Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 09:02:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 37090.82 | 800.75 | 800.75 |
Net Site Energy | 37090.82 | 800.75 | 800.75 |
Total Source Energy | 115810.89 | 2500.21 | 2500.21 |
Net Source Energy | 115810.89 | 2500.21 | 2500.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 158.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7512.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2890.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1666.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2085.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22448.86 |
Humidification | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 636.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36295.94 | 794.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24759.67 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 158.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 7512.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2890.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1666.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2085.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22448.86 |
Humidification | General | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 636.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 158.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7512.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3942.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 905.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1997.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2890.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1666.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2085.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22448.86 |
Humidification | Unassigned | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 636.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 307.36 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 783.58 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 104.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 307.36 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Other | 371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 783.58 | 17.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 36295.936 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 36295.936 | 100.00 |
Total On-Site and Utility Electric Sources | 36295.936 | 100.00 |
Total Electricity End Uses | 36295.936 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 24759.67 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 24759.67 | 100.00 |
Total Water End Uses | 24759.67 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1075.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 9.1390 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.1390 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 9.1390 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 9.1390 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.7111 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 9.1390 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 9.1631 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1390 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.1390 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 9.1390 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.1390 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.1390 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.1390 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.1390 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 11.7111 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 9.1390 | 18.58 | 484.4232 | |
Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 9.1631 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.8180 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-AUG-15:00 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 03-MAY-15:09 |
Heating | 0.00 | 489599.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 645610.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 86589.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 324913.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 96618.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 96599.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28923.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2388568.39 | 518523.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 489599.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 645610.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 324913.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 96618.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 96599.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28923.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 171.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23791.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2866.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6326.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9154.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5278.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6604.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 260.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 689.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 114949.23 | 861.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 513.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 113.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 142.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2481.61 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 513.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 269.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 136.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 197.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 113.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 142.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2481.61 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.95 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.485446 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.62 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.464878 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.96 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.27 | 0.303538 | 0.300000 | 1.88 | 0.809433 | 0.500000 | 0.001255 | 0.000161 | 1.88 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.53 | 0.319504 | 0.300000 | 17.86 | 0.852009 | 0.500000 | 0.001192 | 0.002966 | 17.86 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.10 | 0.311846 | 0.300000 | 1.83 | 0.831588 | 0.500000 | 0.001222 | 0.000537 | 1.87 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.23 | 0.193776 | 0.300000 | 0.369738 | 0.516735 | 0.500000 | 0.001966 | 0.000046 | 0.369738 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.956367 | 0.160927 | 0.300000 | 0.286910 | 0.429138 | 0.500000 | 0.002368 | 0.000037 | 0.286910 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.25 | 0.190458 | 0.300000 | 0.376187 | 0.507888 | 0.500000 | 0.002000 | 0.000063 | 0.376187 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.24 | 0.123789 | 0.300000 | 0.372986 | 0.330104 | 0.500000 | 0.003078 | 0.000033 | 0.372986 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.26 | 0.194748 | 0.300000 | 3.68 | 0.519327 | 0.500000 | 0.001956 | 0.001076 | 3.76 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.04 | 0.153325 | 0.300000 | 3.01 | 0.408867 | 0.500000 | 0.002485 | 0.000760 | 3.01 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.37 | 0.193065 | 0.300000 | 3.71 | 0.514840 | 0.500000 | 0.001973 | 0.001076 | 3.76 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.74 | 0.143256 | 0.300000 | 3.22 | 0.382016 | 0.500000 | 0.002660 | 0.000711 | 3.22 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.44 | 0.165935 | 0.300000 | 0.431772 | 0.442493 | 0.500000 | 0.002296 | 0.000156 | 0.543917 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142644 | 0.300000 | 0.323683 | 0.380385 | 0.500000 | 0.002671 | 0.000102 | 0.358179 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.44 | 0.165525 | 0.300000 | 0.432851 | 0.441400 | 0.500000 | 0.002302 | 0.000156 | 0.543922 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.22 | 0.126635 | 0.300000 | 0.364604 | 0.337692 | 0.500000 | 0.003009 | 0.000098 | 0.364604 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18450.55 | 0.000161 | 371.95 |
CORE_MID VAV BOX REHEAT COIL | 339065.82 | 0.002966 | 7533.21 |
CORE_TOP VAV BOX REHEAT COIL | 61436.22 | 0.000537 | 1623.45 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5232.84 | 0.000046 | 110.30 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4207.40 | 0.000037 | 89.16 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7167.33 | 0.000063 | 159.36 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3775.21 | 0.000033 | 76.34 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 122961.09 | 0.001076 | 3245.27 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 86909.82 | 0.000760 | 2176.68 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 122961.76 | 0.001076 | 3245.28 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 81294.37 | 0.000711 | 1944.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17787.19 | 0.000156 | 469.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11712.55 | 0.000102 | 308.98 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17787.36 | 0.000156 | 469.24 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11189.63 | 0.000098 | 287.16 |
VAV_BOT WITH REHEAT HEATING COIL | 23709.78 | 0.000207 | 414.60 |
VAV_MID WITH REHEAT HEATING COIL | 194338.71 | 0.001700 | 3420.56 |
VAV_TOP WITH REHEAT HEATING COIL | 15772.20 | 0.000138 | 280.93 |
CAV_BAS HEATING COIL | 271929.22 | 0.002379 | 6184.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.48 | 3.29 | 10.95 | 3.29 | 10.30 | 10.30 | 0.300000 | 0.319048 | 10.30 |
VAV_MID WITH REHEAT | 52.47 | 31.48 | 104.95 | 31.48 | 98.19 | 98.19 | 0.300000 | 0.320644 | 98.19 |
VAV_TOP WITH REHEAT | 5.64 | 3.38 | 11.28 | 3.65 | 11.20 | 11.20 | 0.300000 | 0.325780 | 11.20 |
CAV_BAS | 5.95 | 5.95 | 5.95 | 5.95 | 5.95 | 5.95 | 1.00 | 1.00 | 5.95 |
AIRLOOP DATACENTER BASEMENT | 21.96 | 21.96 | 21.96 | 21.96 | 21.96 | 21.96 | 1.00 | 0.999988 | 21.96 |
AIRLOOP DATACENTER BOT | 0.485446 | 0.485446 | 0.485446 | 0.485446 | 0.485446 | 0.485446 | 1.00 | 1.00 | 0.485446 |
AIRLOOP DATACENTER MID | 4.62 | 4.62 | 4.62 | 4.62 | 4.62 | 4.62 | 1.00 | 1.00 | 4.62 |
AIRLOOP DATACENTER TOP | 0.464878 | 0.464878 | 0.464878 | 0.464878 | 0.464878 | 0.464878 | 1.00 | 1.00 | 0.464878 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.30 | 2.65 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 98.19 | 27.61 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.20 | 2.78 |
CAV_BAS_OA_CONTROLLER | 5.95 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.96 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.485446 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.62 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.464878 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.78 | 6.67 | 10.90 | 0.007823 | 0.007000 | 245370.53 | 0.010439 | 10.30 |
VAV_MID WITH REHEAT COOLING COIL | 29.37 | 6.67 | 10.90 | 0.007921 | 0.007000 | 2438079.37 | 0.103722 | 98.19 |
VAV_TOP WITH REHEAT COOLING COIL | 28.48 | 6.67 | 10.90 | 0.007790 | 0.007000 | 261868.66 | 0.011140 | 11.20 |
CAV_BAS COOLING COIL | 27.46 | 6.67 | 11.25 | 0.007833 | 0.007000 | 130114.03 | 0.005535 | 5.95 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.30 |
VAV_MID WITH REHEAT FAN | 98.19 |
VAV_TOP WITH REHEAT FAN | 11.20 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010439 | 0.000046 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000207 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.103722 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001700 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011140 | 0.000043 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000138 | |
CAV_BAS_COOLC_CONTROLLER | 0.005535 | 0.000086 |
CAV_BAS_HEATC_CONTROLLER | 0.002379 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.95 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.96 | 452332.37 | 281689.46 | 0.011078 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.485446 | 9721.16 | 6127.59 | 0.000238 |
AIRLOOP DATACENTER MID COOLING COIL | 4.62 | 92636.81 | 58364.82 | 0.002269 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.464878 | 9570.90 | 5949.67 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.96 | 21.96 | 21.96 | 21.96 | 452332.37 | 452332.37 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.485446 | 0.485446 | 0.485446 | 0.485446 | 9721.16 | 9721.16 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.62 | 4.62 | 4.62 | 4.62 | 92636.81 | 92636.81 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.464878 | 0.464878 | 0.464878 | 0.464878 | 9570.90 | 9570.90 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.96 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.485446 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.62 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.464878 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.96 | 452332.37 | 0.011078 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.485446 | 9721.16 | 0.000238 |
AIRLOOP DATACENTER MID HEATING COIL | 4.62 | 92636.81 | 0.002269 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.464878 | 9570.90 | 0.000234 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.130836 | 26960.45 | |
HEATSYS1 PUMP | 0.012403 | 3735.11 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.130836 | 15.70 |
HEATSYS1 | 0.012403 | 1.49 |
COOLSYS1_SUPPLY | 0.130836 | 15.70 |
SINGLE WATER PLANT LOOP | 0.013819 | 1.66 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.130836 | 0.130836 | 549184.39 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1417689.05 | 1417689.05 | 0.012403 |
CENTRAL BOILER | 569212.87 | 558169.91 | 0.013819 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.130836 | 18665.63 |
PLANT CIRC PUMP | 0.013819 | 3524.47 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.130836 | 0.065735 | 1548963.22 | 1556306.39 | 0.077310 |
COOLSYS1 CHILLER2 | 0.130836 | 0.065735 | 1548963.22 | 1556306.39 | 0.077310 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013819 | 139666.47 | 57342.50 | 69833.23 | 7879.72 | 21218.12 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.154620 | 18.55 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.154620 | 46568.29 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 63.92 | 1846515.70 | 12.78 | 230814.46 |
TOWERWATERSYS COOLTOWER 2 | 63.92 | 1846515.70 | 12.78 | 230814.46 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.079995 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 9.139 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.981 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 9.139 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.209 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 11.711 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.010 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 9.139 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.562 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 25401.240 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25401.240 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 22812.099 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22812.099 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2864.287 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.287 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2864.349 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2864.349 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1845.855 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.855 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 7162.063 | 9.139 | 169.792 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7162.063 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 423.975 | 11.711 | 217.579 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 423.975 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.577 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.047 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4342 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4667 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3211 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.12099322E-14 | 0.54033272E-16 | -0.11477910E-09 | -0.27710807E-17 |
51 | 8 | 0.16940797E-07 | 0.21224416E-12 | 0.32375051E-03 | -0.19262269E-09 |
52 | 7 | -0.10621294E-01 | 0.11709431E-07 | -0.20750295E-01 | 0.12076796E-03 |
53 | 6 | 0.36131393 | 0.41807893E-05 | 0.43439322 | -0.42286832E-02 |
54 | 5 | -4.7606848 | 0.15962239E-03 | -4.1508709 | 0.57853670E-01 |
55 | 4 | 31.100555 | 0.13320798E-02 | 20.303362 | -0.39686686 |
56 | 3 | -107.17647 | 0.29548442E-02 | -53.375374 | 1.4566908 |
57 | 2 | 193.11469 | 0.16882749E-02 | 75.816028 | -2.8369401 |
58 | 1 | -169.67987 | 0.18284532E-03 | -54.662593 | 2.7195671 |
59 | 0 | 57.057407 | 0.10574105E-05 | 15.661805 | |
60 | 9 | 0.96849018E-15 | 0.52038803E-16 | -0.11888120E-09 | -0.34576713E-17 |
61 | 8 | 0.17522454E-07 | 0.20301963E-12 | 0.33037841E-03 | -0.19923634E-09 |
62 | 7 | -0.10820889E-01 | 0.11110298E-07 | -0.21038320E-01 | 0.12303743E-03 |
63 | 6 | 0.36673991 | 0.39540183E-05 | 0.43906086 | -0.42926413E-02 |
64 | 5 | -4.8136684 | 0.15054623E-03 | -4.1869245 | 0.58510612E-01 |
65 | 4 | 31.335116 | 0.12532485E-02 | 20.444744 | -0.39998087 |
66 | 3 | -107.67610 | 0.27739881E-02 | -53.655083 | 1.4639080 |
67 | 2 | 193.61055 | 0.15819361E-02 | 76.071707 | -2.8448132 |
68 | 1 | -169.86329 | 0.17102974E-03 | -54.735356 | 2.7227817 |
69 | 0 | 57.057407 | 0.98718975E-06 | 15.648496 | |
70 | 9 | 0.64231630E-15 | 0.61559974E-16 | -0.96255912E-10 | -0.39759361E-17 |
71 | 8 | 0.14304568E-07 | 0.24979200E-12 | 0.29265740E-03 | -0.16264789E-09 |
72 | 7 | -0.96812919E-02 | 0.14355115E-07 | -0.19392345E-01 | 0.11007978E-03 |
73 | 6 | 0.33575460 | 0.52099710E-05 | 0.41230832 | -0.39274075E-02 |
74 | 5 | -4.5110355 | 0.20170803E-03 | -3.9798717 | 0.54758336E-01 |
75 | 4 | 29.994933 | 0.17040951E-02 | 19.631886 | -0.38218932 |
76 | 3 | -104.82023 | 0.38206815E-02 | -52.046581 | 1.4226568 |
77 | 2 | 190.77483 | 0.22034977E-02 | 74.603222 | -2.7997908 |
78 | 1 | -168.81380 | 0.24070374E-03 | -54.320777 | 2.7043882 |
79 | 0 | 57.057407 | 0.14049976E-05 | 15.727091 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 9.868E-004 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 9.962E-004 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 9.868E-004 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 9.962E-004 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.206 | 6.562E-004 | 1.025E-003 | 0.861 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 0.137 | 6.789E-004 | 1.025E-003 | 0.891 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 1.025E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 1.025E-003 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.305 | 8.549E-005 | 7.891E-005 | 0.252 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 80357.40620 | 80357.40620 | 5.95274 | 5.95274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 84594.36370 | 84594.36370 | 6.26626 | 6.26626 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 803840.25981 | 803840.25981 | 59.53122 | 59.53122 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 163780.30466 | 163780.30466 | 7.01837 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 82349.81973 | 82349.81973 | 6.09931 | 6.09931 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 43064.69665 | 43064.69665 | 1.87182 | 1.87182 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 16489.69819 | 16489.69819 | 1.23246 | 1.23246 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1606.84353 | 1606.84353 | 6.97900E-002 | 0.13533 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12795.73931 | 12795.73931 | 0.95637 | 0.95637 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 38.55650 | 9.15215E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1393.47469 | 1393.47469 | 6.03168E-002 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16777.30825 | 16777.30825 | 1.25396 | 1.25396 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3477.05355 | 3477.05355 | 0.15039 | 0.15039 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16634.67323 | 16634.67323 | 1.24329 | 1.24329 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 122.71695 | 122.71695 | 5.38831E-003 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 164069.69832 | 164069.69832 | 12.26308 | 12.26308 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 86106.57340 | 86106.57340 | 3.75634 | 3.75634 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 134298.07094 | 134298.07094 | 10.03784 | 10.03784 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 57364.26512 | 57364.26512 | 2.50288 | 2.50288 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 165503.29643 | 165503.29643 | 12.37023 | 12.37023 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 86107.04278 | 86107.04278 | 3.75636 | 3.75636 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 143737.64297 | 143737.64297 | 10.74337 | 10.74337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 49675.50326 | 49675.50326 | 2.16575 | 2.16575 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19255.69312 | 19255.69312 | 1.43924 | 1.43924 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12449.81832 | 12449.81832 | 0.54392 | 0.54392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14435.24761 | 14435.24761 | 1.07894 | 1.07894 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8197.78368 | 8197.78368 | 0.35818 | 0.35818 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19303.80651 | 19303.80651 | 1.44284 | 1.44284 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12449.93972 | 12449.93972 | 0.54392 | 0.54392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16260.24442 | 16260.24442 | 1.21535 | 1.21535 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7611.95746 | 7611.95746 | 0.33249 | 0.33249 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8235.74076 | 8235.74076 | 0.48545 | 0.48545 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78409.60752 | 78409.60752 | 4.62176 | 4.62176 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7886.80965 | 7886.80965 | 0.46488 | 0.46488 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372537.70079 | 372537.70079 | 21.96087 | 21.96087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 188155.68 | 10.29844 | 10.29844 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 11791.17 | 1.53798 | 1.53798 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1807864.70 | 98.18893 | 98.18893 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 176023.57 | 22.95957 | 22.95957 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 206882.46 | 11.20492 | 11.20492 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 21322.97 | 3.65034 | 3.65034 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:20:00 |
7 | CAV_BAS | Cooling | Sensible | 94525.56 | 5.95274 | 5.95274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 373291.50 | 21.96113 | 21.96113 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8229.52 | 0.48545 | 0.48545 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78397.76 | 4.62176 | 4.62176 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8045.19 | 0.46488 | 0.46488 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.95274 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.26626 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30354 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87988 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80943 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25520E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61413E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87988 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18450.55078 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61413E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 371.94862 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.53122 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31950 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 17.85937 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85201 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19247E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.96630E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 17.85937 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 339065.81724 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96630E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7533.21041 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.09931 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31185 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.82979 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83159 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22176E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.37471E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87182 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 61436.21948 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.37471E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1623.44733 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23246 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19378 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36974 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51674 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96619E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.57792E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36974 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5232.84230 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.57792E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 110.29977 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95637 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16093 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28691 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42914 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36754E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.68082E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28691 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4207.39981 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.68082E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.15843 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25396 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19046 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37619 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50789 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00044E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.27029E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37619 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7167.32739 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.27029E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.36140 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24329 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12379 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37299 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33010 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07782E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30272E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37299 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3775.20862 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30272E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 76.33943 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.26308 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19475 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.67892 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51933 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95638E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07572E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.75634 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122961.09203 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07572E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3245.26594 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.03784 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15332 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.01135 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40887 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48492E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.60325E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.01135 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 86909.81835 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.60325E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2176.67743 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.37023 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19306 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.71107 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51484 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97343E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07572E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.75636 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122961.75908 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07572E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3245.28364 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.74337 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14326 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.22301 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38202 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65958E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.11199E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.22301 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81294.37338 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.11199E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1944.05317 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43924 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16594 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43177 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44249 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29608E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55610E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54392 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17787.18960 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55610E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 469.23860 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07894 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14264 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32368 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38038 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67098E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02467E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35818 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11712.55173 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02467E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 308.97762 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44284 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16553 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43285 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44140 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30177E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55612E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54392 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17787.36279 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55612E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 469.24317 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21535 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12663 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36460 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33769 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00866E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.78917E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36460 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11189.62671 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.78917E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.15674 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48545 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.62176 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46488 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.96087 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47616 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.28570 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.95232 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.28570 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.29844 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.29844 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31905 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.47287 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.48372 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 104.94573 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 31.48372 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 98.18893 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 98.18893 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32064 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.63784 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.38270 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.27568 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.65034 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.20492 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.20492 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32578 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.95274 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.95274 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.95274 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.95274 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.95274 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.95274 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.96087 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.96087 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.96087 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.96087 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.96113 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.96113 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48545 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48545 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48545 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48545 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48545 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48545 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.62176 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.62176 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.62176 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.62176 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.62176 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.62176 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46488 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46488 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46488 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46488 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46488 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46488 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.29844 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 98.18893 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.20492 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.95274 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.96113 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48545 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.62176 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46488 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.29844 |
289 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.65072 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.77804 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90153 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.82318E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 245370.52983 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.04386E-002 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.29844 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 23709.78185 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07424E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 414.59553 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.29844 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.04386E-002 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.56181E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07424E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 98.18893 |
306 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 27.60938 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.37225 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90187 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.92116E-003 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2438079.37329 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10372 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 98.18893 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 194338.70835 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70016E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3420.55834 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 98.18893 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10372 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.59105E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.70016E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.20492 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.78477 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.47990 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90141 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.79031E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 261868.66321 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.11405E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.20492 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 15772.20121 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37982E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 280.93011 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.20492 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.11405E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.27441E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37982E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.95274 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.46121 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.25469 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.83301E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 130114.03085 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.53535E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.95274 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 271929.21557 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37896E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6184.98228 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.95274 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.53535E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.60271E-005 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.37896E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.96113 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.96113 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 452332.37192 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 281689.45554 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10776E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.96113 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.96113 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.96113 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.96113 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 452332.37192 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 452332.37192 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.96113 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.96113 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 452332.37192 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10776E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.79501E-005 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48545 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48545 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9721.16346 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6127.59228 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38071E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48545 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48545 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48545 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48545 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9721.16346 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9721.16346 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48545 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48545 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9721.16346 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38071E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.62176 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.62176 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92636.81485 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58364.81619 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26867E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.62176 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.62176 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.62176 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.62176 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92636.81485 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92636.81485 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.62176 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.62176 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92636.81485 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26867E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46488 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46488 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9570.90298 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5949.66686 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34391E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46488 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46488 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46488 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46488 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9570.90298 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9570.90298 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46488 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46488 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9570.90298 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34391E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13084 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26960.45286 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13084 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.70032 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13084 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13084 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 549184.39236 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.24026E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.48831 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.24026E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3735.10709 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1417689.04625 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1417689.05000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.24026E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13084 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.70032 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.13084 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18665.63096 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13084 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.57350E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1548963.21668 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1556306.38500 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.73102E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13084 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.57350E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1548963.21668 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1556306.38500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.73102E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.38187E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.65825 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.38187E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3524.46509 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.38187E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57342.49579 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21218.12459 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 569212.86852 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 558169.91000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.38187E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15462 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.55444 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15462 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 46568.28714 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 63.92432 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1846515.69667 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.78486 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 230814.46208 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 63.92432 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1846515.69667 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.78486 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 230814.46208 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.99950E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.99950E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17495.05 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 321343.08 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 58230.69 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4960.87 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3988.35 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6792.67 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3579.65 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 116518.90 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 82315.34 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 116519.53 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 77016.02 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16853.86 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11097.92 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16854.02 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10597.06 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 20553.95 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 170534.26 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 14146.71 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 221142.82 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 301794.80 | 197876.17 | 103918.63 | 0.66 | 40160.73 | 407.33 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2911925.98 | 1901650.45 | 1010275.53 | 0.65 | 385092.37 | 3905.82 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 326538.98 | 214505.96 | 112033.02 | 0.66 | 43608.28 | 442.30 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 167884.90 | 111440.17 | 56444.72 | 0.66 | 22001.87 | 223.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.577 | 1.276 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.047 | 1.567 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.4426453821 | 0.1759108606 | Pass | Pass | 0.5897816328 | 0.5264651753 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.7239580146E-003 | 1.8914633640E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.6753519036E-003 | 1.9453828609E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.1119475121E-002 | 1.2463185793E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1074347015E-002 | 1.4961629788E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.9003281417E-002 | 3.2919621608E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 4.9824673522E-002 | 3.8459646545E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4388893762E-002 | 3.1220549110E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2160361623E-002 | 1.4405173187E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.0539667999E-002 | 3.1151848539E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.5689600303E-002 | 4.0955400090E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.6270193689E-002 | 3.1744225794E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.5128103783E-002 | 2.1548991605E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2595316696E-002 | 2.8499918510E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.7276757913E-002 | 4.4659213276E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9702244476E-002 | 3.6721451180E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7104807065E-003 | 2.9526874888E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9754420820E-003 | 3.2116130880E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2845614099E-002 | 4.8789341167E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7277274147E-005 | 8.3703856144E-005 | Pass | Pass | 2.2215960101E-003 | 1.2190026874E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8921821149E-005 | 5.6619171115E-005 | Pass | Pass | 7.3542387760E-003 | 3.8943153862E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6033055135E-002 | 1.8014470513E-002 | Pass | Pass | 1.1138802857E-002 | 8.9063014450E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7796976505E-004 | 2.2977897992E-004 | Pass | Pass | 5.9924429651E-005 | 1.0972177391E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4690.38 | -77.1 | 0.00 | -8802.5 | 47466.76 | 43277.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.276 | 1.577 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.567 | 2.047 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1390 | 2779.43 | 25401.24 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 235.63 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.1390 | 24961.20 | 228120.99 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 2116.09 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.1390 | 2496.12 | 22812.10 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 211.61 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.1390 | 3134.13 | 28642.87 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.1390 | 3134.20 | 28643.49 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 265.70 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.1390 | 2019.75 | 18458.55 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 171.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.1390 | 313.41 | 2864.29 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.1390 | 313.42 | 2864.35 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 26.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.1390 | 201.98 | 1845.86 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 17.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 9.1390 | 783.68 | 7162.06 | LightsWired | LTG_SCH_OFFICE | 50.73 | 168.00 | 49.42 | 0.0000 | Y | 66.44 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 11.7111 | 362.03 | 4239.75 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 43.70 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 11.7111 | 36.20 | 423.97 | LightsWired | LTG_SCH_DATACENTER | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 4.37 |
Interior Lighting Total | 9.1631 | 46320.38 | 424440.34 | 1212.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 57580.60 | AstronomicalClock | - | 83.75 | 83.75 | 905.27 | |
Exterior Lighting Total | 57580.60 | 905.27 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3068360.01 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1417689.05 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1556306.39 | 6.11 | 1488541.58 | 5.82 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1556306.39 | 6.11 | 1488541.58 | 5.82 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 558169.91 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1846515.70 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1846515.70 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 245370.53 | 301794.80 | 197876.17 | 103918.63 | 0.66 | - | 40160.73 | 407.33 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2438079.37 | 2911925.98 | 1901650.45 | 1010275.53 | 0.65 | - | 385092.37 | 3905.82 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 261868.66 | 326538.98 | 214505.96 | 112033.02 | 0.66 | - | 43608.28 | 442.30 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 130114.03 | 167884.90 | 111440.17 | 56444.72 | 0.66 | - | 22001.87 | 223.16 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 452332.37 | 281689.46 | 170642.92 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9721.16 | 6127.59 | 3593.57 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92636.81 | 58364.82 | 34272.00 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9570.90 | 5949.67 | 3621.24 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18450.55 | 17495.05 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 339065.82 | 321343.08 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 61436.22 | 58230.69 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5232.84 | 4960.87 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4207.40 | 3988.35 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7167.33 | 6792.67 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3775.21 | 3579.65 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 122961.09 | 116518.90 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 86909.82 | 82315.34 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 122961.76 | 116519.53 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 81294.37 | 77016.02 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17787.19 | 16853.86 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11712.55 | 11097.92 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17787.36 | 16854.02 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11189.63 | 10597.06 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 23709.78 | 20553.95 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 194338.71 | 170534.26 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 15772.20 | 14146.71 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 271929.22 | 221142.82 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 452332.37 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9721.16 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92636.81 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9570.90 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.30 | 23393.87 | 2271.59 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 98.19 | 223045.31 | 2271.59 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.20 | 25453.02 | 2271.59 | 1.00 | 1.11 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1110.54 | 5.95 | 11006.91 | 1849.05 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.96 | 36219.33 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 543.75 | 1120.11 | 1.00 | 1.62 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.62 | 5176.87 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 520.71 | 1120.11 | 1.00 | 1.64 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.130836 | 26960.45 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.012403 | 3735.11 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.130836 | 18665.63 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013819 | 3524.47 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.154620 | 46568.29 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 80357.41 | 80357.41 | 28.91 | 5.953 | 5.953 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 84594.36 | 84594.36 | 33.89 | 6.266 | 6.266 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 803840.26 | 803840.26 | 322.04 | 59.531 | 59.531 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 82349.82 | 82349.82 | 32.99 | 6.099 | 6.099 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 34.82 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16489.70 | 16489.70 | 52.61 | 1.232 | 1.232 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00728 | 41.90 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12795.74 | 12795.74 | 63.35 | 0.956 | 0.956 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 24.00 | 24.00 | 0.00723 | 38.56 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16777.31 | 16777.31 | 53.53 | 1.254 | 1.254 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 24.00 | 24.00 | 0.00727 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16634.67 | 16634.67 | 82.36 | 1.243 | 1.243 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00718 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 164069.70 | 164069.70 | 523.49 | 12.263 | 12.263 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00734 | 41.81 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 134298.07 | 134298.07 | 664.92 | 10.038 | 10.038 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00728 | 38.80 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 165503.30 | 165503.30 | 528.06 | 12.370 | 12.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 24.00 | 24.00 | 0.00734 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 143737.64 | 143737.64 | 711.66 | 10.743 | 10.743 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00726 | 41.16 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19255.69 | 19255.69 | 61.44 | 1.439 | 1.439 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00732 | 41.71 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14435.25 | 14435.25 | 71.47 | 1.079 | 1.079 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00728 | 39.53 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19303.81 | 19303.81 | 61.59 | 1.443 | 1.443 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00731 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16260.24 | 16260.24 | 80.51 | 1.215 | 1.215 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00725 | 41.16 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8235.74 | 8235.74 | 227.49 | 0.485 | 0.485 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78409.61 | 78409.61 | 2165.85 | 4.622 | 4.622 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7886.81 | 7886.81 | 217.85 | 0.465 | 0.465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372537.70 | 372537.70 | 475.37 | 21.961 | 21.961 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.84 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.43 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 163780.30 | 163780.30 | 65.61 | 7.018 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 43064.70 | 43064.70 | 17.25 | 1.872 | 1.872 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1606.84 | 1606.84 | 5.13 | 0.070 | 0.135 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1393.47 | 1393.47 | 6.90 | 0.060 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3477.05 | 3477.05 | 11.09 | 0.150 | 0.150 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 122.72 | 122.72 | 0.61 | 0.005 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00676 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 86106.57 | 86106.57 | 274.74 | 3.756 | 3.756 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 57364.27 | 57364.27 | 284.02 | 2.503 | 2.503 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 86107.04 | 86107.04 | 274.73 | 3.756 | 3.756 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 49675.50 | 49675.50 | 245.95 | 2.166 | 2.166 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12449.82 | 12449.82 | 39.72 | 0.544 | 0.544 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8197.78 | 8197.78 | 40.59 | 0.358 | 0.358 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12449.94 | 12449.94 | 39.72 | 0.544 | 0.544 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7611.96 | 7611.96 | 37.69 | 0.332 | 0.332 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.17 | 0.00698 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.11 | 0.00620 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.30 | 10.30 | 1.54 | 1.54 | 10.2984 | 3.2857 | 10.2984 | 0.3190 | 0.3000 |
VAV_MID WITH REHEAT | 98.19 | 98.19 | 22.96 | 22.96 | 98.1889 | 31.4837 | 98.1889 | 0.3206 | 0.3000 |
VAV_TOP WITH REHEAT | 11.20 | 11.20 | 3.65 | 3.65 | 11.2049 | 3.6503 | 11.2049 | 0.3258 | 0.3000 |
