 17.47 0.50 17.70 0.00 17.70 0.00 17.70
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 27.41 0.00 27.41
August 0.00 0.00 0.00 0.00 0.50 27.33 0.33 27.34
September 0.83 19.21 0.00 19.21 0.00 19.21 0.00 19.21
October 3.83 18.23 0.33 18.38 0.00 18.38 0.00 18.38
November 30.33 16.25 9.83 16.36 0.00 16.36 0.00 16.36
December 72.83 16.01 26.67 16.14 0.00 16.14 0.00 16.14
                 
Annual Sum or Average 299.17 16.39 103.50 16.61 1.00 16.64 0.33 16.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 112.33 19.21 45.67 19.21 0.50 27.41 0.33 27.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 61.33 15.19 13.83 15.21 0.00 15.21 0.00 15.21
February 26.17 15.62 3.67 15.50 0.00 15.50 0.00 15.50
March 18.17 16.01 3.00 15.80 0.00 15.80 0.00 15.80
April 3.00 18.56 0.00 18.56 0.00 18.56 0.00 18.56
May 4.33 16.87 0.00 16.87 0.00 16.87 0.00 16.87
June 0.00 0.00 0.00 0.00 3.00 27.78 3.00 27.78
July 0.00 0.00 0.00 0.00 7.83 28.11 7.33 28.13
August 0.00 0.00 0.00 0.00 3.00 28.40 2.67 28.45
September 0.67 19.18 0.00 19.18 4.00 26.57 4.00 27.13
October 2.67 17.68 0.00 17.68 0.00 17.68 0.00 17.68
November 20.67 15.67 3.33 15.49 0.00 15.49 0.00 15.49
December 52.83 15.10 13.33 14.97 0.00 14.97 0.00 14.97
                 
Annual Sum or Average 189.83 15.50 37.17 15.38 17.83 16.30 17.00 17.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.97 0.00 14.97
Maximum of Months 61.33 19.18 13.83 19.18 7.83 28.40 7.33 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 54.00 15.73 12.00 15.88 0.00 15.88 0.00 15.88
February 20.00 16.17 1.50 16.09 0.83 16.53 0.83 16.94
March 15.67 16.34 1.83 16.30 0.00 16.30 0.00 16.30
April 2.50 18.65 0.00 18.65 0.17 19.19 0.17 19.66
May 4.17 16.83 0.00 16.83 0.00 16.83 0.00 16.83
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 4.67 27.86 3.83 27.88
August 0.00 0.00 0.00 0.00 2.67 28.32 2.17 28.36
September 0.67 19.27 0.00 19.27 5.33 27.36 4.50 27.84
October 1.67 18.42 0.00 18.42 1.33 22.75 1.33 24.42
November 14.33 16.30 1.83 16.22 0.00 16.22 0.00 16.22
December 40.33 15.46 8.17 15.35 0.00 15.35 0.00 15.35
                 
Annual Sum or Average 153.33 15.96 25.33 15.93 15.00 16.87 12.83 17.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 54.00 19.27 12.00 19.27 5.33 28.32 4.50 28.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 50.33 15.05 11.17 15.00 0.00 15.00 0.00 15.00
February 20.00 15.90 2.83 15.71 0.00 15.71 0.00 15.71
March 14.33 16.18 1.83 15.99 0.00 15.99 0.00 15.99
April 1.83 18.80 0.00 18.80 0.67 21.16 0.33 21.92
May 2.17 17.69 0.00 17.69 2.17 22.85 0.67 23.51
June 0.00 0.00 0.00 0.00 3.17 28.29 1.17 28.29
July 0.00 0.00 0.00 0.00 7.33 28.63 2.83 28.60
August 0.00 0.00 0.00 0.00 3.00 28.43 1.67 28.39
September 0.50 19.27 0.00 19.27 3.00 27.13 2.00 27.65
October 1.50 18.42 0.00 18.42 0.00 18.42 0.00 18.42
November 14.83 15.97 2.83 15.75 0.00 15.75 0.00 15.75
December 40.33 15.34 10.33 15.18 0.00 15.18 0.00 15.18
                 
Annual Sum or Average 145.83 15.59 29.00 15.43 19.33 16.72 8.67 17.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.00 0.00 15.00
Maximum of Months 50.33 19.27 11.17 19.27 7.33 28.63 2.83 28.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.68 0.00 27.68
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 20.50 27.96 16.00 27.92
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   21.17 27.95 16.00 27.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 20.50 27.96 16.00 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 8.33 27.94 4.50 27.93
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.33 27.94 4.50 27.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.33 27.94 4.50 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 8.50 28.01 4.50 27.98
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.50 28.01 4.50 27.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 28.01 4.50 27.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 24.67 27.89 22.83 27.89
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 500.17 29.07 382.83 29.12
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   524.83 29.02 405.67 29.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 500.17 29.07 382.83 29.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 392.50 23.32 33.50 23.56 0.00 23.56
February 311.00 23.76 36.33 24.02 0.00 24.02
March 280.00 23.97 36.00 24.21 0.00 24.21
April 101.00 24.01 77.17 24.94 0.00 24.94
May 96.00 24.00 103.00 25.02 0.00 25.02
June 11.17 24.33 221.00 24.94 8.50 24.92
July 11.17 25.14 333.33 24.91 11.17 24.91
August 0.00 0.00 214.33 25.14 0.00 25.14
September 25.17 24.00 209.17 25.09 16.50 25.02
October 15.33 24.00 109.83 26.18 0.00 26.18
November 114.50 24.00 89.33 25.09 0.00 25.09
December 258.33 23.82 52.00 24.24 0.00 24.24
             
Annual Sum or Average 1616.17 23.77 1515.00 24.59 36.17 24.59
Minimum of Months 0.00 0.00 33.50 23.56 0.00 23.56
Maximum of Months 392.50 25.14 333.33 26.18 16.50 26.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 442.00 23.53 10.50 23.59 0.00 23.59
February 323.33 23.81 6.33 23.85 0.00 23.85
March 245.00 23.97 22.33 24.12 0.00 24.12
April 75.17 23.99 58.67 24.87 0.00 24.87
May 96.33 23.98 87.33 24.70 0.00 24.70
June 6.67 24.40 218.50 24.52 5.17 24.52
July 2.33 25.18 348.83 24.43 2.33 24.43
August 0.00 0.00 250.17 24.49 0.00 24.49
September 36.17 24.05 198.50 24.60 14.00 24.57
October 50.67 23.98 83.00 25.22 0.00 25.22
November 163.67 23.98 54.33 24.49 0.00 24.49
December 272.50 23.93 22.33 24.08 0.00 24.08
             
Annual Sum or Average 1713.83 23.83 1360.83 24.28 21.50 24.28
Minimum of Months 0.00 0.00 6.33 23.59 0.00 23.59
Maximum of Months 442.00 25.18 348.83 25.22 14.00 25.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.36 98.17 22.10 98.17 21.92
February 449.50 22.91 28.17 22.77 28.17 22.64
March 499.83 23.44 16.17 23.37 16.17 23.30
April 335.67 23.71 0.00 23.71 0.00 23.71
May 228.33 23.78 56.33 24.09 0.00 24.09
June 65.50 23.84 156.67 24.25 5.50 24.25
July 26.17 24.22 258.00 24.41 6.50 24.43
August 14.50 23.80 151.33 24.61 0.00 24.61
September 116.50 23.82 143.33 24.24 14.67 24.24
October 287.33 23.76 6.33 23.80 0.00 23.80
November 432.33 23.48 3.83 23.46 3.83 23.44
December 497.00 22.73 56.50 22.51 56.50 22.33
             
Annual Sum or Average 3454.67 23.22 974.83 23.34 229.50 23.24
Minimum of Months 14.50 22.36 0.00 22.10 0.00 21.92
Maximum of Months 502.00 24.22 258.00 24.61 98.17 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.78 315.17 20.51 315.17 20.38
February 454.00 21.51 189.17 21.14 189.17 20.94
March 514.00 22.26 112.83 21.90 112.83 21.65
April 436.17 22.89 38.67 22.71 38.67 22.55
May 308.33 23.17 65.17 23.23 22.00 23.08
June 109.17 23.57 153.83 24.01 5.17 24.03
July 42.50 23.87 279.00 24.31 8.67 24.32
August 60.50 23.68 155.33 24.29 0.00 24.29
September 224.50 23.31 122.67 23.73 17.00 23.75
October 444.50 22.85 25.00 22.72 25.00 22.60
November 485.50 22.02 127.33 21.67 127.33 21.43
December 497.00 21.12 256.83 20.73 256.83 20.54
             
Annual Sum or Average 4078.17 22.16 1841.00 22.08 1117.83 21.80
Minimum of Months 42.50 20.78 25.00 20.51 0.00 20.38
Maximum of Months 514.00 23.87 315.17 24.31 315.17 24.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.00 288.17 20.78 288.17 20.68
February 454.00 21.75 132.17 21.48 132.17 21.32
March 511.67 22.61 46.67 22.44 46.67 22.30
April 393.33 23.28 0.00 23.28 0.00 23.28
May 284.67 23.29 59.83 23.58 0.00 23.58
June 60.17 23.64 215.33 24.17 4.17 24.17
July 8.17 24.24 349.17 24.41 2.33 24.41
August 35.50 23.66 219.17 24.27 0.50 24.28
September 223.00 23.29 128.33 23.77 9.00 23.78
October 411.83 23.19 4.67 23.21 0.00 23.21
November 476.67 22.54 33.17 22.42 33.17 22.32
December 497.00 21.70 159.33 21.42 159.33 21.26
             
Annual Sum or Average 3858.00 22.42 1636.00 22.55 675.50 22.34
Minimum of Months 8.17 21.00 0.00 20.78 0.00 20.68
Maximum of Months 511.67 24.24 349.17 24.41 288.17 24.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.67 20.92 298.50 20.74 298.50 20.66
February 432.83 21.52 150.17 21.32 147.83 21.18
March 465.33 21.97 60.83 21.87 53.50 21.75
April 340.00 22.43 45.67 22.68 1.00 22.68
May 255.50 22.64 103.00 23.17 0.00 23.17
June 125.00 23.51 271.17 24.09 19.17 24.19
July 60.17 24.47 369.33 24.40 22.67 24.52
August 118.00 23.20 281.17 23.91 5.83 23.96
September 226.67 22.83 177.83 23.58 16.50 23.65
October 380.50 22.54 16.33 22.65 0.00 22.65
November 472.83 21.94 57.83 21.82 57.83 21.72
December 497.00 21.23 198.33 21.04 198.33 20.93
             
Annual Sum or Average 3873.50 22.00 2030.17 22.33 821.17 22.17
Minimum of Months 60.17 20.92 16.33 20.74 0.00 20.66
Maximum of Months 499.67 24.47 369.33 24.40 298.50 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 458.67 21.24 261.50 21.03 251.83 20.88
February 351.67 21.83 152.83 21.83 117.17 21.65
March 388.17 22.14 99.33 22.21 49.33 22.06
April 308.00 22.60 60.17 22.90 3.50 22.89
May 261.83 22.56 111.17 23.09 8.33 23.04
June 127.83 23.15 223.00 23.91 5.50 23.92
July 54.67 24.14 358.83 24.37 15.17 24.45
August 79.17 23.63 311.50 24.18 9.83 24.25
September 181.67 23.19 235.00 24.00 23.17 24.12
October 270.33 22.80 117.17 23.32 7.33 23.38
November 350.00 22.20 105.83 22.40 46.17 22.25
December 423.50 21.56 170.67 21.38 152.50 21.19
             
Annual Sum or Average 3255.50 22.21 2207.00 22.68 689.83 22.50
Minimum of Months 54.67 21.24 60.17 21.03 3.50 20.88
Maximum of Months 458.67 24.14 358.83 24.37 251.83 24.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.17 21.21 218.50 21.02 218.50 20.92
February 404.50 22.01 88.50 21.94 74.17 21.80
March 375.33 22.75 50.50 22.84 14.50 22.78
April 127.00 23.24 150.50 24.20 5.33 24.26
May 207.00 22.84 172.83 23.74 5.00 23.78
June 55.83 23.82 365.67 24.35 14.17 24.41
July 31.33 26.90 467.67 24.67 31.17 24.80
August 20.17 26.30 474.17 24.51 17.00 24.59
September 190.00 22.99 212.33 23.85 16.00 23.92
October 262.00 22.92 92.17 23.44 2.00 23.46
November 349.50 22.67 45.50 22.96 2.17 22.95
December 431.83 22.37 52.67 22.27 45.50 22.15
             
Annual Sum or Average 2954.67 22.47 2391.00 23.16 445.50 23.07
Minimum of Months 20.17 21.21 45.50 21.02 2.00 20.92
Maximum of Months 500.17 26.90 474.17 24.67 218.50 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.99 490.83 19.97 490.83 19.97
February 454.00 20.47 368.67 20.36 368.67 20.32
March 514.00 21.03 254.83 20.78 254.83 20.65
April 475.17 22.04 79.17 21.81 79.17 21.63
May 386.17 22.58 60.50 22.52 33.33 22.35
June 144.00 23.25 152.33 23.75 4.50 23.76
July 47.67 23.57 275.83 24.23 2.50 24.24
August 122.00 23.29 130.50 23.88 0.00 23.88
September 304.17 22.59 102.50 23.00 18.50 22.98
October 495.00 22.00 63.50 21.82 63.50 21.68
November 489.00 20.87 261.67 20.61 261.67 20.49
December 497.00 20.10 438.67 20.03 438.67 20.00
             
Annual Sum or Average 4430.17 21.35 2679.00 21.29 2016.17 21.04
Minimum of Months 47.67 19.99 60.50 19.97 0.00 19.97
Maximum of Months 514.00 23.57 490.83 24.23 490.83 24.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.00 399.17 19.97 399.17 19.95
February 382.83 20.59 270.17 20.44 270.17 20.37
March 423.17 21.03 187.33 20.79 187.33 20.67
April 343.83 21.72 70.83 21.70 51.00 21.56
May 288.83 22.07 82.33 22.29 28.00 22.12
June 148.83 23.15 200.00 23.95 19.83 24.07
July 81.00 24.23 294.33 24.51 28.17 24.67
August 128.83 22.99 215.50 23.93 8.00 24.00
September 250.50 22.32 120.83 23.08 17.83 23.15
October 403.67 21.76 44.67 21.67 41.50 21.56
November 416.00 20.82 216.33 20.63 216.33 20.53
December 422.00 20.02 365.17 19.94 365.17 19.92
             
Annual Sum or Average 3716.50 21.26 2466.67 21.45 1632.50 21.22
Minimum of Months 81.00 20.00 44.67 19.94 8.00 19.92
Maximum of Months 427.00 24.23 399.17 24.51 399.17 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 474.33 20.76 337.83 20.57 331.83 20.45
February 373.33 21.30 227.17 21.23 194.50 21.04
March 411.83 21.43 188.83 21.41 143.33 21.21
April 352.33 21.92 99.17 22.09 50.33 21.95
May 308.33 22.15 110.17 22.43 34.67 22.26
June 183.83 22.80 193.67 23.60 5.00 23.61
July 88.67 23.48 316.50 24.23 13.33 24.30
August 126.33 23.13 285.17 24.04 8.00 24.10
September 216.00 22.79 218.83 23.72 27.50 23.86
October 321.50 22.30 125.17 22.75 29.50 22.73
November 392.00 21.61 178.50 21.59 132.33 21.37
December 455.83 20.79 285.50 20.52 283.50 20.39
             
Annual Sum or Average 3704.33 21.71 2566.50 22.05 1253.83 21.81
Minimum of Months 88.67 20.76 99.17 20.52 5.00 20.39
Maximum of Months 474.33 23.48 337.83 24.23 331.83 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.22 452.33 20.17 452.33 20.15
February 443.33 20.72 287.50 20.55 287.33 20.48
March 489.17 21.06 192.33 20.88 188.83 20.76
April 412.67 21.77 75.17 21.84 46.83 21.75
May 329.17 22.11 116.00 22.50 30.17 22.40
June 190.17 22.75 217.50 23.61 10.50 23.67
July 100.50 23.46 327.00 24.21 17.00 24.31
August 152.50 22.81 254.00 23.84 4.83 23.88
September 307.50 22.23 139.33 22.95 18.50 23.02
October 448.33 21.72 50.83 21.72 35.83 21.64
November 480.67 21.02 204.00 20.80 204.00 20.67
December 497.00 20.30 382.50 20.18 382.50 20.13
             
Annual Sum or Average 4353.00 21.33 2698.50 21.54 1678.67 21.32
Minimum of Months 100.50 20.22 50.83 20.17 4.83 20.13
Maximum of Months 502.00 23.46 452.33 24.21 452.33 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.66 496.17 19.65 496.17 19.65
February 454.00 20.01 433.33 19.98 433.33 19.97
March 514.00 20.41 374.83 20.26 374.83 20.20
April 481.83 21.16 201.17 20.83 201.17 20.65
May 428.00 21.96 121.83 21.76 97.33 21.52
June 210.83 22.72 138.50 23.29 5.50 23.30
July 103.50 23.14 248.83 23.96 3.83 23.97
August 191.17 22.85 124.83 23.43 1.33 23.43
September 358.00 21.99 118.50 22.26 53.33 22.14
October 501.33 21.04 207.17 20.74 207.17 20.58
November 489.00 20.17 380.50 20.03 380.50 19.98
December 497.00 19.82 478.33 19.80 478.33 19.79
             
Annual Sum or Average 4730.67 20.87 3324.00 20.80 2732.83 20.58
Minimum of Months 103.50 19.66 118.50 19.65 1.33 19.65
Maximum of Months 514.00 23.14 496.17 23.96 496.17 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.82 486.67 19.80 486.67 19.80
February 454.00 20.24 372.83 20.13 372.83 20.09
March 507.17 20.69 305.83 20.46 305.83 20.35
April 406.33 21.27 143.67 21.02 133.17 20.82
May 338.67 21.78 135.00 21.89 67.17 21.63
June 154.17 22.69 254.33 23.75 15.17 23.82
July 94.00 24.02 364.67 24.37 29.00 24.51
August 143.33 22.81 293.50 23.84 10.00 23.90
September 301.33 22.16 156.50 22.80 43.50 22.81
October 485.33 21.27 136.33 20.99 136.33 20.82
November 489.00 20.31 345.00 20.15 345.00 20.09
December 497.00 19.88 465.50 19.84 465.50 19.83
             
Annual Sum or Average 4372.33 20.92 3459.83 21.13 2410.17 20.89
Minimum of Months 94.00 19.82 135.00 19.80 10.00 19.80
Maximum of Months 507.17 24.02 486.67 24.37 486.67 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 491.67 20.26 401.17 20.07 401.17 20.00
February 406.17 20.83 274.67 20.63 258.50 20.47
March 437.50 20.90 269.17 20.74 242.33 20.57
April 386.00 21.36 171.83 21.26 134.50 21.02
May 341.50 21.74 152.17 21.88 80.67 21.63
June 213.83 22.44 189.83 23.32 8.00 23.32
July 125.33 23.17 298.17 24.05 15.33 24.14
August 157.00 22.77 280.00 23.81 9.33 23.85
September 244.50 22.29 221.83 23.18 48.50 23.18
October 362.00 21.57 169.50 21.72 97.67 21.50
November 428.83 20.94 247.17 20.73 230.33 20.57
December 475.33 20.28 364.83 20.07 364.83 19.98
             
Annual Sum or Average 4069.67 21.23 3040.33 21.45 1891.17 21.18
Minimum of Months 125.33 20.26 152.17 20.07 8.00 19.98
Maximum of Months 491.67 23.17 401.17 24.05 401.17 24.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.87 473.67 19.84 473.67 19.83
February 448.83 20.36 353.33 20.22 353.33 20.17
March 495.50 20.68 295.33 20.49 293.50 20.40
April 426.33 21.25 154.50 21.14 131.00 20.96
May 368.00 21.82 147.00 22.04 68.00 21.84
June 223.67 22.45 210.33 23.37 11.83 23.42
July 137.50 23.10 304.67 24.01 18.17 24.11
August 190.17 22.57 239.00 23.59 6.83 23.63
September 330.33 21.89 150.33 22.49 45.83 22.47
October 468.83 21.20 144.00 21.03 132.33 20.86
November 487.67 20.52 313.50 20.32 313.50 20.24
December 497.00 19.99 438.17 19.92 438.17 19.89
             
Annual Sum or Average 4575.83 20.99 3223.83 21.14 2286.17 20.91
Minimum of Months 137.50 19.87 144.00 19.84 6.83 19.83
Maximum of Months 502.00 23.10 473.67 24.01 473.67 24.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 26.27 386.67 27.00 0.00 27.00
February 1.17 27.00 437.67 27.00 1.17 27.00
March 5.17 27.00 513.17 27.00 5.17 27.00
April 21.33 27.00 485.00 27.00 21.33 27.00
May 1.50 27.00 508.00 27.00 1.50 27.00
June 13.83 27.00 496.00 27.00 13.83 27.00
July 104.17 27.00 497.00 27.00 104.17 27.00
August 213.83 27.10 514.00 27.06 213.83 27.07
September 7.50 27.00 485.00 27.00 7.50 27.00
October 8.33 27.00 502.00 27.00 8.33 27.00
November 5.67 27.00 489.00 27.00 5.67 27.00
December 2.67 27.00 497.00 27.00 2.67 27.00
             
Annual Sum or Average 386.00 27.06 5810.50 27.01 385.17 27.01
Minimum of Months 0.83 26.27 386.67 27.00 0.00 27.00
Maximum of Months 213.83 27.10 514.00 27.06 213.83 27.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 101.67 25.60 211.17 26.54 0.00 26.54
February 13.17 27.00 315.00 27.00 0.00 27.00
March 6.33 27.00 464.67 27.00 0.00 27.00
April 3.33 27.00 481.67 27.00 3.33 27.00
May 0.83 27.00 500.33 27.00 0.83 27.00
June 6.83 27.00 496.00 27.00 6.83 27.00
July 15.67 27.00 497.00 27.00 15.67 27.00
August 35.00 27.26 514.00 27.04 35.00 27.05
September 3.83 27.00 485.00 27.00 3.83 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 455.83 27.00 0.00 27.00
December 12.00 27.00 345.67 27.00 0.00 27.00
             
Annual Sum or Average 198.67 26.33 5268.33 26.98 65.50 26.98
Minimum of Months 0.00 0.00 211.17 26.54 0.00 26.54
Maximum of Months 101.67 27.26 514.00 27.04 35.00 27.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 272.33 24.60 120.33 24.93 30.33 24.71
February 46.50 26.94 184.83 26.99 0.00 26.99
March 21.83 27.00 356.17 27.00 0.00 27.00
April 4.00 27.00 423.83 27.00 4.00 27.00
May 22.67 25.80 473.33 26.95 1.50 26.95
June 9.67 27.00 496.00 27.00 9.67 27.00
July 38.67 27.00 497.00 27.00 38.67 27.00
August 54.17 27.15 514.00 27.03 54.17 27.04
September 6.00 27.00 476.33 27.00 6.00 27.00
October 0.00 0.00 457.00 27.00 0.00 27.00
November 22.33 27.00 321.00 27.00 0.00 27.00
December 66.00 27.00 205.17 27.00 0.00 27.00
             
Annual Sum or Average 564.17 25.80 4525.00 26.84 144.33 26.81
Minimum of Months 0.00 0.00 120.33 24.93 0.00 24.71
Maximum of Months 272.33 27.15 514.00 27.03 54.17 27.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 241.17 27.00 502.00 27.00 241.17 27.00
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.01 514.00 27.01 514.00 27.01
April 485.00 27.07 485.00 27.07 485.00 27.07
May 491.67 27.00 508.00 27.00 491.67 27.00
June 496.00 27.01 496.00 27.01 496.00 27.01
July 497.00 27.01 497.00 27.01 497.00 27.01
August 514.00 28.66 514.00 28.66 514.00 28.66
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.01 502.00 27.01 502.00 27.01
November 489.00 27.01 489.00 27.01 489.00 27.01
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5665.83 27.16 5943.00 27.16 5665.83 27.16
Minimum of Months 241.17 27.00 454.00 27.00 241.17 27.00
Maximum of Months 514.00 28.66 514.00 28.66 514.00 28.66



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99405 13.62705 0.61061 13.04016
February 454.00000 27.00000 14.88933 0.70518 15.63201
March 514.00000 27.00000 16.83122 0.78837 18.22970
April 485.00000 27.00001 19.99761 0.88481 21.61421
May 508.00000 27.00015 22.19870 0.14055 5.58368
June 496.00000 27.00044 25.69883 0.25490 6.45331
July 497.00000 27.00025 26.88134 0.32863 7.33538
August 514.00000 27.04375 26.41301 0.38385 8.26142
September 485.00000 27.00050 25.35357 0.17549 5.80399
October 502.00000 27.00006 22.35811 0.83585 19.80843
November 489.00000 27.00000 18.48412 0.80606 18.80768
December 497.00000 27.00000 14.81276 0.76660 17.53778
           
Annual Sum or Average 5943.00000 27.00340 20.66825 0.55517 13.14108
Minimum of Months 454.00000 26.99405 13.62705 0.14055 5.58368
Maximum of Months 514.00000 27.04375 26.88134 0.88481 21.61421



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.68681 13.64573 0.43896 9.89855
February 454.00000 27.00000 14.88082 0.57091 12.05691
March 514.00000 27.00000 16.81442 0.64385 13.92053
April 485.00000 27.00002 19.96627 0.73886 16.65944
May 508.00000 27.00014 22.21604 0.04347 5.33628
June 496.00000 27.00042 25.71161 0.15741 5.69508
July 497.00000 27.00027 26.88216 0.21893 6.14458
August 514.00000 27.02071 26.43164 0.23183 6.33626
September 485.00000 27.00042 25.45389 0.08598 5.40024
October 502.00000 27.00006 22.33874 0.72743 16.25041
November 489.00000 27.00000 18.45781 0.65305 14.13850
December 497.00000 27.00000 14.78576 0.57106 12.08281
           
Annual Sum or Average 5943.00000 26.97544 20.67153 0.42184 10.30117
Minimum of Months 454.00000 26.68681 13.64573 0.04347 5.33628
Maximum of Months 514.00000 27.02071 26.88216 0.73886 16.65944



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.65374 14.08579 0.16813 8.77225
February 454.00000 26.99363 14.88239 0.49645 10.51011
March 514.00000 27.00000 16.82124 0.57505 12.29428
April 485.00000 27.00002 19.98205 0.68075 15.08178
May 508.00000 26.94324 22.27237 -0.0193 6.02306
June 496.00000 27.00043 25.72502 0.14559 5.77934
July 497.00000 27.00027 26.89120 0.22018 6.27739
August 514.00000 27.01722 26.44358 0.22246 6.38640
September 485.00000 27.00026 25.53362 0.04753 5.52354
October 502.00000 27.00006 22.36171 0.66256 14.46683
November 489.00000 27.00000 18.46961 0.56931 12.10518
December 497.00000 27.00000 14.79698 0.48893 10.37074
           
Annual Sum or Average 5943.00000 26.88252 20.72878 0.35314 9.44857
Minimum of Months 454.00000 25.65374 14.08579 -0.0193 5.52354
Maximum of Months 514.00000 27.01722 26.89120 0.68075 15.08178



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99981 30.00048 0.99464 25.93402
February 454.00000 27.01076 29.99976 1.18377 34.47959
March 514.00000 27.00792 29.99988 1.34330 42.52384
April 485.00000 27.06801 29.99901 1.49962 50.88221
May 508.00000 27.00178 30.00193 0.46888 9.63623
June 496.00000 27.00941 29.99928 0.71351 15.72974
July 497.00000 27.00526 30.02750 0.93146 23.34127
August 514.00000 28.65540 29.87932 1.59976 55.53314
September 485.00000 27.00301 30.00190 0.52566 10.84545
October 502.00000 27.01093 29.99904 1.24836 37.65016
November 489.00000 27.00796 29.99858 1.37456 44.16500
December 497.00000 27.00096 30.00029 1.48289 49.97483
           
Annual Sum or Average 5943.00000 27.15349 29.99188 1.11435 33.42489
Minimum of Months 454.00000 26.99981 29.87932 0.46888 9.63623
Maximum of Months 514.00000 28.65540 30.02750 1.59976 55.53314



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.73832 12.34237 0.10002 6.72593
February 454.00000 24.15895 14.03776 0.21030 6.55546
March 514.00000 24.28154 15.05086 0.25695 6.67277
April 485.00000 24.44502 18.64676 0.32158 7.49633
May 508.00000 24.46611 22.35799 -0.5038 11.29442
June 496.00000 24.43937 31.09516 -0.4323 9.70914
July 497.00000 24.60722 35.54968 -0.3415 8.74563
August 514.00000 24.47938 30.66735 -0.4036 9.35473
September 485.00000 24.54175 30.22147 -0.4025 9.54645
October 502.00000 24.57479 20.80531 0.38164 8.62212
November 489.00000 24.55173 16.26124 0.33675 7.88526
December 497.00000 24.31282 13.36666 0.25448 6.92385
           
Annual Sum or Average 5943.00000 24.38378 21.74958 -0.0212 8.30922
Minimum of Months 454.00000 23.73832 12.34237 -0.5038 6.55546
Maximum of Months 514.00000 24.60722 35.54968 0.38164 11.29442



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.68651 13.04966 0.06430 5.98185
February 454.00000 24.02110 14.84340 0.17577 6.03968
March 514.00000 24.20936 15.93786 0.25136 6.54130
April 485.00000 24.33272 19.54558 0.32384 7.45273
May 508.00000 24.33909 23.45996 -0.5239 11.43407
June 496.00000 24.24499 32.05497 -0.4530 9.66159
July 497.00000 24.30755 35.72359 -0.3925 8.69594
August 514.00000 24.25038 31.26365 -0.4296 9.17083
September 485.00000 24.30819 31.31189 -0.4579 9.98288
October 502.00000 24.38472 22.34635 0.34878 7.85851
November 489.00000 24.37523 17.39576 0.29984 7.16511
December 497.00000 24.23208 14.27086 0.23116 6.43252
           
Annual Sum or Average 5943.00000 24.22513 22.64948 -0.0495 8.05072
Minimum of Months 454.00000 23.68651 13.04966 -0.5239 5.98185
Maximum of Months 514.00000 24.38472 35.72359 0.34878 11.43407



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.35589 15.70764 -0.2713 8.12650
February 454.00000 22.92322 16.30397 -0.1186 6.60630
March 514.00000 23.46641 17.26424 0.03646 5.92256
April 485.00000 23.88549 20.85431 0.18024 6.00521
May 508.00000 24.11749 24.16080 -0.6367 14.33974
June 496.00000 24.14256 32.54658 -0.5236 11.08990
July 497.00000 24.23947 36.14691 -0.4574 9.82442
August 514.00000 24.22276 31.52262 -0.4953 10.46250
September 485.00000 24.15934 31.90707 -0.5426 11.75378
October 502.00000 23.98325 23.66789 0.22242 6.24108
November 489.00000 23.56446 18.94718 0.06675 5.79849
December 497.00000 22.73498 15.66881 -0.1681 7.25665
           
Annual Sum or Average 5943.00000 23.65457 23.77059 -0.2274 8.64155
Minimum of Months 454.00000 22.35589 15.66881 -0.6367 5.79849
Maximum of Months 514.00000 24.23947 36.14691 0.22242 14.33974



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.78127 14.39112 -0.6949 18.16078
February 454.00000 21.50629 17.11249 -0.4859 12.67041
March 514.00000 22.26133 18.58611 -0.2778 9.43681
April 485.00000 23.01033 22.24621 -0.0483 6.86140
May 508.00000 23.63229 24.95672 -0.8205 21.83846
June 496.00000 24.03352 32.62163 -0.5616 12.36369
July 497.00000 24.20198 36.02322 -0.4615 9.93169
August 514.00000 24.16352 31.55560 -0.5163 11.05732
September 485.00000 23.83717 32.73849 -0.6707 16.32686
October 502.00000 22.98555 25.60804 -0.0387 6.56109
November 489.00000 22.03599 20.52812 -0.3261 10.10001
December 497.00000 21.11673 16.56674 -0.5873 15.94368
           
Annual Sum or Average 5943.00000 22.80717 24.45278 -0.4580 12.61456
Minimum of Months 454.00000 20.78127 14.39112 -0.8205 6.56109
Maximum of Months 514.00000 24.20198 36.02322 -0.0387 21.83846



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.99918 12.62436 -0.6163 15.18572
February 454.00000 21.74864 15.24681 -0.3888 10.09275
March 514.00000 22.62051 16.39018 -0.1551 7.03800
April 485.00000 23.42788 19.92564 0.08019 5.83636
May 508.00000 23.74334 23.59864 -0.7380 18.39244
June 496.00000 24.12182 31.56079 -0.4831 10.47493
July 497.00000 24.30231 34.90862 -0.3700 8.45063
August 514.00000 24.16744 30.75682 -0.4597 9.94140
September 485.00000 23.84059 31.51738 -0.6397 15.52380
October 502.00000 23.35556 22.86250 0.07289 5.77429
November 489.00000 22.58376 18.07312 -0.1560 6.89529
December 497.00000 21.69608 14.73312 -0.3998 10.13592
           
Annual Sum or Average 5943.00000 23.05988 22.72789 -0.3551 10.32128
Minimum of Months 454.00000 20.99918 12.62436 -0.7380 5.77429
Maximum of Months 514.00000 24.30231 34.90862 0.08019 18.39244



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.94028 11.92496 -0.6183 15.19041
February 454.00000 21.65624 14.58214 -0.3847 10.39017
March 514.00000 22.18201 16.02051 -0.2131 8.02203
April 485.00000 22.95723 19.96277 0.02975 6.86849
May 508.00000 23.42212 23.47511 -0.7527 20.13459
June 496.00000 23.97954 31.53244 -0.4271 11.23774
July 497.00000 24.19871 34.93194 -0.2913 8.76484
August 514.00000 23.87382 31.00036 -0.4519 11.21158
September 485.00000 23.58825 31.59396 -0.6301 16.90182
October 502.00000 22.93725 22.81179 0.02533 6.43000
November 489.00000 22.02116 17.90931 -0.2554 7.80942
December 497.00000 21.22731 14.39155 -0.4967 11.59464
           
Annual Sum or Average 5943.00000 22.75670 22.55910 -0.3729 11.22750
Minimum of Months 454.00000 20.94028 11.92496 -0.7527 6.43000
Maximum of Months 514.00000 24.19871 34.93194 0.02975 20.13459



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.52785 11.70618 -0.4662 13.82541
February 454.00000 22.41233 14.01706 -0.1833 10.06063
March 514.00000 22.64086 15.59496 -0.0921 8.27065
April 485.00000 23.19602 19.71806 0.07869 7.16350
May 508.00000 23.40555 23.56771 -0.7870 21.89718
June 496.00000 23.91782 31.74909 -0.4994 12.16169
July 497.00000 24.20829 34.95816 -0.3329 8.84551
August 514.00000 24.08665 30.60633 -0.3800 9.74566
September 485.00000 23.88807 30.98856 -0.5014 14.60569
October 502.00000 23.47316 22.02309 0.17981 7.86180
November 489.00000 22.83121 17.11766 -0.0443 8.24350
December 497.00000 21.97527 13.83822 -0.3036 10.85671
           
Annual Sum or Average 5943.00000 23.13484 22.20735 -0.2793 11.14790
Minimum of Months 454.00000 21.52785 11.70618 -0.7870 7.16350
Maximum of Months 514.00000 24.20829 34.95816 0.17981 21.89718



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.22336 11.59870 -0.5139 12.28287
February 454.00000 22.28596 13.85745 -0.1899 8.14586
March 514.00000 23.17127 14.95698 0.06184 6.70467
April 485.00000 24.11162 18.49627 0.35353 8.68226
May 508.00000 23.76945 22.92951 -0.5912 15.88752
June 496.00000 24.20628 31.10220 -0.2955 8.56886
July 497.00000 24.47833 34.31203 -0.1247 7.07032
August 514.00000 24.38709 29.94851 -0.1663 7.00417
September 485.00000 23.78446 31.06976 -0.5190 14.15876
October 502.00000 23.63098 21.70636 0.22340 7.23012
November 489.00000 23.20763 16.54236 0.06656 6.71967
December 497.00000 22.63015 13.10086 -0.1115 7.10088
           
Annual Sum or Average 5943.00000 23.41443 21.68260 -0.1511 9.13142
Minimum of Months 454.00000 21.22336 11.59870 -0.5912 6.70467
Maximum of Months 514.00000 24.47833 34.31203 0.35353 15.88752



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.98553 12.72868 -0.9403 25.84211
February 454.00000 20.46821 15.78620 -0.7563 18.84629
March 514.00000 21.03231 17.46904 -0.5623 13.69192
April 485.00000 22.07558 21.74296 -0.2565 8.25993
May 508.00000 22.97461 24.75261 -1.0155 29.77769
June 496.00000 23.86244 32.18809 -0.5982 13.70037
July 497.00000 24.16572 35.08864 -0.4519 9.96230
August 514.00000 23.98070 31.11341 -0.5699 12.83708
September 485.00000 23.23534 32.65825 -0.8622 24.21688
October 502.00000 22.02872 24.77953 -0.2523 7.91207
November 489.00000 20.87041 19.27771 -0.5963 14.83153
December 497.00000 20.09934 15.38735 -0.8580 23.04005
           
Annual Sum or Average 5943.00000 22.07781 23.62528 -0.6431 16.90480
Minimum of Months 454.00000 19.98553 12.72868 -1.0155 7.91207
Maximum of Months 514.00000 24.16572 35.08864 -0.2523 29.77769



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.00056 11.60973 -0.9219 25.05661
February 385.00000 20.60899 14.58034 -0.6973 17.43834
March 433.00000 21.09250 16.15237 -0.5171 13.04077
April 410.00000 22.13057 20.61163 -0.1916 8.53810
May 430.00000 22.78934 24.10187 -0.9909 30.00474
June 418.00000 23.83078 31.55332 -0.4987 14.05799
July 422.00000 24.24949 34.44596 -0.3023 9.84818
August 433.00000 23.88198 30.43768 -0.4862 13.10655
September 410.00000 23.12595 32.18143 -0.8094 24.31521
October 427.00000 21.89826 23.79306 -0.2414 7.85736
November 417.00000 20.82537 18.06420 -0.5887 14.08687
December 422.00000 20.01904 14.21640 -0.8660 23.20927
           
Annual Sum or Average 5034.00000 22.04620 22.67987 -0.5926 16.71880
Minimum of Months 385.00000 20.00056 11.60973 -0.9909 7.85736
Maximum of Months 433.00000 24.24949 34.44596 -0.1916 30.00474



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.97184 11.44203 -0.6362 18.01768
February 454.00000 21.85571 13.91524 -0.3401 12.98561
March 514.00000 21.98434 15.83205 -0.2645 10.81426
April 485.00000 22.57303 20.44451 -0.0803 8.37010
May 508.00000 22.97998 24.11504 -0.9386 28.20120
June 496.00000 23.67663 32.21559 -0.5942 15.28868
July 497.00000 24.10393 35.04354 -0.3893 10.27579
August 514.00000 23.98299 30.63275 -0.4416 11.82492
September 485.00000 23.63769 31.39053 -0.5865 18.33589
October 502.00000 22.99173 22.63822 0.06526 8.48776
November 489.00000 22.15960 17.32663 -0.2234 10.58435
December 497.00000 21.06249 13.92676 -0.5629 16.43370
           
