Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 09:02:55


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31188.78 673.33 673.33
Net Site Energy 31188.78 673.33 673.33
Total Source Energy 96252.34 2077.97 2077.97
Net Source Energy 96252.34 2077.97 2077.97


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 469.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3391.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 905.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1997.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2462.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1391.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4100.17
Humidification 2.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 741.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29977.77 1211.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6381.37
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 469.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3391.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 905.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 87.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 61.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2462.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1391.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4100.17
Humidification General 2.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 741.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 469.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3391.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3942.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 905.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1997.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2462.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 670.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1391.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4100.17
Humidification Unassigned 2.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 741.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 104.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 170.96 26.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 371.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 647.18 26.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 104.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 170.96 26.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Other 371.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 647.18 26.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 29977.769 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 29977.769 100.00
     
Total On-Site and Utility Electric Sources 29977.769 100.00
Total Electricity End Uses 29977.769 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6381.37 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6381.37 100.00
Total Water End Uses 6381.37 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 229.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 9.1390 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 9.1390 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 9.1390 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 9.1390 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 11.7111 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 9.1390 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.1631 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 9.1631 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 9.1390 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 9.1390 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 9.1390 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 9.1390 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 9.1390 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 9.1390 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 9.1390 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 9.1390 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 9.1390 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 9.1390 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 9.1390 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 9.1390 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 9.1390 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 9.1390 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 9.1390 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 9.1390 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 11.7111 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 11.7111 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 11.7111 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 9.1390 18.58 484.4232  
Total 46320.38             9.1631 9.29 17.8789  
Conditioned Total 46320.38             9.1631 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.8180 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 18-AUG-15:50 09-JAN-07:10 - - - - - - - - - - 16-OCT-11:09
Heating 0.00 752660.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 448084.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 86589.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 197236.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 63208.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 82101.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 31236.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2015457.69 783896.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 752660.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 448084.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 5474.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 197236.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 63208.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 82101.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 31236.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 508.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10740.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12485.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2866.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6326.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7797.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2124.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4408.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 8.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 804.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 94939.60 1312.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 10.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 231.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 136.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 168.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 95.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 17.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2049.63 28.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 10.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 231.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 269.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 136.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 168.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 45.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 95.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 17.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2049.63 28.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.63
DATACENTER_BOT_ZN_6 DIRECT AIR 0.477450
DATACENTER_MID_ZN_6 DIRECT AIR 4.54
DATACENTER_TOP_ZN_6 DIRECT AIR 0.463128
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.92 0.321237 0.300000 1.78 0.856632 0.500000 0.001186 0.000154 1.78 12.80 0.008000
CORE_MID VAV BOX COMPONENT 55.72 0.341355 0.301000 16.77 0.910281 0.500000 0.001116 0.003093 16.77 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.47 0.347709 0.308000 1.68 0.927225 0.500000 0.001096 0.000596 2.06 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.881074 0.271056 0.300000 0.264322 0.722817 0.500000 0.001406 0.000056 0.264322 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.947007 0.162517 0.300000 0.284102 0.433380 0.500000 0.002344 0.000050 0.284102 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.16 0.205147 0.300000 0.349250 0.547060 0.500000 0.001857 0.000079 0.349250 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.21 0.126859 0.300000 0.363961 0.338290 0.500000 0.003003 0.000043 0.363961 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.25 0.289401 0.301000 2.48 0.771737 0.500000 0.001317 0.001398 4.85 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.63 0.159888 0.301000 2.90 0.426369 0.500000 0.002383 0.000936 3.25 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 11.17 0.213751 0.301000 3.36 0.570003 0.500000 0.001782 0.001405 4.88 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.30 0.149402 0.301000 3.10 0.398406 0.500000 0.002550 0.000857 3.10 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.955114 0.250044 0.308000 0.294175 0.666784 0.500000 0.001524 0.000190 0.661605 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.962924 0.159831 0.308000 0.296581 0.426216 0.500000 0.002384 0.000126 0.438351 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.24 0.192030 0.308000 0.383057 0.512079 0.500000 0.001984 0.000191 0.664281 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.12 0.137660 0.308000 0.344348 0.367092 0.500000 0.002768 0.000119 0.414957 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 17552.69 0.000154 353.85
CORE_MID VAV BOX REHEAT COIL 353599.38 0.003093 8033.88
CORE_TOP VAV BOX REHEAT COIL 68122.29 0.000596 1799.58
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6366.37 0.000056 149.84
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5673.93 0.000050 127.28
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9078.50 0.000079 218.71
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4956.20 0.000043 103.78
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 159768.61 0.001398 4214.86
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 106940.67 0.000936 2821.08
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 160569.90 0.001405 4235.98
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 98000.55 0.000857 2539.12
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 21768.65 0.000190 574.10
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 14422.12 0.000126 380.34
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 21856.52 0.000191 576.41
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 13653.72 0.000119 360.09
VAV_BOT WITH REHEAT HEATING COIL 29592.92 0.000259 508.99
VAV_MID WITH REHEAT HEATING COIL 276530.50 0.002419 4753.75
VAV_TOP WITH REHEAT HEATING COIL 29917.59 0.000262 514.30
CAV_BAS HEATING COIL 261828.03 0.002291 5929.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.06 3.04 10.13 3.04 9.31 9.31 0.300000 0.326268 9.31
VAV_MID WITH REHEAT 47.54 28.62 95.07 28.62 86.25 86.25 0.300000 0.331806 86.25
VAV_TOP WITH REHEAT 4.87 3.00 9.75 4.24 9.33 9.33 0.300000 0.454626 9.33
CAV_BAS 5.63 5.63 5.63 5.63 5.63 5.63 1.00 1.00 5.63
AIRLOOP DATACENTER BASEMENT 21.68 21.68 21.68 21.68 21.68 21.68 1.00 0.999988 21.68
AIRLOOP DATACENTER BOT 0.477450 0.477450 0.477450 0.477450 0.477450 0.477450 1.00 1.00 0.477450
AIRLOOP DATACENTER MID 4.54 4.54 4.54 4.54 4.54 4.54 1.00 1.00 4.54
AIRLOOP DATACENTER TOP 0.463128 0.463128 0.463128 0.463128 0.463128 0.463128 1.00 1.00 0.463128
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.31 2.74
VAV_MID WITH REHEAT_OA_CONTROLLER 86.25 28.64
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.33 3.01
CAV_BAS_OA_CONTROLLER 5.63 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.68 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.477450 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.54 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.463128 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.25 6.67 10.91 0.008660 0.008500 176854.47 0.007524 9.31
VAV_MID WITH REHEAT COOLING COIL 26.62 6.67 10.91 0.008647 0.008500 1673011.05 0.071174 86.25
VAV_TOP WITH REHEAT COOLING COIL 26.35 6.67 10.91 0.008632 0.008500 177525.69 0.007552 9.33
CAV_BAS COOLING COIL 24.27 6.67 11.27 0.008799 0.008500 93307.53 0.003970 5.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.31
VAV_MID WITH REHEAT FAN 86.25
VAV_TOP WITH REHEAT FAN 9.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007524 0.000063
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000259  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.071174 0.000007
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.002419  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.007552 0.000063
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000262  
CAV_BAS_COOLC_CONTROLLER 0.003970 0.000120
CAV_BAS_HEATC_CONTROLLER 0.002291  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.68 427734.10 304842.55 0.010475
AIRLOOP DATACENTER BOT COOLING COIL 0.477450 9238.26 6647.40 0.000226
AIRLOOP DATACENTER MID COOLING COIL 4.54 87938.88 63251.64 0.002154
AIRLOOP DATACENTER TOP COOLING COIL 0.463128 8965.04 6449.24 0.000220
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.68 21.68 21.68 21.68 427734.10 427734.10 14546.91 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.477450 0.477450 0.477450 0.477450 9238.26 9238.26 672.01 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.54 4.54 4.54 4.54 87938.88 87938.88 6720.07 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.463128 0.463128 0.463128 0.463128 8965.04 8965.04 672.01 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.68
AIRLOOP DATACENTER BOT SUPPLY FAN 0.477450
AIRLOOP DATACENTER MID SUPPLY FAN 4.54
AIRLOOP DATACENTER TOP SUPPLY FAN 0.463128
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.68 427734.10 0.010475
AIRLOOP DATACENTER BOT HEATING COIL 0.477450 9238.26 0.000226
AIRLOOP DATACENTER MID HEATING COIL 4.54 87938.88 0.002154
AIRLOOP DATACENTER TOP HEATING COIL 0.463128 8965.04 0.000220
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 14546.91
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 672.01
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6720.07
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 672.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000085 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.090219 18590.88  
HEATSYS1 PUMP 0.014524 4374.04 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.090219 10.83
HEATSYS1 0.014524 1.74
COOLSYS1_SUPPLY 0.090219 10.83
SINGLE WATER PLANT LOOP 0.013075 1.57
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.090219 0.090219 378696.21 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1660199.14 1660199.14 0.014524
CENTRAL BOILER 538561.25 527854.83 0.013075
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.090219 12871.09
PLANT CIRC PUMP 0.013075 3334.68
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.090219 0.045365 1068974.31 1074044.39 0.053354
COOLSYS1 CHILLER2 0.090219 0.045365 1068974.31 1074044.39 0.053354
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013075 139666.47 60190.47 69833.23 7879.72 21503.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.106707 12.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.106707 32137.89
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 44.05 1275205.56 8.81 159400.70
TOWERWATERSYS COOLTOWER 2 44.05 1275205.56 8.81 159400.70
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.055207
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 9.139 4.842 0.000 0.000 0.000 0.000 13.981 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 9.139 8.070 0.000 0.000 0.000 0.000 17.209 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 11.711 215.299 0.000 0.000 0.000 0.000 227.010 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 9.139 484.423 0.000 0.000 0.000 0.000 493.562 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 25401.240 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25401.240
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 22812.099 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 22812.099
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2864.287 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.287
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2864.349 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2864.349
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1845.855 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.855
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 7162.063 9.139 169.792 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 7162.063
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 423.975 11.711 217.579 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 423.975


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.388 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.309 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.748 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5529
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5968
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4048
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
47 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
48 1 -21.915918 0.11588205 -6.3286394 0.20197014
49 0 21.365777 0.10835518 5.5011278  
50 9 0.14936390E-14 0.46629455E-16 -0.12795352E-09 -0.66400649E-17
51 8 0.18805887E-07 0.18159818E-12 0.34474146E-03 -0.21382941E-09
52 7 -0.11252545E-01 0.97723248E-08 -0.21660891E-01 0.12794553E-03
53 6 0.37847320 0.34543709E-05 0.44913146 -0.44309468E-02
54 5 -4.9282258 0.13076234E-03 -4.2646138 0.59931023E-01
55 4 31.842168 0.10829460E-02 20.749181 -0.40671262
56 3 -108.75588 0.23861691E-02 -54.257293 1.4795061
57 2 194.68186 0.13553303E-02 76.622599 -2.8618236
58 1 -170.25944 0.14599092E-03 -54.892904 2.7297248
59 0 57.057407 0.83922952E-06 15.620320  
60 9 0.13190950E-14 0.47053660E-16 -0.13177724E-09 -0.28207423E-17
61 8 0.19344724E-07 0.17221620E-12 0.35067097E-03 -0.21995616E-09
62 7 -0.11430408E-01 0.92046754E-08 -0.21917296E-01 0.12996789E-03
63 6 0.38330737 0.32449471E-05 0.45327188 -0.44879295E-02
64 5 -4.9754179 0.12255100E-03 -4.2965173 0.60516169E-01
65 4 32.051012 0.10128445E-02 20.874116 -0.40948534
66 3 -109.20051 0.22276377E-02 -54.504393 1.4859293
67 2 195.12287 0.12632445E-02 76.848802 -2.8688263
68 1 -170.42247 0.13586949E-03 -54.957888 2.7325821
69 0 57.057407 0.77977499E-06 15.608941  
70 9 0.10819255E-14 0.54711344E-16 -0.11066527E-09 -0.36132711E-17
71 8 0.16356712E-07 0.22118555E-12 0.31701547E-03 -0.18598145E-09
72 7 -0.10418202E-01 0.12306004E-07 -0.20457116E-01 0.11845872E-03
73 6 0.35579247 0.44086679E-05 0.42963628 -0.41635997E-02
74 5 -4.7067638 0.16880913E-03 -4.1140972 0.57185110E-01
75 4 30.861815 0.14123489E-02 20.159088 -0.39369740
76 3 -106.66785 0.31399051E-02 -53.089917 1.4493439
77 2 192.60981 0.17975336E-02 75.555228 -2.8289238
78 1 -169.49307 0.19502980E-03 -54.588616 2.7162932
79 0 57.057407 0.11300463E-05 15.675537  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4644_SHGC_EAST_0.25 35 1 VerySmooth 2.640 2.640 1.000 0.251    
2 WINDOW_U_0.4644_SHGC_SOUTH_0.25 36 1 VerySmooth 2.640 2.640 1.000 0.251    
3 WINDOW_U_0.4644_SHGC_WEST_0.25 37 1 VerySmooth 2.640 2.640 1.000 0.251    
4 WINDOW_U_0.4644_SHGC_NORTH_0.25 38 1 VerySmooth 2.640 2.640 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.481 5.5005E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.206 6.562E-004 9.868E-004 0.861 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 0.137 6.789E-004 9.962E-004 0.891 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.206 6.562E-004 9.868E-004 0.861 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 0.137 6.789E-004 9.962E-004 0.891 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.206 6.562E-004 1.025E-003 0.861 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 0.137 6.789E-004 1.025E-003 0.891 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.206 6.562E-004 1.025E-003 0.861 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 0.137 6.789E-004 1.025E-003 0.891 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.206 6.562E-004 1.025E-003 0.861 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 0.137 6.789E-004 1.025E-003 0.891 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.206 6.562E-004 1.025E-003 0.861 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 0.137 6.789E-004 1.025E-003 0.891 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.305 8.549E-005 1.025E-003 0.252 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.305 8.549E-005 1.025E-003 0.252 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.305 8.549E-005 7.891E-005 0.252 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 76688.93544 76688.93544 5.62609 5.62609 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.71400 8.22310E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 3.80000 5.05843E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 80713.56388 80713.56388 5.92100 5.92100 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.71400 8.22310E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 3.80000 5.05843E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 759760.96948 759760.96948 55.72034 55.72034 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.71400 8.22310E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 187866.90747 187866.90747 8.02400 10.77825 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 73889.26520 73889.26520 5.47021 5.47021 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 47737.95645 47737.95645 2.06286 2.06286 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 11901.42621 11901.42621 0.88107 0.88107 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 31.30000 8.23349E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 3761.33019 3761.33019 0.16177 0.16177 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12884.84675 12884.84675 0.94701 0.94701 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.71400 8.22310E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 2873.21552 2873.21552 0.12385 0.12385 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15725.44031 15725.44031 1.16417 1.16417 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 30.85500 8.23278E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 5633.96746 5633.96746 0.24330 0.24330 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16387.88874 16387.88874 1.21320 1.21320 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 1372.67592 1372.67592 5.90882E-002 8.72129E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 111471.06789 111471.06789 8.25222 8.25222 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 111877.16979 111877.16979 4.85240 4.85240 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 130026.18337 130026.18337 9.62579 9.62579 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 25.27767 8.22398E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 74880.49074 74880.49074 3.24827 3.24827 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 150926.18726 150926.18726 11.17308 11.17308 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 112437.30642 112437.30642 4.87680 4.87680 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 139151.48309 139151.48309 10.30138 10.30138 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 67401.92541 67401.92541 2.92268 2.92268 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 12901.74859 12901.74859 0.95511 0.95511 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 15237.29805 15237.29805 0.66161 0.66161 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 13007.28723 13007.28723 0.96292 0.96292 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:20:00 26.90933 8.22654E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 10094.73660 10094.73660 0.43835 0.43835 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 16799.89557 16799.89557 1.24369 1.24369 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 31.15167 8.23326E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 15298.72887 15298.72887 0.66428 0.66428 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 15102.22618 15102.22618 1.11801 1.11801 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 9557.52177 9557.52177 0.41496 0.41496 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3.80000 5.05843E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8176.66956 8176.66956 0.47745 0.47745 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 28.94150 8.22975E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 3.80000 5.05843E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77777.92418 77777.92418 4.54163 4.54163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 28.94150 8.22975E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 3.80000 5.05843E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7931.34969 7931.34969 0.46313 0.46313 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 29.16400 8.23009E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 3.80000 5.05843E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371299.30296 371299.30296 21.68043 21.68043 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 23.20100 8.22076E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 3.80000 5.05843E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 141483.41 9.31115 9.31115 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 18104.43 1.69395 1.69395 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1307904.75 86.24584 86.24584 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 285130.34 26.67840 26.67840 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 150163.11 9.33086 9.33086 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 32059.03 4.24205 4.24205 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00
7 CAV_BAS Cooling Sensible 76329.63 5.62609 5.62609 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 51592.61 1.20016 1.20016 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 366827.56 21.68069 21.68069 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 14546.91 0.33839 0.33839 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8089.27 0.47745 0.47745 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 672.01 1.56323E-002 1.56323E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 76954.54 4.54163 4.54163 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6720.07 0.15632 0.15632 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7848.91 0.46313 0.46313 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 672.01 1.56323E-002 1.56323E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.62609
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.92100
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32124
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.77630
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85663
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.18604E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.53559E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.77630
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17552.69135
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.53559E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 353.84848
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 55.72034
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34136
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30100
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.77182
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91028
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11614E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.09344E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.77182
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 353599.38375
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.09344E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8033.88418
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.47021
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34771
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.68482
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.92723
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09574E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.95964E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.06286
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 68122.29390
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.95964E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1799.57966
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.88107
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27106
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26432
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72282
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.40561E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.56957E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26432
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6366.36540
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.56957E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 149.83770
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.94701
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16252
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28410
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43338
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.34437E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.96380E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28410
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5673.92669
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.96380E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 127.28467
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16417
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20515
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34925
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54706
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.85720E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.94227E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34925
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9078.50276
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.94227E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 218.71405
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.21320
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12686
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36396
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33829
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.00334E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.33590E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36396
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4956.19805
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.33590E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.78059
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.25222
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28940
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30100
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.48392
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77174
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.31651E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.39773E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.85240
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 159768.61090
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.39773E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4214.86317
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.62579
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15989
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30100
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.89736
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42637
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.38291E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.35564E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.24827
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 106940.67072
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.35564E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2821.07749
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.17308
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21375
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30100
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.36310
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.78245E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40474E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.87680
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 160569.90271
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40474E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4235.97664
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.30138
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14940
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30100
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.10071
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39841
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55016E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.57352E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.10071
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 98000.54662
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.57352E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2539.11791
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.95511
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25004
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29418
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66678
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.52373E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.90442E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.66161
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21768.65055
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.90442E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 574.09703
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96292
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15983
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29658
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42622
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.38377E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.26171E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43835
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14422.12269
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.26171E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 380.33936
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.24369
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19203
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38306
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51208
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.98407E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.91210E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.66428
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21856.52257
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.91210E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 576.41231
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11801
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13766
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30800
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34435
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36709
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76770E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.19449E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41496
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13653.72445
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.19449E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 360.09080
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47745
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.54163
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46313
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.68043
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.06323
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.03794
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.12645
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.03794
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.31115
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.31115
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32627
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 47.53641
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 28.61692
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 95.07282
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 28.61692
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 86.24584
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 86.24584
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33181
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.87498
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.00299
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.74995
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 4.24205
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.33086
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.33086
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.45463
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.62609
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.62609
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.62609
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.62609
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.62609
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.62609
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.68043
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.68043
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.68043
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.68043
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.68069
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.68069
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47745
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47745
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47745
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.47745
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.47745
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.47745
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.54163
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.54163
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.54163
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.54163
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.54163
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.54163
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46313
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46313
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46313
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46313
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46313
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46313
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.31115
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 86.24584
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.33086
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.62609
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.68069
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.47745
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.54163
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46313
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.31115
289 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.73523
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.25396
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90718
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.66029E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 176854.47099
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.52380E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.31115
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 29592.91549
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.58892E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 508.99113
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.31115
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.52380E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.32912E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.58892E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 86.24584
306 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 28.63723
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.62301
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90714
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.64669E-003
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1673011.05238
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.11738E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 86.24584
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 276530.49726
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.41921E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 4753.75390
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 86.24584
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.11738E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.69053E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.41921E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.33086
323 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 3.00717
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.35191
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90709
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.63159E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 177525.69110
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.55235E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.33086
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 29917.58998
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.61732E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 514.30443
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.33086
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.55235E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.30519E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.61732E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.62609
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.27261
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.26784
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.79872E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 93307.53408
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.96952E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.62609
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 261828.02781
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.29059E-003
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5929.35416
352 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.62609
353 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.96952E-003
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.19962E-004
355 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.29059E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.68069
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.68069
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 427734.09707
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 304842.54544
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.04752E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.68069
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.68069
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.68069
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.68069
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 427734.09707
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 427734.09707
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 14546.90948
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.68069
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.68069
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 427734.09707
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.04752E-002
374 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 14546.90948
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 8.49392E-005
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47745
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47745
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9238.26226
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6647.39520
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.26244E-004
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.47745
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.47745
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.47745
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47745
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9238.26226
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9238.26226
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 672.00695
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.47745
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47745
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9238.26226
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.26244E-004
397 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 672.00695
398 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.54163
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.54163
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 87938.87845
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 63251.64278
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.15362E-003
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.54163
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.54163
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.54163
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.54163
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 87938.87845
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 87938.87845
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6720.06953
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.54163
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.54163
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 87938.87845
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.15362E-003
416 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6720.06953
417 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46313
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46313
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 8965.04141
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6449.23822
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.19553E-004
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46313
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46313
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46313
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46313
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 8965.04141
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 8965.04141
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 672.00695
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46313
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46313
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 8965.04141
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.19553E-004
435 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 672.00695
436 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 9.02194E-002
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 18590.88009
438 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 9.02194E-002
439 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 10.82633
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 9.02194E-002
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 9.02194E-002
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 378696.20510
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
444 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.45241E-002
445 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.74290
446 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.45241E-002
447 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 4374.03506
448 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1660199.14366
450 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1660199.14000
451 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.45241E-002
452 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 9.02194E-002
453 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 10.82633
454 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 9.02194E-002
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 12871.09340
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 9.02194E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.53652E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1068974.30771
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1074044.39000
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.33536E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 9.02194E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.53652E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1068974.30771
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1074044.39000
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.33536E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.30746E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.56895
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.30746E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3334.67574
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.30746E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
472 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 60190.46691
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21503.61655
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 538561.25436
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 527854.83000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.30746E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.10671
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 12.80487
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.10671
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 32137.89267
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 44.05221
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1275205.56141
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 8.81044
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 159400.69518
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 44.05221
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1275205.56141
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 8.81044
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 159400.69518
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.52075E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.52075E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 16643.60
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 335082.40
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 64563.42
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6031.64
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 5377.08
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 8600.34
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4698.70
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 151383.62
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 101327.33
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 152142.68
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 92805.72
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 20624.96
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 13664.34
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 20708.20
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 12936.42
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 24861.72
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 232085.64
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 25109.14
19 Coil:Heating:Water CAV_BAS HEATING COIL 211800.41


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 219921.55 153949.18 65972.37 0.70 22910.40 232.37
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2054186.91 1433613.99 620572.92 0.70 213382.00 2164.24
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 220451.68 154294.20 66157.47 0.70 22946.39 232.73
4 Coil:Cooling:Water CAV_BAS COOLING COIL 123829.61 88770.95 35058.66 0.72 12896.63 130.80


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.65 22.69
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.65 22.69


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.388 1.149   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.309 1.094   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.748 1.385   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3091734169 0.2656494879 Pass Pass 0.8447240822 0.9851338063 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.5622810398E-003 2.6688360018E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.7203470910E-003 2.6645872633E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 1.3596102935E-002 9.3545346750E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.1039210835E-002 2.0230751733E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 5.1077637861E-002 8.9220003143E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 5.9907396126E-002 7.2766728148E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 3.1932811091E-002 2.9229461117E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.3538727568E-002 2.3985417690E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 5.3379478374E-002 9.2585238934E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 6.2873764344E-002 7.3619362402E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 3.4435885867E-002 2.9994379283E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 2.7742444964E-002 2.2836681283E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 5.3274078173E-002 8.7233910072E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 6.4945408143E-002 7.1142444996E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 3.9256047803E-002 2.9483582891E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.4397604304E-003 7.1066306362E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.6334810489E-003 9.7566927042E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.6984944850E-002 3.6441798008E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 6.1272292433E-006 6.8816733353E-006 Pass Pass 2.1010461199E-003 1.7972698879E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 5.2892534564E-006 5.5775863515E-006 Pass Pass 1.3121583206E-002 9.0869000263E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 2.2773944850E-002 9.6092523934E-003 Pass Pass 4.9712676852E-003 3.3924486115E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 6.1364154984E-006 7.2241775705E-006 Pass Pass 4.1534688369E-005 1.0451346325E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6714.24 142.04 0.00 21545.59 21414.56 49816.43



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.149 1.388 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.149 1.388 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.149 1.388 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.149 1.388 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.094 1.309 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.094 1.309 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.094 1.309 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.094 1.309 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.385 1.748 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.385 1.748 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.385 1.748 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.385 1.748 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.149 1.388 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.149 1.388 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.149 1.388 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.149 1.388 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.094 1.309 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.094 1.309 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.094 1.309 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.094 1.309 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.385 1.748 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.385 1.748 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.385 1.748 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.385 1.748 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.273 0.283 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.640 0.251 0.251                      
North Total or Average             1043.06 2.640 0.251 0.251                      
Non-North Total or Average             2433.80 2.640 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 9.1390 2779.43 25401.24 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 235.63
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 9.1390 2496.12 22812.10 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 211.61
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 9.1390 24961.20 228120.99 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 2116.09
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 9.1390 2496.12 22812.10 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 211.61
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 9.1390 313.41 2864.29 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 9.1390 313.42 2864.35 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 9.1390 3134.13 28642.87 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 265.70
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 9.1390 2019.75 18458.55 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 171.22
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 9.1390 3134.20 28643.49 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 265.70
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 9.1390 2019.75 18458.55 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 171.22
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 9.1390 313.41 2864.29 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 9.1390 313.42 2864.35 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 26.57
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 9.1390 201.98 1845.86 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 17.12
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 9.1390 783.68 7162.06 LightsWired LTG_SCH_OFFICE 50.73 168.00 49.42 0.0000 Y 66.44
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 11.7111 36.20 423.97 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 4.37
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 11.7111 362.03 4239.75 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 43.70
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 11.7111 36.20 423.97 LightsWired LTG_SCH_DATACENTER 56.37 168.00 54.91 0.0000 Y 4.37
Interior Lighting Total       9.1631 46320.38 424440.34               1212.16


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 57580.60 AstronomicalClock -   83.75 83.75 905.27
Exterior Lighting Total 57580.60           905.27



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2115821.77          
HEATSYS1 BOILER Boiler:HotWater 1660199.14 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1074044.39 6.11 1027277.87 5.82 6.65 22.69
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1074044.39 6.11 1027277.87 5.82 6.65 22.69
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 527854.83 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1275205.56          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1275205.56          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 176854.47 219921.55 153949.18 65972.37 0.70 - 22910.40 232.37
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1673011.05 2054186.91 1433613.99 620572.92 0.70 - 213382.00 2164.24
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 177525.69 220451.68 154294.20 66157.47 0.70 - 22946.39 232.73
CAV_BAS COOLING COIL Coil:Cooling:Water 93307.53 123829.61 88770.95 35058.66 0.72 - 12896.63 130.80
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   427734.10 304842.55 122891.55 0.71 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9238.26 6647.40 2590.87 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   87938.88 63251.64 24687.24 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   8965.04 6449.24 2515.80 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 17552.69 16643.60 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 353599.38 335082.40 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 68122.29 64563.42 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 6366.37 6031.64 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 5673.93 5377.08 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 9078.50 8600.34 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 4956.20 4698.70 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 159768.61 151383.62 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 106940.67 101327.33 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 160569.90 152142.68 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 98000.55 92805.72 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 21768.65 20624.96 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 14422.12 13664.34 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 21856.52 20708.20 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 13653.72 12936.42 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 29592.92 24861.72 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 276530.50 232085.64 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 29917.59 25109.14 -
CAV_BAS HEATING COIL Coil:Heating:Water 261828.03 211800.41 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   427734.10 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9238.26 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   87938.88 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   8965.04 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   14546.91 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   672.01 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6720.07 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   672.01 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.31 21264.14 2283.73 1.00 1.12 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 86.25 196962.03 2283.73 1.00 1.07 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.33 21309.15 2283.73 1.00 1.11 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1110.54 5.63 10402.93 1849.05 1.00 1.15 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.68 35756.81 1649.25 1.00 1.14 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 534.80 1120.11 1.00 1.63 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.54 5087.11 1120.11 1.00 1.16 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 518.75 1120.11 1.00 1.64 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.090219 18590.88 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.014524 4374.04 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.090219 12871.09 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013075 3334.68 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.106707 32137.89 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.48 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 76688.94 76688.94 27.59 5.626 5.626 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 24.71 0.00822 1.200 0.00
CORE_BOTTOM 80713.56 80713.56 32.34 5.921 5.921 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00889 24.71 0.00822 1.078 0.00
CORE_MID 759760.97 759760.97 304.38 55.720 55.720 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00891 24.71 0.00822 10.778 0.00
CORE_TOP 73889.27 73889.27 29.60 5.470 5.470 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00891 31.30 0.00823 1.078 0.00
PERIMETER_BOT_ZN_3 11901.43 11901.43 37.97 0.881 0.881 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00879 31.30 0.00823 0.135 0.00
PERIMETER_BOT_ZN_2 12884.85 12884.85 63.79 0.947 0.947 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00868 24.71 0.00822 0.087 0.00
PERIMETER_BOT_ZN_1 15725.44 15725.44 50.17 1.164 1.164 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 24.00 24.00 0.00873 30.86 0.00823 0.135 0.00
PERIMETER_BOT_ZN_4 16387.89 16387.89 81.14 1.213 1.213 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00864 30.41 0.00823 0.087 0.00
PERIMETER_MID_ZN_3 111471.07 111471.07 355.67 8.252 8.252 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00878 31.30 0.00823 1.353 0.00
PERIMETER_MID_ZN_2 130026.18 130026.18 643.77 9.626 9.626 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 24.00 24.00 0.00866 25.28 0.00822 0.872 0.00
PERIMETER_MID_ZN_1 150926.19 150926.19 481.55 11.173 11.173 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00871 30.93 0.00823 1.353 0.00
PERIMETER_MID_ZN_4 139151.48 139151.48 688.95 10.301 10.301 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00865 30.41 0.00823 0.872 0.00
PERIMETER_TOP_ZN_3 12901.75 12901.75 41.17 0.955 0.955 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00873 31.30 0.00823 0.135 0.00
PERIMETER_TOP_ZN_2 13007.29 13007.29 64.40 0.963 0.963 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:20:00 24.00 24.00 0.00865 26.91 0.00823 0.087 0.00
PERIMETER_TOP_ZN_1 16799.90 16799.90 53.60 1.244 1.244 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00868 31.15 0.00823 0.135 0.00
PERIMETER_TOP_ZN_4 15102.23 15102.23 74.77 1.118 1.118 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 24.00 24.00 0.00863 30.41 0.00823 0.087 0.00
DATACENTER_BOT_ZN_6 8176.67 8176.67 225.86 0.477 0.477 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 27.00 27.00 0.00859 28.94 0.00823 0.016 0.00
DATACENTER_MID_ZN_6 77777.92 77777.92 2148.40 4.542 4.542 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 27.00 27.00 0.00859 28.94 0.00823 0.156 0.00
DATACENTER_TOP_ZN_6 7931.35 7931.35 219.08 0.463 0.463 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 27.00 27.00 0.00859 29.16 0.00823 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371299.30 371299.30 473.79 21.680 21.680 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 23.20 0.00822 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 24.79 0.00506 3.80 0.00506 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 22.59 0.00506 3.80 0.00506 1.078 0.00
CORE_MID 187866.91 187866.91 75.26 8.024 10.778 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 3.80 0.00506 10.778 0.00
CORE_TOP 47737.96 47737.96 19.12 2.063 2.063 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 3.80 0.00506 1.078 0.00
PERIMETER_BOT_ZN_3 3761.33 3761.33 12.00 0.162 0.162 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00667 3.80 0.00506 0.135 0.00
PERIMETER_BOT_ZN_2 2873.22 2873.22 14.23 0.124 0.124 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00682 3.80 0.00506 0.087 0.00
PERIMETER_BOT_ZN_1 5633.97 5633.97 17.98 0.243 0.243 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00707 3.80 0.00506 0.135 0.00
PERIMETER_BOT_ZN_4 1372.68 1372.68 6.80 0.059 0.087 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00610 3.80 0.00506 0.087 0.00
PERIMETER_MID_ZN_3 111877.17 111877.17 356.96 4.852 4.852 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00746 3.80 0.00506 1.353 0.00
PERIMETER_MID_ZN_2 74880.49 74880.49 370.74 3.248 3.248 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00747 3.80 0.00506 0.872 0.00
PERIMETER_MID_ZN_1 112437.31 112437.31 358.74 4.877 4.877 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00746 3.80 0.00506 1.353 0.00
PERIMETER_MID_ZN_4 67401.93 67401.93 333.71 2.923 2.923 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00739 3.80 0.00506 0.872 0.00
PERIMETER_TOP_ZN_3 15237.30 15237.30 48.62 0.662 0.662 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00758 3.80 0.00506 0.135 0.00
PERIMETER_TOP_ZN_2 10094.74 10094.74 49.98 0.438 0.438 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00758 3.80 0.00506 0.087 0.00
PERIMETER_TOP_ZN_1 15298.73 15298.73 48.81 0.664 0.664 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00758 3.80 0.00506 0.135 0.00
PERIMETER_TOP_ZN_4 9557.52 9557.52 47.32 0.415 0.415 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00756 3.80 0.00506 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 3.80 0.00506 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.89 0.00766 3.80 0.00506 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 23.76 0.00525 3.80 0.00506 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 3.80 0.00506 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.31 9.31 1.69 1.69 9.3112 3.0379 9.3112 0.3263 0.3000
VAV_MID WITH REHEAT 86.25 86.25 26.68 26.68 86.2458 28.6169 86.2458 0.3318 0.3000
VAV_TOP WITH REHEAT 9.33 9.33 4.24 4.24 9.3309 4.2421 9.3309 0.4546 0.3000
CAV_BAS 5.63 5.63 1.20 1.20 5.6261 5.6261 5.6261 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.68 21.68 0.34 0.34 21.6807 21.6804 21.6807 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.48 0.48 0.02 0.02 0.4775 0.4775 0.4775 1.0000 1.0000
AIRLOOP DATACENTER MID 4.54 4.54 0.16 0.16 4.5416 4.5416 4.5416 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.46 0.46 0.02 0.02 0.4631 0.4631 0.4631 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 17552.691 17552.691 1.776300 0.00015356 353.848   12/21 00:10:00   12/21 00:10:00 17552.69 17552.69 1.776300 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 0.00 0.00 17617.41 17617.41
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 353599.384 353599.384 16.771823 0.00309344 8033.884 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 353599.38 353599.38 16.771823 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 187866.91 0.00 354803.32 354803.32
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 68122.294 68122.294 2.062858 0.00059596 1799.580 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 68122.29 68122.29 2.062858 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00800000 50.7558 47737.96 0.00 68367.44 68367.44
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 6366.365 6366.365 0.264322 0.00005570 149.838 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6366.37 6366.37 0.264322 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00667187 42.4236 3761.33 0.00 6387.21 6387.21
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 5673.927 5673.927 0.284102 0.00004964 127.285 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5673.93 5673.93 0.284102 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00682198 43.3680 2873.22 0.00 5693.35 5693.35
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 9078.503 9078.503 0.349250 0.00007942 218.714 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9078.50 9078.50 0.349250 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00706926 44.9221 5633.97 0.00 9107.90 9107.90
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 4956.198 4956.198 0.363961 0.00004336 103.781 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4956.20 4956.20 0.363961 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00610385 38.8457 1372.68 0.00 4974.14 4974.14
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 159768.611 159768.611 4.852403 0.00139773 4214.863 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 159768.61 159768.61 4.852403 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00745838 47.3656 111877.17 0.00 160302.47 160302.47
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 106940.671 106940.671 3.248268 0.00093556 2821.077 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 106940.67 106940.67 3.248268 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00747416 47.4646 74880.49 0.00 107297.07 107297.07
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 160569.903 160569.903 4.876803 0.00140474 4235.977 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 160569.90 160569.90 4.876803 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00746190 47.3877 112437.31 0.00 161106.25 161106.25
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 98000.547 98000.547 3.100715 0.00085735 2539.118 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 98000.55 98000.55 3.100715 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00739015 46.9377 67401.93 0.00 98300.90 98300.90
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 21768.651 21768.651 0.661605 0.00019044 574.097 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21768.65 21768.65 0.661605 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00758235 48.1432 15237.30 0.00 21840.07 21840.07
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 14422.123 14422.123 0.438351 0.00012617 380.339 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14422.12 14422.12 0.438351 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00758310 48.1479 10094.74 0.00 14469.37 14469.37
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 21856.523 21856.523 0.664281 0.00019121 576.412 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21856.52 21856.52 0.664281 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00758418 48.1546 15298.73 0.00 21928.22 21928.22
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 13653.724 13653.724 0.414957 0.00011945 360.091 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13653.72 13653.72 0.414957 12.80 11.43 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00755511 47.9725 9557.52 0.00 13698.56 13698.56
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 176854.471 -999.000 9.311152 0.00752380 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 176854.47 172237.73 9.311152 26.25 17.11 0.00866029 10.91 10.91 0.00850000 31.30 0.00823349 18.45 29.3758 24.00 0.00885103 46.7373 119617.85 0.00 179389.26 162355.13
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 29592.915 29592.915 2.793346 0.00025889 508.991 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 29592.92 29592.92 2.793346 3.88 3.86 0.00507145 12.80 11.43 0.00800000 3.80 0.00505843 3.80 97.9195 21.77 0.00592028 35.9405 13641.19 0.00 30095.93 30095.93
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1673011.052 -999.000 86.245844 0.07117376 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 1673011.05 1633887.94 86.245844 26.62 17.23 0.00864669 10.91 10.91 0.00850000 31.30 0.00823349 18.45 33.2042 24.00 0.00887852 46.8803 1076255.13 0.00 1696701.53 1541546.93
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 276530.497 276530.497 25.873753 0.00241921 4753.754 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 276530.50 276530.50 25.873753 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 110.6806 21.00 0.00763456 48.4691 554463.80 0.00 280946.59 280946.59
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 177525.691 -999.000 9.330862 0.00755235 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 177525.69 173727.40 9.330862 26.35 17.12 0.00863159 10.91 10.91 0.00850000 31.30 0.00823349 18.45 32.2282 24.00 0.00882090 46.5802 126039.27 0.00 180066.64 163716.77
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 29917.590 29917.590 2.799258 0.00026173 514.304 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 29917.59 29917.59 2.799258 3.80 3.80 0.00505843 12.80 11.43 0.00800000 3.80 0.00505843 3.80 107.4274 21.00 0.00773405 49.0919 69046.25 0.00 30395.36 30395.36
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 93307.534 -999.000 5.626089 0.00396952 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 93307.53 88233.29 5.626089 24.27 16.55 0.00879872 11.27 11.27 0.00850000 25.28 0.00822398 16.41 21.3320 24.00 0.00895540 47.2810 75676.93 0.00 94760.38 83542.33
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 261828.028 261828.028 5.626089 0.00229059 5929.354 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 261828.03 261828.03 5.626089 0.81 0.81 0.00505843 40.00 20.96 0.00800000 3.80 0.00505843 3.80 21.3320 24.79 0.00505843 25.6219 0.00 0.00 224042.41 224042.41
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 427734.097 304842.545 21.680690 0.01047518 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 397442.20 395281.97 -999.0 28.48 17.77 0.00853750 12.80 11.93 0.00850000 31.30 0.00823349 18.45 -999.0000 27.00 0.00854232 37.7673 370832.86 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9238.262 6647.395 0.477450 0.00022624 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 8556.19 8459.06 -999.0 28.03 17.65 0.00857674 12.80 11.93 0.00850000 29.16 0.00823009 17.74 -999.0000 27.00 0.00858847 37.9663 8175.49 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 87938.878 63251.643 4.541627 0.00215362 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 81455.71 80486.31 -999.0 28.04 17.65 0.00858051 12.80 11.93 0.00850000 29.16 0.00823009 17.74 -999.0000 27.00 0.00859301 37.9863 77754.85 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 8965.041 6449.238 0.463128 0.00021955 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 8303.74 8206.64 -999.0 28.04 17.65 0.00857908 12.80 11.93 0.00850000 29.16 0.00823009 17.74 -999.0000 27.00 0.00859128 37.9786 7931.35 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 427734.097 427734.097 21.680690 0.01047518 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 427734.10 427734.10 21.680690 3.80 3.80 0.00505843 40.00 20.96 0.00800000 3.80 0.00505843 3.80 1.5608 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9238.262 9238.262 0.477450 0.00022624 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9238.26 9238.26 0.477450 3.80 3.80 0.00505843 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.2741 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 87938.878 87938.878 4.541627 0.00215362 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 87938.88 87938.88 4.541627 3.80 3.80 0.00505843 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.4420 24.89 0.00765726 38.3989 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 8965.041 8965.041 0.463128 0.00021955 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 8965.04 8965.04 0.463128 3.80 3.80 0.00505843 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.3754 23.76 0.00525367 28.2990 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 14546.909 14546.909 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 14546.91 14546.91 21.680690 0.06 0.06 0.00844628 40.00 20.96 0.00800000 3.80 0.00505843 3.80 1.5608 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 672.007 672.007 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 672.01 672.01 0.477450 0.12 0.12 0.00838732 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.2741 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6720.070 6720.070 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6720.07 6720.07 4.541627 0.13 0.13 0.00756781 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.4420 24.89 0.00765726 38.3989 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 672.007 672.007 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 672.01 672.01 0.463128 0.13 0.13 0.00524708 40.00 20.96 0.00800000 3.80 0.00505843 3.80 3.3754 23.76 0.00525367 28.2990 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 17552.691 17552.691 1.776300 0.00015356 353.848 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 1.0364 1.057264   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 17552.69 17552.69 1.0000 2.09919365 1.776300 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.15354294 60.00 32.22 27.78 0.000 17552.69 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.7558 0.00 0.00 17617.41 17617.41 2.09919365 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 353599.384 353599.384 16.771823 0.00309344 8033.884 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 20.8784 21.298613 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 353599.38 353599.38 1.0000 19.82058211 16.771823 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 3.09312610 60.00 32.22 27.78 0.000 353599.38 3.80 0.00505843 3.80 0.00000000 0.0000 20.56 0.00800000 21.00 0.00800000 50.7558 187866.91 0.00 354803.32 354803.32 19.82058211 12.80 11.60 0.00800000 33059.8 30.35 18.16 0.00800000 50960.6
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 68122.294 68122.294 2.062858 0.00059596 1799.580 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 4.0223 4.103260 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 68122.29 68122.29 1.0000 2.43784106 2.062858 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.59590275 60.00 32.22 27.78 0.000 68122.29 3.80 0.00505843 3.80 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 50.7558 47737.96 0.00 68367.44 68367.44 2.43784106 12.80 11.60 0.00800000 33059.8 40.30 21.27 0.00800000 61104.1
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 6366.365 6366.365 0.264322 0.00005570 149.838 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.3759 0.383470 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6366.37 6366.37 1.0000 0.31237033 0.264322 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.05569006 60.00 32.22 27.78 0.000 6366.37 3.80 0.00505843 3.80 0.00000000 0.0000 20.87 0.00667187 21.00 0.00667187 42.4236 3761.33 0.00 6387.21 6387.21 0.31237033 12.80 11.60 0.00800000 33059.8 32.85 18.97 0.00800000 53507.4
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 5673.927 5673.927 0.284102 0.00004964 127.285 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.3350 0.341762 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5673.93 5673.93 1.0000 0.33574579 0.284102 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04963292 60.00 32.22 27.78 0.000 5673.93 3.80 0.00505843 3.80 0.00000000 0.0000 20.87 0.00682198 21.00 0.00682198 43.3680 2873.22 0.00 5693.35 5693.35 0.33574579 12.80 11.60 0.00800000 33059.8 29.43 17.85 0.00800000 50017.1
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 9078.503 9078.503 0.349250 0.00007942 218.714 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.5360 0.546832 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9078.50 9078.50 1.0000 0.41273625 0.349250 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.07941460 60.00 32.22 27.78 0.000 9078.50 3.80 0.00505843 3.80 0.00000000 0.0000 20.86 0.00706926 21.00 0.00706926 44.9221 5633.97 0.00 9107.90 9107.90 0.41273625 12.80 11.60 0.00800000 33059.8 34.44 19.48 0.00800000 55126.9
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 4956.198 4956.198 0.363961 0.00004336 103.781 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.2926 0.298530 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4956.20 4956.20 1.0000 0.43012081 0.363961 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.04335456 60.00 32.22 27.78 0.000 4956.20 3.80 0.00505843 3.80 0.00000000 0.0000 20.87 0.00610385 21.00 0.00610385 38.8457 1372.68 0.00 4974.14 4974.14 0.43012081 12.80 11.60 0.00800000 33059.8 24.14 16.01 0.00800000 44624.3
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 159768.611 159768.611 4.852403 0.00139773 4214.863 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 9.4336 9.623461 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 159768.61 159768.61 1.0000 5.73446637 4.852403 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 1.39758292 60.00 32.22 27.78 0.000 159768.61 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00745838 21.00 0.00745838 47.3656 111877.17 0.00 160302.47 160302.47 5.73446637 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 106940.671 106940.671 3.248268 0.00093556 2821.077 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 6.3144 6.441436 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 106940.67 106940.67 1.0000 3.83873339 3.248268 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.93546820 60.00 32.22 27.78 0.000 106940.67 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00747416 21.00 0.00747416 47.4646 74880.49 0.00 107297.07 107297.07 3.83873339 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.0
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 160569.903 160569.903 4.876803 0.00140474 4235.977 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 9.4809 9.671725 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 160569.90 160569.90 1.0000 5.76330223 4.876803 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 1.40459226 60.00 32.22 27.78 0.000 160569.90 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00746190 21.00 0.00746190 47.3877 112437.31 0.00 161106.25 161106.25 5.76330223 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.6
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 98000.547 98000.547 3.100715 0.00085735 2539.118 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 5.7865 5.902939 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 98000.55 98000.55 1.0000 3.66435844 3.100715 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.85726407 60.00 32.22 27.78 0.000 98000.55 3.80 0.00505843 3.80 0.00000000 0.0000 20.91 0.00739015 21.00 0.00739015 46.9377 67401.93 0.00 98300.90 98300.90 3.66435844 12.80 11.60 0.00800000 33059.8 39.11 20.92 0.00800000 59886.1
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 21768.651 21768.651 0.661605 0.00019044 574.097 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 1.2853 1.311207 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 21768.65 21768.65 1.0000 0.78187116 0.661605 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.19042222 60.00 32.22 27.78 0.000 21768.65 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00758235 21.00 0.00758235 48.1432 15237.30 0.00 21840.07 21840.07 0.78187116 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60992.9
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 14422.123 14422.123 0.438351 0.00012617 380.339 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.8516 0.868698 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14422.12 14422.12 1.0000 0.51803426 0.438351 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.12615815 60.00 32.22 27.78 0.000 14422.12 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00758310 21.00 0.00758310 48.1479 10094.74 0.00 14469.37 14469.37 0.51803426 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.1
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 21856.523 21856.523 0.664281 0.00019121 576.412 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 1.2905 1.316500 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 21856.52 21856.52 1.0000 0.78503367 0.664281 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.19119089 60.00 32.22 27.78 0.000 21856.52 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00758418 21.00 0.00758418 48.1546 15298.73 0.00 21928.22 21928.22 0.78503367 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60992.7
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 13653.724 13653.724 0.414957 0.00011945 360.091 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 0.8062 0.822415 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13653.72 13653.72 1.0000 0.49038741 0.414957 12.80 11.43 0.00800000 33059.8 40.00 20.96 0.00800000 60796.0 0.11943655 60.00 32.22 27.78 0.000 13653.72 3.80 0.00505843 3.80 0.00000000 0.0000 20.95 0.00755511 21.00 0.00755511 47.9725 9557.52 0.00 13698.56 13698.56 0.49038741 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60994.0
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 176854.471 -999.000 9.311152 0.00752380 -999.000 -999.0000 1.00000 1.00000 1020.9390 1004.8586 1.1818 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.311152 11.00372113   4197.9300 999.8980 90.21022387 12.27 6.67 5.60 2120698.75 8.3394 8.339443 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 176854.47 172237.73 1.0000 11.00372113 9.311152 26.25 17.11 0.00866029 48462.6 10.91 10.91 0.00850000 32390.3 7.52303053 6.67 12.27 5.60 21264.137 155590.33 31.30 0.00823349 18.45 2.73523000 29.3758 24.00 0.00885103 24.00 0.00885103 46.7373 119617.85 0.00 179389.26 162355.13 11.00372113 26.25 17.31 0.00866029 48462.6 11.80 11.22 0.00804669 32160.0
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 29592.915 29592.915 2.793346 0.00025889 508.991 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.311152 11.00372113   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 1.7473 1.782492 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 29592.92 29592.92 1.0000 3.30111634 2.793346 3.88 3.86 0.00507145 16617.6 12.80 11.43 0.00800000 33059.8 0.25886532 60.00 32.22 27.78 0.000 29592.92 3.80 0.00505843 3.80 2.73523000 97.9195 7.59 0.00568408 21.77 0.00592028 35.9405 13641.19 0.00 30095.93 30095.93 3.30111634 2.80 2.80 0.00507145 15523.3 11.79 7.96 0.00507145 24640.2
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1673011.052 -999.000 86.245844 0.07117376 -999.000 -999.0000 1.00000 1.00000 1020.9138 1004.8586 1.1818 VAV_MID WITH REHEAT FAN Fan:VariableVolume 86.245844 101.92349825   4197.9300 999.8980 90.21022387 12.27 6.67 5.60 2120698.75 78.8896 78.889614 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 1673011.05 1633887.94 1.0000 101.92349825 86.245844 26.62 17.23 0.00864669 48804.6 10.91 10.91 0.00850000 32390.3 71.16649721 6.67 12.27 5.60 196962.032 1476049.02 31.30 0.00823349 18.45 28.63723000 33.2042 24.00 0.00887852 24.00 0.00887852 46.8803 1076255.13 0.00 1696701.53 1541546.93 101.92349825 26.62 17.43 0.00864669 48804.6 11.81 11.22 0.00804330 32157.8
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 276530.497 276530.497 25.873753 0.00241921 4753.754 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_MID WITH REHEAT FAN Fan:VariableVolume 86.245844 101.92349825   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 16.3279 16.656465 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 276530.50 276530.50 1.0000 30.57704947 25.873753 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 2.41896264 60.00 32.22 27.78 0.000 276530.50 3.80 0.00505843 3.80 28.63723000 110.6806 20.79 0.00767229 21.00 0.00763456 48.4691 554463.80 0.00 280946.59 280946.59 30.57704947 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 177525.691 -999.000 9.330862 0.00755235 -999.000 -999.0000 1.00000 1.00000 1020.8857 1004.8586 1.1818 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.330862 11.02701315   4197.9300 999.8980 90.21022387 12.27 6.67 5.60 2120698.75 8.3711 8.371094 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 177525.69 173727.40 1.0000 11.02701315 9.330862 26.35 17.12 0.00863159 48489.4 10.91 10.91 0.00850000 32390.2 7.55158287 6.67 12.27 5.60 21309.148 156216.54 31.30 0.00823349 18.45 3.00717000 32.2282 24.00 0.00882090 24.00 0.00882090 46.5802 126039.27 0.00 180066.64 163716.77 11.02701315 26.35 17.32 0.00863159 48489.4 11.81 11.22 0.00804389 32159.8
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 29917.590 29917.590 2.799258 0.00026173 514.304 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.330862 11.02701315   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 1.7665 1.802048 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 29917.59 29917.59 1.0000 3.30810395 2.799258 3.80 3.80 0.00505843 16505.0 12.80 11.43 0.00800000 33059.8 0.26170543 60.00 32.22 27.78 0.000 29917.59 3.80 0.00505843 3.80 3.00717000 107.4274 21.00 0.00773405 21.00 0.00773405 49.0919 69046.25 0.00 30395.36 30395.36 3.30810395 2.80 2.80 0.00505843 15490.7 11.86 7.98 0.00505843 24678.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 93307.534 -999.000 5.626089 0.00396952 -999.000 -999.0000 1.00000 1.00000 1021.1964 1004.8586 1.1818 CAV_BAS FAN Fan:ConstantVolume 5.626089 6.64879192   4197.9300 999.8980 90.21022387 12.27 6.67 5.60 2120698.75 4.3998 4.399849 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 93307.53 88233.29 1.0000 6.64879192 5.626089 24.27 16.55 0.00879872 46792.2 11.27 11.27 0.00850000 32758.4 3.96911327 6.67 12.27 5.60 10402.925 82904.61 25.28 0.00822398 16.41 1.20015641 21.3320 24.00 0.00895540 24.00 0.00895540 47.2810 75676.93 0.00 94760.38 83542.33 6.64879192 24.27 16.74 0.00879872 46792.2 11.97 11.38 0.00813003 32539.9
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 261828.028 261828.028 5.626089 0.00229059 5929.354 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 CAV_BAS FAN Fan:ConstantVolume 5.626089 6.64879192   4197.9300 999.8980 14.52266474 54.44 82.22 27.78 1693611.31 15.4597 15.770881 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 261828.03 261828.03 1.0000 6.64879192 5.626089 0.81 0.81 0.00505843 13473.0 40.00 20.96 0.00800000 60796.0 2.29035214 60.00 32.22 27.78 0.000 261828.03 3.80 0.00505843 3.80 1.20015641 21.3320 0.00 0.00505843 24.79 0.00505843 25.6219 0.00 0.00 224042.41 224042.41 6.64879192 12.80 8.42 0.00505843 25633.1 46.02 20.83 0.00505843 59329.9
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 427734.097 304842.545 21.680690 0.01047518 -999.000 -999.0000 -999.00000 -999.00000 1020.7108 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 397442.20 395281.97 0.9292 -999.0 -999.0 28.48 17.77 0.00853750 50425.7 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 397442.20 31.30 0.00823349 18.45 0.33839277 -999.0000 27.00 0.00854232 27.00 0.00854232 37.7673 370832.86 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9238.262 6647.395 0.477450 0.00022624 -999.000 -999.0000 -999.00000 -999.00000 1020.7837 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 Sensible 8556.19 8459.06 0.9262 -999.0 -999.0 28.03 17.65 0.00857674 50065.8 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8556.19 29.16 0.00823009 17.74 0.01563234 -999.0000 27.00 0.00858847 27.00 0.00858847 37.9663 8175.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 87938.878 63251.643 4.541627 0.00215362 -999.000 -999.0000 -999.00000 -999.00000 1020.7907 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 Sensible 81455.71 80486.31 0.9263 -999.0 -999.0 28.04 17.65 0.00858051 50079.1 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 81455.71 29.16 0.00823009 17.74 0.15632344 -999.0000 27.00 0.00859301 27.00 0.00859301 37.9863 77754.85 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 8965.041 6449.238 0.463128 0.00021955 -999.000 -999.0000 -999.00000 -999.00000 1020.7881 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 8303.74 8206.64 0.9262 -999.0 -999.0 28.04 17.65 0.00857908 50074.0 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8303.74 29.16 0.00823009 17.74 0.01563234 -999.0000 27.00 0.00859128 27.00 0.00859128 37.9786 7931.35 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 427734.097 427734.097 21.680690 0.01047518 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 427734.10 427734.10 1.0000 25.62177724 21.680690 3.80 3.80 0.00505843 16505.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 427734.10 3.80 0.00505843 3.80 0.33839277 1.5608 0.00 0.00850000 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9238.262 9238.262 0.477450 0.00022624 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9238.26 9238.26 1.0000 0.56424049 0.477450 3.80 3.80 0.00505843 16505.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9238.26 3.80 0.00505843 3.80 0.01563234 3.2741 0.00 0.00850000 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 87938.878 87938.878 4.541627 0.00215362 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 87938.88 87938.88 1.0000 5.36719769 4.541627 3.80 3.80 0.00505843 16505.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 87938.88 3.80 0.00505843 3.80 0.15632344 3.4420 0.00 0.00765726 24.89 0.00765726 38.3989 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8965.041 8965.041 0.463128 0.00021955 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 8965.04 8965.04 1.0000 0.54731423 0.463128 3.80 3.80 0.00505843 16505.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8965.04 3.80 0.00505843 3.80 0.01563234 3.3754 0.00 0.00525367 23.76 0.00525367 28.2990 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 14546.909 14546.909 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.680690 25.62177724   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 14546.91 14546.91 1.0000 25.62177724 21.680690 0.06 0.06 0.00844628 21184.2 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14546.91 3.80 0.00505843 3.80 0.33839277 1.5608 0.00 0.00850000 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 672.007 672.007 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.477450 0.56424049   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 672.01 672.01 1.0000 0.56424049 0.477450 0.12 0.12 0.00838732 21103.1 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 672.01 3.80 0.00505843 3.80 0.01563234 3.2741 0.00 0.00850000 27.00 0.00850000 37.5769 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6720.070 6720.070 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.541627 5.36719769   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6720.07 6720.07 1.0000 5.36719769 4.541627 0.13 0.13 0.00756781 19059.9 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6720.07 3.80 0.00505843 3.80 0.15632344 3.4420 0.00 0.00765726 24.89 0.00765726 38.3989 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 672.007 672.007 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.463128 0.54731423   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 672.01 672.01 1.0000 0.54731423 0.463128 0.13 0.13 0.00524708 13252.8 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 672.01 3.80 0.00505843 3.80 0.01563234 3.3754 0.00 0.00525367 23.76 0.00525367 28.2990 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 2.74 9.31 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 28.64 86.25 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 3.01 9.33 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.63 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 4357.00 401.67 284.33
CORE_BOTTOM 4473.50 108.67 14.33
CORE_MID 3553.17 646.50 20.83
CORE_TOP 2700.83 2051.33 21.00
PERIMETER_BOT_ZN_3 2845.17 1643.33 0.00
PERIMETER_BOT_ZN_2 2746.17 2012.83 39.33
PERIMETER_BOT_ZN_1 3639.67 1199.67 62.50
PERIMETER_BOT_ZN_4 4506.17 722.67 202.50
PERIMETER_MID_ZN_3 1910.83 3090.17 44.50
PERIMETER_MID_ZN_2 1698.17 2738.00 68.17
PERIMETER_MID_ZN_1 2965.00 1957.33 69.33
PERIMETER_MID_ZN_4 2476.00 2747.17 73.83
PERIMETER_TOP_ZN_3 1875.67 3865.50 422.67
PERIMETER_TOP_ZN_2 2107.17 3444.17 237.50
PERIMETER_TOP_ZN_1 2538.83 2738.17 168.33
PERIMETER_TOP_ZN_4 2241.33 3385.33 285.33
DATACENTER_BOT_ZN_6 5943.00 1128.50 1128.50
DATACENTER_MID_ZN_6 5943.00 35.33 35.33
DATACENTER_TOP_ZN_6 5910.50 198.17 187.17
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 70.33 0.00 5.17
CORE_BOTTOM 0.00 3.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 0.00 5.17 0.00 5.17
PERIMETER_BOT_ZN_1 0.00 22.00 0.00 22.00
PERIMETER_BOT_ZN_4 0.00 72.83 0.00 35.33
PERIMETER_MID_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 0.00 3.83 0.00 3.83
PERIMETER_MID_ZN_1 0.00 23.17 0.00 23.17
PERIMETER_MID_ZN_4 0.00 10.50 0.00 8.83
PERIMETER_TOP_ZN_3 3.50 0.00 0.17 0.00
PERIMETER_TOP_ZN_2 2.83 1.67 0.00 1.67
PERIMETER_TOP_ZN_1 1.50 10.33 0.00 10.17
PERIMETER_TOP_ZN_4 1.67 10.33 0.00 8.33
DATACENTER_BOT_ZN_6 0.00 6.00 0.00 6.00
DATACENTER_MID_ZN_6 0.00 1.50 0.00 1.50
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 128.83 0.00 128.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 3.50 334.33 0.17 229.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.54 149.60 6779.02 1.952 0.000 0.000 0.000
CORE_BOTTOM 56.16 134.35 6849.35 1.439 0.000 0.000 0.000
CORE_MID 56.16 134.35 6849.35 1.144 0.000 0.000 0.000
CORE_TOP 56.16 134.35 6849.35 1.057 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.05 16.87 860.00 1.339 0.054 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 1.915 0.055 0.000 0.000
PERIMETER_BOT_ZN_1 7.05 16.87 860.02 1.987 0.054 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 2.876 0.056 0.000 0.000
PERIMETER_MID_ZN_3 7.05 16.87 860.00 1.052 0.125 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 1.699 0.134 0.000 0.000
PERIMETER_MID_ZN_1 7.05 16.87 860.02 1.787 0.126 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 2.013 0.130 0.000 0.000
PERIMETER_TOP_ZN_3 7.05 16.87 860.00 1.142 0.155 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 1.844 0.161 0.000 0.000
PERIMETER_TOP_ZN_1 7.05 16.87 860.02 1.819 0.156 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 2.144 0.161 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.63 42.18 1911.37 0.482 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.54 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.16 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.05 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.05 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.63 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.54 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.16 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.97 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.05 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.05 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.63 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1036.48 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 80360299.67 0.00 80360299.67 0.00 80360299.67 37848132.68 3753.04 337.18 4669.78 466.23
CORE_BOTTOM 61106585.33 0.00 61106585.33 0.00 61106585.33 33990283.35 3179.85 6.96 5573.19 629.55
CORE_MID 0.47E+09 0.00 0.47E+09 0.00 0.47E+09 0.34E+09 3788.68 6.75 4964.57 181.53
CORE_TOP 42390220.73 0.00 42390220.73 0.00 42390220.73 33990283.35 4010.04 3.47 4746.50 95.92
PERIMETER_BOT_ZN_3 7213368.56 0.00 7213368.56 464654.29 7678022.84 4267819.30 3149.59 3.54 5606.88 629.55
PERIMETER_BOT_ZN_2 6734345.99 0.00 6734345.99 309769.31 7044115.30 2750345.05 3132.36 0.00 5627.64 629.55
PERIMETER_BOT_ZN_1 10625120.58 0.00 10625120.58 464654.29 11089774.87 4267912.63 3132.36 0.00 5627.64 629.55
PERIMETER_BOT_ZN_4 9997389.76 0.00 9997389.76 309769.31 10307159.07 2750345.05 3132.36 0.00 5627.64 629.55
PERIMETER_MID_ZN_3 53991191.88 0.00 53991191.88 1089732.13 55080924.01 42678193.03 3758.51 5.44 4996.05 181.53
PERIMETER_MID_ZN_2 59970800.19 0.00 59970800.19 726487.59 60697287.78 27503450.52 3724.11 0.00 5035.89 1090.53
PERIMETER_MID_ZN_1 91266560.21 0.00 91266560.21 1089732.13 92356292.34 42679126.28 3725.69 0.17 5034.14 181.53
PERIMETER_MID_ZN_4 66652549.54 0.00 66652549.54 726487.59 67379037.13 27503450.52 3724.11 0.00 5035.89 181.53
PERIMETER_TOP_ZN_3 5782426.70 0.00 5782426.70 1353003.24 7135429.94 4267819.30 3946.86 1.59 4811.55 95.92
PERIMETER_TOP_ZN_2 6014641.27 0.00 6014641.27 902001.54 6916642.81 2750345.05 3876.57 0.67 4882.75 95.92
PERIMETER_TOP_ZN_1 9185207.59 0.00 9185207.59 1353003.24 10538210.83 4267912.63 3896.54 4.14 4859.32 95.92
PERIMETER_TOP_ZN_4 6994048.46 0.00 6994048.46 902001.54 7896050.00 2750345.05 3872.64 0.26 4887.10 95.92
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.77E+10 0.00 0.77E+10 42383251.12 0.77E+10 0.50E+10 4420.17 4377.21 5846.39 1739.64


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 3.5862 0.0000 3.5862 0.0000 3.5862 1.2002 1278.05 333.05 4331.90
CORE_BOTTOM 2.6718 0.0000 2.6718 0.0000 2.6718 1.0778 954.90 1.76 4986.34
CORE_MID 21.2339 0.0000 21.2339 0.0000 21.2339 10.7782 1141.30 4.99 4796.72
CORE_TOP 1.9612 0.0000 1.9612 0.0000 1.9612 1.0778 1243.71 3.22 4696.08
PERIMETER_BOT_ZN_3 0.3122 0.0000 0.3122 0.0125 0.3247 0.1353 954.31 1.55 4987.13
PERIMETER_BOT_ZN_2 0.2880 0.0000 0.2880 0.0083 0.2963 0.0872 944.91 0.00 4998.09
PERIMETER_BOT_ZN_1 0.4637 0.0000 0.4637 0.0125 0.4762 0.1353 944.91 0.00 4998.09
PERIMETER_BOT_ZN_4 0.4320 0.0000 0.4320 0.0083 0.4404 0.0872 944.91 0.00 4998.09
PERIMETER_MID_ZN_3 2.4547 0.0000 2.4547 0.0293 2.4841 1.3533 1118.97 4.37 4819.65
PERIMETER_MID_ZN_2 2.5592 0.0000 2.5592 0.0202 2.5794 0.8721 1088.64 0.00 3945.36
PERIMETER_MID_ZN_1 4.1724 0.0000 4.1724 0.0293 4.2017 1.3533 1089.97 0.17 4852.86
PERIMETER_MID_ZN_4 3.0289 0.0000 3.0289 0.0196 3.0484 0.8721 1088.64 0.00 4854.36
PERIMETER_TOP_ZN_3 0.2669 0.0000 0.2669 0.0364 0.3033 0.1353 1190.91 1.03 4751.06
PERIMETER_TOP_ZN_2 0.2778 0.0000 0.2778 0.0243 0.3020 0.0872 1149.60 0.29 4793.11
PERIMETER_TOP_ZN_1 0.4250 0.0000 0.4250 0.0364 0.4614 0.1353 1158.35 2.19 4782.46
PERIMETER_TOP_ZN_4 0.3230 0.0000 0.3230 0.0243 0.3472 0.0872 1147.66 0.00 4795.34
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 346.9107 0.0000 346.9107 1.1472 348.0579 158.4706 1603.17 4359.99 5081.98