CAV_BAS | 5.95 | 5.95 | 1.20 | 1.20 | 5.9527 | 5.9527 | 5.9527 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.96 | 21.96 | 0.34 | 0.34 | 21.9611 | 21.9609 | 21.9611 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4854 | 0.4854 | 0.4854 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.62 | 4.62 | 0.16 | 0.16 | 4.6218 | 4.6218 | 4.6218 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4649 | 0.4649 | 0.4649 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18450.551 | 18450.551 | 1.879877 | 0.00016141 | 371.949 | 1/21 00:10:00 | 1/21 00:10:00 | 18450.55 | 18450.55 | 1.879877 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 18518.58 | 18518.58 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 339065.817 | 339065.817 | 17.859367 | 0.00296630 | 7533.210 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 339065.82 | 339065.82 | 17.859367 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 163780.30 | 0.00 | 340231.49 | 340231.49 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 61436.219 | 61436.219 | 1.871825 | 0.00053747 | 1623.447 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61436.22 | 61436.22 | 1.871825 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 43064.70 | 0.00 | 61660.83 | 61660.83 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5232.842 | 5232.842 | 0.369738 | 0.00004578 | 110.300 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5232.84 | 5232.84 | 0.369738 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00757766 | 47.7838 | 1606.84 | 0.00 | 5251.74 | 5251.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4207.400 | 4207.400 | 0.286910 | 0.00003681 | 89.158 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4207.40 | 4207.40 | 0.286910 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00762216 | 48.0612 | 1393.47 | 0.00 | 4222.26 | 4222.26 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7167.327 | 7167.327 | 0.376187 | 0.00006270 | 159.361 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7167.33 | 7167.33 | 0.376187 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00773717 | 48.7775 | 3477.05 | 0.00 | 7191.96 | 7191.96 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3775.209 | 3775.209 | 0.372986 | 0.00003303 | 76.339 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3775.21 | 3775.21 | 0.372986 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00676451 | 42.7110 | 122.72 | 0.00 | 3789.11 | 3789.11 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 122961.092 | 122961.092 | 3.756337 | 0.00107572 | 3245.266 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122961.09 | 122961.09 | 3.756337 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00783698 | 49.3995 | 86106.57 | 0.00 | 123382.19 | 123382.19 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 86909.818 | 86909.818 | 3.011351 | 0.00076032 | 2176.677 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 86909.82 | 86909.82 | 3.011351 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00784248 | 49.4337 | 57364.27 | 0.00 | 87180.48 | 87180.48 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 122961.759 | 122961.759 | 3.756357 | 0.00107572 | 3245.284 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122961.76 | 122961.76 | 3.756357 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00783698 | 49.3994 | 86107.04 | 0.00 | 123382.86 | 123382.86 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 81294.373 | 81294.373 | 3.223010 | 0.00071120 | 1944.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81294.37 | 81294.37 | 3.223010 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00778994 | 49.1068 | 49675.50 | 0.00 | 81558.48 | 81558.48 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17787.190 | 17787.190 | 0.543917 | 0.00015561 | 469.239 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17787.19 | 17787.19 | 0.543917 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791449 | 49.8814 | 12449.82 | 0.00 | 17846.58 | 17846.58 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11712.552 | 11712.552 | 0.358179 | 0.00010247 | 308.978 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11712.55 | 11712.55 | 0.358179 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791591 | 49.8903 | 8197.78 | 0.00 | 11751.60 | 11751.60 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17787.363 | 17787.363 | 0.543922 | 0.00015561 | 469.243 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17787.36 | 17787.36 | 0.543922 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791449 | 49.8814 | 12449.94 | 0.00 | 17846.75 | 17846.75 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11189.627 | 11189.627 | 0.364604 | 0.00009789 | 287.157 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11189.63 | 11189.63 | 0.364604 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00789717 | 49.7738 | 7611.96 | 0.00 | 11224.06 | 11224.06 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 245370.530 | -999.000 | 10.298442 | 0.01043863 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 245370.53 | 222829.84 | 10.298442 | 28.78 | 17.21 | 0.00782318 | 10.90 | 9.51 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 25.7390 | 24.00 | 0.00734072 | 38.5927 | 133580.05 | 0.00 | 249897.42 | 235102.59 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 23709.782 | 23709.782 | 3.089532 | 0.00020742 | 414.596 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23709.78 | 23709.78 | 3.089532 | 6.29 | 6.29 | 0.00613234 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 85.7968 | 22.66 | 0.00655233 | 37.4037 | 6600.09 | 0.00 | 24884.37 | 24884.37 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2438079.373 | -999.000 | 98.188931 | 0.10372153 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2438079.37 | 2196380.37 | 98.188931 | 29.37 | 17.49 | 0.00792116 | 10.90 | 9.51 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 28.1186 | 24.00 | 0.00739487 | 38.8744 | 1237445.94 | 0.00 | 2481823.84 | 2312056.35 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 194338.708 | 194338.708 | 29.456679 | 0.00170016 | 3420.558 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 194338.71 | 194338.71 | 29.456679 | 7.21 | 6.88 | 0.00618757 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 93.7288 | 21.00 | 0.00789198 | 49.7413 | 443033.69 | 0.00 | 206463.98 | 206463.98 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 261868.663 | -999.000 | 11.204922 | 0.01114050 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 261868.66 | 238379.89 | 11.204922 | 28.48 | 17.08 | 0.00779031 | 10.90 | 9.51 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 24.8531 | 24.00 | 0.00733701 | 38.5738 | 149665.41 | 0.00 | 266764.53 | 251780.37 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 15772.201 | 15772.201 | 3.361477 | 0.00013798 | 280.930 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15772.20 | 15772.20 | 3.361477 | 8.82 | 7.89 | 0.00639696 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 82.8437 | 21.00 | 0.00796446 | 50.1917 | 63393.64 | 0.00 | 17127.40 | 17127.40 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 130114.031 | -999.000 | 5.952736 | 0.00553535 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 130114.03 | 117292.23 | 5.952736 | 27.46 | 16.77 | 0.00783301 | 11.25 | 9.66 | 0.00700000 | 39.77 | 0.00915417 | 21.63 | 20.1614 | 24.00 | 0.00746133 | 39.2193 | 79253.74 | 0.00 | 132645.81 | 125194.02 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 271929.216 | 271929.216 | 5.952736 | 0.00237896 | 6184.982 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 271929.22 | 271929.22 | 5.952736 | 1.27 | 1.27 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 20.1614 | 25.84 | 0.00607234 | 28.6564 | 0.00 | 0.00 | 234027.27 | 234027.27 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 452332.372 | 281689.456 | 21.961132 | 0.01107759 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 406282.65 | 402565.36 | -999.0 | 28.66 | 16.55 | 0.00707471 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704207 | 30.9976 | 372053.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9721.163 | 6127.592 | 0.485446 | 0.00023807 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8686.07 | 8610.78 | -999.0 | 28.14 | 16.36 | 0.00706897 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 8189.48 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92636.815 | 58364.816 | 4.621759 | 0.00226867 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 82787.12 | 82034.07 | -999.0 | 28.15 | 16.37 | 0.00707245 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 78020.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9570.903 | 5949.667 | 0.464878 | 0.00023439 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8596.78 | 8427.21 | -999.0 | 28.45 | 16.55 | 0.00716117 | 12.80 | 10.34 | 0.00700000 | 41.29 | 0.00915671 | 22.06 | -999.0000 | 27.00 | 0.00709170 | 31.2118 | 7882.33 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 452332.372 | 452332.372 | 21.961132 | 0.01107759 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 452332.37 | 452332.37 | 21.961132 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5409 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9721.163 | 9721.163 | 0.485446 | 0.00023807 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9721.16 | 9721.16 | 0.485446 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2202 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92636.815 | 92636.815 | 4.621759 | 0.00226867 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92636.81 | 92636.81 | 4.621759 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3823 | 25.17 | 0.00698274 | 34.2433 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9570.903 | 9570.903 | 0.464878 | 0.00023439 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9570.90 | 9570.90 | 0.464878 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3627 | 24.11 | 0.00619814 | 32.4220 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 21.961132 | 0.10 | 0.10 | 0.00698571 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5409 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.485446 | 0.20 | 0.20 | 0.00697013 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2202 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.621759 | 0.21 | 0.21 | 0.00695195 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3823 | 25.17 | 0.00698274 | 34.2433 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.464878 | 0.21 | 0.21 | 0.00619391 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3627 | 24.11 | 0.00619814 | 32.4220 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18450.551 | 18450.551 | 1.879877 | 0.00016141 | 371.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 1.2758 | 1.301453 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 18450.55 | 18450.55 | 1.0000 | 2.20657210 | 1.879877 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16139700 | 60.00 | 32.22 | 27.78 | 0.000 | 18450.55 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 18518.58 | 18518.58 | 2.20657210 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 339065.817 | 339065.817 | 17.859367 | 0.00296630 | 7533.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 23.4450 | 23.916797 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 339065.82 | 339065.82 | 1.0000 | 20.96306577 | 17.859367 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.96599309 | 60.00 | 32.22 | 27.78 | 0.000 | 339065.82 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 163780.30 | 0.00 | 340231.49 | 340231.49 | 20.96306577 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.72 | 17.61 | 0.00800000 | 49289.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 61436.219 | 61436.219 | 1.871825 | 0.00053747 | 1623.447 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 4.2481 | 4.333547 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61436.22 | 61436.22 | 1.0000 | 2.19712085 | 1.871825 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.53741602 | 60.00 | 32.22 | 27.78 | 0.000 | 61436.22 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 43064.70 | 0.00 | 61660.83 | 61660.83 | 2.19712085 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.32 | 21.28 | 0.00800000 | 61124.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5232.842 | 5232.842 | 0.369738 | 0.00004578 | 110.300 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.3618 | 0.369111 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5232.84 | 5232.84 | 1.0000 | 0.43399271 | 0.369738 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.04577452 | 60.00 | 32.22 | 27.78 | 0.000 | 5232.84 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00757766 | 21.00 | 0.00757766 | 47.7838 | 1606.84 | 0.00 | 5251.74 | 5251.74 | 0.43399271 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.67 | 16.19 | 0.00800000 | 45160.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4207.400 | 4207.400 | 0.286910 | 0.00003681 | 89.158 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.2909 | 0.296779 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4207.40 | 4207.40 | 1.0000 | 0.33677082 | 0.286910 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03680441 | 60.00 | 32.22 | 27.78 | 0.000 | 4207.40 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00762216 | 21.00 | 0.00762216 | 48.0612 | 1393.47 | 0.00 | 4222.26 | 4222.26 | 0.33677082 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.10 | 16.35 | 0.00800000 | 45597.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7167.327 | 7167.327 | 0.376187 | 0.00006270 | 159.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.4956 | 0.505564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7167.33 | 7167.33 | 1.0000 | 0.44156232 | 0.376187 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06269651 | 60.00 | 32.22 | 27.78 | 0.000 | 7167.33 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00773717 | 21.00 | 0.00773717 | 48.7775 | 3477.05 | 0.00 | 7191.96 | 7191.96 | 0.44156232 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.77 | 17.62 | 0.00800000 | 49347.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3775.209 | 3775.209 | 0.372986 | 0.00003303 | 76.339 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.2610 | 0.266293 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3775.21 | 3775.21 | 1.0000 | 0.43780556 | 0.372986 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03302380 | 60.00 | 32.22 | 27.78 | 0.000 | 3775.21 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.99 | 0.00676451 | 21.00 | 0.00676451 | 42.7110 | 122.72 | 0.00 | 3789.11 | 3789.11 | 0.43780556 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.29 | 14.96 | 0.00800000 | 41714.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122961.092 | 122961.092 | 3.756337 | 0.00107572 | 3245.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 8.5022 | 8.673347 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122961.09 | 122961.09 | 1.0000 | 4.40913385 | 3.756337 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07560754 | 60.00 | 32.22 | 27.78 | 0.000 | 122961.09 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00783698 | 21.00 | 0.00783698 | 49.3995 | 86106.57 | 0.00 | 123382.19 | 123382.19 | 4.40913385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61043.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 86909.818 | 86909.818 | 3.011351 | 0.00076032 | 2176.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 6.0094 | 6.130387 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 86909.82 | 86909.82 | 1.0000 | 3.53467983 | 3.011351 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.76024744 | 60.00 | 32.22 | 27.78 | 0.000 | 86909.82 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00784248 | 21.00 | 0.00784248 | 49.4337 | 57364.27 | 0.00 | 87180.48 | 87180.48 | 3.53467983 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.99 | 20.27 | 0.00800000 | 57724.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122961.759 | 122961.759 | 3.756357 | 0.00107572 | 3245.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 8.5023 | 8.673394 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122961.76 | 122961.76 | 1.0000 | 4.40915751 | 3.756357 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07561337 | 60.00 | 32.22 | 27.78 | 0.000 | 122961.76 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00783698 | 21.00 | 0.00783698 | 49.3994 | 86107.04 | 0.00 | 123382.86 | 123382.86 | 4.40915751 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61043.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 81294.373 | 81294.373 | 3.223010 | 0.00071120 | 1944.053 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 5.6212 | 5.734288 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 81294.37 | 81294.37 | 1.0000 | 3.78312241 | 3.223010 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.71112609 | 60.00 | 32.22 | 27.78 | 0.000 | 81294.37 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00778994 | 21.00 | 0.00778994 | 49.1068 | 49675.50 | 0.00 | 81558.48 | 81558.48 | 3.78312241 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.94 | 19.32 | 0.00800000 | 54618.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17787.190 | 17787.190 | 0.543917 | 0.00015561 | 469.239 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 1.2299 | 1.254661 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17787.19 | 17787.19 | 1.0000 | 0.63844160 | 0.543917 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15559422 | 60.00 | 32.22 | 27.78 | 0.000 | 17787.19 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791449 | 21.00 | 0.00791449 | 49.8814 | 12449.82 | 0.00 | 17846.58 | 17846.58 | 0.63844160 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11712.552 | 11712.552 | 0.358179 | 0.00010247 | 308.978 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.8099 | 0.826172 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11712.55 | 11712.55 | 1.0000 | 0.42042562 | 0.358179 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10245606 | 60.00 | 32.22 | 27.78 | 0.000 | 11712.55 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791591 | 21.00 | 0.00791591 | 49.8903 | 8197.78 | 0.00 | 11751.60 | 11751.60 | 0.42042562 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17787.363 | 17787.363 | 0.543922 | 0.00015561 | 469.243 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 1.2299 | 1.254673 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17787.36 | 17787.36 | 1.0000 | 0.63844779 | 0.543922 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15559574 | 60.00 | 32.22 | 27.78 | 0.000 | 17787.36 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791449 | 21.00 | 0.00791449 | 49.8814 | 12449.94 | 0.00 | 17846.75 | 17846.75 | 0.63844779 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11189.627 | 11189.627 | 0.364604 | 0.00009789 | 287.157 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 0.7737 | 0.789286 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11189.63 | 11189.63 | 1.0000 | 0.42796725 | 0.364604 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09788175 | 60.00 | 32.22 | 27.78 | 0.000 | 11189.63 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789717 | 21.00 | 0.00789717 | 49.7738 | 7611.96 | 0.00 | 11224.06 | 11224.06 | 0.42796725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.52 | 20.74 | 0.00800000 | 59286.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 245370.530 | -999.000 | 10.298442 | 0.01043863 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3829 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.298442 | 12.08816093 | 4197.9300 | 999.8980 | 130.82266554 | 12.27 | 6.67 | 5.60 | 3075432.60 | 7.9784 | 7.978407 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 245370.53 | 222829.84 | 1.0000 | 12.08816093 | 10.298442 | 28.78 | 17.21 | 0.00782318 | 48901.1 | 10.90 | 9.51 | 0.00700000 | 28602.7 | 10.43756471 | 6.67 | 12.27 | 5.60 | 23393.870 | 221976.66 | 42.00 | 0.00915790 | 22.26 | 2.65072000 | 25.7390 | 24.00 | 0.00734072 | 24.00 | 0.00734072 | 38.5927 | 133580.05 | 0.00 | 249897.42 | 235102.59 | 12.08816093 | 28.78 | 17.48 | 0.00782318 | 48901.1 | 9.70 | 9.55 | 0.00733730 | 28228.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23709.782 | 23709.782 | 3.089532 | 0.00020742 | 414.596 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.298442 | 12.08816093 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 1.6394 | 1.672425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23709.78 | 23709.78 | 1.0000 | 3.62644828 | 3.089532 | 6.29 | 6.29 | 0.00613234 | 21732.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.20740236 | 60.00 | 32.22 | 27.78 | 0.000 | 23709.78 | 6.30 | 0.00607234 | 6.30 | 2.65072000 | 85.7968 | 6.25 | 0.00649473 | 22.66 | 0.00655233 | 37.4037 | 6600.09 | 0.00 | 24884.37 | 24884.37 | 3.62644828 | 2.80 | 2.80 | 0.00613234 | 18182.1 | 9.55 | 8.13 | 0.00613234 | 25044.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2438079.373 | -999.000 | 98.188931 | 0.10372153 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5650 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 98.188931 | 115.25273915 | 4197.9300 | 999.8980 | 130.82266554 | 12.27 | 6.67 | 5.60 | 3075432.60 | 79.2760 | 79.275981 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2438079.37 | 2196380.37 | 1.0000 | 115.25273915 | 98.188931 | 29.37 | 17.49 | 0.00792116 | 49757.3 | 10.90 | 9.51 | 0.00700000 | 28603.1 | 103.71095198 | 6.67 | 12.27 | 5.60 | 223045.310 | 2215034.06 | 42.00 | 0.00915790 | 22.26 | 27.60938000 | 28.1186 | 24.00 | 0.00739487 | 24.00 | 0.00739487 | 38.8744 | 1237445.94 | 0.00 | 2481823.84 | 2312056.35 | 115.25273915 | 29.37 | 17.76 | 0.00792116 | 49757.3 | 9.70 | 9.55 | 0.00733640 | 28223.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 194338.708 | 194338.708 | 29.456679 | 0.00170016 | 3420.558 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 98.188931 | 115.25273915 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 13.4377 | 13.708134 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 194338.71 | 194338.71 | 1.0000 | 34.57582175 | 29.456679 | 7.21 | 6.88 | 0.00618757 | 22799.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.69998636 | 60.00 | 32.22 | 27.78 | 0.000 | 194338.71 | 6.30 | 0.00607234 | 6.30 | 27.60938000 | 93.7288 | 20.76 | 0.00790967 | 21.00 | 0.00789198 | 49.7413 | 443033.69 | 0.00 | 206463.98 | 206463.98 | 34.57582175 | 2.80 | 2.80 | 0.00618757 | 18320.5 | 8.68 | 7.78 | 0.00618757 | 24291.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 261868.663 | -999.000 | 11.204922 | 0.01114050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3218 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.204922 | 13.15217418 | 4197.9300 | 999.8980 | 130.82266554 | 12.27 | 6.67 | 5.60 | 3075432.60 | 8.5149 | 8.514856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 261868.66 | 238379.89 | 1.0000 | 13.15217418 | 11.204922 | 28.48 | 17.08 | 0.00779031 | 48513.3 | 10.90 | 9.51 | 0.00700000 | 28602.6 | 11.13936185 | 6.67 | 12.27 | 5.60 | 25453.024 | 236415.64 | 42.00 | 0.00915790 | 22.26 | 2.78477000 | 24.8531 | 24.00 | 0.00733701 | 24.00 | 0.00733701 | 38.5738 | 149665.41 | 0.00 | 266764.53 | 251780.37 | 13.15217418 | 28.48 | 17.35 | 0.00779031 | 48513.3 | 9.70 | 9.55 | 0.00733803 | 28230.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15772.201 | 15772.201 | 3.361477 | 0.00013798 | 280.930 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.204922 | 13.15217418 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 1.0906 | 1.112529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15772.20 | 15772.20 | 1.0000 | 3.94565225 | 3.361477 | 8.82 | 7.89 | 0.00639696 | 24968.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.13796802 | 60.00 | 32.22 | 27.78 | 0.000 | 15772.20 | 6.30 | 0.00607234 | 6.30 | 2.78477000 | 82.8437 | 21.00 | 0.00796446 | 21.00 | 0.00796446 | 50.1917 | 63393.64 | 0.00 | 17127.40 | 17127.40 | 3.94565225 | 2.80 | 2.80 | 0.00639696 | 18845.3 | 7.07 | 7.07 | 0.00639696 | 23186.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 130114.031 | -999.000 | 5.952736 | 0.00553535 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4012 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.952736 | 6.98723465 | 4197.9300 | 999.8980 | 130.82266554 | 12.27 | 6.67 | 5.60 | 3075432.60 | 4.2308 | 4.230755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 130114.03 | 117292.23 | 1.0000 | 6.98723465 | 5.952736 | 27.46 | 16.77 | 0.00783301 | 47583.9 | 11.25 | 9.66 | 0.00700000 | 28962.2 | 5.53478699 | 6.67 | 12.27 | 5.60 | 11006.912 | 119107.12 | 39.77 | 0.00915417 | 21.63 | 1.20015641 | 20.1614 | 24.00 | 0.00746133 | 24.00 | 0.00746133 | 39.2193 | 79253.74 | 0.00 | 132645.81 | 125194.02 | 6.98723465 | 27.46 | 17.04 | 0.00783301 | 47583.9 | 9.88 | 9.71 | 0.00740969 | 28599.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 271929.216 | 271929.216 | 5.952736 | 0.00237896 | 6184.982 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.952736 | 6.98723465 | 4197.9300 | 999.8980 | 12.40129704 | 54.44 | 82.22 | 27.78 | 1446220.60 | 18.8027 | 19.181161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 271929.22 | 271929.22 | 1.0000 | 6.98723465 | 5.952736 | 1.27 | 1.27 | 0.00607234 | 16477.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.37871273 | 60.00 | 32.22 | 27.78 | 0.000 | 271929.22 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 20.1614 | 0.00 | 0.00607234 | 25.84 | 0.00607234 | 28.6564 | 0.00 | 0.00 | 234027.27 | 234027.27 | 6.98723465 | 12.80 | 9.56 | 0.00607234 | 28193.0 | 45.76 | 21.49 | 0.00607234 | 61686.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 452332.372 | 281689.456 | 21.961132 | 0.01107759 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9915 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 406282.65 | 402565.36 | 0.8982 | -999.0 | -999.0 | 28.66 | 16.55 | 0.00707471 | 46868.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406282.65 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704207 | 27.00 | 0.00704207 | 30.9976 | 372053.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9721.163 | 6127.592 | 0.485446 | 0.00023807 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9809 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8686.07 | 8610.78 | 0.8935 | -999.0 | -999.0 | 28.14 | 16.36 | 0.00706897 | 46329.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8686.07 | 32.36 | 0.00914193 | 19.41 | 0.01563234 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 8189.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92636.815 | 58364.816 | 4.621759 | 0.00226867 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9873 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 82787.12 | 82034.07 | 0.8937 | -999.0 | -999.0 | 28.15 | 16.37 | 0.00707245 | 46346.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82787.12 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 78020.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9570.903 | 5949.667 | 0.464878 | 0.00023439 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1523 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8596.78 | 8427.21 | 0.8982 | -999.0 | -999.0 | 28.45 | 16.55 | 0.00716117 | 46877.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8596.78 | 41.29 | 0.00915671 | 22.06 | 0.01563234 | -999.0000 | 27.00 | 0.00709170 | 27.00 | 0.00709170 | 31.2118 | 7882.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 452332.372 | 452332.372 | 21.961132 | 0.01107759 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 452332.37 | 452332.37 | 1.0000 | 25.77765794 | 21.961132 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 452332.37 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5409 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9721.163 | 9721.163 | 0.485446 | 0.00023807 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9721.16 | 9721.16 | 1.0000 | 0.56980914 | 0.485446 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9721.16 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2202 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92636.815 | 92636.815 | 4.621759 | 0.00226867 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92636.81 | 92636.81 | 1.0000 | 5.42495355 | 4.621759 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92636.81 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3823 | 0.00 | 0.00698274 | 25.17 | 0.00698274 | 34.2433 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9570.903 | 9570.903 | 0.464878 | 0.00023439 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9570.90 | 9570.90 | 1.0000 | 0.54566752 | 0.464878 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9570.90 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3627 | 0.00 | 0.00619814 | 24.11 | 0.00619814 | 32.4220 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.961132 | 25.77765794 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 25.77765794 | 21.961132 | 0.10 | 0.10 | 0.00698571 | 17569.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5409 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.485446 | 0.56980914 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.56980914 | 0.485446 | 0.20 | 0.20 | 0.00697013 | 17638.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2202 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.621759 | 5.42495355 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.42495355 | 4.621759 | 0.21 | 0.21 | 0.00695195 | 17603.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3823 | 0.00 | 0.00698274 | 25.17 | 0.00698274 | 34.2433 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.464878 | 0.54566752 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.54566752 | 0.464878 | 0.21 | 0.21 | 0.00619391 | 15705.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3627 | 0.00 | 0.00619814 | 24.11 | 0.00619814 | 32.4220 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5405.33 | 1528.50 | 1528.50 |
CORE_BOTTOM | 5293.67 | 18.67 | 13.00 |
CORE_MID | 4676.67 | 229.00 | 23.00 |
CORE_TOP | 4243.17 | 956.50 | 26.83 |
PERIMETER_BOT_ZN_3 | 4436.83 | 932.50 | 125.00 |
PERIMETER_BOT_ZN_2 | 4535.17 | 968.17 | 181.17 |
PERIMETER_BOT_ZN_1 | 5141.67 | 654.67 | 277.00 |
PERIMETER_BOT_ZN_4 | 5379.00 | 731.33 | 478.83 |
PERIMETER_MID_ZN_3 | 3805.17 | 1907.67 | 292.83 |
PERIMETER_MID_ZN_2 | 3426.67 | 1546.17 | 376.17 |
PERIMETER_MID_ZN_1 | 4909.17 | 1019.83 | 429.00 |
PERIMETER_MID_ZN_4 | 4236.17 | 1640.00 | 376.17 |
PERIMETER_TOP_ZN_3 | 3760.17 | 2330.50 | 485.83 |
PERIMETER_TOP_ZN_2 | 4045.00 | 2030.00 | 486.67 |
PERIMETER_TOP_ZN_1 | 4622.50 | 1418.17 | 479.17 |
PERIMETER_TOP_ZN_4 | 4042.83 | 2008.67 | 467.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1571.00 | 1571.00 |
DATACENTER_MID_ZN_6 | 5943.00 | 512.67 | 512.67 |
DATACENTER_TOP_ZN_6 | 5909.00 | 731.50 | 719.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 100.67 | 0.00 | 9.50 |
CORE_BOTTOM | 0.00 | 11.00 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.33 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 1.50 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 36.00 | 0.00 | 16.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 35.83 | 0.00 | 27.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 85.17 | 0.00 | 60.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 232.00 | 0.00 | 76.83 |
PERIMETER_MID_ZN_3 | 0.00 | 23.50 | 0.00 | 10.00 |
PERIMETER_MID_ZN_2 | 0.00 | 43.00 | 0.00 | 32.00 |
PERIMETER_MID_ZN_1 | 0.00 | 71.17 | 0.00 | 52.67 |
PERIMETER_MID_ZN_4 | 0.00 | 69.17 | 0.00 | 30.67 |
PERIMETER_TOP_ZN_3 | 0.33 | 52.83 | 0.00 | 25.00 |
PERIMETER_TOP_ZN_2 | 0.33 | 73.17 | 0.00 | 45.17 |
PERIMETER_TOP_ZN_1 | 0.33 | 86.83 | 0.00 | 53.50 |
PERIMETER_TOP_ZN_4 | 0.33 | 88.17 | 0.00 | 36.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 616.17 | 0.00 | 495.00 |
DATACENTER_MID_ZN_6 | 0.00 | 520.50 | 0.00 | 448.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 361.83 | 0.00 | 318.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1283.00 | 0.00 | 919.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.33 | 1652.33 | 0.00 | 1075.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.64 | 149.60 | 6779.02 | 0.536 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.26 | 134.35 | 6849.35 | 0.752 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.26 | 134.35 | 6849.35 | 0.731 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.26 | 134.35 | 6849.35 | 0.716 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.06 | 16.87 | 860.00 | 1.022 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.55 | 10.87 | 554.22 | 1.187 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.06 | 16.87 | 860.02 | 1.258 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.55 | 10.87 | 554.22 | 1.722 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.06 | 16.87 | 860.00 | 1.101 | 0.071 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.98 | 10.87 | 554.22 | 1.354 | 0.075 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.06 | 16.87 | 860.02 | 1.402 | 0.071 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.55 | 10.87 | 554.22 | 1.499 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.06 | 16.87 | 860.00 | 1.178 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.55 | 10.87 | 554.22 | 1.448 | 0.091 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.06 | 16.87 | 860.02 | 1.433 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.55 | 10.87 | 554.22 | 1.560 | 0.091 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.66 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.64 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.26 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.98 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.06 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.06 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.55 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.66 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.64 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.26 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.98 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.06 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.06 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.55 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.82 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.66 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1038.25 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24103313.91 | 0.00 | 24103313.91 | 0.00 | 24103313.91 | 37848132.68 | 3181.26 | 5578.74 | 0.00 | 758.73 |
CORE_BOTTOM | 36648876.57 | 0.00 | 36648876.57 | 0.00 | 36648876.57 | 33990283.35 | 2230.79 | 3.71 | 6525.49 | 1290.12 |
CORE_MID | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 0.34E+09 | 2973.61 | 11.81 | 5774.58 | 751.85 |
CORE_TOP | 32178966.01 | 0.00 | 32178966.01 | 0.00 | 32178966.01 | 33990283.35 | 2977.41 | 2.18 | 5780.41 | 739.36 |
PERIMETER_BOT_ZN_3 | 6415587.94 | 0.00 | 6415587.94 | 243873.99 | 6659461.93 | 4267819.30 | 2230.68 | 1.63 | 6527.69 | 1290.12 |
PERIMETER_BOT_ZN_2 | 4835532.04 | 0.00 | 4835532.04 | 162582.55 | 4998114.59 | 2750345.05 | 2219.98 | 0.62 | 6539.40 | 1290.12 |
PERIMETER_BOT_ZN_1 | 7615851.01 | 0.00 | 7615851.01 | 243873.99 | 7859725.00 | 4267912.63 | 2228.06 | 0.54 | 6531.40 | 1290.12 |
PERIMETER_BOT_ZN_4 | 6921844.39 | 0.00 | 6921844.39 | 162582.55 | 7084426.94 | 2750345.05 | 2216.94 | 0.00 | 6543.06 | 1290.12 |
PERIMETER_MID_ZN_3 | 63057590.62 | 0.00 | 63057590.62 | 571938.60 | 63629529.22 | 42678193.03 | 2945.26 | 0.75 | 5813.99 | 751.85 |
PERIMETER_MID_ZN_2 | 51422839.77 | 0.00 | 51422839.77 | 381292.14 | 51804131.91 | 27503450.52 | 2943.13 | 0.00 | 5816.87 | 1660.85 |
PERIMETER_MID_ZN_1 | 78097592.32 | 0.00 | 78097592.32 | 571938.60 | 78669530.92 | 42679126.28 | 2943.13 | 0.03 | 5816.83 | 751.85 |
PERIMETER_MID_ZN_4 | 55489540.20 | 0.00 | 55489540.20 | 381292.14 | 55870832.34 | 27503450.52 | 2943.13 | 0.00 | 5816.87 | 751.85 |
PERIMETER_TOP_ZN_3 | 6774329.83 | 0.00 | 6774329.83 | 710105.05 | 7484434.88 | 4267819.30 | 2964.22 | 0.13 | 5795.64 | 739.36 |
PERIMETER_TOP_ZN_2 | 5322247.31 | 0.00 | 5322247.31 | 473403.04 | 5795650.35 | 2750345.05 | 2964.09 | 0.00 | 5795.91 | 739.36 |
PERIMETER_TOP_ZN_1 | 8041624.27 | 0.00 | 8041624.27 | 710105.05 | 8751729.32 | 4267912.63 | 2964.09 | 0.00 | 5795.91 | 739.36 |
PERIMETER_TOP_ZN_4 | 5787821.63 | 0.00 | 5787821.63 | 473403.04 | 6261224.67 | 2750345.05 | 2964.09 | 0.00 | 5795.91 | 739.36 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.60E+10 | 0.00 | 0.60E+10 | 22244544.20 | 0.60E+10 | 0.50E+10 | 3912.71 | 8760.00 | 6957.21 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9734 | 0.0000 | 0.9734 | 0.0000 | 0.9734 | 1.2002 | 1122.98 | 4820.02 | 0.00 |
CORE_BOTTOM | 1.3841 | 0.0000 | 1.3841 | 0.0000 | 1.3841 | 1.0778 | 700.48 | 3.27 | 5239.25 |
CORE_MID | 13.4474 | 0.0000 | 13.4474 | 0.0000 | 13.4474 | 10.7782 | 904.34 | 11.43 | 5027.24 |
CORE_TOP | 1.3176 | 0.0000 | 1.3176 | 0.0000 | 1.3176 | 1.0778 | 895.51 | 1.39 | 5046.10 |
PERIMETER_BOT_ZN_3 | 0.2358 | 0.0000 | 0.2358 | 0.0070 | 0.2427 | 0.1353 | 697.69 | 1.23 | 5244.08 |
PERIMETER_BOT_ZN_2 | 0.1765 | 0.0000 | 0.1765 | 0.0046 | 0.1812 | 0.0872 | 692.33 | 0.28 | 5250.39 |
PERIMETER_BOT_ZN_1 | 0.2906 | 0.0000 | 0.2906 | 0.0070 | 0.2975 | 0.1353 | 695.95 | 0.33 | 5246.72 |
PERIMETER_BOT_ZN_4 | 0.2559 | 0.0000 | 0.2559 | 0.0046 | 0.2606 | 0.0872 | 690.06 | 0.00 | 5252.94 |
PERIMETER_MID_ZN_3 | 2.5415 | 0.0000 | 2.5415 | 0.0163 | 2.5579 | 1.3533 | 878.67 | 0.51 | 5063.82 |
PERIMETER_MID_ZN_2 | 2.0159 | 0.0000 | 2.0159 | 0.0112 | 2.0271 | 0.8721 | 877.98 | 0.00 | 4156.02 |
PERIMETER_MID_ZN_1 | 3.2380 | 0.0000 | 3.2380 | 0.0163 | 3.2543 | 1.3533 | 877.98 | 0.00 | 5065.02 |
PERIMETER_MID_ZN_4 | 2.2303 | 0.0000 | 2.2303 | 0.0109 | 2.2412 | 0.8721 | 877.98 | 0.00 | 5065.02 |
PERIMETER_TOP_ZN_3 | 0.2724 | 0.0000 | 0.2724 | 0.0203 | 0.2927 | 0.1353 | 886.48 | 0.00 | 5056.52 |
PERIMETER_TOP_ZN_2 | 0.2157 | 0.0000 | 0.2157 | 0.0135 | 0.2292 | 0.0872 | 886.45 | 0.00 | 5056.55 |
PERIMETER_TOP_ZN_1 | 0.3312 | 0.0000 | 0.3312 | 0.0203 | 0.3515 | 0.1353 | 886.45 | 0.00 | 5056.55 |
PERIMETER_TOP_ZN_4 | 0.2325 | 0.0000 | 0.2325 | 0.0135 | 0.2460 | 0.0872 | 886.45 | 0.00 | 5056.55 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 242.3499 | 0.0000 | 242.3499 | 0.6381 | 242.9880 | 158.4706 | 1278.69 | 5943.00 | 5396.54 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 86024965.44 | 0.00 | 86024965.44 | 48026705.38 | 2216.94 | 0.00 | 6543.06 | 1290.12 |
VAV_MID WITH REHEAT | 0.80E+09 | 0.00 | 0.80E+09 | 0.48E+09 | 2943.13 | 0.00 | 5816.87 | 751.85 |
VAV_TOP WITH REHEAT | 80055451.41 | 0.00 | 80055451.41 | 48026705.38 | 2964.09 | 0.00 | 5795.91 | 739.36 |
CAV_BAS | 33208878.41 | 0.00 | 33208878.41 | 37848132.68 | 3181.26 | 0.00 | 5578.74 | 758.73 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2280 | 0.0000 | 3.2280 | 1.5229 | 690.06 | 0.00 | 5252.94 |
VAV_MID WITH REHEAT | 32.4197 | 0.0000 | 32.4197 | 15.2292 | 877.98 | 0.00 | 5065.02 |
VAV_TOP WITH REHEAT | 3.2645 | 0.0000 | 3.2645 | 1.5229 | 886.45 | 0.00 | 5056.55 |
CAV_BAS | 1.3411 | 0.0000 | 1.3411 | 1.2002 | 1122.98 | 0.00 | 4820.02 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 6543.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 5816.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 5795.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5578.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 3.6527 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 38.0396 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 3.8372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6535 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1335 |
Defaulted Fields | 1179 |
Fields with Defaults | 3690 |
Autosized Fields | 333 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
Electricity:Building | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
Electricity:Zone:BASEMENT | 660.02 | 14600.60 | 01-JAN-00:10 | 34031.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 19155.85 | 253334.51 | 01-JAN-00:10 | 1138237.68 | 03-APR-07:10 |
InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 235.63 | 1143.06 | 01-JAN-00:10 | 20573.73 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3942.44 | 19125.25 | 01-JAN-00:10 | 344233.60 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 532.90 | 7069.41 | 01-JAN-00:10 | 36605.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5328.94 | 70693.84 | 01-JAN-00:10 | 366051.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2116.10 | 10265.44 | 01-JAN-00:10 | 184766.59 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 532.89 | 7069.38 | 01-JAN-00:10 | 36605.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 211.61 | 1026.54 | 01-JAN-00:10 | 18476.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 669.12 | 8876.66 | 01-JAN-00:10 | 45962.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 265.70 | 1288.93 | 01-JAN-00:10 | 23199.29 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 431.21 | 5720.45 | 01-JAN-00:10 | 29619.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 669.13 | 8876.80 | 01-JAN-00:10 | 45963.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 265.70 | 1288.96 | 01-JAN-00:10 | 23199.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 431.20 | 5720.42 | 01-JAN-00:10 | 29619.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 171.23 | 830.63 | 01-JAN-00:10 | 14950.50 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 66.91 | 887.67 | 01-JAN-00:10 | 4596.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.57 | 128.89 | 01-JAN-00:10 | 2319.93 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 43.12 | 572.05 | 01-JAN-00:10 | 2962.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 66.91 | 887.68 | 01-JAN-00:10 | 4596.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.57 | 128.90 | 01-JAN-00:10 | 2319.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 43.12 | 572.04 | 01-JAN-00:10 | 2961.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 17.12 | 83.06 | 01-JAN-00:10 | 1495.05 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7561.29 | 95230.42 | 01-JAN-00:10 | 385433.43 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 66.44 | 322.29 | 01-JAN-00:10 | 5800.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1582.51 | 19698.04 | 01-JAN-00:10 | 81759.99 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 43.70 | 211.99 | 01-JAN-00:10 | 3815.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.25 | 1969.80 | 01-JAN-00:10 | 8176.00 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.37 | 21.20 | 01-JAN-00:10 | 381.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 7836.34 | 8257.07 | 05-JAN-05:50 | 698720.91 | 28-AUG-10:40 |
HeatRejection:Electricity | 2085.38 | 4597.09 | 05-JAN-07:00 | 96599.43 | 07-MAR-11:40 |
General:HeatRejection:Electricity | 2085.38 | 4597.09 | 05-JAN-07:00 | 96599.43 | 07-MAR-11:40 |
Electricity:HVAC | 6488.38 | 82383.36 | 16-JAN-04:50 | 528969.80 | 28-AUG-16:00 |
ExteriorEquipment:Electricity | 1997.59 | 30702.09 | 01-JAN-00:10 | 120520.01 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.51 | 1613.62 | 01-JAN-00:10 | 5474.05 | 03-APR-07:20 |
ElectricityPurchased:Facility | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
ElectricityPurchased:Plant | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
Cogeneration:ElectricityPurchased | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
ElectricityNet:Plant | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
Cogeneration:ElectricityNet | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
General:Cogeneration:ElectricityNet | 36295.94 | 384393.90 | 01-JAN-10:20 | 2388568.39 | 28-AUG-16:00 |
Fans:Electricity | 2890.62 | 42460.67 | 02-JAN-22:10 | 325251.03 | 23-JUN-15:30 |
General:Fans:Electricity | 2890.62 | 42460.67 | 02-JAN-22:10 | 325251.03 | 23-JUN-15:30 |
ExteriorLights:Electricity | 905.27 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 905.27 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 61.31 | 1944.00 | 01-JAN-00:10 | 1944.00 | 01-JAN-00:10 |
Cooling:Electricity | 7512.22 | 33785.90 | 08-JAN-07:00 | 710536.77 | 24-AUG-14:30 |
General:Cooling:Electricity | 7512.22 | 33785.90 | 08-JAN-07:00 | 710536.77 | 24-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 82.38 | 0.00 | 12-JAN-13:10 | 28597.77 | 22-DEC-06:00 |
General:Humidifier:Electricity | 82.38 | 0.00 | 12-JAN-13:10 | 28597.77 | 22-DEC-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1666.62 | 3524.47 | 01-JAN-00:10 | 96618.41 | 25-AUG-13:10 |
General:Pumps:Electricity | 1666.62 | 3524.47 | 01-JAN-00:10 | 96618.41 | 25-AUG-13:10 |
WIRED_LTG_ELECTRICITY | 110.78 | 0.00 | 01-JAN-00:10 | 9672.96 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 794.89 | 8146.58 | 16-APR-15:00 | 518523.54 | 02-JAN-06:20 |
NaturalGas:Plant | 794.89 | 8146.58 | 16-APR-15:00 | 518523.54 | 02-JAN-06:20 |
Heating:NaturalGas | 158.47 | 0.00 | 01-JAN-00:10 | 489599.99 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 158.47 | 0.00 | 01-JAN-00:10 | 489599.99 | 02-JAN-06:20 |
WaterSystems:NaturalGas | 636.42 | 8146.58 | 16-APR-15:00 | 75302.06 | 20-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 636.42 | 8146.58 | 16-APR-15:00 | 75302.06 | 20-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 40435.64 | 166278.83 | 22-JAN-07:00 | 3903371.28 | 28-AUG-13:00 |
PlantLoopCoolingDemand:HVAC | 40435.64 | 166278.83 | 22-JAN-07:00 | 3903371.28 | 28-AUG-13:00 |
CoolingCoils:PlantLoopCoolingDemand | 40435.64 | 166278.83 | 22-JAN-07:00 | 3903371.28 | 28-AUG-13:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 24759.67 | 0.00 | 11-MAR-00:20 | 0.00 | 03-MAY-15:10 |
Water:HVAC | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:Water | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:Water | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
MainsWater:Facility | 24759.67 | 0.00 | 11-MAR-00:20 | 0.00 | 03-MAY-15:10 |
MainsWater:HVAC | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:MainsWater | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:MainsWater | 30.65 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Water:Plant | 24729.03 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 24729.03 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 22448.86 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:00 |
General:HeatRejection:Water | 22448.86 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:00 |
HeatRejection:MainsWater | 22448.86 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:00 |
General:HeatRejection:MainsWater | 22448.86 | 0.00 | 01-JAN-00:10 | 0.00 | 03-MAY-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 144736.71 | 230533.57 | 22-JAN-06:00 | 15193125.44 | 28-AUG-12:20 |
EnergyTransfer:Building | 24001.66 | 97711.95 | 08-JAN-08:00 | 1738079.12 | 27-APR-15:30 |
EnergyTransfer:Zone:BASEMENT | 802.53 | 0.00 | 01-JAN-00:10 | 75984.91 | 13-NOV-06:20 |
Heating:EnergyTransfer | 18.10 | 0.00 | 02-JAN-12:20 | 94108.87 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.96 | 0.00 | 01-JAN-00:10 | 34321.10 | 10-JUN-16:10 |
General:Heating:EnergyTransfer | 18.10 | 0.00 | 02-JAN-12:20 | 94108.87 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.96 | 0.00 | 01-JAN-00:10 | 34321.10 | 10-JUN-16:10 |
Cooling:EnergyTransfer | 23983.56 | 97558.21 | 08-JAN-08:00 | 1738079.12 | 27-APR-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 797.57 | 0.00 | 01-JAN-00:10 | 75984.91 | 13-NOV-06:20 |
General:Cooling:EnergyTransfer | 23983.56 | 97558.21 | 08-JAN-08:00 | 1738079.12 | 27-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 797.57 | 0.00 | 01-JAN-00:10 | 75984.91 | 13-NOV-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 797.45 | 0.00 | 01-JAN-00:10 | 60928.66 | 07-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 797.45 | 0.00 | 01-JAN-00:10 | 60928.66 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 797.45 | 0.00 | 01-JAN-00:10 | 60928.66 | 07-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 6105.99 | 0.00 | 01-JAN-00:10 | 495821.59 | 05-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6105.99 | 0.00 | 01-JAN-00:10 | 495821.59 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6105.99 | 0.00 | 01-JAN-00:10 | 495821.59 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_TOP | 621.91 | 0.00 | 01-JAN-00:10 | 59707.47 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.23 | 0.00 | 01-JAN-00:10 | 40547.82 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.23 | 0.00 | 01-JAN-00:10 | 40547.82 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 621.67 | 0.00 | 01-JAN-00:10 | 59707.47 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 621.67 | 0.00 | 01-JAN-00:10 | 59707.47 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 137.29 | 0.00 | 01-JAN-00:10 | 13589.43 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 137.29 | 0.00 | 01-JAN-00:10 | 13589.43 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 137.29 | 0.00 | 01-JAN-00:10 | 13589.43 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 102.08 | 0.00 | 01-JAN-00:10 | 12739.76 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 102.08 | 0.00 | 01-JAN-00:10 | 12739.76 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 102.08 | 0.00 | 01-JAN-00:10 | 12739.76 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 169.90 | 0.00 | 01-JAN-00:10 | 17363.94 | 02-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 169.90 | 0.00 | 01-JAN-00:10 | 17363.94 | 02-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 169.90 | 0.00 | 01-JAN-00:10 | 17363.94 | 02-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 150.74 | 0.00 | 01-JAN-00:10 | 16910.88 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 150.74 | 0.00 | 01-JAN-00:10 | 16910.88 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 150.74 | 0.00 | 01-JAN-00:10 | 16910.88 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1134.37 | 0.00 | 01-JAN-00:10 | 131144.61 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2826.88 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 2826.88 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1134.37 | 0.00 | 01-JAN-00:10 | 131144.61 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1134.37 | 0.00 | 01-JAN-00:10 | 131144.61 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 930.95 | 0.00 | 01-JAN-00:10 | 127473.94 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 2252.52 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 2252.52 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 930.95 | 0.00 | 01-JAN-00:10 | 127473.94 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 930.95 | 0.00 | 01-JAN-00:10 | 127473.94 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1491.37 | 0.00 | 01-JAN-00:10 | 171760.10 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1491.37 | 0.00 | 01-JAN-00:10 | 171760.10 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1491.37 | 0.00 | 01-JAN-00:10 | 171760.10 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1001.52 | 0.00 | 01-JAN-00:10 | 142633.49 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 686.53 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 686.53 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1001.52 | 0.00 | 01-JAN-00:10 | 142633.49 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1001.52 | 0.00 | 01-JAN-00:10 | 142633.49 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 122.58 | 0.00 | 01-JAN-00:10 | 15188.82 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.74 | 0.00 | 01-JAN-00:10 | 11376.94 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.74 | 0.00 | 01-JAN-00:10 | 11376.94 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.85 | 0.00 | 01-JAN-00:10 | 15188.82 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.85 | 0.00 | 01-JAN-00:10 | 15188.82 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.42 | 0.00 | 01-JAN-00:10 | 14023.81 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.28 | 0.00 | 01-JAN-00:10 | 7100.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.28 | 0.00 | 01-JAN-00:10 | 7100.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.13 | 0.00 | 01-JAN-00:10 | 14023.81 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 99.13 | 0.00 | 01-JAN-00:10 | 14023.81 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 156.24 | 0.00 | 01-JAN-00:10 | 19427.72 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.17 | 0.00 | 01-JAN-00:10 | 8582.83 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.17 | 0.00 | 01-JAN-00:10 | 8582.83 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 156.06 | 0.00 | 01-JAN-00:10 | 19427.72 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 156.06 | 0.00 | 01-JAN-00:10 | 19427.72 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 106.11 | 0.00 | 01-JAN-00:10 | 15685.72 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.17 | 0.00 | 01-JAN-00:10 | 5374.78 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.17 | 0.00 | 01-JAN-00:10 | 5374.78 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 105.95 | 0.00 | 01-JAN-00:10 | 15685.72 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 105.95 | 0.00 | 01-JAN-00:10 | 15685.72 | 06-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 126.19 | 0.00 | 01-JAN-00:10 | 14693.36 | 03-JUL-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.78 | 0.00 | 01-JAN-00:10 | 3120.02 | 24-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.78 | 0.00 | 01-JAN-00:10 | 3120.02 | 24-DEC-11:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 125.40 | 0.00 | 01-JAN-00:10 | 14693.36 | 03-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 125.40 | 0.00 | 01-JAN-00:10 | 14693.36 | 03-JUL-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 983.64 | 0.00 | 01-JAN-00:10 | 108491.83 | 30-MAY-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.29 | 0.00 | 01-JAN-00:10 | 22908.36 | 29-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.29 | 0.00 | 01-JAN-00:10 | 22908.36 | 29-DEC-05:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 978.35 | 0.00 | 01-JAN-00:10 | 108491.83 | 30-MAY-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 978.35 | 0.00 | 01-JAN-00:10 | 108491.83 | 30-MAY-14:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 171.13 | 0.00 | 01-JAN-00:10 | 32399.98 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.40 | 0.00 | 01-JAN-00:10 | 15098.86 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.40 | 0.00 | 01-JAN-00:10 | 15098.86 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 165.72 | 0.00 | 01-JAN-00:10 | 32399.98 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 165.72 | 0.00 | 01-JAN-00:10 | 32399.98 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.11 | 1131.75 | 07-JAN-08:00 | 7729.23 | 17-APR-00:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.11 | 1131.75 | 07-JAN-08:00 | 7729.23 | 17-APR-00:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.11 | 1131.75 | 07-JAN-08:00 | 7729.23 | 17-APR-00:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1327.76 | 6417.23 | 01-JAN-07:50 | 72769.08 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1327.76 | 6417.23 | 01-JAN-07:50 | 72769.08 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1327.76 | 6417.23 | 01-JAN-07:50 | 72769.08 | 12-APR-16:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.92 | 0.58 | 21-JAN-08:00 | 7467.27 | 16-APR-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.06 | 0.00 | 02-JAN-11:10 | 328.49 | 01-JAN-14:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.06 | 0.00 | 02-JAN-11:10 | 328.49 | 01-JAN-14:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.86 | 0.00 | 01-JAN-00:10 | 7467.27 | 16-APR-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.86 | 0.00 | 01-JAN-00:10 | 7467.27 | 16-APR-21:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.46 | 88609.78 | 14-MAY-01:50 | 369982.97 | 15-AUG-23:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.46 | 88609.78 | 14-MAY-01:50 | 369982.97 | 15-AUG-23:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.46 | 88609.78 | 14-MAY-01:50 | 369982.97 | 15-AUG-23:50 |
PlantLoopHeatingDemand:Facility | 406.88 | 0.00 | 01-JAN-00:10 | 385435.23 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 293.17 | 0.00 | 01-JAN-00:10 | 40155.02 | 18-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40155.02 | 18-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40155.02 | 18-JAN-12:20 |
EnergyTransfer:HVAC | 37121.48 | 132489.87 | 22-JAN-07:00 | 3708299.60 | 28-AUG-13:00 |
HeatingCoils:EnergyTransfer | 113.71 | 0.00 | 01-JAN-00:10 | 380546.21 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 113.71 | 0.00 | 01-JAN-00:10 | 380546.21 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 113.71 | 0.00 | 01-JAN-00:10 | 380546.21 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 37007.77 | 132489.87 | 22-JAN-07:00 | 3708299.60 | 28-AUG-13:00 |
EnergyTransfer:Plant | 83613.57 | 0.00 | 01-JAN-00:10 | 9900429.34 | 28-AUG-12:10 |
LoopToLoop:EnergyTransfer | 27268.11 | 0.00 | 01-JAN-00:10 | 3187661.17 | 25-AUG-12:40 |
WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40155.02 | 18-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40155.02 | 18-JAN-12:20 |
Boilers:EnergyTransfer | 112.43 | 0.00 | 01-JAN-00:10 | 384602.42 | 02-JAN-06:20 |
Chillers:EnergyTransfer | 25927.76 | 0.00 | 01-JAN-00:10 | 3112612.77 | 21-JUN-14:40 |
HeatRejection:EnergyTransfer | 30012.11 | 0.00 | 01-JAN-00:10 | 3621361.58 | 28-AUG-10:40 |
General:HeatRejection:EnergyTransfer | 30012.11 | 0.00 | 01-JAN-00:10 | 3621361.58 | 28-AUG-10:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.962 | -797.564 | 0.000 | 0.000 | 92.648 | 235.627 | 424.397 | 0.000 | 0.000 | 0.000 | 39.929 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -797.447 | 0.000 | 0.000 | 83.399 | 211.610 | 321.286 | 0.000 | 0.000 | 0.000 | 181.153 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6105.968 | 0.000 | 0.000 | 834.929 | 2116.097 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -57.903 |
CORE_TOP | 0.000 | 0.000 | 0.234 | -621.669 | 0.000 | 0.000 | 84.032 | 211.610 | 321.285 | 0.000 | 0.000 | 0.000 | 4.509 | 0.000 | 0.000 | 0.000 | 0.000 | -0.006 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -137.287 | 0.000 | 0.000 | 10.531 | 26.570 | 40.342 | 42.542 | 0.000 | 1.171 | 37.791 | 0.000 | -21.021 | 0.000 | -0.639 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -102.078 | 0.000 | 0.000 | 6.784 | 17.123 | 25.998 | 50.560 | 0.000 | 0.797 | 13.964 | 0.000 | -12.727 | 0.000 | -0.421 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -169.899 | 0.000 | 0.000 | 10.490 | 26.570 | 40.343 | 90.470 | 0.000 | 1.145 | 21.996 | 0.000 | -20.422 | 0.000 | -0.693 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -150.741 | 0.000 | 0.000 | 6.757 | 17.123 | 25.998 | 49.092 | 0.000 | 0.732 | 67.578 | 0.000 | -16.036 | 0.000 | -0.504 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.005 | -1134.354 | 0.000 | 0.000 | 106.817 | 265.697 | 403.423 | 435.245 | 0.000 | 26.413 | 103.870 | 0.000 | -193.785 | 0.000 | -13.331 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.003 | -930.935 | 0.000 | 0.000 | 50.308 | 171.225 | 259.981 | 504.809 | 0.000 | 17.378 | 60.417 | 0.000 | -123.765 | 0.000 | -9.422 | -0.010 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1491.348 | 0.000 | 0.000 | 105.127 | 265.703 | 403.429 | 905.088 | 0.000 | 25.547 | 5.297 | 0.000 | -202.690 | 0.000 | -16.152 | -0.009 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.001 | -1001.508 | 0.000 | 0.000 | 68.711 | 171.225 | 259.979 | 506.828 | 0.000 | 17.057 | 124.928 | 0.000 | -137.420 | 0.000 | -9.802 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.736 | -121.845 | 0.000 | 0.000 | 10.864 | 26.570 | 40.342 | 43.459 | 0.000 | 3.236 | 15.848 | 0.000 | -17.761 | 0.000 | -1.449 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.282 | -99.132 | 0.000 | 0.000 | 6.914 | 17.123 | 25.998 | 50.378 | 0.000 | 2.106 | 8.991 | 0.000 | -11.600 | 0.000 | -1.060 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.174 | -156.061 | 0.000 | 0.000 | 10.603 | 26.570 | 40.343 | 90.271 | 0.000 | 3.118 | 5.932 | 0.000 | -19.100 | 0.000 | -1.850 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.165 | -105.945 | 0.000 | 0.000 | 6.963 | 17.123 | 25.998 | 50.553 | 0.000 | 2.099 | 17.055 | 0.000 | -12.895 | 0.000 | -1.115 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.109 | 0.000 | 0.000 | 0.936 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.078 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1327.765 | 0.000 | 0.000 | 9.380 | 43.701 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -264.123 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.063 | -129.861 | 0.000 | 0.000 | 0.942 | 4.370 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.394 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7189.471 | 0.000 | 0.000 | 19.442 | 66.437 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -391.264 |
GROUNDFLOOR_PLENUM | 0.785 | -125.402 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.114 | 123.953 | 0.000 | 0.000 | 0.000 | -1.451 | -0.000 |
MIDFLOOR_PLENUM | 5.292 | -978.345 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37.943 | 959.884 | 0.000 | 0.000 | 0.000 | -24.774 | -0.000 |
TOPFLOOR_PLENUM | 5.401 | -165.721 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.920 | 158.867 | 0.000 | 0.000 | 0.000 | -2.467 | -0.003 |
Total Facility | 11.478 | -1269.468 | 6.627 | -22713.986 | 0.000 | 0.000 | 1526.576 | 3942.443 | 15213.411 | 2819.295 | 0.000 | 144.777 | 1951.969 | 0.000 | -789.223 | 0.000 | -85.130 | -758.800 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-APR-03:02 | 0.00 | 0.00 | 0.00 | -110103.89 | 0.00 | 0.00 | 0.00 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 95503.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -99904.85 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.15 | 0.00 | 0.00 | 0.00 | 90821.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-MAR-03:02 | 0.00 | 0.00 | 0.00 | -884544.96 | 0.00 | 0.00 | 0.00 | 10265.44 | 80571.20 | 0.00 | 0.00 | 0.00 | 793708.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 13-MAR-03:02 | 0.00 | 0.00 | 0.00 | -91073.77 | 0.00 | 0.00 | 0.00 | 1026.54 | 8057.12 | 0.00 | 0.00 | 0.00 | 81990.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-17:01 | 0.00 | 0.00 | 0.00 | -21820.23 | 0.00 | 0.00 | 0.00 | 128.89 | 758.77 | 5125.57 | 0.00 | 295.02 | 15511.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-07:52 | 0.00 | 0.00 | 0.00 | -17453.78 | 0.00 | 0.00 | 22.81 | 83.06 | 488.98 | 10874.14 | 0.00 | 278.35 | 5706.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:31 | 0.00 | 0.00 | 0.00 | -23473.57 | 0.00 | 0.00 | 34.40 | 128.90 | 758.78 | 11548.97 | 0.00 | 120.42 | 10882.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -24727.84 | 0.00 | 0.00 | 17.94 | 83.06 | 488.98 | 10408.97 | 0.00 | 174.71 | 13554.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 28-MAY-16:01 | 0.00 | 0.00 | 0.00 | -222384.76 | 0.00 | 0.00 | 373.87 | 1288.93 | 7587.73 | 51347.85 | 0.00 | 21303.13 | 140483.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-09:01 | 0.00 | 0.00 | 0.00 | -191190.02 | 0.00 | 0.00 | 202.37 | 830.63 | 4889.82 | 109930.49 | 0.00 | 8858.78 | 66477.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-14:31 | 0.00 | 0.00 | 0.00 | -235670.97 | 0.00 | 0.00 | 332.25 | 1288.96 | 7587.84 | 114698.74 | 0.00 | 2686.64 | 109076.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-16:01 | 0.00 | 0.00 | 0.00 | -218531.61 | 0.00 | 0.00 | 170.96 | 830.63 | 4889.79 | 124291.98 | 0.00 | 12309.40 | 76038.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-MAY-16:21 | 0.00 | 0.00 | 0.00 | -25122.37 | 0.00 | 0.00 | 33.67 | 128.89 | 758.77 | 5066.17 | 0.00 | 2639.05 | 16495.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:52 | 0.00 | 0.00 | 0.00 | -19724.83 | 0.00 | 0.00 | 21.66 | 83.06 | 488.98 | 7848.19 | 0.00 | 672.24 | 10610.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-12:52 | 0.00 | 0.00 | 0.00 | -27149.69 | 0.00 | 0.00 | 33.50 | 128.90 | 758.78 | 13928.57 | 0.00 | 63.38 | 12236.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-APR-16:01 | 0.00 | 0.00 | 0.00 | -23165.24 | 0.00 | 0.00 | 19.88 | 83.06 | 488.98 | 9572.33 | 0.00 | 522.80 | 12478.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 17-APR-00:12 | 0.00 | 0.00 | 0.00 | -7730.42 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -85.20 |
DATACENTER_MID_ZN_6 | 12-APR-16:00 | 0.00 | 0.00 | 0.00 | -72764.37 | 0.00 | 0.00 | 985.36 | 3815.77 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9980.98 |
DATACENTER_TOP_ZN_6 | 16-APR-21:32 | 0.00 | 0.00 | 0.00 | -7474.98 | 0.00 | 0.00 | 0.00 | 21.20 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -340.64 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-23:42 | 0.00 | 0.00 | 0.00 | -370167.76 | 0.00 | 0.00 | 0.00 | 322.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9787.05 |
GROUNDFLOOR_PLENUM | 03-JUL-05:13 | 0.00 | -19016.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 18881.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-05:03 | 0.00 | -138831.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.27 | 137139.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -32400.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.13 | 31736.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -89165.63 | 0.00 | -2163928.83 | 0.00 | 0.00 | 15544.31 | 38246.31 | 623236.89 | 11322.67 | 0.00 | 2210.30 | 1562614.82 | 0.00 | -80.83 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-JUN-16:01 | 0.00 | 0.00 | 36265.76 | 0.00 | 0.00 | 0.00 | 520.12 | 1143.06 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -51386.48 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 64486.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2052.86 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -74596.96 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 03-JAN-06:05 | 0.00 | 0.00 | 11306.63 | 0.00 | 0.00 | 0.00 | 1380.54 | 2577.57 | 10116.97 | 0.00 | 0.00 | 0.00 | 9819.68 | 0.00 | -34895.26 | 0.00 | -306.12 | 0.00 |
PERIMETER_MID_ZN_2 | 03-JAN-06:05 | 0.00 | 0.00 | 9009.21 | 0.00 | 0.00 | 0.00 | 884.56 | 1661.09 | 6519.76 | 0.00 | 0.00 | 0.00 | 5331.01 | 0.00 | -23201.52 | 0.00 | -204.11 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JAN-06:06 | 0.00 | 0.00 | 4804.82 | 0.00 | 0.00 | 0.00 | 868.25 | 1661.09 | 6519.72 | 0.00 | 0.00 | 0.00 | 8399.11 | 0.00 | -22252.98 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:02 | 0.00 | 0.00 | 17176.62 | 0.00 | 0.00 | 0.00 | 0.00 | 128.89 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2279.12 | 0.00 | 0.00 | -16038.09 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 11788.09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.11 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1641.01 | 0.00 | 0.00 | -10965.16 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 17041.63 | 0.00 | 0.00 | 0.00 | 0.00 | 257.76 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2551.48 | 0.00 | 0.00 | -15759.63 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 11380.22 | 0.00 | 0.00 | 0.00 | 0.00 | 166.11 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1710.15 | 0.00 | 0.00 | -10488.15 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-14:40 | 0.00 | 0.00 | 332.01 | 0.00 | 0.00 | 0.00 | 6.06 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2307.87 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 29-DEC-04:02 | 10841.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1040.35 | -9801.53 |
MIDFLOOR_PLENUM | 11-SEP-03:02 | 94818.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -94818.37 |
TOPFLOOR_PLENUM | 02-JAN-06:13 | 19624.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19624.33 |
Total Facility | 02-JAN-06:01 | -1161776.58 | 1244437.94 | 113446.43 | -1244437.94 | 0.00 | 0.00 | 17418.16 | 38246.31 | 268362.69 | 0.00 | 0.00 | 0.00 | 855446.16 | 0.00 | -131143.18 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9523 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.2984 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 104.9457 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 98.1889 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.2757 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2049 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9527 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9527 | 0.2016 | 1.0000 | Not calculated | 1.2002 | 0.2016 | ||
AIRLOOP DATACENTER BASEMENT | 21.9609 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9611 | 0.0154 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4854 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4854 | 0.0322 | 1.0000 | Not calculated | 0.0156 | 0.0322 | ||
AIRLOOP DATACENTER MID | 4.6218 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6218 | 0.0338 | 1.0000 | Not calculated | 0.1563 | 0.0338 | ||
AIRLOOP DATACENTER TOP | 0.4649 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4649 | 0.0336 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4762 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2857 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.4729 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 31.4837 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.6378 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3827 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9527 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9527 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2016 | ||
AIRLOOP DATACENTER BASEMENT | 21.9609 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9609 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4854 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4854 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0322 | ||
AIRLOOP DATACENTER MID | 4.6218 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6218 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0338 | ||
AIRLOOP DATACENTER TOP | 0.4649 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4649 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9527 | 5.9527 | 5.9527 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2663 | 6.2663 | 1.8799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.5312 | 59.5312 | 17.8594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0993 | 6.0993 | 1.8298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2325 | 1.2325 | 0.3697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9564 | 0.9564 | 0.2869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2540 | 1.2540 | 0.3762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2433 | 1.2433 | 0.3730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.2631 | 12.2631 | 3.6789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0378 | 10.0378 | 3.0114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3702 | 12.3702 | 3.7111 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.7434 | 10.7434 | 3.2230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4392 | 1.4392 | 0.4318 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0789 | 1.0789 | 0.3237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4428 | 1.4428 | 0.4329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2153 | 1.2153 | 0.3646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4854 | 0.4854 | 0.4854 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6218 | 4.6218 | 4.6218 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4649 | 0.4649 | 0.4649 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9609 | 21.9609 | 21.9609 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9523 | 10.2984 | 10.9523 | 3.2857 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 104.9457 | 98.1889 | 104.9457 | 31.4837 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.2757 | 11.2049 | 11.2757 | 3.3827 | 0.0000 | 1.0000 |
CAV_BAS | 5.9527 | 5.9527 | 5.9527 | 5.9527 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9609 | 21.9611 | 21.9609 | 21.9609 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4854 | 0.4854 | 0.4854 | 0.4854 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6218 | 4.6218 | 4.6218 | 4.6218 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4649 | 0.4649 | 0.4649 | 0.4649 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9527 | 5.9527 | 5.9527 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1331 | 3.1331 | 1.8799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.7656 | 29.7656 | 17.8594 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0497 | 3.0497 | 1.8298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6162 | 0.6162 | 0.3697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4782 | 0.4782 | 0.2869 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6270 | 0.6270 | 0.3762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6216 | 0.6216 | 0.3730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1315 | 6.1315 | 3.6789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0189 | 5.0189 | 3.0114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1851 | 6.1851 | 3.7111 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3717 | 5.3717 | 3.2230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7196 | 0.7196 | 0.4318 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5395 | 0.5395 | 0.3237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7214 | 0.7214 | 0.4329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6077 | 0.6077 | 0.3646 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4854 | 0.4854 | 0.4854 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6218 | 4.6218 | 4.6218 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4649 | 0.4649 | 0.4649 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9609 | 21.9609 | 21.9609 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4762 | 3.2857 | 3.2857 | 3.2857 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.4729 | 31.4837 | 31.4837 | 31.4837 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.6378 | 3.3827 | 3.3827 | 3.3827 | 0.0000 | 1.0000 |
CAV_BAS | 5.9527 | 5.9527 | 5.9527 | 5.9527 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9609 | 21.9609 | 21.9609 | 21.9609 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4854 | 0.4854 | 0.4854 | 0.4854 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6218 | 4.6218 | 4.6218 | 4.6218 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4649 | 0.4649 | 0.4649 | 0.4649 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1075.83 |
Number of hours not met | 1075.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 158.47 | 489599.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7512.22 | 710536.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3942.44 | 344233.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 905.27 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.51 | 5474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 61.31 | 1944.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2890.62 | 325251.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1666.62 | 96618.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2085.38 | 96599.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 82.38 | 28597.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 636.42 | 75302.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 36295.94 |
Natural Gas | 0.00 | 794.89 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 37090.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 85.11 |
Space Heating | 0.00 |
Space Cooling | 162.18 |
Fans (All) | 62.40 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 783.58 |
Subtotal | 783.58 |
Natural Gas [MJ/m2] | |
Space Heating | 3.42 |
Service Water Heating | 13.74 |
Miscellaneous (All) | 17.16 |
Subtotal | 17.16 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.63 |
Space Heating | 0.43 |
Space Cooling | 20.25 |
Fans (All) | 7.79 |
Service Water Heating | 1.72 |
Receptacle Equipment | 41.02 |
Miscellaneous | 18.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2645. | 8760. |
LTG_SCH_DATACENTER | 2939. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7334.83 | 1425.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8634.67 | 125.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8737.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8688.67 | 71.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8674.83 | 85.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8578.67 | 181.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7845.67 | 914.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8458.33 | 301.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8370.83 | 389.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8168.50 | 591.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7998.67 | 761.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8438.17 | 321.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8336.00 | 424.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8182.83 | 577.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8084.33 | 675.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6141.50 | 2618.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6119.50 | 2640.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6720.83 | 2039.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7296.67 | 1463.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8245.33 | 514.67 | 0.00 | 0.00 | 0.00 |
Min | 6119.50 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 2640.50 | 0.00 | 0.00 | 0.00 |