Annual Sum or Average 5943.00000 22.67084 22.46156 -0.4175 14.15950
Minimum of Months 454.00000 20.97184 11.44203 -0.9386 8.37010
Maximum of Months 514.00000 24.10393 35.04354 0.06526 28.20120



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.22103 11.72890 -0.8572 22.56112
February 454.00000 20.79716 14.60741 -0.6331 15.91979
March 514.00000 21.20638 16.42169 -0.4730 12.13123
April 485.00000 22.14280 20.84836 -0.1740 8.06968
May 508.00000 22.87945 24.16951 -0.9360 28.55736
June 496.00000 23.61064 32.32315 -0.5631 15.18531
July 497.00000 24.03410 35.23663 -0.3690 10.42460
August 514.00000 23.80424 31.01509 -0.4978 13.12441
September 485.00000 22.97970 32.51527 -0.8351 25.25725
October 502.00000 21.97539 23.93301 -0.2070 7.76378
November 489.00000 21.07072 18.23502 -0.5087 12.64677
December 497.00000 20.30090 14.36985 -0.7768 20.17113
           
Annual Sum or Average 5943.00000 22.09593 22.99842 -0.5692 15.98941
Minimum of Months 454.00000 20.22103 11.72890 -0.9360 7.76378
Maximum of Months 514.00000 24.03410 35.23663 -0.1740 28.55736



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.65918 12.46043 -1.0954 32.55441
February 454.00000 20.01040 15.71318 -0.9276 25.51783
March 514.00000 20.41078 17.47957 -0.7623 19.72263
April 485.00000 21.17814 22.30994 -0.4930 13.07968
May 508.00000 22.31492 25.34050 -1.2484 39.42905
June 496.00000 23.50811 32.68185 -0.7092 18.25360
July 497.00000 23.96042 35.37420 -0.5071 11.83338
August 514.00000 23.67752 31.55103 -0.6623 16.37219
September 485.00000 22.60678 33.55053 -1.0774 33.75156
October 502.00000 21.04001 25.75063 -0.5130 12.94976
November 489.00000 20.16710 19.62367 -0.8232 22.13715
December 497.00000 19.81939 15.07545 -1.0074 28.90970
           
Annual Sum or Average 5943.00000 21.54284 23.95464 -0.8184 22.85920
Minimum of Months 454.00000 19.65918 12.46043 -1.2484 11.83338
Maximum of Months 514.00000 23.96042 35.37420 -0.4930 39.42905



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.82268 11.98107 -1.0343 29.89003
February 454.00000 20.24156 14.98955 -0.8348 22.26286
March 514.00000 20.73592 16.67275 -0.6431 16.85247
April 485.00000 21.72854 21.08877 -0.3123 11.31696
May 508.00000 22.57310 24.48710 -1.0761 33.03814
June 496.00000 23.73308 31.80617 -0.5131 14.85538
July 497.00000 24.16441 34.66736 -0.2950 9.79355
August 514.00000 23.81421 30.81317 -0.4800 13.41518
September 485.00000 22.95084 32.63217 -0.8764 27.31123
October 502.00000 21.35685 24.79090 -0.3955 10.87616
November 489.00000 20.30915 18.98745 -0.7621 19.82751
December 497.00000 19.88007 14.56901 -0.9732 27.56004
           
Annual Sum or Average 5943.00000 21.78867 23.16975 -0.6823 19.73351
Minimum of Months 454.00000 19.82268 11.98107 -1.0761 9.79355
Maximum of Months 514.00000 24.16441 34.66736 -0.2950 33.03814



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.33887 11.69032 -0.8491 24.44875
February 454.00000 21.19256 14.25556 -0.5481 17.30665
March 514.00000 21.36910 16.11978 -0.4584 14.96891
April 485.00000 21.95074 20.93084 -0.2598 11.42672
May 508.00000 22.56228 24.58045 -1.1027 34.70852
June 496.00000 23.43822 32.51958 -0.6722 18.73357
July 497.00000 23.94691 35.23608 -0.4291 11.92818
August 514.00000 23.80059 30.89434 -0.4967 14.16090
September 485.00000 23.29514 31.94448 -0.7194 23.83454
October 502.00000 22.30140 23.47795 -0.1316 10.42757
November 489.00000 21.32569 17.99184 -0.4698 14.77043
December 497.00000 20.44055 14.17324 -0.7745 22.44491
           
Annual Sum or Average 5943.00000 22.17132 22.86847 -0.5769 18.28530
Minimum of Months 454.00000 20.33887 11.69032 -1.1027 10.42757
Maximum of Months 514.00000 23.94691 35.23608 -0.1316 34.70852



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.87402 11.85611 -1.0091 28.94655
February 454.00000 20.40127 14.75463 -0.7800 20.88740
March 514.00000 20.79352 16.50185 -0.6204 16.32561
April 485.00000 21.61106 21.20115 -0.3302 10.93222
May 508.00000 22.49667 24.56518 -1.0856 34.58652
June 496.00000 23.37985 32.60288 -0.6377 18.42760
July 497.00000 23.86768 35.43630 -0.4111 12.07362
August 514.00000 23.59879 31.30789 -0.5598 15.64472
September 485.00000 22.64971 33.03980 -0.9622 31.01355
October 502.00000 21.38862 24.61306 -0.3786 10.74183
November 489.00000 20.53248 18.64971 -0.6889 17.91495
December 497.00000 19.99197 14.37504 -0.9173 25.50254
           
Annual Sum or Average 5943.00000 21.72699 23.29014 -0.6981 20.24713
Minimum of Months 454.00000 19.87402 11.85611 -1.0856 10.74183
Maximum of Months 514.00000 23.86768 35.43630 -0.3302 34.58652



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 99053850.16 2895.00 13-JAN-05:20 9.52 0.412465E+09 0.00 0.511519E+09 0.05 4.17 03-JAN-06:50 0.00 0.00
February 0.128583E+10 65060.76 27-FEB-15:30 23.68 0.693541E+10 0.00 0.822123E+10 0.16 6.39 27-FEB-15:30 0.00 0.00
March 0.267485E+09 18487.76 14-MAR-13:30 19.95 0.111353E+10 0.00 0.138102E+10 0.11 4.17 15-MAR-05:30 0.00 0.00
April 0.111077E+11 86499.01 07-APR-12:40 99.22 0.607392E+11 0.00 0.718469E+11 0.66 7.01 07-APR-12:40 0.00 0.00
May 0.302983E+11 100697.89 19-MAY-15:30 187.31 0.179619E+12 0.00 0.209917E+12 1.34 7.23 19-MAY-15:30 0.00 0.00
June 0.749624E+11 114923.91 29-JUN-14:50 368.64 0.472897E+12 0.00 0.547859E+12 2.93 7.33 29-JUN-14:50 0.00 0.00
July 0.113914E+12 137064.83 17-JUL-15:40 505.12 0.747905E+12 0.00 0.861819E+12 4.07 7.36 25-JUL-15:50 0.00 0.00
August 0.100072E+12 138784.57 07-AUG-15:30 493.54 0.648925E+12 0.00 0.748997E+12 3.83 7.36 10-AUG-15:20 0.00 0.00
September 0.550771E+11 163680.49 07-SEP-14:50 283.48 0.343351E+12 0.00 0.398428E+12 2.23 7.28 01-SEP-16:00 0.00 0.00
October 0.167268E+11 87767.38 18-OCT-14:00 129.79 0.955486E+11 0.00 0.112275E+12 0.87 7.03 16-OCT-12:40 0.00 0.00
November 0.174623E+10 44217.06 17-NOV-17:00 41.58 0.724393E+10 0.00 0.899016E+10 0.24 4.18 13-NOV-05:00 0.00 0.00
December 85777324.05 2898.10 04-DEC-04:46 8.24 0.357184E+09 0.00 0.442961E+09 0.05 4.17 08-DEC-06:40 0.00 0.00
                         
Annual Sum or Average 0.405642E+12     2170.07 0.256505E+13 0.00 0.297069E+13 1.39     0.00 0.00
Minimum of Months 85777324.05 2895.00   8.24 0.357184E+09 0.00 0.442961E+09 0.05 4.17   0.00 0.00
Maximum of Months 0.113914E+12 163680.49   505.12 0.747905E+12 0.00 0.861819E+12 4.07 7.36   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.230976E+10 100697.89 19-MAY-15:30 7.17 0.163151E+11 0.00 0.186249E+11 0.07 7.23 19-MAY-15:30 0.00 0.00
June 0.239445E+11 114923.91 29-JUN-14:50 71.19 0.169805E+12 0.00 0.193749E+12 0.70 7.33 29-JUN-14:50 0.00 0.00
July 0.499368E+11 137064.83 17-JUL-15:40 143.10 0.355980E+12 0.00 0.405916E+12 1.37 7.36 25-JUL-15:50 0.00 0.00
August 0.413944E+11 138784.57 07-AUG-15:30 120.30 0.295370E+12 0.00 0.336765E+12 1.15 7.36 10-AUG-15:20 0.00 0.00
September 0.121728E+11 163680.49 07-SEP-14:50 36.47 0.856368E+11 0.00 0.978096E+11 0.36 7.28 01-SEP-16:00 0.00 0.00
October 0.109884E+10 87767.38 18-OCT-14:00 3.67 0.762557E+10 0.00 0.872441E+10 0.03 6.98 18-OCT-12:40 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.130857E+12     381.90 0.930732E+12 0.00 0.106159E+13 0.31     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.499368E+11 163680.49   143.10 0.355980E+12 0.00 0.405916E+12 1.37 7.36   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.852750E+10 744.00 7432.49 14-JAN-15:00 203101.59 13-JAN-16:30 21.70 18.33 15.27
February 0.215271E+11 672.00 49248.27 20-FEB-15:40 388031.90 26-FEB-17:03 24.72 18.36 15.27
March 0.388872E+11 744.00 49248.27 14-MAR-11:20 646691.25 31-MAR-24:00 27.64 18.34 15.27
April 0.830388E+11 720.00 49248.27 01-APR-11:00 704416.63 16-APR-18:02 31.47 19.19 15.27
May 0.529467E+11 744.00 49248.27 02-MAY-10:20 365843.25 31-MAY-24:00 23.16 19.26 15.27
June 0.103297E+12 720.00 49248.27 01-JUN-00:10 527592.67 30-JUN-23:23 29.08 22.14 15.27
July 0.127795E+12 744.00 49248.27 01-JUL-00:10 685546.55 31-JUL-23:53 36.33 26.39 15.27
August 0.129383E+12 744.00 49248.27 01-AUG-00:03 758305.36 05-AUG-19:32 39.15 26.45 15.27
September 0.754299E+11 720.00 49248.27 01-SEP-00:02 354011.72 30-SEP-24:00 24.70 20.68 15.27
October 0.612386E+11 744.00 49248.27 02-OCT-13:20 498866.79 31-OCT-24:00 25.60 18.89 15.27
November 0.527401E+11 720.00 49248.27 01-NOV-10:55 528948.10 03-NOV-16:00 27.83 18.44 15.27
December 0.425046E+11 744.00 49248.27 05-DEC-12:00 664886.19 06-DEC-16:10 30.31 18.34 15.27
                   
Annual Sum or Average 0.797316E+12 8760.00         28.51 20.42 15.27
Minimum of Months 0.852750E+10 672.00 7432.49   203101.59   21.70 18.33 15.27
Maximum of Months 0.129383E+12 744.00 49248.27   758305.36   39.15 26.45 15.27



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 191173.26 25-JAN-05:42 21.07 21.07 0.09
February 941504.01 4.42 115.63 27-FEB-15:30 495057.03 27-FEB-15:30 21.12 21.10 0.77
March 0.00 0.00 0.00 01-MAR-00:10 191627.80 01-MAR-07:00 20.94 20.94 0.24
April 96409501.18 51.90 4316.63 06-APR-16:00 932905.12 06-APR-16:00 21.09 20.96 5.46
May 0.856993E+09 136.62 17096.89 19-MAY-14:00 1140795.38 19-MAY-14:40 21.58 21.20 12.11
June 0.508526E+10 308.94 17096.89 06-JUN-14:30 1149349.02 29-JUN-10:30 22.26 21.19 26.65
July 0.100561E+11 429.86 17096.89 01-JUL-13:10 1150417.08 26-JUL-09:10 22.81 21.18 36.03
August 0.687636E+10 379.01 17096.89 05-AUG-11:30 1148781.70 04-AUG-12:20 22.54 21.10 33.06
September 0.368884E+10 232.48 17096.89 02-SEP-10:20 1281217.20 07-SEP-15:00 22.01 21.24 20.52
October 0.256790E+09 72.24 5085.01 18-OCT-15:00 988793.45 18-OCT-12:20 21.29 21.08 7.53
November 466860.52 8.33 38.12 17-NOV-17:00 240598.81 17-NOV-17:00 20.99 20.97 1.39
December 0.00 0.00 0.00 01-DEC-00:10 191554.18 20-DEC-07:00 21.00 21.00 0.09
                   
Annual Sum or Average 0.269181E+11 1623.81         21.56 21.09 12.07
Minimum of Months 0.00 0.00 0.00   191173.26   20.94 20.94 0.09
Maximum of Months 0.100561E+11 429.86 17096.89   1281217.20   22.81 21.24 36.03



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.07 21.07 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.12 21.12 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.94 20.94 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.09 21.09 0.00
May 0.213744E+09 5.50 17096.89 19-MAY-14:00 1140795.38 19-MAY-14:40 21.58 21.55 0.41
June 0.236423E+10 55.67 17096.89 06-JUN-14:30 1149349.02 29-JUN-10:30 22.26 21.94 4.28
July 0.557953E+10 120.33 17096.89 10-JUL-15:00 1150417.08 26-JUL-09:10 22.81 22.13 8.94
August 0.390911E+10 97.50 17096.89 05-AUG-12:20 1148781.70 04-AUG-12:20 22.54 21.99 7.25
September 0.152623E+10 31.17 17096.89 02-SEP-10:20 1281217.20 07-SEP-15:00 22.01 21.82 2.39
October 34719445.08 2.00 5085.01 18-OCT-15:00 988793.45 18-OCT-12:20 21.29 21.28 0.15
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.99 20.99 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.00 21.00 0.00
                   
Annual Sum or Average 0.136276E+11 312.16         21.56 21.41 1.97
Minimum of Months 0.00 0.00 0.00   0.00   20.94 20.94 0.00
Maximum of Months 0.557953E+10 120.33 17096.89   1281217.20   22.81 22.13 8.94



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.128569E+13 0.00 604.50 2527902.40 09-JAN-07:02 0.00 37.11 72.75 3.08 0.00 0.14 0.74 09-JAN-07:02
February 0.733416E+12 0.00 463.71 2015123.65 01-FEB-07:03 0.00 33.25 65.98 1.73 0.00 0.09 0.59 01-FEB-07:03
March 0.490776E+12 0.00 458.69 1911868.99 06-MAR-05:01 0.00 30.43 61.78 0.94 0.00 0.05 0.56 06-MAR-05:01
April 0.165613E+12 0.00 279.77 1281219.27 29-APR-05:01 0.00 26.90 47.93 0.29 0.00 0.02 0.38 29-APR-05:01
May 0.110376E+12 0.00 207.74 1451349.99 22-MAY-04:01 0.00 26.44 41.53 0.19 0.00 0.01 0.43 22-MAY-04:01
June 0.835304E+10 0.00 53.58 342073.22 16-JUN-06:10 0.00 23.72 27.99 0.01 0.00 0.00 0.10 16-JUN-06:10
July 0.187934E+09 0.00 5.88 56890.50 08-JUL-06:10 0.00 23.04 23.51 0.00 0.00 0.00 0.02 08-JUL-06:10
August 0.254773E+10 0.00 29.18 151553.94 18-AUG-06:05 0.00 23.13 25.43 0.00 0.00 0.00 0.04 18-AUG-06:05
September 0.374813E+11 0.00 129.38 740681.87 19-SEP-05:03 0.00 24.24 34.38 0.06 0.00 0.00 0.22 19-SEP-05:03
October 0.128495E+12 0.00 270.54 1275256.03 11-OCT-05:01 0.00 25.71 45.72 0.22 0.00 0.01 0.37 11-OCT-05:01
November 0.388385E+12 0.00 432.20 1661552.86 27-NOV-06:01 0.00 29.02 60.31 0.74 0.00 0.04 0.49 27-NOV-06:01
December 0.885195E+12 0.00 566.81 2057964.46 29-DEC-07:03 0.00 34.19 70.20 1.89 0.00 0.10 0.60 29-DEC-07:03
                           
Annual Sum or Average 0.423652E+13 0.00 3501.98     0.00 28.08 48.04 0.76 0.00 0.04    
Minimum of Months 0.187934E+09 0.00 5.88 56890.50   0.00 23.04 23.51 0.00 0.00 0.00 0.02  
Maximum of Months 0.128569E+13 0.00 604.50 2527902.40   0.00 37.11 72.75 3.08 0.00 0.14 0.74  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.70 21.70 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.72 24.72 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.64 27.64 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 31.47 31.47 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 23.16 23.16 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 29.08 29.08 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 36.33 36.33 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 39.15 39.15 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:02 0.00 24.70 24.70 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 25.60 25.60 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 27.83 27.83 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.31 30.31 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 28.51 28.51 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.70 21.70 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 39.15 39.15 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.668222E+09 0.00 11.73 0.668222E+09 0.00 0.00 0.00 0.00 44378.93 27-FEB-15:30 44378.93 27-FEB-15:30 0.00 0.00 0.00
March 47762575.90 0.00 4.24 47762575.90 0.00 0.00 0.00 0.00 9966.38 14-MAR-13:30 9966.38 14-MAR-13:30 0.00 0.00 0.00
April 0.684875E+10 0.00 77.90 0.684875E+10 0.00 0.00 0.00 0.00 86545.32 07-APR-14:00 86545.32 07-APR-14:00 0.00 0.00 0.00
May 0.187044E+11 0.00 168.39 0.187044E+11 0.00 0.00 0.00 0.00 117249.50 19-MAY-15:20 117249.50 19-MAY-15:20 0.00 0.00 0.00
June 0.621322E+11 0.00 349.79 0.620638E+11 0.00 0.00 0.00 0.00 137820.64 29-JUN-14:50 137820.64 29-JUN-14:50 0.00 0.00 0.00
July 0.106594E+12 0.00 481.39 0.106443E+12 0.00 0.00 0.00 0.00 164290.46 17-JUL-15:40 164290.46 17-JUL-15:40 0.00 0.00 0.00
August 0.982073E+11 0.00 471.61 0.982073E+11 0.00 0.00 0.00 0.00 162762.80 07-AUG-15:20 162762.80 07-AUG-15:20 0.00 0.00 0.00
September 0.400732E+11 0.00 260.48 0.386793E+11 0.00 0.00 0.00 0.00 201959.36 07-SEP-15:00 129958.33 01-SEP-16:00 0.00 0.00 0.00
October 0.108484E+11 0.00 111.98 0.108484E+11 0.00 0.00 0.00 0.00 103923.85 18-OCT-15:50 103923.85 18-OCT-15:50 0.00 0.00 0.00
November 0.603942E+09 0.00 23.07 0.603942E+09 0.00 0.00 0.00 0.00 19068.72 17-NOV-17:00 19068.72 17-NOV-17:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.344728E+12 0.00 1960.59 0.343114E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.106594E+12 0.00 481.39 0.106443E+12 0.00 0.00 0.00 0.00 201959.36   164290.46   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 12346.86 0.00 7.61 12346.86 0.00 0.00 0.00 0.00 3.72 02-JAN-05:24 3.72 02-JAN-05:24 0.00 0.00 0.00
February 0.481262E+10 0.00 20.77 0.481262E+10 0.00 0.00 0.00 0.00 317620.76 27-FEB-13:50 317620.76 27-FEB-13:50 0.00 0.00 0.00
March 0.149095E+09 0.00 18.35 0.149095E+09 0.00 0.00 0.00 0.00 45260.37 14-MAR-13:30 45260.37 14-MAR-13:30 0.00 0.00 0.00
April 0.487552E+11 0.00 89.23 0.487552E+11 0.00 0.00 0.00 0.00 668693.39 06-APR-16:00 668693.39 06-APR-16:00 0.00 0.00 0.00
May 0.159328E+12 0.00 172.60 0.159328E+12 0.00 0.00 0.00 0.00 1124859.96 19-MAY-15:20 1124859.96 19-MAY-15:20 0.00 0.00 0.00
June 0.531036E+12 0.00 328.73 0.530444E+12 0.00 0.00 0.00 0.00 1312498.82 29-JUN-14:50 1312498.82 29-JUN-14:50 0.00 0.00 0.00
July 0.891038E+12 0.00 418.93 0.890185E+12 0.00 0.00 0.00 0.00 1518576.57 17-JUL-15:40 1518576.57 17-JUL-15:40 0.00 0.00 0.00
August 0.771346E+12 0.00 391.58 0.771346E+12 0.00 0.00 0.00 0.00 1410966.27 10-AUG-15:40 1410966.27 10-AUG-15:40 0.00 0.00 0.00
September 0.351058E+12 0.00 255.67 0.338388E+12 0.00 0.00 0.00 0.00 1874627.15 07-SEP-15:00 1194643.76 01-SEP-16:00 0.00 0.00 0.00
October 0.856662E+11 0.00 115.95 0.856662E+11 0.00 0.00 0.00 0.00 885272.71 18-OCT-15:10 885272.71 18-OCT-15:10 0.00 0.00 0.00
November 0.429216E+10 0.00 37.63 0.429216E+10 0.00 0.00 0.00 0.00 152718.07 03-NOV-14:00 152718.07 03-NOV-14:00 0.00 0.00 0.00
December 18227.04 0.00 6.60 18227.04 0.00 0.00 0.00 0.00 4.72 14-DEC-05:01 4.72 14-DEC-05:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.284748E+13 0.00 1863.66 0.283337E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 12346.86 0.00 6.60 12346.86 0.00 0.00 0.00 0.00 3.72   3.72   0.00 0.00 0.00
Maximum of Months 0.891038E+12 0.00 418.93 0.890185E+12 0.00 0.00 0.00 0.00 1874627.15   1518576.57   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2274.08 0.00 1.91 2274.08 0.00 0.00 0.00 0.00 0.71 11-JAN-06:08 0.71 11-JAN-06:08 0.00 0.00 0.00
February 0.324425E+09 0.00 11.96 0.324425E+09 0.00 0.00 0.00 0.00 21826.99 27-FEB-15:30 21826.99 27-FEB-15:30 0.00 0.00 0.00
March 2489376.22 0.00 1.85 2489376.22 0.00 0.00 0.00 0.00 696.31 14-MAR-14:00 696.31 14-MAR-14:00 0.00 0.00 0.00
April 0.450198E+10 0.00 65.60 0.450198E+10 0.00 0.00 0.00 0.00 66876.09 06-APR-16:00 66876.09 06-APR-16:00 0.00 0.00 0.00
May 0.163879E+11 0.00 153.52 0.163879E+11 0.00 0.00 0.00 0.00 132937.35 19-MAY-15:30 132937.35 19-MAY-15:30 0.00 0.00 0.00
June 0.578964E+11 0.00 319.84 0.578252E+11 0.00 0.00 0.00 0.00 155101.84 29-JUN-15:00 155101.84 29-JUN-15:00 0.00 0.00 0.00
July 0.981358E+11 0.00 418.35 0.980708E+11 0.00 0.00 0.00 0.00 185803.12 17-JUL-15:30 185803.12 17-JUL-15:30 0.00 0.00 0.00
August 0.826728E+11 0.00 380.57 0.826728E+11 0.00 0.00 0.00 0.00 167623.81 07-AUG-15:50 167623.81 07-AUG-15:50 0.00 0.00 0.00
September 0.357250E+11 0.00 242.52 0.344700E+11 0.00 0.00 0.00 0.00 191018.01 07-SEP-15:20 136230.45 01-SEP-16:00 0.00 0.00 0.00
October 0.731607E+10 0.00 94.02 0.731607E+10 0.00 0.00 0.00 0.00 90887.39 18-OCT-15:00 90887.39 18-OCT-15:00 0.00 0.00 0.00
November 0.304082E+09 0.00 17.37 0.304082E+09 0.00 0.00 0.00 0.00 11133.88 17-NOV-17:00 11133.88 17-NOV-17:00 0.00 0.00 0.00
December 10175.89 0.00 1.64 10175.89 0.00 0.00 0.00 0.00 69.91 04-DEC-04:46 69.91 04-DEC-04:46 0.00 0.00 0.00
                               
Annual Sum or Average 0.303267E+12 0.00 1709.15 0.301876E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 2274.08 0.00 1.64 2274.08 0.00 0.00 0.00 0.00 0.71   0.71   0.00 0.00 0.00
Maximum of Months 0.981358E+11 0.00 418.35 0.980708E+11 0.00 0.00 0.00 0.00 191018.01   185803.12   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.282783E+09 0.00 5.17 0.282783E+09 0.00 0.00 0.00 0.00 24820.80 27-FEB-15:00 24820.80 27-FEB-15:00 0.00 0.00 0.00
March 13603.64 0.00 0.17 13603.64 0.00 0.00 0.00 0.00 22.67 07-MAR-19:50 22.67 07-MAR-19:50 0.00 0.00 0.00
April 0.245389E+10 0.00 38.46 0.245389E+10 0.00 0.00 0.00 0.00 50035.33 07-APR-14:00 50035.33 07-APR-14:00 0.00 0.00 0.00
May 0.921493E+10 0.00 107.02 0.921493E+10 0.00 0.00 0.00 0.00 79182.78 29-MAY-15:02 79182.78 29-MAY-15:02 0.00 0.00 0.00
June 0.318869E+11 0.00 234.94 0.318637E+11 0.00 0.00 0.00 0.00 68420.25 26-JUN-11:00 68420.25 26-JUN-11:00 0.00 0.00 0.00
July 0.540153E+11 0.00 324.91 0.539751E+11 0.00 0.00 0.00 0.00 119516.51 19-JUL-03:02 89279.45 25-JUL-05:03 0.00 0.00 0.00
August 0.502708E+11 0.00 320.86 0.502698E+11 0.00 0.00 0.00 0.00 105211.96 06-AUG-15:54 105211.96 06-AUG-15:54 0.00 0.00 0.00
September 0.210305E+11 0.00 186.58 0.206158E+11 0.00 0.00 0.00 0.00 109241.30 04-SEP-08:62 109241.30 04-SEP-08:62 0.00 0.00 0.00
October 0.595290E+10 0.00 62.91 0.595290E+10 0.00 0.00 0.00 0.00 60329.65 18-OCT-14:00 60329.65 18-OCT-14:00 0.00 0.00 0.00
November 91667054.30 0.00 5.56 91667054.30 0.00 0.00 0.00 0.00 28477.05 17-NOV-06:03 28477.05 17-NOV-06:03 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.175200E+12 0.00 1286.57 0.174721E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.540153E+11 0.00 324.91 0.539751E+11 0.00 0.00 0.00 0.00 119516.51   109241.30   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.361909E+12 0.918933E+11 744.00 0.328250E+12 0.336590E+11 0.00 0.36 03-JAN-22:02 0.30 09-JAN-07:02 142962.30 18-JAN-22:01 129776.17 02-JAN-22:03 13975.31 18-JAN-22:01 35976.58 03-JAN-22:02 0.00
February 0.575784E+12 0.138535E+12 672.00 0.522013E+12 0.537706E+11 0.00 0.59 27-FEB-16:00 0.54 01-FEB-07:07 245399.65 27-FEB-22:03 222167.03 28-FEB-22:03 23908.25 05-FEB-00:52 66479.59 27-FEB-16:00 0.00
March 0.910685E+12 0.209937E+12 744.00 0.827825E+12 0.828603E+11 0.00 0.98 31-MAR-24:00 0.76 06-MAR-07:07 440877.89 31-MAR-24:00 400397.01 31-MAR-24:00 40480.88 31-MAR-24:00 97771.73 31-MAR-24:00 0.00
April 0.114524E+13 0.261602E+12 720.00 0.104328E+13 0.101963E+12 0.00 1.00 06-APR-09:50 0.39 30-APR-23:55 449754.83 24-APR-21:02 407582.13 06-APR-22:55 44491.16 21-APR-16:00 132384.94 07-APR-14:00 0.00
May 0.375786E+12 0.982122E+11 744.00 0.342806E+12 0.329792E+11 0.00 0.58 31-MAY-23:40 0.33 08-MAY-06:10 238081.21 31-MAY-24:00 217599.45 31-MAY-24:00 20481.75 31-MAY-24:00 59590.13 31-MAY-23:20 0.00
June 0.620356E+12 0.169495E+12 720.00 0.573415E+12 0.469411E+11 0.00 0.80 30-JUN-23:12 0.57 01-JUN-06:10 330267.18 30-JUN-23:02 309528.14 30-JUN-24:00 23537.06 01-JUN-19:00 95880.63 30-JUN-23:12 0.00
July 0.894926E+12 0.267645E+12 744.00 0.842158E+12 0.527680E+11 0.00 1.00 31-JUL-23:02 0.78 08-JUL-06:10 427134.26 31-JUL-24:00 400795.34 31-JUL-23:55 34342.70 05-JUL-09:00 149972.76 17-JUL-16:00 0.00
August 0.116139E+13 0.326789E+12 744.00 0.108102E+13 0.803694E+11 0.00 1.00 01-AUG-00:03 0.41 31-AUG-24:00 456799.34 04-AUG-00:25 412535.18 12-AUG-04:57 47258.71 01-AUG-21:00 167703.01 06-AUG-16:00 0.00
September 0.366932E+12 0.100654E+12 720.00 0.336771E+12 0.301608E+11 0.00 0.57 30-SEP-24:00 0.34 18-SEP-07:00 238747.67 30-SEP-24:00 217327.62 30-SEP-24:00 21420.06 30-SEP-24:00 59151.55 02-SEP-17:00 0.00
October 0.649209E+12 0.158745E+12 744.00 0.590738E+12 0.584707E+11 0.00 0.78 31-OCT-24:00 0.56 10-OCT-06:10 340967.62 31-OCT-24:00 309926.37 31-OCT-24:00 31041.25 31-OCT-24:00 79056.67 18-OCT-15:00 0.00
November 0.889825E+12 0.205428E+12 720.00 0.806765E+12 0.830605E+11 0.00 0.81 17-NOV-17:00 0.77 27-NOV-07:10 349084.27 06-NOV-22:03 315595.10 06-NOV-22:03 34458.66 03-NOV-08:00 89793.90 17-NOV-17:00 0.00
December 0.118270E+13 0.262986E+12 744.00 0.107455E+13 0.108156E+12 0.00 0.99 07-DEC-24:00 0.96 30-DEC-07:10 448640.98 07-DEC-24:00 407066.75 07-DEC-22:03 43518.89 16-DEC-17:00 104955.46 10-DEC-02:00 0.00
                                       
Annual Sum or Average 0.913475E+13 0.229192E+13 8760.00 0.836959E+13 0.765160E+12 0.00                         0.00
Minimum of Months 0.361909E+12 0.918933E+11 672.00 0.328250E+12 0.301608E+11 0.00 0.36   0.30   142962.30   129776.17   13975.31   35976.58   0.00
Maximum of Months 0.118270E+13 0.326789E+12 744.00 0.108102E+13 0.108156E+12 0.00 1.00   0.96   456799.34   412535.18   47258.71   167703.01   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.289943E+10 0.833422E+09 730.24 0.289911E+10 320542.28 0.00 0.27 13-JAN-16:20 0.00 07-JAN-23:35 2188.32 13-JAN-16:20 2188.32 13-JAN-16:20 12.58 02-JAN-07:10 572.95 13-JAN-16:20 0.00
February 0.819962E+10 0.215724E+10 672.00 0.819962E+10 -0.0 0.00 0.58 26-FEB-17:03 0.27 01-FEB-07:03 4834.21 26-FEB-17:14 4834.21 26-FEB-17:14 0.00 06-FEB-18:10 1270.74 26-FEB-16:53 0.00
March 0.148985E+11 0.368919E+10 744.00 0.148985E+11 0.00 0.00 0.82 31-MAR-24:00 0.53 06-MAR-07:03 7467.03 31-MAR-24:00 7467.03 31-MAR-24:00 0.00 15-MAR-18:10 1757.71 31-MAR-24:00 0.00
April 0.199971E+11 0.481875E+10 720.00 0.199896E+11 7462423.50 0.00 1.00 16-APR-17:02 0.30 30-APR-23:55 8873.66 22-APR-18:10 8873.66 22-APR-18:10 128.66 17-APR-16:10 2690.34 07-APR-14:00 0.00
May 0.559262E+10 0.152687E+10 744.00 0.557105E+10 21573746.09 0.00 0.48 31-MAY-24:00 0.14 08-MAY-06:40 4139.15 31-MAY-24:00 4139.15 31-MAY-24:00 138.95 30-MAY-09:10 1072.47 31-MAY-23:30 0.00
June 0.108705E+11 0.303130E+10 720.00 0.107904E+11 80149531.40 0.00 0.68 30-JUN-23:12 0.39 17-JUN-06:40 5991.51 30-JUN-24:00 5991.51 30-JUN-24:00 305.37 06-JUN-16:50 1871.40 29-JUN-15:00 0.00
July 0.165395E+11 0.501897E+10 744.00 0.164503E+11 89209286.81 0.00 0.89 16-JUL-18:45 0.62 08-JUL-06:20 7871.64 31-JUL-23:35 7871.64 31-JUL-23:35 313.07 03-JUL-17:00 3051.04 17-JUL-16:00 0.00
August 0.215283E+11 0.632577E+10 744.00 0.214652E+11 63083612.30 0.00 1.00 03-AUG-18:10 0.31 31-AUG-24:00 8850.50 05-AUG-20:12 8850.50 05-AUG-20:12 368.35 22-AUG-16:00 3594.90 06-AUG-16:00 0.00
September 0.567817E+10 0.160752E+10 720.00 0.559615E+10 82010846.27 0.00 0.46 30-SEP-24:00 0.16 19-SEP-07:00 3948.60 30-SEP-24:00 3948.60 30-SEP-24:00 344.91 07-SEP-15:30 1349.60 04-SEP-17:21 0.00
October 0.105001E+11 0.266959E+10 744.00 0.104895E+11 10523962.02 0.00 0.65 31-OCT-24:00 0.36 10-OCT-06:40 5598.15 31-OCT-24:00 5598.15 31-OCT-24:00 111.43 25-OCT-11:00 1565.40 15-OCT-16:43 0.00
November 0.145875E+11 0.358023E+10 720.00 0.145858E+11 1686766.53 0.00 0.72 12-NOV-16:13 0.54 27-NOV-07:10 6496.40 03-NOV-16:00 6461.92 12-NOV-16:17 83.70 08-NOV-15:20 1649.26 17-NOV-16:50 0.00
December 0.194587E+11 0.471474E+10 744.00 0.194584E+11 217433.99 0.00 0.91 10-DEC-16:05 0.74 29-DEC-07:03 8260.01 10-DEC-16:10 8260.01 10-DEC-16:10 49.64 19-DEC-17:05 1977.14 10-DEC-02:00 0.00
                                       