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 0.13E+09 0.00 0.13E+09 48026705.38 3132.36 0.00 5627.64 629.55
VAV_MID WITH REHEAT 0.10E+10 0.00 0.10E+10 0.48E+09 3724.26 0.39 5035.36 181.53
VAV_TOP WITH REHEAT 98273985.22 0.00 98273985.22 48026705.38 3901.75 4.22 4854.04 95.92
CAV_BAS 0.11E+09 0.00 0.11E+09 37848132.68 3696.05 2.23 5061.72 466.23
AIRLOOP DATACENTER BASEMENT 7385597.71 0.00 7385597.71 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 341184.02 0.00 341184.02 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3411840.17 0.00 3411840.17 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 341184.02 0.00 341184.02 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 5.8206 0.0000 5.8206 1.5229 944.91 0.00 4998.09
VAV_MID WITH REHEAT 46.9435 0.0000 46.9435 15.2292 1088.64 0.29 4854.08
VAV_TOP WITH REHEAT 4.5443 0.0000 4.5443 1.5229 1161.29 1.98 4779.73
CAV_BAS 5.0086 0.0000 5.0086 1.2002 1270.44 0.85 4671.71
AIRLOOP DATACENTER BASEMENT 0.3452 0.0000 0.3452 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0159 0.0000 0.0159 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1595 0.0000 0.1595 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0159 0.0000 0.0159 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 405.61 5222.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 507.39 3965.42 0.00 563.08 0.00 0.00 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 254.31 3261.10 0.00 1377.78 0.00 0.00 0.00 0.00 0.00
CAV_BAS 0.00 332.67 4816.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 3.8258 7.1957 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 40.0255 62.4341 0.0000 39.9724 0.0000 0.0000 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 4.2049 6.3697 0.0000 4.1964 0.0000 0.0000 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6795 6.7145 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4727 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0218 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2184 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0218 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1335
Defaulted Fields 1179
Fields with Defaults 3690
Autosized Fields 333
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
Electricity:Building 19155.85 253334.51 01-JAN-00:10 1138237.68 03-APR-07:10
Electricity:Zone:BASEMENT 660.02 14600.60 01-JAN-00:10 34031.28 02-JAN-08:10
Electricity:SpaceType:GENERAL 19155.85 253334.51 01-JAN-00:10 1138237.68 03-APR-07:10
InteriorLights:Electricity 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 235.63 1143.06 01-JAN-00:10 20573.73 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
LightsWired:InteriorLights:Electricity 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 235.63 1143.06 01-JAN-00:10 20573.73 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 3942.44 19125.25 01-JAN-00:10 344233.60 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 532.90 7069.41 01-JAN-00:10 36605.25 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
Electricity:Zone:CORE_MID 5328.94 70693.84 01-JAN-00:10 366051.79 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 2116.10 10265.44 01-JAN-00:10 184766.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 2116.10 10265.44 01-JAN-00:10 184766.59 02-JAN-08:10
Electricity:Zone:CORE_TOP 532.89 7069.38 01-JAN-00:10 36605.18 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 211.61 1026.54 01-JAN-00:10 18476.66 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 66.91 887.67 01-JAN-00:10 4596.25 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 43.12 572.05 01-JAN-00:10 2962.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 66.91 887.68 01-JAN-00:10 4596.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 43.12 572.04 01-JAN-00:10 2961.99 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 669.12 8876.66 01-JAN-00:10 45962.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 265.70 1288.93 01-JAN-00:10 23199.29 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 265.70 1288.93 01-JAN-00:10 23199.29 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 431.21 5720.45 01-JAN-00:10 29619.96 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 669.13 8876.80 01-JAN-00:10 45963.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 265.70 1288.96 01-JAN-00:10 23199.80 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 265.70 1288.96 01-JAN-00:10 23199.80 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 431.20 5720.42 01-JAN-00:10 29619.87 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 171.23 830.63 01-JAN-00:10 14950.50 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 66.91 887.67 01-JAN-00:10 4596.25 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 26.57 128.89 01-JAN-00:10 2319.93 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 43.12 572.05 01-JAN-00:10 2962.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 66.91 887.68 01-JAN-00:10 4596.33 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 26.57 128.90 01-JAN-00:10 2319.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 43.12 572.04 01-JAN-00:10 2961.99 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 17.12 83.06 01-JAN-00:10 1495.05 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7561.29 95230.42 01-JAN-00:10 385433.43 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 66.44 322.29 01-JAN-00:10 5800.91 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 66.44 322.29 01-JAN-00:10 5800.91 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.25 1969.80 01-JAN-00:10 8176.00 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1582.51 19698.04 01-JAN-00:10 81759.99 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 43.70 211.99 01-JAN-00:10 3815.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 43.70 211.99 01-JAN-00:10 3815.77 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.25 1969.80 01-JAN-00:10 8176.00 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.37 21.20 01-JAN-00:10 381.58 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 2979.33 7150.42 08-JAN-07:00 442261.00 18-AUG-15:50
HeatRejection:Electricity 1391.89 3759.54 08-JAN-07:00 82101.62 13-JAN-13:50
General:HeatRejection:Electricity 1391.89 3759.54 08-JAN-07:00 82101.62 13-JAN-13:50
Electricity:HVAC 5027.23 76595.14 01-JAN-06:50 368994.08 17-AUG-14:20
ExteriorEquipment:Electricity 1997.59 30702.09 01-JAN-00:10 120520.01 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 87.51 1613.62 01-JAN-00:10 5474.05 03-APR-07:20
ElectricityPurchased:Facility 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
ElectricityPurchased:Plant 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
Cogeneration:ElectricityPurchased 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
General:Cogeneration:ElectricityPurchased 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
ElectricityNet:Plant 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
Cogeneration:ElectricityNet 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
General:Cogeneration:ElectricityNet 29977.77 382421.69 01-JAN-10:10 2015457.69 18-AUG-15:50
Fans:Electricity 2462.16 41897.47 01-JAN-00:10 205774.29 31-JUL-15:00
General:Fans:Electricity 2462.16 41897.47 01-JAN-00:10 205774.29 31-JUL-15:00
ExteriorLights:Electricity 905.27 0.00 01-JAN-07:00 57580.60 01-JAN-00:10
General:ExteriorLights:Electricity 905.27 0.00 01-JAN-07:00 57580.60 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 61.31 1944.00 01-JAN-00:10 1944.00 01-JAN-00:10
Cooling:Electricity 3391.36 30837.49 03-JAN-07:10 448084.30 18-AUG-15:50
General:Cooling:Electricity 3391.36 30837.49 03-JAN-07:10 448084.30 18-AUG-15:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 2.77 0.00 01-JAN-00:10 6835.20 19-DEC-10:40
General:Humidifier:Electricity 2.77 0.00 01-JAN-00:10 6835.20 19-DEC-10:40
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 670.87 3334.68 01-JAN-00:10 67222.11 29-SEP-12:30
General:Pumps:Electricity 670.87 3334.68 01-JAN-00:10 67222.11 29-SEP-12:30
WIRED_LTG_ELECTRICITY 110.78 0.00 01-JAN-00:10 9672.96 02-JAN-08:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1211.02 8146.58 30-APR-16:00 783896.78 09-JAN-07:10
NaturalGas:Plant 1211.02 8146.58 30-APR-16:00 783896.78 09-JAN-07:10
Heating:NaturalGas 469.15 0.00 01-JAN-00:10 752660.69 09-JAN-07:10
Boiler:Heating:NaturalGas 469.15 0.00 01-JAN-00:10 752660.69 09-JAN-07:10
WaterSystems:NaturalGas 741.87 8146.58 02-JAN-05:10 78860.74 02-FEB-13:00
Water Heater:WaterSystems:NaturalGas 741.87 8146.58 02-JAN-05:10 78860.74 02-FEB-13:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 18453.81 152646.94 03-JAN-07:10 2669759.43 18-AUG-15:50
PlantLoopCoolingDemand:HVAC 18453.81 152646.94 03-JAN-07:10 2669759.43 18-AUG-15:50
CoolingCoils:PlantLoopCoolingDemand 18453.81 152646.94 03-JAN-07:10 2669759.43 18-AUG-15:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 6381.37 0.00 01-JAN-00:10 0.00 16-OCT-11:10
Water:HVAC 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
Humidifier:Water 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
General:Humidifier:Water 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
MainsWater:Facility 6381.37 0.00 01-JAN-00:10 0.00 16-OCT-11:10
MainsWater:HVAC 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
Humidifier:MainsWater 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
General:Humidifier:MainsWater 1.03 0.00 01-JAN-00:10 0.00 19-DEC-10:40
Water:Plant 6380.34 0.00 01-JAN-00:10 0.00 16-OCT-11:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 6380.34 0.00 01-JAN-00:10 0.00 16-OCT-11:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 4100.17 0.00 01-JAN-00:10 0.00 16-OCT-11:00
General:HeatRejection:Water 4100.17 0.00 01-JAN-00:10 0.00 16-OCT-11:00
HeatRejection:MainsWater 4100.17 0.00 01-JAN-00:10 0.00 16-OCT-11:00
General:HeatRejection:MainsWater 4100.17 0.00 01-JAN-00:10 0.00 16-OCT-11:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 55258.54 227916.80 01-JAN-05:30 10350640.76 18-AUG-15:50
EnergyTransfer:Building 19624.64 93337.60 01-JAN-07:30 1488650.89 14-AUG-15:20
EnergyTransfer:Zone:BASEMENT 704.05 0.00 01-JAN-00:10 72037.57 13-NOV-06:10
Heating:EnergyTransfer 29.23 0.00 02-JAN-22:10 162488.38 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 3.87 0.00 01-JAN-00:10 16819.07 14-OCT-16:10
General:Heating:EnergyTransfer 29.23 0.00 02-JAN-22:10 162488.38 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 3.87 0.00 01-JAN-00:10 16819.07 14-OCT-16:10
Cooling:EnergyTransfer 19595.41 92813.62 01-JAN-07:00 1488650.89 14-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 700.17 0.00 01-JAN-00:10 72037.57 13-NOV-06:10
General:Cooling:EnergyTransfer 19595.41 92813.62 01-JAN-07:00 1488650.89 14-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 700.17 0.00 01-JAN-00:10 72037.57 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 682.06 0.00 01-JAN-00:10 54238.36 26-DEC-10:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 682.06 0.00 01-JAN-00:10 54238.36 26-DEC-10:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 682.06 0.00 01-JAN-00:10 54238.36 26-DEC-10:20
EnergyTransfer:Zone:CORE_MID 5033.32 0.00 01-JAN-00:10 455238.04 02-OCT-10:00
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5033.32 0.00 01-JAN-00:10 455238.04 02-OCT-10:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 5033.32 0.00 01-JAN-00:10 455238.04 02-OCT-10:00
EnergyTransfer:Zone:CORE_TOP 438.16 0.00 01-JAN-00:10 52259.11 16-OCT-14:00
Heating:EnergyTransfer:Zone:CORE_TOP 0.18 0.00 01-JAN-00:10 30548.57 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.18 0.00 01-JAN-00:10 30548.57 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 437.98 0.00 01-JAN-00:10 52259.11 16-OCT-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 437.98 0.00 01-JAN-00:10 52259.11 16-OCT-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 78.39 0.00 01-JAN-00:10 9078.35 16-OCT-11:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 78.39 0.00 01-JAN-00:10 9078.35 16-OCT-11:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 78.39 0.00 01-JAN-00:10 9078.35 16-OCT-11:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.06 0.00 01-JAN-00:10 9628.89 16-OCT-08:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.06 0.00 01-JAN-00:10 9628.89 16-OCT-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 71.06 0.00 01-JAN-00:10 9628.89 16-OCT-08:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.97 0.00 01-JAN-00:10 16630.49 16-OCT-12:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.97 0.00 01-JAN-00:10 16630.49 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 116.97 0.00 01-JAN-00:10 16630.49 16-OCT-12:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 110.57 0.00 01-JAN-00:10 13621.62 26-APR-15:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 110.57 0.00 01-JAN-00:10 13621.62 26-APR-15:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 110.57 0.00 01-JAN-00:10 13621.62 26-APR-15:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 545.25 0.00 01-JAN-00:10 80648.96 16-OCT-12:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.72 0.00 01-JAN-00:10 41666.01 03-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.72 0.00 01-JAN-00:10 41666.01 03-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 544.53 0.00 01-JAN-00:10 80648.96 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 544.53 0.00 01-JAN-00:10 80648.96 16-OCT-12:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 593.01 0.00 01-JAN-00:10 94424.24 19-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.38 0.00 01-JAN-00:10 29192.80 30-MAR-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.38 0.00 01-JAN-00:10 29192.80 30-MAR-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 592.62 0.00 01-JAN-00:10 94424.24 19-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 592.62 0.00 01-JAN-00:10 94424.24 19-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 974.27 0.00 01-JAN-00:10 162685.69 16-OCT-12:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.20 0.00 01-JAN-00:10 40396.14 30-MAR-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.20 0.00 01-JAN-00:10 40396.14 30-MAR-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 974.08 0.00 01-JAN-00:10 162685.69 16-OCT-12:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 974.08 0.00 01-JAN-00:10 162685.69 16-OCT-12:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 665.72 0.00 01-JAN-00:10 110609.86 29-SEP-15:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.13 0.00 01-JAN-00:10 24666.22 30-MAR-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.13 0.00 01-JAN-00:10 24666.22 30-MAR-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 665.58 0.00 01-JAN-00:10 110609.86 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 665.58 0.00 01-JAN-00:10 110609.86 29-SEP-15:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 53.53 0.00 01-JAN-00:10 10320.09 02-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.13 0.00 01-JAN-00:10 10320.09 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.13 0.00 01-JAN-00:10 10320.09 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.40 0.00 01-JAN-00:10 9007.22 16-OCT-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 51.40 0.00 01-JAN-00:10 9007.22 16-OCT-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 56.02 0.00 01-JAN-00:10 9443.44 19-JUL-09:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.93 0.00 01-JAN-00:10 6522.69 30-MAR-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.93 0.00 01-JAN-00:10 6522.69 30-MAR-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 55.09 0.00 01-JAN-00:10 9443.44 19-JUL-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 55.09 0.00 01-JAN-00:10 9443.44 19-JUL-09:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 91.23 0.00 01-JAN-00:10 17841.07 16-OCT-13:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.83 0.00 01-JAN-00:10 9058.90 30-MAR-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.83 0.00 01-JAN-00:10 9058.90 30-MAR-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 90.41 0.00 01-JAN-00:10 17841.07 16-OCT-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 90.41 0.00 01-JAN-00:10 17841.07 16-OCT-13:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 63.91 0.00 01-JAN-00:10 11716.12 29-SEP-15:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.58 0.00 01-JAN-00:10 5698.15 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.58 0.00 01-JAN-00:10 5698.15 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 63.33 0.00 01-JAN-00:10 11716.12 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 63.33 0.00 01-JAN-00:10 11716.12 29-SEP-15:30
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 76.65 0.00 01-JAN-00:10 9003.60 16-OCT-16:00
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.15 0.00 01-JAN-00:10 3321.14 18-DEC-04:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.15 0.00 01-JAN-00:10 3321.14 18-DEC-04:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 75.50 0.00 01-JAN-00:10 9003.60 16-OCT-16:00
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 75.50 0.00 01-JAN-00:10 9003.60 16-OCT-16:00
EnergyTransfer:Zone:MIDFLOOR_PLENUM 484.94 0.00 01-JAN-00:10 69040.06 16-OCT-16:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.71 0.00 01-JAN-00:10 28209.59 02-APR-14:40
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.71 0.00 01-JAN-00:10 28209.59 02-APR-14:40
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 477.23 0.00 01-JAN-00:10 69040.06 16-OCT-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 477.23 0.00 01-JAN-00:10 69040.06 16-OCT-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 80.14 0.00 01-JAN-00:10 18809.70 29-SEP-13:00
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 10.28 0.00 01-JAN-00:10 11110.19 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 10.28 0.00 01-JAN-00:10 11110.19 09-JAN-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.86 0.00 01-JAN-00:10 18809.70 29-SEP-13:00
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 69.86 0.00 01-JAN-00:10 18809.70 29-SEP-13:00
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.20 1116.94 09-JAN-07:00 7895.55 06-AUG-17:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.20 1116.94 09-JAN-07:00 7895.55 06-AUG-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.20 1116.94 09-JAN-07:00 7895.55 06-AUG-17:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1279.62 2378.84 02-JAN-06:00 73500.51 06-AUG-17:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1279.62 2378.84 02-JAN-06:00 73500.51 06-AUG-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1279.62 2378.84 02-JAN-06:00 73500.51 06-AUG-17:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 119.98 0.16 13-JAN-08:00 7499.12 20-AUG-17:30
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.13 0.00 02-JAN-10:20 541.29 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.13 0.00 02-JAN-10:20 541.29 08-JAN-07:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 119.85 0.00 01-JAN-00:10 7499.12 20-AUG-17:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 119.85 0.00 01-JAN-00:10 7499.12 20-AUG-17:30
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7164.58 87418.34 14-MAY-05:00 369050.75 18-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7164.58 87418.34 14-MAY-05:00 369050.75 18-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7164.58 87418.34 14-MAY-05:00 369050.75 18-DEC-17:00
PlantLoopHeatingDemand:Facility 704.06 0.00 01-JAN-00:10 518317.87 09-JAN-07:10
PlantLoopHeatingDemand:Plant 377.81 0.00 01-JAN-00:10 43844.35 03-FEB-13:00
WaterSystems:PlantLoopHeatingDemand 377.81 0.00 01-JAN-00:10 43844.35 03-FEB-13:00
General:WaterSystems:PlantLoopHeatingDemand 377.81 0.00 01-JAN-00:10 43844.35 03-FEB-13:00
EnergyTransfer:HVAC 16305.26 133904.40 02-JAN-06:00 2518625.86 18-AUG-15:50
HeatingCoils:EnergyTransfer 326.24 0.00 01-JAN-00:10 503867.32 09-JAN-07:10
PlantLoopHeatingDemand:HVAC 326.24 0.00 01-JAN-00:10 503867.32 09-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 326.24 0.00 01-JAN-00:10 503867.32 09-JAN-07:10
CoolingCoils:EnergyTransfer 15979.02 121809.46 03-JAN-07:10 2518625.86 18-AUG-15:50
EnergyTransfer:Plant 19328.64 0.00 01-JAN-00:10 6357219.82 18-AUG-15:50
LoopToLoop:EnergyTransfer 6278.47 -0.00 02-JAN-04:10 2027158.25 18-AUG-15:50
WaterSystems:EnergyTransfer 377.81 0.00 01-JAN-00:10 43844.35 03-FEB-13:00
WaterUse:WaterSystems:EnergyTransfer 377.81 0.00 01-JAN-00:10 43844.35 03-FEB-13:00
Boilers:EnergyTransfer 323.01 0.00 01-JAN-00:10 597320.42 09-JAN-07:10
Chillers:EnergyTransfer 5716.39 0.00 01-JAN-00:10 2001327.07 18-AUG-15:50
HeatRejection:EnergyTransfer 6632.96 0.00 01-JAN-00:10 2298277.80 18-AUG-15:50
General:HeatRejection:EnergyTransfer 6632.96 0.00 01-JAN-00:10 2298277.80 18-AUG-15:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 3.872 -700.179 0.000 0.000 92.698 235.627 424.397 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -56.415
CORE_BOTTOM 0.000 0.000 0.000 -682.059 0.000 0.000 83.378 211.610 321.286 0.000 0.000 0.000 65.786 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 0.000 -5033.349 0.000 0.000 835.265 2116.097 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1130.858
CORE_TOP 0.000 0.000 0.179 -437.978 0.000 0.000 84.511 211.610 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -179.606
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -78.394 0.000 0.000 10.544 26.570 40.342 16.002 0.000 0.037 30.201 0.000 -40.544 0.000 -4.759 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -71.064 0.000 0.000 6.832 17.123 25.998 38.353 0.000 0.024 10.918 0.000 -25.086 0.000 -3.098 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -116.976 0.000 0.000 10.543 26.570 40.343 75.789 0.000 0.033 7.991 0.000 -39.447 0.000 -4.847 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -110.574 0.000 0.000 6.773 17.123 25.998 42.651 0.000 0.023 51.385 0.000 -29.820 0.000 -3.558 0.000
PERIMETER_MID_ZN_3 0.000 0.000 0.724 -544.531 0.000 0.000 107.782 265.697 403.423 170.171 0.000 0.947 65.333 0.000 -370.697 0.000 -98.850 0.000
PERIMETER_MID_ZN_2 0.000 0.000 0.383 -592.630 0.000 0.000 51.297 171.225 259.981 385.374 0.000 0.566 29.918 0.000 -238.464 0.000 -67.650 -0.007
PERIMETER_MID_ZN_1 0.000 0.000 0.198 -974.095 0.000 0.000 106.250 265.703 403.429 755.670 0.000 0.744 0.044 0.000 -383.013 0.000 -108.757 -66.130
PERIMETER_MID_ZN_4 0.000 0.000 0.133 -665.589 0.000 0.000 70.142 171.225 259.979 437.530 0.000 0.637 55.514 0.000 -258.677 0.000 -70.895 -0.010
PERIMETER_TOP_ZN_3 0.000 0.000 2.128 -51.403 0.000 0.000 11.112 26.570 40.342 17.905 0.000 0.132 0.000 0.000 -33.853 0.000 -10.995 -1.938
PERIMETER_TOP_ZN_2 0.000 0.000 0.934 -55.086 0.000 0.000 7.074 17.123 25.998 39.048 0.000 0.070 0.000 0.000 -22.309 0.000 -7.734 -5.118
PERIMETER_TOP_ZN_1 0.000 0.000 0.827 -90.408 0.000 0.000 10.824 26.570 40.343 76.218 0.000 0.091 0.002 0.000 -35.756 0.000 -12.434 -16.276
PERIMETER_TOP_ZN_4 0.000 0.000 0.579 -63.331 0.000 0.000 7.183 17.123 25.998 44.030 0.000 0.082 0.704 0.000 -24.207 0.000 -8.160 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -141.201 0.000 0.000 0.950 4.370 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -18.000
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1279.617 0.000 0.000 9.500 43.701 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -312.390
DATACENTER_TOP_ZN_6 0.000 0.000 0.129 -119.849 0.000 0.000 0.950 4.370 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -39.481
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7164.581 0.000 0.000 20.460 66.437 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -417.172
GROUNDFLOOR_PLENUM 1.152 -75.502 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.059 84.652 0.000 0.000 0.000 -10.361 0.000
MIDFLOOR_PLENUM 7.710 -477.226 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.117 645.347 0.000 0.000 0.000 -176.948 0.000
TOPFLOOR_PLENUM 10.283 -69.861 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.096 77.961 0.000 0.000 0.000 -18.479 -0.001
Total Facility 19.146 -622.589 10.087 -18972.894 0.000 0.000 1534.067 3942.443 15213.411 2098.740 0.000 4.659 1125.761 0.000 -1501.872 0.000 -607.524 -2243.404


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 11-DEC-04:02 0.00 0.00 0.00 -110907.18 0.00 0.00 0.00 1143.06 13457.54 0.00 0.00 0.00 96306.58 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 02-JAN-04:02 0.00 0.00 0.00 -94815.85 0.00 0.00 0.00 1026.54 8057.15 0.00 0.00 0.00 85732.16 0.00 -0.00 0.00 0.00 0.00
CORE_MID 02-OCT-03:02 0.00 0.00 0.00 -851126.18 0.00 0.00 0.00 10265.44 80571.20 0.00 0.00 0.00 760289.54 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 02-OCT-03:02 0.00 0.00 0.00 -83446.58 0.00 0.00 0.00 1026.54 8057.12 0.00 0.00 0.00 74362.92 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 05-JUL-05:03 0.00 0.00 0.00 -11799.92 0.00 0.00 108.96 257.76 1011.70 0.00 0.00 0.00 11681.86 0.00 -1260.35 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 15-OCT-08:43 0.00 0.00 0.00 -16198.46 0.00 0.00 24.64 83.06 488.98 10062.94 0.00 186.89 5351.93 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 19-NOV-12:12 0.00 0.00 0.00 -21280.42 0.00 0.00 36.49 128.90 758.78 17534.39 0.00 0.00 2908.89 0.00 -0.00 0.00 -87.03 0.00
PERIMETER_BOT_ZN_4 23-JUL-15:02 0.00 0.00 0.00 -21553.67 0.00 0.00 22.99 83.06 488.98 9144.15 0.00 0.00 11933.59 0.00 -0.00 0.00 -119.11 0.00
PERIMETER_MID_ZN_3 30-SEP-05:02 0.00 0.00 0.00 -95613.43 0.00 0.00 1162.14 2577.57 10116.97 0.00 0.00 0.00 89529.98 0.00 -7765.13 0.00 -8.10 0.00
PERIMETER_MID_ZN_2 23-JUL-08:53 0.00 0.00 0.00 -164896.53 0.00 0.00 250.94 830.63 4889.82 91550.86 0.00 0.00 68656.76 0.00 -0.00 0.00 -1282.49 0.00
PERIMETER_MID_ZN_1 15-OCT-13:01 0.00 0.00 0.00 -215135.22 0.00 0.00 334.12 1288.96 7587.84 145471.87 0.00 4447.58 56004.84 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 04-JUL-16:32 0.00 0.00 0.00 -181182.56 0.00 0.00 241.64 830.63 4889.79 91273.58 0.00 0.00 83946.92 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 30-SEP-05:02 0.00 0.00 0.00 -11534.18 0.00 0.00 110.87 257.76 1011.70 0.00 0.00 0.00 10932.27 0.00 -776.95 0.00 -1.46 0.00
PERIMETER_TOP_ZN_2 15-OCT-09:13 0.00 0.00 0.00 -16417.18 0.00 0.00 24.73 83.06 488.98 8682.31 0.00 486.13 6651.96 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 15-OCT-15:52 0.00 0.00 0.00 -22587.41 0.00 0.00 36.38 128.90 758.78 4006.81 0.00 190.56 17465.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 15-OCT-15:52 0.00 0.00 0.00 -20296.04 0.00 0.00 22.22 83.06 488.98 9325.39 0.00 127.52 10248.87 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 06-AUG-17:43 0.00 0.00 0.00 -7895.50 0.00 0.00 0.00 21.20 7794.42 0.00 0.00 0.00 79.87 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 06-AUG-17:43 0.00 0.00 0.00 -73499.99 0.00 0.00 0.00 211.99 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4656.22
DATACENTER_TOP_ZN_6 20-AUG-17:23 0.00 0.00 0.00 -7499.08 0.00 0.00 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -316.54
DATACENTER_BASEMENT_ZN_6 19-DEC-17:05 0.00 0.00 0.00 -369352.20 0.00 0.00 667.28 3222.71 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14170.32
GROUNDFLOOR_PLENUM 02-OCT-05:15 0.00 -10672.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10748.30 0.00 -0.00 0.00 -76.01 0.00
MIDFLOOR_PLENUM 02-OCT-05:15 0.00 -79326.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80675.33 0.00 -0.00 0.00 -1348.52 0.00
TOPFLOOR_PLENUM 29-SEP-12:10 0.00 -19726.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 502.05 19224.15 0.00 -0.00 0.00 0.00 0.00
Total Facility 21-AUG-05:03 0.00 12092.71 0.00 -1706257.36 0.00 0.00 15826.01 38246.31 623236.89 0.00 0.00 0.00 1084391.20 0.00 -60537.73 0.00 -6998.02 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 14-OCT-16:03 0.00 0.00 18072.26 0.00 0.00 0.00 520.12 1143.06 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -33192.98
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-05:01 0.00 0.00 65150.55 0.00 0.00 0.00 0.00 2052.86 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -75260.53
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 02-JAN-05:01 0.00 0.00 100102.54 0.00 0.00 0.00 0.00 2577.57 10116.97 0.00 0.00 0.00 0.00 0.00 -18536.15 0.00 -17139.19 -77121.75
PERIMETER_MID_ZN_2 30-MAR-04:01 0.00 0.00 101332.89 0.00 0.00 0.00 0.00 1661.09 6519.76 0.00 0.00 0.00 0.00 0.00 -21616.84 0.00 -13381.81 -74515.09
PERIMETER_MID_ZN_1 02-JAN-06:01 0.00 0.00 128983.05 0.00 0.00 0.00 1445.96 2577.63 10117.12 0.00 0.00 0.00 0.00 0.00 -20180.64 0.00 -2760.16 -120182.97
PERIMETER_MID_ZN_4 09-JAN-06:01 0.00 0.00 90750.01 0.00 0.00 0.00 941.49 1661.09 6519.72 0.00 0.00 0.00 0.00 0.00 -25390.03 0.00 -2997.94 -71484.34
PERIMETER_TOP_ZN_3 02-JAN-04:02 0.00 0.00 13393.00 0.00 0.00 0.00 0.00 128.89 1011.70 0.00 0.00 0.00 0.00 0.00 -1372.66 0.00 -1522.17 -11638.76
PERIMETER_TOP_ZN_2 02-JAN-04:02 0.00 0.00 13117.14 0.00 0.00 0.00 0.00 83.06 651.98 0.00 0.00 0.00 0.00 0.00 -959.67 0.00 -1113.53 -11778.98
PERIMETER_TOP_ZN_1 02-JAN-04:02 0.00 0.00 16830.67 0.00 0.00 0.00 0.00 128.90 1011.71 0.00 0.00 0.00 0.00 0.00 -1534.89 0.00 -1705.07 -14731.32
PERIMETER_TOP_ZN_4 02-JAN-05:01 0.00 0.00 13400.16 0.00 0.00 0.00 0.00 166.11 651.97 0.00 0.00 0.00 0.00 0.00 -973.68 0.00 -1244.17 -12000.39
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 08-JAN-07:00 0.00 0.00 541.30 0.00 0.00 0.00 5.58 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2516.69
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 18-DEC-04:02 12550.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1640.50 -10910.05
MIDFLOOR_PLENUM 28-MAR-05:02 83880.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8126.49 -75754.38
TOPFLOOR_PLENUM 30-MAY-05:03 19160.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -240.11 -18920.34
Total Facility 02-JAN-06:01 -456284.07 451377.79 526530.28 -451377.79 0.00 0.00 18724.62 38246.31 268362.69 0.00 0.00 0.00 0.00 0.00 -80325.53 0.00 -15937.38 -299316.94



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.1265 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.3112 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 95.0728 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 86.2458 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 9.7500 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.3309 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.6261 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.6261 0.2133 1.0000 Not calculated 1.2002 0.2133    
AIRLOOP DATACENTER BASEMENT 21.6804 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.6807 0.0156 1.0000 Not calculated 0.3384 0.0156    
AIRLOOP DATACENTER BOT 0.4775 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4775 0.0327 1.0000 Not calculated 0.0156 0.0327    
AIRLOOP DATACENTER MID 4.5416 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5416 0.0344 1.0000 Not calculated 0.1563 0.0344    
AIRLOOP DATACENTER TOP 0.4631 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4631 0.0338 1.0000 Not calculated 0.0156 0.0338    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.0632 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0379 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 47.5364 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 28.6169 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.8750 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0030 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.6261 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.6261 1.0000 1.0000 Not calculated 1.2002 0.2133    
AIRLOOP DATACENTER BASEMENT 21.6804 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.6804 1.0000 1.0000 Not calculated 0.3384 0.0156    
AIRLOOP DATACENTER BOT 0.4775 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4775 1.0000 1.0000 Not calculated 0.0156 0.0327    
AIRLOOP DATACENTER MID 4.5416 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5416 1.0000 1.0000 Not calculated 0.1563 0.0344    
AIRLOOP DATACENTER TOP 0.4631 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4631 1.0000 1.0000 Not calculated 0.0156 0.0338    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6261 5.6261 5.6261 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9210 5.9210 1.7763 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 55.7203 55.7203 16.7718 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4702 5.4702 1.6848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8811 0.8811 0.2643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9470 0.9470 0.2841 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1642 1.1642 0.3493 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2132 1.2132 0.3640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.2522 8.2522 2.4839 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.6258 9.6258 2.8974 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.1731 11.1731 3.3631 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.3014 10.3014 3.1007 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9551 0.9551 0.2942 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9629 0.9629 0.2966 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2437 1.2437 0.3831 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1180 1.1180 0.3443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4775 0.4775 0.4775 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5416 4.5416 4.5416 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4631 0.4631 0.4631 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.6804 21.6804 21.6804 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.1265 9.3112 10.1265 3.0379 0.0000 1.0000
VAV_MID WITH REHEAT 95.0728 86.2458 95.0728 28.6169 0.0000 1.0000
VAV_TOP WITH REHEAT 9.7500 9.3309 9.7500 3.0030 0.0000 1.0000
CAV_BAS 5.6261 5.6261 5.6261 5.6261 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.6804 21.6807 21.6804 21.6804 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4775 0.4775 0.4775 0.4775 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5416 4.5416 4.5416 4.5416 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4631 0.4631 0.4631 0.4631 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6261 5.6261 5.6261 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9605 2.9605 1.7763 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 27.8602 27.8602 16.7718 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7351 2.7351 1.6848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4405 0.4405 0.2643 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4735 0.4735 0.2841 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5821 0.5821 0.3493 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6066 0.6066 0.3640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.1261 4.1261 2.4839 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8129 4.8129 2.8974 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.5865 5.5865 3.3631 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1507 5.1507 3.1007 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4776 0.4776 0.2942 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4815 0.4815 0.2966 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6218 0.6218 0.3831 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5590 0.5590 0.3443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4775 0.4775 0.4775 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5416 4.5416 4.5416 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4631 0.4631 0.4631 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.6804 21.6804 21.6804 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.0632 3.0379 3.0379 3.0379 0.0000 1.0000
VAV_MID WITH REHEAT 47.5364 28.6169 28.6169 28.6169 0.0000 1.0000
VAV_TOP WITH REHEAT 4.8750 3.0030 3.0030 3.0030 0.0000 1.0000
CAV_BAS 5.6261 5.6261 5.6261 5.6261 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.6804 21.6804 21.6804 21.6804 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4775 0.4775 0.4775 0.4775 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5416 4.5416 4.5416 4.5416 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4631 0.4631 0.4631 0.4631 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 229.67
Number of hours not met 229.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 469.15 752660.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3391.36 448084.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 3942.44 344233.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 905.27 57580.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 87.51 5474.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 61.31 1944.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2462.16 205774.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 670.87 67222.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1391.89 82101.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 2.77 6835.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 741.87 78860.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 29977.77
Natural Gas 0.00 1211.02
Additional 0.00 0.00
Total 15213.41 31188.78


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 85.11
Space Heating 0.00
Space Cooling 73.22
Fans (All) 53.16
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 647.18
Subtotal 647.18


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 10.13
Service Water Heating 16.02
Miscellaneous (All) 26.14
Subtotal 26.14


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 12.64
Space Heating 1.50
Space Cooling 10.87
Fans (All) 7.89
Service Water Heating 2.38
Receptacle Equipment 48.78
Miscellaneous 15.93


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2645. 8760.
LTG_SCH_DATACENTER 2939. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 2355. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8140.50 619.50 0.00 0.00 0.00
CORE_BOTTOM 8620.00 140.00 0.00 0.00 0.00
CORE_MID 8756.50 3.50 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8730.00 30.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8728.67 31.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8098.50 661.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8714.50 45.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8706.50 53.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8697.00 63.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8723.17 36.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8716.50 43.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8707.00 53.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6600.33 2159.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6560.17 2199.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6497.83 2262.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6879.00 1881.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8674.83 85.17 0.00 0.00 0.00
Min 6497.83 0.00 0.00 0.00 0.00
Max 8760.00 2262.17 0.00 0.00 0.00
Average 8309.17 450.83 0.00 0.00 0.00
Sum 191111.00 10369.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367030.50 1585.50 0.00 0.00 0.00
CORE_BOTTOM 330660.00 153.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 946.17 1321.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 929.67 1338.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 901.83 1366.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 54920.33 48474.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367030.50 48474.67 0.00 0.00 0.00
Average 77976.67 2358.24 0.00 0.00 0.00
Sum 1793463.50 54239.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7057.50 1702.50 0.00 0.00 0.00
CORE_BOTTOM 7564.33 1195.67 0.00 0.00 0.00
CORE_MID 7709.67 1050.33 0.00 0.00 0.00
CORE_TOP 7982.83 777.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8417.50 342.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8517.83 242.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8362.33 397.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7471.17 1288.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8496.83 263.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8387.83 372.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8320.50 439.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8050.50 709.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8603.83 156.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8433.33 326.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8457.00 303.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8171.50 588.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7800.83 959.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7749.17 1010.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7706.67 1053.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8242.83 517.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 7980.17 779.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8161.00 599.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 7941.67 818.33 0.00 0.00 0.00
Min 7057.50 156.17 0.00 0.00 0.00
Max 8603.83 1702.50 0.00 0.00 0.00
Average 8068.99 691.01 0.00 0.00 0.00
Sum 185586.83 15893.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 361422.17 7193.83 0.00 0.00 0.00
CORE_BOTTOM 328877.83 1935.17 0.00 0.00 0.00
CORE_MID 329300.33 1512.67 0.00 0.00 0.00
CORE_TOP 329713.00 1100.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1519.33 748.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1484.67 783.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1461.33 806.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 86773.33 16621.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 361422.17 16621.67 0.00 0.00 0.00
Average 79000.04 1334.87 0.00 0.00 0.00
Sum 1817001.00 30702.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:55

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.581253E+11 109087.97 23-JAN-04:03 9.00 7.85 0.566860E+10 7499.45 10-JAN-14:20 9.00 7.85
February 0.501685E+11 110018.52 21-FEB-04:02 7.17 5.77 0.513927E+10 7500.25 01-FEB-14:20 7.17 5.77
March 0.593979E+11 110567.16 20-MAR-03:02 8.50 8.42 0.613297E+10 7499.46 01-MAR-14:20 8.50 8.42
April 0.557816E+11 110124.99 17-APR-03:02 10.00 8.82 0.544977E+10 7499.38 13-APR-09:00 10.00 8.82
May 0.566455E+11 107313.42 22-MAY-03:02 12.00 10.34 0.589985E+10 7499.46 05-MAY-13:00 12.00 10.34
June 0.576664E+11 106263.77 05-JUN-03:02 12.00 11.37 0.588005E+10 7499.15 21-JUN-13:20 23.67 16.91
July 0.581716E+11 99412.28 17-JUL-03:02 14.17 13.59 0.547189E+10 7499.08 11-JUL-13:20 14.17 13.59
August 0.642696E+11 95510.00 28-AUG-03:02 14.00 14.00 0.613583E+10 7499.13 30-AUG-13:20 23.67 18.23
September 0.572791E+11 98928.89 19-SEP-03:02 13.83 12.18 0.545122E+10 7499.34 21-SEP-09:09 19.33 17.40
October 0.620112E+11 109906.31 30-OCT-03:02 9.00 6.92 0.567175E+10 7542.41 16-OCT-13:39 9.00 6.92
November 0.605608E+11 110229.24 06-NOV-04:03 8.33 7.63 0.561558E+10 7499.84 30-NOV-14:00 21.00 13.08
December 0.600955E+11 110923.87 11-DEC-04:02 8.00 7.91 0.547274E+10 7500.06 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.700173E+12         0.679895E+11        
Minimum of Months 0.501685E+11 95510.00   7.17 5.77 0.513927E+10 7499.08   7.17 5.77
Maximum of Months 0.642696E+11 110923.87   14.17 14.00 0.613583E+10 7542.41   23.67 18.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.485363E+11 94933.39 02-JAN-04:02 10.17 8.61 0.508104E+10 6735.06 10-JAN-14:09 16.83 11.85
February 0.461100E+11 92459.84 21-FEB-04:02 7.17 5.77 0.460643E+10 6735.61 01-FEB-14:09 7.17 5.77
March 0.569310E+11 91356.22 20-MAR-03:02 8.50 8.42 0.550165E+10 6735.06 01-MAR-14:09 8.50 8.42
April 0.597677E+11 90545.77 17-APR-03:02 10.00 8.82 0.488381E+10 6735.18 13-APR-09:00 10.00 8.82
May 0.531970E+11 92141.81 30-MAY-03:02 11.83 10.73 0.528835E+10 6735.24 03-MAY-13:00 11.83 10.73
June 0.575953E+11 93617.11 12-JUN-03:02 13.00 11.87 0.527353E+10 6734.75 22-JUN-09:00 23.00 17.27
July 0.641172E+11 88784.73 06-JUL-03:02 13.17 12.60 0.489744E+10 6734.77 11-JUL-09:09 19.33 16.00
August 0.714876E+11 87618.97 23-AUG-03:02 15.37 14.00 0.549792E+10 6734.60 29-AUG-13:00 24.00 17.64
September 0.528929E+11 94326.25 05-SEP-03:02 15.17 13.86 0.488403E+10 6734.75 01-SEP-13:09 15.17 13.86
October 0.583542E+11 92240.43 23-OCT-03:02 17.00 14.51 0.507991E+10 6735.08 27-OCT-09:00 22.00 11.71
November 0.557432E+11 93927.82 20-NOV-04:02 11.00 10.37 0.503244E+10 6735.51 30-NOV-14:00 21.00 13.08
December 0.573225E+11 93614.80 11-DEC-04:02 8.00 7.91 0.490382E+10 6735.80 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.682055E+12         0.609304E+11        
Minimum of Months 0.461100E+11 87618.97   7.17 5.77 0.460643E+10 6734.60   7.17 5.77
Maximum of Months 0.714876E+11 94933.39   17.00 14.51 0.550165E+10 6735.80   24.00 17.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.367391E+11 79506.39 20-JAN-06:02 11.33 10.71 0.505377E+10 6735.03 10-JAN-14:09 11.33 10.71
February 0.337704E+11 79576.04 15-FEB-06:02 11.83 10.84 0.458655E+10 6735.52 01-FEB-14:09 11.83 10.84
March 0.398044E+11 79483.82 23-MAR-05:02 10.67 9.62 0.548298E+10 6735.03 01-MAR-14:09 10.67 9.62
April 0.403997E+11 80786.00 27-APR-04:03 15.00 14.41 0.487223E+10 6735.10 13-APR-09:00 15.00 14.41
May 0.432608E+11 80513.69 04-MAY-04:03 13.17 11.94 0.528110E+10 6735.21 03-MAY-13:00 13.17 11.94
June 0.459973E+11 81408.14 21-JUN-04:02 17.00 14.51 0.526759E+10 6734.74 22-JUN-09:00 23.00 17.27
July 0.466878E+11 80964.82 14-JUL-04:03 16.00 14.77 0.489384E+10 6734.76 07-JUL-13:09 16.00 14.77
August 0.505980E+11 80944.80 31-AUG-04:03 14.17 14.07 0.549505E+10 6734.77 22-AUG-13:09 14.17 14.07
September 0.439478E+11 83448.51 25-SEP-03:02 17.00 16.37 0.487845E+10 6734.78 01-SEP-13:09 17.00 16.37
October 0.453807E+11 85128.36 02-OCT-03:02 19.00 17.66 0.507126E+10 6735.03 27-OCT-09:00 22.00 11.71
November 0.390881E+11 82424.43 13-NOV-04:02 11.83 10.73 0.501859E+10 6735.34 30-NOV-14:00 21.00 13.08
December 0.376581E+11 79115.77 02-DEC-06:02 10.00 10.00 0.488056E+10 6735.64 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.503332E+12         0.607820E+11        
Minimum of Months 0.337704E+11 79115.77   10.00 9.62 0.458655E+10 6734.74   10.67 9.62
Maximum of Months 0.505980E+11 85128.36   19.00 17.66 0.549505E+10 6735.64   23.00 17.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.269220E+11 38767.62 19-JAN-15:00 20.00 15.12 0.484341E+10 6734.94 10-JAN-14:09 20.00 15.12
February 0.258002E+11 39245.39 16-FEB-16:20 16.47 13.30 0.443331E+10 6735.72 01-FEB-14:09 16.47 13.30
March 0.313444E+11 69157.68 24-MAR-05:03 12.00 12.00 0.532796E+10 6734.92 01-MAR-14:09 12.00 12.00
April 0.362987E+11 76727.75 27-APR-05:03 15.00 14.41 0.481925E+10 6735.11 13-APR-13:00 15.00 14.41
May 0.389750E+11 76568.26 03-MAY-05:03 14.17 14.07 0.523395E+10 6735.26 03-MAY-13:00 23.00 16.67
June 0.443159E+11 78599.12 20-JUN-05:02 17.00 14.42 0.525190E+10 6734.70 22-JUN-09:00 23.00 17.27
July 0.471388E+11 79754.16 31-JUL-04:02 17.00 16.37 0.488983E+10 6734.73 07-JUL-13:09 17.00 16.37
August 0.502220E+11 78693.54 18-AUG-05:02 17.92 17.36 0.548900E+10 6734.73 22-AUG-13:09 22.67 17.06
September 0.403674E+11 78678.97 25-SEP-04:03 17.00 16.37 0.485865E+10 6734.74 01-SEP-13:09 17.00 16.37
October 0.397195E+11 83462.29 02-OCT-03:02 19.00 17.66 0.503130E+10 6734.99 31-OCT-13:09 26.83 16.92
November 0.294618E+11 65881.64 01-NOV-05:03 12.83 9.89 0.490458E+10 6735.29 30-NOV-14:00 21.00 13.08
December 0.274126E+11 51489.98 06-DEC-06:03 12.33 6.18 0.471442E+10 6735.55 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.437978E+12         0.597976E+11        
Minimum of Months 0.258002E+11 38767.62   12.00 6.18 0.443331E+10 6734.70   12.00 12.00
Maximum of Months 0.502220E+11 83462.29   20.00 17.66 0.548900E+10 6735.72   26.83 17.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.451136E+10 6283.75 17-JAN-13:40 23.33 17.00 0.621693E+09 845.66 10-JAN-14:09 23.33 17.00
February 0.445997E+10 5417.76 01-FEB-12:00 26.00 14.67 0.567397E+09 845.73 01-FEB-14:09 19.00 15.70
March 0.555766E+10 6218.16 13-MAR-14:00 18.00 13.88 0.679464E+09 845.66 01-MAR-14:09 18.00 13.88
April 0.678394E+10 7494.13 26-APR-14:00 26.00 16.74 0.608677E+09 845.68 13-APR-09:00 26.00 16.74
May 0.646533E+10 8678.84 01-MAY-05:03 13.17 11.94 0.659562E+09 845.69 03-MAY-13:00 23.00 16.67
June 0.775702E+10 11716.29 26-JUN-05:03 17.17 15.13 0.660763E+09 845.63 22-JUN-09:00 17.17 15.13
July 0.904973E+10 11801.61 05-JUL-05:03 17.00 14.42 0.614319E+09 845.63 11-JUL-09:09 19.33 16.00
August 0.957668E+10 11527.42 01-AUG-05:03 17.00 15.07 0.689409E+09 845.61 01-AUG-13:09 22.00 16.85
September 0.650468E+10 11638.38 25-SEP-05:03 17.00 16.37 0.610200E+09 845.63 01-SEP-13:09 17.00 16.37
October 0.695022E+10 10637.47 02-OCT-05:03 19.08 17.74 0.634015E+09 845.66 31-OCT-13:09 26.83 16.92
November 0.543734E+10 6075.26 28-NOV-14:10 24.67 11.00 0.624135E+09 845.71 30-NOV-14:00 21.00 13.08
December 0.533905E+10 6655.73 05-DEC-15:00 25.00 13.22 0.605526E+09 845.74 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.783930E+11         0.757516E+10        
Minimum of Months 0.445997E+10 5417.76   13.17 11.00 0.567397E+09 845.61   17.00 12.37
Maximum of Months 0.957668E+10 11801.61   26.00 17.74 0.689409E+09 845.74   26.83 17.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.440375E+10 6143.55 20-JAN-09:10 17.33 14.09 0.399372E+09 544.97 05-JAN-10:00 17.33 14.09
February 0.413377E+10 6980.14 21-FEB-09:10 14.50 10.04 0.360744E+09 545.02 01-FEB-14:09 14.50 10.04
March 0.508982E+10 8095.64 23-MAR-08:40 18.33 14.51 0.431587E+09 544.98 01-MAR-14:09 18.33 14.51
April 0.642188E+10 14325.13 30-APR-08:43 21.33 15.18 0.389683E+09 545.01 13-APR-09:00 21.33 15.18
May 0.598208E+10 10147.17 28-MAY-07:53 18.00 13.88 0.422567E+09 545.00 03-MAY-13:00 18.00 13.88
June 0.666446E+10 11586.75 18-JUN-07:33 18.67 15.17 0.423065E+09 544.96 22-JUN-09:00 23.00 17.27
July 0.809552E+10 15948.18 23-JUL-08:23 24.00 19.32 0.394395E+09 544.95 11-JUL-09:09 24.00 19.32
August 0.863292E+10 10155.69 13-AUG-07:33 21.00 17.80 0.442400E+09 544.95 01-AUG-13:09 21.00 17.80
September 0.603320E+10 10915.30 03-SEP-08:32 19.33 14.88 0.390830E+09 544.96 12-SEP-09:00 23.00 17.26
October 0.611553E+10 16199.39 15-OCT-08:43 32.33 15.60 0.406233E+09 544.99 27-OCT-09:00 22.00 11.71
November 0.474727E+10 6815.30 19-NOV-09:00 24.00 12.56 0.399050E+09 545.00 10-NOV-10:00 24.00 12.56
December 0.474331E+10 6688.20 05-DEC-09:00 24.00 11.80 0.384574E+09 544.98 04-DEC-14:09 24.00 11.80
                     
Annual Sum or Average 0.710635E+11         0.484450E+10        
Minimum of Months 0.413377E+10 6143.55   14.50 10.04 0.360744E+09 544.95   14.50 10.04
Maximum of Months 0.863292E+10 16199.39   32.33 19.32 0.442400E+09 545.02   24.00 19.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.997814E+10 15734.95 18-JAN-13:30 25.30 14.77 0.630028E+09 847.10 20-JAN-14:20 17.00 14.51
February 0.798240E+10 14785.05 21-FEB-13:20 20.33 13.83 0.566981E+09 846.33 16-FEB-14:00 20.33 13.83
March 0.849955E+10 13404.05 23-MAR-13:20 22.33 16.99 0.674747E+09 846.26 01-MAR-14:09 22.33 16.99
April 0.929458E+10 11773.18 26-APR-13:10 26.83 17.07 0.606307E+09 845.71 13-APR-09:00 26.83 17.07
May 0.724931E+10 8852.16 04-MAY-12:30 23.50 16.62 0.653139E+09 845.72 03-MAY-13:00 23.50 16.62
June 0.800961E+10 9275.95 26-JUN-05:03 17.17 15.13 0.656896E+09 845.64 22-JUN-09:00 17.17 15.13
July 0.990923E+10 12782.23 31-JUL-05:03 17.00 16.37 0.612271E+09 845.64 11-JUL-09:09 17.00 16.37
August 0.120776E+11 12572.65 30-AUG-13:00 24.00 18.12 0.688399E+09 846.39 29-AUG-13:00 24.00 18.12
September 0.101083E+11 15988.26 29-SEP-13:50 34.33 17.92 0.610694E+09 890.71 29-SEP-13:09 34.33 17.92
October 0.117890E+11 20994.55 01-OCT-12:32 25.33 20.49 0.637139E+09 898.84 16-OCT-13:09 33.75 16.65
November 0.106781E+11 21280.47 19-NOV-12:12 26.33 15.30 0.627957E+09 847.39 27-NOV-14:09 22.83 9.22
December 0.113985E+11 20300.75 03-DEC-13:02 16.17 12.63 0.611886E+09 868.63 19-DEC-14:09 22.83 9.79
                     
Annual Sum or Average 0.116974E+12         0.757644E+10        
Minimum of Months 0.724931E+10 8852.16   16.17 12.63 0.566981E+09 845.64   17.00 9.22
Maximum of Months 0.120776E+11 21280.47   34.33 20.49 0.688399E+09 898.84   34.33 18.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.597954E+10 8763.50 18-JAN-14:50 23.27 14.80 0.396865E+09 544.99 10-JAN-14:09 23.27 14.80
February 0.627290E+10 10120.84 22-FEB-15:30 16.90 12.24 0.367508E+09 545.04 01-FEB-14:09 16.90 12.24
March 0.838608E+10 13919.15 24-MAR-05:03 12.00 12.00 0.442365E+09 544.99 01-MAR-14:09 12.00 12.00
April 0.110203E+11 20651.18 30-APR-16:02 22.00 15.83 0.395958E+09 545.00 13-APR-13:50 22.00 15.83
May 0.807941E+10 16254.42 01-MAY-05:03 13.17 11.94 0.424581E+09 545.02 03-MAY-13:00 23.00 16.67
June 0.100240E+11 16145.41 26-JUN-05:03 17.17 15.13 0.426942E+09 544.96 22-JUN-09:00 17.17 15.13
July 0.126086E+11 21567.61 23-JUL-15:02 24.00 19.32 0.397469E+09 544.96 11-JUL-09:09 24.00 19.32
August 0.144001E+11 21330.18 13-AUG-14:12 24.33 19.41 0.445905E+09 544.95 01-AUG-13:09 24.33 19.41
September 0.830799E+10 21098.67 04-SEP-15:52 20.00 16.16 0.393825E+09 544.96 01-SEP-13:09 20.00 16.16
October 0.892406E+10 21160.50 01-OCT-14:32 23.33 19.66 0.410260E+09 544.99 31-OCT-13:09 26.83 16.92
November 0.802821E+10 16609.14 19-NOV-13:32 25.67 15.08 0.406012E+09 545.06 30-NOV-14:50 21.33 12.71
December 0.854148E+10 16251.27 05-DEC-04:02 15.17 8.67 0.396161E+09 545.08 20-DEC-14:50 19.20 11.87
                     
Annual Sum or Average 0.110573E+12         0.490385E+10        
Minimum of Months 0.597954E+10 8763.50   12.00 8.67 0.367508E+09 544.95   12.00 11.87
Maximum of Months 0.144001E+11 21567.61   25.67 19.66 0.445905E+09 545.08   26.83 19.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316358E+10 4658.47 18-JAN-14:20 24.07 14.82 0.578403E+09 845.63 25-JAN-14:00 17.00 13.48
February 0.293069E+10 3974.48 03-FEB-15:00 23.00 8.84 0.535190E+09 845.71 01-FEB-14:09 23.00 8.84
March 0.350538E+10 4650.82 23-MAR-15:20 21.67 17.34 0.638804E+09 845.63 09-MAR-14:30 21.67 17.34
April 0.419893E+10 6095.73 26-APR-14:00 26.00 16.74 0.593984E+09 845.67 13-APR-13:00 26.00 16.74
May 0.487253E+10 6561.77 04-MAY-14:00 23.00 16.67 0.650785E+09 845.69 03-MAY-13:00 23.00 16.67
June 0.591687E+10 6528.96 29-JUN-16:00 23.00 18.43 0.656803E+09 845.62 22-JUN-09:00 23.00 18.43
July 0.643101E+10 7299.82 01-JUL-05:03 17.17 15.80 0.612040E+09 845.63 07-JUL-13:09 22.83 17.20
August 0.650012E+10 7019.61 18-AUG-15:00 27.00 20.85 0.685758E+09 845.63 22-AUG-13:09 22.67 17.06
September 0.514010E+10 9561.19 30-SEP-05:02 23.80 13.84 0.604834E+09 845.63 01-SEP-13:09 23.80 13.84
October 0.513911E+10 8699.27 05-OCT-05:03 20.00 18.62 0.624115E+09 845.66 31-OCT-13:09 26.83 16.92
November 0.341549E+10 4148.54 10-NOV-14:30 19.50 15.78 0.597312E+09 845.67 29-NOV-14:00 18.00 10.62
December 0.323889E+10 4651.52 05-DEC-15:00 25.00 13.22 0.563133E+09 845.65 04-DEC-14:09 25.00 13.22
                     
Annual Sum or Average 0.544527E+11         0.734116E+10        
Minimum of Months 0.293069E+10 3974.48   17.17 8.84 0.535190E+09 845.62   17.00 8.84
Maximum of Months 0.650012E+10 9561.19   27.00 20.85 0.685758E+09 845.71   26.83 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359293E+10 5233.30 20-JAN-09:40 18.33 14.51 0.274541E+09 521.21 24-JAN-11:20 23.00 14.46
February 0.327006E+10 5095.67 21-FEB-10:00 17.00 11.03 0.250509E+09 521.23 01-FEB-11:09 17.00 11.03
March 0.401897E+10 7456.22 23-MAR-09:00 19.00 14.76 0.299446E+09 521.22 23-MAR-10:09 22.00 16.49
April 0.505925E+10 8749.37 26-APR-08:50 22.83 16.63 0.282170E+09 521.26 13-APR-10:09 22.83 16.63
May 0.516956E+10 7853.48 18-MAY-08:50 19.50 14.41 0.304655E+09 521.28 24-MAY-10:39 21.00 14.32
June 0.593008E+10 12182.59 18-JUN-08:43 21.50 16.60 0.306865E+09 521.22 22-JUN-10:09 23.00 17.27
July 0.688045E+10 16499.34 23-JUL-08:53 25.00 19.60 0.289592E+09 521.21 05-JUL-07:10 25.00 19.60
August 0.724958E+10 14563.67 06-AUG-09:13 23.67 19.41 0.323528E+09 521.21 23-AUG-10:30 23.50 17.16
September 0.539950E+10 12857.00 10-SEP-08:23 20.50 17.00 0.283181E+09 521.22 12-SEP-10:09 22.83 17.20
October 0.522488E+10 16331.49 15-OCT-09:43 31.33 16.43 0.293525E+09 521.26 27-OCT-10:30 22.00 13.04
November 0.377898E+10 4893.66 20-NOV-09:10 13.50 12.26 0.278817E+09 521.22 08-NOV-11:00 13.50 12.26
December 0.368820E+10 5365.28 05-DEC-09:50 25.67 12.88 0.265230E+09 521.21 04-DEC-13:00 25.67 12.88
                     
Annual Sum or Average 0.592624E+11         0.345206E+10        
Minimum of Months 0.327006E+10 4893.66   13.50 11.03 0.250509E+09 521.21   13.50 11.03
Maximum of Months 0.724958E+10 16499.34   31.33 19.60 0.323528E+09 521.28   25.67 19.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.926299E+10 19671.82 22-JAN-13:53 18.00 12.36 0.624440E+09 863.49 18-JAN-14:09 18.00 12.36
February 0.688423E+10 14321.43 22-FEB-13:50 19.00 12.78 0.557246E+09 846.11 16-FEB-14:00 19.00 12.78
March 0.684621E+10 12999.36 23-MAR-13:30 22.50 17.06 0.656168E+09 846.01 10-MAR-14:39 22.50 17.06
April 0.689589E+10 10910.01 26-APR-13:10 26.83 17.07 0.596961E+09 845.70 13-APR-13:50 26.83 17.07
May 0.598754E+10 8193.61 04-MAY-12:30 23.50 16.62 0.643475E+09 845.72 03-MAY-13:00 23.50 16.62
June 0.649144E+10 7414.96 30-JUN-13:10 23.00 17.85 0.650557E+09 845.64 22-JUN-09:00 23.00 17.85
July 0.737833E+10 10015.14 31-JUL-13:10 27.83 21.13 0.608830E+09 845.65 07-JUL-13:09 27.83 21.13
August 0.910113E+10 11868.97 30-AUG-13:00 24.00 18.12 0.685068E+09 846.10 30-AUG-13:00 23.00 18.43
September 0.915383E+10 15892.19 29-SEP-12:15 36.00 18.21 0.608481E+09 923.88 29-SEP-13:09 35.67 18.16
October 0.105331E+11 21513.42 15-OCT-13:01 31.83 15.74 0.634756E+09 920.58 16-OCT-13:09 33.75 16.65
November 0.920293E+10 19734.99 19-NOV-11:02 26.00 15.13 0.623062E+09 854.41 27-NOV-14:09 22.83 9.22
December 0.967001E+10 19103.60 25-DEC-11:53 23.00 9.63 0.605760E+09 874.13 19-DEC-14:09 23.00 9.63
                     
Annual Sum or Average 0.974076E+11         0.749480E+10        
Minimum of Months 0.598754E+10 7414.96   18.00 9.63 0.557246E+09 845.64   18.00 9.22
Maximum of Months 0.105331E+11 21513.42   36.00 21.13 0.685068E+09 923.88   35.67 21.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.394375E+10 6862.21 18-JAN-15:00 23.00 14.79 0.366304E+09 544.96 18-JAN-14:39 23.00 14.79
February 0.377778E+10 7319.92 22-FEB-16:20 15.33 12.12 0.335949E+09 545.02 01-FEB-14:09 15.33 12.12
March 0.461615E+10 9611.53 23-MAR-15:50 21.17 17.23 0.401373E+09 544.97 09-MAR-14:09 21.17 17.23
April 0.566751E+10 14486.67 30-APR-16:23 22.00 15.83 0.379142E+09 544.99 13-APR-13:00 22.00 15.83
May 0.577486E+10 11411.71 28-MAY-17:03 18.67 14.22 0.411480E+09 545.01 03-MAY-13:00 18.67 14.22
June 0.677201E+10 17180.39 25-JUN-16:33 21.00 16.52 0.418919E+09 544.95 22-JUN-09:00 21.00 16.52
July 0.754007E+10 18121.03 04-JUL-16:32 19.67 15.52 0.393562E+09 544.96 07-JUL-13:09 22.83 17.20
August 0.788177E+10 17734.70 06-AUG-16:12 23.67 19.59 0.440930E+09 544.96 22-AUG-13:09 22.67 17.06
September 0.615897E+10 11060.99 29-SEP-15:30 32.50 17.18 0.386343E+09 544.96 01-SEP-13:09 32.50 17.18
October 0.579937E+10 17465.91 15-OCT-15:02 30.83 15.40 0.395527E+09 544.98 31-OCT-13:09 26.83 16.92
November 0.443523E+10 7279.68 07-NOV-15:30 19.00 14.51 0.376032E+09 545.03 30-NOV-14:00 21.00 13.08
December 0.419086E+10 7172.12 19-DEC-15:30 21.50 8.94 0.357093E+09 545.05 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.665583E+11         0.466265E+10        
Minimum of Months 0.377778E+10 6862.21   15.33 8.94 0.335949E+09 544.95   15.33 12.12
Maximum of Months 0.788177E+10 18121.03   32.50 19.59 0.440930E+09 545.05   32.50 17.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.255531E+10 4129.65 18-JAN-15:00 23.00 14.79 0.532248E+09 845.62 18-JAN-14:30 23.00 14.79
February 0.243713E+10 3492.13 01-FEB-15:00 19.00 14.76 0.491330E+09 845.69 01-FEB-14:20 19.00 14.76
March 0.308992E+10 4644.32 23-MAR-15:20 21.67 17.34 0.589427E+09 845.62 10-MAR-14:00 21.67 17.34
April 0.401190E+10 6593.96 26-APR-14:00 26.00 16.74 0.570003E+09 845.67 13-APR-13:00 26.00 16.74
May 0.464257E+10 7111.49 04-MAY-14:00 23.00 16.67 0.629170E+09 845.69 03-MAY-13:00 23.00 16.67
June 0.591402E+10 7174.78 30-JUN-14:00 23.00 17.85 0.647232E+09 845.62 22-JUN-09:00 23.00 17.85
July 0.667367E+10 8126.84 19-JUL-15:00 27.00 20.17 0.607671E+09 845.63 07-JUL-13:09 27.00 20.17
August 0.666196E+10 7779.99 18-AUG-15:00 27.00 20.85 0.678992E+09 845.63 22-AUG-13:09 22.67 17.06
September 0.501150E+10 11533.95 30-SEP-05:02 23.80 13.84 0.591244E+09 845.63 01-SEP-13:09 23.80 13.84
October 0.485085E+10 9007.22 16-OCT-13:10 33.75 16.65 0.604283E+09 845.66 31-OCT-13:09 26.83 16.92
November 0.292737E+10 3764.35 10-NOV-14:40 19.33 15.82 0.550598E+09 845.62 28-NOV-14:00 23.00 10.79
December 0.262697E+10 4159.26 05-DEC-15:00 25.00 13.22 0.515028E+09 845.60 05-DEC-14:00 25.00 13.22
                     
Annual Sum or Average 0.514032E+11         0.700723E+10        
Minimum of Months 0.243713E+10 3492.13   19.00 13.22 0.491330E+09 845.60   19.00 10.79
Maximum of Months 0.667367E+10 11533.95   33.75 20.85 0.678992E+09 845.69   27.00 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288274E+10 3968.73 20-JAN-10:10 19.33 14.89 0.356316E+09 544.95 19-JAN-10:00 19.33 14.89
February 0.258941E+10 3805.67 02-FEB-10:10 17.17 12.19 0.328172E+09 545.03 01-FEB-14:09 17.17 12.19
March 0.340071E+10 6532.91 23-MAR-09:40 21.00 15.89 0.393029E+09 544.96 23-MAR-09:00 22.00 16.42
April 0.474321E+10 8262.93 26-APR-09:30 23.50 16.85 0.380529E+09 545.00 13-APR-09:00 23.50 16.85
May 0.488610E+10 7479.56 04-MAY-09:30 21.00 15.49 0.409721E+09 545.00 03-MAY-13:00 21.00 15.49
June 0.593232E+10 9080.93 25-JUN-09:23 22.50 16.84 0.415645E+09 544.96 22-JUN-09:00 22.50 16.84
July 0.706879E+10 12884.63 04-JUL-09:02 22.00 15.93 0.393099E+09 544.96 17-JUL-09:39 22.33 17.42
August 0.739078E+10 11215.95 13-AUG-09:23 24.00 19.61 0.440496E+09 544.96 22-AUG-13:09 22.67 17.06
September 0.524075E+10 9154.15 30-SEP-05:02 23.80 13.84 0.382665E+09 544.96 12-SEP-09:00 23.80 13.84
October 0.488377E+10 16418.26 15-OCT-09:13 32.33 16.14 0.395105E+09 544.99 27-OCT-09:00 22.00 11.71
November 0.314245E+10 4041.60 19-NOV-13:22 26.00 15.06 0.364515E+09 544.94 01-NOV-09:50 26.00 15.06
December 0.292443E+10 4132.59 05-DEC-10:00 26.00 13.09 0.343633E+09 544.96 05-DEC-10:39 24.67 13.14
                     