Average | 8056.46 | 703.54 | 0.00 | 0.00 | 0.00 |
Sum | 185298.67 | 16181.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365037.83 | 3578.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330572.00 | 241.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330785.00 | 28.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330781.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1352.17 | 915.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1338.17 | 929.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1494.00 | 774.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82359.00 | 21036.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365037.83 | 21036.00 | 0.00 | 0.00 | 0.00 |
Average | 79137.75 | 1197.17 | 0.00 | 0.00 | 0.00 |
Sum | 1820168.17 | 27534.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5510.00 | 3250.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7158.50 | 1601.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7341.33 | 1418.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7131.00 | 1629.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7122.83 | 1637.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7479.83 | 1280.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6848.50 | 1911.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6457.17 | 2302.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6958.50 | 1801.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6900.17 | 1859.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6636.83 | 2123.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6750.83 | 2009.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6989.83 | 1770.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6900.17 | 1859.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6691.67 | 2068.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6812.33 | 1947.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7093.67 | 1666.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7086.17 | 1673.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7494.67 | 1265.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7548.83 | 1211.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 6189.50 | 2570.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5761.67 | 2998.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4867.00 | 3893.00 | 0.00 | 0.00 | 0.00 |
Min | 4867.00 | 1211.17 | 0.00 | 0.00 | 0.00 |
Max | 7548.83 | 3893.00 | 0.00 | 0.00 | 0.00 |
Average | 6770.91 | 1989.09 | 0.00 | 0.00 | 0.00 |
Sum | 155731.00 | 45749.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 345635.83 | 22980.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327783.00 | 3030.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328325.17 | 2487.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 327848.00 | 2965.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38905.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38894.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24888.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38918.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18351.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38918.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38918.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24906.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38919.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24907.33 | 1.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1645.67 | 622.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1632.83 | 635.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1777.33 | 490.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87391.33 | 16003.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 345635.83 | 22980.17 | 0.00 | 0.00 | 0.00 |
Average | 78190.59 | 2144.32 | 0.00 | 0.00 | 0.00 |
Sum | 1798383.67 | 49319.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.617787E+11 | 109953.05 | 02-JAN-05:01 | 6.48 | 6.26 | 0.567027E+10 | 7499.03 | 04-JAN-10:20 | 13.03 | 10.49 |
February | 0.549759E+11 | 108123.71 | 21-FEB-04:02 | 12.42 | 11.05 | 0.514292E+10 | 7499.06 | 02-FEB-10:09 | 12.42 | 11.05 |
March | 0.632338E+11 | 102952.08 | 06-MAR-04:02 | 15.67 | 14.63 | 0.613615E+10 | 7498.99 | 16-MAR-09:00 | 19.90 | 15.14 |
April | 0.593445E+11 | 110099.59 | 10-APR-03:02 | 18.93 | 13.53 | 0.545301E+10 | 7499.03 | 04-APR-09:09 | 18.93 | 13.53 |
May | 0.633371E+11 | 101656.10 | 29-MAY-17:44 | 40.32 | 21.26 | 0.590430E+10 | 7498.87 | 05-MAY-09:20 | 40.32 | 21.26 |
June | 0.661995E+11 | 96617.74 | 04-JUN-16:07 | 42.22 | 22.27 | 0.588544E+10 | 7498.86 | 07-JUN-09:09 | 37.65 | 20.59 |
July | 0.702160E+11 | 91735.13 | 04-JUL-16:49 | 39.87 | 24.34 | 0.547747E+10 | 7498.76 | 20-JUL-09:20 | 30.57 | 25.64 |
August | 0.800069E+11 | 90561.75 | 29-AUG-03:02 | 27.75 | 24.39 | 0.614341E+10 | 7680.19 | 28-AUG-13:00 | 27.75 | 24.39 |
September | 0.700059E+11 | 90582.27 | 26-SEP-03:02 | 25.65 | 21.91 | 0.545593E+10 | 7498.75 | 08-SEP-09:20 | 25.65 | 21.91 |
October | 0.722415E+11 | 99875.51 | 22-OCT-14:58 | 31.00 | 17.63 | 0.567525E+10 | 7498.95 | 17-OCT-09:20 | 31.00 | 17.63 |
November | 0.694286E+11 | 103820.26 | 21-NOV-04:02 | 13.58 | 11.11 | 0.561916E+10 | 7498.96 | 16-NOV-10:09 | 13.58 | 11.11 |
December | 0.667991E+11 | 109589.38 | 20-DEC-04:02 | 6.20 | 4.71 | 0.547569E+10 | 7498.95 | 13-DEC-10:09 | 6.20 | 4.71 |
Annual Sum or Average | 0.797567E+12 | 0.680390E+11 | ||||||||
Minimum of Months | 0.549759E+11 | 90561.75 | 6.20 | 4.71 | 0.514292E+10 | 7498.75 | 6.20 | 4.71 | ||
Maximum of Months | 0.800069E+11 | 110099.59 | 42.22 | 24.39 | 0.614341E+10 | 7680.19 | 40.32 | 25.64 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487211E+11 | 100045.93 | 02-JAN-04:02 | 6.67 | 6.44 | 0.508240E+10 | 6734.78 | 04-JAN-10:30 | 13.65 | 10.89 |
February | 0.502342E+11 | 98603.12 | 27-FEB-04:02 | 11.72 | 10.91 | 0.460769E+10 | 6734.77 | 02-FEB-10:09 | 11.72 | 10.91 |
March | 0.680731E+11 | 94557.51 | 20-MAR-03:02 | 16.45 | 11.38 | 0.549993E+10 | 6734.75 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.745050E+11 | 90569.92 | 17-APR-05:02 | 24.22 | 18.83 | 0.487746E+10 | 6734.74 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.702992E+11 | 90058.30 | 01-MAY-05:02 | 32.45 | 19.07 | 0.528269E+10 | 6734.55 | 05-MAY-09:00 | 37.50 | 19.96 |
June | 0.718957E+11 | 88728.92 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526692E+10 | 6734.60 | 05-JUN-13:09 | 34.12 | 19.12 |
July | 0.750371E+11 | 90553.46 | 24-JUL-05:04 | 28.48 | 26.16 | 0.489429E+10 | 6734.54 | 17-JUL-13:00 | 28.48 | 26.16 |
August | 0.846662E+11 | 87991.20 | 07-AUG-05:01 | 29.53 | 24.79 | 0.549961E+10 | 6880.69 | 28-AUG-13:00 | 34.40 | 28.36 |
September | 0.641236E+11 | 92150.67 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488287E+10 | 6734.54 | 05-SEP-09:09 | 26.07 | 25.28 |
October | 0.675984E+11 | 96582.38 | 30-OCT-03:02 | 16.75 | 15.27 | 0.507864E+10 | 6734.65 | 16-OCT-09:09 | 16.75 | 15.27 |
November | 0.632086E+11 | 98407.65 | 27-NOV-04:02 | 10.65 | 9.14 | 0.503222E+10 | 6734.69 | 16-NOV-10:09 | 10.65 | 9.14 |
December | 0.590866E+11 | 98430.92 | 18-DEC-04:02 | 11.17 | 9.04 | 0.490496E+10 | 6734.74 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.797449E+12 | 0.609097E+11 | ||||||||
Minimum of Months | 0.487211E+11 | 87991.20 | 6.67 | 6.44 | 0.460769E+10 | 6734.54 | 10.65 | 9.14 | ||
Maximum of Months | 0.846662E+11 | 100045.93 | 34.12 | 26.16 | 0.549993E+10 | 6880.69 | 37.50 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370886E+11 | 84424.13 | 17-JAN-06:02 | 10.70 | 10.27 | 0.505469E+10 | 6734.75 | 04-JAN-10:30 | 10.70 | 10.27 |
February | 0.382676E+11 | 88254.76 | 27-FEB-04:02 | 11.72 | 10.91 | 0.459447E+10 | 6734.75 | 02-FEB-10:09 | 11.72 | 10.91 |
March | 0.521756E+11 | 88472.03 | 14-MAR-03:02 | 20.88 | 16.42 | 0.549568E+10 | 6734.74 | 16-MAR-09:00 | 19.90 | 15.14 |
April | 0.546226E+11 | 88239.72 | 10-APR-03:02 | 18.93 | 13.53 | 0.487695E+10 | 6734.74 | 04-APR-09:09 | 18.93 | 13.53 |
May | 0.607942E+11 | 84626.11 | 23-MAY-03:02 | 28.47 | 24.77 | 0.527967E+10 | 6734.57 | 12-MAY-13:30 | 28.47 | 24.77 |
June | 0.591848E+11 | 84809.06 | 28-JUN-03:02 | 26.40 | 25.45 | 0.526531E+10 | 6734.61 | 05-JUN-13:09 | 26.40 | 25.45 |
July | 0.574631E+11 | 87996.20 | 19-JUL-03:02 | 23.42 | 23.42 | 0.489175E+10 | 6734.56 | 18-JUL-13:09 | 23.42 | 23.42 |
August | 0.594485E+11 | 84515.78 | 24-AUG-03:02 | 25.58 | 24.96 | 0.549515E+10 | 6734.78 | 25-AUG-13:20 | 34.40 | 28.74 |
September | 0.528212E+11 | 85768.24 | 05-SEP-03:02 | 26.38 | 25.08 | 0.488234E+10 | 6734.57 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.531205E+11 | 87880.13 | 24-OCT-03:02 | 18.57 | 14.45 | 0.507544E+10 | 6734.65 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.466000E+11 | 87813.40 | 13-NOV-04:03 | 15.47 | 13.26 | 0.502260E+10 | 6734.68 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.390125E+11 | 84392.77 | 16-DEC-06:02 | 14.32 | 11.10 | 0.488153E+10 | 6734.71 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.610599E+12 | 0.608156E+11 | ||||||||
Minimum of Months | 0.370886E+11 | 84392.77 | 10.70 | 10.27 | 0.459447E+10 | 6734.56 | 10.70 | 10.27 | ||
Maximum of Months | 0.607942E+11 | 88472.03 | 28.47 | 25.45 | 0.549568E+10 | 6734.78 | 34.40 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267616E+11 | 42260.04 | 26-JAN-06:03 | 12.90 | 11.87 | 0.478082E+10 | 6734.59 | 13-JAN-10:30 | 12.90 | 11.87 |
February | 0.315630E+11 | 84044.12 | 23-FEB-06:02 | 15.05 | 13.57 | 0.451630E+10 | 6734.61 | 15-FEB-10:30 | 15.05 | 13.57 |
March | 0.503168E+11 | 91088.90 | 13-MAR-03:02 | 20.98 | 17.40 | 0.548254E+10 | 6734.73 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.602843E+11 | 87798.55 | 10-APR-03:02 | 18.93 | 13.53 | 0.487922E+10 | 6734.73 | 04-APR-09:09 | 18.93 | 13.53 |
May | 0.708600E+11 | 88533.31 | 15-MAY-03:02 | 24.47 | 19.07 | 0.528573E+10 | 6734.56 | 05-MAY-09:09 | 24.47 | 19.07 |
June | 0.695769E+11 | 88336.62 | 01-JUN-03:02 | 27.32 | 22.02 | 0.527009E+10 | 6734.60 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.664099E+11 | 87911.66 | 28-JUL-03:02 | 27.00 | 25.79 | 0.489792E+10 | 6734.53 | 17-JUL-13:00 | 27.00 | 25.79 |
August | 0.666037E+11 | 90291.38 | 21-AUG-03:02 | 25.87 | 25.24 | 0.549902E+10 | 6747.69 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.572163E+11 | 91024.58 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488373E+10 | 6734.54 | 08-SEP-13:00 | 26.07 | 25.28 |
October | 0.530178E+11 | 89909.26 | 10-OCT-03:02 | 20.07 | 18.33 | 0.507127E+10 | 6734.63 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.400114E+11 | 85108.02 | 01-NOV-05:02 | 15.60 | 12.04 | 0.498256E+10 | 6734.63 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.290524E+11 | 65065.87 | 29-DEC-06:03 | 16.53 | 12.55 | 0.472707E+10 | 6734.62 | 27-DEC-10:00 | 16.53 | 12.55 |
Annual Sum or Average | 0.621674E+12 | 0.602763E+11 | ||||||||
Minimum of Months | 0.267616E+11 | 42260.04 | 12.90 | 11.87 | 0.451630E+10 | 6734.53 | 12.90 | 11.87 | ||
Maximum of Months | 0.708600E+11 | 91088.90 | 27.32 | 25.79 | 0.549902E+10 | 6747.69 | 42.20 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526513E+10 | 5659.15 | 26-JAN-14:10 | 22.35 | 13.84 | 0.610279E+09 | 845.62 | 17-JAN-10:00 | 22.35 | 13.84 |
February | 0.614766E+10 | 7464.08 | 23-FEB-14:30 | 26.10 | 14.00 | 0.566428E+09 | 845.62 | 27-FEB-10:09 | 16.10 | 13.56 |
March | 0.101879E+11 | 14256.93 | 14-MAR-05:03 | 20.70 | 16.42 | 0.687229E+09 | 845.62 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.140244E+11 | 17530.77 | 17-APR-05:02 | 24.22 | 18.83 | 0.612642E+09 | 845.63 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.154727E+11 | 20801.30 | 29-MAY-15:11 | 41.30 | 21.81 | 0.664799E+09 | 845.61 | 05-MAY-09:00 | 41.30 | 21.81 |
June | 0.160621E+11 | 20900.03 | 11-JUN-16:21 | 43.25 | 23.12 | 0.662553E+09 | 845.63 | 06-JUN-13:00 | 43.25 | 23.12 |
July | 0.159164E+11 | 21827.95 | 02-JUL-17:01 | 40.18 | 26.57 | 0.616021E+09 | 845.60 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.166565E+11 | 20564.24 | 06-AUG-15:41 | 36.30 | 26.24 | 0.691603E+09 | 887.73 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.120148E+11 | 17282.52 | 05-SEP-03:02 | 26.38 | 25.08 | 0.613561E+09 | 845.60 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.108720E+11 | 15702.72 | 10-OCT-05:03 | 19.80 | 18.03 | 0.636254E+09 | 845.61 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.817703E+10 | 10663.63 | 13-NOV-06:03 | 15.13 | 12.08 | 0.626203E+09 | 845.63 | 06-NOV-14:50 | 15.13 | 12.08 |
December | 0.649102E+10 | 6604.70 | 26-DEC-14:10 | 22.68 | 14.39 | 0.601236E+09 | 845.62 | 18-DEC-10:00 | 22.68 | 14.39 |
Annual Sum or Average | 0.137288E+12 | 0.758881E+10 | ||||||||
Minimum of Months | 0.526513E+10 | 5659.15 | 15.13 | 12.08 | 0.566428E+09 | 845.60 | 15.13 | 12.08 | ||
Maximum of Months | 0.166565E+11 | 21827.95 | 43.25 | 26.57 | 0.691603E+09 | 887.73 | 43.25 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420384E+10 | 4802.94 | 26-JAN-10:20 | 18.10 | 12.94 | 0.399569E+09 | 544.96 | 04-JAN-10:00 | 18.10 | 12.94 |
February | 0.496856E+10 | 7771.10 | 20-FEB-08:52 | 16.10 | 11.72 | 0.365522E+09 | 544.96 | 02-FEB-10:09 | 16.10 | 11.72 |
March | 0.810637E+10 | 12130.24 | 26-MAR-09:32 | 24.67 | 14.70 | 0.442463E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.109041E+11 | 16568.89 | 30-APR-08:22 | 27.05 | 14.40 | 0.394584E+09 | 545.38 | 28-APR-09:50 | 27.05 | 14.40 |
May | 0.123304E+11 | 17457.72 | 29-MAY-07:52 | 31.80 | 19.55 | 0.428612E+09 | 545.26 | 26-MAY-09:00 | 31.80 | 19.55 |
June | 0.116242E+11 | 16516.92 | 11-JUN-10:21 | 37.75 | 25.19 | 0.426668E+09 | 545.15 | 12-JUN-09:00 | 40.00 | 22.14 |
July | 0.108126E+11 | 16737.90 | 02-JUL-15:41 | 40.33 | 26.36 | 0.396573E+09 | 545.09 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.106915E+11 | 16257.30 | 06-AUG-10:22 | 32.90 | 25.51 | 0.444581E+09 | 552.06 | 28-AUG-13:00 | 34.40 | 28.36 |
September | 0.886769E+10 | 12009.72 | 17-SEP-10:53 | 31.90 | 25.59 | 0.394954E+09 | 544.94 | 08-SEP-13:30 | 31.90 | 25.59 |
October | 0.844320E+10 | 16466.91 | 01-OCT-09:52 | 29.70 | 19.34 | 0.409619E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.633136E+10 | 7063.76 | 13-NOV-09:50 | 21.78 | 14.28 | 0.403026E+09 | 544.96 | 06-NOV-14:50 | 21.78 | 14.28 |
December | 0.479528E+10 | 5299.21 | 01-DEC-10:00 | 18.30 | 11.37 | 0.386788E+09 | 544.95 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.102079E+12 | 0.489296E+10 | ||||||||
Minimum of Months | 0.420384E+10 | 4802.94 | 16.10 | 11.37 | 0.365522E+09 | 544.94 | 16.10 | 11.72 | ||
Maximum of Months | 0.123304E+11 | 17457.72 | 40.33 | 26.36 | 0.444581E+09 | 552.06 | 40.00 | 28.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.875065E+10 | 14104.92 | 08-JAN-15:02 | 22.78 | 13.92 | 0.624572E+09 | 845.95 | 11-JAN-14:50 | 22.20 | 11.82 |
February | 0.957429E+10 | 22276.92 | 20-FEB-14:12 | 26.37 | 13.66 | 0.572243E+09 | 846.21 | 07-FEB-14:00 | 26.37 | 13.66 |
March | 0.142256E+11 | 21857.17 | 26-MAR-13:32 | 30.07 | 16.56 | 0.689514E+09 | 846.08 | 08-MAR-14:00 | 30.07 | 16.56 |
April | 0.165186E+11 | 21437.70 | 30-APR-11:42 | 35.52 | 18.19 | 0.613509E+09 | 845.99 | 12-APR-13:00 | 35.52 | 18.19 |
May | 0.161337E+11 | 21336.22 | 29-MAY-15:11 | 41.30 | 21.81 | 0.665000E+09 | 846.15 | 08-MAY-13:20 | 41.30 | 21.81 |
June | 0.160490E+11 | 21231.72 | 11-JUN-16:21 | 43.25 | 23.12 | 0.662541E+09 | 845.91 | 12-JUN-13:39 | 43.70 | 22.38 |
July | 0.160450E+11 | 22169.29 | 02-JUL-16:21 | 40.35 | 26.46 | 0.616060E+09 | 846.29 | 10-JUL-13:20 | 39.20 | 26.73 |
August | 0.172605E+11 | 21137.47 | 06-AUG-15:41 | 36.30 | 26.24 | 0.691929E+09 | 898.68 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.142036E+11 | 21983.54 | 17-SEP-13:32 | 34.27 | 26.14 | 0.614122E+09 | 846.01 | 19-SEP-13:00 | 32.90 | 24.72 |
October | 0.161821E+11 | 23472.36 | 01-OCT-14:31 | 35.97 | 19.90 | 0.639431E+09 | 873.52 | 02-OCT-13:39 | 36.33 | 21.10 |
November | 0.143291E+11 | 23213.46 | 12-NOV-13:02 | 27.78 | 16.19 | 0.631453E+09 | 851.87 | 01-NOV-13:30 | 27.78 | 16.19 |
December | 0.106278E+11 | 21780.31 | 03-DEC-12:43 | 23.78 | 14.19 | 0.609787E+09 | 846.25 | 18-DEC-14:00 | 22.10 | 15.00 |
Annual Sum or Average | 0.169900E+12 | 0.763016E+10 | ||||||||
Minimum of Months | 0.875065E+10 | 14104.92 | 22.78 | 13.66 | 0.572243E+09 | 845.91 | 22.10 | 11.82 | ||
Maximum of Months | 0.172605E+11 | 23472.36 | 43.25 | 26.46 | 0.691929E+09 | 898.68 | 43.70 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584867E+10 | 7617.88 | 31-JAN-16:00 | 21.10 | 11.23 | 0.395763E+09 | 544.95 | 17-JAN-14:09 | 21.10 | 11.23 |
February | 0.708531E+10 | 17729.33 | 20-FEB-14:52 | 26.30 | 14.02 | 0.369561E+09 | 544.95 | 27-FEB-10:09 | 16.10 | 13.56 |
March | 0.123953E+11 | 21717.53 | 26-MAR-14:52 | 30.40 | 16.78 | 0.445774E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.177051E+11 | 23045.62 | 30-APR-16:21 | 37.45 | 18.00 | 0.396394E+09 | 544.96 | 28-APR-13:20 | 37.45 | 18.00 |
May | 0.149731E+11 | 22604.85 | 28-MAY-16:11 | 42.10 | 19.51 | 0.428862E+09 | 544.95 | 05-MAY-09:00 | 42.10 | 19.51 |
June | 0.159328E+11 | 22791.25 | 11-JUN-16:21 | 43.25 | 23.12 | 0.427499E+09 | 547.09 | 22-JUN-15:00 | 39.50 | 28.34 |
July | 0.159016E+11 | 24742.71 | 02-JUL-16:21 | 40.35 | 26.46 | 0.397691E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.188789E+11 | 22680.82 | 06-AUG-15:41 | 36.30 | 26.24 | 0.446961E+09 | 581.06 | 28-AUG-15:00 | 35.00 | 28.31 |
September | 0.115042E+11 | 22038.63 | 17-SEP-16:12 | 34.17 | 26.19 | 0.395846E+09 | 544.94 | 08-SEP-13:30 | 34.17 | 26.19 |
October | 0.117990E+11 | 22997.69 | 01-OCT-15:51 | 35.50 | 20.15 | 0.411758E+09 | 544.95 | 10-OCT-13:00 | 31.70 | 20.64 |
November | 0.100602E+11 | 21319.25 | 12-NOV-15:02 | 28.08 | 15.73 | 0.407554E+09 | 544.97 | 06-NOV-14:50 | 28.08 | 15.73 |
December | 0.865717E+10 | 16170.44 | 29-DEC-06:03 | 16.53 | 12.55 | 0.396375E+09 | 544.96 | 18-DEC-10:00 | 16.53 | 12.55 |
Annual Sum or Average | 0.150741E+12 | 0.492004E+10 | ||||||||
Minimum of Months | 0.584867E+10 | 7617.88 | 16.53 | 11.23 | 0.369561E+09 | 544.94 | 16.10 | 11.23 | ||
Maximum of Months | 0.188789E+11 | 24742.71 | 43.25 | 26.46 | 0.446961E+09 | 581.06 | 42.10 | 28.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404815E+10 | 4271.14 | 26-JAN-14:50 | 21.75 | 13.69 | 0.558741E+09 | 845.60 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.469077E+10 | 6356.75 | 24-FEB-15:00 | 26.40 | 17.38 | 0.540157E+09 | 845.61 | 24-FEB-14:30 | 26.40 | 17.38 |
March | 0.783788E+10 | 14711.07 | 30-MAR-05:02 | 21.37 | 16.59 | 0.679420E+09 | 845.62 | 27-MAR-09:09 | 21.37 | 16.59 |
April | 0.111227E+11 | 15549.65 | 28-APR-05:02 | 27.22 | 17.16 | 0.612509E+09 | 845.63 | 28-APR-13:20 | 37.93 | 20.83 |
May | 0.147150E+11 | 22240.26 | 28-MAY-16:01 | 42.20 | 19.49 | 0.665029E+09 | 845.61 | 05-MAY-09:30 | 42.20 | 19.49 |
June | 0.146592E+11 | 21616.81 | 11-JUN-16:51 | 43.10 | 23.03 | 0.662841E+09 | 845.73 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.136545E+11 | 20348.39 | 02-JUL-16:42 | 40.32 | 26.53 | 0.616597E+09 | 845.60 | 10-JUL-09:30 | 33.55 | 26.55 |
August | 0.130049E+11 | 17148.30 | 01-AUG-03:02 | 27.97 | 25.00 | 0.691392E+09 | 846.44 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.104637E+11 | 16784.09 | 11-SEP-03:02 | 26.07 | 25.28 | 0.613657E+09 | 845.60 | 08-SEP-13:30 | 26.07 | 25.28 |
October | 0.878284E+10 | 14821.69 | 03-OCT-05:03 | 22.92 | 17.52 | 0.633233E+09 | 845.61 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.606149E+10 | 6700.90 | 09-NOV-14:30 | 29.30 | 17.79 | 0.610476E+09 | 845.62 | 06-NOV-14:50 | 29.30 | 17.79 |
December | 0.439581E+10 | 4430.30 | 03-DEC-13:32 | 24.33 | 14.17 | 0.553570E+09 | 845.61 | 29-DEC-14:00 | 19.50 | 14.92 |
Annual Sum or Average | 0.113437E+12 | 0.743762E+10 | ||||||||
Minimum of Months | 0.404815E+10 | 4271.14 | 21.37 | 13.69 | 0.540157E+09 | 845.60 | 19.50 | 13.66 | ||
Maximum of Months | 0.147150E+11 | 22240.26 | 43.10 | 26.53 | 0.691392E+09 | 846.44 | 43.90 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351401E+10 | 3833.43 | 26-JAN-11:10 | 19.98 | 13.28 | 0.273227E+09 | 521.19 | 12-JAN-15:00 | 19.98 | 13.28 |
February | 0.420073E+10 | 6508.01 | 22-FEB-10:00 | 20.60 | 13.92 | 0.260954E+09 | 521.21 | 15-FEB-11:20 | 20.60 | 13.92 |
March | 0.714048E+10 | 11556.30 | 26-MAR-10:13 | 26.23 | 15.14 | 0.322980E+09 | 521.22 | 16-MAR-10:20 | 26.23 | 15.14 |
April | 0.101086E+11 | 18484.46 | 30-APR-09:52 | 31.40 | 16.16 | 0.291156E+09 | 521.86 | 14-APR-10:50 | 31.40 | 16.16 |
May | 0.124060E+11 | 19126.18 | 29-MAY-09:01 | 34.05 | 21.14 | 0.315653E+09 | 521.78 | 19-MAY-10:00 | 34.05 | 21.14 |
June | 0.113405E+11 | 17994.09 | 11-JUN-09:32 | 35.83 | 25.01 | 0.313882E+09 | 521.74 | 12-JUN-10:00 | 41.40 | 22.35 |
July | 0.100630E+11 | 17057.44 | 04-JUL-10:12 | 35.60 | 25.06 | 0.293001E+09 | 521.64 | 06-JUL-10:50 | 37.57 | 25.52 |
August | 0.945512E+10 | 12948.97 | 07-AUG-05:01 | 29.53 | 24.79 | 0.327237E+09 | 523.88 | 28-AUG-15:00 | 35.00 | 28.31 |
September | 0.819922E+10 | 16998.20 | 24-SEP-10:12 | 31.60 | 25.28 | 0.290874E+09 | 521.20 | 29-SEP-14:20 | 33.83 | 22.63 |
October | 0.756810E+10 | 17452.10 | 01-OCT-09:52 | 29.70 | 19.34 | 0.300711E+09 | 521.21 | 10-OCT-14:20 | 31.63 | 20.81 |
November | 0.535275E+10 | 6490.33 | 09-NOV-10:00 | 24.50 | 17.90 | 0.292408E+09 | 521.21 | 08-NOV-15:20 | 24.50 | 17.90 |
December | 0.374621E+10 | 4390.08 | 01-DEC-10:00 | 18.30 | 11.37 | 0.268874E+09 | 521.20 | 27-DEC-11:39 | 20.73 | 14.38 |
Annual Sum or Average | 0.930947E+11 | 0.355096E+10 | ||||||||
Minimum of Months | 0.351401E+10 | 3833.43 | 18.30 | 11.37 | 0.260954E+09 | 521.19 | 19.98 | 13.28 | ||
Maximum of Months | 0.124060E+11 | 19126.18 | 35.83 | 25.28 | 0.327237E+09 | 523.88 | 41.40 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.810044E+10 | 18370.66 | 08-JAN-15:02 | 22.78 | 13.92 | 0.617151E+09 | 845.92 | 11-JAN-14:00 | 22.20 | 11.82 |
February | 0.850907E+10 | 21360.07 | 20-FEB-12:32 | 25.43 | 13.32 | 0.565943E+09 | 846.06 | 07-FEB-14:00 | 25.43 | 13.32 |
March | 0.122158E+11 | 21720.60 | 26-MAR-14:12 | 30.27 | 16.70 | 0.687467E+09 | 848.83 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.137811E+11 | 21988.83 | 16-APR-12:52 | 39.10 | 21.92 | 0.613937E+09 | 845.87 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.153135E+11 | 22507.48 | 28-MAY-16:01 | 42.20 | 19.49 | 0.665185E+09 | 845.89 | 08-MAY-13:00 | 42.20 | 19.49 |
June | 0.145582E+11 | 21570.00 | 11-JUN-16:51 | 43.10 | 23.03 | 0.662820E+09 | 845.82 | 12-JUN-13:39 | 43.70 | 22.38 |
July | 0.137460E+11 | 20439.90 | 02-JUL-16:42 | 40.32 | 26.53 | 0.616620E+09 | 845.69 | 05-JUL-13:39 | 37.90 | 25.56 |
August | 0.136806E+11 | 17542.28 | 06-AUG-14:32 | 36.17 | 26.28 | 0.691744E+09 | 858.77 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.128338E+11 | 22049.03 | 24-SEP-14:52 | 35.10 | 24.83 | 0.614395E+09 | 851.63 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.146948E+11 | 23566.11 | 01-OCT-14:31 | 35.97 | 19.90 | 0.639536E+09 | 876.26 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.128788E+11 | 23105.96 | 05-NOV-13:12 | 29.07 | 17.13 | 0.629688E+09 | 855.73 | 01-NOV-13:39 | 29.07 | 17.13 |
December | 0.882475E+10 | 21413.38 | 03-DEC-12:53 | 24.00 | 14.17 | 0.602619E+09 | 845.97 | 20-DEC-14:00 | 20.30 | 10.35 |
Annual Sum or Average | 0.149137E+12 | 0.760711E+10 | ||||||||
Minimum of Months | 0.810044E+10 | 17542.28 | 22.78 | 13.32 | 0.565943E+09 | 845.69 | 20.30 | 10.35 | ||
Maximum of Months | 0.153135E+11 | 23566.11 | 43.10 | 26.53 | 0.691744E+09 | 876.26 | 43.70 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389259E+10 | 5583.35 | 31-JAN-16:00 | 21.10 | 11.23 | 0.365208E+09 | 544.94 | 25-JAN-14:00 | 21.10 | 11.23 |
February | 0.448312E+10 | 7848.36 | 21-FEB-16:00 | 26.10 | 15.66 | 0.347653E+09 | 544.95 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.759976E+10 | 14285.56 | 26-MAR-14:52 | 30.40 | 16.78 | 0.438343E+09 | 544.95 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.108346E+11 | 20161.86 | 02-APR-16:01 | 33.83 | 20.60 | 0.395600E+09 | 544.96 | 28-APR-13:20 | 37.93 | 20.83 |
May | 0.128120E+11 | 21856.19 | 28-MAY-16:01 | 42.20 | 19.49 | 0.428842E+09 | 544.95 | 05-MAY-09:30 | 42.20 | 19.49 |
June | 0.124097E+11 | 20975.54 | 11-JUN-16:51 | 43.10 | 23.03 | 0.427348E+09 | 545.45 | 22-JUN-15:00 | 39.50 | 28.34 |
July | 0.107976E+11 | 18989.50 | 02-JUL-16:42 | 40.32 | 26.53 | 0.397448E+09 | 544.94 | 10-JUL-09:30 | 33.55 | 26.55 |
August | 0.104097E+11 | 18560.79 | 06-AUG-16:32 | 36.10 | 26.38 | 0.445702E+09 | 544.96 | 25-AUG-13:20 | 34.40 | 28.74 |
September | 0.874943E+10 | 19022.28 | 24-SEP-14:52 | 35.10 | 24.83 | 0.395324E+09 | 544.94 | 08-SEP-13:30 | 35.10 | 24.83 |
October | 0.798820E+10 | 19789.08 | 01-OCT-15:51 | 35.50 | 20.15 | 0.408442E+09 | 544.95 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.592832E+10 | 9517.56 | 05-NOV-15:12 | 28.63 | 17.52 | 0.393902E+09 | 544.96 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.424695E+10 | 5985.47 | 01-DEC-15:30 | 22.85 | 13.56 | 0.361889E+09 | 544.94 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.100152E+12 | 0.480570E+10 | ||||||||
Minimum of Months | 0.389259E+10 | 5583.35 | 21.10 | 11.23 | 0.347653E+09 | 544.94 | 21.10 | 11.23 | ||
Maximum of Months | 0.128120E+11 | 21856.19 | 43.10 | 26.53 | 0.445702E+09 | 545.45 | 42.20 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319333E+10 | 4195.55 | 26-JAN-15:10 | 21.37 | 13.58 | 0.509093E+09 | 822.54 | 26-JAN-14:00 | 21.37 | 13.58 |
February | 0.431776E+10 | 6471.70 | 23-FEB-14:50 | 25.90 | 14.07 | 0.507226E+09 | 845.61 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.804178E+10 | 12451.03 | 30-MAR-05:02 | 21.37 | 16.59 | 0.664348E+09 | 845.62 | 27-MAR-09:00 | 21.37 | 16.59 |
April | 0.124085E+11 | 24250.56 | 16-APR-15:31 | 39.43 | 22.55 | 0.610560E+09 | 845.63 | 28-APR-13:09 | 37.77 | 20.72 |
May | 0.168519E+11 | 25121.71 | 28-MAY-16:21 | 42.00 | 19.52 | 0.664905E+09 | 845.62 | 05-MAY-09:00 | 42.00 | 19.52 |
June | 0.167695E+11 | 24736.88 | 11-JUN-16:31 | 43.20 | 23.09 | 0.662730E+09 | 845.62 | 05-JUN-13:09 | 43.20 | 23.09 |
July | 0.156044E+11 | 24886.18 | 02-JUL-16:31 | 40.33 | 26.50 | 0.616567E+09 | 845.60 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.144883E+11 | 23810.23 | 13-AUG-16:11 | 34.73 | 28.34 | 0.691210E+09 | 845.64 | 25-AUG-13:20 | 34.40 | 28.74 |
September | 0.115072E+11 | 24090.45 | 24-SEP-14:52 | 35.10 | 24.83 | 0.612330E+09 | 845.60 | 08-SEP-13:00 | 35.10 | 24.83 |
October | 0.924677E+10 | 11690.53 | 11-OCT-03:02 | 24.45 | 20.86 | 0.625795E+09 | 845.61 | 27-OCT-13:00 | 30.80 | 19.11 |
November | 0.579534E+10 | 7095.84 | 09-NOV-14:40 | 29.27 | 17.76 | 0.584447E+09 | 845.62 | 15-NOV-14:20 | 26.37 | 17.60 |
December | 0.362195E+10 | 4178.71 | 28-DEC-16:00 | 23.80 | 15.20 | 0.505946E+09 | 815.56 | 28-DEC-14:00 | 23.80 | 15.20 |
Annual Sum or Average | 0.121847E+12 | 0.725516E+10 | ||||||||
Minimum of Months | 0.319333E+10 | 4178.71 | 21.37 | 13.58 | 0.505946E+09 | 815.56 | 21.37 | 13.58 | ||
Maximum of Months | 0.168519E+11 | 25121.71 | 43.20 | 28.34 | 0.691210E+09 | 845.64 | 43.20 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290953E+10 | 3412.75 | 26-JAN-14:40 | 21.90 | 13.73 | 0.345899E+09 | 544.94 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.381456E+10 | 6051.44 | 23-FEB-10:40 | 22.80 | 14.32 | 0.345685E+09 | 544.95 | 15-FEB-10:50 | 22.80 | 14.32 |
March | 0.725230E+10 | 9609.36 | 28-MAR-10:20 | 29.33 | 18.17 | 0.438003E+09 | 544.96 | 16-MAR-09:00 | 29.33 | 18.17 |
April | 0.111354E+11 | 19166.83 | 16-APR-12:52 | 39.10 | 21.92 | 0.395102E+09 | 545.27 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.140070E+11 | 19395.21 | 29-MAY-09:22 | 34.75 | 21.56 | 0.428859E+09 | 545.23 | 26-MAY-09:00 | 34.75 | 21.56 |
June | 0.128827E+11 | 18549.45 | 11-JUN-10:32 | 38.13 | 25.22 | 0.427004E+09 | 545.22 | 13-JUN-09:20 | 35.17 | 26.05 |
July | 0.114527E+11 | 19728.36 | 02-JUL-09:52 | 35.30 | 26.07 | 0.397293E+09 | 545.10 | 06-JUL-09:09 | 35.15 | 25.92 |
August | 0.105762E+11 | 17496.09 | 13-AUG-15:31 | 34.80 | 28.33 | 0.445268E+09 | 544.96 | 25-AUG-13:20 | 34.40 | 28.74 |
September | 0.901801E+10 | 18541.12 | 24-SEP-14:52 | 35.10 | 24.83 | 0.394579E+09 | 544.94 | 12-SEP-09:20 | 35.10 | 24.83 |
October | 0.791561E+10 | 13830.46 | 09-OCT-15:32 | 32.47 | 20.08 | 0.407011E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.503413E+10 | 6162.16 | 09-NOV-10:30 | 25.75 | 18.10 | 0.393038E+09 | 544.95 | 15-NOV-14:30 | 26.40 | 17.66 |
December | 0.313558E+10 | 3500.93 | 01-DEC-15:00 | 23.40 | 13.35 | 0.345189E+09 | 544.94 | 01-DEC-14:00 | 23.40 | 13.35 |
Annual Sum or Average | 0.991337E+11 | 0.476293E+10 | ||||||||
Minimum of Months | 0.290953E+10 | 3412.75 | 21.90 | 13.35 | 0.345189E+09 | 544.94 | 21.60 | 13.35 | ||
Maximum of Months | 0.140070E+11 | 19728.36 | 39.10 | 28.33 | 0.445268E+09 | 545.27 | 35.17 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662572E+10 | 12638.36 | 12-JAN-14:20 | 23.40 | 14.05 | 0.586529E+09 | 845.64 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.780630E+10 | 25187.39 | 20-FEB-14:22 | 26.35 | 13.75 | 0.548058E+09 | 846.00 | 21-FEB-14:00 | 26.30 | 15.42 |
March | 0.123604E+11 | 19961.88 | 12-MAR-14:23 | 31.35 | 19.49 | 0.680391E+09 | 846.06 | 09-MAR-14:00 | 31.35 | 19.49 |
April | 0.152268E+11 | 26196.78 | 16-APR-12:52 | 39.10 | 21.92 | 0.612730E+09 | 845.98 | 25-APR-13:20 | 36.40 | 20.92 |
May | 0.174898E+11 | 25264.49 | 28-MAY-15:41 | 42.28 | 19.40 | 0.665051E+09 | 846.22 | 04-MAY-13:20 | 42.28 | 19.40 |
June | 0.166553E+11 | 24666.94 | 11-JUN-16:31 | 43.20 | 23.09 | 0.662709E+09 | 846.22 | 12-JUN-13:20 | 43.50 | 22.39 |
July | 0.156915E+11 | 24888.07 | 02-JUL-16:31 | 40.33 | 26.50 | 0.616578E+09 | 845.62 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.152086E+11 | 24291.01 | 13-AUG-14:51 | 34.80 | 28.33 | 0.691503E+09 | 852.12 | 25-AUG-13:00 | 34.20 | 28.56 |
September | 0.139851E+11 | 26222.68 | 24-SEP-14:52 | 35.10 | 24.83 | 0.613506E+09 | 845.86 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.152645E+11 | 27151.76 | 09-OCT-12:52 | 32.30 | 19.97 | 0.636349E+09 | 848.65 | 02-OCT-13:50 | 32.30 | 19.97 |
November | 0.122680E+11 | 26675.59 | 05-NOV-13:42 | 29.32 | 17.20 | 0.622108E+09 | 846.14 | 21-NOV-14:50 | 26.73 | 14.88 |
December | 0.748136E+10 | 16096.07 | 03-DEC-12:43 | 23.78 | 14.19 | 0.581055E+09 | 845.64 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.156063E+12 | 0.751657E+10 | ||||||||
Minimum of Months | 0.662572E+10 | 12638.36 | 23.40 | 13.75 | 0.548058E+09 | 845.62 | 23.00 | 13.41 | ||
Maximum of Months | 0.174898E+11 | 27151.76 | 43.20 | 28.33 | 0.691503E+09 | 852.12 | 43.50 | 28.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324700E+10 | 5050.30 | 31-JAN-16:10 | 20.95 | 11.21 | 0.341546E+09 | 544.92 | 12-JAN-14:00 | 20.95 | 11.21 |
February | 0.417187E+10 | 7867.94 | 21-FEB-16:00 | 26.10 | 15.66 | 0.331224E+09 | 544.95 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.772547E+10 | 13647.12 | 29-MAR-03:02 | 21.75 | 18.34 | 0.429787E+09 | 544.95 | 27-MAR-09:50 | 21.75 | 18.34 |
April | 0.117913E+11 | 23170.20 | 02-APR-16:01 | 33.83 | 20.60 | 0.394578E+09 | 544.96 | 28-APR-13:20 | 37.93 | 20.83 |
May | 0.143382E+11 | 22828.37 | 28-MAY-16:21 | 42.00 | 19.52 | 0.428606E+09 | 544.95 | 05-MAY-09:00 | 42.00 | 19.52 |
June | 0.139076E+11 | 22336.31 | 11-JUN-16:31 | 43.20 | 23.09 | 0.427124E+09 | 552.01 | 22-JUN-15:00 | 39.50 | 28.34 |
July | 0.121379E+11 | 22386.08 | 02-JUL-16:31 | 40.33 | 26.50 | 0.397203E+09 | 544.94 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.114123E+11 | 21058.58 | 13-AUG-16:11 | 34.73 | 28.34 | 0.445344E+09 | 544.96 | 25-AUG-13:20 | 34.40 | 28.74 |
September | 0.953178E+10 | 21853.52 | 24-SEP-14:52 | 35.10 | 24.83 | 0.394198E+09 | 544.94 | 08-SEP-13:00 | 35.10 | 24.83 |
October | 0.833707E+10 | 21616.75 | 09-OCT-15:32 | 32.47 | 20.08 | 0.403792E+09 | 544.95 | 27-OCT-13:00 | 30.80 | 19.11 |
November | 0.570292E+10 | 8727.42 | 05-NOV-15:02 | 28.82 | 17.45 | 0.380829E+09 | 544.95 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.364275E+10 | 5692.37 | 28-DEC-15:40 | 24.03 | 15.27 | 0.339777E+09 | 544.94 | 28-DEC-14:50 | 24.03 | 15.27 |
Annual Sum or Average | 0.105946E+12 | 0.471401E+10 | ||||||||
Minimum of Months | 0.324700E+10 | 5050.30 | 20.95 | 11.21 | 0.331224E+09 | 544.92 | 20.95 | 11.21 | ||
Maximum of Months | 0.143382E+11 | 23170.20 | 43.20 | 28.34 | 0.445344E+09 | 552.01 | 42.00 | 28.74 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482711E+10 | 9032.46 | 02-JAN-06:13 | 6.50 | 6.28 | 0.00 | 0.00 | 01-JAN-00:10 | 6.50 | 6.28 |
February | 0.587814E+10 | 11621.08 | 21-FEB-06:13 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.966166E+10 | 11588.03 | 06-MAR-06:13 | 15.77 | 13.93 | 0.00 | 0.00 | 01-MAR-00:10 | 15.77 | 13.93 |
April | 0.127612E+11 | 17105.57 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.137839E+11 | 17645.93 | 01-MAY-05:15 | 32.50 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 32.50 | 19.11 |
June | 0.137708E+11 | 18264.25 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.135076E+11 | 19019.92 | 03-JUL-05:13 | 29.33 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 29.33 | 24.63 |
August | 0.146521E+11 | 17231.74 | 28-AUG-05:15 | 29.10 | 27.36 | 0.00 | 0.00 | 01-AUG-00:10 | 29.10 | 27.36 |
September | 0.108345E+11 | 14219.92 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.106667E+11 | 14074.96 | 10-OCT-05:15 | 19.90 | 18.09 | 0.00 | 0.00 | 01-OCT-00:10 | 19.90 | 18.09 |
November | 0.861074E+10 | 12382.00 | 13-NOV-06:13 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.644754E+10 | 10092.11 | 26-DEC-06:15 | 10.23 | 8.49 | 0.00 | 0.00 | 01-DEC-00:10 | 10.23 | 8.49 |
Annual Sum or Average | 0.125402E+12 | 0.00 | ||||||||
Minimum of Months | 0.482711E+10 | 9032.46 | 6.50 | 6.28 | 0.00 | 0.00 | 6.50 | 6.28 | ||
Maximum of Months | 0.146521E+11 | 19019.92 | 34.23 | 27.36 | 0.00 | 0.00 | 34.23 | 27.36 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294332E+10 | 5491.23 | 06-JAN-06:10 | 5.67 | 5.41 | 0.00 | 0.00 | 01-JAN-00:10 | 5.67 | 5.41 |
February | 0.399415E+10 | 6809.76 | 21-FEB-06:13 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.734882E+10 | 8733.79 | 30-MAR-05:15 | 21.33 | 16.61 | 0.00 | 0.00 | 01-MAR-00:10 | 21.33 | 16.61 |
April | 0.100046E+11 | 9622.78 | 17-APR-15:10 | 34.65 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 34.65 | 21.60 |
May | 0.122198E+11 | 12369.41 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.117802E+11 | 12054.23 | 06-JUN-05:03 | 32.68 | 20.85 | 0.00 | 0.00 | 01-JUN-00:10 | 32.68 | 20.85 |
July | 0.109272E+11 | 13884.53 | 05-JUL-05:03 | 32.57 | 24.73 | 0.00 | 0.00 | 01-JUL-00:10 | 32.57 | 24.73 |
August | 0.108303E+11 | 10857.95 | 14-AUG-05:02 | 28.58 | 26.20 | 0.00 | 0.00 | 01-AUG-00:10 | 28.58 | 26.20 |
September | 0.929871E+10 | 13753.78 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.864145E+10 | 10482.94 | 02-OCT-05:13 | 21.80 | 17.53 | 0.00 | 0.00 | 01-OCT-00:10 | 21.80 | 17.53 |
November | 0.609079E+10 | 8020.57 | 14-NOV-06:13 | 14.73 | 12.75 | 0.00 | 0.00 | 01-NOV-00:10 | 14.73 | 12.75 |
December | 0.375601E+10 | 5555.87 | 09-DEC-06:10 | 9.60 | 9.59 | 0.00 | 0.00 | 01-DEC-00:10 | 9.60 | 9.59 |
Annual Sum or Average | 0.978353E+11 | 0.00 | ||||||||
Minimum of Months | 0.294332E+10 | 5491.23 | 5.67 | 5.41 | 0.00 | 0.00 | 5.67 | 5.41 | ||
Maximum of Months | 0.122198E+11 | 13884.53 | 34.65 | 26.20 | 0.00 | 0.00 | 34.65 | 26.20 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233708E+10 | 7517.70 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.463296E+10 | 14286.13 | 22-FEB-14:40 | 27.07 | 16.24 | 0.00 | 0.00 | 01-FEB-00:10 | 27.07 | 16.24 |
March | 0.113340E+11 | 22174.20 | 28-MAR-15:20 | 35.57 | 18.58 | 0.00 | 0.00 | 01-MAR-00:10 | 35.57 | 18.58 |
April | 0.193881E+11 | 27198.60 | 27-APR-14:50 | 39.93 | 19.43 | 0.00 | 0.00 | 01-APR-00:10 | 39.93 | 19.43 |
May | 0.251857E+11 | 30861.15 | 01-MAY-14:10 | 43.87 | 21.97 | 0.00 | 0.00 | 01-MAY-00:10 | 43.87 | 21.97 |
June | 0.250180E+11 | 32399.98 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.206629E+11 | 28837.19 | 07-JUL-14:00 | 40.30 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 40.30 | 24.54 |
August | 0.190785E+11 | 25878.19 | 07-AUG-14:00 | 37.20 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 37.20 | 26.26 |
September | 0.150554E+11 | 22604.26 | 26-SEP-14:40 | 35.97 | 22.76 | 0.00 | 0.00 | 01-SEP-00:10 | 35.97 | 22.76 |
October | 0.129335E+11 | 21615.56 | 02-OCT-14:20 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.726761E+10 | 15216.18 | 09-NOV-14:10 | 29.37 | 17.83 | 0.00 | 0.00 | 01-NOV-00:10 | 29.37 | 17.83 |
December | 0.283038E+10 | 8932.19 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.165724E+12 | 0.00 | ||||||||
Minimum of Months | 0.233708E+10 | 7517.70 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.251857E+11 | 32399.98 | 43.87 | 26.26 | 0.00 | 0.00 | 43.87 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404938E+10 | 1920.34 | 30-JAN-17:00 | 19.20 | 10.80 | 95236770.67 | 126.85 | 17-JAN-14:00 | 19.20 | 10.80 |
February | 0.849752E+10 | 3898.65 | 20-FEB-17:20 | 24.07 | 14.47 | 86404102.83 | 126.85 | 09-FEB-14:00 | 24.07 | 14.47 |
March | 0.146708E+11 | 7205.66 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103241E+09 | 126.84 | 23-MAR-09:09 | 23.70 | 16.75 |
April | 0.191173E+11 | 7730.44 | 17-APR-00:12 | 26.83 | 20.00 | 95540847.38 | 146.00 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.478654E+10 | 3509.14 | 31-MAY-24:00 | 28.10 | 22.60 | 99240832.30 | 126.85 | 09-MAY-09:50 | 28.10 | 22.60 |
June | 0.950030E+10 | 5388.11 | 30-JUN-23:57 | 33.10 | 24.67 | 98979359.86 | 126.88 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.148484E+11 | 7259.76 | 31-JUL-24:00 | 29.40 | 26.34 | 91893369.87 | 126.85 | 18-JUL-09:09 | 29.40 | 26.34 |
August | 0.195755E+11 | 7566.57 | 16-AUG-09:20 | 25.07 | 24.43 | 0.112965E+09 | 152.07 | 07-AUG-13:00 | 25.07 | 24.43 |
September | 0.457683E+10 | 3507.25 | 30-SEP-23:50 | 26.60 | 21.97 | 91606734.10 | 126.85 | 29-SEP-13:00 | 26.60 | 21.97 |
October | 0.973079E+10 | 5406.49 | 31-OCT-24:00 | 17.80 | 15.13 | 95244693.83 | 126.86 | 13-OCT-09:30 | 17.80 | 15.13 |
November | 0.142109E+11 | 5800.18 | 12-NOV-16:37 | 26.77 | 15.43 | 94304833.53 | 126.83 | 10-NOV-10:09 | 26.77 | 15.43 |
December | 0.195444E+11 | 7648.82 | 28-DEC-17:00 | 22.80 | 14.91 | 91882160.48 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.143109E+12 | 0.115654E+10 | ||||||||
Minimum of Months | 0.404938E+10 | 1920.34 | 17.80 | 10.80 | 86404102.83 | 126.83 | 17.80 | 10.80 | ||
Maximum of Months | 0.195755E+11 | 7730.44 | 33.10 | 26.34 | 0.112965E+09 | 152.07 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292670E+10 | 1758.98 | 12-JAN-17:00 | 22.30 | 14.53 | 95235262.83 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.751653E+10 | 3647.70 | 21-FEB-17:00 | 25.40 | 15.70 | 86403559.80 | 126.84 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.138234E+11 | 6962.37 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.181307E+11 | 7276.91 | 12-APR-16:00 | 28.10 | 17.52 | 95384155.93 | 144.75 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.446921E+10 | 3384.91 | 31-MAY-24:00 | 28.10 | 22.60 | 99238681.43 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.900549E+10 | 5194.05 | 30-JUN-23:55 | 33.10 | 24.67 | 98979767.66 | 126.87 | 28-JUN-13:39 | 33.10 | 24.67 |
July | 0.141101E+11 | 6942.42 | 31-JUL-24:00 | 29.40 | 26.34 | 91894658.23 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.184811E+11 | 7148.75 | 16-AUG-10:00 | 25.40 | 24.76 | 0.111575E+09 | 148.27 | 07-AUG-13:00 | 25.40 | 24.76 |
September | 0.422399E+10 | 3405.90 | 30-SEP-23:57 | 26.60 | 21.92 | 91605660.39 | 126.85 | 27-SEP-13:39 | 26.60 | 21.92 |
October | 0.911878E+10 | 5087.52 | 31-OCT-24:00 | 17.80 | 15.13 | 95244235.83 | 126.86 | 06-OCT-09:39 | 17.80 | 15.13 |
November | 0.131529E+11 | 5469.67 | 13-NOV-16:40 | 26.80 | 16.64 | 94304918.84 | 126.83 | 09-NOV-10:09 | 26.80 | 16.64 |
December | 0.178174E+11 | 7217.65 | 01-DEC-17:00 | 21.20 | 14.26 | 91882334.95 | 126.83 | 11-DEC-10:00 | 10.00 | 9.32 |
Annual Sum or Average | 0.132776E+12 | 0.115499E+10 | ||||||||
Minimum of Months | 0.292670E+10 | 1758.98 | 17.80 | 14.26 | 86403559.80 | 126.83 | 10.00 | 9.32 | ||
Maximum of Months | 0.184811E+11 | 7276.91 | 33.10 | 26.34 | 0.111575E+09 | 148.27 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155979E+10 | 1763.13 | 12-JAN-17:00 | 22.30 | 14.53 | 95044015.39 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.682489E+10 | 3682.59 | 22-FEB-17:00 | 25.70 | 15.75 | 86404237.16 | 126.84 | 10-FEB-14:00 | 25.70 | 15.75 |
March | 0.136378E+11 | 6908.82 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.182696E+11 | 7475.06 | 16-APR-21:32 | 28.07 | 20.03 | 94263993.37 | 143.31 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.468533E+10 | 3352.68 | 31-MAY-24:00 | 28.10 | 22.60 | 99239232.50 | 126.86 | 10-MAY-13:00 | 28.10 | 22.60 |
June | 0.920581E+10 | 5254.36 | 30-JUN-23:55 | 33.10 | 24.67 | 98980870.72 | 126.88 | 26-JUN-09:00 | 33.10 | 24.67 |
July | 0.143086E+11 | 7046.31 | 31-JUL-23:53 | 29.40 | 26.34 | 91895963.75 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.187777E+11 | 7280.30 | 20-AUG-16:55 | 26.70 | 25.64 | 0.109064E+09 | 146.97 | 07-AUG-13:00 | 26.70 | 25.64 |
September | 0.427903E+10 | 3361.13 | 30-SEP-23:57 | 26.60 | 21.92 | 91605720.74 | 126.86 | 27-SEP-13:20 | 26.60 | 21.92 |
October | 0.902385E+10 | 4940.94 | 31-OCT-24:00 | 17.80 | 15.13 | 95245388.30 | 126.86 | 12-OCT-13:00 | 17.80 | 15.13 |
November | 0.126485E+11 | 5522.92 | 08-NOV-16:30 | 28.55 | 18.76 | 94305595.08 | 126.83 | 09-NOV-10:09 | 24.92 | 17.98 |
December | 0.166404E+11 | 7216.23 | 28-DEC-17:00 | 22.80 | 14.91 | 91882917.48 | 126.83 | 11-DEC-10:50 | 22.80 | 14.91 |
Annual Sum or Average | 0.129861E+12 | 0.115117E+10 | ||||||||
Minimum of Months | 0.155979E+10 | 1763.13 | 17.80 | 14.53 | 86404237.16 | 126.83 | 17.80 | 14.91 | ||
Maximum of Months | 0.187777E+11 | 7475.06 | 33.10 | 26.34 | 0.109064E+09 | 146.97 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242052E+12 | 93263.66 | 26-JAN-17:00 | 18.60 | 12.70 | 0.206241E+10 | 2748.31 | 26-JAN-10:09 | 18.60 | 12.70 |
February | 0.438517E+12 | 184654.02 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187105E+10 | 2749.06 | 09-FEB-14:09 | 25.40 | 15.70 |
March | 0.730499E+12 | 359055.49 | 31-MAR-23:55 | 23.70 | 16.75 | 0.223525E+10 | 2749.80 | 20-MAR-09:00 | 23.70 | 16.75 |
April | 0.935247E+12 | 368499.86 | 30-APR-04:25 | 23.15 | 16.67 | 0.240531E+10 | 4042.64 | 28-APR-13:00 | 23.15 | 16.67 |
May | 0.242997E+12 | 176393.40 | 31-MAY-24:00 | 28.10 | 22.60 | 0.214885E+10 | 2747.23 | 24-MAY-09:00 | 28.10 | 22.60 |
June | 0.472684E+12 | 268600.18 | 30-JUN-23:53 | 33.10 | 24.67 | 0.214278E+10 | 2746.95 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.735788E+12 | 356660.60 | 31-JUL-23:20 | 29.40 | 26.34 | 0.198927E+10 | 2746.02 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.968201E+12 | 370174.57 | 15-AUG-23:42 | 23.53 | 22.96 | 0.293185E+10 | 4080.82 | 07-AUG-13:00 | 23.53 | 22.96 |
September | 0.240152E+12 | 177659.37 | 30-SEP-23:57 | 26.60 | 21.92 | 0.198368E+10 | 2747.28 | 14-SEP-13:09 | 26.60 | 21.92 |
October | 0.491283E+12 | 269765.11 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206191E+10 | 2746.42 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.712021E+12 | 277910.77 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204191E+10 | 2749.69 | 28-NOV-10:30 | 18.60 | 13.96 |
December | 0.980015E+12 | 369240.37 | 18-DEC-17:00 | 20.00 | 14.42 | 0.199058E+10 | 2819.35 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.718946E+13 | 0.258649E+11 | ||||||||
Minimum of Months | 0.240152E+12 | 93263.66 | 17.80 | 12.70 | 0.187105E+10 | 2746.02 | 17.80 | 12.70 | ||
Maximum of Months | 0.980015E+12 | 370174.57 | 33.10 | 26.34 | 0.293185E+10 | 4080.82 | 33.10 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8049694.41 | 3663.36 | 14-JAN-17:25 | 20.25 |
February | 83368184.04 | 12149.16 | 20-FEB-14:14 | 26.37 |
March | 0.166097E+09 | 16532.80 | 11-MAR-17:03 | 29.70 |
April | 0.518994E+09 | 31142.00 | 15-APR-16:01 | 39.58 |
May | 0.710657E+09 | 34462.12 | 27-MAY-16:01 | 42.00 |
June | 0.681151E+09 | 36265.09 | 10-JUN-16:01 | 43.12 |
July | 0.811123E+09 | 29062.99 | 02-JUL-16:23 | 40.35 |
August | 0.527234E+09 | 25455.74 | 05-AUG-16:02 | 35.70 |
September | 0.664441E+09 | 23687.42 | 17-SEP-17:33 | 35.23 |
October | 0.566970E+09 | 24762.94 | 01-OCT-13:53 | 35.90 |
November | 0.192836E+09 | 15867.31 | 05-NOV-13:18 | 29.07 |
December | 31495917.66 | 8813.70 | 03-DEC-13:40 | 24.33 |
Annual Sum or Average | 0.496242E+10 | |||
Minimum of Months | 8049694.41 | 3663.36 | 20.25 | |
Maximum of Months | 0.811123E+09 | 36265.09 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233828E+09 | 64493.57 | 02-JAN-05:01 | 6.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.233828E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.48 | |
Maximum of Months | 0.233828E+09 | 64493.57 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 433814.66 | 1130.75 | 03-JAN-06:05 | 5.57 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 83834.71 | 698.62 | 21-DEC-06:06 | 5.27 |
Annual Sum or Average | 517649.37 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 433814.66 | 1130.75 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 244321.13 | 901.01 | 03-JAN-06:05 | 5.57 |
February | 43015.80 | 286.77 | 11-FEB-06:05 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 41605.77 | 231.68 | 22-DEC-06:05 | 12.42 |
Annual Sum or Average | 328942.70 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 244321.13 | 901.01 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80531.51 | 480.57 | 02-JAN-06:06 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 31984.91 | 213.23 | 23-DEC-06:08 | 5.43 |
Annual Sum or Average | 112516.42 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 80531.51 | 480.57 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505625E+09 | 17179.56 | 02-JAN-04:02 | 6.67 |
February | 60301533.50 | 14327.48 | 04-FEB-06:02 | 7.78 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 181013.25 | 742.94 | 27-NOV-06:05 | 9.55 |
December | 0.170307E+09 | 14845.21 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.736415E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.67 | |
Maximum of Months | 0.505625E+09 | 17179.56 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210004E+09 | 11787.61 | 02-JAN-05:01 | 6.48 |
February | 17189635.99 | 9470.21 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 54965318.80 | 9893.47 | 20-DEC-06:03 | 6.40 |
Annual Sum or Average | 0.282159E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.40 | |
Maximum of Months | 0.210004E+09 | 11787.61 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137425E+09 | 17041.18 | 02-JAN-05:01 | 6.48 |
February | 14497407.21 | 14128.22 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 22379420.45 | 13325.35 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.174302E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.48 | |
Maximum of Months | 0.137425E+09 | 17041.18 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131191E+09 | 11379.68 | 02-JAN-05:01 | 6.48 |
February | 8292336.12 | 8510.27 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 25962361.41 | 8737.48 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.165446E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.48 | |
Maximum of Months | 0.131191E+09 | 11379.68 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59220700.23 | 9411.37 | 17-JAN-04:02 | 11.75 |
February | 77845415.43 | 9550.20 | 13-FEB-04:02 | 11.62 |
March | 82302979.55 | 8690.29 | 03-MAR-04:02 | 14.92 |
April | 41449264.65 | 6309.04 | 16-APR-15:02 | 39.63 |
May | 36025898.01 | 7579.77 | 23-MAY-03:02 | 28.47 |
June | 37811145.81 | 6563.25 | 04-JUN-16:01 | 42.22 |
July | 49910519.56 | 6026.79 | 02-JUL-15:41 | 40.33 |
August | 46165281.90 | 6477.38 | 06-AUG-15:41 | 36.30 |
September | 71639402.74 | 8527.10 | 13-SEP-03:02 | 25.90 |
October | 81625566.20 | 7775.75 | 26-OCT-03:02 | 18.02 |
November | 90870731.76 | 8912.45 | 28-NOV-04:02 | 15.28 |
December | 0.109925E+09 | 10841.55 | 29-DEC-04:02 | 16.07 |
Annual Sum or Average | 0.784792E+09 | |||
Minimum of Months | 36025898.01 | 6026.79 | 11.62 | |
Maximum of Months | 0.109925E+09 | 10841.55 | 42.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34370014.13 | 7093.00 | 18-JAN-06:02 | 13.58 |
February | 44721500.75 | 6695.78 | 13-FEB-06:02 | 10.67 |
March | 42603449.79 | 6697.17 | 29-MAR-03:02 | 21.75 |
April | 39376739.03 | 7074.41 | 13-APR-03:02 | 24.18 |
May | 42532789.56 | 7369.92 | 24-MAY-03:02 | 26.12 |
June | 35547098.54 | 7746.17 | 21-JUN-03:02 | 28.25 |
July | 47632317.40 | 7895.84 | 28-JUL-03:02 | 27.00 |
August | 43395917.44 | 7794.93 | 17-AUG-03:02 | 27.35 |
September | 60371403.84 | 9482.42 | 11-SEP-03:02 | 26.07 |
October | 46609509.31 | 6272.34 | 11-OCT-03:02 | 24.45 |
November | 47317672.91 | 6053.09 | 28-NOV-05:03 | 15.20 |
December | 44673423.71 | 7001.54 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.529152E+09 | |||
Minimum of Months | 34370014.13 | 6053.09 | 10.67 | |
Maximum of Months | 60371403.84 | 9482.42 | 28.25 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199921E+10 | 19625.13 | 02-JAN-06:13 | 6.50 |
February | 0.829058E+09 | 18127.92 | 27-FEB-06:03 | 10.82 |
March | 0.268908E+09 | 18167.41 | 02-MAR-06:03 | 14.48 |
April | 84406077.46 | 14591.88 | 10-APR-03:02 | 18.93 |
May | 30622775.48 | 8915.54 | 15-MAY-03:02 | 24.47 |
June | 15463109.34 | 9329.55 | 28-JUN-03:02 | 26.40 |
July | 15816634.26 | 7666.38 | 19-JUL-03:02 | 23.42 |
August | 25025912.37 | 9533.76 | 21-AUG-03:02 | 25.87 |
September | 53254042.77 | 11374.94 | 27-SEP-03:02 | 24.65 |
October | 0.171129E+09 | 17446.18 | 31-OCT-05:02 | 15.53 |
November | 0.496991E+09 | 18362.36 | 06-NOV-06:03 | 14.70 |
December | 0.141157E+10 | 15886.20 | 29-DEC-06:03 | 16.53 |
Annual Sum or Average | 0.540146E+10 | |||
Minimum of Months | 15463109.34 | 7666.38 | 6.50 | |
Maximum of Months | 0.199921E+10 | 19625.13 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62637026.30 | 331.99 | 01-JAN-14:40 | 16.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 62637026.30 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 62637026.30 | 331.99 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196603E+11 | 20573.73 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.178333E+11 | 20573.73 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.211910E+11 | 20573.73 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.189279E+11 | 20573.73 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.204256E+11 | 20573.73 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.203269E+11 | 20573.73 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.190266E+11 | 20573.73 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.211910E+11 | 20573.73 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.189279E+11 | 20573.73 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.196603E+11 | 20573.73 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.194299E+11 | 20573.73 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.190266E+11 | 20573.73 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.235627E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.178333E+11 | 20573.73 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.211910E+11 | 20573.73 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.176563E+11 | 18476.66 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.160156E+11 | 18476.66 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.190310E+11 | 18476.66 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.169985E+11 | 18476.66 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.183436E+11 | 18476.66 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.182550E+11 | 18476.66 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.170872E+11 | 18476.66 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.190310E+11 | 18476.66 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.169985E+11 | 18476.66 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.176563E+11 | 18476.66 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.174494E+11 | 18476.66 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.170872E+11 | 18476.66 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.211610E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.160156E+11 | 18476.66 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.190310E+11 | 18476.66 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221693E+10 | 2319.93 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.201092E+10 | 2319.93 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.238953E+10 | 2319.93 | 01-MAR-08:09 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.213434E+10 | 2319.93 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.230323E+10 | 2319.93 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.229209E+10 | 2319.93 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.214547E+10 | 2319.93 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.238953E+10 | 2319.93 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.213434E+10 | 2319.93 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.221693E+10 | 2319.93 | 02-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.219094E+10 | 2319.93 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.214547E+10 | 2319.93 | 01-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.265697E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.201092E+10 | 2319.93 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.238953E+10 | 2319.93 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259981E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.221698E+10 | 2319.98 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.201096E+10 | 2319.98 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.238958E+10 | 2319.98 | 01-MAR-08:09 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.213438E+10 | 2319.98 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.230328E+10 | 2319.98 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.229214E+10 | 2319.98 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.214552E+10 | 2319.98 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.238958E+10 | 2319.98 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.213438E+10 | 2319.98 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.221698E+10 | 2319.98 | 02-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.219099E+10 | 2319.98 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.214552E+10 | 2319.98 | 01-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.265703E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.201096E+10 | 2319.98 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.238958E+10 | 2319.98 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142867E+10 | 1495.05 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.129591E+10 | 1495.05 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.153990E+10 | 1495.05 | 01-MAR-08:09 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.137545E+10 | 1495.05 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.148429E+10 | 1495.05 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.147711E+10 | 1495.05 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.138262E+10 | 1495.05 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.153990E+10 | 1495.05 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.137545E+10 | 1495.05 | 01-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.142867E+10 | 1495.05 | 02-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.141193E+10 | 1495.05 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.138262E+10 | 1495.05 | 01-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.171225E+11 | 0.259979E+11 | ||||
Minimum of Months | 0.129591E+10 | 1495.05 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.153990E+10 | 1495.05 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.364635E+09 | 381.58 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.330751E+09 | 381.58 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.393025E+09 | 381.58 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.351051E+09 | 381.58 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.378830E+09 | 381.58 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.376998E+09 | 381.58 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.352883E+09 | 381.58 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.393025E+09 | 381.58 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.351051E+09 | 381.58 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.364635E+09 | 381.58 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.360362E+09 | 381.58 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.352883E+09 | 381.58 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.437013E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.330751E+09 | 381.58 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.393025E+09 | 381.58 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554336E+10 | 5800.91 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.502824E+10 | 5800.91 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.597494E+10 | 5800.91 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.533685E+10 | 5800.91 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.575915E+10 | 5800.91 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.573131E+10 | 5800.91 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.536469E+10 | 5800.91 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.597494E+10 | 5800.91 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.533685E+10 | 5800.91 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.554336E+10 | 5800.91 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.547839E+10 | 5800.91 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.536469E+10 | 5800.91 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.664368E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.502824E+10 | 5800.91 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.597494E+10 | 5800.91 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.204256E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.203269E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.189279E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.196603E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.194299E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.190266E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.235627E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.178333E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.211910E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.176563E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.169985E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.183436E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.182550E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.170872E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.169985E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.176563E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.174494E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.170872E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.211610E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.160156E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.190310E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164344E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2788233.21 | 0.170740E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33981984.06 | 0.100230E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133949E+09 | 5465409.19 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284310E+09 | 1996343.00 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193424E+09 | 1115503.50 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247080E+09 | 399918.01 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142030E+09 | 447782.63 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81349608.45 | 2315558.34 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43074874.86 | 8142699.00 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9275018.64 | 35638771.11 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173424.04 | 0.148492E+09 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117144E+10 | 0.639327E+09 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399918.01 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284310E+09 | 0.170740E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110190E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1632550.89 | 0.114023E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22110528.20 | 64341819.21 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89316088.24 | 2986616.98 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189078E+09 | 1199105.85 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131904E+09 | 558956.32 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172008E+09 | 142439.27 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101176E+09 | 111120.82 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55572816.54 | 1150708.67 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27799375.36 | 5258373.14 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6069863.41 | 23774740.75 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119207.10 | 97030567.84 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796786E+09 | 0.420768E+09 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111120.82 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189078E+09 | 0.114023E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173096E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1568028.71 | 0.186279E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28697769.01 | 0.109635E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127692E+09 | 6103162.77 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282290E+09 | 2046208.30 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193518E+09 | 1127539.35 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246947E+09 | 383721.21 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141166E+09 | 482861.06 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78534530.84 | 2243836.59 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37487686.87 | 9180867.19 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6783140.12 | 40843982.34 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30798.28 | 0.161378E+09 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114472E+10 | 0.692800E+09 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383721.21 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282290E+09 | 0.186279E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119380E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107668.94 | 0.131991E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19133527.63 | 86024825.46 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80074764.87 | 7231162.22 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185061E+09 | 1975089.24 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124087E+09 | 1316539.83 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155263E+09 | 514848.82 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84137602.28 | 955787.26 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52136419.86 | 2770143.66 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26366442.27 | 6817972.03 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4934432.91 | 28272035.22 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20780.05 | 0.116571E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732322E+09 | 0.503821E+09 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514848.82 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185061E+09 | 0.131991E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243103.28 | 0.327125E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11189093.75 | 0.348396E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81492911.20 | 0.227639E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305737E+09 | 21028681.99 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644477E+09 | 5246836.33 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436806E+09 | 3848648.04 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539459E+09 | 1708382.38 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310745E+09 | 3384103.11 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180911E+09 | 6403835.51 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101333E+09 | 19614194.92 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26038037.94 | 74033368.64 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2887007.75 | 0.294681E+09 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264132E+10 | 0.133311E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243103.28 | 1708382.38 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644477E+09 | 0.348396E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18374.77 | 0.228267E+09 |
February | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4683817.49 | 0.247310E+09 |
March | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48421941.59 | 0.162114E+09 |
April | 0.688021E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194766E+09 | 16086438.87 |
May | 0.744847E+09 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426070E+09 | 3652274.29 |
June | 0.742030E+09 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293241E+09 | 2585722.32 |
July | 0.690839E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363348E+09 | 1088199.18 |
August | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208095E+09 | 2275862.75 |
September | 0.688021E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120555E+09 | 3969672.30 |
October | 0.715730E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62822628.43 | 14091063.57 |
November | 0.708685E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14788112.14 | 53274301.98 |
December | 0.690839E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1036950.96 | 0.207477E+09 |
Annual Sum or Average | 0.858171E+10 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173785E+10 | 0.942192E+09 |
Minimum of Months | 0.649041E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18374.77 | 1088199.18 |
Maximum of Months | 0.773965E+09 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426070E+09 | 0.247310E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391623E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3336507.10 | 0.423833E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63862432.52 | 0.266765E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289213E+09 | 24703126.43 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641329E+09 | 5485338.29 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437594E+09 | 3759206.33 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539519E+09 | 1708792.70 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306481E+09 | 3537976.73 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173329E+09 | 6976207.56 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84926975.34 | 23769280.39 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15074251.00 | 95438476.99 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52504.63 | 0.367634E+09 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255472E+10 | 0.161523E+10 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1708792.70 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641329E+09 | 0.423833E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.89 | 0.234224E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3817617.64 | 0.252926E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47012612.16 | 0.176116E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192536E+09 | 18852352.21 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422116E+09 | 4842031.66 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286595E+09 | 3325547.22 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355306E+09 | 1409018.27 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202405E+09 | 2909731.93 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117784E+09 | 5150963.95 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62971254.10 | 14302465.62 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14461861.93 | 53267062.64 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 704312.07 | 0.212864E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170571E+10 | 0.980189E+09 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.89 | 1409018.27 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422116E+09 | 0.252926E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.221693E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624796.76 | 0.335823E+09 |
February | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17522558.19 | 0.379217E+09 |
March | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100661E+09 | 0.267639E+09 |
April | 0.145243E+10 | 0.213434E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372097E+09 | 25062782.54 |
May | 0.157338E+10 | 0.230323E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787236E+09 | 7015517.41 |
June | 0.156900E+10 | 0.229209E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533736E+09 | 5541595.55 |
July | 0.145680E+10 | 0.214547E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659013E+09 | 2115234.07 |
August | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377445E+09 | 4724454.05 |
September | 0.145243E+10 | 0.213434E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222175E+09 | 7893935.85 |