Annual Sum or Average 0.150750E+12 0.399736E+11 8746.24 0.150394E+12 0.356238E+09 0.00                         0.00
Minimum of Months 0.289943E+10 0.833422E+09 672.00 0.289911E+10 -0.0 0.00 0.27   0.00   2188.32   2188.32   0.00   572.95   0.00
Maximum of Months 0.215283E+11 0.632577E+10 744.00 0.214652E+11 89209286.81 0.00 1.00   0.74   8873.66   8873.66   368.35   3594.90   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.830672E+10 0.260027E+10 481.53 0.830364E+10 3080852.31 0.00 0.23 13-JAN-16:30 0.00 01-JAN-04:13 18012.41 13-JAN-16:30 18012.41 13-JAN-16:30 136.33 01-JAN-15:45 4771.78 13-JAN-16:30 0.00
February 0.591940E+11 0.159276E+11 672.00 0.591940E+11 -0.0 0.00 0.52 26-FEB-17:23 0.13 06-FEB-04:01 42648.69 28-FEB-17:00 42648.69 28-FEB-17:00 0.00 23-FEB-16:20 11465.36 27-FEB-16:00 0.00
March 0.124458E+12 0.312592E+11 744.00 0.124458E+12 -0.0 0.00 0.76 31-MAR-23:30 0.37 06-MAR-07:03 65300.66 31-MAR-23:30 65300.66 31-MAR-23:30 0.00 26-MAR-09:45 15558.23 31-MAR-23:30 0.00
April 0.179736E+12 0.437101E+11 720.00 0.179659E+12 76457861.13 0.00 1.00 16-APR-17:42 0.14 30-APR-24:00 82415.87 25-APR-18:00 82415.87 25-APR-18:00 1282.90 17-APR-16:10 25471.81 07-APR-14:00 0.00
May 0.453476E+11 0.125618E+11 744.00 0.451359E+11 0.211737E+09 0.00 0.48 31-MAY-24:00 0.03 08-MAY-06:10 39148.00 31-MAY-24:00 39148.00 31-MAY-24:00 1329.36 30-MAY-09:10 10167.55 31-MAY-23:30 0.00
June 0.100138E+12 0.280845E+11 720.00 0.993392E+11 0.798828E+09 0.00 0.69 30-JUN-23:12 0.34 17-JUN-06:10 58470.88 30-JUN-24:00 58470.88 30-JUN-24:00 2991.54 06-JUN-16:50 17822.99 29-JUN-15:00 0.00
July 0.156279E+12 0.475346E+11 744.00 0.155387E+12 0.892314E+09 0.00 0.89 31-JUL-23:12 0.59 08-JUL-06:30 76721.69 31-JUL-23:55 76721.69 31-JUL-23:55 3073.67 03-JUL-17:00 29046.84 17-JUL-16:00 0.00
August 0.202432E+12 0.596950E+11 744.00 0.201800E+12 0.632379E+09 0.00 1.00 03-AUG-18:20 0.27 31-AUG-24:00 84091.67 03-AUG-19:00 84091.67 03-AUG-19:00 3616.71 22-AUG-16:00 34390.74 06-AUG-16:00 0.00
September 0.479241E+11 0.137675E+11 720.00 0.471217E+11 0.802370E+09 0.00 0.43 04-SEP-17:31 0.10 19-SEP-06:10 34913.64 30-SEP-23:40 34913.64 30-SEP-23:40 3444.63 07-SEP-15:30 12696.48 04-SEP-17:21 0.00
October 0.877932E+11 0.226271E+11 744.00 0.876879E+11 0.105298E+09 0.00 0.59 31-OCT-24:00 0.25 10-OCT-06:10 47671.08 31-OCT-24:00 47671.08 31-OCT-24:00 1092.09 25-OCT-11:00 14495.09 18-OCT-16:00 0.00
November 0.120788E+12 0.301158E+11 720.00 0.120770E+12 17602132.04 0.00 0.69 03-NOV-16:00 0.37 27-NOV-07:10 59983.80 03-NOV-16:00 59435.75 03-NOV-16:00 833.91 08-NOV-15:20 15242.55 17-NOV-17:00 0.00
December 0.158815E+12 0.392489E+11 744.00 0.158812E+12 3034038.54 0.00 0.83 12-DEC-16:00 0.56 31-DEC-23:55 74768.39 06-DEC-16:10 74485.33 06-DEC-16:10 527.58 19-DEC-17:05 17037.18 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.129121E+13 0.347133E+12 8497.53 0.128767E+13 0.354310E+10 0.00                         0.00
Minimum of Months 0.830672E+10 0.260027E+10 481.53 0.830364E+10 -0.0 0.00 0.23   0.00   18012.41   18012.41   0.00   4771.78   0.00
Maximum of Months 0.202432E+12 0.596950E+11 744.00 0.201800E+12 0.892314E+09 0.00 1.00   0.59   84091.67   84091.67   3616.71   34390.74   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.230045E+09 74414483.78 168.13 0.230045E+09 -0.0 0.00 0.22 13-JAN-16:30 0.00 01-JAN-00:05 1717.40 13-JAN-16:30 1717.40 13-JAN-16:30 0.00 14-JAN-17:10 457.59 13-JAN-16:30 0.00
February 0.427029E+10 0.117250E+10 649.96 0.427029E+10 -0.0 0.00 0.50 28-FEB-17:00 0.00 04-FEB-02:42 4220.91 28-FEB-17:00 4220.91 28-FEB-17:00 0.00 07-FEB-15:50 1127.87 27-FEB-16:00 0.00
March 0.108040E+11 0.275025E+10 744.00 0.108040E+11 -0.0 0.00 0.72 28-MAR-17:50 0.19 06-MAR-04:02 6164.11 28-MAR-17:50 6164.11 28-MAR-17:50 0.00 10-MAR-05:20 1493.82 28-MAR-17:50 0.00
April 0.168079E+11 0.413369E+10 719.00 0.168004E+11 7519061.60 0.00 0.97 16-APR-17:51 0.00 30-APR-23:05 8308.89 25-APR-18:00 8308.89 25-APR-18:00 127.12 17-APR-16:10 2556.73 07-APR-14:00 0.00
May 0.386146E+10 0.108238E+10 691.95 0.384062E+10 20836967.62 0.00 0.46 31-MAY-23:40 0.00 01-MAY-00:10 3843.15 31-MAY-24:00 3843.15 31-MAY-24:00 128.78 30-MAY-09:20 1003.49 31-MAY-23:20 0.00
June 0.980741E+10 0.276982E+10 720.00 0.972772E+10 79691191.06 0.00 0.68 30-JUN-23:12 0.25 17-JUN-06:10 5857.38 30-JUN-24:00 5857.38 30-JUN-24:00 301.51 06-JUN-16:50 1821.31 29-JUN-15:00 0.00
July 0.155838E+11 0.476269E+10 744.00 0.154948E+11 89067702.31 0.00 0.91 16-JUL-18:45 0.54 08-JUL-06:30 7631.69 31-JUL-23:55 7631.69 31-JUL-23:55 308.14 03-JUL-17:00 2972.71 17-JUL-16:00 0.00
August 0.201183E+11 0.596379E+10 744.00 0.200552E+11 63090107.70 0.00 1.00 03-AUG-18:40 0.26 31-AUG-24:00 8557.07 05-AUG-19:57 8557.07 05-AUG-19:57 362.92 22-AUG-16:00 3501.49 06-AUG-16:00 0.00
September 0.425735E+10 0.124689E+10 718.78 0.417828E+10 79068868.71 0.00 0.45 04-SEP-17:21 0.00 12-SEP-03:43 3403.05 04-SEP-17:32 3403.05 04-SEP-17:32 347.23 07-SEP-15:30 1378.96 04-SEP-17:21 0.00
October 0.739448E+10 0.193847E+10 744.00 0.738418E+10 10298093.99 0.00 0.56 18-OCT-16:50 0.09 10-OCT-03:20 4565.94 18-OCT-16:50 4565.94 18-OCT-16:50 108.23 25-OCT-11:00 1460.81 18-OCT-16:00 0.00
November 0.101922E+11 0.258459E+10 720.00 0.101905E+11 1713153.61 0.00 0.67 03-NOV-16:00 0.19 27-NOV-04:23 5935.38 03-NOV-16:00 5880.69 03-NOV-16:00 82.62 08-NOV-15:20 1502.47 17-NOV-16:50 0.00
December 0.138238E+11 0.347260E+10 744.00 0.138235E+11 263218.83 0.00 0.81 06-DEC-16:10 0.40 31-DEC-23:55 7386.01 06-DEC-16:10 7359.70 06-DEC-16:10 49.97 19-DEC-17:05 1689.66 06-DEC-16:10 0.00
                                       
Annual Sum or Average 0.117151E+12 0.319521E+11 8107.81 0.116800E+12 0.351548E+09 0.00                         0.00
Minimum of Months 0.230045E+09 74414483.78 168.13 0.230045E+09 -0.0 0.00 0.22   0.00   1717.40   1717.40   0.00   457.59   0.00
Maximum of Months 0.201183E+11 0.596379E+10 744.00 0.200552E+11 89067702.31 0.00 1.00   0.54   8557.07   8557.07   362.92   3501.49   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.47 794.59 0.00 0.00 0.00
February 127.65 0.00 127.65 15.34 599.63 0.00 0.00 0.00
March 207.35 0.00 207.35 61.97 489.05 0.00 0.00 0.00
April 236.43 1.38 235.05 115.20 351.27 0.00 0.00 0.00
May 310.49 18.40 292.09 225.01 253.75 0.00 0.00 0.00
June 361.54 41.56 319.99 366.75 158.89 0.00 0.00 0.00
July 330.29 30.94 299.35 398.66 130.67 0.00 0.00 0.00
August 264.66 7.09 257.57 288.48 151.13 0.00 0.00 0.00
September 198.21 0.07 198.14 167.38 235.46 0.00 0.00 0.00
October 144.59 0.00 144.59 58.23 361.27 0.00 0.00 0.00
November 98.29 0.00 98.29 11.43 523.54 0.00 0.00 0.00
December 75.81 0.00 75.81 0.46 709.68 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.33 395.78 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.46 130.67 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.99 398.66 794.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.47 794.59 0.00 0.00 0.00
February 127.64 0.00 127.64 15.33 599.63 0.00 0.00 0.00
March 207.35 0.00 207.35 61.96 489.05 0.00 0.00 0.00
April 236.42 1.38 235.04 115.19 351.27 0.00 0.00 0.00
May 310.48 18.40 292.08 225.01 253.75 0.00 0.00 0.00
June 361.54 41.56 319.98 366.74 158.89 0.00 0.00 0.00
July 330.29 30.93 299.35 398.65 130.67 0.00 0.00 0.00
August 264.66 7.09 257.57 288.48 151.13 0.00 0.00 0.00
September 198.21 0.07 198.14 167.37 235.46 0.00 0.00 0.00
October 144.58 0.00 144.58 58.22 361.27 0.00 0.00 0.00
November 98.29 0.00 98.29 11.43 523.54 0.00 0.00 0.00
December 75.81 0.00 75.81 0.46 709.68 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.32 395.78 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.46 130.67 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.65 794.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.47 794.59 0.00 0.00 0.00
February 127.64 0.00 127.64 15.33 599.63 0.00 0.00 0.00
March 207.35 0.00 207.35 61.97 489.05 0.00 0.00 0.00
April 236.43 1.38 235.05 115.20 351.27 0.00 0.00 0.00
May 310.48 18.40 292.08 225.01 253.75 0.00 0.00 0.00
June 361.54 41.56 319.98 366.74 158.89 0.00 0.00 0.00
July 330.29 30.93 299.35 398.66 130.67 0.00 0.00 0.00
August 264.66 7.09 257.57 288.48 151.13 0.00 0.00 0.00
September 198.21 0.07 198.14 167.37 235.46 0.00 0.00 0.00
October 144.58 0.00 144.58 58.22 361.27 0.00 0.00 0.00
November 98.29 0.00 98.29 11.43 523.54 0.00 0.00 0.00
December 75.81 0.00 75.81 0.46 709.68 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.33 395.78 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.46 130.67 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.66 794.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.47 794.59 0.00 0.00 0.00
February 127.64 0.00 127.64 15.33 599.63 0.00 0.00 0.00
March 207.35 0.00 207.35 61.96 489.05 0.00 0.00 0.00
April 236.42 1.38 235.04 115.19 351.27 0.00 0.00 0.00
May 310.48 18.40 292.08 225.01 253.75 0.00 0.00 0.00
June 361.54 41.56 319.98 366.74 158.89 0.00 0.00 0.00
July 330.29 30.93 299.35 398.65 130.67 0.00 0.00 0.00
August 264.66 7.09 257.57 288.48 151.13 0.00 0.00 0.00
September 198.21 0.07 198.14 167.37 235.46 0.00 0.00 0.00
October 144.58 0.00 144.58 58.22 361.27 0.00 0.00 0.00
November 98.29 0.00 98.29 11.43 523.54 0.00 0.00 0.00
December 75.81 0.00 75.81 0.46 709.68 0.00 0.00 0.00
                 
Annual Sum or Average 204.22 8.33 195.89 143.32 395.78 0.00 0.00 0.00
Minimum of Months 75.81 0.00 75.81 0.46 130.67 0.00 0.00 0.00
Maximum of Months 361.54 41.56 319.98 398.65 794.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.40 0.00 90.40 1.47 794.55 0.00 0.00 0.00
February 127.64 0.00 127.64 15.33 599.61 0.00 0.00 0.00
March 207.34 0.00 207.34 61.96 489.03 0.00 0.00 0.00
April 236.41 1.38 235.04 115.19 351.25 0.00 0.00 0.00
May 310.47 18.40 292.07 225.00 253.74 0.00 0.00 0.00
June 361.52 41.55 319.97 366.73 158.89 0.00 0.00 0.00
July 330.27 30.93 299.34 398.64 130.66 0.00 0.00 0.00
August 264.65 7.09 257.56 288.46 151.12 0.00 0.00 0.00
September 198.20 0.07 198.13 167.37 235.45 0.00 0.00 0.00
October 144.58 0.00 144.58 58.22 361.26 0.00 0.00 0.00
November 98.29 0.00 98.29 11.43 523.52 0.00 0.00 0.00
December 75.80 0.00 75.80 0.46 709.65 0.00 0.00 0.00
                 
Annual Sum or Average 204.21 8.33 195.88 143.32 395.76 0.00 0.00 0.00
Minimum of Months 75.80 0.00 75.80 0.46 130.66 0.00 0.00 0.00
Maximum of Months 361.52 41.55 319.97 398.64 794.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.66 105.75 124.91 118.59 805.10 0.00 0.00 0.00
February 360.77 179.11 181.66 263.74 602.05 0.00 0.00 0.00
March 485.09 200.72 284.37 389.31 497.61 0.00 0.00 0.00
April 618.92 306.73 312.19 594.79 357.85 0.00 0.00 0.00
May 683.68 304.20 379.49 707.92 278.65 0.00 0.00 0.00
June 884.94 455.39 429.55 1058.15 176.05 0.00 0.00 0.00
July 928.77 525.06 403.71 1198.54 138.70 0.00 0.00 0.00
August 807.14 449.71 357.43 1017.87 155.03 0.00 0.00 0.00
September 570.97 294.73 276.24 651.39 240.60 0.00 0.00 0.00
October 409.64 208.01 201.63 383.36 365.15 0.00 0.00 0.00
November 259.62 121.21 138.41 173.72 513.67 0.00 0.00 0.00
December 191.49 82.24 109.24 90.91 705.35 0.00 0.00 0.00
                 
Annual Sum or Average 536.89 269.87 267.02 555.69 402.24 0.00 0.00 0.00
Minimum of Months 191.49 82.24 109.24 90.91 138.70 0.00 0.00 0.00
Maximum of Months 928.77 525.06 429.55 1198.54 805.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.66 105.75 124.91 118.59 805.10 0.00 0.00 0.00
February 360.77 179.11 181.66 263.74 602.05 0.00 0.00 0.00
March 485.09 200.72 284.37 389.31 497.61 0.00 0.00 0.00
April 618.92 306.73 312.19 594.79 357.85 0.00 0.00 0.00
May 683.68 304.20 379.49 707.92 278.65 0.00 0.00 0.00
June 884.94 455.39 429.55 1058.15 176.05 0.00 0.00 0.00
July 928.77 525.06 403.71 1198.54 138.70 0.00 0.00 0.00
August 807.14 449.71 357.43 1017.87 155.03 0.00 0.00 0.00
September 570.97 294.73 276.24 651.39 240.60 0.00 0.00 0.00
October 409.64 208.01 201.63 383.36 365.15 0.00 0.00 0.00
November 259.62 121.21 138.41 173.72 513.67 0.00 0.00 0.00
December 191.49 82.24 109.24 90.91 705.35 0.00 0.00 0.00
                 
Annual Sum or Average 536.89 269.87 267.02 555.69 402.24 0.00 0.00 0.00
Minimum of Months 191.49 82.24 109.24 90.91 138.70 0.00 0.00 0.00
Maximum of Months 928.77 525.06 429.55 1198.54 805.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 230.65 105.75 124.91 118.58 805.09 0.00 0.00 0.00
February 360.76 179.11 181.65 263.74 602.04 0.00 0.00 0.00
March 485.08 200.71 284.37 389.30 497.60 0.00 0.00 0.00
April 618.91 306.73 312.18 594.78 357.84 0.00 0.00 0.00
May 683.67 304.19 379.48 707.90 278.65 0.00 0.00 0.00
June 884.92 455.38 429.54 1058.13 176.05 0.00 0.00 0.00
July 928.75 525.05 403.70 1198.52 138.70 0.00 0.00 0.00
August 807.13 449.71 357.42 1017.85 155.02 0.00 0.00 0.00
September 570.96 294.73 276.23 651.38 240.60 0.00 0.00 0.00
October 409.64 208.01 201.63 383.35 365.14 0.00 0.00 0.00
November 259.62 121.21 138.41 173.72 513.66 0.00 0.00 0.00
December 191.48 82.24 109.24 90.91 705.34 0.00 0.00 0.00
                 
Annual Sum or Average 536.88 269.87 267.02 555.68 402.23 0.00 0.00 0.00
Minimum of Months 191.48 82.24 109.24 90.91 138.70 0.00 0.00 0.00
Maximum of Months 928.75 525.05 429.54 1198.52 805.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.24 455.13 182.11 591.34 666.75 0.00 0.00 0.00
February 811.51 583.67 227.84 828.48 509.62 0.00 0.00 0.00
March 725.39 407.34 318.04 737.83 458.18 0.00 0.00 0.00
April 583.09 278.89 304.20 615.45 344.91 0.00 0.00 0.00
May 518.06 172.06 346.00 558.97 267.31 0.00 0.00 0.00
June 514.75 150.12 364.62 635.32 180.37 0.00 0.00 0.00
July 554.95 204.99 349.95 763.96 141.39 0.00 0.00 0.00
August 659.52 332.52 327.00 880.16 160.00 0.00 0.00 0.00
September 731.48 448.20 283.28 905.80 233.27 0.00 0.00 0.00
October 764.73 528.80 235.93 866.05 334.94 0.00 0.00 0.00
November 697.20 505.03 192.18 716.86 435.61 0.00 0.00 0.00
December 605.98 437.58 168.40 571.80 583.05 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.85 359.05 0.00 0.00 0.00
Minimum of Months 514.75 150.12 168.40 558.97 141.39 0.00 0.00 0.00
Maximum of Months 811.51 583.67 364.62 905.80 666.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.23 455.12 182.11 591.33 666.75 0.00 0.00 0.00
February 811.51 583.66 227.84 828.48 509.62 0.00 0.00 0.00
March 725.38 407.34 318.04 737.83 458.18 0.00 0.00 0.00
April 583.09 278.89 304.19 615.45 344.91 0.00 0.00 0.00
May 518.06 172.06 346.00 558.96 267.31 0.00 0.00 0.00
June 514.74 150.12 364.62 635.31 180.37 0.00 0.00 0.00
July 554.95 204.99 349.95 763.96 141.39 0.00 0.00 0.00
August 659.51 332.51 327.00 880.15 160.00 0.00 0.00 0.00
September 731.48 448.20 283.28 905.80 233.27 0.00 0.00 0.00
October 764.72 528.79 235.93 866.04 334.94 0.00 0.00 0.00
November 697.20 505.02 192.18 716.85 435.61 0.00 0.00 0.00
December 605.97 437.57 168.40 571.80 583.05 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.84 359.05 0.00 0.00 0.00
Minimum of Months 514.74 150.12 168.40 558.96 141.39 0.00 0.00 0.00
Maximum of Months 811.51 583.66 364.62 905.80 666.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.24 455.13 182.11 591.34 666.75 0.00 0.00 0.00
February 811.51 583.67 227.84 828.48 509.62 0.00 0.00 0.00
March 725.39 407.34 318.04 737.83 458.18 0.00 0.00 0.00
April 583.09 278.89 304.20 615.45 344.91 0.00 0.00 0.00
May 518.06 172.06 346.00 558.97 267.31 0.00 0.00 0.00
June 514.75 150.12 364.62 635.32 180.37 0.00 0.00 0.00
July 554.95 204.99 349.95 763.96 141.39 0.00 0.00 0.00
August 659.52 332.52 327.00 880.16 160.00 0.00 0.00 0.00
September 731.48 448.20 283.28 905.80 233.27 0.00 0.00 0.00
October 764.73 528.80 235.93 866.05 334.94 0.00 0.00 0.00
November 697.20 505.03 192.18 716.86 435.61 0.00 0.00 0.00
December 605.98 437.58 168.40 571.80 583.05 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.85 359.05 0.00 0.00 0.00
Minimum of Months 514.75 150.12 168.40 558.97 141.39 0.00 0.00 0.00
Maximum of Months 811.51 583.67 364.62 905.80 666.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.23 455.12 182.11 591.33 666.75 0.00 0.00 0.00
February 811.51 583.66 227.84 828.48 509.62 0.00 0.00 0.00
March 725.38 407.34 318.04 737.83 458.18 0.00 0.00 0.00
April 583.09 278.89 304.19 615.45 344.91 0.00 0.00 0.00
May 518.06 172.06 346.00 558.96 267.31 0.00 0.00 0.00
June 514.74 150.12 364.62 635.31 180.37 0.00 0.00 0.00
July 554.95 204.99 349.95 763.96 141.39 0.00 0.00 0.00
August 659.51 332.51 327.00 880.15 160.00 0.00 0.00 0.00
September 731.48 448.20 283.28 905.80 233.27 0.00 0.00 0.00
October 764.72 528.79 235.93 866.04 334.94 0.00 0.00 0.00
November 697.20 505.02 192.18 716.85 435.61 0.00 0.00 0.00
December 605.97 437.57 168.40 571.80 583.05 0.00 0.00 0.00
                 
Annual Sum or Average 649.20 373.97 275.23 721.84 359.05 0.00 0.00 0.00
Minimum of Months 514.74 150.12 168.40 558.96 141.39 0.00 0.00 0.00
Maximum of Months 811.51 583.66 364.62 905.80 666.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 637.21 455.11 182.10 591.31 666.72 0.00 0.00 0.00
February 811.48 583.64 227.83 828.45 509.60 0.00 0.00 0.00
March 725.35 407.32 318.03 737.80 458.16 0.00 0.00 0.00
April 583.06 278.88 304.18 615.42 344.90 0.00 0.00 0.00
May 518.04 172.05 345.99 558.94 267.30 0.00 0.00 0.00
June 514.72 150.12 364.61 635.29 180.36 0.00 0.00 0.00
July 554.92 204.99 349.94 763.93 141.38 0.00 0.00 0.00
August 659.49 332.50 326.99 880.12 159.99 0.00 0.00 0.00
September 731.45 448.18 283.27 905.76 233.26 0.00 0.00 0.00
October 764.69 528.77 235.92 866.01 334.92 0.00 0.00 0.00
November 697.17 505.00 192.17 716.82 435.60 0.00 0.00 0.00
December 605.95 437.56 168.39 571.78 583.03 0.00 0.00 0.00
                 
Annual Sum or Average 649.18 373.96 275.22 721.81 359.04 0.00 0.00 0.00
Minimum of Months 514.72 150.12 168.39 558.94 141.38 0.00 0.00 0.00
Maximum of Months 811.48 583.64 364.61 905.76 666.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.93 84.20 124.73 102.32 864.59 0.00 0.00 0.00
February 356.61 175.29 181.32 259.47 656.38 0.00 0.00 0.00
March 456.37 167.22 289.15 344.89 565.86 0.00 0.00 0.00
April 595.79 263.96 331.83 557.82 429.52 0.00 0.00 0.00
May 736.96 336.09 400.86 778.04 313.71 0.00 0.00 0.00
June 801.78 368.29 433.49 947.50 215.38 0.00 0.00 0.00
July 821.33 415.03 406.30 1053.28 180.20 0.00 0.00 0.00
August 697.42 342.28 355.14 863.66 203.08 0.00 0.00 0.00
September 561.03 283.64 277.40 643.22 275.53 0.00 0.00 0.00
October 400.98 199.23 201.76 374.75 418.37 0.00 0.00 0.00
November 283.86 140.82 143.04 207.52 586.10 0.00 0.00 0.00
December 190.81 80.53 110.27 91.29 797.05 0.00 0.00 0.00
                 
Annual Sum or Average 510.02 238.28 271.74 520.01 458.09 0.00 0.00 0.00
Minimum of Months 190.81 80.53 110.27 91.29 180.20 0.00 0.00 0.00
Maximum of Months 821.33 415.03 433.49 1053.28 864.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.93 84.20 124.73 102.32 864.59 0.00 0.00 0.00
February 356.61 175.29 181.32 259.47 656.38 0.00 0.00 0.00
March 456.37 167.22 289.15 344.89 565.86 0.00 0.00 0.00
April 595.79 263.96 331.83 557.82 429.52 0.00 0.00 0.00
May 736.96 336.09 400.86 778.04 313.71 0.00 0.00 0.00
June 801.78 368.29 433.49 947.50 215.38 0.00 0.00 0.00
July 821.33 415.03 406.30 1053.28 180.20 0.00 0.00 0.00
August 697.42 342.28 355.14 863.66 203.08 0.00 0.00 0.00
September 561.03 283.64 277.40 643.22 275.53 0.00 0.00 0.00
October 400.98 199.23 201.76 374.75 418.37 0.00 0.00 0.00
November 283.86 140.82 143.04 207.52 586.10 0.00 0.00 0.00
December 190.81 80.53 110.27 91.29 797.05 0.00 0.00 0.00
                 
Annual Sum or Average 510.02 238.28 271.74 520.01 458.09 0.00 0.00 0.00
Minimum of Months 190.81 80.53 110.27 91.29 180.20 0.00 0.00 0.00
Maximum of Months 821.33 415.03 433.49 1053.28 864.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.92 84.20 124.73 102.32 864.57 0.00 0.00 0.00
February 356.60 175.29 181.31 259.47 656.37 0.00 0.00 0.00
March 456.36 167.22 289.14 344.88 565.85 0.00 0.00 0.00
April 595.78 263.96 331.82 557.81 429.51 0.00 0.00 0.00
May 736.94 336.09 400.86 778.02 313.71 0.00 0.00 0.00
June 801.76 368.28 433.48 947.48 215.38 0.00 0.00 0.00
July 821.32 415.02 406.29 1053.26 180.20 0.00 0.00 0.00
August 697.41 342.27 355.14 863.64 203.07 0.00 0.00 0.00
September 561.02 283.63 277.39 643.21 275.53 0.00 0.00 0.00
October 400.98 199.22 201.75 374.75 418.36 0.00 0.00 0.00
November 283.85 140.82 143.04 207.52 586.09 0.00 0.00 0.00
December 190.80 80.53 110.27 91.29 797.04 0.00 0.00 0.00
                 
Annual Sum or Average 510.01 238.27 271.73 520.00 458.08 0.00 0.00 0.00
Minimum of Months 190.80 80.53 110.27 91.29 180.20 0.00 0.00 0.00
Maximum of Months 821.32 415.02 433.48 1053.26 864.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.02 0.00 452.02 15.58 3734.47 0.00 0.00 0.00
February 638.23 0.00 638.23 117.29 2759.65 0.00 0.00 0.00
March 1036.77 0.00 1036.77 374.15 2226.76 0.00 0.00 0.00
April 1182.14 6.90 1175.24 637.97 1584.53 0.00 0.00 0.00
May 1552.43 91.99 1460.44 1163.60 1180.77 0.00 0.00 0.00
June 1807.72 207.78 1599.93 1854.85 763.42 0.00 0.00 0.00
July 1651.45 154.68 1496.77 2013.82 635.95 0.00 0.00 0.00
August 1323.31 35.47 1287.84 1465.95 727.13 0.00 0.00 0.00
September 991.07 0.36 990.71 863.71 1100.39 0.00 0.00 0.00
October 722.93 0.00 722.93 339.85 1626.70 0.00 0.00 0.00
November 491.45 0.00 491.45 83.64 2321.48 0.00 0.00 0.00
December 379.05 0.00 379.05 8.02 3187.12 0.00 0.00 0.00
                 
Annual Sum or Average 1021.09 41.64 979.45 748.76 1817.12 0.00 0.00 0.00
Minimum of Months 379.05 0.00 379.05 8.02 635.95 0.00 0.00 0.00
Maximum of Months 1807.72 207.78 1599.93 2013.82 3734.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.97 317.24 374.73 372.08 2295.76 0.00 0.00 0.00
February 1082.30 537.34 544.96 819.06 1696.14 0.00 0.00 0.00
March 1455.25 602.14 853.11 1195.46 1400.79 0.00 0.00 0.00
April 1856.76 920.19 936.56 1799.00 1010.59 0.00 0.00 0.00
May 2051.03 912.58 1138.45 2129.31 788.67 0.00 0.00 0.00
June 2654.79 1366.15 1288.64 3162.75 518.98 0.00 0.00 0.00
July 2786.28 1575.16 1211.12 3579.47 424.07 0.00 0.00 0.00
August 2421.40 1349.13 1072.27 3038.54 477.34 0.00 0.00 0.00
September 1712.90 884.19 828.71 1956.22 689.02 0.00 0.00 0.00
October 1228.92 624.03 604.89 1172.99 1016.72 0.00 0.00 0.00
November 778.86 363.63 415.24 547.33 1416.02 0.00 0.00 0.00
December 574.46 246.73 327.73 292.92 1955.27 0.00 0.00 0.00
                 
Annual Sum or Average 1610.66 809.61 801.05 1676.98 1138.76 0.00 0.00 0.00
Minimum of Months 574.46 246.73 327.73 292.92 424.07 0.00 0.00 0.00
Maximum of Months 2786.28 1575.16 1288.64 3579.47 2295.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3186.24 2275.68 910.56 2954.49 3259.57 0.00 0.00 0.00
February 4057.63 2918.40 1139.23 4132.75 2469.54 0.00 0.00 0.00
March 3627.00 2036.75 1590.24 3683.31 2210.45 0.00 0.00 0.00
April 2915.50 1394.50 1521.00 3078.53 1649.07 0.00 0.00 0.00
May 2590.34 860.32 1730.02 2790.58 1289.03 0.00 0.00 0.00
June 2573.77 750.63 1823.13 3172.44 880.39 0.00 0.00 0.00
July 2774.78 1025.00 1749.79 3815.13 702.77 0.00 0.00 0.00
August 3297.64 1662.61 1635.03 4389.16 797.13 0.00 0.00 0.00
September 3657.48 2241.06 1416.43 4501.65 1141.78 0.00 0.00 0.00
October 3823.70 2644.04 1179.66 4313.47 1620.91 0.00 0.00 0.00
November 3486.08 2525.18 960.91 3588.27 2088.61 0.00 0.00 0.00
December 3029.94 2187.92 842.02 2882.50 2773.54 0.00 0.00 0.00
                 
Annual Sum or Average 3246.08 1869.91 1376.16 3604.47 1737.53 0.00 0.00 0.00
Minimum of Months 2573.77 750.63 842.02 2790.58 702.77 0.00 0.00 0.00
Maximum of Months 4057.63 2918.40 1823.13 4501.65 3259.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 626.78 252.60 374.18 321.74 2422.95 0.00 0.00 0.00
February 1069.81 525.87 543.95 821.80 1773.66 0.00 0.00 0.00
March 1369.10 501.66 867.44 1096.56 1492.38 0.00 0.00 0.00
April 1787.37 791.89 995.48 1743.05 1101.40 0.00 0.00 0.00
May 2210.84 1008.26 1202.58 2361.08 865.37 0.00 0.00 0.00
June 2405.31 1104.85 1300.46 2872.76 595.99 0.00 0.00 0.00
July 2463.98 1245.08 1218.89 3193.56 499.92 0.00 0.00 0.00
August 2092.25 1026.83 1065.42 2637.96 539.72 0.00 0.00 0.00
September 1683.08 850.90 832.18 1954.08 757.81 0.00 0.00 0.00
October 1202.94 597.68 605.26 1174.76 1097.48 0.00 0.00 0.00
November 851.57 422.45 429.12 670.19 1506.31 0.00 0.00 0.00
December 572.41 241.60 330.81 308.42 2052.34 0.00 0.00 0.00
                 
Annual Sum or Average 1530.03 714.83 815.21 1600.35 1223.51 0.00 0.00 0.00
Minimum of Months 572.41 241.60 330.81 308.42 499.92 0.00 0.00 0.00
Maximum of Months 2463.98 1245.08 1300.46 3193.56 2422.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.02 0.00 452.02 22.08 3600.33 0.00 0.00 0.00
February 638.23 0.00 638.23 140.62 2624.16 0.00 0.00 0.00
March 1036.77 0.00 1036.77 413.02 2091.06 0.00 0.00 0.00
April 1182.14 6.90 1175.24 690.19 1456.73 0.00 0.00 0.00
May 1552.43 91.99 1460.44 1202.19 1103.26 0.00 0.00 0.00
June 1807.72 207.78 1599.93 1871.53 737.60 0.00 0.00 0.00
July 1651.45 154.68 1496.77 2016.68 624.56 0.00 0.00 0.00
August 1323.31 35.47 1287.84 1474.40 703.38 0.00 0.00 0.00
September 991.07 0.36 990.71 890.42 1028.81 0.00 0.00 0.00
October 722.93 0.00 722.93 389.42 1474.20 0.00 0.00 0.00
November 491.45 0.00 491.45 104.38 2139.49 0.00 0.00 0.00
December 379.05 0.00 379.05 10.74 3040.82 0.00 0.00 0.00
                 
Annual Sum or Average 1021.09 41.64 979.45 772.65 1715.40 0.00 0.00 0.00
Minimum of Months 379.05 0.00 379.05 10.74 624.56 0.00 0.00 0.00
Maximum of Months 1807.72 207.78 1599.93 2016.68 3600.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.97 317.24 374.73 384.33 2214.05 0.00 0.00 0.00
February 1082.30 537.34 544.96 844.28 1616.12 0.00 0.00 0.00
March 1455.25 602.14 853.11 1223.99 1323.52 0.00 0.00 0.00
April 1856.76 920.19 936.56 1825.28 945.57 0.00 0.00 0.00
May 2051.03 912.58 1138.45 2140.75 748.82 0.00 0.00 0.00
June 2654.79 1366.15 1288.64 3160.31 510.33 0.00 0.00 0.00
July 2786.28 1575.16 1211.12 3570.51 423.21 0.00 0.00 0.00
August 2421.40 1349.13 1072.27 3033.06 472.21 0.00 0.00 0.00
September 1712.90 884.19 828.71 1963.31 661.08 0.00 0.00 0.00
October 1228.92 624.03 604.89 1205.56 938.10 0.00 0.00 0.00
November 778.86 363.63 415.24 573.35 1313.57 0.00 0.00 0.00
December 574.46 246.73 327.73 304.19 1866.83 0.00 0.00 0.00
                 
Annual Sum or Average 1610.66 809.61 801.05 1690.52 1084.27 0.00 0.00 0.00
Minimum of Months 574.46 246.73 327.73 304.19 423.21 0.00 0.00 0.00
Maximum of Months 2786.28 1575.16 1288.64 3570.51 2214.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3186.24 2275.68 910.56 2993.25 3116.55 0.00 0.00 0.00
February 4057.63 2918.40 1139.23 4177.65 2335.14 0.00 0.00 0.00
March 3627.00 2036.75 1590.24 3721.85 2080.86 0.00 0.00 0.00
April 2915.50 1394.50 1521.00 3114.34 1537.36 0.00 0.00 0.00
May 2590.34 860.32 1730.02 2808.09 1218.17 0.00 0.00 0.00
June 2573.77 750.63 1823.13 3173.56 856.51 0.00 0.00 0.00
July 2774.78 1025.00 1749.79 3807.65 694.14 0.00 0.00 0.00
August 3297.64 1662.61 1635.03 4383.16 781.57 0.00 0.00 0.00
September 3657.48 2241.06 1416.43 4509.31 1090.40 0.00 0.00 0.00
October 3823.70 2644.04 1179.66 4352.89 1497.31 0.00 0.00 0.00
November 3486.08 2525.18 960.91 3646.42 1929.88 0.00 0.00 0.00
December 3029.94 2187.92 842.02 2925.18 2629.08 0.00 0.00 0.00
                 
Annual Sum or Average 3246.08 1869.91 1376.16 3630.24 1644.81 0.00 0.00 0.00
Minimum of Months 2573.77 750.63 842.02 2808.09 694.14 0.00 0.00 0.00
Maximum of Months 4057.63 2918.40 1823.13 4509.31 3116.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 626.78 252.60 374.18 330.23 2337.39 0.00 0.00 0.00
February 1069.81 525.87 543.95 836.52 1695.08 0.00 0.00 0.00
March 1369.10 501.66 867.44 1113.20 1417.76 0.00 0.00 0.00
April 1787.37 791.89 995.48 1763.43 1036.01 0.00 0.00 0.00
May 2210.84 1008.26 1202.58 2370.32 822.45 0.00 0.00 0.00
June 2405.31 1104.85 1300.46 2872.56 582.10 0.00 0.00 0.00
July 2463.98 1245.08 1218.89 3189.04 494.67 0.00 0.00 0.00
August 2092.25 1026.83 1065.42 2636.73 530.07 0.00 0.00 0.00
September 1683.08 850.90 832.18 1960.43 725.16 0.00 0.00 0.00
October 1202.94 597.68 605.26 1196.09 1021.06 0.00 0.00 0.00
November 851.57 422.45 429.12 687.16 1409.11 0.00 0.00 0.00
December 572.41 241.60 330.81 315.90 1966.85 0.00 0.00 0.00
                 
Annual Sum or Average 1530.03 714.83 815.21 1609.94 1168.03 0.00 0.00 0.00
Minimum of Months 572.41 241.60 330.81 315.90 494.67 0.00 0.00 0.00
Maximum of Months 2463.98 1245.08 1300.46 3189.04 2337.39 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242139E+09 0.00 0.242139E+09 3938393.23 0.212822E+10
February 0.308799E+09 0.00 0.308799E+09 37098676.10 0.145062E+10
March 0.555376E+09 0.00 0.555376E+09 0.165973E+09 0.130988E+10
April 0.612820E+09 3576254.47 0.609243E+09 0.298592E+09 0.910482E+09
May 0.831604E+09 49277394.08 0.782327E+09 0.602675E+09 0.679643E+09
June 0.937120E+09 0.107713E+09 0.829407E+09 0.950613E+09 0.411852E+09
July 0.884648E+09 82857303.69 0.801791E+09 0.106777E+10 0.349979E+09
August 0.708873E+09 19000970.75 0.689872E+09 0.772663E+09 0.404790E+09
September 0.513771E+09 184367.60 0.513587E+09 0.433838E+09 0.610303E+09
October 0.387258E+09 0.00 0.387258E+09 0.155952E+09 0.967630E+09
November 0.254769E+09 0.00 0.254769E+09 29623057.50 0.135703E+10
December 0.203047E+09 0.00 0.203047E+09 1240095.59 0.190080E+10
           
Annual Sum or Average 0.644022E+10 0.262610E+09 0.617761E+10 0.451998E+10 0.124812E+11
Minimum of Months 0.203047E+09 0.00 0.203047E+09 1240095.59 0.349979E+09
Maximum of Months 0.937120E+09 0.107713E+09 0.829407E+09 0.106777E+10 0.212822E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242135E+09 0.00 0.242135E+09 3938013.47 0.212822E+10
February 0.308795E+09 0.00 0.308795E+09 37096871.73 0.145062E+10
March 0.555368E+09 0.00 0.555368E+09 0.165966E+09 0.130988E+10
April 0.612811E+09 3576175.85 0.609235E+09 0.298584E+09 0.910482E+09
May 0.831592E+09 49276310.77 0.782316E+09 0.602662E+09 0.679643E+09
June 0.937106E+09 0.107711E+09 0.829396E+09 0.950596E+09 0.411851E+09
July 0.884636E+09 82855482.17 0.801781E+09 0.106775E+10 0.349977E+09
August 0.708864E+09 19000553.03 0.689863E+09 0.772653E+09 0.404789E+09
September 0.513764E+09 184363.55 0.513580E+09 0.433831E+09 0.610302E+09
October 0.387253E+09 0.00 0.387253E+09 0.155947E+09 0.967629E+09
November 0.254766E+09 0.00 0.254766E+09 29621545.97 0.135703E+10
December 0.203044E+09 0.00 0.203044E+09 1239942.68 0.190080E+10
           
Annual Sum or Average 0.644013E+10 0.262604E+09 0.617753E+10 0.451989E+10 0.124812E+11
Minimum of Months 0.203044E+09 0.00 0.203044E+09 1239942.68 0.349977E+09
Maximum of Months 0.937106E+09 0.107711E+09 0.829396E+09 0.106775E+10 0.212822E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242136E+09 0.00 0.242136E+09 3938140.05 0.212822E+10
February 0.308796E+09 0.00 0.308796E+09 37097473.19 0.145062E+10
March 0.555371E+09 0.00 0.555371E+09 0.165969E+09 0.130988E+10
April 0.612814E+09 3576202.05 0.609237E+09 0.298587E+09 0.910482E+09
May 0.831596E+09 49276671.88 0.782319E+09 0.602666E+09 0.679643E+09
June 0.937111E+09 0.107712E+09 0.829399E+09 0.950602E+09 0.411852E+09
July 0.884640E+09 82856089.35 0.801784E+09 0.106776E+10 0.349978E+09
August 0.708867E+09 19000692.27 0.689866E+09 0.772656E+09 0.404789E+09
September 0.513767E+09 184364.90 0.513582E+09 0.433834E+09 0.610302E+09
October 0.387254E+09 0.00 0.387254E+09 0.155949E+09 0.967629E+09
November 0.254767E+09 0.00 0.254767E+09 29622049.81 0.135703E+10
December 0.203045E+09 0.00 0.203045E+09 1239993.65 0.190080E+10
           