Annual Sum or Average 0.550854E+11         0.460293E+10        
Minimum of Months 0.258941E+10 3805.67   17.17 12.19 0.328172E+09 544.94   17.17 11.71
Maximum of Months 0.739078E+10 16418.26   32.33 19.61 0.440496E+09 545.03   26.00 17.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.777129E+10 18682.54 22-JAN-14:02 17.83 12.38 0.605623E+09 846.42 20-JAN-14:09 17.83 12.38
February 0.577041E+10 13932.23 22-FEB-14:10 18.80 12.73 0.533906E+09 846.23 01-FEB-14:20 18.80 12.73
March 0.601256E+10 13223.01 23-MAR-14:00 23.00 17.27 0.622320E+09 845.98 22-MAR-13:50 23.00 17.27
April 0.657579E+10 11515.49 26-APR-13:10 26.83 17.07 0.579794E+09 845.70 13-APR-13:50 26.83 17.07
May 0.573001E+10 8711.30 03-MAY-13:10 23.83 15.35 0.620787E+09 845.72 03-MAY-13:00 23.00 16.67
June 0.656694E+10 8104.86 30-JUN-13:30 23.00 17.85 0.636547E+09 845.64 07-JUN-13:00 23.00 17.85
July 0.768256E+10 10923.44 31-JUL-13:10 27.83 21.13 0.602094E+09 845.65 07-JUL-13:09 27.83 21.13
August 0.932764E+10 12486.67 30-AUG-13:10 23.83 18.18 0.678088E+09 845.65 29-AUG-13:09 23.83 18.18
September 0.896190E+10 16948.39 29-SEP-12:05 36.00 18.21 0.599203E+09 948.12 29-SEP-13:20 35.33 18.10
October 0.100472E+11 22587.73 15-OCT-15:52 30.00 14.89 0.622847E+09 906.49 16-OCT-13:09 33.75 16.65
November 0.788533E+10 22357.69 19-NOV-13:22 26.00 15.06 0.606833E+09 846.42 28-NOV-14:50 23.33 10.84
December 0.807459E+10 16556.66 19-DEC-13:20 25.00 11.01 0.587621E+09 846.20 20-DEC-14:50 19.20 11.87
                     
Annual Sum or Average 0.904063E+11         0.729566E+10        
Minimum of Months 0.573001E+10 8104.86   17.83 11.01 0.533906E+09 845.64   17.83 10.84
Maximum of Months 0.100472E+11 22587.73   36.00 21.13 0.678088E+09 948.12   35.33 21.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.331199E+10 6570.33 18-JAN-15:00 23.00 14.79 0.347453E+09 544.96 18-JAN-14:39 23.00 14.79
February 0.319995E+10 6971.48 22-FEB-16:20 15.33 12.12 0.317486E+09 545.04 01-FEB-14:09 15.33 12.12
March 0.413045E+10 9687.98 23-MAR-15:50 21.17 17.23 0.379284E+09 544.96 10-MAR-14:00 21.17 17.23
April 0.549759E+10 11046.33 26-APR-16:00 22.00 16.41 0.365080E+09 544.99 13-APR-13:00 22.00 16.41
May 0.561322E+10 10849.74 28-MAY-17:03 18.67 14.22 0.396451E+09 545.01 03-MAY-13:00 18.67 14.22
June 0.682708E+10 17114.83 25-JUN-16:42 21.00 16.52 0.409902E+09 544.95 07-JUN-13:00 21.00 16.52
July 0.774465E+10 19957.03 09-JUL-16:02 20.67 15.87 0.389415E+09 544.96 07-JUL-13:09 20.67 15.87
August 0.801932E+10 13788.21 20-AUG-17:33 19.60 16.68 0.435176E+09 544.96 22-AUG-13:09 22.67 17.06
September 0.608451E+10 12328.96 30-SEP-05:02 23.80 13.84 0.376107E+09 544.96 01-SEP-13:09 23.80 13.84
October 0.557568E+10 20296.35 15-OCT-15:52 30.00 14.89 0.382850E+09 544.97 25-OCT-13:00 24.00 11.58
November 0.384136E+10 6963.45 10-NOV-14:50 19.17 15.85 0.357191E+09 545.03 30-NOV-14:00 21.00 13.08
December 0.348480E+10 6928.82 19-DEC-15:30 21.50 8.94 0.337588E+09 545.04 20-DEC-14:00 19.00 12.37
                     
Annual Sum or Average 0.633306E+11         0.449398E+10        
Minimum of Months 0.319995E+10 6570.33   15.33 8.94 0.317486E+09 544.95   15.33 11.58
Maximum of Months 0.801932E+10 20296.35   30.00 17.23 0.435176E+09 545.04   24.00 17.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.464773E+10 8328.31 17-JAN-06:15 15.67 13.46 0.00 0.00 01-JAN-00:10 15.67 13.46
February 0.422456E+10 7140.37 21-FEB-06:15 8.00 6.97 0.00 0.00 01-FEB-00:10 8.00 6.97
March 0.507629E+10 7070.04 20-MAR-05:15 10.67 10.47 0.00 0.00 01-MAR-00:10 10.67 10.47
April 0.635894E+10 8467.78 11-APR-05:13 12.00 12.00 0.00 0.00 01-APR-00:10 12.00 12.00
May 0.571216E+10 9646.56 01-MAY-05:13 13.33 12.00 0.00 0.00 01-MAY-00:10 13.33 12.00
June 0.698284E+10 8409.33 19-JUN-05:13 16.33 14.87 0.00 0.00 01-JUN-00:10 16.33 14.87
July 0.801762E+10 9439.67 05-JUL-05:15 17.00 14.32 0.00 0.00 01-JUL-00:10 17.00 14.32
August 0.893186E+10 10044.23 07-AUG-05:15 18.00 17.96 0.00 0.00 01-AUG-00:10 18.00 17.96
September 0.668793E+10 10460.39 05-SEP-05:13 16.00 14.76 0.00 0.00 01-SEP-00:10 16.00 14.76
October 0.726862E+10 10673.65 02-OCT-05:15 19.07 17.72 0.00 0.00 01-OCT-00:10 19.07 17.72
November 0.584483E+10 8485.86 21-NOV-06:13 13.00 11.87 0.00 0.00 01-NOV-00:10 13.00 11.87
December 0.574850E+10 9100.96 26-DEC-06:15 7.00 1.09 0.00 0.00 01-DEC-00:10 7.00 1.09
                     
Annual Sum or Average 0.755019E+11         0.00        
Minimum of Months 0.422456E+10 7070.04   7.00 1.09 0.00 0.00   7.00 1.09
Maximum of Months 0.893186E+10 10673.65   19.07 17.96 0.00 0.00   19.07 17.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.250163E+10 4871.99 21-JAN-06:13 13.00 13.00 0.00 0.00 01-JAN-00:10 13.00 13.00
February 0.231309E+10 4832.21 04-FEB-06:08 5.67 0.59 0.00 0.00 01-FEB-00:10 5.67 0.59
March 0.250387E+10 4994.74 23-MAR-05:13 10.33 9.39 0.00 0.00 01-MAR-00:10 10.33 9.39
April 0.363080E+10 6541.20 27-APR-05:13 15.00 14.41 0.00 0.00 01-APR-00:10 15.00 14.41
May 0.389755E+10 5571.45 01-MAY-05:13 13.33 12.00 0.00 0.00 01-MAY-00:10 13.33 12.00
June 0.488372E+10 6500.28 22-JUN-05:13 14.00 12.84 0.00 0.00 01-JUN-00:10 14.00 12.84
July 0.568080E+10 6671.30 01-JUL-05:13 17.33 15.87 0.00 0.00 01-JUL-00:10 17.33 15.87
August 0.618384E+10 6523.87 31-AUG-05:13 15.33 14.60 0.00 0.00 01-AUG-00:10 15.33 14.60
September 0.499107E+10 6111.82 26-SEP-05:02 15.83 14.71 0.00 0.00 01-SEP-00:10 15.83 14.71
October 0.507541E+10 7933.24 02-OCT-05:15 19.07 17.72 0.00 0.00 01-OCT-00:10 19.07 17.72
November 0.320407E+10 5053.74 13-NOV-06:15 11.33 10.63 0.00 0.00 01-NOV-00:10 11.33 10.63
December 0.285671E+10 4689.93 02-DEC-06:10 10.00 10.00 0.00 0.00 01-DEC-00:10 10.00 10.00
                     
Annual Sum or Average 0.477226E+11         0.00        
Minimum of Months 0.231309E+10 4689.93   5.67 0.59 0.00 0.00   5.67 0.59
Maximum of Months 0.618384E+10 7933.24   19.07 17.72 0.00 0.00   19.07 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204726E+10 8849.86 18-JAN-14:40 23.53 14.82 0.00 0.00 01-JAN-00:10 23.53 14.82
February 0.205526E+10 8818.12 01-FEB-14:00 19.00 15.88 0.00 0.00 01-FEB-00:10 19.00 15.88
March 0.320132E+10 12845.84 23-MAR-14:40 22.33 17.37 0.00 0.00 01-MAR-00:10 22.33 17.37
April 0.640337E+10 17206.28 26-APR-13:40 26.33 16.87 0.00 0.00 01-APR-00:10 26.33 16.87
May 0.651560E+10 16236.48 03-MAY-13:10 23.83 15.35 0.00 0.00 01-MAY-00:10 23.83 15.35
June 0.892611E+10 16336.37 30-JUN-13:10 23.00 17.85 0.00 0.00 01-JUN-00:10 23.00 17.85
July 0.110912E+11 18429.59 19-JUL-13:10 27.00 20.29 0.00 0.00 01-JUL-00:10 27.00 20.29
August 0.113508E+11 17900.19 14-AUG-12:10 26.83 20.78 0.00 0.00 01-AUG-00:10 26.83 20.78
September 0.749560E+10 19724.66 29-SEP-12:10 36.00 18.21 0.00 0.00 01-SEP-00:10 36.00 18.21
October 0.623823E+10 18398.64 16-OCT-13:10 33.75 16.65 0.00 0.00 01-OCT-00:10 33.75 16.65
November 0.254935E+10 8483.97 10-NOV-14:00 20.00 15.64 0.00 0.00 01-NOV-00:10 20.00 15.64
December 0.198644E+10 8074.10 19-DEC-13:10 25.50 11.30 0.00 0.00 01-DEC-00:10 25.50 11.30
                     
Annual Sum or Average 0.698605E+11         0.00        
Minimum of Months 0.198644E+10 8074.10   19.00 11.30 0.00 0.00   19.00 11.30
Maximum of Months 0.113508E+11 19724.66   36.00 20.78 0.00 0.00   36.00 20.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.402811E+10 2045.85 30-JAN-16:40 14.00 11.39 95232975.30 126.84 20-JAN-14:00 14.00 11.39
February 0.831607E+10 4034.44 22-FEB-17:00 14.00 12.23 86400313.34 126.84 13-FEB-14:00 14.00 12.23
March 0.143901E+11 7024.47 31-MAR-24:00 9.70 9.11 0.103240E+09 126.83 24-MAR-09:09 9.70 9.11
April 0.189624E+11 7812.54 30-APR-17:14 21.33 15.80 91606341.52 126.83 05-APR-09:09 21.33 15.80
May 0.435023E+10 3327.86 31-MAY-24:00 13.10 11.97 99240377.43 126.84 05-MAY-13:00 13.10 11.97
June 0.928852E+10 5366.83 30-JUN-24:00 16.40 15.78 98967684.75 126.85 28-JUN-13:39 16.40 15.78
July 0.146803E+11 7236.87 31-JUL-23:45 18.15 17.39 91888179.90 126.84 20-JUL-09:09 18.15 17.39
August 0.197038E+11 7895.55 06-AUG-17:50 21.33 19.00 0.103239E+09 126.83 08-AUG-09:09 20.42 18.12
September 0.435795E+10 3524.20 30-SEP-24:00 18.40 17.30 91616509.79 126.85 25-SEP-13:00 18.40 17.30
October 0.957069E+10 5332.72 31-OCT-24:00 14.90 11.04 95236607.25 126.85 04-OCT-13:00 14.90 11.04
November 0.140404E+11 5900.41 07-NOV-16:20 18.33 14.34 94302726.58 126.83 20-NOV-14:30 18.00 14.97
December 0.195125E+11 7838.88 25-DEC-16:10 20.17 9.85 92192022.13 136.22 19-DEC-10:00 20.17 9.85
                     
Annual Sum or Average 0.141201E+12         0.114316E+10        
Minimum of Months 0.402811E+10 2045.85   9.70 9.11 86400313.34 126.83   9.70 9.11
Maximum of Months 0.197038E+11 7895.55   21.33 19.00 0.103240E+09 136.22   21.33 18.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.284880E+10 1861.99 30-JAN-16:50 14.00 11.30 95232778.92 126.84 20-JAN-14:00 14.00 11.30
February 0.708930E+10 3767.85 22-FEB-17:00 14.00 12.23 86400043.35 126.84 13-FEB-14:00 14.00 12.23
March 0.128784E+11 6267.75 31-MAR-23:40 9.83 9.24 0.103240E+09 126.83 24-MAR-13:00 9.83 9.24
April 0.176505E+11 7288.86 27-APR-17:00 17.00 14.51 91606503.87 126.83 05-APR-09:09 17.00 14.51
May 0.365852E+10 2991.97 31-MAY-24:00 13.10 11.97 99239939.58 126.84 05-MAY-13:00 13.10 11.97
June 0.854198E+10 5072.43 30-JUN-24:00 16.40 15.78 98967027.55 126.84 29-JUN-13:00 16.40 15.78
July 0.138691E+11 6925.30 31-JUL-23:53 18.10 17.45 91888444.22 126.84 28-JUL-13:00 18.10 17.45
August 0.186787E+11 7350.05 06-AUG-17:50 21.33 19.00 0.103239E+09 126.83 08-AUG-09:09 20.42 18.12
September 0.377951E+10 3378.07 30-SEP-24:00 18.40 17.30 91613808.10 126.85 06-SEP-13:00 18.40 17.30
October 0.865170E+10 4921.29 31-OCT-24:00 14.90 11.04 95236058.82 126.85 02-OCT-13:00 14.90 11.04
November 0.126321E+11 5539.36 07-NOV-16:20 18.33 14.34 94302758.92 126.83 10-NOV-14:00 19.00 15.88
December 0.176831E+11 7326.15 18-DEC-16:20 20.33 7.98 91991959.44 132.37 19-DEC-14:09 22.83 9.79
                     
Annual Sum or Average 0.127962E+12         0.114296E+10        
Minimum of Months 0.284880E+10 1861.99   9.83 7.98 86400043.35 126.83   9.83 9.24
Maximum of Months 0.186787E+11 7350.05   21.33 19.00 0.103240E+09 132.37   22.83 18.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.165907E+10 1821.74 18-JAN-16:10 21.83 15.33 95103140.10 126.84 20-JAN-14:00 17.00 14.51
February 0.598992E+10 3762.00 22-FEB-17:00 14.00 12.23 86400003.61 126.84 13-FEB-14:00 14.00 12.23
March 0.118498E+11 5846.27 31-MAR-23:20 9.97 9.37 0.103240E+09 126.83 24-MAR-13:00 9.97 9.37
April 0.171061E+11 7364.41 26-APR-16:00 22.00 16.41 91606722.70 126.83 05-APR-09:09 22.00 16.41
May 0.310882E+10 2672.04 31-MAY-24:00 13.10 11.97 99240064.07 126.84 05-MAY-13:00 13.10 11.97
June 0.828705E+10 4932.26 30-JUN-24:00 16.40 15.78 98967360.75 126.85 28-JUN-13:50 16.40 15.78
July 0.137604E+11 6814.40 31-JUL-24:00 18.10 17.45 91888730.47 126.84 28-JUL-13:00 18.10 17.45
August 0.185367E+11 7499.12 20-AUG-17:30 19.90 16.77 0.103239E+09 126.83 08-AUG-09:09 19.90 16.77
September 0.343987E+10 3304.93 30-SEP-24:00 18.40 17.30 91615002.79 126.85 25-SEP-13:00 18.40 17.30
October 0.812787E+10 4667.61 31-OCT-23:50 15.02 11.31 95236131.77 126.85 05-OCT-13:00 15.02 11.31
November 0.115956E+11 5518.84 10-NOV-16:20 17.67 15.55 94302825.37 126.83 10-NOV-14:00 17.67 15.55
December 0.163880E+11 7327.28 19-DEC-16:30 20.00 7.77 91901252.01 128.55 19-DEC-14:09 20.00 7.77
                     
Annual Sum or Average 0.119849E+12         0.114274E+10        
Minimum of Months 0.165907E+10 1821.74   9.97 7.77 86400003.61 126.83   9.97 7.77
Maximum of Months 0.185367E+11 7499.12   22.00 17.45 0.103240E+09 128.55   22.00 17.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240120E+12 92704.43 18-JAN-17:00 21.00 15.00 0.206163E+10 2747.17 04-JAN-10:00 21.00 15.00
February 0.436154E+12 183710.63 21-FEB-17:00 16.00 13.03 0.187047E+10 2748.56 06-FEB-10:09 16.00 13.03
March 0.728835E+12 358135.06 31-MAR-24:00 9.70 9.11 0.223483E+10 2745.57 24-MAR-09:09 9.70 9.11
April 0.942073E+12 367252.46 27-APR-16:00 18.00 14.37 0.198778E+10 2989.46 26-APR-13:39 18.00 14.37
May 0.240166E+12 175388.57 31-MAY-24:00 13.10 11.97 0.214833E+10 2745.98 05-MAY-13:00 13.10 11.97
June 0.468588E+12 267121.52 30-JUN-24:00 16.40 15.78 0.214240E+10 2746.00 28-JUN-13:39 16.40 15.78
July 0.730131E+12 359211.30 31-JUL-23:53 18.10 17.45 0.198911E+10 2745.67 28-JUL-13:00 18.10 17.45
August 0.974728E+12 367697.22 25-AUG-16:00 21.00 17.71 0.228840E+10 3080.24 14-AUG-13:09 21.00 17.71
September 0.234134E+12 175694.97 30-SEP-24:00 18.40 17.30 0.198339E+10 2746.60 22-SEP-13:50 18.40 17.30
October 0.486337E+12 267929.38 31-OCT-24:00 14.90 11.04 0.206170E+10 2746.96 27-OCT-09:09 14.90 11.04
November 0.707609E+12 276274.68 13-NOV-17:00 15.00 13.80 0.204168E+10 2748.54 29-NOV-10:39 21.33 8.11
December 0.975707E+12 369381.26 19-DEC-17:05 18.50 7.09 0.203764E+10 3263.11 05-DEC-10:20 18.50 7.09
                     
Annual Sum or Average 0.716458E+13         0.248474E+11        
Minimum of Months 0.234134E+12 92704.43   9.70 7.09 0.187047E+10 2745.57   9.70 7.09
Maximum of Months 0.975707E+12 369381.26   21.00 17.71 0.228840E+10 3263.11   21.33 17.71



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.527732E+09 12418.05 02-JAN-04:17 10.33
February 0.222343E+09 12548.79 27-FEB-04:05 11.00
March 0.171875E+09 12394.89 01-MAR-05:05 7.00
April 0.215727E+09 14122.50 04-APR-03:53 9.00
May 0.247579E+09 12554.08 15-MAY-03:05 9.00
June 0.190008E+09 13954.02 27-JUN-03:53 17.00
July 0.234104E+09 14444.74 06-JUL-03:53 14.00
August 0.242962E+09 13969.67 21-AUG-02:62 17.00
September 0.371143E+09 14492.12 30-SEP-16:03 28.50
October 0.528241E+09 18072.20 14-OCT-16:03 31.17
November 0.449628E+09 14432.94 12-NOV-16:53 15.00
December 0.471162E+09 14259.96 06-DEC-04:53 14.00
         
Annual Sum or Average 0.387251E+10      
Minimum of Months 0.171875E+09 12394.89   7.00
Maximum of Months 0.528241E+09 18072.20   31.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171867E+09 65157.36 02-JAN-05:01 11.00
February 5536643.21 36910.95 27-FEB-06:03 11.00
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 1463221.87 9754.81 26-DEC-06:03 7.00
         
Annual Sum or Average 0.178867E+09      
Minimum of Months 0.00 0.00   7.00
Maximum of Months 0.171867E+09 65157.36   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 43469827.73 10010.22 02-JAN-05:01 11.00
February 817567.95 2765.85 27-FEB-06:03 11.00
March 21159964.03 9936.97 30-MAR-04:01 4.48
April 390154.84 2601.03 01-APR-05:03 7.83
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 710639.54 5659.37 24-NOV-06:02 8.92
December 5838386.00 9413.24 13-DEC-06:03 6.17
         
Annual Sum or Average 72386540.08      
Minimum of Months 0.00 0.00   4.48
Maximum of Months 43469827.73 10010.22   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17148342.22 9771.08 09-JAN-06:01 2.17
February 489822.36 1542.11 28-FEB-06:02 10.17
March 15506034.49 10133.24 30-MAR-04:01 4.48
April 596758.65 2575.61 01-APR-05:03 7.83
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 115796.27 964.97 24-NOV-06:02 8.92
December 4444938.39 8318.96 13-DEC-06:03 6.17
         
Annual Sum or Average 38301692.37      
Minimum of Months 0.00 0.00   2.17
Maximum of Months 17148342.22 10133.24   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4045723.25 12897.97 02-JAN-06:01 11.00
February 0.00 0.00 01-FEB-00:10 13.23
March 14496030.16 12792.64 30-MAR-05:03 4.97
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 1249567.86 5823.23 13-DEC-06:03 6.17
         
Annual Sum or Average 19791321.27      
Minimum of Months 0.00 0.00   4.97
Maximum of Months 14496030.16 12897.97   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7573308.17 9074.93 09-JAN-06:01 2.17
February 0.00 0.00 01-FEB-00:10 13.23
March 4856077.31 8081.80 30-MAR-05:03 4.97
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 909666.18 4129.62 13-DEC-06:03 6.17
         
Annual Sum or Average 13339051.67      
Minimum of Months 0.00 0.00   2.17
Maximum of Months 7573308.17 9074.93   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.655614E+09 13392.99 02-JAN-04:02 10.17
February 0.329859E+09 12267.44 06-FEB-05:01 8.17
March 0.425565E+09 12577.09 30-MAR-04:01 4.48
April 42577670.97 11656.55 01-APR-04:03 8.00
May 7837671.95 11081.26 15-MAY-05:03 8.50
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 16067173.34 11259.80 30-OCT-05:02 10.83
November 0.201891E+09 12284.77 24-NOV-05:01 8.17
December 0.448847E+09 12436.82 13-DEC-05:01 6.83
         
Annual Sum or Average 0.212826E+10      
Minimum of Months 0.00 0.00   4.48
Maximum of Months 0.655614E+09 13392.99   18.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.283600E+09 13117.11 02-JAN-04:02 10.17
February 0.157776E+09 12008.67 27-FEB-05:02 11.00
March 0.202457E+09 12574.35 30-MAR-04:01 4.48
April 19435119.31 10541.32 18-APR-05:02 11.17
May 3239199.45 9178.03 13-MAY-05:03 10.33
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 5368958.69 8726.75 30-OCT-05:02 10.83
November 75021471.54 12018.15 24-NOV-05:01 8.17
December 0.187177E+09 12447.48 13-DEC-05:01 6.83
         
Annual Sum or Average 0.934075E+09      
Minimum of Months 0.00 0.00   4.48
Maximum of Months 0.283600E+09 13117.11   18.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220474E+09 16830.64 02-JAN-04:02 10.17
February 0.136744E+09 15140.92 27-FEB-05:02 11.00
March 0.282819E+09 16223.24 30-MAR-04:01 4.48
April 34119011.89 14280.44 18-APR-05:02 11.17
May 13761519.01 14379.21 13-MAY-05:03 10.33
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 221663.64 1477.76 12-OCT-05:03 9.00
November 31837998.41 14288.25 06-NOV-06:02 10.17
December 0.107202E+09 15842.51 13-DEC-05:01 6.83
         
Annual Sum or Average 0.827180E+09      
Minimum of Months 0.00 0.00   4.48
Maximum of Months 0.282819E+09 16830.64   18.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217857E+09 13399.49 02-JAN-05:01 11.00
February 76009596.98 10570.07 28-FEB-06:02 10.17
March 0.129863E+09 13272.33 30-MAR-04:01 4.48
April 15116794.41 8890.65 01-APR-05:03 7.83
May 2547470.86 8350.62 13-MAY-05:03 10.33
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 47903.53 260.74 28-OCT-05:03 9.33
November 32798122.15 10767.78 24-NOV-05:01 8.17
December 0.105066E+09 12983.49 13-DEC-05:01 6.83
         
Annual Sum or Average 0.579306E+09      
Minimum of Months 0.00 0.00   4.48
Maximum of Months 0.217857E+09 13399.49   18.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 67628152.87 10300.88 02-JAN-04:02 10.17
February 84621616.15 10693.55 13-FEB-04:03 13.83
March 0.100374E+09 11165.41 30-MAR-04:01 4.48
April 0.136227E+09 10962.73 17-APR-03:02 10.00
May 78894177.22 8525.12 08-MAY-03:02 14.00
June 62737119.02 9225.30 12-JUN-03:02 13.00
July 0.112791E+09 7937.58 15-JUL-03:02 17.83
August 0.120541E+09 8647.28 23-AUG-03:02 15.37
September 65457660.53 8857.74 25-SEP-03:02 17.00
October 87778884.46 9788.81 23-OCT-03:02 17.00
November 0.112860E+09 10345.84 24-NOV-04:03 7.17
December 0.122223E+09 12549.43 18-DEC-04:02 18.00
         
Annual Sum or Average 0.115213E+10      
Minimum of Months 62737119.02 7937.58   4.48
Maximum of Months 0.136227E+09 12549.43   18.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154552E+09 7820.48 04-JAN-06:03 7.17
February 68889780.91 8165.40 28-FEB-06:02 10.17
March 73842338.55 8387.51 28-MAR-05:02 11.83
April 56557908.25 7063.06 18-APR-05:02 11.17
May 58625193.79 7169.82 08-MAY-04:03 14.00
June 46693741.11 6205.52 13-JUN-04:03 11.00
July 46594086.41 5965.21 12-JUL-04:03 17.00
August 45278260.81 5854.68 28-AUG-03:02 14.00
September 52889016.81 6907.61 25-SEP-03:02 17.00
October 62326287.29 6620.93 02-OCT-03:02 19.00
November 52253478.11 7642.64 13-NOV-04:02 11.83
December 52514250.13 7610.60 18-DEC-06:03 17.00
         
Annual Sum or Average 0.771016E+09      
Minimum of Months 45278260.81 5854.68   7.17
Maximum of Months 0.154552E+09 8387.51   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202411E+10 12030.13 09-JAN-06:03 2.17
February 0.143211E+10 10104.58 16-FEB-06:03 11.98
March 0.166438E+10 14681.07 24-MAR-05:03 12.00
April 0.583269E+09 17916.05 25-APR-05:03 11.33
May 0.444400E+09 19160.14 30-MAY-05:03 11.00
June 0.182766E+09 18922.42 05-JUN-05:03 12.17
July 0.103766E+09 16072.32 06-JUL-05:03 14.33
August 0.113572E+09 16020.45 31-AUG-05:02 15.17
September 0.221590E+09 16174.46 12-SEP-05:03 15.00
October 0.533674E+09 16618.02 18-OCT-05:03 15.00
November 0.116792E+10 15740.62 01-NOV-05:03 12.83
December 0.181167E+10 17066.21 06-DEC-06:03 12.33
         
Annual Sum or Average 0.102832E+11      
Minimum of Months 0.103766E+09 10104.58   2.17
Maximum of Months 0.202411E+10 19160.14   15.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128322E+09 541.29 08-JAN-07:00 1.00
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 918937.26 359.19 14-MAY-07:35 14.00
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.129241E+09      
Minimum of Months 0.00 0.00   1.00
Maximum of Months 0.128322E+09 541.29   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:03 18.07
September 0.00 0.00 01-SEP-00:03 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196603E+11 20573.73 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.178333E+11 20573.73 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.211910E+11 20573.73 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.189279E+11 20573.73 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.204256E+11 20573.73 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.203269E+11 20573.73 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.190266E+11 20573.73 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.211910E+11 20573.73 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.189279E+11 20573.73 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.196603E+11 20573.73 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.194299E+11 20573.73 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.190266E+11 20573.73 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.235627E+12     0.424397E+12    
Minimum of Months 0.178333E+11 20573.73   0.325565E+11 13457.54  
Maximum of Months 0.211910E+11 20573.73   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321286E+12    
Minimum of Months 0.160156E+11 18476.66   0.244881E+11 18128.59  
Maximum of Months 0.190310E+11 18476.66   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321285E+12    
Minimum of Months 0.160156E+11 18476.66   0.244880E+11 18128.52  
Maximum of Months 0.190310E+11 18476.66   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.176563E+11 18476.66 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.160156E+11 18476.66 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.190310E+11 18476.66 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.169985E+11 18476.66 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.183436E+11 18476.66 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.182550E+11 18476.66 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.170872E+11 18476.66 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.190310E+11 18476.66 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.169985E+11 18476.66 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.176563E+11 18476.66 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.174494E+11 18476.66 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.170872E+11 18476.66 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.211610E+12     0.321285E+12    
Minimum of Months 0.160156E+11 18476.66   0.244880E+11 18128.52  
Maximum of Months 0.190310E+11 18476.66   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221693E+10 2319.93 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.201092E+10 2319.93 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.238953E+10 2319.93 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.213434E+10 2319.93 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.230323E+10 2319.93 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.229209E+10 2319.93 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.214547E+10 2319.93 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.238953E+10 2319.93 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.213434E+10 2319.93 01-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.221693E+10 2319.93 02-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.219094E+10 2319.93 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.214547E+10 2319.93 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.265697E+11     0.403423E+11    
Minimum of Months 0.201092E+10 2319.93   0.307485E+10 2276.32  
Maximum of Months 0.238953E+10 2319.93   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259981E+11    
Minimum of Months 0.129591E+10 1495.05   0.198155E+10 1466.95  
Maximum of Months 0.153990E+10 1495.05   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.221698E+10 2319.98 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.201096E+10 2319.98 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.238958E+10 2319.98 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.213438E+10 2319.98 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.230328E+10 2319.98 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.229214E+10 2319.98 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.214552E+10 2319.98 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.238958E+10 2319.98 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.213438E+10 2319.98 01-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.221698E+10 2319.98 02-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.219099E+10 2319.98 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.214552E+10 2319.98 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.265703E+11     0.403429E+11    
Minimum of Months 0.201096E+10 2319.98   0.307490E+10 2276.35  
Maximum of Months 0.238958E+10 2319.98   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142867E+10 1495.05 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.129591E+10 1495.05 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.153990E+10 1495.05 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.137545E+10 1495.05 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.148429E+10 1495.05 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.147711E+10 1495.05 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.138262E+10 1495.05 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.153990E+10 1495.05 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.137545E+10 1495.05 01-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.142867E+10 1495.05 02-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.141193E+10 1495.05 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.138262E+10 1495.05 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.171225E+11     0.259979E+11    
Minimum of Months 0.129591E+10 1495.05   0.198154E+10 1466.94  
Maximum of Months 0.153990E+10 1495.05   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.364635E+09 381.58 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.330751E+09 381.58 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.393025E+09 381.58 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.351051E+09 381.58 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.378830E+09 381.58 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.376998E+09 381.58 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.352883E+09 381.58 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.393025E+09 381.58 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.351051E+09 381.58 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.364635E+09 381.58 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.360362E+09 381.58 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.352883E+09 381.58 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.437013E+10     0.153881E+12    
Minimum of Months 0.330751E+09 381.58   0.505780E+10 1948.61  
Maximum of Months 0.393025E+09 381.58   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554336E+10 5800.91 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.502824E+10 5800.91 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.597494E+10 5800.91 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.533685E+10 5800.91 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.575915E+10 5800.91 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.573131E+10 5800.91 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.536469E+10 5800.91 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.597494E+10 5800.91 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.533685E+10 5800.91 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.554336E+10 5800.91 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.547839E+10 5800.91 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.536469E+10 5800.91 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.664368E+11     0.749486E+13    
Minimum of Months 0.502824E+10 5800.91   0.246344E+12 94908.13  
Maximum of Months 0.597494E+10 5800.91   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.196603E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.178333E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.189279E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.204256E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.203269E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.190266E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.189279E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.196603E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.194299E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.190266E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.235627E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.178333E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.211910E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.176563E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.169985E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.183436E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.182550E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.170872E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.169985E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.176563E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.174494E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.170872E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.211610E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.160156E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.190310E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 491476.83 0.519750E+09
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 81550.31 0.606496E+09
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 6404.13 0.644015E+09
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 622869.85 0.373473E+09
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 91.77 0.443286E+09
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 50738.04 0.237088E+09
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 3492589.11 0.164388E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 3667314.46 0.204201E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 5763898.03 0.206212E+09
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 21110959.59 0.330666E+09
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 1262122.20 0.491101E+09
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 354069.55 0.538222E+09
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 36904083.88 0.475890E+10
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 91.77 0.164388E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 21110959.59 0.644015E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 386654.74 0.345741E+09
February 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 54365.53 0.396521E+09
March 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 20114.50 0.419344E+09
April 0.936002E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 294849.27 0.241492E+09
May 0.101394E+10 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 59.41 0.294059E+09
June 0.101113E+10 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 33813.59 0.153642E+09
July 0.938820E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 2271836.95 0.104808E+09
August 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 2487884.13 0.127163E+09
September 0.936002E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 3849815.60 0.136230E+09
October 0.973041E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 13698375.95 0.213983E+09
November 0.963541E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 788008.64 0.319168E+09
December 0.938820E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 289032.84 0.345807E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 24174811.17 0.309796E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 59.41 0.104808E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 13698375.95 0.419344E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 409744.69 0.538909E+09
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 81513.59 0.617973E+09
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 155.71 0.642151E+09
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 412986.51 0.375693E+09
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 90.20 0.430515E+09
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 50739.90 0.227363E+09
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 3635348.71 0.158322E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 3562720.43 0.204106E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 5707822.67 0.220651E+09
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 18342634.89 0.352819E+09
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 174103.87 0.514178E+09
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 305107.80 0.564040E+09
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 32682968.97 0.484672E+10
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 90.20 0.158322E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 18342634.89 0.642151E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 324159.26 0.367916E+09
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 54368.06 0.445921E+09
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 105.86 0.475962E+09
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 290250.00 0.288583E+09
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 60.69 0.322608E+09
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 33819.75 0.176603E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 2305857.42 0.129446E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 2365503.44 0.163318E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 3834407.39 0.155532E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 13234104.16 0.251066E+09
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 432188.44 0.369361E+09
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 220171.37 0.412117E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 23094995.85 0.355843E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 60.69 0.129446E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 13234104.16 0.475962E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 2038192.23 0.104711E+10
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 171984.70 0.121597E+10
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 407591.09 0.132257E+10
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 2763169.37 0.786733E+09
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.959374E+09
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 94915.93 0.522526E+09
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 8381565.73 0.372201E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 8747371.11 0.462264E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 13283724.13 0.443773E+09
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 50220823.11 0.687051E+09
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 5894051.47 0.100163E+10
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 2736770.75 0.106375E+10
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 94740159.62 0.988496E+10
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.372201E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 50220823.11 0.132257E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 1372820.52 0.714919E+09
February 0.649041E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 131455.92 0.823798E+09
March 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 88281.18 0.896233E+09
April 0.688021E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 614567.08 0.552913E+09
May 0.744847E+09 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.658013E+09
June 0.742030E+09 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 63247.40 0.352231E+09
July 0.690839E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 5026420.40 0.263387E+09
August 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 5224680.75 0.325524E+09
September 0.688021E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 8870582.88 0.307029E+09
October 0.715730E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 31043980.90 0.468232E+09
November 0.708685E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 2710113.32 0.679616E+09
December 0.690839E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 1491752.98 0.723092E+09
                   
Annual Sum or Average 0.858171E+10 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 56637903.33 0.676499E+10
Minimum of Months 0.649041E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.263387E+09
Maximum of Months 0.773965E+09 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 31043980.90 0.896233E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 845429.31 0.120841E+10
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 171961.27 0.135987E+10
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.140818E+10
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 1207298.05 0.848451E+09
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.962415E+09
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 94917.87 0.507667E+09
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 8724566.19 0.368628E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 7848354.69 0.487567E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 13000376.99 0.510302E+09
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 41563434.75 0.802592E+09
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 350470.17 0.115562E+10
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 631031.33 0.125598E+10
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 74437840.63 0.108757E+11
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.368628E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 41563434.75 0.140818E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 1220248.83 0.730803E+09
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 200487.74 0.853124E+09
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 249033.19 0.918852E+09
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 1844759.73 0.585486E+09
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.693203E+09
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 63274.82 0.374275E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 6338785.05 0.285446E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 6315216.87 0.353439E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 8962774.33 0.334336E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 32903427.97 0.497739E+09
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 3511249.54 0.708607E+09
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 2058006.36 0.754140E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 63667264.42 0.708945E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.285446E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 32903427.97 0.918852E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.221693E+10 0.339718E+10 0.00 0.00 0.00 0.00 4763698.54 0.110886E+10
February 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 335954.85 0.128825E+10
March 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 926151.07 0.145687E+10
April 0.145243E+10 0.213434E+10 0.328108E+10 0.00 0.00 0.00 0.00 4938548.54 0.900189E+09
May 0.157338E+10 0.230323E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.110839E+10
June 0.156900E+10 0.229209E+10 0.339353E+10 0.00 0.00 0.00 0.00 91341.09 0.627523E+09
July 0.145680E+10 0.214547E+10 0.334664E+10 0.00 0.00 0.00 0.00 10339013.58 0.458598E+09
August 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 10785851.05 0.557333E+09
September 0.145243E+10 0.213434E+10 0.327926E+10 0.00 0.00 0.00 0.00 16259951.53 0.519887E+09
October 0.150991E+10 0.221693E+10 0.339809E+10 0.00 0.00 0.00 0.00 62521308.48 0.766216E+09
November 0.149516E+10 0.219094E+10 0.332024E+10 0.00 0.00 0.00 0.00 10167621.00 0.107455E+10
December 0.145680E+10 0.214547E+10 0.334573E+10 0.00 0.00 0.00 0.00 10725107.91 0.112796E+10
                   
Annual Sum or Average 0.181194E+11 0.265697E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.131855E+09 0.109946E+11
Minimum of Months 0.136985E+10 0.201092E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.458598E+09
Maximum of Months 0.163685E+10 0.238953E+10 0.352283E+10 0.00 0.00 0.00 0.00 62521308.48 0.145687E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218927E+10 0.00 0.00 0.00 0.00 2329951.00 0.775539E+09
February 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 130343.79 0.898966E+09
March 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 169648.88 0.101029E+10
April 0.936002E+09 0.137545E+10 0.211446E+10 0.00 0.00 0.00 0.00 817444.74 0.651356E+09
May 0.101394E+10 0.148429E+10 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.777692E+09
June 0.101113E+10 0.147711E+10 0.218692E+10 0.00 0.00 0.00 0.00 60879.89 0.432534E+09
July 0.938820E+09 0.138262E+10 0.215670E+10 0.00 0.00 0.00 0.00 5877610.31 0.333472E+09
August 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 6038353.05 0.404739E+09
September 0.936002E+09 0.137545E+10 0.211328E+10 0.00 0.00 0.00 0.00 10814740.60 0.372731E+09
October 0.973041E+09 0.142867E+10 0.218986E+10 0.00 0.00 0.00 0.00 36774547.58 0.539285E+09
November 0.963541E+09 0.141193E+10 0.213969E+10 0.00 0.00 0.00 0.00 4014591.78 0.750173E+09
December 0.938820E+09 0.138262E+10 0.215612E+10 0.00 0.00 0.00 0.00 3035475.88 0.787112E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259981E+11 0.00 0.00 0.00 0.00 70063587.51 0.773389E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.333472E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227025E+10 0.00 0.00 0.00 0.00 36774547.58 0.101029E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.221698E+10 0.339723E+10 0.00 0.00 0.00 0.00 1152911.25 0.133815E+10
February 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 189697.61 0.149782E+10
March 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.158212E+10
April 0.145246E+10 0.213438E+10 0.328113E+10 0.00 0.00 0.00 0.00 1745286.51 0.988339E+09
May 0.157341E+10 0.230328E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.111650E+10
June 0.156904E+10 0.229214E+10 0.339359E+10 0.00 0.00 0.00 0.00 91343.72 0.608802E+09
July 0.145684E+10 0.214552E+10 0.334669E+10 0.00 0.00 0.00 0.00 10726010.44 0.454601E+09
August 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 9351952.72 0.593708E+09
September 0.145246E+10 0.213438E+10 0.327931E+10 0.00 0.00 0.00 0.00 15737206.37 0.613899E+09
October 0.150994E+10 0.221698E+10 0.339814E+10 0.00 0.00 0.00 0.00 51103363.32 0.932408E+09
November 0.149520E+10 0.219099E+10 0.332029E+10 0.00 0.00 0.00 0.00 399237.37 0.130460E+10
December 0.145684E+10 0.214552E+10 0.334578E+10 0.00 0.00 0.00 0.00 735722.21 0.140312E+10
                   
Annual Sum or Average 0.181198E+11 0.265703E+11 0.403429E+11 0.00 0.00 0.00 0.00 91232731.52 0.124341E+11
Minimum of Months 0.136988E+10 0.201096E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.454601E+09
Maximum of Months 0.163688E+10 0.238958E+10 0.352288E+10 0.00 0.00 0.00 0.00 51103363.32 0.158212E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.142867E+10 0.218926E+10 0.00 0.00 0.00 0.00 2235044.48 0.809743E+09
February 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 346614.01 0.948074E+09
March 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 440264.28 0.104349E+10
April 0.936002E+09 0.137545E+10 0.211444E+10 0.00 0.00 0.00 0.00 2466680.15 0.689264E+09
May 0.101394E+10 0.148429E+10 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.819442E+09
June 0.101113E+10 0.147711E+10 0.218691E+10 0.00 0.00 0.00 0.00 60890.88 0.453138E+09
July 0.938820E+09 0.138262E+10 0.215669E+10 0.00 0.00 0.00 0.00 7888551.20 0.352268E+09
August 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 8136005.04 0.432010E+09
September 0.936002E+09 0.137545E+10 0.211327E+10 0.00 0.00 0.00 0.00 11099150.51 0.402447E+09
October 0.973041E+09 0.142867E+10 0.218984E+10 0.00 0.00 0.00 0.00 40688347.63 0.576673E+09
November 0.963541E+09 0.141193E+10 0.213967E+10 0.00 0.00 0.00 0.00 5055425.10 0.795899E+09
December 0.938820E+09 0.138262E+10 0.215610E+10 0.00 0.00 0.00 0.00 3929720.27 0.837870E+09
                   
Annual Sum or Average 0.116768E+11 0.171225E+11 0.259979E+11 0.00 0.00 0.00 0.00 82346693.55 0.816032E+10
Minimum of Months 0.882782E+09 0.129591E+10 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.352268E+09
Maximum of Months 0.105485E+10 0.153990E+10 0.227023E+10 0.00 0.00 0.00 0.00 40688347.63 0.104349E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.364635E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.330751E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.393025E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.351051E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.378830E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.376998E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.352883E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.393025E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.351051E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.364635E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.360362E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.352883E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.437013E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.330751E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.393025E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.554336E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.502824E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.597494E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.533685E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.575915E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.573131E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.536469E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.597494E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.533685E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.554336E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.547839E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.536469E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.664368E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.502824E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.597494E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 498129.59 0.113629E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90445.56 0.131622E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.138061E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 643902.10 0.811641E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.941958E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11468.86 0.504716E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4603090.91 0.365295E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4307936.74 0.462825E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10087206.03 0.454719E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36906253.35 0.729750E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1190417.79 0.107559E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 264639.24 0.118110E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58603490.16 0.103607E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.365295E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36906253.35 0.138061E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1363419.56 0.191061E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 186099.65 0.222524E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.235212E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1920669.41 0.138502E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.163813E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17428.40 0.878332E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8548071.78 0.639989E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7867714.94 0.813873E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18064706.25 0.791316E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68590368.58 0.125119E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4302591.74 0.183079E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 832238.68 0.197822E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111693E+09 0.176948E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.639989E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68590368.58 0.235212E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2895625.66 0.180512E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40020.86 0.214146E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.238572E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 188300.43 0.155796E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.185226E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107527E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3337888.67 0.845621E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2375949.04 0.972036E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17973370.34 0.932586E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63491310.66 0.128243E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4897103.10 0.177794E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1153377.37 0.185075E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96352946.11 0.184792E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.845621E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63491310.66 0.238572E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 20573.73 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 20573.73 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 20573.73 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 20573.73 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 20573.73 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 20573.73 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 20573.73 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 20573.73 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 20573.73 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 20573.73 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 20573.73 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 20573.73 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   20573.73   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   20573.73   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 18476.66 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 18476.66 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 18476.66 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 18476.66 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 18476.66 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 18476.66 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 18476.66 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 18476.66 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 18476.66 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 18476.66 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 18476.66 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 18476.66 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   18476.66   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 22.77 14-JAN-11:00 1287.91 02-JAN-02:55
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 25.68 01-FEB-12:00 1137.25 25-FEB-03:00
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 1.00 11-MAR-13:10 1224.20 28-MAR-22:00
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 69.90 30-APR-10:53 768.17 17-APR-03:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.03 03-MAY-12:00 715.72 20-MAY-17:57
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 14.47 29-JUN-11:00 503.29 07-JUN-01:00
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 63.37 31-JUL-13:00 388.30 09-JUL-17:10
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 52.39 06-AUG-12:50 351.59 21-AUG-24:00
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 154.89 29-SEP-14:00 414.04 04-SEP-18:00
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 448.08 15-OCT-13:00 824.62 30-OCT-03:00
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 135.97 19-NOV-13:00 1082.95 23-NOV-04:00
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 22.65 05-DEC-10:00 999.28 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.03   351.59  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 448.08   1287.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 18.37 14-JAN-15:00 862.45 02-JAN-02:55
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 17.12 01-FEB-12:00 729.86 25-FEB-03:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 3.73 11-MAR-14:00 778.51 28-MAR-22:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 25.58 26-APR-13:00 497.81 17-APR-03:00
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.02 03-MAY-12:00 454.55 27-MAY-05:00
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 9.65 29-JUN-11:00 325.56 07-JUN-01:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 42.25 31-JUL-13:00 253.45 02-JUL-18:57
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 42.30 06-AUG-12:50 217.17 21-AUG-24:00
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 103.26 29-SEP-14:00 323.90 03-SEP-07:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 315.82 15-OCT-12:50 549.11 30-OCT-03:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 105.86 19-NOV-13:00 699.69 23-NOV-04:00
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 17.12 17-DEC-13:00 648.26 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 0.02   217.17  
Maximum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 315.82   862.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 19.52 14-JAN-11:00 1148.94 02-JAN-02:55
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 25.68 01-FEB-12:00 1104.20 25-FEB-03:00
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.02 11-MAR-14:00 1192.31 28-MAR-22:00
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 38.37 26-APR-13:00 753.65 17-APR-03:00
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.03 03-MAY-12:00 670.13 20-MAY-17:57
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 14.47 29-JUN-11:00 493.12 07-JUN-01:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 69.68 23-JUL-10:50 376.97 02-JUL-18:57
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 51.05 17-AUG-14:00 346.26 21-AUG-24:00
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 152.31 29-SEP-14:00 462.37 24-SEP-15:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 370.77 15-OCT-12:56 853.89 30-OCT-03:00
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 19.21 19-NOV-12:55 1100.71 23-NOV-04:00
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 22.65 05-DEC-10:00 1014.50 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.02   346.26  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 370.77   1192.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 17.36 14-JAN-11:00 888.26 02-JAN-02:55
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 17.12 01-FEB-12:00 851.58 12-FEB-19:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.02 11-MAR-14:00 897.47 28-MAR-22:00
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 30.13 30-APR-10:53 630.11 16-APR-17:50
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.02 03-MAY-12:00 604.23 20-MAY-17:57
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 9.65 29-JUN-11:00 406.74 03-JUN-17:08
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 42.25 31-JUL-13:00 389.61 09-JUL-17:10
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 34.03 17-AUG-14:00 311.22 27-AUG-17:50
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 103.26 29-SEP-14:00 380.91 03-SEP-16:20
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 294.33 15-OCT-09:00 634.30 11-OCT-02:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 50.25 19-NOV-13:00 835.13 23-NOV-04:00
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 15.10 05-DEC-10:00 752.48 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.02   311.22  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 294.33   897.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 126.45 15-JAN-10:00 2226.30 27-JAN-04:55
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 56.95 01-FEB-12:00 2245.87 25-FEB-03:00
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 39.65 11-MAR-14:00 2507.95 28-MAR-21:03
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 252.39 30-APR-11:20 1555.32 21-APR-22:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1561.37 20-MAY-17:53
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 30.25 29-JUN-11:00 1071.74 06-JUN-21:10
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 206.61 23-JUL-11:00 842.02 02-JUL-18:53
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 179.30 06-AUG-12:50 774.23 21-AUG-23:53
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 359.29 29-SEP-14:00 855.48 04-SEP-17:57
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 1082.79 15-OCT-08:52 1647.10 30-OCT-03:00
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 434.50 19-NOV-12:52 2102.53 23-NOV-04:00
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 240.71 25-DEC-12:00 2051.43 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.00   774.23  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 1082.79   2507.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 81.35 15-JAN-14:50 1483.03 27-JAN-04:55
February 1239.33 01-FEB-08:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 37.96 01-FEB-12:00 1460.97 08-FEB-05:53
March 1239.33 01-MAR-08:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 15.32 11-MAR-14:00 1663.34 28-MAR-21:03
April 1239.33 03-APR-07:10 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 57.82 26-APR-13:00 1035.58 17-APR-03:00
May 1239.33 01-MAY-07:10 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 980.93 20-MAY-17:53
June 1239.33 01-JUN-07:10 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 20.16 29-JUN-11:00 723.76 04-JUN-14:00
July 1239.33 03-JUL-07:10 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 96.38 31-JUL-13:00 618.13 04-JUL-13:55
August 1239.33 01-AUG-07:10 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 77.63 17-AUG-14:00 514.53 21-AUG-23:53
September 1239.33 01-SEP-07:10 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 239.51 29-SEP-14:00 686.78 03-SEP-07:00
October 1239.33 02-OCT-07:10 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 677.48 15-OCT-13:10 1135.11 30-OCT-03:00
November 1239.33 01-NOV-07:10 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 255.11 19-NOV-13:10 1399.86 23-NOV-04:00
December 1239.33 01-DEC-08:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 91.39 17-DEC-13:10 1369.38 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   1495.05   1466.95   0.00 0.00 0.00 0.00 0.00   514.53  
Maximum of Months 1239.33   1495.05   1466.95   0.00 0.00 0.00 0.00 677.48   1663.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 43.27 14-JAN-11:00 2350.92 07-JAN-02:00
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 56.95 01-FEB-12:00 2287.02 08-FEB-05:53
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2511.73 28-MAR-21:03
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 111.25 30-APR-10:32 1588.37 17-APR-03:00
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1498.87 20-MAY-17:53
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 30.25 29-JUN-11:00 1058.35 07-JUN-01:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 243.67 23-JUL-11:00 839.44 02-JUL-18:53
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 116.46 17-AUG-14:00 791.49 21-AUG-23:53
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 337.02 29-SEP-14:00 1062.26 04-SEP-14:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 836.88 15-OCT-12:46 1887.31 30-OCT-03:00
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 36.29 18-NOV-13:00 2296.97 23-NOV-04:00
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 50.23 05-DEC-10:00 2201.95 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.00   791.49  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 836.88   2511.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 59.59 14-JAN-12:40 1510.36 27-JAN-04:55
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 49.12 01-FEB-12:00 1504.53 25-FEB-03:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 27.21 11-MAR-12:30 1677.16 28-MAR-21:03
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 186.22 30-APR-11:20 1281.68 16-APR-17:42
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1361.72 20-MAY-17:53
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 20.17 29-JUN-11:00 890.43 03-JUN-17:10
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 222.33 23-JUL-11:00 790.52 09-JUL-17:30
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 159.23 06-AUG-12:40 645.88 27-AUG-18:10
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 239.53 29-SEP-14:00 863.50 03-SEP-16:53
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 753.64 15-OCT-08:52 1184.95 30-OCT-03:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 281.50 19-NOV-12:30 1468.95 23-NOV-04:00
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 150.02 25-DEC-12:00 1419.06 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.00   645.88  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 753.64   1677.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 2319.93 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 358.68 15-JAN-10:00 2519.66 27-JAN-05:08
February 2010.79 01-FEB-10:09 2319.93 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 76.64 01-FEB-12:00 2468.47 08-FEB-05:57
March 2010.79 01-MAR-10:09 2319.93 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 70.60 11-MAR-13:20 3078.86 28-MAR-21:03
April 2010.79 03-APR-09:09 2319.93 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 378.64 30-APR-11:20 1769.33 21-APR-22:00
May 2010.79 01-MAY-09:09 2319.93 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1851.86 20-MAY-17:53
June 2010.79 01-JUN-09:09 2319.93 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 32.97 29-JUN-11:00 1272.01 06-JUN-21:10
July 2010.79 03-JUL-09:09 2319.93 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 282.45 23-JUL-11:00 1074.60 02-JUL-18:53
August 2010.79 01-AUG-09:09 2319.93 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 254.55 06-AUG-13:00 900.11 21-AUG-23:53
September 2010.79 01-SEP-09:09 2319.93 01-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 441.16 29-SEP-14:00 1054.48 04-SEP-17:53
October 2010.79 02-OCT-09:09 2319.93 02-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 1404.80 15-OCT-08:52 1755.33 30-OCT-03:00
November 2010.79 01-NOV-09:09 2319.93 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 639.70 19-NOV-13:00 2143.74 23-NOV-04:00
December 2010.79 01-DEC-10:09 2319.93 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 548.66 25-DEC-11:53 2274.88 13-DEC-05:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 0.00   900.11  
Maximum of Months 2010.79   2319.93   2276.32   0.00 0.00 0.00 0.00 1404.80   3078.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 172.91 15-JAN-10:00 1690.00 27-JAN-05:05
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 44.42 01-FEB-12:00 1645.77 08-FEB-06:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 22.54 11-MAR-14:00 2048.46 28-MAR-21:03
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 69.08 26-APR-13:00 1213.99 16-APR-17:53
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1194.19 29-MAY-12:53
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 21.98 29-JUN-11:00 969.35 04-JUN-14:00
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 116.31 31-JUL-13:00 792.76 04-JUL-14:00
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 93.70 17-AUG-14:00 634.72 27-AUG-18:30
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 294.11 29-SEP-14:00 776.01 03-SEP-18:00
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 797.23 15-OCT-12:40 1227.34 30-OCT-03:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 349.57 19-NOV-13:00 1453.66 23-NOV-04:00
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 212.06 17-DEC-13:00 1531.24 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 0.00   634.72  
Maximum of Months 1295.83   1495.05   1466.95   0.00 0.00 0.00 0.00 797.23   2048.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 2319.98 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 130.70 15-JAN-10:00 2721.16 06-JAN-23:00
February 2010.83 01-FEB-10:09 2319.98 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 66.63 01-FEB-12:00 2778.18 20-FEB-15:00
March 2010.83 01-MAR-10:09 2319.98 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3085.89 28-MAR-21:03
April 2010.83 03-APR-09:09 2319.98 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 189.44 30-APR-10:30 1896.90 16-APR-17:53
May 2010.83 01-MAY-09:09 2319.98 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1786.48 20-MAY-17:53
June 2010.83 01-JUN-09:09 2319.98 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 32.97 29-JUN-11:00 1251.21 04-JUN-14:00
July 2010.83 03-JUL-09:09 2319.98 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 315.74 23-JUL-11:00 1074.90 02-JUL-18:53
August 2010.83 01-AUG-09:09 2319.98 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 140.54 17-AUG-14:00 960.99 27-AUG-18:10
September 2010.83 01-SEP-09:09 2319.98 01-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 403.24 29-SEP-12:05 1323.68 24-SEP-15:00
October 2010.83 02-OCT-09:09 2319.98 02-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 1092.45 15-OCT-08:52 2089.71 30-OCT-03:00
November 2010.83 01-NOV-09:09 2319.98 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 42.46 18-NOV-13:00 2435.17 23-NOV-04:00
December 2010.83 01-DEC-10:09 2319.98 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 58.77 05-DEC-10:00 2493.37 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 0.00   960.99  
Maximum of Months 2010.83   2319.98   2276.35   0.00 0.00 0.00 0.00 1092.45   3085.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1495.05 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 166.43 15-JAN-10:00 1708.09 06-JAN-23:00
February 1295.83 01-FEB-10:09 1495.05 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 64.85 01-FEB-12:00 1658.45 08-FEB-02:00
March 1295.83 01-MAR-10:09 1495.05 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 42.88 11-MAR-12:30 2065.20 28-MAR-21:03
April 1295.83 03-APR-09:09 1495.05 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 256.73 30-APR-11:13 1684.75 16-APR-17:53
May 1295.83 01-MAY-09:09 1495.05 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1644.77 20-MAY-17:53
June 1295.83 01-JUN-09:09 1495.05 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 21.98 29-JUN-11:00 1111.39 03-JUN-17:10
July 1295.83 03-JUL-09:09 1495.05 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 267.03 23-JUL-11:00 1040.97 09-JUL-17:20
August 1295.83 01-AUG-09:09 1495.05 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 195.73 06-AUG-12:50 814.43 27-AUG-18:10
September 1295.83 01-SEP-09:09 1495.05 01-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 294.11 29-SEP-14:00 1037.94 03-SEP-16:40
October 1295.83 02-OCT-09:09 1495.05 02-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 983.22 15-OCT-08:52 1314.46 30-OCT-03:00
November 1295.83 01-NOV-09:09 1495.05 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 383.28 19-NOV-12:12 1557.44 23-NOV-04:00
December 1295.83 01-DEC-10:09 1495.05 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 166.84 17-DEC-12:53 1605.48 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 0.00   814.43  
Maximum of Months 1295.83   1495.05   1466.94   0.00 0.00 0.00 0.00 983.22   2065.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 381.58 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 381.58 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 381.58 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 381.58 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 381.58 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 381.58 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 381.58 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 381.58 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 381.58 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 381.58 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 381.58 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 381.58 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   381.58   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   381.58   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 5800.91 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 5800.91 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 5800.91 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 5800.91 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 5800.91 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 5800.91 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 5800.91 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 5800.91 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 5800.91 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 5800.91 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 5800.91 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 5800.91 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   5800.91   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   5800.91   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.14 14-JAN-11:00 2838.31 02-JAN-02:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.36 01-FEB-12:00 2484.74 25-FEB-03:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2633.68 28-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.02 30-APR-11:00 1637.20 17-APR-03:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1482.36 27-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.73 29-JUN-11:00 1042.85 07-JUN-01:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102.66 31-JUL-13:00 782.27 02-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.90 17-AUG-14:00 749.88 21-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 282.93 29-SEP-13:50 899.51 04-SEP-18:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 844.99 15-OCT-13:00 1772.17 30-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.87 19-NOV-13:00 2413.17 23-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.20 05-DEC-10:00 2163.50 23-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   749.88  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 844.99   2838.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.65 15-JAN-10:00 4027.22 02-JAN-02:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.68 01-FEB-12:00 4228.58 25-FEB-03:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4508.13 28-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.89 30-APR-10:53 2748.91 17-APR-03:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2609.11 27-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.83 29-JUN-11:00 1812.86 07-JUN-01:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 192.13 23-JUL-10:53 1359.38 02-JUL-18:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.47 06-AUG-12:53 1314.43 21-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 506.09 29-SEP-13:50 1516.67 04-SEP-18:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1590.06 15-OCT-12:51 2997.62 30-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 436.70 19-NOV-12:52 4109.04 23-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.08 05-DEC-10:00 3734.86 23-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1314.43  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1590.06   4508.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 547.14 15-JAN-10:00 3863.05 27-JAN-04:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.04 01-FEB-12:00 3948.31 25-FEB-03:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4755.33 28-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.30 26-APR-13:00 3046.39 16-APR-17:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 3204.26 07-MAY-14:52
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 2583.38 04-JUN-14:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 132.12 31-JUL-13:00 2034.63 09-JUL-12:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.18 17-AUG-14:00 1607.00 27-AUG-17:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 529.24 29-SEP-13:20 2024.45 24-SEP-15:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1810.99 15-OCT-08:52 2869.37 11-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 364.42 19-NOV-13:00 3448.03 23-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.82 04-DEC-10:00 3661.62 23-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1607.00  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1810.99   4755.33  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 109087.97 23-JAN-04:03 0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
February 110018.52 21-FEB-04:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 110567.16 20-MAR-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 110124.99 17-APR-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 107313.42 22-MAY-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 106263.77 05-JUN-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 99412.28 17-JUL-03:02 0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
August 95510.00 28-AUG-03:02 0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
September 98928.89 19-SEP-03:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 109906.31 30-OCT-03:02 0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
November 110229.24 06-NOV-04:03 0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
December 110923.87 11-DEC-04:02 0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 95510.00   0.00 4572.22 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 110923.87   0.00 5715.28 67287.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 94933.39 02-JAN-04:02 0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
February 92459.84 21-FEB-04:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
March 91356.22 20-MAR-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
April 90545.77 17-APR-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 92141.81 30-MAY-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
June 93617.11 12-JUN-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
July 88784.73 06-JUL-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
August 87618.97 23-AUG-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
September 94326.25 05-SEP-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 92240.43 23-OCT-03:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 93927.82 20-NOV-04:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 93614.80 11-DEC-04:02 0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87618.97   0.00 5132.72 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 94933.39   0.00 6159.27 48342.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 79506.39 20-JAN-06:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
February 79576.04 15-FEB-06:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 79483.82 23-MAR-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 80786.00 27-APR-04:03 0.00 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 80513.69 04-MAY-04:03 0.00 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
June 81408.14 21-JUN-04:02 0.00 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 80964.82 14-JUL-04:03 0.00 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
August 80944.80 31-AUG-04:03 0.00 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
September 83448.51 25-SEP-03:02 0.00 6159.27 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 85128.36 02-OCT-03:02 0.00 5132.72 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 82424.43 13-NOV-04:02 0.00 5132.72 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 79115.77 02-DEC-06:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 79115.77   0.00 5132.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 85128.36   8061.19 10264.30 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 38767.62 19-JAN-15:00 16014.58 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 39245.39 16-FEB-16:20 15316.26 18476.66 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 69157.68 24-MAR-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 76727.75 27-APR-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 76568.26 03-MAY-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
June 78599.12 20-JUN-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 79754.16 31-JUL-04:02 0.00 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 78693.54 18-AUG-05:02 8061.19 10264.30 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 78678.97 25-SEP-04:03 0.00 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
October 83462.29 02-OCT-03:02 0.00 5132.72 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 65881.64 01-NOV-05:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 51489.98 06-DEC-06:03 6448.95 8211.44 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 38767.62   0.00 5132.72 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 83462.29   16014.58 18476.66 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6283.75 17-JAN-13:40 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 7.24
February 5417.76 01-FEB-12:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 25.68 0.00
March 6218.16 13-MAR-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 109.92
April 7494.13 26-APR-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 22.54 0.00
May 8678.84 01-MAY-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
June 11716.29 26-JUN-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 5.70
July 11801.61 05-JUL-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
August 11527.42 01-AUG-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 45.73
September 11638.38 25-SEP-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 5.78
October 10637.47 02-OCT-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 32.51
November 6075.26 28-NOV-14:10 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 6.36 0.00
December 6655.73 05-DEC-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 12.93 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5417.76   809.73 1031.03 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11801.61   2010.79 2319.93 4046.79 0.00 0.00 0.00 0.00 25.68 109.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6143.55 20-JAN-09:10 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 3.60
February 6980.14 21-FEB-09:10 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 36.22
March 8095.64 23-MAR-08:40 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
April 14325.13 30-APR-08:43 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 81.26
May 10147.17 28-MAY-07:53 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 195.11
June 11586.75 18-JUN-07:33 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 117.83
July 15948.18 23-JUL-08:23 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 36.72
August 10155.69 13-AUG-07:33 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 73.11
September 10915.30 03-SEP-08:32 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 143.13
October 16199.39 15-OCT-08:43 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 186.89 0.00
November 6815.30 19-NOV-09:00 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 48.49
December 6688.20 05-DEC-09:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6143.55   260.91 332.25 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16199.39   1239.33 1495.05 1955.93 0.00 0.00 0.00 0.00 186.89 195.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15734.95 18-JAN-13:30 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 13.14 0.00
February 14785.05 21-FEB-13:20 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 44.22
March 13404.05 23-MAR-13:20 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 25.20
April 11773.18 26-APR-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 35.53 0.00
May 8852.16 04-MAY-12:30 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 8.52
June 9275.95 26-JUN-05:03 809.75 1031.05 4046.85 0.00 0.00 0.00 0.00 0.00 5.52
July 12782.23 31-JUL-05:03 809.75 1031.05 4046.85 0.00 0.00 0.00 0.00 0.00 47.77
August 12572.65 30-AUG-13:00 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
September 15988.26 29-SEP-13:50 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 150.93 0.00
October 20994.55 01-OCT-12:32 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 127.53
November 21280.47 19-NOV-12:12 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 87.03
December 20300.75 03-DEC-13:02 404.87 515.58 3035.14 0.00 0.00 0.00 0.00 0.00 364.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8852.16   404.87 515.58 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21280.47   2010.83 2319.98 4046.85 0.00 0.00 0.00 0.00 150.93 364.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8763.50 18-JAN-14:50 1295.83 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 6.22
February 10120.84 22-FEB-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 58.72
March 13919.15 24-MAR-05:03 521.82 664.43 2607.89 0.00 0.00 0.00 0.00 0.00 39.68
April 20651.18 30-APR-16:02 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 143.54
May 16254.42 01-MAY-05:03 521.82 664.43 2607.89 0.00 0.00 0.00 0.00 0.00 0.00
June 16145.41 26-JUN-05:03 521.82 664.43 2607.89 0.00 0.00 0.00 0.00 0.00 3.81
July 21567.61 23-JUL-15:02 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 119.11
August 21330.18 13-AUG-14:12 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 126.33
September 21098.67 04-SEP-15:52 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 221.00
October 21160.50 01-OCT-14:32 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 137.50
November 16609.14 19-NOV-13:32 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 34.24
December 16251.27 05-DEC-04:02 0.00 415.32 3259.86 0.00 0.00 0.00 0.00 0.00 47.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8763.50   0.00 415.32 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21567.61   1295.83 1495.05 3259.86 0.00 0.00 0.00 0.00 0.00 221.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4658.47 18-JAN-14:20 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 1.15
February 3974.48 03-FEB-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 37.81
March 4650.82 23-MAR-15:20 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 68.50
April 6095.73 26-APR-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 49.99 0.00
May 6561.77 04-MAY-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 55.14
June 6528.96 29-JUN-16:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 29.58
July 7299.82 01-JUL-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
August 7019.61 18-AUG-15:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 76.31 0.00
September 9561.19 30-SEP-05:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 0.81
October 8699.27 05-OCT-05:03 809.73 1031.03 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
November 4148.54 10-NOV-14:30 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 176.68
December 4651.52 05-DEC-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 27.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3974.48   809.73 1031.03 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9561.19   2010.79 2319.93 5058.48 0.00 0.00 0.00 0.00 76.31 176.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5233.30 20-JAN-09:40 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 29.19
February 5095.67 21-FEB-10:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
March 7456.22 23-MAR-09:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
April 8749.37 26-APR-08:50 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 16.29
May 7853.48 18-MAY-08:50 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 49.97
June 12182.59 18-JUN-08:43 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 213.77
July 16499.34 23-JUL-08:53 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 128.25
August 14563.67 06-AUG-09:13 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 198.75
September 12857.00 10-SEP-08:23 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 164.89
October 16331.49 15-OCT-09:43 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 269.25 0.00
November 4893.66 20-NOV-09:10 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 23.54
December 5365.28 05-DEC-09:50 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 30.30 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4893.66   260.91 332.25 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16499.34   1239.33 1495.05 1955.93 0.00 0.00 0.00 0.00 269.25 213.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19671.82 22-JAN-13:53 404.87 515.58 3035.14 0.00 0.00 0.00 0.00 0.00 897.56
February 14321.43 22-FEB-13:50 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 67.72
March 12999.36 23-MAR-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 55.05
April 10910.01 26-APR-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 80.11 0.00
May 8193.61 04-MAY-12:30 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 24.35
June 7414.96 30-JUN-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 37.79
July 10015.14 31-JUL-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 138.46 0.00
August 11868.97 30-AUG-13:00 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 3.68
September 15892.19 29-SEP-12:15 3846.30 4639.96 4552.71 0.00 0.00 0.00 0.00 322.23 0.00
October 21513.42 15-OCT-13:01 708.53 902.27 5311.49 0.00 0.00 0.00 0.00 444.76 0.00
November 19734.99 19-NOV-11:02 404.87 515.58 3035.14 0.00 0.00 0.00 0.00 0.00 157.18
December 19103.60 25-DEC-11:53 404.87 515.58 3035.14 0.00 0.00 0.00 0.00 0.00 784.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7414.96   404.87 515.58 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21513.42   3846.30 4639.96 5311.49 0.00 0.00 0.00 0.00 444.76 897.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6862.21 18-JAN-15:00 1295.83 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 22.56
February 7319.92 22-FEB-16:20 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 189.70
March 9611.53 23-MAR-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 47.80
April 14486.67 30-APR-16:23 260.91 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 302.63
May 11411.71 28-MAY-17:03 0.00 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 677.59
June 17180.39 25-JUN-16:33 260.91 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 426.17
July 18121.03 04-JUL-16:32 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 0.00
August 17734.70 06-AUG-16:12 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 305.57
September 11060.99 29-SEP-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 164.16 0.00
October 17465.91 15-OCT-15:02 391.37 498.38 2933.87 0.00 0.00 0.00 0.00 281.02 0.00
November 7279.68 07-NOV-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 85.98
December 7172.12 19-DEC-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 46.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6862.21   0.00 332.25 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18121.03   1295.83 1495.05 2933.87 0.00 0.00 0.00 0.00 281.02 677.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4129.65 18-JAN-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 46.14
February 3492.13 01-FEB-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 73.01
March 4644.32 23-MAR-15:20 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 88.84
April 6593.96 26-APR-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 58.49 0.00
May 7111.49 04-MAY-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 75.19
June 7174.78 30-JUN-14:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 51.53
July 8126.84 19-JUL-15:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 116.25 0.00
August 7779.99 18-AUG-15:00 1923.11 2319.93 2276.32 0.00 0.00 0.00 0.00 91.18 0.00
September 11533.95 30-SEP-05:02 1012.16 1288.79 5058.48 0.00 0.00 0.00 0.00 0.00 1.46
October 9007.22 16-OCT-13:10 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 424.71 0.00
November 3764.35 10-NOV-14:40 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 0.00 232.63
December 4159.26 05-DEC-15:00 2010.79 2319.93 2276.32 0.00 0.00 0.00 0.00 29.45 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3492.13   1012.16 1288.79 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11533.95   2010.79 2319.93 5058.48 0.00 0.00 0.00 0.00 424.71 232.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3968.73 20-JAN-10:10 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 45.82
February 3805.67 02-FEB-10:10 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 122.27
March 6532.91 23-MAR-09:40 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 27.91
April 8262.93 26-APR-09:30 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 13.63
May 7479.56 04-MAY-09:30 1295.83 1495.05 1466.95 0.00 0.00 0.00 0.00 0.00 35.88
June 9080.93 25-JUN-09:23 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 365.46
July 12884.63 04-JUL-09:02 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 350.85
August 11215.95 13-AUG-09:23 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 0.00 261.59
September 9154.15 30-SEP-05:02 652.28 830.54 3259.88 0.00 0.00 0.00 0.00 0.00 1.01
October 16418.26 15-OCT-09:13 260.91 332.25 1955.93 0.00 0.00 0.00 0.00 486.13 0.00
November 4041.60 19-NOV-13:22 326.14 415.32 2444.91 0.00 0.00 0.00 0.00 151.42 0.00
December 4132.59 05-DEC-10:00 1239.33 1495.05 1466.95 0.00 0.00 0.00 0.00 39.18 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3805.67   260.91 332.25 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16418.26   1295.83 1495.05 3259.88 0.00 0.00 0.00 0.00 486.13 365.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18682.54 22-JAN-14:02 404.87 515.58 3035.14 0.00 0.00 0.00 0.00 0.00 1093.92
February 13932.23 22-FEB-14:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 89.27
March 13223.01 23-MAR-14:00 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 46.09
April 11515.49 26-APR-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 95.49 0.00
May 8711.30 03-MAY-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 15.72
June 8104.86 30-JUN-13:30 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 51.53
July 10923.44 31-JUL-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 166.88 0.00
August 12486.67 30-AUG-13:10 2010.83 2319.98 2276.35 0.00 0.00 0.00 0.00 0.00 15.90
September 16948.39 29-SEP-12:05 3846.30 4639.96 4552.71 0.00 0.00 0.00 0.00 403.24 0.00
October 22587.73 15-OCT-15:52 607.31 773.37 4552.71 0.00 0.00 0.00 0.00 190.56 0.00
November 22357.69 19-NOV-13:22 506.09 644.48 3793.92 0.00 0.00 0.00 0.00 0.00 280.65
December 16556.66 19-DEC-13:20 1923.15 2319.98 2276.35 0.00 0.00 0.00 0.00 26.97 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8104.86   404.87 515.58 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22587.73   3846.30 4639.96 4552.71 0.00 0.00 0.00 0.00 403.24 1093.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6570.33 18-JAN-15:00 1295.83 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 30.76
February 6971.48 22-FEB-16:20 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 238.46
March 9687.98 23-MAR-15:50 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 61.55
April 11046.33 26-APR-16:00 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 42.32
May 10849.74 28-MAY-17:03 0.00 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 851.27
June 17114.83 25-JUN-16:42 260.91 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 540.72
July 19957.03 09-JUL-16:02 326.14 415.32 2444.89 0.00 0.00 0.00 0.00 0.00 135.80
August 13788.21 20-AUG-17:33 0.00 332.25 1955.92 0.00 0.00 0.00 0.00 0.00 589.61
September 12328.96 30-SEP-05:02 652.28 830.54 3259.86 0.00 0.00 0.00 0.00 0.00 1.13
October 20296.35 15-OCT-15:52 391.37 498.38 2933.87 0.00 0.00 0.00 0.00 127.52 0.00
November 6963.45 10-NOV-14:50 1295.83 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 160.48
December 6928.82 19-DEC-15:30 1239.33 1495.05 1466.94 0.00 0.00 0.00 0.00 0.00 60.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6570.33   0.00 332.25 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20296.35   1295.83 1495.05 3259.86 0.00 0.00 0.00 0.00 127.52 851.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8328.31 17-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.43
February 7140.37 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.11
March 7070.04 20-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 176.78
April 8467.78 11-APR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 9646.56 01-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 8409.33 19-JUN-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94.72
July 9439.67 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 10044.23 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.58
September 10460.39 05-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 10673.65 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.01
November 8485.86 21-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.88
December 9100.96 26-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.29
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 7070.04   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10673.65   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4871.99 21-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 4832.21 04-FEB-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 951.18
March 4994.74 23-MAR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 146.57
April 6541.20 27-APR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
May 5571.45 01-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 6500.28 22-JUN-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 127.90
July 6671.30 01-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 6523.87 31-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.09
September 6111.82 26-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 131.63
October 7933.24 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.85
November 5053.74 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 532.03
December 4689.93 02-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4689.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7933.24   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 951.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8849.86 18-JAN-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.96
February 8818.12 01-FEB-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 374.19
March 12845.84 23-MAR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 193.30
April 17206.28 26-APR-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.49 0.00
May 16236.48 03-MAY-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136.92
June 16336.37 30-JUN-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 194.27
July 18429.59 19-JUL-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.11 0.00
August 17900.19 14-AUG-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.74 0.00
September 19724.66 29-SEP-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 502.05 0.00
October 18398.64 16-OCT-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 483.82 0.00
November 8483.97 10-NOV-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.62
December 8074.10 19-DEC-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 8074.10   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19724.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 502.05 385.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2045.85 30-JAN-16:40 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4034.44 22-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7024.47 31-MAR-24:00 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7812.54 30-APR-17:14 0.00 105.99 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3327.86 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5366.83 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7236.87 31-JUL-23:45 0.00 42.40 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7895.55 06-AUG-17:50 0.00 63.60 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
September 3524.20 30-SEP-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5332.72 31-OCT-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5900.41 07-NOV-16:20 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7838.88 25-DEC-16:10 23.38 42.40 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2045.85   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7895.55   222.14 381.58 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1861.99 30-JAN-16:50 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3767.85 22-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6267.75 31-MAR-23:40 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7288.86 27-APR-17:00 70.15 211.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2991.97 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5072.43 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6925.30 31-JUL-23:53 0.00 63.60 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7350.05 06-AUG-17:50 0.00 63.60 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
September 3378.07 30-SEP-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4921.29 31-OCT-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5539.36 07-NOV-16:20 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7326.15 18-DEC-16:20 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1861.99   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7350.05   222.14 381.58 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1821.74 18-JAN-16:10 222.14 381.58 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3762.00 22-FEB-17:00 222.14 381.58 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5846.27 31-MAR-23:20 0.00 21.20 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7364.41 26-APR-16:00 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 2672.04 31-MAY-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4932.26 30-JUN-24:00 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6814.40 31-JUL-24:00 0.00 63.60 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7499.12 20-AUG-17:30 0.00 84.79 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3304.93 30-SEP-24:00 0.00 21.20 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4667.61 31-OCT-23:50 0.00 21.20 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5518.84 10-NOV-16:20 222.14 381.58 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7327.28 19-DEC-16:30 222.14 381.58 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1821.74   0.00 21.20 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7499.12   222.14 381.58 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92704.43 18-JAN-17:00 4808.68 5800.91 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183710.63 21-FEB-17:00 4808.68 5800.91 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358135.06 31-MAR-24:00 0.00 322.29 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367252.46 27-APR-16:00 4808.68 5800.91 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175388.57 31-MAY-24:00 0.00 322.29 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267121.52 30-JUN-24:00 0.00 322.29 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359211.30 31-JUL-23:53 0.00 966.88 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 367697.22 25-AUG-16:00 4808.68 5800.91 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 175694.97 30-SEP-24:00 0.00 322.29 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267929.38 31-OCT-24:00 0.00 322.29 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276274.68 13-NOV-17:00 4808.68 5800.91 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 369381.26 19-DEC-17:05 3037.06 6445.43 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92704.43   0.00 322.29 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369381.26   4808.68 6445.43 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.182319E+13 1320566.92 24-JAN-14:30 0.162307E+12 783896.78 09-JAN-07:10
February 0.199822E+13 1439636.75 01-FEB-13:20 0.132196E+12 564312.75 10-FEB-07:10
March 0.264558E+13 1707294.40 23-MAR-15:20 0.175323E+12 753326.56 30-MAR-06:10
April 0.297485E+13 1852857.80 26-APR-15:39 0.941019E+11 613480.74 01-APR-06:10
May 0.189388E+13 1374060.70 18-MAY-15:20 0.849479E+11 268352.36 15-MAY-06:10
June 0.234622E+13 1589988.07 29-JUN-15:00 0.634310E+11 193056.73 12-JUN-20:00
July 0.288162E+13 1858287.16 31-JUL-15:50 0.595749E+11 74953.92 11-JUL-11:20
August 0.339990E+13 2015457.69 18-AUG-15:50 0.629918E+11 74991.35 31-AUG-11:50
September 0.195662E+13 1472508.33 29-SEP-15:00 0.606708E+11 165827.12 20-SEP-06:19
October 0.244227E+13 1610794.82 17-OCT-15:00 0.682474E+11 355209.46 12-OCT-06:10
November 0.258915E+13 1580896.56 28-NOV-14:09 0.105526E+12 435756.73 24-NOV-07:10
December 0.302627E+13 1787884.33 05-DEC-09:39 0.141698E+12 643326.08 13-DEC-07:10
             