October | 0.150991E+10 | 0.221693E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124187E+09 | 22923237.05 |
November | 0.149516E+10 | 0.219094E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35755173.88 | 81537518.76 |
December | 0.145680E+10 | 0.214547E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5352829.63 | 0.309568E+09 |
Annual Sum or Average | 0.181194E+11 | 0.265697E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323581E+10 | 0.144906E+10 |
Minimum of Months | 0.136985E+10 | 0.201092E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624796.76 | 2115234.07 |
Maximum of Months | 0.163685E+10 | 0.238953E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787236E+09 | 0.379217E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119836.20 | 0.240850E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6731529.44 | 0.279284E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57751557.82 | 0.197213E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235215E+09 | 20079381.87 |
May | 0.101394E+10 | 0.148429E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516562E+09 | 5104009.19 |
June | 0.101113E+10 | 0.147711E+10 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355682E+09 | 3782653.06 |
July | 0.938820E+09 | 0.138262E+10 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440600E+09 | 1386989.10 |
August | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250711E+09 | 3204095.37 |
September | 0.936002E+09 | 0.137545E+10 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146823E+09 | 5097619.34 |
October | 0.973041E+09 | 0.142867E+10 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75499613.98 | 17130930.07 |
November | 0.963541E+09 | 0.141193E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18947392.34 | 61597450.19 |
December | 0.938820E+09 | 0.138262E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1672340.15 | 0.224925E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210632E+10 | 0.105966E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119836.20 | 1386989.10 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516562E+09 | 0.279284E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.221698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430798E+09 |
February | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3737708.21 | 0.484623E+09 |
March | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77143461.27 | 0.323030E+09 |
April | 0.145246E+10 | 0.213438E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353439E+09 | 30344413.39 |
May | 0.157341E+10 | 0.230328E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782754E+09 | 7332779.88 |
June | 0.156904E+10 | 0.229214E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534267E+09 | 5450667.43 |
July | 0.145684E+10 | 0.214552E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658830E+09 | 2121205.66 |
August | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372522E+09 | 4933525.35 |
September | 0.145246E+10 | 0.213438E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213237E+09 | 8802443.81 |
October | 0.150994E+10 | 0.221698E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103715E+09 | 28782018.23 |
November | 0.149520E+10 | 0.219099E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18045329.91 | 0.112285E+09 |
December | 0.145684E+10 | 0.214552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44738.46 | 0.411790E+09 |
Annual Sum or Average | 0.181198E+11 | 0.265703E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311774E+10 | 0.185029E+10 |
Minimum of Months | 0.136988E+10 | 0.201096E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2121205.66 |
Maximum of Months | 0.163688E+10 | 0.238958E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782754E+09 | 0.484623E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.142867E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36945.96 | 0.255581E+09 |
February | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5853151.24 | 0.287230E+09 |
March | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57792397.88 | 0.212149E+09 |
April | 0.936002E+09 | 0.137545E+10 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236531E+09 | 23128226.06 |
May | 0.101394E+10 | 0.148429E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517450E+09 | 6260188.62 |
June | 0.101113E+10 | 0.147711E+10 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352112E+09 | 4538233.76 |
July | 0.938820E+09 | 0.138262E+10 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437663E+09 | 1745447.38 |
August | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247829E+09 | 3939627.24 |
September | 0.936002E+09 | 0.137545E+10 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145929E+09 | 6335888.70 |
October | 0.973041E+09 | 0.142867E+10 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77630669.75 | 17101511.03 |
November | 0.963541E+09 | 0.141193E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19071287.70 | 61231174.59 |
December | 0.938820E+09 | 0.138262E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1056217.88 | 0.235877E+09 |
Annual Sum or Average | 0.116768E+11 | 0.171225E+11 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209895E+10 | 0.111512E+10 |
Minimum of Months | 0.882782E+09 | 0.129591E+10 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36945.96 | 1745447.38 |
Maximum of Months | 0.105485E+10 | 0.153990E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517450E+09 | 0.287230E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.364635E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.330751E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.393025E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.351051E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.378830E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.376998E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.352883E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.393025E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.351051E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.364635E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.360362E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.352883E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.437013E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.330751E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.393025E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.554336E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.502824E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.597494E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.533685E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.575915E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.573131E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.536469E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.597494E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.533685E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.554336E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.547839E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.536469E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.664368E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.502824E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.597494E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361949E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1787708.92 | 0.383432E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52678986.46 | 0.234931E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238595E+09 | 17920071.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530172E+09 | 5149526.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359540E+09 | 2684466.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453264E+09 | 1261809.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249433E+09 | 1909786.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143404E+09 | 3732437.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73158529.44 | 20183544.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12066340.71 | 83280188.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334181E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211410E+10 | 0.145061E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1261809.60 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530172E+09 | 0.383432E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614282E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4850085.93 | 0.651882E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97464255.11 | 0.411421E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429499E+09 | 35883345.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950234E+09 | 9184332.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643090E+09 | 5036848.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809586E+09 | 2377083.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448135E+09 | 3963495.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254956E+09 | 6748895.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132164E+09 | 36250512.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23967686.50 | 0.141669E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336560.76 | 0.558666E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379428E+10 | 0.247737E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2377083.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950234E+09 | 0.651882E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591394E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175685.19 | 0.661187E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80815940.76 | 0.433952E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425291E+09 | 34426129.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100868E+10 | 10745809.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691483E+09 | 6559940.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844671E+09 | 2466655.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464707E+09 | 6579297.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259827E+09 | 8771727.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124766E+09 | 35520464.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18305962.77 | 0.139480E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444463.66 | 0.536237E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392016E+10 | 0.246732E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2466655.23 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100868E+10 | 0.661187E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 20573.73 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 20573.73 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 20573.73 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 20573.73 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 20573.73 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 20573.73 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 20573.73 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 20573.73 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 20573.73 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 20573.73 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 20573.73 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 20573.73 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 20573.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 18476.66 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 18476.66 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 18476.66 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 18476.66 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 18476.66 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 18476.66 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 18476.66 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 18476.66 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 18476.66 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 18476.66 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 18476.66 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 18476.66 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 18476.66 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 422.72 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.02 | 19-FEB-15:10 | 556.34 | 09-FEB-22:20 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 371.54 | 26-MAR-15:00 | 1175.68 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.84 | 15-APR-17:02 | 176.29 | 22-APR-17:50 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.21 | 28-MAY-14:54 | 87.85 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.83 | 17-JUN-20:30 | 85.69 | 18-JUN-03:40 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.25 | 02-JUL-11:47 | 72.20 | 19-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.02 | 06-AUG-13:47 | 72.57 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.93 | 24-SEP-14:30 | 51.09 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.43 | 15-OCT-12:10 | 173.53 | 12-OCT-02:20 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.70 | 12-NOV-14:30 | 279.75 | 28-NOV-04:43 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 24-DEC-14:20 | 650.72 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.21 | 1175.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 275.92 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 19-FEB-15:10 | 354.08 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.68 | 26-MAR-15:00 | 770.71 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.19 | 15-APR-17:10 | 106.58 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.42 | 28-MAY-14:54 | 59.20 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.06 | 17-JUN-20:30 | 49.48 | 18-JUN-03:40 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.07 | 02-JUL-11:45 | 38.62 | 19-JUL-02:10 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.19 | 06-AUG-13:50 | 37.09 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.41 | 24-SEP-14:30 | 28.79 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.19 | 15-OCT-12:50 | 108.21 | 12-OCT-02:20 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.52 | 12-NOV-14:30 | 180.41 | 28-NOV-04:43 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 | 24-DEC-14:20 | 408.37 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.79 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 728.42 | 770.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 432.27 | 22-JAN-14:58 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 21-FEB-15:00 | 548.55 | 09-FEB-22:20 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.75 | 26-MAR-15:36 | 1268.71 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.93 | 15-APR-17:02 | 186.65 | 22-APR-17:50 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.37 | 28-MAY-14:54 | 95.40 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.27 | 17-JUN-20:30 | 87.04 | 18-JUN-03:40 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.17 | 02-JUL-11:45 | 71.29 | 19-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.36 | 06-AUG-13:45 | 74.57 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.25 | 24-SEP-14:28 | 49.17 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.52 | 15-OCT-12:05 | 173.20 | 12-OCT-02:20 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.30 | 12-NOV-13:45 | 303.37 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 28-DEC-14:00 | 730.15 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.37 | 1268.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 303.65 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 21-FEB-15:00 | 408.60 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.96 | 26-MAR-14:16 | 1051.55 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.20 | 15-APR-17:05 | 205.73 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.35 | 28-MAY-14:53 | 83.74 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.22 | 04-JUN-12:48 | 86.26 | 18-JUN-03:40 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.30 | 02-JUL-11:47 | 72.50 | 19-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.21 | 06-AUG-09:06 | 85.66 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.79 | 24-SEP-14:28 | 48.49 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.80 | 15-OCT-12:10 | 142.38 | 12-OCT-02:20 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.46 | 12-NOV-13:45 | 229.22 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28-DEC-14:00 | 519.57 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 737.35 | 1051.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 08-JAN-14:33 | 832.69 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 361.50 | 19-FEB-15:10 | 1155.27 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 922.32 | 26-MAR-14:40 | 2149.25 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1534.12 | 15-APR-17:02 | 360.77 | 22-APR-18:20 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2536.93 | 28-MAY-14:44 | 190.13 | 13-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.38 | 03-JUN-17:02 | 206.50 | 18-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.12 | 02-JUL-11:28 | 190.77 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 842.69 | 06-AUG-08:52 | 222.19 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.03 | 24-SEP-15:00 | 96.06 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 894.97 | 15-OCT-12:10 | 368.01 | 12-OCT-02:53 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.58 | 12-NOV-14:30 | 598.62 | 28-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.25 | 24-DEC-13:53 | 1256.18 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 96.06 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2536.93 | 2149.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 08-JAN-14:33 | 553.14 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.11 | 19-FEB-15:10 | 744.38 | 18-FEB-05:53 |
March | 1239.33 | 01-MAR-08:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 551.08 | 26-MAR-15:00 | 1517.98 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.47 | 15-APR-17:02 | 271.52 | 22-APR-18:10 |
May | 1239.33 | 01-MAY-07:10 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.68 | 28-MAY-14:44 | 134.10 | 15-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 835.81 | 17-JUN-20:40 | 136.49 | 18-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 826.79 | 02-JUL-11:28 | 124.19 | 19-JUL-02:53 |
August | 1239.33 | 01-AUG-07:10 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 564.19 | 06-AUG-14:00 | 152.43 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.10 | 24-SEP-14:57 | 57.91 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.97 | 15-OCT-12:50 | 244.26 | 12-OCT-02:53 |
November | 1239.33 | 01-NOV-07:10 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.32 | 12-NOV-14:30 | 411.27 | 28-NOV-04:53 |
December | 1239.33 | 01-DEC-08:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 24-DEC-14:20 | 820.30 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 57.91 | |||||
Maximum of Months | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.68 | 1517.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1025.07 | 22-JAN-14:58 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.75 | 21-FEB-15:00 | 1184.66 | 18-FEB-05:53 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.46 | 26-MAR-15:36 | 2466.53 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.50 | 15-APR-17:02 | 405.10 | 22-APR-18:10 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2526.24 | 28-MAY-14:52 | 197.32 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.63 | 03-JUN-17:02 | 204.26 | 18-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.92 | 02-JUL-11:28 | 190.11 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.74 | 06-AUG-08:52 | 227.79 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 683.00 | 24-SEP-14:55 | 97.21 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 683.01 | 15-OCT-13:00 | 380.98 | 12-OCT-02:53 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 | 13-NOV-14:00 | 684.85 | 28-NOV-04:53 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 28-DEC-14:00 | 1683.59 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.21 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2526.24 | 2466.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 08-JAN-13:53 | 576.38 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.85 | 19-FEB-13:50 | 765.79 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 548.30 | 26-MAR-13:00 | 1671.12 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 950.20 | 15-APR-17:08 | 282.31 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1674.89 | 28-MAY-14:55 | 174.61 | 15-MAY-01:53 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 787.58 | 04-JUN-13:16 | 163.05 | 18-JUN-04:13 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.62 | 02-JUL-11:30 | 134.18 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 595.23 | 06-AUG-09:20 | 165.67 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 466.76 | 24-SEP-14:16 | 65.38 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.03 | 15-OCT-12:10 | 255.27 | 12-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.51 | 12-NOV-13:10 | 427.86 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.36 | 24-DEC-13:53 | 856.95 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 65.38 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1674.89 | 1671.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2319.93 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.13 | 08-JAN-15:00 | 867.33 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2319.93 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 496.85 | 19-FEB-15:00 | 1299.29 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2319.93 | 01-MAR-08:09 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.36 | 26-MAR-14:50 | 2415.06 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 2319.93 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.15 | 15-APR-17:02 | 405.93 | 22-APR-18:23 |
May | 2010.79 | 01-MAY-09:09 | 2319.93 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3087.95 | 28-MAY-15:05 | 314.60 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 2319.93 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478.44 | 03-JUN-17:02 | 280.45 | 18-JUN-04:13 |
July | 2010.79 | 03-JUL-09:09 | 2319.93 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.30 | 02-JUL-11:56 | 230.22 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 2319.93 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.81 | 06-AUG-09:20 | 301.33 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2319.93 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 884.58 | 24-SEP-14:57 | 105.82 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2319.93 | 02-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.42 | 15-OCT-12:30 | 426.52 | 12-OCT-02:53 |
November | 2010.79 | 01-NOV-09:09 | 2319.93 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.59 | 12-NOV-14:00 | 650.12 | 28-NOV-04:53 |
December | 2010.79 | 01-DEC-10:09 | 2319.93 | 01-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 400.90 | 24-DEC-13:50 | 1364.18 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 117.13 | 105.82 | |||||
Maximum of Months | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3087.95 | 2415.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 | 08-JAN-15:00 | 576.75 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 248.75 | 19-FEB-15:20 | 858.21 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.12 | 26-MAR-15:10 | 1742.91 | 24-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.83 | 15-APR-17:02 | 317.44 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2058.92 | 28-MAY-15:05 | 233.65 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 981.29 | 03-JUN-17:02 | 188.02 | 18-JUN-04:13 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.29 | 02-JUL-11:56 | 150.50 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 693.71 | 06-AUG-13:58 | 206.96 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 590.29 | 24-SEP-14:18 | 65.68 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.32 | 15-OCT-12:30 | 285.11 | 12-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.40 | 12-NOV-14:00 | 455.98 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.25 | 24-DEC-14:20 | 903.58 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 | 65.68 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2058.92 | 1742.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2319.98 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1158.61 | 22-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 2319.98 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 21-FEB-15:00 | 1344.92 | 18-FEB-05:53 |
March | 2010.83 | 01-MAR-10:09 | 2319.98 | 01-MAR-08:09 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 782.51 | 26-MAR-15:08 | 2866.03 | 24-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 2319.98 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.09 | 15-APR-17:02 | 466.88 | 22-APR-18:15 |
May | 2010.83 | 01-MAY-09:09 | 2319.98 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3090.59 | 28-MAY-15:05 | 334.37 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 2319.98 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1490.60 | 03-JUN-17:02 | 278.06 | 18-JUN-04:13 |
July | 2010.83 | 03-JUL-09:09 | 2319.98 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.46 | 02-JUL-11:56 | 229.38 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 2319.98 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.43 | 06-AUG-09:20 | 308.85 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2319.98 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 852.24 | 24-SEP-14:57 | 107.70 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2319.98 | 02-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.30 | 15-OCT-12:50 | 444.53 | 12-OCT-02:53 |
November | 2010.83 | 01-NOV-09:09 | 2319.98 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.41 | 12-NOV-13:55 | 775.83 | 28-NOV-04:53 |
December | 2010.83 | 01-DEC-10:09 | 2319.98 | 01-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 28-DEC-14:00 | 1850.38 | 31-DEC-14:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.70 | |||||
Maximum of Months | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3090.59 | 2866.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1495.05 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 | 08-JAN-13:53 | 624.73 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1495.05 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.53 | 19-FEB-14:12 | 878.40 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1495.05 | 01-MAR-08:09 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 693.43 | 26-MAR-13:10 | 1931.49 | 24-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1495.05 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.63 | 15-APR-17:08 | 322.96 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 1495.05 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2060.00 | 28-MAY-15:05 | 270.19 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 1495.05 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 956.29 | 04-JUN-13:00 | 216.48 | 18-JUN-03:53 |
July | 1295.83 | 03-JUL-09:09 | 1495.05 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.58 | 02-JUL-11:58 | 161.82 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1495.05 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.06 | 06-AUG-09:20 | 221.75 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1495.05 | 01-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.41 | 24-SEP-14:16 | 72.34 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1495.05 | 02-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 757.12 | 15-OCT-12:30 | 298.24 | 12-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 1495.05 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.77 | 12-NOV-13:20 | 481.08 | 28-NOV-04:53 |
December | 1295.83 | 01-DEC-10:09 | 1495.05 | 01-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.05 | 24-DEC-13:50 | 946.13 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 | 72.34 | |||||
Maximum of Months | 1295.83 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2060.00 | 1931.49 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 381.58 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 381.58 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 381.58 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 381.58 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 381.58 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 381.58 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 381.58 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 381.58 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 381.58 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 381.58 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 381.58 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 381.58 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5800.91 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5800.91 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5800.91 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5800.91 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5800.91 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5800.91 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5800.91 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5800.91 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5800.91 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5800.91 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5800.91 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5800.91 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 878.75 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.60 | 19-FEB-14:52 | 1249.02 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.95 | 26-MAR-14:42 | 2546.68 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1283.76 | 15-APR-17:02 | 373.85 | 22-APR-17:56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.19 | 28-MAY-15:00 | 162.30 | 15-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.07 | 03-JUN-17:02 | 165.77 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.08 | 02-JUL-12:00 | 139.48 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.41 | 06-AUG-14:00 | 140.56 | 15-AUG-23:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.46 | 24-SEP-14:10 | 69.90 | 08-SEP-22:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.82 | 15-OCT-12:30 | 335.00 | 12-OCT-02:26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.63 | 12-NOV-14:10 | 632.54 | 28-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1387.41 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.19 | 2546.68 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1474.67 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.49 | 19-FEB-14:52 | 2174.42 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.50 | 26-MAR-14:42 | 4247.92 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2337.82 | 15-APR-17:02 | 632.63 | 22-APR-18:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3914.50 | 28-MAY-15:00 | 278.57 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.44 | 03-JUN-17:02 | 297.06 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.58 | 02-JUL-11:50 | 261.14 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1295.10 | 06-AUG-14:10 | 275.49 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.33 | 24-SEP-14:00 | 122.55 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1207.80 | 15-OCT-12:30 | 582.24 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.93 | 12-NOV-14:10 | 1090.18 | 28-NOV-05:07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.37 | 24-DEC-14:00 | 2345.86 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3914.50 | 4247.92 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1426.02 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.49 | 19-FEB-15:00 | 2212.14 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.59 | 26-MAR-14:50 | 4040.12 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.12 | 15-APR-17:02 | 541.26 | 22-APR-18:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3795.15 | 28-MAY-14:50 | 358.31 | 15-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1969.31 | 03-JUN-17:10 | 365.37 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.68 | 02-JUL-10:52 | 279.39 | 19-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.98 | 06-AUG-08:52 | 399.07 | 15-AUG-23:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.73 | 24-SEP-14:00 | 117.07 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.99 | 15-OCT-12:02 | 621.04 | 12-OCT-02:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.39 | 12-NOV-14:20 | 1019.58 | 28-NOV-04:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.72 | 24-DEC-13:53 | 2226.71 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3795.15 | 4040.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 109953.05 | 02-JAN-05:01 | 0.00 | 16001.00 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 108123.71 | 21-FEB-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 102952.08 | 06-MAR-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110099.59 | 10-APR-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 101656.10 | 29-MAY-17:44 | 0.00 | 8001.39 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96617.74 | 04-JUN-16:07 | 8078.51 | 10287.50 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91735.13 | 04-JUL-16:49 | 7180.90 | 9144.45 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90561.75 | 29-AUG-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90582.27 | 26-SEP-03:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99875.51 | 22-OCT-14:58 | 5385.68 | 6858.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 103820.26 | 21-NOV-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 109589.38 | 20-DEC-04:02 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90561.75 | 0.00 | 5715.28 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 110099.59 | 8078.51 | 16001.00 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 100045.93 | 02-JAN-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98603.12 | 27-FEB-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94557.51 | 20-MAR-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90569.92 | 17-APR-05:02 | 9673.43 | 12317.16 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90058.30 | 01-MAY-05:02 | 9673.43 | 12317.16 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88728.92 | 12-JUN-05:02 | 9673.43 | 12317.16 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90553.46 | 24-JUL-05:04 | 8061.19 | 10264.30 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87991.20 | 07-AUG-05:01 | 11285.67 | 14370.03 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92150.67 | 11-SEP-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96582.38 | 30-OCT-03:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98407.65 | 27-NOV-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98430.92 | 18-DEC-04:02 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87991.20 | 0.00 | 5132.72 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100045.93 | 11285.67 | 14370.03 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84424.13 | 17-JAN-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88254.76 | 27-FEB-04:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88472.03 | 14-MAR-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88239.72 | 10-APR-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84626.11 | 23-MAY-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84809.06 | 28-JUN-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87996.20 | 19-JUL-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84515.78 | 24-AUG-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85768.24 | 05-SEP-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87880.13 | 24-OCT-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87813.40 | 13-NOV-04:03 | 0.00 | 4106.18 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 84392.77 | 16-DEC-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84392.77 | 0.00 | 4106.18 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88472.03 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 42260.04 | 26-JAN-06:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84044.12 | 23-FEB-06:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91088.90 | 13-MAR-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87798.55 | 10-APR-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88533.31 | 15-MAY-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88336.62 | 01-JUN-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87911.66 | 28-JUL-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90291.38 | 21-AUG-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91024.58 | 11-SEP-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89909.26 | 10-OCT-03:02 | 0.00 | 5132.72 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85108.02 | 01-NOV-05:02 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65065.87 | 29-DEC-06:03 | 6448.95 | 8211.44 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 42260.04 | 0.00 | 5132.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91088.90 | 8061.19 | 10264.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5659.15 | 26-JAN-14:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
February | 7464.08 | 23-FEB-14:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 0.00 |
March | 14256.93 | 14-MAR-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 |
April | 17530.77 | 17-APR-05:02 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
May | 20801.30 | 29-MAY-15:11 | 1012.16 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 532.10 | 0.00 |
June | 20900.03 | 11-JUN-16:21 | 1012.16 | 1288.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 194.37 | 0.00 |
July | 21827.95 | 02-JUL-17:01 | 0.00 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 295.02 | 0.00 |
August | 20564.24 | 06-AUG-15:41 | 809.73 | 1031.14 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 295.52 | 0.00 |
September | 17282.52 | 05-SEP-03:02 | 0.00 | 644.46 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
October | 15702.72 | 10-OCT-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10663.63 | 13-NOV-06:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
December | 6604.70 | 26-DEC-14:10 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5659.15 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21827.95 | 2010.79 | 2319.93 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 532.10 | 18.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4802.94 | 26-JAN-10:20 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 |
February | 7771.10 | 20-FEB-08:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.08 |
March | 12130.24 | 26-MAR-09:32 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 |
April | 16568.89 | 30-APR-08:22 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
May | 17457.72 | 29-MAY-07:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 278.35 | 0.00 |
June | 16516.92 | 11-JUN-10:21 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 112.06 | 0.00 |
July | 16737.90 | 02-JUL-15:41 | 587.05 | 747.57 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 206.98 | 0.00 |
August | 16257.30 | 06-AUG-10:22 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 181.06 | 0.00 |
September | 12009.72 | 17-SEP-10:53 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 0.00 |
October | 16466.91 | 01-OCT-09:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
November | 7063.76 | 13-NOV-09:50 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
December | 5299.21 | 01-DEC-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4802.94 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17457.72 | 1295.83 | 1495.05 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 278.35 | 100.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14104.92 | 08-JAN-15:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 |
February | 22276.92 | 20-FEB-14:12 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
March | 21857.17 | 26-MAR-13:32 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 171.07 | 0.00 |
April | 21437.70 | 30-APR-11:42 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 305.47 | 0.00 |
May | 21336.22 | 29-MAY-15:11 | 1012.19 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 527.76 | 0.00 |
June | 21231.72 | 11-JUN-16:21 | 1012.19 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 194.63 | 0.00 |
July | 22169.29 | 02-JUL-16:21 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 307.14 | 0.00 |
August | 21137.47 | 06-AUG-15:41 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 290.96 | 0.00 |
September | 21983.54 | 17-SEP-13:32 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 225.67 | 0.00 |
October | 23472.36 | 01-OCT-14:31 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 120.42 | 0.00 |
November | 23213.46 | 12-NOV-13:02 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 |
December | 21780.31 | 03-DEC-12:43 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14104.92 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23472.36 | 1012.19 | 1288.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 527.76 | 62.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7617.88 | 31-JAN-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
February | 17729.33 | 20-FEB-14:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 |
March | 21717.53 | 26-MAR-14:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 133.39 | 0.00 |
April | 23045.62 | 30-APR-16:21 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 274.10 | 0.00 |
May | 22604.85 | 28-MAY-16:11 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 593.02 | 0.00 |
June | 22791.25 | 11-JUN-16:21 | 652.28 | 830.63 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 120.34 | 0.00 |
July | 24742.71 | 02-JUL-16:21 | 587.05 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 0.00 |
August | 22680.82 | 06-AUG-15:41 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 169.70 | 0.00 |
September | 22038.63 | 17-SEP-16:12 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 0.00 |
October | 22997.69 | 01-OCT-15:51 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 | 0.00 |
November | 21319.25 | 12-NOV-15:02 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 |
December | 16170.44 | 29-DEC-06:03 | 521.82 | 664.43 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7617.88 | 326.14 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24742.71 | 1239.33 | 1495.05 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 593.02 | 92.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4271.14 | 26-JAN-14:50 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
February | 6356.75 | 24-FEB-15:00 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 43.20 | 0.00 |
March | 14711.07 | 30-MAR-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 |
April | 15549.65 | 28-APR-05:02 | 1214.60 | 1546.54 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 0.00 |
May | 22240.26 | 28-MAY-16:01 | 910.95 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2130.31 | 0.00 |
June | 21616.81 | 11-JUN-16:51 | 809.73 | 1031.14 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 411.76 | 0.00 |
July | 20348.39 | 02-JUL-16:42 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 764.93 | 0.00 |
August | 17148.30 | 01-AUG-03:02 | 0.00 | 644.46 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 100.75 | 0.00 |
September | 16784.09 | 11-SEP-03:02 | 0.00 | 644.46 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14821.69 | 03-OCT-05:03 | 809.73 | 1031.03 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 6700.90 | 09-NOV-14:30 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
December | 4430.30 | 03-DEC-13:32 | 404.87 | 515.57 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4271.14 | 0.00 | 515.57 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22240.26 | 2010.79 | 2319.93 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2130.31 | 49.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3833.43 | 26-JAN-11:10 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 |
February | 6508.01 | 22-FEB-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
March | 11556.30 | 26-MAR-10:13 | 260.91 | 332.25 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.81 |
April | 18484.46 | 30-APR-09:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 0.00 |
May | 19126.18 | 29-MAY-09:01 | 456.59 | 581.44 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 885.88 | 0.00 |
June | 17994.09 | 11-JUN-09:32 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 182.30 | 0.00 |
July | 17057.44 | 04-JUL-10:12 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 339.15 | 0.00 |
August | 12948.97 | 07-AUG-05:01 | 913.19 | 1162.76 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 | 0.00 |
September | 16998.20 | 24-SEP-10:12 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 0.00 |
October | 17452.10 | 01-OCT-09:52 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 42.70 | 0.00 |
November | 6490.33 | 09-NOV-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
December | 4390.08 | 01-DEC-10:00 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3833.43 | 260.91 | 332.25 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19126.18 | 1239.33 | 1495.05 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 885.88 | 62.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18370.66 | 08-JAN-15:02 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.60 |
February | 21360.07 | 20-FEB-12:32 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 |
March | 21720.60 | 26-MAR-14:12 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 418.47 | 0.00 |
April | 21988.83 | 16-APR-12:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 308.56 | 0.00 |
May | 22507.48 | 28-MAY-16:01 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.70 | 0.00 |
June | 21570.00 | 11-JUN-16:51 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 416.04 | 0.00 |
July | 20439.90 | 02-JUL-16:42 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 768.23 | 0.00 |
August | 17542.28 | 06-AUG-14:32 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 768.02 | 0.00 |
September | 22049.03 | 24-SEP-14:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 559.13 | 0.00 |
October | 23566.11 | 01-OCT-14:31 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 268.66 | 0.00 |
November | 23105.96 | 05-NOV-13:12 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 0.00 |
December | 21413.38 | 03-DEC-12:53 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17542.28 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23566.11 | 910.97 | 1160.06 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.70 | 151.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5583.35 | 31-JAN-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 |
February | 7848.36 | 21-FEB-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | 0.00 |
March | 14285.56 | 26-MAR-14:52 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 388.44 | 0.00 |
April | 20161.86 | 02-APR-16:01 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 456.54 | 0.00 |
May | 21856.19 | 28-MAY-16:01 | 587.05 | 747.57 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.94 | 0.00 |
June | 20975.54 | 11-JUN-16:51 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 246.04 | 0.00 |
July | 18989.50 | 02-JUL-16:42 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 475.38 | 0.00 |
August | 18560.79 | 06-AUG-16:32 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 388.76 | 0.00 |
September | 19022.28 | 24-SEP-14:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 378.02 | 0.00 |
October | 19789.08 | 01-OCT-15:51 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 132.41 | 0.00 |
November | 9517.56 | 05-NOV-15:12 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | 0.00 |
December | 5985.47 | 01-DEC-15:30 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5583.35 | 326.14 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21856.19 | 1239.33 | 1495.05 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.94 | 35.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4195.55 | 26-JAN-15:10 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 |
February | 6471.70 | 23-FEB-14:50 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 | 0.00 |
March | 12451.03 | 30-MAR-05:02 | 1012.16 | 1288.79 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
April | 24250.56 | 16-APR-15:31 | 910.95 | 1160.04 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 249.33 | 0.00 |
May | 25121.71 | 28-MAY-16:21 | 708.51 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2639.05 | 0.00 |
June | 24736.88 | 11-JUN-16:31 | 708.51 | 902.25 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 542.52 | 0.00 |
July | 24886.18 | 02-JUL-16:31 | 809.73 | 1031.14 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 903.98 | 0.00 |
August | 23810.23 | 13-AUG-16:11 | 809.73 | 1031.14 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 563.02 | 0.00 |
September | 24090.45 | 24-SEP-14:52 | 607.30 | 773.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 771.08 | 0.00 |
October | 11690.53 | 11-OCT-03:02 | 0.00 | 644.46 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 |
November | 7095.84 | 09-NOV-14:40 | 2010.79 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 37.52 | 0.00 |
December | 4178.71 | 28-DEC-16:00 | 1923.11 | 2319.93 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4178.71 | 0.00 | 644.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25121.71 | 2010.79 | 2319.93 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2639.05 | 63.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3412.75 | 26-JAN-14:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 |
February | 6051.44 | 23-FEB-10:40 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
March | 9609.36 | 28-MAR-10:20 | 1239.33 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 0.00 |
April | 19166.83 | 16-APR-12:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 251.68 | 0.00 |
May | 19395.21 | 29-MAY-09:22 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.99 | 0.00 |
June | 18549.45 | 11-JUN-10:32 | 326.14 | 415.32 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 337.35 | 0.00 |
July | 19728.36 | 02-JUL-09:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 672.24 | 0.00 |
August | 17496.09 | 13-AUG-15:31 | 521.82 | 664.51 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 381.06 | 0.00 |
September | 18541.12 | 24-SEP-14:52 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 489.58 | 0.00 |
October | 13830.46 | 09-OCT-15:32 | 391.37 | 498.38 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 108.44 | 0.00 |
November | 6162.16 | 09-NOV-10:30 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
December | 3500.93 | 01-DEC-15:00 | 1295.83 | 1495.05 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3412.75 | 326.14 | 415.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19728.36 | 1295.83 | 1495.05 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.99 | 41.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12638.36 | 12-JAN-14:20 | 2010.83 | 2319.98 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
February | 25187.39 | 20-FEB-14:22 | 506.09 | 644.48 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
March | 19961.88 | 12-MAR-14:23 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 112.97 | 0.00 |
April | 26196.78 | 16-APR-12:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 366.34 | 0.00 |
May | 25264.49 | 28-MAY-15:41 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.84 | 0.00 |
June | 24666.94 | 11-JUN-16:31 | 708.53 | 902.27 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 545.16 | 0.00 |
July | 24888.07 | 02-JUL-16:31 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 906.45 | 0.00 |
August | 24291.01 | 13-AUG-14:51 | 809.75 | 1031.17 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 549.97 | 0.00 |
September | 26222.68 | 24-SEP-14:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 653.69 | 0.00 |
October | 27151.76 | 09-OCT-12:52 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 63.38 | 0.00 |
November | 26675.59 | 05-NOV-13:42 | 607.31 | 773.37 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 0.00 |
December | 16096.07 | 03-DEC-12:43 | 404.87 | 515.58 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12638.36 | 404.87 | 515.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27151.76 | 2010.83 | 2319.98 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2803.84 | 34.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5050.30 | 31-JAN-16:10 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 |
February | 7867.94 | 21-FEB-16:00 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 0.00 |
March | 13647.12 | 29-MAR-03:02 | 0.00 | 415.32 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23170.20 | 02-APR-16:01 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 522.80 | 0.00 |
May | 22828.37 | 28-MAY-16:21 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1621.35 | 0.00 |
June | 22336.31 | 11-JUN-16:31 | 456.59 | 581.44 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 338.77 | 0.00 |
July | 22386.08 | 02-JUL-16:31 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 558.02 | 0.00 |
August | 21058.58 | 13-AUG-16:11 | 521.82 | 664.51 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 343.00 | 0.00 |
September | 21853.52 | 24-SEP-14:52 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 446.34 | 0.00 |
October | 21616.75 | 09-OCT-15:32 | 391.37 | 498.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 88.21 | 0.00 |
November | 8727.42 | 05-NOV-15:02 | 326.14 | 415.32 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 | 0.00 |
December | 5692.37 | 28-DEC-15:40 | 1239.33 | 1495.05 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5050.30 | 0.00 | 415.32 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23170.20 | 1239.33 | 1495.05 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1621.35 | 47.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9032.46 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11621.08 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
March | 11588.03 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 |
April | 17105.57 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
May | 17645.93 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 | 0.00 |
June | 18264.25 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.13 | 0.00 |
July | 19019.92 | 03-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 0.00 |
August | 17231.74 | 28-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
September | 14219.92 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 |
October | 14074.96 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12382.00 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 |
December | 10092.11 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9032.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19019.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 | 43.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5491.23 | 06-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6809.76 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 |
March | 8733.79 | 30-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 |
April | 9622.78 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.92 | 0.00 |
May | 12369.41 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
June | 12054.23 | 06-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 0.00 |
July | 13884.53 | 05-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.23 | 0.00 |
August | 10857.95 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
September | 13753.78 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 0.00 |
October | 10482.94 | 02-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
November | 8020.57 | 14-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 |
December | 5555.87 | 09-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5491.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13884.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.92 | 55.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7517.70 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 |
February | 14286.13 | 22-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 | 0.00 |
March | 22174.20 | 28-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27198.60 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.82 | 0.00 |
May | 30861.15 | 01-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.57 | 0.00 |
June | 32399.98 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.13 | 0.00 |
July | 28837.19 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.73 | 0.00 |
August | 25878.19 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.15 | 0.00 |
September | 22604.26 | 26-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.37 | 0.00 |
October | 21615.56 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.83 | 0.00 |
November | 15216.18 | 09-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 | 0.00 |
December | 8932.19 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7517.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32399.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.82 | 84.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1920.34 | 30-JAN-17:00 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3898.65 | 20-FEB-17:20 | 23.38 | 42.40 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7205.66 | 31-MAR-23:55 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7730.44 | 17-APR-00:12 | 0.00 | 105.99 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3509.14 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5388.11 | 30-JUN-23:57 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7259.76 | 31-JUL-24:00 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7566.57 | 16-AUG-09:20 | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3507.25 | 30-SEP-23:50 | 0.00 | 63.60 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5406.49 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5800.18 | 12-NOV-16:37 | 35.07 | 63.60 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7648.82 | 28-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1920.34 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7730.44 | 232.27 | 381.58 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1758.98 | 12-JAN-17:00 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3647.70 | 21-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6962.37 | 31-MAR-23:55 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7276.91 | 12-APR-16:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3384.91 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5194.05 | 30-JUN-23:55 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6942.42 | 31-JUL-24:00 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7148.75 | 16-AUG-10:00 | 232.27 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3405.90 | 30-SEP-23:57 | 0.00 | 63.60 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5087.52 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5469.67 | 13-NOV-16:40 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7217.65 | 01-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1758.98 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7276.91 | 232.27 | 381.58 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1763.13 | 12-JAN-17:00 | 222.14 | 381.58 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3682.59 | 22-FEB-17:00 | 222.14 | 381.58 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6908.82 | 31-MAR-23:55 | 0.00 | 42.40 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7475.06 | 16-APR-21:32 | 0.00 | 105.99 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3352.68 | 31-MAY-24:00 | 0.00 | 21.20 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5254.36 | 30-JUN-23:55 | 0.00 | 84.79 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7046.31 | 31-JUL-23:53 | 0.00 | 63.60 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7280.30 | 20-AUG-16:55 | 46.77 | 84.79 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3361.13 | 30-SEP-23:57 | 0.00 | 63.60 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4940.94 | 31-OCT-24:00 | 0.00 | 21.20 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5522.92 | 08-NOV-16:30 | 222.14 | 381.58 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7216.23 | 28-DEC-17:00 | 222.14 | 381.58 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1763.13 | 0.00 | 21.20 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7475.06 | 222.14 | 381.58 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93263.66 | 26-JAN-17:00 | 4808.68 | 5800.91 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184654.02 | 21-FEB-17:00 | 4808.68 | 5800.91 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359055.49 | 31-MAR-23:55 | 0.00 | 644.59 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368499.86 | 30-APR-04:25 | 0.00 | 644.59 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176393.40 | 31-MAY-24:00 | 0.00 | 322.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268600.18 | 30-JUN-23:53 | 0.00 | 1289.17 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356660.60 | 31-JUL-23:20 | 0.00 | 644.59 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370174.57 | 15-AUG-23:42 | 0.00 | 1611.46 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177659.37 | 30-SEP-23:57 | 0.00 | 966.88 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269765.11 | 31-OCT-24:00 | 0.00 | 322.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277910.77 | 13-NOV-17:00 | 4808.68 | 5800.91 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369240.37 | 18-DEC-17:00 | 4808.68 | 5800.91 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93263.66 | 0.00 | 322.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370174.57 | 4808.68 | 5800.91 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.192680E+13 | 1295094.47 | 12-JAN-16:49 | 0.139576E+12 | 518523.54 | 02-JAN-06:19 |
February | 0.220046E+13 | 1608013.33 | 23-FEB-16:30 | 0.806634E+11 | 369390.39 | 02-FEB-07:10 |
March | 0.307910E+13 | 1910683.28 | 28-MAR-15:00 | 0.598554E+11 | 73035.94 | 02-MAR-12:50 |
April | 0.359336E+13 | 2181634.74 | 18-APR-15:09 | 0.522526E+11 | 68254.95 | 04-APR-11:20 |
May | 0.271239E+13 | 1781459.94 | 17-MAY-15:09 | 0.512984E+11 | 62213.19 | 03-MAY-11:00 |
June | 0.324084E+13 | 2087844.28 | 23-JUN-15:39 | 0.474098E+11 | 55003.50 | 01-JUN-11:00 |
July | 0.381575E+13 | 2219840.17 | 05-JUL-15:00 | 0.458094E+11 | 50105.63 | 03-JUL-11:50 |
August | 0.427490E+13 | 2388568.39 | 28-AUG-15:00 | 0.488597E+11 | 53968.81 | 29-AUG-11:00 |
September | 0.262928E+13 | 1849075.29 | 14-SEP-15:30 | 0.482127E+11 | 60403.71 | 26-SEP-11:00 |
October | 0.275791E+13 | 1780462.66 | 03-OCT-15:09 | 0.533280E+11 | 67966.63 | 31-OCT-11:50 |
November | 0.286992E+13 | 1816545.84 | 13-NOV-16:19 | 0.599811E+11 | 232772.44 | 27-NOV-06:00 |
December | 0.319522E+13 | 1763643.00 | 28-DEC-16:00 | 0.107639E+12 | 428412.77 | 23-DEC-06:00 |
Annual Sum or Average | 0.362959E+14 | 0.794886E+12 | ||||
Minimum of Months | 0.192680E+13 | 1295094.47 | 0.458094E+11 | 50105.63 | ||
Maximum of Months | 0.427490E+13 | 2388568.39 | 0.139576E+12 | 518523.54 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328950E+12 | 0.869928E+11 | 0.811612E+12 | 0.169596E+12 | 0.190416E+12 | 0.802460E+11 | 0.00 | 0.178545E+12 | 0.684389E+11 | 0.120079E+11 | 0.00 | 0.00 | 0.00 |
February | 0.298382E+12 | 0.752809E+11 | 0.102011E+13 | 0.153195E+12 | 0.184652E+12 | 0.821910E+11 | 0.00 | 0.267073E+12 | 0.106477E+12 | 0.131055E+11 | 0.00 | 0.00 | 0.00 |
March | 0.354561E+12 | 0.780102E+11 | 0.146267E+13 | 0.169879E+12 | 0.238291E+12 | 0.119886E+12 | 0.00 | 0.496945E+12 | 0.152070E+12 | 0.678818E+10 | 0.00 | 0.00 | 0.00 |
April | 0.316695E+12 | 0.702714E+11 | 0.170311E+13 | 0.164100E+12 | 0.260140E+12 | 0.150700E+12 | 0.00 | 0.751400E+12 | 0.176003E+12 | 0.939327E+09 | 0.00 | 0.00 | 0.00 |
May | 0.341755E+12 | 0.680257E+11 | 0.820521E+12 | 0.169738E+12 | 0.285645E+12 | 0.171963E+12 | 0.00 | 0.639398E+12 | 0.215333E+12 | 15413297.32 | 0.00 | 0.00 | 0.00 |
June | 0.340103E+12 | 0.633617E+11 | 0.110677E+13 | 0.164363E+12 | 0.281831E+12 | 0.179997E+12 | 0.00 | 0.878515E+12 | 0.225896E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.318348E+12 | 0.668165E+11 | 0.143888E+13 | 0.169473E+12 | 0.272683E+12 | 0.195044E+12 | 0.00 | 0.111129E+13 | 0.243217E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.354561E+12 | 0.705132E+11 | 0.177780E+13 | 0.169879E+12 | 0.282769E+12 | 0.195126E+12 | 0.00 | 0.118308E+13 | 0.241176E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316695E+12 | 0.732425E+11 | 0.784732E+12 | 0.164097E+12 | 0.248088E+12 | 0.162488E+12 | 0.00 | 0.662837E+12 | 0.217101E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328950E+12 | 0.811195E+11 | 0.112899E+13 | 0.169597E+12 | 0.237927E+12 | 0.134402E+12 | 0.00 | 0.499176E+12 | 0.176422E+12 | 0.132493E+10 | 0.00 | 0.00 | 0.00 |
November | 0.325095E+12 | 0.830197E+11 | 0.140306E+13 | 0.164207E+12 | 0.210810E+12 | 0.106151E+12 | 0.00 | 0.425863E+12 | 0.138028E+12 | 0.136799E+11 | 0.00 | 0.00 | 0.00 |
December | 0.318348E+12 | 0.886165E+11 | 0.175516E+13 | 0.169471E+12 | 0.197371E+12 | 0.884237E+11 | 0.00 | 0.418088E+12 | 0.125217E+12 | 0.345227E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394244E+13 | 0.905271E+12 | 0.152134E+14 | 0.199759E+13 | 0.289062E+13 | 0.166662E+13 | 0.00 | 0.751222E+13 | 0.208538E+13 | 0.823838E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298382E+12 | 0.633617E+11 | 0.784732E+12 | 0.153195E+12 | 0.184652E+12 | 0.802460E+11 | 0.00 | 0.178545E+12 | 0.684389E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354561E+12 | 0.886165E+11 | 0.177780E+13 | 0.169879E+12 | 0.285645E+12 | 0.195126E+12 | 0.00 | 0.118308E+13 | 0.243217E+12 | 0.345227E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.788362E+11 | 0.00 | 0.607399E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.263088E+11 | 0.00 | 0.543546E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 14542663.42 | 0.00 | 0.598409E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 7817.58 | 0.00 | 0.522526E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 7822.68 | 0.00 | 0.512984E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.474098E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.458094E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.488597E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.482127E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 604.76 | 0.00 | 0.533280E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.443891E+10 | 0.00 | 0.555422E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.488708E+11 | 0.00 | 0.587684E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158469E+12 | 0.00 | 0.636417E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.458094E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.788362E+11 | 0.00 | 0.607399E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 344233.60 | 02-JAN-08:09 | 57580.60 | 01-JAN-00:10 | 439129.89 | 02-JAN-08:09 | 120520.01 | 02-JAN-08:20 | 135035.93 | 12-JAN-15:20 | 84593.58 | 12-JAN-14:39 | 0.00 | 01-JAN-00:10 |
February | 344233.60 | 01-FEB-08:09 | 57580.60 | 01-FEB-00:10 | 557421.28 | 01-FEB-08:09 | 120520.01 | 01-FEB-08:20 | 174794.13 | 22-FEB-15:50 | 86621.84 | 23-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 344233.60 | 01-MAR-08:09 | 57580.60 | 01-MAR-00:10 | 675712.68 | 01-MAR-08:09 | 120520.01 | 01-MAR-08:20 | 212075.81 | 13-MAR-15:00 | 87873.25 | 28-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 344233.60 | 03-APR-07:10 | 57580.60 | 01-APR-00:10 | 794004.08 | 03-APR-07:10 | 120520.01 | 03-APR-07:19 | 231979.03 | 17-APR-15:09 | 89628.45 | 19-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 344233.60 | 01-MAY-07:10 | 57580.60 | 01-MAY-00:10 | 439129.89 | 01-MAY-07:10 | 120520.01 | 01-MAY-07:19 | 260809.92 | 30-MAY-14:09 | 89886.42 | 03-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 344233.60 | 01-JUN-07:10 | 57580.60 | 01-JUN-00:10 | 557421.28 | 01-JUN-07:10 | 120520.01 | 01-JUN-07:19 | 325251.03 | 23-JUN-15:30 | 96374.12 | 23-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 344233.60 | 03-JUL-07:10 | 57580.60 | 01-JUL-00:10 | 675712.68 | 03-JUL-07:10 | 120520.01 | 03-JUL-07:19 | 260436.72 | 05-JUL-15:20 | 89702.91 | 17-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 344233.60 | 01-AUG-07:10 | 57580.60 | 01-AUG-00:10 | 794004.08 | 01-AUG-07:10 | 120520.01 | 01-AUG-07:19 | 324952.60 | 28-AUG-15:30 | 96618.41 | 25-AUG-13:09 | 0.00 | 01-AUG-00:10 |
September | 344233.60 | 01-SEP-07:10 | 57580.60 | 01-SEP-00:10 | 439129.89 | 01-SEP-07:10 | 120520.01 | 01-SEP-07:19 | 231880.10 | 25-SEP-15:00 | 90192.16 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 344233.60 | 02-OCT-07:10 | 57580.60 | 01-OCT-00:10 | 557421.28 | 02-OCT-07:10 | 120520.01 | 02-OCT-07:19 | 211949.79 | 04-OCT-15:00 | 88724.72 | 03-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 344233.60 | 01-NOV-07:10 | 57580.60 | 01-NOV-00:10 | 675712.68 | 01-NOV-07:10 | 120520.01 | 01-NOV-07:19 | 183652.51 | 13-NOV-16:10 | 88753.79 | 01-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 344233.60 | 01-DEC-08:09 | 57580.60 | 01-DEC-00:10 | 794004.08 | 01-DEC-08:09 | 120520.01 | 01-DEC-08:20 | 149741.38 | 01-DEC-15:39 | 84790.24 | 12-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 344233.60 | 57580.60 | 439129.89 | 120520.01 | 135035.93 | 84593.58 | 0.00 | |||||||