Annual Sum or Average 0.644016E+10 0.262606E+09 0.617756E+10 0.451992E+10 0.124812E+11
Minimum of Months 0.203045E+09 0.00 0.203045E+09 1239993.65 0.349978E+09
Maximum of Months 0.937111E+09 0.107712E+09 0.829399E+09 0.106776E+10 0.212822E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242135E+09 0.00 0.242135E+09 3938013.47 0.212822E+10
February 0.308795E+09 0.00 0.308795E+09 37096871.73 0.145062E+10
March 0.555368E+09 0.00 0.555368E+09 0.165966E+09 0.130988E+10
April 0.612811E+09 3576175.85 0.609235E+09 0.298584E+09 0.910482E+09
May 0.831592E+09 49276310.77 0.782316E+09 0.602662E+09 0.679643E+09
June 0.937106E+09 0.107711E+09 0.829396E+09 0.950596E+09 0.411851E+09
July 0.884636E+09 82855482.17 0.801781E+09 0.106775E+10 0.349977E+09
August 0.708864E+09 19000553.03 0.689863E+09 0.772653E+09 0.404789E+09
September 0.513764E+09 184363.55 0.513580E+09 0.433831E+09 0.610302E+09
October 0.387253E+09 0.00 0.387253E+09 0.155947E+09 0.967629E+09
November 0.254766E+09 0.00 0.254766E+09 29621545.97 0.135703E+10
December 0.203044E+09 0.00 0.203044E+09 1239942.68 0.190080E+10
           
Annual Sum or Average 0.644013E+10 0.262604E+09 0.617753E+10 0.451989E+10 0.124812E+11
Minimum of Months 0.203044E+09 0.00 0.203044E+09 1239942.68 0.349977E+09
Maximum of Months 0.937106E+09 0.107711E+09 0.829396E+09 0.106775E+10 0.212822E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.242126E+09 0.00 0.242126E+09 3937918.04 0.212813E+10
February 0.308783E+09 0.00 0.308783E+09 37095677.28 0.145057E+10
March 0.555347E+09 0.00 0.555347E+09 0.165961E+09 0.130983E+10
April 0.612788E+09 3576044.81 0.609211E+09 0.298573E+09 0.910446E+09
May 0.831561E+09 49274505.26 0.782286E+09 0.602640E+09 0.679616E+09
June 0.937071E+09 0.107707E+09 0.829364E+09 0.950561E+09 0.411835E+09
July 0.884602E+09 82852446.31 0.801750E+09 0.106771E+10 0.349964E+09
August 0.708837E+09 18999856.84 0.689837E+09 0.772623E+09 0.404773E+09
September 0.513745E+09 184356.80 0.513560E+09 0.433815E+09 0.610278E+09
October 0.387238E+09 0.00 0.387238E+09 0.155942E+09 0.967590E+09
November 0.254756E+09 0.00 0.254756E+09 29620604.00 0.135697E+10
December 0.203036E+09 0.00 0.203036E+09 1239918.19 0.190072E+10
           
Annual Sum or Average 0.643989E+10 0.262594E+09 0.617729E+10 0.451972E+10 0.124807E+11
Minimum of Months 0.203036E+09 0.00 0.203036E+09 1239918.19 0.349964E+09
Maximum of Months 0.937071E+09 0.107707E+09 0.829364E+09 0.106771E+10 0.212813E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617795E+09 0.283234E+09 0.334561E+09 0.317623E+09 0.215639E+10
February 0.872775E+09 0.433312E+09 0.439463E+09 0.638044E+09 0.145648E+10
March 0.129926E+10 0.537598E+09 0.761663E+09 0.104272E+10 0.133281E+10
April 0.160425E+10 0.795056E+09 0.809197E+09 0.154169E+10 0.927543E+09
May 0.183118E+10 0.814759E+09 0.101642E+10 0.189608E+10 0.746343E+09
June 0.229376E+10 0.118037E+10 0.111339E+10 0.274272E+10 0.456334E+09
July 0.248761E+10 0.140631E+10 0.108130E+10 0.321018E+10 0.371490E+09
August 0.216185E+10 0.120451E+10 0.957333E+09 0.272625E+10 0.415225E+09
September 0.147996E+10 0.763951E+09 0.716011E+09 0.168840E+10 0.623634E+09
October 0.109719E+10 0.557135E+09 0.540053E+09 0.102679E+10 0.978020E+09
November 0.672946E+09 0.314177E+09 0.358768E+09 0.450286E+09 0.133143E+10
December 0.512881E+09 0.220284E+09 0.292597E+09 0.243495E+09 0.188921E+10
           
Annual Sum or Average 0.169315E+11 0.851070E+10 0.842076E+10 0.175243E+11 0.126849E+11
Minimum of Months 0.512881E+09 0.220284E+09 0.292597E+09 0.243495E+09 0.371490E+09
Maximum of Months 0.248761E+10 0.140631E+10 0.111339E+10 0.321018E+10 0.215639E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617795E+09 0.283234E+09 0.334561E+09 0.317623E+09 0.215639E+10
February 0.872775E+09 0.433312E+09 0.439463E+09 0.638044E+09 0.145648E+10
March 0.129926E+10 0.537598E+09 0.761663E+09 0.104272E+10 0.133281E+10
April 0.160425E+10 0.795056E+09 0.809197E+09 0.154169E+10 0.927543E+09
May 0.183118E+10 0.814759E+09 0.101642E+10 0.189608E+10 0.746343E+09
June 0.229376E+10 0.118037E+10 0.111339E+10 0.274272E+10 0.456334E+09
July 0.248761E+10 0.140631E+10 0.108130E+10 0.321018E+10 0.371490E+09
August 0.216185E+10 0.120451E+10 0.957333E+09 0.272625E+10 0.415225E+09
September 0.147996E+10 0.763951E+09 0.716011E+09 0.168840E+10 0.623634E+09
October 0.109719E+10 0.557135E+09 0.540053E+09 0.102679E+10 0.978020E+09
November 0.672946E+09 0.314177E+09 0.358768E+09 0.450286E+09 0.133143E+10
December 0.512881E+09 0.220284E+09 0.292597E+09 0.243495E+09 0.188921E+10
           
Annual Sum or Average 0.169315E+11 0.851070E+10 0.842076E+10 0.175243E+11 0.126849E+11
Minimum of Months 0.512881E+09 0.220284E+09 0.292597E+09 0.243495E+09 0.371490E+09
Maximum of Months 0.248761E+10 0.140631E+10 0.111339E+10 0.321018E+10 0.215639E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.617784E+09 0.283229E+09 0.334555E+09 0.317617E+09 0.215635E+10
February 0.872759E+09 0.433304E+09 0.439455E+09 0.638033E+09 0.145645E+10
March 0.129924E+10 0.537588E+09 0.761649E+09 0.104270E+10 0.133278E+10
April 0.160422E+10 0.795042E+09 0.809182E+09 0.154166E+10 0.927526E+09
May 0.183114E+10 0.814744E+09 0.101640E+10 0.189605E+10 0.746329E+09
June 0.229372E+10 0.118035E+10 0.111337E+10 0.274267E+10 0.456325E+09
July 0.248757E+10 0.140629E+10 0.108128E+10 0.321012E+10 0.371483E+09
August 0.216181E+10 0.120449E+10 0.957315E+09 0.272620E+10 0.415218E+09
September 0.147994E+10 0.763937E+09 0.715998E+09 0.168837E+10 0.623623E+09
October 0.109717E+10 0.557125E+09 0.540043E+09 0.102677E+10 0.978003E+09
November 0.672933E+09 0.314171E+09 0.358762E+09 0.450277E+09 0.133141E+10
December 0.512872E+09 0.220279E+09 0.292592E+09 0.243491E+09 0.188918E+10
           
Annual Sum or Average 0.169312E+11 0.851055E+10 0.842060E+10 0.175240E+11 0.126847E+11
Minimum of Months 0.512872E+09 0.220279E+09 0.292592E+09 0.243491E+09 0.371483E+09
Maximum of Months 0.248757E+10 0.140629E+10 0.111337E+10 0.321012E+10 0.215635E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170677E+10 0.121901E+10 0.487764E+09 0.158384E+10 0.178583E+10
February 0.196321E+10 0.141201E+10 0.551198E+09 0.200426E+10 0.123287E+10
March 0.194287E+10 0.109103E+10 0.851849E+09 0.197621E+10 0.122719E+10
April 0.151137E+10 0.722894E+09 0.788475E+09 0.159525E+10 0.894006E+09
May 0.138758E+10 0.460849E+09 0.926727E+09 0.149714E+10 0.715953E+09
June 0.133422E+10 0.389120E+09 0.945104E+09 0.164674E+10 0.467508E+09
July 0.148637E+10 0.549058E+09 0.937317E+09 0.204619E+10 0.378697E+09
August 0.176645E+10 0.890610E+09 0.875845E+09 0.235741E+10 0.428541E+09
September 0.189601E+10 0.116174E+10 0.734266E+09 0.234784E+10 0.604639E+09
October 0.204824E+10 0.141633E+10 0.631912E+09 0.231962E+10 0.897097E+09
November 0.180715E+10 0.130903E+10 0.498126E+09 0.185809E+10 0.112911E+10
December 0.162305E+10 0.117200E+10 0.451044E+09 0.153152E+10 0.156164E+10
           
Annual Sum or Average 0.204733E+11 0.117937E+11 0.867963E+10 0.227641E+11 0.113231E+11
Minimum of Months 0.133422E+10 0.389120E+09 0.451044E+09 0.149714E+10 0.378697E+09
Maximum of Months 0.204824E+10 0.141633E+10 0.945104E+09 0.235741E+10 0.178583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170676E+10 0.121900E+10 0.487761E+09 0.158382E+10 0.178583E+10
February 0.196319E+10 0.141200E+10 0.551195E+09 0.200425E+10 0.123287E+10
March 0.194286E+10 0.109102E+10 0.851844E+09 0.197619E+10 0.122719E+10
April 0.151136E+10 0.722889E+09 0.788471E+09 0.159523E+10 0.894006E+09
May 0.138757E+10 0.460846E+09 0.926722E+09 0.149713E+10 0.715953E+09
June 0.133422E+10 0.389117E+09 0.945099E+09 0.164673E+10 0.467508E+09
July 0.148637E+10 0.549054E+09 0.937312E+09 0.204618E+10 0.378696E+09
August 0.176644E+10 0.890603E+09 0.875840E+09 0.235740E+10 0.428540E+09
September 0.189599E+10 0.116173E+10 0.734262E+09 0.234782E+10 0.604639E+09
October 0.204823E+10 0.141632E+10 0.631909E+09 0.231960E+10 0.897097E+09
November 0.180714E+10 0.130902E+10 0.498123E+09 0.185808E+10 0.112911E+10
December 0.162303E+10 0.117199E+10 0.451041E+09 0.153150E+10 0.156164E+10
           
Annual Sum or Average 0.204732E+11 0.117936E+11 0.867958E+10 0.227639E+11 0.113231E+11
Minimum of Months 0.133422E+10 0.389117E+09 0.451041E+09 0.149713E+10 0.378696E+09
Maximum of Months 0.204823E+10 0.141632E+10 0.945099E+09 0.235740E+10 0.178583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170677E+10 0.121901E+10 0.487764E+09 0.158384E+10 0.178583E+10
February 0.196321E+10 0.141201E+10 0.551198E+09 0.200426E+10 0.123287E+10
March 0.194287E+10 0.109103E+10 0.851849E+09 0.197621E+10 0.122719E+10
April 0.151137E+10 0.722894E+09 0.788475E+09 0.159525E+10 0.894006E+09
May 0.138758E+10 0.460849E+09 0.926727E+09 0.149714E+10 0.715953E+09
June 0.133422E+10 0.389120E+09 0.945104E+09 0.164674E+10 0.467508E+09
July 0.148637E+10 0.549058E+09 0.937317E+09 0.204619E+10 0.378697E+09
August 0.176645E+10 0.890610E+09 0.875845E+09 0.235741E+10 0.428541E+09
September 0.189601E+10 0.116174E+10 0.734266E+09 0.234784E+10 0.604639E+09
October 0.204824E+10 0.141633E+10 0.631912E+09 0.231962E+10 0.897097E+09
November 0.180715E+10 0.130903E+10 0.498126E+09 0.185809E+10 0.112911E+10
December 0.162305E+10 0.117200E+10 0.451044E+09 0.153152E+10 0.156164E+10
           
Annual Sum or Average 0.204733E+11 0.117937E+11 0.867963E+10 0.227641E+11 0.113231E+11
Minimum of Months 0.133422E+10 0.389120E+09 0.451044E+09 0.149714E+10 0.378697E+09
Maximum of Months 0.204824E+10 0.141633E+10 0.945104E+09 0.235741E+10 0.178583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170676E+10 0.121900E+10 0.487761E+09 0.158382E+10 0.178583E+10
February 0.196319E+10 0.141200E+10 0.551195E+09 0.200425E+10 0.123287E+10
March 0.194286E+10 0.109102E+10 0.851844E+09 0.197619E+10 0.122719E+10
April 0.151136E+10 0.722889E+09 0.788471E+09 0.159523E+10 0.894006E+09
May 0.138757E+10 0.460846E+09 0.926722E+09 0.149713E+10 0.715953E+09
June 0.133422E+10 0.389117E+09 0.945099E+09 0.164673E+10 0.467508E+09
July 0.148637E+10 0.549054E+09 0.937312E+09 0.204618E+10 0.378696E+09
August 0.176644E+10 0.890603E+09 0.875840E+09 0.235740E+10 0.428540E+09
September 0.189599E+10 0.116173E+10 0.734262E+09 0.234782E+10 0.604639E+09
October 0.204823E+10 0.141632E+10 0.631909E+09 0.231960E+10 0.897097E+09
November 0.180714E+10 0.130902E+10 0.498123E+09 0.185808E+10 0.112911E+10
December 0.162303E+10 0.117199E+10 0.451041E+09 0.153150E+10 0.156164E+10
           
Annual Sum or Average 0.204732E+11 0.117936E+11 0.867958E+10 0.227639E+11 0.113231E+11
Minimum of Months 0.133422E+10 0.389117E+09 0.451041E+09 0.149713E+10 0.378696E+09
Maximum of Months 0.204823E+10 0.141632E+10 0.945099E+09 0.235740E+10 0.178583E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170670E+10 0.121896E+10 0.487742E+09 0.158376E+10 0.178575E+10
February 0.196312E+10 0.141195E+10 0.551174E+09 0.200417E+10 0.123282E+10
March 0.194279E+10 0.109098E+10 0.851812E+09 0.197612E+10 0.122714E+10
April 0.151130E+10 0.722862E+09 0.788441E+09 0.159518E+10 0.893970E+09
May 0.138752E+10 0.460829E+09 0.926687E+09 0.149707E+10 0.715924E+09
June 0.133417E+10 0.389103E+09 0.945063E+09 0.164667E+10 0.467489E+09
July 0.148631E+10 0.549034E+09 0.937277E+09 0.204610E+10 0.378681E+09
August 0.176638E+10 0.890571E+09 0.875807E+09 0.235731E+10 0.428523E+09
September 0.189592E+10 0.116169E+10 0.734234E+09 0.234774E+10 0.604615E+09
October 0.204815E+10 0.141627E+10 0.631885E+09 0.231952E+10 0.897061E+09
November 0.180707E+10 0.130897E+10 0.498104E+09 0.185801E+10 0.112906E+10
December 0.162297E+10 0.117195E+10 0.451025E+09 0.153145E+10 0.156158E+10
           
Annual Sum or Average 0.204724E+11 0.117932E+11 0.867925E+10 0.227631E+11 0.113226E+11
Minimum of Months 0.133417E+10 0.389103E+09 0.451025E+09 0.149707E+10 0.378681E+09
Maximum of Months 0.204815E+10 0.141627E+10 0.945063E+09 0.235731E+10 0.178575E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559591E+09 0.225519E+09 0.334072E+09 0.274047E+09 0.231572E+10
February 0.862705E+09 0.424063E+09 0.438642E+09 0.627720E+09 0.158792E+10
March 0.122234E+10 0.447885E+09 0.774459E+09 0.923751E+09 0.151560E+10
April 0.154430E+10 0.684197E+09 0.860104E+09 0.144587E+10 0.111330E+10
May 0.197386E+10 0.900187E+09 0.107368E+10 0.208389E+10 0.840253E+09
June 0.207821E+10 0.954601E+09 0.112361E+10 0.245592E+10 0.558273E+09
July 0.219986E+10 0.111162E+10 0.108824E+10 0.282110E+10 0.482660E+09
August 0.186798E+10 0.916764E+09 0.951214E+09 0.231322E+10 0.543924E+09
September 0.145420E+10 0.735184E+09 0.719015E+09 0.166723E+10 0.714182E+09
October 0.107400E+10 0.533611E+09 0.540386E+09 0.100374E+10 0.112056E+10
November 0.735763E+09 0.365001E+09 0.370762E+09 0.537894E+09 0.151918E+10
December 0.511052E+09 0.215701E+09 0.295352E+09 0.244511E+09 0.213482E+10
           
Annual Sum or Average 0.160839E+11 0.751434E+10 0.856953E+10 0.163989E+11 0.144464E+11
Minimum of Months 0.511052E+09 0.215701E+09 0.295352E+09 0.244511E+09 0.482660E+09
Maximum of Months 0.219986E+10 0.111162E+10 0.112361E+10 0.282110E+10 0.231572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559591E+09 0.225519E+09 0.334072E+09 0.274047E+09 0.231572E+10
February 0.862705E+09 0.424063E+09 0.438642E+09 0.627720E+09 0.158792E+10
March 0.122234E+10 0.447885E+09 0.774459E+09 0.923751E+09 0.151560E+10
April 0.154430E+10 0.684197E+09 0.860104E+09 0.144587E+10 0.111330E+10
May 0.197386E+10 0.900187E+09 0.107368E+10 0.208389E+10 0.840253E+09
June 0.207821E+10 0.954601E+09 0.112361E+10 0.245592E+10 0.558273E+09
July 0.219986E+10 0.111162E+10 0.108824E+10 0.282110E+10 0.482660E+09
August 0.186798E+10 0.916764E+09 0.951214E+09 0.231322E+10 0.543924E+09
September 0.145420E+10 0.735184E+09 0.719015E+09 0.166723E+10 0.714182E+09
October 0.107400E+10 0.533611E+09 0.540386E+09 0.100374E+10 0.112056E+10
November 0.735763E+09 0.365001E+09 0.370762E+09 0.537894E+09 0.151918E+10
December 0.511052E+09 0.215701E+09 0.295352E+09 0.244511E+09 0.213482E+10
           
Annual Sum or Average 0.160839E+11 0.751434E+10 0.856953E+10 0.163989E+11 0.144464E+11
Minimum of Months 0.511052E+09 0.215701E+09 0.295352E+09 0.244511E+09 0.482660E+09
Maximum of Months 0.219986E+10 0.111162E+10 0.112361E+10 0.282110E+10 0.231572E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.559581E+09 0.225515E+09 0.334066E+09 0.274042E+09 0.231568E+10
February 0.862689E+09 0.424056E+09 0.438634E+09 0.627709E+09 0.158789E+10
March 0.122232E+10 0.447877E+09 0.774445E+09 0.923734E+09 0.151557E+10
April 0.154427E+10 0.684184E+09 0.860088E+09 0.144585E+10 0.111328E+10
May 0.197383E+10 0.900170E+09 0.107366E+10 0.208386E+10 0.840237E+09
June 0.207817E+10 0.954583E+09 0.112359E+10 0.245587E+10 0.558263E+09
July 0.219982E+10 0.111160E+10 0.108822E+10 0.282105E+10 0.482652E+09
August 0.186794E+10 0.916748E+09 0.951197E+09 0.231317E+10 0.543914E+09
September 0.145417E+10 0.735170E+09 0.719002E+09 0.166720E+10 0.714169E+09
October 0.107398E+10 0.533602E+09 0.540376E+09 0.100372E+10 0.112054E+10
November 0.735749E+09 0.364994E+09 0.370755E+09 0.537884E+09 0.151915E+10
December 0.511043E+09 0.215697E+09 0.295346E+09 0.244507E+09 0.213478E+10
           
Annual Sum or Average 0.160836E+11 0.751420E+10 0.856937E+10 0.163986E+11 0.144461E+11
Minimum of Months 0.511043E+09 0.215697E+09 0.295346E+09 0.244507E+09 0.482652E+09
Maximum of Months 0.219982E+10 0.111160E+10 0.112359E+10 0.282105E+10 0.231568E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121069E+10 0.00 0.121069E+10 41722084.11 0.100024E+11
February 0.154399E+10 0.00 0.154399E+10 0.283747E+09 0.667614E+10
March 0.277688E+10 0.00 0.277688E+10 0.100213E+10 0.596415E+10
April 0.306410E+10 17881386.28 0.304622E+10 0.165363E+10 0.410710E+10
May 0.415802E+10 0.246389E+09 0.391163E+10 0.311660E+10 0.316259E+10
June 0.468560E+10 0.538570E+09 0.414703E+10 0.480776E+10 0.197877E+10
July 0.442324E+10 0.414289E+09 0.400895E+10 0.539381E+10 0.170332E+10
August 0.354436E+10 95005459.17 0.344936E+10 0.392641E+10 0.194754E+10
September 0.256885E+10 921843.89 0.256793E+10 0.223873E+10 0.285221E+10
October 0.193629E+10 0.00 0.193629E+10 0.910255E+09 0.435694E+10
November 0.127385E+10 0.00 0.127385E+10 0.216783E+09 0.601727E+10
December 0.101523E+10 0.00 0.101523E+10 21475302.38 0.853638E+10
           
Annual Sum or Average 0.322011E+11 0.131306E+10 0.308881E+11 0.236131E+11 0.573048E+11
Minimum of Months 0.101523E+10 0.00 0.101523E+10 21475302.38 0.170332E+10
Maximum of Months 0.468560E+10 0.538570E+09 0.414703E+10 0.539381E+10 0.100024E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185337E+10 0.849694E+09 0.100367E+10 0.996576E+09 0.614897E+10
February 0.261830E+10 0.129992E+10 0.131838E+10 0.198148E+10 0.410331E+10
March 0.389774E+10 0.161278E+10 0.228496E+10 0.320193E+10 0.375187E+10
April 0.481271E+10 0.238514E+10 0.242757E+10 0.466302E+10 0.261946E+10
May 0.549347E+10 0.244425E+10 0.304922E+10 0.570316E+10 0.211236E+10
June 0.688122E+10 0.354107E+10 0.334015E+10 0.819784E+10 0.134520E+10
July 0.746276E+10 0.421890E+10 0.324386E+10 0.958727E+10 0.113582E+10
August 0.648547E+10 0.361351E+10 0.287197E+10 0.813842E+10 0.127852E+10
September 0.443984E+10 0.229183E+10 0.214801E+10 0.507053E+10 0.178595E+10
October 0.329153E+10 0.167139E+10 0.162014E+10 0.314174E+10 0.272318E+10
November 0.201882E+10 0.942522E+09 0.107629E+10 0.141868E+10 0.367034E+10
December 0.153863E+10 0.660844E+09 0.877783E+09 0.784550E+09 0.523701E+10
           
Annual Sum or Average 0.507939E+11 0.255318E+11 0.252620E+11 0.528852E+11 0.359120E+11
Minimum of Months 0.153863E+10 0.660844E+09 0.877783E+09 0.784550E+09 0.113582E+10
Maximum of Months 0.746276E+10 0.421890E+10 0.334015E+10 0.958727E+10 0.614897E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.853404E+10 0.609518E+10 0.243886E+10 0.791329E+10 0.873042E+10
February 0.981623E+10 0.706020E+10 0.275603E+10 0.999794E+10 0.597430E+10
March 0.971455E+10 0.545524E+10 0.425930E+10 0.986536E+10 0.592047E+10
April 0.755697E+10 0.361455E+10 0.394242E+10 0.797954E+10 0.427440E+10
May 0.693798E+10 0.230429E+10 0.463369E+10 0.747430E+10 0.345253E+10
June 0.667121E+10 0.194564E+10 0.472556E+10 0.822297E+10 0.228198E+10
July 0.743197E+10 0.274535E+10 0.468662E+10 0.102184E+11 0.188229E+10
August 0.883241E+10 0.445314E+10 0.437927E+10 0.117559E+11 0.213503E+10
September 0.948020E+10 0.580882E+10 0.367137E+10 0.116683E+11 0.295949E+10
October 0.102414E+11 0.708180E+10 0.315960E+10 0.115532E+11 0.434144E+10
November 0.903593E+10 0.654527E+10 0.249067E+10 0.930079E+10 0.541367E+10
December 0.811539E+10 0.586013E+10 0.225526E+10 0.772049E+10 0.742866E+10
           
Annual Sum or Average 0.102368E+12 0.589696E+11 0.433987E+11 0.113671E+12 0.547947E+11
Minimum of Months 0.667121E+10 0.194564E+10 0.225526E+10 0.747430E+10 0.188229E+10
Maximum of Months 0.102414E+11 0.708180E+10 0.472556E+10 0.117559E+11 0.873042E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167876E+10 0.676552E+09 0.100221E+10 0.861749E+09 0.648962E+10
February 0.258809E+10 0.127218E+10 0.131591E+10 0.198811E+10 0.429085E+10
March 0.366700E+10 0.134364E+10 0.232335E+10 0.293703E+10 0.399718E+10
April 0.463285E+10 0.205257E+10 0.258029E+10 0.451799E+10 0.285482E+10
May 0.592153E+10 0.270053E+10 0.322099E+10 0.632391E+10 0.231781E+10
June 0.623457E+10 0.286377E+10 0.337080E+10 0.744620E+10 0.154481E+10
July 0.659951E+10 0.333483E+10 0.326468E+10 0.855363E+10 0.133899E+10
August 0.560388E+10 0.275026E+10 0.285361E+10 0.706551E+10 0.144558E+10
September 0.436255E+10 0.220553E+10 0.215702E+10 0.506497E+10 0.196423E+10
October 0.322196E+10 0.160082E+10 0.162114E+10 0.314648E+10 0.293950E+10
November 0.220727E+10 0.109499E+10 0.111227E+10 0.173714E+10 0.390436E+10
December 0.153314E+10 0.647096E+09 0.886046E+09 0.826068E+09 0.549698E+10
           
Annual Sum or Average 0.482511E+11 0.225428E+11 0.257083E+11 0.504688E+11 0.385847E+11
Minimum of Months 0.153314E+10 0.647096E+09 0.886046E+09 0.826068E+09 0.133899E+10
Maximum of Months 0.659951E+10 0.333483E+10 0.337080E+10 0.855363E+10 0.648962E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121069E+10 0.00 0.121069E+10 59127059.33 0.964311E+10
February 0.154399E+10 0.00 0.154399E+10 0.340190E+09 0.634837E+10
March 0.277688E+10 0.00 0.277688E+10 0.110622E+10 0.560069E+10
April 0.306410E+10 17881386.28 0.304622E+10 0.178898E+10 0.377585E+10
May 0.415802E+10 0.246389E+09 0.391163E+10 0.321993E+10 0.295496E+10
June 0.468560E+10 0.538570E+09 0.414703E+10 0.485099E+10 0.191186E+10
July 0.442324E+10 0.414289E+09 0.400895E+10 0.540147E+10 0.167283E+10
August 0.354436E+10 95005459.17 0.344936E+10 0.394904E+10 0.188394E+10
September 0.256885E+10 921843.89 0.256793E+10 0.230798E+10 0.266667E+10
October 0.193629E+10 0.00 0.193629E+10 0.104303E+10 0.394849E+10
November 0.127385E+10 0.00 0.127385E+10 0.270563E+09 0.554557E+10
December 0.101523E+10 0.00 0.101523E+10 28777957.44 0.814453E+10
           
Annual Sum or Average 0.322011E+11 0.131306E+10 0.308881E+11 0.243663E+11 0.540969E+11
Minimum of Months 0.101523E+10 0.00 0.101523E+10 28777957.44 0.167283E+10
Maximum of Months 0.468560E+10 0.538570E+09 0.414703E+10 0.540147E+10 0.964311E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185337E+10 0.849694E+09 0.100367E+10 0.102938E+10 0.593010E+10
February 0.261830E+10 0.129992E+10 0.131838E+10 0.204248E+10 0.390973E+10
March 0.389774E+10 0.161278E+10 0.228496E+10 0.327833E+10 0.354492E+10
April 0.481271E+10 0.238514E+10 0.242757E+10 0.473112E+10 0.245092E+10
May 0.549347E+10 0.244425E+10 0.304922E+10 0.573379E+10 0.200565E+10
June 0.688122E+10 0.354107E+10 0.334015E+10 0.819151E+10 0.132279E+10
July 0.746276E+10 0.421890E+10 0.324386E+10 0.956325E+10 0.113351E+10
August 0.648547E+10 0.361351E+10 0.287197E+10 0.812374E+10 0.126478E+10
September 0.443984E+10 0.229183E+10 0.214801E+10 0.508891E+10 0.171353E+10
October 0.329153E+10 0.167139E+10 0.162014E+10 0.322897E+10 0.251261E+10
November 0.201882E+10 0.942522E+09 0.107629E+10 0.148612E+10 0.340478E+10
December 0.153863E+10 0.660844E+09 0.877783E+09 0.814734E+09 0.500011E+10
           
Annual Sum or Average 0.507939E+11 0.255318E+11 0.252620E+11 0.533123E+11 0.341934E+11
Minimum of Months 0.153863E+10 0.660844E+09 0.877783E+09 0.814734E+09 0.113351E+10
Maximum of Months 0.746276E+10 0.421890E+10 0.334015E+10 0.956325E+10 0.593010E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.853404E+10 0.609518E+10 0.243886E+10 0.801711E+10 0.834737E+10
February 0.981623E+10 0.706020E+10 0.275603E+10 0.101066E+11 0.564916E+10
March 0.971455E+10 0.545524E+10 0.425930E+10 0.996859E+10 0.557337E+10
April 0.755697E+10 0.361455E+10 0.394242E+10 0.807238E+10 0.398484E+10
May 0.693798E+10 0.230429E+10 0.463369E+10 0.752120E+10 0.326274E+10
June 0.667121E+10 0.194564E+10 0.472556E+10 0.822587E+10 0.222007E+10
July 0.743197E+10 0.274535E+10 0.468662E+10 0.101984E+11 0.185918E+10
August 0.883241E+10 0.445314E+10 0.437927E+10 0.117399E+11 0.209335E+10
September 0.948020E+10 0.580882E+10 0.367137E+10 0.116881E+11 0.282631E+10
October 0.102414E+11 0.708180E+10 0.315960E+10 0.116588E+11 0.401040E+10
November 0.903593E+10 0.654527E+10 0.249067E+10 0.945151E+10 0.500225E+10
December 0.811539E+10 0.586013E+10 0.225526E+10 0.783481E+10 0.704172E+10
           
Annual Sum or Average 0.102368E+12 0.589696E+11 0.433987E+11 0.114483E+12 0.518708E+11
Minimum of Months 0.667121E+10 0.194564E+10 0.225526E+10 0.752120E+10 0.185918E+10
Maximum of Months 0.102414E+11 0.708180E+10 0.472556E+10 0.117399E+11 0.834737E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167876E+10 0.676552E+09 0.100221E+10 0.884481E+09 0.626046E+10
February 0.258809E+10 0.127218E+10 0.131591E+10 0.202371E+10 0.410073E+10
March 0.366700E+10 0.134364E+10 0.232335E+10 0.298160E+10 0.379732E+10
April 0.463285E+10 0.205257E+10 0.258029E+10 0.457082E+10 0.268534E+10
May 0.592153E+10 0.270053E+10 0.322099E+10 0.634868E+10 0.220284E+10
June 0.623457E+10 0.286377E+10 0.337080E+10 0.744566E+10 0.150881E+10
July 0.659951E+10 0.333483E+10 0.326468E+10 0.854154E+10 0.132493E+10
August 0.560388E+10 0.275026E+10 0.285361E+10 0.706222E+10 0.141973E+10
September 0.436255E+10 0.220553E+10 0.215702E+10 0.508144E+10 0.187961E+10
October 0.322196E+10 0.160082E+10 0.162114E+10 0.320360E+10 0.273480E+10
November 0.220727E+10 0.109499E+10 0.111227E+10 0.178111E+10 0.365241E+10
December 0.153314E+10 0.647096E+09 0.886046E+09 0.846095E+09 0.526802E+10
           
Annual Sum or Average 0.482511E+11 0.225428E+11 0.257083E+11 0.507710E+11 0.368350E+11
Minimum of Months 0.153314E+10 0.647096E+09 0.886046E+09 0.846095E+09 0.132493E+10
Maximum of Months 0.659951E+10 0.333483E+10 0.337080E+10 0.854154E+10 0.626046E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.35 3972.90 452.01 0.00 452.01 0.00 0.00
February 76.67 2998.12 638.21 0.00 638.21 0.00 0.00
March 309.82 2445.25 1036.75 0.00 1036.75 0.00 0.00
April 575.97 1756.32 1182.12 6.90 1175.22 0.00 0.00
May 1125.04 1268.74 1552.40 91.99 1460.41 0.00 0.00
June 1833.71 794.46 1807.68 207.78 1599.91 0.00 0.00
July 1993.26 653.33 1651.42 154.67 1496.75 0.00 0.00
August 1442.37 755.65 1323.29 35.47 1287.82 0.00 0.00
September 836.86 1177.27 991.05 0.36 990.70 0.00 0.00
October 291.12 1806.34 722.92 0.00 722.92 0.00 0.00
November 57.14 2617.70 491.44 0.00 491.44 0.00 0.00
December 2.31 3548.36 379.04 0.00 379.04 0.00 0.00
               
Annual Sum or Average 716.62 1978.87 1021.07 41.64 979.44 0.00 0.00
Minimum of Months 2.31 653.33 379.04 0.00 379.04 0.00 0.00
Maximum of Months 1993.26 3972.90 1807.68 207.78 1599.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 355.76 2415.29 691.97 317.24 374.73 0.00 0.00
February 791.22 1806.14 1082.30 537.34 544.97 0.00 0.00
March 1167.91 1492.83 1455.26 602.14 853.11 0.00 0.00
April 1784.35 1073.54 1856.76 920.20 936.56 0.00 0.00
May 2123.74 835.95 2051.04 912.58 1138.45 0.00 0.00
June 3174.42 528.16 2654.80 1366.16 1288.64 0.00 0.00
July 3595.61 416.09 2786.29 1575.16 1211.13 0.00 0.00
August 3053.58 465.08 2421.41 1349.13 1072.27 0.00 0.00
September 1954.15 721.79 1712.91 884.20 828.71 0.00 0.00
October 1150.07 1095.45 1228.92 624.03 604.89 0.00 0.00
November 521.16 1541.00 778.87 363.63 415.24 0.00 0.00
December 272.73 2116.04 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1667.06 1206.70 1610.67 809.61 801.06 0.00 0.00
Minimum of Months 272.73 416.09 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3595.61 2415.29 2786.29 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2956.65 3333.73 3186.14 2275.60 910.54 0.00 0.00
February 4142.36 2548.08 4057.51 2918.31 1139.20 0.00 0.00
March 3689.11 2290.87 3626.89 2036.69 1590.20 0.00 0.00
April 3077.21 1724.54 2915.42 1394.46 1520.96 0.00 0.00
May 2794.80 1336.52 2590.28 860.30 1729.98 0.00 0.00
June 3176.54 901.82 2573.71 750.61 1823.10 0.00 0.00
July 3819.76 706.94 2774.71 1024.96 1749.75 0.00 0.00
August 4400.73 799.99 3297.56 1662.56 1635.00 0.00 0.00
September 4528.96 1166.35 3657.38 2240.99 1416.39 0.00 0.00
October 4330.19 1674.67 3823.59 2643.96 1179.63 0.00 0.00
November 3584.24 2178.05 3485.98 2525.10 960.88 0.00 0.00
December 2858.98 2915.22 3029.84 2187.85 841.99 0.00 0.00
               
Annual Sum or Average 3609.18 1795.25 3245.98 1869.85 1376.13 0.00 0.00
Minimum of Months 2794.80 706.94 2573.71 750.61 841.99 0.00 0.00
Maximum of Months 4528.96 3333.73 4057.51 2918.31 1823.10 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 306.95 2593.75 626.78 252.60 374.18 0.00 0.00
February 778.42 1969.13 1069.82 525.87 543.95 0.00 0.00
March 1034.66 1697.57 1369.10 501.66 867.44 0.00 0.00
April 1673.46 1288.54 1787.37 791.89 995.48 0.00 0.00
May 2334.10 941.14 2210.85 1008.27 1202.59 0.00 0.00
June 2842.48 646.15 2405.32 1104.86 1300.47 0.00 0.00
July 3159.82 540.61 2463.99 1245.09 1218.90 0.00 0.00
August 2590.95 609.23 2092.26 1026.84 1065.42 0.00 0.00
September 1929.66 826.59 1683.09 850.90 832.19 0.00 0.00
October 1124.25 1255.10 1202.95 597.68 605.27 0.00 0.00
November 622.56 1758.30 851.57 422.45 429.12 0.00 0.00
December 273.87 2391.14 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1560.01 1374.27 1530.04 714.83 815.21 0.00 0.00
Minimum of Months 273.87 540.61 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3159.82 2593.75 2463.99 1245.09 1300.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.58 3734.47 452.02 0.00 452.02 0.00 0.00
February 117.29 2759.65 638.23 0.00 638.23 0.00 0.00
March 374.15 2226.76 1036.77 0.00 1036.77 0.00 0.00
April 637.97 1584.53 1182.14 6.90 1175.24 0.00 0.00
May 1163.60 1180.77 1552.43 91.99 1460.44 0.00 0.00
June 1854.85 763.42 1807.72 207.78 1599.93 0.00 0.00
July 2013.82 635.95 1651.45 154.68 1496.77 0.00 0.00
August 1465.95 727.13 1323.31 35.47 1287.84 0.00 0.00
September 863.71 1100.39 991.07 0.36 990.71 0.00 0.00
October 339.85 1626.70 722.93 0.00 722.93 0.00 0.00
November 83.64 2321.48 491.45 0.00 491.45 0.00 0.00
December 8.02 3187.12 379.05 0.00 379.05 0.00 0.00
               
Annual Sum or Average 748.76 1817.12 1021.09 41.64 979.45 0.00 0.00
Minimum of Months 8.02 635.95 379.05 0.00 379.05 0.00 0.00
Maximum of Months 2013.82 3734.47 1807.72 207.78 1599.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 372.08 2295.76 691.97 317.24 374.73 0.00 0.00
February 819.06 1696.14 1082.30 537.34 544.96 0.00 0.00
March 1195.46 1400.79 1455.25 602.14 853.11 0.00 0.00
April 1799.00 1010.59 1856.76 920.19 936.56 0.00 0.00
May 2129.31 788.67 2051.03 912.58 1138.45 0.00 0.00
June 3162.75 518.98 2654.79 1366.15 1288.64 0.00 0.00
July 3579.47 424.07 2786.28 1575.16 1211.12 0.00 0.00
August 3038.54 477.34 2421.40 1349.13 1072.27 0.00 0.00
September 1956.22 689.02 1712.90 884.19 828.71 0.00 0.00
October 1172.99 1016.72 1228.92 624.03 604.89 0.00 0.00
November 547.33 1416.02 778.86 363.63 415.24 0.00 0.00
December 292.92 1955.27 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1676.98 1138.76 1610.66 809.61 801.05 0.00 0.00
Minimum of Months 292.92 424.07 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3579.47 2295.76 2786.28 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2954.49 3259.57 3186.24 2275.68 910.56 0.00 0.00
February 4132.75 2469.54 4057.63 2918.40 1139.23 0.00 0.00
March 3683.31 2210.45 3627.00 2036.75 1590.24 0.00 0.00
April 3078.53 1649.07 2915.50 1394.50 1521.00 0.00 0.00
May 2790.58 1289.03 2590.34 860.32 1730.02 0.00 0.00
June 3172.44 880.39 2573.77 750.63 1823.13 0.00 0.00
July 3815.13 702.77 2774.78 1025.00 1749.79 0.00 0.00
August 4389.16 797.13 3297.64 1662.61 1635.03 0.00 0.00
September 4501.65 1141.78 3657.48 2241.06 1416.43 0.00 0.00
October 4313.47 1620.91 3823.70 2644.04 1179.66 0.00 0.00
November 3588.27 2088.61 3486.08 2525.18 960.91 0.00 0.00
December 2882.50 2773.54 3029.94 2187.92 842.02 0.00 0.00
               