Annual Sum or Average 0.299778E+14     0.121102E+13    
Minimum of Months 0.182319E+13 1320566.92   0.595749E+11 74953.92  
Maximum of Months 0.339990E+13 2015457.69   0.175323E+12 783896.78  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.328950E+12 0.892039E+11 0.811612E+12 0.169596E+12 0.189626E+12 0.391172E+11 0.00 0.132956E+12 0.616638E+11 0.461790E+09 0.00 0.00 0.00
February 0.298382E+12 0.762482E+11 0.102011E+13 0.153195E+12 0.172238E+12 0.301035E+11 0.00 0.169226E+12 0.783599E+11 0.363149E+09 0.00 0.00 0.00
March 0.354561E+12 0.781484E+11 0.146267E+13 0.169879E+12 0.195551E+12 0.311839E+11 0.00 0.252605E+12 0.100959E+12 19214979.11 0.00 0.00 0.00
April 0.316695E+12 0.694768E+11 0.170311E+13 0.164100E+12 0.202287E+12 0.469622E+11 0.00 0.346082E+12 0.126075E+12 69008067.34 0.00 0.00 0.00
May 0.341755E+12 0.663329E+11 0.820521E+12 0.169738E+12 0.205717E+12 0.508473E+11 0.00 0.152648E+12 0.863182E+11 0.00 0.00 0.00 0.00
June 0.340103E+12 0.614961E+11 0.110677E+13 0.164363E+12 0.215135E+12 0.662736E+11 0.00 0.260319E+12 0.131758E+12 0.00 0.00 0.00 0.00
July 0.318348E+12 0.647436E+11 0.143888E+13 0.169473E+12 0.227779E+12 0.878400E+11 0.00 0.418714E+12 0.155844E+12 0.00 0.00 0.00 0.00
August 0.354561E+12 0.693386E+11 0.177780E+13 0.169879E+12 0.243202E+12 0.953385E+11 0.00 0.528562E+12 0.161228E+12 0.00 0.00 0.00 0.00
September 0.316695E+12 0.730007E+11 0.784732E+12 0.164097E+12 0.213262E+12 0.677110E+11 0.00 0.208453E+12 0.128669E+12 0.00 0.00 0.00 0.00
October 0.328950E+12 0.818105E+11 0.112899E+13 0.169597E+12 0.213036E+12 0.724986E+11 0.00 0.310687E+12 0.136504E+12 0.191897E+09 0.00 0.00 0.00
November 0.325095E+12 0.847471E+11 0.140306E+13 0.164207E+12 0.192643E+12 0.423380E+11 0.00 0.267008E+12 0.109467E+12 0.587012E+09 0.00 0.00 0.00
December 0.318348E+12 0.907240E+11 0.175516E+13 0.169471E+12 0.191685E+12 0.406540E+11 0.00 0.344098E+12 0.115047E+12 0.107969E+10 0.00 0.00 0.00
                           
Annual Sum or Average 0.394244E+13 0.905271E+12 0.152134E+14 0.199759E+13 0.246216E+13 0.670868E+12 0.00 0.339136E+13 0.139189E+13 0.277176E+10 0.00 0.00 0.00
Minimum of Months 0.298382E+12 0.614961E+11 0.784732E+12 0.153195E+12 0.172238E+12 0.301035E+11 0.00 0.132956E+12 0.616638E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.354561E+12 0.907240E+11 0.177780E+13 0.169879E+12 0.243202E+12 0.953385E+11 0.00 0.528562E+12 0.161228E+12 0.107969E+10 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.980989E+11 0.00 0.642077E+11 0.00 0.00
February 0.00 0.00 0.739358E+11 0.00 0.582601E+11 0.00 0.00
March 0.00 0.00 0.108690E+12 0.00 0.666339E+11 0.00 0.00
April 0.00 0.00 0.331128E+11 0.00 0.609892E+11 0.00 0.00
May 0.00 0.00 0.216515E+11 0.00 0.632963E+11 0.00 0.00
June 0.00 0.00 0.213311E+10 0.00 0.612979E+11 0.00 0.00
July 0.00 0.00 152297.47 0.00 0.595747E+11 0.00 0.00
August 0.00 0.00 18993071.69 0.00 0.629728E+11 0.00 0.00
September 0.00 0.00 0.170774E+10 0.00 0.589631E+11 0.00 0.00
October 0.00 0.00 0.652555E+10 0.00 0.617219E+11 0.00 0.00
November 0.00 0.00 0.442686E+11 0.00 0.612570E+11 0.00 0.00
December 0.00 0.00 0.790045E+11 0.00 0.626937E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.469147E+12 0.00 0.741868E+12 0.00 0.00
Minimum of Months 0.00 0.00 152297.47 0.00 0.582601E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.108690E+12 0.00 0.666339E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 344233.60 02-JAN-08:09 57580.60 01-JAN-00:10 439129.89 02-JAN-08:09 120520.01 02-JAN-08:20 158365.29 18-JAN-15:50 64302.10 13-JAN-13:00 0.00 01-JAN-00:10
February 344233.60 01-FEB-08:09 57580.60 01-FEB-00:10 557421.28 01-FEB-08:09 120520.01 01-FEB-08:20 160522.39 03-FEB-15:50 61773.64 01-FEB-13:20 0.00 01-FEB-00:10
March 344233.60 01-MAR-08:09 57580.60 01-MAR-00:10 675712.68 01-MAR-08:09 120520.01 01-MAR-08:20 184729.35 23-MAR-15:20 61408.99 23-MAR-13:50 0.00 01-MAR-00:10
April 344233.60 03-APR-07:10 57580.60 01-APR-00:10 794004.08 03-APR-07:10 120520.01 03-APR-07:19 193528.21 26-APR-14:30 61926.11 12-APR-13:00 0.00 01-APR-00:10
May 344233.60 01-MAY-07:10 57580.60 01-MAY-00:10 439129.89 01-MAY-07:10 120520.01 01-MAY-07:19 177044.13 03-MAY-15:20 62719.96 03-MAY-12:00 0.00 01-MAY-00:10
June 344233.60 01-JUN-07:10 57580.60 01-JUN-00:10 557421.28 01-JUN-07:10 120520.01 01-JUN-07:19 186653.93 30-JUN-15:00 61870.02 29-JUN-12:00 0.00 01-JUN-00:10
July 344233.60 03-JUL-07:10 57580.60 01-JUL-00:10 675712.68 03-JUL-07:10 120520.01 03-JUL-07:19 205774.29 31-JUL-14:00 63200.70 31-JUL-15:50 0.00 01-JUL-00:10
August 344233.60 01-AUG-07:10 57580.60 01-AUG-00:10 794004.08 01-AUG-07:10 120520.01 01-AUG-07:19 204633.81 18-AUG-14:00 63208.66 18-AUG-15:50 0.00 01-AUG-00:10
September 344233.60 01-SEP-07:10 57580.60 01-SEP-00:10 439129.89 01-SEP-07:10 120520.01 01-SEP-07:19 191638.08 11-SEP-14:30 67222.11 29-SEP-12:30 0.00 01-SEP-00:10
October 344233.60 02-OCT-07:10 57580.60 01-OCT-00:10 557421.28 02-OCT-07:10 120520.01 02-OCT-07:19 196298.86 16-OCT-08:30 66885.77 17-OCT-14:00 0.00 01-OCT-00:10
November 344233.60 01-NOV-07:10 57580.60 01-NOV-00:10 675712.68 01-NOV-07:10 120520.01 01-NOV-07:19 162773.45 13-NOV-15:09 61293.27 28-NOV-13:50 0.00 01-NOV-00:10
December 344233.60 01-DEC-08:09 57580.60 01-DEC-00:10 794004.08 01-DEC-08:09 120520.01 01-DEC-08:20 165120.50 05-DEC-15:00 61537.93 19-DEC-13:20 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 344233.60   57580.60   439129.89   120520.01   158365.29   61293.27   0.00  
Maximum of Months 344233.60   57580.60   794004.08   120520.01   205774.29   67222.11   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 235002.27 13-JAN-13:00 82101.62 13-JAN-13:50 4637.11 07-JAN-09:00 0.00 0.00 0.00
February 246212.12 01-FEB-11:00 80839.38 01-FEB-13:20 5362.42 04-FEB-12:00 0.00 0.00 0.00
March 283760.64 23-MAR-13:50 82101.62 22-MAR-12:00 1890.35 11-MAR-13:00 0.00 0.00 0.00
April 331560.79 26-APR-12:00 82101.62 04-APR-13:00 6074.20 01-APR-11:00 0.00 0.00 0.00
May 224341.67 03-MAY-12:00 82101.62 03-MAY-11:00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 300002.16 29-JUN-12:00 82101.62 15-JUN-14:00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 412703.01 31-JUL-15:50 82101.62 03-JUL-12:09 0.00 01-JUL-00:10 0.00 0.00 0.00
August 448084.30 18-AUG-15:50 82101.62 02-AUG-09:09 0.00 01-AUG-00:10 0.00 0.00 0.00
September 314117.85 29-SEP-12:20 82101.62 05-SEP-12:30 0.00 01-SEP-00:10 0.00 0.00 0.00
October 371046.61 16-OCT-10:00 82101.62 02-OCT-07:19 4308.07 25-OCT-20:00 0.00 0.00 0.00
November 288727.03 28-NOV-13:00 65674.94 10-NOV-12:00 5551.32 22-NOV-21:00 0.00 0.00 0.00
December 327195.03 05-DEC-14:00 64169.08 07-DEC-13:30 6835.20 19-DEC-10:39 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 224341.67   64169.08   0.00   0.00 0.00 0.00
Maximum of Months 448084.30   82101.62   6835.20   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1320566.92 24-JAN-14:30 344233.60 439129.89 0.00 41348.64 141998.95 62216.29 0.00 209537.94 82101.62
February 1439636.75 01-FEB-13:20 344233.60 557421.28 0.00 41348.64 117909.53 61773.64 0.00 236110.67 80839.38
March 1707294.40 23-MAR-15:20 344233.60 675712.68 0.00 86589.42 184729.35 60546.55 0.00 273381.18 82101.62
April 1852857.80 26-APR-15:39 344233.60 794004.08 0.00 86589.42 185283.32 60589.08 0.00 300056.69 82101.62
May 1374060.70 18-MAY-15:20 344233.60 439129.89 0.00 86589.42 161006.87 62160.41 0.00 207464.70 73475.81
June 1589988.07 29-JUN-15:00 344233.60 557421.28 0.00 86589.42 185382.58 61394.98 0.00 272864.59 82101.62
July 1858287.16 31-JUL-15:50 344233.60 675712.68 0.00 86589.42 193746.13 63200.70 0.00 412703.01 82101.62
August 2015457.69 18-AUG-15:50 344233.60 794004.08 0.00 86589.42 197236.02 63208.66 0.00 448084.30 82101.62
September 1472508.33 29-SEP-15:00 344233.60 439129.89 0.00 86589.42 176055.97 64690.32 0.00 279707.52 82101.62
October 1610794.82 17-OCT-15:00 344233.60 557421.28 0.00 86589.42 188946.74 62738.25 0.00 288763.91 82101.62
November 1580896.56 28-NOV-14:09 344233.60 675712.68 0.00 41348.64 118232.26 60970.53 0.00 286782.73 52106.82
December 1787884.33 05-DEC-09:39 344233.60 794004.08 0.00 86589.42 126151.66 59303.73 0.00 310559.86 61337.54
                       
Annual Sum or Average                      
Minimum of Months 1320566.92   344233.60 439129.89 0.00 41348.64 117909.53 59303.73 0.00 207464.70 52106.82
Maximum of Months 2015457.69   344233.60 794004.08 0.00 86589.42 197236.02 64690.32 0.00 448084.30 82101.62



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 752660.69 09-JAN-07:10 0.00 78854.17 25-JAN-12:39 0.00
February 0.00 0.00 533092.11 10-FEB-07:10 0.00 78860.74 02-FEB-12:00 0.00
March 0.00 0.00 722165.05 30-MAR-06:10 0.00 78672.36 01-MAR-12:30 0.00
April 0.00 0.00 583856.90 01-APR-06:10 0.00 77949.89 03-APR-11:30 0.00
May 0.00 0.00 237355.43 15-MAY-06:10 0.00 76893.49 05-MAY-11:39 0.00
June 0.00 0.00 184910.15 12-JUN-20:00 0.00 75748.55 01-JUN-11:20 0.00
July 0.00 0.00 253.83 07-JUL-20:00 0.00 74953.92 11-JUL-11:20 0.00
August 0.00 0.00 5721.42 28-AUG-06:00 0.00 74991.35 31-AUG-11:50 0.00
September 0.00 0.00 148672.93 20-SEP-06:10 0.00 75679.86 28-SEP-11:20 0.00
October 0.00 0.00 323956.89 12-OCT-06:10 0.00 76761.84 30-OCT-11:39 0.00
November 0.00 0.00 411886.16 30-NOV-07:10 0.00 77694.81 27-NOV-12:39 0.00
December 0.00 0.00 612185.97 13-DEC-07:10 0.00 78515.72 29-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 253.83   0.00 74953.92   0.00
Maximum of Months 0.00 0.00 752660.69   0.00 78860.74   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.67 26.83 2.83 26.96
February 0.00 0.00 0.00 0.00 3.67 26.29 0.17 26.33
March 0.00 0.00 0.00 0.00 2.67 25.95 0.00 25.95
April 0.00 0.00 0.00 0.00 3.67 26.00 0.00 26.00
May 0.00 0.00 0.00 0.00 4.50 26.30 0.00 26.30
June 0.00 0.00 0.00 0.00 1.33 25.73 0.00 25.73
July 0.00 0.00 0.00 0.00 5.17 25.99 0.17 25.94
August 0.00 0.00 0.00 0.00 4.67 26.06 0.00 26.06
September 0.00 0.00 0.00 0.00 6.17 26.42 0.83 26.54
October 0.00 0.00 0.00 0.00 9.17 26.87 0.50 26.89
November 0.00 0.00 0.00 0.00 9.17 26.84 0.17 26.85
December 0.00 0.00 0.00 0.00 9.50 26.73 0.50 26.76
                 
Annual Sum or Average 0.00   0.00   70.33 26.51 5.17 26.57
Minimum of Months 0.00 0.00 0.00 0.00 1.33 25.73 0.00 25.73
Maximum of Months 0.00 0.00 0.00 0.00 10.67 26.87 2.83 26.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 25.61 0.00 25.61
August 0.00 0.00 0.00 0.00 0.17 25.66 0.00 25.66
September 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
October 0.00 0.00 0.00 0.00 0.67 25.74 0.00 25.74
November 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
December 0.00 0.00 0.00 0.00 1.00 25.61 0.00 25.61
                 
Annual Sum or Average 0.00   0.00   3.00 25.64 0.00 25.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.00 25.74 0.00 25.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.40 0.17 27.40
March 0.00 0.00 0.00 0.00 0.17 27.42 0.17 27.42
April 0.00 0.00 0.00 0.00 0.50 27.44 0.50 27.44
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.83 27.36 0.83 27.36
July 0.00 0.00 0.00 0.00 1.33 27.48 1.33 27.48
August 0.00 0.00 0.00 0.00 0.83 27.44 0.83 27.44
September 0.00 0.00 0.00 0.00 0.67 27.43 0.67 27.43
October 0.00 0.00 0.00 0.00 0.67 27.80 0.67 27.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.17 27.48 5.17 27.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 27.80 1.33 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.00 27.53 2.00 27.53
February 0.00 0.00 0.00 0.00 2.17 27.47 2.17 27.47
March 0.00 0.00 0.00 0.00 0.33 27.29 0.33 27.29
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.50 24.56 0.50 24.56
October 0.00 0.00 0.00 0.00 8.00 27.12 8.00 27.12
November 0.00 0.00 0.00 0.00 3.83 27.73 3.83 27.73
December 0.00 0.00 0.00 0.00 5.17 27.72 5.17 27.72
                 
Annual Sum or Average 0.00   0.00   22.00 27.39 22.00 27.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.00 27.73 8.00 27.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.31 0.33 27.31
March 0.00 0.00 0.00 0.00 1.33 27.72 1.17 27.74
April 0.00 0.00 0.00 0.00 10.17 27.70 5.33 27.85
May 0.00 0.00 0.00 0.00 3.50 27.52 2.83 27.52
June 0.00 0.00 0.00 0.00 4.00 27.74 2.67 27.78
July 0.00 0.00 0.00 0.00 19.33 27.43 7.00 27.59
August 0.00 0.00 0.00 0.00 23.17 27.05 6.33 27.25
September 0.00 0.00 0.00 0.00 2.33 27.68 2.17 27.69
October 0.00 0.00 0.00 0.00 5.00 27.71 3.83 27.76
November 0.00 0.00 0.00 0.00 1.50 27.38 1.50 27.38
December 0.00 0.00 0.00 0.00 2.17 27.56 2.17 27.56
                 
Annual Sum or Average 0.00   0.00   72.83 27.40 35.33 27.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 27.74 7.00 27.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.27 0.33 27.27
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.50 27.57 1.50 27.57
August 0.00 0.00 0.00 0.00 1.00 27.42 1.00 27.42
September 0.00 0.00 0.00 0.00 0.33 27.31 0.33 27.31
October 0.00 0.00 0.00 0.00 0.67 27.85 0.67 27.85
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.83 27.53 3.83 27.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 27.85 1.50 27.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 27.71 1.33 27.71
February 0.00 0.00 0.00 0.00 0.67 27.41 0.67 27.41
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.67 24.85 1.67 24.85
October 0.00 0.00 0.00 0.00 12.17 26.05 12.17 26.05
November 0.00 0.00 0.00 0.00 3.17 27.71 3.17 27.71
December 0.00 0.00 0.00 0.00 4.17 27.63 4.17 27.63
                 
Annual Sum or Average 0.00   0.00   23.17 26.61 23.17 26.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.17 27.71 12.17 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.38 0.67 27.38
May 0.00 0.00 0.00 0.00 0.33 27.35 0.33 27.35
June 0.00 0.00 0.00 0.00 1.00 27.55 0.67 27.56
July 0.00 0.00 0.00 0.00 3.83 27.72 3.00 27.74
August 0.00 0.00 0.00 0.00 2.83 27.68 2.33 27.70
September 0.00 0.00 0.00 0.00 0.50 27.37 0.50 27.37
October 0.00 0.00 0.00 0.00 1.33 27.88 1.33 27.88
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.50 27.66 8.83 27.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.83 27.88 3.00 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 18.84 0.17 18.96 0.00 18.96 0.00 18.96
February 0.33 19.33 0.00 19.33 0.00 19.33 0.00 19.33
March 0.50 19.06 0.00 19.06 0.00 19.06 0.00 19.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.31 0.00 19.31 0.00 19.31 0.00 19.31
December 0.33 19.27 0.00 19.27 0.00 19.27 0.00 19.27
                 
Annual Sum or Average 3.50 19.00 0.17 19.07 0.00 19.07 0.00 19.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 19.33 0.17 19.33 0.00 19.33 0.00 19.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 18.89 0.00 18.89 0.00 18.89 0.00 18.89
February 0.33 19.41 0.00 19.41 0.00 19.41 0.00 19.41
March 0.50 19.06 0.00 19.06 0.00 19.06 0.00 19.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 27.54 1.00 27.54
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.67 27.70 0.67 27.70
November 0.17 19.32 0.00 19.32 0.00 19.32 0.00 19.32
December 0.33 19.24 0.00 19.24 0.00 19.24 0.00 19.24
                 
Annual Sum or Average 2.83 19.05 0.00 19.05 1.67 22.22 1.67 23.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.41 0.00 19.41 1.00 27.70 1.00 27.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 18.99 0.00 18.99 0.17 20.18 0.17 21.08
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.33 19.07 0.00 19.07 0.00 19.07 0.00 19.07
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 2.50 25.01 2.50 25.01
October 0.00 0.00 0.00 0.00 6.33 26.89 6.17 26.88
November 0.00 0.00 0.00 0.00 1.00 27.78 1.00 27.78
December 0.17 19.27 0.00 19.27 0.33 24.63 0.33 25.70
                 
Annual Sum or Average 1.50 19.04 0.00 19.04 10.33 25.59 10.17 26.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.27 0.00 19.27 6.33 27.78 6.17 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 19.03 0.00 19.03 0.00 19.03 0.00 19.03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.33 19.24 0.00 19.24 0.00 19.24 0.00 19.24
April 0.00 0.00 0.00 0.00 0.50 27.42 0.33 27.45
May 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
June 0.00 0.00 0.00 0.00 1.00 27.65 0.83 27.67
July 0.00 0.00 0.00 0.00 4.33 27.80 3.33 27.81
August 0.00 0.00 0.00 0.00 2.83 27.79 2.33 27.81
September 0.00 0.00 0.00 0.00 0.17 27.48 0.17 27.48
October 0.00 0.00 0.00 0.00 1.33 28.04 1.17 28.06
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.36 0.00 19.36 0.00 19.36 0.00 19.36
                 
Annual Sum or Average 1.67 19.11 0.00 19.11 10.33 26.58 8.33 27.09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.17 19.36 0.00 19.36 4.33 28.04 3.33 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 6.00 27.86 6.00 27.86
                 
Annual Sum or Average 0.00   0.00   6.00 27.86 6.00 27.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 27.86 6.00 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 1.50 27.65 1.50 27.65
                 
Annual Sum or Average 0.00   0.00   1.50 27.65 1.50 27.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 27.65 1.50 27.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 15.83 27.88 15.83 27.88
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 58.83 27.97 58.83 27.97
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 54.17 28.19 54.17 28.19
                 
Annual Sum or Average 0.00   0.00   128.83 28.05 128.83 28.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 58.83 28.19 58.83 28.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.17 24.00 257.83 24.97 0.00 24.97
February 26.83 24.00 235.33 24.85 0.00 24.85
March 0.00 0.00 313.33 24.67 0.00 24.67
April 2.83 24.00 396.67 24.60 0.00 24.60
May 0.83 24.00 382.67 24.62 0.00 24.62
June 2.17 24.00 478.50 24.44 2.17 24.44
July 103.33 25.13 497.00 24.67 103.33 24.74
August 115.17 25.04 514.00 24.56 115.17 24.63
September 32.50 25.49 453.50 24.62 32.50 24.67
October 33.17 24.64 338.00 24.85 29.83 24.84
November 23.50 24.18 284.17 24.93 1.33 24.94
December 35.17 24.00 206.00 25.17 0.00 25.17
             
Annual Sum or Average 401.67 24.77 4357.00 24.70 284.33 24.72
Minimum of Months 0.00 0.00 206.00 24.44 0.00 24.44
Maximum of Months 115.17 25.49 514.00 25.17 115.17 25.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 43.33 24.78 255.33 24.77 12.17 24.85
February 20.33 24.00 258.83 24.56 0.00 24.56
March 0.00 0.00 336.33 24.49 0.00 24.49
April 2.50 24.00 437.67 24.36 0.00 24.36
May 0.17 23.68 387.00 24.42 0.00 24.42
June 0.00 0.00 485.83 24.32 0.00 24.32
July 0.00 0.00 497.00 24.31 0.00 24.31
August 0.00 0.00 514.00 24.25 0.00 24.25
September 0.00 0.00 453.17 24.36 0.00 24.36
October 1.83 24.00 342.17 24.55 0.00 24.55
November 16.17 24.43 283.50 24.68 2.17 24.70
December 24.33 24.00 222.67 24.79 0.00 24.79
             
Annual Sum or Average 108.67 24.37 4473.50 24.45 14.33 24.46
Minimum of Months 0.00 0.00 222.67 24.25 0.00 24.25
Maximum of Months 43.33 24.78 514.00 24.79 12.17 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 148.33 23.74 144.83 24.08 13.00 24.06
February 87.17 23.71 128.33 24.11 0.00 24.11
March 62.83 23.68 205.83 24.19 0.00 24.19
April 27.17 23.57 302.17 24.26 0.00 24.26
May 13.67 23.52 314.00 24.34 0.00 24.34
June 0.17 23.55 445.50 24.26 0.00 24.26
July 0.00 0.00 493.00 24.25 0.00 24.25
August 0.00 0.00 514.00 24.21 0.00 24.21
September 0.00 0.00 430.50 24.29 0.00 24.29
October 31.33 23.85 284.83 24.38 0.00 24.38
November 105.83 24.04 195.67 24.34 7.83 24.38
December 170.00 23.81 94.50 24.08 0.00 24.08
             
Annual Sum or Average 646.50 23.79 3553.17 24.24 20.83 24.24
Minimum of Months 0.00 0.00 94.50 24.08 0.00 24.06
Maximum of Months 170.00 24.04 514.00 24.38 13.00 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 354.50 22.82 50.00 22.83 12.83 22.73
February 299.00 22.91 44.17 23.05 0.00 23.05
March 288.83 23.05 98.00 23.30 0.00 23.30
April 130.50 23.11 210.00 23.77 0.00 23.77
May 125.83 23.22 230.17 23.87 0.00 23.87
June 21.17 23.37 389.83 24.17 0.00 24.17
July 0.00 0.00 480.67 24.24 0.00 24.24
August 0.00 0.00 499.50 24.18 0.00 24.18
September 26.17 23.45 373.33 24.15 0.33 24.15
October 136.33 23.43 222.83 23.93 0.00 23.93
November 278.67 23.20 82.17 23.42 6.50 23.44
December 390.33 23.01 20.17 23.05 1.33 23.04
             
Annual Sum or Average 2051.33 23.05 2700.83 23.69 21.00 23.68
Minimum of Months 0.00 0.00 20.17 22.83 0.00 22.73
Maximum of Months 390.33 23.45 499.50 24.24 12.83 24.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 315.00 23.18 35.50 23.29 0.00 23.29
February 273.00 23.31 48.67 23.41 0.00 23.41
March 209.83 23.21 122.83 23.54 0.00 23.54
April 80.33 23.44 231.33 23.98 0.00 23.98
May 89.83 23.43 240.17 24.00 0.00 24.00
June 2.00 23.32 430.67 24.23 0.00 24.23
July 0.00 0.00 490.83 24.25 0.00 24.25
August 0.00 0.00 506.17 24.16 0.00 24.16
September 21.67 23.39 362.67 24.16 0.00 24.16
October 92.50 23.59 251.83 24.12 0.00 24.12
November 235.83 23.51 96.50 23.74 0.00 23.74
December 323.33 23.51 28.00 23.57 0.00 23.57
             
Annual Sum or Average 1643.33 23.37 2845.17 23.90 0.00 23.90
Minimum of Months 0.00 0.00 28.00 23.29 0.00 23.29
Maximum of Months 323.33 23.59 506.17 24.25 0.00 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 285.83 22.87 74.67 23.23 0.00 23.23
February 271.17 22.80 73.67 23.12 0.00 23.12
March 256.33 22.73 152.50 23.29 0.17 23.29
April 144.50 22.92 252.83 23.76 1.67 23.78
May 138.83 23.01 255.50 23.91 1.00 23.92
June 69.83 23.32 352.50 24.11 6.67 24.15
July 33.33 24.43 430.83 24.26 13.17 24.33
August 37.00 23.96 431.50 24.13 10.17 24.18
September 80.83 23.15 335.17 24.04 5.17 24.07
October 124.17 23.12 244.33 23.94 1.33 23.95
November 244.67 23.02 112.67 23.43 0.00 23.43
December 326.33 22.99 30.00 23.14 0.00 23.14
             
Annual Sum or Average 2012.83 22.98 2746.17 23.73 39.33 23.75
Minimum of Months 33.33 22.73 30.00 23.12 0.00 23.12
Maximum of Months 326.33 24.43 431.50 24.26 13.17 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 157.33 23.21 214.67 23.96 4.67 24.00
February 184.17 23.03 167.00 23.71 4.00 23.74
March 198.17 22.97 196.33 23.61 3.17 23.63
April 100.83 23.10 285.67 23.96 0.00 23.96
May 166.50 23.07 204.83 23.70 0.00 23.70
June 52.83 23.15 353.50 24.04 0.00 24.04
July 2.83 23.25 450.00 24.17 0.00 24.17
August 1.67 23.35 488.00 24.16 0.00 24.16
September 32.00 24.01 407.00 24.32 7.83 24.36
October 76.00 24.57 361.50 24.55 27.33 24.69
November 102.17 23.61 273.33 24.27 7.67 24.33
December 125.17 23.51 237.83 24.23 7.83 24.29
             
Annual Sum or Average 1199.67 23.29 3639.67 24.07 62.50 24.11
Minimum of Months 1.67 22.97 167.00 23.61 0.00 23.63
Maximum of Months 198.17 24.57 488.00 24.55 27.33 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 221.17 22.97 153.33 23.60 0.00 23.60
February 104.67 23.11 218.17 24.03 0.67 24.04
March 50.67 23.53 357.17 24.33 5.33 24.37
April 28.50 26.44 469.67 24.65 24.67 24.76
May 63.50 23.65 364.83 24.36 11.17 24.42
June 20.83 26.55 485.83 24.53 19.33 24.61
July 50.33 26.88 497.00 24.76 50.33 24.94
August 45.33 26.91 514.00 24.65 45.33 24.81
September 19.50 25.70 444.33 24.44 14.17 24.51
October 41.33 24.96 383.00 24.63 19.83 24.73
November 38.67 24.10 320.50 24.57 6.67 24.61
December 38.17 23.96 298.33 24.67 5.00 24.70
             
Annual Sum or Average 722.67 24.15 4506.17 24.46 202.50 24.55
Minimum of Months 19.50 22.97 153.33 23.60 0.00 23.60
Maximum of Months 221.17 26.91 514.00 24.76 50.33 24.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 439.00 22.29 29.83 22.27 17.33 22.21
February 391.67 22.38 16.33 22.41 5.33 22.39
March 420.50 22.48 37.17 22.59 1.17 22.59
April 285.00 22.89 95.67 23.17 0.00 23.17
May 234.17 23.10 132.83 23.44 0.00 23.44
June 64.00 23.29 309.00 23.95 0.00 23.95
July 17.83 23.58 436.00 24.12 3.33 24.13
August 30.50 23.20 411.33 24.01 0.33 24.01
September 119.67 23.16 255.50 23.77 0.00 23.77
October 230.50 23.12 151.00 23.54 0.00 23.54
November 386.67 22.66 19.33 22.69 5.17 22.67
December 470.67 22.43 16.83 22.40 11.83 22.36
             
Annual Sum or Average 3090.17 22.64 1910.83 23.17 44.50 23.15
Minimum of Months 17.83 22.29 16.33 22.27 0.00 22.21
Maximum of Months 470.67 23.58 436.00 24.12 17.33 24.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 379.33 22.32 23.17 22.38 5.67 22.35
February 324.17 22.17 23.50 22.30 1.83 22.29
March 322.50 22.17 57.67 22.49 1.67 22.48
April 192.33 22.60 160.17 23.44 1.33 23.45
May 203.00 22.73 159.83 23.50 0.33 23.50
June 126.17 23.03 227.67 23.86 5.83 23.91
July 67.83 24.18 333.83 24.37 24.00 24.49
August 71.33 23.79 327.33 24.18 18.00 24.29
September 140.67 22.84 217.50 23.71 3.83 23.74
October 186.83 22.78 139.67 23.50 0.83 23.51
November 325.00 22.51 24.17 22.62 1.17 22.62
December 398.83 22.38 3.67 22.37 3.67 22.35
             
Annual Sum or Average 2738.00 22.54 1698.17 23.23 68.17 23.26
Minimum of Months 67.83 22.17 3.67 22.30 0.33 22.29
Maximum of Months 398.83 24.18 333.83 24.37 24.00 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 204.00 22.91 193.17 23.66 7.33 23.70
February 236.67 22.58 127.67 23.25 3.17 23.28
March 290.83 22.52 138.00 23.08 2.00 23.09
April 187.33 22.78 203.33 23.56 0.00 23.56
May 251.83 22.86 151.50 23.34 0.00 23.34
June 138.33 23.05 245.00 23.71 0.00 23.71
July 50.83 23.22 377.00 24.05 3.67 24.06
August 38.67 23.35 424.67 24.08 3.00 24.10
September 67.67 23.52 370.50 24.19 8.50 24.24
October 117.17 24.00 318.33 24.41 28.17 24.56
November 170.50 23.19 216.83 23.95 7.33 24.01
December 203.50 23.08 199.00 23.86 6.17 23.91
             
Annual Sum or Average 1957.33 22.95 2965.00 23.77 69.33 23.82
Minimum of Months 38.67 22.52 127.67 23.08 0.00 23.09
Maximum of Months 290.83 24.00 424.67 24.41 28.17 24.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 411.00 22.21 43.17 22.35 4.50 22.33
February 360.83 22.25 50.50 22.49 0.00 22.49
March 383.17 22.32 85.83 22.65 0.33 22.65
April 186.33 22.74 207.83 23.58 5.00 23.62
May 201.50 22.83 215.83 23.62 4.33 23.65
June 80.83 23.17 346.17 24.05 7.17 24.10
July 36.67 25.30 435.33 24.42 23.33 24.53
August 33.50 24.59 445.67 24.25 15.00 24.32
September 97.50 23.11 324.33 24.00 7.67 24.05
October 199.00 22.97 218.00 23.68 6.50 23.73
November 342.00 22.52 79.17 22.84 0.00 22.84
December 414.83 22.37 24.17 22.46 0.00 22.46
             
Annual Sum or Average 2747.17 22.56 2476.00 23.37 73.83 23.41
Minimum of Months 33.50 22.21 24.17 22.35 0.00 22.33
Maximum of Months 414.83 25.30 445.67 24.42 23.33 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 482.17 21.43 113.33 21.17 112.33 20.98
February 435.00 21.56 71.83 21.37 69.17 21.21
March 470.17 21.71 67.33 21.65 47.83 21.53
April 340.83 22.28 88.50 22.56 9.17 22.51
May 308.33 22.50 107.00 22.86 2.67 22.84
June 163.00 22.98 245.17 23.63 0.00 23.63
July 66.67 23.06 363.33 23.95 3.00 23.96
August 115.83 22.98 335.50 23.76 2.00 23.77
September 222.17 22.78 183.67 23.34 0.00 23.34
October 299.17 22.52 125.00 22.95 6.83 22.90
November 470.50 21.92 56.00 21.79 50.67 21.65
December 491.67 21.47 119.00 21.23 119.00 21.06
             
Annual Sum or Average 3865.50 22.01 1875.67 22.39 422.67 22.24
Minimum of Months 66.67 21.43 56.00 21.17 0.00 20.98
Maximum of Months 491.67 23.06 363.33 23.95 119.00 23.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.17 21.74 73.17 21.59 62.83 21.44
February 399.67 21.72 50.33 21.64 38.50 21.51
March 414.33 21.78 74.67 21.95 23.83 21.87
April 224.83 22.19 194.00 23.11 3.00 23.09
May 255.67 22.38 177.67 23.16 0.83 23.16
June 162.33 22.79 273.50 23.69 4.33 23.72
July 80.67 23.86 399.00 24.25 24.00 24.36
August 88.83 23.38 392.67 24.05 16.17 24.13
September 181.50 22.59 248.67 23.51 2.33 23.52
October 240.50 22.46 154.67 23.15 2.83 23.14
November 448.83 22.14 27.00 22.11 18.00 22.05
December 480.83 21.78 41.83 21.66 40.83 21.56
             
Annual Sum or Average 3444.17 22.11 2107.17 22.78 237.50 22.73
Minimum of Months 80.67 21.72 27.00 21.59 0.83 21.44
Maximum of Months 480.83 23.86 399.00 24.25 62.83 24.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 277.17 22.14 167.83 22.66 33.50 22.48
February 296.00 21.87 121.83 22.41 21.33 22.29
March 360.50 21.88 131.00 22.29 27.67 22.20
April 253.83 22.32 180.17 23.07 7.17 23.05
May 315.33 22.33 128.67 22.81 3.00 22.79
June 215.83 22.73 201.50 23.36 0.00 23.36
July 106.33 22.88 329.33 23.82 3.67 23.83
August 92.50 22.92 369.50 23.88 4.83 23.90
September 125.17 22.98 307.00 23.91 8.67 23.97
October 174.50 23.16 272.67 23.99 20.50 24.12
November 249.17 22.49 173.17 23.20 13.50 23.16
December 271.83 22.31 156.17 22.90 24.50 22.77
             
Annual Sum or Average 2738.17 22.37 2538.83 23.19 168.33 23.15
Minimum of Months 92.50 21.87 121.83 22.29 0.00 22.20
Maximum of Months 360.50 23.16 369.50 23.99 33.50 24.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 448.67 21.60 93.50 21.56 65.83 21.41
February 390.67 21.64 64.67 21.74 30.17 21.64
March 419.83 21.71 88.33 21.94 25.33 21.87
April 265.67 22.38 168.17 23.09 9.83 23.11
May 273.00 22.42 168.83 23.14 6.83 23.18
June 147.00 22.82 286.00 23.74 8.00 23.79
July 77.67 23.93 399.67 24.25 25.00 24.37
August 86.83 23.42 397.83 24.04 17.67 24.13
September 165.50 22.72 257.50 23.63 6.83 23.68
October 262.33 22.53 171.00 23.24 7.17 23.30
November 396.33 21.96 77.67 22.11 25.33 22.02
December 451.83 21.75 68.17 21.66 57.33 21.53
             
Annual Sum or Average 3385.33 22.09 2241.33 22.80 285.33 22.76
Minimum of Months 77.67 21.60 64.67 21.56 6.83 21.41
Maximum of Months 451.83 23.93 399.67 24.25 65.83 24.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 12.50 27.00 454.00 27.00 12.50 27.00
March 51.33 27.00 514.00 27.00 51.33 27.00
April 244.50 27.00 485.00 27.00 244.50 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 51.00 27.00 496.00 27.00 51.00 27.00
July 219.83 27.00 497.00 27.00 219.83 27.00
August 343.83 27.00 514.00 27.00 343.83 27.00
September 11.17 27.00 485.00 27.00 11.17 27.00
October 32.50 27.00 502.00 27.00 32.50 27.00
November 63.00 27.00 489.00 27.00 63.00 27.00
December 98.83 27.07 497.00 27.03 98.83 27.03
             
Annual Sum or Average 1128.50 27.01 5943.00 27.00 1128.50 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 343.83 27.07 514.00 27.03 343.83 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 4.00 27.00 485.00 27.00 4.00 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 0.33 27.00 497.00 27.00 0.33 27.00
August 28.50 27.00 514.00 27.00 28.50 27.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 1.83 27.00 502.00 27.00 1.83 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.67 27.00 497.00 27.01 0.67 27.01
             
Annual Sum or Average 35.33 27.00 5943.00 27.00 35.33 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 28.50 27.00 514.00 27.01 28.50 27.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.00 25.53 476.67 26.96 0.00 26.96
February 0.00 0.00 446.83 27.00 0.00 27.00
March 1.17 27.00 514.00 27.00 1.17 27.00
April 24.33 27.00 485.00 27.00 24.33 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.50 27.00 496.00 27.00 0.50 27.00
July 48.67 27.00 497.00 27.00 48.67 27.00
August 105.00 27.00 514.00 27.00 105.00 27.00
September 2.50 27.00 485.00 27.00 2.50 27.00
October 4.50 27.00 502.00 27.00 4.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.50 27.00 497.00 27.00 0.50 27.00
             
Annual Sum or Average 198.17 26.92 5910.50 27.00 187.17 27.00
Minimum of Months 0.00 0.00 446.83 26.96 0.00 26.96
Maximum of Months 105.00 27.00 514.00 27.00 105.00 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.04 485.00 27.04 485.00 27.04
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.18 514.00 27.18 514.00 27.18
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.16 497.00 27.16 497.00 27.16
             
Annual Sum or Average 5943.00 27.03 5943.00 27.03 5943.00 27.03
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 27.18 514.00 27.18 514.00 27.18



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00027 32.25054 0.88548 21.63694
February 454.00000 27.00034 33.08090 0.92932 23.31539
March 514.00000 27.00028 34.43592 0.97882 25.28217
April 485.00000 27.00012 35.37810 1.03543 27.67423
May 508.00000 27.00063 36.53776 0.26958 6.58252
June 496.00000 27.00089 37.05004 0.34091 7.47072
July 497.00000 27.00070 37.47366 0.39808 8.35050
August 514.00000 27.00024 37.43911 0.44061 9.09903
September 485.00000 27.00109 37.91670 0.29714 6.90496
October 502.00000 27.00058 34.30663 0.96769 24.83127
November 489.00000 27.00021 32.06334 0.97049 24.97215
December 497.00000 27.01868 29.65045 0.98035 25.37313
           
Annual Sum or Average 5943.00000 27.00201 34.81404 0.70566 17.56293
Minimum of Months 454.00000 27.00012 29.65045 0.26958 6.58252
Maximum of Months 514.00000 27.01868 37.91670 1.03543 27.67423



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00025 32.31082 0.81004 18.96073
February 454.00000 27.00032 33.10447 0.83657 19.86967
March 514.00000 27.00027 34.42406 0.86830 20.99419
April 485.00000 27.00013 35.35861 0.92465 23.13820
May 508.00000 27.00060 36.62455 0.19439 5.89441
June 496.00000 27.00085 37.08809 0.24896 6.36986
July 497.00000 27.00071 37.49544 0.29164 6.83658
August 514.00000 27.00024 37.44757 0.31273 7.11049
September 485.00000 27.00087 38.07085 0.22910 6.18464
October 502.00000 27.00054 34.33226 0.89404 21.95051
November 489.00000 27.00021 32.04637 0.86030 20.73511
December 497.00000 27.00672 29.63225 0.83938 19.96450
           
Annual Sum or Average 5943.00000 27.00098 34.84329 0.60692 14.78026
Minimum of Months 454.00000 27.00013 29.63225 0.19439 5.89441
Maximum of Months 514.00000 27.00672 38.07085 0.92465 23.13820



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.94915 32.74078 0.74082 16.91550
February 454.00000 27.00032 33.16239 0.78036 18.04370
March 514.00000 27.00028 34.45854 0.81951 19.34725
April 485.00000 27.00015 35.38236 0.89923 22.24928
May 508.00000 27.00068 36.68679 0.16209 5.81417
June 496.00000 27.00087 37.10636 0.23790 6.37025
July 497.00000 27.00074 37.50763 0.29511 6.96628
August 514.00000 27.00025 37.46433 0.31094 7.18198
September 485.00000 27.00094 38.13082 0.20932 6.10841
October 502.00000 27.00054 34.35637 0.86936 21.09537
November 489.00000 27.00022 32.07641 0.80758 18.95243
December 497.00000 27.00126 29.64889 0.77409 17.80929
           
Annual Sum or Average 5943.00000 26.99623 34.90906 0.57343 13.85786
Minimum of Months 454.00000 26.94915 29.64889 0.16209 5.81417
Maximum of Months 514.00000 27.00126 38.13082 0.89923 22.24928



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00083 33.79348 1.10622 30.81971
February 454.00000 27.00103 34.46323 1.25185 37.82889
March 514.00000 27.00034 34.73292 1.39788 45.40410
April 485.00000 27.03800 35.74115 1.54943 53.59023
May 508.00000 27.00101 36.08289 0.52388 10.79869
June 496.00000 27.00112 36.65894 0.74775 16.79501
July 497.00000 27.00076 37.13069 0.96208 24.57005
August 514.00000 27.17521 37.10145 1.20386 35.54898
September 485.00000 27.00186 36.91956 0.56310 11.68859
October 502.00000 27.00119 34.78271 1.28320 39.42000
November 489.00000 27.00159 33.97463 1.41392 46.26002
December 497.00000 27.15529 32.80845 1.56074 54.19260
           
Annual Sum or Average 5943.00000 27.03205 35.35607 1.12939 33.86960
Minimum of Months 454.00000 27.00034 32.80845 0.52388 10.79869
Maximum of Months 514.00000 27.17521 37.13069 1.56074 54.19260



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.55146 34.90280 0.47326 10.35673
February 454.00000 24.49733 37.64769 0.47453 10.29795
March 514.00000 24.40908 40.45568 0.47895 10.21651
April 485.00000 24.49968 44.20022 0.52612 11.24201
May 508.00000 24.46607 43.65393 -0.3454 8.32015
June 496.00000 24.42519 50.44370 -0.3034 7.64445
July 497.00000 24.57421 56.97816 -0.2057 6.99479
August 514.00000 24.45008 58.36347 -0.2251 6.95918
September 485.00000 24.51819 52.25025 -0.2557 7.45898
October 502.00000 24.59116 41.82093 0.53894 11.89854
November 489.00000 24.59152 35.82747 0.49655 10.97773
December 497.00000 24.58286 31.02831 0.45869 10.26231
           
Annual Sum or Average 5943.00000 24.51264 44.02389 0.17295 9.37386
Minimum of Months 454.00000 24.40908 31.02831 -0.3454 6.95918
Maximum of Months 514.00000 24.59152 58.36347 0.53894 11.89854



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.40297 37.56893 0.46073 10.19600
February 454.00000 24.34800 38.81657 0.46049 9.79225
March 514.00000 24.32030 41.62830 0.48316 10.19966
April 485.00000 24.32808 45.10581 0.52092 10.92612
May 508.00000 24.31574 45.00248 -0.3635 8.22612
June 496.00000 24.31235 50.96083 -0.3044 7.41913
July 497.00000 24.30652 54.48025 -0.2696 6.83826
August 514.00000 24.25177 55.18145 -0.2697 6.79534
September 485.00000 24.33891 52.07737 -0.2947 7.37313
October 502.00000 24.38080 42.17576 0.51068 10.93823
November 489.00000 24.42642 36.79393 0.47999 10.38664
December 497.00000 24.41223 31.57580 0.44190 9.60033
           
Annual Sum or Average 5943.00000 24.34495 44.32922 0.15158 9.04820
Minimum of Months 454.00000 24.25177 31.57580 -0.3635 6.79534
Maximum of Months 514.00000 24.42642 55.18145 0.52092 10.93823



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.09884 38.96395 0.36379 8.07467
February 454.00000 24.09001 40.23376 0.37334 8.11855
March 514.00000 24.11519 42.81920 0.40032 8.53568
April 485.00000 24.17630 46.21280 0.44945 9.44098
May 508.00000 24.21379 45.69177 -0.4276 9.13953
June 496.00000 24.22147 51.64467 -0.3676 8.10763
July 497.00000 24.24912 55.39212 -0.3272 7.50930
August 514.00000 24.21149 56.25167 -0.3268 7.46183
September 485.00000 24.25153 52.68341 -0.3516 7.94127
October 502.00000 24.24660 43.03438 0.45464 9.67212
November 489.00000 24.22357 38.24460 0.39988 8.80890
December 497.00000 24.10064 33.20296 0.33072 7.57635
           
Annual Sum or Average 5943.00000 24.18363 45.41089 0.07797 8.36568
Minimum of Months 454.00000 24.09001 33.20296 -0.4276 7.46183
Maximum of Months 514.00000 24.25153 56.25167 0.45464 9.67212



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.16462 41.64864 0.11713 6.75525
February 454.00000 23.28416 43.07092 0.16302 6.61536
March 514.00000 23.47727 44.90107 0.22933 7.00599
April 485.00000 23.83247 47.46831 0.36300 8.36037
May 508.00000 23.91519 46.88537 -0.5355 11.86621
June 496.00000 24.11600 52.15877 -0.4022 8.71174
July 497.00000 24.22354 55.56076 -0.3263 7.49209
August 514.00000 24.16512 56.53755 -0.3364 7.57738
September 485.00000 24.10035 53.60091 -0.4078 8.86237
October 502.00000 23.97145 44.39939 0.38171 8.60419
November 489.00000 23.56202 40.66488 0.22331 6.98333
December 497.00000 23.22001 36.43406 0.10172 6.23844
           
Annual Sum or Average 5943.00000 23.75579 46.98021 -0.0381 7.93382
Minimum of Months 454.00000 23.16462 36.43406 -0.5355 6.23844
Maximum of Months 514.00000 24.22354 56.53755 0.38171 11.86621



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.53237 36.86112 0.20428 6.57390
February 454.00000 23.58225 39.56321 0.24328 6.69741
March 514.00000 23.69905 42.35183 0.29749 7.37668
April 485.00000 23.97351 45.39568 0.40618 8.68961
May 508.00000 23.99228 44.92168 -0.4961 10.62690
June 496.00000 24.18069 50.53307 -0.3625 8.04239
July 497.00000 24.24211 54.15420 -0.2983 7.11828
August 514.00000 24.15536 55.09421 -0.3217 7.35390
September 485.00000 24.08495 52.15554 -0.4080 8.85269
October 502.00000 24.08524 42.27176 0.41512 9.07634
November 489.00000 23.81876 37.33361 0.29389 7.30782
December 497.00000 23.70412 31.88269 0.22481 6.44423
           
Annual Sum or Average 5943.00000 23.92298 44.41984 0.01403 7.85431
Minimum of Months 454.00000 23.53237 31.88269 -0.4961 6.44423
Maximum of Months 514.00000 24.24211 55.09421 0.41512 10.62690



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.44616 36.48101 0.22036 6.98314
February 454.00000 23.32250 39.81931 0.21769 6.91606
March 514.00000 23.41458 42.65956 0.26854 7.60696
April 485.00000 23.75876 45.70773 0.40441 9.25394
May 508.00000 23.88224 44.94576 -0.4738 11.32786
June 496.00000 23.98817 50.91763 -0.3742 9.17587
July 497.00000 24.11303 54.29270 -0.2775 7.75519
August 514.00000 23.99282 55.30972 -0.3073 8.01726
September 485.00000 23.92308 52.34152 -0.3994 9.59041
October 502.00000 23.89673 42.52111 0.40838 9.24720
November 489.00000 23.57322 37.57396 0.26903 7.30071
December 497.00000 23.36878 32.18463 0.18137 6.41008
           
Annual Sum or Average 5943.00000 23.72602 44.60502 0.00915 8.30790
Minimum of Months 454.00000 23.32250 32.18463 -0.4738 6.41008
Maximum of Months 514.00000 24.11303 55.30972 0.40838 11.32786



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.95036 35.22663 0.37943 9.25618
February 454.00000 23.74583 38.76307 0.33788 8.67331
March 514.00000 23.67408 41.92561 0.33367 8.53023
April 485.00000 23.94598 45.19276 0.43599 9.65966
May 508.00000 23.75908 45.43074 -0.5562 12.58983
June 496.00000 23.97643 51.13291 -0.4260 9.31316
July 497.00000 24.11581 54.48169 -0.3273 7.66871
August 514.00000 24.13194 54.94971 -0.2853 7.19800
September 485.00000 24.20828 51.40737 -0.2917 7.92513
October 502.00000 24.32608 41.31176 0.53799 12.19066
November 489.00000 24.16072 36.05127 0.44962 10.27247
December 497.00000 24.13383 30.49405 0.41156 9.71200
           
Annual Sum or Average 5943.00000 24.01129 43.91190 0.08021 9.42173
Minimum of Months 454.00000 23.67408 30.49405 -0.5562 7.19800
Maximum of Months 514.00000 24.32608 54.94971 0.53799 12.58983



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.68949 35.65122 0.30764 7.93441
February 454.00000 23.98037 37.91054 0.41522 9.35958
March 514.00000 24.19226 40.36299 0.50785 11.14255
April 485.00000 24.51566 43.44122 0.66343 15.09775
May 508.00000 24.17837 43.95267 -0.3188 8.72369
June 496.00000 24.42275 49.39937 -0.1394 6.67801
July 497.00000 24.54266 52.72218 -0.0243 6.50269
August 514.00000 24.44585 53.54560 -0.0209 6.29619
September 485.00000 24.30760 50.96871 -0.2076 7.19349
October 502.00000 24.39950 40.95372 0.57747 12.94568
November 489.00000 24.36107 35.39813 0.51445 11.38102
December 497.00000 24.40974 29.76537 0.49225 10.83474
           
Annual Sum or Average 5943.00000 24.28828 42.88422 0.22838 9.49550
Minimum of Months 454.00000 23.68949 29.76537 -0.3188 6.29619
Maximum of Months 514.00000 24.54266 53.54560 0.66343 15.09775



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.49835 38.84952 -0.0528 6.66057
February 454.00000 22.59890 42.00797 -0.0017 6.23485
March 514.00000 22.74533 44.98333 0.05532 6.35456
April 485.00000 23.33935 47.47357 0.23264 6.94921
May 508.00000 23.58223 46.24227 -0.6550 14.99660
June 496.00000 23.92779 51.62821 -0.4743 10.09109
July 497.00000 24.07514 55.55224 -0.3857 8.38567
August 514.00000 23.94702 57.07122 -0.4250 9.08058
September 485.00000 23.77400 53.52170 -0.5332 11.53485
October 502.00000 23.63731 43.73449 0.29110 7.65771
November 489.00000 22.93734 39.61255 0.06671 6.35749
December 497.00000 22.50838 34.12634 -0.0768 6.31928
           
Annual Sum or Average 5943.00000 23.30240 46.27410 -0.1653 8.40610
Minimum of Months 454.00000 22.49835 34.12634 -0.6550 6.23485
Maximum of Months 514.00000 24.07514 57.07122 0.29110 14.99660



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.50907 38.11208 -0.0140 6.35657
February 385.00000 22.47247 41.57451 0.00502 6.30429
March 433.00000 22.65860 43.92146 0.07265 6.88797
April 410.00000 23.47098 46.39209 0.31224 8.50639
May 430.00000 23.53742 45.75829 -0.6104 15.21773
June 418.00000 23.77640 51.58217 -0.4662 11.46166
July 422.00000 24.13600 54.84049 -0.2946 8.72818
August 433.00000 23.97737 56.35718 -0.3348 9.03669
September 410.00000 23.65687 53.32424 -0.5100 12.28675
October 427.00000 23.56369 43.78976 0.31508 8.25018
November 417.00000 22.83402 39.14611 0.08085 6.28638
December 422.00000 22.46888 33.42552 -0.0485 6.03303
           
Annual Sum or Average 5034.00000 23.25972 45.70763 -0.1256 8.79421
Minimum of Months 385.00000 22.46888 33.42552 -0.6104 6.03303
Maximum of Months 433.00000 24.13600 56.35718 0.31508 15.21773



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.70648 35.44798 0.31805 8.98544
February 454.00000 23.36955 39.58236 0.24362 8.24371
March 514.00000 23.21094 43.04595 0.21366 7.90203
April 485.00000 23.62108 46.21668 0.34050 8.61457
May 508.00000 23.45078 46.33741 -0.6724 16.06692
June 496.00000 23.71234 52.18901 -0.5317 11.69417
July 497.00000 23.95539 55.76688 -0.4054 9.07810
August 514.00000 23.99563 56.44964 -0.3560 8.40011
September 485.00000 24.08937 51.96979 -0.3426 8.87998
October 502.00000 24.18529 41.79566 0.49591 11.63512
November 489.00000 23.91118 36.57582 0.37984 9.58975
December 497.00000 23.84097 30.80016 0.32770 9.06213
           