Maximum of Months | 344233.60 | 57580.60 | 794004.08 | 120520.01 | 325251.03 | 96618.41 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 162692.01 | 12-JAN-15:09 | 57811.89 | 12-JAN-15:30 | 7524.46 | 21-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 312773.77 | 23-FEB-16:30 | 68883.97 | 23-FEB-16:30 | 11146.37 | 04-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 424183.28 | 28-MAR-15:00 | 96599.43 | 07-MAR-11:39 | 13980.00 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 558068.69 | 18-APR-15:30 | 96599.43 | 03-APR-08:39 | 7607.69 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 525882.47 | 17-MAY-15:30 | 96599.43 | 01-MAY-07:10 | 2093.06 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 648295.93 | 22-JUN-13:50 | 96599.43 | 01-JUN-03:30 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 683308.32 | 17-JUL-10:50 | 96599.43 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 710536.77 | 24-AUG-14:30 | 96599.43 | 01-AUG-00:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 576421.65 | 14-SEP-15:00 | 96599.43 | 01-SEP-00:30 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 454302.88 | 04-OCT-12:20 | 96599.43 | 02-OCT-08:09 | 7233.56 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 397534.36 | 06-NOV-13:09 | 96599.43 | 06-NOV-12:50 | 15187.93 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 279089.85 | 28-DEC-14:00 | 60771.26 | 28-DEC-13:00 | 28597.77 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 162692.01 | 57811.89 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 710536.77 | 96599.43 | 28597.77 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1295094.47 | 12-JAN-16:49 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 128023.64 | 82874.60 | 0.00 | 161457.31 | 52786.01 |
February | 1608013.33 | 23-FEB-16:30 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 151489.44 | 86621.84 | 0.00 | 312773.77 | 68883.97 |
March | 1910683.28 | 28-MAR-15:00 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 195739.81 | 87625.06 | 0.00 | 424183.28 | 96599.43 |
April | 2181634.74 | 18-APR-15:09 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 216840.65 | 87936.28 | 0.00 | 555431.28 | 96599.43 |
May | 1781459.94 | 17-MAY-15:09 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 204516.33 | 88796.18 | 0.00 | 521595.09 | 96599.43 |
June | 2087844.28 | 23-JUN-15:39 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 325251.03 | 96368.34 | 0.00 | 581381.19 | 96599.43 |
July | 2219840.17 | 05-JUL-15:00 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 257923.36 | 89177.50 | 0.00 | 669604.18 | 96599.43 |
August | 2388568.39 | 28-AUG-15:00 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 324913.38 | 96618.41 | 0.00 | 645610.06 | 96599.43 |
September | 1849075.29 | 14-SEP-15:30 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 217396.63 | 89154.74 | 0.00 | 575971.59 | 96599.43 |
October | 1780462.66 | 03-OCT-15:09 | 344233.60 | 557421.28 | 0.00 | 86589.42 | 158705.11 | 88578.52 | 0.00 | 448335.30 | 96599.43 |
November | 1816545.84 | 13-NOV-16:19 | 344233.60 | 675712.68 | 0.00 | 86589.42 | 177731.38 | 86490.99 | 0.00 | 364778.61 | 81009.15 |
December | 1763643.00 | 28-DEC-16:00 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 135875.31 | 82681.49 | 0.00 | 266978.54 | 53280.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1295094.47 | 344233.60 | 439129.89 | 0.00 | 86589.42 | 128023.64 | 82681.49 | 0.00 | 161457.31 | 52786.01 | |
Maximum of Months | 2388568.39 | 344233.60 | 794004.08 | 0.00 | 86589.42 | 325251.03 | 96618.41 | 0.00 | 669604.18 | 96599.43 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 489599.99 | 02-JAN-06:19 | 0.00 | 75302.06 | 20-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 344665.60 | 02-FEB-06:00 | 0.00 | 74749.01 | 08-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 6624.25 | 01-MAR-05:30 | 0.00 | 73035.94 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 13.03 | 27-APR-10:00 | 0.00 | 68254.95 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 13.04 | 19-MAY-14:30 | 0.00 | 62213.19 | 03-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 55003.50 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 50105.63 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 53968.81 | 29-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 60403.71 | 26-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 1.01 | 09-OCT-07:00 | 0.00 | 67966.63 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 213894.33 | 27-NOV-06:49 | 0.00 | 72175.85 | 27-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 401065.89 | 23-DEC-07:10 | 0.00 | 74880.97 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50105.63 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 489599.99 | 0.00 | 75302.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.95 | 3.17 | 27.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.64 | 0.50 | 26.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.04 | 0.00 | 26.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.00 | 0.00 | 26.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.08 | 0.00 | 26.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.92 | 0.00 | 25.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.82 | 0.17 | 25.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.01 | 1.67 | 26.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.09 | 0.33 | 26.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.95 | 0.67 | 25.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.26 | 1.50 | 26.24 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.36 | 1.50 | 26.47 |
Annual Sum or Average | 0.00 | 0.00 | 100.67 | 26.21 | 9.50 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.82 | 0.00 | 25.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.95 | 3.17 | 27.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.23 | 0.00 | 26.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.66 | 0.00 | 25.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.64 | 0.00 | 25.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.65 | 0.17 | 25.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.64 | 0.00 | 25.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.84 | 0.00 | 25.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.62 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 11.00 | 25.69 | 0.17 | 25.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.23 | 0.17 | 26.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.75 | 0.00 | 25.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.91 | 0.00 | 25.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.10 | 0.00 | 19.10 | 1.50 | 25.06 | 0.00 | 25.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.10 | 0.00 | 19.10 | 0.50 | 25.91 | 0.00 | 25.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.79 | 1.33 | 27.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.06 | 3.67 | 27.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.74 | 1.83 | 26.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.97 | 4.33 | 27.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.26 | 5.67 | 26.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.00 | 26.72 | 16.83 | 26.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.06 | 5.67 | 27.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.67 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.71 | 4.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.72 | 8.17 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.09 | 3.00 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.35 | 5.17 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.04 | 2.17 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.49 | 2.17 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.83 | 27.46 | 27.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.72 | 8.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 3.50 | 27.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.72 | 4.17 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.35 | 4.83 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.15 | 4.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.83 | 2.17 | 27.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.06 | 6.50 | 27.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.30 | 8.67 | 26.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.30 | 3.33 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.97 | 10.50 | 28.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.94 | 8.67 | 27.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.58 | 3.50 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 85.17 | 27.26 | 60.67 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.30 | 0.33 | 26.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.97 | 10.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.28 | 4.83 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 27.57 | 12.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.34 | 6.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.19 | 5.67 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 27.46 | 12.17 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 27.42 | 18.50 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.17 | 3.67 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.42 | 6.33 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.62 | 4.17 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.33 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 232.00 | 27.41 | 76.83 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 27.62 | 18.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.32 | 4.67 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.69 | 1.83 | 26.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.95 | 3.33 | 27.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.85 | 0.17 | 26.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 26.96 | 10.00 | 27.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.32 | 4.67 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.52 | 0.50 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.92 | 5.67 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.82 | 8.33 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.24 | 4.00 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.55 | 6.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.61 | 2.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.44 | 2.00 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.55 | 3.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.00 | 27.63 | 32.00 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.92 | 8.33 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.74 | 3.17 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 3.83 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.70 | 4.50 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.32 | 5.00 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.71 | 2.00 | 26.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.99 | 4.83 | 27.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.88 | 3.67 | 27.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 3.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.05 | 10.67 | 28.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.92 | 9.00 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.59 | 2.17 | 27.59 |
Annual Sum or Average | 0.00 | 0.00 | 71.17 | 27.49 | 52.67 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.71 | 0.50 | 26.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.05 | 10.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.76 | 1.00 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.62 | 4.33 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.63 | 7.00 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.21 | 4.17 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.49 | 5.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.16 | 3.00 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.89 | 1.83 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.88 | 3.83 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.17 | 27.50 | 30.67 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.89 | 7.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 2.50 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.53 | 7.00 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.11 | 3.33 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.35 | 7.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.15 | 3.33 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.50 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.46 | 0.00 | 18.46 | 52.83 | 27.30 | 25.00 | 27.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.46 | 0.00 | 18.46 | 17.67 | 27.64 | 7.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.02 | 6.83 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.93 | 10.83 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.44 | 4.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.68 | 9.83 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.58 | 5.83 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.70 | 4.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.63 | 3.00 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.55 | 0.00 | 18.55 | 73.17 | 27.70 | 45.17 | 27.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.55 | 0.00 | 18.55 | 19.00 | 28.02 | 10.83 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.64 | 1.83 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.84 | 3.83 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.91 | 4.83 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.58 | 7.83 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.10 | 2.83 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.40 | 7.67 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.31 | 4.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.80 | 3.33 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.22 | 10.17 | 28.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.92 | 6.83 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.89 | 0.00 | 18.89 | 86.83 | 27.60 | 53.50 | 27.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.89 | 0.00 | 18.89 | 17.50 | 28.22 | 10.17 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.82 | 1.33 | 27.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.98 | 5.17 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.91 | 7.67 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.48 | 5.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.70 | 7.67 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.45 | 3.50 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.15 | 2.00 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 4.00 | 28.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.93 | 0.00 | 18.93 | 88.17 | 27.72 | 36.67 | 27.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.93 | 0.00 | 18.93 | 20.83 | 28.15 | 7.67 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 172.33 | 28.27 | 150.67 | 28.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 443.83 | 28.28 | 344.33 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 616.17 | 28.27 | 495.00 | 28.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 443.83 | 28.28 | 344.33 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 162.17 | 28.20 | 148.00 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 358.33 | 28.17 | 300.50 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 520.50 | 28.18 | 448.50 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 358.33 | 28.20 | 300.50 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 118.67 | 28.24 | 105.17 | 28.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 243.17 | 28.16 | 213.33 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 361.83 | 28.18 | 318.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 243.17 | 28.24 | 213.33 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 539.00 | 29.49 | 405.83 | 29.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.26 | 0.00 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.00 | 30.22 | 514.00 | 30.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1283.00 | 29.91 | 919.83 | 30.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.00 | 30.22 | 514.00 | 30.31 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 27.26 | 323.67 | 24.90 | 1.50 | 24.91 |
February | 12.00 | 26.81 | 365.33 | 24.75 | 12.00 | 24.81 |
March | 34.00 | 25.15 | 446.00 | 24.56 | 34.00 | 24.60 |
April | 26.00 | 24.28 | 422.83 | 24.60 | 26.00 | 24.59 |
May | 269.33 | 24.51 | 494.33 | 24.53 | 269.33 | 24.53 |
June | 280.67 | 24.70 | 496.00 | 24.57 | 280.67 | 24.61 |
July | 288.50 | 25.12 | 497.00 | 24.82 | 288.50 | 24.90 |
August | 243.33 | 25.07 | 514.00 | 24.69 | 243.33 | 24.78 |
September | 271.67 | 25.05 | 485.00 | 24.75 | 271.67 | 24.83 |
October | 101.00 | 25.22 | 502.00 | 24.73 | 101.00 | 24.81 |
November | 0.50 | 27.42 | 470.00 | 24.67 | 0.50 | 24.67 |
December | 0.00 | 0.00 | 389.17 | 24.80 | 0.00 | 24.80 |
Annual Sum or Average | 1528.50 | 24.92 | 5405.33 | 24.69 | 1528.50 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 323.67 | 24.53 | 0.00 | 24.53 |
Maximum of Months | 288.50 | 27.42 | 514.00 | 24.90 | 288.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.00 | 25.91 | 259.83 | 24.89 | 12.33 | 24.97 |
February | 0.67 | 26.61 | 348.50 | 24.48 | 0.67 | 24.48 |
March | 0.00 | 0.00 | 444.33 | 24.33 | 0.00 | 24.33 |
April | 0.00 | 0.00 | 433.50 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 492.33 | 24.22 | 0.00 | 24.22 |
June | 0.00 | 0.00 | 496.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 485.00 | 24.31 | 0.00 | 24.31 |
October | 0.00 | 0.00 | 502.00 | 24.36 | 0.00 | 24.36 |
November | 0.00 | 0.00 | 462.00 | 24.44 | 0.00 | 24.44 |
December | 0.00 | 0.00 | 359.17 | 24.59 | 0.00 | 24.59 |
Annual Sum or Average | 18.67 | 25.93 | 5293.67 | 24.35 | 13.00 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 259.83 | 24.20 | 0.00 | 24.20 |
Maximum of Months | 18.00 | 26.61 | 514.00 | 24.89 | 12.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 23.74 | 136.83 | 24.22 | 13.00 | 24.25 |
February | 47.17 | 23.99 | 253.00 | 24.32 | 8.00 | 24.36 |
March | 4.17 | 23.98 | 394.00 | 24.28 | 0.50 | 24.29 |
April | 1.50 | 23.94 | 385.33 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 483.00 | 24.17 | 0.00 | 24.17 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 1.50 | 26.33 | 485.00 | 24.31 | 1.50 | 24.32 |
October | 0.00 | 0.00 | 492.17 | 24.32 | 0.00 | 24.32 |
November | 6.50 | 23.69 | 381.83 | 24.33 | 0.00 | 24.33 |
December | 67.00 | 23.59 | 158.50 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 229.00 | 23.77 | 4676.67 | 24.25 | 23.00 | 24.25 |
Minimum of Months | 0.00 | 0.00 | 136.83 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 101.17 | 26.33 | 514.00 | 24.33 | 13.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.00 | 22.64 | 41.33 | 22.61 | 13.50 | 22.50 |
February | 177.50 | 23.18 | 147.83 | 23.63 | 7.67 | 23.66 |
March | 24.17 | 23.63 | 361.50 | 24.19 | 1.67 | 24.20 |
April | 0.00 | 0.00 | 406.83 | 24.30 | 0.00 | 24.30 |
May | 0.50 | 26.67 | 499.17 | 24.27 | 0.50 | 24.28 |
June | 0.17 | 26.56 | 496.00 | 24.25 | 0.17 | 24.25 |
July | 0.00 | 0.00 | 497.00 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 514.00 | 24.27 | 0.00 | 24.27 |
September | 3.33 | 26.91 | 483.33 | 24.36 | 3.33 | 24.38 |
October | 0.00 | 0.00 | 482.83 | 24.30 | 0.00 | 24.30 |
November | 76.17 | 23.26 | 267.67 | 23.98 | 0.00 | 23.98 |
December | 308.67 | 22.88 | 45.67 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 956.50 | 22.91 | 4243.17 | 24.01 | 26.83 | 24.00 |
Minimum of Months | 0.00 | 0.00 | 41.33 | 22.61 | 0.00 | 22.50 |
Maximum of Months | 366.00 | 26.91 | 514.00 | 24.36 | 13.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.67 | 22.92 | 61.83 | 23.15 | 0.00 | 23.15 |
February | 160.50 | 23.08 | 163.50 | 23.63 | 0.00 | 23.63 |
March | 32.17 | 23.27 | 380.33 | 24.15 | 0.00 | 24.15 |
April | 5.33 | 26.59 | 443.00 | 24.32 | 5.33 | 24.35 |
May | 14.50 | 26.84 | 508.00 | 24.47 | 14.50 | 24.54 |
June | 16.83 | 26.34 | 496.00 | 24.40 | 16.83 | 24.47 |
July | 42.33 | 26.42 | 497.00 | 24.60 | 42.33 | 24.73 |
August | 21.00 | 26.64 | 514.00 | 24.40 | 21.00 | 24.49 |
September | 25.00 | 26.10 | 485.00 | 24.46 | 25.00 | 24.54 |
October | 0.00 | 0.00 | 484.83 | 24.29 | 0.00 | 24.29 |
November | 64.67 | 23.26 | 317.50 | 24.06 | 0.00 | 24.06 |
December | 228.50 | 23.11 | 85.83 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 932.50 | 23.50 | 4436.83 | 24.18 | 125.00 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 61.83 | 23.15 | 0.00 | 23.15 |
Maximum of Months | 321.67 | 26.84 | 514.00 | 24.60 | 42.33 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 253.83 | 22.77 | 88.00 | 23.19 | 0.00 | 23.19 |
February | 144.33 | 22.88 | 209.33 | 23.71 | 0.00 | 23.71 |
March | 52.67 | 23.27 | 387.67 | 24.14 | 3.00 | 24.15 |
April | 27.33 | 25.81 | 436.00 | 24.40 | 19.67 | 24.50 |
May | 38.67 | 26.91 | 508.00 | 24.61 | 38.67 | 24.76 |
June | 20.33 | 26.42 | 496.00 | 24.38 | 20.33 | 24.46 |
July | 38.50 | 26.45 | 497.00 | 24.52 | 38.50 | 24.65 |
August | 18.17 | 26.53 | 514.00 | 24.28 | 18.17 | 24.35 |
September | 28.00 | 26.08 | 485.00 | 24.43 | 28.00 | 24.52 |
October | 22.17 | 25.46 | 465.00 | 24.40 | 14.67 | 24.47 |
November | 81.17 | 23.01 | 324.50 | 24.02 | 0.17 | 24.02 |
December | 243.00 | 22.85 | 124.67 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 968.17 | 23.55 | 4535.17 | 24.18 | 181.17 | 24.26 |
Minimum of Months | 18.17 | 22.77 | 88.00 | 23.19 | 0.00 | 23.19 |
Maximum of Months | 253.83 | 26.91 | 514.00 | 24.61 | 38.67 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 169.83 | 22.97 | 211.33 | 23.74 | 0.00 | 23.74 |
February | 84.17 | 23.28 | 305.67 | 24.20 | 7.50 | 24.26 |
March | 35.00 | 24.99 | 439.67 | 24.42 | 16.33 | 24.50 |
April | 20.83 | 26.92 | 464.00 | 24.49 | 20.83 | 24.59 |
May | 25.00 | 26.80 | 508.00 | 24.54 | 25.00 | 24.64 |
June | 17.83 | 26.37 | 496.00 | 24.41 | 17.83 | 24.47 |
July | 42.67 | 26.48 | 497.00 | 24.61 | 42.67 | 24.74 |
August | 23.33 | 26.76 | 514.00 | 24.43 | 23.33 | 24.53 |
September | 37.33 | 26.39 | 485.00 | 24.58 | 37.33 | 24.70 |
October | 45.83 | 26.97 | 497.33 | 24.75 | 45.83 | 24.92 |
November | 49.67 | 25.84 | 428.17 | 24.70 | 34.50 | 24.85 |
December | 103.17 | 23.30 | 295.50 | 24.19 | 5.83 | 24.23 |
Annual Sum or Average | 654.67 | 24.59 | 5141.67 | 24.45 | 277.00 | 24.55 |
Minimum of Months | 17.83 | 22.97 | 211.33 | 23.74 | 0.00 | 23.74 |
Maximum of Months | 169.83 | 26.97 | 514.00 | 24.75 | 45.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.17 | 22.86 | 179.00 | 23.65 | 0.00 | 23.65 |
February | 52.17 | 23.33 | 344.00 | 24.34 | 4.33 | 24.36 |
March | 23.50 | 26.97 | 499.33 | 24.57 | 23.50 | 24.67 |
April | 64.17 | 26.83 | 485.00 | 24.82 | 64.17 | 25.03 |
May | 49.33 | 26.88 | 508.00 | 24.70 | 49.33 | 24.87 |
June | 56.33 | 26.67 | 496.00 | 24.67 | 56.33 | 24.86 |
July | 83.67 | 26.66 | 497.00 | 24.87 | 83.67 | 25.10 |
August | 86.50 | 26.63 | 514.00 | 24.81 | 86.50 | 25.04 |
September | 44.17 | 26.75 | 485.00 | 24.66 | 44.17 | 24.82 |
October | 42.50 | 26.96 | 502.00 | 24.72 | 42.50 | 24.88 |
November | 20.83 | 26.90 | 473.33 | 24.65 | 20.83 | 24.74 |
December | 17.00 | 24.10 | 396.33 | 24.60 | 3.50 | 24.62 |
Annual Sum or Average | 731.33 | 25.44 | 5379.00 | 24.62 | 478.83 | 24.78 |
Minimum of Months | 17.00 | 22.86 | 179.00 | 23.65 | 0.00 | 23.65 |
Maximum of Months | 191.17 | 26.97 | 514.00 | 24.87 | 86.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.33 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
February | 317.83 | 22.59 | 50.50 | 22.81 | 0.00 | 22.81 |
March | 116.50 | 23.09 | 272.83 | 23.83 | 0.00 | 23.83 |
April | 5.33 | 24.62 | 414.50 | 24.39 | 2.00 | 24.40 |
May | 23.17 | 26.72 | 508.00 | 24.54 | 23.17 | 24.63 |
June | 38.67 | 26.10 | 496.00 | 24.51 | 38.67 | 24.62 |
July | 102.50 | 26.11 | 497.00 | 24.80 | 102.50 | 24.99 |
August | 69.50 | 26.03 | 514.00 | 24.58 | 69.50 | 24.73 |
September | 56.33 | 26.06 | 485.00 | 24.59 | 56.33 | 24.73 |
October | 21.50 | 23.05 | 432.00 | 24.21 | 0.67 | 24.21 |
November | 224.67 | 22.90 | 133.33 | 23.33 | 0.00 | 23.33 |
December | 453.33 | 22.34 | 2.00 | 22.35 | 0.00 | 22.35 |
Annual Sum or Average | 1907.67 | 23.05 | 3805.17 | 23.93 | 292.83 | 24.03 |
Minimum of Months | 5.33 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
Maximum of Months | 478.33 | 26.72 | 514.00 | 24.80 | 102.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.17 | 22.39 | 3.83 | 22.41 | 0.00 | 22.41 |
February | 210.67 | 22.56 | 95.50 | 23.10 | 0.00 | 23.10 |
March | 74.83 | 23.04 | 278.67 | 24.10 | 3.33 | 24.12 |
April | 30.50 | 26.55 | 365.33 | 24.76 | 28.00 | 24.89 |
May | 48.67 | 26.88 | 429.83 | 24.81 | 48.67 | 25.00 |
June | 43.00 | 26.39 | 418.00 | 24.64 | 43.00 | 24.79 |
July | 103.17 | 26.19 | 422.00 | 24.92 | 103.17 | 25.13 |
August | 68.33 | 26.14 | 433.00 | 24.68 | 68.33 | 24.86 |
September | 64.17 | 26.15 | 404.83 | 24.73 | 64.17 | 24.90 |
October | 38.50 | 24.59 | 374.17 | 24.51 | 17.50 | 24.60 |
November | 141.00 | 22.79 | 191.83 | 23.66 | 0.00 | 23.66 |
December | 332.17 | 22.40 | 9.67 | 22.46 | 0.00 | 22.46 |
Annual Sum or Average | 1546.17 | 23.45 | 3426.67 | 24.17 | 376.17 | 24.32 |
Minimum of Months | 30.50 | 22.39 | 3.83 | 22.41 | 0.00 | 22.41 |
Maximum of Months | 391.17 | 26.88 | 433.00 | 24.92 | 103.17 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 231.00 | 22.81 | 184.33 | 23.50 | 0.50 | 23.50 |
February | 123.17 | 22.97 | 255.83 | 23.99 | 7.50 | 24.05 |
March | 49.67 | 24.18 | 405.17 | 24.37 | 14.50 | 24.45 |
April | 18.50 | 26.90 | 445.67 | 24.59 | 18.33 | 24.67 |
May | 29.33 | 26.75 | 508.00 | 24.58 | 29.33 | 24.69 |
June | 38.50 | 26.10 | 496.00 | 24.50 | 38.50 | 24.61 |
July | 101.83 | 26.13 | 497.00 | 24.80 | 101.83 | 24.99 |
August | 69.33 | 26.17 | 514.00 | 24.62 | 69.33 | 24.78 |
September | 63.67 | 26.34 | 485.00 | 24.71 | 63.67 | 24.88 |
October | 46.83 | 27.01 | 488.83 | 24.81 | 46.83 | 24.98 |
November | 76.17 | 24.87 | 403.50 | 24.61 | 34.33 | 24.77 |
December | 171.83 | 22.93 | 225.83 | 23.87 | 4.33 | 23.90 |
Annual Sum or Average | 1019.83 | 24.35 | 4909.17 | 24.46 | 429.00 | 24.59 |
Minimum of Months | 18.50 | 22.81 | 184.33 | 23.50 | 0.50 | 23.50 |
Maximum of Months | 231.00 | 27.01 | 514.00 | 24.81 | 101.83 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.33 | 22.31 | 23.50 | 22.40 | 0.00 | 22.40 |
February | 249.00 | 22.55 | 122.00 | 23.13 | 0.00 | 23.13 |
March | 72.67 | 23.14 | 359.17 | 24.11 | 4.67 | 24.14 |
April | 22.83 | 26.97 | 466.17 | 24.61 | 22.83 | 24.71 |
May | 46.00 | 26.93 | 508.00 | 24.70 | 46.00 | 24.87 |
June | 52.83 | 26.55 | 496.00 | 24.64 | 52.83 | 24.80 |
July | 100.50 | 26.31 | 497.00 | 24.84 | 100.50 | 25.05 |
August | 71.50 | 26.31 | 514.00 | 24.66 | 71.50 | 24.84 |
September | 61.67 | 26.35 | 482.17 | 24.67 | 61.67 | 24.84 |
October | 32.50 | 24.85 | 459.33 | 24.43 | 16.17 | 24.51 |
November | 137.83 | 22.80 | 251.00 | 23.73 | 0.00 | 23.73 |
December | 376.33 | 22.48 | 57.83 | 22.71 | 0.00 | 22.71 |
Annual Sum or Average | 1640.00 | 23.42 | 4236.17 | 24.15 | 376.17 | 24.29 |
Minimum of Months | 22.83 | 22.31 | 23.50 | 22.40 | 0.00 | 22.40 |
Maximum of Months | 416.33 | 26.97 | 514.00 | 24.84 | 100.50 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 21.26 | 79.67 | 21.06 | 79.67 | 20.91 |
February | 383.83 | 22.02 | 35.50 | 22.11 | 8.67 | 22.06 |
March | 187.33 | 22.76 | 231.67 | 23.52 | 0.00 | 23.52 |
April | 30.00 | 24.22 | 409.17 | 24.36 | 9.00 | 24.41 |
May | 39.67 | 26.68 | 506.83 | 24.60 | 39.67 | 24.74 |
June | 50.17 | 26.05 | 496.00 | 24.53 | 50.17 | 24.66 |
July | 108.67 | 26.11 | 497.00 | 24.81 | 108.67 | 25.01 |
August | 74.17 | 26.03 | 514.00 | 24.59 | 74.17 | 24.76 |
September | 62.17 | 25.93 | 476.50 | 24.56 | 61.83 | 24.70 |
October | 69.00 | 22.84 | 382.00 | 24.02 | 2.17 | 24.03 |
November | 331.50 | 22.45 | 82.17 | 22.74 | 2.17 | 22.72 |
December | 494.50 | 21.54 | 49.67 | 21.39 | 49.67 | 21.27 |
Annual Sum or Average | 2330.50 | 22.52 | 3760.17 | 23.56 | 485.83 | 23.61 |
Minimum of Months | 30.00 | 21.26 | 35.50 | 21.06 | 0.00 | 20.91 |
Maximum of Months | 499.50 | 26.68 | 514.00 | 24.81 | 108.67 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.33 | 21.63 | 44.67 | 21.48 | 44.67 | 21.35 |
February | 297.33 | 22.26 | 96.83 | 22.68 | 3.33 | 22.65 |
March | 108.33 | 22.89 | 332.50 | 23.95 | 4.67 | 23.98 |
April | 43.00 | 25.84 | 444.67 | 24.61 | 31.00 | 24.75 |
May | 56.17 | 26.89 | 506.33 | 24.74 | 56.17 | 24.94 |
June | 53.83 | 26.37 | 496.00 | 24.58 | 53.83 | 24.74 |
July | 108.50 | 26.25 | 497.00 | 24.84 | 108.50 | 25.06 |
August | 72.67 | 26.19 | 514.00 | 24.61 | 72.67 | 24.79 |
September | 69.67 | 25.92 | 470.00 | 24.61 | 66.50 | 24.77 |
October | 62.00 | 24.04 | 427.50 | 24.37 | 22.17 | 24.47 |
November | 198.67 | 22.49 | 192.33 | 23.31 | 0.00 | 23.31 |
December | 472.50 | 21.97 | 23.17 | 21.89 | 23.17 | 21.82 |
Annual Sum or Average | 2030.00 | 22.95 | 4045.00 | 23.87 | 486.67 | 23.99 |
Minimum of Months | 43.00 | 21.63 | 23.17 | 21.48 | 0.00 | 21.35 |
Maximum of Months | 487.33 | 26.89 | 514.00 | 24.84 | 108.50 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.83 | 21.98 | 135.83 | 22.49 | 18.83 | 22.38 |
February | 193.67 | 22.39 | 198.67 | 23.42 | 3.83 | 23.45 |
March | 94.67 | 23.46 | 365.33 | 24.17 | 14.67 | 24.26 |
April | 28.67 | 25.90 | 439.83 | 24.56 | 20.33 | 24.66 |
May | 42.33 | 26.73 | 506.50 | 24.63 | 42.33 | 24.78 |
June | 48.83 | 26.05 | 496.00 | 24.52 | 48.83 | 24.65 |
July | 108.17 | 26.12 | 497.00 | 24.81 | 108.17 | 25.01 |
August | 73.33 | 26.17 | 514.00 | 24.63 | 73.33 | 24.80 |
September | 67.33 | 26.19 | 479.00 | 24.68 | 67.00 | 24.84 |
October | 62.50 | 25.87 | 465.83 | 24.73 | 45.67 | 24.91 |
November | 113.17 | 23.68 | 351.00 | 24.30 | 27.17 | 24.45 |
December | 265.67 | 22.27 | 173.50 | 23.06 | 9.00 | 23.01 |
Annual Sum or Average | 1418.17 | 23.59 | 4622.50 | 24.23 | 479.17 | 24.36 |
Minimum of Months | 28.67 | 21.98 | 135.83 | 22.49 | 3.83 | 22.38 |
Maximum of Months | 319.83 | 26.73 | 514.00 | 24.81 | 108.17 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 451.50 | 21.57 | 47.00 | 21.49 | 36.50 | 21.38 |
February | 316.50 | 22.12 | 91.83 | 22.60 | 0.00 | 22.60 |
March | 129.67 | 22.84 | 308.67 | 23.85 | 5.50 | 23.89 |
April | 31.33 | 26.28 | 452.17 | 24.60 | 25.83 | 24.72 |
May | 54.67 | 26.88 | 506.83 | 24.72 | 54.67 | 24.91 |
June | 59.50 | 26.50 | 496.00 | 24.63 | 59.50 | 24.82 |
July | 106.67 | 26.26 | 497.00 | 24.84 | 106.67 | 25.05 |
August | 75.00 | 26.31 | 514.00 | 24.65 | 75.00 | 24.84 |
September | 68.33 | 26.05 | 469.67 | 24.63 | 65.33 | 24.80 |
October | 62.83 | 23.86 | 419.17 | 24.31 | 18.83 | 24.40 |
November | 228.00 | 22.48 | 186.33 | 23.24 | 0.00 | 23.24 |
December | 424.67 | 21.83 | 54.17 | 21.93 | 19.83 | 21.86 |
Annual Sum or Average | 2008.67 | 22.91 | 4042.83 | 23.87 | 467.67 | 24.00 |
Minimum of Months | 31.33 | 21.57 | 47.00 | 21.49 | 0.00 | 21.38 |
Maximum of Months | 451.50 | 26.88 | 514.00 | 24.84 | 106.67 | 25.05 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 66.50 | 27.00 | 514.00 | 27.00 | 66.50 | 27.00 |
April | 356.50 | 27.62 | 485.00 | 27.52 | 356.50 | 27.55 |
May | 36.17 | 27.00 | 508.00 | 27.00 | 36.17 | 27.00 |
June | 164.33 | 27.00 | 496.00 | 27.00 | 164.33 | 27.00 |
July | 274.17 | 27.00 | 497.00 | 27.00 | 274.17 | 27.00 |
August | 499.17 | 27.97 | 514.00 | 27.96 | 499.17 | 27.96 |
September | 36.17 | 27.00 | 485.00 | 27.00 | 36.17 | 27.00 |
October | 34.50 | 27.00 | 502.00 | 27.00 | 34.50 | 27.00 |
November | 57.67 | 27.00 | 489.00 | 27.00 | 57.67 | 27.00 |
December | 45.83 | 27.00 | 497.00 | 27.00 | 45.83 | 27.00 |
Annual Sum or Average | 1571.00 | 27.45 | 5943.00 | 27.19 | 1571.00 | 27.23 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 499.17 | 27.97 | 514.00 | 27.96 | 499.17 | 27.96 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 174.50 | 28.07 | 485.00 | 27.59 | 174.50 | 27.69 |
May | 1.17 | 27.00 | 508.00 | 27.00 | 1.17 | 27.00 |
June | 6.83 | 27.00 | 496.00 | 27.00 | 6.83 | 27.00 |
July | 11.83 | 27.00 | 497.00 | 27.00 | 11.83 | 27.00 |
August | 318.00 | 28.17 | 514.00 | 27.92 | 318.00 | 27.99 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.33 | 27.00 | 502.00 | 27.00 | 0.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 512.67 | 28.09 | 5943.00 | 27.18 | 512.67 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 318.00 | 28.17 | 514.00 | 27.92 | 318.00 | 27.99 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 24.55 | 468.00 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 5.00 | 27.00 | 514.00 | 27.00 | 5.00 | 27.00 |
April | 160.67 | 27.90 | 485.00 | 27.45 | 160.67 | 27.54 |
May | 70.67 | 27.00 | 508.00 | 27.00 | 70.67 | 27.00 |
June | 105.17 | 27.00 | 496.00 | 27.00 | 105.17 | 27.00 |
July | 91.83 | 27.00 | 497.00 | 27.00 | 91.83 | 27.00 |
August | 257.00 | 28.03 | 514.00 | 27.70 | 257.00 | 27.78 |
September | 18.83 | 27.00 | 485.00 | 27.00 | 18.83 | 27.00 |
October | 9.83 | 27.00 | 502.00 | 27.00 | 9.83 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 731.50 | 27.52 | 5909.00 | 27.12 | 719.00 | 27.17 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 257.00 | 28.03 | 514.00 | 27.70 | 257.00 | 27.78 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.31 | 485.00 | 29.31 | 485.00 | 29.31 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 30.43 | 514.00 | 30.43 | 514.00 | 30.43 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.49 | 5943.00 | 27.49 | 5943.00 | 27.49 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.43 | 514.00 | 30.43 | 514.00 | 30.43 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00071 | 29.14587 | 0.85945 | 20.63205 |
February | 454.00000 | 27.00090 | 29.62405 | 0.91448 | 22.69922 |
March | 514.00000 | 27.00054 | 31.22698 | 0.98078 | 25.34747 |
April | 485.00000 | 27.45318 | 32.49998 | 1.12884 | 32.12864 |
May | 508.00000 | 27.00075 | 37.40355 | 0.33372 | 7.36546 |
June | 496.00000 | 27.00234 | 37.16925 | 0.37855 | 8.02630 |
July | 497.00000 | 27.00152 | 36.37365 | 0.41207 | 8.58018 |
August | 514.00000 | 27.94390 | 34.69206 | 0.69954 | 16.14738 |
September | 485.00000 | 27.00014 | 40.20204 | 0.34615 | 7.53011 |
October | 502.00000 | 27.00160 | 33.22825 | 0.97635 | 25.16174 |
November | 489.00000 | 27.00058 | 30.47700 | 0.97472 | 25.09969 |
December | 497.00000 | 27.00016 | 28.24707 | 0.96684 | 24.78172 |
Annual Sum or Average | 5943.00000 | 27.11939 | 33.37720 | 0.74626 | 18.58221 |
Minimum of Months | 454.00000 | 27.00014 | 28.24707 | 0.33372 | 7.36546 |
Maximum of Months | 514.00000 | 27.94390 | 40.20204 | 1.12884 | 32.12864 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00052 | 29.43562 | 0.78712 | 18.12061 |
February | 454.00000 | 27.00084 | 29.71248 | 0.83311 | 19.70432 |
March | 514.00000 | 27.00053 | 31.24539 | 0.90460 | 22.32668 |
April | 485.00000 | 27.41646 | 32.54424 | 1.03493 | 27.91352 |
May | 508.00000 | 27.00052 | 37.61406 | 0.28874 | 6.78274 |
June | 496.00000 | 27.00234 | 37.32412 | 0.30877 | 7.02820 |
July | 497.00000 | 27.00158 | 36.50299 | 0.31667 | 7.12543 |
August | 514.00000 | 27.77404 | 34.91091 | 0.51220 | 11.22764 |
September | 485.00000 | 27.00005 | 40.70212 | 0.29674 | 6.86930 |
October | 502.00000 | 27.00154 | 33.33632 | 0.91828 | 22.84315 |
November | 489.00000 | 27.00057 | 30.50418 | 0.88111 | 21.44123 |
December | 497.00000 | 27.00017 | 28.24251 | 0.83190 | 19.67086 |
Annual Sum or Average | 5943.00000 | 27.10165 | 33.52609 | 0.65791 | 15.87755 |
Minimum of Months | 454.00000 | 27.00005 | 28.24251 | 0.28874 | 6.78274 |
Maximum of Months | 514.00000 | 27.77404 | 40.70212 | 1.03493 | 27.91352 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.91721 | 29.86633 | 0.70240 | 15.82111 |
February | 454.00000 | 27.00092 | 29.20066 | 0.79093 | 18.32938 |
March | 514.00000 | 27.00061 | 30.60696 | 0.89314 | 21.94272 |
April | 485.00000 | 27.30740 | 32.05503 | 1.02556 | 27.54229 |
May | 508.00000 | 27.00058 | 36.95235 | 0.31881 | 7.22696 |
June | 496.00000 | 27.00248 | 36.64117 | 0.33907 | 7.49870 |
July | 497.00000 | 27.00175 | 35.81277 | 0.34163 | 7.52117 |
August | 514.00000 | 27.53927 | 34.34599 | 0.47177 | 10.47778 |
September | 485.00000 | 27.00006 | 40.05121 | 0.30484 | 7.01157 |
October | 502.00000 | 27.00167 | 32.71844 | 0.91249 | 22.65930 |
November | 489.00000 | 27.00065 | 29.87845 | 0.84927 | 20.34028 |
December | 497.00000 | 27.00024 | 27.68864 | 0.76627 | 17.53881 |
Annual Sum or Average | 5943.00000 | 27.06548 | 33.00498 | 0.64153 | 15.28745 |
Minimum of Months | 454.00000 | 26.91721 | 27.68864 | 0.30484 | 7.01157 |
Maximum of Months | 514.00000 | 27.53927 | 40.05121 | 1.02556 | 27.54229 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00512 | 30.03432 | 1.09630 | 30.35164 |
February | 454.00000 | 27.00589 | 30.19750 | 1.24090 | 37.27604 |
March | 514.00000 | 27.00305 | 31.02771 | 1.38242 | 44.58102 |
April | 485.00000 | 29.31046 | 31.12780 | 1.98389 | 74.31464 |
May | 508.00000 | 27.00345 | 34.93663 | 0.56277 | 11.70628 |
June | 496.00000 | 27.00316 | 35.07150 | 0.78973 | 18.17046 |
July | 497.00000 | 27.00171 | 34.49285 | 1.00243 | 26.23982 |
August | 514.00000 | 30.42987 | 31.92565 | 2.20047 | 83.30024 |
September | 485.00000 | 27.00418 | 35.49424 | 0.63837 | 13.62119 |
October | 502.00000 | 27.00273 | 32.00089 | 1.30180 | 40.36786 |
November | 489.00000 | 27.00420 | 30.64568 | 1.42197 | 46.68857 |
December | 497.00000 | 27.00664 | 30.05239 | 1.53454 | 52.77952 |
Annual Sum or Average | 5943.00000 | 27.48852 | 32.26133 | 1.26442 | 40.02474 |
Minimum of Months | 454.00000 | 27.00171 | 30.03432 | 0.56277 | 11.70628 |
Maximum of Months | 514.00000 | 30.42987 | 35.49424 | 2.20047 | 83.30024 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.57724 | 39.64134 | 0.51912 | 11.28380 |
February | 454.00000 | 24.55069 | 44.26618 | 0.54440 | 11.76882 |
March | 514.00000 | 24.45080 | 48.08250 | 0.55089 | 11.84773 |
April | 485.00000 | 24.54508 | 47.37209 | 0.56614 | 12.27625 |
May | 508.00000 | 24.52776 | 57.95791 | -0.2044 | 6.91179 |
June | 496.00000 | 24.49849 | 61.49077 | -0.1751 | 6.87928 |
July | 497.00000 | 24.64839 | 62.33427 | -0.1088 | 7.16005 |
August | 514.00000 | 24.51023 | 61.14144 | -0.1406 | 7.00885 |
September | 485.00000 | 24.58608 | 62.30818 | -0.1235 | 7.13171 |
October | 502.00000 | 24.63643 | 55.35884 | 0.66622 | 15.05103 |
November | 489.00000 | 24.63944 | 46.76483 | 0.60281 | 13.30433 |
December | 497.00000 | 24.62591 | 39.72924 | 0.54152 | 11.80170 |
Annual Sum or Average | 5943.00000 | 24.56591 | 52.27302 | 0.26702 | 10.18364 |
Minimum of Months | 454.00000 | 24.45080 | 39.64134 | -0.2044 | 6.87928 |
Maximum of Months | 514.00000 | 24.64839 | 62.33427 | 0.66622 | 15.05103 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42992 | 40.56705 | 0.48762 | 10.74772 |
February | 454.00000 | 24.36703 | 43.49790 | 0.50960 | 10.77235 |
March | 514.00000 | 24.28311 | 47.05079 | 0.53351 | 11.21318 |
April | 485.00000 | 24.21606 | 47.13138 | 0.53467 | 11.14949 |
May | 508.00000 | 24.21240 | 53.73354 | -0.2934 | 7.00802 |
June | 496.00000 | 24.19517 | 55.72168 | -0.2757 | 6.76421 |
July | 497.00000 | 24.25112 | 56.09868 | -0.2493 | 6.51823 |
August | 514.00000 | 24.22275 | 55.81494 | -0.2393 | 6.41434 |
September | 485.00000 | 24.31231 | 56.33072 | -0.2474 | 6.71728 |
October | 502.00000 | 24.35865 | 53.34844 | 0.59844 | 12.78444 |
November | 489.00000 | 24.41512 | 46.18263 | 0.55901 | 11.91089 |
December | 497.00000 | 24.43020 | 39.15043 | 0.50220 | 10.67711 |
Annual Sum or Average | 5943.00000 | 24.30710 | 49.60499 | 0.19862 | 9.37495 |
Minimum of Months | 454.00000 | 24.19517 | 39.15043 | -0.2934 | 6.41434 |
Maximum of Months | 514.00000 | 24.43020 | 56.33072 | 0.59844 | 12.78444 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12068 | 41.45582 | 0.38897 | 8.49109 |
February | 454.00000 | 24.18390 | 43.98304 | 0.43676 | 9.27136 |
March | 514.00000 | 24.22455 | 47.10945 | 0.49063 | 10.26007 |
April | 485.00000 | 24.21317 | 47.35321 | 0.49906 | 10.39546 |
May | 508.00000 | 24.16523 | 54.04246 | -0.3346 | 7.51099 |
June | 496.00000 | 24.17268 | 56.25646 | -0.3165 | 7.28095 |
July | 497.00000 | 24.21129 | 57.04894 | -0.3038 | 7.13442 |
August | 514.00000 | 24.20816 | 57.21455 | -0.2994 | 7.10721 |
September | 485.00000 | 24.30661 | 56.74065 | -0.2777 | 7.08240 |
October | 502.00000 | 24.30932 | 53.73458 | 0.56218 | 11.85560 |
November | 489.00000 | 24.26166 | 46.64841 | 0.48941 | 10.24659 |
December | 497.00000 | 24.12922 | 40.04101 | 0.38843 | 8.37456 |
Annual Sum or Average | 5943.00000 | 24.20875 | 50.19073 | 0.14064 | 8.74512 |
Minimum of Months | 454.00000 | 24.12068 | 40.04101 | -0.3346 | 7.08240 |
Maximum of Months | 514.00000 | 24.30932 | 57.21455 | 0.56218 | 11.85560 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00447 | 44.36440 | 0.09504 | 6.66982 |
February | 454.00000 | 23.70093 | 45.59427 | 0.30840 | 7.73305 |
March | 514.00000 | 24.14333 | 47.55627 | 0.47217 | 9.90980 |
April | 485.00000 | 24.25764 | 47.32498 | 0.52667 | 11.04560 |
May | 508.00000 | 24.26669 | 53.68248 | -0.2641 | 6.83385 |
June | 496.00000 | 24.24697 | 55.84074 | -0.2528 | 6.69850 |
July | 497.00000 | 24.31629 | 56.58419 | -0.2381 | 6.61552 |
August | 514.00000 | 24.26750 | 57.02446 | -0.2537 | 6.71044 |
September | 485.00000 | 24.33704 | 56.90021 | -0.2493 | 6.86398 |
October | 502.00000 | 24.28436 | 54.38436 | 0.56190 | 11.81797 |
November | 489.00000 | 23.96365 | 47.88449 | 0.40892 | 8.83459 |
December | 497.00000 | 23.30365 | 42.65085 | 0.17210 | 6.67887 |
Annual Sum or Average | 5943.00000 | 24.00978 | 50.86294 | 0.10504 | 8.03333 |
Minimum of Months | 454.00000 | 23.00447 | 42.65085 | -0.2641 | 6.61552 |
Maximum of Months | 514.00000 | 24.33704 | 57.02446 | 0.56190 | 11.81797 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.34240 | 41.21419 | 0.19744 | 6.59871 |
February | 454.00000 | 23.72167 | 44.26191 | 0.33639 | 7.94256 |
March | 514.00000 | 24.09430 | 46.72592 | 0.48425 | 10.19116 |
April | 485.00000 | 24.26488 | 46.11044 | 0.57622 | 12.28924 |
May | 508.00000 | 24.40538 | 52.33146 | -0.1474 | 6.21774 |
June | 496.00000 | 24.33856 | 54.65465 | -0.1341 | 5.98044 |
July | 497.00000 | 24.44428 | 55.52197 | -0.1031 | 6.22630 |
August | 514.00000 | 24.31022 | 55.37462 | -0.1423 | 6.09780 |
September | 485.00000 | 24.38029 | 56.05980 | -0.1768 | 6.39609 |
October | 502.00000 | 24.26373 | 52.82935 | 0.58052 | 12.30827 |
November | 489.00000 | 24.01191 | 46.51572 | 0.44203 | 9.36966 |
December | 497.00000 | 23.61463 | 40.32181 | 0.27582 | 7.10314 |
Annual Sum or Average | 5943.00000 | 24.10192 | 49.37080 | 0.18059 | 8.05377 |
Minimum of Months | 454.00000 | 23.34240 | 40.32181 | -0.1768 | 5.98044 |
Maximum of Months | 514.00000 | 24.44428 | 56.05980 | 0.58052 | 12.30827 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44736 | 40.76194 | 0.24203 | 7.10822 |
February | 454.00000 | 23.73803 | 44.06414 | 0.36713 | 8.61309 |
March | 514.00000 | 24.06685 | 46.63208 | 0.50995 | 11.00953 |
April | 485.00000 | 24.25533 | 45.98643 | 0.60982 | 13.42417 |
May | 508.00000 | 24.43751 | 52.07654 | -0.0783 | 6.35095 |
June | 496.00000 | 24.30161 | 54.66502 | -0.1173 | 6.00102 |
July | 497.00000 | 24.37435 | 55.71217 | -0.1172 | 6.37073 |
August | 514.00000 | 24.20026 | 55.77964 | -0.1843 | 6.34781 |
September | 485.00000 | 24.33487 | 56.04752 | -0.1632 | 6.38721 |
October | 502.00000 | 24.27424 | 52.62536 | 0.61062 | 13.36072 |
November | 489.00000 | 23.95986 | 46.47432 | 0.45533 | 9.88764 |
December | 497.00000 | 23.48766 | 40.50962 | 0.26442 | 7.27225 |
Annual Sum or Average | 5943.00000 | 24.07547 | 49.32333 | 0.19798 | 8.50317 |
Minimum of Months | 454.00000 | 23.44736 | 40.50962 | -0.1843 | 6.00102 |
Maximum of Months | 514.00000 | 24.43751 | 56.04752 | 0.61062 | 13.42417 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.80209 | 39.76022 | 0.35371 | 8.70418 |
February | 454.00000 | 24.11367 | 43.01748 | 0.48017 | 10.84223 |
March | 514.00000 | 24.27823 | 45.96732 | 0.58025 | 12.68015 |
April | 485.00000 | 24.35981 | 45.72177 | 0.63079 | 13.89740 |
May | 508.00000 | 24.42404 | 52.24671 | -0.1301 | 6.25133 |
June | 496.00000 | 24.33519 | 54.66437 | -0.1360 | 6.01452 |
July | 497.00000 | 24.44507 | 55.50669 | -0.1012 | 6.27335 |
August | 514.00000 | 24.32480 | 55.27707 | -0.1276 | 6.13806 |
September | 485.00000 | 24.44304 | 55.70303 | -0.1147 | 6.33731 |
October | 502.00000 | 24.53621 | 51.69718 | 0.71320 | 16.53606 |
November | 489.00000 | 24.44889 | 44.89843 | 0.62810 | 14.20591 |
December | 497.00000 | 24.11045 | 38.83284 | 0.45008 | 10.28259 |
Annual Sum or Average | 5943.00000 | 24.30255 | 48.65710 | 0.26645 | 9.82891 |
Minimum of Months | 454.00000 | 23.80209 | 38.83284 | -0.1360 | 6.01452 |
Maximum of Months | 514.00000 | 24.53621 | 55.70303 | 0.71320 | 16.53606 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.72686 | 39.77584 | 0.33807 | 8.32737 |
February | 454.00000 | 24.21879 | 42.59391 | 0.52161 | 11.46752 |
March | 514.00000 | 24.43733 | 45.45062 | 0.66990 | 15.06536 |
April | 485.00000 | 24.55161 | 45.04032 | 0.79042 | 18.97067 |
May | 508.00000 | 24.48365 | 51.87099 | -0.0058 | 6.32939 |
June | 496.00000 | 24.44503 | 54.01799 | 0.03142 | 6.23521 |
July | 497.00000 | 24.57258 | 54.64928 | 0.06457 | 6.75051 |
August | 514.00000 | 24.50414 | 54.26673 | 0.09924 | 6.72203 |
September | 485.00000 | 24.46943 | 55.36337 | -0.0531 | 6.21202 |
October | 502.00000 | 24.53002 | 51.69331 | 0.72794 | 16.82202 |
November | 489.00000 | 24.52269 | 44.69484 | 0.65389 | 14.65662 |
December | 497.00000 | 24.45073 | 37.91458 | 0.55783 | 12.20867 |
Annual Sum or Average | 5943.00000 | 24.41023 | 48.15902 | 0.36456 | 10.79276 |
Minimum of Months | 454.00000 | 23.72686 | 37.91458 | -0.0531 | 6.21202 |
Maximum of Months | 514.00000 | 24.57258 | 55.36337 | 0.79042 | 18.97067 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26429 | 43.33533 | -0.0677 | 6.01867 |
February | 454.00000 | 22.99668 | 45.87760 | 0.14792 | 6.55055 |
March | 514.00000 | 23.84671 | 47.15008 | 0.40232 | 8.89282 |
April | 485.00000 | 24.30967 | 46.09493 | 0.55446 | 11.82428 |
May | 508.00000 | 24.43580 | 52.56603 | -0.1532 | 6.39396 |
June | 496.00000 | 24.38382 | 55.53441 | -0.1385 | 6.17262 |
July | 497.00000 | 24.52406 | 57.49006 | -0.0992 | 6.52949 |
August | 514.00000 | 24.38458 | 57.50249 | -0.1575 | 6.39210 |
September | 485.00000 | 24.41789 | 57.57565 | -0.1783 | 6.75362 |
October | 502.00000 | 24.14021 | 53.36513 | 0.53090 | 11.21728 |
November | 489.00000 | 23.46604 | 47.90362 | 0.29102 | 7.36999 |
December | 497.00000 | 22.46872 | 42.62325 | -0.0153 | 6.05570 |
Annual Sum or Average | 5943.00000 | 23.80908 | 50.62654 | 0.09202 | 7.51500 |
Minimum of Months | 454.00000 | 22.26429 | 42.62325 | -0.1783 | 6.01867 |
Maximum of Months | 514.00000 | 24.52406 | 57.57565 | 0.55446 | 11.82428 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.51462 | 42.19792 | 0.00820 | 5.91579 |
February | 385.00000 | 23.26434 | 44.64394 | 0.23396 | 7.36897 |
March | 433.00000 | 24.02488 | 46.02339 | 0.47476 | 10.59156 |
April | 410.00000 | 24.51472 | 44.91322 | 0.64251 | 14.56699 |
May | 430.00000 | 24.57087 | 51.97551 | -0.0558 | 6.76087 |
June | 418.00000 | 24.45943 | 55.22625 | -0.0859 | 6.33416 |
July | 422.00000 | 24.61347 | 57.21876 | -0.0562 | 6.86110 |
August | 433.00000 | 24.45122 | 57.28608 | -0.1257 | 6.57893 |
September | 410.00000 | 24.48614 | 57.41258 | -0.1320 | 6.92395 |
October | 427.00000 | 24.33154 | 52.58407 | 0.60187 | 13.42804 |
November | 417.00000 | 23.67820 | 46.92941 | 0.36678 | 8.66361 |
December | 422.00000 | 22.72819 | 41.62274 | 0.06365 | 6.21984 |
Annual Sum or Average | 5034.00000 | 23.97340 | 49.87309 | 0.16035 | 8.34937 |
Minimum of Months | 385.00000 | 22.51462 | 41.62274 | -0.1320 | 5.91579 |
Maximum of Months | 433.00000 | 24.61347 | 57.41258 | 0.64251 | 14.56699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57519 | 39.84617 | 0.29514 | 8.25922 |
February | 454.00000 | 23.92445 | 43.15714 | 0.42288 | 10.16777 |
March | 514.00000 | 24.22595 | 45.77716 | 0.54929 | 12.09269 |
April | 485.00000 | 24.44294 | 45.57662 | 0.62196 | 13.74551 |
May | 508.00000 | 24.45071 | 52.48525 | -0.1378 | 6.39002 |
June | 496.00000 | 24.37911 | 55.55143 | -0.1422 | 6.19426 |
July | 497.00000 | 24.52432 | 57.46851 | -0.0976 | 6.55059 |
August | 514.00000 | 24.41006 | 57.32692 | -0.1369 | 6.42995 |
September | 485.00000 | 24.49523 | 57.06909 | -0.1070 | 6.69567 |
October | 502.00000 | 24.56628 | 51.67016 | 0.70793 | 16.50756 |
November | 489.00000 | 24.36945 | 44.80358 | 0.59494 | 13.55543 |
December | 497.00000 | 23.86156 | 38.96903 | 0.37170 | 9.50651 |
Annual Sum or Average | 5943.00000 | 24.27059 | 49.19529 | 0.24296 | 9.66030 |
Minimum of Months | 454.00000 | 23.57519 | 38.96903 | -0.1422 | 6.19426 |
Maximum of Months | 514.00000 | 24.56628 | 57.46851 | 0.70793 | 16.50756 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.58861 | 42.16861 | 0.03821 | 6.16943 |
February | 454.00000 | 23.24065 | 44.92744 | 0.24146 | 7.53966 |
March | 514.00000 | 24.02586 | 46.40525 | 0.49639 | 10.92639 |
April | 485.00000 | 24.46300 | 45.53390 | 0.66108 | 14.92150 |
May | 508.00000 | 24.49385 | 52.20830 | -0.0554 | 6.55273 |
June | 496.00000 | 24.43352 | 55.13123 | -0.0506 | 6.32977 |
July | 497.00000 | 24.54754 | 56.97884 | -0.0471 | 6.70141 |
August | 514.00000 | 24.42567 | 56.96889 | -0.0955 | 6.39223 |
September | 485.00000 | 24.44973 | 57.06276 | -0.1144 | 6.77301 |
October | 502.00000 | 24.29693 | 52.67257 | 0.61337 | 13.58414 |
November | 489.00000 | 23.71875 | 46.80486 | 0.39458 | 9.03292 |
December | 497.00000 | 22.85148 | 41.29465 | 0.10688 | 6.45790 |
Annual Sum or Average | 5943.00000 | 23.96639 | 49.89019 | 0.18127 | 8.44498 |
Minimum of Months | 454.00000 | 22.58861 | 41.29465 | -0.1144 | 6.16943 |
Maximum of Months | 514.00000 | 24.54754 | 57.06276 | 0.66108 | 14.92150 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26896 | 45.49021 | -0.3296 | 8.94404 |
February | 454.00000 | 22.31590 | 47.52957 | -0.0183 | 6.70969 |
March | 514.00000 | 23.56381 | 48.01620 | 0.34402 | 8.46038 |
April | 485.00000 | 24.25104 | 46.48363 | 0.56120 | 12.18036 |
May | 508.00000 | 24.43616 | 52.63838 | -0.1147 | 6.43893 |
June | 496.00000 | 24.37830 | 55.58012 | -0.1005 | 6.17562 |
July | 497.00000 | 24.52749 | 57.55924 | -0.0647 | 6.67404 |
August | 514.00000 | 24.38649 | 57.65290 | -0.1298 | 6.40290 |
September | 485.00000 | 24.35970 | 58.03284 | -0.1762 | 6.88442 |
October | 502.00000 | 23.95842 | 54.47116 | 0.50032 | 10.83255 |
November | 489.00000 | 22.90770 | 49.56286 | 0.16145 | 6.76422 |
December | 497.00000 | 21.55260 | 44.57177 | -0.2487 | 7.82222 |
Annual Sum or Average | 5943.00000 | 23.50111 | 51.50039 | 0.03184 | 7.85910 |
Minimum of Months | 454.00000 | 21.26896 | 44.57177 | -0.3296 | 6.17562 |
Maximum of Months | 514.00000 | 24.52749 | 58.03284 | 0.56120 | 12.18036 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69402 | 44.29013 | -0.2037 | 7.53897 |
February | 454.00000 | 22.85727 | 45.94626 | 0.13611 | 7.13160 |
March | 514.00000 | 23.89630 | 46.85440 | 0.46469 | 10.61693 |
April | 485.00000 | 24.41768 | 45.79062 | 0.66244 | 15.12794 |
May | 508.00000 | 24.49873 | 52.24255 | -0.0149 | 6.76339 |
June | 496.00000 | 24.39083 | 55.34352 | -0.0457 | 6.31377 |
July | 497.00000 | 24.53565 | 57.28628 | -0.0303 | 6.94097 |
August | 514.00000 | 24.38908 | 57.41380 | -0.1005 | 6.51298 |
September | 485.00000 | 24.37523 | 57.67958 | -0.1277 | 6.87915 |
October | 502.00000 | 24.20569 | 53.44708 | 0.59718 | 13.39667 |
November | 489.00000 | 23.39452 | 47.92905 | 0.30485 | 8.17784 |
December | 497.00000 | 22.06016 | 43.18100 | -0.1076 | 6.80200 |
Annual Sum or Average | 5943.00000 | 23.73268 | 50.65787 | 0.12723 | 8.51797 |
Minimum of Months | 454.00000 | 21.69402 | 43.18100 | -0.2037 | 6.31377 |
Maximum of Months | 514.00000 | 24.53565 | 57.67958 | 0.66244 | 15.12794 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.77325 | 41.65360 | 0.07854 | 8.08728 |
February | 454.00000 | 23.45462 | 44.35083 | 0.30261 | 9.28683 |
March | 514.00000 | 24.06043 | 46.37256 | 0.51703 | 11.78523 |
April | 485.00000 | 24.39681 | 45.95023 | 0.63299 | 14.19468 |
May | 508.00000 | 24.45051 | 52.56500 | -0.0990 | 6.47586 |
June | 496.00000 | 24.37396 | 55.59786 | -0.1041 | 6.19568 |
July | 497.00000 | 24.52776 | 57.54549 | -0.0631 | 6.70541 |
August | 514.00000 | 24.41026 | 57.48585 | -0.1093 | 6.46521 |
September | 485.00000 | 24.45035 | 57.49661 | -0.0993 | 6.81909 |
October | 502.00000 | 24.47646 | 52.52215 | 0.69927 | 16.45087 |
November | 489.00000 | 24.10621 | 45.74590 | 0.52927 | 12.55669 |
December | 497.00000 | 23.22714 | 40.33723 | 0.20075 | 8.55739 |
Annual Sum or Average | 5943.00000 | 24.06277 | 49.85083 | 0.20555 | 9.45573 |
Minimum of Months | 454.00000 | 22.77325 | 40.33723 | -0.1093 | 6.19568 |
Maximum of Months | 514.00000 | 24.52776 | 57.54549 | 0.69927 | 16.45087 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79997 | 43.87197 | -0.1709 | 7.54440 |
February | 454.00000 | 22.71127 | 46.23654 | 0.11124 | 7.23610 |
March | 514.00000 | 23.79957 | 47.13011 | 0.45152 | 10.51842 |
April | 485.00000 | 24.40781 | 45.93157 | 0.66918 | 15.33271 |
May | 508.00000 | 24.47966 | 52.35803 | -0.0212 | 6.80234 |
June | 496.00000 | 24.41074 | 55.25725 | -0.0174 | 6.49420 |
July | 497.00000 | 24.53043 | 57.16772 | -0.0195 | 6.92194 |
August | 514.00000 | 24.40668 | 57.22017 | -0.0756 | 6.50031 |
September | 485.00000 | 24.37732 | 57.59839 | -0.1156 | 6.97850 |
October | 502.00000 | 24.14007 | 53.70258 | 0.58962 | 13.26908 |
November | 489.00000 | 23.29280 | 48.12693 | 0.29607 | 8.20929 |
December | 497.00000 | 22.14509 | 42.81317 | -0.0755 | 6.99540 |
Annual Sum or Average | 5943.00000 | 23.71579 | 50.65656 | 0.13471 | 8.56640 |
Minimum of Months | 454.00000 | 21.79997 | 42.81317 | -0.1709 | 6.49420 |
Maximum of Months | 514.00000 | 24.53043 | 57.59839 | 0.66918 | 15.33271 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.788312E+11 | 114743.41 | 25-JAN-14:30 | 417.80 | 0.439728E+12 | 0.00 | 0.518559E+12 | 2.79 | 6.95 | 25-JAN-14:30 | 0.00 | 0.00 |
February | 0.975722E+11 | 120384.45 | 16-FEB-15:30 | 415.30 | 0.572794E+12 | 0.00 | 0.670367E+12 | 3.32 | 7.03 | 16-FEB-15:30 | 0.00 | 0.00 |
March | 0.161142E+12 | 163318.51 | 30-MAR-05:04 | 566.85 | 0.101496E+13 | 0.00 | 0.117610E+13 | 4.45 | 7.27 | 30-MAR-05:04 | 0.00 | 0.00 |
April | 0.214442E+12 | 213567.34 | 17-APR-05:03 | 669.04 | 0.139624E+13 | 0.00 | 0.161068E+13 | 5.63 | 7.30 | 28-APR-05:03 | 0.00 | 0.00 |
May | 0.288679E+12 | 230262.15 | 22-MAY-05:02 | 685.27 | 0.188277E+13 | 0.00 | 0.217145E+13 | 5.82 | 7.34 | 15-MAY-05:03 | 0.00 | 0.00 |
June | 0.323444E+12 | 256374.93 | 28-JUN-12:10 | 667.09 | 0.205822E+13 | 0.00 | 0.238167E+13 | 5.72 | 7.29 | 12-JUN-05:02 | 0.00 | 0.00 |
July | 0.367868E+12 | 256409.92 | 17-JUL-10:50 | 703.84 | 0.227081E+13 | 0.00 | 0.263868E+13 | 5.59 | 7.08 | 19-JUL-05:03 | 0.00 | 0.00 |
August | 0.370016E+12 | 256426.42 | 28-AUG-10:40 | 709.64 | 0.228223E+13 | 0.00 | 0.265225E+13 | 5.57 | 7.24 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.275141E+12 | 250060.33 | 14-SEP-16:00 | 599.71 | 0.173800E+13 | 0.00 | 0.201314E+13 | 5.01 | 7.24 | 26-SEP-05:03 | 0.00 | 0.00 |
October | 0.191894E+12 | 193304.24 | 04-OCT-05:03 | 592.41 | 0.124440E+13 | 0.00 | 0.143630E+13 | 4.84 | 7.33 | 19-OCT-05:03 | 0.00 | 0.00 |
November | 0.134028E+12 | 135920.62 | 21-NOV-15:00 | 515.83 | 0.819936E+12 | 0.00 | 0.953964E+12 | 4.01 | 7.05 | 21-NOV-15:00 | 0.00 | 0.00 |
December | 0.918805E+11 | 119338.99 | 28-DEC-15:00 | 456.89 | 0.526710E+12 | 0.00 | 0.618590E+12 | 3.13 | 7.02 | 28-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259494E+13 | 6999.67 | 0.162468E+14 | 0.00 | 0.188418E+14 | 4.66 | 0.00 | 0.00 | ||||
Minimum of Months | 0.788312E+11 | 114743.41 | 415.30 | 0.439728E+12 | 0.00 | 0.518559E+12 | 2.79 | 6.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.370016E+12 | 256426.42 | 709.64 | 0.228223E+13 | 0.00 | 0.265225E+13 | 5.82 | 7.34 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 67688819.01 | 112814.70 | 23-FEB-16:30 | 0.17 | 0.468145E+09 | 0.00 | 0.535834E+09 | 0.00 | 6.92 | 23-FEB-16:30 | 0.00 | 0.00 |
March | 0.258247E+11 | 163318.51 | 30-MAR-05:04 | 60.44 | 0.179395E+12 | 0.00 | 0.205220E+12 | 0.56 | 7.27 | 30-MAR-05:04 | 0.00 | 0.00 |
April | 0.812107E+11 | 213567.34 | 17-APR-05:03 | 177.12 | 0.562243E+12 | 0.00 | 0.643453E+12 | 1.70 | 7.30 | 28-APR-05:03 | 0.00 | 0.00 |
May | 0.169143E+12 | 230262.15 | 22-MAY-05:02 | 319.42 | 0.113479E+13 | 0.00 | 0.130394E+13 | 2.88 | 7.34 | 15-MAY-05:03 | 0.00 | 0.00 |
June | 0.253293E+12 | 256374.93 | 28-JUN-12:10 | 439.21 | 0.164405E+13 | 0.00 | 0.189735E+13 | 3.97 | 7.29 | 12-JUN-05:02 | 0.00 | 0.00 |
July | 0.325662E+12 | 256409.92 | 17-JUL-10:50 | 529.87 | 0.206221E+13 | 0.00 | 0.238787E+13 | 4.52 | 7.08 | 19-JUL-05:03 | 0.00 | 0.00 |
August | 0.328042E+12 | 256426.42 | 28-AUG-10:40 | 518.52 | 0.207945E+13 | 0.00 | 0.240749E+13 | 4.43 | 7.24 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.226422E+12 | 250060.33 | 14-SEP-16:00 | 407.88 | 0.146808E+13 | 0.00 | 0.169450E+13 | 3.68 | 7.24 | 26-SEP-05:03 | 0.00 | 0.00 |
October | 0.665488E+11 | 193304.24 | 04-OCT-05:03 | 145.68 | 0.458634E+12 | 0.00 | 0.525183E+12 | 1.35 | 7.33 | 19-OCT-05:03 | 0.00 | 0.00 |
November | 0.131932E+11 | 128384.55 | 06-NOV-13:10 | 31.71 | 0.916266E+11 | 0.00 | 0.104820E+12 | 0.31 | 7.05 | 21-NOV-15:50 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.148941E+13 | 2630.01 | 0.968094E+13 | 0.00 | 0.111703E+14 | 1.96 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.328042E+12 | 256426.42 | 529.87 | 0.207945E+13 | 0.00 | 0.240749E+13 | 4.52 | 7.34 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.662872E+11 | 744.00 | 49248.27 | 02-JAN-13:30 | 215366.98 | 12-JAN-17:00 | 22.68 | 19.07 | 14.72 |
February | 0.101168E+12 | 672.00 | 49248.27 | 01-FEB-10:20 | 379448.59 | 24-FEB-16:10 | 28.02 | 21.42 | 14.72 |
March | 0.131870E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 650394.70 | 31-MAR-24:00 | 36.95 | 27.20 | 14.72 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 720464.12 | 16-APR-17:22 | 48.61 | 35.66 | 14.72 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 379859.50 | 31-MAY-23:50 | 39.87 | 35.27 | 14.72 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 558030.78 | 30-JUN-23:53 | 45.36 | 37.53 | 14.72 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 689672.06 | 31-JUL-24:00 | 48.03 | 37.15 | 14.72 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 726583.78 | 25-AUG-15:10 | 50.14 | 36.79 | 14.72 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 377752.74 | 30-SEP-23:17 | 35.71 | 31.05 | 14.72 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 487889.00 | 31-OCT-23:40 | 35.80 | 28.63 | 14.72 |
November | 0.125529E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 550900.07 | 08-NOV-16:10 | 34.19 | 24.54 | 14.72 |
December | 0.122083E+12 | 744.00 | 49248.27 | 01-DEC-07:00 | 671219.89 | 28-DEC-16:30 | 33.56 | 21.43 | 14.72 |
Annual Sum or Average | 0.145752E+13 | 8760.00 | 38.30 | 29.69 | 14.72 | ||||
Minimum of Months | 0.662872E+11 | 672.00 | 49248.27 | 215366.98 | 22.68 | 19.07 | 14.72 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 726583.78 | 50.14 | 37.53 | 14.72 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.215174E+10 | 275.06 | 8563.62 | 12-JAN-15:30 | 1128182.40 | 25-JAN-15:50 | 21.84 | 21.20 | 36.25 |
February | 0.530285E+10 | 334.00 | 18937.67 | 24-FEB-15:40 | 1417974.87 | 22-FEB-15:10 | 22.30 | 21.32 | 44.27 |
March | 0.177266E+11 | 524.68 | 23675.58 | 06-MAR-11:50 | 1507071.87 | 30-MAR-05:04 | 22.90 | 21.30 | 57.97 |
April | 0.363278E+11 | 656.30 | 23675.58 | 01-APR-09:00 | 1552774.40 | 07-APR-15:20 | 23.83 | 21.66 | 71.55 |
May | 0.552615E+11 | 685.27 | 23675.58 | 01-MAY-03:45 | 1630614.47 | 17-MAY-15:30 | 26.55 | 23.93 | 70.52 |
June | 0.567870E+11 | 667.09 | 23675.58 | 01-JUN-00:12 | 1829582.86 | 21-JUN-13:50 | 28.98 | 26.03 | 69.04 |
July | 0.599897E+11 | 703.84 | 23675.58 | 01-JUL-00:03 | 1830443.70 | 17-JUL-11:00 | 30.85 | 27.69 | 69.11 |
August | 0.604841E+11 | 709.64 | 23675.58 | 01-AUG-00:03 | 1830665.02 | 24-AUG-14:40 | 30.72 | 27.55 | 70.69 |
September | 0.510709E+11 | 599.71 | 23675.58 | 01-SEP-00:03 | 1793343.49 | 14-SEP-16:00 | 28.88 | 26.38 | 61.95 |
October | 0.345310E+11 | 586.56 | 23675.58 | 01-OCT-00:42 | 1417579.18 | 24-OCT-10:40 | 23.62 | 21.80 | 61.51 |
November | 0.116753E+11 | 441.61 | 23675.58 | 06-NOV-10:40 | 1456840.63 | 01-NOV-14:00 | 22.61 | 21.23 | 53.38 |
December | 0.313414E+10 | 309.07 | 11522.99 | 28-DEC-14:00 | 1252551.63 | 01-DEC-16:10 | 21.91 | 21.15 | 41.32 |
Annual Sum or Average | 0.394443E+12 | 6492.82 | 25.43 | 23.45 | 59.03 | ||||
Minimum of Months | 0.215174E+10 | 275.06 | 8563.62 | 1128182.40 | 21.84 | 21.15 | 36.25 | ||
Maximum of Months | 0.604841E+11 | 709.64 | 23675.58 | 1830665.02 | 30.85 | 27.69 | 71.55 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 21.84 | 21.84 | 0.00 |
February | 5890709.78 | 0.17 | 9817.85 | 23-FEB-16:30 | 1380821.19 | 23-FEB-16:30 | 22.30 | 22.30 | 0.02 |
March | 0.247310E+10 | 29.73 | 23675.58 | 07-MAR-11:40 | 1507071.87 | 30-MAR-05:04 | 22.90 | 22.76 | 3.08 |
April | 0.120233E+11 | 143.89 | 23675.58 | 03-APR-08:40 | 1552774.40 | 07-APR-15:20 | 23.83 | 23.12 | 15.39 |
May | 0.281645E+11 | 330.45 | 23675.58 | 01-MAY-05:02 | 1630614.47 | 17-MAY-15:30 | 26.55 | 24.97 | 33.73 |
June | 0.414574E+11 | 486.41 | 23675.58 | 01-JUN-03:02 | 1829582.86 | 21-JUN-13:50 | 28.98 | 26.50 | 49.71 |
July | 0.513203E+11 | 602.12 | 23675.58 | 01-JUL-00:03 | 1830443.70 | 17-JUL-11:00 | 30.85 | 27.83 | 58.59 |
August | 0.487849E+11 | 572.38 | 23675.58 | 01-AUG-00:10 | 1830665.02 | 24-AUG-14:40 | 30.72 | 27.72 | 56.48 |
September | 0.383789E+11 | 450.29 | 23675.58 | 01-SEP-00:15 | 1793343.49 | 14-SEP-16:00 | 28.88 | 26.66 | 45.96 |
October | 0.998479E+10 | 117.21 | 23675.58 | 01-OCT-01:10 | 1380875.69 | 03-OCT-05:05 | 23.62 | 23.09 | 12.13 |
November | 0.824296E+09 | 13.50 | 23675.58 | 06-NOV-12:50 | 1456840.63 | 01-NOV-14:00 | 22.61 | 22.53 | 1.44 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.91 | 21.91 | 0.00 |
Annual Sum or Average | 0.233417E+12 | 2746.14 | 25.43 | 24.28 | 23.18 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 | 21.84 | 0.00 | ||
Maximum of Months | 0.513203E+11 | 602.12 | 23675.58 | 1830665.02 | 30.85 | 27.83 | 58.59 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.572096E+11 | 0.00 | 197.68 | 425968.22 | 02-JAN-06:04 | 0.00 | 38.38 | 49.64 | 0.14 | 0.00 | 0.02 | 0.30 | 02-JAN-06:04 |
February | 0.183748E+11 | 0.00 | 87.66 | 327458.38 | 04-FEB-06:08 | 0.00 | 33.38 | 39.31 | 0.05 | 0.00 | 0.01 | 0.23 | 04-FEB-06:08 |
March | 8873062.74 | 0.00 | 2.14 | 4406.44 | 01-MAR-05:20 | 0.00 | 28.55 | 28.70 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-05:20 |
April | 6351.78 | 0.00 | 0.17 | 10.59 | 27-APR-11:00 | 0.00 | 28.54 | 28.56 | 0.00 | 0.00 | 0.00 | 0.00 | 27-APR-11:00 |
May | 6355.93 | 0.00 | 0.17 | 10.59 | 19-MAY-14:30 | 0.00 | 28.54 | 28.56 | 0.00 | 0.00 | 0.00 | 0.00 | 19-MAY-14:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 491.37 | 0.00 | 0.03 | 4.09 | 09-OCT-07:52 | 0.00 | 28.54 | 28.55 | 0.00 | 0.00 | 0.00 | 0.00 | 09-OCT-07:52 |
November | 0.293736E+10 | 0.00 | 28.50 | 175983.11 | 27-NOV-06:10 | 0.00 | 29.71 | 31.65 | 0.01 | 0.00 | 0.00 | 0.12 | 27-NOV-06:10 |
December | 0.338960E+11 | 0.00 | 177.00 | 337490.72 | 23-DEC-06:08 | 0.00 | 33.82 | 44.66 | 0.08 | 0.00 | 0.01 | 0.24 | 23-DEC-06:08 |
Annual Sum or Average | 0.112427E+12 | 0.00 | 493.34 | 0.00 | 30.29 | 32.80 | 0.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.572096E+11 | 0.00 | 197.68 | 425968.22 | 0.00 | 38.38 | 49.64 | 0.14 | 0.00 | 0.02 | 0.30 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 22.68 | 22.68 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 28.02 | 28.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.95 | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 48.61 | 48.61 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 39.87 | 39.87 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 45.36 | 45.36 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 48.03 | 48.03 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 50.14 | 50.14 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 35.71 | 35.71 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 35.80 | 35.80 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 34.19 | 34.19 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.56 | 33.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.30 | 38.30 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 22.68 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 50.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.430529E+11 | 0.00 | 337.22 | 0.430212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93564.44 | 02-JAN-06:03 | 84188.92 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 |
February | 0.640763E+11 | 0.00 | 382.21 | 0.639421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143153.15 | 25-FEB-04:02 | 112926.04 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.127796E+12 | 0.00 | 547.86 | 0.125758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 205815.13 | 14-MAR-05:03 | 155988.20 | 14-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.201841E+12 | 0.00 | 625.01 | 0.192281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269308.63 | 17-APR-05:03 | 187871.17 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.265645E+12 | 0.00 | 612.82 | 0.216240E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299686.69 | 22-MAY-05:02 | 209718.14 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.326590E+12 | 0.00 | 608.54 | 0.223482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 333376.73 | 26-JUN-04:12 | 216534.00 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.392101E+12 | 0.00 | 637.96 | 0.212508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349445.89 | 18-JUL-05:03 | 201703.86 | 05-JUL-04:32 | 0.00 | 0.00 | 0.00 |
August | 0.421781E+12 | 0.00 | 660.11 | 0.221304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352011.27 | 28-AUG-04:22 | 194491.05 | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.284652E+12 | 0.00 | 536.83 | 0.160253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 323895.79 | 05-SEP-03:02 | 180890.90 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.167162E+12 | 0.00 | 546.37 | 0.143617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268176.59 | 11-OCT-05:03 | 171362.02 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.101684E+12 | 0.00 | 476.04 | 0.100742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 162277.79 | 06-NOV-06:03 | 135688.68 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.629009E+11 | 0.00 | 412.02 | 0.629009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107797.90 | 29-DEC-06:03 | 107797.90 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245928E+13 | 0.00 | 6382.98 | 0.176605E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.430529E+11 | 0.00 | 337.22 | 0.430212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93564.44 | 84188.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.421781E+12 | 0.00 | 660.11 | 0.223482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352011.27 | 216534.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.292614E+12 | 0.00 | 290.44 | 0.292594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 858787.78 | 18-JAN-06:02 | 763682.83 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.465179E+12 | 0.00 | 333.16 | 0.463893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1335250.62 | 25-FEB-06:02 | 947945.45 | 22-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 0.100068E+13 | 0.00 | 472.53 | 0.985698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2087346.66 | 11-MAR-06:02 | 1543887.60 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.160852E+13 | 0.00 | 515.06 | 0.153850E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2319218.39 | 17-APR-05:02 | 1685060.73 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.249288E+13 | 0.00 | 586.54 | 0.201321E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3184945.36 | 24-MAY-03:02 | 1865710.05 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.296692E+13 | 0.00 | 564.06 | 0.199482E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3336617.41 | 29-JUN-05:03 | 1938907.56 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.338482E+13 | 0.00 | 559.31 | 0.176194E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3596906.02 | 25-JUL-03:02 | 1872022.28 | 07-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.336888E+13 | 0.00 | 545.66 | 0.166311E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3497735.43 | 11-AUG-03:02 | 1798818.43 | 08-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.253262E+13 | 0.00 | 478.49 | 0.139040E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3337720.37 | 11-SEP-03:02 | 1699405.62 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.139517E+13 | 0.00 | 479.96 | 0.119290E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2579318.64 | 04-OCT-03:02 | 1612477.69 | 04-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.758642E+12 | 0.00 | 420.52 | 0.753137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1499219.40 | 09-NOV-06:03 | 1066110.32 | 08-NOV-15:10 | 0.00 | 0.00 | 0.00 |