Annual Sum or Average 3604.47 1737.53 3246.08 1869.91 1376.16 0.00 0.00
Minimum of Months 2790.58 702.77 2573.77 750.63 842.02 0.00 0.00
Maximum of Months 4501.65 3259.57 4057.63 2918.40 1823.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 321.74 2422.95 626.78 252.60 374.18 0.00 0.00
February 821.80 1773.66 1069.81 525.87 543.95 0.00 0.00
March 1096.56 1492.38 1369.10 501.66 867.44 0.00 0.00
April 1743.05 1101.40 1787.37 791.89 995.48 0.00 0.00
May 2361.08 865.37 2210.84 1008.26 1202.58 0.00 0.00
June 2872.76 595.99 2405.31 1104.85 1300.46 0.00 0.00
July 3193.56 499.92 2463.98 1245.08 1218.89 0.00 0.00
August 2637.96 539.72 2092.25 1026.83 1065.42 0.00 0.00
September 1954.08 757.81 1683.08 850.90 832.18 0.00 0.00
October 1174.76 1097.48 1202.94 597.68 605.26 0.00 0.00
November 670.19 1506.31 851.57 422.45 429.12 0.00 0.00
December 308.42 2052.34 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1600.35 1223.51 1530.03 714.83 815.21 0.00 0.00
Minimum of Months 308.42 499.92 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3193.56 2422.95 2463.98 1245.08 1300.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.08 3600.33 452.02 0.00 452.02 0.00 0.00
February 140.62 2624.16 638.23 0.00 638.23 0.00 0.00
March 413.02 2091.06 1036.77 0.00 1036.77 0.00 0.00
April 690.19 1456.73 1182.14 6.90 1175.24 0.00 0.00
May 1202.19 1103.26 1552.43 91.99 1460.44 0.00 0.00
June 1871.53 737.60 1807.72 207.78 1599.93 0.00 0.00
July 2016.68 624.56 1651.45 154.68 1496.77 0.00 0.00
August 1474.40 703.38 1323.31 35.47 1287.84 0.00 0.00
September 890.42 1028.81 991.07 0.36 990.71 0.00 0.00
October 389.42 1474.20 722.93 0.00 722.93 0.00 0.00
November 104.38 2139.49 491.45 0.00 491.45 0.00 0.00
December 10.74 3040.82 379.05 0.00 379.05 0.00 0.00
               
Annual Sum or Average 772.65 1715.40 1021.09 41.64 979.45 0.00 0.00
Minimum of Months 10.74 624.56 379.05 0.00 379.05 0.00 0.00
Maximum of Months 2016.68 3600.33 1807.72 207.78 1599.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 384.33 2214.05 691.97 317.24 374.73 0.00 0.00
February 844.28 1616.12 1082.30 537.34 544.96 0.00 0.00
March 1223.99 1323.52 1455.25 602.14 853.11 0.00 0.00
April 1825.28 945.57 1856.76 920.19 936.56 0.00 0.00
May 2140.75 748.82 2051.03 912.58 1138.45 0.00 0.00
June 3160.31 510.33 2654.79 1366.15 1288.64 0.00 0.00
July 3570.51 423.21 2786.28 1575.16 1211.12 0.00 0.00
August 3033.06 472.21 2421.40 1349.13 1072.27 0.00 0.00
September 1963.31 661.08 1712.90 884.19 828.71 0.00 0.00
October 1205.56 938.10 1228.92 624.03 604.89 0.00 0.00
November 573.35 1313.57 778.86 363.63 415.24 0.00 0.00
December 304.19 1866.83 574.46 246.73 327.73 0.00 0.00
               
Annual Sum or Average 1690.52 1084.27 1610.66 809.61 801.05 0.00 0.00
Minimum of Months 304.19 423.21 574.46 246.73 327.73 0.00 0.00
Maximum of Months 3570.51 2214.05 2786.28 1575.16 1288.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2993.25 3116.55 3186.24 2275.68 910.56 0.00 0.00
February 4177.65 2335.14 4057.63 2918.40 1139.23 0.00 0.00
March 3721.85 2080.86 3627.00 2036.75 1590.24 0.00 0.00
April 3114.34 1537.36 2915.50 1394.50 1521.00 0.00 0.00
May 2808.09 1218.17 2590.34 860.32 1730.02 0.00 0.00
June 3173.56 856.51 2573.77 750.63 1823.13 0.00 0.00
July 3807.65 694.14 2774.78 1025.00 1749.79 0.00 0.00
August 4383.16 781.57 3297.64 1662.61 1635.03 0.00 0.00
September 4509.31 1090.40 3657.48 2241.06 1416.43 0.00 0.00
October 4352.89 1497.31 3823.70 2644.04 1179.66 0.00 0.00
November 3646.42 1929.88 3486.08 2525.18 960.91 0.00 0.00
December 2925.18 2629.08 3029.94 2187.92 842.02 0.00 0.00
               
Annual Sum or Average 3630.24 1644.81 3246.08 1869.91 1376.16 0.00 0.00
Minimum of Months 2808.09 694.14 2573.77 750.63 842.02 0.00 0.00
Maximum of Months 4509.31 3116.55 4057.63 2918.40 1823.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 330.23 2337.39 626.78 252.60 374.18 0.00 0.00
February 836.52 1695.08 1069.81 525.87 543.95 0.00 0.00
March 1113.20 1417.76 1369.10 501.66 867.44 0.00 0.00
April 1763.43 1036.01 1787.37 791.89 995.48 0.00 0.00
May 2370.32 822.45 2210.84 1008.26 1202.58 0.00 0.00
June 2872.56 582.10 2405.31 1104.85 1300.46 0.00 0.00
July 3189.04 494.67 2463.98 1245.08 1218.89 0.00 0.00
August 2636.73 530.07 2092.25 1026.83 1065.42 0.00 0.00
September 1960.43 725.16 1683.08 850.90 832.18 0.00 0.00
October 1196.09 1021.06 1202.94 597.68 605.26 0.00 0.00
November 687.16 1409.11 851.57 422.45 429.12 0.00 0.00
December 315.90 1966.85 572.41 241.60 330.81 0.00 0.00
               
Annual Sum or Average 1609.94 1168.03 1530.03 714.83 815.21 0.00 0.00
Minimum of Months 315.90 494.67 572.41 241.60 330.81 0.00 0.00
Maximum of Months 3189.04 2337.39 2463.98 1245.08 1300.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 19690478.26 0.106410E+11 0.121067E+10 0.00 0.121067E+10 0.00 0.00
February 0.185486E+09 0.725306E+10 0.154397E+10 0.00 0.154397E+10 0.00 0.00
March 0.829835E+09 0.654935E+10 0.277683E+10 0.00 0.277683E+10 0.00 0.00
April 0.149292E+10 0.455237E+10 0.306404E+10 17880853.02 0.304616E+10 0.00 0.00
May 0.301330E+10 0.339819E+10 0.415795E+10 0.246381E+09 0.391156E+10 0.00 0.00
June 0.475297E+10 0.205924E+10 0.468551E+10 0.538554E+09 0.414696E+10 0.00 0.00
July 0.533875E+10 0.174988E+10 0.442316E+10 0.414277E+09 0.400889E+10 0.00 0.00
August 0.386325E+10 0.202393E+10 0.354431E+10 95002625.92 0.344930E+10 0.00 0.00
September 0.216915E+10 0.305149E+10 0.256881E+10 921816.40 0.256789E+10 0.00 0.00
October 0.779736E+09 0.483811E+10 0.193626E+10 0.00 0.193626E+10 0.00 0.00
November 0.148109E+09 0.678508E+10 0.127382E+10 0.00 0.127382E+10 0.00 0.00
December 6199892.79 0.950392E+10 0.101522E+10 0.00 0.101522E+10 0.00 0.00
               
Annual Sum or Average 0.225994E+11 0.624056E+11 0.322005E+11 0.131302E+10 0.308875E+11 0.00 0.00
Minimum of Months 6199892.79 0.174988E+10 0.101522E+10 0.00 0.101522E+10 0.00 0.00
Maximum of Months 0.533875E+10 0.106410E+11 0.468551E+10 0.538554E+09 0.414696E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.952863E+09 0.646912E+10 0.185337E+10 0.849697E+09 0.100368E+10 0.00 0.00
February 0.191412E+10 0.436941E+10 0.261831E+10 0.129993E+10 0.131838E+10 0.00 0.00
March 0.312813E+10 0.399840E+10 0.389776E+10 0.161278E+10 0.228497E+10 0.00 0.00
April 0.462504E+10 0.278261E+10 0.481273E+10 0.238515E+10 0.242758E+10 0.00 0.00
May 0.568822E+10 0.223901E+10 0.549350E+10 0.244426E+10 0.304924E+10 0.00 0.00
June 0.822811E+10 0.136899E+10 0.688124E+10 0.354108E+10 0.334016E+10 0.00 0.00
July 0.963048E+10 0.111446E+10 0.746279E+10 0.421892E+10 0.324388E+10 0.00 0.00
August 0.817871E+10 0.124567E+10 0.648550E+10 0.361352E+10 0.287198E+10 0.00 0.00
September 0.506516E+10 0.187089E+10 0.443986E+10 0.229184E+10 0.214802E+10 0.00 0.00
October 0.308035E+10 0.293404E+10 0.329155E+10 0.167140E+10 0.162015E+10 0.00 0.00
November 0.135085E+10 0.399428E+10 0.201882E+10 0.942526E+09 0.107630E+10 0.00 0.00
December 0.730482E+09 0.566761E+10 0.153863E+10 0.660846E+09 0.877787E+09 0.00 0.00
               
Annual Sum or Average 0.525725E+11 0.380545E+11 0.507941E+11 0.255320E+11 0.252621E+11 0.00 0.00
Minimum of Months 0.730482E+09 0.111446E+10 0.153863E+10 0.660846E+09 0.877787E+09 0.00 0.00
Maximum of Months 0.963048E+10 0.646912E+10 0.746279E+10 0.421892E+10 0.334016E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.791908E+10 0.892905E+10 0.853377E+10 0.609498E+10 0.243879E+10 0.00 0.00
February 0.100212E+11 0.616432E+10 0.981593E+10 0.705997E+10 0.275596E+10 0.00 0.00
March 0.988092E+10 0.613588E+10 0.971426E+10 0.545506E+10 0.425920E+10 0.00 0.00
April 0.797613E+10 0.447000E+10 0.755676E+10 0.361443E+10 0.394233E+10 0.00 0.00
May 0.748560E+10 0.357973E+10 0.693780E+10 0.230422E+10 0.463359E+10 0.00 0.00
June 0.823360E+10 0.233752E+10 0.667105E+10 0.194558E+10 0.472547E+10 0.00 0.00
July 0.102309E+11 0.189347E+10 0.743179E+10 0.274526E+10 0.468653E+10 0.00 0.00
August 0.117869E+11 0.214269E+10 0.883217E+10 0.445300E+10 0.437918E+10 0.00 0.00
September 0.117391E+11 0.302317E+10 0.947992E+10 0.580863E+10 0.367129E+10 0.00 0.00
October 0.115980E+11 0.448545E+10 0.102411E+11 0.708157E+10 0.315953E+10 0.00 0.00
November 0.929034E+10 0.564550E+10 0.903565E+10 0.654505E+10 0.249060E+10 0.00 0.00
December 0.765749E+10 0.780813E+10 0.811513E+10 0.585994E+10 0.225520E+10 0.00 0.00
               
Annual Sum or Average 0.113819E+12 0.566149E+11 0.102365E+12 0.589677E+11 0.433977E+11 0.00 0.00
Minimum of Months 0.748560E+10 0.189347E+10 0.667105E+10 0.194558E+10 0.225520E+10 0.00 0.00
Maximum of Months 0.117869E+11 0.892905E+10 0.102411E+11 0.708157E+10 0.472547E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.822135E+09 0.694711E+10 0.167876E+10 0.676554E+09 0.100221E+10 0.00 0.00
February 0.188315E+10 0.476372E+10 0.258810E+10 0.127218E+10 0.131592E+10 0.00 0.00
March 0.277124E+10 0.454676E+10 0.366701E+10 0.134365E+10 0.232336E+10 0.00 0.00
April 0.433760E+10 0.333989E+10 0.463287E+10 0.205258E+10 0.258030E+10 0.00 0.00
May 0.625165E+10 0.252074E+10 0.592155E+10 0.270054E+10 0.322101E+10 0.00 0.00
June 0.736770E+10 0.167481E+10 0.623460E+10 0.286378E+10 0.337081E+10 0.00 0.00
July 0.846325E+10 0.144797E+10 0.659954E+10 0.333485E+10 0.326470E+10 0.00 0.00
August 0.693960E+10 0.163176E+10 0.560390E+10 0.275028E+10 0.285362E+10 0.00 0.00
September 0.500167E+10 0.214253E+10 0.436257E+10 0.220554E+10 0.215703E+10 0.00 0.00
October 0.301120E+10 0.336166E+10 0.322197E+10 0.160082E+10 0.162115E+10 0.00 0.00
November 0.161367E+10 0.455750E+10 0.220727E+10 0.109500E+10 0.111228E+10 0.00 0.00
December 0.733529E+09 0.640442E+10 0.153315E+10 0.647098E+09 0.886049E+09 0.00 0.00
               
Annual Sum or Average 0.491964E+11 0.433389E+11 0.482513E+11 0.225429E+11 0.257084E+11 0.00 0.00
Minimum of Months 0.733529E+09 0.144797E+10 0.153315E+10 0.647098E+09 0.886049E+09 0.00 0.00
Maximum of Months 0.846325E+10 0.694711E+10 0.659954E+10 0.333485E+10 0.337081E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 41722084.11 0.100024E+11 0.121069E+10 0.00 0.121069E+10 0.00 0.00
February 0.283747E+09 0.667614E+10 0.154399E+10 0.00 0.154399E+10 0.00 0.00
March 0.100213E+10 0.596415E+10 0.277688E+10 0.00 0.277688E+10 0.00 0.00
April 0.165363E+10 0.410710E+10 0.306410E+10 17881386.28 0.304622E+10 0.00 0.00
May 0.311660E+10 0.316259E+10 0.415802E+10 0.246389E+09 0.391163E+10 0.00 0.00
June 0.480776E+10 0.197877E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00
July 0.539381E+10 0.170332E+10 0.442324E+10 0.414289E+09 0.400895E+10 0.00 0.00
August 0.392641E+10 0.194754E+10 0.354436E+10 95005459.17 0.344936E+10 0.00 0.00
September 0.223873E+10 0.285221E+10 0.256885E+10 921843.89 0.256793E+10 0.00 0.00
October 0.910255E+09 0.435694E+10 0.193629E+10 0.00 0.193629E+10 0.00 0.00
November 0.216783E+09 0.601727E+10 0.127385E+10 0.00 0.127385E+10 0.00 0.00
December 21475302.38 0.853638E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
               
Annual Sum or Average 0.236131E+11 0.573048E+11 0.322011E+11 0.131306E+10 0.308881E+11 0.00 0.00
Minimum of Months 21475302.38 0.170332E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
Maximum of Months 0.539381E+10 0.100024E+11 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.996576E+09 0.614897E+10 0.185337E+10 0.849694E+09 0.100367E+10 0.00 0.00
February 0.198148E+10 0.410331E+10 0.261830E+10 0.129992E+10 0.131838E+10 0.00 0.00
March 0.320193E+10 0.375187E+10 0.389774E+10 0.161278E+10 0.228496E+10 0.00 0.00
April 0.466302E+10 0.261946E+10 0.481271E+10 0.238514E+10 0.242757E+10 0.00 0.00
May 0.570316E+10 0.211236E+10 0.549347E+10 0.244425E+10 0.304922E+10 0.00 0.00
June 0.819784E+10 0.134520E+10 0.688122E+10 0.354107E+10 0.334015E+10 0.00 0.00
July 0.958727E+10 0.113582E+10 0.746276E+10 0.421890E+10 0.324386E+10 0.00 0.00
August 0.813842E+10 0.127852E+10 0.648547E+10 0.361351E+10 0.287197E+10 0.00 0.00
September 0.507053E+10 0.178595E+10 0.443984E+10 0.229183E+10 0.214801E+10 0.00 0.00
October 0.314174E+10 0.272318E+10 0.329153E+10 0.167139E+10 0.162014E+10 0.00 0.00
November 0.141868E+10 0.367034E+10 0.201882E+10 0.942522E+09 0.107629E+10 0.00 0.00
December 0.784550E+09 0.523701E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
               
Annual Sum or Average 0.528852E+11 0.359120E+11 0.507939E+11 0.255318E+11 0.252620E+11 0.00 0.00
Minimum of Months 0.784550E+09 0.113582E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
Maximum of Months 0.958727E+10 0.614897E+10 0.746276E+10 0.421890E+10 0.334015E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.791329E+10 0.873042E+10 0.853404E+10 0.609518E+10 0.243886E+10 0.00 0.00
February 0.999794E+10 0.597430E+10 0.981623E+10 0.706020E+10 0.275603E+10 0.00 0.00
March 0.986536E+10 0.592047E+10 0.971455E+10 0.545524E+10 0.425930E+10 0.00 0.00
April 0.797954E+10 0.427440E+10 0.755697E+10 0.361455E+10 0.394242E+10 0.00 0.00
May 0.747430E+10 0.345253E+10 0.693798E+10 0.230429E+10 0.463369E+10 0.00 0.00
June 0.822297E+10 0.228198E+10 0.667121E+10 0.194564E+10 0.472556E+10 0.00 0.00
July 0.102184E+11 0.188229E+10 0.743197E+10 0.274535E+10 0.468662E+10 0.00 0.00
August 0.117559E+11 0.213503E+10 0.883241E+10 0.445314E+10 0.437927E+10 0.00 0.00
September 0.116683E+11 0.295949E+10 0.948020E+10 0.580882E+10 0.367137E+10 0.00 0.00
October 0.115532E+11 0.434144E+10 0.102414E+11 0.708180E+10 0.315960E+10 0.00 0.00
November 0.930079E+10 0.541367E+10 0.903593E+10 0.654527E+10 0.249067E+10 0.00 0.00
December 0.772049E+10 0.742866E+10 0.811539E+10 0.586013E+10 0.225526E+10 0.00 0.00
               
Annual Sum or Average 0.113671E+12 0.547947E+11 0.102368E+12 0.589696E+11 0.433987E+11 0.00 0.00
Minimum of Months 0.747430E+10 0.188229E+10 0.667121E+10 0.194564E+10 0.225526E+10 0.00 0.00
Maximum of Months 0.117559E+11 0.873042E+10 0.102414E+11 0.708180E+10 0.472556E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.861749E+09 0.648962E+10 0.167876E+10 0.676552E+09 0.100221E+10 0.00 0.00
February 0.198811E+10 0.429085E+10 0.258809E+10 0.127218E+10 0.131591E+10 0.00 0.00
March 0.293703E+10 0.399718E+10 0.366700E+10 0.134364E+10 0.232335E+10 0.00 0.00
April 0.451799E+10 0.285482E+10 0.463285E+10 0.205257E+10 0.258029E+10 0.00 0.00
May 0.632391E+10 0.231781E+10 0.592153E+10 0.270053E+10 0.322099E+10 0.00 0.00
June 0.744620E+10 0.154481E+10 0.623457E+10 0.286377E+10 0.337080E+10 0.00 0.00
July 0.855363E+10 0.133899E+10 0.659951E+10 0.333483E+10 0.326468E+10 0.00 0.00
August 0.706551E+10 0.144558E+10 0.560388E+10 0.275026E+10 0.285361E+10 0.00 0.00
September 0.506497E+10 0.196423E+10 0.436255E+10 0.220553E+10 0.215702E+10 0.00 0.00
October 0.314648E+10 0.293950E+10 0.322196E+10 0.160082E+10 0.162114E+10 0.00 0.00
November 0.173714E+10 0.390436E+10 0.220727E+10 0.109499E+10 0.111227E+10 0.00 0.00
December 0.826068E+09 0.549698E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
               
Annual Sum or Average 0.504688E+11 0.385847E+11 0.482511E+11 0.225428E+11 0.257083E+11 0.00 0.00
Minimum of Months 0.826068E+09 0.133899E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
Maximum of Months 0.855363E+10 0.648962E+10 0.659951E+10 0.333483E+10 0.337080E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 59127059.33 0.964311E+10 0.121069E+10 0.00 0.121069E+10 0.00 0.00
February 0.340190E+09 0.634837E+10 0.154399E+10 0.00 0.154399E+10 0.00 0.00
March 0.110622E+10 0.560069E+10 0.277688E+10 0.00 0.277688E+10 0.00 0.00
April 0.178898E+10 0.377585E+10 0.306410E+10 17881386.28 0.304622E+10 0.00 0.00
May 0.321993E+10 0.295496E+10 0.415802E+10 0.246389E+09 0.391163E+10 0.00 0.00
June 0.485099E+10 0.191186E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00
July 0.540147E+10 0.167283E+10 0.442324E+10 0.414289E+09 0.400895E+10 0.00 0.00
August 0.394904E+10 0.188394E+10 0.354436E+10 95005459.17 0.344936E+10 0.00 0.00
September 0.230798E+10 0.266667E+10 0.256885E+10 921843.89 0.256793E+10 0.00 0.00
October 0.104303E+10 0.394849E+10 0.193629E+10 0.00 0.193629E+10 0.00 0.00
November 0.270563E+09 0.554557E+10 0.127385E+10 0.00 0.127385E+10 0.00 0.00
December 28777957.44 0.814453E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
               
Annual Sum or Average 0.243663E+11 0.540969E+11 0.322011E+11 0.131306E+10 0.308881E+11 0.00 0.00
Minimum of Months 28777957.44 0.167283E+10 0.101523E+10 0.00 0.101523E+10 0.00 0.00
Maximum of Months 0.540147E+10 0.964311E+10 0.468560E+10 0.538570E+09 0.414703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.102938E+10 0.593010E+10 0.185337E+10 0.849694E+09 0.100367E+10 0.00 0.00
February 0.204248E+10 0.390973E+10 0.261830E+10 0.129992E+10 0.131838E+10 0.00 0.00
March 0.327833E+10 0.354492E+10 0.389774E+10 0.161278E+10 0.228496E+10 0.00 0.00
April 0.473112E+10 0.245092E+10 0.481271E+10 0.238514E+10 0.242757E+10 0.00 0.00
May 0.573379E+10 0.200565E+10 0.549347E+10 0.244425E+10 0.304922E+10 0.00 0.00
June 0.819151E+10 0.132279E+10 0.688122E+10 0.354107E+10 0.334015E+10 0.00 0.00
July 0.956325E+10 0.113351E+10 0.746276E+10 0.421890E+10 0.324386E+10 0.00 0.00
August 0.812374E+10 0.126478E+10 0.648547E+10 0.361351E+10 0.287197E+10 0.00 0.00
September 0.508891E+10 0.171353E+10 0.443984E+10 0.229183E+10 0.214801E+10 0.00 0.00
October 0.322897E+10 0.251261E+10 0.329153E+10 0.167139E+10 0.162014E+10 0.00 0.00
November 0.148612E+10 0.340478E+10 0.201882E+10 0.942522E+09 0.107629E+10 0.00 0.00
December 0.814734E+09 0.500011E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
               
Annual Sum or Average 0.533123E+11 0.341934E+11 0.507939E+11 0.255318E+11 0.252620E+11 0.00 0.00
Minimum of Months 0.814734E+09 0.113351E+10 0.153863E+10 0.660844E+09 0.877783E+09 0.00 0.00
Maximum of Months 0.956325E+10 0.593010E+10 0.746276E+10 0.421890E+10 0.334015E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.801711E+10 0.834737E+10 0.853404E+10 0.609518E+10 0.243886E+10 0.00 0.00
February 0.101066E+11 0.564916E+10 0.981623E+10 0.706020E+10 0.275603E+10 0.00 0.00
March 0.996859E+10 0.557337E+10 0.971455E+10 0.545524E+10 0.425930E+10 0.00 0.00
April 0.807238E+10 0.398484E+10 0.755697E+10 0.361455E+10 0.394242E+10 0.00 0.00
May 0.752120E+10 0.326274E+10 0.693798E+10 0.230429E+10 0.463369E+10 0.00 0.00
June 0.822587E+10 0.222007E+10 0.667121E+10 0.194564E+10 0.472556E+10 0.00 0.00
July 0.101984E+11 0.185918E+10 0.743197E+10 0.274535E+10 0.468662E+10 0.00 0.00
August 0.117399E+11 0.209335E+10 0.883241E+10 0.445314E+10 0.437927E+10 0.00 0.00
September 0.116881E+11 0.282631E+10 0.948020E+10 0.580882E+10 0.367137E+10 0.00 0.00
October 0.116588E+11 0.401040E+10 0.102414E+11 0.708180E+10 0.315960E+10 0.00 0.00
November 0.945151E+10 0.500225E+10 0.903593E+10 0.654527E+10 0.249067E+10 0.00 0.00
December 0.783481E+10 0.704172E+10 0.811539E+10 0.586013E+10 0.225526E+10 0.00 0.00
               
Annual Sum or Average 0.114483E+12 0.518708E+11 0.102368E+12 0.589696E+11 0.433987E+11 0.00 0.00
Minimum of Months 0.752120E+10 0.185918E+10 0.667121E+10 0.194564E+10 0.225526E+10 0.00 0.00
Maximum of Months 0.117399E+11 0.834737E+10 0.102414E+11 0.708180E+10 0.472556E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.884481E+09 0.626046E+10 0.167876E+10 0.676552E+09 0.100221E+10 0.00 0.00
February 0.202371E+10 0.410073E+10 0.258809E+10 0.127218E+10 0.131591E+10 0.00 0.00
March 0.298160E+10 0.379732E+10 0.366700E+10 0.134364E+10 0.232335E+10 0.00 0.00
April 0.457082E+10 0.268534E+10 0.463285E+10 0.205257E+10 0.258029E+10 0.00 0.00
May 0.634868E+10 0.220284E+10 0.592153E+10 0.270053E+10 0.322099E+10 0.00 0.00
June 0.744566E+10 0.150881E+10 0.623457E+10 0.286377E+10 0.337080E+10 0.00 0.00
July 0.854154E+10 0.132493E+10 0.659951E+10 0.333483E+10 0.326468E+10 0.00 0.00
August 0.706222E+10 0.141973E+10 0.560388E+10 0.275026E+10 0.285361E+10 0.00 0.00
September 0.508144E+10 0.187961E+10 0.436255E+10 0.220553E+10 0.215702E+10 0.00 0.00
October 0.320360E+10 0.273480E+10 0.322196E+10 0.160082E+10 0.162114E+10 0.00 0.00
November 0.178111E+10 0.365241E+10 0.220727E+10 0.109499E+10 0.111227E+10 0.00 0.00
December 0.846095E+09 0.526802E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
               
Annual Sum or Average 0.507710E+11 0.368350E+11 0.482511E+11 0.225428E+11 0.257083E+11 0.00 0.00
Minimum of Months 0.846095E+09 0.132493E+10 0.153314E+10 0.647096E+09 0.886046E+09 0.00 0.00
Maximum of Months 0.854154E+10 0.626046E+10 0.659951E+10 0.333483E+10 0.337080E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -8.8 -10.9 -16.1 5.70 -23.3 32.48 106.19 0.00
February -2.2 -5.0 -9.9 6.21 -16.1 41.31 158.25 0.00
March 0.30 -2.9 -8.4 5.38 -12.8 78.62 145.02 0.00
April 6.67 2.34 -2.9 4.89 -6.2 82.10 182.32 0.01
May 10.10 5.18 0.22 5.28 -1.1 102.67 205.47 0.01
June 16.46 10.06 4.91 4.56 5.05 103.05 264.47 0.02
July 20.57 12.46 6.56 4.24 8.00 89.47 301.47 0.00
August 19.17 11.04 4.61 4.29 7.19 78.96 261.05 0.00
September 14.69 9.08 4.37 5.43 3.42 63.03 204.21 0.00
October 8.64 4.13 -1.0 5.38 -4.2 47.64 162.42 0.00
November 2.84 -0.9 -6.9 5.91 -11.0 33.00 125.52 0.00
December -4.1 -6.5 -11.1 5.64 -18.2 26.54 97.81 0.00
                 
Annual Sum or Average 7.07 2.37 -2.9 5.23 -5.7 65.04 184.63 0.00
Minimum of Months -8.8 -10.9 -16.1 4.24 -23.3 26.54 97.81 0.00
Maximum of Months 20.57 12.46 6.56 6.21 8.00 103.05 301.47 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.60 14-JAN-12:00 5.16 -1.1 8.20 -2.3 105.00 464.50
February 18.90 27-FEB-14:00 7.23 -7.8 5.20 1.37 76.00 634.50
March 15.00 14-MAR-13:20 6.67 -2.4 9.30 1.23 201.67 711.67
April 23.30 07-APR-13:00 9.68 -4.4 9.30 4.92 314.50 110.00
May 30.00 20-MAY-15:00 15.22 5.60 6.70 20.57 215.50 18.50
June 32.20 29-JUN-12:00 14.40 0.60 9.30 17.03 187.00 729.00
July 37.20 17-JUL-15:00 17.28 4.40 4.60 20.22 119.50 797.00
August 35.60 05-AUG-15:00 17.65 6.70 5.20 22.47 136.50 625.50
September 34.40 02-SEP-14:00 16.28 4.40 7.70 20.75 95.50 789.50
October 25.00 18-OCT-13:00 11.40 -1.1 7.70 7.35 48.00 913.00
November 17.20 04-NOV-13:00 8.18 -1.1 11.30 2.22 81.00 689.50
December 13.90 10-DEC-01:00 5.50 -5.0 13.90 5.74 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.60   5.16 -7.8 4.60 -2.3 0.00 0.00
Maximum of Months 37.20   17.65 6.70 13.90 22.47 314.50 913.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -33.9 10-JAN-21:00 -34.1 -37.8 3.10 -54.3 0.00 0.00
February -25.0 01-FEB-03:00 -25.2 -27.8 2.10 -45.6 0.00 0.00
March -23.3 04-MAR-23:00 -23.8 -28.9 3.60 -44.5 0.00 0.00
April -7.8 29-APR-03:00 -8.7 -10.6 4.10 -25.6 0.00 0.00
May -2.8 08-MAY-00:10 -3.3 -3.9 6.18 -10.2 0.00 0.00
June 0.60 15-JUN-03:00 -0.5 -1.7 2.60 -15.7 0.00 0.00
July 5.60 08-JUL-03:00 2.99 0.00 4.10 -9.2 0.00 0.00
August 6.70 17-AUG-00:00 4.32 1.70 2.60 -7.1 0.00 0.00
September 0.00 17-SEP-02:00 -1.6 -3.9 4.10 -16.8 0.00 0.00
October -6.1 10-OCT-05:19 -6.6 -7.8 3.77 -20.6 0.00 0.00
November -16.7 26-NOV-07:00 -17.3 -20.6 4.60 -33.8 19.50 94.00
December -28.3 29-DEC-08:00 -28.6 -32.2 2.10 -48.7 69.50 0.00
                 
Annual Sum or Average                
Minimum of Months -33.9   -34.1 -37.8 2.10 -54.3 0.00 0.00
Maximum of Months 6.70   4.32 1.70 6.18 -7.1 69.50 94.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.18 13-JAN-14:00 10.00 0.00 8.80 -3.0 40.00 694.00
February 7.23 27-FEB-14:00 18.90 -7.8 5.20 1.37 76.00 634.50
March 6.94 14-MAR-13:00 15.00 -1.7 10.30 1.80 241.00 538.00
April 11.02 06-APR-15:00 22.20 1.10 3.60 5.33 110.00 779.00
May 15.22 20-MAY-15:00 30.00 5.60 6.70 20.57 215.50 18.50
June 19.20 20-JUN-14:00 29.40 14.40 2.60 18.28 204.00 614.00
July 19.21 19-JUL-11:00 29.40 14.40 8.80 19.52 306.50 563.50
August 17.65 05-AUG-15:00 35.60 6.70 5.20 22.47 136.50 625.50
September 20.12 07-SEP-15:20 25.17 17.93 4.10 15.88 127.67 652.00
October 11.61 18-OCT-14:00 25.00 -0.6 7.70 7.55 40.50 852.00
November 8.89 17-NOV-16:00 17.20 1.10 11.30 4.10 0.00 0.00
December 7.62 19-DEC-14:00 12.80 2.80 8.20 1.37 74.00 138.50
                 
Annual Sum or Average                
Minimum of Months 5.18   10.00 -7.8 2.60 -3.0 0.00 0.00
Maximum of Months 20.12   35.60 17.93 11.30 22.47 306.50 852.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.70 12-JAN-14:00 7.20 4.48 5.20 -1.0 107.00 61.00
February -0.6 11-FEB-08:00 4.40 2.16 10.80 -5.7 69.50 50.50
March -0.6 10-MAR-12:00 8.90 4.51 10.30 -2.3 253.00 140.50
April 6.10 17-APR-16:19 7.97 6.96 4.50 0.87 201.50 117.50
May 12.20 02-MAY-12:00 18.90 14.61 12.90 14.84 108.50 934.50
June 15.60 20-JUN-19:00 25.60 18.76 3.60 20.22 17.50 17.00
July 16.70 18-JUL-21:00 19.40 17.51 4.10 16.49 0.00 0.00
August 11.10 08-AUG-11:00 26.70 16.75 2.60 12.03 134.50 869.00
September 18.30 07-SEP-14:00 24.40 20.10 4.10 15.57 111.00 720.00
October 6.70 01-OCT-14:09 9.08 7.78 2.10 4.07 260.33 0.33
November 3.30 16-NOV-19:00 10.60 6.88 9.80 -1.7 0.00 0.00
December 2.80 19-DEC-14:09 10.97 6.81 10.78 -1.0 95.00 292.00
                 
Annual Sum or Average                
Minimum of Months -0.6   4.40 2.16 2.10 -5.7 0.00 0.00
Maximum of Months 18.30   26.70 20.10 12.90 20.22 260.33 934.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 5.41 12.59 0.00
February 18.00 13.00 16.00 4.46 20.37 0.00
March 18.00 13.00 16.00 5.03 30.19 0.00
April 18.00 13.00 16.00 7.01 37.07 0.00
May 18.00 13.00 16.00 9.90 46.35 0.00
June 18.00 13.00 16.00 12.91 55.45 0.00
July 18.00 13.00 16.00 15.24 57.38 0.00
August 18.00 13.00 16.00 16.26 48.01 0.00
September 18.00 13.00 16.00 15.67 34.51 0.00
October 18.00 13.00 16.00 13.64 22.84 0.00
November 18.00 13.00 16.00 10.74 14.52 0.00
December 18.00 13.00 16.00 7.74 10.24 0.00
             