Annual Sum or Average 5943.00000 23.75515 44.73202 -0.0022 9.86466
Minimum of Months 454.00000 23.21094 30.80016 -0.6724 7.90203
Maximum of Months 514.00000 24.18529 56.44964 0.49591 16.06692



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.53438 37.86143 0.00322 6.61246
February 454.00000 22.61386 41.09324 0.05357 6.55543
March 514.00000 22.74569 44.04108 0.11112 6.92296
April 485.00000 23.59306 46.11228 0.36154 9.25437
May 508.00000 23.62397 45.56793 -0.5551 13.98406
June 496.00000 23.93902 51.15827 -0.3761 9.49312
July 497.00000 24.20984 54.62056 -0.2378 7.65836
August 514.00000 24.07640 55.97745 -0.2720 7.82849
September 485.00000 23.89192 52.57934 -0.3990 9.91554
October 502.00000 23.65696 43.04911 0.35295 9.03303
November 489.00000 22.98256 38.51561 0.13269 6.90320
December 497.00000 22.63667 32.97178 0.00533 6.33126
           
Annual Sum or Average 5943.00000 23.38002 45.33719 -0.0701 8.38816
Minimum of Months 454.00000 22.53438 32.97178 -0.5551 6.33126
Maximum of Months 514.00000 24.20984 55.97745 0.36154 13.98406



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.52916 40.77178 -0.3011 9.57228
February 454.00000 21.65595 43.97287 -0.2394 8.21081
March 514.00000 21.89385 46.86852 -0.1569 7.54609
April 485.00000 22.77369 48.96303 0.10003 6.93014
May 508.00000 23.07063 47.62141 -0.8233 21.65906
June 496.00000 23.65291 52.48601 -0.5587 12.69867
July 497.00000 23.90751 56.14968 -0.4281 9.53054
August 514.00000 23.74058 57.89826 -0.4825 10.72026
September 485.00000 23.40216 54.85822 -0.6523 15.45367
October 502.00000 23.14256 45.06574 0.17342 7.48734
November 489.00000 21.99680 41.49192 -0.1658 7.54883
December 497.00000 21.49886 35.84543 -0.3337 9.28888
           
Annual Sum or Average 5943.00000 22.69620 47.70207 -0.3238 10.58096
Minimum of Months 454.00000 21.49886 35.84543 -0.8233 6.93014
Maximum of Months 514.00000 23.90751 57.89826 0.17342 21.65906



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.88929 39.43189 -0.1799 7.85869
February 454.00000 21.96734 42.86366 -0.1351 7.40449
March 514.00000 22.20949 45.48031 -0.0452 7.47744
April 485.00000 23.22483 47.22727 0.25851 8.46348
May 508.00000 23.26210 46.64081 -0.6953 18.46850
June 496.00000 23.65041 52.06501 -0.4892 12.45637
July 497.00000 24.07422 55.06699 -0.2860 8.66873
August 514.00000 23.91596 56.55819 -0.3287 9.06874
September 485.00000 23.50034 54.01087 -0.5492 13.78023
October 502.00000 23.31726 44.32269 0.25692 7.99421
November 489.00000 22.27567 40.40750 -0.0644 6.61832
December 497.00000 21.84466 34.74409 -0.2161 7.43532
           
Annual Sum or Average 5943.00000 22.93442 46.60379 -0.2074 9.66064
Minimum of Months 454.00000 21.84466 34.74409 -0.6953 6.61832
Maximum of Months 514.00000 24.07422 56.55819 0.25851 18.46850



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.07541 36.81352 0.14338 8.88400
February 454.00000 22.71118 41.11743 0.06631 8.47401
March 514.00000 22.54820 44.61591 0.04225 8.25172
April 485.00000 23.17363 47.41893 0.23424 8.35806
May 508.00000 22.96063 47.63914 -0.8340 22.56375
June 496.00000 23.40667 53.09982 -0.6237 14.84914
July 497.00000 23.77723 56.39362 -0.4488 10.41479
August 514.00000 23.81479 57.18132 -0.4028 9.76901
September 485.00000 23.82476 52.95796 -0.4270 11.32041
October 502.00000 23.84952 42.78465 0.41366 10.88324
November 489.00000 23.35899 37.83988 0.23031 8.68405
December 497.00000 23.23618 31.91195 0.15735 8.46852
           
Annual Sum or Average 5943.00000 23.31380 45.86268 -0.1236 10.94332
Minimum of Months 454.00000 22.54820 31.91195 -0.8340 8.25172
Maximum of Months 514.00000 23.84952 57.18132 0.41366 22.56375



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.85676 39.31974 -0.1774 8.19406
February 454.00000 21.97472 42.48458 -0.1156 7.53866
March 514.00000 22.12831 45.49147 -0.0473 7.50995
April 485.00000 23.15110 47.27230 0.25840 8.80884
May 508.00000 23.19350 46.68829 -0.6950 19.17896
June 496.00000 23.67128 51.94919 -0.4543 11.88333
July 497.00000 24.05022 55.19162 -0.2740 8.59237
August 514.00000 23.89257 56.70917 -0.3189 9.05485
September 485.00000 23.57788 53.68128 -0.4962 12.73099
October 502.00000 23.25471 44.13671 0.25790 8.65875
November 489.00000 22.34392 39.89411 -0.0318 7.24067
December 497.00000 21.95178 34.22309 -0.1779 7.63822
           
Annual Sum or Average 5943.00000 22.92667 46.45945 -0.1908 9.77421
Minimum of Months 454.00000 21.85676 34.22309 -0.6950 7.24067
Maximum of Months 514.00000 24.05022 56.70917 0.25840 19.17896



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.345551E+11 92886.13 18-JAN-14:30 241.82 0.197067E+12 0.00 0.231622E+12 1.66 7.18 13-JAN-14:00 0.00 0.00
February 0.220488E+11 82201.94 03-FEB-12:20 186.23 0.117044E+12 0.00 0.139092E+12 1.32 7.01 03-FEB-12:20 0.00 0.00
March 0.233605E+11 86280.47 23-MAR-13:50 183.41 0.127155E+12 0.00 0.150516E+12 1.20 7.05 23-MAR-13:50 0.00 0.00
April 0.471358E+11 89407.86 12-APR-14:00 305.43 0.276562E+12 0.00 0.323698E+12 2.24 7.05 26-APR-13:50 0.00 0.00
May 0.522540E+11 88392.16 03-MAY-13:00 336.89 0.298062E+12 0.00 0.350316E+12 2.34 7.09 03-MAY-13:00 0.00 0.00
June 0.758837E+11 108626.22 29-JUN-13:00 442.21 0.453199E+12 0.00 0.529082E+12 3.33 7.04 29-JUN-16:00 0.00 0.00
July 0.111316E+12 146882.69 31-JUL-15:50 567.26 0.700343E+12 0.00 0.811659E+12 4.30 7.14 29-JUL-05:03 0.00 0.00
August 0.124160E+12 148475.36 18-AUG-15:50 598.32 0.795338E+12 0.00 0.919498E+12 4.62 7.27 17-AUG-05:03 0.00 0.00
September 0.815125E+11 126703.19 29-SEP-12:20 430.69 0.501788E+12 0.00 0.583301E+12 3.34 7.34 30-SEP-05:02 0.00 0.00
October 0.904472E+11 135187.03 03-OCT-13:30 446.41 0.570061E+12 0.00 0.660509E+12 3.44 7.31 02-OCT-05:03 0.00 0.00
November 0.385073E+11 83018.93 28-NOV-14:00 276.37 0.220576E+12 0.00 0.259083E+12 1.96 7.03 08-NOV-12:30 0.00 0.00
December 0.381397E+11 88058.36 05-DEC-15:00 252.66 0.226325E+12 0.00 0.264465E+12 1.79 7.05 05-DEC-14:30 0.00 0.00
                         
Annual Sum or Average 0.739321E+12     4267.70 0.448352E+13 0.00 0.522284E+13 2.64     0.00 0.00
Minimum of Months 0.220488E+11 82201.94   183.41 0.117044E+12 0.00 0.139092E+12 1.20 7.01   0.00 0.00
Maximum of Months 0.124160E+12 148475.36   598.32 0.795338E+12 0.00 0.919498E+12 4.62 7.34   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.219818E+10 92886.13 18-JAN-14:30 7.33 0.154101E+11 0.00 0.176083E+11 0.07 7.18 13-JAN-14:00 0.00 0.00
February 0.191081E+09 80454.60 01-FEB-12:00 0.67 0.132659E+10 0.00 0.151767E+10 0.01 6.96 01-FEB-13:20 0.00 0.00
March 0.982937E+09 86280.47 23-MAR-13:50 3.33 0.683578E+10 0.00 0.781871E+10 0.03 7.05 23-MAR-13:50 0.00 0.00
April 0.266871E+10 89407.86 12-APR-14:00 9.00 0.185573E+11 0.00 0.212260E+11 0.09 7.05 26-APR-13:50 0.00 0.00
May 0.108142E+10 88392.16 03-MAY-13:00 3.67 0.755523E+10 0.00 0.863665E+10 0.03 7.09 03-MAY-13:00 0.00 0.00
June 0.124995E+11 108626.22 29-JUN-13:00 39.71 0.868856E+11 0.00 0.993851E+11 0.38 7.04 29-JUN-16:00 0.00 0.00
July 0.408316E+11 146882.69 31-JUL-15:50 113.98 0.283112E+12 0.00 0.323944E+12 1.06 7.14 29-JUL-05:03 0.00 0.00
August 0.565302E+11 148475.36 18-AUG-15:50 157.41 0.392226E+12 0.00 0.448757E+12 1.47 7.27 17-AUG-05:03 0.00 0.00
September 0.239105E+11 126703.19 29-SEP-12:20 73.58 0.166591E+12 0.00 0.190502E+12 0.71 7.34 30-SEP-05:02 0.00 0.00
October 0.330136E+11 135187.03 03-OCT-13:30 98.87 0.231144E+12 0.00 0.264158E+12 0.93 7.31 02-OCT-05:03 0.00 0.00
November 0.534798E+09 83018.93 28-NOV-14:00 1.83 0.372510E+10 0.00 0.425990E+10 0.02 7.01 28-NOV-13:10 0.00 0.00
December 0.280482E+10 88058.36 05-DEC-15:00 9.67 0.195001E+11 0.00 0.223049E+11 0.09 7.05 05-DEC-14:30 0.00 0.00
                         
Annual Sum or Average 0.177247E+12     519.04 0.123287E+13 0.00 0.141012E+13 0.41     0.00 0.00
Minimum of Months 0.191081E+09 80454.60   0.67 0.132659E+10 0.00 0.151767E+10 0.01 6.96   0.00 0.00
Maximum of Months 0.565302E+11 148475.36   157.41 0.392226E+12 0.00 0.448757E+12 1.47 7.34   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.597406E+11 744.00 49248.27 03-JAN-11:40 214300.22 17-JAN-14:20 22.72 18.98 13.93
February 0.776705E+11 672.00 49248.27 01-FEB-03:40 355036.18 01-FEB-12:10 25.44 18.83 13.93
March 0.994085E+11 744.00 49248.27 01-MAR-09:00 588884.68 31-MAR-24:00 28.64 19.16 13.93
April 0.122060E+12 720.00 49248.27 01-APR-07:40 666078.56 26-APR-14:20 33.43 20.96 13.93
May 0.828452E+11 744.00 49248.27 01-MAY-08:50 317723.49 31-MAY-24:00 23.12 19.24 13.93
June 0.120799E+12 720.00 49248.27 01-JUN-07:45 466983.66 30-JUN-24:00 27.74 20.85 13.93
July 0.131795E+12 744.00 49248.27 01-JUL-00:10 617940.40 31-JUL-23:53 33.50 23.55 13.93
August 0.131892E+12 744.00 49248.27 01-AUG-00:03 675150.62 18-AUG-15:30 37.89 25.02 13.93
September 0.113850E+12 720.00 49248.27 01-SEP-07:50 330988.72 30-SEP-24:00 24.60 20.59 13.93
October 0.121834E+12 744.00 49248.27 01-OCT-00:10 464388.22 31-OCT-23:40 29.14 22.19 13.93
November 0.108037E+12 720.00 49248.27 01-NOV-00:10 513440.64 19-NOV-14:02 29.39 19.81 13.93
December 0.113874E+12 744.00 49248.27 01-DEC-10:30 652357.97 05-DEC-15:50 32.86 20.46 13.93
                   
Annual Sum or Average 0.128381E+13 8760.00         29.07 20.82 13.93
Minimum of Months 0.597406E+11 672.00 49248.27   214300.22   22.72 18.83 13.93
Maximum of Months 0.131892E+12 744.00 49248.27   675150.62   37.89 25.02 13.93



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.176158E+10 180.05 16426.67 13-JAN-13:50 1012476.59 18-JAN-13:50 21.62 21.17 15.22
February 0.679862E+09 126.04 15795.55 01-FEB-13:20 982455.49 01-FEB-13:20 21.37 21.08 13.09
March 0.140250E+10 134.78 16426.67 22-MAR-11:30 850560.29 23-MAR-13:50 21.38 21.09 11.93
April 0.371210E+10 244.65 16426.67 04-APR-11:30 956879.22 13-APR-09:20 21.80 21.16 21.16
May 0.338691E+10 283.61 16426.67 02-MAY-12:30 988127.51 18-MAY-15:20 21.81 21.15 23.16
June 0.879066E+10 400.34 16426.67 13-JUN-10:50 887046.61 20-JUN-15:10 22.33 21.28 31.90
July 0.173713E+11 505.73 16426.67 01-JUL-10:30 1150991.54 31-JUL-16:00 23.10 21.62 39.62
August 0.201819E+11 541.56 16426.67 01-AUG-09:50 1150723.53 18-AUG-16:00 23.39 21.74 42.05
September 0.108092E+11 393.58 16426.67 01-SEP-10:40 1016610.60 29-SEP-08:20 22.64 21.51 30.96
October 0.103597E+11 405.14 16426.67 01-OCT-10:40 1093176.46 17-OCT-08:50 22.70 21.46 31.07
November 0.142760E+10 199.78 16426.67 10-NOV-13:00 976793.13 28-NOV-11:50 21.61 21.09 18.27
December 0.113488E+10 184.54 14920.81 07-DEC-13:30 985678.23 18-DEC-13:10 21.63 21.10 16.06
                   
Annual Sum or Average 0.810183E+11 3599.81         22.12 21.29 24.62
Minimum of Months 0.679862E+09 126.04 14920.81   850560.29   21.37 21.08 11.93
Maximum of Months 0.201819E+11 541.56 16426.67   1150991.54   23.39 21.74 42.05



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.161651E+09 3.17 16426.67 13-JAN-13:50 1012476.59 18-JAN-13:50 21.62 21.60 0.23
February 9477332.46 0.17 15795.55 01-FEB-13:20 982455.49 01-FEB-13:20 21.37 21.37 0.01
March 0.147840E+09 2.50 16426.67 22-MAR-13:00 850560.29 23-MAR-13:50 21.38 21.37 0.18
April 0.303239E+09 5.17 16426.67 04-APR-14:00 956879.22 13-APR-09:20 21.80 21.77 0.38
May 86116286.19 1.50 16426.67 03-MAY-12:00 988127.51 18-MAY-15:20 21.81 21.80 0.11
June 0.216832E+10 36.67 16426.67 15-JUN-15:00 881092.06 29-JUN-13:00 22.33 22.16 2.71
July 0.667728E+10 112.91 16426.67 03-JUL-12:10 1150991.54 31-JUL-16:00 23.10 22.55 8.06
August 0.915393E+10 154.79 16426.67 02-AUG-09:10 1150723.53 18-AUG-16:00 23.39 22.62 11.06
September 0.401014E+10 68.02 16426.67 05-SEP-12:30 1016610.60 29-SEP-08:20 22.64 22.31 5.02
October 0.431043E+10 77.59 16426.67 01-OCT-12:32 1093176.46 17-OCT-08:50 22.70 22.30 5.54
November 2429067.48 0.17 4048.45 28-NOV-11:50 976793.13 28-NOV-11:50 21.61 21.60 0.01
December 37681604.13 2.17 6357.98 05-DEC-11:10 985678.23 18-DEC-13:10 21.63 21.62 0.15
                   
Annual Sum or Average 0.270685E+11 464.83         22.12 21.93 2.82
Minimum of Months 2429067.48 0.17 4048.45   850560.29   21.37 21.37 0.01
Maximum of Months 0.915393E+10 154.79 16426.67   1150991.54   23.39 22.62 11.06



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.703403E+11 0.00 207.87 811333.50 02-JAN-06:01 0.00 36.62 49.35 0.16 0.00 0.02 0.49 02-JAN-06:01
February 0.504628E+11 0.00 203.48 417537.49 10-FEB-07:10 0.00 32.49 47.32 0.11 0.00 0.01 0.25 10-FEB-07:10
March 0.759570E+11 0.00 248.86 817124.51 30-MAR-05:03 0.00 35.00 50.66 0.16 0.00 0.02 0.49 30-MAR-05:03
April 0.211443E+11 0.00 114.75 458938.46 01-APR-06:10 0.00 29.12 37.38 0.04 0.00 0.00 0.28 01-APR-06:10
May 0.137213E+11 0.00 89.37 169544.12 15-MAY-06:10 0.00 29.02 35.35 0.02 0.00 0.00 0.10 15-MAY-06:10
June 0.131553E+10 0.00 21.25 124745.56 12-JUN-21:00 0.00 28.48 30.12 0.00 0.00 0.00 0.08 12-JUN-21:00
July 92922.80 0.00 0.17 154.87 07-JUL-21:00 0.00 30.37 30.38 0.00 0.00 0.00 0.00 07-JUL-21:00
August 11588435.48 0.00 2.17 3491.72 28-AUG-07:00 0.00 30.31 30.47 0.00 0.00 0.00 0.00 28-AUG-07:00
September 0.104381E+10 0.00 19.54 93791.87 20-SEP-06:10 0.00 28.00 29.49 0.00 0.00 0.00 0.06 20-SEP-06:10
October 0.422594E+10 0.00 32.58 265240.19 12-OCT-06:05 0.00 29.20 31.47 0.01 0.00 0.00 0.16 12-OCT-06:05
November 0.290211E+11 0.00 158.67 318627.61 30-NOV-07:10 0.00 31.60 42.65 0.06 0.00 0.01 0.19 30-NOV-07:10
December 0.557633E+11 0.00 197.44 520745.29 23-DEC-07:05 0.00 34.97 47.20 0.12 0.00 0.01 0.31 23-DEC-07:05
                           
Annual Sum or Average 0.323007E+12 0.00 1296.13     0.00 31.28 38.45 0.06 0.00 0.01    
Minimum of Months 92922.80 0.00 0.17 154.87   0.00 28.00 29.49 0.00 0.00 0.00 0.00  
Maximum of Months 0.759570E+11 0.00 248.86 817124.51   0.00 36.62 50.66 0.16 0.00 0.02 0.49  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 22.72 22.72 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 25.44 25.44 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 28.64 28.64 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 33.43 33.43 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 23.12 23.12 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 27.74 27.74 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 33.50 33.50 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 37.89 37.89 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 24.60 24.60 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 29.14 29.14 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.39 29.39 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 32.86 32.86 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 29.07 29.07 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.72 22.72 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 37.89 37.89 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.207122E+11 0.00 219.99 0.206778E+11 0.00 0.00 0.00 0.00 90868.20 18-JAN-13:10 90868.20 18-JAN-13:10 0.00 0.00 0.00
February 0.121801E+11 0.00 171.64 0.121008E+11 0.00 0.00 0.00 0.00 87297.82 01-FEB-12:00 87297.82 01-FEB-12:00 0.00 0.00 0.00
March 0.147850E+11 0.00 173.81 0.143362E+11 0.00 0.00 0.00 0.00 100180.10 23-MAR-14:00 83220.37 23-MAR-14:00 0.00 0.00 0.00
April 0.333266E+11 0.00 292.90 0.332214E+11 0.00 0.00 0.00 0.00 112697.87 26-APR-11:00 112480.53 26-APR-13:10 0.00 0.00 0.00
May 0.301885E+11 0.00 324.66 0.300778E+11 0.00 0.00 0.00 0.00 82853.43 03-MAY-13:00 82853.43 03-MAY-13:00 0.00 0.00 0.00
June 0.561840E+11 0.00 427.58 0.502566E+11 0.00 0.00 0.00 0.00 134915.59 29-JUN-13:00 90598.68 29-JUN-11:00 0.00 0.00 0.00
July 0.104123E+12 0.00 543.62 0.744661E+11 0.00 0.00 0.00 0.00 188451.06 31-JUL-15:40 119130.22 31-JUL-13:10 0.00 0.00 0.00
August 0.128606E+12 0.00 580.52 0.862185E+11 0.00 0.00 0.00 0.00 190354.86 07-AUG-10:40 120395.30 14-AUG-11:00 0.00 0.00 0.00
September 0.636230E+11 0.00 414.47 0.522577E+11 0.00 0.00 0.00 0.00 152911.92 22-SEP-12:30 135869.44 29-SEP-13:00 0.00 0.00 0.00
October 0.784053E+11 0.00 422.75 0.655185E+11 0.00 0.00 0.00 0.00 176946.09 04-OCT-05:03 149068.67 16-OCT-11:00 0.00 0.00 0.00
November 0.253077E+11 0.00 254.30 0.249706E+11 0.00 0.00 0.00 0.00 96446.35 28-NOV-14:00 96446.35 28-NOV-14:00 0.00 0.00 0.00
December 0.295185E+11 0.00 236.30 0.294169E+11 0.00 0.00 0.00 0.00 103801.22 05-DEC-15:00 103801.22 05-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.596959E+12 0.00 4062.54 0.493519E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.121801E+11 0.00 171.64 0.121008E+11 0.00 0.00 0.00 0.00 82853.43   82853.43   0.00 0.00 0.00
Maximum of Months 0.128606E+12 0.00 580.52 0.862185E+11 0.00 0.00 0.00 0.00 190354.86   149068.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.172506E+12 0.00 227.82 0.171849E+12 0.00 0.00 0.00 0.00 777380.88 18-JAN-13:10 777380.88 18-JAN-13:10 0.00 0.00 0.00
February 0.939737E+11 0.00 175.73 0.931998E+11 0.00 0.00 0.00 0.00 741571.96 01-FEB-12:00 741571.96 01-FEB-12:00 0.00 0.00 0.00
March 0.106589E+12 0.00 169.47 0.103675E+12 0.00 0.00 0.00 0.00 818431.57 23-MAR-14:20 681846.43 23-MAR-14:00 0.00 0.00 0.00
April 0.237220E+12 0.00 267.94 0.237071E+12 0.00 0.00 0.00 0.00 921181.56 26-APR-13:00 921181.56 26-APR-13:00 0.00 0.00 0.00
May 0.250196E+12 0.00 315.20 0.249228E+12 0.00 0.00 0.00 0.00 745828.92 03-MAY-13:00 745828.92 03-MAY-13:00 0.00 0.00 0.00
June 0.454366E+12 0.00 402.50 0.408591E+12 0.00 0.00 0.00 0.00 1169203.87 29-JUN-13:00 786417.63 29-JUN-11:00 0.00 0.00 0.00
July 0.799079E+12 0.00 447.59 0.580492E+12 0.00 0.00 0.00 0.00 1549712.96 31-JUL-15:50 1004716.72 31-JUL-13:00 0.00 0.00 0.00
August 0.945120E+12 0.00 466.08 0.651876E+12 0.00 0.00 0.00 0.00 1575514.05 18-AUG-15:50 1016884.83 17-AUG-14:00 0.00 0.00 0.00
September 0.544737E+12 0.00 398.27 0.449783E+12 0.00 0.00 0.00 0.00 1365300.00 22-SEP-12:30 1309611.89 29-SEP-13:00 0.00 0.00 0.00
October 0.638222E+12 0.00 402.53 0.536457E+12 0.00 0.00 0.00 0.00 1682907.34 05-OCT-05:03 1354048.95 16-OCT-11:00 0.00 0.00 0.00
November 0.183258E+12 0.00 251.55 0.181383E+12 0.00 0.00 0.00 0.00 746291.43 28-NOV-14:00 746291.43 28-NOV-14:00 0.00 0.00 0.00
December 0.207585E+12 0.00 225.21 0.206864E+12 0.00 0.00 0.00 0.00 788584.41 05-DEC-15:00 788584.41 05-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.463285E+13 0.00 3749.89 0.387047E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.939737E+11 0.00 169.47 0.931998E+11 0.00 0.00 0.00 0.00 741571.96   681846.43   0.00 0.00 0.00
Maximum of Months 0.945120E+12 0.00 466.08 0.651876E+12 0.00 0.00 0.00 0.00 1682907.34   1354048.95   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.131388E+11 0.00 197.89 0.131388E+11 0.00 0.00 0.00 0.00 75255.74 18-JAN-13:30 75255.74 18-JAN-13:30 0.00 0.00 0.00
February 0.740741E+10 0.00 150.03 0.734068E+10 0.00 0.00 0.00 0.00 68162.52 01-FEB-12:00 68162.52 01-FEB-12:00 0.00 0.00 0.00
March 0.918160E+10 0.00 150.72 0.904819E+10 0.00 0.00 0.00 0.00 80375.68 23-MAR-15:00 71781.24 23-MAR-14:00 0.00 0.00 0.00
April 0.233213E+11 0.00 253.22 0.233150E+11 0.00 0.00 0.00 0.00 110117.24 26-APR-14:00 110117.24 26-APR-14:00 0.00 0.00 0.00
May 0.245790E+11 0.00 299.98 0.245021E+11 0.00 0.00 0.00 0.00 84671.26 03-MAY-13:00 84671.26 03-MAY-13:00 0.00 0.00 0.00
June 0.472310E+11 0.00 390.09 0.422587E+11 0.00 0.00 0.00 0.00 132681.07 29-JUN-13:00 85054.48 29-JUN-11:00 0.00 0.00 0.00
July 0.858566E+11 0.00 433.07 0.623418E+11 0.00 0.00 0.00 0.00 195991.94 31-JUL-15:10 123204.27 31-JUL-13:10 0.00 0.00 0.00
August 0.100159E+12 0.00 449.09 0.687529E+11 0.00 0.00 0.00 0.00 193425.62 18-AUG-15:30 122339.91 17-AUG-14:00 0.00 0.00 0.00
September 0.536031E+11 0.00 372.99 0.446671E+11 0.00 0.00 0.00 0.00 155159.47 29-SEP-13:00 155159.47 29-SEP-13:00 0.00 0.00 0.00
October 0.612202E+11 0.00 379.98 0.516692E+11 0.00 0.00 0.00 0.00 156844.69 05-OCT-05:03 152620.36 16-OCT-12:10 0.00 0.00 0.00
November 0.141092E+11 0.00 223.67 0.141032E+11 0.00 0.00 0.00 0.00 72217.30 28-NOV-14:00 72217.30 28-NOV-14:00 0.00 0.00 0.00
December 0.160405E+11 0.00 199.97 0.160405E+11 0.00 0.00 0.00 0.00 80413.59 05-DEC-15:00 80413.59 05-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.455848E+12 0.00 3500.70 0.377178E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.740741E+10 0.00 150.03 0.734068E+10 0.00 0.00 0.00 0.00 68162.52   68162.52   0.00 0.00 0.00
Maximum of Months 0.100159E+12 0.00 449.09 0.687529E+11 0.00 0.00 0.00 0.00 195991.94   155159.47   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.121005E+11 0.00 149.63 0.120595E+11 0.00 0.00 0.00 0.00 70283.31 17-JAN-14:00 68583.98 17-JAN-12:00 0.00 0.00 0.00
February 0.537816E+10 0.00 94.02 0.534066E+10 0.00 0.00 0.00 0.00 64735.52 13-FEB-06:03 56568.59 01-FEB-12:00 0.00 0.00 0.00
March 0.624411E+10 0.00 96.30 0.619945E+10 0.00 0.00 0.00 0.00 47834.86 23-MAR-14:00 47834.86 23-MAR-14:00 0.00 0.00 0.00
April 0.160624E+11 0.00 193.95 0.159714E+11 0.00 0.00 0.00 0.00 63932.99 27-APR-05:03 59551.72 26-APR-13:10 0.00 0.00 0.00
May 0.156200E+11 0.00 211.32 0.155462E+11 0.00 0.00 0.00 0.00 60871.43 03-MAY-05:03 53257.82 03-MAY-13:00 0.00 0.00 0.00
June 0.285060E+11 0.00 277.02 0.271747E+11 0.00 0.00 0.00 0.00 84518.98 30-JUN-05:03 63730.26 26-JUN-10:00 0.00 0.00 0.00
July 0.484688E+11 0.00 327.83 0.411180E+11 0.00 0.00 0.00 0.00 105925.76 31-JUL-09:10 69936.55 31-JUL-12:10 0.00 0.00 0.00
August 0.562466E+11 0.00 365.67 0.457965E+11 0.00 0.00 0.00 0.00 121803.78 07-AUG-09:50 71902.06 14-AUG-11:00 0.00 0.00 0.00
September 0.340179E+11 0.00 283.03 0.301664E+11 0.00 0.00 0.00 0.00 97954.20 22-SEP-10:00 83785.91 30-SEP-04:02 0.00 0.00 0.00
October 0.440538E+11 0.00 307.50 0.383321E+11 0.00 0.00 0.00 0.00 110840.74 05-OCT-04:03 86694.13 16-OCT-11:00 0.00 0.00 0.00
November 0.134614E+11 0.00 175.33 0.134305E+11 0.00 0.00 0.00 0.00 61339.83 10-NOV-04:02 60316.64 27-NOV-12:00 0.00 0.00 0.00
December 0.166741E+11 0.00 159.71 0.166620E+11 0.00 0.00 0.00 0.00 70463.54 25-DEC-15:10 70463.54 25-DEC-15:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.296834E+12 0.00 2641.33 0.267797E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.537816E+10 0.00 94.02 0.534066E+10 0.00 0.00 0.00 0.00 47834.86   47834.86   0.00 0.00 0.00
Maximum of Months 0.562466E+11 0.00 365.67 0.457965E+11 0.00 0.00 0.00 0.00 121803.78   86694.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.331040E+12 0.838854E+11 744.00 0.329840E+12 0.120003E+10 0.00 0.37 14-JAN-12:00 0.31 28-JAN-07:10 130973.02 17-JAN-14:50 127419.32 18-JAN-13:10 5465.73 17-JAN-15:00 42136.49 14-JAN-12:00 0.00
February 0.518421E+12 0.123697E+12 672.00 0.516791E+12 0.163027E+10 0.00 0.60 03-FEB-15:00 0.53 11-FEB-07:40 220265.99 13-FEB-17:00 217491.00 03-FEB-15:00 6229.62 01-FEB-17:00 70548.62 01-FEB-12:00 0.00
March 0.819587E+12 0.189624E+12 744.00 0.817356E+12 0.223076E+10 0.00 0.93 31-MAR-24:00 0.73 01-MAR-07:05 393891.87 31-MAR-24:00 393891.87 31-MAR-24:00 6395.74 23-MAR-16:10 95029.03 11-MAR-12:00 0.00
April 0.103220E+13 0.243465E+12 720.00 0.102956E+13 0.263927E+10 0.00 1.00 01-APR-09:50 0.36 30-APR-24:00 408230.00 26-APR-15:00 402236.12 26-APR-16:00 6569.97 26-APR-15:00 127894.82 26-APR-13:00 0.00
May 0.333693E+12 0.845005E+11 744.00 0.330665E+12 0.302800E+10 0.00 0.53 31-MAY-24:00 0.32 15-MAY-06:10 211325.01 31-MAY-23:20 211147.21 31-MAY-24:00 5966.65 05-MAY-15:00 49338.69 31-MAY-24:00 0.00
June 0.562586E+12 0.142361E+12 720.00 0.557048E+12 0.553783E+10 0.00 0.74 30-JUN-24:00 0.53 01-JUN-06:10 303012.04 30-JUN-24:00 302878.42 30-JUN-24:00 7439.08 28-JUN-13:00 72513.01 30-JUN-24:00 0.00
July 0.829763E+12 0.218780E+12 744.00 0.822910E+12 0.685299E+10 0.00 0.95 31-JUL-23:22 0.74 17-JUL-06:10 394968.11 31-JUL-23:53 394968.11 31-JUL-23:53 8960.15 28-JUL-14:00 106657.40 31-JUL-13:00 0.00
August 0.107393E+13 0.284640E+12 744.00 0.106710E+13 0.682936E+10 0.00 1.00 02-AUG-09:50 0.36 31-AUG-24:00 411515.09 18-AUG-17:00 402179.49 25-AUG-15:40 10273.83 18-AUG-16:10 130672.73 14-AUG-11:00 0.00
September 0.328657E+12 0.868723E+11 720.00 0.323200E+12 0.545668E+10 0.00 0.55 30-SEP-24:00 0.32 20-SEP-06:10 211451.78 30-SEP-24:00 211451.78 30-SEP-24:00 8534.47 22-SEP-10:50 57485.30 29-SEP-12:05 0.00
October 0.582342E+12 0.155383E+12 744.00 0.578820E+12 0.352197E+10 0.00 0.74 31-OCT-23:20 0.53 28-OCT-06:15 304835.47 31-OCT-24:00 303687.02 31-OCT-24:00 9023.80 05-OCT-16:00 100239.12 16-OCT-11:00 0.00
November 0.796594E+12 0.188830E+12 720.00 0.794786E+12 0.180743E+10 0.00 0.84 28-NOV-14:00 0.73 01-NOV-07:00 314123.47 10-NOV-17:00 310687.69 28-NOV-14:00 6430.70 10-NOV-17:10 102438.78 19-NOV-13:00 0.00
December 0.106628E+13 0.249858E+12 744.00 0.106563E+13 0.646031E+09 0.00 1.00 04-DEC-08:55 0.92 23-DEC-07:05 405241.38 29-DEC-16:30 405241.38 29-DEC-16:30 5416.17 07-DEC-17:00 124961.63 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.827508E+13 0.205190E+13 8760.00 0.823370E+13 0.413806E+11 0.00                         0.00
Minimum of Months 0.328657E+12 0.838854E+11 672.00 0.323200E+12 0.646031E+09 0.00 0.37   0.31   130973.02   127419.32   5416.17   42136.49   0.00
Maximum of Months 0.107393E+13 0.284640E+12 744.00 0.106710E+13 0.685299E+10 0.00 1.00   0.92   411515.09   405241.38   10273.83   130672.73   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.522427E+10 0.132507E+10 744.00 0.517997E+10 44295557.81 0.00 0.33 15-JAN-15:53 0.17 28-JAN-07:20 2492.25 18-JAN-16:10 2402.22 18-JAN-16:10 178.42 20-JAN-17:00 740.88 13-JAN-14:00 0.00
February 0.940320E+10 0.222251E+10 672.00 0.933815E+10 65043290.21 0.00 0.56 03-FEB-15:00 0.39 25-FEB-18:00 4498.56 21-FEB-17:00 4455.18 20-FEB-17:07 229.90 13-FEB-17:00 1320.47 01-FEB-12:00 0.00
March 0.155809E+11 0.354443E+10 744.00 0.154876E+11 93336503.86 0.00 0.85 31-MAR-24:00 0.61 01-MAR-07:05 7559.27 31-MAR-24:00 7559.27 31-MAR-24:00 253.23 23-MAR-16:10 1781.50 11-MAR-14:00 0.00
April 0.202252E+11 0.468752E+10 720.00 0.201093E+11 0.115927E+09 0.00 0.99 02-APR-13:52 0.31 30-APR-24:00 8360.58 16-APR-17:30 8347.34 30-APR-17:14 230.36 17-APR-16:00 2572.08 26-APR-13:00 0.00
May 0.564666E+10 0.140969E+10 744.00 0.553903E+10 0.107622E+09 0.00 0.46 31-MAY-24:00 0.19 13-MAY-07:00 3881.69 31-MAY-24:00 3862.81 31-MAY-24:00 214.54 05-MAY-15:20 888.71 31-MAY-24:00 0.00
June 0.106846E+11 0.264527E+10 720.00 0.104797E+11 0.204884E+09 0.00 0.68 30-JUN-24:00 0.43 01-JUN-06:10 5913.33 30-JUN-24:00 5901.62 30-JUN-24:00 291.41 28-JUN-13:00 1383.03 30-JUN-24:00 0.00
July 0.162546E+11 0.418781E+10 744.00 0.159745E+11 0.280107E+09 0.00 0.88 31-JUL-23:33 0.66 07-JUL-21:00 7773.03 31-JUL-23:50 7771.67 31-JUL-23:45 360.56 28-JUL-14:00 2103.48 31-JUL-13:00 0.00
August 0.212940E+11 0.552801E+10 744.00 0.209851E+11 0.308928E+09 0.00 1.00 17-AUG-14:00 0.31 31-AUG-24:00 8520.65 17-AUG-15:50 8430.35 06-AUG-17:47 365.21 18-AUG-16:00 2708.64 17-AUG-14:00 0.00
September 0.577372E+10 0.149864E+10 720.00 0.557702E+10 0.196697E+09 0.00 0.50 30-SEP-24:00 0.22 20-SEP-06:20 4059.00 30-SEP-24:00 4059.00 30-SEP-24:00 336.51 22-SEP-10:50 1094.51 29-SEP-13:00 0.00
October 0.109838E+11 0.288560E+10 744.00 0.108509E+11 0.132978E+09 0.00 0.68 31-OCT-24:00 0.42 28-OCT-06:35 5893.22 31-OCT-24:00 5867.56 31-OCT-24:00 349.49 05-OCT-16:00 1980.38 16-OCT-11:00 0.00
November 0.152437E+11 0.357506E+10 720.00 0.151712E+11 72490589.70 0.00 0.83 28-NOV-14:00 0.62 18-NOV-07:40 6444.37 07-NOV-16:20 6388.76 12-NOV-16:17 250.94 10-NOV-17:00 2037.74 28-NOV-14:00 0.00
December 0.207071E+11 0.483688E+10 744.00 0.206768E+11 30284661.36 0.00 1.00 18-DEC-13:00 0.81 23-DEC-07:05 8373.67 25-DEC-16:10 8373.67 25-DEC-16:10 212.67 07-DEC-17:00 2579.07 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.157022E+12 0.383465E+11 8760.00 0.155369E+12 0.165259E+10 0.00                         0.00
Minimum of Months 0.522427E+10 0.132507E+10 672.00 0.517997E+10 30284661.36 0.00 0.33   0.17   2492.25   2402.22   178.42   740.88   0.00
Maximum of Months 0.212940E+11 0.552801E+10 744.00 0.209851E+11 0.308928E+09 0.00 1.00   0.81   8520.65   8430.35   365.21   2708.64   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.397351E+11 0.102771E+11 744.00 0.393082E+11 0.426814E+09 0.00 0.31 18-JAN-16:10 0.08 02-JAN-07:10 23086.00 18-JAN-16:20 22212.75 18-JAN-16:10 1758.75 20-JAN-16:30 6761.07 24-JAN-16:00 0.00
February 0.811230E+11 0.193630E+11 672.00 0.804831E+11 0.639886E+09 0.00 0.56 03-FEB-15:00 0.34 25-FEB-18:00 42195.79 01-FEB-16:50 40322.40 22-FEB-17:00 2287.07 13-FEB-17:00 12234.55 01-FEB-12:00 0.00
March 0.139988E+12 0.320817E+11 744.00 0.139060E+12 0.927305E+09 0.00 0.80 31-MAR-23:40 0.55 30-MAR-06:10 67764.60 31-MAR-23:40 67764.60 31-MAR-23:40 2511.99 23-MAR-16:10 16861.14 23-MAR-14:00 0.00
April 0.188456E+12 0.438296E+11 720.00 0.187298E+12 0.115836E+10 0.00 0.97 26-APR-13:20 0.27 30-APR-24:00 78656.43 26-APR-16:00 77588.07 30-APR-17:14 2275.25 17-APR-16:00 24488.57 26-APR-13:00 0.00
May 0.488200E+11 0.122916E+11 744.00 0.477745E+11 0.104542E+10 0.00 0.44 31-MAY-24:00 0.15 13-MAY-07:00 35242.03 31-MAY-24:00 35008.69 31-MAY-24:00 2112.64 05-MAY-15:20 8103.04 31-MAY-24:00 0.00
June 0.986743E+11 0.245200E+11 720.00 0.966553E+11 0.201900E+10 0.00 0.68 30-JUN-24:00 0.41 01-JUN-06:10 55934.26 30-JUN-24:00 55811.43 30-JUN-24:00 2892.49 28-JUN-13:10 13092.49 30-JUN-24:00 0.00
July 0.153719E+12 0.396403E+11 744.00 0.150934E+12 0.278505E+10 0.00 0.89 31-JUL-23:53 0.65 06-JUL-06:10 74374.95 31-JUL-24:00 74340.15 31-JUL-24:00 3579.08 28-JUL-14:00 20077.87 31-JUL-13:00 0.00
August 0.201986E+12 0.524651E+11 744.00 0.198901E+12 0.308510E+10 0.00 1.00 17-AUG-14:00 0.26 31-AUG-24:00 81024.64 17-AUG-16:00 78587.75 06-AUG-17:47 3632.80 18-AUG-16:00 25784.18 17-AUG-14:00 0.00
September 0.512239E+11 0.133899E+11 720.00 0.493092E+11 0.191469E+10 0.00 0.50 30-SEP-24:00 0.19 20-SEP-06:40 38867.78 30-SEP-24:00 38867.78 30-SEP-24:00 3324.29 22-SEP-10:50 10329.65 29-SEP-13:00 0.00
October 0.999301E+11 0.264204E+11 744.00 0.986202E+11 0.130987E+10 0.00 0.66 31-OCT-24:00 0.38 28-OCT-07:00 54548.75 31-OCT-24:00 54300.39 31-OCT-24:00 3461.11 05-OCT-16:00 18805.32 16-OCT-11:00 0.00
November 0.137672E+12 0.325125E+11 720.00 0.136954E+12 0.718586E+09 0.00 0.81 28-NOV-14:00 0.58 18-NOV-07:40 60820.14 10-NOV-16:20 59325.16 12-NOV-16:30 2495.31 10-NOV-17:00 19122.53 28-NOV-14:00 0.00
December 0.188085E+12 0.442730E+11 744.00 0.187780E+12 0.304966E+09 0.00 1.00 18-DEC-15:30 0.76 13-DEC-07:10 78611.87 07-DEC-16:10 77208.71 18-DEC-16:20 2117.49 07-DEC-17:00 24536.82 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.142941E+13 0.351064E+12 8760.00 0.141308E+13 0.163350E+11 0.00                         0.00
Minimum of Months 0.397351E+11 0.102771E+11 672.00 0.393082E+11 0.304966E+09 0.00 0.31   0.08   23086.00   22212.75   1758.75   6761.07   0.00
Maximum of Months 0.201986E+12 0.524651E+11 744.00 0.198901E+12 0.308510E+10 0.00 1.00   0.76   81024.64   78587.75   3632.80   25784.18   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.268086E+10 0.715037E+09 687.26 0.263987E+10 40991754.53 0.00 0.31 18-JAN-16:10 0.00 01-JAN-00:05 2331.04 18-JAN-16:10 2243.61 18-JAN-16:10 175.90 20-JAN-16:30 676.74 24-JAN-16:00 0.00
February 0.703618E+10 0.170376E+10 672.00 0.697325E+10 62926743.08 0.00 0.55 03-FEB-15:00 0.23 26-FEB-07:40 4241.43 01-FEB-16:50 4037.81 03-FEB-16:50 229.25 13-FEB-17:00 1228.45 03-FEB-15:00 0.00
March 0.129964E+11 0.301156E+10 744.00 0.129044E+11 91982780.68 0.00 0.75 31-MAR-23:20 0.45 30-MAR-06:10 6365.03 31-MAR-23:20 6365.03 31-MAR-23:20 251.49 23-MAR-16:10 1701.50 23-MAR-14:00 0.00
April 0.183270E+11 0.429476E+10 720.00 0.182115E+11 0.115489E+09 0.00 0.96 26-APR-14:00 0.24 30-APR-24:00 7967.24 26-APR-16:00 7833.97 30-APR-17:25 226.90 17-APR-16:00 2473.29 26-APR-13:00 0.00
May 0.435687E+10 0.111083E+10 743.83 0.425376E+10 0.103110E+09 0.00 0.40 31-MAY-23:30 0.00 14-MAY-04:25 3231.45 31-MAY-23:20 3191.03 31-MAY-24:00 209.34 05-MAY-15:20 748.88 31-MAY-23:30 0.00
June 0.963787E+10 0.240887E+10 720.00 0.943663E+10 0.201235E+09 0.00 0.66 30-JUN-24:00 0.35 01-JUN-06:30 5463.85 30-JUN-24:00 5451.01 30-JUN-24:00 291.01 28-JUN-13:00 1286.78 29-JUN-11:00 0.00
July 0.152898E+11 0.395838E+10 744.00 0.150116E+11 0.278248E+09 0.00 0.86 31-JUL-23:53 0.61 06-JUL-06:20 7336.91 31-JUL-23:57 7333.16 31-JUL-24:00 358.78 28-JUL-14:00 2036.35 31-JUL-13:00 0.00
August 0.200832E+11 0.523844E+10 744.00 0.197750E+11 0.308146E+09 0.00 1.00 17-AUG-14:30 0.23 31-AUG-24:00 8212.26 17-AUG-16:00 8017.88 20-AUG-17:25 363.73 18-AUG-16:00 2612.38 17-AUG-14:00 0.00
September 0.480689E+10 0.126954E+10 720.00 0.461736E+10 0.189532E+09 0.00 0.48 30-SEP-24:00 0.12 20-SEP-06:50 3823.69 30-SEP-24:00 3823.69 30-SEP-24:00 332.67 22-SEP-11:00 1071.53 29-SEP-13:00 0.00
October 0.949510E+10 0.253704E+10 744.00 0.936511E+10 0.129991E+09 0.00 0.64 16-OCT-11:00 0.30 30-OCT-06:20 5211.27 31-OCT-23:50 5186.42 31-OCT-23:50 346.18 05-OCT-16:00 1907.89 16-OCT-11:00 0.00
November 0.127562E+11 0.304849E+10 720.00 0.126849E+11 71219815.12 0.00 0.80 28-NOV-14:00 0.47 27-NOV-07:05 6096.57 10-NOV-16:20 5874.19 07-NOV-16:10 249.00 10-NOV-17:00 1916.80 28-NOV-14:00 0.00
December 0.175402E+11 0.418530E+10 744.00 0.175100E+11 30208279.11 0.00 1.00 19-DEC-11:30 0.65 26-DEC-07:05 7858.31 07-DEC-16:10 7739.69 19-DEC-16:30 211.64 07-DEC-17:00 2500.27 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.135006E+12 0.334820E+11 8703.10 0.133383E+12 0.162308E+10 0.00                         0.00
Minimum of Months 0.268086E+10 0.715037E+09 672.00 0.263987E+10 30208279.11 0.00 0.31   0.00   2331.04   2243.61   175.90   676.74   0.00
Maximum of Months 0.200832E+11 0.523844E+10 744.00 0.197750E+11 0.308146E+09 0.00 1.00   0.65   8212.26   8017.88   363.73   2612.38   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.16 0.00 78.16 36.24 356.56 0.00 0.00 0.00
February 98.12 0.00 98.12 44.72 325.86 0.00 0.00 0.00
March 120.24 0.00 120.24 69.74 331.09 0.00 0.00 0.00
April 138.53 0.53 137.99 104.27 258.89 0.00 0.00 0.00
May 166.46 7.75 158.71 137.34 219.22 0.00 0.00 0.00
June 177.38 17.34 160.03 181.65 172.99 0.00 0.00 0.00
July 167.95 14.08 153.87 193.22 151.40 0.00 0.00 0.00
August 139.47 2.79 136.68 153.64 160.27 0.00 0.00 0.00
September 118.05 0.02 118.03 118.51 196.57 0.00 0.00 0.00
October 93.64 0.00 93.64 101.15 223.00 0.00 0.00 0.00
November 84.79 0.00 84.79 43.32 327.30 0.00 0.00 0.00
December 72.76 0.00 72.76 29.87 366.69 0.00 0.00 0.00
                 
Annual Sum or Average 121.39 3.56 117.83 101.48 257.13 0.00 0.00 0.00
Minimum of Months 72.76 0.00 72.76 29.87 151.40 0.00 0.00 0.00
Maximum of Months 177.38 17.34 160.03 193.22 366.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.16 0.00 78.16 36.24 356.56 0.00 0.00 0.00
February 98.12 0.00 98.12 44.72 325.86 0.00 0.00 0.00
March 120.23 0.00 120.23 69.74 331.09 0.00 0.00 0.00
April 138.52 0.53 137.99 104.27 258.89 0.00 0.00 0.00
May 166.46 7.75 158.71 137.33 219.22 0.00 0.00 0.00
June 177.37 17.34 160.03 181.64 172.99 0.00 0.00 0.00
July 167.94 14.08 153.87 193.22 151.40 0.00 0.00 0.00
August 139.47 2.79 136.68 153.64 160.27 0.00 0.00 0.00
September 118.05 0.02 118.03 118.51 196.57 0.00 0.00 0.00
October 93.64 0.00 93.64 101.15 223.00 0.00 0.00 0.00
November 84.78 0.00 84.78 43.32 327.30 0.00 0.00 0.00
December 72.76 0.00 72.76 29.87 366.69 0.00 0.00 0.00
                 
Annual Sum or Average 121.39 3.56 117.83 101.48 257.13 0.00 0.00 0.00
Minimum of Months 72.76 0.00 72.76 29.87 151.40 0.00 0.00 0.00
Maximum of Months 177.37 17.34 160.03 193.22 366.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.16 0.00 78.16 36.24 356.56 0.00 0.00 0.00
February 98.12 0.00 98.12 44.72 325.86 0.00 0.00 0.00
March 120.23 0.00 120.23 69.74 331.09 0.00 0.00 0.00
April 138.52 0.53 137.99 104.27 258.89 0.00 0.00 0.00
May 166.46 7.75 158.71 137.33 219.22 0.00 0.00 0.00
June 177.37 17.34 160.03 181.64 172.99 0.00 0.00 0.00
July 167.95 14.08 153.87 193.22 151.40 0.00 0.00 0.00
August 139.47 2.79 136.68 153.64 160.27 0.00 0.00 0.00
September 118.05 0.02 118.03 118.51 196.57 0.00 0.00 0.00
October 93.64 0.00 93.64 101.15 223.00 0.00 0.00 0.00
November 84.79 0.00 84.79 43.32 327.30 0.00 0.00 0.00
December 72.76 0.00 72.76 29.87 366.69 0.00 0.00 0.00
                 
Annual Sum or Average 121.39 3.56 117.83 101.48 257.13 0.00 0.00 0.00
Minimum of Months 72.76 0.00 72.76 29.87 151.40 0.00 0.00 0.00
Maximum of Months 177.37 17.34 160.03 193.22 366.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.16 0.00 78.16 36.24 356.56 0.00 0.00 0.00
February 98.12 0.00 98.12 44.72 325.86 0.00 0.00 0.00
March 120.23 0.00 120.23 69.74 331.09 0.00 0.00 0.00
April 138.52 0.53 137.99 104.27 258.89 0.00 0.00 0.00
May 166.46 7.75 158.71 137.33 219.22 0.00 0.00 0.00
June 177.37 17.34 160.03 181.64 172.99 0.00 0.00 0.00
July 167.94 14.08 153.87 193.22 151.40 0.00 0.00 0.00
August 139.47 2.79 136.68 153.64 160.27 0.00 0.00 0.00
September 118.05 0.02 118.03 118.51 196.57 0.00 0.00 0.00
October 93.64 0.00 93.64 101.15 223.00 0.00 0.00 0.00
November 84.78 0.00 84.78 43.32 327.30 0.00 0.00 0.00
December 72.76 0.00 72.76 29.87 366.69 0.00 0.00 0.00
                 
Annual Sum or Average 121.39 3.56 117.83 101.48 257.13 0.00 0.00 0.00
Minimum of Months 72.76 0.00 72.76 29.87 151.40 0.00 0.00 0.00
Maximum of Months 177.37 17.34 160.03 193.22 366.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 78.16 0.00 78.16 36.24 356.54 0.00 0.00 0.00
February 98.11 0.00 98.11 44.72 325.84 0.00 0.00 0.00
March 120.23 0.00 120.23 69.73 331.08 0.00 0.00 0.00
April 138.52 0.53 137.99 104.26 258.88 0.00 0.00 0.00
May 166.46 7.75 158.70 137.33 219.21 0.00 0.00 0.00
June 177.37 17.34 160.03 181.64 172.98 0.00 0.00 0.00
July 167.94 14.08 153.86 193.21 151.39 0.00 0.00 0.00
August 139.47 2.79 136.67 153.63 160.26 0.00 0.00 0.00
September 118.04 0.02 118.03 118.50 196.57 0.00 0.00 0.00
October 93.64 0.00 93.64 101.15 222.99 0.00 0.00 0.00
November 84.78 0.00 84.78 43.32 327.29 0.00 0.00 0.00
December 72.76 0.00 72.76 29.87 366.67 0.00 0.00 0.00
                 
Annual Sum or Average 121.39 3.56 117.83 101.48 257.12 0.00 0.00 0.00
Minimum of Months 72.76 0.00 72.76 29.87 151.39 0.00 0.00 0.00
Maximum of Months 177.37 17.34 160.03 193.21 366.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 234.27 125.29 108.98 267.43 361.83 0.00 0.00 0.00
February 247.13 113.21 133.92 265.11 329.96 0.00 0.00 0.00
March 300.19 133.75 166.44 340.00 332.83 0.00 0.00 0.00
April 383.79 192.48 191.31 506.42 265.15 0.00 0.00 0.00
May 362.19 151.15 211.04 457.11 243.06 0.00 0.00 0.00
June 359.94 156.17 203.77 490.99 192.78 0.00 0.00 0.00
July 407.84 202.66 205.17 604.93 166.77 0.00 0.00 0.00
August 402.77 213.94 188.83 605.80 168.75 0.00 0.00 0.00
September 293.25 134.38 158.87 413.02 207.33 0.00 0.00 0.00
October 259.58 133.42 126.16 372.50 228.10 0.00 0.00 0.00
November 236.64 120.22 116.42 272.30 328.50 0.00 0.00 0.00
December 225.75 125.43 100.32 257.46 360.90 0.00 0.00 0.00
                 
Annual Sum or Average 309.86 150.47 159.39 405.39 265.15 0.00 0.00 0.00
Minimum of Months 225.75 113.21 100.32 257.46 166.77 0.00 0.00 0.00
Maximum of Months 407.84 213.94 211.04 605.80 361.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 234.27 125.29 108.98 267.43 361.83 0.00 0.00 0.00
February 247.13 113.21 133.92 265.11 329.96 0.00 0.00 0.00
March 300.19 133.75 166.44 340.00 332.83 0.00 0.00 0.00
April 383.79 192.48 191.31 506.42 265.15 0.00 0.00 0.00
May 362.19 151.15 211.04 457.11 243.06 0.00 0.00 0.00
June 359.94 156.17 203.77 490.99 192.78 0.00 0.00 0.00
July 407.84 202.66 205.17 604.93 166.77 0.00 0.00 0.00
August 402.77 213.94 188.83 605.80 168.75 0.00 0.00 0.00
September 293.25 134.38 158.87 413.02 207.33 0.00 0.00 0.00
October 259.58 133.42 126.16 372.50 228.10 0.00 0.00 0.00
November 236.64 120.22 116.42 272.30 328.50 0.00 0.00 0.00
December 225.75 125.43 100.32 257.46 360.90 0.00 0.00 0.00
                 
Annual Sum or Average 309.86 150.47 159.39 405.39 265.15 0.00 0.00 0.00
Minimum of Months 225.75 113.21 100.32 257.46 166.77 0.00 0.00 0.00
Maximum of Months 407.84 213.94 211.04 605.80 361.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 234.27 125.29 108.98 267.42 361.82 0.00 0.00 0.00
February 247.13 113.21 133.92 265.10 329.96 0.00 0.00 0.00
March 300.19 133.75 166.44 339.99 332.83 0.00 0.00 0.00
April 383.79 192.48 191.31 506.41 265.15 0.00 0.00 0.00
May 362.19 151.15 211.04 457.11 243.05 0.00 0.00 0.00
June 359.93 156.17 203.76 490.98 192.77 0.00 0.00 0.00
July 407.83 202.66 205.17 604.92 166.77 0.00 0.00 0.00
August 402.76 213.93 188.83 605.79 168.75 0.00 0.00 0.00
September 293.24 134.38 158.87 413.01 207.33 0.00 0.00 0.00
October 259.57 133.41 126.16 372.49 228.10 0.00 0.00 0.00
November 236.63 120.22 116.41 272.30 328.49 0.00 0.00 0.00
December 225.74 125.43 100.32 257.46 360.89 0.00 0.00 0.00
                 
Annual Sum or Average 309.85 150.47 159.38 405.38 265.15 0.00 0.00 0.00
Minimum of Months 225.74 113.21 100.32 257.46 166.77 0.00 0.00 0.00
Maximum of Months 407.83 213.93 211.04 605.79 361.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 515.82 378.38 137.44 744.88 327.99 0.00 0.00 0.00
February 405.41 249.71 155.70 547.58 301.85 0.00 0.00 0.00
March 323.21 156.12 167.08 427.34 315.88 0.00 0.00 0.00
April 270.05 102.97 167.08 383.12 261.75 0.00 0.00 0.00
May 192.30 23.66 168.63 218.04 232.89 0.00 0.00 0.00
June 168.70 10.19 158.51 191.26 183.40 0.00 0.00 0.00
July 178.69 20.12 158.58 240.39 159.35 0.00 0.00 0.00
August 229.57 72.41 157.16 360.19 167.49 0.00 0.00 0.00
September 319.44 161.87 157.57 504.49 199.45 0.00 0.00 0.00
October 406.26 271.59 134.66 643.32 217.65 0.00 0.00 0.00
November 493.76 348.59 145.17 710.45 303.91 0.00 0.00 0.00
December 551.07 419.43 131.63 799.03 333.79 0.00 0.00 0.00
                 
Annual Sum or Average 337.57 184.37 153.21 480.66 250.17 0.00 0.00 0.00
Minimum of Months 168.70 10.19 131.63 191.26 159.35 0.00 0.00 0.00
Maximum of Months 551.07 419.43 168.63 799.03 333.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 515.82 378.38 137.44 744.87 327.99 0.00 0.00 0.00
February 405.41 249.71 155.70 547.57 301.85 0.00 0.00 0.00
March 323.21 156.12 167.08 427.33 315.88 0.00 0.00 0.00
April 270.05 102.97 167.08 383.12 261.75 0.00 0.00 0.00
May 192.30 23.66 168.63 218.04 232.89 0.00 0.00 0.00
June 168.69 10.18 158.51 191.26 183.40 0.00 0.00 0.00
July 178.69 20.12 158.58 240.39 159.35 0.00 0.00 0.00
August 229.57 72.41 157.16 360.19 167.49 0.00 0.00 0.00
September 319.44 161.87 157.57 504.49 199.45 0.00 0.00 0.00
October 406.25 271.59 134.66 643.31 217.65 0.00 0.00 0.00
November 493.76 348.58 145.17 710.45 303.91 0.00 0.00 0.00
December 551.06 419.43 131.63 799.02 333.79 0.00 0.00 0.00
                 
Annual Sum or Average 337.57 184.36 153.21 480.66 250.17 0.00 0.00 0.00
Minimum of Months 168.69 10.18 131.63 191.26 159.35 0.00 0.00 0.00
Maximum of Months 551.06 419.43 168.63 799.02 333.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 515.82 378.38 137.44 744.88 327.99 0.00 0.00 0.00
February 405.41 249.71 155.70 547.58 301.85 0.00 0.00 0.00
March 323.21 156.12 167.08 427.34 315.88 0.00 0.00 0.00
April 270.05 102.97 167.08 383.12 261.75 0.00 0.00 0.00
May 192.30 23.66 168.63 218.04 232.89 0.00 0.00 0.00
June 168.70 10.19 158.51 191.26 183.40 0.00 0.00 0.00
July 178.69 20.12 158.58 240.39 159.35 0.00 0.00 0.00
August 229.57 72.41 157.16 360.19 167.49 0.00 0.00 0.00
September 319.44 161.87 157.57 504.49 199.45 0.00 0.00 0.00
October 406.26 271.59 134.66 643.32 217.65 0.00 0.00 0.00
November 493.76 348.59 145.17 710.45 303.91 0.00 0.00 0.00
December 551.07 419.43 131.63 799.03 333.79 0.00 0.00 0.00
                 
Annual Sum or Average 337.57 184.37 153.21 480.66 250.17 0.00 0.00 0.00
Minimum of Months 168.70 10.19 131.63 191.26 159.35 0.00 0.00 0.00
Maximum of Months 551.07 419.43 168.63 799.03 333.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 515.82 378.38 137.44 744.87 327.99 0.00 0.00 0.00
February 405.41 249.71 155.70 547.57 301.85 0.00 0.00 0.00
March 323.21 156.12 167.08 427.33 315.88 0.00 0.00 0.00
April 270.05 102.97 167.08 383.12 261.75 0.00 0.00 0.00
May 192.30 23.66 168.63 218.04 232.89 0.00 0.00 0.00
June 168.69 10.18 158.51 191.26 183.40 0.00 0.00 0.00
July 178.69 20.12 158.58 240.39 159.35 0.00 0.00 0.00
August 229.57 72.41 157.16 360.19 167.49 0.00 0.00 0.00
September 319.44 161.87 157.57 504.49 199.45 0.00 0.00 0.00
October 406.25 271.59 134.66 643.31 217.65 0.00 0.00 0.00
November 493.76 348.58 145.17 710.45 303.91 0.00 0.00 0.00
December 551.06 419.43 131.63 799.02 333.79 0.00 0.00 0.00
                 
Annual Sum or Average 337.57 184.36 153.21 480.66 250.17 0.00 0.00 0.00
Minimum of Months 168.69 10.18 131.63 191.26 159.35 0.00 0.00 0.00
Maximum of Months 551.06 419.43 168.63 799.02 333.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 515.80 378.36 137.44 744.84 327.98 0.00 0.00 0.00
February 405.39 249.70 155.69 547.55 301.84 0.00 0.00 0.00
March 323.19 156.12 167.08 427.32 315.86 0.00 0.00 0.00
April 270.04 102.97 167.07 383.11 261.74 0.00 0.00 0.00
May 192.29 23.66 168.62 218.03 232.88 0.00 0.00 0.00
June 168.69 10.18 158.50 191.25 183.39 0.00 0.00 0.00
July 178.69 20.11 158.57 240.38 159.35 0.00 0.00 0.00
August 229.56 72.41 157.15 360.17 167.48 0.00 0.00 0.00
September 319.43 161.86 157.56 504.47 199.44 0.00 0.00 0.00
October 406.24 271.58 134.66 643.29 217.64 0.00 0.00 0.00
November 493.74 348.57 145.17 710.42 303.90 0.00 0.00 0.00
December 551.04 419.41 131.63 798.99 333.77 0.00 0.00 0.00
                 
Annual Sum or Average 337.56 184.36 153.20 480.64 250.16 0.00 0.00 0.00
Minimum of Months 168.69 10.18 131.63 191.25 159.35 0.00 0.00 0.00
Maximum of Months 551.04 419.41 168.62 798.99 333.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 222.99 112.46 110.52 262.96 405.77 0.00 0.00 0.00
February 266.02 122.81 143.21 296.12 384.81 0.00 0.00 0.00
March 304.93 134.91 170.03 342.81 397.52 0.00 0.00 0.00
April 420.37 218.88 201.48 548.86 328.78 0.00 0.00 0.00
May 412.93 190.73 222.20 532.25 275.07 0.00 0.00 0.00
June 437.46 218.72 218.74 597.84 226.54 0.00 0.00 0.00
July 463.08 247.79 215.29 670.11 202.59 0.00 0.00 0.00
August 434.46 235.46 199.00 635.38 215.59 0.00 0.00 0.00
September 371.98 199.04 172.94 531.45 236.24 0.00 0.00 0.00
October 284.36 155.25 129.11 410.17 272.32 0.00 0.00 0.00
November 256.86 134.36 122.51 307.89 394.05 0.00 0.00 0.00
December 226.85 121.67 105.18 264.95 447.44 0.00 0.00 0.00
                 
Annual Sum or Average 342.16 174.56 167.59 450.82 315.20 0.00 0.00 0.00
Minimum of Months 222.99 112.46 105.18 262.96 202.59 0.00 0.00 0.00
Maximum of Months 463.08 247.79 222.20 670.11 447.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 222.99 112.46 110.52 262.96 405.77 0.00 0.00 0.00
February 266.02 122.81 143.21 296.12 384.81 0.00 0.00 0.00
March 304.93 134.91 170.03 342.81 397.52 0.00 0.00 0.00
April 420.37 218.88 201.48 548.86 328.78 0.00 0.00 0.00
May 412.93 190.73 222.20 532.25 275.07 0.00 0.00 0.00
June 437.46 218.72 218.74 597.84 226.54 0.00 0.00 0.00
July 463.08 247.79 215.29 670.11 202.59 0.00 0.00 0.00
August 434.46 235.46 199.00 635.38 215.59 0.00 0.00 0.00
September 371.98 199.04 172.94 531.45 236.24 0.00 0.00 0.00
October 284.36 155.25 129.11 410.17 272.32 0.00 0.00 0.00
November 256.86 134.36 122.51 307.89 394.05 0.00 0.00 0.00
December 226.85 121.67 105.18 264.95 447.44 0.00 0.00 0.00
                 
Annual Sum or Average 342.16 174.56 167.59 450.82 315.20 0.00 0.00 0.00
Minimum of Months 222.99 112.46 105.18 262.96 202.59 0.00 0.00 0.00
Maximum of Months 463.08 247.79 222.20 670.11 447.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 222.98 112.46 110.52 262.95 405.76 0.00 0.00 0.00
February 266.02 122.81 143.21 296.11 384.80 0.00 0.00 0.00
March 304.93 134.90 170.02 342.81 397.51 0.00 0.00 0.00
April 420.36 218.88 201.48 548.85 328.78 0.00 0.00 0.00
May 412.92 190.73 222.20 532.24 275.07 0.00 0.00 0.00
June 437.45 218.72 218.73 597.83 226.54 0.00 0.00 0.00
July 463.07 247.79 215.29 670.09 202.59 0.00 0.00 0.00
August 434.45 235.46 199.00 635.37 215.59 0.00 0.00 0.00
September 371.97 199.04 172.94 531.44 236.24 0.00 0.00 0.00
October 284.36 155.25 129.11 410.16 272.31 0.00 0.00 0.00
November 256.86 134.36 122.50 307.88 394.05 0.00 0.00 0.00
December 226.85 121.67 105.18 264.94 447.43 0.00 0.00 0.00
                 