December | 0.360288E+12 | 0.00 | 318.42 | 0.360288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 815832.01 | 29-DEC-06:03 | 815832.01 | 29-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206272E+14 | 0.00 | 5564.14 | 0.144105E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.292614E+12 | 0.00 | 290.44 | 0.292594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 815832.01 | 763682.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.338482E+13 | 0.00 | 586.54 | 0.201321E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3596906.02 | 1938907.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208903E+11 | 0.00 | 260.42 | 0.208903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68078.97 | 12-JAN-15:00 | 68078.97 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.418387E+11 | 0.00 | 310.79 | 0.417231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123144.95 | 25-FEB-06:02 | 106771.47 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.102997E+12 | 0.00 | 455.47 | 0.101626E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 205041.87 | 11-MAR-06:02 | 166438.78 | 28-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.179099E+12 | 0.00 | 520.28 | 0.172033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261189.92 | 27-APR-05:03 | 197247.52 | 27-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.280010E+12 | 0.00 | 598.44 | 0.230050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322399.56 | 22-MAY-05:02 | 219574.17 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 |
June | 0.330319E+12 | 0.00 | 575.53 | 0.229026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 366540.81 | 29-JUN-05:03 | 229068.48 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.370140E+12 | 0.00 | 576.10 | 0.199831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 389580.37 | 18-JUL-05:03 | 222386.54 | 05-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.361733E+12 | 0.00 | 556.86 | 0.185116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 377870.57 | 10-AUG-05:03 | 203008.15 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.270393E+12 | 0.00 | 491.74 | 0.151985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 365329.73 | 11-SEP-03:02 | 182981.95 | 16-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.143907E+12 | 0.00 | 472.93 | 0.124952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250752.91 | 11-OCT-03:02 | 168897.06 | 02-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.716544E+11 | 0.00 | 395.51 | 0.714217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137318.31 | 10-NOV-06:02 | 121038.56 | 08-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.274376E+11 | 0.00 | 290.21 | 0.274376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76206.47 | 28-DEC-15:00 | 76206.47 | 28-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220042E+13 | 0.00 | 5504.28 | 0.155609E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.208903E+11 | 0.00 | 260.42 | 0.208903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68078.97 | 68078.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.370140E+12 | 0.00 | 598.44 | 0.230050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 389580.37 | 229068.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.572262E+11 | 0.00 | 402.30 | 0.571302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131425.39 | 18-JAN-04:03 | 96862.41 | 18-JAN-04:03 | 0.00 | 0.00 | 0.00 |
February | 0.584359E+11 | 0.00 | 376.30 | 0.583337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141975.86 | 25-FEB-04:02 | 111012.08 | 20-FEB-14:52 | 0.00 | 0.00 | 0.00 |
March | 0.800910E+11 | 0.00 | 446.20 | 0.797856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165426.40 | 11-MAR-04:02 | 105585.59 | 27-MAR-03:13 | 0.00 | 0.00 | 0.00 |
April | 0.914767E+11 | 0.00 | 419.38 | 0.894053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164193.93 | 24-APR-03:02 | 127976.65 | 16-APR-17:30 | 0.00 | 0.00 | 0.00 |
May | 0.117337E+12 | 0.00 | 455.34 | 0.104633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198742.01 | 22-MAY-03:13 | 134858.89 | 29-MAY-15:44 | 0.00 | 0.00 | 0.00 |
June | 0.137207E+12 | 0.00 | 456.37 | 0.108715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236263.89 | 26-JUN-03:02 | 131535.37 | 04-JUN-16:07 | 0.00 | 0.00 | 0.00 |
July | 0.158194E+12 | 0.00 | 473.56 | 0.108157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250145.32 | 23-JUL-19:36 | 123423.61 | 04-JUL-16:49 | 0.00 | 0.00 | 0.00 |
August | 0.176498E+12 | 0.00 | 503.76 | 0.116683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257507.09 | 27-AUG-11:46 | 115307.03 | 06-AUG-15:37 | 0.00 | 0.00 | 0.00 |
September | 0.140816E+12 | 0.00 | 469.14 | 0.100953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239430.35 | 11-SEP-00:32 | 112237.92 | 24-SEP-14:57 | 0.00 | 0.00 | 0.00 |
October | 0.103132E+12 | 0.00 | 478.11 | 0.959612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180804.89 | 04-OCT-03:02 | 123754.92 | 01-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.801098E+11 | 0.00 | 444.57 | 0.797266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152505.79 | 09-NOV-04:03 | 119030.92 | 05-NOV-13:17 | 0.00 | 0.00 | 0.00 |
December | 0.648993E+11 | 0.00 | 419.27 | 0.648550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126074.69 | 30-DEC-04:02 | 102366.20 | 29-DEC-04:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126542E+13 | 0.00 | 5344.28 | 0.106434E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.572262E+11 | 0.00 | 376.30 | 0.571302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126074.69 | 96862.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.176498E+12 | 0.00 | 503.76 | 0.116683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257507.09 | 134858.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.338674E+12 | 0.877475E+11 | 744.00 | 0.325024E+12 | 0.136501E+11 | 0.00 | 0.36 | 12-JAN-16:00 | 0.32 | 22-JAN-06:00 | 132372.64 | 17-JAN-16:00 | 127907.59 | 12-JAN-15:00 | 6654.00 | 17-JAN-16:00 | 41398.21 | 12-JAN-15:00 | 0.00 |
February | 0.533999E+12 | 0.142039E+12 | 672.00 | 0.517087E+12 | 0.169112E+11 | 0.00 | 0.60 | 22-FEB-15:00 | 0.53 | 01-FEB-00:10 | 226098.73 | 24-FEB-17:00 | 220664.49 | 22-FEB-15:00 | 10353.55 | 27-FEB-09:40 | 77866.66 | 22-FEB-15:00 | 0.00 |
March | 0.836927E+12 | 0.254745E+12 | 744.00 | 0.822905E+12 | 0.140222E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.74 | 01-MAR-02:70 | 396190.99 | 31-MAR-24:00 | 393957.35 | 31-MAR-23:55 | 13900.97 | 05-MAR-06:00 | 136774.81 | 28-MAR-15:30 | 0.00 |
April | 0.103526E+13 | 0.370178E+12 | 720.00 | 0.102905E+13 | 0.621167E+10 | 0.00 | 1.00 | 01-APR-08:20 | 0.42 | 30-APR-24:00 | 410045.05 | 25-APR-04:55 | 403747.61 | 30-APR-04:30 | 8779.16 | 26-APR-21:00 | 173943.93 | 15-APR-15:00 | 0.00 |
May | 0.363416E+12 | 0.148995E+12 | 744.00 | 0.346666E+12 | 0.167505E+11 | 0.00 | 0.60 | 31-MAY-23:13 | 0.35 | 28-MAY-05:00 | 226630.51 | 31-MAY-23:03 | 213137.81 | 31-MAY-24:00 | 15173.77 | 22-MAY-23:10 | 79221.09 | 31-MAY-23:13 | 0.00 |
June | 0.599388E+12 | 0.245972E+12 | 720.00 | 0.573781E+12 | 0.256064E+11 | 0.00 | 0.85 | 30-JUN-24:00 | 0.58 | 18-JUN-05:00 | 318667.16 | 30-JUN-23:03 | 307413.68 | 30-JUN-23:57 | 18592.71 | 28-JUN-13:30 | 127702.42 | 30-JUN-23:33 | 0.00 |
July | 0.874812E+12 | 0.339884E+12 | 744.00 | 0.838275E+12 | 0.365378E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.80 | 19-JUL-03:00 | 401697.40 | 31-JUL-24:00 | 390330.61 | 31-JUL-24:00 | 19569.20 | 18-JUL-08:30 | 157845.49 | 07-JUL-15:00 | 0.00 |
August | 0.110063E+13 | 0.392197E+12 | 744.00 | 0.106510E+13 | 0.355238E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.44 | 31-AUG-23:17 | 422135.51 | 10-AUG-14:00 | 405135.28 | 15-AUG-23:55 | 20796.46 | 31-AUG-23:13 | 166617.87 | 07-AUG-15:00 | 0.00 |
September | 0.367387E+12 | 0.132622E+12 | 720.00 | 0.336171E+12 | 0.312161E+11 | 0.00 | 0.59 | 30-SEP-23:13 | 0.36 | 27-SEP-05:00 | 227193.75 | 30-SEP-23:05 | 213794.66 | 30-SEP-23:57 | 18113.39 | 12-SEP-16:00 | 76336.24 | 30-SEP-23:13 | 0.00 |
October | 0.602783E+12 | 0.198141E+12 | 744.00 | 0.586394E+12 | 0.163896E+11 | 0.00 | 0.76 | 31-OCT-23:30 | 0.55 | 31-OCT-05:00 | 311080.24 | 31-OCT-24:00 | 302623.05 | 31-OCT-24:00 | 11523.38 | 13-OCT-08:30 | 102056.81 | 02-OCT-15:00 | 0.00 |
November | 0.818526E+12 | 0.230139E+12 | 720.00 | 0.798970E+12 | 0.195565E+11 | 0.00 | 0.84 | 08-NOV-15:00 | 0.75 | 26-NOV-06:00 | 321931.75 | 24-NOV-08:15 | 314936.80 | 08-NOV-15:00 | 14621.68 | 23-NOV-08:00 | 118982.30 | 08-NOV-15:00 | 0.00 |
December | 0.110013E+13 | 0.270435E+12 | 744.00 | 0.106547E+13 | 0.346571E+11 | 0.00 | 1.00 | 25-DEC-13:57 | 0.93 | 01-DEC-00:10 | 422266.44 | 22-DEC-06:03 | 404440.30 | 28-DEC-17:00 | 25597.34 | 22-DEC-06:03 | 130566.31 | 28-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.857192E+13 | 0.281309E+13 | 8760.00 | 0.830489E+13 | 0.267033E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338674E+12 | 0.877475E+11 | 672.00 | 0.325024E+12 | 0.621167E+10 | 0.00 | 0.36 | 0.32 | 132372.64 | 127907.59 | 6654.00 | 41398.21 | 0.00 | ||||||
Maximum of Months | 0.110063E+13 | 0.392197E+12 | 744.00 | 0.106547E+13 | 0.365378E+11 | 0.00 | 1.00 | 0.93 | 422266.44 | 405135.28 | 25597.34 | 173943.93 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.497121E+10 | 0.129571E+10 | 744.00 | 0.482668E+10 | 0.144532E+09 | 0.00 | 0.32 | 12-JAN-17:00 | 0.17 | 07-JAN-08:00 | 2497.49 | 12-JAN-17:00 | 2367.43 | 12-JAN-17:00 | 248.75 | 17-JAN-16:00 | 744.79 | 12-JAN-16:00 | 0.00 |
February | 0.958723E+10 | 0.253037E+10 | 672.00 | 0.936120E+10 | 0.226029E+09 | 0.00 | 0.56 | 21-FEB-17:00 | 0.40 | 01-FEB-07:00 | 4544.48 | 21-FEB-17:00 | 4394.85 | 21-FEB-17:00 | 267.95 | 15-FEB-17:00 | 1500.87 | 22-FEB-15:00 | 0.00 |
March | 0.162276E+11 | 0.484542E+10 | 744.00 | 0.158972E+11 | 0.330348E+09 | 0.00 | 0.91 | 31-MAR-24:00 | 0.63 | 01-MAR-07:00 | 7788.30 | 31-MAR-24:00 | 7688.52 | 31-MAR-23:55 | 336.11 | 10-MAR-17:10 | 2736.04 | 28-MAR-16:00 | 0.00 |
April | 0.209214E+11 | 0.745845E+10 | 720.00 | 0.206144E+11 | 0.306981E+09 | 0.00 | 1.00 | 01-APR-14:10 | 0.39 | 30-APR-23:05 | 8513.86 | 17-APR-00:12 | 8276.97 | 17-APR-00:05 | 382.91 | 26-APR-08:00 | 3579.20 | 15-APR-15:00 | 0.00 |
May | 0.721026E+10 | 0.284871E+10 | 744.00 | 0.655003E+10 | 0.660233E+09 | 0.00 | 0.56 | 31-MAY-23:03 | 0.28 | 13-MAY-07:00 | 4644.81 | 31-MAY-23:03 | 4077.14 | 31-MAY-24:00 | 643.47 | 22-MAY-23:10 | 1605.64 | 01-MAY-15:40 | 0.00 |
June | 0.123209E+11 | 0.485036E+10 | 720.00 | 0.112422E+11 | 0.107871E+10 | 0.00 | 0.81 | 30-JUN-23:12 | 0.54 | 02-JUN-06:00 | 6536.06 | 30-JUN-23:03 | 6051.51 | 30-JUN-24:00 | 812.17 | 28-JUN-13:40 | 2553.34 | 08-JUN-16:00 | 0.00 |
July | 0.181653E+11 | 0.676586E+10 | 744.00 | 0.165573E+11 | 0.160795E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.75 | 19-JUL-03:00 | 8585.00 | 31-JUL-23:03 | 7854.92 | 31-JUL-24:00 | 845.52 | 18-JUL-08:20 | 3274.81 | 02-JUL-16:50 | 0.00 |
August | 0.228481E+11 | 0.807663E+10 | 744.00 | 0.211574E+11 | 0.169063E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.37 | 31-AUG-23:04 | 8810.19 | 10-AUG-14:10 | 8088.05 | 29-AUG-03:32 | 862.05 | 21-AUG-14:00 | 3434.61 | 07-AUG-15:00 | 0.00 |
September | 0.735223E+10 | 0.252334E+10 | 720.00 | 0.608339E+10 | 0.126883E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.30 | 27-SEP-06:00 | 4627.40 | 30-SEP-23:05 | 4046.94 | 30-SEP-23:50 | 733.21 | 12-SEP-16:00 | 1480.30 | 30-SEP-23:13 | 0.00 |
October | 0.117135E+11 | 0.374515E+10 | 744.00 | 0.110957E+11 | 0.617720E+09 | 0.00 | 0.69 | 31-OCT-23:20 | 0.47 | 28-OCT-06:50 | 5980.60 | 31-OCT-23:10 | 5779.23 | 31-OCT-24:00 | 494.43 | 06-OCT-09:40 | 2048.31 | 02-OCT-15:00 | 0.00 |
November | 0.155748E+11 | 0.431822E+10 | 720.00 | 0.152648E+11 | 0.309985E+09 | 0.00 | 0.80 | 08-NOV-16:20 | 0.63 | 25-NOV-08:00 | 6598.18 | 08-NOV-16:40 | 6349.74 | 08-NOV-16:30 | 283.11 | 08-NOV-20:00 | 2337.62 | 08-NOV-15:00 | 0.00 |
December | 0.205473E+11 | 0.503908E+10 | 744.00 | 0.203775E+11 | 0.169842E+09 | 0.00 | 0.96 | 28-DEC-16:40 | 0.80 | 23-DEC-08:00 | 8274.71 | 28-DEC-17:00 | 8114.34 | 28-DEC-17:00 | 252.92 | 29-DEC-17:10 | 2567.92 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.167440E+12 | 0.542973E+11 | 8760.00 | 0.159028E+12 | 0.841180E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.497121E+10 | 0.129571E+10 | 672.00 | 0.482668E+10 | 0.144532E+09 | 0.00 | 0.32 | 0.17 | 2497.49 | 2367.43 | 248.75 | 744.79 | 0.00 | ||||||
Maximum of Months | 0.228481E+11 | 0.807663E+10 | 744.00 | 0.211574E+11 | 0.169063E+10 | 0.00 | 1.00 | 0.80 | 8810.19 | 8276.97 | 862.05 | 3579.20 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.377004E+11 | 0.100216E+11 | 744.00 | 0.363412E+11 | 0.135921E+10 | 0.00 | 0.31 | 12-JAN-17:00 | 0.11 | 03-JAN-08:00 | 23183.23 | 13-JAN-17:00 | 21896.42 | 12-JAN-17:00 | 2413.76 | 17-JAN-16:10 | 6882.90 | 12-JAN-16:50 | 0.00 |
February | 0.854044E+11 | 0.227327E+11 | 672.00 | 0.831714E+11 | 0.223295E+10 | 0.00 | 0.56 | 22-FEB-17:00 | 0.35 | 11-FEB-08:00 | 42880.72 | 22-FEB-17:00 | 41361.12 | 21-FEB-17:00 | 2654.62 | 15-FEB-17:00 | 14208.72 | 22-FEB-15:00 | 0.00 |
March | 0.153092E+12 | 0.458082E+11 | 744.00 | 0.149800E+12 | 0.329164E+10 | 0.00 | 0.92 | 31-MAR-24:00 | 0.61 | 01-MAR-07:00 | 75195.09 | 31-MAR-24:00 | 74191.72 | 31-MAR-23:55 | 3342.80 | 10-MAR-17:10 | 26072.56 | 28-MAR-16:00 | 0.00 |
April | 0.198702E+12 | 0.708997E+11 | 720.00 | 0.195624E+12 | 0.307826E+10 | 0.00 | 1.00 | 01-APR-13:50 | 0.33 | 30-APR-24:00 | 80614.87 | 12-APR-16:00 | 78376.67 | 12-APR-16:10 | 3829.96 | 26-APR-08:00 | 34102.27 | 15-APR-15:00 | 0.00 |
May | 0.681529E+11 | 0.269279E+11 | 744.00 | 0.616266E+11 | 0.652635E+10 | 0.00 | 0.57 | 31-MAY-23:13 | 0.27 | 13-MAY-07:00 | 44851.89 | 31-MAY-23:03 | 39268.90 | 31-MAY-24:00 | 6305.86 | 22-MAY-23:22 | 14886.48 | 31-MAY-23:13 | 0.00 |
June | 0.117526E+12 | 0.462156E+11 | 720.00 | 0.106798E+12 | 0.107282E+11 | 0.00 | 0.82 | 30-JUN-23:12 | 0.53 | 02-JUN-06:00 | 63227.46 | 30-JUN-23:03 | 58313.81 | 30-JUN-23:55 | 8086.71 | 28-JUN-13:30 | 24342.40 | 08-JUN-16:00 | 0.00 |
July | 0.173524E+12 | 0.645328E+11 | 744.00 | 0.157491E+12 | 0.160330E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.76 | 19-JUL-03:00 | 81906.53 | 31-JUL-23:03 | 75042.59 | 31-JUL-24:00 | 8431.78 | 18-JUL-08:20 | 30883.14 | 02-JUL-17:00 | 0.00 |
August | 0.216971E+12 | 0.768717E+11 | 744.00 | 0.200030E+12 | 0.169407E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.33 | 31-AUG-23:04 | 83828.02 | 10-AUG-14:10 | 76413.16 | 16-AUG-10:00 | 8598.21 | 21-AUG-14:00 | 32719.76 | 07-AUG-15:00 | 0.00 |
September | 0.691594E+11 | 0.237151E+11 | 720.00 | 0.566274E+11 | 0.125320E+11 | 0.00 | 0.57 | 30-SEP-23:05 | 0.28 | 09-SEP-17:20 | 44957.67 | 30-SEP-23:05 | 39195.35 | 30-SEP-23:57 | 7254.05 | 12-SEP-16:00 | 14323.92 | 30-SEP-23:13 | 0.00 |
October | 0.110266E+12 | 0.353065E+11 | 744.00 | 0.104139E+12 | 0.612740E+10 | 0.00 | 0.68 | 31-OCT-23:20 | 0.44 | 31-OCT-06:00 | 56384.60 | 31-OCT-23:10 | 54341.71 | 31-OCT-24:00 | 4932.72 | 06-OCT-09:40 | 19447.71 | 02-OCT-15:00 | 0.00 |
November | 0.144479E+12 | 0.402404E+11 | 720.00 | 0.141393E+12 | 0.308638E+10 | 0.00 | 0.80 | 08-NOV-16:20 | 0.59 | 25-NOV-08:00 | 62666.39 | 08-NOV-16:50 | 60169.14 | 08-NOV-16:30 | 2790.50 | 08-NOV-20:00 | 22182.25 | 08-NOV-15:00 | 0.00 |
December | 0.187507E+12 | 0.463125E+11 | 744.00 | 0.185807E+12 | 0.169977E+10 | 0.00 | 0.95 | 28-DEC-16:40 | 0.75 | 23-DEC-08:00 | 78130.00 | 28-DEC-17:00 | 76535.00 | 28-DEC-17:00 | 2519.61 | 29-DEC-17:10 | 24293.19 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.156248E+13 | 0.509585E+12 | 8760.00 | 0.147885E+13 | 0.836359E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.377004E+11 | 0.100216E+11 | 672.00 | 0.363412E+11 | 0.135921E+10 | 0.00 | 0.31 | 0.11 | 23183.23 | 21896.42 | 2413.76 | 6882.90 | 0.00 | ||||||
Maximum of Months | 0.216971E+12 | 0.768717E+11 | 744.00 | 0.200030E+12 | 0.169407E+11 | 0.00 | 1.00 | 0.76 | 83828.02 | 78376.67 | 8598.21 | 34102.27 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.234191E+10 | 0.649448E+09 | 667.49 | 0.221737E+10 | 0.124541E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2332.92 | 12-JAN-17:00 | 2196.92 | 12-JAN-17:00 | 254.55 | 17-JAN-15:40 | 696.46 | 12-JAN-16:40 | 0.00 |
February | 0.786922E+10 | 0.213113E+10 | 672.00 | 0.763304E+10 | 0.236189E+09 | 0.00 | 0.55 | 22-FEB-17:00 | 0.26 | 11-FEB-06:15 | 4340.53 | 22-FEB-17:00 | 4179.75 | 22-FEB-17:00 | 273.12 | 15-FEB-17:00 | 1446.08 | 22-FEB-15:00 | 0.00 |
March | 0.151508E+11 | 0.457942E+10 | 744.00 | 0.148028E+11 | 0.348080E+09 | 0.00 | 0.89 | 31-MAR-24:00 | 0.56 | 01-MAR-08:00 | 7476.36 | 31-MAR-24:00 | 7368.75 | 31-MAR-23:55 | 342.09 | 10-MAR-17:10 | 2677.95 | 28-MAR-16:00 | 0.00 |
April | 0.200388E+11 | 0.721164E+10 | 720.00 | 0.197134E+11 | 0.325407E+09 | 0.00 | 1.00 | 01-APR-15:20 | 0.33 | 30-APR-24:00 | 8302.65 | 16-APR-20:54 | 8029.45 | 16-APR-21:15 | 390.23 | 26-APR-08:00 | 3522.93 | 15-APR-15:00 | 0.00 |
May | 0.706091E+10 | 0.280414E+10 | 744.00 | 0.638726E+10 | 0.673642E+09 | 0.00 | 0.55 | 31-MAY-23:13 | 0.26 | 13-MAY-07:00 | 4464.51 | 31-MAY-23:03 | 3897.86 | 31-MAY-24:00 | 642.83 | 31-MAY-23:03 | 1650.91 | 28-MAY-16:31 | 0.00 |
June | 0.119815E+11 | 0.473933E+10 | 720.00 | 0.108883E+11 | 0.109323E+10 | 0.00 | 0.80 | 30-JUN-23:12 | 0.51 | 24-JUN-14:00 | 6396.70 | 30-JUN-23:03 | 5894.88 | 30-JUN-23:55 | 819.67 | 28-JUN-13:30 | 2586.13 | 11-JUN-16:11 | 0.00 |
July | 0.175802E+11 | 0.657982E+10 | 744.00 | 0.159563E+11 | 0.162390E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 19-JUL-03:00 | 8391.06 | 31-JUL-23:03 | 7618.92 | 31-JUL-23:53 | 850.46 | 18-JUL-08:20 | 3311.23 | 02-JUL-17:00 | 0.00 |
August | 0.220411E+11 | 0.787971E+10 | 744.00 | 0.203197E+11 | 0.172142E+10 | 0.00 | 1.00 | 01-AUG-08:30 | 0.34 | 31-AUG-23:13 | 8561.16 | 10-AUG-14:10 | 7808.14 | 20-AUG-16:45 | 871.25 | 21-AUG-14:00 | 3379.44 | 07-AUG-15:00 | 0.00 |
September | 0.699846E+10 | 0.241418E+10 | 720.00 | 0.572607E+10 | 0.127239E+10 | 0.00 | 0.55 | 30-SEP-23:05 | 0.26 | 09-SEP-17:12 | 4515.58 | 30-SEP-23:05 | 3877.94 | 30-SEP-23:57 | 732.49 | 12-SEP-16:00 | 1442.72 | 30-SEP-23:10 | 0.00 |
October | 0.109582E+11 | 0.354061E+10 | 744.00 | 0.103274E+11 | 0.630833E+09 | 0.00 | 0.65 | 31-OCT-23:20 | 0.40 | 28-OCT-07:00 | 5521.30 | 31-OCT-23:10 | 5290.76 | 31-OCT-24:00 | 502.87 | 06-OCT-09:40 | 2003.80 | 02-OCT-15:10 | 0.00 |
November | 0.139690E+11 | 0.394377E+10 | 720.00 | 0.136430E+11 | 0.326034E+09 | 0.00 | 0.79 | 08-NOV-16:20 | 0.50 | 26-NOV-07:40 | 6327.92 | 08-NOV-16:40 | 6074.11 | 08-NOV-16:30 | 285.89 | 08-NOV-20:00 | 2253.43 | 08-NOV-15:00 | 0.00 |
December | 0.175978E+11 | 0.442132E+10 | 744.00 | 0.174121E+11 | 0.185640E+09 | 0.00 | 0.93 | 28-DEC-16:30 | 0.62 | 31-DEC-08:00 | 7825.87 | 28-DEC-17:00 | 7658.84 | 28-DEC-17:00 | 258.56 | 29-DEC-17:10 | 2449.85 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.153588E+12 | 0.508945E+11 | 8683.49 | 0.145027E+12 | 0.856130E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.234191E+10 | 0.649448E+09 | 667.49 | 0.221737E+10 | 0.124541E+09 | 0.00 | 0.30 | 0.00 | 2332.92 | 2196.92 | 254.55 | 696.46 | 0.00 | ||||||
Maximum of Months | 0.220411E+11 | 0.787971E+10 | 744.00 | 0.203197E+11 | 0.172142E+10 | 0.00 | 1.00 | 0.73 | 8561.16 | 8029.45 | 871.25 | 3522.93 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.08 | 365.25 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.02 | 277.19 | 0.00 | 0.00 | 0.00 |
March | 130.25 | 0.00 | 130.25 | 198.18 | 157.54 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.98 | 49.37 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 477.76 | 7.41 | 0.00 | 0.00 | 0.00 |
June | 162.09 | 6.00 | 156.08 | 518.01 | 5.61 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.13 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.20 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.46 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 220.15 | 119.23 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.45 | 243.88 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.27 | 355.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.08 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.09 | 6.00 | 157.32 | 518.01 | 365.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.08 | 365.25 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.02 | 277.18 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.18 | 157.54 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.98 | 49.37 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 477.76 | 7.41 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 518.01 | 5.61 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.12 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.20 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.46 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 220.15 | 119.23 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.45 | 243.88 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.27 | 355.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.08 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 518.01 | 365.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.08 | 365.25 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.02 | 277.18 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.18 | 157.54 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.98 | 49.37 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 477.76 | 7.41 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 518.01 | 5.61 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.12 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.20 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.46 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 220.15 | 119.23 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.45 | 243.88 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.27 | 355.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.08 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 518.01 | 365.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 48.08 | 365.25 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 101.02 | 277.18 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.18 | 157.54 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 341.98 | 49.37 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 477.76 | 7.41 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 518.01 | 5.61 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 462.12 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 386.34 | 4.20 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 303.46 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 220.15 | 119.23 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 117.45 | 243.88 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 53.27 | 355.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 269.80 | 133.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 48.08 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 518.01 | 365.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.14 | 0.00 | 91.14 | 48.08 | 365.23 | 0.00 | 0.00 | 0.00 |
February | 108.08 | 0.00 | 108.08 | 101.01 | 277.17 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 198.17 | 157.53 | 0.00 | 0.00 | 0.00 |
April | 141.32 | 0.48 | 140.84 | 341.97 | 49.37 | 0.00 | 0.00 | 0.00 |
May | 156.57 | 4.39 | 152.18 | 477.74 | 7.41 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.07 | 517.99 | 5.61 | 0.00 | 0.00 | 0.00 |
July | 159.84 | 2.53 | 157.31 | 462.10 | 1.15 | 0.00 | 0.00 | 0.00 |
August | 146.74 | 0.46 | 146.28 | 386.32 | 4.20 | 0.00 | 0.00 | 0.00 |
September | 130.75 | 0.01 | 130.74 | 303.44 | 20.11 | 0.00 | 0.00 | 0.00 |
October | 113.27 | 0.00 | 113.27 | 220.14 | 119.22 | 0.00 | 0.00 | 0.00 |
November | 95.94 | 0.00 | 95.94 | 117.45 | 243.87 | 0.00 | 0.00 | 0.00 |
December | 88.91 | 0.00 | 88.91 | 53.26 | 355.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.17 | 1.16 | 126.01 | 269.79 | 133.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.91 | 0.00 | 88.91 | 48.08 | 1.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.31 | 517.99 | 365.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 218.83 | 366.76 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 341.36 | 281.03 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 524.93 | 160.75 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 782.46 | 49.36 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.86 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 805.40 | 5.28 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 666.59 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 565.58 | 2.46 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 521.47 | 19.85 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 502.96 | 124.91 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.80 | 247.71 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.69 | 355.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 534.42 | 134.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 218.83 | 0.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 887.86 | 366.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 218.83 | 366.76 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 341.36 | 281.03 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 524.93 | 160.75 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 782.46 | 49.36 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.86 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 805.40 | 5.28 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 666.59 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 565.58 | 2.46 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 521.47 | 19.85 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 502.96 | 124.91 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.80 | 247.71 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.69 | 355.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 534.42 | 134.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 218.83 | 0.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 887.86 | 366.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.95 | 87.08 | 129.87 | 218.83 | 366.75 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.81 | 154.75 | 341.35 | 281.03 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.71 | 188.81 | 524.92 | 160.75 | 0.00 | 0.00 | 0.00 |
April | 382.53 | 178.36 | 204.18 | 782.44 | 49.36 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 887.84 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 306.43 | 101.67 | 204.76 | 805.38 | 5.28 | 0.00 | 0.00 | 0.00 |
July | 257.55 | 54.39 | 203.16 | 666.58 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 232.06 | 40.38 | 191.68 | 565.57 | 2.46 | 0.00 | 0.00 | 0.00 |
September | 247.93 | 69.14 | 178.79 | 521.46 | 19.85 | 0.00 | 0.00 | 0.00 |
October | 271.21 | 109.55 | 161.66 | 502.95 | 124.91 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 356.79 | 247.71 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 230.69 | 355.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.78 | 174.34 | 534.41 | 134.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.38 | 126.60 | 218.83 | 0.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.53 | 178.36 | 209.59 | 887.84 | 366.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 568.23 | 333.16 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 588.76 | 268.11 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.38 | 161.86 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 549.65 | 54.02 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.32 | 7.52 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.70 | 5.60 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 468.97 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 438.87 | 4.42 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.93 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 736.57 | 127.15 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.66 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 629.55 | 331.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.76 | 129.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.87 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.66 | 333.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 568.22 | 333.16 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 588.76 | 268.11 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.38 | 161.86 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.65 | 54.02 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.31 | 7.52 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.70 | 5.60 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 468.97 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 438.87 | 4.42 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.93 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 736.57 | 127.15 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.65 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 629.55 | 331.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.76 | 129.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.87 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.65 | 333.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 568.23 | 333.16 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 588.76 | 268.11 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.38 | 161.86 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 549.65 | 54.02 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.32 | 7.52 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.70 | 5.60 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 468.97 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 438.87 | 4.42 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.93 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 736.57 | 127.15 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.66 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 629.55 | 331.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.76 | 129.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.87 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.66 | 333.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 568.22 | 333.16 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 588.76 | 268.11 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 589.38 | 161.86 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.65 | 54.02 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 511.31 | 7.52 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 505.70 | 5.60 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 468.97 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 438.87 | 4.42 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 496.93 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 736.57 | 127.15 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 804.65 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 629.55 | 331.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 573.76 | 129.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 438.87 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 804.65 | 333.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.52 | 251.87 | 162.65 | 568.20 | 333.15 | 0.00 | 0.00 | 0.00 |
February | 394.15 | 218.92 | 175.23 | 588.74 | 268.10 | 0.00 | 0.00 | 0.00 |
March | 337.01 | 148.85 | 188.15 | 589.36 | 161.85 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 549.62 | 54.01 | 0.00 | 0.00 | 0.00 |
May | 170.23 | 12.60 | 157.63 | 511.29 | 7.52 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.06 | 505.68 | 5.60 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.19 | 468.95 | 1.07 | 0.00 | 0.00 | 0.00 |
August | 172.30 | 9.20 | 163.10 | 438.85 | 4.42 | 0.00 | 0.00 | 0.00 |
September | 230.98 | 59.95 | 171.03 | 496.91 | 22.60 | 0.00 | 0.00 | 0.00 |
October | 397.38 | 221.89 | 175.49 | 736.54 | 127.14 | 0.00 | 0.00 | 0.00 |
November | 496.35 | 328.07 | 168.27 | 804.62 | 244.27 | 0.00 | 0.00 | 0.00 |
December | 442.98 | 277.58 | 165.40 | 629.53 | 331.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.36 | 132.89 | 167.47 | 573.74 | 129.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.06 | 438.85 | 1.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.35 | 328.07 | 188.15 | 804.62 | 333.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 235.06 | 422.59 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.81 | 339.96 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 507.36 | 208.98 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 754.21 | 85.00 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 847.77 | 13.42 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 835.61 | 10.81 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 614.24 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.41 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 521.34 | 33.43 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 487.66 | 157.14 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 361.05 | 309.05 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 225.60 | 441.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.91 | 169.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 225.60 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 847.77 | 441.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 235.06 | 422.59 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.81 | 339.96 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 507.36 | 208.98 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 754.21 | 85.00 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 847.77 | 13.42 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 835.61 | 10.81 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 614.24 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.41 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 521.34 | 33.43 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 487.66 | 157.14 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 361.05 | 309.05 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 225.60 | 441.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.91 | 169.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 225.60 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 847.77 | 441.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.25 | 82.60 | 129.65 | 235.05 | 422.58 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 316.81 | 339.96 | 0.00 | 0.00 | 0.00 |
March | 314.74 | 125.81 | 188.93 | 507.35 | 208.98 | 0.00 | 0.00 | 0.00 |
April | 382.56 | 179.41 | 203.16 | 754.19 | 85.00 | 0.00 | 0.00 | 0.00 |
May | 362.25 | 153.66 | 208.59 | 847.75 | 13.42 | 0.00 | 0.00 | 0.00 |
June | 340.25 | 132.16 | 208.09 | 835.60 | 10.81 | 0.00 | 0.00 | 0.00 |
July | 252.48 | 49.11 | 203.38 | 614.23 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 513.40 | 17.02 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 521.33 | 33.43 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.66 | 487.65 | 157.14 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 361.04 | 309.05 | 0.00 | 0.00 | 0.00 |
December | 205.38 | 78.32 | 127.07 | 225.60 | 441.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 518.90 | 169.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.38 | 41.21 | 127.07 | 225.60 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.56 | 179.41 | 208.59 | 847.75 | 441.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 287.83 | 1647.12 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 548.44 | 1261.98 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1016.74 | 747.83 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1745.04 | 252.61 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2409.35 | 38.88 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2610.59 | 31.67 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2324.45 | 8.75 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1962.49 | 27.99 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1527.87 | 106.94 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1124.73 | 578.88 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 628.34 | 1124.50 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 327.44 | 1578.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1380.15 | 614.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 287.83 | 8.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2610.59 | 1647.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 685.97 | 1019.37 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1036.02 | 799.47 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1568.83 | 487.80 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2330.67 | 175.99 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2653.21 | 26.19 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2402.67 | 20.90 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1975.65 | 4.99 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1671.78 | 18.55 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1555.54 | 72.61 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1504.87 | 385.63 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1078.81 | 721.22 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 721.30 | 997.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1600.74 | 392.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 685.97 | 4.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2653.21 | 1019.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2824.61 | 1639.41 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2928.70 | 1311.12 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2937.50 | 806.86 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2758.39 | 284.66 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2576.44 | 38.95 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2550.87 | 31.18 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2361.11 | 7.72 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2217.28 | 29.27 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2479.32 | 124.67 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3669.43 | 649.97 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4007.67 | 1212.53 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3144.76 | 1611.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2870.02 | 642.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2217.28 | 7.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4007.67 | 1639.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 743.57 | 1125.54 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 993.47 | 882.79 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1558.41 | 546.79 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2323.47 | 206.07 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2570.48 | 35.37 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2558.01 | 26.99 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1915.03 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1647.11 | 24.19 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1584.74 | 87.34 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1490.88 | 424.34 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1130.43 | 798.13 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 748.38 | 1086.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1607.14 | 435.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 743.57 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2570.48 | 1125.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 346.16 | 1439.67 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 587.92 | 1150.52 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1021.93 | 714.70 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1721.74 | 249.46 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2367.69 | 41.73 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2567.05 | 34.17 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2279.74 | 8.88 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1926.85 | 30.52 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1510.61 | 107.39 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1121.26 | 559.25 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 657.33 | 1043.82 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 382.47 | 1408.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1378.06 | 563.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 346.16 | 8.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2567.05 | 1439.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 739.33 | 905.08 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1061.43 | 745.74 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1566.03 | 477.31 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2309.75 | 178.20 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2618.96 | 29.14 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2368.33 | 23.12 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1941.00 | 5.09 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1644.59 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1540.53 | 74.90 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1498.03 | 380.71 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1093.91 | 686.00 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 765.84 | 908.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1597.49 | 367.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 739.33 | 5.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2618.96 | 908.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2886.71 | 1471.32 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2954.81 | 1225.92 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2930.75 | 786.33 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2730.91 | 285.20 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2533.67 | 41.86 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2506.84 | 33.81 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2315.90 | 7.78 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2181.03 | 31.99 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2458.23 | 127.48 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3656.52 | 642.83 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4016.24 | 1162.72 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3195.68 | 1484.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2862.49 | 605.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2181.03 | 7.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4016.24 | 1484.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 773.75 | 1014.44 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 1010.51 | 823.97 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1556.66 | 530.85 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2306.27 | 205.41 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2544.04 | 37.09 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2530.32 | 28.21 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1889.16 | 7.85 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1626.96 | 25.50 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1573.56 | 87.35 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1486.32 | 414.77 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1141.78 | 757.06 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 776.28 | 996.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1603.02 | 408.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 773.75 | 7.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2544.04 | 1014.44 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244134E+09 | 0.00 | 0.244134E+09 | 0.128785E+09 | 0.978282E+09 |
February | 0.261485E+09 | 0.00 | 0.261485E+09 | 0.244387E+09 | 0.670567E+09 |
March | 0.348851E+09 | 0.00 | 0.348851E+09 | 0.530806E+09 | 0.421945E+09 |
April | 0.366321E+09 | 1242306.39 | 0.365078E+09 | 0.886420E+09 | 0.127976E+09 |
May | 0.419386E+09 | 11768647.88 | 0.407617E+09 | 0.127963E+10 | 19850452.45 |
June | 0.420126E+09 | 15561451.75 | 0.404565E+09 | 0.134268E+10 | 14538337.87 |
July | 0.428151E+09 | 6779998.49 | 0.421371E+09 | 0.123776E+10 | 3085361.92 |
August | 0.393055E+09 | 1224970.50 | 0.391830E+09 | 0.103477E+10 | 11238130.49 |
September | 0.338926E+09 | 23798.53 | 0.338902E+09 | 0.786564E+09 | 52120665.30 |
October | 0.303407E+09 | 0.00 | 0.303407E+09 | 0.589642E+09 | 0.319346E+09 |
November | 0.248699E+09 | 0.00 | 0.248699E+09 | 0.304442E+09 | 0.632140E+09 |
December | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.142670E+09 | 0.953170E+09 |
Annual Sum or Average | 0.401070E+10 | 36601173.55 | 0.397410E+10 | 0.850856E+10 | 0.420426E+10 |
Minimum of Months | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.128785E+09 | 3085361.92 |
Maximum of Months | 0.428151E+09 | 15561451.75 | 0.421371E+09 | 0.134268E+10 | 0.978282E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.128782E+09 | 0.978280E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.244383E+09 | 0.670565E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.530800E+09 | 0.421942E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.886416E+09 | 0.127974E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127962E+10 | 19849757.23 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.134268E+10 | 14538087.13 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.123775E+10 | 3085235.77 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.103476E+10 | 11237777.66 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.786557E+09 | 52119307.94 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.589638E+09 | 0.319343E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.304440E+09 | 0.632137E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.142667E+09 | 0.953167E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.850849E+10 | 0.420424E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.128782E+09 | 3085235.77 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.134268E+10 | 0.978280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244132E+09 | 0.00 | 0.244132E+09 | 0.128783E+09 | 0.978280E+09 |
February | 0.261483E+09 | 0.00 | 0.261483E+09 | 0.244385E+09 | 0.670566E+09 |
March | 0.348848E+09 | 0.00 | 0.348848E+09 | 0.530802E+09 | 0.421943E+09 |
April | 0.366318E+09 | 1242288.19 | 0.365075E+09 | 0.886418E+09 | 0.127974E+09 |
May | 0.419382E+09 | 11768475.40 | 0.407614E+09 | 0.127962E+10 | 19849988.97 |
June | 0.420122E+09 | 15561223.69 | 0.404561E+09 | 0.134268E+10 | 14538170.71 |
July | 0.428147E+09 | 6779899.12 | 0.421367E+09 | 0.123775E+10 | 3085277.81 |
August | 0.393051E+09 | 1224952.55 | 0.391826E+09 | 0.103477E+10 | 11237895.27 |
September | 0.338923E+09 | 23798.18 | 0.338899E+09 | 0.786560E+09 | 52119760.39 |
October | 0.303405E+09 | 0.00 | 0.303405E+09 | 0.589639E+09 | 0.319344E+09 |
November | 0.248697E+09 | 0.00 | 0.248697E+09 | 0.304441E+09 | 0.632138E+09 |
December | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.142668E+09 | 0.953168E+09 |
Annual Sum or Average | 0.401066E+10 | 36600637.13 | 0.397406E+10 | 0.850852E+10 | 0.420424E+10 |
Minimum of Months | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.128783E+09 | 3085277.81 |
Maximum of Months | 0.428147E+09 | 15561223.69 | 0.421367E+09 | 0.134268E+10 | 0.978280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.128782E+09 | 0.978280E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.244383E+09 | 0.670565E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.530800E+09 | 0.421942E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.886416E+09 | 0.127974E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127962E+10 | 19849757.23 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.134268E+10 | 14538087.13 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.123775E+10 | 3085235.77 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.103476E+10 | 11237777.66 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.786557E+09 | 52119307.94 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.589638E+09 | 0.319343E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.304440E+09 | 0.632137E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.142667E+09 | 0.953167E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.850849E+10 | 0.420424E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.128782E+09 | 3085235.77 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.134268E+10 | 0.978280E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244121E+09 | 0.00 | 0.244121E+09 | 0.128777E+09 | 0.978241E+09 |
February | 0.261472E+09 | 0.00 | 0.261472E+09 | 0.244374E+09 | 0.670538E+09 |
March | 0.348833E+09 | 0.00 | 0.348833E+09 | 0.530780E+09 | 0.421926E+09 |
April | 0.366302E+09 | 1242233.56 | 0.365060E+09 | 0.886381E+09 | 0.127969E+09 |
May | 0.419364E+09 | 11767957.96 | 0.407596E+09 | 0.127957E+10 | 19849073.06 |
June | 0.420105E+09 | 15560539.49 | 0.404544E+09 | 0.134262E+10 | 14537542.97 |
July | 0.428128E+09 | 6779601.02 | 0.421349E+09 | 0.123770E+10 | 3085132.44 |
August | 0.393034E+09 | 1224898.69 | 0.391809E+09 | 0.103472E+10 | 11237383.53 |
September | 0.338908E+09 | 23797.13 | 0.338884E+09 | 0.786527E+09 | 52117433.52 |
October | 0.303392E+09 | 0.00 | 0.303392E+09 | 0.589615E+09 | 0.319330E+09 |
November | 0.248686E+09 | 0.00 | 0.248686E+09 | 0.304428E+09 | 0.632112E+09 |
December | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.142662E+09 | 0.953129E+09 |
Annual Sum or Average | 0.401049E+10 | 36599027.86 | 0.397389E+10 | 0.850816E+10 | 0.420407E+10 |
Minimum of Months | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.128777E+09 | 3085132.44 |
Maximum of Months | 0.428128E+09 | 15560539.49 | 0.421349E+09 | 0.134262E+10 | 0.978241E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.586119E+09 | 0.982332E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.825814E+09 | 0.679876E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140596E+10 | 0.430551E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.202813E+10 | 0.127931E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.237804E+10 | 20019067.74 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.208759E+10 | 13674514.61 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.178540E+10 | 2051042.10 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.151484E+10 | 6593387.85 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.135165E+10 | 51446132.96 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134712E+10 | 0.334566E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.924825E+09 | 0.642065E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.617885E+09 | 0.951091E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.168534E+11 | 0.424220E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.586119E+09 | 2051042.10 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.237804E+10 | 0.982332E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.586119E+09 | 0.982332E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.825814E+09 | 0.679876E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140596E+10 | 0.430551E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.202813E+10 | 0.127931E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.237804E+10 | 20019067.74 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.208759E+10 | 13674514.61 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.178540E+10 | 2051042.10 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.151484E+10 | 6593387.85 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.135165E+10 | 51446132.96 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134712E+10 | 0.334566E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.924825E+09 | 0.642065E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.617885E+09 | 0.951091E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.168534E+11 | 0.424220E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.586119E+09 | 2051042.10 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.237804E+10 | 0.982332E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581082E+09 | 0.233238E+09 | 0.347844E+09 | 0.586109E+09 | 0.982314E+09 |
February | 0.637624E+09 | 0.263241E+09 | 0.374383E+09 | 0.825799E+09 | 0.679864E+09 |
March | 0.861174E+09 | 0.355463E+09 | 0.505711E+09 | 0.140593E+10 | 0.430543E+09 |
April | 0.991523E+09 | 0.462299E+09 | 0.529224E+09 | 0.202809E+10 | 0.127929E+09 |
May | 0.100846E+10 | 0.447097E+09 | 0.561365E+09 | 0.237799E+10 | 20018701.95 |
June | 0.794279E+09 | 0.263541E+09 | 0.530738E+09 | 0.208755E+10 | 13674264.75 |
July | 0.689824E+09 | 0.145672E+09 | 0.544151E+09 | 0.178537E+10 | 2051004.63 |
August | 0.621560E+09 | 0.108166E+09 | 0.513394E+09 | 0.151482E+10 | 6593267.38 |
September | 0.642644E+09 | 0.179218E+09 | 0.463427E+09 | 0.135163E+10 | 51445192.93 |
October | 0.726410E+09 | 0.293422E+09 | 0.432988E+09 | 0.134710E+10 | 0.334560E+09 |
November | 0.623291E+09 | 0.267545E+09 | 0.355746E+09 | 0.924808E+09 | 0.642053E+09 |
December | 0.561600E+09 | 0.222509E+09 | 0.339091E+09 | 0.617874E+09 | 0.951074E+09 |
Annual Sum or Average | 0.873947E+10 | 0.324141E+10 | 0.549806E+10 | 0.168531E+11 | 0.424212E+10 |
Minimum of Months | 0.561600E+09 | 0.108166E+09 | 0.339091E+09 | 0.586109E+09 | 2051004.63 |
Maximum of Months | 0.100846E+10 | 0.462299E+09 | 0.561365E+09 | 0.237799E+10 | 0.982314E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152194E+10 | 0.892348E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142434E+10 | 0.648604E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157861E+10 | 0.433517E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.142469E+10 | 0.140010E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136951E+10 | 20152994.35 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.131077E+10 | 14525568.86 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.125610E+10 | 2865357.97 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.117547E+10 | 11839123.80 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128805E+10 | 58575979.37 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197284E+10 | 0.340559E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208568E+10 | 0.633178E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168619E+10 | 0.888360E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180942E+11 | 0.408453E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.117547E+10 | 2865357.97 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208568E+10 | 0.892348E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152192E+10 | 0.892347E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142433E+10 | 0.648604E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157860E+10 | 0.433517E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.142468E+10 | 0.140009E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136951E+10 | 20152762.15 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.131077E+10 | 14525492.11 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.125609E+10 | 2865322.38 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.117546E+10 | 11839002.21 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128804E+10 | 58575501.39 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197282E+10 | 0.340557E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208566E+10 | 0.633177E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168618E+10 | 0.888359E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180941E+11 | 0.408453E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.117546E+10 | 2865322.38 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208566E+10 | 0.892347E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152194E+10 | 0.892348E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142434E+10 | 0.648604E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157861E+10 | 0.433517E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.142469E+10 | 0.140010E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136951E+10 | 20152994.35 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.131077E+10 | 14525568.86 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.125610E+10 | 2865357.97 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.117547E+10 | 11839123.80 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128805E+10 | 58575979.37 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197284E+10 | 0.340559E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208568E+10 | 0.633178E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168619E+10 | 0.888360E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180942E+11 | 0.408453E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.117547E+10 | 2865357.97 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208568E+10 | 0.892348E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152192E+10 | 0.892347E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142433E+10 | 0.648604E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157860E+10 | 0.433517E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.142468E+10 | 0.140009E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136951E+10 | 20152762.15 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.131077E+10 | 14525492.11 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.125609E+10 | 2865322.38 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.117546E+10 | 11839002.21 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128804E+10 | 58575501.39 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197282E+10 | 0.340557E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208566E+10 | 0.633177E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168618E+10 | 0.888359E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180941E+11 | 0.408453E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.117546E+10 | 2865322.38 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208566E+10 | 0.892347E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111025E+10 | 0.674614E+09 | 0.435635E+09 | 0.152187E+10 | 0.892311E+09 |
February | 0.953523E+09 | 0.529612E+09 | 0.423911E+09 | 0.142428E+10 | 0.648578E+09 |
March | 0.902639E+09 | 0.398686E+09 | 0.503953E+09 | 0.157854E+10 | 0.433500E+09 |
April | 0.613567E+09 | 0.173166E+09 | 0.440401E+09 | 0.142463E+10 | 0.140004E+09 |
May | 0.455946E+09 | 33751886.52 | 0.422194E+09 | 0.136945E+10 | 20152066.00 |
June | 0.403619E+09 | 6887546.88 | 0.396732E+09 | 0.131071E+10 | 14524945.04 |
July | 0.435045E+09 | 5983626.10 | 0.429061E+09 | 0.125604E+10 | 2865224.69 |
August | 0.461490E+09 | 24646825.33 | 0.436843E+09 | 0.117542E+10 | 11838585.84 |
September | 0.598706E+09 | 0.155394E+09 | 0.443312E+09 | 0.128799E+10 | 58573379.52 |
October | 0.106434E+10 | 0.594322E+09 | 0.470021E+09 | 0.197275E+10 | 0.340544E+09 |
November | 0.128653E+10 | 0.850370E+09 | 0.436165E+09 | 0.208559E+10 | 0.633152E+09 |
December | 0.118647E+10 | 0.743475E+09 | 0.442998E+09 | 0.168612E+10 | 0.888323E+09 |
Annual Sum or Average | 0.947214E+10 | 0.419091E+10 | 0.528123E+10 | 0.180934E+11 | 0.408437E+10 |
Minimum of Months | 0.403619E+09 | 5983626.10 | 0.396732E+09 | 0.117542E+10 | 2865224.69 |
Maximum of Months | 0.128653E+10 | 0.850370E+09 | 0.503953E+09 | 0.208559E+10 | 0.892311E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.629574E+09 | 0.113186E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.766434E+09 | 0.822436E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135892E+10 | 0.559735E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.195491E+10 | 0.220323E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.227065E+10 | 35933042.07 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.216590E+10 | 28024670.93 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.164517E+10 | 11446293.33 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.137513E+10 | 45575800.47 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.135132E+10 | 86662298.51 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130616E+10 | 0.420892E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.935834E+09 | 0.801065E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.604260E+09 | 0.118135E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.163643E+11 | 0.534530E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.604260E+09 | 11446293.33 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.227065E+10 | 0.118135E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.629574E+09 | 0.113186E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.766434E+09 | 0.822436E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135892E+10 | 0.559735E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.195491E+10 | 0.220323E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.227065E+10 | 35933042.07 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.216590E+10 | 28024670.93 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.164517E+10 | 11446293.33 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.137513E+10 | 45575800.47 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.135132E+10 | 86662298.51 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130616E+10 | 0.420892E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.935834E+09 | 0.801065E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.604260E+09 | 0.118135E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.163643E+11 | 0.534530E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.604260E+09 | 11446293.33 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.227065E+10 | 0.118135E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568496E+09 | 0.221237E+09 | 0.347259E+09 | 0.629562E+09 | 0.113184E+10 |
February | 0.587178E+09 | 0.216391E+09 | 0.370787E+09 | 0.766420E+09 | 0.822421E+09 |
March | 0.843001E+09 | 0.336977E+09 | 0.506024E+09 | 0.135890E+10 | 0.559725E+09 |
April | 0.991605E+09 | 0.465025E+09 | 0.526580E+09 | 0.195487E+10 | 0.220319E+09 |
May | 0.970256E+09 | 0.411563E+09 | 0.558693E+09 | 0.227061E+10 | 35932385.50 |
June | 0.881932E+09 | 0.342566E+09 | 0.539366E+09 | 0.216586E+10 | 28024158.85 |
July | 0.676253E+09 | 0.131532E+09 | 0.544722E+09 | 0.164514E+10 | 11446084.18 |
August | 0.621068E+09 | 0.110383E+09 | 0.510685E+09 | 0.137510E+10 | 45574967.70 |
September | 0.660693E+09 | 0.193961E+09 | 0.466732E+09 | 0.135129E+10 | 86660715.00 |
October | 0.710603E+09 | 0.282961E+09 | 0.427642E+09 | 0.130613E+10 | 0.420885E+09 |
November | 0.622120E+09 | 0.265144E+09 | 0.356976E+09 | 0.935817E+09 | 0.801050E+09 |
December | 0.550097E+09 | 0.209764E+09 | 0.340333E+09 | 0.604249E+09 | 0.118133E+10 |
Annual Sum or Average | 0.868330E+10 | 0.318750E+10 | 0.549580E+10 | 0.163640E+11 | 0.534520E+10 |
Minimum of Months | 0.550097E+09 | 0.110383E+09 | 0.340333E+09 | 0.604249E+09 | 11446084.18 |
Maximum of Months | 0.991605E+09 | 0.465025E+09 | 0.558693E+09 | 0.227061E+10 | 0.118133E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.770926E+09 | 0.441163E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.132678E+10 | 0.305299E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.272324E+10 | 0.200298E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.452316E+10 | 0.654753E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.645319E+10 | 0.104133E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.676664E+10 | 82101368.19 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.622582E+10 | 23443576.69 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.525633E+10 | 74959161.40 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.396025E+10 | 0.277196E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.301247E+10 | 0.155047E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.162866E+10 | 0.291470E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.877003E+09 | 0.422915E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.435245E+11 | 0.193785E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.770926E+09 | 23443576.69 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.676664E+10 | 0.441163E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.183731E+10 | 0.273029E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.250633E+10 | 0.193407E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.420195E+10 | 0.130653E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.604110E+10 | 0.456161E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.710637E+10 | 70134612.65 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.622772E+10 | 54163211.38 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.529157E+10 | 13367478.11 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.447769E+10 | 49688439.34 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.403196E+10 | 0.188216E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.403066E+10 | 0.103288E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.279627E+10 | 0.186940E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.193193E+10 | 0.267161E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.504809E+11 | 0.123765E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.183731E+10 | 13367478.11 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.710637E+10 | 0.273029E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.756544E+10 | 0.439099E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.708511E+10 | 0.317187E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.786779E+10 | 0.216110E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.714975E+10 | 0.737837E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.690073E+10 | 0.104332E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.661186E+10 | 80829854.03 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.632400E+10 | 20687873.06 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.593875E+10 | 78391884.38 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.642640E+10 | 0.323154E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.982821E+10 | 0.174089E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.103879E+11 | 0.314289E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.842293E+10 | 0.431606E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.905088E+11 | 0.202690E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.593875E+10 | 20687873.06 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.103879E+11 | 0.439099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.199157E+10 | 0.301464E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.240341E+10 | 0.213564E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.417406E+10 | 0.146452E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.602243E+10 | 0.534122E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.688478E+10 | 94745930.21 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.663035E+10 | 69969362.54 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.512922E+10 | 21495870.76 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.441161E+10 | 64786845.55 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.410764E+10 | 0.226390E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.399318E+10 | 0.113654E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.293008E+10 | 0.206875E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.200447E+10 | 0.291044E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.506828E+11 | 0.137420E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.199157E+10 | 21495870.76 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.688478E+10 | 0.301464E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.927162E+09 | 0.385600E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.142229E+10 | 0.278333E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.273713E+10 | 0.191425E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.446274E+10 | 0.646600E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.634162E+10 | 0.111777E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.665380E+10 | 88557232.72 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.610606E+10 | 23777652.66 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.516088E+10 | 81754208.37 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.391549E+10 | 0.278363E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.300318E+10 | 0.149790E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.170381E+10 | 0.270558E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.102440E+10 | 0.377320E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.434586E+11 | 0.177611E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.927162E+09 | 23777652.66 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.665380E+10 | 0.385600E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.198023E+10 | 0.242417E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.256781E+10 | 0.180408E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.419447E+10 | 0.127843E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.598687E+10 | 0.461895E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.701462E+10 | 78056346.88 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.613870E+10 | 59920710.63 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.519876E+10 | 13630153.48 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.440486E+10 | 55100088.80 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.399305E+10 | 0.194128E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.401232E+10 | 0.101968E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.283541E+10 | 0.177812E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.205122E+10 | 0.243302E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.503783E+11 | 0.116002E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.198023E+10 | 13630153.48 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.701462E+10 | 0.243302E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.773177E+10 | 0.394079E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.714827E+10 | 0.296574E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.784973E+10 | 0.210611E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.707851E+10 | 0.739235E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.678618E+10 | 0.112125E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.649772E+10 | 87646053.78 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.620291E+10 | 20825881.41 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.584166E+10 | 85689032.40 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.637173E+10 | 0.330434E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.979362E+10 | 0.172176E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.104101E+11 | 0.301377E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.855930E+10 | 0.397618E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.902715E+11 | 0.191003E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.584166E+10 | 20825881.41 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.104101E+11 | 0.397618E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.207241E+10 | 0.271707E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.244462E+10 | 0.199335E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.416937E+10 | 0.142182E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.597785E+10 | 0.532421E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.681396E+10 | 99333638.78 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.655858E+10 | 73112733.06 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.505993E+10 | 21025773.69 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.435766E+10 | 68303362.12 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.407866E+10 | 0.226418E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.398096E+10 | 0.111091E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.295949E+10 | 0.196229E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.207920E+10 | 0.266898E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.505527E+11 | 0.128951E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.207241E+10 | 21025773.69 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.681396E+10 | 0.271707E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 240.41 | 1826.23 | 455.74 | 0.00 | 455.74 | 0.00 | 0.00 |