Annual Sum or Average 18.00 13.00 16.00 10.37 32.53 0.00
Minimum of Months 18.00 13.00 16.00 4.46 10.24 0.00
Maximum of Months 18.00 13.00 16.00 16.26 57.38 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.436859E+11 -0.426369E+11 0.00 0.00 744.00 0.00 -0.104892E+10 58.99 0.00 0.00
February 0.403610E+11 -0.394250E+11 0.00 0.00 672.00 0.00 -935960464.6 58.98 0.00 0.00
March 0.469302E+11 -0.458978E+11 0.00 0.00 744.00 0.00 -0.103240E+10 58.98 0.00 0.00
April 0.410870E+11 -0.400940E+11 0.00 0.00 720.00 0.00 -992974006.6 58.98 0.00 0.00
May 0.414898E+11 -0.404645E+11 0.00 0.00 744.00 0.00 -0.102530E+10 58.98 0.00 0.00
June 0.386219E+11 -0.376295E+11 0.00 0.00 720.00 0.00 -992388715.7 58.98 0.00 0.00
July 0.349796E+11 -0.339604E+11 0.00 0.00 744.00 0.00 -0.101919E+10 58.98 0.00 0.00
August 0.373659E+11 -0.363426E+11 0.00 0.00 744.00 0.00 -0.102329E+10 58.97 0.00 0.00
September 0.344094E+11 -0.334210E+11 0.00 0.00 720.00 0.00 -988419292.2 58.97 0.00 0.00
October 0.371110E+11 -0.360906E+11 0.00 0.00 744.00 0.00 -0.102036E+10 58.97 0.00 0.00
November 0.386508E+11 -0.376621E+11 0.00 0.00 720.00 0.00 -988774192.4 58.97 0.00 0.00
December 0.408244E+11 -0.397945E+11 0.00 0.00 744.00 0.00 -0.102987E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.475517E+12 -0.463419E+12 0.00 0.00 8760.00 0.00 -0.120979E+11 58.98 0.00 0.00
Minimum of Months 0.344094E+11 -0.458978E+11 0.00 0.00 672.00 0.00 -0.104892E+10 58.97 0.00 0.00
Maximum of Months 0.469302E+11 -0.334210E+11 0.00 0.00 744.00 0.00 -935960464.6 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 226.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 275.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 304.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 325.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 385.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 434.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 417.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 421.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 352.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 317.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 269.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 236.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3965.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 226.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 434.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.598126E+11 103258.03 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.329097E+11 96883.97 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.179924E+11 83854.98 04-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.410754E+10 45516.70 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.293158E+10 36392.75 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.113068E+09 15446.64 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.887931E+09 20886.20 19-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.336346E+10 36211.44 10-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.120175E+11 65676.18 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.341690E+11 99810.91 29-DEC-08:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.168305E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.598126E+11 103258.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.332737E+10 15095.78 18-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.999054E+09 14780.47 11-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.226301E+09 13965.28 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 2064419.59 1069.71 08-MAY-05:06 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.121006E+09 13976.57 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.763495E+09 14087.99 28-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.543929E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.332737E+10 15095.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319889E+10 15822.69 31-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.132125E+10 16122.39 11-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.474191E+09 16019.40 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 55376055.64 10551.11 15-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 32357541.16 5192.24 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 3638105.76 693.23 19-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 41101978.97 3251.03 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.443701E+09 15808.10 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.150060E+10 16229.06 16-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.707111E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319889E+10 16229.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.376151E+10 23190.29 17-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.126099E+10 23168.48 23-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.503285E+09 21920.59 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 67137452.68 19166.52 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.109038E+09 23218.64 08-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 8810060.62 1868.11 19-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 49896257.70 18451.36 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.448435E+09 23193.84 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.137629E+10 23191.86 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.758539E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.376151E+10 23218.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.237616E+10 15111.00 30-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.502363E+09 15094.49 09-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 66993328.60 15096.08 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 7039226.47 2008.44 22-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 36410700.46 15095.70 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.178336E+09 15090.78 29-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.316730E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.237616E+10 15111.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.732674E+12 1116038.05 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.453617E+12 1033935.17 01-FEB-07:07 0.00 0.00 0.00 0.00 0.00
March 0.318381E+12 902358.33 04-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.114583E+12 524517.79 29-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.736923E+11 420036.32 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.587426E+10 263744.73 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 0.101762E+09 46946.95 08-JUL-06:10 0.00 0.00 0.00 0.00 0.00
August 0.156477E+10 99720.32 18-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.239898E+11 272706.04 19-SEP-06:30 0.00 0.00 0.00 0.00 0.00
October 0.858357E+11 512196.41 10-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.231761E+12 722960.93 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.527710E+12 1077860.06 29-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.256978E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.101762E+09 46946.95   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.732674E+12 1116038.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.114457E+11 638713.16 10-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.264673E+10 638242.19 06-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.118914E+10 638051.46 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.572816E+09 636084.74 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.315899E+10 638254.04 26-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190134E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114457E+11 638713.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.988770E+11 149171.20 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.496007E+11 134288.26 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.246844E+11 142493.18 30-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.438396E+10 142067.30 28-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.310571E+10 141546.92 23-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.751293E+09 142549.56 20-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.378379E+10 142518.13 05-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.244530E+11 142553.15 03-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.629701E+11 133352.59 29-DEC-07:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272610E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.988770E+11 149171.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.769324E+11 183650.11 09-JAN-06:14 0.00 0.00 0.00 0.00 0.00
February 0.395949E+11 183680.49 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.230549E+11 183604.57 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.607023E+10 181786.76 15-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.408077E+10 195135.09 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.136484E+09 22996.44 17-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 47016913.46 24519.21 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.164619E+10 113690.42 20-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.590571E+10 181789.35 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.248178E+11 195373.95 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.540810E+11 184086.55 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236367E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.769324E+11 195373.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.751244E+11 222094.62 11-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.326027E+11 222111.06 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.204196E+11 222021.28 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.595492E+10 231278.11 19-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.524114E+10 237546.30 23-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.171194E+09 31183.35 17-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 79734081.64 30318.20 18-AUG-05:04 0.00 0.00 0.00 0.00 0.00
September 0.106518E+10 125110.39 19-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.300702E+10 220392.92 10-OCT-04:41 0.00 0.00 0.00 0.00 0.00
November 0.193785E+11 222051.58 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.461490E+11 222756.95 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.209193E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.751244E+11 237546.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.732064E+11 196437.35 30-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.359387E+11 196545.11 06-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.217386E+11 196463.61 06-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.538954E+10 194525.75 29-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.385823E+10 200634.66 22-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.174175E+09 33135.90 17-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 98914955.83 29345.36 18-AUG-05:04 0.00 0.00 0.00 0.00 0.00
September 0.170238E+10 102504.55 19-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.547610E+10 195276.21 10-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.215513E+11 196491.11 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.473173E+11 195411.67 26-DEC-04:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.216452E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.732064E+11 200634.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.840420E+11 120651.26 09-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.530162E+11 111640.67 01-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.416783E+11 101065.17 04-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.181895E+11 60853.53 29-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.116148E+11 48447.44 08-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.145143E+10 31490.23 16-JUN-07:00 0.00 0.00 0.00 0.00 0.00
July 73515691.36 9463.88 05-JUL-06:20 0.00 0.00 0.00 0.00 0.00
August 0.537851E+09 15822.51 28-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.510892E+10 33289.99 19-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.141097E+11 58577.97 10-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.306745E+11 78733.27 27-NOV-07:20 0.00 0.00 0.00 0.00 0.00
December 0.629578E+11 114954.04 29-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.323454E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 73515691.36 9463.88   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.840420E+11 120651.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.146453E+11 80063.48 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.582507E+10 80054.93 11-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.311099E+10 79764.64 20-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.264987E+09 79011.81 10-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.833293E+09 80037.98 08-MAY-05:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.455101E+09 80039.38 10-OCT-05:04 0.00 0.00 0.00 0.00 0.00
November 0.356752E+10 79723.43 13-NOV-05:24 0.00 0.00 0.00 0.00 0.00
December 0.851134E+10 79781.42 04-DEC-06:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.372136E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146453E+11 80063.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.183300E+11 20284.94 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.102936E+11 17059.64 01-FEB-07:07 0.00 0.00 0.00 0.00 0.00
March 0.699638E+10 16809.03 20-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.237264E+10 16814.08 10-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.164291E+10 16812.57 01-MAY-04:33 0.00 0.00 0.00 0.00 0.00
June 72822313.18 16721.55 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 43449564.28 16725.99 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.717703E+09 16785.53 20-SEP-04:03 0.00 0.00 0.00 0.00 0.00
October 0.241585E+10 16858.93 10-OCT-04:25 0.00 0.00 0.00 0.00 0.00
November 0.724039E+10 16814.77 06-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.138130E+11 18413.67 29-DEC-08:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.639387E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.183300E+11 20284.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.125262E+11 18433.85 12-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.675626E+10 18437.24 08-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.465918E+10 18434.64 09-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.169328E+10 18375.63 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.116962E+10 18483.73 08-MAY-04:43 0.00 0.00 0.00 0.00 0.00
June 76866765.43 17246.63 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 5261980.32 1808.17 05-JUL-05:08 0.00 0.00 0.00 0.00 0.00
August 47357987.32 12471.23 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.579177E+09 18349.91 13-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.169254E+10 18362.82 05-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.511558E+10 18483.41 29-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.963865E+10 18435.40 19-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.439600E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5261980.32 1808.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125262E+11 18483.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.141282E+11 24445.88 11-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.684228E+10 24003.30 14-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.533144E+10 23998.89 09-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.226349E+10 23906.05 29-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.184725E+10 24088.76 08-MAY-04:14 0.00 0.00 0.00 0.00 0.00
June 0.211037E+09 23872.35 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 10549064.50 1971.90 08-JUL-05:05 0.00 0.00 0.00 0.00 0.00
August 77580503.02 19337.98 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.668820E+09 23969.78 19-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.163020E+10 24093.59 10-OCT-04:53 0.00 0.00 0.00 0.00 0.00
November 0.499922E+10 24087.73 29-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.102046E+11 23999.86 19-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.482147E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10549064.50 1971.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141282E+11 24445.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122185E+11 20968.33 18-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.628770E+10 20971.14 17-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.465143E+10 20958.67 04-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.172115E+10 20882.84 19-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.122496E+10 20953.51 22-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.150772E+09 11483.35 17-JUN-04:02 0.00 0.00 0.00 0.00 0.00
July 1526320.81 320.72 08-JUL-05:40 0.00 0.00 0.00 0.00 0.00
August 70027111.04 12299.81 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.687166E+09 20837.88 19-SEP-04:01 0.00 0.00 0.00 0.00 0.00
October 0.180353E+10 20945.69 10-OCT-04:12 0.00 0.00 0.00 0.00 0.00
November 0.462646E+10 20962.82 14-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.855086E+10 20968.76 04-DEC-04:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.419941E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1526320.81 320.72   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122185E+11 20971.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319450E+09 23714.12 10-JAN-22:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319450E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319450E+09 23714.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:02 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.668222E+09 0.668222E+09 44378.93 27-FEB-15:30 44378.93 0.00
March 0.00 0.00 47762575.90 47762575.90 9966.38 14-MAR-13:30 9966.38 0.00
April 0.00 0.00 0.684875E+10 0.684875E+10 86545.32 07-APR-14:00 86545.32 0.00
May 0.00 0.00 0.187044E+11 0.187044E+11 117249.50 19-MAY-15:20 117249.50 0.02
June 0.00 0.00 0.621322E+11 0.620638E+11 137820.64 29-JUN-14:50 137820.64 0.19
July 0.00 0.00 0.106594E+12 0.106443E+12 164290.46 17-JUL-15:40 164290.46 0.30
August 0.00 0.00 0.982073E+11 0.982073E+11 162762.80 07-AUG-15:20 162762.80 0.14
September 0.00 0.00 0.400732E+11 0.386793E+11 201959.36 07-SEP-15:00 106758.95 0.12
October 0.00 0.00 0.108484E+11 0.108484E+11 103923.85 18-OCT-15:50 103923.85 0.00
November 0.00 0.00 0.603942E+09 0.603942E+09 19068.72 17-NOV-17:00 19068.72 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.344728E+12 0.343114E+12       0.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.106594E+12 0.106443E+12 201959.36   164290.46 0.30



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 12346.86 12346.86 3.72 02-JAN-05:24 3.72 0.00
February 0.00 0.00 0.481262E+10 0.481262E+10 317620.76 27-FEB-13:50 317620.76 0.00
March 0.00 0.00 0.149095E+09 0.149095E+09 45260.37 14-MAR-13:30 45260.37 0.00
April 0.00 0.00 0.487552E+11 0.487552E+11 668693.39 06-APR-16:00 668693.39 0.00
May 0.00 0.00 0.159328E+12 0.159328E+12 1124859.96 19-MAY-15:20 1124859.96 0.02
June 0.00 0.00 0.531036E+12 0.530444E+12 1312498.82 29-JUN-14:50 1312498.82 0.18
July 0.00 0.00 0.891038E+12 0.890185E+12 1518576.57 17-JUL-15:40 1518576.57 0.27
August 0.00 0.00 0.771346E+12 0.771346E+12 1410966.27 10-AUG-15:40 1410966.27 0.12
September 0.00 0.00 0.351058E+12 0.338388E+12 1874627.15 07-SEP-15:00 992409.20 0.12
October 0.00 0.00 0.856662E+11 0.856662E+11 885272.71 18-OCT-15:10 885272.71 0.00
November 0.00 0.00 0.429216E+10 0.429216E+10 152718.07 03-NOV-14:00 152718.07 0.00
December 0.00 0.00 18227.04 18227.04 4.72 14-DEC-05:01 4.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.284748E+13 0.283337E+13       0.06
Minimum of Months 0.00 0.00 12346.86 12346.86 3.72   3.72 0.00
Maximum of Months 0.00 0.00 0.891038E+12 0.890185E+12 1874627.15   1518576.57 0.27



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2274.08 2274.08 0.71 11-JAN-06:08 0.71 0.00
February 0.00 0.00 0.324425E+09 0.324425E+09 21826.99 27-FEB-15:30 21826.99 0.00
March 0.00 0.00 2489376.22 2489376.22 696.31 14-MAR-14:00 696.31 0.00
April 0.00 0.00 0.450198E+10 0.450198E+10 66876.09 06-APR-16:00 66876.09 0.00
May 0.00 0.00 0.163879E+11 0.163879E+11 132937.35 19-MAY-15:30 132937.35 0.02
June 0.00 0.00 0.578964E+11 0.578252E+11 155101.84 29-JUN-15:00 155101.84 0.17
July 0.00 0.00 0.981358E+11 0.980708E+11 185803.12 17-JUL-15:30 185803.12 0.27
August 0.00 0.00 0.826728E+11 0.826728E+11 167623.81 07-AUG-15:50 167623.81 0.11
September 0.00 0.00 0.357250E+11 0.344700E+11 191018.01 07-SEP-15:20 109280.12 0.11
October 0.00 0.00 0.731607E+10 0.731607E+10 90887.39 18-OCT-15:00 90887.39 0.00
November 0.00 0.00 0.304082E+09 0.304082E+09 11133.88 17-NOV-17:00 11133.88 0.00
December 0.00 0.00 10175.89 10175.89 69.91 04-DEC-04:46 69.91 0.00
                 
Annual Sum or Average 0.00 0.00 0.303267E+12 0.301876E+12       0.06
Minimum of Months 0.00 0.00 2274.08 2274.08 0.71   0.71 0.00
Maximum of Months 0.00 0.00 0.981358E+11 0.980708E+11 191018.01   185803.12 0.27



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.282783E+09 0.282783E+09 24820.80 27-FEB-15:00 24820.80 0.00
March 0.00 0.00 13603.64 13603.64 22.67 07-MAR-19:50 22.67 0.00
April 0.00 0.00 0.245389E+10 0.245389E+10 50035.33 07-APR-14:00 50035.33 0.00
May 0.00 0.00 0.921493E+10 0.921493E+10 79182.78 29-MAY-15:02 79182.78 0.02
June 0.00 0.00 0.318869E+11 0.318637E+11 68420.25 26-JUN-11:00 68420.25 0.14
July 0.00 0.00 0.540153E+11 0.539751E+11 119516.51 19-JUL-03:02 75800.38 0.24
August 0.00 0.00 0.502708E+11 0.502698E+11 105211.96 06-AUG-15:54 105211.96 0.14
September 0.00 0.00 0.210305E+11 0.206158E+11 109241.30 04-SEP-08:62 109241.30 0.10
October 0.00 0.00 0.595290E+10 0.595290E+10 60329.65 18-OCT-14:00 60329.65 0.00
November 0.00 0.00 91667054.30 91667054.30 28477.05 17-NOV-06:03 28477.05 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.175200E+12 0.174721E+12       0.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.540153E+11 0.539751E+11 119516.51   109241.30 0.24



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.361909E+12 0.328250E+12 142962.30 18-JAN-22:01 128986.99 0.00
February 0.00 0.00 0.575784E+12 0.522013E+12 245399.65 27-FEB-22:03 222099.61 0.00
March 0.00 0.00 0.910685E+12 0.827825E+12 440877.89 31-MAR-24:00 400397.01 0.00
April 0.00 0.00 0.114524E+13 0.104328E+13 449754.83 24-APR-21:02 407450.27 0.00
May 0.00 0.00 0.375786E+12 0.342806E+12 238081.21 31-MAY-24:00 217599.45 0.00
June 0.00 0.00 0.620356E+12 0.573415E+12 330267.18 30-JUN-23:02 309028.28 0.00
July 0.00 0.00 0.894926E+12 0.842158E+12 427134.26 31-JUL-24:00 400767.91 0.00
August 0.00 0.00 0.116139E+13 0.108102E+13 456799.34 04-AUG-00:25 411584.40 0.00
September 0.00 0.00 0.366932E+12 0.336771E+12 238747.67 30-SEP-24:00 217327.62 0.00
October 0.00 0.00 0.649209E+12 0.590738E+12 340967.62 31-OCT-24:00 309926.37 0.00
November 0.00 0.00 0.889825E+12 0.806765E+12 349084.27 06-NOV-22:03 315595.10 0.00
December 0.00 0.00 0.118270E+13 0.107455E+13 448640.98 07-DEC-24:00 406798.23 0.00
                 
Annual Sum or Average 0.00 0.00 0.913475E+13 0.836959E+13       0.00
Minimum of Months 0.00 0.00 0.361909E+12 0.328250E+12 142962.30   128986.99 0.00
Maximum of Months 0.00 0.00 0.118270E+13 0.108102E+13 456799.34   411584.40 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.289943E+10 0.289911E+10 2188.32 13-JAN-16:20 2188.32 0.00
February 0.00 0.00 0.819962E+10 0.819962E+10 4834.21 26-FEB-17:14 4834.21 0.00
March 0.00 0.00 0.148985E+11 0.148985E+11 7467.03 31-MAR-24:00 7467.03 0.00
April 0.00 0.00 0.199971E+11 0.199896E+11 8873.66 22-APR-18:10 8873.66 0.00
May 0.00 0.00 0.559262E+10 0.557105E+10 4139.15 31-MAY-24:00 4139.15 0.00
June 0.00 0.00 0.108705E+11 0.107904E+11 5991.51 30-JUN-24:00 5991.51 0.00
July 0.00 0.00 0.165395E+11 0.164503E+11 7871.64 31-JUL-23:35 7871.64 0.00
August 0.00 0.00 0.215283E+11 0.214652E+11 8850.50 05-AUG-20:12 8850.50 0.00
September 0.00 0.00 0.567817E+10 0.559615E+10 3948.60 30-SEP-24:00 3948.60 0.00
October 0.00 0.00 0.105001E+11 0.104895E+11 5598.15 31-OCT-24:00 5598.15 0.00
November 0.00 0.00 0.145875E+11 0.145858E+11 6496.40 03-NOV-16:00 6441.50 0.00
December 0.00 0.00 0.194587E+11 0.194584E+11 8260.01 10-DEC-16:10 8260.01 0.00
                 
Annual Sum or Average 0.00 0.00 0.150750E+12 0.150394E+12       0.00
Minimum of Months 0.00 0.00 0.289943E+10 0.289911E+10 2188.32   2188.32 0.00
Maximum of Months 0.00 0.00 0.215283E+11 0.214652E+11 8873.66   8873.66 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.830672E+10 0.830364E+10 18012.41 13-JAN-16:30 18012.41 0.00
February 0.00 0.00 0.591940E+11 0.591940E+11 42648.69 28-FEB-17:00 42648.69 0.00
March 0.00 0.00 0.124458E+12 0.124458E+12 65300.66 31-MAR-23:30 65300.66 0.00
April 0.00 0.00 0.179736E+12 0.179659E+12 82415.87 25-APR-18:00 82415.87 0.00
May 0.00 0.00 0.453476E+11 0.451359E+11 39148.00 31-MAY-24:00 39148.00 0.00
June 0.00 0.00 0.100138E+12 0.993392E+11 58470.88 30-JUN-24:00 58470.88 0.00
July 0.00 0.00 0.156279E+12 0.155387E+12 76721.69 31-JUL-23:55 76721.69 0.00
August 0.00 0.00 0.202432E+12 0.201800E+12 84091.67 03-AUG-19:00 84091.67 0.00
September 0.00 0.00 0.479241E+11 0.471217E+11 34913.64 30-SEP-23:40 34913.64 0.00
October 0.00 0.00 0.877932E+11 0.876879E+11 47671.08 31-OCT-24:00 47671.08 0.00
November 0.00 0.00 0.120788E+12 0.120770E+12 59983.80 03-NOV-16:00 59435.75 0.00
December 0.00 0.00 0.158815E+12 0.158812E+12 74768.39 06-DEC-16:10 74485.33 0.00
                 
Annual Sum or Average 0.00 0.00 0.129121E+13 0.128767E+13       0.00
Minimum of Months 0.00 0.00 0.830672E+10 0.830364E+10 18012.41   18012.41 0.00
Maximum of Months 0.00 0.00 0.202432E+12 0.201800E+12 84091.67   84091.67 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.230045E+09 0.230045E+09 1717.40 13-JAN-16:30 1717.40 0.00
February 0.00 0.00 0.427029E+10 0.427029E+10 4220.91 28-FEB-17:00 4220.91 0.00
March 0.00 0.00 0.108040E+11 0.108040E+11 6164.11 28-MAR-17:50 6164.11 0.00
April 0.00 0.00 0.168079E+11 0.168004E+11 8308.89 25-APR-18:00 8308.89 0.00
May 0.00 0.00 0.386146E+10 0.384062E+10 3843.15 31-MAY-24:00 3843.15 0.00
June 0.00 0.00 0.980741E+10 0.972772E+10 5857.38 30-JUN-24:00 5857.38 0.00
July 0.00 0.00 0.155838E+11 0.154948E+11 7631.69 31-JUL-23:55 7631.69 0.00
August 0.00 0.00 0.201183E+11 0.200552E+11 8557.07 05-AUG-19:57 8557.07 0.00
September 0.00 0.00 0.425735E+10 0.417828E+10 3403.05 04-SEP-17:32 3403.05 0.00
October 0.00 0.00 0.739448E+10 0.738418E+10 4565.94 18-OCT-16:50 4565.94 0.00
November 0.00 0.00 0.101922E+11 0.101905E+11 5935.38 03-NOV-16:00 5880.69 0.00
December 0.00 0.00 0.138238E+11 0.138235E+11 7386.01 06-DEC-16:10 7359.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.117151E+12 0.116800E+12       0.00
Minimum of Months 0.00 0.00 0.230045E+09 0.230045E+09 1717.40   1717.40 0.00
Maximum of Months 0.00 0.00 0.201183E+11 0.200552E+11 8557.07   8557.07 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 480023.47 2527902.40 09-JAN-07:02
February 0.00 0.00 01-FEB-00:10 303164.77 2015123.65 01-FEB-07:03
March 0.00 0.00 01-MAR-00:10 183234.93 1911868.99 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 63893.97 1281219.27 29-APR-05:01
May 0.00 0.00 01-MAY-00:10 41209.60 1451349.99 22-MAY-04:01
June 0.00 0.00 01-JUN-00:10 3222.62 342073.22 16-JUN-06:10
July 0.00 0.00 01-JUL-00:10 70.17 56890.50 08-JUL-06:10
August 0.00 0.00 01-AUG-00:03 951.21 151553.94 18-AUG-06:05
September 0.00 0.00 01-SEP-00:02 14460.37 740681.87 19-SEP-05:03
October 0.00 0.00 01-OCT-00:10 47974.42 1275256.03 11-OCT-05:01
November 0.00 0.00 01-NOV-00:10 149839.85 1661552.86 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 330493.89 2057964.46 29-DEC-07:03
             
Annual Sum or Average 0.00     134339.20    
Minimum of Months 0.00 0.00   70.17 56890.50  
Maximum of Months 0.00 0.00   480023.47 2527902.40  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 305.84 23912.03 25-JAN-05:10 0.00 0.00 01-JAN-00:05
February 5693.53 826197.23 27-FEB-15:30 0.00 0.00 01-FEB-00:10
March 825.67 152822.36 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 46551.88 1213503.56 07-APR-12:40 0.00 0.00 01-APR-00:10
May 133338.71 1456136.29 19-MAY-15:30 0.00 0.00 01-MAY-00:10
June 363351.68 1684751.88 29-JUN-14:50 0.00 0.00 01-JUN-00:10
July 556560.39 1966244.79 17-JUL-15:40 0.00 0.00 01-JUL-00:10
August 482858.86 2019470.65 07-AUG-15:30 0.00 0.00 01-AUG-00:03
September 263757.44 2704073.55 07-SEP-15:00 0.00 0.00 01-SEP-00:02
October 70926.62 1218008.98 16-OCT-12:40 0.00 0.00 01-OCT-00:10
November 5550.35 362823.85 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 264.85 23960.44 04-DEC-04:46 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 162008.96     0.00    
Minimum of Months 264.85 23912.03   0.00 0.00  
Maximum of Months 556560.39 2704073.55   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 0.00 0.00 01-JAN-00:05
February 2647.44 445040.33 27-FEB-15:30 0.00 0.00 01-FEB-00:10
March 92.70 67616.28 14-MAR-13:30 0.00 0.00 01-MAR-00:10
April 26208.98 947434.34 06-APR-16:00 0.00 0.00 01-APR-00:10
May 82155.35 1445921.39 19-MAY-15:20 0.00 0.00 01-MAY-00:10
June 281583.70 1675261.25 29-JUN-14:50 0.00 0.00 01-JUN-00:10
July 453509.67 1957819.28 17-JUL-15:40 0.00 0.00 01-JUL-00:10
August 393777.54 2035012.82 07-AUG-15:30 0.00 0.00 01-AUG-00:03
September 186087.32 2531478.16 07-SEP-15:00 0.00 0.00 01-SEP-00:02
October 44595.02 1206972.75 18-OCT-14:00 0.00 0.00 01-OCT-00:10
November 2160.65 180549.92 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 0.01 75.24 04-DEC-04:46 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 123707.91     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 453509.67 2531478.16   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 178882.23 203101.59 13-JAN-16:30 0.00 0.00 01-JAN-00:05
February 339929.93 609079.57 27-FEB-16:00 0.00 0.00 01-FEB-00:10
March 496669.48 646691.25 31-MAR-24:00 0.00 0.00 01-MAR-00:10
April 703935.88 1327720.89 07-APR-14:00 0.00 0.00 01-APR-00:10
May 257135.32 975040.46 20-MAY-16:00 0.00 0.00 01-MAY-00:10
June 575841.98 1377905.50 29-JUN-15:00 0.00 0.00 01-JUN-00:10
July 970669.83 1956865.43 17-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1125235.96 2072271.40 06-AUG-16:00 0.00 0.00 01-AUG-00:03
September 339770.54 1245137.13 02-SEP-17:00 0.00 0.00 01-SEP-00:02
October 387310.63 961169.91 18-OCT-15:00 0.00 0.00 01-OCT-00:10
November 506782.82 750693.74 17-NOV-17:00 0.00 0.00 01-NOV-00:10
December 640662.97 768649.98 10-DEC-02:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 545374.06     0.00    
Minimum of Months 178882.23 203101.59   0.00 0.00  
Maximum of Months 1125235.96 2072271.40   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 17320.88 58837.17 31-JAN-12:50
February 0.00 0.00 01-FEB-00:10 17697.89 59145.27 16-FEB-12:40
March 0.00 0.00 01-MAR-00:10 18534.81 59081.24 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 16871.72 57467.63 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 16514.02 54935.49 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 15920.98 51670.33 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 14087.26 48630.05 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 14974.26 46956.75 01-AUG-11:40
September 0.00 0.00 01-SEP-00:02 14302.61 48062.99 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 14888.17 50858.03 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 15938.81 54021.94 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 16263.11 56856.14 29-DEC-12:40
             
Annual Sum or Average 0.00     16100.34    
Minimum of Months 0.00 0.00   14087.26 46956.75  
Maximum of Months 0.00 0.00   18534.81 59145.27  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9.65 13877.38 25-JAN-05:42 314.51 101747.55 17-JAN-06:30
February 2785.11 495057.03 27-FEB-15:30 521.01 104307.37 20-FEB-04:30
March 31.14 23677.28 01-MAR-07:00 713.37 120998.68 21-MAR-05:30
April 29179.71 932905.12 06-APR-16:00 1171.11 99930.25 14-APR-16:00
May 95345.93 2281590.76 19-MAY-14:40 963.97 121002.38 06-MAY-05:30
June 343872.09 2881577.65 20-JUN-15:20 640.58 86472.28 02-JUN-05:30
July 574789.11 3012469.21 17-JUL-16:00 328.18 55923.47 29-JUL-06:30
August 487455.53 2621173.96 07-AUG-15:30 941.10 63406.59 30-AUG-07:50
September 237331.38 4551358.72 07-SEP-15:00 560.53 96544.40 16-SEP-06:00
October 50561.47 1977586.91 18-OCT-12:20 1061.14 97708.60 31-OCT-10:00
November 2556.07 240598.81 17-NOV-17:00 919.02 113422.72 29-NOV-05:30
December 10.88 22090.58 20-DEC-07:00 280.48 113252.48 11-DEC-07:00
             
Annual Sum or Average 153206.78     701.40    
Minimum of Months 9.65 13877.38   280.48 55923.47  
Maximum of Months 574789.11 4551358.72   1171.11 121002.38  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.174828E+11 0.96 11794.21 01-JAN-00:10 1.73
February 0.155487E+11 0.94 11794.21 01-FEB-06:01 1.73
March 0.187145E+11 1.02 11794.21 01-MAR-04:20 1.72
April 0.174026E+11 0.98 11794.21 01-APR-04:01 1.73
May 0.185322E+11 1.01 11794.21 01-MAY-03:05 1.73
June 0.185411E+11 1.04 11794.21 01-JUN-03:02 1.71
July 0.185708E+11 1.01 11794.21 01-JUL-03:02 1.71
August 0.202277E+11 1.10 11794.21 01-AUG-03:02 1.71
September 0.189750E+11 1.06 11794.21 01-SEP-03:02 1.71
October 0.186655E+11 1.02 11794.21 01-OCT-23:40 1.72
November 0.177535E+11 1.00 11794.21 01-NOV-03:10 1.73
December 0.173201E+11 0.95 11794.21 01-DEC-05:01 1.73
           
Annual Sum or Average 0.217734E+12 1.01      
Minimum of Months 0.155487E+11 0.94 11794.21   1.71
Maximum of Months 0.202277E+11 1.10 11794.21   1.73



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.469374E+10 0.38 15628.84 18-JAN-06:01 1.60
February 0.527111E+10 0.41 16164.09 07-FEB-06:01 1.63
March 0.785973E+10 0.48 14652.00 28-MAR-15:40 1.54
April 0.966328E+10 0.55 20031.02 24-APR-15:00 1.86
May 0.890906E+10 0.52 18710.42 30-MAY-05:03 1.78
June 0.135143E+11 0.69 24654.76 21-JUN-05:03 2.11
July 0.163002E+11 0.78 24654.76 18-JUL-05:02 2.12
August 0.177722E+11 0.84 24654.76 07-AUG-04:02 2.12
September 0.981073E+10 0.57 24654.76 05-SEP-05:03 2.12
October 0.877571E+10 0.50 17440.54 16-OCT-16:00 1.71
November 0.736984E+10 0.46 14960.79 06-NOV-14:50 1.56
December 0.633126E+10 0.42 16164.09 23-DEC-06:01 1.64
           
Annual Sum or Average 0.116271E+12 0.55      
Minimum of Months 0.469374E+10 0.38 14652.00   1.54
Maximum of Months 0.177722E+11 0.84 24654.76   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.435905E+11 0.42 60836.23 09-JAN-05:11 0.96
February 0.397318E+11 0.40 138182.32 28-FEB-06:02 1.55
March 0.510296E+11 0.42 140044.96 02-MAR-06:02 1.57
April 0.554782E+11 0.42 158627.52 19-APR-05:02 1.69
May 0.667292E+11 0.46 176480.97 22-MAY-04:01 1.81
June 0.104582E+12 0.61 221023.48 21-JUN-05:03 2.07
July 0.122355E+12 0.64 210393.23 31-JUL-15:40 2.01
August 0.119194E+12 0.64 228333.16 07-AUG-05:03 2.12
September 0.762832E+11 0.50 228333.16 05-SEP-03:02 2.12
October 0.570605E+11 0.41 143431.07 31-OCT-05:02 1.59
November 0.452959E+11 0.39 150463.13 06-NOV-06:01 1.64
December 0.432169E+11 0.40 60836.23 26-DEC-05:01 0.96
           
Annual Sum or Average 0.824546E+12 0.48      
Minimum of Months 0.397318E+11 0.39 60836.23   0.96
Maximum of Months 0.122355E+12 0.64 228333.16   2.12



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.541981E+10 0.50 5635.22 02-JAN-04:11 0.86
February 0.425912E+10 0.43 5635.22 01-FEB-05:01 0.87
March 0.462097E+10 0.41 6227.97 28-MAR-15:50 0.91
April 0.448921E+10 0.38 12819.31 25-APR-16:00 1.38
May 0.580186E+10 0.42 18592.93 19-MAY-15:40 1.73
June 0.977286E+10 0.55 21703.86 29-JUN-14:50 1.91
July 0.120759E+11 0.60 25518.42 17-JUL-15:20 2.12
August 0.111030E+11 0.58 24310.91 11-AUG-15:40 2.06
September 0.645737E+10 0.44 17845.71 05-SEP-14:50 1.69
October 0.438305E+10 0.36 10504.68 18-OCT-16:00 1.23
November 0.423959E+10 0.40 5635.22 06-NOV-06:01 0.86
December 0.498120E+10 0.46 5635.22 01-DEC-06:01 0.86
           
Annual Sum or Average 0.776039E+11 0.46      
Minimum of Months 0.423959E+10 0.36 5635.22   0.86
Maximum of Months 0.120759E+11 0.60 25518.42   2.12



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.108058E+12 1.54 40344.20 01-JAN-00:05 1.54
February 0.976007E+11 1.54 40344.20 01-FEB-00:10 1.54
March 0.108058E+12 1.54 40344.20 01-MAR-00:10 1.54
April 0.104572E+12 1.54 40344.20 01-APR-00:10 1.54
May 0.108058E+12 1.54 40344.20 01-MAY-00:10 1.54
June 0.104572E+12 1.54 40344.20 01-JUN-00:10 1.54
July 0.108058E+12 1.54 40344.20 01-JUL-00:10 1.54
August 0.108058E+12 1.54 40344.20 01-AUG-00:03 1.54
September 0.104572E+12 1.54 40344.20 01-SEP-00:06 1.54
October 0.108058E+12 1.54 40344.20 01-OCT-00:10 1.54
November 0.104572E+12 1.54 40344.20 01-NOV-00:10 1.54
December 0.108058E+12 1.54 40344.20 01-DEC-00:10 1.54
           
Annual Sum or Average 0.127229E+13 1.54      
Minimum of Months 0.976007E+11 1.54 40344.20   1.54
Maximum of Months 0.108058E+12 1.54 40344.20   1.54



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.169392E+10 1.05 632.44 01-JAN-00:05 1.05
February 0.152999E+10 1.05 632.44 01-FEB-00:10 1.05
March 0.169392E+10 1.05 632.44 01-MAR-00:10 1.05
April 0.163927E+10 1.05 632.44 01-APR-00:10 1.05
May 0.169392E+10 1.05 632.44 01-MAY-00:10 1.05
June 0.163927E+10 1.05 632.44 01-JUN-00:10 1.05
July 0.169392E+10 1.05 632.44 01-JUL-00:10 1.05
August 0.169392E+10 1.05 632.44 01-AUG-00:03 1.05
September 0.163927E+10 1.05 632.44 01-SEP-00:02 1.05
October 0.169392E+10 1.05 632.44 01-OCT-00:10 1.05
November 0.163927E+10 1.05 632.44 01-NOV-00:10 1.05
December 0.169392E+10 1.05 632.44 01-DEC-00:10 1.05
           
Annual Sum or Average 0.199445E+11 1.05      
Minimum of Months 0.152999E+10 1.05 632.44   1.05
Maximum of Months 0.169392E+10 1.05 632.44   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.162084E+11 1.05 6051.52 01-JAN-00:10 1.05
February 0.146398E+11 1.05 6051.52 01-FEB-00:25 1.05
March 0.162084E+11 1.05 6051.52 01-MAR-00:10 1.05
April 0.156855E+11 1.05 6051.52 01-APR-00:10 1.05
May 0.162084E+11 1.05 6051.52 01-MAY-00:10 1.05
June 0.156855E+11 1.05 6051.52 01-JUN-00:10 1.05
July 0.162084E+11 1.05 6051.52 01-JUL-00:10 1.05
August 0.162084E+11 1.05 6051.52 01-AUG-00:03 1.05
September 0.156855E+11 1.05 6051.52 01-SEP-00:02 1.05
October 0.162084E+11 1.05 6051.52 01-OCT-00:10 1.05
November 0.156855E+11 1.05 6051.52 01-NOV-00:10 1.05
December 0.162084E+11 1.05 6051.52 01-DEC-00:10 1.05
           
Annual Sum or Average 0.190841E+12 1.05      
Minimum of Months 0.146398E+11 1.05 6051.52   1.05
Maximum of Months 0.162084E+11 1.05 6051.52   1.05



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.165013E+10 1.05 616.09 01-JAN-00:05 1.05
February 0.149044E+10 1.05 616.09 01-FEB-00:10 1.05
March 0.165013E+10 1.05 616.09 01-MAR-00:10 1.05
April 0.159690E+10 1.05 616.09 01-APR-00:10 1.05
May 0.165013E+10 1.05 616.09 01-MAY-00:10 1.05
June 0.159690E+10 1.05 616.09 01-JUN-00:20 1.05
July 0.165013E+10 1.05 616.09 01-JUL-00:10 1.05
August 0.165013E+10 1.05 616.09 01-AUG-00:03 1.05
September 0.159690E+10 1.05 616.09 01-SEP-00:02 1.05
October 0.165013E+10 1.05 616.09 01-OCT-00:10 1.05
November 0.159690E+10 1.05 616.09 01-NOV-00:10 1.05
December 0.165013E+10 1.05 616.09 01-DEC-00:10 1.05
           
Annual Sum or Average 0.194289E+11 1.05      
Minimum of Months 0.149044E+10 1.05 616.09   1.05
Maximum of Months 0.165013E+10 1.05 616.09   1.05



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.544035E+10 0.489631E+10 7120.99 09-JAN-07:06 6408.89 6408.89 50.51 18.21
February 0.315889E+10 0.284300E+10 6632.89 01-FEB-07:10 5969.60 5969.60 51.41 13.65
March 0.209107E+10 0.188196E+10 6405.33 06-MAR-07:03 5764.80 5764.80 45.93 12.31
April 0.692171E+09 0.622954E+09 4811.40 29-APR-05:01 4330.26 4330.26 38.14 6.99
May 0.463238E+09 0.416914E+09 4793.01 09-MAY-05:01 4313.71 4313.71 37.30 6.95
June 33884191.38 30495772.24 1420.56 16-JUN-07:00 1278.50 1278.50 30.11 1.56
July 745908.91 671318.02 224.40 08-JUL-06:10 201.96 201.96 23.18 0.23
August 10087189.47 9078470.53 589.75 18-AUG-06:05 530.78 530.78 23.51 0.62
September 0.153087E+09 0.137778E+09 2954.53 19-SEP-05:03 2659.08 2659.08 32.79 3.60
October 0.535079E+09 0.481571E+09 4574.99 11-OCT-05:01 4117.49 4117.49 34.85 6.47
November 0.163936E+10 0.147542E+10 6301.46 27-NOV-06:01 5671.32 5671.32 48.21 11.76
December 0.377872E+10 0.340085E+10 6805.02 29-DEC-08:00 6124.52 6124.52 52.38 14.95
                 
Annual Sum or Average 0.179967E+11 0.161970E+11            
Minimum of Months 745908.91 671318.02 224.40   201.96 201.96 23.18 0.23
Maximum of Months 0.544035E+10 0.489631E+10 7120.99   6408.89 6408.89 52.38 18.21



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 282.34 254.11 0.07 02-JAN-05:24 0.06 0.06 6.70 0.00
February 90655806.83 81590226.15 6056.42 27-FEB-13:40 5450.78 5450.78 7.79 10.73
March 4079062.29 3671156.06 1123.61 14-MAR-13:30 1011.25 1011.25 7.27 1.72
April 0.816187E+09 0.734568E+09 8551.16 06-APR-16:00 7696.04 7696.04 7.42 16.71
May 0.241263E+10 0.217137E+10 14273.89 19-MAY-16:00 12846.50 12846.50 6.77 43.53
June 0.774509E+10 0.697058E+10 14891.69 23-JUN-14:00 13402.52 13402.52 6.76 51.08
July 0.120772E+11 0.108695E+11 15697.36 17-JUL-16:00 14127.63 14127.63 6.75 64.30
August 0.100916E+11 0.908245E+10 15570.82 07-AUG-15:40 14013.74 14013.74 6.75 62.26
September 0.527761E+10 0.474985E+10 15092.84 01-SEP-16:00 13583.56 13583.56 6.76 54.19
October 0.134166E+10 0.120749E+10 10427.14 18-OCT-14:00 9384.42 9384.42 7.22 22.39
November 92582658.37 83324392.53 3373.25 03-NOV-14:00 3035.92 3035.92 7.26 5.49
December 569.87 512.88 1.39 04-DEC-04:46 1.26 1.26 6.99 0.00
                 
Annual Sum or Average 0.399493E+11 0.359544E+11            
Minimum of Months 282.34 254.11 0.07   0.06 0.06 6.70 0.00
Maximum of Months 0.120772E+11 0.108695E+11 15697.36   14127.63 14127.63 7.79 64.30