Annual Sum or Average 342.15 174.56 167.59 450.81 315.20 0.00 0.00 0.00
Minimum of Months 222.98 112.46 105.18 262.95 202.59 0.00 0.00 0.00
Maximum of Months 463.07 247.79 222.20 670.09 447.43 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 390.82 0.00 390.82 222.69 1601.83 0.00 0.00 0.00
February 490.59 0.00 490.59 265.32 1455.51 0.00 0.00 0.00
March 601.18 0.00 601.18 393.25 1491.36 0.00 0.00 0.00
April 692.63 2.67 689.96 562.25 1184.98 0.00 0.00 0.00
May 832.32 38.76 793.56 714.00 1035.86 0.00 0.00 0.00
June 886.88 86.71 800.17 921.67 821.16 0.00 0.00 0.00
July 839.73 70.38 769.35 982.96 731.03 0.00 0.00 0.00
August 697.37 13.96 683.41 790.27 765.47 0.00 0.00 0.00
September 590.25 0.09 590.16 608.77 924.38 0.00 0.00 0.00
October 468.21 0.00 468.21 533.85 1027.36 0.00 0.00 0.00
November 423.93 0.00 423.93 258.41 1469.52 0.00 0.00 0.00
December 363.82 0.00 363.82 201.52 1614.59 0.00 0.00 0.00
                 
Annual Sum or Average 606.97 17.81 589.16 539.61 1175.47 0.00 0.00 0.00
Minimum of Months 363.82 0.00 363.82 201.52 731.03 0.00 0.00 0.00
Maximum of Months 886.88 86.71 800.17 982.96 1614.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 702.81 375.88 326.93 827.22 1000.17 0.00 0.00 0.00
February 741.39 339.64 401.75 814.87 913.06 0.00 0.00 0.00
March 900.57 401.25 499.33 1036.12 935.20 0.00 0.00 0.00
April 1151.37 577.43 573.93 1516.99 771.05 0.00 0.00 0.00
May 1086.56 453.45 633.12 1371.78 701.78 0.00 0.00 0.00
June 1079.80 468.51 611.29 1467.02 563.01 0.00 0.00 0.00
July 1223.49 607.99 615.51 1799.54 508.64 0.00 0.00 0.00
August 1208.30 641.81 566.49 1802.70 518.11 0.00 0.00 0.00
September 879.74 403.13 476.61 1238.07 598.32 0.00 0.00 0.00
October 778.73 400.25 378.48 1121.02 653.74 0.00 0.00 0.00
November 709.90 360.66 349.24 835.98 919.96 0.00 0.00 0.00
December 677.23 376.28 300.96 798.91 1000.55 0.00 0.00 0.00
                 
Annual Sum or Average 929.57 451.41 478.15 1222.01 756.16 0.00 0.00 0.00
Minimum of Months 677.23 339.64 300.96 798.91 508.64 0.00 0.00 0.00
Maximum of Months 1223.49 641.81 633.12 1802.70 1000.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2579.17 1891.94 687.23 3707.39 1609.62 0.00 0.00 0.00
February 2027.09 1248.58 778.51 2721.70 1456.15 0.00 0.00 0.00
March 1616.06 780.64 835.43 2135.47 1512.38 0.00 0.00 0.00
April 1350.26 514.87 835.39 1915.65 1258.68 0.00 0.00 0.00
May 961.49 118.32 843.17 1092.24 1127.02 0.00 0.00 0.00
June 843.48 50.93 792.56 964.53 880.38 0.00 0.00 0.00
July 893.48 100.58 792.90 1210.10 779.21 0.00 0.00 0.00
August 1147.85 362.07 785.78 1801.14 824.65 0.00 0.00 0.00
September 1597.24 809.38 787.86 2504.74 979.57 0.00 0.00 0.00
October 2031.31 1357.99 673.32 3197.16 1067.60 0.00 0.00 0.00
November 2468.85 1742.97 725.88 3533.19 1478.04 0.00 0.00 0.00
December 2755.38 2097.20 658.18 3981.25 1615.98 0.00 0.00 0.00
                 
Annual Sum or Average 1687.89 921.85 766.04 2396.21 1214.53 0.00 0.00 0.00
Minimum of Months 843.48 50.93 658.18 964.53 779.21 0.00 0.00 0.00
Maximum of Months 2755.38 2097.20 843.17 3981.25 1615.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 668.95 337.39 331.56 824.29 1075.84 0.00 0.00 0.00
February 798.06 368.42 429.64 931.78 981.52 0.00 0.00 0.00
March 914.79 404.72 510.07 1082.03 1003.46 0.00 0.00 0.00
April 1261.09 656.65 604.44 1693.59 847.84 0.00 0.00 0.00
May 1238.78 572.19 666.59 1611.53 761.26 0.00 0.00 0.00
June 1312.36 656.15 656.20 1812.00 608.63 0.00 0.00 0.00
July 1389.23 743.37 645.87 2035.50 554.70 0.00 0.00 0.00
August 1303.37 706.37 597.00 1938.39 573.86 0.00 0.00 0.00
September 1115.93 597.12 518.81 1603.57 648.88 0.00 0.00 0.00
October 853.08 465.74 387.33 1261.26 712.84 0.00 0.00 0.00
November 770.58 403.07 367.51 972.12 991.41 0.00 0.00 0.00
December 680.56 365.02 315.54 855.78 1092.50 0.00 0.00 0.00
                 
Annual Sum or Average 1026.45 523.68 502.77 1387.40 820.26 0.00 0.00 0.00
Minimum of Months 668.95 337.39 315.54 824.29 554.70 0.00 0.00 0.00
Maximum of Months 1389.23 743.37 666.59 2035.50 1092.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 390.82 0.00 390.82 274.57 1415.18 0.00 0.00 0.00
February 490.59 0.00 490.59 317.01 1283.82 0.00 0.00 0.00
March 601.18 0.00 601.18 442.04 1348.47 0.00 0.00 0.00
April 692.63 2.67 689.96 589.49 1099.59 0.00 0.00 0.00
May 832.32 38.76 793.56 745.76 967.77 0.00 0.00 0.00
June 886.88 86.71 800.17 926.12 784.42 0.00 0.00 0.00
July 839.73 70.38 769.35 975.15 709.74 0.00 0.00 0.00
August 697.37 13.96 683.41 787.27 737.10 0.00 0.00 0.00
September 590.25 0.09 590.16 619.53 868.55 0.00 0.00 0.00
October 468.21 0.00 468.21 556.31 949.14 0.00 0.00 0.00
November 423.93 0.00 423.93 307.64 1306.96 0.00 0.00 0.00
December 363.82 0.00 363.82 253.72 1423.81 0.00 0.00 0.00
                 
Annual Sum or Average 606.97 17.81 589.16 567.78 1073.48 0.00 0.00 0.00
Minimum of Months 363.82 0.00 363.82 253.72 709.74 0.00 0.00 0.00
Maximum of Months 886.88 86.71 800.17 975.15 1423.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 702.81 375.88 326.93 868.50 904.53 0.00 0.00 0.00
February 741.39 339.64 401.75 847.92 825.62 0.00 0.00 0.00
March 900.57 401.25 499.33 1066.71 865.45 0.00 0.00 0.00
April 1151.37 577.43 573.93 1528.01 733.36 0.00 0.00 0.00
May 1086.56 453.45 633.12 1384.49 668.16 0.00 0.00 0.00
June 1079.80 468.51 611.29 1465.00 547.46 0.00 0.00 0.00
July 1223.49 607.99 615.51 1788.53 503.37 0.00 0.00 0.00
August 1208.30 641.81 566.49 1794.03 509.93 0.00 0.00 0.00
September 879.74 403.13 476.61 1239.43 574.31 0.00 0.00 0.00
October 778.73 400.25 378.48 1132.13 618.63 0.00 0.00 0.00
November 709.90 360.66 349.24 870.50 839.19 0.00 0.00 0.00
December 677.23 376.28 300.96 840.14 905.99 0.00 0.00 0.00
                 
Annual Sum or Average 929.57 451.41 478.15 1238.19 707.41 0.00 0.00 0.00
Minimum of Months 677.23 339.64 300.96 840.14 503.37 0.00 0.00 0.00
Maximum of Months 1223.49 641.81 633.12 1794.03 905.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2579.17 1891.94 687.23 3754.25 1470.31 0.00 0.00 0.00
February 2027.09 1248.58 778.51 2764.26 1319.10 0.00 0.00 0.00
March 1616.06 780.64 835.43 2175.53 1390.27 0.00 0.00 0.00
April 1350.26 514.87 835.39 1931.99 1184.82 0.00 0.00 0.00
May 961.49 118.32 843.17 1114.26 1055.21 0.00 0.00 0.00
June 843.48 50.93 792.56 969.79 841.92 0.00 0.00 0.00
July 893.48 100.58 792.90 1202.78 759.54 0.00 0.00 0.00
August 1147.85 362.07 785.78 1792.86 801.39 0.00 0.00 0.00
September 1597.24 809.38 787.86 2503.50 936.55 0.00 0.00 0.00
October 2031.31 1357.99 673.32 3208.53 1011.84 0.00 0.00 0.00
November 2468.85 1742.97 725.88 3568.92 1362.97 0.00 0.00 0.00
December 2755.38 2097.20 658.18 4026.71 1482.97 0.00 0.00 0.00
                 
Annual Sum or Average 1687.89 921.85 766.04 2416.84 1133.81 0.00 0.00 0.00
Minimum of Months 843.48 50.93 658.18 969.79 759.54 0.00 0.00 0.00
Maximum of Months 2755.38 2097.20 843.17 4026.71 1482.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 668.95 337.39 331.56 847.91 980.26 0.00 0.00 0.00
February 798.06 368.42 429.64 953.83 894.63 0.00 0.00 0.00
March 914.79 404.72 510.07 1102.78 928.93 0.00 0.00 0.00
April 1261.09 656.65 604.44 1700.38 803.24 0.00 0.00 0.00
May 1238.78 572.19 666.59 1618.97 721.51 0.00 0.00 0.00
June 1312.36 656.15 656.20 1807.55 587.39 0.00 0.00 0.00
July 1389.23 743.37 645.87 2023.79 543.69 0.00 0.00 0.00
August 1303.37 706.37 597.00 1929.07 559.67 0.00 0.00 0.00
September 1115.93 597.12 518.81 1603.35 621.13 0.00 0.00 0.00
October 853.08 465.74 387.33 1269.03 672.74 0.00 0.00 0.00
November 770.58 403.07 367.51 992.49 909.79 0.00 0.00 0.00
December 680.56 365.02 315.54 878.81 995.88 0.00 0.00 0.00
                 
Annual Sum or Average 1026.45 523.68 502.77 1396.17 767.61 0.00 0.00 0.00
Minimum of Months 668.95 337.39 315.54 847.91 543.69 0.00 0.00 0.00
Maximum of Months 1389.23 743.37 666.59 2023.79 995.88 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209357E+09 0.00 0.209357E+09 97067783.51 0.955009E+09
February 0.237367E+09 0.00 0.237367E+09 0.108197E+09 0.788315E+09
March 0.322040E+09 0.00 0.322040E+09 0.186788E+09 0.886795E+09
April 0.359060E+09 1381952.98 0.357678E+09 0.270265E+09 0.671045E+09
May 0.445857E+09 20761368.39 0.425095E+09 0.367840E+09 0.587157E+09
June 0.459758E+09 44948691.38 0.414809E+09 0.470828E+09 0.448381E+09
July 0.449829E+09 37702800.77 0.412126E+09 0.517532E+09 0.405508E+09
August 0.373568E+09 7480269.97 0.366088E+09 0.411507E+09 0.429262E+09
September 0.305987E+09 47959.78 0.305939E+09 0.307174E+09 0.509519E+09
October 0.250810E+09 0.00 0.250810E+09 0.270929E+09 0.597292E+09
November 0.219765E+09 0.00 0.219765E+09 0.112285E+09 0.848367E+09
December 0.194894E+09 0.00 0.194894E+09 79999694.23 0.982140E+09
           
Annual Sum or Average 0.382829E+10 0.112323E+09 0.371597E+10 0.320041E+10 0.810879E+10
Minimum of Months 0.194894E+09 0.00 0.194894E+09 79999694.23 0.405508E+09
Maximum of Months 0.459758E+09 44948691.38 0.425095E+09 0.517532E+09 0.982140E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209354E+09 0.00 0.209354E+09 97066060.89 0.955007E+09
February 0.237363E+09 0.00 0.237363E+09 0.108194E+09 0.788314E+09
March 0.322035E+09 0.00 0.322035E+09 0.186783E+09 0.886795E+09
April 0.359055E+09 1381922.60 0.357673E+09 0.270261E+09 0.671045E+09
May 0.445851E+09 20760911.98 0.425090E+09 0.367832E+09 0.587156E+09
June 0.459751E+09 44947703.23 0.414804E+09 0.470819E+09 0.448381E+09
July 0.449823E+09 37701971.92 0.412122E+09 0.517525E+09 0.405507E+09
August 0.373564E+09 7480105.53 0.366084E+09 0.411502E+09 0.429261E+09
September 0.305984E+09 47958.73 0.305936E+09 0.307170E+09 0.509517E+09
October 0.250807E+09 0.00 0.250807E+09 0.270926E+09 0.597289E+09
November 0.219762E+09 0.00 0.219762E+09 0.112282E+09 0.848365E+09
December 0.194891E+09 0.00 0.194891E+09 79998150.82 0.982138E+09
           
Annual Sum or Average 0.382824E+10 0.112321E+09 0.371592E+10 0.320036E+10 0.810878E+10
Minimum of Months 0.194891E+09 0.00 0.194891E+09 79998150.82 0.405507E+09
Maximum of Months 0.459751E+09 44947703.23 0.425090E+09 0.517525E+09 0.982138E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209355E+09 0.00 0.209355E+09 97066370.15 0.955008E+09
February 0.237365E+09 0.00 0.237365E+09 0.108195E+09 0.788315E+09
March 0.322037E+09 0.00 0.322037E+09 0.186785E+09 0.886795E+09
April 0.359057E+09 1381932.73 0.357675E+09 0.270263E+09 0.671045E+09
May 0.445853E+09 20761064.12 0.425092E+09 0.367835E+09 0.587156E+09
June 0.459754E+09 44948032.62 0.414806E+09 0.470822E+09 0.448381E+09
July 0.449825E+09 37702248.20 0.412123E+09 0.517527E+09 0.405507E+09
August 0.373565E+09 7480160.34 0.366085E+09 0.411504E+09 0.429261E+09
September 0.305985E+09 47959.08 0.305937E+09 0.307171E+09 0.509518E+09
October 0.250808E+09 0.00 0.250808E+09 0.270927E+09 0.597290E+09
November 0.219763E+09 0.00 0.219763E+09 0.112283E+09 0.848366E+09
December 0.194892E+09 0.00 0.194892E+09 79998665.33 0.982139E+09
           
Annual Sum or Average 0.382826E+10 0.112321E+09 0.371594E+10 0.320038E+10 0.810878E+10
Minimum of Months 0.194892E+09 0.00 0.194892E+09 79998665.33 0.405507E+09
Maximum of Months 0.459754E+09 44948032.62 0.425092E+09 0.517527E+09 0.982139E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209354E+09 0.00 0.209354E+09 97066060.89 0.955007E+09
February 0.237363E+09 0.00 0.237363E+09 0.108194E+09 0.788314E+09
March 0.322035E+09 0.00 0.322035E+09 0.186783E+09 0.886795E+09
April 0.359055E+09 1381922.60 0.357673E+09 0.270261E+09 0.671045E+09
May 0.445851E+09 20760911.98 0.425090E+09 0.367832E+09 0.587156E+09
June 0.459751E+09 44947703.23 0.414804E+09 0.470819E+09 0.448381E+09
July 0.449823E+09 37701971.92 0.412122E+09 0.517525E+09 0.405507E+09
August 0.373564E+09 7480105.53 0.366084E+09 0.411502E+09 0.429261E+09
September 0.305984E+09 47958.73 0.305936E+09 0.307170E+09 0.509517E+09
October 0.250807E+09 0.00 0.250807E+09 0.270926E+09 0.597289E+09
November 0.219762E+09 0.00 0.219762E+09 0.112282E+09 0.848365E+09
December 0.194891E+09 0.00 0.194891E+09 79998150.82 0.982138E+09
           
Annual Sum or Average 0.382824E+10 0.112321E+09 0.371592E+10 0.320036E+10 0.810878E+10
Minimum of Months 0.194891E+09 0.00 0.194891E+09 79998150.82 0.405507E+09
Maximum of Months 0.459751E+09 44947703.23 0.425090E+09 0.517525E+09 0.982138E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.209346E+09 0.00 0.209346E+09 97062502.05 0.954969E+09
February 0.237354E+09 0.00 0.237354E+09 0.108190E+09 0.788283E+09
March 0.322023E+09 0.00 0.322023E+09 0.186777E+09 0.886759E+09
April 0.359042E+09 1381871.97 0.357660E+09 0.270251E+09 0.671018E+09
May 0.445834E+09 20760151.29 0.425073E+09 0.367818E+09 0.587133E+09
June 0.459734E+09 44946056.33 0.414788E+09 0.470801E+09 0.448363E+09
July 0.449806E+09 37700590.50 0.412106E+09 0.517505E+09 0.405491E+09
August 0.373550E+09 7479831.45 0.366070E+09 0.411486E+09 0.429244E+09
September 0.305972E+09 47956.97 0.305924E+09 0.307158E+09 0.509497E+09
October 0.250797E+09 0.00 0.250797E+09 0.270915E+09 0.597266E+09
November 0.219753E+09 0.00 0.219753E+09 0.112278E+09 0.848331E+09
December 0.194884E+09 0.00 0.194884E+09 79995183.80 0.982099E+09
           
Annual Sum or Average 0.382810E+10 0.112316E+09 0.371578E+10 0.320024E+10 0.810845E+10
Minimum of Months 0.194884E+09 0.00 0.194884E+09 79995183.80 0.405491E+09
Maximum of Months 0.459734E+09 44946056.33 0.425073E+09 0.517505E+09 0.982099E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.627473E+09 0.335587E+09 0.291886E+09 0.716276E+09 0.969122E+09
February 0.597862E+09 0.273886E+09 0.323977E+09 0.641349E+09 0.798251E+09
March 0.804038E+09 0.358236E+09 0.445802E+09 0.910655E+09 0.891465E+09
April 0.994793E+09 0.498909E+09 0.495884E+09 0.131264E+10 0.687274E+09
May 0.970094E+09 0.404843E+09 0.565251E+09 0.122434E+10 0.651001E+09
June 0.932955E+09 0.404793E+09 0.528162E+09 0.127264E+10 0.499677E+09
July 0.109235E+10 0.542816E+09 0.549530E+09 0.162024E+10 0.446688E+09
August 0.107878E+10 0.573012E+09 0.505768E+09 0.162258E+10 0.451989E+09
September 0.760101E+09 0.348307E+09 0.411794E+09 0.107054E+10 0.537402E+09
October 0.695256E+09 0.357344E+09 0.337912E+09 0.997694E+09 0.610944E+09
November 0.613362E+09 0.311613E+09 0.301749E+09 0.705808E+09 0.851461E+09
December 0.604640E+09 0.335945E+09 0.268696E+09 0.689594E+09 0.966628E+09
           
Annual Sum or Average 0.977170E+10 0.474529E+10 0.502641E+10 0.127843E+11 0.836190E+10
Minimum of Months 0.597862E+09 0.273886E+09 0.268696E+09 0.641349E+09 0.446688E+09
Maximum of Months 0.109235E+10 0.573012E+09 0.565251E+09 0.162258E+10 0.969122E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.627473E+09 0.335587E+09 0.291886E+09 0.716276E+09 0.969122E+09
February 0.597862E+09 0.273886E+09 0.323977E+09 0.641349E+09 0.798251E+09
March 0.804038E+09 0.358236E+09 0.445802E+09 0.910655E+09 0.891465E+09
April 0.994793E+09 0.498909E+09 0.495884E+09 0.131264E+10 0.687274E+09
May 0.970094E+09 0.404843E+09 0.565251E+09 0.122434E+10 0.651001E+09
June 0.932955E+09 0.404793E+09 0.528162E+09 0.127264E+10 0.499677E+09
July 0.109235E+10 0.542816E+09 0.549530E+09 0.162024E+10 0.446688E+09
August 0.107878E+10 0.573012E+09 0.505768E+09 0.162258E+10 0.451989E+09
September 0.760101E+09 0.348307E+09 0.411794E+09 0.107054E+10 0.537402E+09
October 0.695256E+09 0.357344E+09 0.337912E+09 0.997694E+09 0.610944E+09
November 0.613362E+09 0.311613E+09 0.301749E+09 0.705808E+09 0.851461E+09
December 0.604640E+09 0.335945E+09 0.268696E+09 0.689594E+09 0.966628E+09
           
Annual Sum or Average 0.977170E+10 0.474529E+10 0.502641E+10 0.127843E+11 0.836190E+10
Minimum of Months 0.597862E+09 0.273886E+09 0.268696E+09 0.641349E+09 0.446688E+09
Maximum of Months 0.109235E+10 0.573012E+09 0.565251E+09 0.162258E+10 0.969122E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.627461E+09 0.335581E+09 0.291880E+09 0.716263E+09 0.969104E+09
February 0.597852E+09 0.273881E+09 0.323971E+09 0.641338E+09 0.798236E+09
March 0.804023E+09 0.358229E+09 0.445794E+09 0.910638E+09 0.891448E+09
April 0.994775E+09 0.498900E+09 0.495875E+09 0.131262E+10 0.687261E+09
May 0.970077E+09 0.404836E+09 0.565241E+09 0.122431E+10 0.650989E+09
June 0.932938E+09 0.404785E+09 0.528152E+09 0.127261E+10 0.499668E+09
July 0.109233E+10 0.542806E+09 0.549520E+09 0.162021E+10 0.446680E+09
August 0.107876E+10 0.573001E+09 0.505759E+09 0.162255E+10 0.451981E+09
September 0.760087E+09 0.348301E+09 0.411786E+09 0.107052E+10 0.537392E+09
October 0.695243E+09 0.357337E+09 0.337906E+09 0.997675E+09 0.610933E+09
November 0.613351E+09 0.311608E+09 0.301743E+09 0.705795E+09 0.851445E+09
December 0.604629E+09 0.335938E+09 0.268691E+09 0.689581E+09 0.966610E+09
           
Annual Sum or Average 0.977152E+10 0.474520E+10 0.502632E+10 0.127841E+11 0.836175E+10
Minimum of Months 0.597852E+09 0.273881E+09 0.268691E+09 0.641338E+09 0.446680E+09
Maximum of Months 0.109233E+10 0.573001E+09 0.565241E+09 0.162255E+10 0.969104E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138158E+10 0.101345E+10 0.368131E+09 0.199508E+10 0.878492E+09
February 0.980770E+09 0.604101E+09 0.376669E+09 0.132470E+10 0.730237E+09
March 0.865679E+09 0.418162E+09 0.447517E+09 0.114458E+10 0.846045E+09
April 0.699966E+09 0.266902E+09 0.433064E+09 0.993056E+09 0.678462E+09
May 0.515046E+09 63382741.22 0.451663E+09 0.583991E+09 0.623775E+09
June 0.437258E+09 26399694.62 0.410858E+09 0.495747E+09 0.475363E+09
July 0.478615E+09 53877696.07 0.424738E+09 0.643866E+09 0.426810E+09
August 0.614875E+09 0.193949E+09 0.420926E+09 0.964732E+09 0.448597E+09
September 0.827995E+09 0.419571E+09 0.408424E+09 0.130764E+10 0.516966E+09
October 0.108811E+10 0.727433E+09 0.360682E+09 0.172306E+10 0.582943E+09
November 0.127983E+10 0.903539E+09 0.376292E+09 0.184150E+10 0.787747E+09
December 0.147597E+10 0.112341E+10 0.352567E+09 0.214011E+10 0.894013E+09
           
Annual Sum or Average 0.106457E+11 0.581418E+10 0.483153E+10 0.151581E+11 0.788945E+10
Minimum of Months 0.437258E+09 26399694.62 0.352567E+09 0.495747E+09 0.426810E+09
Maximum of Months 0.147597E+10 0.112341E+10 0.451663E+09 0.214011E+10 0.894013E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138158E+10 0.101345E+10 0.368129E+09 0.199506E+10 0.878491E+09
February 0.980763E+09 0.604097E+09 0.376667E+09 0.132469E+10 0.730236E+09
March 0.865673E+09 0.418159E+09 0.447515E+09 0.114457E+10 0.846044E+09
April 0.699962E+09 0.266900E+09 0.433063E+09 0.993049E+09 0.678462E+09
May 0.515043E+09 63382276.75 0.451661E+09 0.583987E+09 0.623774E+09
June 0.437256E+09 26399501.16 0.410856E+09 0.495744E+09 0.475363E+09
July 0.478613E+09 53877301.25 0.424736E+09 0.643863E+09 0.426810E+09
August 0.614872E+09 0.193947E+09 0.420924E+09 0.964726E+09 0.448597E+09
September 0.827990E+09 0.419568E+09 0.408422E+09 0.130763E+10 0.516966E+09
October 0.108811E+10 0.727427E+09 0.360680E+09 0.172305E+10 0.582942E+09
November 0.127982E+10 0.903532E+09 0.376290E+09 0.184148E+10 0.787746E+09
December 0.147596E+10 0.112340E+10 0.352566E+09 0.214010E+10 0.894012E+09
           
Annual Sum or Average 0.106456E+11 0.581413E+10 0.483151E+10 0.151579E+11 0.788944E+10
Minimum of Months 0.437256E+09 26399501.16 0.352566E+09 0.495744E+09 0.426810E+09
Maximum of Months 0.147596E+10 0.112340E+10 0.451661E+09 0.214010E+10 0.894012E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138158E+10 0.101345E+10 0.368131E+09 0.199508E+10 0.878492E+09
February 0.980770E+09 0.604101E+09 0.376669E+09 0.132470E+10 0.730237E+09
March 0.865679E+09 0.418162E+09 0.447517E+09 0.114458E+10 0.846045E+09
April 0.699966E+09 0.266902E+09 0.433064E+09 0.993056E+09 0.678462E+09
May 0.515046E+09 63382741.22 0.451663E+09 0.583991E+09 0.623775E+09
June 0.437258E+09 26399694.62 0.410858E+09 0.495747E+09 0.475363E+09
July 0.478615E+09 53877696.07 0.424738E+09 0.643866E+09 0.426810E+09
August 0.614875E+09 0.193949E+09 0.420926E+09 0.964732E+09 0.448597E+09
September 0.827995E+09 0.419571E+09 0.408424E+09 0.130764E+10 0.516966E+09
October 0.108811E+10 0.727433E+09 0.360682E+09 0.172306E+10 0.582943E+09
November 0.127983E+10 0.903539E+09 0.376292E+09 0.184150E+10 0.787747E+09
December 0.147597E+10 0.112341E+10 0.352567E+09 0.214011E+10 0.894013E+09
           
Annual Sum or Average 0.106457E+11 0.581418E+10 0.483153E+10 0.151581E+11 0.788945E+10
Minimum of Months 0.437258E+09 26399694.62 0.352567E+09 0.495747E+09 0.426810E+09
Maximum of Months 0.147597E+10 0.112341E+10 0.451663E+09 0.214011E+10 0.894013E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138158E+10 0.101345E+10 0.368129E+09 0.199506E+10 0.878491E+09
February 0.980763E+09 0.604097E+09 0.376667E+09 0.132469E+10 0.730236E+09
March 0.865673E+09 0.418159E+09 0.447515E+09 0.114457E+10 0.846044E+09
April 0.699962E+09 0.266900E+09 0.433063E+09 0.993049E+09 0.678462E+09
May 0.515043E+09 63382276.75 0.451661E+09 0.583987E+09 0.623774E+09
June 0.437256E+09 26399501.16 0.410856E+09 0.495744E+09 0.475363E+09
July 0.478613E+09 53877301.25 0.424736E+09 0.643863E+09 0.426810E+09
August 0.614872E+09 0.193947E+09 0.420924E+09 0.964726E+09 0.448597E+09
September 0.827990E+09 0.419568E+09 0.408422E+09 0.130763E+10 0.516966E+09
October 0.108811E+10 0.727427E+09 0.360680E+09 0.172305E+10 0.582942E+09
November 0.127982E+10 0.903532E+09 0.376290E+09 0.184148E+10 0.787746E+09
December 0.147596E+10 0.112340E+10 0.352566E+09 0.214010E+10 0.894012E+09
           
Annual Sum or Average 0.106456E+11 0.581413E+10 0.483151E+10 0.151579E+11 0.788944E+10
Minimum of Months 0.437256E+09 26399501.16 0.352566E+09 0.495744E+09 0.426810E+09
Maximum of Months 0.147596E+10 0.112340E+10 0.451661E+09 0.214010E+10 0.894012E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138152E+10 0.101341E+10 0.368115E+09 0.199499E+10 0.878456E+09
February 0.980727E+09 0.604074E+09 0.376653E+09 0.132464E+10 0.730207E+09
March 0.865641E+09 0.418143E+09 0.447498E+09 0.114453E+10 0.846010E+09
April 0.699936E+09 0.266890E+09 0.433046E+09 0.993013E+09 0.678434E+09
May 0.515024E+09 63379954.39 0.451644E+09 0.583965E+09 0.623749E+09
June 0.437239E+09 26398533.87 0.410841E+09 0.495726E+09 0.475344E+09
July 0.478595E+09 53875327.16 0.424720E+09 0.643839E+09 0.426793E+09
August 0.614849E+09 0.193940E+09 0.420908E+09 0.964690E+09 0.448579E+09
September 0.827959E+09 0.419553E+09 0.408406E+09 0.130758E+10 0.516945E+09
October 0.108807E+10 0.727401E+09 0.360666E+09 0.172298E+10 0.582919E+09
November 0.127977E+10 0.903499E+09 0.376276E+09 0.184142E+10 0.787715E+09
December 0.147591E+10 0.112336E+10 0.352552E+09 0.214002E+10 0.893977E+09
           
Annual Sum or Average 0.106452E+11 0.581392E+10 0.483132E+10 0.151574E+11 0.788913E+10
Minimum of Months 0.437239E+09 26398533.87 0.352552E+09 0.495726E+09 0.426793E+09
Maximum of Months 0.147591E+10 0.112336E+10 0.451644E+09 0.214002E+10 0.893977E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.597244E+09 0.301223E+09 0.296021E+09 0.704301E+09 0.108681E+10
February 0.643562E+09 0.297098E+09 0.346464E+09 0.716365E+09 0.930923E+09
March 0.816733E+09 0.361335E+09 0.455397E+09 0.918190E+09 0.106471E+10
April 0.108959E+10 0.567348E+09 0.522243E+09 0.142264E+10 0.852209E+09
May 0.110600E+10 0.510859E+09 0.595139E+09 0.142558E+10 0.736751E+09
June 0.113389E+10 0.566922E+09 0.566965E+09 0.154959E+10 0.587193E+09
July 0.124032E+10 0.663685E+09 0.576636E+09 0.179481E+10 0.542622E+09
August 0.116366E+10 0.630657E+09 0.533006E+09 0.170180E+10 0.577436E+09
September 0.964171E+09 0.515914E+09 0.448257E+09 0.137751E+10 0.612342E+09
October 0.761634E+09 0.415819E+09 0.345814E+09 0.109860E+10 0.729375E+09
November 0.665790E+09 0.348255E+09 0.317535E+09 0.798043E+09 0.102139E+10
December 0.607608E+09 0.325892E+09 0.281715E+09 0.709640E+09 0.119841E+10
           
Annual Sum or Average 0.107902E+11 0.550501E+10 0.528519E+10 0.142171E+11 0.994017E+10
Minimum of Months 0.597244E+09 0.297098E+09 0.281715E+09 0.704301E+09 0.542622E+09
Maximum of Months 0.124032E+10 0.663685E+09 0.595139E+09 0.179481E+10 0.119841E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.597244E+09 0.301223E+09 0.296021E+09 0.704301E+09 0.108681E+10
February 0.643562E+09 0.297098E+09 0.346464E+09 0.716365E+09 0.930923E+09
March 0.816733E+09 0.361335E+09 0.455397E+09 0.918190E+09 0.106471E+10
April 0.108959E+10 0.567348E+09 0.522243E+09 0.142264E+10 0.852209E+09
May 0.110600E+10 0.510859E+09 0.595139E+09 0.142558E+10 0.736751E+09
June 0.113389E+10 0.566922E+09 0.566965E+09 0.154959E+10 0.587193E+09
July 0.124032E+10 0.663685E+09 0.576636E+09 0.179481E+10 0.542622E+09
August 0.116366E+10 0.630657E+09 0.533006E+09 0.170180E+10 0.577436E+09
September 0.964171E+09 0.515914E+09 0.448257E+09 0.137751E+10 0.612342E+09
October 0.761634E+09 0.415819E+09 0.345814E+09 0.109860E+10 0.729375E+09
November 0.665790E+09 0.348255E+09 0.317535E+09 0.798043E+09 0.102139E+10
December 0.607608E+09 0.325892E+09 0.281715E+09 0.709640E+09 0.119841E+10
           
Annual Sum or Average 0.107902E+11 0.550501E+10 0.528519E+10 0.142171E+11 0.994017E+10
Minimum of Months 0.597244E+09 0.297098E+09 0.281715E+09 0.704301E+09 0.542622E+09
Maximum of Months 0.124032E+10 0.663685E+09 0.595139E+09 0.179481E+10 0.119841E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.597233E+09 0.301218E+09 0.296016E+09 0.704288E+09 0.108679E+10
February 0.643550E+09 0.297093E+09 0.346457E+09 0.716351E+09 0.930906E+09
March 0.816718E+09 0.361329E+09 0.455389E+09 0.918174E+09 0.106469E+10
April 0.108957E+10 0.567338E+09 0.522233E+09 0.142261E+10 0.852193E+09
May 0.110598E+10 0.510849E+09 0.595129E+09 0.142555E+10 0.736738E+09
June 0.113387E+10 0.566912E+09 0.566955E+09 0.154956E+10 0.587182E+09
July 0.124030E+10 0.663673E+09 0.576625E+09 0.179478E+10 0.542612E+09
August 0.116364E+10 0.630646E+09 0.532996E+09 0.170177E+10 0.577426E+09
September 0.964154E+09 0.515905E+09 0.448249E+09 0.137748E+10 0.612330E+09
October 0.761620E+09 0.415812E+09 0.345808E+09 0.109858E+10 0.729362E+09
November 0.665778E+09 0.348249E+09 0.317529E+09 0.798028E+09 0.102137E+10
December 0.607596E+09 0.325886E+09 0.281710E+09 0.709627E+09 0.119839E+10
           
Annual Sum or Average 0.107900E+11 0.550491E+10 0.528510E+10 0.142168E+11 0.993999E+10
Minimum of Months 0.597233E+09 0.297093E+09 0.281710E+09 0.704288E+09 0.542612E+09
Maximum of Months 0.124030E+10 0.663673E+09 0.595129E+09 0.179478E+10 0.119839E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.104678E+10 0.00 0.104678E+10 0.596445E+09 0.429034E+10
February 0.118683E+10 0.00 0.118683E+10 0.641858E+09 0.352118E+10
March 0.161020E+10 0.00 0.161020E+10 0.105329E+10 0.399445E+10
April 0.179529E+10 6909808.95 0.178838E+10 0.145736E+10 0.307147E+10
May 0.222928E+10 0.103808E+09 0.212547E+10 0.191239E+10 0.277444E+10
June 0.229879E+10 0.224745E+09 0.207404E+10 0.238897E+10 0.212846E+10
July 0.224914E+10 0.188515E+09 0.206063E+10 0.263276E+10 0.195800E+10
August 0.186784E+10 37401588.21 0.183043E+10 0.211666E+10 0.205022E+10
September 0.152993E+10 239800.43 0.152969E+10 0.157794E+10 0.239598E+10
October 0.125405E+10 0.00 0.125405E+10 0.142985E+10 0.275168E+10
November 0.109882E+10 0.00 0.109882E+10 0.669811E+09 0.380900E+10
December 0.974467E+09 0.00 0.974467E+09 0.539762E+09 0.432451E+10
           
Annual Sum or Average 0.191414E+11 0.561619E+09 0.185798E+11 0.170171E+11 0.370697E+11
Minimum of Months 0.974467E+09 0.00 0.974467E+09 0.539762E+09 0.195800E+10
Maximum of Months 0.229879E+10 0.224745E+09 0.212547E+10 0.263276E+10 0.432451E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.188240E+10 0.100675E+10 0.875648E+09 0.221562E+10 0.267886E+10
February 0.179357E+10 0.821648E+09 0.971921E+09 0.197134E+10 0.220887E+10
March 0.241209E+10 0.107470E+10 0.133739E+10 0.277514E+10 0.250485E+10
April 0.298435E+10 0.149671E+10 0.148764E+10 0.393203E+10 0.199857E+10
May 0.291025E+10 0.121452E+10 0.169574E+10 0.367418E+10 0.187964E+10
June 0.279884E+10 0.121437E+10 0.158447E+10 0.380252E+10 0.145932E+10
July 0.327700E+10 0.162843E+10 0.164857E+10 0.481989E+10 0.136234E+10
August 0.323631E+10 0.171902E+10 0.151729E+10 0.482835E+10 0.138770E+10
September 0.228028E+10 0.104491E+10 0.123537E+10 0.320909E+10 0.155085E+10
October 0.208575E+10 0.107202E+10 0.101373E+10 0.300255E+10 0.175099E+10
November 0.184007E+10 0.934830E+09 0.905237E+09 0.216686E+10 0.238454E+10
December 0.181390E+10 0.100782E+10 0.806080E+09 0.213981E+10 0.267986E+10
           
Annual Sum or Average 0.293148E+11 0.142357E+11 0.150791E+11 0.385374E+11 0.238464E+11
Minimum of Months 0.179357E+10 0.821648E+09 0.806080E+09 0.197134E+10 0.136234E+10
Maximum of Months 0.327700E+10 0.171902E+10 0.169574E+10 0.482835E+10 0.267986E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.690805E+10 0.506738E+10 0.184068E+10 0.992988E+10 0.431121E+10
February 0.490394E+10 0.302057E+10 0.188337E+10 0.658434E+10 0.352271E+10
March 0.432847E+10 0.209085E+10 0.223761E+10 0.571964E+10 0.405077E+10
April 0.349988E+10 0.133454E+10 0.216534E+10 0.496536E+10 0.326249E+10
May 0.257525E+10 0.316920E+09 0.225833E+10 0.292547E+10 0.301860E+10
June 0.218631E+10 0.132001E+09 0.205430E+10 0.250007E+10 0.228193E+10
July 0.239309E+10 0.269394E+09 0.212370E+10 0.324112E+10 0.208703E+10
August 0.307441E+10 0.969765E+09 0.210464E+10 0.482417E+10 0.220873E+10
September 0.414004E+10 0.209790E+10 0.204214E+10 0.649230E+10 0.253905E+10
October 0.544067E+10 0.363724E+10 0.180343E+10 0.856328E+10 0.285947E+10
November 0.639927E+10 0.451779E+10 0.188148E+10 0.915803E+10 0.383107E+10
December 0.738001E+10 0.561715E+10 0.176286E+10 0.106634E+11 0.432823E+10
           
Annual Sum or Average 0.532294E+11 0.290715E+11 0.241579E+11 0.755670E+11 0.383013E+11
Minimum of Months 0.218631E+10 0.132001E+09 0.176286E+10 0.250007E+10 0.208703E+10
Maximum of Months 0.738001E+10 0.561715E+10 0.225833E+10 0.106634E+11 0.432823E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179171E+10 0.903660E+09 0.888054E+09 0.220777E+10 0.288153E+10
February 0.193067E+10 0.891285E+09 0.103938E+10 0.225417E+10 0.237450E+10
March 0.245017E+10 0.108400E+10 0.136618E+10 0.289812E+10 0.268766E+10
April 0.326874E+10 0.170203E+10 0.156671E+10 0.438978E+10 0.219761E+10
May 0.331796E+10 0.153256E+10 0.178540E+10 0.431633E+10 0.203896E+10
June 0.340163E+10 0.170075E+10 0.170088E+10 0.469671E+10 0.157758E+10
July 0.372092E+10 0.199103E+10 0.172989E+10 0.545187E+10 0.148570E+10
August 0.349095E+10 0.189195E+10 0.159900E+10 0.519177E+10 0.153704E+10
September 0.289248E+10 0.154773E+10 0.134476E+10 0.415646E+10 0.168191E+10
October 0.228488E+10 0.124745E+10 0.103743E+10 0.337816E+10 0.190927E+10
November 0.199735E+10 0.104475E+10 0.952595E+09 0.251973E+10 0.256974E+10
December 0.182280E+10 0.977667E+09 0.845137E+09 0.229212E+10 0.292616E+10
           
Annual Sum or Average 0.323703E+11 0.165149E+11 0.158554E+11 0.437530E+11 0.258677E+11
Minimum of Months 0.179171E+10 0.891285E+09 0.845137E+09 0.220777E+10 0.148570E+10
Maximum of Months 0.372092E+10 0.199103E+10 0.178540E+10 0.545187E+10 0.292616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.104678E+10 0.00 0.104678E+10 0.735419E+09 0.379041E+10
February 0.118683E+10 0.00 0.118683E+10 0.766900E+09 0.310583E+10
March 0.161020E+10 0.00 0.161020E+10 0.118397E+10 0.361175E+10
April 0.179529E+10 6909808.95 0.178838E+10 0.152795E+10 0.285013E+10
May 0.222928E+10 0.103808E+09 0.212547E+10 0.199744E+10 0.259207E+10
June 0.229879E+10 0.224745E+09 0.207404E+10 0.240050E+10 0.203321E+10
July 0.224914E+10 0.188515E+09 0.206063E+10 0.261183E+10 0.190096E+10
August 0.186784E+10 37401588.21 0.183043E+10 0.210863E+10 0.197424E+10
September 0.152993E+10 239800.43 0.152969E+10 0.160583E+10 0.225128E+10
October 0.125405E+10 0.00 0.125405E+10 0.149001E+10 0.254217E+10
November 0.109882E+10 0.00 0.109882E+10 0.797410E+09 0.338764E+10
December 0.974467E+09 0.00 0.974467E+09 0.679569E+09 0.381354E+10
           
Annual Sum or Average 0.191414E+11 0.561619E+09 0.185798E+11 0.179054E+11 0.338532E+11
Minimum of Months 0.974467E+09 0.00 0.974467E+09 0.679569E+09 0.190096E+10
Maximum of Months 0.229879E+10 0.224745E+09 0.212547E+10 0.261183E+10 0.381354E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.188240E+10 0.100675E+10 0.875648E+09 0.232620E+10 0.242269E+10
February 0.179357E+10 0.821648E+09 0.971921E+09 0.205128E+10 0.199734E+10
March 0.241209E+10 0.107470E+10 0.133739E+10 0.285707E+10 0.231801E+10
April 0.298435E+10 0.149671E+10 0.148764E+10 0.396060E+10 0.190087E+10
May 0.291025E+10 0.121452E+10 0.169574E+10 0.370823E+10 0.178961E+10
June 0.279884E+10 0.121437E+10 0.158447E+10 0.379729E+10 0.141901E+10
July 0.327700E+10 0.162843E+10 0.164857E+10 0.479039E+10 0.134822E+10
August 0.323631E+10 0.171902E+10 0.151729E+10 0.480514E+10 0.136578E+10
September 0.228028E+10 0.104491E+10 0.123537E+10 0.321261E+10 0.148861E+10
October 0.208575E+10 0.107202E+10 0.101373E+10 0.303230E+10 0.165693E+10
November 0.184007E+10 0.934830E+09 0.905237E+09 0.225634E+10 0.217519E+10
December 0.181390E+10 0.100782E+10 0.806080E+09 0.225023E+10 0.242660E+10
           
Annual Sum or Average 0.293148E+11 0.142357E+11 0.150791E+11 0.390477E+11 0.223089E+11
Minimum of Months 0.179357E+10 0.821648E+09 0.806080E+09 0.205128E+10 0.134822E+10
Maximum of Months 0.327700E+10 0.171902E+10 0.169574E+10 0.480514E+10 0.242660E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.690805E+10 0.506738E+10 0.184068E+10 0.100554E+11 0.393808E+10
February 0.490394E+10 0.302057E+10 0.188337E+10 0.668729E+10 0.319118E+10
March 0.432847E+10 0.209085E+10 0.223761E+10 0.582695E+10 0.372371E+10
April 0.349988E+10 0.133454E+10 0.216534E+10 0.500771E+10 0.307104E+10
May 0.257525E+10 0.316920E+09 0.225833E+10 0.298445E+10 0.282629E+10
June 0.218631E+10 0.132001E+09 0.205430E+10 0.251369E+10 0.218226E+10
July 0.239309E+10 0.269394E+09 0.212370E+10 0.322153E+10 0.203435E+10
August 0.307441E+10 0.969765E+09 0.210464E+10 0.480198E+10 0.214644E+10
September 0.414004E+10 0.209790E+10 0.204214E+10 0.648907E+10 0.242753E+10
October 0.544067E+10 0.363724E+10 0.180343E+10 0.859372E+10 0.271012E+10
November 0.639927E+10 0.451779E+10 0.188148E+10 0.925064E+10 0.353281E+10
December 0.738001E+10 0.561715E+10 0.176286E+10 0.107851E+11 0.397199E+10
           
Annual Sum or Average 0.532294E+11 0.290715E+11 0.241579E+11 0.762175E+11 0.357558E+11
Minimum of Months 0.218631E+10 0.132001E+09 0.176286E+10 0.251369E+10 0.203435E+10
Maximum of Months 0.738001E+10 0.561715E+10 0.225833E+10 0.107851E+11 0.397199E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.179171E+10 0.903660E+09 0.888054E+09 0.227105E+10 0.262553E+10
February 0.193067E+10 0.891285E+09 0.103938E+10 0.230751E+10 0.216430E+10
March 0.245017E+10 0.108400E+10 0.136618E+10 0.295370E+10 0.248804E+10
April 0.326874E+10 0.170203E+10 0.156671E+10 0.440737E+10 0.208199E+10
May 0.331796E+10 0.153256E+10 0.178540E+10 0.433624E+10 0.193250E+10
June 0.340163E+10 0.170075E+10 0.170088E+10 0.468517E+10 0.152252E+10
July 0.372092E+10 0.199103E+10 0.172989E+10 0.542052E+10 0.145621E+10
August 0.349095E+10 0.189195E+10 0.159900E+10 0.516683E+10 0.149901E+10
September 0.289248E+10 0.154773E+10 0.134476E+10 0.415588E+10 0.160997E+10
October 0.228488E+10 0.124745E+10 0.103743E+10 0.339896E+10 0.180186E+10
November 0.199735E+10 0.104475E+10 0.952595E+09 0.257253E+10 0.235819E+10
December 0.182280E+10 0.977667E+09 0.845137E+09 0.235382E+10 0.266737E+10
           
Annual Sum or Average 0.323703E+11 0.165149E+11 0.158554E+11 0.440296E+11 0.242075E+11
Minimum of Months 0.179171E+10 0.891285E+09 0.845137E+09 0.227105E+10 0.145621E+10
Maximum of Months 0.372092E+10 0.199103E+10 0.178540E+10 0.542052E+10 0.266737E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 181.20 1782.78 390.82 0.00 390.82 0.00 0.00
February 223.62 1629.27 490.58 0.00 490.58 0.00 0.00
March 348.68 1655.44 601.17 0.00 601.17 0.00 0.00
April 521.34 1294.44 692.62 2.67 689.95 0.00 0.00
May 686.66 1096.09 832.30 38.76 793.55 0.00 0.00
June 908.21 864.93 886.86 86.70 800.16 0.00 0.00
July 966.10 756.99 839.72 70.38 769.34 0.00 0.00
August 768.18 801.33 697.36 13.96 683.40 0.00 0.00
September 592.53 982.86 590.24 0.09 590.15 0.00 0.00
October 505.76 1115.00 468.20 0.00 468.20 0.00 0.00
November 216.59 1636.49 423.92 0.00 423.92 0.00 0.00
December 149.34 1833.43 363.82 0.00 363.82 0.00 0.00
               
Annual Sum or Average 507.41 1285.63 606.96 17.81 589.15 0.00 0.00
Minimum of Months 149.34 756.99 363.82 0.00 363.82 0.00 0.00
Maximum of Months 966.10 1833.43 886.86 86.70 800.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 802.28 1085.48 702.81 375.88 326.93 0.00 0.00
February 795.32 989.89 741.39 339.64 401.75 0.00 0.00
March 1019.99 998.50 900.57 401.25 499.33 0.00 0.00
April 1519.25 795.45 1151.37 577.44 573.94 0.00 0.00
May 1371.34 729.16 1086.57 453.45 633.12 0.00 0.00
June 1472.95 578.33 1079.80 468.51 611.29 0.00 0.00
July 1814.77 500.32 1223.50 607.99 615.51 0.00 0.00
August 1817.39 506.26 1208.30 641.81 566.49 0.00 0.00
September 1239.04 621.99 879.74 403.13 476.61 0.00 0.00
October 1117.48 684.30 778.73 400.25 378.48 0.00 0.00
November 816.90 985.48 709.91 360.66 349.24 0.00 0.00
December 772.39 1082.69 677.24 376.28 300.96 0.00 0.00
               
Annual Sum or Average 1216.16 795.46 929.57 451.41 478.16 0.00 0.00
Minimum of Months 772.39 500.32 677.24 339.64 300.96 0.00 0.00
Maximum of Months 1817.39 1085.48 1223.50 641.81 633.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3724.34 1639.94 2579.09 1891.88 687.21 0.00 0.00
February 2737.85 1509.24 2027.03 1248.54 778.49 0.00 0.00
March 2136.66 1579.37 1616.02 780.61 835.41 0.00 0.00
April 1915.60 1308.75 1350.23 514.85 835.38 0.00 0.00
May 1090.17 1164.44 961.47 118.32 843.15 0.00 0.00
June 956.29 916.97 843.47 50.92 792.54 0.00 0.00
July 1201.95 796.76 893.46 100.58 792.89 0.00 0.00
August 1800.93 837.43 1147.83 362.06 785.77 0.00 0.00
September 2522.42 997.23 1597.19 809.35 787.85 0.00 0.00
October 3216.54 1088.22 2031.25 1357.95 673.31 0.00 0.00
November 3552.23 1519.56 2468.78 1742.92 725.86 0.00 0.00
December 3995.09 1668.92 2755.30 2097.14 658.16 0.00 0.00
               
Annual Sum or Average 2403.27 1250.85 1687.85 921.82 766.03 0.00 0.00
Minimum of Months 956.29 796.76 843.47 50.92 658.16 0.00 0.00
Maximum of Months 3995.09 1668.92 2755.30 2097.14 843.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 788.86 1217.30 668.95 337.39 331.56 0.00 0.00
February 888.34 1154.41 798.06 368.42 429.64 0.00 0.00
March 1028.43 1192.55 914.79 404.72 510.07 0.00 0.00
April 1646.56 986.35 1261.09 656.65 604.44 0.00 0.00
May 1596.74 825.21 1238.79 572.19 666.59 0.00 0.00
June 1793.50 679.62 1312.36 656.16 656.21 0.00 0.00
July 2010.30 607.77 1389.24 743.37 645.87 0.00 0.00
August 1906.13 646.77 1303.38 706.38 597.00 0.00 0.00
September 1594.33 708.72 1115.93 597.12 518.81 0.00 0.00
October 1230.50 816.95 853.08 465.74 387.33 0.00 0.00
November 923.65 1182.15 770.59 403.07 367.52 0.00 0.00
December 794.84 1342.30 680.56 365.02 315.54 0.00 0.00
               
Annual Sum or Average 1352.45 945.60 1026.46 523.68 502.77 0.00 0.00
Minimum of Months 788.86 607.77 668.95 337.39 315.54 0.00 0.00
Maximum of Months 2010.30 1342.30 1389.24 743.37 666.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 222.69 1601.83 390.82 0.00 390.82 0.00 0.00
February 265.32 1455.51 490.59 0.00 490.59 0.00 0.00
March 393.25 1491.36 601.18 0.00 601.18 0.00 0.00
April 562.25 1184.98 692.63 2.67 689.96 0.00 0.00
May 714.00 1035.86 832.32 38.76 793.56 0.00 0.00
June 921.67 821.16 886.88 86.71 800.17 0.00 0.00
July 982.96 731.03 839.73 70.38 769.35 0.00 0.00
August 790.27 765.47 697.37 13.96 683.41 0.00 0.00
September 608.77 924.38 590.25 0.09 590.16 0.00 0.00
October 533.85 1027.36 468.21 0.00 468.21 0.00 0.00
November 258.41 1469.52 423.93 0.00 423.93 0.00 0.00
December 201.52 1614.59 363.82 0.00 363.82 0.00 0.00
               
Annual Sum or Average 539.61 1175.47 606.97 17.81 589.16 0.00 0.00
Minimum of Months 201.52 731.03 363.82 0.00 363.82 0.00 0.00
Maximum of Months 982.96 1614.59 886.88 86.71 800.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 827.22 1000.17 702.81 375.88 326.93 0.00 0.00
February 814.87 913.06 741.39 339.64 401.75 0.00 0.00
March 1036.12 935.20 900.57 401.25 499.33 0.00 0.00
April 1516.99 771.05 1151.37 577.43 573.93 0.00 0.00
May 1371.78 701.78 1086.56 453.45 633.12 0.00 0.00
June 1467.02 563.01 1079.80 468.51 611.29 0.00 0.00
July 1799.54 508.64 1223.49 607.99 615.51 0.00 0.00
August 1802.70 518.11 1208.30 641.81 566.49 0.00 0.00
September 1238.07 598.32 879.74 403.13 476.61 0.00 0.00
October 1121.02 653.74 778.73 400.25 378.48 0.00 0.00
November 835.98 919.96 709.90 360.66 349.24 0.00 0.00
December 798.91 1000.55 677.23 376.28 300.96 0.00 0.00
               
Annual Sum or Average 1222.01 756.16 929.57 451.41 478.15 0.00 0.00
Minimum of Months 798.91 508.64 677.23 339.64 300.96 0.00 0.00
Maximum of Months 1802.70 1000.55 1223.49 641.81 633.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3707.39 1609.62 2579.17 1891.94 687.23 0.00 0.00
February 2721.70 1456.15 2027.09 1248.58 778.51 0.00 0.00
March 2135.47 1512.38 1616.06 780.64 835.43 0.00 0.00
April 1915.65 1258.68 1350.26 514.87 835.39 0.00 0.00
May 1092.24 1127.02 961.49 118.32 843.17 0.00 0.00
June 964.53 880.38 843.48 50.93 792.56 0.00 0.00
July 1210.10 779.21 893.48 100.58 792.90 0.00 0.00
August 1801.14 824.65 1147.85 362.07 785.78 0.00 0.00
September 2504.74 979.57 1597.24 809.38 787.86 0.00 0.00
October 3197.16 1067.60 2031.31 1357.99 673.32 0.00 0.00
November 3533.19 1478.04 2468.85 1742.97 725.88 0.00 0.00
December 3981.25 1615.98 2755.38 2097.20 658.18 0.00 0.00
               
Annual Sum or Average 2396.21 1214.53 1687.89 921.85 766.04 0.00 0.00
Minimum of Months 964.53 779.21 843.48 50.93 658.18 0.00 0.00
Maximum of Months 3981.25 1615.98 2755.38 2097.20 843.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 824.29 1075.84 668.95 337.39 331.56 0.00 0.00
February 931.78 981.52 798.06 368.42 429.64 0.00 0.00
March 1082.03 1003.46 914.79 404.72 510.07 0.00 0.00
April 1693.59 847.84 1261.09 656.65 604.44 0.00 0.00
May 1611.53 761.26 1238.78 572.19 666.59 0.00 0.00
June 1812.00 608.63 1312.36 656.15 656.20 0.00 0.00
July 2035.50 554.70 1389.23 743.37 645.87 0.00 0.00
August 1938.39 573.86 1303.37 706.37 597.00 0.00 0.00
September 1603.57 648.88 1115.93 597.12 518.81 0.00 0.00
October 1261.26 712.84 853.08 465.74 387.33 0.00 0.00
November 972.12 991.41 770.58 403.07 367.51 0.00 0.00
December 855.78 1092.50 680.56 365.02 315.54 0.00 0.00
               
Annual Sum or Average 1387.40 820.26 1026.45 523.68 502.77 0.00 0.00
Minimum of Months 824.29 554.70 668.95 337.39 315.54 0.00 0.00
Maximum of Months 2035.50 1092.50 1389.23 743.37 666.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 274.57 1415.18 390.82 0.00 390.82 0.00 0.00
February 317.01 1283.82 490.59 0.00 490.59 0.00 0.00
March 442.04 1348.47 601.18 0.00 601.18 0.00 0.00
April 589.49 1099.59 692.63 2.67 689.96 0.00 0.00
May 745.76 967.77 832.32 38.76 793.56 0.00 0.00
June 926.12 784.42 886.88 86.71 800.17 0.00 0.00
July 975.15 709.74 839.73 70.38 769.35 0.00 0.00
August 787.27 737.10 697.37 13.96 683.41 0.00 0.00
September 619.53 868.55 590.25 0.09 590.16 0.00 0.00
October 556.31 949.14 468.21 0.00 468.21 0.00 0.00
November 307.64 1306.96 423.93 0.00 423.93 0.00 0.00
December 253.72 1423.81 363.82 0.00 363.82 0.00 0.00
               
Annual Sum or Average 567.78 1073.48 606.97 17.81 589.16 0.00 0.00
Minimum of Months 253.72 709.74 363.82 0.00 363.82 0.00 0.00
Maximum of Months 975.15 1423.81 886.88 86.71 800.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 868.50 904.53 702.81 375.88 326.93 0.00 0.00
February 847.92 825.62 741.39 339.64 401.75 0.00 0.00
March 1066.71 865.45 900.57 401.25 499.33 0.00 0.00
April 1528.01 733.36 1151.37 577.43 573.93 0.00 0.00
May 1384.49 668.16 1086.56 453.45 633.12 0.00 0.00
June 1465.00 547.46 1079.80 468.51 611.29 0.00 0.00
July 1788.53 503.37 1223.49 607.99 615.51 0.00 0.00
August 1794.03 509.93 1208.30 641.81 566.49 0.00 0.00
September 1239.43 574.31 879.74 403.13 476.61 0.00 0.00
October 1132.13 618.63 778.73 400.25 378.48 0.00 0.00
November 870.50 839.19 709.90 360.66 349.24 0.00 0.00
December 840.14 905.99 677.23 376.28 300.96 0.00 0.00
               
Annual Sum or Average 1238.19 707.41 929.57 451.41 478.15 0.00 0.00
Minimum of Months 840.14 503.37 677.23 339.64 300.96 0.00 0.00
Maximum of Months 1794.03 905.99 1223.49 641.81 633.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3754.25 1470.31 2579.17 1891.94 687.23 0.00 0.00
February 2764.26 1319.10 2027.09 1248.58 778.51 0.00 0.00
March 2175.53 1390.27 1616.06 780.64 835.43 0.00 0.00
April 1931.99 1184.82 1350.26 514.87 835.39 0.00 0.00
May 1114.26 1055.21 961.49 118.32 843.17 0.00 0.00
June 969.79 841.92 843.48 50.93 792.56 0.00 0.00
July 1202.78 759.54 893.48 100.58 792.90 0.00 0.00
August 1792.86 801.39 1147.85 362.07 785.78 0.00 0.00
September 2503.50 936.55 1597.24 809.38 787.86 0.00 0.00
October 3208.53 1011.84 2031.31 1357.99 673.32 0.00 0.00
November 3568.92 1362.97 2468.85 1742.97 725.88 0.00 0.00
December 4026.71 1482.97 2755.38 2097.20 658.18 0.00 0.00
               
Annual Sum or Average 2416.84 1133.81 1687.89 921.85 766.04 0.00 0.00
Minimum of Months 969.79 759.54 843.48 50.93 658.18 0.00 0.00
Maximum of Months 4026.71 1482.97 2755.38 2097.20 843.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 847.91 980.26 668.95 337.39 331.56 0.00 0.00
February 953.83 894.63 798.06 368.42 429.64 0.00 0.00
March 1102.78 928.93 914.79 404.72 510.07 0.00 0.00
April 1700.38 803.24 1261.09 656.65 604.44 0.00 0.00
May 1618.97 721.51 1238.78 572.19 666.59 0.00 0.00
June 1807.55 587.39 1312.36 656.15 656.20 0.00 0.00
July 2023.79 543.69 1389.23 743.37 645.87 0.00 0.00
August 1929.07 559.67 1303.37 706.37 597.00 0.00 0.00
September 1603.35 621.13 1115.93 597.12 518.81 0.00 0.00
October 1269.03 672.74 853.08 465.74 387.33 0.00 0.00
November 992.49 909.79 770.58 403.07 367.51 0.00 0.00
December 878.81 995.88 680.56 365.02 315.54 0.00 0.00
               
Annual Sum or Average 1396.17 767.61 1026.45 523.68 502.77 0.00 0.00
Minimum of Months 847.91 543.69 668.95 337.39 315.54 0.00 0.00
Maximum of Months 2023.79 995.88 1389.23 743.37 666.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.485329E+09 0.477500E+10 0.104677E+10 0.00 0.104677E+10 0.00 0.00
February 0.540971E+09 0.394154E+10 0.118681E+10 0.00 0.118681E+10 0.00 0.00
March 0.933917E+09 0.443394E+10 0.161017E+10 0.00 0.161017E+10 0.00 0.00
April 0.135130E+10 0.335520E+10 0.179527E+10 6909602.89 0.178836E+10 0.00 0.00
May 0.183916E+10 0.293576E+10 0.222924E+10 0.103804E+09 0.212544E+10 0.00 0.00
June 0.235409E+10 0.224189E+10 0.229875E+10 0.224738E+09 0.207401E+10 0.00 0.00
July 0.258762E+10 0.202752E+10 0.224911E+10 0.188510E+09 0.206060E+10 0.00 0.00
August 0.205750E+10 0.214629E+10 0.186781E+10 37400472.82 0.183041E+10 0.00 0.00
September 0.153584E+10 0.254757E+10 0.152991E+10 239793.28 0.152967E+10 0.00 0.00
October 0.135462E+10 0.298643E+10 0.125403E+10 0.00 0.125403E+10 0.00 0.00
November 0.561410E+09 0.424179E+10 0.109880E+10 0.00 0.109880E+10 0.00 0.00
December 0.399990E+09 0.491065E+10 0.974451E+09 0.00 0.974451E+09 0.00 0.00
               
Annual Sum or Average 0.160017E+11 0.405436E+11 0.191411E+11 0.561602E+09 0.185795E+11 0.00 0.00
Minimum of Months 0.399990E+09 0.202752E+10 0.974451E+09 0.00 0.974451E+09 0.00 0.00
Maximum of Months 0.258762E+10 0.491065E+10 0.229875E+10 0.224738E+09 0.212544E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.214882E+10 0.290735E+10 0.188241E+10 0.100676E+10 0.875651E+09 0.00 0.00
February 0.192404E+10 0.239474E+10 0.179358E+10 0.821652E+09 0.971925E+09 0.00 0.00
March 0.273195E+10 0.267438E+10 0.241210E+10 0.107470E+10 0.133740E+10 0.00 0.00
April 0.393791E+10 0.206181E+10 0.298436E+10 0.149672E+10 0.148764E+10 0.00 0.00
May 0.367298E+10 0.195299E+10 0.291027E+10 0.121452E+10 0.169574E+10 0.00 0.00
June 0.381789E+10 0.149902E+10 0.279885E+10 0.121437E+10 0.158448E+10 0.00 0.00
July 0.486069E+10 0.134006E+10 0.327702E+10 0.162844E+10 0.164858E+10 0.00 0.00
August 0.486770E+10 0.135596E+10 0.323632E+10 0.171902E+10 0.151730E+10 0.00 0.00
September 0.321160E+10 0.161220E+10 0.228029E+10 0.104491E+10 0.123537E+10 0.00 0.00
October 0.299306E+10 0.183282E+10 0.208575E+10 0.107202E+10 0.101373E+10 0.00 0.00
November 0.211741E+10 0.255437E+10 0.184007E+10 0.934834E+09 0.905241E+09 0.00 0.00
December 0.206877E+10 0.289986E+10 0.181391E+10 0.100783E+10 0.806083E+09 0.00 0.00
               
Annual Sum or Average 0.383528E+11 0.250855E+11 0.293149E+11 0.142358E+11 0.150791E+11 0.00 0.00
Minimum of Months 0.192404E+10 0.134006E+10 0.179358E+10 0.821652E+09 0.806083E+09 0.00 0.00
Maximum of Months 0.486770E+10 0.290735E+10 0.327702E+10 0.171902E+10 0.169574E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.997528E+10 0.439242E+10 0.690784E+10 0.506721E+10 0.184063E+10 0.00 0.00
February 0.662340E+10 0.365115E+10 0.490379E+10 0.302047E+10 0.188332E+10 0.00 0.00
March 0.572283E+10 0.423019E+10 0.432835E+10 0.209078E+10 0.223756E+10 0.00 0.00
April 0.496522E+10 0.339228E+10 0.349979E+10 0.133449E+10 0.216530E+10 0.00 0.00
May 0.291992E+10 0.311885E+10 0.257520E+10 0.316910E+09 0.225829E+10 0.00 0.00
June 0.247871E+10 0.237680E+10 0.218627E+10 0.131997E+09 0.205427E+10 0.00 0.00
July 0.321930E+10 0.213403E+10 0.239305E+10 0.269385E+09 0.212367E+10 0.00 0.00
August 0.482361E+10 0.224297E+10 0.307434E+10 0.969733E+09 0.210461E+10 0.00 0.00
September 0.653812E+10 0.258481E+10 0.413993E+10 0.209783E+10 0.204210E+10 0.00 0.00
October 0.861519E+10 0.291469E+10 0.544051E+10 0.363712E+10 0.180339E+10 0.00 0.00
November 0.920738E+10 0.393870E+10 0.639908E+10 0.451764E+10 0.188144E+10 0.00 0.00
December 0.107004E+11 0.447003E+10 0.737979E+10 0.561697E+10 0.176282E+10 0.00 0.00
               