February | 505.09 | 1385.91 | 540.43 | 0.00 | 540.43 | 0.00 | 0.00 |
March | 990.89 | 787.67 | 651.22 | 0.00 | 651.22 | 0.00 | 0.00 |
April | 1709.90 | 246.86 | 706.63 | 2.40 | 704.23 | 0.00 | 0.00 |
May | 2388.76 | 37.06 | 782.89 | 21.97 | 760.92 | 0.00 | 0.00 |
June | 2590.02 | 28.04 | 810.41 | 30.02 | 780.40 | 0.00 | 0.00 |
July | 2310.60 | 5.76 | 799.25 | 12.66 | 786.60 | 0.00 | 0.00 |
August | 1931.67 | 20.98 | 733.74 | 2.29 | 731.45 | 0.00 | 0.00 |
September | 1517.27 | 100.54 | 653.78 | 0.05 | 653.73 | 0.00 | 0.00 |
October | 1100.72 | 596.14 | 566.39 | 0.00 | 566.39 | 0.00 | 0.00 |
November | 587.26 | 1219.39 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 266.33 | 1779.35 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Annual Sum or Average | 1349.01 | 666.57 | 635.88 | 5.80 | 630.08 | 0.00 | 0.00 |
Minimum of Months | 240.41 | 5.76 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Maximum of Months | 2590.02 | 1826.23 | 810.41 | 30.02 | 786.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 656.49 | 1100.28 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1024.07 | 843.10 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1574.77 | 482.25 | 964.59 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2347.36 | 148.07 | 1147.61 | 535.07 | 612.54 | 0.00 | 0.00 |
May | 2663.56 | 22.42 | 1129.56 | 500.79 | 628.78 | 0.00 | 0.00 |
June | 2416.18 | 15.83 | 919.32 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1999.76 | 2.30 | 772.66 | 163.17 | 609.50 | 0.00 | 0.00 |
August | 1696.72 | 7.39 | 696.20 | 121.16 | 575.04 | 0.00 | 0.00 |
September | 1564.41 | 59.54 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1508.87 | 374.74 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1070.39 | 743.13 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 692.07 | 1065.28 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1603.24 | 403.56 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 656.49 | 2.30 | 629.04 | 121.16 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2663.56 | 1100.28 | 1147.61 | 535.07 | 628.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2841.10 | 1665.81 | 2072.66 | 1259.40 | 813.26 | 0.00 | 0.00 |
February | 2943.79 | 1340.52 | 1970.80 | 1094.64 | 876.17 | 0.00 | 0.00 |
March | 2946.89 | 809.28 | 1685.09 | 744.29 | 940.80 | 0.00 | 0.00 |
April | 2748.21 | 270.08 | 1183.62 | 334.05 | 849.57 | 0.00 | 0.00 |
May | 2556.56 | 37.62 | 851.18 | 63.01 | 788.17 | 0.00 | 0.00 |
June | 2528.46 | 28.02 | 778.61 | 13.29 | 765.32 | 0.00 | 0.00 |
July | 2344.84 | 5.35 | 812.16 | 11.17 | 800.99 | 0.00 | 0.00 |
August | 2194.33 | 22.10 | 861.53 | 46.01 | 815.52 | 0.00 | 0.00 |
September | 2484.64 | 112.99 | 1154.95 | 299.77 | 855.18 | 0.00 | 0.00 |
October | 3682.82 | 635.74 | 1986.97 | 1109.51 | 877.46 | 0.00 | 0.00 |
November | 4023.25 | 1221.40 | 2481.82 | 1640.43 | 841.39 | 0.00 | 0.00 |
December | 3147.73 | 1658.36 | 2214.96 | 1387.95 | 827.01 | 0.00 | 0.00 |
Annual Sum or Average | 2868.78 | 647.59 | 1501.85 | 664.49 | 837.36 | 0.00 | 0.00 |
Minimum of Months | 2194.33 | 5.35 | 778.61 | 11.17 | 765.32 | 0.00 | 0.00 |
Maximum of Months | 4023.25 | 1665.81 | 2481.82 | 1640.43 | 940.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 705.16 | 1267.75 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 950.43 | 1019.88 | 728.16 | 268.35 | 459.81 | 0.00 | 0.00 |
March | 1522.08 | 626.94 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2262.61 | 255.00 | 1147.71 | 538.23 | 609.48 | 0.00 | 0.00 |
May | 2543.28 | 40.25 | 1086.77 | 460.99 | 625.78 | 0.00 | 0.00 |
June | 2506.82 | 32.44 | 1020.77 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1842.70 | 12.82 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1540.23 | 51.05 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1564.02 | 100.30 | 764.70 | 224.49 | 540.21 | 0.00 | 0.00 |
October | 1462.98 | 471.43 | 795.94 | 316.94 | 479.00 | 0.00 | 0.00 |
November | 1083.13 | 927.15 | 720.06 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 676.81 | 1323.19 | 616.16 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1556.71 | 508.49 | 826.05 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 676.81 | 12.82 | 616.16 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2543.28 | 1323.19 | 1147.71 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.83 | 1647.12 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 548.44 | 1261.98 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1016.74 | 747.83 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1745.04 | 252.61 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2409.35 | 38.88 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2610.59 | 31.67 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2324.45 | 8.75 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1962.49 | 27.99 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1527.87 | 106.94 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1124.73 | 578.88 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 628.34 | 1124.50 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 327.44 | 1578.98 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1380.15 | 614.49 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 287.83 | 8.75 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2610.59 | 1647.12 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 685.97 | 1019.37 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1036.02 | 799.47 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1568.83 | 487.80 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2330.67 | 175.99 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2653.21 | 26.19 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2402.67 | 20.90 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1975.65 | 4.99 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1671.78 | 18.55 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1555.54 | 72.61 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1504.87 | 385.63 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1078.81 | 721.22 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 721.30 | 997.47 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1600.74 | 392.46 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 685.97 | 4.99 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2653.21 | 1019.37 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2824.61 | 1639.41 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2928.70 | 1311.12 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2937.50 | 806.86 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2758.39 | 284.66 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2576.44 | 38.95 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2550.87 | 31.18 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2361.11 | 7.72 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2217.28 | 29.27 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2479.32 | 124.67 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3669.43 | 649.97 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4007.67 | 1212.53 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3144.76 | 1611.43 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2870.02 | 642.73 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2217.28 | 7.72 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4007.67 | 1639.41 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 743.57 | 1125.54 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 993.47 | 882.79 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1558.41 | 546.79 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2323.47 | 206.07 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2570.48 | 35.37 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2558.01 | 26.99 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1915.03 | 8.03 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1647.11 | 24.19 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1584.74 | 87.34 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1490.88 | 424.34 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1130.43 | 798.13 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 748.38 | 1086.63 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1607.14 | 435.76 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 743.57 | 8.03 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2570.48 | 1125.54 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.16 | 1439.67 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 587.92 | 1150.52 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1021.93 | 714.70 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1721.74 | 249.46 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2367.69 | 41.73 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2567.05 | 34.17 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2279.74 | 8.88 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1926.85 | 30.52 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1510.61 | 107.39 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1121.26 | 559.25 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 657.33 | 1043.82 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 382.47 | 1408.75 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1378.06 | 563.20 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 346.16 | 8.88 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2567.05 | 1439.67 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 739.33 | 905.08 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1061.43 | 745.74 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1566.03 | 477.31 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2309.75 | 178.20 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2618.96 | 29.14 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2368.33 | 23.12 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1941.00 | 5.09 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1644.59 | 20.57 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1540.53 | 74.90 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1498.03 | 380.71 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1093.91 | 686.00 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 765.84 | 908.39 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1597.49 | 367.84 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 739.33 | 5.09 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2618.96 | 908.39 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2886.71 | 1471.32 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2954.81 | 1225.92 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2930.75 | 786.33 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2730.91 | 285.20 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2533.67 | 41.86 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2506.84 | 33.81 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2315.90 | 7.78 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2181.03 | 31.99 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2458.23 | 127.48 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3656.52 | 642.83 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4016.24 | 1162.72 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3195.68 | 1484.54 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2862.49 | 605.67 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2181.03 | 7.78 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4016.24 | 1484.54 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 773.75 | 1014.44 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 1010.51 | 823.97 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1556.66 | 530.85 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2306.27 | 205.41 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2544.04 | 37.09 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2530.32 | 28.21 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1889.16 | 7.85 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1626.96 | 25.50 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1573.56 | 87.35 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1486.32 | 414.77 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1141.78 | 757.06 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 776.28 | 996.48 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1603.02 | 408.90 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 773.75 | 7.85 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2544.04 | 1014.44 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643908E+09 | 0.489136E+10 | 0.122065E+10 | 0.00 | 0.122065E+10 | 0.00 | 0.00 |
February | 0.122191E+10 | 0.335280E+10 | 0.130740E+10 | 0.00 | 0.130740E+10 | 0.00 | 0.00 |
March | 0.265399E+10 | 0.210970E+10 | 0.174422E+10 | 0.00 | 0.174422E+10 | 0.00 | 0.00 |
April | 0.443205E+10 | 0.639866E+09 | 0.183157E+10 | 6211386.31 | 0.182536E+10 | 0.00 | 0.00 |
May | 0.639806E+10 | 99249028.93 | 0.209689E+10 | 58841859.56 | 0.203805E+10 | 0.00 | 0.00 |
June | 0.671334E+10 | 72690225.82 | 0.210059E+10 | 77805434.24 | 0.202279E+10 | 0.00 | 0.00 |
July | 0.618870E+10 | 15426243.70 | 0.214072E+10 | 33899197.52 | 0.210682E+10 | 0.00 | 0.00 |
August | 0.517380E+10 | 56188964.63 | 0.196524E+10 | 6124708.88 | 0.195911E+10 | 0.00 | 0.00 |
September | 0.393277E+10 | 0.260596E+09 | 0.169460E+10 | 118989.86 | 0.169448E+10 | 0.00 | 0.00 |
October | 0.294817E+10 | 0.159670E+10 | 0.151701E+10 | 0.00 | 0.151701E+10 | 0.00 | 0.00 |
November | 0.152219E+10 | 0.316066E+10 | 0.124347E+10 | 0.00 | 0.124347E+10 | 0.00 | 0.00 |
December | 0.713335E+09 | 0.476580E+10 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.425422E+11 | 0.210210E+11 | 0.200531E+11 | 0.183002E+09 | 0.198701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.643908E+09 | 15426243.70 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Maximum of Months | 0.671334E+10 | 0.489136E+10 | 0.214072E+10 | 77805434.24 | 0.210682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175835E+10 | 0.294698E+10 | 0.174327E+10 | 0.699724E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.247743E+10 | 0.203962E+10 | 0.191290E+10 | 0.789733E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.421785E+10 | 0.129165E+10 | 0.258355E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.608435E+10 | 0.383791E+09 | 0.297461E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.713407E+10 | 60056837.43 | 0.302542E+10 | 0.134131E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.626273E+10 | 41023293.98 | 0.238287E+10 | 0.790633E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.535617E+10 | 6153088.83 | 0.206950E+10 | 0.437022E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.454450E+10 | 19780043.08 | 0.186470E+10 | 0.324502E+09 | 0.154020E+10 | 0.00 | 0.00 |
September | 0.405494E+10 | 0.154337E+09 | 0.192796E+10 | 0.537659E+09 | 0.139030E+10 | 0.00 | 0.00 |
October | 0.404135E+10 | 0.100369E+10 | 0.217926E+10 | 0.880276E+09 | 0.129898E+10 | 0.00 | 0.00 |
November | 0.277446E+10 | 0.192618E+10 | 0.186990E+10 | 0.802644E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.185364E+10 | 0.285326E+10 | 0.168482E+10 | 0.667536E+09 | 0.101729E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505598E+11 | 0.127265E+11 | 0.262187E+11 | 0.972435E+10 | 0.164944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175835E+10 | 6153088.83 | 0.168482E+10 | 0.324502E+09 | 0.101729E+10 | 0.00 | 0.00 |
Maximum of Months | 0.713407E+10 | 0.294698E+10 | 0.302542E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760959E+10 | 0.446170E+10 | 0.555142E+10 | 0.337318E+10 | 0.217825E+10 | 0.00 | 0.00 |
February | 0.712161E+10 | 0.324299E+10 | 0.476777E+10 | 0.264814E+10 | 0.211962E+10 | 0.00 | 0.00 |
March | 0.789294E+10 | 0.216757E+10 | 0.451334E+10 | 0.199349E+10 | 0.251985E+10 | 0.00 | 0.00 |
April | 0.712337E+10 | 0.700042E+09 | 0.306794E+10 | 0.865857E+09 | 0.220208E+10 | 0.00 | 0.00 |
May | 0.684748E+10 | 0.100764E+09 | 0.227980E+10 | 0.168765E+09 | 0.211104E+10 | 0.00 | 0.00 |
June | 0.655378E+10 | 72627066.98 | 0.201816E+10 | 34438844.85 | 0.198372E+10 | 0.00 | 0.00 |
July | 0.628042E+10 | 14326585.39 | 0.217530E+10 | 29919095.19 | 0.214538E+10 | 0.00 | 0.00 |
August | 0.587728E+10 | 59194837.87 | 0.230752E+10 | 0.123238E+09 | 0.218429E+10 | 0.00 | 0.00 |
September | 0.644018E+10 | 0.292876E+09 | 0.299363E+10 | 0.776997E+09 | 0.221663E+10 | 0.00 | 0.00 |
October | 0.986407E+10 | 0.170278E+10 | 0.532189E+10 | 0.297171E+10 | 0.235018E+10 | 0.00 | 0.00 |
November | 0.104283E+11 | 0.316586E+10 | 0.643288E+10 | 0.425199E+10 | 0.218090E+10 | 0.00 | 0.00 |
December | 0.843087E+10 | 0.444176E+10 | 0.593256E+10 | 0.371749E+10 | 0.221506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.904699E+11 | 0.204225E+11 | 0.473622E+11 | 0.209552E+11 | 0.264070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.587728E+10 | 14326585.39 | 0.201816E+10 | 29919095.19 | 0.198372E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104283E+11 | 0.446170E+10 | 0.643288E+10 | 0.425199E+10 | 0.251985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188871E+10 | 0.339555E+10 | 0.170551E+10 | 0.663719E+09 | 0.104179E+10 | 0.00 | 0.00 |
February | 0.229929E+10 | 0.246729E+10 | 0.176155E+10 | 0.649181E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.407674E+10 | 0.167919E+10 | 0.252903E+10 | 0.101094E+10 | 0.151809E+10 | 0.00 | 0.00 |
April | 0.586468E+10 | 0.660964E+09 | 0.297485E+10 | 0.139509E+10 | 0.157976E+10 | 0.00 | 0.00 |
May | 0.681192E+10 | 0.107798E+09 | 0.291080E+10 | 0.123470E+10 | 0.167610E+10 | 0.00 | 0.00 |
June | 0.649767E+10 | 84073500.71 | 0.264583E+10 | 0.102771E+10 | 0.161812E+10 | 0.00 | 0.00 |
July | 0.493549E+10 | 34338670.84 | 0.202878E+10 | 0.394599E+09 | 0.163419E+10 | 0.00 | 0.00 |
August | 0.412535E+10 | 0.136727E+09 | 0.186323E+10 | 0.331152E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.405393E+10 | 0.259985E+09 | 0.198210E+10 | 0.581889E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.391844E+10 | 0.126267E+10 | 0.213183E+10 | 0.848893E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.280749E+10 | 0.240318E+10 | 0.186638E+10 | 0.795441E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.181277E+10 | 0.354403E+10 | 0.165031E+10 | 0.629301E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490925E+11 | 0.160358E+11 | 0.260502E+11 | 0.956263E+10 | 0.164876E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181277E+10 | 34338670.84 | 0.165031E+10 | 0.331152E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.681192E+10 | 0.354403E+10 | 0.297485E+10 | 0.139509E+10 | 0.167610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770926E+09 | 0.441163E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.132678E+10 | 0.305299E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.272324E+10 | 0.200298E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.452316E+10 | 0.654753E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.645319E+10 | 0.104133E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.676664E+10 | 82101368.19 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.622582E+10 | 23443576.69 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.525633E+10 | 74959161.40 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.396025E+10 | 0.277196E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.301247E+10 | 0.155047E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.162866E+10 | 0.291470E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.877003E+09 | 0.422915E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.435245E+11 | 0.193785E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.770926E+09 | 23443576.69 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676664E+10 | 0.441163E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.183731E+10 | 0.273029E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.250633E+10 | 0.193407E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.420195E+10 | 0.130653E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.604110E+10 | 0.456161E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.710637E+10 | 70134612.65 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.622772E+10 | 54163211.38 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.529157E+10 | 13367478.11 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.447769E+10 | 49688439.34 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.403196E+10 | 0.188216E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.403066E+10 | 0.103288E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.279627E+10 | 0.186940E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.193193E+10 | 0.267161E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.504809E+11 | 0.123765E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183731E+10 | 13367478.11 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.710637E+10 | 0.273029E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756544E+10 | 0.439099E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.708511E+10 | 0.317187E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.786779E+10 | 0.216110E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.714975E+10 | 0.737837E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.690073E+10 | 0.104332E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.661186E+10 | 80829854.03 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.632400E+10 | 20687873.06 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.593875E+10 | 78391884.38 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.642640E+10 | 0.323154E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.982821E+10 | 0.174089E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.103879E+11 | 0.314289E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.842293E+10 | 0.431606E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.905088E+11 | 0.202690E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.593875E+10 | 20687873.06 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103879E+11 | 0.439099E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199157E+10 | 0.301464E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.240341E+10 | 0.213564E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.417406E+10 | 0.146452E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.602243E+10 | 0.534122E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.688478E+10 | 94745930.21 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.663035E+10 | 69969362.54 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.512922E+10 | 21495870.76 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.441161E+10 | 64786845.55 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.410764E+10 | 0.226390E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.399318E+10 | 0.113654E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.293008E+10 | 0.206875E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.200447E+10 | 0.291044E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.506828E+11 | 0.137420E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199157E+10 | 21495870.76 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688478E+10 | 0.301464E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.927162E+09 | 0.385600E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.142229E+10 | 0.278333E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.273713E+10 | 0.191425E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.446274E+10 | 0.646600E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.634162E+10 | 0.111777E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.665380E+10 | 88557232.72 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.610606E+10 | 23777652.66 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.516088E+10 | 81754208.37 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.391549E+10 | 0.278363E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.300318E+10 | 0.149790E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.170381E+10 | 0.270558E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.102440E+10 | 0.377320E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.434586E+11 | 0.177611E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.927162E+09 | 23777652.66 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.665380E+10 | 0.385600E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198023E+10 | 0.242417E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.256781E+10 | 0.180408E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.419447E+10 | 0.127843E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.598687E+10 | 0.461895E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.701462E+10 | 78056346.88 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.613870E+10 | 59920710.63 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.519876E+10 | 13630153.48 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.440486E+10 | 55100088.80 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.399305E+10 | 0.194128E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.401232E+10 | 0.101968E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.283541E+10 | 0.177812E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.205122E+10 | 0.243302E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.503783E+11 | 0.116002E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.198023E+10 | 13630153.48 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.701462E+10 | 0.243302E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773177E+10 | 0.394079E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.714827E+10 | 0.296574E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.784973E+10 | 0.210611E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.707851E+10 | 0.739235E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.678618E+10 | 0.112125E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.649772E+10 | 87646053.78 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.620291E+10 | 20825881.41 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.584166E+10 | 85689032.40 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.637173E+10 | 0.330434E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.979362E+10 | 0.172176E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.104101E+11 | 0.301377E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.855930E+10 | 0.397618E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.902715E+11 | 0.191003E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.584166E+10 | 20825881.41 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104101E+11 | 0.397618E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207241E+10 | 0.271707E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.244462E+10 | 0.199335E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.416937E+10 | 0.142182E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.597785E+10 | 0.532421E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.681396E+10 | 99333638.78 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.655858E+10 | 73112733.06 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.505993E+10 | 21025773.69 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.435766E+10 | 68303362.12 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.407866E+10 | 0.226418E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.398096E+10 | 0.111091E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.295949E+10 | 0.196229E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.207920E+10 | 0.266898E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505527E+11 | 0.128951E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.207241E+10 | 21025773.69 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.681396E+10 | 0.271707E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.312942E+11 | -0.302739E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102028E+10 | 58.97 | 0.00 | 0.00 |
February | 0.278503E+11 | -0.269278E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922424131.6 | 58.97 | 0.00 | 0.00 |
March | 0.305695E+11 | -0.295448E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102468E+10 | 58.98 | 0.00 | 0.00 |
April | 0.250264E+11 | -0.240385E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987845935.5 | 58.97 | 0.00 | 0.00 |
May | 0.237030E+11 | -0.226812E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102177E+10 | 58.97 | 0.00 | 0.00 |
June | 0.211369E+11 | -0.201477E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989217913.7 | 58.96 | 0.00 | 0.00 |
July | 0.192836E+11 | -0.182668E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101679E+10 | 58.97 | 0.00 | 0.00 |
August | 0.217370E+11 | -0.207162E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102085E+10 | 58.97 | 0.00 | 0.00 |
September | 0.217880E+11 | -0.208025E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985518359.4 | 58.96 | 0.00 | 0.00 |
October | 0.253260E+11 | -0.243083E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101768E+10 | 58.98 | 0.00 | 0.00 |
November | 0.276753E+11 | -0.266901E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985122701.1 | 58.98 | 0.00 | 0.00 |
December | 0.297105E+11 | -0.286923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101815E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.305101E+12 | -0.293090E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120103E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.192836E+11 | -0.302739E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102468E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.312942E+11 | -0.182668E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -922424131.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295300E+10 | 23921.66 | 05-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.749852E+09 | 18621.13 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113678E+09 | 9635.31 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134704E+10 | 23880.24 | 21-DEC-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295300E+10 | 23921.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413795E+11 | 202636.23 | 21-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148687E+11 | 198206.98 | 02-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7779879.74 | 5212.19 | 01-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8105.38 | 13.51 | 27-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8127.70 | 13.55 | 19-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 618.31 | 5.15 | 09-OCT-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.249445E+10 | 137328.87 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267019E+11 | 210114.90 | 21-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413795E+11 | 210114.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178849E+10 | 43248.47 | 03-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148960E+09 | 16543.60 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531509E+09 | 39752.41 | 21-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178849E+10 | 43248.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.964960E+09 | 35163.30 | 03-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134678E+09 | 24519.65 | 11-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323077E+09 | 27400.89 | 21-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.964960E+09 | 35163.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85955542.86 | 14697.20 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46480406.71 | 13345.98 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11578537.24 | 5805.71 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85955542.86 | 14697.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101662E+10 | 30623.01 | 03-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122738E+09 | 20563.87 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304266E+09 | 30411.90 | 23-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101662E+10 | 30623.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.487287E+10 | 18897.87 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153022E+10 | 16139.25 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236954E+09 | 14133.72 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285617E+10 | 17068.83 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.487287E+10 | 18897.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652877E+09 | 76629.15 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7102271.91 | 1774.48 | 23-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652877E+09 | 76629.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176539E+10 | 20450.55 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415090E+09 | 18995.65 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2496079.43 | 559.32 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63922880.49 | 3528.81 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.988378E+09 | 20392.87 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176539E+10 | 20450.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.826704E+09 | 14314.94 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188730E+09 | 12116.56 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 354130.06 | 314.82 | 01-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18956346.63 | 1967.46 | 27-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.460271E+09 | 14274.82 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826704E+09 | 14314.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.712192E+09 | 20024.25 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155941E+09 | 18083.71 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274394E+09 | 17849.28 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.712192E+09 | 20024.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.896790E+09 | 13918.11 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220271E+09 | 10892.23 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14909805.84 | 1031.61 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453980E+09 | 12728.97 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896790E+09 | 13918.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.430529E+11 | 0.430212E+11 | 93564.44 | 02-JAN-06:03 | 64434.90 | 0.30 |
February | 0.00 | 0.00 | 0.640763E+11 | 0.639421E+11 | 143153.15 | 25-FEB-04:02 | 101629.15 | 0.47 |
March | 0.00 | 0.00 | 0.127796E+12 | 0.125758E+12 | 205815.13 | 14-MAR-05:03 | 155988.20 | 0.67 |
April | 0.00 | 0.00 | 0.201841E+12 | 0.192281E+12 | 269308.63 | 17-APR-05:03 | 183950.65 | 0.77 |
May | 0.00 | 0.00 | 0.265645E+12 | 0.216240E+12 | 299686.69 | 22-MAY-05:02 | 180565.51 | 0.81 |
June | 0.00 | 0.00 | 0.326590E+12 | 0.223482E+12 | 333376.73 | 26-JUN-04:12 | 176922.98 | 0.85 |
July | 0.00 | 0.00 | 0.392101E+12 | 0.212508E+12 | 349445.89 | 18-JUL-05:03 | 180770.97 | 0.86 |
August | 0.00 | 0.00 | 0.421781E+12 | 0.221304E+12 | 352011.27 | 28-AUG-04:22 | 189035.07 | 0.89 |
September | 0.00 | 0.00 | 0.284652E+12 | 0.160253E+12 | 323895.79 | 05-SEP-03:02 | 179098.24 | 0.75 |
October | 0.00 | 0.00 | 0.167162E+12 | 0.143617E+12 | 268176.59 | 11-OCT-05:03 | 171362.02 | 0.73 |
November | 0.00 | 0.00 | 0.101684E+12 | 0.100742E+12 | 162277.79 | 06-NOV-06:03 | 128988.94 | 0.62 |
December | 0.00 | 0.00 | 0.629009E+11 | 0.629009E+11 | 107797.90 | 29-DEC-06:03 | 107797.90 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.245928E+13 | 0.176605E+13 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 0.430529E+11 | 0.430212E+11 | 93564.44 | 64434.90 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.421781E+12 | 0.223482E+12 | 352011.27 | 189035.07 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.292614E+12 | 0.292594E+12 | 858787.78 | 18-JAN-06:02 | 718261.56 | 0.25 |
February | 0.00 | 0.00 | 0.465179E+12 | 0.463893E+12 | 1335250.62 | 25-FEB-06:02 | 905878.82 | 0.39 |
March | 0.00 | 0.00 | 0.100068E+13 | 0.985698E+12 | 2087346.66 | 11-MAR-06:02 | 1543887.60 | 0.57 |
April | 0.00 | 0.00 | 0.160852E+13 | 0.153850E+13 | 2319218.39 | 17-APR-05:02 | 1603254.44 | 0.62 |
May | 0.00 | 0.00 | 0.249288E+13 | 0.201321E+13 | 3184945.36 | 24-MAY-03:02 | 1636916.67 | 0.77 |
June | 0.00 | 0.00 | 0.296692E+13 | 0.199482E+13 | 3336617.41 | 29-JUN-05:03 | 1696446.59 | 0.78 |
July | 0.00 | 0.00 | 0.338482E+13 | 0.176194E+13 | 3596906.02 | 25-JUL-03:02 | 1693714.88 | 0.75 |
August | 0.00 | 0.00 | 0.336888E+13 | 0.166311E+13 | 3497735.43 | 11-AUG-03:02 | 1637981.83 | 0.73 |
September | 0.00 | 0.00 | 0.253262E+13 | 0.139040E+13 | 3337720.37 | 11-SEP-03:02 | 1642119.03 | 0.66 |
October | 0.00 | 0.00 | 0.139517E+13 | 0.119290E+13 | 2579318.64 | 04-OCT-03:02 | 1612477.69 | 0.65 |
November | 0.00 | 0.00 | 0.758642E+12 | 0.753137E+12 | 1499219.40 | 09-NOV-06:03 | 990721.26 | 0.53 |
December | 0.00 | 0.00 | 0.360288E+12 | 0.360288E+12 | 815832.01 | 29-DEC-06:03 | 815832.01 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.206272E+14 | 0.144105E+14 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.292614E+12 | 0.292594E+12 | 815832.01 | 718261.56 | 0.25 | |
Maximum of Months | 0.00 | 0.00 | 0.338482E+13 | 0.201321E+13 | 3596906.02 | 1696446.59 | 0.78 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208903E+11 | 0.208903E+11 | 68078.97 | 12-JAN-15:00 | 68078.97 | 0.22 |
February | 0.00 | 0.00 | 0.418387E+11 | 0.417231E+11 | 123144.95 | 25-FEB-06:02 | 82190.48 | 0.36 |
March | 0.00 | 0.00 | 0.102997E+12 | 0.101626E+12 | 205041.87 | 11-MAR-06:02 | 153463.90 | 0.55 |
April | 0.00 | 0.00 | 0.179099E+12 | 0.172033E+12 | 261189.92 | 27-APR-05:03 | 197247.52 | 0.63 |
May | 0.00 | 0.00 | 0.280010E+12 | 0.230050E+12 | 322399.56 | 22-MAY-05:02 | 190962.91 | 0.79 |
June | 0.00 | 0.00 | 0.330319E+12 | 0.229026E+12 | 366540.81 | 29-JUN-05:03 | 190084.44 | 0.80 |
July | 0.00 | 0.00 | 0.370140E+12 | 0.199831E+12 | 389580.37 | 18-JUL-05:03 | 196389.87 | 0.77 |
August | 0.00 | 0.00 | 0.361733E+12 | 0.185116E+12 | 377870.57 | 10-AUG-05:03 | 191249.87 | 0.75 |
September | 0.00 | 0.00 | 0.270393E+12 | 0.151985E+12 | 365329.73 | 11-SEP-03:02 | 181336.56 | 0.68 |
October | 0.00 | 0.00 | 0.143907E+12 | 0.124952E+12 | 250752.91 | 11-OCT-03:02 | 159312.81 | 0.64 |
November | 0.00 | 0.00 | 0.716544E+11 | 0.714217E+11 | 137318.31 | 10-NOV-06:02 | 94145.18 | 0.50 |
December | 0.00 | 0.00 | 0.274376E+11 | 0.274376E+11 | 76206.47 | 28-DEC-15:00 | 76206.47 | 0.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.220042E+13 | 0.155609E+13 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.208903E+11 | 0.208903E+11 | 68078.97 | 68078.97 | 0.22 | |
Maximum of Months | 0.00 | 0.00 | 0.370140E+12 | 0.230050E+12 | 389580.37 | 197247.52 | 0.80 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.572262E+11 | 0.571302E+11 | 131425.39 | 18-JAN-04:03 | 96862.41 | 0.41 |
February | 0.00 | 0.00 | 0.584359E+11 | 0.583337E+11 | 141975.86 | 25-FEB-04:02 | 96019.24 | 0.52 |
March | 0.00 | 0.00 | 0.800910E+11 | 0.797856E+11 | 165426.40 | 11-MAR-04:02 | 97647.24 | 0.57 |
April | 0.00 | 0.00 | 0.914767E+11 | 0.894053E+11 | 164193.93 | 24-APR-03:02 | 106876.59 | 0.53 |
May | 0.00 | 0.00 | 0.117337E+12 | 0.104633E+12 | 198742.01 | 22-MAY-03:13 | 97255.65 | 0.61 |
June | 0.00 | 0.00 | 0.137207E+12 | 0.108715E+12 | 236263.89 | 26-JUN-03:02 | 92417.83 | 0.63 |
July | 0.00 | 0.00 | 0.158194E+12 | 0.108157E+12 | 250145.32 | 23-JUL-19:36 | 96774.90 | 0.64 |
August | 0.00 | 0.00 | 0.176498E+12 | 0.116683E+12 | 257507.09 | 27-AUG-11:46 | 100622.15 | 0.68 |
September | 0.00 | 0.00 | 0.140816E+12 | 0.100953E+12 | 239430.35 | 11-SEP-00:32 | 93453.53 | 0.65 |
October | 0.00 | 0.00 | 0.103132E+12 | 0.959612E+11 | 180804.89 | 04-OCT-03:02 | 103051.36 | 0.64 |
November | 0.00 | 0.00 | 0.801098E+11 | 0.797266E+11 | 152505.79 | 09-NOV-04:03 | 95752.43 | 0.60 |
December | 0.00 | 0.00 | 0.648993E+11 | 0.648550E+11 | 126074.69 | 30-DEC-04:02 | 93356.91 | 0.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.126542E+13 | 0.106434E+13 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.572262E+11 | 0.571302E+11 | 126074.69 | 92417.83 | 0.41 | |
Maximum of Months | 0.00 | 0.00 | 0.176498E+12 | 0.116683E+12 | 257507.09 | 106876.59 | 0.68 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.338674E+12 | 0.325024E+12 | 132372.64 | 17-JAN-16:00 | 125718.64 | 0.00 |
February | 0.00 | 0.00 | 0.533999E+12 | 0.517087E+12 | 226098.73 | 24-FEB-17:00 | 220065.53 | 0.00 |
March | 0.00 | 0.00 | 0.836927E+12 | 0.822905E+12 | 396190.99 | 31-MAR-24:00 | 393954.92 | 0.00 |
April | 0.00 | 0.00 | 0.103526E+13 | 0.102905E+13 | 410045.05 | 25-APR-04:55 | 402263.06 | 0.00 |
May | 0.00 | 0.00 | 0.363416E+12 | 0.346666E+12 | 226630.51 | 31-MAY-23:03 | 212579.42 | 0.00 |
June | 0.00 | 0.00 | 0.599388E+12 | 0.573781E+12 | 318667.16 | 30-JUN-23:03 | 306787.88 | 0.00 |
July | 0.00 | 0.00 | 0.874812E+12 | 0.838275E+12 | 401697.40 | 31-JUL-24:00 | 390330.61 | 0.00 |
August | 0.00 | 0.00 | 0.110063E+13 | 0.106510E+13 | 422135.51 | 10-AUG-14:00 | 402334.99 | 0.00 |
September | 0.00 | 0.00 | 0.367387E+12 | 0.336171E+12 | 227193.75 | 30-SEP-23:05 | 213109.72 | 0.00 |
October | 0.00 | 0.00 | 0.602783E+12 | 0.586394E+12 | 311080.24 | 31-OCT-24:00 | 302623.05 | 0.00 |
November | 0.00 | 0.00 | 0.818526E+12 | 0.798970E+12 | 321931.75 | 24-NOV-08:15 | 307748.97 | 0.00 |
December | 0.00 | 0.00 | 0.110013E+13 | 0.106547E+13 | 422266.44 | 22-DEC-06:03 | 396669.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.857192E+13 | 0.830489E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338674E+12 | 0.325024E+12 | 132372.64 | 125718.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110063E+13 | 0.106547E+13 | 422266.44 | 402334.99 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.497121E+10 | 0.482668E+10 | 2497.49 | 12-JAN-17:00 | 2367.43 | 0.00 |
February | 0.00 | 0.00 | 0.958723E+10 | 0.936120E+10 | 4544.48 | 21-FEB-17:00 | 4394.85 | 0.00 |
March | 0.00 | 0.00 | 0.162276E+11 | 0.158972E+11 | 7788.30 | 31-MAR-24:00 | 7688.43 | 0.00 |
April | 0.00 | 0.00 | 0.209214E+11 | 0.206144E+11 | 8513.86 | 17-APR-00:12 | 8276.64 | 0.00 |
May | 0.00 | 0.00 | 0.721026E+10 | 0.655003E+10 | 4644.81 | 31-MAY-23:03 | 4035.96 | 0.00 |
June | 0.00 | 0.00 | 0.123209E+11 | 0.112422E+11 | 6536.06 | 30-JUN-23:03 | 6024.93 | 0.00 |
July | 0.00 | 0.00 | 0.181653E+11 | 0.165573E+11 | 8585.00 | 31-JUL-23:03 | 7784.92 | 0.00 |
August | 0.00 | 0.00 | 0.228481E+11 | 0.211574E+11 | 8810.19 | 10-AUG-14:10 | 7990.56 | 0.00 |
September | 0.00 | 0.00 | 0.735223E+10 | 0.608339E+10 | 4627.40 | 30-SEP-23:05 | 4006.30 | 0.00 |
October | 0.00 | 0.00 | 0.117135E+11 | 0.110957E+11 | 5980.60 | 31-OCT-23:10 | 5731.68 | 0.00 |
November | 0.00 | 0.00 | 0.155748E+11 | 0.152648E+11 | 6598.18 | 08-NOV-16:40 | 6344.72 | 0.00 |
December | 0.00 | 0.00 | 0.205473E+11 | 0.203775E+11 | 8274.71 | 28-DEC-17:00 | 8114.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167440E+12 | 0.159028E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.497121E+10 | 0.482668E+10 | 2497.49 | 2367.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228481E+11 | 0.211574E+11 | 8810.19 | 8276.64 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.377004E+11 | 0.363412E+11 | 23183.23 | 13-JAN-17:00 | 21297.10 | 0.00 |
February | 0.00 | 0.00 | 0.854044E+11 | 0.831714E+11 | 42880.72 | 22-FEB-17:00 | 41351.83 | 0.00 |
March | 0.00 | 0.00 | 0.153092E+12 | 0.149800E+12 | 75195.09 | 31-MAR-24:00 | 74190.88 | 0.00 |
April | 0.00 | 0.00 | 0.198702E+12 | 0.195624E+12 | 80614.87 | 12-APR-16:00 | 78353.06 | 0.00 |
May | 0.00 | 0.00 | 0.681529E+11 | 0.616266E+11 | 44851.89 | 31-MAY-23:03 | 38576.37 | 0.00 |
June | 0.00 | 0.00 | 0.117526E+12 | 0.106798E+12 | 63227.46 | 30-JUN-23:03 | 58062.14 | 0.00 |
July | 0.00 | 0.00 | 0.173524E+12 | 0.157491E+12 | 81906.53 | 31-JUL-23:03 | 73947.37 | 0.00 |
August | 0.00 | 0.00 | 0.216971E+12 | 0.200030E+12 | 83828.02 | 10-AUG-14:10 | 75690.93 | 0.00 |
September | 0.00 | 0.00 | 0.691594E+11 | 0.566274E+11 | 44957.67 | 30-SEP-23:05 | 38607.43 | 0.00 |
October | 0.00 | 0.00 | 0.110266E+12 | 0.104139E+12 | 56384.60 | 31-OCT-23:10 | 53823.49 | 0.00 |
November | 0.00 | 0.00 | 0.144479E+12 | 0.141393E+12 | 62666.39 | 08-NOV-16:50 | 60066.35 | 0.00 |
December | 0.00 | 0.00 | 0.187507E+12 | 0.185807E+12 | 78130.00 | 28-DEC-17:00 | 76535.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156248E+13 | 0.147885E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377004E+11 | 0.363412E+11 | 23183.23 | 21297.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216971E+12 | 0.200030E+12 | 83828.02 | 78353.06 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234191E+10 | 0.221737E+10 | 2332.92 | 12-JAN-17:00 | 2196.92 | 0.00 |
February | 0.00 | 0.00 | 0.786922E+10 | 0.763304E+10 | 4340.53 | 22-FEB-17:00 | 4179.75 | 0.00 |
March | 0.00 | 0.00 | 0.151508E+11 | 0.148028E+11 | 7476.36 | 31-MAR-24:00 | 7368.67 | 0.00 |
April | 0.00 | 0.00 | 0.200388E+11 | 0.197134E+11 | 8302.65 | 16-APR-20:54 | 8018.83 | 0.00 |
May | 0.00 | 0.00 | 0.706091E+10 | 0.638726E+10 | 4464.51 | 31-MAY-23:03 | 3821.67 | 0.00 |
June | 0.00 | 0.00 | 0.119815E+11 | 0.108883E+11 | 6396.70 | 30-JUN-23:03 | 5871.47 | 0.00 |
July | 0.00 | 0.00 | 0.175802E+11 | 0.159563E+11 | 8391.06 | 31-JUL-23:03 | 7570.06 | 0.00 |
August | 0.00 | 0.00 | 0.220411E+11 | 0.203197E+11 | 8561.16 | 10-AUG-14:10 | 7732.13 | 0.00 |
September | 0.00 | 0.00 | 0.699846E+10 | 0.572607E+10 | 4515.58 | 30-SEP-23:05 | 3871.85 | 0.00 |
October | 0.00 | 0.00 | 0.109582E+11 | 0.103274E+11 | 5521.30 | 31-OCT-23:10 | 5252.94 | 0.00 |
November | 0.00 | 0.00 | 0.139690E+11 | 0.136430E+11 | 6327.92 | 08-NOV-16:40 | 6068.81 | 0.00 |
December | 0.00 | 0.00 | 0.175978E+11 | 0.174121E+11 | 7825.87 | 28-DEC-17:00 | 7658.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153588E+12 | 0.145027E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.234191E+10 | 0.221737E+10 | 2332.92 | 2196.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220411E+11 | 0.203197E+11 | 8561.16 | 8018.83 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 21359.63 | 425968.22 | 02-JAN-06:04 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7595.41 | 327458.38 | 04-FEB-06:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.31 | 4406.44 | 01-MAR-05:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 10.59 | 27-APR-11:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 10.59 | 19-MAY-14:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 4.09 | 09-OCT-07:52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1133.24 | 175983.11 | 27-NOV-06:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12655.32 | 337490.72 | 23-DEC-06:08 |
Annual Sum or Average | 0.00 | 3565.03 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 21359.63 | 425968.22 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 326796.58 | 1594393.57 | 25-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 471380.99 | 1692677.54 | 16-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 755073.60 | 2375721.52 | 30-MAR-05:04 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1074489.19 | 3310459.50 | 17-APR-05:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1403433.97 | 3423300.94 | 31-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1616665.58 | 5924845.90 | 23-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1697116.96 | 4141467.93 | 19-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1733015.25 | 6044047.92 | 28-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1340399.67 | 4362550.10 | 05-SEP-05:05 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 926644.25 | 2765690.79 | 04-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 630086.36 | 1916715.66 | 21-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 391503.52 | 1674535.34 | 28-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1033668.49 | 0.00 | ||||
Minimum of Months | 326796.58 | 1594393.57 | 0.00 | 0.00 | ||
Maximum of Months | 1733015.25 | 6044047.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174636.32 | 1297987.32 | 18-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 296000.85 | 2179854.72 | 25-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 552323.58 | 3403329.89 | 11-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 866724.57 | 4104532.92 | 17-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1233895.00 | 5076598.34 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1514469.01 | 5892700.15 | 23-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1624922.87 | 5648238.95 | 03-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1659919.61 | 6032962.43 | 28-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1275509.92 | 5652573.75 | 16-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 735458.53 | 4111542.64 | 04-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 450921.19 | 2425180.87 | 09-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 219993.77 | 1343700.83 | 01-DEC-16:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 886992.89 | 0.00 | ||||
Minimum of Months | 174636.32 | 1297987.32 | 0.00 | 0.00 | ||
Maximum of Months | 1659919.61 | 6032962.43 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222595.95 | 585712.30 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 499379.25 | 1020372.93 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 967619.89 | 1766089.35 | 28-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1589845.92 | 2227924.21 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1121975.88 | 1783451.98 | 01-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1414857.64 | 2070632.17 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1557954.26 | 2093254.35 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1671856.78 | 2090186.25 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 901322.35 | 1397927.86 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 906795.39 | 1580576.33 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 822232.14 | 1428648.64 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 788623.96 | 1326856.81 | 28-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1041617.66 | 0.00 | ||||
Minimum of Months | 222595.95 | 585712.30 | 0.00 | 0.00 | ||
Maximum of Months | 1671856.78 | 2227924.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12725.85 | 41927.31 | 17-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12554.37 | 41679.43 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12446.63 | 39940.62 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 10694.98 | 36276.05 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9895.27 | 32609.59 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9206.65 | 28990.28 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 8254.27 | 26816.34 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 9167.18 | 28562.54 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 9455.76 | 31750.99 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10502.47 | 35895.01 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11719.15 | 39406.23 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12135.10 | 41504.85 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 10719.86 | ||||
Minimum of Months | 0.00 | 0.00 | 8254.27 | 26816.34 | ||
Maximum of Months | 0.00 | 0.00 | 12725.85 | 41927.31 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 194487.25 | 1128182.40 | 25-JAN-15:50 | 2612.15 | 118774.05 | 07-JAN-06:00 |
February | 316978.46 | 2761642.37 | 23-FEB-16:30 | 930.10 | 74285.16 | 03-FEB-07:00 |
March | 638017.81 | 3479641.97 | 10-MAR-17:00 | 104.96 | 51344.51 | 20-MAR-03:00 |
April | 1255300.56 | 5877172.55 | 18-APR-14:00 | 14.23 | 13348.43 | 09-APR-22:55 |
May | 2733730.63 | 7868817.05 | 17-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 4288248.87 | 8980594.72 | 21-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 5505281.37 | 8983059.08 | 17-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 5469505.94 | 8983692.66 | 24-AUG-14:40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3886665.11 | 8876696.42 | 14-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1084430.22 | 5436596.23 | 04-OCT-12:20 | 1.70 | 8507.61 | 30-OCT-02:15 |
November | 499907.61 | 2913681.27 | 01-NOV-14:00 | 268.78 | 50869.25 | 22-NOV-04:30 |
December | 237968.23 | 1252551.63 | 01-DEC-16:10 | 1804.68 | 108634.60 | 21-DEC-08:00 |
Annual Sum or Average | 2187794.87 | 478.80 | ||||
Minimum of Months | 194487.25 | 1128182.40 | 0.00 | 0.00 | ||
Maximum of Months | 5505281.37 | 8983692.66 | 2612.15 | 118774.05 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181207E+11 | 0.95 | 11006.91 | 01-JAN-00:30 | 1.55 |
February | 0.160415E+11 | 0.93 | 11006.91 | 01-FEB-04:03 | 1.55 |
March | 0.182307E+11 | 0.95 | 11006.91 | 01-MAR-04:02 | 1.55 |
April | 0.169505E+11 | 0.92 | 11006.91 | 01-APR-03:02 | 1.54 |
May | 0.183054E+11 | 0.95 | 11006.91 | 01-MAY-00:03 | 1.54 |
June | 0.183301E+11 | 0.99 | 11006.91 | 01-JUN-03:02 | 1.54 |
July | 0.190274E+11 | 0.99 | 11006.91 | 01-JUL-03:02 | 1.54 |
August | 0.201872E+11 | 1.05 | 11006.91 | 01-AUG-03:02 | 1.54 |
September | 0.189432E+11 | 1.02 | 11006.91 | 01-SEP-03:02 | 1.54 |
October | 0.195132E+11 | 1.02 | 11006.91 | 01-OCT-09:16 | 1.53 |
November | 0.187761E+11 | 1.01 | 11006.91 | 01-NOV-03:02 | 1.54 |
December | 0.186310E+11 | 0.98 | 11006.91 | 01-DEC-04:02 | 1.55 |
Annual Sum or Average | 0.221057E+12 | 0.98 | |||
Minimum of Months | 0.160415E+11 | 0.92 | 11006.91 | 1.53 | |
Maximum of Months | 0.201872E+11 | 1.05 | 11006.91 | 1.55 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.670227E+10 | 0.40 | 10669.31 | 02-JAN-04:02 | 1.16 |
February | 0.773403E+10 | 0.47 | 14342.73 | 21-FEB-16:10 | 1.39 |
March | 0.120468E+11 | 0.61 | 23384.51 | 14-MAR-05:03 | 1.89 |
April | 0.148063E+11 | 0.74 | 23384.51 | 17-APR-03:02 | 1.89 |
May | 0.143362E+11 | 0.70 | 23384.51 | 01-MAY-04:22 | 1.89 |
June | 0.153031E+11 | 0.75 | 23384.51 | 01-JUN-05:03 | 1.89 |
July | 0.154211E+11 | 0.74 | 23384.51 | 01-JUL-05:03 | 1.89 |
August | 0.189735E+11 | 0.84 | 23384.51 | 07-AUG-03:02 | 1.89 |
September | 0.118364E+11 | 0.61 | 23384.51 | 02-SEP-05:03 | 1.89 |
October | 0.112935E+11 | 0.59 | 23384.51 | 03-OCT-05:03 | 1.90 |
November | 0.996587E+10 | 0.54 | 21187.51 | 13-NOV-06:03 | 1.78 |
December | 0.915728E+10 | 0.49 | 14043.57 | 29-DEC-06:03 | 1.38 |
Annual Sum or Average | 0.147576E+12 | 0.62 | |||
Minimum of Months | 0.670227E+10 | 0.40 | 10669.31 | 1.16 | |
Maximum of Months | 0.189735E+11 | 0.84 | 23384.51 | 1.90 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.482396E+11 | 0.34 | 101750.77 | 02-JAN-06:01 | 1.16 |
February | 0.538171E+11 | 0.39 | 112339.09 | 23-FEB-06:02 | 1.23 |
March | 0.861837E+11 | 0.49 | 222956.09 | 11-MAR-06:02 | 1.89 |
April | 0.106568E+12 | 0.59 | 222956.09 | 17-APR-05:02 | 1.89 |
May | 0.124707E+12 | 0.65 | 222956.09 | 05-MAY-05:03 | 1.89 |
June | 0.123571E+12 | 0.66 | 222956.09 | 01-JUN-03:02 | 1.89 |
July | 0.111965E+12 | 0.60 | 222956.09 | 03-JUL-05:02 | 1.89 |
August | 0.117353E+12 | 0.61 | 222956.09 | 01-AUG-03:02 | 1.89 |
September | 0.971509E+11 | 0.54 | 222956.09 | 02-SEP-05:03 | 1.89 |
October | 0.848719E+11 | 0.49 | 222956.09 | 02-OCT-05:03 | 1.89 |
November | 0.661801E+11 | 0.43 | 122908.83 | 10-NOV-06:02 | 1.30 |
December | 0.519937E+11 | 0.36 | 101750.77 | 01-DEC-05:03 | 1.17 |
Annual Sum or Average | 0.107260E+13 | 0.51 | |||
Minimum of Months | 0.482396E+11 | 0.34 | 101750.77 | 1.16 | |
Maximum of Months | 0.124707E+12 | 0.66 | 222956.09 | 1.89 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.362669E+10 | 0.30 | 5456.12 | 12-JAN-15:30 | 0.76 |
February | 0.433809E+10 | 0.33 | 9600.46 | 22-FEB-15:00 | 1.04 |
March | 0.810283E+10 | 0.44 | 20567.09 | 30-MAR-05:02 | 1.65 |
April | 0.117565E+11 | 0.58 | 25442.84 | 21-APR-05:03 | 1.89 |
May | 0.145699E+11 | 0.67 | 25442.84 | 11-MAY-05:03 | 1.89 |
June | 0.145692E+11 | 0.68 | 25442.84 | 23-JUN-14:40 | 1.89 |
July | 0.125434E+11 | 0.61 | 25442.84 | 10-JUL-04:03 | 1.89 |
August | 0.125279E+11 | 0.60 | 25442.84 | 07-AUG-05:01 | 1.89 |
September | 0.100990E+11 | 0.52 | 24220.32 | 16-SEP-03:02 | 1.83 |
October | 0.852167E+10 | 0.46 | 18186.19 | 11-OCT-03:02 | 1.53 |
November | 0.583016E+10 | 0.37 | 12001.74 | 10-NOV-06:02 | 1.18 |
December | 0.386228E+10 | 0.30 | 9353.60 | 29-DEC-06:03 | 1.02 |
Annual Sum or Average | 0.110348E+12 | 0.49 | |||
Minimum of Months | 0.362669E+10 | 0.30 | 5456.12 | 0.76 | |
Maximum of Months | 0.145699E+11 | 0.68 | 25442.84 | 1.89 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.970099E+11 | 1.38 | 36219.33 | 01-JAN-00:10 | 1.38 |
February | 0.876218E+11 | 1.38 | 36219.33 | 01-FEB-00:10 | 1.38 |
March | 0.970099E+11 | 1.38 | 36219.33 | 01-MAR-00:10 | 1.38 |
April | 0.938805E+11 | 1.38 | 36219.33 | 01-APR-00:03 | 1.38 |
May | 0.970099E+11 | 1.38 | 36219.33 | 01-MAY-00:03 | 1.38 |
June | 0.938805E+11 | 1.38 | 36219.33 | 01-JUN-00:10 | 1.38 |
July | 0.970099E+11 | 1.38 | 36219.33 | 01-JUL-00:03 | 1.38 |
August | 0.970099E+11 | 1.38 | 36219.33 | 01-AUG-00:03 | 1.38 |
September | 0.938805E+11 | 1.38 | 36219.33 | 01-SEP-00:03 | 1.38 |
October | 0.970099E+11 | 1.38 | 36219.33 | 01-OCT-00:03 | 1.38 |
November | 0.938805E+11 | 1.38 | 36219.33 | 01-NOV-00:10 | 1.38 |
December | 0.970099E+11 | 1.38 | 36219.33 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.114221E+13 | 1.38 | |||
Minimum of Months | 0.876218E+11 | 1.38 | 36219.33 | 1.38 | |
Maximum of Months | 0.970099E+11 | 1.38 | 36219.33 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145638E+10 | 0.94 | 543.75 | 01-JAN-00:10 | 0.94 |
February | 0.131544E+10 | 0.94 | 543.75 | 01-FEB-00:10 | 0.94 |
March | 0.145638E+10 | 0.94 | 543.75 | 01-MAR-00:10 | 0.94 |
April | 0.140940E+10 | 0.94 | 543.75 | 01-APR-00:03 | 0.94 |
May | 0.145638E+10 | 0.93 | 543.75 | 01-MAY-00:07 | 0.94 |
June | 0.140940E+10 | 0.93 | 543.75 | 01-JUN-00:10 | 0.94 |
July | 0.145638E+10 | 0.93 | 543.75 | 01-JUL-00:03 | 0.93 |
August | 0.145638E+10 | 0.93 | 543.75 | 01-AUG-00:03 | 0.94 |
September | 0.140940E+10 | 0.93 | 543.75 | 01-SEP-00:03 | 0.93 |
October | 0.145638E+10 | 0.94 | 543.75 | 01-OCT-00:03 | 0.94 |
November | 0.140940E+10 | 0.94 | 543.75 | 01-NOV-00:10 | 0.94 |
December | 0.145638E+10 | 0.94 | 543.75 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.171478E+11 | 0.94 | |||
Minimum of Months | 0.131544E+10 | 0.93 | 543.75 | 0.93 | |
Maximum of Months | 0.145638E+10 | 0.94 | 543.75 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138657E+11 | 0.94 | 5176.87 | 01-JAN-00:10 | 0.94 |
February | 0.125239E+11 | 0.94 | 5176.87 | 01-FEB-00:10 | 0.94 |
March | 0.138657E+11 | 0.94 | 5176.87 | 01-MAR-00:10 | 0.94 |
April | 0.134184E+11 | 0.94 | 5176.87 | 01-APR-00:03 | 0.94 |
May | 0.138657E+11 | 0.93 | 5176.87 | 01-MAY-00:03 | 0.94 |
June | 0.134184E+11 | 0.93 | 5176.87 | 01-JUN-00:10 | 0.94 |
July | 0.138657E+11 | 0.93 | 5176.87 | 01-JUL-00:03 | 0.93 |
August | 0.138657E+11 | 0.93 | 5176.87 | 01-AUG-00:03 | 0.93 |
September | 0.134184E+11 | 0.93 | 5176.87 | 01-SEP-00:03 | 0.93 |
October | 0.138657E+11 | 0.94 | 5176.87 | 01-OCT-00:03 | 0.94 |
November | 0.134184E+11 | 0.94 | 5176.87 | 01-NOV-00:10 | 0.94 |
December | 0.138657E+11 | 0.94 | 5176.87 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.163258E+12 | 0.94 | |||
Minimum of Months | 0.125239E+11 | 0.93 | 5176.87 | 0.93 | |
Maximum of Months | 0.138657E+11 | 0.94 | 5176.87 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139468E+10 | 0.94 | 520.71 | 01-JAN-00:10 | 0.94 |
February | 0.125971E+10 | 0.94 | 520.71 | 01-FEB-00:10 | 0.94 |
March | 0.139468E+10 | 0.94 | 520.71 | 01-MAR-00:10 | 0.94 |
April | 0.134969E+10 | 0.94 | 520.71 | 01-APR-00:03 | 0.94 |
May | 0.139468E+10 | 0.93 | 520.71 | 01-MAY-00:03 | 0.94 |
June | 0.134969E+10 | 0.93 | 520.71 | 01-JUN-00:10 | 0.94 |
July | 0.139468E+10 | 0.93 | 520.71 | 01-JUL-00:03 | 0.94 |
August | 0.139468E+10 | 0.93 | 520.71 | 01-AUG-00:03 | 0.94 |
September | 0.134969E+10 | 0.93 | 520.71 | 01-SEP-00:03 | 0.93 |
October | 0.139468E+10 | 0.94 | 520.71 | 01-OCT-00:03 | 0.94 |
November | 0.134969E+10 | 0.94 | 520.71 | 01-NOV-00:10 | 0.94 |
December | 0.139468E+10 | 0.94 | 520.71 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.164212E+11 | 0.94 | |||
Minimum of Months | 0.125971E+10 | 0.93 | 520.71 | 0.93 | |
Maximum of Months | 0.139468E+10 | 0.94 | 520.71 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.315855E+09 | 0.284270E+09 | 2059.07 | 02-JAN-06:13 | 1853.17 | 1853.17 | 48.95 | 3.03 |
February | 99422799.34 | 89480519.40 | 1630.53 | 02-FEB-06:10 | 1467.48 | 1467.48 | 52.75 | 2.14 |
March | 39151.51 | 35236.36 | 19.46 | 01-MAR-05:20 | 17.51 | 17.51 | 28.90 | 0.02 |
April | 27.92 | 25.13 | 0.05 | 27-APR-11:00 | 0.04 | 0.04 | 28.54 | 0.00 |
May | 27.94 | 25.15 | 0.05 | 19-MAY-14:30 | 0.04 | 0.04 | 28.54 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 28.54 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 28.54 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 28.54 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 28.54 | 0.00 |
October | 2.16 | 1.94 | 0.02 | 09-OCT-07:52 | 0.02 | 0.02 | 28.54 | 0.00 |
November | 14321555.46 | 12889399.91 | 916.73 | 27-NOV-06:10 | 825.05 | 825.05 | 42.10 | 1.06 |
December | 0.179456E+09 | 0.161510E+09 | 1818.79 | 23-DEC-06:08 | 1636.91 | 1636.91 | 49.73 | 2.50 |
Annual Sum or Average | 0.609094E+09 | 0.548185E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 | |
Maximum of Months | 0.315855E+09 | 0.284270E+09 | 2059.07 | 1853.17 | 1853.17 | 52.75 | 3.03 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.727699E+10 | 0.654929E+10 | 17616.82 | 11-JAN-06:02 | 15855.13 | 15855.13 | 7.07 | 44.18 |
February | 0.100751E+11 | 0.906757E+10 | 19656.62 | 25-FEB-06:02 | 17690.96 | 17690.96 | 7.13 | 58.24 |
March | 0.184495E+11 | 0.166045E+11 | 21800.93 | 11-MAR-06:02 | 19620.83 | 19620.83 | 7.19 | 88.11 |
April | 0.241163E+11 | 0.217046E+11 | 22894.91 | 28-APR-05:02 | 20605.42 | 20605.42 | 7.61 | 102.43 |
May | 0.308353E+11 | 0.277518E+11 | 27096.38 | 24-MAY-05:03 | 24386.74 | 24386.74 | 7.43 | 127.90 |
June | 0.328075E+11 | 0.295268E+11 | 27853.01 | 27-JUN-05:03 | 25067.71 | 25067.71 | 7.20 | 130.75 |
July | 0.349199E+11 | 0.314279E+11 | 27869.02 | 03-JUL-05:02 | 25082.12 | 25082.12 | 7.37 | 130.82 |
August | 0.350528E+11 | 0.315475E+11 | 27869.02 | 02-AUG-05:03 | 25082.12 | 25082.12 | 7.25 | 130.82 |
September | 0.283786E+11 | 0.255407E+11 | 27869.02 | 16-SEP-05:03 | 25082.12 | 25082.12 | 7.84 | 130.82 |
October | 0.214139E+11 | 0.192725E+11 | 22929.74 | 04-OCT-05:03 | 20636.76 | 20636.76 | 7.33 | 102.79 |
November | 0.156204E+11 | 0.140583E+11 | 20338.93 | 09-NOV-06:03 | 18305.04 | 18305.04 | 7.02 | 65.42 |
December | 0.915140E+10 | 0.823626E+10 | 17599.84 | 04-DEC-14:10 | 15839.85 | 15839.85 | 7.21 | 44.09 |
Annual Sum or Average | 0.268098E+12 | 0.241288E+12 | ||||||
Minimum of Months | 0.727699E+10 | 0.654929E+10 | 17599.84 | 15839.85 | 15839.85 | 7.02 | 44.09 | |
Maximum of Months | 0.350528E+11 | 0.315475E+11 | 27869.02 | 25082.12 | 25082.12 | 7.84 | 130.82 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.280748E+11 | 0.252674E+11 | 18665.63 | 01-JAN-00:35 | 16799.07 | 16799.07 | 6.82 | 130.82 |
February | 0.279064E+11 | 0.251158E+11 | 18665.63 | 01-FEB-04:03 | 16799.07 | 16799.07 | 6.95 | 130.82 |
March | 0.380900E+11 | 0.342810E+11 | 18665.63 | 01-MAR-04:02 | 16799.07 | 16799.07 | 7.51 | 130.82 |
April | 0.449570E+11 | 0.404613E+11 | 18665.63 | 01-APR-00:03 | 16799.07 | 16799.07 | 6.87 | 130.82 |
May | 0.460473E+11 | 0.414426E+11 | 18665.63 | 01-MAY-00:03 | 16799.07 | 16799.07 | 9.05 | 130.82 |
June | 0.448257E+11 | 0.403431E+11 | 18665.63 | 01-JUN-00:12 | 16799.07 | 16799.07 | 7.10 | 130.82 |
July | 0.472953E+11 | 0.425658E+11 | 18665.63 | 01-JUL-00:03 | 16799.07 | 16799.07 | 9.58 | 130.82 |
August | 0.476852E+11 | 0.429167E+11 | 18665.63 | 01-AUG-00:03 | 16799.07 | 16799.07 | 7.50 | 130.82 |
September | 0.402984E+11 | 0.362685E+11 | 18665.63 | 01-SEP-00:03 | 16799.07 | 16799.07 | 7.25 | 130.82 |
October | 0.398080E+11 | 0.358272E+11 | 18665.63 | 01-OCT-00:42 | 16799.07 | 16799.07 | 8.04 | 130.82 |
November | 0.346621E+11 | 0.311959E+11 | 18665.63 | 01-NOV-03:02 | 16799.07 | 16799.07 | 9.30 | 130.82 |
December | 0.307014E+11 | 0.276313E+11 | 18665.63 | 01-DEC-04:02 | 16799.07 | 16799.07 | 7.32 | 130.82 |
Annual Sum or Average | 0.470352E+12 | 0.423317E+12 | ||||||
Minimum of Months | 0.279064E+11 | 0.251158E+11 | 18665.63 | 16799.07 | 16799.07 | 6.82 | 130.82 | |
Maximum of Months | 0.476852E+11 | 0.429167E+11 | 18665.63 | 16799.07 | 16799.07 | 9.58 | 130.82 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-JAN-00:10 | 3172.02 | 3172.02 | 21.73 | 14.72 |
February | 0.852639E+10 | 0.767375E+10 | 3524.47 | 01-FEB-00:10 | 3172.02 | 3172.02 | 24.24 | 14.72 |
March | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-MAR-00:10 | 3172.02 | 3172.02 | 28.60 | 14.72 |
April | 0.913541E+10 | 0.822187E+10 | 3524.47 | 01-APR-00:03 | 3172.02 | 3172.02 | 42.41 | 14.72 |
May | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-MAY-00:03 | 3172.02 | 3172.02 | 37.76 | 14.72 |
June | 0.913541E+10 | 0.822187E+10 | 3524.47 | 01-JUN-00:10 | 3172.02 | 3172.02 | 38.99 | 14.72 |
July | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-JUL-00:03 | 3172.02 | 3172.02 | 49.03 | 14.72 |
August | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-AUG-00:03 | 3172.02 | 3172.02 | 49.14 | 14.72 |
September | 0.913541E+10 | 0.822187E+10 | 3524.47 | 01-SEP-00:03 | 3172.02 | 3172.02 | 36.31 | 14.72 |
October | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-OCT-00:03 | 3172.02 | 3172.02 | 37.36 | 14.72 |
November | 0.913541E+10 | 0.822187E+10 | 3524.47 | 01-NOV-00:10 | 3172.02 | 3172.02 | 31.81 | 14.72 |
December | 0.943993E+10 | 0.849593E+10 | 3524.47 | 01-DEC-00:10 | 3172.02 | 3172.02 | 29.91 | 14.72 |
Annual Sum or Average | 0.111148E+12 | 0.100033E+12 | ||||||
Minimum of Months | 0.852639E+10 | 0.767375E+10 | 3524.47 | 3172.02 | 3172.02 | 21.73 | 14.72 | |
Maximum of Months | 0.943993E+10 | 0.849593E+10 | 3524.47 | 3172.02 | 3172.02 | 49.14 | 14.72 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.79 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.72 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.96 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.10 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.66 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.70 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 58.06 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.63 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.63 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.15 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.44 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.30 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.79 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.06 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.350255E+11 | 0.315229E+11 | 46279.59 | 12-JAN-14:40 | 41651.63 | 41651.63 | 22.74 | 153.99 |
February | 0.354817E+11 | 0.319335E+11 | 46369.97 | 23-FEB-16:30 | 41732.97 | 41732.97 | 25.39 | 153.99 |
March | 0.537936E+11 | 0.484143E+11 | 46413.35 | 10-MAR-17:00 | 41772.02 | 41772.02 | 26.51 | 153.99 |
April | 0.723822E+11 | 0.651440E+11 | 46503.09 | 17-APR-10:20 | 41852.78 | 41852.78 | 28.85 | 153.99 |
May | 0.855273E+11 | 0.769746E+11 | 46503.09 | 01-MAY-14:20 | 41852.78 | 41852.78 | 28.87 | 153.99 |
June | 0.931191E+11 | 0.838071E+11 | 46503.09 | 05-JUN-13:00 | 41852.78 | 41852.78 | 28.85 | 153.99 |