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.458370E+09 0.412533E+09 13378.05 01-JAN-13:32 12040.24 12040.24 6.76 93.76
February 0.114046E+10 0.102641E+10 13378.05 01-FEB-04:01 12040.24 12040.24 6.76 93.76
March 0.960907E+09 0.864816E+09 13378.05 01-MAR-05:01 12040.24 12040.24 6.84 93.76
April 0.477851E+10 0.430066E+10 13378.05 01-APR-12:05 12040.24 12040.24 6.76 93.76
May 0.902122E+10 0.811910E+10 13378.05 01-MAY-13:20 12040.24 12040.24 6.76 93.76
June 0.177539E+11 0.159785E+11 13378.05 01-JUN-03:02 12040.24 12040.24 7.37 93.76
July 0.243272E+11 0.218944E+11 13378.05 01-JUL-00:12 12040.24 12040.24 6.90 93.76
August 0.237696E+11 0.213926E+11 13378.05 01-AUG-00:03 12040.24 12040.24 6.86 93.76
September 0.136526E+11 0.122873E+11 13378.05 01-SEP-00:02 12040.24 12040.24 6.83 93.76
October 0.625064E+10 0.562558E+10 13378.05 02-OCT-05:05 12040.24 12040.24 7.67 93.76
November 0.200266E+10 0.180240E+10 13378.05 01-NOV-04:01 12040.24 12040.24 6.88 93.76
December 0.396898E+09 0.357208E+09 13378.05 01-DEC-04:33 12040.24 12040.24 6.76 93.76
                 
Annual Sum or Average 0.104513E+12 0.940616E+11            
Minimum of Months 0.396898E+09 0.357208E+09 13378.05   12040.24 12040.24 6.76 93.76
Maximum of Months 0.243272E+11 0.218944E+11 13378.05   12040.24 12040.24 7.67 93.76



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.979405E+10 0.881465E+10 3656.68 01-JAN-00:05 3291.01 3291.01 21.85 15.27
February 0.884624E+10 0.796162E+10 3656.68 01-FEB-00:10 3291.01 3291.01 24.25 15.27
March 0.979405E+10 0.881465E+10 3656.68 01-MAR-00:10 3291.01 3291.01 27.43 15.27
April 0.947812E+10 0.853031E+10 3656.68 01-APR-00:10 3291.01 3291.01 30.42 15.27
May 0.979405E+10 0.881465E+10 3656.68 01-MAY-00:10 3291.01 3291.01 22.36 15.27
June 0.947812E+10 0.853031E+10 3656.68 01-JUN-00:10 3291.01 3291.01 26.00 15.27
July 0.979405E+10 0.881465E+10 3656.68 01-JUL-00:10 3291.01 3291.01 34.65 15.27
August 0.979405E+10 0.881465E+10 3656.68 01-AUG-00:03 3291.01 3291.01 38.65 15.27
September 0.947812E+10 0.853031E+10 3656.68 01-SEP-00:02 3291.01 3291.01 25.52 15.27
October 0.979405E+10 0.881465E+10 3656.68 01-OCT-00:10 3291.01 3291.01 24.99 15.27
November 0.947812E+10 0.853031E+10 3656.68 01-NOV-00:10 3291.01 3291.01 27.68 15.27
December 0.979405E+10 0.881465E+10 3656.68 01-DEC-00:10 3291.01 3291.01 30.08 15.27
                 
Annual Sum or Average 0.115317E+12 0.103785E+12            
Minimum of Months 0.884624E+10 0.796162E+10 3656.68   3291.01 3291.01 21.85 15.27
Maximum of Months 0.979405E+10 0.881465E+10 3656.68   3291.01 3291.01 38.65 15.27



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:03 16.86 16.86 55.97 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:01 16.86 16.86 55.91 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:02 16.86 16.86 55.94 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:01 16.86 16.86 55.91 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 56.21 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 55.38 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:02 16.86 16.86 56.85 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 56.51 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 55.55 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.17 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 55.93 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:01 16.86 16.86 56.19 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.38 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 56.85 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.568770E+09 0.511893E+09 16602.14 25-JAN-05:42 14941.92 14941.92 21.16 55.31
February 0.141553E+10 0.127398E+10 16627.01 27-FEB-15:30 14964.31 14964.31 23.24 55.31
March 0.119234E+10 0.107310E+10 16602.64 01-MAR-07:00 14942.38 14942.38 21.20 55.31
April 0.600335E+10 0.540302E+10 33242.93 06-APR-14:20 29918.63 29918.63 22.77 110.61
May 0.119998E+11 0.107999E+11 33325.14 19-MAY-14:40 29992.62 29992.62 26.04 110.61
June 0.268510E+11 0.241659E+11 33361.43 20-JUN-15:20 30025.29 30025.29 27.33 110.61
July 0.395561E+11 0.356005E+11 33369.36 17-JUL-16:00 30032.42 30032.42 27.62 110.61
August 0.375346E+11 0.337811E+11 33345.67 07-AUG-15:30 30011.10 30011.10 26.77 110.61
September 0.195931E+11 0.176338E+11 33402.76 07-SEP-14:30 30062.49 30062.49 28.94 110.61
October 0.819189E+10 0.737270E+10 33306.77 18-OCT-12:20 29976.10 29976.10 25.38 110.61
November 0.248541E+10 0.223687E+10 16613.85 17-NOV-17:00 14952.46 14952.46 22.14 55.31
December 0.492491E+09 0.443242E+09 16602.56 20-DEC-07:00 14942.31 14942.31 21.20 55.31
                 
Annual Sum or Average 0.155884E+12 0.140296E+12            
Minimum of Months 0.492491E+09 0.443242E+09 16602.14   14941.92 14941.92 21.16 55.31
Maximum of Months 0.395561E+11 0.356005E+11 33402.76   30062.49 30062.49 28.94 110.61



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 35.81 35.81 480023.47 2527902.40 09-JAN-07:02
February 0.00 0.00 01-FEB-00:10 36.31 36.31 303164.77 2015123.65 01-FEB-07:03
March 0.00 0.00 01-MAR-00:10 31.63 31.63 183234.93 1911868.99 06-MAR-05:01
April 0.00 0.00 01-APR-00:10 31.93 31.93 63893.97 1281219.27 29-APR-05:01
May 0.00 0.00 01-MAY-00:10 28.20 82.00 41209.60 1451349.99 22-MAY-04:01
June 0.00 0.00 01-JUN-00:10 23.99 23.99 3222.62 342073.22 16-JUN-06:10
July 0.00 0.00 01-JUL-00:10 23.35 23.35 70.17 56890.50 08-JUL-06:10
August 0.00 0.00 01-AUG-00:03 22.95 22.95 951.21 151553.94 18-AUG-06:05
September 0.00 0.00 01-SEP-00:02 23.39 23.39 14460.37 740681.87 19-SEP-05:03
October 0.00 0.00 01-OCT-00:10 23.05 23.05 47974.42 1275256.03 11-OCT-05:01
November 0.00 0.00 01-NOV-00:10 32.21 32.21 149839.85 1661552.86 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 34.74 34.74 330493.89 2057964.46 29-DEC-07:03
                 
Annual Sum or Average 0.00         134339.20    
Minimum of Months 0.00 0.00   22.95 22.95 70.17 56890.50  
Maximum of Months 0.00 0.00   36.31 82.00 480023.47 2527902.40  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 305.84 23912.03 25-JAN-05:10 6.76 6.73 0.00 0.00 01-JAN-00:05
February 5693.53 826197.23 27-FEB-15:30 8.80 7.74 0.00 0.00 01-FEB-00:10
March 825.67 152822.36 14-MAR-13:30 7.09 6.89 0.00 0.00 01-MAR-00:10
April 46551.88 1213503.56 07-APR-12:40 9.79 8.12 0.00 0.00 01-APR-00:10
May 133338.71 1456136.29 19-MAY-15:30 10.41 6.70 0.00 0.00 01-MAY-00:10
June 363351.68 1684751.88 29-JUN-14:50 10.99 6.70 0.00 0.00 01-JUN-00:10
July 556560.39 1966244.79 17-JUL-15:40 11.71 6.70 0.00 0.00 01-JUL-00:10
August 482858.86 2019470.65 07-AUG-15:30 11.84 6.70 0.00 0.00 01-AUG-00:03
September 263757.44 2704073.55 07-SEP-15:00 13.59 7.89 0.00 0.00 01-SEP-00:02
October 70926.62 1218008.98 16-OCT-12:40 9.80 8.12 0.00 0.00 01-OCT-00:10
November 5550.35 362823.85 17-NOV-17:00 7.62 7.16 0.00 0.00 01-NOV-00:10
December 264.85 23960.44 04-DEC-04:46 6.76 6.73 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 162008.96         0.00    
Minimum of Months 264.85 23912.03   6.76 6.70 0.00 0.00  
Maximum of Months 556560.39 2704073.55   13.59 8.12 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 6.70 6.70 0.00 0.00 01-JAN-00:05
February 2647.44 445040.33 27-FEB-15:30 18.19 7.75 0.00 0.00 01-FEB-00:10
March 92.70 67616.28 14-MAR-13:30 16.07 6.89 0.00 0.00 01-MAR-00:10
April 26208.98 947434.34 06-APR-16:00 20.26 7.91 0.00 0.00 01-APR-00:10
May 82155.35 1445921.39 19-MAY-15:20 14.74 6.70 0.00 0.00 01-MAY-00:10
June 281583.70 1675261.25 29-JUN-14:50 22.52 6.70 0.00 0.00 01-JUN-00:10
July 453509.67 1957819.28 17-JUL-15:40 14.08 6.70 0.00 0.00 01-JUL-00:10
August 393777.54 2035012.82 07-AUG-15:30 14.83 6.70 0.00 0.00 01-AUG-00:03
September 186087.32 2531478.16 07-SEP-15:00 18.71 7.85 0.00 0.00 01-SEP-00:02
October 44595.02 1206972.75 18-OCT-14:00 19.59 6.70 0.00 0.00 01-OCT-00:10
November 2160.65 180549.92 03-NOV-14:00 14.55 7.16 0.00 0.00 01-NOV-00:10
December 0.01 75.24 04-DEC-04:46 15.33 6.73 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 123707.91         0.00    
Minimum of Months 0.00 0.00   6.70 6.70 0.00 0.00  
Maximum of Months 453509.67 2531478.16   22.52 7.91 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 178882.23 203101.59 13-JAN-16:30 22.16 18.33 0.00 0.00 01-JAN-00:05
February 339929.93 609079.57 27-FEB-16:00 29.72 22.72 0.00 0.00 01-FEB-00:10
March 496669.48 646691.25 31-MAR-24:00 30.42 18.33 0.00 0.00 01-MAR-00:10
April 703935.88 1327720.89 07-APR-14:00 42.86 30.29 0.00 0.00 01-APR-00:10
May 257135.32 975040.46 20-MAY-16:00 36.45 32.29 0.00 0.00 01-MAY-00:10
June 575841.98 1377905.50 29-JUN-15:00 43.76 36.33 0.00 0.00 01-JUN-00:10
July 970669.83 1956865.43 17-JUL-16:00 54.10 43.30 0.00 0.00 01-JUL-00:10
August 1125235.96 2072271.40 06-AUG-16:00 56.14 43.03 0.00 0.00 01-AUG-00:03
September 339770.54 1245137.13 02-SEP-17:00 41.36 36.88 0.00 0.00 01-SEP-00:02
October 387310.63 961169.91 18-OCT-15:00 36.20 28.97 0.00 0.00 01-OCT-00:10
November 506782.82 750693.74 17-NOV-17:00 32.34 22.55 0.00 0.00 01-NOV-00:10
December 640662.97 768649.98 10-DEC-02:00 32.67 20.54 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 545374.06         0.00    
Minimum of Months 178882.23 203101.59   22.16 18.33 0.00 0.00  
Maximum of Months 1125235.96 2072271.40   56.14 43.30 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.49 57.49 17320.88 58837.17 31-JAN-12:50
February 0.00 0.00 01-FEB-00:10 56.23 56.23 17697.89 59145.27 16-FEB-12:40
March 0.00 0.00 01-MAR-00:10 56.34 56.34 18534.81 59081.24 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 56.17 56.17 16871.72 57467.63 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 57.21 57.21 16514.02 54935.49 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 56.06 56.06 15920.98 51670.33 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.35 57.35 14087.26 48630.05 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 57.03 57.03 14974.26 46956.75 01-AUG-11:40
September 0.00 0.00 01-SEP-00:02 56.07 56.07 14302.61 48062.99 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.19 57.19 14888.17 50858.03 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 56.59 56.59 15938.81 54021.94 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 56.69 56.69 16263.11 56856.14 29-DEC-12:40
                 
Annual Sum or Average 0.00         16100.34    
Minimum of Months 0.00 0.00   56.06 56.06 14087.26 46956.75  
Maximum of Months 0.00 0.00   57.49 57.49 18534.81 59145.27  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9.65 13877.38 25-JAN-05:42 21.16 20.33 314.51 101747.55 17-JAN-06:30
February 2785.11 495057.03 27-FEB-15:30 23.24 21.10 521.01 104307.37 20-FEB-04:30
March 31.14 23677.28 01-MAR-07:00 21.20 20.37 713.37 120998.68 21-MAR-05:30
April 29179.71 932905.12 06-APR-16:00 25.14 21.10 1171.11 99930.25 14-APR-16:00
May 95345.93 2281590.76 19-MAY-14:40 26.04 21.10 963.97 121002.38 06-MAY-05:30
June 343872.09 2881577.65 20-JUN-15:20 27.33 23.34 640.58 86472.28 02-JUN-05:30
July 574789.11 3012469.21 17-JUL-16:00 27.62 22.74 328.18 55923.47 29-JUL-06:30
August 487455.53 2621173.96 07-AUG-15:30 26.77 21.87 941.10 63406.59 30-AUG-07:50
September 237331.38 4551358.72 07-SEP-15:00 30.94 25.40 560.53 96544.40 16-SEP-06:00
October 50561.47 1977586.91 18-OCT-12:20 25.38 21.10 1061.14 97708.60 31-OCT-10:00
November 2556.07 240598.81 17-NOV-17:00 22.14 21.10 919.02 113422.72 29-NOV-05:30
December 10.88 22090.58 20-DEC-07:00 21.20 20.37 280.48 113252.48 11-DEC-07:00
                 
Annual Sum or Average 153206.78         701.40    
Minimum of Months 9.65 13877.38   21.16 20.33 280.48 55923.47  
Maximum of Months 574789.11 4551358.72   30.94 25.40 1171.11 121002.38  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.724766E+11 0.00 0.00 0.469374E+10 0.00 0.00
February 0.369934E+11 0.00 0.668222E+09 0.527111E+10 0.00 0.00
March 0.192631E+11 0.00 47762575.90 0.785973E+10 0.00 0.00
April 0.423006E+10 0.00 0.684875E+10 0.966328E+10 0.00 0.00
May 0.308207E+10 0.00 0.187044E+11 0.890906E+10 0.00 0.00
June 0.113068E+09 0.00 0.621322E+11 0.135143E+11 0.00 0.00
July 0.00 0.00 0.106594E+12 0.163002E+11 0.00 0.00
August 0.00 0.00 0.982073E+11 0.177722E+11 0.00 0.00
September 0.900379E+09 0.00 0.400732E+11 0.981073E+10 0.00 0.00
October 0.345445E+10 0.00 0.108484E+11 0.877571E+10 0.00 0.00
November 0.130670E+11 0.00 0.603942E+09 0.736984E+10 0.00 0.00
December 0.379877E+11 0.00 0.00 0.633126E+10 0.00 0.00
             
Annual Sum or Average 0.191568E+12 0.00 0.344728E+12 0.116271E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.469374E+10 0.00 0.00
Maximum of Months 0.724766E+11 0.00 0.106594E+12 0.177722E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.106826E+13 0.00 12346.86 0.435905E+11 0.00 0.00
February 0.614001E+12 0.00 0.481262E+10 0.397318E+11 0.00 0.00
March 0.409468E+12 0.00 0.149095E+09 0.510296E+11 0.00 0.00
April 0.136382E+12 0.00 0.487552E+11 0.554782E+11 0.00 0.00
May 0.899782E+11 0.00 0.159328E+12 0.667292E+11 0.00 0.00
June 0.635612E+10 0.00 0.531036E+12 0.104582E+12 0.00 0.00
July 0.101762E+09 0.00 0.891038E+12 0.122355E+12 0.00 0.00
August 0.179044E+10 0.00 0.771346E+12 0.119194E+12 0.00 0.00
September 0.291548E+11 0.00 0.351058E+12 0.762832E+11 0.00 0.00
October 0.104008E+12 0.00 0.856662E+11 0.570605E+11 0.00 0.00
November 0.322534E+12 0.00 0.429216E+10 0.452959E+11 0.00 0.00
December 0.741386E+12 0.00 18227.04 0.432169E+11 0.00 0.00
             
Annual Sum or Average 0.352342E+13 0.00 0.284748E+13 0.824546E+12 0.00 0.00
Minimum of Months 0.101762E+09 0.00 12346.86 0.397318E+11 0.00 0.00
Maximum of Months 0.106826E+13 0.00 0.891038E+12 0.122355E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.155890E+12 0.00 2274.08 0.541981E+10 0.00 0.00
February 0.890210E+11 0.00 0.324425E+09 0.425912E+10 0.00 0.00
March 0.664277E+11 0.00 2489376.22 0.462097E+10 0.00 0.00
April 0.265050E+11 0.00 0.450198E+10 0.448921E+10 0.00 0.00
May 0.183328E+11 0.00 0.163879E+11 0.580186E+10 0.00 0.00
June 0.196293E+10 0.00 0.578964E+11 0.977286E+10 0.00 0.00
July 90853056.98 0.00 0.981358E+11 0.120759E+11 0.00 0.00
August 0.776267E+09 0.00 0.826728E+11 0.111030E+11 0.00 0.00
September 0.776179E+10 0.00 0.357250E+11 0.645737E+10 0.00 0.00
October 0.221069E+11 0.00 0.731607E+10 0.438305E+10 0.00 0.00
November 0.562236E+11 0.00 0.304082E+09 0.423959E+10 0.00 0.00
December 0.113676E+12 0.00 10175.89 0.498120E+10 0.00 0.00
             
Annual Sum or Average 0.558776E+12 0.00 0.303267E+12 0.776039E+11 0.00 0.00
Minimum of Months 90853056.98 0.00 2274.08 0.423959E+10 0.00 0.00
Maximum of Months 0.155890E+12 0.00 0.981358E+11 0.120759E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.319450E+09 0.00 0.00 0.174828E+11 0.00 0.00
February 0.00 0.00 0.282783E+09 0.155487E+11 0.00 0.00
March 0.00 0.00 13603.64 0.187145E+11 0.00 0.00
April 0.00 0.00 0.245389E+10 0.174026E+11 0.00 0.00
May 0.00 0.00 0.921493E+10 0.185322E+11 0.00 0.00
June 0.00 0.00 0.318869E+11 0.185411E+11 0.00 0.00
July 0.00 0.00 0.540153E+11 0.185708E+11 0.00 0.00
August 0.00 0.00 0.502708E+11 0.202277E+11 0.00 0.00
September 0.00 0.00 0.210305E+11 0.189750E+11 0.00 0.00
October 0.00 0.00 0.595290E+10 0.186655E+11 0.00 0.00
November 0.00 0.00 91667054.30 0.177535E+11 0.00 0.00
December 0.00 0.00 0.00 0.173201E+11 0.00 0.00
             
Annual Sum or Average 0.319450E+09 0.00 0.175200E+12 0.217734E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.155487E+11 0.00 0.00
Maximum of Months 0.319450E+09 0.00 0.540153E+11 0.202277E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.453802E+12 0.240996E+12 0.00 15.27
February 0.00 0.00 0.714318E+12 0.297545E+12 0.00 22.84
March 0.00 0.00 0.112062E+13 0.410549E+12 0.00 34.43
April 0.00 0.00 0.140684E+13 0.477524E+12 0.00 41.42
May 0.00 0.00 0.473998E+12 0.243288E+12 0.00 13.77
June 0.00 0.00 0.789851E+12 0.323435E+12 0.00 18.36
July 0.00 0.00 0.116257E+13 0.430565E+12 0.00 20.41
August 0.00 0.00 0.148818E+13 0.521186E+12 0.00 32.12
September 0.00 0.00 0.467587E+12 0.236764E+12 0.00 11.73
October 0.00 0.00 0.807954E+12 0.331172E+12 0.00 23.95
November 0.00 0.00 0.109525E+13 0.401771E+12 0.00 34.14
December 0.00 0.00 0.144569E+13 0.490799E+12 0.00 44.55
             
Annual Sum or Average 0.00 0.00 0.114267E+14 0.440559E+13 0.00 312.99
Minimum of Months 0.00 0.00 0.453802E+12 0.236764E+12 0.00 11.73
Maximum of Months 0.00 0.00 0.148818E+13 0.521186E+12 0.00 44.55



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.373285E+10 0.252734E+10 0.00 0.00
February 0.00 0.00 0.103569E+11 0.368723E+10 0.00 0.00
March 0.00 0.00 0.185876E+11 0.538311E+10 0.00 0.00
April 0.00 0.00 0.248159E+11 0.645803E+10 0.00 0.00
May 0.00 0.00 0.711949E+10 0.322079E+10 0.00 0.00
June 0.00 0.00 0.139018E+11 0.467058E+10 0.00 0.00
July 0.00 0.00 0.215584E+11 0.671289E+10 0.00 0.00
August 0.00 0.00 0.278541E+11 0.801969E+10 0.00 0.00
September 0.00 0.00 0.728569E+10 0.324679E+10 0.00 0.00
October 0.00 0.00 0.131697E+11 0.436350E+10 0.00 0.00
November 0.00 0.00 0.181677E+11 0.521950E+10 0.00 0.00
December 0.00 0.00 0.241734E+11 0.640866E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.190723E+12 0.599181E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.373285E+10 0.252734E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.278541E+11 0.801969E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.109070E+11 0.188087E+11 0.00 0.00
February 0.00 0.00 0.751216E+11 0.305675E+11 0.00 0.00
March 0.00 0.00 0.155718E+12 0.474676E+11 0.00 0.00
April 0.00 0.00 0.223446E+12 0.593957E+11 0.00 0.00
May 0.00 0.00 0.579095E+11 0.287702E+11 0.00 0.00
June 0.00 0.00 0.128223E+12 0.437701E+11 0.00 0.00
July 0.00 0.00 0.203814E+12 0.637430E+11 0.00 0.00
August 0.00 0.00 0.262127E+12 0.759034E+11 0.00 0.00
September 0.00 0.00 0.616915E+11 0.294530E+11 0.00 0.00
October 0.00 0.00 0.110420E+12 0.388355E+11 0.00 0.00
November 0.00 0.00 0.150904E+12 0.458014E+11 0.00 0.00
December 0.00 0.00 0.198064E+12 0.554573E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.163834E+13 0.537973E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.109070E+11 0.188087E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.262127E+12 0.759034E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.304459E+09 0.172454E+10 0.00 0.00
February 0.00 0.00 0.544278E+10 0.266294E+10 0.00 0.00
March 0.00 0.00 0.135543E+11 0.440038E+10 0.00 0.00
April 0.00 0.00 0.209416E+11 0.573058E+10 0.00 0.00
May 0.00 0.00 0.494384E+10 0.273251E+10 0.00 0.00
June 0.00 0.00 0.125772E+11 0.436672E+10 0.00 0.00
July 0.00 0.00 0.203465E+11 0.641281E+10 0.00 0.00
August 0.00 0.00 0.260821E+11 0.761392E+10 0.00 0.00
September 0.00 0.00 0.550424E+10 0.284379E+10 0.00 0.00
October 0.00 0.00 0.933294E+10 0.358859E+10 0.00 0.00
November 0.00 0.00 0.127768E+11 0.418149E+10 0.00 0.00
December 0.00 0.00 0.172964E+11 0.512272E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.149103E+12 0.513810E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.304459E+09 0.172454E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.260821E+11 0.761392E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.469374E+10 0.00 0.724766E+11 0.00 0.00 0.00 0.00 0.00
February 0.527111E+10 0.668222E+09 0.369934E+11 0.00 0.00 0.00 0.00 0.00
March 0.785973E+10 47762575.90 0.192631E+11 0.00 0.00 0.00 0.00 0.00
April 0.966328E+10 0.684875E+10 0.423006E+10 0.00 0.00 0.00 0.00 0.00
May 0.890906E+10 0.187044E+11 0.308207E+10 0.00 0.00 0.00 0.00 0.00
June 0.135143E+11 0.621322E+11 0.113068E+09 0.00 0.00 0.00 0.00 0.00
July 0.163002E+11 0.106594E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.177722E+11 0.982073E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.981073E+10 0.400732E+11 0.900379E+09 0.00 0.00 0.00 0.00 0.00
October 0.877571E+10 0.108484E+11 0.345445E+10 0.00 0.00 0.00 0.00 0.00
November 0.736984E+10 0.603942E+09 0.130670E+11 0.00 0.00 0.00 0.00 0.00
December 0.633126E+10 0.00 0.379877E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116271E+12 0.344728E+12 0.191568E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.469374E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177722E+11 0.106594E+12 0.724766E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.435905E+11 12346.86 0.106826E+13 0.00 0.00 0.00 0.00 0.00
February 0.397318E+11 0.481262E+10 0.614001E+12 0.00 0.00 0.00 0.00 0.00
March 0.510296E+11 0.149095E+09 0.409468E+12 0.00 0.00 0.00 0.00 0.00
April 0.554782E+11 0.487552E+11 0.136382E+12 0.00 0.00 0.00 0.00 0.00
May 0.667292E+11 0.159328E+12 0.899782E+11 0.00 0.00 0.00 0.00 0.00
June 0.104582E+12 0.531036E+12 0.635612E+10 0.00 0.00 0.00 0.00 0.00
July 0.122355E+12 0.891038E+12 0.101762E+09 0.00 0.00 0.00 0.00 0.00
August 0.119194E+12 0.771346E+12 0.179044E+10 0.00 0.00 0.00 0.00 0.00
September 0.762832E+11 0.351058E+12 0.291548E+11 0.00 0.00 0.00 0.00 0.00
October 0.570605E+11 0.856662E+11 0.104008E+12 0.00 0.00 0.00 0.00 0.00
November 0.452959E+11 0.429216E+10 0.322534E+12 0.00 0.00 0.00 0.00 0.00
December 0.432169E+11 18227.04 0.741386E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.824546E+12 0.284748E+13 0.352342E+13 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.397318E+11 12346.86 0.101762E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122355E+12 0.891038E+12 0.106826E+13 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.541981E+10 2274.08 0.155890E+12 0.00 0.00 0.00 0.00 0.00
February 0.425912E+10 0.324425E+09 0.890210E+11 0.00 0.00 0.00 0.00 0.00
March 0.462097E+10 2489376.22 0.664277E+11 0.00 0.00 0.00 0.00 0.00
April 0.448921E+10 0.450198E+10 0.265050E+11 0.00 0.00 0.00 0.00 0.00
May 0.580186E+10 0.163879E+11 0.183328E+11 0.00 0.00 0.00 0.00 0.00
June 0.977286E+10 0.578964E+11 0.196293E+10 0.00 0.00 0.00 0.00 0.00
July 0.120759E+11 0.981358E+11 90853056.98 0.00 0.00 0.00 0.00 0.00
August 0.111030E+11 0.826728E+11 0.776267E+09 0.00 0.00 0.00 0.00 0.00
September 0.645737E+10 0.357250E+11 0.776179E+10 0.00 0.00 0.00 0.00 0.00
October 0.438305E+10 0.731607E+10 0.221069E+11 0.00 0.00 0.00 0.00 0.00
November 0.423959E+10 0.304082E+09 0.562236E+11 0.00 0.00 0.00 0.00 0.00
December 0.498120E+10 10175.89 0.113676E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.776039E+11 0.303267E+12 0.558776E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.423959E+10 2274.08 90853056.98 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120759E+11 0.981358E+11 0.155890E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.174828E+11 0.00 0.319450E+09 0.00 0.00 0.00 0.00 0.00
February 0.155487E+11 0.282783E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.187145E+11 13603.64 0.00 0.00 0.00 0.00 0.00 0.00
April 0.174026E+11 0.245389E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.185322E+11 0.921493E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.185411E+11 0.318869E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.185708E+11 0.540153E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.202277E+11 0.502708E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189750E+11 0.210305E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.186655E+11 0.595290E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.177535E+11 91667054.30 0.00 0.00 0.00 0.00 0.00 0.00
December 0.173201E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.217734E+12 0.175200E+12 0.319450E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155487E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.202277E+11 0.540153E+11 0.319450E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.108058E+12 0.361909E+12 0.00 0.00 0.00 0.408609E+11 0.00 0.00
February 0.976007E+11 0.575784E+12 0.00 0.00 0.00 0.611342E+11 0.00 0.00
March 0.108058E+12 0.910685E+12 0.00 0.00 0.00 0.921393E+11 0.00 0.00
April 0.104572E+12 0.114524E+13 0.00 0.00 0.00 0.110851E+12 0.00 0.00
May 0.108058E+12 0.375786E+12 0.00 0.00 0.00 0.368520E+11 0.00 0.00
June 0.104572E+12 0.620356E+12 0.00 0.00 0.00 0.491468E+11 0.00 0.00
July 0.108058E+12 0.894926E+12 0.00 0.00 0.00 0.546166E+11 0.00 0.00
August 0.108058E+12 0.116139E+13 0.00 0.00 0.00 0.859527E+11 0.00 0.00
September 0.104572E+12 0.366932E+12 0.00 0.00 0.00 0.313960E+11 0.00 0.00
October 0.108058E+12 0.649209E+12 0.00 0.00 0.00 0.640807E+11 0.00 0.00
November 0.104572E+12 0.889825E+12 0.00 0.00 0.00 0.913596E+11 0.00 0.00
December 0.108058E+12 0.118270E+13 0.00 0.00 0.00 0.119218E+12 0.00 0.00
                 
Annual Sum or Average 0.127229E+13 0.913475E+13 0.00 0.00 0.00 0.837608E+12 0.00 0.00
Minimum of Months 0.976007E+11 0.361909E+12 0.00 0.00 0.00 0.313960E+11 0.00 0.00
Maximum of Months 0.108058E+12 0.118270E+13 0.00 0.00 0.00 0.119218E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.169392E+10 0.289943E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.152999E+10 0.819962E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.169392E+10 0.148985E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.163927E+10 0.199971E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.169392E+10 0.559262E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163927E+10 0.108705E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.169392E+10 0.165395E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.169392E+10 0.215283E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163927E+10 0.567817E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.169392E+10 0.105001E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163927E+10 0.145875E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.169392E+10 0.194587E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.199445E+11 0.150750E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.152999E+10 0.289943E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.169392E+10 0.215283E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.162084E+11 0.830672E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.146398E+11 0.591940E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.162084E+11 0.124458E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.156855E+11 0.179736E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.162084E+11 0.453476E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.156855E+11 0.100138E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.162084E+11 0.156279E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162084E+11 0.202432E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.156855E+11 0.479241E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.162084E+11 0.877932E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.156855E+11 0.120788E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.162084E+11 0.158815E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.190841E+12 0.129121E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.146398E+11 0.830672E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162084E+11 0.202432E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.165013E+10 0.230045E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.149044E+10 0.427029E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.165013E+10 0.108040E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.159690E+10 0.168079E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.165013E+10 0.386146E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.159690E+10 0.980741E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.165013E+10 0.155838E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.165013E+10 0.201183E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159690E+10 0.425735E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165013E+10 0.739448E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.159690E+10 0.101922E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.165013E+10 0.138238E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.194289E+11 0.117151E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.149044E+10 0.230045E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.165013E+10 0.201183E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.469374E+10 0.724766E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.527111E+10 0.369934E+11 0.668222E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.785973E+10 0.192631E+11 47762575.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.966328E+10 0.423006E+10 0.684875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.890906E+10 0.308207E+10 0.187044E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135143E+11 0.113068E+09 0.621322E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163002E+11 0.00 0.106594E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.177722E+11 0.00 0.982073E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.981073E+10 0.900379E+09 0.400732E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.877571E+10 0.345445E+10 0.108484E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.736984E+10 0.130670E+11 0.603942E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.633126E+10 0.379877E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.116271E+12 0.191568E+12 0.344728E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.469374E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177722E+11 0.724766E+11 0.106594E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.435905E+11 0.106826E+13 12346.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.397318E+11 0.614001E+12 0.481262E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.510296E+11 0.409468E+12 0.149095E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.554782E+11 0.136382E+12 0.487552E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.667292E+11 0.899782E+11 0.159328E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.104582E+12 0.635612E+10 0.531036E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.122355E+12 0.101762E+09 0.891038E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.119194E+12 0.179044E+10 0.771346E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.762832E+11 0.291548E+11 0.351058E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.570605E+11 0.104008E+12 0.856662E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.452959E+11 0.322534E+12 0.429216E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.432169E+11 0.741386E+12 18227.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.824546E+12 0.352342E+13 0.284748E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.397318E+11 0.101762E+09 12346.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122355E+12 0.106826E+13 0.891038E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.541981E+10 0.155890E+12 2274.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.425912E+10 0.890210E+11 0.324425E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.462097E+10 0.664277E+11 2489376.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.448921E+10 0.265050E+11 0.450198E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.580186E+10 0.183328E+11 0.163879E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.977286E+10 0.196293E+10 0.578964E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.120759E+11 90853056.98 0.981358E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.111030E+11 0.776267E+09 0.826728E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.645737E+10 0.776179E+10 0.357250E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.438305E+10 0.221069E+11 0.731607E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.423959E+10 0.562236E+11 0.304082E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.498120E+10 0.113676E+12 10175.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.776039E+11 0.558776E+12 0.303267E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.423959E+10 90853056.98 2274.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120759E+11 0.155890E+12 0.981358E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.174828E+11 0.319450E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155487E+11 0.00 0.282783E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.187145E+11 0.00 13603.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.174026E+11 0.00 0.245389E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.185322E+11 0.00 0.921493E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.185411E+11 0.00 0.318869E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.185708E+11 0.00 0.540153E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.202277E+11 0.00 0.502708E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189750E+11 0.00 0.210305E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.186655E+11 0.00 0.595290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.177535E+11 0.00 91667054.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.173201E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.217734E+12 0.319450E+09 0.175200E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155487E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.202277E+11 0.319450E+09 0.540153E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.108058E+12 0.00 0.453802E+12 0.00 0.918933E+11 0.00 0.00 0.00 0.410448E+11 0.00 0.00 0.00
February 0.976007E+11 0.00 0.714318E+12 0.00 0.138535E+12 0.00 0.00 0.00 0.614094E+11 0.00 0.00 0.00
March 0.108058E+12 0.00 0.112062E+13 0.00 0.209937E+12 0.00 0.00 0.00 0.925541E+11 0.00 0.00 0.00
April 0.104572E+12 0.00 0.140684E+13 0.00 0.261602E+12 0.00 0.00 0.00 0.111350E+12 0.00 0.00 0.00
May 0.108058E+12 0.00 0.473998E+12 0.00 0.982122E+11 0.00 0.00 0.00 0.370179E+11 0.00 0.00 0.00
June 0.104572E+12 0.00 0.789851E+12 0.00 0.169495E+12 0.00 0.00 0.00 0.493680E+11 0.00 0.00 0.00
July 0.108058E+12 0.00 0.116257E+13 0.00 0.267645E+12 0.00 0.00 0.00 0.548624E+11 0.00 0.00 0.00
August 0.108058E+12 0.00 0.148818E+13 0.00 0.326789E+12 0.00 0.00 0.00 0.863396E+11 0.00 0.00 0.00
September 0.104572E+12 0.00 0.467587E+12 0.00 0.100654E+12 0.00 0.00 0.00 0.315373E+11 0.00 0.00 0.00
October 0.108058E+12 0.00 0.807954E+12 0.00 0.158745E+12 0.00 0.00 0.00 0.643691E+11 0.00 0.00 0.00
November 0.104572E+12 0.00 0.109525E+13 0.00 0.205428E+12 0.00 0.00 0.00 0.917708E+11 0.00 0.00 0.00
December 0.108058E+12 0.00 0.144569E+13 0.00 0.262986E+12 0.00 0.00 0.00 0.119755E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.127229E+13 0.00 0.114267E+14 0.00 0.229192E+13 0.00 0.00 0.00 0.841378E+12 0.00 0.00 0.00
Minimum of Months 0.976007E+11 0.00 0.453802E+12 0.00 0.918933E+11 0.00 0.00 0.00 0.315373E+11 0.00 0.00 0.00
Maximum of Months 0.108058E+12 0.00 0.148818E+13 0.00 0.326789E+12 0.00 0.00 0.00 0.119755E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.169392E+10 0.00 0.373285E+10 0.00 0.833422E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.152999E+10 0.00 0.103569E+11 0.00 0.215724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.169392E+10 0.00 0.185876E+11 0.00 0.368919E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.163927E+10 0.00 0.248159E+11 0.00 0.481875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.169392E+10 0.00 0.711949E+10 0.00 0.152687E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163927E+10 0.00 0.139018E+11 0.00 0.303130E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.169392E+10 0.00 0.215584E+11 0.00 0.501897E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.169392E+10 0.00 0.278541E+11 0.00 0.632577E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.163927E+10 0.00 0.728569E+10 0.00 0.160752E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.169392E+10 0.00 0.131697E+11 0.00 0.266959E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163927E+10 0.00 0.181677E+11 0.00 0.358023E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.169392E+10 0.00 0.241734E+11 0.00 0.471474E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.199445E+11 0.00 0.190723E+12 0.00 0.399736E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.152999E+10 0.00 0.373285E+10 0.00 0.833422E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.169392E+10 0.00 0.278541E+11 0.00 0.632577E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.162084E+11 0.00 0.109070E+11 0.00 0.260027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.146398E+11 0.00 0.751216E+11 0.00 0.159276E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.162084E+11 0.00 0.155718E+12 0.00 0.312592E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.156855E+11 0.00 0.223446E+12 0.00 0.437101E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.162084E+11 0.00 0.579095E+11 0.00 0.125618E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.156855E+11 0.00 0.128223E+12 0.00 0.280845E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.162084E+11 0.00 0.203814E+12 0.00 0.475346E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162084E+11 0.00 0.262127E+12 0.00 0.596950E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.156855E+11 0.00 0.616915E+11 0.00 0.137675E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.162084E+11 0.00 0.110420E+12 0.00 0.226271E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.156855E+11 0.00 0.150904E+12 0.00 0.301158E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.162084E+11 0.00 0.198064E+12 0.00 0.392489E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.190841E+12 0.00 0.163834E+13 0.00 0.347133E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.146398E+11 0.00 0.109070E+11 0.00 0.260027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162084E+11 0.00 0.262127E+12 0.00 0.596950E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.165013E+10 0.00 0.304459E+09 0.00 74414483.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.149044E+10 0.00 0.544278E+10 0.00 0.117250E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.165013E+10 0.00 0.135543E+11 0.00 0.275025E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.159690E+10 0.00 0.209416E+11 0.00 0.413369E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.165013E+10 0.00 0.494384E+10 0.00 0.108238E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.159690E+10 0.00 0.125772E+11 0.00 0.276982E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.165013E+10 0.00 0.203465E+11 0.00 0.476269E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.165013E+10 0.00 0.260821E+11 0.00 0.596379E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159690E+10 0.00 0.550424E+10 0.00 0.124689E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165013E+10 0.00 0.933294E+10 0.00 0.193847E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.159690E+10 0.00 0.127768E+11 0.00 0.258459E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.165013E+10 0.00 0.172964E+11 0.00 0.347260E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.194289E+11 0.00 0.149103E+12 0.00 0.319521E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.149044E+10 0.00 0.304459E+09 0.00 74414483.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.165013E+10 0.00 0.260821E+11 0.00 0.596379E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.249746E+11 0.00 0.00 62017720.89 0.00 0.00 0.460334E+11 0.00 0.43
February 0.845178E+10 0.00 0.00 76470015.44 0.00 0.00 0.549091E+11 0.00 0.55
March 0.271370E+10 0.00 0.00 0.113026E+09 0.00 0.00 0.755399E+11 0.00 0.69
April 0.339076E+09 0.00 0.00 0.108718E+09 0.00 0.00 0.714405E+11 0.00 0.95
May 0.159295E+09 41999800.24 0.00 0.113538E+09 6376103.83 0.00 0.692177E+11 0.00 1.15
June 0.106587E+09 0.376684E+09 0.00 0.108100E+09 354436.60 0.00 0.512737E+11 0.00 1.34
July 0.124298E+09 0.132368E+10 0.00 0.105376E+09 30573486.60 0.00 0.319779E+11 0.00 1.13
August 0.111198E+09 0.930228E+09 0.00 0.122940E+09 49603332.19 0.00 0.447037E+11 0.00 1.36
September 0.249879E+09 0.375528E+09 0.00 0.119885E+09 37349549.71 0.00 0.620434E+11 0.00 1.34
October 0.420469E+09 0.00 0.00 0.130493E+09 0.00 0.00 0.779676E+11 0.00 1.12
November 0.395849E+09 0.00 0.00 0.125859E+09 0.00 0.00 0.783608E+11 0.00 0.83
December 0.579433E+10 0.00 0.00 0.107327E+09 0.00 0.00 0.699801E+11 0.00 0.55
                   