Annual Sum or Average 0.757894E+11 0.394469E+11 0.532279E+11 0.290705E+11 0.241574E+11 0.00 0.00
Minimum of Months 0.247871E+10 0.213403E+10 0.218627E+10 0.131997E+09 0.176282E+10 0.00 0.00
Maximum of Months 0.107004E+11 0.447003E+10 0.737979E+10 0.561697E+10 0.225829E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.211289E+10 0.326041E+10 0.179172E+10 0.903664E+09 0.888058E+09 0.00 0.00
February 0.214908E+10 0.279275E+10 0.193067E+10 0.891289E+09 0.103938E+10 0.00 0.00
March 0.275455E+10 0.319412E+10 0.245018E+10 0.108400E+10 0.136618E+10 0.00 0.00
April 0.426789E+10 0.255661E+10 0.326875E+10 0.170204E+10 0.156672E+10 0.00 0.00
May 0.427671E+10 0.221024E+10 0.331797E+10 0.153257E+10 0.178541E+10 0.00 0.00
June 0.464875E+10 0.176157E+10 0.340164E+10 0.170076E+10 0.170089E+10 0.00 0.00
July 0.538440E+10 0.162786E+10 0.372094E+10 0.199104E+10 0.172990E+10 0.00 0.00
August 0.510538E+10 0.173230E+10 0.349097E+10 0.189196E+10 0.159901E+10 0.00 0.00
September 0.413250E+10 0.183701E+10 0.289250E+10 0.154773E+10 0.134476E+10 0.00 0.00
October 0.329578E+10 0.218811E+10 0.228489E+10 0.124745E+10 0.103744E+10 0.00 0.00
November 0.239411E+10 0.306414E+10 0.199736E+10 0.104476E+10 0.952599E+09 0.00 0.00
December 0.212891E+10 0.359522E+10 0.182281E+10 0.977671E+09 0.845141E+09 0.00 0.00
               
Annual Sum or Average 0.426510E+11 0.298203E+11 0.323704E+11 0.165149E+11 0.158555E+11 0.00 0.00
Minimum of Months 0.211289E+10 0.162786E+10 0.179172E+10 0.891289E+09 0.845141E+09 0.00 0.00
Maximum of Months 0.538440E+10 0.359522E+10 0.372094E+10 0.199104E+10 0.178541E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.596445E+09 0.429034E+10 0.104678E+10 0.00 0.104678E+10 0.00 0.00
February 0.641858E+09 0.352118E+10 0.118683E+10 0.00 0.118683E+10 0.00 0.00
March 0.105329E+10 0.399445E+10 0.161020E+10 0.00 0.161020E+10 0.00 0.00
April 0.145736E+10 0.307147E+10 0.179529E+10 6909808.95 0.178838E+10 0.00 0.00
May 0.191239E+10 0.277444E+10 0.222928E+10 0.103808E+09 0.212547E+10 0.00 0.00
June 0.238897E+10 0.212846E+10 0.229879E+10 0.224745E+09 0.207404E+10 0.00 0.00
July 0.263276E+10 0.195800E+10 0.224914E+10 0.188515E+09 0.206063E+10 0.00 0.00
August 0.211666E+10 0.205022E+10 0.186784E+10 37401588.21 0.183043E+10 0.00 0.00
September 0.157794E+10 0.239598E+10 0.152993E+10 239800.43 0.152969E+10 0.00 0.00
October 0.142985E+10 0.275168E+10 0.125405E+10 0.00 0.125405E+10 0.00 0.00
November 0.669811E+09 0.380900E+10 0.109882E+10 0.00 0.109882E+10 0.00 0.00
December 0.539762E+09 0.432451E+10 0.974467E+09 0.00 0.974467E+09 0.00 0.00
               
Annual Sum or Average 0.170171E+11 0.370697E+11 0.191414E+11 0.561619E+09 0.185798E+11 0.00 0.00
Minimum of Months 0.539762E+09 0.195800E+10 0.974467E+09 0.00 0.974467E+09 0.00 0.00
Maximum of Months 0.263276E+10 0.432451E+10 0.229879E+10 0.224745E+09 0.212547E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.221562E+10 0.267886E+10 0.188240E+10 0.100675E+10 0.875648E+09 0.00 0.00
February 0.197134E+10 0.220887E+10 0.179357E+10 0.821648E+09 0.971921E+09 0.00 0.00
March 0.277514E+10 0.250485E+10 0.241209E+10 0.107470E+10 0.133739E+10 0.00 0.00
April 0.393203E+10 0.199857E+10 0.298435E+10 0.149671E+10 0.148764E+10 0.00 0.00
May 0.367418E+10 0.187964E+10 0.291025E+10 0.121452E+10 0.169574E+10 0.00 0.00
June 0.380252E+10 0.145932E+10 0.279884E+10 0.121437E+10 0.158447E+10 0.00 0.00
July 0.481989E+10 0.136234E+10 0.327700E+10 0.162843E+10 0.164857E+10 0.00 0.00
August 0.482835E+10 0.138770E+10 0.323631E+10 0.171902E+10 0.151729E+10 0.00 0.00
September 0.320909E+10 0.155085E+10 0.228028E+10 0.104491E+10 0.123537E+10 0.00 0.00
October 0.300255E+10 0.175099E+10 0.208575E+10 0.107202E+10 0.101373E+10 0.00 0.00
November 0.216686E+10 0.238454E+10 0.184007E+10 0.934830E+09 0.905237E+09 0.00 0.00
December 0.213981E+10 0.267986E+10 0.181390E+10 0.100782E+10 0.806080E+09 0.00 0.00
               
Annual Sum or Average 0.385374E+11 0.238464E+11 0.293148E+11 0.142357E+11 0.150791E+11 0.00 0.00
Minimum of Months 0.197134E+10 0.136234E+10 0.179357E+10 0.821648E+09 0.806080E+09 0.00 0.00
Maximum of Months 0.482835E+10 0.267986E+10 0.327700E+10 0.171902E+10 0.169574E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.992988E+10 0.431121E+10 0.690805E+10 0.506738E+10 0.184068E+10 0.00 0.00
February 0.658434E+10 0.352271E+10 0.490394E+10 0.302057E+10 0.188337E+10 0.00 0.00
March 0.571964E+10 0.405077E+10 0.432847E+10 0.209085E+10 0.223761E+10 0.00 0.00
April 0.496536E+10 0.326249E+10 0.349988E+10 0.133454E+10 0.216534E+10 0.00 0.00
May 0.292547E+10 0.301860E+10 0.257525E+10 0.316920E+09 0.225833E+10 0.00 0.00
June 0.250007E+10 0.228193E+10 0.218631E+10 0.132001E+09 0.205430E+10 0.00 0.00
July 0.324112E+10 0.208703E+10 0.239309E+10 0.269394E+09 0.212370E+10 0.00 0.00
August 0.482417E+10 0.220873E+10 0.307441E+10 0.969765E+09 0.210464E+10 0.00 0.00
September 0.649230E+10 0.253905E+10 0.414004E+10 0.209790E+10 0.204214E+10 0.00 0.00
October 0.856328E+10 0.285947E+10 0.544067E+10 0.363724E+10 0.180343E+10 0.00 0.00
November 0.915803E+10 0.383107E+10 0.639927E+10 0.451779E+10 0.188148E+10 0.00 0.00
December 0.106634E+11 0.432823E+10 0.738001E+10 0.561715E+10 0.176286E+10 0.00 0.00
               
Annual Sum or Average 0.755670E+11 0.383013E+11 0.532294E+11 0.290715E+11 0.241579E+11 0.00 0.00
Minimum of Months 0.250007E+10 0.208703E+10 0.218631E+10 0.132001E+09 0.176286E+10 0.00 0.00
Maximum of Months 0.106634E+11 0.432823E+10 0.738001E+10 0.561715E+10 0.225833E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.220777E+10 0.288153E+10 0.179171E+10 0.903660E+09 0.888054E+09 0.00 0.00
February 0.225417E+10 0.237450E+10 0.193067E+10 0.891285E+09 0.103938E+10 0.00 0.00
March 0.289812E+10 0.268766E+10 0.245017E+10 0.108400E+10 0.136618E+10 0.00 0.00
April 0.438978E+10 0.219761E+10 0.326874E+10 0.170203E+10 0.156671E+10 0.00 0.00
May 0.431633E+10 0.203896E+10 0.331796E+10 0.153256E+10 0.178540E+10 0.00 0.00
June 0.469671E+10 0.157758E+10 0.340163E+10 0.170075E+10 0.170088E+10 0.00 0.00
July 0.545187E+10 0.148570E+10 0.372092E+10 0.199103E+10 0.172989E+10 0.00 0.00
August 0.519177E+10 0.153704E+10 0.349095E+10 0.189195E+10 0.159900E+10 0.00 0.00
September 0.415646E+10 0.168191E+10 0.289248E+10 0.154773E+10 0.134476E+10 0.00 0.00
October 0.337816E+10 0.190927E+10 0.228488E+10 0.124745E+10 0.103743E+10 0.00 0.00
November 0.251973E+10 0.256974E+10 0.199735E+10 0.104475E+10 0.952595E+09 0.00 0.00
December 0.229212E+10 0.292616E+10 0.182280E+10 0.977667E+09 0.845137E+09 0.00 0.00
               
Annual Sum or Average 0.437530E+11 0.258677E+11 0.323703E+11 0.165149E+11 0.158554E+11 0.00 0.00
Minimum of Months 0.220777E+10 0.148570E+10 0.179171E+10 0.891285E+09 0.845137E+09 0.00 0.00
Maximum of Months 0.545187E+10 0.292616E+10 0.372092E+10 0.199103E+10 0.178540E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.735419E+09 0.379041E+10 0.104678E+10 0.00 0.104678E+10 0.00 0.00
February 0.766900E+09 0.310583E+10 0.118683E+10 0.00 0.118683E+10 0.00 0.00
March 0.118397E+10 0.361175E+10 0.161020E+10 0.00 0.161020E+10 0.00 0.00
April 0.152795E+10 0.285013E+10 0.179529E+10 6909808.95 0.178838E+10 0.00 0.00
May 0.199744E+10 0.259207E+10 0.222928E+10 0.103808E+09 0.212547E+10 0.00 0.00
June 0.240050E+10 0.203321E+10 0.229879E+10 0.224745E+09 0.207404E+10 0.00 0.00
July 0.261183E+10 0.190096E+10 0.224914E+10 0.188515E+09 0.206063E+10 0.00 0.00
August 0.210863E+10 0.197424E+10 0.186784E+10 37401588.21 0.183043E+10 0.00 0.00
September 0.160583E+10 0.225128E+10 0.152993E+10 239800.43 0.152969E+10 0.00 0.00
October 0.149001E+10 0.254217E+10 0.125405E+10 0.00 0.125405E+10 0.00 0.00
November 0.797410E+09 0.338764E+10 0.109882E+10 0.00 0.109882E+10 0.00 0.00
December 0.679569E+09 0.381354E+10 0.974467E+09 0.00 0.974467E+09 0.00 0.00
               
Annual Sum or Average 0.179054E+11 0.338532E+11 0.191414E+11 0.561619E+09 0.185798E+11 0.00 0.00
Minimum of Months 0.679569E+09 0.190096E+10 0.974467E+09 0.00 0.974467E+09 0.00 0.00
Maximum of Months 0.261183E+10 0.381354E+10 0.229879E+10 0.224745E+09 0.212547E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.232620E+10 0.242269E+10 0.188240E+10 0.100675E+10 0.875648E+09 0.00 0.00
February 0.205128E+10 0.199734E+10 0.179357E+10 0.821648E+09 0.971921E+09 0.00 0.00
March 0.285707E+10 0.231801E+10 0.241209E+10 0.107470E+10 0.133739E+10 0.00 0.00
April 0.396060E+10 0.190087E+10 0.298435E+10 0.149671E+10 0.148764E+10 0.00 0.00
May 0.370823E+10 0.178961E+10 0.291025E+10 0.121452E+10 0.169574E+10 0.00 0.00
June 0.379729E+10 0.141901E+10 0.279884E+10 0.121437E+10 0.158447E+10 0.00 0.00
July 0.479039E+10 0.134822E+10 0.327700E+10 0.162843E+10 0.164857E+10 0.00 0.00
August 0.480514E+10 0.136578E+10 0.323631E+10 0.171902E+10 0.151729E+10 0.00 0.00
September 0.321261E+10 0.148861E+10 0.228028E+10 0.104491E+10 0.123537E+10 0.00 0.00
October 0.303230E+10 0.165693E+10 0.208575E+10 0.107202E+10 0.101373E+10 0.00 0.00
November 0.225634E+10 0.217519E+10 0.184007E+10 0.934830E+09 0.905237E+09 0.00 0.00
December 0.225023E+10 0.242660E+10 0.181390E+10 0.100782E+10 0.806080E+09 0.00 0.00
               
Annual Sum or Average 0.390477E+11 0.223089E+11 0.293148E+11 0.142357E+11 0.150791E+11 0.00 0.00
Minimum of Months 0.205128E+10 0.134822E+10 0.179357E+10 0.821648E+09 0.806080E+09 0.00 0.00
Maximum of Months 0.480514E+10 0.242660E+10 0.327700E+10 0.171902E+10 0.169574E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100554E+11 0.393808E+10 0.690805E+10 0.506738E+10 0.184068E+10 0.00 0.00
February 0.668729E+10 0.319118E+10 0.490394E+10 0.302057E+10 0.188337E+10 0.00 0.00
March 0.582695E+10 0.372371E+10 0.432847E+10 0.209085E+10 0.223761E+10 0.00 0.00
April 0.500771E+10 0.307104E+10 0.349988E+10 0.133454E+10 0.216534E+10 0.00 0.00
May 0.298445E+10 0.282629E+10 0.257525E+10 0.316920E+09 0.225833E+10 0.00 0.00
June 0.251369E+10 0.218226E+10 0.218631E+10 0.132001E+09 0.205430E+10 0.00 0.00
July 0.322153E+10 0.203435E+10 0.239309E+10 0.269394E+09 0.212370E+10 0.00 0.00
August 0.480198E+10 0.214644E+10 0.307441E+10 0.969765E+09 0.210464E+10 0.00 0.00
September 0.648907E+10 0.242753E+10 0.414004E+10 0.209790E+10 0.204214E+10 0.00 0.00
October 0.859372E+10 0.271012E+10 0.544067E+10 0.363724E+10 0.180343E+10 0.00 0.00
November 0.925064E+10 0.353281E+10 0.639927E+10 0.451779E+10 0.188148E+10 0.00 0.00
December 0.107851E+11 0.397199E+10 0.738001E+10 0.561715E+10 0.176286E+10 0.00 0.00
               
Annual Sum or Average 0.762175E+11 0.357558E+11 0.532294E+11 0.290715E+11 0.241579E+11 0.00 0.00
Minimum of Months 0.251369E+10 0.203435E+10 0.218631E+10 0.132001E+09 0.176286E+10 0.00 0.00
Maximum of Months 0.107851E+11 0.397199E+10 0.738001E+10 0.561715E+10 0.225833E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.227105E+10 0.262553E+10 0.179171E+10 0.903660E+09 0.888054E+09 0.00 0.00
February 0.230751E+10 0.216430E+10 0.193067E+10 0.891285E+09 0.103938E+10 0.00 0.00
March 0.295370E+10 0.248804E+10 0.245017E+10 0.108400E+10 0.136618E+10 0.00 0.00
April 0.440737E+10 0.208199E+10 0.326874E+10 0.170203E+10 0.156671E+10 0.00 0.00
May 0.433624E+10 0.193250E+10 0.331796E+10 0.153256E+10 0.178540E+10 0.00 0.00
June 0.468517E+10 0.152252E+10 0.340163E+10 0.170075E+10 0.170088E+10 0.00 0.00
July 0.542052E+10 0.145621E+10 0.372092E+10 0.199103E+10 0.172989E+10 0.00 0.00
August 0.516683E+10 0.149901E+10 0.349095E+10 0.189195E+10 0.159900E+10 0.00 0.00
September 0.415588E+10 0.160997E+10 0.289248E+10 0.154773E+10 0.134476E+10 0.00 0.00
October 0.339896E+10 0.180186E+10 0.228488E+10 0.124745E+10 0.103743E+10 0.00 0.00
November 0.257253E+10 0.235819E+10 0.199735E+10 0.104475E+10 0.952595E+09 0.00 0.00
December 0.235382E+10 0.266737E+10 0.182280E+10 0.977667E+09 0.845137E+09 0.00 0.00
               
Annual Sum or Average 0.440296E+11 0.242075E+11 0.323703E+11 0.165149E+11 0.158554E+11 0.00 0.00
Minimum of Months 0.227105E+10 0.145621E+10 0.179171E+10 0.891285E+09 0.845137E+09 0.00 0.00
Maximum of Months 0.542052E+10 0.266737E+10 0.372092E+10 0.199103E+10 0.178540E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.340789E+11 -0.330571E+11 0.00 0.00 744.00 0.00 -0.102182E+10 58.98 0.00 0.00
February 0.309987E+11 -0.300737E+11 0.00 0.00 672.00 0.00 -925070694.1 58.98 0.00 0.00
March 0.360195E+11 -0.349929E+11 0.00 0.00 744.00 0.00 -0.102663E+10 58.97 0.00 0.00
April 0.320555E+11 -0.310658E+11 0.00 0.00 720.00 0.00 -989728801.4 58.96 0.00 0.00
May 0.333498E+11 -0.323248E+11 0.00 0.00 744.00 0.00 -0.102499E+10 58.98 0.00 0.00
June 0.323035E+11 -0.313106E+11 0.00 0.00 720.00 0.00 -992892425.9 58.97 0.00 0.00
July 0.303458E+11 -0.293259E+11 0.00 0.00 744.00 0.00 -0.101992E+10 58.97 0.00 0.00
August 0.330865E+11 -0.320617E+11 0.00 0.00 744.00 0.00 -0.102475E+10 58.99 0.00 0.00
September 0.304275E+11 -0.294386E+11 0.00 0.00 720.00 0.00 -988963504.8 58.97 0.00 0.00
October 0.320807E+11 -0.310608E+11 0.00 0.00 744.00 0.00 -0.101988E+10 58.98 0.00 0.00
November 0.322667E+11 -0.312800E+11 0.00 0.00 720.00 0.00 -986709981.4 58.96 0.00 0.00
December 0.328584E+11 -0.318385E+11 0.00 0.00 744.00 0.00 -0.101982E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.389872E+12 -0.377830E+12 0.00 0.00 8760.00 0.00 -0.120412E+11 58.97 0.00 0.00
Minimum of Months 0.303458E+11 -0.349929E+11 0.00 0.00 672.00 0.00 -0.102663E+10 58.96 0.00 0.00
Maximum of Months 0.360195E+11 -0.293259E+11 0.00 0.00 744.00 0.00 -925070694.1 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 293.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 279.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 338.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 358.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 393.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 381.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 408.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 390.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 328.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 296.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 300.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 297.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4065.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 279.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 408.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.236170E+10 30189.53 28-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.100927E+10 17149.05 09-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.155746E+10 23597.14 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 42037811.24 16693.05 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.130064E+09 7151.61 10-MAY-21:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 12770830.23 4735.55 12-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.112780E+09 7972.77 18-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.924681E+09 19712.26 12-DEC-22:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.615076E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.236170E+10 30189.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 1547278.15 1012.67 30-MAR-05:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1547278.15     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1547278.15 1012.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 861371.69 466.20 30-MAR-05:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 861371.69     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 861371.69 466.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.535513E+11 290645.89 03-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.400529E+11 273281.17 09-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.602343E+11 284778.32 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.180681E+11 252737.87 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.119722E+11 139284.62 10-MAY-20:10 0.00 0.00 0.00 0.00 0.00
June 0.111014E+10 105098.13 12-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.883495E+09 76184.26 20-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.355059E+10 183445.14 12-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.242412E+11 217576.82 30-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.449326E+11 285018.19 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.258597E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.602343E+11 290645.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161956E+10 131344.58 10-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.316158E+09 46631.51 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.878613E+09 132095.76 08-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 89860357.30 48607.91 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.102321E+09 80255.55 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.587521E+09 131871.52 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.359404E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161956E+10 132095.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.129360E+10 126758.45 03-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.840316E+09 41887.97 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.103334E+10 129248.48 29-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 71898701.48 52092.61 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 1285252.35 1761.16 12-OCT-05:50 0.00 0.00 0.00 0.00 0.00
November 0.131258E+09 37094.62 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.695135E+09 121704.91 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.406683E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.129360E+10 129248.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.389148E+09 163421.85 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.117424E+09 14206.59 28-FEB-06:06 0.00 0.00 0.00 0.00 0.00
March 0.731046E+09 170951.43 29-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.103597E+09 24049.13 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 90651172.47 89117.58 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.143187E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.731046E+09 170951.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137226E+10 121851.86 03-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.490172E+09 19446.02 28-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.796281E+09 105077.47 30-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.117616E+09 21957.68 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 5984305.88 5404.46 13-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 63533700.10 11964.88 24-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 0.514095E+09 69751.16 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.335994E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137226E+10 121851.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.675425E+10 31073.07 09-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.540639E+10 28689.15 09-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.854645E+10 30390.18 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.239442E+10 26533.27 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.151706E+10 14627.20 10-MAY-20:00 0.00 0.00 0.00 0.00 0.00
June 0.200666E+09 11040.24 12-JUN-21:00 0.00 0.00 0.00 0.00 0.00
July 116948.42 194.91 07-JUL-21:00 0.00 0.00 0.00 0.00 0.00
August 12978636.37 3830.82 28-AUG-07:00 0.00 0.00 0.00 0.00 0.00
September 0.174352E+09 10439.96 20-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.480800E+09 19377.46 12-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.328819E+10 22843.63 30-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.593839E+10 30415.67 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.347141E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 116948.42 194.91   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.854645E+10 31073.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.429607E+09 76136.39 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 61911724.61 47673.04 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 1217119.93 856.42 30-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2998362.05 1516.44 27-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 37320088.33 20528.32 26-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.533054E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.429607E+09 76136.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131299E+10 14116.58 02-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.838823E+09 14093.08 13-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.929934E+09 14035.42 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.142492E+09 13990.13 17-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 41113556.70 13990.45 13-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 85129.47 128.92 20-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 87513775.28 13984.98 30-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.529179E+09 14039.35 13-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.101676E+10 13990.98 12-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.489889E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.131299E+10 14116.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.737039E+09 14153.67 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.626071E+09 14089.67 27-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.633196E+09 14142.93 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 92677988.10 13491.31 18-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 25419780.19 11744.29 13-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 751763.08 161.65 01-JUN-05:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 2404407.82 982.27 20-SEP-05:10 0.00 0.00 0.00 0.00 0.00
October 47507642.14 11177.86 30-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.278901E+09 14094.45 08-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.582459E+09 14095.33 13-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.302643E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.737039E+09 14153.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.553738E+09 18300.16 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.558506E+09 18308.10 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.757677E+09 18247.74 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.147020E+09 18248.62 18-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.100611E+09 18250.11 13-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 62339.46 64.91 13-JUN-05:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 26148228.35 3957.11 12-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.178641E+09 18200.02 06-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.374496E+09 18208.75 13-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.269690E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.757677E+09 18308.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.810358E+09 15373.23 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.579533E+09 13517.41 28-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.610935E+09 15356.54 30-MAR-04:02 0.00 0.00 0.00 0.00 0.00
April 0.106694E+09 11376.54 01-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 57039381.10 10695.36 13-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 410721.99 216.84 01-JUN-05:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 57512830.59 2489.55 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.333599E+09 13765.97 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.615494E+09 15351.32 13-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.317158E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.810358E+09 15373.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 107.33 0.72 07-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 80.47 0.80 27-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 187.80     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 107.33 0.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.207122E+11 0.206778E+11 90868.20 18-JAN-13:10 90868.20 0.18
February 0.00 0.00 0.121801E+11 0.121008E+11 87297.82 01-FEB-12:00 87297.82 0.15
March 0.00 0.00 0.147850E+11 0.143362E+11 100180.10 23-MAR-14:00 83220.37 0.19
April 0.00 0.00 0.333266E+11 0.332214E+11 112697.87 26-APR-11:00 103660.65 0.38
May 0.00 0.00 0.301885E+11 0.300778E+11 82853.43 03-MAY-13:00 82853.43 0.41
June 0.00 0.00 0.561840E+11 0.502566E+11 134915.59 29-JUN-13:00 85567.29 0.59
July 0.00 0.00 0.104123E+12 0.744661E+11 188451.06 31-JUL-15:40 106375.55 0.73
August 0.00 0.00 0.128606E+12 0.862185E+11 190354.86 07-AUG-10:40 108702.04 0.78
September 0.00 0.00 0.636230E+11 0.522577E+11 152911.92 22-SEP-12:30 79638.94 0.55
October 0.00 0.00 0.784053E+11 0.655185E+11 176946.09 04-OCT-05:03 85177.32 0.40
November 0.00 0.00 0.253077E+11 0.249706E+11 96446.35 28-NOV-14:00 96446.35 0.20
December 0.00 0.00 0.295185E+11 0.294169E+11 103801.22 05-DEC-15:00 103801.22 0.08
                 
Annual Sum or Average 0.00 0.00 0.596959E+12 0.493519E+12       0.39
Minimum of Months 0.00 0.00 0.121801E+11 0.121008E+11 82853.43   79638.94 0.08
Maximum of Months 0.00 0.00 0.128606E+12 0.862185E+11 190354.86   108702.04 0.78



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.172506E+12 0.171849E+12 777380.88 18-JAN-13:10 777380.88 0.18
February 0.00 0.00 0.939737E+11 0.931998E+11 741571.96 01-FEB-12:00 741571.96 0.15
March 0.00 0.00 0.106589E+12 0.103675E+12 818431.57 23-MAR-14:20 668620.59 0.18
April 0.00 0.00 0.237220E+12 0.237071E+12 921181.56 26-APR-13:00 921181.56 0.35
May 0.00 0.00 0.250196E+12 0.249228E+12 745828.92 03-MAY-13:00 745828.92 0.39
June 0.00 0.00 0.454366E+12 0.408591E+12 1169203.87 29-JUN-13:00 747597.07 0.55
July 0.00 0.00 0.799079E+12 0.580492E+12 1549712.96 31-JUL-15:50 877079.72 0.60
August 0.00 0.00 0.945120E+12 0.651876E+12 1575514.05 18-AUG-15:50 898014.93 0.63
September 0.00 0.00 0.544737E+12 0.449783E+12 1365300.00 22-SEP-12:30 712745.79 0.53
October 0.00 0.00 0.638222E+12 0.536457E+12 1682907.34 05-OCT-05:03 728786.01 0.37
November 0.00 0.00 0.183258E+12 0.181383E+12 746291.43 28-NOV-14:00 746291.43 0.20
December 0.00 0.00 0.207585E+12 0.206864E+12 788584.41 05-DEC-15:00 788584.41 0.08
                 
Annual Sum or Average 0.00 0.00 0.463285E+13 0.387047E+13       0.35
Minimum of Months 0.00 0.00 0.939737E+11 0.931998E+11 741571.96   668620.59 0.08
Maximum of Months 0.00 0.00 0.945120E+12 0.651876E+12 1682907.34   921181.56 0.63



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.131388E+11 0.131388E+11 75255.74 18-JAN-13:30 75255.74 0.16
February 0.00 0.00 0.740741E+10 0.734068E+10 68162.52 01-FEB-12:00 68162.52 0.14
March 0.00 0.00 0.918160E+10 0.904819E+10 80375.68 23-MAR-15:00 66249.16 0.16
April 0.00 0.00 0.233213E+11 0.233150E+11 110117.24 26-APR-14:00 110117.24 0.33
May 0.00 0.00 0.245790E+11 0.245021E+11 84671.26 03-MAY-13:00 84671.26 0.37
June 0.00 0.00 0.472310E+11 0.422587E+11 132681.07 29-JUN-13:00 84348.16 0.54
July 0.00 0.00 0.858566E+11 0.623418E+11 195991.94 31-JUL-15:10 116270.65 0.58
August 0.00 0.00 0.100159E+12 0.687529E+11 193425.62 18-AUG-15:30 112913.97 0.60
September 0.00 0.00 0.536031E+11 0.446671E+11 155159.47 29-SEP-13:00 155159.47 0.49
October 0.00 0.00 0.612202E+11 0.516692E+11 156844.69 05-OCT-05:03 67857.81 0.35
November 0.00 0.00 0.141092E+11 0.141032E+11 72217.30 28-NOV-14:00 72217.30 0.18
December 0.00 0.00 0.160405E+11 0.160405E+11 80413.59 05-DEC-15:00 80413.59 0.06
                 
Annual Sum or Average 0.00 0.00 0.455848E+12 0.377178E+12       0.33
Minimum of Months 0.00 0.00 0.740741E+10 0.734068E+10 68162.52   66249.16 0.06
Maximum of Months 0.00 0.00 0.100159E+12 0.687529E+11 195991.94   155159.47 0.60



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.121005E+11 0.120595E+11 70283.31 17-JAN-14:00 66306.61 0.11
February 0.00 0.00 0.537816E+10 0.534066E+10 64735.52 13-FEB-06:03 29000.37 0.08
March 0.00 0.00 0.624411E+10 0.619945E+10 47834.86 23-MAR-14:00 47834.86 0.10
April 0.00 0.00 0.160624E+11 0.159714E+11 63932.99 27-APR-05:03 29302.97 0.25
May 0.00 0.00 0.156200E+11 0.155462E+11 60871.43 03-MAY-05:03 25235.80 0.26
June 0.00 0.00 0.285060E+11 0.271747E+11 84518.98 30-JUN-05:03 36063.99 0.38
July 0.00 0.00 0.484688E+11 0.411180E+11 105925.76 31-JUL-09:10 63943.32 0.44
August 0.00 0.00 0.562466E+11 0.457965E+11 121803.78 07-AUG-09:50 67065.76 0.49
September 0.00 0.00 0.340179E+11 0.301664E+11 97954.20 22-SEP-10:00 40906.59 0.38
October 0.00 0.00 0.440538E+11 0.383321E+11 110840.74 05-OCT-04:03 51106.65 0.28
November 0.00 0.00 0.134614E+11 0.134305E+11 61339.83 10-NOV-04:02 28941.60 0.13
December 0.00 0.00 0.166741E+11 0.166620E+11 70463.54 25-DEC-15:10 70463.54 0.03
                 
Annual Sum or Average 0.00 0.00 0.296834E+12 0.267797E+12       0.25
Minimum of Months 0.00 0.00 0.537816E+10 0.534066E+10 47834.86   25235.80 0.03
Maximum of Months 0.00 0.00 0.562466E+11 0.457965E+11 121803.78   70463.54 0.49



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.331040E+12 0.329840E+12 130973.02 17-JAN-14:50 125751.53 0.00
February 0.00 0.00 0.518421E+12 0.516791E+12 220265.99 13-FEB-17:00 214222.50 0.00
March 0.00 0.00 0.819587E+12 0.817356E+12 393891.87 31-MAR-24:00 393891.87 0.00
April 0.00 0.00 0.103220E+13 0.102956E+13 408230.00 26-APR-15:00 401660.03 0.00
May 0.00 0.00 0.333693E+12 0.330665E+12 211325.01 31-MAY-23:20 210927.45 0.00
June 0.00 0.00 0.562586E+12 0.557048E+12 303012.04 30-JUN-24:00 302878.42 0.00
July 0.00 0.00 0.829763E+12 0.822910E+12 394968.11 31-JUL-23:53 394968.11 0.00
August 0.00 0.00 0.107393E+13 0.106710E+13 411515.09 18-AUG-17:00 401833.85 0.00
September 0.00 0.00 0.328657E+12 0.323200E+12 211451.78 30-SEP-24:00 211451.78 0.00
October 0.00 0.00 0.582342E+12 0.578820E+12 304835.47 31-OCT-24:00 303687.02 0.00
November 0.00 0.00 0.796594E+12 0.794786E+12 314123.47 10-NOV-17:00 307762.88 0.00
December 0.00 0.00 0.106628E+13 0.106563E+13 405241.38 29-DEC-16:30 405241.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.827508E+13 0.823370E+13       0.00
Minimum of Months 0.00 0.00 0.328657E+12 0.323200E+12 130973.02   125751.53 0.00
Maximum of Months 0.00 0.00 0.107393E+13 0.106710E+13 411515.09   405241.38 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.522427E+10 0.517997E+10 2492.25 18-JAN-16:10 2402.22 0.00
February 0.00 0.00 0.940320E+10 0.933815E+10 4498.56 21-FEB-17:00 4339.17 0.00
March 0.00 0.00 0.155809E+11 0.154876E+11 7559.27 31-MAR-24:00 7559.27 0.00
April 0.00 0.00 0.202252E+11 0.201093E+11 8360.58 16-APR-17:30 8338.97 0.00
May 0.00 0.00 0.564666E+10 0.553903E+10 3881.69 31-MAY-24:00 3862.81 0.00
June 0.00 0.00 0.106846E+11 0.104797E+11 5913.33 30-JUN-24:00 5901.62 0.00
July 0.00 0.00 0.162546E+11 0.159745E+11 7773.03 31-JUL-23:50 7771.66 0.00
August 0.00 0.00 0.212940E+11 0.209851E+11 8520.65 17-AUG-15:50 8170.94 0.00
September 0.00 0.00 0.577372E+10 0.557702E+10 4059.00 30-SEP-24:00 4059.00 0.00
October 0.00 0.00 0.109838E+11 0.108509E+11 5893.22 31-OCT-24:00 5867.56 0.00
November 0.00 0.00 0.152437E+11 0.151712E+11 6444.37 07-NOV-16:20 6272.32 0.00
December 0.00 0.00 0.207071E+11 0.206768E+11 8373.67 25-DEC-16:10 8373.67 0.00
                 
Annual Sum or Average 0.00 0.00 0.157022E+12 0.155369E+12       0.00
Minimum of Months 0.00 0.00 0.522427E+10 0.517997E+10 2492.25   2402.22 0.00
Maximum of Months 0.00 0.00 0.212940E+11 0.209851E+11 8520.65   8373.67 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.397351E+11 0.393082E+11 23086.00 18-JAN-16:20 22164.44 0.00
February 0.00 0.00 0.811230E+11 0.804831E+11 42195.79 01-FEB-16:50 39992.43 0.00
March 0.00 0.00 0.139988E+12 0.139060E+12 67764.60 31-MAR-23:40 67764.60 0.00
April 0.00 0.00 0.188456E+12 0.187298E+12 78656.43 26-APR-16:00 76877.70 0.00
May 0.00 0.00 0.488200E+11 0.477745E+11 35242.03 31-MAY-24:00 35008.69 0.00
June 0.00 0.00 0.986743E+11 0.966553E+11 55934.26 30-JUN-24:00 55811.43 0.00
July 0.00 0.00 0.153719E+12 0.150934E+12 74374.95 31-JUL-24:00 74340.15 0.00
August 0.00 0.00 0.201986E+12 0.198901E+12 81024.64 17-AUG-16:00 77550.24 0.00
September 0.00 0.00 0.512239E+11 0.493092E+11 38867.78 30-SEP-24:00 38867.78 0.00
October 0.00 0.00 0.999301E+11 0.986202E+11 54548.75 31-OCT-24:00 54300.39 0.00
November 0.00 0.00 0.137672E+12 0.136954E+12 60820.14 10-NOV-16:20 58476.31 0.00
December 0.00 0.00 0.188085E+12 0.187780E+12 78611.87 07-DEC-16:10 76589.16 0.00
                 
Annual Sum or Average 0.00 0.00 0.142941E+13 0.141308E+13       0.00
Minimum of Months 0.00 0.00 0.397351E+11 0.393082E+11 23086.00   22164.44 0.00
Maximum of Months 0.00 0.00 0.201986E+12 0.198901E+12 81024.64   77550.24 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.268086E+10 0.263987E+10 2331.04 18-JAN-16:10 2243.61 0.00
February 0.00 0.00 0.703618E+10 0.697325E+10 4241.43 01-FEB-16:50 4021.47 0.00
March 0.00 0.00 0.129964E+11 0.129044E+11 6365.03 31-MAR-23:20 6365.03 0.00
April 0.00 0.00 0.183270E+11 0.182115E+11 7967.24 26-APR-16:00 7789.26 0.00
May 0.00 0.00 0.435687E+10 0.425376E+10 3231.45 31-MAY-23:20 3180.62 0.00
June 0.00 0.00 0.963787E+10 0.943663E+10 5463.85 30-JUN-24:00 5451.01 0.00
July 0.00 0.00 0.152898E+11 0.150116E+11 7336.91 31-JUL-23:57 7333.16 0.00
August 0.00 0.00 0.200832E+11 0.197750E+11 8212.26 17-AUG-16:00 7864.89 0.00
September 0.00 0.00 0.480689E+10 0.461736E+10 3823.69 30-SEP-24:00 3823.69 0.00
October 0.00 0.00 0.949510E+10 0.936511E+10 5211.27 31-OCT-23:50 5186.42 0.00
November 0.00 0.00 0.127562E+11 0.126849E+11 6096.57 10-NOV-16:20 5862.40 0.00
December 0.00 0.00 0.175402E+11 0.175100E+11 7858.31 07-DEC-16:10 7656.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.135006E+12 0.133383E+12       0.00
Minimum of Months 0.00 0.00 0.268086E+10 0.263987E+10 2331.04   2243.61 0.00
Maximum of Months 0.00 0.00 0.200832E+11 0.197750E+11 8212.26   7864.89 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 26262.07 811333.50 02-JAN-06:01
February 0.00 0.00 01-FEB-00:10 20859.31 417537.49 10-FEB-07:10
March 0.00 0.00 01-MAR-00:10 28359.09 817124.51 30-MAR-05:03
April 0.00 0.00 01-APR-00:10 8157.52 458938.46 01-APR-06:10
May 0.00 0.00 01-MAY-00:10 5122.95 169544.12 15-MAY-06:10
June 0.00 0.00 01-JUN-00:10 507.53 124745.56 12-JUN-21:00
July 0.00 0.00 01-JUL-00:10 0.03 154.87 07-JUL-21:00
August 0.00 0.00 01-AUG-00:03 4.33 3491.72 28-AUG-07:00
September 0.00 0.00 01-SEP-00:03 402.70 93791.87 20-SEP-06:10
October 0.00 0.00 01-OCT-00:10 1577.79 265240.19 12-OCT-06:05
November 0.00 0.00 01-NOV-00:10 11196.40 318627.61 30-NOV-07:10
December 0.00 0.00 01-DEC-00:10 20819.63 520745.29 23-DEC-07:05
             
Annual Sum or Average 0.00     10242.49    
Minimum of Months 0.00 0.00   0.03 154.87  
Maximum of Months 0.00 0.00   28359.09 817124.51  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 146408.74 1328627.50 13-JAN-14:00 0.00 0.00 01-JAN-00:05
February 96234.30 1152935.75 03-FEB-12:20 0.00 0.00 01-FEB-00:10
March 94455.42 1216619.57 23-MAR-13:50 0.00 0.00 01-MAR-00:10
April 212313.15 1243759.71 12-APR-14:00 0.00 0.00 01-APR-00:10
May 221395.34 1253185.81 03-MAY-13:00 0.00 0.00 01-MAY-00:10
June 348152.75 1517911.77 29-JUN-13:00 0.00 0.00 01-JUN-00:10
July 521288.72 1985103.15 31-JUL-15:50 0.00 0.00 01-JUL-00:10
August 592302.03 2001327.07 18-AUG-15:50 0.00 0.00 01-AUG-00:03
September 385792.86 1790777.20 29-SEP-12:20 0.00 0.00 01-SEP-00:03
October 424332.75 1852748.50 03-OCT-13:30 0.00 0.00 01-OCT-00:10
November 169304.21 1165884.92 08-NOV-12:30 0.00 0.00 01-NOV-00:10
December 168168.45 1225054.88 05-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 283233.82     0.00    
Minimum of Months 94455.42 1152935.75   0.00 0.00  
Maximum of Months 592302.03 2001327.07   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 95146.19 1327421.49 13-JAN-14:00 0.00 0.00 01-JAN-00:05
February 56173.18 1110276.85 01-FEB-12:00 0.00 0.00 01-FEB-00:10
March 57760.91 1210040.45 23-MAR-13:50 0.00 0.00 01-MAR-00:10
April 138219.21 1237860.10 12-APR-14:00 0.00 0.00 01-APR-00:10
May 140395.37 1244111.18 03-MAY-13:00 0.00 0.00 01-MAY-00:10
June 252385.29 1578196.13 30-JUN-05:03 0.00 0.00 01-JUN-00:10
July 415016.46 2189227.63 29-JUL-05:03 0.00 0.00 01-JUL-00:10
August 487379.89 2431179.96 07-AUG-05:02 0.00 0.00 01-AUG-00:03
September 293305.58 2403659.50 30-SEP-05:02 0.00 0.00 01-SEP-00:03
October 333481.04 2812206.03 05-OCT-05:03 0.00 0.00 01-OCT-00:10
November 105699.67 1420182.26 19-NOV-12:23 0.00 0.00 01-NOV-00:10
December 115924.18 1222812.73 05-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 208929.77     0.00    
Minimum of Months 56173.18 1110276.85   0.00 0.00  
Maximum of Months 487379.89 2812206.03   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 212913.89 660512.84 13-JAN-14:00 0.00 0.00 01-JAN-00:05
February 345277.26 869994.96 01-FEB-12:00 0.00 0.00 01-FEB-00:10
March 502179.87 975489.14 11-MAR-14:00 0.00 0.00 01-MAR-00:10
April 739587.98 1363370.23 26-APR-13:00 0.00 0.00 01-APR-00:10
May 232100.82 569275.70 03-MAY-13:00 0.00 0.00 01-MAY-00:10
June 458429.03 842990.15 29-JUN-11:00 0.00 0.00 01-JUN-00:10
July 742887.99 1234814.01 31-JUL-13:00 0.00 0.00 01-JUL-00:10
August 961780.97 1425758.93 14-AUG-11:00 0.00 0.00 01-AUG-00:03
September 304630.97 1206350.36 29-SEP-13:00 0.00 0.00 01-SEP-00:03
October 527572.46 1498438.32 16-OCT-11:00 0.00 0.00 01-OCT-00:10
November 539601.56 1140845.15 19-NOV-13:00 0.00 0.00 01-NOV-00:10
December 710954.16 1291884.46 19-DEC-13:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 524759.85     0.00    
Minimum of Months 212913.89 569275.70   0.00 0.00  
Maximum of Months 961780.97 1498438.32   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 13761.22 45604.66 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 13850.03 45610.16 02-FEB-12:30
March 0.00 0.00 01-MAR-00:10 14479.53 45388.87 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 13398.11 44586.71 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 13487.12 43620.80 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 13496.54 42534.91 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 12365.30 41693.94 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 13385.15 41613.85 31-AUG-11:20
September 0.00 0.00 01-SEP-00:03 12778.31 42289.81 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 13013.81 43383.91 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 13485.38 44436.83 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 13306.31 45227.38 29-DEC-12:50
             
Annual Sum or Average 0.00     13398.09    
Minimum of Months 0.00 0.00   12365.30 41613.85  
Maximum of Months 0.00 0.00   14479.53 45610.16  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 106766.44 2099476.79 13-JAN-13:50 959.92 90861.30 04-JAN-06:40
February 62682.99 1964910.99 01-FEB-13:20 664.88 92724.52 06-FEB-06:30
March 66631.05 2148432.22 23-MAR-13:50 387.17 71153.54 31-MAR-05:40
April 152771.35 2184802.58 26-APR-13:40 293.37 67152.59 01-APR-05:50
May 152648.04 1976255.02 18-MAY-15:20 208.05 47366.38 24-MAY-05:30
June 309385.17 2997583.62 29-JUN-13:00 127.57 29780.78 22-JUN-20:10
July 636625.77 4249943.31 31-JUL-13:00 99.10 28108.21 17-JUL-06:00
August 777221.25 4242209.77 17-AUG-14:10 106.17 29867.54 21-AUG-20:20
September 393499.55 3903193.36 22-SEP-12:30 219.48 34800.05 15-SEP-20:00
October 459594.30 3838963.26 03-OCT-13:30 262.75 52881.51 27-OCT-06:00
November 113929.32 1953586.26 28-NOV-11:50 709.68 76819.85 30-NOV-06:50
December 126803.10 1971356.46 18-DEC-13:10 833.38 93099.85 28-DEC-06:30
             
Annual Sum or Average 282075.82     404.58    
Minimum of Months 62682.99 1953586.26   99.10 28108.21  
Maximum of Months 777221.25 4249943.31   959.92 93099.85  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.169526E+11 0.94 10402.93 01-JAN-00:20 1.54
February 0.147321E+11 0.90 10402.93 01-FEB-04:03 1.54
March 0.169401E+11 0.93 10402.93 01-MAR-05:03 1.54
April 0.155451E+11 0.88 10402.93 01-APR-04:03 1.54
May 0.164257E+11 0.90 10402.93 01-MAY-03:02 1.54
June 0.163888E+11 0.93 10402.93 01-JUN-03:02 1.53
July 0.156377E+11 0.86 10402.93 01-JUL-03:02 1.53
August 0.171897E+11 0.94 10402.93 01-AUG-03:02 1.53
September 0.161062E+11 0.91 10402.93 01-SEP-03:02 1.53
October 0.168618E+11 0.93 10402.93 01-OCT-19:20 1.53
November 0.163479E+11 0.93 10402.93 01-NOV-03:02 1.54
December 0.165075E+11 0.91 10402.93 01-DEC-04:03 1.54
           
Annual Sum or Average 0.195635E+12 0.91      
Minimum of Months 0.147321E+11 0.86 10402.93   1.53
Maximum of Months 0.171897E+11 0.94 10402.93   1.54



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.713698E+10 0.43 11455.46 18-JAN-15:40 1.28
February 0.694513E+10 0.46 13534.48 21-FEB-15:50 1.42
March 0.890471E+10 0.51 14241.38 23-MAR-15:20 1.46
April 0.107086E+11 0.59 15891.67 26-APR-14:00 1.57
May 0.836995E+10 0.49 17174.40 01-MAY-05:03 1.65
June 0.100582E+11 0.56 20392.20 26-JUN-05:03 1.84
July 0.118191E+11 0.63 21255.63 03-JUL-05:03 1.89
August 0.140552E+11 0.71 19928.13 07-AUG-05:02 1.81
September 0.921968E+10 0.52 20090.50 25-SEP-05:03 1.83
October 0.968026E+10 0.53 21255.63 02-OCT-05:03 1.89
November 0.900659E+10 0.51 15071.64 13-NOV-15:10 1.52
December 0.895690E+10 0.50 15950.98 18-DEC-16:10 1.60
           
Annual Sum or Average 0.114861E+12 0.54      
Minimum of Months 0.694513E+10 0.43 11455.46   1.28
Maximum of Months 0.140552E+11 0.71 21255.63   1.89



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.495175E+11 0.37 125921.84 03-JAN-06:02 1.44
February 0.456579E+11 0.38 102169.07 01-FEB-06:03 1.26
March 0.532505E+11 0.40 126716.88 29-MAR-05:03 1.44
April 0.619449E+11 0.43 112478.91 26-APR-14:30 1.33
May 0.631051E+11 0.43 107730.73 01-MAY-05:03 1.30
June 0.730499E+11 0.48 127684.93 24-JUN-05:02 1.44
July 0.798750E+11 0.49 142052.47 01-JUL-05:03 1.54
August 0.906323E+11 0.53 123111.28 18-AUG-15:00 1.40
September 0.727225E+11 0.47 176420.89 30-SEP-05:02 1.77
October 0.683322E+11 0.45 146492.31 02-OCT-03:02 1.57
November 0.546350E+11 0.40 102237.00 24-NOV-06:02 1.27
December 0.502046E+11 0.38 114193.81 13-DEC-06:03 1.35
           
Annual Sum or Average 0.762927E+12 0.43      
Minimum of Months 0.456579E+11 0.37 102169.07   1.26
Maximum of Months 0.906323E+11 0.53 176420.89   1.77



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.380114E+10 0.32 7776.06 18-JAN-15:30 1.02
February 0.354472E+10 0.33 7657.90 03-FEB-15:10 1.02
March 0.423762E+10 0.35 10709.79 23-MAR-15:20 1.23
April 0.548970E+10 0.38 13162.35 26-APR-14:30 1.40
May 0.559796E+10 0.38 12184.51 03-MAY-15:20 1.33
June 0.704032E+10 0.44 12904.06 30-JUN-15:50 1.38
July 0.822852E+10 0.47 15335.72 31-JUL-14:40 1.53
August 0.910614E+10 0.50 14872.01 18-AUG-15:00 1.50
September 0.661569E+10 0.42 21300.62 30-SEP-05:02 1.90
October 0.594331E+10 0.39 13404.12 17-OCT-16:00 1.41
November 0.405523E+10 0.33 9154.85 01-NOV-05:03 1.12
December 0.379781E+10 0.32 9154.85 06-DEC-06:03 1.13
           
Annual Sum or Average 0.674582E+11 0.39      
Minimum of Months 0.354472E+10 0.32 7657.90   1.02
Maximum of Months 0.910614E+10 0.50 21300.62   1.90



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.957710E+11 1.37 35756.81 01-JAN-00:05 1.37
February 0.865029E+11 1.37 35756.81 01-FEB-00:10 1.37
March 0.957710E+11 1.37 35756.81 01-MAR-00:10 1.37
April 0.926817E+11 1.37 35756.81 01-APR-00:10 1.37
May 0.957710E+11 1.37 35756.81 01-MAY-00:10 1.37
June 0.926817E+11 1.37 35756.81 01-JUN-00:10 1.37
July 0.957710E+11 1.37 35756.81 01-JUL-00:10 1.37
August 0.957710E+11 1.37 35756.81 01-AUG-00:03 1.37
September 0.926817E+11 1.37 35756.81 01-SEP-00:03 1.37
October 0.957710E+11 1.37 35756.81 01-OCT-00:10 1.37
November 0.926817E+11 1.37 35756.81 01-NOV-00:10 1.37
December 0.957710E+11 1.37 35756.81 01-DEC-00:10 1.37
           
Annual Sum or Average 0.112763E+13 1.37      
Minimum of Months 0.865029E+11 1.37 35756.81   1.37
Maximum of Months 0.957710E+11 1.37 35756.81   1.37



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.143240E+10 0.93 534.80 01-JAN-00:05 0.93
February 0.129378E+10 0.93 534.80 01-FEB-00:10 0.93
March 0.143240E+10 0.93 534.80 01-MAR-00:10 0.93
April 0.138619E+10 0.93 534.80 01-APR-00:10 0.93
May 0.143240E+10 0.93 534.80 01-MAY-00:10 0.93
June 0.138619E+10 0.93 534.80 01-JUN-00:10 0.93
July 0.143240E+10 0.93 534.80 01-JUL-00:10 0.93
August 0.143240E+10 0.93 534.80 01-AUG-00:03 0.93
September 0.138619E+10 0.93 534.80 01-SEP-00:03 0.93
October 0.143240E+10 0.93 534.80 01-OCT-00:10 0.93
November 0.138619E+10 0.93 534.80 01-NOV-00:10 0.93
December 0.143240E+10 0.93 534.80 01-DEC-00:10 0.93
           
Annual Sum or Average 0.168653E+11 0.93      
Minimum of Months 0.129378E+10 0.93 534.80   0.93
Maximum of Months 0.143240E+10 0.93 534.80   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.136253E+11 0.93 5087.11 01-JAN-00:05 0.93
February 0.123067E+11 0.93 5087.11 01-FEB-00:10 0.93
March 0.136253E+11 0.93 5087.11 01-MAR-00:10 0.93
April 0.131858E+11 0.93 5087.11 01-APR-00:20 0.93
May 0.136253E+11 0.93 5087.11 01-MAY-00:24 0.93
June 0.131858E+11 0.93 5087.11 01-JUN-00:10 0.93
July 0.136253E+11 0.93 5087.11 01-JUL-00:10 0.93
August 0.136253E+11 0.93 5087.11 01-AUG-00:03 0.93
September 0.131858E+11 0.93 5087.11 01-SEP-00:03 0.93
October 0.136253E+11 0.93 5087.11 01-OCT-00:10 0.93
November 0.131858E+11 0.93 5087.11 01-NOV-00:10 0.93
December 0.136253E+11 0.93 5087.11 01-DEC-00:10 0.93
           
Annual Sum or Average 0.160427E+12 0.93      
Minimum of Months 0.123067E+11 0.93 5087.11   0.93
Maximum of Months 0.136253E+11 0.93 5087.11   0.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138943E+10 0.93 518.75 01-JAN-00:05 0.93
February 0.125497E+10 0.93 518.75 01-FEB-00:10 0.93
March 0.138943E+10 0.93 518.75 01-MAR-00:10 0.93
April 0.134461E+10 0.93 518.75 01-APR-00:10 0.93
May 0.138943E+10 0.93 518.75 01-MAY-00:10 0.93
June 0.134461E+10 0.93 518.75 01-JUN-00:10 0.93
July 0.138943E+10 0.93 518.75 01-JUL-00:10 0.93
August 0.138943E+10 0.93 518.75 01-AUG-00:03 0.93
September 0.134461E+10 0.93 518.75 01-SEP-00:03 0.93
October 0.138943E+10 0.93 518.75 01-OCT-00:10 0.93
November 0.134461E+10 0.93 518.75 01-NOV-00:10 0.93
December 0.138943E+10 0.93 518.75 01-DEC-00:10 0.93
           
Annual Sum or Average 0.163594E+11 0.93      
Minimum of Months 0.125497E+10 0.93 518.75   0.93
Maximum of Months 0.138943E+10 0.93 518.75   0.93



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.360341E+09 0.324307E+09 2927.27 02-JAN-06:01 2634.54 2634.54 44.09 5.12
February 0.239797E+09 0.215817E+09 1999.53 09-FEB-07:10 1799.58 1799.58 46.04 2.68
March 0.378368E+09 0.340531E+09 2804.14 29-MAR-05:03 2523.73 2523.73 47.02 4.66
April 94166555.21 84749899.69 1895.37 01-APR-06:10 1705.83 1705.83 38.02 2.50
May 60296384.15 54266745.73 782.80 10-MAY-21:00 704.52 704.52 38.01 0.87
June 5401301.01 4861170.91 535.71 12-JUN-21:00 482.14 482.14 30.38 0.58
July 423.10 380.79 0.71 07-JUL-21:00 0.63 0.63 30.37 0.00
August 52490.83 47241.74 15.77 28-AUG-06:55 14.19 14.19 30.05 0.02
September 4332003.28 3898802.96 379.02 20-SEP-06:10 341.12 341.12 26.20 0.40
October 18773633.69 16896270.32 1108.10 12-OCT-06:05 997.29 997.29 32.66 1.29
November 0.132699E+09 0.119429E+09 1422.38 30-NOV-07:10 1280.14 1280.14 37.84 1.73
December 0.283827E+09 0.255444E+09 2353.30 13-DEC-06:03 2117.97 2117.97 48.26 3.41
                 
Annual Sum or Average 0.157805E+10 0.142025E+10            
Minimum of Months 423.10 380.79 0.71   0.63 0.63 26.20 0.00
Maximum of Months 0.378368E+09 0.340531E+09 2927.27   2634.54 2634.54 48.26 5.12



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.405178E+10 0.364660E+10 16055.86 13-JAN-14:00 14450.28 14450.28 6.89 73.20
February 0.225834E+10 0.203250E+10 13698.83 21-FEB-13:10 12328.95 12328.95 8.05 41.53
March 0.244436E+10 0.219993E+10 13131.34 23-MAR-13:50 11818.21 11818.21 7.08 36.65
April 0.563821E+10 0.507439E+10 13673.84 12-APR-14:00 12306.46 12306.46 7.04 41.29
May 0.621133E+10 0.559020E+10 14477.88 03-MAY-13:00 13030.10 13030.10 6.98 51.44
June 0.895700E+10 0.806130E+10 14243.15 30-JUN-05:03 12818.84 12818.84 7.09 47.94
July 0.127134E+11 0.114421E+11 15794.41 29-JUL-05:03 14214.97 14214.97 7.03 70.71
August 0.143434E+11 0.129091E+11 16109.35 07-AUG-05:02 14498.41 14498.41 7.34 73.67
September 0.955455E+10 0.859910E+10 18894.91 29-SEP-12:20 17005.42 17005.42 6.75 89.01
October 0.107927E+11 0.971340E+10 18989.58 05-OCT-05:03 17090.62 17090.62 7.18 89.37
November 0.433103E+10 0.389793E+10 14506.20 08-NOV-13:30 13055.58 13055.58 8.13 51.89
December 0.427983E+10 0.385184E+10 13613.56 07-DEC-11:30 12252.21 12252.21 8.05 40.71
                 
Annual Sum or Average 0.855760E+11 0.770184E+11            
Minimum of Months 0.225834E+10 0.203250E+10 13131.34   11818.21 11818.21 6.75 36.65
Maximum of Months 0.143434E+11 0.129091E+11 18989.58   17090.62 17090.62 8.13 89.37



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112050E+11 0.100845E+11 12871.09 02-JAN-04:02 11583.98 11583.98 6.72 90.21
February 0.862930E+10 0.776637E+10 12871.09 01-FEB-04:03 11583.98 11583.98 6.80 90.21
March 0.849840E+10 0.764856E+10 12871.09 01-MAR-06:05 11583.98 11583.98 6.95 90.21
April 0.141525E+11 0.127373E+11 12871.09 01-APR-05:03 11583.98 11583.98 6.83 90.21
May 0.156102E+11 0.140492E+11 12871.09 01-MAY-00:33 11583.98 11583.98 6.77 90.21
June 0.204901E+11 0.184411E+11 12871.09 01-JUN-05:02 11583.98 11583.98 7.11 90.21
July 0.262847E+11 0.236562E+11 12871.09 01-JUL-03:02 11583.98 11583.98 7.29 90.21
August 0.277236E+11 0.249512E+11 12871.09 01-AUG-00:52 11583.98 11583.98 6.88 90.21
September 0.199565E+11 0.179609E+11 12871.09 01-SEP-01:12 11583.98 11583.98 6.78 90.21
October 0.206846E+11 0.186162E+11 12871.09 01-OCT-06:12 11583.98 11583.98 6.95 90.21
November 0.128060E+11 0.115254E+11 12871.09 01-NOV-03:02 11583.98 11583.98 7.19 90.21
December 0.117070E+11 0.105363E+11 12871.09 01-DEC-06:03 11583.98 11583.98 6.87 90.21
                 
Annual Sum or Average 0.197748E+12 0.177973E+12            
Minimum of Months 0.849840E+10 0.764856E+10 12871.09   11583.98 11583.98 6.72 90.21
Maximum of Months 0.277236E+11 0.249512E+11 12871.09   11583.98 11583.98 7.29 90.21



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.893160E+10 0.803844E+10 3334.68 01-JAN-00:05 3001.21 3001.21 21.89 13.93
February 0.806725E+10 0.726052E+10 3334.68 01-FEB-00:10 3001.21 3001.21 24.55 13.93
March 0.893160E+10 0.803844E+10 3334.68 01-MAR-00:10 3001.21 3001.21 27.30 13.93
April 0.864348E+10 0.777913E+10 3334.68 01-APR-00:10 3001.21 3001.21 30.40 13.93
May 0.893160E+10 0.803844E+10 3334.68 01-MAY-00:10 3001.21 3001.21 22.58 13.93
June 0.864348E+10 0.777913E+10 3334.68 01-JUN-00:10 3001.21 3001.21 24.88 13.93
July 0.893160E+10 0.803844E+10 3334.68 01-JUL-00:10 3001.21 3001.21 29.94 13.93
August 0.893160E+10 0.803844E+10 3334.68 01-AUG-00:03 3001.21 3001.21 35.88 13.93
September 0.864348E+10 0.777913E+10 3334.68 01-SEP-00:03 3001.21 3001.21 22.58 13.93
October 0.893160E+10 0.803844E+10 3334.68 01-OCT-00:10 3001.21 3001.21 28.01 13.93
November 0.864348E+10 0.777913E+10 3334.68 01-NOV-00:10 3001.21 3001.21 28.21 13.93
December 0.893160E+10 0.803844E+10 3334.68 01-DEC-00:10 3001.21 3001.21 30.25 13.93
                 
Annual Sum or Average 0.105162E+12 0.946461E+11            
Minimum of Months 0.806725E+10 0.726052E+10 3334.68   3001.21 3001.21 21.89 13.93
Maximum of Months 0.893160E+10 0.803844E+10 3334.68   3001.21 3001.21 35.88 13.93



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 55.88 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:03 16.86 16.86 56.92 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 55.92 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 55.90 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 55.92 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:02 16.86 16.86 56.74 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 56.71 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:03 16.86 16.86 56.09 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 57.32 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.73 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 56.58 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:03 16.86 16.86 56.96 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.88 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.32 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.144555E+11 0.130100E+11 32012.72 13-JAN-13:50 28811.45 28811.45 25.83 106.27
February 0.108068E+11 0.972615E+10 32004.59 01-FEB-13:20 28804.13 28804.13 25.52 106.27
March 0.108183E+11 0.973647E+10 32015.68 23-MAR-13:50 28814.11 28814.11 25.94 106.27
April 0.183245E+11 0.164921E+11 32017.87 26-APR-13:40 28816.09 28816.09 26.02 106.27
May 0.199210E+11 0.179289E+11 32005.28 18-MAY-15:20 28804.75 28804.75 25.55 106.27
June 0.280683E+11 0.252615E+11 32067.06 29-JUN-13:00 28860.35 28860.35 27.85 106.27
July 0.397974E+11 0.358177E+11 32092.90 18-JUL-12:10 28883.61 28883.61 29.01 106.27
August 0.442270E+11 0.398043E+11 32092.90 07-AUG-09:20 28883.61 28883.61 28.87 106.27
September 0.294428E+11 0.264986E+11 32092.90 22-SEP-10:00 28883.61 28883.61 29.01 106.27
October 0.319580E+11 0.287622E+11 32092.90 03-OCT-13:20 28883.61 28883.61 29.49 106.27
November 0.163156E+11 0.146840E+11 32003.91 28-NOV-11:50 28803.52 28803.52 25.50 106.27
December 0.153388E+11 0.138049E+11 32004.98 18-DEC-13:10 28804.48 28804.48 25.54 106.27
                 
Annual Sum or Average 0.279474E+12 0.251527E+12            
Minimum of Months 0.108068E+11 0.972615E+10 32003.91   28803.52 28803.52 25.50 106.27
Maximum of Months 0.442270E+11 0.398043E+11 32092.90   28883.61 28883.61 29.49 106.27



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 82.00 82.00 26262.07 811333.50 02-JAN-06:01
February 0.00 0.00 01-FEB-00:10 35.95 35.95 20859.31 417537.49 10-FEB-07:10
March 0.00 0.00 01-MAR-00:10 46.41 46.41 28359.09 817124.51 30-MAR-05:03
April 0.00 0.00 01-APR-00:10 37.81 37.81 8157.52 458938.46 01-APR-06:10
May 0.00 0.00 01-MAY-00:10 27.13 27.13 5122.95 169544.12 15-MAY-06:10
June 0.00 0.00 01-JUN-00:10 26.20 26.20 507.53 124745.56 12-JUN-21:00
July 0.00 0.00 01-JUL-00:10 30.37 30.37 0.03 154.87 07-JUL-21:00
August 0.00 0.00 01-AUG-00:03 30.37 30.37 4.33 3491.72 28-AUG-07:00
September 0.00 0.00 01-SEP-00:03 30.01 30.01 402.70 93791.87 20-SEP-06:10
October 0.00 0.00 01-OCT-00:10 28.06 28.06 1577.79 265240.19 12-OCT-06:05
November 0.00 0.00 01-NOV-00:10 28.16 28.16 11196.40 318627.61 30-NOV-07:10
December 0.00 0.00 01-DEC-00:10 35.34 35.34 20819.63 520745.29 23-DEC-07:05
                 
Annual Sum or Average 0.00         10242.49    
Minimum of Months 0.00 0.00   26.20 26.20 0.03 154.87  
Maximum of Months 0.00 0.00   82.00 82.00 28359.09 817124.51  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 146408.74 1328627.50 13-JAN-14:00 10.21 6.70 0.00 0.00 01-JAN-00:05
February 96234.30 1152935.75 03-FEB-12:20 9.75 8.10 0.00 0.00 01-FEB-00:10
March 94455.42 1216619.57 23-MAR-13:50 9.92 6.70 0.00 0.00 01-MAR-00:10
April 212313.15 1243759.71 12-APR-14:00 9.99 6.70 0.00 0.00 01-APR-00:10
May 221395.34 1253185.81 03-MAY-13:00 10.01 6.70 0.00 0.00 01-MAY-00:10
June 348152.75 1517911.77 29-JUN-13:00 10.72 6.70 0.00 0.00 01-JUN-00:10
July 521288.72 1985103.15 31-JUL-15:50 11.95 6.70 0.00 0.00 01-JUL-00:10
August 592302.03 2001327.07 18-AUG-15:50 12.00 6.70 0.00 0.00 01-AUG-00:03
September 385792.86 1790777.20 29-SEP-12:20 11.44 6.70 0.00 0.00 01-SEP-00:03
October 424332.75 1852748.50 03-OCT-13:30 11.60 6.70 0.00 0.00 01-OCT-00:10
November 169304.21 1165884.92 08-NOV-12:30 9.78 8.12 0.00 0.00 01-NOV-00:10
December 168168.45 1225054.88 05-DEC-15:00 9.94 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 283233.82         0.00    
Minimum of Months 94455.42 1152935.75   9.75 6.70 0.00 0.00  
Maximum of Months 592302.03 2001327.07   12.00 8.12 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 95146.19 1327421.49 13-JAN-14:00 11.03 7.91 0.00 0.00 01-JAN-00:05
February 56173.18 1110276.85 01-FEB-12:00 16.01 7.92 0.00 0.00 01-FEB-00:10
March 57760.91 1210040.45 23-MAR-13:50 14.59 6.70 0.00 0.00 01-MAR-00:10
April 138219.21 1237860.10 12-APR-14:00 13.86 6.70 0.00 0.00 01-APR-00:10
May 140395.37 1244111.18 03-MAY-13:00 12.47 7.94 0.00 0.00 01-MAY-00:10
June 252385.29 1578196.13 30-JUN-05:03 14.56 6.86 0.00 0.00 01-JUN-00:10
July 415016.46 2189227.63 29-JUL-05:03 14.10 6.74 0.00 0.00 01-JUL-00:10
August 487379.89 2431179.96 07-AUG-05:02 14.58 7.04 0.00 0.00 01-AUG-00:03
September 293305.58 2403659.50 30-SEP-05:02 16.29 7.06 0.00 0.00 01-SEP-00:03
October 333481.04 2812206.03 05-OCT-05:03 14.22 6.75 0.00 0.00 01-OCT-00:10
November 105699.67 1420182.26 19-NOV-12:23 14.97 7.68 0.00 0.00 01-NOV-00:10
December 115924.18 1222812.73 05-DEC-15:00 14.97 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 208929.77         0.00    
Minimum of Months 56173.18 1110276.85   11.03 6.70 0.00 0.00  
Maximum of Months 487379.89 2812206.03   16.29 7.94 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 212913.89 660512.84 13-JAN-14:00 31.85 27.71 0.00 0.00 01-JAN-00:05
February 345277.26 869994.96 01-FEB-12:00 36.07 28.95 0.00 0.00 01-FEB-00:10
March 502179.87 975489.14 11-MAR-14:00 38.18 28.17 0.00 0.00 01-MAR-00:10
April 739587.98 1363370.23 26-APR-13:00 45.87 32.60 0.00 0.00 01-APR-00:10
May 232100.82 569275.70 03-MAY-13:00 30.00 25.75 0.00 0.00 01-MAY-00:10
June 458429.03 842990.15 29-JUN-11:00 35.53 28.08 0.00 0.00 01-JUN-00:10
July 742887.99 1234814.01 31-JUL-13:00 43.33 32.53 0.00 0.00 01-JUL-00:10
August 961780.97 1425758.93 14-AUG-11:00 47.09 33.67 0.00 0.00 01-AUG-00:03
September 304630.97 1206350.36 29-SEP-13:00 42.77 38.00 0.00 0.00 01-SEP-00:03
October 527572.46 1498438.32 16-OCT-11:00 48.52 40.43 0.00 0.00 01-OCT-00:10
November 539601.56 1140845.15 19-NOV-13:00 41.47 31.27 0.00 0.00 01-NOV-00:10
December 710954.16 1291884.46 19-DEC-13:00 44.46 31.47 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 524759.85         0.00    
Minimum of Months 212913.89 569275.70   30.00 25.75 0.00 0.00  
Maximum of Months 961780.97 1498438.32   48.52 40.43 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.42 57.42 13761.22 45604.66 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 57.31 57.31 13850.03 45610.16 02-FEB-12:30
March 0.00 0.00 01-MAR-00:10 56.48 56.48 14479.53 45388.87 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.45 56.45 13398.11 44586.71 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 56.62 56.62 13487.12 43620.80 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 57.21 57.21 13496.54 42534.91 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 57.22 57.22 12365.30 41693.94 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 56.58 56.58 13385.15 41613.85 31-AUG-11:20
September 0.00 0.00 01-SEP-00:03 57.65 57.65 12778.31 42289.81 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.56 57.56 13013.81 43383.91 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 57.12 57.12 13485.38 44436.83 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 57.44 57.44 13306.31 45227.38 29-DEC-12:50
                 