July | 0.103276E+12 | 0.929481E+11 | 46503.09 | 01-JUL-00:03 | 41852.78 | 41852.78 | 28.99 | 153.99 |
August | 0.102836E+12 | 0.925520E+11 | 46503.09 | 01-AUG-00:12 | 41852.78 | 41852.78 | 29.82 | 153.99 |
September | 0.845667E+11 | 0.761100E+11 | 46503.09 | 01-SEP-00:15 | 41852.78 | 41852.78 | 29.06 | 153.99 |
October | 0.636272E+11 | 0.572645E+11 | 46503.09 | 03-OCT-14:10 | 41852.78 | 41852.78 | 28.83 | 153.99 |
November | 0.466098E+11 | 0.419488E+11 | 46379.15 | 01-NOV-14:00 | 41741.23 | 41741.23 | 25.63 | 153.99 |
December | 0.388386E+11 | 0.349548E+11 | 46283.22 | 28-DEC-15:00 | 41654.90 | 41654.90 | 22.85 | 153.99 |
Annual Sum or Average | 0.815083E+12 | 0.733575E+12 | ||||||
Minimum of Months | 0.350255E+11 | 0.315229E+11 | 46279.59 | 41651.63 | 41651.63 | 22.74 | 153.99 | |
Maximum of Months | 0.103276E+12 | 0.929481E+11 | 46503.09 | 41852.78 | 41852.78 | 29.82 | 153.99 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 82.00 | 82.00 | 21359.63 | 425968.22 | 02-JAN-06:04 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 37.38 | 37.38 | 7595.41 | 327458.38 | 04-FEB-06:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.08 | 29.08 | 3.31 | 4406.44 | 01-MAR-05:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 28.54 | 28.54 | 0.00 | 10.59 | 27-APR-11:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.54 | 28.54 | 0.00 | 10.59 | 19-MAY-14:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.54 | 28.54 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 28.54 | 28.54 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.54 | 28.54 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.54 | 28.54 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.54 | 28.54 | 0.00 | 4.09 | 09-OCT-07:52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.54 | 28.54 | 1133.24 | 175983.11 | 27-NOV-06:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 35.70 | 35.70 | 12655.32 | 337490.72 | 23-DEC-06:08 |
Annual Sum or Average | 0.00 | 3565.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.54 | 28.54 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 21359.63 | 425968.22 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 326796.58 | 1594393.57 | 25-JAN-14:30 | 9.61 | 8.03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 471380.99 | 1692677.54 | 16-FEB-15:30 | 9.79 | 8.11 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 755073.60 | 2375721.52 | 30-MAR-05:04 | 11.03 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1074489.19 | 3310459.50 | 17-APR-05:03 | 12.74 | 7.06 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1403433.97 | 3423300.94 | 31-MAY-05:03 | 12.95 | 7.27 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1616665.58 | 5924845.90 | 23-JUN-16:00 | 17.53 | 11.84 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1697116.96 | 4141467.93 | 19-JUL-05:03 | 14.26 | 8.58 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1733015.25 | 6044047.92 | 28-AUG-16:00 | 17.75 | 12.06 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1340399.67 | 4362550.10 | 05-SEP-05:05 | 14.67 | 8.98 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 926644.25 | 2765690.79 | 04-OCT-05:03 | 11.75 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 630086.36 | 1916715.66 | 21-NOV-15:00 | 10.20 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 391503.52 | 1674535.34 | 28-DEC-15:00 | 9.75 | 8.11 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1033668.49 | 0.00 | ||||||
Minimum of Months | 326796.58 | 1594393.57 | 9.61 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1733015.25 | 6044047.92 | 17.75 | 12.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174636.32 | 1297987.32 | 18-JAN-06:02 | 14.97 | 7.17 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 296000.85 | 2179854.72 | 25-FEB-06:02 | 15.65 | 7.61 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 552323.58 | 3403329.89 | 11-MAR-06:02 | 15.93 | 6.73 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 866724.57 | 4104532.92 | 17-APR-05:02 | 16.36 | 6.83 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1233895.00 | 5076598.34 | 24-MAY-05:03 | 16.19 | 7.07 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1514469.01 | 5892700.15 | 23-JUN-16:00 | 17.55 | 11.83 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1624922.87 | 5648238.95 | 03-JUL-05:02 | 17.02 | 7.36 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1659919.61 | 6032962.43 | 28-AUG-16:00 | 17.72 | 12.04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1275509.92 | 5652573.75 | 16-SEP-03:02 | 17.06 | 7.88 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 735458.53 | 4111542.64 | 04-OCT-05:03 | 16.26 | 6.84 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 450921.19 | 2425180.87 | 09-NOV-06:03 | 15.56 | 7.58 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 219993.77 | 1343700.83 | 01-DEC-16:10 | 14.60 | 7.83 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 886992.89 | 0.00 | ||||||
Minimum of Months | 174636.32 | 1297987.32 | 14.60 | 6.73 | 0.00 | 0.00 | ||
Maximum of Months | 1659919.61 | 6032962.43 | 17.72 | 12.04 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222595.95 | 585712.30 | 12-JAN-15:00 | 29.70 | 25.60 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 499379.25 | 1020372.93 | 22-FEB-15:00 | 37.98 | 30.71 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 967619.89 | 1766089.35 | 28-MAR-15:20 | 51.89 | 41.06 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1589845.92 | 2227924.21 | 15-APR-15:00 | 60.34 | 47.10 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1121975.88 | 1783451.98 | 01-MAY-15:00 | 52.21 | 46.90 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1414857.64 | 2070632.17 | 08-JUN-16:00 | 57.48 | 48.96 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1557954.26 | 2093254.35 | 07-JUL-15:00 | 57.89 | 46.32 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1671856.78 | 2090186.25 | 07-AUG-15:00 | 57.83 | 44.25 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 901322.35 | 1397927.86 | 17-SEP-20:00 | 45.07 | 40.03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 906795.39 | 1580576.33 | 02-OCT-15:00 | 48.46 | 40.44 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 822232.14 | 1428648.64 | 08-NOV-15:00 | 45.64 | 35.16 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 788623.96 | 1326856.81 | 28-DEC-14:20 | 43.74 | 30.96 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1041617.66 | 0.00 | ||||||
Minimum of Months | 222595.95 | 585712.30 | 29.70 | 25.60 | 0.00 | 0.00 | ||
Maximum of Months | 1671856.78 | 2227924.21 | 60.34 | 48.96 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.69 | 56.69 | 12725.85 | 41927.31 | 17-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.23 | 57.23 | 12554.37 | 41679.43 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.51 | 56.51 | 12446.63 | 39940.62 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.48 | 57.48 | 10694.98 | 36276.05 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.05 | 57.05 | 9895.27 | 32609.59 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.99 | 57.99 | 9206.65 | 28990.28 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.31 | 58.31 | 8254.27 | 26816.34 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.51 | 58.51 | 9167.18 | 28562.54 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.91 | 56.91 | 9455.76 | 31750.99 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.69 | 57.69 | 10502.47 | 35895.01 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.91 | 56.91 | 11719.15 | 39406.23 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.96 | 56.96 | 12135.10 | 41504.85 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 10719.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.51 | 56.51 | 8254.27 | 26816.34 | ||
Maximum of Months | 0.00 | 0.00 | 58.51 | 58.51 | 12725.85 | 41927.31 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 194487.25 | 1128182.40 | 25-JAN-15:50 | 24.61 | 21.10 | 2612.15 | 118774.05 | 07-JAN-06:00 |
February | 316978.46 | 2761642.37 | 23-FEB-16:30 | 25.39 | 21.10 | 930.10 | 74285.16 | 03-FEB-07:00 |
March | 638017.81 | 3479641.97 | 10-MAR-17:00 | 26.51 | 23.36 | 104.96 | 51344.51 | 20-MAR-03:00 |
April | 1255300.56 | 5877172.55 | 18-APR-14:00 | 30.23 | 25.96 | 14.23 | 13348.43 | 09-APR-22:55 |
May | 2733730.63 | 7868817.05 | 17-MAY-15:30 | 33.32 | 28.26 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 4288248.87 | 8980594.72 | 21-JUN-13:50 | 35.05 | 29.37 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 5505281.37 | 8983059.08 | 17-JUL-11:00 | 35.06 | 29.37 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 5469505.94 | 8983692.66 | 24-AUG-14:40 | 35.06 | 29.37 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3886665.11 | 8876696.42 | 14-SEP-16:00 | 34.89 | 29.32 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1084430.22 | 5436596.23 | 04-OCT-12:20 | 29.55 | 25.41 | 1.70 | 8507.61 | 30-OCT-02:15 |
November | 499907.61 | 2913681.27 | 01-NOV-14:00 | 25.63 | 21.10 | 268.78 | 50869.25 | 22-NOV-04:30 |
December | 237968.23 | 1252551.63 | 01-DEC-16:10 | 24.99 | 21.10 | 1804.68 | 108634.60 | 21-DEC-08:00 |
Annual Sum or Average | 2187794.87 | 478.80 | ||||||
Minimum of Months | 194487.25 | 1128182.40 | 24.61 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 5505281.37 | 8983692.66 | 35.06 | 29.37 | 2612.15 | 118774.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.295300E+10 | 0.00 | 0.430529E+11 | 0.670227E+10 | 0.00 | 0.00 |
February | 0.749852E+09 | 0.00 | 0.640763E+11 | 0.773403E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.127796E+12 | 0.120468E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.201841E+12 | 0.148063E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.265645E+12 | 0.143362E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.326590E+12 | 0.153031E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.392101E+12 | 0.154211E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.421781E+12 | 0.189735E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.284652E+12 | 0.118364E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.167162E+12 | 0.112935E+11 | 0.00 | 0.00 |
November | 0.113678E+09 | 0.00 | 0.101684E+12 | 0.996587E+10 | 0.00 | 0.00 |
December | 0.134704E+10 | 0.00 | 0.629009E+11 | 0.915728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.516357E+10 | 0.00 | 0.245928E+13 | 0.147576E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.430529E+11 | 0.670227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.295300E+10 | 0.00 | 0.421781E+12 | 0.189735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.452356E+11 | 0.00 | 0.292614E+12 | 0.482396E+11 | 0.00 | 0.00 |
February | 0.153215E+11 | 0.00 | 0.465179E+12 | 0.538171E+11 | 0.00 | 0.00 |
March | 7779879.74 | 0.00 | 0.100068E+13 | 0.861837E+11 | 0.00 | 0.00 |
April | 8105.38 | 0.00 | 0.160852E+13 | 0.106568E+12 | 0.00 | 0.00 |
May | 8127.70 | 0.00 | 0.249288E+13 | 0.124707E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.296692E+13 | 0.123571E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.338482E+13 | 0.111965E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.336888E+13 | 0.117353E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.253262E+13 | 0.971509E+11 | 0.00 | 0.00 |
October | 618.31 | 0.00 | 0.139517E+13 | 0.848719E+11 | 0.00 | 0.00 |
November | 0.249445E+10 | 0.00 | 0.758642E+12 | 0.661801E+11 | 0.00 | 0.00 |
December | 0.278724E+11 | 0.00 | 0.360288E+12 | 0.519937E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.909317E+11 | 0.00 | 0.206272E+14 | 0.107260E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.292614E+12 | 0.482396E+11 | 0.00 | 0.00 |
Maximum of Months | 0.452356E+11 | 0.00 | 0.338482E+13 | 0.124707E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.972683E+10 | 0.00 | 0.208903E+11 | 0.362669E+10 | 0.00 | 0.00 |
February | 0.251025E+10 | 0.00 | 0.418387E+11 | 0.433809E+10 | 0.00 | 0.00 |
March | 2850209.49 | 0.00 | 0.102997E+12 | 0.810283E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.179099E+12 | 0.117565E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.280010E+12 | 0.145699E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.330319E+12 | 0.145692E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.370140E+12 | 0.125434E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.361733E+12 | 0.125279E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.270393E+12 | 0.100990E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.143907E+12 | 0.852167E+10 | 0.00 | 0.00 |
November | 0.334743E+09 | 0.00 | 0.716544E+11 | 0.583016E+10 | 0.00 | 0.00 |
December | 0.504029E+10 | 0.00 | 0.274376E+11 | 0.386228E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.176150E+11 | 0.00 | 0.220042E+13 | 0.110348E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.208903E+11 | 0.362669E+10 | 0.00 | 0.00 |
Maximum of Months | 0.972683E+10 | 0.00 | 0.370140E+12 | 0.145699E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.572262E+11 | 0.181207E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.584359E+11 | 0.160415E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.800910E+11 | 0.182307E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.914767E+11 | 0.169505E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.117337E+12 | 0.183054E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137207E+12 | 0.183301E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.158194E+12 | 0.190274E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.176498E+12 | 0.201872E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.140816E+12 | 0.189432E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.103132E+12 | 0.195132E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.801098E+11 | 0.187761E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.648993E+11 | 0.186310E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126542E+13 | 0.221057E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.572262E+11 | 0.160415E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.176498E+12 | 0.201872E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.426422E+12 | 0.196765E+12 | 0.00 | 4.47 |
February | 0.00 | 0.00 | 0.676038E+12 | 0.242766E+12 | 0.00 | 4.88 |
March | 0.00 | 0.00 | 0.109167E+13 | 0.358543E+12 | 0.00 | 2.53 |
April | 0.00 | 0.00 | 0.140544E+13 | 0.464997E+12 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.512411E+12 | 0.246020E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.845360E+12 | 0.339853E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.121470E+13 | 0.436894E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149282E+13 | 0.489206E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.500009E+12 | 0.226502E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.800924E+12 | 0.296476E+12 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.104867E+13 | 0.337699E+12 | 0.00 | 5.09 |
December | 0.00 | 0.00 | 0.137056E+13 | 0.401967E+12 | 0.00 | 12.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.113850E+14 | 0.403769E+13 | 0.00 | 30.65 |
Minimum of Months | 0.00 | 0.00 | 0.426422E+12 | 0.196765E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149282E+13 | 0.489206E+12 | 0.00 | 12.84 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.626693E+10 | 0.275210E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121176E+11 | 0.384581E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210730E+11 | 0.630180E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.283798E+11 | 0.886785E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100590E+11 | 0.430510E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.171713E+11 | 0.625977E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.249311E+11 | 0.822224E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.309247E+11 | 0.953302E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.987556E+10 | 0.393274E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.154586E+11 | 0.520154E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198931E+11 | 0.572763E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.255864E+11 | 0.649546E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221737E+12 | 0.714450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.626693E+10 | 0.275210E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.309247E+11 | 0.953302E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.477221E+11 | 0.238874E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108137E+12 | 0.352566E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198900E+12 | 0.596739E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.269602E+12 | 0.843182E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.950808E+11 | 0.407936E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.163741E+12 | 0.596340E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.238057E+12 | 0.783985E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.293842E+12 | 0.907374E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.928745E+11 | 0.371336E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145573E+12 | 0.491722E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184720E+12 | 0.536589E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.233819E+12 | 0.601783E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207207E+13 | 0.672842E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.477221E+11 | 0.238874E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.293842E+12 | 0.907374E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.299136E+10 | 0.204413E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.100003E+11 | 0.339084E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197303E+11 | 0.597410E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.272504E+11 | 0.856133E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.986505E+10 | 0.419882E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167209E+11 | 0.608902E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.241600E+11 | 0.797450E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.299208E+11 | 0.927439E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.941264E+10 | 0.376387E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144988E+11 | 0.493529E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179128E+11 | 0.529346E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.220191E+11 | 0.581600E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204482E+12 | 0.673157E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.299136E+10 | 0.204413E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.299208E+11 | 0.927439E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.670227E+10 | 0.430529E+11 | 0.295300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773403E+10 | 0.640763E+11 | 0.749852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120468E+11 | 0.127796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148063E+11 | 0.201841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143362E+11 | 0.265645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153031E+11 | 0.326590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154211E+11 | 0.392101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189735E+11 | 0.421781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118364E+11 | 0.284652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112935E+11 | 0.167162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.996587E+10 | 0.101684E+12 | 0.113678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915728E+10 | 0.629009E+11 | 0.134704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147576E+12 | 0.245928E+13 | 0.516357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670227E+10 | 0.430529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189735E+11 | 0.421781E+12 | 0.295300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.482396E+11 | 0.292614E+12 | 0.452356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538171E+11 | 0.465179E+12 | 0.153215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861837E+11 | 0.100068E+13 | 7779879.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106568E+12 | 0.160852E+13 | 8105.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124707E+12 | 0.249288E+13 | 8127.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123571E+12 | 0.296692E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111965E+12 | 0.338482E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117353E+12 | 0.336888E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.971509E+11 | 0.253262E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848719E+11 | 0.139517E+13 | 618.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661801E+11 | 0.758642E+12 | 0.249445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.519937E+11 | 0.360288E+12 | 0.278724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107260E+13 | 0.206272E+14 | 0.909317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.482396E+11 | 0.292614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124707E+12 | 0.338482E+13 | 0.452356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.362669E+10 | 0.208903E+11 | 0.972683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433809E+10 | 0.418387E+11 | 0.251025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810283E+10 | 0.102997E+12 | 2850209.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117565E+11 | 0.179099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145699E+11 | 0.280010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145692E+11 | 0.330319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125434E+11 | 0.370140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125279E+11 | 0.361733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100990E+11 | 0.270393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852167E+10 | 0.143907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.583016E+10 | 0.716544E+11 | 0.334743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386228E+10 | 0.274376E+11 | 0.504029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110348E+12 | 0.220042E+13 | 0.176150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.362669E+10 | 0.208903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145699E+11 | 0.370140E+12 | 0.972683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.181207E+11 | 0.572262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160415E+11 | 0.584359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182307E+11 | 0.800910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169505E+11 | 0.914767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183054E+11 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.183301E+11 | 0.137207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190274E+11 | 0.158194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201872E+11 | 0.176498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189432E+11 | 0.140816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195132E+11 | 0.103132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187761E+11 | 0.801098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186310E+11 | 0.648993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221057E+12 | 0.126542E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160415E+11 | 0.572262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201872E+11 | 0.176498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.970099E+11 | 0.338674E+12 | 0.00 | 0.00 | 0.00 | 0.119541E+11 | 0.00 | 0.00 |
February | 0.876218E+11 | 0.533999E+12 | 0.00 | 0.00 | 0.00 | 0.130467E+11 | 0.00 | 0.00 |
March | 0.970099E+11 | 0.836927E+12 | 0.00 | 0.00 | 0.00 | 0.675777E+10 | 0.00 | 0.00 |
April | 0.938805E+11 | 0.103526E+13 | 0.00 | 0.00 | 0.00 | 0.935117E+09 | 0.00 | 0.00 |
May | 0.970099E+11 | 0.363416E+12 | 0.00 | 0.00 | 0.00 | 15344226.73 | 0.00 | 0.00 |
June | 0.938805E+11 | 0.599388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970099E+11 | 0.874812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970099E+11 | 0.110063E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938805E+11 | 0.367387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.970099E+11 | 0.602783E+12 | 0.00 | 0.00 | 0.00 | 0.131899E+10 | 0.00 | 0.00 |
November | 0.938805E+11 | 0.818526E+12 | 0.00 | 0.00 | 0.00 | 0.136185E+11 | 0.00 | 0.00 |
December | 0.970099E+11 | 0.110013E+13 | 0.00 | 0.00 | 0.00 | 0.343680E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.114221E+13 | 0.857192E+13 | 0.00 | 0.00 | 0.00 | 0.820146E+11 | 0.00 | 0.00 |
Minimum of Months | 0.876218E+11 | 0.338674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970099E+11 | 0.110063E+13 | 0.00 | 0.00 | 0.00 | 0.343680E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145638E+10 | 0.497121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131544E+10 | 0.958723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145638E+10 | 0.162276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140940E+10 | 0.209214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145638E+10 | 0.721026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140940E+10 | 0.123209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145638E+10 | 0.181653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145638E+10 | 0.228481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140940E+10 | 0.735223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145638E+10 | 0.117135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140940E+10 | 0.155748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145638E+10 | 0.205473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171478E+11 | 0.167440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131544E+10 | 0.497121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145638E+10 | 0.228481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138657E+11 | 0.377004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125239E+11 | 0.854044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138657E+11 | 0.153092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134184E+11 | 0.198702E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138657E+11 | 0.681529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134184E+11 | 0.117526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138657E+11 | 0.173524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138657E+11 | 0.216971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134184E+11 | 0.691594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138657E+11 | 0.110266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134184E+11 | 0.144479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138657E+11 | 0.187507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163258E+12 | 0.156248E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125239E+11 | 0.377004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138657E+11 | 0.216971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139468E+10 | 0.234191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125971E+10 | 0.786922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139468E+10 | 0.151508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134969E+10 | 0.200388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139468E+10 | 0.706091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134969E+10 | 0.119815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139468E+10 | 0.175802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139468E+10 | 0.220411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134969E+10 | 0.699846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139468E+10 | 0.109582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134969E+10 | 0.139690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139468E+10 | 0.175978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164212E+11 | 0.153588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125971E+10 | 0.234191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139468E+10 | 0.220411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.670227E+10 | 0.295300E+10 | 0.430529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773403E+10 | 0.749852E+09 | 0.640763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120468E+11 | 0.00 | 0.127796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148063E+11 | 0.00 | 0.201841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143362E+11 | 0.00 | 0.265645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153031E+11 | 0.00 | 0.326590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154211E+11 | 0.00 | 0.392101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189735E+11 | 0.00 | 0.421781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118364E+11 | 0.00 | 0.284652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112935E+11 | 0.00 | 0.167162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.996587E+10 | 0.113678E+09 | 0.101684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915728E+10 | 0.134704E+10 | 0.629009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147576E+12 | 0.516357E+10 | 0.245928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670227E+10 | 0.00 | 0.430529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189735E+11 | 0.295300E+10 | 0.421781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.482396E+11 | 0.452356E+11 | 0.292614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538171E+11 | 0.153215E+11 | 0.465179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861837E+11 | 7779879.74 | 0.100068E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106568E+12 | 8105.38 | 0.160852E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124707E+12 | 8127.70 | 0.249288E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123571E+12 | 0.00 | 0.296692E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111965E+12 | 0.00 | 0.338482E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117353E+12 | 0.00 | 0.336888E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.971509E+11 | 0.00 | 0.253262E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848719E+11 | 618.31 | 0.139517E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661801E+11 | 0.249445E+10 | 0.758642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.519937E+11 | 0.278724E+11 | 0.360288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107260E+13 | 0.909317E+11 | 0.206272E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.482396E+11 | 0.00 | 0.292614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124707E+12 | 0.452356E+11 | 0.338482E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.362669E+10 | 0.972683E+10 | 0.208903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433809E+10 | 0.251025E+10 | 0.418387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810283E+10 | 2850209.49 | 0.102997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117565E+11 | 0.00 | 0.179099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145699E+11 | 0.00 | 0.280010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145692E+11 | 0.00 | 0.330319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125434E+11 | 0.00 | 0.370140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125279E+11 | 0.00 | 0.361733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100990E+11 | 0.00 | 0.270393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852167E+10 | 0.00 | 0.143907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.583016E+10 | 0.334743E+09 | 0.716544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386228E+10 | 0.504029E+10 | 0.274376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110348E+12 | 0.176150E+11 | 0.220042E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.362669E+10 | 0.00 | 0.208903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145699E+11 | 0.972683E+10 | 0.370140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.181207E+11 | 0.00 | 0.572262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160415E+11 | 0.00 | 0.584359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182307E+11 | 0.00 | 0.800910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169505E+11 | 0.00 | 0.914767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183054E+11 | 0.00 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.183301E+11 | 0.00 | 0.137207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190274E+11 | 0.00 | 0.158194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201872E+11 | 0.00 | 0.176498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189432E+11 | 0.00 | 0.140816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195132E+11 | 0.00 | 0.103132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187761E+11 | 0.00 | 0.801098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186310E+11 | 0.00 | 0.648993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221057E+12 | 0.00 | 0.126542E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160415E+11 | 0.00 | 0.572262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201872E+11 | 0.00 | 0.176498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.970099E+11 | 0.00 | 0.426422E+12 | 0.00 | 0.877475E+11 | 0.00 | 0.00 | 0.00 | 0.120079E+11 | 0.00 | 0.00 | 0.00 |
February | 0.876218E+11 | 0.00 | 0.676038E+12 | 0.00 | 0.142039E+12 | 0.00 | 0.00 | 0.00 | 0.131055E+11 | 0.00 | 0.00 | 0.00 |
March | 0.970099E+11 | 0.00 | 0.109167E+13 | 0.00 | 0.254745E+12 | 0.00 | 0.00 | 0.00 | 0.678818E+10 | 0.00 | 0.00 | 0.00 |
April | 0.938805E+11 | 0.00 | 0.140544E+13 | 0.00 | 0.370178E+12 | 0.00 | 0.00 | 0.00 | 0.939327E+09 | 0.00 | 0.00 | 0.00 |
May | 0.970099E+11 | 0.00 | 0.512411E+12 | 0.00 | 0.148995E+12 | 0.00 | 0.00 | 0.00 | 15413297.32 | 0.00 | 0.00 | 0.00 |
June | 0.938805E+11 | 0.00 | 0.845360E+12 | 0.00 | 0.245972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.970099E+11 | 0.00 | 0.121470E+13 | 0.00 | 0.339884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970099E+11 | 0.00 | 0.149282E+13 | 0.00 | 0.392197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938805E+11 | 0.00 | 0.500009E+12 | 0.00 | 0.132622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.970099E+11 | 0.00 | 0.800924E+12 | 0.00 | 0.198141E+12 | 0.00 | 0.00 | 0.00 | 0.132493E+10 | 0.00 | 0.00 | 0.00 |
November | 0.938805E+11 | 0.00 | 0.104867E+13 | 0.00 | 0.230139E+12 | 0.00 | 0.00 | 0.00 | 0.136799E+11 | 0.00 | 0.00 | 0.00 |
December | 0.970099E+11 | 0.00 | 0.137056E+13 | 0.00 | 0.270435E+12 | 0.00 | 0.00 | 0.00 | 0.345227E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114221E+13 | 0.00 | 0.113850E+14 | 0.00 | 0.281309E+13 | 0.00 | 0.00 | 0.00 | 0.823838E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.876218E+11 | 0.00 | 0.426422E+12 | 0.00 | 0.877475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970099E+11 | 0.00 | 0.149282E+13 | 0.00 | 0.392197E+12 | 0.00 | 0.00 | 0.00 | 0.345227E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145638E+10 | 0.00 | 0.626693E+10 | 0.00 | 0.129571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131544E+10 | 0.00 | 0.121176E+11 | 0.00 | 0.253037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145638E+10 | 0.00 | 0.210730E+11 | 0.00 | 0.484542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140940E+10 | 0.00 | 0.283798E+11 | 0.00 | 0.745845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145638E+10 | 0.00 | 0.100590E+11 | 0.00 | 0.284871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140940E+10 | 0.00 | 0.171713E+11 | 0.00 | 0.485036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145638E+10 | 0.00 | 0.249311E+11 | 0.00 | 0.676586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145638E+10 | 0.00 | 0.309247E+11 | 0.00 | 0.807663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140940E+10 | 0.00 | 0.987556E+10 | 0.00 | 0.252334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145638E+10 | 0.00 | 0.154586E+11 | 0.00 | 0.374515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140940E+10 | 0.00 | 0.198931E+11 | 0.00 | 0.431822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145638E+10 | 0.00 | 0.255864E+11 | 0.00 | 0.503908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171478E+11 | 0.00 | 0.221737E+12 | 0.00 | 0.542973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131544E+10 | 0.00 | 0.626693E+10 | 0.00 | 0.129571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145638E+10 | 0.00 | 0.309247E+11 | 0.00 | 0.807663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138657E+11 | 0.00 | 0.477221E+11 | 0.00 | 0.100216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125239E+11 | 0.00 | 0.108137E+12 | 0.00 | 0.227327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138657E+11 | 0.00 | 0.198900E+12 | 0.00 | 0.458082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134184E+11 | 0.00 | 0.269602E+12 | 0.00 | 0.708997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138657E+11 | 0.00 | 0.950808E+11 | 0.00 | 0.269279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134184E+11 | 0.00 | 0.163741E+12 | 0.00 | 0.462156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138657E+11 | 0.00 | 0.238057E+12 | 0.00 | 0.645328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138657E+11 | 0.00 | 0.293842E+12 | 0.00 | 0.768717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134184E+11 | 0.00 | 0.928745E+11 | 0.00 | 0.237151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138657E+11 | 0.00 | 0.145573E+12 | 0.00 | 0.353065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134184E+11 | 0.00 | 0.184720E+12 | 0.00 | 0.402404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138657E+11 | 0.00 | 0.233819E+12 | 0.00 | 0.463125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163258E+12 | 0.00 | 0.207207E+13 | 0.00 | 0.509585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125239E+11 | 0.00 | 0.477221E+11 | 0.00 | 0.100216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138657E+11 | 0.00 | 0.293842E+12 | 0.00 | 0.768717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139468E+10 | 0.00 | 0.299136E+10 | 0.00 | 0.649448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125971E+10 | 0.00 | 0.100003E+11 | 0.00 | 0.213113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139468E+10 | 0.00 | 0.197303E+11 | 0.00 | 0.457942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134969E+10 | 0.00 | 0.272504E+11 | 0.00 | 0.721164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139468E+10 | 0.00 | 0.986505E+10 | 0.00 | 0.280414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134969E+10 | 0.00 | 0.167209E+11 | 0.00 | 0.473933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139468E+10 | 0.00 | 0.241600E+11 | 0.00 | 0.657982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139468E+10 | 0.00 | 0.299208E+11 | 0.00 | 0.787971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134969E+10 | 0.00 | 0.941264E+10 | 0.00 | 0.241418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139468E+10 | 0.00 | 0.144988E+11 | 0.00 | 0.354061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134969E+10 | 0.00 | 0.179128E+11 | 0.00 | 0.394377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139468E+10 | 0.00 | 0.220191E+11 | 0.00 | 0.442132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164212E+11 | 0.00 | 0.204482E+12 | 0.00 | 0.508945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125971E+10 | 0.00 | 0.299136E+10 | 0.00 | 0.649448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139468E+10 | 0.00 | 0.299208E+11 | 0.00 | 0.787971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279318E+10 | 0.00 | 0.00 | 0.123162E+09 | 0.00 | 0.00 | 0.258976E+11 | 0.00 | 0.40 |
February | 0.917755E+09 | 0.00 | 0.00 | 0.112286E+09 | 0.00 | 0.00 | 0.168242E+11 | 0.00 | 0.39 |
March | 0.404255E+09 | 0.154376E+10 | 0.00 | 0.101741E+09 | 26989587.81 | 0.00 | 0.856228E+10 | 0.00 | 0.41 |
April | 20016549.12 | 0.107995E+11 | 0.00 | 23399939.38 | 0.273154E+09 | 0.00 | 0.531157E+09 | 0.00 | 0.39 |
May | 8189786.93 | 0.305269E+11 | 0.00 | 2957202.11 | 0.543910E+09 | 0.00 | 63835226.27 | 0.00 | 0.41 |
June | 0.00 | 0.472488E+11 | 0.00 | 184959.73 | 0.818961E+09 | 0.00 | 289045.08 | 0.00 | 0.43 |
July | 0.00 | 0.645556E+11 | 0.00 | 0.00 | 0.155342E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.716386E+11 | 0.00 | 0.00 | 0.118216E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.474382E+11 | 0.00 | 0.00 | 0.977316E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.197728E+09 | 0.910867E+10 | 0.00 | 65171859.37 | 0.145035E+09 | 0.00 | 0.285105E+10 | 0.00 | 0.44 |
November | 0.968761E+09 | 0.249581E+09 | 0.00 | 0.145008E+09 | 20797513.53 | 0.00 | 0.132120E+11 | 0.00 | 0.43 |
December | 0.207601E+10 | 0.00 | 0.00 | 0.137288E+09 | 0.00 | 0.00 | 0.243015E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.738590E+10 | 0.283110E+12 | 0.00 | 0.711198E+09 | 0.554174E+10 | 0.00 | 0.922439E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.279318E+10 | 0.716386E+11 | 0.00 | 0.145008E+09 | 0.155342E+10 | 0.00 | 0.258976E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277826E+10 | 0.00 | 0.00 | 86859433.31 | 0.00 | 0.00 | 0.319880E+11 | 0.00 | 0.51 |
February | 0.271828E+10 | 0.00 | 0.00 | 87301045.61 | 9287006.80 | 0.00 | 0.207439E+11 | 0.00 | 0.55 |
March | 0.317113E+10 | 0.242357E+10 | 0.00 | 81420940.37 | 0.547319E+09 | 0.00 | 0.108153E+11 | 0.00 | 0.63 |
April | 0.909783E+09 | 0.130052E+11 | 0.00 | 17867513.57 | 0.589406E+10 | 0.00 | 0.110325E+10 | 0.00 | 0.70 |
May | 23666670.94 | 0.386901E+11 | 0.00 | 746072.14 | 0.148104E+11 | 0.00 | 12608432.50 | 0.00 | 0.66 |
June | 0.00 | 0.582786E+11 | 0.00 | 0.00 | 0.269194E+11 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.750363E+11 | 0.00 | 0.00 | 0.463765E+11 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.868824E+11 | 0.00 | 0.00 | 0.423621E+11 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.588649E+11 | 0.00 | 0.00 | 0.220538E+11 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.120573E+10 | 0.130048E+11 | 0.00 | 30245501.98 | 0.280151E+10 | 0.00 | 0.317565E+10 | 0.00 | 0.62 |
November | 0.340892E+10 | 0.462764E+09 | 0.00 | 95095673.25 | 0.167146E+09 | 0.00 | 0.154261E+11 | 0.00 | 0.59 |
December | 0.416429E+10 | 0.00 | 0.00 | 0.103414E+09 | 0.00 | 0.00 | 0.300435E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.183801E+11 | 0.346649E+12 | 0.00 | 0.502950E+09 | 0.161942E+12 | 0.00 | 0.113308E+12 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.416429E+10 | 0.868824E+11 | 0.00 | 0.103414E+09 | 0.463765E+11 | 0.00 | 0.319880E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296555E+11 | 0.00 | 0.00 | 0.582580E+09 | 0.00 | 0.00 | 0.266939E+12 | 0.00 | 0.48 |
February | 0.161619E+11 | 8200073.65 | 0.00 | 0.635551E+09 | 0.287143E+09 | 0.00 | 0.183006E+12 | 0.00 | 0.51 |
March | 0.143850E+11 | 0.257436E+11 | 0.00 | 0.664996E+09 | 0.504788E+10 | 0.00 | 0.992333E+11 | 0.00 | 0.56 |
April | 0.281090E+10 | 0.126779E+12 | 0.00 | 0.138023E+09 | 0.470644E+11 | 0.00 | 0.937872E+10 | 0.00 | 0.59 |
May | 0.239470E+09 | 0.383958E+12 | 0.00 | 4757911.01 | 0.132990E+12 | 0.00 | 0.108607E+09 | 0.00 | 0.64 |
June | 0.00 | 0.572800E+12 | 0.00 | 0.00 | 0.217942E+12 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 0.00 | 0.723751E+12 | 0.00 | 0.00 | 0.332700E+12 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.833477E+12 | 0.00 | 0.00 | 0.243857E+12 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.588813E+12 | 0.00 | 0.00 | 0.140883E+12 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.763437E+10 | 0.129297E+12 | 0.00 | 0.233433E+09 | 0.207725E+11 | 0.00 | 0.283873E+11 | 0.00 | 0.56 |
November | 0.211170E+11 | 0.513892E+10 | 0.00 | 0.667442E+09 | 0.178288E+10 | 0.00 | 0.127974E+12 | 0.00 | 0.53 |
December | 0.261192E+11 | 0.00 | 0.00 | 0.620583E+09 | 59389401.02 | 0.00 | 0.243913E+12 | 0.00 | 0.49 |
Annual Sum or Average | 0.118123E+12 | 0.338977E+13 | 0.00 | 0.354737E+10 | 0.114339E+13 | 0.00 | 0.958940E+12 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.296555E+11 | 0.833477E+12 | 0.00 | 0.667442E+09 | 0.332700E+12 | 0.00 | 0.266939E+12 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139570E+11 | 0.00 | 0.00 | 21569139.02 | 0.00 | 0.348805E+09 | 0.919049E+10 | 0.00 | 0.43 |
February | 0.554786E+10 | 0.00 | 0.00 | 39200826.71 | 9754949.63 | 0.00 | 0.103245E+11 | 0.00 | 0.46 |
March | 0.118178E+10 | 0.198265E+10 | 0.00 | 58703670.15 | 0.329057E+09 | 0.00 | 0.828851E+10 | 0.00 | 0.53 |
April | 0.241595E+09 | 0.116481E+11 | 0.00 | 14507495.56 | 0.413099E+10 | 0.00 | 0.736020E+09 | 0.00 | 0.60 |
May | 15892714.41 | 0.383533E+11 | 0.00 | 363317.20 | 0.123067E+11 | 0.00 | 6858894.53 | 0.00 | 0.66 |
June | 0.00 | 0.583130E+11 | 0.00 | 0.00 | 0.209688E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.743523E+11 | 0.00 | 0.00 | 0.324596E+11 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.845027E+11 | 0.00 | 0.00 | 0.239669E+11 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.583086E+11 | 0.00 | 0.00 | 0.148770E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.472243E+09 | 0.116029E+11 | 0.00 | 19220942.34 | 0.168904E+10 | 0.00 | 0.214880E+10 | 0.00 | 0.54 |
November | 0.302943E+10 | 0.223548E+09 | 0.00 | 51129703.67 | 0.140579E+09 | 0.00 | 0.819207E+10 | 0.00 | 0.48 |
December | 0.103199E+11 | 0.00 | 0.00 | 28416953.77 | 912640.84 | 0.00 | 0.105203E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.347657E+11 | 0.339287E+12 | 0.00 | 0.233112E+09 | 0.110879E+12 | 0.348805E+09 | 0.494076E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.139570E+11 | 0.845027E+11 | 0.00 | 58703670.15 | 0.324596E+11 | 0.348805E+09 | 0.105203E+11 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341062E+10 | 0.00 | 0.00 | 3497992.84 | 0.00 | 0.00 | 0.119952E+10 | 0.00 | 0.53 |
February | 0.193063E+10 | 0.00 | 0.00 | 5912095.26 | 1826585.79 | 0.00 | 0.121448E+10 | 0.00 | 0.60 |
March | 0.102378E+10 | 0.431520E+09 | 0.00 | 8131945.47 | 0.107648E+09 | 0.00 | 0.102690E+10 | 0.00 | 0.79 |
April | 0.200141E+09 | 0.267855E+10 | 0.00 | 2135778.51 | 0.113427E+10 | 0.00 | 0.131072E+09 | 0.00 | 1.06 |
May | 4044728.51 | 0.899676E+10 | 0.00 | 133695.62 | 0.265493E+10 | 0.00 | 3221835.34 | 0.00 | 1.12 |
June | 0.00 | 0.136359E+11 | 0.00 | 0.00 | 0.492266E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
July | 0.00 | 0.171179E+11 | 0.00 | 0.00 | 0.821175E+10 | 0.00 | 0.00 | 0.00 | 1.17 |
August | 0.00 | 0.175520E+11 | 0.00 | 0.00 | 0.791219E+10 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.109331E+11 | 0.00 | 0.00 | 0.439587E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 0.348435E+09 | 0.218841E+10 | 0.00 | 2320522.97 | 0.565608E+09 | 0.00 | 0.292693E+09 | 0.00 | 0.82 |
November | 0.155478E+10 | 69449024.89 | 0.00 | 7333441.63 | 32874574.18 | 0.00 | 0.103691E+10 | 0.00 | 0.66 |
December | 0.300803E+10 | 0.00 | 0.00 | 5390886.10 | 0.00 | 0.00 | 0.135677E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.114805E+11 | 0.736037E+11 | 0.00 | 34856358.41 | 0.299396E+11 | 0.00 | 0.626157E+10 | 0.00 | 0.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.341062E+10 | 0.175520E+11 | 0.00 | 8131945.47 | 0.821175E+10 | 0.00 | 0.135677E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239291E+10 | 0.00 | 0.00 | 3569353.34 | 0.00 | 0.00 | 0.125268E+10 | 0.00 | 0.65 |
February | 0.142066E+10 | 0.00 | 0.00 | 5117051.18 | 1417398.93 | 0.00 | 0.114322E+10 | 0.00 | 0.74 |
March | 0.830180E+09 | 0.309585E+09 | 0.00 | 6675782.64 | 82759776.46 | 0.00 | 0.854837E+09 | 0.00 | 0.97 |
April | 0.165301E+09 | 0.203621E+10 | 0.00 | 1806833.45 | 0.852079E+09 | 0.00 | 0.107087E+09 | 0.00 | 1.28 |
May | 3283293.13 | 0.708889E+10 | 0.00 | 74301.84 | 0.197697E+10 | 0.00 | 2142447.96 | 0.00 | 1.38 |
June | 0.00 | 0.943703E+10 | 0.00 | 0.00 | 0.398781E+10 | 0.00 | 0.00 | 0.00 | 1.33 |
July | 0.00 | 0.109087E+11 | 0.00 | 0.00 | 0.677352E+10 | 0.00 | 0.00 | 0.00 | 1.27 |
August | 0.00 | 0.102921E+11 | 0.00 | 0.00 | 0.671134E+10 | 0.00 | 0.00 | 0.00 | 1.20 |
September | 0.00 | 0.783464E+10 | 0.00 | 0.00 | 0.342107E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
October | 0.319775E+09 | 0.161593E+10 | 0.00 | 2010314.80 | 0.435213E+09 | 0.00 | 0.207193E+09 | 0.00 | 0.99 |
November | 0.131020E+10 | 48196467.11 | 0.00 | 5707855.14 | 25510100.09 | 0.00 | 0.775038E+09 | 0.00 | 0.80 |
December | 0.240296E+10 | 0.00 | 0.00 | 3925519.19 | 0.00 | 0.00 | 0.968597E+09 | 0.00 | 0.67 |
Annual Sum or Average | 0.884528E+10 | 0.495712E+11 | 0.00 | 28887011.57 | 0.242677E+11 | 0.00 | 0.531080E+10 | 0.00 | 1.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.240296E+10 | 0.109087E+11 | 0.00 | 6675782.64 | 0.677352E+10 | 0.00 | 0.125268E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243790E+10 | 0.00 | 0.00 | 11345730.52 | 0.00 | 0.00 | 0.361849E+10 | 0.00 | 0.76 |
February | 0.150157E+10 | 1463040.68 | 0.00 | 13919661.32 | 618085.88 | 0.00 | 0.251189E+10 | 0.00 | 0.83 |
March | 0.953039E+09 | 0.696644E+09 | 0.00 | 12791721.53 | 61338637.56 | 0.00 | 0.149156E+10 | 0.00 | 1.03 |
April | 0.198473E+09 | 0.347233E+10 | 0.00 | 2596242.80 | 0.974705E+09 | 0.00 | 0.147397E+09 | 0.00 | 1.20 |
May | 4059340.10 | 0.953572E+10 | 0.00 | 146884.24 | 0.256915E+10 | 0.00 | 3335134.68 | 0.00 | 1.16 |
June | 0.00 | 0.135492E+11 | 0.00 | 0.00 | 0.504544E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
July | 0.00 | 0.173894E+11 | 0.00 | 0.00 | 0.817751E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
August | 0.00 | 0.184168E+11 | 0.00 | 0.00 | 0.785663E+10 | 0.00 | 0.00 | 0.00 | 1.18 |
September | 0.00 | 0.134603E+11 | 0.00 | 0.00 | 0.396955E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
October | 0.304430E+09 | 0.356047E+10 | 0.00 | 4933483.65 | 0.392012E+09 | 0.00 | 0.432065E+09 | 0.00 | 1.13 |
November | 0.114164E+10 | 0.163486E+09 | 0.00 | 20314065.91 | 20540860.25 | 0.00 | 0.225828E+10 | 0.00 | 1.02 |
December | 0.214285E+10 | 0.00 | 0.00 | 14853433.02 | 0.00 | 0.00 | 0.357130E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.868396E+10 | 0.802458E+11 | 0.00 | 80901222.98 | 0.290675E+11 | 0.00 | 0.140343E+11 | 0.00 | 1.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
Maximum of Months | 0.243790E+10 | 0.184168E+11 | 0.00 | 20314065.91 | 0.817751E+10 | 0.00 | 0.361849E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274691E+10 | 0.00 | 0.00 | 5179382.58 | 0.00 | 0.00 | 0.204701E+10 | 0.00 | 0.87 |
February | 0.117220E+10 | 1622208.82 | 0.00 | 9325836.28 | 338743.02 | 0.00 | 0.214384E+10 | 0.00 | 1.01 |
March | 0.634290E+09 | 0.619082E+09 | 0.00 | 13246141.25 | 55414095.56 | 0.00 | 0.164174E+10 | 0.00 | 1.44 |
April | 0.121217E+09 | 0.434937E+10 | 0.00 | 4451424.23 | 0.428398E+09 | 0.00 | 0.260459E+09 | 0.00 | 2.00 |
May | 3383839.96 | 0.931035E+10 | 0.00 | 187860.62 | 0.207194E+10 | 0.00 | 3840504.33 | 0.00 | 1.71 |
June | 0.00 | 0.148344E+11 | 0.00 | 0.00 | 0.366934E+10 | 0.00 | 0.00 | 0.00 | 1.83 |
July | 0.00 | 0.196642E+11 | 0.00 | 0.00 | 0.584653E+10 | 0.00 | 0.00 | 0.00 | 1.83 |
August | 0.00 | 0.248647E+11 | 0.00 | 0.00 | 0.373377E+10 | 0.00 | 0.00 | 0.00 | 2.00 |
September | 0.00 | 0.110725E+11 | 0.00 | 0.00 | 0.375862E+10 | 0.00 | 0.00 | 0.00 | 1.41 |
October | 0.281730E+09 | 0.252560E+10 | 0.00 | 3695196.91 | 0.420329E+09 | 0.00 | 0.379367E+09 | 0.00 | 1.36 |
November | 0.907013E+09 | 0.113131E+09 | 0.00 | 13073755.40 | 19928021.86 | 0.00 | 0.191754E+10 | 0.00 | 1.18 |
December | 0.119770E+10 | 0.00 | 0.00 | 12956839.75 | 0.00 | 0.00 | 0.381557E+10 | 0.00 | 1.05 |
Annual Sum or Average | 0.706445E+10 | 0.873549E+11 | 0.00 | 62116437.00 | 0.200046E+11 | 0.00 | 0.122094E+11 | 0.00 | 1.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.274691E+10 | 0.248647E+11 | 0.00 | 13246141.25 | 0.584653E+10 | 0.00 | 0.381557E+10 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437757E+11 | 0.00 | 0.00 | 5075484.85 | 0.00 | 50898835.24 | 0.310429E+10 | 0.00 | 0.58 |
February | 0.249471E+11 | 1155950.12 | 0.00 | 26562101.33 | 59149645.56 | 0.00 | 0.535290E+10 | 0.00 | 0.62 |
March | 0.949076E+10 | 0.484298E+10 | 0.00 | 49998419.13 | 0.104004E+10 | 0.00 | 0.722848E+10 | 0.00 | 0.72 |
April | 0.773492E+09 | 0.290696E+11 | 0.00 | 14422028.22 | 0.949336E+10 | 0.00 | 0.115019E+10 | 0.00 | 0.95 |
May | 37818265.89 | 0.100008E+12 | 0.00 | 1337547.40 | 0.227549E+11 | 0.00 | 37467528.36 | 0.00 | 1.18 |
June | 0.00 | 0.151032E+12 | 0.00 | 0.00 | 0.386383E+11 | 0.00 | 0.00 | 0.00 | 1.21 |
July | 0.00 | 0.189462E+12 | 0.00 | 0.00 | 0.559341E+11 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 0.00 | 0.189364E+12 | 0.00 | 0.00 | 0.455958E+11 | 0.00 | 0.00 | 0.00 | 1.08 |
September | 0.00 | 0.117301E+12 | 0.00 | 0.00 | 0.287962E+11 | 0.00 | 0.00 | 0.00 | 0.90 |
October | 0.391543E+10 | 0.226067E+11 | 0.00 | 12262247.65 | 0.458617E+10 | 0.00 | 0.153729E+10 | 0.00 | 0.76 |
November | 0.180758E+11 | 0.685444E+09 | 0.00 | 33838850.24 | 0.478504E+09 | 0.00 | 0.462379E+10 | 0.00 | 0.64 |
December | 0.385614E+11 | 0.00 | 0.00 | 10326128.04 | 12233860.89 | 9388224.30 | 0.386732E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.139577E+12 | 0.804373E+12 | 0.00 | 0.153823E+09 | 0.207389E+12 | 60287059.54 | 0.269017E+11 | 0.00 | 0.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.437757E+11 | 0.189462E+12 | 0.00 | 49998419.13 | 0.559341E+11 | 50898835.24 | 0.722848E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313964E+11 | 0.00 | 0.00 | 11026745.07 | 0.00 | 33573916.83 | 0.701284E+10 | 0.00 | 0.74 |
February | 0.173002E+11 | 973849.31 | 0.00 | 35469392.89 | 48416438.31 | 8113104.31 | 0.858019E+10 | 0.00 | 0.82 |
March | 0.667646E+10 | 0.399755E+10 | 0.00 | 57548053.73 | 0.833154E+09 | 0.00 | 0.854660E+10 | 0.00 | 0.99 |
April | 0.527124E+09 | 0.268251E+11 | 0.00 | 18725604.95 | 0.649693E+10 | 0.00 | 0.132583E+10 | 0.00 | 1.32 |
May | 32999988.12 | 0.832397E+11 | 0.00 | 861526.42 | 0.176319E+11 | 0.00 | 25762006.37 | 0.00 | 1.54 |
June | 0.00 | 0.113247E+12 | 0.00 | 0.00 | 0.325627E+11 | 0.00 | 0.00 | 0.00 | 1.46 |
July | 0.00 | 0.136735E+12 | 0.00 | 0.00 | 0.463558E+11 | 0.00 | 0.00 | 0.00 | 1.34 |
August | 0.00 | 0.135013E+12 | 0.00 | 0.00 | 0.369470E+11 | 0.00 | 0.00 | 0.00 | 1.23 |
September | 0.00 | 0.910428E+11 | 0.00 | 0.00 | 0.224884E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 0.292414E+10 | 0.184974E+11 | 0.00 | 16793399.12 | 0.363976E+10 | 0.00 | 0.193997E+10 | 0.00 | 1.00 |
November | 0.132187E+11 | 0.614442E+09 | 0.00 | 41410733.94 | 0.314691E+09 | 0.00 | 0.636114E+10 | 0.00 | 0.84 |
December | 0.276917E+11 | 0.00 | 0.00 | 16244457.96 | 10013922.58 | 13173386.44 | 0.708519E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.997678E+11 | 0.609213E+12 | 0.00 | 0.198080E+09 | 0.167329E+12 | 54860407.58 | 0.408775E+11 | 0.00 | 1.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.313964E+11 | 0.136735E+12 | 0.00 | 57548053.73 | 0.463558E+11 | 33573916.83 | 0.858019E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262876E+11 | 0.00 | 0.00 | 0.103583E+09 | 0.00 | 0.00 | 0.357944E+11 | 0.00 | 0.85 |
February | 0.158910E+11 | 63005236.77 | 0.00 | 0.119362E+09 | 11684057.47 | 0.00 | 0.237159E+11 | 0.00 | 0.91 |
March | 0.680442E+10 | 0.858139E+10 | 0.00 | 0.108148E+09 | 0.407923E+09 | 0.00 | 0.143758E+11 | 0.00 | 1.02 |
April | 0.638496E+09 | 0.394175E+11 | 0.00 | 20405852.53 | 0.755602E+10 | 0.00 | 0.142625E+10 | 0.00 | 1.14 |
May | 35348473.51 | 0.105155E+12 | 0.00 | 1479077.41 | 0.221708E+11 | 0.00 | 40970519.79 | 0.00 | 1.22 |
June | 0.00 | 0.149378E+12 | 0.00 | 0.00 | 0.394342E+11 | 0.00 | 0.00 | 0.00 | 1.21 |
July | 0.00 | 0.191368E+12 | 0.00 | 0.00 | 0.557098E+11 | 0.00 | 0.00 | 0.00 | 1.16 |
August | 0.00 | 0.203913E+12 | 0.00 | 0.00 | 0.417611E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 0.00 | 0.148464E+12 | 0.00 | 0.00 | 0.236038E+11 | 0.00 | 0.00 | 0.00 | 1.07 |
October | 0.184921E+10 | 0.407684E+11 | 0.00 | 40204715.77 | 0.211206E+10 | 0.00 | 0.470986E+10 | 0.00 | 1.17 |
November | 0.952106E+10 | 0.223768E+10 | 0.00 | 0.179513E+09 | 0.188273E+09 | 0.00 | 0.221676E+11 | 0.00 | 1.11 |
December | 0.226706E+11 | 5102301.08 | 0.00 | 0.119686E+09 | 7722039.92 | 0.00 | 0.341527E+11 | 0.00 | 0.89 |
Annual Sum or Average | 0.836977E+11 | 0.889350E+12 | 0.00 | 0.692382E+09 | 0.192963E+12 | 0.00 | 0.136384E+12 | 0.00 | 1.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.262876E+11 | 0.203913E+12 | 0.00 | 0.179513E+09 | 0.557098E+11 | 0.00 | 0.357944E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357596E+11 | 0.00 | 0.00 | 17050164.29 | 0.00 | 19399454.01 | 0.595569E+10 | 0.00 | 0.81 |
February | 0.205085E+11 | 2443192.67 | 0.00 | 32670022.13 | 50509481.27 | 0.00 | 0.659956E+10 | 0.00 | 0.88 |
March | 0.715489E+10 | 0.545258E+10 | 0.00 | 54782381.26 | 0.647465E+09 | 0.00 | 0.774042E+10 | 0.00 | 1.06 |
April | 0.530179E+09 | 0.329076E+11 | 0.00 | 15324266.40 | 0.568219E+10 | 0.00 | 0.112171E+10 | 0.00 | 1.42 |
May | 29212784.48 | 0.923419E+11 | 0.00 | 1435565.16 | 0.156897E+11 | 0.00 | 34723212.98 | 0.00 | 1.61 |
June | 0.00 | 0.132586E+12 | 0.00 | 0.00 | 0.284350E+11 | 0.00 | 0.00 | 0.00 | 1.61 |
July | 0.00 | 0.153563E+12 | 0.00 | 0.00 | 0.436839E+11 | 0.00 | 0.00 | 0.00 | 1.44 |
August | 0.00 | 0.156760E+12 | 0.00 | 0.00 | 0.343765E+11 | 0.00 | 0.00 | 0.00 | 1.36 |
September | 0.00 | 0.101304E+12 | 0.00 | 0.00 | 0.219235E+11 | 0.00 | 0.00 | 0.00 | 1.18 |
October | 0.298801E+10 | 0.213738E+11 | 0.00 | 12501024.33 | 0.333997E+10 | 0.00 | 0.172376E+10 | 0.00 | 1.06 |
November | 0.140318E+11 | 0.923972E+09 | 0.00 | 37964438.45 | 0.324317E+09 | 0.00 | 0.607900E+10 | 0.00 | 0.92 |
December | 0.314615E+11 | 0.00 | 0.00 | 21348682.51 | 10717772.70 | 10883946.33 | 0.640470E+10 | 0.00 | 0.83 |
Annual Sum or Average | 0.112464E+12 | 0.697216E+12 | 0.00 | 0.193077E+09 | 0.154164E+12 | 30283400.34 | 0.356596E+11 | 0.00 | 1.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
Maximum of Months | 0.357596E+11 | 0.156760E+12 | 0.00 | 54782381.26 | 0.436839E+11 | 19399454.01 | 0.774042E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384094E+10 | 0.00 | 0.00 | 67864.91 | 0.00 | 0.124639E+10 | 53213923.68 | 0.00 | 0.73 |
February | 0.252299E+10 | 0.00 | 0.00 | 1586232.64 | 2301853.82 | 0.283075E+09 | 0.303684E+09 | 0.00 | 0.70 |
March | 0.101843E+10 | 0.364845E+09 | 0.00 | 4532899.85 | 82369788.25 | 0.00 | 0.606691E+09 | 0.00 | 0.76 |
April | 0.102646E+09 | 0.258826E+10 | 0.00 | 1563521.74 | 0.918927E+09 | 0.00 | 79512690.65 | 0.00 | 1.00 |
May | 2826706.74 | 0.958944E+10 | 0.00 | 97782.45 | 0.231972E+10 | 0.00 | 2574356.08 | 0.00 | 1.23 |
June | 0.00 | 0.147475E+11 | 0.00 | 0.00 | 0.409178E+10 | 0.00 | 0.00 | 0.00 | 1.25 |
July | 0.00 | 0.191440E+11 | 0.00 | 0.00 | 0.584319E+10 | 0.00 | 0.00 | 0.00 | 1.21 |
August | 0.00 | 0.189014E+11 | 0.00 | 0.00 | 0.490738E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 0.00 | 0.115397E+11 | 0.00 | 0.00 | 0.356380E+10 | 0.00 | 0.00 | 0.00 | 0.96 |
October | 0.415346E+09 | 0.194219E+10 | 0.00 | 1128661.84 | 0.553605E+09 | 0.00 | 87729844.98 | 0.00 | 0.81 |
November | 0.185717E+10 | 21415043.59 | 0.00 | 2954054.67 | 50112709.89 | 1657904.15 | 0.296187E+09 | 0.00 | 0.68 |
December | 0.355979E+10 | 0.00 | 0.00 | 97684.92 | 215353.83 | 0.765121E+09 | 54401446.17 | 0.00 | 0.70 |
Annual Sum or Average | 0.133201E+11 | 0.788387E+11 | 0.00 | 12028703.00 | 0.223334E+11 | 0.229624E+10 | 0.148399E+10 | 0.00 | 0.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.384094E+10 | 0.191440E+11 | 0.00 | 4532899.85 | 0.584319E+10 | 0.124639E+10 | 0.606691E+09 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295604E+10 | 0.00 | 0.00 | 284497.84 | 0.00 | 0.662217E+09 | 0.231655E+09 | 0.00 | 0.85 |
February | 0.158290E+10 | 0.00 | 0.00 | 2843334.15 | 1725610.03 | 0.116691E+09 | 0.707106E+09 | 0.00 | 0.85 |
March | 0.555214E+09 | 0.301739E+09 | 0.00 | 6077560.08 | 58301141.27 | 0.00 | 0.840154E+09 | 0.00 | 1.00 |
April | 57854562.57 | 0.241186E+10 | 0.00 | 2117436.30 | 0.576317E+09 | 0.00 | 0.112347E+09 | 0.00 | 1.36 |
May | 1947561.09 | 0.805863E+10 | 0.00 | 76684.53 | 0.156467E+10 | 0.00 | 2041457.48 | 0.00 | 1.56 |
June | 0.00 | 0.112340E+11 | 0.00 | 0.00 | 0.304742E+10 | 0.00 | 0.00 | 0.00 | 1.48 |
July | 0.00 | 0.140632E+11 | 0.00 | 0.00 | 0.427953E+10 | 0.00 | 0.00 | 0.00 | 1.38 |
August | 0.00 | 0.137945E+11 | 0.00 | 0.00 | 0.353394E+10 | 0.00 | 0.00 | 0.00 | 1.27 |
September | 0.00 | 0.893433E+10 | 0.00 | 0.00 | 0.266397E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
October | 0.260316E+09 | 0.164953E+10 | 0.00 | 1769785.65 | 0.365549E+09 | 0.00 | 0.156470E+09 | 0.00 | 1.03 |
November | 0.111115E+10 | 28928853.92 | 0.00 | 4306661.27 | 25631578.09 | 0.00 | 0.575517E+09 | 0.00 | 0.84 |
December | 0.266718E+10 | 0.00 | 0.00 | 507252.60 | 161442.37 | 0.289251E+09 | 0.325627E+09 | 0.00 | 0.82 |
Annual Sum or Average | 0.919260E+10 | 0.604768E+11 | 0.00 | 17983212.42 | 0.161172E+11 | 0.106816E+10 | 0.295092E+10 | 0.00 | 1.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.295604E+10 | 0.140632E+11 | 0.00 | 6077560.08 | 0.427953E+10 | 0.662217E+09 | 0.840154E+09 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277640E+10 | 0.00 | 0.00 | 7118888.59 | 0.00 | 0.562469E+09 | 0.274822E+10 | 0.00 | 0.91 |
February | 0.180156E+10 | 1150010.68 | 0.00 | 9841379.59 | 1306608.52 | 58707714.20 | 0.201568E+10 | 0.00 | 0.93 |
March | 0.690966E+09 | 0.612228E+09 | 0.00 | 11090311.42 | 35522936.37 | 0.00 | 0.138527E+10 | 0.00 | 1.02 |
April | 76714327.12 | 0.343398E+10 | 0.00 | 2372296.82 | 0.738735E+09 | 0.00 | 0.121155E+09 | 0.00 | 1.17 |
May | 2726023.89 | 0.100921E+11 | 0.00 | 111391.14 | 0.219093E+10 | 0.00 | 2735087.40 | 0.00 | 1.27 |
June | 0.00 | 0.145592E+11 | 0.00 | 0.00 | 0.418037E+10 | 0.00 | 0.00 | 0.00 | 1.24 |
July | 0.00 | 0.192760E+11 | 0.00 | 0.00 | 0.583130E+10 | 0.00 | 0.00 | 0.00 | 1.21 |
August | 0.00 | 0.202261E+11 | 0.00 | 0.00 | 0.457151E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
September | 0.00 | 0.144266E+11 | 0.00 | 0.00 | 0.300071E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
October | 0.253079E+09 | 0.342620E+10 | 0.00 | 5833102.02 | 0.284438E+09 | 0.00 | 0.351414E+09 | 0.00 | 1.19 |
November | 0.946573E+09 | 0.109703E+09 | 0.00 | 17835872.49 | 19123411.55 | 0.00 | 0.204919E+10 | 0.00 | 1.11 |
December | 0.248235E+10 | 205127.48 | 0.00 | 8630714.17 | 44494.29 | 0.164119E+09 | 0.271491E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.903038E+10 | 0.861635E+11 | 0.00 | 62833956.25 | 0.208540E+11 | 0.785295E+09 | 0.113886E+11 | 0.00 | 1.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
Maximum of Months | 0.277640E+10 | 0.202261E+11 | 0.00 | 17835872.49 | 0.583130E+10 | 0.562469E+09 | 0.274822E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319411E+10 | 0.00 | 0.00 | 1022238.11 | 0.00 | 0.710889E+09 | 0.442081E+09 | 0.00 | 0.96 |
February | 0.211474E+10 | 40325.72 | 0.00 | 2565019.43 | 1903443.39 | 71680275.41 | 0.499865E+09 | 0.00 | 0.95 |
March | 0.734311E+09 | 0.402312E+09 | 0.00 | 5335935.53 | 46323002.18 | 0.00 | 0.698287E+09 | 0.00 | 1.08 |
April | 60753790.09 | 0.280045E+10 | 0.00 | 1668316.79 | 0.556256E+09 | 0.00 | 90880032.37 | 0.00 | 1.44 |
May | 2169567.48 | 0.855763E+10 | 0.00 | 113870.05 | 0.160752E+10 | 0.00 | 2316444.08 | 0.00 | 1.63 |
June | 0.00 | 0.126009E+11 | 0.00 | 0.00 | 0.301013E+10 | 0.00 | 0.00 | 0.00 | 1.62 |
July | 0.00 | 0.150673E+11 | 0.00 | 0.00 | 0.466414E+10 | 0.00 | 0.00 | 0.00 | 1.49 |
August | 0.00 | 0.152787E+11 | 0.00 | 0.00 | 0.375050E+10 | 0.00 | 0.00 | 0.00 | 1.39 |
September | 0.00 | 0.960196E+10 | 0.00 | 0.00 | 0.294763E+10 | 0.00 | 0.00 | 0.00 | 1.24 |
October | 0.312641E+09 | 0.181393E+10 | 0.00 | 1347001.55 | 0.393385E+09 | 0.00 | 0.111536E+09 | 0.00 | 1.10 |
November | 0.142450E+10 | 42881590.52 | 0.00 | 3948414.93 | 28282937.31 | 0.00 | 0.437533E+09 | 0.00 | 0.95 |
December | 0.309933E+10 | 18443.21 | 0.00 | 1322856.32 | 163409.40 | 0.174990E+09 | 0.445966E+09 | 0.00 | 0.93 |
Annual Sum or Average | 0.109426E+11 | 0.661661E+11 | 0.00 | 17323652.71 | 0.170062E+11 | 0.957559E+09 | 0.272846E+10 | 0.00 | 1.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
Maximum of Months | 0.319411E+10 | 0.152787E+11 | 0.00 | 5335935.53 | 0.466414E+10 | 0.710889E+09 | 0.698287E+09 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 8585956.54 | 0.00 | 0.00 | 0.623337E+09 | 0.00 | 0.58 |
February | 0.00 | 5569345.10 | 0.00 | 17983044.78 | 0.00 | 0.00 | 0.307542E+09 | 0.00 | 0.59 |
March | 0.00 | 0.106365E+09 | 0.00 | 19396201.36 | 0.00 | 0.00 | 0.106879E+09 | 0.00 | 0.59 |
April | 0.00 | 0.320314E+09 | 0.00 | 9127001.11 | 0.00 | 0.00 | 8948742.74 | 0.00 | 0.59 |
May | 0.00 | 0.840373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.174935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.170941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.124798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.404175E+09 | 0.00 | 2197483.23 | 0.00 | 0.00 | 5831479.59 | 0.00 | 0.59 |
November | 0.00 | 37224039.07 | 0.00 | 26639832.65 | 0.00 | 0.00 | 0.162742E+09 | 0.00 | 0.59 |
December | 0.00 | 5076.55 | 0.00 | 46416766.18 | 0.00 | 0.00 | 0.501687E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.770061E+10 | 0.00 | 0.130346E+09 | 0.00 | 0.00 | 0.171697E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174935E+10 | 0.00 | 46416766.18 | 0.00 | 0.00 | 0.623337E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 60661414.04 | 0.00 | 0.00 | 0.634392E+10 | 0.00 | 0.58 |
February | 0.00 | 53088472.77 | 0.00 | 0.158879E+09 | 0.00 | 0.00 | 0.311641E+10 | 0.00 | 0.59 |
March | 0.00 | 0.106008E+10 | 0.00 | 0.182761E+09 | 0.00 | 0.00 | 0.108072E+10 | 0.00 | 0.59 |
April | 0.00 | 0.322815E+10 | 0.00 | 88314060.41 | 0.00 | 0.00 | 91520690.33 | 0.00 | 0.59 |
May | 0.00 | 0.834392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.174565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.172379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.401350E+10 | 0.00 | 20765400.95 | 0.00 | 0.00 | 61858972.56 | 0.00 | 0.59 |
November | 0.00 | 0.369385E+09 | 0.00 | 0.246310E+09 | 0.00 | 0.00 | 0.165201E+10 | 0.00 | 0.59 |
December | 0.00 | 41352.60 | 0.00 | 0.422310E+09 | 0.00 | 0.00 | 0.505585E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.768565E+11 | 0.00 | 0.118000E+10 | 0.00 | 0.00 | 0.174023E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174565E+11 | 0.00 | 0.422310E+09 | 0.00 | 0.00 | 0.634392E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129836E+09 | 0.00 | 0.00 | 2921732.27 | 0.00 | 0.00 | 0.514182E+09 | 0.00 | 0.58 |
February | 0.00 | 6425220.85 | 0.00 | 14055307.55 | 0.00 | 0.00 | 0.301776E+09 | 0.00 | 0.59 |
March | 0.00 | 0.114942E+09 | 0.00 | 16992580.37 | 0.00 | 0.00 | 99881093.90 | 0.00 | 0.59 |
April | 0.00 | 0.342903E+09 | 0.00 | 7796245.62 | 0.00 | 0.00 | 7613679.03 | 0.00 | 0.59 |
May | 0.00 | 0.853776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.176483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.417793E+09 | 0.00 | 1780835.75 | 0.00 | 0.00 | 5157597.95 | 0.00 | 0.59 |
November | 0.00 | 42036388.13 | 0.00 | 22626450.58 | 0.00 | 0.00 | 0.154890E+09 | 0.00 | 0.59 |
December | 0.00 | 34928.56 | 0.00 | 39105780.50 | 0.00 | 0.00 | 0.492738E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.129836E+09 | 0.785621E+10 | 0.00 | 0.105279E+09 | 0.00 | 0.00 | 0.157624E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.129836E+09 | 0.176610E+10 | 0.00 | 39105780.50 | 0.00 | 0.00 | 0.514182E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.516470E+09 | 0.00 | 0.00 | 0.139766E+11 | 0.00 | 0.66 |
February | 0.00 | 0.161626E+09 | 0.00 | 0.907873E+09 | 0.00 | 0.00 | 0.671762E+10 | 0.00 | 0.66 |
March | 0.00 | 0.246970E+10 | 0.00 | 0.870099E+09 | 0.00 | 0.00 | 0.203213E+10 | 0.00 | 0.66 |
April | 0.00 | 0.467721E+10 | 0.00 | 0.630767E+09 | 0.00 | 0.00 | 0.360874E+09 | 0.00 | 0.67 |
May | 0.00 | 0.197124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.289885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.390377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.330402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.299119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.949457E+10 | 0.00 | 89377611.20 | 0.00 | 0.00 | 87693313.50 | 0.00 | 0.66 |
November | 0.00 | 0.892052E+09 | 0.00 | 0.124478E+10 | 0.00 | 0.00 | 0.324480E+10 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 0.227082E+10 | 0.00 | 0.00 | 0.109833E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.168386E+12 | 0.00 | 0.653019E+10 | 0.00 | 0.00 | 0.374030E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.390377E+11 | 0.00 | 0.227082E+10 | 0.00 | 0.00 | 0.139766E+11 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290610E+12 | 0.496254E+10 | 0.00 | 0.131909E+13 | 0.113130E+13 |
February | 0.336467E+12 | 0.564629E+10 | 0.00 | 0.836070E+12 | 0.170056E+13 |
March | 0.457375E+12 | 0.301799E+10 | 0.00 | 0.351284E+12 | 0.300884E+13 |
April | 0.497492E+12 | -0.330146E+10 | 0.00 | -0.473693E+12 | 0.433927E+13 |
May | 0.542443E+12 | -0.130894E+11 | 0.00 | -0.147884E+13 | 0.444684E+13 |
June | 0.506292E+12 | -0.145984E+11 | 0.00 | -0.229950E+13 | 0.568167E+13 |
July | 0.412033E+12 | -0.306851E+11 | 0.00 | -0.313981E+13 | 0.689828E+13 |
August | 0.345090E+12 | -0.216487E+11 | 0.00 | -0.319920E+13 | 0.728207E+13 |
September | 0.372744E+12 | -0.123278E+11 | 0.00 | -0.233605E+13 | 0.465361E+13 |
October | 0.355351E+12 | -0.126634E+10 | 0.00 | -0.265672E+12 | 0.319324E+13 |
November | 0.308004E+12 | 0.128362E+10 | 0.00 | 0.663557E+12 | 0.265592E+13 |
December | 0.266481E+12 | 0.488226E+10 | 0.00 | 0.121977E+13 | 0.247505E+13 |
Annual Sum or Average | 0.469038E+13 | -0.771244E+11 | 0.00 | -0.880298E+13 | 0.474667E+14 |
Minimum of Months | 0.266481E+12 | -0.306851E+11 | 0.00 | -0.319920E+13 | 0.113130E+13 |
Maximum of Months | 0.542443E+12 | 0.564629E+10 | 0.00 | 0.131909E+13 | 0.728207E+13 |