Annual Sum or Average 0.438411E+11 0.304812E+10 0.00 0.129375E+10 0.124257E+09 0.00 0.733448E+12 0.00 0.96
Minimum of Months 0.106587E+09 0.00 0.00 62017720.89 0.00 0.00 0.319779E+11 0.00 0.43
Maximum of Months 0.249746E+11 0.132368E+10 0.00 0.130493E+09 49603332.19 0.00 0.783608E+11 0.00 1.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254387E+11 0.00 0.00 37590533.64 0.00 0.00 0.434579E+11 0.00 0.40
February 0.967281E+10 0.00 0.00 57333126.70 0.00 0.00 0.483354E+11 0.00 0.48
March 0.355624E+10 0.00 0.00 93188894.49 0.00 0.00 0.644311E+11 0.00 0.58
April 0.403519E+10 0.00 0.00 96272826.17 0.00 0.00 0.593320E+11 0.00 0.80
May 0.242762E+10 26495848.49 0.00 89267813.44 14532957.14 0.00 0.506574E+11 0.00 0.81
June 0.466387E+10 0.461765E+09 0.00 89736536.97 11827359.90 0.00 0.388784E+11 0.00 1.07
July 0.719025E+10 0.138261E+10 0.00 77822023.58 72629495.85 0.00 0.218791E+11 0.00 1.00
August 0.932397E+10 0.964595E+09 0.00 94930644.37 73971252.17 0.00 0.334942E+11 0.00 1.21
September 0.303906E+10 0.505297E+09 0.00 86943878.95 54249455.57 0.00 0.418854E+11 0.00 0.91
October 0.279794E+10 0.00 0.00 95354457.73 0.00 0.00 0.553168E+11 0.00 0.80
November 0.213484E+10 0.00 0.00 87885571.50 0.00 0.00 0.594264E+11 0.00 0.62
December 0.451350E+10 0.00 0.00 77885656.27 0.00 0.00 0.641899E+11 0.00 0.48
                   
Annual Sum or Average 0.787940E+11 0.334077E+10 0.00 0.984212E+09 0.227211E+09 0.00 0.581284E+12 0.00 0.77
Minimum of Months 0.213484E+10 0.00 0.00 37590533.64 0.00 0.00 0.218791E+11 0.00 0.40
Maximum of Months 0.254387E+11 0.138261E+10 0.00 96272826.17 73971252.17 0.00 0.644311E+11 0.00 1.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.486649E+12 0.00 0.00 58177873.88 0.00 0.743414E+10 0.130558E+12 0.00 0.37
February 0.314742E+12 0.00 0.00 0.146525E+09 0.00 0.128664E+10 0.170534E+12 0.00 0.40
March 0.210177E+12 0.00 0.00 0.342626E+09 0.00 0.131220E+10 0.316677E+12 0.00 0.45
April 0.806886E+11 0.00 0.00 0.483167E+09 0.00 0.00 0.357636E+12 0.00 0.56
May 0.463766E+11 0.292583E+09 0.00 0.580972E+09 0.157953E+09 0.00 0.373104E+12 0.00 0.66
June 0.249676E+11 0.510864E+10 0.00 0.695254E+09 0.146662E+09 0.00 0.306612E+12 0.00 0.85
July 0.267083E+11 0.145533E+11 0.00 0.620732E+09 0.513499E+09 0.00 0.166428E+12 0.00 0.74
August 0.241394E+11 0.101037E+11 0.00 0.722265E+09 0.714597E+09 0.00 0.250046E+12 0.00 0.84
September 0.251605E+11 0.492433E+10 0.00 0.628880E+09 0.573261E+09 0.00 0.322335E+12 0.00 0.72
October 0.567900E+11 0.00 0.00 0.529097E+09 0.00 0.00 0.359500E+12 0.00 0.58
November 0.184030E+12 0.00 0.00 0.307909E+09 0.00 51038884.84 0.257699E+12 0.00 0.45
December 0.369410E+12 0.00 0.00 0.144244E+09 0.00 0.210153E+10 0.177734E+12 0.00 0.39
                   
Annual Sum or Average 0.184984E+13 0.349826E+11 0.00 0.525985E+10 0.210597E+10 0.121856E+11 0.318886E+13 0.00 0.59
Minimum of Months 0.241394E+11 0.00 0.00 58177873.88 0.00 0.00 0.130558E+12 0.00 0.37
Maximum of Months 0.486649E+12 0.145533E+11 0.00 0.722265E+09 0.714597E+09 0.743414E+10 0.373104E+12 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.413310E+11 0.00 0.00 81160.80 0.00 0.134341E+11 0.166007E+09 0.00 0.36
February 0.359231E+11 0.00 0.00 1907190.93 0.00 0.416761E+10 0.287425E+10 0.00 0.38
March 0.306186E+11 0.00 0.00 9212894.96 0.00 0.292581E+10 0.111395E+11 0.00 0.41
April 0.166599E+11 0.00 0.00 23789887.64 0.00 36921490.94 0.201276E+11 0.00 0.49
May 0.112939E+11 18434716.18 0.00 39352187.43 11888898.10 0.317084E+09 0.259711E+11 0.00 0.61
June 0.384748E+10 0.366783E+09 0.00 62567519.01 13205794.38 0.00 0.268267E+11 0.00 0.85
July 0.251936E+10 0.128128E+10 0.00 60431518.19 43845819.21 0.00 0.151905E+11 0.00 0.76
August 0.266444E+10 0.831145E+09 0.00 64358962.22 60267806.08 0.00 0.212897E+11 0.00 0.82
September 0.718483E+10 0.438074E+09 0.00 43513877.54 47400086.10 0.00 0.216535E+11 0.00 0.66
October 0.165856E+11 0.00 0.00 21842867.53 475538.05 0.227114E+09 0.157523E+11 0.00 0.48
November 0.266998E+11 0.00 0.00 6682729.39 0.00 0.216559E+10 0.672103E+10 0.00 0.39
December 0.382078E+11 0.00 0.00 1485359.94 0.00 0.682110E+10 0.213075E+10 0.00 0.36
                   
Annual Sum or Average 0.233536E+12 0.293572E+10 0.00 0.335226E+09 0.177084E+09 0.300953E+11 0.169843E+12 0.00 0.55
Minimum of Months 0.251936E+10 0.00 0.00 81160.80 0.00 0.00 0.166007E+09 0.00 0.36
Maximum of Months 0.413310E+11 0.128128E+10 0.00 64358962.22 60267806.08 0.134341E+11 0.268267E+11 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.427441E+10 0.00 0.00 29.88 0.00 0.498839E+10 4609210.47 0.00 0.42
February 0.484373E+10 0.00 0.00 370642.44 0.00 0.164407E+10 0.392775E+09 0.00 0.44
March 0.482356E+10 0.00 0.00 1977355.29 0.00 0.286930E+09 0.193174E+10 0.00 0.47
April 0.290648E+10 0.00 0.00 4997068.89 0.00 0.00 0.380747E+10 0.00 0.71
May 0.203410E+10 7271913.04 0.00 6798765.21 2319219.38 0.00 0.419051E+10 0.00 0.83
June 0.109691E+10 91022906.90 0.00 11195776.04 1887450.85 0.00 0.490920E+10 0.00 1.30
July 0.131135E+10 0.293993E+09 0.00 10842053.62 11599399.59 0.00 0.289115E+10 0.00 1.26
August 0.181244E+10 0.195634E+09 0.00 10983096.31 11804587.30 0.00 0.380872E+10 0.00 1.39
September 0.182240E+10 90922892.84 0.00 6395912.44 8657315.04 0.00 0.326195E+10 0.00 0.89
October 0.309151E+10 0.00 0.00 3963154.27 0.00 0.00 0.280912E+10 0.00 0.67
November 0.453533E+10 0.00 0.00 1355910.55 0.00 81350658.88 0.135821E+10 0.00 0.47
December 0.565975E+10 0.00 0.00 220663.20 0.00 0.118761E+10 0.366072E+09 0.00 0.38
                   
Annual Sum or Average 0.382120E+11 0.678845E+09 0.00 59100428.12 36267972.15 0.818835E+10 0.297315E+11 0.00 0.77
Minimum of Months 0.109691E+10 0.00 0.00 29.88 0.00 0.00 4609210.47 0.00 0.38
Maximum of Months 0.565975E+10 0.293993E+09 0.00 11195776.04 11804587.30 0.498839E+10 0.490920E+10 0.00 1.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.580859E+10 0.00 0.00 10406.40 0.00 0.561194E+10 22941546.93 0.00 0.80
February 0.575586E+10 0.00 0.00 893720.78 0.00 0.206404E+10 0.772957E+09 0.00 0.85
March 0.617331E+10 0.00 0.00 2500417.79 0.00 0.550777E+09 0.213468E+10 0.00 0.90
April 0.437322E+10 0.00 0.00 5048806.98 0.00 4122883.72 0.374840E+10 0.00 1.27
May 0.287598E+10 4999154.39 0.00 7321796.61 2880301.09 431896.30 0.472819E+10 0.00 1.47
June 0.184172E+10 70382252.26 0.00 11602701.17 2344076.11 0.00 0.486606E+10 0.00 2.15
July 0.182839E+10 0.216937E+09 0.00 12586295.53 14405607.19 0.00 0.327298E+10 0.00 2.19
August 0.281966E+10 0.152306E+09 0.00 9823478.74 14226181.18 0.00 0.376557E+10 0.00 2.33
September 0.274681E+10 73840515.83 0.00 6184093.63 10680047.97 0.00 0.333826E+10 0.00 1.56
October 0.411613E+10 0.00 0.00 3754326.83 0.00 1384836.57 0.285043E+10 0.00 1.17
November 0.587376E+10 0.00 0.00 768050.65 0.00 0.311646E+09 0.110857E+10 0.00 0.88
December 0.667117E+10 0.00 0.00 23250.58 0.00 0.220275E+10 83340448.26 0.00 0.74
                   
Annual Sum or Average 0.508846E+11 0.518465E+09 0.00 60517345.67 44536213.54 0.107471E+11 0.306924E+11 0.00 1.36
Minimum of Months 0.182839E+10 0.00 0.00 10406.40 0.00 0.00 22941546.93 0.00 0.74
Maximum of Months 0.667117E+10 0.216937E+09 0.00 12586295.53 14405607.19 0.561194E+10 0.486606E+10 0.00 2.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.659413E+10 0.00 0.00 2447698.52 0.00 0.595936E+10 0.273319E+10 0.00 0.70
February 0.606380E+10 0.00 0.00 7260141.16 0.00 0.183609E+10 0.498036E+10 0.00 0.90
March 0.662709E+10 0.00 0.00 8910119.95 0.00 0.541491E+09 0.684879E+10 0.00 0.99
April 0.497664E+10 0.00 0.00 9202971.88 0.00 11769117.81 0.655376E+10 0.00 1.26
May 0.396769E+10 10099449.60 0.00 9343002.97 3643276.32 71459094.10 0.572499E+10 0.00 1.30
June 0.264224E+10 0.122242E+09 0.00 11897655.99 2965008.42 0.00 0.512234E+10 0.00 1.68
July 0.247520E+10 0.405408E+09 0.00 12549552.82 18221569.88 0.00 0.312634E+10 0.00 1.69
August 0.333056E+10 0.334050E+09 0.00 15560835.50 18543900.54 0.00 0.488601E+10 0.00 2.12
September 0.293041E+10 0.225982E+09 0.00 13540124.97 6005895.93 0.00 0.620462E+10 0.00 1.71
October 0.389394E+10 0.00 0.00 14855188.69 0.00 25492483.26 0.818668E+10 0.00 1.45
November 0.542253E+10 0.00 0.00 8060594.82 0.00 0.460948E+09 0.602765E+10 0.00 0.97
December 0.697306E+10 0.00 0.00 4177503.62 0.00 0.222939E+10 0.345612E+10 0.00 0.70
                   
Annual Sum or Average 0.558973E+11 0.109778E+10 0.00 0.117805E+09 49379651.09 0.111360E+11 0.638509E+11 0.00 1.29
Minimum of Months 0.247520E+10 0.00 0.00 2447698.52 0.00 0.00 0.273319E+10 0.00 0.70
Maximum of Months 0.697306E+10 0.405408E+09 0.00 15560835.50 18543900.54 0.595936E+10 0.818668E+10 0.00 2.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.913639E+10 0.00 0.00 157079.36 0.00 0.487549E+10 0.243094E+09 0.00 1.00
February 0.852137E+10 0.00 0.00 1862706.29 0.00 0.330047E+09 0.201808E+10 0.00 1.09
March 0.571575E+10 0.00 0.00 5798255.40 0.00 42302912.69 0.578889E+10 0.00 1.22
April 0.210980E+10 0.00 0.00 12853118.89 0.00 0.00 0.893042E+10 0.00 1.85
May 0.292896E+10 8110637.71 0.00 10195124.42 3589152.50 0.00 0.618730E+10 0.00 1.84
June 0.152490E+10 0.129558E+09 0.00 14632557.94 972230.94 0.00 0.606706E+10 0.00 2.55
July 0.171048E+10 0.440057E+09 0.00 17365970.34 9590657.66 0.00 0.382657E+10 0.00 2.57
August 0.211154E+10 0.319119E+09 0.00 19369031.59 4730159.78 0.00 0.598355E+10 0.00 3.11
September 0.278876E+10 0.146972E+09 0.00 7641951.05 2135997.08 0.00 0.432560E+10 0.00 1.91
October 0.364432E+10 0.00 0.00 6803051.33 0.00 0.00 0.533494E+10 0.00 1.56
November 0.536494E+10 0.00 0.00 4102800.25 0.00 1570726.85 0.422988E+10 0.00 1.18
December 0.867669E+10 0.00 0.00 2212317.36 0.00 13549441.90 0.267367E+10 0.00 0.94
                   
Annual Sum or Average 0.542339E+11 0.104382E+10 0.00 0.102994E+09 21018197.96 0.526296E+10 0.556091E+11 0.00 1.74
Minimum of Months 0.152490E+10 0.00 0.00 157079.36 0.00 0.00 0.243094E+09 0.00 0.94
Maximum of Months 0.913639E+10 0.440057E+09 0.00 19369031.59 9590657.66 0.487549E+10 0.893042E+10 0.00 3.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121385E+11 0.00 0.00 0.00 0.00 0.962790E+11 0.00 0.00 0.50
February 0.221376E+11 0.00 0.00 0.00 0.00 0.538038E+11 0.00 0.00 0.49
March 0.482707E+11 0.00 0.00 93509.84 0.00 0.237730E+11 0.276244E+09 0.00 0.48
April 0.390214E+11 0.00 0.00 10974933.55 0.00 0.381931E+10 0.915146E+10 0.00 0.53
May 0.291156E+11 80883403.26 0.00 35387013.05 26338574.07 0.252898E+10 0.199062E+11 0.00 0.68
June 0.112466E+11 0.107392E+10 0.00 80312850.14 23438154.07 0.00 0.332084E+11 0.00 1.02
July 0.646914E+10 0.341663E+10 0.00 81206977.99 83192405.40 0.00 0.204489E+11 0.00 0.96
August 0.110990E+11 0.227416E+10 0.00 69693139.41 0.114200E+09 0.00 0.227970E+11 0.00 0.95
September 0.246161E+11 0.879882E+09 0.00 35491098.15 91613033.71 0.621244E+09 0.151338E+11 0.00 0.71
October 0.397210E+11 0.00 0.00 8354732.25 0.00 0.347433E+10 0.581550E+10 0.00 0.53
November 0.349467E+11 0.00 0.00 0.00 0.00 0.257439E+11 0.00 0.00 0.47
December 0.200590E+11 0.00 0.00 0.00 0.00 0.655639E+11 0.00 0.00 0.47
                   
Annual Sum or Average 0.298841E+12 0.772547E+10 0.00 0.321514E+09 0.338782E+09 0.275608E+12 0.126737E+12 0.00 0.65
Minimum of Months 0.646914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.482707E+11 0.341663E+10 0.00 81206977.99 0.114200E+09 0.962790E+11 0.332084E+11 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.268842E+11 0.00 0.00 0.00 0.00 0.110934E+12 0.00 0.00 1.01
February 0.400059E+11 0.00 0.00 1353427.15 0.00 0.620231E+11 0.116884E+10 0.00 1.04
March 0.626905E+11 0.00 0.00 9084652.47 0.00 0.280063E+11 0.101103E+11 0.00 1.05
April 0.475791E+11 0.00 0.00 32779030.85 0.00 0.367407E+10 0.262303E+11 0.00 1.21
May 0.350599E+11 64399230.56 0.00 54748209.59 35044719.18 0.361400E+10 0.358777E+11 0.00 1.45
June 0.169453E+11 0.936246E+09 0.00 0.107082E+09 31775042.11 0.00 0.431486E+11 0.00 2.03
July 0.100896E+11 0.288992E+10 0.00 0.127548E+09 0.115497E+09 0.00 0.308996E+11 0.00 2.00
August 0.173243E+11 0.218072E+10 0.00 92260096.76 0.157750E+09 0.00 0.335021E+11 0.00 2.00
September 0.333828E+11 0.851951E+09 0.00 46214256.27 0.127068E+09 0.609339E+09 0.227108E+11 0.00 1.47
October 0.529259E+11 0.00 0.00 14097954.03 0.00 0.315045E+10 0.123077E+11 0.00 1.15
November 0.510465E+11 0.00 0.00 711135.30 0.00 0.313342E+11 0.113212E+10 0.00 1.01
December 0.345256E+11 0.00 0.00 0.00 0.00 0.814499E+11 0.00 0.00 1.00
                   
Annual Sum or Average 0.428460E+12 0.692323E+10 0.00 0.485879E+09 0.467135E+09 0.324796E+12 0.217088E+12 0.00 1.37
Minimum of Months 0.100896E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.00
Maximum of Months 0.626905E+11 0.288992E+10 0.00 0.127548E+09 0.157750E+09 0.110934E+12 0.431486E+11 0.00 2.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.529320E+11 0.00 0.00 15889586.42 0.00 0.971806E+11 0.234333E+11 0.00 0.83
February 0.568692E+11 0.00 0.00 62541380.79 0.00 0.429294E+11 0.438489E+11 0.00 1.02
March 0.691597E+11 0.00 0.00 72893015.65 0.00 0.237476E+11 0.557152E+11 0.00 1.06
April 0.530549E+11 0.00 0.00 70097723.37 0.00 0.471350E+10 0.474632E+11 0.00 1.15
May 0.444996E+11 0.129625E+09 0.00 77920585.52 42385325.82 0.438569E+10 0.447046E+11 0.00 1.25
June 0.264848E+11 0.154710E+10 0.00 95505052.63 33849796.43 0.00 0.390903E+11 0.00 1.49
July 0.160044E+11 0.508898E+10 0.00 0.104415E+09 0.139690E+09 0.00 0.244402E+11 0.00 1.42
August 0.213983E+11 0.448618E+10 0.00 0.130354E+09 0.191756E+09 0.00 0.378318E+11 0.00 1.74
September 0.319710E+11 0.266441E+10 0.00 0.125146E+09 68929734.69 0.608596E+09 0.519959E+11 0.00 1.64
October 0.430689E+11 0.00 0.00 0.134611E+09 0.00 0.239551E+10 0.690989E+11 0.00 1.40
November 0.547697E+11 0.00 0.00 62058652.08 0.00 0.210437E+11 0.469862E+11 0.00 0.99
December 0.631185E+11 0.00 0.00 23128532.91 0.00 0.605657E+11 0.243545E+11 0.00 0.83
                   
Annual Sum or Average 0.533331E+12 0.139163E+11 0.00 0.974560E+09 0.476610E+09 0.257570E+12 0.508963E+12 0.00 1.23
Minimum of Months 0.160044E+11 0.00 0.00 15889586.42 0.00 0.00 0.234333E+11 0.00 0.83
Maximum of Months 0.691597E+11 0.508898E+10 0.00 0.134611E+09 0.191756E+09 0.971806E+11 0.690989E+11 0.00 1.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.326693E+11 0.00 0.00 0.00 0.00 0.115022E+12 0.00 0.00 1.08
February 0.517303E+11 0.00 0.00 3623358.47 0.00 0.560878E+11 0.328325E+10 0.00 1.12
March 0.732207E+11 0.00 0.00 10747809.00 0.00 0.257908E+11 0.987782E+10 0.00 1.14
April 0.585134E+11 0.00 0.00 28420206.26 0.00 0.310622E+10 0.199618E+11 0.00 1.32
May 0.430870E+11 77572278.56 0.00 59786183.50 39252820.27 0.311715E+10 0.320064E+11 0.00 1.57
June 0.230211E+11 0.143597E+10 0.00 75294481.78 19117113.04 8096346.06 0.317822E+11 0.00 1.91
July 0.137796E+11 0.469718E+10 0.00 82890996.67 47204790.48 0.00 0.190723E+11 0.00 1.76
August 0.200597E+11 0.308738E+10 0.00 70290995.57 89976259.21 6035692.34 0.236788E+11 0.00 1.84
September 0.394198E+11 0.140207E+10 0.00 38360243.06 35774177.22 0.620749E+09 0.182212E+11 0.00 1.56
October 0.589729E+11 0.00 0.00 17098832.43 0.00 0.314586E+10 0.120469E+11 0.00 1.26
November 0.609097E+11 0.00 0.00 3744137.08 0.00 0.239697E+11 0.486706E+10 0.00 1.09
December 0.480244E+11 0.00 0.00 111741.67 0.00 0.760968E+11 0.317016E+09 0.00 1.07
                   
Annual Sum or Average 0.523408E+12 0.107002E+11 0.00 0.390369E+09 0.231325E+09 0.306971E+12 0.175115E+12 0.00 1.39
Minimum of Months 0.137796E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.07
Maximum of Months 0.732207E+11 0.469718E+10 0.00 82890996.67 89976259.21 0.115022E+12 0.320064E+11 0.00 1.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.343501E+09 0.00 0.00 0.00 0.00 0.130869E+11 0.00 0.00 0.67
February 0.149769E+10 0.00 0.00 0.00 0.00 0.789017E+10 0.00 0.00 0.65
March 0.383743E+10 0.00 0.00 0.00 0.00 0.539185E+10 0.00 0.00 0.66
April 0.452496E+10 0.00 0.00 385642.19 0.00 0.181681E+10 0.363880E+09 0.00 0.68
May 0.377411E+10 5029020.00 0.00 2342358.28 2487969.10 0.114045E+10 0.139898E+10 0.00 0.80
June 0.176707E+10 73073458.80 0.00 7190662.01 2763553.70 40419577.67 0.287648E+10 0.00 1.11
July 0.105319E+10 0.280936E+09 0.00 7678261.75 9329720.95 0.00 0.174930E+10 0.00 1.03
August 0.166370E+10 0.176646E+09 0.00 5973188.68 12612139.33 29371949.41 0.186216E+10 0.00 1.01
September 0.311326E+10 75749599.41 0.00 2485235.37 11160006.98 0.514924E+09 0.101341E+10 0.00 0.82
October 0.404714E+10 0.00 0.00 158685.81 99515.02 0.190025E+10 0.140929E+09 0.00 0.69
November 0.230733E+10 0.00 0.00 0.00 0.00 0.509912E+10 0.00 0.00 0.63
December 0.964096E+09 0.00 0.00 0.00 0.00 0.952120E+10 0.00 0.00 0.63
                   
Annual Sum or Average 0.288935E+11 0.611434E+09 0.00 26214034.08 38452905.09 0.464314E+11 0.940514E+10 0.00 0.78
Minimum of Months 0.343501E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.63
Maximum of Months 0.452496E+10 0.280936E+09 0.00 7678261.75 12612139.33 0.130869E+11 0.287648E+10 0.00 1.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106031E+10 0.00 0.00 0.00 0.00 0.116782E+11 0.00 0.00 1.02
February 0.296777E+10 0.00 0.00 1152.20 0.00 0.687594E+10 15660889.71 0.00 1.07
March 0.529786E+10 0.00 0.00 380870.22 0.00 0.420102E+10 0.500086E+09 0.00 1.11
April 0.435642E+10 0.00 0.00 2503577.96 0.00 0.135941E+10 0.207067E+10 0.00 1.24
May 0.329255E+10 3815396.42 0.00 4774126.18 2732611.03 0.877710E+09 0.328108E+10 0.00 1.46
June 0.164404E+10 62825775.22 0.00 10688358.93 3035293.86 30079249.46 0.413030E+10 0.00 2.07
July 0.864347E+09 0.235318E+09 0.00 13023763.39 10247112.13 0.00 0.309081E+10 0.00 2.07
August 0.151769E+10 0.171331E+09 0.00 9345356.94 13669854.50 13565718.08 0.322958E+10 0.00 2.00
September 0.299101E+10 76289992.33 0.00 4110245.83 10797604.10 0.374424E+09 0.199877E+10 0.00 1.46
October 0.468963E+10 0.00 0.00 727102.49 109300.33 0.136793E+10 0.627617E+09 0.00 1.18
November 0.359076E+10 0.00 0.00 0.00 0.00 0.440450E+10 0.00 0.00 1.06
December 0.172130E+10 0.00 0.00 0.00 0.00 0.912625E+10 0.00 0.00 1.02
                   
Annual Sum or Average 0.339937E+11 0.549581E+09 0.00 45554554.13 40591775.95 0.403091E+11 0.189446E+11 0.00 1.40
Minimum of Months 0.864347E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.02
Maximum of Months 0.529786E+10 0.235318E+09 0.00 13023763.39 13669854.50 0.116782E+11 0.413030E+10 0.00 2.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.406423E+10 0.00 0.00 652142.82 0.00 0.117249E+11 0.111337E+10 0.00 0.87
February 0.467755E+10 0.00 0.00 3724128.52 0.00 0.629027E+10 0.303293E+10 0.00 1.04
March 0.616947E+10 0.00 0.00 5405258.98 0.00 0.438197E+10 0.455652E+10 0.00 1.11
April 0.522017E+10 0.00 0.00 5321254.76 0.00 0.188772E+10 0.398149E+10 0.00 1.19
May 0.437445E+10 7435691.72 0.00 6769467.88 3557150.48 0.143954E+10 0.413163E+10 0.00 1.31
June 0.288863E+10 0.100494E+09 0.00 9697431.00 3951164.98 61471951.67 0.378894E+10 0.00 1.57
July 0.170017E+10 0.399080E+09 0.00 11075997.65 13339080.98 0.00 0.245754E+10 0.00 1.52
August 0.218038E+10 0.339871E+09 0.00 13153242.84 13489669.18 41441033.38 0.376148E+10 0.00 1.81
September 0.324216E+10 0.226296E+09 0.00 11139893.65 5751733.94 0.497465E+09 0.476203E+10 0.00 1.67
October 0.465603E+10 159548.23 0.00 9737689.45 0.00 0.111185E+10 0.529500E+10 0.00 1.39
November 0.463232E+10 0.00 0.00 3707336.01 0.00 0.392262E+10 0.321523E+10 0.00 1.02
December 0.452772E+10 0.00 0.00 1228921.99 0.00 0.847827E+10 0.146303E+10 0.00 0.88
                   
Annual Sum or Average 0.483333E+11 0.107334E+10 0.00 81612765.56 40088799.55 0.398375E+11 0.415592E+11 0.00 1.28
Minimum of Months 0.170017E+10 0.00 0.00 652142.82 0.00 0.00 0.111337E+10 0.00 0.87
Maximum of Months 0.616947E+10 0.399080E+09 0.00 13153242.84 13489669.18 0.117249E+11 0.529500E+10 0.00 1.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.142793E+10 0.00 0.00 0.00 0.00 0.129766E+11 0.00 0.00 1.16
February 0.356408E+10 0.00 0.00 221352.51 0.00 0.743077E+10 0.241363E+09 0.00 1.22
March 0.615823E+10 0.00 0.00 791622.06 0.00 0.453313E+10 0.805990E+09 0.00 1.28
April 0.585973E+10 0.00 0.00 2287625.37 0.00 0.135384E+10 0.163318E+10 0.00 1.43
May 0.453909E+10 4734339.14 0.00 5359278.51 3115045.31 0.905581E+09 0.295529E+10 0.00 1.68
June 0.262891E+10 98465511.97 0.00 8324131.52 1024171.20 40227354.44 0.296927E+10 0.00 2.05
July 0.151930E+10 0.372567E+09 0.00 9124437.30 4246721.45 0.00 0.180877E+10 0.00 1.86
August 0.214832E+10 0.237204E+09 0.00 6858620.08 7895738.85 36526324.53 0.215477E+10 0.00 1.91
September 0.396484E+10 0.120321E+09 0.00 3441369.25 4566832.39 0.420776E+09 0.157313E+10 0.00 1.64
October 0.542362E+10 0.00 0.00 1239342.32 124597.13 0.135864E+10 0.929600E+09 0.00 1.38
November 0.439318E+10 0.00 0.00 127391.62 0.00 0.448468E+10 0.224014E+09 0.00 1.21
December 0.267619E+10 0.00 0.00 421.38 0.00 0.964218E+10 10132693.15 0.00 1.16
                   
Annual Sum or Average 0.443034E+11 0.833292E+09 0.00 37775591.92 20973106.33 0.431830E+11 0.153055E+11 0.00 1.50
Minimum of Months 0.142793E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.16
Maximum of Months 0.615823E+10 0.372567E+09 0.00 9124437.30 7895738.85 0.129766E+11 0.296927E+10 0.00 2.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 16595666.86 0.00 0.00 2218040.25 0.00 0.00 0.833107E+09 0.00 0.28
February 0.00 0.00 0.00 7049352.96 0.00 0.00 0.645519E+09 0.00 0.28
March 0.00 0.00 0.00 13705713.73 0.00 0.00 0.660970E+09 0.00 0.31
April 0.00 0.00 0.00 17215289.28 0.00 0.00 0.462854E+09 0.00 0.29
May 0.00 143399.66 0.00 3900858.10 0.00 0.00 0.407828E+09 0.00 0.29
June 0.00 13403669.55 0.00 7431706.91 0.00 0.00 0.201194E+09 0.00 0.30
July 0.00 21322335.00 0.00 9021917.80 0.00 0.00 81813280.51 0.00 0.28
August 0.00 5612491.84 0.00 16503821.57 0.00 0.00 0.152172E+09 0.00 0.31
September 0.00 11368597.48 0.00 3451254.10 0.00 0.00 0.257568E+09 0.00 0.29
October 0.00 0.00 0.00 8277901.24 0.00 0.00 0.439690E+09 0.00 0.28
November 0.00 0.00 0.00 12063774.15 0.00 0.00 0.543950E+09 0.00 0.28
December 0.00 0.00 0.00 16568441.08 0.00 0.00 0.716686E+09 0.00 0.28
                   
Annual Sum or Average 16595666.86 51850493.53 0.00 0.117408E+09 0.00 0.00 0.540335E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2218040.25 0.00 0.00 81813280.51 0.00 0.28
Maximum of Months 16595666.86 21322335.00 0.00 17215289.28 0.00 0.00 0.833107E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.291351E+10 0.00 0.00 8147513.27 0.00 0.00 0.552456E+10 0.00 0.28
February 0.00 0.00 0.00 54758098.88 0.00 0.00 0.647117E+10 0.00 0.28
March 0.00 0.00 0.00 0.118463E+09 0.00 0.00 0.662790E+10 0.00 0.31
April 0.00 0.00 0.00 0.156928E+09 0.00 0.00 0.464116E+10 0.00 0.29
May 0.00 1351187.95 0.00 31291592.59 0.00 0.00 0.409093E+10 0.00 0.29
June 0.00 0.132730E+09 0.00 68601801.57 0.00 0.00 0.201973E+10 0.00 0.30
July 0.00 0.212285E+09 0.00 85232475.30 0.00 0.00 0.823344E+09 0.00 0.28
August 0.00 58666637.34 0.00 0.154427E+09 0.00 0.00 0.152739E+10 0.00 0.31
September 0.00 0.110849E+09 0.00 28184791.85 0.00 0.00 0.259714E+10 0.00 0.29
October 0.00 0.00 0.00 70934306.57 0.00 0.00 0.440798E+10 0.00 0.28
November 0.00 0.00 0.00 0.103582E+09 0.00 0.00 0.545556E+10 0.00 0.28
December 0.00 0.00 0.00 0.142294E+09 0.00 0.00 0.718798E+10 0.00 0.28
                   
Annual Sum or Average 0.291351E+10 0.515882E+09 0.00 0.102284E+10 0.00 0.00 0.513748E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 8147513.27 0.00 0.00 0.823344E+09 0.00 0.28
Maximum of Months 0.291351E+10 0.212285E+09 0.00 0.156928E+09 0.00 0.00 0.718798E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.606268E+09 0.00 0.00 246534.67 0.00 0.00 0.218872E+09 0.00 0.28
February 0.00 0.00 0.00 4492817.06 0.00 0.00 0.648037E+09 0.00 0.28
March 0.00 0.00 0.00 10827164.88 0.00 0.00 0.663825E+09 0.00 0.31
April 0.00 0.00 0.00 14980378.05 0.00 0.00 0.464987E+09 0.00 0.29
May 28709560.03 137152.95 0.00 2677942.54 0.00 0.00 0.380144E+09 0.00 0.29
June 0.00 13309660.90 0.00 6718166.48 0.00 0.00 0.202326E+09 0.00 0.30
July 0.00 21232271.97 0.00 8493275.44 0.00 0.00 82479775.99 0.00 0.28
August 0.00 5906715.87 0.00 15302650.64 0.00 0.00 0.152866E+09 0.00 0.31
September 7047073.91 11064536.49 0.00 2419627.78 0.00 0.00 0.254285E+09 0.00 0.29
October 0.00 0.00 0.00 6269141.26 0.00 0.00 0.441886E+09 0.00 0.28
November 0.00 0.00 0.00 9298106.52 0.00 0.00 0.546674E+09 0.00 0.28
December 0.00 0.00 0.00 13079601.28 0.00 0.00 0.720045E+09 0.00 0.28
                   
Annual Sum or Average 0.642025E+09 51650338.19 0.00 94805406.61 0.00 0.00 0.477643E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 246534.67 0.00 0.00 82479775.99 0.00 0.28
Maximum of Months 0.606268E+09 21232271.97 0.00 15302650.64 0.00 0.00 0.720045E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.216601E+09 0.00 0.00 0.230704E+11 0.00 0.32
February 0.00 0.00 0.00 0.407125E+09 0.00 0.00 0.176929E+11 0.00 0.32
March 0.00 0.00 0.00 0.712707E+09 0.00 0.00 0.179595E+11 0.00 0.35
April 0.00 0.00 0.00 0.863455E+09 0.00 0.00 0.123157E+11 0.00 0.32
May 0.00 0.00 0.00 0.220047E+09 0.00 0.00 0.110013E+11 0.00 0.33
June 0.00 0.269553E+09 0.00 0.378334E+09 0.00 0.00 0.531985E+10 0.00 0.34
July 0.00 0.421842E+09 0.00 0.459977E+09 0.00 0.00 0.221016E+10 0.00 0.31
August 0.00 0.00 0.00 0.935221E+09 0.00 0.00 0.549376E+10 0.00 0.35
September 0.00 0.251405E+09 0.00 0.195488E+09 0.00 0.00 0.667052E+10 0.00 0.32
October 0.00 0.00 0.00 0.436266E+09 0.00 0.00 0.114184E+11 0.00 0.32
November 0.00 0.00 0.00 0.629818E+09 0.00 0.00 0.145839E+11 0.00 0.32
December 0.00 0.00 0.00 0.866095E+09 0.00 0.00 0.192765E+11 0.00 0.32
                   
Annual Sum or Average 0.00 0.942800E+09 0.00 0.632113E+10 0.00 0.00 0.147013E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.195488E+09 0.00 0.00 0.221016E+10 0.00 0.31
Maximum of Months 0.00 0.421842E+09 0.00 0.935221E+09 0.00 0.00 0.230704E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:59

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.279061E+12 0.456807E+11 0.00 0.211017E+13 0.866305E+12
February 0.371583E+12 0.356649E+11 0.00 0.188299E+13 0.108466E+13
March 0.634618E+12 0.333850E+11 0.00 0.216405E+13 0.155326E+13
April 0.679568E+12 0.239685E+11 0.00 0.215028E+13 0.194596E+13
May 0.893715E+12 0.236969E+11 0.00 0.206377E+13 0.912854E+12
June 0.976872E+12 0.121997E+11 0.00 0.169231E+13 0.190803E+13
July 0.967427E+12 0.779028E+10 0.00 0.131988E+13 0.300940E+13
August 0.805540E+12 0.853993E+10 0.00 0.149249E+13 0.321949E+13
September 0.607826E+12 0.157173E+11 0.00 0.177507E+13 0.122632E+13
October 0.401095E+12 0.230578E+11 0.00 0.221642E+13 0.121403E+13
November 0.221802E+12 0.322648E+11 0.00 0.206027E+13 0.150257E+13
December 0.183626E+12 0.408763E+11 0.00 0.203107E+13 0.203871E+13
           
Annual Sum or Average 0.702273E+13 0.302842E+12 0.00 0.229588E+14 0.204816E+14
Minimum of Months 0.183626E+12 0.779028E+10 0.00 0.131988E+13 0.866305E+12
Maximum of Months 0.976872E+12 0.456807E+11 0.00 0.221642E+13 0.321949E+13