Annual Sum or Average 0.00         13398.09    
Minimum of Months 0.00 0.00   56.45 56.45 12365.30 41613.85  
Maximum of Months 0.00 0.00   57.65 57.65 14479.53 45610.16  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 106766.44 2099476.79 13-JAN-13:50 25.83 21.36 959.92 90861.30 04-JAN-06:40
February 62682.99 1964910.99 01-FEB-13:20 25.52 21.10 664.88 92724.52 06-FEB-06:30
March 66631.05 2148432.22 23-MAR-13:50 25.94 22.11 387.17 71153.54 31-MAR-05:40
April 152771.35 2184802.58 26-APR-13:40 26.02 22.03 293.37 67152.59 01-APR-05:50
May 152648.04 1976255.02 18-MAY-15:20 25.55 21.10 208.05 47366.38 24-MAY-05:30
June 309385.17 2997583.62 29-JUN-13:00 27.85 23.88 127.57 29780.78 22-JUN-20:10
July 636625.77 4249943.31 31-JUL-13:00 30.67 25.98 99.10 28108.21 17-JUL-06:00
August 777221.25 4242209.77 17-AUG-14:10 30.65 25.95 106.17 29867.54 21-AUG-20:20
September 393499.55 3903193.36 22-SEP-12:30 29.89 25.42 219.48 34800.05 15-SEP-20:00
October 459594.30 3838963.26 03-OCT-13:30 29.74 24.86 262.75 52881.51 27-OCT-06:00
November 113929.32 1953586.26 28-NOV-11:50 25.50 21.10 709.68 76819.85 30-NOV-06:50
December 126803.10 1971356.46 18-DEC-13:10 25.54 21.10 833.38 93099.85 28-DEC-06:30
                 
Annual Sum or Average 282075.82         404.58    
Minimum of Months 62682.99 1953586.26   25.50 21.10 99.10 28108.21  
Maximum of Months 777221.25 4249943.31   30.67 25.98 959.92 93099.85  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.236170E+10 0.00 0.207122E+11 0.713698E+10 0.00 0.00
February 0.100927E+10 0.00 0.121801E+11 0.694513E+10 0.00 0.00
March 0.155987E+10 0.00 0.147850E+11 0.890471E+10 0.00 0.00
April 42037811.24 0.00 0.333266E+11 0.107086E+11 0.00 0.00
May 0.130064E+09 0.00 0.301885E+11 0.836995E+10 0.00 0.00
June 0.00 0.00 0.561840E+11 0.100582E+11 0.00 0.00
July 0.00 0.00 0.104123E+12 0.118191E+11 0.00 0.00
August 0.00 0.00 0.128606E+12 0.140552E+11 0.00 0.00
September 0.00 0.00 0.636230E+11 0.921968E+10 0.00 0.00
October 12770830.23 0.00 0.784053E+11 0.968026E+10 0.00 0.00
November 0.112780E+09 0.00 0.253077E+11 0.900659E+10 0.00 0.00
December 0.924681E+09 0.00 0.295185E+11 0.895690E+10 0.00 0.00
             
Annual Sum or Average 0.615317E+10 0.00 0.596959E+12 0.114861E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.121801E+11 0.694513E+10 0.00 0.00
Maximum of Months 0.236170E+10 0.00 0.128606E+12 0.140552E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.582259E+11 0.00 0.172506E+12 0.495175E+11 0.00 0.00
February 0.418170E+11 0.00 0.939737E+11 0.456579E+11 0.00 0.00
March 0.636736E+11 0.00 0.106589E+12 0.532505E+11 0.00 0.00
April 0.184511E+11 0.00 0.237220E+12 0.619449E+11 0.00 0.00
May 0.119782E+11 0.00 0.250196E+12 0.631051E+11 0.00 0.00
June 0.111014E+10 0.00 0.454366E+12 0.730499E+11 0.00 0.00
July 0.00 0.00 0.799079E+12 0.798750E+11 0.00 0.00
August 0.00 0.00 0.945120E+12 0.906323E+11 0.00 0.00
September 0.883495E+09 0.00 0.544737E+12 0.727225E+11 0.00 0.00
October 0.355187E+10 0.00 0.638222E+12 0.683322E+11 0.00 0.00
November 0.245383E+11 0.00 0.183258E+12 0.546350E+11 0.00 0.00
December 0.468200E+11 0.00 0.207585E+12 0.502046E+11 0.00 0.00
             
Annual Sum or Average 0.271050E+12 0.00 0.463285E+13 0.762927E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.939737E+11 0.456579E+11 0.00 0.00
Maximum of Months 0.636736E+11 0.00 0.945120E+12 0.906323E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.105980E+11 0.00 0.131388E+11 0.380114E+10 0.00 0.00
February 0.807123E+10 0.00 0.740741E+10 0.354472E+10 0.00 0.00
March 0.114794E+11 0.00 0.918160E+10 0.423762E+10 0.00 0.00
April 0.288330E+10 0.00 0.233213E+11 0.548970E+10 0.00 0.00
May 0.174125E+10 0.00 0.245790E+11 0.559796E+10 0.00 0.00
June 0.201891E+09 0.00 0.472310E+11 0.704032E+10 0.00 0.00
July 116948.42 0.00 0.858566E+11 0.822852E+10 0.00 0.00
August 12978636.37 0.00 0.100159E+12 0.910614E+10 0.00 0.00
September 0.176842E+09 0.00 0.536031E+11 0.661569E+10 0.00 0.00
October 0.699482E+09 0.00 0.612202E+11 0.594331E+10 0.00 0.00
November 0.461150E+10 0.00 0.141092E+11 0.405523E+10 0.00 0.00
December 0.856492E+10 0.00 0.160405E+11 0.379781E+10 0.00 0.00
             
Annual Sum or Average 0.490409E+11 0.00 0.455848E+12 0.674582E+11 0.00 0.00
Minimum of Months 116948.42 0.00 0.740741E+10 0.354472E+10 0.00 0.00
Maximum of Months 0.114794E+11 0.00 0.100159E+12 0.910614E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 107.33 0.00 0.121005E+11 0.169526E+11 0.00 0.00
February 80.47 0.00 0.537816E+10 0.147321E+11 0.00 0.00
March 0.00 0.00 0.624411E+10 0.169401E+11 0.00 0.00
April 0.00 0.00 0.160624E+11 0.155451E+11 0.00 0.00
May 0.00 0.00 0.156200E+11 0.164257E+11 0.00 0.00
June 0.00 0.00 0.285060E+11 0.163888E+11 0.00 0.00
July 0.00 0.00 0.484688E+11 0.156377E+11 0.00 0.00
August 0.00 0.00 0.562466E+11 0.171897E+11 0.00 0.00
September 0.00 0.00 0.340179E+11 0.161062E+11 0.00 0.00
October 0.00 0.00 0.440538E+11 0.168618E+11 0.00 0.00
November 0.00 0.00 0.134614E+11 0.163479E+11 0.00 0.00
December 0.00 0.00 0.166741E+11 0.165075E+11 0.00 0.00
             
Annual Sum or Average 187.80 0.00 0.296834E+12 0.195635E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.537816E+10 0.147321E+11 0.00 0.00
Maximum of Months 107.33 0.00 0.562466E+11 0.171897E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.414925E+12 0.180118E+12 0.00 0.17
February 0.00 0.00 0.642118E+12 0.210563E+12 0.00 0.14
March 0.00 0.00 0.100921E+13 0.285415E+12 0.00 0.01
April 0.00 0.00 0.127566E+13 0.336216E+12 0.00 0.03
May 0.00 0.00 0.418193E+12 0.180272E+12 0.00 0.00
June 0.00 0.00 0.704947E+12 0.235043E+12 0.00 0.00
July 0.00 0.00 0.104854E+13 0.314551E+12 0.00 0.00
August 0.00 0.00 0.135857E+13 0.380411E+12 0.00 0.00
September 0.00 0.00 0.415529E+12 0.179554E+12 0.00 0.00
October 0.00 0.00 0.737725E+12 0.251346E+12 0.00 0.07
November 0.00 0.00 0.985423E+12 0.282098E+12 0.00 0.22
December 0.00 0.00 0.131613E+13 0.346709E+12 0.00 0.40
             
Annual Sum or Average 0.00 0.00 0.103270E+14 0.318230E+13 0.00 1.03
Minimum of Months 0.00 0.00 0.414925E+12 0.179554E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.135857E+13 0.380411E+12 0.00 0.40



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.654934E+10 0.275747E+10 0.00 0.00
February 0.00 0.00 0.116257E+11 0.351629E+10 0.00 0.00
March 0.00 0.00 0.191254E+11 0.497683E+10 0.00 0.00
April 0.00 0.00 0.249128E+11 0.607371E+10 0.00 0.00
May 0.00 0.00 0.705635E+10 0.284209E+10 0.00 0.00
June 0.00 0.00 0.133298E+11 0.403147E+10 0.00 0.00
July 0.00 0.00 0.204424E+11 0.562021E+10 0.00 0.00
August 0.00 0.00 0.268220E+11 0.696040E+10 0.00 0.00
September 0.00 0.00 0.727236E+10 0.288483E+10 0.00 0.00
October 0.00 0.00 0.138695E+11 0.431800E+10 0.00 0.00
November 0.00 0.00 0.188188E+11 0.496125E+10 0.00 0.00
December 0.00 0.00 0.255440E+11 0.626928E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.195368E+12 0.552118E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.654934E+10 0.275747E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.268220E+11 0.696040E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.500121E+11 0.239024E+11 0.00 0.00
February 0.00 0.00 0.100486E+12 0.316698E+11 0.00 0.00
March 0.00 0.00 0.172069E+12 0.457070E+11 0.00 0.00
April 0.00 0.00 0.232286E+12 0.570154E+11 0.00 0.00
May 0.00 0.00 0.611116E+11 0.259170E+11 0.00 0.00
June 0.00 0.00 0.123194E+12 0.377058E+11 0.00 0.00
July 0.00 0.00 0.193359E+12 0.532656E+11 0.00 0.00
August 0.00 0.00 0.254452E+12 0.660904E+11 0.00 0.00
September 0.00 0.00 0.646138E+11 0.265757E+11 0.00 0.00
October 0.00 0.00 0.126350E+12 0.400457E+11 0.00 0.00
November 0.00 0.00 0.170185E+12 0.456983E+11 0.00 0.00
December 0.00 0.00 0.232358E+12 0.578983E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.178048E+13 0.511491E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.500121E+11 0.239024E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.254452E+12 0.660904E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.339590E+10 0.210446E+10 0.00 0.00
February 0.00 0.00 0.873993E+10 0.295872E+10 0.00 0.00
March 0.00 0.00 0.160079E+11 0.440099E+10 0.00 0.00
April 0.00 0.00 0.226217E+11 0.563936E+10 0.00 0.00
May 0.00 0.00 0.546771E+10 0.250026E+10 0.00 0.00
June 0.00 0.00 0.120467E+11 0.375348E+10 0.00 0.00
July 0.00 0.00 0.192482E+11 0.534781E+10 0.00 0.00
August 0.00 0.00 0.253216E+11 0.662787E+10 0.00 0.00
September 0.00 0.00 0.607643E+10 0.261415E+10 0.00 0.00
October 0.00 0.00 0.120321E+11 0.392646E+10 0.00 0.00
November 0.00 0.00 0.158047E+11 0.439310E+10 0.00 0.00
December 0.00 0.00 0.217255E+11 0.557472E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.168488E+12 0.498414E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.339590E+10 0.210446E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.253216E+11 0.662787E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.713698E+10 0.207122E+11 0.236170E+10 0.00 0.00 0.00 0.00 0.00
February 0.694513E+10 0.121801E+11 0.100927E+10 0.00 0.00 0.00 0.00 0.00
March 0.890471E+10 0.147850E+11 0.155987E+10 0.00 0.00 0.00 0.00 0.00
April 0.107086E+11 0.333266E+11 42037811.24 0.00 0.00 0.00 0.00 0.00
May 0.836995E+10 0.301885E+11 0.130064E+09 0.00 0.00 0.00 0.00 0.00
June 0.100582E+11 0.561840E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.118191E+11 0.104123E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140552E+11 0.128606E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.921968E+10 0.636230E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.968026E+10 0.784053E+11 12770830.23 0.00 0.00 0.00 0.00 0.00
November 0.900659E+10 0.253077E+11 0.112780E+09 0.00 0.00 0.00 0.00 0.00
December 0.895690E+10 0.295185E+11 0.924681E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114861E+12 0.596959E+12 0.615317E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.694513E+10 0.121801E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140552E+11 0.128606E+12 0.236170E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.495175E+11 0.172506E+12 0.582259E+11 0.00 0.00 0.00 0.00 0.00
February 0.456579E+11 0.939737E+11 0.418170E+11 0.00 0.00 0.00 0.00 0.00
March 0.532505E+11 0.106589E+12 0.636736E+11 0.00 0.00 0.00 0.00 0.00
April 0.619449E+11 0.237220E+12 0.184511E+11 0.00 0.00 0.00 0.00 0.00
May 0.631051E+11 0.250196E+12 0.119782E+11 0.00 0.00 0.00 0.00 0.00
June 0.730499E+11 0.454366E+12 0.111014E+10 0.00 0.00 0.00 0.00 0.00
July 0.798750E+11 0.799079E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.906323E+11 0.945120E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.727225E+11 0.544737E+12 0.883495E+09 0.00 0.00 0.00 0.00 0.00
October 0.683322E+11 0.638222E+12 0.355187E+10 0.00 0.00 0.00 0.00 0.00
November 0.546350E+11 0.183258E+12 0.245383E+11 0.00 0.00 0.00 0.00 0.00
December 0.502046E+11 0.207585E+12 0.468200E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.762927E+12 0.463285E+13 0.271050E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.456579E+11 0.939737E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.906323E+11 0.945120E+12 0.636736E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.380114E+10 0.131388E+11 0.105980E+11 0.00 0.00 0.00 0.00 0.00
February 0.354472E+10 0.740741E+10 0.807123E+10 0.00 0.00 0.00 0.00 0.00
March 0.423762E+10 0.918160E+10 0.114794E+11 0.00 0.00 0.00 0.00 0.00
April 0.548970E+10 0.233213E+11 0.288330E+10 0.00 0.00 0.00 0.00 0.00
May 0.559796E+10 0.245790E+11 0.174125E+10 0.00 0.00 0.00 0.00 0.00
June 0.704032E+10 0.472310E+11 0.201891E+09 0.00 0.00 0.00 0.00 0.00
July 0.822852E+10 0.858566E+11 116948.42 0.00 0.00 0.00 0.00 0.00
August 0.910614E+10 0.100159E+12 12978636.37 0.00 0.00 0.00 0.00 0.00
September 0.661569E+10 0.536031E+11 0.176842E+09 0.00 0.00 0.00 0.00 0.00
October 0.594331E+10 0.612202E+11 0.699482E+09 0.00 0.00 0.00 0.00 0.00
November 0.405523E+10 0.141092E+11 0.461150E+10 0.00 0.00 0.00 0.00 0.00
December 0.379781E+10 0.160405E+11 0.856492E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.674582E+11 0.455848E+12 0.490409E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.354472E+10 0.740741E+10 116948.42 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.910614E+10 0.100159E+12 0.114794E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.169526E+11 0.121005E+11 107.33 0.00 0.00 0.00 0.00 0.00
February 0.147321E+11 0.537816E+10 80.47 0.00 0.00 0.00 0.00 0.00
March 0.169401E+11 0.624411E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.155451E+11 0.160624E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.164257E+11 0.156200E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163888E+11 0.285060E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.156377E+11 0.484688E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171897E+11 0.562466E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.161062E+11 0.340179E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.168618E+11 0.440538E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163479E+11 0.134614E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.165075E+11 0.166741E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.195635E+12 0.296834E+12 187.80 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147321E+11 0.537816E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171897E+11 0.562466E+11 107.33 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.957710E+11 0.331040E+12 0.00 0.00 0.00 0.459721E+09 0.00 0.00
February 0.865029E+11 0.518421E+12 0.00 0.00 0.00 0.361522E+09 0.00 0.00
March 0.957710E+11 0.819587E+12 0.00 0.00 0.00 19128872.30 0.00 0.00
April 0.926817E+11 0.103220E+13 0.00 0.00 0.00 68698826.08 0.00 0.00
May 0.957710E+11 0.333693E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.926817E+11 0.562586E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.957710E+11 0.829763E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.957710E+11 0.107393E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.926817E+11 0.328657E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.957710E+11 0.582342E+12 0.00 0.00 0.00 0.191037E+09 0.00 0.00
November 0.926817E+11 0.796594E+12 0.00 0.00 0.00 0.584381E+09 0.00 0.00
December 0.957710E+11 0.106628E+13 0.00 0.00 0.00 0.107485E+10 0.00 0.00
                 
Annual Sum or Average 0.112763E+13 0.827508E+13 0.00 0.00 0.00 0.275934E+10 0.00 0.00
Minimum of Months 0.865029E+11 0.328657E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.957710E+11 0.107393E+13 0.00 0.00 0.00 0.107485E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.143240E+10 0.522427E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129378E+10 0.940320E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143240E+10 0.155809E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138619E+10 0.202252E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143240E+10 0.564666E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138619E+10 0.106846E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143240E+10 0.162546E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143240E+10 0.212940E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138619E+10 0.577372E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143240E+10 0.109838E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138619E+10 0.152437E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143240E+10 0.207071E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.168653E+11 0.157022E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129378E+10 0.522427E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143240E+10 0.212940E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.136253E+11 0.397351E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.123067E+11 0.811230E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.136253E+11 0.139988E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131858E+11 0.188456E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.136253E+11 0.488200E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131858E+11 0.986743E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.136253E+11 0.153719E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.136253E+11 0.201986E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131858E+11 0.512239E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.136253E+11 0.999301E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131858E+11 0.137672E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.136253E+11 0.188085E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160427E+12 0.142941E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.123067E+11 0.397351E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136253E+11 0.201986E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138943E+10 0.268086E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125497E+10 0.703618E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138943E+10 0.129964E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134461E+10 0.183270E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138943E+10 0.435687E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134461E+10 0.963787E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138943E+10 0.152898E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138943E+10 0.200832E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134461E+10 0.480689E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138943E+10 0.949510E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134461E+10 0.127562E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138943E+10 0.175402E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163594E+11 0.135006E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125497E+10 0.268086E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138943E+10 0.200832E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.713698E+10 0.236170E+10 0.207122E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.694513E+10 0.100927E+10 0.121801E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.890471E+10 0.155987E+10 0.147850E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.107086E+11 42037811.24 0.333266E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.836995E+10 0.130064E+09 0.301885E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.100582E+11 0.00 0.561840E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.118191E+11 0.00 0.104123E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140552E+11 0.00 0.128606E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.921968E+10 0.00 0.636230E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.968026E+10 12770830.23 0.784053E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.900659E+10 0.112780E+09 0.253077E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.895690E+10 0.924681E+09 0.295185E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.114861E+12 0.615317E+10 0.596959E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.694513E+10 0.00 0.121801E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140552E+11 0.236170E+10 0.128606E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.495175E+11 0.582259E+11 0.172506E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.456579E+11 0.418170E+11 0.939737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.532505E+11 0.636736E+11 0.106589E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.619449E+11 0.184511E+11 0.237220E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.631051E+11 0.119782E+11 0.250196E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.730499E+11 0.111014E+10 0.454366E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.798750E+11 0.00 0.799079E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.906323E+11 0.00 0.945120E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.727225E+11 0.883495E+09 0.544737E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.683322E+11 0.355187E+10 0.638222E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.546350E+11 0.245383E+11 0.183258E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.502046E+11 0.468200E+11 0.207585E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.762927E+12 0.271050E+12 0.463285E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.456579E+11 0.00 0.939737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.906323E+11 0.636736E+11 0.945120E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.380114E+10 0.105980E+11 0.131388E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.354472E+10 0.807123E+10 0.740741E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.423762E+10 0.114794E+11 0.918160E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.548970E+10 0.288330E+10 0.233213E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.559796E+10 0.174125E+10 0.245790E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.704032E+10 0.201891E+09 0.472310E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.822852E+10 116948.42 0.858566E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.910614E+10 12978636.37 0.100159E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.661569E+10 0.176842E+09 0.536031E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.594331E+10 0.699482E+09 0.612202E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.405523E+10 0.461150E+10 0.141092E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.379781E+10 0.856492E+10 0.160405E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.674582E+11 0.490409E+11 0.455848E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.354472E+10 116948.42 0.740741E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.910614E+10 0.114794E+11 0.100159E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.169526E+11 107.33 0.121005E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.147321E+11 80.47 0.537816E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.169401E+11 0.00 0.624411E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.155451E+11 0.00 0.160624E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.164257E+11 0.00 0.156200E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.163888E+11 0.00 0.285060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.156377E+11 0.00 0.484688E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171897E+11 0.00 0.562466E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.161062E+11 0.00 0.340179E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.168618E+11 0.00 0.440538E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.163479E+11 0.00 0.134614E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.165075E+11 0.00 0.166741E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.195635E+12 187.80 0.296834E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.147321E+11 0.00 0.537816E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171897E+11 107.33 0.562466E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.957710E+11 0.00 0.414925E+12 0.00 0.838854E+11 0.00 0.00 0.00 0.461790E+09 0.00 0.00 0.00
February 0.865029E+11 0.00 0.642118E+12 0.00 0.123697E+12 0.00 0.00 0.00 0.363149E+09 0.00 0.00 0.00
March 0.957710E+11 0.00 0.100921E+13 0.00 0.189624E+12 0.00 0.00 0.00 19214979.11 0.00 0.00 0.00
April 0.926817E+11 0.00 0.127566E+13 0.00 0.243465E+12 0.00 0.00 0.00 69008067.34 0.00 0.00 0.00
May 0.957710E+11 0.00 0.418193E+12 0.00 0.845005E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.926817E+11 0.00 0.704947E+12 0.00 0.142361E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.957710E+11 0.00 0.104854E+13 0.00 0.218780E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.957710E+11 0.00 0.135857E+13 0.00 0.284640E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.926817E+11 0.00 0.415529E+12 0.00 0.868723E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.957710E+11 0.00 0.737725E+12 0.00 0.155383E+12 0.00 0.00 0.00 0.191897E+09 0.00 0.00 0.00
November 0.926817E+11 0.00 0.985423E+12 0.00 0.188830E+12 0.00 0.00 0.00 0.587012E+09 0.00 0.00 0.00
December 0.957710E+11 0.00 0.131613E+13 0.00 0.249858E+12 0.00 0.00 0.00 0.107969E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.112763E+13 0.00 0.103270E+14 0.00 0.205190E+13 0.00 0.00 0.00 0.277176E+10 0.00 0.00 0.00
Minimum of Months 0.865029E+11 0.00 0.414925E+12 0.00 0.838854E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.957710E+11 0.00 0.135857E+13 0.00 0.284640E+12 0.00 0.00 0.00 0.107969E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.143240E+10 0.00 0.654934E+10 0.00 0.132507E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129378E+10 0.00 0.116257E+11 0.00 0.222251E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143240E+10 0.00 0.191254E+11 0.00 0.354443E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138619E+10 0.00 0.249128E+11 0.00 0.468752E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143240E+10 0.00 0.705635E+10 0.00 0.140969E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138619E+10 0.00 0.133298E+11 0.00 0.264527E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143240E+10 0.00 0.204424E+11 0.00 0.418781E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143240E+10 0.00 0.268220E+11 0.00 0.552801E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.138619E+10 0.00 0.727236E+10 0.00 0.149864E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143240E+10 0.00 0.138695E+11 0.00 0.288560E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138619E+10 0.00 0.188188E+11 0.00 0.357506E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143240E+10 0.00 0.255440E+11 0.00 0.483688E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.168653E+11 0.00 0.195368E+12 0.00 0.383465E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129378E+10 0.00 0.654934E+10 0.00 0.132507E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143240E+10 0.00 0.268220E+11 0.00 0.552801E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.136253E+11 0.00 0.500121E+11 0.00 0.102771E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.123067E+11 0.00 0.100486E+12 0.00 0.193630E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.136253E+11 0.00 0.172069E+12 0.00 0.320817E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131858E+11 0.00 0.232286E+12 0.00 0.438296E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.136253E+11 0.00 0.611116E+11 0.00 0.122916E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131858E+11 0.00 0.123194E+12 0.00 0.245200E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.136253E+11 0.00 0.193359E+12 0.00 0.396403E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.136253E+11 0.00 0.254452E+12 0.00 0.524651E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131858E+11 0.00 0.646138E+11 0.00 0.133899E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.136253E+11 0.00 0.126350E+12 0.00 0.264204E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131858E+11 0.00 0.170185E+12 0.00 0.325125E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.136253E+11 0.00 0.232358E+12 0.00 0.442730E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.160427E+12 0.00 0.178048E+13 0.00 0.351064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.123067E+11 0.00 0.500121E+11 0.00 0.102771E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136253E+11 0.00 0.254452E+12 0.00 0.524651E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138943E+10 0.00 0.339590E+10 0.00 0.715037E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125497E+10 0.00 0.873993E+10 0.00 0.170376E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138943E+10 0.00 0.160079E+11 0.00 0.301156E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134461E+10 0.00 0.226217E+11 0.00 0.429476E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138943E+10 0.00 0.546771E+10 0.00 0.111083E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134461E+10 0.00 0.120467E+11 0.00 0.240887E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138943E+10 0.00 0.192482E+11 0.00 0.395838E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138943E+10 0.00 0.253216E+11 0.00 0.523844E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134461E+10 0.00 0.607643E+10 0.00 0.126954E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138943E+10 0.00 0.120321E+11 0.00 0.253704E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134461E+10 0.00 0.158047E+11 0.00 0.304849E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138943E+10 0.00 0.217255E+11 0.00 0.418530E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.163594E+11 0.00 0.168488E+12 0.00 0.334820E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125497E+10 0.00 0.339590E+10 0.00 0.715037E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138943E+10 0.00 0.253216E+11 0.00 0.523844E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.540138E+09 93268399.34 0.00 0.119951E+09 0.00 0.00 0.678443E+11 0.00 1.24
February 0.370586E+09 5300542.89 0.00 0.101848E+09 0.00 0.00 0.642592E+11 0.00 1.23
March 0.308466E+09 0.00 0.00 0.118770E+09 0.00 0.00 0.758317E+11 0.00 1.26
April 0.240115E+09 9731625.54 0.00 0.112469E+09 0.00 0.00 0.602310E+11 0.00 1.38
May 0.271318E+09 4268669.93 0.00 0.112292E+09 0.00 0.00 0.629137E+11 0.00 1.45
June 0.181067E+09 0.177347E+09 0.00 0.113140E+09 0.00 0.00 0.512422E+11 0.00 1.62
July 0.162656E+09 0.255887E+10 0.00 96568563.10 0.00 0.00 0.329016E+11 0.00 1.40
August 0.151041E+09 0.325392E+10 0.00 0.102497E+09 0.00 0.00 0.341337E+11 0.00 1.54
September 0.244729E+09 0.117902E+10 0.00 0.109256E+09 31436097.51 0.00 0.455872E+11 0.00 1.52
October 0.308478E+09 0.291159E+10 0.00 0.107308E+09 20847139.15 0.00 0.426812E+11 0.00 1.40
November 0.359653E+09 11240089.23 0.00 0.125019E+09 0.00 0.00 0.686525E+11 0.00 1.36
December 0.564176E+09 1049088.24 0.00 0.124200E+09 0.00 0.00 0.643441E+11 0.00 1.24
                   
Annual Sum or Average 0.370242E+10 0.102056E+11 0.00 0.134332E+10 52283236.66 0.00 0.670622E+12 0.00 1.39
Minimum of Months 0.151041E+09 0.00 0.00 96568563.10 0.00 0.00 0.329016E+11 0.00 1.23
Maximum of Months 0.564176E+09 0.325392E+10 0.00 0.125019E+09 31436097.51 0.00 0.758317E+11 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.275348E+10 82668194.57 0.00 88614767.37 18615916.20 0.00 0.470981E+11 0.00 0.84
February 0.344142E+10 22238397.39 0.00 82166804.48 0.00 0.00 0.474460E+11 0.00 0.90
March 0.327283E+10 0.00 0.00 0.102140E+09 9010515.32 0.00 0.603072E+11 0.00 0.99
April 0.693745E+10 14870613.75 0.00 98608795.99 39132122.45 0.00 0.481072E+11 0.00 1.13
May 0.396645E+10 34984088.89 0.00 91814034.38 0.00 0.00 0.448126E+11 0.00 1.01
June 0.378772E+10 0.745826E+09 0.00 92622705.69 0.00 0.00 0.359210E+11 0.00 1.16
July 0.742332E+10 0.601697E+10 0.00 63301828.18 0.315741E+09 0.00 0.173415E+11 0.00 1.18
August 0.629993E+10 0.821036E+10 0.00 63038628.38 0.368460E+09 0.00 0.162778E+11 0.00 1.31
September 0.317154E+10 0.180732E+10 0.00 79566992.08 53271911.96 0.00 0.281489E+11 0.00 1.03
October 0.318790E+10 0.368536E+10 0.00 76012770.92 0.266098E+09 0.00 0.272729E+11 0.00 1.00
November 0.386904E+10 12115442.44 0.00 98961233.83 13106353.29 0.00 0.512124E+11 0.00 1.02
December 0.468298E+10 5193857.26 0.00 0.102044E+09 0.00 0.00 0.493306E+11 0.00 0.96
                   
Annual Sum or Average 0.527941E+11 0.206379E+11 0.00 0.103889E+10 0.108344E+10 0.00 0.473276E+12 0.00 1.04
Minimum of Months 0.275348E+10 0.00 0.00 63038628.38 0.00 0.00 0.162778E+11 0.00 0.84
Maximum of Months 0.742332E+10 0.821036E+10 0.00 0.102140E+09 0.368460E+09 0.00 0.603072E+11 0.00 1.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.397382E+11 0.450440E+09 0.00 0.585170E+09 0.460830E+09 0.00 0.338918E+12 0.00 0.67
February 0.289177E+11 0.226713E+09 0.00 0.552760E+09 0.00 0.00 0.350880E+12 0.00 0.70
March 0.258331E+11 0.00 0.00 0.649032E+09 0.283650E+09 0.00 0.434602E+12 0.00 0.74
April 0.243517E+11 0.122852E+09 0.00 0.684566E+09 0.410981E+09 0.00 0.347549E+12 0.00 0.80
May 0.226625E+11 0.373577E+09 0.00 0.741767E+09 0.00 0.00 0.370409E+12 0.00 0.84
June 0.184477E+11 0.538533E+10 0.00 0.759739E+09 0.00 0.00 0.289883E+12 0.00 0.93
July 0.243180E+11 0.456177E+11 0.00 0.513471E+09 0.211344E+10 0.00 0.138188E+12 0.00 0.87
August 0.137271E+11 0.570702E+11 0.00 0.531635E+09 0.245796E+10 0.00 0.130326E+12 0.00 0.94
September 0.188507E+11 0.172500E+11 0.00 0.651255E+09 0.523121E+09 0.00 0.232975E+12 0.00 0.86
October 0.168684E+11 0.324260E+11 0.00 0.579826E+09 0.207103E+10 0.00 0.206953E+12 0.00 0.79
November 0.204517E+11 0.155261E+09 0.00 0.665491E+09 0.180111E+09 0.00 0.368973E+12 0.00 0.74
December 0.281076E+11 79218258.55 0.00 0.601733E+09 36533514.74 0.00 0.333604E+12 0.00 0.67
                   
Annual Sum or Average 0.282274E+12 0.159157E+12 0.00 0.751645E+10 0.853766E+10 0.00 0.354326E+13 0.00 0.80
Minimum of Months 0.137271E+11 0.00 0.00 0.513471E+09 0.00 0.00 0.130326E+12 0.00 0.67
Maximum of Months 0.397382E+11 0.570702E+11 0.00 0.759739E+09 0.245796E+10 0.00 0.434602E+12 0.00 0.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.139074E+11 5851259.30 0.00 25508196.74 68674962.24 0.240109E+09 0.150207E+11 0.00 0.55
February 0.114928E+11 9421656.84 0.00 26463906.72 0.00 1652581.12 0.184531E+11 0.00 0.58
March 0.129811E+11 0.00 0.00 33045247.84 51159.52 0.00 0.248268E+11 0.00 0.63
April 0.605652E+10 516911.47 0.00 49888732.33 20959750.13 0.00 0.282193E+11 0.00 0.74
May 0.573051E+10 12146490.88 0.00 55176348.69 0.00 0.00 0.302949E+11 0.00 0.78
June 0.253083E+10 0.245572E+09 0.00 67482951.80 0.00 0.00 0.273757E+11 0.00 0.91
July 0.208326E+10 0.385456E+10 0.00 52283852.61 0.164711E+09 0.00 0.137322E+11 0.00 0.89
August 0.881589E+09 0.504141E+10 0.00 53777705.84 0.146591E+09 0.00 0.122652E+11 0.00 0.96
September 0.264174E+10 0.127521E+10 0.00 55059906.97 45828584.86 0.00 0.200794E+11 0.00 0.80
October 0.397837E+10 0.267144E+10 0.00 39309973.53 0.209507E+09 0.00 0.137868E+11 0.00 0.71
November 0.914665E+10 838653.28 0.00 33645598.90 18867076.90 0.00 0.208932E+11 0.00 0.61
December 0.124578E+11 1650921.39 0.00 26505253.43 9930138.42 1543173.57 0.146085E+11 0.00 0.54
                   
Annual Sum or Average 0.838885E+11 0.131186E+11 0.00 0.518148E+09 0.685120E+09 0.243305E+09 0.239556E+12 0.00 0.72
Minimum of Months 0.881589E+09 0.00 0.00 25508196.74 0.00 0.00 0.122652E+11 0.00 0.54
Maximum of Months 0.139074E+11 0.504141E+10 0.00 67482951.80 0.209507E+09 0.240109E+09 0.302949E+11 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.263993E+10 10665014.41 0.00 4142744.98 2978778.65 0.00 0.226370E+10 0.00 0.66
February 0.234167E+10 2662727.57 0.00 4380791.56 0.00 0.00 0.283645E+10 0.00 0.73
March 0.226205E+10 0.00 0.00 6050236.88 1340808.94 0.00 0.413311E+10 0.00 0.81
April 0.188699E+10 1905022.94 0.00 8108521.59 5823052.06 0.00 0.435078E+10 0.00 1.05
May 0.144413E+10 5042161.30 0.00 8311209.15 0.00 0.00 0.444947E+10 0.00 1.00
June 0.768262E+09 0.113357E+09 0.00 10513491.87 0.00 0.00 0.435442E+10 0.00 1.25
July 0.121823E+10 0.958137E+09 0.00 7207174.05 46983868.79 0.00 0.206108E+10 0.00 1.34
August 0.106350E+10 0.123745E+10 0.00 6329108.44 54828682.03 0.00 0.170437E+10 0.00 1.40
September 0.896203E+09 0.286804E+09 0.00 6701307.94 7927122.19 0.00 0.269924E+10 0.00 1.01
October 0.110133E+10 0.554298E+09 0.00 5732051.07 39755731.35 0.00 0.219348E+10 0.00 0.94
November 0.207468E+10 1418088.73 0.00 5947612.31 1950289.75 0.00 0.340888E+10 0.00 0.82
December 0.241046E+10 608367.23 0.00 5442625.91 0.00 0.00 0.273783E+10 0.00 0.74
                   
Annual Sum or Average 0.201074E+11 0.317234E+10 0.00 78866875.75 0.161588E+09 0.00 0.371928E+11 0.00 0.98
Minimum of Months 0.768262E+09 0.00 0.00 4142744.98 0.00 0.00 0.170437E+10 0.00 0.66
Maximum of Months 0.263993E+10 0.123745E+10 0.00 10513491.87 54828682.03 0.00 0.444947E+10 0.00 1.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273198E+10 3960246.23 0.00 3906702.03 10091008.62 0.00 0.237028E+10 0.00 1.03
February 0.272157E+10 1917914.85 0.00 3576300.21 0.00 0.00 0.238314E+10 0.00 1.10
March 0.298058E+10 147932.25 0.00 4742380.47 1293212.82 0.00 0.315447E+10 0.00 1.18
April 0.270790E+10 2259837.39 0.00 7001650.86 6133853.13 0.00 0.353769E+10 0.00 1.58
May 0.201448E+10 4491010.47 0.00 6898618.43 0.00 0.00 0.368133E+10 0.00 1.46
June 0.154821E+10 86904851.00 0.00 7536850.01 0.00 0.00 0.306156E+10 0.00 1.71
July 0.160635E+10 0.756633E+09 0.00 5503243.64 43125321.93 0.00 0.166138E+10 0.00 1.90
August 0.154928E+10 0.105640E+10 0.00 4476201.31 49837722.41 0.00 0.128640E+10 0.00 2.02
September 0.155844E+10 0.218799E+09 0.00 5473570.14 11431044.20 0.00 0.204663E+10 0.00 1.49
October 0.169921E+10 0.410219E+09 0.00 4098706.19 46345581.36 0.00 0.161223E+10 0.00 1.32
November 0.260013E+10 1266567.74 0.00 4537696.19 2096234.87 0.00 0.257821E+10 0.00 1.14
December 0.300123E+10 520513.32 0.00 3841945.12 0.00 0.00 0.204174E+10 0.00 1.08
                   
Annual Sum or Average 0.267194E+11 0.254352E+10 0.00 61593864.61 0.170354E+09 0.00 0.294151E+11 0.00 1.42
Minimum of Months 0.154821E+10 147932.25 0.00 3576300.21 0.00 0.00 0.128640E+10 0.00 1.03
Maximum of Months 0.300123E+10 0.105640E+10 0.00 7536850.01 49837722.41 0.00 0.368133E+10 0.00 2.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.217991E+10 43444640.22 0.00 14013377.33 3660197.57 0.00 0.749007E+10 0.00 1.42
February 0.242866E+10 6689382.50 0.00 10399613.57 0.00 0.00 0.616733E+10 0.00 1.31
March 0.293318E+10 614093.87 0.00 10221259.21 1236232.25 0.00 0.634125E+10 0.00 1.26
April 0.276984E+10 3828005.11 0.00 11004598.71 6850225.75 0.00 0.557208E+10 0.00 1.45
May 0.263025E+10 5994788.52 0.00 7879360.12 0.00 0.00 0.414725E+10 0.00 1.15
June 0.172577E+10 0.123871E+09 0.00 8694429.52 0.00 0.00 0.373546E+10 0.00 1.32
July 0.177852E+10 0.105352E+10 0.00 6017114.83 60757125.99 0.00 0.196968E+10 0.00 1.48
August 0.149529E+10 0.160938E+10 0.00 6676942.87 71211299.93 0.00 0.194484E+10 0.00 1.77
September 0.123676E+10 0.463810E+09 0.00 10836358.89 10420408.95 0.00 0.391293E+10 0.00 1.55
October 0.130684E+10 0.982830E+09 0.00 11409558.80 27374895.86 0.00 0.362862E+10 0.00 1.51
November 0.171670E+10 7265768.87 0.00 15571043.38 867781.71 0.00 0.801371E+10 0.00 1.57
December 0.196439E+10 1290237.33 0.00 17589224.65 0.00 0.00 0.764755E+10 0.00 1.54
                   
Annual Sum or Average 0.241661E+11 0.430254E+10 0.00 0.130313E+09 0.182378E+09 0.00 0.605708E+11 0.00 1.44
Minimum of Months 0.123676E+10 614093.87 0.00 6017114.83 0.00 0.00 0.194484E+10 0.00 1.15
Maximum of Months 0.293318E+10 0.160938E+10 0.00 17589224.65 71211299.93 0.00 0.801371E+10 0.00 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.307192E+10 17888054.26 0.00 5242255.65 3814366.04 0.00 0.362275E+10 0.00 1.37
February 0.180306E+10 3461442.87 0.00 7307004.62 0.00 0.00 0.535189E+10 0.00 1.57
March 0.117304E+10 111973.53 0.00 12137421.66 1734264.03 0.00 0.813791E+10 0.00 1.84
April 0.130075E+10 7286098.25 0.00 18643708.27 3899017.73 0.00 0.851271E+10 0.00 2.56
May 0.143358E+10 5076110.70 0.00 10779172.51 0.00 0.00 0.599948E+10 0.00 1.93
June 0.811921E+09 0.123088E+09 0.00 15111479.12 0.00 0.00 0.584510E+10 0.00 2.49
July 0.129009E+10 0.128213E+10 0.00 13750047.94 41254542.31 0.00 0.333981E+10 0.00 2.84
August 0.103821E+10 0.172594E+10 0.00 13828224.89 41363536.89 0.00 0.315664E+10 0.00 3.22
September 0.773764E+09 0.307284E+09 0.00 9829622.35 10859319.28 0.00 0.399384E+10 0.00 2.00
October 0.966946E+09 0.622723E+09 0.00 8978329.01 43807510.30 0.00 0.339229E+10 0.00 1.85
November 0.103926E+10 3861806.22 0.00 11580131.66 2133443.43 0.00 0.679432E+10 0.00 1.82
December 0.117248E+10 749941.94 0.00 13024167.59 0.00 0.00 0.669823E+10 0.00 1.78
                   
Annual Sum or Average 0.158750E+11 0.409960E+10 0.00 0.140212E+09 0.148866E+09 0.00 0.648450E+11 0.00 2.11
Minimum of Months 0.773764E+09 111973.53 0.00 5242255.65 0.00 0.00 0.315664E+10 0.00 1.37
Maximum of Months 0.307192E+10 0.172594E+10 0.00 18643708.27 43807510.30 0.00 0.851271E+10 0.00 3.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.339374E+11 19440622.60 0.00 12370357.88 0.103465E+09 0.142466E+10 0.633532E+10 0.00 0.56
February 0.299999E+11 22795703.84 0.00 13705798.91 0.00 17339572.06 0.989693E+10 0.00 0.57
March 0.354370E+11 0.00 0.00 17993145.98 42008744.76 0.646055E+09 0.124698E+11 0.00 0.60
April 0.215148E+11 11027394.02 0.00 39391082.67 64918169.11 6451102.99 0.196463E+11 0.00 0.70
May 0.185392E+11 50002413.95 0.00 53693167.16 0.00 0.00 0.270734E+11 0.00 0.79
June 0.973532E+10 0.796229E+09 0.00 71434402.93 0.00 0.00 0.287223E+11 0.00 0.97
July 0.635514E+10 0.726966E+10 0.00 46418427.80 0.313003E+09 0.00 0.141865E+11 0.00 0.96
August 0.703396E+10 0.836414E+10 0.00 36173852.15 0.366052E+09 0.00 0.966423E+10 0.00 0.97
September 0.132616E+11 0.266909E+10 0.00 42440006.75 0.104046E+09 0.00 0.151086E+11 0.00 0.82
October 0.151662E+11 0.473731E+10 0.00 29959347.63 0.330848E+09 0.00 0.954292E+10 0.00 0.72
November 0.264511E+11 4469583.99 0.00 20802786.60 41494712.75 7915939.83 0.130435E+11 0.00 0.58
December 0.330035E+11 5563862.81 0.00 11578089.36 6788888.79 0.215704E+09 0.579114E+10 0.00 0.55
                   
Annual Sum or Average 0.250435E+12 0.239497E+11 0.00 0.395960E+09 0.137262E+10 0.231813E+10 0.171481E+12 0.00 0.73
Minimum of Months 0.635514E+10 0.00 0.00 11578089.36 0.00 0.00 0.579114E+10 0.00 0.55
Maximum of Months 0.354370E+11 0.836414E+10 0.00 71434402.93 0.366052E+09 0.142466E+10 0.287223E+11 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.373812E+11 31524411.59 0.00 13509074.89 0.110232E+09 0.671255E+09 0.102549E+11 0.00 0.98
February 0.333121E+11 20993169.93 0.00 17094779.14 0.00 27008861.04 0.132489E+11 0.00 1.02
March 0.381563E+11 0.00 0.00 24766599.71 49001011.05 0.364904E+09 0.180644E+11 0.00 1.09
April 0.219053E+11 23034412.57 0.00 55417334.88 69539428.61 69716479.28 0.278580E+11 0.00 1.31
May 0.230593E+11 51197266.39 0.00 53365162.95 0.00 0.00 0.275601E+11 0.00 1.33
June 0.155609E+11 0.683312E+09 0.00 64127245.47 0.00 0.00 0.247934E+11 0.00 1.54
July 0.960389E+10 0.672590E+10 0.00 51518711.20 0.300820E+09 0.00 0.145185E+11 0.00 1.62
August 0.899887E+10 0.895718E+10 0.00 43146068.54 0.336274E+09 0.00 0.113083E+11 0.00 1.70
September 0.168766E+11 0.226522E+10 0.00 43918526.08 0.120788E+09 0.00 0.154871E+11 0.00 1.37
October 0.175237E+11 0.406861E+10 0.00 28578125.06 0.437443E+09 0.00 0.106455E+11 0.00 1.17
November 0.296287E+11 2006310.02 0.00 18188432.28 51459689.35 5228150.30 0.156289E+11 0.00 1.02
December 0.371099E+11 4996310.35 0.00 11749047.90 10048531.86 0.169315E+09 0.796634E+10 0.00 0.99
                   
Annual Sum or Average 0.289117E+12 0.228340E+11 0.00 0.425379E+09 0.148561E+10 0.130743E+10 0.197335E+12 0.00 1.26
Minimum of Months 0.899887E+10 0.00 0.00 11749047.90 0.00 0.00 0.796634E+10 0.00 0.98
Maximum of Months 0.381563E+11 0.895718E+10 0.00 64127245.47 0.437443E+09 0.671255E+09 0.278580E+11 0.00 1.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.235415E+11 0.538579E+09 0.00 0.128821E+09 0.00 0.224037E+09 0.653823E+11 0.00 1.35
February 0.269592E+11 79528316.55 0.00 86342575.87 0.00 0.00 0.487604E+11 0.00 1.19
March 0.355781E+11 23555785.25 0.00 74663635.94 40454370.34 0.604092E+09 0.440944E+11 0.00 1.10
April 0.248193E+11 30142437.71 0.00 78774919.12 78535937.73 0.00 0.382697E+11 0.00 1.13
May 0.282491E+11 62158605.43 0.00 57566992.30 0.00 0.00 0.292901E+11 0.00 0.99
June 0.190380E+11 0.897418E+09 0.00 62219649.53 0.00 0.00 0.251848E+11 0.00 1.09
July 0.129461E+11 0.832686E+10 0.00 40523108.56 0.421118E+09 0.00 0.117446E+11 0.00 1.12
August 0.915555E+10 0.120305E+11 0.00 49292178.92 0.497663E+09 0.00 0.133460E+11 0.00 1.35
September 0.123208E+11 0.490235E+10 0.00 93882829.43 0.140873E+09 0.00 0.327918E+11 0.00 1.42
October 0.125238E+11 0.102475E+11 0.00 96888190.66 0.172433E+09 0.00 0.285394E+11 0.00 1.36
November 0.194008E+11 0.123016E+09 0.00 0.129743E+09 3614758.40 0.00 0.642149E+11 0.00 1.40
December 0.219087E+11 51335396.48 0.00 0.143011E+09 0.00 46602799.69 0.588497E+11 0.00 1.37
                   
Annual Sum or Average 0.246441E+12 0.373130E+11 0.00 0.104173E+10 0.135469E+10 0.874731E+09 0.460468E+12 0.00 1.24
Minimum of Months 0.915555E+10 23555785.25 0.00 40523108.56 0.00 0.00 0.117446E+11 0.00 0.99
Maximum of Months 0.355781E+11 0.120305E+11 0.00 0.143011E+09 0.497663E+09 0.604092E+09 0.653823E+11 0.00 1.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.413492E+11 85365006.50 0.00 17725789.19 70630091.14 0.674330E+09 0.110097E+11 0.00 1.09
February 0.368180E+11 25686901.83 0.00 20661751.50 0.00 0.00 0.151829E+11 0.00 1.15
March 0.425035E+11 0.00 0.00 29017977.39 52440154.00 0.261690E+09 0.209166E+11 0.00 1.24
April 0.215042E+11 15213000.65 0.00 59928476.89 75971681.85 0.00 0.335758E+11 0.00 1.46
May 0.214333E+11 43634048.42 0.00 60368786.70 0.00 0.00 0.343627E+11 0.00 1.47
June 0.120447E+11 0.720030E+09 0.00 79435190.90 0.00 0.00 0.332243E+11 0.00 1.74
July 0.717787E+10 0.823707E+10 0.00 61090775.66 0.329897E+09 0.00 0.180257E+11 0.00 1.75
August 0.658907E+10 0.927083E+10 0.00 52572226.65 0.339317E+09 0.00 0.140694E+11 0.00 1.83
September 0.127032E+11 0.259963E+10 0.00 54725777.16 0.133139E+09 0.00 0.231820E+11 0.00 1.53
October 0.177546E+11 0.449887E+10 0.00 32099454.95 0.488275E+09 0.00 0.120330E+11 0.00 1.29
November 0.334661E+11 18473228.44 0.00 27741125.90 41111283.49 0.00 0.179121E+11 0.00 1.18
December 0.387548E+11 14625703.87 0.00 19333575.58 1722169.60 54373681.88 0.109506E+11 0.00 1.10
                   
Annual Sum or Average 0.292099E+12 0.255294E+11 0.00 0.514701E+09 0.153250E+10 0.990394E+09 0.244445E+12 0.00 1.40
Minimum of Months 0.658907E+10 0.00 0.00 17725789.19 0.00 0.00 0.109506E+11 0.00 1.09
Maximum of Months 0.425035E+11 0.927083E+10 0.00 79435190.90 0.488275E+09 0.674330E+09 0.343627E+11 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.337106E+10 61770.66 0.00 382205.62 12607503.52 0.803647E+09 0.226319E+09 0.00 0.63
February 0.343510E+10 808964.47 0.00 364236.00 0.00 0.510387E+09 0.313285E+09 0.00 0.65
March 0.432772E+10 0.00 0.00 735708.19 8932.60 0.489632E+09 0.598277E+09 0.00 0.69
April 0.259760E+10 62419.70 0.00 2950132.37 3659632.87 75777290.99 0.170697E+10 0.00 0.74
May 0.234543E+10 1450980.18 0.00 4186728.05 0.00 11103434.04 0.235160E+10 0.00 0.80
June 0.135722E+10 34869206.77 0.00 6543684.40 0.00 0.00 0.273440E+10 0.00 1.00
July 0.898080E+09 0.596890E+09 0.00 4718128.51 29127692.29 0.00 0.133985E+10 0.00 1.02
August 0.831670E+09 0.713261E+09 0.00 4102765.82 34775935.19 0.00 0.921012E+09 0.00 1.04
September 0.160699E+10 0.193110E+09 0.00 3859920.74 12952730.04 0.00 0.134850E+10 0.00 0.83
October 0.166351E+10 0.373776E+09 0.00 2138399.11 56495765.99 56088139.12 0.707972E+09 0.00 0.75
November 0.325424E+10 73239.67 0.00 474059.33 3294246.08 0.336346E+09 0.484863E+09 0.00 0.64
December 0.328353E+10 0.00 0.00 255558.46 1923492.41 0.619334E+09 0.157144E+09 0.00 0.63
                   
Annual Sum or Average 0.289722E+11 0.191436E+10 0.00 30711526.61 0.154846E+09 0.290231E+10 0.128902E+11 0.00 0.78
Minimum of Months 0.831670E+09 0.00 0.00 255558.46 0.00 0.00 0.157144E+09 0.00 0.63
Maximum of Months 0.432772E+10 0.713261E+09 0.00 6543684.40 56495765.99 0.803647E+09 0.273440E+10 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.360582E+10 578195.54 0.00 608013.53 12194668.86 0.443365E+09 0.378748E+09 0.00 0.98
February 0.306659E+10 841463.78 0.00 1030465.60 0.00 0.361925E+09 0.870345E+09 0.00 1.01
March 0.396710E+10 9005.64 0.00 1520258.15 0.00 0.328907E+09 0.122438E+10 0.00 1.11
April 0.199555E+10 336616.19 0.00 5166672.12 3447734.47 35244126.91 0.278929E+10 0.00 1.29
May 0.222296E+10 1816533.71 0.00 4940561.63 0.00 2198632.72 0.267652E+10 0.00 1.30
June 0.146838E+10 31336898.78 0.00 6737105.29 0.00 0.00 0.266123E+10 0.00 1.56
July 0.824594E+09 0.567252E+09 0.00 5939364.84 17760326.88 0.00 0.161999E+10 0.00 1.68
August 0.737567E+09 0.792007E+09 0.00 5347082.09 21571573.59 0.00 0.121862E+10 0.00 1.77
September 0.150047E+10 0.176528E+09 0.00 4735013.59 12875087.50 0.00 0.162739E+10 0.00 1.34
October 0.153669E+10 0.359617E+09 0.00 2533261.21 43244731.42 23320718.71 0.904122E+09 0.00 1.14
November 0.304199E+10 73838.52 0.00 740972.11 3321181.46 0.119014E+09 0.939708E+09 0.00 1.00
December 0.349104E+10 259457.30 0.00 476738.26 1737290.83 0.326102E+09 0.271411E+09 0.00 0.98
                   
Annual Sum or Average 0.274587E+11 0.193066E+10 0.00 39775508.42 0.116153E+09 0.164008E+10 0.171817E+11 0.00 1.27
Minimum of Months 0.737567E+09 9005.64 0.00 476738.26 0.00 0.00 0.271411E+09 0.00 0.98
Maximum of Months 0.396710E+10 0.792007E+09 0.00 6737105.29 43244731.42 0.443365E+09 0.278929E+10 0.00 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.268858E+10 45103009.32 0.00 9505865.81 0.00 0.319342E+09 0.520079E+10 0.00 1.29
February 0.300539E+10 3414079.53 0.00 6470308.60 0.00 0.312219E+09 0.392666E+10 0.00 1.17
March 0.436065E+10 11631.49 0.00 5603812.96 0.00 0.437530E+09 0.351934E+10 0.00 1.13
April 0.277057E+10 118033.09 0.00 7025616.85 4765353.64 74474371.61 0.376812E+10 0.00 1.15
May 0.328932E+10 1756173.81 0.00 4720040.02 0.00 39966992.11 0.266621E+10 0.00 1.01
June 0.225715E+10 39218840.42 0.00 5835476.31 0.00 0.00 0.253044E+10 0.00 1.14
July 0.135612E+10 0.676900E+09 0.00 4572444.83 38521177.40 0.00 0.133509E+10 0.00 1.19
August 0.974601E+09 0.100092E+10 0.00 6125624.85 44562150.26 0.00 0.140811E+10 0.00 1.45
September 0.143250E+10 0.348265E+09 0.00 9621673.21 16819572.73 0.00 0.331786E+10 0.00 1.41
October 0.142357E+10 0.853228E+09 0.00 8358885.62 27897564.55 477479.32 0.252817E+10 0.00 1.37
November 0.235222E+10 6287328.40 0.00 9819706.38 1521000.08 65982560.49 0.530999E+10 0.00 1.33
December 0.262895E+10 6044058.07 0.00 10174315.60 0.00 0.189007E+09 0.448460E+10 0.00 1.30
                   
Annual Sum or Average 0.285396E+11 0.298127E+10 0.00 87833771.04 0.134087E+09 0.143900E+10 0.399954E+11 0.00 1.25
Minimum of Months 0.974601E+09 11631.49 0.00 4572444.83 0.00 0.00 0.133509E+10 0.00 1.01
Maximum of Months 0.436065E+10 0.100092E+10 0.00 10174315.60 44562150.26 0.437530E+09 0.530999E+10 0.00 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.375101E+10 4551040.91 0.00 1185903.20 10279017.98 0.609836E+09 0.865086E+09 0.00 1.17
February 0.373847E+10 1053139.57 0.00 1459915.52 0.00 0.343824E+09 0.112271E+10 0.00 1.23
March 0.462017E+10 0.00 0.00 2234440.66 10456.08 0.355328E+09 0.172594E+10 0.00 1.35
April 0.255825E+10 305127.91 0.00 5169840.78 4065966.34 45011426.99 0.316356E+10 0.00 1.51
May 0.265161E+10 1118884.16 0.00 5144042.50 0.00 7489815.57 0.313859E+10 0.00 1.51
June 0.144705E+10 29744424.92 0.00 7729125.02 0.00 0.00 0.342035E+10 0.00 1.80
July 0.804156E+09 0.679171E+09 0.00 6791244.45 32511450.81 0.00 0.190359E+10 0.00 1.84
August 0.688539E+09 0.771816E+09 0.00 6174623.26 38795331.51 0.00 0.145306E+10 0.00 1.94
September 0.153020E+10 0.184028E+09 0.00 5315604.81 20017985.03 0.00 0.218336E+10 0.00 1.56
October 0.186756E+10 0.349415E+09 0.00 2729787.59 73098245.02 1037039.66 0.102059E+10 0.00 1.33
November 0.355799E+10 739219.40 0.00 2009053.84 3244513.36 0.147821E+09 0.129984E+10 0.00 1.23
December 0.365550E+10 638607.24 0.00 1279210.50 1631690.25 0.423091E+09 0.762661E+09 0.00 1.17
                   
Annual Sum or Average 0.308705E+11 0.202258E+10 0.00 47222792.13 0.183655E+09 0.193344E+10 0.220593E+11 0.00 1.47
Minimum of Months 0.688539E+09 0.00 0.00 1185903.20 0.00 0.00 0.762661E+09 0.00 1.17
Maximum of Months 0.462017E+10 0.771816E+09 0.00 7729125.02 73098245.02 0.609836E+09 0.342035E+10 0.00 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3605843.26 0.00 0.00 0.333032E+09 0.00 0.28
February 0.00 0.00 0.00 7324633.31 0.00 0.00 0.293317E+09 0.00 0.29
March 0.00 8393.27 0.00 13156804.16 0.00 0.00 0.340829E+09 0.00 0.31
April 0.00 158512.19 0.00 16411205.53 0.00 0.00 0.202944E+09 0.00 0.29
May 0.00 0.00 0.00 3868114.56 0.00 0.00 0.247038E+09 0.00 0.29
June 0.00 7422133.04 0.00 7372454.48 0.00 0.00 0.122206E+09 0.00 0.30
July 0.00 58766526.24 0.00 4935027.45 0.00 0.00 27854700.86 0.00 0.28
August 0.00 75987865.28 0.00 5438823.55 0.00 0.00 20011839.43 0.00 0.31
September 0.00 13269212.04 0.00 2985024.77 0.00 0.00 96849752.85 0.00 0.29
October 0.00 22302941.32 0.00 6141068.14 0.00 0.00 0.149653E+09 0.00 0.28
November 0.00 0.00 0.00 11889538.24 0.00 0.00 0.278160E+09 0.00 0.28
December 0.00 0.00 0.00 16430780.36 0.00 0.00 0.313501E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.177916E+09 0.00 99559317.81 0.00 0.00 0.242540E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2985024.77 0.00 0.00 20011839.43 0.00 0.28
Maximum of Months 0.00 75987865.28 0.00 16430780.36 0.00 0.00 0.340829E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 28296948.02 0.00 0.00 0.334779E+10 0.00 0.28
February 0.00 0.00 0.00 64722180.52 0.00 0.00 0.294589E+10 0.00 0.29
March 0.00 63986.23 0.00 0.119982E+09 0.00 0.00 0.341948E+10 0.00 0.31
April 0.00 1571780.83 0.00 0.154048E+09 0.00 0.00 0.203772E+10 0.00 0.29
May 0.00 0.00 0.00 33727369.15 0.00 0.00 0.249095E+10 0.00 0.29
June 0.00 72509585.24 0.00 68620307.13 0.00 0.00 0.123287E+10 0.00 0.30
July 0.00 0.583901E+09 0.00 46798400.28 0.00 0.00 0.281993E+09 0.00 0.28
August 0.00 0.757463E+09 0.00 51827008.90 0.00 0.00 0.202571E+09 0.00 0.31
September 0.00 0.125129E+09 0.00 26730430.67 0.00 0.00 0.989968E+09 0.00 0.29
October 0.00 0.219768E+09 0.00 56138932.17 0.00 0.00 0.150324E+10 0.00 0.28
November 0.00 0.00 0.00 0.109028E+09 0.00 0.00 0.279042E+10 0.00 0.28
December 0.00 0.00 0.00 0.151332E+09 0.00 0.00 0.313879E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.176041E+10 0.00 0.911251E+09 0.00 0.00 0.243817E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 26730430.67 0.00 0.00 0.202571E+09 0.00 0.28
Maximum of Months 0.00 0.757463E+09 0.00 0.154048E+09 0.00 0.00 0.341948E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27235329.30 0.00 0.00 2095698.54 0.00 0.00 0.310547E+09 0.00 0.28
February 0.00 0.00 0.00 5856181.32 0.00 0.00 0.296059E+09 0.00 0.29
March 0.00 6120.47 0.00 11375244.31 0.00 0.00 0.343118E+09 0.00 0.31
April 0.00 155864.44 0.00 15125099.60 0.00 0.00 0.204384E+09 0.00 0.29
May 0.00 0.00 0.00 3106270.66 0.00 0.00 0.250381E+09 0.00 0.29
June 0.00 7274206.14 0.00 6758999.86 0.00 0.00 0.123693E+09 0.00 0.30
July 0.00 58318265.12 0.00 4657206.70 0.00 0.00 28332936.62 0.00 0.28
August 0.00 75584390.53 0.00 5148376.16 0.00 0.00 20417298.17 0.00 0.31
September 0.00 12316575.83 0.00 2523150.58 0.00 0.00 99795550.19 0.00 0.29
October 0.00 21897807.23 0.00 5347109.63 0.00 0.00 0.150902E+09 0.00 0.28
November 0.00 0.00 0.00 10349466.36 0.00 0.00 0.280016E+09 0.00 0.28
December 0.00 0.00 0.00 14433002.63 0.00 0.00 0.314573E+09 0.00 0.28
                   
Annual Sum or Average 27235329.30 0.175553E+09 0.00 86775806.35 0.00 0.00 0.242222E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 2095698.54 0.00 0.00 20417298.17 0.00 0.28
Maximum of Months 27235329.30 75584390.53 0.00 15125099.60 0.00 0.00 0.343118E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.209158E+09 0.00 0.00 0.743756E+10 0.00 0.32
February 0.00 0.00 0.00 0.379981E+09 0.00 0.00 0.646113E+10 0.00 0.32
March 0.00 1038470.64 0.00 0.661179E+09 0.00 0.00 0.705551E+10 0.00 0.34
April 0.00 2078785.04 0.00 0.810547E+09 0.00 0.00 0.402347E+10 0.00 0.32
May 0.00 0.00 0.00 0.209949E+09 0.00 0.00 0.503828E+10 0.00 0.33
June 0.00 0.203735E+09 0.00 0.358247E+09 0.00 0.00 0.233280E+10 0.00 0.34
July 0.00 0.137912E+10 0.00 0.231192E+09 0.00 0.00 0.448077E+09 0.00 0.32
August 0.00 0.149208E+10 0.00 0.236721E+09 0.00 0.00 0.308210E+09 0.00 0.35
September 0.00 0.414621E+09 0.00 0.146217E+09 0.00 0.00 0.176693E+10 0.00 0.33
October 0.00 0.506548E+09 0.00 0.308332E+09 0.00 0.00 0.319853E+10 0.00 0.32
November 0.00 0.00 0.00 0.597913E+09 0.00 0.00 0.623182E+10 0.00 0.32
December 0.00 0.00 0.00 0.823573E+09 0.00 0.00 0.751932E+10 0.00 0.31
                   
Annual Sum or Average 0.00 0.399922E+10 0.00 0.497301E+10 0.00 0.00 0.518216E+11 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.146217E+09 0.00 0.00 0.308210E+09 0.00 0.31
Maximum of Months 0.00 0.149208E+10 0.00 0.823573E+09 0.00 0.00 0.751932E+10 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:55

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.340850E+12 0.156118E+11 0.00 0.208921E+13 0.853922E+12
February 0.413706E+12 0.182977E+11 0.00 0.201739E+13 0.103578E+13
March 0.570339E+12 0.189918E+11 0.00 0.216197E+13 0.154748E+13
April 0.715878E+12 0.117197E+11 0.00 0.199831E+13 0.210118E+13
May 0.752778E+12 0.140600E+11 0.00 0.207921E+13 0.997888E+12
June 0.734711E+12 0.740125E+10 0.00 0.174434E+13 0.170124E+13
July 0.785469E+12 0.359775E+10 0.00 0.114089E+13 0.267174E+13
August 0.733668E+12 0.394290E+10 0.00 0.906405E+12 0.329136E+13
September 0.573784E+12 0.615560E+10 0.00 0.155767E+13 0.146802E+13
October 0.411046E+12 0.980989E+10 0.00 0.148350E+13 0.202769E+13
November 0.370982E+12 0.154155E+11 0.00 0.217098E+13 0.163058E+13
December 0.311031E+12 0.170313E+11 0.00 0.219548E+13 0.208763E+13
           
Annual Sum or Average 0.671424E+13 0.142035E+12 0.00 0.215454E+14 0.214145E+14
Minimum of Months 0.311031E+12 0.359775E+10 0.00 0.906405E+12 0.853922E+12
Maximum of Months 0.785469E+12 0.189918E+11 0.00 0.219548E+13 0.329136E+13